50EZ ---A
Comfortt Single --- Packaged Heat Pump System with PuronR
(R ---410A) Refrigerant
S i n g l e --- A n d T h r e e --- P h a s e U n i t s
2to5NominalTons(Sizes24---60)
Product Data
Innovative Unit Base Design
On the inside a high--tech composite material will not rust and
incorporates a sloped drain pan which improves drainage and helps
inhibit mold, algae and bacterial growth. On the outside metal base
rails provide added stability as well as easier handling and rigging.
Durable, dependable components Compressors are designed
for high efficiency. Each compressor is hermetically sealed against
contamination to help promote longer life and dependable
operation. Each compressor also has vibration isolation to provide
quieter operation. All compressors have internal high pressure and
overcurrent protection.
Direct--drive multi--speed brushless DC blower motoris
standard on all 50EZ--A models. Direct--drive, PSC (Permanent
Split Capacitor)condenser--fan motors are designed to help reduce
energy consumption and provide for cooling operation down to
40_F(4.4_C) outdoor temperature. MotormasterR II low ambient
kit is available as a field installed accessory.
Thermostat controls designed to work as a system with Carrier’s
small packaged product.
A09034
Fig. 1 -- Unit 50EZ--A
Single--Packaged Products with Energy--Saving Features and
PuronR refrigerant.
S Up to 13.5 SEER
S Up to 7.7 HSPF
S Up to 11.5 EER at 95_FOD
S Factory--Installed TXV
S Multi-- Speed High Efficiency DC Blower--Standard
S Dehumidification Feature
FEATURES/BENEFITS
One--piece Heat Pump unit with optional electric heater, low
installation cost, dependable performance and easy maintenance.
Efficient operation High--efficiency design with SEERs
(Seasonal Energy Efficiency Ratio) of up to 13.5.
Puron Environmentally Sound Refrigerant is Carrier’s unique
refrigerant designed to help protect the environment. Puron is an
HFC refrigerant which does not contain chlorine that can harm the
ozone layer. Puron refrigerant is in service in millions of systems,
proving highly reliable, environmentally sound performance.
Easy Installation
Factory--assembled package is a compact, fully self--contained,
heat pump unit that is prewired, pre--piped, and pre--charged for
minimum installation expense. These units are available in a
variety of standard capacity ranges with voltage options to meet
residential and light commercial requirements. Units are
lightweight and install easily on a rooftop or at ground level. The
high tech composite base eliminates rust problems associated with
ground level applications.
Thermostatic Expansion Valve -- A hard shutoff, balance port
TXV maintains a constant superheat at the evaporator exit (cooling
cycle) resulting in higher overall system efficiency.
Refrigerant system is designed to provide dependability. Liquid
filter driers are used to promote clean, unrestricted operation. Each
unit leaves the factory with a full refrigerant charge. Refrigerant
service connections make checking operating pressures easier.
High and Low Pressure Switches provide added reliability for the
compressor.
Indoor and Outdoor coils are computer--designed for optimum
heat transfer and efficiency. The indoor coil is fabricated from
copper tube and aluminum fins and is located inside the unit for
protection against damage. The outdoor coil is internally mounted
on the top tier of the unit.
Low sound ratings ensure a quiet indoor and outdoor
environment with sound ratings as low as 74dBA.
Easy to service cabinets provide easy 3--panel accessibility to
serviceable components during maintenance and installation. The
base with integrated drain pan provides easy ground level
installation with a mounting pad. A nesting feature ensures a
positive basepan to roof curb seal when the unit is roof mounted. A
convenient 3/4 -- in. wide perimeter flange makes frame mounting
on a rooftop easy.
Convertible duct configuration
Unit is designed for use in either downflow or horizontal
applications. Each unit is converted from horizontal to downflow
and includes two horizontal duct covers. Downflow operation is
provided in the field to allow vertical ductwork connections. The
basepan seals on the bottom openings to ensure a positive seal in
the vertical airflow mode.
Cabinets are constructed of heavyduty, phosphated, zinc--coated
prepainted steel capable of withstanding 500 hours in salt spray.
