Carrier 58ZAV User Manual

5 (3)
WeatherMaker 8000™
Downflow/Horizontal Induced-Combustion Furnaces
Visit www.carrier.com
Installation, Start-Up, and Operating Instructions
Sizes 050—135, Series 140
NOTE: Read the entire instruction manual before starting the
installation. This symbol indicates a change since the last issue. Index Page
SAFETY CONSIDERATIONS.....................................................1
ELECTROSTATIC DISCHARGE (ESD) PRECAUTIONS
PROCEDURE...........................................................................2
INTRODUCTION.......................................................................3-4
Dimensional Drawing...............................................................2
Clearances From Combustible Materials.................................3
General......................................................................................4
Location Relative to Cooling Equipment ................................4
Hazardous Locations.................................................................4
AIR FOR COMBUSTION AND VENTILATION...................4-5
Unconfined Space..................................................................4-5
Confined Space.........................................................................5
AIR DUCTS................................................................................5-6
General Requirements...............................................................5
Ductwork Acoustical Treatment...............................................5
Supply-Air Connections........................................................5-6
Return-Air Connections............................................................6
DOWNFLOW INSTALLATION..................................................6
HORIZONTAL ATTIC INSTALLATION...................................7
Construct a Working Platform .................................................7
Install Furnace...........................................................................7
HORIZONTAL CRAWLSPACE INSTALLATION....................7
FILTER ARRANGEMENT...........................................................8
GAS PIPING.............................................................................8-10
ELECTRICAL CONNECTIONS................................................10
115-v Wiring...........................................................................10
24-v Wiring.............................................................................11
Accessories..............................................................................11
START-UP, ADJUSTMENT, AND SAFETY CHECK.......11-20
General...............................................................................11-13
Sequence Of Operation...........................................................13
Heating Mode..........................................................................13
Cooling Mode .........................................................................13
Continuous Blower Mode.......................................................13
Heat Pump Mode....................................................................13
Start-up Procedures.................................................................13
Adjustments .......................................................................15-20
Set Gas Input Rate..................................................................15
Set Temperature Rise............................................................ 18
Set Thermostat Heat Anticipator............................................19
Check Safety Controls............................................................20
Checklist..................................................................................20
®
REGISTERED QUALITY SYSTEM
SAFETY CONSIDERATIONS
Installing and servicing heating equipment can be hazardous due to gas and electrical components. Only trained and qualified person­nel should install, repair, or service heating equipment.
Untrained personnel can perform basic maintenance functions such as cleaning and replacing air filters. All other operations must be performed by trained service personnel. When working on heating equipment, observe precautions in the literature, on tags, and on labels attached to or shipped with the unit and other safety precautions that may apply.
In the United States, follow all safety codes including the National
Fuel Gas Code (NFGC) NFPA 54-1996/ANSI Z223.1-1996 and the Installation Standards, Warm Air Heating and Air Condition­ing Systems (NFPA 90B) ANSI/NFPA 90B.
In Canada, refer to the CAN/CGA-B149.1- and .2-M95 National
Standard of Canada, Natural Gas and Propane Installation Codes (NSCNGPIC).
Wear safety glasses and work gloves. Have fire extinguisher available during start-up and adjustment procedures and service calls.
Recognize safety information. This is the safety-alert symbol When you see this symbol on the furnace and in instructions or manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, CAUTION,
and NOTE. These words are used with the safety-alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies a hazard which could result in personal injury or death. CAUTION is used to identify unsafe practices which would result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
These instructions cover minimum requirements and conform to existing national standards and safety codes. In some instances, these instructions exceed certain local codes and ordinances, especially those that may not have kept up with changing residen­tial construction practices. We require these instructions as a minimum for a safe installation.
