Carrier HUMCCLFP1025-A User Manual

Page 1
Visit www.carrier.com
Installation, Start-Up, and Operating Instructions
MODEL HUMCCLFP1025-A--
FAN-POWERED
HUMIDIFIER
MODEL HUMCCLBP2018-A--
BYPASS HUMIDIFIER
Humidifiers and
Humidistat
MODEL HUMCCSFP1016-A--
FAN-POWERED
HUMIDIFIER
MODEL HUMCCWTR2019-A--
WATER-SAVER
BYPASS HUMIDIFIER
Humidifiers
NOTE: Read the entire instruction in manual applicable to
specific unit before starting the installation. This symbol indicates a change since the last issue.
SAFETY CONSIDERATIONS
Improper installation, adjustment, alteration, service, maintenance, or use can cause explosion, fire, electrical shock, or other conditions which may cause personal injury or property damage. Consult a qualified installer, service agency, distributor, or branch for information or assistance. The qualified installer or agency must use factory-authorized kits or accessories when modifying this product. Refer to the individual instructions packaged with the kits or accessories when installing.
Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth for brazing operations. Have fire extinguisher available. Read these instructions thoroughly and follow all warnings or cautions attached to the unit. Consult local building codes and National Electrical Code (NEC) for special require­ments.
Recognize safety information. This is the safety-alert symbol When you see this symbol on the unit and in instructions or manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, and CAU­TION. These words are used with the safety-alert symbol. DAN­GER identifies the most serious hazards which willresultinsevere personal injury or death. WARNING signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices which would result in minor personal injury or product and property damage.
MODEL HUMCCSBP2017-A--
A98362
Before installing or servicing system, always turn off main power to system. There may be more than 1 disconnect switch. Turn off accessory heater power if applicable. Elec­trical shock can cause personal injury or death.
Unit must not be installed where freezing temperatures could occur. Do not install unit on the furnace or fan coil jacket. Do not install unit where ends of cooling coil could restrict airflow to the humidifier. Condensation damage could occur if home has closed-off, unheated rooms.
INSTALLATION OF HUMCCLBP2018-A--
BYPASS HUMIDIFIER
Carrier’s HUMCCLBP2018-A-- bypass humidifier can be in­stalled on eitherthesupply or return plenum of a forced-air system.
.
This unit requires an external bypass duct between the supply- and return-air ductwork.
It is recommended to install the humidifier where it can be easily serviced. If this humidifier is installed with a central cooling system the bypass duct must have a shutoff damper to close during the cooling season. Always install humidifier downstream of an electronic air cleaner.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4 Tab 7a 9a
PC 101 Catalog No. 03HU-MC1 Printed in U.S.A. Form HUM-1SI Pg 1 7-98 Replaces: 49-4SI
Page 2
Step 1—Inspect Package and Check Equipment
Inspect contents of packaged humidifier. File claim with shipping company prior to installation if shipment is damaged or incom­plete. The package should contain:
1. Humidifier and media assembly
2. Humidistat
3. Template
4. Owner’s Manual
5. Warranty Certificate
6. Solenoid valve with bridge rectifier
7. Saddle valve assembly with adapter
8. Four sheet metal screws
9. Foam tape
10. Water noise reducer (use for water pressure over 60 psi)
11. 6-in. damper
12. Worm clamp for field-supplied drain tube
13. Humidifier maintenance instruction sticker
14. Carrier logo label
BYPASS UNITS
"N" COIL
TEMPLATE
PLENUM
LEVEL
A97096
Fig. 2—Preparing Plenum Opening
FOAM TAPE
SCREWS
DRILL (2) HOLES IN DUCT FOR #8 SHEETMETAL SCREWS
VERTICAL
BYPASS UNITS ONLY
HORIZONTAL
A98363
Fig. 1—Installation of HUMCCLBP2018-A--
Bypass-Type Humidifier
Step 2—Select Location (See Fig. 1.)
Humidifier may be installed on either supply or return plenum. If furnace has air conditioning coil, be sure humidifier does not interfere with coil ends. Remember to provide clearance for maintenance and evaporator pad removal.
Step 3—Prepare Plenum Opening (See Fig. 2.)
1. Use template for marking humidifier opening.
2. Tape in place on plenum making sure template is level.
IMPORTANT: For humidifier to operate properly it must be level and mounted on a vertical surface.
3. Drill four 1/8-in. holes in plenum.
4. Cut opening in plenum using heavy solid lines on template as a guide.
NOTCH
Fig. 3—Mounting the Humidifier
Step 4—Mount the Humidifier (See Fig. 3.)
