25HCD3
Comfort™ 13 Heat Pump
with Puronr Refrigerant
1 --- 1 / 2 t o 5 N o m i n a l To n s
Product Data
the environmentally sound refrigerant
Carrier heat pumps with Puronr refrigerant provide a collection of
features unmatched by any other family of equipment. The 25HCD
has been designed utilizing Carrier’s Puron refrigerant. The
environmentally sound refrigerant allows consumers to make a
responsible decision in the protection of the earth’s ozone layer.
NOTE: Ratings contained in this document are subject to
change at any time. Always refer to the AHRI directory
(www.ahridirectory.org) for the most up--to--date ratings
information.
INDUSTRY LEADING
FEATURES / BENEFITS
Efficiency
S 13.0 -- 14.5 SEER/ 11.0 -- 12.2 EER/ 7.7 -- 8.5 HSPF
S Microtube Technologyt refrigeration system
S Indoor air quality accessories available
Sound
S Sound level as low as 69 dBA
S Sound levels as low as 69 dBA with accessory sound blanket
Comfort
S System supports Edger Thermidistatt or standard thermostat
controls
Reliability
S Puronr refrigerant -- environmentally sound, won’t deplete the
ozone layer and low lifetime service cost.
S Scroll compressor
S Internal pressure relief valve
S Internal thermal overload
S High pressure switch
S Loss of charge switch
S Filter drier
S Balanced refrigeration system for maximum reliability
Durability
WeatherArmort protection package:
S Solid, durable sheet metal construction
S Dense wire coil guard
S Baked--on powder paint
Applications
S Long--line -- up to 250 feet (76.20 m) total equivalent length, up
to 200 feet (60.96 m) condenser above evaporator, or up to 80 ft.
(24.38 m) evaporator above condenser (See Longline Guide for
more information.)
S Low ambient (down to --20_F/--28.9_C) with accessory kit
Page 2
MODEL NUMBER NOMENCLATURE
12345678910111213
NNAAA/NNNNA/NA/NA/NNN
25HCD336A 0030
Product
Series
25=HPH=RESHP C=Comfort D=Puron3=13SEER
25HCD3
Product
Famil y
the environmentally sound refrigerant
Tier
Major
Series
SEER
Use of the AHRI Certified
TM Mark indicates a
manufacturer’s
participation in the
program For verification
of certification for individual
products, go to
www.ahridirectory.org.
*Units are rated with 25 ft (7.6 m) of lineset length. See Vapor Line Sizing and Cooling Capacity Loss table when using other sizes and lengths of lineset.
Note: See unit Installation Instruction for proper installation.
119
(54.1)
137
(62.3)
Piston
49
4.0
(1.81)
124
(56.4)
142
(64.5)
Piston
57
5.11
(2.32)
149
(67.7)
170
(77.3)
Piston
67
5.83
(2.64)
36-- -31, 50,
60
169
(76.7)
189
(85.9)
Piston
70 (31)
73 (50,60)
6.06
(2.75)
42-- -31, 50
180
(81.6)
200
(90.9)
Piston
76
6.75
(3.06)
48-- -31, 50,
60
208
(94.3)
228
(103.6)
Piston
80 (31)
82 (50, 60)
7.72
(3.50)
60-- -30, 50, 60
250
(113.4)
282
(127.9)
TXV
(Puron Hard
Shutoff)
11.00
(4.99)
25HCD3
VAPOR LINE SIZING AND COOLING CAPACITY LOSS
Acceptable vapor line diameters provide adequate oil return to the compressor while avoiding excessive capacity loss. The suction line
diameters shown in the chart below are acceptable for HP systems with Puron refrigerant:
Vapor Line Sizing and Cooling Capacity Losses -- Puronr Refrigerant 1-- Stage Heat Pump Applications
Cooling Capacity Loss (%)
Unit
Nominal
Size (Btuh)
18,000
1 --- S t a g e
HP with
Puron
24,000
1 --- S t a g e
HP with
Puron
30,000
1 --- S t a g e
