Carrier Infinity ICS 58MVC 100 Series Installation Instructions Manual

Infinity ICS --- Model 58MVC, Series 100 Direct Vent, 4---Way Multipoise Condensing Gas Furnace With IdealComfort™ Ideal Humidity™
Installation Instructions
Visit www.Carrier.com
NOTE: Read the entire instruction manual before starting the installation.
NOTE: This furnace can be installed as a condensing gas furnace.
Special Venting Requirements for Installations in Canada
Installation in Canada must conform to the requirements of CSA B149 code. Vent systems must be composed of pipe, fittings, cements, and primers listed to ULC S636. The special vent fittings and accessory concentric vent termination kits and accessory external drain trap have been certified to ULC S636 for use with those IPEX PVC vent components which have been certified to this standard. In Canada, the primer and cement must be of the same manufacturer as the vent system -- IPEX System 636, PVC/CPVC Primer, Purple Violet for Flue Gas Venting and IPEX System 636 IIA, 65 deg C. must be used with this venting system -- do not mix primers and cements from one manufacturer with a vent system from a different manufacturer. Follow the manufacturer’s instructions in the use of primer and cement and never use primer or cement beyond its expiration date.
The safe operation, as defined by ULC S636, of the vent system is based on following these installation instructions, the vent system manufacturer’s installation instructions, and proper use of primer and cement. All fire stop and roof flashing used with this system must be UL listed material. Acceptability under Canadian standard CSA B149 is dependent upon full compliance with all installation instructions. Under this standard, it is recommended that the vent system be checked once a year by qualified service personnel.
The authority having jurisdiction (gas inspection authority, municipal building department, fire department, etc) should be consulted before installation to determine the need to obtain a permit.
(1)
t, PVC Cement for Flue Gas Venting, rated Class
(2-pipe) direct vent
ama
ISO 9001:2000
CERTIFIED
REGISTERED
Consignes spéciales pour l’installation de ventillation au Canada
L’installation faite au Canada doit se conformer aux exigences du code CSA B149. Ce systême de ventillation doit se composer de tuyaux, raccords, ciments et apprêts conformes au ULC S636. La tuyauterie de ventillation des gaz, ses accessoires, le terminal concentrique mural ainsi que l’ensemble du drain de condensat extérieur ont été certifiés ULCS 636 pour l’application des composantes IPEX PVC qui sont certifiées à ce standard. Au Canada l’apprêt et le ciment doivent être du même manufacturier que le systême de ventillation -- IPEX Système 636, Apprêt PVC/CPVC. Mauve Violette pour conduit en évacuation des gaz et IPEX Système 636 évacuation des gaz, évalué CLASSE IIA, 65 deg. C. doit ëtre utilisé avec ce systèeme d’évacuation -- ne pas mélanger l’apprêt et le ciment d’un manufacturier avec le systême de ventillation d’un autre manufacturier. Bien suivre les indications du manufacturier lors de l’utilisation de l’apprêt et du ciment et ne pas utiliser ceux--ci si la date d’expiration est atteinte.
L’opération sécuritaire, tel que définit par ULC S636, du système de ventilation est basé sur les instructions d’installation suivantes, ainsi que l’usage approprié de l’apprêt et ciment. Tout arrët feu et solin de toit utilisés avec ce système doivent être des matériaux listés UL. L’acceptation du standard Canadien CSA B419 est directement relié à l’installation conforme aux instructions ci-- haut mentionnées. Le standard Canadien recommande l’ inspection par un personel qualifié et ce, une fois par année.
Les autoritées ayant juridiction (inspecteurs de gas, inspecteurs en bâtiments, département des incendies, etc) devraient être consultées avant l’installation afin de déterminer si un permis est requis.
t, ciment pour PVC pour conduit en
(1)
(1) System 636 is a trademark of IPEX In c.
Required Notice for Massachusetts Installations
IMPORTANT
The Commonwealth of Massachusetts requires compliance with regulation 248 CMR as follows:
5.08: Modifications to NFPA--54, Chapter 10
2) Revise 10.8.3 by adding the following additional requirements: a. For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in
whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above finished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall be satisfied:
1. INSTALLATION OF CARBON MONOXIDE DETECTORS. At the time of installation of the side wall horizontal vented gas fueled equipment, the installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back--up is installed on the floor level where the gas equipment is to be installed. In addition, the installing plumber or gasfitter shall observe that a battery operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of qualified licensed professionals for the installation of hard wired carbon monoxide detectors
58MVC
a. In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard
wired carbon monoxide detector with alarm and battery back--up may be installed on the next adjacent floor level.
b. In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner
shall have a period of thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed.
2. APPROVED CARBON MONOXIDE DETECTORS. Each carbon monoxide detector as required in accordance with the above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified.
3. SIGNAGE. A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print size no less than one--half (1/2) inch in size, ”GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS”.
4. INSPECTION. The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.08(2)(a)1 through 4.
5. EXEMPTIONS: The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:
(1.) The equipment listed in Chapter 10 entitled ”Equipment Not Required To Be Vented” in the most current edition of
NFPA 54 as adopted by the Board; and
(2.) Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from
the dwelling, building or structure used in whole or in part for residential purposes.
c. MANUFACTURER REQUIREMENTS -- GAS EQUIPMENT VENTING SYSTEM PROVIDED. When the
manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the instructions provided by the manufacturer for installation of the equipment and the venting system shall include:
1. Detailed instructions for the installation of the venting system design or the venting system components; and
2. A complete parts list for the venting system design or venting system.
d. MANUFACTURER REQUIREMENTS -- GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED. When
the manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the flue gases, but identifies “special venting systems”, the following requirements shall be satisfied by the manufacturer:
1. The referenced “special venting system” instructions shall be included with the appliance or equipment installation instructions; and
2. The “special venting systems” shall be Product Approved by the Board, and the instructions for that system shall include a parts list and detailed installation instructions.
e. A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment,
all venting instructions, all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of the installation.
For questions regarding these requirements, please contact the Commonwealth of Massachusetts Board of State Examiners of Plumbers and
Gas Fitters, 239 Causeway Street, Boston, MA 02114. 617--727--9952.
2
TABLE OF CONTENTS
PAGE
IMPORTANT INFORMATION 2.........................
SAFETY CONSIDERATIONS 3.........................
CODES AND STANDARDS 7...........................
ELECTROSTATIC DISCHARGE (ESD) PRECAUTIONS 7...
INTRODUCTION 7...................................
APPLICATIONS 8....................................
Upflow 8.........................................
Downflow 11......................................
Horizontal Left 12...................................
Horizontal Right 15.................................
LOCATION 16.......................................
INSTALLATION 18...................................
Air Ducts 21........................................
Air for Combustion and Ventilation 28...................
Combustion Air Pipe 34...............................
Vent Pipe 36.......................................
Vent Termination 39.................................
Condensate Drain 43.................................
START--UP, ADJUSTMENTS, AND SAFETY CHECK 44....
CHECKLIST 60......................................
AIRFLOW
UPFLOW
AIRFLOW
HORIZONTAL
LEFT
DOWNFLOW
HORIZONTAL
RIGHT
AIRFLOW
SAFETY CONSIDERATIONS
!
CAUTION
FURNACE RELIABILITY HAZARD
Failure to follow this caution may result in unit damage. Improper installation or misapplication of furnace may
require excessive servicing or cause premature component failure. This furnace can be vented as either a direct vent (2--pipe) furnace or as an optional ventilated combustion air application. A direct vent system shall be installed in accordance with the direct vent (2--pipe) procedures in the Combustion Air and Vent Pipe Systems section within this instruction. For optional ventilated combustion air applications, refer to the ventilated combustion air option procedures in the same section.
Application of this furnace should be indoors with special attention given to vent sizing and material, gas input rate, air temperature rise, unit leveling, and unit sizing.
!
WARNING
FIRE, EXPLOSION, ELECTRICAL SHOCK AND CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury, death, or property damage.
Improper installation, adjustment, alteration, service, maintenance, or use can cause carbon monoxide poisoning, explosion, fire, electrical shock, or other conditions which may cause personal injury or property damage. Consult a qualified installer, service agency, local gas supplier, or your distributor or branch for information or assistance. The qualified installer or agency must use only factory--authorized and listed kits or accessories when modifying this product.
58MVC
AIRFLOW
Fig. 1 -- Furnace Orientation
A93041
!
CAUTION
CUT HAZARD
Failure to follow this caution may result in personal injury. Sheet metal parts may have sharp edges or burrs. Use care
and wear appropriate protective clothing and gloves when handling parts.
Improper installation, adjustment, alteration, service, maintenance, or use can cause explosion, fire, electrical shock, or other conditions which may cause death, personal injury, or property damage. Consult a qualified installer, service agency, or your distributor or branch for information or assistance. The qualified installer or agency must use factory--authorized kits or accessories when modifying this product. Refer to the individual instructions packaged with the kits or accessories when installing.
Follow all safety codes. Wear safety glasses, protective clothing, and work gloves. Have a fire extinguisher available. Read these instructions thoroughly and follow all warnings or cautions include in literature and attached to the unit. Consult local building codes, the current editions of the National Fuel Gas Code (NFGC) NFPA 54/ANSI Z223.1 and the National Electrical Code (NEC) NFPA 70.
3
(684 mm)
26 15⁄16"
1
(667 mm)
⁄4"
26
1
(622 mm)
24
⁄2"
5
⁄16"
22
2-IN. (51 mm) COMBUSTION­AIR CONN
1
⁄2-IN . (13mm) D IA
1
⁄2"
14
TYP
(368 mm)
1
(32 mm)
⁄4"
1
1"
(25mm)
58MVC
(567 mm)
GAS CONN
2-IN (51mm)
.
VENT CONN
1
⁄2-IN . DIA (13mm)
THERMOSTAT ENTRY
22 11⁄16"
SIDE INLET
(591 mm)
1
23
⁄4" TYP
SIDE INLET
15
26
⁄16" TYP
(684 mm)
CONDENSATE DRAIN TRAP LOCATION (DOWNFLOW & HORIZONTAL LEFT)
7
⁄8-IN. DIA (22mm)
POWER CONN
(783 mm)
11
⁄16"
7
⁄8-IN. DIA (22mm)
ACCESSORY POWER ENTRY
CONDENSATE DRAIN TRAP LOCATION (ALTERNATE UPFLOW)
(240 mm)
7
9
⁄16"
17 5⁄16"
TYP
(439 mm)
CONDENSATE DRAIN LOCATION (UPFLOW)
(622 mm)
NOTES: 1. Minimum return-air openings at furnace, based on metal duct. If flex duct is used,
2. Minimum return-air opening at furnace:
29
TYP
(754 mm)
5
27
⁄8"
(702 mm)
9
⁄16"
27
TYP
(700 mm)
1
⁄2"
24
see flex duct manufacturerís recommendations for equivalent diameters.
a. For 800 CFM–16-in. (406mm) round or 14 b. For 1200 CFM–20-in. (508mm) round or 141/2 c. For 1600 CFM–22-in. (559mm) round or 141/2 d. For airflow requirements above 1800 CFM, see Air Delivery table in Product Data
literature for specific use of single side inlets. The use of both side inlets, a combination of 1 side and the bottom, or the bottom only will ensure adequate return air openings for airflow requirements above 1800 CFM.
13
/16"
(21 mm)
1
13
⁄4"
33
⁄16"
30
TYP
(845 mm)
5
32
⁄8"
TYP
(829 mm)
11
/16"
(17 mm) (17 mm)
AIRFLOW
A
D
OUTLET
INLET
E
1
/2
(368 mm)x 12-in. (305 mm) rectangle.
(368mm)x 191/2 (368mm)x 231/4
13
(21 mm)
CONDENSATE DRAIN
HORIZONTAL RIGHT)
1
11
/16"
TRAP LOCATION
(DOWNFLOW &
OR ALTERNATE
⁄2-IN. DIA GAS CONN
30 1⁄2"
(775 mm)
CONDENSATE
DRAIN LOCATION
/16"
DIMPLE LOCATORS
FOR HORIZONTAL
-in. (495mm) rectangle.
-in.(591mm) rectangle.
18
(464 mm)
(UPFLOW)
HANGING
(14 mm)
9
⁄16"
TYP
1
⁄4"
1
(724 mm)
⁄2"
28
15
(684 mm)
⁄16"
26
1
(667 mm)
⁄4"
26
5
(567 mm)
22
⁄16"
(483 mm)
19"
OUTLET
2-IN. (51mm) COMBUSTION-AIR CONN
1
⁄2-IN. DIA (13mm)
GAS CONN
7
⁄8-IN. DIA (22mm)
POWER CONN
1
⁄2-IN. DIA (13 mm)
THERMOSTAT ENTRY
2-IN. (51 mm)
VENT CONN
11
22
⁄16"
(576 mm)
SIDE INLET
1
22
⁄4" TYP
(565 mm)
3
24
⁄16"
BOTTOM INLET
(614 mm)
13
⁄16"
5
⁄8"
(16 mm)
(25 mm) 1"
7
⁄16"
11
⁄16"
(21 mm) (16 mm)
5
⁄16"
7
39
⁄8"
(1013 mm)
(11 mm)
(25 mm)
A05124
Dimensions (In. / mm)
UNIT SIZE A D E
060 ---14 / 042060 17--- 1/2 / 445 15--- 7/8 / 403 16 / 406
080 ---14 / 042080 21 / 533 19---3/8 / 492 19--- 1/2 / 495
080 ---20 / 060080 21 / 533 19---3/8 / 492 19--- 1/2 / 495
100 ---20 / 060100 21 / 533 19---3/8 / 492 19--- 1/2 / 495
120 ---20 / 060120 24--- 1/2 / 622 22--- 7/8 / 581 23 / 584
Fig. 2 -- Dimensional Drawing
In Canada, refer to the current editions of the National Standards of Canada CAN/CSA--B149.1 and .2 Natural Gas and Propane Installation Codes, and Canadian Electrical Code CSA C22.1
Recognize safety information. This is the safety--alert symbol
. When you see this symbol on the unit and in instructions or manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING,and
CAUTION. These words are used with the safety--alert symbol. DANGER identifies the most serious hazards which will result in
severe personal injury or death. WARNING signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
!
CAUTION
ENVIRONMENTAL HAZARD
Failure to follow this caution may result in environmental polution.
Remove and recycle all components or materials (i.e., oil, refrigerant, control boards, etc.) before unit final disposal.
The 58MVC Condensing Gas--Fired Furnaces are CSA (formerly AGA and CGA) design--certified for natural and propane gases (see furnace rating plate) and for installation in alcoves, attics,
basements, closets, utility rooms, crawlspaces, and garages. The furnace is factory--shipped for use with natural gas. A CSA listed gas conversion kit is required to convert furnace for use with propane gas.
See Fig. 3 for required clearances to combustibles. Maintain a 1--in. (25 mm) clearance from combustible materials to
supply air ductwork for a distance of 36 inches (914 mm) horizontally from the furnace. See NFPA 90B or local code for further requirements.
These furnaces SHALL NOT be installed directly on carpeting, tile, or any other combustible material other than wood flooring. These furnaces are suitable for installation in a structure built on site or a manufactured building completed at final site. The design of this furnace line is NOT CSA design--certified for installation in recreation vehicles, manufactured (mobile) homes or outdoors.
This furnace is designed for continuous return--air minimum temperature of 60_F(16_C) db or intermittent operation down to 55_F(13_C) db such as when used with a night setback thermostat. Return--air temperature must not exceed 80_F(27_C) db. Failure to follow these return air limits may affect reliability of heat exchangers, motors and controls. (See Fig. 4.)
These furnaces are shipped with the drain and pressure tubes connected for UPFLOW applications. Minor modifications are required when used in DOWNFLOW, HORIZONTAL RIGHT, or HORIZONTAL LEFT (supply--air discharge direction) applications as shown in Fig. 1. See details in Applications section.
4
Install this furnace only in a location and position as specified in LOCATION and INSTALLATION sections of these instructions.
Combustion products must be discharged outdoors. Connect this furnace to an approved vent system only, as specified in the Combustion Air and Vent piping sections of these instructions.
Never test for gas leaks with an open flame. Use a commercially available soap solution made specifically for detection of leaks to check all connections as specified in the GAS PIPING section of these instructions.
Always install the furnace to operate within the furnace’s intended rise range with a duct system which has an external static pressure within the allowable range as specified in the SET TEMPERATURE RISE section of these instructions.
When a furnace is installed so that supply ducts carry air circulated by the furnace to areas outside the space containing the furnace, the return air shall also be handled by ducts sealed to the furnace casing and terminating outside the space containing the furnace.
A gas--fired furnace for installation in a residential garage must be installed as specified in the Hazardous Locations section of these instructions and Fig. 5.
The furnace may be used for construction heat provided that the furnace installation and operation complies with the first CAUTION in the LOCATION section of these instructions.
This gas furnace may be used for construction heat provided that:
S The furnace is permanently installed with all electrical wiring,
piping, air filters, venting and ducting installed according to these installation instructions. A return air duct is provided, sealed to the furnace casing, and terminated outside the space containing the furnace. This prevents a negative pressure condition as created by the circulating air blower, causing a flame rollout and/or drawing combustion products into the structure.
S The furnace is controlled by a thermostat. It may not be “hot
wired”to provide heat continuously to the structure without thermostatic control.
S Clean outside air is provided for combustion. This is to
minimize the corrosive effects of adhesives, sealers and other construction materials. It also prevents the entrainment of drywall dust into combustion air, which can cause fouling and plugging of furnace components.
S The temperature of the return air to the furnace is maintained
between 55_F(13_C) and 80_F(27_C), with no evening setback or shutdown. The use of the furnace while the structure is under construction is deemed to be intermittent operation per
our installation instructions.
S The air temperature rise is within the rated rise range on the
furnace rating plate, and the firing rate has been set to the nameplate value.
S The filters used to clean the circulating air during the
construction process must be either changed or thoroughly cleaned prior to occupancy.
S The furnace, ductwork and filters are cleaned as necessary to
remove drywall dust and construction debris from all HVAC system components after construction is completed.
S After construction is complete, verify furnace operating
conditions including ignition, input rate, temperature rise and venting, according to the manufacturer’s instructions.
If this furnace is installed with a direct--vent (combustion air and flue) system, a factory accessory termination kit must be installed. In a direct--vent system, all air for combustion is taken directly from the outside atmosphere and all flue products are discharged to the outside atmosphere. See furnace and factory accessory termination kit instructions for proper installation.
These furnaces are shipped with the following materials to assist in proper furnace installation. These materials are shipped in the main blower compartment.
Installer Packet Includes:
Installation, Start --- up, and Operating Instructions
Service and Maintenance Instructions
User’s Information Manual
Warranty Certificate
Loose Parts Bag includes: Quantity
Collector Box or Condensate trap extension tube 1
Inducer housing drain tube 1
1/2---in CPVC street elbow 2
Drain tube coupling 1
Drain tube coupling grommet 1
Gas line grommet 1
Vent pipe grommet 1
Combustion ---air pipe grommet 1
Gas line entry hole filler plug 1
Power entry hole filler plug 2
Condensate trap hole filler plug 3
Vent and combustion--- air intake hole filler plug 2
Combustion - -- air pipe perforated disk assembly 1
58MVC
5
58MVC
335122-201 REV. B LIT TOP
A08435
Fig. 3 -- Clearances to Combustibles
Fig. 4 -- Return--Air Temperature
80 / 27 C
60
/ 16 C
A06745
18-IN. (457.2 mm)
MINIMUM TO BURNERS
A93044
Fig. 5 -- Installation in a Garage
6
The furnace shall be installed so that the electrical components are protected from water.
For accessory installation details, refer to applicable installation literature.
CODES AND STANDARDS
Follow all national and local codes and standards in addition to these instructions. The installation must comply with
regulations of the serving gas supplier, local building, heating, plumbing, and other codes. In absence of local codes, the installation must comply with the national codes listed below and all authorities having jurisdiction in Canada.
In the United States and Canada, follow all codes and standards for the following:
Safety
S US: National Fuel Gas Code (NFGC) NFPA 54--2006/ANSI
Z223.1--2006 and the Installation Standards, Warm Air Heating and Air Conditioning Systems ANSI/NFPA 90B
S CANADA: National Standard of Canada, Natural Gas and
Propane Installation Code (CAN/CSA--B149.1--05) CSA B149.1--05
General Installation
S US: NFGC and theNFPA 90B. For copies, contact the National
Fire Protection Association Inc., Batterymarch Park, Quincy, MA 02269; or for only the NFGC contact the American Gas Association, 400 N. Capitol, N.W., Washington DC 20001.
S A manufactured (Mobile) home installation must conform with
the Manufactured Home Construction and SafetyStandard, Title 24 CFR, Part 3280, or when this standard is not applicable, the Standard for Manufactured Home Installation (Manufactured
Home Suites, Communities, and Set--Ups), ANSI/NCS A225.1, and/or CAN/CSA--z240, MH Series Mobile Homes.
S CANADA: CAN/CSA--B149.1--05. For a copy, contact
Standard Sales, CSA International, 178 Rexdale Boulevard, Etobicoke (Toronto), Ontario, M9W 1R3, Canada.
Combustion and Ventilation Air
S US: Section 9.3 NFPA 54/ANSI Z223.1--2006, Air for
Combustion and Ventilation.
S CANADA: Part 8 of the CAN/CSA--B149.1--05, Venting
Systems and Air Supply for Appliances.
Duct Systems
S US and CANADA: Air Conditioning Contractors Association
(ACCA) Manual D, Sheet Metal and Air Conditioning Contractors National Association (SMACNA), or American Society of Heating, Refrigeration, and Air Conditioning Engineers (ASHRAE) 2005 Fundamentals Handbook Chapter
35.
Acoustical Lining and Fibrous Glass Duct
S US and CANADA: current edition of SMACNA, NFPA 90B as
tested by UL Standard 181 for Class I Rigid Air Ducts.
Gas Piping and Gas Pipe Pressure Testing
S US: Section 9.3 NFPA 54/ANSI Z223.1--2006 NFGC; chapters
5, 6, 7, and 8 and national plumbing codes.
S CANADA: CAN/CSA--B149.1--05 Parts 4, 5, 6, and 9.
In the state of Massachusetts:
S This product must be installed by a licensed plumber or gas
fitter.
S When flexible connectors are used, the maximum length shall
not exceed 36 inches (914 mm).
S When lever type gas shutoffs are used they shall be T--handle
type.
S The use of copper tubing for gas piping is not approved by the
state of Massachusetts.
Electrical Connections
S US: National Electrical Code (NEC) ANSI/NFPA 70--2008. S CANADA: Canadian Electrical Code CSA C22.1.
ELECTROSTATIC DISCHARGE (ESD)
PRECAUTIONS
!
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in damage to unit components.
Electrostatic discharge can affect electronic components. Take precautions during furnace installation and servicing to protect the furnace electronic control. Precautions will prevent electrostatic discharges from personnel and hand tools which are held during the procedure. These precautions will help to avoid exposing the control to electrostatic discharge by putting the furnace, the control, and the person at the same electrostatic potential.
3. Disconnect all power to the furnace. Multiple disconnects may be required. DO NOT TOUCH THE CONTROL OR ANY WIRE CONNECTED TO THE CONTROL PRIOR TO DISCHARGING YOUR BODY’S ELECTROSTATIC CHARGE TO GROUND.
4. Firmly touch a clean, unpainted, metal surface of the furnace chassis which is close to the control. Tools held in a person’s hand during grounding will be satisfactorily discharged.
5. After touching the chassis, you may proceed to service the control or connecting wires as long as you do nothing that recharges your body with static electricity (for example; DO NOT move or shuffle your feet, DO NOT touch ungrounded objects, etc.).
6. If you touch ungrounded objects (recharge your body with static electricity), firmly touch furnace again before touching control or wires.
7. Use this procedure for installed and uninstalled (ungrounded) furnaces.
8. Before removing a new control from its container, discharge your body’s electrostatic charge to ground to protect the control from damage. If the control is to be installed in a furnace, follow items 1 through 5 before bringing the control or yourself into contact with the furnace. Put all used AND new controls into containers before touching ungrounded objects.
9. An ESD service kit (available from commercial sources) mayalsobeusedtopreventESDdamage.
INTRODUCTION
The model 58MVC Direct Vent, Upflow, Gas--Fired, Category IV, condensing furnace is available in model sizes ranging in input capacities of 60,000 to 120,000 Btuh.
APPLICATIONS
General
Some assembly and modifications are required for furnaces installed in any of the four applications shown in Fig. 1. All drain
58MVC
7
and pressure tubes are connected as shown in Fig. 7. See appropriate application instructions for these procedures.
!
CAUTION
PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in property damage.
Local codes may require a drain pan under entire furnace and condensate trap when a condensing furnace is used in an attic application or over a finished ceiling.
NOTE: In Canada, installations shall be in accordance with current CAN/CSA--B149.1--05 and/or local codes.
UPFLOW APPLICATION
An upflow furnace application is where furnace blower is located below combustion and controls section of furnace, and conditioned air is discharged upwards.
58MVC
Condensate Trap (Factory--Shipped Orientation)
The condensate trap is factory installed in the blower shelf and factory connected for UPFLOW applications. A factory--supplied tube is used to extend the condensate trap drain connection to the desired furnace side for field drain attachment. See Condensate Trap Tubing section for drain tube extension details. (See Fig. 6.)
Condensate Trap Tubing (Factory--Shipped Orientation)
NOTE: See Fig. 7 or tube routing label on main furnace door to
confirm location of these tubes.
1. Collector Box Drain, Inducer Housing Drain, Relief Port, and Pressure Switch Tubes. These tubes should be factory attached to condensate trap and pressure switch ready for use in UPFLOW applications. These tubes can be identified by their connection location and also by a color label on each tube. These tubes are identified as follows: collector box drain tube (blue label), inducer housing drain tube (violet label or molded), relief port tube (green label), and pressure switch tube (pink label).
2. Condensate Trap Drain Tube The condensate trap drain connection must be extended for field attachment by doing the following:
f. Determine location of field drain connection. (See Fig. 2
or 7.)
