Carrier 30GTN, GTR, GUN, GUR040-420 Installation Instructions Manual

30GTN,GTR,GUN,GUR040-420
Remote Cooler Mounting Accessory
Installation Instructions
Part No. 30GT911050
50/60 Hz
SAFETY CONSIDERATIONS
Installation of this accessory can be hazardous due to sys­tem pressures, electrical components, and equipment location (such as a roof, or elevated structure).
Only trained, qualified installers and service technicians should install, start up, and service this equipment.
When installing this accessory, observe precautions in the literature and on any labels attached to the equipment, and all other safety precautions that may apply.
Follow all safety codes.
Wear safety glasses and work gloves.
Use care in handling and installing this accessory.
ELECTRIC SHOCK HAZARD To avoid the possibility of electrical shock,
open and tag all remote disconnects before installing this equipment.
INTRODUCTION
The remote cooler mounting accessory permits indoor relo­cation of the cooler from 30GTN, GTR, G UN, GUR units up to 75 ft (22 m) away from the base unit. Relocating the cooler introduces minimal line losses if correct piping practices are followed. See Table 1 for the number of accessory packages re­quired for each unit and for the package contents.
In addition to the parts supplied with the accessory package, the following material must be field-supplied:
refrigerant-grade liquid and suction line piping (length
determined by installation). See Table 2 for connection sizes.
pressure relief valves and fittings
suction flange gasket
suction line tubing insulation (length determined by installation)
5
/8-in. strain relief
conduit (length determined by installation)
Table 1 — Unit Application
UNIT 30GTN,
GTR, GUN,
GUR
040 045, 050 060, 070
080, 090,
230B, 245B
100, 110,
255B, 270B,
290B, 315B
130, 150,
230A, 245A
255A
170,190,
270A, 290A,
330A/B, 360A/B,
390B
210, 315A,
390A,
420A/B
LEGEND
EXV
— Electronic Expansion Valve
* For modular units (230-420), quantity listed is per module.
For modular units (230-420), 1 package required for Module A and 1 package required for Module B; total of 2 packages required per unit.
(QTY)
COOLER*
(1)
10HB040
(1)
10HB050
(1)
10HB070
(1)
10HB090
(1)
10HB110
(1)
10HB160
(1)
10HB200
(1)
10HB210
ACCESSORY
PACKAGES
REQUIRED†
1 1 1 1
1
1
1
1
PACKAGE
CONTENTS
2 Shutoff Valv es
200 ft (61 m)
5-Wire Jacket ed
Cable
2 100-ft (30.5 m)
EXV Cable
Assemblies
1 Junction Box
1 Junction Box
Cover
1 Screw,
3
8B-18 x
1
2 Screws, /4-14 x 5/
/
8
8
Table 2 — Cooler Refrigerant-Line Connection Sizes
UNIT 30GTN, GTR,
GUN, GUR
Circuit A Circuit B Circuit A Circuit B 040 045 050
060-110,
230B-315B
130, 150,
230A-255A
170-210, 270A-315A
330A/B-420A/B
LEGEND
ODS —
Outside Diameter, Sweat
* On unit sizes 040-110 and 230B-315B, the actual liquid line is
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 2 Tab 5 c
PC 903 Catalog No. 563-000 Printed in U.S.A. Form 30G-22SI Pg 1 6-99 Replaces: 30G-17SI
1 1 2
2 2 3
COOLER SUCTION LINE CONNECTIONS
60 Hz Units 50 Hz Units
5
/
8
5
/
8
1
/
8
1
/
8
5
/
8
1
/
8
15/ 15/ 21/
21/ 25/ 31/
7
8 8 8
8
8
8
/8 inch.
(in. ODS)
15/ 15/ 15/
21/ 25/ 31/
8 8 8
8
8
8
15/ 21/ 21/
21/ 25/ 31/
COOLER
LIQUID LINE
CONNECTIONS
(in. ODS)
8 8 8
8
8
8
11/8*
INSTALLATION
1. Inspect package contents for any missing or damaged parts. File a claim with the shipping agency if parts are damaged. Notify your Carrier representative if any item is missing.
2. Determine the new location for the cooler(s). Ensure that the new location supports the cooler weight and that there is enough room for service access and tube removal. See Table 1 to determine the model numbers and quantities of coolers in each unit. See Table 3 for cooler weights and Fig. 1 for cooler dimensions.
NOTE: Steps 3-20 below describe how to relocate and reinstall one cooler. For units with two coolers, per­form these for each cooler.
Table 3 — Nominal Cooler Weights
WEIGHT
COOLER
10HB040 10HB050 10HB070 10HB090 10HB110 10HB160 10HB200 10HB210
*Cooler weight when filled with water or brine.
(FILLED*)
Lb Kg Lb Kg
576 261 485 220 658 299 545 247 770 349 620 281
949 431 745 338 1080 491 860 391 1736 789 1320 600 2119 963 1630 741 2428 1104 1865 848
WEIGHT
(UNFILLED)
enough room to install the EXV or TXV (if used), sight glass, filter drier, and service valve. See Fig. 2. Also ensure that there is sufficient room to remove cooler tubes if required for future service.
New cooler location and supporting structures must be able to support the weight of the filled cooler.
6. At the base unit control box, (see Fig. 3) disconnect the other ends of the thermistor leads; make sure to label the leads. If applicable, disconnect the other ends of the EXV cables that came with the unit and discard them.
7. At the base unit, remove the liqui d li n e pi ping bet ween the manual shutoffs and the old cooler conections. The piping includes EXVs or TXVs, sight glasses, and fil­ter driers. See Fig. 2.
