NOTE: Some options/configurations not availaible on all series. Please consult Engineering Guides for model specific options.
UNIT TYPE:
CONDENSING UNIT
SIZE:
YDS
026
038
049
064
AIRFLOW CONFIGURATION:
2
N = NONE
CONTROL:
YDS - C = CXM
YCS - L = CXM
86754
C06N
3C
HEAT EXCHANGER OPTIONS:
C = COPPER WATER COIL
D = COPPER WATER COIL W/HOT WATER GENERATOR
N = CUPRO-NICKEL WATER COIL
P = CUPRO-NICKEL WATER COIL W/HOT WATER GENERATOR
NOTE: Above model nomenclature is a general reference. Consult individual specifi cation catalogs
for detailed information.
1211109
0
1
PACKAGING:
1=SINGLE PACK,DOMESTIC
REVISION LEVEL:
0 = CURRENT REV IS ION
VOLTAGE:
3 = 208V, 230V/1PH/60Hz
Rev.: 08/15/05D
Model Nomenclature: for Outdoor Split Series
38SS0 2 4C311
Prefix
WQS = Extended Range Ultra High
Efficiency Residential Outdoor Split
Series
018, 024, 030, 036, 042, 048, 060
1 2 3
WQS
Unit Size
4 5 67 89101112
Voltage
3 = 208-230/60/1
Standard
SS = Standard
Heat Exchanger Options
Standard
Packaging
1 = Single Pack, Domestic
Revision Level
1 = Current Revision
Copper Cupro-Nickel
CN
Carrier: Turn to the Experts
3
Page 4
Residential Split - 60Hz R22 &R410A
Rev.: 5 June, 2008
Safety
Safety
Warnings, cautions and notices appear throughout this
manual. Read these items carefully before attempting any
installation, service or troubleshooting of the equipment.
DANGER: Indicates an immediate hazardous situation, which
if not avoided will result in death or serious injury. DANGER
labels on unit access panels must be observed.
WARNING: Indicates a potentially hazardous situation, which
if not avoided could result in death or serious injury.
CAUTION: Indicates a potentially hazardous situation or an
unsafe practice, which if not avoided could result in minor or
moderate injury or product or property damage.
NOTICE: Notifi cation of installation, operation or
maintenance information, which is important, but which is
not hazard-related.
WARNING!
WARNING! All refrigerant discharged from this unit must be
recovered WITHOUT EXCEPTION. Technicians must follow
industry accepted guidelines and all local, state, and federal
statutes for the recovery and disposal of refrigerants. If a
compressor is removed from this unit, refrigerant circuit oil will
remain in the compressor. To avoid leakage of compressor oil,
refrigerant lines of the compressor must be sealed after it is
removed.
CAUTION!
CAUTION!
these units as a source of heating or cooling during the
construction process. The mechanical components and
fi lters will quickly become clogged with construction dirt
and debris, which may cause system damage.
To avoid equipment damage, DO NOT use
WARNING!
WARNING! Verify refrigerant type before proceeding.
Units are shipped with R-22, R-407c and R-410A (Puron®)
refrigerants. The unit label will indicate which refrigerant
is provided. The Puron® Application and Service Manual
should be read and understood before attempting to service
refrigerant circuits with R-407c or R-410A.
WARNING!
WARNING! To avoid the release of refrigerant into the
atmosphere, the refrigerant circuit of this unit must be
serviced only by technicians who meet local, state, and
federal profi ciency requirements.
4
Water-Source Heating and Cooling Systems
Page 5
Residential Split - 60Hz R22 &R410A
Rev.: 5 June, 2008
General Information
Inspection
Upon receipt of the equipment, carefully check the shipment
against the bill of lading. Make sure all units have been
received. Inspect the packaging of each unit, and inspect each
unit for damage. Insure that the carrier makes proper notation
of any shortages or damage on all copies of the freight bill and
completes a common carrier inspection report. Concealed
damage not discovered during unloading must be reported
to the carrier within 15 days of receipt of shipment. If not fi led
within 15 days, the freight company can deny the claim without
recourse. Note: It is the responsibility of the purchaser to fi le
all necessary claims with the carrier. Notify your equipment
supplier of all damage within fi fteen (15) days of shipment.
Storage
Equipment should be stored in its original packaging in a
clean, dry area. Store units in an upright position at all times.
Stack units a maximum of 3 units high.
Unit Protection
Cover units on the job site with either the original packaging
or an equivalent protective covering. Cap the open ends of
pipes stored on the job site. In areas where painting, plastering,
and/or spraying has not been completed, all due precautions
must be taken to avoid physical damage to the units and
contamination by foreign material. Physical damage and
contamination may prevent proper start-up and may result in
costly equipment clean-up.
5. Loosen compressor bolts on units equipped with
compressor spring vibration isolation until the
compressor rides freely on the springs. Remove shipping
restraints.
6. REMOVE COMPRESSOR SUPPORT PLATE 1/4”
SHIPPING BOLTS (2 on each side) TO MAXIMIZE
VIBRATION AND SOUND ATTENUATION (R22 indoor
units only).
7. Locate and verify any hot water generator (HWG) or
other accessory kit located in the compressor section.
CAUTION!
CAUTION! DO NOT store or install units in corrosive
environments or in locations subject to temperature or
humidity extremes (e.g., attics, garages, rooftops, etc.).
Corrosive conditions and high temperature or humidity can
signifi cantly reduce performance, reliability, and service life.
Always move and store units in an upright position. Tilting
units on their sides may cause equipment damage.
NOTICE! Failure to remove shipping brackets from springmounted compressors will cause excessive noise, and could
cause component failure due to added vibration.
CAUTION!
Examine all pipes, fi ttings, and valves before installing any of
the system components. Remove any dirt or debris found in
or on these components.
Pre-Installation
Installation, Operation, and Maintenance instructions
are provided with each unit. Horizontal equipment is
designed for installation above false ceiling or in a ceiling
plenum. Other unit confi gurations are typically installed
in a mechanical room. The installation site chosen should
include adequate service clearance around the unit. Before
unit start-up, read all manuals and become familiar with the
unit and its operation. Thoroughly check the system before
operation.
Prepare units for installation as follows:
1. Compare the electrical data on the unit nameplate with
ordering and shipping information to verify that the
correct unit has been shipped.
2. Keep the cabinet covered with the original packaging
until installation is complete and all plastering, painting,
etc. is fi nished.
3. Verify refrigerant tubing is free of kinks or dents and that
it does not touch other unit components.
4. Inspect all electrical connections. Connections must be
clean and tight at the terminals.
CAUTION! CUT HAZARD - Failure to follow this caution
may result in personal injury. Sheet metal parts may have
sharp edges or burrs. Use care and wear appropriate
protective clothing, safety glasses and gloves when
handling parts and servicing heat pumps.
Carrier: Turn to the Experts
5
Page 6
Residential Split - 60Hz R22 &R410A
Rev.: 5 June, 2008
Equipment Selection
The installation of geothermal heat pump units and all
associated components, parts, and accessories which make
up the installation shall be in accordance with the regulations
of ALL authorities having jurisdiction and MUST conform to
all applicable codes. It is the responsibility of the installing
contractor to determine and comply with ALL applicable
codes and regulations.
General
Proper indoor coil selection is critical to system effi ciency.
Using an older-model coil can affect effi ciency and may
not provide the customer with rated or advertised EER
and COP. Coil design and technology have dramatically
improved operating effi ciency and capacity in the past 20
years. Homeowners using an older coil are not reaping these
cost savings and comfort benefi ts. NEVER MATCH AN R-22
INDOOR COIL WITH AN R-410A COMPRESSOR SECTION.
Newer indoor coils have a larger surface area, enhanced fi n
design, and grooved tubing. These features provide a larger
area for heat transfer, improving effi ciency and expanding
capacity. Typical older coils may only have one-third to onehalf the face area of these redesigned coils.
Table 1a: GT-PX Air Handler Matches for ARI Ratings
Indoor Coil Selection - GT-PX Split (50YDS)
Carrier Geothermal split system heat pumps are rated in
the ARI directory with a specifi c indoor coil match. GT-PX
Split (50YDS) models are rated with Carrier/Bryant FV4 or
FE4 series variable speed air handlers as shown in Table
1a. Other brands of air handlers may attain the same ARI
ratings providing that the specifi cations meet or exceed
those listed in Table 1a AND Table 1b. An ECM motor
and TXV is required. Cap tubes and fi xed orifi ces are not
acceptable. PSC fans may be used if matched to Table 1b,
but will not meet ARI ratings. If using PSC fan, compressor
section must be operated as a single stage unit (i.e. wired for
either 1st stage or 2nd stage). Without the ability to vary the
airfl ow, supply air temperatures may not be acceptable if the
compressor is allowed to change stages when used with a
PSC fan motor.
Compressor Section026038049064
Air Handler
Model FV4
003005006006
RefrigerantR-410A
Metering DeviceTXV (required)
Air Coil
Type
Rows - Fins/in.
Face Area (sq. ft.)
Cabinet Confi gura-
Slope
3 - 14.5
3.46
A
3 - 14.5
5.93
Upfl ow/Downfl ow/Horizontal (Multipoise)
A
3 - 14.5
7.42
A
3 - 14.5
7.42
tion
ECM Settings for
ARI Ratings
(FV4 Fan Coil)
AC/HP size: 036
System Type:
Comfort AC/HP
CFM Adjust: Nom
AC/HP size: 036
System Type:
HP-Effi c AC/HP
CFM Adjust: High
AC/HP size: 048
System Type:
Comfort AC/HP
CFM Adjust: High
AC/HP size: 060
System Type:
Comfort AC/HP
CFM Adjust: High
Fan Motor Type - HPECM - 1/2ECM - 1/2ECM - 3/4ECM - 3/4
6
Water-Source Heating and Cooling Systems
Page 7
Residential Split - 60Hz R22 &R410A
Table 1b: GT-PX Air Handler Characteristics for Brands other than Above Models
Rev.: 5 June, 2008
Equipment Selection
Model*
Nominal
Tons*
Evaporator
Temp (ºF)
CFM
Capacity
(MBtuh)**
026 - Part Load1.55053019.2 - 22.4
026 - Full Load2.05288024.2 - 28.2
038 - Part Load2.55170025.2 - 29.2
038 - Full Load3.050120034.5 - 40.1
049 - Part Load3.547100034.3 - 39.9
049 - Full Load4.048165046.3 - 53.8
064 - Full Load5.048185054.5 - 63.3
* Nominal tons are at ARI/ISO 13256-1 GLHP conditions. Two-stage units may be operated in single-stage mode if desired, where smaller
capacity is required. For example, a model 026 may be used as a 1-1/2 ton unit if “locked” into 1st stage operation only. If PSC fan is used,
unit must be “locked” into either 1st or 2nd stage. An ECM fan is required for two-stage operation and for ARI ratings. Size air handler for
“Full Load” if operating in two-stage mode.
**When selecting an air handler based upon the above conditions, choose entering WB temperature of 67ºF. Use evaporator temperature,
CFM and capacity requirements as listed above. The air handler capacity must be at least at the minimum capacity shown in the table in
order for the ARI rating condition to be valid. See Figure 1 for an example selection.
Indoor Coil Selection - R-22 Units
Geothermal split system heat pumps with R-22 refrigerant
are rated in the ARI directory with a “generic” indoor
coil match and PSC fan. Selection of air handlers that
attain the published ARI ratings must meet or exceed the
specifi cations listed in Table 2. A TXV is required. Cap tubes
and fi xed orifi ces are not acceptable.
Table 2: R-22 Air Handler Characteristics
Model*
Nominal
Tons*
0181.55060018.5 - 21.3
0242.04780025.5 - 29.3
0302.549100031.5 - 36.2
0363.048120037.0 - 42.5
0423.545140042.2 - 48.5
0484.046160050.0 - 57.5
0605.045200058.0 - 66.7
* Nominal tons are at ARI/ISO 13256-1 GLHP conditions.
**When selecting an air handler based upon the above conditions, choose entering WB temperature of 67ºF. Use evaporator temperature,
CFM and capacity requirements as listed above. The air handler capacity must be at least at the minimum capacity shown in the table in
order for the ARI rating condition to be valid. See Figure 1 for an example selection.
Evaporator
Temp (ºF)
CFM
Capacity
(MBtuh)**
Carrier: Turn to the Experts
7
Page 8
Residential Split - 60Hz R22 &R410A
Rev.: 5 June, 2008
Equipment Selection
Air Handler Selection Example
Figure 1 shows a typical performance table for a heat pump air
handler. Suppose the evaporator temperature required is 50ºF,
the capacity required is 35,000 Btuh and the airfl ow required
is 1,200 CFM. Each evaporator temperature listed in the table
shows three wet bulb temperatures. As recommended in the
table notes above, select the 67ºF WB column. At 1,200 CFM,
the model 003 capacity is 36 MBtuh, which is higher than the
minimum capacity required of 35,000 Btuh. In this example,
model 003 would be the appropriate match.
Figure 1: Selecting Air Handler
Utilizing the Existing Air Handler or Coil (R22 units only)
It is recommended that a new coil or air handler be installed
with any geothermal split system compressor section due
to the low initial cost of the additional equipment versus the
reliability and benefi t of new technology, increased reliability
and warranty. However, if the existing air handler must be used
(R22 systems only), the following conditions apply:
• If the existing coil currently uses an orifi ce, the orifi ce
must be removed and replaced with a TXV. If the coil
utilizes capillary tubes, it will not operate properly with the
geothermal split system and should be replaced.
• If life expectancy of indoor coil (and associated components
- fan, cabinet, etc.) is less than 7-10 years, indoor section
should be replaced.
8
Water-Source Heating and Cooling Systems
Page 9
Residential Split - 60Hz R22 &R410A
Rev.: 5 June, 2008
Installation
NOTICE! Failure to remove shipping brackets from springmounted compressors will cause excessive noise, and could
cause component failure due to added vibration.
The installation of water source heat pump units and all
associated components, parts and accessories which make
up the installation shall be in accordance with the regulations
of ALL authorities having jurisdiction and MUST conform to
all applicable codes. It is the responsibility of the installing
contractor to determine and comply with ALL applicable
codes and regulations.
Removing Existing Condensing Unit (Where Applicable)
1. Pump down condensing unit. Close the liquid line
service valve of existing condensing unit and start
compressor to pump refrigerant back into compressor
section. Then, close suction service valve while
compressor is still running to trap refrigerant in outdoor
section. Immediately kill power to the condensing unit.
2. Disconnect power and low voltage and remove old
condensing unit. Cut or unbraze line set from unit.
Remove condensing unit.
3. If condensing unit is not operational or will not pump
down, refrigerant should be recovered using appropriate
equipment.
4. Replace line set, especially if upgrading system from R22 to R-410A refrigerant. If line set cannot be replaced,
it must be thoroughly fl ushed before installing new
compressor section. R-410A compressors use POE
oil instead of mineral oil (R-22 systems). Mineral oil is
not compatible with POE oil, and could cause system
damage if not completely fl ushed from the line set.
“Indoor” Compressor Section Location
Both “indoor” and “outdoor” versions of the geothermal split
system compressor section are available. “Indoor” version
is not designed for outdoor installation. Locate the unit
in an INDOOR area that allows enough space for service
personnel to perform typical maintenance or repairs without
removing unit. Units are typically installed in a mechanical
room or closet. Never install units in areas subject to freezing
or where humidity levels could cause cabinet condensation
(such as unconditioned spaces subject to 100% outside air).
Consideration should be given to access for easy removal
of service access panels. Provide suffi cient room to make
water, electrical, and line set connections.
2. Provide adequate clearance for maintenance and
service. Do not block access panels with piping, conduit
or other materials.
3. Provide access for servicing the compressor and coils
without removing the unit.
4. Provide an unobstructed path to the unit within the
closet or mechanical room. Space should be suffi cient to
allow removal of the unit, if necessary.
5.
In limited side access installations, pre-removal of the
control box side mounting screws will allow control box
removal for future servicing (R22 units only).
6. Provide access to water valves and fi ttings and
screwdriver access to the unit side panels and all
electrical connections.
“Outdoor” Compressor Section Loacation
Locate the unit in an outdoor area that allows easy loop
and lineset access and also has enough space for service
personnel to perform typical maintenance or repairs. The
“outdoor” compressor section is usually installed on a
condensor pad directly outside the lineset access into the
building. The service valve side can be located toward
the building, keeping the loop access end away from the
building. Conform to the following guidelines when selecting
unit location:
1. Provide adequate access for loop trench excavation.
2.
