24ABC6
Baset16 Air Conditioner
with Puronr Refrigerant
Wiring Diagram
*CHS
BLK
or
RED
RED or B LK
208/230 1Ø
POWER
SUPPLY
(NOTE #14)
YEL/PNK
YEL/ BLU
Y
INDOOR THERMOSTAT (NOTE #6)
*CH
BLK
(NOTE #9)
L1
L2
EQUIP
GND
YEL
YEL/ BLU
*LPS
YEL/PNK
*LLS
BLK
R
G
CONDENSING UNIT CHARGING INSTRUCTIONS
For use with units using R-410A refrigerant
REQUIRED LIQUID LINE TEMPERATURE
Liquid Pressure
at Service
Valve (psig)
251
259
266
274
283
291
299
308
317
326
335
345
354
364
374
384
395
406
416
427
439
450
462
474
Required Subcooling
Temperature (ºF)
681012 14
76 74 72 70 68
78
78 76 74 72 70
80
80 78 76 74 72
82
82 80 78 76 74
84
84 82 80 78 76
86
86 84 82 80 78
88
88 86 84 82 80
90
90 88 86 84 82
92
92 90 88 86 84
94
94 92 90 88 86
96
96 94 92 90 88
98
98 96 94 92 90
100
100 98 96 94 92
102
102 100 98 96 94
104
104 102 100 98 96
106
106 104 102 100 98
108
108 106 1 04 102 100
110
110 108 1 06 104 102
112
112 110 1 08 106 104
114
114 112 110 108 106
116
118
116 114 112 110 108
118 116 114 112 110
120
120 118 116 114 112
122
122 120 118 116 114
124
CONNECTION DIAGRAM
BLK
*DTS
COMP
S
BLK
C
21
23
YEL
YEL
OFM
BLK
BLU/PNK
BLK
R
INDOOR BLOWER MOTOR
CONT
11
23
BLK
BLK
16
BLK
BLU
BLU
BRN
BLU
t
P
CA
H
C
F
BLK
*HPS
1. Only use sub cooling charging method
when OD ambient is greater than 70ºF
and less than 100ºF, indoor temp is
greater than 70ºF and less than 80ºF, and
line set is less than 80 ft.
2. Operate unit a minimum of 15 minutes before
checking the charge.
3. Measure liquid service valve pressure by
attaching an accurate gauge to the
service port.
4. Measure the liquid line temperature by
attaching an accurate thermistor type or
electronic thermometer to the liquid line
near the outdoor coil.
5. Refer to unit rating plate for required
subcooling temperature.
6. Find the point where the required subcooling
temperature intersects the measured liquid
service valve pressure.
7. To obtain the required subcooling temperature
at specific liquid line pressure, add refrigerant
if liquid line temperature is higher than indicated.
When adding refrigerant, charge in liquid form
using a flow restricting device into suction
service port. Recover refrigerant if temperature
is lower. Allow a tolerance of +/- 3ºF.
+
YEL
YEL
BLU/PNK
BRN/YEL
CHARGING PROCEDURE
*ST
BRN
1
(NOTE #8)
BRN/YEL
VIO
LOGIC
T1 T3
EXTERNAL
POWER
SUPPLY
(NOTE #3)
24 V
2
5
*SR
T2
*CTD
C
R
*SC
COOLING ONLY
EQUIP
GND
Y
G
R
INDOOR
THERMOSTAT
*CHS
NOTES:
1. Symbols are electrical representation only.
2. Compressor and fan motor furnished with inherent thermal protection.
3. To be wired in accordance with National Electric N.E.C. and local codes.
4. N.E.C. class 2, 24 V circuit, min. 40 VA required, 60 VA on units installed with LLS.
5. Use copper conductors only. Use conductors suitable for at least 75ºC (167ºF).
6. Connection for typical cooling only thermostat. For other arrangements see installation instructions.
7. If indoor section has a transformer with a grounded secondary, connect the grounded
side to the BRN/YEL lead.
8. When start relay and start capacitor are installed, start thermistor is not used.
9. CH not used on all units.
10. If any of the original wire, as supplied must be replaced, use the same or equivalent wire.
11. Check all electrical connections inside control box for tightness.
12. Do not attempt to operate unit until service valves have been opened.
13. Do not rapid cycle compressor. Compressor must be off 3 minutes to allow pressures to equalize
between high and low side before starting.
14. Wire not present if HPS, LPS or CTD are used.
SCHEMATIC DIAGRAM (LADDER FORM)
L1
CONT
11
21
2
5
1
*SR
*CH
*LPS
OFM
(NOTE #14)
*DTS
*LLS
EXTERNAL POWER SUPPLY 2 4 V
*SC
*HPS
R
C
T1 T3
IFR
COMP
S
H
C
F
C
R
LOGIC
* CTD
CAP
*ST
t
+
T2
CONT
23
CONT
L2
23
LEGEND
FACTORY POWER WIRING
FACTORY CONTROL WIRING
FIELD CONTROL WIRING
FIELD POWER WIRING
COMPONENT CONNECTION
FIELD SPLICE
JUNCTION
CONT
COMP
CONTACTOR
CAPACITOR (DUAL RUN)
CAP
CRANKCASE HEATER
*CH
CRANKCASE HEATER SWITCH
*CHS
COMPRESSOR
COMPRESSOR TIME DELAY
*CTD
DISCHARGE TEMP SWITCH
*DTS
HIGH PRESSURE SWITCH
*HPS
INDOOR FAN RELAY
IFR
LIQ LINE SOLENOID VALVE
*LLS
LOW PRESSURE SWITCH
*LPS
OUTDOOR FAN MOTOR
OFM
START CAPICATOR
*SC
START RELAY
*SR
START THERMISTOR
*ST
* MAY BE FACTORY INSTALLED
CAUTION
1. Compressor damage may occur if system is over charged.
2. This unit is factory charged with R-410A in accordance with
the amount shown on the rating plate. The charge is
adequate for most systems using matched coils and tubing
not over 15 feet long. Check refrigerant charge for maximum
efficiency. See Product Data Literature for required Indoor
air Flow Rates and for use of line lengths over 15 feet.
3. Relieve pressure and recover all refrigerant before system
repair or final disposal. Use all service ports and open all
flow-control devices, including solenoid valves.
4. Never vent refrigerant to atmosphere. Use approved
recovery equipment.
330440-101 REV. F
Fig. 1 – Wiring Diagram — Model sizes 1--1/2 -- 5 tons, 208/230--1

Copyright 2010 Carrier Corp. S 7310 W. Morris St. S Indianapolis, IN 46231
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
Printed in U.S.A. Edition Date: 0 1/10
Catalog No: 24ABC6--- 1W
Replaces: New