Carrier 58UVB series Installation, Start-up, And Operating Instructions Manual

Page 1
58UVB D i r e c t --- Ve n t U p f l o w Var iable---Capacity Condensing Gas Furnace For Sizes 060--- 120, Series 100
Installation, Start---Up, and Operating Instructions
NOTE: Read the entire instruction manual before starting the installation.
PAGE
SAFETY CONSIDERATIONS 2........................
DIMENSIONAL DRAWING 3..........................
Clearances to Combustibles 4........................
CODES AND STANDARDS 5..........................
ELECTROSTATIC DISCHARGE (ESD) PRECAUTIONS 6..
INTRODUCTION 6..................................
APPLICATIONS 6...................................
General 6........................................
Applications 6.....................................
LOCATION 8.......................................
General 8........................................
Low--Heat Only Installation 10........................
Location Relative to Cooling Equipment 10..............
Hazardous Locations 10.............................
INSTALLATION 10..................................
Leveling Legs (If Desired) 10.........................
Air Ducts 11.......................................
Filter Arrangement 11...............................
Bottom Closure Panel 12.............................
Gas Piping 12.....................................
Electrical Connections 14............................
Removal of Existing Furnaces from Common Vent Systems 17
Combustion-- air and Vent Pipe Systems 18...............
Condensate Drain 32................................
START--UP, ADJUSTMENTS, AND SAFETY CHECK 33...
General 33........................................
AIRFLOW
UPFLOW
A06340
Fig. 1 --- Furnace Orientation
ama
ISO 9001:2000
As an ENERGY STAR® Partner, Carrier Co rporation has deter­mined that this pro duct meets the ENERGY STAR® guidelines for energy efficiency.
Select Setup Switch Positions 33.......................
Prime Condensate Trap with Water 34...................
Purge Gas Lines 35.................................
Sequence of Operation 35............................
Adjustments 43....................................
Check Safety Controls 48............................
CHECKLIST 49.....................................
CERTIFIED
REGISTERED
Page 2
SAFETY CONSIDERATIONS
!
CAUTION
FURNACE RELIABILITY HAZARD
Improper installation or misapplication of furnace may require excessive servicing or cause premature component failure.
Application of this furnace should be indoors with special attention given to vent sizing and material combustion air requirements, gas input rate, air temperature rise, unit leveling, and unit sizing.
!
FIRE, EXPLOSION, ELECTRICAL SHOCK AND CARBON MONOXIDE POISONING HAZARD
58UVB
Failure to follow this warning could result in electrical shock, fire, personal injury, or death.
Improper installation, adjustment, alteration, service, maintenance, or use can cause carbon monoxide poisoning, explosion, tire, electrical shock, or other conditions which may cause personal injury or property damage. Consult a qualified installer, service agency, local gas supplier, or your distributor or branch for information or assistance. The qualified installer or agency must use only factory--authorized and listed kits or accessories when modifying this product.
Installing and servicing heating equipment can be hazardous due to gas and electrical components. Only trained and qualified
personnel should install, repair, or service heating equipment.
Untrained personnel can perform basic maintenance functions such as cleaning and replacing air filters. All other operations must be performed by trained service personnel. When working on heating equipment, observe precautions in literature, on tags, and on labels attached to or shipped with unit and other safety precautions that may apply.
These instructions cover the minimum requirements and conform to existing national standards and safety codes. In some instances, these instructions exceed certain local codes and ordinances, especially those that may not have kept up with changing residential construction practices. We require these instructions as a minimum for a safe installation.
Wear safety glasses and work gloves. Have a fire extinguisher available during start--up and adjustment procedures and service calls.
Recognize safety information. This is the safety--alert symbol
. When you see this symbol on the furnace and in instructions or manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, and CAUTION. These words are used with the safety--alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies a hazard which could result in personal injury or death. CAUTION is used to identify unsafe practices which may result in minor personal
WARNING
injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
!
CAUTION
CUT HAZARD
Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate protective clothing and gloves when handling parts.
The 58UVB Condensing Gas--Fired Furnaces are CSA (formerly AGA and CGA) design--certified for natural and propane gases (see furnace rating plate) and for installation in alcoves, attics, basements, closets, utility rooms, crawlspaces, and garages. The furnace is factory--shipped for use with natural gas. A CSA listed gas conversion kit is required to convert furnace for use with propane gas.
See Fig. 3 for required clearances to combustibles. Maintain a 1--in. clearance from combustible materials to supply
air ductwork for a distance of 36 inches horizontally from the furnace. See NFPA 90B or local code for further requirements.
These furnaces SHALL NOT be installed directly on carpeting, tile, or any other combustible material other than wood flooring. These furnaces are suitable for installation in a structure built on site or a manufactured building completed at final site. The design of this furnace line is NOT CSA design--certified for installation in recreation vehicles, manufactured (mobile) homes or outdoors.
This furnace is designed for continuous return--air minimum temperature of 60_F db or intermittent operation down to 55_F db such as when used with a night setback thermostat. Return--air temperature must not exceed 80_F db. Failure to follow these return air limits may affect reliability of heat exchangers, motors and controls. (See Fig. 4.)
These furnaces are shipped for UPFLOW applications ONLY. See details in Applications section.
Install this furnace only in a location and position as specified in LOCATION and INSTALLATION sections of these instructions.
Combustion products must be discharged outdoors. Connect this furnace to an approved vent system only, as specified in the Combustion Air and Vent piping sections of these instructions.
Never test for gas leaks with an open flame. Use a commercially available soap solution made specifically for detection of leaks to check all connections as specified in the GAS PIPING section of these instructions.
Always install the furnace to operate within the furnace’s intended rise range with a duct system which has an external static pressure within the allowable range as specified in the SET TEMPERA TURE RISE section of these instructions.
When a furnace is installed so that supply ducts carry air circulated by the furnace to areas outside the space containing the furnace, the return air shall also be handled by ducts sealed to the furnace casing and terminating outside the space containing the furnace.
2
Page 3
14 1⁄2"
TYP
1
26 15⁄16"
26 1⁄4"
1
⁄2"
24
5
22
⁄16"
-IN. COMBUSTION-
2 AIR CONN
1
⁄2-IN. DIA
GAS CONN
2
-IN. VENT CONN
⁄2-IN. DIA THERMOSTAT
ENTRY
22 11⁄16"
SIDE INLET
7
⁄8-IN. DIA
POWER CONN
7
⁄8-IN. DIA
ACCESSORY POWER ENTRY
CONDENSATE DRAIN TRAP LOCATION (ALTERNATE UPFLOW)
9 7⁄16"
TYP
17 5⁄16"
1
⁄2"
28
AIRFLOW
13
⁄16"
1
33
⁄4"
TYP
5
⁄8"
32
TYP
13
⁄16"
30
11
29
⁄16"
TYP
5
27
⁄8"
9
27
⁄16"
TYP
1
24
⁄2"
A
D
OUTLET
13
⁄16"
CONDENSATE
ALTERNATE 1/2-IN. DIA GAS CONN
DRAIN
30 1⁄2"
18 1⁄4"
TYP
9
⁄16"
26 15⁄16"
26 1⁄4"
5
⁄16"
22
19"
OUTLET
2-IN. COMBUSTION­AIR CONN
1
⁄2-IN. DIA
GAS CONN
7
⁄8-IN. DIA
POWER CONN
1
⁄2-IN. DIA
THERMOSTAT ENTRY
2-IN. VENT CONN
22 11⁄16"
SIDE INLET
13
⁄16"
5
⁄8"
5
⁄16"
7
39
⁄8"
1"
11⁄4"
1" E
23 1⁄4" TYP
SIDE INLET
26 15⁄16" TYP
CONDENSATE DRAIN LOCATION (UPFLOW)
NOTES: 1. Minimum return-air openings at furnace, based on metal duct. If flex duct is used,
see flex duct manufacturer’s recommendations for equivalent diameters.
2. Minimum return-air opening at furnace: a. For 800 CFM–16-in. round or 14 b. For 1200 CFM–20-in. round or 141/2 c. For 1600 CFM–22-in. round or 14 d. For airflow requirements above 1800 CFM, see Air Delivery table in Product Data
literature for specific use of single side inlets. The use of both side inlets, a combination of 1 side and the bottom, or the bottom only will ensure adequate return air openings for airflow requirements above 1800 CFM.
11
⁄16"
1
/2
x 12-in. rectangle.
1
/2
DIMENSIONS (IN.)
UNIT SIZE A D E
060 --- 14 17--- 1/2 15--- 7/8 16
080 --- 14 21 19---3/8 19---1/2
080 --- 20 21 19---3/8 19---1/2
100 --- 20 21 19---3/8 19---1/2
120 --- 20 24--- 1/2 22--- 7/8 23
Fig. 2 --- Dimensional Drawing
A gas--fired furnace for installation in a residential garage must be installed as specified in the Hazardous Locations section of these instructions and Fig. 5.
The furnace may be used for construction heat provided that the furnace installation and operation complies with the first CAUTION in the LOCATION section of these instructions.
This gas furnace may be used for construction heat provided that:
S The furnace is permanently installed with all electrical
wiring, piping, air filters, venting and ducting installed according to these installation instructions. A return air duct is provided, sealed to the furnace casing, and ter­minated outside the space containing the furnace. This prevents a negative pressure condition as created by the circulating air blower, causing a flame rollout and/or drawing combustion products into the structure.
S The furnace is controlled by a thermostat. It may not be
“hot wired” to provide heat continuously to the struc­ture without thermostatic control.
S Clean outside air is provided for combustion. This is to
minimize the corrosive effects of adhesives, sealers and other construction materials. It also prevents the en­trainment of drywall dust into combustion air, which can cause fouling and plugging of furnace components.
INLET
x 191/2 x 231/4
-in. rectangle.
-in. rectangle.
