Carrier CNPVU2417ACA, CNPVU2414ACA, CNPVU3017ACA, CNPVU3117ACA, CNPVU3617ACA Installation Instructions Manual

...
Page 1
CNPVU CNRVU
Installation Instructions
NOTE: Read the entire instruction manual before starting the
installation.
PAGE
SAFETY CONSIDERATIONS 1.........................
INTRODUCTION 1...................................
INSTALLATION 2....................................
Procedure 1 — Inspect Equipment 2....................
Procedure 2 — Select Installation 3....................
Procedure 3 — Installation of Evaporator Coil 4...........
Procedure 4 — Connect Refrigerant Piping 6.............
Procedure 5 — Connect Refrigerant Liquid
and Suction Lines 6....................
Procedure 6 — Condensate Drain Line Connection 7.......
Procedure 7 — Humidifier Application 8................
SAFETY CONSIDERATIONS
Improper installation, adjustment, alteration, service, maintenance, or use can cause explosion, fire, electrical shock, or other conditions which may cause death, personal injury or property damage. Consult a qualified installer, service agency, or your distributor or branch for information or assistance. The qualified installer or agency must use factoryauthorized kits or accessories when modifying this product. Refer to the individual instructions packaged with the kits or accessories when installing.
Follow all safety codes. Wear safety glasses, protective clothing, and work gloves. Use quenching cloth for brazing operations. Have fire extinguisher available. Read these instructions thoroughly and follow all warning or cautions included in literature and attached to the unit. Consult local building codes and the current editions of the National Electrical Code (NEC) NFPA 70.
In Canada, refer to the current editions of the Canadian Electrical Code CSA C22.1.
Recognize safety information. When you see this symbol the unit and in instructions or manuals, be alert to the potential for
personal injury. Understand the signal words DANGER, WARNING, CAUTION, and NOTE. These words are used with the safetyalert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
on
Uncased Coils
Upflow - Downflow
Heating - Cooling
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Before installing or servicing system, always turn off main power to system. There may be more than one disconnect switch. Tag disconnect switch with a suitable warning label. Turn off accessory heater power if applicable.
!
CAUTION
UNIT OR PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in product or property damage.
This coil contains Nitrogen precharge of 15 PSI. Release of this pressure through the center of the rubber plugs is required before removing the plugs.
!
CAUTION
CUT HAZARD
Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate protective clothing and gloves when handling parts.
IMPORTANT: Nitrogen can leak out through the hole that the needle pierced in the plugs. This does not indicate a leaking coil nor warrant return of the coil.
INTRODUCTION
Use this instruction manual to install indoor coils on upflow or downflow furnaces. (See Fig. 1.) Do not install coil in horizontal position. Models CNPVU/CNRVU have factory−installed thermostatic expansion valves (TXVs). CNPVU models are used with Puronr refrigerant (R410A) systems and CNRVU models are used with R22 systems.
Page 2
INSTALLATION
These units can be installed in either upflow or downflow configurations. Before installation, there are several performance requirements that must be considered because poor installation can negatively alter performance. This section will briefly discuss those factors.
TXV
A thermal expansion valve is utilized in this coil design to optimize performance and comfort throughout the entire operating range of the system. Special attention needs to be taken to the TXV when installing the coil
S Do not overheat valve. Temperatures that exceed 212_F (100_C)
can harm valve performance. Use a wet cloth or heat sink when
brazing.
S Place filter dryer near ID unit to reduce the risk of debris
clogging the valve.
S Make sure TXV bulb is securely fastened and wrapped in the
indentation on heater tube.
CNPVU Models: These coils have a factoryinstalled hardshutoff TXV designed
only for use with R−410A refrigerant. Use only with outdoor units designed for R410A.
CNRVU Models:
These coils have a factoryinstalled hardshutoff TXV designed only for use with R22 refrigerant. Use only with outdoor units designed for R−22.
NOTE: All TXVs have preset superheat settings and are not fieldadjustable.
Airflow
Airflow amount and distribution are vital to adequate system performance. Problems that can be experienced with incorrect airflow include:
S low system performance
S restricted TXV
S frosted coil
S poor humidity control
S water blowoff
When attaching the coil and building the plenum, pay special attention to the effect these details will have on airflow. After system startup, check the cfm to insure that it is correct. (Generally, the cfm should be 350 to 400 cfm/ton during normal cooling operation.)
