Carrier FLOTRONIC II 30GN040-420 User Manual

Flotronic™ II Reciprocating Liquid Chillers
Controls, Operation, and
Troubleshooting
with Microprocessor Controls and Electronic Expansion Valves
CONTENTS
Page
SAFETY CONSIDERATIONS ..................2
GENERAL ...................................2
MAJOR SYSTEM COMPONENTS ............2-5
Electronic Expansion Valve Module ...........4
Options Module .............................4
Keypad and Display Module
(Also Called HSIO or LID) ..................4
Control Switch ..............................4
Electronic Expansion Valve (EXV) ............4
Thermostatic Expansion Valves (TXV) ........4
Sensors .....................................5
Compressor Protection Control
Module (CPCS) ............................5
OPERATION DATA ..........................5-46
Head Pressure Control ......................24
• EXV UNITS
• TXV UNITS
Pumpout ...................................24
• EXV UNITS
• TXV UNITS
Keypad and Display Module
(Also Called HSIO or LID) .................24
• ACCESSING FUNCTIONS AND SUBFUNCTIONS
• AUTOMATIC DEFAULT DISPLAY
• AUTOMATIC DISPLAY OPERATION/DEFAULT
DISPLAY
• KEYPAD OPERATING INSTRUCTIONS
• STATUS FUNCTION
• TEST FUNCTION
• HISTORY FUNCTION
• SET POINT FUNCTION
• SERVICE FUNCTION
• SCHEDULE FUNCTION
TROUBLESHOOTING ......................47-64
Checking Display Codes ....................47
30GN040-420
50/60 Hz
Page
Unit Shutoff ................................48
Lag Compressor Stoppage ..................48
Restart Procedure ..........................48
• POWER FAILURE EXTERNAL TO THE UNIT
Alarms and Alerts ..........................48
Compressor Alarm/Alert Circuit .............50
Electronic Expansion Valve (EXV) ...........55
• EXV OPERATION
• CHECKOUT PROCEDURE
Thermostatic Expansion Valve (TXV) .........57
• LOCATION
• THERMISTOR REPLACEMENT (T1, T2, T7, T8)
Pressure Transducers ......................60
• TROUBLESHOOTING
• TRANSDUCER REPLACEMENT
Control Modules ............................63
• PROCESSOR MODULE (PSIO), 4IN/4OUT MODULE (SIO), LOW-VOLTAGE RELAY MODULE (DSIO-LV), AND EXV DRIVER MODULE (DSIO-EXV)
• RED LED
• GREEN LED
• PROCESSOR MODULE (PSIO)
• LOW-VOLTAGE RELAY MODULE (DSIO)
• 4IN/4OUT MODULE (SIO)
ACCESSORY UNLOADER INSTALLATION . . . 64-68
Installation .................................65
• 040-110, 130 (60 Hz) UNITS (And Associated Modular Units)
• 130 (50 Hz), 150-210 UNITS (And Associated Modular Units)
FIELD WIRING .............................69,70
REPLACING DEFECTIVE PROCESSOR
MODULE (PSIO) ..........................70
Installation .................................70
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 2 Tab 5c
PC 903 Catalog No. 563-079 Printed in U.S.A. Form 30GN-3T Pg 1 7-95 Replaces: 30G-1T
SAFETY CONSIDERATIONS
Installing, starting up, and servicing this equipment can be hazardous due to system pressures, electrical compo­nents, and equipment location (roof, elevatedstructures,etc.). Only trained, qualified installers and service mechanics should install, start up, and service this equipment.
When working on this equipment, observe precautions in the literature, and ontags, stickers, and labelsattached to the equipment, and any other safety precautions that apply. Fol­low all safety codes. Wear safety glasses and work gloves. Use care in handling, rigging, and setting this equipment, and in handling all electrical components.
Electrical shock can cause personal injury and death. Shut off all power to this equipment during installation and service. There may be more than one disconnect switch. Tag all disconnect locations to alert others not to restore power until work is completed.
This unit uses a microprocessor-based electronic con­trol system. Do not use jumpers or other tools to short out components, or to bypass or otherwise depart from recommended procedures. Any short-to-ground of the control board or accompanying wiring may destroy the electronic modules or electrical components.
GENERAL
IMPORTANT: This publication contains controls, op­eration and troubleshooting data for 30GN040-420 Flotronic™ II chillers.
Circuits are identified as circuitsAand B, and com­pressors are identified as A1,A2, etc. in circuit A, and B1, B2, etc. in circuit B.
Use this guide in conjunction with separate Instal­lation Instructions booklet packaged with the unit.
The 30G Series standard Flotronic II chillers feature microprocessor-based electronic controls and an electronic expansion valve (EXV) in each refrigeration circuit.
NOTE: The 30GN040 and 045 chillers with a factory­installed brine option have thermal expansion valves (TXV) instead of the EXV.
Unit sizes 230-420 are modular units which are shipped as separate sections (modulesAand B). Installation instruc­tions specific to these units are shipped inside the individual modules. See Table 1 for a listing of unit sizes and modular combinations. For modules 230B-315B, follow all general instructions as noted for unit sizes 080-110. For all remain­ing modules, follow instructions for unit sizes 130-210.
Table 1 — Unit Sizes and Modular Combinations
UNIT MODEL
30GN
040 40 045 45 050 50 060 60 070 70 080 80 090 90 100 100 110 110 130 125 150 145 170 160 190 180 210 200 230 220 150 080 245 230 150 090 255 240 150 100 270 260 170 100 290 280 190 110 315 300 210 110 330 325 170 170 360 350 190 190/170* 390 380 210 190 420 400 210 210
*60 Hz units/50 Hz units.
NOMINAL
TONS
SECTION A UNIT 30GN
SECTION B
UNIT 30GN
The Flotronic II control system cycles compressor un­loaders and/or compressors to maintain the selected leaving fluid temperature set point. It automatically positions theEXV to maintain the specified refrigerant superheat entering the compressor cylinders. It also cycles condenser fans on and off to maintain suitable head pressure for each circuit. Safe­ties are continuously monitored to prevent the unit from op­erating under unsafe conditions. A scheduling function, pro­grammed by the user, controls the unit occupied/unoccupied schedule. The control also operates a test program that al­lows the operator to check output signals and ensure com­ponents are operable.
The control system consists ofaprocessor module (PSIO), a low-voltage relay module (DSIO-LV), 2 EXVs, an EXV driver module (DSIO-EXV), a 6-pack relay board, a keypad and display module (also called HSIO or LID), thermistors, and transducers to provide inputs to the microprocessor. A standard options module (SIO) is used to provide additional functions. See Fig. 1 for a typical 30GN Control Panel.
MAJOR SYSTEM COMPONENTS
Processor Module —
ating software and controls the operation of the machine. It continuously monitors information received from the vari­ous transducers and thermistors and communicates with the relay modules and 6-pack relay board to increase or de­crease the active stages of capacity. The processor module
This module contains the oper-
2
COMM 3 PWR
POINT NUMBER
OF
FIRST CHANNEL
COMM 1
PWR
COMM 3
S1 S2
XX
XX
STAT EXPN
HIST CLR SCHD
SRVC SET
TEST ENTR
STATUS
COMM
J4 J4
789 456 123 –
0•
STATUS
J5
COMM
LVEXV
FUSE 1
S
U
E
F
F
E
U
S
S
U
E
F
FUSE 2
GFI - CO
( 5 AMP MAX )
LOCAL/ ENABLE
STOP
CCN
CB5
CB6
12
3+
5VDC
HK35AA002
Potter & Brumfield
CZ770
SW1
FUSE 3
30GT510568 –
4-
EQUIP GND
99NA505322 D
LEGEND
CCN — Carrier Comfort Network TB Terminal Block
Fig. 1 — 30GN Control Panel (040-110 Unit Shown)
3
also controls the EXV driver module (as appropriate), com­manding it to open or close each EXV in order to maintain the proper superheat entering thecylinders of each lead com­pressor.Information istransmittedbetweentheprocessormod­ule and relay module, the EXV driver module, and the key­pad and display module through a 3-wire communications bus. The options module is also connected to the commu­nications bus.
For the Flotronic™ II chillers,the processor monitors sys­tem pressure by means of 6 transducers, 3 in each lead com­pressor.Compressorsuctionpressure, discharge pressure, and oil pressure are sensed. If the processor senses high dis­charge pressure or low suction pressure,it immediately shuts down all compressors in the affected circuit. During opera­tion, if low oil pressure is sensed for longer than one minute, all compressors in the affected circuit are shut down. At start­up, the oil pressure signal is ignored for 2 minutes. If shut­down occurs due to any of these pressure faults, the circuit is locked out and the appropriate fault code is displayed.
Low-Voltage Relay Module — This module closes
contacts to energize compressor unloaders and/or compres­sors. It also senses the status of the safeties for all compres­sors and transmits this information to the processor.
Electronic Expansion Valve Module (If So Equipped)—
cessor and operates the electronic expansion valves.
This module receives signals fromthe pro-
Options Module — This module allows the use of Flo-
tronic II features such as dual set point, remote reset, de­mand limit, hot gas bypass, and accessory unloaders. The options module also allows for reset and demand limit to be activated from a remote 4-20 mA signal. The options mod­ule is installed at the factory.
Keypad andDisplay Module (Also Called HSIO or LID) —
tion keys, 5 operative keys, 12 numeric keys, and an alpha­numeric 8-character LCD (liquid crystal display). Key us­age is explained in Accessing Functions and Subfunctions section on page 24.
This device consists of a keypad with 6 func-
Control Switch — Control of the chiller is defined by
the position of the LOCAL/ENABLE-STOP-CCN switch. This is a 3-position manual switch that allows the chiller to be put under the control of its own FlotronicIIcontrols,manu­ally stopped, or put under the control of a Carrier Comfort Network (CCN). Switch allows unit operation as shown in Table 2.
In the LOCAL/ENABLE position, the chiller is under lo­cal control and responds to the scheduling configuration and set point data input at its own local interface device (keypad and display module).