Locate unit directly outside lineset penetration if possible.
Utilize existing condensor pad where possible.
3. Provide access for servicing and maintenance.
“Outdoor” compressor section may be mounted on a
vibration isolation pad with loop access hole as shown in
Figure 3. When mounting on an existing concrete condenser
pad, 3” [76mm] holes should be bored through the pad to
accomodate the pipe (1-1/4” - 32mm) and insulation (1/2”
[13mm] wall thickness). Figure 3 illustrates location and
dimensions of the holes required.
Air Handler Installation
This manual specifi cally addresses the compressor section
of the system. Air handler location and installation should
be according to the instructions provided with the air
handling unit.
Any access panel screws that would be diffi cult to remove
after the unit is installed should be removed prior to setting
the unit. Refer to Figure 2 for an illustration of a typical
installation. Refer to “Physical Dimensions” section for
dimensional data.
selecting unit location:
Install the unit on a piece of rubber, neoprene or other
1.
mounting pad material for sound isolation. The pad should
be at least 3/8” [10mm] to 1/2” [13mm] in thickness.
Extend the pad beyond all four edges of the unit.
Conform to the following guidelines when
Carrier: Turn to the Experts
9
Page 10
Residential Split - 60Hz R22 &R410A
Air Pad with
access hole
Existing Pad larger than 22" x 33" [54 x 84cm]
Bottom view
of Unit
22" x 33"
[56 x 84cm]
Flow
Controller
8.00"
25"
[63.5cm]
Drill 3" [76mm] holes for
clearance of 1-1/4" [32mm] pipe
with 1/2" [13mm] wall insulation
5.5"
[14.0cm]
8.25"
[21.0cm]
Gasket
Swivel Nut
Stainless steel
snap ring
Brass Adaptor
Hand Tighten
Only!
Do Not
Overtighten!
Rev.: 5 June, 2008
Installation
Figure 2: 50YDS/GT-GS Installation
Figure 3: GT-S Installation
External Flow Controller Mounting
The Flow Controller can be mounted beside the unit as
shown in Figure 7. Review the Flow Controller installation
manual for more details.
Water Connections-Residential (Distributor) Models
Residential models utilize swivel piping fi ttings for water
connections that are rated for 450 psi (3101 kPa) operating
pressure. The connections have a rubber gasket seal
similar to a garden hose gasket, which when mated to the
10
fl ush end of most 1” threaded male pipe fi ttings provides
a leak-free seal without the need for thread sealing tape or
joint compound. Insure that the rubber seal is in the swivel
connector prior to attempting any connection (rubber seals
are shipped attached to the swivel connector). DO NOT
OVER TIGHTEN or leaks may occur.
Water-Source Heating and Cooling Systems
The female locking ring is threaded onto the pipe threads
which holds the male pipe end against the rubber gasket,
and seals the joint. HAND TIGHTEN ONLY! DO NOT
OVERTIGHTEN!
Figure 4: Water Connections (Indoor Compressor Section)
Page 11
Residential Split - 60Hz R22 &R410A
Rev.: 5 June, 2008
Installation
Internal Flow Controller Mounting “Outdoor” Compressor Section Only
The Flow Controller can be mounted in the “outdoor”
compressor section directly inside the cabinet as shown in
Figure 5. Remove the water legs from the outdoor unit at the
union fi ttings. Attached the AFC4T 1” MPT x o-ring fi ttings
to the removed water legs. Carefully attached the Flow
Controller to the loop piping and mount to the outdoor unit
using the mounting lugs attached to the unit. Insert the water
legs into the Flow Controller using the o-ring fi ttings. Re-
connect the water leg unions.
NOTICE! Opening in the bottom of the unit for loop piping
must be sealed to prevent rodents from getting into the
cabinet and damaging control wiring. Spray type foam may
be used to seal the opening(s).
Figure 6: AFC4T Connector
Figure 5: Water Connections (Outdoor Compressor Section)
1” IPT Water Connections
Mount Flow Controller
on studs provided
Wire pump power
using provided wires
for L1 and L2
GROUND-LOOP HEAT PUMP APPLICATIONS
CAUTION!
CAUTION! The following instructions represent industry
accepted installation practices for closed loop earth
coupled heat pump systems. Instructions are provided
to assist the contractor in installing trouble free ground
loops. These instructions are recommendations only.
State/provincial and local codes MUST be followed and
installation MUST conform to ALL applicable codes. It is
the responsibility of the installing contractor to determine
and comply with ALL applicable codes and regulations.
Pre-Installation
Prior to installation, locate and mark all existing underground
utilities, piping, etc. Install loops for new construction before
sidewalks, patios, driveways, and other construction has
begun. During construction, accurately mark all ground loop
piping on the plot plan as an aid in avoiding potential future
damage to the installation.
Piping Installation
The typical closed loop ground source system is shown in
Figures 7 and 8. All earth loop piping materials should be
limited to polyethylene fusion only for in-ground sections of
the loop. Galvanized or steel fi ttings should not be used at
any time due to their tendency to corrode. All plastic to metal
threaded fi ttings should be avoided due to their potential to
leak in earth coupled applications. A fl anged fi tting should
be substituted. P/T plugs should be used so that fl ow
can be measured using the pressure drop of the unit heat
exchanger.
Carrier: Turn to the Experts
11
Page 12
Residential Split - 60Hz R22 &R410A
Rev.: 5 June, 2008
Ground-Loop Heat Pump Applications
Earth loop temperatures can range between 25 and
110°F [-4 to 43°C]. Flow rates between 2.25 and 3 gpm
per ton [2.41 to 3.23 l/m per kW] of cooling capacity is
recommended in these applications.
Test individual horizontal loop circuits before backfi lling.
Test vertical U-bends and pond loop assemblies prior to
installation. Pressures of at least 100 psi [689 kPa] should be
used when testing. Do not exceed the pipe pressure rating.
Test entire system when all loops are assembled.
Flushing the Earth Loop
Once piping is completed between the unit, Flow Controller
and the ground loop (Figures 7 and 8), the loop is ready for
fi nal purging and charging. A fl ush cart with at least a 1.5 hp
[1.1 kW] pump is required to achieve enough fl uid velocity
in the loop piping system to purge air and dirt particles. An
antifreeze solution is used in most areas to prevent freezing.
All air and debris must be removed from the earth loop
piping before operation. Flush the loop with a high volume
of water at a minimum velocity of 2 fps (0.6 m/s) in all piping.
The steps below must be followed for proper fl ushing.
1. Fill loop with water from a garden hose through the fl ush
cart before using the fl ush cart pump to insure an even fi ll.
2. Once full, the fl ushing process can begin. Do not allow
the water level in the fl ush cart tank to drop below the
pump inlet line to avoid air being pumped back out to
the earth loop.
3. Try to maintain a fl uid level in the tank above the return
tee so that air cannot be continuously mixed back into
the fl uid. Surges of 50 psi (345 kPa) can be used to help
purge air pockets by simply shutting off the return valve
going into the fl ush cart reservoir. This “dead heads”
the pump to 50 psi (345 kPa). To purge, dead head the
pump until maximum pumping pressure is reached.
Open the return valve and a pressure surge will be sent
through the loop to help purge air pockets from the
piping system.
4. Notice the drop in fl uid level in the fl ush cart tank when
the return valve is shut off. If air is adequately purged
from the system, the level will drop only 1-2 inches (2.5
- 5 cm) in a 10” (25 cm) diameter PVC fl ush tank (about a
half gallon [2.3 liters]), since liquids are incompressible. If
the level drops more than this, fl ushing should continue
since air is still being compressed in the loop fl uid.
Perform the “dead head” procedure a number of times.
Note: This fl uid level drop is your only indication of air in
the loop.
Antifreeze may be added before, during or after the fl ushing
procedure. However, depending upon which time is chosen,
antifreeze could be wasted when emptying the fl ush cart
tank. See antifreeze section for more details.
Loop static pressure will fl uctuate with the seasons.
Pressures will be higher in the winter months than during
the cooling season. This fl uctuation is normal and should
be considered when charging the system initially. Run the
unit in either heating or cooling for a number of minutes to
condition the loop to a homogenous temperature. This is
a good time for tool cleanup, piping insulation, etc. Then,
perform fi nal fl ush and pressurize the loop to a static
pressure of 50-75 psi [345-517 kPa] (winter) or 35-40 psi
[241-276 kPa] (summer). After pressurization, be sure to
loosen the plug at the end of the Grundfos loop pump
motor(s) to allow trapped air to be discharged and to insure
the motor housing has been fl ooded. This is not required
for Taco circulators. Insure that the Flow Controller provides
adequate fl ow through the unit by checking pressure drop
across the heat exchanger and compare to the pressure
drop tables at the back of the manual.
Antifreeze
In areas where minimum entering loop temperatures drop
below 40°F [5°C] or where piping will be routed through
areas subject to freezing, antifreeze is required. Alcohols
and glycols are commonly used as antifreeze; however your
local sales manager should be consulted for the antifreeze
best suited to your area. Freeze protection should be
maintained to 15°F [9°C] below the lowest expected
entering loop temperature. For example, if 30°F [-1°C] is
the minimum expected entering loop temperature, the
leaving loop temperature would be 25 to 22°F [-4 to -6°C]
and freeze protection should be at 15°F [-10°C]. Calculation
is as follows:
30°F - 15°F = 15°F [-1°C - 9°C = -10°C].
All alcohols should be premixed and pumped from a
reservoir outside of the building when possible or introduced
under the water level to prevent fumes. Calculate the
total volume of fl uid in the piping system. Then use the
percentage by volume shown in Table 2 for the amount
of antifreeze needed. Antifreeze concentration should be
checked from a well mixed sample using a hydrometer to
measure specifi c gravity.
Low Water Temperature Cutout Setting
CXM or DXM Control
When antifreeze is selected, the FP1 jumper (JW3) should
be clipped to select the low temperature (antifreeze 13°F
[-10.6°C]) set point and avoid nuisance faults (see “Low
Water Temperature Cutout Selection” in this manual). NOTE:
Low water temperature operation requires extended range
equipment.
12
Water-Source Heating and Cooling Systems
Page 13
Residential Split - 60Hz R22 &R410A
Rev.: 5 June, 2008
Ground-Loop Heat Pump Applications
Table 1: Approximate Fluid Volume (U.S. gal. [L]) per
100' of Pipe
Fluid Volume (gal [liters] per 100’ [30 meters) Pipe)
Minimum Temperature for Low Temperature Protection
NOTICE! Cabinet opening around loop piping (outdoor
compressor section) must be sealed to prevent entry of
rodents that could potentially damage unit wiring by chewing
on the insulation.
NOTICE! Outdoor compressor section may not be tilted
more than 5 degrees from level. Damage to the compressor
or stress on the loop piping could result if unit is tilted. A
concrete pad, anchor posts and/or soil compaction may be
required to avoid tilting as ground settles.
21%
25%
25%
16%
22%
20%
10%
15%
14%
* Must not be denatured with any petroleum based product
Carrier: Turn to the Experts
13
Page 14
Residential Split - 60Hz R22 &R410A
Rev.: 5 June, 2008
Ground-Water Heat Pump Applications “Indoor” Compressor Section Only
Open Loop - Ground Water Systems
(“Indoor” Compressor Section Only)
The “outdoor” version of the compressor section may not
be used with open loop systems due to potential freezing of
water piping. Typical open loop piping is shown in Figure 9.
Shut off valves should be included for ease of servicing. Boiler
drains or other valves should be “tee’d” into the lines to allow
acid fl ushing of the heat exchanger. Shut off valves should
be positioned to allow fl ow through the coax via the boiler
drains without allowing fl ow into the piping system. P/T plugs
should be used so that pressure drop and temperature can be
measured. Piping materials should be limited to copper or PVC
SCH80. Note: Due to the pressure and temperature extremes,
PVC SCH40 is not recommended.
Water quantity should be plentiful and of good quality.
Consult Table 3 for water quality guidelines. The unit can
be ordered with either a copper or cupro-nickel water
heat exchanger. Consult Table 3 for recommendations.
Copper is recommended for closed loop systems and open
loop ground water systems that are not high in mineral
content or corrosiveness. In conditions anticipating heavy
scale formation or in brackish water, a cupro-nickel heat
exchanger is recommended. In ground water situations
where scaling could be heavy or where biological growth
such as iron bacteria will be present, an open loop system
is not recommended. Heat exchanger coils may over time
lose heat exchange capabilities due to build up of mineral
deposits. Heat exchangers must only be serviced by a
qualifi ed technician, as acid and special pumping equipment
is required. Desuperheater coils can likewise become scaled
and possibly plugged. In areas with extremely hard water,
the owner should be informed that the heat exchanger
may require occasional acid fl ushing. In some cases, the
desuperheater option should not be recommended due to
hard water conditions and additional maintenance required.
Water Quality Standards
Table 3 should be consulted for water quality requirements.
Scaling potential should be assessed using the pH/Calcium
hardness method. If the pH <7.5 and the Calcium hardness
is less than 100 ppm, scaling potential is low. If this method
yields numbers out of range of those listed, the Ryznar
Stability and Langelier Saturation indecies should be
calculated. Use the appropriate scaling surface temperature
for the application, 150°F [66°C] for direct use (well water/
open loop) and DHW (desuperheater); 90°F [32°F] for
indirect use. A monitoring plan should be implemented in
these probable scaling situations. Other water quality issues
such as iron fouling, corrosion prevention and erosion and
clogging should be referenced in Table 3.
Expansion Tank and Pump
Use a closed, bladder-type expansion tank to minimize
mineral formation due to air exposure. The expansion tank
should be sized to provide at least one minute continuous
run time of the pump using its drawdown capacity rating to
prevent pump short cycling. Discharge water from the unit
is not contaminated in any manner and can be disposed
of in various ways, depending on local building codes (e.g.
recharge well, storm sewer, drain fi eld, adjacent stream
or pond, etc.). Most local codes forbid the use of sanitary
sewer for disposal. Consult your local building and zoning
department to assure compliance in your area.
The pump should be sized to handle the home’s domestic
water load (typically 5-9 gpm [23-41 l/m]) plus the fl ow rate
required for the heat pump. Pump sizing and expansion
tank must be chosen as complimentary items. For example,
an expansion tank that is too small can causing premature
pump failure due to short cycling. Variable speed pumping
applications should be considered for the inherent energy
savings and smaller expansion tank requirements.
Water Control Valve
Note the placement of the water control valve in fi gure 9.
Always maintain water pressure in the heat exchanger by
placing the water control valve(s) on the discharge line
to prevent mineral precipitation during the off-cycle. Pilot
operated slow closing valves are recommended to reduce
water hammer. If water hammer persists, a mini-expansion
tank can be mounted on the piping to help absorb the
excess hammer shock. Insure that the total ‘VA’ draw of the
valve can be supplied by the unit transformer. For instance,
a slow closing valve can draw up to 35VA. This can overload
smaller 40 or 50 VA transformers depending on the other
controls in the circuit. A typical pilot operated solenoid valve
draws approximately 15VA (see Figure 24). Note the special
wiring diagrams for slow closing valves (Figures 25 & 26).
Flow Regulation
Flow regulation can be accomplished by two methods. One
method of fl ow regulation involves simply adjusting the ball
valve or water control valve on the discharge line. Measure
the pressure drop through the unit heat exchanger, and
determine fl ow rate from Tables 11a through 11b. Since
the pressure is constantly varying, two pressure gauges
may be needed. Adjust the valve until the desired fl ow of
1.5 to 2 gpm per ton [2.0 to 2.6 l/m per kW] is achieved. A
second method of fl ow control requires a fl ow control device
mounted on the outlet of the water control valve. The device
is typically a brass fi tting with an orifi ce of rubber or plastic
material that is designed to allow a specifi ed fl ow rate. On
occasion, fl ow control devices may produce velocity noise
that can be reduced by applying some back pressure from
the ball valve located on the discharge line. Slightly closing
the valve will spread the pressure drop over both devices,
lessening the velocity noise. NOTE: When EWT is below
50°F [10°C], a minimum of 2 gpm per ton (2.6 l/m per kW)
is required.
14
Water-Source Heating and Cooling Systems
Page 15
Residential Split - 60Hz R22 &R410A
Rev.: 5 June, 2008
Ground-Water Heat Pump Applications
Water Coil Low Temperature Limit Setting
For all open loop systems the 30°F [-1.1°C] FP1 setting
(factory setting-water) should be used to avoid freeze damage
to the unit. See “Low Water Temperature Cutout Selection” in
this manual for details on the low limit setting.
