Carrier 59MN7A, 59TP6A Series 2 Installation, Start-up, Operating And Service And Maintenance Instructions

Page 1
59MN7A Modulating 4---Way Multipoise Condensing Gas Furnace Series 200
Installation, Start---up, Operating and
Service and Maintenance Instructio ns
NOTE: Read the entire instruction manual before starting the installation.
SAFETY CONSIDERATIONS 3.........................
INTRODUCTION 3...................................
CODES AND STANDARDS 4...........................
ELECTROSTATIC DISCHARGE (ESD) PRECAUTIONS 4...
ACCESSORIES 4.....................................
LOCATION 5........................................
AIR FOR COMBUSTION AND VENTILATION 9..........
CONDENSATE TRAP 11...............................
Upflow 11........................................
Downflow 11.....................................
Horizontal 11......................................
CONDENSATE DRAIN 15.............................
INSTALLATION 18...................................
Upflow 18........................................
Downflow 18.....................................
Horizontal 19......................................
Filter Arrangement 19...............................
AIR DUCTS 28.......................................
Ductwork Acoustical Treatment 28.....................
GAS PIPING 32......................................
ELECTRICAL CONNECTIONS 33.......................
115--V Wiring 33...................................
J--Box Installation 34................................
24--V Wiring 34....................................
Accessories 34.....................................
Alternate Power Supplies 35..........................
VENTING 40........................................
Special Venting Requirements for Installations in Canada 40.
Materials 41.......................................
Venting Systems 41.................................
Locating Vent Termination 42.........................
Size the Vent and Combustion Air Pipes 42...............
Combustion Air and Vent Piping Insulation Guidelines 43...
Configure the Furnace 44............................
Installing the Vent Termination 46......................
Venting System Length Calculations 50.................
START--UP, ADJUSTMENT, AND SAFETY CHECK 64......
Select Setup Switch Positions 64........................
Prime Condensate Trap 64.............................
Purge Gas Lines 65...................................
Adjustments 66......................................
Check Safety Controls 69..............................
Checklist 69........................................
SERVICE AND MAINTENANCE PROCEDURES 79........
Cleaning Heat Exchangers 85...........................
SEQUENCE OF OPERATION 92........................
PARTS REPLACEMENT GUIDE 97......................
TABLE
Loose Parts Bag Contents 6..............................
Minimum Clearances to Combustible Materials 6.............
Minimum Free Area Required 10.........................
Minimum Space Volumes 10.............................
Filter Size Information 22...............................
Opening Dimensions 24................................
Air Delivery CFM 29...................................
Maximum Capacity of Pipe 33...........................
Electrical Data 35......................................
Vent Termination Kit for Direct Vent (2--Pipe) Systems 42......
Combustion--Air Vent Pipe, Fitting & Cement Material.. 47.....
Maximum Allowable Exposed Vent Lengths Insulation 48......
Maximum Equivalent Vent Length 49......................
Deductions from Maximum Equivalent Vent Length 49........
Altitude Derate Multiplier for U.S.A. 74....................
Blower Off Delay Setup Switch 74........................
Gas Rate 74..........................................
Orifice Size and Manifold Pressure 75.....................
CERTIFIED
Use of the AHRI Certified manufacturer’s participation in the program. For verification of certification for individual products, go to www.ahridirectory.org.
Portions of the text and tables are reprinted from NFPA 54/ANSI Z223.1--2009E, with permission of National Fire Protection Association, Quincy, MA 02269 and American Gas Association, Washington DC 20001. This reprinted material is not the complete and official position of the NFPA or ANSI on the referenced subject, which is represented only by the standard in its entirety.
TM
Mark indicates a
1
Page 2
Required Notice for Massachusetts Installations
IMPORTANT
The Commonwealth of Massachusetts requires compliance with regulation 248 CMR as follows:
5.08: Modifications to NFPA--54, Chapter 10
2) Revise 10.8.3 by adding the following additional requirements: a. For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in
whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above finished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall be satisfied:
1. INSTALLATION OF CARBON MONOXIDE DETECTORS. At the time of installation of the side wall horizontal vented gas fueled equipment, the installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back--up is installed on the floor level where the gas equipment is to be installed. In addition, the installing plumber or gasfitter shall observe that a battery operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of qualified licensed professionals for the installation of hard wired carbon monoxide detectors
a. In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired
carbon monoxide detector with alarm and battery back--up may be installed on the next adjacent floor level.
59MN7A
b. In the event that the requirements of this subdivision can not be met atthe time of completion of installation, the ownershall
have a period of thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed.
2. APPROVED CARBON MONOXIDE DETECTORS. Each carbon monoxide detector as required in accordance with the above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified.
3. SIGNAGE. A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print size no less than one--half (1/2) inch in size, ”GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS”.
4. INSPECTION. The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.08(2)(a)1 through 4.
5. EXEMPTIONS: The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:
(1.) The equipment listed in Chapter 10 entitled ”Equipment Not Required To Be Vented” in the most current edition of
NFPA 54 as adopted by the Board; and
(2.) Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from
the dwelling, building or structure used in whole or in part for residential purposes.
c. MANUFACTURER REQUIREMENTS -- GAS EQUIPMENT VENTING SYSTEM PROVIDED. When the
manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the instructions provided by the manufacturer for installation of the equipment and the venting system shall include:
1. Detailed instructions for the installation of the venting system design or the venting system components; and
2. A complete parts list for the venting system design or venting system.
d. MANUFACTURER REQUIREMENTS -- GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED. When
the manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the flue gases, but identifies “special venting systems”, the following requirements shall be satisfied by the manufacturer:
1. The referenced “special venting system” instructions shall be included with the appliance or equipment installation instructions; and
2. The “special venting systems” shall be Product Approved by the Board, and the instructions for that system shall include a parts list and detailed installation instructions.
e. A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment,
all venting instructions, all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of the installation.
For questions regarding these requirements, please contact the Commonwealth of Massachusetts Board of State Examiners of Plumbers and
Gas Fitters, 239 Causeway Street, Boston, MA 02114. 617--727--9952.
2
Page 3
SAFETY CONSIDERATIONS
!
WARNING
FIRE, EXPLOSION, ELECTRICAL SHOCK, AND CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in dangerous operation, personal injury, death, or property damage.
Improper installation, adjustment, alteration, service, maintenance, or use can cause carbon monoxide poisoning, explosion, fire, electrical shock, or other conditions which may cause personal injury or property damage. Consult a qualified service agency, local gas supplier, or your distributor or branch for information or assistance. The qualified service agency must use only factory--authorized and listed kits or accessories when modifying this product.
!
WARNING
FIRE HAZARD
Failure to follow this warning could result in personal injury, death, or property damage.
Solvents, cements and primers are combustible. Keep away from heat, sparks and open flame. Use only in well--ventilated areas. Avoid breathing in vapor or allowing contact with skin or eyes.
!
CAUTION
FURNACE RELIABILITY HAZARD
Failure to follow this caution may result in unit component damage.
Application of this furnace should be indoors with special attention given to vent sizing and material, gas input rate, air temperature rise, unit leveling, and unit sizing.
Improper installation, adjustment, alteration, service, maintenance, or use can cause explosion, fire, electrical shock, or other conditions which may cause death, personal injury, or property damage. Consult a qualified installer, service agency, or your distributor or branch for information or assistance. The qualified installer or agency must use factory-authorized kits or accessories when modifying this product. Refer to the individual instructions packaged with the kits or accessories when installing.
Installing and servicing heating equipment can be hazardous due to gas and electrical components. Only trained and qualified
personnel should install, repair, or service heating equipment.
Untrained personnel can perform basic maintenance functions such as cleaning and replacing air filters. All other operations must be performed by trained service personnel. When working on heating equipment, observe precautions in literature, on tags, and on labels attached to or shipped with furnace and other safety precautions that may apply.
These instructions cover minimum requirements and conform to existing national standards and safety codes. In some instances, these instructions exceed certain local codes and ordinances, especially those that may not have kept up with changing residential construction practices. We require these instructions as a minimum for a safe installation.
Follow all safety codes. Wear safety glasses, protective clothing, and work gloves. Have a fire extinguisher available. Read these instructions thoroughly and follow all warnings or cautions included in literature and attached to the unit.
!
CAUTION
CUT HAZARD
Failure to follow this caution may result in personal injury. Sheet metal parts may have sharp edges or burrs. Use care
and wear appropriate protective clothing, safety glasses and gloves when handling parts, and servicing furnaces.
This is the safety--alert symbol . When you see this symbol on the furnace and in instructions or manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING,and
CAUTION. These words are used with the safety--alert symbol. DANGER identifies the most serious hazards which will result in
severe personal injury or death. WARNING signifies a hazard which could result in personal injury or death. CAUTION is used to identify hazards which may result in minor personal injury or product and property damage. NOTE and NOTICE are used to highlight suggestions which will result in enhanced installation, reliability, or operation.
1. Use only with type of gas approved for this furnace. Refer to the furnace rating plate.
2. Install this furnace only in a location and position as spe­cified in the “Location” section of these instructions.
3. Provide adequate combustion and ventilation air to the fur­nace space as specified in “Air for Combustion and Ventila­tion” section.
4. Combustion products must be discharged outdoors. Con­nect this furnace to an approved vent system only, as spe­cified in the “Venting” section of these instructions.
5. Never test for gas leaks with an open flame. Use a commer­cially available soap solution made specifically for the de­tection of leaks to check all connections, as specified in the “Gas Piping” section.
6. Always install furnace to operate within the furnace’s inten­ded temperature--rise range with a duct system which has an external static pressure within the allowable range, as spe­cified in the “Start--Up, Adjustments, and Safety Check” section. See furnace rating plate.
7. When a furnace is installed so that supply ducts carry air circulated by the furnace to areas outside the space contain­ing the furnace, the return air shall also be handled by duct(s) sealed to the furnace casing and terminating outside the space containing the furnace. See “Air Ducts” section.
8. A gas--fired furnace for installation in a residential garage must be installed as specified in the warning box in the “Location” section.
9. The furnace may be used for construction heat provided that the furnace installation and operation complies with the first CAUTION in the LOCATION section of these instruc­tions.
10. These Multipoise Gas--Fired Furnaces are CSA design--cer­tified for use with natural and propane gases (see furnace rating plate) and for installation in alcoves, attics, base­ments, closets, utility rooms, crawlspaces, and garages. The furnace is factory--shipped for use with natural gas. A CSA (A.G.A. and C.G.A.) listed accessory gas conversion kit is required to convert furnace for use with propane gas.
11. See Table 2 for required clearances to combustible con­struction.
12. Maintain a 1--in. (25 mm) clearance from combustible ma­terials to supply air ductwork for a distance of 36 in. (914 mm) horizontally from the furnace. See NFPA 90B or local code for further requirements.
59MN7A
3
Page 4
13. These furnaces SHALL NOT be installed directly on carpet­ing, combustible tile, or any other combustible material oth­er than wood flooring. In downflow installations, factory accessory floor base MUST be used when installed on com­bustible materials and wood flooring. Special base is not re­quired when this furnace is installed on manufacturer’s Coil Assembly Part No. CNRV, CNPV, CAP, or CAR or when Coil Box Part No. KCAKC is used. See Table 2 for clear­ance to combustible construction information.
INTRODUCTION
The 4--way multipoise Category IV condensing furnace is CSA design--certified for both direct--vent (2-pipe) and ventilated combustion air venting installations. See Fig. 2. The furnace is factory--shipped for use with natural gas. The furnace can be converted in the field for use with propane gas when a factory-supplied conversion kit is used. Refer to the furnace rating plate for conversion kit information.
This furnace is not approved for installation in mobile homes, recreational vehicles, or outdoors.
This furnace is designed for minimum continuous return--air temperature of 60_F(15_C) db or intermittent operation down to 55_F(13_C) db such as when used with a night setback
59MN7A
thermostat. Return-air temperature must not exceed 80_F(27_C) db. Failure to follow these return-air temperature limits may affect reliability of heat exchangers, motors, and controls. See Fig. 3.
The furnace should be sized to provide 100 percent of the design heating load requirement plus any margin that occurs because of furnace model size capacity increments. Heating load estimates can be made using approved methods available from Air Conditioning Contractors of America (Manual J); American Society of Heating, Refrigerating, and Air--Conditioning Engineers; or other approved engineering methods. Excessive oversizing of the furnace could cause the furnace and/or vent to fail prematurely.
For accessory installation details, refer to the applicable instruction literature.
NOTE: Remove all shipping materials, loose parts bag, and literature before operating the furnace. See Table 1.
CODES AND STANDARDS
Follow all national and local codes and standards in addition to these instructions. The installation must comply with
regulations of the serving gas supplier, local building, heating, plumbing, and other codes. In absence of local codes, the installation must comply with the national codes listed below and all authorities having jurisdiction.
In the United States and Canada, follow all codes and standards for the following:
Safety
S US: National Fuel Gas Code (NFGC) NFPA 54--2009/ANSI
Z223.1--2009 and the Installation Standards, Warm Air Heating and Air Conditioning Systems ANSI/NFPA 90B
S CANADA: National Standard of Canada, Natural Gas and
Propane Installation Code (NSCNGPIC) CAN/CSA B149.1--2010
General Installation
S US: NFGC and the NFPA 90B. For copies, contact the National
Fire Protection Association Inc., Batterymarch Park, Quincy, MA 02269; or for only the NFGC contact the American Gas Association, 400 N. Capitol, N.W., Washington DC 20001
S CANADA: NSCNGPIC. For a copy, contact Standard Sales,
CSA International, 178 Rexdale Boulevard, Etobicoke (Toronto), Ontario, M9W 1R3, Canada
Combustion and Ventilation Air
S US: Section 9.3 of the NFPA54/ANSI Z223.1--2009 Air for
Combustion and Ventilation
S CANADA: Part 8 of the CAN/CSA B149.1--2010, Venting
Systems and Air Supply for Appliances
Duct Systems
S US and CANADA: Air Conditioning Contractors Association
(ACCA) Manual D, Sheet Metal and Air Conditioning Contractors National Association (SMACNA), or American Society of Heating, Refrigeration, and Air Conditioning Engineers (ASHRAE) 2005 Fundamentals Handbook Chapter 35
Acoustical Lining and Fibrous Glass Duct
S US and CANADA: current edition of SMACNA, NFPA 90B as
tested by UL Standard 181 for Class I Rigid Air Ducts
Gas Piping and Gas Pipe Pressure Testing
S US: NFPA 54/ANSI Z223.1--2009 NFGC; Chapters 5, 6, 7, and 8
and national plumbing codes. CANADA: CAN/CSA--B149.1--2010, Parts 4, 5, 6, and 9.
In the state of Massachusetts:
S This product must be installed by a licensed plumber or gas fitter. S When flexible connectors are used, the maximum length shall
not exceed 36 in. (914 mm).
S When lever typegas shutoffs are used they shall be T--handle
type.
S The use of copper tubing for gas piping is not approved by the
state of Massachusetts.
Electrical Connections
S US: National Electrical Code (NEC) ANSI/NFPA 70--2011 S CANADA: Canadian Electrical Code CSA C22.1
ELECTROSTATIC DISCHARGE (ESD)
PRECAUTIONS PROCEDURE
!
CAUTION
FURNACE RELIABILITY HAZARD
Failure to follow this caution may result in unit component damage.
Electrostatic discharge can affect electronic components. Take precautions during furnace installation and servicing to protect the furnace electronic control. Precautions will prevent electrostatic discharges from personnel and hand tools which are held during the procedure. These precautions will help to avoid exposing the control to electrostatic discharge by putting the furnace, the control, and the person at the same electrostatic potential.
1. Disconnect all power to the furnace. Multiple disconnects
may be required. DO NOT TOUCH THE CONTROL
OR ANY WIRE CONNECTED TO THE CONTROL PRIOR TO DISCHARGING YOUR BODY’S ELECTROSTATIC CHARGE TO GROUND.
2. Firmly touch the clean, unpainted, metal surface of the fur­nace chassis which is close to the control. Tools held in a person’s hand during grounding will be satisfactorily dis­charged.
3. After touching the chassis, you may proceed to service the control or connecting wires as long as you do nothing to recharge your body with static electricity (for example; DO NOT move or shuffle your feet, do not touch ungrounded objects, etc.).
4. If you touch ungrounded objects (and recharge your body with static electricity), firmly touch a clean, unpainted metal
4
Page 5
surface of the furnace again before touching control or wires.
5. Use this procedure for installed and uninstalled (ungroun­ded) furnaces.
6. Before removing a new control from its container, discharge your body’s electrostatic charge to ground to protect the control from damage. If the control is to be installed in a furnace, follow items 1 through 4 before bringing the con­trol or yourself in contact with the furnace. Put all used and new controls into containers before touching ungrounded objects.
7. An ESD service kit (available from commercial sources) mayalsobeusedtopreventESDdamage.
ACCESSORIES
See Product Data Sheet for a list of accessories for this product.
LOCATION
General
These furnaces are shipped with materials to assist in proper furnace installation. These materials are shipped in the main blower compartment. See Table 1 for loose parts bag contents.
This furnace must:
S be installed so the electrical components are protected from
water.
S not be installed directly on any combustiblematerial other than
wood flooring (refer to SAFETY CONSIDERATIONS).
S be located close to the chimney or vent and attached to an air
distribution system. Refer to Air Ducts section.
S be provided ample space for servicing and cleaning. Always
comply with minimum fire protection clearances shown in Tabl e 2 or on the furnace clearance to combustible construction label.
!
CAUTION
PERSONAL INJURY AND/OR PROPERTY DAMAGE HAZARD
Improper use or installation of this furnace may result in premature furnace component failure. This gas furnace may be used for heating buildings under construction provided that:
--The furnace is permanently installed with all electrical wiring, piping, venting and ducting installed according to these installation instructions. A return air duct is provided, sealed to the furnace casing, and terminated outside the space containing the furnace. This prevents a negative pressure condition as created by the circulating air blower, causing a flame rollout and/or drawing combustion products into the structure.
--The furnace is controlled by a thermostat. It may not be “hot wired” to provide heat continuously to the structure without thermostatic control.
--Clean outside air is provided for combustion. This is to minimize the corrosive effects of adhesives, sealers and other construction materials. It also prevents the entrainment of drywall dust into combustion air, which can cause fouling and plugging of furnace components.
--The temperature of the return air to the furnace is maintained between 55_F(13_C) and 80_F(27_C), with no evening setback or shutdown. The use of the furnace while the structure is under construction is deemed to be intermittent operation per our installation instructions.
--The air temperature rise is within the rated rise range on the furnace rating plate, and the gas input rate has been set to the nameplate value.
--The filters used to clean the circulating air during the construction process must be either changed or thoroughly cleaned prior to occupancy.
--The furnace, ductwork and filters are cleaned as necessary to remove drywall dust and construction debris from all HVAC system components after construction is completed.
--Verify proper furnace operating conditions including ignition, gas input rate, air temperature rise, and venting according to these installation instructions.
!
WARNING
CARBON MONOXIDE POISONING / COMPONENT DAMAGE HAZARD
Failure to follow this warning could result in personal injury or death and unit component damage.
Corrosive or contaminated air may cause failure of parts containing flue gas, which could leak into the living space. Air for combustion must not be contaminated by halogen compounds, which include fluoride, chloride, bromide, and iodide. These elements can corrode heat exchangers and shorten furnace life. Air contaminants are found in aerosol sprays, detergents, bleaches, cleaning solvents, salts, air fresheners, and other household products. Do not install furnace in a corrosive or contaminated atmosphere. Make sure all combustion and circulating air requirements are met, in addition to all local codes and ordinances.
The following types of furnace installations may require OUTDOOR AIR for combustion due to chemical exposures:
S Commercial buildings S Buildings with indoor pools S Laundry rooms S Hobby or craft rooms S Chemical storage areas
If air is exposed to the following substances, it should not be used for combustion air, and outdoor air may be required for combustion:
S Permanent wave solutions S Chlorinated waxes and cleaners S Chlorine based swimming pool chemicals S Water softening chemicals S De--icing salts or chemicals S Carbon tetrachloride S Halogen type refrigerants S Cleaning solvents (such as perchloroethylene) S Printing inks, paint removers, varnishes, etc. S Hydrochloric acid S Cements and glues S Antistatic fabric softeners for clothes dryers S Masonry acid washing materials
All fuel--burning equipment must be supplied with air for fuel combustion. Sufficient air must be provided to avoid negative
59MN7A
5
Page 6
pressure in the equipment room or space. A positive seal must be made between the furnace cabinet and the return--air duct to prevent pulling air from the burner area.
!
WARNING
FIRE, INJURY OR DEATH HAZARD
Failure to follow this warning could result in personal injury, death and/or property damage.
When the furnace is installed in a residential garage, the burners and ignition sources must be located at least 18 in. (457 mm) above the floor. The furnace must be located or protected to avoid damage by vehicles. When the furnace is installed in a public garage, airplane hangar, or other building having a hazardous atmosphere, the furnace must be installed in accordance with the NFPA 54/ANSI Z223.1--2009 or CAN/CSA B149.2--2010. See Fig. 5.
59MN7A
Table 1 – Factory--Supplied Installation Parts
DESCRIPTION QUANTITY
AirIntakePipeFlange 1
Vent Pipe Flange 1
Coupling Flange Gaskets 2
Sharp Tip Screws (Vent and Inlet Flanges) 10
Vent Pipe Coupling 1
Vent Pipe Coupling Clamps 2
Rubber Drain Elbow 1
Drain Tube Clamps 4
1 / 2 --- i n . C P V C t o 3 / 4 --- i n . P V C P i p e A d a p t e r 1
Gas Line Grommet 1
Junction Box Cover 1
Junction Box Base 1
Green Ground Screw 1
Blunt Tip Screws (Junction Box) 3
Thermostat Wire Grommet 1
Drain Extension Tube (Z --- pipe) (Provided separately in furnace) 1
!
WARNING
FIRE HAZARD
Failure to follow this warning could result in personal injury, death and/or property damage.
Do not install the furnace on its back or hang furnace with control compartment facing downward. Safety control operation will be adversely affected. Never connect return--air ducts to the back of the furnace. See Fig. 4.
Location Relative to Cooling Equipment
The cooling coil must be installed parallel with, or on the downstream side of the unit to avoid condensation in the heat exchangers. When installed parallel with the furnace, dampers or other flow control must prevent chilled air from entering the furnace. If the dampers are manually operated, they must be equipped with means to prevent operation of either unit unless the damper is in the full--heat or full--cool position.
Table 2 – Minimum Clearances to Combustible Materials for All Units
POSITION CLEARANCE
Rear 0(0mm)
Front (Combustion air openings in furnace and in structure) 1in.(25mm)
Required for service *24 in. (610 mm)
All Sides of Supply Plenum *1 in. (25 mm)
Sides 0(0mm)
Vent 0(0mm)
Top of Furnace 1in. (25mm)
* Consult local building codes.
6
Page 7
29 1/2
[749.3]
28 3/4
[730.5]
[678.1]
26 11/16
26 3/8
[669.9]
[557.4]
21 15/16
21 1/16
[535.8]
20 5/8
[522.7]
AIR FLOW
3
[76.2]
1 3/4
[44.5]
AIR INTAKE
7/8
GAS CONN
[22.2]
E
REV
1
SHT
23 3/8
7/8
[22.2] POWER CONN
4
[63.5]
35
[101.6]
[889.0]
SIDE INLET
28 3/8
[720.4]
[757]
29 13/16
7/8
[22.2]
24
28 5/8
7/8
[22.2]
THERMOSTAT ENTRY
[420.9]
16 9/16
[442.3]
17 7/16
[458.6]
18 1/16
20 1/4
[513.9]
[609.7]
[726.9]
7/8
[22.2]
2 1/2
3
[76.2 ]
21 5/8
[592.0]
[549.5]
BOTTOM INLET
6 1/16
[154.0]
11/16
[17.5]
26 5/16
1 5/16
[33.3]
[668.8]
SD5024-4
2
PART NUMBER
NEXT SHEET
59MN7A
B
A
NOTES:
1. Doors may vary by model.
2. Minimum return-air openings at furnace, based on metal duct. If ex duct is used,
see ex duct manufacturer's recommendations for equivalent diameters.
a. For 800 CFM-16-in. (406 mm) round or 14 1/2 x 12-in. (368 x 305 mm) rectangle.
b. For 1200 CFM-20-in. (508 mm) round or 14 1/2 x 19 1/2-in. (368 x 495 mm) rectangle.
c. For 1600 CFM-22-in. (559 mm) round or 14 1/2 x 22 1/16-in. (368 x 560mm) rectangle.
d. Return air above 1800 CFM at 0.5 in. w.c. ESP on 24.5" casing, requires one of the following
congurations: 2 sides, 1 side and a bottom or bottom only. See Air Delivery table in this
document for specic use to allow for sucient airow to the furnace.
3. Vent and Combustion air pipes through blower compartment must
use accessory “Vent Kit - Through the Cabinet”. See accessory list for
current part number.
D
[58.4]
6 15/16
[176.1]
2 3/10
3
[76.2]
VENT
3
[76.2]
AIR INTAKE
[170.1]
6 11/16
TOP VIEW
[678.1]
26 11/16
26 3/8
[670.0]
25 1/8
[638.7]
23 5/16
[592.9]
20 5/8
[522.7]
19 1/8
OUTLET WIDTH
3
[76.2]
AIR INTAKE
[485.8]
AIR FLOW
5/8
[15.8]
1 3/4
AIR FLOW
[44.5]
GAS CONN
3
[76.2]
VENT
7/8
[22.2]
4
[101.6]
CONDENSATE DRAIN TRAP
LOCATION
7/8
32 5/8
28 3/16
7/8
[22.2] POWER CONN
2 1/2
[63.5]
7/8
[22.2]
[829.5]
[715.9]
[22.2]
28 5/8
[726.4]
23 7/16
SIDE INLET
[639.1]
25 3/16
[595.6]
22 15/16
20 1/4
[513.9]
[420.9]
16 9/16
14 13/16
7/8
[22.2]
THERMOSTAT ENTRY
[581.9]
[439.2]
17 5/16
[376.3]
C
WIDTH
BOTTOM RETURN
NOTE: ALL DIMENSIONS IN INCH [MM]
11/16
[17.5]
SEE NOTE #3
[668.8]
22
26 5/16
21
[534.0]
[558.3] (BOTH SIDES)
[25.4]
1 (BOTH SIDES)
59MN7
FURNACE SIZE
060--- 14 080--- 14 164.0 (73.8)
A B C D
CABINET WIDTH OUTLET WIDTH
17--- 1/2 (445) 15---7/8 (403) 16 (406) 8--- 3/4 (222)
060--- 20 080--- 20 168.5 (76.6)
21 (533) 19--- 3/8 (492) 19--- 1/2 (495) 10--- 1/2 (267) 100--- 22 178.5 (80.3) 120--- 22 24--- 1/2 (622) 22---7/8 (581) 23 (584) 12--- 1/4 (311) 202.5 (91.1)
BOTTOM
INLET WIDTH
Fig. 1 -- Dimensional Drawing
7
AIR INTAKE
SHIP WT.
LB (KG)
154.0 (69.3)
158.5 (72.0)
A12267
Page 8
THE BLOWER IS LOCATED
TO THE RIGHT OF THE
BURNER SECTION, AND
CONDITIONED AIR IS
DISCHARGED TO THE LEFT.
THE BLOWER IS
LOCATED BELOW THE
BURNER SECTION, AND
CONDITIONED AIR IS
DISCHARGED UPWARD.
THE BLOWER IS
LOCATED ABOVE THE
BURNER SECTION, AND
CONDITIONED AIR IS
DISCHARGED DOWNWARD
59MN7A
THE BLOWER IS
LOCATED TO THE LEFT
OF THE BURNER SECTION,
AND CONDITIONED AIR IS
DISCHARGED TO THE RIGHT.
A12181
Fig. 2 -- Multipoise Orientations
80 / 27˚C
SUPPLY AIR
60
/ 16˚C
A10490
Fig. 3 -- Freeze Protection and Return Air Temperature
BACK POSITIONED
DOWNWARD
BACK POSITIONED
UPWARD
Fig. 4 -- Prohibited Installations
AIR RETURN
CUT IN BACK
A12182
18-IN. (457.2 mm)
MINIMUM TO BURNERS
A93044
Fig. 5 -- Installation in a Garage
8
Page 9
AIR FOR COMBUSTION AND
VENTILATION
Introduction
Direct Vent (2--pipe) Applications
When the furnace is installed as a direct vent (2-pipe) furnace, no special provisions for air for combustion are required. However, other gas appliances installed in the space with the furnace may require outside air for combustion. Follow the guidelines below to insure that other gas appliances have sufficient air for combustion.
Ventilated Combustion Air Applications
When the furnace is installed using the ventilated combustion air option, the attic or crawlspace must freely communicate with the outdoor to provide sufficient air for combustion. The combustion air pipe cannot be terminated in attics or crawlspaces that use ventilation fans designed to operate during the heating season. If ventilation fans are present in these areas, the combustion air pipe must terminate outdoors as a Direct Vent/ 2-Pipe system.
All air for combustion is piped directly to the furnace from a space that is well ventilated with outdoor air (such as an attic, crawl space, or equipment closet) and the space is well isolated from the living space or garage. In addition, other gas appliances installed in the space with the furnace may require outside air for combustion. Follow the guidelines below to insure that the roof or crawlspace walls have sufficient free area to provide sufficient air for combustion and ventilation for the furnaces. The guidelines below can be used to insure that other gas appliances have sufficient air for combustion.
Provisions for adequate combustion, ventilation, and dilution air must be provided in accordance with:
S U.S.A. Installations: Section 9.3 of the NFPA 54/ANSI
Z223.1--2009 , Air for Combustion and Ventilation and applicable provisions ofthe local building codes.
S Canada: Part 8 of the CAN/CSA--B149.1--2010, Venting
Systems and Air Supply for Appliances.
Outdoor Combustion Air Method
1. Provide the space with sufficient air for proper combustion, ventilation, and dilution of flue gases using permanent hori­zontal or vertical duct(s) or opening(s) directly communicat­ing with the outdoors or spaces that freely communicate with the outdoors.
2. Fig. 6 illustrates how to provide TWO OUTDOOR OPENINGS, one inlet and one outlet combustion and vent­ilation air opening, to the outdoors.
a. One opening MUST commence within 12 in. (300 mm)
of the ceiling and the second opening MUST commence within 12 in. (300 mm) of the floor.
b. Size openings and ducts per Fig. 6 and Table 3.
c. TWO HORIZONTAL DUCTS require 1 sq.in. (645 sq.
mm) of free areaper 2,000 Btuh (1,100mm binedinputforall gas appliances in the spaceperFig.6 and Tab le 3.
d. TWO OPENINGS OR VERTICAL DUCTS require 1
sq. in. (645 sq. mm) of free area per 4,000 Btuh (550
2
/kW) for combined input of all gas appliances in the
mm space per Fig. 6 and Table 3.
3. ONE OUTDOOR OPENING requires:
a. 1 sq. in. (645 sq. mm) of free area per 3,000 Btuh (734
2
/kW) for combined input of all gas appliances in the
mm space per Fig. 6 and Table 3.
b. Not less than thesum of the areasof all vent connectors in
the space.
The opening shall commence within 12 in. (300 mm) of the ceiling. Appliances in the space shall have clearances of at least 1 in. (25 mm) from the sides and back and 6 in. (150 mm) from the front. The opening shall directly communicate with the outdoors or shall communicate through a vertical or horizontal duct to the outdoors or spaces (crawl or attic) that freely communicate with the outdoors.
2
/kW) of com-
59MN7A
!
CAUTION
FURNACE CORROSION HAZARD
Failure to follow this caution may result in furnace damage. Air for combustion must not be contaminated by halogen
compounds, which include fluoride, chloride, bromide, and iodide. These elements can corrode heat exchangers and shorten furnace life. Air contaminants are found in aerosol sprays, detergents, bleaches, cleaning solvents, salts, air fresheners, and other household products.
!
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury or death.
The operation of exhaust fans, kitchen ventilation fans, clothes dryers, attic exhaust fans or fireplaces could create a NEGATIVE PRESSURE CONDITION at the furnace. Make--up air MUST be provided for the ventilation devices, in addition to that required by the furnace. Refer to the Carbon Monoxide Poisoning Hazard warning in the venting section of these instructions to determine if an adequate amount ofmake--up air is available.
9
Page 10
Table 3 – Minimum Free Area Required for Each Combustion Air Opening or Duct to Outdoors
TWO HORIZONTAL DUCTS
FURNACE
INPUT
(BTUH)
40,000*
60,000
80,000 100,000 120,000
140,000*
*Not all families have these models.
(1 SQ. IN./2,000 BTUH )
(1,100 SQ. MM/KW)
Free Area of
Opening and Du ct
Sq. In (Sq. mm)
20 (12904) 5 (127) 14 (8696) 5 (127) 10 (6452) 4 (102)
30 (19355) 6 (152) 20 (13043) 5 (127) 15 (9678) 5 (127)
40 (25807) 7 (178) 27 (17391) 6 (152) 20 (12904) 5 (127)
50 (32258) 8 (203) 34 (21739) 7 (178) 25 (16130) 6 (152)
60 (38709) 9 (229) 40 (26087) 7 (178) 30 (19355) 6 (152)
70 (45161) 10 (254) 47 (30435) 8 ( 203) 35 (22581) 7 (178)
Round Duct
In. (mm) Dia
FURNACE WATER HEATER TOTAL INPUT
100,000 + 30,000 = (130,000 divided by 4,000) = 32.5 Sq. In. for each two Vertical Ducts or Openings
60,000 + 40,000 = (100,000 divided by 3,000) = 33.3 Sq. In. for each Single Duct or Opening
80,000 + 30,000 = (110,000 divided by 2,000) = 55.0 Sq. In. for each two Horizontal Ducts
Table 4 – Minimum Space Volumes for 100% Combustion, Ventilation and Dilution Air from Outdoors
OTHER THAN FAN-ASSISTED TOTAL
(1,000’S BTUH GAS INPUT RATE)
59MN7A
NP = Not Permitted
ACH
0.60
0.50
0.40
0.30
0.20
0.10
0.00
30 40 50 40 60 80 100 120 140
1,050 (29.7)
1,260 (35.6)
1,575 (44.5)
2,100 (59.4)
3,150 (89.1)
6,300
(178.0)
NP NP NP NP NP NP NP NP NP
1,400 (39.6)
1,680 (47.5)
2,100 (59.4)
2,800 (79.2)
4,200
(118.9)
8,400
(237.8)
1,750
(49.5)
2,100 (59.4)
2,625 (74.3)
3,500 (99.1)
5,250
(148.6)
10,500 (297.3)
SINGLE DUCT OR OPENING
(1 SQ. IN./3,000 BTUH )
(734 SQ. MM/KW)
Free Area of
Opening and Du ct
Sq. In (Sq. mm)
Round Duct
In. (mm) Dia
EXAMPLES: Determining Free Area
FAN-ASSISTED TOTAL
(1,000’S BTUH GAS INPUT RATE)
SpaceVolumeFt3(M3)
1,400 (39.6)
1,680 (47.5)
2,100 (59.4)
2,800 (79.2)
4,200
(118.9)
8,400
(237.8)
1,500 (42.5)
1,800 (51.0)
2,250 (63.7)
3,000 (84.9)
4,500
(127.3)
9,000
(254.6)
2,000
(56.6)
2,400
(67.9)
3,000
(84.9)
4,000
(113.2)
6,000
(169.8)
12,000
(339.5)
TWO OPENINGS OR
VERTICAL DUCTS
(1 SQ. IN./4,000 BTUH )
Free Area of Open-
2,500 (70.8)
3,000 (84.9)
3,750
(106.1)
5,000
(141.5)
7,500
(212.2)
15,000 (424.4)
(550 SQ. MM/KW)
ing and Duct
Sq. In (mm)
3,000 (84.9)
3,600
(101.9)
4,500
(127.3)
6,000
(169.8)
9,000
(254.6)
18,000 (509.2)
Round Duct
In. (mm) Dia.
3,500
(99.1)
4,200
(118.9)
5,250
(148.6)
7,000
(198.1)
10,500 (297.1)
21,000 (594.1)
*Minimum dimensions of 3‐in. (76mm)
NOTE: Use any of the following combinations of openings:
Fig. 6 -- Air for Combustion, Ventilation, and Dilution for Outdoors
A & B, C & D, D & E, F & G
L12F012
10
Page 11
CONDENSATE TRAP
Condensate Trap--Upflow Orientation
When the furnace is installed in the upflow position, it is not necessary to relocate the condensate trap or associated tubing. Refer to Fig. 7 for upflow condensate trap information. Refer to Condensate Drain section for information how to install the condensate drain.
Condensate Trap--Downflow Orientation.
When the furnace is installed in the downflow position, the condensate trap will be initially located at the upper left corner of the collector box, as received from the factory. See the top image in Fig. 8. When the furnace is installed in the downflow orientation, the condensate trap must be relocated for proper condensate drainage. See the bottom image in Fig. 8.
To Relocate the Condensate Trap:
S Orient the furnace in the downflow position. S Fig. 8 shows the condensate trap and tubing before and after
relocation. Refer to Fig. 8 To begin the trap conversion.
S Refer to Condensate Drain section for information how to install
the condensate drain.
Condensate Trap--Horizontal Orientation.
When the furnace is installed in the horizontal right position, the condensate trap will be initially located at the bottom left corner of the collector box, as received from the factory. See the top image in Fig. 9. When the furnace is installed in the horizontal left position, the condensate trap will be initially located at the top of the collector box, as received from the factory. See the top image in Fig. 10. In both cases, the trap must be repositioned on the collector box for proper condensate drainage. See the bottom images in Fig. 9 and 10.
A field--supplied, accessory Horizontal Installation kit (trap grommet) is required for all direct--vent horizontal installations (only). The kit contains a rubber casing grommet designed to seal between the furnace casing and the condensate trap. See Fig. 17.
NOTICE
The field--supplied, accessory horizontal drain trap grommet is ONLY REQUIRED FOR DIRECT VENT APPLICATIONS. It it NOT required for applications using single--pipe or ventilated combustion air venting.
NOTICE
The condensate trap extends below the side of the casing in the horizontal position. A minimum of 2--in. (51 mm) of clearance is required between the casing side and the furnace platform for the trap to extend out of the casing in the horizontal position. Allow at least 1/4--in. per foot (20 mm per meter) of slope down.
To Relocate the Condensate Trap:
S Remove the knockout in the casing for the condensate trap. S Install the grommet in the casing when required for direct--vent
horizontal applications.
S Orient the furnace in the desired position. S Allow for 2 in. (51 mm) of clearance underneath the furnacefor
the condensate trap and drain line.
S Fig. 9 shows the condensate trap and tubing before and after
relocation in the horizontal right position.
S Fig. 10 shows the condensate trap and tubing before and after
relocation in the horizontal left position.
S Refer to the appropriate figure to begin the trap conversion. S Refer to Condensate Drain section for information how to install
the condensate drain.
59MN7A
Collector Box
Plugs
Condensate Trap
Relief Port
Fig. 7 -- Upflow Trap Configuration
Vent Pipe Clamp
Pressure Switch
(Appearance May Vary)
Vent Elbow Clamp
Vent Elbow
Collector Box
Plug
Condensate Trap
Relief Port
Condensate Trap
Outlet
Port
A11306
11
Page 12
Remove relief tube from relief port on condensate trap.