Table 2 — LOCAL/ENABLE-STOP-CCN
Switch Positions and Operation
SWITCH
POSITION
STOP Unit Cannot Run Read/Write Read Only LOCAL/ENABLE Unit Can Run Read/Limited Write Read Only CCN Stop — Unit Cannot Run Read Only Read/Write
Run — Unit Can Run Read Only
UNIT
OPERATION
CONFIGURATION AND
SET POINT CONTROL
Keypad Control CCN Control
Read/Limited Write
In the CCN position, the chiller is under remote control and responds only to CCN network commands. The occupied/ unoccupied conditions are defined by the network. All key­pad and display functions can be read at the chiller regard­less of position of the switch.
CCN run or stop condition is established by a command from the CCN network. It is not possible to force outputs from the CCN network, except that an emergency stop com­mand shuts down the chiller immediately and causes ‘ ‘ALARM 52’’ to be displayed.
Electronic Expansion Valve (EXV) — The micro-
processor controls the EXV (if so equipped) throughtheEXV driver module. Inside the expansion valve is a linear actua­tor stepper motor.
The lead compressor in each circuit has a thermistor and a pressure transducer located in the suction manifold after the compressor motor. The thermistor measures the tem­perature of the superheated gas entering the compressor cyl­inders.Thepressuretransducermeasurestherefrigerant pressure in the suction manifold. The microprocessor converts the pres­sure reading to a saturated temperature. The difference be­tween the temperature of the superheated gas and the satu­ration temperature is the superheat.Themicroprocessorcontrols the position of the electronic expansion valve stepper motor to maintain 30 F (17 C) superheat.
At initial unit start-up, the EXV position is at zero. After that, the microprocessor keeps accurate track of the valve position in order to usethis information as input for theother control functions. The control monitors the superheat and the rate of change of superheat to control the position of the valve. The valve stroke is very large, which results in very accurate control of the superheat.
Thermostatic Expansion Valves(TXV) — Model
30GN040 and 045 units with factory-installed brine option are equipped with conventional thermostatic expansion valves with liquid line solenoids. The liquid line solenoid valves are not intended to be a mechanical shut-off. When service is required, use the liquid line service valve to pump down the system.
4
The TXV is set at the factory to maintain approximately 8 to 12° F (4.4to6.7° C) suction superheat leaving thecooler by monitoring the proper amount of refrigerant intothecooler. All TXVs are adjustable, but should not be adjusted unless absolutely necessary.When TXVis used,thermistorsT7 and T8 are not required.
The TXV is designed to limit the cooler saturated suction temperature to 55 F (12.8 C). This makes it possible for unit to start at high cooler fluid temperatures without overload­ing the compressor.
Sensors— The Flotronic™ II chillercontrolsystemgath-
ers information from sensors to control the operation of the chiller. The units use 6 standard pressure transducers and 4 standard thermistors to monitor system pressures and tem­peratures at various points within the chiller. Sensors are listed in Table 3.
Table 3 — Thermistor and Transducer Locations
Fig. 2 — Compressor Protection Control Module
Sensor Location
T1 Cooler Leaving Fluid Temp T2 Cooler Entering Fluid Temp T7 Compressor Suction Gas Temp Circuit A T8 Compressor Suction Gas Temp Circuit B T10 Remote Temperature Sensor (Accessory)
Sensor Location
DPT-A Compressor A1 Discharge Pressure SPT-A Compressor A1 Suction Pressure OPT-A Compressor A1 Oil Pressure DPT-B Compressor B1 Discharge Pressure SPT-B Compressor B1 Suction Pressure OPT-B Compressor B1 Oil Pressure
THERMISTORS
PRESSURE TRANSDUCERS
Compressor Protection ControlModule(CPCS)
Each compressor on models 30GN070 (50 Hz), 080-
110, and 230B-315B, has its own CPCS as standard equip­ment. See Fig. 2. All 30GN040-060 and 070 (60 Hz) units feature the CPCS as an accessory, and CR (control relay) as standard equipment. The 30GN130-210 and associated modu­lar units havea CR as standard equipment. The CPCS or CR is used tocontrol and protect the compressors and crankcase heaters. The CPCS provides the following functions:
• compressor contactor control
• crankcase heater control
• compressor ground current protection
• status communication to processor board
• high-pressure protection
The CR provides all of the same functions as the CPCS with the exception of compressor ground current protection. Ground current protection is accomplished by using a CGF (compressor ground fault module) in conjunction with the CR. The CGF (See Fig. 3) provides the same ground fault function as the CPCS for units where the CPCS is not utilized.
One large relay is located on the CPCS board. This relay (or CR) controls the crankcase heater and compressor contactor. The CPCS also provides a set of signal contacts that the microprocessor monitors to determine the operating status of the compressor. If the processor board determines that the compressor is notoperatingproperly through the sig­nal contacts, it will lock the compressor off by deenergizing the proper 24-v control relay on the relay board. The CPCS board contains logic that can detect if the current-to-
Fig. 3 — Compressor Ground Fault Module
ground of any compressor winding exceeds 2.5 amps. If this condition occurs, the CPCS module shuts down the compressor.
A high-pressure switch with a trip pressure of 426 ± 7 psig (2936 ± 48 kPa), is wired in series with the CPCS. If this switch opens during operation, the compressor stops and the failure is detected by the processor when the signal contacts open. The compressor islocked off. If the leadcom­pressor in either circuit is shut down by the high-pressure switch or ground current protector, all compressors in the circuit are locked off.
OPERATION DATA
Capacity Control —
compressor to give capacity control steps as shown in Tables 4A-4C. The unit controls leaving chilled fluid tem­perature. Entering fluid temperature is used by the micro­processor in determining the optimum time to add or sub­tract steps of capacity, but is not a control set point.
The chilled fluid temperature set point can be automati­cally reset by the return temperature reset or space and outdoor-air temperature reset features. It can also be reset from an external 4 to 20 mA signal, or from a network signal.
The operating sequences shown are some of many pos­sible loading sequences for the control of the leaving fluid temperature. If a circuit has more unloaders than another, that circuit will always be the lead circuit.
The control system cycles
5
Table 4A — Capacity Control Steps, 040-070
UNIT
30GN
040 (60 Hz)
A1†,B1
040 (60 Hz)
A1†,B1**
040 (50 Hz) 045 (60 Hz)
A1†,B1
040 (50 Hz) 045 (60 Hz)
A1†,B1**
040 (50 Hz) 045 (60 Hz)
A1†,B1**
045 (50 Hz) 050 (60 Hz)
A1†,B1
045 (50 Hz) 050 (60 Hz)
A1†,B1**
045 (50 Hz) 050 (60 Hz)
A1†**,B1
045 (50 Hz) 050 (60 Hz)
A1†**,B1**
045 (50 Hz) 050 (60 Hz)
A1†,B1**
*Unloaded compressor.
†Compressor unloader, standard.
**Compressor unloader(s), accessory.
††Two unloaders, both unloaded.
CONTROL
STEPS
1 25 A1* — 250A1— — 3 75 A1*, B1 — 4 100 A1,B1
1 25 A1* 25 B1* 250A1 50B1 3 75 A1*,B1 75 A1,B1* 4 100 A1,B1 100 A1,B1
1 24 A1* — 247A1— — 3 76 A1*,B1 — 4 100 A1,B1
1 24 A1* 37 B1* 247A1 53B1 3 61 A1*,B1* 61 A1*,B1* 4 76 A1*,B1 84 A1,B1* 5 100 A1,B1 100 A1,B1
1 21 B1†† 2 37 B1* 3— — 53B1 4 68 A1,B1†† 5 84 A1,B1* 6 100 A1,B1
1 31 A1* — 244A1— — 3 87 A1*,B1 — 4 100 A1,B1
1 31 A1* 38 B1* 244A1 56B1 3 69 A1*,B1* 69 A1*,B1* 4 87 A1*,B1 82 A1,B1* 5 100 A1,B1 100 A1,B1
1 18 A1†† — 2 31 A1* — 3 73 A1††,B1 — 4 87 A1*,B1 — 5 100 A1,B1
1 18 A1†† — 2 31 A1* — 344A1— — 4 56 A1††,B1* — 5 73 A1††,B1 — 6 87 A1*,B1 — 7 100 A1,B1
1 20 B1†† 2 38 B1* 3— — 56B1 4 51 A1*,B1†† 5 64 A1,B1†† 6 82 A1,B1* 7 100 A1,B1
LOADING SEQUENCE A LOADING SEQUENCE B
%
(Approx) (Approx)
Compressors
%
CompressorsDisplacement Displacement
6
Table 4A — Capacity Control Steps, 040-070 (cont)
UNIT
30GN
045 (50 Hz) 050 (60 Hz)
A1†**,B1**
050 (50 Hz) 060 (60 Hz)
A1†,B1
050 (50 Hz) 060 (60 Hz)
A1†,B1**
050 (50 Hz) 060 (60 Hz)
A1†**,B1
050 (50 Hz) 060 (60 Hz)
A1†**,B1**
050 (50 Hz) 060 (60 Hz)
A1†,B1**
050 (50 Hz) 060 (60 Hz)
A1†**,B1**
060 (50 Hz) 070 (60 Hz)
A1†,B1
060 (50 Hz) 070 (60 Hz)
A1†,B1**
060 (50 Hz) 070 (60 Hz)
A1†**,B1
060 (50 Hz) 070 (60 Hz)
A1†**,B1**
060 (50 Hz) 070 (60 Hz)
A1†,B1**
*Unloaded compressor.
†Compressor unloader, standard.
**Compressor unloader(s), accessory.
††Two unloaders, both unloaded.
