Carrier 59TN6A080V14, 59TN6A060V17, 59TN6A080V21, 59TN6A080V20, 59TN6A100V21 Product Data

...
Page 1
59TN6A InfinityR Two---Stage, V ariable Speed 4 --- W a y M u lt i p o i s e Condensing Gas Furnace Series 100
Product Data
A11263
STANDARD FEATURES
S InfinityR System; compatible with single-- and multiple--zone
Infinity systems.
S All sizes meet ENERGY STARR Version 4.0 criteria for gas
furnaces: 95+ AFUE; AMACF electrical rating; 2% or less cabinet airflow leakage.
S Quiet operation. Compare for yourself at HVACpartners.com. S Ideal height 35--in. (889 mm) cabinet: short enough for taller
coils, but still allows enough room for service.
S Infinity Features—match with the Infinity Control for Infinity
System benefits.
S Integral part of the Ideal Humidity SystemR Technology.
S Silicon Nitride Power Heat™ Hot Surface Igniter. S SmartEvap™ technology helps control humidity levels in the
home when used with a compatible humidity control system.
S ComfortFan™ technology allows control of continuous fan
speed from a compatible thermostat.
S External Media Filter Cabinet included. S 4--way multipoise design for upflow, downflow or horizontal
installation, with unique vent elbow and optional through-­the--cabinet downflow venting capability.
S Variable--Speed blower motor, two--speed inducer motor, and
two--stage gas valve.
S Self--diagnostics and extended diagnostic data through the
Advanced Product Monitor (APM) accessory or Infinity User Interface.
S Adjustable blower speed for cooling, continuous fan, and
dehumidification.
S Aluminized--steel primary heat exchanger. S Stainless--steel condensing secondary heat exchanger. S Propane convertible(See Accessory list). S Factory--configured ready for upflow applications. S Fully--insulated casing including blower section. S Convenient Air Purifier and Humidifier connections. S Direct--vent/sealed combustion, single--pipe venting or
ventilated combustion air.
S Installation flexibility: (sidewall or vertical vent). S Residential installations may be eligible for consumer financing
through the Retail Credit Program.
S Certified to leak 2% or less of nominal air conditioning CFM
delivered when pressurized to 1--in. water column with all present air inlets, air outlets, and condensate drain port(s) sealed.
LIMITED WARRANTY*
S 10 year parts and lifetime heat exchanger limited warranty to the
original purchaser upon timely registration.
S Limited warranty period is five years for parts and twenty years
for the heat exchanger if not registered within 90 days of installation.{
* For owner occupied, residential applications.
{Jurisdictions where warranty benefits cannot be conditioned on registra-
tion will receive registered limited warranty benefits.
Always Ask For
Use of the AHRI Certified TM Mark indicates a manufacturer’s participation in the program. For verification of certification for individual products,
CERTIFIED
go to www.ahridirectory.org.
1
Page 2
CASING
DIMENSIONS
SAP ORDERING
NO.
59TN6A060V17--14 35 30 17.5 58,000 38,000 96.3% 855 1075 0.12 510 - 1335 1/2 16 140 59TN6A080V17--14 35 30 17.5 78,000 50,000 96.2% 1060 1500 0.15 490 - 1375 1/2 16 150 59TN6A080V21--20 35 30 21.0 78,000 51,000 96.7% 1095 1345 0.15 750 - 1945 1 20 155 59TN6A100V21--22 35 30 21.0 98,000 63,000 96.1% 1385 1575 0.20 715 - 2160 1 20 165 59TN6A120V24--22 35 30 24.5 117,000 76,000 96.7% 1640 1820 0.20 885 - 2185 1 24 189
† Capacity in accordance with DOE test procedures. See rating plate.
‡ Heating CFM at factory default blower motor heating settings.
ESP --- External Static Pressure
(IN.)
H D W High Low AFUE
FEATURES AND BENEFITS
Comfort Heat TechnologyR feature — This feature with
Adaptive Control is a proprietary function that promotes homeowner comfort through two stages of heating. This Carrier furnace offers a patented algorithm that continually monitors and adjusts furnace operation by looking at both current and past conditions to determine the most effective stage of heating and the amount of time to run each stage, every cycle.
Ideal Humidity SystemR Technology — The Ideal Humidity system actively controls both temperature and humidity in the
59TN6A
home to provide the best comfort all year long. Other systems depend on heating or cooling demand to manage the moisture in the air. But, Ideal Humidity gives the homeowner the right amount of humidity day and night, even in mild weather. No other manufacturer can do this! Ideal Humidity saves energy, too. By keeping humidity under control, the homeowner can set their thermostat lower to stay comfortable and save energy.
SmartEvapt Technology — When paired with a compatible thermostat, this dehumidification feature overrides the cooling blower off-delay when there is a call for dehumidification. By deactivating the blower off-delay, SmartEvap technology prevents condensate that remains on the coil after a dehumidification cycle from re-humidifying throughout the home. This results in reduced humidity and a more comfortable indoor environment for the homeowner.
Unlike competitive systems, SmartEvap technology only overrides the cooling blower off--delay when humidity control is needed. Once humidity is back in control, SmartEvap re-enables the energy-saving cooling blower off-delay.
ComfortFant Technology — Sometimes the constant fan setting on a standard furnace system can actually reduce homeowner comfort by providing too much or too little air! Comfort Fan technology improves comfort all year long by allowing the homeowner to select the continuous fan speed of their choice using a compatible thermostat.
HYBRID HEATR Dual Fuel System — This system can provide more control over your monthly energy bills by automatically selecting the most economical method of heating. With HYBRID HEAT components, our system automatically switches between the gas furnace and the electric heat pump as outside temperatures change to maintain greater efficiency and comfort than with any traditional single-source heating system. The heat pump also delivers high-efficiency cooling in the summer.
Power Heatt Igniter — Carrier’s unique SiN igniter is not only physically robust but it is also electrically robust. It is capable of running at line voltage and does not require complex voltage regulators as do other brands. This unique feature further enhances the gas furnace reliability and continues Carrier’s tradition of technology leadership and innovation in providing a reliable and durable product.
Full-Featured, Communicating, Variable Speed Motors —Our ECMs (Electronically Commutated Motors) provide variable-speed operation to optimize comfort levels in the home year round; features such as passive/active dehumidification, ramping profiles,
RATED HEATING
OUTPUT
† (BTUH)
HEATING AIRFLOW
CFM‡
(Low
Heating)
MEDIA
CABINET
SUPPLIED
(IN.)
CFM
(High
Heating)
Rated
High Heating
ESP
COOLING
CFM @ 0.5
ESP
MOTOR HP (VARIABLE
SPEED)
match enhancements to increase the effective SEER of select Carrier air conditioner or heat pump system, and feature the highest efficiency of all indoor fan motors.
Reliable Heat Exchanger Design — The aluminized steel, clamshell primary heat exchanger was re--engineered to achieve greater efficiency out of a smaller size. The first two passes of the heat exchanger are based on the current 80% product, a design with more than ten years of field-proven performance and success. These innovations, paired with the continuation of a crimped, no-weld seam create an efficient, robust design for this essential component.