Condensate Management
With proper installation, these coils will manage the condensate without blowoff into the duct work. See detailed instructions for more info.
Procedure 1 — Inspect Equipment
File claim with shipper if equipment is damaged. The following parts are included with this coil (See Fig. 1),
depending on your application different components will be required.
COMPONENT QUANTITY
Support Rails 2
Collar 1
Header Plate 1
Grommets 2
Extension Air Baffles 2
Header Plate 1 pc.
Support Rails 2 pcs.
Extension Air Baffles 2 pcs. (Attached to coil)
Uncased N-coil
Collar 1 pc.
A06362
Fig. 1 Uncased NCoil Components
2
Page 3
Procedure 2 — Select Installation
Select and follow the installation instruction that best suits your needs:
Uncased N - Coil
Applications
Replacement
Applications
Cased
Cased
Applications
Applications
Cased “ A ” Cased “ N ” Uncased “ A ”
Cased “ A ”
Old CD5
Follow
procedur e
3A
Cased “ N ”
Old CK5
Follow
procedur e
3B
Plenum
Applications
Uncased “ A ”
Old CC5
Follow
procedur e
3C
N-Coil
Kit Casing
Applications
Follow
procedur e
3D
New
Applications
Plenum
Applications
Follow
procedur e
3E
A06363
Fig. 2 Uncased NCoil Applications
Table 1 – CNPVU Uncased Coil Information
MODEL NUMBER TONNAGE
COIL SIZE (IN.) COLLAR SIZE (IN.)
Depth Width Depth Width Liquid Suction
CNPVU1814A(C,T,L)A 1-1/2 19-1/8 13-1/2 19-3/8 12-7/8 3/8 5/8 KCAKC2601ECC CNPVU1917A(C,T,L)A 1-1/2 19-1/8 16-3/4 19-3/8 16-1/4 3/8 3/4 KCAKC3001ECC CNPVU2414A(C,T,L)A 2 19-1/8 13-1/2 19-3/8 12-7/8 3/8 5/8 KCAKC2601ECC CNPVU2417A(C,T,L)A 2 19-1/8 16-7/8 19-3/8 16-1/4 3/8 5/8 KCAKC2701ECC CNPVU3014A(C,T,L)A 2-1/2 19-1/8 13-1/2 19-3/8 12-7/8 3/8 3/4 KCAKC2601ECC CNPVU3017A(C,T,L)A 2-1/2 19-1/8 16-7/8 19-3/8 16-1/4 3/8 3/4 KCAKC2701ECC CNPVU3117A(C,T,L)A 2-1/2 19-1/8 16-3/4 19-3/8 16-1/4 3/8 3/4 KCAKC3101ECC CNPVU3617A(C,T,L)A 3 19-1/8 16-7/8 19-3/8 16-1/4 3/8 3/4 KCAKC2701ECC CNPVU3621A(C,T,L)A 3 19-1/8 20-1/4 19-3/8 19-5/8 3/8 3/4 KCAKC2801ECC
CNPVU37171A(C,T,L)A 3 19-1/8 16-3/4 19-3/8 16-1/4 3/8 7/8 KCAKC3201ECC
CNPVU4221A(C,T,L)A 3-1/2 19-1/8 20-1/4 19-3/8 19-5/8 3/8 7/8 KCAKC2801ECC CNPVU4324A(C,T,L)A 3-1/2 19-1/8 23-3/4 19-3/8 23-1/8 3/8 7/8 KCAKC3301ECC CNPVU4821A(C,T,L)A 4 19-1/8 20-1/4 19-3/8 19-5/ 3/8 7/8 KCAKC2801ECC CNPVU4824A(C,T,L)A 4 19-1/8 23-3/4 19-3/8 23-1/8 3/8 7/8 KCAKC2901ECC CNPVU6024A(C,T,L)A 5 19-1/8 23-3/4 19-3/8 23-1/8 3/8 7/8 KCAKC2901ECC CNPVU6124A(C,T,L)A 5 19-1/8 23-3/4 19-3/8 23-1/8 3/8 7/8 KCAKC3401ECC
COIL CONNECTION
TUBE SIZE (IN.)