CONTROL
STEPS
1 18 A1†† 20 B1†† 2 31 A1* 38 B1* 344A1 56B1 4 56 A1††,B1* 64 A1,B1†† 5 73 A1††,B1 82 A1,B1* 6 87 A1*,B1 100 A1,B1 7 100 A1,B1
1 28 A1* — 242A1— — 3 87 A1*,B1 — 4 100 A1,B1
1 28 A1* 38 B1* 242A1 58B1 3 67 A1*,B1* 67 A1*,B1* 4 87 A1*,B1 80 A1,B1* 5 100 A1,B1 100 A1,B1
1 15 A1†† — 2 28 A1* — 3 73 A1††,B1 — 4 87 A1*,B1 — 5 100 A1,B1
1 15 A1†† — 2 28 A1* — 342A1— — 4 53 A1,B1* — 5 73 A1††,B1 — 6 87 A1*,B1 — 7 100 A1,B1
1 18 B1†† 2 38 B1* 3— — 58B1 4 60 A1,B1†† 5 80 A1,B1* 6 100 A1,B1
1 15 A1†† 18 B1†† 2 28 A1* 38 B1* 342A1 58B1 4 53 A1††,B1* 60 A1,B1†† 5 73 A1††,B1 80 A1,B1* 6 87 A1*,B1 100 A1,B1 7 100 A1,B1
1 33 A1* — 250A1— — 3 83 A1*,B1 — 4 100 A1,B1
1 33 A1* 33 B1* 250A1 50B1 3 67 A1*,B1* 66 A1*,B1* 4 83 A1*,B1 83 A1,B1* 5 100 A1,B1 100 A1,B1
1 16 A1†† — 2 33 A1* — 3 66 A1††,B1 — 4 83 A1* — 5 100 A1,B1
1 16 A1†† — 2 33 A1* — 350A1— — 4 66 A1††,B1 — 5 83 A1*,B1 — 6 100 A1,B1
1 16 B1†† 2 33 B1* 3— — 50B1 4 66 A1,B1†† 5 83 A1,B1* 6 100 A1,B1
LOADING SEQUENCE A LOADING SEQUENCE B
%
(Approx) (Approx)
Compressors
%
CompressorsDisplacement Displacement
7
Table 4A — Capacity Control Steps, 040-070 (cont)
UNIT
30GN
060 (50 Hz) 070 (60 Hz)
A1†**,B1|
070 (50 Hz)
A1†,B1
070 (50 Hz)
A1†,B1**
070 (50 Hz)
A1†**,B1
070 (50 Hz)
A1†**,B1**
070 (50 Hz)
A1†,B1|
070 (50 Hz)
A1†**,B1|
*Unloaded compressor.
†Compressor unloader, standard.
**One compressor unloader, accessory.
††Two unloaders, both unloaded.
\ Two compressor unloaders, accessory.
CONTROL
STEPS
1 16 A1†† 16 B1†† 2 33 A1* 33 B1* 350A1 50B1 4 66 A1††,B1 66 A1,B1†† 5 83 A1*,B1 83 A1,B1* 6 100 A1,B1 100 A1,B1
1 19 A1* — 227A1 — — 3 65 A1*,B1 — 4 73 A1,B1 — 5 92 A1*,A2,B1 — 6 100 A1,A2,B1
1 19 A1* 31 B1* 227A1 47B1 3 49 A1*,B1* 49 A1*,B1* 4 65 A1*,B1 57 A1,B1* 5 73 A1,B1 73 A1,B1 6 76 A1*,A2,B1* 76 A1*,A2,B1* 7 92 A1*,A2,B1 84 A1,A2,B1* 8 100 A1,A2,B1 100 A1,A2,B1
1 11 A1†† — 2 19 A1* — 3 57 A1††,B1 — 4 65 A1*,B1 — 5 73 A1,B1 — 6 84 A1††,A2,B1 — 7 92 A1*,A2,B1 — 8 100 A1,A2,B1
1 11 A1†† — 2 19 A1* — 327A1 — — 4 41 A1††,B1* — 5 57 A1††,B1 — 6 65 A1*,B1 — 7 73 A1,B1 — 8 84 A1††,A2,B1 — 9 92 A1*,A2,B1
10 100 A1,A2,B1
1 15 B1†† 2 31 B1* 3— — 47 B1 4 57 A1*,B1* 5 73 A1,B1 6 84 A1,A2,B1* 7 100 A1,A2,B1
1 11 A1†† 15 B1†† 2 19 A1* 31 B1* 327A1 47B1 4 41 A1††,B1* 54 A1*,B1* 5 57 A1††,B1 73 A1,B1 6 65 A1*,B1 84 A1,A2,B1* 7 73 A1,B1 100 A1,A2,B1 8 84 A1††,A2,B1 — 9 92 A1*,A2,B1
10 100 A1,A2,B1
LOADING SEQUENCE A LOADING SEQUENCE B
%
(Approx) (Approx)
Compressors
%
CompressorsDisplacement Displacement
8
Table 4B — Capacity Control Steps, 080-110 and Associated Modular Units
UNIT
30GN
080, 230B (60 Hz)
A1†,B1†
080, 230B (60 Hz)
A1†**, B1†
080, 230B (60 Hz)
A1†,B1†**
080, 230B (60 Hz)
A1†**,B1†**
080, 230B (50 Hz)
A1†,B1†
080, 230B (50 Hz)
A1†**,B1†
080, 230B (50 Hz)
A1†,B1†**
080, 230B (50 Hz)
A1†**,B1†**
*Unloaded compressor.
†Compressor unloader, standard.
**Compressor unloader, accessory.
††Two unloaders, both unloaded.
CONTROL
STEPS
1 22 A1* 30 B1* 234A1 44B1 3 52 A1*,B1* 52 A1*,B1* 4 67 A1*,B1 63 A1,B1* 5 78 A1,B1 78 A1,B1 6 89 A1*,A2,B1 85 A1,A2,B1* 7 100 A1,A2,B1 100 A1,A2,B1
1 11 A1†† — 2 22 A1* — 334A1 — — 4 41 A1††,B1* — 5 55 A1††,B1 — 6 67 A1*,B1 — 7 78 A1,B1 — 8 89 A1*,A2,B1 — 9 100 A1,A2,B1
1 15 B1†† 2 30 B1* 3— — 44 B1 4 48 A1,B1†† 5 63 A1,B1* 6 78 A1,B1 7 85 A1,A2,B1* 8 100 A1,A2,B1
1 11 A1†† 15 B1†† 2 22 A1* 30 B1* 334A1 44B1 4 41 A1††,B1* 48 A1,B1†† 5 55 A1††,B1 63 A1,B1* 6 67 A1*,B1 78 A1,B1 7 78 A1,B1 85 A1,A2,B1* 8 89 A1*,A2,B1 100 A1,A2,B1 9 100 A1,A2,B1
1 17 A1* 25 B1* 225A1 38B1 3 42 A1*,B1* 42 A1*,B1* 4 54 A1*,B1 50 A1, B1* 5 62 A1,B1 62 A1,B1 6 79 A1*,A2,B1* 79 A1*,A2,B1* 7 92 A1*,A2,B1 88 A1,A2,B1* 8 100 A1,A2,B1 100 A1,A2,B1
1 8 A1†† — 2 17 A1* — 325A1 — — 4 33 A1††,B1* — 5 46 A1††,B1 — 6 54 A1*,B1 — 7 62 A1,B1 — 8 71 A1††,A2,B1*
9 84 A1††,A2,B1 — 10 92 A1*,A2,B1 — 11 100 A1,A2,B1
1 13 B1††
2 25 B1*
3— — 38 B1
4 50 A1,B1*
5 62 A1,B1
6 67 A1*,A2,B1††
7 75 A1,A2,B1††
8 88 A1,A2,B1*
9 100 A1,A2,B1
1 8 A1†† 13 B1††
2 17 A1* 25 B1*
325A1 38B1
4 33 A1††,B1* 50 A1,B1*
5 46 A1††,B1 62 A1,B1
6 54 A1*,B1 67 A1*,A2,B1††
7 62 A1,B1 75 A1,A2,B1††
8 71 A1††,A2,B1* 88 A1,A2,B1*
9 84 A1††,A2,B1 100 A1,A2,B1 10 92 A1*,A2,B1 — 11 100 A1,A2,B1
LOADING SEQUENCE A LOADING SEQUENCE B %
(Approx) (Approx)
Compressors
NOTE: Thesecapacitycontrolsteps may vary due to lag compressor sequencing.
%
CompressorsDisplacement Displacement
9
Table 4B — Capacity Control Steps, 080-110 and Associated Modular Units (cont)
UNIT
30GN
090, 245B (60 Hz)
A1†,B1†
090, 245B (60 Hz)
A1†**,B1†
090, 245B (60 Hz)
A1†,B1†**
090, 245B (60 Hz)
A1†**,B1†**
090, 245B (50 Hz)
A1†,B1†
090, 245B (50 Hz)
A1†**,B1†
*Unloaded compressor.
†Compressor unloader, standard.
**Compressor unloader, accessory.
††Two unloaders, both unloaded.
