Screw liquid chillers are designed to provide safe and
reliable service when operated within design specifications. When operating this equipment, use good judgment and safety precautions to avoid damage to
equipment and property or injury to personnel.
Be sure you understand and follow the procedures and
safety precautions contained in the machine instructions, as well as those listed in this guide.
DO NOT VENT refrigerant relief devices within a building. Outlet
from rupture disc or relief valve must be vented outdoors in accordance with the latest edition of ANSI/ASHRAE 15 (American
National Standards Institute/American Society of Heating, Refrigeration and Air-Conditioning Engineers) (Safety Code for Mechanical
Refrigeration). The accumulation of refrigerant in an enclosed space
can displace oxygen and cause asphyxiation.
PROVIDE adequate ventilation in accordance with ANSI/
ASHRAE 15, especially for enclosed and low overhead spaces.
Inhalation of high concentrations of vapor is harmful and may cause
heart irregularities, unconsciousness, or death. Intentional misuse can
be fatal. Vapor is heavier than air and reduces the amount of oxygen
available for breathing. Product causes eye and skin irritation.
Decomposition products are hazardous.
DO NOT USE OXYGEN to purge lines or to pressurize a machine
for any purpose. Oxygen gas reacts violently with oil, grease, and
other common substances.
DO NOT USE air to leak test. Use only refrigerant or dry nitrogen.
NEVER EXCEED specified test pressures. VERIFY the allowable
test pressure by checking the instruction literature and the design
pressures on the equipment nameplate.
DO NOT VALVE OFF any safety device.
BE SURE that all pressure relief devices are properly installed and
functioning before operating any machine.
RISK OF INJURY OR DEATH by electrocution. High voltage
is present on motor leads even though the motor is not running.
Open the power supply disconnect before touching motor leads or
terminals.
DO NOT WELD OR FLAMECUT any refrigerant line or vessel until
all refrigerant (liquid and vapor) has been removed from chiller.
Traces of vapor should be displaced with dry air or nitrogen and the
work area should be well ventilated. Refrigerant in contact with an
open flame produces toxic gases.
DO NOT USE eyebolts or eyebolt holes to rig heat exchangers or the
entire assembly.
DO NOT work on high-voltage equipment unless you are a qualified
electrician.
DO NOT WORK ON electrical components, including control
panels, switches, starters, or oil heater until you are sure ALL
POWER IS OFF and no residual voltage can leak from capacitors or
solid-state components.
LOCK OPEN AND TAG electrical circuits during servicing. IF
WORK IS INTERRUPTED, confirm that all circuits are deenergized
before resuming work.
AVOID SPILLING liquid refrigerant on skin or getting it into the
eyes. USE SAFETY GOGGLES. Wash any spills from the skin with
soap and water. If liquid refrigerant enters the eyes, IMMEDIATELY
FLUSH EYES with water and consult a physician.
EVERGREEN®
with Foxfire™ Compression Technology
and PIC III Controls
50/60 Hz
HFC-134a
NEVER APPLY an open flame or live steam to a refrigerant cylinder.
Dangerous over pressure can result. When it is necessary to heat
refrigerant, use only warm (110 F [43 C]) water.
DO NOT REUSE disposable (nonreturnable) cylinders or attempt to
refill them. It is DANGEROUS AND ILLEGAL. When cylinder is
emptied, evacuate remaining gas pressure, loosen the collar, and
unscrew and discard the valve stem. DO NOT INCINERATE.
CHECK THE REFRIGERANT TYPE before adding refrigerant to
the machine. The introduction of the wrong refrigerant can cause
machine damage or malfunction.
Operation of this equipment with refrigerants other than those
cited herein should comply with ANSI/ASHRAE 15 (latest edition).
Contact Carrier for further information on use of this machine with
other refrigerants.
DO NOT ATTEMPT TO REMOVE fittings, covers, etc., while
machine is under pressure or while machine is running. Be sure pressure is at 0 psig (0 kPa) before breaking any refrigerant connection.