HP with
Puron
36,000
1 --- S t a g e
HP with
Puron
42,000
1 --- S t a g e
HP with
Puron
48,000
1 --- S t a g e
HP with
Puron
60,000
1 --- S t a g e
HP with
Puron
Standard Length = 80 ft. (24.4 m) or less total equivalent length
Applications in this area are long line. Accessories are required as shown recommended on Long Line Application Guidelines
Applications in this area may have height restrictions that limit allowable total equivalent length, when outdoor unit is below indoor unit See Long Line Application Guidelin es
Maximum
Liquid Line
Diameters
(In. OD)
3/8
3/8
3/8
3/8
3/8
3/8
3/8
Vapo r Line
Diameters
(In.) OD
1/21234678910
5/8001112233
5/8011233445
3/4000011111
5/8123345678
3/4001112223
7/8000011111
5/812456791011
3/4001122334
7/8000011112
3/4012234456
7/8001112223
3/4012345567
7/8001122233
3/412456791011
7/8012234455
1 --- 1/8000111111
Standard
Application
26-- -50
(7.9--- 15.2)
51-- -80
(15.5--- 24.4)
81-- -100
(24.7--- 30.5)
Total Equivalent Line Length ft. (m)
Long Line Application Re quires Accessories
101-- -125
(30.8--- 38.1)
126-- -150
(38.4--- 45.7)
151-- -175
(46.0--- 50.3)
176-- -200
(53.6--- 60.0)
201-- -225
(61.3--- 68.6)
226-- -250
(68.9--- 76.2)
3
Page 4
REFRIGERANT PIPING LENGTH LIMITATIONS
Maximum Line Lengths:
The maximum allowable total equivalent length for heat pumps varies depending on the vertical separation. See the tables below for
allowable lengths depending on whether the outdoor unit is on the same level, above or below the outdoor unit.
Maximum Line Lengths for Heat Pump Applications
MAXIMUM ACTUAL LENGTH
Units on equal level200 (61)250 (76.2)N/A
Outdoor u n it ABOVE
indoor unit
Outdoor unit BE LOW
indoor unit
{ Total equivalent length accounts for losses due to elbows or fitting. See the Long Line Guideline for details.
ft (m)
200 (61)250 (76.2)200 (61)
See Table ’Maximum Total Equivalent Length: Outdoor Unit BELOW Indoor Unit’
Maximum Total Equivalent Length{-- Outdoor Unit BELOW Indoor Unit
Liquid Line
Size
18000
HP with
25HCD3
Puron
24000
HP with
Puron
30000
HP with
Puron
36000
HP with
Puron
42000
HP with
Puron
48000
HP with
Puron
60000
HP with
Puron
* Maximum actual length not to exceed 200 ft (61 m)
{ Total equivalent length accounts for losses due to elbows or fitting. See the Long Line Guideline for details.
--- --- = o u t s i de a c c e p t a b l e r a n g e
Diameter
w/ TXV
3/8250*250*250*250*250*250*250*
3/8250*250*250*250*250*250*250*
3/8250*250*250*250*250*250*250*
3/8250*250*250*250*250*250*250*
3/8250*250*250*250*250*250*150
3/8250*250*250*250*230160--- ---
3/8250*225*190150110--- ------ ---
0 --- 2 0
(0 --- 6.1)
21-- -30
(6.4 --- 9.1)
HP with Puronr Refrigerant --- Maximum Total Equivalent Length{
Vertical Se paration ft (m) Outdoor unit BELOW indoor unit;
31-- -40
(9.4 --- 12.2)
MAXIMUM EQUIVALENT LENGTH{
41-- -50
(12.5 --- 15.2)
ft (m)
51-- -60
(15.5 --- 18.3)
MAXIMUM VERTICAL
SEPARATION ft (m)
61-- -70
(18.6 --- 21.3)
(21.6 --- 24.4)
71-- -80
LONG LINE APPLICATIONS
An application is considered Long Line when the refrigerant level in the system requires the use of accessories to maintain acceptable
refrigerant management for systems reliability. Defining a system as long line depends on the liquid line diameter, actual length of the tubing,
and vertical separation between the indoor and outdoor units.