NOTE: If internal filter or side filter/media cabinet is used, drain tube should be located to opposite side of casing from return duct attachment to assist in filter removal.
g. Remove and discard casing drain hole plug button from
desired side.
h. Install drain tube coupling grommet (factory--supplied
in loose parts bag) in selected casing hole.
i. Slide drain tube coupling (factory--supplied in loose
parts bag) through grommet so long end of coupling faces blower.
j. Cement 2 factory--supplied 1/2--in. (13 mm) street
CPVC elbows to rigid drain tube connection on condensate trap. (See Fig. 7.) These elbows must be cemented together and cemented to condensate trap drain connection.
8
BLOWER SHELF
CONDENSATE TRAP (INSIDE)
ALTERNATE DRAIN TUBE LOCATION
CONDENSATE TRAP
DRAIN TUBE LOCATION
UPFLOW APPLICATIONS
FURNACE DOOR
FIELD
DRAIN
CONN
1
26
4
(667mm)
CONDENSATE TRAP
FURNACE
SIDE
1
(38mm)
SIDE VIEW FRONT VIEW END VIEW FRONT VIEW
DOWNFLOW AND ALTERNATE
EXTERNAL UPFLOW APPLICATIONS
FURNACE DOOR
7
(124mm)
8
4
1
2
(102mm)
FIELD
DRAIN
CONN
4
(667mm)
3
(146mm) (146mm)
4
5
1
26
4
HORIZONTAL
APPLICATIONS
4
(102mm)
(19mm)
FURNACE SIDE
5
3
4
3
4
SLOT FOR SCREW
HORIZONTAL
APPLICATION
(OPTIONAL)
1
(88mm)
1
2
(19mm)
3
4
WIRE TIE GUIDES (WHEN USED)
1
3
4
(181mm)
(44mm)
(3mm)
1
8
7
7
8
2
(57mm)
FRONT VIEW SIDE VIEW
Fig. 6 -- Condensate Trap
NOTE: Failure to use CPVC elbows may allow drain to kink,
preventing draining.
k. Connect larger diameter drain tube and clamp
(factory--supplied in loose parts bag) to condensate trap and clamp securely.
l. Route tube to coupling and cut to appropriate length.
m. Attach tube to coupling and clamp securely.
Condensate Trap (Alternate Upflow Orientation)
An alternate location for the condensate trap is the left--hand side of casing. (See Fig. 2 and 8.)
NOTE: If the alternate left--hand side of casing location is used, the factory--connected drain and relief port tubes must be disconnected and modified for attachment. See Condensate Trap Tubing (Alternate Upflow Orientation) section for tubing attachment.
To relocate condensate trap to the left--hand side, perform the following:
1. Remove three tubes connected to condensate trap.
2. Remove trap from blower shelf by gently pushing tabs inward and rotating trap.
3. Install casing hole filler cap (factory--supplied in loose parts bag) into blower shelf hole where trap was removed.
1/4 OD COLLECTOR BOX TO TRAP RELIEF PORT
1/2 OD INDUCER HOUSING DRAIN CONNECTION
5/8 OD COLLECTOR BOX DRAIN CONNECTION
SCREW HOLE FOR UPFLOW OR DOWN­FLOW APPLICATIONS (OPTIONAL)
1
4
1/2 IN. PVC OR CPVC
!
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury or death.
Casing hole filler cap must be installed in blower shelf hole when condensate trap is relocated to prevent combustion products being drawn in from appliances in the equipment room.
4. Install condensate trap into left--hand casing hole by inserting tube connection stubs through casing hole and rotating until tabs snap into locking position.
5. Fill unused condensate trap casing holes with plastic filler caps (factory--supplied in loose parts bag).
Condensate Trap Tubing (Alternate Upflow Orientation)
NOTE: See Fig. 8 or tube routing label on main furnace door to
confirm location of these tubes.
58MVC
A07459
9
PLUG
T
COLLECTOR BOX
DRAIN TUBE (BLUE &
WHITE STRIPED)
CAP
COLLECTOR BOX
TUBE (PINK)
INDUCER HOUSING
(MOLDED) DRAIN
UBE (BEHIND
COLLECTOR BOX
DRAIN TUBE)
COLLECTOR BOX
DRAIN TUBE (BLUE)
COLLECTOR BOX
TUBE (GREEN
ROUTES BEHIND
INDUCER)
CONDENSATE
58MVC
FIELD-INSTALLED
FACTORY-SUPPLIED
DRAIN TUBE
COUPLING (LEFT
DRAIN OPTION)
FIELD-INSTALLED
FACTORY-
SUPPLIED
DRAIN TUBE
FIELD-INSTALLED FACTORY­½ - IN. CPVC STREET
LEFT DRAIN OPTION
SUPPLIED
ELBOWS (2) FOR
FIELD- INSTALLED
FACTORY-
SUPPLIED
DRAIN TUBE
COUPLING (LEFT
DRAIN OPTION)
Fig. 7 -- Factory--Shipped Trap Location
(Shown with Blower Access Panel Removed)
1. Collector Box Drain Tube Connect collector box drain tube (blue label) to condensate trap.
NOTE: On 17--1/2--in. (445 mm) wide furnaces ONLY, cut tube between corrugated sections to prevent kinks.
2. Inducer Housing Drain Tube
a. Remove and discard LOWER (molded) inducer housing
drain tube which was previously connected to condensate trap.
b. Use inducer housing drain extension tube (violet label
and factory--supplied in loose parts bag) to connect LOWER inducer housing drain connection to condensate trap.
c. Determine appropriate length, then cut and connect
tube.
d. Clamp tube to prevent any condensate leakage.
3. Relief Port Tube
a. Connect relief port tube (green label) to condensate trap.
b. Extend this tube (if required) by splicing to small
diameter tube (factory--supplied in loose parts bag).
c. Determine appropriate length, then cut and connect
tube.
Condensate Trap Field Drain Attachment
Refer to Condensate Drain section for recommendations and procedures.
A07274
PLUG
COLLECTOR BOX
DRAIN TUBE (BLUE &
WHITE STRIPED)
CAP
COLLECTOR BOX
TUBE (PINK)
COLLECTOR BOX
DRAIN TUBE (BLUE)
COLLECTOR BOX
TUBE (GREEN)
CONDENSATE
INDUCER HOUSING
(MOLDED) DRAIN
TUBE (VIOLET)
A07281
Fig. 8 -- Alternate Trap Location
Pressure Switch Tubing
The LOWER collector box pressure tube (pink label) is factory connected to the pressure switch and should not require any modification.
NOTE: See Fig. 7 or 8 or tube routing label on main furnace door to check for proper connections.
Upper Collector Box and Inducer Housing (Unused)
Connections
Drain Upper Collector Box Drain
Connection
Attached to the UPPER collector box drain connection is a factory--installed corrugated, plugged tube (blue and white striped label). This tube is plugged to prevent condensate leakage in this application. Ensure this tube is plugged.
NOTE: See Fig. 7 or 8 or tube routing label on main furnace door to check for proper connections.
Upper Inducer Housing Drain Connection
Attached to the UPPER (unused) inducer housing drain connection is a cap and clamp. This cap is used to prevent condensate leakage in this application. Ensure this connection is capped.
NOTE: See Fig. 7 or 8 or tube routing label on main furnace door to check for proper connections.
Condensate Trap Freeze Protection
Refer to Condensate Drain Protection section for recommendations and procedures.
10
COLLECTOR BOX
DRAIN TUBE (BLUE)
COLLECTOR BOX
TUBE (GREEN)
COLLECTOR BOX
TUBE (PINK)
COLLECTOR BOX
DRAIN TUBE (BLUE &
WHITE STRIPED)
COLLECTOR BOX
TUBE EXTENSION
CONDENSATE
PLUG
CAP
COLLECTOR BOX TUBE (GREEN)
CAP
COLLECTOR BOX DRAIN TUBE (BLUE)
COLLECTOR BOX TUBE (PINK)
PLUG
COLLECTOR BOX DRAIN TUBE (BLUE & WHITE STRIPED)
COLLECTOR BOX TUBE EXTENSION
INDUCER HOUSING (MOLDED) DRAIN TUBE (VIOLET)
CONDENSATE
INDUCER HOUSING
(MOLDED) DRAIN
TUBE (VIOLET)
A07276
Fig. 9 -- Downflow Tube Configuration
(Left--hand Trap Installation)
DOWNFLOW APPLICATIONS
A downflow furnace application is where furnace blower is located above combustion and controls section of furnace, and conditioned air is discharged downwards.
Condensate Trap Location
The condensate trap must be removed from the factory--installed blower shelf location and relocated in selected application location asshowninFig.2,9,or10.
To relocate condensate trap from the blower shelf to desired location, perform the following:
1. Remove three tubes connected to condensate trap.
2. Remove trap from blower shelf by gently pushing tabs inward and rotating trap.
3. Remove casing hole filler cap from casing hole. (See Fig. 2 and 10.)
4. Install casing hole filler cap (factory--supplied in loose parts bag) into blower shelf hole where trap was removed.
!
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury or death.
Casing hole filler cap must be installed in blower shelf hole when condensate trap is relocated to prevent combustion products being drawn in from appliances in the equipment room.
5. Install condensate trap into left--hand side casing hole by inserting tube connection stubs through casing hole and rotating until tabs snap into locking position.
6. Fill unused condensate trap casing holes with plastic filler caps (factory--supplied in loose parts bag).
COLLECTOR BOX
EXTENSION DRAIN TUBE COUPLING
DRAIN TUBE
A07277
Fig. 10 -- Downflow Tube Configuration
(Right--Hand Trap Configuration)
Condensate Trap Tubing
NOTE: See Fig. 9 or 10 or tube routing label on main furnace
door to check for proper connections.
1. Collector Box Drain Tube a. Remove factory--installed plug from LOWER collector
box drain tube (blue and white striped label).
b. Install removed clamp and plug into UPPER collector
box drain tube (blue label) which was connected to condensate trap.
c. Connect LOWER collector box drain connection to
condensate trap.
(3.) Condensate Trap Located on Left Side of Casing
a. Connect LOWER collector box drain tube (blue
and white striped label) to condensatetrap. Tube does not need to be cut.
b. Clamp tube to prevent any condensate leakage.
(4.) Condensate Trap Located on Right Side of Casing
a. Install drain tube coupling (factory--supplied in
loose parts bag) into collector box drain tube (blue and white striped label) which was previously plugged.
b. Connect larger diameter drain tube
(factory--supplied in loose parts bag) to drain tube coupling, extending collector box drain tube for connection to condensate trap.
c. Route extended collector box drain tube between
gas valve and inlet housing as shown in Fig. 10.
d. Determine appropriate length and cut.
e. Connect to condensate trap.
2. Inducer Housing Drain Tube a. Remove factory--installed cap and clamp from LOWER
inducer housing drain connection.
58MVC
11
PLUG
AUXILIARY “J” BOX
CONDENSATE
CAP
58MVC
COLLECTOR BOX
TUBE EXTENSION
COLLECTOR BOX
EXTENSION
DRAIN TUBE
DRAIN TUBE
COUPLING
COLLECTOR BOX DRAIN TUBE (BLUE & WHITE STRIPED)
COLLECTOR BOX TUBE (GREEN)
INDUCER HOUSING (MOLDED) DRAIN TUBE (VIOLET)
COLLECTOR BOX DRAIN TUBE (BLUE)
COLLECTOR BOX TUBE (PINK)
A07278
Fig. 11 -- Horizontal Left Tube Configuration
b. Remove and discard UPPER (molded) inducer housing
drain tube which was previously connected to condensate trap.
c. Install cap and clamp on UPPER inducer housing drain
connection where molded drain tube was removed.
d. Use inducer housing drain tube (violet label and
factory--supplied in loose parts bag) to connect LOWER inducer housing drain connection to the condensate trap.
e. Connect inducer housing drain connection to
condensate trap.
(1.) Condensate Trap Located on Left Side of Casing
a. Determine appropriate length and cut.
b. connect tube to condensate trap.
c. Clamp tube to prevent any condensate leakage.
(2.) Condensate Trap Located on Right Side of Casing
a. Route inducer housing drain tube (violet label)
directly from inducer housing to condensate trap.
b. Determine appropriate length and cut.
c. Connect tube to condensate trap.
d. Clamp tube to prevent any condensate leakage.
3. Relief Port Tube Refer to Pressure Switch Tubing section for connection procedure.
Condensate Trap Field Drain Attachment
Refer to Condensate Drain section for recommendations and procedures.
Pressure Switch Tubing
One collector box pressure tube (pink label) is factory connected to the pressure switch for use when furnace is installed in UPFLOW or HORIZONTAL LEFT applications. The tube MUST be disconnected and used or the condensate trap relief port tube. The
other collector box pressure tube (green label) which was factory connected to the condensate trap relief port connection MUST be connected to the pressure switch in DOWNFLOW or HORIZONTAL RIGHT applications.
NOTE: See Fig. 9 or 10 or tube routing label on man furnace door to check for proper connections.
Relocate tubes as described below.
1. Disconnect collector box pressure tube (pink label) attached to pressure switch.
2. Extend collector box pressure tube (green label) which was previously connected to condensate trap relief port connection by splicing to small diameter tube (factory--supplied in loose parts bag).
3. Connect collector box pressure tube (green label) to pressure switch connection labeled COLLECTOR BOX.
4. Extend collector box pressure tube (pink label) which was previously connected to pressure switch by splicing to remaining small diameter tube (factory--supplied in loose parts bag).
5. Route this extended tube (pink label) to condensate trap relief port connection.
6. Determine appropriate length, cut, and connect tube.
7. Clamp tube to relief port connection.
Condensate Trap Freeze Protection
Refer to Condensate Drain Protection section for recommendations and procedures.
HORIZONTAL LEFT (SUPPLY--AIR DISCHARGE) APPLICATIONS
A horizontal left furnace application is where furnace blower is located to the right of combustion and controls section of furnace, and conditioned air is discharged to the left.
12
MANUAL
SHUTOFF
GAS VALVE
COMBUSTION - AIR
SEDIMENT TRAP
INTAKE
3
5
/4″ (146 mm)
CONDENSATE TRAP
VENT
30 (762 mm)MIN WORK AREA
DRAIN
A 12-IN. (305 mm) MIN HORIZONTAL PIPE SECTION IS RECOMMENDED WITH SHORT (5 TO 8 FT / 1.5 TO 2.4 M) VENT SYSTEMS TO REDUCE EXCESSIVE CONDENSATE DROPLETS FROM EXITING THE VENT PIPE.
ACCESS OPENING FOR TRAP
58MVC
NOTE: LOCAL CODES MAY REQUIRE A DRAIN PAN UNDER THE
FURNACE AND CONDENSATE TRAP WHEN A CONDENSING FURNACE IS INSTALLED ABOVE FINISHED CEILINGS.
Fig. 12 -- Attic Location and Working Platform for Direct Vent (2--Pipe) Application
COMBUSTION AIR
GAS VALVE
INTAKE
MANUAL
SHUTOFF
NOTE: LOCAL CODES MAY REQUIRE A DRAIN PAN UNDER THE
A 3-IN.(76mm) MINIMUM CLEARANCE TO COMBUSTION-AIR INTAKE IS REQUIRED.
3
5
/4 IN. (146mm)
SEDIMENT TRAP
FURNACE AND CONDENSATE TRAP WHEN A CONDENSING FURNACE IS INSTALLED ABOVE FINISHED CEILINGS.
CONDENSATE TRAP
VENT
30-IN. (762mm) MIN WORK AREA
ACCESS OPENING
DRAIN
FOR TRAP
A 12-IN. (305mm) MIN HORIZONTAL PIPE SECTION IS RECOMMENDED WITH SHORT (5 TO 8 FT / 1.5 TO 2.4M) VENT SYSTEMS TO REDUCE EXCESSIVE CONDENSATE DROPLETS FROM EXITING THE VENT PIPE.
Fig. 13 -- Attic Location and Working Platform for
Ventilated Combustion Air Applications
A93031
A96184
13
!
CAUTION
PROPERTY DAMAGE
Failure to follow this caution may result in property damage.
Local codes may require a drain pan under entire furnace and condensate trap when a condensing furnace is used in an attic application or over a finished ceiling.
NOTE: In Canada, installations shall be in accordance with current NSCNGPIC and/or local codes.
Condensate Trap Location
The condensate trap must be removed from the factory--installed blower shelf location and relocated in selected application location as shown in Fig. 2 or 11.
To relocate condensate trap from the blower shelf to desired location, perform the following:
58MVC
1. Remove three tubes connected to condensate trap.
2. Remove trap from blower shelf by gently pushing tabs inward and rotating trap.
3. Remove casing hole filler cap from casing hole. (See Fig. 2 or 11.)
4. Install casing hole filler cap (factory--supplied in loose parts bag) into blower shelf hole where trap was removed.
!
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury or death.
Casing hole filler cap must be installed in blower shelf hole when condensate trap is relocated to prevent combustion products being drawn in from appliances in the equipment room.
5. Install condensate trap into left--hand side casing hole by inserting tube connection stubs through casing hole and rotating until tabs snap into locking position.
6. Fill unused condensate trap casing holes with plastic filler caps (factory--supplied in loose parts bag).
Condensate Trap Tubing
NOTE: See Fig. 11 or tube routing label on main furnace door to
check for proper connections.
1. Collector Box Drain Tube
a. Install drain tube coupling (factory--supplied in loose
parts bag) into collector box drain tube (blue label) which was previously connected to condensate trap.
b. Connect large diameter drain tube and clamp
(factory--supplied in loose parts bag) to drain tube coupling, extending collector box drain tube.
c. Route extended tube (blue label) to condensate trap and
cut to appropriate length.
d. Clamp tube to prevent any condensate leakage.
2. Inducer Housing Drain Tube
a. Remove and discard LOWER (molded) inducer
housing drain tube which was previously connected to condensate trap.
b. Use inducer housing drain extension tube (violet
label and factory--supplied in loose parts bag) to
connect LOWER inducer housing drain connection to condensate trap.
c. Determine appropriate length, cut and connect
tube.
d. Clamp tube to prevent any condensate leakage.
3. Relief Port Tube a. Extend collector box tube (green label) which was
previously connected to condensate trap by splicing to small diameter tube (factory--supplied in loose parts bag).
b. Route extended collector box pressure tube to relief port
connection on condensate trap.
c. Determine appropriate length, cut, and connect tube.
d. Clamp tube to prevent any condensate leakage.
Condensate Trap Field Drain Attachment
Refer to Condensate Drain section for recommendations and procedures.
Pressure Switch Tubing
The LOWER collector box pressure tube (pink label) is factory connected to the High Pressure Switch for use when furnace is installed in UPFLOW applications. This tube MUST be disconnected, extended rerouted, and then reconnected to the pressure switch in HORIZONTAL LEFT applications for 060 and 080 heating input furnaces.
NOTE: See Fig. 11 or tube routing label on main furnace door to check for proper connections.
Modify tube as described below.
1. Disconnect collector box pressure tube (pink label) attached
to High Pressure Switch.
2. Use smaller diameter tube (factory--supplied in loose parts
bag) to extend tube disconnected in Item 1.
3. Route extended tube: a. Behind inducer housing.
b. Between blower shelf and inducer housing.
4. Determine appropriate length, cut, and reconnect tube to
High Pressure Switch connections labeled COLLECTOR BOX.
Condensate Trap Freeze Protection
Refer to Condensate Drain Protection section for recommendations and procedures.
Construct a Working Platform
Construct working platform where all required furnace clearances are met. (See Fig. 3 and 12 or 13.)
!
CAUTION
UNIT OPERATION HAZARD
Failure to follow this caution may result in intermittent unit operation.
The condensate trap MUST be installed below furnace. See Fig. 6 for dimensions. The drain connection to condensate trap must also be properly sloped to an open drain.
NOTE: A 12--in. (305 mm) minimum offset pipe section is recommended with short (5 to 8 ft. or 1.5M to 2.4M) vent systems. This recommendation is to reduce excessive condensate droplets from exiting the vent pipe. (See Fig. 12, 13, or 44.)
14
HORIZONTAL RIGHT (SUPPLY--AIR DISCHARGE) APPLICATIONS
A horizontal right furnace application is where furnace blower is located to the left of combustion and controls section of furnace, and conditioned air is discharged to the right.
!
CAUTION
PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in property damage.
Local codes may require a drain pan under entire furnace and condensate trap when a condensing furnace is used in an attic application or over a finished ceiling.
NOTE: In Canada, installations shall be in accordance with current NSCNGPIC and/or local codes.
NOTE: The auxiliary junction box (J--box ) MUST be relocated to opposite side of furnace casing. (See Fig. 14.) See Electrical Connection section for J--box relocation.
Condensate Trap Location
PLUG
COLLECTOR BOX
DRAIN TUBE (BLUE)
CAP
COLLECTOR BOX
DRAIN TUBE (BLUE &
WHITE STRIPED)
INDUCER HOUSING
(MOLDED) DRAIN
TUBE (VIOLET)
COLLECTOR BOX
EXTENSION TUBE
Fig. 14 -- Horizontal Right Tube Configuration
The condensate trap must be removed from the factory--installed blower shelf location and relocated in selected application location as shown in Fig. 2 or 14.
To relocate condensate trap from the blower shelf to desired location, perform the following:
1. Remove three tubes connected to condensate trap.
2. Remove trap from blower shelf by gently pushing tabs inward and rotating trap.
!
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury or death.
Casing hole filler cap must be installed in blower shelf hole when condensate trap is relocated to prevent combustion products being drawn in from appliances in the equipment room.
COLLECTOR BOX TUBE (GREEN)
COLLECTOR BOX TUBE (PINK)
AUXILIARY “J” BOX RELOCATED HERE
CONDENSATE
A07279
3. Install casing hole filler cap (factory--supplied in loose parts bag) into blower shelf hole where trap was removed.
4. Install condensate trap into right--hand side casing hole by inserting tube connection tabs through casing hole and rotating until tabs snap into locking position.
5. Fill unused condensate trap casing holes with plastic filler caps (factory--supplied in loose parts bag).
LEVEL (0”)
TO 1/2” (13mm)
MAX
UPFLOW OR DOWNFLOW
FRONT FRONT
MIN 1/4” (7mm) TO 1/2” (13mm)
MAX
HORIZONTAL
A02146
Fig. 15 -- Proper Condensate Drainage
Condensate Trap Tubing
NOTE: See Fig. 14 or tube routing label on main furnace door to
check for proper connections.
1. Collector Box Drain Tube
a. Remove factory--installed plug from LOWER collector
box drain tube (blue and white striped label).
b. Install removed clamp and plug into UPPER collector
box drain tube (blue label) which was previously connected to condensate trap.
c. Connect LOWER collector box drain tube (blue and
white striped label) to condensate trap. Tube does not need to be cut.
d. Clamp tube to prevent any condensate leakage.
2. Inducer Housing Drain Tube
a. Remove factory--installed cap and clamp from
LOWER inducer housing drain connection.
b. Remove and discard UPPER (molded) inducer
housing drain tube which was previously connected to condensate trap.
c. Install cap and clamp on UPPER inducer
housing drain connection where molded drain tube was removed.
d. Use inducer housing drain extension tube (violet
label and factory--supplied in loose parts bag) to connect LOWER inducer housing drain connection to condensate trap.
e. Determine appropriate length, cut, and connect
tube to condensate trap.
f. Clamp tube to prevent any condensate leakage.
3. Relief Port Tube Refer to Pressure Switch Tubing section for recommendations and procedures.
Condenste Trap Field Drain Attachment
Refer to Condensate Drain section for recommendations and procedures.
Pressure Switch Tubing
One collector box pressure tube (pink label) is factory connected to the pressure switch for use when furnace is installed in UPFLOW or HORIZONTAL LEFT applications. This tube MUST be disconnected and used for the condensate trap relief port tube. The other collector box pressure tube (green label) which was factory connected to the condensate trap relief port connection MUST be connect to the pressure switch in DOWNFLOW or HORIZONTAL RIGHT applications.
58MVC
15
NOTE: See Fig. 14 or tube routing label on main furnace door to check for proper connections.
Relocate tubes as described below.
1. Disconnect collector box pressure tube (pink label) attached to pressure switch.
2. Extend collector box pressure tube (green label) which was previously connected to condensate trap relief port connection by splicing to small diameter tube (factory--supplied in loose parts bag.)
3. Connect collector box pressure tube (green label) to pressure switch connection labeled COLLECTOR BOX.
4. Use remaining small diameter tube (factory--supplied in loose parts bag) to extend collector box pressure tube (pink label) which was previously connected to pressure switch.
5. Route this extended tube (pink label) to condensate trap relief port connection.
6. Determine appropriate Length, cut, and connect tube.
7. Clamp tube to relief port connection.
Condensate Trap Freeze Protection
58MVC
Refer to condensate Drain Protection section for recommendations and procedures.
Construct a Working Platform
Construct working platform where all required furnace clearances are met. (See Fig. 3 and 12 or 13.)
!
CAUTION
S not be installed directly on any combustible material other than
wood flooring (refer to SAFETY CONSIDERATIONS).
S be located so combustion--air and vent pipe maximum lengths
are not exceeded. Refer to Table 7.
S be located where available electric power and gas supplies meet
specifications on the furnace rating plate.
S be attached to an air distribution system and be located as close
to the center of the distribution system as possible. Refer to Air Ducts section.
S be provided with ample space for servicing and cleaning.
Always comply with minimum fire protection clearances shown on the furnace clearance--to--combustibles label. (See Fig. 3.)
This furnace may be located in a confined space without special provisions for dilution or ventilation air.
NOTE: For upflow/downflow applications install furnace so that it is level or pitched and forward within 1/2--in. (13 mm) for proper furnace operation. For horizontal applications pitch 1/4--in. (6 mm) minimum to 1/2--in. (13 mm) maximum forward to ensure proper condensate drainage from secondary heat exchangers. (See Fig. 15.) When a furnace is installed so that supply ducts carry air circulated by the furnace to areas outside the space containing the furnace, the return air shall also be handled by ducts sealed to furnace casing. The ducts terminate outside the space containing the furnace to ensure there will not be a negative pressure condition within equipment room or space.
