Installation, Start-Up an
Service Instructions
(For Use in High Wall Applications)
CONTENTS
Page
SAFETY CONSIDERATIONS ................... 1
GENERAL .................................. 1,2
INSTALLATION ............................. 2-13
Step 1 - Complete Pre-lnstallation Checks .... 2
• UNPACK UNIT
• INSPECT SHIPMENT
Step 2 - Select Location ..................... 2
Step 3 - Mount Mounting Bracket on Wall .... 3
Step 4 - Mount Outdoor Section ............. 9
Step 5 - Connect Refrigerant Piping ........ I0
• RIGHT REAR AND BOTTOM PIPING
CONNECTIONS
• RIGHT SIDE PIPING CONNECTIONS
• LEFT SIDE PIPING CONNECTIONS
• ALL TYPES PIPING CONNECTIONS
Step 6 - Make Piping Connections .......... 10
Step 7 - Connect Condensate Drain Line .... ll
Step 8 - Make Electrical Connections ....... 11
• INDOOR SECTION WIRING
• OUTDOOR SECTION WIRING
Step 9 - Install Fan Coil Unit Onto
Mounting Bracket ......................... 13
START-UP ................................ 14-17
40QN Control System ....................... 14
Wireless Remote Controllers ................ 14
After Extended Shutdowns .................. 14
Seasonal Changeovers ...................... 14
To Turn the Unit On and Off ................. 14
Adjusting Airflow ........................... 14
Operating Mode Memory .................... 14
Automatic Operation (Auto) Mode ............ 14
Operating Fault Diagnosis ................... 15
Microprocessor Control Operation ........... 15
CLEANING AND MAINTENANCE ............ 18-19
Lubrication ................................. 18
To Install or Replace Remote Controller
Batteries ................................. 18
To Set the Current Time ..................... 18
To Remove and Clean or Replace Air Filters .. 18
• TO REMOVE AIR FILTERS
• TO CLEAN OR REPLACE FILTERS
To Clean Indoor Unit Front Panel ............ 19
To Clean Indoor Coil ........................ 19
To Clean Outdoor Coil (Outdoor Unit) ........ 19
To Clean Condensate Drains ................. 19
SERVICE ................................... 20
Diagnostic Codes ........................... 20
System Tests ............................... 20
• THERMISTOR TESTS
• COMPRESSOR FAILURE
• REVERSING VALVE FAILURE (38BK Only)
38AN,BK
with 40QN009,012
Cooling Only/Heat Pump Systems
Page
System Safeties and Interlocks .............. 20
• INDOOR FAN FAILURE
• COMPRESSOR SHORT-CYCLING PROTECTION
• INDOOR COIL FREEZE PROTECTION
• INDOOR COIL HIGH-TEMPERATURE
PROTECTION
TROUBLESHOOTING ...................... 20-27
START-UP CHECKLIST ............... CL-I, CL-2
SAFETY CONSIDERATIONS
Installing and servicing air-conditioning equipment can be
hazardous due to system pressure and electrical compo-
nents. Only trained and qualified service personnel should
install or service air-conditioning equipment.
Untrained personnel can perform basic maintenance func-
tions such as cleaning coils and filters and replacing filters.
All other operations should be performed by trained service
personnel.
When working on air conditioning equipment, observe pre-
cautions in the literature and on tags and labels attached to
unit. Follow all safety codes. Wear safety glasses and work
gloves. Use quenching cloth for brazing operations. Have
fire extinguisher available. Before installation, read these in-
structiens thoroughly. Consult local building codes and Na-
tional Electrical Code (NEC) for special installation
requirements.
Electrical shock cancause personal injury or death. Be-
fore installing or servicing system, be sure to turn off
main power to system. There may be more than one dis-
connect switch. Turn off indoor fan coil power as
applicable.
GENERAL
The Carrier 40QNHOI 2 heat pump high wall fan coil unh
(Fig. 1) comes with supplemental electric heat (40QNE009
heat pump fan coil unit does not have electric heat). If your
application requires heating, heat pump units must be used
both outdoors and indoors. See Table 1 for recommended
system combinations.