KIT CASING
Model #
Table 2 – CNRVU Uncased Coil Information
MODEL NUMBER TONNAGE
COIL SIZE (IN.) COLLAR SIZE (IN.)
Depth Width Depth Width Liquid Suction
CNRVU1814A(T,L)A 1-1/2 19-1/8 12-1/4 19-3/8 12-1/2 3/8 5/8 KCAKC2601ECC CNRVU2414A(T,L)A 2 19-1/8 12-5/16 19-3/8 12-9/16 3/8 5/8 KCAKC2601ECC CNRVU2417A(T,L)A 2 19-1/8 16-7/8 19-3/8 16-1/4 3/8 5/8 KCAKC2701ECC CNRVU3014A(T,L)A 2-1/2 19-1/8 12-5/16 19-3/8 12-5/8 3/8 3/4 KCAKC2601ECC CNRVU3017A(T,L)A 2-1/2 19-1/8 16-7/8 19-3/8 16-1/4 3/8 3/4 KCAKC2701ECC CNRVU3617A(T,L)A 3 19-1/8 15-5/8 19-3/8 15-15/16 3/8 3/4 KCAKC2701ECC CNRVU3621A(T,L)A 3 19-1/8 20-1/4 19-3/8 19-5/8 3/8 3/4 KCAKC2801ECC CNRVU4221A(T,L)A 3-1/2 19-1/8 19 19-3/8 19-5/16 3/8 7/8 KCAKC2801ECC CNRVU4821A(T,L)A 4 19-1/8 19 19-3/8 19-5/16 3/8 7/8 KCAKC2801ECC CNRVU4824A(T,L)A 4 19-1/8 23-3/4 19-3/8 23-1/8 3/8 7/8 KCAKC2901ECC CNRVU6024A(T,L)A 5 19-1/8 22-5/8 19-3/8 22-7/8 3/8 7/8 KCAKC2901ECC
For the 11th digit position in the model number; C = standard copper, L = Aluminum and T = tin-plated copper
COIL CONNECTION
TUBE SIZE (IN.)
KIT CASING
Model #
3
Page 4
See Table 1 and 2 for dimensions and overhang options. Note
Remove this portion
Remove this portion
instructions for placement of coil casing on furnace. For replacement applications using an existing CD5 coil assembly
follow Procedure 3A. For replacement applications using an existing CK5 coil assembly
follow Procedure 3B.
For replacement applications using an existing uncased A−coil plenum installation follow Procedure 3C.
For new applications using a KCAKC Ncoil kit casing follow Procedure 3D.
For new applications using a field−fabricated plenum installation follow Procedure 3E.
Procedure 3 — Installation of Evaporator Coil
!
CAUTION
Remove this portion
Remove this portion
A96359
Fig. 4 Channel Cutting
4. Place the two support rails in the sides of the casing and the collar as indicated in Fig. 5 & 6.
UNIT OR PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in product or property damage.
Take precautions to ensure that aluminum tubes do no come in direct contact or allow for condensate runoff with dissimilar metal. Dissimilar metals can cause galvanic corrosion and possible premature failure.
!
CAUTION
CUT HAZARD
Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate protective clothing and gloves when handling parts.
3A. Upflow and downflow applications using an existing CD5 coil casing.
1. Remove and keep front access and tubing header panel.
2. Remove old A−coil from casing and discard coil.
3. Remove the two internal side channels from existing casing by removing 4 screws each side (see Fig.3, recommended procedure). When screws cannot be reached, cut top and bottom portions of the channels as indicated in Fig. 4.
A06286
Fig. 5 Support Rails Installation
A06287
Fig. 6 Collar Installation
IMPORTANT: Insure that collar is level for proper drainage.
5. Slide new Ncoil on top of collar. See Fig. 7 & 8.
Fig. 3 Channels Removal
A06284
A06288
Fig. 7 Uncased NCoil Installation
4
Page 5
A
66.2
A06289
Fig. 8 Uncased NCoil & CD5 Casing
6. Cut new holes for liquid, suction and drain connections in the existing header panel. Use new header plate supplied with new coil as template to locate holes. Align bottom of new header plate to the bottom of the header panel as indic­ated in Fig. 9.
