Carrier 260L, 1300L User Manual

OWNER’S MANUAL
MIRACOOL™ GLASS DOOR MERCHANDISER
260L - 1300L
300L 750L
a79-13
1300L
Sales Office: P.O. Box 5932
Spartanburg, S.C. 29304-5932
Technical Service: 1-800-558-7627
Parts Order Fax: 1-800-262-9381
Printed in Mexico 6-06 79BC560002-01_C
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
CONTENTS
Page
GENERAL. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
UNIT INSPECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-5
LOCATE UNIT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
LEVEL UNIT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
INSTALL SHELVES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
CONDENSATE DISPOSAL. . . . . . . . . . . . . . . . . . . . . . . . . . 5
START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6,7
PRELIMINARY CHECKS . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
INITIAL START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
REFRIGERATION SYSTEM SERVICE . . . . . . . . . . . . 8-13
COMPONENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
SERVICE AND TROUBLESHOOTING . . . . . . . . . . . . . . . 8
MAINTENANCE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14,15
LAMP REPLACEMENT . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
CONDENSATE REMOVAL . . . . . . . . . . . . . . . . . . . . . . . . 14
CONDENSER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
CABINET EXTERIOR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
INTERIOR SURFACE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
GENERAL
These instructions cover the installation, operation, and maintenance of Carrier Miracool™ series glass door merchandiser units, sizes 260L, 300L, 750L, 1100L, and 1300L.
UNIT INSPECTION
Examine all packages for damage to packaging mate­rial. Damage to external packaging may have resulted in unit damage. Check packages for all accessories and components, including legs, casters, and shelves. File a claim immediately with the shipping company if shipment is damaged or incomplete.
INSTALLATION
LOCATE UNIT
Refer to Figure 1 for unit components. Units are designed for indoor placement only. Provide at least 3 in. of space between unit cabinet and any adjacent wall or fixture. Remove skid base by removing the retaining screws (4 hex head bolt screws). If optional casters will be used, unit must be located on flat, level surface. Refer to Table 1 for a list of standard parts.
TABLE 1 — STANDARD PARTS
PART
Refrigeration Cartridge X111
Shelves X4510
Shelf Clips X162040
Instruction Manual ——111
Leveling Feet X444
Lamps X122
NOTE: Parts shown are for standard units. Quantity of shelves and clips may vary based on factory-supplied options.
FAC TOR Y
INSTALLED
FIELD
INSTALLED
260L, 300L 750L 1100L, 1300L
UNIT SIZE
Quantity
2
FLUORESCENT LAMP SIGNBOARD (SIZES 750L, 1100L, AND 1300L ONLY)
UNIT DATA LABEL (INSIDE COOLER IN UPPER LEFT CORNER)
SHELF
PRODUCT CHAMBER
INTERNAL FLUORESCENT LAMP — SIZE 750L (SIZE 260L, 300L — ALONG TOP; SIZE 1100L, 1300L — IN CENTER)
FRONT GRILLE
CARTRIDGE COMPARTMENT
SERVICE CORD
LEVELING FOOT
FRONT VIEW
GRILLE RETAINING SCREW
WOOD SKID RETAINING SCREW, IF USED (HEX HEAD BOLT SCREW)
WOOD SKID
REAR VIEW
LIGHTING CORD (RIGHT CONNECTOR)
POWER CORD (LEFT CONNECTOR)
UNIT WITH FRONT GRILLE REMOVED
FIGURE 1 — MIRACOOL™ BOTTLE COOLER UNIT COMPONENTS (Size 750L Shown)
a79-1
3
LEVEL UNIT
To provide adequate condensate drainage and proper door alignment and operation of unit, the unit cabinet must be level. Leveling feet are factory installed. Remove refrigeration system cartridge for easier access to back feet.
Before servicing unit, disconnect electrical service. On sizes 1100L and 1300L, turn disconnect switch (located on power cord) to the OFF position. Failure to disconnect electrical service could result in elec­trical shock and cause personal injury or death.