UNIT OPERATION HAZARD
Failure to follow this caution may result in intermittent unit operation.
The condensate trap MUST be installed below furnace. See Fig. 6 for dimensions. The drain connection to condensate trap must also be properly sloped to an open drain.
NOTE: A 12--in. (305 mm) minimum offset pipe section is recommended with short (5 to 8 ft. or 1.5M to 2.4M) vent systems. This recommendation is to reduce excessive condensate droplets from exiting the vent pipe. (See Fig. 12, 13, or 44.)
LOCATION
General
This furnace must
S be installed so the electrical components are protected from
water.
FRONT
BACK
FRONT
Fig. 16 -- Prohibit Installation on Back
B A C K
A93043
16
!
CAUTION
!
CAUTION
UNIT DAMAGE HAZARD
This gas furnace may be used for construction heat provided that:
--The furnace is permanently installed with all electrical wiring, piping, air filters, venting and ducting installed according to these installation instructions. A return air duct is provided, sealed to the furnace casing, and terminated outside the space containing the furnace. This prevents a negative pressure condition as created by the circulating air blower, causing a flame rollout and/or drawing combustion products into the structure.
--The furnace is controlled by a thermostat. It may not be “hot wired” to provide heat continuously to the structure without thermostatic control.
--Clean outside air is provided for combustion. This is to minimize the corrosive effects of adhesives, sealers and other construction materials. It also prevents the entrainment of drywall dust into combustion air, which can cause fouling and plugging of furnace components.
--The temperature of the return air to the furnace is maintained between 55_F(13_C) and 80_F(27_C), with no evening setback or shutdown. The use of the furnace while the structure is under construction is deemed to be intermittent operation per our installation instructions.
--The air temperature rise is within the rated rise range on the furnace rating plate, and the firing rate has been set to the nameplate value.
--The filters used to clean the circulating air during the construction process must be either changed or thoroughly cleaned prior to occupancy.
--The furnace, ductwork and filters are cleaned as necessary to remove drywall dust and construction debris from all HVAC system components after construction is completed.
--After construction is complete, verify furnace operating conditions including ignition, input rate, temperature rise and venting, according to the manufacturer’s instructions.
!
WARNING
FIRE OR DEATH HAZARD
Failure to follow this warning could result in property damage, personal injury, or death.
Do not install furnace on its back. (See Fig. 16.) Safety control operation will be adversely affected. Never connect return--air ducts to back of furnace.
The furnace and its return air system shall be designed and installed so that negative pressure created by the air circulating fan cannot affect another appliance’s combustion air supply or act to mix products of combustion with circulating air, and that the air circulating fan of the furnace, if installed in an enclosure communicating with another fuel--burning appliance not of the direct--vent type, shall be operable only when any door or panel covering an opening in the furnace fan compartment or in a return air plenum on ducts is in the closed position.
UNIT DAMAGE HAZARD
Failure to follow this caution may result in minor property or unit damage.
If these furnaces are installed in an unconditioned space where ambient temperatures may be 32_F(0_C) or lower, freeze protection measures must be taken. See Condensate Drain Protection section and Fig. 17.
A07911
Fig. 17 -- Freeze Protection
Furnace Location Relative to Cooling Equipment
The cooling coil must be installed parallel with or on downstream side of furnace to avoid condensation in heat exchanger. When installed parallel with a furnace, dampers or other means used to control flow of air shall be adequate to prevent chilled air from entering furnace. If dampers are manually operated, they must be equipped with a means to prevent operation of either unit unless damper is in full--heat or full--cool position.
Hazardous Locations
!
WARNING
FIRE, EXPLOSION, INJURY OR DEATH HAZARD
Improper location or inadequate protection could result in fire or explosion.
When furnace is installed in a residential garage, it must be installed so that burners and ignition sources are located a minimum of 18 in. (457 mm) above floor. The furnace must be located or protected to avoid physical damage by vehicles. When furnace is installed in a public garage, airplane hangar, or other building having a hazardous atmosphere, unit must be installed in accordance with requirements of National Fire Protection Association, Inc. (See Fig. 5.)
58MVC
17
5/
(8mm)
(44mm)
16
1 3/ 4
(8mm)
5/
16
and forth until it breaks off. Be careful of sharp edges. (See Fig.
22.)
!
CAUTION
UNIT MAY NOT OPERATE HAZARD
Failure to follow this caution may result in intermittent unit operation or performance satisfaction.
3
/ 4
1
(44mm)
Do not bend duct flanges inward as shown in Fig. 22. This will affect airflow across heat exchangers and may cause limit cycling or premature heat exchanger failure. Remove duct flange completely or bend it inward a minimum of
(8mm)
5
/ 16
210_F(99_C) as shown in Fig. 22.
Installation in Horizontal Applications
(8mm)
5/
16
1
(44mm)
3/
4
1 3/ 4
A89014
58MVC
(44mm)
Fig. 18 -- Leveling Legs
These furnaces can be installed in either horizontal left or right discharge position. In a crawlspace, furnace can either be hung from floor joist or installed on suitable blocks or pad. Furnace can be suspended from each corner by hanger bolts and angle iron supports. (See Fig. 23.) Cut hanger bolts (4 each 3/8--in. all--thread rod) to desired length. Use 1 X 3/8--in. flat washers, 3/8--in. lock washers, and 3/8--in. nuts on hanger rods as shown in Fig. 23. Dimples are provided for hole locations. (See Fig. 2.)
INSTALLATION
Leveling Legs (If Desired)
When furnace is used in upflow position with side inlet(s), leveling legs may be desired. (See Fig. 18.) Install field--supplied, corrosion--resistant 5/16--in. (8 mm) machine bolts and nuts.
NOTE: The maximum length of bolt should not exceed 1--1/2 in. (38 mm).
1. Position furnace on its back. Locate and drill a 5/16--in. (8 mm) diameter hole in each bottom corner of furnace. (See Fig. 18.) Holes in bottom closure panel may be used as guide locations.
2. For each hole, install nut on bolt and then install bolt and nut in hole. (Install flat washer if desired.)
3. Install another nut on other side of furnace base. (Install flat washer if desired.)
4. Adjust outside nut to provide desired height, and tighten inside nut to secure arrangement.
NOTE: Bottom closure must be used when leveling legs are used. See Bottom Closure Panel section.
Installation in Upflow or Downflow Applications
NOTE: For downflow applications, this furnace is approved for
use on combustible flooring when special base (available from Manufacturer) Part No. KGB is used. Special base is not required when this furnace is installed on Manufacturer’s Cased Coil Assembly or when Manufacturer’s Coil Box is used.
1. Determine application being installed from Table 1.
2. Construct hole in floor per dimensions specified in Table 1 and Fig. 19.
3. Construct plenum to dimensions specified in Table 2 and Fig. 19.
4. If special base (KGASB) is used, install as shown in Fig.
20.
5. If Manufacturer’s Cased Coil Assembly or Manufacturer’s Coil Box is used, install as shown in Fig. 21.
NOTE: Remove furnace perforated discharge duct flanges when they interfere with mating flanges on coil on downflow subbase. To remove furnace perforated discharge duct flange, use hand scanners, wide duct pliers or duct flange tool to bend flange back
!
CAUTION
UNIT MAY NOT OPERATE HAZARD
Failure to follow this caution may result in intermittent unit operation or performance satisfaction.
The entire length of furnace MUST be supported when furnace is used in a horizontal position to ensure proper draining. When suspended, bottom brace supports sides and center blower shelf. When unit is supported from the ground, blocks or pad should support sides and center blower shelf area.
A
PLENUM
OPENING
B D
FLOOR
OPENING
C
Fig. 19 -- Floor and Plenum Opening Dimensions
A96283
18
FURNACE
(OR OTHER MANUFACTURER’S COIL CASING WHEN USED)
FURNACE
FACTORY SUPPLIED
CASED COIL OR COIL BOX
COMBUSTIBLE
FLOORING
DOWNFLOW
SUBBASE
SHEET METAL
PLENUM
FLOOR
OPENING
Fig. 20 -- Furnace, Plenum, and Subbase Installed on a
Combustible Floor
PERFORATED DISCHARGE DUCT FLANGE
A07585
COMBUSTIBLE
FLOORING
SHEET METAL
PLENUM
FLOOR
OPENING
58MVC
A07586
Fig. 21 -- Furnace, Plenum, and Coil Assembly or Coil Box
Installed on a Combustible Floor
NO
210 DEG.
MIN
Fig. 22 -- Duct Flanges
YES
YES
A93029
19
3-IN. MINIMUM CLEARANCE TO COMBUSTION-AIR INTAKE IS REQUIRED (NON-DIRECT VENT/1-PIPE APPLICATION,)
COMBUSTION-AIR INTAKE (NON-DIRECT VENT/1-PIPE APPLICATION)
COMBUSTION-AIR PIPE (DIRECT VENT/2-PIPE APPLICATION,ALL SIZES)
VENT
-IN. (10mm) ROD
3/8
ANGLE IRON OR EQUIVALENT
(B)
58MVC
(A)
(B)
(A) ROD LOCATION
USING DIMPLE LOCATORS (SEE DIMENSIONAL DWG FOR LOCATIONS)
(A) PREFERRED ROD LOCATION
(B) ALTERNATE ROD LOCATION
3
/8-IN. HEX NUT
& WASHER (4)
REQD PER ROD
NOTES:
(A)
1. A 1 In. (25mm) clearance minimum between top of furnace and combustible material.
2. The entire length of furnace must be supported when furnace is used in horizontal position to ensure proper drainage.
3. For non-direct vent/1-pipe application, bottom side combustion-air entry cannot be used when furnace is installed with hangers as shown.
5
(B)
3
DRAIN
/4
″ (146mm)
(A)
(B)
13
/16-IN. (21mm) MAX ALTERNATE SUPPORT LOCATION FROM BACK
ALTERNATE SUPPORT LOCATION 4-IN. (102mm) MIN 8-IN. (203mm) MAX
Fig. 23 -- Crawlspace Horizontal Application for Direct Vent / 2--Pipe Installation and for Ventilated Combustion Air Installation
A93304
20
FURNACE
CASING
WIDTH
17 ½
(445)
21
(533)
24 ---1/2
(622)
Table 1 – Opening Dimensions -- In. (mm)
APPLICATION
(APPROVED FACTORY SUPPLIED CASED COILS AND
COIL BOX: CD5, CKR, CAPVP, CARVP, CAPMP, CARMP,
CNPVP, CNRVP, AND KCAKC)
Upflow Applications on Combustible or Noncombustible Flooring (KGASB subbase not required)
Downflow Applications on Noncombustible Flooring (KGASB subbase not required)
Downflow applications on combustible flooring (KGASB subbase required)
Downflow Applications on Combustible Flooring with Factory supplied cased coil or Factory supplied coil box (KGASB
subbase not required) Upflow Applications on Combustible or Noncombustible
Flooring (KGASB subbase not required) Downflow Applications on Noncombustible Flooring (KGASB
subbase not required) Downflow applications on combustible flooring (KGASB
subbase required) Downflow Applications on Combustible Flooring with Factory
supplied cased coil or Factory supplied coil box (KGASB subbase not required)
Upflow Applications on Combustible or Noncombustible Flooring (KGASB subbase not required)
Downflow Applications on Noncombustible Flooring (KGASB subbase not required)
Downflow applications on Combustible flooring (KGASB subbase required)
Downflow Applications on Combustible Flooring with Factory supplied cased coil or Factory supplied coil box (KGASB subbase not required)
PLENUM OPENING FLOOR OPENING
A B C D
16
(406)
15--- 7/8
(403)
15--- 1/8
(384)
15--- 1/2
(394)
19--- 1/2
(495)
19--- 3/8
(492)
18--- 5/8
(473)
19
(483)
23
(584)
22--- 7/8
(581)
22--- 1/8
(562)
22--- 1/2
(572)
24--- 1/8
(613)
19
(483)
19
(483)
19
(483)
24--- 1/8
(613)
19
(483)
19
(483)
19
(483)
24--- 1/8
(613)
19
(483)
19
(483)
19
(483)
16--- 5/8
(422)
16--- 1/2
(419)
16--- 3/4
(425)
16--- 1/2
(419)
20--- 1/8
(511)
20
(508)
20--- 1/4
(514)
20
(508)
23--- 5/8
(600)
23--- 1/2
(597)
23--- 3/4
(603)
23--- 1/2
(597)
24--- 3/4
(629)
19--- 5/8
(498)
20--- 3/8
(518)
(508)
24--- 3/4
(629)
19--- 5/8
(498)
20--- 3/8
(518)
(508)
24--- 3/4
(629)
19--- 5/8
(498)
20--- 3/8
(518)
(508)
20
20
20
58MVC
AIR DUCTS
General Requirements
The duct system should be designed and sized according to accepted national standards such as those published by: Air Conditioning Contractors Association (ACCA), Sheet Metal and Air Conditioning Contractors National Association (SMACNA) or American Society of Heating, Refrigerating and Air Conditioning Engineers (ASHRAE) or consult The Air Systems Design Guidelines reference tables available from your local distributor. The duct system should be sized to handle the required system design CFM at the design static pressure.
When a furnace is installed so that the supply ducts carry air circulated by the furnace to areas outside the space containing the furnace, the return air must also be handled by a duct(s) sealed to the furnace casing and terminating outside the space containing the furnace.
Secure ductwork with proper fasteners for type of ductwork used. Seal supply-- and return--duct connections to furnace with code approved tape or duct sealer.
Flexible connections should be used between ductwork and furnace to prevent transmission of vibration. Ductwork passing through unconditioned space should be insulated to enhance system performance. When air conditioning is used, a vapor barrier is recommended.
Maintain a 1--in. (25 mm) clearance from combustible materials to supply air ductwork for a distance of 36 in. (914 mm) horizontally from the furnace. See NFPA 90B or local code for further requirements.
For a furnace not equipped with a cooling coil, the outlet duct shall be provided with a removable access panel. This opening shall be accessible when the furnace is installed and shall be of such a size that the heat exchanger can be viewed for possible openings using light assistance or a probe can be inserted for sampling the air stream. The cover attachment shall prevent leaks.
Ductwork Acoustical Treatment
Metal duct systems that do not have a 90 degree elbow and 10 ft. (3M) of main duct to the first branch take--off may require internal acoustical lining. As an alternative, fibrous ductwork may be used if constructed and installed in accordance with the latest edition of SMACNA construction standard on fibrous glass ducts. Both acoustical lining and fibrous ductwork shall comply with NFPA 90B as tested by UL Standard 181 for Class 1 Rigid air ducts.
Supply Air Connections Upflow
Connect supply--air duct to 3/4--in. (19 mm)flange on furnace supply--air outlet. The supply--air duct attachment must ONLY be connected to furnace supply--/outlet--air duct flanges or air conditioning coil casing (when used). DO NOT cut main furnace casing to attach supply side air duct, humidifier, or other accessories. All accessories MUST be connected external to furnace main casing.
Furnaces
Downflow Furnaces
Connect supply--air duct to supply--air opening on furnace. The supply--air duct attachment must ONLY be connected to furnace supply/outlet or air conditioning coil casing (when used) when installed on non--combustible material When installed on combustible material, supply air duct attachment must ONLY be connected to an accessory subbase or factory approved air conditioning coil casing. DO NOT cut main furnace casing to attach supply side air duct, humidifier, or other accessories. All accessories MUST be connected external to furnace main casing. Supply air opening duct flanges must be modified per Fig. 22.
Horizontal Furnaces
Connect supply--air duct to supply--air opening on furnace. The supply--air duct attachment must ONLY be connected to furnace supply/outlet or air conditioning coil casing (when used). DO NOT cut main furnace casing to attach supply side air duct, humidifier,
21
or other accessories. All accessories MUST be connected external
R
to furnace main casing.
Return Air Connections
!
WARNING
FIRE HAZARD
Failure to follow this warning could result in personal injury, death or property damage.
Never connect return--air ducts to the back of the furnace. Return air duct connections on furnace side(s) permitted in upflow applications only.
!
CAUTION
CUT HAZARD
Failure to follow this caution may result in personal injury. Use care when cutting support rods in filters to protect
against flying pieces and sharp rod ends. Wear safety glasses, gloves, and appropriate protective clothing.
!
CAUTION
Upflow Furnaces
The return--air duct must be connected to bottom, sides (left or right), or a combination of bottom and side(s) of main furnace casing. Bypass humidifier may be attached into unused side return air portion of the furnace casing. DO NOT connect any portion of
58MVC
return--air duct to back of furnace casing.
Downflow and Horizontal Furnaces
The return--air duct must be connected to return--air opening provided. DO NOT cut into casing sides or back to attach any portion of return--air duct. Bypass humidifier connections should be made at ductwork or coil casing sides exterior to furnace.
Filter Arrangement
!
WARNING
FIRE, CARBON MONOXIDE AND POISONING
HAZARD
Failure to follow this warning could result in personal injury, death or property damage.
Never operate unit without a filter or with filter access door removed.
The air filter arrangement will vary due to application, furnace orientation and filter type. The filter may be installed in an external Filter/Media cabinet (if provided) or the furnace blower compartment. Factory supplied washable filters are shipped in the blower compartment.
If a factory--supplied external Filter/Media cabinet is provided, instructions for its application, assembly, and installation are packaged with the cabinet. The Filter/Media cabinet can be used with the factory--supplied washable filter or a factory--specified high--efficiency disposable filter (see cabinet instructions).
If installing the filter in the furnace blower compartment, determine location for filter and relocate filter retaining wire, if necessary. See Table 2 to determine correct filter size for desired filter location. Table 2 indicates filter size, location, and quantity shipped with this furnace. See Fig. 2 for location and size of bottom and side return--air openings.
UNIT MAY NOT OPERATE
Failure to follow this caution may result in intermittent unit operation or performance satisfaction.
For airflow requirements above 1800 CFM, see Air Delivery table in Product Data literature for specific use of single side inlets. The use of both side inlets, a combination of one side and the bottom, or the bottom only will ensure adequate return air openings for airflow requirementsabove 1800 CFM.
Table 2 – Filter Information -- In. (mm)
AIR FILTER L OCATED IN BLOWER COMPARTMEN T
Furn ace
Casing Width
17---1/2
(445)
21
(533)
24---1/2
(622)
* Filters may be field modified by cutting filter material and support rods (3) i n filters. Alternate sizes can be ordered from your distributor or dealer
{ Factory--- provided with the furnace
(1) 16 x 25 x 3/4 {
(406 x 635 x 19)
(1) 16 x 25 x 3/4*
(406 x 635 x 19)
16 x 25 x 3/4*
(406 x 635 x 19)
WASHABLE
FILTER
Side
Return
(1 or 2 )
Filter Size
Bottom Return*
(1) 16 x 25 x 3/4{
(406 x 635 x 19)
(1) 20 x 25 x 3/4{
(508 x 635 x 19)
(1) 24 x 25 x 3/4{
(610 x 635 x 19)
Filter Type
Framed
Washab le
Washab le
Washab le
FILTER RETAINE
A93045
Fig. 24 -- Filter Installed for Side Inlet
22
For bottom return--air applications, filter may need to be cut to fit some furnace widths. Install filter as shown in Fig. 25.
171⁄2-IN. (444mm) WIDE CASINGS ONLY:
INSTALL FIELD-SUPPLIED FILTER FILLER STRIP UNDER FILTER.
3
(76mm)
1
24
(533mm)
/2″
1
(25.4mm)
21-IN. (533mm) WIDE CASINGS ONLY:
SUPPORT RODS (3) EXTEND 1/4" (6mm) ON EACH SIDE OF FILTER AND REST ON CASING FLANGE
for recommended gas pipe sizing. Risers must be used to connect to furnace and to meter. Support all gas piping with appropriate straps, hangers, etc. Use a minimum of one hanger every 6 ft. (1.8M). Joint compound (pipe dope) should be applied sparingly and only to male threads of joints. Pipe dope must be resistant to propane gas.
!
WARNING
FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in personal injury, death, or property damage.
-- Connect gas pipe to furnace using a backup wrench to avoid damaging gas controls.
-- Gas valve shutoff switch MUST be facing forward or tilted upward.
-- Never purge a gas line into a combustion chamber. Never test for gas leaks with an open flame. Use a
commercially available soap solution made specifically
for the detection of leaks to check all connections.
-- Use proper length of pipe to avoid stress on gas
control manifold.
-- If a flexible connector is required or allowed by authority having jurisdiction, black iron pipe shall be installed at furnace gas valve and extend a minimum
of 2 in. (51 mm) outside furnace casing.
--Protect gas valve from water and debris. Gas valve inlet and/or inlet piping must remain capped until gas
supply line is permanently installed to protect thevalve
from moisture and debris. Also, install a sediment trap
in the gas supply piping at the inlet to the gas valve.
58MVC
WASHABLE FILTER
FILTER SUPPORT
FILTER RETAINER
A00290
Fig. 25 -- Bottom Filter Arrangement
NOTE: Remove and discard bottom closure panel when bottom
inlet is used.
Bottom Closure Panel
These furnaces are shipped with bottom closure panel installed in bottom return--air opening. This panel MUST be in place when side return air is used.
To remove bottom closure panel, perform following:
1. Tilt or raise furnace and remove two screws holding front filler panel. (See Fig. 26.)
2. Rotate front filler panel downward to release holding tabs.
3. Remove bottom closure panel.
4. Reinstall front filler panel and screws.
Gas Piping
Gas piping must be installed in accordance with national and local codes. Refer to NFGC in the U.S. Canadian installations must be made in accordance with CAN/CSA--B149.1--05 and all authorities having jurisdiction. Gas supply line should be a separate line running directly from meter to furnace, if possible. Refer to Table 3
Install a sediment trap in riser leading to furnace. Trap can be installed by connecting a tee to riser leading to furnace so straight--through section of tee is vertical. Then connect a capped nipple into lower end of tee. Capped nipple should extend below level of gas controls. Place a ground joint union between gas control manifold and manual gas shutoff valve. (See Fig. 27.)
An accessible manual shutoff valve MUST be installed external to furnace casing and within 6 ft. (1.8M) of furnace. A 1/8--in. NPT (3 mm) plugged tapping, accessible for test gauge connection, MUST be installed immediately upstream of gas supply connection to furnace and downstream of manual shutoff valve.
Gas line grommet (factory--supplied loose parts bag) should be used when installing gas piping. Gas line entry hole filler plug should be installed in unused gas line entry hole. (See Fig. 28.)
BOTTOM CLOSURE PAN EL
FRONT FILLER PANEL
A93047
Fig. 26 -- Removing Bottom Closure Panel
23
GAS SUPPLY
MANUAL SHUTOFF VALVE (REQUIRED)
SEDIMENT TRAP
UNION
A93324
Fig. 27 -- Typical Gas Pipe Arrangement
58MVC
COMBUSTION-AIR PIPE GROMMET
UNUSED 1-3/4 -IN. (44 mm)
COMBUSTION
-AIR PIPE
DIAMETER GAS CONN. HOLE
GAS LINE
VENT PIPE
GAS LINE GROMMET
VENT PIPE GROMMET
NOTE: PIPE GROMMETS AND ENTRY HOLE FILLER PLUGS ARE INCLUDED IN FACTORY-SUPPLIED LOOSE PARTS BAG
Fig. 28 -- Casing Pipe Grommets
Tabl e 3 – Maximum Capacity of Pipe*
NOMINAL
IRON
PIPE SIZE
IN. (MM)
1/2 (13)
3/4 (19)
1 (25)
1-1/4
(32)
1-1/2
(38)
* Cubic f t. of gas pe r hr f or ga s pressure of 0.5 psi g (14 --- in. wc) or less, and a pressure drop of 0.5---in. wc (based on a 0.60 specific gravity gas). Ref: Table 9---2 NFPA 54---2002.
INTERNAL
DIA.
IN. (MM)
0.622 (158)
0.824
(21)
1.049
(27)
1.380
(35)
1.610
(41)
1400 950 770 660 580
2100 1460 1180 990 900
LENGTH OF PIPE --- FT (M)
10
(3.0)20(6.0)30(9.1)40(12.1)50(15.2)
175 120 97 82 73
360 250 200 170 151
680 465 375 320 285
NOTE: The gas valve inlet pressure tap connection is suitable to use as test gauge connection providing test pressure DOES NOT
GAS LINE ENTRY HOLE FILLER PLUG
A05057
exceed maximum 0.5 psig (14--in. wc) stated on gas valve. (See Fig. 60.)
Piping should be pressure and leak tested in accordance with NFGC in the United States or CAN/CSA--B149.1--05 in Canada, local, and national plumbing and gas codes before the furnace has been connected. If pressure exceeds 0.5 psig (14--in. wc), gas supply pipe must be disconnected from furnace and capped before pressure test.
If test pressure is equal to or less than 0.5 psig (14--in. wc), turn off electric shutoff switch located on gas valve before test. It is recommended that ground joint union be loosened before pressure testing. After all connections have been made, purge lines and check for leakage at furnace prior to placing it into service.
The gas supply pressure shall be within the maximum (13.6--in. wc) and minimum (4.5--in. wc) inlet supply pressures marked on the rating plate with the furnace burners ON at HI--HEAT and OFF.
24
Electrical Connections
See Fig. 29 for field wiring diagram showing typical field 115--v and 24--v wiring. Check all factory and field electrical connections for tightness.
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Blower access door switch opens 115--v power to furnace control. No component operation can occur. Do not bypass or close switch with panel removed.
!
WARNING
UNIT MAY NOT OPERATE
Failure to follow this caution may result in intermittent unit operation.
Furnace control must be grounded for proper operation or control will lock out. Control is grounded through green/yellow wire connected to gas valve and burner box screw.
115--v Wiring
Before proceeding with electrical connections, make certain that voltage, frequency, and phase correspond to that specified on furnace rating plate. Also, check to be sure that service provided by
115-V
SINGLE
PHASE
115-V
FIELD-SUPPLIED
DISCONNECT
SWITCH
FURNACE
CONTROL
THREE-WIRE
AUXILIARY J-BOX
CENTER
NOTE 5
FIVE
WIRE
HEATING
ONLY
TERMINAL
BLOCK
WCR GY
W/W1
NOTE
W2
3
R
G
C
Y/Y2
24-V
power supply is sufficient to handle load imposed by this equipment. Refer to rating plate or Table 4 for equipment electrical specifications.