1. Attach foam tape on inside of mounting flange.
2. Hook bottom notch of humidifier on opening cut in plenum.
3. Push top of humidifier to plenum aligning screw holes with flange.
4. Align, level, and secure using top screws first.
5. Insert bottom screws and tighten all screws for air tight seal.
Step 5—Install Bypass Duct
Attach field-supplied 6-in. diameter duct, elbow, or starting collar with field-supplied 1/4-in. zip screws. Install supplied 6-in. damper in 6-in. duct connector.
Do not support weight of bypass duct from humidifier — damage could result.
Step 6—Install Drain Line
1. Use 1/2- or 5/8-in. vinyl tubing (field supplied) to connect drain on bottom of humidifier housing to an open drain.
2. Usesupplied worm clamp to hold drain tubing in position over
drain fitting outlet.
Unit may leak if drain tubing is misapplied. Do not insert tubing inside of drain fitting outlet.
3. Make sure line is free of traps due to sagging and has sufficient pitch to drain.
2
A98364
Page 3
HUMIDIFIER HUMIDISTAT
HUMIDIFIER HUMIDISTAT
BROWN BROWN
RED BLU
FURNACE
TRANSFORMER
(FIELD SUPPLIED)
24V
WIRING
Fig. 4—Installation of Humidistat
on Bypass-Type Humidifier
Step 7—Make Water Connection
If garden hose is not used for water supply:
1. Mount saddle valve on water line according to instructions supplied with valve.
2. Run 1/4-in. diameter (water line grade) tubing from saddle valve to adapter on solenoid valve and tighten compression fittings.
IMPORTANT: If water pressure is higher than normal (60 psi), use noise suppression disk included in parts bag. (Read water noise reducer note located inside package for instructions.) For normal operation, saddle valve need only be opened 1 full turn to meet performance requirements.
3. Open valve and check installation for leaks.
NOTE: Saddle valve is self piercing on copper lines; 1/4-in. hole must be drilled in steel or iron pipes. Use only a grounded drill or a hand drill to avoid shock hazard. Turn off water and drain the pipe prior to drilling 1/4-in. hole.
Step 8—Install Humidistat and Complete Wiring
1. Mount humidistat on inside wall, or return-air duct in accor­dance with section INSTALLATION OF HUMIDISTAT on page 10.
2. Wire brown low voltage leads to furnace control board, or install a field-supplied step-down transformer 115vac/24vac 60Hz to power solenoid valve. (See Fig. 4.) Make sure bridge rectifier is attached to coil of solenoid valve.
NOTE: Wiring must comply with National Electrical Code and any local codes or ordinances that may apply.
Step 9—Start-Up
1. Open saddle valve to permit water flow to the solenoid.
2. Check all connections for water leaks.
3. Set thermostat to call for heat. Set humidistat for highest humidity setting making sure contacts are closed. After a few minutes of operation, check the drain connection for leaks and to see if water is flowing through humidifier.
4. Reverse thermostat and humidistat settings to insure proper shutdown.
5. Reset thermostat to normal setting. Reset humidistat to rec­ommended setting.
Step 10—Final Steps
Attach humidifier maintenance instruction sticker to a visible location.
24VAC
115V
FIELD
A98365
1. Inform homeowner of proper operation, maintenance, and humidistat setting.
a. If unit is installed during cooling season, close bypass
damper, set humidistat for summer setting (OFF or lowest setting).
b. If installed during heating season, set unit for normal
operation.
INSTALLATION OF HUMCCLFP1025-A--
FAN POWERED HUMIDIFIER
Carrier’s HUMCCLFP1025-A-- fan powered humidifier can only be installed on the supply plenum of a forced-air system. This unit requires an external 115-vac (fused) plug-in receptacle near the equipment for proper operation.
It is recommended to install the humidifier where it can be easily serviced. Pad access can be easily obtained from either the top or bottom of unit. Always install humidifier downstream of an electronic air cleaner.
Step 1—Inspect Package and Check Equipment
Inspect the contents of packaged humidifier. File claim with shipping company prior to installation if shipment is damaged or incomplete. The package should contain:
1. Humidifier and media assembly
2. Humidistat
3. Template
4. Owner’s Manual
5. Warranty Certificate
6. Solenoid valve
7. Saddle valve assembly with adapter
8. Four sheet metal screws
9. Foam tape
10. Water noise reducer (use for water pressure over 60 psi)
11. Worm clamp for field-supplied drain tube
12. Humidifier maintenance instruction sticker
13. Carrier logo label
"N" COIL
VERTICAL HORIZONTAL
Fig. 5—Installation of HUMCCLFP1025-A--
Fan-Type Humidifier
Step 2—Select Location (See Fig. 5.)
Humidifier must be installed on supply plenum only. If furnace has air conditioning coil, be sure humidifier does not interfere with coil ends.