UNPLUG CARTRIDGE POWER AND LIGHTING CORDS
a79-2
TO REMOVE CARTRIDGE
1. After disconnecting the unit from the power supply, remove the grille retaining screw located in the upper-most part of the grille. (See Figure 1.)
2. Lift the grille up and away from the unit.
3. Unplug the power supply and lighting supply cords located in the front of the cartridge (Figure 2).
4. Using a pair of wire cutters, cut wire tie that secures lifting rods at center of front base rail. (See Figure 2.)
5. Take hold of the end of each lifting rod and rotate each approximately 90-degrees upward so that they are nominally vertical (Figure 3.) The car­tridge should be disengaged from the cabinet and resting on the base of the cabinet assembly. Han­dling holes are located on either side of the car­tridge near the top and along the side of the cartridge (Figure 4). Grasp the cartridge by these holes and slide the unit forward from the cabinet until the cartridge is free. Use caution to ensure that power and electrical cords do not get pinched between the cartridge and cabinet while removing cartridge.
TO LEVEL UNIT — The door is equipped with gravity assisted cams and will not function properly without proper leveling of cabinet. Adjust feet using adjustable wrench so that unit sits approximately level to floor and door closes properly. For best door operation, adjust leveling feet so that cabinet has
1
a
/16-in. rake or slant from front to back. Optional
casters are available to replace leveling feet.
NOTE: If casters are not used, local codes may require cabinet to be sealed around the perimeter of the cabi­net base. Consult local sanitation codes. Use only seal­ant material approved for this use, such as Dow Corning #732.
CUT WIRE TIE THAT SECURES LIFTING RODS TO BASE
FIGURE 2 — PREPARE CARTRIDGE FOR REMOVAL
CARTRIDGE POWER AND LIGHTING CORDS
a79-3
FIGURE 3 — ROTATE LIFTING WIRES IN
DIRECTION SHOWN
PULL THE CARTRIDGE USING THE HANDLING HOLES ON SIDES
a79-4
FIGURE 4 — REMOVE CARTRIDGE
4
INSTALL SHELVES
Product shelves and a bag containing shelf support clips are packed inside the unit. Refer to Table 1 to verify quantity of shelves and shelf supporting clips. Bottom shelf must be placed on interior floor and should be inserted into the two retainer clips provided at the rear corners of the unit floor.
Improper shelf clip installation may cause shelf and/ or product to fall which could result in personal injury or damage to the unit.
Do not overload the shelves. The unit is designed to use all the shelves provided, installed in equally spaced configuration. Failure to install shelves cor­rectly could result in personal injury or damage to the unit. If fewer shelves or a different installation configuration is desired, contact the manufacturer to ensure that shelf overloading will not occur.
TO INSTALL SHELVES — Refer to Figures 5 and 6.
1. Determine proper location for shelf clips. Refer to the numbers on the pilaster to ensure that all clips are properly located.
2. Insert top tab of the shelf clip into the desired hole of the pilaster. The retaining tab should be facing upward as shown in Figure 5.
3. Rotate the clip downward and insert the bottom tab into the appropriate hole on the pilaster. If necessary, squeeze the clip slightly during installation.
4. Install all remaining clips as described above.
5. Install shelves onto clips so that the product retention bar is facing upward. Be careful not to dislodge clips during shelf installation.
6. Shelves must be placed so that the retaining tab on the shelf clip captures the shelf as shown in Figure 6.
7. Before loading the shelf, ensure that the shelf is resting on each of 4 clips and that the clips are installed as shown in Figures 5 and 6.
CONDENSATE DISPOSAL
The evaporator drain pan is located in the base of the cartridge. Airflow in cartridge compartment hastens condensate evaporation so that external drain plumb­ing is not required.