CONTROL
LOADING SEQUENCE A LOADING SEQUENCE B
STEPS
1 18 A1* 18 B1* 227 A1 27 B1 3 35 A1*,B1* 35 A1*,B1* 4 44 A1*,B1 44 A1,B1* 5 53 A1,B1 53 A1,B1 6 56 A1*,A2,B1* 62 A1*,B1*,B2 7 65 A1*,A2,B1 71 A1,B1*,B2 8 74 A1,A2,B1 80 A1,B1,B2
9 82 A1*,A2,B1*,B2 82 A1*,A2,B1*,B2 10 91 A1*,A2,B1,B2 91 A1,A2,B1*,B2 11 100 A1,A2,B1,B2 100 A1,A2,B1,B2
1 9 A1††
2 18 A1*
327 A1 — —
4 35 A1††,B1
5 44 A1*,B1
6 53 A1,B1
7 56 A1††,A2,B1
8 65 A1*,A2,B1
9 74 A1,A2,B1 — 10 82 A1††,A2,B1,B2 — 11 91 A1*,A2,B1,B2 — 12 100 A1,A2,B1,B2
1 9 B1††
2 18 B1*
3— — 27 B1
4 35 A1,B1††
5 44 A1,B1*
6 53 A1,B1
7 62 A1,B1††,B2
8 71 A1,B1*,B2
9 80 A1,B1,B2 10 82 A1,A2,B1††,B2 11 91 A1,A2,B1*,B2 12 100 A1,A2,B1,B2
1 9 A1†† 9 B1††
2 18 A1* 18 B1*
327 A1 27 B1
4 35 A1††,B1 35 A1,B1††
5 44 A1*,B1 44 A1,B1*
6 53 A1,B1 53 A1,B1
7 56 A1††,A2,B1 62 A1,B1††,B2
8 65 A1*,A2,B1 71 A1,B1*,B2
9 74 A1,A2,B1 80 A1,B1,B2 10 82 A1††,A2,B1,B2 82 A1,A2,B1††,B2 11 91 A1*,A2,B1,B2 91 A1,A2,B1*,B2 12 100 A1,A2,B1,B2 100 A1,A2,B1,B2
1 14 A1* 14 B1*
221 A1 21 B1
3 29 A1*,B1* 29 A1*,B1*
4 36 A1*,B1 36 A1,B1*
5 43 A1,B1 43 A1,B1
6 61 A1*,A2,B1* 53 A1*,B1*,B2
7 68 A1*,A2,B1 60 A1,B1*,B2
8 75 A1,A2,B1 67 A1,B1,B2
9 86 A1*,A2,B1*,B2 86 A1*,A2,B1*,B2 10 93 A1*,A2,B1,B2 93 A1,A2,B1*,B2 11 100 A1,A2,B1,B2 100 A1,A2,B1,B2
1 7 A1††
2 14 A1*
321 A1 — —
4 29 A1††,B1
5 36 A1*,B1
6 43 A1,B1
7 54 A1††,A2,B1*
8 61 A1††,A2,B1
9 68 A1*,A2,B1 — 10 75 A1,A2,B1 — 11 79 A1††,A2,B1*,B2 — 12 86 A1††,A2,B1,B2 — 13 93 A1*,A2,B1,B2 — 14 100 A1,A2,B1,B2
%
(Approx) (Approx)
Compressors
NOTE: Thesecapacitycontrolsteps may vary due to lag compressor sequencing.
%
CompressorsDisplacement Displacement
10
Table 4B — Capacity Control Steps, 080-110 and Associated Modular Units (cont)
UNIT 30GN
090, 245B (50 Hz)
A1†,B1†**
090, 245B (50 Hz)
A1†**,B1†**
100, 255B,
270B (60 Hz)
A1†,B1†
100, 255B,
270B (60 Hz)
A1†**,B1†
100, 255B,
270B (60 Hz)
A1†,B1†**
*Unloaded compressor.
†Compressor unloader, standard.
**Compressor unloader, accessory.
††Two unloaders, both unloaded.
CONTROL
LOADING SEQUENCE A LOADING SEQUENCE B
STEPS
1 7 B1†† 2 14 B1* 3— — 21 B1 4 29 A1,B1†† 5 36 A1,B1* 6 43 A1,B1 7 46 A1*,B1††,B2 8 53 A1,B1††,B2
9 60 A1,B1*,B2 10 67 A1,B1,B2 11 79 A1*,A2,B1††,B1 12 86 A1,A2,B1††,B1 13 93 A1,A2,B1*,B2 14 100 A1,2,B1,B2
1 7 A1†† 7 B1††
2 14 A1* 14 B1*
321 A1 21 B1
4 29 A1††,B1 29 A1,B1††
5 36 A1*,B1 36 A1,B1*
6 43 A1,B1 43 A1,B1
7 49 A1††,A2,B1†† 46 A1*,B1††,B2
8 54 A1††,A2,B1* 53 A1,B1††,B2
9 61 A1††,A2,B1 60 A1,B1*,B2 10 68 A1*,A2,B1 67 A1,B1,B2 11 75 A1,A2,B1 72 A1††,A2,B1††,B2 12 79 A1††,A2,B1*,B2 79 A1*,A2,B1††,B2 13 86 A1††,A2,B1,B2 86 A1,A2,B1††,B2 14 93 A1*,A2,B1,B2 93 A1,A2,B1*,B2 15 100 A1,A2,B1,B2 100 A1,A2,B1,B2
1 16 A1* 16 A1*
223 A1 23 A1
3 31 A1*,B1* 31 A1*,B1*
4 39 A1*,B1 39 A1*,B1
5 46 A1,B1 46 A1,B1
6 58 A1*,A2,B1* 58 A1*,A2,B1*
7 66 A1*,A2,B1 66 A1*,A2,B1
8 73 A1,A2,B1 73 A1,A2,B1
9 85 A1*,A2,B1*,B2 85 A1*,A2,B1*,B2 10 92 A1*,A2,B1,B2 92 A1*,A2,B1,B2 11 100 A1,A2,B1,B2 100 A1,A2,B1,B2
1 8 A1††
2 16 A1*
323 A1 —
4 31 A1††,B1
5 39 A1*,B1
6 46 A1,B1
7 50 A1††,A2,B1*
8 58 A1††,A2,B1
9 66 A1*,A2,B1 — 10 73 A1,A2,B1 — 11 77 A1††,A2,B1*,B2 — 12 85 A1††,A2,B1,B2 — 13 92 A1*,A2,B1,B2 — 14 100 A1,A2,B1,B2
1 8 B1††
2 16 B1*
3— — 23 B1
4 31 A1,B1††
5 39 A1,B1*
6 46 A1,B1
7 50 A1*,B1††,B2
8 58 A1,B1††,B2
9 66 A1,B1*,B2 10 73 A1,B1,B2 11 77 A1*,A2,B1††,B2 12 85 A1,A2,B1††,B2 13 92 A1,A2,B1*,B2 14 100 A1,A2,B1,B2
%
(Approx) (Approx)
Compressors
NOTE: Thesecapacitycontrolsteps may vary due to lag compressor sequencing.
%
CompressorsDisplacement Displacement
11
Table 4B — Capacity Control Steps, 080-110 and Associated Modular Units (cont)
UNIT
30GN
100, 255B,
270B (60 Hz)
A1†**,B1†**
100, 255B,
270B (50 Hz)
A1†,B1†
100, 255B,
270B (50 Hz)
A1†**,B1†
100, 255B,
270B (50 Hz)
A1†,B1†**
100, 255B,
270B (50 Hz)
A1†**,B1†**
*Unloaded compressor.
†Compressor unloader, standard.
**Compressor unloader, accessory.
††Two unloaders, both unloaded.
CONTROL
STEPS
10 73 A1,A2,B1 73 A1,B1,B2 11 77 A1††,A2,B1*,B2 77 A1*,A2,B1††,B2 12 85 A1††,A2,B1,B2 85 A1,A2,B1††,B2 13 92 A1*,A2,B1,B2 92 A1,A2,B1*,B2 14 100 A1,A2,B1,B2 100 A1,A2,B1,B2
10 93 A1*,A2,B1,B2 93 A1,A2,B1*,B2 11 100 A1,A2,B1,B2 100 A1,A2,B1,B2
10 70 A1,A2,B1 — 11 80 A1††,A2,B1*,B2 — 12 87 A1††,A2,B1,B2 — 13 93 A1*,A2,B1,B2 — 14 100 A1,A2,B1,B2
10 70 A1,B1,B2 11 80 A1*,A2,B1††,B2 12 87 A1,A2,B1††,B2 13 93 A1,A2,B1*,B2 14 100 A1,A2,B1,B2
10 63 A1*,A2,B1 63 A1,B1*,B2 11 70 A1,A2,B1 70 A1,B1,B2 12 74 A1††,A2,B1††,B2 74 A1††,A2,B1††,B2 13 80 A1††,A2,B1*,B2 80 A1*,A2,B1††,B2 14 89 A1††,A2,B1,B2 87 A1,A2,B1††,B2 15 93 A1*,A2,B1,B2 93 A1,A2,B1*,B2 16 100 A1,A2,B1,B2 100 A1,A2,B1,B2
LOADING SEQUENCE A LOADING SEQUENCE B
%
(Approx) (Approx)
1 8 A1†† 8 B1†† 2 16 A1* 16 B1* 323A1 23B1 4 31 A1††,B1 31 A1,B1†† 5 39 A1*,B1 39 A1,B1* 6 46 A1,B1 46 A1,B1 7 50 A1††,A2,B1* 50 A1*,B1††,B2 8 58 A1††,A2,B1 58 A1,B1††,B2 9 66 A1*,A2,B1 66 A1,B1*,B2
1 13 A1* 13 B1* 220A1 20B1 3 26 A1*,B1* 26 A1*,B1* 4 33 A1,B1 33 A1,B1* 5 40 A1,B1 40 A1,B1 6 57 A1*,A2,B1* 57 A1*,B1*,B2 7 63 A1*,A2,B1 63 A1,B1*,B2 8 70 A1,A2,B1 70 A1,B1,B2 9 87 A1*,A2,B1*,B2 87 A1*,A2,B1*,B2
1 7 A1†† — 2 13 A1* — 320 A1 — — 4 26 A1††,B1 — 5 33 A1*,B1 — 6 40 A1,B1 — 7 50 A1††,A2,B1* — 8 57 A1††,A2,B1 — 9 63 A1*,A2,B1
1 7 B1†† 2 13 B1* 3— 20 B1 4 26 A1,B1†† 5 33 A1,B1* 6 40 A1,B1 7 50 A1*,B1††,B2 8 57 A1,B1††,B2 9 63 A1,B1*,B2
1 7 A1†† 7 B1†† 2 13 A1* 13 B1* 320A1 20B1 4 26 A1††,B1 26 A1,B1†† 5 33 A1*,B1 33 A1,B1* 6 40 A1,B1 40 A1,B1 7 43 A1††,A2,B1†† 43 A1††,B1††,B2 8 50 A1††,A2,B1* 50 A1*,B1††,B2 9 57 A1††,A2,B1 57 A1,B1††,B2
Compressors
NOTE: Thesecapacitycontrolsteps may vary due to lag compressor sequencing.
%
CompressorsDisplacement Displacement
12
Table 4B — Capacity Control Steps, 080-110 and Associated Modular Units (cont)
UNIT
30GN
110, 290B,
315B (60 Hz)
A1†,B1†
110, 290B,
315B (60 Hz)
A1†**,B1†
110, 290B,
315B (60 Hz)
A1†,B1†**
110, 290B,
315B (60 Hz)
A1†**,B1†**
110, 290B,
315B (50 Hz)
A1†,B1†
*Unloaded compressor.
†Compressor unloader, standard.