For Heat Pump systems, the chart below shows when an application is considered Long Line. Beyond these lengths, long line accessories
are required:
HP WITH PURONr REFRIGERANT LONG LINE DESCRIPTION ft (m)
Beyond these lengths, long line accessories are required
Liquid Line SizeUnits On Same LevelOutdoor Below IndoorOutdoor Above Indoor
3/880 (24.4)20 (6.1) vertical or 80 (24.4) total80 (24.4)
x = Accessory S = Standard
*AvailablethroughRCD
{ Required accessories include ball bearing fan motor, compressor start assist (CAP / Relay), crankcase heater, evaporator freeze stat, isolation relay, hard
shut--- off TXV or liquid line solenoid valve.
60--- 30,
50
60--- 60
25HCD3
ACCESSORY THERMOSTATS
PAR T NU MB ERPROGRAMGASELEC TRICHEAT PUMPHEATCOOL
TC ---PHP015 --- 2 D a y
T C ---NHP 0 1NP
TCSNHP01NP
TB ---PHP015 --- 2 D a y
T B --- NH P 0 1NP
PAR T NU MB ERBRIEF DESCRIPTIONTHERMOSTATS USED WITH
T X --- L BP0 1LargeDecorativeBackplateT P --- Px x , T P --- Nx x , TC --- Px x
T X --- MBP 0 1Medium Decorative BackplateT C --- N x x, T B --- Pxx
T X --- SBP 0 1Small Decorative BackplateT B --- Nx x
√√√
√√√
THERMOSTAT ACCESSORIES
√√
√√
√√
32
32
21
21
21
5
Page 6
ACCESSORY USAGE GUIDELINE
REQUIRED FOR LOW--- AMBIENT
Accessory
AccumulatorStandardStandardStandard
Ball Bearing Fan MotorYe s{NoNo
Compressor Start Assist Capacitor and
Evaporator Freeze ThermostatYe sNoNo
Liquid Line Solenoid ValveNoSee Long--- Line Application GuidelineNo
Motor Master Control or
* For tubing line sets between 80 and 200 ft. (24.38 and 60.96 m) and/or 20 ft. (6.09 m) vertical differential, refer to Residential Split---System Longline
Accessory Description and Usage (Listed Alphabetically)
1. Ball--Bearing Fan Motor
A fan motor with ball bearings which permits speed reduction
25HCD3
while maintaining bearing lubrication.
Usage Guideline:
Required on all units when using MotorMasterr
2. Compressor Start Assist -- Capacitor and Relay
Start capacitor and relay gives a ”hard” boost to compressor motor
at each start up.
Usage Guideline:
Required for reciprocating compressors in the following
applications:
Long line
Low ambient cooling
Hard shut off expansion valve on indoor coil
Liquid line solenoid on indoor coil
Required for single--phase scroll compressors in the
following applications:
Long line
Low ambient cooling
Suggested for all compressors in areas with a history of
low voltage problems.
3. Compressor Start Assist — PTC Type
Solid state electrical device which gives a ”soft” boost to the
compressor at each start--up.
Usage Guideline:
Suggested in installations with marginal power supply.
4. Crankcase Heater
An electric resistance heater which mounts to the base of the
compressor to keep the lubricant warm during off cycles. Improves
compressor lubrication on restart and minimizes the chance of
liquid slugging.
Usage Guideline:
Required in low ambient cooling applications.
Required in long line applications.
Suggested in all commercial applications.
5. Evaporator Freeze Thermostat
An SPST temperature--actuated switch that stops unit operation
when evaporator reaches freeze--up conditions.
Usage Guideline:
Required when low ambient kit has been added.
6. Isolation Relay
An SPDT relay which switches the low--ambient controller out of
the outdoor fan motor circuit when the heat pump switches to
heating mode.
7. Liquid--Line Solenoid Valve (LLS)
An electrically operated shutoff valve which stops and starts
refrigerant liquid flow in response to compressor operation. It is to
be installed at the outdoor unit to control refrigerant off cycle
migration in the heating mode.
8. Low--Ambient Pressure Switch Kit
A long life pressure switch which is mounted to outdoor unit
service valve. It is designed to cycle the outdoor fan motor in order
to maintain head pressure within normal operating limits. The
control will maintain working head pressure at low--ambient
temperatures down to 0_F(--18_C) when properly installed.
9. MotorMasterr Low--Ambient Controller
A fan--speed control device activated by a temperature sensor,
designed to control condenser fan motor speed in response to the
saturated, condensing temperature during operation in cooling
mode only. For outdoor temperatures down to --20_F (--28.9_C), it
maintains condensing temperature at 100_F 10_F (37.8_C
6.5_C).
