Carrier FLOTRONIC II 30GN040-420 User Manual

Page 1
Flotronic™ II Reciprocating Liquid Chillers
Controls, Operation, and
Troubleshooting
with Microprocessor Controls and Electronic Expansion Valves
CONTENTS
Page
SAFETY CONSIDERATIONS ..................2
GENERAL ...................................2
MAJOR SYSTEM COMPONENTS ............2-5
Electronic Expansion Valve Module ...........4
Options Module .............................4
Keypad and Display Module
(Also Called HSIO or LID) ..................4
Control Switch ..............................4
Electronic Expansion Valve (EXV) ............4
Thermostatic Expansion Valves (TXV) ........4
Sensors .....................................5
Compressor Protection Control
Module (CPCS) ............................5
OPERATION DATA ..........................5-46
Head Pressure Control ......................24
• EXV UNITS
• TXV UNITS
Pumpout ...................................24
• EXV UNITS
• TXV UNITS
Keypad and Display Module
(Also Called HSIO or LID) .................24
• ACCESSING FUNCTIONS AND SUBFUNCTIONS
• AUTOMATIC DEFAULT DISPLAY
• AUTOMATIC DISPLAY OPERATION/DEFAULT
DISPLAY
• KEYPAD OPERATING INSTRUCTIONS
• STATUS FUNCTION
• TEST FUNCTION
• HISTORY FUNCTION
• SET POINT FUNCTION
• SERVICE FUNCTION
• SCHEDULE FUNCTION
TROUBLESHOOTING ......................47-64
Checking Display Codes ....................47
30GN040-420
50/60 Hz
Page
Unit Shutoff ................................48
Lag Compressor Stoppage ..................48
Restart Procedure ..........................48
• POWER FAILURE EXTERNAL TO THE UNIT
Alarms and Alerts ..........................48
Compressor Alarm/Alert Circuit .............50
Electronic Expansion Valve (EXV) ...........55
• EXV OPERATION
• CHECKOUT PROCEDURE
Thermostatic Expansion Valve (TXV) .........57
• LOCATION
• THERMISTOR REPLACEMENT (T1, T2, T7, T8)
Pressure Transducers ......................60
• TROUBLESHOOTING
• TRANSDUCER REPLACEMENT
Control Modules ............................63
• PROCESSOR MODULE (PSIO), 4IN/4OUT MODULE (SIO), LOW-VOLTAGE RELAY MODULE (DSIO-LV), AND EXV DRIVER MODULE (DSIO-EXV)
• RED LED
• GREEN LED
• PROCESSOR MODULE (PSIO)
• LOW-VOLTAGE RELAY MODULE (DSIO)
• 4IN/4OUT MODULE (SIO)
ACCESSORY UNLOADER INSTALLATION . . . 64-68
Installation .................................65
• 040-110, 130 (60 Hz) UNITS (And Associated Modular Units)
• 130 (50 Hz), 150-210 UNITS (And Associated Modular Units)
FIELD WIRING .............................69,70
REPLACING DEFECTIVE PROCESSOR
MODULE (PSIO) ..........................70
Installation .................................70
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 2 Tab 5c
PC 903 Catalog No. 563-079 Printed in U.S.A. Form 30GN-3T Pg 1 7-95 Replaces: 30G-1T
Page 2
SAFETY CONSIDERATIONS
Installing, starting up, and servicing this equipment can be hazardous due to system pressures, electrical compo­nents, and equipment location (roof, elevatedstructures,etc.). Only trained, qualified installers and service mechanics should install, start up, and service this equipment.
When working on this equipment, observe precautions in the literature, and ontags, stickers, and labelsattached to the equipment, and any other safety precautions that apply. Fol­low all safety codes. Wear safety glasses and work gloves. Use care in handling, rigging, and setting this equipment, and in handling all electrical components.
Electrical shock can cause personal injury and death. Shut off all power to this equipment during installation and service. There may be more than one disconnect switch. Tag all disconnect locations to alert others not to restore power until work is completed.
This unit uses a microprocessor-based electronic con­trol system. Do not use jumpers or other tools to short out components, or to bypass or otherwise depart from recommended procedures. Any short-to-ground of the control board or accompanying wiring may destroy the electronic modules or electrical components.
GENERAL
IMPORTANT: This publication contains controls, op­eration and troubleshooting data for 30GN040-420 Flotronic™ II chillers.
Circuits are identified as circuitsAand B, and com­pressors are identified as A1,A2, etc. in circuit A, and B1, B2, etc. in circuit B.
Use this guide in conjunction with separate Instal­lation Instructions booklet packaged with the unit.
The 30G Series standard Flotronic II chillers feature microprocessor-based electronic controls and an electronic expansion valve (EXV) in each refrigeration circuit.
NOTE: The 30GN040 and 045 chillers with a factory­installed brine option have thermal expansion valves (TXV) instead of the EXV.
Unit sizes 230-420 are modular units which are shipped as separate sections (modulesAand B). Installation instruc­tions specific to these units are shipped inside the individual modules. See Table 1 for a listing of unit sizes and modular combinations. For modules 230B-315B, follow all general instructions as noted for unit sizes 080-110. For all remain­ing modules, follow instructions for unit sizes 130-210.
Table 1 — Unit Sizes and Modular Combinations
UNIT MODEL
30GN
040 40 045 45 050 50 060 60 070 70 080 80 090 90 100 100 110 110 130 125 150 145 170 160 190 180 210 200 230 220 150 080 245 230 150 090 255 240 150 100 270 260 170 100 290 280 190 110 315 300 210 110 330 325 170 170 360 350 190 190/170* 390 380 210 190 420 400 210 210
*60 Hz units/50 Hz units.
NOMINAL
TONS
SECTION A UNIT 30GN
SECTION B
UNIT 30GN
The Flotronic II control system cycles compressor un­loaders and/or compressors to maintain the selected leaving fluid temperature set point. It automatically positions theEXV to maintain the specified refrigerant superheat entering the compressor cylinders. It also cycles condenser fans on and off to maintain suitable head pressure for each circuit. Safe­ties are continuously monitored to prevent the unit from op­erating under unsafe conditions. A scheduling function, pro­grammed by the user, controls the unit occupied/unoccupied schedule. The control also operates a test program that al­lows the operator to check output signals and ensure com­ponents are operable.
The control system consists ofaprocessor module (PSIO), a low-voltage relay module (DSIO-LV), 2 EXVs, an EXV driver module (DSIO-EXV), a 6-pack relay board, a keypad and display module (also called HSIO or LID), thermistors, and transducers to provide inputs to the microprocessor. A standard options module (SIO) is used to provide additional functions. See Fig. 1 for a typical 30GN Control Panel.
MAJOR SYSTEM COMPONENTS
Processor Module —
ating software and controls the operation of the machine. It continuously monitors information received from the vari­ous transducers and thermistors and communicates with the relay modules and 6-pack relay board to increase or de­crease the active stages of capacity. The processor module
This module contains the oper-
2
Page 3
COMM 3 PWR
POINT NUMBER
OF
FIRST CHANNEL
COMM 1
PWR
COMM 3
S1 S2
XX
XX
STAT EXPN
HIST CLR SCHD
SRVC SET
TEST ENTR
STATUS
COMM
J4 J4
789 456 123 –
0•
STATUS
J5
COMM
LVEXV
FUSE 1
S
U
E
F
F
E
U
S
S
U
E
F
FUSE 2
GFI - CO
( 5 AMP MAX )
LOCAL/ ENABLE
STOP
CCN
CB5
CB6
12
3+
5VDC
HK35AA002
Potter & Brumfield
CZ770
SW1
FUSE 3
30GT510568 –
4-
EQUIP GND
99NA505322 D
LEGEND
CCN — Carrier Comfort Network TB Terminal Block
Fig. 1 — 30GN Control Panel (040-110 Unit Shown)
3
Page 4
also controls the EXV driver module (as appropriate), com­manding it to open or close each EXV in order to maintain the proper superheat entering thecylinders of each lead com­pressor.Information istransmittedbetweentheprocessormod­ule and relay module, the EXV driver module, and the key­pad and display module through a 3-wire communications bus. The options module is also connected to the commu­nications bus.
For the Flotronic™ II chillers,the processor monitors sys­tem pressure by means of 6 transducers, 3 in each lead com­pressor.Compressorsuctionpressure, discharge pressure, and oil pressure are sensed. If the processor senses high dis­charge pressure or low suction pressure,it immediately shuts down all compressors in the affected circuit. During opera­tion, if low oil pressure is sensed for longer than one minute, all compressors in the affected circuit are shut down. At start­up, the oil pressure signal is ignored for 2 minutes. If shut­down occurs due to any of these pressure faults, the circuit is locked out and the appropriate fault code is displayed.
Low-Voltage Relay Module — This module closes
contacts to energize compressor unloaders and/or compres­sors. It also senses the status of the safeties for all compres­sors and transmits this information to the processor.
Electronic Expansion Valve Module (If So Equipped)—
cessor and operates the electronic expansion valves.
This module receives signals fromthe pro-
Options Module — This module allows the use of Flo-
tronic II features such as dual set point, remote reset, de­mand limit, hot gas bypass, and accessory unloaders. The options module also allows for reset and demand limit to be activated from a remote 4-20 mA signal. The options mod­ule is installed at the factory.
Keypad andDisplay Module (Also Called HSIO or LID) —
tion keys, 5 operative keys, 12 numeric keys, and an alpha­numeric 8-character LCD (liquid crystal display). Key us­age is explained in Accessing Functions and Subfunctions section on page 24.
This device consists of a keypad with 6 func-
Control Switch — Control of the chiller is defined by
the position of the LOCAL/ENABLE-STOP-CCN switch. This is a 3-position manual switch that allows the chiller to be put under the control of its own FlotronicIIcontrols,manu­ally stopped, or put under the control of a Carrier Comfort Network (CCN). Switch allows unit operation as shown in Table 2.
In the LOCAL/ENABLE position, the chiller is under lo­cal control and responds to the scheduling configuration and set point data input at its own local interface device (keypad and display module).
Table 2 — LOCAL/ENABLE-STOP-CCN
Switch Positions and Operation
SWITCH
POSITION
STOP Unit Cannot Run Read/Write Read Only LOCAL/ENABLE Unit Can Run Read/Limited Write Read Only CCN Stop — Unit Cannot Run Read Only Read/Write
Run — Unit Can Run Read Only
UNIT
OPERATION
CONFIGURATION AND
SET POINT CONTROL
Keypad Control CCN Control
Read/Limited Write
In the CCN position, the chiller is under remote control and responds only to CCN network commands. The occupied/ unoccupied conditions are defined by the network. All key­pad and display functions can be read at the chiller regard­less of position of the switch.
CCN run or stop condition is established by a command from the CCN network. It is not possible to force outputs from the CCN network, except that an emergency stop com­mand shuts down the chiller immediately and causes ‘ ‘ALARM 52’’ to be displayed.
Electronic Expansion Valve (EXV) — The micro-
processor controls the EXV (if so equipped) throughtheEXV driver module. Inside the expansion valve is a linear actua­tor stepper motor.
The lead compressor in each circuit has a thermistor and a pressure transducer located in the suction manifold after the compressor motor. The thermistor measures the tem­perature of the superheated gas entering the compressor cyl­inders.Thepressuretransducermeasurestherefrigerant pressure in the suction manifold. The microprocessor converts the pres­sure reading to a saturated temperature. The difference be­tween the temperature of the superheated gas and the satu­ration temperature is the superheat.Themicroprocessorcontrols the position of the electronic expansion valve stepper motor to maintain 30 F (17 C) superheat.
At initial unit start-up, the EXV position is at zero. After that, the microprocessor keeps accurate track of the valve position in order to usethis information as input for theother control functions. The control monitors the superheat and the rate of change of superheat to control the position of the valve. The valve stroke is very large, which results in very accurate control of the superheat.
Thermostatic Expansion Valves(TXV) — Model
30GN040 and 045 units with factory-installed brine option are equipped with conventional thermostatic expansion valves with liquid line solenoids. The liquid line solenoid valves are not intended to be a mechanical shut-off. When service is required, use the liquid line service valve to pump down the system.
4
Page 5
The TXV is set at the factory to maintain approximately 8 to 12° F (4.4to6.7° C) suction superheat leaving thecooler by monitoring the proper amount of refrigerant intothecooler. All TXVs are adjustable, but should not be adjusted unless absolutely necessary.When TXVis used,thermistorsT7 and T8 are not required.
The TXV is designed to limit the cooler saturated suction temperature to 55 F (12.8 C). This makes it possible for unit to start at high cooler fluid temperatures without overload­ing the compressor.
Sensors— The Flotronic™ II chillercontrolsystemgath-
ers information from sensors to control the operation of the chiller. The units use 6 standard pressure transducers and 4 standard thermistors to monitor system pressures and tem­peratures at various points within the chiller. Sensors are listed in Table 3.
Table 3 — Thermistor and Transducer Locations
Fig. 2 — Compressor Protection Control Module
Sensor Location
T1 Cooler Leaving Fluid Temp T2 Cooler Entering Fluid Temp T7 Compressor Suction Gas Temp Circuit A T8 Compressor Suction Gas Temp Circuit B T10 Remote Temperature Sensor (Accessory)
Sensor Location
DPT-A Compressor A1 Discharge Pressure SPT-A Compressor A1 Suction Pressure OPT-A Compressor A1 Oil Pressure DPT-B Compressor B1 Discharge Pressure SPT-B Compressor B1 Suction Pressure OPT-B Compressor B1 Oil Pressure
THERMISTORS
PRESSURE TRANSDUCERS
Compressor Protection ControlModule(CPCS)
Each compressor on models 30GN070 (50 Hz), 080-
110, and 230B-315B, has its own CPCS as standard equip­ment. See Fig. 2. All 30GN040-060 and 070 (60 Hz) units feature the CPCS as an accessory, and CR (control relay) as standard equipment. The 30GN130-210 and associated modu­lar units havea CR as standard equipment. The CPCS or CR is used tocontrol and protect the compressors and crankcase heaters. The CPCS provides the following functions:
• compressor contactor control
• crankcase heater control
• compressor ground current protection
• status communication to processor board
• high-pressure protection
The CR provides all of the same functions as the CPCS with the exception of compressor ground current protection. Ground current protection is accomplished by using a CGF (compressor ground fault module) in conjunction with the CR. The CGF (See Fig. 3) provides the same ground fault function as the CPCS for units where the CPCS is not utilized.
One large relay is located on the CPCS board. This relay (or CR) controls the crankcase heater and compressor contactor. The CPCS also provides a set of signal contacts that the microprocessor monitors to determine the operating status of the compressor. If the processor board determines that the compressor is notoperatingproperly through the sig­nal contacts, it will lock the compressor off by deenergizing the proper 24-v control relay on the relay board. The CPCS board contains logic that can detect if the current-to-
Fig. 3 — Compressor Ground Fault Module
ground of any compressor winding exceeds 2.5 amps. If this condition occurs, the CPCS module shuts down the compressor.
A high-pressure switch with a trip pressure of 426 ± 7 psig (2936 ± 48 kPa), is wired in series with the CPCS. If this switch opens during operation, the compressor stops and the failure is detected by the processor when the signal contacts open. The compressor islocked off. If the leadcom­pressor in either circuit is shut down by the high-pressure switch or ground current protector, all compressors in the circuit are locked off.
OPERATION DATA
Capacity Control —
compressor to give capacity control steps as shown in Tables 4A-4C. The unit controls leaving chilled fluid tem­perature. Entering fluid temperature is used by the micro­processor in determining the optimum time to add or sub­tract steps of capacity, but is not a control set point.
The chilled fluid temperature set point can be automati­cally reset by the return temperature reset or space and outdoor-air temperature reset features. It can also be reset from an external 4 to 20 mA signal, or from a network signal.
The operating sequences shown are some of many pos­sible loading sequences for the control of the leaving fluid temperature. If a circuit has more unloaders than another, that circuit will always be the lead circuit.
The control system cycles
5
Page 6
Table 4A — Capacity Control Steps, 040-070
UNIT
30GN
040 (60 Hz)
A1†,B1
040 (60 Hz)
A1†,B1**
040 (50 Hz) 045 (60 Hz)
A1†,B1
040 (50 Hz) 045 (60 Hz)
A1†,B1**
040 (50 Hz) 045 (60 Hz)
A1†,B1**
045 (50 Hz) 050 (60 Hz)
A1†,B1
045 (50 Hz) 050 (60 Hz)
A1†,B1**
045 (50 Hz) 050 (60 Hz)
A1†**,B1
045 (50 Hz) 050 (60 Hz)
A1†**,B1**
045 (50 Hz) 050 (60 Hz)
A1†,B1**
*Unloaded compressor.
†Compressor unloader, standard.
**Compressor unloader(s), accessory.
††Two unloaders, both unloaded.
CONTROL
STEPS
1 25 A1* — 250A1— — 3 75 A1*, B1 — 4 100 A1,B1
1 25 A1* 25 B1* 250A1 50B1 3 75 A1*,B1 75 A1,B1* 4 100 A1,B1 100 A1,B1
1 24 A1* — 247A1— — 3 76 A1*,B1 — 4 100 A1,B1
1 24 A1* 37 B1* 247A1 53B1 3 61 A1*,B1* 61 A1*,B1* 4 76 A1*,B1 84 A1,B1* 5 100 A1,B1 100 A1,B1
1 21 B1†† 2 37 B1* 3— — 53B1 4 68 A1,B1†† 5 84 A1,B1* 6 100 A1,B1
1 31 A1* — 244A1— — 3 87 A1*,B1 — 4 100 A1,B1
1 31 A1* 38 B1* 244A1 56B1 3 69 A1*,B1* 69 A1*,B1* 4 87 A1*,B1 82 A1,B1* 5 100 A1,B1 100 A1,B1
1 18 A1†† — 2 31 A1* — 3 73 A1††,B1 — 4 87 A1*,B1 — 5 100 A1,B1
1 18 A1†† — 2 31 A1* — 344A1— — 4 56 A1††,B1* — 5 73 A1††,B1 — 6 87 A1*,B1 — 7 100 A1,B1
1 20 B1†† 2 38 B1* 3— — 56B1 4 51 A1*,B1†† 5 64 A1,B1†† 6 82 A1,B1* 7 100 A1,B1
LOADING SEQUENCE A LOADING SEQUENCE B
%
(Approx) (Approx)
Compressors
%
CompressorsDisplacement Displacement
6
Page 7
Table 4A — Capacity Control Steps, 040-070 (cont)
UNIT
30GN
045 (50 Hz) 050 (60 Hz)
A1†**,B1**
050 (50 Hz) 060 (60 Hz)
A1†,B1
050 (50 Hz) 060 (60 Hz)
A1†,B1**
050 (50 Hz) 060 (60 Hz)
A1†**,B1
050 (50 Hz) 060 (60 Hz)
A1†**,B1**
050 (50 Hz) 060 (60 Hz)
A1†,B1**
050 (50 Hz) 060 (60 Hz)
A1†**,B1**
060 (50 Hz) 070 (60 Hz)
A1†,B1
060 (50 Hz) 070 (60 Hz)
A1†,B1**
060 (50 Hz) 070 (60 Hz)
A1†**,B1
060 (50 Hz) 070 (60 Hz)
A1†**,B1**
060 (50 Hz) 070 (60 Hz)
A1†,B1**
*Unloaded compressor.
†Compressor unloader, standard.
**Compressor unloader(s), accessory.
††Two unloaders, both unloaded.
CONTROL
STEPS
1 18 A1†† 20 B1†† 2 31 A1* 38 B1* 344A1 56B1 4 56 A1††,B1* 64 A1,B1†† 5 73 A1††,B1 82 A1,B1* 6 87 A1*,B1 100 A1,B1 7 100 A1,B1
1 28 A1* — 242A1— — 3 87 A1*,B1 — 4 100 A1,B1
1 28 A1* 38 B1* 242A1 58B1 3 67 A1*,B1* 67 A1*,B1* 4 87 A1*,B1 80 A1,B1* 5 100 A1,B1 100 A1,B1
1 15 A1†† — 2 28 A1* — 3 73 A1††,B1 — 4 87 A1*,B1 — 5 100 A1,B1
1 15 A1†† — 2 28 A1* — 342A1— — 4 53 A1,B1* — 5 73 A1††,B1 — 6 87 A1*,B1 — 7 100 A1,B1
1 18 B1†† 2 38 B1* 3— — 58B1 4 60 A1,B1†† 5 80 A1,B1* 6 100 A1,B1
1 15 A1†† 18 B1†† 2 28 A1* 38 B1* 342A1 58B1 4 53 A1††,B1* 60 A1,B1†† 5 73 A1††,B1 80 A1,B1* 6 87 A1*,B1 100 A1,B1 7 100 A1,B1
1 33 A1* — 250A1— — 3 83 A1*,B1 — 4 100 A1,B1
1 33 A1* 33 B1* 250A1 50B1 3 67 A1*,B1* 66 A1*,B1* 4 83 A1*,B1 83 A1,B1* 5 100 A1,B1 100 A1,B1
1 16 A1†† — 2 33 A1* — 3 66 A1††,B1 — 4 83 A1* — 5 100 A1,B1
1 16 A1†† — 2 33 A1* — 350A1— — 4 66 A1††,B1 — 5 83 A1*,B1 — 6 100 A1,B1
1 16 B1†† 2 33 B1* 3— — 50B1 4 66 A1,B1†† 5 83 A1,B1* 6 100 A1,B1
LOADING SEQUENCE A LOADING SEQUENCE B
%
(Approx) (Approx)
Compressors
%
CompressorsDisplacement Displacement
7
Page 8
Table 4A — Capacity Control Steps, 040-070 (cont)
UNIT
30GN
060 (50 Hz) 070 (60 Hz)
A1†**,B1|
070 (50 Hz)
A1†,B1
070 (50 Hz)
A1†,B1**
070 (50 Hz)
A1†**,B1
070 (50 Hz)
A1†**,B1**
070 (50 Hz)
A1†,B1|
070 (50 Hz)
A1†**,B1|
*Unloaded compressor.
†Compressor unloader, standard.
**One compressor unloader, accessory.
††Two unloaders, both unloaded.
\ Two compressor unloaders, accessory.
CONTROL
STEPS
1 16 A1†† 16 B1†† 2 33 A1* 33 B1* 350A1 50B1 4 66 A1††,B1 66 A1,B1†† 5 83 A1*,B1 83 A1,B1* 6 100 A1,B1 100 A1,B1
1 19 A1* — 227A1 — — 3 65 A1*,B1 — 4 73 A1,B1 — 5 92 A1*,A2,B1 — 6 100 A1,A2,B1
1 19 A1* 31 B1* 227A1 47B1 3 49 A1*,B1* 49 A1*,B1* 4 65 A1*,B1 57 A1,B1* 5 73 A1,B1 73 A1,B1 6 76 A1*,A2,B1* 76 A1*,A2,B1* 7 92 A1*,A2,B1 84 A1,A2,B1* 8 100 A1,A2,B1 100 A1,A2,B1
1 11 A1†† — 2 19 A1* — 3 57 A1††,B1 — 4 65 A1*,B1 — 5 73 A1,B1 — 6 84 A1††,A2,B1 — 7 92 A1*,A2,B1 — 8 100 A1,A2,B1
1 11 A1†† — 2 19 A1* — 327A1 — — 4 41 A1††,B1* — 5 57 A1††,B1 — 6 65 A1*,B1 — 7 73 A1,B1 — 8 84 A1††,A2,B1 — 9 92 A1*,A2,B1
10 100 A1,A2,B1
1 15 B1†† 2 31 B1* 3— — 47 B1 4 57 A1*,B1* 5 73 A1,B1 6 84 A1,A2,B1* 7 100 A1,A2,B1
1 11 A1†† 15 B1†† 2 19 A1* 31 B1* 327A1 47B1 4 41 A1††,B1* 54 A1*,B1* 5 57 A1††,B1 73 A1,B1 6 65 A1*,B1 84 A1,A2,B1* 7 73 A1,B1 100 A1,A2,B1 8 84 A1††,A2,B1 — 9 92 A1*,A2,B1
10 100 A1,A2,B1
LOADING SEQUENCE A LOADING SEQUENCE B
%
(Approx) (Approx)
Compressors
%
CompressorsDisplacement Displacement
8
Page 9
Table 4B — Capacity Control Steps, 080-110 and Associated Modular Units
UNIT
30GN
080, 230B (60 Hz)
A1†,B1†
080, 230B (60 Hz)
A1†**, B1†
080, 230B (60 Hz)
A1†,B1†**
080, 230B (60 Hz)
A1†**,B1†**
080, 230B (50 Hz)
A1†,B1†
080, 230B (50 Hz)
A1†**,B1†
080, 230B (50 Hz)
A1†,B1†**
080, 230B (50 Hz)
A1†**,B1†**
*Unloaded compressor.
†Compressor unloader, standard.
**Compressor unloader, accessory.
††Two unloaders, both unloaded.
CONTROL
STEPS
1 22 A1* 30 B1* 234A1 44B1 3 52 A1*,B1* 52 A1*,B1* 4 67 A1*,B1 63 A1,B1* 5 78 A1,B1 78 A1,B1 6 89 A1*,A2,B1 85 A1,A2,B1* 7 100 A1,A2,B1 100 A1,A2,B1
1 11 A1†† — 2 22 A1* — 334A1 — — 4 41 A1††,B1* — 5 55 A1††,B1 — 6 67 A1*,B1 — 7 78 A1,B1 — 8 89 A1*,A2,B1 — 9 100 A1,A2,B1
1 15 B1†† 2 30 B1* 3— — 44 B1 4 48 A1,B1†† 5 63 A1,B1* 6 78 A1,B1 7 85 A1,A2,B1* 8 100 A1,A2,B1
1 11 A1†† 15 B1†† 2 22 A1* 30 B1* 334A1 44B1 4 41 A1††,B1* 48 A1,B1†† 5 55 A1††,B1 63 A1,B1* 6 67 A1*,B1 78 A1,B1 7 78 A1,B1 85 A1,A2,B1* 8 89 A1*,A2,B1 100 A1,A2,B1 9 100 A1,A2,B1
1 17 A1* 25 B1* 225A1 38B1 3 42 A1*,B1* 42 A1*,B1* 4 54 A1*,B1 50 A1, B1* 5 62 A1,B1 62 A1,B1 6 79 A1*,A2,B1* 79 A1*,A2,B1* 7 92 A1*,A2,B1 88 A1,A2,B1* 8 100 A1,A2,B1 100 A1,A2,B1
1 8 A1†† — 2 17 A1* — 325A1 — — 4 33 A1††,B1* — 5 46 A1††,B1 — 6 54 A1*,B1 — 7 62 A1,B1 — 8 71 A1††,A2,B1*
9 84 A1††,A2,B1 — 10 92 A1*,A2,B1 — 11 100 A1,A2,B1
1 13 B1††
2 25 B1*
3— — 38 B1
4 50 A1,B1*
5 62 A1,B1
6 67 A1*,A2,B1††
7 75 A1,A2,B1††
8 88 A1,A2,B1*
9 100 A1,A2,B1
1 8 A1†† 13 B1††
2 17 A1* 25 B1*
325A1 38B1
4 33 A1††,B1* 50 A1,B1*
5 46 A1††,B1 62 A1,B1
6 54 A1*,B1 67 A1*,A2,B1††
7 62 A1,B1 75 A1,A2,B1††
8 71 A1††,A2,B1* 88 A1,A2,B1*
9 84 A1††,A2,B1 100 A1,A2,B1 10 92 A1*,A2,B1 — 11 100 A1,A2,B1
LOADING SEQUENCE A LOADING SEQUENCE B %
(Approx) (Approx)
Compressors
NOTE: Thesecapacitycontrolsteps may vary due to lag compressor sequencing.
%
CompressorsDisplacement Displacement
9
Page 10
Table 4B — Capacity Control Steps, 080-110 and Associated Modular Units (cont)
UNIT
30GN
090, 245B (60 Hz)
A1†,B1†
090, 245B (60 Hz)
A1†**,B1†
090, 245B (60 Hz)
A1†,B1†**
090, 245B (60 Hz)
A1†**,B1†**
090, 245B (50 Hz)
A1†,B1†
090, 245B (50 Hz)
A1†**,B1†
*Unloaded compressor.
†Compressor unloader, standard.
**Compressor unloader, accessory.
††Two unloaders, both unloaded.