RED
BLUE
A98366
3
Page 4
Remember to provide clearance for maintenance and evaporator pad removal. To access pad remove top or bottom cover to expose assembly (turn knob counter-clockwise).
Step 3—Prepare Plenum Opening (See Fig. 2.)
1. Use template for marking humidifier opening.
2. Tape in place on plenum making sure template is level.
IMPORTANT: For humidifier to operate properly it must be level and mounted on a vertical surface.
3. Drill four 1/8-in. holes in plenum.
4. Cut opening in plenum using heavy solid lines on template as a guide.
Step 4—Mount the Humidifier (See Fig. 3.)
1. Attach foam tape on inside of mounting flange.
2. Hook bottom notch of humidifier on opening cut in plenum.
3. Push top of humidifier to plenum aligning screw holes with flange.
4. Align, level, and secure using top screws first.
5. Insert bottom screws and tighten all screws for air tight seal.
Step 5—Install Drain Line
1. Use 1/2- or 5/8-in. vinyl tubing (field supplied) to connect drain on bottom of humidifier housing to an open drain.
2. Use supplied worm drain clamp to hold drain tubing in position over drain fitting outlet.
Unit may leak if drain tubing is misapplied. Do not insert tubing inside of drain fitting outlet.
3. Make sure line is free of traps due to sagging and has sufficient pitch to drain.
Step 6—Make Water Connection
If garden hose is not used for water supply:
1. Mount saddle valve on water line according to instructions supplied with saddle valve.
2. Run 1/4-in. diameter (water line grade) tubing from saddle valve to adapter on solenoid valve and tighten compression fittings.
IMPORTANT: If water pressure is higher than normal (60 psi), use noise suppression disk included in parts bag. (Read water noise reducer note located inside package for instructions). For normal operation, saddle valve need only be opened 1 full turn to meet performance requirements.
3. Open valve and check installation for leaks.
Step 7—Install Humidistat and Complete Wiring
1. Mount humidistat on inside wall, or return-air duct in accor­dance with section INSTALLATION OF HUMIDISTAT on page 10.
2. Wire red and blue low voltage. (See Fig. 6.)
3. Plug power cord in to 115-vac 60Hz source.
NOTE: Wiring must comply with National Electrical Code and any local codes or ordinances that may apply.
Step 8—Start-Up
1. Open saddle valve to permit water flow to the solenoid.
2. Check all connections for water leaks.
HUMIDIFIER HUMIDISTAT
HUMIDIFIER HUMIDISTAT
RED BLU
RED BLU
115V FIELD WIRING FAN TYPE UNITS ONLY
TRANSFORMER
(FIELD SUPPLIED)
24V
115V FIELD WIRING FAN TYPE UNITS ONLY
Fig. 6—Installation of Humidistat
on Fan-Type Humidifier
3. Set thermostat to call for heat. Set humidistat for highest humidity setting making sure contacts are closed. After a few minutes of operation, check the drain connection for leaks and to see if water is flowing through humidifier.
4. Reverse thermostat and humidistat settings to insure proper shutdown.
5. Reset thermostat to normal setting. Reset humidistat to rec­ommended setting.
Step 9—Final Steps
Attach humidifier maintenance instruction sticker to a visible location.
1. Inform homeowner of proper operation, maintenance, and humidistat setting.
a. If unit is installed during cooling season set humidistat for
summer setting (OFF or lowest setting).
b. If installed during heating season, set unit for normal
operation.
INSTALLATION OF HUMCCSFP1016-A--
FAN POWERED HUMIDIFIER
Carrier’s HUMCCSFP1016-A-- fan powered humidifier can only be installed on the supply plenum of a forced-air system. This unit requires an external 115-vac (fused) plug-in receptacle near the equipment for proper operation.
It is recommended to install the humidifier where it can be easily serviced. Pad access door can be easily converted from right to the left hand side. Always install humidifier downstream of an electronic air cleaner.
Step 1—Inspect Package and Check Equipment
Inspect contents of packaged humidifier. File claim with shipping company prior to installation, if shipment is damaged or incom­plete.
The package should contain:
1. Humidifier and media assembly
2. Humidistat
3. Template
4. Owner’s Manual
5. Warranty Certificate
6. Solenoid valve
4
24VAC
FURNACE
115V
FIELD
WIRING
A96010
Page 5
7. Saddle valve assembly with adapter
8. Four sheet metal screws
9. Foam tape
10. Noise suppressor (use for water pressure over 60 psi)
11. Worm clamp for field-supplied drain tube
12. Humidifier maintenance instruction sticker
13. Carrier logo label
"N" COIL
HORIZONTAL
VERTICAL HORIZONTAL
A96049
Fig. 8—Reversing Door Access
on HUMCCSFP1016-A--
A97098
Fig. 7—Installation of HUMCCSFP1016-A--
Fan-Type Humidifier
Step 2— Select Location (See Fig. 7.)