CAREFULLY INSPECT all relief valves, rupture discs, and other
relief devices AT LEAST ONCE A YEAR. If machine operates in a
corrosive atmosphere, inspect the devices at more frequent intervals.
DO NOT ATTEMPT TO REPAIR OR RECONDITION any relief
valve when corrosion or build-up of foreign material (rust, dirt, scale,
etc.) is found within the valve body or mechanism. Replace the valve.
DO NOT install relief devices in series or backwards.
USE CARE when working near or in line with a compressed spring.
Sudden release of the spring can cause it and objects in its path to act
as projectiles.
DO NOT STEP on refrigerant lines. Broken lines can whip about and
release refrigerant, causing personal injury.
DO NOT climb over a machine. Use platform, catwalk, or staging.
Follow safe practices when using ladders.
USE MECHANICAL EQUIPMENT (crane, hoist, etc.) to lift or
move inspection covers or other heavy components. Even if components are light, use mechanical equipment when there is a risk of
slipping or losing your balance.
BE AWARE that certain automatic start arrangements CAN
ENGAGE THE STARTER, TOWER FAN, OR PUMPS. Open the
disconnect ahead of the starter, tower fan, and pumps. Shut off the
machine or pump before servicing equipment.
USE only repaired or replacement parts that meet the code requirements of the original equipment.
DO NOT VENT OR DRAIN waterboxes containing industrial brines,
liquid, gases, or semisolids without the permission of your process
control group.
DO NOT LOOSEN waterbox cover bolts until the waterbox has been
completely drained.
DOUBLE-CHECK that coupling nut wrenches, dial indicators, or
other items have been removed before rotating any shafts.
DO NOT LOOSEN a packing gland nut before checking that the nut
has a positive thread engagement.
PERIODICALLY INSPECT all valves, fittings, and piping for corrosion, rust, leaks, or damage.
PROVIDE A DRAIN connection in the vent line near each pressure
relief device to prevent a build-up of condensate or rain water.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 2
Ta b 5 e
Catalog No. 532-309Printed in U.S.A.Form 23XRV-1SIPg 1309 6-06Replaces: New
Do not open any valves or loosen any connections. The
23XRV machine may be shipped with a full refrigerant
charge. Some machines may be shipped with a nitrogen
holding charge as an option.
1. Inspect for shipping damage while machine is still on shipping conveyance. If machine appears to be damaged or
has been torn loose from its anchorage, have it examined
by transportation inspectors before removal. Forward
claim papers directly to transportation company. Manufac-
turer is not responsible for any damage incurred in transit.
2. Check all items against shipping list. Immediately notify
the nearest Carrier representative if any item is missing.
3. To prevent loss or damage, leave all parts in original packages until beginning installation. All openings are closed
with covers or plugs to prevent dirt and debris from entering machine components during shipping. A full operating
oil charge is placed in the oil sump before shipment.
IDENTIFY MACHINE (Fig. 1-4) — Refer to machine nameplate in Fig. 1. The machine model number, serial number, and
heat exchanger sizes are stamped on the Refrigeration Machine
nameplate located on the side of the VFD (variable frequency
drive) enclosure. Check this information against shipping
papers and job data.
INTRODUCTION
General —
wired, and leak tested. Installation (not by Carrier) consists
primarily of establishing water and electrical services to the
machine. The rigging, installation, field wiring, field piping,
and insulation of waterbox covers are the responsibility of the
contractor and/or customer. Carrier has no installation responsibilities for the equipment.