CONTROL
LOADING SEQUENCE A LOADING SEQUENCE B
STEPS
1 18 A1* 18 B1* 227 A1 27 B1 3 35 A1*,B1* 35 A1*,B1* 4 44 A1*,B1 44 A1,B1* 5 53 A1,B1 53 A1,B1 6 56 A1*,A2,B1* 62 A1*,B1*,B2 7 65 A1*,A2,B1 71 A1,B1*,B2 8 74 A1,A2,B1 80 A1,B1,B2
9 82 A1*,A2,B1*,B2 82 A1*,A2,B1*,B2 10 91 A1*,A2,B1,B2 91 A1,A2,B1*,B2 11 100 A1,A2,B1,B2 100 A1,A2,B1,B2
1 9 A1††
2 18 A1*
327 A1 — —
4 35 A1††,B1
5 44 A1*,B1
6 53 A1,B1
7 56 A1††,A2,B1
8 65 A1*,A2,B1
9 74 A1,A2,B1 — 10 82 A1††,A2,B1,B2 — 11 91 A1*,A2,B1,B2 — 12 100 A1,A2,B1,B2
1 9 B1††
2 18 B1*
3— — 27 B1
4 35 A1,B1††
5 44 A1,B1*
6 53 A1,B1
7 62 A1,B1††,B2
8 71 A1,B1*,B2
9 80 A1,B1,B2 10 82 A1,A2,B1††,B2 11 91 A1,A2,B1*,B2 12 100 A1,A2,B1,B2
1 9 A1†† 9 B1††
2 18 A1* 18 B1*
327 A1 27 B1
4 35 A1††,B1 35 A1,B1††
5 44 A1*,B1 44 A1,B1*
6 53 A1,B1 53 A1,B1
7 56 A1††,A2,B1 62 A1,B1††,B2
8 65 A1*,A2,B1 71 A1,B1*,B2
9 74 A1,A2,B1 80 A1,B1,B2 10 82 A1††,A2,B1,B2 82 A1,A2,B1††,B2 11 91 A1*,A2,B1,B2 91 A1,A2,B1*,B2 12 100 A1,A2,B1,B2 100 A1,A2,B1,B2
1 14 A1* 14 B1*
221 A1 21 B1
3 29 A1*,B1* 29 A1*,B1*
4 36 A1*,B1 36 A1,B1*
5 43 A1,B1 43 A1,B1
6 61 A1*,A2,B1* 53 A1*,B1*,B2
7 68 A1*,A2,B1 60 A1,B1*,B2
8 75 A1,A2,B1 67 A1,B1,B2
9 86 A1*,A2,B1*,B2 86 A1*,A2,B1*,B2 10 93 A1*,A2,B1,B2 93 A1,A2,B1*,B2 11 100 A1,A2,B1,B2 100 A1,A2,B1,B2
1 7 A1††
2 14 A1*
321 A1 — —
4 29 A1††,B1
5 36 A1*,B1
6 43 A1,B1
7 54 A1††,A2,B1*
8 61 A1††,A2,B1
9 68 A1*,A2,B1 — 10 75 A1,A2,B1 — 11 79 A1††,A2,B1*,B2 — 12 86 A1††,A2,B1,B2 — 13 93 A1*,A2,B1,B2 — 14 100 A1,A2,B1,B2
%
(Approx) (Approx)
Compressors
NOTE: Thesecapacitycontrolsteps may vary due to lag compressor sequencing.
%
CompressorsDisplacement Displacement
10
Page 11
Table 4B — Capacity Control Steps, 080-110 and Associated Modular Units (cont)
UNIT 30GN
090, 245B (50 Hz)
A1†,B1†**
090, 245B (50 Hz)
A1†**,B1†**
100, 255B,
270B (60 Hz)
A1†,B1†
100, 255B,
270B (60 Hz)
A1†**,B1†
100, 255B,
270B (60 Hz)
A1†,B1†**
*Unloaded compressor.
†Compressor unloader, standard.
**Compressor unloader, accessory.
††Two unloaders, both unloaded.
CONTROL
LOADING SEQUENCE A LOADING SEQUENCE B
STEPS
1 7 B1†† 2 14 B1* 3— — 21 B1 4 29 A1,B1†† 5 36 A1,B1* 6 43 A1,B1 7 46 A1*,B1††,B2 8 53 A1,B1††,B2
9 60 A1,B1*,B2 10 67 A1,B1,B2 11 79 A1*,A2,B1††,B1 12 86 A1,A2,B1††,B1 13 93 A1,A2,B1*,B2 14 100 A1,2,B1,B2
1 7 A1†† 7 B1††
2 14 A1* 14 B1*
321 A1 21 B1
4 29 A1††,B1 29 A1,B1††
5 36 A1*,B1 36 A1,B1*
6 43 A1,B1 43 A1,B1
7 49 A1††,A2,B1†† 46 A1*,B1††,B2
8 54 A1††,A2,B1* 53 A1,B1††,B2
9 61 A1††,A2,B1 60 A1,B1*,B2 10 68 A1*,A2,B1 67 A1,B1,B2 11 75 A1,A2,B1 72 A1††,A2,B1††,B2 12 79 A1††,A2,B1*,B2 79 A1*,A2,B1††,B2 13 86 A1††,A2,B1,B2 86 A1,A2,B1††,B2 14 93 A1*,A2,B1,B2 93 A1,A2,B1*,B2 15 100 A1,A2,B1,B2 100 A1,A2,B1,B2
1 16 A1* 16 A1*
223 A1 23 A1
3 31 A1*,B1* 31 A1*,B1*
4 39 A1*,B1 39 A1*,B1
5 46 A1,B1 46 A1,B1
6 58 A1*,A2,B1* 58 A1*,A2,B1*
7 66 A1*,A2,B1 66 A1*,A2,B1
8 73 A1,A2,B1 73 A1,A2,B1
9 85 A1*,A2,B1*,B2 85 A1*,A2,B1*,B2 10 92 A1*,A2,B1,B2 92 A1*,A2,B1,B2 11 100 A1,A2,B1,B2 100 A1,A2,B1,B2
1 8 A1††
2 16 A1*
323 A1 —
4 31 A1††,B1
5 39 A1*,B1
6 46 A1,B1
7 50 A1††,A2,B1*
8 58 A1††,A2,B1
9 66 A1*,A2,B1 — 10 73 A1,A2,B1 — 11 77 A1††,A2,B1*,B2 — 12 85 A1††,A2,B1,B2 — 13 92 A1*,A2,B1,B2 — 14 100 A1,A2,B1,B2
1 8 B1††
2 16 B1*
3— — 23 B1
4 31 A1,B1††
5 39 A1,B1*
6 46 A1,B1
7 50 A1*,B1††,B2
8 58 A1,B1††,B2
9 66 A1,B1*,B2 10 73 A1,B1,B2 11 77 A1*,A2,B1††,B2 12 85 A1,A2,B1††,B2 13 92 A1,A2,B1*,B2 14 100 A1,A2,B1,B2
%
(Approx) (Approx)
Compressors
NOTE: Thesecapacitycontrolsteps may vary due to lag compressor sequencing.
%
CompressorsDisplacement Displacement
11
Page 12
Table 4B — Capacity Control Steps, 080-110 and Associated Modular Units (cont)
UNIT
30GN
100, 255B,
270B (60 Hz)
A1†**,B1†**
100, 255B,
270B (50 Hz)
A1†,B1†
100, 255B,
270B (50 Hz)
A1†**,B1†
100, 255B,
270B (50 Hz)
A1†,B1†**
100, 255B,
270B (50 Hz)
A1†**,B1†**
*Unloaded compressor.
†Compressor unloader, standard.
**Compressor unloader, accessory.
††Two unloaders, both unloaded.
CONTROL
STEPS
10 73 A1,A2,B1 73 A1,B1,B2 11 77 A1††,A2,B1*,B2 77 A1*,A2,B1††,B2 12 85 A1††,A2,B1,B2 85 A1,A2,B1††,B2 13 92 A1*,A2,B1,B2 92 A1,A2,B1*,B2 14 100 A1,A2,B1,B2 100 A1,A2,B1,B2
10 93 A1*,A2,B1,B2 93 A1,A2,B1*,B2 11 100 A1,A2,B1,B2 100 A1,A2,B1,B2
10 70 A1,A2,B1 — 11 80 A1††,A2,B1*,B2 — 12 87 A1††,A2,B1,B2 — 13 93 A1*,A2,B1,B2 — 14 100 A1,A2,B1,B2
10 70 A1,B1,B2 11 80 A1*,A2,B1††,B2 12 87 A1,A2,B1††,B2 13 93 A1,A2,B1*,B2 14 100 A1,A2,B1,B2
10 63 A1*,A2,B1 63 A1,B1*,B2 11 70 A1,A2,B1 70 A1,B1,B2 12 74 A1††,A2,B1††,B2 74 A1††,A2,B1††,B2 13 80 A1††,A2,B1*,B2 80 A1*,A2,B1††,B2 14 89 A1††,A2,B1,B2 87 A1,A2,B1††,B2 15 93 A1*,A2,B1,B2 93 A1,A2,B1*,B2 16 100 A1,A2,B1,B2 100 A1,A2,B1,B2
LOADING SEQUENCE A LOADING SEQUENCE B
%
(Approx) (Approx)
1 8 A1†† 8 B1†† 2 16 A1* 16 B1* 323A1 23B1 4 31 A1††,B1 31 A1,B1†† 5 39 A1*,B1 39 A1,B1* 6 46 A1,B1 46 A1,B1 7 50 A1††,A2,B1* 50 A1*,B1††,B2 8 58 A1††,A2,B1 58 A1,B1††,B2 9 66 A1*,A2,B1 66 A1,B1*,B2
1 13 A1* 13 B1* 220A1 20B1 3 26 A1*,B1* 26 A1*,B1* 4 33 A1,B1 33 A1,B1* 5 40 A1,B1 40 A1,B1 6 57 A1*,A2,B1* 57 A1*,B1*,B2 7 63 A1*,A2,B1 63 A1,B1*,B2 8 70 A1,A2,B1 70 A1,B1,B2 9 87 A1*,A2,B1*,B2 87 A1*,A2,B1*,B2
1 7 A1†† — 2 13 A1* — 320 A1 — — 4 26 A1††,B1 — 5 33 A1*,B1 — 6 40 A1,B1 — 7 50 A1††,A2,B1* — 8 57 A1††,A2,B1 — 9 63 A1*,A2,B1
1 7 B1†† 2 13 B1* 3— 20 B1 4 26 A1,B1†† 5 33 A1,B1* 6 40 A1,B1 7 50 A1*,B1††,B2 8 57 A1,B1††,B2 9 63 A1,B1*,B2
1 7 A1†† 7 B1†† 2 13 A1* 13 B1* 320A1 20B1 4 26 A1††,B1 26 A1,B1†† 5 33 A1*,B1 33 A1,B1* 6 40 A1,B1 40 A1,B1 7 43 A1††,A2,B1†† 43 A1††,B1††,B2 8 50 A1††,A2,B1* 50 A1*,B1††,B2 9 57 A1††,A2,B1 57 A1,B1††,B2
Compressors
NOTE: Thesecapacitycontrolsteps may vary due to lag compressor sequencing.
%
CompressorsDisplacement Displacement
12
Page 13
Table 4B — Capacity Control Steps, 080-110 and Associated Modular Units (cont)
UNIT
30GN
110, 290B,
315B (60 Hz)
A1†,B1†
110, 290B,
315B (60 Hz)
A1†**,B1†
110, 290B,
315B (60 Hz)
A1†,B1†**
110, 290B,
315B (60 Hz)
A1†**,B1†**
110, 290B,
315B (50 Hz)
A1†,B1†
*Unloaded compressor.
†Compressor unloader, standard.
**Compressor unloader, accessory.
††Two unloaders, both unloaded.
CONTROL
STEPS
10 93 A1*,A2,B1,B2 93 A1,A2,B1*,B2 11 100 A1,A2,B1,B2 100 A1,A2,B1,B2
10 75 A1,A2,B1 — 11 79 A1††,A2,B1*,B2 — 12 86 A1††,A2,B1,B2 — 13 93 A1*,A2,B1,B2 — 14 100 A1,A2,B1,B2
10 67 A1,B1,B2 11 79 A1*,A2,B1††,B2 12 86 A1,A2,B1††,B2 13 93 A1,A2,B1*,B2 14 100 A1,A2,B1,B2
10 68 A1*,A2,B1 67 A1,B1,B2 11 75 A1,A2,B1 72 A1††,A2,B1††,B2 12 79 A1††,A2,B1*,B2 79 A1*,A2,B1††,B2 13 86 A1††,A2,B1,B2 86 A1,A2,B1††,B2 14 93 A1*,A2,B1,B2 93 A1,A2,B1*,B2 15 100 A1,A2,B1,B2 100 A1,A2,B1,B2
10 92 A1*,A2,B1,B2 92 A1,A2,B1*,B2 11 100 A1,A2,B1,B2 100 A1,A2,B1,B2
LOADING SEQUENCE A LOADING SEQUENCE B
%
(Approx) (Approx)
1 14 A1* 14 B1* 221 A1 21 B1 3 29 A1*,B1* 29 A1*,B1* 4 36 A1*,B1 36 A1,B1* 5 43 A1,B1 43 A1,B1 6 61 A1*,A2,B1* 53 A1*,B1*,B2 7 68 A1*,A2,B1 60 A1,B1*,B2 8 75 A1,A2,B1 67 A1,B1,B2 9 86 A1*,A2,B1*,B2 86 A1*,A2,B1*,B2
1 7 A1†† — 2 14 A1* — 321 A1 — — 4 29 A1††,B1 — 5 36 A1*,B1 — 6 43 A1,B1 — 7 54 A1††,A2,B1* — 8 61 A1††,A2,B1 — 9 68 A1*,A2,B1
1 7 B1†† 2 14 B1* 3— — 21 B1 4 29 A1,B1†† 5 36 A1,B1* 6 43 A1,B1 7 46 A1*,B1††,B2 8 53 A1,B1††,B2 9 60 A1,B1*,B2
1 7 A1†† 7 B1†† 2 14 A1* 14 B1* 321 A1 21 B1 4 29 A1††,B1 29 A1,B1†† 5 36 A1*,B1 36 A1,B1* 6 43 A1,B1 43 A1,B1 7 47 A1††,A2,B1†† 46 A1*,B1††,B2 8 54 A1††,A2,B1* 53 A1,B1††,B2 9 61 A1††,A2,B1 60 A1,B1*,B2
1 17 A1* 17 B1* 225 A1 25 B1 3 33 A1*,B1* 33 A1*,B1* 4 42 A1*,B1 42 A1,B1* 5 50 A1,B1 50 A1,B1 6 58 A1*,A2,B1* 58 A1*,B1*,B2 7 67 A1*,A2,B1 67 A1,B1*,B2 8 75 A1,A2,B1 75 A1,B1,B2 9 83 A1*,A2,B1*,B2 83 A1*,A2,B1*,B2
Compressors
NOTE: Thesecapacitycontrolsteps may vary due to lag compressor sequencing.
%
CompressorsDisplacement Displacement
13
Page 14
Table 4B — Capacity Control Steps, 080-110 and Associated Modular Units (cont)
UNIT
30GN
110, 290B,
315B (50 Hz)
A1†**,B1†
110, 290B,
315B (50 Hz)
A1†,B1†**
110, 290B,
315B (50 Hz)
A1†**,B1†**
*Unloaded compressor.
†Compressor unloader, standard.
**Compressor unloader, accessory.
††Two unloaders, both unloaded.
CONTROL
STEPS
LOADING SEQUENCE A LOADING SEQUENCE B
%
(Approx) (Approx)
1 8 A1†† — 2 17 A1* — 325 A1 — — 4 33 A1††,B1 — 5 42 A1*,B1 — 6 50 A1,B1 — 7 58 A1††,A2,B1 — 8 67 A1*,A2,B1 — 9 75 A1,A2,B1
10 83 A1††,A2,B1,B2
11 92 A1*,A2,B1,B2
12 100 A1,A2,B1,B2
1 8 B1†† 2 17 B1* 3— — 25 B1 4 33 A1,B1†† 5 42 A1,B1* 6 50 A1,B1 7 58 A1,B1††,B2 8 67 A1,B1*,B2 9 75 A1,B1,B2
10 83 A1,A2,B1††,B2
11 92 A1,A2,B1*,B2
12 100 A1,A2,B1,B2
1 8 A1†† 8 B1†† 2 17 A1* 17 B1* 325A1 25B1 4 33 A1††,B1 33 A1,B1†† 5 42 A1*,B1 42 A1,B1* 6 50 A1,B1 50 A1,B1 7 58 A1††,A2,B1 58 A1,B1††,B2 8 67 A1*,A2,B1 67 A1,B1*,B2 9 75 A1,A2,B1 75 A1,B1,B2
10 83 A1††,A2,B1,B2 83 A1,A2,B1††,B2
11 92 A1*,A2,B1,B2 92 A1,A2,B1*,B2
12 100 A1,A2,B1,B2 100 A1,A2,B1,B2
Compressors
NOTE: Thesecapacitycontrolsteps may vary due to lag compressor sequencing.
%
CompressorsDisplacement Displacement
14
Page 15
Table 4C — Capacity Control Steps, 130-210 and Associated Modular Units
UNIT
30GN
130 (60 Hz)
A1†,B1†
130 (60 Hz)
A1†**,B1†
130 (60 Hz)
A1†,B1†**
130 (60 Hz)
A1†**,B1†**
130 (50 Hz)
A1†,B1†
*Unloaded compressor.
†Compressor unloader, standard.
**Compressor unloader, accessory.
††Two unloaders, both unloaded.
CONTROL
STEPS
1 2 3 4 5 6 7 8
9 10 11
1
2
3
4
5
6
7
8
9 10 11 12 13 14 15
1
2
3
4
5
6
7
8
9 10 11 12 13 14 15
1
2
3
4
5
6
7
8
9 10 11 12 13 14 15 16 17
1
2
3
4
5
6
7
8
9 10 11 12 13 14
LOADING SEQUENCE A LOADING SEQUENCE B
%
(Approx) (Approx)
14 21 28 35 42 58 64 71 87 93
100
8 14 21 22 28 35 42 51 58 64 71 80 87 93
100
— — — — — — — — — — — — — — —
8 14 21 22 28 35 42 44 51 58 64 71 73 80 87 93
100
10 14 26 35 39 44 53 57 69 78 82 87 96
100
Compressors
A1*
A1
A1*,B1*
A1*,B1
A1,B1
A1*,A2,B1*
A1*,A2,B1
A1,A2,B1
A1*,A2,B1*,B2
A1*,A2,B1,B2
A1,A2,B1,B2
A1††
A1*
A1
A1††,B1*
A1††,B1
A1*,B1
A1,B1
A1††,A2,B1*
A1††,A2,B1
A1*,A2,B1
A1,A2,B1
A1††,A2,B1*,B2
A1††,A2,B1,B2
A1*,A2,B1,B2
A1,A2,B1,B2
— — — — — — — — — — — — — — —
A1††
A1*
A1
A1††,B1*
A1††,B1
A1*,B1
A1,B1
A1††,A2,B1††
A1††,A2,B1*
A1††,A2,B1
A1*,A2,B1
A1,A2,B1
A1††,A2,B1††,B2
A1††,A2,B1*,B2
A1††,A2,B1,B2
A1*,A2,B1,B2
A1,A2,B1,B2
A1*
A1
A1*,B1*
A1*,B1
A1,B1
A1*,A2,B1*
A1*,A2,B1
A1,A2,B1
A1*,A2,B1*,B2
A1*,A2,B1,B2
A1,A2,B1,B2
A1*,A2,A3,B1*,B2
A1*,A2,A3,B1,B2
A1,A2,A3,B1,B2
NOTE: Thesecapacitycontrolsteps may vary due to lag compressor sequencing.
%
14 21 28 35 42 58 64 71 87 93
100
— — — — — — — — — — — — — — —
14 21 22 28 35 42 51 58 64 71 80 87 93
100
14 21 22 28 35 42 44 51 58 64 71 73 80 87 93
100
16 25 26 31 39 51 56 64 69 74 82 87 91
100
8
8
CompressorsDisplacement Displacement
B1*
B1
A1*,B1*
A1,B1*
A1,B1
A1*,B1*,B2
A1,B1*,B2
A1,B1,B2
A1*,A2,B1*,B2
A1,A2,B1*,B2
A1,A2,B1,B2
— — — — — — — — — — — — — — —
B1††
B1*
B1
A1*,B1††
A1,B1††
A1,B1*
A1,B1
A1*,B1††,B2
A1,B1††,B2
A1,B1*,B2
A1,B1,B2
A1*,A2,B1††,B2
A1,A2,B1††,B2
A1,A2,B1*,B2
A1,A2,B1,B2
B1††
B1*
B1
A1*,B1††
A1,B1††
A1,B1*
A1,B1
A1††,B1††,B2
A1*,B1††,B2
A1,B1††,B2
A1,B1*,B2
A1,B1,B2
A1††,A2,B1††,B2
A1*,A2,B1††,B2
A1,A2,B1††,B2
A1,A2,B1*,B2
A1,A2,B1,B2
B1*
B1
A1*,B1*
A1,B1*
A1,B1
A1*,B1*,B2
A1,B1*,B2
A1,B1,B2
A1*,A2,B1*,B2
A1,A2,B1*,B2
A1,A2,B1,B2
A1*,A2,A3,B1*,B2
A1,A2,A3,B1*,B2
A1,A2,A3,B1,B2
15
Page 16
Table 4C — Capacity Control Steps, 130-210 and Associated Modular Units (cont)
UNIT
30GN
130 (50 Hz)
A1†**,B1†
130 (50 Hz)
A1†,B1†**
130 (50 Hz) A1†**,B1†**
150, 230A, 245A,
255A (60 Hz)
A1†,B1†
*Unloaded compressor.
†Compressor unloader, standard.
**Compressor unloader, accessory.
††Two unloaders, both unloaded.
CONTROL
STEPS
10
11 12 13 14 15 16 17 18 19
10
11 12 13 14 15
10
11 12 13 14 15 16 17 18 19
10
11 12 13 14
LOADING SEQUENCE A LOADING SEQUENCE B
%
(Approx) (Approx)
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
10 14 22 31 35 39 40 49 53 57 65 74 78 82 83 91 96
100
— — — — — — — — — — — — — — —
10 14 22 31 35 39 40 49 53 57 65 74 78 82 83 91 96
100
11 15 29 38 42 44 53 58 71 80 85 86 95
100
6
6
Compressors
A1††
A1*
A1
A1††,B1*
A1††,B1
A1*,B1
A1,B1
A1††,A2,B1*
A1††,A2,B1
A1*,A2,B1
A1,A2,B1
A1††,A2,B1*,B2
A1††,A2,B1,B2
A1*,A2,B1,B2
A1,A2,B1,B2
A1††,A2,A3,B1*,B2
A1††,A2,A3,B1,B2
A1*,A2,A3,B1,B2
A1,A2,A3,B1,B2
— — — — — — — — — — — — — — —
A1††
A1*
A1
A1††,B1*
A1††,B1
A1*,B1
A1,B1
A1††,A2,B1*
A1††,A2,B1
A1*,A2,B1
A1,A2,B1
A1††,A2,B1*,B2
A1††,A2,B1,B2
A1*,A2,B1,B2
A1,A2,B1,B2
A1††,A2,A3,B1*,B2
A1††,A2,A3,B1,B2
A1*,A2,A3,B1,B2
A1,A2,A3,B1,B2
A1*
A1
A1*,B1*
A1*,B1
A1,B1
A1*,A2,B1*
A1*,A2,B1
A1,A2,B1
A1*,A2,B1*,B2
A1*,A2,B1,B2
A1,A2,B1,B2
A1*,A2,A3,B1*,B2
A1*,A2,A3,B1,B2
A1,A2,A3,B1,B2
NOTE: Thesecapacitycontrolsteps may vary due to lag compressor sequencing.
%
— — — — — — — — — — — — — — — — — — —
16 25 31 39 43 47 56 64 65 74 82 83 91
100
16 25 31 39 43 47 56 64 65 74 82 83 91
100
— — — —
18 27 29 33 42 55 60 69 71 75 85 86 91
100
CompressorsDisplacement Displacement
— — — — — — — — — — — — — — — — — — —
8
8
B1††
B1*
B1
A1,B1*
A1,B1
A1*,B1††,B2
A1,B1††,B2
A1,B1*,B2
A1,B1,B2
A1,A2,B1††,B2
A1,A2,B1*,B2
A1,A2,B1,B2
A1,A2,A3,B1††,B2,B3
A1,A2,A3,B1*,B2,B3
A1,A2,A3,B1,B2,B3
B1††
B1*
B1
A1,B1*
A1,B1
A1*,B1††,B2
A1,B1††,B2
A1,B1*,B2
A1,B1,B2
A1,A2,B1††,B2
A1,A2,B1*,B2
A1,A2,B1,B2
A1,A2,A3,B1††,B2
A1,A2,A3,B1*,B2
A1,A2,A3,B1,B2
— — — —
B1*
B1
A1*,B1*
A1,B1*
A1,B1
A1*,B1*,B2
A1,B1*,B2
A1,B1,B2
A1*,A2,B1*,B2
A1,A2,B1*,B2
A1,A2,B1,B2
A1*,A2,A3,B1*,B2
A1,A2,A3,B1*,B2
A1,A2,A3,B1,B2
16
Page 17
Table 4C — Capacity Control Steps, 130-210 and Associated Modular Units (cont)
UNIT
30GN
150, 230A, 245A,
255A (60 Hz)
A1†**,B1†
150, 230A, 245A,
255A (60 Hz)
A1†,B1†**
150, 230A, 245A,
255A (60 Hz)
A1†**,B1†**
150, 230A, 245A,
255A (50 Hz)
A1†,B1†
150, 230A, 245A,
255A (50 Hz)
A1†**,B1†
*Unloaded compressor.
†Compressor unloader, standard.
**Compressor unloader, accessory.
††Two unloaders, both unloaded.
CONTROL
STEPS
10 11 12 13 14 15 16 17
10 11 12 13
10 11 12 13 14 15 16 17
10 11 12 13 14
10 11 12 13 14 15
LOADING SEQUENCE A LOADING SEQUENCE B
%
(Approx) (Approx)
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
11 15 24 33 38 42 49 53 58 66 75 80 85 91 95
100
— — — — — — — — — — — — —
11 15 24 33 38 42 49 53 58 66 75 80 85 91 95
100
13 20 26 33 40 46 53 60 66 73 80 86 93
100
13 20 26 33 40 46 53 60 66 73 80 86 93
100
6
6
6
Compressors
A1††
A1*
A1
A1††,B1*
A1††,B1
A1*,B1
A1,B1
A1††,A2,B1
A1*,A2,B1
A1,A2,B1
A1††,A2,B1*,B2
A1††,A2,B1,B2
A1*,A2,B1,B2
A1,A2,B1,B2
A1††,A2,A3,B1,B2
A1*,A2,A3,B1,B2
A1,A2,A3,B1,B2
— — — — — — — — — — — — —
A1††
A1*
A1
A1††,B1*
A1††,B1
A1*,B1
A1,B1
A1††,A2,B1
A1*,A2,B1
A1,A2,B1
A1††,A2,B1*,B2
A1††,A2,B1,B2
A1*,A2,B1,B2
A1,A2,B1,B2
A1††,A2,A3,B1,B2
A1*,A2,A3,B1,B2
A1,A2,A3,B1,B2
A1*
A1
A1*,B1*
A1*,B1
A1,B1
A1*,A2,B1*
A1*,A2,B1
A1,A2,B1
A1*,A2,B1*,B2
A1*,A2,B1,B2
A1,A2,B1,B2
A1*,A2,A3,B1*,B2
A1*,A2,A3,B1,B2
A1,A2,A3,B1,B2
A1††
A1*
A1
A1††,B1
A1*,B1
A1,B1
A1††,A2,B1
A1*,A2,B1
A1,A2,B1
A1††,A2,B1,B2
A1*,A2,B1,B2
A1,A2,B1,B2
A1††,A2,A3,B1,B2
A1*,A2,A3,B1,B2
A1,A2,A3,B1,B2
NOTE: Thesecapacitycontrolsteps may vary due to lag compressor sequencing.
%
— — — — — — — — — — — — — — — — —
18 27 33 42 46 51 60 69 75 85 91
100
18 27 33 42 46 51 60 69 75 86 91
100
— — — —
13 20 26 33 40 46 53 60 66 73 80 86 93
100
— — — — — — — — — — — — — — —
CompressorsDisplacement Displacement
— — — — — — — — — — — — — — — — —
9
9
B1††
B1*
B1
A1,B1*
A1,B1
A1*,B1††,B2
A1,B1††,B2
A1,B1*,B2
A1,B1,B2
A1,A2,B1*,B2
A1,A2,B1,B2
A1,A2,A3,B1*,B2
A1,A2,A3,B1,B2
B1††
B1*
B1 A1,B1* A1,kB1
A1*,B1††,B2
A1,B1††,B2
A1,B1*,B2
A1,B1,B2
A1,A2,B1*,B2
A1,A2,B1,B2
A1,A2,A3,B1*,B2
A1,A2,A3,B1,B2
— — — —
B1*
B1
A1*,B1*
A1,B1*
A1,B1
A1*,B1*,B2
A1,B1*,B2
A1,B1,B2
A1*,A2,B1*,B2
A1,A2,B1*,B2
A1,A2,B1,B2
A1*,A2,A3,B1*,B2
A1,A2,A3,B1*,B2
A1,A2,A3,B1,B2
— — — — — — — — — — — — — — —
17
Page 18
Table 4C — Capacity Control Steps, 130-210 and Associated Modular Units (cont)
UNIT
SIZE
150, 230A, 245A,
255A (50 Hz)
A1†,B1†**
150, 230A, 245A,
255A (50 Hz)
A1†**,B1†**
170, 270A,
330A/B (60 Hz)
A1†,B1†
170, 270A,
330A/B (60 Hz)
A1†**,B1†
*Unloaded compressor.