Interior surfaces of the evaporator and electricheater
compartments are insulated with cleanable semi-- rigid insulation
1
Page 2
board, which keeps the conditioned air from being affected by the
outdoor ambient temperature and provides improved indoor air
quality. (Conforms to American Society of Heating, Refrigeration
and Air Conditioning Engineers No. 62P.) The sloped drain pan
minimizes standing water in the drain. An external drain is
provided.
Short--Cycling protection for the compressor is incorporated into
our defrost control board ensuring a five minute delay (+/--2
minutes) before restarting compressor after shutdown for any
reason.
d B --- Sound Levels (decibels)
db—Dry Bulb
SEER—Seasonal Energy Efficiency Ratio
wb—Wet Bulb
COP--- Coefficient of Performance
HSPF ---Heating Season Performance Factor
* Air Conditioing & Refrigeration Institute.
**At “A” conditions - -- 80_F (26.7_C) indoor db/67_F (19.4_C) indoor wb &
95_F(35_C) outdoor db.{ Rated in accordance with U.S. Government DOE Department of Energy)
test procedures an d/or ARI Standards 210/240.
Notes:
1. Ratings are net values, reflecting the effects of circulating fan heat.
Ratings are based on:
Cooling Standard: 80°F (26.7_C) db, 67°F (19.4_C ) w b i n d o o r e n t e r i n g ---
air temperature and 95°F(35_C)dboutdoorentering---airtemperature.
2. Before purchasing this appliance, read important energy cost and efficiency information availabl e from your retailer.
L O S S --- O F --- C H A R G E / L O W --- PR E S SU R E
RETURN--- AIR FILTERS*{
*Required filter sizes shown are based on the larger of the ARI (Air conditioning and Refrigeration Institute) rated cooling airflow or the heating airflow velocity of
300 ft/minute for throwaway type or 450 ft/minute for high ---capacity type. Air filter pressure drop for non --- standard filters must not exceed 0.08 IN. W.C.
{ If using accessory filter rack refer to the filter rack installation instructions for correct filter size and quantity.
} For 460 volt units, add 14 lb (6.4 kg) to the weight.
NOTE: Tested in accordance with ARI Standard 270 (not listed in ARI ).
RATING
(dBA)
TYPICAL OCTAVE BAND SPECTRUM (dBA) (without tone adjustment)
1252505001000200040008000
4
Page 5
OPTIONS AND ACCESSORIES
FACTORY
ITEMDESCRIPTION
Coil OptionsBase unit with tin plated indoor coil h airpinsX
Compressor Start Kit
Corporate Thermostats
Crankcase Heater
Economizer
Electric HeatersElectric Heat SupplementX
Filter Rack
Flat Roof Curbs
Low Ambient Kit
Louver Metal Outdoor Coil Grilles
Manual Outside Air Damper
S q u a r e --- t o --- R o u n d D u c t T r a n s i t i o n K i t
Time Guard II
*Refer to Price Page for application detail.
Compressor Start Kit assists compressor start - -- up by providing
additional starting torque on sing phase units only.
Thermostats provide control for the system heating and cooling
functions.
Crankcase Heater provides anti --- floodback protection for low --load cooling application s.
Horizontal Economizer with solid state controls and barometric
relief dampers includes filter racks and provide outdoor air during
cooling and reduce compressor operation.
Vertical Economizer with solid state controls and barometric relief
dampers includes filter racks and provide outdoor air during
cooling and reduce compressor operation.
Filter Rack features easy in stallation, serviceability, and high--filtering performance for vertical applications. Includes 1 ---in. filter.
F l a t R o o f C u r b s i n b o t h 1 1 --- i n ( 2 7 9 m m ) a n d 1 4 --- i n . ( 3 5 6 m m )
sizes are available for roof mounted applications.
Low A mbi ent Kit (Motormaster II Control) allows the use of mechanical cooling down to outdoor temperatures as low as 0°F
( ---18° C) when properly installed.
Louver Metal Outdoor Coil Grilles provides hail and vandalism
protection.
Manual Outside Air Damper includes hood and filter rack with
adjustable damper blade for up to 25% outdoor air.
Square---to --- Round Duct Transition Kit enable 24 ---48 size units to
be fitted to 14 in. (356 mm) round ductwork.