Remove pressure switch tube from pressure switch port.
Remove trap from collector box.
Loosen clamp on inlet to vent elbow.
59MN7A
Remove middle and bottom plugs. DO NOT DISCARD.
7
Install plugs on open ports on collector box.
Connect relief tube to port on collector box.
Remove tube from relief port.
Trim excess tube. Connect pressure switch tube to port on collector box.
Attach condensate trap with screw to collector box.
Rotate elbow to desired position and
9
tighten clamp to 15 lb.-in.
Slide tube in stand-offs to adjust length.
Connect relief tube to relief port on condensate trap.
Align condensate trap over middle and bottom ports of collector box.
A11585
Fig. 8 -- Downflow Trap Configuration
(Appearance May Vary)
12
Page 13
Remove plug from collector box. DO NOT DISCARD.
Unconverted Factory Trap Configuration
As Viewed in the Horizontal Right Orientation
If alternate vent position is required, loosen clamp on inlet of vent elbow.
Remove trap from collector box.
59MN7A
Attach condensate trap to collector box with screw.
Install plug in open port on collector box.
Horizontal Right Trap Configuration
Slide relief tube in stand-offs to adjust length.
Vent elbow shown in alternate orientation. Tighten clamp on inlet to vent elbow 15 lb.-in.
Align trap over middle and right-hand port on collector box.
A11278
Fig. 9 -- Horizontal Right Trap Configuration
(Appearance May Vary)
13
Page 14
If alternate vent position is required, loosen clamp on vent elbow inlet.
Remove trap from collector box.
Remove relief tube from relief port on condensate trap.
Remove pressure switch tube from port on collector box.
59MN7A
Remove relief tube from port on collector box.
Remove middle and right plug from collector box. DO NOT DISCARD
Unconverted Factory Trap Configuration
As Viewed in the Horizontal Left Orientation
Install plugs in open
Rotate elbow to desired position and torque clamp on inlet 15 lb.-in.
Slide relief tube in stand-offs to adjust length.
ports on collector box.
Connect relief tube to port on collector box.
Attach condensate trap to collector box with screw.
Align trap over middle and right-hand port on collector box.
Horizontal Left Trap Configuration
Trim excess tube. Route pressure switch tube underneath relief tube and connect to port on collector box.
Connect relief tube to relief port on condensate trap.
A11586
Fig. 10 -- Horizontal Left Configuration
(Appearance May Vary)
14
Page 15
CONDENSATE DRAIN CONNECTION
!
CAUTION
FROZEN AND BURST WATER PIPE HAZARD
Failure to protect against the risk of freezing may result in property damage.
Special precautions MUST be made if installing furnace in an area which may drop below freezing. This can cause improper operation or damage to equipment. If furnace environment has the potential of freezing, the drain trap and drain line must be protected. The use of accessory drain trap heaters, electric heat tape and/or RV antifreeze is recommended for these installations.
!
CAUTION
PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in burst water pipes and/or property damage.
If a condensate pump is installed, a plugged condensate drain or a failed pump may cause the furnace to shut down. Do not leave the home unattended during freezing weather without turning off water supply and draining water pipes or otherwise protecting against the risk of frozen pipes.
DO NOT trap the drain line in any other location than at the condensate drain trap supplied with the furnace. If possible, DO NOT route the drain line where it may freeze. The drain line must terminate at an inside drain to prevent freezing of the condensate and possible property damage.
Special precautions MUST be made if installing furnace in an area which may drop below freezing. This can cause improper operation or damage to the equipment. If the furnace environment has the potential of freezing, the drain trap and drain line must be protected. A self--regulating, shielded and waterproof heat tape rated at 3 to 6 watt per foot (10 to 20 watt per meter) at 115 volt, 40_F(4_C) may be used to help provide freeze protection. Wrap the drain trap and drain line with the heat tape and secure with appropriate plastic ties. Follow the heat tape manufacturer’s recommendations. Prime the trap before furnace operation.
Upflow/Downflow Orientation
In the Upflow or Downflow orientation, the condensate trap is inside the furnace casing. The condensate drain must be routed from the trap through the furnace casing. The condensate drain can be routed through the left or right side of the casing. (The left or right side is as you are viewing/facing the furnace from the front.) The furnace condensate drain can be connected to the indoor coil condensate drain, humidifier or auxiliary drain traps as shown in Fig. 12.
NOTE: On narrower casings, it may be easier to remove the condensate trap, connect the drain line components and re-install the condensate trap. Read the steps thoroughly to familiarize yourself with the required steps.
For Right Side Condensate Drain:
1. Remove the 7/8--in. knock--out from the right side of the casing. See Fig. 11 for suggested knockout removal tech­nique.
2. Remove the pre--formed rubber drain elbow and two spring clamps from the loose parts bag.
3. Slide a spring clamp 1--in. (25 mm) down the plain end (the end without the formed grommet) of the drain elbow.
4. From inside the casing, insert the formed grommet end of the elbow through the 7/8--in. knockout in the casing.
5. Pull the grommet through the casing from the outside until it is seated in the knockout
6. Attach the plain end of the drain elbow to the outlet stub on the drain trap. Secure the drain elbow to the trap with the spring clamp.
The remaining drain line can be constructed from field supplied 1/2--in. CPVC or 3/4--in. PVC pipe, in compliance with local building codes. A factory--supplied 1/2--in. CPVC to 3/4--in. PVC adapter is supplied in the loose parts bag for use as required.
7. Install the adapter or connect the 1/2--in. CPVC pipe by sliding a spring clamp over the open end of the grommet on the outside the furnace casing.
8. Open the spring clamp and insert the long end of the adapter or the 1/2--in. CPVC pipe into the outlet stub on the drain tube.
9. Connect additional condensate piping to a code--approved drain, or to a condensate pump approved for use with acidic furnace condensate and compatible with mineral and vegetable oils, such as canola oil.
Allow at least 1/4-in. per foot (20 mm per meter) of slope down and away from the furnace in horizontal sections of drain line.
TIP FROM CONTRACTORS: Contractors have found that temporarily removing the inducer assembly in upflow applications while performing the steps, below, makes upflow left--side drain connections easier.
For Left Side Condensate Drain Connection:
1. For left side condensate drainage, the drain line is routed from the condensate trap, behind the inducer (upflow) or gas valve (downflow) and out through the left side of the furnace casing. A pre-formed 1/2--in. CPVC “Z-pipe” is provided with the furnace. The Z-pipe is long enough to extend across the casing for drain connections.
2. Locate the Z-pipe. Remove the pre-formed drain elbow and four spring clamps from the loose parts bag.
3. The Z-pipe is connected to the condensate trap and the outside of the furnace by modifying the formed rubber drain elbow as shown in Fig. 14.
4. Remove the formed grommet from the rubber drain elbow by cutting the elbow along the vertical line located about 1--3/8 in. (35 mm) away from the formed grommet. See Fig.
14. DO NOT DISCARD THE FORMED GROMMET OR THE RUBBER ELBOW. Both of these pieces will be used.
Assemble and route the drain line to the opposite side of the furnace as detailed below:
5. Remove the knock-out from the left side of the casing. See Fig. 11 for suggested knockout removal technique.
6. From the outside of the casing, insert the angled end of the Z-pipe through drain hole in the left side of the casing and behind the inducer or gas valve. Allow the Z-pipe to temporarily rest on the blower shelf (upflow) or burner box (downflow). (NOTE: When the inducer housing has been removed to ease installation in upflow applications, this step is not needed.)
7. After inserting the Z--pipe through the casing, slide a spring clamp over each end of the Z--pipe.
8. From inside the casing, insert the short end of the formed grommet cut from the rubber drain elbow through the 7/8-in. drain knockout in the casing.
9. Pull the grommet through the casing from the outside until it is seated in the knockout.
10. Align the Z-pipe with the long end of the grommet inside the furnace and insert slightly. The angled end of the tube at
59MN7A
15
Page 16
the other side of the casing should be facing the front of the furnace.
11. Slide a spring clamp over the end of the remaining rubber drain elbow.
12. Attach the drain elbow to the angled end of Z-pipe and the drain trap outlet stub. Adjust the length of Z-pipe inserted into the grommet at the opposite side of the furnace as necessary for proper fit and positioning. In both upflow and downflow orientations, the Z-pipe should NOT be resting on any sheet metal parts.
13. Secure the rubber elbow to the drain trap and the Z-pipe with spring clamps.
14. Secure the grommet to the Z-pipe with the spring clamp.
The remaining drain line can be constructed from field supplied 1/2--in. CPVC or 3/4--in. PVC pipe, in compliance with local building codes. A factory-supplied 1/2--in. CPVC to 3/4--in. PVC adapter is supplied in the loose parts bag for use as required.
15. Install the adapter or connect the 1/2--in. CPVC pipe by sliding a spring clamp over the open end of the grommet on the outside the furnace casing.
16. Open the spring clamp and insert the long end of the
59MN7A
adapter or the 1/2--in. CPVC pipe into the outlet stub on the drain tube.
17. Connect additional condensate piping to a code-approved drain, or to a condensate pump approved for use with acidic furnace condensate and compatible with mineral and vegetable oils, such as canola oil.
Allow at least 1/4-in. per foot (20 mm per meter) of slope down and away from the furnace in horizontal sections of drain line.
7. The remaining drain line can be constructed from field-­supplied 1/2--in. CPVC or 3/4--in. PVC pipe, in compliance with local building codes. A factory--supplied 1/2--in. CPVC to 3/4--in. PVC adapter is supplied in the loose parts bag for use as required.
8. Install the adapter or connect the 1/2--in. CPVC pipe by sliding a spring clamp over the open end of the elbow or grommet on the outside the furnace casing.
9. Open the spring clamp and insert the long end of the adapter or the 1/2--in. CPVC pipe into the outlet stub on the drain tube.
10. Connect additional condensate piping to a code--approved drain, or to a condensate pump approved for use with acidic furnace condensate and compatible with mineral and vegetable oils, such as canola oil.
Allow at least 1/4-in. per foot (20 mm per meter) of slope down and away from the furnace in horizontal sections of drain line.
NOTICE
The field--supplied, accessory horizontal drain trap grommet is ONLY REQUIRED FOR DIRECT VENT APPLICATIONS. It is NOT required for applications using single--pipe or ventilated combustion air venting.
TIP FROM CONTRACTORS: When installing the furnace horizontally, use the entire drain elbow (that is, do NOT cut as shown in Fig. 14 to connect the trap to the drain line. This helps to prevent bumps and shocks to the drain line from damaging the furnace drain trap. Avoid misalignment of the drain pipe which may cause kinks in the elbow.
Horizontal Orientation
1. The condensate trap outlet extends 2--in. (51 mm) below the furnace casing. Leave enough clearance between the furnace and the furnace platform for the trap.
2. To allow for servicing the trap, the condensate drain elbow in the loose parts bag can be used to make a coupler to allow for future service of the condensate trap and drain line.
3. Remove the knock-out for the condensate trap in the side of the casing.
4. Install the drain trap grommet in the casing if required for direct--vent applications. If necessary, remove the trap, install the grommet and re-install the trap.
5. Remove the pre-formed rubber drain elbow, and two spring clamps from the loose parts bag.
6. Connect the full or modified elbow and/or grommet to the outlet of the condensate trap with one spring clamp. Avoid misalignment of the drain pipe which may cause kinks in the elbow or grommet.
!
CAUTION
CUT HAZARD
Failure to follow this caution may result in personal injury. Sheet metal parts may have sharp edges or burrs. Use care
and wear appropriate protective clothing, safety glasses and gloves when handling parts, and servicing furnaces.
L12F019B
Fig. 11 -- Knockout Removal
OPEN STAND PIPE FOR A/C OR HUMIDIFIER DRAIN
TEE
TO OPEN DRAIN
Fig. 12 -- Example of Field Drain Attachment
A11276
16
Page 17
INSTALL CLAMPS ON DRAIN TUBE ATTACH DRAIN TUBE TO CONDENSATE DRAIN TRAP
PULL DRAIN STUB THROUGH CASING
OPEN SPRING CLAMP
INSERT FACTORYïSUPPLIED 1/2ïIN. CPVC TO 3/4ïIN. PVC ADAPTER OR 1/2ïIN. CPVC PIPE
*CLAMP MAY BE LOCATED ON OUTSIDE OF DRAIN TUBE
NOTE: Trap grommet is required only for direct-vent applications.
Remove knockout. Install grommet before relocating condensate trap.
59MN7A
Fig. 13 -- Formed Rubber Drain Grommet
A11342A
Fig. 15 -- Horizontal Drain Trap Grommet
Attach elbow to condensate trap
Cut formed end off
Formed end of grommet
Factory supplied 1/2ïin. CPVC to 3/4ïin. PVC adapter
TRAP, DRAIN ELBOW WITH DISCHARGE PIPE
Formed end of grommet Open spring clamp. Insert 1/2ïin. to 3/4ïin. CPVC to PVC adapter or 1/2ïin. CPVC pipe
condensate drain elbow
Connect short end of “Z” pipe to modified drain elbow
A11582
s
Modified drain elbow connect to condensate trap and “Z” pipe
Fig. 14 -- Modify Rubber Drain Elbow
A11581
NOTE: Remove Inducer Housing for easier access, if desired.
LEFT SIDE DRAIN ROUTED BEHIND INDUCER
L12F015
Fig. 16 -- Drain Trap Connection and Routing
(Appearance may vary)
17
Page 18
INSTALLATION
NOTICE
This furnace is certified to leak 2% or less of nominal air conditioning CFM delivered when pressurized to 1--in. water column with all present air inlets, including bottom closure in upflow and horizontal applications, air outlets, and plumbing and electrical ports sealed.
Upflow Installation
NOTE: The furnace must be pitched as shown in Fig. 22 for
proper condensate drainage.
Supply Air Connections
For a furnace not equipped with a cooling coil, the outlet duct shall be provided with a removable access panel. This opening shall be accessible when the furnace is installed and shall be of such a size that the heat exchanger can be viewed for possible openings using light assistance or a probe can be inserted for sampling the air stream. The cover attachment shall prevent leaks.
59MN7A
Connect supply--air duct to flanges on furnace supply--air outlet. Bend flange upward to 90_ with wide duct pliers. See Fig. 19. The supply--air duct must be connected to ONLY the furnace supply--outlet--air duct flanges or air conditioning coil casing (when used). DO NOT cut main furnace casing side to attach supply air duct, humidifier, or other accessories. All supply--side accessories MUST be connected to duct external to furnace main casing.
Return Air Connections
!
WARNING
FIRE HAZARD
A failure to follow this warning could cause personal injury, death and/or property damage.
Never connect return--air ducts to the back of the furnace. Follow instructions below.
The return--air duct must be connected to bottom, sides (left or right), or a combination of bottom and side(s) of main furnace casing. Bypass humidifier may be attached into unused return air side of the furnace casing. See Fig. 23, 24, 25.
Bottom Return Air Inlet
These furnaces are shipped with bottom closure panel installed in bottom return--air opening. Remove this panel when bottom return air is used. This panel may be used as the bottom closure of an accessory bottom return air box, or discarded. To remove bottom closure panel, perform the following:
1. Tilt or raise furnace and remove 4 screws holding bottom plate. See Fig. 21.
2. Remove bottom plate.
3. Remove bottom closure panel.
4. Reinstall bottom plate and screws.
Side Return Air Inlet
These furnaces are shipped with bottom closure panel installed in bottom return--air opening. This panel MUST be in place when only side return air is used.
NOTE: Side return--air openings can be used in UPFLOW and some HORIZONTAL configurations. Do not use side return--air openings in DOWNFLOW configuration. See Fig. 23, 24, and
25.
Leveling Legs (If Desired)
In upflow position with side return inlet(s), leveling legs may be used. See Fig. 20. Install field--supplied, 5/16 x 1--1/2 in. (8 x 38 mm) (max) corrosion--resistant machine bolts, washers and nuts.
NOTE: Bottom closure must be used when leveling legs are used. It may be necessary to remove and reinstall bottom closure panel to install leveling legs. To remove bottom closure panel, see Item 1 in Bottom Return Air Inlet section in Step 1 above.
To install leveling legs:
1. Position furnace on its back. Locate and drill a hole in each bottom corner of furnace.
2. For each leg, install nut on bolt and then install bolt with nut in hole. (Install flat washer if desired.)
3. Install another nut on other side of furnace base. (Install flat washer if desired.)
4. Adjust outside nut to provide desired height, and tighten in­side nut to secure arrangement.
5. Reinstall bottom closure panel if removed.
Downflow Installation
NOTE: The furnace must be pitched as shown in Fig. 22 for
proper condensate drainage.
Supply Air Connections
NOTE: For downflow applications, this furnace is approved for
use on combustible flooring when any one of the following 3 accessories are used:
S Special Base, KGASB S Cased Coil Assembly Part No. CNPV, CNRV, CAP, or CAR S Coil Box Part No. KCAKC
1. Determine application being installed from Table 8.
2. Construct hole in floor per Table 8 and Fig. 18.
3. Construct plenum to dimensions specified in Table 8 and Fig. 18.
4. Install special base coil assembly or coil box as shown in in Fig. 18.
NOTE: It is recommended that the perforated supply--air duct flanges be completely removed from furnace when installing the furnace on a factory--supplied cased coil or coil box. To remove the supply--air duct flange, use wide duct pliers or hand seamers to bend flange back and forth until it breaks off. Be careful of sharp edges. See Fig. 19.
!
CAUTION
CUT HAZARD
Failure to follow this caution may result in personal injury. Sheet metal parts may have sharp edges or burrs. Use care
and wear appropriate protective clothing, safety glasses and gloves when handling parts, and servicing furnaces.
Connect supply--air duct to supply--air outlet on furnace. Bend flange inward past 90_ with wide duct pliers. See Fig. 19. The supply--air duct must be connected to ONLY the furnace supply outlet or air conditioning coil casing (when used). When installed on combustible material, supply--air duct must be connected to ONLY the factory--approved accessory subbase, or a factory--approved air conditioning coil casing. DO NOT cut main furnace casing to attach supply side air duct, humidifier, or other accessories. All supply--side accessories MUST be connected to duct external to furnace casing.
18
Page 19
Return Air Connections
!
WARNING
FIRE HAZARD
A failure to follow this warning could cause personal injury, death and/or property damage.
Never connect return--air ducts to the back of the furnace. Follow instructions below.
The return--air duct must be connected to return--air opening (bottom inlet). DO NOT cut into casing sides (left or right). Bypass humidifier connections should be made at ductwork or coil casing sides exterior to furnace. See Fig. 24.
Bottom Return Air Inlet
These furnaces are shipped with bottom closure panel installed in bottom return--air opening. Remove and discard this panel when bottom return air is used in downflow applications. To remove bottom closure panel, perform the following:
1. Tilt or raise furnace and remove 4 screws holding bottom plate. See Fig. 21.
2. Remove bottom plate.
3. Remove bottom closure panel.
4. Reinstall bottom plate and screws.
Horizontal Installation
NOTE: The furnace must be pitched forward as shown in Fig. 22
for proper condensate drainage.
!
WARNING
FIRE, EXPLOSION, AND CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury, death, or property damage.
Do not install the furnace on its back or hang furnace with control compartment facing downward. Safety control operation will be adversely affected. Never connect return--air ducts to the back of the furnace.
!
CAUTION
MINOR PROPERTY HAZARD
Failure to follow this caution may result in minor property damage.
Local codes may require a drain pan under entire furnace and condensate trap when a condensing furnace is used in an attic application or over a finished ceiling.
The furnace can be installed horizontally in an attic or crawlspace on either the left--hand (LH) or right--hand (RH) side. The furnace can be hung from floor joists, rafters or trusses or installed on a non--combustible platform, blocks, bricks or pad.
Platform Furnace Support
Construct working platform at location where all required furnace clearances are met. See Table 2 and Fig. 26.) For furnaces with 1--in. (25 mm) clearance requirement on side, set furnace on non--combustible blocks, bricks or angle iron. For crawlspace installations, if the furnace is not suspended from the floor joists, the ground underneath furnace must be level and the furnace set on blocks or bricks.
Suspended Furnace Support
The furnace must be supported under the entire length of the furnace with threaded rod and angle iron. See Fig. 27. Secure angle iron to bottom of furnace as shown.
Roll--Out Protection
Provide a minimum 12--in. x 22--in. (305 x 559 mm) piece of sheet metal for flame roll--out protection in front of burner area for furnaces closer than 12--in. (305 mm) above the combustible deck or suspended furnaces closer than 12--in. (305 mm) to joists. The sheet metal MUST extend underneath the furnace casing by 1--in. (25 mm) with the door removed.
The bottom closure panel on furnaces of widths 17--1/2--in. (445 mm) and larger may be used for flame roll--out protection when bottom of furnace is used for return air connection. See Fig. 26 for proper orientation of roll--out shield.
Supply Air Connections
For a furnace not equipped with a cooling coil, the outlet duct shall be provided with a removable access panel. This opening shall be accessible when the furnace is installed and shall be of such a size that the heat exchanger can be viewed for possible openings using light assistance or a probe can be inserted for sampling the air stream. The cover attachment shall prevent leaks.
Connect supply--air duct to flanges on furnace supply--air outlet. Bend flange upward to 90_ with wide duct pliers. See Fig. 19. The supply--air duct must be connected to ONLY the furnace supply--outlet--air duct flanges or air conditioning coil casing (when used). DO NOT cut main furnace casing side to attach supply air duct, humidifier, or other accessories. All accessories MUST be connected to duct external to furnace main casing.
Return Air Connections
The return--air duct may be connected to bottom of the furnace. The side of casing that faces downward may also be used for return air connection. A combination of the bottom and downward facing side may also be used. The upward facing side of the casing cannot be used as a return air connection. See Fig. 25.
Bottom Return Air Inlet
These furnaces are shipped with bottom closure panel installed in bottom return--air opening. Remove this panel when bottom return air is used. This panel may be used as a roll--out shield or discard. To remove bottom closure panel, perform the following:
1. Tilt or raise furnace and remove 4 screws holding bottom plate. See Fig. 21.
2. Remove bottom plate.
3. Remove bottom closure panel.
4. Reinstall bottom plate and screws.
Side Return Air Inlet
These furnaces are shipped with bottom closure panel installed in bottom return--air opening. This panel MUST be in place when side return air inlet(s) are used without a bottom return air inlet.
Not all horizontal furnaces are approved for side return air connections. See Fig. 25.
Filter Arrangement
!
WARNING
FIRE, CARBON MONOXIDE AND POISONING HAZARD
Failure to follow this warning could result in fire, personal injury or death.
Never operate a furnace without a filter or filtration device installed. Never operate a furnace with filter or filtration device access doors removed.
59MN7A
19
Page 20
There are no provisions for an internal filter rack in these furnaces. An external filter is required.
The furnace is shipped with a factory-supplied Media Filter Cabinet. The Media Filter Cabinet uses either a standard 1--in. (25 mm) filter or 4--in. (102 mm) wide Media Filter which can be purchased separately. A field supplied accessory air cleaner may also be used in place of the media cabinet.
The Media Cabinet is sized for bottom return applications for use in upflow, downflow and horizontal applications. A 16--inch (406 mm) Media Cabinet is shipped with the 14--3/16-in. (360 mm) furnace and includes block-off plates.
For upflow side return applications, the Media Cabinet (or field supplied accessory air cleaner) can be installed on the side of the furnace or side and bottom when a bottom plenum is used. See Fig. 17 and 23.
For downflow applications, the Media Cabinet (or field supplied accessory air cleaner) must only be connected to the bottom opening on the furnace. See Fig. 17 and 24.
For horizontal applications, the Media Cabinet (or field supplied accessory air cleaner) for all models can be connected to the bottom opening on the furnace. For side return use in the horizontal position, refer to Fig. 25. If both side and bottom
59MN7A
openings are used in Fig. 25, each opening used will require a filter.
The media cabinet (or field supplied accessory air cleaner) can also be installed in the common return duct prior to entering the return air opening in any orientation.
Refer to the instructions supplied with Media Cabinet or accessory air filter for assembly and other details. See Table 7 for filter size details.
Filter and Return Duct Sizing
Pressure drop must be taken into account when sizing filters, filter racks, IAQ devices, and associated system ductwork. See Table 5 for a comparison of Pressure Drop (initial/clean resistance to airflow) versus Airflow for a variety of filter media types and sizes. These are representative numbers. Consult the filter or IAQ device manufacturers’ specification sheet for performance data for a particular filter media or IAQ device.
Design the filter and associated ductwork for the best match of pressure drop versus filter size. Best practice usually chooses filter systems with pressure drops under 0.2 in. W.C. (50 Pa), with the best blower electrical efficiency and system airflow performance occurring with filter pressure drops under 0.1 in. W.C. (25 Pa).
NOTICE
Design the duct system FIRST to determine how much pressure drop may be allowed in the filter system. See the Air Ducts section. Excessive filter pressure drop often compromises system airflow and duct performance, causes inadequate airflow to the furthest ends of the duct system, as well as causes excess noise and higher than anticipated electrical consumption.
Provide duct transitions, as required, to smoothly transition airflow from the return duct system to the filter (or IAQ device) to the furnace when the dimensions of the ductwork or furnace return air opening do not match the required filter or IAQ device dimensions. See the instructions supplied with factory--accessory duct adapters.
20
Page 21
Table 5 – Filter Media Pressure Drop (Clean) Versus Airflow -- In. W.C. (Pa)
14 x 25 Filter
(356 x 635 mm)
CFM L/s (1-in. / 2.5 cm) (4-in. / 10 cm) (1-in. / 2.5 cm) (2-in. / 5 cm) (1-in. / 2.5 cm) (2-in. / 5 cm)
600 (283) 0.04 (12) 0.05 (12) 0.07 (17) 0.10 (26) 0.24 (60) 0.16 (40)
800 (378) 0.06 (15) 0.07 (19) 0.10 (25) 0.15 (39) 0.34 (85) 0.23 (59) 1000 (472) 0.07 (18) 0.10 (27) 0.13 (34) 0.21 (52) - - 0.32 (81) 1200 (566) 0.08 (20) 0.14 (36) 0.17 (43) 0.27 (68) - - - -
Factory-Accessory
Washable
Factory-Accessory
Media*
Representative After-Market Filter Media*
Fiberglass* Pleated*
16 x 25 Filter
(406 x 635 mm)
CFM L/s (1-in. / 2.5 cm) (4-in. / 10 cm) (1-in. / 2.5 cm) (2-in. / 5 cm) (1-in. / 2.5 cm) (2-in. / 5 cm)
600 (283) 0.04 (10) 0.05 (13) 0.06 (15) 0.09 (22) 0.20 (51) 0.13 (34)
800 (378) 0.05 (13) 0.07 (18) 0.08 (21) 0.13 (32) 0.29 (72) 0.20 (49) 1000 (472) 0.06 (16) 0.11 (28) 0.11 (28) 0.17 (43) - - 0.27 (67) 1200 (566) 0.07 (18) 0.15 (37) 0.14 (36) 0.22 (56) - - - ­1400 (661) 0.08 (21) 0.19 (48) 0.18 (45) 0.28 (70) - - - ­1600 (755) 0.09 (23) 0.24 (60) 0.21 (54) - - - - - ­1800 (850) 0.10 (25) - - 0.26 (64) - - - - - -
20 x 25 Filter
(508 x 635 mm)
CFM (L/s) (1-in. / 2.5 cm) (4-in. / 10 cm) (1-in. / 2.5 cm) (2-in. / 5 cm) (1-in. / 2.5 cm) (2-in. / 5 cm)
800 (378) 0.04 (11) 0.05 (12) 0.06 (16) 0.09 (24) 0.22 (55) 0.15 (37) 1000 (472) 0.05 (13) 0.07 (18) 0.08 (21) 0.13 (32) 0.29 (72) 0.20 (49) 1200 (566) 0.06 (15) 0.09 (22) 0.11 (27) 0.16 (41) - - 0.25 (63) 1400 (661) 0.07 (17) 0.12 (31) 0.13 (33) 0.20 (51) - - 0.31 (79) 1600 (755) 0.08 (19) 0.15 (38) 0.16 (40) 0.24 (61) - - - ­1800 (850) 0.08 (21) 0.18 (47) 0.18 (47) 0.29 (73) - - - ­2000 (944) 0.09 (23) 0.22 (56) 0.21 (54) - - - - - ­2200 (1038) 0.09 (24) 0.26 (66) 0.25 (62) - - - - - -
25 x 25 Filter
(635 x 635 mm)
CFM L/s (1-in. / 2.5 cm) (4-in. / 10 cm) (1-in. / 2.5 cm) (2-in. / 5 cm) (1-in. / 2.5 cm) (2-in. / 5 cm)
800 (378) 0.03 (9) 0.03 (8) 0.05 (12) 0.07 (18) 0.17 (43) 0.11 (28) 1000 (472) 0.04 (11) 0.05 (12) 0.06 (16) 0.09 (24) 0.22 (55) 0.15 (37) 1200 (566) 0.05 (13) 0.07 (17) 0.08 (20) 0.12 (31) 0.27 (68) 0.18 (47) 1400 (661) 0.06 (15) 0.09 (23) 0.10 (24) 0.15 (38) - - 0.23 (58) 1600 (755) 0.06 (16) 0.12 (31) 0.11 (29) 0.18 (45) - - 0.28 (69) 1800 (850) 0.07 (18) 0.14 (35) 0.13 (34) 0.21 (53) - - - ­2000 (944) 0.08 (19) 0.16 (41) 0.16 (39) 0.24 (61) - - - ­2200 (1038) 0.08 (21) 0.19 (49) 0.18 (45) 0.28 (70) - - - -
Factory-Accessory
Washable
Factory-Accessory
Washable
Factory-Accessory
Washable
Factory-Accessory
Media*
Factory-Accessory
Media*
Factory-Accessory
Media*
Representative After-Market Filter Media*
Fiberglass* Pleated*
Representative After-Market Filter Media*
Fiberglass* Pleated*
Representative After-Market Filter Media*
Fiberglass* Pleated*
59MN7A
If the filter size that you are looking for is not contained in Table 5, refer to Table 6 for a comparison of Pressure Drop (initial/clean resistance to airflow) versus Face Velocity for a variety of filter media types.
The following equations relate Face Velocity (FPM), Filter Area and Airflow (CFM):
Filter Face Velocity = Airflow / Filter Area Minimum Filter Area = Rated System Airflow / Maximum Filter Face Velocity
Table 6 – Filter Media Pressure Drop (Clean) Versus Face Velocity-- In. W.C. (Pa)
Face Velocity
FPM (m/s) (1-in. / 2.5 cm) (1-in. / 2.5 cm) (2-in. / 5 cm) (1-in. / 2.5 cm) (2-in. / 5 cm)
200 (1) 0.04 (10) 0.05 (13) 0.08 (20) 0.18 (47) 0.12 (31) 300 (1.5) 0.05 (14) 0.09 (22) 0.13 (34) 0.30 (75) 0.21 (52) 400 (2) 0.07 (17) 0.13 (32) 0.20 (50) - - 0.31 (78) 500 (2.5) 0.08 (21) 0.18 (44) 0.27 (69) - - - ­600 (3) 0.09 (23) 0.23 - - - - - - ­700 (3.6) 0.10 (26) 0.29 - - - - - - -
Factory-Accessory
Washable
Representative After-Market Filter Media*
Fiberglass* Pleated*
21
Page 22
Table 7 – AirFilter Selection and Duct Sizing -- In. (mm)
FURNACE CASING WIDTH
17 --- 1/2 (445)
21 (533)
24 --- 1/2 (622)
* Recommended to maintain air filter face velocity. See Product Data for part number.
SIDE RETURN BOTTOM RETURN
16 x 25 x 3/4
(406 x 635 x 19)
16 x 25 x 3/4
(406 x 635 x 19)
16 x 25 x 3/4
(406 x 635 x 19)
FILTER SIZE
Air Filter Located in Filter Cabinet
FILTER CABINET HEIGHT --- IN (MM) F I L T E R S I Z E --- I N ( M M ) FILTER TYPE
(1) 16 x 25 x 3/4*
16 (406)
20 (508)
59MN7A
24 (610)
* Filters with a side return---air may have a different filter size. Measure the filter to obtain the correct size. * Recommended to maintain air filter face velocity. See Product Data for part number.
(406 x 635 x 19) or
(1) 16 x 25 x 4--- 5/16
(406 x 635 x 110)
(1) 20 x 25 x 3/4*
(508 x 635 x 19) or
(1) 20 x 25 x 4--- 5/16
(508 x 635 x 110)
(1) 24 x 25 x 3/4*or
(610 x 635 x 19) or
(1) 24 x 25 x 4--- 5/16
(610 x 635 x 110)
16 x 25 x 3/4
(406 x 635 x 19)
20 x 25 x 3/4
(508 x 635 x 19)
24 x 25 x 3/4
(610 x 635 x 19)
FILTER TYPE
Washable*
Washable*
Washable*
Washable or Media*
Washable or Media*
Washable or Media*
22
Page 23
14-3/16 and 17-1/2-in.
Furnace
21-in. Furnace
4-Ton or less, AC
capacity airflow
4-in. Block Off Plate
Screws
1/2-in.
16-in. Media Cabinet
Media Cabinet Installation
Side Return
21- or 24-1/2-in.
Furnace
Up to 5-Ton AC
capacity airflow
20- or 24-in. Media
Cabinet
Bottom Return Plenum
20- or -24-in. Media Cabinet Installation
for Combination Side and Bottom Return
20-in. Media Cabinet
Media Cabinet Installation Option for
4-Ton or Less A/C Capacity
59MN7A
21-in. Furnace up to 5-Ton AC Capacity
24-1/2-in. Furnace up to 4-Ton AC Capacity
45°
Transition
20- or 24-in. Media Cabinet
20- or -24-in. Media Cabinet Installation
with Angled Transition
14-3/16-in. Furnace
Screw
Filler plates
14--3/16-in. Furnace with Filler Plates, Centered
14-3/16-in. Furnace
Screws
Screw
Filler plate
14--3/16-in. Furnace with Filler Plates, Off-- Set to Right
A11437
Fig. 17 -- Media Filter
23
Page 24
FURNACE
(OR COIL CASING
WHEN USED)
FURNACE
APPROVED
COIL ASSEMBLY
OR
COIL BOX
A
PLENUM
OPENING
B
C
FLOOR
OPENING
COMBUSTIBLE
FLOORING
D
DOWNFLOW
SUBBASE
SHEET METAL
PLENUM
FLOOR
OPENING
COMBUSTIBLE
FLOORING
SHEET METAL
PLENUM
FLOOR
OPENING
A10491
Fig. 18 -- Installation on Combustible Flooring
59MN7A
Table 8 – Opening Dimensions -- In. (mm)
FURNACE
CASING
WIDTH
IN. (mm)
17–1/2
(445)
21
(533)
24 --- 1/2
(622)
APPLICATION
Upflow Applications on Combustible or Noncombustible Floor-
Downflow Applications on Noncombustible Flooring (KGASB
Downflow applications on combustible flooring (KGASB sub-
Downflow Applications on Combustible Flooring with CNPV,
CNRV, CAR or CAP Coil Assembly or KCAKC coil box (KGASB
ing (KGASB subbase not required)
subbase not required)
base required)
subbase not required)
Upflow Applications on Combustible or Noncombustible Floor-
Downflow Applications on Noncombustible Flooring (KGASB
Downflow applications on combustible flooring (KGASB sub-
Downflow Applications on Combustible Flooring with CNPV,
CNRV, CAR or CAP Coil Assembly or KCAKC coil box (KGASB
ing (KGASB subbase not required)
subbase not required)
base required)
subbase not required)
Upflow Applications on Combustible or Noncombustible Floor-
Downflow Applications on Noncombustible Flooring (KGASB
Downflow applications on Combustible flooring (KGASB sub-
Downflow Applications on Combustible Flooring with CNPV,
CNRV, CAR or CAP Coil Assembly or KCAKC coil box (KGASB
ing (KGASB subbase not required)
subbase not required)
base required)
subbase not required)
PLENUM OPENING FLOOR OPENING
A B C D
16
(406)
15--- 7/8
(403)
15--- 1/8
(384)
15--- 1/2
(394)
19--- 1/2
(495)
19--- 3/8
(492)
18--- 5/8
(473)
19
(483)
23
(584)
22--- 7/8
(581)
22--- 1/8
(562)
22--- 1/2
(572)
21--- 5/8
(549)
19
(483)
19
(483)
19
(483)
21--- 5/8
(549)
19
(483)
19
(483)
19
(483)
21--- 1/8
(537)
19
(483)
19
(483)
19
(483)
16--- 5/8
(422)
16--- 1/2
(419)
16--- 3/4
(425)
16--- 1/2
(419)
20--- 1/8
(511)
20
(508)
20--- 1/4
(514)
20
(508)
23--- 5/8
(600)
23--- 1/2
(597)
23--- 3/4
(603)
23--- 1/2
(597)
22--- 1/4
(565)
19--- 5/8
(498)
20--- 5/8
(600)
(508)
22--- 1/4
(565)
19--- 5/8
(498)
20--- 5/8
(600)
(508)
22--- 1/4
(565)
19--- 5/8
(498)
20--- 5/8
(600)
(508)
20
20
20
24
Page 25
PERFORATED DISCHARGE DUCT FLANGE
UPFLOW DOWNFLOW HORIZONTAL
90°
90°
5/
(8mm)
(44mm)
16
″
1 3 / 4 ″
(8mm)
5/
16
″
3
/ 4 ″
1 (44mm)
120°
MIN
YES
YES
NO
Fig. 19 -- Duct Flanges
120°
MIN
YES
YES
NO
120°
MIN
YES
YES
NO
A10493
59MN7A
(8mm)
5
/
16
″
1
(44mm)
3/
4 ″
3/
1
4 ″
(44mm)
Fig. 20 -- Leveling Legs
LEVEL 0-IN. (0 MM) TO 1/2-IN. (13 MM) MAX
(8mm)
5/
16
″
UPFLOW OR DOWNFLOW
A89014
Fig. 21 -- Removing Bottom Closure Panel
MIN 1/4-IN. (6 MM) TO 1/2-IN. (13 MM) MAX
HORIZONTAL
Fig. 22 -- Furnace Pitch Requirements
BOTTOM CLOSURE PAN EL
BOTTOM PLA TE
A11092
A11237
25
Page 26
ANY COMBINATION OF 1, 2, OR 3 PERMITTED.
Fig. 23 -- Upflow Return Air Configurations and Restrictions
59MN7A
Fig. 25 -- Horizontal Return Air Configurations
A11036
HORIZONTAL TOP RETURN NOT PERMITTED FOR ANY MODEL
and Restrictions
A11037
Fig. 24 -- Downflow Return Air Configurations
and Restrictions
A11038
26
Page 27
COMBUSTION - AIR PIPE (SEE VENTING SECTION)
2-IN.
(51 mm)
30 IN. (762 mm)
MIN. WORK AREA
ROLLOUT PROTECTION REQUIRED
Install 12” x 22” (305 x 559 mm) sheet metal in front of burner compartment area.
A11154
Fig. 26 -- Working Platform for Attic Installation
NOTE: Local codes may require a drain pan and condensate trap when a condensing furnace is installed over a finished ceiling.