TOP TAB FULLY INSERTED INTO SLOT
BOTTOM TAB FULLY SEATED
PROPERLY INSTALLED CLIP
RETAINING TAB
SHELF CLIP
a79-5
IMPROPERLY INSTALLED CLIP (UPSIDE DOWN)
BOTTOM TAB
FIGURE 5 — SHELF CLIP INSTALLATION
PILASTER
SHELF RETAINED BY TAB
a79-6
PRODUCT RETENTION BAR
FIGURE 6 — PROPER INSTALLATION OF
SHELF ON CLIP
TOP TAB
5
START-UP
PRELIMINARY CHECKS
BI-PIN FLUORESCENT LAMP INSTALLATION/ VERIFICATION — Before applying power to the unit,
verify that all lamps have been properly installed and are fully engaged in the lamp holders. Sizes 750L, 1100L, and 1300L have 2 lamps, one in the signboard and one inside the cooler. Sizes 260L and 300L have one lamp inside the cooler.
Improperly installed lamps may cause damage to the lighting circuit. Carrier will not be responsible for equipment or component failures or other dam­ages or losses that arise as a result of improper lamp installation.
To achieve proper lamp engagement, rotate the lamp 90 degrees from its insertion position until it snaps or clicks into place.
On units without safety shields, visually verify proper lamp installation by checking the identification mark on the end of the bulb. If the bulb has been properly installed, the mark will be centered between the “halves” of the lamp holder. Refer to Figure 7.
On units with safety shields, the identification mark cannot be seen. (See Figure 8.) Verify manually that the lamp has been rotated and locked into place.
BI-PIN LAMP END IDENTIFICATION MARK
Properly installed lamp without shield. Verify identification mark is positioned as shown.
a79-7
FIGURE 7 — CHECK INSTALLATION OF LAMP WITHOUT SAFETY SHIELD
PINS MAY NOT BE VISIBLE IN ACTUAL INSTALLATION
Properly installed lamp with shield. Requires manual verification that lamp has been rotated and locked into place.
Improperly installed lamp with shield. Note that pins have not achieved full 90° rotation.
a79-8
FIGURE 8 — CHECK INSTALLATION OF LAMP WITH SHIELD
6
ELECTRICAL SUPPLY AND CONNECTIONS
Check to be sure that the electrical service to the unit meets all local and national electrical codes. Unit elec­trical data is shown in the unit data label, located on the inside of the cabinet in the upper lefthand corner. Review this label before initiating electrical service. Voltage range of power supply to unit should be 105 to 125 volts. Refer to Table 2 for unit data.
NOTE: Other motors or heavy appliances should not be used on the same circuit with the cooler.
See Figure 1 for location of service cord.
Before servicing unit, disconnect electrical service. On sizes 1100L and 1300L, turn disconnect switch (located on power cord) to the OFF position. Failure to disconnect electrical service could result in elec­trical shock and cause personal injury or death.
If an extension cord is necessary, use only three­wire grounding type. The use of ungrounded cords or overloaded circuit voids compressor warranty.
TABLE 2 — UNIT DATA
UNIT
Vol ta ge
Nominal 115 115 115
Range 105-125 105-125 105-125 Frequency 60 60 60 Tot a l A m p s 4.6 8.9 10.6 Refrigerant Type R-134A R-134A R-134A
Charge Amount (oz) 4.3 7.5 14.5 Design Pressure
High Side (psig) 220 265 222
Low Side (psig) 88 93 88
MC260,
MC300
MC750
MC1100,
MC1300
INITIAL START-UP
POWER SUPPLY — Connect unit to power supply. On sizes 1100L and 1300L, turn disconnect switch to the ON position. Check to verify that the compressor, lamp, and fans are running.
IMPORTANT: Low line voltage is often the cause of service complaints. Check to see that the line volt­age is within specified range with the unit running.
TEMPERATURE CONTROL — The temperature control knob is located in the front power panel. See Figure 9. Unit is factory set at the number 4 position (normal), which will maintain the product at approxi­mately 38 F. For colder temperature, turn the black adjustment knob to a higher setting. Adjust tempera­ture control in small increments, one position at a time.
Allow 24 hours between temperature control adjust­ments. Excessive tampering with temperature con­trol could lead to service difficulties.
NOTE: For operation above 3,000-ft altitude, ther­mostat should be adjusted by a qualified service technician.
a79-9
FIGURE 9 — TEMPERATURE CONTROL KNOB
7
TEMPERATURE CONTROL KNOB
REFRIGERATION SYSTEM SERVICE
COMPONENTS
The Carrier Miracool™ refrigeration system consists of a hermetically sealed compressor and finned evapo­rator and condenser coils.