Automatically prevents the compressor from restarting for at least
4 minutes and 45 seconds after shutdown of the compressor. Not
required when a corporate programmable thermostat is applied
o r w i t h a R T U --- M P c o n t r o l .
Dashed lines show cross support
location for large basepan units.
E
A09096
50EZ -- A
SMALL
BASE
UNIT
F
LARGE
A
RETURN
AIR
BASE
UNIT
E
D
LARGE CURB
UNIT SIZE
Small or
Large
Large
* Part Numbers CPRCURB010A00 and CPRCURB011A00 can be used on both small and large basepan units. The cross supports must be located based on
whether the unit is a small basepan or a large basepan.
NOTES:
1. Roof curb must be set up for unit being installed.
2. Seal strip must be applied, as required, to unit being installed.
3. Roof curb is made of 16-- gauge steel.
4. Attach ductwork to curb (flanges of duct rest on curb).
2. Select unit based on required cooling capacity.
Enter Net Cooling Capacities table at condenser entering
temperature of 95°F(35°C). Unit 036 at 1200 cfm and 67°F
(19°C) ewb (entering wet bulb) will provide a total capacity of
35,000 Btuh and a SHC of 26,200 Btuh. Calculate SHC correction,
if required, using Note 4 under Cooling Capacities tables.
50EZ -- A
3. Select heating capacity of unit to provide design
condition requirement.
In the Heating Capacities and Efficiencies table, note that the 36
size unit will deliver 35,000 BTUH at the ARI high temp rating
point. To achieve 60,000 BTUH, accessory electric heat will be
required. Use the Balance Point Worksheet to plot the load line
with the unit capacity. The difference between the load line and
unit capacity at the design heating temperature is the amount of
electric heat that will be required.
4. Determine fan speed and power requirements at
design conditions.
Before entering the air delivery tables, calculate the total static
pressure required. From the given example, the Wet Coil Pressure
Drop Table, and the Filter Pressure Drop Table:
External Static Pressure0.200 IN. W.C.
Filter0.130 IN. W.C.
Wet Coil Pressure Drop0.18
Total Static Pressure0.51 IN. W.C.
Enter the table for Dry Coil Air Delivery— At 0.50 IN. W.C.
ESP (external static pressure) and MEDIUM speed the motor
delivers 1209 cfm.
IN. W.C.
5. Select unit that corresponds to power source
available.
The Electrical Data Table shows that the unit is designed to operate
at 208/230-- 1--60.
*At 75_F (23.9 _C) entering dry bulb—Tennessee Valley Authority [TVA] rating conditions; all others at 80_F (26.7 _C) entering dry bulb. See Legend and Notes.
*At 75_F (23.9 _C) entering dry bulb—Tennessee Valley Authority [TVA] rating conditions; all others at 80_F (26.7 _C) entering dry bulb. See Legend and Notes.
*At 75_F (23.9 _C) entering dry bulb—Tennessee Valley Authority [TVA] rating conditions; all others at 80_F (26.7 _C) entering dry bulb. See Legend and Notes.
*At 75_F (23.9 _C) entering dry bulb—Tennessee Valley Authority [TVA] rating conditions; all others at 80_F (26.7 _C) entering dry bulb. See Legend and Notes.
*At 75_F (23.9 _C) entering dry bulb—Tennessee Valley Authority [TVA] rating conditions; all others at 80_F (26.7 _C) entering dry bulb. See Legend and Notes.
*At 75_F (23.9 _C) entering dry bulb—Tennessee Valley Authority [TVA] rating conditions; all others at 80_F (26.7 _C) entering dry bulb. See Legend and Notes.
1. Ratings are net; they account for the effects of the evaporator---fan motor power and heat.
2. Direct interpolation is permissible. Do not extrapolate.
t
3. The following formulas may be used:
lwb =
t
lwb)
h
ewb = Enthalpy of air entering evaporator coil
air leaving evaporator coil (
h
4. Th e SHC is based on 80_F (26.7 _C) edb temperature of air entering evaporator coil. Below 80_F (26.7_C) edb, subtract (corr factor x cfm) from SHC. Above 80_F (26.7_C) edb, add (corr factor x cfm) to SHC.