CAUTION!
CAUTION! Many units installed with a factory or fi eld
supplied manual or electric shut-off valve. DAMAGE WILL OCCUR if shut-off valve is closed during unit operation. A
high pressure switch must be installed on the heat pump
side of any fi eld provided shut-off valves and connected to
the heat pump controls in series with the built-in refrigerant
circuit high pressure switch to disable compressor operation
if water pressure exceeds pressure switch setting. The fi eld
installed high pressure switch shall have a cut-out pressure
of 300 psig and a cut-in pressure of 250 psig. This pressure
switch can be ordered from Carrier Geothermal with a 1/4”
internal fl are connection as part number 39B0005N02.
CAUTION!
CAUTION! Refrigerant pressure activated water regulating
valves should never be used with Carrier Geothermal
equipment.
s.2Application not recommended.
s.ODESIGN-AXIMUM
16
CLOSEDPRESSURIZEDPIPINGSYSTEM
Water-Source Heating and Cooling Systems
Re
Page 17
CAUTION!
CAUTION! R-410A systems operate at higher pressures
than R-22 systems. Be certain that service equipment
(gauges, tools, etc.) is rated for R-410A. Some R-22
service equipment may not be acceptable.
Residential Split - 60Hz R22 &R410A
Rev.: 5 June, 2008
Refrigeration Installation
R-410A models are shipped with a fi lter drier (loose) inside the
cabinet that must be installed in the liquid line at the line set.
All brazing should be performed using nitrogen circulating
at 2-3 psi [13.8-20.7 kPa] to prevent oxidation inside the
tubing. All linesets should be insulated with a minimum
of 1/2” [13mm] thick closed cell insulation. All insulation
tubing should be sealed using a UV resistant paint or
covering to prevent deterioration from sunlight.
CAUTION!
CAUTION! Installation of a factory supplied liquid line
bi-directional fi lter drier is required. Never install a suction
line fi lter in the liquid line.
When passing refrigerant lines through a wall, seal
opening with silicon-based caulk. Avoid direct contact
with water pipes, duct work, fl oor joists, wall studs, fl oors or other structural components that could transmit
compressor vibration. Do not suspend refrigerant tubing
from joists with rigid straps. Do not attach line set to the
Line Set Installation
Figures 12a through 13b illustrate typical installations with the
“indoor” and “outdoor” versions of the compressor section
wall. When necessary, use hanger straps with isolation
sleeves to minimize transmission of line set vibration to
the structure.
matched to either an air handler (fan coil) or add-on furnace
coil. Table 4 shows typical line-set diameters at various lengths.
Lineset lengths should be kept to a minimum and should always
be installed with care to avoid kinking. Line sets over 60 feet [18
meters] long are not recommended due to potential oil transport
problems and excessive pressure drop. If the line set is kinked
or distorted, and it cannot be formed back into its original
shape, the damaged portion of the line should be replaced. A
restricted line set will effect the performance of the system.
Installing the Lineset at the Compressor Section
Braze the line set to the service valve stubs as shown in Figure
10. On installations with long line sets, copper adapters may
be needed to connect the larger diameter tube to the stubs.
Nitrogen should be circulated through the system at 2-3 psi
[13.8-20.7 kPa] to prevent oxidation contamination. Use a
low silver phos-copper braze alloy on all brazed connections.
Compressor section is shipped with a factory charge.
Therefore, service valves should not be opened until the
A reversible heat pump fi lter drier is installed on the liquid
line inside the compressor section cabinet (R-22 units only).
line set has been leak tested, purged and evacuated. See
“Charging the System.”
• Basic charge includes only the amount required for the condensing unit and the evaporating coil.
An additional amount should be added allowing 0.6oz per ft. for 3/8” [0.6g per cm] and 1.2oz per ft. for 1/2” [1.1g per cm] of lineset used.
†Factory charge is preset for 25’ [7.6 meters] lineset.
The indoor coil should be located in the supply side of
the furnace to avoid condensation damage to the furnace
heat exchanger for add-on heat pump applications. A high
temperature limit switch should be installed as shown in Figures
12b and 13b just upstream of the coil to de-energize the
compressor any time the furnace is energized to avoid blowing
hot air directly into the coil, elevating refrigerant pressures
during operation. The heat pump will trip out on high pressure
lockout without some method of disengaging the compressor
during furnace operation. Alternatively, some thermostats with
“dual fuel” mode will automatically de-energize the compressor
when second stage (backup) heat is required.
TXV (‘IN’ toward
compressor section)
TXV has internal
check valve
Table 5: Service Valve Positions
18
Installing the Indoor Coil and Lineset
Figure 11 shows the installation of the lineset and TXV to a
typical indoor coil. An indoor coil or air handler (fan coil) with a
TXV is required. Coils with cap tubes may not be used. If coil
includes removable fi xed orifi ce, the orifi ce must be removed
and a TXV must be installed as shown in Figure 11. Fasten
the copper line set to the coil. Nitrogen should be circulated
through the system at 2-3 psi [13.8-20.7 kPa] to prevent
oxidation inside the refrigerant tubing. Use a low silver phoscopper braze alloy on all brazed connections.
Water-Source Heating and Cooling Systems
The TXV should be brazed into place as shown in Figure 11,
keeping the “IN” side toward the compressor section. The
TXV has an internal check valve and must be installed in the
proper direction for operation. Always keep the valve body
cool with a brazing shield and wet rags to prevent damage
to the TXV. Attach the bulb to the suction line using the
supplied hose clamp. Be careful not to overtighten the clamp
and deform the bulb.
NOTICE! The air coil should be thoroughly washed with a
fi lming agent, (dishwasher detergent like Cascade) to help
condensate drainage. Apply a 20 to 1 solution of detergent
and water. Spray both sides of coil, repeat and rinse
thoroughly with water.
Evacuation and Charging the Unit
LEAK TESTING -
The refrigeration line set must be pressurized
and checked for leaks before evacuating and charging the unit.
To pressurize the line set, attach refrigerant gauges to the service
ports and add an inert gas (nitrogen or dry carbon dioxide) until
pressure reaches 60-90 psig [413-620 kPa]. Never use oxygen or
acetylene to pressure test. Use a halogen leak tester or a good
quality bubble solution to detect leaks on all connections made
in the fi eld. Check the service valve ports and stem for leaks. If
a leak is found, repair it and repeat the above steps. For safety
reasons do not pressurize system above 150 psig [1034 kPa].
System is now ready for evacuation and charging.
The line set and coil must be evacuated to at least 500
microns to remove any moisture and noncondensables.
Evacuate the system through both service ports in the
shipping position (full CW in - see table 5) to prevent false
readings on the gauge because of pressure drop through
service ports. A vacuum gauge or thermistor capable of
accurately meausuring the vacuum depth is crucial in
determining if the system is ready for charging. If the system
meets the requirements in Figure 14, it is ready for charging.
Figure 14: Evacuation Graph
There are two methods of charging a refrigerant system. One
method is the total charge method, where the volume of the
system is determined and the refrigerant is measured and
added into the evacuated system. The other method is the
partial charge method where a small initial charge is added
to an evacuated system, and remaining refrigerant added
during operation.
Total Charge Method - See Table 4 for the compressor
section basic charge. For line sets with 3/8” liquid lines
add 0.6 ounces of refrigerant to the basic charge for every
installed foot of liquid line [0.6 grams per cm]. Add 1.2 oz.
per foot [1.1 grams per cm] if using l/2” line. Once the total
charge is determined, the factory pre-charge (Table 4) is
subtracted and the remainder is the amount needed to be
added to the system. This method should be used with the
ARI matched air handler.
EXAMPLE: R22 model 048 with 40 feet [12 meters] of
installed liquid line (3/8” O.D.). The basic charge of model
048 is 115 oz [3.26 kg]. The 40 ft. [12 meter] 3/8” line set
requires 24 oz. [0.72 kg] (40 ft. x 0.6 oz./ft = 24 oz. -1200cm x 0.6g/cm = 720g). Total charge = 115 + 24 = 139 oz
[3.26 + 0.72 = 3.98 kg]. The compressor section is shipped
from the factory with 130 oz. [3.69 kg] of refrigerant (for 25 ft
[7.6m] lineset), so the amount to be added is 9 oz. [0.29 kg]
(total charge - shipped charge = charge to be added).
Charging The System
Table 6a: R-22 Charging Values
NOTICE!
NOTICE: Use tables 14a to 15 for superheat/subcooling
values. These tables use discharge pressure (converted
to saturation temperature) and liquid line temperature
for subcooling calculations. If using liquid line pressure,
subtract 3°F from the table values.
Turn service valves full out CCW (see Table 5) and then turn
back in one-half turn to open service ports. Add the required
Table 6b: R-410A Charging Values
NOTICE!
NOTICE: Use tables 14a to 15 for superheat/subcooling
values. These tables use discharge pressure (converted
to saturation temperature) and liquid line temperature
for subcooling calculations. If using liquid line pressure,
subtract 3°F from the table values.
Carrier: Turn to the Experts
21
Page 22
Residential Split - 60Hz R22 &R410A
Rev.: 5 June, 2008
Refrigeration Installation
refrigerant so that the total charge calculated for the unit and
line set is now in the system. Open the service valve fully
counter clockwise so that the stem will backseat and prevent
leakage through the schrader port while it is not in use.
Start unit in the heating mode and measure superheat and
subcooling values after 5 minutes of run time. See tables
14a to 15 for superheat and sub-cooling values. Superheat
is measured using suction temperature and pressure at the
compressor suction line. Subcooling should be measured
using the liquid line temperature immediately outside the
compressor section cabinet and either the liquid line service
valve pressure or the compressor discharge pressure. Note
that different values from tables 14a to 15 will be obtained
due to the pressure losses through the condenser heat
exchanger. Adding refrigerant will increase sub-cooling
while superheat should remain fairly constant allowing for
a slight amount of hunting in TXV systems. This increase in
subcooling will require 5 minutes or so of operation before it
should be measured. After values are measured, compare to
the chart and go to “FINAL EVALUATION.”
PARTIAL CHARGE METHOD - Open service valve fully
counterclockwise and then turn back in one-half turn to
open service port. Add vaporized (Gas) into the suction
side of the compressor until the pressure in the system
reaches approximately 60-70 psig (R-22 systems) or 100120 psig (R-410A systems). Never add liquid refrigerant into
the suction side of a compressor. Start the unit in heating
and add gas to the suction port at a rate not to exceed
fi ve pounds [2.27 kg] per minute. Keep adding refrigerant
until the complete charge has been entered. Superheat is
measured using suction temperature and pressure at the
compressor suction line. Subcooling should be measured
using the liquid line temperature immediately outside the
compressor section cabinet and either the liquid line service
valve pressure or the compressor discharge pressure. Note
that different values from tables 14a to 15 will be obtained
due to the pressure losses through the condenser heat
exchanger. Adding refrigerant will increase sub-cooling
while superheat should remain fairly constant allowing for
a slight amount of hunting in TXV systems. This increase in
subcooling will require 5 minutes or so of operation before it
should be measured. After values are measured, compare to
the chart and go to “FINAL EVALUATION.”
FINAL EVALUATION -In a split system, cooling subcooling
values can be misleading depending on the location of the
measurement. Therefore, it is recommended that charging
be monitored in the heating mode. Charge should be
evaluated by monitoring the subcooling in the heating mode.
After initial check of heating sub-cooling, shut off unit and
allow to sit 3-5 minutes until pressures equalize. Restart
unit in the cooling mode and check the cooling superheat
against Tables 14a to 15. If unit runs satisfactorily, charging
is complete. If unit does not perform to specifi cations the
cooling TXV (air coil side) may need to be readjusted (if
possible) until the cooling superheat values are met.
Checking Superheat and Subcooling
Determining Superheat:
1. Measure the temperature of the suction line at a point
near the expansion valve bulb.
2. Determine the suction pressure by attaching refrigeration
gauges to the suction schrader connection at the
compressor.
3. Convert the pressure obtained in step 2 to saturation
temperature (boiling point) by using the pressure/
temperature conversion table on the gauge set.
4. Subtract the temperature obtained in step 3 from step
1. The difference will be the superheat of the unit or the
total number of degrees above saturation temperature.
Refer to Tables 14a to 15 for superheat ranges at
specifi c entering water conditions.
Example (R-22 refrigerant):
The temperature of the suction line at the sensing bulb is
50°F. The suction pressure at the compressor is 65 psig
which is equivalent to 38°F saturation temperature from the
R-22 press/temp conversion table on the gauge set.
38°F subtracted from 50°F = 12°F Superheat.
Determining Sub-Cooling:
1. Measure the temperature of the liquid line on the smaller
refrigerant line (liquid line) just outside of the cabinet.
This location will be adequate for measurement in both
modes unless a signifi cant temperature drop in the liquid
line is anticipated.
2. Determine the condensor pressure (high side) by
attaching refrigerant gauges to the schrader connection
on the liquid line service valve. If the hot gas discharge
line of the compressor is used, refer to the appropriate
column in Tables 14a to 15.
3. Convert the pressure obtained in step 2 to the
saturation temperature by using the press/temp
conversion table on the gauge set.
4.
Subtract the temperature of Step 3 from the temperature
of Step 1. The difference will be the sub-cooling value for
that unit (total degrees below the saturation temperature).
Refer to Tables 14a or 6b for sub-cooling values at specifi c
entering water temperatures.
Example (R-22 refrigerant):
The condenser pressure at the service port is 225 psig,
which is equivalent to 110°F saturation temperature.
Discharge pressure is 236 psig at the compressor (113°F
saturation temperature). Measured liquid line temperature
is 100°F. 100°F subtracted from 110°F = 10 degrees subcooling (13 degrees if using the compressor discharge
pressure).
22
Water-Source Heating and Cooling Systems
Page 23
Residential Split - 60Hz R22 &R410A
Rev.: 5 June, 2008
Hot Water Generator
The HWG (Hot Water Generator) or desuperheater
option provides considerable operating cost savings by
utilizing excess heat energy from the heat pump to help
satisfy domestic hot water requirements. The HWG
is active throughout the year, providing virtually free
hot water when the heat pump operates in the cooling
mode or hot water at the COP of the heat pump during
operation in the heating mode. Actual HWG water
heating capacities are provided in the appropriate heat
pump performance data.
Heat pumps equipped with the HWG option include
a built-in water to refrigerant heat exchanger that
eliminates the need to tie into the heat pump
refrigerant circuit in the fi eld. The control circuit and
pump are also built in for residential equipment. Figure
15 shows a typical example of HWG water piping
connections on a unit with built-in pump. This piping
layout minimizes scaling potential.
Electric water heaters are recommended. If a gas,
propane, or oil water heater is used, a second preheat
tank must be installed (Figure 16). If the electric water
heater has only a single center element, the dual tank
system is recommended to insure a usable entering
water temperature for the HWG.
Typically a single tank of at least 52 gallons (235 liters)
is used to limit installation costs and space. However,
a dual tank, as shown in Figure 16, is the most effi cient
system, providing the maximum storage and temperate
source water to the HWG. Using a concentric or coaxial
hot water tank connection fi tting eliminates the need to
tie into the hot water tank cold water piping, but is more
susceptible to scaling. The optional concentric fi tting
(part # S69619804) is available from your equipment
supplier and should be installed as shown in Figure
17 for applications with low scaling potential or where
a water softener is used. Consult Table 3 for scaling
potential tests.
It is always advisable to use water softening
equipment on domestic water systems to reduce
the scaling potential and lengthen equipment life.
In extreme water conditions, it may be necessary to
avoid the use of the HWG option since the potential
cost of frequent maintenance may offset or exceed
any savings.
R-410 systems inherently have a lower hot gas
temperature than R-22 systems because the
equipment is more effi cient (i.e. less waste heat
is available). It is possible that energy could be
transferred from the water heater to the hot gas line
instead of from the hot gas line to the water heater
during certain times of the year. To prevent this from
occuring, a temperature switch will deactivate the
pump at those conditions that typically occur in the
cooling mode with entering water temperatures of less
than 50°F [10°C].