The 23XRV machine is factory assembled,
Job Data — Necessary information consists of:
• job contract or specifications
• machine location prints
• rigging information
• piping prints and details
• field wiring drawings
• starter manufacturer’s installation details
• Carrier certified print
a23-1547
Fig. 1 — Refrigeration Machine Nameplate
2
23XRV – High Efficiency
Variable Speed Screw Chiller
Cooler Size*
30-32
35-37
40-42
45-47
50-52
55-57
Condenser Size*
30-32
35-37
40-42
45-47
50-52
55-57
Economizer Option
E – With Economizer
N – No Economizer
R – Compressor
*First number denotes frame size.
†Maximum limits only. Additional application limits apply that may reduce these ampacities.
2.0 AC drive can be identified by its part number. See Fig. 5.
This number appears on the shipping label and on the VFD
nameplate.
Drive Input Component Location
— Figure 6 identifies the
control center components.
Identifying the Power Module by I.D. Number
— Each LiquiFlo 2.0 AC power module can be identified by its I.D. number.
See Fig. 5. This number appears on the shipping label and on the
power module’s nameplate. Power ratings are provided in
Table 1.
INSTALLATION REQUIREMENTS — Certain requirements
should be checked before continuing with the chiller’s electrical installation. Input power wire sizes, branch circuit protection, and control wiring are all areas that need to be evaluated.
Determining Wire Size Requirements
— Wire size should be
determined based on the size of the conduit openings, and
applicable local, national, and international codes (e.g., NEC
[National Electric Code]/CEC [California Energy Commission] regulations). General recommendations are included in
the Carrier field wiring drawing.
Conduit Entry Size
— It is important to determine the size of
the conduit openings in the enclosure power entry plate so that
the wire planned for a specific entry point will fit through the
opening. Do NOT punch holes or drill into the top surface of
the control center enclosure for field wiring. Do not punch
holes or drill into the top surface of the control center enclosure
for field wiring. Knockouts are provided in the back of the
control center for field control wiring connections.
Recommended Control and Signal Wire Sizes
— The recommended minimum size wire to connect I/O signals to the
control terminal blocks is 18 AWG (American Wire Gage).
Recommended terminal tightening torque is 7 to 9 in.-lb
(0.79 to 1.02 N-m).
Recommended Air Flow Clearances
— Be sure there is adequate clearance for air circulation around the enclosure.
A 6-in. (152.4 mm) minimum clearance is required wherever
vents are located in the VFD enclosure.
Match Power Module Input and Supply Power Ratings
— It
is important to verify that building power will meet the input
power requirements of the Machine Electrical Data nameplate
input power rating. Be sure the input power to the chiller
corresponds to the chiller’s nameplate voltage, current, and frequency. Refer to machine nameplate in Fig. 7. The machine
electrical data nameplate is located on the right side of the
control center.
PROVIDE MACHINE PROTECTION — Protect machine
and VFD enclosure from construction dirt and moisture. Keep
protective shipping covers in place until machine is ready for
installation.
If machine is exposed to freezing temperatures after water
circuits have been installed, open waterbox drains and remove
all water from cooler and condenser. Leave drains open until
system is filled.
It is important to properly plan before installing a 23XRV
unit to ensure that the environment and operating conditions
are satisfactory. The installation must comply with all requirements in the certified prints.
Rigging the Machine — The 23XRV machine can be
rigged as an entire assembly. Large interconnecting piping has
flanged connections that allow the compressor, cooler, and
condenser sections to be separated and rigged individually. In
addition, the VFD can be removed and rigged separately.
RIG MACHINE ASSEMBLY — See rigging instructions on
label attached to machine. Also refer to rigging guide (Fig. 8),
physical data in Fig. 9, and Tables 2-9B. Lift machine only fromthe points indicated in rigging guide. Each lifting cable or
chain must be capable of supporting the entire weight of the
machine.
Lifting machine from points other than those specified may
result in serious damage to the unit and personal injury.
Rigging equipment and procedures must be adequate for
machine weight. See Fig. 8 for machine weights.
NOTE: These weights are broken down into component
sections for use when installing the unit in sections. For the
complete machine weight, add all component sections and
refrigerant charge together. See Tables 5-9B for machine
component weights.