11
⁄16"
CONDENSATE
DRAIN LOCATION
(UPFLOW)
22 1⁄4" TYP
24 3⁄16"
BOTTOM INLET
S The temperature of the return air to the furnace is
maintained between 55_F(13_C) and 80_F(27_C), with no evening setback or shutdown. The use of the furnace while the structure is under construction is deemed to be intermittent operation per our installation instructions.
S The air temperature rise is within the rated rise range on
the furnace rating plate, and the firing rate has been set to the nameplate value.
S The filters used to clean the circulating air during the
construction process must be either changed or thoroughly cleaned prior to occupancy.
S The furnace, ductwork and filters are cleaned as
necessary to remove drywall dust and construction debris from all HVAC system components after construction is completed.
S After construction is complete, verify furnace operating
conditions including ignition, input rate, temperature rise and venting, according to the manufacturer’s instructions.
7
⁄16"
11
⁄16"
A06341
58UVB
3
Page 4
58UVB
Fig. 3 --- Clearances to Combustibles
If this furnace is installed with a direct-- vent (combustion air and flue) system, a factory accessory termination kit must be installed. In a direct--vent system, all air for combustion is taken directly from the outside atmosphere and all flue products are discharged to the outside atmosphere. See furnace and factory accessory termination kit instructions for proper installation.
These furnaces are shipped with the following materials to assist in proper furnace installation. These materials are shipped in the main blower compartment.
332713-201 REV. A (LIT. TOP)
A06489
Installer Packet Includes:
Installation, Startup, and Op erating Instructions
Service and Maintenance Instructions
User’s Information Manual
Warranty Certificate
Loose Parts Bag includes: Quantity
Collector Box or Condensate trap extension tube 1
Inducer housing drain tube 1
1/2--- in CPVC street elbow 2
Drain tube coupling 1
Drain tube coupling grommet 1
Gas line grommet 1
Vent pipe grommet 1
Combustion --- air pipe grommet 1
Gas line entry hole filler plug 1
Power entry hole filler plug 2
Condensate trap hole filler plug 3
Vent and combustion---air intake hole filler plug 2
Combustion - -- air pipe perforated disk assembly 1
4
Page 5
0
60
A05004
Fig. 4 --- Return--Air Temperature
18-IN. MINIMUM
TO BURNERS
A93044
Fig. 5 --- Installation in a Garage
The furnace shall be installed so that the electrical components are protected from water.
For accessory installation details, refer to applicable installation literature.
CODES AND STANDARDS
Follow all national and local codes and standards in addition to these instructions. The installation must comply with
regulations of the serving gas supplier, local building, heating, plumbing, and other codes. In absence of local codes, the installation must comply with the national codes listed below and all authorities having jurisdiction in Canada.
In the United States and Canada, follow all codes and standards for the following:
Step 1 —Safety
US: National Fuel Gas Code (NFGC) NFPA
S
54--2002/ANSI Z223.1--2002 and the Installation Standards, Warm Air Heating and Air Conditioning Systems ANSI/NFPA 90B
S CANADA: National Standard of Canada, Natural Gas
and Propane Installation Code (NSCNGPIC) CSA B149.1--05
Step 2 —General Installation
US: NFGC and the NFPA 90B. For copies, contact the
S
National Fire Protection Association Inc., Batterymarch Park, Quincy, MA 02269; or for only the NFGC contact the American Gas Association, 400 N. Capitol, N.W., Washington DC 20001
S CANADA: NSCNGPIC. For a copy, contact Standard
Sales, CSA International, 178 Rexdale Boulevard, Etobicoke (Toronto), Ontario, M9W 1R3, Canada.
Step 3 —Combustion and Ventilation Air
US: Section 9.3 of the NFGC, Air for Combustion and
S
Ventilation
S CANADA: Part 7 of the NSCNGPIC, Venting Systems
and Air Supply for Appliances
Step 4 —Duct Systems
US and CANADA: Air Conditioning Contractors
S
Association (ACCA) Manual D, Sheet Metal and Air Conditioning Contractors National Association (SMACNA), or American Society of Heating, Refrigeration, and Air Conditioning Engineers (ASHRAE) 2001 Fundamentals Handbook Chapter 34.
Step 5 —Acoustical Lining and Fibrous Glass Duct
US and CANADA: current edition of SMACNA,
S
NFPA 90B as tested by UL Standard 181 for Class I Rigid Air Ducts
Step 6 —Gas Piping and Gas Pipe Pressure Testing
US: NFGC; chapters 5, 6, 7, and 12 and national
S
plumbing codes
S CANADA: NSCNGPIC Parts 3, 4, 5, A, B, E, G, and
H
In the state of Massachusetts:
S This product must be installed by a licensed plumber or
gas fitter.
S When flexible connectors are used, the maximum
length shall not exceed 36 inches.
S When lever type gas shutoffs are used they shall be
T--handle type.
S The use of copper tubing for gas piping is not approved
by the state of Massachusetts.
Step 7 —Electrical Connections
US: National Electrical Code (NEC) ANSI/NFPA
S
70--2002
S CANADA: Canadian Electrical Code CSA C22 .1
58UVB
5
Page 6
ELECTROSTATIC DISCHARGE (ESD)
PRECAUTIONS
!
CAUTION
!
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in damage to unit components.
Electrostatic discharge can affect electronic components. Take precautions during furnace installation and servicing to protect the furnace electronic control. Precautions will prevent electrostatic discharges from personnel and hand tools which are held during the procedure. These precautions will help to avoid exposing the control to electrostatic discharge by putting the furnace, the control, and the person at the same electrostatic potential.
1. Disconnect all power to the furnace. Multiple disconnects may be required. DO NOT TOUCH THE CONTROL OR
58UVB
ANY WIRE CONNECTED TO THE CONTROL PRIOR TO DISCHARGING YOUR BODY’S ELECTROSTATIC CHARGE TO GROUND.
2. Firmly touch a clean, unpainted, metal surface of the furnace chassis which is close to the control. T ools held in a person’s hand during grounding will be satisfactorily discharged.
3. After touching the chassis, you may proceed to service the control or connecting wires as long as you do nothing that recharges your body with static electricity (for example; DO NOT move or shuffle your feet, DO NOT touch ungrounded objects, etc.).
4. If you touch ungrounded objects (recharge your body with static electricity), firmly touch furnace again before touching control or wires.
5. Use this procedure for installed and uninstalled (ungrounded) furnaces.
6. Before removing a new control from its container, discharge your body’s electrostatic charge to ground to protect the control from damage. If the control is to be installed in a furnace, follow items 1 through 5 before bringing the control or yourself into contact with the furnace. Put all used AND new controls into containers before touching ungrounded objects.
7. An ESD service kit (available from commercial sources) mayalsobeusedtopreventESDdamage.
INTRODUCTION
The model 58UVB Direct Vent, Upflow, Gas-- Fired, Category IV, condensing furnace is available in model sizes ranging in input capacities of 60,000 to 120,000 Btuh.
APPLICATIONS
Step 1 —General
Some assembly and modifications are required for condensate trap drainage tubes. (See Fig. 6, 7 and 8.) All drain and pressure tubes are connected as shown in Fig. 7 from the factory. See appropriate application instructions for these procedures.
MINOR PROPERTY DAMAGE
Failure to follow this caution may result in minor property damage.
Local codes may require a drain pan under entire furnace and condensate trap when a condensing furnace is used in an attic application or over a finished ceiling.
NOTE: In Canada, installations shall be in accordance with current NSCNGPIC and/or local codes.
Step 2 —Upflow Application Only
An upflow furnace application is where furnace blower is located below combustion and controls section of furnace, and conditioned air is discharged upwards.
CONDENSATE TRAP (FACTORY--SHIPPED LOCA
The condensate trap is factory installed in the blower shelf. A factory--supplied tube is used to extend the condensate trap drain connection to the desired furnace side for field drain attachment. See Condensate Trap Tubing section for drain tube extension details. (See Fig. 6.)
CONDENSATE TRAP TUBING (FACTOR CONFIGURA
NOTE: See Fig. 7 or review label on main furnace door to
confirm location of these tubes.
1. Collector Box Drain, Inducer Housing Drain, Relief Port,
2. Condensate Trap Drain Tube
NOTE: If internal filter or side filter/media cabinet is used, drain tube should be located to opposite side of casing from return duct attachment to assist in filter removal.
TION)
and Pressure Switch Tubes These tubes should be factory attached to condensate trap andpressureswitchreadyforuseininternaltrapapplica­tions. These tubes can be identified by their connection location and also by a color label on each tube. These tubes are identified as follows: collector box drain tube (blue label), inducer housing drain tube (violet label or molded), relief port tube (green label), and pressure switch tube (pink label).
The condensate trap drain connection must be extended for field attachment by doing the following:
a. Determine location of field drain connection. (See Fig.
2or7.)
b. Remove and discard casing drain hole plug button
from desired side.
c. Install drain tube coupling grommet (factory--supplied
in loose parts bag) in selected casing hole.
d. Slide drain tube coupling (factory--supplied in loose
parts bag) through grommet so long end of coupling faces blower.
e. Cement 2 factory--supplied 1/2--in. street CPVC
elbows to rigid drain tube connection on condensate trap. (See Fig. 7.) These elbows must be cemented together and cemented to condensate trap drain connection.
Y--SHIPPED
TION)
6
Page 7
BLOWER SHELF
CONDENSATE TRAP (INSIDE)
FURNACE DOOR
CONDENSATE TRAP
FURNACE
7
4
8
SIDE
ALTERNATE DRAIN TUBE LOCATION
CONDENSATE TRAP
DRAIN TUBE LOCATION
FACTORY-SHIPPED LOCATION
1
2
1
3
4
3
1
4
WIRE TIE GUIDES (WHEN USED)
7
FRONT VIEW SIDE VIEW
Fig. 6 --- Condensate Trap
NOTE: Failure to use CPVC elbows may allow drain to kink,
preventing draining.
f. Connect larger diameter drain tube and clamp
(factory--supplied in loose parts bag) to condensate
trap and clamp securely. g. Route tube to coupling and cut to appropriate length.
h. Attach tube to coupling and clamp securely.