CONDENSER — The condenser has wide finned spaces, which allow more air passage with less dirt or dust accumulation. The condenser still requires peri­odic cleaning for maximum efficiency.
CONDENSER FAN MOTOR — The condenser fan motor assembly is mounted between the condenser and the compressor. Air is drawn through the con­denser, over the body of the compressor and out the rear of the unit compartment.
The motor is wired to cycle with the compressor but will continue to operate should the compressor cut out on the overload. (The motor is permanently lubricated; therefore, oiling is not required.)
DRIER — The drier is installed in the system just before the capillary tube. The drier traps minute parti­cles of foreign material and absorbs any moisture in the system.
LIQUID CONTROL AND HEAT EXCHANGER — Liquid refrigerant control to the evaporator of the system is accomplished by the use of a capillary tube. This capillary tube is soldered to the suction line to form a heat exchanger, which subcools the liquid refrigerant to maintain high efficiency within the system.
SERVICE AND TROUBLESHOOTING
CARTRIDGE REMOVAL
Before servicing unit, disconnect electrical service. On sizes 1100L and 1300L, turn disconnect switch (located on power cord) to the OFF position. Failure to disconnect electrical service could result in elec­trical shock and cause personal injury or death.
1. After disconnecting the unit from the power supply, remove the grille retaining screw located in the upper-most part of the grille. (See Figure 1.)
2. Lift the grille up and away from the unit.
3. Unplug the power supply and lighting supply cords located in the front of the cartridge (Figure 2).
4. Using a pair of wire cutters, cut wire tie that secures lifting rods at center of front base rail. (See Figure 2.)
5. Take hold of the end of each lifting rod and rotate each approximately 90-degrees upward so that they are nominally vertical (Figure 3). The car­tridge should be disengaged from the cabinet and resting on the base of the cabinet assembly. Han­dling holes are located on either side of the car­tridge near the top and along the side of the cartridge (Figure 4). Grasp the cartridge by these holes and slide the unit forward from the cabinet until it is free. Use caution to ensure that power and electrical cords do not get pinched between the cartridge and cabinet while removing cartridge.
Before servicing unit, disconnect electrical service. On sizes 1100L and 1300L, turn disconnect switch (located on power cord) to the OFF position. Failure to disconnect electrical service could result in elec­trical shock and cause personal injury or death.
8
EVAPORATOR COMPARTMENT (Interior top area) — All serviceable parts are directly accessible from the top of the cartridge compartment.
COMPRESSOR COMPARTMENT (Bottom rear area) — Access to compressor compartment requires removal of the side panel of the cartridge. Condenser fan access also requires removal of a side panel. Side panels are secured with 5 Phillips screws. After tubing and electrical connections are removed, compressor replacement requires removal of four clips securing compressor to the base.
Before servicing unit, disconnect electrical service. On sizes 1100L and 1300L, turn disconnect switch (located on power cord) to the OFF position. Failure to disconnect electrical service could result in elec­trical shock and cause personal injury or death.
EVACUATION — Moisture in a refrigeration system may affect performance.
When large amounts of moisture are present, system freeze ups will occur. Even in minute amounts, mois­ture will combine with refrigerants to form an acid. The corrosive action of this acid forms sludge, which will plug the lines and drier.
Since most field type vacuum pumps cannot pull a low enough vacuum to remove all moisture from the sys­tem, it is recommended that the system be triple evac­uated, breaking each time with dry refrigerant nitrogen. Use care to purge air from the charging hose when breaking the vacuum.
CHARGING REFRIGERATION SYSTEM — Refer to Table 2 for refrigerant type and amount of charge. Since capillary tube systems have small critical refrig­erant charges, it is recommended that a field charge either be weighed in or transferred from a portable charging cylinder. After maximum vacuum has been obtained as detailed above, attach charging cylinder to the system line making sure to purge air from hose with refrigerant. With the unit running, allow refrig­erant to run slowly into the system until the desired charge is reached. When using refrigerant blends it is recommended to charge into the high side of the sys­tem with the initial charge and then add any remain­ing charge into the suction side; however, care must be taken to meter the remaining amount into the low side so that excess liquid does not enter the compressor.