COMBUSTION-AIR PIPE (SEE VENTING SECTION)
2-IN.
(51 mm)
59MN7A
NOTE: Local codes may require a drain pan and condensate trap when a condensing furnace is installed over a finished ceiling.
A11155
Fig. 27 -- Suspended Furnace Installation
27
Page 28
AIR DUCTS
NOTICE
Many states, provinces and localities are considering or have
implemented standards and/or restrictions on duct sizing
practices, ductwork leakage, and/or ductwork thermal, airflow
and electrical efficiencies. CONSULT LOCAL CODE
OFFICIALS for ductwork design and performance
requirements in your area.
General Requirements
The duct system should be designed and sized according to accepted national standards such as those published by: Air Conditioning Contractors Association (ACCA Manual D) , Sheet Metal and Air Conditioning Contractors National Association (SMACNA) or American Society of Heating, Refrigerating and Air Conditioning Engineers (ASHRAE) or consult The Air Systems Design Guidelines reference tables available from your local distributor. The duct system should be sized to handle the required system design CFM at the design external static pressure.
59MN7A
The furnace airflow rates are provided in Table 9--Air Delivery--CFM (With Filter). When a furnace is installed so that the supply ducts carry air circulated by the furnace to areas outside the space containing the furnace, the return air shall also be handled by duct(s) sealed to the furnace casing and terminating outside the space containing the furnace.
Secure ductwork with proper fasteners for type of ductwork used. Seal supply-- and return--duct connections to furnace with code approved tape or duct sealer.
NOTE: Flexible connections should be used between ductwork and furnace to prevent transmission of vibration.
Ductwork passing through unconditioned space should be insulated to enhance system performance. When air conditioning is used, a vapor barrier is recommended.
Maintain a 1--in. (25 mm) clearance from combustible materials to supply air ductwork for a distance of 36--in. (914 mm) horizontally from the furnace. See NFPA 90B or local code for further requirements.
Return Duct Sizing
Refer to the Filter Selection and Duct Sizing section for information on the proper selection of filter sizes and the associated ductwork and duct transitions. Improperly designed filtering systems and return ductwork are the most common causes of airflow and/or noise complaints in HVAC systems.
Ductwork Acoustical Treatment
NOTE: Metal duct systems that do not have a 90 degree elbow
and 10 ft. (3 M) of main duct to the first branch take--off may require internal acoustical lining. As an alternative, fibrous ductwork may be used if constructed and installed in accordance with the latest edition of SMACNA construction standard on fibrous glass ducts. Both acoustical lining and fibrous ductwork shall comply with NFPA 90B as tested by UL Standard 181 for Class 1 Rigid air ducts.
NOTE: For horizontal applications, the top most flange may be bent past 90_ to allow the evaporator coil to hang on the flange temporarily while the remaining attachment and sealing of the coil are performed.
28
Page 29
4
Table9–Cooling
and Heating Air Delivery -- CFM (Bottom Return5With Filter)
(SW1-5 and SW4-3 set to OFF, except as indicated. See notes 1 and 2)
Unit Size
Clg/CF Switch Settings External Static Pressure (ESP)
SWx-3 SWx-2 SWx-1 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
060-14
Clg Default: OFF OFF OFF 1060 1070 1080 1080 1075 1065 1050 1035 1025 1010
CF Default: OFF OFF OFF 545 530 520 525 510 Seenote4
OFF OFF ON 545 530 520 525 510 Seenote4
OFF ON OFF 710 710 710 695 690 Seenote4
OFF ON ON 875 880 890 895 895 890 885 880 870 855
Cooling (SW2)
ON OFF OFF 1060 1070 1080 1080 1075 1065 1050 1035 1025 1010
Cont Fan (SW3)
ON OFF ON 1235 1240 1250 1255 1255 1250 1230 1190 1155 1115
ON ON OFF 1235 1240 1250 1255 1255 1250 1230 1190 1155 1115
ON ON ON 1235 1240 1250 1255 1255 1250 1230 1190 1155 1115
Clg SW2: Maximum Clg Airflow
Maximum Heat Airflow
Heating
(SW1)
Intermediate Heat Airflow
Minimum Heat Airflow
Unit Size
Clg/CF Switch Settings External Static Pressure (ESP)
SWx-3 SWx-2 SWx-1 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
2
1425 1425 1405 1370 1335 1300 1260 1225 1190 1155
3
1075 1085 1095 1095 1090 1080 1065 1050 1035 1020
3
535 515 505 515 495 Seenote4
3
420 410 415 400 380 Seenote4
060 --- 20
Clg Default: OFF OFF OFF 1735 1735 1725 1715 1700 1685 1665 1650 1625 1605
CF Default: OFF OFF OFF 545 530 520 525 510 Seenote4
OFF OFF ON 540 525 525 520 540 Seenote4
OFF ON OFF 680 725 725 720 720 Seenote4
OFF ON ON 925 915 910 895 900 890 875 865 860 855
Cooling (SW2)
ON OFF OFF 1070 1075 1080 1070 1080 1075 1055 1045 1030 1020
Cont Fan (SW3)
ON OFF ON 1215 1245 1235 1220 1220 1210 1200 1195 1185 1175
ON ON OFF 1380 1385 1395 1390 1395 1390 1380 1365 1355 1340
59MN7A
ON ON ON 1735 1735 1725 1715 1700 1685 1665 1650 1625 1605
Clg SW2: Maximum Clg Airflow
Maximum Heat Airflow
Heating
(SW1)
Intermediate Heat Airflow
Minimum Heat Airflow
NOTE: See notes at end of table.
2
1955 1950 1940 1925 1905 1885 1855 1815 1745 1685
3
1080 1085 1095 1090 1095 1085 1070 1055 1045 1030
3
685 725 730 725 730 Seenote4
3
560 555 555 550 565 Seenote4
29
Page 30
4
and Heating Air Delivery -- CFM (Bottom Return5With Filter) (Continued)
Unit Size
Table 9 -- Cooling
Clg/CF Switch Settings External Static Pressure (ESP)
SWx-3 SWx-2 SWx-1 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
080-14
Clg Default: OFF OFF OFF 1055 1065 1080 1075 1065 1050 1045 1035 1025 1005
CF Default: OFF OFF OFF 520 505 505 495 490 Seenote4
OFF OFF ON 520 505 505 495 490 Seenote4
OFF ON OFF 665 685 680 660 665 Seenote4
OFF ON ON 885 895 905 900 900 895 885 875 860 845
Cooling (SW2)
ON OFF OFF 1055 1065 1080 1075 1065 1050 1045 1035 1025 1005
Cont Fan (SW3)
ON OFF ON 1245 1245 1255 1255 1260 1255 1250 1235 1220 1185
ON ON OFF 1245 1245 1255 1255 1260 1255 1250 1235 1220 1185
ON ON ON 1245 1245 1255 1255 1260 1255 1250 1235 1220 1185
59MN7A
Clg SW2: Maximum Clg Airflow
Maximum Heat Airflow
Heating
(SW1)
Intermediate Heat Airflow
Minimum Heat Airflow
Unit Size
Clg/CF Switch Settings External Static Pressure (ESP)
SWx-3 SWx-2 SWx-1 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
2
1520 1485 1450 1415 1375 1335 1300 1265 1225 1190
3
1520 1485 1450 1415 1375 1335 1300 1265 1225 1190
3
755 745 755 755 765 Seenote4
3
620 625 630 620 610 Seenote4
080 --- 20
Clg Default: OFF OFF OFF 1745 1755 1755 1760 1755 1750 1745 1725 1705 1685
CF Default: OFF OFF OFF 700 710 750 725 750 Seenote4
OFF OFF ON 700 710 750 725 750 Seenote4
OFF ON OFF 830 860 870 890 960 Seenote4
OFF ON ON 1045 1045 1060 1070 1070 1070 1095 1090 1080 1070
Cooling (SW2)
ON OFF OFF 1215 1220 1245 1240 1235 1235 1225 1220 1235 1235
Cont Fan (SW3)
ON OFF ON 1370 1370 1390 1390 1400 1395 1400 1390 1390 1385
ON ON OFF 1745 1755 1755 1760 1755 1750 1745 1725 1705 1685
ON ON ON 1745 1755 1755 1760 1755 1750 1745 1725 1705 1685
Clg SW2: Maximum Clg Airflow
Maximum Heat Airflow
Heating
(SW1)
Intermediate Heat Airflow
Minimum Heat Airflow
NOTE: See notes at end of table.
2
1920 1920 1945 1945 1945 1960 1950 1940 1915 1900
3
1340 1355 1370 1385 1380 1385 1400 1400 1385 1380
3
780 810 835 840 845 Seenote4
3
595 595 600 595 605 Seenote4
30
Page 31
4
and Heating Air Delivery -- CFM (Bottom Return5With Filter) (Continued)
Unit Size
Table 9 -- Cooling
Clg/CF Switch Settings External Static Pressure (ESP)
SWx-3 SWx-2 SWx-1 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
100-22
Clg Default: OFF OFF OFF 1820 1825 1840 1845 1840 1835 1825 1805 1780 1770
CF Default: OFF OFF OFF 750 740 745 730 715 Seenote4
OFF OFF ON 750 740 745 730 715 Seenote4
OFF ON OFF 900 900 915 910 905 Seenote4
Cooling (SW2)
Cont Fan (SW3)
OFF ON ON 1070 1075 1095 1095 1090 1085 1095 1080 1065 1070
ON OFF OFF 1280 1285 1305 1305 1310 1305 1295 1300 1290 1285
ON OFF ON 1440 1445 1465 1465 1470 1485 1480 1485 1475 1460
ON ON OFF 1820 1825 1840 1845 1840 1835 1825 1805 1780 1770
ON ON ON 2135 2140 2140 2135 2140 2130 2115 2100 2070 2015
Clg SW2: Maximum Clg Airflow
Maximum Heat Airflow
Heating
(SW1)
Intermediate Heat Airflow
Minimum Heat Airflow
Unit Size
Clg/CF Switch Settings External Static Pressure (ESP)
SWx-3 SWx-2 SWx-1 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
2
2160 2165 2175 2170 2160 2150 2135 2120 2065 2020
3
1570 1575 1595 1595 1600 1605 1600 1600 1590 1575
3
950 955 965 975 970 Seenote4
3
755 745 750 735 720 Seenote4
120-22
Clg Default: OFF OFF OFF 1850 1855 1860 1855 1850 1830 1805 1775 1750 1730
CF Default: OFF OFF OFF 930 925 915 900 885 Seenote4
OFF OFF ON 765 745 740 705 680 Seenote4
OFF ON OFF 930 925 915 900 885 Seenote4
59MN7A
OFF ON ON 1095 1100 1110 1105 1085 Seenote4
Cooling (SW2)
ON OFF OFF 1265 1255 1265 1280 1275 1285 1270 1260 1250 1230
Cont Fan (SW3)
ON OFF ON 1465 1455 1470 1465 1465 1470 1455 1450 1435 1415
ON ON OFF 1850 1855 1860 1855 1850 1830 1805 1775 1750 1730
ON ON ON 2200 2200 2200 2190 2185 2170 2145 2085 1990 1890
Clg SW2: Maximum Clg Airflow
Maximum Heat Airflow
Heating
(SW1)
Intermediate Heat Airflow
Minimum Heat Airflow
1. Nominal 350 CFM/ton cooling airflow is delivered with SW1--5 and SW4--3 set to OFF.
2. Maximum cooling airflow is achieved when switches SW2--1, SW2--2, SW2--3 and SW1--5 are set to ON, and SW4--3 is set to OFF.
3. All heating CFM’s are when low/medium heat rise adjustment switch (SW1--3) and comfort/efficiency adjustment switch (SW1--4) are both
set to OFF.
4. Ductwork must be sized for high--heating CFM within the operational range of ESP. Operation within the blank areas of the chart is not recommended because high--heat operation will be above 1.0 ESP.
5. All airflows on 21” casing size furnaces are 5% less on side return only installations.
6. Return air above 1800 CFM on 24.5” casing sizes requires two sides, one side and bottom or bottom only , to allow sufficient airflow to the furnace.
Set SW1--5 to ON for nominal 400 CFM/ton (+15% airflow). Set SW4--3 to ON for nominal 325 CFM/ton (--7% airflow). Set both SW1--5 and SW4--3 to ON for nominal 370 CFM/ton (+7% airflow). The above adjustments in airflow are subject to motor horsepower range/capacity.
2
2200 2200 2200 2190 2185 2170 2145 2085 1990 1890
3
1815 1820 1825 1820 1815 1795 1775 1745 1720 1700
3
1095 1100 1110 1105 1085 Seenote4
3
905 900 890 875 855 Seenote4
31
Page 32
GAS PIPING
!
WARNING
FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in personal injury, death, and/orproperty damage.
Never purge a gas line into a combustion chamber. Never test for gas leaks with an open flame. Use a commercially available soap solution made specifically for the detection of leaks to check all connections. A fire or explosion may result causing property damage, personal injury or loss of life.
!
WARNING
FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in personal
59MN7A
injury, death, and/orproperty damage. Use proper length of pipe to avoid stress on gas control
manifold and gas valve.
!
WARNING
FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in personal injury, death, and/orproperty damage.
Gas valve inlet and/or inlet pipe must remain capped until gas supply line is permanently installed to protect the valve from moisture and debris. Also, install a sediment trap in the gas supply piping at the inlet to the gasvalve.
Gas piping must be installed in accordance with national and local codes. Refer to current edition of NFGC in the U.S.A. Refer to current edition of NSCNGPIC in Canada.
Installations must be made in accordance with all authorities having jurisdiction. If possible, the gas supply line should be a separate line running directly from meter to furnace.
NOTE: Use a back--up wrench on the inlet of the gas valve when connecting the gas line to the gas valve.
NOTICE
In the State of Massachusetts:
1. Gas supply connections MUST be performed by a licensed plumber or gas fitter.
2. When flexible connectors are used, the maximum length shall not exceed 36 in. (915 mm).
3. When lever handle type manual equipment shutoff valves are used, they shall be T--handle valves.
4. The use of copper tubing for gas piping is NOT approved by the State of Massachusetts.
Refer to Table 10 for recommended gas pipe sizing. Risers must be used to connect to furnace and to meter. Support all gas piping with appropriate straps, hangers, etc. Use a minimum of one hanger every 6 ft. (2 M). Joint compound (pipe dope) should be applied sparingly and only to male threads of joints. Pipe dope must be resistant to the action of propane gas.
!
WARNING
FIRE OR EXPLOSION HAZARD
A failure to follow this warning could result in personal injury, death, and/orproperty damage.
If local codes allow the use of a flexible gas appliance connector, always use a new listed connector. Do not use a connector which has previously served another gas appliance. Black iron pipe shall be installed at the furnace gas control valve and extend a minimum of 2--in. (51 mm) outside the furnace.
!
CAUTION
FURNACE DAMAGE HAZARD
Failure to follow this caution may result in furnace damage. Connect gas pipe to furnace using a backup wrench to
avoid damaging gas controls and burner misalignment.
An accessible manual equipment shutoff valve MUST be installed external to furnace casing and within 6 ft. (2 M) of furnace.
Install a sediment trap in riser leading to furnace as shown in Fig.
29. Connect a capped nipple into lower end of tee. Capped nipple should extend below level of furnace gas controls. Place a ground joint union between furnace gas control valve and exterior manual equipment gas shutoff valve.
A 1/8--in. (3 mm) NPT plugged tapping, accessible for test gauge connection, MUST be installed immediately upstream of gas supply connection to furnace and downstream of manual equipment shutoff valve.
Piping should be pressure and leak tested in accordance with the current addition of the NFGC in the United States, local, and national plumbing and gas codes before the furnace has been connected. Refer to current edition of NSCNGPIC in Canada. After all connections have been made, purge lines and check for leakage at furnace prior to operating furnace.
NOTE: The furnace gas control valve inlet pressure tap connection is suitable to use as test gauge connection providing test pressure DOES NOT exceed maximum 0.5 psig (14--In. W.C.) stated on gas control valve. See Fig. 52.
If pressure exceeds 0.5 psig (14--In. W.C.), gas supply pipe must be disconnected from furnace and capped before and during supply pipe pressure test. If test pressure is equal to or less than 0.5 psig (14--In. W.C.), turn off electric shutoff switch located on furnace gas control valve and accessible manual equipment shutoff valve before and during supply pipe pressure test. After all connections have been made, purge lines and check for leakage at furnace prior to operating furnace.
The gas supply pressure shall be within the maximum and minimum inlet supply pressures marked on the rating plate with the furnace burners ON and OFF.
Some installations require gas entry on right side of furnace (as viewed in upflow). See Fig. 28.
Gas Pipe Grommet
For direct vent (2-pipe) applications, the knockout for the gas pipe must be sealed to prevent air leakage. Remove the knockout, install the grommet in the knockout, then insert the gas pipe. The grommet is included in the loose parts bag. See Fig. 28.
32
Page 33
Table 10 – Maximum Capacity of Pipe
NOMINAL
IRON PIPE
SIZE
IN. (MM)
1/2 (13) 175 120 97 82 73 3/4 (19) 360 250 200 170 151
1 ( 25) 680 465 375 320 285 1-1/4 (32) 1400 950 770 660 580 1-1/2 (39) 2100 1460 1180 990 900
* Cubic ft of gas per hr for gas pressures of 0.5 psig (14 --- In. W.C.) or less and a pressure drop of 0.5--- In. W.C. (based on a 0.60 specific gravity gas). Ref: Table 10 above and 6.2 of NFPA54/ANSI Z223.1 --- 2009.
Left Side Gas Entry. Gas Pipe Grommet Required For Direct Vent Applications.
(3.0)20(6.0)30(9.1)40(12.1)50(15.2)
LENGTH OF PIPE --- FT (M)
10
Gas Pipe Grommet Required For Direct Vent Applications
Field--supplied wiring shall conform with the limitations of 63_F (33_C) rise.
!
WARNING
ELECTRICAL SHOCK AND FIRE HAZARD
Failure to follow this warning could result in personal injury, death, or property damage.
The cabinet MUST have an uninterrupted or unbroken ground according to NEC ANSI/NFPA 70--2011 or local codes to minimize personal injury if an electrical fault should occur. In Canada, refer to Canadian Electrical Code CSA C22.1. This may consist of electrical wire, conduit approved for electrical ground or a listed, grounded power cord (where permitted by local code) when installed in accordance with existing electrical codes. Refer to the power cord manufacturer’s ratings for proper wire gauge. Do not use gas piping as an electrical ground.
GAS
SUPPLY
MANUAL SHUT OFF VALV E (REQUIRED)
SEDIMENT TRAP
Fig. 28 -- Gas Entry
FRONT
UNION
Fig. 29 -- Typical Gas Pipe Arrangement
NOTE: Union may be inside the vestibule where permitted by local codes.
ELECTRICAL CONNECTIONS
A11338
A11035
!
CAUTION
FURNACE MAY NOT OPERATE HAZARD
Failure to follow this caution may result in intermittent furnace operation.
Furnace control must be grounded for proper operation or else control will lock out. Control must remain grounded through green/yellow wire routed to gas valve and manifold bracket screw.
115-- V Wiring
Furnace must have a 115-v power supply properly connected and grounded.
NOTE: Proper polarity must be maintained for 115-v wiring. If polarity is incorrect, control LED status indicator light will flash rapidly and furnace will NOT operate.
Verify that the voltage, frequency, and phase correspond to that specified on unit rating plate. Also, check to be sure that service provided by utility is sufficient to handle load imposed by this equipment. Refer to rating plate or Table 11 for equipment electrical specifications.
U.S.A. Installations: Make all electrical connections in accordance with the current edition of the National Electrical Code (NEC) ANSI/NFPA 70 and any local codes or ordinances that might apply.
Canada Installations: Make all electrical connections in accordance with the current edition of the Canadian Electrical Code CSA C22.1 and any local codes or ordinances that might apply.
59MN7A
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal
injury or death.
Blower door switch opens 115--v power to control. No
component operation can occur. Do not bypass or close
switch with blower door removed.
See Fig. 33 for field wiring diagram showing typical field 115--v wiring. Check all factory and field electrical connections for tightness.
!
WARNING
FIRE HAZARD
Failure to follow this warning could result in personal injury, death, or property damage.
Do not connect aluminum wire between disconnect switch and furnace. Use only copper wire. See Fig. 31.
Use a separate, fused branch electrical circuit with a properly sized fuse or circuit breaker for this furnace. See Table 11 for wire size and fuse specifications. A readily accessible means of electrical disconnect must be located within sight of the furnace.
33
Page 34
J--Box Installation
!
WARNING
FIRE OR ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal
injury, death, or property damage.
If field--supplied manual disconnect switch is to be mounted
on furnace casing side, select a location where a drill or
fastener cannot damage electrical or gas components.
The J-Box is used when field line voltage electrical connections are made to the furnace wiring harness inside the furnace casing. The J-Box is not required if a field-supplied electrical box is attached to the outside of the furnace casing and the box is grounded to the green ground wire of the main wiring harness and the earth ground of the field electrical supply.
The J--Box cover, mounting bracket and screws are shipped in the loose parts bag included with the furnace. The J--Box can be mounted on the left or right side of the casing, as viewed from the upflow position. See Fig. 30.
59MN7A
Remove the J--Box cover and mounting bracket from the loose parts bag. Select a 7/8--in. (22 mm) knock-out on the desired side of the casing. Remove the knock-out from the casing. Drill two (2) 1/8--in. (3 mm) pilot holes in the casing dimples by the desired 7/8--in. (22 mm) knock-out.
Align the J--box mounting bracket against the inside of the casing and secure the mounting bracket with the screws. See Fig. 30.
Electrical Box on Furnace Casing Side
NOTE: Check that duct on side of furnace will not interfere with
installed electrical box.
1. Fasten a field-supplied external electrical box to the outside of the casing by driving two field-supplied screws from in­side electrical box into casing. See Fig. 31.
2. Route field power wiring into external electrical box.
3. Pull furnace power wires through 1/2-in. (12 mm) diameter hole in J-Box. If necessary, loosen power wires from strain-­relief wire-tie on furnace wiring harness.
4. Connect any code required external disconnect(s) to field power wiring.
5. Route external field power wires through holes in electrical box and casing.
6. Connect field ground wire and factory ground wire to green ground screw on J--Box mounting bracket as shown in Fig.
30.
7. Connect field power and neutral leads to furnace power leads as shown in Fig. 33.
8. Attach furnace J-Box cover to mounting bracket with screws supplied in loose parts bag. Do not pinch wires between cover and bracket.
9. Complete external disconnect wiring and installation. Con­nect line voltage leads as shown in Fig. 31. Use best prac­tices (NEC in U.S.A. for wire bushings, strain relief, etc., CANADA: Canadian Electrical Code CSA C22.1)
Power Cord Installation in Furnace J--Box
NOTE: Power cords must be able to handle the electrical
requirements listed in Table 11. Refer to power cord manufacturer’s listings.
1. Install J--Box mounting bracket to inside of furnace casing. See Fig. 30.
2. Route listed power cord through 7/8--in. (22 mm) diameter hole in casing and J--Box bracket.
3. Secure power cord to J--Box bracket with a strain relief bushing or a connector approved for the type of cord used.
4. Pull furnace power wires through 1/2--in. (12 mm) diameter hole in J--Box. If necessary, loosen power wires from strain—relief wire--tie on furnace wiring harness.
5. Connect field ground wire and factory ground wire to green ground screw on J--Box mounting bracket as shown in Fig.
30.
6. Connect power cord power and neutral leads to furnace power leads as shown in Fig. 33.
7. Attach furnace J--Box cover to mounting bracket with screws supplied in loose parts bag. Do not pinch wires between cover and bracket. See Fig. 30.
BX Cable Installation in Furnace J--Box
1. Install J--Box mounting bracket to inside of furnace casing. See Fig. 30.
2. Route BX connector through 7/8--in. (22 mm) diameter hole in casing and J--Box bracket.
3. Secure BX cable to J--Box bracket with connectors ap­proved for the type of cable used.
4. Connect field ground wire and factory ground wire to green ground screw on J--Box mounting bracket as shown in Fig.
30.
5. Connect field power and neutral leads to furnace power leads. as shown in Fig. 33.
6. Attach furnace J--Box cover to mounting bracket with screws supplied in loose parts bag. Do not pinch wires between cover and bracket.
24--V Wiring
Make field 24--v connections at the 24--v terminal strip. See Fig.
34. Connect terminal Y/Y2 as shown in Fig. 33 for proper cooling operation. Use only AWG No. 18, color--coded, copper thermostat wire.
NOTE: Use AWG No. 18 color-coded copper thermostat wire for lengths up to 100 ft. (31 M). For wire lengths over 100 ft., use AWG No. 16 wire.
The 24--v circuit contains an automotive--type, 3--amp. fuse located on the control. Any direct shorts during installation, service, or maintenance could cause this fuse to blow. If fuse replacement is required, use ONLY a 3--amp. fuse of identical size. See Fig. 34.
Thermostats
For best results, use a communicating wall control to control this modulating furnace. A single stage or two--stage heating and cooling thermostat can be used with the furnace. The furnace control board CPU will control the furnace and outdoor unit staging. A two stage heating and cooling thermostat can also be used to control the staging. However, full modulating capability will not be available when the furnace staging is controlled by the thermostat. Furnace staging will be limited to Minimum and Maximum inputs or Intermediate and Maximum inputs depending on the configuration of set-up switches SW1-2 and SW4-2. For two stage thermostat control of a 2-stage outdoor unit, remove the ACRDJ jumper from the furnace control board. Refer to typical thermostat wiring diagrams and the Sequence of Operation section for additional details. Consult the thermostat installation instructions for specific information about configuring the thermostat. See Fig. 34 and 35.
Accessories (See Fig. 32 and 34.)
1. Electronic Air Cleaner (EAC) Connect an accessory Electronic Air Cleaner (if used) using 1/4--in. female quick connect terminals to the two male 1/4--in. quick--connect terminals on the control board marked EAC--1 and EAC--2. The terminals are rated for 115VAC, 1.0 amps maximum and are energized during blower motor operation.
34
Page 35
2. Humidifier (HUM)
The HUM terminal is a 24 VAC output, energized when the blower is operating during a call for heat.
Connect an accessory 24 VAC, 0.5 amp. maximum humidifier (if used) to the ¼--in. male quick--connect HUM terminal and COM--24V screw terminal on the control board thermostat strip.
NOTE: If the humidifier has its own 24 VAC power supply, an isolation relay may be required. Connect the 24 VAC coil of the isolation relay to the HUM and COM/24V screw terminal on the control board thermostat strip. See Fig. 32.
3. Communication Connector (communication connection) This connection is used when the furnace is controlled by an optional communicating User Interface instead of a standard thermostat. The communication plug is supplied with the User Interface. Refer to the instructions supplied with the User Interface for complete details. See Fig. 34.
4. Outside Air Thermistor (OAT) The OAT connection is used in conjunction with commu-
nicating User Interface. It is not required when the furnace is controlled by a standard type thermostat. Refer to the in­structions supplied with the User Interface for complete de­tails.
Alternate Power Supplies
This furnace is designed to operate on utility generated power which has a smooth sinusoidal waveform. If the furnace is to be operated on a generator or other alternate power supply, the alternate power supply must produce a smooth sinusoidal waveform for compatibility with the furnace electronics. The alternate power supply must generate the same voltage, phase, and frequency (Hz) as shown in Table 11 or the furnace rating plate.
Power from an alternate power supply that is non-sinusoidal may damage the furnace electronics or cause erratic operation.
Contact the alternate power supply manufacturer for specifications and details.
Table 11 – Electrical Data
MODULATING
UNIT SIZE V O LT S ---
060 --- 14 1 1 5 --- 6 0 --- 1 127 104 9.7 12.7 14 29 (8.8) 15 060 --- 20 1 1 5 --- 6 0 --- 1 127 104 14.8 19.1 12 30 (9.1) 20 080 --- 14 1 1 5 --- 6 0 --- 1 127 104 9.7 12.7 14 29 (8.8) 15 080 --- 20 1 1 5 --- 6 0 --- 1 127 104 14.8 19.1 12 30 (9.1) 20 100 --- 22 1 1 5 --- 6 0 --- 1 127 104 14.8 19.1 12 30 (9.1) 20 120 --- 22 1 1 5 --- 6 0 --- 1 127 104 14.8 19.1 12 30 (9.1) 20
* Permissible limits of the vol tage range at which the un it operates satisfactorily. # Unit ampacity = 125 percent of largest operating component’s full load amps plus 100 percent of all other potential operating components’ (EAC, humidifier,
etc.) full load amps.
{Time---delay type is recommended. }Length shown is as measured one way along wire path between furnace and service panel for maximum 2 percent voltage drop.
H E R T Z ---
PHASE
OPERATING VOLTAGE
RANGE*
Maximum* Minimum*
MAXIMUM
UNIT
AMPS
UNIT
AMPACITY#
MINIMUM
WIRE
SIZE
AWG
MAXIMUM
WIRE
LENGTH
FT (M)}
MAXIMUM
FUSE OR CKT
BKR
AMPS{
59MN7A
35
Page 36
GROUND
NEUTRAL
LINE VOLTAGE
59MN7A
ELECTRIC
DISCONNECT
SWITCH
COPPER
WIRE ONLY
Fig. 30 -- Installing J--Box (When Used)
Appearance May Vary
A12226
ALUMINUM
WIRE
A11146
Fig. 31 -- Field--Supplied Electrical Box on Furnace Casing
36
Page 37
To Humidifier Leads
To HUM Terminal On
Furnace Control Board
24 V
Coil
To Humidifier Leads
To Com/24V Screw Terminal
on Thermostat Strip
Fig. 32 -- Field--supplied Isolation Relay for Humidifiers with Internal Power Supply
W2
COM
W/W1
Y/Y2
R
G
A11157
59MN7A
Fig. 33 -- Typical Field Wiring Diagram
37
A11401
Page 38
24-V THERMOSTAT
TERMINALS
PL2 – HOT SURFACE
IGNITER & INDUCER
MOTOR CONNECTOR
115-VAC (L2) NEUTRAL
CONNECTIONS
115-VAC (L1) LINE
VOLTAGE CONNECTIONS
EAC-1 TERMINAL
(115-VAC 1.0 AMP MAX.)
PL1 – LOW VOLTAGE MAIN
HARNESS CONNECTOR
PL3 – ECM BLOWER
HARNESS
CONNECTOR
TRANSFORMER 24-VAC
CONNECTIONS
3-AMP FUSE
STATUS AND COMM
LED LIGHTS
SW1 SETUP
SWITCHES AND
BLOWER OFF-
DELAY
MODEL PLUG CONNECTOR
AIR CONDITIONING
(A/C) AIRFLOW
SETUP SWITCHES
COMMUNICATION
CONNECTOR
CONTINUOUS FAN
(CF) AIRFLOW
SETUP SWITCHES
OUTDOOR
AIR TEMP
CONNECTOR
HUMIDIFIER
TERMINAL (24-VAC
0.5 AMP MAX.
ACRDJ – AIR
CONDITIONING
RELAY DISABLE
JUMPER
FLASH
UPGRADE
CONNECTOR
(FACTORY
ONLY)
SW4 SETUP
SWITCHES
SOFTWARE
VERSION
PART NUMBER AND
DATE CODE WWYY
PL8 - MODULATING
GAS VALVE
CONNECTOR
59MN7A
A11616
Fig. 34 -- Example of Modulating Furnace Control
38
Page 39
THERMOSTAT
THERMOSTAT
D
D
59MN7A
See notes 2, 5, 7, 10, 11, 16, and 17 See notes 1, 2, 4, 6, 7, 9, 10, 11, 15, 16, and 17
Modulating and 2-Stage Furnace with Single-Speed Air Conditioner
THERMOSTAT
D
Modulating and 2-Stage Furnace with Single-Speed Heat Pump
THERMOSTAT
D
See notes 2, 5, 8, 10, 11, 12, 16, and 17
Modulating and 2-Stage Furnace with Two-Speed Air Conditioner
See notes 1, 2, 3, 4, 6, 8, 9, 10, 12, 13, 15, 16, and 17
Modulating and 2-Stage Furnace with Two-Speed Heat Pump
A12222
Fig. 35 -- Thermostat Wiring Diagrams
39
Page 40
NOTES FOR THERMOSTAT WIRING DIAGRAMS
1. Heat pump MUST have a high pressure switch for dual fuel applications.
2. Refer to outdoor equipment Installation Instructions for additional information and setup procedure.
3. If the heat pump date code is 1501E or earlier, select the “ZONE” position on the two speed heat pump control. Heat pumps with date code 1601E and later do not have or require a “ZONE” selection.
4. Outdoor Air Temperature - sensor must be attached in all dual fuel applications.
5. Configure the thermostat for air conditioner installations. Refer to thermostat instructions.
6. Configure thermostat for heat pump installations. Refer to thermostat instructions.
7. Configure thermostat for single-stage compressor operation. Refer to thermostat instructions.
8. Configure thermostat for two-stage compressor operation. Refer to thermostat instructions.
9. Configure thermostat for Dual Fuel Operation. Refer to thermostat instructions.
10. NO connection should be made to the furnace HUM terminal when using a thermostat with a 24 volt humidifier output.
11. Optional connection - If wire is connected to W2 on furnace control board, either dip switch SW1-2 or SW4-2 on furnace control should be set in ON position to allow thermostat to control furnace at 2 stages Min/Max or Intermediate/Max.
12. Optional connection - If wire is connected, ACRDJ jumper on furnace control should be removed to allow thermostat to control outdoor unit staging.
13. Furnace must control its own staging operation via furnace control algorithm. This is factory default.
14. The RVS Sensing terminal “L” should not be connected. This is internally used to sense defrost operation.
15. If thermostat has internal control of heat pump balance point, DO NOT SELECT the “FURNACE INTERFACE” or “BALANCE POINT” option on the two-speed heat pump control board. Refer to thermostat instructions
59MN7A
16. Configure Dehumidify function to remove 24 VAC from Dehum terminal on a demand to dehumidify.
17. Thermostat signals may vary. Consult thermostat installation instructions for more information.
VENTING
NOTE: Planning for the venting system should be done in
conjunction with planning for the ductwork, drainage, and furnace accessories, such as air cleaners and humidifiers. Begin assembling the venting system AFTER the furnace is set in place in the required orientation.
Venting for this furnace shall follow all Local codes for Category IV venting systems. This furnace is CSA approved for venting with PVC/ABS DWV venting systems. This furnace is also CSA approved for venting with M&G DuraVentR PolyProR polypropylene venting systems.
NOTE: THESE INSTRUCTIONS DO NOT CONTAIN DETAILED INSTALLATION INSTRUCTIONS FOR POLYPROPYLENE VENTING SYSTEMS. Refer to the polypropylene venting system manufacturer’s installation instructions for the polypropylene venting system installation.
NOTE: When using polypropylene venting systems, all venting materials used, including the vent terminations, must be from the same manufacturer.
Special Venting Requirements for Installations in Canada
Installation in Canada must conform to the requirements of CSA B149 code. Vent systems must be composed of pipe, fittings, cements, and primers listed to ULC S636. The special vent fittings, accessory concentric vent termination kits and accessory external drain trap available from the furnace manufacturer have been certified to ULC S636 for use with those Royal Pipe and IPEX PVC vent components which have been certified to this standard. In Canada, the primer and cement must be of the same manufacturer as the vent system – GVS-65 Primer (Purple) for Royal Pipe or IPEX System 636, PVC/CPVC Primer, Purple Violet for Flue Gas Venting and GVS-65 PVC Solvent Cement for Royal Pipe or IPEX System 636 Venting, rated Class IIA, 65 deg C. must be used with this venting system - do not mix primers and cements from one manufacturer with a vent system from a different manufacturer. Follow the manufacturer’s instructions in the use of primer and cement and never use primer or cement beyond its expiration date.
The safe operation, as defined by ULC S636, of the vent system is based on following these installation instructions, the vent system manufacturer’s installation instructions, and proper use of primer and cement. All fire stop and roof flashing used with this system
t, PVC Cement for Flue Gas
(1)
must be UL listed material. Acceptability under Canadian standard CAN/CSA B149 is dependent upon full compliance with all installation instructions. Under this standard, it is recommended that the vent system be checked once a year by qualified service personnel.
The authority having jurisdiction (gas inspection authority, municipal building department, fire department, etc.) should be consulted before installation to determine the need to obtain a permit.
*IPEX System 636™ is a trademark of IPEX Inc.
Consignes spéciales pour l’installation de ventilation au Canada
L’installation faite au Canada doit se conformer aux exigences du code CSA B149--2010. Ce systême de ventillation doit se composer de tuyaux, raccords, ciments et apprêts conformes au ULC S636. La tuyauterie de ventilation des gaz, ses accessoires, le terminal concentrique mural ainsi que l’ensemble du drain de condensation extérieur fourni par le fabricant de cette fournaise ont été certifiés ULCS 636 pour l’application des composantes Royal Pipe, IPEX PVC qui sont certifiées à ce standard. Au Canada, l’apprêt et le ciment doivent être du même fabricant que le système d’évacuation. L’apprêt GVS-65 (Purple) et le ciment-solvant GVS-65 doivent être utilisé avec les Royal Pipe. Système IPEX 636, apprêt PVC/CPVC, Purple pour évacuation des gaz de combustion et système IPEX 636(1)t, ciment PVC pour évacuation des gaz de combustion, coté classe IIA, 65 deg C. doivent être utilisés avec le système d’évacuation IPEX 636 – Ne pas combiner l ’apprêt et le ciment d’un manufacturier avec un système d’évacuation d’un manufacturier différent.
Bien suivre les indications du manufacturier lors de l’utilisation de l’apprêt et du ciment et ne pas utiliser ceux-ci si la date d’expiration est atteinte.
L’opération sécuritaire, tel que définit par ULC S636, du système de ventilation est basé sur les instructions d’installation suivantes, ainsi que l’usage approprié de l’apprêt et ciment. Tout arrët feu et solin de toit utilisés avec ce système doivent être des matériaux listés UL. L’acceptation du standard Canadien CAN/CSA B149 est directement relié à l’installation conforme aux instructions ci­haut mentionnées. Le standard Canadien recommande l’ inspection par un personel qualifié et ce, une fois par année.
Les autoritées ayant juridiction (inspecteurs de gas, inspecteurs en bâtiments, département des incendies, etc) devraient être consultées avant l’installation afin de déterminer si un permis est requis.
40
Page 41
!
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow the steps outlined below for each appliance connected to the venting system being placed into operation could result in carbon monoxide poisoning or death.
The following steps shall be followed for each appliance connected to the venting system being placed into operation, while all other appliances connected to the venting system are not in operation:
1. Seal any unused openings in venting system.
2. Inspect the venting system for proper size and horizontal pitch, as required in the National Fuel Gas Code, ANSI Z223.1/NFPA 54 or the CSA B149.1 Natural Gas and Propane Installation Code and these instructions. Determine that there is no blockage or restriction, leakage, corrosion and other deficiencies, which could cause an unsafe condition.
3. As far as practical, close all building doors and windows and all doors between the space in which the appliance(s) connected to the venting system are located and other spaces of the building.
4. Close fireplace dampers.
5. Turn on clothes dryers and any appliance not connected to the venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they are operating at maximum speed. Do not operate a summer exhaust fan.
6. Follow the lighting instructions. Place the appliance being inspected into operation. Adjust the thermostat so appliance is operating continuously.