CONDENSATE T RAP(ALTERNATE LOCA
TION)
An alternate location for the condensate trap is the left--hand side of casing. (See Fig. 2 and 8.)
NOTE: If the alternate left--hand side of casing location is used, the factory--connected drain and relief port tubes must be disconnected and modified for attachment. See Condensate Trap Tubing (Alternate Configuration) section for tubing attachment.
To relocate condensate trap to the left-- hand side, perform the following:
1. Remove 3 tubes connected to condensate trap.
2. Remove trap from blower shelf by gently pushing tabs inward and rotating trap.
3. Install casing hole filler cap (factory--supplied in loose parts bag) into blower shelf hole where trap was removed.
FIELD
DRAIN
CONN
1
26
4
1
1
2
SIDE VIEW FRONT VIEW
ALTERNATE LOCATION
1/
OD
4
COLLECTOR BOX TO TRAP RELIEF PORT
1/
OD
2
INDUCER HOUSING DRAIN CONNECTION
5/
OD
8
COLLECTOR BOX
1
8
7
8
1
2
4
DRAIN CONNECTION
SCREW HOLE FOR UPFLOW APPLICATIONS (OPTIONAL)
1/
-IN. PVC OR CPVC
2
!
WARNING
A06501
58UVB
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury or death.
Casing hole filler cap must be installed in blower shelf hole when condensate trap is relocated to prevent combustion products being drawn in from appliances in the equipment room.
4. Install condensate trap into left--hand casing hole by inserting the top two outer tabs into casing hole, while making sure that the larger center tab is on the outside of the casing. Push the condensate trap up as far as possible and then rotate the connection stubs through the hole. Slide the condensate trap downwards to secure it in the casing hole.
5. Fill unused condensate trap casing holes with plastic filler caps (factory--supplied in loose parts bag).
CONDENSATE T RAP TUBING (ALTERNA CONFIGURA
TION)
TE
NOTE: See Fig. 8 or tube routing label on main furnace door to
confirm location of these tubes.
1. Collector Box Drain Tube Connect collector box drain tube (blue label) to condensate trap.
NOTE: On 17--1/2--in. wide furnaces ONLY, cut tube between corrugated sections to prevent kinks.
7
Page 8
2. Inducer Housing Drain Tube
a. Remove and discard LOWER (molded) inducer
housing drain tube which was previously connected to condensate trap.
b. Use inducer housing drain extension tube (violet label
and factory--supplied in loose parts bag) to connect LOWER inducer housing drain connection to condensate trap.
c. Determine appropriate length, then cut and connect
tube.
d. Clamp tube to prevent any condensate leakage.
3. Relief Port Tube a. Connect relief port tube (green label) to condensate
trap.
b. Determine appropriate length, then cut and connect
tube.
Attached to the UPPER collector box drain connection is a factory--installed plug. This plug prevents condensate leakage in this application. Ensure this plug is secure.
NOTE: See Fig. 7 or 8 or tube routing label on main furnace door to check for proper connections.
Upper Inducer Housing Drain Connection
Attached to the UPPER (unused) inducer housing drain connection is a cap and clamp. This cap is used to prevent condensate leakage in this application. Ensure this connection is capped.
NOTE: See Fig. 7 or 8 or tube routing label on main furnace door to check for proper connections.
CAP
58UVB
CAP
COLLECTOR BOX
TUBE (PINK)
INDUCER HOUSING
(MOLDED) DRAIN
TUBE (BEHIND
COLLECTOR BOX
DRAIN TUBE)
COLLECTOR BOX
DRAIN TUBE (BLUE)
COLLECTOR BOX
TUBE (GREEN)
FIELD-INSTALLED
FACTORY-SUPPLIED
DRAIN TUBE
COUPLING (LEFT
DRAIN OPTION)
FIELD-INSTALLED
FACTORY-SUPPLIED
DRAIN TUBE
FIELD-INSTALLED
FACTORY-SUPPLIED
1/2-IN. CPVC STREET
ELBOWS (2) FOR
LEFT DRAIN OPTION
FIELD-INSTALLED
FACTORY-SUPPLIED
COUPLING (RIGHT
Fig. 7 --- Factory--Shipped Trap Location
(Shown with Blower Access Panel Removed)
CONDENSATE TRAP FIELD DRAIN ATT
Refer to Condensate Drain section for recommendations and procedures.
PRESSURE SWITCH
TUBING
The LOWER collector box pressure tube (pink label) is factory connected to the pressure switch and should not require any modification.
NOTE: See Fig. 7 or 8 or tube routing label on main furnace door to check for proper connections.
UPPER COLLECTOR BOX AND INDUCER (UNUSED) DRAIN
CONNECTIONS
Upper Collector Box Drain Connection
CONDENSATE TRAP
DRAIN TUBE
DRAIN OPTION)
ACHMENT
HOUSING
PLUG
A06498
COLLECTOR BOX
TUBE (PINK)
COLLECTOR BOX
TUBE (GREEN)
COLLECTOR BOX
DRAIN TUBE (GREEN)
CONDENSATE
TRAP
INDUCER HOUSING
DRAIN TUBE
(VIOLET)
PLUG
A06499
Fig. 8 --- Alternate Trap Location
CONDENSATE TRAP FREEZE
PROTECTION
Refer to Condensate Drain Protection section for recommendations and procedures.
CONDENSATE TRAP FIELD DRAIN ATT
ACHMENT
Refer to Condensate Drain section for recommendations and procedures.
LOCATION
Step 1 —General
This furnace must
S be installed in upflow position ONLY S be installed so the electrical components are protected
from water .
S not be installed directly on any combustible material
other than wood flooring (refer to SAFETY CONSIDERATIONS).
S be located so combustion--air and vent pipe maximum
lengths are not exceeded. Refer to Table 8.
S be located where available electric power and gas
supplies meet specifications on the furnace rating plate.
S be attached to an air distribution system and be located
as close to the center of the distribution system as possible. Refer to Air Ducts section.
8
Page 9
S be provided with ample space for servicing and
cleaning. Always comply with minimum fire protection clearances shown on the furnace clearance--to--combustibles label. (See Fig. 3.)
This furnace may be located in a confined space without special provisions for dilution or ventilation air.
NOTE: Install furnace so that it is level or pitched forward within 1/2--in. for proper furnace operation. (See Fig. 9.)
LEVEL (0″)
TO
1
⁄2″ MAX
UPFLOW
Fig. 9 --- Proper Condensate Drainage
When a furnace is installed so that supply ducts carry air circulated by the furnace to areas outside the space containing the furnace, the return air shall also be handled by ducts sealed to furnace casing. The ducts terminate outside the space containing the furnace to ensure there will not be a negative pressure condition within equipment room or space.
!
FIRE, INJURY OR DEATH HAZARD
Failure to follow this warning could result in fire, property damage, personal injury, or death.
Do not install furnace on its back. (See Fig. 10.) Safety control operation will be adversely affected. Never connect return--air ducts to back of furnace.
WARNING
FRONT
A06343
!
CAUTION
UNIT DAMAGE HAZARD
This gas furnace may be used for construction heat provided that:
--The furnace is permanently installed with all electrical wiring, piping, air filters, venting and ducting installed according to these installation instructions. A return air duct is provided, sealed to the furnace casing, and terminated outside the space containing the furnace. This prevents a negative pressure condition as created by the circulating air blower, causing a flame rollout and/or drawing combustion products into the structure.
--The furnace is controlled by a thermostat. It may not be “hot wired” to provide heat continuously to the structure without thermostatic control.
--Clean outside air is provided for combustion. This is to minimize the corrosive effects of adhesives, sealers and other construction materials. It also prevents the entrainment of drywall dust into combustion air, which can cause fouling and plugging of furnace components.
--The temperature of the return air to the furnace is maintained between 55_F(13_C) and 80_F(27_C), with no evening setback or shutdown. The use of the furnace while the structure is under construction is deemed to be intermittent operation per our installation instructions.
--The air temperature rise is within the rated rise range on the furnace rating plate, and the firing rate has been set to the nameplate value.
--The filters used to clean the circulating air during the construction process must be either changed or thoroughly cleaned prior to occupancy.
--The furnace, ductwork and filters are cleaned as necessary to remove drywall dust and construction debris from all HVAC system components after construction is completed.
--After construction is complete, verify furnace operating conditions including ignition, input rate, temperature rise and venting, according to the manufacturer’s instructions.
58UVB
FRONT
B A C K
BACK
FRONT
A93043
Fig. 10 --- Prohibit Installation on Back
The furnace and its return air system shall be designed and installed so that negative pressure created by the air circulating fan cannot affect another appliance’s combustion air supply or act to mix products of combustion with circulating air, and that the air circulating fan of the furnace, if installed in an enclosure communicating with another fuel--burning appliance not of the direct--vent type, shall be operable only when any door or panel covering an opening in the furnace fan compartment or in a return air plenum on ducts is in the closed position.
9
Page 10
!
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in minor property or unit damage.
If these furnaces are installed in an unconditioned space where ambient temperatures may be 32_F or lower, freeze protection measures must be taken. See Condensate Drain Protection section and Fig. 11.
Step 3 —Furnace Location Relative to Cooling Equipment
The cooling coil must be installed parallel with or on downstream side of furnace to avoid condensation in heat exchanger. When installed parallel with a furnace, dampers or other means used to control flow of air shall be adequate to prevent chilled air from entering furnace. If dampers are manually operated, they must be equipped with a means to prevent operation of either unit unless damper is in full--heat or full--cool position.
Step 4 —Hazardous Locations
32oF MINIMUM INSTALLED
58UVB
AMBIENT OR FREEZE PROTECTION REQUIRED
Fig. 11 --- Freeze Protection
Step 2 —Low--Heat Only Installation
This 58UVB furnace can be installed to operate in the low--heat only heating mode when sized using the low-- heat heating capacity. This is accomplished by placing setup switch SW1--2 in the ON position to provide only low--heat operation. See Fig. 33 and Table 9. With this setup, high --heat operation will not occur.