REQUIRED FOR
LONG LINE APPLICATIONS*
Ye s
SEA COAST APPLICATIONS
(Within 2 miles / 3.22 km)
Usage Guideline:
Required in all heat pumps where low ambient kit has
been added.
Usage Guideline:
An LLS is required in all long line heat pump
applications to control refrigerant off cycle migration in
the heating mode. See Long Line Guideline.
Usage Guideline:
A Low--Ambient Pressure Switch or MotorMasterr
Low--Ambient Controller must be used when cooling
operation is used at outdoor temperatures below 55_F
(12.8_C).
Usage Guideline:
A MotorMasterr
Low Ambient Controller or
Low--Ambient Pressure Switch must be used when
cooling operation is used at outdoor temperatures
below 55_F (12.8_C).
Suggested for all commercial applications.
REQUIRED FOR
No
6
Page 7
Accessory Description and Usage (Listed Alphabetically) -- CONTINUED
10. Outdoor Air Temperature Sensor
Designed for use with Carrier Thermostats listed in this
publication. This device enables the thermostat to display the
outdoor temperature. This device also is required to enable special
thermostat features such as auxiliary heat lock out.
Usage Guideline:
Suggested for all Carrier thermostats listed in this
publication.
11. Outdoor Thermostat
AnSPDTtemperature--actuatedswitch which turns on
supplemental electric heaters when outdoor air temperature drops
below a user--selected set point.
Usage Guideline:
Electric supplemental heat applications in non--variable
speed indoor units when electric heat staging is desired.
12. Secondary Outdoor Thermostat
An SPDT temperature--actuated switch which turns on third--stage
of supplemental electric heaters when outdoor air temperature
drops below the second--stage set point.
Usage Guideline:
Outdoor thermostat applications where electric heater is
capable of 3--stage operation.
13. Snow Stand Rack
Coated wire rack which supports unit 18 in. (457.2 mm) above
mounting pad to allow for drainage from unit base.
Usage Guideline:
Suggested in the following applications:
Heat pump installations in heavy snowfall areas.
Heat pump installations in snow drift locations.
Heat pump installations in areas of prolonged
subfreezing temperatures.
All commercial installations.
14. Sound Hood
Wraparound sound reducing cover for the compressor. Reduces the
sound level by about 2 dBA.
Usage Guideline:
Suggested when unit is installed closer than 15 ft.
(4.577 m) to quiet areas, bedrooms, etc.
Suggested when unit is installed between two houses less
than 10 ft. (3.05 m) apart.
15. Thermostatic Expansion Valve (TXV) Bi--Flow
A modulating flow--control valve which meters refrigerant liquid
flow rate into the evaporator in response to the superheat of the
refrigerant gas leaving the evaporator.
Usage Guideline:
Accessory required to meet AHRI rating and system
reliability, where indoor not equipped.
Required in all heat pump applications designed with
Puron refrigerant.
16. Time--Delay Relay
An SPST delay relay which briefly continues operation of indoor
blower motor to provide additional cooling after the compressor
cycles off.
Note: Most indoor unit controls include this feature. For those that
do not, use the guideline below.
Usage Guideline:
Accessory required to meet AHRI rating, where indoor
* Permissible limits of the voltage range at which the unit will operate satisfactorily
{ If wire is applied at ambient greater than 30_C , c o n s u l t t a b l e 31 0 --- 1 6 o f t h e N E C ( NFPA 7 0 ) . The a m p a c it y o f n o n --- m e t a l l ic --- s h e a t h e d c a b l e (NM ) ,
trade name ROMEX, shall be that of 60_C conditions, per the NEC (NFPA 70) Article 336--- 26. If other than uncoated (no ---plated), 60 or 75_C
insulation, copper wire (solid wire for 10 AWG or smaller, stranded wire for larger than 10 AWG) is used, consult applicable tables of the NEC (NFPA 70).
} Length shown is as measured 1 way along wire path between unit and service panel for voltage drop not to exceed 2%.
* * Ti m e --- D e l a y f u s e .
