Carrier Humcclbp18a, Humcclfp1218, Humcclfp1318, P110lfp1418 Installation Instruction

1. Place unit on
flat surface, pull front cover up on right side. It snaps loose. Disconnect feed tube nozzle and lift evaporative
2. The unit is
assembled for left side dis­charge. If right discharge is nec­essary, remove the right and left screws from
the unit interior side walls and exchange the two sides.Reassemble with screws.
3. Draw a level
line on furnace
supply plenum at
least 11/2" above
furnace cabinet
to allow for water
supply line and
drain hose.
Accurately cut a plenum opening (Small Bypass Unit, 9
3
/8"W x 91/2"H and Large Bypass Unit, 93/4"W x 121/2"H), being careful to avoid injury from sharp edges.
4. Place the unit
into the plenum opening so that the locking tabs on the bottom are closed down onto the lower sheet metal
edge.While hold­ing the unit in place, install two screws at the top of the unit interior.
5. Install a 6"
collar in a con-
venient location
on the opposite
plenum. Slip on a
90˚elbow and
measure the
length of 6"
round duct required to make the connection.The 6" duct will fit into the round collar on the side of the unit. If the furnace has central air conditioning, add a duct damper.Assemble components with sheet metal screws.Suppor t bypass ducts in excess of 4' to prevent sagging.
6. Reattach feed
tube nozzle and
replace the evap-
orative assembly
complete with
the evaporative
media by fitting
the drain tube
into the round receptacle at the bottom of the unit. Push the assembly in at the top against the beveled tabs. Replace the front cover.
7. HUMIDISTAT INSTALLATION INSTRUCTIONS
The humidistat is designed for low voltage service to control humidifi­cation equipment. An increase in relative humidity expands the
nylon ribbon that opens the control switch to stop operation on the humidifier.A decrease in relative humidity revers­es the process and closes the control switch. Install the humidistat.
DISCONNECT ELECTRICAL POWER TO
FURNACE BEFORE PROCEEDING
LOCATION
a) Locate on inside wall of living area approxi-
mately 5' above floor, or in the furnace return air plenum. Use enclosed adapter plate for return air installation.
b) Do not locate control in the direct path of
furnace discharge air or drafts from open doors and windows.
c) Do not install where operation might be
affected by lamps, sunlight, fireplace registers, radiators, concealed air ducts and pipes, or room occupants.
d) The basic r ules for location of thermostats
also apply to humidistats.
GENERAL INSTRUCTIONS
a) DO NOT ATTEMPT TO REPAIR OR RECALI-
BRATE CONTROL. Controls requiring ser vice
should be returned to your distributor. b) Control must be installed using 24 volts! c) Make sure no bare wires are exposed or
insulation damaged. Insulation on wire should
extend to head of binding screws. d) Make sure all splices are mechanically and
electrically secure. e) To remove dirt or other foreign matter from
nylon ribbon and control interior, dust lightly
with a fine, soft brush.
8. Tap into a
water supply line with the saddle valve furnished. The humidifier will function with cold, hot, softened or unsoftened
water.The use of service hot water (140˚F MAX.) and constant blow­er operation will provide maximum evaporative capacities. NOTE:The saddle valve is designed to be fully opened or closed. Do not use it to regulate water flow.
TO INSTALL ON COPPER OR PLASTIC PIPE
a) Place r ubber gasket in center of hole in top
saddle clamp.Place top and bottom saddle clamp around water pipe. Using bolts, tighten saddle clamps evenly – clamps should be par­allel – DO NOT over-tighten.
b) Screw valve body into opening in top saddle
clamp and tighten. c) Tighten gland nut onto valve body. d) Install
1
/4" water supply line from humidifier
using compression fittings. e) You are now ready to pierce the pipe.Turn
handle until spindle is firmly seated into valve
body.The water pipe is now fully pierced.
Tur ning spindle in shuts valve off. Open valve
completely for normal operation.
TO INSTALL ON STEEL OR BRASS PIPE
a) Shut off water supply.Open any faucet to
relieve water pressure. b) Drill
3
/16" diameter hole into pipe where saddle
valve will be placed. c) Place rubber gasket in center of hole in top
saddle clamp. d) Place top saddle clamp assembly over hole so
that lance fits into hole. e) Place top and bottom saddle clamp around
water pipe. f) Screw valve body into opening in top saddle
clamp and tighten. g) Tighten gland nut onto valve body. h) Install 1/4" water supply line from humidifier
using compression fittings. NOTE: For pipe over 1" O.D., use 1/4"-20,
13/4" long bolts.
9. Connect tubing
from the saddle valve to the inlet side of the solenoid valve using
1
/4
" O.D. copper tubing (not furnished).
DOUBLE WRENCH TO PREVENT LEAKING AND VALVE BREAKA GE!
10. Connect
1
/2" I.D.plastic hose (not furnished) from unit to floor drain. Be sure drain hose has continuous slope. Use cau­tion if hose
clamp is used to not over tighten and crack drain spud. NOTE: Do not sweat or directly attach
metal drain line to fitting. Do not use solvent type adhesive when connecting plastic drain hose, since damage to fitting could result.
11. Open saddle
valve and turn on furnace.Turn up humidistat to operate unit. Allow unit to run until water is observed coming out of drain line.
Check to see if unit is watertight and all electrical components function properly. Reset humidistat to recommended level.
DP #10005592 5.01.02 © 2002 CAC/BDP Form: IM-HUM-02
P.O. Box 70 Indianapolis, IN 46206 Catalog: 63HU-M01
Loading...