The matched cooling and heat pump systems consist of an
outdoor section (condensing unit or heat pump) and an in-
door section (fan coil). The outdoor section (38AN or 38BK)
is installed alongside the building structure. It can also be
installed on a flat roof, deck, or on an apartment building
balcony. The indoor section (40QNB009,012 or 40QNE009,
40QNH012) is mounted high on an interior wall that is con-
venient for piping connection to the outdoor section. Two
sizes are available: 9,000 and 12,000 Btuh cooling capaci-
ties. See Fig. 1 for system components, Table 1 for system
ManuPacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4 PC 111 Catalog NO. 535-848 Printed in U.S.A. Form 38A,BI40Q-1SI Pg 1 5-99 Replaces: 53AN,BK-1SI
combinations, and Table 2 for application range. Refer to
this manual for proper installation of the complete system.
Refer to Table 1 to make sure the correct indoor unit is in-
stalled with the correct outdoor unit. Be sure the unit will be
operated within the application guidelines shown in Table 2.
When installing the 38AN or 38BK unit, it is important to
note that for cooling operation when the outdoor air tem-
perature is below 55 F, it is necessary to equip the outdoor
unit with the low-ambient accessory.
To install this unit you will need:
1 40QNB or 40QNE/H Fan Coil unit with standard wire-
less remote controller and indoor unit wire
1 -- 38AN or 38BK Outdoor Unit
1 -- Low-Ambient Kit (if required for your application)
NOTE: Field-supplied wire, drain pipe, refrigerant tubing,
etc., are also required to install unit.
The installation materials provided are for use on instal-
lations where the indoor section is mounted to gypsum wall
board with wall studs. Other types of applications require
field-supplied mounting hardware. Be sure to follow all in-
stanation instructions in this manual carefully in order to achieve
proper unit operation, and be sure that you have all of the
required parts before beginning installation.
Note that the cooling only and heat pump systems utilize
a microprocessor control system to deliver optimum levels
of comfort and efficiency. Refer to Microprocessor Control
Operation section on page 15 for details.
Table 1 -- System Combinations for Indoor
and Outdoor Units
SYSTEM UNIT UNIT
HighWall Cooling Only 40QNB009 38AN009
HighWail Hea_Pump 40QNH012 38BK012
NOTE:Acoolingonlyoutdoorunitmaynotbe matchedwitha heat
pumpindoorunit.a heatpumpoutdoorunitmaynotbe matchedwith
a coolingonlyindoorunit.Donotmismatchsystems.
INDOOR OUTDOOR
40QNB012 38AN012
40QNE009 38BK009
INSTALLATION
Step 1 -- Complete Pre-lnstallation Checks
UNPACK UNIT(S) Store unit(s) in original packaging
until moved to the final site for installation. When removing
unit from carton, lift by its 4 comers. Note that there is a
plastic bag containing mounting screws taped to the mount-
ing bracket.
INSPECT SHIPMENT -- Upon receipt of shipment, in-
spect unit (Fig. 1) for damage. Forward claim papers di-
rectly to the transportation company. Manufacturer is not re-
sponsible for damage incurred in transit.
Check all items (see Table 3), and if any item is missing,
notify your Carrier distributor. To prevent loss or damage,
leave all parts in the original packages until installation.
NOTE: The expansion device is located in outdoor unit.
Step 2 -- Select Location -- Consult local building
codes and NEC for special installation requirements.
NOTE: There are several ways the unit may be installed in
different types of wall construction. These instractions do
not cover all installation methods. As a typical installation,
these instructions focus primarily on mounting the unit to
wall studs in new construction.
Plan your installation carefully before you begin. Listed
below are some guidelines to follow when determining a lo-
cation for the unit:
1. Center unit (horizontally) on the wall selected.
2. Allow sufficient space for airflow clearance, wrong, re-
frigerant piping, and servicing the unit. See Fig. 2-4.
3. Place the unit so it faces normal location of room
occupants.
Table 2 -- Application Range
COOLING
Maximum Minimum
Indoor I Outdoor Indoor Outdoor
95 F DB ] 115 F DB 67 F DB 55 F DB*71 F WB 57 F WB
HEATING
Maximum Minimum
Indoor Outdoor Indoor Outdoor
80FDB 75FDB 55FDB 0°FDB
71 F WB 65 F WB
LEGEND
DB -- Dry Bulb
WB -- Wet Bulb
"Unit may be equipped with a low-ambient control that will allow op-
eration down to -20 F.