7. Test for spillage from draft hood equipped appliances at the draft hood relief opening after 5 minutes of main burner operation. Use the flame of a match or candle.
8. If improper venting is observed during any of the above tests, the venting system must be corrected in accordance with the National Fuel Gas Code, ANSI Z223.1/NFPA 54 and/or CSA B149.1 Natural Gas and Propane Installation Code.
9. After it has been determined that each appliance connected to the venting system properly vents when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and any other gas--fired burning appliance to their previous conditions of use.
General
If this furnace replaces a furnace that was connected to a vent system or chimney, the vent or vent connectors of other remaining appliances may need to be re--sized. Vent systems or vent connectors of other appliances must be sized to the minimum size as determined using appropriate table found in the current edition of National Fuel Gas Code NFPA 54/ANSI Z--223.1. In Canada, refer to CAN/CSA--B149.1.
An abandoned masonry chimney may be used as a raceway for properly insulated and supported combustion--air (when applicable) and vent pipes. Each furnace must have its own set of combustion--air and vent pipes and be terminated individually, as shown in Fig. 46 for Direct Vent (2--Pipe) system or Fig. 47 for ventilated combustion air option.
A furnace shall not be connected to a chimney flue serving a separate appliance designed to burn solid fuel.
Other gas appliances with their own venting system may also use the abandoned chimney as a raceway providing it is permitted by local code, the current edition of the National Fuel Gas Code and the vent or liner manufacturer’s installation instructions. Care must be taken to prevent the exhaust gases from one appliance from contaminating the combustion air of other gas appliances.
Do not take combustion air from inside the chimney when using ventilated combustion air or single pipe vent option.
These furnaces can be vented as either direct vent (two--pipe) or as ventilated combustion air system. Each type of venting system is described below. Common venting between these furnaces or other appliances is prohibited.
Materials
U.S.A.
Combustion air and vent pipe, fittings, primers, and solvents must conform to American National Standards Institute (ANSI) standards and American Society for Testing and Materials (ASTM) standards. See Table 13 for approved materials for use in the U.S.A. This furnace is also CSA approved for venting with M&G DuraVentR PolyProR polypropylene venting systems.
Canada
Special Venting Requirements for Installations in Canada Installation in Canada must conform to the requirements of CAN/CSA B149 code. Vent systems must be composed of pipe, fittings, cements, and primers listed to ULC S636. M&G DuraVent PolyPro polypropylene venting systems are ULC S636 listed.
NOTE: When using polypropylene venting systems, all venting materials used, including the vent terminations must be from the same manufacturer.
Ventin g Systems
!
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow the instructions outlined below for each appliance being placed into operation could result in carbon monoxide poisoning or death.
For all venting configurations for this appliance and other gas appliances placed into operation for this structure, provisions for adequate combustion, ventilation, and dilution air must be provided in accordance with: U.S.A. Installations: Section 9.3 NFPA 54/ANSI Z223.1
--2009, Air for Combustion and Ventilation and applicable provisions of the local building codes.
Canadian Installations: Part 8 of CAN/CSA--B149.1--10. Venting Systems and Air Supply for Appliances and all authorities having jurisdiction.
NOTICE
RECOMMENDED SUPPORT FOR VENT TERMINATION
It is recommended that sidewall vent terminations of over 24 inches (0.6 M) in length or rooftop vent terminations of over 36 inches (1 M) in length be supported by EITHER the factory accessory vent termination kit or field--supplied brackets or supports attached to the structure. A factory accessory vent termination kit may be used for direct vent terminations. Termination kits are available for 2--in. or 3--in. pipe. See Table 12 for available options.
59MN7A
41
Page 42
Table 12 – Vent Termination Kit for Direct Vent (2--pipe)
Systems
DIRECT VENT
(2 --- PIPE)
TERMINATION KIT
2 --- in . ( 5 1 mm)
Concentric Vent Kit
3 --- in . ( 7 6 mm)
Concentric Vent Kit
TERMINATION
SYSTEM
Single Penetration of
Wall or Roof
Single Penetration of
wall or Roof
DIAM. OF COMBUS­TION AIR AND VENT
PIPES --- IN. (mm)
1, 1---1/2, 2, or 2---1/2
(24, 36, 51, 64 mm)
2---1/2, 3 or 4
(64, 76, 102 mm)
Direct Vent / 2-Pipe System
In a direct-vent (2-pipe) system, all air for combustion is taken directly from outdoor atmosphere, and all flue products are discharged to outdoor atmosphere. Combustion-air and vent pipes must terminate together in the same atmospheric pressure zone, either through the roof (preferred) or a sidewall. See Fig. 44 for references to clearances required by National code authorities.
NOTICE
OPTIONAL CONFIGURATION FOR COMBUSTION AIR INLET PIPE
In applications where there is a risk of excessive moisture entering the combustion air inlet pipe, a moisture trap may be
59MN7A
added to the inlet pipe to help prevent moisture from entering the furnace from the combustion air inlet pipe. See Fig. 51.
When sizing venting systems, the equivalent length of the optional inlet pipe moisture trap must be taken into account.
Ventilated Combustion Air Systems
In a ventilated combustion air option, the vent terminates and discharges the flue products directly to the outdoors similar to a direct vent system. See Fig. 45 for references to clearances required by National code authorities.
All air for combustion is piped directly to the furnace from a space that is well ventilated with outdoor air (such as an attic or crawl space) and the space is well isolated from the living space or garage. Combustion air requirements for this option are the same as the requirements for providing outside air for combustion for a single pipe vent system. Refer to the “Air For Combustion and Ventilation” Section.
NOTICE
!
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow the instructions outlined below for each appliance being placed into operation could result in carbon monoxide poisoning or death.
The instructions included with this furnace DO NOT APPLY to vent systems that are located below the furnace.
CAREFULLY FOLLOW THE INSTRUCTIONS PROVIDED WITH THE EXTERNAL VENT TRAP KIT FOR LAYING OUT THE VENTING SYSTEM AND THE DRAIN SYSTEM when all or part of the venting
system is placed below the furnace. Proper configuration of the venting and drain system is critical
when placing all or part of the venting system below the level of the furnace. VENT GASSES COULD BE RELEASED FROM THE DRAINAGE SYSTEM if the instructions provided with the External Vent Trap Kit are not followed.
Locating the Vent Termination
General
NOTE: Termination Requirements for the Provinces of Alberta and Saskatchewan are located at the end of this section.
Combustion--air inlet pipe (direct vent/2--pipe system only) and vent pipe must terminate outside structure, either through sidewall or roof.
For vent termination clearance, references to National codes are shown in Fig. 44 for Direct Vent/2--Pipe system and Fig. 45 for Ventilated Combustion Air system. For exterior termination arrangements, refer to Fig. 46 for Direct Vent/2--Pipe system and Fig. 47 for Ventilated Combustion Air system. Contact Local code authorities for other requirements to and/or exemptions from the National codes shown in the figures.
Roof termination is often preferred since it is less susceptible to damage or contamination, is usually located away from adjacent structures, is less prone to icing conditions, and it often has less visible vent vapors. Sidewall terminations may require sealing or shielding of building surfaces with a corrosive resistance material due to the corrosive properties of combustion products from the vent system, as well as protection of adjacent structures.
OPTIONAL VENTING BELOW THE FURNACE
The venting system may be positioned below the furnace ONLY IF the factory accessory External Vent Trap Kit is used. The External Vent Trap Kit is only approved for PVC/ABS DWV venting systems.
CAREFULLY FOLLOW THE INSTRUCTIONS PROVIDED WITH THE EXTERNAL VENT TRAP KIT FOR LAYING OUT THE VENTING SYSTEM AND THE DRAIN SYSTEM. The instructions included with this
furnace DO NOT APPLY to vent systems that are located below the furnace.
NOTICE
RECOMMENDED SUPPORT FOR VENT TERMINATIONS
It is recommended that sidewall vent terminations in excess of 24 inches (0.6 M) or rooftop terminations in excess of 36 inches (1 M) in vertical length be supported by EITHER the Direct Vent Termination Kit shown in Table 12 or by field--supplied brackets or supports fastened to the structure.
When determining appropriate location for termination, consider the following guidelines:
1. Comply with all clearance requirements stated in Fig. 44 or Fig. 45 per application.
2. Termination or termination kit should be positioned where vent vapors will not damage plants/shrubs or air condi­tioning equipment.
3. Termination or termination kit should be positioned so that it will not be affected by wind eddy, such as inside building corners, nor by recirculation of flue gases, airborne leaves, or light snow.
42
Page 43
4. Termination or termination kit should be positioned where it will not be damaged by or subjected to foreign objects such as stones, balls, etc.
5. Termination or termination kit should be positioned where vent vapors are not objectionable.
Direct Vent / 2-Pipe System
Direct vent (2--pipe) vent and combustion air pipes must terminate outside the structure. See Fig. 44 For references to vent clearances re. Allowable vent and combustion air terminations are shown in Fig. 46.
!
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow the instructions outlined below for each appliance being placed into operation could result in carbon monoxide poisoning or death.
For all venting configurations for this appliance and other gas appliances placed into operation for this structure, provisions for adequate combustion, ventilation, and dilution air must be provided in accordance with: U.S.A. Installations: Section 9.3 NFPA 54/ANSI Z223.1
--2009, Air for Combustion and Ventilation and applicable provisions of the local building codes.
Canadian Installations: Part 8 of CAN/CSA--B149.1--10. Venting Systems and Air Supply for Appliances and all authorities having jurisdiction.
Ventilated Combustion Air
The vent pipe for a Ventilated Combustion Air System must terminate outdoors. See Fig. 45 For references to vent clearances required by National code authorities. Allowable vent terminations are shown in Fig. 47. The combustion air pipe terminates in a well--ventilated attic or crawl space. Follow the clearances as shown in Fig. 49.
The combustion air pipe cannot terminate in attics or crawl spaces that use ventilation fans designed to operate in the heating season. If ventilation fans are present in these areas, the combustion air pipe must terminate outdoors as a Direct Vent System.
Termination Requirements for the Provinces of Alberta and Saskatchewan
The Provinces of Alberta and Saskatchewan require a minimum unobstructed distance of 4 ft. (1.2 M) from the foundation to the property line of the adjacent lot for vent termination of any appliance with an input over 35,000 btuh. If there is less than 4 ft. (1.2 M) of unobstructed distance to the property line of the adjacent lot, no type of vent termination is permitted for appliances with inputs greater than 35,000 btuh.
There are no additional restrictions on unobstructed distances greater than 8 ft. (2.4 M). All single, two-pipe and concentric vents may be used, providing all other Code and manufacturer’s requirements in these instructions are adhered to. Refer to the appropriate Vent Termination section above for locating the vent termination
If the unobstructed distance from the foundation to the property line of the adjacent lot is no less than 4 ft. (1.2 M) and no greater than 8 ft. (2.4 M), it will be necessary to re-direct the flue gas plume. In this situation, a concentric vent kit cannot be used. A 2-pipe termination (or single pipe termination when permitted with ventilated combustion air applications) that re-directs the flue gas
away by use of an elbow or tee, certified to ULC S636 from the adjacent property line must be used. See Fig. 48.
The concentric vent kit currently cannot be modified to attach an elbow to the vent portion of the rain cap. A tee attached to the rain cap could potentially direct the flue gas plume toward the intake air stream and contaminate the incoming combustion air for the furnace.
Refer to Fig. 48 for terminations approved for use in Alberta and Saskatchewan.
Size the Vent and Combustion Air Pipes
General
Furnace combustion air and vent pipe connections are sized for 2-in. (50 mm ND) PVC/ABS DWV pipe. The combustion air and vent pipe connections also accommodate 60 mm polypropylene venting systems with outside diameters of approximately 60 mm (2--3/8 inches). Any pipe diameter change should be made outside furnace casing in vertical pipe. Any change is diameter to the pipe must be made as close to the furnace as reasonably possible.
The Maximum Vent Length for the vent and combustion air pipe (when used) is determined from the Maximum Equivalent Vent Length in Table 15 or 17, minus the number of fittings multiplied by the deduction for each type of fitting used from Table 16.
NOTICE
OPTIONAL CONFIGURATION FOR COMBUSTION AIR INLET PIPE
In applications where there is a risk of excessive moisture entering the combustion air inlet pipe, a moisture trap may be added to the inlet pipe to help prevent moisture from entering the furnace from the combustion air inlet pipe. See Fig. 51.
When sizing venting systems, the equivalent length of the optional moisture trap (15 feet/5 M) must be taken into account.
Optional Combustion Air Inlet Moisture Trap
As an option to prevent moisture from trickling into the furnace vestibule, a trap can be installed in the intake air pipe near the furnace. Connecting a drain line to the trap is optional as trace amounts of moisture will evaporate into the intake air stream. If the combustion air inlet is located near a moisture exhaust duct, or there are other concerns of excessive moisture being drawn into the combustion air inlet, it is encouraged to connect a drain line to the trap.
The trap can be constructed from a running tee of the same diameter of the intake air pipe with EITHER a removable cap attached to a 6-inch long pipe connected to the tee or the External Vent Trap Kit to help prevent contaminants from entering the furnace. See Fig. 51.
The External Vent Trap Kit accessory may be used as a trap for the combustion air inlet pipe if a large amount of moisture must be removed. The drain line may be connected to the same drain as the furnace condensate and the evaporator coil condensate line ONLY if the inlet air trap drain and the evaporator coil drain empty into an open segment of pipe above the drain. See Fig.12. When using the External Vent Trap Kit, refer to those instructions for proper drain connections.
The tee may also be connected to the intake air pipe on the side of the casing. See Fig. 51.
59MN7A
43
Page 44
In any configuration, it will be necessary to add the equivalent length of the tee (15 feet/5 M) to the Total Equivalent Vent Length of the venting system.
NOTICE
ADDITIONAL INFORMATION FOR POLYPROPYLENE VENTING SYSTEMS
Polypropylene venting systems include flexible vent pipe. These flexible vent pipes have a different equivalent vent length than straight sections of PVC/ABS DWV vent pipe. Be sure to make the appropriate deductions from the Maximum Equivalent Vent Length (MEVL), or additions to the Total Equivalent Vent Length (TEVL), when applying flexible vent pipes in polypropylene venting systems. See the polypropylene vent system manufacturer’s installation instructions for details.
When using metric-sized venting systems, use these equivalencies for obtaining the proper MEVL from the Tables: Use 2” Vent Tables for 60 mm (o.d.) vent systems Use 3” Vent Tables for 80 mm (o.d.) vent systems
59MN7A
Use 4” Vent Tables for 100 mm (o.d.) vent systems
The measured length of pipe used in a single or 2--pipe termination is included in the total vent length. Include deductions from the Maximum Equivalent Vent Length (MEVL) contained in the Venting Tables for elbows and flexible vent pipe. Factory accessory concentric vent terminations or pipe lengths and elbows used for “standard” vent terminations do not require a deduction from the Maximum Equivalent Vent Length. See vent termination figures associated with Table 15. Include a deduction for a Tee when used for Alberta and Saskatchewan terminations.
NOTE: Polypropylene venting systems MAY require additional deductions from the MEVL, or additions to the TEVL, for vent terminations and flexible pipe sections. See the polypropylene venting system manufacturer’s instructions for details on equivalent lengths of vent terminations and flexible vent pipes, and for calculating total vent lengths.
To calculate the Total Equivalent Vent Length (TEVL) of the venting system:
1. Measure the individual distance from the furnace to the ter­mination for each pipe.
2. Count the number of elbows for each pipe.
3. For each pipe, multiply the number of elbows by the equi­valent length for the type of elbow used. Record the equi­valent length of all the elbows for each pipe.
4. If a Tee is used on the termination (Alberta and Saskat­chewan, when required) record the equivalent length of the Tee u sed .
5. Calculate Total Equivalent Vent Length by adding the equi­valent lengths of the fittings to the lengths of the individual vent and combustion air pipes.
6. When using polypropylene venting systems with flexible vent pipes, perform adjustments for the equivalent length of the flexible vent pipe to the calculated total equivalent venting system length. See the polypropylene vent system manufacturer’s instructions for details.
7. Select a diameter of vent pipe from Tables 15 and 17 and note the Maximum Equivalent Vent Length (MEVL) shown for that application for that specific furnace input size. Compare the Total Equivalent Vent Length (TEVL) to the MEVL:
8. If the Total Equivalent Vent Length is shorter than the Maximum Equivalent Vent Length for the diameter of pipe chosen, then that diameter of pipe selected may be used.
9. If the Total Vent Length is longer than the Maximum
Equivalent Vent Length for the diameter of pipe chosen, that diameter pipe MAY NOT be used for venting the furnace. Try the next larger diameter pipe
NOTE: If the calculated Total Equivalent Vent Lengths results in different diameter pipes for the vent and combustion air, select the larger diameter for both pipes.
NOTE: If the Maximum Vent Length for diameter of the pipe selected is longer than the measured length and the equivalent length of all the fittings and terminations (TEVL), recalculate Total Equivalent Vent Length using the next smaller diameter. If the Maximum Equivalent Vent Length is still longer than the longer TEVL of the vent pipe or combustion air pipe, then that diameter of pipe selected may be used.
When installing vent systems pipe lengths of 10 ft. (3 M) or less, use the smallest allowable pipe diameter. Using a pipe size greater than required for short venting systems may result in loss of efficiency, incomplete combustion, flame disturbance, or flame sense lockout.
For vent systems longer than 10 ft. (3 M), any larger diameter vent pipe shown in Table 15 or 17 FOR THAT SIZE FURNACE may be used.
.
Combustion Air and Vent Piping Insulation Guidelines
NOTE: Use closed cell, neoprene insulation or equivalent.
The vent pipe may pass through unconditioned areas. The amount of exposed pipe allowed is shown in Table 14.
1. Using winter design temperature (used in load calculations), find appropriate temperature for your application and fur­nace model.
2. Determine the amount of total and exposed vent pipe.
3. Determine required insulation thickness for exposed pipe length(s).
4. When combustion air inlet piping is installed above a sus­pended ceiling, the pipe MUST be insulated with moisture resistant insulation such as Armaflex or other equivalent type of insulation.
5. Insulate combustion air inlet piping when run in warm, hu­mid spaces.
6. Install the insulation per the insulation manufacturer’s in­stallation instructions.
NOTE: Pipe length (ft. / M) specified for maximum pipe lengths located in unconditioned spaces cannot exceed total allowable pipe length as calculated from Table 15 or 17.
Configure the Furnace
!
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury or death.
To route the vent pipe and combustion air pipe through the furnace, the manufacturer supplied kit must be used. Failure to properly seal the blower compartment from the furnace vestibule could result in the circulation of carbon monoxide throughout the structure. The vent pipe and combustion air pipe must be a continuous pipe while passing through the blower compartment. Seals supplied in this kit must be installed per the instructions provided. Follow all procedures outlined in these instructions.
44
Page 45
Install the Vent and Combustion Air Pipes
With the furnace installed in the required position, remove the desired knockouts from the casing. It will be necessary to remove one knockout for the vent pipe and the other knockout for the combustion air connection. See Fig. 11.
Use a flat blade screwdriver and tap on the knockout on opposite sides, where the knockout meets the casing. Fold the knockout down with duct pliers and work the knockout back and forth until it is removed. Trim any excess metal from the knockout with tin snips.
The vent elbow can be rotated to the required location on the casing if necessary. See Fig. 37. To rotate the vent elbow:
1. Loosen the clamp on the inlet of the vent elbow attached to the inducer.
2. Rotate the vent elbow to the required position. There are rounded notches in the vent elbow to align it with the inducer housing for each orientation.
3. Tighten the clamp around the vent elbow. Torque the clamp to 15 lb--in. See Fig. 38--41.
Installing the Vent Pipe Adapter and Combustion Air Pipe Adapter
!
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury or death.
To route the vent pipe and combustion air pipe through the furnace, the manufacturer supplied kit must be used. Failure to properly seal the blower compartment from the furnace vestibule could result in the circulation of carbon monoxide throughout the structure. The vent pipe and combustion air pipe must be a continuous pipe while passing through the blower compartment. Seals supplied in this kit must be installed per the instructions provided. Follow all procedures outlined in these instructions.
!
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury or death.
DO NOT use cement to join polypropylene venting systems. Follow the polypropylene venting system manufacturer’s instructions for installing polypropylene venting systems.
NOTE: The rubber coupling that attaches to the vent pipe adapter must be used. The adapter seals the vent pipe to the casing and reduces the strain on the vent elbow attached to the inducer.
1. Apply the gaskets to the vent pipe and combustion air pipe adapters. If supplied, remove and discard round center “slug” from interior of gasket. See Fig. 36.
NOTE: The vent pipe adapter can be distinguished from the inlet pipe adapter by the absence of an internal pipe--stopping ring. The vent pipe can pass through the vent pipe adapter; it cannot pass through the inlet pipe adapter.
2. Align the screw holes in the plastic vent pipe adapter with the dimples in the casing.
3. Pilot drill the screw holes for the adapter in the casing and attach the vent pipe adapter to the furnace with sheet metal screws
4. Slide the end of the rubber vent coupling with notches in it over the standoffs on the vent pipe adapter.
5. Insert a length of vent pipe through the coupling into the outlet of the vent elbow.
6. Tighten the clamp around the outlet of the vent elbow. Torque the clamp to 15 lb--in.
NOTICE
The following instructions are for PVC/ABS DWV vent piping only. DO NOT USE THESE TECHNIQUES FOR POLYPROPYLENE VENT PIPING SYSTEMS. See the polypropylene vent system manufacturer’s instructions for installing polypropylene venting systems.
Install the remaining vent and combustion air pipes as shown below. It is recommended that all pipes be cut, prepared, and preassembled before permanently cementing any joint.
1. Working from furnace to outside, cut pipe to required length(s).
2. De--burr inside and outside of pipe.
3. Chamfer outside edge of pipe for better distribution of primer and cement.
4. Clean and dry all surfaces to be joined.
5. Check dry fit of pipe and mark insertion depth on pipe.
6. Insert the vent pipe into the vent elbow.
7. Torque clamp on vent elbow 15 lb--in.
8. Torque clamp on vent coupling 15 lb--in.
9. Insert the combustion air pipe into the adapter.
10. Pilot drill a screw hole through the adapter into the combus­tion air pipe and secure the pipe to the adapter with sheet metal screws. DO NOT DRILL INTO POLYPROPYLENE VENT PIPES. Use an optional accessory vent coupling, if needed.
11. Seal around the combustion air pipe with silicone or foil tape. SILICONE SEALERS MAY NOT BE APPROPRI­ATE FOR POLYPROPYLENE VENT SYSTEMS. SEE POLYPROPYLENE VENT SYSTEM MANUFAC­TURER’S INSTRUCTIONS.
12. After pipes havebeen cut and preassembled, apply generous layer of cement primer to pipe fitting socket and end of pipe to insertion mark. Quickly apply approved cement to end of pipe and fitting socket (over primer). Apply cement in a light, uniform coat on inside of socket to prevent buildup of excess cement. Apply second coat. DO NOT CEMENT POLYPROPYLENE FITTINGS.
13. While cement is still wet, twist pipe into socket with 1/4--in. turn. Be sure pipe is fully inserted into fitting socket.
14. Wipe excess cement from joint. A continuous bead of ce­ment will be visible around perimeter of a properly made joint.
15. Handle pipe joints carefully until cement sets.
16. Horizontal portions of the venting system shall be suppor­ted to prevent sagging. Support combustion air piping and vent piping a minimum of every 5 ft. (1.5M)[3 ft. (.91M) for SDR--21 or --26 PVC] using perforated metal hanging strap or commercially available hangars designed to support plastic pipe.
17. Prevent condensate from accumulating in the pipes by slop­ing the combustion air piping and vent piping downward towards furnace a minimum of 1/4-in. per linear ft. with no sags between hangers.
18. Complete the vent and combustion air pipe installation by connecting the concentric vent or by installing the required
59MN7A
45
Page 46
termination elbows as shown in Fig. 46, 47 and 48. For Ventilated Combustion Air Termination, See Fig. 49.
19. Use appropriate methods to seal openings where combus­tion air pipe and vent pipe pass through roof or sidewall.
!
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury or death.
DO NOT use cement to join polypropylene venting systems. Follow the polypropylene venting system manufacturer’s instructions for installing polypropylene venting systems.
Optional Installation of the Vent Pipe
NOTE: DO NOT USE THIS TECHNIQUE FOR
POLYPROPYLENE VENTING SYSTEMS. This option provides a disconnect point for the vent pipe. The vent
pipe must be cemented to the plastic vent pipe adapter to maintain a sealed vestibule. See Fig. 42.
59MN7A
1. Insert a length of vent pipe through the casing into the outlet of the vent elbow.
2. Slide the plastic vent pipe adapter over the length of the vent pipe down to the furnace casing. Mark the pipe where it is flush with the outlet of the adapter.
3. Remove the pipe from the furnace and the adapter and cut off any excess pipe.
4. Clean and prime the end of the pipe that is flush with the vent adapter with a primer that is appropriate for the type of pipe being used.
5. Re--insert the pipe through the casing into the vent elbow.
6. Tighten the clamp around the outlet of the vent elbow. Torque the clamp to 15 lb--in.
7. Apply cement to the end of the pipe and to the inside of the plastic vent adapter.
8. Slide the adapter over the vent pipe and align the screw holes in the adapter with the dimples in the furnace casing.
9. Pilot drill 1/8--in. screw holes for the adapter in the casing and secure the adapter to the furnace with sheet metal screws.
10. Loosen the clamps on the rubber vent coupling.
11. Slide the end of the coupling with notches in it over the standoffs in the vent pipe adapter.
12. Tighten the clamp of the coupling over the vent pipe adapter. Torque the lower clamp around the vent pipe adapter to 15 lb--in.
13. Pilot drill a 1/8--in. hole in the combustion air pipe adapter.
14. Complete the vent and combustion air pipe as shown in “Install the Vent and Combustion Air Pipe.”
NOTICE
FOR POLYPROPYLENE VENTING SYSTEMS
When using polypropylene venting systems, all venting materials used, including the vent terminations, must be from the same manufacturer.
Installing the Vent Termination
Roof Terminations
A roof termination of any type will require a 4-in. (102 mm) flashing for a 2 inch (50 mm ND) concentric vent or a 5--in.
diameter (127 mm) flashing for a 3-inch (80 mm ND) concentric vent kit. For two-pipe or single pipe vent systems, a flashing for each pipe of the required diameter will be necessary.
It is recommended that the flashing be installed by a roofer or competent professional prior to installing the concentric vent. The terminations can be installed on a flat or pitched roof.
Concentric Vent
Single or multiple concentric vent must be installed as shown in Fig. 46. Maintain the required separation distance between vents or pairs of vents as shown in Fig. 46 and all clearance shown in Fig. 44.
NOTE: Follow the instructions of the vent terminal manufacturer. These instructions are provided as a reference, only.
Cut one 4--in. (102 mm) diameter hole for 2--in. (50 mm ND) kit, or one 5--in. (127 mm) diameter hole for 3--in. (80 mm ND) kit in the desired location.
Loosely assemble concentric vent/combustion air termination components together using instructions in kit.
Slide assembled kit with rain shield REMOVED through hole in wall or roof flashing.
NOTE: Do not allow insulation or other materials to accumulate inside of pipe assembly when installing it through hole.
Disassemble loose pipe fittings. Clean and cement using same procedures as used for system piping. DO NOT CEMENT POLYPROPYLENE FITTINGS.
Two--Pipe (Direct Vent) and Single--Pipe (Ventilated Combustion Air) Terminations
Single and two pipe vent terminals must be installed as shown in Fig. 46 and 47. Maintain the required separation distance between vents or pairs of vents as shown in Fig. 46 and 47. and all clearance shown in Fig. 44 and 45.
NOTICE
RECOMMENDED SUPPORT FOR VENT TERMINATIONS
It is recommended that rooftop vent terminations in excess of 36 inches (1 M) in vertical length be supported by EITHER the Direct Vent Termination Kit shown in Table 12 or by field--supplied brackets or supports fastened to the structure.
Cut the required number of holes in the roof or sidewall for vent and (when used) combustion air pipes. Sidewall holes for two-pipe vent terminations should be side-by-side, allowing space between the pipes for the elbows to fit on the pipes.
Holes in the roof for direct--vent (two pipe) terminations should be spaced no more than 18 in. (457 mm) apart to help avoid vent gas recirculation into combustion air intake.
Termination elbows will be installed after the vent and (if used) combustion air pipe is installed.
Sidewall Terminations Concentric Vent Termination
NOTE: Follow the instructions of the vent terminal manufacturer.
These instructions are provided as a reference only. Determine an appropriate location for termination kit using the guidelines provided in section “Locating The Vent Termination” in this instruction.
1. Cut one 4--in. diameter hole for 2--in. kit, or one 5--in. dia­meter hole for 3--in. kit.
2. Loosely assemble concentric vent/combustion air termina­tion components together using instructions in kit.
3. Slide assembled kit with rain shield REMOVED through hole.
46
Page 47
NOTE: Do not allow insulation or other materials to accumulate inside of pipe assembly when installing it through hole.
4. Locate assembly through sidewall with rain shield posi­tioned no more than 1--in. (25 mm) from wall as shown in Fig. 46.
5. Disassemble loose pipe fittings. Clean and cement using same procedures as used for system piping. DO NOT CE­MENT POLYPROPYLENE FITTINGS.
2--Pipe (Direct Vent) and 1--Pipe (Ventilated Combus­tion Air) Vent Termination
NOTE: Follow the instructions of the vent terminal manufacturer.
These instructions are provided as a reference, only.
NOTICE
RECOMMENDED SUPPORT FOR VENT TERMINATIONS
It is recommended that sidewall vent terminations in excess of 24 inches (0.6 M) in vertical length be supported by EITHER the Direct Vent Termination Kit shown in Table 12 or by field--supplied brackets or supports fastened to the structure.
Determine an appropriate location for termination kit using the guidelines provided in section “Locating The Vent Termination” in
this instruction.
1. Cut two holes, one for each pipe, of appropriate size for pipe size being used.
2. Loosely install elbow in bracket (if used) and place as­sembly on combustion--air pipe.
3. Install bracket as shown in Fig. 46 and 48.
NOTE: For applications using vent pipe option indicated by dashed lines in Fig. 46 and 47, rotate vent elbow 90_ from position.
4. Disassemble loose pipe fittings. Clean and cement using same procedures as used for system piping. DO NOT CE­MENT POLYPROPYLENE FITTINGS.
For ventilated Combustion Air Terminations, terminate as shown in Fig. 47.
(Direct Vent / 2-Pipe System ONLY)
When two or more furnaces are vented near each other, two vent terminations may be installed as shown in Fig. 46, but next vent termination, or pair of vent terminations, must be at least 36 in. (914 mm) away from the first two terminations. It is important that vent terminations be made as shown in Fig. 46 to avoid recirculation of vent gases.
Inducer Outlet Restrictor
The loose parts bag may contain an inducer outlet restrictor. The outlet restrictor is NOT used on these furnaces. Discard restrictor.
59MN7A
Table 13 – Approved Combustion-Air and Vent Pipe, Fitting and Cement Materials (U.S.A. Installations)
ASTM SPECIFICATION
(MARKED ON MATERIAL)
D1527 ABS Pipe — — S c h e d u le --- 4 0 D1785 PVC Pipe — — S c h e d u le --- 4 0 D2235 For ABS — — Solvent Cement For ABS D2241 PVC Pipe — — SD R --- 2 1 & S D R --- 2 6 D2466 PVC — Fittings — S c h ed u l e --- 4 0 D2468 ABS — Fittings — S c he d u l e --- 4 0 D2564 For PVC — — Solvent Cement For PVC D2661 ABS Pipe Fittings — DWV at Schedule--- 40 IPS sizes D2665 PVC Pipe Fittings — DWV
F438 CPVC — Fittings — S c h e d u le --- 4 0 F441 CPVC Pipe — — S c h e d u l e --- 4 0 F442 CPVC Pipe — — SDR F493 For C PVC — — Solvent Cement For CPVC
F628 ABS Pipe — —
F656 For PVC — — Primer For PVC F891 PVC Pipe — — Cellular Core Schedule --- 40 & DWV
MATERIAL PIPE FITTINGS
SOLVENT CEMENT
AND PRIMERS
DESCRIPTION
Cellular Core DWV at Schedule --- 40
IPS sizes
47
Page 48
Modulating
Furnace High
Heat Input
60000
Winter Design
Te m p ° F ( ° C )
20 (-10)
0 (-20)
-20 (-30)
-40 (-40)
Table 14 – Maximum Allowable Exposed Vent Lengths Insulation Table -- Ft. / M
Maximum Length of Uninsulated and Insulated Vent Pipe-Ft (M)
Pipe
Length in
Ft. & M
Ft. 34.0 29.0 28.0 23.0 N/A 55.0 88.0 79.0 69.0 N/A 55.0 104.0 93.0 81.0 N/A
M 10.4 8.8 8.5 7.0 N/A 16.8 26.8 24.1 21.0 N/A 16.8 31.7 28.3 24.7 N/A
Ft. 14.0 9.0 7.0 0.0 N/A 55.0 49.0 43.0 34.0 N/A 55.0 60.0 52.0 42.0 N/A
M 4.3 2.7 2.1 0.0 N/A 16.8 14.9 13.1 10.4 N/A 16.8 18.3 15.8 12.8 N/A
Ft. 5.0 0.0 0.0 0.0 N/A 41.0 32.0 26.0 18.0 N/A 50.0 40.0 33.0 24.0 N/A
M 1.5 0.0 0.0 0.0 N/A 12.5 9.8 7.9 5.5 N/ A 15.2 12.2 10.1 7.3 N/A
Ft. 0.0 0.0 0.0 0.0 N/A 30.0 21.0 16.0 8.0 N/A 37.0 28.0 22.0 13.0 N/A
M 0.0 0.0 0.0 0.0 N/A 9.1 6.4 4.9 2.4 N/A 11.3 8.5 6.7 4.0 N/A
No Insulatio n 3/8-in. (9.5 mm) 1/2-in. (12.7 mm)
Pipe Diameter-inches (mm) Pipe Diameter-inches (mm) Pipe Diameter-inches (mm)
1.5 2.0 2.5 3.0 4.0 1.5 2.0 2.5 3.0 4.0 1.5 2.0 2.5 3.0 4.0
(38) (51) (64) (76) (102) (38) (51) (64) (76) (102) (38) (51) (64) (76) (102)
20 (-10)
0 (-20)
60600
59MN7A
80000
100000
-20 (-30)
-40 (-40)
20 (-10)
0 (-20)
-20 (-30)
-40 (-40)
20 (-10)
0 (-20)
-20 (-30) Ft. N/A 8.0 6.0 0.0 0.0 N/A 50.0 49.0 38.0 23.0 N/A 50.0 60.0 48.0 32.0
-40 (-40) Ft. N/A 1.0 0.0 0.0 0.0 N/A 42.0 34.0 24.0 10.0 N/A 50.0 43.0 32.0 18.0
Ft. 34.0 29.0 28.0 23.0 N/A 55.0 88.0 79.0 69.0 N/A 55.0 104.0 93.0 81.0 N/A
M 10.4 8.8 8.5 7.0 N/A 16.8 26.8 24.1 21.0 N/A 16.8 31.7 28.3 24.7 N/A
Ft. 14.0 9.0 7.0 0.0 N/A 55.0 49.0 43.0 34.0 N/A 55.0 60.0 52.0 42.0 N/A
M 4.3 2.7 2.1 0.0 N/A 16.8 14.9 13.1 10.4 N/A 16.8 18.3 15.8 12.8 N/A
Ft. 5.0 0.0 0.0 0.0 N/A 41.0 32.0 26.0 18.0 N/A 50.0 40.0 33.0 24.0 N/A
M 1.5 0.0 0.0 0.0 N/A 12.5 9.8 7.9 5.5 N/ A 15.2 12.2 10.1 7.3 N/A
Ft. 0.0 0.0 0.0 0.0 N/A 30.0 21.0 16.0 8.0 N/A 37.0 28.0 22.0 13.0 N/A
M 0.0 0.0 0.0 0.0 N/A 9.1 6.4 4.9 2.4 N/A 11.3 8.5 6.7 4.0 N/A
Ft. 35.0 39.0 39.0 33.0 25.0 35.0 118.0 107.0 92.0 76.0 35.0 130.0 125.0 109.0 90.0
M 10.7 11.9 11.9 10.1 7.6 10.7 36.0 32.6 28.0 23.2 10.7 39.6 38.1 33.2 27.4
Ft. 22.0 16.0 14.0 7.0 0.0 35.0 69.0 60.0 49.0 35.0 35.0 83.0 72.0 60.0 45.0
M 6.7 4.9 4.3 2.1 0.0 10.7 21.0 18.3 14.9 10.7 10.7 25.3 21.9 18.3 13.7
Ft. 11.0 5.0 2.0 0.0 0.0 35.0 46.0 39.0 29.0 16.0 35.0 57.0 48.0 37.0 23.0
M 3.4 1.5 0.6 0.0 0.0 10.7 14.0 11.9 8.8 4.9 10.7 17.4 14.6 11.3 7.0
Ft. 4.0 0.0 0.0 0.0 0.0 35.0 33.0 26.0 17.0 4.0 35.0 41.0 34.0 24.0 11.0
M 1.2 0.0 0.0 0.0 0.0 10.7 10.1 7.9 5.2 1.2 10.7 12.5 10.4 7.3 3.4
Ft. N/A 47.0 47.0 41.0 32.0 N/A 50.0 110.0 112.0 93.0 N/A 50.0 110.0 132.0 110.0
M N/A 14.3 14.3 12.5 9.8 N/A 15.2 33.5 34.1 28.3 N/A 15.2 33.5 40.2 33.5
Ft. N/A 21.0 19.0 12.0 1.0 N/A 50.0 74.0 61.0 45.0 N/A 50.0 89.0 74.0 57.0
M N/A 6.4 5.8 3.7 0.3 N/ A 15.2 22.6 18.6 13.7 N/A 15.2 27.1 22.6 17.4
M N/A 2.4 1.8 0.0 0.0 N/ A 15.2 14.9 11.6 7.0 N/A 15.2 18.3 14.6 9.8
M N/A 0.3 0.0 0.0 0.0 N/ A 12.8 10.4 7.3 3.0 N/A 15.2 13.1 9.8 5.5
20 (-10)
0 (-20)
120000
-20 (-30)
-40 (-40)
* Pipe length (ft) specified for maximum pipe lengths located in unconditioned spaces. Pipes located in unconditioned space cannot exceed total allowable pipe length calculated from Table 15 or 17.
† Insulation thickness based on R value of 3.5 per in.
