• 040-110, 130 (60 Hz) UNITS
(And Associated Modular Units)
• 130 (50 Hz), 150-210 UNITS
(And Associated Modular Units)
FIELD WIRING .............................69,70
REPLACING DEFECTIVE PROCESSOR
MODULE (PSIO) ..........................70
Installation .................................70
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 2
Tab 5c
PC 903Catalog No. 563-079Printed in U.S.A.Form 30GN-3TPg 17-95Replaces: 30G-1T
Page 2
SAFETY CONSIDERATIONS
Installing, starting up, and servicing this equipment can
be hazardous due to system pressures, electrical components, and equipment location (roof, elevatedstructures,etc.).
Only trained, qualified installers and service mechanics should
install, start up, and service this equipment.
When working on this equipment, observe precautions in
the literature, and ontags, stickers, and labelsattached to the
equipment, and any other safety precautions that apply. Follow all safety codes. Wear safety glasses and work gloves.
Use care in handling, rigging, and setting this equipment,
and in handling all electrical components.
Electrical shock can cause personal injury and death.
Shut off all power to this equipment during installation
and service. There may be more than one disconnect
switch. Tag all disconnect locations to alert others not
to restore power until work is completed.
This unit uses a microprocessor-based electronic control system. Do not use jumpers or other tools to short
out components, or to bypass or otherwise depart from
recommended procedures. Any short-to-ground of the
control board or accompanying wiring may destroy the
electronic modules or electrical components.
GENERAL
IMPORTANT: This publication contains controls, operation and troubleshooting data for 30GN040-420
Flotronic™ II chillers.
Circuits are identified as circuitsAand B, and compressors are identified as A1,A2, etc. in circuit A, and
B1, B2, etc. in circuit B.
Use this guide in conjunction with separate Installation Instructions booklet packaged with the unit.
The 30G Series standard Flotronic II chillers feature
microprocessor-based electronic controls and an electronic
expansion valve (EXV) in each refrigeration circuit.
NOTE: The 30GN040 and 045 chillers with a factoryinstalled brine option have thermal expansion valves (TXV)
instead of the EXV.
Unit sizes 230-420 are modular units which are shipped
as separate sections (modulesAand B). Installation instructions specific to these units are shipped inside the individual
modules. See Table 1 for a listing of unit sizes and modular
combinations. For modules 230B-315B, follow all general
instructions as noted for unit sizes 080-110. For all remaining modules, follow instructions for unit sizes 130-210.
The Flotronic II control system cycles compressor unloaders and/or compressors to maintain the selected leaving
fluid temperature set point. It automatically positions theEXV
to maintain the specified refrigerant superheat entering the
compressor cylinders. It also cycles condenser fans on and
off to maintain suitable head pressure for each circuit. Safeties are continuously monitored to prevent the unit from operating under unsafe conditions. A scheduling function, programmed by the user, controls the unit occupied/unoccupied
schedule. The control also operates a test program that allows the operator to check output signals and ensure components are operable.
The control system consists ofaprocessor module (PSIO),
a low-voltage relay module (DSIO-LV), 2 EXVs, an EXV
driver module (DSIO-EXV), a 6-pack relay board, a keypad
and display module (also called HSIO or LID), thermistors,
and transducers to provide inputs to the microprocessor. A
standard options module (SIO) is used to provide additional
functions. See Fig. 1 for a typical 30GN Control Panel.
MAJOR SYSTEM COMPONENTS
Processor Module —
ating software and controls the operation of the machine. It
continuously monitors information received from the various transducers and thermistors and communicates with the
relay modules and 6-pack relay board to increase or decrease the active stages of capacity. The processor module
This module contains the oper-
2
Page 3
COMM 3 PWR
POINT NUMBER
OF
FIRST CHANNEL
COMM 1
PWR
COMM 3
S1
S2
XX
XX
STAT EXPN
HIST CLR SCHD
SRVCSET
TESTENTR
STATUS
COMM
J4J4
789
456
123
–
0•
STATUS
J5
COMM
LVEXV
FUSE 1
S
U
E
F
F
E
U
S
S
U
E
F
FUSE 2
GFI - CO
( 5 AMP MAX )
LOCAL/
ENABLE
STOP
CCN
CB5
CB6
12
3+
5VDC
HK35AA002
Potter & Brumfield
CZ770
SW1
FUSE 3
30GT510568 –
4-
EQUIP GND
99NA505322 D
LEGEND
CCN — Carrier Comfort Network
TB— Terminal Block
Fig. 1 — 30GN Control Panel (040-110 Unit Shown)
3
Page 4
also controls the EXV driver module (as appropriate), commanding it to open or close each EXV in order to maintain
the proper superheat entering thecylinders of each lead compressor.Information istransmittedbetweentheprocessormodule and relay module, the EXV driver module, and the keypad and display module through a 3-wire communications
bus. The options module is also connected to the communications bus.
For the Flotronic™ II chillers,the processor monitors system pressure by means of 6 transducers, 3 in each lead compressor.Compressorsuctionpressure, discharge pressure, and
oil pressure are sensed. If the processor senses high discharge pressure or low suction pressure,it immediately shuts
down all compressors in the affected circuit. During operation, if low oil pressure is sensed for longer than one minute,
all compressors in the affected circuit are shut down. At startup, the oil pressure signal is ignored for 2 minutes. If shutdown occurs due to any of these pressure faults, the circuit
is locked out and the appropriate fault code is displayed.
Low-Voltage Relay Module — This module closes
contacts to energize compressor unloaders and/or compressors. It also senses the status of the safeties for all compressors and transmits this information to the processor.
Electronic Expansion Valve Module (If So
Equipped)—
cessor and operates the electronic expansion valves.
This module receives signals fromthe pro-
Options Module — This module allows the use of Flo-
tronic II features such as dual set point, remote reset, demand limit, hot gas bypass, and accessory unloaders. The
options module also allows for reset and demand limit to be
activated from a remote 4-20 mA signal. The options module is installed at the factory.
Keypad andDisplay Module (Also Called HSIO
or LID) —
tion keys, 5 operative keys, 12 numeric keys, and an alphanumeric 8-character LCD (liquid crystal display). Key usage is explained in Accessing Functions and Subfunctions
section on page 24.
This device consists of a keypad with 6 func-
Control Switch — Control of the chiller is defined by
the position of the LOCAL/ENABLE-STOP-CCN switch.
This is a 3-position manual switch that allows the chiller to
be put under the control of its own FlotronicIIcontrols,manually stopped, or put under the control of a Carrier Comfort
Network (CCN). Switch allows unit operation as shown in
Table 2.
In the LOCAL/ENABLE position, the chiller is under local control and responds to the scheduling configuration and
set point data input at its own local interface device (keypad
and display module).
Table 2 — LOCAL/ENABLE-STOP-CCN
Switch Positions and Operation
SWITCH
POSITION
STOPUnit Cannot Run Read/WriteRead Only
LOCAL/ENABLE Unit Can RunRead/Limited Write Read Only
CCN Stop —Unit Cannot Run Read OnlyRead/Write
Run —Unit Can RunRead Only
UNIT
OPERATION
CONFIGURATION AND
SET POINT CONTROL
Keypad ControlCCN Control
Read/Limited
Write
In the CCN position, the chiller is under remote control
and responds only to CCN network commands. The occupied/
unoccupied conditions are defined by the network. All keypad and display functions can be read at the chiller regardless of position of the switch.
CCN run or stop condition is established by a command
from the CCN network. It is not possible to force outputs
from the CCN network, except that an emergency stop command shuts down the chiller immediately and causes ‘ ‘ALARM
52’’ to be displayed.
Electronic Expansion Valve (EXV) — The micro-
processor controls the EXV (if so equipped) throughtheEXV
driver module. Inside the expansion valve is a linear actuator stepper motor.
The lead compressor in each circuit has a thermistor and
a pressure transducer located in the suction manifold after
the compressor motor. The thermistor measures the temperature of the superheated gas entering the compressor cylinders.Thepressuretransducermeasurestherefrigerant pressure
in the suction manifold. The microprocessor converts the pressure reading to a saturated temperature. The difference between the temperature of the superheated gas and the saturation temperature is the superheat.Themicroprocessorcontrols
the position of the electronic expansion valve stepper motor
to maintain 30 F (17 C) superheat.
At initial unit start-up, the EXV position is at zero. After
that, the microprocessor keeps accurate track of the valve
position in order to usethis information as input for theother
control functions. The control monitors the superheat and
the rate of change of superheat to control the position of the
valve. The valve stroke is very large, which results in very
accurate control of the superheat.
Thermostatic Expansion Valves(TXV) — Model
30GN040 and 045 units with factory-installed brine option
are equipped with conventional thermostatic expansion valves
with liquid line solenoids. The liquid line solenoid valves
are not intended to be a mechanical shut-off. When service
is required, use the liquid line service valve to pump down
the system.
4
Page 5
The TXV is set at the factory to maintain approximately
8 to 12° F (4.4to6.7° C) suction superheat leaving thecooler
by monitoring the proper amount of refrigerant intothecooler.
All TXVs are adjustable, but should not be adjusted unlessabsolutely necessary.When TXVis used,thermistorsT7 and
T8 are not required.
The TXV is designed to limit the cooler saturated suction
temperature to 55 F (12.8 C). This makes it possible for unit
to start at high cooler fluid temperatures without overloading the compressor.
Sensors— The Flotronic™ II chillercontrolsystemgath-
ers information from sensors to control the operation of the
chiller. The units use 6 standard pressure transducers and
4 standard thermistors to monitor system pressures and temperatures at various points within the chiller. Sensors are listed
in Table 3.
Table 3 — Thermistor and Transducer Locations
Fig. 2 — Compressor Protection Control Module
SensorLocation
T1Cooler Leaving Fluid Temp
T2Cooler Entering Fluid Temp
T7Compressor Suction Gas Temp Circuit A
T8Compressor Suction Gas Temp Circuit B
T10Remote Temperature Sensor (Accessory)
110, and 230B-315B, has its own CPCS as standard equipment. See Fig. 2. All 30GN040-060 and 070 (60 Hz) units
feature the CPCS as an accessory, and CR (control relay) as
standard equipment. The 30GN130-210 and associated modular units havea CR as standard equipment. The CPCS or CR
is used tocontrol and protect the compressors and crankcase
heaters. The CPCS provides the following functions:
• compressor contactor control
• crankcase heater control
• compressor ground current protection
• status communication to processor board
• high-pressure protection
The CR provides all of the same functions as the CPCS
with the exception of compressor ground current protection.
Ground current protection is accomplished by using a CGF
(compressor ground fault module) in conjunction with the
CR. The CGF (See Fig. 3) provides the same ground fault
function as the CPCS for units where the CPCS is not
utilized.
One large relay is located on the CPCS board. This relay
(or CR) controls the crankcase heater and compressor
contactor. The CPCS also provides a set of signal contacts
that the microprocessor monitors to determine the operating
status of the compressor. If the processor board determines
that the compressor is notoperatingproperly through the signal contacts, it will lock the compressor off by deenergizing
the proper 24-v control relay on the relay board. The
CPCS board contains logic that can detect if the current-to-
Fig. 3 — Compressor Ground Fault Module
ground of any compressor winding exceeds 2.5 amps. If this
condition occurs, the CPCS module shuts down the
compressor.
A high-pressure switch with a trip pressure of 426
± 7 psig (2936 ± 48 kPa), is wired in series with the CPCS.
If this switch opens during operation, the compressor stops
and the failure is detected by the processor when the signal
contacts open. The compressor islocked off. If the leadcompressor in either circuit is shut down by the high-pressure
switch or ground current protector, all compressors in the
circuit are locked off.
OPERATION DATA
Capacity Control —
compressor to give capacity control steps as shown in
Tables 4A-4C. The unit controls leaving chilled fluid temperature. Entering fluid temperature is used by the microprocessor in determining the optimum time to add or subtract steps of capacity, but is not a control set point.
The chilled fluid temperature set point can be automatically reset by the return temperature reset or space and
outdoor-air temperature reset features. It can also be reset
from an external 4 to 20 mA signal, or from a network
signal.
The operating sequences shown are some of many possible loading sequences for the control of the leaving fluid
temperature. If a circuit has more unloaders than another,
that circuit will always be the lead circuit.
EXV UNITS (All 30GN units except 040 and 045 with optional brine) — The microprocessor controls the condenser
fans in order to maintain the lowest condensing temperature
possible, thus the highestunit efficiency. Instead of using the
conventional head pressure control methods, thefansare controlled by the position of the EXV and suction superheat.
As the condensing temperature drops, the EXV opens to
maintain the proper suction superheat.Once the EXV is fully
open, if the condensing temperature continues to drop, the
suction superheat begins to rise. Once the suction superheat
is greater than 40 F (22.2 C), a fan stage is removed after
2 minutes.
As the condensing temperature rises, the EXV closes to
maintain the proper suction superheat. Once the EXV has
closed to 39.5% open (600 steps open), a fan stage is added
after 2 minutes.
During start-up, all the condenser fans are started when
the condensing temperature reaches 95 F (35 C) to prevent
excessive discharge pressure during pulldown. See Table 5
for condenser fan sequence of operation.
For low-ambient operation, the leadfan in each circuit can
be equipped with the optional or accessory Motormastert
III head pressure controller. This control has its own sensor
which is mounted on a return bend in the liquid portion of
the condenser. It will vary the fan speed to maintain a saturated condensing temperature of 100 F. The controls automatically default to condensing temperature control during
this first stage of condenser-fan operation. When subsequent
fan stages start, the controls revert to EXV fan control.
TXV UNITS (30GN040,045 with optional brine only) —
Head pressure control is based on set point control. The microprocessor stages the condenser fans to maintain the set point
temperature specified by the controller.
Keypad andDisplay Module (Also Called HSIO
or LID) —
the operator to communicate with the processor. It is used to
enter configurations and set points and to read data, perform
tests, and set schedules. This device consists of a keypad
with 6 function keys, 5 operative keys, 12 numeric keys
(0 to 9, •,and -), and an alphanumeric, 8-character LCD. See
Fig. 4. See Table 6 for key usage.
IMPORTANT: When entering multiple character inputs beginning with a zero, a decimal point must be
entered in place of the first zero. When entering an input of zero, only the decimal point need be entered.
ACCESSING FUNCTIONSANDSUBFUNCTIONS — See
Tables6-8.Table 7 shows the 6 functions (identified by
name) and the subfunctions (identified by number).
AUTOMATIC DEFAULT DISPLAY — When keypad has
not been used for 10minutes, display automatically switches
to the rotating automatic default display. This display has
7 parts, listed below, which appear in continuous rotating
sequence.
DISPLAYEXPANSION
TUE 15:45TODAY IS TUE, TIME IS 15:45 (3:45 PM)
LOCAL ONUNIT IN LOCAL MODE
CLOCK ONUNIT IS ON VIA CLOCK SCHEDULE
8 MODETEMPERATURE RESET IN EFFECT
COOL 1NUMBER OF STAGES IS 1
2 ALARMSTHERE ARE 2 ALARMS
3 MINS
The only function of this module is to allow
3 MINUTES REMAINING IN THE OFF-TO-ON
TIME DELAY
Pumpout
EXV UNITS — When the lead compressor in each circuit
is started or stopped, that circuit goes through a pumpout
cycle to purge the cooler and refrigerant suction lines of
refrigerant.
The pumpout cycle starts immediately upon starting the
lead compressor and continues until the saturatedsuctiontemperature is 10° F (5.6° C) below the saturated suction temperature at start-up, is 10° F (5.6° C) below the cooler leaving fluid temperature, or reaches a saturated suction temperature
of –15 F (–26 C). No pumpout is necessary if the saturated
suction temperature is below –15 F (–26 C). At this point,
the EXV starts to open and continues to open gradually to
provide a controlled start-up to prevent liquid flood-back to
the compressor.
At shutdown, the pumpout cycle continues until the saturated suction temperature for that circuit is 10° F (5.5° C)
below the saturated suction temperature when pumpout is
initiated, or saturated suction temperature reaches –15 F
(–26 C). At that point, the compressor shuts down and the
EXV continues to move until fully closed.
TXV UNITS — Pumpout is based on timed pumpout. On a
command for start-up, the lead compressor starts. After
10 seconds, the liquid line solenoid opens.At shutdown, the
liquid line solenoid closes, and the lead compressor continues to run for 10 seconds before stopping.
AUTOMATIC DISPLAY OPERATION/DEFAULT DISPLAY — This display automatically rotates as follows:
DOW — Day of Week
HH— Hour(s)
MM— Minute(s)
The default rotating display is displayed every 2 seconds
if there has been no manual input from the keypad for
10 minutes.