†Compressor unloader, standard.
**Compressor unloader, accessory.
††Two unloaders, both unloaded.
CONTROL
STEPS
10 11 12 13 14 15
10 11 12 13 14 15
10 11 12 13 14 15 16 17
10 11 12 13 14 15 16 17 18 19 20 21 22 23
LOADING SEQUENCE A LOADING SEQUENCE B
%
(Approx) (Approx)
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
— — — — — — — — — — — — — — —
13 20 26 33 40 46 53 60 66 73 80 86 93
100
11 17 23 28 33 39 45 50 56 61 67 73 78 83 89 95
100
11 17 17 23 28 33 34 39 45 50 51 56 61 67 67 73 78 83 84 89 95
100
6
6
Compressors
— — — — — — — — — — — — — — —
A1††
A1*
A1
A1††,B1
A1*,B1
A1,B1
A1††,A2,B1
A1*,A2,B1
A1,A2,B1
A1††,A2,B1,B2
A1*,A2,B1,B2
A1,A2,B1,B2
A1††,A2,A3,B1,B2
A1*,A2,A3,B1,B2
A1,A2,A3,B1,B2
A1*
A1
A1*,B1*
A1*,B1
A1,B1
A1*,A2,B1*
A1*,A2,B1
A1,A2,B1
A1*,A2,B1*,B2
A1*,A2,B1,B2
A1,A2,B1,B2
A1*,A2,A3,B1*,B2
A1*,A2,A3,B1,B2
A1,A2,A3,B1,B2
A1*,A2,A3,B1*,B2,B3
A1*,A2,A3,B1,B2,B3
A1,A2,A3,B1,B2,B3
A1††
A1*
A1
A1††,B1*
A1††,B1
A1*,B1
A1,B1
A1††,A2,B1*
A1††,A2,B1
A1*,A2,B1
A1,A2,B1
A1††,A2,B1*,B2
A1††,A2,B1,B2
A1*,A2,B1,B2
A1,A2,B1,B2
A1††,A2,A3,B1*,B2
A1††,A2,A3,B1,B2
A1*,A2,A3,B1,B2
A1,A2,A3,B1,B2
A1††,A2,A3,B1*,B2,B3
A1††,A2,A3,B1,B2,B3
A1*,A2,A3,B1,B2,B3
A1,A2,A3,B1,B2,B3
NOTE: Thesecapacitycontrolsteps may vary due to lag compressor sequencing.
%
13 20 26 33 40 46 53 60 66 73 80 86 93
100
13 20 26 33 40 46 53 60 66 73 80 86 93
100
11 17 23 28 33 39 45 50 56 61 67 73 78 83 89 95
100
— — — — — — — — — — — — — — — — — — — — — — —
CompressorsDisplacement Displacement
6
6
B1††
B1*
B1
A1,B1††
A1,B1*
A1,B1
A1,B1††,B2
A1,B1*,B2
A1,B1,B2
A1,A2,B1††,B2
A1,A2,B1*,B2
A1,A2,B1,B2
A1,A2,A3,B1††,B2
A1,A2,A3,B1*,B2
A1,A2,A3,B1,B2
B1††
B1*
B1
A1,B1††
A1,B1*
A1,B1
A1,B1††,B2
A1,B1*,B2
A1,B1,B2
A1,A2,B1††,B2
A1,A2,B1*,B2
A1,A2,B1,B2
A1,A2,A3,B1††,B2
A1,A2,A3,B1*,B2
A1,A2,A3,B1,B2
B1*
B1
A1*,B1*
A1,B1*
A1,B1
A1*,B1*,B2
A1,B1*,B2
A1,B1,B2
A1*,A2,B1*,B2
A1,A2,B1*,B2
A1,A2,B1,B2
A1*,A2,B1*,B2,B3
A1,A2,B1*,B2,B3
A1,A2,B1,B2,B3
A1*,A2,A3,B1*,B2,B3
A1,A2,A3,B1*,B2,B3
A1,A2,A3,B1,B2,B3
— — — — — — — — — — — — — — — — — — — — — — —
18
Page 19
Table 4C — Capacity Control Steps, 130-210 and Associated Modular Units (cont)
UNIT
SIZE
170, 270A,
330A/B (60 Hz)
A1†,B1†**
170, 270A,
330A/B (60 Hz)
A1†**,B1†**
170, 270A,
330A/B,360B (50 Hz)
A1†,B1†
*Unloaded compressor.
†Compressor unloader, standard.
**Compressor unloader, accessory.
††Two unloaders, both unloaded.
CONTROL
STEPS
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16 17 18 19 20 21 22 23
1
2
3
4
5
6
7
8
9 10 11 12 13 14 15 16 17 18 19 20 21 22 23
1
2
3
4
5
6
7
8
9 10 11 12 13 14 15 16 17
LOADING SEQUENCE A LOADING SEQUENCE B
%
(Approx) (Approx)
— — — — — — — — — — — — — — — — — — — — — — —
6 11 17 17 23 28 33 34 39 45 50 51 56 61 67 67 73 78 83 84 89 95
100
9 14 19 23 28 33 37 42 52 57 61 72 76 81 91 96
100
Compressors
— — — — — — — — — — — — — — — — — — — — — — —
A1††
A1*
A1
A1††,B1*
A1††,B1
A1*,B1
A1,B1
A1††,A2,B1*
A1††,A2,B1
A1*,A2,B1
A1,A2,B1
A1††,A2,B1*,B2
A1††,A2,B1,B2
A1*,A2,B1,B2
A1,A2,B1,B2
A1††,A2,A3,B1*,B2
A1††,A2,A3,B1,B2
A1*,A2,A3,B1,B2
A1,A2,A3,B1,B2
A1††,A2,A3,B1*,B2,B3
A1††,A2,A3,B1,B2,B3
A1*,A2,A3,B1,B2,B3
A1,A2,A3,B1,B2,B3
A1*
A1
A1*,B1*
A1*,B1
A1,B1
A1*,A2,B1*
A1*,A2,B1
A1,A2,B1
A1*,A2,B1*,B2
A1*,A2,B1,B2
A1,A2,B1,B2
A1*,A2,A3,B1*,B2
A1*,A2,A3,B1,B2
A1,A2,A3,B1,B2
A1*,A2,A3,B1*,B2,B3
A1*,A2,A3,B1,B2,B3
A1,A2,A3,B1,B2,B3
NOTE: Thesecapacitycontrolsteps may vary due to lag compressor sequencing.
%
11 17 17 23 28 33 34 39 45 50 51 56 61 67 67 73 78 83 84 89 95
100
11 17 17 23 28 33 34 39 45 50 51 56 61 67 67 73 78 83 84 89 95
100
14 19 23 28 38 43 47 52 57 61 72 76 81 91 96
100
6
6
9
CompressorsDisplacement Displacement
B1††
B1*
B1
A1*,B1††
A1,B1††
A1,B1*
A1,B1
A1*,B1††,B2
A1,B1††,B2
A1,B1*,B2
A1,B1,B2
A1*,A2,B1††,B2
A1,A2,B1††,B2
A1,A2,B1*,B2
A1,A2,B1,B2
A1*,A2,B1††,B2,B3
A1,A2,B1††,B2,B3
A1,A2,B1*,B2,B3
A1,A2,B1,B2,B3
A1*,A2,A3,B1††,B2,B3
A1,A2,A3,B1††,B2,B3
A1,A2,A3,B1*,B2,B3
A1,A2,A3,B1,B2,B3
B1††
B1*
B1
A1*,B1††
A1,B1††
A1,B1*
A1,B1
A1*,B1††,B2
A1,B1††,B2
A1,B1*,B2
A1,B1,B2
A1*,A2,B1††,B2
A1,A2,B1††,B2
A1,A2,B1*,B2
A1,A2,B1,B2
A1*,A2,B1††,B2,B3
A1,A2,B1††,B2,B3
A1,A2,B1*,B2,B3
A1,A2,B1,B2,B3
A1*,A2,A3,B1††,B2,B3
A1,A2,A3,B1††,B2,B3
A1,A2,A3,B1*,B2,B3
A1,A2,A3,B1,B2,B3
B1*
B1
A1*,B1*
A1,B1*
A1,B1
A1*,B1*,B2
A1,B1*,B2
A1,B1,B2
A1*,A2,B1*,B2
A1,A2,B1*,B2
A1,A2,B1,B2
A1*,A2,B1*,B2,B3
A1,A2,B1*,B2,B3
A1,A2,B1,B2,B3
A1*,A2,A3,B1*,B2,B3
A1,A2,A3,B1*,B2,B3
A1,A2,A3,B1,B2,B3
19
Page 20
Table 4C — Capacity Control Steps, 130-210 and Associated Modular Units (cont)
UNIT
SIZE
170, 270A,
330A/B, 360B (50 Hz)
A1†**,B1†
170, 270A,
330A/B, 360B (50 Hz)
A1†,B1†**
170, 270A,
330A/B, 360B (50 Hz)
A1†**,B1†**
*Unloaded compressor.
†Compressor unloader, standard.
**Compressor unloader, accessory.
††Two unloaders, both unloaded.
CONTROL
STEPS
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16 17 18 19 20 21 22 23
1
2
3
4
5
6
7
8
9 10 11 12 13 14 15 16 17 18 19 20 21 22 23
1
2
3
4
5
6
7
8
9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26
LOADING SEQUENCE A LOADING SEQUENCE B
%
(Approx) (Approx)
5
9 14 14 19 23 28 28 33 37 42 48 52 57 61 67 72 76 81 87 91 96
100
— — — — — — — — — — — — — — — — — — — — — — —
5
9 14 14 19 23 28 28 33 37 42 43 48 52 57 61 63 67 72 76 81 82 87 91 96
100
Compressors
A1††
A1*
A1
A1††,B1*
A1††,B1
A1*,B1
A1,B1
A1††,A2,B1*
A1††,A2,B1
A1*,A2,B1
A1,A2,B1
A1††,A2,B1*,B2
A1††,A2,B1,B2
A1*,A2,B1,B2
A1,A2,B1,B2
A1††,A2,A3,B1*,B2
A1††,A2,A3,B1,B2
A1*,A2,A3,B1,B2
A1,A2,A3,B1,B2
A1††,A2,A3,B1*,B2,B3
A1††,A2,A3,B1,B2,B3
A1*,A2,A3,B1,B2,B3
A1,A2,A3,B1,B2,B3
— — — — — — — — — — — — — — — — — — — — — — —
A1††
A1*
A1
A1††,B1*
A1††,B1
A1*,B1
A1,B1
A1††,A2,B1*
A1††,A2,B1
A1*,A2,B1
A1,A2,B1
A1††,A2,B1††,B2
A1††,A2,B1*,B2
A1††,A2,B1,B2
A1*,A2,B1,B2
A1,A2,B1,B2
A1††,A2,A3,B1††,B2
A1††,A2,A3,B1*,B2
A1††,A2,A3,B1,B2
A1*,A2,A3,B1,B2
A1,A2,A3,B1,B2
A1††,A2,A3,B1††,B2,B3
A1††,A2,A3,B1*,B2,B3
A1††,A2,A3,B1,B2,B3
A1*,A2,A3,B1,B2,B3
A1,A2,A3,B1,B2,B3
NOTE: Thesecapacitycontrolsteps may vary due to lag compressor sequencing.
%
— — — — — — — — — — — — — — — — — — — — — — —
14 14 19 23 28 34 38 43 47 48 52 57 61 67 72 76 81 87 91 96
100
14 14 19 23 28 29 34 38 43 47 48 52 57 61 63 67 72 76 81 82 87 91 96
100
5 9
5 9
CompressorsDisplacement Displacement
— — — — — — — — — — — — — — — — — — — — — — —
B1††
B1*
B1
A1*,B1††
A1,B1††
A1,B1*
A1,B1
A1*,B1††,B2
A1,B1††,B2
A1,B1*,B2
A1,B1,B2
A1*,A2,B1††,B2
A1,A2,B1††,B2
A1,A2,B1*,B2
A1,A2,B1,B2
A1*,A2,B1††,B2,B3
A1,A2,B1††,B2,B3
A1,A2,B1*,B2,B3
A1,A2,B1,B2,B3
A1*,A2,A3,B1††,B2,B3
A1,A2,A3,B1††,B2,B3
A1,A2,A3,B1*,B2,B3
A1,A2,A3,B1,B2,B3
B1††
B1*
B1
A1*,B1††
A1,B1††
A1,B1*
A1,B1
A1††,B1††,B2
A1*,B1††,B2
A1,B1††,B2
A1,B1*,B2
A1,B1,B2
A1*,A2,B1††,B2
A1,A2,B1††,B2
A1,A2,B1*,B2
A1,A2,B1,B2
A1††,A2,B1††,B2,B3
A1*,A2,B1††,B2,B3
A1,A2,B1††,B2,B3
A1,A2,B1*,B2,B3
A1,A2,B1,B2,B3
A1††,A2,A3,B1††,B2,B3
A1*,A2,A3,B1††,B2,B3
A1,A2,A3,B1††,B2,B3
A1,A2,A3,B1*,B2,B3
A1,A2,A3,B1,B3,B3
20
Page 21
Table 4C — Capacity Control Steps, 130-210 and Associated Modular Units (cont)
UNIT SIZE
190, 290A, 360A/B,
390B (60 Hz)
A1,B1
190, 290A, 360A/B,
390B (60 Hz)
A1**,B1
190, 290A, 360A/B,
390B (60 Hz)
A1,B1**
190, 290A, 360A/B,
390B (60 Hz)
A1**,B1**
190, 290A, 360A,
390B (50 Hz)
A1,B1
190, 290A, 360A,
390B (50 Hz)
A1**,B1
*Unloaded compressor.
†Compressor unloader, standard.
**Compressor unloader, accessory.
††Two unloaders, both unloaded.
CONTROL
STEPS
10 11 12
10 11 12
10 11 12 13 14 15 16 17
10 11 12
LOADING SEQUENCE A LOADING SEQUENCE B
%
(Approx) (Approx)
1 2 3 4 5 6
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6
1 2 3 4 5 6 7 8 9
13 25 41 56 78
100
13 21 25 37 41 53 56 74 78 96
100
— — — — — — — — — — — —
13 18 21 25 33 37 41 49 53 56 71 74 78 93 96
100
17 33 50 67 83
100
11 17 28 33 44 50 61 67 78 83 94
100
9
9
Compressors
A1
A1,B1
A1,A2,B1
A1,A2,B1,B2
A1,A2,A3,B1,B2
A1,A2,A3,B1,B2,B3
A1*
A1
A1*,B1
A1,B1
A1*,A2,B1
A1,A2,B1
A1*,A2,B1,B2
A1,A2,B1,B2
A1*,A2,A3,B1,B2
A1,A2,A3,B1,B2
A1*,A2,A3,B1,B2,B3
A1,A2,A3,B1,B2,B3
— — — — — — — — — — — —
A1*
A1
A1*,B1*
A1*,B1
A1,B1
A1*,A2,B1*
A1*,A2,B1
A1,A2,B1
A1*,A2,B1*,B2
A1*,A2,B1,B2
A1,A2,B1,B2
A1*,A2,A3,B1*,B2
A1*,A2,A3,B1,B2
A1,A2,A3,B1,B2
A1*,A2,A3,B1*,B2,B3
A1*,A2,A3,B1,B2,B3
A1,A2,A3,B1,B2,B3
A1
A1,B1
A1,A2,B1
A1,A2,B1,B2
A1,A2,A3,B1,B2
A1,A2,A3,B1,B2,B3
A1*
A1
A1*,B1
A1,B1
A1*,A2,B1
A1,A2,B1
A1*,A2,B1,B2
A1,A2,B1,B2
A1*,A2,A3,B1,B2
A1,A2,A3,B1,B2
A1*,A2,A3,B1,B2,B3
A1,A2,A3,B1,B2,B3
NOTE: Thesecapacitycontrolsteps may vary due to lag compressor sequencing.
%
13 25 41 56 78
100
— — — — — — — — — — — —
13 21 25 37 41 53 56 74 78 96
100
13 18 21 25 33 37 41 49 53 56 71 74 78 93 96
100
17 33 50 67 83
100
— — — — — — — — — — — —
CompressorsDisplacement Displacement
B1
A1,B1
A1,B1,B2
A1,A2,B1,B2
A1,A2,B1,B2,B3
A1,A2,A3,B1,B2,B3
— — — — — — — — — — — —
9
A1,A2,A3,B1*,B2,B3
9
A1*,A2,A3,B1*,B2,B3
A1,A2,A3,B1*,B2,B3
B1*
B1
A1,B1*
A1,B1
A1,B1*,B2
A1,B1,B2
A1,A2,B1*,B2
A1,A2,B1,B2
A1,A2,B1*,B2,B3
A1,A2,B1,B2,B3
A1,A2,A3,B1,B2,B3
B1*
B1
A1*,B1*
A1,B1*
A1,B1
A1*,B1*,B2
A1,B1*,B2
A1,B1,B2
A1*,A2,B1*,B2
A1,A2,B1*,B2
A1,A2,B1,B2
A1*,A2,B1*,B2,B3
A1,A2,B1*,B2,B3
A1,A2,B1,B2,B3
A1,A2,A3,B1,B2,B3
B1
A1,B1
A1,B1,B2
A1,A2,B1,B2
A1,A2,B1,B2,B3
A1,A2,A3,B1,B2,B3
— — — — — — — — — — — —
21
Page 22
Table 4C — Capacity Control Steps, 130-210 and Associated Modular Units (cont)
UNIT SIZE
190, 290A, 360A,
390B (50 Hz)
A1,B1**
190, 290A, 360A,
390B (50 Hz)
A1**,B1**
210, 315A, 390A,
420A/B (60 Hz)
A1,B1
210, 315A, 390A,
420A/B (60 Hz)
A1**,B1
210, 315A, 390A,
420A/B (60 Hz)
A1,B1**
*Unloaded compressor.
†Compressor unloader, standard.
**Compressor unloader, accessory.
††Two unloaders, both unloaded.
CONTROL
STEPS
10 11 12
10
11 12 13 14 15 16 17
10
11
12
13
14
10
11
12
13
14
LOADING SEQUENCE A LOADING SEQUENCE B
%
(Approx) (Approx)
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
— — — — — — — — — — — —
11 17 22 28 33 39 44 50 55 61 67 72 78 83 89 94
100
11 25 36 56 67 86
100
11 22 25 33 36 52 56 63 67 83 86 97
100
— — — — — — — — — — — — — —
8
Compressors
— — — — — — — — — — — —
A1*
A1
A1*,B1*
A1*,B1
A1,B1
A1*,A2,B1*
A1*,A2,B1
A1,A2,B1
A1*,A2,B1*,B2
A1*,A2,B1,B2
A1,A2,B1,B2
A1*,A2,A3,B1*,B2
A1*,A2,A3,B1,B2
A1,A2,A3,B1,B2
A1*,A2,A3,B1*,B2,B3
A1*,A2,A3,B1,B2,B3
A1,A2,A3,B1,B2,B3
A1
A1,B1
A1,A2,B1
A1,A2,B1,B2
A1,A2,A3,B1,B2
A1,A2,A3,B1,B2,B3
A1,A2,A3,A4,B1,B2,B3
A1*
A1
A1*,B1
A1,B1
A1*,A2,B1
A1,A2,B1
A1*,A2,B1,B2
A1,A2,B1,B2
A1*,A2,A3,B1,B2
A1,A2,A3,B1,B2
A1*,A2,A3,B1,B2,B3
A1,A2,A3,B1,B2,B3
A1*,A2,A3,A4,B1,B2,B3
A1,A2,A3,A4,B1,B2,B3
— — — — — — — — — — — — — —
NOTE: Thesecapacitycontrolsteps may vary due to lag compressor sequencing.
%
17 28 33 44 50 61 67 78 83 94
100
17 22 28 33 39 44 50 55 61 67 72 78 83 89 94
100
14 25 44 56 75 86
100
— — — — — — — — — — — — — —
14 21 25 40 44 51 56 71 75 82 86 96
100
CompressorsDisplacement Displacement
11
11
A1*,A2,A3,B1*,B2,B3
A1,A2,A3,A4,B1,B2,B3
9
A1,A2,A3,A4,B1*,B2,B3
A1,A2,A3,A4,B1,B2,B3
B1*
B1
A1,B1*
A1,B1
A1,B1*,B2
A1,B1,B2
A1,A2,B1*,B2
A1,A2,B1,B2
A1,A2,B1*,B2,B3
A1,A2,B1,B2,B3
A1,A2,A3,B1*,B2,B3
A1,A2,A3,B1,B2,B3
B1*
B1
A1*,B1*
A1,B1*
A1,B1
A1*,B1*,B2
A1,B1*,B2
A1,B1,B2
A1*,A2,B1*,B2
A1,A2,B1*,B2
A1,A2,B1,B2
A1*,A2,B1*,B2,B3
A1,A2,B1*,B2,B3
A1,A2,B1,B2,B3
A1,A2,A3,B1*,B2,B3
A1,A2,A3,B1,B2,B3
B1
A1,B1
A1,B1,B2
A1,A2,B1,B2
A1,A2,B1,B2,B3
A1,A2,A3,B1,B2,B3
— — — — — — — — — — — — — —
B1*
B1
A1,B1*
A1,B1
A1,B1*,B2
A1,B1,B2
A1,A2,B1*,B2
A1,A2,B1,B2
A1,A2,B1*,B2,B3
A1,A2,B1,B2,B3
A1,A2,A3,B1*,B2,B3
A1,A2,A3,B1,B2,B3
22
Page 23
Table 4C — Capacity Control Steps, 130-210 and Associated Modular Units (cont)
UNIT
SIZE
210, 315A, 390A,
420A/B (60 Hz)
A1**,B1**
210, 315A, 390A,
420A/B (50 Hz)
A1,B1
210, 315A, 390A,
420A/B (50 Hz)
A1**,B1
210, 315A, 390A,
420A/B (50 Hz)
A1,B1**
210, 315A, 390A,
420A/B (50 Hz)
A1**,B1**
*Unloaded compressor.
†Compressor unloader, standard.
**Compressor unloader, accessory.
††Two unloaders, both unloaded.
CONTROL
STEPS
10 11 12 13 14 15 16 17 18 19 20
10 11 12 13 14
10 11 12 13 14
10 11 12 13 14 15 16 17 18 19 20
LOADING SEQUENCE A LOADING SEQUENCE B
%
(Approx) (Approx)
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
11 17 22 25 28 33 36 48 52 56 59 63 67 78 83 86 92 97
100
26 35 51 67 84
100
23 26 32 35 48 51 65 67 81 84 97
100
— — — — — — — — — — — — — —
17 23 26 27 32 35 43 48 51 59 65 67 75 81 84 92 97
100
8
9
6 9
7 9
Compressors
A1*
A1
A1*,B1*
A1*,B1
A1,B1
A1*,A2,B1*
A1*,A2,B1
A1,A2,B1
A1*,A2,B1*,B2
A1*,A2,B1,B2
A1,A2,B1,B2
A1*,A2,A3,B1*,B2
A1*,A2,A3,B1,B2
A1,A2,A3,B1,B2
A1*,A2,A3,B1*,B2,B3
A1*,A2,A3,B1,B2,B3
A1,A2,A3,B1,B2,B3
A1*,A2,A3,A4,B1*,B2,B3
A1*,A2,A3,A4,B1,B2,B3
A1,A2,A3,A4,B1,B2,B3
A1
A1,B1
A1,A2,B1
A1,A2,B1,B2
A1,A2,A3,B1,B2
A1,A2,A3,B1,B2,B3
A1,A2,A3,A4,B1,B2,B3
A1*
A1
A1*,B1
A1,B1
A1*,A2,B1
A1,A2,B1
A1*,A2,B1,B2
A1,A2,B1,B2
A1*,A2,A3,B1,B2
A1,A2,A3,B1,B2
A1*,A2,A3,B1,B2,B3
A1,A2,A3,B1,B2,B3
A1*,A2,A3,A4,B1,B2,B3
A1,A2,A3,A4,B1,B2,B3
— — — — — — — — — — — — — —
A1*
A1
A1*,B1*
A1*,B1
A1,B1
A1*,A2,B1*
A1*,A2,B1
A1,A2,B1
A1*,A2,B1*,B2
A1*,A2,B1,B2
A1,A2,B1,B2
A1*,A2,A3,B1*,B2
A1*,A2,A3,B1,B2
A1,A2,A3,B1,B2
A1*,A2,A3,B1*,B2,B3
A1*,A2,A3,B1,B2,B3
A1,A2,A3,B1,B2,B3
A1*,A2,A3,A4,B1*,B2,B3
A1*,A2,A3,A4,B1,B2,B3
A1,A2,A3,A4,B1,B2,B3
NOTE: Thesecapacitycontrolsteps may vary due to lag compressor sequencing.
%
14 17 21 25 37 40 44 48 51 56 67 71 75 78 82 86 92 96
100
16 26 42 51 67 84
100
— — — — — — — — — — — — — —
11 16 20 26 36 42 46 51 62 67 78 84 94
100
11 16 17 20 26 34 36 42 43 46 51 59 62 67 75 78 84 92 94
100
CompressorsDisplacement Displacement
9
A1*,A2,A3,B1*,B2,B3
A1,A2,A3,B1*,B2,B3
A1*,A2,A3,A4,B1*,B2,B3
A1,A2,A3,A4,B1*,B2,B3
A1,A2,A3,A4,B1,B2,B3
A1,A2,A3,A4,B1,B2,B3
A1,A2,A3,B1*,B2,B3
A1,A2,A3,A4,B1*,B2,B3
A1,A2,A3,A4,B1,B2,B3
A1*,A2,A3,B1*,B2,B3
A1,A2,A3,B1*,B2,B3
A1*,A2,A3,A4,B1*,B2,B3
A1,A2,A3,A4,B1*,B2,B3
A1,A2,A3,A4,B1,B2,B3
B1*
B1
A1*,B1*
A1,B1*
A1,B1
A1*,B1*,B2
A1,B1*,B2
A1,B1,B2
A1*,A2,B1*,B2
A1,A2,B1*,B2
A1,A2,B1,B2
A1*,A2,B1*,B2,B3
A1,A2,B1*,B2,B3
A1,A2,B1,B2,B3
A1,A2,A3,B1,B2,B3
B1
A1,B1
A1,B1,B2
A1,A2,B1,B2
A1,A2,B1,B2,B3
A1,A2,A3,B1,B2,B3
— — — — — — — — — — — — — —
B1*
B1
A1,B1*
A1,B1
A1,B1*,B2
A1,B1,B2
A1,A2,B1*,B2
A1,A2,B1,B2
A1,A2,B1*,B2,B3
A1,A2,B1,B2,B3
A1,A2,A3,B1,B2,B3
B1*
B1
A1*,B1*
A1,B1*
A1,B1
A1*,B1*,B2
A1,B1*,B2
A1,B1,B2
A1*,A2,B1*,B2
A1,A2,B1*,B2
A1,A2,B1,B2
A1*,A2,B1*,B2,B3
A1,A2,B1*,B2,B3
A1,A2,B1,B2,B3
A1,A2,A3,B1,B2,B3
23
Page 24
Head Pressure Control
EXV UNITS (All 30GN units except 040 and 045 with op­tional brine) — The microprocessor controls the condenser fans in order to maintain the lowest condensing temperature possible, thus the highestunit efficiency. Instead of using the conventional head pressure control methods, thefansare con­trolled by the position of the EXV and suction superheat.
As the condensing temperature drops, the EXV opens to maintain the proper suction superheat.Once the EXV is fully open, if the condensing temperature continues to drop, the suction superheat begins to rise. Once the suction superheat is greater than 40 F (22.2 C), a fan stage is removed after 2 minutes.
As the condensing temperature rises, the EXV closes to maintain the proper suction superheat. Once the EXV has closed to 39.5% open (600 steps open), a fan stage is added after 2 minutes.
During start-up, all the condenser fans are started when the condensing temperature reaches 95 F (35 C) to prevent excessive discharge pressure during pulldown. See Table 5 for condenser fan sequence of operation.