25HCD3
FLA --- Fu l l L oad A m ps
LRA --- L oc k e d R o t o r A m p s
M C A --- Minimum Circuit Amps
RLA --- RatedLoadAmps
NOTE: Control circuit is 24--- V on all units and requires external power source. Copper wire must be used from service disconnect to unit.
All motors/compressors contain internal overload protection.
Complies with 2007 requirements of ASHRAE Standards 90.1
NOTE: Subcooling is for field installed TXV (except for 060)
9 (5.0)
MAX
LENGTH
ft (m)‡
MAX
FUSE**
or CKT
BRK
AMPS
8
Page 9
25HCD3
DIMENSIONS -- ENGLISH
9
Page 10
25HCD3
DIMENSIONS -- SI
10
Page 11
-23.3-17.8-12.2-6.7-1.14.410.015.621.126.7
0.0
2.9
5.9
8.8
11.7
14.7
17.6
20.5
23.4
0
10
20
30
40
50
60
70
80
-10.00.010.020.030.040.050.060.070.080.0
kW
BUILDING HEAT LOSS, UNIT INTEGRAT ED HEATING CAPACITY, MB TUH
OUTDOOR TEMPERATURE
25HCD 360
25HCD 318
FB4CNF 018
25HCD 342
FB4CNF 042
0F0
C
FY5BNB060
25HCD 348
FB4CNF 048
FB4CNF 036
25HCD 330
25HCD 336
FB4CNF 030
25HCD 324
FB4CNF 024
BASED ON INDOOR ENTERING
AIR AT 70◦F (21.1◦C) AND AT RATED
CFM
25HCD3
25HCD3 BALANCE POINT WORKSHEET
11
Page 12
Wall
6”
(152.4)
24”
(609.6)
25HCD3
Wall
Service
12”
(304.8)
12”
(304.8)
24”
(609.6)
Service
18”
(457.2)
24”
(609.6)
Service
18”
(457.2)
Clearances (various examples)
12”
(304.8)
6”
Wall
(152.4)
Wall
12”
(304.8)
24”
CLEARANCES
(609.6)
Service
12
24”
(609.6)
Service
18”
(457.2)
Note: Numbers in ( ) = mm
IMPORTANT: When installing multiple units in an alcove, roof well, or partially enclosed area, ensure there is adequate ventilation to prevent re--circulation of discharge air.
Page 13
TESTED AHRI* COMBINATION RATINGS
NOTE: Ratings contained in this document are subject to change at any time.
For AHRI ratings certificates, please refer to the AHRI directory www.ahridirectory.org
Additional ratings and system combinations can be accessed via the Carrier database at: www.MyCarrierRatings.com
For performance data at specific application &/or design conditions with various indoor unit combinations, the
equipment performance calculator can be accessed at :
* AHRI = Air Conditioning, Heating & Refrigeration Institute
Model
Number
Cooling
Capacity
EERSEER
High Temp
Capacity
47˚F(8_C)
COP
HSPF
Low Temp
Capacity
17˚F ( --- 8_C)
* Ratings are net values reflecting the effects of circulating fan heat. Supplemental electric heat is not included. Ratings are based on:
Cooling Standard: 80_F(27_C) db 67_F(19_C) wb indoor entering air temperature and 95_F(35_C) db air entering outdoor unit.
High---Temp Heating Standard: 70_F(21_C) db indoor entering air temperature and 47_F(8_C) db 43°F (6_C) wb air entering outdoor unit.
Low--- Temp Heating Standard: 70_F(21_C) db indoor entering air temperature and 17_F ( --- 8_C ) d b 1 5 ° F ( --- 9 _C) wb air entering outdoor unit.
COP — Coefficient of Performance
EER — Energy Efficiency Ratio
HSPF — Heating Seasonal Performance Factor
SEER — Seasonal Energy Efficiency Ratio
COP
25HCD3
13
Page 14
Tot a l
KW**
System
Tot a l
KW**
System
Capacity MBtuh
Tot a l
KW**
System
Capacity MBtuh
25HCD3
Tot a l
Tot a l
Capacity MBtuh
KW**
System
KW**
System
Capacity MBtuh
Tot a l
KW**
System
Capacity MBtuh
Tot a l
KW**
System
Capacity MBtuh
Tot a l
KW**
System
CONDENSER ENTERING AIR TEMPERATURES ° F (°C )
Capacity MBtuh
Tot a l
KW**
System
25HCD318(A,W)**30 Outdoor Section With FB4CNF018 Indoor Section
{ Total and sensible capacities are net capacities. Blower motor heat has been subtracted.