To return to automatic display, enterat any time.
KEYPAD OPERATING INSTRUCTIONS(Refer to
Table 9.)
1. White keys on left side of keypad are shown and operated in these instructions according to the following ex-
ample: keypad entrymeanspressthe, then
the white key marked.
2. The standard display uses abbreviations. Expanded information scrolls through the display wheneverkey
is pressed.
25
Page 26
Table 6 — Keypad and Display Module Usage
FUNCTION
KEYS
OPERATIVE
KEYS
STATUS — For displaying diagnostic codes and
current operating information about the machine.
HISTORY — For displaying run time, cycles and
previous alarms.
SERVICE — For entering specific unit configuration information.
TEST — For checking inputs and outputs for
proper operation.
SCHEDULE — For entering occupied/unoccupied
schedules for unit operation.
SET POINT — For entering operating set points
and day/time information.
EXPAND — For displaying a non-abbreviated expansion of the display.
CLEAR — For clearing the screen of all displays.
UP ARROW — For returning to previous display
position.
DOWN ARROW — For advancing to next display
position.
ENTER — For entering data.
USE
USE
Table 7 — Functions and Subfunctions
3. All functions are made up of a group of subfunctions. To
enter a subfunction, first press subfunction number desired. Then press the function key in which the subfunction resides. To move within that subfunction, press
theorarrow. For example, aenters
the Temperature Information subfunction.
4. At any time, anothersubfunctionmay be entered by pressing the subfunction number, then the function key.
5. Prior to startingunit, check leaving fluid setpoint for correct setting. Refer to Set Point Function section on
page 38.
6. Depending on system configuration, all displays may not
be shown. All displays are shown unless marked with the
following symbol:
†Must be configured.
For additional unit start-up procedures, see separate
Installation, Start-Up, and Service Instructions supplied
with unit.
Log Off
(Software)
Configuration
Configuration
Configuration
Run TimeSet Points
StartsReset
Alarm
History
—Date and
—Leaving Chiller
(Chiller Fluid)
Set Points
Demand Limit
Set Points
Time
Fluid Alert Limit
26
Page 27
Table 8 — Accessing Functions and Subfunctions
OPERATION
To access a function, press
subfunction no. and function
name key. Display shows subfunction group.
To move to other elements,
scroll up or down using arrow
keys. NOTE: These
displays do not show if
control is not configured
for reset.
When the last element in a
subfunction has been displayed,
the first element is repeated.
To move to next subfunction
it is not necessary to use
subfunction number. Press
function name key to advance display through all
subfunctions within a
function and then back
to the first.
To move to another function,
either depress function name
key for desired function
(display shows the first
subfunction),
Access a specific subfunction by using the subfunction number and the
function name key.
or
KEYPADDISPLAY
ENTRYRESPONSE
RESETRESET SETPOINTS
CRT1 xCOOL RESET AT 20 MA
CRT2N xCOOL RTEMP (NO RESET)
CRT2F xCOOL RTEMP (FULL RESET)
CRT2D xCOOL DEGREES RESET
RESETRESET SETPOINTS
CRT1 xCOOL RESET AT 20 MA
DEMANDDEMAND LIMIT SETPOINTS
TIME
SETPOINTUNIT SETPOINTS
X ALARMSTHERE ARE n ALARMS
STAGE
EXPANSION
CURRENT TIME AND DAY OF
WEEK
CAPACITY STAGING
INFORMATION
Table 9 — Keypad Directory
STATUS
SUBFUNCTIONKEYPAD ENTRYDISPLAYCOMMENT
1 AUTOMATIC DISPLAY
2 ALARMS/ALERTS
To toggle between inputs (Yes/No) Press:(no) or(yes)
3 MODES
Refer to Automatic Display Operation/Default Display section on page 25.
X ALARMSNumber of Tripped Alarms/Alerts
R S ALReset all Alarms/Alerts
ALARM* X
ALARM* X
ALARM* X
ALARM* X
ALARM* X
X MODESNumber of Modes in Effect
X MODE
X MODE
X MODE
}
Displays Tripped Alarms/Alerts
Displays Mode in Effect
}
X MODE
27
Page 28
Table 9 — Keypad Directory (cont)
STATUS (cont)
SUBFUNCTIONKEYPAD ENTRYDISPLAYCOMMENT
4 STAGE
5 SET POINT
STAGECapacity Staging Information
COOL XNumber of Requested Stages
CAPT XPercent of Total Capacity
CAPAXPercent Circuit A Total Capacity
CAPB XPercent Circuit B Total Capacity
AVAIL XPercent Available Capacity
AVA XPercent Circuit AAvailable Capacity
AV B XPercent Circuit B Available Capacity
LMT X†Demand Limit Set Point (percent)
CIRA XCircuit A Compressor Relay Status
CIRB XCircuit B Compressor Relay Status
SMZ XLoad/Unload Factor for Compressors
Factor = 1 Unloader Factor = 0.6
SETPOINTFluid Set Point Information
SET XSet Point (F)
MSP XModified Set Point = Set Point + Reset (F)
TW XActual Control Temperature (F)
TEMPSTemperature Information (F)
EWT XCooler Entering Fluid Temperature (F)
LWT XCooler Leaving Fluid Temperature (F)
SCTAXCircuit A Saturated Condenser Temperature (F)
SSTAXCircuit A Saturated Suction Temperature (F)
CTAXCompressorA1 Suction Temperature (F)
SHA XCircuit A Suction Superheat (F)
SCTB XCircuit B Saturated Condenser Temperature (F)
SSTB XCircuit B Saturated Suction Temperature (F)
CTB XCompressor B1 Suction Temperature (F)
SHB XCircuit B Suction Superheat (F)
SPC XSpace Temperature (F)
OAT XOutdoor-Air Temperature (F)
*Will read ALARM or ALERT as appropriate.
†Must be configured.
**If applicable.
††Not manually resettable.
NOTE: If metric option is selected under, temperature
expressed as Celsius and pressure will be expressed as kPa.
28
Page 29
Table 9 — Keypad Directory (cont)
STATUS (cont)
SUBFUNCTIONKEYPAD ENTRYDISPLAYCOMMENT
7 PRESSURE
8 ANALOG
9 INPUTS
PRESSURERefrigerant System Pressure (psig)
MM DD YYDate of Last Calibration
DPAXCircuit A Discharge Pressure (psig)
SPAXCircuit A Suction Pressure (psig)
XXXX XXXCircuit A Discharge/Suction (psig)
OPAXCircuit A Oil Pressure Differential (psig)
DPB XCircuit B Discharge Pressure (psig)
SPB XCircuit B Suction Pressure (psig)
XXXX XXXCircuit B Discharge/Suction (psig)
OPB XCircuit B Oil Pressure Differential (psig)
ANALOGStatus of Analog Inputs
REF XTransducer Supply Voltage (volts)
LMT X†Demand 4-20 mA Signal (mA)
RST X†Reset 4-20 mA Signal (mA)
SW INPUTStatus of Switch Inputs
SPW X†Dual Set Point Switch (open/closed)
††Not manually resettable.
NOTE: If metric option is selected under, temperature
expressed as Celsius and pressure will be expressed as kPa.
29
Page 30
Table 9 — Keypad Directory (cont)
STATUS (cont)
SUBFUNCTIONKEYPAD ENTRYDISPLAYCOMMENT
10 OUTPUTS (cont)
EXVB XEXVB Percent Open**
HGBA X†Hot Gas Bypass Relay Circuit A (on/off)**
HGBB X†Hot Gas Bypass Relay Circuit B (on/off)**
MMA X†MotormasterT A Output Percent**
MMB X†Motormaster B Output Percent**
TEST
To use Test function, LOCAL/ENABLE-STOP-CCN switch must be in STOP position. To operate a test, scroll to desired test.
Then, pressto start test. Pressto stop test.
SUBFUNCTIONKEYPAD ENTRYDISPLAYCOMMENT
1 OUTPUTS
OUTPUTSTest Outputs
8.8.8.8.8.8.8.8Display Check
ALMR XEnergize Alarm Relay K3 (on/off)
FRA1 XEnergize Fan Relay A1 K1 (on/off)
FRA2 XEnergize Fan Relay A2 K2 (on/off)
FRB1 XEnergize Fan Relay B1 K4 (on/off)
FRB2 XEnergize Fan Relay B2 K5 (on/off)
CHWP X†Energize Cooler Water Pump K6 (on/off)
LSVAXEnergize Liquid Line SolenoidA (on/off)**
LSVB XEnergize Liquid Line Solenoid B (on/off)**
EXVAXEnter Desired EXVA Position (percent)**
EXVB XEnter Desired EXVB Position (percent)**
HGBA X†Energize Hot Gas Bypass Relay A (on/off)**
HGBB X†Energize Hot Gas Bypass Relay B (on/off)**
MMA X†Enter Desired MotormasterA Output Signal (percent)**
MMB X†Enter Desired Motormaster B Output Signal (percent)**
To toggle between inputs (Yes/No) Press:(no) or(yes)
During compressor test, compressors start and run for
10 seconds. Compressor service valves and liquid line
valves must be open. Energize crankcase heaters 24hours
prior to performing compressor tests.
SUBFUNCTIONKEYPAD ENTRYDISPLAYCOMMENT
2 COMPRESSORS AND
UNLOADERS
COMPCompressor and Unloader Test
CPA1 XTest Compressor A1 (on/off)
CPA2 X†Test Compressor A2 (on/off)**
XDR CALTransducer Calibration
CDPAXCircuit A Discharge Pressure (psig)
CSPAXCircuit A Suction Pressure (psig)
COPAXCircuit A Oil Pressure (psig)
CDPB XCircuit B Discharge Pressure (psig)
CSPB XCircuit B Suction Pressure (psig)
COPB XCircuit B Oil Pressure (psig)
SCHEDULE
The Schedule function keyis used to configure the occupancy schedule. The clock select subfunction can be used for
unoccupied shutdown or unoccupied setback depending on the cooling set point control configuration. The Schedule function
described is for clock 1, which is the internal clock. Password required for all subfunctions except override.
SUBFUNCTIONKEYPAD ENTRYDISPLAYCOMMENT
1 OVERRIDE
For example, to extend current occupied mode for 3 hrs, press:
PERIOD 1Period 1 Time Schedule
OCC HH.MMOccupied Time
UNO HH.MMUnoccupied Time
MON XMonday Flag (yes/no)
TUE XTuesday Flag (yes/no)
WED XWednesday Flag (yes/no)
THU XThursday Flag (yes/no)
††Not manually resettable.
NOTE: If metric option is selected under, temperature
expressed as Celsius and pressure will be expressed as kPa.
31
Page 32
Table 9 — Keypad Directory (cont)
SCHEDULE (cont)
SUBFUNCTIONKEYPAD ENTRYDISPLAYCOMMENT
3 PERIOD 1 (cont)
To toggle between inputs (Yes/No) Press:(no) or(yes)
4 PERIOD 2
5 PERIOD 3 ... 9 PERIOD 7
10 PERIOD 8
11 HOLIDAYS
New = Unassigned Holiday Date
For example: To enter July 4th holiday press: 07.04.01. Display shows Jul 04. For further information on the Schedule function and its
operation, refer to Schedule Function section on page 44.
...
FRI XFriday Flag (yes/no)
SAT XSaturday Flag (yes/no)
SUN XSunday Flag (yes/no)
HOL XHoliday Flag (yes/no)
PERIOD 2Period 2 Time Schedule
PERIOD 3 ...
PERIOD 7
PERIOD 8Period 8 Time Schedule
HOLIDAYSDefine Calendar Holidays
DAT MM.DDHoliday Date 1
DAT MM.DD.NNHoliday Date 30
Period 3 ... Period 7 Time Schedule
SERVICE
To view and modify configurations, the password must be entered under the log on subfunction.
SUBFUNCTIONKEYPAD ENTRYDISPLAYCOMMENT
1 LOG ON AND LOG OFF
At this time, configurations may be modified. When finished viewing and/or modifying configurations, log out as follows:
2 VERSION
The next 3 subfunctions provide the ability to modify configurations. Refer to separate Installation, Start-Up, and Service Instructions
supplied with unit for further information on changing configurations.
To change a configuration, enter the new configuration and presswhile on the correct configuration.
3 FACTORY
CONFIGURATION
PASSWORDEnter Password/Disable Password Protection
LOGGEDONLogged On
FLD CFGAdjustable Field Configuration
ENO XCCN Element Address
BUS XCCN Bus Number
BAUD XCCN Baud Rate
FLUID XCooler Fluid Select (water/medium brine)
UNITS XDisplay Unit Select (English/Metric)
DELAY XDelay at Power Up (minutes)
NULA XNo. Circuit A Unloaders
NULB XNo. Circuit B Unloaders
HGB XHot Gas Bypass Select (used, not used)
SEQT XLoading Sequence Select (equal circuit, staged circuit)
LEADT XLead/Lag Sequence Type
OPS XOil Pressure Switch Select (enable/disable)
HEADT X
Head Pressure Control Type
(none, air cooled, water cooled)
MM XMotormasterT Select
CSPTYP XCooling Set Point Control Select
CRTYP XCooling Reset Control Select
ERTYP XExternal Reset Sensor Select
OATSEL XOutdoor-Air Sensor Select
LSTYP XDemand Limit Control Select
RAMP XRamp Load Select (enable, disable)
LOCK XCooler Pump Interlock Select
CPC XCooler Pump Control Select
REMA XRemote Alarm Option Select (yes/no)
ALRST XAllow Local/Stop/CCN Reset of Alarms (yes/no)
To toggle between inputs (Yes/No) Press:(no) or(yes)
5 SERVICE
CONFIGURATION
SRV CFGService Configurations
XXXXXXXXConfiguration Code 8
XXXXXXXXConfiguration Code 9
REFRIG XRefrigerant
TDTYP XPressure Transducer Select
OPS XOil Transducer Set Point (psig)
LPS XLow Pressure Set Point (psig)
FANTYP XFan Staging Select
SH XEXV Superheat Set Point (F)
MOP XEXV MOP Set Point (F)
ZM XZ Multiplier
NOTE: If metric option is selected under, temperature
expressed as Celsius and pressure will be expressed as kPa.
Page 34
Table 9 — Keypad Directory (cont)
HISTORY
SUBFUNCTIONKEYPAD ENTRYDISPLAYCOMMENT
1 RUN TIME
2 STARTS
RUN TIMERun Time Information
HR XTotal Hrs Unit Has a Comp Operating
HRA XCircuit A Run Time
HRB XCircuit B Run Time
HA1 XCircuit A, Comp A1 Operating Hours
HA2 XCircuit A, Comp A2 Operating Hours**
HA3 XCircuit A, Comp A3 Operating Hours**
HA4 XCircuit A, Comp A4 Operating Hours**
HB1 XCircuit B, Comp B1 Operating Hours
HB2 XCircuit B, Comp B2 Operating Hours**
HB3 XCircuit B, Comp B3 Operating Hours**
HB4 XCircuit B, Comp B4 Operating Hours**
STARTSStarts Information
CY XCycles from Stage 0 to Stage 1
CYAXCircuit A Starts
CYB XCircuit B Starts
CA1 XCircuit A, Comp A1 Starts
CA2 XCircuit A, Comp A2 Starts**
CA3 XCircuit A, Comp A3 Starts**
CA4 XCircuit A, Comp A4 Starts**
CB1 XCircuit B, Comp B1 Starts
CB2 XCircuit B, Comp B2 Starts**
CB3 XCircuit B, Comp B3 Starts**
CB4 XCircuit B, Comp B4 Starts**
ALRMHISTLast 10 Alarms/Alerts
ALARM X
ALARM X
ALARM X
ALARM X
ALARM X
ALARM X
ALARM X
ALARM X
ALARM X
ALARM X
}
*Will read ALARM or ALERT as appropriate.
†Must be configured.
**If applicable.
††Not manually resettable.
NOTE: If metric option is selected under, temperature
expressed as Celsius and pressure will be expressed as kPa.
Alarm/Alert Description
34
Page 35
Table 9 — Keypad Directory (cont)
SET POINT
To read a set point, go to proper subfunction and read desired set point. To change a set point, enter new set point value, then press.
LOCAL/ENABLE-STOP-CCN switch must be in LOCAL/ENABLE or STOP position.
