Carrier KFCEH2401C05, KFCEH0501N05, KFCEH0901N10, KFCEH2601C10, KFCEH3001F15 Installation Instructions Manual

...
Installation Instructions
Electric Heater Packages
NOTE: Read the entire instruction manual before starting the installation. This symbol indicates a change since the last issue.
SINGLE-CIRCUIT
GROUND LUG
TERMINAL
BLOCK
MULTI-CIRCUIT
GROUND LUG
KFCEH
(MUST BE REMOVED WHEN
INSTALLING LARGE HEATER)
FUSE BLOCK (24- AND 30-KW)
FUSE COVER
CLIP LATCH
Fig. 1—Installation of 18-, 24-, and 30-kw Model Heaters
Installing and servicing heating and air conditioning equipment can be hazardous due to system pressures and electrical components. Only trained personnel should install or service heating and air conditioning equipment. Untrained personnel can perform basic maintenance functions such as cleaning coils, or cleaning and replacing filters. All other operations should be performed bytrained service personnel. When working on heating and air conditioning equipment, observe precautions in the literature, on tags, and on labels attached to the unit. Follow all safety codes. Wear safety glasses and work gloves. Have a fire extinguisher available. Recognize safety information. This is the safety-alert symbol When you see this symbol on the unit and in instructions or manuals, be alert to the potential for personal injury. Understand the signal words DANGER, WARNING, CAUTION, and NOTE. These words are used with the safety-alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices which would result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
WARNING: Before beginning any installation or modification, be sure the main electrical disconnect switch is in the
OFF position. Tag the disconnect switch with a suitable warning label. Electrical shock can cause personal injury or death.
SAFETY CONSIDERATIONS
.
(OMITTED ON 18-KW)
ADAPTER PLATE
A90154
Form: AG-FCEH-09 Cancels: AG-FCEH-08 Printed in U.S.A. 4-03 Catalog No. 63FC-EH7
INTRODUCTION
Table 1Accessory Heater Usage
ELECTRIC HEATER
PART NO.
KFCEH0401N03 3 Non-fused 018, 024 024 001 NO KFCEH0501N05
KFCEH2401C05 KFCEH0801N08
KFCEH2501C08 KFCEH2901N09 9* Non-fused 036-071 036-070 002-004 036-060 003-006 YES† KFCEH0901N10
KFCEH2601C10 KFCEH3001F15
KFCEH2701C15 KFCEH3101C15
KFCEH3201F20 KFCEH2801C20 KFCEH3301C20
KFCEH1601315 15 Non-fused 036-071 036-070 002-004 036-060 001-006 NO KFCEH2001318 18 Non-fused 042-071 042-070 003, 004 042-060 003-006 NO
KFCEH3401F24 KFCEH3501F302430
† These heaters are Intelligent Heat capable when used with the FK4, FV4, and 40FK fan coils and corporate 2-speed programmable thermostat (TSTATXXP2S01-B), Thermidistat™ Control (TSTATXXPRH01-B), or capable zoning system. ‡ Field convertible to 1 phase, single or multiple supply circuit. * Field convertible to 3 phase.
KW
PROTECTION
5
Circuit Breaker
8
Circuit Breaker
10
Circuit Breaker
15
Circuit Breaker Circuit Breaker
20
Circuit Breaker Circuit Breaker
INTERNAL
Non-fused
Non-fused
Non-fused
Fused
Fused
Fused Fused
MODEL FA, FB, PF
SIZE
018-071 024-070 001-004 030-060 001-006
018-071 024-070 001-004 030-060 001-006
018-071 024-070 001-004 030-060 001-006
024-071 024-070 001-004 030-060 001-006
030-071 030-070 002-004 030-060 001-006
048-071 048-070 003, 004 048-060 005, 006
MODEL FC
SIZE 1 Phase
3 Phase Only
3 Phase, Factory Shipped‡
MODEL FH
SIZE
MODEL FX
SIZE
MODEL
FE4, FK4, FV4, 40FK
SIZE
FK, FV, 40FK
INTELLIGENT
HEAT CAPABLE
NO NO
NO NO
NO NO
YES† YES† YES†
YES† YES† YES†
YES† YES†
Table 2Minimum CFM and Motor Speed Selection
FAN COIL
SIZES
FA, FB, FC, FH, FX,
PF 018 525 525 525 600* 024 700 700 700 700 700 775*
030, 033 875 875 875 875 875 1060*
036, 038, 1050 970 970 970 920 1040
042 1225 1225 1225 1225 1225 1225 1225
048, 054, 1400 1400 1400 1400 1400 1400 1400 1400 1400 060, 070, 1750 1750 1750 1750 1750 1750 1750 1750 1750
* Indicates medium speed (blue). All other motor speeds at low tap.