TROUBLESHOOTING — Refer to Table 3 and Figures 10-12.
9
TABLE 3 — REFRIGERATION SYSTEM SERVICE AND ANALYSIS CHART
(Refer to Figures 10-12 for wiring diagrams)
MALFUNCTION POSSIBLE CAUSE SOLUTION
Compressor Will Not Start — No Hum.
Compressor Will Not Start — Hums but Trips on Overload Protector.
Compressor Starts but Does Not Switch Off of Start Winding.
Compressor Starts and Runs, but Short Cycles on Overload Protector.
Unit Runs, but Short Cycles. 1. Overload protector. 1. Check wiring diagram for correct wiring.
Unit Operates Long or Continuously.
Start Capacitor Open, Shorted or Blown.
Run Capacitor Open, Shorted or Blown.
Relay Defective or Burned Out. 1. Incorrect relay. 1. Check and replace.
Space Temperature Too High. 1. Control setting too high. 1. Reset control.
Cooler Freezing Beverage. 1. Temperature control knob set too high. 1. Reset control. Unit Noisy. 1. Loose parts or mountings. 1. Find and tighten.
NOTE: All servicing must comply with state and federal regulations.
1. Line cord not plugged in. 1. Plug in the cord.
2. Power disconnect switch in OFF position. (Sizes 1100L and 1300L only.)
3. Fuse removed or blown. 3. Replace fuse.
4. Overload protector tripped. 4. Refer to electrical section.
5. Temperature control stuck in open position.
6. Wiring improper or loose. 6. Check wiring against diagram.
1. Low voltage to unit. 1. Determine reason and correct.
2. Relay failing to close. 2. Determine reason and correct, replace if
3. Starting capacitor defective. 3. Determine reason and replace.
4. Improperly wired. 4. Check wiring against diagram.
1. Low voltage to unit. 1. Determine reason and correct.
2. Relay failing to open. 2. Determine reason and correct; replace if
3. Run capacitor defective. 3. Determine reason and replace.
4. Compressor motor winding is open or shorted.
1. Additional current passing through over­load protector.
2. Low voltage to unit. 2. Determine reason and correct.
3. Overload protector defective. 3. Check current, replace protector.
4. Run capacitor defective. 4. Determine reason and replace.
5. Excessive discharge pressure. 5. Check ventilation, restrictions in cooling
6. Compressor too hot — return gas hot. 6. Check refrigerant charge; fix leak if neces-
2. Cold control. 2. Differential set too close.
3. Overcharge. 3. Reduce refrigerant charge.
4. Air in system. 4. Recover and recharge.
5. Undercharge. 5. Fix leak and recharge with refrigerant.
1. Dirty condenser. 1. Clean condenser.
2. Shortage of refrigerant. 2. Fix leak, add charge, correct charge.
3. Temp control contacts stuck or frozen. 3. Replace Temp control.
4. Evaporator coil iced. 4. Defrost.
5. Restriction in refrigeration system. 5. Determine location and remove.
1. Relay contacts not opening properly. 1. Replace relay.
2. Low voltage to unit. 2. Determine reason and correct.
3. Improper relay. 3. Replace.
1. Improper capacitor. 1. Determine correct size and replace.
2. Excessively high line voltage (110% of rated max).
2. Line voltage too high or too low. 2. Determine reason and replace.
3. Relay being influenced by loose vibrating mounting.
2. Overcharged with refrigerant. 2. Recover refrigerant and recharge with
3. Inadequate air circulation. 3. Improve air movement.
2. Tubing rattle. 2. Reform to be free of contact.
3. Bent fan blade causing vibration. 3. Replace blade.
4. Fan motor bearings worn. 4. Replace motor.
2. Turn disconnect switch to ON position.
5. Repair or replace temperature control.
necessary.
necessary.