Make all electrical connections in accordance with National Electrical Code (NEC) ANSI/NFPA 70--2008 and any local codes or ordinances that might apply. For Canadian installations, all electrical connections must be made in accordance with Canadian Electrical Code CSA C22.1 or authorities having jurisdiction.
Field--supplied wiring shall conform with the limitations of 63_F (33_C) rise.
The furnace must be electrically grounded in accordance with local codes; or in the absence of local codes, with the National Electric Code ANSI/NFPA 70 and/or the Canadian Electric Code, CSA C22.1, Part I, if an external electrical source is utilized.
Use a separate branch electrical circuit containing a properly sized fuse or circuit breaker for this furnace. See Table 4 for wire size and fuse specifications. A disconnecting means must be located within sight from and readily accessible to furnace.
NOTE: Proper polarity must be maintained for 115--v wiring. If polarity is incorrect or furnace is not grounded properly, furnace control status code indicator light will flash rapidly and furnace will NOT operate.
!
WARNING
FIRE HAZARD
Failure to follow this warning could result in personal injury, death, or property damage.
Do not connect aluminum wire between disconnect switch and furnace. Use only copper wire. (See Fig. 30.)
FIELD 24-V WIRING FIELD 115-, 208/230-, 460-V WIRING FACTORY 24-V WIRING FACTORY 115-, 208/230-, 460-V WIRING
THERMOSTAT TERMINALS
GND
NOTE 1
TWO WIRE
NOTES:
1.
Connect Y or Y/Y2 terminal as shown for proper cooling operation.
2.
Proper polarity must be maintained for 115-v wiring.
3.
Use W2 with 2-stage thermostat when zoning.
4.
If any of the original wire, as supplied, must be replaced, use same type or equivalent wire.
5.
Some thermostats require a "C" terminal connection as shown.
GND
CONDENSING
UNIT
FIELD-SUPPLIED
DISCONNECT
GND
GND
58MVC
208/230- OR
460-V
THREE PHASE
208/230-V
SINGLE
PHASE
Fig. 29 -- Heating and Cooling Application Wiring Diagram
A98325
25
Table 4 – Electrical Data
MAXIMUM
WIRE
LENGTH
FT (M)}
UNIT SIZE
V O L T S ---
H E R T Z ---
PHASE
OPERATING VOLTAGE
RANGE
Maximum* Minimum*
MAXIMUM
UNIT
AMPS
MINIMUM
WIRE SIZE
060--- 14/042060 11 5 --- 6 0 --- 1 127 104 8.96 14 30 (9.1) 15
080--- 14/042080 11 5 --- 6 0 --- 1 127 104 8.96 14 30 (9.1) 15
080--- 20/060080 11 5 --- 6 0 --- 1 127 104 14.06 12 31 (9.4) 20
100--- 20/060100 11 5 --- 6 0 --- 1 127 104 14.06 12 31 (9.4) 20
120--- 20/060120 11 5 --- 6 0 --- 1 127 104 14.06 12 31 (9.4) 20
* Permissible limits of voltage range at which unit will operate satisfactorily. { Unit ampacity = 125 percent of largest operating component’s full load
amps plus 100 percent of all other potential operating components’ (EAC, humidifier, etc.) full load amps.
!
WARNING
ELECTRICAL SHOCK AND FIRE HAZARD
58MVC
Failure to follow this warning could result in electrical shock, fire, or death.
The cabinet MUST have an uninterrupted or unbroken ground according to NEC ANSI/NFPA 70--2008 and
} Length shown is as measured 1 way along wire path between unit and service panel for maximum 2 percent voltage drop.
** Time ---delay type is recommended.
ALTERNATE
FIELD
LOCATION
POWER ENTRY HOLE FILLER PLUG (FACTORY­SUPPLIED LOOSE PARTS BAG)
UNUSED 7/8-IN. DIAMETER POWER ENTRY HOLES
Canadian Electrical Code CSA C22.1 or local codes to minimize personal injury if an electrical fault should occur. This may consist of electrical wire or conduit approved for electrical ground when installed in accordance with existing electrical codes. Do not use gas piping as an electrical ground.
ELECTRIC
DISCONNECT
SWITCH
COPPER
WIRE ONLY
POWER ENTRY HOLE FILLER PLUG (FACTORY­SUPPLIED LOOSE PARTS BAG)
UNUSED 7/8-IN. (22 mm) DIAMETER POWER ENTRY HOLES
ALTERNATE
FIELD
LOCATION
Fig. 32 -- J--Box Relocation
FACT ORY INSTALLED LOCATION
MAXIMUM
FUSE OR CKT
BKR
AMPS**
FACT ORY INSTALLED LOCATION
POWER ENTRY HOLE FILLER PLUG (FACTORY­SUPPLIED LOOSE PARTS BAG)
UNUSED 7/8-IN. DIAMETER POWER ENTRY HOLES
POWER ENTRY HOLE FILLER PLUG (FACTORY­SUPPLIED LOOSE PARTS BAG)
UNUSED 7/8-IN. (22 mm) DIAMETER POWER ENTRY HOLES
A05058
ALUMINUM
WIRE
A93033
Fig. 30 -- Disconnect Switch and Furnace
Install power entry hole filler plugs (factory--supplied in loose parts bag) in unused power entry holes. (See Fig. 31.)
FACT ORY INSTALLED LOCATION
POWER ENTRY HOLE FILLER PLUG (FACTORY­SUPPLIED LOOSE PARTS BAG)
UNUSED 7/8-IN. (22 mm) DIAMETER POWER ENTRY HOLES
A05113
Fig. 31 -- Factory Installed J--Box Location
J--Box Relocation
1. Remove two screws holding auxiliary J--box. (See Fig. 32.)
2. Rotate J--box 180_ and attach box to left side, using holes provided.
3. Install power entry hole filler plugs (factory--supplied loose parts bag) in unused power entry holes. (See Fig. 31.)
!
WARNING
FIRE OR ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury, death, or property damage.
If manual disconnect switch is to be mounted on furnace, select a location where a drill or fastener will not contact electrical or gas components.
NOTE: If modulating dampers are used, blower motor automatically compensates for modulating dampers. If manual disconnect switch is to be mounted on furnace, select a location where a drill or fastener will not contact electrical or gas components.
24--v wiring
Make field 24--v thermostat connections at 24--v terminal block on furnace control. Y wire from thermostat MUST be connected to Y/Y2 terminal on control, as shown in Fig. 19, for proper cooling operation. The 24--v terminal block is marked for easy connection of field wiring. (See Fig. 33.) The 24--v circuit contains a 3--amp, automotive--type fuse located on furnace control. (See Fig. 33.)
26
Any electrical shorts of 24--v wiring during installation, service, or maintenance may cause fuse to blow. If fuse replacement is required, use only a fuse of identical size (3 amp) and type. The furnace control will flash status code 24 when fuse needs replacement.
NOTE: Use AWG No. 18 color--coded copper thermostat wire for lengths up to 100 ft. (30.4M). For wire lengths over 100 ft., (30.4M) use AWG No. 16 wire.
NOTE: For additional thermostat connection diagrams, reference Fig. 52--59.
Accessories
1. Electronic Air Cleaner (EAC) The furnace control EAC terminals are energized with 115v (1.0--amp maximum) during blower operation. Connect an accessory Electronic Air Cleaner (if used) using 1/4--in. female quick connect terminals to the two male 1/4--in. quick--connect terminals on the control board marked EAC--1 and EAC--2. The terminals are rated for 115VAC, 1.0 amps maximum and are energized during blower motor operation. (See Fig. 33.)
NOTE: Low stage airflow may slightly increase the trace amount of ozone created by an electronic air cleaner. Individual sensitivity levels to ozone, along with other operating characteristics of electronic air cleaners may affect the amount noticed by an individual. Refer to the air cleaner manufacturer’s installation instructions for more information regarding ozone and ozone reduction methods available for your air cleaner.
!
UNIT DAMAGE HAZARD
Failure to follow this caution may result in unit component damage.
DO NOT connect furnace control HUM terminal to HUM (humidifier) terminal on Thermidistatt, Zone Controller or similar device. See Thermidistatt, Zone Controller, thermostat, or controller manufacturer’s instructions for proper connection.
2. Humidifier (HUM) Connect an accessory 24 VAC, 0.5 amp maximum humidifier (if used) to the 1/4--in. male quick--connect HUM terminal and COM--24V screw terminal on the control board thermostat strip. The HUM terminal is energized when blower is energized in heating. (See Fig.
33.)
CAUTION
Removal of Existing Furnaces from Common Vent Systems
When an existing Category I furnace is removed or replaced, the original venting system may no longer be sized to properly vent the remaining attached appliances. An improperly sized Category I venting system could cause the formation of condensate in the furnace and vent, leakage of condensate and combustion products, spillage of combustion products into the living space, etc.
AIR FOR COMBUSTION AND VENTILATION
!
CAUTION
FURNACE RELIABILITY HAZARD
Failure to follow this caution may result in premature component failure.
This furnace can be vented as either a direct vent (2--pipe) furnace or as an optional ventilated combustion air application. A direct vent system shall be installed in accordance with the direct vent (2-- pipe) procedures in the Combustion Air and Vent Pipe Systems section within this supplemental instruction. For optional ventilated combustion air applications, refer to the ventilated combustion air option procedures in the same section. Application of this furnace should be indoors with special attention given to vent sizing and material, gas input rate, air temperature rise, unit leveling, and unit sizing.
Combustion--Air and Vent Pipe Systems
For additional venting information contact www.Carrier.com.
General
Vent system or vent connectors of other appliances may need to be re--sized. For any other appliances when resizing vent systems or vent connectors, system or connector must be sized to approach minimum size as determined using appropriate table found in the NFGC or CAN/CSA--B149.1--05.
The 58MVC furnaces can be vented as either a direct vent furnace or as an optional ventilated combustion air application. A direct vent system shall be installed in accordance with the direct vent (2--pipe) procedures in the following Combustion Air and Vent Pipe Systems section. For optional ventilated combustion air applications, refer to the ventilated combustion air option procedures in the same section. Common venting prohibited.
Direct Vent / 2--Pipe System
In a direct--vent (2--pipe) system, all air for combustion is taken directly from outdoor atmosphere, and all flue products are discharged to outdoor atmosphere. Combustion--air and vent pipes must terminate together in the same atmospheric pressure zone, either through the roof or a sidewall (roof termination preferred). A factory accessory vent termination kit MUST be used in a direct vent (2--pipe) system. See Fig. 34 for required clearances.
Ventilated Combustion Air Option Materials
In a ventilated combustion air option, the vent terminates and discharges the flue products directly to the outdoors similar to a direct vent system. See Fig. 35 for required clearances. All air for combustion is piped directly to the furnace from a space that is well ventilated with outdoor air (such as an attic or crawl space) and the space is well isolated from the living space or garage.
Materials
Combustion--air and vent pipe, fittings, primers, and solvents must conform to American National Standards Institute (ANSI) standards and American Society for Testing and Materials (ASTM) standards. See Table 5 for approved materials for use in the USA.
58MVC
27
!
WARNING
FIRE AND EXPLOSION HAZARD
Failure to follow this warning could result in personal injury, death, or property damage.
Solvent cements are combustible. Keep away from heat, sparks, and open flame. Use only in well ventilated areas. Avoid breathing in vapor or allowing contact with skin or eyes.
In Canada, construct all combustion--air and vent pipes for this unit of CSA or ULC listed schedule--40 PVC, PVC--DWV or ABSDWV pipe and pipe cement. SDR pipe is NOT approved in Canada.
!
WARNING
CARBON MONOXIDE POISONING HAZARD
58MVC
Failure to follow this warning could result in personal injury, death, or property damage.
All combustion--air and vent pipes must be airtight and watertight. Pipes must also terminate exactly as shown in Fig. 36 for direct vent (2--pipe) system or Fig. 37 for ventilated combustion air option.
An abandoned masonry chimney may be used as a raceway for properly insulated and supported combustion--air (when applicable) and vent pipes. Each furnace must have its own set of combustion--air and vent pipes and be terminated individually, as shown in Fig. 36 for Direct Vent (2--Pipe) system or Fig. 37 for ventilated combustion air option.
A furnace shall not be connected to a chimney flue serving a separate appliance designed to burn solid fuel.
Other gas appliances with their own venting system may also use the abandoned chimney as a raceway providing it is permitted by local code, the current edition of the National Fuel Gas Code and the vent or liner manufacturer’s installation instructions. Care must be taken to prevent the exhaust gases from one appliance from contaminating the combustion air of other gas appliances. Do not take combustion air from inside the chimney when using the Ventilated Combustion Air option.
!
UNIT MAY NOT OPERATE HAZARD
Failure to follow this caution may result in intermittent unit operation.
When vent pipe is exposed to temperatures below freezing, such as when it passes through an unheated space or when a chimney is used as a raceway, pipe must be insulated as shown in Table 6 with Armaflex--type insulation.
CAUTION
Furnace combustion air and vent pipe connections are sized for 2-­in. pipe. Any pipe size change should be made outside furnace casing in vertical pipe. The transition has to be made as close to the furnace as reasonably possible. (See Fig. 38.)
28
Table 5 – Approved Combustion--Air and Vent Pipe, Fitting and Cement Materials
ASTM
SPECIFICATION
(MARKED ON
MATERIAL)
D1527 ABS Pipe Schedule40 D1785 PVC Pipe Schedule40
D2235 For ABS
D2241 PVC Pipe SDR21 & SDR26 D2466 PVC Fittings Schedule40 D2468 ABS Fittings Schedule40
D2564 For PVC
D2661 ABS Pipe Fittings DWV at Schedule40 IPS sizes D2665 PVC Pipe Fittings DWV
F438 CPVC Fittings Schedule40 F441 CPVC Pipe Schedule40 F442 CPVC Pipe SDR
F493 For CPVC
F628 ABS Pipe
F656 For PVC Primer For PVC F891 PVC Pipe Cellular Core Schedule 40 & DWV
MATERIAL PIPE FITTINGS
SOLVENT
CEMENT
AND PRIMERS
Solvent
Cement
Solvent
Cement
Solvent
Cement
DESCRIPTION
For ABS
For PVC
For CPVC
Cellular Core DWV at Schedule40
IPS sizes
58MVC
Installation Guidelines for Combustion Air Pipe and
Pipe
Ve nt
It is recommended that all pipes be cut, prepared, and preassembled before permanently cementing any joint.
1. Attach combustion air pipe and vent pipe per instructions in sections “Combustion Air Pipe” and “Vent Pipe.”
2. Working from furnace to outside, cut pipe to required length(s).
3. Deburr inside and outside of pipe.
4. Chamfer outside edge of pipe for better distribution of primer and cement.
5. Clean and dry all surfaces to be joined.
6. Check dry fit of pipe and mark insertion depth on pipe.
7. After pipes have been cut and preassembled, apply generous layer of cement primer to pipe fitting socket and end of pipe to insertion mark. Quickly apply approved cement to end of pipe and fitting socket (over primer). Apply cement in a light, uniform coat on inside of socket to prevent buildup of excess cement. Apply second coat.
8. While cement is still wet, twist pipe into socket with 1/4 turn. Be sure pipe is fully inserted into fitting socket.
9. Wipe excess cement from joint. A continuous bead of cement will be visible around perimeter of a properly made joint.
10. Handle pipe joints carefully until cement sets.
11. Horizontal portions of the venting system shall be supported to prevent sagging. Support combustion air
piping and vent piping a minimum of every 5 ft. (1.5M)(3 ft. (.91M) for SDR--21 or --26 PVC) using perforated metal hanging strap.
12. Slope combustion air piping and vent piping downward towards furnace a minimum of 1/4--in. per linear ft. with no sags between hangers.
13. Horizontal portions of the venting system shall be installed so as to prevent the accumulation of condensate.
14. Use appropriate methods to seal openings where combustion air pipe and vent pipe pass through roof or sidewall.
Combustion--Air and Vent Pipe Diameter
Determine combustion--air and vent pipe diameter.
1. Using Table 7, individually determine the diameter of the combustion--air and vent pipe allowed. If different, pick the larger of these two diameters and use this diameter for both combustion--air and vent pipes.
2. When installing vent systems of short pipe length, use the smallest allowable pipe diameter. Do not use pipe size greater than required or incomplete combustion, flame disturbance, or flame sense lockout may occur.
NOTE: Do not count elbows or pipe sections in terminations or within furnace.
NOTE: A 2--in. diameter pipe must be used within furnace casing. Make all pipe diameter transitions outside furnace casing.
29
T
58MVC
MODEL PLUG
CONNECTOR
SW1 SETUP
SWITCHES AND
BLOWER OFF-
DELAY
AIR CONDITIONING
(A/C) AIRFLOW
SETUP SWITCHES
24-V THERMOSTAT
TERMINALS
USER INTERFACE
OR ADVANCED
PRODUCT MONITOR
CONNECTOR
CONTINUOUS FAN
(CF) AIRFLOW
SETUP SWITCHES
OAT
CONNECTOR
SW4 SETUP
SWIT CHES
HUMIDIFIER
TERMINAL (24-VAC
0.5 AMP MAX.
ACRDJ – AIR
CONDITIONING
RELAY DISABLE
JUMPER
FLASH
UPGRADE
CONNECTOR
(FACTORY
ONLY)
STATUS AND COMM
LED LIGHTS
3-AMP FUSE
RANSFORMER 24-VAC
CONNECTIONS
115-VAC (L2) NEUTRAL
CONNECTIONS
PL1 – LOW VOLTAGE MAIN
HARNESS CONNECTOR
EAC-1 TERMINAL
(115 -VAC 1.0 AMP MAX.)
EXAMPLE:
V12 HK42FZ022 3407
SOFTWARE
VERSION
PART
NUMBER
Fig. 33 -- Furnace Control
VOLTAGE CONNECTIONS
DATE
CODE
115-VAC (L1) LINE
PL3 – ECM BLOWER
HARNESS
CONNECTOR
BOARD SERIAL
NUMBER
PL2 – HOT SURFACE
IGNITER & INDUCER
MOTOR CONNECTOR
A07422
30
V
V
58MVC
12 inches (30 cm) for applieances >10,000 Btuh(3 kW) and <
100,000 Btuh(30kW), 36 inches (91cm) for
appliances > 100,000 Btuh(30kW)
Fig. 34 -- Direct Vent Termination Clearance
A08600
31
58MVC
Fig. 35 -- Ventilated Combustion Air Vent Termination Clearance
A08601
32
Vertical separation between combustion air and vent 8 3/4 in. (222mm)for 3 in. (76mm)kit
6 3/4 in. (172mm)for 2 in. (51mm) kit
Maintain 12 in. (305mm)min. clearance above highest anticipated snow level Maximum of 24 in.(614mm) above roof
Note: "A" denotes 0 to < 2 in. Between the first 2 vents Third vent must be > 36 in. away
Roof Ter mination (Preferred)
18 in. maximum
90°
At least 36 in.
(914mm)
(457mm)
At least
(51mm)
(914mm)
Concentric Vent and Combustion Air
A
Abandoned masonry used as raceway (per code)
(914mm)
in.
min from
12
overhang or roof
(typ)
in.
(305mm)
At least 36 in.
(914mm)
12
in. (305mm)
separation between
A
.
in
36
bottom ofcombustion air and
bottom of vent (typ)
Maintain 12 min. clearance above highest anticipated snow level or grade whichever is greater (typ)
Roof Termination (preferred)
A
Side wall termination
of less than 12
At least
36 in.
(914mm)
in. (305mm)
A
above highest snow level
Maintain 12
in.
min. clearance above highest anticipated snow level, maximum of 24 in. above roof
1
in. (25mm)
12 overhang or roof
A
t le
a
3
st
6
in
.
Concentric Vent and Combustion - Air Side Te rmination
(305mm)
maximum (typ) from wall to inlet
in. (305mm)
minimum from
A
Maintain 12
in.
min. clearance above highest anticipated snow level or grade whichever is greater
(305mm)
58MVC
Fig. 36 -- Combustion Air and Vent Termination for Direct Vent (2--pipe) System
Roof Ter mination (Preferred)
Ven t
(305mm)
Maintain 12 in .
minimum clearance
above highest anticipated
snow level maximum of
24 in. (610mm) above roof.
Abandoned masonry used as raceway (per code)
12 in. min. (305 mm)from
overhang or roof
Sidewall Ter mi na t io n
with Straight Pipe (preferred)
90°
Side wall termination with 2 elbows (preferred)
12 in. (305 mm) min. from
overhang or roof
Maintain 12 in. (305mm) minimum clearance above highest anticipated snow level or grade whichever is greater.
6 in. (152mm) minimum clearance
between wall and end of vent pipe.
10 in. (254mm) maximum pipe length
Maintain 12 in. (305mm) minimum clearance above highest anticipated snow level or grade whichever is greater
A05090
Fig. 37 -- Vent Pipe Termination for Ventilated Combustion Air System
A05091
33
NOT IN HORIZONTAL SECTION
FURNACE
PIPE DIAMETER
TRANSITION IN
VERTICAL SECTION
COMBUSTION AIR PIPE
General
Furnace combustion--air connection must be attached as shown in Fig. 39. Combustion--air intake housing plug may need to be relocated in some applications.
Select 1 vent pipe connection and
NOTE: Select 1 vent pipe connection and
1 combustion-air pipe connection.
AIR
AIR
FLOW
COMBUSTION-
COMBUSTION-
VENT
AIR
VENT
NOTE:
1 combustion-air pipe connection.
VENT
VENT
Fig. 38 -- Combustion Air and Vent Pipe Transition
Location and Elbow Configuration
58MVC
!
CAUTION
UNIT OPERATION HAZARD
Failure to follow this caution may result in intermittent unit operation.
When installing combustion air and vent system of short pipe length, the smallest allowable pipe diameter must be used.
!
CAUTION
UNIT CORROSION HAZARD
Failure to follow this caution may result in unit component damage.
Excessive exposure to contaminated combustion air may result in safety and performance related problems. Combustion air must not be taken from inside structure because that air is frequently contaminated by halogens, which include fluorides, chlorides, bromides, and iodides. These elements are found in aerosols, detergents, bleaches, cleaning solvents, salts, air fresheners, adhesives, paint, and other household products. Locate combustion--air inlet as far as possible from swimming pool and swimming pool pump house.
EXAMPLE: This 80,000 BTUH furnace located in Indianapolis, elevation 650 ft. (198.1M) above sea level, could be installed as a direct Vent / 2--pipe system that requires 3 elbows and 17 ft. (5.1M) of vent pipe, along with 5 elbows and 16 ft. (4.8M) of combustion--air pipe. Table 7 indicates this application would allow a 1--1/2--in. diameter vent pipe, but require a 2--in. diameter combustion air pipe. According to Table 7, 1--1/2--in. diameter pipe is good for 20 ft. (6.0M) with 3 elbows, but only 10 ft. (3.0M) with 5 elbows. Therefore, 2--in. diameter pipe must be used for both vent and combustion--air pipes since the largest required diameter must always be used for both pipes. If the same installation was made in Albuquerque, elevation 5250 ft. (1600.2M) above sea level, installation would require 2-- in. diameter vent pipe and combustion--air pipe. At 5001 to 6000--ft (1524M -- 1828M) elevation, 1--1/2--in. pipe is not allowed with 5 elbows, but 2--in. pipe is good for 68 ft. (20.7M) with 5 elbows are required.
A93034
COMBUSTION-
AIR
UPFLOW DOWNFLOW
COMBUSTION-
AIR
VENT
AIR
FLOW
HORIZONTAL-LEFT DISCHARGE HORIZONTAL-RIGHT DISCHARGE
COMBUSTION-
AIR
FLOW
COMBUSTION-
AIR
VENT
AIR
AIR
FLOW
A96187
Fig. 39 -- Combustion Air and Vent Pipe Connections
NOTE: All pipe joints must be cemented except attachment of
combustion--air pipe to inlet housing connection, since it may be necessary to remove pipe for servicing.
NOTE: A 2--in. diameter pipe must be used within the furnace casing. Make all pipe diameter transitions outside furnace casing.
Attachment of Combustion Air Pipe
NOTE: Combustion air pipe system has the same diameter and
same length as the vent pipe as mentioned in section “Combustion-- --Air and Vent Pipe Diameter.”
1. Determine location of combustion--air intake pipe connection to combustion--air intake housing as shown in Fig. 39 for application.
2. Verify combustion--air intake housing plug fitting is installed in appropriate unused intake housing connection.
3. Install combustion--air pipe grommet (factory--supplied in loose parts bag) into selected furnace casing combustion air pipe hole.
4. Determine the number of combustion air disk halves to be installed in the combustion air intake housing. Insert perforated disk half or assembly (factory supplied in loose parts bag) in intake housing where combustion--air intake pipe will be connected.
5. Insert assembled combustion air inlet pipe into intake housing as shown in Fig. 39.
NOTE: Do not cement combustion air intake pipe permanently to combustion air intake housing since it may be necessary to remove pipe for service of igniter or flame sensor.
6. Drill a 1/8--in. hole in 2--in, combustion air pipe using the hole in intake housing as a guide.
7. Install a field--supplied No. 6 or No. 8 sheet metal screw into combustion air pipe.
34
COMBUSTION AIR
3/8" ID TUBE
3/16"
DRILL
4
TRAP
TO OPEN
8. Install casing hole filler cap (factory--supplied in loose parts
(102mm)
MIN
DRAIN
Fig. 40 -- Intake Housing Plug Fitting Drain
bag) in unused combustion air pipe casing hole.
INTAKE HOUSING
BURNER BOX
COMBUSTION AIR PIPE
A93035
Attachment of Combustion Air Intake Housing Plug Fitting
The combustion--air intake plug fitting must be installed in unused combustion air intake housing. This fitting must be attached by using RTV sealant, or by drilling a 1/8--in. hole in fitting, using hole in intake housing as a guide. Install a field--supplied No. 6 or No. 8 sheet metal screw.