SUBFUNCTIONKEYPAD ENTRYDISPLAYCOMMENT
1 SET POINTS
2 RESET SET POINTS
3 DEMAND SET POINTS
SET POINTUnit Set Point
CSP1 XChiller Fluid Set Point 1 (F)
CSP2 XChiller Fluid Set Point 2 (F)
HSPAXHead Pressure Set Point Circuit A (F)
HSPB XHead Pressure Set Point Circuit B (F)
CRAMP XCooling Ramp Loading Rate (F)
RESETReset Set Points
CRT1 XCooling reset at 20 mA (F)
CRT2N XReference Temperature at No Reset (F)
CRT2F XReference Temperature at Full Reset (F)
CRT2D XTotal Degrees of Reset (F)
CRT3N XChiller Fluid DT at No Reset (F)
CRT3F XChiller Fluid DT at Full Reset (F)
CRT3D XTotal Degrees of Reset (F)
DEMANDDemand Set Points
DLS1 X†Demand Switch 1 Set Point (percent)
DLS2 X†Demand Switch 2 Set Point (percent)
DL20 XDemand Limit at 20 mA (percent)
DLGN XLoadshed Group Number
LSDD XLoadshed Demand (percent)
TIME XMinimum Loadshed Time (minutes)
DATE.TIMEDate, Time and Day of Week
DOW.HR.MINDay1=Mon,2=Tues...7=Sun
Hours are displayed in 24-hr time. Decimal point serves as colon.
MM.DD.YRMonth.Day.Year. When entering date, enter a decimal
point between entries. Each entry must be two numbers.
LMT XLeaving Chiller Fluid Alert Limit (F)
*Will read ALARM or ALERT as appropriate.
†Must be configured.
**If applicable.
††Not manually resettable.
NOTE: If metric option is selected under, temperature
expressed as Celsius and pressure will be expressed as kPa.
35
Page 36
STATUS FUNCTION — This function shows the rotating
display, current status of alarm and alert (diagnostic) codes,
capacity stages, operating modes, chilled water set point, all
measured system temperatures and pressures, superheat values, pressure switch positions, analog inputs, and switch inputs. These subfunctions are defined on pages 36 and 37.
(Rotating Display)
To reset alarms/alerts using keypad and display module:
KEYPAD
ENTRY
DISPLAY
RESPONSE
RSAL DSB
RSAL ENB
COMMENTS
Reset all alarms/alerts
function disabled
Reset all alarms/alerts
function enabled
(Alarms/Alerts) — Alarms and alerts are messages
that one or more faults have been detected. Each fault is assigned a code number which is reported with the alarm or
alert. See Table 10 for code definitions. The codes indicate
failures that cause the unit toshut down, terminate an option
(such as reset) or result in the use of a default value as set
point.
Up to 10 codes can be stored at once. To view them
in sequence, pressto enter the alarm/alert displays and then pressto move to the individual displays. Pressafter a code has been displayed. The mean-
ing of the code scrolls across the screen. See Example 1.
Example 1 — Reading Alarm Codes
KEYPADDISPLAY
ENTRYRESPONSE
TUE 12:45
LOCAL ON
CLOCK ON
13 MODE
8 MODE
COOL 1
2 ALARMS
3 MINS
Keypad has not been used for
at least 10 minutes. Alternating
summary display appears on
screen
Explanation of alarm/alert code
Second alarm/alert code.
Cooler freeze protection
Explanation of alarm/alert code
COMMENTS
When a diagnostic (alarm or alert) code is stored in the
display and themachine automatically resets, the code is deleted. Codes for safeties which do not automatically reset
are not deleted until the problem is corrected and either the
machine is switched to STOP position, then back to LOCAL/
ENABLE or CCN position, or by using the keypad and display module.
(Modes) — The operating mode codes are displayed to indicate the operating status of the unit at a given
time. See Table 10.
To enter the MODES subfunction, pressand
press thekey to determine if more than one mode applies. See Example 2 to read current mode with expansion.
Example 2 — Reading Current Operating Modes
KEYPADDISPLAY
ENTRYRESPONSE
TUE 15:45
LOCAL ON
CLOCK ON
8 MODE
COOL 1
0 ALARMS
3 MINS
2 MODESThere are 2 modes currently in effect
LOCAL ONUnit is on by chiller on/off switch
8 MODETemperature reset is in effect
Keypad has not been used for at
least 10 minutes. Rotating summary
display appears on screen
COMMENTS
(Stage) — This subfunction displays the capac-
ity stage number. See Tables 4A-4C for compressor loading
sequence. To enter the STAGE subfunction, press
and press theto display the stage number.
Continue pressingfor the following information:
• Number of requested stages.
• Percent of total unit capacity being utilized.
• Percent of each circuit capacity being utilized.
• Percent of total capacity available.
• Percent of capacity available in each circuit.
• Demand limit set point in effect (can be any value be-
tween 0% and 100%).
• Status of each compressor relay. When a compressor is
on, the number of that compressor is displayed. If a compressor is off,a0isdisplayed. For example: In a given
circuit, if compressors 1and 3 are running, and2 and 4 are
not running, 0301 is displayed for that circuit.
• Load/Unload factor for compressors. This factor is an in-
dication of when a step of capacity is added or subtracted.
Its value can range from slightly less than –1.0 to slightly
more than +1.0. When load/unload factor reaches +1.0, a
compressor is added.When the load/unload factorreaches
–1.0, a compressor is subtracted. If compressor unloaders
are used, at –.6 a compressor is unloaded and at +.6, a
compressor is loaded up.
36
Page 37
Table 10 — Operational and Mode Display Codes
The operating modes are displayed by name or code number, to indicate the operating status of the unit at a given
time. The modes are:
CODEDESCRIPTION
Unit isoff.LOCAL/ENABLE-STOP-CCN switch is in
LOCAL OFF
CCN OFF
CLOCK OFF
LOCAL ON
CCN ON
CLOCK ON
MODE 7
MODE 8
MODE 9
MODE 10
MODE 11Not applicable.
MODE 12
MODE 13
MODE 14
MODE 15Water System Manager is controlling the chiller.
MODE 16Slow change override is in effect.
MODE 17X minute off-to-on delay is in effect.
MODE 18Low suction superheat protection is in effect.
CCN — Carrier Comfort Network
OFFposition,or LOCAL/ENABLE-STOP-CCNswitch
may be in LOCAL position with external ON/OFF
switch in OFF position.
Unit is off due to CCN network command. LOCAL/
ENABLE-STOP-CCN switch is in CCN position.
Unit is off due to internal clock schedule. LOCAL/
ENABLE-STOP-CCN switch is in LOCAL position.
Unit ison.LOCAL/ENABLE-STOP-CCN switch is in
LOCALposition.Ifexternal ON/OFF switch is used,
it will be in ON position.
Unit is on due to CCN command. LOCAL/ENABLESTOP-CCN switch is in CCN position.
Unit is on due to internal clock schedule or occupied override function. LOCAL/ENABLE-STOPCCN switch is in LOCAL/ENABLE position.
Dual set point is in effect. In this mode, unit continues to run in unoccupied condition,butleaving fluid
set point is automatically increased to ahigherlevel
(CSP2 set point is in SET function).
Temperature reset is in effect. In this mode, unit is
using temperature reset to adjust leaving fluid set
point upward, and unitis currently controlling to the
modifiedsetpoint.Theset pointcanbe modifiedbased
onreturnfluid, outdoor-air temperature,or space temperature.
Demand limit is in effect. This indicates that capacity ofunitis being limited by demandlimitcontrol
option. Because of this limitation, unit may not
be able to produce the desired leaving fluid
temperature.
Flotronic™SystemManager (FSM) is controllingthe
chiller.
Rampload(pulldown) limitingisin effect. Inthis mode,
therateat which leavingfluidtemperature is dropped
is limited to a predetermined value to prevent compressor overloading. See CRAMP set point in the
SET function in Table 9. The pulldown limit can be
modified, if desired, to any rate from .2 F to 2 F
(.1° to 1° C)/minute.
Timedoverrideisineffect.This isa1to4hourtemporary override of the programmed schedule, forcing unit to occupied mode. Override can be implemented with unit under LOCAL/ENABLE or CCN
control. Override expires after each use.
Lowcoolersuction protection isin effect. Inthismode,
circuit capacity is not allowed to increase if cooler
saturated suction temperature is 20° F (11° C) for
fluid or30°F(16° C) for brine ormorebelowleaving
fluid temperature, and saturated suction temperature is less than 32 F (0° C). If these conditions persistbeyond10 minutes, circuit isshutdown and fault
code 44 or 45 is displayed.
(Set Point) — This subfunction displays leaving
fluid temperature and leaving chilled fluid set point. If unit
is programmed for dual set point, the chilled fluid set point
currently in effect (either occupied or unoccupied) is
displayed. If reset is in effect, the unit operates to the modified chilled fluid set point. This means the leaving fluid temperature may not equal the chilled fluid set point. The
modified chilled fluid set point can also be displayed in the
Status function. To enter the set point subfunction,
pressand pressto display the set point followed by the modified leaving chilled fluid set point and ac-
tual control temperature.
(Temperature) — The temperature subfunction dis-
plays the readings at temperature sensing thermistors.
To read a temperature, enter, then scroll to de-
sired temperature using thekey. See Table 9 for the
order of readouts. This subfunction also displays the satu-
rated refrigerant temperatures corresponding to the suction
and discharge pressures measured by the compressor
transducers.
(Pressure) — This subfunction displays suction,
discharge, and net oil pressure at lead compressor of each
circuit of unit.
(Analog Inputs) — This subfunction displays
analog inputs, if any. Press, then press. The
transducer supply voltage, 4-20 mA reset signal can be dis-
played. This is useful for problem diagnosis prior to using
the test function.
(Discrete Inputs) — This subfunction displays sta-
tus (open/closed) of discrete input switch where applicable.
Status of dual set point switch and demand limit switches 1
and 2 can be displayed. This is useful for problem diagnosis
prior to using the test function.
(Outputs) — This function displays on/off sta-
tus of alarm relay, all fan relays, and chilled water pump
relay. It also displays on/off status of compressor unloaders
(if used). The position of each EXV(in percent open) can be
displayed.
TEST FUNCTION — The test function operates the diagnostic program. To initiate test function, the LOCAL/
ENABLE-STOP-CCN switch must be in STOP position.
To reach a particular test, press its subfunction number,
then scroll to desired test by pressing. Pressto
start a test. Pressororto terminate or exit a
test. Pressing thekey after a test has started advances
system to next test, whether current test is operating or has
timed out. Once in the next step, you may start
test by pressingor advance past it by pressing.
While the unit is in test, you may leave test function and
access another display or function by pressing appropriate
keys. However, a component that is operating when another function is accessed remains operating. You must
re-enter test function and pressto shut down the component. Components with a timed operating limit time out
normally even if another function is accessed.
37
Page 38
Keypad entryallows the operator to make the
following checks by using:
• LID display check. Proper display is 8.8.8.8.8.8.8.8.
• Operation of alarm relay.
• Operation of condenser fans.
• Operation of chilled fluid pump.
• Operation of liquid line solenoids.
• Operation of the hot gas bypass relays.
• Operation of EXVs. To drive EXV fully open, enter
(100% open). To drive EXV fully closed, en-
ter(0% open).
• Operation of each remote alarm.
• Operation of Motormastert signals.
Keypad entryaccesses the compressor and
compressor unloader operational tests.
During compressor operational tests, compressor starts
and runs for 10 seconds. Compressorservicevalvesmust
be open. Energize crankcase heaters 24 hours prior to
performing compressor tests.
Since test function checks only certain outputs, it is good
practice to also check all inputs and outputs accessible
through the status function. These are located at,
, and(see Table 9). If keypad is not used
for 10 minutes, unit automatically leaves test function and
resumes rotating display. See Example 3.
Example 3 — Using Test Function
KEYPADDISPLAY
ENTRY RESPONSE
COMPFactory/field test of compressors
CPA1 OFF Circuit A, Compressor 1A test
CPA1 ONPressing ENTR starts the test:
CPA1 OFF If the test is allowed to time out (10 secCPA 2 OFF Pressingthedown arrow keyadvances the
NOTE: Once a compressor has been run using thefunction,
it is not allowed to run again for 30 seconds.
subfunction of test function
when the compressor should be running
the display shows CPA1 on
onds) the display will show CPA1 off
system to Circuit A, compressor 2 test
COMMENTS
accesses the transducer calibration subfunction.
All transducers must be calibrated in order for the unit to
operate. Refer to Pressure Transducers section on page 60
for calibration procedure.
HISTORY FUNCTION — Pressinganddisplays total unit run time, total run time for each circuit, and
total run time for each compressor.
Pressinganddisplays total unit starts, the
total starts for each circuit, and total starts for each compressor.Pressinganddisplays the last 10alarms
along with a description of each alarm.
SET POINT FUNCTION — Set points are entered through
the keypad. Set points can be changed within the upper and
lower limits, which are fixed. The ranges are listed below.
Chilled Fluid Set Point
Water:
38 to 86 F (3.3 to 30 C)
Medium Brine:
14 to 86 F (–10 to 30 C)
Pulldown Set Point
0.2 to 2.0 F (0.11 to 1.1 C)/min.
Reset Set Points
Maximum Reset Range:
–30° to 30° F (–17° to 17° C)
External Temperature Reset –40 to 240 F
Maximum Demand Limit 4 to 20 mA
Minimum Demand Limit 4 to 20 mA
Loadshed Demand Delta: 0 to 60%
Maximum Loadshed Time: 0 to 120 min.
Set points are grouped in subfunctions as follows:
Subfunction displays chiller fluid set points.
a. The first value shown is the occupied chilled fluid set
point.
b. The next value displayed depends on how the sched-
ule function has been programmed. (See pages 44-
47.) If dual set point has been selected, the next set
point afterhas been pressed is the second chilled
fluid set point. If single set point or inactive schedule has been selected in the schedule function,
then whenis pressed, the display shows the
head pressure set points, one for each circuit. These
are utilized only if the set point controlled method of
head pressure control is selected in.
c. The final value displayed when theis pressed
is the cooling ramp loading rate. This is the maximum
rate at which the leaving chilled fluid is allowed to
drop, and can be field set from 0.2 to 2.0 F (.11° to
1.1° C)/minute. This value is not displayed unless the
function is enabled (see Adjustable Field Configurations on page 44).
Reading and Changing Set Points — Example 4 shows how
to read and change thechilled fluid set point. Other setpoints
can be changed by following the same procedure. Refer to
Table 9 for the sequence of display of set points in each subfunction.
38
Page 39
Example 4 — Reading and Changing
Chilled Fluid Set Point
KEYPADDISPLAY
ENTRYRESPONSE
SET POINTSystem set points
CSP1 44.0Present occupied chilled fluid
CSP1 42.0
CSP2 44.0
CSP2 50.0
RESETDisplays the maximum reset
set point is 44.0 F
Press the.
Display shows new occupied
chilled fluid set point is 42.0 F
Present unoccupied chilled fluid
set point is 44.0 F
Press the. Display
shows new unoccupied chilled
fluid set point is 50.0 F
set point. The minimum and
maximum reference reset
set points can also be displayed.
These set points are not
accessible when reset type has
been configured for NONE in
the service function.
COMMENTS
Subfunction displays temperature reset set points.
Temperature Reset Based on Return Fluid Temperature —
The control system is capableof providing leaving fluid temperature reset based onreturn fluid temperature. Becausethe
temperature difference between leaving and return temperature is a measure of the building load, return fluid temperature reset is essentially an averagebuildingloadreset method.
Under normal operation, the chiller maintains a constant
leaving fluid temperature approximately equal tochilledfluid
set point. As building load drops from 100% down to 0%,
entering cooler fluid temperature dropsin proportion to load.
Thus, temperature drop across the cooler drops from a typical 10 F (5.5 C) at full load to a theoretical 0° F (0° C) at no
load. See Fig. 5.
At partial load, leaving chilled fluid temperature may be
lower than required. If this is allowed to increase (reset), the
efficiency of the chiller increases. Amount of reset can be
defined as a function of cooler temperature drop, as shown
in Fig. 5. This is a simple linear function that requires
3 pieces of input data for the set function that will vary depending on measurement method used as follows (see
Table 11):
NOTE: Reset set points are not accessible unless the reset
function is enabled first. This is done as a field
configuration. Select one of the 4 choices for type of reset:
Return Fluid Reset, External Temperature Reset, 4-20 mA
External Signal Reset, or 4-20 mA Internal Signal Reset.
If dual set point control is enabled (see Field Wiring section on page 69), the amount ofreset is applied to whichever
set point is in effect at the time.