TYPICAL FAN COL UNIT
TYPICAL OUTDOOR UNIT
Fig. I -- Typical Cooling Only/
Heat Pump System
m 8 "....._
+
36"
*Aclearanceof 31,_"istheabsoluteminimum.Aclearanceof 10"is
recommended.
NOTE: Remove unitfront cover for control box access.
Fig. 2 -- Minimum Required Fan Coil Unit
Clearances
4. Select walls that are:
a. Strong enough to support the weight of the unit (see
Tables 4A-4D for unit operating weight).
b. Accessible to convenient condensate drainage.
c. Free of obstacles that may block air circulation to the
fan coil.
d. Outside walls (if pussible) to make piping easier.
5. Place top of fan coil unit as high on wall as possible, mak-
ing sure that unit is at least 31Ain. down from ceiling to
permit proper airflow (the recommended clearance is
10 inches). Also, make sure that the unit is not placed
directly over anything that would prevent filter removal
or block airflow.
6. Make sure units are easily accessible to electric power.
7. Refrigerant piping can enter tbe unit through the prepunched
holes. Refrigerant piping can run down along the wall, to
the right or lef_ along the wall, straight through the wall,
or into the wall (recommended location: right rear).
See Fig. 5. Once the piping is through the wall, it can run
inside walls, in ceilings, between floors, or straight to
the outside. See Fig. 6 for maximum line lengths. See
Table 5 for System Piston Guide and Refrigerant
Charging.
NOTE: Run refrigerant piping as directly as possible, and
avoid any unnecessary turns or bends.
8. Condensate piping canbe directed through the inside wall
to an approved drain or directed straight outside.
NOTE: The piping hole for condensate line must be made
at a downward slope to ensure proper drainage. See Mount
Mounting Bracket on Wall section below for details.
Step 3 -- Mount Mounting Bracket on Wall
l. Decide how refrigerant will be piped. If necessary, knock
out the appropriate pre-puncbed holes (Fig. 5) on unit for
piping and electrical connections.
2. Remove bracket from fan coil nnit by pulling it down
from fan coil unit bottom as shown in Fig. 7.
3. Using a carpenter's level, fasten mounting brackets into
the studs in the wall at least 10 in. away from the ceiling
with all the screws provided. Always be sure to insert screws
into the top 2 holes indicated in Fig. 7. Make sure the
attached bracket will support a 200 lb vertical load. For
a masonry wall, anchor shields can be used to attach bracket
to the wall.
4. Temporarily hang unit on bracket to check location and
level.
I_] [,,"_lii[.] _"I
If mounting bracket is not mounted level, the indoor sec-
tion will be mounted unevenly, and condensate drain-
age water may drip onto the floor. Also, a gap between
thebracket and the wall may result in vibration and noise
from the indoor section.
5.
Mark and cut condensate and piping holes.
a. For piping through the wall, mark the wall below the
condensate connection and cut a 2V2-in. hole into the
wall at either point "A" or point "B" in Fig. 8.
NOTE: The 2V2-in hole must be made at a downward
slope to ensure proper condensate drainage. See
Fig. 9. Slope condensate line at a minimum pitch of
1/4in. per foot of line. The condensate line cannot be
run up for upper piping connections -- only refriger-
ant lines may be run up.
b. Push the wall sleeve (factory supplied with the unit)
through the 2]/2-in. wall opening.