Where:
Correction Factor = 1.10 x (1 + BF) x (edb + 80).
5. Integrated capacity is maximum (instantaneous) capacity less the effect of frost on the outdoor coil and the heat required to defrost it.
4. Th e SHC is based on 80_F (26.7 _C) edb temperature of air entering evaporator coil. Below 80_F (26.7_C) edb, subtract (corr factor x cfm) from SHC. Above 80_F (26.7_C) edb, add (corr factor x cfm) to SHC.
Correction Factor = 1.10 x (1 + BF) x (edb + 80).
5. Integrated capacity is maximum (instantaneous) capacity less the effect of frost on the outdoor coil and the heat required to defrost it.
17
Page 18
PERFORMANCE DATA (CONT)
Wet Coil Air Delivery (CFM)-- Downflow -- High Speed with 1--in. (25 mm) Filter and Economizer
Dry Coil Air Delivery* -- Horizontal and Downflow Discharge -- Unit 50EZ--A24--60
UNIT
50EZ---A24
50EZ---A30
50EZ---A36
50EZ---A42
50EZ---A48
50EZ---A60
* Air delivery values are without air filter and are for dry coil (See 50EZ - -- A Horizontal Wet Coil Pressure Drop Table).
1
Factory--- shipped cooling speed
NOTE: For horizontal applications deduct field - -- supplied air filter pressure drop and wet coil pressure drop to obtain external static pressure available for ducting.
For downflow applications see Wet Coil Air Delivery T able for available static in cluding wet coil, 1---in. (25 mm) filter and economizer.
Shaded areas indicate speed/static combinations that are not permitted for dehumidification speed.
Condensate trap — A 2-- in. (51 mm) condensate trap must be
field supplied.
Ductwork — Secure downflow discharge ductwork to roof curb.
For horizontal discharge applications, attach ductwork to unit with
flanges.
To convert a unit to downflow discharge — Units are equipped
with factory--installed inserts in the downflow openings. Removal
of the inserts is similar to removing an electrical knock -- out. Units
installed in horizontal discharge orientation do not require duct
covers.
BALANCE POINT WORKSHEET
70
60
Maximum cooling airflow — To minimize the possibility of
condensate blow--off from the evaporator, airflow through the units
should not exceed 450 cfm per ton.
Minimum cooling airflow — Minimum cooling airflow is 350
cfm per ton in cooling mode. Airlow can be lower in certain modes
when humidity removal is an issue.
Minimum ambient cooling operation temperature —All
standard units have a minimum ambient cooling operating
temperature of 40_F(4.4_C). With accessory low ambient
temperature kit, units can operate at temperatures down to 0_F
(17.8_C).
Maximum operating outdoor air temperature for cooling is
125_F (51.7_C).
60
48
50
40
30
20
42
36
30
24
HEATING CAPACITY, MBTUH
BUILDING HEAT LOSS, UNIT INTEGRATED
10
BASED ON INDOOR ENT. AIR AT
70 ºF AND AT RATED CFM
When power is supplied to unit, the transformer (TRAN) is
energized.
On units with crankcase heater, heater is also energized.
Cooling — With the thermostat in the cooling position, the
thermostat makes circuit “R” to “O”. This energizes the reversing
valve solenoid (RVS) and places the unit in standby condition for
cooling.
As the space temperature rises, the thermostat closes circuit “R” to
“Y”. A circuit is made to contactor (C), starting the compressor
(COMP) and outdoor--fan motor (OFM). Circuit “R” to “G” is
made at the same time and starts the indoor--fan motor (IFM).
When the thermostat is satisfied, contacts open, deenergizing C.
The COMP and OFM stop, and the IFM stops after the preselected
time delay.
On the loss of the thermostat call for cooling, 24 V is removed
from both the “Y1/Y” and “G” terminals (provided the fan switch
is in the “AUTO” position) de--energizing the compressor
contactor and opening the contacts supplying power to
compressor/OFM. After a 90--second delay, the IFM shuts off. If
the thermostat fan selector switch is in the “ON” position, the IFM
will run continuously.
Heating — On a call for heat, thermostat makes circuites “R” to
“Y) and “R” to “G”.