Humidifier must be installed on supply plenum only. If furnace has air conditioning coil, be sure humidifier does not interfere with coil ends. Remember to provide clearance for maintenance and evapo­rator pad removal. To reverse pad access from right to the left side:
1. Remove side door and media pad assembly.
2. Remove 4 screws and separate top assembly from lower mounting base. (See Fig. 8.)
3. Rotate lower mounting base 180 degrees, so side access door is now on left.
4. Snap together top assembly to mounting base and reinstall screws.
5. Replace media pad assembly (with distributor reservoir up) and side access door.
When re-installing media pad assembly into plastic housing, insure the assembly drain stub aligns into the drain outlet located in bottom of humidifier. Unit can leak if drain stub does not align with drain outlet. (See Fig. 9.)
Step 3—Prepare Plenum Opening (See Fig. 2.)
1. Use template for marking humidifier opening.
2. Tape in place on plenum making sure template is level.
MEDIA PAD ASSEMBLY
DRAIN OUTLET
HOUSING ENCLOSURE
DRAIN OUTLET
VINYL DRAIN TUBING
A97108
Fig. 9—Media Pad Assembly Installation
IMPORTANT: For humidifier to operate properly it must be level
and mounted on a vertical surface.
3. Drill four 1/8-in. holes in plenum.
4. Cut opening in plenum using heavy solid lines on template as a guide.
Step 4—Mount the Humidifier
1. Attach foam tape to back of mounting flange (exclude the off-set edge).
2. Hook off-set edge over opening cut in plenum.
3. Place humidifier in plenum aligning screw holes with flange.
4. Align, level, and tighten all screws for air tight seal.
Step 5—Install Drain Line
1. Use 5/8-in. vinyl tubing (field supplied) to connect drain on bottom of humidifier housing to an open drain.
2. Use clamp to hold drain tubing in position over drain fitting outlet.
Unit may leak if drain tubing is misapplied. Do not insert tubing inside of drain fitting outlet.
3. Make sure line is free of traps due to sagging and has sufficient pitch to drain.
5
Page 6
INLET HOLE
SOLENOID VALVE
TUBING
ENCLOSURE
INLET HOLE
HOUSING
ENCLOSURE
SEAT  SOLENOID  VALVE FLUSH  AGAINST INLET
A97107
Fig. 10—Top Mounting of Water Solenoid Valve
Step 6—Mount Solenoid Valve
The water solenoid valve should be mounted on top of humidifier enclosure.
1. To mount solenoid on top, see Fig. 10. a. Firmly press valve into the top inlet hole on enclosure. Seat
valve flush against inlet hole.
2. If alternate mounting of solenoid is required, see Fig. 11. a. To mount solenoid on side, use 3/8-in. ID, 1/2-in. OD vinyl
tubing (field supplied). Place tubing onto valve stem and
secure with clamp. b. Mount valve upside down securing to side of housing. c. Place open end of tubing into the top inlet hole.
IMPORTANT: Be careful not to kink tubing. Step 7—Make Water Connection
If garden hose is not used for water supply:
1. Mount saddle valve on water line according to instructions supplied with valve.
2. Run 1/4-in. diameter (water line grade) tubing from saddle valve to adapter on solenoid valve and tighten compression fittings.
IMPORTANT: If water pressure is higher than normal (60 psi), use noise suppression disk included in parts bag. (Read water noise reducer note located inside package for instructions). For normal operation, saddle valve need only be opened 1 full turn to meet performance requirements.
3. Open valve and check installation for leaks.
NOTE: Saddle valve is self piercing on copper lines; 1/4-in. hole must be drilled in steel or iron pipes. Use only a grounded drill or a hand drill to avoid shock hazard. Turn off water and drain the pipe prior to drilling 1/4-in. hole.
Step 8—Install Humidistat and Complete Wiring
1. Mount humidistat on inside wall, or return-air duct in accor­dance with section INSTALLATION OF HUMIDISTAT on page 10.
2. Wire red and blue low-voltage leads. (See Fig. 6.)
3. Plug power cord in to 115-vac 60Hz source.
NOTE: Wiring must comply with National Electrical Code and any local codes or ordinances that may apply.
POSITION TUBING  INSIDE INLET HOLE (CUT LENGTH  IF REQUIRED)
A97099
Fig. 11—Alternate Mounting of Solenoid Valve
on HUMCCSFP1016-A-- Humidifier
Step 9—Start-Up
1. Open saddle valve to permit water flow to the solenoid.
2. Check all connections for water leaks.
3. Set thermostat to call for heat. Set humidistat for highest humidity setting making sure contacts are closed. After a few minutes of operation, check the drain connection for leaks and to see if water is flowing through humidifier.