!
CAUTION
A93058
!
FIRE, EXPLOSION, INJURY OR DEATH HAZARD
Improper location or inadequate protection could result in fire or explosion.
When furnace is installed in a residential garage, it must be installed so that burners and ignition sources are located a minimum of 18 in. above floor. The furnace must be located or protected to avoid physical damage by vehicles. When furnace is installed in a public garage, airplane hangar, or other building having a hazardous atmosphere, unit must be installed in accordance with requirements of National Fire Protection Association, Inc. (See Fig. 5.)
5
WARNING
⁄16″
5
⁄16″
1 3⁄4″
3
⁄4″
1
UNIT DAMAGE HAZARD
Failure to follow this caution may result in minor property or unit damage.
The furnace can operate in the high--heat mode when certain fault conditions occur. The following precautions should be taken:
1. Size gas piping based on the high--heat input.
2. Check the high-- heat input and adjust it per the main literature instructions.
5
⁄16″
5
⁄16″
3
⁄4″
1
3
⁄4″
1
A89014
Fig. 12 --- Leveling Legs
INSTALLATION
Step 1 —Leveling Legs (If Desired)
When furnace is used in upflow position with side inlet(s), leveling legs may be desired. (See Fig. 12.) Install field--supplied, corrosion --resistant 5/16-- in. machine bolts and nuts.
NOTE: The maximum length of bolt should not exceed 1 --1/2 in.
1. Position furnace on its back. Locate and drill a 5/16--in. diameter hole in each bottom corner of furnace. (See Fig.
12.) Holes in bottom closure panel may be used as guide locations.
10
Page 11
2. For each hole, install nut on bolt and then install bolt and nut in hole. (Install flat washer if desired.)
3. Install another nut on other side of furnace base. (Install flat washer if desired.)
4. Adjust outside nut to provide desired height, and tighten inside nut to secure arrangement.
NOTE: Bottom closure must be used when leveling legs are used. See Bottom Closure Panel section.
Step 2 —Installation
1. Construct hole in floor per dimensions specified in Fig. 13 and Table 1.
2. Construct plenum to dimensions specified in Fig. 13 and Tab le 1.
A
PLENUM
OPENING
B
OPENING
C
D
FLOOR
Secure ductwork with proper fasteners for type of ductwork used. Seal supply-- and return--duct connections to furnace with code approved tape or duct sealer.
Flexible connections should be used between ductwork and furnace to prevent transmission of vibration. Ductwork passing through unconditioned space should be insulated to enhance system performance. When air conditioning is used, a vapor barrier is recommended.
Maintain a 1-- in. clearance from combustible materials to supply air ductwork for a distance of 36 in. horizontally from the furnace. See NFPA 90B or local code for further requirements.
For a furnace not equipped with a cooling coil, the outlet duct shall be provided with a removable access panel. This opening shall be accessible when the furnace is installed and shall be of such a size that the heat exchanger can be viewed for possible openings using light assistance or a probe can be inserted for sampling the air stream. The cover attachment shall prevent leaks.
DUCTWORK ACOUSTICAL TREA
Metal duct systems that do not have a 90 degree elbow and 10 ft of main duct to the first branch take--off may require internal acoustical lining. As an alternative, fibrous ductwork may be used if constructed and installed in accordance with the latest edition of SMACNA construction standard on fibrous glass ducts. Both acoustical lining and fibrous ductwork shall comply with NFPA 90B as tested by UL Standard 181 for Class 1 Rigid air ducts.
SUPPLY AIR
Connect supply--air duct to 3/4--in. flange on furnace supply--air outlet. The supply--air duct attachment must ONLY be connected to furnace supply-- /outlet-- air duct flanges or air conditioning coil casing (when used). DO NOT cut main furnace casing to attach supply side air duct, humidifier, or other accessories. All accessories MUST be connected external to furnace main casing.
RETURN AIR
CONNECTIONS
CONNECTIONS
TMENT
58UVB
A96283
Fig. 13 --- Floor and Plenum Opening Dimensions
TABLE 1—OPENING DIMENSIONS (IN.)
FURNACE
CASING
WIDTH
17--- 1/2 16 24---1/8 16- --5/8 24---3/4
21 19---1/2 24---1/8 20--- 1/8 24---3/4
24--- 1/2 23 24---1/8 23- --5/8 24---3/4
PLENUM OPENING
A
B C D
FLOOR OPENING
Step 3 —Air Ducts
GENERAL REQUIREMENTS
The duct system should be designed and sized according to accepted national standards such as those published by: Air Conditioning Contractors Association (ACCA), Sheet Metal and Air Conditioning Contractors National Association (SMACNA) or American Society of Heating, Refrigerating and Air Conditioning Engineers (ASHRAE) or consult The Air Systems Design Guidelines reference tables available from your local distributor. The duct system should be sized to handle the required system design CFM at the design static pressure.
When a furnace is installed so that the supply ducts carry air circulated by the furnace to areas outside the space containing the furnace, the return air must also be handled by a duct(s) sealed to the furnace casing and terminating outside the space containing the furnace.
!
FIRE HAZARD
Failure to follow this warning could result in fire, personal injury, or death.
Never connect return--air ducts to the back of the furnace.
The return--air duct must be connected to bottom, sides (left or right), or a combination of bottom and side(s) of main furnace casing. Bypass humidifier may be attached into unused side return air portion of the furnace casing. DO NOT connect any portion of return-- air duct to back of furnace casing.
WARNING
Step 4 —Filter Arrangement
!
FIRE, CARBON MONOXIDE AND POISONING HAZARD
Failure to follow this warning could result in fire, personal injury or death.
Never operate unit without a filter or with filter access door removed.
The air filter arrangement will vary due to return air configuration and filter type. The filter may be installed in an external Filter/Media cabinet (if provided) or the furnace blower compartment. Factory supplied washable filters are shipped in the blower compartment.
If a factory--supplied external Filter/Media cabinet is provided, instructions for its application, assembly, and installation are
WARNING
11
Page 12
packaged with the cabinet. The Filter/Media cabinet can be used
R
with the factory--supplied washable filter or a factory--specified high--efficiency disposable filter (see cabinet instructions).
If installing the filter in the furnace blower compartment, determine location for filter and relocate filter retaining wire, if necessary. See Table 2 to determine correct filter size for desired filter location. Table 2 indicates filter size, location, and quantity shipped with this furnace. See Fig. 2 for location and size of bottom and side return--air openings.
!
CAUTION
CUT HAZARD
Failure to follow this caution may result in minor personal injury.
Use care when cutting support rods in filters to protect against flying pieces and sharp rod ends. Wear safety glasses, gloves, and appropiate protective clothing.
NOTE: Side return--air openings can be used for return air connections. Install filter(s) as shown in Fig. 14.
For bottom return--air applications, filter may need to be cut to fit some furnace widths. Install filter as shown in Fig. 15.
171⁄2-IN. WIDE CASINGS ONLY:
INSTALL FIELD-SUPPLIED FILTER FILLER STRIP UNDER FILTER.
3
″
1
24
/2″
1
″
21-IN. WIDE CASINGS ONLY:
SUPPORT RODS (3) EXTEND 1/4" ON EACH SIDE OF FILTER AND REST ON CASING FLANGE
58UVB
Furnace
Casing Width
* Filters may be field modified by cutting filter material and support rods
(3) in filters. Alternate sizes can be ordered from your distributor or dealer.
{ Factory--- provided with the furnace
TABLE 2—FILTER INFORMATION
AIR FILTER LOCATED IN BLOWER COMPARTMENT
Filter Size (In.)
(In.)
17---1/2 (1) 16 x 25 x 1{ (1) 16 x 25 x 1{ Cleanable
21 (1) 16 x 25 x 1* (1) 20 x 25 x 1{ Cleanable
24---1/2
WASHABLE
Side
Return
(1 or 2)
16 x 25 x 1*
FILTER
Bottom Return*
(1) 24 x 25 x 1{ Cleanable
Fig. 14 --- Filter Installed for Side Inlet
!
CAUTION
UNIT MAY NOT OPERATE
Failure to follow this caution may result in intermittent unit operation or performance satisfaction.
For airflow requirements above 1800 CFM, see Air Delivery table in Product Data literature for specific use of single side inlets. The use of both side inlets, a combination of 1 side and the bottom, or the bottom only will ensure adequate return air openings for airflow requirements above 1800 CFM.
Filter Type
Framed
FILTER RETAINE
A93045
WASHABLE FILTER
FILTER SUPPORT
FILTER RETAINER
Fig. 15 --- Bottom Filter Arrangement
NOTE: Remove and discard bottom closure panel when bottom
inlet is used.
Step 5 —Bottom Closure Panel
These furnaces are shipped with bottom closure panel installed in bottom return--air opening. This panel MUST be in place when side return air is used.
To remove bottom closure panel, perform following:
1. Tilt or raise furnace and remove 2 screws holding front filler panel. (See Fig. 16.)
2. Rotate front filler panel downward to release holding tabs.
3. Remove bottom closure panel.
4. Reinstall front filler panel and screws.
Step 6 —Gas Piping
Gas piping must be installed in accordance with national and local codes. Refer to NFGC in the U.S. Canadian installations must be made in accordance with NSCNGPIC and all authorities having jurisdiction. Gas supply line should be a separate line running directly from meter to furnace, if possible. Refer to Table 3 for recommended gas pipe sizing. Risers must be used to connect to furnace and to meter. Support all gas piping with
12
A00290
Page 13
appropriate straps, hangers, etc. Use a minimum of 1 hanger every 6 ft. Joint compound (pipe dope) should be applied sparingly and only to male threads of joints. Pipe dope must be resistant to propane gas.
!
WARNING
FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in fire, explosion, personal injury, or death.
-- Connect gas pipe to furnace using a backup wrench to avoid damaging gas controls.
-- Gas valve shutoff switch MUST be facing forward or tilted upward.