*Assumes both cooler and condenser nozzles on same end of chiller.
†1 or 3 pass length applies if either (or both) cooler or condenser is a 1 or 3 pass design.
NOTES:
1. Service access should be provided per American Society of Heating, Refrigeration, and Air Conditioning Engineers
(ASHRAE) 15, latest edition, National Fire Protection Association (NFPA) 70, and local safety code.
2. Allow at least 3 ft (915 mm) overhead clearance for service rigging for frame R compressor.
3. Certified drawings available upon request.
4. Marine waterboxes may add 6 in. to the width of the machine. See certified drawings for details.
5. ‘A’ length dimensions shown are for standard 150 psi design and victaulic connections. The 300 psi design and/or flanges will
add length. See certified drawings.
6. Dished head waterbox covers not available for 3 pass design.
B (Width)C (Height)
21277-63/
4
21277-63/
4
8
2200
8
2200
8
2305
4
2305
4
Table 3 — 23XRV Dimensions (Marine Waterbox)
HEAT EXCHANGER
SIZE
30 to 3214- 9449616-4
35 to 3716- 5
40 to 4215- 2
45 to 4716-11
50 to 5215- 3
A (Length, Marine Waterbox — not shown)
2-Pass*1 or 3 Pass†
ft-in.mmft-in.mmft-in.mmft-in.mm
3
/
1
/
2
3
/
4
1
/
4
1
/
2
501718-11/
464216-81/
516318-43/
466116-81/
4
4
4
4
2
49976-93/
55186-93/
50866-9
56076-93/
50937-121597-63/
55 to 5717- 0518218-556137-121597-6
MAXIMUM
B WIDTH
8
8
3
/
4
4
20677-25/
20677-25/
20767-61/
20767-61/
3
*Assumes both cooler and condenser nozzles on same end of chiller.
†1 or 3 pass length applies if cooler is a 1 or 3 pass design.
NOTES:
1. Service access should be provided per American Society of Heating, Refrigeration, and Air Conditioning Engineers
(ASHRAE) 15, latest edition, National Fire Protection Association (NFPA) 70, and local safety code.
2. Allow at least 3 ft (915 mm) overhead clearance for service rigging for frame R compressor.
3. Certified drawings available upon request.
4. Marine waterboxes may add 6 in. to the width of the machine. See certified drawings for details.
5. ‘A’ length and ‘B’ width dimensions shown are for standard 150 psi design and victaulic connections. The 300 psi design and/
or flanges will add length. See certified drawings.
*Rows with two entries list nozzle end and return end weights.
NOTE: Weight for NIH 2-pass cover, 150 psig (1034 kPa), is included in the heat exchanger weights shown in Table 7.
Frame 3Frame 4Frame 5Frame 3Frame 4Frame 5
Victaulic
Nozzles
Flanged
Victaulic
Nozzles
Flanged
Victaulic
Nozzles
Flanged
Victaulic
Nozzles
163/215 163/215 237/237 237/237 298/298 298/298
Flanged
Victaulic
Nozzles
Flanged
Victaulic
Nozzles
Flanged
RIG MACHINE COMPONENTS — Refer to Fig. 10-26 and
Carrier Certified Prints for machine component disassembly.
IMPORTANT: Only a qualified service technician
should perform this operation.
Do not attempt to disconnect flanges while the machine is
under pressure. Failure to relieve pressure can result in
personal injury or damage to the unit.
Before rigging the compressor remove control panel and
control center.
NOTE: Label each wire before removal when wiring must be
disconnected (see Fig. 10 and 11). Clip all wire ties necessary
when removing pressure and temperature sensors. Disconnect
all pressure transducer wires at the sensor. Temperature sensors
cannot be disconnected from their cables; remove temperature
sensors from their thermowells and label as required.