4. Reverse thermostat and humidistat settings to insure proper shutdown.
5. Reset thermostat to normal setting. Reset humidistat to rec­ommended setting.
Step 10—Final Steps
Attach humidifier maintenance instruction sticker to a visible location.
1. Inform homeowner of proper operation, maintenance, and humidistat setting.
a. If unit is installed during cooling season set humidistat for
summer setting (OFF or lowest setting).
b. If installed during heating season, set unit for normal
operation.
INSTALLATION OF HUMCCSBP2017-A--
BYPASS HUMIDIFIER
Carrier’s HUMCCSBP2017-A-- bypass humidifier can be in­stalled on either the supply or return plenum of a forced air system. This unit requires an external bypass duct between the supply- and return-air ductwork.
It is recommended to install the humidifier where it can be easily serviced. If this humidifier is installed with a central cooling system the bypass duct must have a shutoff damper to close during the cooling season. Always install humidifier downstream of an electronic air cleaner.
6
Page 7
Step 1—Inspect Package and Check Equipment
Inspect the contents of packaged humidifier. File claim with shipping company prior to installation if shipment is damaged or incomplete.
The package should contain:
1. Humidifier and media assembly
2. Humidistat
3. Template
4. 6-in. damper
5. Owner’s Manual
6. Warranty Certificate
7. Solenoid valve with bridge rectifier
8. Transfer tube
9. Saddle valve assembly with adapter
10. Three pair of miscellaneous screws
11. Six sheet metal screws
12. Foam tape
13. Water noise reducer (use for water pressure over 60 psi)
14. Worm clamp for field-supplied drain tube
15. Humidifier maintenance instruction sticker
16. Carrier logo label
Step 3—Prepare Plenum Opening (See Fig. 2.)
1. Use template for marking humidifier opening.
2. Tape in place on plenum making sure template is level.
IMPORTANT: For humidifier to operate properly it must be level and mounted on a vertical surface.
3. Drill four 1/8-in. holes in plenum.
SOLENOID
BROWN
VALVE ASSEMBLY
BYPASS UNITS
"N" COIL
ACCESS DOOR
DRILL (2) HOLES IN DUCT FOR #8 SHEETMETAL SCREWS
VERTICAL
HORIZONTAL
A98367
Fig. 12—Installation of
HUMCCSBP2017-A--
Bypass-Type Humidifier
Step 2—Select Location (See Fig. 12.)
Humidifier may be installed on either supply or return plenum. If furnace has air conditioning coil, be sure unit does not interfere with coil ends. Remember to provide clearance for maintenance and evaporator pad removal.
PAD
ACCESS
DOOR
A98368
Fig. 13—Mounting Solenoid Valve
on HUMCCSBP2017-A-- Humidifier
4. Cut opening in plenum using heavy solid lines on template as a guide.
Step 4—Mount Humidifier
1. Attach foam tape on inside of mounting flange.
2. Determine discharge direction.
3. If right-hand discharge is required: a. Remove side door and media pad assembly. b. Invert unit 180 degrees. c. Re-install media pad and door.
IMPORTANT: Always ensure pad assembly is in the upright position.
4. Attach solenoid valve to unit housing using two screws in upper mounting holes. (See Fig. 13.) Do not over tighten screws.
5. Attach transfer tube to solenoid valve and insert free end into inlet fitting on top of unit housing.
6. Attach bridge rectifier to solenoid valve.
7. Insert sheet metal screws into lower holes in plenum, pre­drilled using template.
8. Tighten screws until heads protrude approximately 3/16-in.
9. Hang humidifier on bottom screws and push top of humidifier to plenum, aligning top screw holes with flange, and insert screws.
10. Align and level unit.
11. Tighten all screws for air tight seal.
7
Page 8
Step 5—Install Bypass Duct
Attach field-supplied 6-in. diameter duct, elbow, or starting collar with field-supplied 1/4-in. zip screws. Install supplied 6-in. damper in 6-in. duct connector.
Do not support weight of bypass duct from humidifier — damage could result.
Step 6—Install Drain Line
1. Use5/8-in. ID vinyl tubing (field supplied) to connect drain on bottom of humidifier housing to an open drain.
2. Use worm clamp to hold drain tubing in position over drain
fitting outlet.
3. Make sure line is free of traps due to sagging and has sufficient pitch to drain.
to see if water is flowing through humidifier.
4. Reverse thermostat and humidistat settings to insure proper shutdown.
5. Reset thermostat to normal setting. Reset humidistat to rec­ommended setting.
Step 10—Final Steps
Attach humidifier maintenance instruction sticker to a visible location.