Examples 5A-5C demonstrate how to activate reset. Example 6 demonstrates how to change the type of reset. Assume that reset is to be based on return fluid temperature,
the desired reset range is to be 0° to 10° F (0° to 5.5° C) and
full load is a 10° F (5.5° C) drop across the cooler. See
Fig. 5.
Activating reset based on external temperature or
4-20 mA signal is done the same way, except the reference
set point range is –40° to 240° F (–40° to 115° C), or 4 to
20 mA depending on which method was selected at the field
configuration step.
Example 5A — External Reset
In this example, the unit set point is reset from full load
at 90 F (32 C) to a maximum reset value of 10 F (5.5 C) at
20 F (–6.7 C) outdoor ambient.
NOTE: All temperatures given in this example are in F.
KEYPADDISPLAY
ENTRYRESPONSE
FLD CFG
CRTYP 0Scroll past to reset type
CRTYP 2External reset selected
ERTYP 0
ERTYP 1OAT selected
RESET
CRT2N 0
CRT2N 90
CRT2F 0
CRT2F 20
CRT2D 0Maximum reset is 0
CRT2D 10Maximum reset is 10
COMMENTS
Scroll past to space
thermistor sensor selected
Temperature for no
reset is 0
Temperature for no
reset is 90
Temperature for maximum
reset is 0
Temperature for maximum
reset is 20
INPUT DATA DESCRIPTION
Maximum Reset Amount — Allowable range for
maximum amount which LWT is to be reset.
Maximum Reset Reference — Temperature at
which maximum reset occurs.
Minimum Reset Reference — Temperature at
which no reset occurs.
LEGEND
OAT — Outdoor-Air Temperature
LWT — Leaving Fluid Temperature
In this example, the unit set point is reset from full load
at 4 mA to a maximum reset value of 10 F (5.5 C) at
20 mA. Internally powered 4 to 20 mAoption is used in this
example.
NOTE: To use externally powered reset, when CRTYP
appears, pressso CRTYP 4 appears in the
display.The remainder of theinformation in the fol-
lowing example applies to either type of reset.
KEYPAD
ENTRY
DISPLAY
RESPONSE
FLD CFG
CRTYP 0Scroll past to reset type
CRTYP 1
RESET
CRT1 0Reset at 20 mA is 0
CRT1 10Reset at 20 mA is 10
COMMENTS
Internally powered reset
selected
Example 5C — Using Return Fluid
Temperature Reset
KEYPADDISPLAY
ENTRYRESPONSE
FLD CFG
CSPTYP XScroll past single/dual
CRTYP 0
CRTYP 3
RESETReset set points
COMMENTS
Field configuration
subfunction of
service function
Display shows no reset
type has been selected
Return fluid temperature
is selected and activated
Temperature Reset Based on External Temperature — If desired, temperature reset can be based on an external temperature, such as space or outdoor-air temperature. This requires a thermistor (T10, Part No. 30GB660002) located in
the space or outdoor air and wired to terminals as follows
(also see Field Wiring section on page 69 and Fig. 6):
4 in/4 out Module — J7-15 and J7-16.
At the field configuration step, enter set points as de-
scribed in Examples 5A-5C on pages 39 and 40. Then
select external temperature reset by enteringwhen
CRTYP 0 appears. See Fig. 7.
Temperature Reset Based on 4-20 mA Signal— If desired,
temperature reset can be based on a 4-20 mA signal. For
proper connections, refer to Field Wiring section on
page 69 and Fig. 8.
At the field configuration step, select 4-20 mA reset by
entering(internally powered) or(externally powered) when CRTYP 0 appears. Then enter set points as de-
scribed previously in Examples 5A-C. See Fig. 8.
Subfunction displays demand limit set points.
Demand Limit, 2-Stage Switch Control — This control has
been designed to accept demand limit signals from a building load shedding control. The demand limit function provides for 2 capacity steps. The keypad is used to set the 2
demand limit set points, which range from 100 to 0% of capacity. Capacity steps are controlled by 2 field-supplied relay contacts connected to the designated chiller terminals.
(See Field Wiring section on page 69 and Fig. 7.)
Fig. 5 — Cooling Return Fluid Reset
40
Page 41
Fig. 6 — Cooling External Temperature Reset
LEGEND
COMM — Communications Bus
PWR— Power
SW— Switch
NOTE: Forspecificconnection points,
see Fig. 25 - 29.
Fig.7—4IN/4 OUT Options Module Wiring for Reset, Demand Limit, and Dual Set Point
41
Page 42
Fig. 8 — 4-20 mA Cooling Temperature Reset
Example 6 — Changing Reset Type
To change type of reset, first log on as shown in
Table 12. Also refer to Set Point Function section, page 38,
for information on entering reset set points using reset
feature.
KEYPADDISPLAY
ENTRYRESPONSE
FLD CFG
CSPTYP 0
CRTYP 0
CRTYP 1
CRTYP 2
CRTYP 3
CRTYP 4
CRTYP 0Reset is deactivated
COMMENTS
Field configuration
subfunction of
service function
Scroll past single cooling
set point
No reset has been
selected
Internally powered 4-20 mA
signal reset is selected
Space or outdoor-air
temperature reset is
selected
Return fluid temperature
reset is selected
Externally powered 4-20 mA
signal reset is selected
To use Demand Limit, first enable loadshed, then enter
demand limit set points. See Example 7A. Closing the first
stage demand limit contact putsuniton the first demand limit
level, that is, the unit does not exceed the percentage of capacity entered as demand limit stage 1. Closing contacts on
second-stage demand limit relay prevents unit from exceeding capacity entered as demand limit stage 2. The demand
limit stage that is set to the lowest demand takes priority if
both demand limit inputs are closed.
The demand limit function must be enabled in order to
function and may be turned off when its operation is not desired. The demand limit relays can, in off condition, remain
connected without affecting machine operation.
Table 12 — Service Functions
To view and modify configurations, the password must be
entered under the log on subfunction.
SUB-KEYPAD
FUNCTIONENTRY
1 Log On
DISPLAYCOMMENT
PASSWORD
LOGGEDON Logged On
Enter Password/
Disable Password
NOTE: Configurations may be modified at this time. When
finished viewing and/or modifyingconfigurations, log out as
follows:
LOGGEDON —
Disable Password
Protection
Logged Off/
Enable Password
Protection
Software
Information
Version No.
of Software
2 Version
LOG OFF
EXIT LOG
VERSION
XXXXXXXX
Demand Limit, 4 to 20 mA Signal — The controls can also
accepta4to20mAsignal for load shedding. Input for the
signal are terminals shown below:
Externally powered
Positive lead to J7-5 - 4 In/4 Out Module
Negative lead to J7-6 - 4 In/4 Out Module
Internally powered
Positive lead to J7-6 - 4 In/4 Out Module
Negative lead to J7-7 - 4 In/4 Out Module
See Field Wiring section on page 69 and Fig. 7.
42
Page 43
At field configuration step, select 4 to 20 mA loadshed
by entering(internally powered) or(externally powered) when the LSTYP 0 display appears. See Example 7B.
Then enter set points as follows. In this example, set points
are coordinates of the demand limit curve shown in Fig. 9.
Example 7A — Using Demand Limit
(First Log On as Shown in Table 12)
KEYPADDISPLAY
ENTRYRESPONSE
FLD CFG
LSTYP 0Loadshed is not enabled
LSTYP 1
DEMAND
DLS1 80
DLS1 60Loadshed reset to 60%
DLS2 50
DLS2 40Loadshed 2 reset to 40%
COMMENTS
Field configuration subfunction of service function
Loadshed is now enabled
for 2-stage switch control
Demand Limit set points
subfunction of set point
function
Loadshed 1 currently set
at 80%
Loadshed 2 currently set
at 50%
To Disable Demand Limit:
KEYPADDISPLAY
ENTRYRESPONSE
FLD CFG
ERTYP 0
LSTYP 1
LSTYP 0Loadshed is now disabled
NOTES:
1. Select 2 for internally powered 4 to 20 mA signal load limiting.
2. Select 3 for Carrier Comfort Network loadshed.
3. Select 4 for externally powered 4 to 20 mA signal load limiting.
COMMENTS
Field configuration subfunction of service function
Scroll past other elements
in the subfunction
Loadshed is enabled for
2-stage switch control
Example 7B — Using Demand Limit (4-20 mA)
(First Log On As Shown in Table 12)
the loadshed demand delta, which defines the percent of the
load to be removed when a loadshed command is in effect.
The third set point is maximum loadshed time, which defines the maximum length of time that a loadshed condition
is allowed to exist. The allowable range for this entry is zero
to 120 minutes.
Subfunction displays date, time, and dayofthe week.
Reading and ChangingTime Display — Time is entered and
displayed in 24-hour time. The day of the week is entered as
a number.
1 = Mon, 2 = Tue, 7 = Sun, etc.
Key is used as the colon when entering time. See
Example 8.
subfunction accesses the leaving chillerfluid alert
limit (LMT) option. Thevalue to be enteredhere is the number of degrees above the control set point at which an alert
should be generated. For example, if the control set point is
44 F,and an alert isdesired (alert 70) if the fluid temperature
reaches 50 F, then enter 6 for this set point. The allowable
range for this entry is between 2 and 30 (F).
SERVICE FUNCTION — This function allows the technician to view and input configuration data. Factory configuration data, field configuration data, and service configuration data may be viewed or entered through the keypad and
display module. See Table 9 for a complete listing of configurable items. Whenever a processor module is replaced in
the field, the complete list of configuration codes must be
entered.
Logging On/Logging Off — The service function is password protected. Therefore, to gain entry to this function,
this password must be entered. Pressing
allows the technician to view, change, or enter configuration
codes. To log off, perform the following keystrokes:
. The service functionis once again password
protected.
Software Information —displays the version
number of the software that resides in the processor
module. Theandsubfunctions are summa-
rized in Table 12.
KEYPADDISPLAY
ENTRYRESPONSE
FLD CFG
ERTYP 0
LSTYP 0Loadshed is not enabled
LSTYP 2
DEMANDDemand Limit set points
DL20 100Maximum demand limit is 100%
DL20 90Maximum demand limit is 90%
Field configuration subfunction
of service function
Scroll past other elements in
the subfunction
Loadshed is now enabled
for 4-20 mA internally-powered
signal control
COMMENTS
Scrolling past the 4 to 20mAdemand limit setpointbrings
up the loadshed set points. The loadshed feature is activated
by a redline alert and loadshed commands from the CCN
loadshed option. The first set point is the group number, established by the CCN system designer. The second option is
43
Example 8 — Setting Time of Day and
Day of Week
KEYPADDISPLAY
ENTRYRESPONSE
TIME
MON 16.00
TUE 13.05
JAN 01 90
APR 15 90
COMMENTS
Time display subfunction of set point
function
Current setting is
Monday, 4:00 p.m.
New setting of
Tuesday, 1:05 p.m.
is entered
and displayed
Current date is
Jan. 1, 1990
New setting
April 15, 1990
is entered
and displayed
Page 44
Fig. 9 — 4-20 mA Demand Limiting
Factory Configuration Codes —allows entry into
the factory configuration subfunction. Under this subfunc-
tion, there are 7 groupsof configuration codes that are downloaded at the factory. Each group is made up of 8 digits. If
processor module is replaced in the field, these 7 groups of
configuration codes must be entered through the keypad
and display module. Factory configuration codes (groups 1
through 7) that apply to the particular Flotronic™ II chiller
being serviced are found on a label diagram located inside
the control box cover. See Table13 for a summary of factory
configuration subfunction keystrokes.
Adjustable Field Configurations — After logging on, press
to enter subfunction. The subfunction allows operation of the chiller to be customized to meet the particular
needs of the application. The chiller comes from the factory
preconfigured to meet the needs of most applications. Each
item should be checked to determine which configuration
alternative best meets the needs of a particular application.
See Table 14 for factory loaded configuration codes and alternative configurations.
If processor module is replaced, the replacement module
is preloaded with factory default configuration codes. Each
configuration code must be checked and, if necessary, reconfigured to meet needsof the application. See Table 14 for
pre-loaded service replacement configuration codes.
Service Configuration Codes — Pressto enter the
service configuration subfunction. The first 2 itemsunder this
subfunction are 2 groups (8 digits each) ofconfigurationcodes
that are downloaded at the factory. If processor module is
replaced in the field, the 2groupsof configuration codes must
be entered through the keypad and display module. The
2 groups of configuration codes (groups 8 and 9) that apply
to the unit being serviced can be found on a label diagram
inside the control box cover. See Table 13 for keystroke information to enter configuration codes 8 and 9. The remaining items in this subfunction are read-only data provided to
assist in service evaluations.
SCHEDULE FUNCTION — This function provides ameans
to automatically switch chiller from an occupied mode to an
unoccupied mode. When using schedule function, chilled fluid
pump relay must be used to switch chilled fluid pump on
and off. Connections for chilled fluid pump relay are: TB3-3
and TB3-4. The chilled fluid pump relay starts chilled fluid
pump but compressors do not run until remote chilled fluid
pump interlock contacts are between TB6-1 and TB6-2 are
closed and leaving chilled fluid temperature is abovesetpoint.
If a remote chilled fluid pump interlock is not used, the first
compressor starts (upon a call for cooling) approximately
one minute after chilled fluid pump is turned on.
The unit can be programmedfor inactive, single set point,
or dual set point operation.
When unit is configured for inactive, chilled fluid pump
relay remains energized continuously but is not used since
chiller is usually controlled by remote chilled fluid pump interlock contacts.
When unit is configured for single set point operation, chilled
fluid pump relay is energized whenever chiller is in occupied mode regardless of whether chiller is running. When
chiller is in unoccupied mode, chilled fluid pump relay is
not energized.
44
Page 45
Table 13 — Factory Configuration Keystrokes
To change a configuration enter the new configuration
and presswhile on the correct configuration.
SUB-KEYPAD
FUNCTIONENTRY
3 FACTORY
CFG
5 SERVICE
CFG
LEGEND
MOP — Maximum Operating Pressure
EXV — Electronic Expansion Valve
DISPLAYCOMMENTS
FACT CFG
XXXXXXXX
XXXXXXXX
XXXXXXXX
XXXXXXXX
XXXXXXXX
XXXXXXXX
XXXXXXXX
SRV CFG
XXXXXXXX
XXXXXXXX
FACTORY
CONFIGURATION
CODES
Configuration
Code 1
Configuration
Code 2
Configuration
Code 3
Configuration
Code 4
Configuration
Code 5
Configuration
Code 6
Configuration
Code 7
SERVICE
CONFIGURATION
CODES
Configuration
Code 8
Configuration
Code 9
REFRIG XRefrigerant Type
TDTYPE XPressure Transducer Select
OPS XOil Pressure Set Point
LPS XLow Pressure Set Point
FANTYP XFan Staging Select
SH XEXV Superheat Set Point
MOP XEXV MOP Superheat
ZM XZ Multiplier
When unit is configured for dual set point, chilled liquid
pump relay is energized continuously, in both occupied and
unoccupied modes. Occupied mode places occupied chilled
water set point into effect; unoccupied mode places unoccupied chilled water set point into effect.
Scheduling —is usedtooverrideany current schedule in effect (for 0-4 hours).is used to activate a
clock for the scheduling function.-are used
to program schedules for specific occupied and unoccupied
periods.
The schedule consists of from one to 8 occupied time periods, set by the operator.These time periods can be flagged
to be in effect or not in effect on each day of the week. The
day begins at 00.00 and ends at 24.00. The machine is in
unoccupied mode unless a scheduled time period isin effect.
If an occupied period is to extend past midnight, it must be
programmed in the following manner: occupiedperiod must
end at 24:00 hours (midnight); a new occupied period must
be programmed to begin at 00:00 hours.
Table 14 — Adjustable Field Configurations
FIELD CONFIGURATION
ITEM AND CODES
CCN element address
(Entered by CCN Technician)
CCN Bus Number
(Entered by CCN Technician)
CCN Baud Rate
(Entered by CCN Technician)
Cooler Fluid Select
1 = Water (38 to 70 F
[3.3 to 21 C] Set Point)
2 = Medium Brine (15 to 70 F
[–9 to 21 C] Set Point)
Display Unit Select
0 = English
1 = Metric SI
Delay at Power Up00
No. Circuit A Unloaders
0 = No Unloaders
1 = One Unloader
2 = Two Unloaders
No. Circuit B Unloaders
0 = No Unloaders
1 = One Unloader
2 = Two Unloaders
*And associated modular units.
†For reset of alarms.
1
0
0
1
45
Page 46
NOTE: This is true only ifthe occupied period starts at 00:00
(midnight). If the occupied period starts at a time other than
midnight, then the occupied period must end at 00:00 hours
(midnight) and new occupied period must be programmed
to start at 00:00 in order for the chiller to stay in the occupied mode past midnight.