For low-ambient operation, the leadfan in each circuit can be equipped with the optional or accessory Motormastert III head pressure controller. This control has its own sensor which is mounted on a return bend in the liquid portion of the condenser. It will vary the fan speed to maintain a satu­rated condensing temperature of 100 F. The controls auto­matically default to condensing temperature control during this first stage of condenser-fan operation. When subsequent fan stages start, the controls revert to EXV fan control.
TXV UNITS (30GN040,045 with optional brine only) — Head pressure control is based on set point control. The micro­processor stages the condenser fans to maintain the set point temperature specified by the controller.
Keypad andDisplay Module (Also Called HSIO or LID) —
the operator to communicate with the processor. It is used to enter configurations and set points and to read data, perform tests, and set schedules. This device consists of a keypad with 6 function keys, 5 operative keys, 12 numeric keys (0 to 9, •,and -), and an alphanumeric, 8-character LCD. See Fig. 4. See Table 6 for key usage.
IMPORTANT: When entering multiple character in­puts beginning with a zero, a decimal point must be entered in place of the first zero. When entering an in­put of zero, only the decimal point need be entered.
ACCESSING FUNCTIONSANDSUBFUNCTIONS — See Tables6-8.Table 7 shows the 6 functions (identified by name) and the subfunctions (identified by number).
AUTOMATIC DEFAULT DISPLAY — When keypad has not been used for 10minutes, display automatically switches to the rotating automatic default display. This display has 7 parts, listed below, which appear in continuous rotating sequence.
DISPLAY EXPANSION TUE 15:45 TODAY IS TUE, TIME IS 15:45 (3:45 PM) LOCAL ON UNIT IN LOCAL MODE CLOCK ON UNIT IS ON VIA CLOCK SCHEDULE 8 MODE TEMPERATURE RESET IN EFFECT COOL 1 NUMBER OF STAGES IS 1 2 ALARMS THERE ARE 2 ALARMS
3 MINS
The only function of this module is to allow
3 MINUTES REMAINING IN THE OFF-TO-ON TIME DELAY
Pumpout
EXV UNITS — When the lead compressor in each circuit is started or stopped, that circuit goes through a pumpout cycle to purge the cooler and refrigerant suction lines of refrigerant.
The pumpout cycle starts immediately upon starting the lead compressor and continues until the saturatedsuctiontem­perature is 10° F (5.6° C) below the saturated suction tem­perature at start-up, is 10° F (5.6° C) below the cooler leav­ing fluid temperature, or reaches a saturated suction temperature of –15 F (–26 C). No pumpout is necessary if the saturated suction temperature is below –15 F (–26 C). At this point, the EXV starts to open and continues to open gradually to provide a controlled start-up to prevent liquid flood-back to the compressor.
At shutdown, the pumpout cycle continues until the satu­rated suction temperature for that circuit is 10° F (5.5° C) below the saturated suction temperature when pumpout is initiated, or saturated suction temperature reaches –15 F (–26 C). At that point, the compressor shuts down and the EXV continues to move until fully closed.
TXV UNITS — Pumpout is based on timed pumpout. On a command for start-up, the lead compressor starts. After 10 seconds, the liquid line solenoid opens.At shutdown, the liquid line solenoid closes, and the lead compressor contin­ues to run for 10 seconds before stopping.
Fig. 4 — Keypad and Display Module
24
Page 25
Table 5 — Condenser Fan Sequence
FAN ARRANGEMENT
040-050 1 FC-A1 Compressor A1
060,070 1 FC-A1 Compressor A1
080,090 (and associated modular units*) 1 FC-A1 Compressor A1
100,110 (and associated modular units*) 1 FC-A1 Compressor A1
130-170 (and associated modular units*) 5, 7 FC-A1 Compressor A1
190,210 (and associated modular units*) 5, 7 FC-A1 Compressor A1
*See Table 1. †Control box.
30GN
FAN NUMBER(S)
2 FC-B1 Compressor B1 3 FC-A2
4 FC-B2
2 FC-B1 Compressor B1
3, 4 FC-A2
5, 6 FC-B2
2 FC-B1 Compressor B1 3 FC-A2 4 FC-B2
3, 4, 5, 6
2 FC-B1 Compressor B1 3 FC-A2 4 FC-B2
5, 7, 6, 8 FC-A3, FC-B3
3, 4, 5, 6, 7, 8
6, 8 FC-B1 Compressor B1 3, 9 FC-A2
4, 10 FC-B2
1, 3, 9 FC-A2, FC-A3
2, 4, 10 FC-B2, FC-B3
6, 8 FC-B1 Compressor B1 3, 9 FC-A2
4, 10 FC-B2
1, 3, 9, 11 FC-A2, FC-A3
2, 4, 10, 12 FC-B2, FC-B3
FAN CONTACTOR
(FC)
FC-A2, FC-B2,
FC-A3, FC-B3
FC-A2, FC-A3,
FC-B2, FC-B3
CONTROLLED BY
First Stage
Microprocessor
Second Stage
Microprocessor
First Stage
Microprocessor
Second Stage
Microprocessor
First Stage
Microprocessor
Second Stage
Microprocessor
First Stage
Microprocessor
Second Stage
Microprocessor
Third Stage
Microprocessor
First Stage
Microprocessor
Second Stage
Microprocessor
First Stage
Microprocessor
Second Stage
Microprocessor
AUTOMATIC DISPLAY OPERATION/DEFAULT DIS­PLAY — This display automatically rotates as follows:
DOW — Day of Week HH Hour(s) MM Minute(s)
The default rotating display is displayed every 2 seconds if there has been no manual input from the keypad for 10 minutes.
To return to automatic display, enter at any time.
KEYPAD OPERATING INSTRUCTIONS (Refer to Table 9.)
1. White keys on left side of keypad are shown and oper­ated in these instructions according to the following ex-
ample: keypad entry meanspressthe , then the white key marked .
2. The standard display uses abbreviations. Expanded in­formation scrolls through the display whenever key
is pressed.
25
Page 26
Table 6 — Keypad and Display Module Usage
FUNCTION
KEYS
OPERATIVE
KEYS
STATUS — For displaying diagnostic codes and current operating information about the machine.
HISTORY — For displaying run time, cycles and previous alarms.
SERVICE — For entering specific unit configura­tion information.
TEST — For checking inputs and outputs for proper operation.
SCHEDULE — For entering occupied/unoccupied schedules for unit operation.
SET POINT — For entering operating set points and day/time information.
EXPAND — For displaying a non-abbreviated ex­pansion of the display.
CLEAR — For clearing the screen of all displays. UP ARROW — For returning to previous display
position. DOWN ARROW — For advancing to next display
position. ENTER — For entering data.
USE
USE
Table 7 — Functions and Subfunctions
3. All functions are made up of a group of subfunctions. To enter a subfunction, first press subfunction number de­sired. Then press the function key in which the subfunc­tion resides. To move within that subfunction, press
the or arrow. For example, a enters the Temperature Information subfunction.
4. At any time, anothersubfunctionmay be entered by press­ing the subfunction number, then the function key.
5. Prior to startingunit, check leaving fluid setpoint for cor­rect setting. Refer to Set Point Function section on page 38.
6. Depending on system configuration, all displays may not be shown. All displays are shown unless marked with the following symbol:
†Must be configured. For additional unit start-up procedures, see separate
Installation, Start-Up, and Service Instructions supplied with unit.
FUNCTIONS
SUBFUNCTION
NO.
1 Automatic 2 Alarm 3 Mode (Operating) 4 Capacity 5 Set Points 6 Temperatures Period 4
7 Pressures Period 5 8 Analog Inputs Period 6
9 Discrete Inputs Period 7 10 Outputs Period 8 11 HOLIDAYS
Status Test Schedule Service History Set Point
Display Display Display Stages (Current Operating)
Outputs Override Log On and Compressors
and Unloaders Calibrate
Transducers — Period 2 Field
Period 3 Service
Clock Select Version Period 1 Factory
Log Off (Software) Configuration Configuration Configuration
Run Time Set Points Starts Reset Alarm
History — Date and
Leaving Chiller
(Chiller Fluid) Set Points
Demand Limit Set Points
Time Fluid Alert Limit
26
Page 27
Table 8 — Accessing Functions and Subfunctions
OPERATION
To access a function, press subfunction no. and function name key. Display shows sub­function group.
To move to other elements, scroll up or down using arrow keys. NOTE: These displays do not show if control is not configured for reset.
When the last element in a subfunction has been displayed, the first element is repeated.
To move to next subfunction it is not necessary to use subfunction number. Press function name key to ad­vance display through all subfunctions within a function and then back to the first.
To move to another function, either depress function name key for desired function (display shows the first subfunction),
Access a specific sub­function by using the sub­function number and the function name key.
or
KEYPAD DISPLAY
ENTRY RESPONSE
RESET RESET SETPOINTS
CRT1 x COOL RESET AT 20 MA CRT2N x COOL RTEMP (NO RESET) CRT2F x COOL RTEMP (FULL RESET) CRT2D x COOL DEGREES RESET
RESET RESET SETPOINTS CRT1 x COOL RESET AT 20 MA
DEMAND DEMAND LIMIT SETPOINTS
TIME
SETPOINT UNIT SETPOINTS
X ALARMS THERE ARE n ALARMS
STAGE
EXPANSION
CURRENT TIME AND DAY OF WEEK
CAPACITY STAGING INFORMATION
Table 9 — Keypad Directory
STATUS
SUBFUNCTION KEYPAD ENTRY DISPLAY COMMENT
1 AUTOMATIC DISPLAY
2 ALARMS/ALERTS
To toggle between inputs (Yes/No) Press: (no) or (yes)
3 MODES
Refer to Automatic Display Operation/Default Display section on page 25.
X ALARMS Number of Tripped Alarms/Alerts R S AL Reset all Alarms/Alerts ALARM* X ALARM* X ALARM* X ALARM* X ALARM* X
X MODES Number of Modes in Effect X MODE X MODE X MODE
}
Displays Tripped Alarms/Alerts
Displays Mode in Effect
}
X MODE
27
Page 28
Table 9 — Keypad Directory (cont)
STATUS (cont)
SUBFUNCTION KEYPAD ENTRY DISPLAY COMMENT
4 STAGE
5 SET POINT
STAGE Capacity Staging Information COOL X Number of Requested Stages CAPT X Percent of Total Capacity CAPAX Percent Circuit A Total Capacity CAPB X Percent Circuit B Total Capacity AVAIL X Percent Available Capacity AVA X Percent Circuit AAvailable Capacity AV B X Percent Circuit B Available Capacity LMT X† Demand Limit Set Point (percent) CIRA X Circuit A Compressor Relay Status CIRB X Circuit B Compressor Relay Status SMZ X Load/Unload Factor for Compressors
Factor = 1 Unloader Factor = 0.6 SETPOINT Fluid Set Point Information SET X Set Point (F) MSP X Modified Set Point = Set Point + Reset (F) TW X Actual Control Temperature (F)
6 TEMPERATURE
LEGEND
CCN — Carrier Comfort Network EXV — Electronic Expansion Valve MOP — Maximum Operating Pressure
TEMPS Temperature Information (F) EWT X Cooler Entering Fluid Temperature (F) LWT X Cooler Leaving Fluid Temperature (F) SCTAX Circuit A Saturated Condenser Temperature (F) SSTAX Circuit A Saturated Suction Temperature (F) CTAX CompressorA1 Suction Temperature (F) SHA X Circuit A Suction Superheat (F) SCTB X Circuit B Saturated Condenser Temperature (F) SSTB X Circuit B Saturated Suction Temperature (F) CTB X Compressor B1 Suction Temperature (F) SHB X Circuit B Suction Superheat (F) SPC X Space Temperature (F) OAT X Outdoor-Air Temperature (F)
*Will read ALARM or ALERT as appropriate.
†Must be configured.
**If applicable.
††Not manually resettable. NOTE: If metric option is selected under , temperature
expressed as Celsius and pressure will be expressed as kPa.
28
Page 29
Table 9 — Keypad Directory (cont)
STATUS (cont)
SUBFUNCTION KEYPAD ENTRY DISPLAY COMMENT
7 PRESSURE
8 ANALOG
9 INPUTS
PRESSURE Refrigerant System Pressure (psig) MM DD YY Date of Last Calibration DPAX Circuit A Discharge Pressure (psig) SPAX Circuit A Suction Pressure (psig) XXXX XXX Circuit A Discharge/Suction (psig) OPAX Circuit A Oil Pressure Differential (psig) DPB X Circuit B Discharge Pressure (psig) SPB X Circuit B Suction Pressure (psig) XXXX XXX Circuit B Discharge/Suction (psig) OPB X Circuit B Oil Pressure Differential (psig)
ANALOG Status of Analog Inputs REF X Transducer Supply Voltage (volts) LMT X† Demand 4-20 mA Signal (mA) RST X† Reset 4-20 mA Signal (mA)
SW INPUT Status of Switch Inputs SPW X† Dual Set Point Switch (open/closed)
10 OUTPUTS
DL1 X† Demand Limit Switch 1 (open/closed) DL2 X† Demand Limit Switch 2 (open/closed)
OUTPUTS Status of Outputs ALMR X Alarm Relay K3 (on/off) FRA1 X Fan Relay K1 (on/off) FRA2 X Fan Relay K2 (on/off) FRB1 X Fan Relay K4 (on/off) FRB2 X Fan Relay K5 (on/off) CHWP X† Cooler Water Pump Relay K6 (on/off) ULA1 X Unloader A1 (on/off)** ULA2 X† Unloader A2 (on/off)** ULB1 X Unloader B1 (on/off)** ULB2 X† Unloader B2 (on/off)** LLSA X Liquid Line Solenoid A LLSB X Liquid Line Solenoid B EXVAX EXVA Percent Open†
LEGEND
CCN — Carrier Comfort Network EXV — Electronic Expansion Valve MOP — Maximum Operating Pressure
*Will read ALARM or ALERT as appropriate.
†Must be configured.
**If applicable.
††Not manually resettable. NOTE: If metric option is selected under , temperature
expressed as Celsius and pressure will be expressed as kPa.
29
Page 30
Table 9 — Keypad Directory (cont)
STATUS (cont)
SUBFUNCTION KEYPAD ENTRY DISPLAY COMMENT
10 OUTPUTS (cont)
EXVB X EXVB Percent Open** HGBA X† Hot Gas Bypass Relay Circuit A (on/off)** HGBB X† Hot Gas Bypass Relay Circuit B (on/off)** MMA X† MotormasterT A Output Percent** MMB X† Motormaster B Output Percent**
TEST
To use Test function, LOCAL/ENABLE-STOP-CCN switch must be in STOP position. To operate a test, scroll to desired test. Then, press to start test. Press to stop test.
SUBFUNCTION KEYPAD ENTRY DISPLAY COMMENT
1 OUTPUTS
OUTPUTS Test Outputs
8.8.8.8.8.8.8.8 Display Check ALMR X Energize Alarm Relay K3 (on/off) FRA1 X Energize Fan Relay A1 K1 (on/off) FRA2 X Energize Fan Relay A2 K2 (on/off) FRB1 X Energize Fan Relay B1 K4 (on/off) FRB2 X Energize Fan Relay B2 K5 (on/off) CHWP X† Energize Cooler Water Pump K6 (on/off) LSVAX Energize Liquid Line SolenoidA (on/off)** LSVB X Energize Liquid Line Solenoid B (on/off)** EXVAX Enter Desired EXVA Position (percent)** EXVB X Enter Desired EXVB Position (percent)** HGBA X† Energize Hot Gas Bypass Relay A (on/off)** HGBB X† Energize Hot Gas Bypass Relay B (on/off)** MMA X† Enter Desired MotormasterA Output Signal (percent)** MMB X† Enter Desired Motormaster B Output Signal (percent)**
To toggle between inputs (Yes/No) Press: (no) or (yes)
During compressor test, compressors start and run for 10 seconds. Compressor service valves and liquid line valves must be open. Energize crankcase heaters 24hours prior to performing compressor tests.
SUBFUNCTION KEYPAD ENTRY DISPLAY COMMENT
2 COMPRESSORS AND
UNLOADERS
COMP Compressor and Unloader Test CPA1 X Test Compressor A1 (on/off) CPA2 X† Test Compressor A2 (on/off)**
30
Page 31
SUBFUNCTION KEYPAD ENTRY DISPLAY COMMENT
2 COMPRESSORS AND
UNLOADERS (cont)
Table 9 — Keypad Directory (cont)
TEST (cont)
CPA3 X† Test Compressor A3 (on/off)** CPA4 X† Test Compressor A4 (on/off)** CPB1 X Test Compressor B1 (on/off) CPB2 X† Test Compressor B2 (on/off)** CPB3 X† Test Compressor B3 (on/off)** CPB4 X† Test Compressor B4 (on/off)** UNA1 X Energize Unloader A1 (on/off)** UNA2 X† Energize Unloader A2 (on/off)** UNB1 X Energize Unloader B1 (on/off)** UNB2 X† Energize Unloader B2 (on/off)**
3 CALIBRATE
TRANSDUCERS
XDR CAL Transducer Calibration CDPAX Circuit A Discharge Pressure (psig) CSPAX Circuit A Suction Pressure (psig) COPAX Circuit A Oil Pressure (psig) CDPB X Circuit B Discharge Pressure (psig) CSPB X Circuit B Suction Pressure (psig) COPB X Circuit B Oil Pressure (psig)
SCHEDULE
The Schedule function key is used to configure the occupancy schedule. The clock select subfunction can be used for unoccupied shutdown or unoccupied setback depending on the cooling set point control configuration. The Schedule function
described is for clock 1, which is the internal clock. Password required for all subfunctions except override.
SUBFUNCTION KEYPAD ENTRY DISPLAY COMMENT
1 OVERRIDE
For example, to extend current occupied mode for 3 hrs, press:
2 CLOCK SELECT
OVRD X Number of Override Hrs (0 - 4 Hrs)
OVRD 3 Extended Occupied Time
CLOCK XX Type of Clock Control
0 = No Clock, 1 = Clock 1 (Internal)
3 PERIOD 1 Yes = Schedule Opera-
tional for that day
LEGEND
CCN — Carrier Comfort Network EXV — Electronic Expansion Valve MOP — Maximum Operating Pressure
*Will read ALARM or ALERT as appropriate.
†Must be configured.
**If applicable.
PERIOD 1 Period 1 Time Schedule OCC HH.MM Occupied Time UNO HH.MM Unoccupied Time MON X Monday Flag (yes/no) TUE X Tuesday Flag (yes/no) WED X Wednesday Flag (yes/no) THU X Thursday Flag (yes/no)
††Not manually resettable. NOTE: If metric option is selected under , temperature
expressed as Celsius and pressure will be expressed as kPa.
31
Page 32
Table 9 — Keypad Directory (cont)
SCHEDULE (cont)
SUBFUNCTION KEYPAD ENTRY DISPLAY COMMENT
3 PERIOD 1 (cont)
To toggle between inputs (Yes/No) Press: (no) or (yes)
4 PERIOD 2
5 PERIOD 3 ... 9 PERIOD 7
10 PERIOD 8
11 HOLIDAYS
New = Unassigned Holiday Date
For example: To enter July 4th holiday press: 07.04.01 . Display shows Jul 04. For further information on the Schedule function and its operation, refer to Schedule Function section on page 44.
...
FRI X Friday Flag (yes/no) SAT X Saturday Flag (yes/no) SUN X Sunday Flag (yes/no) HOL X Holiday Flag (yes/no)
PERIOD 2 Period 2 Time Schedule PERIOD 3 ...
PERIOD 7 PERIOD 8 Period 8 Time Schedule
HOLIDAYS Define Calendar Holidays DAT MM.DD Holiday Date 1
DAT MM.DD.NN Holiday Date 30
Period 3 ... Period 7 Time Schedule
SERVICE
To view and modify configurations, the password must be entered under the log on subfunction.
SUBFUNCTION KEYPAD ENTRY DISPLAY COMMENT
1 LOG ON AND LOG OFF
At this time, configurations may be modified. When finished viewing and/or modifying configurations, log out as follows:
2 VERSION
The next 3 subfunctions provide the ability to modify configurations. Refer to separate Installation, Start-Up, and Service Instructions supplied with unit for further information on changing configurations.
To change a configuration, enter the new configuration and press while on the correct configuration.
3 FACTORY
CONFIGURATION
PASSWORD Enter Password/Disable Password Protection LOGGEDON Logged On
LOGGEDON — LOG OFF Disable Password Protection EXIT LOG Logged Off/Enable Password Protection
VERSION Software Information XXXXXXXX Version No. of Software (CESRXX)
FACT CFG Factory Configuration Codes
XXXXXXXX Configuration Code 1 XXXXXXXX Configuration Code 2 XXXXXXXX Configuration Code 3 XXXXXXXX Configuration Code 4
32
Page 33
Table 9 — Keypad Directory (cont)
SERVICE (cont)
SUBFUNCTION KEYPAD ENTRY DISPLAY COMMENT
3 FACTORY
CONFIGURATION (cont)
4 FIELD
CONFIGURATION
XXXXXXXX Configuration Code 5 XXXXXXXX Configuration Code 6 XXXXXXXX Configuration Code 7
FLD CFG Adjustable Field Configuration ENO X CCN Element Address BUS X CCN Bus Number BAUD X CCN Baud Rate FLUID X Cooler Fluid Select (water/medium brine) UNITS X Display Unit Select (English/Metric) DELAY X Delay at Power Up (minutes) NULA X No. Circuit A Unloaders NULB X No. Circuit B Unloaders HGB X Hot Gas Bypass Select (used, not used) SEQT X Loading Sequence Select (equal circuit, staged circuit) LEADT X Lead/Lag Sequence Type OPS X Oil Pressure Switch Select (enable/disable) HEADT X
Head Pressure Control Type (none, air cooled, water cooled)
MM X MotormasterT Select CSPTYP X Cooling Set Point Control Select CRTYP X Cooling Reset Control Select ERTYP X External Reset Sensor Select OATSEL X Outdoor-Air Sensor Select LSTYP X Demand Limit Control Select RAMP X Ramp Load Select (enable, disable) LOCK X Cooler Pump Interlock Select CPC X Cooler Pump Control Select REMA X Remote Alarm Option Select (yes/no) ALRST X Allow Local/Stop/CCN Reset of Alarms (yes/no)
To toggle between inputs (Yes/No) Press: (no) or (yes)
5 SERVICE
CONFIGURATION
SRV CFG Service Configurations XXXXXXXX Configuration Code 8 XXXXXXXX Configuration Code 9 REFRIG X Refrigerant TDTYP X Pressure Transducer Select OPS X Oil Transducer Set Point (psig) LPS X Low Pressure Set Point (psig) FANTYP X Fan Staging Select SH X EXV Superheat Set Point (F) MOP X EXV MOP Set Point (F) ZM X Z Multiplier
CCN — Carrier Comfort Network EXV — Electronic Expansion Valve MOP — Maximum Operating Pressure
*Will read ALARM or ALERT as appropriate.
†Must be configured.
LEGEND
33
**If applicable.
††Not manually resettable.
NOTE: If metric option is selected under , temperature expressed as Celsius and pressure will be expressed as kPa.
Page 34
Table 9 — Keypad Directory (cont)
HISTORY
SUBFUNCTION KEYPAD ENTRY DISPLAY COMMENT
1 RUN TIME
2 STARTS
RUN TIME Run Time Information HR X Total Hrs Unit Has a Comp Operating HRA X Circuit A Run Time HRB X Circuit B Run Time HA1 X Circuit A, Comp A1 Operating Hours HA2 X Circuit A, Comp A2 Operating Hours** HA3 X Circuit A, Comp A3 Operating Hours** HA4 X Circuit A, Comp A4 Operating Hours** HB1 X Circuit B, Comp B1 Operating Hours HB2 X Circuit B, Comp B2 Operating Hours** HB3 X Circuit B, Comp B3 Operating Hours** HB4 X Circuit B, Comp B4 Operating Hours**
STARTS Starts Information CY X Cycles from Stage 0 to Stage 1 CYAX Circuit A Starts CYB X Circuit B Starts CA1 X Circuit A, Comp A1 Starts CA2 X Circuit A, Comp A2 Starts** CA3 X Circuit A, Comp A3 Starts** CA4 X Circuit A, Comp A4 Starts** CB1 X Circuit B, Comp B1 Starts CB2 X Circuit B, Comp B2 Starts** CB3 X Circuit B, Comp B3 Starts** CB4 X Circuit B, Comp B4 Starts**
3 ALARM/ALERT HISTORY††
LEGEND
CCN — Carrier Comfort Network EXV — Electronic Expansion Valve MOP — Maximum Operating Pressure
ALRMHIST Last 10 Alarms/Alerts ALARM X ALARM X ALARM X ALARM X ALARM X ALARM X ALARM X ALARM X ALARM X ALARM X
}
*Will read ALARM or ALERT as appropriate.
†Must be configured.
**If applicable.
††Not manually resettable. NOTE: If metric option is selected under , temperature
expressed as Celsius and pressure will be expressed as kPa.
Alarm/Alert Description
34
Page 35
Table 9 — Keypad Directory (cont)
SET POINT
To read a set point, go to proper subfunction and read desired set point. To change a set point, enter new set point value, then press . LOCAL/ENABLE-STOP-CCN switch must be in LOCAL/ENABLE or STOP position.
SUBFUNCTION KEYPAD ENTRY DISPLAY COMMENT
1 SET POINTS
2 RESET SET POINTS
3 DEMAND SET POINTS
SET POINT Unit Set Point CSP1 X Chiller Fluid Set Point 1 (F) CSP2 X Chiller Fluid Set Point 2 (F) HSPAX Head Pressure Set Point Circuit A (F) HSPB X Head Pressure Set Point Circuit B (F) CRAMP X Cooling Ramp Loading Rate (F)
RESET Reset Set Points CRT1 X Cooling reset at 20 mA (F) CRT2N X Reference Temperature at No Reset (F) CRT2F X Reference Temperature at Full Reset (F) CRT2D X Total Degrees of Reset (F) CRT3N X Chiller Fluid DT at No Reset (F) CRT3F X Chiller Fluid DT at Full Reset (F) CRT3D X Total Degrees of Reset (F)
DEMAND Demand Set Points DLS1 X† Demand Switch 1 Set Point (percent) DLS2 X† Demand Switch 2 Set Point (percent) DL20 X Demand Limit at 20 mA (percent) DLGN X Loadshed Group Number LSDD X Loadshed Demand (percent) TIME X Minimum Loadshed Time (minutes)
4 DATE AND TIME
5 LEAVING CHILLER
FLUID ALERT LIMIT
LEGEND
CCN — Carrier Comfort Network EXV — Electronic Expansion Valve MOP — Maximum Operating Pressure
DATE.TIME Date, Time and Day of Week DOW.HR.MIN Day1=Mon,2=Tues...7=Sun
Hours are displayed in 24-hr time. Decimal point serves as colon.
MM.DD.YR Month.Day.Year. When entering date, enter a decimal
point between entries. Each entry must be two numbers.
LMT X Leaving Chiller Fluid Alert Limit (F)
*Will read ALARM or ALERT as appropriate.
†Must be configured.
**If applicable.
††Not manually resettable. NOTE: If metric option is selected under , temperature
expressed as Celsius and pressure will be expressed as kPa.
35
Page 36
STATUS FUNCTION — This function shows the rotating display, current status of alarm and alert (diagnostic) codes, capacity stages, operating modes, chilled water set point, all measured system temperatures and pressures, superheat val­ues, pressure switch positions, analog inputs, and switch in­puts. These subfunctions are defined on pages 36 and 37.
(Rotating Display)
To reset alarms/alerts using keypad and display module:
KEYPAD
ENTRY
DISPLAY
RESPONSE
RSAL DSB
RSAL ENB
COMMENTS
Reset all alarms/alerts function disabled
Reset all alarms/alerts function enabled
(Alarms/Alerts) — Alarms and alerts are messages that one or more faults have been detected. Each fault is as­signed a code number which is reported with the alarm or alert. See Table 10 for code definitions. The codes indicate failures that cause the unit toshut down, terminate an option (such as reset) or result in the use of a default value as set point.
Up to 10 codes can be stored at once. To view them in sequence, press to enter the alarm/alert dis­plays and then press to move to the individual dis­plays. Press after a code has been displayed. The mean-
ing of the code scrolls across the screen. See Example 1.
Example 1 — Reading Alarm Codes
KEYPAD DISPLAY
ENTRY RESPONSE
TUE 12:45 LOCAL ON CLOCK ON 13 MODE 8 MODE COOL 1 2 ALARMS 3 MINS
2 ALARMS 2 alarms/alerts detected RSAL DSB Reset all alarms/alerts ALARM 9 First alarm/alert code
COOLER LEAVING FLUID THERMISTOR FAILURE
ALARM 42 COOLER FREEZE
PROTECTION
Keypad has not been used for at least 10 minutes. Alternating summary display appears on screen
Explanation of alarm/alert code Second alarm/alert code.