The condensing heat exchanger, a stainless steel fin and tube design, is positioned in the furnace to extract additional heat. Stainless steel coupling box componentry between heat exchangers has exceptional corrosion resistance in both natural gas and propane applications.
Media Filter Cabinet — Enhanced indoor air quality in the home is made easier with our media filter cabinet—a standard accessory on all deluxe furnaces. When installed as a part of the system, this cabinet allows for easy and convenient addition of a Carrier high efficiency air filter.
4-Way Multipoise Design — One model for all applications – there is no need to stock special downflow or horizontal models when one unit will do it all. The new heat exchanger design allows these units to achieve the certified AFUE in all positions.
Direct or Single-pipe Venting, or Optional Ventilated Combustion Air — This furnace can be installed as a 2-pipe
(Direct Vent) furnace, in an optional ventilated combustion air application, or in single-pipe, non-direct vent applications. This provides added flexibility to meet diverse installation needs.
Sealed Combustion System — This furnace brings in combustion air from outside the furnace, which results in especially quiet operation. By sealing the entire combustion vestibule, the entire furnace can be made quieter, not just the burners.
Insulated Casing — Foil-faced insulation in the heat exchanger section of the casing minimizes heat loss. The acoustical insulation in the blower compartment reduces air and motor noise for quiet operation.
Monoport Burners — The burners are specially designed and finely tuned for smooth, quiet combustion and economical operation.
Bottom Closure — Factory-installed for side return; easily removable for bottom return. The multi-use bottom closure can also serve for roll-out protection in horizontal applications, and act as the bottom closure for the optional return air base accessory.
Blower Access Panel Switch — Automatically shuts off 115-v power to furnace whenever blower access panel is opened.
Quality Registration — Our furnaces are engineered and manufactured under an ISO 9001 registered quality system.
Certifications — This furnace is CSA (AGA and CGA) design certified for use with natural and propane gases. The furnace is factory--shipped for use with natural gas. A CSA listed gas conversion kit is required to convert furnace for use with propane gas. The efficiency is GAMA efficiency rating certified. This furnace meets California Air Quality Management District emission requirements.
constant air flow and quiet operation. They can provide cooling
APPROX. SHIP WT.
(LB)
2
Page 3
SPECIFICATIONS
Heating Capacity and Efficiency 060-14 080-14 080-20 100-22 120-22
High
Input
Output
Efficiency AFUE % (ICS) 96.3 96.2 96.7 96.1 96.7
Certified Temperature Rise Range ºF (ºC)
Airflow Capacity and Blower Data 060-14 080-14 080-20 100-22 120-22
Certified External Static Pressure (in. w.c.)
Airflow Delivery @ Rated ESP (CFM)
Cooling Capacity (tons) @ 400, 350 CFM/ton
Direct-Drive Motor Type Electronically Commutated Motor (ECM) Direct-Drive Motor HP 1/2 1/2 1 1 1 Motor Full Load Amps 7.7 7.7 12.8 12.8 12.8 RPM Range 300 - 1300 Speed Selections Variable (Communicating) Blower Wheel Dia x Width in. 11 x 8 11 x 8 11x10 11 x 10 11 x 11
Air Filtration System
Filter Used for Certified Watt Data
Heat Low
Heat High
Heat Low
Heat
(BTUH) 60,000 80,000 80,000 100,000 120,000
(BTUH) 39,000 52,000 52,000 65,000 78,000
(BTUH) 58,000 78,000 78,000 98,000 117,000
(BTUH) 38,000 50,000 51,000 63,000 76,000
High Heat
Low Heat
Heating 0.12 0.15 0.15 0.20 0.20 Cooling 0.5 0.5 0.5 0.5 0.5
High Heat 1075 1500 1345 1575 1820
Low Heat 855 1060 1095 1385 1640
Cooling 1335 1375 1945 2160 2185 400 CFM/ton 3 3.5 4.5 5 5.5 350 CFM/ton 3.5 4 5.5 6 6
35 - 65
(19 - 36)
30 - 60
(17 - 33)
KGAWF1306UFR KGAWF1406UFR
40 - 70
(22 - 39)
30 - 60
(17 - 33)
Factory Supplied Media Cabinet
40 - 70
(22 - 39)
30 - 60
(17 - 33)
Field Supplied Filter
45 - 75
(25 - 42)
30 - 60
(17 - 33)
45 - 75
(25 - 42)
30 - 60
(17 - 33)
KGAWF1506UFR
59TN6A
Electrical Data 060-14 080-14 080-20 100-22 120-22
Input Voltage
Operating Voltage Range Min-Max 104-127 Maximum Input Amps Amps 8.5 8.5 13.6 13.7 13.7 Unit Ampacity Amps 11.5 11.5 17.9 18.0 18.0 Minimum Wire Size AWG 14 14 12 12 12
Maximum Wire Length @ Minimum Wire Size
Maximum Fuse/Ckt Bkr (Time-Delay Type Recommen­ded)
Transformer Capacity (24vac output)
External Control Power Available
Controls 060-14 080-14 080-20 100-22 120-22
Gas Connection Size 1/2" - NPT Burners (Monoport) 3 4 4 5 6 Gas Valve (Redundant)
Minimum Inlet Gas pressure (in. wc) 4.5
Maximum Inlet Gas pressure (in. wc) 13.6 Gas Conversion Kit - Natural to Propane KGANP5201VSP Gas Conversion Kit - Propane to Natural KGAPN4401VSP Manufactured (Mobile) Home Kit not approved for MH use Ignition Device Silicon Nitride Limit Control 180 170 200 180 160 Heating Blower Control (Heating Off-Delay) Adjustable: 90, 120, 150, 180 seconds Cooling Blower Control (Time Delay Relay) 90 seconds Communication System Infinity; Infinity Zoning Thermostat Connections R, W/W1, W2 Y/Y2, Y1, G, Com 24V, DHUM Accessory Connections EAC (115vac); HUM (24vac); 1-stg AC (via Y/Y2)
Volts-Hertz-Phase 115-60-1
Feet 32 32 32 31 31
(M) (9.8) (9.8) (9.8) (9.4) (9.4)
Amps 15 15 20 20 20
40 VA
Heating 24.3 VA Cooling 34.6 VA
Manufacturer White Rogers
3
Page 4
MODEL NUMBER NOMENCLATURE
1 - 2
Family
59
Family
3
Htg. Stages Tier
T
S - Single Stage T - Two Stage M - Modulating
4
N
C - Comfort P - Performance N - Infinity
5
Effy.
6
0 --- 90 AFUE 3 --- 93 AFUE 5 --- 95 AFUE 6 --- 96 AFUE 7 --- 97 AFUE
6
Major Series
A
Major Series
Not all familes have these models.
7 - 9
Htg. Cap.