NOTE: DO NOT OVER--TIGHTEN SCREW. Breakage of intake housing or fitting may cause air leakage to occur.
A plugged drain connection has been provided on this fitting for use when moisture is found in combustion air intake pipe and combustion box.
If use of this drain connection is desired, drill out fitting’s tap plug with 3/16--in. drill and connect a field--supplied 3/8--in. tube. This tube should be routed to open condensate drain for furnace and A/C (if used), and should be trapped, as shown in Fig. 40.
NOTE: (Direct Vent / 2--Pipe System ONLY). Moisture in combustion air intake may be a result of improper termination. Ensure combustion air pipe termination is similar to those as shown in Fig. 36 so that it will not be susceptible to area where light snow or others sources of moisture could be pulled in.
Combustion Air Termination -- Ventilated Combustion
Option
Air
Provisions for adequate combustion, ventilation, and dilution air must be provided in accordance with:
S U.S. Installations: Section 9.3 NFPA 54/ANSI Z223.1--2006,
Air for Combustion and Ventilation and applicable provisions of the local building codes.
S Canadian Installations: Part 8 of CAN/CS--B149.1--05. Venting
Systems and Air Supply for Appliances and all authorities having jurisdiction.
Combustion air is piped directly to the burner box on furnace using the same materials used to vent the furnace. (See Table 5.) The combustion air pipe is terminated in an attic or crawl space that is well ventilated with OUTDOOR AIR and is well isolated from the living space or garage. If the furnace is installed in a well ventilated attic, crawlspace or other enclosure, the combustion air pipe can be terminated in the same space.
!
CAUTION
UNIT CORROSION HAZARD
Failure to follow this caution may result in reduced furnace component life.
Air for combustion must not be contaminated by halogen compounds, which include fluoride, chloride, bromide, and iodide. These elements may corrode heat exchangers and shorten furnace life. Air contaminants are found in aerosol sprays, detergents, bleaches, cleaning solvents, salts, air fresheners, and other household products.
The combustion air pipe cannot be terminated in attics or crawlspaces that use ventilation fans designed to operate during the heating season. If ventilation fans are present in these areas, the combustion air pipe must terminate outdoors as a Direct Vent/ 2--Pipe system.
!
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury or death.
The operation of exhaust fans, kitchen ventilation fans, clothes dryers, attic exhaust fans or fireplaces could create a NEGATIVE PRESSURE CONDITION at the furnace. Makeup air MUST be provided for the ventilation devices, in addition to that required by the furnace. Refer to the Carbon Monoxide Poisoning Hazard warning at the end of this section to determine if an adequate amount of make--up air is available.
NOTE: Combustion air pipe must have the same diameter as vent pipe.
An attic or crawlspace may be considered a space that freely communicates with the outdoors provided there are adequate permanent ventilation openings directly to outdoors having free area of at least 1--in. appliances in the space.
NOTE: In determining the free area of an opening, the blocking effect of the louvers, grilles, and screens must be considered. If the free area of a louver or grille design is unknown, it may be assumed that wood louvers have a 20 percent free area, and metal louvers or grilles have a 60 percent free area. Screens, when used, must not be smaller than 1/4--in. mesh. Louvers and grilles must be constructed so they cannot be closed.
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury or death.
Many homes require air to be supplied from outdoors for furnace combustion, ventilation, and dilution of flue gases.
The furnace combustion air supply must be provided in accordance with this instruction manual.
2
/4,000 Btuh of total input rating for all gas
!
WARNING
58MVC
Attic terminations require at least (1) 90 degree elbow, with the open end pointing horizontally or downward. The open end of the elbow must be at least 12--in. (305 mm) above any insulation or other materials. Screen the elbow with a wire mesh screen no smaller than 3/8--inch square. (See Fig. 41.)
35
Crawlspace terminations require the open end of the combustion air intake pipe to point downward. Maintain 3 inches (76 mm) of clearance below the floor joist insulation and 12 inches (305 mm) above the grade. Screen the elbow with a wire mesh screen no smaller than 3/8--in. (10 mm) square. (See Fig. 42 and 43.)
VENT PIPE
General
Furnace vent connection must be attached as shown in Fig. 39.
!
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow the steps outlined below for each appliance connected to the venting system being placed into operation could result in carbon monoxide poisoning or death.
The following steps shall be followed for each appliance connected to the venting system being placed into operation, while all other appliances connected to the venting system are not in operation:
1. Seal any unused openings in venting system.
58MVC
2. Inspect the venting system for proper size and horizontal pitch, as required in the National Fuel Gas Code, ANSI Z223.1--2006/NFPA 54--2006 or the CSA B149.1--05, Natural Gas and Propane Installation Code and these instructions. Determine that there is no blockage or restriction, leakage, corrosion and other deficiencies, which could cause an unsafe condition.
3. As far as practical, close all building doors and windows and all doors between the space in which the appliance(s) connected to the venting system are located and other spaces of the building.
4. Close fireplace dampers.
5. Turn on clothes dryers and any appliance not connected to the venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they are operating at maximum speed. Do not operate a summer exhaust fan.
6. Follow the lighting instructions. Place the appliance being inspected into operation. Adjust the thermostat so appliance is operating continuously.
7. Test for spillage from draft hood equipped appliances at the draft hood relief opening after 5 minutes of main burner operation. Use the flame of a match or candle.
8. If improper venting is observed during any of the above tests, the venting system must be corrected in accordance with the National Fuel Gas Code, ANSI Z223.1--2006/NFPA 54--2006 and/or CSA B149.1--05, Natural Gas and Propane Installation Code.
9. After it has been determined that each appliance connected to the venting system properly vents when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and any other gas--fired burning appliance to their previous conditions of use.
Combustion Air Termination--Direct Vent / 2--Pipe System
Combustion air pipe must terminate outside the structure with the vent pipe as shown in Fig. 36. Follow the clearance requirements shown in Fig. 39. Refer to Vent Termination section for complete details on termination options.
!
WARNING
CARBON MONOXIDE POISONING AND PROPERTY DAMAGE HAZARD
Failure to follow this warning could result in personal injury or death.
Vent pipes must be airtight.
NOTE: A 2--in. (51 mm) diameter pipe must be used within the furnace casing. Make all pipe diameter transitions outside furnace casing per Fig. 38.
The minimum vent pipe length for these furnaces is 5 ft. (1.5M) Short pipe lengths (5--8 ft. or 1.5M--2.4M) may discharge condensate droplets. These condensate droplets may be undesirable. A 12--in. (305 mm) minimum offset pipe section is recommended to reduce excessive condensate droplets from exiting vent pipe outlet. (See Fig. 44.)
Attachment of Vent Pipe
NOTE: Vent pipe system has the same diameter and same length
as combustion air pipe as mentioned in section “Combustion Air Pipe and Vent Pipe Diameter.”
!
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in unit component damage.
Inducer housing outlet cap must be installed and fully seated against inducer housing. Clamp must be tightened to prevent any condensate leakage.
Vent pipe must be installed and fully seated against inducer housing. Clamp must be tightened to prevent any condensate leakage.
1. Determine location of vent pipe connection to inducer housing as shown in Fig. 39 for application.
2. Verify synthetic rubber inducer housing outlet cap and clamp are installed on appropriate unused inducer housing connection and that clamp is tight.
3. Install vent pipe grommet (factory--supplied in loose parts bag) into selected furnace casing vent pipe hole. (See Fig.
28.)
4. Be certain that mating surfaces of inducer housing connection synthetic rubber coupling, and 2--in. diameter vent pipe are clean and dry. Assemble the synthetic rubber vent coupling (with 2 loose clamps) onto inducer housing connection. Insert the 2--in. diameter vent pipe through the synthetic rubber coupling and fully into inducer housing connection until it touches a stop inside the inducer housing outlet. Tighten the screws on both clamps to 15--in lb. of torque.
5. Install casing hole filler cap (factory--supplied in loose parts bag) in unused vent pipe casing hole.
36
Fig. 41 -- Attic Termination
(304.8mm) minimum
58MVC
A06672
(76.2 mm) minimum
(304.8 mm) minimum
A06673
Fig. 42 -- Crawlspace Termination
37
3” (76.2mm) minimum
(304.8mm) minimum
58MVC
A06674
Fig. 43 -- Crawlspace Termination
12 MIN
12 MIN
(305mm)
(305mm)
VENT PIPE
COMBUSTION-AIR PIPE COMBUSTION-AIR PIPE
HORIZONTAL TO ROOF HORIZONTAL TO SIDEWALL
COMBUSTION-AIR PIPE
12 MIN
(304.8mm)
NOTE: A 12-in. (304.8mm) minimum offset pipe section is recommended
with short (5 to 8 ft / 1.5 to 2.5M) vent systems. This recommendation is to reduce excessive condensate droplets.
VENT PIPE
COMBUSTION-AIR PIPE
VENT PIPE
VERTICAL TO SIDEWALLVERTICAL TO ROOF
Fig. 44 -- Short Vent (5 to 8 ft. / 1.5M to 2.4M) System
12 MIN
(304.8mm)
VENT PIPE
A96230
38
NOTE: Starting at furnace, slope vent pipe a minimum of 1/4--in. (6 mm) per linear ft. back toward furnace with no sags between hangers.
VENT TERMINATION
General
Combustion--air (direct Vent / 2--pipe system only) and vent pipe must terminate outside structure, either through sidewall or roof. For vent termination clearance, refer to Fig. 34 for Direct Vent / 2-­Pipe system and Fig. 35 for Ventilated Combustion Air option.
Roof termination is preferred since it is less susceptible to damage or contamination, and it has less visible vent vapors. Sidewall termination require sealing or shielding of building surfaces with a corrosive resistance material due to corrosive combustion products of vent system.
NOTE: (Direct Vent / 2--Pipe system ONLY) A factory accessory termination kit MUST be used. See section “Vent Termination Kit (Direct Vent / 2--Pipe System Only)” in this instruction.
When determining appropriate location for termination, consider the following guidelines:
1. Comply with all clearance requirements stated in Fig. 34 or Fig. 35 per application.
2. Termination or termination kit should be positioned where vent vapors will not damage plants/shrubs or air conditioning equipment.
3. Termination or termination kit should be positioned so that it will not be affected by wind eddy, such as inside building corners, nor by recirculation of flue gases, airborne leaves, or light snow.
4. Termination or termination kit should be positioned where it will not be damaged by or subjected to foreign objects such as stones, balls, etc.
5. Termination or termination kit should be positioned where vent vapors are not objectionable.
Extended Exposed Sidewall Pipes
Sidewall combustion air pipe termination (direct Vent / 2--pipe system only) and vent pipe termination may be extended beyond areashowninFig.36orinFig.37perapplicationinoutside ambient by insulating pipe as indicated in Table 6.
1. Determine combustion air pipe diameter (direct Vent / 2--pipe system only) and vent pipe diameter, as stated above, using total pipe length and number of elbows.
2. Using winter design temperature (used in load calculations), find appropriate temperature for your application and furnace model.
3. Determine required insulation thickness for exposed pipe length(s).
NOTE: Pipe length (ft / M) specified for maximum pipe lengths located in unconditioned spaces cannot exceed total allowable pipe length as specified in Table 6.
Vent Termination Kit (Direct Vent / 2--Pipe System Only)
NOTE: Always refer to the instructions in termination kit for the
latest version. Combustion air and vent pipes MUST terminate outside structure.
A factory accessory termination kit must be installed as shown in Table 8. There are four options of vent/combustion air termination kits available as shown in Table 8.
NOTE: Combustion air pipe must have the same diameter as vent pipe.
Concentric Vent / Combustion Air Termination Kit (Direct Vent / 2--Pipe System
Determine an appropriate location for termination kit using the guidelines provided in section “Vent Termination: General” in this instruction.
1. Cut one 4--in. diameter hole for 2--in. kit, or one 5--in. diameter hole for 3--in. kit.
2. Loosely assemble concentric vent/combustion air termination components together using instructions in kit.
3. Slide assembled kit with rain shield REMOVED through hole.
NOTE: Do not allow insulation or other materials to accumulate inside of pipe assembly when installing it through hole.
Roof terminations--Locate assembly through roof to appropriate height as shown in Fig. 36 or Fig. 37.
Sidewall terminations--Locate assembly through sidewall with rain shield positioned no more than 1--in (25 mm). from wall as shown in Fig. 36 and Fig. 37.
4. Disassemble loose pipe fittings. Clean and cement using same procedures as used for system piping.
5. Check required dimensions as shown.
Only
Two--Pipe Termination Kit (Direct Vent / 2--Pipe System
Determine an appropriate location for termination kit using the guidelines provided in section “Vent Termination: General” in this instruction.
For applications using vent pipe option indicated by dashed lines in Fig. 36, rotate vent elbow 90_ from position shown in Fig. 36.
(Direct Vent / 2--Pipe System ONLY)--When 2 or more 58MVC furnaces are vented near each other, 2 vent terminations may be installed as shown in Fig. 36, but next vent termination must be at least 36 in. (914 mm) away from first 2 terminations. It is important that vent terminations be made as shown in Fig. 36 to avoid recirculation of flue gases.
Only)
1. Cut 2 holes, 1 for each pipe, of appropriate size for pipe size being used.
2. Loosely install elbow in bracket and place assembly on combustion--air pipe. Roof terminations--Loosely install pipe coupling on properly cut vent pipe. Coupling must be positioned so bracket will mount as shown in Fig. 38. For applications using combustion--air pipe option, indicated by dashed lines in Fig. 36, install 90_ street elbow into 90_ elbow, making a U--fitting. A 180_ U--fitting may be used. Sidewall terminations--Install bracket as shown in Fig. 36.
3. Disassemble loose pipe fittings. Clean and cement using same procedures as used for system piping.
4. Check required dimensions as shown in Fig. 36.
58MVC
39
Table 6 – Maximum Allowable Exposed Vent Pipe Length with Insulation in
Winter Design Temperature Ambient*
UNIT SIZE
060
080
100
120
* Pipe length (ft/m) specified for maximum pipe lengths located in unconditioned spaces. Pipes located in unconditioned space cannot exceed total allowable pipe length as specified in Table 7.
58MVC
Insulation thickness based on R value of 3.5 per in.
WINTER DESIGN
TEMPERATURE
20° F / --- 7° C 2 (51) 28 (8.5) 50 (15.2) 56 (17.1) 66 (20.1) 70 (21.3) 0° F / --- 18° C 2 (51) 11 (3.4) 25 (7.6) 29 (8.8) 35 (10.7) 41 (12.5)
--- 2 0 ° F / --- 29 ° C 2 (51) 4 (1.2) 15 (4.6) 18 (5.5) 23 (7.0) 27 (8.2) 20° F / --- 7° C 2 (51) 36 (11.0) 65 (19.8) 70 (21.3) 70 (21.3) 70 (21.3) 0° F / --- 18° C 2 (51) 16 (4.9) 34 (10.4) 39 (11.9) 47 (14.3) 55 (16.8)
--- 2 0 ° F / --- 29 ° C 2 (51) 8 (2.4) 21 (6.4) 25 (7.6) 31 (9.4) 37 (11.3) 20° F / --- 7° C 2 --- 1/2 (64) 42 (12.8) 70 (21.3) 70 (21.3) 70 (21.3) 70 (21.3) 0° F / --- 18° C 2 --- 1/2 (64) 18 (5.5) 38 (11.6) 43 (13.1) 53 (16.2) 61 (18.6)
--- 2 0 ° F / --- 29 ° C 2 --- 1/2 (64) 9 (2.7) 23 (7.0) 27 (8.2) 34 (10.4) 41 (12.5) 20° F / --- 7° C 3 (76) 44 (13.4) 70 (21.3) 70 (21.3) 70 (21.3) 70 (21.3) 0° F / --- 18° C 3 (76) 18 (5.5) 38 (11.6) 44 (13.4) 54 (16.5) 63 (19.2)
--- 2 0 ° F / --- 29 ° C 3 (76) 8 (2.4) 23 (7.0) 27 (8.2) 35 (10.7) 41 (12.5)
MAXIMUM PIPE
DIAMETER IN.
(MM)
INSULATION THICKNESS†
0 3/8 1/2 3/4 1
40
Table 7 – Maximum Allowable Pipe Length -- Ft (M)
ALTITUDE
0 to 2000 (0 to 610)
ALTITUDE
2001 to 3000
(610 to 914)
ALTITUDE
3001 to 4000 (914 to 1219)
ALTITUDE
4001 to 5000 (1219 to 1524)‡
ALTITUDE
5001 to 6000 (1524 to 1829)‡
*See notes on next page.
UNIT SIZE
(BTUH)
60,000
80,000
100,000
120,000
UNIT SIZE
(BTUH)
60,000
80,000
100,000
120,000
UNIT SIZE
(BTUH)
60,000
80,000
100,000
120,000
UNIT SIZE
(BTUH)
60,000
80,000
100,000
120,000
UNIT SIZE
(BTUH)
60,000
80,000
100,000
120,000
D i r e c t V e n t ( 2 --- P i p e O n l y )
Termination
Type
2 P i p e o r 2 --- I n . ( 5 1 ) Concentric
2 P i p e o r 2 --- I n . ( 5 1 ) Concentric
2 P i p e o r 2 --- I n . ( 5 1 ) Concentric
2 P i p e o r 3 --- I n . ( 7 6 ) Concentric
Termination
Type
2 P i p e o r 2 --- I n . ( 5 1 ) Concentric
2 P i p e o r 2 --- I n . ( 5 1 ) Concentric
2 P i p e o r 2 --- I n . ( 5 1 ) Concentric
2 P i p e o r 3 --- I n . ( 7 6 ) Concentric
Termination
Type
2 P i p e o r 2 --- I n . ( 5 1 ) Concentric
2 P i p e o r 2 --- I n . ( 5 1 ) Concentric
2 P i p e o r 2 --- I n . ( 5 1 ) Concentric
2 P i p e o r 3 --- I n . Concentric
Termination
Type
2 P i p e o r 2 --- I n . ( 5 1 ) Concentric
2 P i p e o r 2 --- I n . ( 5 1 ) Concentric
2 P i p e o r 2 --- I n . ( 5 1 ) Concentric
2 P i p e o r 3 --- I n . ( 7 6 ) Concentric
Termination
Type
2 P i p e o r 2 --- I n . ( 5 1 ) Concentric
2 P i p e o r 2 --- I n . ( 5 1 ) Concentric
2 P i p e o r 2 --- I n . ( 5 1 ) Concentric
2 P i p e o r 3 --- I n . ( 7 6 ) Concentric
Pipe Dia
In. (mm)*
1--- 1/2 (38) 50 (15.2) 45 (13.7) 40 (12.9) 35 (10.7) 30 (9.1) 25 (7.6)
2 (51) 70 (21.3) 70 (21.3) 70 ( 21.3) 70 (21.3) 70 (21.3) 70 (21.3)
1--- 1/2 (38) 30 (9.14) 25 (7.6) 20 (6.1) 15 (4.6) 10 (3.0) 5 (1.5)
2 (51) 70 (21.3) 70 (21.3) 70 ( 21.3) 70 (21.3) 70 (21.3) 70 (21.3) 2 (51) 45 (13.7) 40 (12.9) 35 ( 10.7) 30 (9.1) 25 (7.6) 20 (6.1)
2--- 1/2 (64) 70 (21.3) 70 (21.3) 70 (21.3) 70 (21.3) 70 (21.3) 70 (21.3)
2 --- 1 / 2 o n e d i s k 10 (3.0) NA NA NA NA NA
3 (76) one disk 35 (10.7) 30 (9.1) 15 (4.8) NA NA NA
3 (76) one disk† 70 (21.3) 70 ( 21.3) 70 (21.3) 70 (21.3) 70 (21.3) 70 (21.3)
1 2 3 4 5 6
Pipe Dia
In. (mm)*
1--- 1/2 (38) 45 (13.7) 40 (12.9) 35 (10.7) 30 (9.14) 25 (7.6) 20 (6.1)
2 (51) 70 (21.3) 70 (21.3) 70 ( 21.3) 70 (21.3) 70 (21.3) 70 (21.3)
1--- 1/2 (38) 26 (7.9) 21 (6.4) 16 (4.9) 11 (3.4) 6 ( 1.8) NA
2 (51) 70 (21.3) 70 (21.3) 70 ( 21.3) 70 (21.3) 70 (21.3) 70 (21.3) 2 (51) 40 (12.2) 35 (10.7) 30 (9.1) 25 (7.6) 20 (6.1) 15 (4.6)
2--- 1/2 (64) 70 (21.3) 70 (21.3) 70 (21.3) 70 (21.3) 70 (21.3) 70 (21.3)
3 (76) one disk 31 (9.4) 26 (7.9) 12 (3.7) NA NA NA
3 (76) one
disk†
1 2 3 4 5 6
63 (19.2) 62 (18.9) 62 ( 18.9) 61 (18.6) 61 (18.6) 61 (18.6)
Pipe Dia
In. (mm)*
1--- 1/2 (38) 42 (12.8) 37 (11.2) 32 (9.8) 27 (8.2) 22 (6.7)
2 (51) 70 (21.3) 70 (21.3) 70 ( 21.3) 70 (21.3) 70 (21.3) 70 (21.3)
1--- 1/2 (38) 25 (7.6) 20 (6.1) 15 (4.6) 10 (3.0) 5 ( 1.5) NA
2 (51) 70 (21.3) 70 (21.3) 70 ( 21.3) 70 (21.3) 70 (21.3) 70 (21.3) 2 (51) 38 (11.6) 33 (10.1) 28 (8.5) 23 (7.0) 18 (5.5) 13 (4.0)
2--- 1/2 (64) 70 (21.3) 70 (21.3) 70 (21.3) 70 (21.3) 70 (21.3) 70 (21.3)
3 (76) one disk 29 (8.8) 24 (7.3) 10 (3.0) NA NA NA
3 (76) one
disk†
1 2 3 4 5 6
59 (18.0) 59 (18.0) 58 ( 17.8) 57 (17.4) 57 (17.4) 56 (17.0)
Pipe Dia
In. (mm)*
1--- 1/2 (38) 40 (12.2) 35 (10.7) 30 (9.1) 25 (7.6) 20 (6.1) 15 (9.6)
2 (51) 70 (21.3) 70 (21.3) 70 ( 21.3) 70 (21.3) 70 (21.3) 70 (21.3)
1--- 1/2 (38) 23 (7.0) 18 (5.5) 13 (4.0) 8 (2.4) NA NA
2 (51) 70 (21.3) 70 (21.3) 70 ( 21.3) 70 (21.3) 70 (21.3) 68 (20.7)
2 (51) 36 (11.0) 31 (9.4) 26 (7.9) 21 (6.4) 16 (4.8) 11 ( 3.4) 2--- 1/2 (64) 70 (21.3) 70 (21.3) 70 (21.3) 70 (21.3) 70 (21.3) 70 (21.3) 3 (76) one
disk†
1 2 3 4 5 6
56 (17.1) 55 (16.8) 54 ( 16.5) 53 (6.2) 52 (15.8) 52 (15.8)
Pipe Dia
In. (mm)*
1--- 1/2 (38) 37 (11.3) 32 ( 9 .8) 27 (8.2) 22 (6.7) 17 (5.2) 12 (3.7)
2 (51) 70 (21.3) 70 (21.3) 70 ( 21.3) 70 (21.3) 70 (21.3) 70 (21.3) 1--- 1/2 (38) 22 (6.7) 17 (5.2) 12 (3.7) 7 (2.1) NA NA
2 (51) 70 (21.3) 70 (21.3) 70 ( 21.3) 70 (21.3) 68 (20.7) 63 (19.2)
2 (51) 33 (10) 28 (8.5) 23 (7.0) 18 (5.5) 13 (4.0) 8 (2.4) 2--- 1/2 (64) 70 (21.3) 70 (21.3) 70 (21.3) 70 (21.3) 70 (21.3) 70 (21.3) 3 (76) one
disk†
1 2 3 4 5 6
53 (16.2) 52 (15.8) 50 ( 15.2) 49 (14.9) 48 (14.6) 47 (14.3)
NUMBER OF 90_ ELBOWS
NUMBER OF 90_ ELBOWS
NUMBER OF 90_ ELBOWS
17 (5.2)
NUMBER OF 90_ ELBOWS
NUMBER OF 90_ ELBOWS
58MVC
41
Table 7 — Maximum Allowable Pipe Length --- Ft (M) (Continued)
ALTITUDE
6001 to 7000 (1829 to 2134)‡
ALTITUDE
7001 to 8000 (2134 to 2438)‡
58MVC
ALTITUDE
8001 to 9000
(2438 to 2743)‡
ALTITUDE
9001 to 10000
(2743 to 3048)‡
* Disk usage---Unless otherwise stated, use perforated disk assembly (factory---supplied in loose parts bag).
{ Wide radius elbow. } Vent sizing for Canadian installations over 4500 ft. (1370M) above sea l evel are subject to a cceptance by the local authorities having jurisdiction.
NA---Not Allowed; pressure switch will not make.
NOTES:
1. Do not use pipe size greater than those specified in table or incomplete combustion , flame disturbance, or flame sense lockout may occur.
2. Size both the combustion ---air and vent pipe independently, determine the smallest diameter allowed by the table for each pipe, then use the larger diameter for both pipes.
3. Assume two 45_ elbows equal one 90_ elbow. Long radius elbows are desirable and may be required in some cases.
4. Elbows and pipe sections within the furnace casing and at the vent termination should not be included in vent length or elbow count.