Ft. N/A N/A 15.0 49.0 40.0 N/A N/A 15.0 100.0 111.0 N/A N/A 15.0 100.0 131.0
M N/A N/A 4.6 14.9 12.2 N/A N/A 4.6 30.5 33.8 N/A N/A 4.6 30.5 39.9
Ft. N/A N/A 15.0 17.0 6.0 N/A N/A 15.0 75.0 57.0 N/A N/A 15.0 90.0 70.0
M N/A N/A 4.6 5.2 1.8 N/A N/A 4.6 22.9 17.4 N/A N/A 4.6 27.4 21.3
Ft. N/A N/A 10.0 2.0 0.0 N/A N/A 15.0 48.0 32.0 N/A N/A 15.0 59.0 42.0
M N/A N/A 3.0 0.6 0.0 N/A N/A 4.6 14.6 9.8 N/A N/A 4.6 18.0 12.8
Ft. N/A N/A 1.0 0.0 0.0 N/ A N/A 15.0 32.0 17.0 N/A N/A 15.0 41.0 25.0
M N/A N/A 0.3 0.0 0.0 N/A N/A 4.6 9.8 5.2 N/A N/A 4.6 12.5 7.6
48
Page 49
NOTE: Maximum Equivalent Vent Length (MEVL) includes standard and concentric vent termination and does NOT include elbows.
Use Table 16 - Deductions from Maximum Equivalent Vent Length to determine allowable vent length for each application.
Table 15 – Maximum Equivalent Vent Length -- Ft. (M)
0 to 4500 Ft. (0 to 1370 M) Altitude
Altitude
FT (M)
0 to 2000 (0 to 610)
2001 to 3000
(610 to 914)
3001 to 4000 (914 to 1219)
4001 to 4500
(1219 to
1370)
* See notes at end of venting tables. *See Table 17 for altitudes over 4500 ft. (1370 M)
Unit Size
BTU/Hr
60,000 55 (16.8) 135 (41.1) 235 (71.6) 265 (80.8) NA
80,000 35 (10.7) 130 (39.6) 175 (53.3) 235 (71.6) 265 (80.8)
100,000 NA 50 (15.2) 110 (33.5) 235 (71.6) 265 (80.8)
120,000 NA NA 15 (4.6) 100 (30.5) 250 (76.2)
60,000 45 (13.7) 127 (38.7) 222 (67.7) 250 (76.2) NA
80,000 30 (9.1) 90 (27.4) 165 (50.3) 222 (67.7) 249 (75.9)
100,000 NA 40 (12.2) 104 (31.7) 223 (68.0) 250 (76.2)
120,000 NA NA 11 (3.4) 93 (28.3) 237 (72.2)
60,000 40 (12.2) 119 (36.3) 210 (64.0) 235 (71.6) NA
80,000 25 (7.6) 85 (25.9) 155 (47.2) 210 (64.0) 232 (70.7)
100,000 NA 40 (12.2) 98 (29.9) 211 (64.3) 236 (71.9)
120,000 NA NA 8 (2.4) 86 (26.2) 224 (68.3)
60,000 35 (10.7) 115 (35.1) 204 (62.2) 228 (69.5) NA
80,000 23 (7.0) 85 (25.9) 150 (45.7) 202 (61.6) 224 (68.3)
100,000 NA 40 (12.2) 94 (28.7) 205 (62.5) 229 (69.8)
120,000 NA NA NA 83 (25.3) 217 (66.1)
DIRECT VENT (2-PIPE) AND VENTILATED COMBUSTION AIR ONLY
Vent Pipe Diameter (in.)
1-1/2 2 2-1/2 3 4
59MN7A
ELBOW CONFIGURATIONS VENT TERMINAL CONFIGURATIONS
Concentric
Long
Medium
Mitered
Standard
Table 16 – Deductions from Maximum Equivalent VentLength -- Ft. (M)
Pipe Diameter (in): 1-1/2 2 2-1/2 3 4
Mitered 90º Elbow 8 (2.4) 8 (2.4) 8 (2.4) 8 (2.4) 8 (2.4)
Medium Radius 90º Elbow 5 (1.5) 5 (1.5) 5 (1.5) 5 (1.5) 5 (1.5)
Long Radius 90º Elbow 3 (0.9) 3 (0.9) 3 (0.9) 3 (0.9) 3 (0.9)
Mitered 45º Elbow 4 (1.2) 4 (1.2) 4 (1.2) 4 (1.2) 4 (1.2)
Medium Radius 45º Elbow 2.5 (0.8) 2.5 (0.8) 2.5 (0.8) 2.5 (0.8) 2.5 (0.8)
Long Radius 45º Elbow 1.5 (0.5) 1.5 (0.5) 1.5 (0.5) 1.5 (0.5) 1.5 (0.5)
Tee 16 (4.9) 16 (4.9) 16 (4.9) 16 (4.9) 16 (4.9)
Concentric Vent Termination NA 0 (0.0) NA 0 (0.0) NA
Standard Vent Termination 0 (0.0) 0 (0.0) 0 (0.0) 0 (0.0) 0 (0.0)
A11580
49
Page 50
Venting System Length Calculations
The Total Equivalent Vent Length (TEVL) for EACH combustion air or vent pipe equals the length of the venting system, plus the equivalent length of elbows used in the venting system from Table 16.
Standard vent terminations or factory accessory concentric vent terminations count for zero deduction. See vent system manufacturer’s data for equivalent lengths of flexible vent pipe or other termination systems. DO NOT ASSUME that one
foot of flexible vent pipe equals one foot of straight PVC/ABS DWV vent pipe. Compare the Total Equivalent Vent Length to the Maximum Equivalent Vent Lengths in Tables 15 and 17.
Example 1
A direct--vent 60,000 Btuh furnace installed at 2100 ft. (640 M). Venting system includes, FOR EACH PIPE, 100 feet (30 M) of vent pipe, 95 feet (28 M) of combustion air inlet pipe, (3) 90_ long radius elbows, (2) 45_ long radius elbows and a factory accessory concentric vent kit.
Can this application use 2--in. (50 mm ND) PVC/ABS DWV vent piping?
Measure the required linear length of air inlet and vent pipe; insert the longest of the two here:
Add equiv length of (3) 90º long-radius elbows (use the highest number of elbows for either the vent or inlet pipe)
Add equiv length of (2) 45º long-radius elbows (use the highest number of elbows for either the
59MN7A
vent or inlet pipe) Add equiv length of vent termination 0ft. From Table 16
Add correction for flexible vent pipe, if any 0ft.
Total Equivalent Vent Length (TEVL) 112 ft. Add all of the above lines
Maximum Equivalent Vent Length (MEVL) 127 ft. For 2” pipe from Table 15
Is TEVL less than MEVL? YES Therefore, 2” pipe may be used
3 x 3ft = 9ft. From Table 16
2 x 1.5 ft = 3ft. From T able 16
100 ft
Use length of the longer of the vent
or air inlet piping system
From Vent Manufacturer’s instructions;
zero for PVC/ABS DWV
Example 2
A direct--vent 60,000 Btuh furnace installed at 2100 ft. (640 M) Venting system includes, FOR EACH PIPE, 100 feet (30 M) of vent pipe, 95 feet (28 M) of combustion air inlet pipe, (3) 90_ long radius elbows, and a polypropylene concentric vent kit. Also includes 20 feet (6 M) of flexible polypropylene vent pipe, included within the 100 feet (30 M) of vent pipe.
Assume that one meter of flexible 60 mm or 80 mm polypropylene pipe equals 1.8 meters of PVC/ABS pipe. VERIFY FROM VENT
MANUFACTURER’S INSTRUCTIONS.
Can this application use 60 mm (O.D.) polypropylene vent piping? If not what size piping can be used?
Measure the required linear length of air inlet and vent pipe; insert the longest of the two here:
Add equiv length of (3) 90º long-radius elbows (use the highest number of elbows for either the vent or inlet pipe)
Add equiv length of (2) 45º long-radius elbows (use the highest number of elbows for either the vent or inlet pipe)
Add equiv length of of vent termination 9M x 3ft/M = 18 ft. From Vent Manufacturer’s instructions Add correction for flexible vent pipe, if any 1.8 x 20 ft = 36 ft. From Vent Manufacturer’s instructions Total Equivalent Vent Length (TEVL) 163 ft. Add all of the above lines
3 x 3ft = 9ft. From Vent Manufacturer’s instructions
0 x = 0ft. From Vent Manufacturer’s instructions
100 ft
Use length of the longer of the vent
or air inlet piping system
Maximum Equivalent Vent Length (MEVL) 127 ft. For 2” pipe from Table 15
Is TEVL less than MEVL? NO
Maximum Equivalent Vent Length (MEVL) 250 ft. For 3” pipe from Table 15
Is TEVL less than MEVL? YES Therefore, 80 mm pipe may be used
Therefore, 60mm pipe may NOT be used;
try 80 mm
50
Page 51
NOTE: Maximum Equivalent Vent Length (MEVL) includes standard and concentric vent termination and does NOT include elbows.
Use Table 16 - Deductions from Maximum Equivalent Vent Length to determine allowable vent length for each application.
Table 17 – Maximum Equivalent Vent Length -- Ft. (M)
4501 to 10,000 Ft. (0 to 1370 M) Altitude
Altitude
FT (M)
4501 to 5000
(1370 to
1524)
5001 to 6000
(1524 to
1829)
6001 to 7000
(1829 to
2134)
7001 to 8000
(2134 to
2438)
8001 to 9000
(2438 to
2743)
9001 to
10,000
(2743 to
3048)
Unit Size
60,000 35 (10.7) 111 (33.8) 198 (60.4) 221 (67.4) NA
80,000 23 (7.0) 85 (25.9) 146 (44.5) 195 (59.4) 216 (65.8)
100,000 NA 40 (12.2) 91 (27.7) 200 (61.0) 222 (67.7)
120,000 NA NA NA 80 (24.4) 211 (64.3)
60,000 37 (11.3) 103 (31.4) 186 (56.7) 207 (63.1) NA
80,000 22 (6.7) 76 (23.2) 137 (41.8) 183 (55.8) 200 (61.0)
100,000 NA 33 (10.1) 85 (25.9) 188 (57.3) 208 (63.4)
120,000 NA NA NA 74 (22.6) 199 (60.7)
60,000 35 (10.7) 96 (29.3) 174 (53.0) 194 (59.1) NA
80,000 20 (6.1) 71 (21.6) 120 (36.6) 171 (52.1) 185 (56.4)
100,000 NA 31 (9.4) 79 (24.1) 178 (54.3) 195 (59.4)
120,000 NA NA NA 68 (20.7) 187 (57.0)
60,000 32 (9.8) 89 (27.1) 163 (49.7) 181 (55.2) NA
80,000 18 (5.5) 66 (20.1) 120 (36.6) 159 (48.5) 170 (51.8)
100,000 NA 29 (8.8) 73 (22.3) 167 (50.9) 182 (55.5)
120,000 NA NA NA 62 (18.9) 175 (53.3)
60,000 30 (9.1) 82 (25.0) 152 (46.3) 168 (51.2) NA
80,000 17 (5.2) 62 (18.9) 111 (33.8) 148 (45.1) 156 (47.5)
100,000 NA 27 (8.2) 67 (20.4) 157 (47.9) 170 (51.8)
120,000 NA NA NA 56 (17.1) 164 (50.0)
60,000 27 (8.2) 76 (23.2) 142 (43.3) 156 (47.5) NA
80,000 15 (4.6) 57 (17.4) 103 (31.4) 137 (41.8) 142 (43.3)
100,000 NA 24 (7.3) 62 (18.9) 147 (44.8) 157 (47.9)
120,000 NA NA NA 51 (15.5) 153 (46.6)
DIRECT VENT (2-PIPE) AND VENTILATED COMBUSTION AIR ONLY
Vent Pipe Diameter
1-1/2 2 2-1/2 3 4
59MN7A
Notes:
1. Use only the vent pipe sizes shown for each furnace. It is NOT necessary to choose the smallest diameter pipe possible for venting.
2. NA - -- Not allowed. Pressure switch will not cl ose, or flame disturbance may result.
3. Vent sizing for Canadian installations over 4500 ft. (1370 M) above sea level are subject to acceptance by the local authorities having jurisdiction.
4. Size both the combustion air and vent pipe independently, then use the larger size for both pipes.
5. Assume the two 45_ elbows equal one 90_ elbow. Wide radius elbows are desirable and may be required in some cases.
6. Elbow and pipe sections within the furnace casing and at the vent termination should not be included in vent length or elbow count.
7. T he minimum pipe length is 5 ft. (2 M) linear feet (meters) for all applications.
8. U se 3--- in. (76 mm) diameter vent termination kit for in stallations requiring 4--- in. (102 mm) diameter pipe.
51
Page 52
Attach gaskets to vent pipe and combustion air adapters.
Vent Coupling and Adapter
A11314
Fig. 36 -- Vent Coupling and Adapter with Gaskets
59MN7A
VENT ELBOW CLAMP TORQUE 15 LB-IN.
MODULATING INDUCER ASSEMBLY
INDUCER OUTLET
Fig. 37 -- Inducer Vent Elbow
(Appearance May Vary)
VENT PIPE CLAMP TORQUE 15 LB-IN.
VENT ELBOW
A11286
52
Page 53
7
6
7
Any other unused
6
knockout may be used
for combustion air
connection.
Any other unused
knockout may be used
5
Rotate vent elbow to
1
3
2
&
5
4
required position.
A11309
for combustion air
connection.
Rotate vent elbow to
required position.
4
5
2
5
1
3
A11308
3
2
5
1
4
5
Any other unused
knockout may be used
7
6
for combustion air
connection.
A11310
Attach vent pipe adapter with gasket to furnace casing.
1
Align notches in rubber coupling over standoffs on adapter. Slide clamps over the coupling.
2
Slide vent pipe through adapter and coupling into vent elbow.
3
4
Insert vent pipe into vent elbow.
Torque all clamps 15 lb.-in.
5
6
Attach combustion air pipe adapter with gasket to furnace.
Attach combustion air pipe to adapter with silicone. Pilot drill a 1/8-in.
7
hole in adapter and secure with a #7 x 1/2-in sheet metal screw.
Fig. 38 -- Upflow Configurations
(Appearance May Vary)
59MN7A
A11399
53
Page 54
Rotate vent elbow to
required position.
3
2
5
1
4
5
Rotate vent elbow to
required position.
4
5
2
5
1
3
Any other unused
knockout may be used
for combustion air
connection.
6
7
A11311
6
7
A11312
59MN7A
A11313
Downflow Vertical
Requires Accessory Internal Vent Kit.
See Product Data for current kit number.
Attach vent pipe adapter with gasket to furnace casing.
1
Align notches in rubber coupling over standoffs on adapter. Slide clamps over the coupling.
2
Slide vent pipe through adapter and coupling into vent elbow.
3
4
Insert vent pipe into vent elbow.
Torque all clamps 15 lb.-in.
5
6
Attach combustion air pipe adapter with gasket to furnace.
Attach combustion air pipe to adapter with silicone. Pilot drill a 1/8-in.
7
hole in adapter and secure with a #7 x 1/2-in sheet metal screw.
Fig. 39 -- Downflow Configurations
(Appearance May Vary)
A11400
54
Page 55
HORIZONTAL LEFT ­VERTICAL VENT CONFIGURATION
HORIZONTAL LEFT ­RIGHT VENT CONFIGURATION*
*Requires Accessory Internal Vent Kit See Product Data for Current Kit Number
HORIZONTAL LEFT ­LEFT VENT CONFIGURATION
59MN7A
Attach vent pipe adapter with gasket to furnace casing.
1
Align notches in rubber coupling over standoffs on adapter. Slide clamps over the coupling.
2
Slide vent pipe through adapter and coupling into vent elbow.
3
4
Insert vent pipe into vent elbow.
Torque all clamps 15 lb.-in.
5
Attach combustion air pipe adapter with gasket to furnace.
6
Attach combustion air pipe to adapter with silicone. Pilot drill a 1/8-in.
7
hole in adapter and secure with a #7 x 1/2-in sheet metal screw.
A11340
Fig. 40 -- Horizontal Left
(Appearance May Vary)
55
Page 56
HORIZONTAL RIGHT ­VERTICAL VENT CONFIGURATION
59MN7A
HORIZONTAL RIGHT ­LEFT VENT CONFIGURATION* *Requires Internal Vent Kit See Product Data for Current Kit Number
HORIZONTAL RIGHT ­RIGHT VENT CONFIGURATION
Attach vent pipe adapter with gasket to furnace casing.
1
Align notches in rubber coupling over standoffs on adapter. Slide clamps over the coupling.
2
Slide vent pipe through adapter and coupling into vent elbow.
3
4
Insert vent pipe into vent elbow.
Torque all clamps 15 lb.-in.
5
Attach combustion air pipe adapter with gasket to furnace.
6
Attach combustion air pipe to adapter with silicone. Pilot drill a 1/8-in.
7
hole in adapter and secure with a #7 x 1/2-in sheet metal screw.
A11341
Fig. 41 -- Horizontal Right
(Appearance May Vary)
56
Page 57
VENT PIPE ADAPTER WITH GASKET INSTALLED ON FURNACE VENT PIPE IS CUT FLUSH WITH TOP OF ADAPTER.
ALIGN NOTCHES IN VENT PIPE COUPLING OVER STAND-OFF ON ADAPTER. TORQUE LOWER CLAMP 15 LB-IN. WHEN REMAINING VENT PIPE IS INSTALLED, TORQUE UPPER CLAMP TO 15 LB-IN.
59MN7A
VENT PIPE FLUSH WITH ADAPTER
Fig. 42 -- Vent Pipe Flush with Adaptor
CASING SIDE ATTACHMENT COMBUSTION AIR PIPE (NON-DIRECT VENT)
VENT PIPE FLUSH SHOWING COUPLING
A11339
Point elbow down towards back of furnace
12" (256mm) minimum to
60”(1524 mm) or 1 additional elbow maximum
L12F042
Fig. 43 -- Combustion Air Pipe Attachment
57
Page 58
NOTE: The following is based upon National codes for gas appliances and is provided as a reference.
59MN7A
Refer to local codes which may supersede these standards and/or recommendations.
Item Clearance Description
Clearance above grade, veranda, porch, deck, balcony
A
B Clearance to a window or door that may be opened
C Clearance to a permanently closed window
Vertical clearance to a ventilated soffit located above the terminal within a horizontal distance of 2 feet (61
D
E Clearance to an unventilated soffit F Clearance to an outside corner
G Clearance to an inside corner
Clearance to each side of the centerline extended above
H
electrical meter or gas service regulator assembly
I Clearance to service regulator vent outlet 3ft. (.9 M) SeeNote4.
Clearance to non—mechanical air supply inlet to building
J
or the combustion air inlet to any other appliance
K Clearance to a mechanical air supply inlet 6 ft. (1.8 M) 3ft. (.9 M)
L Clearance under a veranda, porch, deck, or balcony
Clearance to each side of the centerline extended above
or below vent terminal of the furnace to a dryer or water
M
heater vent, or other appliance’s direct vent intake or
N
0 Clearance from a plumbing vent stack 3ft.(.9M) 3 ft. (.9 M)
Clearance above paved sidewalk or paved driveway
P
> greater than, ≥ greater than or equal to, < less than, ≤ less than or equal to
or anticipated snow level
cm) from the centerline of the terminal
exhaust
Inlet air clearance to a moisture exhaust duct
(dryer vent, spa exhaust, etc.)
located on public property
12 in. (305 mm) for appliances >10,000 Btuh (3 kW)
36 in. (914 mm) for appliances >100,000 Btuh (30 kW)
For clearances not specified in ANSI Z223.1/NFPA 54 or CAN/CSA B149.1, clearances shall be in accordance with local
12 in. (305 mm) for appliances >10,000 Btuh(3 kW)
36 in. (914 mm) for appliances >100,000 Btuh (30 kW)
Permitted only if veranda, porch, deck, or balcony is fully open on a
Vent shall not terminate above a sidewalk or paved driveway that is
located between two single family dwellings and serves both
Canadian Installations
(per CAN/CSA B149.1)
12 in. (305 mm)
18 in. (457 mm) above roof surface.
and </=100,000 Btuh ( 30 kW),
installation codes and the requirements of the gas supplier and the manufacturer’s installation instructions.
3 ft. (.9 M) within 15 ft. (4.6 M)
above the meter/regulator assembly.
and </= 100,000 Btuh ( 30 kW),
12 in. (305 mm).
minimum of two sides beneath the floor.
12 in. (305 mm) 12 in. (305 mm)
3ft.(.9M) 3 ft. (.9 M)
7 ft. (2.1 M)
dwellings.
(1 )
Manufacturer’s Recommendation: See Notes 3-8.
Notes:
1 In accordance with the current CAN/CSA B149.1, Natural Gas and Propane Installation Code. 2 In accordance with the current ANSI Z223.1/NFPA 54, National Fuel Gas Code 3 NOTE: This table is based upon National codes for gas appliances, and are provided as a reference.
Refer to Local codes which may supersede these standards and/or recommendations.
4 For clearances not specified in ANSI Z223.1/NFPA 54 or CAN/CSA B 149.1, clearances shall be in accordance with local installation codes and the requirements
of the gas supplier and the manufacturer’s installation instructions.
5 When locating vent terminations, consideration must be given to prevailing winds, location, and other conditions which may cause recirculation of the combustion
products of adjacent vents. Recirculation can cause poor combustion, inlet condensate problems, and accelerated corrosion of the heat exchangers. 6 Design and position vent outlets to avoid ice build-up on and moisture damage to surrounding surfaces. 7 The vent for this appliance shall not terminate:
a. Near soffit vents of crawl space vents or other areas where condensate or vapor could create a nuisance or hazard or property damage; or b. Where condensate vapor could cause damage or could be detrimental to the operation of regulators, relief valves, or other equipment.
8 Avoid venting under a deck or large overhang. Recirculation could occur and cause performance or system problems. Ice build-up may occur.
Fig. 44 -- Direct Vent Termination Clearance
58
V
V
A12326
U.S. Installations
(per ANSI Z223.1/NFPA 54)
12 in. (305 mm)
9 in. (229 mm) for appliances >10,000 Btuh (3 kW)
and </= 50,000 Btuh ( 15 kW),
12 in. (305 mm) for appliances >50,000 Btuh (15kW)
3ft.(.9M)within15ft.(4.6M)
above the meter/regulator assembly.
9 in. (9 mm) for appliances >10,000 Btuh (3 kW)
and </= 50,000 Btuh (15 kW),
12 in.(305 mm) for appliances >50,000 Btuh (15kW)
SeeNote4.
Manufacturer’s Recommendation: See Notes 3-8.
SeeNote4.
Manufacturer’s Recommendation: See Notes 3-8.
(2 )
Page 59
V
V
NOTE: The following is based upon National codes for gas appliances and is provided as a reference. Refer to local codes which may supersede these standards and/or recommendations.
Item Clearance Description
Clearance above grade, veranda, porch, deck, balcony or
A
B Clearance to a window or door that may be opened
C Clearance to a permanently closed window
Vertical clearance to a ventilated soffit located above the
terminal within a horizontal distance of 2 feet (61 cm) from
D
E Clearance to an unventilated soffit F Clearance to an outside corner
G Clearance to an inside corner
Clearance to each side of the centerline extended above
H
I Clearance to service regulator vent outlet 3ft. (.9 M) SeeNote4.
J
K Clearance to a mechanical air supply inlet 6 ft. (1.8 M) 3ft. (.9 M)
L Clearance under a veranda, porch, deck, or balcony
M
N
0 Clearance from a plumbing vent stack 3 ft. (.9 M) 3 ft. (.9 M)
P
> greater than, ≥ greater than or equal to, < less than, ≤ less than or equal to
electrical meter or gas service regulator assembly
Clearance to non—mechanical air supply inlet to building or
the combustion air inlet to any other appliance
Clearance to each side of the centerline extended above or
below vent terminal of the furnace to a dryer or water heater
vent, or other appliance’s direct vent intake or exhaust
Inlet air clearance to a moisture exhaust duct
Clearance above paved sidewalk or paved driveway located
anticipated snow level
the centerline of the terminal
(dryer vent, spa exhaust, etc.)
on public property
12 in. (305 mm) for appliances >10,000 Btuh (3 kW)
36 in. (914 mm) for appliances >100,000 Btuh (30 kW)
For clearances not specified in ANSI Z223.1/NFPA 54 or CAN/CSA B149.1, clearances shall be in accordance with local
12 in. (305 mm) for appliances >10,000 Btuh(3 kW)
36 in. (914 mm) for appliances >100,000 Btuh (30 kW)
Permitted only if veranda, porch, deck, or balcony is fully open
Vent shall not terminate above a sidewalk or paved driveway
that is located between two single-family dwellings and serves
Canadian Installations
(per CAN/CSA B149.1)
12 in. (305 mm)
18 in. (457 mm) above roof surface.
and </=100,000 Btuh ( 30 kW),
installation codes and the requirements of the gas supplier and the manufacturer’s installation instructions.
3 ft. (.9 M) within 15 ft. (4.6 M)
above the meter/regulator assembly.
and </= 100,000 Btuh ( 30 kW),
12 in. (305 mm).
on a minimum of two sides beneath the floor.
12 in. (305 mm) 12 in. (305 mm)
3 ft. (.9 M) 3 ft. (.9 M)
7 ft. (2.1 M).
both dwellings.
Notes:
1 In accordance with the current CAN/CSA B149.1, Natural Gas and Propane Installation Code. 2 In accordance with the current ANSI Z223.1/NFPA 54, National Fuel Gas Code 3 NOTE: This table is based upon National codes for gas appliances, and are provided as a reference.
Refer to Local codes which may supersede these standards and/or recommendations.
4 For clearances not specified in ANSI Z223.1/NFPA 54 or CAN/CSA B 149.1, clearances shall be in accordance with local installation codes and the requirements
of the gas supplier and the manufacturer’s installation instructions. 5 When locating vent terminations, consideration must be given to prevailing winds, location, and other conditions which may cause recirculation of the combustion
products of adjacent vents. Recirculation can cause poor combustion, inlet condensation problems, and/or accelerated corrosion of the heat exchangers. 6 Design and position vent outlets to avoid ice build-up on and moisture damage to surrounding surfaces. 7 The vent for this appliance shall not terminate:
a. Near soffit vents of crawl space vents or other areas where condensate or vapor could create a nuisance or hazard or property damage; or b. Where condensate vapor could cause damage or could be detrimental to the operation of regulators, relief valves, or other equipment.
8 These National standards apply to all non-direct-vent gas appliances. Contact Local code officials for additional requirements and/or exclusions.
(1 )
Manufacturer’s Recommendation: See Notes 3-8.
(per ANSI Z223.1/NFPA 54)
4ft. (1.2M) below or to the side of the opening,
1 ft (.3M) above the opening.
Manufacturer’s Recommendation: See Note 8.
3 ft. (.9 M) within 15 ft. (4.6 M)
above the meter/regulator assembly.
4ft. (1.2M) below or to the side of the opening,
1 ft (.3M) above the opening.
Manufacturer’s Recommendation: See Note 8
Manufacturer’s Recommendation: See Notes 3-8.
U.S. Installations
12 in. (305 mm)
SeeNote4.
7ft. (2.1M)
Fig. 45 -- Ventilated Combustion Air and Non--Direct Vent Termination Clearance
A12325
(2 )
59MN7A
59
Page 60
Roof Termination (Preferred)
Note:
36ïin. separation between pairs of inlets only required
Vertical separation between combustion air and vent
At least 36 in.
(914mm)
8 ¾ in. (222mm) or 3 in.(76mm)
6
¾ in. (172mm) or 2in. (51mm)
Maintain 12 in. (305mm) min. Clearance above highest anticipated snow level maximum of 24 in. (614mm) above roof
59MN7A
18 in. Maximum
(457mm)
0
90
At least 36 in. (914mm)
Abandoned masonry used as raceway (per code)
Concentric Vent and Combustion Air Side Termination
12 in. Min from overhang or roof (Typ.)
A
Note:
“A” denotes 0 To 2 in. (51mm)
A
Between the first 2 vents Third vent (and fourth vent, if used) must be 36 in. Away (914mm)
At least 36 in.
12 in. (305mm) separation between bottom of comï bustion air and bottom of vent (Typ.)
Maintain 12 in. (305mm) min. Clearance above highest anï ticipated snow level or grade whichever is greater (Typ.)
(914mm)
A
At least 36 in.
(914mm)
Concentric Vent and Combustion Air
Roof Termination (preferred)
A
Note:
“A” denotes 0 To 2 in. (51mm) Between the first 2 vents Third vent (and fourth vent, if used) must be 36 in. Away (914mm)
for directïvent systems
Maintain 12 in. (305mm) min. Clearance above highest anticipated snow level maximum of 24 in. (614mm) above roof
1 in. (25mm) maximum (Typ.) from wall to inlet
12 in. From Overhang or roof (Typ.)
A
Maintain 12 in. (305mm) min. Clearï At least 36 in. (914mm)
Side wall termination of less than 12 in. (305mm) above highest snow level
ance above highest anticipated snow
level or grade whichever is greater
(Typ.)
L12F032
Fig. 46 -- Combustion Air and Vent Pipe Termination for Direct Vent (2--Pipe) System
Roof Termination (Preferred)
Ven t
(305mm)
Maintain 12 in .
minimum clearance
above highest anticipated
snow level maximum of
24 in. (610mm) above roof.
Abandoned masonry used as raceway (per code)
12 in. min. (305 mm)from
overhang or roof
Sidewall Termination
with Straight Pipe (preferred)
Maintain 12 in. (305mm) minimum clearance above highest anticipated snow level or grade whichever is greater
90°
Side wall termination with 2 elbows (preferred)
12 in. (305 mm) min. from
overhang or roof
Maintain 12 in. (305mm) minimum clearance above highest anticipated snow level or grade whichever is greater.
6 in. (152mm) minimum clearance
between wall and end of vent pipe.
10 in. (254mm) maximum pipe length
Fig. 47 -- Vent Pipe Termination for Non--Direct Vent and Ventilated Combustion Air System
A05091
60
Page 61
OPTIONAL TERMINATION BRACKET FOR 2-PIPE TERMINATIONS
12-IN.
(305 MM)
12-IN. (305 MM)
ABOVE ANTICIPATED
SNOW LEVEL
OPTIONAL BRACKET COUPLING
(ELBOW PARALLEL TO WALL)
COMBUSTION-AIR
12 IN. (305 MM) SEPARATION BETWEEN BOTTOM OF COMBUSTION AIR AND BOTTOM OF VENT.
MAINTAIN 12 IN. (305 MM) CLEARANCE ABOVE HIGHEST ANTICIPATED SNOW LEVEL OR GRADE, WHICHEVER IS GREATER.
59MN7A
EXHAUST
OVERHANG
CLEARANCE TO OVERHANG PER CODE
12 IN.
(305 MM) MIN. GROUND
LEVEL OR SNOW LEVEL
Fig. 48 -- Alberta and Saskatchewan Vent Termination
A12221
61
Page 62
Ventilated Combustion Air intake pipe
Pipe hangar
3” (76 mm)
Ventilated Combustion Air
59MN7A
intake termination in crawl space
12” (305 mm)
CRAWL SPACE
highest level of insulation
Fig. 49 -- Vent Terminations for Ventilated Combustion Air
ATTIC
A10497
62
Page 63
EXAMPLE FOR
1
UPFLOW INSTALLATIONS. MAY BE APPLIED TO OTHER CONFIGURATIONS.
Fig. 50 -- Sample Inlet Air Pipe Connection for
Polypropylene Venting Systems
A12220
59MN7A
Fig. 51 -- Optional Combustion Air Inlet Moisture Trap
TO CODEïAPPROVED DRAIN OR CONDENSATE PUMP
Representative drawing only, some models may vary in appearance
63
L
L12F028
Page 64
START--UP, ADJUSTMENT, AND SAFETY
CHECK
General
1. Furnace must have a 115-v power supply properly connec­ted and grounded.
NOTE: Proper polarity must be maintained for 115-v wiring. Control status indicator light flashes rapidly and furnace does not operate if polarity is incorrect or if furnace is not grounded.
2. Thermostat wire connections at terminals R, W/W1, G, and Y/Y2 must be made at 24-v terminal block on furnace con­trol. See communicating wall control instructions for proper wiring of communicating controls.
3. Natural gas service pressure must not exceed 0.5 psig (14­in. w.c., 350 Pa), but must be no less than 0.16 psig (4.5-in. w.c., 1125 Pa).
4. Blower door must be in place to complete 115-v electrical circuit and supply power to the furnace components.
!
CAUTION
59MN7A
UNIT OPERATION HAZARD
Failure to follow this caution may result in intermittent unit operation or performance dissatisfaction.
These furnaces are equipped with a manual reset limit switch in burner assembly. This switch opens and shuts off power to the gas valve if an overheat condition (flame rollout) occurs in the burner assembly/enclosure. Correct inadequate combustion--air supply, improper gas pressure setting, improper burner or gas orifice positioning, or improper venting condition before resetting switch. DO NOT jumper this switch.
Before operating furnace, check flame rollout manual reset switch for continuity. If necessary, press button to reset switch.
EAC-1 terminal is energized whenever blower operates, HUM terminal is only energized when blower is energized in heating.
Setup Switches
There are 4 sets of setup switches on the furnace control board. These switches configure the furnace for correct application requirement. They also select the airflow settings for Air Conditioning and Continuous Fan airflows.
The Setup Switch locations are shown and described on Fig. 56. The setup switches are also shown on the unit wiring label.
Setup Switches (SW1)
The furnace control has 8 setup switches that may be set to meet the application requirements. Refer to Fig. 56 and the Adjustments section for setup switch configurations. To set these setup switches for the appropriate requirement:
1. Remove blower door.
2. Locate setup switches on furnace control.
3. Configure the set-up switches as necessary for the application.
4. Replace blower door.
NOTE: If a bypass humidifier is used, setup switch SW1-3 (Min/Int Heat Rise Adjust) should be in ON position. This compensates for the increased temperature in return air resulting from bypass.
NOTE: If modulating dampers are used, blower motor automatically compensates for modulating dampers.
Air Conditioning (A/C) Setup Switches (SW2)
The air conditioning setup switches are used to match furnace airflow to required cooling airflow or high stage cooling airflow when a two--stage outdoor unit is used. Refer to Fig. 56 and the Adjustments section for setup switch configurations.
To set the desired cooling airflow:
1. Remove blower door.
2. Locate A/C setup switches on furnace control.
3. Determine air conditioning tonnage used.
4. Configure the switches for the required cooling airflow.
NOTE: Incorrect airflow caused by improper A/C switch setup may cause condensate blow-off or a frozen indoor coil in the cooling mode.
5. Replace blower door.
Continuous Fan (CF) Setup Switches (SW3)
The CF setup switches are used to select desired airflow when thermostat is in continuous fan mode or to select low-cooling airflow for two-speed cooling units. Refer to Fig. 56 and the Adjustments section for setup switch configurations. This setup feature allows continuous fan airflow or low-cooling airflow to be adjusted. To set desired continuous fan airflow or low-cooling airflow:
1. Remove blower door.
2. Locate CF setup switches on furnace control.
3. Determine desired continuous fan airflow or low-cooling airflow.
4. Configure the switches for the required continuous fan or low--cooling airflow.
5. Replace blower door.
Additional Setup Switches (SW4)
The furnace control has 3 additional setup switches labeled SW4. Setup switch SW4-2 can be used to lock the furnace into intermediate heat. When setup switch SW4-2 is ON it will over ride setup switch SW1-2 if it is ON. SW4--3 is used to adjust airflow. Refer to Fig. 56 and the Adjustments section for setup switch configurations. To activate setup switch SW4-2 and SW4--3:
1. Remove blower door.
2. Locate setup switch SW4 on furnace control.
3. Configure the switches for the required heat stages and airflow if necessary.
4. Replace blower door.
Prime Condensate Trap with Water
!
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow these warnings could result in personal injury or death.
Failure to use a properly configured trap or NOT water--priming trap before operating furnace may allow positive pressure vent gases to enter the structure through drain tube. Vent gases contain carbon monoxide which is tasteless and odorless.
64
Page 65
!
CAUTION
!
WARNING
UNIT OPERATION HAZARD
Failure to follow this caution may result in intermittent unit operation or performance satisfaction.
Condensate trap must be PRIMED or proper draining may not occur. The condensate trap has two internal chambers which can ONLY be primed by pouring water into the inducer drain side of condensate trap.
1. Remove upper and middle collector box drain plugs oppos­ite of the condensate trap. See Fig. 59.
2. Connect field-supplied 5/8-in. (16 mm) ID tube with at­tached funnel to upper collector box drain connection. See Fig. 59.
3. Pour one quart (liter) of water into funnel/tube. Water should run through collector box, overfill condensate trap, and flow into open field drain.
4. Remove funnel; replace collector box drain plug.
5. Connect field-supplied 5/8-in. (16 mm) ID tube to middle collector box drain port.
6. Pour one quart (liter) of water into funnel/tube. Water should run through collector box, overfill condensate trap, and flow into open field drain.
7. Remove funnel and tube from collector box and replace col­lector box drain plug.
Purge Gas Lines
If not previously done, purge the lines after all connections have been made and check for leaks.
!
WARNING
FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in personal injury, death, and/orproperty damage.
Never purge a gas line into a combustion chamber. Never test for gas leaks with an open flame. Use a commercially available soap solution made specifically for the detection of leaks to check all connections. A fire or explosion may result causing property damage, personal injury or loss of life.
Adjustments
FIRE HAZARD
Failure to follow this warning could result in personal injury, death and/or property damage.
DO NOT push or force gas valve adjusting screw. This can result in damage to the adjustment screw resulting in incorrect manifold pressure, which can result in a no heat situation or shorten the life of the heat exchangers.
!
CAUTION
FURNACE DAMAGE HAZARD
Failure to follow this caution may result in reduced furnace life.
DO NOT redrill orifices. Improper drilling (burrs, out--of--round holes, etc.) can cause excessive burner noise and misdirection of burner flames. This can result in flame impingement of heat exchangers, causing failures. See Fig.
53.
For proper operation and long term reliability, the Furnace input rate must be within +/--2 percent of input rate on furnace rating plate or as adjusted for altitude.
The gas input rate on rating plate is for installations at altitudes up to 2000 ft. (609.6M).
NOTICE
The NATURAL GAS manifold pressure adjustments in Tables 21 and 22 compensate for BOTH altitude AND gas heating value. DO NOT apply an additional derate factor to the pressures show in Table 21 or 22. The values in this table are NOT referenced to sea level; they are AS--MEASURED AT ALTITUDE.
The heating content of natural gas at altitude may already provide for a reduction in capacity of the furnace. Be sure to obtain the expected in--season gas heating value of the gas from the gas supplier BEFORE making any adjustments for capacity or altitude. Refer to Table 21 or 22. No adjustments to the furnace may be necessary at altitude for certain gas heating values.
Refer to the instructions provided in the factory--specified LP/Propane conversion kit for instructions for setting gas manifold pressures for LP/Propane applications.
59MN7A
!
CAUTION
FURNACE DAMAGE HAZARD
Failure to follow this caution could result in reduced furnace life. DO NOT push or force gas valve adjusting screw. This can result in damage to the adjustment screw resulting in incorrect manifold pressure, which can result in a no heat situation or shorten the life of the heat exchangers.
In the USA, the input rating for altitudes above 2000 ft. (609.6M) must be reduced by 2 percent for each 1000 ft. (304.8M) above sea level. Refer to Table 18.
In Canada, the input rating must be reduced by 5 percent for altitudes of 2000 ft. (609.6M) to 4500 ft. (1371.6M) above sea level. The natural gas manifold pressures in Tables 21 and 22 adjust for BOTH altitude and natural gas heating value.
