Carrier CRTWOPOS010A00, CRTWOPOS011A00 Installation Instructions Manual

Page 1
CRTWOPOS010A00 CRTWOPOS011A00
Installation Instructions
SMALL ROOFTOP PRODUCTS
GAS/ELECTRI C HEA T AND HEAT PUMP UNITS
2 to 12---1/2 TONS (50/60 Hz) ACCESSORY
ADJUSTABLE TWO POSITION OUTDOOR AIR DAMPER
Read these instructions completely before attempting to install the accessory outdoor air damper.
SAFETY CONSIDERATIONS
Installation and servicing of air--conditioning equipment can be hazardous due to system pressure and electrical components. Only trained and qualified service personnel should install, repair, or service air--conditioning equipment.
Untrained personnel can perform basic maintenance functions of cleaning coils and filters and replacing filters. All other operations should be performed by trained service personnel. When working on air--conditioning equipment, observe precautions in the literature, tags and labels attached to the unit, and other safety precautions that may apply.
Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth for unbrazing operations. Have fire extinguishers available for all brazing operations.
Recognize safety information. This is the safety--alert symbol When you see this symbol on the unit and in instructions or manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, and CAUTION. These words are used with the safety--alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies a hazard which could result in personal injury or death. CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
GENERAL
These 2 position outdoor air packages can be used in either a vertical or horizontal airflow configuration. The damper assembly travel can be adjusted to allow from 25% to 100% outdoor air for the applicable rooftop unit.
PACKAGE USAGE AND CONTENTS
INSTALLATION
To install the outdoor damper, perform the following:
IMPORTANT: Follow all applicable local and national electrical codes when installing this accessory.
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Before installing accessory, disconnect power supply and install lockout tag.
1. Turn off unit power supply and install lockout tag. For gas
.
units, turn off the gas supply.
2. Determine quantity of ventilation air required for building. Record amount of air for use in Step 10.
3. Remove filter access panel by raising panel and swinging panel outward. Panel is now disengaged from track and can be removed. No tools are required to remove filter access panel. Remove the outdoor--air opening/indoor coil access panel. (See Fig. 1.)
UNIT SIZE PAR T NU M BE R PAC K A G E C O N TEN T S
2 --- H oo d s i d e 1 --- H o o d t o p 1 --- Hood divider
2to6Tons CRTWOPOS010A00
7 --- 1 / 2 t o 1 2 --- 1 / 2
Ton s
CRTWOPOS011A00
1 --- A l u m i n u m f i l t e r 1 --- B o t t o m p a n e l 1 --- Damper assembly 1 - -- Hardware bag
2 --- H o o d s i d e 1 --- H o o d t o p 1 --- Hood divider 1 --- A l u m i n u m f i l t e r 1 --- B o t t o m p a n e l 1 --- Damper assembly 1 - -- Hardware bag
C07340
Fig. 1 -- Rooftop Unit Panels
(2--6 ton unit shown)
4. Assemble outside--air hood top, sides and divider as shown in Fig. 2. Do not install hood at this time.
5. Install galvanized, insulated bottom panel per Fig. 3, with the slot at the top of the panel. The lip of the slot should fit behind the corner post as shown. Screw in place.
Page 2
C07341
Fig. 2 -- Damper Hood Panels
C07342
Fig. 3 -- Damper and Hood Panel Installation
6. Adjust the actuator limiter to limit the maximum open position of the damper to the amount of desired ventilation air from step 2. The adjustment is made by setting the set screw on the end of the actuator to the desired position. Tighten screw firmly to hold in place. (See Fig. 5--7.) Adjustments can be made after the assembly is installed, by removing rooftop unit’s horizontal return panel and accessing the actuator.
7. Lift damper assembly and set in place over the top of the bottom panel, per Fig. 3. Secure the damper assembly in place with provided screws.
8. Remove the jumper plug shipped attached to the economizer harness in the HVAC unit. DO NOT DISCARD. Connect the plug from the damper actuator assembly to the economizer plug in the HVAC unit. Set the jumper plug aside in case it is determined at a later date that the two position damper is no longer required, at which time the jumper plug can be reinstalled.
C07343
Fig. 4 -- Filter Installation
C07344
Fig. 5 -- Actuator Limit Screw
9. Install the assembled outside-- air hood onto the HVAC unit, covering the damper assembly. Screw in place.
10. Install the provided aluminum filter into the hood. Lock in place with top filter clips. (See Fig. 4.)
11. Replace the top filter access panel.
12. Remove lockout tag and restore base unit to operation.
2
Page 3
0.8
0.7
0.6
0.5
0.4
0.3
0.2
0.1
0
0 500 1,000 1,500 2,000 2,500 3,000
0.4
0.5
0.6
0.7
0.8
0.9
Outdoor Airflow (CFM)
Fig. 6 -- Actuator Limit Screw Setting (2-- 6 Ton Units)
CRTWOPOS010A00
0.8
C07363
0.7
0.4
0.6
0.5
0.4
0.3
0.2
0.1
0.0
0 1,000 2,000 3,000 4,000 5,000 6,000
0.5
0.6
0.7
0.8 0.9
Airflow (CFM)
Fig. 7 -- Actuator Limit Screw Setting (7.5--12.5 Ton Units)
CRTWOPOS011A00
C07364
3
Page 4
SEQUENCE OF OPERATION
Cooling
When the room thermostat calls for cooling, the compressor contactor no. 1 is energized to start compressor no. 1 and outdoor--fan motor(s). The indoor--fan motor is energized and the two--position damper moves to its field--adjusted position. On a further call for cooling, compressor contactor no. 2 is energized starting compressor no. 2 (7--1/2 to 12--1/2 ton units only). When the indoor--fan motor is de--energized, the two position damper moves to the fully closed position.
Heating
When the room thermostat calls for heating, the heating controls are energized as described in the base unit installation, start--up and service instructions. The indoor--fan motor is energized and the two--position damper moves to the set position. When the indoor--fan motor is de--energized, the two--position damper moves to the fully closed position.
Ventilation (Continuous Fan)
The two--position damper remains at set position as long as the indoor fan is energized. When the indoor fan is cycled off, the two--position damper moves to the fully closed position.
WIRING DIAGRAM
Low Temperature Lockout (Optional)
If desired, a temperature lockout switch can be field installed to over ride the damper signal and keep it closed if the outside air temperature falls below a specified air temperature. The recommended method is to use an outside air lockout switch or thermostat to make/break the red wire on the damper actuator harness.
NOTE: In the event of a power failure or if the disconnect to the unit is shut off, the damper will close due to the internal spring in the actuator.
SERVICE
Once each heating or cooling season or as conditions require, perform the following:
1. Inspect the two--position damper blade to ensure it is clean and moves freely.
2. Visually verify that the damper opens upon a call for cooling or heating and shuts when the unit is cycled off.
3. Inspect the actuator limit screw on the damper actuator. Verify it is still in the desired position, and that it has not slipped. Adjust as required.
RTU PL-6
Fig. 8 -- CRTWOPOS010A00 and CRTWOPOS011A00 Wiring
Copyright 2007 CAC / BDP D 7310 W. Morris St. D Indianapolis, IN 46231 Printed in U.S.A. Edition Date: 11/07
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
4
C07345
Catalog No:IIK--- CRTWOPOS01 ---01
Replaces: 48_50 --- 63SI and 48_50---64SI
Loading...