5. The minimum pipe length is 5 ft. (1.5M) for all applications.
UNIT SIZE
(BTUH)
60,000
80,000
100,000
120,000
UNIT SIZE
(BTUH)
60,000
80,000
100,000
120,000
UNIT SIZE
(BTUH)
60,000
80,000
100,000
120,000
UNIT SIZE
(BTUH)
60,000
80,000
100,000
120,000
Direct Vent (2--Pipe Only)
Termination
Type
2 P i p e o r 2 --- I n . ( 5 1 ) Concentric
2 P i p e o r 2 --- I n . ( 5 1 ) Concentric
2 P i p e o r 2 --- I n . ( 5 1 ) Concentric
2 P i p e o r 3 --- I n . ( 7 6 ) Concentric
Termination
Type
2 P i p e o r 2 --- I n . ( 5 1 ) Concentric
2 P i p e o r 2 --- I n . ( 5 1 ) Concentric
2 P i p e o r 2 --- I n . ( 5 1 ) Concentric
2 P i p e o r 3 --- I n . ( 7 6 ) Concentric
Termination
Type
2 P i p e o r 2 --- I n . ( 5 1 ) Concentric
2 P i p e o r 2 --- I n . ( 5 1 ) Concentric
2 P i p e o r 2 --- I n . ( 5 1 ) Concentric
2 P i p e o r 3 --- I n . ( 7 6 ) Concentric
Termination
Type
2 P i p e o r 2 --- I n . ( 5 1 ) Concentric
2 P i p e o r 2 --- I n . ( 5 1 ) Concentric
2 P i p e o r 2 --- I n . ( 5 1 ) Concentric
2 P i p e o r 3 --- I n . ( 7 6 ) Concentric
3 (76) one disk† 49 (14.9) 48 ( 14.6) 47 (14.3) 45 (13.7) 44 (13.4) 43 (13.1)
3 (76) one disk† 46 (14.0) 44 ( 13.4) 43 (13.1) 41 (12.5) 40 (12.2) 38 (11.6)
3 (76) one disk† 43 (13.1) 41 ( 12.5) 39 /11.9) 37 (11.3) 35 (10.7) 34 (10.4)
3 (76) one disk† 39 (11.9) 37 ( 11.3) 35 (10.7) 33 (10.1) 31 (9.5) 29 (8.8)
Pipe Dia
In. (mm)*
1--- 1/2 (38) 35 (10.7) 30 ( 9 .1) 25 (7.6) 20 (6.1) 15 (4.6) 10 (3.0)
2 (51) 70 (21.3) 70 (21.3) 68 ( 20.7) 67 (20.4) 66 (20.1) 64 (19.5) 1--- 1/2 (38) 20 (6.1) 15 (4.6) 10 (3.0) 5 (1.5) NA NA
2 (51) 70 (21.3) 70 (21.3) 68 ( 20.7) 67 (20.4)
2 (51) 31 (9.4) 26 (7.9) 21 (6.4) 16 (4.9) 11 (3.4) 6 (1.8) 2--- 1/2 (64) 70 (21.3) 70 (21.3) 68 (20.7) 67 (20.4) 66 (20.1) 64 (19.5)
1 2 3 4 5 6
Pipe Dia
In. (mm)*
1--- 1/2 (38) 32 (9.8) 27 (8.2) 22 (6.7) 17 (5.2) 12 (3.7) 7 (2.1)
2 (51) 66 (20.1) 65 (19.8) 63 ( 19.2) 62 (18.9) 60 (18.3) 59 (18.0) 1--- 1/2 (38) 18 (5.5) 13 (4.0) 8 (2.4) NA NA NA
2 (51) 66 (20.1) 65 (19.8) 63 ( 19.2) 62 (18.9) 57 (17.4) 52 (15.8)
2 (51) 29 (8.8) 24 (7.3) 19 (5.8) 14 (4.3) 9 (2.7) NA 2--- 1/2 (64) 66 (20.1) 65 (19.8) 63 (19.2) 62 (18.9) 60 (18.3) 59 (18.0)
1 2 3 4 5 6
Pipe Dia
In. (mm)*
1--- 1/2 (38) 30 (9.1) 25 (7.6) 20 (6.1) 15 (4.6) 10 (3.0) 5 (1.5)
2 (51) 62 (18.9) 60 (17.8) 58 ( 17.7) 56 (17.1) 55 (16.8) 53 (16.2) 1--- 1/2 (38) 17 (5.2) 12 (3.1) 7 (2.1) NA NA NA
2 (51) 62 (18.9) 60 (18.3) 58 ( 17.7) 56 (17.1) 51 (15.5) 46 (14.0)
2 (51) 27 (8.2) 22 (6.7) 17 (5.2) 12 (3.7) 7 (2.1) NA 2--- 1/2 (64) 62 (18.9) 60 (18.3) 58 (17.7) 56 (17.1) 55 (16.8) 53 (16.2)
1 2 3 4 5 6
Pipe Dia
In. (mm)*
1--- 1/2 (38) 27 (8.2) 22 (6.7) 17 (5.2) 12 (3.7) 7 ( 2.1) NA
2 (51) 57 (17.4) 55 (16.8) 53 ( 16.2) 51 (15.5) 49 (14.9) 47 (14.3) 1--- 1/2 (38) 15 (4.6) 10 (3.0) 5 (1.5) NA NA NA
2 (51) 57 (17.4) 55 (16.8) 53 ( 16.2) 51 (15.5) 46 (14.0) 41 (12.5)
2 (51) 24 (7.3) 19 (5.8) 14 (4.3) 9 (2.7) NA NA 2--- 1/2 (64) 57 (17.4) 55 (16.8) 53 (16.2) 51 (15.5) 49 (14.9) 47 (14.3)
1 2 3 4 5 6
NUMBER OF 90_ ELBOWS
NUMBER OF 90_ ELBOWS
NUMBER OF 90_ ELBOWS
NUMBER OF 90_ ELBOWS
62
(18.9)
57 (17.4)
42
Tabl e 8 – Vent Termination Kit for Direct Vent/2-Pipe System
DIRECT VENT (2 -PIPE) TERMINATION KIT TERMINATION SYSTEM DIAM. OF COMBUSTION AIR AND VENT
2-in. (51 mm) Concentric Vent Kit Single Penetration of Wall or Roof 1, 1--- 1/2, 2, or 2--- 1/2 (25, 38, 51, 64 mm)
3-in. (76 mm)Concentric Vent Kit Single Penetration of Wall or Roof 2- -- 1/2, 3 or 4 (64, 76, 102 mm)
2-in. (51 mm)Termination Bracket Kit 2--- Pipe Termination System 1, 1 ---1/2 or 2 (25, 38, 51mm)
3-in. (76 mm) Termination Bracket Kit 2--- Pipe Termination System 2 --- 1/2, 3 or 4 (64, 76, 102 mm)
Multi--venting and Vent Terminations
When 2 or more 58MVC Furnaces are vented near each other, each furnace must be individually vented. NEVER common vent or breach vent 58MVC furnaces.
OPEN STAND
PIPE FOR
A/C OR
HUMIDIFIER
DRAIN
TEE
Application
The furnace, A/C, and humidifier drains may be combined and drained together. The A/C drain must have an external, field--supplied trap prior to the furnace drain connection. All drain connections (furnace, A/C, or humidifier) must be terminated into an open or vented drain as close to the respective equipment as possible to to prevent siphoning of the equipment’s drain.
CONDENSATE TRAP
WIRE TIE(S)
PIPES --- IN (mm)
58MVC
TO OPEN DRAIN
A94054
Fig. 45 -- Example of Field Drain Attachment
CONDENSATE DRAIN
General
Condensate trap is shipped installed in the blower shelf and factory connected for UPFLOW applications. Condensate trap must be RELOCATED for use in DOWNFLOW and HORIZONTAL applications.
Condensate trap MUST be used for all applications. An external trap is not required when connecting the field drain to
this condensate trap. The field drain connection (condensate trap or drain tube coupling)
is sized for 1/2--in. CPVC, 1/2--in. PVC, or 5/8--in. ID tube connection.
Drain pipe and fittings must conform to ANSI standards and ASTM D1785, D2466, or D2846. CPVC or PVC cement must conform to ASTM D2564 or F493. Primer must conform to ASTM F656. In Canada, use CSA or ULC certified schedule 40 CPVC or PVC drain pipe, fittings, and cement.
When a condensate pump is required, select a pump which is approved for condensing furnace applications. To avoid condensate spillage, select a pump with an overflow switch.
Furnace condensate is mildly acidic, typically in the pH range of
3.2 to 4.5. Due to corrosive nature of this condensate, a condensate pH neutralizing filter may be desired. Check with local authorities to determine if a pH neutralizer is required.
(3 WRAPS MINIMUM)
See Fig. 45 for example of possible field drain attachment using 1/2--in. CPVC or PVC tee for vent and A/C or humidifier drain connection.
Outdoor draining of the furnace is permissible if allowed by local codes. Caution should be taken when freezing ambient may freeze drain pipe and prohibit draining.
PERSONAL INJURY HAZARD
Failure to follow this warning could result in personal injury or death.
Caution should be taken to prevent draining where slippery conditions may cause personal injuries. Excessive condensate draining may cause saturated soil conditions which may result in damage to plants.
HEAT TAPE
Fig. 46 -- Condensate Trap Heat Tape
!
WARNING
A93036
Condensate Drain Protection
Freezing condensate left in condensate trap and drain line may cause cracks, and possible water damage may occur. If freeze protection is required, use condensate freeze protection accessory or equivalent 3 to 6 watt per ft. (.3M) at 120v and 40_F(4.4_ C) self--regulating, shielded, and waterproof heat tape. See Installation Instructions supplied with accessory or heat tape manufacturer’s recommendations.
1. Fold heat tape in half and wrap on itself 3 times.
43
2. Locate heat tape between sides of condensate trap back. (See Fig. 46.)
3. Use wire ties to secure heat tape in place. Wire ties can be positioned in notches of condensate trap sides. (See Fig.
46.)
4. Wrap field drain pipe with remaining heat tape, approximately 1 wrap per ft. (.3M).
5. When using field--supplied heat tape, follow heat tape manufacturer’s instructions for all other installation guidelines.
START--UP, ADJUSTMENT AND SAFETY
CHECK
Step 1 — General
1. Furnace must have a 115--v power supply properly connected and grounded.
NOTE: Proper polarity must be maintained for 115--v wiring. If polarity is incorrect, control status indicator light flashes rapidly and furnace does not operate.
58MVC
2. Thermostat wire connections at terminals R, W/W1, G, and Y/Y2 must be made at 24--v terminal block on furnace control.
3. Natural gas service pressure must not exceed 0.5 psig (14-­in. wc), but must be no less than 0.16 psig (4.5--in. wc).
4. Blower access panel must be in place to complete 115--v electrical circuit to furnace.
!
CAUTION
UNIT MAY NOT OPERATE
Failure to follow this caution may result in intermittent unit operation or performance satisfaction.
These furnaces are equipped with a manual reset limit switch in burner box. This switch opens and shuts off power to the gas valve if an overheat condition (flame rollout) occurs in burner enclosure. Correct inadequate combustion--air supply or improper venting condition before resetting switch. DO NOT jumper this switch.
Before operating furnace, check flame rollout manual reset switch for continuity. If necessary, press button to reset switch.
Step 2 — Select Setup Switch Positions
Air Conditioning (A/C) Setup Switches
The air conditioning setup switches are used to match furnace airflow to cooling unit used.
To set the desired cooling airflow:
1. Remove main furnace door and blower access panel.
2. Locate A/C setup switches on furnace control. (See Fig. 33.)
3. Determine air conditioning tonnage used.
4. Use Fig. 47 or wiring schematic to determine proper setup position of A/C switches. (See Fig. 48 and Fig. 49.)
NOTE: Excessive airflow caused by improper A/C switch setup may cause condensate blow--off in cooling mode.
5. Replace main furnace door and blower access panel.
NOTE: EAC--1 terminal is energized whenever blower operates. HUM terminal is only energized when blower is energized in heating.
Continuous Fan (CF) Setup Switches
The CF setup switches are used to select desired airflow when thermostat is in continuous fan mode or to select low--cooling airflow for two--speed cooling units. This setup feature allows
continuous fan airflow or low--cooling airflow to be adjusted. To set desired continuous fan airflow or low--cooling airflow:
1. Remove main furnace door and blower access panel.
2. Locate CF setup switches on furnace control. (See Fig. 33.)
3. Determine desired continuous fan airflow or low--cooling airflow.
4. Use Fig. 47 or wiring schematic to determine proper setup position of CF switches. (See Fig. 48 and Fig. 49.)
5. Replace main furnace door and blower access panel.
AIR CONDITIONING (A/C) OR CONTINUOUS-FAN (CF)
BASED ON 350 CFM/TON (SETUP SWITCH SW1-5 OFF)
MODEL
SIZE
060, 3.5T080
5T080, 100
120
BASED ON 400 CFM/TON (SETUP SWITCH SW1-5 ON)
MODEL
SIZE
060, 3.5T080
5T080, 100
120
1. DEFAULT A/C AIRFLOW WHEN A/C SWITCHES ARE IN OFF POSITION
2. DEFAULT CONT. FAN AIRFLOW WHEN CF SWITCHES ARE IN OFF POSITION
3. SWITCH POSITIONS ARE ALSO SHOWN ON FURNACE WIRING DIAGRAM
AIRFLOW SELECTION CHART
SETUP SWITCH SW3 POSITIONS
525
DEF.
DEF.
DEF.
DEF.
DEF.
DEF.
700
2
875
700
2
700 875
SETUP SWITCH SW3 POSITIONS
800
600
2
1000
800
2
800 1000
875
1050
1050
2
1000
1200
1200
2
1050
1225
1225
1200
1400
1400
1225
1225
1750
1750
1400
2000
2000
1225
1750
1
2100
1
1400
2000
1
2100
1
A07424
1
1400
1400
1400
1
1600
1600
Fig. 47 -- A/C or CF Airflow Selection Chart Based on 350
and 400 CFM/Ton
Setup Switches (SW1)
The furnace control has 8 setup switches that may be set to meet the application requirements. To set these setup switches for the appropriate requirement:
1. Remove main furnace door and blower access panel.
2. Locate setup switches on furnace control. (See Fig. 33.)
3. See Table 9 for setup switch description. (See Fig. 48 and Fig. 49.)
4. Replace main furnace door and blower access panel.
NOTE: If a bypass humidifier is used, setup switch SW1--3 (Low Heat Rise Adjust) should be in ON position. This compensates for the increased temperature in return air resulting from bypass.
NOTE: If modulating dampers are used, blower motor automatically compensates for modulating dampers.
Additional Setup Switches (SW4)
The furnace control has 3 additional setup switches labeled SW4. (See Fig. 33.) Setup switch SW4--2 can be used to lock the furnace into medium heat. When setup switch SW4--2 is ON the furnace will remain at medium heat until W/W1 is de--energized to end a heating cycle or when both W/W1 and W2 are energized. When both W/W1 and W2 are energized the furnace will run at high heat. The other 2 setup switches are currently not used for anything. When setup switch SW4--2 is ON it will over ride setup switch SW1--2 if it is ON. To activate setup switch SW4--2:
1. Remove main furnace door and blower access panel.
2. Locate setup switch SW4 on furnace control. (See Fig. 33.)
44
3. See Table 5 for setup switch description. (See Fig. 40 and Fig. 49.)
4. Replace main furnace door and blower access panel.
Prime Condensate Trap with Water
!
UNIT OPERATION HAZARD
Failure to follow this caution may result in intermittent unit operation or performance satisfaction.
Condensate trap must be PRIMED or proper draining may not occur. The condensate trap has two internal chambers which can ONLY be primed by pouring water into the inducer drain side of condensate trap.
CAUTION
A04001
Fig. 48 -- Example of Setup Switch in Off Position
58MVC
45
58MVC
A06677
Fig. 49 -- Wiring Diagram
46
58MVC
A99118
Fig. 50 -- Inducer Housing Drain Tube
Fig. 51 -- Filling Condensate Trap
Table 9 – Furnace Setup Switch Description
SETUP SWITCH
NO.
S W 1 --- 1 Status Code Recovery OFF
S W 1 --- 2
S W 1 --- 3 Low/Medium Heat Rise Adjust OFF
S W 1 --- 4
S W 1 --- 5 CFM per ton adjust OFF Turn ON for 400 CFM per ton. Turn OFF for 350 CFM per ton.
S W 1 --- 6 Component Self Test OFF
S W 1 --- 7
a n d S W 1 --- 8
S W 4 --- 2
SWITCH NAME
Low Heat Only
(Adaptive Heat Mode when
OFF)
Comfort/Efficiency Adjust-
ment
Blower OFF delay ON or OFF
Medium Heat Only (Adaptive
Heat Mode when OFF)
NORMAL
POSITION
OFF
ON
OFF
DESCRIPTION OF USE
Turn ON to retrieve up to 7 stored status codes for troubleshooting assistance when R thermostat lead is disconnected.
W h e n S W 1 --- 2 a n d S W 4 --- 2 a r e O F F a l l o w s s t e p --- m o d u l a t i n g o p e r a ­tion with a single stage thermostat. Turn ON when using 2 stage thermostat to allow Low Heat operation when R to W/W1 closes and High Heat operation when R to W/W1 and W2 close. Turn ON to increase Low and Medium Heat airflow by 18 percent. This compensates for increased return air temperature caused with bypass humidifier. This also increases the Low and Medium Heat inducer speed 15 percent
Turn ON to decrease Low Heat airflow 9 percent, Medium Heat airflow 7 percent, and High Heat airflow 15 percent for maximum comfort.
Turn ON to initiate Component Self T es t for troubleshooting assistance when R thermostat lead is disconnected. Turn OFF when Self Test is completed.
Blower Off Delay time. See Table 6.
W h e n S W 1 --- 2 a n d S W 4 --- 2 a r e O F F a l l o w s s t e p --- m o d u l a t i n g o p e r a ­tion with a single stage thermostat. Turn ON when using 2 stage thermostat to allow Medium Heat operation when R to W/W1 closes and High Heat operation when R to W/W1 and W2 close.
A01050
1. Remove upper inducer housing drain connection cap. (See Fig. 50.)
2. Connect field--supplied 1/2--in. ID tube to upper inducer housing drain connection.
3. Insert field--supplied funnel into tube.
4. Pour 1 quart of water into funnel/tube. Water should run through inducer housing, overfill condensate trap, and flow into open field drain. (See Fig. 51.)
47
Purge Gas Lines
If not previously done, purge the lines after all connections have been made and check for leaks.
!
WARNING
FIRE AND EXPLOSION HAZARD
Failure to follow this warning could result in a fire, explosion, personal injury, or death.
Never purge a gas line into a combustion chamber. Never test for gas leaks with an open flame. Use a commercially available soap solution made specifically for the detection of leaks to check all connections.
Step 3 — Sequence of Operation
!
58MVC
UNIT OPERATION HAZARD
Failure to follow this caution may result in intermittent unit operation.
Furnace control must be grounded for proper operation, or control will lock out. Control is grounded through green/yellow wire routed to gas valve and burner box screw.
Using the schematic diagram (See Fig. 48), follow the sequence of operation through the different modes. Read and follow the wiring diagram very carefully. ! !
NOTE: If a power interruption occurs during a call for heat (W/W1 or W/W1--and--W2), the control will start a 90--second blower--only ON period two seconds after power is restored, if the thermostat is still calling for gas heating. The amber LED light will flash code 12 during the 90--second period, after which the LED will be ON continuous, as long as no faults are detected. After the 90--second period, the furnace will respond to the thermostat normally.
The blower door must be installed for power to be conducted through the blower door interlock switch ILK to the furnace control CPU, transformer TRAN, inducer motor IDM, blower motor BLWM, hot surface igniter HSI, throttling valve TV, and gas valve GV.
Single--Stage Thermostat and Step--Modulating Heating (Adaptive
See Fig. 29 or Fig. 59 for thermostat connections. NOTE: Low--heat only switch SW1--2 selects the low--heat only
operation mode when ON. Medium--heat only switch SW4--2 selects medium--heat only operation mode when ON. If both switches are ON the furnace control will default to medium--heat. If either or both switches are ON the furnace control will operate at two--stages only as referenced in Section 2 below. If both switches are OFF the furnace control will operate in the adaptive heating mode in response to a call for heat. (See Fig. 33.) When the W2 thermostat terminal is energized it will always cause high--heat operation as long as the R to W circuit is closed, regardless of the setting of the low--heat or medium--heat only switches.
This furnace can operate as a step--modulating furnace with a single--stage thermostat because the furnace control CPU includes a programmed adaptive sequence of controlled operation, which selects low--heat, medium--heat, or high--heat operation. This selection is based upon the stored history of the length of previous gas--heating periods of the single--stage thermostat.
The furnace will start up in either medium--, or high--heat. The furnace will operate in low--heat after starting and operating for 1
CAUTION
Mode)
minute at medium--heat before transitioning to low--heat. The furnace control CPU determines the combined low--heat and medium--heat on--time (from 0 to 16 minutes) which is permitted before switching to high heat.
If the power is interrupted, the stored history is erased and the furnace control CPU will select medium--heat for 1 minute, low--heat for 15 minutes and then switch to high--heat, as long as the thermostat continues to call for heat. Subsequent selection is based on stored history of the thermostat cycle times.
The wall thermostat ”calls for heat”, closing the R to W circuit. The furnace control CPU performs a self--check, verifies the low--heat and medium--heat pressure switch contacts LPS and MPS are open, then de--energizes the HPSR relay to close the NC contact.
1. Inducer Prepurge Period -- The furnace control CPU turns on inducer motor IDM and slowly increases the inducer motor speed. After the low--heat pressure switch LPS closes the furnace control CPU continues to increase the inducer motor speed until the medium--heat pressure switch MPS closes. When the medium--heat pressure switch MPS closes, throttling valve TV is energized, inducer motor RPM is noted by the furnace control CPU, and a 25--second prepurge period begins. The RPM is used to evaluate vent system resistance. This evaluation is then used to determine the required RPM necessary to operate the inducer motor during medium--heat prepurge, the first minute of medium--heat mode, and low--heat mode.
NOTE: The heat cycle can start in either high-- or medium--heat. If a high--heat cycle is initiated, the furnace control CPU will continue to increase the inducer motor speed after the medium--heat pressure switch MPS closes. When the medium--heat pressure switch closes, throttling valve TV is energized, inducer motor RPM is noted by the furnace control CPU, and a 25--second prepurge period begins. The RPM is used to evaluate vent system resistance. This evaluation is then used to determine the required RPM necessary to operate the inducer motor in high--heat pre--purge, and high--heat mode.
2. Igniter Warm--Up — At the end of the prepurge period, the Hot--Surface Igniter HSI is energized for a 17--second igniter warm--up period.
3. Trial--For--Ignition Sequence — When the igniter warm--up period is completed the main gas valve relay contact GVR closes to energize the gas valve solenoid GV--M. The gas valve solenoid GV--M permits gas flow to the burners where it is ignited. Five seconds after the GVR closes, a 2-­second Flame--Proving period begins. The HSI igniter will remain energized until flame is sensed or until the 2--second flame proving period begins. If the furnace control CPU selects high--heat operation, the high--heat gas valve solenoid GV--HI is energized when the high--heat pressure switch HPS closes.
4. Flame--Proving — When the burner flame is proved at the flame--proving sensor electrode FSE, the furnace control CPU begins the blower--ON delay period and continues to hold the gas valve GV--M open. If the burner flame is not proved within two seconds, the furnace control CPU will close the gas valve GV--M, and the furnace control CPU will repeat the ignition sequence for up to three more Trials--For--Ignition before going to Ignition--Lockout. Lockout will be reset automatically after three hours, by momentarily interrupting 115 vac power to the furnace, or by interrupting 24 vac power at SEC1 or SEC2 to the furnace control CPU (not at W/W1, G, R, etc.). If flame is proved when flame should not be present, the furnace control CPU will lock out of Gas--Heating mode and operate the inducer motor IDM at full speed until flame is no longer proved.
48
5. Inducer Speed Change — If the cycle starts in medium heat, the furnace control CPU reduces the inducer speed slightly after flame sense. If cycle starts in high--heat, the furnace control CPU increases the inducer speed after flame sense. The reduction in speed in medium--heat is to optimize combustion for maximum efficiency.
6. Blower--On delay — If the burner flame is proven the blower--ON delay for medium--heat and high--heat are as follows: Medium--heat — 60 seconds after the gas valve GV--M is opened the blower motor BLWM is turned ON at low-- or medium--heat airflow. High--heat — 35 seconds after the gas valve GV--M is opened the BLWM is turned ON at high--heat airflow. Simultaneously, the humidifier terminal HUM and electronic air cleaner terminal EAC--1 are energized and remain energized throughout the heating cycle.
7. Switching from Medium-- to Low--Heat — If the furnace control switches from medium--heat to low--heat, the furnace control will turn the blower ON at low--heat airflow, energize the HPSR relay to open the NC contact, and slowly decrease the inducer motor speed. When the HPSR relay is energized and the NC contact opens the throttling valve TV is deenergized and the gas flow reduces to low--heat rate. Switching from Low-- to Medium--Heat — If the furnace control CPU switches from low--heat to medium--heat, the furnace control CPU will de--energize the HPSR relay to close the NC contact and slowly increase the inducer motor speed until the medium--heat pressure switch MPS closes. When the medium--heat pressure switch MPS closes, the throttling valve solenoid TV is energized and the inducer motor RPM is noted by the furnace control CPU. The RPM is used to evaluate vent system resistance. This evaluation is then used to determine the required RPM necessary to operate the inducer motor in medium--heat and high--heat mode. The blower motor BLWM will transition to medium--heat airflow five seconds after the furnace control CPU switches from low--heat to medium--heat. Switching from Low-- to High--Heat — If the furnace control CPU switches from low--heat to high--heat, the furnace control CPU will de--energize the HPSR relay to close the NC contact and slowly increase the inducer motor speed until the medium--heat pressure switch MPS closes. When the medium--heat pressure switch MPS closes, the throttling valve solenoid TV is energized and the inducer motor RPM is noted by the furnace control CPU. The RPM is used to evaluate vent system resistance. This evaluation is then used to determine the required RPM necessary to operate the inducer motor in medium-- and high--heat mode. The blower motor BLWM will transition to high--heat airflow five seconds after the furnace control CPU switches from low--heat to high--heat. As the inducer RPM gradually increases the high--heat pressure switch HPS closes and the gas valve solenoid GV--HI is energized. Switching from Medium-- to High--Heat — If the furnace control CPU switches from medium--heat to high--heat, the furnace control CPU will gradually increase the inducer motor speed to the required high--heat RPM. The blower motor BLWM will transition to high--heat airflow five seconds after the furnace control CPU switches from medium--heat to high heat. As the inducer RPM gradually increases the high--heat pressure switch HPS closes and the gas valve solenoid GV--HI is energized. Switching from High-- to Medium-- or Low--Heat —The furnace control CPU will not switch from high--heat to medium-- or low--heat while the thermostat R to W circuit is closed when using a single--stage thermostat.