**Compressor unloader, accessory.
††Two unloaders, both unloaded.
CONTROL
STEPS
10 93 A1*,A2,B1,B2 93 A1,A2,B1*,B2 11 100 A1,A2,B1,B2 100 A1,A2,B1,B2
10 75 A1,A2,B1 — 11 79 A1††,A2,B1*,B2 — 12 86 A1††,A2,B1,B2 — 13 93 A1*,A2,B1,B2 — 14 100 A1,A2,B1,B2
10 67 A1,B1,B2 11 79 A1*,A2,B1††,B2 12 86 A1,A2,B1††,B2 13 93 A1,A2,B1*,B2 14 100 A1,A2,B1,B2
10 68 A1*,A2,B1 67 A1,B1,B2 11 75 A1,A2,B1 72 A1††,A2,B1††,B2 12 79 A1††,A2,B1*,B2 79 A1*,A2,B1††,B2 13 86 A1††,A2,B1,B2 86 A1,A2,B1††,B2 14 93 A1*,A2,B1,B2 93 A1,A2,B1*,B2 15 100 A1,A2,B1,B2 100 A1,A2,B1,B2
10 92 A1*,A2,B1,B2 92 A1,A2,B1*,B2 11 100 A1,A2,B1,B2 100 A1,A2,B1,B2
LOADING SEQUENCE A LOADING SEQUENCE B
%
(Approx) (Approx)
1 14 A1* 14 B1* 221 A1 21 B1 3 29 A1*,B1* 29 A1*,B1* 4 36 A1*,B1 36 A1,B1* 5 43 A1,B1 43 A1,B1 6 61 A1*,A2,B1* 53 A1*,B1*,B2 7 68 A1*,A2,B1 60 A1,B1*,B2 8 75 A1,A2,B1 67 A1,B1,B2 9 86 A1*,A2,B1*,B2 86 A1*,A2,B1*,B2
1 7 A1†† — 2 14 A1* — 321 A1 — — 4 29 A1††,B1 — 5 36 A1*,B1 — 6 43 A1,B1 — 7 54 A1††,A2,B1* — 8 61 A1††,A2,B1 — 9 68 A1*,A2,B1
1 7 B1†† 2 14 B1* 3— — 21 B1 4 29 A1,B1†† 5 36 A1,B1* 6 43 A1,B1 7 46 A1*,B1††,B2 8 53 A1,B1††,B2 9 60 A1,B1*,B2
1 7 A1†† 7 B1†† 2 14 A1* 14 B1* 321 A1 21 B1 4 29 A1††,B1 29 A1,B1†† 5 36 A1*,B1 36 A1,B1* 6 43 A1,B1 43 A1,B1 7 47 A1††,A2,B1†† 46 A1*,B1††,B2 8 54 A1††,A2,B1* 53 A1,B1††,B2 9 61 A1††,A2,B1 60 A1,B1*,B2
1 17 A1* 17 B1* 225 A1 25 B1 3 33 A1*,B1* 33 A1*,B1* 4 42 A1*,B1 42 A1,B1* 5 50 A1,B1 50 A1,B1 6 58 A1*,A2,B1* 58 A1*,B1*,B2 7 67 A1*,A2,B1 67 A1,B1*,B2 8 75 A1,A2,B1 75 A1,B1,B2 9 83 A1*,A2,B1*,B2 83 A1*,A2,B1*,B2
Compressors
NOTE: Thesecapacitycontrolsteps may vary due to lag compressor sequencing.
%
CompressorsDisplacement Displacement
13
Table 4B — Capacity Control Steps, 080-110 and Associated Modular Units (cont)
UNIT
30GN
110, 290B,
315B (50 Hz)
A1†**,B1†
110, 290B,
315B (50 Hz)
A1†,B1†**
110, 290B,
315B (50 Hz)
A1†**,B1†**
*Unloaded compressor.
†Compressor unloader, standard.
**Compressor unloader, accessory.
††Two unloaders, both unloaded.
CONTROL
STEPS
LOADING SEQUENCE A LOADING SEQUENCE B
%
(Approx) (Approx)
1 8 A1†† — 2 17 A1* — 325 A1 — — 4 33 A1††,B1 — 5 42 A1*,B1 — 6 50 A1,B1 — 7 58 A1††,A2,B1 — 8 67 A1*,A2,B1 — 9 75 A1,A2,B1
10 83 A1††,A2,B1,B2
11 92 A1*,A2,B1,B2
12 100 A1,A2,B1,B2
1 8 B1†† 2 17 B1* 3— — 25 B1 4 33 A1,B1†† 5 42 A1,B1* 6 50 A1,B1 7 58 A1,B1††,B2 8 67 A1,B1*,B2 9 75 A1,B1,B2
10 83 A1,A2,B1††,B2
11 92 A1,A2,B1*,B2
12 100 A1,A2,B1,B2
1 8 A1†† 8 B1†† 2 17 A1* 17 B1* 325A1 25B1 4 33 A1††,B1 33 A1,B1†† 5 42 A1*,B1 42 A1,B1* 6 50 A1,B1 50 A1,B1 7 58 A1††,A2,B1 58 A1,B1††,B2 8 67 A1*,A2,B1 67 A1,B1*,B2 9 75 A1,A2,B1 75 A1,B1,B2
10 83 A1††,A2,B1,B2 83 A1,A2,B1††,B2
11 92 A1*,A2,B1,B2 92 A1,A2,B1*,B2
12 100 A1,A2,B1,B2 100 A1,A2,B1,B2
Compressors
NOTE: Thesecapacitycontrolsteps may vary due to lag compressor sequencing.
%
CompressorsDisplacement Displacement
14
Table 4C — Capacity Control Steps, 130-210 and Associated Modular Units
UNIT
30GN
130 (60 Hz)
A1†,B1†
130 (60 Hz)
A1†**,B1†
130 (60 Hz)
A1†,B1†**
130 (60 Hz)
A1†**,B1†**
130 (50 Hz)
A1†,B1†
*Unloaded compressor.
†Compressor unloader, standard.
**Compressor unloader, accessory.
††Two unloaders, both unloaded.
CONTROL
STEPS
1 2 3 4 5 6 7 8
9 10 11
1
2
3
4
5
6
7
8
9 10 11 12 13 14 15
1
2
3
4
5
6
7
8
9 10 11 12 13 14 15
1
2
3
4
5
6
7
8
9 10 11 12 13 14 15 16 17
1
2
3
4
5
6
7
8
9 10 11 12 13 14
LOADING SEQUENCE A LOADING SEQUENCE B
%
(Approx) (Approx)
14 21 28 35 42 58 64 71 87 93
100
8 14 21 22 28 35 42 51 58 64 71 80 87 93
100
— — — — — — — — — — — — — — —
8 14 21 22 28 35 42 44 51 58 64 71 73 80 87 93
100
10 14 26 35 39 44 53 57 69 78 82 87 96
100
Compressors
A1*
A1
A1*,B1*
A1*,B1
A1,B1
A1*,A2,B1*
A1*,A2,B1
A1,A2,B1
A1*,A2,B1*,B2
A1*,A2,B1,B2
A1,A2,B1,B2
A1††
A1*
A1
A1††,B1*
A1††,B1
A1*,B1
A1,B1
A1††,A2,B1*
A1††,A2,B1
A1*,A2,B1
A1,A2,B1
A1††,A2,B1*,B2
A1††,A2,B1,B2
A1*,A2,B1,B2
A1,A2,B1,B2
— — — — — — — — — — — — — — —
A1††
A1*
A1
A1††,B1*
A1††,B1
A1*,B1
A1,B1
A1††,A2,B1††
A1††,A2,B1*
A1††,A2,B1
A1*,A2,B1
A1,A2,B1
A1††,A2,B1††,B2
A1††,A2,B1*,B2
A1††,A2,B1,B2
A1*,A2,B1,B2
A1,A2,B1,B2
A1*
A1
A1*,B1*
A1*,B1
A1,B1
A1*,A2,B1*
A1*,A2,B1
A1,A2,B1
A1*,A2,B1*,B2
A1*,A2,B1,B2
A1,A2,B1,B2
A1*,A2,A3,B1*,B2
A1*,A2,A3,B1,B2
A1,A2,A3,B1,B2
NOTE: Thesecapacitycontrolsteps may vary due to lag compressor sequencing.
%
14 21 28 35 42 58 64 71 87 93
100
— — — — — — — — — — — — — — —
14 21 22 28 35 42 51 58 64 71 80 87 93
100
14 21 22 28 35 42 44 51 58 64 71 73 80 87 93
100
16 25 26 31 39 51 56 64 69 74 82 87 91
100
8
8
CompressorsDisplacement Displacement
B1*
B1
A1*,B1*
A1,B1*
A1,B1
A1*,B1*,B2
A1,B1*,B2
A1,B1,B2
A1*,A2,B1*,B2
A1,A2,B1*,B2
A1,A2,B1,B2
— — — — — — — — — — — — — — —
B1††
B1*
B1
A1*,B1††
A1,B1††
A1,B1*
A1,B1
A1*,B1††,B2
A1,B1††,B2
A1,B1*,B2
A1,B1,B2
A1*,A2,B1††,B2
A1,A2,B1††,B2
A1,A2,B1*,B2
A1,A2,B1,B2
B1††
B1*
B1
A1*,B1††
A1,B1††
A1,B1*
A1,B1
A1††,B1††,B2
A1*,B1††,B2
A1,B1††,B2
A1,B1*,B2
A1,B1,B2
A1††,A2,B1††,B2
A1*,A2,B1††,B2
A1,A2,B1††,B2
A1,A2,B1*,B2
A1,A2,B1,B2
B1*
B1
A1*,B1*
A1,B1*
A1,B1
A1*,B1*,B2
A1,B1*,B2
A1,B1,B2
A1*,A2,B1*,B2
A1,A2,B1*,B2
A1,A2,B1,B2
A1*,A2,A3,B1*,B2
A1,A2,A3,B1*,B2
A1,A2,A3,B1,B2
15
Table 4C — Capacity Control Steps, 130-210 and Associated Modular Units (cont)
UNIT
30GN
130 (50 Hz)
A1†**,B1†
130 (50 Hz)
A1†,B1†**
130 (50 Hz) A1†**,B1†**
150, 230A, 245A,
255A (60 Hz)
A1†,B1†
*Unloaded compressor.