8. Reinstall the piping at the cooler; install the shutoff valves (supplied with the accessory) immediately upstream from the filter driers. See Fig. 2.
9. Following Carrier-recommended piping practices, install additional field-supplied liquid line piping in the required lengths to reconnect the cooler and base unit. As shown in Fig. 2, the new liquid lines between the service valves must each have a field-supplied and installed pressure relief valve.
3. Open and tag all electrical disconnects.
4. Remove the cooler from the base unit, following the directions in the base unit Installation, Start-up and Service Instructions. If required, strip back the insula­tion on the cooler tube sheets and use the 2 large holes in the top corners of the tube sheets for lifting. Make sure to label the thermistors with corresponding ther­mistor numbers for reinstallation. For u nits with elec­tronic expansion valves (EXVs), disconnect the electrical cables from the EXVs. For units with ther­mostatic expansion valves (TXVs); note the locations of the equalizer lines and sensor bulbs and detach them.
5. Transport the cooler to its new location, and bolt it in position according to the instructions for replacing a cooler in the base unit Installation, Start-Up and Ser­vice Instructions. Make sure the new location has
Do not shut off both service valves in either liquid line. Pressure can build within the trapped area. To avoid the possibility of personal injury or property damage, a field­supplied pressure relief valve must be installed in each liq­uid line between the two shutoff valves. See Fig. 2.
10. Following Carrier-recommended piping practices, replace the suction flange gaskets and install additional field-supplied suction line piping in the required lengths to reconnect the cooler and bas e unit. For units with TXVs: Replace the sensor bulbs and equalizer lines according to their original positioning. Make sure to insulate the TXV bulbs.
11. Following the instructions for replacing a cooler in the base unit Installation, S tart-up an d S ervice in struction , reinstall the thermistors in the cooler.
2
NOTE:
1. Dimensions are in inches. Dimensions in ( ) are
in millimeters.
2. All numbers in ( ) indicate cooler part numbers.
Fig. 1 — Cooler Dimensions
57.92 (1471) 69.67 (1770) 6.73 (171) 7.75 (197) 53.44 (1357) 4.51 (115) 2.21 (56) 14.32 (364) 13.44 (341) 9.92 (252) 3.60 (91)
69.92 (1776) 81.67 (2074) 6.73 (171) 7.57 (193) 65.44 (1662) 4.51 (115) 2.21 (56) 14.32 (364) 13.44 (341) 9.92 (252) 3.60 (91)
69.92 (1776) 81.67 (2074) 6.98 (177) 8.57 (218) 64.94 (1649) 4.51 (115) 2.46 (63) 16.32 (415) 15.44 (392) 11.17 (284) 4.10 (104)
94.09 (2390) 105.85 (2689) 8.70 (221) 8.57 (218) 85.68 (2176) 4.51 (115) 5.19 (132) 16.32 (415) 15.44 (392) 11.17 (284) 4.10 (104)
97.19 (2469) 107.22 (2723) 8.94 (216) 9.19 (233) 86.12 (2187) 4.51 (115) 4.97 (126) 17.57 (446) 16.70 (424) 12.47 (317) 4.23 (107)
111.04 (2820) 118.84 (3019) 11.19 (284) 10.42 (265) 92.22 (2342) 1.78 (45) 10.41 (264) 19.98 (508) 19.12 (486) 13.42 (341) 4.85 (123)
111.04 (2820) 119.96 (3047) 11.69 (297) 11.39 (289) 92.22 (2342) 2.28 (58) 10.41 (264) 22.07 (561) 21.30 (541) 15.00 (381) 4.81 (122)
109.40 (2779) 121.67 (3090) 8.82 (224) 12.19 (310) 98.60 (2504) 5.63 (143) 3.80 (97) 23.58 (599) 22.70 (577) 16.79 (427) 4.66 (118)
10HB040
10HB050
10HB070
10HB090
10HB110
10HB160
10HB200
COOLER “A” “B” “C” “D” “E” “F” “G” “H” “J” “K” “L”
10HB210
12.29 (312) 1.25 (32) 4.51 (115) 4.42 (112) 5.20 (132) 3.04 (77) 3 (76) .58 (15) 2.87 (73) 2.87 (73)
10HB040
COOLER “M” “N” “P” “R” “S” “T” “V” “W” “X” “Y”
12.29 (312) 1.25 (32) 4.51 (115) 4.42 (112) 5.20 (132) 3.04 (77) 3 (76) .58 (15) 2.87 (73) 2.87 (73)
10HB050
15.42 (392) 1.25 (32) 5.22 (133) 5.00 (127) 5.99 (152) 3.46 (88) 4 (102) 0 2.87 (73) 2.87 (73)
15.42 (392) 1.25 (32) 5.22 (133) 5.00 (127) 5.99 (152) 3.46 (88) 4 (102) 0 2.87 (73) 2.87 (73)
15.42 (392) 1.25 (32) 5.60 (142) 5.50 (140) 6.62 (168) 3.46 (88) 5 (127) .64 (16) 2.87 (73) 2.87 (73)
10HB070
10HB090
10HB110
17.58 (447) 4.37 (111) 6.37 (162) 6.39 (162) 7.74 (197) 3.63 (92) 6 (152) .77 (20) 3.12 (79) 3.12 (79)
17.58 (447) 3.28 (83) 6.52 (166) 8.27 (210) 7.63 (194) 6.05 (154) 6 (152) 1.86 (47) 3.12 (79) 3.12 (79)
21.56 (548) 2.65 (67) 6.93 (176) 8.84 (225) 8.29 (211) 6.12 (156) 6 (152) .57 (15) 3.00 (76) 2.87 (73)
10HB160
10HB200
10HB210
3
Loading...
+ 5 hidden pages