11
CONDENSER
PRESSURE
CABLE
CABLE TRAY CONTAINING
VAPORIZER HTR CONDUIT
OIL HEATER CONDUIT
OIL PUMP CONDUIT
OIL SUMP TEMP. CABLE
OIL SUMP PRESS. CABLE
OIL PRESS. CABLE
OIL RECLAIM ACTUATOR CABLE
HGBP CONDUIT (OPTIONAL)
CONTROL
PA NE L
MOTOR TEMPERATURE
CABLE
a23-1558
WATER SENSOR CABLES
FOR NOZZLE ARRANGEMENTS
A,B,C,E,F,P,Q,R,T,&U
(SAME FOR OTHER END
OF MACHINE)
the 23XRV allows for disassembly at the job site so that
individual components may be moved through existing doorways. Use the following procedures to separate the machine
components.
Suggested locations to cut piping will minimize the width of
the condenser/economizer assembly.
SEPARATE COOLER AND CONDENSER
IMPORTANT: If the cooler and condenser vessels
must be separated, the heat exchangers should be kept
level by placing a support plate under the tube sheets.
The support plate will also help to keep the vessels
level and aligned when the vessels are bolted back
together.
NOTE: For steps 1 through 13 refer to Fig. 12. The cooler has
been removed from the picture to show the pipes and lines that
must be cut.
Check that the holding charge has been removed from the
chiller.
1. Place a support plate under each tube sheet to keep each
vessel level.
2. Remove cooler relief valve and relief valve vent piping.
3. Cut the motor cooling refrigerant drain line.
4. Rig the suction elbow and disconnect the compressor
suction line at the cooler and compressor. Remove bolts
from the vaporizer vent line flange.
5. Cut the VFD cooling drain line.
6. Cut the oil reclaim line(s).
7. Cut the hot gas bypass line between the HGBP (hot gas
bypass) solenoid valve and the cooler feed line.
8. Unbolt the cooler liquid feed line near the economizer or
condenser float chamber at the flanged connection.
Temporarily secure the in-line economizer orifice plate
(economized chillers only) to the economizer flange (see
Fig. 12).
17
16
15
14
5
13
a23-1560
1—Suction Elbow (Unbolt)11 — VFD Cooling Drain Line
2—Vaporizer Vent Line (Unbolt)12 — Oil Reclaim Line (Cut)
3—Motor Cooling Line (Unbolt)13 — Vaporizer Hot Gas Return Line (Cut)
4—Motor Cooling Drain Line (Cut)14 — Discharge Isolation Valve (Optional)
5—Tubesheet Mounting Bracket15 — Condenser Relief Valves (Unscrew)
6—Bearing Oil Drain Line16 — Discharge Temperature Sensor
7—Support Plate17 — Discharge Pipe Assembly Relief Valve (Unscrew)
8—In-Line Economizer Orifice Plate18 — Discharge Pressure Sensor
9—Cooler Liquid Feed LIne (Unbolt)19 — Discharge Pressure Switch
10 — Hot Gas Bypass Line (Cut)
19
18
12
11
1
2
3
4
5
6
5
10
9
8
7
Fig. 12 — Cooler/Discharge Pipe Assembly Removal
13
9. Cut the vaporizer refrigerant return line as shown.
10. Disconnect all sensors with cables that cross from
the condenser side of the machine to the cooler side
including:
a. Evaporator refrigerant liquid temperature sensor.
See Fig. 13.
b. Entering and leaving chiller liquid temperature
sensors. See Fig. 14.
c. Evaporator pressure sensor.
11. Disconnect the tubesheet mounting brackets from the
vessel connectors on the tube cooler tubesheet.
12. Cover all openings.
13. Rig the cooler away from the condenser/compressor.
NOTE: To reassemble, follow steps in reverse order. Connect
sensors and cables after major components have been secured
to reduce the risk damaging them.