-- Never purge a gas line into a combustion chamber. Never test for gas leaks with an open flame. Use a
commercially available soap solution made specifically
for the detection of leaks to check all connections.
-- Use proper length of pipe to avoid stress on gas
control manifold.
-- If a flexible connector is required or allowed by authority having jurisdiction, black iron pipe shall be installed at furnace gas valve and extend a minimum
of 2 in. outside furnace casing.
--Protect gas valve from water and debris. Gas valve inlet and/or inlet piping must remain capped until gas
supply line is permanently installed to protect the valve
from moisture and debris. Also, install a sediment trap
in the gas supply piping at the inlet to the gas valve.
Install a sediment trap in riser leading to furnace. Trap can be installed by connecting a tee to riser leading to furnace so straight--through section of tee is vertical. Then connect a capped nipple into lower end of tee. Capped nipple should extend below level of gas controls. Place a ground joint union between gas control manifold and manual gas shutoff valve. (See Fig. 17.)
An accessible manual shutoff valve MUST be installed external to furnace casing and within 6 ft of furnace. A 1/8--in. NPT plugged tapping, accessible for test gauge connection, MUST be installed immediately upstream of gas supply connection to furnace and downstream of manual shutoff valve.
Gas line grommet (factory--supplied loose parts bag) should be used when installing gas piping. Gas line entry hole filler plug should be installed in unused gas line entry hole. (See Fig. 18.)
COMBUSTION-AIR PIPE GROMMET
BOTTOM CLOSURE PANEL
FRONT FILLER PANEL
Fig. 16 --- Removing Bottom Closure Panel
GAS SUPPLY
MANUAL SHUTOFF VALVE (REQUIRED)
SEDIMENT TRAP
UNION
Fig. 17 --- Typical Gas Pipe Arrangement
A93047
58UVB
A93324
COMBUSTION
-AIR PIPE
GAS LINE
VENT PIPE
NOTE: PIPE GROMMETS AND ENTRY HOLE FILLER PLUGS ARE INCLUDED IN FACTORY-SUPPLIED LOOSE PARTS BAG
UNUSED 1-3/4 -IN. DIAMETER GAS CONN. HOLE
GAS LINE ENTRY HOLE FILLER PLUG
GAS LINE GROMMET
VENT PIPE GROMMET
A05057
Fig. 18 --- Casing Pipe Grommets
13
Page 14
TABLE 3 —MAXIMUM CAPACITY OF PIPE*
NOMINAL
IRON
PIPE SIZE
(IN.)
1/2 0.622 175 120 97 82 73 3/4 0.824 360 250 200 170 151
1 1.049 680 465 375 320 285 1 --- 1 / 4 1.380 1400 950 770 660 580 1 --- 1 / 2 1.610 2100 1460 1180 990 900
*Cubic ft of gas per h r for gas pressures of 0.5 psig (14 ---in. wc) or less,
and a pressure drop of 0.5---in. wc (based on a 0.60 specific gravity gas). Ref: Table 9---2 NFPA 54 --- 2002.
NOTE: The gas valve inlet pressure tap connection is suitable to use as test gauge connection providing test pressure DOES NOT exceed maximum 0.5 psig (14-- in. wc) stated on gas valve. (See Fig. 51.)
Piping should be pressure and leak tested in accordance with
58UVB
NFGC in the United States or NSCNGPIC in Canada, local, and national plumbing and gas codes before the furnace has been connected. If pressure exceeds 0.5 psig (14 --in. wc), gas supply pipe must be disconnected from furnace and capped before pressure test.
If test pressure is equal to or less than 0.5 psig (14--in. wc), turn off electric shutoff switch located on gas valve before test. It is recommended that ground joint union be loosened before pressure testing. After all connections have been made, purge lines and check for leakage at furnace prior to placing it into service.
The gas supply pressure shall be within the maximum and minimum inlet supply pressures marked on the rating plate with the furnace burners ON at HI--HEAT and OFF.
INTERNAL DIAMETER
(IN.)
LENGTH OF PIPE (FT)
10 20 30 40 50
Step 7 —Electrical Connections
See Fig. 19 for field wiring diagram showing typical field 115--v and 24-- v wiring. Check all factory and field electrical connections for tightness.
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Blower access door switch opens 115--v power to furnace control. No component operation can occur. Do not bypass or close switch with panel removed.
WARNING
!
UNIT MAY NOT OPERATE
Failure to follow this caution may result in intermittent unit operation.
Furnace control must be grounded for proper operation or control will lock out. Control is grounded through green/yellow wire connected to gas valve and burner box screw.
115 -- V WIRING
Before proceeding with electrical connections, make certain that voltage, frequency, and phase correspond to that specified on furnace rating plate. Also, check to be sure that service provided by power supply is sufficient to handle load imposed by this equipment. Refer to rating plate or Table 4 for equipment electrical specifications.
Make all electrical connections in accordance with National Electrical Code (NEC) ANSI/NFPA 70--2002 and any local codes or ordinances that might apply. For Canadian installations, all electrical connections must be made in accordance with Canadian Electrical Code CSA C22.1 or authorities having jurisdiction.
Field--supplied wiring shall conform with the limitations of 63_F (33_C) rise.
The furnace must be electrically grounded in accordance with local codes; or in the absence of local codes, with the National Electric Code ANSI/NFPA 70 and/or the Canadian Electric Code, CSA C22.1, Part I, if an external electrical source is utilized.
Use a separate branch electrical circuit containing a properly sized fuse or circuit breaker for this furnace. See Table 4 for wire size and fuse specifications. A disconnecting means must be located within sight from and readily accessible to furnace.
NOTE: Proper polarity must be maintained for 115-- v wiring. If polarity is incorrect or furnace is not grounded properly, furnace control status code indicator light will flash rapidly and furnace will NOT operate.
!
FIRE HAZARD
Failure to follow this warning could result in intermittent operation or performance satisfaction.
Do not connect aluminum wire between disconnect switch and furnace. Use only copper wire. (See Fig. 20.)
WARNING
WARNING
14
Page 15
115-V SINGLE PHASE
115-V
FIELD-SUPPLIED
DISCONNECT
SWITCH
FURNACE
CONTROL
CENTER
FIVE
WIRE
THREE-WIRE
NOTE 5
WCR GY
THERMOSTAT TERMINALS
HEATING
ONLY
W/W1
NOTE
W2
3
R
Y/Y2
24-V
G
C
NOTE 1
CONDENSING
TWO WIRE
AUXILIARY J-BOX
TERMINAL
BLOCK
NOTES:
1.
Connect Y or Y/Y2 terminal as shown for proper cooling operation.
2.
Proper polarity must be maintained for 115-v wiring.
3.
Use W2 with 2-stage thermostat when zoning.
4.
If any of the original wire, as supplied, must be replaced, use same type or equivalent wire.
5.
Some thermostats require a "C" terminal connection as shown.
Fig. 19 --- Heating and Cooling Application Wiring Diagram
FIELD 24-V WIRING FIELD 115-, 208/230-, 460-V WIRING FACTORY 24-V WIRING FACTORY 115-, 208/230-, 460-V WIRING
FIELD-SUPPLIED
DISCONNECT
208/230- OR
460-V
THREE PHASE
GND
GND
208/230-V
SINGLE
PHASE
GND
GND
UNIT
58UVB
A98325
TABLE 4—ELECTRICAL DATA
MAXIMUM
WIRE
LENGTH
(FT)}
UNIT SIZE
V O L T S ---
H E R T Z ---
PHASE
OPERATING VOLTAGE
RANGE
Maximum* Minimum*
MAXIMUM
UNIT
AMPS
MINIMUM
WIRE SIZE
060--- 14 1 1 5 --- 6 0 --- 1 127 104 8.9 14 31 15
080--- 14 1 1 5 --- 6 0 --- 1 127 104 8.9 14 31 15
080--- 20 1 1 5 --- 6 0 --- 1 127 104 13.8 12 32 20
100--- 20 1 1 5 --- 6 0 --- 1 127 104 13.8 12 32 20
120--- 20 1 1 5 --- 6 0 --- 1 127 104 13.8 12 32 20
* Permissible limits of voltage range at which unit will operate satisfactorily. { Unit ampacity = 125 percent of largest operating component’s full load amps plus 100 percent of al l other potential operating components’ (EAC,
humidifier, etc.) full l oad amps.
} Length shown is as measured 1 way along wire path between unit and service panel for maximum 2 percent voltage drop. ** Time ---delay type is recommended.
!
ELECTRICAL SHOCK AND FIRE HAZARD
Failure to follow this warning coud result in electrical shock, fire, or death.
The cabinet MUST have an uninterrupted or unbroken
WARNING
ELECTRIC
DISCONNECT
SWITCH
COPPER
WIRE ONLY
MAXIMUM
FUSE OR CKT
AMPS**
ground according to NEC ANSI/NFPA 70--2002 and Canadian Electrical Code CSA C22.1 or local codes to minimize personal injury if an electrical fault should
ALUMINUM
WIRE
occur. This may consist of electrical wire or conduit approved for electrical ground when installed in accordance with existing electrical codes. Do not use
Fig. 20 --- Disconnect Switch and Furnace
gas piping as an electrical ground.
BKR
A93033
15
Page 16
FACTORY INSTALLED J--BOX LOCA
TION
Install power entry hole filler plugs (factory--supplied in loose parts bag) in unused power entry holes. (See Fig. 21.)
POWER ENTRY HOLE FILLER PLUG (FACTORY­SUPPLIED LOOSE PARTS BAG)
UNUSED 7/8-IN. DIAMETER POWER ENTRY HOLES
Fig. 21 --- Factory Installed J--Box Location
J--BOX RELOCA
TION
1. Remove 2 screws holding auxiliary J--box. (See Fig. 22.)
2. Rotate J--box 180_ and attach box to left side, using holes
58UVB
provided.
3. Install power entry hole filler plugs (factory--supplied loose parts bag) in unused power entry holes. (See Fig.
22.)
!