Table 3 -- High Wall Unit Package Contents
ITEM QUANTITY
Unit Mounting Template 1
Unit Mounting Bracket 1
1-in. Lag Screws for Unit Mounting 8
Hollow Wall Anchor Bolls for Unit Mounting 5
Wall Sleeve with Wall Cap 1
Infrared Wireless Remote Control 1
AAA Batteries (for Remote Control) 2
Remote Control Mounting Bracket 1
3/n-in. Lag Screws for Remote Mounting Bracket 2
35 ff High Voltage Power Wiring
40QNB009 (3-Wiro with Ground) 1
40QNE009 (2-Wire with Ground) 1
40QNB012 (2-Wire with Ground) 1
40QNH012 (2-Wiro with Ground) 1
35 ft High Voltage Control Power Wiring (3-Wire) 1
35 ft Low Voltage Thermistor Wiring 1
Owner's Manual 1
Installation Instructions 1
Warranty Registration Card 1
Table 4A-- Physical Data, 38AN Cooling Only Condensing Units*
UNIT 38AN
NOMINAL CAPACITY (Tons)
OPERATING WEIGHT (Ib)
REFRIGERANT TYPE
Control (Cooling)
Factory Charge (Ib)
COMPRESSOR TYPE
Model
Oil (Recharge) (oz)
Crankcase Heater
Accumulator
OUTDOOR FAN
Rpm
Diameter (in.)...No. of Blades
Motor Watts
Nominal Air Cfm
OUTDOOR COIL
Face Area (sq tt),..No, of Rows
Fins/In,
CONTROLS
Fusible Plug (F)
Control Voltage
REFRIGERANT LINES
Connection Type
Liquid Line OD (in,)
Vapor Line OD (in,)
Maximum Length (ft)
Maximum Lift Fan Coil (Above Outdoor) (ft)
Maximum Lift Fan Coil (Below Outdoor) (ft)
*These units may only be used with 40QNB009,012 fan coil units
EAA090111A10.1 I EBB120111A10.1
12¼...4 12¼...4
Table 4B -- Physical Data, 40QNB Cooling Only High Wall Units
UNIT 40QNB 009* 012"
NOMINAL CAPACITY (Tons) ¥4 1
NOMINAL SIZE (Btuh) 9000 12,000
OPERATING WEIGHT (Ib) 18.7 24.2
MOISTURE REMOVAL RATE (Pints/Hr) 2.4 3.4
FINISH White
REFRIGERANT R-22
Control (Cooling) Capillary Tube in Outdoor Unit
Factory or System Charge (Ib)t 1.5 I 1,8
INDOOR FAN Direct Drive Centrifugal
Rpm..,Cfm High 1200,,.240 1040...260
Rpm..,Cfm Medium 1100..,210 940,,,240
Rpm...Cfm Low 1000,..180 850,,,210
Motor Watts 34 35
Blowers -- No...,Size (in.) 1,..3.54 x 27.75 1,,,3,94 x 27.75
INDOOR COIL Copper Tube, Aluminum Fin
Face Area (sq ft) 1.45 t6
No. of Rows 2 2
Fins/in, 18 17
Circuits 2 3
FILTERS Cleanable
(Quantity) Size (in.) (2) 9 x 12 I (2) 9_,_x 13_A
AIRSWEEP
Horizontal Manual
Vertical Automatic
CONTROLS integrated Microprocessor
Remote Controller Wireless
Freeze Protection Yes
Auto. Restart Yes
Diagnostics Yes
Timer Mode 24-Hour Startup/Shutdown Type
Test Mode Yes
Dehumidification Mode Yes
Fan Mode HighlMediumlLowlAuto.
Control Voltage 115 v I 230 v
REFRIGERANT LINES
Connection Type Male Flare
Liquid Line OD (in.) ¼ ¼
Vapor Line OD (in.) ½ _,_
Maximum Length (ft) 35 35
Maximum Lift Fan Coil (Above Outdoor)(ft) 16 16
Maximum Lift Fan Coil (Below Outdoor) (ft) 30 30
CONDENSATE DRAIN CONNECTION (in.) % OD, 7/_8ID
*Units may onlybe matched with 38AN outdoorunits.
1"Fullfactory charge shipped in outdoor unit. Charge is determined based on 25 ft of line.
4
009 012
¾ 1
55 62
R-22
1.5 1.8
87 87
850 Propeller, iirect Drive 850
750 750
3.5...1 3.5...2
18 17
210 210
115 230
¼ ¼
½ ½
35 35
16 16
30 30
Capilla_ Tube
Carrier Hermetic Rotary
None
Yes
Copper Tube, Aluminum Fin
Male Flare
Table 4C -- Physical Data, 38BK009,012 Outdoor Heat Pump Units*
UNIT 38BK
NOMINAL CAPACITY (Tons)
OPERATING WEIGHT (Ib)
REFRIGERANT TYPE
Control (Cooling)
Control (Heating)
Factory Charge (Ib)
COMPRESSOR TYPE
Model
Oil (Recharge) (oz)
CRANKCASE HEATER (Watts)
OUTDOOR FAN
Rpm
Diameter (in,),..No. of Blades
Motor Wafts
Nominal Air Cfm
OUTDOOR COIL
Face Area (sq ft)...No, of Rows
Finslln.
CONTROLS
Fusible Plug
Accumulator
Defrost Method
Control Voltage
REFRIGERANT LINES
Connection l_jpe
Liquid Line OD (in.)