8. Blower--Off Delay — When the thermostat is satisfied, the R to W circuit is opened, de--energizing the gas valve
GV--M, stopping gas flow to the burners, and de--energizing the throttling valve TV, and humidifier terminal HUM. The inducer motor IDM will remain energized for a 15--second post--purge period. The blower motor BLWM and air cleaner terminal EAC--1 will remain energized at low--heat airflow or transition to low--heat airflow for 90, 120, 150, or 180 seconds (depending on selection at blower--OFF delay switches). The furnace control CPU is factory--set for a 120--second blower-- OFF delay.
Two--Stage Thermostat and Two--Stage Low / High Heating
See Fig. 58 for thermostat connections. NOTE: In this mode the low--heat only switch SW1--2 must be
ON to select the low--heat only operation mode in response to closing the thermostat R to W1 circuit. Closing the thermostat R to W1--and--W2 circuits always causes high--heat operation, regardless of the setting of the low--heat only switch.
The furnace will start up in either medium--, or high--heat. The furnace will operate in low--heat after starting and operating for 1 minute at medium--heat before transitioning to low--heat.
The wall thermostat ”calls for heat”, closing the R to W1 circuit for low--heat or closing the R to W1--and--W2 circuits for high--heat. The furnace control performs a self--check, and verifies the low--heat and medium--heat pressure switch contacts LPS and MPS are open, then de--energizes the HPSR relay to close the NC contact.
The start up and shut down functions and delays described above apply to the 2--stage low/high heating mode as well, except for switching from high-- to low--heat.
1. Switching from High-- to Low--Heat — If the thermostat
R to W2 circuit opens, and the R to W1 circuit remains closed, the furnace control CPU will gradually decrease the inducer motor speed to the required medium--heat RPM. When the inducer motor IDM reduces pressure sufficiently, the high heat pressure switch HPS will open and the high--heat gas valve solenoid GV--HI will be de--energized. The gas valve solenoid GV--M will remain energized as long as the low--heat pressure switch LPS remains closed. When the inducer motor speed gets within 15% of the required medium--heat RPM the furnace control CPU will start a 5 second blower airflow change delay. After the 5 second blower airflow change delay is completed the blower airflow will transition to low--heat airflow. At this point the furnace control CPU will energize the HPSR relay to open the NC contact and slowly decrease the inducer motor speed to the required low--heat RPM. When the HPSR relay is energized and the NC contact opens the throttling valve TV is de--energized and the gas flow reduces to low--heat rate. When the inducer motor IDM reduces pressure sufficiently, the medium--heat pressure switch MPS will open.
Two--Stage Thermostat and Two--Stage Medium/High Heating
See Fig. 58 for thermostat connections. NOTE: In this mode the medium--heat only switch SW4--2 must
be ON to select the medium--heat only operation mode in response to closing the thermostat R to W1 circuit. Closing the thermostat R to W1--and--W2 circuits always causes high--heat operation, regardless of the setting of the medium--heat only switch.
The wall thermostat ”calls for heat”, closing the R to W1 circuit for medium--heat or closing the R to W1--and--W2 circuits for high--heat. The furnace control performs a self--check, and verifies the low--heat and medium--heat pressure switch contacts LPS and MPS are open, then de--energizes the HPSR relay to close the NC contact.
58MVC
49
The start up and shut down functions and delays described above apply to the 2--stage medium/high heating mode as well, except for switching from high-- to medium--heat.
1. Switching from High-- to Medium--Heat —Ifthe thermostat R to W2 circuit opens, and the R to W1 circuit remains closed, the furnace control CPU will gradually decrease the inducer motor speed to the required medium--heat RPM. When the inducer motor IDM reduces pressure sufficiently, the high heat pressure switch HPS will open and the high--heat gas valve solenoid GV--HI will be de--energized. The gas valve solenoid GV--M will remain energized as long as the low--heat pressure switch LPS remains closed. When the inducer motor speed gets within 15% of the required medium--heat RPM the furnace control CPU will start a 5 second blower airflow change delay. After the 5 second blower airflow change delay is completed the blower airflow will transition to medium--heat airflow.
Cooling Mode
The thermostat “calls for cooling.”
58MVC
2. Single--Speed Cooling See Fig. 29 for thermostat connections. The thermostat closes the R to G--and--Y circuits. The R to Y circuit starts the outdoor unit, and the R to G--and--Y/Y2 circuits start the furnace blower motor BLWM on cooling airflow. Cooling airflow is based on the A/C selection shown in Fig. 47. The electronic air cleaner terminal EAC--1 is energized with 115 vac when the blower motor BLWM is operating. When the thermostat is satisfied, the R to G--and--Y circuits are opened. The outdoor unit will stop, and the furnace blower motor BLWM will continue operating at cooling airflow for an additional 90 seconds. Jumper Y/Y2 to DHUM to reduce the cooling off--delay to 5 seconds. (See Fig. 33.)
3. Single--Stage Thermostat and Two--Speed Cooling (Adaptive Mode) See Fig. 59 for thermostat connections. This furnace can operate a two--speed cooling unit with a single--stage thermostat because the furnace control CPU includes a programmed adaptive sequence of controlled operation, which selects low--cooling or high--cooling operation. This selection is based upon the stored history of the length of previous cooling period of the single--stage thermostat.
NOTE: The air conditioning relay disable jumper ACRDJ must be connected to enable the adaptive cooling mode in response to a call for cooling. (See Fig. 33.) When in place the furnace control CPU can turn on the air conditioning relay ACR to energize the Y/Y2 terminal and switch the outdoor unit to high--cooling.
The furnace control CPU can start up the cooling unit in either low-- or high--cooling. If starting up in low--cooling, the furnace control CPU determines the low--cooling on--time (from 0 to 20 minutes) which is permitted before switching to high--cooling.
If the power is interrupted, the stored history is erased and the furnace control CPU will select low--cooling for up to 20 minutes and then energize the air conditioning relay ACR to energize the Y/Y2 terminal and switch the outdoor unit to high--cooling, as long as the thermostat continues to call for cooling. Subsequent selection is based on stored history of the thermostat cycle times.
The wall thermostat “calls for cooling”, closing the R to G and-- Y circuits. The R to Y1 circuit starts the outdoor unit on low--cooling speed, and the R to G--and--Y1 circuits starts the furnace blower motor BLWM at low--cooling airflow which is the true on--board CFselectionasshowninFig.47. If the furnace control CPU switches from low--cooling to high cooling, the furnace control CPU will energize the air conditioning relay ACR. When the air conditioning relay ACR is energized the
R to Y1--and--Y2 circuits switch the outdoor unit to high--cooling speed, and the R to G--and--Y1-- and--Y/Y2 circuits transition the furnace blower motor BLWM to high--cooling airflow. High--cooling airflow is based on the A/C selection shown in Fig.
47. NOTE: When transitioning from low--cooling to high--cooling the
outdoor unit compressor will shut down for 1 minute while the furnace blower motor BLWM transitions to run at high--cooling airflow.
The electronic air cleaner terminal EAC--1 is energized with 115 vac whenever the blower motor BLWM is operating.
When the thermostat is satisfied, the R to G--and--Y circuit are opened. The outdoor unit stops, and the furnace blower BLWM and electronic air cleaner terminal EAC--1 will remain energized for an additional 90 seconds. Jumper Y1 to DHUM to reduce the cooling off--delay to 5 seconds. (See Fig. 33.)
4. Two--Stage Thermostat and Two--Speed Cooling See Fig. 58 for thermostat connections.
NOTE: The air conditioning relay disable jumper ACRDJ must be disconnected to allow thermostat control of the outdoor unit staging. (See Fig. 33.)
The thermostat closes the R to G--and--Y1 circuits for low cooling or closes the R to G--and--Y1--and--Y2 circuits for high cooling. The R to Y1 circuit starts the outdoor unit on low cooling speed, and the R to G--and--Y1 circuit starts the furnace blower motor BLWM at low--cooling airflow which is the true on--board CF selection as shown in Fig. 47. The R to Y1--and--Y2 circuits start the outdoor unit on high--cooling speed, and the R to G--and--Y/Y2 circuits start the furnace blower motor BLWM at high--cooling airflow. High--cooling airflow is based on the A/C selection shown in Fig. 47.
The electronic air cleaner terminal EAC--1 is energized with 115 vac whenever the blower motor BLWM is operating.
When the thermostat is satisfied, the R to G--and--Y1 or R to G--and--Y1--and--Y2 circuits are opened. The outdoor unit stops, and the furnace blower BLWM and electronic air cleaner terminal EAC--1 will remain energized for an additional 90 seconds. Jumper Y1 to DHUM to reduce the cooling off--delay to 5 seconds. (See Fig. 33.)
Thermidistat Mode
See Fig. 52--55 for thermostat connections. The dehumidification output, DHUM on the Thermidistat should
be connected to the furnace control thermostat terminal DHUM. When there is a dehumidify demand, the DHUM input is activated, which means 24 vac signal is removed from the DHUM input terminal. In other words, the DHUM input logic is reversed. The DHUM input is turned ON when no dehumidify demand exists. Once 24 vac is detected by the furnace control on the DHUM input, the furnace control operates in Thermidistat mode. If the DHUM input is low for more than 48 hours, the furnace control reverts back to non--Thermidistat mode.
The cooling operation described above also applies to operation with a Thermidistat. The exceptions are listed below:
1. Low cooling – When the R to G--and--Y1 circuit is closed and there is a demand for dehumidification, the furnace blower motor BLWM will drop the blower airflow to 86% of low cooling airflow which is the true on--board CF selectionasshowninFig.47.
2. High cooling – When the R to G--and Y/Y2 circuit is closed and there is a demand for dehumidification, the furnace blower motor BLWM will drop the blower airflow to 86% of high--cooling airflow. High--cooling airflow is basedontheA/CselectionshowninFig.47.
3. Cooling off--delay – When the “call for cooling” is satisfied and there is a demand for dehumidification, the cooling
50
blower--off delay is decreased from 90 seconds to 5 seconds.
Super Dehumidify Mode
Super--Dehumidify mode can only be entered if the furnace control is in the Thermidistat mode and there is a demand for dehumidification. The cooling operation described in item 4. above also applies to operation with a Thermidistat. The exceptions are listed below:
1. Low cooling –WhentheRtoY1circuitisclosed,RtoG
circuit is open, and there is a demand for dehumidification, the furnace blower motor BLWM will drop the blower airflow to 65% of low--cooling airflow for a maximum of 10 minutes each cooling cycle or until the R to G circuit closes or the demand for dehumidification is satisfied. Low--cooling airflow is the true on--board CF selection as shown in Fig. 47.
2. High cooling – When the R to Y/Y2 circuit is closed, R to
G circuit is open, and there is a demand for dehumidification, the furnace blower motor BLWM will drop the blower airflow to 65% of high--cooling airflow for a maximum of 10 minutes each cooling cycle or until the R to G circuit closes or the demand for dehumidification is satisfied. High--cooling airflow is based on the A/C selectionshowninFig.47.
3. Cooling off--delay – When the “call for cooling” is satisfied
and there is a demand for dehumidification, the cooling blower--off delay is decreased from 90 seconds to 5 seconds.
Continuous Blower Mode
When the R to G circuit is closed by the thermostat, the blower motor BLWM will operate at continuous blower airflow. Continuous blower airflow selection is initially based on the CF selection shown in Fig. 47. Factory default is shown in Fig. 47. Terminal EAC--1 is energized as long as the blower motor BLWM is energized.
During a call for heat, the furnace control CPU will transition the blower motor BLWM to continuous blower airflow, low--heat airflow, or the mid--range airflow, whichever is lowest. The blower motor BLWM will remain ON until the main burners ignite then shut OFF and remain OFF for the blower--ON delay (60 seconds in medium heat, and 35 seconds in high--heat), allowing the furnace heat exchangers to heat up more quickly, then restarts at the end of the blower--ON delay period at low--heat, medium--heat, or high--heat airflow respectively. The blower motor BLWM will revert to continuous--blower airflow after the heating cycle is completed. In high--heat, the furnace control CPU will drop the blower motor BLWM to low--heat airflow during the selected blower--OFF delay period before transitioning to continuous--blower airflow. When the thermostat “calls for low--cooling”, the blower motor BLWM will operate at low--cooling airflow. When the thermostat is satisfied, the blower motor BLWM will operate an additional 90 seconds at low--cooling airflow before transitioning back to continuous--blower airflow.
When the thermostat “calls for high--cooling”, the blower motor BLWM will operate at high cooling airflow. When the thermostat is satisfied, the blower motor BLWM will operate an additional 90 seconds at high--cooling airflow before transitioning back to continuous--blower airflow.
When the R to G circuit is opened, the blower motor BLWM will continue operating for an additional 5 seconds, if no other function requires blower motor BLWM operation.
Continuous Blower Speed Selection from Thermostat
To select different continuous--blower airflows from the room thermostat, momentarily turn off the FAN switch or push button on the room thermostat for 1--3 seconds after the blower motor BLWM is operating. The furnace control CPU will shift the
continuous--blower airflow from the factory setting to the next highest CF selection airflow as shown in Fig. 47. Momentarily turning off the FAN switch again at the thermostat will shift the continuous--blower airflow up one more increment. If you repeat this procedure enough you will eventually shift the continuous blower airflow to the lowest CF selection as shown in Fig. 47. The selection can be changed as many times as desired and is stored in the memory to be automatically used following a power interruption.
Heat Pump
See Fig. 54--57 for thermostat connections. When installed with a heat pump, the furnace control automatically changes the timing sequence to avoid long blower off times during demand defrost cycles. Whenever W/W1 is energized along with Y1 or Y/Y2, the furnace control CPU will transition to or bring on the blower motor BLWM at cooling airflow, low--heat airflow, or the mid--range airflow, whichever is lowest. The blower motor BLWM will remain on until the main burners ignite then shut OFF and remain OFF for 25 seconds before coming back on at heating airflow. When the W/W1 input signal disappears, the furnace control begins a normal inducer post--purge period while changing the blower airflow. If Y/Y2 input is still energized the furnace control CPU will transition the blower motor BLWM airflow to cooling airflow. If Y/Y2 input signal disappears and the Y1 input is still energized the furnace control CPU will transition the blower motor BLWM to low--cooling airflow. If both the Y1 and Y/Y2 signals disappear at the same time, the blower motor BLWM will remain on at low--heat airflow for the selected blower--OFF delay period. At the end of the blower--OFF delay, the blower motor BLWM will shut OFF unless G is still energized, in which case the blower motor BLWM will operate at continuous blower airflow.
Component Test
The furnace features a component test system to help diagnose a system problem in the case of a component failure. To initiate the component test procedure, ensure that there are no thermostat inputs to the control and all time delays have expired. Turn on setup switch SW1--6. (See Fig. 33)
NOTE: The component test feature will not operate if the control is receiving any thermostat signals or until all time delays have expired.
The component test sequence is as follows:
1. The furnace control CPU turns the inducer motor IDM ON at medium speed and keeps it ON through step 3.
2. After waiting 15 seconds the furnace control CPU turns the hot surface igniter ON for 15 seconds, then OFF.
3. The furnace control CPU then turns the blower motor BLWM ON at mid--range airflow for 15 seconds, then OFF.
4. After shutting the blower motor BLWM OFF the furnace control CPU shuts the inducer motor IDM OFF.
NOTE: The EAC terminals are energized when the blower is operating.
After the component test is completed , 1 or more status codes (11, 25, 41, or 42) will flash. See Service Label on blower access panel or Service/Status Code Instructions for explanation of status codes.
NOTE: To repeat component test, turn setup switch SW1--6 to OFF and then back ON.
51
58MVC
58MVC
A06678
Fig. 52 -- Step--Modulating Furnace with Single--Speed Air
Conditioning
A06680
Fig. 54 -- Step Modulating Furnace with Single--Speed Heat
Pump (Dual Fuel)
Fig. 53 -- Step Modulating Furnace with Two--Speed Air
Conditioner
A06679
A06681
Fig. 55 -- Step Modulating Furnace with Two--Speed Heat
Pump (Dual Fuel)
52
58MVC
A06682
Fig. 56 -- Step Modulating Furnace with Single--Speed Heat
Pump
A06684
Fig. 58 -- Two--Stage Thermostat with Step Modulating
Furnace and Two--Speed Air Conditioner
Fig. 57 -- Dual Fuel thermostat with Step--Modulating
Furnace and Two--Speed Heat Pump
A06683
A06685
Fig. 59 -- Single--Stage Thermostat with Step Modulating Fur-
nace and Two--Speed Air Conditioner
53
NOTE: Reference Fig. 52--59:
1. Heat pump MUST have a high pressure switch for dual fuel applications.
2. Refer to outdoor equipment Installation Instructions for additional information and setup procedure.
3. Select the “ZONE” position on the two--speed heat pump control.
4. Outdoor Air Temperature Sensor must be attached in all dual fuel applications.
5. Dip switch No.1 on Thermidistat should be set in OFF position for air conditioner installations. This is factory default.
6. Dip switch No. 1 on Thermidistat should be set in ON position for heat pump installations.
7. Dip switch No. 2 on Thermidistat should be set in OFF position for single--speed compressor operation. This is factory default.
8. Dip switch No. 2 on Thermidistat should be set in ON
58MVC
position for two--speed compressor operation.
9. Configuration Option No. 10 “Dual Fuel Selection” must be turned ON in all dual fuel applications.
10. NO connection should be made to the furnace HUM terminal when using a Thermidistat.
11. Optional connection. If wire is connected to W2 on furnace control board, either dip switch SW1--2 or SW4--2 on furnace control should be set in ON position to allow Thermidistat/Thermostat to control furnace at 2 stages Low/High or Medium/High.
12. Optional connection. If wire is connected, ACRDJ jumper on furnace control should be removed to allow Thermidistat/Thermostat to control outdoor unit staging.
13. Furnace must control its own staging operation via furnace control algorithm. This is factory default.
14. The RVS Sensing terminal “L” should not be connected. This is internally used to sense defrost operation.
15. DO NOT SELECT the “FURNACE INTERFACE” or “BALANCE POINT” option on the two--speed heat pump control board. This is controlled internally by the Thermidistat/Dual Fuel Thermostat.
16. Dip switch D on Dual Fuel Thermostat should be set in OFF position for single--speed compressor operation. This is factory default.
17. Dip switch D on Dual Fuel Thermostat should be set in ON position for two--speed compressor operation.
Step 4 — Adjustments
Set Gas Input Rate
Furnace gas input rate on rating plate is for installations at altitudes up to 2000 ft. (609.6M).
In the USA., the input rating for altitudes above 2000 ft. (609.6M) must be reduced by 2 percent for each 1000 ft. (304.8M) above sea level.
In Canada, the input rating must be derated by 5 percent for altitudes of 2000 ft. (609.6M) to 4500 ft. (1371.6M) above sea level.
Adjust manifold pressure to obtain input rate. Furnace input rate must be within +2 percent of input rate on
furnace rating plate.
1. Determine natural gas orifice size and manifold pressure for correct input.
a. Obtain average heat value (at installed altitude) from
local gas supplier.
b. Obtain average specific gravity from local gas supplier.
c. Verify furnace model. Table 10 can only be used for
model 58MVC Furnaces.
d. Find installation altitude in Table 10.
NOTE: For Canadian altitudes of 2000 to 4500 ft. (609.6 to
1371.6M), use USA. altitudes of 2001 to 3000 ft. (609.6 to
914.4M) in Table 10. e. Find closest natural gas heat value and specific gravity
in Table 10.
f. Follow heat value and specific gravity lines to point of
intersection to find orifice size and low--, medium--, and high--heat manifold pressure settings for proper operation.
EXAMPLE: 0 -- 2000 ft. (0 -- 609.6M) altitude Heating value = 1050 Btu/cu ft. Specific gravity = 0.62 Therefore: Orifice No. 45 Manifold pressure: 3.8--in. wc for high heat 1.6--in. wc for medium heat 0.6--in. wc for low heat * Furnace is shipped with No. 45 orifices. In this example, all main burner orifices are the correct size and do not need to be changed to obtain proper input rate.
g. Check and verify burner orifice size in furnace. NEVER
ASSUME ORIFICE SIZE; ALWAYS CHECK AND VERIFY.
2. Adjust manifold pressure to obtain input rate.
HIGH-HEAT ADJUSTMENT (UNDER CAP)
BURNER
ENCLOSURE
REFFERENCE
TAP
MANIFOLD
PRESSURE
TAP
A07280
INLET
PRESSURE
TAP
MEDIUM-HEAT
ADJUSTMENT (UNDER CAP)
ON/OFF SWITCH
LOW-HEAT ADJUSTMENT (UNDER CAP)
Fig. 60 -- Redundant Automatic Gas Valve
a. Remove burner enclosure front.
NOTE: Manifold pressure MUST always be measured with the burner box cover REMOVED.
b. Remove regulator seal caps that conceal adjustment
screws for medium-- and high--heat gas valve regulators. (See Fig. 60.)
c.MovesetupswitchSW4--2oncontrolcentertoON
position. (See Fig. 33.) This keeps furnace locked in medium--heat operation.
54
d. Jumper R and W/W1 thermostat connections on control
to start furnace.
e. Turn medium--heat adjusting screw counterclockwise
(out) to decrease manifold pressure or clockwise (in) to increase manifold pressure.
NOTE: DO NOT set medium--heat manifold pressure less than
1.3-- in. wc or more than 1.7--in. wc for natural gas.
!
UNIT DAMAGE HAZARD
Failure to follow this caution may result in reduced furnace life.
DO NOT bottom out gas valve regulator adjusting screws. This can result in unregulated manifold pressure and result in excess over--fire and heat exchanger failures.
NOTE: If orifice hole appears damaged or it is suspected to have been redrilled, check orifice hole with a numbered drill bit of correct size. Never redrill an orifice. A burr--free and squarely aligned orifice hole is essential for proper flame characteristics. (See Fig. 61.)
f. Move setup switch SW4--2 to OFF position after
completing medium--heat adjustment.
g. Jumper R and W/W1 and W2 thermostat connections
on furnace control. (See Fig. 33.) This keeps furnace locked in high--heat operation.
h. Turn high--heat adjusting screw counterclockwise (out)
to decrease manifold pressure or clockwise (in) to increase manifold pressure.
NOTE: DO NOT set high--heat manifold pressure less than
3.2--in. wc or more than 3.8--in. wc for natural gas. i. Remove jumpers R to W/W1 and R to W2. j. Wait for blower off--delay to finish then reset 115--v
power to furnace.
k. Jumper R and W/W1 thermostat connections on control
to start furnace.
l. Wait for the blower to turn ON then check low--heat
manifold pressure. It should be between .5 to .6--in. wc. This setting should not require adjustment but if it does remove the low--heat adjustment cap (See Fig. 60) and turn the low--heat adjusting screw clockwise (in) to decrease manifold pressure or counterclockwise (out) to increase manifold pressure. You will only have 15 minutes to make an adjustment if needed. If you need moretimethenmovesetupswitchSW1--2oncontrol center to ON position (See Fig. 33).
NOTE: DO NOT set low--heat manifold pressure before setting medium--heat manifold pressure. DO NOT set low--heat manifold pressure less than .5--in. wc or more than .6--in. wc for natural gas.
m. When correct manifold pressures are obtained, replace
caps that conceal gas valve adjustment screws. Main burner flame should be clear blue, almost transparent. (See Fig. 62.)
n. Remove jumper across R and W/W1. If necessary move
setupswitchSW1--2totheOFFposition.
CAUTION
3. Verify natural gas input rate by clocking gas meter.
NOTE: Be sure all pressure tubing, combustion--air and vent pipes, and burner enclosure front are in place when checking input by clocking gas meter.
a. Calculate high--altitude adjustment (if required).
UNITED STATES At altitudes above 2000 ft. (609.6M), this furnace has been approved for 2 percent derate for each 1000 ft. (304.8M) above sea level. See Table 11 for derate multiplier factor and example. CANADA At installation altitudes from 2000 to 4500 ft. (609.6 to
1371.6M), this furnace must be derated 5 percent by an authorized Gas Conversion Station or Dealer. To determine correct input rate for altitude, see example and use 0.95 as derate multiplier factor. EXAMPLE: 80,000 BTUH HIGH--HEAT INPUT FURNACE INSTALLED AT 4,300 ft. (1310.6M). Furnace Input Rate at Sea Level X Derate Multiplier Factor = Furnace Input Rate at Installation Altitude 80,000 X 0.91 = 72,800
b. Reinstall burner box cover.
NOTE: Clocking gas input rate MUST always be performed with the burner box cover INSTALLED.
c. Check that gas valve adjustment caps are in place for
proper input to be clocked.
d. Obtain average heat value (at altitude) from local gas
supplier.
NOTE: Be sure heating value of gas used for calculations is correct for your altitude. Consult local gas utility for altitude adjustment of gas heating value.
e. Check and verify orifice size in furnace. NEVER
ASSUME THE ORIFICE SIZE. ALWAYS CHECK AND VERIFY.
f. Turn off all other gas appliances and pilots.
g. Move setup switch SW4--2 to ON position. (See Fig.
33.) This keeps furnace locked in medium--heat operation.