Cooler freeze protection Explanation of alarm/alert code
COMMENTS
When a diagnostic (alarm or alert) code is stored in the display and themachine automatically resets, the code is de­leted. Codes for safeties which do not automatically reset are not deleted until the problem is corrected and either the machine is switched to STOP position, then back to LOCAL/ ENABLE or CCN position, or by using the keypad and dis­play module.
(Modes) — The operating mode codes are dis­played to indicate the operating status of the unit at a given time. See Table 10.
To enter the MODES subfunction, press and press the key to determine if more than one mode ap­plies. See Example 2 to read current mode with expansion.
Example 2 — Reading Current Operating Modes
KEYPAD DISPLAY
ENTRY RESPONSE
TUE 15:45 LOCAL ON CLOCK ON 8 MODE COOL 1 0 ALARMS 3 MINS
2 MODES There are 2 modes currently in effect LOCAL ON Unit is on by chiller on/off switch 8 MODE Temperature reset is in effect
Keypad has not been used for at least 10 minutes. Rotating summary display appears on screen
COMMENTS
(Stage) — This subfunction displays the capac-
ity stage number. See Tables 4A-4C for compressor loading sequence. To enter the STAGE subfunction, press
and press the to display the stage number.
Continue pressing for the following information:
• Number of requested stages.
• Percent of total unit capacity being utilized.
• Percent of each circuit capacity being utilized.
• Percent of total capacity available.
• Percent of capacity available in each circuit.
• Demand limit set point in effect (can be any value be-
tween 0% and 100%).
• Status of each compressor relay. When a compressor is
on, the number of that compressor is displayed. If a com­pressor is off,a0isdisplayed. For example: In a given circuit, if compressors 1and 3 are running, and2 and 4 are not running, 0301 is displayed for that circuit.
• Load/Unload factor for compressors. This factor is an in-
dication of when a step of capacity is added or subtracted. Its value can range from slightly less than –1.0 to slightly more than +1.0. When load/unload factor reaches +1.0, a compressor is added.When the load/unload factorreaches –1.0, a compressor is subtracted. If compressor unloaders are used, at –.6 a compressor is unloaded and at +.6, a compressor is loaded up.
36
Page 37
Table 10 — Operational and Mode Display Codes
The operating modes are displayed by name or code num­ber, to indicate the operating status of the unit at a given time. The modes are:
CODE DESCRIPTION
Unit isoff.LOCAL/ENABLE-STOP-CCN switch is in
LOCAL OFF
CCN OFF
CLOCK OFF
LOCAL ON
CCN ON
CLOCK ON
MODE 7
MODE 8
MODE 9
MODE 10 MODE 11 Not applicable.
MODE 12
MODE 13
MODE 14
MODE 15 Water System Manager is controlling the chiller. MODE 16 Slow change override is in effect. MODE 17 X minute off-to-on delay is in effect. MODE 18 Low suction superheat protection is in effect.
CCN — Carrier Comfort Network
OFFposition,or LOCAL/ENABLE-STOP-CCNswitch may be in LOCAL position with external ON/OFF switch in OFF position.
Unit is off due to CCN network command. LOCAL/ ENABLE-STOP-CCN switch is in CCN position.
Unit is off due to internal clock schedule. LOCAL/ ENABLE-STOP-CCN switch is in LOCAL position.
Unit ison.LOCAL/ENABLE-STOP-CCN switch is in LOCALposition.Ifexternal ON/OFF switch is used, it will be in ON position.
Unit is on due to CCN command. LOCAL/ENABLE­STOP-CCN switch is in CCN position.
Unit is on due to internal clock schedule or occu­pied override function. LOCAL/ENABLE-STOP­CCN switch is in LOCAL/ENABLE position.
Dual set point is in effect. In this mode, unit contin­ues to run in unoccupied condition,butleaving fluid set point is automatically increased to ahigherlevel (CSP2 set point is in SET function).
Temperature reset is in effect. In this mode, unit is using temperature reset to adjust leaving fluid set point upward, and unitis currently controlling to the modifiedsetpoint.Theset pointcanbe modifiedbased onreturnfluid, outdoor-air temperature,or space tem­perature.
Demand limit is in effect. This indicates that ca­pacity ofunitis being limited by demandlimitcontrol option. Because of this limitation, unit may not be able to produce the desired leaving fluid temperature.
Flotronic™SystemManager (FSM) is controllingthe chiller.
Rampload(pulldown) limitingisin effect. Inthis mode, therateat which leavingfluidtemperature is dropped is limited to a predetermined value to prevent com­pressor overloading. See CRAMP set point in the SET function in Table 9. The pulldown limit can be modified, if desired, to any rate from .2 F to 2 F (.1° to 1° C)/minute.
Timedoverrideisineffect.This isa1to4hourtem­porary override of the programmed schedule, forc­ing unit to occupied mode. Override can be imple­mented with unit under LOCAL/ENABLE or CCN control. Override expires after each use.
Lowcoolersuction protection isin effect. Inthismode, circuit capacity is not allowed to increase if cooler saturated suction temperature is 20° F (11° C) for fluid or30°F(16° C) for brine ormorebelowleaving fluid temperature, and saturated suction tempera­ture is less than 32 F (0° C). If these conditions per­sistbeyond10 minutes, circuit isshutdown and fault code 44 or 45 is displayed.
(Set Point) — This subfunction displays leaving
fluid temperature and leaving chilled fluid set point. If unit is programmed for dual set point, the chilled fluid set point currently in effect (either occupied or unoccupied) is displayed. If reset is in effect, the unit operates to the modi­fied chilled fluid set point. This means the leaving fluid tem­perature may not equal the chilled fluid set point. The modified chilled fluid set point can also be displayed in the Status function. To enter the set point subfunction,
press and press to display the set point fol­lowed by the modified leaving chilled fluid set point and ac-
tual control temperature.
(Temperature) — The temperature subfunction dis-
plays the readings at temperature sensing thermistors. To read a temperature, enter , then scroll to de-
sired temperature using the key. See Table 9 for the order of readouts. This subfunction also displays the satu-
rated refrigerant temperatures corresponding to the suction and discharge pressures measured by the compressor transducers.
(Pressure) — This subfunction displays suction,
discharge, and net oil pressure at lead compressor of each circuit of unit.
(Analog Inputs) — This subfunction displays
analog inputs, if any. Press , then press . The transducer supply voltage, 4-20 mA reset signal can be dis-
played. This is useful for problem diagnosis prior to using the test function.
(Discrete Inputs) — This subfunction displays sta-
tus (open/closed) of discrete input switch where applicable. Status of dual set point switch and demand limit switches 1 and 2 can be displayed. This is useful for problem diagnosis prior to using the test function.
(Outputs) — This function displays on/off sta-
tus of alarm relay, all fan relays, and chilled water pump relay. It also displays on/off status of compressor unloaders (if used). The position of each EXV(in percent open) can be displayed.
TEST FUNCTION — The test function operates the diag­nostic program. To initiate test function, the LOCAL/ ENABLE-STOP-CCN switch must be in STOP position.
To reach a particular test, press its subfunction number,
then scroll to desired test by pressing . Press to start a test. Press or or to terminate or exit a test. Pressing the key after a test has started advances
system to next test, whether current test is operating or has timed out. Once in the next step, you may start
test by pressing or advance past it by pressing .
While the unit is in test, you may leave test function and access another display or function by pressing appropriate keys. However, a component that is operating when an­other function is accessed remains operating. You must
re-enter test function and press to shut down the com­ponent. Components with a timed operating limit time out
normally even if another function is accessed.
37
Page 38
Keypad entry allows the operator to make the
following checks by using :
• LID display check. Proper display is 8.8.8.8.8.8.8.8.
• Operation of alarm relay.
• Operation of condenser fans.
• Operation of chilled fluid pump.
• Operation of liquid line solenoids.
• Operation of the hot gas bypass relays.
• Operation of EXVs. To drive EXV fully open, enter (100% open). To drive EXV fully closed, en-
ter (0% open).
• Operation of each remote alarm.
• Operation of Motormastert signals.
Keypad entry accesses the compressor and
compressor unloader operational tests.
During compressor operational tests, compressor starts and runs for 10 seconds. Compressorservicevalvesmust be open. Energize crankcase heaters 24 hours prior to performing compressor tests.
Since test function checks only certain outputs, it is good
practice to also check all inputs and outputs accessible through the status function. These are located at ,
, and (see Table 9). If keypad is not used
for 10 minutes, unit automatically leaves test function and resumes rotating display. See Example 3.
Example 3 — Using Test Function
KEYPAD DISPLAY
ENTRY RESPONSE
COMP Factory/field test of compressors
CPA1 OFF Circuit A, Compressor 1A test CPA1 ON Pressing ENTR starts the test:
CPA1 OFF If the test is allowed to time out (10 sec­CPA 2 OFF Pressingthedown arrow keyadvances the
NOTE: Once a compressor has been run using the function, it is not allowed to run again for 30 seconds.
subfunction of test function
when the compressor should be running the display shows CPA1 on
onds) the display will show CPA1 off system to Circuit A, compressor 2 test
COMMENTS
accesses the transducer calibration subfunction.
All transducers must be calibrated in order for the unit to operate. Refer to Pressure Transducers section on page 60 for calibration procedure.
HISTORY FUNCTION — Pressing and dis­plays total unit run time, total run time for each circuit, and
total run time for each compressor.
Pressing and displays total unit starts, the
total starts for each circuit, and total starts for each com­pressor.Pressing and displays the last 10alarms
along with a description of each alarm.
SET POINT FUNCTION — Set points are entered through the keypad. Set points can be changed within the upper and lower limits, which are fixed. The ranges are listed below.
Chilled Fluid Set Point
Water:
38 to 86 F (3.3 to 30 C)
Medium Brine:
14 to 86 F (–10 to 30 C)
Pulldown Set Point
0.2 to 2.0 F (0.11 to 1.1 C)/min.
Reset Set Points
Maximum Reset Range:
–30° to 30° F (–17° to 17° C) External Temperature Reset –40 to 240 F
(–40 to 118 C)
Chiller Fluid DT: 0° to 15° F
(0° to 8° C)
External Signal Reset 4 to 20 mA
Demand Limit Set Points
Switch Input:
Step1—0to100% Capacity Reduction Step2—0to100% Capacity Reduction
External Signal:
Maximum Demand Limit 4 to 20 mA Minimum Demand Limit 4 to 20 mA
Loadshed Demand Delta: 0 to 60% Maximum Loadshed Time: 0 to 120 min.
Set points are grouped in subfunctions as follows:
Subfunction displays chiller fluid set points.
a. The first value shown is the occupied chilled fluid set
point.
b. The next value displayed depends on how the sched-
ule function has been programmed. (See pages 44-
47.) If dual set point has been selected, the next set point after has been pressed is the second chilled
fluid set point. If single set point or inactive sched­ule has been selected in the schedule function,
then when is pressed, the display shows the head pressure set points, one for each circuit. These
are utilized only if the set point controlled method of head pressure control is selected in .
c. The final value displayed when the is pressed
is the cooling ramp loading rate. This is the maximum rate at which the leaving chilled fluid is allowed to drop, and can be field set from 0.2 to 2.0 F (.11° to
1.1° C)/minute. This value is not displayed unless the function is enabled (see Adjustable Field Configura­tions on page 44).
Reading and Changing Set Points — Example 4 shows how to read and change thechilled fluid set point. Other setpoints can be changed by following the same procedure. Refer to Table 9 for the sequence of display of set points in each sub­function.
38
Page 39
Example 4 — Reading and Changing
Chilled Fluid Set Point
KEYPAD DISPLAY
ENTRY RESPONSE
SET POINT System set points CSP1 44.0 Present occupied chilled fluid
CSP1 42.0
CSP2 44.0 CSP2 50.0
RESET Displays the maximum reset
set point is 44.0 F Press the .
Display shows new occupied chilled fluid set point is 42.0 F
Present unoccupied chilled fluid set point is 44.0 F
Press the . Display shows new unoccupied chilled
fluid set point is 50.0 F set point. The minimum and
maximum reference reset set points can also be displayed.
These set points are not accessible when reset type has been configured for NONE in the service function.
COMMENTS
Subfunction displays temperature reset set points.
Temperature Reset Based on Return Fluid Temperature — The control system is capableof providing leaving fluid tem­perature reset based onreturn fluid temperature. Becausethe temperature difference between leaving and return tempera­ture is a measure of the building load, return fluid tempera­ture reset is essentially an averagebuildingloadreset method.
Under normal operation, the chiller maintains a constant leaving fluid temperature approximately equal tochilledfluid set point. As building load drops from 100% down to 0%, entering cooler fluid temperature dropsin proportion to load. Thus, temperature drop across the cooler drops from a typi­cal 10 F (5.5 C) at full load to a theoretical 0° F (0° C) at no load. See Fig. 5.
At partial load, leaving chilled fluid temperature may be lower than required. If this is allowed to increase (reset), the efficiency of the chiller increases. Amount of reset can be defined as a function of cooler temperature drop, as shown in Fig. 5. This is a simple linear function that requires 3 pieces of input data for the set function that will vary de­pending on measurement method used as follows (see Table 11):
NOTE: Reset set points are not accessible unless the reset function is enabled first. This is done as a field
configuration. Select one of the 4 choices for type of reset: Return Fluid Reset, External Temperature Reset, 4-20 mA External Signal Reset, or 4-20 mA Internal Signal Reset.
If dual set point control is enabled (see Field Wiring sec­tion on page 69), the amount ofreset is applied to whichever set point is in effect at the time.
Examples 5A-5C demonstrate how to activate reset. Ex­ample 6 demonstrates how to change the type of reset. As­sume that reset is to be based on return fluid temperature, the desired reset range is to be 0° to 10° F (0° to 5.5° C) and full load is a 10° F (5.5° C) drop across the cooler. See Fig. 5.
Activating reset based on external temperature or 4-20 mA signal is done the same way, except the reference set point range is –40° to 240° F (–40° to 115° C), or 4 to 20 mA depending on which method was selected at the field configuration step.
Example 5A — External Reset
In this example, the unit set point is reset from full load at 90 F (32 C) to a maximum reset value of 10 F (5.5 C) at 20 F (–6.7 C) outdoor ambient.
NOTE: All temperatures given in this example are in F.
KEYPAD DISPLAY
ENTRY RESPONSE
FLD CFG CRTYP 0 Scroll past to reset type CRTYP 2 External reset selected ERTYP 0 ERTYP 1 OAT selected RESET CRT2N 0 CRT2N 90 CRT2F 0 CRT2F 20 CRT2D 0 Maximum reset is 0 CRT2D 10 Maximum reset is 10
COMMENTS
Scroll past to space thermistor sensor selected
Temperature for no reset is 0
Temperature for no reset is 90
Temperature for maximum reset is 0
Temperature for maximum reset is 20
INPUT DATA DESCRIPTION
Maximum Reset Amount — Allowable range for maximum amount which LWT is to be reset.
Maximum Reset Reference — Temperature at which maximum reset occurs.
Minimum Reset Reference — Temperature at which no reset occurs.
LEGEND
OAT — Outdoor-Air Temperature LWT — Leaving Fluid Temperature
Table 11 — Reset Amounts
MEASUREMENT METHOD
4-20 mA
Variable Limits (F) Variable Limits (F) Variable Limits (F)
CRT1 –30 to 30 CRT2D –30 to 30 CRT3D –30 to 30
CRT2F –40 to 240 CRT3F 0 to 15
CRT2N –40 to 240 CRT3N 0 to 15
OAT/Occupied Space
or Internal/External
Return Water
39
Page 40
Example 5B—4to20mAandInternally or
Externally Powered Reset
In this example, the unit set point is reset from full load at 4 mA to a maximum reset value of 10 F (5.5 C) at 20 mA. Internally powered 4 to 20 mAoption is used in this example.
NOTE: To use externally powered reset, when CRTYP
appears, press so CRTYP 4 appears in the display.The remainder of theinformation in the fol-
lowing example applies to either type of reset.
KEYPAD
ENTRY
DISPLAY
RESPONSE
FLD CFG CRTYP 0 Scroll past to reset type CRTYP 1 RESET
CRT1 0 Reset at 20 mA is 0 CRT1 10 Reset at 20 mA is 10
COMMENTS
Internally powered reset selected
Example 5C — Using Return Fluid
Temperature Reset
KEYPAD DISPLAY
ENTRY RESPONSE
FLD CFG
CSPTYP X Scroll past single/dual
CRTYP 0 CRTYP 3 RESET Reset set points
COMMENTS
Field configuration subfunction of service function
Display shows no reset type has been selected
Return fluid temperature is selected and activated
Temperature Reset Based on External Temperature — If de­sired, temperature reset can be based on an external tem­perature, such as space or outdoor-air temperature. This re­quires a thermistor (T10, Part No. 30GB660002) located in the space or outdoor air and wired to terminals as follows (also see Field Wiring section on page 69 and Fig. 6):
4 in/4 out Module — J7-15 and J7-16.
At the field configuration step, enter set points as de-
scribed in Examples 5A-5C on pages 39 and 40. Then select external temperature reset by entering when
CRTYP 0 appears. See Fig. 7. Temperature Reset Based on 4-20 mA Signal— If desired,
temperature reset can be based on a 4-20 mA signal. For proper connections, refer to Field Wiring section on page 69 and Fig. 8.
At the field configuration step, select 4-20 mA reset by
entering (internally powered) or (externally pow­ered) when CRTYP 0 appears. Then enter set points as de-
scribed previously in Examples 5A-C. See Fig. 8.
Subfunction displays demand limit set points.
Demand Limit, 2-Stage Switch Control — This control has been designed to accept demand limit signals from a build­ing load shedding control. The demand limit function pro­vides for 2 capacity steps. The keypad is used to set the 2 demand limit set points, which range from 100 to 0% of ca­pacity. Capacity steps are controlled by 2 field-supplied re­lay contacts connected to the designated chiller terminals. (See Field Wiring section on page 69 and Fig. 7.)
Fig. 5 — Cooling Return Fluid Reset
40
Page 41
Fig. 6 — Cooling External Temperature Reset
LEGEND
COMM — Communications Bus PWR Power SW Switch
NOTE: Forspecificconnection points, see Fig. 25 - 29.
Fig.7—4IN/4 OUT Options Module Wiring for Reset, Demand Limit, and Dual Set Point
41
Page 42
Fig. 8 — 4-20 mA Cooling Temperature Reset
Example 6 — Changing Reset Type
To change type of reset, first log on as shown in Table 12. Also refer to Set Point Function section, page 38, for information on entering reset set points using reset feature.
KEYPAD DISPLAY
ENTRY RESPONSE
FLD CFG
CSPTYP 0 CRTYP 0 CRTYP 1
CRTYP 2
CRTYP 3 CRTYP 4 CRTYP 0 Reset is deactivated
COMMENTS
Field configuration subfunction of service function
Scroll past single cooling set point
No reset has been selected
Internally powered 4-20 mA signal reset is selected
Space or outdoor-air temperature reset is selected
Return fluid temperature reset is selected
Externally powered 4-20 mA signal reset is selected
To use Demand Limit, first enable loadshed, then enter demand limit set points. See Example 7A. Closing the first stage demand limit contact putsuniton the first demand limit level, that is, the unit does not exceed the percentage of ca­pacity entered as demand limit stage 1. Closing contacts on second-stage demand limit relay prevents unit from exceed­ing capacity entered as demand limit stage 2. The demand limit stage that is set to the lowest demand takes priority if both demand limit inputs are closed.
The demand limit function must be enabled in order to function and may be turned off when its operation is not de­sired. The demand limit relays can, in off condition, remain connected without affecting machine operation.
Table 12 — Service Functions
To view and modify configurations, the password must be
entered under the log on subfunction.
SUB- KEYPAD
FUNCTION ENTRY
1 Log On
DISPLAY COMMENT
PASSWORD
LOGGEDON Logged On
Enter Password/ Disable Password
NOTE: Configurations may be modified at this time. When finished viewing and/or modifyingconfigurations, log out as follows:
LOGGEDON —
Disable Password Protection
Logged Off/ Enable Password Protection
Software Information
Version No. of Software
2 Version
LOG OFF
EXIT LOG
VERSION
XXXXXXXX
Demand Limit, 4 to 20 mA Signal — The controls can also accepta4to20mAsignal for load shedding. Input for the signal are terminals shown below:
Externally powered
Positive lead to J7-5 - 4 In/4 Out Module Negative lead to J7-6 - 4 In/4 Out Module
Internally powered
Positive lead to J7-6 - 4 In/4 Out Module Negative lead to J7-7 - 4 In/4 Out Module
See Field Wiring section on page 69 and Fig. 7.
42
Page 43
At field configuration step, select 4 to 20 mA loadshed by entering (internally powered) or (externally pow­ered) when the LSTYP 0 display appears. See Example 7B.
Then enter set points as follows. In this example, set points are coordinates of the demand limit curve shown in Fig. 9.
Example 7A — Using Demand Limit
(First Log On as Shown in Table 12)
KEYPAD DISPLAY
ENTRY RESPONSE
FLD CFG LSTYP 0 Loadshed is not enabled LSTYP 1
DEMAND
DLS1 80 DLS1 60 Loadshed reset to 60% DLS2 50 DLS2 40 Loadshed 2 reset to 40%
COMMENTS
Field configuration sub­function of service function
Loadshed is now enabled for 2-stage switch control
Demand Limit set points subfunction of set point function
Loadshed 1 currently set at 80%
Loadshed 2 currently set at 50%
To Disable Demand Limit:
KEYPAD DISPLAY
ENTRY RESPONSE
FLD CFG ERTYP 0 LSTYP 1 LSTYP 0 Loadshed is now disabled
NOTES:
1. Select 2 for internally powered 4 to 20 mA signal load limiting.
2. Select 3 for Carrier Comfort Network loadshed.
3. Select 4 for externally powered 4 to 20 mA signal load limiting.
COMMENTS
Field configuration sub­function of service function
Scroll past other elements in the subfunction
Loadshed is enabled for 2-stage switch control
Example 7B — Using Demand Limit (4-20 mA)
(First Log On As Shown in Table 12)
the loadshed demand delta, which defines the percent of the load to be removed when a loadshed command is in effect. The third set point is maximum loadshed time, which de­fines the maximum length of time that a loadshed condition is allowed to exist. The allowable range for this entry is zero to 120 minutes.
Subfunction displays date, time, and dayofthe week.
Reading and ChangingTime Display — Time is entered and displayed in 24-hour time. The day of the week is entered as a number.
1 = Mon, 2 = Tue, 7 = Sun, etc.
Key is used as the colon when entering time. See
Example 8.
subfunction accesses the leaving chillerfluid alert
limit (LMT) option. Thevalue to be enteredhere is the num­ber of degrees above the control set point at which an alert should be generated. For example, if the control set point is 44 F,and an alert isdesired (alert 70) if the fluid temperature reaches 50 F, then enter 6 for this set point. The allowable range for this entry is between 2 and 30 (F).
SERVICE FUNCTION — This function allows the techni­cian to view and input configuration data. Factory configu­ration data, field configuration data, and service configura­tion data may be viewed or entered through the keypad and display module. See Table 9 for a complete listing of con­figurable items. Whenever a processor module is replaced in the field, the complete list of configuration codes must be entered.
Logging On/Logging Off — The service function is pass­word protected. Therefore, to gain entry to this function,
this password must be entered. Pressing allows the technician to view, change, or enter configuration
codes. To log off, perform the following keystrokes:
. The service functionis once again password
protected. Software Information — displays the version
number of the software that resides in the processor module. The and subfunctions are summa-
rized in Table 12.
KEYPAD DISPLAY
ENTRY RESPONSE
FLD CFG ERTYP 0 LSTYP 0 Loadshed is not enabled
LSTYP 2
DEMAND Demand Limit set points DL20 100 Maximum demand limit is 100% DL20 90 Maximum demand limit is 90%
Field configuration subfunction of service function
Scroll past other elements in the subfunction
Loadshed is now enabled for 4-20 mA internally-powered signal control
COMMENTS
Scrolling past the 4 to 20mAdemand limit setpointbrings up the loadshed set points. The loadshed feature is activated by a redline alert and loadshed commands from the CCN loadshed option. The first set point is the group number, es­tablished by the CCN system designer. The second option is
43
Example 8 — Setting Time of Day and
Day of Week
KEYPAD DISPLAY
ENTRY RESPONSE
TIME
MON 16.00
TUE 13.05
JAN 01 90
APR 15 90
COMMENTS
Time display sub­function of set point function
Current setting is Monday, 4:00 p.m.
New setting of Tuesday, 1:05 p.m. is entered and displayed
Current date is Jan. 1, 1990
New setting April 15, 1990 is entered and displayed
Page 44
Fig. 9 — 4-20 mA Demand Limiting
Factory Configuration Codes — allows entry into the factory configuration subfunction. Under this subfunc-
tion, there are 7 groupsof configuration codes that are down­loaded at the factory. Each group is made up of 8 digits. If processor module is replaced in the field, these 7 groups of configuration codes must be entered through the keypad and display module. Factory configuration codes (groups 1 through 7) that apply to the particular Flotronic™ II chiller being serviced are found on a label diagram located inside the control box cover. See Table13 for a summary of factory configuration subfunction keystrokes.
Adjustable Field Configurations — After logging on, press
to enter subfunction. The subfunction allows opera­tion of the chiller to be customized to meet the particular needs of the application. The chiller comes from the factory preconfigured to meet the needs of most applications. Each item should be checked to determine which configuration alternative best meets the needs of a particular application. See Table 14 for factory loaded configuration codes and al­ternative configurations.
If processor module is replaced, the replacement module is preloaded with factory default configuration codes. Each configuration code must be checked and, if necessary, re­configured to meet needsof the application. See Table 14 for pre-loaded service replacement configuration codes.
Service Configuration Codes — Press to enter the service configuration subfunction. The first 2 itemsunder this
subfunction are 2 groups (8 digits each) ofconfigurationcodes that are downloaded at the factory. If processor module is
replaced in the field, the 2groupsof configuration codes must be entered through the keypad and display module. The 2 groups of configuration codes (groups 8 and 9) that apply to the unit being serviced can be found on a label diagram inside the control box cover. See Table 13 for keystroke in­formation to enter configuration codes 8 and 9. The remain­ing items in this subfunction are read-only data provided to assist in service evaluations.
SCHEDULE FUNCTION — This function provides ameans to automatically switch chiller from an occupied mode to an unoccupied mode. When using schedule function, chilled fluid pump relay must be used to switch chilled fluid pump on and off. Connections for chilled fluid pump relay are: TB3-3 and TB3-4. The chilled fluid pump relay starts chilled fluid pump but compressors do not run until remote chilled fluid pump interlock contacts are between TB6-1 and TB6-2 are closed and leaving chilled fluid temperature is abovesetpoint. If a remote chilled fluid pump interlock is not used, the first compressor starts (upon a call for cooling) approximately one minute after chilled fluid pump is turned on.
The unit can be programmedfor inactive, single set point,
or dual set point operation.
When unit is configured for inactive, chilled fluid pump relay remains energized continuously but is not used since chiller is usually controlled by remote chilled fluid pump in­terlock contacts.
When unit is configured for single set point operation, chilled fluid pump relay is energized whenever chiller is in occu­pied mode regardless of whether chiller is running. When chiller is in unoccupied mode, chilled fluid pump relay is not energized.
44
Page 45
Table 13 — Factory Configuration Keystrokes
To change a configuration enter the new configuration
and press while on the correct configuration.
SUB- KEYPAD
FUNCTION ENTRY
3 FACTORY
CFG
5 SERVICE
CFG
LEGEND
MOP — Maximum Operating Pressure EXV — Electronic Expansion Valve
DISPLAY COMMENTS
FACT CFG
XXXXXXXX
XXXXXXXX
XXXXXXXX
XXXXXXXX
XXXXXXXX
XXXXXXXX
XXXXXXXX
SRV CFG
XXXXXXXX
XXXXXXXX
FACTORY
CONFIGURATION
CODES
Configuration Code 1
Configuration Code 2
Configuration Code 3
Configuration Code 4
Configuration Code 5
Configuration Code 6
Configuration Code 7
SERVICE
CONFIGURATION
CODES
Configuration Code 8
Configuration Code 9
REFRIG X Refrigerant Type
TDTYPE X Pressure Transducer Select
OPS X Oil Pressure Set Point
LPS X Low Pressure Set Point
FANTYP X Fan Staging Select
SH X EXV Superheat Set Point
MOP X EXV MOP Superheat
ZM X Z Multiplier
When unit is configured for dual set point, chilled liquid pump relay is energized continuously, in both occupied and unoccupied modes. Occupied mode places occupied chilled water set point into effect; unoccupied mode places unoc­cupied chilled water set point into effect.