4. Cut holes for liquid, suction and drain connections in the existing header panel. Use new header plate supplied with coil as template to locate holes. Align header plate to the header panel using the upper hole as indicated in Fig. 11.
lign through
upper hole
A06292
Fig. 11 Use Header Plate as Template
5. Slide header panel over tubing and condensate pan connec­tions. Secure fitting panel to casing.
6. Cut bottom portion of header plate, just below the drain connections, see Fig. 12.
Align Through Bottom Hole
A06290
Fig. 9 Use Header Plate as Template
Cut this portion
mmmm66.2
7. Slide header panel over tubing and condensate pan connec­tions. Secure fitting panel to casing.
8. Slide new header plate and grommets over tubing and
Fig. 12 Header Plate CutOff
approx. 2-5/8"
A06293
condensate pan connections and secure it to the header pan­el to cover up oversized and additional holes. This will provide an airtight seal and better installation presentation. See Fig. 10.
7. Slide header plate and grommets over tubing and con- densate pan connections and secure it to the header panel to cover up oversized and additional holes. This will provide an airtight seal and better installation presentation (See Fig.
13).
8. Reinstall and secure front access panel to casing.
Fig. 10 Header Plate Installation
A06291
9. Reinstall and secure front access panel to casing.
3B. Upflow and downflow applications using an existing CK5 coil casing.
1. Remove and keep front access and tubing header panel.
2. Remove old N−coil from casing and discard coil.
3. Slide new N−coil into casing.
Fig. 13 − Uncased N−Coil & CK5 Casing
3C. Upflow and downflow replacement applications using an existing plenum with an uncased A−coil.
1. Cut front access of plenum so that old A−coil can be re- moved.
A06364
5
Page 6
2. Remove old A−coil from plenum and discard coil.
3. Place collar over furnace flanges inside of plenum (See Fig.
1).
IMPORTANT: Insure that collar is level for proper drainage.
4. Remove front and rear extension air baffles from new Ncoil.
5. Slide new N−coil into plenum.
6. Cut holes for liquid, suction and drain connections in the existing fieldfabricated front access panel of plenum on fabricated new panel. Use header plate supplied with coil as template to locate holes.
7. Slide header plate and grommets over tubing and con- densate pan connections and secure it to the plenum front access to cover up oversized and additional holes. This will provide an airtight seal and better installation presentation.
8. Seal all joints to create air tight seal using locally approved materials.
3D. Upflow and downflow applications using KCAKC N−coil casing. See Table 1 and 2 for proper kit casing model number matchup.
1. Remove and keep front access and tubing header panel.
IMPORTANT: Insure that collar is level for proper drainage.
2. Slide new N−coil into casing.
3. Cut holes for liquid and suction connections in the existing header panel. Use header plate supplied with coil as tem­plate to locate holes. Align header plate to header panel us­ing the upper hole as indicated in Fig. 11.
4. Slide header panel over tubing and condensate pan connec­tions. Secure header panel to casing.
5. Cut bottom portion of header plate, just below the drain connections. See Fig. 12.
6. Slide header plate and grommets over tubing and con- densate pan connections and secure it to the fitting plate to cover up oversized and additional holes. This will provide an airtight seal and better installation presentation.
7. Reinstall and secure front access panel to casing.
3E. Upflow and downflow applications using a new field fabricated plenum installation.
For uncased Ncoil CNPVU/CNRVU width and depth dimensions See Table 1 and 2. Fabricate plenum accordingly.
1. Mount collar directly on furnace flanges to support the coil.
2. Remove front and rear extension air baffles from new Ncoil.
3. Slide new N−coil into plenum opening.
4. Cut holes for liquid, suction connections in field fabricated front plenum panel. Use header plate supplied as template to locate holes.
5. Cover plenum opening with fieldfabricated front plenum panel.
6. Slide header plate and grommets over tubing and con- densate pan connections and secure it to the field fabricated front plenum panel to cover up oversized holes. This will provide an airtight seal and better installation presentation.
7. Seal all joints to create air tight seal using locally approved materials.
IMPORTANT: Locate caution label stapled to installation instructions. Attach to right side of plenum or accessory casing (See Fig. 14).