WARNING
FIRE OR ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in intermittent unit operation or performance satisfaction.
If manual disconnect switch is to be mounted on furnace, select a location where a drill or fastener will not contact electrical or gas components.
CONTINUOUS FAN (CF) SETUP SWITCHES
The CF setup switches are used to select desired airflow when thermostat is in continuous fan mode or to select low--cooling airflow for two--speed cooling units. This setup feature allows continuous fan airflow or low-- cooling airflow to be adjusted. To set desired continuous fan airflow or low--cooling airflow:
1. Remove main furnace door and blower access panel.
2. Locate CF setup switches on furnace control. (See Fig.
33.)
3. Determine desired continuous fan airflow or low--cooling airflow.
4. Use wiring schematic to determine proper setup position of CF switches. (See Fig. 23 and 39.)
5. Replace main furnace door and blower access panel.
FACT ORY INSTALLED LOCATION
A05113
SETUP SWITCHES
(SW1)
The furnace control has 8 setup switches that may be set to meet the application requirements. Position these setup switches for the appropriate requirement.
1. Remove main furnace door and blower access panel.
2. Locate setup switches on furnace control. (See Fig. 33.)
3. See Table 9 for setup switch description.
4. Replace main furnace door and blower access panel.
NOTE: If a bypass humidifier is used, setup switch SW1--3 (Low Heat Rise Adjust) should be in ON position. This compensates for the increased temperature in return air resulting from bypass.
NOTE: If modulating dampers are used, blower motor automatically compensates for modulating dampers. If manual disconnect switch is to be mounted on furnace, select a location where a drill or fastener will not contact electrical or gas components.
24--V
WIRING
Make field 24--v thermostat connections at 24-- v terminal block on furnace control. Y wire from thermostat MUST be connected to Y/Y2 terminal on control, as shown in Fig. 19, for proper cooling operation. The 24--v terminal block is marked for easy connection of field wiring. (See Fig. 33.) The 24 -- v circuit contains a 3-- amp, automotive--type fuse located on furnace control. (See Fig. 33.)
Any electrical shorts of 24--v wiring during installation, service, or maintenance may cause fuse to blow. If fuse replacement is required, use only a fuse of identical size (3 amp) and type. The furnace control will flash status code 24 when fuse needs replacement.
NOTE: Use AWG No. 18 color--coded copper thermostat wire for lengths up to 100 ft. For wire lengths over 100 ft, use AWG No. 16 wire.
NOTE: For additional thermostat connection diagrams, reference Fig. 43--50.
ACCESSORIES
1. Electronic Air Cleaner (EAC) The furnace control EAC terminals are energized with 115v (1.0--amp maximum) during blower operation. Connect an accessory Electronic Air Cleaner (if used) using 1/4--in. female quick connect terminals to the two male 1/4--in. quick--connect terminals on the control board marked EAC--1 and EAC--2. The terminals are rated for 115VAC, 1.0 amps maximum and are energized during blower motor operation. (See Fig. 33.)
POWER ENTRY HOLE FILLER PLUG (FACTORY­SUPPLIED LOOSE PARTS BAG)
UNUSED 7/8-IN. DIAMETER POWER ENTRY HOLES
ALTERNATE
FIELD
LOCATION
Fig. 22 --- Relocating J--Box
16
FACTORY INSTALLED LOCATION
POWER ENTRY HOLE FILLER PLUG (FACTORY­SUPPLIED LOOSE PARTS BAG)
UNUSED 7/8-IN. DIAMETER POWER ENTRY HOLES
A05058
Page 17
* * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * ** * * * * * * * * * * * * * * * * ** * * * * * * * * * * * * * * * *
* * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * ** * * * * * * * * * * * * * * * * ** * * * * * * * * * * * * * * * *
* * * * * * ** * * * * * * * * * * * * * * * * * * * * * * ** * * * * * * * * * * * * * * * * * * * * * * * * * * * * * *
* * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * ** * * * * * * * * * * * * * * * * ** * * * * * * * * * * * * * * * * *
* * * * * * ** * * * * * * * * * * * * * * * * * * * * * * ** * * * * * * * * * * * * * * * * * * * * * * * * * * * * *
*
SW1-7,8
BLOWER OFF DELAY
SELECTION
OFF
7 8 7 8 7 8
OFF OFF
OFF
7 8
PL4 - MODEL PLUG CHART
MODEL
MODEL
PLUG
SIZE
HK70EZ
060
3.5T080 5T-080
100 120 061
PRINTED CIRCIUT BOARD
SW4
OAT
PL9
PL7
ABCD
1
PL4
SW1
1
L
A/C Air Conditioning (Adjustable Air flow -CFM) ACR Air Conditioning Relay, SPST (N.O.)
E
ACRDJ Air Conditioning Relay Defeat Jumper
G
BLWM Blower Motor (ECM)
E
CF Continuous Fan (Adjustable Air flow -CFM) COMMR Communication Relay, SPDT
N
CPU Microprocessor / Circuitry
D
DHUM DHUM Connection (24VAC ) EAC-1 Electronic Air Cleaner Connection
(115VAC 1.0 Amp Max.) EAC-2 Electronic Air Cleaner Connection (Common) FRS Flame Rollout Switch, Man. Reset, SPST(N.C.) FSE Flame-Proving Sensor Electrode FUSE Fuse, 3 Amp, Automotive Blade Type,
Factory Installed GV Gas Valve GVR Gas Valve Relay, DPST (N.O.) HPS High-Heat Pressure Switch, SPST (N.O.) HPSR High-Heat Pressure Switch Relay, SPST (N.C.) HSI Hot Sur face Igniter (115VAC) HSIR Hot Sur face Igniter Relay, SPST (N.O.) HUM 24VAC Humidifier Connection (0.5 Amp Max.) HUMR Humidifier Relay, SPST (N.O.) IDM Inducer Draft Motor, 2-Speed, Shaded Pole IDR Inducer Motor Relay, SPST (N.O.) IHI/LOR Inducer Motor Speed Change Relay, SPDT ILK Blower Door Interlock Switch, SPST (N.O.)
* * * * * * ** * * * * * * * * * * * * * * * * * * * * * * ** * * * * * * * * * * * * * * * * * * * * * * * * * * * * * *
* * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * ** * * * * * * * * * * * * * * * * ** * * * * * * * * * * * * * *
CONNECTION DIAGRAM
M
90 SEC 120 SEC 150 SEC 180 SEC
057 058 059 060
MODEL
060
3.5T080
5T080,100
120
1. Default A/C airflow when A/C switches are in OFF position
2. Default cont. fan airfl ow when C F swit ches are in OFF position
1
CF
1
AC
GV
BRN
C
HI
GRN/YEL
NOTE #3
PIN RESISTANCE K
1 - 4
2 - 3
24
91
24
120
24
150
24
180
24
220
PL8
A/C OR CF AIRFLOW SELECTION CHART BASED ON 350 CFM/TON
1 2 3
1 2 3
OFF
OFF
525
2
700
2
700
HUM
ACRDJ
1 2 3
700 875 1050 1225 1400
875
C 24V
SIZE
OFF
W2 Y/ Y2 RY1
DEF. DEF.
DEF.
BLU
HPS
GRY
BRN
GRN/YEL
PL3
1
GRN
RED
BLU
YEL
PL1
4
1 2 3
1 2 3
1 2 3
OFF
OFF
OFF
1
1050
875
1225
1050
2
COMM
LEDS
W/W1DHUM G
om
STATUS
IND Inductor (Note #7) LED Light Emitting Diode for Status Codes LGPS Low Gas Pressure Switch, SPST (N.O.) LPS Low-Heat Pressure Switch, SPST (N.O.) LS Limit Switch, Auto-Reset, SPST (N.C.) PCB Printed Circuit Board PL1 12-Circuit Connector PL2 4-Circuit HSI & IDM Connector PL3 4-Circuit ECM BLWM Connector PL4 4-Circuit Model Plug Connector PL7 4-Circuit Communication Connector PL9 2-Circuit OAT Connector PL10 2-Circuit HSI Connector PL11 IDM Connector (12-Circuit) PL12 1-Circuit Inductor Splice Connector PL13 16-Circuit ECM Blower Ctrl. Connec tor PL14 5-Circuit ECM Blower Power Connector SW1-1 Manual Switch, Status Code Recall, SPST (N.O.) SW1-2 Manual Switch, Low-Heat Only, SPST(N.O.) SW1-3 Manual Switch, Low-Heat Rise Adj. SPST (N.O.) SW1-4 Manual Switch, Comfort/Efficiency Adjustment,
SW1-5 Manual Switch, Cooling CFM/Ton, SPST (N.O.) SW1-6 Manual Switch, Component Test, SPST (N.O.) SW1-7,8 Manual Switches, Blower Off-Delay, SPST(N.O.) SW4-1 Manual Switch, Twinning Main (OFF) / Sec. (ON) SW4-2&3 FOR FUTURE USE TRAN Transformer, 115VAC / 24VAC
1 2 3
OFF
1750
CODE
SPST (N.O.)