A circuit is made to C, starting COMP and OFM. Circuit “R” to
“G” also is complted, energizing IFR and starting IFM after the
selected time delay.
Should room temperature continue to fall, circuit “R” to “W” is
made through second--stage thermostat. If optional electric heat
package is used, a relay is energized, bringing on first bank of
supplemental electric heat. When thermostat is satisfied, contacts
open, deenergizing contactor and relay; motors and heaters
deenergize.
Defrost — Defrost board (DB) is a time and temperature control,
which includes a field --selectable time period (dip switch 1 and 2
on the board) between checks for defrost (30, 60, 90, or 120
minutes). Electronic timer and defrost cycle start only when
contactor is energized and defrost thermostat (DFT) is closed.
The defrost board is also equipped with a third dip switch for
selecting Quiet Shift operation. The Quiet Shift operation turns
compressor off at defrost initiation and termination. Unit is factory
shipped with quiet shift turned off.
Defrost mode is identical to cooling mode, except outdoor fan
motor stops and a bank of optional electric heat turns on to warm
air supplying the conditioned space.
NOTE:
1. Compressor time delay occurs through the defrost control
board.
2. Defrost control board has built in 5 minute compressor
delay; once the compressor has started and then stopped, it
cannot be restarted again until 5 minutes have elapsed.
50EZ -- A
27
Page 28
GUIDE SPECIFICATIONS
Packaged Heat Pumps
HVAC Guide Specifications
Size Range: 2to5Tons,NominalCooling
Carrier Model Number: 50EZ--A
Part 1⎯General
SYSTEM DESCRIPTION
Outdoor, packaged,air--to--air heat pump unitutilizing a hermetic
scroll compressor for cooling duty and optional electric heating.
Unit shall discharge supply airvertically or horizontallyasshown
on contract drawings. Outdoor fan/coil section shall have a
draw--thru design with vertical discharge for minimum sound
levels.
QUALITY ASSURANCE
A. Unit shall be rated in accordance with ARI Standards 210/240
and 270.
B. Unit shall be designed in accordance with UL Standard
1995.
C. Unit shall be manufactured in a facility registered to ISO 9001
50EZ -- A
manufacturing quality standard.
D. Unit shall be UL listed and c--UL certified as a total package
for safety requirements.
E. Roof curb shall be designed to conform to NRCA Standards.
F. Insulation and adhesives shall meet NFPA 90A requirements
for flame spread and smoke generation.
G. Cabinet insulation shall meet ASHRAE Standard 62P.
DELIVERY, STORAGE AND HANDLING
Unit shall be stored and handled per manufacturer’s
recommendations.
Part 2 ⎯ Products
EQUIPMENT
A. General:
Factory--assembled, single--piece, heat pump unit. Contained
within the enclosure shall be all factory wiring, piping, controls,
refrigerant charge (R--22), and special features required prior to
field start--up.
B. Unit Cabinet:
1. Unit cabinet shall be constructed of phosphated,
zinc--coated, pre--painted steel capable of withstanding 500
hours of salt spray.
2. Normal service shall be through a single removable cabinet
panel.
3. The unit shall be constructed on a rust proof unit base that
has an externally trapped, integrated sloped drain.
4. Indoor fan compartment top surface shall be insulated with
a minimum 1/2--in. (12.7 mm) thick, flexible fiberglass
insulation, coated on the air side and retained by adhesive
and mechanical means. The indoor wall sections will be
insulated with a minimum semi--rigid, foil-- faced board
capable of being wiped clean. Aluminum foil--faced
fiberglass insulation shall be used in the entire indoor air
cavity section.
5. Unit shall have a field--supplied condensate trap.
6. Metal Insulated Duct Covers for side discharge will be
standard on all sizes.
7. Unit insulation conforms to ASHRAE 62P.
C. Fans:
1. The indoor fan shall be 5--speed, direct--drive, as shown on
equipment drawings.
2. Fan wheel shall be made from steel and shall be
double--inlet type with forward--curved blades with
corrosion resistant finish. Fan wheel shall be dynamically
balanced.
3. Outdoor fan shall be direct--drive, propeller--type with
aluminum blades riveted to corrosion resistant steel spiders,
be dynamically balanced, and discharge air vertically.