The time schedule can be overridden to keep unit in occupied mode for one, 2, 3, or 4 hours on a one-time basis.
See Example 9.
All subfunctions of schedule function are password
protected except the override subfunction,. Password entry into subfunctionsthrough,
is done through service function. See page 43, logging on/
logging off.
Figure 10 shows a schedule for an office building with the
chiller operating on a single set point schedule. The schedule is based on building occupancy with a 3-hour off-peak
cool-down period from midnight to 3 a.m. following the weekend shutdown. To learn how this sample schedule would be
programmed, see Example 9.
NOTE: This schedule was designed to illustrate the programming of the schedule function and is not intended as a
recommended schedule for chiller operation.
Example 9 — Using the Schedule Function
KEYPAD
ENTRY
PROGRAMMING PERIOD 1:
DISPLAYCOMMENT
OVRD 0
OVRD 33 hours override in effect
OVRD 0Override cancelled
CLOCK 0Schedule function is inactive
CLOCK 1
PERIOD 1
OCC 00.00
UNO 00.00
UNO 3.00Period 1 ends at 3:00 a.m.
MON NO
MON YES
TUE YES
TUE NO
No scheduled override
in effect
Schedule function is enabled
through local unit clock
Define schedule period 1.
Start of occupied time
For this example, first
period should start here
(at midnight) so no entry
is needed
Start of unoccupied time
(end of period). For this
example, period 1 should
end at 3:00 a.m.
Monday is now flagged no
for period 1. To put period 1
into effect on Monday,
Monday must be flagged
yes
Monday is now flagged for
period 1 to be in effect
For this example, period 1
is to be in effect on Monday
only.All other days must be
checked to be sure that they
are flagged no. If any day is
flagged yes, change to no
Tuesday is now flagged
no for period 1
Example 9 — Using the Schedule Function (cont)
KEYPAD
ENTRY
PROGRAMMING PERIOD 2:
CCN — Carrier Comfort Network
DISPLAYCOMMENT
PERIOD 2 Define schedule period 2
OCC 00.00 Start of occupied time
OCC 7.00
UNO 00.00
UNO 18.00
MON NO
MON YES
TUE NO
TUE YES
WED YES
WED NO
PERIOD 3
OCC 00.00
OCC 7.00
UNO 00.00
UNO 21.30
MON NO
TUE NO
WED NO
WED YES
THUR NO
FRI NO
SAT NO
SUN NO
Occupied time will start
at 7:00 a.m.
Start of unoccupied time
(end of period). For this
example, period 2 should
end at 18:00 (6:00 p.m.)
Period 2 ends at 18:00
(6:00 p.m.)
Monday is now flagged no
for period 2. To put period 2
into effect on Monday,
Monday must be flagged yes
Monday is now flagged for
period 2 to be in effect
Tuesay is now flagged no
for period 2. To put period 2
into effect on Tuesday,
Tuesday must be flagged
yes
Tuesday is now flagged for
period 2 to be in effect
For this example, period 2
is to be in effect only on
Monday and Tuesday.
All other days must be
checked to be sure that
they are flagged no. If
a day is flagged yes,
change to no
Wednesday is now flagged
no for period 2
Define schedule
period 3
Start of occupied
time
Occupied time will start
at 7:00 a.m.
Start of unoccupied time
(end of period 3). For this
example, period 3 should
end at 21:30 (9:30 p.m.)
Period 3 ends at 21:30
(9:30 p.m.)
Check to be sure that
Monday and Tuesday are
flagged no for period 3
Wednesday is flagged
no, change to yes
Wednesday is now
flagged yes for period 3
Check to be sure that all
other days are flagged no
46
Page 47
Periods 4 and 5 can be programmed in the same manner,
flagging Thursday and Friday yes for period 4 and Saturday
yes for period 5. For this example, periods 6, 7, and 8
are not used: they should be programmed OCC 00.00,
UNO 00.00.
NOTE: When a dayis flagged yes for2 overlapping periods,
occupied time will take precedence over unoccupied time.
Occupied times can overlap in the schedule with no
consequence.
To extend an occupied mode beyond its normal termination for a one-time schedule override, program as shown
below:
OVRD 0
OVRD 3
Override is set for 0. Enter
the number of hours of
override desired
Unit will now remain in
occupied mode for
an additional 3 hours
Holiday Schedule — Pressto schedule up to
30 holiday periods. All holidays are entered with numerical
values. First, the month (01 to 12), then the day (01 to 31),
then the duration of the holiday period in days.
Examples: July 04 is 07.04.01.
Dec 25 - 26 is 12.25.02
If any of the 30 holiday periods are not used, the display
shows NEW.
NEW indicates a holiday that has not been assigned yet.
and 2nd)
and 27th)
and 25th)
and 31st)
Fig. 10 — Sample Time Schedule
TROUBLESHOOTING
The Flotronic™ II control has many features to aid the
technicians in troubleshooting a Flotronic II Chiller. By using the keypad and display module and the status function,
actual operating conditions of the chiller are displayed while
unit is running. Testfunction allows proper operation of compressors, compressor unloaders, fans, EXVs and other components to be checkedwhile chiller is stopped.Service function displays how configurable items are configured. If an
operating fault is detected, an alarm is generated and an
alarm code(s) is displayed under the subfunction,
along with an explanation ofthe fault. Up to 10 current alarm
codes are stored under this subfunction. For checking specific items, see Table 9.
Checking Display Codes — To determine how ma-
chine has been programmed to operate, check diagnostic
information () and operating mode displays ().
If no displayappears, follow procedures in Control Modules
section on page 63. If display is working, continue as
follows:
1. Note all alarm codes displayed,.
2. Note all operating mode codes displayed,.
3. Note leaving chilled water temperature set point in ef-
fect and current leaving water temperature,.
If machine is running, compare the ‘‘in effect’’ leaving
water temperature set point with current water temperature. Remember, if reset is in effect, the values may be
differentbecausemachineis operating to the modified chilled
water set point. If currenttemperatureis equal to set point,
but set point is not the one desired, remember that if dual
set point hasbeen selected in the schedule function, there
are 2 set points to which the machine can be operating.
Check the programming ofschedule function to see ifoccupied or unoccupied set point should be in effect.
47
Page 48
UnitShutoff— Toshut unitoff, move LOCAL/ENABLE-
STOP-CCN switch to STOP position. Any refrigeration circuit operating at this time continues to complete the pumpout cycle. Lag compressors stop immediately, and lead
compressors run to complete pumpout.
Complete Unit Stoppage — Complete unit stoppage
can be caused by any of the following conditions:
1. Cooling load satisfied
2. Remote on/off contacts open
3. Programmed schedule
4. Emergency stop command from CCN
5. General power failure
6. Blown fuse in control power feed disconnect
7. Open control circuit fuse
8. LOCAL/ENABLE-STOP-CCN switch moved to STOP
position
9. Freeze protection trip
10. Low flow protection trip
11. Open contacts in chilled water flow switch (optional)
12. Open contacts in any auxiliary interlock. Terminals that
are jumpered from factory are in series with control switch.
Opening the circuit between these terminals places unit
in stop mode, similar to moving the control switch to
STOP position. Unit cannot start if these contacts are
open. If they open while unit is running,unitpumpsdown
and stops.
13. Cooler entering or leaving fluid thermistor failure
14. Low transducer supply voltage
15. Loss of communicationsbetween processor module and
other control modules
16. Low refrigerant pressure
17. Off-to-on delay is in effect.
Single Circuit Stoppage — Single circuit stoppage
can be caused by the following:
1. Low oil pressure in lead compressor
2. Open contacts in lead compressor high-pressure switch
3. Low refrigerant pressure
4. Thermistor failure
5. Transducer failure
6. Ground fault in lead compressor indicator (indicator is
field-supplied on 040-060, 070 [60 Hz],and080-110and
associated modular units)
7. High suction superheat
8. Low suction superheat
9. Lead compressor circuit breaker trip. Stoppage of one
circuit by a safety device action does not affect other
circuit. When a safety device trips on a lead compressor, circuit is shut down immediately and EXV closes.
10. Ground fault for any circuit compressor (130-210 and
associated modular units).
Lag Compressor Stoppage — Lag compressor stop-
page can be caused by the following:
1. Open contacts in high-pressure switch
2. Compressor ground fault (indicator is field-supplied on
4. Not required to run to meet cooling load requirement
If stoppage occurs more than once as a result of any of
the above safety devices, determine andcorrectthe cause
before attempting another restart.
RestartProcedure — After cause for stoppage hasbeen
corrected, restart is either automatic or manual, depending
on fault. Manual reset requires that LOCAL/ENABLESTOP-CCN switch be moved to STOP position, then back
to original operating position. Some typical fault conditions
are described in Table 15. For a complete list of fault conditions, codes, and reset type, see Table 16.
Unit restarts automatically when
power is restored
Auto reset first time, then
manual if within same day
POWER FAILURE EXTERNAL TO THE UNIT — Unit
restarts automatically when power is restored.
Alarms and Alerts— These are warnings of abnormal
or fault conditions, and may cause either one circuit or the
whole unit to shut down. They are assignedcode numbers as
described below. These code numbers are displayed
on the HSIO when thesubfunction is entered. A
fault that affects one one circuit of the chiller will generate
an alert, and a fault that affects the entire unit will generate
an alarm.
Following is a detailed description of each alarm and alert
code error and possible cause. Manual reset is accomplished
by moving LOCAL/ENABLE-STOP-CCN Switch to STOP
position, then back to LOCAL or CCN position. See
Table 16 for listing of each alarm and alert code.
Code 0No alarms or alerts exist
Codes1-8 Compressor failure
If DSIO-LVor-EXV relay module controlrelay feedback
switch or signal issensed as open during operation ofa compressor, microprocessor detects this and stops compressor,
energizes alert light, and displays a code of 1, 2, 3, 4, 5, 6,
7, or 8 depending on the compressor. Compressor locks off;
to reset, use manual reset method.
If lead compressor in a circuit shuts down, the other compressors in the circuit stop and lock off. Only the alert mode
for lead compressor is displayed.
The microprocessor is also programmed to indicate compressor failure if feedbackterminal on DSIO-LVor-EXV J3
terminal strip receives voltage when compressor is not supposed to be on.
NOTE: It takes 5 seconds forthecontrolto generate the alarm
code and lock out the compressor(s) on compressor failure
code(s) 1 through 8.
44
45Low suction temperature circuit BCircuit B shut down
46
47High suction superheat circuit BCircuit B shut downYesManualLow charge, faulty expansion valve or
48
49Low suction superheat circuit BCircuit B shut downYesManualFaulty EXV or thermistor.
50
51Initial configuration requiredUnit cannot start—Manual Configuration omitted.
52Emergency stop by CCN commandUnit shut downYesCCNNetwork command.
53
54Cooler pump interlock failureUnit shut downNoManual Failure of cooler pump or controls
55Cooler pump interlock failureCooler pump shut down—Manual Failure of cooler pump relay or interlock
56AlertWSM communication failureWSM forces removed—Auto.Wiring fault or module failure
57
58Calibration required for discharge pressure
59Calibration required for suction pressure
60Calibration required for suction pressure
61Calibration required for oil pressure
62Calibration required for oil pressure
Compressor A1 failureCircuit A shut downNoManualHigh-pressure switch trip, or wiring
faulty expansion valve, crankcase
heater, or pressure transducer.
faulty expansion valve, crankcase
heater, or pressure transducer.
or faulty thermistor.
thermistor, or plugged filter drier.
thermistor, or plugged filter drier.
Transducer not calibrated
49
Page 50
Table 16 — Alarm and Alert Codes (cont)
DISPLAY
68,69—Not used————
CPCS — Compressor Protection Control Module
FSM— Flotronic™ System Manager
PS— Power Supply
WSM — Water System Manager
ALARM
ALERT
63AlarmComplete unit shutdownAlarm only—Auto.Check individual alarms
64
66AlarmFSM communication lossFSM forces removed—Auto.Wiring faulty or module failure
67AlarmTransducer calibration date code failureUnit cannot start—Auto.Incorrect date code entered
70AlertHigh leaving chilled fluid temperatureAlarm only—Auto.Building load greater than unit capacity,
Alert
Loss of charge, circuit ACircuit cannot start—Auto.Refrigerant leak or transducer
LEGEND
DESCRIPTION
Possible causes of failure:
1. High-Pressure Switch Open — High-pressure switch for
each compressor is wired in series with 24-v power that
energizes compressor control relay.Ifhigh-pressureswitch
opens during operation, compressor stops. This is
detected by microprocessor through the feedback
terminals.
2. DSIO-L Vor DSIO-EXV Module Failure—If a DSIO-LV
relay module relay fails open or closed, microprocessor
detects this, locks compressor off, and indicates an
error.
3. Wiring Errors — If a wiring error exists causing CPCS,
CR, or feedback switch to not function properly, microprocessor indicates an error.
4. Processor (PSIO) Failure — If hardware that monitors
feedback switch fails, or processor fails to energize relay
module relay to on, an error may be indicated.
NOTE: The control does not detect circuit breaker failures. If a circuit breaker trips on lead compressor in a
circuit, a low oil pressurefailure is indicated. On the other
compressors, no failure is indicated.
5. Ground Fault Module on 130-210 and associated modular units (CGFAor CGFB) Open — Module contacts are
in lead compressor circuits, but ground fault could be in
any compressor in affected circuit.
Ground fault of any 040-110 and associated modular unit
compressor (field-supplied accessory on 040-060 and070,
60 Hz units; standard on 070, 50 Hz and 80-110 and associated modular units) will cause a trip.
6. Checkout Procedure —Shut offmain power to unit. Turn
oncontrolpower, thenstepthroughsubfunc-
tionto proper compressor number (i.e., failure
code 5 is compressor B1). Next, energize the step. If step
works correctly, then failure code is caused by:
• HPS (high-pressure switch) open
• Misplaced feedback wire from J4 and J5 terminals
• Ground wire and 24-v feeds reversed on one or more
points on J3
ACTION TAKENCIRCUITRESET
BY CONTROLPUMPDOWNMETHOD
*Reset automatic first time, manual if repeated same day.
Compressor Alarm/Alert Circuit — For compres-
sor A1 circuit, processor closes contacts between J4 terminals 2 and 3 to start compressor. See Fig. 11A-11C. Safeties
shown to left of J4 must be closed in order for power to
reach compressor control relay, and the feedback input terminals on J3.
Failure of power to terminal 1 on J3, when contacts be-
tween 2 and 3 on J4 should be closed, causes a code 1 alert.
Terminal 2 on J3 is the other leg of the compressor A1
feedback channel. It is connected to the 24-v common.
NOTE: Similar connections for each compressor can be fol-
lowed on the unit wiring diagrams located on the unit.
If temperature measured by these thermistors is outside
range of –40 to 240 F (–40 to 116 C), unit shuts down after
going through a normal pumpout. Reset is automatic if temperature returns to the acceptablerange, and unit start-up follows normal sequence. The cause of the fault is usually a
bad thermistor, wiring error, or loose connection.
On units with thermistors, if temperature measured bythese
thermistors is outside the range of –40 to 240 F (–40 to
116C), affectedcircuitshuts down after going through anormal pumpout. Other circuit continues to run. Reset is automatic if temperature returns to the acceptable range, and circuit start-up follows normal sequence.Thecause of this fault
is usually a bad thermistor, wiring error, or loose
connection.
On units with transducers, if the saturated suction temperature is greater than the leaving fluid temperature plus
10° F (5.5 C) for more than 5 minutes, the affected circuit
shuts down (after going through normal pumpout). Thereset
is automatic if the saturated suction temperature returns to
the acceptable range and start-up follows the normal sequence. The cause of this fault is usually a bad transducer,
a wiring error, or a loose connection.
PROBABLE CAUSEOR
failure65Loss of charge, circuit BCircuit cannot start—Auto.
low water/brine flow, or compressor
fault. Check for other alarms or alerts.
50
Page 51
C—Contactor
CB— Circuit Breaker
COM, COMM — Communications Bus
CPCS— Compressor Protection
CR— Compressor Contactor Relay
DGT— Discharge Gas Thermostat (Optional)
DSIO— Relay Module (Low Voltage)
HPS— High-Pressure Switch
LV— Low Voltage
NC— Normally Closed
NO— Normally Open
PL— Plug
PWR— Power
SNB— Snubber
TB— Terminal Block
TRAN— Transformer
U—Unloader
Fig. 11A — 24-V Safety Circuit Wiring (040-070)
LEGEND
Control Module
Code 21 Reset thermistor failure (applies only to installa-
tions having external temperature reset) (alert)
If temperature measured by this thermistorisoutside range
of –40 to 240F (–40 to 116 C), resetfunction is disabled and
unit controls to normal set point. If temperature returns to
the acceptable range, reset function is automatically enabled. The cause of this fault is usually a bad thermistor,
wiring error, or loose connection.