†Compressor unloader, standard.
**Compressor unloader, accessory.
††Two unloaders, both unloaded.
CONTROL
STEPS
10
11 12 13 14 15 16 17 18 19
10
11 12 13 14 15
10
11 12 13 14 15 16 17 18 19
10
11 12 13 14
LOADING SEQUENCE A LOADING SEQUENCE B
%
(Approx) (Approx)
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
10 14 22 31 35 39 40 49 53 57 65 74 78 82 83 91 96
100
— — — — — — — — — — — — — — —
10 14 22 31 35 39 40 49 53 57 65 74 78 82 83 91 96
100
11 15 29 38 42 44 53 58 71 80 85 86 95
100
6
6
Compressors
A1††
A1*
A1
A1††,B1*
A1††,B1
A1*,B1
A1,B1
A1††,A2,B1*
A1††,A2,B1
A1*,A2,B1
A1,A2,B1
A1††,A2,B1*,B2
A1††,A2,B1,B2
A1*,A2,B1,B2
A1,A2,B1,B2
A1††,A2,A3,B1*,B2
A1††,A2,A3,B1,B2
A1*,A2,A3,B1,B2
A1,A2,A3,B1,B2
— — — — — — — — — — — — — — —
A1††
A1*
A1
A1††,B1*
A1††,B1
A1*,B1
A1,B1
A1††,A2,B1*
A1††,A2,B1
A1*,A2,B1
A1,A2,B1
A1††,A2,B1*,B2
A1††,A2,B1,B2
A1*,A2,B1,B2
A1,A2,B1,B2
A1††,A2,A3,B1*,B2
A1††,A2,A3,B1,B2
A1*,A2,A3,B1,B2
A1,A2,A3,B1,B2
A1*
A1
A1*,B1*
A1*,B1
A1,B1
A1*,A2,B1*
A1*,A2,B1
A1,A2,B1
A1*,A2,B1*,B2
A1*,A2,B1,B2
A1,A2,B1,B2
A1*,A2,A3,B1*,B2
A1*,A2,A3,B1,B2
A1,A2,A3,B1,B2
NOTE: Thesecapacitycontrolsteps may vary due to lag compressor sequencing.
%
— — — — — — — — — — — — — — — — — — —
16 25 31 39 43 47 56 64 65 74 82 83 91
100
16 25 31 39 43 47 56 64 65 74 82 83 91
100
— — — —
18 27 29 33 42 55 60 69 71 75 85 86 91
100
CompressorsDisplacement Displacement
— — — — — — — — — — — — — — — — — — —
8
8
B1††
B1*
B1
A1,B1*
A1,B1
A1*,B1††,B2
A1,B1††,B2
A1,B1*,B2
A1,B1,B2
A1,A2,B1††,B2
A1,A2,B1*,B2
A1,A2,B1,B2
A1,A2,A3,B1††,B2,B3
A1,A2,A3,B1*,B2,B3
A1,A2,A3,B1,B2,B3
B1††
B1*
B1
A1,B1*
A1,B1
A1*,B1††,B2
A1,B1††,B2
A1,B1*,B2
A1,B1,B2
A1,A2,B1††,B2
A1,A2,B1*,B2
A1,A2,B1,B2
A1,A2,A3,B1††,B2
A1,A2,A3,B1*,B2
A1,A2,A3,B1,B2
— — — —
B1*
B1
A1*,B1*
A1,B1*
A1,B1
A1*,B1*,B2
A1,B1*,B2
A1,B1,B2
A1*,A2,B1*,B2
A1,A2,B1*,B2
A1,A2,B1,B2
A1*,A2,A3,B1*,B2
A1,A2,A3,B1*,B2
A1,A2,A3,B1,B2
16
Table 4C — Capacity Control Steps, 130-210 and Associated Modular Units (cont)
UNIT
30GN
150, 230A, 245A,
255A (60 Hz)
A1†**,B1†
150, 230A, 245A,
255A (60 Hz)
A1†,B1†**
150, 230A, 245A,
255A (60 Hz)
A1†**,B1†**
150, 230A, 245A,
255A (50 Hz)
A1†,B1†
150, 230A, 245A,
255A (50 Hz)
A1†**,B1†
*Unloaded compressor.
†Compressor unloader, standard.
**Compressor unloader, accessory.
††Two unloaders, both unloaded.
CONTROL
STEPS
10 11 12 13 14 15 16 17
10 11 12 13
10 11 12 13 14 15 16 17
10 11 12 13 14
10 11 12 13 14 15
LOADING SEQUENCE A LOADING SEQUENCE B
%
(Approx) (Approx)
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
11 15 24 33 38 42 49 53 58 66 75 80 85 91 95
100
— — — — — — — — — — — — —
11 15 24 33 38 42 49 53 58 66 75 80 85 91 95
100
13 20 26 33 40 46 53 60 66 73 80 86 93
100
13 20 26 33 40 46 53 60 66 73 80 86 93
100
6
6
6
Compressors
A1††
A1*
A1
A1††,B1*
A1††,B1
A1*,B1
A1,B1
A1††,A2,B1
A1*,A2,B1
A1,A2,B1
A1††,A2,B1*,B2
A1††,A2,B1,B2
A1*,A2,B1,B2
A1,A2,B1,B2
A1††,A2,A3,B1,B2
A1*,A2,A3,B1,B2
A1,A2,A3,B1,B2
— — — — — — — — — — — — —
A1††
A1*
A1
A1††,B1*
A1††,B1
A1*,B1
A1,B1
A1††,A2,B1
A1*,A2,B1
A1,A2,B1
A1††,A2,B1*,B2
A1††,A2,B1,B2
A1*,A2,B1,B2
A1,A2,B1,B2
A1††,A2,A3,B1,B2
A1*,A2,A3,B1,B2
A1,A2,A3,B1,B2
A1*
A1
A1*,B1*
A1*,B1
A1,B1
A1*,A2,B1*
A1*,A2,B1
A1,A2,B1
A1*,A2,B1*,B2
A1*,A2,B1,B2
A1,A2,B1,B2
A1*,A2,A3,B1*,B2
A1*,A2,A3,B1,B2
A1,A2,A3,B1,B2
A1††
A1*
A1
A1††,B1
A1*,B1
A1,B1
A1††,A2,B1
A1*,A2,B1
A1,A2,B1
A1††,A2,B1,B2
A1*,A2,B1,B2
A1,A2,B1,B2
A1††,A2,A3,B1,B2
A1*,A2,A3,B1,B2
A1,A2,A3,B1,B2
NOTE: Thesecapacitycontrolsteps may vary due to lag compressor sequencing.
%
— — — — — — — — — — — — — — — — —
18 27 33 42 46 51 60 69 75 85 91
100
18 27 33 42 46 51 60 69 75 86 91
100
— — — —
13 20 26 33 40 46 53 60 66 73 80 86 93
100
— — — — — — — — — — — — — — —
CompressorsDisplacement Displacement
— — — — — — — — — — — — — — — — —
9
9
B1††
B1*
B1
A1,B1*
A1,B1
A1*,B1††,B2
A1,B1††,B2
A1,B1*,B2
A1,B1,B2
A1,A2,B1*,B2
A1,A2,B1,B2
A1,A2,A3,B1*,B2
A1,A2,A3,B1,B2
B1††
B1*
B1 A1,B1* A1,kB1
A1*,B1††,B2
A1,B1††,B2
A1,B1*,B2
A1,B1,B2
A1,A2,B1*,B2
A1,A2,B1,B2
A1,A2,A3,B1*,B2
A1,A2,A3,B1,B2
— — — —
B1*
B1
A1*,B1*
A1,B1*
A1,B1
A1*,B1*,B2
A1,B1*,B2
A1,B1,B2
A1*,A2,B1*,B2
A1,A2,B1*,B2
A1,A2,B1,B2
A1*,A2,A3,B1*,B2
A1,A2,A3,B1*,B2
A1,A2,A3,B1,B2
— — — — — — — — — — — — — — —
17
Table 4C — Capacity Control Steps, 130-210 and Associated Modular Units (cont)
UNIT
SIZE
150, 230A, 245A,
255A (50 Hz)
A1†,B1†**
150, 230A, 245A,
255A (50 Hz)
A1†**,B1†**
170, 270A,
330A/B (60 Hz)
A1†,B1†
170, 270A,
330A/B (60 Hz)
A1†**,B1†
*Unloaded compressor.
†Compressor unloader, standard.
**Compressor unloader, accessory.
††Two unloaders, both unloaded.
CONTROL
STEPS
10 11 12 13 14 15
10 11 12 13 14 15
10 11 12 13 14 15 16 17
10 11 12 13 14 15 16 17 18 19 20 21 22 23
LOADING SEQUENCE A LOADING SEQUENCE B
%
(Approx) (Approx)
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
— — — — — — — — — — — — — — —
13 20 26 33 40 46 53 60 66 73 80 86 93
100
11 17 23 28 33 39 45 50 56 61 67 73 78 83 89 95
100
11 17 17 23 28 33 34 39 45 50 51 56 61 67 67 73 78 83 84 89 95
100
6
6
Compressors
— — — — — — — — — — — — — — —
A1††
A1*
A1
A1††,B1
A1*,B1
A1,B1
A1††,A2,B1
A1*,A2,B1
A1,A2,B1
A1††,A2,B1,B2
A1*,A2,B1,B2
A1,A2,B1,B2
A1††,A2,A3,B1,B2
A1*,A2,A3,B1,B2
A1,A2,A3,B1,B2
A1*
A1
A1*,B1*
A1*,B1
A1,B1
A1*,A2,B1*
A1*,A2,B1
A1,A2,B1
A1*,A2,B1*,B2
A1*,A2,B1,B2
A1,A2,B1,B2
A1*,A2,A3,B1*,B2
A1*,A2,A3,B1,B2
A1,A2,A3,B1,B2
A1*,A2,A3,B1*,B2,B3
A1*,A2,A3,B1,B2,B3
A1,A2,A3,B1,B2,B3
A1††
A1*
A1
A1††,B1*
A1††,B1
A1*,B1
A1,B1
A1††,A2,B1*
A1††,A2,B1
A1*,A2,B1
A1,A2,B1
A1††,A2,B1*,B2
A1††,A2,B1,B2
A1*,A2,B1,B2
A1,A2,B1,B2
A1††,A2,A3,B1*,B2
A1††,A2,A3,B1,B2
A1*,A2,A3,B1,B2
A1,A2,A3,B1,B2
A1††,A2,A3,B1*,B2,B3
A1††,A2,A3,B1,B2,B3
A1*,A2,A3,B1,B2,B3
A1,A2,A3,B1,B2,B3
NOTE: Thesecapacitycontrolsteps may vary due to lag compressor sequencing.