3 5 8 9 10 15 18 20 24 30
HEATER KW
This instruction describes the installation of Part No. KFCEH accessory heaters in FA, FB, FC, FH, FX, and PF1MNB018-070 fan coils and in the FE4, FK4, FV4, 40FK, and PF1MNA071 fan coils.
NOTE: Electric heaters require a minimum airflow. Minimum airflow and motor speed selection are listed in Table 2. For 3- through 18-kw standard heaters there are no clearance requirements for the first 36 in. of ductwork. For 20- through 30-kw heaters, a 1-in. clearance is required for the first 36 in. of ductwork.
INSTALLATION
PROCEDURE 1INSTALL ELECTRIC HEATER ASSEMBLY NOTE: Ensure heater coils are not deformed or damaged during heater installation.
1. Make sure power to unit is off.
2. Remove blower access panel of fan coil unit.
CAUTION:
Before installation of heater, the black and yellow pigtail leads must be removed from the fan coil PCB or wire harness to prevent possible damage to the product. Electrical power will be provided to the board through the heater circuit plug.
3. Disconnect 2 power wires (black and yellow pigtail leads) from PCB or wire harness (if applicable) and discard. Wires may be part of a plug assembly or attached to terminals L1 and L2. Remove cooling control plate from fan coil (if equipped). For 18-, 24-, and 30-kw heaters, remove adapter plate. (See Fig. 1.)
4. Insert heater assembly into front of fan coil so that element rods engage holes in rear heat shield.
5. Attach heater control plate to fan coil using 2 screws provided. For 18-, 24-, and 30-kw heater models, attach front of heater to fan deck using third screw. (See Fig. 1.)
—2—
PROCEDURE 2ATTACH FUSE BOX OR CIRCUIT BREAKER BOX
1. For 15- and 20-kw fused models:
After installing heater assembly, attach fuse assembly to side of fan coil unit by inserting fuse box tab between insulation and to left side of unit and fan deck. Mount front of assembly to side flange with 2 screws provided. On fan coil units size 042 and larger, remove wire tie that shortens wire length between heater and fuses. Fuse cover is closed by engaging dimples in fuse box. (See Fig. 2.)
INSERT FUSE
BOX TAB HERE
SINGLE-CIRCUIT
GROUND LUG
FUSE BOX TAB
DIMPLE
FUSE BOX
DUAL-CIRCUIT
GROUND LUG
COVER PLATE OR KNOCKOUT
HEATER/CUTOUT COVER
WIRE TIE
FUSE COVER
(REMOVE ON LARGE FAN COILS)
Fig. 2Installation of Fused Model Heater
2. For 24- and 30-kw fused models:
Fuse assembly is mounted on heater. Be sure fuse cover is closed by engaging clip latch on unit top panel. (See Fig. 1.)
WARNING:
Ensure fuse box is closed before power is turned to ON position. Electrical shock may cause personal
injury or death.
3. For 5- through 20-kw circuit breaker models:
After installing heater assembly, attach circuit breaker assembly to unit with screws provided. (See Fig. 3.) On fan coil units size 042 and larger, remove wire tie that shortens wire length between heater and circuit breaker assembly to allow mounting of circuit breaker assembly. (See Fig. 3.)
4. Circuit breaker models require installing a window bezel in unit door to provide safe access to circuit breakers. The Window Bezel mounts
on the outside of the blower door. (See Fig. 4.)
a. Cut insulation away from rectangular access hole in blower access panel. b. Remove adhesive backing from window bezel and from the outside. Insert the window through the rectangular hole and seat firmly on
the door surface. Press firmly in place to seat the adhesive. (See Fig. 4.)
PROCEDURE 3ELECTRICAL CONNECTIONS
Refer to unit instructions for recommended wiring procedures. Install wiring in accordance with all applicable local and national codes. (See Tables 3, 4, and 5.)
Connect heater wiring harness plug to receptacle on PCB or wire harness. A positive connection must be made between plug and receptacle. Plug will interlock with receptacle when properly seated. Harness contains both 24-v control and high-voltage wiring. Blower power is provided through heater harness.