ama
58ZAV
CANADIAN GAS ASSOCIATION
APPROVED
R
.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4 Tab 6a 8a
PC 101 Catalog No. 535-729 Printed in U.S.A. Form 58ZAV-10SI Pg 1 8-99 Replaces: 58ZAV-9SI
13
⁄16†
39 7⁄8†
11
⁄16†
28 1⁄2†
20
INLET
7
⁄8† DIA
ACCESSORY
3
1
⁄4† DIA HOLE
GAS ENTRY
OUTLET
19
NOTE:
ADDITIONAL LOCA TED IN THE TOP PLA TE AND BOTTOM PLATE
VENT CONNECTION
13
⁄16†
9 1⁄8†
10 1⁄4†
1 1⁄16† 2 1⁄8† 8 1⁄4†
11
⁄16†
7
⁄8† DIA K.O.’s ARE
D
E
A
AIRFLOW
1
⁄2† DIA
2
4 3⁄16†
2 15⁄16†
16 1⁄16†
13 5 ⁄16†
10 1⁄4†
11
⁄16†
DIMPLES TO DRILL HOLES FOR HANGER BOLTS (4 PLACES) IN HORIZONTAL POSITION
THERMOSTAT WIRE ENTRY
7
⁄8† DIA
ACCESSORY
7
⁄8† DIA HOLE
POWER ENTRY
1 1⁄2† DIA R.H. GAS ENTRY
7
⁄8† DIA
ACCESSORY
1 1⁄16†
2 1⁄8†
TYP
1
5
⁄8† TYP
NOTE:
Minimum return-air openings at furnace, based on metal duct. If flex duct is used, see flex duct manufacturer's recommendations for equivalent diameters. a. For 800 CFM–16-in. round or 141⁄2 x 12-in. rectangle. b. For 1200 CFM–20-in. round or 141⁄2 x 191⁄2-in. rectangle. c. For 1600 CFM–22-in. round or 141⁄2 x 231⁄4-in. rectangle. d. For airflow requirements above 1800 CFM, must use entire return air opening.
Fig. 1—Dimensional Drawing
Table 1—Dimensions (In.)
UNIT SIZE A D E VENT CONN SHIP. WT (LB)
050-08 14-3/16 12-9/16 12-11/16 4 124 050-12 14-3/16 12-9/16 12-11/16 4 128 070-08 14-3/16 12-9/16 12-11/16 4 129 070-12 14-3/16 12-9/16 12-11/16 4 137 096-12 17-1/2 15-7/8 16 4 146 096-16 17-1/2 15-7/8 16 4 151 115-16 17-1/2 15-7/8 16 4 159 115-20 21 19-3/8 19-1/2 4 174 115-22 21 19-3/8 19-1/2 4 176 135-20 24-1/2 22-7/8 23 5 193
ELECTROSTATIC DISCHARGE (ESD) PRECAUTIONS
PROCEDURE
3. After touching the chassis you may proceed to service the control or connecting wires as long as you do nothing that recharges your body with static electricity (for example; DO NOT move or shuffle your feet, DO NOT touch ungrounded
Electrostatic discharge can affect electronic components. Take precautions during furnace installation and servicing to protect the furnace electronic control. Precautions will pre­vent electrostatic discharges from personnel and hand tools which are held during the procedure. These precautions will help to avoid exposing the control to electrostatic discharge by putting the furnace, the control, and the person at the same electrostatic potential.
1. Disconnect all power to the furnace. DO NOT TOUCH THE
CONTROL OR ANY WIRE CONNECTED TO THE CON­TROL PRIOR TO DISCHARGING YOUR BODY’S ELEC­TROSTATIC CHARGE TO GROUND.
2. Firmly touch a clean, unpainted, metal surface of the furnace chassis which is close to the control. Tools held in a person’s hand during grounding will be satisfactorily discharged.
objects, etc.).
4. If you touch ungrounded objects (recharge your body with static electricity), firmly touch furnace again before touching control or wires.
5. Use this procedure for installed and uninstalled (ungrounded) furnaces.
6. Before removing a new control from its container, discharge your body’s electrostatic charge to ground to protect the control from damage. If the control is to be installed in a furnace, follow items 1 through 5 before bringing the control or yourself into contact with the furnace. Put all used AND new controls into containers before touching ungrounded objects.
7. An ESD service kit (available from commercial sources) may also be used to prevent ESD damage.
2
A99288
MINIMUM INCHES CLEARANCE TO COMBUSTIBLE CONSTRUCTION
This fo rced air furnace is equipped for use with natura l
gas at altitudes0-10,000ft (0-3,050m).