1. Inform homeowner of proper operation, maintenance, and humidistat setting.
a. If unit is installed during cooling season, close bypass
damper, set humidistat for summer setting (OFF or lowest setting).
b. If installed during heating season, set unit for normal
operation.
INSTALLATION OF HUMCCWTR2019-A--
BYPASS WATER SAVER HUMIDIFIER
Unit may leak if drain tubing is misapplied. Do not insert tubing inside of drain fitting outlet.
Step 7—Make Water Connection
If garden hose is not used for water supply:
1. Mount saddle valve on water line according to instructions supplied with valve.
2. Run 1/4-in. diameter (water line grade) tubing from saddle valve to adapter on solenoid valve and tighten compression fittings.
IMPORTANT: If water pressure is higher than normal (60 psi), use noise suppression disk included in parts bag. (Read water noise reducer note located inside package for instructions). For normal operation, saddle valve need only be opened 1 full turn to meet performance requirements.
3. Open valve and check installation for leaks.
Step 8—Install Humidistat and Complete Wiring
1. Mount humidistat on inside wall, or return-air duct in accor­dance with section INSTALLATION OF HUMIDISTAT on page 10.
2. Wire brown low-voltage leads to furnace control board, or
install a field-supplied step-down transformer 115vac/24vac 60Hz to power solenoid valve. (See Fig. 4.) Make sure bridge rectifier is attached to coil of solenoid valve.
NOTE: Wiring must comply with National Electrical Code and any local codes or ordinances that may apply.
Step 9—Start-Up
1. Open saddle valve to permit water flow to the solenoid.
2. Check all connections for water leaks.
3. Set thermostat to call for heat. Set humidistat for highest humidity setting making sure contacts are closed. After a few minutes of operation, check the drain connection for leaks and
Carrier’s HUMCCWTR2019-A-- bypass water saver humidifier can be installed on either the supply or return plenum of a forced-air system. This unit requires an external bypass duct between the supply- and return-air ductwork.
It is recommended to install the humidifier where it can be easily serviced. If this humidifier is installed with a central cooling system the factory-supplied 6-in. shutoff damper must be installed to close during the cooling season to prevent bypass air. Always install humidifier downstream of an electronic air cleaner.
Step 1—Inspect Package and Check Equipment
Inspect contents of packaged humidifier. File claim with shipping company prior to installation if shipment is damaged or incom­plete.
The package should contain:
1. Humidifier and media assembly
2. Humidistat
3. Template
4. Ten ft 1/4-in. water supply tubing
5. Owner’s Manual
6. Warranty Certificate
7. Support Bracket
8. One 1/4-in. blunt point screw
9. Saddle valve assembly
10. Four sheet metal screws
11. 6-in. damper
12. Worm clamp for field-supplied drain tube
13. Humidifier maintenance instruction sticker
14. Carrier logo label
Step 2—Select Location (See Fig. 14.)
Humidifier may be installed on either supply or return plenum. If furnace has air conditioning coil, be sure humidifier does not interfere with coil ends. Remember to provide clearance for maintenance and evaporator pad removal.
8
Page 9
GASKET
DRAIN PLUG
OVERFLOW TUBE
1
4
1
2 IN. LONG
1
4 IN. BLUNT
POINT SCREW
(LEFT HAND INSTALLATION SHOWN) FLOAT VALVE ASSEMBLY REINSTALLING MEDIA ASSEMBLY
SCREW
SUPPORT BRACKET
FLOAT
ARM
VALVE SEAT
PIN
RETAINER
BEARING
VALVE BODY
WASHER
Fig. 15—Valve and Media Assembly for HUMCCWTR2019-A--
A98370
Step 3—Prepare Plenum Opening (See Fig. 2.)
1. Use template for marking humidifier opening.
BYPASS UNITS
VERTICAL
"N" COIL
HORIZONTAL
DRILL (2) HOLES IN DUCT FOR #8 SHEETMETAL SCREWS
A98369
Fig. 14—Installation of HUMCCWTR2019-A--
Water Saver Humidifier
2. Tape in place on plenum making sure template is level.
IMPORTANT: For humidifier to operate properly it must be level and mounted on a vertical surface.
3. Drill four 1/8-in. holes in plenum.
4. Cut opening in plenum using heavy solid lines on template as a guide.
Step 4—Mount the Humidifier
Supply or return plenum mounting:
1. Remove unit access door by turning 2 pawl latches 1/2 turn and pulling door forward.
2. Determine whether unit is to be used for right- or left-hand installation and apply gasket tape (supplied) to unit flange intended to seat against duct.
3. Remove media assembly from cabinet by lifting bearing end of assembly out of bearing retainer and pulling assembly toward outlet duct, thus disengaging media from motor. Remove media through unit access opening.