060
040=40,000 BTU 060=60,000 BTU 080=80,000 BTU 100=100,000 BTU 120=120,000 BTU
10
Motor
V
S - Standard E - Energy Efficient V - Variable Speed
11 - 12
Width
17
14 - 14.2” 17 - 17.5” 21 - 21.0” 24 - 24.5”
Voltage
Voltage
13
--
14
Minor Series
--
Minor Series
15 - 16
Airflow
14
08 - 800 CFM 10 - 1000 CFM 12 - 1200 CFM 14 - 1400 CFM 16 - 1600 CFM 18 - 1800 CFM 20 - 2000 CFM 22 - 2200 CFM
A11160
FURNACE COMPONENTS
HOT SURFACE
59TN6A
FLAME SENSOR
MANUAL RESET ROLLOUT SWITCH
GAS VALVE
OPERATING INSTRUCTIONS NOT SHOWN (LOCATED ON MAIN FURNACE DOOR, SEE OPERATING INSTRUCTIONS INSIDE DOOR FIGURE).
ELECTRICAL JUNCTION
BOX (IF REQUIRED,
LOCATION MAY VARY)
GAS BURNER
IGNITER
MANUAL RESET ROLLOUT SWITCH
MAIN LIMIT SWITCH
(BEHIND GAS VALVE)
INDUCER MOTOR ASSEMBLY
BLOWER DOOR SAFETY SWITCH
FURNACE CONTROL BOARD
RATING PLATE NOT SHOWN
(LOCATED ON BLOWER DOOR)
REPRESENTATIVE DRAWING ONLY, SOME MODELS MAY VARY IN APPEARANCE.
MEDIA CABINET
BLOWER AND MOTOR
CAPACITOR/ POWER CHOKE (IF USED)
A11408
4
Page 5
Vent Kit - Through the Cabinet
Venting Accessories
Vent Terminal - Concentric
Vent Terminal Bracket
ACCESSORIES
2-in.
3-in.
2-in.
3-in.
Part Number Used With Notes
KGADC0101BVC All 1 KGAVT0701CVT See Venting Tables 1 KGAVT0801CVT See Venting Tables 1 KGAVT0101BRA See Venting Tables 1, 2 KGAVT0201BRA See Venting Tables 1, 2
Freeze Protect Kit - Heat Patch for Drain Trap
Condensate Drainage Accessories
Freeze Protect Kit - Heat Tape
CPVC to PVC Drain Adapter - 1/2-in. CPVC to 3/4-in. PVC
Horizontal Trap Grommet for Direct Vent Applications
Condensate Neutralizer Kit
Ductwork Adapter Accessories
Furnace Base Kit for Combustible Floors
Coil Adapters Kits - Painted
Return Air Base (Upflow applications) - Painted
IAQ Device Duct Adapters (side return) - Painted
Gas Conversion Accessories
Gas Conversion Kit - Nat to LP; Var-spd Products Gas Conversion Kit - LP to Nat; Var-spd Products
Gas Orifice Kit
No Offset Single Offsett Double Offset
14.2-in. wide
17.5-in. wide 21-in. wide
24.5-in. wide
20-in IAQ to 16-in side return 24-in IAQ to 16-in side return
#42 Natural Gas #43 Natural Gas #44 Natural Gas #45 Natural Gas #46 Natural Gas #47 Natural Gas #48 Natural Gas
#54 LP #55 LP #56 LP
1.25 mm LP
1.30 mm LP
Part Number Used With Notes
KGAHT0201CFP All 7
KGACK0101HCK All DV Horizontal -
P908-0001 All 6
Part Number Used With Notes
KGARP0301B14 14.2" W ide Furnaces 7 KGARP0301B17 17.5" W ide Furnaces 7 KGARP0301B21 21" W ide Furnaces 7
KGARP0301B24 24.5" W ide Furnaces 7 KGAAD0101MEC 20"x25" IAQ Devices 7 KGAAD0201MEC 24"x25" IAQ Devices 7
Part Number Used With Notes
KGAHA0150N42 All 4, 6
KGAHA0250N43 All 4, 6
KGAHA0350N44 All 4
KGAHA0450N45 All 4
KGAHA0550N46 All 4
KGAHA1550N47 All 4
KGAHA1650N48 All 4
KGAHA0650P54 All 4, 6
KGAHA0750P55 All 4
KGAHA0850P56 All 4, 6
KGAHA5750125 All 4, 6
KGAHA5750130 All 4, 6
-llAPFC1010THAGK
-llACVP0110DAAGK
-llALLA1020BSAGK
-llALLA1010ADAGK
-llALLA1020ADAGK
-llALLA1030ADAGK
59TN6A
-llAPSV1025PNAGK
-llAPSV1044NPAGK
Control Accessories
ECM Motor Simulator Kit
Advanced Product Monitor - APM
Infinity Control User Interface
Infinity Control Zoning User Interface
IAQ Accessories
Filter Pack (6 pack) - W ashable
EZ-Flex Filter
EZ-Flex Filter with End Caps
Cartridge Media Filter
Carrier Infinity Air Purifier
Carrier Infinity Air Purifier Replacement Filter
Carrier Performance Air Purifier
Carrier Performance Air Purifier Replacement Filter
16 x 25 x 1 24 x 25 x 1
16-in. 20-in. 24-in. 16-in. 20-in. 24-in. 16-in. 20-in.
24.in. 16 x 25 20 x 25 16 x 25 20 x 25 16 x 25 20 x 25 16 x 25 20 x 25
Part Number Used With Notes
Part Number Used With Notes
KGAWF1306UFR All 5 KGAWF1506UFR All 5
EXPXXFIL0016 EZXCAB--1016 3, 5 EXPXXFIL0020 EZXCAB--1020 3, 5
EXPXXFIL0024 EZXCAB--1024 3, 5 EXPXXUNV0016 EZXCAB--1016 3, 5 EXPXXUNV0020 EZXCAB--1020 3, 5 EXPXXUNV0024 EZXCAB--1024 3, 5
FILXXCAR0016 FILCABXL1016 3, 5
FILXXCAR0020 FILCABXL1020 3, 5
FILXXCAR0024 FILCABXL2024 3, 5 GAPAAXCC1625 Upto1600CFM 5 GAPAAXCC2025 Upto2000CFM 5 GAPCCCAR1625 GAPAAXCC1625-A08 5 GAPCCCAR2025 GAPAAXCC2025-A08 5
PGAPXX1625 Upto1600CFM 5,7
PGAPXX2025 Upto2000CFM 5,7 PGAPAXXCAR1625 GAPAAXCC1625 5, 7 PGAPAXXCAR2025 GAPAAXCC2025 5, 7
Notes:
1. CSA requires that a termination kit be used. See latest PD for pipe and kit size selection. The qualified installer or agency must use only
factory-authorized kits when modifying these furnaces.
2. Not for use with Concentric Vent Termination Kits.
3. Last 2 digits of Part Number indicate filter size.
4. Last 2 digits of Part Number indicate orifice size.
5. Choose IAQ/filter assembly appropriate for the designed system airflow and static pressure. Use optional IAQ Device Duct Adapters as required.
6. Available from Replacement Components group.
7. Kit coming soon. Expected availability 2Q2012.
-llASMF1030DSAGK
-llAMPA1030DSAGK
-llAV-10DIUCCXTSYS
-llAV-10ZIUCCXTSYS
5
Page 6
AIR DELIVERY
COOLING
4
AND HEATING AIR DELIVERY - CFM (Bottom Return5With Filter)
(SW1-5 and SW4-3 set to OFF, except as indicated. See notes 1 and 2.)