If output voltage of anyofthese transducers is greater than
5 v, affected circuit shuts down without going through pumpout process (Alerts 24-27). Other circuit continues to run.
Reset is automaticif output voltage returns to the acceptable
range, and circuit start-up follows normal sequence. The cause
of this fault is usually a bad transducer or a wiring error.
Code 28Low transducer supply voltage (alarm)
If transducer supply voltage is less than 4.5 v or greater
than 5.5 v, unit shuts down without going through pumpout
process. Reset is automatic if supply voltage returns to the
acceptable range, and circuit start-up follows normal sequence. The cause of this fault is usually a faulty transformer or primary voltage is out of range.
51
Page 52
C—Contactor
CB— Circuit Breaker
COMM — Communications Bus
CPCS — Compressor Protection Control Module
DGT— Discharge Gas Thermostat (Optional)
DSIO— Relay Module (Low Voltage)
HPS— High-Pressure Switch
LV— Low Voltage
PL— Plug
PWR— Power
TB— Terminal Block
TRAN — Transformer
U—Unloader
The voltage supplied to the processor is polarized. When
checking for proper voltage supply, be sure to consider this
polarity. If voltage appears to be within acceptable tolerance, check to be sure the transformer supplying PS1 is not
grounded. Grounding the supply transformer can result in
serious damage to the control system.
Code 29LOCAL/ENABLE-STOP-CCN Switch Failure
(switch resistances out of range) (alarm)
This fault occurs due to the failure of the switch or due to
a wiring error.
These codes apply only ifunitis configured for these functions. If 4 to 20 mA signal is less than 4 or more than
20 mA, reset or demand limit function is disabled and unit
functions normally. If mA signal returns to the acceptable
range, function is automatically enabled.
Code 32 Loss of communication with compressor
relay module (DISO-LV) (alarm)
Code 33 Loss of communication with EXV relay
module (DSIO-EXV) (alarm)
If communication is lost witheither of these modules, unit
shuts down without pumpout. This alarm resets automatically when communication is restored.The unitstarts up normally after alarm condition is reset. Probable cause of condition is a faulty or improperly connected plug, wiring error,
or faulty module.
Loss of communication can be attributed to a grounded
transformer with a secondary voltage of 21 vac supplying
the PSIO, DSIO-LV, or 4 IN/4 OUT modules; the 12.5-vac
transformer supplying the DSIO-EXV module; or the
24-vac transformer supplying PS1 for thetransformers.These
transformers should not be grounded, or serious damage to
controls can result. Check to be sure the transformers are
not grounded.
NOTE: If a blank PSIO module is downloaded without be-
ing connected to the modules DSIO, this alarm is
energized.
Code 34 Loss of communication with 4 In/4 Out module
(alarm)
This applies only if one or more of the following options
are used:
• external temperature reset
• 4 to 20 mA temperature reset
• external switch controlled dual set point
• switch controlled demand limit
• 4 to 20 mA demand limit
• hot gas bypass
If communication is lost with 4 IN/4 OUT module, the
unit shuts off automatically, after finishing pumpout. Reset
of alarm is automatic when communication is restored. Start-up
after alarm is remediedfollows a normal sequence.Probable
cause of condition is a faulty or improperly connected plug,
wiring error, or faulty module.
Loss of communication can be attributed to a grounded
transformer with a secondary voltage of 21 vac supplying
the PSIO, DSIO-LV, or 4 IN/4 OUT; the 12.5-vac transformer supplying the DSIO-EXV module, or the 24-vac transformer supplying PS1 for the transformers.Thesetransformers
should not be grounded, or serious damage to controls can
result. Check to be sure the transformers are not grounded.
Code 36 Low refrigerant pressure, Circuit A (alert)
Code 37 Low refrigerant pressure, Circuit B (alert)
If suction pressure transducer senses a pressure below set
point for more than 5 minutes at start-up or more than
2 minutes during normal operation, affected circuit shuts down
without going through the pumpout process. Reset is automatic when pressure reaches 10 psig above set point if there
have been no previous occurrences of this fault on the same
day. If this is a repeat occurrence on same day, then reset is
manual, with LOCAL/ENABLE-STOP-CCN switch. Factory configured set point is 27 psig for standard chillers and
12 psig for brine chillers.
Possible causes of fault are low refrigerant charge, faulty
EXV, plugged filter drier, or faulty transducer.
Code 38 Failure to pump out, Circuit A (alert)
Code 39 Failure to pump out, Circuit B (alert)
The pumpout process is terminated when saturated suction temperature is 10° F (5.6° C) below temperature at beginning of pumpout, or 10° F (5.6° C) below leaving water
temperature or reaches a saturated suction temperature of
–15 F (–26 C). If appropriate saturated suction temperature
is not met within 3 minutes (on 2 consecutive tries), circuit
shuts down without pumpout. Resetis manual with LOCAL/
ENABLE-STOP-CCN switch, and start-up follows normal
sequence.
Possible causes for this alarmarea bad thermistor or transducer or a faulty expansion valve.
Code 40 Low oil pressure, Circuit A (alert)
Code 41 Low oil pressure, Circuit B (alert)
53
Page 54
If oil pressure differential is less than set point for more
than 2 minutes at start-up, or more than one minute during
normal operation, affected circuit shuts down without going
through pumpout process. Reset is manual with LOCAL/
ENABLE-STOP-CCN switch, and start-up follows normal
sequence. Factory configured differential oil pressure is
6 psig.
Possible causes of fault are faulty compressor, expansion
valve, crankcase heater or transducer, refrigerant overcharge, insufficient oil charge, or tripped circuit breaker.
Code 42 Cooler freeze protection (alarm)
If cooler entering or leaving water temperature is below
34° F (1.1° C) for water or more than 8° F (4.4° C) below
set point for brine, unitshutsdown without pumpout. Chilled
water pump continues to run if controlled by chiller controls. Reset is automatic when leaving fluid temperature reaches
6° F (3° C) aboveset point, providing there has beenno prior
occurrence of this fault the same day. If fault has occurred
previously the same day, reset is manual with LOCAL/
ENABLE-STOP-CCN switch.
Possible causes of fault are low fluid flow or faulty
thermistor.
Code 43 Low fluid flow (alarm)
If any compressors are operating and entering fluid temperature is 3° F (1.7° C) or more below leaving fluid temperature for more than one minute, unit shuts down without
pumpout. Chilled fluid pump also shuts down. Reset is manual
with LOCAL/ENABLE-STOP-CCN switch, and start-up follows normal sequence.
This is a suitable method for sensing low fluid flow because entering fluid thermistor is in the cooler shell and responds more quickly to compressor operation than the leaving fluid thermistor in the leaving water nozzle. Possible causes
of fault are faulty chilled fluid pump, control or thermistor.
If saturated suction temperature is less than 32 F (0°C)
and is 20° F (11° C) for water or 30° F (16° C) for brine or
more below leaving fluid temperature, mode 14 is displayed. Unit continues to run,but additional compressors are
not allowed to start. If condition persists for more than
10 minutes, fault code is displayed,andunit shuts down without pumpout. Reset is manual with LOCAL/ENABLE-STOPCCN switch, and start-up follows normal sequence.
Possible causes of fault are lowrefrigerantcharge,plugged
filter drier, or a faulty expansion valve or thermistor.
Code 46 High suction superheat, Circuit A (alert)
Code 47 High suction superheat, Circuit B (alert)
If expansion valve is fully open, suction superheatisgreater
than 75 F (42 C), and saturated evaporator temperature is
less than MOP(maximum operating pressure) for more than
5 minutes, unit shuts down after normal pumpout process.
Reset is manual with LOCAL/ENABLE-STOP-CCN switch,
and start-up follows normal sequence.
Possible causes of fault are lowrefrigerantcharge,plugged
filter drier, or a faulty expansion valve or thermistor.
Code 48 Low suction superheat, Circuit A (alert)
Code 49 Low suction superheat, Circuit B (alert)
If EXV is at minimum position, suction superheat is less
than 10° F (5.5° C) or saturated evaporator temperature is
greater than MOP (maximum operating pressure) for more
than 5 minutes, affectedcircuit shuts down after going through
pumpout process. Reset is manual with LOCAL/ENABLESTOP-CCN switch, and start-up follows normal sequence.
Possible causes of fault are faulty expansion valve or
thermistor.
Code 50 Illegal configuration (alarm)
This fault indicates a configuration error. Unit is not allowed to start. Check all configuration data and set points
and correct any errors.
Code 51 Initial configuration required (alarm)
This fault indicates factory configuration has not beendone,
and unit is not allowed to start. Refer to unit wiring
label diagrams for factory configuration codes. There are
9 groups of 8-digit numbers that must be entered. The first
7 groups must be entered undersubfunction. Groups
8 and 9 must be entered undersubfunction.
Enter each group, then press thekey. Press the
down arrowafter each group to bring up the next
empty screen. Unit should start after factory and field con-
figurations are correctly entered.
The usual cause of this fault is replacement of the processor module. Refer to instructions accompanying the replacement module.
Code 52 Emergency stop by CCN command (alarm).
Unit shuts down immediately without pumpout when this
command is received, and goes throughnormalstart-up when
command is cancelled.
Code 53Cooler pump interlock failure — Contacts fail to
close at start-up (alarm)
If the unit is configuredforcooler pump control and cooler
pump interlock, and the interlock fails to close within one
minute of starting the cooler pump, the unit is shut down
without pumpout. The cooler pump is also shut down. Reset
is manual with the LOCAL/ENABLE-STOP-CCN switch,
and start-up follows the normal sequence.
Possible causes are:
1. Interlock switch fails to close within one minute after chilled
water pump starts
2. Interlock switch opens during unit operation
3. Interlock voltage is detected, but unit is not configured
for interlock
4. Interlock voltage is outside its valid range
If any of these conditions occur, all compressors are disabled and, if running, shutdown occurs without pumpout.
Chilled fluid pump also shuts down. Reset is manual, with
LOCAL/ENABLE-STOP-CCN switch. Most probable cause
of this fault is shutdown or failure of chilled fluid pump to
start. Other possibilities are improper configuration or wiring errors.
Code 54 Cooler pump interlock failure — Contacts open
during normal operation (alarm)
If the unit is configuredforcooler pump control and cooler
pump interlock, and the interlock opens during normal operation, the unit is shut down without pumpout. The cooler
pump is also shut down. Reset is manual with the LOCAL/
ENABLE-STOP-CCN switch, and startup follows the normal sequence.
Possible causes are:
1. Interlock switch fails to close within one minute after chilled
water pump starts
2. Interlock switch opens during unit operation
3. Interlock voltage is detected, but unit is not configured
for interlock
4. Interlock voltage is outside its valid range
If any of these conditions occur, all compressors are disabled and, if running, shutdown occurs without pumpout.
Chilled fluid pump also shuts down. Reset is manual, with
54
Page 55
LOCAL/ENABLE-STOP-CCN switch. Most probable cause
of this fault is shutdown or failure of chilled fluid pump to
start. Other possibilities are improper configuration or wiring errors.
If the unit is configuredforcooler pump control and cooler
pump interlock, and the interlock is closed when the cooler
pump relay is off, the cooler pump shall be shut down and
the unit prevented from starting. Reset is manual with the
LOCAL/ENABLE-STOP-CCN switch.
Possible causes are:
1. Interlock switch fails to close within one minute after chilled
water pump starts
2. Interlock switch opens during unit operation
3. Interlock voltage is detected, but unit is not configured
for interlock
4. Interlock voltage is outside its valid range
If any of these conditions occur, all compressors are disabled and, if running, shutdown occurs without pumpout.
Chilled fluid pump also shuts down. Reset is manual, with
LOCAL/ENABLE-STOP-CCN switch. Most probable cause
of this fault is shutdown or failure of chilled fluid pump to
start. Other possibilities are improper configuration or wiring errors.
Code 56 Water System Manager (WSM) communication
failure (alert)
If the WSM has previously established communications
with the control and the WSM is not disabled and has not
communicated with the controlwithin the last 5minutes, the
control will remove all WSM forces from the chillers variables. The chiller will continue to operate on a stand-alone
basis. Reset is automatic whenthe WSM re-establishes communication with the unit.
Code 57Calibration required for discharge pressure trans-
ducer, circuit A (alert)
Code 58Calibration required for discharge pressure trans-
ducer, circuit B (alert)
If the discharge pressure transducer has not been successfully calibrated, the circuit will not start. Reset is automatic
upon successful calibration of the transducer.
Code 59Calibration required for suction pressure trans-
ducer, circuit A (alert)
Code 60Calibration required for suction pressure trans-
ducer, circuit B (alert
If the suction pressure transducer has not been successfully calibrated, the circuit will not start. Reset is automatic
upon successful calibration of the transducer.
Code 61Calibration required for oil pressure transducer,
circuit A (alert)
Code 62Calibration required for oil pressure transducer,
circuit B (alert)
If the oil pressure transducer has not been successfully
calibrated, the circuit will not start. Reset is automatic upon
successful calibration of the transducer.
Code 63 Complete unit shutdown due to failure (alarm)
This alarm alertsthe user that the unit is totallyshut down
due to one ormore fault conditions. Resetis automatic when
all alarms causing complete unit shutdown are reset.
Code 64 Loss of charge, circuit A (alert)
Code 65 Loss of charge, circuit B (alert)
If the unit uses suction and discharge transducers with the
same part number, and the discharge pressure is below
10 psig when the unit is shut down, the circuit will not start.
Reset is automatic when the discharge pressure rises above
15 psig. This alarm does notfunction in unitsusing different
part number transducers for suction and discharge pressure,
since the discharge transducer in that application does not
function below 20 psig.
Code 66Flotronic™ System Manager loss of communi-
cations (alarm)
If the FSM has established communication with the control, and the communication is subsequently lost for more
than 20 seconds, the control will remove all forces on the
chiller variables. Control of the unit will revert to standalone basis, and reset is automatic upon re-establishment of
communication.
Code 67 Transducer calibration failure due to incorrectdate
code (alarm)
This applies to units having pressure transducers with the
same part number for both suction and discharge pressures.
If the transducer calibration is attempted and the factory default date code (Jan. 1, 1980) is in the date variable, then the
unit will not start. Reset is automatic when the proper date
code is entered upon calibration.
Code 70 High leaving chilled fluid temperature (alert)
If the leaving chilled fluid temperature is rising and is
higher than the limit established in thesubfunction
and the unit is at full capacity then alert 70 will be activated.
The unit will continue to function normally, and reset will
be automatic upon leaving chilled fluid temperature dropping to 5° F below the limit or less than control
set point.
Electronic Expansion Valve (EXV)
NOTE: This applies to all units except 30GN040 and 045
with optional brine. The 040 and 045 unitswithoptionalbrine
have TXVs.
EXV OPERATION — These valves control the flow of liquid refrigerant into the cooler. They are operated by the processor to maintain a specified superheat at lead compressor
entering gas thermistor (located between compressor motor
and cylinders). There is one EXV per circuit. See
Fig. 12.
High-pressure liquid refrigerant enters valve through bottom. A series of calibrated slots are located in side of orifice
assembly.As refrigerant passes through orifice, pressure drops
and refrigerant changes to a 2-phase condition (liquid and
Fig. 12 — Electronic Expansion Valve (EXV)
55
Page 56
vapor). To control refrigerant flow fordifferent operating conditions, sleeve moves up and down over orifice, thereby changing orifice size. Sleeve is moved by a linear stepper motor.
Stepper motor moves in increments and is controlled directly by the processor module. As stepper motor rotates,
motion is transferred into linear movement by lead screw.
Through stepper motor and lead screws, 1500 discrete steps
of motion are obtained. The large number of steps and long
stroke result in very accurate control of refrigerant flow.
Thesubfunction shows EXV valve position as
a percent of full open. Position should change constantlywhile
unit operates. If a valve stops moving for any reason (mechanical or electrical) other than a processor or thermistor
failure, the processor continues to attempt to open or close
the valve to correct the superheat. Once the calculated valve
position reaches 120 (fully closed) or 1500 (fully open), it
remains there. If EXV position reading remains at 120 or
1500, and the thermistors and pressure transducers are reading correctly, the EXV is notmoving. Follow EXV checkout
procedure below to determine cause.