Scheduling — is usedtooverrideany current sched­ule in effect (for 0-4 hours). is used to activate a
clock for the scheduling function. - are used to program schedules for specific occupied and unoccupied
periods.
The schedule consists of from one to 8 occupied time pe­riods, set by the operator.These time periods can be flagged to be in effect or not in effect on each day of the week. The day begins at 00.00 and ends at 24.00. The machine is in unoccupied mode unless a scheduled time period isin effect. If an occupied period is to extend past midnight, it must be programmed in the following manner: occupiedperiod must end at 24:00 hours (midnight); a new occupied period must be programmed to begin at 00:00 hours.
Table 14 — Adjustable Field Configurations
FIELD CONFIGURATION
ITEM AND CODES
CCN element address (Entered by CCN Technician)
CCN Bus Number (Entered by CCN Technician)
CCN Baud Rate (Entered by CCN Technician)
Cooler Fluid Select 1 = Water (38 to 70 F
[3.3 to 21 C] Set Point)
2 = Medium Brine (15 to 70 F
[–9 to 21 C] Set Point)
Display Unit Select 0 = English 1 = Metric SI
Delay at Power Up 00 No. Circuit A Unloaders
0 = No Unloaders 1 = One Unloader 2 = Two Unloaders
No. Circuit B Unloaders 0 = No Unloaders 1 = One Unloader 2 = Two Unloaders
Hot Gas Bypass Select 0 = No Valve
Loading Sequence Select 1 = Equal Circuit Loading 2 = Staged Circuit Loading
Lead/Lag Sequence Select 1 = Automatic 2 = Manual, Circuit A Leads 3 = Manual, Circuit B Leads
Oil Pressure Switch Select 0 = Not Used 1 = Air Cooled
Head Pressure Control Type 0 = Not Used 1 = Air Cooled
Head Pressure Control Method 1 = EXV Controlled 2 = Set Point Control for
Both Circuits
3 = Set Point Control for
Circuit A; EXV Control for Circuit B
4 = Set Point Control for
Circuit B; EXV Control for Circuit A
MotormasterT Select 0 = None 2 = Indirect Control
Cooling Set Point Control Select 0 = Single Set Point Control 1 = External Switch
Controlled Set Point
2 = Clock Controlled
Set Point
Cooling Reset Control Select 0 = No Reset 1 = 4-20 mA, Internally Powered 2 = External Temperature
Reset 3 = Return Fluid Reset 4 = 4-20 mA, Externally Powered
External Reset Sensor Select 0 = Thermistor Connected to
Options Module 1 = Obtained Through CCN
Outdoor-Air Sensor Select 0 = Not Selected 1 = Selected
Demand Limit Control Select 0 = No Demand Limiting 1 = Two External Switch Inputs 2 = Internal 4-20 mA Input 3 = CCN Loadshed 4 = External 4-20 mA Input
Ramp Load Select (Pulldown Control) 0 = Disabled 1 = Enabled
Cooler Pump Interlock Select 0 = No Interlock 1 = With Interlock
Cooler Pump Control Select 0 = Not Controlled 1 = ON/OFF Controlled
Remote Alarm Option Select 0 = Not Selected 1 = Selected
Local/Enable-Stop-CCN Switch Usage† 0 = Not Allowed 1 = Allowed
LEGEND
CCN — Carrier Comfort Network EXV — Electronic Expansion Valve
FACTORY SERVICE
CONFIGURATION REPLACEMENT
CODE CODE
001 001
000 000
9600 9600
1 = Standard Models 2 = Brine Models
00
0 = 30GN190-210* 1 = 30GN040-170*
0 = 30GN040-070,
190-210*
1 = 30GN080-170*
00
11
11
00
10
1
2 = 040,045
Brine Units
00
00
00
00
00
00
10
10
10
00
11
*And associated modular units. †For reset of alarms.
1
0
0
1
45
Page 46
NOTE: This is true only ifthe occupied period starts at 00:00 (midnight). If the occupied period starts at a time other than midnight, then the occupied period must end at 00:00 hours (midnight) and new occupied period must be programmed to start at 00:00 in order for the chiller to stay in the occu­pied mode past midnight.
The time schedule can be overridden to keep unit in oc­cupied mode for one, 2, 3, or 4 hours on a one-time basis. See Example 9.
All subfunctions of schedule function are password protected except the override subfunction, . Pass­word entry into subfunctions through ,
is done through service function. See page 43, logging on/ logging off.
Figure 10 shows a schedule for an office building with the chiller operating on a single set point schedule. The sched­ule is based on building occupancy with a 3-hour off-peak cool-down period from midnight to 3 a.m. following the week­end shutdown. To learn how this sample schedule would be programmed, see Example 9.
NOTE: This schedule was designed to illustrate the pro­gramming of the schedule function and is not intended as a recommended schedule for chiller operation.
Example 9 — Using the Schedule Function
KEYPAD
ENTRY
PROGRAMMING PERIOD 1:
DISPLAY COMMENT
OVRD 0
OVRD 3 3 hours override in effect
OVRD 0 Override cancelled
CLOCK 0 Schedule function is inactive
CLOCK 1
PERIOD 1
OCC 00.00
UNO 00.00
UNO 3.00 Period 1 ends at 3:00 a.m.
MON NO
MON YES
TUE YES
TUE NO
No scheduled override in effect
Schedule function is enabled through local unit clock
Define schedule period 1. Start of occupied time
For this example, first period should start here (at midnight) so no entry is needed
Start of unoccupied time (end of period). For this example, period 1 should end at 3:00 a.m.
Monday is now flagged no for period 1. To put period 1 into effect on Monday, Monday must be flagged yes
Monday is now flagged for period 1 to be in effect
For this example, period 1 is to be in effect on Monday only.All other days must be checked to be sure that they are flagged no. If any day is flagged yes, change to no
Tuesday is now flagged no for period 1
Example 9 — Using the Schedule Function (cont)
KEYPAD
ENTRY
PROGRAMMING PERIOD 2:
CCN — Carrier Comfort Network
DISPLAY COMMENT
PERIOD 2 Define schedule period 2
OCC 00.00 Start of occupied time
OCC 7.00
UNO 00.00
UNO 18.00
MON NO
MON YES
TUE NO
TUE YES
WED YES
WED NO
PERIOD 3
OCC 00.00
OCC 7.00
UNO 00.00
UNO 21.30
MON NO
TUE NO
WED NO
WED YES
THUR NO
FRI NO
SAT NO
SUN NO
Occupied time will start at 7:00 a.m.
Start of unoccupied time (end of period). For this example, period 2 should end at 18:00 (6:00 p.m.)
Period 2 ends at 18:00 (6:00 p.m.)
Monday is now flagged no for period 2. To put period 2 into effect on Monday, Monday must be flagged yes
Monday is now flagged for period 2 to be in effect
Tuesay is now flagged no for period 2. To put period 2 into effect on Tuesday, Tuesday must be flagged yes
Tuesday is now flagged for period 2 to be in effect
For this example, period 2 is to be in effect only on Monday and Tuesday. All other days must be checked to be sure that they are flagged no. If a day is flagged yes, change to no
Wednesday is now flagged no for period 2
Define schedule period 3
Start of occupied time
Occupied time will start at 7:00 a.m.
Start of unoccupied time (end of period 3). For this example, period 3 should end at 21:30 (9:30 p.m.)
Period 3 ends at 21:30 (9:30 p.m.)
Check to be sure that Monday and Tuesday are flagged no for period 3
Wednesday is flagged no, change to yes
Wednesday is now flagged yes for period 3
Check to be sure that all other days are flagged no
46
Page 47
Periods 4 and 5 can be programmed in the same manner, flagging Thursday and Friday yes for period 4 and Saturday yes for period 5. For this example, periods 6, 7, and 8 are not used: they should be programmed OCC 00.00, UNO 00.00.
NOTE: When a dayis flagged yes for2 overlapping periods, occupied time will take precedence over unoccupied time. Occupied times can overlap in the schedule with no consequence.
To extend an occupied mode beyond its normal termina­tion for a one-time schedule override, program as shown below:
OVRD 0
OVRD 3
Override is set for 0. Enter the number of hours of override desired
Unit will now remain in occupied mode for an additional 3 hours
Holiday Schedule — Press to schedule up to 30 holiday periods. All holidays are entered with numerical
values. First, the month (01 to 12), then the day (01 to 31), then the duration of the holiday period in days.
Examples: July 04 is 07.04.01.
Dec 25 - 26 is 12.25.02
If any of the 30 holiday periods are not used, the display shows NEW.
See Example 10.
Example 10 — Holiday Schedule Function
ENTER DISPLAY
HOLIDAY JAN01 02 (Includes Jan 1st
APR17 01 (Includes April 17th)
MAY21 01(Includes May 21st)
JUL03 01 (Includes July 3rd)
JUL04 01 (Includes July 4th)
SEP07 01 (Includes Sep. 7th) NOV26 02 (Includes Nov. 26th
DEC24 02 (Includes Dec. 24th
DEC30 02 (Includes Dec. 30th
NEW
MAY25 01 (Includes May 25th)
NEW
NEW
NEW
NEW
NEW (30TH HOLIDAY)
NEW indicates a holiday that has not been assigned yet.
and 2nd)
and 27th)
and 25th)
and 31st)
Fig. 10 — Sample Time Schedule
TROUBLESHOOTING
The Flotronic™ II control has many features to aid the technicians in troubleshooting a Flotronic II Chiller. By us­ing the keypad and display module and the status function, actual operating conditions of the chiller are displayed while unit is running. Testfunction allows proper operation of com­pressors, compressor unloaders, fans, EXVs and other com­ponents to be checkedwhile chiller is stopped.Service func­tion displays how configurable items are configured. If an operating fault is detected, an alarm is generated and an
alarm code(s) is displayed under the subfunction , along with an explanation ofthe fault. Up to 10 current alarm
codes are stored under this subfunction. For checking spe­cific items, see Table 9.
Checking Display Codes — To determine how ma-
chine has been programmed to operate, check diagnostic information ( ) and operating mode displays ( ).
If no displayappears, follow procedures in Control Modules section on page 63. If display is working, continue as follows:
1. Note all alarm codes displayed, .
2. Note all operating mode codes displayed, .
3. Note leaving chilled water temperature set point in ef-
fect and current leaving water temperature, . If machine is running, compare the ‘‘in effect’’ leaving
water temperature set point with current water tempera­ture. Remember, if reset is in effect, the values may be differentbecausemachineis operating to the modified chilled water set point. If currenttemperatureis equal to set point, but set point is not the one desired, remember that if dual set point hasbeen selected in the schedule function, there are 2 set points to which the machine can be operating. Check the programming ofschedule function to see ifoc­cupied or unoccupied set point should be in effect.
47
Page 48
UnitShutoff— Toshut unitoff, move LOCAL/ENABLE-
STOP-CCN switch to STOP position. Any refrigeration cir­cuit operating at this time continues to complete the pum­pout cycle. Lag compressors stop immediately, and lead compressors run to complete pumpout.
Complete Unit Stoppage — Complete unit stoppage
can be caused by any of the following conditions:
1. Cooling load satisfied
2. Remote on/off contacts open
3. Programmed schedule
4. Emergency stop command from CCN
5. General power failure
6. Blown fuse in control power feed disconnect
7. Open control circuit fuse
8. LOCAL/ENABLE-STOP-CCN switch moved to STOP position
9. Freeze protection trip
10. Low flow protection trip
11. Open contacts in chilled water flow switch (optional)
12. Open contacts in any auxiliary interlock. Terminals that are jumpered from factory are in series with control switch. Opening the circuit between these terminals places unit in stop mode, similar to moving the control switch to STOP position. Unit cannot start if these contacts are open. If they open while unit is running,unitpumpsdown and stops.
13. Cooler entering or leaving fluid thermistor failure
14. Low transducer supply voltage
15. Loss of communicationsbetween processor module and other control modules
16. Low refrigerant pressure
17. Off-to-on delay is in effect.
Single Circuit Stoppage — Single circuit stoppage
can be caused by the following:
1. Low oil pressure in lead compressor
2. Open contacts in lead compressor high-pressure switch
3. Low refrigerant pressure
4. Thermistor failure
5. Transducer failure
6. Ground fault in lead compressor indicator (indicator is field-supplied on 040-060, 070 [60 Hz],and080-110and associated modular units)
7. High suction superheat
8. Low suction superheat
9. Lead compressor circuit breaker trip. Stoppage of one circuit by a safety device action does not affect other circuit. When a safety device trips on a lead compres­sor, circuit is shut down immediately and EXV closes.
10. Ground fault for any circuit compressor (130-210 and associated modular units).
Lag Compressor Stoppage — Lag compressor stop-
page can be caused by the following:
1. Open contacts in high-pressure switch
2. Compressor ground fault (indicator is field-supplied on
040-060, 070 [60 Hz], and080-110and associated modu­lar units)
3. Compressor circuit breaker trip
4. Not required to run to meet cooling load requirement
If stoppage occurs more than once as a result of any of the above safety devices, determine andcorrectthe cause before attempting another restart.
RestartProcedure — After cause for stoppage hasbeen
corrected, restart is either automatic or manual, depending on fault. Manual reset requires that LOCAL/ENABLE­STOP-CCN switch be moved to STOP position, then back to original operating position. Some typical fault conditions are described in Table 15. For a complete list of fault con­ditions, codes, and reset type, see Table 16.
T able15 —TypicalStoppageFaultsand Reset Types
Chilled Fluid, Low Flow Manual reset Chilled Fluid, Low Temperature Auto reset first time, manual
Chilled Fluid Pump Interlock Manual reset Control Circuit Fuse Blown High-Pressure Switch Open Manual reset Low Refrigerant Pressure Low Oil Pressure Manual reset
Discharge Gas Thermostat Open Manual reset
if repeated in same day
Unit restarts automatically when power is restored
Auto reset first time, then manual if within same day
POWER FAILURE EXTERNAL TO THE UNIT — Unit restarts automatically when power is restored.
Alarms and Alerts— These are warnings of abnormal
or fault conditions, and may cause either one circuit or the whole unit to shut down. They are assignedcode numbers as described below. These code numbers are displayed
on the HSIO when the subfunction is entered. A fault that affects one one circuit of the chiller will generate
an alert, and a fault that affects the entire unit will generate an alarm.
Following is a detailed description of each alarm and alert code error and possible cause. Manual reset is accomplished by moving LOCAL/ENABLE-STOP-CCN Switch to STOP position, then back to LOCAL or CCN position. See Table 16 for listing of each alarm and alert code.
Code 0 No alarms or alerts exist Codes1-8 Compressor failure
If DSIO-LVor-EXV relay module controlrelay feedback switch or signal issensed as open during operation ofa com­pressor, microprocessor detects this and stops compressor, energizes alert light, and displays a code of 1, 2, 3, 4, 5, 6, 7, or 8 depending on the compressor. Compressor locks off; to reset, use manual reset method.
If lead compressor in a circuit shuts down, the other com­pressors in the circuit stop and lock off. Only the alert mode for lead compressor is displayed.
The microprocessor is also programmed to indicate com­pressor failure if feedbackterminal on DSIO-LVor-EXV J3 terminal strip receives voltage when compressor is not sup­posed to be on.
NOTE: It takes 5 seconds forthecontrolto generate the alarm code and lock out the compressor(s) on compressor failure code(s) 1 through 8.
48
Page 49
Table 16 — Alarm and Alert Codes
DISPLAY
2, 3, 4 Compressor A2, A3, A4 failure Compressor shut down Yes Manual CPCS Ground Fault Protection
6, 7, 8 Compressor B2, B3, B4 failure Compressor shut down Yes Manual
ALARM
ALERT
0 No Alarms or Alerts Exist 1
5 Compressor B1 failure Circuit B shut down No Manual
9
10 Entering fluid thermistor failure Unit shut down Yes Auto. 19 20 Compressor B1 sensor failure Circuit B shut down Yes Auto. 21 Reset thermistor failure Normal set point used No Auto. 22 23 Discharge pressure transducer failure, circuit B Circuit B shut down Yes Auto. 24 Suction pressure transducer failure, circuit A Circuit A shut down No Auto. 25 Suction pressure transducer failure, circuit B Circuit B shut down No Auto. 26 Oil pressure transducer failure, circuit A Circuit A shut down No Auto. 27 Oil pressure transducer failure, circuit B Circuit B shut down No Auto. 28 29 LOCAL/ENABLE-STOP-CCN Unit shut down No Manual Switch failure or wiring error. 30 31 4-20 mA demand limit failure Demand limit ignored No Auto. 32
33 Loss of communication with DSIO-EXV Unit shut down No Auto. 34 Loss of communication with 4 In/4 Out module Unit shut down Yes Auto. 35 Not used 36
37 Low refrigerant pressure circuit B Circuit B shut down No * Low refrigerant charge, plugged filter
38 39 Failure to pump out circuit B Circuit B shut down No Manual Faulty expansion valve, transducer,
40
41 Low oil pressure circuit B Circuit B shut down No Manual Low oil level, circuit breaker trip,
42 43 Low cooler fluid flow Unit shut down No Manual Chilled fluid pump failure
44 45 Low suction temperature circuit B Circuit B shut down
46 47 High suction superheat circuit B Circuit B shut down Yes Manual Low charge, faulty expansion valve or
48 49 Low suction superheat circuit B Circuit B shut down Yes Manual Faulty EXV or thermistor. 50 51 Initial configuration required Unit cannot start Manual Configuration omitted. 52 Emergency stop by CCN command Unit shut down Yes CCN Network command. 53 54 Cooler pump interlock failure Unit shut down No Manual Failure of cooler pump or controls 55 Cooler pump interlock failure Cooler pump shut down Manual Failure of cooler pump relay or interlock 56 Alert WSM communication failure WSM forces removed Auto. Wiring fault or module failure 57
58 Calibration required for discharge pressure 59 Calibration required for suction pressure 60 Calibration required for suction pressure 61 Calibration required for oil pressure 62 Calibration required for oil pressure
Compressor A1 failure Circuit A shut down No Manual High-pressure switch trip, or wiring
Alert
Leaving fluid thermistor failure Unit shut down Yes Auto.
Alarm
Compressor A1 sensor failure Circuit A shut down Yes Auto.
Alert
Discharge pressure transducer failure, circuit A Circuit A shut down Yes Auto.
Alert
Transducer supply voltage low Unit shut down No Auto. Unit voltage low or PS1 faulty.
Alarm
4-20 mA reset input failure Normal set point used No Auto.
Alert
Loss of communication with DSIO-LV Unit shut down No Auto. Wiring error or faulty module
Alarm
Low refrigerant pressure circuit A Circuit A shut down No * Low refrigerant charge, plugged filter
Alert
Failure to pump out circuit A Circuit A shut down No Manual Faulty expansion valve, transducer,
Alert
Low oil pressure circuit A Circuit A shut down No Manual Low oil level, circuit breaker trip,
Alert
Cooler freeze protection Unit shut down No * Low fluid flow or faulty thermistor.
Alarm
Low suction temperature circuit A Circuit A shut down
Alert
High suction superheat circuit A Circuit A shut down Yes Manual Low charge, faulty expansion valve or
Alert
Low suction superheat circuit A Circuit A shut down Yes Manual Faulty EXV or thermistor.
Alert
Illegal configuration Unit cannot start Manual Configuration error.
Alarm
Cooler pump interlock failure Unit shut down No Manual Failure of cooler pump or controls
Alarm
Calibration required for discharge pressure transducer, circuit A
transducer, circuit B transducer, circuit A
Alert
transducer, circuit B transducer, circuit A transducer, circuit B
DESCRIPTION
ACTION TAKEN CIRCUIT RESET
BY CONTROL PUMPDOWN METHOD
after 10 minutes after 10 minutes
Circuit cannot start Auto. Circuit cannot start Auto. Circuit cannot start Auto. Circuit cannot start Auto. Circuit cannot start Auto. Circuit cannot start Auto.
No Manual Faulty expansion valve or thermistor. No Manual Faulty expansion valve or thermistor.
PROBABLE CAUSEOR
error.
Thermistor or transducer failure or wiring error.
Transducer failure or wiring error.
or improper address code.
drier, faulty expansion valve. drier, faulty expansion valve.
or thermistor. or thermistor.
faulty expansion valve, crankcase heater, or pressure transducer.
faulty expansion valve, crankcase heater, or pressure transducer.
or faulty thermistor.
thermistor, or plugged filter drier. thermistor, or plugged filter drier.
Transducer not calibrated
49
Page 50
Table 16 — Alarm and Alert Codes (cont)
DISPLAY
68,69 Not used
CPCS — Compressor Protection Control Module FSM Flotronic™ System Manager PS Power Supply WSM — Water System Manager
ALARM
ALERT
63 Alarm Complete unit shutdown Alarm only Auto. Check individual alarms 64
66 Alarm FSM communication loss FSM forces removed Auto. Wiring faulty or module failure 67 Alarm Transducer calibration date code failure Unit cannot start Auto. Incorrect date code entered
70 Alert High leaving chilled fluid temperature Alarm only Auto. Building load greater than unit capacity,
Alert
Loss of charge, circuit A Circuit cannot start Auto. Refrigerant leak or transducer
LEGEND
DESCRIPTION
Possible causes of failure:
1. High-Pressure Switch Open — High-pressure switch for each compressor is wired in series with 24-v power that energizes compressor control relay.Ifhigh-pressureswitch opens during operation, compressor stops. This is detected by microprocessor through the feedback terminals.
2. DSIO-L Vor DSIO-EXV Module Failure—If a DSIO-LV relay module relay fails open or closed, microprocessor detects this, locks compressor off, and indicates an error.
3. Wiring Errors — If a wiring error exists causing CPCS, CR, or feedback switch to not function properly, micro­processor indicates an error.
4. Processor (PSIO) Failure — If hardware that monitors feedback switch fails, or processor fails to energize relay module relay to on, an error may be indicated.
NOTE: The control does not detect circuit breaker fail­ures. If a circuit breaker trips on lead compressor in a circuit, a low oil pressurefailure is indicated. On the other compressors, no failure is indicated.
5. Ground Fault Module on 130-210 and associated modu­lar units (CGFAor CGFB) Open — Module contacts are in lead compressor circuits, but ground fault could be in any compressor in affected circuit.
Ground fault of any 040-110 and associated modular unit compressor (field-supplied accessory on 040-060 and070, 60 Hz units; standard on 070, 50 Hz and 80-110 and as­sociated modular units) will cause a trip.
6. Checkout Procedure —Shut offmain power to unit. Turn on control power, then step through subfunc-
tion to proper compressor number (i.e., failure code 5 is compressor B1). Next, energize the step. If step
works correctly, then failure code is caused by:
• HPS (high-pressure switch) open
• Misplaced feedback wire from J4 and J5 terminals
• Ground wire and 24-v feeds reversed on one or more
points on J3
ACTION TAKEN CIRCUIT RESET
BY CONTROL PUMPDOWN METHOD
*Reset automatic first time, manual if repeated same day.
Compressor Alarm/Alert Circuit — For compres-
sor A1 circuit, processor closes contacts between J4 termi­nals 2 and 3 to start compressor. See Fig. 11A-11C. Safeties shown to left of J4 must be closed in order for power to reach compressor control relay, and the feedback input ter­minals on J3.
Failure of power to terminal 1 on J3, when contacts be-
tween 2 and 3 on J4 should be closed, causes a code 1 alert.
Terminal 2 on J3 is the other leg of the compressor A1
feedback channel. It is connected to the 24-v common. NOTE: Similar connections for each compressor can be fol-
lowed on the unit wiring diagrams located on the unit.
Code 9 Leaving fluid thermistor failure (alarm) Code 10 Entering fluid thermistor failure (alarm)
If temperature measured by these thermistors is outside range of –40 to 240 F (–40 to 116 C), unit shuts down after going through a normal pumpout. Reset is automatic if tem­perature returns to the acceptablerange, and unit start-up fol­lows normal sequence. The cause of the fault is usually a bad thermistor, wiring error, or loose connection.
Code 19 Compressor A1 suction sensor failure (alert) Code 20 Compressor B1 suction sensor failure (alert)
On units with thermistors, if temperature measured bythese thermistors is outside the range of –40 to 240 F (–40 to 116C), affectedcircuitshuts down after going through anor­mal pumpout. Other circuit continues to run. Reset is auto­matic if temperature returns to the acceptable range, and cir­cuit start-up follows normal sequence.Thecause of this fault is usually a bad thermistor, wiring error, or loose connection.
On units with transducers, if the saturated suction tem­perature is greater than the leaving fluid temperature plus 10° F (5.5 C) for more than 5 minutes, the affected circuit shuts down (after going through normal pumpout). Thereset is automatic if the saturated suction temperature returns to the acceptable range and start-up follows the normal se­quence. The cause of this fault is usually a bad transducer, a wiring error, or a loose connection.
PROBABLE CAUSEOR
failure65 Loss of charge, circuit B Circuit cannot start Auto.
low water/brine flow, or compressor fault. Check for other alarms or alerts.
50
Page 51
C—Contactor CB Circuit Breaker COM, COMM — Communications Bus CPCS Compressor Protection
CR Compressor Contactor Relay DGT Discharge Gas Thermostat (Optional) DSIO Relay Module (Low Voltage) HPS High-Pressure Switch LV Low Voltage NC Normally Closed NO Normally Open PL Plug PWR Power SNB Snubber TB Terminal Block TRAN Transformer U—Unloader
Fig. 11A — 24-V Safety Circuit Wiring (040-070)
LEGEND
Control Module
Code 21 Reset thermistor failure (applies only to installa-
tions having external temperature reset) (alert)
If temperature measured by this thermistorisoutside range of –40 to 240F (–40 to 116 C), resetfunction is disabled and unit controls to normal set point. If temperature returns to the acceptable range, reset function is automatically en­abled. The cause of this fault is usually a bad thermistor, wiring error, or loose connection.
Code 22 Compressor A1 discharge pressure
transducer failure (alert)
Code 23 Compressor B1 discharge pressure
transducer failure (alert)
Code 24 Compressor A1 suction pressure transducer
failure (alert)
Code 25 Compressor B1 suction pressure transducer
failure (alert)
Code 26 CompressorA1oilpressuretransducerfailure(alert)
Code 27 Compressor B1 oil pressure transducer failure (alert)
If output voltage of anyofthese transducers is greater than 5 v, affected circuit shuts down without going through pum­pout process (Alerts 24-27). Other circuit continues to run. Reset is automaticif output voltage returns to the acceptable range, and circuit start-up follows normal sequence. The cause of this fault is usually a bad transducer or a wiring error.
Code 28 Low transducer supply voltage (alarm)
If transducer supply voltage is less than 4.5 v or greater than 5.5 v, unit shuts down without going through pumpout process. Reset is automatic if supply voltage returns to the acceptable range, and circuit start-up follows normal se­quence. The cause of this fault is usually a faulty trans­former or primary voltage is out of range.
51
Page 52
C—Contactor CB Circuit Breaker COMM — Communications Bus CPCS — Compressor Protection Control Module DGT Discharge Gas Thermostat (Optional) DSIO Relay Module (Low Voltage) HPS High-Pressure Switch LV Low Voltage PL Plug PWR Power TB Terminal Block TRAN — Transformer U—Unloader
LEGEND
Fig. 11B — 24-V Safety Circuit Wiring (080-110 and Associated Modular Units)
*And associated modular units.
The voltage supplied to the processor is polarized. When checking for proper voltage supply, be sure to consider this polarity. If voltage appears to be within acceptable toler­ance, check to be sure the transformer supplying PS1 is not grounded. Grounding the supply transformer can result in
serious damage to the control system.
Code 29 LOCAL/ENABLE-STOP-CCN Switch Failure
(switch resistances out of range) (alarm)
This fault occurs due to the failure of the switch or due to a wiring error.
Code 30 Reset input failure (4 to 20 mA) (alert) Code 31 Demand limit input failure (4 to 20 mA) (alert)
These codes apply only ifunitis configured for these func­tions. If 4 to 20 mA signal is less than 4 or more than 20 mA, reset or demand limit function is disabled and unit functions normally. If mA signal returns to the acceptable range, function is automatically enabled.
Code 32 Loss of communication with compressor
relay module (DISO-LV) (alarm)
Code 33 Loss of communication with EXV relay
module (DSIO-EXV) (alarm)
If communication is lost witheither of these modules, unit shuts down without pumpout. This alarm resets automati­cally when communication is restored.The unitstarts up nor­mally after alarm condition is reset. Probable cause of con­dition is a faulty or improperly connected plug, wiring error, or faulty module.