Unit Size Clg/CF Switch Settings External Static Pressure (ESP)
SWx-3 SWx-2 SWx-1 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
060-14
Clg Default: OFF OFF OFF 1060 1070 1080 1080 1075 1065 1050 1035 1025 1010
CF Default: OFF OFF OFF 545 530 520 525 510 Seenote4
OFF OFF ON 545 530 520 525 510 Seenote4
Cooling (SW2)
Cont Fan
(SW3)
OFF ON OFF 710 710 710 695 690 Seenote4 OFF ON ON 875 880 890 895 895 890 885 880 870 855
ON OFF OFF 1060 1070 1080 1080 1075 1065 1050 1035 1025 1010 ON OFF ON 1235 1240 1250 1255 1255 1250 1230 1190 1155 1115 ON ON OFF 1235 1240 1250 1255 1255 1250 1230 1190 1155 1115 ON ON ON 1235 1240 1250 1255 1255 1250 1230 1190 1155 1115
Clg SW2: Maximum Clg Airflow
59TN6A
Heating
(SW1)
Unit Size Clg/CF Switch Settings External Static Pressure (ESP)
080-14
Clg Default: OFF OFF OFF 1055 1065 1080 1075 1065 1050 1045 1035 1025 1005
CF Default: OFF OFF OFF 520 505 505 495 490 Seenote4
Cooling (SW2)
Cont Fan
(SW3)
Clg SW2: Maximum Clg Airflow
Heating
(SW1)
Unit Size Clg/CF Switch Settings External Static Pressure (ESP)
080-20
Clg Default: OFF OFF OFF 1745 1755 1755 1760 1755 1750 1745 1725 1705 1685
High Heat Airflow
Low Heat Airflow
SWx-3 SWx-2 SWx-1 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
OFF OFF ON 520 505 505 495 490 Seenote4 OFF ON OFF 665 685 680 660 665 Seenote4 OFF ON ON 885 895 905 900 900 895 885 875 860 845
ON OFF OFF 1055 1065 1080 1075 1065 1050 1045 1035 1025 1005 ON OFF ON 1245 1245 1255 1255 1260 1255 1250 1235 1220 1185 ON ON OFF 1245 1245 1255 1255 1260 1255 1250 1235 1220 1185 ON ON ON 1245 1245 1255 1255 1260 1255 1250 1235 1220 1185
High Heat Airflow
Low Heat Airflow
SWx-3 SWx-2 SWx-1 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
2
3
3
2
3
3
1425 1425 1405 1370 1335 1300 1260 1225 1190 1155
1075 1085 1095 1095 1090 1080 1065 1050 1035 1020
855 855 860 870 870 865 860 855 845 785
1520 1485 1450 1415 1375 1335 1300 1265 1225 1190
1520 1485 1450 1415 1375 1335 1300 1265 1225 1190 1055 1065 1080 1075 1065 1050 1045 1035 1025 1005
CF Default: OFF OFF OFF 700 710 750 725 750 Seenote4
OFF OFF ON 700 710 750 725 750 Seenote4 OFF ON OFF 830 860 870 890 960 Seenote4
Cooling (SW2)
Cont Fan
(SW3)
Clg SW2: Maximum Clg Airflow
Heating
(SW1)
OFF ON ON 1045 1045 1060 1070 1070 1070 1095 1090 1080 1070
ON OFF OFF 1215 1220 1245 1240 1235 1235 1225 1220 1235 1235 ON OFF ON 1370 1370 1390 1390 1400 1395 1400 1390 1390 1385 ON ON OFF 1745 1755 1755 1760 1755 1750 1745 1725 1705 1685 ON ON ON 1745 1755 1755 1760 1755 1750 1745 1725 1705 1685
High Heat Airflow
Low Heat Airflow
3
3
See notes at end of table.
2
1920 1920 1945 1945 1945 1960 1950 1940 1915 1900
1340 1355 1370 1385 1380 1385 1400 1400 1385 1380 1080 1115 1115 1120 1125 1135 1125 1120 1125 1110
6
Page 7
AIR DELIVERY (CONTINUED)
COOLING
4
AND HEATING AIR DELIVERY - CFM (Bottom Return5With Filter)
(SW1-5 and SW4-3 set to OFF, except as indicated. See notes 1 and 2.)
Unit Size Clg/CF Switch Settings External Static Pressure (ESP)
SWx-3 SWx-2 SWx-1 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
100-22
Clg Default: OFF OFF OFF 1820 1825 1840 1845 1840 1835 1825 1805 1780 1770
CF Default: OFF OFF OFF 750 740 745 730 715 Seenote4
OFF OFF ON 750 740 745 730 715 Seenote4 OFF ON OFF 900 900 915 910 905 Seenote4
Cooling (SW2)
Cont Fan
(SW3)
OFF ON ON 1070 1075 1095 1095 1090 1085 1095 1080 1065 1070
ON OFF OFF 1280 1285 1305 1305 1310 1305 1295 1300 1290 1285 ON OFF ON 1440 1445 1465 1465 1470 1485 1480 1485 1475 1460 ON ON OFF 1820 1825 1840 1845 1840 1835 1825 1805 1780 1770 ON ON ON 2135 2140 2140 2135 2140 2130 2115 2100 2070 2015
Clg SW2: Maximum Clg Airflow
Heating
(SW1)
High Heat Airflow
Low Heat Airflow
2
3
3
2160 2165 2175 2170 2160 2150 2135 2120 2065 2020
1570 1575 1595 1595 1600 1605 1600 1600 1590 1575 1365 1385 1395 1395 1395 1400 1400 1405 1395 1380
Unit Size Clg/CF Switch Settings External Static Pressure (ESP)
SWx-3 SWx-2 SWx-1 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
120-22
Clg Default: OFF OFF OFF 1850 1855 1860 1855 1850 1830 1805 1775 1750 1730
CF Default: OFF OFF OFF 930 925 915 900 885 Seenote4
OFF OFF ON 765 745 740 705 680 Seenote4
Cooling (SW2)
Cont Fan
(SW3)
OFF ON OFF 930 925 915 900 885 Seenote4 OFF ON ON 1095 1100 1110 1105 1085 Seenote4
ON OFF OFF 1265 1255 1265 1280 1275 1285 1270 1260 1250 1230 ON OFF ON 1465 1455 1470 1465 1465 1470 1455 1450 1435 1415 ON ON OFF 1850 1855 1860 1855 1850 1830 1805 1775 1750 1730 ON ON ON 2200 2200 2200 2190 2185 2170 2145 2085 1990 1890
Clg SW2: Maximum Clg Airflow
Heating
(SW1)
1. Nominal 350 CFM/ton cooling airflow is delivered with SW1-5 and SW4-3set to OFF.
High Heat Airflow
Low Heat Airflow
2
3
3
2200 2200 2200 2190 2185 2170 2145 2085 1990 1890
1815 1820 1825 1820 1815 1795 1775 1745 1720 1700 1640 1640 1645 1650 1645 1645 1630 1620 1600 1580
Set SW1-5 to ON for nominal 400 CFM/ton (+15% airflow). Set SW4-3 to ON for nominal 325 CFM/ton (-7% airflow). Set both SW1-5 and SW4-3 to ON for nominal 370 CFM/ton (+7% airflow).