The EXV is also used to limit cooler suction temperature
to 50 F (10 C). This makes it possible for chiller to start at
higher cooler fluid temperatures without overloading compressor. This is commonly referred to as MOP (maximum
operating pressure), and serves as a load limiting device to
prevent compressor motor overloading. This MOP or load
limiting feature enables the 30G Flotronic™ II chillers to
operate with up to 95 F (35 C) entering fluid temperatures
during start-up and subsequent pull-down.
CHECKOUT PROCEDURE — Follow steps below to diagnose and correct EXV problems.
1. Check EXV driver outputs. Check EXV output signals at
appropriate terminals on EXV driver module (see
Fig. 13) as follows:
Connect positive test lead to terminal 1 on EXV driver.
Set meter for approximately 20 vdc. Enter outputs
subfunction of test function by pressing, then
advance to EXVA test by pressing10 times. Press
. The driver should drive the circuit A
EXVfully open. During next several seconds connect negative test lead to pins 2, 3, 4, and 5 in succession. Voltage
should rise and fall at each pin. If it remains constant at
a voltage or at zero v, remove connector to valve and
recheck.
Pressto close circuit A EXV. If a problem still
exists, replace EXV driver module. If voltage reading is
correct, expansion valve should be checked. Next, test
EXVB. Connect positive test lead to pin 7 and the negative test lead to pin 8, 9, 10, and 11 in succession during
EXVB test.
2. Check EXV wiring. Check wiring to electronic expan-
sion valves from terminal strip on EXV driver. See
Fig. 13.
a. Check color coding and wire connections. Make sure
they are connected to correct terminals at driver and
EXV plug connections.
b. Check for continuity and tight connection at all pin
terminals.
c. Check plug connections at driver and at EXVs to be
sure EXV cables are not crossed.
3. Check resistance of EXV motor windings. Remove plug
at J4 terminal strip and check resistance between common lead (red wire, terminal D) and remaining leads, A,
B, C, and E (see Fig. 13). Resistance should be
25 ohms 6 2 ohms.
EXV — Electronic Expansion Valve
Fig. 13 — EXV Cable Connections to EXV Driver
Module, DSIO (EXV)
Control of valve is by microprocessor. A thermistor and
a pressure transducerlocated in lead compressor are used
to determine superheat. The thermistor measures temperature of the superheated gas entering the compressor
cylinders. The pressure transducer measures refrigerant
pressure in the suction manifold.The microprocessorconverts pressure reading to a saturation temperature. The
difference between temperature of superheated gas and
saturation temperature is the superheat.
Because the EXVs are controlled by the processor module, it is possible to track valve position. During initial
start-up, EXV is fully closed. After start-up, valve position is tracked by processor by constantly observing amount
of valve movement.
The processor keeps track of EXV position by counting
the number of open and closed steps it has sent to each
valve. It has no direct physical feedback of valve position. Whenever unit is switched from STOP to RUN position, both valves are initialized, allowing the processor
to send enough closing pulsestothe valve to move it from
fully open to fully closed, then reset the position counter
to zero.
4. The EXV test can be used to drive EXV to any desired
position. When EXV opens, the metering slots begin to
provide enough refrigerant foroperation at step 120. This
is fully closed position when circuitisoperating.The fully
open position is 1500 steps.
5. Check thermistors and pressure transducers that control
EXV.Checkthermistors and pressure transducers that control processor outputvoltage pulses to EXVs. See Fig. 14
for locations.
Circuit A — Thermistor T7, Suction Pressure Transducer
SPTA
Circuit B — Thermistor T8, Suction Pressure Transducer
SPTB
a. Use temperature subfunction of the status function
() to determine if thermistors are reading
correctly.
b. Check thermistor calibration at known temperature by
measuring actual resistance and comparingvaluemeasured with values listed in Tables 17 and 18.
c. Make sure thermistor leads are connected to proper
pin terminals at J7 terminal strip on processor module
and that thermistor probes are located in proper position in refrigerant circuit. See Fig. 15 and 16.
d. Use the pressure subfunction of the Status function
() to determine if pressure transducers are
56
Page 57
reading correctly. Connect a calibrated gage to lead
compressor suction or discharge pressure connection
to check transducer reading.
e. Make sure transducer leads are properly connected in
junction box and at processor board. Check transformer 5 output. Check voltage transducer 5 vdc
6 .2 v.
When above checks have been completed, check actual operation of EXV by using procedures outlined in
this step.
6. Check operation of EXV.
a. Close liquid lineservicevalve of circuit to be checked,
and run through the test step () for lead compressor in that circuit to pump down low side of system. Repeat test step 3 times to ensure all refrigerant
has been pumped from low side.
NOTE: Be sure to allow compressors to run for the
full pumpout period.
b. Turn off compressor circuit breaker(s). Close com-
pressor discharge service valves and remove any remaining refrigerant from low side of system.
c. Remove screws holding top cover of EXV. Carefully
remove top cover. If EXV plug was disconnected during this process, reconnect it after cover is removed.
When removing top cover, be careful to avoid damaging motor leads.
d. Enter appropriate EXV test step for EXVA or
EXVB in the outputs subfunction of the test function
(). Pressto initiate test. With
cover lifted off EXV valve body, observe operation of
valve motor and lead screw. The motor should turn
counterclockwise, and the lead screw should move up
out of motor hub until valve is fully open. Lead screw
movement should be smooth and uniform from
fully closed to fully open position. Pressto
check open to closed operation.
If valve is properlyconnected to processor and receiving correct signals, yet does not operate as described
above, valve should be replaced.
Operation of EXV valve can also be checked without
removing top cover. This method depends on operator’s skill in determining whether or not valve is moving. To use this method, initiate EXV test and open
valve. Immediately grasp EXV valve body. As valve
drives open, a soft, smooth pulse is felt for approximately 26 seconds as valve travels from fully closed
to fully open. When valve reaches end of its opening
stroke, a hard pulse is felt momentarily. Drive valve
closed and a soft, smooth pulse is felt for the 52 seconds necessary for valve to travel from fully open to
fully closed. When valve reaches end of its stroke, a
hard pulse is again feltas valve overdrives by 50 steps.
Valveshouldbedriventhroughatleast2completecycles
to be sure it is operating properly. If a hard pulse is
felt for the 26-second duration, valve is not moving
and should be replaced.
The EXV test can be repeated as required by entering any percentage from 0 () to 100 to initiate
movement.
If operating problems persist after reassembly,they may
be due to out-of-calibration thermistor(s) or intermittent
connections between processor boardterminals and EXV
plug. Recheck all wiringconnections and voltage signals.
Other possible causes of improperrefrigerantflow control could be restrictionsin liquid line. Check forplugged
filter drier(s) or restricted metering slots in the EXV. Formation of ice or frost on lower body of electronic expansion valve is one symptomofrestricted metering slots.
However,frostor ice formation is normally expected when
leaving fluid temperature from the cooler is below 40 F.
Clean or replace valve if necessary.
NOTE: Frosting of valve is normal during compressor
test steps and at initial start-up. Frost should dissipate after 5 to 10 minutes operation in a system that is operating
properly.If valve is tobe replaced, wrap valve with a wet
cloth to prevent excessive heat from damaging internal
components.
Thermostatic Expansion Valve (TXV)— Refer to
base unit Installation Instructions for TXV information
(30GN040,045 with optional brine only).
Thermistors— All thermistors are identicalin their tem-
perature vs. resistance performance. Resistance at various temperatures are listed in Tables 17 and 18.
LOCATION — General location of thermistor sensors are
shown in Fig. 14.
Cooler Leaving Fluid Thermistor (T1) — T1 is located in
leaving fluid nozzle. The probe is immersed directly in the
fluid. All thermistor connections are made through a1⁄4-in.
coupling. See Fig. 16. Actual location is shown in Fig. 14
and 15.
Cooler Entering Fluid Thermistor (T2) — T2 is located in
cooler shell in first baffle space near tube bundle. Thermistor
connection is made through a1⁄4-in. coupling. See Fig. 16.
Actual location is shown in Fig. 14 and 15.
Compressor Suction Gas Temperature Thermistors (T7 and
T8) — T7 and T8 are located in lead compressor in each
circuit in suction passage between motorandcylinders,above
oil pump. They are well-type thermistors. See Fig. 14
and 15.
THERMISTOR REPLACEMENT (T1, T2, T7, T8)
Thermistors are installed directly in fluid Relieve allpressure using standard practices or drain fluid before removing.
Proceed as follows (see Fig. 16):
To replace thermistor sensor T2:
1. Remove and discard original thermistor and coupling.
IMPORTANT: Do not disassemble new coupling.
Install as received.
2. Apply pipe sealant to1⁄4-in. NPT threads on replacement
coupling and install in place of original. Do not use packing nut to tighten coupling. This damages ferrules (see
Fig. 16).
3. Insert new thermistor in coupling body to its full depth.
If thermistor bottoms out beforefulldepth is reached, pull
thermistor back out
Hand tighten packing nut to position ferrules, then finish
tightening 11⁄4turns with a suitabletool. Ferrules are now
attached to thermistor whichcan be withdrawn fromcou-
pling for unit servicing.
To replace thermistors T1, T7, and T8:
Add a small amount of thermal conductive grease to ther-
mistor well. Thermistors are friction-fit thermistors, which
must be slipped into well located in the compressor pump
end.
1
⁄8in. before tightening packing nut.
57
Page 58
Table 17 — Thermistor Temperature (°F) vs Resistance/Voltage Drop; Flotronic™ II
Fig. 14 — Thermistor and Pressure Transducer Locations
Pressure Transducers — A single style of pressure
transducer is used for both high- and low-pressure sensing
on Flotronic™ II chillers. However, this transducer must be
calibrated before the unit will operate. On new units, this
will have been done at the factory in order to test run the
unit. If a transducer or PSIO is replaced in the field, however, the transducer will have to be field calibrated as
follows:
1. Disconnect transducer from the system.
2. Hang the transducer in the atmosphere.
3. Presson the HSIO keypad, and Read the pressure. Pressures before calibration must be within the
range of 6 5 psig. If the pressure is outside the range of
6 5 psig, the HSIO display will read ---. If this is the
case, replace the transducer or PSIO or check for a wiring error.Ifthe value of the atmospheric pressure is greater
than 5 psig or less than –5 psig, the transducer will be
considered out of range and will not calibrate.
4. Presson the HSIO keypad. This automatically applies the proper correction factor to all future inputsfrom
the transducer.
Three pressure transducers are mountedon each lead compressor: 2 low-pressure transducers to monitor compressor
suction pressure and oil pressure, and a high-pressure transducer to monitor compressor discharge pressure (see
Fig. 17 for exact locations on compressor). Each transducer
is supplied with 5 vdc power from a rectifier which changes
24 vac to 5 vdc.
TROUBLESHOOTING — If transducer is suspected of being faulty, first check supply voltage to transducer. Supply
voltage should be 5 vdc ± .2 v. If supply voltage is correct,
compare pressure reading displayed on keypad and display
module against pressure shown on acalibratedpressure gage.
If the 2 pressure readings are not reasonably close, replace
pressure transducer.
60
Page 61
Fig. 15 — Thermistor Locations
(Circuits A and B, Lead Compressor Only)
FLUID-SIDE TEMPERATURE THERMISTOR T2
(ALL UNITS)
Fig. 16 — Thermistors
61
COMPRESSOR SUCTION GAS TEMPERATURE
(ALL UNITS) AND FLUID-SIDE TEMPERATURE
THERMISTORS T7 AND T8
THERMISTOR T1 (ALL UNITS)
Page 62
Fig. 17 — Lead Compressor Transducer and Thermistor Locations
TRANSDUCER REPLACEMENT
Transducers are installed directly in the refrigerant circuit. Relieve all refrigerant pressure using standard refrigeration practices before removing.
1. Relieve refrigerant pressure using standard refrigeration
practices.
2. Disconnect transducer wiring at transducer by pulling up
on locking tab while pullingweathertightconnection plug
from end of transducer. Do not pull on transducer wires.
3. Unscrew transducer from
1
⁄4-in. male flare fitting. When
installing new pressure transducer, do not use thread
sealer. Thread sealer can plug transducer and render it
inoperative.
4. Insert weathertight wiring plug into end oftransducer until locking tab snaps in place.
5. Check for refrigerant leaks.
62
Page 63
Control Modules
Turn controller power off before servicing controls. This
ensures safety and prevents damage to controller.
PROCESSOR MODULE (PSIO), 4 IN/4 OUT MODULE
(SIO), LOW-VOLTAGE RELAY MODULE (DSIO-LV),
AND EXV DRIVER MODULE (DSIO-EXV)—The PSIO,
DSIO and SIO modules all perform continuous diagnostic
evaluations of the condition of the hardware. Proper operation of these modules is indicated by LEDs (light-emitting
diodes) on the front surface of the DSIOs, and on the top
horizontal surface of the PSIO and SIO.
RED LED — Blinking continuously at a 3- to 5-second rate
indicates proper operation. Lighted continuously indicates a
problem requiring replacement of module. Off continuously
indicates power should be checked. Ifthereis no input power,
check fuses. If fuse is bad, check for shorted secondary of
transformer or for bad module. On the PSIO module, if the
light is blinking at a rate of twice per second, the module
should be replaced.
GREEN LED — On a PSIO and an SIO, this is the green
LED closest toCOMM connectors. The othergreen LED on
module indicates external communications, when used. Green
LED should always be blinking when power is on. It indicates modules are communicating properly. If green LED is
not blinking, check red LED. If red LED is normal, check
module address switches. See Fig. 18. Proper addresses are:
If all modules indicate communication failure,checkCOMM
plug on PSIO module for proper seating. If a good connection is assured and condition persists, replace PSIO module.
If only DSIO or SIO moduleindicatescommunication failure, check COMM plug on that mode for proper seating. If
a good connection is assured and condition persists, replace
DSIO or SIO module.
All system operating intelligence rests in PSIO module,
the module that controls unit. This module monitors conditions through input and outputports and through DSIO modules (low-voltage relay module and EXV driver module).
The machine operator communicates with microprocessor through keypad anddisplay module. Communication between PSIO and other modules is accomplished by a 3-wire
sensor bus. These 3 wires run in parallel from module to
module.
On sensor bus terminal strips, terminal 1 of PSIO module
is connected to terminal 1 of each of the other modules.
Terminals 2 and 3 are connected in the same manner. See
Fig. 19. If a terminal 2 wire is connected to terminal 1, system does not work.
In Flotronic™ II chillers, processor module, low-voltage
relay module, and keypad and display module are all powered from a common 21-vac power source which connects
to terminals 1 and 2 of power input strip on each module.A
separate source of 21-vac power is used to power options
module through terminals 1 and 2 on power input strip. A
separate source of 12.5 vac power is used to power EXV
driver module through terminals 1 and2on power input strip.
Fig. 18 — Module Address
Selector Switch Locations
63
Page 64
Fig. 19 — Sensor Bus Wiring
(Communications)
PROCESSOR MODULE (PSIO) (Fig. 20)
Inputs — Each input channel has 3 terminals; only 2 of the
terminals are used. Application of machine determines which
terminals are used. Always refer to individual unit wiring
for terminal numbers.
Outputs — Output is 24 vdc. There are 3 terminals, only 2
of which are used, depending on application. Refer to unit
wiring diagram.
NOTE:Address switches (see Fig. 20) mustbe set at 01 (different when CCN connected).
LOW VOLTAGE RELAY MODULE (DSIO-LV) (Fig. 21)
Inputs — Inputs on strip J3 are discrete inputs (ON/OFF).
When 24-vac power is applied across the 2 terminals in a
channel it reads as on signal. Zero v reads as an off signal.
Outputs — Terminalstrips J4 and J5 are internal relayswhose
coils are powered-up and powered-off by a signal from
microprocessor. The relays switch the circuit to which they
are connected. No power is supplied to these connectionsby
DSIO module.
4 IN/4 OUT MODULE (SIO) (Fig. 22) — 4 In/4 Out module allows the following features to be utilized:
1. Temperature Reset by outdoor air or space temperature.
A remote thermistor (Part No. 30GB660002) is also required.
NOTE: This accessory is not required for return water
temperature reset.
2. Temperature Reset by remote 4 to 20 mA signal.
3. Demand Limit by remote 2-stage switch.
4. Demand Limit by remote 4 to 20 mA signal
5. Dual Set Point by remote switch.
The options module is standard. Remember to reconfigure the chiller for each feature selected (see Table 14). For
temperature reset, demand limit, and dual set point, desired
set points must be entered through keypad and display module (see Set Point Function section on page 38).