NOTE: For Canadian altitudes of 2000 to 4500 ft. (610 to 1372 M), use USA altitudes of 2001 to 2000 ft. (611 to 914 M) in Table
21. To adjust manifold pressure to obtain the proper input rate, first,
determine if the furnace has the correct orifice installed. At higher altitudes or different gas heat contents, it may be necessary to change the factory orifice to a different orifice. Tables have been
65
Page 66
provided in the furnace installation instructions to match the required orifice to the manifold pressure to the heat content and specific gravity of the gas.
NOTICE
THERE ARE TWO MANIFOLD PRESSURE TABLES
Use Table 21 for all models EXCEPT 59MN7A060V21--20. Use Table 22 for Model 59MN7A060V21--20 ONLY.
To do this:
1. Obtain average yearly gas heat value (at installed altitude) from local gas supplier.
2. Obtain average yearly specific gravity from local gas supplier.
3. Find installation altitude range for your installation in the manifold pressure tables. See Table 21 for 20,000 Btuh Max--Heat/8,000 Btuh min--heat per burner or Table 22 for
59MN7A
20,200 Btuh Max--Heat/8,000 Btuh Min--Heat per burner.
4. Find closest natural gas heat value and specific gravity in Table 21 or Table 22 depending on furnace gas input rate.
5. Follow heat value and specific gravity lines to point of intersection to find orifice size and maximum and minimum manifold pressure settings for proper operation.
6. Check and verify burner orifice size in furnace. NEVER ASSUME ORIFICE SIZE. ALWAYS CHECK AND VERIFY.
NOTICE
If orifice hole appears damaged or it is suspected to have been redrilled, check orifice hole with a numbered drill bit of correct size. Never redrill an orifice. A burr--free and squarely aligned orifice hole is essential for proper flame characteristics.
7. Replace original orifice with correct size, if required by Table 21 or Table 22 depending on furnace gas input rate. Use only factory--supplied orifices. See EXAMPLE 1.
EXAMPLE 1 -- 80,000 BTUH INPUT:
EXAMPLE: 0 -- 2000 ft. (0 -- 609.6M) altitude Heating value = 1050 Btu/cu ft. Specific gravity = 0.62 Therefore: Orifice No. 44 * Furnace is shipped with No. 44 orifices. In this example, all main
burner orifices are the correct size and do not need to be changed to obtain proper input rate.
Manifold pressure: 3.4--in. w.c. for maximum heat, 0.55--in. w.c. for minimum heat.
NOTE: To convert gas manifold Table pressures to Pascals, multiply the in. w.c. value by 249.1 Pa/in. w.c. (1 in. w.c. = 249.1 Pa).
Check Inlet Gas Pressure
The inlet gas pressure must be checked with the furnace operating in maximum heat. This is necessary to make sure the inlet gas pressure does not fall below the minimum pressure of 4.5 in. w.c. for natural gas. The maximum inlet gas pressure is 13.6 in. of water column. If the inlet pressure is too low, you will not be able to adjust the manifold pressure to obtain the proper input rate. To check the inlet gas pressure:
1. Make sure the gas supply is turned off to the furnace and at the electric switch on the gas valve.
2. Remove the 1/8 in. NPT plug from the inlet pressure tap on the gas valve.
3. Connect a manometer to the inlet pressure tap on gas valve.
4. Turn on furnace power supply.
5. Turn gas supply manual shutoff valve to ON position.
6. Turn furnace gas valve switch to ON position.
7. Jumper the R to W/W1 and W2 thermostat connections at the furnace control board.
8. When main burners ignite, confirm inlet gas pressure is Between 4.5 in. w.c. and 13.6 in. w.c.
9. Remove jumper across thermostat connections to terminate call for heat. Wait until the blower off delay is completed.
10. Turn furnace gas valve electric switch to OFF position.
11. Turn gas supply manual shutoff valve to OFF position.
12. Turn off furnace power supply.
13. Remove manometer from the inlet pressure tap of the gas valve.
!
WARNING
FIRE HAZARD
Failure to follow this warning could result in personal injury, death, and/orproperty damage.
Reinstall manifold pressure tap plug in gas valve to prevent gas leak.
14. Apply pipe dope sparingly to end of inlet gas pipe plug and re--install in the gas valve.
Adjust Manifold Pressure -- Maximum Heat
For proper operation and long term reliability, the manifold pressure must be adjusted within +/--2 percent of input rate on furnace rating plate.
The modulating furnace manifold pressure is set at two points. The first point is Maximum Heat. The second point is Minimum Heat. Do not adjust Intermediate Heat manifold pressure. Intermediate Heat manifold pressure is checked as part of the temperature rise, but is not adjustable. Always adjust Maximum Heat first, then Minimum Heat.
NOTICE
DO NOT set Maximum Heat manifold pressure less than
3.2--in. w.c. or more than 3.8 in. w.c. for natural gas. If required manifold pressure is outside this range, change main burner orifices to obtain manifold pressure in this range.
To adjust manifold pressure to obtain input rate for Maximum Heat:
1. Make sure the gas supply is turned off to the furnace and at the electric switch on the gas valve.
2. Remove the 1/8 inch NPT plug from the outlet pressure tap on the gas valve.
3. Connect a manometer to the outlet pressure tap on gas valve.
4. Turn on furnace power supply.
5. Turn gas supply manual shutoff valve to ON position.
6. Turn furnace gas valve switch to ON position.
7. Jumper the R to W/W1 and W2 thermostat connections at the furnace control board.
66
Page 67
8. After the main burners ignite and the blower starts, confirm Maximum Heat manifold pressure is correct, based on the manifold pressure tables in the installation instructions.
9. To adjust the Maximum Heat manifold pressure, slowly turn adjusting screw counterclockwise to decrease manifold pressure or clockwise to increase manifold pressure. Turn adjustment no more than one click per second until you obtain the required manifold pressure. See Fig. 52.
10. Main burner flame should be clear blue, almost transparent.
11. After adjusting the Maximum Heat manifold pressure, remove jumpers across thermostat connections to terminate the call for heat.
12. Wait for blower off-delay to finish then reset 115--v power to furnace.
Adjust Manifold Pressure -- Minimum Heat
To adjust manifold pressure to obtain input rate for Minimum Heat:
1.TurnSW1--2ONandSW4--2mustbeOFF.
2. Jumper R and W/W1 thermostat connections on control to start furnace.
3. After the main burners ignite and the blower starts, confirm Minimum Heat manifold pressure is correct, based on the manifold pressure tables in the installation instructions.
4. To adjust the Minimum Heat manifold pressure, slowly turn adjusting screw counterclockwise to decrease manifold pressure or clockwise to increase manifold pressure. Turn adjustment no more than one click per second until you obtain the required manifold pressure. See Fig. 52.
5. After adjusting the manifold pressure, remove jumpers across thermostat connections to terminate the call for heat. Wait until the blower off delay is completed.
6. Move setup switch SW1--2 to the OFF position.
7. Turn gas supply manual shutoff valve to OFF position.
8. Turn off furnace power supply.
!
WARNING
FIRE HAZARD
Failure to follow this warning could result in personal injury, death, and/orproperty damage.
Reinstall manifold pressure tap plug in gas valve to prevent gas leak.
9. Remove manometer from the inlet pressure tap of the gas valve.
10. Apply pipe dope sparingly to end of inlet gas pipe plug and re-install in the gas valve.
11. Re-install cap over adjustment screw on the top of the gas valve.
Clocking The Meter
Verify natural gas input rate by clocking meter. NOTE: Contact your HVAC distributor or gas supplier for metric
gas meter Tables, if required.
1. Turn off all other gas appliances and pilots served by the meter.
2. Move setup switches SW1--2 to ON position and SW4-2 to OFF. This keeps furnace locked in low--heat operation when only W/W1 is energized or high heat operation when R to W/W1 and W2 are jumpered.
3. Jumper R to W/W1 and W2. Run furnace for 3 minutes in maximum heat operation.
4. Measure time (in sec) for gas meter to complete one revolution and note reading. The 2 or 5 cubic feet dial provides a more accurate measurement of gas flow.
5. Refer to Table 20 for cubic ft. of gas per hr. Multiply gas rate cu ft./hr by heating value (Btuh/cu ft.) to obtain input rate.
6. If clocked rate does not match required input from Step 5, increase manifold pressure to increase input or decrease manifold pressure to decrease input. Repeat steps 3 through 5 until correct maximum heat input is achieved. See Fig.
61.
7. Remove jumpers across thermostat connections to terminate the call for heat. Wait until the blower off delay is completed then reset 115--v power to furnace.
8. Jumper R and W/W1 thermostat connections on control to start furnace.
NOTE: Setup switches SW1--2 must be ON and SW4--2 must be OFF. This keeps furnace locked in minimum heat operation when R to W/W1 is energized. Repeat items 3 through 6 for minimum heat operation until minimum heat input is achieved
9. Restore furnace to normal operating condition.
10. Remove jumpers across thermostat connections to termi-­nate the call for heat. Wait until the blower off delay is completed.
11. Disconnect 115 VAC power to furnace.
12. Turn gas valve ON/OFF switch to OFF.
13. Remove water column manometer or similar device from manifold pressure tap (if still connected).
!
WARNING
FIRE HAZARD
Failure to follow this warning could result in personal injury, death, and/orproperty damage.
Reinstall manifold pressure tap plug in gas valve to prevent gas leak.
14. Replace manifold pressure tap plug to gas valve.
15. Turn gas valve ON/OFF switch to ON.
16. Move setup SW1--2 on furnace control to position required for attached thermostat (OFF for single-stage thermostats, ON for two-stage thermostats).
17. Check for gas leaks and verify furnace operation.
Adjust Temperature Rise
NOTE: Blower door must be installed when taking temperature
rise reading. Leaving blower door off will result in incorrect temperature measurements, due to possible changes in duct static pressure and airflow.
!
CAUTION
FURNACE DAMAGE HAZARD
Failure to follow this caution may result in: S Overheating the heat exchangers or condensing flue gases in heat exchanger areas not designed for condensate.
S Shortened furnace life S Component damage.
Temperature rise must be within limits specified on furnace rating plate. Recommended operation is at midpoint of rise range or slightly above.
59MN7A
67
Page 68
When setup switch SW1--4 is ON, operation will be near the high end of the rise range for improved comfort.
Furnace must operate within ranges of temperature rise specified on the furnace rating plate. Determine air temperature rise as follows:
1. Place thermometers in return and supply ducts as near furnace as possible. Be sure thermometers do not see heat exchanger so that radiant heat does not affect readings. This practice is particularly important with straight-run ducts.
2. When thermometer readings stabilize, subtract return-air temperature from supply-air temperature to determine air temperature rise.
NOTE: Temperature rise can be determined for Minimum Heat, Intermediate Heat and Maximum Heat operation by locking the furnace in each mode of operation. The mode of operation is based on the position of Set-up switch SW1--2 and SW4--2 on the furnace control board.
The furnace is capable of automatically providing proper airflow to maintain the temperature rise within the range specified on furnace rating plate. If temperature rise is outside this range, proceed as follows:
59MN7A
a. Check gas input for minimum, intermediate and maximum
heat operation.
b. Check derate for altitude if applicable.
c. Check all return and supply ducts for excessive restrictions
causing static pressure greater than 0.5--in. w.c.
d. Ensure Min/Int Heat Rise Adjust switch SW1--3 on furnace
control is in ON position when a bypass humidifier is used. See Fig. 56 for switch location.
e. Check Troubleshooting Guide for Variable--Speed Step
Modulating Condensing Furnaces.
f. Verify correct model plug is installed.
To lock the furnace in Minimum Heat:
1. Turn SW1--2 ON at the furnace control. Setup switch SW4--2 must be OFF.
2. Connect a jumper across R and W/W1 at the thermostat terminals at the furnace control.
3. Allow the burners to ignite and the blower to turn on.
4. Allow the supply temperature to stabilize and verify the proper rise range.
If the temperature rise is too high or too low in Minimum Heat:
1. Remove jumpers from R and W/W1.
2. Wait until the blower off delay is completed.
3. Turn 115 VAC power off.
4. Check the position of setup switch SW1--3. When set to ON, airflow is raised 18% for Minimum Heat and for Intermediate Heat. Factory default position is OFF.
5. Turn 115 VAC power on.
6. Re--check Minimum Heat Temperature Rise
To lock the furnace in Intermediate Heat:
1. Turn SW1--2 OFF and SW4--2 ON at the furnace control.
2. Connect a jumper across R and W/W1 at the thermostat terminals at the furnace control.
3. Allow the burners to ignite and the blower to turn on.
4. Allow the supply temperature to stabilize and verify the proper rise range.
If the temperature rise is too high or too low in Intermediate Heat:
1. Remove jumpers from R and W/W1.
2. Wait until the blower off delay is completed.
3. Turn 115 VAC power off.
4. Check the position of setup switch SW1--3. When set to ON, airflow is raised 18% for Minimum Heat and for Intermediate Heat. Factory default position is OFF.
5. Turn 115 VAC power on.
6. Re--check Minimum Heat Temperature Rise.
To lock the furnace in Maximum Heat:
1. Connect a jumper across R and W/W1 and W2 at the thermostat terminals at the furnace control.
2. Allow the burners to ignite and the blower to turn on.
3. Allow the supply temperature to stabilize and verify the proper rise range.
If the temperature rise is too high or too low in Maximum Heat:
1. Remove jumpers from R and W/W1 and W2.
2. Wait until the blower off delay is completed.
3. Turn 115 VAC power off.
4. Check the position of setup switch SW1--4. When set to OFF and SW1--3 is set to OFF, airflow is raised 10% for Minimum Heat, 7.5% for Intermediate Heat and 17.5% for Maximum Heat. Factory default position is ON. If SW1--3 is ON and SW1--4 is OFF, airflow is raised 18% for Minim­um and Intermediate heat and 10% for Maximum Heat.
5. Turn 115 VAC power on.
6. Re--check Maximum Heat Temperature Rise.
After the temperature rise has been verified:
1. Remove jumpers from thermostat terminals.
2. Allow the blower off delay to complete.
3. Turn set--up switches SW1--2 and SW4--2 to the OFF position unless two--stage thermostat operation is desired. See Fig. 56.
4. Proceed to “Adjust Blower Off Delay” or install blower door if complete.
!
WARNING
FIRE HAZARD
Failure to follow this warning could result in personal injury, death, and/orproperty damage.
Reinstall manifold pressure tap plug in gas valve to prevent gas leak.
!
CAUTION
FURNACE OVERHEATING HAZARD
Failure to follow this caution may result in reduced furnace life.
Recheck temperature rise. It must be within limits specified on the rating plate. Recommended operation is at the mid--point of rise range or slightly above.
Adjust Blower Off Delay (Heat Mode)
a. Remove blower door if installed.
b.TurnDipswitchSW--7orSW--8ONorOFFfordesired
blower off delay. See Table 19 and Fig. 34, 56 and 65.)
Adjust Cooling Airflow – High-Speed and Low-Speed
The ECM blower can be adjusted for a range of airflows for low-speed or high-speed cooling. See Table 9 – Air Delivery – CFM (With Filter ) and Fig. 56 – Furnace Setup Switches and
Cooling
68
Page 69
Descriptions. Depending on the model size, the cooling airflow can be adjusted from 1.5 to 6 tons based on 350 CFM ton.
NOTE: 6 ton airflow will truncate at 2200 CFM on applicable models.
Air Conditioning Setup Switch SW2
The high-speed or single-speed cooling airflow is adjusted by turning Setup switches SW2-1, SW2-2 and SW2-3 either ON or OFF. Select the required airflow from Table 9. Table is based upon 350 CFM per ton. For other CFM per ton Setup switch selections, see Fig. 34, Fig. 56 and Fig. 65.
Continuous Fan (CF) Setup Switch SW3
The Continuous Fan airflow selection via Setup switches SW3 is also the airflow for low-speed cooling when the furnace is used with a 2-speed cooling or heat pump unit. Adjust the Continuous Fan CFM Setup switches SW3 to match the airflow required for low-speed cooling. Select the required airflow from Table 9 and Fig. 56.
NOTE: The airflow selected via SW3 (Low-Speed Cooling Airflow) cannot exceed the airflow selected via SW2 (High-Speed Cooling Airflow). For other CFM per ton Setup switch selections, see Fig. 34 and Fig. 56.
NOTE: The airflow settings for SW2 and SW3 selections are the same, EXCEPT for the default values. See Table 9.
For a complete explanation of cooling airflow, refer to the section titled “Sequence of Operation.”
Adjust Continuous Fan Airflow (and Low-Speed Cooling
NOTE: When the furnace is used with a 2-speed cooling or heat
pump unit, the airflow selected for continuous fan via Setup switch SW3 will also be the airflow used for low-speed cooling, and vice versa. The continuous fan speed can be further adjusted at a conventional thermostat using the continuous fan speed select function. Changing the continuous fan speed at a conventional thermostat DOES NOT change the low-speed cooling airflow selected via SW3 at the control board.
NOTE: When the furnace is used with a 2-speed cooling or heat pump unit, adjust the Continuous Fan CFM Setup switches SW3 to match the airflow required for low-speed cooling.
Select the required continuous fan airflow using Setup switches SW3asshowninFig.56andTable9.
Airflow)
Adjust Thermostat Heat Anticipator.
1. Mechanical thermostat. Set thermostat heat anticipator to match the amp. draw of the electrical components in the R--W/W1 circuit. Accurate amp. draw readings can be obtained at the wires normally connected to thermostat subbase terminals, R and W. The thermostat anticipator should NOT be in the circuit while measuring current.
a. Set SW1--2 switch on furnace control board to ON.
b. Remove thermostat from subbase or from wall.
c. Connect an amp. meter as shown in Fig. 54 across the R
and W subbase terminals or R and W wires at wall.
d. Record amp. draw across terminals when furnace is in
minimum heat and after blower starts.
e. Set heat anticipator on thermostat per thermostat
instructions and install on subbase or wall.
f. Turn SW1--2 switch OFF. g. Install blower door. h. Electronic thermostat: Set cycle rate for 3 cycles per hr.
Check Safety Controls
The flame sensor, gas valve, and pressure switch were all checked in the Start--up procedure section as part of normal operation.
1. Check Main Limit Switch This control shuts off combustion system and energizes air-­circulating blower motor, if furnace overheats. By using this method to check limit control, it can be established that lim­it is functioning properly and will operate if there is a re­stricted return--air supply or motor failure. If limit control does not function during this test, cause must be determined and corrected.
a. Run furnace for at least 5 minutes.
b. Gradually blockoff return air with a pieceof cardboard or
sheet metal until the limit trips.
c. Unblock return air to permit normal circulation.
d. Burners will re--light when furnace cools down.
2. Check Pressure Switch(es) This control proves operation of the draft inducer blower.
a. Turn off 115--v power to furnace.
b. Disconnect inducer motor lead wires from wire harness.
c. Turn on 115--v power to furnace.
d. Set thermostat to “call for heat” and wait 1 minute. When
pressure switch is functioning properly, hot surfaceigniter should NOT glow and control diagnostic light flashes a status code 32. If hot surface igniter glows when inducer motor is disconnected, shut down furnace immediately.
e. Determine reason pressure switch did not function prop-
erly and correct condition.
f. Turn off 115--v power to furnace.
g. Reconnect inducer motor wires, replace blower door, and
turn on 115--v power.
h. Blower will run for 90 seconds before beginning the call
for heat again.
i. Furnace should ignite normally.
Checklist
1. Put away tools and instruments. Clean up debris.
2. Verify that switches SW1--1 and SW1--6 are OFF and other setup switches are set as desired. Verify that switches SW1--7 and SW1--8 for the blower OFF DELAY are set as desired per Table 19.
3. Verify that blower and control doors are properly installed.
4. Cycle test furnace with room thermostat.
5. Check operation of accessories per manufacturer’s instruc­tions.
6. Review Owner’s Manual with owner.
7. Attach literature packet to furnace.
59MN7A
69
Page 70
MODULATING
Turn screw 1 click per second to adjust rate. Clockwise to increase rate, counter clockwise to decrease rate.
Min/Max Heat Adust (Under Cap)
BURNER
Inlet Pressure Tap
ON/OFF Switch
GAS FLOW
ORIFICE
1/2” NPT Outlet
Manifold Pressure Tap
59MN7A
Fig. 52 -- Gas Valve
A10496
Fig. 53 -- Orifice Hole
A93059
THERMOSTAT SUBBASE TERMINALS WITH THERMOSTAT REMOVED (ANITICIPATOR, CLOCK, ETC., MUST BE OUT OF CIRCUIT.)
HOOK-AROUND AMMETER
R Y W G
10 TURNS
FROM UNIT 24-V CONTROL TERMINALS
EXAMPLE:
5.0 AMPS ON AMMETER 10 TURNS AROUND JAWS
0.5 AMPS FOR THERMOSTAT
=
ANTICIPATOR SETTING
Fig. 54 -- Amp. Draw Check with Ammeter
A96316
70
Page 71
59MN7A
338307-201 Rev. F
A11594
Fig. 55 -- Service Label Information
71
Page 72
59MN7A
A11623
Fig. 56 -- Furnace Setup Switches and Description
72
Page 73
Furnace Setup Switch Description
T
Bl
Off Del
Allows additional CFM per ton selections when used with SW
p
p
SW1-1 Status Code Recovery OFF
Minimum Heat Only
SW1-2
SW1-3
SW1-4
SW1-5 CFM per ton adjust OFF
SW1-6 Component Self Test OFF
SW1-7 & SW1-8 Blower OFF delay ON or OFF
SW4-2
(Adaptive Heat Mode
when SW1-2 and SW4-2
are OFF)
Min/Int Heat Rise
Adjustment
Comfort/Efficiency
Adjustment
Intermendiate Heat
Only
(Adaptive Heat Mode
when both SW1-2 and
SW4-2 are OFF)
OFF
OFF
ON
OFF
ESU FO NOITPIRCSEDNOITISOP LAMRONEMAN HCTIWSHCTIWS PUTES
Turn ON to retrieve up to 7 stored status codes for troubleshooting assistance when R thermostat lead is disconnected. When SW1-2 and SW4-2 are OFF allows Modulating operation with a single stage thermostat. Turn ON SW1-2 when using two-stage thermostat to allow Minimum Heat operation when R to W/W1 closed and a Maximum heat operation when R to W/W1 and R to W2 close.
urn ON to increase Minimum Heat and Intermediate Heat airflow by 18 percent. This compensates for increased return air temperature caused with bypass humidifier. This also increases the Intermediate Heat inducer speed 15 percent. Turn ON to decrease Minimum heat airflow by 10 percent, Intermediate Heat airflow 7.5 percent and Maximum Heat airflow 17.5 percent for maximum comfort. Turn ON for 400 CFM per ton, Turn OFF for 350 CFM per ton. See also SW4.
Turn ON to initiate Component Self Test for troubleshooting assistance when R thermostat lead is disconnected. Turn OFF when Self Test is completed.
ower seconds. See table in Adjustments section or refer to unit wiring diagram.
When SW1-2 and SW4-2 are OFF allows Modulating operation with a single stage thermostat. Turn ON SW4-2 when using two-stage thermostat to allow Intermediate Heat operation when R to W/W1 closed and a Maximum heat operation when R to W/W1 and R to W2 close.
ay time – adjustable 90 seconds to 180
59MN7A
1
SW2
1
SW3
1-5
325 CFM per ton (nominal) when SW 4-3 ON and SW 1-5 OFF
350 CFM per ton (nominal) when SW 4-3 OFF and SW 1-5 OFF
SW4-3
O
N
1 2 3
AC
O
N
1 2 3
CF
SW 2, AC (Cooling Airflow) SETUP SWITCHES
The AC setup switch selects desired cooling or high stage cooling (two stage units) airflow.
See Air Delivery Tables for specific switch settings
SW 3, CF (Continuous Fan) SETUP SWITCHES
The CF setup switch selects desired Continuous Fan Airflow
The CF switch position is the low cooling airflow selection for two stage cooling units.
The CFM values in the Air Delivery Tables for SW 3 settings are the same as SW 2 settings.
SW 3 cannot be set for airflow higher than SW 2
See Air Delivery Tables for specific switch settings
CFM per ton Adjust
AIR CONDITIONING (A/C) SETUP SWITCHES
CONTINUOUS FAN (CF) SETUP SWITCHES
OFF
370 CFM per ton (nominal) when SW4-3 ON and SW 1-5 ON
400 CFM per ton (nominal) when SW 1-5 ON and SW 4-3 OFF
See Air Delivery Tables for model specific CFM vs. static
ressure
A11575 AMV
Fig. 56 -- Furnace Setup Switches and Description (Continued)
73
Page 74
Table 18 – Altitude Derate Multiplier for U.S.A.*
ALTITUDE
FT. M
0–2000 0 --- 6 1 0 0 1.00 2001–3000 610---914 4 --- 6 0.95 3001–4000 914--- 1219 6 --- 8 0.93 4001–5000 1219---1524 8 --- 1 0 0.91 5001–6000 1524---1829 10---12 0.89 6001–7000 1829---2134 12---14 0.87 7001–8000 2134 --- 2438 14---16 0.85 8001–9000 2438 --- 2743 16---18 0.83
9001–10,000 2743--- 3048 18---20 0.81
*Derate multiplier factors are based on midpoint altitude for al titude range.
SECONDS
FOR 1 REVOLUTION
10 360 720 1800 50 72 144 360 11 327 655 1636 51 71 141 355
59MN7A
12 300 600 1500 52 69 138 346 13 277 555 1385 53 68 136 340 14 257 514 1286 54 67 133 333 15 240 480 1200 55 65 131 327 16 225 450 1125 56 64 129 321 17 212 424 1059 57 63 126 316 18 200 400 1000 58 62 124 310 19 189 379 947 59 61 122 305 20 180 360 900 60 60 120 300 21 171 343 857 62 58 116 290 22 164 327 818 64 56 112 281 23 157 313 783 66 54 109 273 24 150 300 750 68 53 106 265 25 144 288 720 70 51 103 257 26 138 277 692 72 50 100 250 27 133 267 667 74 48 97 243 28 129 257 643 76 47 95 237 29 124 248 621 78 46 92 231 30 120 240 600 80 45 90 225 31 116 232 581 82 44 88 220 32 113 225 563 84 43 86 214 33 109 218 545 86 42 84 209 34 106 212 529 88 41 82 205 35 103 206 514 90 40 80 200 36 100 200 500 92 39 78 196 37 97 195 486 94 38 76 192 38 95 189 474 96 38 75 188 39 92 185 462 98 37 74 184 40 90 180 450 100 36 72 180 41 88 176 439 102 35 71 178 42 86 172 429 104 35 69 173 43 84 167 419 106 34 68 170 44 82 164 409 108 33 67 167 45 80 160 400 110 33 65 164 46 78 157 391 112 32 64 161 47 76 153 383 116 31 62 155 48 75 150 375 120 30 60 150 49 73 147 367
PERCENT
OF
DERATE
SIZE OF TEST DIAL
1CuFt. 2CuFt. 5CuFt. 1CuFt. 2CuFt. 5CuFt.
DERATE
MULTIPLIER
FACTOR*
DESIRED HEATING MODE
BLOWER OFF DELAY (SEC.)
Table 20 – Gas Rate (CU ft./hr)
FOR 1 REVOLUTION
Table 19 – Blower Off Delay Setup Switch
SETUP SWITCH
( S W 1 --- 7 A N D --- 8 )
POSITION
S W 1 --- 7 S W 1 --- 8
90 OFF OFF 120 ON OFF 150 OFF ON 180 ON ON
SECONDS
SIZE OF TEST DIAL
74
Page 75
Table 21 – Orifice Size and Manifold Pressure (In. W.C.) for Gas Input Rate
To Be Used with Modulating Furnaces Except 59MN7A060V21--20
MODULATING FURNACE
(TABULATED DATA BASED ON 20,000 BTUH M AX-HEAT / 8,000 BTUH MIN-HEAT PER BURNER,
DERATED 2%/1000 FT (305M) ABOVE SEA LEVEL)
ALTITUDE
RANGE
ft (m)
092543 3.6 /0.55 43 3.7 /0.60 43 3.8 /0.60 42 3.2 /0.50
(0) 950 43 3.4 /0.55 43 3.5 /0.55 43 3.6 /0.60 43 3.7 /0.60
to 1000 44 3.5 /0.55 44 3.6 /0.60 44 3.8 /0.60 43 3.4 /0.55
U.S.A. and CanadaU.S.A. and CanadaU.S.A. Only
y
l
U.S.A. On
ly
U.S.A. On
ly
U.S.A. On
2000 1050 44 3.2 /0.50 44 3.3 /0.55 44 3.4 /0.55 44 3.5 /0.55
(610) 1075 45 3.7 /0.60 45 3.8 /0.60 44 3.3 /0.50 44 3.4 /0.55
U.S.A. 800 42 3.4 /0.55 42 3.5 /0.55 42 3.6 /0.55 42 3.7 /0.60
2001 (611) 825 43 3.8 /0.60 42 3.3 /0.50 42 3.4 /0.55 42 3.5 /0.55
to 850 43 3.6 /0.60 43 3.7 /0.60 42 3.2 /0.50 42 3.3 /0.55
3000 (914) 875 43 3.4 /0.55 43 3.5 /0.55 43 3.7 /0.60 43 3.8 /0.60
Canada 925 44 3.5 /0.55 44 3.6 /0.60 44 3.8 /0.60 43 3.4 /0.55
2001 (611) 950 44 3.3 /0.55 44 3.4 /0.55 44 3.6 /0.55 44 3.7 /0.60
to 975 44 3.2 /0.50 44 3.3 /0.50 44 3.4 /0.55 44 3.5 /0.55
4500 (1372) 1000 46 3.8 /0.60 45 3.8 /0.60 44 3.2 /0.50 44 3.3 /0.55
3001 800 43 3.8 /0.60 42 3.2 /0.50 42 3.3 /0.55 42 3.4 /0.55
(915) 825 43 3.6 /0.55 43 3.7 /0.60 43 3.8 /0.60 42 3.2 /0.50
to
4000 900 44 3.4 /0.55 44 3.5 /0.55 44 3.7 /0.60 44 3.8 /0.60
(1219) 925 44 3.2 /0.50 44 3.4 /0.55 44 3.5 /0.55 44 3.6 /0.55
4001 775 43 3.7 /0.60 43 3.8 /0.60 42 3.3 /0.50 42 3.4 /0.55
(1220) 800 43 3.5 /0.55 43 3.6 /0.60 43 3.7 /0.60 43 3.8 /0.60
to
5000 875 44 3.3 /0.55 44 3.5 /0.55 44 3.6 /0.55 44 3.7 /0.60
(1524) 900 44 3.2 /0.50 44 3.3 /0.50 44 3.4 /0.55 44 3.5 /0.55
5001 750 43 3.7 /0.60 43 3.8 /0.60 42 3.2 /0.50 42 3.3 /0.55
(1525) 775 43 3.4 /0.55 43 3.5 /0.55 43 3.7 /0.60 43 3.8 /0.60
to
6000 850 44 3.3 /0.50 44 3.4 /0.55 44 3.5 /0.55 44 3.6 /0.60
(1829) 875 45 3.7 /0.60 44 3.2 /0.50 44 3.3 /0.55 44 3.4 /0.55
6001 700 42 3.2 /0.50 42 3.3 /0.50 42 3.4 /0.55 42 3.5 /0.55
(1830) 725 43 3.6 /0.60 43 3.7 /0.60 43 3.8 /0.60 42 3.3 /0.50
to
7000 800 44 3.4 /0.55 44 3.5 /0.55 44 3.6 /0.60 44 3.7 /0.60
(2133) 825 44 3.2 /0.50 44 3.3 /0.55 44 3.4 /0.55 44 3.5 /0.55
HEATVALUE0.580.600.620.64
AT ALTITUDE Orifice Mnfld Press Orifice Mnfld Press Orifice Mnfld Press Orifice Mnfld Press
(Btu/cu ft) No. Max/Min No. Max/Min No. Max/Min No. Max/Min
900 43 3.8 /0.60 42 3.2 /0.50 42 3.3 /0.55 42 3.4 /0.55
975 44 3.7 /0.60 44 3.8 /0.60 43 3.4 /0.55 43 3.6 /0.55
1025 44 3.3 /0.55 44 3.5 /0.55 44 3.6 /0.55 44 3.7 /0.60
1100 46 3.7 /0.60 46 3.8 /0.60 45 3.8 /0.60 44 3.2 /0.50
900 44 3.7 /0.60 44 3.8 /0.60 43 3.5 /0.55 43 3.6 /0.55
775 42 3.3 /0.55 42 3.4 /0.55 42 3.5 /0.55 42 3.6 /0.60
850 44 3.8 /0.60 43 3.5 /0.55 43 3.6 /0.55 43 3.7 /0.60
875 44 3.6 /0.60 44 3.7 /0.60
950 45 3.7 /0.60 44 3.2 /0.50 44 3.3 /0.55 44 3.4 /0.55
750 42 3.3 /0.50 42 3.4 /0.55 42 3.5 /0.55 42 3.6 /0.55
825 44 3.8 /0.60 43 3.4 /0.55 43 3.5 /0.55 43 3.6 /0.60
850 44 3.5 /0.55 44 3.7 /0.60 44 3.8 /0.60 43 3.4 /0.55
925 46 3.8 /0.60 45 3.7 /0.60 44 3.2 /0.50 44 3.3 /0.55
725 42 3.2 /0.50 42 3.3 /0.55 42 3.4 /0.55 42 3.5 /0.55
800 44 3.7 /0.60 44 3.8 /0.60 43 3.4 /0.55 43 3.5 /0.55
825 44 3.5 /0.55 44 3.6 /0.55 44 3.7 /0.60 44 3.8 /0.60
900 46 3.7 /0.60 46 3.8 /0.60 45 3.8 /0.60 44 3.2 /0.50
675 42 3.4 /0.55 42 3.5 /0.55 42 3.6 /0.60 42 3.8 /0.60
750 43 3.4 /0.55 43 3.5 /0.55 43 3.6 /0.55 43 3.7 /0.60
775 44 3.6 /0.60 44 3.7 /0.60 43 3.4 /0.55 43 3.5 /0.55
850 46 3.8 /0.60 45 3.8 /0.60 44 3.2 /0.50 44 3.3 /0.55
43 3.4 /0.55 43 3.5 /0.55
SAGLARUTANFOYTIVARGCIFICEPSSAG.GVA
59MN7A
A11251A
75
Page 76
Table 21-- Orifice Size and Manifold Pressure (In. W.C.) for Gas Input Rate (Continued)
To Be Used with Modulating Furnaces Except 59MN7A060V21--20
MODULATING FURNACE
(TABULATED DATA BASED ON 20,000 BTUH M AX-HEAT / 8,000 BT UH MIN-HEAT PER BURNER,
DERATED 2%/1000 FT (305M) ABOVE SEA LEVEL)
ALTITUDE
RANGE
ft (m)
7001 675 43 3.8 /0.60 42 3.2 /0.50 42 3.3 /0.55 42 3.4 /0.55
(2134) 700 43 3.5 /0.55 43 3.7 /0.60 43 3.8 /0.60 42 3.2 /0.50
to
U.S.A. Only
59MN7A
U.S.A. Only
U.S.A. Only
* Orifice numbers shown in BOLD are factory-installed.