CAUTION
AIR CONDITIONING COIL BEHIND THIS PANEL. DO NOT DRILL OR CUT PANEL UNTIL COIL LOCATION HAS BEEN VERIFIED BY REMOVING ACCESS COVER.
A06285
Fig. 14 Plenum Caution Label
NOTE: The uncased Ncoil features an enclosure to direct airflow
through the third coil slab.
NOTE: If coil is not being installed in the standard orientation (front of coil matching front of furnace) then coil must be raised 21/4 in. above furnace.
NOTE: Installing coils rotated 90_ from the front of the furnace, in upflow or downflow applications, can cause water blow−off or coil freeze−up due to the concentration of air on one slab of the coil or lack of air to a slab in the coil. It is recommended that on this type of application, a field−supplied adapter be placed between the coil and furnace to allow air to distribute properly between all slabs of the coil.
Procedure 4 — Refrigerant Line Connections
Use accessory tubing package or fieldsupplied tubing of refrigerant grade. Suction tube must be insulated. Do not use damaged, dirty, or contaminated tubing because it may plug refrigerant flowcontrol device. ALWAYS evacuate the coil and fieldsupplied tubing before opening outdoor unit service valves.
Procedure 5 — Connect Refrigerant Liquid and Suction Lines
SUCTION LINE
Suction line is designed for field sweat connection. Line is plugged to keep out moisture and dirt. Remove these plugs only when ready to make connection.
See Table 1 and 2 for coil connection tube size.
For matched and mismatched systems, use line sizes recommended in outdoor unit Installation Instructions.
!
CAUTION
UNIT OR PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in property damage.
Take precautions to ensure aluminum tubes do not come in direct contact or allow for condensate runoff with a dissimilar metal. Dissimilar metals can cause galvanic corrosion and possible premature failure.
The coil can be connected to outdoor units using field−supplied tubing of refrigerant grade. Always evacuate tubing and reclaim refrigerant when making connections or flaring tubing. Leak check connections before insulating entire suction line.
1. Remove cabinet access door.
2. Remove rubber plugs, suction plug then liquid plug, from coil stubs using a pulling and twisting motion. Hold coil stubs steady to avoid bending or distorting.
3. Remove tubing plate with rubber grommets and slide plate with grommets onto the refrigerant lines (field line−set), away from braze joints.
6
Page 7
4. Fit refrigerant lines into coil stubs. Wrap a heat sinking material such as a wet cloth behind braze joints.
5. Wrap TXV and nearby tubing with a heatsinking material such as a wet cloth.
6. Use 1/2 psig Nitrogen purge in the suction and out the liquid line.
7. Braze using a Sil−Fos or Phos−copper alloy. Do not use soft solder.
8. After brazing, allow joints to cool. Carefully remove TXV bulb insulation and verify that the TXV bulb is securely fastened with hose clamp. Tighten screw a halfturn past hand tight with TXV bulb placed in the indentation with full contact with the vapor line tube. Rewrap TXV bulb with insulation.
9. Leak check connections before insulating entire suction line.
10. Slide tubing plate with rubber grommets over joints. Position tubing at center of each grommet to ensure an air seal around the tube. Reinstall cabinet door.
!
CAUTION
PRODUCT DAMAGE HAZARD
Failure to follow this caution may result in product or property damage.
To avoid damage to the refrigerant control device while brazing, wrap tubing or fittings with a heatsinking material such as a wet cloth.
Procedure 6 — Condensate Drain Line Connection
!
CAUTION
PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in property damage.
When installing over a finished ceiling and/or living area, install a fieldfabricated secondary condensate pan under the entire unit.
The coil is designed to dispose of accumulated water through built−in condensate drain fittings. It is recommended that PVC fittings be used on the condensate pan. Do not overtighten. Finger tighten plus 11/2 turns. Be sure to install plastic plug in unused condensate drain fitting. Two 3/4in. female threaded pipe connections are provided in each coil condensate pan.
A trap is not necessary on the condensate line. Consult local codes for additional restrictions or precautions. If local codes require a trap then the following guidelines are suggested to assure proper drainage. Install a trap in condensate line of coil as close to the coil as possible. Make trap at least 3 in. (76 mm) deep and no higher than the bottom of unit condensate drain opening (See Fig. 15). Pitch condensate line 1 in. (25.4 mm) for every 10 ft. of length to an open drain or sump. Make sure that the outlet of each trap is below its connection to condensate pan to prevent condensate from overflowing the drain pan. Prime all traps, test for leaks, and insulate traps and lines if located above a living area.