5/8” OD, 50 ft maximum
[16mm OD, 15 meters
maximum]
Figure 16: HWG Double Tank In stal la tion
(Indoor Compressor Section)
Cold Inlet
Hot Outlet
to home
Shut-off Valve
Upper
element to
120 - 130°F
[49 - 54°C]
Lower
Powered
Water
Heater
element to
100 - 110°F
[38 - 43°C]
Tee and drain
Carrier: Turn to the Experts
Shut Off Valve #2
Hot Outlet to
Cold Inlet from
Domestic supply
Hot Outlet
Shut-off
Valve #3
Water Heater
Insulated water lines - 5/8” OD, 50 ft maximum
[16mm OD, 15 meters maximum]
house
Shut-off
Valve #4
Unpowered
Field Supplied 3/4” brass nipple and “T”
Shut-off
Valve #1
Water Heater
Cold Inlet
Powered
Upper element to 130°F [54°C]
(or owner preference)
Lower element to 120°F [49°C]
23
Page 24
Residential Split - 60Hz R22 &R410A
Rev.: 5 June, 2008
Hot Water Generator
Figure 17: Alternate HWG Piping with concentric/coaxial
fi tting (part #S69619804 not included with unit)
(Indoor Compressor Section)
Hot Outlet
Cold Inlet
Upper element to
120-130ϒF
[49-54ϒC]
Insulated water lines 5/8" OD, 50 ft [15m] maximum
Compressor Section
Waste Vent Coupling
at high point
Coaxial
Fitting
Water Heater
Lower element to
ϒ
100-110
F
ϒ
[38-43
C]
The heat pump, water piping, pump, and hot water tank should
be located where the ambient temperature does not fall below
50°F [10°C]. Keep water piping lengths at a minimum. DO NOT
use a one way length greater than 50 ft. [15 m].
All installations must be in accordance with local codes. The
installer is responsible for knowing the local requirements,
and for performing the installation accordingly. DO NOT
connect the pump wiring until “Initial Start-Up” section, below.
Powering the pump before all installation steps are completed
will damage the pump.
Water Tank Preparation
1. Turn off power or fuel supply to the hot water tank.
2. Connect a hose to the drain valve on the water tank.
3. Shut off the cold water supply to the water tank.
4. Open the drain valve and open the pressure relief valve or
a hot water faucet to drain tank.
5. When using an existing tank, it should be fl ushed with
cold water after it is drained until the water leaving the
drain hose is clear and free of sediment.
6. Close all valves and remove the drain hose.
7. Install HWG water piping.
HWG Water Piping
1. Using at least 5/8” [16mm] O.D. copper, route and
install the water piping, valves and air vent as shown in
Figures 14, 15, or 16. An appropriate method must be
employed to purge air from the HWG piping. This may be
accomplished by fl ushing water through the HWG (as In
Figures 14 and 15) or by Installing an air vent at the high
point of the HWG piping system (as in Figure 16).
2. Insulate all HWG water piping with no less than 3/8”
[10mm] wall closed cell insulation.
3. Open both shut off valves and make sure the tank drain
valve is closed.
Water Tank Refi ll (Figures 14 and 15)
1. Close valve #4. Ensure that the HWG valves (valves #2
and #3) are open. Open the cold water supply (valve #1)
to fi ll the tank through the HWG piping. This will purge air
from the HWG piping.
2. Open a hot water faucet to vent air from the system until
water fl ows from the faucet; turn off faucet. Open valve
#4.
Water Tank Refi ll (Figure 16)
1. Open the cold water supply to fi ll the tank. Use the air vent
to bleed air from the HWG piping.
2. Open a hot water faucet to vent air from the system until
water fl ows from the faucet; turn faucet off.
Water Tank Refi ll (All)
3.
Depress the hot water tank pressure relief valve handle to
ensure that there is no air remaining in the tank.
4. Inspect all work for leaks.
5.
Before restoring power or fuel supply to the water heater,
adjust the temperature setting on the tank thermostat(s)
to insure maximum utilization of the heat available from
the refrigeration system and conserve the most energy.
On tanks with both upper and lower elements and
thermostats, the lower element should be turned down
to 100°F [38°C] or the lowest setting; the upper element
should be adjusted to 120-130°F [49-54°C]. Depending
upon the specifi c needs of the customer, you may want to
adjust the upper element differently. On tanks with a single
thermostat, a preheat tank should be used (fi gure 16).
6. Replace access cover(s) and restore power or
fuel supply.
Initial Start-Up
1. Make sure all valves in the HWG water circuit are
fully open.
2. Turn on the heat pump and allow it to run for
10-15 minutes.
Figure 18: HWG In stal la tion (shown with optional
concentric/coaxial fi tting part #S69619804 not included
with unit) (Outdoor Compressor Section)
Water
Heater
Waste Vent
Coupling
Coaxial
Fitting
Cold
Inlet
Insulated
line set with
UV Paint
Insulated water
Insulated lineset
enters structure
Add-On Hot Water
Generator with
internal pump
lines
Hot
Outlet
24
Water-Source Heating and Cooling Systems
Page 25
Residential Split - 60Hz R22 &R410A
Unbraze u-tube
Hot water generator
service valve assembly
(inside cabinet)
Hot Gas to
Reversing Valve
Hot Gas from
Compressor
Field connection of
Hot Water lineset
Pinch off here after evacuating
lineset and opening valves
Open Valves CW Close
valves CCW as looking up
from underneath
Rev.: 5 June, 2008
Hot Water Generator Module Refrigeration Installation -
Outdoor Compressor Section Only
3. Turn the heat pump and heat pump power supply “OFF”
and CONNECT POWER TO THE HWG PUMP as shown
in the unit wiring diagram. Connect the pump power lead
as instructed on the tag attached to the pump wiring.
4. The HWG pump should not run if the compressor is
not running.
5. The temperature difference between the water entering
and leaving the HWG coil should be approximately 5-10°F
[3-6°C].
6. Allow the unit to operate for 20 to 30 minutes to insure
that it is functioning properly.
General Information
The HWG Module consists of an all-copper, vented doublewall heat exchanger and a water-cooled water circulating
pump. The pump is controlled by the use of one or more
limit switches. Power for the pump is provided from either
the compressor contactor of the outdoor section of the heat
pump, or it may come from a remote power source if the
appropriate controls are used.
Location/Mounting
The HWG module should be mounted as close to the heat
pump outdoor section as possible, in order to minimize
the length of refrigerant run. Indoor mounting is preferred,
where practical, to reduce the likelihood of freezing ambient
temperature. It is recommended that the HWG module be
mounted above the system compressor in order to promote
proper oil movement and drain-down. This means that the
HWG module can be wall mounted in any orientation
except for stubs up. Mounting should be accomplished
by fastening the HWG module cabinet to the wall or other
selected vertical surface. A fl ange is provided at the top rear
of the unit. Any fastener suitable for supporting a 12 pound
[5.4] vertical load is acceptable.
Table 7: HWG Module Lineset Sizing
the lineset to 500 microns through the hot gas valves in
the outdoor unit. Open the valves up fully (CCW looking up
from cap end). Check the lineset for leaks. Pinch the bypass
tubing as shown in Figure 19 being careful not to damage
the tubing. Verify that lineset tubing is completely insulated
with a minimum 1/2” thick closed cell and painted to prevent
deterioration of the insulation due to ultra violet light and
weather. Make the connections with high temperature solder
or brazing rod. The recommended line size is dependent on
the one way distance between the Heat Recovery Unit and
the compressor; and the size of the system. Use the Table 7
as a guideline.
Figure 19: HWG Connection Details
Capacity
2 TonUp to 16 ft.
3 TonUp to 9 ft.
4 TonUp to 5 ft.
5 TonN/AUp to 9 ft.
1/2” OD5/8” OD3/4” OD
[4.9m]
[2.7m]
[1.5m]
Line Set Size
Up to 30 ft.
[9.1m]
Up to 25 ft.
[7.6m]
Up to 13 ft.
[4.0m]
[2.7m]
N/A
Up to 30 ft.
[9.1m]
Up to 30 ft.
[9.1]
Up to 25 ft.
[7.6m]
As a guideline add 1.0 oz. of R-22 for the heat exchanger
plus 1.0 oz. for each 10 ft of 1/2” OD refrigerant line, if the
weighed charge method is used (28g for the heat exchanger
plus 9g per meter of 1/2” OD refrigerant line).
SPECIAL NOTE: The selected mounting location and
orientation must allow the circulator pump to be positioned
with the motor shaft horizontal. DO NOT install the Heat
Recovery Unit fl at on its back.
Refrigerant Line Installation
Before starting the installation into the refrigerant circuit,
inspect and note the condition and performance of the
heat pump. Disconnect power to the heat pump outdoor
unit. Any system defi ciencies must be corrected prior to
installing the HWG module. Addition of the unit will not
correct system problems. Record the suction and discharge
pressures and compressor amperage draw. These will
be used for comparison with system operation after the
refrigerant line installation is complete and before the water
line installation is performed. Install the Add-On HWG kit
using the installation instructions below. Locate the HWG
as close to the water heater as possible. Unbraze the hot
gas u-bend as shown in Figure 19. Take care to avoid
overheating components. Install the dual 1/2” lineset to the
HWG. Maximum length should be 30 feet one way. Evacuate
Carrier: Turn to the Experts
25
Page 26
Residential Split - 60Hz R22 &R410A
Rev.: 5 June, 2008
Hot Water Generator Module Refrigeration Installation Outdoor Compressor Section Only
CAUTION!
CAUTION! The HWG module must be installed in an area
that is not subject to freezing temperatures.
NOTICE! Make sure the compressor discharge line
is connected to the “Hot Gas In” stub on the Heat
Recovery Unit.
CAUTION!
CAUTION! Locate Refrigerant lines to avoid accidental
damage by lawnmowers or children.
WARNING!
WARNING! The HWG module is an appliance that operates
in conjunction with the heat pump system, the hot water
system and the electrical system. Installation should only be
performed by skilled technicians with appropriate training and
experience. The installation must be in compliance with local
codes and ordinances. Local plumbing and electrical building
codes take precedence over instructions contained herein.
The Manufacturer accepts no liability for equipment damaged
and/or personal injury arising from improper installation of the
HWG module.
26
Water-Source Heating and Cooling Systems
Page 27
WARNING!
WARNING! To avoid possible injury or death due to
electrical shock, open the power supply disconnect switch
and secure it in an open position during installation.
CAUTION!
CAUTION!
electrical wiring. Unit terminals are not designed to accept other
types of conductors.
Electrical - Line Voltage
All fi eld installed wiring, including electrical ground, must
comply with the National Electrical Code as well as all
applicable local codes. Refer to the unit electrical data for fuse
sizes. Consult wiring diagram for fi eld connections that must
be made by the installing (or electrical) contractor.
Use only copper conductors for fi eld installed
Residential Split - 60Hz R22 &R410A
Rev.: 5 June, 2008
Electrical - Line Voltage
All fi nal electrical connections must be made with a length of
fl exible conduit to minimize vibration and sound transmission
to the building.
General Line Voltage Wiring
Be sure the available power is the same voltage and phase
shown on the unit serial plate. Line and low voltage wiring
must be done in accordance with local codes or the National
Electric Code, whichever is applicable.
Power Connection
Line voltage connection is made by connecting the incoming
line voltage wires to the “L” side of the contactor as shown
in Figures 21a through 21c. Consult Tables 8a through 8c for
correct fuse size.
208-230 Volt Operation
Verify transformer tap with air handler wiring diagram to
insure that the transformer tap is set to the correct voltage,
208V or 230V.
Table 8a: GT-PX (50YDS) Series Electrical Data
Model
Compressor
RLALRAQty
02610.352.010.44.014.717.32510107 (32.7)
03816.782.010.44.021.125.3401073 (22.3)
04921.296.010.44.025.630.950895 (29.2)
06425.6118.010.44.030.036.460881 (24.8)
Rated Voltage of 208/230/60/1 Min/Max Voltage of 197/254
HACR circuit breaker in USA only All fuses Class RK-5
Wire length based on one way measurement with 2% voltage drop Wire size based on 60°C copper conductor and Minimum Circuit Ampacity.
HWG
Pump
FLA
External
Pump
FLA
Total
Unit
FLA
Min
Circuit
Amps
Max
Fuse/
HACR
Min
AWG
Max Wire
Ft.
(m)
Table 8b: GT-GS (50YCS) Series Electrical Data
Model
Compressor
RLALRAQty
018
024
030
036
042
048
060
Rated Voltage of 208/230/60/1 Min/Max Voltage of 197/254
HACR circuit breaker in USA only All fuses Class RK-5
Wire length based on one way measurement with 2% voltage drop Wire size based on 60°C copper conductor and Minimum Circuit Ampacity.
7.740.310.404.012.114.0201276 (23.3)
10.356.010.404.014.717.32510107 (32.7)
12.267.010.404.016.619.7301094 (28.7)
13.573.010.404.017.921.3351087 (26.5)
16.595.010.404.020.925.0401074 (22.6)
18.3109.010.404.022.727.3451067 (20.7)
25.0148.010.404.029.435.760882 (25.2)
HWG
Pump
FLA
External
Pump
FLA
Total
Unit
FLA
Min
Circuit
Amps
Max
Fuse/
HACR
Min
AWG
Max Wire
Ft
(m)
Carrier: Turn to the Experts
27
Page 28
Residential Split - 60Hz R22 &R410A
Rev.: 5 June, 2008
Electrical - Line Voltage
Table 8c: GT-S Outdoor (38WQS) Series Electrical Data
Compressor
Model
018
024
030
036
042
048
060
Rated Voltage of 208-230/60/1 Min/Max Voltage of 197/254
HACR circuit breaker in USA only All fuses Class RK-5
Wire length based on one way measurement with 2% voltage drop Wire size based on 60°C copper conductor and Minimum Circuit Ampacity.
RLALRAQty
7.138.01N/A0.404.011.513.3201287 (26.6)
10.356.010.170.404.014.917.42510106 (32.5)
12.267.010.170.404.016.819.8301093 (28.6)
13.573.010.170.404.018.121.4301086 (26.4)
16.595.010.170.404.021.125.2401073 (22.4)
18.3109.010.170.404.022.927.4451067 (20.6)
25.0148.010.290.404.029.735.960882 (25.1)
Crank-
case
HWG
Pump
FLA
Ext Loop
Pump
FLA
Total
Unit
FLA
Min
Circuit
Amps
Max
Fuse/
HACR
Min
AWG
Max
Wire Ft
(m)
ELECTRICAL - POWER WIRING
Electrical - Line Voltage
All fi eld installed wiring, including electrical ground, must
comply with the National Electrical Code as well as all
applicable local codes. Refer to the unit electrical data for fuse
sizes. Consult wiring diagram for fi eld connections that must
be made by the installing (or electrical) contractor.
All fi nal electrical connections must be made with a length of fl exible conduit to minimize vibration and sound transmission
to the building.
General Line Voltage Wiring
Be sure the available power is the same voltage and phase
shown on the unit serial plate. Line and low voltage wiring
must be done in accordance with local codes or the National
Electric Code, whichever is applicable.
Power Connection
Line voltage connection is made by connecting the incoming
line voltage wires to the “L” side of the contactor as shown
in Figures 21a through 21c. Consult Tables 8a through 8c for
correct fuse size.
208-230 Volt Operation
Verify transformer tap with air handler wiring diagram to
insure that the transformer tap is set to the correct voltage,
208V or 230V.
Figure 20: HWG Module Wiring
Figure 21a: R-410A Compressor Section Line Voltage
Field Wiring
Unit Power Supply
(see electrical table for wire
and breaker size)
28
Water-Source Heating and Cooling Systems
Page 29
Residential Split - 60Hz R22 &R410A
Capacitor
Transformer
CXM Control
Circ Brkr
Contactor -CC
BR
Low Voltage
Connector
CB
HWG PB2
Loop PB1
L2
L1
Unit Power Supply
See electrical table for
wire and breaker size
External Pump
Power Supply
See electrical table for
wire and breaker size
T2
T1
Grnd
Install HWG Pump
Power after insuring
water is in HWG circuit
T2
T1
Pink
Blk
.
Rev.: 5 June, 2008
Electrical - HWG Wiring
Figure 21b: R-22 Indoor Compressor Section Line
Voltage Field Wiring
Figure 21c: R-22 Outdoor Compressor
Section Line Voltage Field Wiring
CRC
CRR
CXM Control
Low Voltage
Connector
T2 T1
CC
L2L1
FCR
Grnd
HWG Wiring - “Indoor” Compressor Section
The hot water generator pump power wiring is disabled at
the factory to prevent operating the HWG pump “dry.” After
all HWG piping is completed and air purged from the water
piping, the pump power wires should be applied to terminals
on the HWG power block PB2 as shown in the unit wiring
diagram. This connection can also serve as a HWG disable
when servicing the unit.