Vapor Line OD (in.)
Maximum Length (ft)
Maximum Lift (Fan Coil Above) (ft)
Maximum Lift (Fan Coil Below) (ft)
*These units may only be used with40QNF-./H fan coil units.
009 012
1
60,7 66.5
AccuRatar _ Piston at Outdoor Unit
AccuRater Pistonat Outdoor Unit
1.5 I 2.0
Carder Hermetic Rotary
EBA095111H10.1 I EBC130111H10.1
850
12¼...4
87
756
210 F 210 F
Yes Yes
Demand Demand
3.5._118 Copper Tube, Aluminum
115 v 230 v
¼ ¼
½ ½
35 35
16 16
30 30
R-22
40
Propeller, Direct Drive
Male Flare
Fin
850
121/4._4
87
756
3.5...2
17
Table 4D -- Physical Data, 40QNEIH Heat Pump High Wall Units
UNIT
NOMINAL CAPACITY (Tons)
NOMINAL SIZE (Btuh)
OPERATING WEIGHT (Ih)
MOISTURE REMOVAL RATE (Pints/hr)
REFRIGERANT
Control (Cooling)
Control (Heating)
Factory Charge (Ib)t
INDOOR FAN
RpndCfm High
Rpm/Cfm Medium
RpndCfm Low
Motor Watts
Blowers Quantity...Size (in.)
INDOOR COIL
Face Area
NO. of Rows
Fins/in.
Clrculta
FILTERS
Quantity...Size (in.)
40QNEO09* 40QNH012*
_, 1
9000 12.000
18.7 242
24 3.4
AccuRate_ Piston at Outdoor Unit
AccuRater Piston at Outdoor Unit
15 I 20
1200/240 1040/280
1100/210 940/240
Direct Dnve Centrifugal
10001180 850/210
34 35
1354 x 27.75 1394 x 27.75
Copper Tube. Aluminum Fin
1.45 1.6
2 2
18 17
2 3
Cleanabie
2...9 x 12 I 2...91/2x 13_/4
AIRSWEEP
Horizontal
Vertical
CONTROLS
Remote Controller Options
Diagnostics
Defrost Method
Timer Mode
Integrated Microprocessor
Manual
Automatic
Wireless
Demand Defrost
Warm Start Feature
Teat Mode
Freeze Protection
Dehumidification Mode
Fan Mode
Auto Changeover
Auto Restart
Control Voltage
115 v I
High/MediumlLowlAuto
REFRIGERANT LINES
Connection Type
Liquid Line OD (in.)
Vapor Line OD (in.)
Maximum Length (ft)
Maximum Lift (Fan Coil Above) (ft)
Maximum Lift (Fan Coil Below) (tt)
CONDENSATE DRAIN SIZE (in.)
¼ ¼
½ ½
35 35
16 16
30 30
Male Flare
OD, 7A6ID
"These units may only be matched with 38BK outdoor units. The 40QNH unit available in size 012 only.
l-Full factory charge is shipped in the outdoor unit. The charge is determined based on 25 It of line.
R-22
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
I
230 v
2'_0"
[6103
- 19 u
2 O"
C6101
, 1
l'
°..5o._sciso,
7/8"-
[2513
2"_2 o
HIGH VOLTA_I_ TO _1
I 1/8" Dik.
INDOOR _ECT]ON _!
i I I,,', i-- --* _ \ ' _ _ "_q
_ _ ._ - ,
TOP VIEW
0"-1 3/1_"
'f 0''1[4215/B"
[3o] [o'&_]i/e"
? ,
0"-3 11/16"
1
[941
_'_HI_'IV_-TAGE TO
3/4" DIA,
0".23 1/4"
C590]
_ "_0,_4.
[101_
PIIONT VlE_
NOTES:
1. Dimensions in [ ] are in millimeters.
k
2. _ Direction of airflow.
3. _ Center of Gravity.
4. Minimum clearances: 4 in. on coil sides, 24 in. on fan side, and
30 in. service side.
LJI]%,,:-I
Fig. 3 -- 38AN/BK Dimensional Drawing
UNIT
38
AN009
AN012
BK009
BK012
NleHT 810E VIEW
WEIGHT
Lb
55.0
62.0
60.7
66.5
Kg
25,0
28.1
27.5
30.2
I_T A]R
!