!
WARNING
PERSONAL INJURY HAZARD
Failure to follow this warning could result in personal injury.
Wear eye protection.
Coil is factory charged with 15 psi nitrogen. The coil is under pressure and TXV screen is in place behind liquid line plug. DO NOT removed liquid line plug first; always remove the suction line plug first to depressurize the coil.
REFRIGERANT METERING DEVICE
CNPVU Models:
These coils have a factoryinstalled hardshutoff TXV designed only for use with Puron refrigerant (R410A). Use only with outdoor units designed for R−410A.
CNRVU Models:
These coils have a factoryinstalled hardshutoff TXV designed only for use with R22 refrigerant. Use only with outdoor units designed for R−22.
NOTE: ALL TXVs HAVE PRESET SUPERHEAT SETTINGS AND ARE FIELD NONADJUSTABLE.
3” / 76mm
A08067
Fig. 15 Condensate Trap
NOTE: If unit is located in or above a living space, where damage
may result from condensate overflow, a fieldsupplied, external condensate pan should be installed underneath the entire unit, and a secondary condensate line (with appropriate trap) should be run from the unit into the pan. Any condensate in this external condensate pan should be drained to a noticeable place. As an alternative to using an external condensate pan, some localities may allow the running of a separate 3/4in. (19 mm) condensate line (with appropriate trap) per local code to a place where the condensate will be noticeable. The owner of the structure must be informed that when condensate flows from secondary drain or external condensate pan, the unit requires servicing or water damage will occur. To further protect against water damage, install a float switch to shut the unit off if the water in the secondary pan gets too high.
NOTE: To avoid drainage problems, test the primary drain line by slowly pouring water into the pan. Check piping for leaks and proper condensate drainage. Using the secondary drain as
7
Page 8
explained in the previous note provides further protection against overflow due to a clogged primary drain.
NOTE: In applications where return air humidity levels stay at 70% or above for a prolonged period of time, condensation can form on the bottom of pan and drip.
WASTE LINE CONNECTION
If the condensate line is to be connected to a waste (sewer) line, an open trap must be installed ahead of the waste line to prevent escape of sewer gases (See Fig. 16 ).
A10216
Fig. 16 Condensate Drain to Waste Line
Supply
Evaporator N*Coil
Upflow Furnace
!
WARNING
EXPLOSION HAZARD
Failure to follow this warning could result in personal injury or death.
Provide trap with air gap in drain line when connecting to waste (sewer) line.
Procedure 7 — Humidifier Application
When installing a humidifier in a system which contains an Ncoil, consideration must be given to location of coil slabs. (See Fig. 17.)
1. Care must be taken to prevent damage of Ncoil when at­taching humidifier to coil casing or plenum.
2. These models are shipped with a Caution Label (see Fig.
14) to be applied to plenum to indicate slab location. When these coils are removed from their casing and applied dir­ectly into the plenum, affix this Caution Label to the right side of the plenum enclosure. This is needed only in cases where the humidifier is not installed with original equip­ment. Label will alert future service and installation techni­cians about coil slab location.
3. Ensure that humidifier has adequate airflow.
A180085
Fig. 17 Installation of Humidifier in System with NCoil
NOTE: The State of California requires Proposition 65 labels
(Prop 65) for products containing materials of concern. Taped to the header plate door is the Proposition 65 Label for this product. Apply this label on the outside front of the furnace coil casing.
3URS /DEHO
)LUH([SORVLRQ
Hazard Warning Label
A180077
Fig. 18 Label Placement on Casing
NOTE: Attached to the literature assembly is the Fire and
Explosion Hazard warning label for this product. Apply this label on the outside front of the furnace coil casing if one does not exist on the casing. (See Fig. 18)
Copyright 2018 CAC / BDP D 7310 W. Morris St. D Indianapolis, IN 46231 Edition Date: 03/18
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
Catalog No: IM-CNPVU-09
Replaces: IM-CNPVU-08
8
Loading...