The above adjustments in airflow are subject to motor horsepower range/capacity.
2. Maximum cooling airflow is achieved when switches SW2-1, SW2-2, SW2-3 and SW1-5 are set to ON, and SW4-3 is set to OFF.
3. All heating CFM's are when low heat rise adjustment switch (SW1-3) and comfort/efficiency adjustment switch (SW1-4) are both set to OFF.
4. Ductwork must be sized for high-heating CFM within the operational range of ESP. Operation within the blank areas of the chart is not re-
commended because high-heat operation will be above 1.0 ESP.
5. All airflows on 21" (533 mm) casing size furnaces are 5% less on side return only installations.
6. Side returns for 24.5" (622 mm) casing sizes require two sides, or side and bottom, to allow sufficient airflow at the return of the furnace.
7. Airflows over 1800 CFM require bottom return, two-side return, or bottom and side return; otherwise excessive watt draws may result. A
minimum filter size of 20" x 25" (508 x 635 mm) is required.
59TN6A
7
Page 8
MAXIMUM EQUIVALENT VENT LENGTH -- FT. (M)
NOTE: Maximum Equivalent Vent Length (MEVL) includes standard and concentric vent termination and does NOT include elbows.
Use Table 2 - Deductions from Maximum Equivalent Vent Length to determine allowable vent length for each application.
Table 1 – Maximum Equivalent Vent Length -- Ft. (M)
0 to 4500 Ft. (0 to 1370 M) Altitude
Unit Size
Altitude
FT (M)
0 to 2000
(0 to 610)
2001 to 3000
(610 to 914)
59TN6A
3001 to 4000 (914 to 1219)
4001 to 4500
(1219 to
1370)
NOTES: See notes at end of venting tables.
See Table 3 for altitudes over 4500 ft. (1370 M)
BTU/Hr
40,000
60,000 30 (9.1) 135 (41.1) 235 (71.6) 265 (80.8) NA
80,000 20 (6.1) 70 (21.3) 175 (53.3) 235 (71.6) 265 (80.8) 100,000 NA 25 (7.6) 110 (33.5) 235 (71.6) 265 (80.8) 120,000 NA NA 15 (4.6) 100 (30.5) 250 (76.2)
140,000
40,000 45 (13.7) 198 (60.4) 232 (70.7) NA NA
60,000 27 (8.2) 127 (38.7) 222 (67.7) 250 (76.2) NA
80,000 17 (5.2) 64 (19.5) 165 (50.3) 222 (67.7) 249 (75.9) 100,000 NA 22 (6.7) 104 (31.7) 223 (68.0) 250 (76.2) 120,000 NA NA 11 (3.4) 93 (28.3) 237 (72.2)
140,000
40,000 39 (11.9) 184 (56.1) 214 (65.2) NA NA
60,000 23 (7.0) 119 (36.3) 210 (64.0) 235 (71.6) NA
80,000 15 (4.6) 59 (18.0) 155 (47.2) 210 (64.0) 232 (70.7) 100,000 NA 19 (5.8) 98 (29.9) 211 (64.3) 236 (71.9) 120,000 NA NA 8 (2.4) 86 (26.2) 224 (68.3)
140,000
40,000 36 (11.0) 177 (53.9) 205 (62.5) NA NA
60,000 21 (6.4) 115 (35.1) 204 (62.2) 228 (69.5) NA
80,000 14 (4.3) 56 (17.1) 150 (45.7) 202 (61.6) 224 (68.3) 100,000 NA 17 (5.2) 94 (28.7) 205 (62.5) 229 (69.8) 120,000 NA NA NA 83 (25.3) 217 (66.1)
140,000
3
4
4
4
4
50 (15.2) 210 (64.0) 250 (76.2) NA
NA NA 10 (3.0) 90 (27.4) 210 (64.0)
NA NA NA 80 (24.4) 185 (56.4)
NA NA NA 79 (24.1) 158 (48.2)
NA NA NA 69 (21.0) 146 (44.5)
DIRECT VENT (2-PIPE) AND NON-DIRECT VENT (1-PIPE)
Vent Pipe Diameter (in.)
1-1/2 2 2-1/2 3 4
1
2
NA
Long
ELBOW CONFIGURATIONS VENT TERMINAL CONFIGURATIONS
Concentric
Medium
Mitered
Standard
A11580
8
Page 9
MAXIMUM EQUIVALENT VENT LENGTH -- FT. (M) (CONTINUED)
Table 2 – Deductions from Maximum Equivalent Vent Length -- Ft. (M)
Pipe Diameter (in): 1-1/2 2 2-1/2 3 4
Mitered 90º Elbow 8 (2.4) 8 (2.4) 8 (2.4) 8 (2.4) 8 (2.4)
Medium Radius 90º Elbow 5 (1.5) 5 (1.5) 5 (1.5) 5 (1.5) 5 (1.5)
Long Radius 90º Elbow 3 (0.9) 3 (0.9) 3 (0.9) 3 (0.9) 3 (0.9)
Mitered 45º Elbow 4 (1.2) 4 (1.2) 4 (1.2) 4 (1.2) 4 (1.2)
Medium Radius 45º Elbow 2.5 (0.8) 2.5 (0.8) 2.5 (0.8) 2.5 (0.8) 2.5 (0.8)
Long Radius 45º Elbow 1.5 (0.5) 1.5 (0.5) 1.5 (0.5) 1.5 (0.5) 1.5 (0.5)
Tee 16 (4.9) 16 (4.9) 16 (4.9) 16 (4.9) 16 (4.9)
Concentric Vent Termination NA 0 (0.0) NA 0 (0.0) NA
Standard Vent Termination 0 (0.0) 0 (0.0) 0 (0.0) 0 (0.0) 0 (0.0)
Venting System Length Calculations
The maximum length for each vent pipe (inlet or exhaust) equals the Maximum Equivalent Vent Length (MEVL) from Table 1 or Table 3 minus the number of elbows multiplied by the deduction for each elbow in Table 2.
Standard vent terminations and concentric vent terminations count for zero deductions. See Vent Manufacturers’ data for equivalent lengths of flexible vent piping. DO NOT ASSUME that one foot of flexible vent pipe is equivalent to one foot of standard PVC vent pipe.
Example
A direct--vent 60,000 Btuh furnace installed at 2100 ft. (640 M) with 2--in.(51 mm) vent piping. Venting system includes, FOR EACH PIPE, (3) 90_ long radius elbows, (2) 45_ long radius elbows and a concentric vent kit.
Maximum Equivalent Vent Length = 127 ft. (From Table 1)
Deduct (3) 90 long radius 3 x 3 ft. = - 9 ft. (From Table 2) Deduct (2) 45 long radius 2 x 1.5 ft. = - 3 ft. (From Table 2) No deduction for Concentric Vent Kit 0 ft. = - 0 ft. (From Table 2)
Maximum Vent Length = 115 ft. For EACH vent or inlet pipe
59TN6A
9
Page 10
MAXIMUM EQUIVALENT VENT LENGTH -- FT. (M) (CONTINUED)
NOTE: Maximum Equivalent Vent Length (MEVL) includes standard and concentric vent termination and does NOT include elbows.