An accessory kit, supplied by the manu facturer,shall be used to convert to propane gas use or may be required for somenatura l gas applicatio ns.
This furnace is for indoor in stallatio n in a building constructedonsite.
This furnace may be installed on combustible flooring in alcove or closet at minimum clea rance from combustible material.
This furnace may be used with a Type B-1 Vent and may be vented in commonwithother gas-fired appliances.
For installation on non-combustible floorsonly.
For installation on combustible flooring only when installedon special base, Part No. KGASB0201ALL, Coil Assembly, Part No. CD5 or CK5, or Coil Casing, Part No. KCAKC.
For furnaces wider than14.25 inches (362mm) may
#
be 0 inches.
18 inches front clearance requiredfor alcove.
Ø
Indicates supply or return sides whenfurnace isin
*
the horizontal position. Line contact only permissible betweenlines formed by intersectionsof the Top and two Sides of the furnace jacket, and building joists, studs or framing.
For single wall vent type 6 inches.
##
For Type B-1 vent type 3 inches.
Clearance to Back 0 inches in downflowand horizontal (attic/alcove& crawlspace) positionsand 3 inches in horizontal closet positions.
Fig. 2—Clearances to Combustibles
This f ur nace is approved f or DOWNFLOWand HORIZONTAL installations.
Clearance arrows do not change with furnace orientation.
0"
B
A
C
K
E
D
I
S
1" #
*
Clearance in inches
1"
TOP / PLENUM
E
C
A
N
R
U
F
1
T
N
O
R
F
F
R
BOTTOM
#
"
S
O
N
T
##
Ø
1"
#
E
*
D
I
S
E
R
V
I
C
E
30"
Vent Clearance to combustibles:
For Single Wall vents 6 i nches. For Type B-1 vent type 1 inch.
322286-101REV.F (LIT)
MIN
A99262
INTRODUCTION
The model 58ZAV Series 140 Furnaces are available in sizes 46,000 through 135,000 Btuh input capacities.
The design of the downflow/horizontal gas-fired furnace is A.G.A./C.G.A. certified for natural and propane gases and for installation on noncombustible flooring. The furnace is factory­shipped for use with natural gas. A factory accessory gas conver­sion kit, as listed on the furnace rating plate is required to convert furnace for use with propane gas.
These furnaces SHALL NOT be installed directly on carpeting, tile, or any other combustible material other than wood flooring. In downflow installations, a factory accessory floor base, as listed on the furnace rating plate MUST be used when installed on com­bustible materials and wood flooring. A factory base is not required when this furnace is installed on manufacturer’s Coil Assembly Part No. CD5 or CK5, or when Coil Box Part No. KCAKC is used. This furnace is for installation in alcoves, attics, crawlspaces, basements, closets, or utility rooms. The design of this furnace line is not A.G.A./C.G.A. certified for installation in mobile homes, recreation vehicles, or outdoors.
Before installing the furnace in the United States, refer to the current edition of the NFGC and the NFPA 90B. For further information, the NFGC and NFPA 90B are available from Na­tional Fire Protection Association Inc., Batterymarch Park, Quincy, MA 02269; or the American Gas Association, 400 N. Capitol St., NW, Washington DC 20001.
Before installing the furnace in Canada, refer to the current edition
of the NSCNGPIC. For a copy of the NSCNGPIC, contact
Standard Sales, CSA International, 178 Rexdale Boulevard, Eto­bicoke (Toronto), Ontario, M9W 1R3 Canada.
Installation must comply with regulations of serving gas supplier and local building, heating, plumbing or other codes in effect in the area in which installation is made. In absence of local building codes, installation must conform with NFGC in the United States and the NSCNGPIC and all authorities having jurisdiction in Canada.
These instructions cover minimum requirements for a safe instal­lation and conform to existing national standards and safety codes. In some instances, these instructions exceed certain local codes and ordinances, especially those that may not have kept pace with changing residential construction practices. We require these instructions as a minimum for a safe installation.