} Sensible capacities shown are based on 80_F(27_C) entering air at the indoor coil. For sensible capacities at other than 80_F(27_C), deduct 835 Btuh
(245 kW) per 1000 CFM (480 L/S) of indoor coil air for each degree below 80_F(27_C), or add 835 Btuh (245 kW) per 1000 C FM (480 L/S) of indoor coil air per degree above 80_F(27_C).
# Detailed cooling capacities are based on indoor and outdoor unit at the same elevation per AHRI standard 210/240 ---2008. If additional tubing length and/or indoor unit is l ocated above outdoor unit, a slight variation in capacity may
occur.
** System kw is total of indoor and outdoor unit ki lowatts.
{{ At TVA rating indoor condition (75_F edb/63_F ewb). All other indoor air temperatures are at 80_F edb.
NOTE: When the required data falls between the published data, interpolation may be performed. Extrapolation is not an acceptable practice.
EWB — Entering Wet Bulb
17
Page 18
KW
tem
KW†
Tot a l
Syst.
In-
teg*
Tot a l
Capacity MBtuh
KW†
Tot a l
Syst.
In-
teg*
Tot a l
Capacity MBtuh
KW†
Tot a l
Syst.
In-
teg*
Sys-
Tot a l
Capacity MBtuh
KW
tem
Sys-
Tot a l
Capacity MBtuh
KW
tem
Sys-
Tot a l
25HCD3
Tot a l
Capacity MBtuh
KW†
Tot a l
Syst.
In-
teg*
Tot a l
Capacity MBtuh
KW†
Tot a l
Syst.
In-
teg*
OUTDOOR COIL ENTERING AIR TEMPERATURES ° F (°C)
Tot a l
Capacity MBtuh
KW†
Tot a l
Syst.
25HCD318(A,W)** 30 Outdoor Section With FB4CNF 018 Indoor Section
In-
teg*
Tot a l
Capacity MBtuh
KW†
Tot a l
Syst.
Capacity MBtuh
KW
tem
Sys-
Tot a l
Capacity MBtuh
KW
tem
Sys-
Tot a l
OUTDOOR COIL ENTERING AIR TEMPERATURES ° F (°C)
Capacity MBtuh
KW
tem
Sys-
Tot a l
25HCD324(A,W)** 30 Outdoor Section With FB4CNF 024 Indoor Section
NOTE: When the required data falls between the published data, interpolation may be performed. Extrapolation is not an acceptable practice.
* The Btuh heating capacity values shown are net integrated values from which the defrost effect has been subtracted. The Btuh heating from supplement heaters should be added to those values to obtain total system capacity.
{ The kW values i nclude the compressor, outdoor fan motor, and i ndoor blower motor. The kW from supplement heaters should be added to these values to obtain total system kilowatts.
EDB —EnteringDryBulb
21
Page 22
GUIDE SPECIFICATIONS
GENERAL
AIR--COOLED, SPLIT--SYSTEM HEAT PUMP
25HCD3
1--1/2 TO 5 NOMINAL TONS
System Description
Outdoor--mounted, air--cooled, split--system heat pump unit
suitable for ground or rooftop installation. Unit consists of a
hermetic compressor, an air--cooled coil, propeller--type condenser
fan, and a control box. Unit will discharge supply air upward as
shown on contract drawings. Unit will be used in a refrigeration
circuit to match up to a packaged fan coil or coil unit.
Quality Assurance
— Unit will be rated in accordance with the latest edition of
AHRI Standard 240.
— Unit will be certified for capacity and efficiency, and
listed in the latest AHRI directory.
— Unit construction will comply with latest edition of
ANSI/ ASHRAE and with NEC.
— Unit will be constructed in accordance with UL
standards and will carry the UL label of approval. Unit
25HCD3
will have C--UL approval.
— Unit cabinet will be capable of withstanding Federal Test
Method Standard No. 141 (Method 6061) 500--hr salt
spray test.