Use Table 2 - Deductions from Maximum Equivalent Vent Length to determine allowable vent length for each application.
Table 3 – Maximum Equivalent Vent Length -- Ft. (M)
4501 to 10,000 Ft. (1371 to 3048 M) Altitude
Altitude
FT (M)
5
Unit Size
1-1/2 2 2-1/2 3 4
40,000 33 (10.1) 171 (52.1) 196 (59.7)
4501 to 5000
(1370 to
1524)
60,000 20 (6.1) 111 (33.8) 198 (60.4) 221 (67.4) NA
80,000 13 (4.0) 54 (16.5) 146 (44.5) 195 (59.4) 216 (65.8) 100,000 NA 16 (4.9) 91 (27.7) 200 (61.0) 222 (67.7) 120,000 NA NA NA 80 (24.4) 211 (64.3)
4
140,000
NA NA NA 60 (18.3) 134 (40.8)
40,000 27 (8.2) 158 (48.2) 179 (54.6) NA NA
5001 to 6000
(1524 to
1829)
59TN6A
6001 to 7000
(1829 to
2134)
60,000 16 (4.9) 103 (31.4) 186 (56.7) 207 (63.1) NA
80,000 11 (3.4) 49 (14.9) 137 (41.8) 183 (55.8) 200 (61.0) 100,000 NA 12 (3.7) 85 (25.9) 188 (57.3) 208 (63.4) 120,000 NA NA NA 74 (22.6) 199 (60.7)
4
140,000
NA NA NA 50 (15.2) 109 (33.2) 40,000 21 (6.4) 145 (44.2) 162 (49.4) NA NA 60,000 13 (4.0) 96 (29.3) 174 (53.0) 194 (59.1) NA 80,000 NA 44 (13.4) 120 (36.6) 171 (52.1) 185 (56.4)
100,000 NA 10 (3.0) 79 (24.1) 178 (54.3) 195 (59.4) 120,000 NA NA NA 68 (20.7) 187 (57.0)
4
140,000
NA NA NA 41 (12.5) 87 (26.5) 40,000 15 (4.6) 133 (40.5) 146 (44.5) NA NA
7001 to 8000
(2134 to
2438)
60,000 10 (3.0) 89 (27.1) 163 (49.7) 181 (55.2) NA 80,000 NA 40 (12.2) 120 (36.6) 159 (48.5) 170 (51.8)
100,000 NA NA 73 (22.3) 167 (50.9) 182 (55.5) 120,000 NA NA NA 62 (18.9) 175 (53.3)
4
140,000
NA NA NA 32 (9.8) 63 (19.2) 40,000 10 (3.0) 121 (36.9) 130 (39.6) NA NA
8001 to 9000
(2438 to
2743)
60,000 7 (2.1) 82 (25.0) 152 (46.3) 168 (51.2) NA 80,000 NA 35 (10.7) 111 (33.8) 148 (45.1) 156 (47.5)
100,000 NA NA 67 (20.4) 157 (47.9) 170 (51.8) 120,000 NA NA NA 56 (17.1) 164 (50.0)
4
140,000
NA NA NA 23 (7.0) 42 (12.8) 40,000 5 (1.5) 110 (33.5) 115 (35.1) NA NA
9001 to
10,000
(2743 to
3048)
NOTES:
1. Use only the vent pipe sizes shown for each furnace. It is NOT necessary to choose the smallest diameter pipe possible for venting.
2. NA --- Not allowed. Pressure switch will not cl ose, or flame disturbance may result.
3. Total equ ivalent vent lengths under 10’ for 40,000 BTUH fur naces from 0 to 2000 ft. (0 to 610 M) above sea level require use of an outlet choke plate .
Failure to use an outlet choke when required may result in flame disturbance or flame sense lockout.
4. Not all furnace f a milies include 140,000 BTUH input models.
5. Vent sizing for Canadian installations over 4500 ft (1370 M) above sea level are subject to acceptance by local authorities having jur isdiction.
6. Size both the combustion air and vent pipe independently, then use the larger size for both pipes.
7. Assume the two 45_ elbows equal one 90_ elbow. Wide radius elbows are desirable and may be required in some cases.
8. Elbow and pipe sections within the furnace casing and at the vent termination should not be included in vent length or elbow count.
9. The minimum pipe length is 5 ft. (1.5 M) lin ear feet (meters) f or all applications.
10. Use 3 ---in. (76 mm) diameter vent termination kit for installations requiring 4 - --in . (102 mm) diameter pipe.
60,000 NA 76 (23.2) 142 (43.3) 156 (47.5) NA 80,000 NA 31 (9.4) 103 (31.4) 137 (41.8) 142 (43.3)
100,000 NA NA 62 (18.9) 147 (44.8) 157 (47.9) 120,000 NA NA NA 51 (15.5) 153 (46.6)
4
140,000
NA NA NA 16 (4.9) 20 (6.1)
DIRECT VENT (2-PIPE) AND SINGLE-PIPE
NA
1
2
Vent Pipe Diameter (in.)
NA
10
Page 11
MAXIMUM ALLOWABLE EXPOSED VENT PIPE LENGTH INSULATION TABLE -- FT. / M
Two S t ag e
Furnace High
Heat Input
40000*
Winter Design
Te m p ° F ( ° C )
20 (-10)
0 (-20)
-20 (-30)
-40 (-40)
Pipe
Length in
Ft. & M
Ft. 40.0 35.0 35.0 N/A N/A 50.0 104.0 94.0 N/A N/A 50.0 122.0 110.0 N/A N/A
M 12.2 10.7 10.7 N/A N/A 15.2 31.7 28.7 N/A N/A 15.2 37.2 33.5 N/A N/A
Ft. 19.0 14.0 12.0 N/A N/A 50.0 61.0 54.0 N/A N/A 50.0 74.0 65.0 N/A N/A
M 5.8 4.3 3.7 N/A N/A 15.2 18.6 16.5 N/A N/A 15.2 22.6 19.8 N/A N/A
Ft. 9.0 3.0 1.0 N/A N/A 50.0 41.0 35.0 N/A N/A 50.0 51.0 43.0 N/A N/A
M 2.7 0.9 0.3 N/A N/A 15.2 12.5 10.7 N/A N/ A 15.2 15.5 13.1 N/A N/A
Ft. 3.0 0.0 0.0 N/A N/A 39.0 29.0 23.0 N/A N/A 48.0 37.0 30.0 N/A N/A
M 0.9 0.0 0.0 N/A N/A 11.9 8.8 7.0 N/A N/A 14.6 11.3 9.1 N/A N/A
No Insulation 3/8-in. (9.5 mm) 1/2-in. (12.7 mm)