NOTE: Units with or without electric heaters require a minimum CFM. Refer to unit wiring label to ensure the fan speed selected with electric heaters is equal to or greater than the minimum fan speed indicated. The minimum CFM for cooling is determined by the outdoor unit requirements. Use the higher of the 2 for year-round operation.
A90151
3
208/230v (Ft)‡‡
Max Wire Length
Dual Circuit
Single
Circuit
208/230v (Ft)‡‡
Max Wire Length
Dual Circuit
Single
Circuit
208/230V (FT)‡‡
MAX WIRE LENGTH
208/230v
Max Fuse/Ckt Bkr Amps
BRANCH CIRCUIT
208/230v
Min Gnd Wire Size
208/230v††
Min Wire Size (AWG)
208/230V**
MIN AMPACITY
Dual Circuit
Single
Circuit
Dual Circuit
Single
Circuit
Dual Circuit
Single
Circuit
Dual Circuit
Single
Circuit
208/230v
Max Fuse/Ckt Bkr Amps
BRANCH CIRCUIT
208/230v
Min Gnd Wire Size
208/230v††
Min Wire Size (AWG)
208/230V**
MIN AMPACITY
Dual Circuit
Single
Circuit
Dual Circuit
Single
Circuit
Dual Circuit
Single
Circuit
Dual Circuit
Single
Circuit
208/230V
MAX FUSE/CKT BKR AMPS
208/230V
MIN GND
WIRE SIZE
208/230V††
MIN WIRE SIZE (AWG)
208/230V**
MIN AMPACITY
Table 3Electric Heater Electrical Data
208/230V
HEATER AMPS
CIRCUIT
INTERNAL
PHASE
KW
HEATER PART NO.
Dual Circuit
Single
Circuit
PROTECTION
240v 208v L1,L2 L3,L4 L1,L2 L3,L4 L1,L2 L3,L4 L1,L2 L3,L4 L1,L2 L3,L4 L1,L2 L3,L4
1
KFCEH0401N03 3 2.3 1 None 10.9/12.0 ——15.9/17.3 ——12/12 ——12/12 ——20/20 ——67/68 ——
5 3.8 1 None 18.1/20.0 ——26.0/28.4 ——10/10 ——10/10 ——30/30 ——66/66 ——
5 3.8 1 None 18.1/20.0 ——31.2/33.5 ——8/8 ——10/10 ——35/35 ——85/88 ——
5 3.8 1 Ckt Bkr 18.1/20.0 ——31.2/33.5 ——8/8 ——10/10 ——35/35 ——85/88 ——
2
2
KFCEH2501C08 8 6.0 1 Ckt Bkr 28.9/32.0 ——44.7/48.5 ——8/8 ——10/10 ——45/50 ——59/60 ——
KFCEH2401N08 8 6.0 1 None 28.9/32.0 ——44.7/48.5 ——8/8 ——10/10 ——45/50 ——59/60 ——
KFCEH0501N05
KFCEH2401C05
KFCEH0501N05
KFCEH0901N10 10 7.5 1 None 36.2/40.0 ——53.8/58.5 ——6/6 ——10/10 ——60/60 ——78/80 ——
KFCEH2601C10 10 7.5 1 Ckt Bkr 36.2/40.0 ——53.8/58.5 ——6/6 ——10/10 ——60/60 ——78/80 ——
KFCEH2901N09 9 6.8 3 None 18.8/20.8 ——32.0/34.5 ——8/8 ——10/10 ——35/35 ——83/85 ——
KFCEH2901N09*** 9 6.8 1 None 32.8/36.0 ——49.5/53.5 ——8/6 ——10/10 ——50/60 ——54/87 ——
KFCEH3001F15*** 15 11.3 1 Fuse 54.2/59.9 36.2/40.0 18.1/20.0 76.3/83.4 53.8/58.5 22.7/25.0 4/4 6/6 10/10 8/8 10/10 10/10 80/90 60/60 25/25 88/89 78/80 75/76
15 11.3 1 Ckt Bkr 36.2/40.0 18.1/20.0 53.8/58.5 22.7/25.0 6/6 10/10 10/10 10/10 60/60 25/25 78/80 75/76
KFCEH1601315 15 11.3 3 None 31.3/34.6 ——47.7/51.8 ——8/6 ——10/10 ——50/60 ——56/90 ——
KFCEH2001318 18 13.5 3 None 37.6/41.5 ——55.5/60.4 ——6/6 ——10/8 ——60/70 ——76/77 ——
KFCEH2701C15***