Loss of communication can be attributed to a grounded transformer with a secondary voltage of 21 vac supplying the PSIO, DSIO-LV, or 4 IN/4 OUT modules; the 12.5-vac transformer supplying the DSIO-EXV module; or the 24-vac transformer supplying PS1 for thetransformers.These
transformers should not be grounded, or serious damage to controls can result. Check to be sure the transformers are
not grounded. NOTE: If a blank PSIO module is downloaded without be-
ing connected to the modules DSIO, this alarm is energized.
Code 34 Loss of communication with 4 In/4 Out module (alarm)
This applies only if one or more of the following options are used:
• external temperature reset
• 4 to 20 mA temperature reset
• external switch controlled dual set point
• switch controlled demand limit
• 4 to 20 mA demand limit
• hot gas bypass
If communication is lost with 4 IN/4 OUT module, the unit shuts off automatically, after finishing pumpout. Reset of alarm is automatic when communication is restored. Start-up after alarm is remediedfollows a normal sequence.Probable cause of condition is a faulty or improperly connected plug, wiring error, or faulty module.
52
Page 53
LEGEND
CB Circuit Breaker CGF Ground Fault Module COMM — Communications Bus CR Compressor Contactor Relay DSIO Relay Module (Low Voltage) HPS High-Pressure Switch LV Low Voltage PL Plug SNB Snubber TB Terminal Block TRAN — Transformer U—Unloader
Fig. 11C — 24-V Safety Circuit Wiring (130-210 and Associated Modular Units)
*And associated modular units.
Loss of communication can be attributed to a grounded transformer with a secondary voltage of 21 vac supplying the PSIO, DSIO-LV, or 4 IN/4 OUT; the 12.5-vac trans­former supplying the DSIO-EXV module, or the 24-vac trans­former supplying PS1 for the transformers.Thesetransformers
should not be grounded, or serious damage to controls can result. Check to be sure the transformers are not grounded.
Code 36 Low refrigerant pressure, Circuit A (alert) Code 37 Low refrigerant pressure, Circuit B (alert)
If suction pressure transducer senses a pressure below set point for more than 5 minutes at start-up or more than 2 minutes during normal operation, affected circuit shuts down without going through the pumpout process. Reset is auto­matic when pressure reaches 10 psig above set point if there have been no previous occurrences of this fault on the same day. If this is a repeat occurrence on same day, then reset is manual, with LOCAL/ENABLE-STOP-CCN switch. Fac­tory configured set point is 27 psig for standard chillers and 12 psig for brine chillers.
Possible causes of fault are low refrigerant charge, faulty
EXV, plugged filter drier, or faulty transducer.
Code 38 Failure to pump out, Circuit A (alert) Code 39 Failure to pump out, Circuit B (alert)
The pumpout process is terminated when saturated suc­tion temperature is 10° F (5.6° C) below temperature at be­ginning of pumpout, or 10° F (5.6° C) below leaving water temperature or reaches a saturated suction temperature of –15 F (–26 C). If appropriate saturated suction temperature is not met within 3 minutes (on 2 consecutive tries), circuit shuts down without pumpout. Resetis manual with LOCAL/ ENABLE-STOP-CCN switch, and start-up follows normal sequence.
Possible causes for this alarmarea bad thermistor or trans­ducer or a faulty expansion valve.
Code 40 Low oil pressure, Circuit A (alert) Code 41 Low oil pressure, Circuit B (alert)
53
Page 54
If oil pressure differential is less than set point for more than 2 minutes at start-up, or more than one minute during normal operation, affected circuit shuts down without going through pumpout process. Reset is manual with LOCAL/ ENABLE-STOP-CCN switch, and start-up follows normal sequence. Factory configured differential oil pressure is 6 psig.
Possible causes of fault are faulty compressor, expansion valve, crankcase heater or transducer, refrigerant over­charge, insufficient oil charge, or tripped circuit breaker.
Code 42 Cooler freeze protection (alarm)
If cooler entering or leaving water temperature is below 34° F (1.1° C) for water or more than 8° F (4.4° C) below set point for brine, unitshutsdown without pumpout. Chilled water pump continues to run if controlled by chiller con­trols. Reset is automatic when leaving fluid temperature reaches 6° F (3° C) aboveset point, providing there has beenno prior occurrence of this fault the same day. If fault has occurred previously the same day, reset is manual with LOCAL/ ENABLE-STOP-CCN switch.
Possible causes of fault are low fluid flow or faulty thermistor.
Code 43 Low fluid flow (alarm)
If any compressors are operating and entering fluid tem­perature is 3° F (1.7° C) or more below leaving fluid tem­perature for more than one minute, unit shuts down without pumpout. Chilled fluid pump also shuts down. Reset is manual with LOCAL/ENABLE-STOP-CCN switch, and start-up fol­lows normal sequence.
This is a suitable method for sensing low fluid flow be­cause entering fluid thermistor is in the cooler shell and re­sponds more quickly to compressor operation than the leav­ing fluid thermistor in the leaving water nozzle. Possible causes of fault are faulty chilled fluid pump, control or thermistor.
Code 44 Low cooler suction temperature, CircuitA(alert) Code 45 Low cooler suction temperature, Circuit B (alert)
If saturated suction temperature is less than 32 F (0°C) and is 20° F (11° C) for water or 30° F (16° C) for brine or more below leaving fluid temperature, mode 14 is dis­played. Unit continues to run,but additional compressors are not allowed to start. If condition persists for more than 10 minutes, fault code is displayed,andunit shuts down with­out pumpout. Reset is manual with LOCAL/ENABLE-STOP­CCN switch, and start-up follows normal sequence.
Possible causes of fault are lowrefrigerantcharge,plugged filter drier, or a faulty expansion valve or thermistor.
Code 46 High suction superheat, Circuit A (alert) Code 47 High suction superheat, Circuit B (alert)
If expansion valve is fully open, suction superheatisgreater than 75 F (42 C), and saturated evaporator temperature is less than MOP(maximum operating pressure) for more than 5 minutes, unit shuts down after normal pumpout process. Reset is manual with LOCAL/ENABLE-STOP-CCN switch, and start-up follows normal sequence.
Possible causes of fault are lowrefrigerantcharge,plugged filter drier, or a faulty expansion valve or thermistor.
Code 48 Low suction superheat, Circuit A (alert) Code 49 Low suction superheat, Circuit B (alert)
If EXV is at minimum position, suction superheat is less than 10° F (5.5° C) or saturated evaporator temperature is greater than MOP (maximum operating pressure) for more than 5 minutes, affectedcircuit shuts down after going through pumpout process. Reset is manual with LOCAL/ENABLE­STOP-CCN switch, and start-up follows normal sequence.
Possible causes of fault are faulty expansion valve or thermistor.
Code 50 Illegal configuration (alarm)
This fault indicates a configuration error. Unit is not al­lowed to start. Check all configuration data and set points and correct any errors.
Code 51 Initial configuration required (alarm)
This fault indicates factory configuration has not beendone, and unit is not allowed to start. Refer to unit wiring label diagrams for factory configuration codes. There are 9 groups of 8-digit numbers that must be entered. The first
7 groups must be entered under subfunction. Groups 8 and 9 must be entered under subfunction.
Enter each group, then press the key. Press the
down arrow after each group to bring up the next empty screen. Unit should start after factory and field con-
figurations are correctly entered.
The usual cause of this fault is replacement of the pro­cessor module. Refer to instructions accompanying the re­placement module.
Code 52 Emergency stop by CCN command (alarm).
Unit shuts down immediately without pumpout when this command is received, and goes throughnormalstart-up when command is cancelled.
Code 53 Cooler pump interlock failure — Contacts fail to
close at start-up (alarm)
If the unit is configuredforcooler pump control and cooler pump interlock, and the interlock fails to close within one minute of starting the cooler pump, the unit is shut down without pumpout. The cooler pump is also shut down. Reset is manual with the LOCAL/ENABLE-STOP-CCN switch, and start-up follows the normal sequence.
Possible causes are:
1. Interlock switch fails to close within one minute after chilled
water pump starts
2. Interlock switch opens during unit operation
3. Interlock voltage is detected, but unit is not configured
for interlock
4. Interlock voltage is outside its valid range
If any of these conditions occur, all compressors are dis­abled and, if running, shutdown occurs without pumpout. Chilled fluid pump also shuts down. Reset is manual, with LOCAL/ENABLE-STOP-CCN switch. Most probable cause of this fault is shutdown or failure of chilled fluid pump to start. Other possibilities are improper configuration or wir­ing errors.
Code 54 Cooler pump interlock failure — Contacts open
during normal operation (alarm)
If the unit is configuredforcooler pump control and cooler pump interlock, and the interlock opens during normal op­eration, the unit is shut down without pumpout. The cooler pump is also shut down. Reset is manual with the LOCAL/ ENABLE-STOP-CCN switch, and startup follows the nor­mal sequence.
Possible causes are:
1. Interlock switch fails to close within one minute after chilled
water pump starts
2. Interlock switch opens during unit operation
3. Interlock voltage is detected, but unit is not configured
for interlock
4. Interlock voltage is outside its valid range
If any of these conditions occur, all compressors are dis­abled and, if running, shutdown occurs without pumpout. Chilled fluid pump also shuts down. Reset is manual, with
54
Page 55
LOCAL/ENABLE-STOP-CCN switch. Most probable cause of this fault is shutdown or failure of chilled fluid pump to start. Other possibilities are improper configuration or wir­ing errors.
Code 55 Cooler pump interlock failure — Contacts closed
when pump is off (alarm)
If the unit is configuredforcooler pump control and cooler pump interlock, and the interlock is closed when the cooler pump relay is off, the cooler pump shall be shut down and the unit prevented from starting. Reset is manual with the LOCAL/ENABLE-STOP-CCN switch.
Possible causes are:
1. Interlock switch fails to close within one minute after chilled
water pump starts
2. Interlock switch opens during unit operation
3. Interlock voltage is detected, but unit is not configured
for interlock
4. Interlock voltage is outside its valid range
If any of these conditions occur, all compressors are dis­abled and, if running, shutdown occurs without pumpout. Chilled fluid pump also shuts down. Reset is manual, with LOCAL/ENABLE-STOP-CCN switch. Most probable cause of this fault is shutdown or failure of chilled fluid pump to start. Other possibilities are improper configuration or wir­ing errors.
Code 56 Water System Manager (WSM) communication
failure (alert)
If the WSM has previously established communications with the control and the WSM is not disabled and has not communicated with the controlwithin the last 5minutes, the control will remove all WSM forces from the chillers vari­ables. The chiller will continue to operate on a stand-alone basis. Reset is automatic whenthe WSM re-establishes com­munication with the unit.
Code 57 Calibration required for discharge pressure trans-
ducer, circuit A (alert)
Code 58 Calibration required for discharge pressure trans-
ducer, circuit B (alert)
If the discharge pressure transducer has not been success­fully calibrated, the circuit will not start. Reset is automatic upon successful calibration of the transducer.
Code 59 Calibration required for suction pressure trans-
ducer, circuit A (alert)
Code 60 Calibration required for suction pressure trans-
ducer, circuit B (alert
If the suction pressure transducer has not been success­fully calibrated, the circuit will not start. Reset is automatic upon successful calibration of the transducer.
Code 61 Calibration required for oil pressure transducer,
circuit A (alert)
Code 62 Calibration required for oil pressure transducer,
circuit B (alert)
If the oil pressure transducer has not been successfully calibrated, the circuit will not start. Reset is automatic upon successful calibration of the transducer.
Code 63 Complete unit shutdown due to failure (alarm)
This alarm alertsthe user that the unit is totallyshut down due to one ormore fault conditions. Resetis automatic when all alarms causing complete unit shutdown are reset.
Code 64 Loss of charge, circuit A (alert) Code 65 Loss of charge, circuit B (alert)
If the unit uses suction and discharge transducers with the same part number, and the discharge pressure is below 10 psig when the unit is shut down, the circuit will not start. Reset is automatic when the discharge pressure rises above
15 psig. This alarm does notfunction in unitsusing different part number transducers for suction and discharge pressure, since the discharge transducer in that application does not function below 20 psig.
Code 66 Flotronic™ System Manager loss of communi-
cations (alarm)
If the FSM has established communication with the con­trol, and the communication is subsequently lost for more than 20 seconds, the control will remove all forces on the chiller variables. Control of the unit will revert to stand­alone basis, and reset is automatic upon re-establishment of communication. Code 67 Transducer calibration failure due to incorrectdate
code (alarm)
This applies to units having pressure transducers with the same part number for both suction and discharge pressures. If the transducer calibration is attempted and the factory de­fault date code (Jan. 1, 1980) is in the date variable, then the unit will not start. Reset is automatic when the proper date code is entered upon calibration.
Code 70 High leaving chilled fluid temperature (alert)
If the leaving chilled fluid temperature is rising and is higher than the limit established in the subfunction and the unit is at full capacity then alert 70 will be activated.
The unit will continue to function normally, and reset will be automatic upon leaving chilled fluid temperature drop­ping to 5° F below the limit or less than control set point.
Electronic Expansion Valve (EXV)
NOTE: This applies to all units except 30GN040 and 045 with optional brine. The 040 and 045 unitswithoptionalbrine have TXVs.
EXV OPERATION — These valves control the flow of liq­uid refrigerant into the cooler. They are operated by the pro­cessor to maintain a specified superheat at lead compressor entering gas thermistor (located between compressor motor and cylinders). There is one EXV per circuit. See Fig. 12.
High-pressure liquid refrigerant enters valve through bot­tom. A series of calibrated slots are located in side of orifice assembly.As refrigerant passes through orifice, pressure drops and refrigerant changes to a 2-phase condition (liquid and
Fig. 12 — Electronic Expansion Valve (EXV)
55
Page 56
vapor). To control refrigerant flow fordifferent operating con­ditions, sleeve moves up and down over orifice, thereby chang­ing orifice size. Sleeve is moved by a linear stepper motor. Stepper motor moves in increments and is controlled di­rectly by the processor module. As stepper motor rotates, motion is transferred into linear movement by lead screw. Through stepper motor and lead screws, 1500 discrete steps of motion are obtained. The large number of steps and long stroke result in very accurate control of refrigerant flow.
The subfunction shows EXV valve position as
a percent of full open. Position should change constantlywhile unit operates. If a valve stops moving for any reason (me­chanical or electrical) other than a processor or thermistor failure, the processor continues to attempt to open or close the valve to correct the superheat. Once the calculated valve position reaches 120 (fully closed) or 1500 (fully open), it remains there. If EXV position reading remains at 120 or 1500, and the thermistors and pressure transducers are read­ing correctly, the EXV is notmoving. Follow EXV checkout procedure below to determine cause.
The EXV is also used to limit cooler suction temperature to 50 F (10 C). This makes it possible for chiller to start at higher cooler fluid temperatures without overloading com­pressor. This is commonly referred to as MOP (maximum operating pressure), and serves as a load limiting device to prevent compressor motor overloading. This MOP or load limiting feature enables the 30G Flotronic™ II chillers to operate with up to 95 F (35 C) entering fluid temperatures during start-up and subsequent pull-down.
CHECKOUT PROCEDURE — Follow steps below to di­agnose and correct EXV problems.
1. Check EXV driver outputs. Check EXV output signals at
appropriate terminals on EXV driver module (see Fig. 13) as follows:
Connect positive test lead to terminal 1 on EXV driver. Set meter for approximately 20 vdc. Enter outputs
subfunction of test function by pressing , then advance to EXVA test by pressing 10 times. Press
. The driver should drive the circuit A
EXVfully open. During next several seconds connect nega­tive test lead to pins 2, 3, 4, and 5 in succession. Voltage should rise and fall at each pin. If it remains constant at a voltage or at zero v, remove connector to valve and recheck.
Press to close circuit A EXV. If a problem still exists, replace EXV driver module. If voltage reading is
correct, expansion valve should be checked. Next, test EXVB. Connect positive test lead to pin 7 and the nega­tive test lead to pin 8, 9, 10, and 11 in succession during EXVB test.
2. Check EXV wiring. Check wiring to electronic expan-
sion valves from terminal strip on EXV driver. See Fig. 13.
a. Check color coding and wire connections. Make sure
they are connected to correct terminals at driver and EXV plug connections.
b. Check for continuity and tight connection at all pin
terminals.
c. Check plug connections at driver and at EXVs to be
sure EXV cables are not crossed.
3. Check resistance of EXV motor windings. Remove plug
at J4 terminal strip and check resistance between com­mon lead (red wire, terminal D) and remaining leads, A, B, C, and E (see Fig. 13). Resistance should be 25 ohms 6 2 ohms.
EXV — Electronic Expansion Valve
Fig. 13 — EXV Cable Connections to EXV Driver
Module, DSIO (EXV)
Control of valve is by microprocessor. A thermistor and a pressure transducerlocated in lead compressor are used to determine superheat. The thermistor measures tem­perature of the superheated gas entering the compressor cylinders. The pressure transducer measures refrigerant pressure in the suction manifold.The microprocessorcon­verts pressure reading to a saturation temperature. The difference between temperature of superheated gas and saturation temperature is the superheat.
Because the EXVs are controlled by the processor mod­ule, it is possible to track valve position. During initial start-up, EXV is fully closed. After start-up, valve posi­tion is tracked by processor by constantly observing amount of valve movement.
The processor keeps track of EXV position by counting the number of open and closed steps it has sent to each valve. It has no direct physical feedback of valve posi­tion. Whenever unit is switched from STOP to RUN po­sition, both valves are initialized, allowing the processor to send enough closing pulsestothe valve to move it from fully open to fully closed, then reset the position counter to zero.
4. The EXV test can be used to drive EXV to any desired position. When EXV opens, the metering slots begin to provide enough refrigerant foroperation at step 120. This is fully closed position when circuitisoperating.The fully open position is 1500 steps.
5. Check thermistors and pressure transducers that control EXV.Checkthermistors and pressure transducers that con­trol processor outputvoltage pulses to EXVs. See Fig. 14 for locations.
Circuit A — Thermistor T7, Suction Pressure Transducer SPTA Circuit B — Thermistor T8, Suction Pressure Transducer SPTB
a. Use temperature subfunction of the status function
( ) to determine if thermistors are reading correctly.
b. Check thermistor calibration at known temperature by
measuring actual resistance and comparingvaluemea­sured with values listed in Tables 17 and 18.
c. Make sure thermistor leads are connected to proper
pin terminals at J7 terminal strip on processor module and that thermistor probes are located in proper posi­tion in refrigerant circuit. See Fig. 15 and 16.
d. Use the pressure subfunction of the Status function
( ) to determine if pressure transducers are
56
Page 57
reading correctly. Connect a calibrated gage to lead compressor suction or discharge pressure connection to check transducer reading.
e. Make sure transducer leads are properly connected in
junction box and at processor board. Check trans­former 5 output. Check voltage transducer 5 vdc 6 .2 v.
When above checks have been completed, check ac­tual operation of EXV by using procedures outlined in this step.
6. Check operation of EXV. a. Close liquid lineservicevalve of circuit to be checked,
and run through the test step ( ) for lead com­pressor in that circuit to pump down low side of sys­tem. Repeat test step 3 times to ensure all refrigerant has been pumped from low side.
NOTE: Be sure to allow compressors to run for the full pumpout period.
b. Turn off compressor circuit breaker(s). Close com-
pressor discharge service valves and remove any re­maining refrigerant from low side of system.
c. Remove screws holding top cover of EXV. Carefully
remove top cover. If EXV plug was disconnected dur­ing this process, reconnect it after cover is removed.
When removing top cover, be careful to avoid dam­aging motor leads.
d. Enter appropriate EXV test step for EXVA or
EXVB in the outputs subfunction of the test function ( ). Press to initiate test. With
cover lifted off EXV valve body, observe operation of valve motor and lead screw. The motor should turn counterclockwise, and the lead screw should move up out of motor hub until valve is fully open. Lead screw movement should be smooth and uniform from
fully closed to fully open position. Press to check open to closed operation.
If valve is properlyconnected to processor and receiv­ing correct signals, yet does not operate as described above, valve should be replaced.
Operation of EXV valve can also be checked without removing top cover. This method depends on opera­tor’s skill in determining whether or not valve is mov­ing. To use this method, initiate EXV test and open valve. Immediately grasp EXV valve body. As valve drives open, a soft, smooth pulse is felt for approxi­mately 26 seconds as valve travels from fully closed to fully open. When valve reaches end of its opening stroke, a hard pulse is felt momentarily. Drive valve closed and a soft, smooth pulse is felt for the 52 sec­onds necessary for valve to travel from fully open to fully closed. When valve reaches end of its stroke, a hard pulse is again feltas valve overdrives by 50 steps. Valveshouldbedriventhroughatleast2completecycles to be sure it is operating properly. If a hard pulse is felt for the 26-second duration, valve is not moving and should be replaced.
The EXV test can be repeated as required by enter­ing any percentage from 0 ( ) to 100 to initiate
movement.
If operating problems persist after reassembly,they may be due to out-of-calibration thermistor(s) or intermittent connections between processor boardterminals and EXV plug. Recheck all wiringconnections and voltage signals.
Other possible causes of improperrefrigerantflow con­trol could be restrictionsin liquid line. Check forplugged filter drier(s) or restricted metering slots in the EXV. For­mation of ice or frost on lower body of electronic ex­pansion valve is one symptomofrestricted metering slots. However,frostor ice formation is normally expected when leaving fluid temperature from the cooler is below 40 F. Clean or replace valve if necessary.
NOTE: Frosting of valve is normal during compressor test steps and at initial start-up. Frost should dissipate af­ter 5 to 10 minutes operation in a system that is operating properly.If valve is tobe replaced, wrap valve with a wet cloth to prevent excessive heat from damaging internal components.
Thermostatic Expansion Valve (TXV)— Refer to
base unit Installation Instructions for TXV information (30GN040,045 with optional brine only).
Thermistors— All thermistors are identicalin their tem-
perature vs. resistance performance. Resistance at various tem­peratures are listed in Tables 17 and 18.
LOCATION — General location of thermistor sensors are shown in Fig. 14.
Cooler Leaving Fluid Thermistor (T1) — T1 is located in leaving fluid nozzle. The probe is immersed directly in the fluid. All thermistor connections are made through a1⁄4-in. coupling. See Fig. 16. Actual location is shown in Fig. 14 and 15.
Cooler Entering Fluid Thermistor (T2) — T2 is located in cooler shell in first baffle space near tube bundle. Thermistor connection is made through a1⁄4-in. coupling. See Fig. 16. Actual location is shown in Fig. 14 and 15.
Compressor Suction Gas Temperature Thermistors (T7 and T8) — T7 and T8 are located in lead compressor in each circuit in suction passage between motorandcylinders,above oil pump. They are well-type thermistors. See Fig. 14 and 15.
THERMISTOR REPLACEMENT (T1, T2, T7, T8)
Thermistors are installed directly in fluid Relieve allpres­sure using standard practices or drain fluid before re­moving.
Proceed as follows (see Fig. 16): To replace thermistor sensor T2:
1. Remove and discard original thermistor and coupling. IMPORTANT: Do not disassemble new coupling.
Install as received.
2. Apply pipe sealant to1⁄4-in. NPT threads on replacement
coupling and install in place of original. Do not use pack­ing nut to tighten coupling. This damages ferrules (see Fig. 16).
3. Insert new thermistor in coupling body to its full depth.
If thermistor bottoms out beforefulldepth is reached, pull thermistor back out Hand tighten packing nut to position ferrules, then finish tightening 11⁄4turns with a suitabletool. Ferrules are now attached to thermistor whichcan be withdrawn fromcou-
pling for unit servicing. To replace thermistors T1, T7, and T8: Add a small amount of thermal conductive grease to ther-
mistor well. Thermistors are friction-fit thermistors, which must be slipped into well located in the compressor pump end.
1
⁄8in. before tightening packing nut.