Pipe Diameter-inches (mm) Pipe Diameter-inches (mm) Pipe Diameter-inches (mm)
1.5 2.0 2.5 3.0 4.0 1.5 2.0 2.5 3.0 4.0 1.5 2.0 2.5 3.0 4.0
(38) (51) (64) (76) (102) (38) (51) (64) (76) (102) (38) (51) (64) (76) (102)
60000
80000
100000
20 (-10)
0 (-20)
-20 (-30)
-40 (-40)
20 (-10)
0 (-20)
-20 (-30)
-40 (-40)
20 (-10)
0 (-20)
-20 (-30)
-40 (-40)
Ft. 30.0 51.0 51.0 45.0 N/A 30.0 135.0 138.0 120.0 N/A 30.0 135.0 162.0 141.0 N/A
M 9.1 15.5 15.5 13.7 N/A 9.1 41.1 42.1 36.6 N/A 9.1 41.1 49.4 43.0 N/A
Ft. 30.0 24.0 23.0 16.0 N/A 30.0 93.0 82.0 69.0 N/A 30.0 111.0 98.0 83.0 N/A
M 9.1 7.3 7.0 4.9 N/A 9.1 28.3 25.0 21.0 N/A 9.1 33.8 29.9 25.3 N/A
Ft. 18.0 11.0 9.0 1.0 N/A 30.0 65.0 56.0 44.0 N/A 30.0 79.0 68.0 55.0 N/A
M 5.5 3.4 2.7 0.3 N/A 9.1 19.8 17.1 13.4 N/A 9.1 24.1 20.7 16.8 N/A
Ft. 10.0 3.0 0.0 0.0 N/A 30.0 48.0 40.0 29.0 N/A 30.0 59.0 50.0 38.0 N/A
M 3.0 0.9 0.0 0.0 N/A 9.1 14.6 12.2 8.8 N/A 9.1 18.0 15.2 11.6 N/A
Ft. 20.0 64.0 64.0 56.0 47.0 20.0 70.0 173.0 150.0 125.0 20.0 70.0 175.0 177.0 147.0
M 6.1 19.5 19.5 17.1 14.3 6.1 21.3 52.7 45.7 38.1 6.1 21.3 53.3 53.9 44.8
Ft. 20.0 32.0 30.0 22.0 11.0 20.0 70.0 104.0 87.0 67.0 20.0 70.0 124.0 104.0 82.0
M 6.1 9.8 9.1 6.7 3.4 6.1 21.3 31.7 26.5 20.4 6.1 21.3 37.8 31.7 25.0
Ft. 20.0 17.0 14.0 6.0 0.0 20.0 70.0 71.0 57.0 40.0 20.0 70.0 86.0 71.0 52.0
M 6.1 5.2 4.3 1.8 0.0 6.1 21.3 21.6 17.4 12.2 6.1 21.3 26.2 21.6 15.8
Ft. 15.0 7.0 5.0 0.0 0.0 20.0 61.0 52.0 40.0 24.0 20.0 70.0 64.0 50.0 33.0
M 4.6 2.1 1.5 0.0 0.0 6.1 18.6 15.8 12.2 7.3 6.1 21.3 19.5 15.2 10.1
Ft. N/A 25.0 79.0 70.0 59.0 N/A 25.0 110.0 186.0 155.0 N/A 25.0 110.0 219.0 182.0
M N/A 7.6 24.1 21.3 18.0 N/A 7.6 33.5 56.7 47.2 N/A 7.6 33.5 66.8 55.5
Ft. N/A 25.0 40.0 31.0 19.0 N/A 25.0 110.0 109.0 86.0 N/A 25.0 110.0 131.0 104.0
M N/A 7.6 12.2 9.4 5.8 N/A 7.6 33.5 33.2 26.2 N/A 7.6 33.5 39.9 31.7
Ft. N/A 23.0 21.0 13.0 0.0 N/A 25.0 91.0 74.0 54.0 N/A 25.0 110.0 90.0 68.0
M N/A 7.0 6.4 4.0 0.0 N/A 7.6 27.7 22.6 16.5 N/A 7.6 33.5 27.4 20.7
Ft. N/A 13.0 10.0 1.0 0.0 N/A 25.0 68.0 53.0 35.0 N/A 25.0 83.0 66.0 46.0
M N/A 4.0 3.0 0.3 0.0 N/A 7.6 20.7 16.2 10.7 N/A 7.6 25.3 20.1 14.0
59TN6A
20 (-10)
0 (-20)
120000
-20 (-30)
-40 (-40)
* Not all families have these models. * Pipe length (ft) specified for maximum pipe l en gths located in unconditioned spaces. Pipes located in unconditioned space cannot exceed total allowable pipe
length calculated from Table 1 or 3.
† Insulation thickness based on R value of 3.5 per in.
Ft. N/A N/A 15.0 85.0 73.0 N/A N/A 15.0 100.0 190.0 N/A N/A 15.0 100.0 224.0
M N/A N/A 4.6 25.9 22.3 N/A N/A 4.6 30.5 57.9 N/A N/A 4.6 30.5 68.3
Ft. N/A N/A 15.0 41.0 29.0 N/A N/A 15.0 100.0 109.0 N/A N/A 15.0 100.0 131.0
M N/A N/A 4.6 12.5 8.8 N/A N/A 4.6 30.5 33.2 N/A N/A 4.6 30.5 39.9
Ft. N/A N/A 15.0 20.0 7.0 N/A N/A 15.0 94.0 71.0 N/A N/A 15.0 114.0 88.0
M N/A N/A 4.6 6.1 2.1 N/ A N/A 4.6 28.7 21.6 N/A N/A 4.6 34.7 26.8
Ft. N/A N/A 15.0 7.0 0.0 N/A N/A 15.0 69.0 48.0 N/A N/A 15.0 85.0 62.0
M N/A N/A 4.6 2.1 0.0 N/ A N/A 4.6 21.0 14.6 N/A N/A 4.6 25.9 18.9
11
Page 12
RETURN AIR TEMPERATURE
This furnace is designed for continuous return--air minimum temperature of 60_F(15_C) db or intermittent operation down to 55_F(13_C) db such as when used with a night setback thermometer. Return--air temperature must not exceed 80_F(27_C) db. Failure to follow these return air limits may affect reliability of heat exchangers, motors and controls.
80 / 27˚C
SUPPLY AIR
60
/ 16˚C
59TN6A
MINIMUM CLEARANCES TO COMBUSTIBLE MATERIALS
POSITION CLEARANCE
Rear 0(0mm)
Front (Combustion air openings in furnace and in structure) 1in.(25mm)
Required for service *24 in. (610 mm)
All Sides of Supply Plenum 1in.(25mm)
Sides 0(0mm)
Ve n t 0(0mm)
* Recommended
Top of Furnace 1in. (25mm)
A10490
COMBUSTION--AIR PIPE FOR NON--DIRECT (1--PIPE) VENT APPLICATION
FIELD-SUPPLIED 2-IN. (51 mm) DIA. TIGHT RADIUS PVC 90° ELBOW
FIELD-SUPPLIED 2-IN. (51 mm) DIA. PVC PIPE
12” (300 mm) Minimum
A11487
12
Page 13
DOWNFLOW SUBBASE
LOCATING
TAB
11/
4-IN. TYP
PLENUM OPENING
A
LOCATING
TAB
B
4
3
D
2
1
FACTORY-SUPPLIED
FIELD-INSTALLED
INSULATION
C
A97427
Assembled
DIMENSIONS (IN. / MM)
FURNACE
CASING WIDTH
17---1/2 (444.5)
21 (533.4)
24---1/2 (622.3)
*The plenum should be constructed 1/4 ---in. (6 mm) smaller in width and depth than the plenum dimensions shown above.