OPTIONAL
HOT GAS
BYPASS LINE
Do not rig the condenser before the control center and
compressor are removed. The condenser/compressor
assembly has a high center of gravity and may tip over
when lifted at the tubesheet rigging points, which could
result in equipment damage and/or serious personal injury.
REMOVE THE CONTROLS/DRIVE ENCLOSURE
FROM THE CONDENSER — Confirm that the power
supply disconnect is open and all safety procedures are
observed before removing the VFD. This procedure minimizes
the number of sensors and cables that need to be disconnected.
Do not attempt to remove the VFD without first isolating
the refrigerant charge in the condenser. Damage to one of
the motor terminals during VFD removal will result in an
uncontrolled refrigerant leak.
a23-1635
Fig. 13 — Evaporator Refrigerant Liquid
Temperature Sensor on Bottom of Cooler
LEAVING CONDENSER
LIQUID TEMPERATURE
SENSOR
EVAPORATOR
REFRIGERANT
LIQUID
TEMPERATURE
SENSOR
COOLER
REFRIGERANT
PUMPOUT
VALV E
LEAVING CHILLED
LIQUID TEMPERATURE
SENSOR
1. Close the 2 filter drier isolation valves (Fig. 15) and the
2 VFD isolation valves. Isolate the refrigerant charge into
the condenser to prevent a refrigerant leak if one of the
motor terminals is accidentally damaged during VFD
removal or installation. Evacuate the VFD coldplate
through the Schrader valve (Fig. 15) on the VFD drain
isolation valve.
2. Remove the shipping bracket between the VFD and the
compressor if it is still in place. Remove any conduits that
bring power to the VFD. See Fig. 16.
VFD
REFRIGERANT
COOLING
SOLENOID
VALV E
VFD
REFRIGERANT
COOLING
ISOLATION
VALV E
VFD
REFRIGERANT
STRAINER
FILTER DRIER
ISOLATION VALVE
a23-1564
FILTER
DRIER
MOTOR
COOLING
SIGHT
GLASS
FILTER DRIER
ISOLATION VALVE
SCHRADER
VALV E
VFD DRAIN
ISOLATION
VALV E
ENTERING CONDENSER
LIQUID TEMPERATURE
SENSOR
Fig. 14 — Chiller End View
a23-1563
ENTERING CHILLED
LIQUID TEMPERATURE
SENSOR
Fig. 15 — VFD Refrigerant Isolation Valves
14
SHIPPING
BRACKET
a23-1565
Fig. 16 — VFD Shipping Bracket
3. Remove the nuts that secure the terminal box transition
piece to the motor housing.
4. Disconnect the motor leads from the motor terminals
(Fig. 17). Note the position of the motor terminal cable
lugs so they can be reinstalled with sufficient clearance
away from surrounding structure.
5. Remove the motor temperature sensor leads (Fig. 17), the
motor ground lead, and the bolts that secure the VFD
enclosure to the terminal box transition piece.
6. Disconnect the communication cables from the back of
the ICVC (Fig. 18).
7. Disconnect the high pressure switch leads from terminal
strip TB1, terminals 15 and 16 (Fig. 19).
8. Unplug connectors CN1A, CN1B, CN2, and CN3
(Fig. 19).
9. Disconnect the control panel ground wire (Fig. 19) that is
located next to connectors CN1A and CN1B.
10. Disconnect the VFD cooling lines (Fig. 20) and cover all
openings.
11. Remove the 12 screws that secure the control panel to the
VFD enclosure. Tilt the control panel away from the back
of the control center.