Application of this furnace should be indoors with special attention given to vent sizing and material, gas input rate, air temperature rise, and unit sizing. Improper installation or misapplication of the furnace can require excessive servicing or cause premature component failure.
NOTE: These furnaces are designed for a minimum continuous return-air temperature of 60°F or intermittent operation down to 55°F such as when used with a night setback thermostat. Return-air temperature must not exceed a maximum of 85°F. Failure to follow these return-air temperature limits may affect reliability of heat exchangers, motors, and controls.
3
FRONT
°F °F
RETURN AIR
MAX 85°F MIN 55°F
A93042
Improper installation, adjustment, alteration, service, mainte­nance, or use can cause carbon monoxide poisoning, explo­sion, fire, electrical shock, or other conditions which may cause personal injury, loss of life, or property damage. Consult a qualified installer, service agency, local gas sup­plier, or your distributor or branch for information or assis­tance. The qualified installer or agency must use only factory-authorized and listed kits or accessories when modi­fying this product. Failure to follow this warning could result in electrical shock, fire, personal injury, or death.
Locate the furnace as close to the chimney/vent and as near the center of the air distribution system as possible. The furnace should be installed as level as possible.
Provide ample space for servicing and cleaning. Always comply with the minimum fire protection clearances shown on the unit rating plate. This furnace shall not be installed directly on carpeting, tile, or any combustible material other than wood flooring. The furnace may be installed on combustible flooring when installed with the accessory downflow subbase, which is available from your distributor or branch when required.
LOCATION RELATIVE TO COOLING EQUIPMENT — The cooling coil must be installed parallel with or on the downstream side of the furnace to avoid condensation in the heat exchangers. When installed parallel with a furnace, dampers or other means used to control the flow of air must prevent chilled air from entering the unit. If the dampers are manually operated, they must be equipped with means to prevent operation of either unit unless the damper is in the full-heat or full-cool position.
HAZARDOUS LOCATIONS
For accessory installation details, refer to the applicable installa­tion literature.
NOTE: Remove all shipping brackets and materials before oper­ating the furnace.
Step 1—Location
GENERAL
Do not install furnace in a corrosive or contaminated atmo­sphere. Make sure all combustion and circulating air require­ments are followed, in addition to all local codes and ordinances. Do not use this furnace during construction when adhesives, sealers, and/or new carpets are being installed. If the furnace is required during construction, use clean outside air for combustion and ventilation. Compounds of chlorine and fluorine when burned with combustion air form acids which cause corrosion of the heat exchangers and metal vent system. Some of these compounds are found in paneling and dry wall adhesives, paints, thinners, masonry cleaning materials, and many other solvents commonly used in the construction process. Excessive exposure to contaminated combustion air will result in safety and performance related problems.
18-IN. MINIMUM
TO BURNERS
A93044
When furnace is installed in a residential garage, it must be installed so that burners and ignition sources are located a minimum of 18 in. above floor. The furnace must be located or protected to avoid physical damage by vehicles. When furnace is installed in a public garage, airplane hangar, or other building having a hazardous atmosphere, unit must be installed in accordance with requirements of National Fire Protection Association, Inc.
Step 2—Air For Combustion and Ventilation
Provisions for adequate combustion and ventilation air must be provided in accordance with Section 5.3 of the NFGC, Air for Combustion and Ventilation, or applicable provisions of the local building codes.
Canadian installations must be installed in accordance with NSC­NGPIC and all authorities having jurisdiction.
Do not install the furnace on its back; safety control operation will be adversely affected. Failure to follow this warning could result in fire, personal injury, or death.
This furnace must be installed so the electrical components are protected from water.
Air for combustion must not be contaminated by halogen compounds, which include fluoride, chloride, bromide, and iodide. These elements are found in aerosol sprays, deter­gents, bleaches, cleaning solvents, salts, air fresheners, and other household products.
4
The operation of exhaust fans, kitchen ventilation fans, clothes dryers, or fireplaces could create a NEGATIVE PRESSURE CONDITION at the furnace. Make-up air MUST be provided for the ventilation devices, in addition to that required by the furnace.
The requirements for combustion and ventilation air depend upon whether the furnace is located in an unconfined or confined space.