HWG Wiring - “Outdoor” Compressor Section
The HWG module should be wired to the outdoor section
pump controls (see Figure 20). A safety disconnect should
be installed at the HWG module to allow servicing of the
module. If wired as shown, any time the compressor is
energized, the HWG module pump will be activated, which
will circulate water from the water heater tank to the HWG
module. DO NOT energize the pump until all HWG piping is
completed and air is purged from the water piping to avoid
running the pump “dry.”
Consult Electrical Table for wire and fuse size
All power wiring per local code
Note: See FC Mounting for Flow Controller Wiring
208-230 Volt Operation
Verify transformer tap with air handler wiring diagram to
insure that the transformer tap is set to the correct voltage,
208V or 230V.
Carrier: Turn to the Experts
29
Page 30
Residential Split - 60Hz R22 &R410A
Capacitor
CXM Control
Circ Brkr
Contactor -CC
BR
Low Voltage
Connector
HWG PB2
Loop PB1
L2
L1
Grnd
FCR
CR
R
Thermostat Connection
See Thermostat section
for Wiring Details
CRC
Grnd
L2L1
T2T1
CC
CXM Control
Low Voltage
Connector
Rev.: 5 June, 2008
Electrical - Low Voltage Wiring
ELECTRICAL - LOW VOLTAGE WIRING
Thermostat Connections
The thermostat should be wired directly to the CXM board.
Figures 22a through 22c show low voltage wiring. Note that
the air handler or furnace transformer will be used to power
the CXM board in the compressor section. See “Electrical –
Thermostat” for specifi c terminal connections.
Figure 22a: 50YDS Low Voltage Field Wiring
Low voltage
fi eld wiring
Figure 22b: GT-GS Low Voltage Field Wiring
Figure 22c: GT-S Low Voltage Field Wiring
Low Water Temperature Cutout Selection
The CXM control allows the fi eld selection of low water (or
water-antifreeze solution) temperature limit by clipping jumper
JW3, which changes the sensing temperature associated with
thermistor FP1. Note that the FP1 thermistor is located on
the refrigerant line between the coaxial heat exchanger and
expansion device (TXV). Therefore, FP1 is sensing refrigerant
temperature, not water temperature, which is a better indication
of how water fl ow rate/temperature is affecting the refrigeration
circuit.
30
Water-Source Heating and Cooling Systems
The factory setting for FP1 is for systems using water (30°F
[-1.1°C] refrigerant temperature). In low water temperature
(extended range) applications with antifreeze (most ground
loops), jumper JW3 should be clipped as shown in Figure
23 to change the setting to 10°F [-12.2°C] refrigerant
temperature, a more suitable temperature when using
an antifreeze solution. All residential units include water/
refrigerant circuit insulation to prevent internal condensation,
which is required when operating with entering water
temperatures below 59°F [15°C].
Page 31
Residential Split - 60Hz R22 &R410A
Rev.: 5 June, 2008
Electrical - Low Voltage Wiring
Figure 23: FP1 Limit Setting
JW3-FP1 jumper
should be clipped
for low temperature
CXM PCB
Accessory Connections
A terminal paralleling the compressor contactor coil has
been provided on the CXM control. Terminal “A” is designed
to control accessory devices, such as water valves. Note:
This terminal should be used only with 24 Volt signals
and not line voltage. Terminal “A” is energized with the
compressor contactor. See Figure 24 or the specifi c unit
wiring diagram for details.
Figure 24: Accessory Wiring
operation
Note: This valve can overheat the anticipator of an
electromechanical thermostat. Therefore, only relay or triac
based thermostats should be used.
Two-stage Units
Two-stage units should be designed with two parallel valves
for ground water applications to limit water use during fi rst
stage operation. For example, at 1.5 gpm/ton [2.0 l/m per
kW], a model 049 unit requires 6 gpm [23 l/m] for full load
(2nd stage) operation, but only 4 gpm [15 l/m] during 1st
stage operation. Since the unit will operate on fi rst stage 80-
90% of the time, signifi cant water savings can be realized by
using two parallel solenoid valves with two fl ow regulators.
In the example above, stage one solenoid would be installed
with a 4 gpm [15 l/m] fl ow regulator on the outlet, while stage
two would utilize a 2 gpm [8 l/m] fl ow regulator. When stage
one is operating, the second solenoid valve will be closed.
When stage two is operating, both valves will be open,
allowing full load fl ow rate.
Figure 27 illustrates piping for two-stage solenoid valves.
Review fi gures 24-26 for wiring of stage one valve. Stage two
valve should be wired between “Y2” (compressor solenoid
-- wire nut connection) and terminal “C.” NOTE: When EWT
is below 50°F [10°C], a minimum of 2 gpm per ton (2.6 l/m
per kW) is required.
Water Solenoid Valves - “Indoor” Compressor
Section Only
An external solenoid valve(s) should be used on ground
water installations to shut off fl ow to the unit when the
compressor is not operating. A slow closing valve may be
required to help reduce water hammer. Figure 24 shows
typical wiring for a 24VAC external solenoid valve. Figures
25 and 26 illustrate typical slow closing water control valve
wiring for Taco 500 series (Carrier Geothermal P/N AVM…)
and Taco ESP series valves. Slow closing valves take
approximately 60 seconds to open (very little water will fl ow
before 45 seconds). Once fully open, an end switch allows
the compressor to be energized. Only relay or triac based
electronic thermostats should be used with slow closing
valves. When wired as shown, the slow closing valve will
operate properly with the following notations:
Figure 25: AMV Valve Wiring
C
1
Heater Switch
C
Thermostat
Figure 26: Taco SBV Valve Wiring
Y1
2
3
Y1
AVM
Taco Valve
1. The valve will remain open during a unit lockout.
2. The valve will draw approximately 25-35 VA through the
“Y” signal of the thermostat.
Carrier: Turn to the Experts
31
Page 32
Residential Split - 60Hz R22 &R410A
q
Rev.: 5 June, 2008
Electrical - Low Voltage Wiring
Figure 27: Two-Stage Piping
OUT
IN
Solenoid
Valve
Stage 2
From Water Source
NOTE: Shut-off valves, strainers and
other re
Flow
Regulator
To Discharge
Stage 1
uired components not shown.
CAUTION!
CAUTION! Many units installed with a factory or fi eld
supplied manual or electric shut-off valve. DAMAGE WILL OCCUR if shut-off valve is closed during unit operation. A
high pressure switch must be installed on the heat pump
side of any fi eld provided shut-off valves and connected to
the heat pump controls in series with the built-in refrigerant
circuit high pressure switch to disable compressor operation
if water pressure exceeds pressure switch setting. The fi eld
installed high pressure switch shall have a cut-out pressure
of 300 psig and a cut-in pressure of 250 psig. This pressure
switch can be ordered from Carrier Geothermal with a 1/4”
internal fl are connection as part number 39B0005N02.
CAUTION!
CAUTION! Refrigerant pressure activated water regulating
valves should never be used with Carrier Geothermal
equipment.
Figure 28b: Typical Thermostat Wiring, Single-Stage
Units (2 Heat/1 Cool)
CXM Board
(Compressor
Section)
Y
O
G
R
C
Typical
Air Handler
Y/Y2
O
G
R
C
W1
Optional
Jumper
W2
Typical
T-stat
Y
O
G
R
C
W
E
ELECTRICAL - THERMOSTAT WIRING
Thermostat Installation
The thermostat should be located on an interior wall in a
larger room, away from supply duct drafts. DO NOT locate
the thermostat in areas subject to sunlight, drafts or on
external walls. The wire access hole behind the thermostat
may in certain cases need to be sealed to prevent erroneous
temperature measurement. Position the thermostat back
plate against the wall so that it appears level and so the
thermostat wires protrude through the middle of the back
plate. Mark the position of the back plate mounting holes
and drill holes with a 3/16” (5mm) bit. Install supplied
anchors and secure plate to the wall. Thermostat wire
must be 18 AWG wire. Wire the appropriate thermostat as
shown in Figures 28a and 28b to the low voltage terminal
strip on the CXM control board. Practically any heat pump
thermostat will work with these units, provided it has the
correct number of heating and cooling stages.
AL1
L
Figure 28a: Typical Thermostat Wiring, Two-Stage Units
(3 Heat/2 Cool)
From Compressor
Solenoid Valve
CXM Board
(Compressor
Section)
Y
O
G
R
C
Typical
Air Handler
Y/Y2
Y1
O
G
R
C
W1
W2
Typical
T-stat
Y2
Y1
O
G
R
C
W
E
32
Water-Source Heating and Cooling Systems
AL1
L
Page 33
Residential Split - 60Hz R22 &R410A
Description of OperationLEDAlarm Relay
Normal ModeOnOpen
Normal Mode with UPS WarningOnCycle (closed 5 sec., Open 25 sec.)
CXM is non-functionalOffOpen
Fault RetrySlow FlashOpen
LockoutFast FlashClosed
Over/Under Voltage ShutdownSlow FlashOpen (Closed after 15 minutes)
Test Mode - No fault in memory Flashing Code 1Cycling Code 1
Test Mode - HP Fault in memory Flashing Code 2Cycling Code 2
Test Mode - LP Fault in memory Flashing Code 3Cycling Code 3
Test Mode - FP1 Fault in memory Flashing Code 4Cycling Code 4
Test Mode - FP2 Fault in memory Flashing Code 5Cycling Code 5
Test Mode - CO Fault in memory Flashing Code 6Cycling Code 6
Test Mode - Over/Under
shutdown in memory
Flashing Code 7Cycling Code 7
Test Mode - UPS in memoryFlashing Code 8Cycling Code 8
Test Mode - Swapped Thermistor Flashing Code 9Cycling Code 9
Rev.: 5 June, 2008
CXM Controls
CXM Control
For detailed control information, see CXM/DXM Application,
Operation and Maintenance (AOM) manual (part
#97B0003N08).
Field Selectable Inputs
Test mode: Test mode allows the service technician to
check the operation of the control in a timely manner. By
momentarily shorting the test terminals, the CXM control
enters a 20 minute test mode period in which all time delays
are sped up 15 times. Upon entering test mode, the status
LED will fl ash a code representing the last fault. For diagnostic
ease at the thermostat, the alarm relay will also cycle during
test mode. The alarm relay will cycle on and off similar to the
status LED to indicate a code representing the last fault, at
the thermostat. Test mode can be exited by shorting the test
terminals for 3 seconds.
Retry Mode: If the control is attempting a retry of a fault,
the status LED will slow fl ash (slow fl ash = one fl ash every 2
seconds) to indicate the control is in the process of retrying.
Field Confi guration Options
Note: In the following fi eld confi guration options, jumper
wires should be clipped ONLY when power is removed from
the CXM control.
Water coil low temperature limit setting: Jumper 3 (JW3FP1 Low Temp) provides fi eld selection of temperature limit
setting for FP1 of 30°F or 10°F [-1°F or -12°C] (refrigerant
temperature).
Not Clipped = 30°F [-1°C]. Clipped = 10°F [-12°C].
Air coil low temperature limit setting: Jumper 2 (JW2-FP2
Low Temp) provides fi eld selection of temperature limit
setting for FP2 of 30°F or 10°F [-1°F or -12°C] (refrigerant
temperature). Note: This jumper should only be clipped
under extenuating circumstances, as recommended by
the factory.
Not Clipped = 30°F [-1°C]. Clipped = 10°F [-12°C].
Alarm relay setting: Jumper 1 (JW1-AL2 Dry) provides fi eld
selection of the alarm relay terminal AL2 to be jumpered to
24VAC or to be a dry contact (no connection).
Not Clipped = AL2 connected to R. Clipped = AL2 dry
contact (no connection).
DDC operation. If set to “DDC Output at EH2,” the EH2
terminal will continuously output the last fault code of
the controller. If set to “EH2 normal,” EH2 will operate as
standard electric heat output.
On = EH2 Normal. Off = DDC Output at EH2.
NOTE: Some CXM controls only have a 2 position DIP switch
package. If this is the case, this option can be selected by
clipping the jumper which is in position 4
of SW1.
Jumper not clipped = EH2 Normal. Jumper clipped = DDC
Output at EH2.
DIP switch 5: Factory Setting - Normal position is “On.” Do
not change selection unless instructed to do so by
the factory.
-Slow Flash = 1 fl ash every 2 seconds
-Fast Flash = 2 fl ashes every 1 second
Table 9a: CXM LED And Alarm
Relay Operations
-Flash code 2 = 2 quick fl ashes, 10 second pause, 2 quick
fl ashes, 10 second pause, etc.
-On pulse 1/3 second; off pulse 1/3 second
DIP Switches
Note: In the following fi eld confi guration options, DIP
switches should only be changed when power is removed
from the CXM control.
DIP switch 1: Unit Performance Sentinel Disable - provides
fi eld selection to disable the UPS feature.
On = Enabled. Off = Disabled.
DIP switch 2: Stage 2 Selection - provides selection of
whether compressor has an “on” delay. If set to stage 2, the
compressor will have a 3 second delay before energizing.
Also, if set for stage 2, the alarm relay will NOT cycle during
test mode.
On = Stage 1. Off = Stage 2
DIP switch 3: Not Used.
DIP switch 4: DDC Output at EH2 - provides selection for
Carrier: Turn to the Experts
33
Page 34
Residential Split - 60Hz R22 &R410A
Rev.: 5 June, 2008
CXM Controls
Safety Features – CXM Control
The safety features below are provided to protect the
compressor, heat exchangers, wiring and other components
from damage caused by operation outside of design
conditions.
Anti-short cycle protection: The control features a 5 minute
anti-short cycle protection for the compressor.
Note: The 5 minute anti-short cycle also occurs at power up.
Random start: The control features a random start upon
power up of 5-80 seconds.
Fault Retry: In Fault Retry mode, the Status LED begins
slowly fl ashing to signal that the control is trying to recover
from a fault input. The control will stage off the outputs and
then “try again” to satisfy the thermostat input call. Once the
thermostat input call is satisfi ed, the control will continue on
as if no fault occurred. If 3 consecutive faults occur without
satisfying the thermostat input call, the control will go into
“lockout” mode. The last fault causing the lockout will be
stored in memory and can be viewed by going into test mode.
Note: FP1/FP2 faults are factory set at only one try.
Lockout: In lockout mode, the status LED will begin fast
fl ashing. The compressor relay is turned off immediately.
Lockout mode can be “soft” reset by turning off the
thermostat (or satisfying the call). A “soft” reset keeps
the fault in memory but resets the control. A “hard” reset
(disconnecting power to the control) resets the control and
erases fault memory.
Lockout with emergency heat: While in lockout mode, if W
becomes active (CXM), emergency heat mode will occur.
High pressure switch: When the high pressure switch opens due
to high refrigerant pressures, the compressor relay is de-energized
immediately since the high pressure switch is in series with the
compressor contactor coil. The high pressure fault recognition is
immediate (does not delay for 30 continuous seconds before deenergizing the compressor).
High pressure lockout code = 2
Example: 2 quick fl ashes, 10 sec pause, 2 quick fl ashes, 10
sec. pause, etc.
Low pressure switch: The low pressure switch must be open
and remain open for 30 continuous seconds during “on” cycle
to be recognized as a low pressure fault. If the low pressure
switch is open for 30 seconds prior to compressor power up it
will be considered a low pressure (loss of charge) fault. The low
pressure switch input is bypassed for the initial 60 seconds of a
compressor run cycle.
Low pressure lockout code = 3
Water coil low temperature (FP1): The FP1 thermistor
temperature must be below the selected low temperature limit
setting for 30 continuous seconds during a compressor run
cycle to be recognized as a FP1 fault. The FP1 input is bypassed
for the initial 60 seconds of a compressor run cycle. FP1 is set at
the factory for one try. Therefore, the control will go into lockout
mode once the FP1 fault has occurred.
FP1 lockout code = 4
34
Water-Source Heating and Cooling Systems
Air coil low temperature (FP2): The FP2 thermistor temperature
must be below the selected low temperature limit setting for
30 continuous seconds during a compressor run cycle to be
recognized as a FP2 fault. The FP2 input is bypassed for the
initial 60 seconds of a compressor run cycle. FP2 is set at the
factory for one try. Therefore, the control will go into lockout
mode once the FP2 fault has occurred.