4. Remove pin from float assembly and remove float and arm. Remove drain plug and water pan.
NOTE: Water pan must be tilted for removal.
5. Mount unit to duct using pre-drilled holes and four 1/2-in. long screws found in parts bag.
6. Level unit and attach support bracket to unit using 1/4-in. blunt point screw. Attach other end of support bracket to duct by drilling a hole and using remaining 1/4-in. long screw.
7. Re-install water pan and drain plug. Re-attach float arm to valve body by aligning holes in both parts and re-inserting pin.
NOTE: Pin may be re-inserted from either direction.
8. Re-install media assembly. Ensure that square shaft of media assembly is located inside mating opening of motor coupling. Ensure that bearing washer is located on interior side of bearing retainer. (See Fig. 15.)
Step 5—Install Bypass Duct
Attach field-supplied 6-in. diameter duct, elbow, or starting collar with field-supplied 1/4-in. zip screws. Install supplied 6-in. damper in 6-in. duct connector.
Do not support weight of duct from humidifier — damage could result.
Step 6—Install Drain Line
1. Use 1/2-in. ID field-supplied vinyl tubing or equivalent tubing to connect overflow drain connection on unit water pan to drain. (See Fig. 16.)
2. Use worm drain clamp to hold tubing in position over overflow drain connection.
IMPORTANT: Make sure that line is free of traps due to sagging and has sufficient pitch to drain.
3. Unit must be level to provide proper drainage.
Fig. 16—Water Level in HUMCCWTR2019-A--
Step 7—Make Water Connection
1. Mount saddle valve on cold water line according to local codes.
2. For plastic tube installations: run 1/4-in. OD tubing (supplied) from saddle valve to float valve. Prepare tubing ends with plastic compression sleeves and brass inserts, and tighten
A96013
9
Page 10
compression fittings. Plastic compression nut supplied with float valve should not be torqued greater than 25 in.-lb. For copper tubing installations: copper tubing may be connected to float valve by using a field-supplied 1/4 to 1/4 in. straight­through compression union. Run copper tubing to 1 side of compression union and use a standard compression sleeve. Tighten compression nut to torque recommended by manu­facturer. Attach approximately 6 in. of polyethylene supply tubing (supplied) between compression union and float valve. Prepare polyethylene tubing on both ends with brass inserts to prevent tubing collapse. Use compression nut at union to manufacturer’s recommended torque, tighten plastic nut on float valve to maximum of 25 in.-lb.
3. Open valve and check installation for leaks.
NOTE: Valve is self piercing on copper lines; 1/4-in. hole must be drilled in steel or iron pipes. Use only a grounded drill or a hand drill to avoid shock hazard. Turn off water and drain the pipe prior to drilling 1/4-in. hole.
Step 8—Install Humidistat and Complete Wiring
1. Mount humidistat on inside wall or return-air duct in accor­dance with section INSTALLATION OF HUMIDISTAT on page 10.
NOTE: Wiring must comply with national electrical code and any local codes or ordinances that may apply. (See Fig. 17.)
HUMIDISTAT
MOTOR
MOTOR
HUMIDISTAT
TRANSFORMER
(10-VA)
24V
24VAC
FURNACE
115V
FIELD
WIRING
b. If installed during heating season, set unit for normal
operation.
INSTALLATION OF HUMIDISTAT
The humidistat provides automatic control of humidifiers in central heating systems. It is designed for low voltage, wall, or surface duct mounting and contains a SPST snap-acting dustproof switch.
Disconnect power supply before making wiring connections to prevent possible electrical shock and equipment damage. Make wiring connections in accordance with Installation Instruction supplied with the humidifier.
1. Installer must be a trained, experienced service person.
2. Disconnect power supply before beginning installation.
3. Conduct a thorough checkout before leaving installation.
Step 1—Wall Mounting (Low Voltage)
1. Choose a location for humidistat about 5 ft above floor on inside wall with average room temperature and relative humidity conditions. Maximum ambient temperature of se­lected location must not exceed 125°F. Humidistat may be mounted directly on wall.
2. Drill a small hole in wall and run low-voltage wiring to location chosen. Pull about 6 in. of wire through hole. Plug opening to prevent drafts from affecting humidistat operation.
3. Remove knob, faceplate, and switch assembly from case by following steps listed below.
a. Remove knob by pulling away from casing. (See Fig. 18.) b. Lift off faceplate, starting at right side. Left end of
faceplate protrudes under lip of casing. (See Fig. 18.)
c. Remove switch by removing 2 screws in back of casing.
Pressing tab on case. Lift out control. (See Fig. 19.)