MINIMUM CLEARANCE FOR SERVICE
I
I
I
I
I
I
I_] DU_(NOTE3)
NOTES:
1, Dimensionsare in inches.Dimensions in[ ]areinmillimeters,
2. _ Diroctionof airflow.
3. _erant, d_in, Bnd power conneofionsrubybe _de rear,leftsideor
rightside.
4. Refrigerantismetered by capilla_tubesintheoutdoorunit.Insulatebeth
refrigerantlines.
5. Clearancesof 3½ on topof and tothe leftofthefancoilunitareabsolute
minLmu_. Clea_nc_=sof10" arerecommended.
6. Do not inset{a trapincondensatedrainline,Drainisinternallytrapped,
Fig. 4 -- 40QN Dimensional Drawing
012 )NIT OUTLI_ 012 MOLWWTI_BR:T 7
6 30 24 O0 _ O_
_ 2_ _4] DIA(NOTE 3)
UNIT WEIGHT A B C
4OGNI Lb I Kgl i.. I mml in. I mmlie. I mm
00,118,I°8133401=0011102]28016201160012 24.2 11.0 36.61 930 11.81 300 7.28 185
8
Table 5 -- System Piston Guide and
Refrigerant Charges
35" MAX (FOR COOLING ONLY AND
HEAT PUMP SYSTEMS)
UNIT INDOOR
Indoor Outdoor SIZE
40QNB009 38AN009 Capillary Tube
40QNB012 38AN012 Capillary Tube
40QNEO09 38BK009 321"
40QNH012 38BK012 421"
*Charge is based on25 f_of interconnectingtubing.Charge may need
to be added for longer tubing runs or when used with certain fan
coils. Check unit nameplate for required charge. This is a total sys-
tem charge.
tNon-serviceable Aeroquip piston.
POSSIBLE PIPING DIRECTIONS
RIGHT
SIDE
BoTroM KNOCKOUT
PISTON
PREPUNGHED HOLES
OUTDOOR
PISTON
SIZE
Capillary Tube
Capillary Tube
30t
42"_
REQUIRED
SYSTEM
CHARGE
(Ib)*
1.50
180
150
2.00
LEFT
SIDE
KNOCKOUT
"_1_ UNIT
30"
INDOOR ELEVATION INDOOR
UNIT IT
MAX
/t/Hi--till/I/I////// // H//////H
OUTDOOR
UNIT
GROUND-LEVEL ROOFTOP
INSTALLATION INSTALLATION
Fig, 6 -- Maximum System Line Lengths
Step 4 -- Mount Outdoor Section
1. If outdoor section is to be installed at ground level, mount
on a solid, level support pad one in. longer and one in.
wider than the outdoor section dimensions.
2.
Provide sufficient clearance for airflow, wiring, refriger-
ant piping, service and maintenance. Provide a minimum
clearance of 2 ft from obstructions in front of outdoor
section, 2 ft on outdoor coil side, and 2_A ft on electrical
and piping side. If more than one outdoor section is in-
stalled, provide aminimum clearance of 2 ft between sec-
tions. Position outdoor section so that water or ice from
roof cannot fall directly on unit.
NOTE: The outdoor section can be installed higher than,
lower than, or level with the elevation of the indoor
section. If outdoor section is mounted higher than the in-
door section, the vertical distance between the 2 units
should not exceed 30 i_. If the outdoor section is installed
lower than indoor section, the vertical distance between
the units should not exceed 16 ft. See table below:
FOR LEFT
SIDE PIPING
FOR RIGHT
SIDE PIPING
FOR
BOTi-OM/REAR
PIPING
Fig. 5 -- Fan Coil Unit Refrigerant Piping
Jlllll!_ilj=*:'=_: ! " _--H "-'-'': *="0_: : : : " : ::::=:l_
FAN COIL
UNIT BOTI OM
BACK VIEW
\
MAXIMUM DISTANCE BETWEEN OUTDOOR UNITS
Outdoor Section Higher 30 Ft Maximum
Than Indoor Section (Vertical)
Outdoor Section Lower 16 Ft Maximum
Than Indoor Section (Vertical)
NOTE: Maximum system piping length between indoor and outdoor
units is 35 ft.
TOP HOLES
FRONT VIEW
/
Fig. 7 -- Fan Coil Unit Bracket Mounting (Size 009 Shown)