FP2 lockout code = 5
Condensate overfl ow: The condensate overfl ow sensor
must sense overfl ow level for 30 continuous seconds to
be recognized as a CO fault. Condensate overfl ow will be
monitored at all times.
CO lockout code = 6
Over/under voltage shutdown: An over/under voltage
condition exists when the control voltage is outside the range
of 19VAC to 30VAC. Over/under voltage shut down is a
self-resetting safety. If the voltage comes back within range
for at least 0.5 seconds, normal operation is restored. This is
not considered a fault or lockout. If the CXM is in over/under
voltage shutdown for 15 minutes, the alarm relay will close.
Over/under voltage shut down code = 7
Unit Performance Sentinel-UPS (patent pending): The UPS
feature indicates when the heat pump is operating ineffi ciently.
A UPS condition exists when:
a) In heating mode with compressor energized, FP2 is
greater than 125°F [52°C] for 30 continuous seconds, or:
b) In cooling mode with compressor energized, FP1 is
greater than 125°F [52°C] for 30 continuous seconds, or:
c)
In cooling mode with compressor energized, FP2 is less
than 40°F [4.5°C] for 30 continuous seconds. If a UPS
condition occurs, the control will immediately go to UPS
warning. The status LED will remain on as if the control
is in normal mode. Outputs of the control, excluding LED
and alarm relay, will NOT be affected by UPS. The UPS
condition cannot occur during a compressor off cycle.
During UPS warning, the alarm relay will cycle on and
off. The cycle rate will be “on” for 5 seconds, “off” for 25
seconds, “on” for 5 seconds, “off” for 25 seconds, etc.
UPS warning code = 8
Swapped FP1/FP2 thermistors: During test mode, the control
monitors to see if the FP1 and FP2 thermistors are in the
appropriate places. If the control is in test mode, the control
will lockout, with code 9, after 30 seconds if:
a) The compressor is on in the cooling mode and the FP1
sensor is colder than the FP2 sensor, or:
b) The compressor is on in the heating mode and the FP2
sensor is colder than the FP1 sensor.
Swapped FP1/FP2 thermistor code = 9.
Diagnostic Features
The LED on the CXM board advises the technician of the
current status of the CXM control. The LED can display either
the current CXM mode or the last fault in memory if in test
mode. If there is no fault in memory, the LED will fl ash Code 1
(when in test mode).
Page 35
CXM Control Start-up Operation
The control will not operate until all inputs and safety controls
are checked for normal conditions. The compressor will have a
5 minute anti-short cycle delay at power-up. The fi rst time after
power-up that there is a call for compressor, the compressor
will follow a 5 to 80 second random start delay. After the
random start delay and anti-short cycle delay, the compressor
relay will be energized. On all subsequent compressor calls, the
random start delay is omitted.
Table 9b: Unit Operation
50YDSGT-GS/GT-SGT-GS/GT-S
T-stat signal
GFan onlyFan onlyFan only
G, Y or Y1Stage 1 heating
G, Y1, Y2Stage 2 heating
G, Y1, Y2, WStage 3 heating
G, WEmergency heatEmergency heatEmergency heat
G, Y or Y1, OStage 1 cooling
G, Y1, Y2, OStage 2 cooling
Variable Speed
Air Handler
1
1
1
2
2
Residential Split - 60Hz R22 &R410A
Rev.: 5 June, 2008
CXM Controls
Variable Speed
Air Handler
Stage 1 heating
Stage 2 heating
Stage 3 heating
Stage 1 cooling
Stage 2 cooling
3
3
3
4
4
PSC Air Handler
Stage 1 heating
Stage 2 heating
N/A
Cooling
6
N/A
5
5
1 Stage 1 = 1st stage compressor, 1st stage fan operation
Stage 2 = 2nd stage compressor, 2nd stage fan operation
Stage 3 = 2nd stage compressor, auxiliary electric heat, 2nd
or 3rd stage fan operation (depending on fan settings)
2 Stage 1 = 1st stage compressor, 1st stage fan operation, reversing valve
Stage 2 = 2nd stage compressor, 2nd stage fan operation, reversing valve
3 Stage 1 = compressor, 1st stage fan operation
Stage 2 = compressor, 2nd stage fan operation
Stage 3 = compressor, auxiliary electric heat, 2nd or 3rd stage fan operation (depending on fan settings)
4 Stage 1 = compressor, 1st stage fan operation, reversing valve
Stage 2 = compressor, 2nd stage fan operation, reversing valve
5 Stage 1 = compressor, fan
Stage 2 = compressor, auxiliary electric heat, fan
6 Cooling = compressor, fan, reversing valve
Carrier: Turn to the Experts
35
Page 36
Residential Split - 60Hz R22 &R410A
Rev.: 5 June, 2008
CXM Controls
Table 10: Nominal resistance at
various temperatures
ϒϒϒϒ
CXM Thermostat Details
Thermostat Compatibility - Most all heat pump thermostats can be used with the CXM control. However Heat/Cool
stats are NOT compatible with the CXM.
Anticipation Leakage Current - Maximum leakage current
for "Y" is 50 mA and for "W" is 20mA. Triacs can be used
if leakage current is less than above. Thermostats with
anticipators can be used if anticipation current is less than
that specifi ed above.
Thermostat Signals -
• "Y" and "W" have a 1 second recognition time when
being activated or being removed.
• "O" and "G" are direct pass through signals but are
monitored by the micro processor.
• "R" and "C" are from the transformer.
• "AL1" and "AL2" originate from the alarm relay.
• "A" is paralleled with the compressor output for use
with well water solenoid valves.
• The "Y" 1/4" quick connect is a connection point to the
"Y" input terminal P1 for factory use. This "Y" terminal
can be used to drive panel mounted relays such as the
loop pump relay.
36
Water-Source Heating and Cooling Systems
Page 37
Residential Split - 60Hz R22 &R410A
Rev.: 5 June, 2008
Unit Starting and Operating Conditions
Operating Limits
Environment – “Indoor” compressor section is designed for
indoor installation only. Never install “indoor” compressor
section in areas subject to freezing or where humidity levels
could cause cabinet condensation (such as unconditioned
spaces subject to 100% outside air). “Outdoor” unit is
designed for conditions where ambient air is below freezing
(see Table 11).
Power Supply – A voltage variation of +/– 10% of nameplate
utilization voltage is acceptable.
Starting Conditions
Consult Table 11 for the particular model. Starting conditions
vary depending upon model and are based upon the
following notes:
Notes:
1. Conditions in Table 11 are not normal or continuous
operating conditions. Minimum/maximum limits are
start-up conditions to bring the building space up to
occupancy temperatures. Units are not designed to
operate under these conditions on a regular basis.
Table 11: Unit Operation
2. Voltage utilization range complies with ARI
Standard 110.
Determination of operating limits is dependent primarily upon
three factors: 1) return air temperature. 2) water temperature,
and 3) ambient temperature. When any one of these factors
is at minimum or maximum levels, the other two factors
should be at normal levels to insure proper unit operation.
Extreme variations in temperature and humidity and/or
corrosive water or air will adversely affect unit performance,
reliability, and service life.
GT-PX/GT-GSGT-S
Operating Limits
CoolingHeatingCoolingHeating
Air Limits
Min. ambient air, DB45°F [7°C]39°F [4°C]-10°F [-23°C]-10°F [-23°C]
BEFORE POWERING SYSTEM, please check the following:
UNIT CHECKOUT
Balancing/shutoff valves: Insure that all isolation valves
are open and water control valves are wired.
Line voltage and wiring: Verify that voltage is within
an acceptable range for the unit and wiring and fuses/
breakers are properly sized. Verify that low voltage wiring
is complete.
Unit control transformer: Insure that transformer has the
properly selected voltage tap. Residential 208-230V units
are factory wired for 230V operation unless specifi ed
otherwise.
Loop/water piping is complete and purged of air. Water/
piping is clean.
Antifreeze has been added if necessary.
Entering water and air: Insure that entering water and air
temperatures are within operating limits of Table 7.
Low water temperature cutout: Verify that low water
temperature cut-out on the CXM/DXM control is properly
set.
Unit fan: Manually rotate fan to verify free rotation and
insure that blower wheel is secured to the motor shaft.
Be sure to remove any shipping supports if needed.
DO NOT oil motors upon start-up. Fan motors are preoiled at the factory. Check unit fan speed selection and
compare to design requirements.
Condensate line: Verify that condensate line is open and
properly pitched toward drain.
HWG pump is disconnected unless piping is completed
and air has been purged from the system.
Water fl ow balancing: Record inlet and outlet water
temperatures for each heat pump upon startup. This
check can eliminate nuisance trip outs and high velocity
water fl ow that could erode heat exchangers.
Unit air coil and fi lters: Insure that fi lter is clean and
accessible. Clean air coil of all manufacturing oils.
Unit controls: Verify that CXM fi eld selection options are
properly set. Low voltage wiring is complete.
Blower speed is set.
Service/access panels are in place.
SYSTEM CHECKOUT
System water temperature: Check water temperature
for proper range and also verify heating and cooling set
points for proper operation.
System pH: Check and adjust water pH if necessary to
maintain a level between 6 and 8.5. Proper pH promotes
longevity of hoses and fi ttings (see Table 3).
System fl ushing: Verify that all air is purged from the
system. Air in the system can cause poor operation or
system corrosion. Water used in the system must be
potable quality initially and clean of dirt, piping slag,
and strong chemical cleaning agents. Some antifreeze
solutions may require distilled water.
38
Water-Source Heating and Cooling Systems
Flow Controller pump(s): Verify that the pump(s) is wired
and in operating condition.
System controls: Verify that system controls function and
operate in the proper sequence.
Low water temperature cutout: Verify that low water
temperature cut-out controls are set properly
(FP1 - JW3).
Miscellaneous: Note any questionable aspects of
the installation.
CAUTION!
CAUTION! Verify that ALL water control valves are open
and allow water fl ow prior to engaging the compressor.
Freezing of the coax or water lines can permanently
damage the heat pump.
NOTICE! Failure to remove shipping brackets from springmounted compressors will cause excessive noise, and could
cause component failure due to added vibration.
CAUTION!
CAUTION! To avoid equipment damage, DO NOT
leave system fi lled in a building without heat during the
winter unless antifreeze is added to the water loop. Heat
exchangers never fully drain by themselves and will freeze
unless winterized with antifreeze.
Unit Start-up Procedure
1. Turn the thermostat fan position to “ON.” Blower should
start.
2. Balance air fl ow at registers.
3. Adjust all valves to their full open position. Turn on the
line power to all heat pump units.
4. Room temperature should be within the minimummaximum ranges of Table 11. During start-up checks,
loop water temperature entering the heat pump should
be between 30°F [-1°C] and 95°F [35°C].
5.
Two factors determine the operating limits of water
source heat pumps, (a) return air temperature, and (b)
water temperature. When any one of these factors is at a
minimum or maximum level, the other factor must be at
normal level to insure proper unit operation.
a. Adjust the unit thermostat to the warmest setting.
Place the thermostat mode switch in the “COOL”
position. Slowly reduce thermostat setting until the
compressor activates.
b. Check for cool air delivery at the unit grille within a
few minutes after the unit has begun to operate.
Note: Units have a fi ve minute time delay in the
control circuit that can be eliminated on the CXM/
DXM control board as shown below in Figure 29. See
controls description for details.
Page 39
Residential Split - 60Hz R22 &R410A
Rev.: 5 June, 2008
Unit Start-Up Procedure
c. Verify that the compressor is on and that the water
fl ow rate is correct by measuring pressure drop
through the heat exchanger using the P/T plugs and
comparing to Tables 12a through 12b.
d. Check the elevation and cleanliness of the
condensate lines. Dripping may be a sign of a
blocked line. Check that the condensate trap is fi lled
to provide a water seal.
e. Refer to Table 13. Check the temperature of both
entering and leaving water. If temperature is within
range, proceed with the test. If temperature is outside
of the operating range, check refrigerant pressures
and compare to Tables 14 and 15. Verify correct
water fl ow by comparing unit pressure drop across
the heat exchanger versus the data in Tables 12a
through 12b. Heat of rejection (HR) can be calculated
and compared to catalog data capacity pages. The
formula for HR for systems with water is as follows:
HR = TD x GPM x 500, where TD is the temperature
difference between the entering and leaving water,
and GPM is the fl ow rate in U.S. GPM, determined
by comparing the pressure drop across the heat
exchanger to Tables 12a through 12b.
f.
Check air temperature drop across the air coil when
compressor is operating. Air temperature drop should
be between 15°F and 25°F [8°C and 14°C].
g. Turn thermostat to “OFF” position. A hissing noise
indicates proper functioning of the reversing valve.
6. Allow fi ve (5) minutes between tests for pressure to
equalize before beginning heating test.
a. Adjust the thermostat to the lowest setting. Place the
thermostat mode switch in the “HEAT” position.
b. Slowly raise the thermostat to a higher temperature
until the compressor activates.
c. Check for warm air delivery within a few minutes after
the unit has begun to operate.
d. Refer to Table 13. Check the temperature of both
entering and leaving water. If temperature is within
range, proceed with the test. If temperature is outside
of the operating range, check refrigerant pressures
and compare to Tables 14 and 15 Verify correct water
fl ow by comparing unit pressure drop across the heat
exchanger versus the data in Tables 12a through
12b. Heat of extraction (HE) can be calculated and
compared to submittal data capacity pages. The
formula for HE for systems with water is as follows:
HE = TD x GPM x 500, where TD is the temperature
difference between the entering and leaving water,
and GPM is the fl ow rate in U.S. GPM, determined
by comparing the pressure drop across the heat
exchanger to Tables 12a through 12b.
e.
Check air temperature rise across the air coil when
compressor is operating. Air temperature rise should
be between 20°F and 30°F [11°C and 17°C].
f. Check for vibration, noise, and water leaks.
7. If unit fails to operate, perform troubleshooting analysis
(see troubleshooting section). If the check described
fails to reveal the problem and the unit still does not
operate, contact a trained service technician to insure
proper diagnosis and repair of the equipment.
8. When testing is complete, set system to maintain
desired comfort level.
9. BE CERTAIN TO FILL OUT AND RETURN ALL
WARRANTY REGISTRATION PAPERWORK.
Note: If performance during any mode appears abnormal,
refer to the CXM section or troubleshooting section of this
manual. To obtain maximum performance, the air coil should
be cleaned before start-up. A 10% solution of dishwasher
detergent and water is recommended.
WARNING!
WARNING! When the disconnect switch is closed, high
voltage is present in some areas of the electrical panel.
Exercise caution when working with energized equipment.
CAUTION!
CAUTION! Verify that ALL water control valves are open
and allow water fl ow prior to engaging the compressor.
Freezing of the coax or water lines can permanently
damage the heat pump.
Figure 29: Test Mode Pins
Short test pins together
to enter Test Mode and
speed-up timing and delays
for 20 minutes.