D. Compressor:
1. Fully hermetic compressors with factory--installed vibration
isolation.
2. Scroll compressors shall be standard on all units.
3. Compressor Protection:
Defrost control shall protect compressor by preventing
“short cycling.”
E. Coils:
Indoor and outdoor coils shall have aluminum plate fins
mechanically bonded to seamless copper tubes with all joints
brazed. (Copper/copper and vinyl--coated construction available
as option.) Tube sheet openings shall be belled to prevent tube
wear.
F. Refrigerant Metering Device:
Refrigerant metering device shall be thermostatic expansion
valve for cooling, and fixed orifice for heating.
G. Filters:
Filter section shall consist of field --installed, throwaway, 1--in.
(25 mm) -- thick fiberglass filters of commercially available
sizes.
H. Controls and Safeties:
1. Unit controls shall be complete with a self--contained, low-voltage control circuit.
2. Units shall incorporate an internal compressor protector that
provides reset capability.
I. Operating Characteristics:
1. Unit shall be capable of starting and running at 125_F
(51.7_C) ambient outdoor temperature.
2. Compressor with standard controls shall be capable of
operation down to 40_F(4.4_C) ambient outdoor
temperature in cooling mode.
3. Unit shall be provided with 60--second fan time delay after
the thermostat is satisfied.
J. Electrical Requirements:
All unit power wiring shall enter the unit cabinet at a single
location.
K. Motors:
1. Compressor motors shall be of the refrigerant--cooled type
with line--break thermal and current overload protection.
2. All fan motors shall have permanently lubricated bearings,
and inherent, automatic reset, thermal overload protection.
3. Condenser fan motor shall be totally enclosed.
4. Evaporator Fan Motor to be high--efficiency brushless DC
motor.
5. Condenser fan motor shall be totally enclosed.
28
Page 29
GUIDE SPECIFICATI ONS (CONT)
L. Special Features Available:
1. Coil Options:
Base unit with tin plated indoor coil hairpins.
2. Compressor Start Kit (single phase units only
Shall provide additional starting torque for single--phase
compressors.
3. Thermostat:
To provide for two--stage heating and one--stage cooling in
addition manual or automatic changeover and indoor fan
control.
4. Crankcase Heater:
Shall provide anti--floodback protection for lowload cooling
applications.
5. Economizer:
a. Economizer controls capable of providing free cooling
using outside air.
b. Equipped with low leakage dampers not to exceed 3%
leakage, at 1.0 in. wc pressure differential.
c. Spring return motor shuts off outdoor damper on power
failure.
6. Electric heaters:
a. Electric heater shall be available as a field installed
option.
b. Heater elements shall be open wire type, adequately
supported and insulated with ceramic bushings.
c. Electric heater packages must provide single point
power connection capability.
7. Filter Rack Kit:
Shall provide filter mounting for downflow applications.
8. Flat Roof Curb:
Curbs shall have seal strip and a wood nailer for flashing
and shall be installed per manufacturer’s instructions.
9. Low Ambient Package:
Shall consist of a solid--state control and outdoor coil temperature sensor for controlling outdoor--fan motor operation, which shall allow unit to operate down to 0_F
(--17.7_C) outdoor ambient temperature.
10. Louvered Grille:
Wire grille shall be standard on all units. Louvered grille
shall be available as a field--installed option to provide hail
guard and vandalism protection.
11. Manual Outdoor Air Damper:
Package shall consist of damper, birdscreen, and rainhood
which can be preset to admit outdoor air for year--round
ventilation.
12. Square--To--Round Duct Transitions (24--48 size):
Shall have the ability to convert the supply and return openings from rectangular to round.
13. Time Guard II
Automatically prevents the compressor from restarting for
at least 4 minutes and 45 seconds after shutdown of the
compressor. Not required when a corporate programmable
thermostat is applied or with a RTU--MP control.
50EZ -- A
29
Page 30
50EZ -- A
Copyright 2009 Carrier Corp. D 7310 W. Morris St. D Indianapolis, IN 46231Printed in U.S.A.Edition Date: 05/09
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
Catalog No:50EZ---03PD
Replaces: 50EZ ---02PD
30