KFCEH3201F20*** 20 15.0 1 Fuse 72.3/79.9 36.2/40.0 36.2/40.0 98.9/108.4 53.8/58.5 45.3/50.0 3/2 6/6 8/8 8/6 10/10 10/10 100/110 60/60 50/50 85/109 78/80 59/59
KFCEH3101C15***
20 15.0 1 Ckt Bkr 36.2/40.0 36.2/40.0 53.8/58.5 45.3/50.0 6/6 8/8 10/10 10/10 60/60 50/50 78/80 59/59
KFCEH2801C20***
30 22.5 3 Fuse 62.6/69.2 ——86.8/95.0 ——3/3 ——8/8 ——90/100 ——97/98 ——
24 18.0 3 Fuse 50.1/55.4 ——71.2/77.8 ——4/4 ——8/8 ——80/80 ——94/95 ——
24 18.0 1 Fuse 86.7/95.5 ——116.9/127.9 ——1/1 ——6/6 ——125/150 ——115/116 ——
KFCEH3301C20***
KFCEH3501F30***
KFCEH3401F24***
Table 4Smart Heat Electrical Data
30 22.5 1 Fuse 109.0/120.0 ——144.8/158.5 ——0/00 ——6/6 ——150/175 ——117/150 ——
208/230V
HEATER AMPS
CIRCUIT
INTERNAL
PHASE
KW
HEATER PART NO.
Dual Circuit
Single
Circuit
PROTECTION
240v 208v L1,L2 L3,L4 L1,L2 L3,L4 L1,L2 L3,L4 L1,L2 L3,L4 L1,L2 L3,L4 L1,L2 L3,L4
KFCEH0101H10 9 6.8 1 None 32.5/35.9 ——44.0/48.3 ——8/8 ——10/10 ——45/50 ——60/61 ——
KFCEH0201H15 15 11.3 1 Fuse 54.2/59.9 39.7/43.9 14.4/16.0 73.2/80.3 49.7/54.9 23.4/25.4 4/4 8/6 10/10 8/8 10/10 10/10 80/90 50/60 25/30 92/92 53/85 73/74
KFCEH0301H20 20 15.0 1 Fuse 72.3/79.9 36.2/40.0 36.2/40.0 97.2/106.7 52.0/56.8 45.3/50.0 3/2 6/6 8/8 8/6 10/10 10/10 100/110 60/60 50/50 87/111 81/82 93/93
Table 5Field Multipoint Wiring or 24- and 30-Kw Single Phase
HEATER AMPS
KW
208/230V
PHASE
240V 208V L1,L2 L3,L4 L5,L6 L1,L2 L3,L4 L5,L6 L1,L2 L3,L4 L5,L6 L1,L2 L3,L4 L5,L6 L1,L2 L3,L4 L5,L6
HEATER PART NO.
KFCEH3401F24 24 18.0 1 28.9/32.0 28.9/32.0 28.9/32.0 44.7/48.5 36.2/40.0 36.2/40.0 8/8 8/8 8/8 10/10 45/50 40/40 40/40 59/60 73/73 73/73
KFCEH3501F30 30 22.5 1 36.2/40.0 36.2/40.0 36.2/40.0 53.8/58.5 45.3/50.0 45.3/50.0 6/6 8/8 8/8 10/10 60/60 50/50 50/50 78/80 59/59 59/59
Field convertible to 1 phase, single or multiple supply circuit.
Field convertible to 3 phase.
(ANSI/NFPA 70).
** Includes blower motor amps of largest fan coil used with heater.
†† Copper wire must be used. If other than uncoated (non-plated), 75°C ambient, copper wire (solid wire for 10 AWG and smaller, stranded wire for larger than 10 AWG) is used, consult applicable tables of the National Electric Code
‡‡ Length shown is as measured 1 way along wire path between unit and service panel for a voltage drop not to exceed 2%.
*** Heaters are Intelligent Heat capable when used with the FK4, FV4, and 40FK fan coils and corporate 2-speed programmable thermostat (TSTATXXP2S01-B), or ThermidistatControl (TSTATXXPRH01-B).
2. For fan coil sizes 042-060 and all FE4, FK4, FV4, 40FK sizes.
3. Single circuit application of F15 and F20 heaters requires single-point wiring kit accessory.
NOTES: 1. For fan coil sizes 018-036.
4