%
13 20 26 33 40 46 53 60 66 73 80 86 93
100
13 20 26 33 40 46 53 60 66 73 80 86 93
100
11 17 23 28 33 39 45 50 56 61 67 73 78 83 89 95
100
— — — — — — — — — — — — — — — — — — — — — — —
CompressorsDisplacement Displacement
6
6
B1††
B1*
B1
A1,B1††
A1,B1*
A1,B1
A1,B1††,B2
A1,B1*,B2
A1,B1,B2
A1,A2,B1††,B2
A1,A2,B1*,B2
A1,A2,B1,B2
A1,A2,A3,B1††,B2
A1,A2,A3,B1*,B2
A1,A2,A3,B1,B2
B1††
B1*
B1
A1,B1††
A1,B1*
A1,B1
A1,B1††,B2
A1,B1*,B2
A1,B1,B2
A1,A2,B1††,B2
A1,A2,B1*,B2
A1,A2,B1,B2
A1,A2,A3,B1††,B2
A1,A2,A3,B1*,B2
A1,A2,A3,B1,B2
B1*
B1
A1*,B1*
A1,B1*
A1,B1
A1*,B1*,B2
A1,B1*,B2
A1,B1,B2
A1*,A2,B1*,B2
A1,A2,B1*,B2
A1,A2,B1,B2
A1*,A2,B1*,B2,B3
A1,A2,B1*,B2,B3
A1,A2,B1,B2,B3
A1*,A2,A3,B1*,B2,B3
A1,A2,A3,B1*,B2,B3
A1,A2,A3,B1,B2,B3
— — — — — — — — — — — — — — — — — — — — — — —
18
Table 4C — Capacity Control Steps, 130-210 and Associated Modular Units (cont)
UNIT
SIZE
170, 270A,
330A/B (60 Hz)
A1†,B1†**
170, 270A,
330A/B (60 Hz)
A1†**,B1†**
170, 270A,
330A/B,360B (50 Hz)
A1†,B1†
*Unloaded compressor.
†Compressor unloader, standard.
**Compressor unloader, accessory.
††Two unloaders, both unloaded.
CONTROL
STEPS
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16 17 18 19 20 21 22 23
1
2
3
4
5
6
7
8
9 10 11 12 13 14 15 16 17 18 19 20 21 22 23
1
2
3
4
5
6
7
8
9 10 11 12 13 14 15 16 17
LOADING SEQUENCE A LOADING SEQUENCE B
%
(Approx) (Approx)
— — — — — — — — — — — — — — — — — — — — — — —
6 11 17 17 23 28 33 34 39 45 50 51 56 61 67 67 73 78 83 84 89 95
100
9 14 19 23 28 33 37 42 52 57 61 72 76 81 91 96
100
Compressors
— — — — — — — — — — — — — — — — — — — — — — —
A1††
A1*
A1
A1††,B1*
A1††,B1
A1*,B1
A1,B1
A1††,A2,B1*
A1††,A2,B1
A1*,A2,B1
A1,A2,B1
A1††,A2,B1*,B2
A1††,A2,B1,B2
A1*,A2,B1,B2
A1,A2,B1,B2
A1††,A2,A3,B1*,B2
A1††,A2,A3,B1,B2
A1*,A2,A3,B1,B2
A1,A2,A3,B1,B2
A1††,A2,A3,B1*,B2,B3
A1††,A2,A3,B1,B2,B3
A1*,A2,A3,B1,B2,B3
A1,A2,A3,B1,B2,B3
A1*
A1
A1*,B1*
A1*,B1
A1,B1
A1*,A2,B1*
A1*,A2,B1
A1,A2,B1
A1*,A2,B1*,B2
A1*,A2,B1,B2
A1,A2,B1,B2
A1*,A2,A3,B1*,B2
A1*,A2,A3,B1,B2
A1,A2,A3,B1,B2
A1*,A2,A3,B1*,B2,B3
A1*,A2,A3,B1,B2,B3
A1,A2,A3,B1,B2,B3
NOTE: Thesecapacitycontrolsteps may vary due to lag compressor sequencing.
%
11 17 17 23 28 33 34 39 45 50 51 56 61 67 67 73 78 83 84 89 95
100
11 17 17 23 28 33 34 39 45 50 51 56 61 67 67 73 78 83 84 89 95
100
14 19 23 28 38 43 47 52 57 61 72 76 81 91 96
100
6
6
9
CompressorsDisplacement Displacement
B1††
B1*
B1
A1*,B1††
A1,B1††
A1,B1*
A1,B1
A1*,B1††,B2
A1,B1††,B2
A1,B1*,B2
A1,B1,B2
A1*,A2,B1††,B2
A1,A2,B1††,B2
A1,A2,B1*,B2
A1,A2,B1,B2
A1*,A2,B1††,B2,B3
A1,A2,B1††,B2,B3
A1,A2,B1*,B2,B3
A1,A2,B1,B2,B3
A1*,A2,A3,B1††,B2,B3
A1,A2,A3,B1††,B2,B3
A1,A2,A3,B1*,B2,B3
A1,A2,A3,B1,B2,B3
B1††
B1*
B1
A1*,B1††
A1,B1††
A1,B1*
A1,B1
A1*,B1††,B2
A1,B1††,B2
A1,B1*,B2
A1,B1,B2
A1*,A2,B1††,B2
A1,A2,B1††,B2
A1,A2,B1*,B2
A1,A2,B1,B2
A1*,A2,B1††,B2,B3
A1,A2,B1††,B2,B3
A1,A2,B1*,B2,B3
A1,A2,B1,B2,B3
A1*,A2,A3,B1††,B2,B3
A1,A2,A3,B1††,B2,B3
A1,A2,A3,B1*,B2,B3
A1,A2,A3,B1,B2,B3
B1*
B1
A1*,B1*
A1,B1*
A1,B1
A1*,B1*,B2
A1,B1*,B2
A1,B1,B2
A1*,A2,B1*,B2
A1,A2,B1*,B2
A1,A2,B1,B2
A1*,A2,B1*,B2,B3
A1,A2,B1*,B2,B3
A1,A2,B1,B2,B3
A1*,A2,A3,B1*,B2,B3
A1,A2,A3,B1*,B2,B3
A1,A2,A3,B1,B2,B3
19
Table 4C — Capacity Control Steps, 130-210 and Associated Modular Units (cont)
UNIT
SIZE
170, 270A,
330A/B, 360B (50 Hz)
A1†**,B1†
170, 270A,
330A/B, 360B (50 Hz)
A1†,B1†**
170, 270A,
330A/B, 360B (50 Hz)
A1†**,B1†**
*Unloaded compressor.
†Compressor unloader, standard.
**Compressor unloader, accessory.
††Two unloaders, both unloaded.
CONTROL
STEPS
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16 17 18 19 20 21 22 23
1
2
3
4
5
6
7
8
9 10 11 12 13 14 15 16 17 18 19 20 21 22 23
1
2
3
4
5
6
7
8
9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26
LOADING SEQUENCE A LOADING SEQUENCE B
%
(Approx) (Approx)
5
9 14 14 19 23 28 28 33 37 42 48 52 57 61 67 72 76 81 87 91 96
100
— — — — — — — — — — — — — — — — — — — — — — —
5
9 14 14 19 23 28 28 33 37 42 43 48 52 57 61 63 67 72 76 81 82 87 91 96
100
Compressors
A1††
A1*
A1
A1††,B1*
A1††,B1
A1*,B1
A1,B1
A1††,A2,B1*
A1††,A2,B1
A1*,A2,B1
A1,A2,B1
A1††,A2,B1*,B2
A1††,A2,B1,B2
A1*,A2,B1,B2
A1,A2,B1,B2
A1††,A2,A3,B1*,B2
A1††,A2,A3,B1,B2
A1*,A2,A3,B1,B2
A1,A2,A3,B1,B2
A1††,A2,A3,B1*,B2,B3
A1††,A2,A3,B1,B2,B3
A1*,A2,A3,B1,B2,B3
A1,A2,A3,B1,B2,B3
— — — — — — — — — — — — — — — — — — — — — — —
A1††
A1*
A1
A1††,B1*
A1††,B1
A1*,B1
A1,B1
A1††,A2,B1*
A1††,A2,B1
A1*,A2,B1
A1,A2,B1
A1††,A2,B1††,B2
A1††,A2,B1*,B2
A1††,A2,B1,B2
A1*,A2,B1,B2
A1,A2,B1,B2
A1††,A2,A3,B1††,B2
A1††,A2,A3,B1*,B2
A1††,A2,A3,B1,B2
A1*,A2,A3,B1,B2
A1,A2,A3,B1,B2
A1††,A2,A3,B1††,B2,B3
A1††,A2,A3,B1*,B2,B3
A1††,A2,A3,B1,B2,B3
A1*,A2,A3,B1,B2,B3
A1,A2,A3,B1,B2,B3
NOTE: Thesecapacitycontrolsteps may vary due to lag compressor sequencing.