A96014
Fig.17—Humidistat Installation for
HUMCCWTR2019-A--
Step 9—Start-Up
1. Open saddle valve to permit water to flow to the solenoid valve.
2. Check all connections for water leaks.
3. Set thermostat to call for heat. Set humidistat at highest humidity setting to be sure the contacts are closed. After a few minutes of operation, check the drain connection for leaks and to see if water is flowing through humidifier.
4. Reverse thermostat and humidistat settings to insure proper shutdown.
5. Reset thermostat to normal setting. Reset humidistat to rec­ommended setting.
Step 10—Final Steps
Attach humidifier maintenance instruction sticker to a visible location.
1. Inform homeowner of proper operation, maintenance, and humidistat setting.
a. If unit is installed during cooling season, close bypass
damper, set humidistat for summer setting (OFF or lowest setting).
MOUNTING HOLES
KNOB
CASE
FACEPLATE
A97102
Fig. 18—Knob and Faceplate Removal
4. Make connections to screw terminals on switch assembly. Re-install switch into casing — secure with 2 short screws.
10
Page 11
CASING
CONTROL
TAB
A97103
Fig. 19—Switch Assembly Removal
5. Mount case horizontally over wires directly to wall using 2 long screws provided.
6. Replace faceplate and knob.
Step 2—Duct Mounting (Low Voltage)
1. Locate humidistat at least 8 in. upstream of humidifier in return-air duct. If mounting near elbow area, keep device 6 in. upstream of elbow so element will be affected by normal airflow. (See Fig. 20.)
2. Removeprotective backing from template furnished with each control and apply self-adhesive side on return air duct at selected location. Following instructions on template and in Fig. 21, drill 2 mounting holes and six 1/4-in. diameter sensing holes in duct. Sensing holes allow return air to reach nylon sensing element and operate humidistat.
NOTE: If desired, cut square hole in duct as indicated on template as an alternative to holes.
3. Remove protective backing from foam gasket provided with control and apply to template.
4. Run low-voltage wire from humidifier to template. Lay wire over 1 side of foam gasket. Wire can enter humidistat case from any direction.
IMPORTANT: Do not position wire directly under standoff pro­jections at back of case. If wire is under these projections, case will not seat tightly against gasket causing air leakage and possible improper operation.
5. Remove knob, faceplate, and switch assembly from case by following steps listed below.
a. Remove knob by pulling away from casing. (See Fig. 18.) b. Lift off faceplate, starting at right side. Left end of
faceplate protrudes under lip on casing. (See Fig. 18.)
c. Remove switch by removing 2 screws in back of casing.
Pressing tab on case. Lift out control. (See Fig. 19.)
6. Make connections to screw terminals on switch assembly. Re-install switch into casing — secure with 2 short screws.
7. While holding wire in place. Mount humidistat case horizon­tally on duct using 2 mounting screws provided. Tighten firmly so that gasket seals space around wires and between case and duct. (See Fig. 21.)
8. Replace faceplate and knob.
Step 3—Wiring
All wiring must comply with local codes and ordinances.
Step 4—Adjustment
Recommended humidistat setting should only be used as a guide. After adjustment of setting, allow at least 5 hr for equilibrium to be reached. Condensation on single pane windows or woodwork indicates excessive moisture. Condensation must not be allowed to continue for extended periods of time, or moisture damage can result. Lower humidistat setting in small steps until condensation disappears. However, if air is too dry, raise the setting.
ALTERNATE LOCATIONS
RETURN AIR RETURN AIR
5 IN. MIN. 15 IN. MIN.
RETURN AIR DUCT
BEST LOCATION
Fig. 20—Alternate Location Duct Mount Installation
A97104
11
Page 12
Step 5—Operation
When relative humidity falls to humidistat set point, the humidistat switch makes contact and starts humidifier. In some central unit humidifier systems, furnace fan must be operating before humidi­fier will start. An increase in relative humidity above set point will stop humidifier.
Step 6—Checkout
Recommended Humidistat Setting
OUTSIDE
TEMPERATURES
-20°F 15%
-10°F 20% (LO) 0°F 25%
+10°F 30% +20°F 35% +30°F 40% (MED)
RECOMMENDED
HUMIDISTAT SETTING
MAKE OPENING IN DUCT
DRILL SIX 1/4 IN.  DIAMETER HOLES
ALTERNATE PROCEDURE:
MOUNT HUMIDISTAT CASE
MOUNTING TEMPLATE
FOAM GASKET
CASE
MOUNTING SCREWS (2)
A97105
Fig. 21—Humidistat Installation Schematic
Copyright 1998 CARRIER Corp. • 7310 W. Morris St. • Indianapolis, IN 46231 hum1si
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4 Tab 7a 9a
PC 101 Catalog No. 03HU-MC1 Printed in U.S.A. Form HUM-1SI Pg 12 7-98 Replaces: 49-4SI
Loading...