If the unconfined space is of unusually tight construction, air for For Example:
58ZAV FURNACE
INPUT BTUH
46,000 307 69,000 460
92,000 613 115,000 767 135,000 920
MINIMUM SQ FT
WITH
7-1/2 FT CEILING
combustion and ventilation MUST come from either the outdoors or spaces freely communicating with the outdoors. Combustion and ventilation openings must be sized the same as for a confined space as defined below. Return air must not be taken from the room unless an equal or greater amount of air is supplied to the room.
CONFINED SPACE A confined space is defined as a space whose volume is less than
NOTE: In determining free area of an opening, the blocking effect of louvers, grilles, and screens must be considered. If free area of louver or grille design is unknown, assume that wood louvers have a 20 percent free area and metal louvers or grilles have a 60 percent free area. Screens, when used, must not be smaller than 1/4-in. mesh. Louvers and grilles must be constructed so they cannot be closed.
1. All air from inside the structure requires 2 openings (for structures not usually tight):
a. Each opening MUST have at least 1 sq in. of free area per
1000 Btuh of total input for all equipment within the confined space, but not less than 100 sq in. per opening. (See Fig. 3 and Table 2.) The minimum dimension of air openings shall not be less than 3 in.
b. If building is constructed unusually tight, a permanent
opening directly communicating with the outdoors shall be provided. See item 2 below.
c. If furnace is installed on a raised platform to provide a
return-air plenum, and return air is taken directly from hallway or space adjacent to furnace, all air for combustion must come from outdoors.
2. Air from outside the structure requires 1 of the following methods:
a. If combustion air is taken from outdoors through 2 vertical
ducts, the openings and ducts MUST have at least 1 sq in. of free area per 4000 Btuh of total input for all equipment within the confined space. (See Fig. 4 and Table 2.)
b. If combustion air is taken from outdoors through 2 hori-
zontal ducts, the openings and ducts MUST have at least 1 sq in. of free area per 2000 Btuh of total input for all equipment within the confined space. (See Fig. 4 and Table
2.)
c. If combustion air is taken from outdoors through a single
opening or duct (horizontal or vertical) commencing within 12 in. of the top of the confined space, opening and duct MUST have at least 1 sq in. of free area per 3000 Btuh of the total input for all equipment within the confined space and not less than the sum of the areas of all vent connectors in the confined space. (See Fig. 4 and Table 2.) Equipment clearances to the structure shall be at least 1 in. from the sides and back and 6 in. from the front of the appliances.
When ducts are used, they must be of the same cross-sectional area as the free area of the openings to which they connect. The minimum dimension of ducts must not be less than 3 in. (See Fig.
4.)
AIR DUCTS
Step 1—General Requirements
The duct system should be designed and sized according to accepted national standards such as those published by: Air Conditioning Contractors Association (ACCA), Sheet Metal and Air Conditioning Contractors National Association (SMACNA) or American Society of Heating, Refrigerating and Air Conditioning Engineers (ASHRAE). Or consult factory The Air Systems Design Guidelines reference tables available from your local distributor. The duct system should be sized to handle the required system design CFM at the design static pressure.
When a furnace is installed so that the supply ducts carry air to areas outside the space containing the furnace, the return air must also be handled by a duct(s) sealed to the furnace casing and terminating outside the space containing the furnace.
Secure ductwork with proper fasteners for type of ductwork used. Seal supply- and return-duct connections to furnace with code approved tape or duct sealer.
Flexible connections should be used between ductwork and furnace to prevent transmission of vibration. Ductwork passing through unconditioned space should be insulated to enhance system performance. When air conditioning is used, a vapor barrier is recommended.
Maintain a 1-in. clearance from combustible materials to supply air ductwork for a distance of 36 in. horizontally from the furnace. See NFPA 90B or local code for further requirements.
Step 2—Ductwork acoustical treatment
Metal duct systems that do not have a 90 degree elbow and 10 ft of main duct to the first branch take-off may require internal acoustical lining. As an alternative, fibrous ductwork may be used if constructed and installed in accordance with the latest edition of SMACNA construction standard on fibrous glass ducts. Both acoustical lining and fibrous ductwork shall comply with NFPA 90B as tested by UL Standard 181 for Class 1 Rigid air ducts.