12. Position the control panel on top of the condenser and
secure it in place to prevent damage.
a23-1567
Fig. 18 — ICVC Communication Cables
CONTROL PANEL
CONNECTOR CN1A
GROUND WIRE
CONNECTOR CN1B
MOTOR TERMINALS
MOTOR
TEMPERATURE
SENSOR TERMINAL
BLOCK
MOTOR
TEMPERATURE
CABLE
Fig. 17 — Motor Terminals
MOTOR TERMINAL
BOX FRAME
a23-1566
15
CONNECTOR
CN2
a23-1570
LOW VOLTAGE FIELD
WIRING TERMINAL STRIP
CONNECTOR CN3
Fig. 19 — Control Panel Connectors
HIGH
PRESSURE
SWITCH
CABLE
OIL HEATER CONDUIT ASY
3/4 IN. - 10 x 2 IN. LIFTING EYEBOLT WITH
SHOULDER OR SWIVEL HOIST RING
6000 LB (2722 KG) WORKING LOAD LIMIT
TYPICAL — CHICAGO HARDWARE P/N 28
GRAINGER P/N 5ZA63
OIL PUMP CONDUIT ASY
VAPORIZER HEATER CONDUIT ASY
VFD COOLING LINE
O-RING FACE SEAL
COUPLINGS
OIL RECLAIM
ACTUATOR CABLE
VFD COOLING
SOLENOID CABLE
a23-1571
TEMPERATURE SENSOR
PRESSURE SENSOR
CABLES
CABLES
Fig. 20 — Control Panel Back
Lifting the Control Center
— Care should be used to prevent
damage due to dropping or jolting when moving the control
center. A fork truck or similar means of lifting and transporting
may be used. Sling in a manner that will equalize the load at the
pickup points. Use a spreader bar if the angle of the sling is less
than 45 degrees relative to horizontal. Do not jolt while lifting.
Use the following procedure to lift the control center.
1. Remove the rubber hole plugs in the top of the control
center and fully thread in 4 eyebolts or swivel hoist rings
(see Fig. 21). Lifting hardware must have
3
/4 in.-10 x 2 in.
long threads and must have a working load limit of at
least 6000 lb (2722 kg). Typical eyebolts are Chicago
Hardware (size 28) or Grainger (P/N 5ZA63).
2. Attach a sling to the four lifting eyebolts. Make certain
that the angle of the sling is not less than 45 degrees
relative to horizontal.
3. Using an overhead or portable hoist (minimum 2 ton
rated capacity), attach a free-fall chain to the sling
secured to the drive. Take up any slack in the chain.
4. Rig the control center and remove the bolts that secure it
to the VFD mounting brackets on the condenser (see
Fig. 21).
5. Confirm that welding procedures comply with local
Pressure Vessel Codes before removing a portion of the
VFD support bracket from the condenser. Custom brackets should be fabricated if part of the VFD supports must
be cut off of the condenser to reduce the width of the
condenser assembly. Clamp ¼-in. plates over both sides
of the VFD bracket and drill two pairs of holes that
LIFTING
EYEBOLT
45° MIN
a23-1561
Fig. 21 — Control Center Lifting Points
straddle the line along which the VFD brackets will be
cut. This will allow the VFD brackets to be reinstalled
and welded in their original position.
NOTE: To reassemble, follow steps in reverse order. Connect
sensors and cables after major components have been secured
to reduce the risk damaging them. (See Fig. 22.)
REMOVE THE DISCHARGE PIPE ASSEMBLY FROM
THE CONDENSER
NOTE: For steps 1 through 6 refer to Fig. 12.
The condenser relief valve and relief valve vent piping should
be removed if they will interfere with discharge pipe assembly
rigging.
1. Remove the discharge pipe assembly relief valve and
relief valve vent piping.
2. Disconnect the compressor discharge temperature sensor.
3. Disconnect the compressor discharge pressure sensor and
remove the high discharge pressure switch sensor.
4. Rig the discharge pipe assembly and remove the bolts
from the compressor discharge and condenser inlet
flange. Note the position and orientation of the discharge
isolation valve on the condenser inlet flange.
5. Remove the discharge pipe assembly.
6. Cover all openings.
NOTE: To reassemble, follow steps in reverse order. Connect
sensors and cables after major components have been secured
to reduce the risk of damaging them.
16
Loading...
+ 36 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.