FURNACE IN DOWNFLOW
APPLICATION
Furnace with or without Cased Coil
Assembly or Coil Box
Furnace with or without Cased Coil
Assembly or Coil Box
Furnace with or without Cased Coil
Assembly or Coil Box
PLENUM OPENING* FLOOR OPENING
A B C D
15---1/8
(384.2)
18---5/8
(396.4)
22---1/8
(562.0)
19 (482.6)
19 (482.6)
19 (482.6)
16---3/4
(425.5)
20---1/4
(514.4)
23---3/4
(603.3)
Disassembled
20---3/8 (517.5)
20---3/8 (517.5)
20---3/8 (517.5)
1
2
3
4
A88207
HOLE NO. FOR
WIDTH
ADJUSTMENT
3
2
1
59TN6A
Concentric Vent Kit
A concentric vent kit allows vent and combustion--air pipes to terminate through a single exit in a roof or side wall. One pipe runs inside the other allowing venting through the inner pipe and combustion air to be drawn in through the outer pipe.
A93086
Downflow Subbase
A88202
One base fits all furnace sizes. The base is designed to be installed between the furnace and a combustible floor when no coil box is used or when a coil box other than a Carrier cased coil is used. It is CSA design certified for use with Carrier branded furnaces when installed in downflow applications.
13
Page 14
23-5/8"
(600mm)
23-3/8”
(594mm)
MEDIA FILTER CABINET
A
25-5/8"
(651mm)
24-1/4”
(616mm)
Opening with Flanges Bent
23-1/8”
(588mm)
Opening
B Opening
Furnace Side
59TN6A
23-3/4”
(603mm)
Centerline Screw Slots
3
"
5
4
(146mm)
Media Filter
Cabinet
16" (406mm)
20" (508mm) 24" (610mm)
Duct Side
A 17" (432mm) 21" (533mm) 25" (635mm)
B 16" (406mm) 20" (508mm)
24" (610mm)
A11456
TYPICAL WIRING SCHEMATIC
FIELD 24-VOLT WIRING FIELD 115-, 208/230-, 460-VOLT WIRING FACTORY 24-VOLT WIRING FACTORY 115-VOLT WIRING
BLOWER
DOOR
SWITCH
BLK
WHT
GND
115-VOLT FIELD-
SUPPLIED
FUSED
DISCONNECT
BLK
WHT
JUNCTION BOX
FIVE
WIRE
THREE-WIRE
HEATING-
ONLY
FURNACE
W2
C
COM
O N
W/W1
T
Y/Y2
R O
R
L
G
24-VOLT
TERMINAL
BLOCK
NOTE 2
WCY RG
NOTE 1
NOTES: 1.
Connect Y/Y2-terminal as shown for proper operation. Some thermostats require a "C" terminal connection as shown.
2. If any of the original wire, as supplied, must be replaced, use
3. same type or equivalent wire.
1-STAGE THERMOSTAT TERMINALS
CONDENSING
UNIT
FIELD-SUPPLIED
FUSED DISCONNECT
GND
208/230- OR 460-VOLT THREE PHASE
208/230­VOLT SINGLE PHASE
A11401
14
Page 15
DIMENSIONAL DRAWING
59TN6A
A11589
15
Page 16
GUIDE SPECIFICATIONS
General
System Description
Furnish a ______________________ 4--way multipoise two--stage gas--fired condensing furnace for use with natural gas or propane (factory-- authorized conversion kit required for propane); furnish cold air return plenum; furnish external media cabinet for use with accessory media filter or standard filter.
Quality Assurance
Unit will be designed, tested and constructed to the current ANSI Z
21.47/CSA 2.3 design standard for gas--fired central furnaces. Unit will be third party certified by CSA to the current ANSI Z
21.47/CSA 2.3 design standard for gas--fired central furnaces. Unit will carry the CSA Blue StarR and Blue FlameR labels. Unit efficiency testing will be performed per the current DOE test procedure as listed in the Federal Register.
Unit will be certified for capacity and efficiency and listed in the latest AHRI Consumer’s Directory of Certified Efficiency Ratings.
Unit will carry the current Federal Trade Commission Energy Guide efficiency label.
59TN6A
Delivery, Storage, and Handling
Unit will be shipped as single package only and is stored and handled per unit manufacturer’s recommendations.
Warranty (for inclusion by specifying engineer)
U.S. and Canada only. Warranty certificate available upon request.
Equipment
Blower Wheel and ECM Blower Motor Galvanized blower wheel shall be centrifugal type, statically and
dynamically balanced. Blower motor of ECM type shall be permanently lubricated with sealed ball bearings, of _______hp, and have infinitely variable speed from 300--1300 RPM operating only when motor inputs are provided. Blower motor shall be direct drive and soft mounted to the blower scroll to reduce vibration transmission.
Filters Furnace shall have reusable--type filters. Filter shall be ______ in.
(mm) X ________ in. (mm). An accessory highly efficient Media Filter is available as an option. _____________ Media Filter.
Casing Casing shall be of .030 in. thickness minimum, pre--painted
galvanized steel. Draft Inducer Draft Inducer motor shall be two--speed design.
Motor
Primary Heat Primary heat exchangers shall be 3--Pass corrosion--resistant
aluminized steel of fold--and--crimp sectional design and applied operating under negative pressure.
Secondary Heat Secondary heat exchangers shall be of a stainless steel
flow--through of fin--and--tube design and applied operating under negative pressure.
Controls Controls shall include a micro--processor--based integrated
electronic control board with at least 16 service troubleshooting codes displayed via diagnostic flashing LED light on the control, a self--test feature that checks all major functions of the furnace, and a replaceable automotive--type circuit protection fuse. Multiple operational settings available, including separate blower speeds for low heat, high heat, low cooling, high cooling and continuous fan. Continuous fan speed may be adjusted from the thermostat. Cooling airflow will be selectable between 325 and 400 CFM per ton of air conditioning. Features will also include temporary reduced airflow in the cooling mode for improved dehumidification when an Infinity Control or TP--PRH edgeR is selected as the thermostat.
Exchangers
Exchangers
Operating Characteristics
Heating capacity shall be _________________ Btuh input; ______________ Btuh output capacity.
Fuel Gas Efficiency shall be __________ AFUE. Air delivery shall be ________________ cfm minimum at 0.50 in.
W.C. external static pressure. Dimensions shall be: depth_________in. (mm); width
__________in. (mm); height___________in. (mm) (casing only). Height shall be _________in. (mm) with A/C coil and _________________in. (mm) overall with plenum.
Electrical Requirements
Electrical supply shall be 115 volts, 60 Hz, single--phase (nominal). Minimum wire size shall be ________AWG; maximum fuse size of HACR--type designated circuit breaker shall be _________ amps.
Special Features
Refer to section of the product data identifying accessories and descriptions for specific features and available enhancements.
Copyright 2012 Carrier Corp. S 7310 W. Morris St. S Indianapolis, IN 46231 Printed in U.S.A. Edition Date: 02/12
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
Catalog No: 59TN6A ---04PD
Replaces: 59TN6A--- 03PD
16