8000 775 44 3.3 /0.55 44 3.4 /0.55 44 3.5 /0.55 44 3.7 /0.60
(2438) 800 45 3.8 /0.60 44 3.2 /0.50 44 3.3 /0.55 44 3.4 /0.55
8001 650 43 3.8 /0.60 42 3.2 /0.50 42 3.3 /0.55 42 3.4 /0.55
(2439) 675 43 3.5 /0.55 43 3.6 /0.60 43 3.7 /0.60 42 3.2 /0.50
to
9000 750 44 3.3 /0.50 44 3.4 /0.55 44 3.5 /0.55 44 3.6 /0.55
(2743) 775 45 3.7 /0.60 44 3.2 /0.50 44 3.3 /0.50 44 3.4 /0.55
9001 600 42 3.3 /0.55 42 3.4 /0.55 42 3.6 /0.55 42 3.7 /0.60
(2744) 625 43 3.7 /0.60 42 3.2 /0.50 42 3.3 /0.55 42 3.4 /0.55
to
10000 700 44 3.4 /0.55 44 3.5 /0.55 44 3.7 /0.60 44 3.8 /0.60
(3048) 725 44 3.2 /0.50 44 3.3 /0.55 44 3.4 /0.55 44 3.5 /0.55
HEATVALUE0.580.600.620.64
AT ALTITUDE Orifice Mnfld Press Orifice Mnfld Press Orifice Mnfld Press Orifice Mnfld Press
(Btu/cu ft) No. Max/Min No. Max/Min No. Max/Min No. Max/Min
650 42 3.4 /0.55 42 3.5 /0.55 42 3.6 /0.60 42 3.7 /0.60
725 44 3.8 /0.60 43 3.4 /0.55 43 3.5 /0.55 43 3.6 /0.60
750 44 3.5 /0.55 44 3.7 /0.60 44 3.8 /0.60 43 3.4 /0.55
825 46 3.7 /0.60 46 3.8 /0.60 45 3.8 /0.60 44 3.2 /0.50
625 42 3.4 /0.55 42 3.5 /0.55 42 3.6 /0.55 42 3.7 /0.60
700 44 3.7 /0.60 43 3.4 /0.55 43 3.5 /0.55 43 3.6 /0.55
725 44 3.5 /0.55 44 3.6 /0.60 44 3.7 /0.60 44 3.8 /0.60
650 43 3.5 /0.55 43 3.6 /0.55 43 3.7 /0.60 43 3.8 /0.60
675 44 3.7 /0.60 44 3.8 /0.60 43 3.4 /0.55 43 3.5 /0.55
SAGLARUTANFOYTIVARGCIFICEPSSAG.GVA
A11251B
76
Page 77
Table 22 – Orifice Size and Manifold Pressure (In. W.C.) for Gas Input Rate
To Be Used with Modulating Furnaces 59MN7A060V21--20 Only
(TABULATED DATA BASED ON 20,200 BTUH M AX-HEAT / 8,000 BT UH MIN-HEAT PER BURNER,
DERATED 2%/1000 FT (305M) ABOVE SEA LEVEL)
ALTITUDE
RANGE
ft (m)
092543 3.7 /0.55 43 3.8 /0.60 42 3.2 /0.50 42 3.3 /0.50
(0) 950 43 3.5 /0.55 43 3.6 /0.55 43 3.7 /0.60 43 3.8 /0.60
to 1000 44 3.6 /0.55 44 3.7 /0.60 44 3.8 /0.60 43 3.5 /0.55
U.S.A. and CanadaU.S.A. and CanadaU.S.A. Only
y
l
U.S.A. On
ly
U.S.A. On
ly
U.S.A. On
2000 1050 44 3.3 /0.50 44 3.4 /0.55 44 3.5 /0.55 44 3.6 /0.55
(610) 1075 45 3.8 /0.60 44 3.2 /0.50 44 3.3 /0.50 44 3.4 /0.55
U.S.A. 800 42 3.4 /0.55 42 3.5 /0.55 42 3.7 /0.55 42 3.8 /0.60
2001 (611) 825 42 3.2 /0.50 42 3.3 /0.50 42 3.4 /0.55 42 3.6 /0.55
to 850 43 3.7 /0.60 43 3.8 /0.60 42 3.2 /0.50 42 3.3 /0.55
3000 (914) 875 43 3.5 /0.55 43 3.6 /0.55 43 3.7 /0.60 43 3.8 /0.60
Canada 925 44 3.6 /0.55 44 3.7 /0.60 44 3.8 /0.60 43 3.4 /0.55
2001 (611) 950 44 3.4 /0.55 44 3.5 /0.55 44 3.6 /0.55 44 3.7 /0.60
to 975 44 3.2 /0.50 44 3.3 /0.50 44 3.4 /0.55 44 3.6 /0.55
4500 (1372) 1000 45 3.7 /0.60 44 3.2 /0.50 44 3.3 /0.50 44 3.4 /0.55
3001 800 42 3.2 /0.50 42 3.3 /0.50 42 3.4 /0.55 42 3.5 /0.55
(915) 825 43 3.6 /0.55 43 3.7 /0.60 42 3.2 /0.50 42 3.3 /0.50
to
4000 900 44 3.5 /0.55 44 3.6 /0.55 44 3.7 /0.60 43 3.4 /0.55
(1219) 925 44 3.3 /0.50 44 3.4 /0.55 44 3.5 /0.55 44 3.6 /0.55
4001 775 43 3.8 /0.60 42 3.2 /0.50 42 3.3 /0.50 42 3.4 /0.55
(1220) 800 43 3.6 /0.55 43 3.7 /0.60 43 3.8 /0.60 42 3.2 /0.50
to
5000 875 44 3.4 /0.55 44 3.5 /0.55 44 3.6 /0.55 44 3.8 /0.60
(1524) 900 44 3.2 /0.50 44 3.3 /0.50 44 3.4 /0.55 44 3.6 /0.55
5001 750 43 3.7 /0.60 42 3.2 /0.50 42 3.3 /0.50 42 3.4 /0.55
(1525) 775 43 3.5 /0.55 43 3.6 /0.55 43 3.7 /0.60 42 3.2 /0.50
to
6000 850 44 3.3 /0.50 44 3.4 /0.55 44 3.6 /0.55 44 3.7 /0.60
(1829) 875 45 3.8 /0.60 44 3.3 /0.50 44 3.4 /0.55 44 3.5 /0.55
6001 700 42 3.2 /0.50 42 3.3 /0.50 42 3.5 /0.55 42 3.6 /0.55
(1830) 725 43 3.7 /0.60 43 3.8 /0.60 42 3.2 /0.50 42 3.3 /0.50
to
7000 800 44 3.5 /0.55 44 3.6 /0.55 44 3.7 /0.60 44 3.8 /0.60
(2133) 825 44 3.2 /0.50 44 3.4 /0.55 44 3.5 /0.55 44 3.6 /0.55
HEATVALUE0.580.600.620.64
AT ALTITUDE Orifice Mnfld Press Orifice Mnfld Press Orifice Mnfld Press Orifice Mnfld Press
(Btu/cu ft) No. Max/Min No. Max/Min No. Max/Min No. Max/Min
900 42 3.2 /0.50 42 3.3 /0.50 42 3.4 /0.55 42 3.5 /0.55
975 44 3.8 /0.60 43 3.4 /0.55 43 3.5 /0.55 43 3.6 /0.55
1025 44 3.4 /0.55 44 3.5 /0.55 44 3.6 /0.55 44 3.8 /0.60
1100 46 3.8 /0.60 45 3.7 /0.60 44 3.2 /0.50 44 3.3 /0.50
900 44 3.8 /0.60 43 3.4 /0.55 43 3.5 /0.55 43 3.6 /0.55
775 42 3.4 /0.55 42 3.5 /0.55 42 3.6 /0.55 42 3.7 /0.60
850
875 44 3.7 /0.60 44 3.8 /0.60 43 3.4 /0.55 43 3.6 /0.55
950 45 3.8 /0.60 44 3.2 /0.50 44 3.4 /0.55 44 3.5 /0.55
750 42 3.3 /0.50 42 3.4 /0.55 42 3.6 /0.55 42 3.7 /0.55
825 44 3.8 /0.60 43 3.5 /0.55 43 3.6 /0.55 43 3.7 /0.60
850 44 3.6 /0.55 44 3.7 /0.60 43 3.4 /0.55 43 3.5 /0.55
925 45 3.7 /0.60 44 3.2 /0.50 44 3.3 /0.50 44 3.4 /0.55
725 42 3.3 /0.50 42 3.4 /0.55 42 3.5 /0.55 42 3.6 /0.55
800 44 3.8 /0.60 43 3.4 /0.55 43 3.5 /0.55 43 3.6 /0.55
825 44 3.5 /0.55 44 3.7 /0.55 44 3.8 /0.60 43 3.4 /0.55
900 46 3.8 /0.60 45 3.7 /0.60 44 3.2 /0.50 44 3.3 /0.50
675 42 3.5 /0.55 42 3.6 /0.55 42 3.7 /0.60 42 3.8 /0.60
750 43 3.4 /0.55 43 3.5 /0.55 43 3.7 /0.55 43 3.8 /0.60
775 44 3.7 /0.60 44 3.8 /0.60 43 3.4 /0.55 43 3.5 /0.55
850 45 3.7 /0.60 44 3.2 /0.50 44 3.3 /0.50 44 3.4 /0.55
43 3.4 /0.55 43 3.5 /0.55 43 3.6 /0.55 43 3.8 /0.60
SAGLARUTANFOYTIVARGCIFICEPSSAG.GVA
59MN7A
A11621A
77
Page 78
Table 22 -- Orifice Size and Manifold Pressure(In. W.C.) for Gas Input Rate (Continued)
To Be Used with Modulating Furnaces 59MN7A060V21--20 Only
(TABULATED DATA BASED ON 20,200 BTUH M AX-HEAT / 8,000 BT UH MIN-HEAT PER BURNER,
DERATED 2%/1000 FT (305M) ABOVE SEA LEVEL)
ALTITUDE
RANGE
ft (m)
7001 675 42 3.2 /0.50 42 3.3 /0.50 42 3.4 /0.55 42 3.5 /0.55
(2134) 700 43 3.6 /0.55 43 3.7 /0.60 42 3.2 /0.50 42 3.3 /0.50
to
U.S.A. Only
59MN7A
U.S.A. Only
U.S.A. Only
* Orifice numbers shown in BOLD are factory-installed.
8000 775 44 3.4 /0.55 44 3.5 /0.55 44 3.6 /0.55 44 3.7 /0.60
(2438) 800 44 3.2 /0.50 44 3.3 /0.50 44 3.4 /0.55 44 3.5 /0.55
8001 650 42 3.2 /0.50 42 3.3 /0.50 42 3.4 /0.55 42 3.5 /0.55
(2439) 675 43 3.6 /0.55 43 3.7 /0.60 43 3.8 /0.60 42 3.2 /0.50
to
9000 750 44 3.3 /0.50 44 3.4 /0.55 44 3.5 /0.55 44 3.7 /0.55
(2743) 775 45 3.8 /0.60 44 3.2 /0.50 44 3.3 /0.50 44 3.4 /0.55
9001 600 42 3.4 /0.55 42 3.5 /0.55 42 3.6 /0.55 42 3.8 /0.60
(2744) 625 43 3.8 /0.60 42 3.2 /0.50 42 3.3 /0.55 42 3.5 /0.55
to
10000 700 44 3.5 /0.55 44 3.6 /0.55 44 3.7 /0.60 44 3.8 /0.60
(3048) 725 44 3.3 /0.50 44 3.4 /0.55 44 3.5 /0.55 44 3.6 /0.55
HEATVALUE0.580.600.620.64
AT ALTITUDE Orifice Mnfld Press Orifice Mnfld Press Orifice Mnfld Press Orifice Mnfld Press
(Btu/cu ft) No. Max/Min No. Max/Min No. Max/Min No. Max/Min
650 42 3.4 /0.55 42 3.6 /0.55 42 3.7 /0.60 42 3.8 /0.60
725 43 3.4 /0.55 43 3.5 /0.55 43 3.6 /0.55 43 3.7 /0.60
750 44 3.6 /0.55 44 3.7 /0.60 43 3.4 /0.55 43 3.5 /0.55
825 46 3.8 /0.60 45 3.7 /0.60 44 3.2 /0.50 44 3.3 /0.50
625 42 3.4 /0.55 42 3.5 /0.55 42 3.7 /0.55 42 3.8 /0.60
700 44 3.8 /0.60 43 3.4 /0.55 43 3.6 /0.55 43 3.7 /0.55
725 44 3.6 /0.55 44 3.7 /0.60 44 3.8 /0.60 43 3.4 /0.55
650 43 3.5 /0.55 43 3.6 /0.55 43 3.8 /0.60 42 3.2 /0.50
675 44 3.8 /0.60 43 3.4 /0.55 43 3.5 /0.55 43 3.6 /0.55
SAGLARUTANFOYTIVARGCIFICEPSSAG.GVA
A11621B
78
Page 79
SERVICE AND MAINTENANCE
PROCEDURES
!
WARNING
FIRE, INJURY OR DEATH HAZARD
Failure to follow this warning could result in personal injury, death and/or property damage.
The ability to properly perform maintenance on this equipment requires certain knowledge, mechanical skills, tools, and equipment. If you do not possess these, do not attempt to perform any service and maintenance on this equipment other than those procedures recommended in the Owner’s Manual.
!
CAUTION
ENVIRONMENTAL HAZARD
Failure to follow this caution may result in environmental pollution.
Remove and recycle all components or materials (i.e. oil, refrigerant, control board, etc.) before unit final disposal.
!
WARNING
ELECTRICAL SHOCK, FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in personal injury or death, or property damage.
Before installing, modifying, or servicing system, main electrical disconnect switch must be in the OFF position and install a lockout tag. There may be more than one disconnect switch. Lock out and tag switch with a suitable warning label. Verify proper operation after servicing.
!
CAUTION
ELECTRICAL OPERATION HAZARD
Failure to follow this caution may result in improper furnace operation or failure of furnace.
Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation.
General
These instructions are written as if the furnace is installed in an upflow application. An upflow furnace application is where the blower is located below the combustion and controls section of the furnace, and conditioned air is discharged upward. Since this furnace can be installed in any of the 4 positions shown in Fig. 2, you must revise your orientation to component location accordingly.
Electrical Controls and Wiring
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
There may be more than one electrical supply to the furnace. Check accessories and cooling unit for additional electrical supplies that must be shut off during furnace servicing. Lock out and tag switch with a suitable warning label.
The electrical ground and polarity for 115--v wiring must be properly maintained. Refer to Fig. 33 for field wiring information and to Fig. 65 for furnace wiring information.
NOTE: If the polarity is not correct, the STATUS LED on the control will flash rapidly and prevent the furnacefrom heating. The control system also requires an earth ground for proper operation of the control and flame--sensing electrode.
The 24--v circuit contains an automotive--type, 3--amp. fuse located on the control. See Fig. 34. Any shorts of the 24--v wiring during installation, service, or maintenance will cause this fuse to blow. If fuse replacement is required, use ONLY a 3--amp. fuse. The control LED will display status code 24 when fuse needs to be replaced.
Troubleshooting
Refer to the service label. See Fig. 55. The Troubleshooting Guide can be a useful tool in isolating
furnace operation problems. Beginning with the word “Start,” answer each question and follow the appropriate arrow to the next item. See Fig. 64.
The Guide will help to identify the problem or failed component. After replacing any component, verify correct operation sequence.
Proper instrumentation is required to service electrical controls. The control in this furnace is equipped with a Status Code LED (Light--Emitting Diode) to aid in installation, servicing, and troubleshooting. Status codes can be viewed at the indicator in blower door. The amber furnace control LED is either ON continuously, rapid flashing, or a code composed of 2 digits. The first digit is the number of short flashes, the second digit is the number of long flashes.
For an explanation of status codes, refer to service label located on control door or Fig. 55, and the troubleshooting guide which can be obtained from your distributor.
Retrieving Stored Fault Codes
The stored status codes will NOT be erased from the control memory, when 115-- or 24--v power is interrupted. The control will store up to the last 7 Status Codes in order of occurrence.
1. To retrieve status codes, proceed with the following:
NOTE: NO thermostat signal may be present at control, and all blower--OFF delays must be completed.
a. Leave 115--v power to furnace turned on.
b. Look into blower door indicator for current LED status.
c. Remove blower door.
NOTE: The Status Codes cannot be retrieved by disconnecting the limit switch. To retrieve Status Codes, follow the procedure below.
59MN7A
79
Page 80
2. Turn Setup Switch, SW1--1 “ON.”
3. Manually close blower door switch.
4. Control will flash up to 7 Status Codes.
5. The last Status Code, or 8th Code, will be Code 11.
6. Turn SW1--1 “OFF.”
7. A continuously--lit Amber LED will appear and indicates proper operation.
8. Release blower door switch, install blower door and refer to the SERVICE label on the control door for more inform­ation.
Component Self--Test
Component Test can ONLY be initiated by performing the following:
1. Remove blower door.
2. Remove the wire from the “R” terminal of the control board.
3. Turn Setup Switch, SW--1--6 “ON.”
4. Manually close blower door switch.
Blower door switch opens 115--v power to control. No component operation can occur unless switch is closed. Caution must be taken
59MN7A
when manually closing this switch for service purposes.
!
WARNING
Care and Maintenance
!
WARNING
FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in personal injury, death and/or property damage.
Never store flammable or combustible materials on, near, or in contact with the furnace, such as:
1. Spray or aerosol cans, rags, brooms, dust mops, vacuum cleaners, or other cleaning tools.
2. Soap powders, bleaches, waxes or other cleaning compounds, plastic or plastic containers, gasoline, kerosene, cigarette lighter fluid, dry cleaning fluids, or other volatile fluids.
3. Paint thinners and other painting compounds, paper bags, or other paper products. Exposure to these materials could lead to corrosion of the heat exchangers.
For continuing high performance and to minimize possible furnace failure, periodic maintenance must be performed on this furnace. Consult your local dealer about proper frequency of maintenance and the availability of a maintenance contract.
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury, or death.
Blower door switch opens 115--v power to furnace control. No component operation can occur unless switch is closed. Exercise caution to avoid electrical shock from exposed electrical components when manually closing this switch for service purposes.
5. Component Test sequence will function as follows: a. The furnace control CPU turns the inducer motor IDM ON
at medium speed and keeps it ON through Step d.
b. The furnace control CPU will test communication with the
modulating gas valve GV.
c. After waiting 15 seconds the furnace control CPU turns the
hot surface igniter ON for 15 seconds, then OFF.
d. The furnace control CPU then turns the blower motor
BLWM ON at mid-range airflow for 15 seconds, then OFF.
e. After shutting the blower motor BLWM OFF the furnace
control CPU shuts the inducer motor IDM OFF.
NOTE: The EAC terminals are energized when the blower is operating.
After the component test is completed, 1 or more status codes (11, 25, 35, 41, or 42) will flash. See Service Label on control door or Service/Status Code Instructions for explanation of status codes.
NOTE: To repeat component test, turn setup switch SW1-6 to OFF and then back ON.
f.TurnsetupswitchSW1--6OFF.
6. RELEASE BLOWER DOOR SWITCH, reattach wire to
“R” terminal on furnace control board and replace blower door.
!
WARNING
ELECTRICAL SHOCK AND FIRE HAZARD
Failure to follow this warning could result in personal injury, death, and/or property damage.
Turn off the gas and electrical supplies to the furnace and install lockout tag before performing any maintenance or service. Follow the operating instructions on the label attached to the furnace.
!
WARNING
CARBON MONOXIDE POISONING AND FIRE HAZARD
Failure to follow this warning could result in personal injury, death and/or property damage.
Never operate furnace without a filter or filtration device installed. Never operate a furnace with filter or filtration device access doors removed.
!
CAUTION
CUT HAZARD
Failure to follow this caution may result in personal injury. Sheet metal parts may have sharp edges or burrs. Use care
and wear appropriate protective clothing, safety glasses and gloves when handling parts, and servicing furnaces.
The minimum maintenance on this furnace is as follows:
1. Check and clean air filter each month or more frequently if required. Replace if torn.
2. Check blower motor and wheel for cleanliness each heating and cooling season. Clean as necessary.
80
Page 81
3. Check electrical connections for tightness and controls for proper operation each heating season. Service as necessary.
4. Inspect burner compartment before each heating season for rust, corrosion, soot or excessive dust. If necessary, have furnace and burner serviced by a qualified service agency.
5. Inspect the vent pipe/vent system before each heating sea­son for water leakage, sagging pipes or broken fittings. Have vent pipes/vent system serviced by a qualified service agency.
6. Inspect any accessories attached to the furnace such as a hu­midifier or electronic air cleaner. Perform any service or maintenance to the accessories as recommended in the ac­cessory instructions.
Cleaning and/or Replacing Air Filter
The air filter type may vary depending on the application or orientation. The filter is external to the furnace casing. There are no provisions for an internal filter with this furnace. See “Filter Arrangement” under the “Installation” section of this manual.
!
WARNING
CARBON MONOXIDE POISONING AND FIRE HAZARD
Failure to follow this warning could result in personal injury, death and/or property damage.
Never operate furnace without a filter or filtration device installed. Never operate a furnace with filter or filtration device access doors removed.
NOTE: If the filter has an airflow direction arrow, the arrow must point toward the blower. To clean or replace filters, proceed as follows:
!
WARNING
ELECTRICAL SHOCK, FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in personal injury or death, or property damage.
Before installing, modifying, or servicing system, main electrical disconnect switch must be in the OFF position and install a lockout tag. There may be more than one disconnect switch. Lock out and tag switch with a suitable warning label. Verify proper operation after servicing.
1. Turn off electrical supply to furnace.
2. Remove filter cabinet door.
3. Slide filter out of cabinet.
4. If equipped with permanent, washable filter, clean filter by spraying cold tap water through filter in opposite direction of airflow. Rinse filter and let dry. Oiling or coating of the filter is not recommended.
5. If equipped with factory specified disposable media filter, replace only with a factory specified media filter of the same size.
6. Slide filter into cabinet.
7. Replace filter cabinet door.
8. Turn on electrical supply to furnace.
Blower Motor and Wheel Maintenance
To ensure long life, economy, and high efficiency, clean accumulated dirt and grease from blower wheel and motor annually.
The inducer and blower motors are pre--lubricated and require no additional lubrication. These motors can be identified by the absence of oil ports on each end of the motor.
The following items should be performed by a qualified service technician. Clean blower motor and wheel as follows:
1. Turn off electrical supply to furnace.
2. Remove blower door.
3. All factory wires can be left connected, but field thermostat and accessory wiring may need to be disconnected depend­ing on their length and routing.
4. If the vent and combustion air pipe passes through the blower compartment, it will be necessary to remove the pipes from the blower compartment.
Disconnect the vent and combustion air pipe by:
a. Loosen theclamps on the vent couplings and combustion
air pipe external to the furnace.
b. Separate the pipes from the couplings and move them
aside.
c. Loosen the clamps on the vent couplings and combustion
air pipe located on the blower shelf.
d. Separate the pipes from the blower compartment and set
aside.
e. Removethecouplingsfrom the pipeadaptersandset aside.
f. After servicing the blower, reverse steps a through e.
g. Tighten all clamps 15 lb --in.
See Fig. 62 For Steps 5 through 14.
5. Remove screws securing blower assembly to blower shelf and slide blower assembly out of furnace. Detach ground wire and disconnect blower motor harness plugs from blower motor.
NOTE: Blower wheel is fragile. Use care.
6. Clean blower wheel and motor by using a vacuum with soft brush attachment. Be careful not to disturb balance weights (clips) on blower wheel vanes. Do not bend wheel or blades as balance will be affected.
7. If greasy residue is present on blower wheel, remove wheel from the blower housing and wash it with an appropriate degreaser. To remove wheel:
a. Mark blower wheel location on shaft before disassembly
to ensure proper reassembly.
b. Loosen setscrew holding blower wheel on motor shaft.
NOTE: Mark blower mounting arms and blower housing so each arm is positioned at the same hole location during reassembly.
c. Mark blower wheel orientation and cutoffplate location to
ensure proper reassembly.
d. Remove screws securing cutoff plate and remove cutoff
plate from housing.
e. Remove bolts holding motor mounts to blower housing
and slide motor and mounts out of housing.
f. Remove blower wheel from housing.
g. Clean wheel per instructions on degreaser cleaner. Do not
get degreaser in motor.
8. Reassemble motor and blower wheel by reversing items 7b through 7f. Ensure wheel is positioned for proper rotation.
9. Torque motor mounting bolts to 40 +/-- 10 lb--in. when reas­sembling.
10. Torque blower wheel set screw to 160 +/-- 20 lb--in. when reassembling.
11. Verify that blower wheel is centered in blower housing and set screw contacts the flat portion of the motor shaft. Loosen set screw on blower wheel and reposition if necessary.
12. Spin the blower wheel by hand to verify that the wheel does not rub on the housing.
59MN7A
81
Page 82
13. Reinstall blower assembly in furnace.
14. Reinstall 2 screws securing blower assembly to blower deck.
15. Reconnect blower leads to furnace control. Refer to furnace wiring diagram, and connect thermostat leads if previously disconnected.
NOTE: Be sure to attach ground wire and reconnect blower harness plugs to blower motor.
!
WARNING
ELECTRICAL OPERATION HAZARD
Failure to follow this warning could result in personal injury or death.
Blower door switch opens 115--v power to control. No component operation can occur unless switch is closed. Caution must be taken when manually closing this switch for service purposes.
59MN7A
16. Downflow or horizontal furnaces with vent pipe through furnace only:
a. Install and connect short piece of vent pipe inside furnace
to existing vent.
b. Connect vent connector to vent elbow.
17. Turn on electrical supply. If outdoor temperature is below 70_F, turn off circuit breaker to outdoor unit before running furnace in the cooling cycle. Turn outdoor circuit breaker on after completing cooling cycle. See Fig. 34. Manually close blower door switch. Use a piece of tape to hold switch closed. Check for proper rotation and speed changes between heating and cooling by jumpering R to G and R to Y/Y2 on furnace control thermostat terminals.
NOTE: If R--W/W1 thermostat terminals are jumpered at the time blower door switch is closed, blower will run for 90 sec before beginning a heating cycle.
a. Perform component self--testas shown at the bottom of the
SERVICE label, located on the control door.
b. Verify blower is rotating in the correct direction
18. If furnace is operating properly, RELEASE BLOWER DOOR SWITCH. Remove any jumpers or reconnect any disconnected thermostat leads. Replace blower door.
19. Turn on gas supply and cycle furnace through one complete heating cycle. Verify the furnace temperature rise as shown in Adjustments Section. Adjust temperature rise as shown in Adjustments Section.
Cleaning Burners and Flame Sensor
The following items must be performed by a qualified service technician. If the burners develop an accumulation of light dirt or dust, they may be cleaned by using the following procedure:
NOTE: Use a back-up wrench on the gas valve to prevent the valve from rotating on the manifold or damaging the mounting to the burner assembly.
!
WARNING
ELECTRICAL SHOCK AND FIRE HAZARD
Failure to follow this warning could result in personal injury, death, and/or property damage.
Turn off the gas and electrical supplies to the furnace and install lockout tag before performing any maintenance or service. Follow the operating instructions on the label attached to the furnace.
Refer to Fig. 63.
1. Disconnect power at external disconnect, fuse or circuit breaker.
2. Turn off gas at external shut-off or gas meter.
3. Remove control door and set aside.
4. Turn electric switch on gas valve to OFF.
5. Disconnect the gas pipe from gas valve and remove pipe from the furnace casing.
6. Disconnect the connector harness from gas valve (Modulat­ing only) or remove individual wires from terminals on gas valve (All other models).
7. Disconnect Hot Surface Igniter (HSI) wires from HSI.
8. Disconnect Flame Sensor wire from Flame Sensor.
9. Support the manifold and remove the 4 screws that secure the manifold assembly to the burner assembly and set aside. Note the location of the green/yellow wire and ground ter­minal.
10. Inspect the orifices in the manifold assembly for blockages or obstructions. Remove orifice and clean or replace orifice.
11. Remove the four screws that attach the top plate of the cas­ing to the furnace.
12. Raise top plate up slightly and prop it up with a small piece of wood or folded cardboard.
13. Support the burner assembly and remove the screws that at­tach the burner assembly to the heat exchanger cell panel.
14. Remove wires from both rollout switches.
15. Slide one--piece burner out of slots on sides of burner as­sembly.
16. Remove the flame sensor from the burner assembly.
17. (Optional) Remove the Hot Surface Igniter (HSI) and bracket from the burner assembly.
18. Check igniter resistance. Nominal resistance is 40 to 70 ohms at room temperature and is stable over the life of the igniter.
19. Clean burner with a brush and a vacuum.
20. Clean the flame sensor with fine steel wool (0000 grade). Do not use sand paper or emery cloth.
To reinstall burner assembly:
1. Install the Hot Surface Igniter (HSI) and bracket in burner assembly.
2. Install flame sensor on burner.
3. Align the edges of the one-piece burner with the slots in the burner assembly and slide the burners forward until they are fully seated in the burner assembly.
4. Align the orificesin the manifold assembly with the support rings on the end of the burner.
5. Insert the orifices in the support rings of the burners.
NOTE: If manifold does not fit flush against the burner, do not force the manifold on the burner assembly. The burners are not fully seated forward in the burner assembly. Remove the manifold and check burner positioning in the burner assembly assembly before re-installing the manifold.
6. Attach the green/yellow wire and ground terminal to one of the manifold mounting screws.
7. Install the remaining manifold mounting screws.
8. Check the igniter alignment. See Fig. 57, 58 and 63.
9. Attach the wires to the roll-out switches.
10. Align the burner assembly with the openings in the primary cell inlet panel and attach the burner assembly to the cell panel.
11. Connect the wire for the flame sensor.
12. Connect the wire for the Hot Surface Igniter.
82
Page 83
NOTE: Use propane-resistant pipe dope to prevent leaks. Do not use Teflon tape.
13. Install the gas pipe to the gas valve.
Flushing Collector Box and Drainage System
!
WARNING
!
WARNING
FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in personal injury, death, and/orproperty damage.
Never purge a gas line into a combustion chamber. Never test for gas leaks with an open flame. Use a commercially available soap solution made specifically for the detection of leaks to check all connections. A fire or explosion may result causing property damage, personal injury or loss of life.
14. Check for gas leaks with a commercially available soap solution made specifically for the detection of leaks.
15. Turn gas on at electric switch on gas valve and at external shut-off or meter
16. Turn power on at external disconnect, fuse or circuit break­er.
17. Run the furnace through two complete heating cycles to check for proper operation
18. Install control door when complete.
Servicing Hot Surface Igniter
The igniter does NOT require annual inspection. Check igniter resistance before removal. Refer to Fig. 57, 58 and 63.
1. Turn off gas and electrical supplies to furnace.
2. Remove control door.
3. Disconnect igniter wire connection.
4. Check igniter resistance. Igniter resistance is affected by temperature. Only check resistance when the igniter is at room temperature.
a. Using an ohm meter, check resistance across both igniter
leads in connector.
b. Cold reading should be between 40 ohms and 70 ohms.
Resistance reading will increase as igniter temperature increases.
5. Remove igniter assembly.
a. Usinga 1/4--in. driver,removethetwoscrews securing the
igniter mounting bracket to the burner assembly See Fig.
63.
b. Carefully withdraw the igniter and bracket assembly
through the frontof theburner assembly without striking the igniter on surrounding parts.
c. Inspect igniter for signs of damage or failure.
d. If replacement is required, remove the screw that secures
the igniter on igniter bracket and remove the igniter.
6. To replace igniter and bracket assembly, reverse items 5a through 5d.
7. Reconnect igniter harness to the igniter, dressing the igniter wires to ensure there is no tension on the igniter itself. See Fig. 63.
8. Turn on gas and electrical supplies to furnace.
9. Verify igniter operation by initiating control board self--test feature or by cycling thermostat.
10. Replace control door.
ELECTRICAL SHOCK AND FIRE HAZARD
Failure to follow this warning could result in personal injury, death, and/or property damage.
Turn off the gas and electrical supplies to the furnace and install lockout tag before performing any maintenance or service. Follow the operating instructions on the label attached to the furnace.
1. Turn off gas and electrical supplies to furnace.
2. Remove control door.
3. Disconnect pressure switch tube from pressure switch port.
NOTE: Ensure the pressure switch tube disconnected from the pressure switch is higher than the collector box opening or water will flow out of tube.
4. Remove the collector box plug from the top port on the up­per corner of the collector box. See Fig. 59.
5. Attach a funnel with a flexible tube to port on the collector box.
6. Flush inside of collector box with water until discharge water from condensate trap is clean and runs freely.
7. Repeat steps 4 thru 6 with middle plug on upper corner of collector box.
8. Remove the pressure switch tube from the collector box.
NOTE:DoNOT blow into tube with tube connected to the pressure switch.
9. Clean pressure switch port on collect box with a small wire. Shake any water out of pressure switch tube.
10. Reconnect tube to pressure switch and pressure switch port.
11. Remove the relief tube from the port on the collector box and the trap.
12. Clean the relief port on collect box and the trap with a small wire. Shake any water out of the tube.
13. Reconnect relief tube to trap and collector box ports.
Cleaning Condensate Drain and Trap
NOTE: If the condensate trap is removed, a new gasket between
the trap and collector box is required. Verify a condensate trap gasket is included in the service kit or obtain one from your local distributor.
1. Disconnect power at external disconnect, fuse or circuit breaker.
2. Turn off gas at external shut-off or gas meter.
3. Remove control door and set aside.
4. Turn electric switch on gas valve to OFF.
5. Disconnect external drain from condensate drain elbow or drain extension pipe inside the furnace and set aside.
6. Disconnect the condensate trap relief hose from collector box port and condensate trap.
NOTE: If condensate has a heat pad attached to the trap, trace the wires for the pad back to the connection point and disconnect the wires for the heat pad.
7. Remove the screw that secures the condensate trap to the collector box, remove the trap and set aside.
8. Remove the trap gasket from the collector box if it did not come off when the trap was removed.
9. Discard the old trap gasket.
10. Rinse condensate trap in warm water until trap is clean.
11. Flush condensate drain lines with warm water. Remember to check and clean the relief port on the collector box.
12. Shake trap dry.
13. Clean port on collector box with a small wire.
To re-install Condensate Drain and Trap:
1. Remove adhesive backing from condensate trap gasket
2. Install gasket on collector box
59MN7A
83
Page 84
3. Align the condensate trap with the drain opening on the col­lector box and secure the trap with the screw
4. Attach the relief hose to the relief port on the condensate trap and collector box.
5. Secure tubing to prevent any sags or traps in the tubing.
6. Connect condensate drain elbow or drain extension elbow to the condensate trap
7. Connect the leads of the condensate heat pad (if used)
8. Connect external drain piping to the condensate drain elbow or drain extension pipe.
9. Turn gas on at electric switch on gas valve and at external shut-off or meter
10. Turn power on at external disconnect, fuse or circuit break­er.
11. Run the furnace through two complete heating cycles to check for proper operation
12. Install control door when complete.
Checking Heat Pad Operation (If Applicable)
In applications where the ambient temperature around the furnace is 32_F or lower, freeze protection measures are required. If this application is where heat tape has been applied, check to ensure it
59MN7A
will operate when low temperatures are present. NOTE: The Heat Pad, when used, should be wrapped around the
condensate drain trap. There is no need to use heat tape within the furnace casing. Most heat tapes are temperature activated, and it is not practical to verify the actual heating of the tape. Check the following:
1. Check for signs of physical damage to heat tape such as nicks, cuts, abrasions, gnawing by animals, etc.
2. Check for discolored heat tape insulation. If any damage or discolored insulation is evident, replace heat tape.
3. Check that heat tape power supply circuit is on.
Cleaning Heat Exchangers
The following items must be performed by a qualified service technician.
Primary Heat Exchangers
If the heat exchangers get an accumulation of light dirt or dust on the inside, they may be cleaned by the following procedure:
NOTE: If the heat exchangers get a heavy accumulation of soot and carbon, both the primary and secondary heat exchangers should be replaced rather than trying to clean them thoroughly due to their intricate design. A build--up of soot and carbon indicates that a problem exists which needs to be corrected, such as improper adjustment of manifold pressure, insufficient or poor quality combustion air, improper vent termination, incorrect size or damaged manifold orifice(s), improper gas, or a restricted heat exchanger (primary or secondary). Action must be taken to correct the problem.
1. Turn off gas and electrical supplies to furnace.
!
WARNING
ELECTRICAL SHOCK, FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in personal injury or death, or property damage.
Before installing, modifying, or servicing system, main electrical disconnect switch must be in the OFF position and install a lockout tag. There may be more than one disconnect switch. Lock out and tag switch with a suitable warning label. Verify proper operation after servicing.
!
WARNING
ELECTRICAL SHOCK AND FIRE HAZARD
Failure to follow this warning could result in personal injury, death, and/or property damage.
Turn off the gas and electrical supplies to the furnace and install lockout tag before performing any maintenance or service. Follow the operating instructions on the label attached to the furnace.
2. Remove control door.
3. Disconnect wires or connectors to flame rollout switch, gas valve, igniter, and flame sensor.
4. Using backup wrench, disconnect gas supply pipe from fur­nace gas control valve.
5. Remove two screws attaching top filler plate and rotate up­wards to gain access to screws attaching burner assembly to cell panel.
6. Remove screws attaching burner assembly to cell panel. See Fig. 63.
NOTE: Burner cover, manifold, gas valve, and burner assembly should be removed as one assembly.
7. Clean heat exchanger openings with a vacuum and a soft brush. See Fig. 60.
NOTE: After cleaning, inspect the heat exchangers to ensure they are free of all foreign objects that may restrict flow of combustion products.
8. Reverse items 6 through 1 for reassembly.
9. Refer to furnace wiring diagram and reconnect wires to flame rollout switch, gas valve, igniter, and flame sensor.
10. Turn on gas and electrical supplies to furnace.
11. Check furnace operation through 2 complete heat operating cycles. Look at burners. Burner flames should be clear blue, almost transparent. See Fig. 61.
12. Check for gas leaks.
84
Page 85
!
WARNING
FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in personal injury, death, and/orproperty damage.
Never purge a gas line into a combustion chamber. Never test for gas leaks with an open flame. Use a commercially available soap solution made specifically for the detection of leaks to check all connections. A fire or explosion may result causing property damage, personal injury or loss of life.
13. Replace main furnace door.
Secondary Heat Exchangers
The condensing side (inside) of the secondary heat exchanger CANNOT be serviced or inspected without complete removal of the heat exchanger assembly. Detailed information on heat exchanger removal can be obtained from your Distributor.
Wiring Diagrams
See Fig. 65 for the Deluxe 4--Way Multipoise Furnace wiring diagrams.
WINTERIZATION
!
CAUTION
3. Remove furnace control door.
4. Remove the top unused rubber plug from the port on the collector box opposite the condensate trap. See Fig. 59.
5. Connect a field supplied 3/8--in. (9.5--mm) ID tube to the open port on the collector box
6. Insert a field supplied funnel into the tube.
7. Pour 1 quart of anti--freeze solution into the funnel/tube. Antifreeze should run through the inducer housing, overfill condensate trap and flow to an open drain.
8. Replace the rubber plug in the port on the collector box.
9. Remove themiddle unused rubber plug from the port on the collector box opposite the condensate trap. See Fig. 59.
10. Repeat Steps 5 through 8.
11. If a condensate pump is used, check with pump manufacturer to verify pump is safe for use with antifreeze used. Allow pump to start and pump anti--freeze to open drain.
12. Replace main door.
13. When furnace is re--started, flush condensate pump with clear water to check for proper operation before re--starting furnace.
14. Propylene glycol need not be removed before re--starting furnace.
59MN7A
UNIT AND PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in unit component or property damage.
If the furnace is installed in an unconditioned space where the ambient temperatures may be 32_ F(0_ C) or lower, freeze protection measures must be taken to prevent property or product damage.
Since the furnace uses a condensing heat exchanger, some water will accumulate in the unit as a result of the heat transfer process. Therefore, once it has been operated, it cannot be turned off and left off for an extended period of time when temperatures will reach 32_F(0_C) or lower unless winterized. Follow these procedures to winterize your furnace:
!
CAUTION
UNIT COMPONENT DAMAGE HAZARD
Failure to follow this caution may result in damage to the furnace and other property damage.
Do not use ethylene glycol (automotive antifreeze coolant or equivalent). Failure of plastic components may occur.
1. Obtain propylene glycol (RV/swimming pool antifreeze or equivalent).
2. Turn off gas and electrical supplies to your furnace.
1-1/4-in.
(31.8)
2-1/2-in.
(64.4)
Fig. 57 -- Igniter Position -- Top View
2 − in. 50 mm
3/8 − in.
9.6 mm
Fig. 58 -- Igniter Position -- Side View
3/16 − in.
4.6 mm
3/32 − in.
2.5 mm
A11405
+0.8
−1.5
A12278
85
Page 86
A11392
Fig. 59 -- Priming Condensate Trap
59MN7A
(Appearance May Vary)
Fig. 60 -- Cleaning Heat Exchanger Cell
A11273
Burner Flame
Burner
Manifold
A11461
Fig. 61 -- Burner Flame
86
Page 87
MOTOR SHAFT FLAT
SET SCREW
GROMMET
MOTOR ARM
SCREW
MOTOR WHEEL HUB
SCREW LOCATION
BLOWER HSG ASSY
BRACKET
BRACKET ENGAGEMENT
DETAIL
BRACKET
SEE DETAIL
A
59MN7A
A
CUTOFF, BLOWER
WHEEL, BLOWER
BLOWER HSG ASSY
CAPACITOR OR POWER CHOKE (WHEN USED)
MOTOR, BLOWER
SCREW
(GND)
A11584
Fig. 62 -- Blower Assembly
87
Page 88
BURNER SUPT. ASSY
IGNITER
BRACKET, IGNITER
BURNER ASSY
FLAME ROLLOUT SWITCH
FLAME SENSOR (BELOW BURNER)
59MN7A
A11403
Fig. 63 -- Burner Assembly
88
Page 89
NO
g
SEYSEYSEY
NO
YES
NO
Close door switch.
NO
Guide
Is door switch closed?
Troubleshootin
Is circuit breaker closed?
NO
YES
Check for continuity in wire from circuit
breaker to furnace.
Close circuit breaker and go back to
START.
Is 24V present at W /W1, W2, Y1, Y/Y2 or
G thermostat terminals on the furnace
Check room thermostat or
interconnecting cable.
control?
Disconnect all the thermostat wires from
the furnace control.
Does the problem repeat when using a
jumper wire?
The thermostat is not c ompatible with the
furnace control. Eithe r install a ballast
resistor, connect the Com24V thermostat
terminal to the thermostat, or replace the
thermostat.
YES
YES
59MN7A
Is there 115V going to switch?
Replace door switch.
NO
YES
Replace transformer.
Does the control respond to W/W1, W2,
Y1, Y/Y2, and G (24V) thermostat
signals?
Run system through a minimum-heat,
maximum-heat, or cooling cycle to check
operation. Status codes are erased after
72 hours or can be m anually erased by
putting setup switch SW1-1 in the ON
position and jumpering R, W/W1, and
Y/Y2 simultaneously until status code
#11 is flashed.
Replace furnace control.
ONON
Is the re 115V at L1 and L2?
ONON
Is there 24V at SEC-1 and SEC-2?