LS
RED
RED
LPS
YEL
1
1 2 3
OFF
122512251225 1750
1
210017501400
1
NEUTRAL - L2
SEC-1
EAC-2
FUSE 3-AMP
SEC-2
WHT
EAC-1
NOTE #11
NOTE #8
WHT
FSE
BLK
HSI VS
WHT
PL2
BLK
L1
BLK
PL12
NOTE #7
BLK
WHT
BLU
WHT
FRS
RED RED
ORN
(WHEN USED)
LGPS
GRN/YEL
4
BRN
2
YEL
10 1
ORN
12
WHT
6
BLK
BLK
BLK
4
PL13
IND
10
16
17
GRN
BLU
YEL
PL12
WHT
TRAN
RED
IDM
HSI
1
PL10
2
BLWM
PL14
1
432
5
RED
YEL
GRN/YEL
JUNCTION TERMINAL CONTROL TERMINAL FACTORY POWER WIRING (115VAC) FACTORY CONTROL WIRING (24VAC) FIELD CONTROL WIRING (24VAC) CONDUCTOR ON CONTROL FIELD WIRING SCREW TERMINAL EQUIPMENT GROUND PLUG RECEPTACLE
FUSED OR CIRCUIT BREAKER DISCONNECT SWITCH (WHEN REQ'D)
NOTE #2
L1
FU2
BLK
WHT
JB
ILK
PRINTED CIRCIUT BOARD
NOTES:
1. If any of the original equipment wire is replaced use wire rat ed for 105°C.
2. Use only copper wire between the disconnect switch and the furnace junction box (JB).
3. This wire must be connected to furnace sheet metal f or control to pr ove flame.
4. Symbols are electrical representation only.
5. Soli d lines inside PCB ar e printed circu it board conductor s and are not included in legend.
6. Replace only with a 3 amp fuse.
7. Inductor is used with 3/4 hp and 1 hp ECM Blower motors.
8. Factory connected when (LGPS) not used.
9. Blower off-delay, gas heating selections are (90, 120, 150, 180) seconds, cooling or heat pump
10. Ignition lockout will occur after four consecutive unsuccessful trials for ignition. Control will
11. Any of the 5 wires shown within the NEUTRAL L2 box can be connected to any terminal within the box.
12. Blower motor (BLWM) and Inducer motor (IDM) are locked-rotor overload protected by redundant
TO 115VAC FIELD-DISCONNECT SWITCH
ILK
NEUTRAL
GND
IDR
NOTE #5
PCB
CPU
PL3
123 4
PL12
L1
EAC
FRS
ACRDJ
PCB
NOTE #5
HUMR
ACR
CPU
HUM
R
COMMR
W/W1
DHUM
W2
Y/Y2
G
Y1
COM
90 seconds or 5 sec onds when dehumidify cal l is active.
auto-reset after three hours.
electronic control circuits.
Fig. 23 --- Wiring Diagram
L2
HSIR
IHI/LOR
IND
NOTE #7
EQUIPMENT GROUND
L2
HPSR
GVR
PL2
PL1-7 PL1-11 PL1-9
EAC-1
LS
3
1 2
4
SCHEMATIC DI AGRAM
PL10
2
HSI
1
12 6 1 2
10
4
PL13
10 16
1
7
PL12
5
4
3
2
1
PL14 EAC-2
PL1-6
PL1-8
PL1-12
PL1-2
NOTE #8
PL1-4
LGPS
(WHEN USED)
PL1-3
PL1-10
M
GV
NOTE #3
C
PL1-1
FU1
NOTE #6
L2
PL11
IDM
BLWM
L2
L1
L2
115VAC
TRAN
SEC1
SEC2
24VAC
LPS
58UVB
HPS
HI
PL1-5
FSE
332710-101 REV. A
* * * * * * ** * * * * * * * * * * * * * * * * * * * * * * ** * * * * * * * * * * * * * * * * * * * * * * * * * * * * *
A06459
!
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in unit component damage.
DO NOT connect furnace control HUM terminal to HUM (humidifier) terminal on Thermidistatt, Zone Controller or similar device. See Thermidistatt, Zone Controller, thermostat, or controller manufacturer’s instructions for proper connection.
2. Humidifier (HUM) Connect an accessory 24 VAC, 0.5 amp maximum humidifier (if used) to the 1/4--in. male quick--connect HUM terminal and COM --24V screw terminal on the control board thermostat strip. The HUM terminal is energized when blower is energized in heating. (See Fig. 23 and 33.)
Step 8 —Removal of Existing Furnaces from Common Vent Systems
When an existing Category I furnace is removed or replaced, the original venting system may no longer be sized to properly vent the remaining attached appliances. An improperly sized Category I venting system could cause the formation of condensate in the furnace and vent, leakage of condensate and combustion products, spillage of combustion products into the living space, etc.
17
Page 18
!
CAUTION
CARBON MONOXIDE POISONING HAZARD
Failure to follow the steps outlined below for each appliance connected to the venting system being placed into operation could result in carbon monoxide poisoning or death.
The following steps shall be followed for each appliance connected to the venting system being placed into operation, while all other appliances connected to the venting system are not in operation:
1. Seal any unused openings in venting system.
2. Inspect the venting system for proper size and horizontal pitch, as required in the National Fuel Gas Code, ANSI
Z223.1--2002/NFPA 54--2002 or the CSA B149.1, Natural Gas and Propane Installation Code and these instructions.
Determine that there is no blockage or restriction, leakage, corrosion and other deficiencies, which could cause an
58UVB
unsafe condition.
3. As far as practical, close all building doors and windows and all doors between the space in which the appliance(s) connected to the venting system are located and other spaces of the building.
4. Close fireplace dampers.
5. Turn on clothes dryers and any appliance not connected to the venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they are operating at maximum speed. Do not operate a summer exhaust fan.
6. Follow the lighting instructions. Place the appliance being inspected into operation. Adjust the thermostat so appliance is operating continuously.
7. Test for spillage from draft hood equipped appliances at the draft hood relief opening after 5 minutes of main burner operation. Use the flame of a match or candle.
8. If improper venting is observed during any of the above tests, the venting system must be corrected in accordance with the National Fuel Gas Code, ANSI
Z223.1--2002/NFPA 54--2002 and/or CSA B149.1, Natural Gas and Propane Installation Code.
9. After it has been determined that each appliance connected to the venting system properly vents when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and any other gas--fired burning appliance to their previous conditions of use.
Step 9 —Combustion Air and Vent Pipe Systems
GENERAL
Vent system or vent connectors of other appliances may need to be resized. For any other appliances when resizing vent systems or vent connectors, system or connector must be sized to approach minimum size as determined using appropriate table found in the NFGC or NSCNGPIC.
The 58UVB can be vented as either a direct vent furnace or as an optional ventilated combustion air application. A direct vent system shall be installed in accordance with the direct vent (2--pipe) procedures in the following Combustion Air and Vent Pipe Systems section. For optional ventilated combustion air applications, refer to the ventilated combustion air option procedures in the same section. Common venting prohibited.
DIRECT VENT/2--PIPE
In a direct--vent (2--pipe) system, all air for combustion is taken directly from outdoor atmosphere, and all flue products are discharged to outdoor atmosphere. Combustion-- air and vent pipes must terminate together in the same atmospheric pressure zone, either through the roof or a sidewall (roof termination preferred). A factory accessory vent termination kit MUST be used in a direct vent (2--pipe) system. See Table 6. See Fig. 34 for required clearances.
SYSTEM
VENTILATED COMBUSTION AIR
In a ventilated combustion air option, the vent terminates and discharges the flue products directly to the outdoors similar to a direct vent system. See Fig. 35 for required clearances. All air for combustion is piped directly to the furnace from a space that is well ventilated with outdoor air (such as an attic or crawl space) and the space is well isolated from the living space or garage.
TERIALS
MA
Combustion-- air and vent pipe, fittings, primers, and solvents must conform to American National Standards Institute (ANSI) standards and American Society for Testing and Materials (ASTM) standards. See Table 5 for approved materials for use in the U.S.A.
!
FIRE AND EXPLOSION HAZARD
Failure to follow this warning could result in fire, property damage, personal injury, or death. Solvent cements are combustible. Keep away from heat, sparks, and open flame. Use only in well ventilated areas. Avoid breathing in vapor or allowing contact with skin or eyes.
In Canada, construct all combustion--air and vent pipes for this unit of CSA or ULC listed schedule--40 PVC, PVC-- DWV or ABS--DWV pipe and pipe cement. SDR pipe is NOT approved in Canada.
!
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in property damage, personal injury, or death.
All combustion--air and vent pipes must be airtight and watertight. Pipes must also terminate exactly as shown in Fig. 31 for direct vent (2--pipe) system or Fig. 32 for ventilated combusion air option.
An abandoned masonry chimney may be used as a raceway for properly insulated and supported combustion--air (when applicable) and vent pipes. Each furnace must have its own set of combustion--air and vent pipes and be terminated individually, as shown in Fig. 31 for Direct Vent (2-- Pipe) system or Fig. 32 for ventilated combusion air option.
A furnace shall not be connected to a chimney flue serving a separate appliance designed to burn solid fuel.
Other gas appliances with their own venting system may also use the abandoned chimney as a raceway providing it is permitted by local code, the current edition of the National Fuel Gas Code and the vent or liner manufacturer’s installation instructions. Care must be taken to prevent the exhaust gases from one appliance from contaminating the combustion air of other gas appliances. Do not take combustion air from inside the chimney when using the Ventilated Combustion Air option.
WARNING
WARNING
OPTION
18
Page 19
TABLE 5 —APPROVED COMBUSTION--AIR AND VENT PIPE, FITTING AND CEMENT MATERIALS
ASTM
SPECIFICATION
(MARKED ON MATERIAL)
D1527 ABS Pipe — — S c h e d u l e --- 4 0 D1785 PVC Pipe — — S c h e d u l e --- 4 0 D2235 For ABS — — Solvent Cement For ABS D2241 PVC Pipe — — SD R --- 21 & S D R --- 26 D2466 PVC — Fittings — S c h e d u l e --- 4 0 D2468 ABS — Fittings — S c h e d u l e --- 4 0 D2564 For PVC — — Solvent Cement For PVC D2661 ABS Pipe Fittings — DWV at Schedule---40 IPS sizes D2665 PVC Pipe Fittings — DWV
F438 CPVC — Fittings — S ch e d u l e --- 4 0 F441 CPVC Pipe — — S c h e d u l e --- 40 F442 CPVC Pipe — — SDR F493 For CPVC — — Solvent Cement For CPVC
F628 ABS Pipe — —
F656 For PVC — — Primer For PVC F891 PVC Pipe — — Cellular Core Schedule ---40 & DWV
!
CAUTION
MATERIAL
PIPE
FITTINGS
UNIT MAY NOT OPERATE
Failure to follow this caution may result in intermittent unit operation.