See Table 19 for overall troubleshooting information.
PWR — Power
Fig. 20 — Processor Module (PSIO)
ACCESSORY UNLOADER INSTALLATION
Some of the 30G Flotronic™ II units come standard with
unloader(s), and many permit additional unloader(s) to be
added if desired. See Table 20.
IMPORTANT:The following combinationsARE NOT
permitted (combinations are per circuit):
1. Two unloaders and hot gas bypass
2. Four compressors and 2 unloaders.
3. Four compressors, 1 unloader, and hot gas
bypass.
COMM — Communications Bus
NC— Normally Closed
Fig. 21 — Low-Voltage Relay Module (DSIO)
64
LEGEND
NO— Normally Open
PWR — Power
Page 65
COMM — Communications Bus
PWR— Power
LEGEND
Fig. 22 — 4 In/4 Out Module (SIO)
If accessory unloaders are desired, an accessory unloader
package is used. Package includes a suction cutoff unloader
head package. The 24-v coil in the package can be used
for 040-110, 130 (60 Hz), and associated modular units
(Table 1). A 115 v or 230 v coil must be used for 130
(50 Hz), 150-210, and associated modular units (Table 1).
Coil voltage depends on control circuit voltage. Consult current Carrier price pages for appropriate part numbers.
NOTE:The accessory package will include all necessary components and wiring with the following exceptions: The field
must provide screws, and on the 130-210, and associated modular units, the field must also supply a 20 vdc (part number
HK35AB001) unloader relay and wire (90° C or
equivalent).
Installation
1. Be sure all electrical disconnectsare open and tagged be-
fore any work begins. Inspect the package contents for
any damage during shipping. File a claim with the shipper if damage has occurred.
2. For ease of installation, factory-supplied wiring for the
additional unloader is provided in the compressor
harness.
3. Install the additional unloader cylinder head on the lead
compressor,A1 or B1, according to instructions provided
by the compressor manufacturer in the accessory
package.
4. Continue installation per either 040-110, 130 (60 Hz) units
or 130 (50 Hz), 150-210 units section as appropriate.
1. Wire the solenoid before any field wiring begins. Wiring
between components and control box must be enclosed
in conduit. All local electrical codes and National Electrical Code (NEC) must be followed. Factory wires are
provided in the compressor harness to connect the solenoid. These wires are in the compressor control box.
2. Wire the control side. Open the left side control box door
and remove inner panel. Using the holes provided and
field-supplied screws,installfield-suppliedtransformerabove
the DSIO-LV on the control panel.
Wire the primary side of the transformer in parallel with
TRAN4. See Fig. 23. This supplies transformer with proper
line voltage. Be sure to connect proper tap of the transformer to ensure supply of proper secondary voltage.
Wirethesecondary side of transformer to DSIO-LV- J5-9,
and a jumper from DSIO-LV - J5-9 to DSIO-LV - J4-9.
Wirethe secondary common to TB7-2. Connect thetransformer ground to ground hole supplied near the transformer. These connections provide DSIO with necessary
power to energize the solenoid coils.
3. When all connections are made, check for proper wiring
and tight connections. Replace and secure inner panel.
Restore power to unit.
4. Configure the processor. With the addition of extra unloaders, the unit configuration has changed. To change
the configuration of the processor, enter the service function using the keypad and display module. Before any
changes can be made, the LOCAL/ENABLE-STOPCCN switch must be in the STOP position, and the servicer must log on to the processor.
a. Press. Keypad LCD displays the word
PASSWORD.
b. Enter. Keypad LCD displays
LOGGEDON.
c. To change configuration, press. Keypad LCD
displays FLD CFG.
d. If an additional unloader was added to compressor
A1, pressuntil NULA 1 appears in keypad display. Pressfor the number of unloaders on
circuit A. Keypad display now reads NULA 2.
e. If an additional unloader was added to compressor
B1, pressuntil NULB 1 appears in keypad display. Pressfor the number of unloaders on
SYSTEM NOISESPiping vibrationSupport piping as required.
COMPRESSOR LOSES OILLeak in systemRepair leak.
FROSTED SUCTION LINEExpansion valve admitting either too
HOT LIQUID LINEShortage of refrigerant due to leakRepair leak and recharge.
FROSTED LIQUID LINEShutoff valve partially closed or restrictedOpen valve or remove restriction.
COMPRESSOR DOES NOT
UNLOAD
COMPRESSOR DOES NOT
LOAD
EXV — Electronic Expansion Valve
Power line openReset circuit breaker.
Control fuse openCheck control circuit for ground or short.
High-Pressure Switch (HPS)
tripped
Tripped power breakerCheck the controls. Find cause of trip
Loose terminal connectionCheck connections.
Improperly wired controlsCheck wiring and rewire.
Low line voltageCheck line voltage. Determine location
Compressor motor defectiveCheck motor winding for open or short.
Seized compressorReplace compressor.
Loss of chargeRepair leak and recharge.
Bad transducerReplace transducer.
Low refrigerant chargeAdd refrigerant.
High-pressure control erratic in actionReplace control.
Compressor discharge valve partially closedOpen valve or replace if defective.
Condenser fan(s) not operatingCheck wiring. Repair or replace motor(s)
Condenser coil plugged or dirtyClean coil.
Low refrigerant chargeAdd refrigerant.
Control contacts fusedReplace control.
Partially plugged or plugged expansion
valve or filter driver
Defective insulationReplace or repair.
Service loadKeep doors and windows closed.
Inefficient compressorCheck valves. Replace if necessary.
Expansion valve hissingAdd refrigerant.
Compressor noisyCheck valve plates for valve noise.
Mechanical damage (blown piston or
broken discharge valve)
Crankcase heaters not energized
during shutdown
much or too little refrigerant
Burned out coilReplace coil.
Defective capacity control valveReplace valve.
Miswired solenoidRewire correctly.
Weak, broken, or wrong valve body springReplace spring
Miswired solenoidRewire correctly.
Defective capacity control valveReplace valve.
Plugged strainer (high side)Clean or replace strainer.
Stuck or damaged unloader piston or
piston ring(s)
Replace fuse.
Move LOCAL/ENABLE-STOP-CCN switch to STOP
position then back to RUN or CCN position.
and reset breaker.
of voltage drop and remedy deficiency.
Replace compressor if necessary.
if defective.
Clean or replace.
Check for plugged liquid line filter drier.
Replace compressor (worn bearings).
Check for loose compressor holddown bolts.
Repair damage or replace compressor.
Replace heaters, check wiring and
crankcase heater relay contacts.
Check cooler and compressor thermistors.
Test EXV.
Clean or replace the necessary parts.
Table 20 — Standard and Accessory Unloaders
NO. OF ACCESSORY
UNIT
30GN040-070111or2
30GN080-170*211
30GN190-210*011
*And associated modular units.
NO. OF STANDARD
UNLOADER(s)
UNLOADERS
PERMITTED
Circuit ACircuit B
66
Page 67
5. Using test function,check unloaders. Press. Keypad display reads OUTPUTS. Pressuntil display
reads UNA2 OFF. Press. Relay energizes. Press
and relay deenergizes. Pressuntil display reads
UNB2 OFF. Press. Relay energizes. Press
and relay deenergizes.
6. When unloader check has been performed,returnLOCAL/
ENABLE-STOP-CCN to proper position. Close and secure control box door.
130 (50 Hz), 150-210 UNITS (AndAssociatedModular Units)
1. Install control wiring. The minimum wire size for installation is 16 AWG (American Wire Gage). Refer to
Fig. 23 and 24 for proper wiring. Open the control box
door. Locate unloader relaysA and B (UA, UB) in place
of the hot gas bypass relays as shown on the component
arrangement diagram on the unit. Mount the relays with
the field-supplied screws. Be careful not to damage the
components and wiring in the area when mounting the
relays.
2. Wire the control side. Wire the UA coil in series between
J6-18 and J6-19 of the4 IN/4 OUT module with thewires
provided. Wire the UB coil in series between J6-21 and
J6-22 of the same module with the wires provided.
Locate the black wire in the control harness originating
from TRAN5 labeled HGBPR-A-COM. Connect this wire
to the UAterminal COM. Connect the wire labeled HGBPRA-NO to UA-NO. Connect the wire from UA-NO to
TB3-5. For an extra unloader on circuit B, connect the
wire labeled HGBPR-B-COM to UR-B-COM, and the wire
labeled HGBPR-B-NO to UB-NO. Connectthewire from
UB-NO to TB3-6.
3. Wire in the solenoid valves.
NOTE: Wires external to the control box must be run in
conduit.
Terminal blocks are provided for easy field wiring. Use
one of the isolated
7
⁄8-in. (22-mm) holes in the side of the
compressor electrical box with a strain relief to run the
wires to the solenoid coil. Connect UA between TB3-5
andTB3-8. Connect UB between TB3-6 and TB3-8. Check
all of the electrical connections for proper location and
tightness, and replace and secure the electrical box of the
compressor.
4. Configure the microprocessor.Once the relays are mounted
in the control box, the microprocessor must be configured for the unloader option. To do so:
a. Be sure the LOCAL/ENABLE-STOP-CCN switch is
in the STOP position.
b. Log into the processor and enter the service func-
tion usingthekeypadand displaymodule.
Press. The keypadLCD will display
‘‘PASSWORD.’’ Enter, and the
keypad LCD will display ‘‘LOGGEDON.’’
c. To change the configuration, press, and the
keypad LCD will display ‘‘FLD CFG.’’ Press
until either ‘‘NULA 0’’ or ‘‘NULA 1’’ is displayed
(depending on the number of unloaders provided as
standard). Then press(for 1 unloader on A1)
or(for 2 unloaders on compressor A1). The
display will now read either ‘‘NULA 1’’ or
‘‘NULA 2,’’ as appropriate. Pressto get to the
NULB display,andchangethissetting in the same manner as with circuit A.
d. Once the configuration is complete, press,
and the keypad LCD will display ‘‘LOGGEDON,’’
Pressuntil the keypad LCD display reads ‘‘LOG
OFF.’’ Pressand the keypad LCD will display
‘‘EXIT LOG.’’
5. Once theunloader heads are installed, the unit is checked
for leaks, and the system is prepared for operation per the
instructions for the compressor unloader head installation, check theoutput of the relays using the testfunction
as follows:
a. Press, and the display will read ‘‘COMP.’’
b. Press theto scroll down until the display reads
‘‘CPA1 OFF.’’
c. Press, and the compressor should start.
d. Press, and the compressor should stop.
e. Pressuntil the display reads ‘‘UNA1 OFF.’’
f. Press, and the solenoid should energize.
g. Pressand the solenoid should deenergize.
h. Use theandkeys to check the remainder of
the unloader coils.
6. Once the check has been performed, return the LOCAL/
ENABLE-STOP-CCN switch to the proper position.
7. Close and secure the control box door.
8. Start the unit and confirm that the chiller operates
properly.
67
Page 68
LEGEND
C—ContactorPWR — Power
CB— Circuit BreakerSW— Switch
COMM — Communications BusTRAN — Transformer
HGBPR — Hot Gas Bypass RelayU—Unloader
Fig. 23 — Accessory Unloader Control Wiring, All Units
*Or HGBPR-A.
†Or HGBPR-B.
COM— Communications BusTB— Terminal Block
HGBPR — Hot Gas Bypass RelayTRAN — Transformer
NO— Normally OpenU—Unloader
SNB— Snubber
LEGEND
Fig. 24 — Flotronic™ II 115/230-V (Unloader Wiring, 130 (50 Hz), 150-210 and Associated Modular Units
(See Table 1)
68
Page 69
FIELD WIRING
Refer to Fig. 25-35 for field wiring.
NOTE: Contacts must be rated for dry circuit application, capable of
reliably switching a 5 vdc, 1 mA to 20 mA load.
Fig. 25 — Demand Limit — Two External
Switch Inputs
Fig. 26 − Demand Limit — 4-20 mA Signal
(Externally Powered)
Fig. 27 — Demand Limit — 4-20 mA Signal
(Internally Powered)
Fig. 28 — Remote Reset from Space or
Outdoor-Air Temperature
Fig. 30 — Remote Reset from 4-20 mA Signal
(Internally Powered)
TB — Terminal Block
NOTE: Contacts must be rated for dry circuit application, capable of
reliably switching a 5 vdc, 1 mA to 20 mA load.
Fig. 31 — Remote On/Off
Fig. 32 — Remote Dual Set Point Control
Fig. 29 — Remote Reset from 4-20 mA Signal
(Externally Powered)
CWP — Chilled Water (Fluid) Pump
TB— Terminal Block
Fig. 33 — Chilled Fluid Pump
69
Page 70
TB — Terminal Block
Fig. 34 — Remote Alarm
CWP1 — Chilled Water (Fluid) Pump Interlock
CWFS — Chilled Water (Fluid) Flow Switch (not required — low flow
TB— Terminal Block
protection is provided by Flotronic™ II controls)
Fig. 35 — Interlocks
REPLACING DEFECTIVE
PROCESSOR MODULE
The replacement part number is printed on a small label
on the front of the PSIO module. The model and serial numbers are printed on the unit nameplate located on an exterior
corner post. The proper software and unit configuration data
is factory installed by Carrier in the replacement module.
Therefore, when ordering a replacement processor module
(PSIO), specify complete replacement part number, full unit
model number, and serial number. If these numbers are not
provided, the replacement module order is configured instead as a generic Flotronic II replacement module. This requires reconfiguration of the module by the installer.
Electrical shock can cause personal injury. Disconnect
all electrical power before servicing.
Installation
1. Verify the existing PSIO module is defective by using
the procedure described in the Control Modules section
on page 63.
2. Refer to Start-Up Checklist for Flotronic II Chiller Systems (completed at time of original start-up) found in
job folder. This information is needed later in this
procedure. If checklist doesnot exist, fill out the
andconfiguration code sectionsona new check-
list.Tailor the various options and configurations as needed
for this particular installation.
3. Check that all power to unit is off. Carefully disconnect
all wires from defective module by unpluggingthe6connectors. It is not necessary to remove any of the individual wires fromtheconnectors.Removethegreenground
wire.
4. Remove defective PSIO by removing its mounting screws
with a Phillips screwdriver, and removing the module
from the control box. Save the screws for later use.
5. Use a small screwdriver to set address switches S1 and
S2 on the new PSIO module to exactly match the settings on the defective module.
6. Package the defective module in the carton of the new
module for return to Carrier.
7. Mount the new module in the unit control box using a
Phillips screwdriver and the screws saved in Step 4 above.
8. Reinstall all 6 wire connectorsandthegreen ground wire.
9. Carefully check all wiring connections before restoring
power.
10. Verify the LOCAL/ENABLE-STOP-CCN switch is in
STOP position.
11. Restore control power. Verify the red and green lights
on top of PSIO and front of each DSIO module respond
as described in Control Modulessection on page 63. The
keypad and display module should also begin its rotating display.
12. Using the keypad and display module, press
to verify that the software version number matches the
ER (engineering requirement) number shown on the PSIO
label.
13. Pressto verify that the 7 factory configuration
codes (CODE 1 through CODE 7) exactly match the codes
listed for this unitmodel on the component arrangement
label diagram on the control box door. If they are different or are all zeros,reenter the 7 codes. If any changes
are required, the PSIO display becomes blank and
reconfigures itself after pressing thekey while displaying CODE 7. The display returns in approximately
15 seconds.
NOTE: Codes with leading zeros in the configuration
will be displayed starting with the first number greater
than zero.
14. Pressto verify eachitemis configured as needed
for this particular installation. Table 14 shows the fac-
tory configuration code default settings. Table 14 also
shows the service replacement code default settings which
are used if no model number was specified when ordering the replacement PSIO module. It is strongly suggested that the Start-Up ChecklistforFlotronic II Chiller
Systems (completed attime of original start-up) be used
at this time to verify and/or reprogram the various options and configurations required for this job.
15. Pressto verify that the 2 field configuration
codes (codes 8 and 9) match exactly the codes listed on
the label diagram on the control box door. If they are
different, or are all zeros, reenter the 2 codes.
16. After completing theconfigurationsteps outlined above,
restore main power and perform a unit test as de-
scribed inandsections on page 38.
17. Complete this procedure and restore chiller to normal
operation by returning the LOCAL/ENABLE-STOPCCN switch to desired position.
70
Page 71
Page 72
Copyright 1995 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 2
Tab 5c
PC 903Catalog No. 563-079Printed in U.S.A.Form 30GN-3TPg 727-95Replaces: 30G-1T
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.