Carrier: Turn to the Experts
39
Page 40
Residential Split - 60Hz R22 &R410A
Rev.: 5 June, 2008
Unit Operating Conditions
Table 12a: Two-Stage R-410A Compressor Section Coax
Water Pressure Drop
ModelGPM
4.0
026
038
049
064
6.0
7.0
8.0
4.0
6.0
8.0
9.0
5.5
8.3
11.0
12.0
7.0
10.5
14.0
15.0
30°F50°F70°F90°F
1.5
3.1
4.1
5.1
1.2
2.6
4.5
5.7
1.1
2.2
3.9
4.5
0.5
1.9
3.9
4.8
Pressure Drop (psi)
1.3
2.6
3.4
4.3
1.0
2.5
4.2
5.2
0.9
2.1
3.6
4.2
0.3
1.8
3.5
4.3
1.1
2.3
3.0
3.8
0.8
2.3
4.0
4.8
0.8
2.0
3.2
3.8
0.2
1.7
3.2
3.9
1.0
2.1
2.7
3.4
0.6
2.1
3.7
4.4
0.7
1.8
3.1
3.5
0.1
1.6
2.9
3.5
Table 12b: R-22 Compressor Section Coax Water
Pressure Drop
ModelGPM
2
018
024
030
036
042
048
060
4
5
6
3
5
6
8
4
6
8
10
5
7
9
12
6
8
11
13
6
9
12
15
8
11
15
18
30°F50°F70°F90°F
0.6
1.6
2.1
2.8
0.6
1.3
1.8
2.9
0.9
1.8
2.9
4.2
1.6
2.6
3.9
6.4
2.1
3.2
5.5
7.3
2.1
3.9
6.4
9.4
1.2
2.1
3.6
5.0
Pressure Drop (psi)
0.6
1.4
2.0
2.6
0.6
1.2
1.7
2.7
0.9
1.7
2.7
3.9
1.4
2.4
3.7
5.9
1.9
3.0
5.1
6.8
1.9
3.7
5.9
8.7
1.2
2.0
3.4
4.7
0.5
1.3
1.8
2.4
0.5
1.1
1.5
2.5
0.8
1.5
2.5
3.6
1.3
2.3
3.4
5.5
1.8
2.8
4.7
6.3
1.8
3.4
5.5
8.1
1.1
1.8
3.1
4.3
0.5
1.3
1.7
2.3
0.5
1.1
1.4
2.3
0.8
1.4
2.3
3.4
1.3
2.1
3.2
5.2
1.7
2.6
4.5
5.9
1.7
3.2
5.2
7.6
1.0
1.7
2.9
4.1
Table 13: Water Temperature Change Through Heat
Exchanger
40
Water-Source Heating and Cooling Systems
Page 41
Residential Split - 60Hz R22 &R410A
Unit Operating Conditions
Table 14a: Size 026 Two-Stage R-410A Typical Unit Operating Pressures and Temperatures
Entering
Water
Temp °F
30
50
70
90
110
Water
Flow
GPM/
ton
1.5
2.25
3
1.5
2.25
3
1.5
2.25
3
1.5
2.25
3
1.5
2.25
3
Suction
Pressure
PSIG
122-132
122-132
122-132
132-142
132-142
132-142
139-149
139-149
139-149
141-151
141-151
141-151
145-155
145-155
145-155
Full Load Cooling - without HWG activeFull Load Heating - without HWG active
Discharge
Pressure
PSIG
159-179
146-166
132-152
186-206
172-192
158-178
281-301
267-287
253-273
374-394
360-380
346-366
473-493
458-478
441-461
Super-
heat
13-18
13-18
14-19
8-13
8-13
8-13
7-12
7-12
7-12
7-12
7-12
7-12
7-12
7-12
7-12
Sub-
cooling
9-14
7-12
7-12
8-13
6-11
6-11
8-13
8-13
7-12
9-14
9-14
8-13
10-15
10-15
9-14
Water Temp
Rise °F
16.7-18.7
12.3-14.3
7.9-9.9
16.3-18.3
12.1-14.1
7.8-9.8
15.7-17.7
11.6-13.6
7.6-9.6
14.6-16.6
10.7-12.7
6.9-8.9
13.6-15.6
9.9-11.9
6.2-8.2
Air Temp
Drop °F
DB
18-24
19-25
19-25
18-24
19-25
19-25
18-24
18-24
18-24
17-23
17-23
17-23
16-22
16-22
16-22
Suction
Pressure
PSIG
77-87
79-89
82-92
107-117
111-121
115-125
139-149
145-155
152-162
177-187
181-191
186-196
Discharge
Pressure
PSIG
278-298
280-300
282-302
314-334
315-335
317-337
350-370
352-372
354-374
392-412
397-417
402-422
Super-
heat
4-9
4-9
4-9
6-11
6-11
6-11
7-12
7-12
7-12
9-14
10-15
11-16
Operation Not Recommended
Sub-
cooling
10-15
10-15
10-15
13-18
13-18
13-18
15-20
15-20
15-20
17-22
17-22
17-22
Rev.: 5 June, 2008
Water Temp
Drop °F
5.9-7.9
4.2-6.2
2.7-4.7
8.9-10.9
6.7-8.7
4.5-6.5
11.3-13.3
8.5-10.5
5.8-7.8
14.4-16.4
10.8-12.8
7.1-9.1
Air Temp
Rise °F
DB
18-24
19-25
20-26
25-31
26-32
26-32
31-38
32-39
32-39
37-45
38-46
38-46
Table 14b: Size 038 Two-Stage R-410A Typical Unit Operating Pressures and Temperatures
Entering
Water
Temp °F
30
50
70
90
110
Water
Flow
GPM/
ton
1.5
2.25
3
1.5
2.25
3
1.5
2.25
3
1.5
2.25
3
1.5
2.25
3
Suction
Pressure
PSIG
122-132
121-131
121-131
131-141
130-140
130-140
138-148
137-147
137-147
142-152
142-152
142-152
147-157
147-157
147-157
Full Load Cooling - without HWG activeFull Load Heating - without HWG active
Discharge
Pressure
PSIG
153-173
145-165
135-155
222-242
208-228
194-214
299-319
280-300
263-283
388-408
367-387
347-367
486-506
465-475
444-464
Super-
heat
18-23
18-23
18-23
13-18
13-18
14-19
8-13
8-13
8-13
6-11
7-12
7-12
6-11
7-12
7-12
Sub-
cooling
9-14
8-13
8-13
10-15
9-14
9-14
13-18
12-17
12-17
13-18
8-13
8-13
13-18
8-13
8-13
Water Temp
Rise °F
22.1-24.1
16.8-18.8
10.5-12.5
21.9-23.9
16.1-18.1
10.3-12.3
21.5-23.5
15.8-17.8
10-12
20.5-22.5
14.9-16.9
9.3-11.3
19-21
14-16
9-11
Air Temp
Drop °F
DB
19-25
20-26
20-26
19-25
20-26
20-26
19-25
20-26
20-26
18-24
18-24
18-24
18-24
18-24
18-24
Suction
Pressure
PSIG
71-81
75-85
78-88
103-113
107-117
112-122
134-144
140-150
146-156
172-182
184-194
196-206
Discharge
Pressure
PSIG
263-283
267-287
270-290
292-312
296-316
301-321
322-342
328-358
334-354
360-380
369-389
378-398
Super-
heat
5-10
5-10
5-10
6-11
6-11
6-11
7-12
7-12
7-12
8-13
8-13
8-13
Operation Not Recommended
Table 14c: Size 049 Two-Stage R-410A Typical Unit Operating Pressures and Temperatures
Entering
Water
Temp °F
30
30
30
50
50
50
70
70
70
90
90
90
110
110
110
Water
Flow
GPM/
ton
1.5
2.25
3
1.5
2.25
3
1.5
2.25
3
1.5
2.25
3
1.5
2.25
3
Suction
Pressure
PSIG
112-122
111-121
111-121
125-135
123-133
122-132
133-143
132-142
131-141
138-148
137-147
136-146
144-154
143-153
142-152
Full Load Cooling - without HWG activeFull Load Heating - without HWG active
Discharge
Pressure
PSIG
187-207
167-187
147-167
245-265
227-247
208-228
314-334
294-314
274-294
401-421
379-399
357-377
502-522
477-497
452-472
Super-
heat
18-23
18-23
18-23
13-18
13-18
14-19
9-14
9-14
10-15
8-13
8-13
9-14
8-13
8-13
9-14
Sub-
cooling
23-28
21-26
20-25
19-24
18-23
16-21
17-22
16-21
14-19
16-21
15-20
13-18
14-19
13-18
12-17
Water Temp
Rise °F
20.7-22.7
15.5-17.5
10.2-12.2
20.9-22.9
15.6-17.6
10.2-12.2
20.5-22.5
15.2-17.2
9.9-11.9
19.2-21.2
14.3-16.3
9.3-11.3
18-20
13.3-15.3
8.5-10.5
Air Temp
Drop °F
DB
19-25
19-25
19-25
20-26
20-26
20-26
20-26
20-26
20-26
19-25
19-25
19-25
18-24
18-24
18-24
Suction
Pressure
PSIG
66-76
69-79
72-82
93-103
98-108
103-113
123-133
130-140
137-147
167-177
177-187
187-197
Discharge
Pressure
PSIG
261-281
264-284
267-287
289-309
295-315
301-321
319-339
329-349
336-356
365-385
374-394
388-408
Super-
heat
8-13
8-13
8-13
7-12
7-12
7-12
7-12
7-12
7-12
7-12
7-12
7-12
Operation Not Recommended
Sub-
cooling
2-5
2-5
2-5
2.5-7
2.5-7
2.5-7
2.5-7
2.5-7
2.5-7
2.5-7
2.5-7
2.5-7
Sub-
cooling
5-10
5-10
5-10
5-10
5-10
5-10
5-10
5-10
5-10
5-10
5-10
5-10
Water Temp
Drop °F
8.1-10.1
5.9-7.9
3.7-5.7
11.5-13.5
8.6-10.6
5.7-7.7
14.5-16.5
11.1-13.1
7.7-9.7
20.5-22.5
15-17
10-12
Water Temp
Drop °F
8-10
6-8
4-6
11.5-13.5
8.7-10.7
5.9-7.9
15-17
11.5-13.5
7.9-9.9
19.6-21.6
15-17
10.3-12.3
Air Temp
Rise °F
DB
17-23
18-24
19-25
23-29
24-30
24-30
28-35
29-36
30-37
36-44
37-45
39-47
Air Temp
Rise °F
DB
18-24
19-25
19-25
23-29
24-30
25-31
28-35
29-36
30-37
37-45
38-46
39-47
Carrier: Turn to the Experts
41
Page 42
Residential Split - 60Hz R22 &R410A
Rev.: 5 June, 2008
Unit Operating Conditions
Table 14d: Size 064 Two-Stage R-410A Typical Unit Operating Pressures and Temperatures
Entering
Water
Temp °F
30
50
70
90
110
Water
Flow
GPM/
ton
1.5
2.25
3
1.5
2.25
3
1.5
2.25
3
1.5
2.25
3
1.5
2.25
3
Suction
Pressure
PSIG
117-127
116-126
115-125
126-136
124-134
123-133
130-140
129-139
128-138
133-143
132-142
132-142
138-148
137-147
136-146
Full Load Cooling - without HWG activeFull Load Heating - without HWG active
Discharge
Pressure
PSIG
160-180
133-153
125-145
228-248
212-232
195-215
305-325
286-306
266-286
398-418
376-396
354-374
505-525
483-503
459-479
Super-
heat
16-21
17-22
18-23
8-13
11-16
14-19
8-13
9-14
11-16
8-13
8-13
8-13
6-11
6-11
6-11
Sub-
cooling
8-13
6-11
5-10
8-13
6-11
5-10
10-15
9-14
7-12
10-15
9-14
7-12
10-15
9-14
8-13
Water Temp
Rise °F
17.5-19.5
11.9-13.9
6.3-8.3
19.8-21.8
14.2-16.2
8.5-10.5
20.3-22.3
14.8-16.8
9.3-11.3
19.4-21.4
14.1-16.1
8.8-10.8
18.3-20.3
13.3-15.3
8.3-10.3
Air Temp
Drop °F
DB
16-22
16-22
16-22
20-26
20-26
20-26
21-27
21-27
21-27
20-26
20-26
20-26
19-25
19-25
19-25
Suction
Pressure
PSIG
66-76
69-79
72-82
95-105
100-110
105-115
128-138
133-143
139-149
173-183
177-187
182-192
Discharge
Pressure
PSIG
282-302
285-305
289-309
318-338
321-341
324-344
360-380
364-384
368-388
407-427
411-431
415-435
Super-
heat
9-15
9-15
9-15
9-15
9-15
9-15
8-14
8-14
8-14
8-14
8-14
8-14
Operation Not Recommended
Sub-
cooling
8-13
8-13
9-14
12-17
12-17
12-17
12-17
12-17
12-17
13-18
13-18
14-19
Water Temp
Drop °F
8-10
6-8
4-6
11.3-13.3
8.5-10.5
5.7-7.7
14-16
10.6-12.6
7.3-9.3
18.2-20.2
13.9-15.9
9.6-11.6
Air Temp
Rise °F
DB
21-27
21-27
22-28
27-33
28-34
30-36
33-38
34-40
35-41
42-50
43-51
44-52
Table 15: R-22 Typical Unit Operating Pressures and Temperatures
Entering
Water
Temp °F
Water
Flow
GPM/
ton
1.5
30
2.3
1.5
50
2.3
1.5
70
2.3
1.5
90
2.3
Suction
Pressure
PSIG
61-70
62-71
3
62-71
79-85
75-83
3
72-82
78-88
78-90
3
78-91
79-82
80-93
3
80-93
* Based on Nominal 400 CFM per ton per circuit arifl ow and 70°F EAT heating and 80/67°F cooling.
** Cooling air and water numbers can vary greatly with changes in humidity.
*** Water temperature difference based upon 1.5 - 3 GPM per ton of active circuit water fl ow.
**** Using liquid line pressure.
Full Load Cooling - without HWG activeFull Load Heating - without HWG active
Discharge
Pressure
PSIG
100-117
92-109
88-104
145-170
130-155
125-150
180-200
169-187
160-180
230-272
215-248
208-240
Super-
12-18
12-18
12-18
10-15
10-15
10-15
8-12
8-12
8-12
8-10
8-10
8-10
heat
Sub-
cooling
****
12-22
12-22
12-22
9-16
9-16
9-16
7-12
7-12
7-12
7-11
7-11
7-11
Water Temp
Rise *** °F
21-24
13-16
6-11
20-23
12-15
8-12
19-22
11-14
7-12
18-21
10-14
6-11
Air Temp
Drop °F
DB
21-26
21-26
21-26
20-25
20-25
20-25
19-24
19-24
19-24
17-23
17-23
17-23
Suction
Pressure
PSIG
34-39
37-42
38-44
51-58
53-62
55-65
71-82
77-89
81-92
Discharge
Pressure
PSIG
163-183
165-185
167-186
175-202
178-206
180-208
215-250
203-235
200-235
Super-
heat
5-10
5-10
5-10
9-12
9-12
9-12
10-14
10-14
10-14
Operation Not Recommended
Sub-
cooling
****
5-9
5-9
5-9
8-12
8-12
8-12
6-10
6-10
6-10
Water Temp
Drop *** °F
7.6-8.4
4.8-5.6
3.4-4.2
10.8-11.9
6.7-8.1
5.1-5.9
14.0-15.2
9.0-10.2
6.7-7.9
Air Temp
Rise °F
DB
14-20
16-22
16-22
23-29
24-30
25-31
28-34
30-37
31-38
42
Water-Source Heating and Cooling Systems
Page 43
Residential Split - 60Hz R22 &R410A
Rev.: 5 June, 2008
Preventive Maintenance
Water Coil Maintenance
(Direct ground water applications only)
If the system is installed in an area with a known high mineral
content (125 P.P.M. or greater) in the water, it is best to
establish a periodic maintenance schedule with the owner
so the coil can be checked regularly. Consult the well water
applications section of this manual for a more detailed water
coil material selection. Should periodic coil cleaning be
necessary, use standard coil cleaning procedures, which are
compatible with the heat exchanger material and copper
water lines. Generally, the more water fl owing through the
unit, the less chance for scaling. Therefore, 1.5 gpm per
ton [2.0 l/m per kW] is recommended as a minimum fl ow.
Minimum fl ow rate for entering water temperatures below
50°F [10°C] is 2.0 gpm per ton [2.6 l/m per kW].
Water Coil Maintenance
(All other water loop applications)
Generally water coil maintenance is not needed for closed
loop systems. However, if the piping is known to have
high dirt or debris content, it is best to establish a periodic
maintenance schedule with the owner so the water coil
can be checked regularly. Dirty installations are typically
the result of deterioration of iron or galvanized piping or
components in the system. Open cooling towers requiring
heavy chemical treatment and mineral buildup through water
use can also contribute to higher maintenance. Should
periodic coil cleaning be necessary, use standard coil
cleaning procedures, which are compatible with both the
heat exchanger material and copper water lines. Generally,
the more water fl owing through the unit, the less chance for
scaling. However, fl ow rates over 3 gpm per ton (3.9 l/m per
kW) can produce water (or debris) velocities that can erode
the heat exchanger wall and ultimately produce leaks.
Hot Water Generator Coils
See water coil maintenance for ground water units. If the
potable water is hard or not chemically softened, the high
temperatures of the desuperheater will tend to scale even
quicker than the water coil and may need more frequent
inspections. In areas with extremely hard water, a HWG is
not recommended.
Condensate Drain
In areas where airborne bacteria may produce a “slimy”
substance in the drain pan, it may be necessary to treat the
drain pan chemically with an algaecide approximately every
three months to minimize the problem. The condensate pan
may also need to be cleaned periodically to insure indoor
air quality. The condensate drain can pick up lint and dirt,
especially with dirty fi lters. Inspect the drain twice a year to
avoid the possibility of plugging and eventual overfl ow.