4. Determine cause, correct, and replace compressor.
1. Check wiring diagram. Check for added fan motors, pumps, etc. connected to wrong side of protector.
medium, restrictions in refrigeration system.
sary. Check airflow across condenser.
2. Determine reason and correct.
3. Remount rigidly.
proper charge specified on dataplate.
10
a79-10
FIGURE 10 — WIRING DIAGRAM, SIZES 260L, 300L
11
a79-12
FIGURE 11 — WIRING DIAGRAM, SIZE 750L
12
a79-11
FIGURE 12 — WIRING DIAGRAM, SIZES 1100L, 1300L
13
MAINTENANCE
LAMP REPLACEMENT
Before proceeding with replacement, disconnect electrical service. Failure to unplug unit could result in serious personal injury or death.
Remove lamp by rotating lamp 90 degrees to align lamp pins with holder slots. Refer to Bi-Pin Fluores­cent lamp Installation/Verification section on page 6.
CONDENSATE REMOVAL
The evaporator drain pan is located in the base of the cartridge. In general, the condensate disposal system is maintenance free.
CONDENSER
The condenser should be inspected periodically for accumulation of debris, which should be removed. A vacuum cleaner or brush can be used to remove debris.
CABINET EXTERIOR
Cabinets should be cleaned with a solution of mild soap and water or mild household cleaner. Do not use caustic soap or abrasive cleaners, since these might damage the cabinet finish. If stainless steel surface becomes discolored, scrub by rubbing only in direction of the finish grain. Do not use steel wool or rusting may occur. Refer to Table 4.
INTERIOR SURFACE
The inside of the cabinet is coated with baked-on epoxy. To clean, use a mild soap and water solution or mild household cleaner.
14
TABLE 4 — METHODS FOR CLEANING STAINLESS STEEL
TASK CLEANING AGENT*
Routine Cleaning Soap, ammonia or detergent and
Stubborn Spots and Stains, Caked-on Splatter, and other Light Discolorations
Heat Tint or Heavy Discoloration Revere Ware or Goddard’s stain-
Caked-on Foods and Grease, Fatty Acids Milkstone (where swabbing or rubbing is not practical)
Hard Water Spots and Scale Vinegar Swab or wipe with cloth. Rinse with
*Use of brand names is intended only to indicate a type of cleaner and
does not constitute an endorsement; nor does the omission of any brand name cleaner imply its inadequacy. Many products named are regional in distribution and can be found in local supermarkets, depart­ment and hardware stores.
†All products should be used in strict accordance with instructions on
package.
water Revere Ware, Goddard’s, Twinkle,
or Cameo stainless steel cleaner or Soft Scrub cleaner
Household cleansers, such as Old Dutch, Bon Ami, Ajax, Comet
less steel cleaner
Easy-Off oven cleaner Apply generous coating. Allow to
Sponge with cloth, then rinse with clear water and wipe dry.
Apply with damp sponge or cloth. Rub with damp cloth.
Rub with a damp cloth. May contain chlorine bleaches. Rinse thoroughly after use.
Apply with damp sponge or cloth. Use in direction of polish lines.
stand for 10 to 15 minutes. Rinse. Repeated application may be necessary.
water and dry.
NOTES:
1. Use the mildest cleaning procedure that will do the job efficiently and
2. Always rub in the direction of polish lines for maximum effectiveness
3. Use only a soft cloth, sponge, fiberous brushes, plastic or stainless
4. Rinse thoroughly with fresh water after every cleaning operation.
5. Always wipe dry to avoid water marks.
6. Never use common steel wool pads; these will cause rust!
METHOD OF
APPLICATION†
effectively.
and to avoid marring the surface.
steel pads for cleaning and scouring.
EFFECT ON FINISH
Satisfactory for use on all finishes.
Satisfactory for use on all finishes if
rubbing is light. Use in direction of polish lines.
Use in direction of polish lines. May scratch or dull highly polished finishes.
May scratch or dull highly polished finishes.
Excellent removal. Satisfactory for use on all finishes.
Satisfactory for use on all finishes.
15
Copyright 2006 Carrier Corporation
Printed in Mexico 6-06 79BC560002-01_C
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Loading...