5
VENT THROUGH ROOF (CATEGORY I)
DUCTS TO
OUTDOORS
1 SQ IN. PER 4000 BTUH
*
RETURN
AIR
INTERIOR
HEATED
SPACE
SUPPLY AIR
* Minimum opening size is 100 sq in. with minimum dimensions of 3 in.
Minimum of 3 in. when type B-1 vent is used.
12 MAX
1 SQ IN. PER 1000 BTUH* IN DOOR OR WALL
UNCONFINED SPACE
6 MIN (FRONT)
1 SQ IN. PER 1000 BTUH* IN DOOR OR WALL
12 MAX
A93387
Fig. 3—Confined Space: Air for Combustion and
Ventilation from an Unconfined Indoor Space
12 MAX
1 SQ IN. PER 2000 BTUH
*
DUCTS
TO
OUTSIDE
1 SQ IN. PER 2000 BTUH
*
12 MAX
SUPPLY AIR
Minimum dimensions of 3 in.
*
Use any of the following
NOTE:
combinations of openings: A & B C & D D & E F & G
RETURN
A
B
AIR
D
VENT THROUGH ROOF (CATEGORY I)
CONFINED
C
DUCT
TO
OUTDOORS
F
SPACE
G
E
12 MAX
12″
MAX
1 SQ IN. PER 4000 BTUH
OUTDOORS 1 SQ IN.
PER 4000 BTUH
12″
MAX
1 SQ IN. PER 4000 BTUH
*
*
A93388
Fig. 4—Confined Space: Air for Combustion and
Ventilation from Outdoors
Table 2—Minimum Free Area Of Combustion Air Opening
AIR FROM UNCON-
58ZAV
FURNACE
INPUT
(BTUH)
46,000 100 11.50 4 23.0 6 15.33 5 69,000 100 17.25 5 34.5 7 23.00 6
92,000 100 23.00 6 46.0 8 30.67 7 115,000 115 28.75 7 57.5 9 38.33 7 135,000 135 33.75 7 67.5 10 45.00 8
* Free area shall be equal to or greater than the sum of the areas of all vent connectors in the confined space. Opening area must be increased if other gas appliances in the space require combustion air.
FINED INDOOR
SPACE
Free Area
of Opening
(Sq In.)
Step 3—Supply Air Connections
DOWNFLOW FURNACES Connect supply-air duct to supply-air opening on furnace. The
supply-air duct attachment must ONLY be connected to furnace supply/outlet or air conditioning coil casing (when used), when installed on non-combustible material. When installed on combus­tible material, supply-air duct attachment must ONLY be con­nected to an accessory subbase or factory approved air condition­ing coil casing. DO NOT cut main furnace casing to attach supply side air duct, humidifier, or other accessories. All accessories MUST be connected external to furnace main casing.
HORIZONTAL FURNACES Connect supply-air duct to supply air opening on furnace. The
supply-air duct attachment must ONLY be connected to furnace
OUTDOOR AIR THROUGH
VERTICAL DUCTS
Free Area of
Opening and Duct
(Sq In.)
Round
Pipe
(In. Dia)
OUTDOOR AIR THROUGH
HORIZONTAL DUCTS
Free Area of
Opening and Duct
(Sq In.)
Round
Pipe
(In. Dia)
OUTDOOR AIR THROUGH
SINGLE DUCT
Free Area of
Opening and Duct
(Sq In.)
Round
Pipe
(In. Dia)
supply/outlet or air conditioning coil casing (when used). DO NOT cut main furnace casing to attach supply side air duct, humidifier, or other accessories. All accessories MUST be connected external to furnace main casing.
Step 4—Return Air Connections
Do not install the furnace on its back or sides. Safety control operation will be adversely affected. Never connect return-air ducts to the back of the furnace. A failure to follow this warning can cause a fire, personal injury, or death.
The return-air duct must be connected to return-air opening provided as shown in Fig. 1. DO NOT cut into casing sides or back
6
Loading...
+ 14 hidden pages