57
Page 58
Table 17 — Thermistor Temperature (°F) vs Resistance/Voltage Drop; Flotronic™ II
TEMPERATURE VOLTAGE RESISTANCE
(F) DROP (V) (OHMS)
−25.0 4.821 98010
−24.0 4.818 94707
−23.0 4.814 91522
−22.0 4.806 88449
−21.0 4.800 85486
−20.0 4.793 82627
−19.0 4.786 79871
−18.0 4.779 77212
−17.0 4.772 74648
−16.0 4.764 72175
−15.0 4.757 69790
−14.0 4.749 67490
−13.0 4.740 65272
−12.0 4.734 63133
−11.0 4.724 61070
−10.0 4.715 59081
−9.0 4.705 57162
−8.0 4.696 55311
−7.0 4.688 53526
−6.0 4.676 51804
−5.0 4.666 50143
−4.0 4.657 48541
−3.0 4.648 46996
−2.0 4.636 45505
−1.0 4.624 44066
0.0 4.613 42679
1.0 4.602 41339
2.0 4.592 40047
3.0 4.579 38800
4.0 4.567 37596
5.0 4.554 36435
6.0 4.540 35313
7.0 4.527 34231
8.0 4.514 33185
9.0 4.501 32176
10.0 4.487 31202
11.0 4.472 30260
12.0 4.457 29351
13.0 4.442 28473
14.0 4.427 27624
15.0 4.413 26804
16.0 4.397 26011
17.0 4.381 25245
18.0 4.366 24505
19.0 4.348 23789
20.0 4.330 23096
21.0 4.313 22427
22.0 4.295 21779
23.0 4.278 21153
24.0 4.258 20547
25.0 4.241 19960
26.0 4.223 19393
27.0 4.202 18843
28.0 4.184 18311
29.0 4.165 17796
30.0 4.145 17297
31.0 4.125 16814
32.0 4.103 16346
33.0 4.082 15892
34.0 4.059 15453
35.0 4.037 15027
36.0 4.017 14614
37.0 3.994 14214
38.0 3.968 13826
39.0 3.948 13449
40.0 3.927 13084
41.0 3.902 12730
42.0 3.878 12387
43.0 3.854 12053
44.0 3.828 11730
45.0 3.805 11416
46.0 3.781 11112
47.0 3.757 10816
48.0 3.729 10529
49.0 3.705 10250
50.0 3.679 9979
51.0 3.653 9717
52.0 3.627 9461
53.0 3.600 9213
54.0 3.575 8973
55.0 3.547 8739
56.0 3.520 8511
57.0 3.493 8291
58.0 3.464 8076
59.0 3.437 7868
60.0 3.409 7665
61.0 3.382 7468
62.0 3.353 7277
63.0 3.323 7091
64.0 3.295 6911
65.0 3.267 6735
66.0 3.238 6564
67.0 3.210 6399
68.0 3.181 6238
69.0 3.152 6081
70.0 3.123 5929
TEMPERATURE VOLTAGE RESISTANCE
(F) DROP (V) (OHMS)
71 3.093 5781 72 3.064 5637 73 3.034 5497 74 3.005 5361 75 2.977 5229 76 2.947 5101 77 2.917 4976 78 2.884 4855 79 2.857 4737 80 2.827 4622 81 2.797 4511 82 2.766 4403 83 2.738 4298 84 2.708 4196 85 2.679 4096 86 2.650 4000 87 2.622 3906 88 2.593 3814 89 2.563 3726 90 2.533 3640 91 2.505 3556 92 2.476 3474 93 2.447 3395 94 2.417 3318 95 2.388 3243 96 2.360 3170 97 2.332 3099 98 2.305 3031
99 2.277 2964 100 2.251 2898 101 2.217 2835 102 2.189 2773 103 2.162 2713 104 2.136 2655 105 2.107 2597 106 2.080 2542 107 2.053 2488 108 2.028 2436 109 2.001 2385 110 1.973 2335
111 1.946 2286 112 1.919 2239 113 1.897 2192 114 1.870 2147 115 1.846 2103 116 1.822 2060 117 1.792 2018 118 1.771 1977 119 1.748 1937 120 1.724 1898 121 1.702 1860 122 1.676 1822 123 1.653 1786 124 1.630 1750 125 1.607 1715 126 1.585 1680 127 1.562 1647 128 1.538 1614 129 1.517 1582 130 1.496 1550 131 1.474 1519 132 1.453 1489 133 1.431 1459 134 1.408 1430 135 1.389 1401 136 1.369 1373 137 1.348 1345 138 1.327 1318 139 1.308 1291 140 1.291 1265 141 1.289 1240 142 1.269 1214 143 1.250 1190 144 1.230 1165 145 1.211 1141 146 1.192 1118 147 1.173 1095 148 1.155 1072 149 1.136 1050 150 1.118 1029 151 1.100 1007 152 1.082 986 153 1.064 965 154 1.047 945 155 1.029 925 156 1.012 906 157 0.995 887 158 0.978 868 159 0.962 850 160 0.945 832 161 0.929 815 162 0.914 798 163 0.898 782 164 0.883 765 165 0.868 750 166 0.853 734
TEMPERATURE VOLTAGE RESISTANCE
(F) DROP (V) (OHMS)
167 0.838 719 168 0.824 705 169 0.810 690 170 0.797 677 171 0.783 663 172 0.770 650 173 0.758 638 174 0.745 626 175 0.734 614 176 0.722 602 177 0.710 591 178 0.700 581 179 0.689 570 180 0.678 561 181 0.668 551 182 0.659 542 183 0.649 533 184 0.640 524 185 0.632 516 186 0.623 508 187 0.615 501 188 0.607 494 189 0.600 487 190 0.592 480 191 0.585 473 192 0.579 467 193 0.572 461 194 0.566 456 195 0.560 450 196 0.554 445 197 0.548 439 198 0.542 434 199 0.537 429 200 0.531 424 201 0.526 419 202 0.520 415 203 0.515 410 204 0.510 405 205 0.505 401 206 0.499 396 207 0.494 391 208 0.488 386 209 0.483 382 210 0.477 377 211 0.471 372 212 0.465 367 213 0.459 361 214 0.453 356 215 0.446 350 216 0.439 344 217 0.432 338 218 0.425 332 219 0.417 325 220 0.409 318 221 0.401 311 222 0.393 304 223 0.384 297 224 0.375 289 225 0.366 282
58
Page 59
Table 18 — Thermistor Temperature (°C) vs Resistance/Voltage Drop; Flotronic™ II
TEMPERATURE VOLTAGE RESISTANCE
(C) DROP (V) (Ohms)
−40 4.896 168 230
−39 4.889 157 440
−38 4.882 147 410
−37 4.874 138 090
−36 4.866 129 410
−35 4.857 121 330
−34 4.848 113 810
−33 4.838 106 880
−32 4.828 100 260
−31 4.817 94 165
−30 4.806 88 480
−29 4.794 83 170
−28 4.782 78 125
−27 4.769 73 580
−26 4.755 69 250
−25 4.740 65 205
−24 4.725 61 420
−23 4.710 57 875
−22 4.693 54 555
−21 4.676 51 450
−20 4.657 48 536
−19 4.639 45 807
−18 4.619 43 247
−17 4.598 40 845
−16 4.577 38 592
−15 4.554 38 476
−14 4.531 34 489
−13 4.507 32 621
−12 4.482 30 866
−11 4.456 29 216
−10 4.428 27 633
−9 4.400 26 202
−8 4.371 24 827
−7 4.341 23 532
−6 4.310 22 313
−5 4.278 21 163
−4 4.245 20 079
−3 4.211 19 058
−2 4.176 18 094
−1 4.140 17 184 0 4.103 16 325 1 4.065 15 515 2 4.026 14 749 3 3.986 14 026 4 3.945 13 342 5 3.903 12 696 6 3.860 12 085 7 3.816 11 506 8 3.771 10 959 9 3.726 10 441
10 3.680 9 949 11 3.633 9 485 12 3.585 9 044 13 3.537 8 627 14 3.487 8 231 15 3.438 7 855 16 3.387 7 499 17 3.337 7 161 18 3.285 6 840 19 3.234 6 536 20 3.181 6 246 21 3.129 5 971 22 3.076 5 710 23 3.023 5 461 24 2.970 5 225 25 2.917 5 000 26 2.864 4 786 27 2.810 4 583 28 2.757 4 389 29 2.704 4 204 30 2.651 4 028 31 2.598 3 861 32 2.545 3 701 33 2.493 3 549 34 2.441 3 404 35 2.389 3 266 36 2.337 3 134 37 2.286 3 008 38 2.236 2 888 39 2.186 2 773 40 2.137 2 663 41 2.087 2 559 42 2.039 2 459 43 1.991 2 363
TEMPERATURE VOLTAGE RESISTANCE
(C) DROP (V) (Ohms)
44 1.944 2 272 45 1.898 2 184 46 1.852 2 101 47 1.807 2 021 48 1.763 1 944 49 1.719 1 871 50 1.677 1 801 51 1.635 1 734 52 1.594 1 670 53 1.553 1 609 54 1.513 1 550 55 1.474 1 493 56 1.436 1 439 57 1.399 1 387 58 1.363 1 337 59 1.327 1 290 60 1.291 1 244 61 1.258 1 200 62 1.225 1 158 63 1.192 1 118 64 1.160 1 079 65 1.129 1 041 66 1.099 1 006 67 1.069 971 68 1.040 938 69 1.012 906 70 0.984 876 71 0.949 836 72 0.920 805 73 0.892 775 74 0.865 747 75 0.838 719 76 0.813 693 77 0.789 669 78 0.765 645 79 0.743 623 80 0.722 602 81 0.702 583 82 0.683 564 83 0.665 547 84 0.648 531 85 0.632 516 86 0.617 502 87 0.603 489 88 0.590 477 89 0.577 466 90 0.566 456 91 0.555 446 92 0.545 436 93 0.535 427 94 0.525 419 95 0.515 410 96 0.506 402 97 0.496 393 98 0.486 385
99 0.476 376 100 0.466 367 101 0.454 357 102 0.442 346 103 0.429 335 104 0.416 324 105 0.401 312 106 0.386 299 107 0.370 285
59
Page 60
LEGEND
DPT — Discharge Pressure Transducer EXV — Electronic Expansion Valve OPT — Oil Pressure Transducer SPT — Suction Pressure Transducer T—Thermistor Number
Fig. 14 — Thermistor and Pressure Transducer Locations
Pressure Transducers — A single style of pressure
transducer is used for both high- and low-pressure sensing on Flotronic™ II chillers. However, this transducer must be calibrated before the unit will operate. On new units, this will have been done at the factory in order to test run the unit. If a transducer or PSIO is replaced in the field, how­ever, the transducer will have to be field calibrated as follows:
1. Disconnect transducer from the system.
2. Hang the transducer in the atmosphere.
3. Press on the HSIO keypad, and Read the pres­sure. Pressures before calibration must be within the
range of 6 5 psig. If the pressure is outside the range of 6 5 psig, the HSIO display will read ---. If this is the case, replace the transducer or PSIO or check for a wir­ing error.Ifthe value of the atmospheric pressure is greater than 5 psig or less than –5 psig, the transducer will be considered out of range and will not calibrate.
4. Press on the HSIO keypad. This automatically ap­plies the proper correction factor to all future inputsfrom
the transducer.
Three pressure transducers are mountedon each lead com­pressor: 2 low-pressure transducers to monitor compressor suction pressure and oil pressure, and a high-pressure trans­ducer to monitor compressor discharge pressure (see Fig. 17 for exact locations on compressor). Each transducer is supplied with 5 vdc power from a rectifier which changes 24 vac to 5 vdc.
TROUBLESHOOTING — If transducer is suspected of be­ing faulty, first check supply voltage to transducer. Supply voltage should be 5 vdc ± .2 v. If supply voltage is correct, compare pressure reading displayed on keypad and display module against pressure shown on acalibratedpressure gage. If the 2 pressure readings are not reasonably close, replace pressure transducer.
60
Page 61
Fig. 15 — Thermistor Locations
(Circuits A and B, Lead Compressor Only)
FLUID-SIDE TEMPERATURE THERMISTOR T2
(ALL UNITS)
Fig. 16 — Thermistors
61
COMPRESSOR SUCTION GAS TEMPERATURE
(ALL UNITS) AND FLUID-SIDE TEMPERATURE
THERMISTORS T7 AND T8
THERMISTOR T1 (ALL UNITS)
Page 62
Fig. 17 — Lead Compressor Transducer and Thermistor Locations
TRANSDUCER REPLACEMENT
Transducers are installed directly in the refrigerant cir­cuit. Relieve all refrigerant pressure using standard re­frigeration practices before removing.
1. Relieve refrigerant pressure using standard refrigeration practices.
2. Disconnect transducer wiring at transducer by pulling up on locking tab while pullingweathertightconnection plug from end of transducer. Do not pull on transducer wires.
3. Unscrew transducer from
1
⁄4-in. male flare fitting. When installing new pressure transducer, do not use thread sealer. Thread sealer can plug transducer and render it inoperative.
4. Insert weathertight wiring plug into end oftransducer un­til locking tab snaps in place.
5. Check for refrigerant leaks.
62
Page 63
Control Modules
Turn controller power off before servicing controls. This ensures safety and prevents damage to controller.
PROCESSOR MODULE (PSIO), 4 IN/4 OUT MODULE (SIO), LOW-VOLTAGE RELAY MODULE (DSIO-LV), AND EXV DRIVER MODULE (DSIO-EXV)—The PSIO, DSIO and SIO modules all perform continuous diagnostic evaluations of the condition of the hardware. Proper opera­tion of these modules is indicated by LEDs (light-emitting diodes) on the front surface of the DSIOs, and on the top horizontal surface of the PSIO and SIO.
RED LED — Blinking continuously at a 3- to 5-second rate indicates proper operation. Lighted continuously indicates a problem requiring replacement of module. Off continuously indicates power should be checked. Ifthereis no input power, check fuses. If fuse is bad, check for shorted secondary of transformer or for bad module. On the PSIO module, if the light is blinking at a rate of twice per second, the module should be replaced.
GREEN LED — On a PSIO and an SIO, this is the green LED closest toCOMM connectors. The othergreen LED on module indicates external communications, when used. Green LED should always be blinking when power is on. It indi­cates modules are communicating properly. If green LED is not blinking, check red LED. If red LED is normal, check module address switches. See Fig. 18. Proper addresses are:
PSIO (Processor Module) — 01 (different when CCN
connected) DSIO (Relay Module) — 19 DSIO (EXV Driver Module) — 31 SIO (4 In/4 Out Module) — 59
If all modules indicate communication failure,checkCOMM plug on PSIO module for proper seating. If a good connec­tion is assured and condition persists, replace PSIO module.
If only DSIO or SIO moduleindicatescommunication fail­ure, check COMM plug on that mode for proper seating. If a good connection is assured and condition persists, replace DSIO or SIO module.
All system operating intelligence rests in PSIO module, the module that controls unit. This module monitors condi­tions through input and outputports and through DSIO mod­ules (low-voltage relay module and EXV driver module).
The machine operator communicates with microproces­sor through keypad anddisplay module. Communication be­tween PSIO and other modules is accomplished by a 3-wire sensor bus. These 3 wires run in parallel from module to module.
On sensor bus terminal strips, terminal 1 of PSIO module is connected to terminal 1 of each of the other modules. Terminals 2 and 3 are connected in the same manner. See Fig. 19. If a terminal 2 wire is connected to terminal 1, sys­tem does not work.
In Flotronic™ II chillers, processor module, low-voltage relay module, and keypad and display module are all pow­ered from a common 21-vac power source which connects to terminals 1 and 2 of power input strip on each module.A separate source of 21-vac power is used to power options module through terminals 1 and 2 on power input strip. A separate source of 12.5 vac power is used to power EXV driver module through terminals 1 and2on power input strip.
Fig. 18 — Module Address
Selector Switch Locations
63
Page 64
Fig. 19 — Sensor Bus Wiring
(Communications)
PROCESSOR MODULE (PSIO) (Fig. 20) Inputs — Each input channel has 3 terminals; only 2 of the
terminals are used. Application of machine determines which terminals are used. Always refer to individual unit wiring for terminal numbers.
Outputs — Output is 24 vdc. There are 3 terminals, only 2 of which are used, depending on application. Refer to unit wiring diagram.
NOTE:Address switches (see Fig. 20) mustbe set at 01 (dif­ferent when CCN connected).
LOW VOLTAGE RELAY MODULE (DSIO-LV) (Fig. 21) Inputs — Inputs on strip J3 are discrete inputs (ON/OFF).
When 24-vac power is applied across the 2 terminals in a channel it reads as on signal. Zero v reads as an off signal.
Outputs — Terminalstrips J4 and J5 are internal relayswhose coils are powered-up and powered-off by a signal from microprocessor. The relays switch the circuit to which they are connected. No power is supplied to these connectionsby DSIO module.
4 IN/4 OUT MODULE (SIO) (Fig. 22) — 4 In/4 Out mod­ule allows the following features to be utilized:
1. Temperature Reset by outdoor air or space temperature. A remote thermistor (Part No. 30GB660002) is also re­quired.
NOTE: This accessory is not required for return water temperature reset.
2. Temperature Reset by remote 4 to 20 mA signal.
3. Demand Limit by remote 2-stage switch.
4. Demand Limit by remote 4 to 20 mA signal
5. Dual Set Point by remote switch.
The options module is standard. Remember to reconfig­ure the chiller for each feature selected (see Table 14). For temperature reset, demand limit, and dual set point, desired set points must be entered through keypad and display mod­ule (see Set Point Function section on page 38).
See Table 19 for overall troubleshooting information.
PWR — Power
Fig. 20 — Processor Module (PSIO)
ACCESSORY UNLOADER INSTALLATION
Some of the 30G Flotronic™ II units come standard with unloader(s), and many permit additional unloader(s) to be added if desired. See Table 20.
IMPORTANT:The following combinationsARE NOT permitted (combinations are per circuit):
1. Two unloaders and hot gas bypass
2. Four compressors and 2 unloaders.
3. Four compressors, 1 unloader, and hot gas bypass.
COMM — Communications Bus NC Normally Closed
Fig. 21 — Low-Voltage Relay Module (DSIO)
64
LEGEND
NO Normally Open PWR — Power
Page 65
COMM — Communications Bus PWR Power
LEGEND
Fig. 22 — 4 In/4 Out Module (SIO)
If accessory unloaders are desired, an accessory unloader package is used. Package includes a suction cutoff unloader head package. The 24-v coil in the package can be used for 040-110, 130 (60 Hz), and associated modular units (Table 1). A 115 v or 230 v coil must be used for 130 (50 Hz), 150-210, and associated modular units (Table 1). Coil voltage depends on control circuit voltage. Consult cur­rent Carrier price pages for appropriate part numbers.
NOTE:The accessory package will include all necessary com­ponents and wiring with the following exceptions: The field must provide screws, and on the 130-210, and associated modu­lar units, the field must also supply a 20 vdc (part number HK35AB001) unloader relay and wire (90° C or equivalent).
Installation
1. Be sure all electrical disconnectsare open and tagged be-
fore any work begins. Inspect the package contents for any damage during shipping. File a claim with the ship­per if damage has occurred.
2. For ease of installation, factory-supplied wiring for the
additional unloader is provided in the compressor harness.
3. Install the additional unloader cylinder head on the lead compressor,A1 or B1, according to instructions provided by the compressor manufacturer in the accessory package.
4. Continue installation per either 040-110, 130 (60 Hz) units or 130 (50 Hz), 150-210 units section as appropriate.
040-110,130(60Hz)UNITS (AndAssociated ModularUnits)
1. Wire the solenoid before any field wiring begins. Wiring between components and control box must be enclosed in conduit. All local electrical codes and National Elec­trical Code (NEC) must be followed. Factory wires are provided in the compressor harness to connect the sole­noid. These wires are in the compressor control box.
2. Wire the control side. Open the left side control box door and remove inner panel. Using the holes provided and field-supplied screws,installfield-suppliedtransformerabove the DSIO-LV on the control panel.
Wire the primary side of the transformer in parallel with TRAN4. See Fig. 23. This supplies transformer with proper line voltage. Be sure to connect proper tap of the trans­former to ensure supply of proper secondary voltage.
Wirethesecondary side of transformer to DSIO-LV- J5-9, and a jumper from DSIO-LV - J5-9 to DSIO-LV - J4-9. Wirethe secondary common to TB7-2. Connect thetrans­former ground to ground hole supplied near the trans­former. These connections provide DSIO with necessary power to energize the solenoid coils.
3. When all connections are made, check for proper wiring and tight connections. Replace and secure inner panel. Restore power to unit.
4. Configure the processor. With the addition of extra un­loaders, the unit configuration has changed. To change the configuration of the processor, enter the service func­tion using the keypad and display module. Before any changes can be made, the LOCAL/ENABLE-STOP­CCN switch must be in the STOP position, and the ser­vicer must log on to the processor.
a. Press . Keypad LCD displays the word
PASSWORD.
b. Enter . Keypad LCD displays
LOGGEDON.
c. To change configuration, press . Keypad LCD
displays FLD CFG.
d. If an additional unloader was added to compressor
A1, press until NULA 1 appears in keypad dis­play. Press for the number of unloaders on
circuit A. Keypad display now reads NULA 2.
e. If an additional unloader was added to compressor
B1, press until NULB 1 appears in keypad dis­play. Press for the number of unloaders on
circuit B. Keypad display now reads NULB 2.
f. When configuration is complete, press . Key-
pad display reads LOGGEDON. Press until key­pad display reads LOG OFF. Press . Keypad dis-
play reads EXIT LOG.
65
Page 66
Table 19 — Troubleshooting
SYMPTOMS CAUSE REMEDY COMPRESSOR DOES
NOT RUN
COMPRESSOR CYCLES OFF ON LOW PRESSURE
COMPRESSOR SHUTS DOWN ON HIGH PRESSURE CONTROL
UNIT OPERATES LONG OR CONTINUOUSLY
SYSTEM NOISES Piping vibration Support piping as required.
COMPRESSOR LOSES OIL Leak in system Repair leak.
FROSTED SUCTION LINE Expansion valve admitting either too HOT LIQUID LINE Shortage of refrigerant due to leak Repair leak and recharge.
FROSTED LIQUID LINE Shutoff valve partially closed or restricted Open valve or remove restriction. COMPRESSOR DOES NOT
UNLOAD
COMPRESSOR DOES NOT LOAD
EXV — Electronic Expansion Valve
Power line open Reset circuit breaker. Control fuse open Check control circuit for ground or short.
High-Pressure Switch (HPS) tripped
Tripped power breaker Check the controls. Find cause of trip Loose terminal connection Check connections.
Improperly wired controls Check wiring and rewire. Low line voltage Check line voltage. Determine location
Compressor motor defective Check motor winding for open or short. Seized compressor Replace compressor.
Loss of charge Repair leak and recharge. Bad transducer Replace transducer. Low refrigerant charge Add refrigerant. High-pressure control erratic in action Replace control. Compressor discharge valve partially closed Open valve or replace if defective. Condenser fan(s) not operating Check wiring. Repair or replace motor(s)
Condenser coil plugged or dirty Clean coil. Low refrigerant charge Add refrigerant. Control contacts fused Replace control. Partially plugged or plugged expansion
valve or filter driver Defective insulation Replace or repair. Service load Keep doors and windows closed. Inefficient compressor Check valves. Replace if necessary.
Expansion valve hissing Add refrigerant.
Compressor noisy Check valve plates for valve noise.
Mechanical damage (blown piston or broken discharge valve)
Crankcase heaters not energized during shutdown
much or too little refrigerant
Burned out coil Replace coil. Defective capacity control valve Replace valve. Miswired solenoid Rewire correctly. Weak, broken, or wrong valve body spring Replace spring Miswired solenoid Rewire correctly. Defective capacity control valve Replace valve. Plugged strainer (high side) Clean or replace strainer. Stuck or damaged unloader piston or
piston ring(s)
Replace fuse. Move LOCAL/ENABLE-STOP-CCN switch to STOP
position then back to RUN or CCN position. and reset breaker.
of voltage drop and remedy deficiency. Replace compressor if necessary.
if defective.
Clean or replace.
Check for plugged liquid line filter drier.
Replace compressor (worn bearings). Check for loose compressor holddown bolts.
Repair damage or replace compressor. Replace heaters, check wiring and
crankcase heater relay contacts. Check cooler and compressor thermistors.
Test EXV.
Clean or replace the necessary parts.
Table 20 — Standard and Accessory Unloaders
NO. OF ACCESSORY
UNIT
30GN040-070 1 1 1or2 30GN080-170* 211 30GN190-210* 011
*And associated modular units.
NO. OF STANDARD
UNLOADER(s)
UNLOADERS
PERMITTED
Circuit A Circuit B
66
Page 67
5. Using test function,check unloaders. Press . Key­pad display reads OUTPUTS. Press until display reads UNA2 OFF. Press . Relay energizes. Press
and relay deenergizes. Press until display reads
UNB2 OFF. Press . Relay energizes. Press and relay deenergizes.
6. When unloader check has been performed,returnLOCAL/ ENABLE-STOP-CCN to proper position. Close and se­cure control box door.
130 (50 Hz), 150-210 UNITS (AndAssociatedModular Units)
1. Install control wiring. The minimum wire size for instal­lation is 16 AWG (American Wire Gage). Refer to Fig. 23 and 24 for proper wiring. Open the control box door. Locate unloader relaysA and B (UA, UB) in place of the hot gas bypass relays as shown on the component arrangement diagram on the unit. Mount the relays with the field-supplied screws. Be careful not to damage the components and wiring in the area when mounting the relays.
2. Wire the control side. Wire the UA coil in series between J6-18 and J6-19 of the4 IN/4 OUT module with thewires provided. Wire the UB coil in series between J6-21 and J6-22 of the same module with the wires provided.
Locate the black wire in the control harness originating from TRAN5 labeled HGBPR-A-COM. Connect this wire to the UAterminal COM. Connect the wire labeled HGBPR­A-NO to UA-NO. Connect the wire from UA-NO to TB3-5. For an extra unloader on circuit B, connect the wire labeled HGBPR-B-COM to UR-B-COM, and the wire labeled HGBPR-B-NO to UB-NO. Connectthewire from UB-NO to TB3-6.
3. Wire in the solenoid valves. NOTE: Wires external to the control box must be run in
conduit. Terminal blocks are provided for easy field wiring. Use
one of the isolated
7
⁄8-in. (22-mm) holes in the side of the compressor electrical box with a strain relief to run the wires to the solenoid coil. Connect UA between TB3-5 andTB3-8. Connect UB between TB3-6 and TB3-8. Check all of the electrical connections for proper location and tightness, and replace and secure the electrical box of the compressor.
4. Configure the microprocessor.Once the relays are mounted in the control box, the microprocessor must be config­ured for the unloader option. To do so:
a. Be sure the LOCAL/ENABLE-STOP-CCN switch is
in the STOP position.
b. Log into the processor and enter the service func-
tion using the keypad and display module. Press . The keypad LCD will display
‘‘PASSWORD.’’ Enter , and the keypad LCD will display ‘‘LOGGEDON.’’
c. To change the configuration, press , and the
keypad LCD will display ‘‘FLD CFG.’’ Press until either ‘‘NULA 0’’ or ‘‘NULA 1’’ is displayed
(depending on the number of unloaders provided as standard). Then press (for 1 unloader on A1) or (for 2 unloaders on compressor A1). The
display will now read either ‘‘NULA 1’’ or ‘‘NULA 2,’’ as appropriate. Press to get to the
NULB display,andchangethissetting in the same man­ner as with circuit A.
d. Once the configuration is complete, press ,
and the keypad LCD will display ‘‘LOGGEDON,’’ Press until the keypad LCD display reads ‘‘LOG OFF.’’ Press and the keypad LCD will display
‘‘EXIT LOG.’’
5. Once theunloader heads are installed, the unit is checked for leaks, and the system is prepared for operation per the instructions for the compressor unloader head installa­tion, check theoutput of the relays using the testfunction as follows:
a. Press , and the display will read ‘‘COMP.’’ b. Press the to scroll down until the display reads
‘‘CPA1 OFF.’’
c. Press , and the compressor should start. d. Press , and the compressor should stop. e. Press until the display reads ‘‘UNA1 OFF.’’
f. Press , and the solenoid should energize. g. Press and the solenoid should deenergize. h. Use the and keys to check the remainder of
the unloader coils.
6. Once the check has been performed, return the LOCAL/ ENABLE-STOP-CCN switch to the proper position.
7. Close and secure the control box door.
8. Start the unit and confirm that the chiller operates properly.
67
Page 68
LEGEND
C—Contactor PWR — Power CB Circuit Breaker SW Switch COMM — Communications Bus TRAN — Transformer HGBPR — Hot Gas Bypass Relay U—Unloader
Fig. 23 — Accessory Unloader Control Wiring, All Units
*Or HGBPR-A. †Or HGBPR-B.
COM Communications Bus TB Terminal Block HGBPR — Hot Gas Bypass Relay TRAN — Transformer NO Normally Open U—Unloader SNB Snubber
LEGEND
Fig. 24 — Flotronic™ II 115/230-V (Unloader Wiring, 130 (50 Hz), 150-210 and Associated Modular Units
(See Table 1)
68
Page 69
FIELD WIRING
Refer to Fig. 25-35 for field wiring.
NOTE: Contacts must be rated for dry circuit application, capable of reliably switching a 5 vdc, 1 mA to 20 mA load.
Fig. 25 — Demand Limit — Two External
Switch Inputs
Fig. 26 − Demand Limit — 4-20 mA Signal
(Externally Powered)
Fig. 27 — Demand Limit — 4-20 mA Signal
(Internally Powered)
Fig. 28 — Remote Reset from Space or
Outdoor-Air Temperature
Fig. 30 — Remote Reset from 4-20 mA Signal
(Internally Powered)
TB — Terminal Block
NOTE: Contacts must be rated for dry circuit application, capable of reliably switching a 5 vdc, 1 mA to 20 mA load.
Fig. 31 — Remote On/Off
Fig. 32 — Remote Dual Set Point Control
Fig. 29 — Remote Reset from 4-20 mA Signal
(Externally Powered)
CWP — Chilled Water (Fluid) Pump TB Terminal Block
Fig. 33 — Chilled Fluid Pump
69
Page 70
TB — Terminal Block
Fig. 34 — Remote Alarm
CWP1 — Chilled Water (Fluid) Pump Interlock CWFS — Chilled Water (Fluid) Flow Switch (not required — low flow
TB Terminal Block
protection is provided by Flotronic™ II controls)
Fig. 35 — Interlocks
REPLACING DEFECTIVE
PROCESSOR MODULE
The replacement part number is printed on a small label on the front of the PSIO module. The model and serial num­bers are printed on the unit nameplate located on an exterior corner post. The proper software and unit configuration data is factory installed by Carrier in the replacement module. Therefore, when ordering a replacement processor module (PSIO), specify complete replacement part number, full unit model number, and serial number. If these numbers are not provided, the replacement module order is configured in­stead as a generic Flotronic II replacement module. This re­quires reconfiguration of the module by the installer.
Electrical shock can cause personal injury. Disconnect all electrical power before servicing.
Installation
1. Verify the existing PSIO module is defective by using the procedure described in the Control Modules section on page 63.
procedure. If checklist doesnot exist, fill out the and configuration code sectionsona new check-
list.Tailor the various options and configurations as needed for this particular installation.
3. Check that all power to unit is off. Carefully disconnect all wires from defective module by unpluggingthe6con­nectors. It is not necessary to remove any of the indi­vidual wires fromtheconnectors.Removethegreenground wire.
4. Remove defective PSIO by removing its mounting screws with a Phillips screwdriver, and removing the module from the control box. Save the screws for later use.
5. Use a small screwdriver to set address switches S1 and S2 on the new PSIO module to exactly match the set­tings on the defective module.
6. Package the defective module in the carton of the new module for return to Carrier.
7. Mount the new module in the unit control box using a Phillips screwdriver and the screws saved in Step 4 above.
8. Reinstall all 6 wire connectorsandthegreen ground wire.
9. Carefully check all wiring connections before restoring power.
10. Verify the LOCAL/ENABLE-STOP-CCN switch is in STOP position.
11. Restore control power. Verify the red and green lights on top of PSIO and front of each DSIO module respond as described in Control Modulessection on page 63. The keypad and display module should also begin its rotat­ing display.
12. Using the keypad and display module, press to verify that the software version number matches the ER (engineering requirement) number shown on the PSIO label.
13. Press to verify that the 7 factory configuration codes (CODE 1 through CODE 7) exactly match the codes
listed for this unitmodel on the component arrangement label diagram on the control box door. If they are dif­ferent or are all zeros,reenter the 7 codes. If any changes are required, the PSIO display becomes blank and
reconfigures itself after pressing the key while dis­playing CODE 7. The display returns in approximately
15 seconds. NOTE: Codes with leading zeros in the configuration
will be displayed starting with the first number greater than zero.
14. Press to verify eachitemis configured as needed for this particular installation. Table 14 shows the fac-
tory configuration code default settings. Table 14 also shows the service replacement code default settings which are used if no model number was specified when order­ing the replacement PSIO module. It is strongly sug­gested that the Start-Up ChecklistforFlotronic II Chiller Systems (completed attime of original start-up) be used at this time to verify and/or reprogram the various op­tions and configurations required for this job.
15. Press to verify that the 2 field configuration codes (codes 8 and 9) match exactly the codes listed on
the label diagram on the control box door. If they are different, or are all zeros, reenter the 2 codes.
16. After completing theconfigurationsteps outlined above, restore main power and perform a unit test as de-
scribed in and sections on page 38.
17. Complete this procedure and restore chiller to normal operation by returning the LOCAL/ENABLE-STOP­CCN switch to desired position.
70
Page 71
Page 72
Copyright 1995 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 2 Tab 5c
PC 903 Catalog No. 563-079 Printed in U.S.A. Form 30GN-3T Pg 72 7-95 Replaces: 30G-1T
Loading...