— Air--cooled condenser coils are pressure tested and the
outdoor unit is leak tested.
— Unit constructed in ISO9001 approved facility.
Delivery, Storage, and Handling
— Unit will be shipped as single package only and is stored
and handled per unit manufacturer’s recommendations.
Warranty (for inclusion by specifying engineer)
— U.S. and Canada only.
PRODUCTS
Equipment
— Factory assembled, single piece, air--cooled heat pump
unit. Contained within the unit enclosure is all factory
wiring, piping, controls, compressor, refrigerant charge
Puronr (R--410A), and special features required prior to
field start--up.
Unit Cabinet
— Unit cabinet will be constructed of galvanized steel,
bonderized, and coated with a powder coat paint.
— Available with dense grille only.
Fans
— Condenser fan will be direct--drive propeller type,
discharging air upward.
— Condenser fan motors will be totally enclosed, 1--phase
type with class B insulation and permanently lubricated
bearings.
— Shafts will be corrosion resistant.
— Fan blades will be statically and dynamically balanced.
— Condenser fan openings will be equipped with steel wire
safety guards.
Compressor
— Compressor will be hermetically sealed.
— Compressor will be mounted on rubber vibration
isolators.
Condenser Coil
— Condenser coil will be air cooled.
— Coil will be constructed of aluminum fins mechanically
bonded to copper tubes which are then cleaned,
dehydrated, and sealed.
Refrigeration Components
— Refrigeration circuit components will include liquid--line
shutoff valve with sweat connections, vapor--line shutoff
valve with sweat connections, system charge of Puronr
— The capacity of the unit will meet or exceed _____ Btuh
at a suction temperature of _____ _F/_C. The power
consumption at full load will not exceed _____ kW.
— Combination of the unit and the evaporator or fan coil
unit will have a total net cooling capacity of _____ Btuh
or greater at conditions of _____ CFM entering air
temperature at the evaporator at _____ _F wet bulb and
_____ _F/_C dry bulb, and air entering the unit at _____
_F/_C.
— The system will have a SEER of _____ Btuh/watt or
greater at DOE conditions.
Electrical Requirements
— Nominal unit electrical characteristics will be _____ v,
single phase, 60 hz. The unit will be capable of
satisfactory operation within voltage limits of _____ v to
_____ v.
— Nominal unit electrical characteristics will be _____ v,
three phase, 60 hz. The unit will be capable of
satisfactory operation within voltage limits of _____ v to
_____ v.
— Unit electrical power will be single point connection.
— Control circuit will be 24v.
Special Features
— Refer to section of this literature identifying accessories
and descriptions for specific features and available
enhancements.
22
Page 23
SYSTEM DESIGN SUMMARY
1. Intended for outdoor installation with free air inlet and outlet. Outdoor fan external static pressure available is less than 0.01--in. wc.
2. Minimum outdoor operating air temperature without low--ambient operation accessory is 55_F (12.8_C).
3. Maximum outdoor operating air temperature for cooling mode is 125_F (51.7_C).
4. Minimum outdoor operating air temperature for heating mode is –30_F (–34.4_C).
5. Maximum outdoor operating air temperature for heating mode is 66_F (18.9_C).
6. For reliable operation, unit should be level in all horizontal planes.
7. For interconnecting refrigerant tube lengths greater than 80 ft (23.4 m) and/or elevation differences between indoor and outdoor units
greater than 20 ft (6.1 m), consult Residential Piping and Longline Guideline and Service Manual available from equipment distributor.
8. If any refrigerant tubing is buried, provide a 6 in. (152.4 mm) vertical rise to the valve connections at the unit. Refrigerant tubing
lengths up to 36 in. (914.4 mm) may be buried without further consideration. Do not bury refrigerant lines longer than 36 in. (914.4
mm).
9. Use only copper wire for electric connection at unit. Aluminum and clad aluminum are not acceptable for the type of connector
provided.
10. Do not apply capillary tube indoor coils to these units.
11. Factory--supplied filter drier must be installed.
25HCD3
23
Page 24
25HCD3
Copyright 2013 Carrier Corp. S 7310 W. Morris St. S Indianapolis, IN 46231Edition Date: 03/13
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
Catalog No: 25HCD3--- 1PD
Replaces: New
24
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.