Compressor
Conduct annual amperage checks to insure that amp draw is
no more than 10% greater than indicated on the serial plate
data.
Fan Motors
Consult air handler I.O.M. for maintenance requirements.
Air Coil
The air coil must be cleaned to obtain maximum
performance. Check once a year under normal operating
conditions and, if dirty, brush or vacuum clean. Care must
be taken not to damage the aluminum fi ns while cleaning.
CAUTION: Fin edges are sharp.
Cabinet - “Indoor” Compressor Section
Do not allow water to stay in contact with the cabinet for
long periods of time to prevent corrosion of the cabinet sheet
metal. Generally, cabinets are set up from the fl oor a few
inches [7 - 8 cm] to prevent water from entering the cabinet.
The cabinet can be cleaned using a mild detergent.
Refrigerant System
To maintain sealed circuit integrity, do not install service
gauges unless unit operation appears abnormal. Reference
the operating charts for pressures and temperatures. Verify
that air and water fl ow rates are at proper levels before
servicing the refrigerant circuit.
Filters
Filters must be clean to obtain maximum performance.
Filters should be inspected every month under normal
operating conditions and be replaced when necessary. Units
should never be operated without a fi lter.
Washable, high effi ciency, electrostatic fi lters, when dirty,
can exhibit a very high pressure drop for the fan motor and
reduce air fl ow, resulting in poor performance. It is especially
important to provide consistent washing of these fi lters (in
the opposite direction of the normal air fl ow) once per month
using a high pressure wash similar to those found at selfserve car washes.
Carrier: Turn to the Experts
43
Page 44
Residential Split - 60Hz R22 &R410A
Rev.: 5 June, 2008
Troubleshooting
General
If operational diffi culties are encountered, perform
the preliminary checks below before referring to the
troubleshooting charts.
• Verify that the unit is receiving electrical supply power.
• Make sure the fuses in the fused disconnect switches
are intact.
After completing the preliminary checks described above,
inspect for other obvious problems such as leaking
connections, broken or disconnected wires, etc. If everything
appears to be in order, but the unit still fails to operate
properly, refer to the “CXM Troubleshooting Process
Flowchart” or “Functional Troubleshooting Chart.”
CXM Board
CXM board troubleshooting in general is best summarized
as simply verifying inputs and outputs. After inputs and
outputs have been verifi ed, board operation is confi rmed and
the problem must be elsewhere. Below are some general
guidelines for troubleshooting the CXM control.
Field Inputs
All inputs are 24VAC from the thermostat and can be verifi ed
using a volt meter between C and Y, G, O, W. 24VAC will be
present at the terminal (for example, between “Y” and “C”) if
the thermostat is sending an input to the CXM board.
Sensor Inputs
All sensor inputs are ‘paired wires’ connecting each component
to the board. Therefore, continuity on pressure switches, for
example can be checked at the board connector.
Test Mode
Test mode can be entered for 20 minutes by shorting the test
pins. The CXM board will automatically exit test mode after
20 minutes.
CXM Troubleshooting Process Flowchart/Functional
Troubleshooting Chart
The “CXM Troubleshooting Process Flowchart” is a quick
overview of how to start diagnosing a suspected problem,
using the fault recognition features of the CXM board. The
“Functional Troubleshooting Chart” on the following page is
a more comprehensive method for identifying a number of
malfunctions that may occur, and is not limited to just the
CXM controls. Within the chart are fi ve columns:
• The “Fault” column describes the symptoms.
• Columns 2 and 3 identify in which mode the fault is likey to
occur, heating or cooling.
• The “Possible Cause column” identifi es the most likely
sources of the problem.
• The “Solution” column describes what should be done to
correct the problem.
WARNING!
WARNING! HAZARDOUS VOLTAGE! DISCONNECT ALL
ELECTRIC POWER INCLUDING REMOTE DISCONNECTS
BEFORE SERVICING.
Failure to disconnect power before servicing can cause
severe personal injury or death.
The thermistor resistance should be measured with the
connector removed so that only the impedance of the
thermistor is measured. If desired, this reading can be
compared to the thermistor resistance chart shown in the
CXM/DXM AOM manual. An ice bath can be used to check
calibration of the thermistor.
Outputs
The compressor relay is 24VAC and can be verifi ed using a
voltmeter. The fan signal is passed through the board to the
external fan relay (units with PSC motors only). The alarm
relay can either be 24VAC as shipped or dry contacts for use
with DDC controls by clipping the JW1 jumper. Electric heat
outputs are 24VDC “ground sinking” and require a volt meter
set for DC to verify operation. The terminal marked “24VDC”
is the 24VDC supply to the electric heat board; terminal “EH1”
is stage 1 electric heat; terminal “EH2” is stage 2 electric heat.
When electric heat is energized (thermostat is sending a “W”
input to the CXM controller), there will be 24VDC between
terminal “24VDC” and “EH1” (stage 1 electric heat) and/or
“EH2” (stage 2 electric heat). A reading of 0VDC between
“24VDC” and “EH1” or “EH2” will indicate that the CXM board
is NOT sending an output signal to the electric heat board.
44
Water-Source Heating and Cooling Systems
Page 45
See “Does
not Operate
in Clg”
See “Only
Comp
Runs”
Start
Did Unit
Attempt to
Start?
Did Unit
Lockout at
Start-up?
Unit Short
Cycles?
Only Fan
Runs?
Only
Compressor
Runs?
Did unit lockout
after a period of
operation?
Does unit
operate in
cooling?
Unit is OK!
‘See Performance
Troubleshooting’ for
further help
Check Main
power (see power
problems)
Check fault LED code
on control board
Yes
No
No
No
No
No
Yes
No
Yes
See HP
Fault
See
LP/LOC
Fault
See FP1
Fault
See FP2
Fault
See
Condensate
Fault
See Over/
Under
Voltage
No fault
shown
Replace
CXM
See “Unit
short
cycles”
See “Only
Fan Runs”
No
Yes
Yes
Yes
Yes
CXM Functional
Troubleshooting Chart
WARNING!
WARNING! HAZARDOUS VOLTAGE! DISCONNECT ALL
ELECTRIC POWER INCLUDING REMOTE DISCONNECTS
BEFORE SERVICING.
Failure to disconnect power before servicing can cause
severe personal injury or death.
Residential Split - 60Hz R22 &R410A
Rev.: 5 June, 2008
CXM Process Flow Chart
Carrier: Turn to the Experts
45
Page 46
Residential Split - 60Hz R22 &R410A
Rev.: 5 June, 2008
Functional Troubleshooting
FaultHtg Clg Possible CauseSolution
Main power ProblemsXX Green Status LED OffCheck Line Voltage circuit breaker and disconnect
HP Fault-Code 2X Reduced or no water flowCheck pump operation or valve operation/setting
High pressurein cooling
LP/LOC Fault-Code 3XX Insufficient chargeCheck for refrigerant leaks
Low Pressure/Loss of Charge X
FP1 Fault - Code 4XReduced or no water flowCheck pump operation or water valve operation/setting
Water Coil low
temperature limit
FP2 fault - Code 5X Reduced or no Air flowCheck for dirty air filter and clean or replace
Air Coil low
temperature limit
Condensate Fault-Code
Over/Under VoltageCode 7
(Auto resetting)Check power supply wire size
Unit Performance
Sentinel-Code 8
No Fault Code ShownXX No compre ssor operationSee "Only fan operates"
Unit Short CyclesXX Dirty Air FilterCheck and Clean air filter
Only Fan RunsXX Thermostat positionInsure thermostat set for heating or cooling operation
6
X
Water Temperature out of range in
cooling
XReduced or no Air flowCheck for dirty air filter and clean or replace
in heatingCheck fan motor operation and airflow restrictions
X
Air Temperature out of range in
heating
XX
Overcharged with refrigerant
XX
Bad HP SwitchCheck switch continuity and operation. Replace
Compressor pump down at startup
in heatingPlugged strainer or filter. Clean or replace.
XInadequate anti-freeze levelCheck antifreeze density with hydrometer
Improper temperature limit setting
X
(30°F vs 10°F [-1°C vs -12°C])
XWater Temperature out of range Bring water temp within design parameters
XX Bad thermistorCheck temp and impedance correlation per chart
in coolingCheck fan motor operation and airflow restrictions
X Air Temperature out of range
Improper temperature limit setting
X
(30°F vs 10°F [-1°C vs -12°C])
XX Bad thermistorCheck temp and impedance correlation per chart
XX Blocked DrainCheck for blockage and clean drain
XX Improper trapCheck trap dimensions and location ahead of vent
X Poor DrainageCheck for piping slope away from unit
X Moisture on sensorCheck for moisture shorting to air coil
XX Under Voltage
XX
Over Voltage
XHeating mode FP2>125°F [52°C] Check for poor air flow or overcharged unit.
Cooling Mode FP1>125°F [52°C]
X
OR FP2< 40ϒF [4ϒC]
XX Compressor OverloadCheck and Replace if necessary
XX Control boardReset power and check operation
XX Unit in "Test Mode"Reset p ower or wait 20 minutes for auto exit.
XX Unit selection
XX Compressor OverloadCheck and Replace if necessary
XX Unit locked outCheck for lockout codes. Reset power.
XX Compressor OverloadCheck compressor overload. Replace if necessary.
XX Thermostat wiring
Check for line voltage between L1 and L2 on the contactor
Check for 24VAC between R and C on CXM/DXM
Check primary/secondary voltage on transformer
Check water flow adjust to proper flow rate
Bring water temp within design parameters
Dirty Air Coil- construction dust etc.
Too high of external static. Check static vs blower table
Bring return air temp within design parameters
Check superheat/subcooling vs typical operating condition
table
Check charge and start-up water flow
Check water flow adjust to proper flow rate
Clip JW3 jumper for antifreeze (10°F [-12°C]) use
Too high of external static. Check static vs blower table
Too much cold vent air? Bring entering air temp within
design parameters
Normal airside applications will require 30°F [-1°C] only
Check slope of unit toward outlet
Poor venting. Check vent location
Check power supply and 24VAC voltage before and during
operation.
Check compressor starting. Need hard start kit?
Check 24VAC and unit transformer tap for correct power
supply voltage
Check power supply voltage and 24VAC before and during
operation.
Check 24VAC and unit transformer tap for correct power
supply voltage
Check for poor water flow, or air flow
Unit may be oversized for space. Check sizing for actual
load of space.
Check thermostat wiring at heat pump. Jumper Y and R
for compressor operation in test mode.
46
Water-Source Heating and Cooling Systems
Page 47
Residential Split - 60Hz R22 &R410A
r
C
g
g
Functional Troubleshooting
FaultHtg Clg Possible CauseSolution
Main power ProblemsXX Green Status LED OffCheck Line Voltage circuit breaker and disconnect
HP Fault-Code 2X Reduced or no water flowCheck pump operation or valve operation/setting
High pressurein cooling
LP/LOC Fault-Code 3XX Insufficient chargeCheck for refrigerant leaks
Performance Troubleshooting
Low Pressure/Loss of Charge X
FP1 Fault - Code 4XReduced or no water flowCheck pump operation or water valve operation/setting
Water Coil low
temperature limit
FP2 fault - Code 5X Reduced or no Air flowCheck for dirty air filter and clean or replace
Air Coil low
temperature limit
Condensate Fault-Code
Over/Under VoltageCode 7
(Auto resetting)Check power supply wire size
Unit Performance
Sentinel-Code 8
No Fault Code ShownXX No compressor operationSee "Only fan operates"
Unit Short CyclesXX Dirty Air FilterCheck and Clean air filter
6
X
Water Temperature out of range in
cooling
XReduced or no Air flowCheck for dirty air filter and clean or replace
in heatingCheck fan motor operation and airflow restrictions
X
Air Temperature out of range in
heating
XX
Overcharged with refrigerant
XX
Bad HP SwitchCheck switch continuity and operation. Replace
ompressor pump down at start-
up
in heatingPlugged strainer or filter. Clean or replace.
XInadequate anti-freeze levelCheck antifreeze density with hydrometer
Improper temperature limit setting
X
(30°F vs 10°F [-1°C vs -12°C])
XWater Temperature out of range Bring water temp within design parameters
XX Bad thermistorCheck temp and impedance correlation per chart
in coolingCheck fan motor operation and airflow restrictions
X Air Temperature out of range
Improper temperature limit setting
X
(30°F vs 10°F [-1°C vs -12°C])
XX Bad thermistorCheck temp and impedance correlation per chart
XX Blocked DrainCheck for blockage and clean drain
XX Improper trapCheck trap dimensions and location ahead of vent
X Poor DrainageCheck for piping slope away from unit
X Moisture on sensorCheck for moisture shorting to air coil
XX Under Voltage
XX
Over Voltage
XHeating mode FP2>125°F [52°C] Check for poor air flow or overcharged unit.
Cooling Mode FP1>125°F [52°C]
X
OR FP2< 40ϒF [4ϒC]
XX Compressor OverloadCheck and Replace if necessary
XX Control boardReset power and check operation
XX Unit in "Test Mode"Reset power or wait 20 minutes for auto exit.
XX Unit selection
XX Compressor OverloadCheck and Replace if necessary
Check for line voltage between L1 and L2 on the contacto
Check for 24VAC between R and C on CXM/DXM
Check primary/secondary voltage on transformer
Check water flow adjust to proper flow rate
Bring water temp within design parameters
Dirty Air Coil- construction dust etc.
Too high of external static. Check static vs blower table
Bring return air temp within design parameters
Check superheat/subcooling vs typical operating condition
table
Check charge and start-up water flow
Check water flow adjust to proper flow rate
Clip JW3 jumper for antifreeze (10°F [-12°C]) use
Too high of external static. Check static vs blower table
Too much cold vent air? Bring entering air temp within
design parameters
Normal airside applications will require 30°F [-1°C] only
Check slope of unit toward outlet
Poor venting. Check vent location
Check power supply and 24VAC voltage before and durin
operation.
Check compressor starting. Need hard start kit?
Check 24VAC and unit transformer tap for correct power
supply voltage
Check power supply voltage and 24VAC before and durin
operation.
Check 24VAC and unit transformer tap for correct power
supply voltage
Check for poor water flow, or air flow
Unit may be oversized for space. Check sizing for actual
load of space.
Look up pressure drop in
I.O.M. or spec. catalog to
determine flow rate.
COOLING CYCLE ANALYSIS -
AIR HANDLER SECTION COMPRESSOR SECTION
AIR
COIL
ϒFϒF
COOLING
EXPANSION
VALVE*
HEATING
EXPANSION
VALV E* *
ϒF
LIQUID LINE
COAX
ϒFϒF
PSIPSI
WATER INWATER OUT
HWG
PSI
ϒF
SUCTION
COMPRESSOR
DISCHARGE
ϒF
PSI
PSI
ϒF
SAT
SAT
SAT
AIR
COIL
ϒFϒF
COOLING
EXPANSION
VALVE*
Look up pressure drop in
I.O.M. or spec. catalog to
determine flow rate.
*Cooling expansion valve meters in the cooling mode, and bypasses in the heating mode.
**Heating expansion valve meters in the heating mode, and bypasses in the cooling mode.
HEATING
EXPANSION
VALV E* *
ϒF
LIQUID LINE
COAX
ϒFϒF
PSIPSI
WATER INWATER OUT
HWG
SUCTION
COMPRESSOR
DISCHARGE
ϒF
PSI
SAT
Heat of Extraction ( Absorbtion) or Heat of Rejection =
________ flow rate (gpm) x ________ temp. diff. (deg. F) x __________ fluid factor
Superheat
Subcooling
Note: Never connect refrigerant gauges during startup procedures. Conduct water-side analysis using P/T ports to determine water fl ow
and temperature difference. If water-side analysis shows poor performance, refrigerant troubleshooting may be required. Connect refrigerant
gauges as a last resort.
The Manufacturer works continually to improve its products. As a result, the design and specifi cations of each product at the time for order may be
changed without notice and may not be as described herein. Please contact the Manufacturer’s Customer Service Department at 1-405-745-6000 for
specifi c information on the current design and specifi cations. Statements and other information contained herein are not express warranties and do
not form the basis of any bargain between the parties, but are merely Manufacturer’s opinion or commendation of its products.
The management system governing the manufacture of Manufacturer’s products is ISO 9001:2000 certifi ed.