YES
Replace furnace control.
Check for correct line volt age polarity. If
units are twinned, check for proper low-
voltage (24V) transformer phasing.
YES
NO
To recall previous status codes disconnect t he R
NO
thermostat connection, reset power, and put setup
switch SW1-1 in the ON position. The AMBER LED
will flash the status codes in the order of occurrence.
Record status codes until status code #11 flashes (1
short and 1 long flash). After status code #11
flashes the status codes will repeat. Status codes
are erased after 72 hours or can be manually erased
by putting setup switch SW1-1 in the ON position
and jumpering R, W/W1, and Y/Y2 simultaneously
until status code #11 is flashed. W hen done put
setup switch SW1-1 in the O FF position.
Was there a previous status code oth er
than #11?
YES
YES
START
Is AMBER LED status light on?
Is AMBER LED status light blinking
rapidly without a paus e?
Is AMBER LED status light blinking
ON/OFF slowly with a combination of
short and long flashes?
Determine status code. The status code
is a 2 digit number with the first digit
determined by the number of short
flashes and the second digit by the
number of long flashes?
Go to section below for the status code
that was flashed.
A11290A
Fig. 64 -- Troubleshooting Guide
89
Page 90
LOCKOUT Auto-reset
45 CONTROL CIRCUITRY
open.
after 1 hour lockout due
to:
- Gas valve relay stuck
- Flame circuit failure.
- Software check error.
Reset power to clear
lockout. Replace control
if code repeats.
Replace furnace control.
Check for continuity in the
harness and igniter. Replace
defective component.
Check that all gas valves are
Check connections. If OK,
turned on. Repl ace valve.
replace control.
or rough ignition.
Check for:
- Inadequa te flame carryover
Allow unit to drop to min-heat,
- Low inlet gas pressure.
and check manifold pres sure.
- Proper firing rate.
Check connections and r etry.
If current is near typical value
(4.0-6.0 nominal) and burners
will not stay on, repeat check
in max-heat. If burners will
still not stay on replace
control. If burn ers operate in
max-heat then switch to
intermediate-heat, check
manifold pressure. If OK,
check burner carryover and
Repeat test to check for
intermittent operation.
flame sensor location.
NO
YES
NO
NO
NO
YES
YES
YES
YES
NO
NO
NO
NO
YES
YES
59MN7A
43 LOW OR MEDIUM PRESSURE SW ITCH
32 LOW PRESSURE SWITCH DID NOT
OPEN W HILE MEDIUM OR H IGH
CLOSE OR REOPENED – If opens during
tubing.
PRESSURE SWIT CH IS CLOSED -
Check for:
- Low or Me d press. switch stuck open.
- Disconnected or obstructed pressure
blower on-delay period, blower will come
on for the selected blower off-delay. If
opens within 5 minutes af ter ignition the
next heating cycle will be restricted to
maximum-heat. Check for:
pipe.
Unplug igniter harness from control and
repeat component test by turning setup
switch SW1-6 OFF and then back ON.
Check for 115V between pin 3 and
NEUTRAL-L2 on the control. W as 115V
present for the 15 second period?
Reconnect the R thermos tat lead and set
thermostat to call for heat. Connect
voltmeter across gas valve BLUE and
GREEN/YELLOW wires. Does gas valve
receive 24V?
Does gas valve open and allow gas to
flow?
Do the main burners ignite?
- Low inlet gas pressure (if LGPS used).
- Plugged condensate drain.
- Water in vent piping, possible sagging
- Improper pressure switch wiring.
Do the main burners stay on?
Repeat call for heat and check flame
sensor current during trial for ignition
period. Is the DC microamps below 0.5?
NO
71% of maximum
compartment.
tubing.
setup switch SW1-3 ON to boost
inducer speed
- Proper v ent sizing.
- Air leak between vestibule and blower
- Low inlet gas pressure (if LGPS used).
-Restrictedvent.
- Disconnected or obstructed pressure
- Defective or miswired pressure switches
- Excessive wind. If pro blem persists turn
pipe.
- Plugged condensate drain.
- Water in vent piping, possible sagging
33 LIMIT CIRCUIT FAULT – Indicates the
limit or a flame rollout switch is open or the
rate. Blower will run for 4 min. or until
open switch remakes whichever is longer.
If open longer than 3 min., code changes
to lockout #13. If open less than 3 min.
status code #33 continues to flash until
furnace is operating in maximum-heat only
mode due to 2 successive limit trips while
operating at any rate <
blower shuts off. Flame rollout switch
gas input adjustment.
requires manual reset. Check for:
- Loose blower wheel.
- Defective s witch or connections.
- Improper minimum- or maximum-heat
- Improper limit switch or no limit gasket.
- Dirty filter or restricted duct s ystem.
not sensed during the trial for ignition
period, the control will repeat the ignition
34 IGNITION PROVING FAILURE – If flame is
Clean flame sensor with fine steel wool
and recheck current. Nominal current i s
4.0 to 6.0 microamps.
Is current near typical value? Replace electrode.
Will main burners ignite and stay on? Replace f urnace control.
Fixed.
YES
sequence 3 more times before lockout #14
occurs. If flame signal is lost during the
blower on-delay period, blower will come on
for the selected blower off-delay. Ch eck
the following items first before proceeding
connected to furnace s heet metal.
to the next step.
- Gas valve turned off.
- GREEN/YELLOW wire MUST be
- Flame sensor must not be grounded.
To determine whether the problem is in the
gas valve, igniter, or flame sensor the
system can be operated in component test
mode. To check the igniter remove the R
thermostat connection from the control,
reset power, and put setup switch SW1-6 in
the ON position to start the component test.
Does the igniter glow orange/white by the
- Manual shut-off valve.
end of the 15 second warm-up period?
erased after 72 hours or can be manually
erased by putting setup switch SW1-1 in
the ON position and jumperi ng R, W/W1,
and Y/Y2 simultaneously until status code
#11 is flashed. Run system through a
minimum-heat, maximum-heat, or cooling
cycle to check system.
(115V OR 24V) – Normal operation.
Blower runs for 90 sec onds, if unit is
powered up during a c all for heat (R-
W/W1 closed) or when (R-W /W1 opens)
during the blower on- delay period.
11 NO PREVIOUS CODE – Status codes are
12 BLOWER ON AFTER POWER UP –
13 LIMIT CIRCUIT LOCKOUT – Lockout
wiring including thermostat leads.
Disconnect thermostat leads to isolate
occurs if the limit or flame rollout switch is
open longer than 3 minutes or 10
successive limit trips occurred during
maximum-heat. Control will auto-reset
after 3 hours. See code 33.
ignite gas and prove flame i n 4 attempts.
Control will auto-reset after 3 hours. See
status code 34.
the blower failed to reach 250 RPM or the
blower failed to communicate within 30
seconds after being tur ned ON in two
successive heating cycles. Control will
14 IGNITION LOCKOUT – System failed to
15 BLOWER MOTOR LOCKOUT – Indicates
power a nd wait 5 m inutes to retry. Che ck
for:
- Stuck closed gas valve relay on control.
- Miswire or short to gas valve BLUE wire.
Flame is proved while gas valve is de-
energized. Inducer will run until fault is
cleared. Check for:
- Stuck open or leaky gas valve.
auto-reset after 3 hours. See code 41.
21 GAS HEATING LOCKOUT – Turn off
22 ABNORMAL FLAME-PROVING SIGNAL
Check for:
- Obstruct ed pressure tube.
- Pressure switch stuck closed.
23 PRESSURE SWITCH DID NOT OPEN –
24 SECONDARY VOLTAGE FUSE IS OPEN
Check for:
- Short circ uit in secondary voltage (24V)
short circuit.
A11290B
90
Page 91
NO
Youhaveanopenwireorbad
terminal on either the BLACK or
WHITE power leads between
the furnace control and the
blower motor. If you have a
power choke disconnect it and
check continuity.
Youhaveanopenwireorbad
terminal on either the RED or
GREEN wire between the
furnace control and the blower
motor.
YES
Is there 5-VDC at PL3-3
YELLOW (+) and PL3-2
GREEN (-)?
Youhaveanopenwireorbad
terminal on the YELLOW wire
between the furnace control and
the blower motor.
NO
YES
YES
YES
NO
NO
NO
YES
NO
59MN7A
Turn power back on. Is there 115VAC at
PL14-5 and PL14-4?
Is there 12-VDC at PL13-1 RED (+) and
PL13-4 GREEN (-)?
YES
Is there 12-VDC at P L3-1 RED (+) and
PL3-2 GREEN (-)?
Replace the furnace control.
Is there 5-VDC at PL13-2 YELLOW (+)
and PL13-4 GREEN (-)?
The voltage just measured should be
very stable and should not fluctuate more
than .02-VDC. If the voltage fluctuates
more than this get a different voltmeter
before proceeding.
Turn power off, reconnect PL13 and
PL14 to the blower motor, then turn
power back on. Connect a DC voltmeter
across PL3-3 YELLOW (+) and PL3-2
GREEN (-). Does the voltage fluctuate
more than it did in the previous step?
Turn power off, disconnect PL13 and
PL14 from the blower motor, then turn
power back on. Connect a DC voltmeter
across PL13-3 BLUE (+) and PL13-4
GREEN (-). The voltage should be near
0-VDC but it will fluctuate briefly several
times a second. If you have an analog
voltmeter the needle will briefly go high
several times a second. If you have a
digital voltmeter with a bar graph it will
show a large change in magnitude on the
bar graph several times a second. If you
have a standard digi tal voltmeter it will
show a brief fluctuation in voltage and the
magnitude may vary depending on the
voltmeter used.
YES
NO
NO
NO
YES
blower failed to reach 250 RPM or the
blower failed to communicate within the
prescribed time limits. Thirty seconds
after being turned ON or ten seconds
during steady-state operation. Turn power
off and check the following items first
before proceeding to the next step.
41 BLOWER MOTOR FAULT – Indicates the
- Rubbing blower wheel.
motor.
- Loose blower wheel.
- Wiring from furnace control to blower
Remove the R thermostat connection from
the furnace control, disconnect both
connectors from the blower motor PL13
and PL14. Does the blower wheel turn
freely?
Replace the blower control module attached to
the blower motor. Follow the instructions with
the blower control module to make sure the
entire blower motor does not need to be
replaced.
You have an open wire or bad terminal on the
BLUE wire between the furnace control and the
blower motor.
Replace the furnace control.
Connect a DC voltmeter across PL3-4 BLUE
(+) and PL3-2 GREEN (-). Does the voltage
fluctuate as described two steps back?
Does the voltage fluctuate as described in the
previous step?
Replace the blower control module attached to
the blower motor. Follow the instructions with
the blower control module to make sure the
entire blower motor does not need to be
replaced.
YES
no valid model stored in permanent
memory. This will happen if you forget
to install the model plug PL4 on a
SETUP ERROR – If status code 25 only
flashes 4 times on power-up the control is
missing its model plug PL4 and is
defaulting to the model selection stored in
memory. If status code 25 flashes
continuously it could indicate any of the
following:
- Model plug PL4 is missing and there is
25 INVA LID MODEL SELEC TION OR
service replacement control.
- Thermostat call with SW1-1 ON.
- Thermostat call with SW1-6 ON.
Need modulating board with software
-SW1-1andSW1-6bothON.
version V17 or later.
- Two different furnace models twinned.
- Service replacement control is incorrect.
PRESSURE SWITCH, OR PSR RELAY
DID NOT CLOSE OR REOPENED -
Check for:
- PSR relay may be defective.
- See status code 32.
modulating gas valve failed to respond to
a command from the furnace control or
31 MEDIUM PRESSURE SWITCH, HIGH
35 GAS VALVE FAULT – Indicates the
ORANGE wire at gas valve or PL8
connections.
inducer motor has not started within 20
seconds after a call for heat, the inducer
motor RPM is outside its valid range of
operation, or the inducer RPM signal was
lost for 5 seconds during operation.
Check for:
- Proper vent sizing.
-Failedinducermotor.
- Restricted combustion air supply.
power to the gas valve electronics was
interrupted. Check for:
- Intermittent RED, YELLOW , or
42 INDUCER MOTOR FAULT – Indicates the
- Improper motor wiring.
A11290C
91
Page 92
SEQUENCE OF OPERATION
!
CAUTION
UNIT OPERATION HAZARD
Failure to follow this caution may result in intermittent unit operation.
Furnace control must be grounded for proper operation or control will lock out. Control is grounded through green/yellow wire routed to gas valve and burner box screw.
Using the schematic diagram, follow the sequence of operation through the different modes. See Fig. wiring diagram very carefully!!
NOTE: If a power interruption occurs during a call for heat (W/W1 or W/W1-and-W2), the control will start a 90-second blower-only ON period two seconds after power is restored, if the thermostat is still calling for gas heating. The amber LED light will flash code 12 during the 90-second period, after which the LED
59MN7A
will be ON continuous, as long as no faults are detected. After the 90-second period, the furnace will respond to the thermostat normally.
The blower door must be installed for power to be conducted through the blower door interlock switch ILK to the furnace control CPU, transformer TRAN, inducer motor IDM, blower motor BLWM, hot surface igniter HSI, and gas valve GV.
Communicating Control and Modulating Heating (Adaptive Mode)
Best comfort will be attained when a communicating wall control is used with this product. Wiring and set--up instructions are provided with the communicating control. See the furnace data sheet accessory section for help in selecting the appropriate communicating control for this furnace.
When a communicating control is used, the furnace will modulate through its full operation range, or can be limited via the minimum and maximum cfm configurations.
Operation of the furnace at the beginning and end of each heating cycle will be the same as detailed below in the Single--Stage Thermostat section EXCEPT that the communicating control will send modulating rate command signals through the communication bus rather than energizing the 24--v thermostat terminals. Note that the R to W/W1 circuit signal will be controlled by the COMMR relay on the furnace control. See the wiring diagram in Fig. 65 .
Single-Stage Thermostat and Modulating Heating (Adaptive Mode)
See Fig. 34 and 35 for thermostat connections. NOTE: Minimum-heat only switch SW1-2 selects the
minimum-heat only operation mode when ON. Intermediate-heat only switch SW4-2 selects intermediate-heat only operation mode when ON. If both switches are ON the furnace control will default to intermediate-heat. If either or both switches are ON, the furnace control will operate at two-stages only as referenced in Two Stage Thermostat section below. If both switches are OFF the furnace control will operate in the adaptive heating mode in response to a call for heat. See Fig. 56. When the W2 thermostat terminal is energized it will always cause maximum-heat operation as long as the R to W circuit is closed, regardless of the setting of the minimum-heat or intermediate-heat only switches.
This furnace can operate as a modulating furnace with a single-stage thermostat because the furnace control CPU includes a programmed adaptive sequence of controlled operation, which selects a modulated rate between minimum- and maximum-heat.
65. Read and follow the
This selection is based upon the stored history of the length of previous gas-heating periods of the single-stage thermostat.
The furnace will start up in either intermediate-, or maximum-heat. The furnace will transition and operate at minimum-heat or the calculated modulating rate after starting and operating for 45 seconds at intermediate-heat. The furnace control CPU defaults to minimum-heat on the first thermostat cycle and calculates the modulating rate that the furnace should run at for 19 minutes on subsequent heat cycles.
If the power is interrupted, the stored modulating rate is erased and the furnace control will select intermediate-heat for 45 seconds, minimum-heat for 19 minutes and then switch to maximum-heat, as long as the thermostat continues to call for heat. The furnace control CPU then uses this information to calculate the modulating rate the furnace will operate at on the next heating cycle. If the calculated modulating rate is between 40% - 99% then the furnace control CPU will operate for 45 seconds at intermediate-heat, and then operate at the calculated modulating rate for up to 19 minutes and then switch to maximum-heat as long as the thermostat continues to call for heat. If the calculated modulating rate is 100% then the furnace control will only operate at maximum-heat until the thermostat is satisfied.
The wall thermostat ”calls for heat”, closing the R to W circuit. The furnace control CPU performs a self-check, verifies the low, medium, and high pressure switch contacts LPS,MPS, and HPS are open, then de-energizes the PSR relay to close the NC contact.
1. Inducer Prepurge Period - The furnace control CPU turns
on inducer motor IDM and slowly increases the inducer motor speed. After the low pressure switch LPS closes the furnace control CPU continues to increase the inducer mo­tor speed until the medium pressure switch MPS closes. When the medium pressure switch MPS closes, inducer mo­tor RPM is noted by the furnace control CPU, and a 25-second prepurge period begins. The RPM is used to evaluate vent system resistance. This evaluation is then used to determine the required RPM necessary to operate the inducer motor during pre-purge, the first 45 seconds of intermediate-heat, or any modulating rate that the furnace will transition to after the blower on-delay is completed.
NOTE: The heat cycle can start in either intermediate- or maximum-heat. If a maximum-heat cycle is initiated, the furnace control CPU will continue to increase the inducer motor speed after the medium pressure switch MPS closes. When the medium pressure switch closes, inducer motor RPM is noted by the furnace control CPU, and a 25-second prepurge period begins. The RPM is used to evaluate vent system restriction. This evaluation is then used to determine the required RPM necessary to operate the inducer motor in maximum-heat pre-purge, or maximum-heat. The high pressure switch HPS should be closed before ignition but the furnace control ignores this input until after ignition occurs.
2. Igniter Warm-Up - At the end of the prepurge period, the
Hot-Surface Igniter HSI is energized for a 17-second ig­niter warm-up period
3. Trial-For-Ignition Sequence - When the igniter warm-up
period is completed the main gas valve relay contact GVR closes to energize the gas valve solenoid GV (pin 5). The gas valve solenoid GV (pin 5) permits gas flow to the burn­ers where it is ignited. Five seconds after the GVR closes, a 2-second Flame-Proving period begins. The HSI igniter will remain energized until flame is sensed or until the 2-second flame proving period begins.
4. Flame-Proving - When the burner flame is proved at the
flame-proving sensor electrode FSE, the furnace control CPU begins the blower-ON delay period and continues to hold the gas valve GV (pin 5) open. If the burner flame is not proved within two seconds, the furnace control CPU will close the gas valve GV (pin 5), and the furnace control
92
Page 93
CPU will repeat the ignition sequence for up to three more Trials-For-Ignition before going to Ignition-Lockout. Lock- out will be reset automatically after three hours, or by mo­mentarily interrupting 115 vac power to the furnace, or by interrupting 24 vac power at SEC1 or SEC2 to the furnace control CPU (not at W/W1, G, R, etc.). If flame is proved when flame should not be present, the furnace control CPU will lock out of Gas-Heating mode and operate the inducer motor IDM at full speed until flame is no longer proved.
5. Inducer Speed Change - If the cycle starts in intermedi­ate-heat, the furnace control CPU reduces the inducer speed slightly after flame sense. If cycle starts in maximum-heat, the furnace control CPU increases the inducer speed after flame sense.
6. Blower-On delay — If the burner flame is proven, the blower-ON delay for intermediate-heat and maximum-heat are as follows: Intermediate-heat - 45 seconds after the gas valve GV (pin
5) is opened the blower motor BLWM is turned ON at the modulating heat airflow. Maximum-heat - 25 seconds after the gas valve GV (pin 5) is opened the BLWM is turned ON at maximum-heat air­flow. Simultaneously, the humidifier terminal HUM and elec­tronic air cleaner terminal EAC-1 are energized and remain energized throughout the heating cycle.
7. Switching from Intermediate-Heat to a Low Range In- put - If the furnace control CPU switches from intermedi­ate-heat to a low range input (low range input is an input rate less than or equal to 51% of full rate), the furnace control CPU will turn the blower ON or switch to the mod­ulating heat airflow, energize the PSR relay to open the NC contact, and slowly decrease the inducer motor speed to the desired inducer RPM.
Switching from a Intermediate-Heat to a Medium Range Input - If the furnace control CPU switches from
intermediate-heat to a different medium range input (medi­um range input is an input rate between 52% and 71% of full rate), the furnace control CPU will turn the blower ON or switch to the modulating heat airflow, and continue to maintain the inducer motor speed or change it further if re­quired.
Switching from a Intermediate-Heat to a High Range Input - If the furnace control CPU switches from intermedi-
ate-heat to a high range input (high range input is an input rate greater than or equal to 72% of full rate), the furnace control CPU will turn the blower ON or switch to the mod­ulating heat airflow, and increase the inducer motor speed to the desired inducer motor RPM. Switching from Low Range Input to Maximum-Heat - If the furnace control CPU switches from a low range input to maximum-heat, the furnace control CPU will de-ener­gize the PSR relay to close the NC contact and slowly in­crease the inducer motor speed until the medium pressure switch MPS closes. When the medium pressure switch MPS closes the inducer motor RPM is noted by the furnace control CPU. The RPM is used to evaluate vent system res­istance. This evaluation is then used to determine the re­quired RPM necessary to operate the inducer motor at maximum-heat. The blower motor BLWM will transition to maximum-heat airflow five seconds after the furnace control CPU switches from a low range input to maxim­um-heat. As the inducer RPM increases, the high pressure switch HPS should close.
Switching from Medium Range Input to Maxim­um-Heat - If the furnace control CPU switches from medi-
um range input to maximum-heat, the furnace control CPU will increase the inducer motor speed to the maximum-heat
inducer motor RPM. The blower motor BLWM will trans­ition to the maximum-heat airflow five seconds after the furnace control CPU switches from a medium range input to maximum-heat. As the inducer RPM increases, the high pressure switch HPS should close.
8. Blower-Off Delay — When the thermostat is satisfied, the
R to W circuit is opened, de-energizing the gas valve GV (pin 5), stopping gas flow to the burners, and humidifier ter­minal HUM. The inducer motor IDM will remain energized fora 15-second post-purge period. The blower motor BL­WM and air cleaner terminal EAC-1 will remain energized at minimum-heat airflow or transition to minimum-heat air­flow for 90, 120, 150, or 180 seconds (depending on selec­tion at blower-OFF delay switches). The furnace control CPU is factory-set for a 120-second blower- OFF delay.
Two--Stage Thermostat and Modulating Heating (Adaptive Mode)
Operation of Modulating Heating (Adaptive Mode; SW1--2 and SW4--2 are both OFF) with a two--stage thermostat is the same as with a single--stage thermostat, EXCEPT for the following:
If the two--stage thermostat R--W2 circuit closes along with the R to W/W1 circuit, while the furnace is operating at any capacity less than maximum, the furnace will switch to the maximum heating capacity. At this point, the furnace control heating algorithm is overridden and the two--stage thermostat takes control of staging until BOTH R to W/W1 and R to W2 circuits are opened.
The furnace with transition back to the lower heating capacity if the two--stage thermostat opens the R--W2 circuit, but leaves R to W/W1 circuit closed. The furnace control will continue to follow the commands from the two--stage thermostat for W/W1 and W2, until the R to W/W1 circuit is opened.
After the two--stage thermostat opens both the R to W/W1 and R to W2 circuits, the adaptive algorithm will set the beginning capacity of the next heating cycle to the same value as the heating cycle that most recently completed.
Two-Stage Thermostat and Two-Stage Minimum/Max­imum Heating
See Fig. 34 and 35 for thermostat connections. NOTE: In this mode, the minimum-heat only switch SW1-2 must
be ON to select the minimum-heat only operation mode in response to closing the thermostat R to W1 circuit. Closing the thermostat R to W1-and-W2 circuits always causes maximum-heat operation, regardless of the setting of the minimum-heat only switch.
The furnace will start up in either intermediate-, or maximum-heat. The furnace will operate in minimum-heat after starting and operating for 1 minute at intermediate-heat before transitioning to minimum-heat.
The wall thermostat ”calls for heat”, closing the R to W1 circuit for minimum-heat or closing the R to W1-and-W2 circuits for maximum-heat. The furnace control performs a self-check, and verifies the low, medium and high pressure switch contacts LPS, MPS and HPS are open,then de-energizes the PSR relay to close the NC contact.
The start up and shut down functions and delays described above apply to the 2-stage minimum/maximum heating mode as well, except for switching from maximum- to minimum-heat.
1. Switching from Maximum- to Minimum-Heat —Ifthe
thermostat R to W2 circuit opens, and the R to W1 circuit remains closed, the furnace control CPU will gradually de­crease the inducer motor speed to the required intermedi­ate-heat RPM. When the inducer motor IDM reduces pres­sure sufficiently, the high pressure switch HPS will open and the gas rate will be changed to intermediate-heat. The gas valve solenoid GV (pin 5) will remain energized as long as the low pressure switch LPS remains closed. When the
59MN7A
93
Page 94
inducer motor speed gets within 15% of the required inter­mediate-heat RPM the furnace control CPU will start a 5 second blower airflow change delay. After the 5 second blower airflow change delay is completed the blower air­flow will transition to minimum-heat airflow. At this point the furnace control CPU will energize the PSR relay to open the NC contact and slowly decrease the inducer motor speed to the required minimum-heat RPM. When the PSR relay is energized and the NC contact opens the fur­nace control CPU will reduce the gas rate to minimum-heat RPM.
Two-Stage Thermostat and Two-Stage Intermediate/ Maximum Heating
See Fig. 34 and 35 for thermostat connections NOTE: In this mode the intermediate-heat only switch SW4-2
must be ON to select the intermediate-heat only operation mode in response to closing the thermostat R to W1 circuit. Closing the thermostat R to W1-and-W2 circuits always causes maximum-heat operation, regardless of the setting of the intermediate-heat only switch.
The wall thermostat ”calls for heat”, closing the R to W1 circuit for
59MN7A
intermediate-heat or closing the R to W1-and-W2 circuits for maximum-heat. The furnace control performs a self-check, and verifies the low, medium and high pressure switch contacts LPS, MPS and HPS are open , then de-energizes the PSR relay to close the NC contact.
The start up and shut down functions and delays described above apply to the 2-stage intermediate/maximum heating mode as well, except for switching from maximum- to intermediate-heat.
1. Switching from Maximum- to Intermediate-Heat — If the thermostat R to W2 circuit opens, and the R to W1 cir­cuit remains closed, the furnace control CPU will gradually decrease the inducer motor speed to the required interme­diate-heat RPM. When the inducer motor IDM reduces pressure sufficiently, the high pressure switch HPS will open and the gas rate will be changed to intermediate-heat. When the inducer motor speed gets within 15% of the re­quired intermediate-heat RPM the furnace control CPU will start a 5 second blower airflow change delay. After the 5 second blower airflow change delay is completed the blower airflow will transition to intermediate-heat airflow.
Cooling Mode
The thermostat “calls for cooling.”
1. Single-Speed Cooling
See Fig. 34 and 35 for thermostat connections. The thermostat closes the R to G-and-Y circuits. The R to Y circuit
starts the outdoor unit, and the R to G-and-Y/Y2 circuits start the furnace blower motor BLWM on cooling airflow. Cooling airflow isbasedontheA/CselectionshowninFig.56.
The electronic air cleaner terminal EAC-1 is energized with 115 vac when the blower motor BLWM is operating. When the thermostat is satisfied, the R to G-and-Y circuits are opened. The outdoor unit will stop, and the furnace blower motor BLWM will continue operating at cooling airflow for an additional 90 seconds. Jumper Y/Y2 to DHUM to reduce the cooling off-delay to 5 seconds. See Fig. 34.
2. Single-Stage Thermostat and Two-Speed Cooling (Ad- aptive Mode)
See Fig. 34 and 35 for thermostat connections. This furnace can operate a two-speed cooling unit with a
single-stage thermostat because the furnace control CPU includes a programmed adaptive sequence of controlled operation, which selects low-cooling or high-cooling operation. This selection is based upon the stored history of the length of previous cooling period of the single-stage thermostat.
NOTE: The air conditioning relay disable jumper ACRDJ must be connected to enable the adaptive cooling mode in response to a call for cooling. See Fig. 34. When in place the furnace control CPU can turn on the air conditioning relay ACR to energize the Y/Y2 terminal and switch the outdoor unit to high-cooling.
The furnace control CPU can start up the cooling unit in either low- or high-cooling. If starting up in low-cooling, the furnace control CPU determines the low-cooling on-time (from 0 to 20 minutes) which is permitted before switching to high-cooling.
If the power is interrupted, the stored history is erased and the furnace control CPU will select low-cooling for up to 20 minutes and then energize the air conditioning relay ACR to energize the Y/Y2 terminal and switch the outdoor unit to high-cooling, as long as the thermostat continues to call for cooling. Subsequent selection is based on stored history of the thermostat cycle times. The wall thermostat “calls for cooling”, closing the R to G and- Y circuits. The R to Y1 circuit starts the outdoor unit on low-cooling speed, and the R to G-and-Y1 circuits starts the furnace blower motor BLWM at low-cooling airflow which is the true on-board CFselectionasshowninFig.56.
If the furnace control CPU switches from low-cooling to high cooling, the furnace control CPU will energize the air conditioning relay ACR. When the air conditioning relay ACR is energized the R to Y1-and-Y2 circuits switch the outdoor unit to high-cooling speed, and the R to G-and-Y1- and-Y/Y2 circuits transition the furnace blower motor BLWM to high-cooling airflow. High-cooling airflow is based on the A/C selection shown in Fig.
56. NOTE: When transitioning from low-cooling to high-cooling the
outdoor unit compressor will shut down for 1 minute while the furnace blower motor BLWM transitions to run at high-cooling airflow.
The electronic air cleaner terminal EAC-1 is energized with 115 vac whenever the blower motor BLWM is operating.
When the thermostat is satisfied, the R to G-and-Y circuit are opened. The outdoor unit stops, and the furnace blower BLWM and electronic air cleaner terminal EAC-1 will remain energized for an additional 90 seconds. Jumper Y1 to DHUM to reduce the cooling off-delay to 5 seconds. See Fig. 34.
3. Two Stage Thermostat and Two-Speed Cooling
See Fig. 34 and 35 for thermostat connections. NOTE: The air conditioning relay disable jumper ACRDJ must
be disconnected to allow thermostat control of the outdoor unit staging. See Fig. 34.
The thermostat closes the R to G-and-Y1 circuits for low cooling or closes the R to G-and-Y1-and-Y2 circuits for high cooling. The R to Y1 circuit starts the outdoor unit on low cooling speed, and the R to G-and-Y1 circuit starts the furnace blower motor BLWM at low-cooling airflow which is the true on-board CF selection as shown in Fig. 56. The R to Y1-and-Y2 circuits start the outdoor unit on high-cooling speed, and the R to G-and-Y/Y2 circuits start the furnace blower motor BLWM at high-cooling airflow. High-cooling airflow is based on the A/C selection shown in Fig.
56. The electronic air cleaner terminal EAC-1 is energized with 115
vac whenever the blower motor BLWM is operating. When the thermostat is satisfied, the R to G-and-Y1 or R to
G-and-Y1-and-Y2 circuits are opened. The outdoor unit stops, and the furnace blower BLWM and electronic air cleaner terminal EAC-1 will remain energized for an additional 90 seconds. Jumper Y1 to DHUM to reduce the cooling off-delay to 5 seconds. See Fig. 56.
4. Dehumidification Mode
See Fig. 34 and 35 for thermostat connections. The dehumidification output, D or DHUM on the Thermostat
should be connected to the furnace control thermostat terminal
94
Page 95
DHUM. When there is a dehumidify demand, the DHUM input is activated, which means 24 vac signal is removed from the DHUM input terminal. In other words, the DHUM input logic is reversed. The DHUM input is turned ON when no dehumidify demand exists. Once 24 vac is detected by the furnace control, dehumidification capability is activated. If the DHUM input is removed for more than 48 hours, the furnace control reverts back to non-dehumidification mode.
The cooling operation described above in the Cooling Mode section also applies to Dehumidification mode. The exceptions are listed below:
a. Low cooling – When the R to G-and-Y1 circuit is closed
and there is a demand for dehumidification, the furnace blowermotorBLWM will drop theblowerairflow to 86% of low cooling airflow which is the true on-board CF
selectionasshowninFig.56.
b. High cooling–WhentheRtoG-and Y/Y2 circuit isclosed
and there is a demand for dehumidification, the furnace blowermotorBLWM will drop theblowerairflow to 86% of high-cooling airflow. High-cooling airflow is basedon
the A/C selection shown in Fig. 56.
c. Cooling off-delay – When the “call for cooling” is
satisfied and there is a demand for dehumidification, the cooling blower-off delay is decreased from 90 seconds
to 5 seconds.
Super Dehumidify Mode
Super-Dehumidify mode can only be entered if the furnace control is in the Dehumidification mode and there is a demand for dehumidification. The cooling operation described in Cooling Mode section above also applies to Super Dehumidify Mode. The exceptions are listed below:
1. Low cooling –WhentheRtoY1circuitisclosed,RtoG circuit is open, and there is a demand for dehumidification, the furnace blower motor BLWM will drop the blower air­flow to 65% of low-cooling airflow for a maximum of 10 minutes each cooling cycle or until the R to G circuit closes or the demand for dehumidification is satisfied. Low-cool­ing airflow is the true on-board CF selection as shown in
Fig. 56.
2. High cooling – When the R to Y/Y2 circuit is closed, R to G circuit is open, and there is a demand for dehumidifica­tion, the furnace blower motor BLWM will drop the blower airflow to 65% of high-cooling airflow for a maximum of 10 minutes each cooling cycle or until the R to G circuit closes or the demand for dehumidification is satisfied. High-cooling airflow is based on the A/C selection shown
in Fig. 56.
3. Cooling off-delay – When the “call for cooling” is satisfied and there is a demand for dehumidification, the cooling blower-off delay is decreased from 90 seconds to 5 seconds.
Continuous Blower Mode
When the R to G circuit is closed by the thermostat, the blower motor BLWM will operate at continuous blower airflow. Continuous blower airflow selection is initially based on the CF selection shown in Fig. 56. Factory default is shown in Fig. 56. Terminal EAC-1 is energized as long as the blower motor BLWM is energized.
During a call for heat, the furnace control CPU will transition the blower motor BLWM to continuous blower airflow, minimum-heat airflow, or the mid-range airflow, whichever is lowest. The blower
motor BLWM will remain ON until the main burners ignite then shut OFF and remain OFF for the blower-ON delay (45 seconds in intermediate heat, and 25 seconds in maximum-heat), allowing the furnace heat exchangers to heat up more quickly, then restarts at the end of the blower-ON delay period at modulating or maximum-heat airflow respectively.
The blower motor BLWM will revert to continuous-blower airflow after the heating cycle is completed. When the thermostat satisfies, the furnace control CPU will drop the blower motor BLWM to minimum-heat airflow during the selected blower-OFF delay period before transitioning to continuous-blower airflow.
When the thermostat “calls for low-cooling”, the blower motor BLWM will operate at low-cooling airflow. When the thermostat is satisfied, the blower motor BLWM will operate an additional 90 seconds at low-cooling airflow before transitioning back to continuous-blower airflow.
When the thermostat “calls for high-cooling”, the blower motor BLWM will operate at high cooling airflow. When the thermostat is satisfied, the blower motor BLWM will operate an additional 90 seconds at high-cooling airflow before transitioning back to continuous-blower airflow.
When the R to G circuit is opened, the blower motor BLWM will continue operating for an additional 5 seconds, if no other function requires blower motor BLWM operation.
Continuous Blower Speed Selection from Thermostat
To select different continuous-blower airflows from the room thermostat, momentarily turn off the FAN switch or push button on the room thermostat for 1-3 seconds after the blower motor BLWM is operating.
The furnace control CPU will shift the continuous-blower airflow from the factory setting to the next highest CF selection airflow as shown in Fig. 56. Momentarily turning off the FAN switch again at the thermostat will shift the continuous-blower airflow up one more increment. If you repeat this procedure enough you will eventually shift the continuous blower airflow to the lowest CF selection as shown in Fig. 56. The selection can be changed as many times as desired and is stored in the memory to be automatically used following a power interruption.
Heat Pump
See Fig. 34 and 35 for thermostat connections. When installed with a heat pump, the furnace control automatically changes the timing sequence to avoid long blower off times during demand defrost cycles. Whenever W/W1 is energized along with Y1 or Y/Y2, the furnace control CPU will transition to or bring on the blower motor BLWM at cooling airflow, minimum-heat airflow, or the mid-range airflow, whichever is lowest. The blower motor BLWM will remain on until the main burners ignite then shut OFF and remain OFF for 25 seconds before coming back on at modulating heat airflow. When the W/W1 input signal disappears, the furnace control begins a normal inducer post-purge period while changing the blower airflow. If Y/Y2 input is still energized the furnace control CPU will transition the blower motor BLWM airflow to cooling airflow. If Y/Y2 input signal disappears and the Y1 input is still energized the furnace control CPU will transition the blower motor BLWM to low-cooling airflow. If both the Y1 and Y/Y2 signals disappear at the same time, the blower motor BLWM will remain on at minimum-heat airflow for the selected blower-OFF delay period. At the end of the blower-OFF delay, the blower motor BLWM will shut OFF unless G is still energized, in which case the blower motor BLWM will operate at continuous blower airflow.
Component Self Test
Refer to page 80 for instructions.
59MN7A
95
Page 96
59MN7A
338307-201 Rev. F
A11595
Fig. 65 -- Wiring Diagram
96
Page 97
PARTS REPLACEMENT INFORMATION GUIDE
Casing Group
Blower door Bottom plate Control door Door knob assembly Top filler plate
Electrical Group
3--Amp fuse Circuit board Control box Door switch Junction box Limit switch(es) Transformer
Blower Group
Blower housing Blower motor Blower wheel Capacitor (when used) Capacitor strap (when used) Cut--off plate Power choke (where used)
Filter Group
Filter(s) Media Cabinet (when used)
Gas Control Group
Burner Flame sensor Gas valve Hot surface igniter Manifold Orifice
Heat Exchanger Group
Containment plate Coupling Box Heat exchanger assembly Primary HX cell panel Secondary HX assembly Tubing gaskets
Inducer Group
Collector box Condensate trap
Condensate trap elbow Gaskets Inducer Inducer assembly Inducer motor capacitor (when used) Inducer motor module (when used) Pressure switch(es)
59MN7A
TO OBTAIN INFORMATION ON PARTS: Consult your installing dealer or classified section of your local telephone directory under “Heating Equipment” or “Air Conditioning Contractors and Systems” headings for dealer listing by brand name or contact:
CARRIER CORPORATION
Consumer Relations Department
P.O. Box 4808
Syracuse, New York 13221
1--800--CARRIER
Have available the model number, series number, and serial number located on the unit rating plate to ensure correct replacement part.
Model Nomenclature
MODEL
59MN7A 120 V 24 -- -- -- -- 22
FIRE, EXPLOSION, ELECTRICAL SHOCK AND CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in dangerous operation, personal injury, death or property damage. Improper installation, adjustment, alteration, service, or maintenance can cause personal injury, property damage, or death. Consult a
qualified installer, service agency, or your local gas supplier for information or assistance. The qualified installer or service agency must use only factory--authorized replacement parts, kits, or accessories when modifying this product.
HEATING
SIZE
MOTOR WIDTH V OLTAGE MINOR SERIES
WARNING
!
COOLING AIRFLOW
(CFM)
97
Page 98
59MN7A
Copyright 2012 Carrier Corp. D 7310 W. Morris St. D Indianapolis, IN 46231 Edition Date: 06/12
Manufacturer reserves the r ight to change, at any time, specifications and designs without notice and without obligations.
Catalog No:59MN7A --- 05SI
Replaces: 59MN7A ---04SI
98