%
— — — — — — — — — — — — — — — — — — — — — — —
14 14 19 23 28 34 38 43 47 48 52 57 61 67 72 76 81 87 91 96
100
14 14 19 23 28 29 34 38 43 47 48 52 57 61 63 67 72 76 81 82 87 91 96
100
5 9
5 9
CompressorsDisplacement Displacement
— — — — — — — — — — — — — — — — — — — — — — —
B1††
B1*
B1
A1*,B1††
A1,B1††
A1,B1*
A1,B1
A1*,B1††,B2
A1,B1††,B2
A1,B1*,B2
A1,B1,B2
A1*,A2,B1††,B2
A1,A2,B1††,B2
A1,A2,B1*,B2
A1,A2,B1,B2
A1*,A2,B1††,B2,B3
A1,A2,B1††,B2,B3
A1,A2,B1*,B2,B3
A1,A2,B1,B2,B3
A1*,A2,A3,B1††,B2,B3
A1,A2,A3,B1††,B2,B3
A1,A2,A3,B1*,B2,B3
A1,A2,A3,B1,B2,B3
B1††
B1*
B1
A1*,B1††
A1,B1††
A1,B1*
A1,B1
A1††,B1††,B2
A1*,B1††,B2
A1,B1††,B2
A1,B1*,B2
A1,B1,B2
A1*,A2,B1††,B2
A1,A2,B1††,B2
A1,A2,B1*,B2
A1,A2,B1,B2
A1††,A2,B1††,B2,B3
A1*,A2,B1††,B2,B3
A1,A2,B1††,B2,B3
A1,A2,B1*,B2,B3
A1,A2,B1,B2,B3
A1††,A2,A3,B1††,B2,B3
A1*,A2,A3,B1††,B2,B3
A1,A2,A3,B1††,B2,B3
A1,A2,A3,B1*,B2,B3
A1,A2,A3,B1,B3,B3
20
Table 4C — Capacity Control Steps, 130-210 and Associated Modular Units (cont)
UNIT SIZE
190, 290A, 360A/B,
390B (60 Hz)
A1,B1
190, 290A, 360A/B,
390B (60 Hz)
A1**,B1
190, 290A, 360A/B,
390B (60 Hz)
A1,B1**
190, 290A, 360A/B,
390B (60 Hz)
A1**,B1**
190, 290A, 360A,
390B (50 Hz)
A1,B1
190, 290A, 360A,
390B (50 Hz)
A1**,B1
*Unloaded compressor.
†Compressor unloader, standard.
**Compressor unloader, accessory.
††Two unloaders, both unloaded.
CONTROL
STEPS
10 11 12
10 11 12
10 11 12 13 14 15 16 17
10 11 12
LOADING SEQUENCE A LOADING SEQUENCE B
%
(Approx) (Approx)
1 2 3 4 5 6
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6
1 2 3 4 5 6 7 8 9
13 25 41 56 78
100
13 21 25 37 41 53 56 74 78 96
100
— — — — — — — — — — — —
13 18 21 25 33 37 41 49 53 56 71 74 78 93 96
100
17 33 50 67 83
100
11 17 28 33 44 50 61 67 78 83 94
100
9
9
Compressors
A1
A1,B1
A1,A2,B1
A1,A2,B1,B2
A1,A2,A3,B1,B2
A1,A2,A3,B1,B2,B3
A1*
A1
A1*,B1
A1,B1
A1*,A2,B1
A1,A2,B1
A1*,A2,B1,B2
A1,A2,B1,B2
A1*,A2,A3,B1,B2
A1,A2,A3,B1,B2
A1*,A2,A3,B1,B2,B3
A1,A2,A3,B1,B2,B3
— — — — — — — — — — — —
A1*
A1
A1*,B1*
A1*,B1
A1,B1
A1*,A2,B1*
A1*,A2,B1
A1,A2,B1
A1*,A2,B1*,B2
A1*,A2,B1,B2
A1,A2,B1,B2
A1*,A2,A3,B1*,B2
A1*,A2,A3,B1,B2
A1,A2,A3,B1,B2
A1*,A2,A3,B1*,B2,B3
A1*,A2,A3,B1,B2,B3
A1,A2,A3,B1,B2,B3
A1
A1,B1
A1,A2,B1
A1,A2,B1,B2
A1,A2,A3,B1,B2
A1,A2,A3,B1,B2,B3
A1*
A1
A1*,B1
A1,B1
A1*,A2,B1
A1,A2,B1
A1*,A2,B1,B2
A1,A2,B1,B2
A1*,A2,A3,B1,B2
A1,A2,A3,B1,B2
A1*,A2,A3,B1,B2,B3
A1,A2,A3,B1,B2,B3
NOTE: Thesecapacitycontrolsteps may vary due to lag compressor sequencing.
%
13 25 41 56 78
100
— — — — — — — — — — — —
13 21 25 37 41 53 56 74 78 96
100
13 18 21 25 33 37 41 49 53 56 71 74 78 93 96
100
17 33 50 67 83
100
— — — — — — — — — — — —
CompressorsDisplacement Displacement
B1
A1,B1
A1,B1,B2
A1,A2,B1,B2
A1,A2,B1,B2,B3
A1,A2,A3,B1,B2,B3
— — — — — — — — — — — —
9
A1,A2,A3,B1*,B2,B3
9
A1*,A2,A3,B1*,B2,B3
A1,A2,A3,B1*,B2,B3
B1*
B1
A1,B1*
A1,B1
A1,B1*,B2
A1,B1,B2
A1,A2,B1*,B2
A1,A2,B1,B2
A1,A2,B1*,B2,B3
A1,A2,B1,B2,B3
A1,A2,A3,B1,B2,B3
B1*
B1
A1*,B1*
A1,B1*
A1,B1
A1*,B1*,B2
A1,B1*,B2
A1,B1,B2
A1*,A2,B1*,B2
A1,A2,B1*,B2
A1,A2,B1,B2
A1*,A2,B1*,B2,B3
A1,A2,B1*,B2,B3
A1,A2,B1,B2,B3
A1,A2,A3,B1,B2,B3
B1
A1,B1
A1,B1,B2
A1,A2,B1,B2
A1,A2,B1,B2,B3
A1,A2,A3,B1,B2,B3
— — — — — — — — — — — —
21
Table 4C — Capacity Control Steps, 130-210 and Associated Modular Units (cont)
UNIT SIZE
190, 290A, 360A,
390B (50 Hz)
A1,B1**
190, 290A, 360A,
390B (50 Hz)
A1**,B1**
210, 315A, 390A,
420A/B (60 Hz)
A1,B1
210, 315A, 390A,
420A/B (60 Hz)
A1**,B1
210, 315A, 390A,
420A/B (60 Hz)
A1,B1**
*Unloaded compressor.
†Compressor unloader, standard.
**Compressor unloader, accessory.
††Two unloaders, both unloaded.
CONTROL
STEPS
10 11 12
10
11 12 13 14 15 16 17
10
11
12
13
14
10
11
12
13
14
LOADING SEQUENCE A LOADING SEQUENCE B
%
(Approx) (Approx)
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
— — — — — — — — — — — —
11 17 22 28 33 39 44 50 55 61 67 72 78 83 89 94
100
11 25 36 56 67 86
100
11 22 25 33 36 52 56 63 67 83 86 97
100
— — — — — — — — — — — — — —
8
Compressors
— — — — — — — — — — — —
A1*
A1
A1*,B1*
A1*,B1
A1,B1
A1*,A2,B1*
A1*,A2,B1
A1,A2,B1
A1*,A2,B1*,B2
A1*,A2,B1,B2
A1,A2,B1,B2
A1*,A2,A3,B1*,B2
A1*,A2,A3,B1,B2
A1,A2,A3,B1,B2
A1*,A2,A3,B1*,B2,B3
A1*,A2,A3,B1,B2,B3
A1,A2,A3,B1,B2,B3
A1
A1,B1
A1,A2,B1
A1,A2,B1,B2
A1,A2,A3,B1,B2
A1,A2,A3,B1,B2,B3
A1,A2,A3,A4,B1,B2,B3
A1*
A1
A1*,B1
A1,B1
A1*,A2,B1
A1,A2,B1
A1*,A2,B1,B2
A1,A2,B1,B2
A1*,A2,A3,B1,B2
A1,A2,A3,B1,B2
A1*,A2,A3,B1,B2,B3
A1,A2,A3,B1,B2,B3
A1*,A2,A3,A4,B1,B2,B3
A1,A2,A3,A4,B1,B2,B3
— — — — — — — — — — — — — —
NOTE: Thesecapacitycontrolsteps may vary due to lag compressor sequencing.
%
17 28 33 44 50 61 67 78 83 94
100
17 22 28 33 39 44 50 55 61 67 72 78 83 89 94
100
14 25 44 56 75 86
100
— — — — — — — — — — — — — —
14 21 25 40 44 51 56 71 75 82 86 96
100
CompressorsDisplacement Displacement
11
11
A1*,A2,A3,B1*,B2,B3
A1,A2,A3,A4,B1,B2,B3
9
A1,A2,A3,A4,B1*,B2,B3
A1,A2,A3,A4,B1,B2,B3
B1*
B1
A1,B1*
A1,B1
A1,B1*,B2
A1,B1,B2
A1,A2,B1*,B2
A1,A2,B1,B2
A1,A2,B1*,B2,B3
A1,A2,B1,B2,B3
A1,A2,A3,B1*,B2,B3
A1,A2,A3,B1,B2,B3
B1*
B1
A1*,B1*
A1,B1*
A1,B1
A1*,B1*,B2
A1,B1*,B2
A1,B1,B2
A1*,A2,B1*,B2
A1,A2,B1*,B2
A1,A2,B1,B2
A1*,A2,B1*,B2,B3
A1,A2,B1*,B2,B3
A1,A2,B1,B2,B3
A1,A2,A3,B1*,B2,B3
A1,A2,A3,B1,B2,B3
B1
A1,B1
A1,B1,B2
A1,A2,B1,B2
A1,A2,B1,B2,B3
A1,A2,A3,B1,B2,B3
— — — — — — — — — — — — — —
B1*
B1
A1,B1*
A1,B1
A1,B1*,B2
A1,B1,B2
A1,A2,B1*,B2
A1,A2,B1,B2
A1,A2,B1*,B2,B3
A1,A2,B1,B2,B3
A1,A2,A3,B1*,B2,B3
A1,A2,A3,B1,B2,B3
22
Loading...
+ 50 hidden pages