BURNER
ORIFICE
A93059
Fig. 61 -- Burner Orifice
58MVC
55
Table 10 – Orifice Size* and Manifold Pressures for Gas Input Rate
AVG. GAS SPECIFIC GRAVITY OF NATURAL GAS
HEAT VALUE 0.58 0.60 0.62 0.64
AT ALTITUDE
Orifice Mnfld Press Orifice Mnfld Press Orifice Mnfld Press Orifice Mnfld Press
(Btu/cu ft)
No. High/Med/Low No. High/Med/Low No. High/Med/Low No. High/Med/Low
900
43 3.5 / 1.5 /0.55 43 3.6 / 1.5 /0.60 43 3.8 / 1.6 /0.60 42 3.2 / 1.3 /0.50
0925
44 3.8 / 1.6 /0.60 43 3.5 / 1.5 /0.55 43 3.6 / 1.5 /0.55 43 3.7 / 1.6 /0.60
(0) 950
44 3.6 / 1.5 /0.60 44 3.8 / 1.6 /0.60 43 3.4 / 1.4 /0.55 43 3.5 / 1.5 /0.55
975
44 3.4 / 1.5 /0.55 44 3.6 / 1.5 /0.55 44 3.7 / 1.6 /0.60 44 3.8 / 1.6 /0.60
to 1000
44 3.3 / 1.4 /0.50 44 3.4 / 1.4 /0.55 44 3.5 / 1.5 /0.55 44 3.6 / 1.5 /0.60
1025 45 3.8 / 1.6 /0.60
44 3.2 / 1.4 /0.50 44 3.3 / 1.4 /0.55 44 3.4 / 1.5 /0.55
2000 1050 45 3.6 / 1.5 /0.60 45 3.7 / 1.6 /0.60 45 3.8 / 1.6 /0.60
44 3.3 / 1.4 /0.50
(610) 1075 45 3.4 / 1.4 /0.55 45 3.5 / 1.5 /0.55 45 3.7 / 1.5 /0.60 45 3.8 / 1.6 /0.60
1100 45 3.3 / 1.4 /0.50 45 3.4 / 1.4 /0.55 45 3.5 / 1.5 /0.55 45 3.6 / 1.5 /0.60
U.S.A. 800
43 3.8 / 1.6 /0.60 42 3.2 / 1.4 /0.50 42 3.3 / 1.4 /0.55 42 3.5 / 1.5 /0.55
2001 (611) 825
43 3.6 / 1.5 /0.55 43 3.7 / 1.6 /0.60 43 3.8 / 1.6 /0.60 42 3.2 / 1.4 /0.50
to 850
43 3.4 / 1.4 /0.55 43 3.5 / 1.5 /0.55 43 3.6 / 1.5 /0.60 43 3.7 / 1.6 /0.60
3000 (914) 875
44 3.7 / 1.5 /0.60 44 3.8 / 1.6 /0.60 43 3.4 / 1.4 /0.55 43 3.5 / 1.5 /0.55
900
44 3.5 / 1.5 /0.55 44 3.6 / 1.5 /0.55 44 3.7 / 1.6 /0.60 44 3.8 / 1.6 /0.60
Canada 925
44 3.3 / 1.4 /0.50 44 3.4 / 1.4 /0.55 44 3.5 / 1.5 /0.55 44 3.6 / 1.5 /0.60
2001 (611) 950 45 3.7 / 1.6 /0.60
44 3.2 / 1.4 /0.50 44 3.3 / 1.4 /0.55 44 3.4 / 1.4 /0.55
to 975 45 3.6 / 1.5 /0.55 45 3.7 / 1.6 /0.60 45 3.8 / 1.6 /0.60
44 3.2 / 1.4 /0.50
4500 (1372) 1000 45 3.4 / 1.4 /0.55 45 3.5 / 1.5 /0.55 45 3.6 / 1.5 /0.60 45 3.7 / 1.6 /0.60
775
43 3.7 / 1.6 /0.60 42 3.2 / 1.3 /0.50 42 3.3 / 1.4 /0.55 42 3.4 / 1.4 /0.55
3001 800
43 3.5 / 1.5 /0.55 43 3.6 / 1.5 /0.60 43 3.8 / 1.6 /0.60 42 3.2 / 1.3 /0.50
(915) 825
44 3.8 / 1.6 /0.60 43 3.4 / 1.4 /0.55 43 3.5 / 1.5 /0.55 43 3.7 / 1.5 /0.60
850
44 3.6 / 1.5 /0.55 44 3.7 / 1.6 /0.60 44 3.8 / 1.6 /0.60 43 3.4 / 1.5 /0.55
875
44 3.4 / 1.4 /0.55 44 3.5 / 1.5 /0.55 44 3.6 / 1.5 /0.60 44 3.7 / 1.6 /0.60
4000 900
44 3.2 / 1.3 /0.50 44 3.3 / 1.4 /0.55 44 3.4 / 1.4 /0.55 44 3.5 / 1.5 /0.55
(1219) 925 45 3.7 / 1.5 /0.60 45 3.8 / 1.6 /0.60
44 3.2 / 1.4 /0.50 44 3.3 / 1.4 /0.55
950 45 3.5 / 1.5 /0.55 45 3.6 / 1.5 /0.55 45 3.7 / 1.6 /0.60 45 3.8 / 1.6 /0.60
750
43 3.7 / 1.6 /0.60 43 3.8 / 1.6 /0.60 42 3.2 / 1.4 /0.50 42 3.3 / 1.4 /0.55
4001 775
43 3.5 / 1.5 /0.55 43 3.6 / 1.5 /0.55 43 3.7 / 1.6 /0.60 43 3.8 / 1.6 /0.60
(1220) 800
44 3.7 / 1.6 /0.60 43 3.4 / 1.4 /0.55 43 3.5 / 1.5 /0.55 43 3.6 / 1.5 /0.55
825
44 3.5 / 1.5 /0.55 44 3.6 / 1.5 /0.60 44 3.7 / 1.6 /0.60 43 3.4 / 1.4 /0.55
850
44 3.3 / 1.4 /0.55 44 3.4 / 1.4 /0.55 44 3.5 / 1.5 /0.55 44 3.6 / 1.5 /0.60
5000 875 45 3.8 / 1.6 /0.60
44 3.2 / 1.4 /0.50 44 3.3 / 1.4 /0.55 44 3.4 / 1.5 /0.55
(1524) 900 45 3.6 / 1.5 /0.55 45 3.7 / 1.6 /0.60 45 3.8 / 1.6 /0.60
44 3.2 / 1.4 /0.50
925 45 3.4 / 1.4 /0.55 45 3.5 / 1.5 /0.55 45 3.6 / 1.5 /0.60 45 3.7 / 1.6 /0.60
725
43 3.6 / 1.5 /0.60 43 3.8 / 1.6 /0.60 42 3.2 / 1.4 /0.50 42 3.3 / 1.4 /0.55
5001 750
43 3.4 / 1.4 /0.55 43 3.5 / 1.5 /0.55 43 3.6 / 1.5 /0.60 43 3.8 / 1.6 /0.60
(1525) 775
44 3.7 / 1.5 /0.60 44 3.8 / 1.6 /0.60 43 3.4 / 1.4 /0.55 43 3.5 / 1.5 /0.55
800
44 3.4 / 1.5 /0.55 44 3.6 / 1.5 /0.55 44 3.7 / 1.6 /0.60 44 3.8 / 1.6 /0.60
825
44 3.2 / 1.4 /0.50 44 3.3 / 1.4 /0.55 44 3.4 / 1.5 /0.55 44 3.6 / 1.5 /0.55
6000 850 45 3.7 / 1.6 /0.60 45 3.8 / 1.6 /0.60
44 3.2 / 1.4 /0.50 44 3.4 / 1.4 /0.55
(1829) 875 45 3.5 / 1.5 /0.55 45 3.6 / 1.5 /0.55 45 3.7 / 1.6 /0.60 45 3.8 / 1.6 /0.60
900 45 3.3 / 1.4 /0.50 45 3.4 / 1.4 /0.55 45 3.5 / 1.5 /0.55 45 3.6 / 1.5 /0.60
675
42 3.2 / 1.3 /0.50 42 3.3 / 1.4 /0.55 42 3.4 / 1.4 /0.55 42 3.5 / 1.5 /0.55
6001 700
43 3.6 / 1.5 /0.55 43 3.7 / 1.6 /0.60 43 3.8 / 1.6 /0.60 42 3.3 / 1.4 /0.50
(1830) 725
44 3.8 / 1.6 /0.60 43 3.5 / 1.5 /0.55 43 3.6 / 1.5 /0.55 43 3.7 / 1.6 /0.60
750
44 3.6 / 1.5 /0.55 44 3.7 / 1.6 /0.60 44 3.8 / 1.6 /0.60 43 3.5 / 1.5 /0.55
775
44 3.4 / 1.4 /0.55 44 3.5 / 1.5 /0.55 44 3.6 / 1.5 /0.55 44 3.7 / 1.6 /0.60
7000 800 45 3.8 / 1.6 /0.60
44 3.3 / 1.4 /0.50 44 3.4 / 1.4 /0.55 44 3.5 / 1.5 /0.55
(2133) 825 45 3.6 / 1.5 /0.55 45 3.7 / 1.6 /0.60 45 3.8 / 1.6 /0.60
44 3.3 / 1.4 /0.50
850 45 3.4 / 1.4 /0.55 45 3.5 / 1.5 /0.55 45 3.6 / 1.5 /0.60 45 3.7 / 1.6 /0.60
U.S.A. and Canada
U.S.A. Only
RANGE
to
to
to
ALTITUDE
ft (m)
U.S.A. and Canada
U.S.A. Only
U.S.A. Only
U.S.A. Only
to
* Orifice numbers shown in
BOLD
are factory-installed.
(Tabulated Data Based on 20,000 BTUH High Heat / 13,000 Btuh Med--Heat / 8,000 Btuh Low--Heat per Burner,
58MVC
Derated 2% / 1000 Ft. (304.8M) Above Sea Level)
56
A08202
Table 10 --- Orifice Size* and Manifold Pressures for Gas Input Rate (Continued)
AVG. GAS SPECIFIC GRAVITY OF NATURAL GAS
HEAT VALUE 0.58 0.60 0.62 0.64
AT ALT ITUDE
Orifice Mnfld Press Orifice Mnfld Press Orifice Mnfld Press Orifice Mnfld Press
(Btu/cu ft)
No. High/Med/Low No. High/Med/Low No. High/Med/Low No. High/Med/Low
RANGE
ALTITUDE
ft (m)
650
43 3.8 / 1.6 /0.60 42 3.2 / 1.4 /0.50 42 3.4 / 1.4 /0.55 42 3.5 / 1.5 /0.55
7001 675
43 3.5 / 1.5 /0.55 43 3.7 / 1.6 /0.60 43 3.8 / 1.6 /0.60 42 3.2 / 1.4 /0.50
(2134) 700
44 3.8 / 1.6 /0.60 43 3.4 / 1.4 /0.55 43 3.5 / 1.5 /0.55 43 3.6 / 1.5 /0.60
725
44 3.5 / 1.5 /0.55 44 3.6 / 1.5 /0.60 44 3.8 / 1.6 /0.60 43 3.4 / 1.4 /0.55
750
44 3.3 / 1.4 /0.55 44 3.4 / 1.4 /0.55 44 3.5 / 1.5 /0.55 44 3.6 / 1.5 /0.60
8000 775 45 3.7 / 1.6 /0.60
44 3.2 / 1.3 /0.50 44 3.3 / 1.4 /0.55 44 3.4 / 1.4 /0.55
(2438) 800 45 3.5 / 1.5 /0.55 45 3.6 / 1.5 /0.60 45 3.7 / 1.6 /0.60
44 3.2 / 1.4 /0.50
825 45 3.3 / 1.4 /0.55 45 3.4 / 1.4 /0.55 45 3.5 / 1.5 /0.55 45 3.6 / 1.5 /0.60
625
43 3.8 / 1.6 /0.60 42 3.2 / 1.4 /0.50 42 3.3 / 1.4 /0.55 42 3.4 / 1.5 /0.55
8001 650
43 3.5 / 1.5 /0.55 43 3.6 / 1.5 /0.60 43 3.8 / 1.6 /0.60 42 3.2 / 1.3 /0.50
(2439) 675
44 3.7 / 1.6 /0.60 43 3.4 / 1.4 /0.55 43 3.5 / 1.5 /0.55 43 3.6 / 1.5 /0.60
700
44 3.5 / 1.5 /0.55 44 3.6 / 1.5 /0.60 44 3.7 / 1.6 /0.60 44 3.8 / 1.6 /0.60
725
44 3.2 / 1.4 /0.50 44 3.4 / 1.4 /0.55 44 3.5 / 1.5 /0.55 44 3.6 / 1.5 /0.55
9000 750 45 3.7 / 1.5 /0.60 45 3.8 / 1.6 /0.60
44 3.2 / 1.4 /0.50 44 3.3 / 1.4 /0.55
(2743) 775 45 3.4 / 1.5 /0.55 45 3.6 / 1.5 /0.55 45 3.7 / 1.6 /0.60 45 3.8 / 1.6 /0.60
9001 600
43 3.8 / 1.6 /0.60 42 3.2 / 1.4 /0.50 42 3.3 / 1.4 /0.55 42 3.4 / 1.4 /0.55
(2744) 625
43 3.5 / 1.5 /0.55 43 3.6 / 1.5 /0.60 43 3.7 / 1.6 /0.60 43 3.8 / 1.6 /0.60
650
44 3.7 / 1.6 /0.60 44 3.8 / 1.6 /0.60 43 3.4 / 1.5 /0.55 43 3.6 / 1.5 /0.55
675
44 3.4 / 1.4 /0.55 44 3.5 / 1.5 /0.55 44 3.7 / 1.5 /0.60 44 3.8 / 1.6 /0.60
10000 700
44 3.2 / 1.3 /0.50 44 3.3 / 1.4 /0.55 44 3.4 / 1.4 /0.55 44 3.5 / 1.5 /0.55
(3048) 725 45 3.6 / 1.5 /0.55 45 3.7 / 1.6 /0.60 45 3.8 / 1.6 /0.60
44 3.3 / 1.4 /0.50
* Orifice numbers shown in
BOLD
are factory-installed.
U.S.A. Only U.S.A. Only
U.S.A. Only
to
to
to
(Tabulated Data Based on 20,000 BTUH High Heat / 13,000 Btuh Med--- Heat / 8,000 Btuh Low ---Heat per Burner,
Derated 2% / 1000 Ft. (304.8M) Above Sea Level)
58MVC
A08203
57
!
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in component damage.
DO NOT redrill orifices. Improper drilling (burrs, out--of--round holes, etc.) can cause excessive burner noise and misdirection of burner flames. (See Fig. 61.)
h. Jumper R to W/W1.
i. Let furnace run for 3 minutes in medium--heat
operation.
j. Measure time (in sec) for gas meter to complete 1
revolution. Note reading.
k. Refer to Table 12 for cubic ft. of gas per hr.
l. Multiply gas rate cu ft/hr by heating value (Btu/cu ft).
58MVC
m. Move setup switch SW4--2 to OFF position and jumper
R and W/W1 and W2 thermostat connections. (See Fig.
33.) This keeps furnace locked in high--heat operation. Repeat items i through l for high--heat operation.
EXAMPLE: High--heat operation at 0 -- 2000 ft. (0--609.6M) altitude Furnace input from rating plate is 80,000 Btuh Btuh heating input = Btuh/cu ft. X cu ft/hr Heating value of gas = 975 Btuh/cu ft. Time for 1 revolution of 2--cu ft. dial = 88 sec Gas rate = 82 cu ft/hr (from Table 12) Btuh heating input = 103 X 975 = 79,950 Btuh
In this example, the orifice size and manifold pressure adjustment is within +/-- 2 percent of the furnace input rate.
n. Remove jumper across R, W/W1, and W2 thermostat
connections to terminate call for heat.
o. Wait for blower off--delay to finish then reset 115--v
power to furnace.
p. Wait for blower off--delay to finish then reset 115--v
power to furnace.
q. Jumper R and W/W1 thermostat connections on control
to start furnace.
r. Wait for the blower to turn ON then repeat items i
through l for low--heat operation. This setting should not require adjustment but if it does you will only have 15 minutes to make the adjustment. If you need more timethenmovesetupswitchSW1--2oncontrolcenter to ON position (See Fig. 33).
NOTE: Measured gas inputs (high heat, medium heat, and low heat) must be within +/--2 percent of that stated on furnace rating plate when installed at sea level or derated as stated above when installed at higher altitudes.
Table 11 – Altitude Derate Multiplier for USA
ALTITUDE
FT (M)
0—2000 (0—610) 0 1.00
2001—3000
(610—914)
3001—4000 (914—1219)
4001—5000
(1219—1524)
5001—6000
(1524—1829)
6001—7000
(1829—2134)
7001—8000
(2134—2438)
8001—9000
(2438—2743)
9001—10,000
(2743—3048)
*Derate multiplier factor is based on midpoint altitude for altitude ran ge.
BURNER FLAME
MANIFOLD
%OF
DERATE
4—6 0.95
6—8 0.93
8—10 0.91
10—12 0.89
12—14 0.87
14—16 0.85
16—18 0.83
18—20 0.81
DERATE MULTIPLIER
FACTOR FOR USA.*
BURNER
Fig. 62 -- Burner Flame
A89020
58
Table12–GasRatecuFt/Hr
SECONDS
FOR 1
REVOLUTION
10 360 720 1800 50 72 144 360 11 327 655 1636 51 71 141 355 12 300 600 1500 52 69 138 346 13 277 555 1385 53 68 136 340 14 257 514 1286 54 67 133 333 15 240 480 1200 55 65 131 327 16 225 450 1125 56 64 129 321 17 212 424 1059 57 63 126 316 18 200 400 1000 58 62 124 310 19 189 379 947 59 61 122 305 20 180 360 900 60 60 120 300 21 171 343 857 62 58 116 290 22 164 327 818 64 56 112 281 23 157 313 783 66 54 109 273 24 150 300 750 68 53 106 265 25 144 288 720 70 51 103 257 26 138 277 692 72 50 100 250 27 133 267 667 74 48 97 243 28 129 257 643 76 47 95 237 29 124 248 621 78 46 92 231 30 120 240 600 80 45 90 225 31 116 232 581 82 44 88 220 32 113 225 563 84 43 86 214 33 109 218 545 86 42 84 209 34 106 212 529 88 41 82 205 35 103 206 514 90 40 80 200 36 100 200 500 92 39 78 196 37 97 195 486 94 38 76 192 38 95 189 474 96 38 75 188 39 92 185 462 98 37 74 184 40 90 180 450 100 36 72 180 41 88 176 439 102 35 71 178 42 86 172 429 104 35 69 173 43 84 167 419 106 34 68 170 44 82 164 409 108 33 67 167 45 80 160 400 110 33 65 164 46 78 157 391 112 32 64 161 47 76 153 383 116 31 62 155 48 75 150 375 120 30 60 150
49 73 147 367
SIZE OF TEST DIAL
1
cu ft.
cu ft.
SECONDS
2
5
cu ft.
FOR 1
REVOLUTION
SIZE OF TEST DIAL
1
cu ft.
2
cu ft.
5
cu ft.
58MVC
Set Temperature Rise
!
UNIT DAMAGE HAZARD
Failure to follow this caution may result in component damage.
Temperature rise must be within limits specified on unit rating plate. Operation is within a few degrees of midpoint ofriserangewhensetupswitchSW1--4isOFF.
Furnace must operate within ranges of temperature rise specified on the furnace rating plate. Determine air temperature rise as follows:
1. Place thermometers in return and supply ducts as near furnace as possible. Be sure thermometers do not see heat exchanger so that radiant heat does not affect readings. This practice is particularly important with straight--run ducts.
2. When thermometer readings stabilize, subtract return--air temperature from supply--air temperature to determine air temperature rise.
CAUTION
NOTE: Temperature rise can be determined for low--heat
operation by placing setup switch SW1--2 on furnace control in ON position. Temperature rise can be determined for medium--heat operation by placing setup switch SW4--2 on furnace control in ON position. For high--heat operation, place setup switch SW1--2 and SW4--2 in OFF position and jumper R--W2 on furnace control. DO NOT forget to return setup switch to OFF position and remove R--W2 jumper upon completion of testing. (See Fig. 33 for switch and terminal location.)
3. This furnace is capable of automatically providing proper airflow to maintain the temperature rise within the range specified on furnace rating plate. If temperature rise is outside this range, proceed as follows:
a. Check gas input for low--, medium--, and high--heat
operation.
b. Check derate for altitude if applicable.
c. Check all return and supply ducts for excessive
restrictions causing static pressure greater than 0.5--in. wc.
d. Ensure Low Heat Rise Adjust switch SW1--3 on furnace
control is in ON position when a bypass humidifier is used. (See Fig. 33 for switch location.)
e. Check Troubleshooting Guide for Variable--Speed Step
Modulating Condensing Furnaces.
59
Set Thermostat Heat Anticipator
When using a non--electronic thermostat, the thermostat heat anticipator must be set to match the amp draw of components in the R--W/W1 circuit. Accurate amp draw measurements can be obtained only at the thermostat subbase terminals R and W.
The thermostat and anticipator should NOT be in the circuit while measuring current. If thermostat has no subbase, the thermostat must be disconnected from R and W/W1 wires during current measurement.
Fig. 63 illustrates an easy method of obtaining thermostat amp draw measurements. The amp reading should be taken after blower motor has started and furnace is operating in low--heat.
1. To operate furnacein low--heat, turn setup switch SW1--2 to ON position (See Fig. 33) and connect ammeter leads across thermostat subbase R--W.
2. See thermostat manufacturer’s instructions for adjusting the heat anticipator and for varying heating cycle length.
NOTE: When using an electronic thermostat, set cycle rate for 3 cycles per hr.
58MVC
3. Return setup switch SW1--2 to OFF position and replace thermostat on subbase.
Check Safety Controls
This section covers the safety controls that must be checked before the installation is complete. The flame sensor, gas valve, and pressure switches were all checked in the Start--up procedure section as part of normal operation.
Check Primary Limit Control
This control shuts off the gas control system and energizes the air--circulating blower motor if furnace overheats.
1. The recommended method of checking this limit control is to gradually block off return air after furnace has been operating for a period of at least 5 minutes.
2. As soon as limit control has shut off burners, a status code 33 will appear on furnace control.
3. The return--air opening should be unblocked to permit normal air circulation.
By using this method to check the limit control, it can be established that the limit is functioning properly and the furnace will operate safely if there is a restricted return--air duct or motor failure. If the limit control does not function during this test, the cause must be determined and corrected.
Check Pressure Switches
This control proves operation of the draft inducer. Check switch operation as follows:
1. Turn off 115--v power to furnace.
2. Remove control access door and disconnect inducer motor 12--pin wire harness at inducer motor.
3. Turn on 115--v power to furnace.
4. Set thermostat to “call for heat.” When pressure switches are functioning properly, status code 42 will flash on furnace control approximately 20 sec after thermostat switch is closed. If either a status code 31 or 32 is flashed when inducer motor is disconnected, the furnace will shut itself down immediately. Determine the reason pressure switches did not function properly and correct the condition.
5. Turn off 115--v power to furnace.
6. Reconnect inducer motor wire harness. Reinstall furnace access door.
7. Turn on 115--v power to furnace.
8. Reset thermostat to desired temperature.
1. Put away tools and instruments. Clean up debris.
2. Verify flame rollout manual reset switch has continuity.
3. Verify that blower and main access doors are properly installed.
4. Cycle test furnace with room thermostat.
5. Check operation of accessories per manufacturer’s instructions.
6. Review User’s Manual with owner.
7. Leave literature packet near
THERMOSTAT SUBBASE TERMINALS WITH THERMOSTAT REMOVED (ANITICIPATOR, CLOCK, ETC., MUST BE OUT OF CIRCUIT.)
HOOK-AROUND AMMETER
CHECKLIST
furnace.
EXAMPLE:
R Y W G
10 TURNS
FROM UNIT 24-V CONTROL TERMINALS
5.0 AMPS ON AMMETER 10 TURNS AROUND JAWS
0.5 AMPS FOR THERMOSTAT
=
ANTICIPATOR SETTING
Fig. 63 -- Amp Draw with Ammeter
60
A96316
CHECKLIST — INSTALLATION
LOAD CALCULATION
________________ Heating Load (Btuh) Condensate Drain
________________ Cooling Load (Btuh) ________________ Unit Level or Pitched Forward
________________
COMBUSTION AND VENT PIPING
________________ Vent Heat Tape Installed if Required
________________ Roof C H E C K L I S T --- S T A R T --- U P
________________
________________ Combustion---Air ________________ Temperature Rise Adjusted
________________ Roof Thermostat Anticipator
________________ Sidewall ________________ Anticipator Setting Adjusted or
________________ Attic ________________ Cycle Rate (3 Cycles per Hr)
________________ Crawl Space Safety Controls Check Operation
________________ Termination Kit ---2 Pipe or
________________
________________ Combustion---Air Pipe Elbow
________________ Vent Pipe Length Thermostat Anticipator
________________ Vent Pipe Elbow Quantity ________________ Anticipator Setting Adjusted or
________________ Pipe Diameter Determined from
________________ Pipe Sloped To Furnace Safety Controls Check Operation
________________ Over Ceilings ________________ Pressure Switches
________________ Low--- Ambient Exposed Pipes
Furn ace Model Selection
Termination Location
Sidewall
Concentric
C o m b u s t i o n --- Ai r P i p e L e n g t h
Quantity
Sizing Table
Pipe Insulation ________________ Primary Limit
________________ Internal Tubing Connections
________________ External Drain Connection Leak
________________ Condensate Trap Primed before
________________ Gas Input Rate (Set Within 2
C H E C K L I S T --- S T A R T --- U P
________________ Gas Input Rate (Set Within 2
________________
________________ Cycle Rate (3 Cycles per Hr)
Free of Kinks and Traps
Tight and Slop ed
S t a r t --- Up
percent of Rating Plate)
Selected
percent of Rating Plate)
TemperatureRiseAdjusted
Selected
58MVC
61
58MVC
Copyright 2009 Carrier Corp. S 7310 W. Morris St. S Indianapolis, IN 46231 Printed in U.S.A. Edition Date: 12/09
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
Catalog No: 58MVC ---5SI
Replaces: 58MVC --- 4SI
62
Loading...