When vent pipe is exposed to temperatures below freezing, such as when it passes through an unheated space or when a chimney is used as a raceway, pipe must be insulated as shown in Table 7 with Armaflex--type insulation.
FURNACE
NOT IN HORIZONTAL SECTION
PIPE DIAMETER
TRANSITION IN
VERTICAL SECTION
A93034
Fig. 24 --- Combustion-- Air and Vent Pipe Diameter
Transition Location and Elbow Configuration
Furnace combustion air and vent pipe connections are sized for 2--in. pipe. Any pipe size change should be made outside furnace casing in vertical pipe. The transition has to be made as close to the furnace as reasonably possible. (See Fig. 24.)
Installation Guidelines for Combustion Air Pipe and Vent Pipe
It is recommended that all pipes be cut, prepared, and preassembled before permanently cementing any joint.
1. Attach combustion air pipe and vent pipe per instructions in sections “Combustion Air Pipe” and “Vent Pipe.”
2. Working from furnace to outside, cut pipe to required length(s).
3. Deburr inside and outside of pipe.
SOLVENT CEMENT AND
PRIMERS
Cellular Core DWV at Schedule --- 40
DESCRIPTION
IPS sizes
4. Chamfer outside edge of pipe for better distribution of primer and cement.
5. Clean and dry all surfaces to be joined.
6. Check dry fit of pipe and mark insertion depth on pipe.
7. After pipes have been cut and preassembled, apply generous layer of cement primer to pipe fitting socket and end of pipe to insertion mark. Quickly apply approved cement to end of pipe and fitting socket (over primer). Apply cement in a light, uniform coat on inside of socket to prevent buildup of excess cement. Apply second coat.
8. While cement is still wet, twist pipe into socket with 1/4 turn. Be sure pipe is fully inserted into fitting socket.
9. Wipe excess cement from joint. A continuous bead of cement will be visible around perimeter of a properly made joint.
10. Handle pipe joints carefully until cement sets.
11. Horizontal portions of the venting system shall be supported to prevent sagging. Support combustion air piping (if applicable) and vent piping a minimum of every 5ft(3ftforSDR--21or--26PVC)usingperforatedmetal hanging strap.
12. Slope combustion air piping (if applicable) and vent piping downward towards furnace a minimum of 1/4--in. per linear ft with no sags between hangers.
13. Horizontal portions of the venting system shall be installed so as to prevent the accumulation of condensate.
14. Use appropriate methods to seal openings where combustion air pipe (if applicable) and vent pipe pass through roof or sidewall.
Combustion--Air and Vent Pipe Diameter
Determine combustion--air and vent pipe diameter.
1. Using Table 8, individually determine the diameter of the combustion--air and vent pipe allowed. If different, pick the larger of these two diameters and use this diameter for both combustion--air and vent pipes.
2. When installing vent systems of short pipe length, use the smallest allowable pipe diameter. Do not use pipe size greater than required or incomplete combustion, flame disturbance, or flame sense lockout may occur.
NOTE: Do not count elbows or pipe sections in terminations or within furnace.
58UVB
19
Page 20
NOTE: A 2 --in. diameter pipe must be used within furnace
-
casing. Make all pipe diameter transitions outside furnace casing. (See Fig. 24).
!
CAUTION
NOTE:
Select 1 vent pipe connection and 1 combustion-air pipe connection.
AIR
COMBUSTION-
AIR
VENT
FLOW
COMBUSTION
AIR
UNIT MAY NOT OPERATE
VENT
Failure to follow this caution may result in incomplete combustion, flame disturbance, or flame sense lockout.
When installing combustion air and vent system of short pipe length, the smallest allowable pipe diameter must be used.
UPFLOW
!
CAUTION
A06500
Fig. 25 --- Combustion Air and Vent Pipe Connections
UNIT CORROSION HAZARD
Excessive exposure to contaminated combustion air may
58UVB
result in safety and performance related problems. Combustion air must not be taken from inside structure because that air is frequently contaminated by halogens, which include fluorides, chlorides, bromides, and iodides. These elements are found in aerosols, detergents, bleaches, cleaning solvents, salts, air fresheners, adhesives, paint, and other household products. Locate combustion--air inlet as far as possible from swimming pool and swimming pool pump house.
Attachment of Combustion Air Pipe
NOTE: Combustion air pipe system has the same diameter and
same length as the vent pipe as mentioned in section “Combustion-- Air and Vent Pipe Diameter.”
1. Determine location of combustion--air intake pipe connection to combustion--air intake housing as shown in Fig. 25.
2. Verify combustion--air intake housing plug fitting is installed in appropriate unused intake housing connection.
3. Install combustion--air pipe grommet (factory-- supplied in
EXAMPLE:
An 100,000 BTUH furnace located in Indianapolis, elevation 650 ft above sea level, could be installed as either a direct vent/2--pipe system that requires 3 elbows and 28 ft of vent pipe, along with 5 elbows and 34 ft of combustion--air pipe. Table 8 indicates this application would allow a 2--in. diameter vent pipe, but require a 2--1/2 in. diameter combustion air pipe. According to Table 8, 2--in. diameter pipe is good for 35 ft with 3 elbows, but only 25 ft with 5 elbows. Therefore, 2--1/2 in. diameter pipe must be used for both vent and combustion air pipes since larger required diameter must always be used for both pipes. If same installations were in Albuquerque, elevation 5250 ft above sea level: Table 8 indicates that 2--1/2 in. diameter vent pipe and combustion--air pipe are required. If same applications are to be installed at 5001-- to 6000 ft elevation: 2--in. pipe is only good for 23 ft (with 3 elbows) and 13
loose parts bag) into selected furnace casing combustion--air pipe hole.
4. Determine the number of combustion air disk halves to be installed in the combustion air intake housing. Insert perforated disk half or assembly (factory supplied in loose parts bag) in intake housing where combustion--air intake pipe will be connected.
5. Insert assembled combustion air inlet pipe into intake housing as shown in Fig. 25.
NOTE: Do not cement combustion air intake pipe permanently to combustion air intake housing since it may be necessary to remove pipe for service of igniter or flame sensor.
6. Drill a 1/8--in. hole in 2-- in, combustion air pipe using the hole in intake housing as a guide.
7. Install a field--supplied No. 6 or No. 8 sheet metal screw into combustion air pipe.
8. Install casing hole filler cap (factory--supplied in loose parts bag) in unused combustion air pipe casing hole.
ft (with 5 elbows). Therefore, 2--1/2 in. diameter combustion air and vent pipe must be used.
3/8" ID TUBE
COMBUSTION AIR INTAKE HOUSING
BURNER BOX
COMBUSTION AIR
PIPE
General
Furnace combustion-- air connection must be attached as shown in Fig. 25. Combustion-- air intake housing plug may need to be relocated in some applications.
NOTE: All pipe joints must be cemented except attachment of combustion--air pipe to inlet housing connection, since it may be necessary to remove pipe for servicing.
NOTE: A 2--in. diameter pipe must be used within the furnace casing. Make all pipe diameter transitions outside furnace casing. (See Fig. 24).
20
3/16"
DRILL
TRAP
4″
MIN
TO OPEN
DRAIN
Fig. 26 --- Intake Housing Plug Fitting Drain
COMBUSTION AIR PIPE
A93035
Page 21
Fig. 27 --- Attic Termination
58UVB
A06497
Attachment of Combustion Air Intake Housing Plug Fitting
The combustion-- air intake plug fitting must be installed in unused combustion air intake housing. This fitting must be attached by using RTV sealant, or by drilling a 1/8--in. hole in fitting, using hole in intake housing as a guide. Install a field--supplied No. 6 or No. 8 sheet metal screw.
NOTE: DO NOT OVERTIGHTEN SCREW. Breakage of intake housing or fitting may cause air leakage to occur.
A plugged drain connection has been provided on this fitting for use when moisture is found in combustion air intake pipe and combustion box.
If use of this drain connection is desired, drill out fitting’s tap plug with 3/16--in. drill and connect a field-- supplied 3/8--in. tube. This tube should be routed to open condensate drain for furnace and A/C (if used), and should be trapped, as shown in Fig. 26.
!
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in unit component damage.
Inducer housing outlet cap must be installed and fully seated against inducer housing. Clamp must be tightened to prevent any condensate leakage.
NOTE: (Direct Vent/2--Pipe System ONLY). Moisture in combustion air intake may be a result of improper termination. Ensure combustion air pipe termination is similar to those as shown in Fig. 31 so that it will not be susceptible to area where light snow or others sources of moisture could be pulled in.
21
Page 22
Combustion Air Termination-- Ventilated Combustion Air Option
Combustion air is piped directly to the burner box on furnace using the same materials used to vent the furnace. (See Table 5.) The combustion air pipe is terminated in an attic or crawl space that is well ventilated with outdoor air and is well isolated from the living space or garage. If the furnace is installed in a well ventilated attic, the combustion air pipe can be terminated in the same space. Refer to the Air for Combustion and Ventilation -­Ventilated Combusion Air Option Section in these instructions.
The combustion air pipe cannot be terminated in attics or crawlspaces that use ventilation fans designed to operate during the heating season. If ventilation fans are present in these areas, the combustion air pipe must terminate outdoors as a Direct Vent/2--Pipe system.
NOTE: Combustion air pipe must have the same diameter as vent pipe.
Attic terminations require at least (1) 90 degree elbow, with the open end pointing horizontally or downward. The open end of the elbow must be at least 12--inches above any insulation or
58UVB
other materials. Screen the elbow with a wire mesh screen no smaller than 3/8--inch square. (See Fig. 27.)
Crawlspace termination requires the open end of the pipe pointing downward. Maintain 3 -- inches of clearance below the floor joist insulation and 12--inches above the grade. Screen the elbow with a wire mesh screen no smaller than 3/8--inch square. (See Fig. 28 and 29.)
AIR FOR COMBUSTION AND VENTILATION -­Ventilated Combustion Air Option
Provisions for adequate combustion, ventilation, and dilution air must be provided in accordance with:
U.S. Installations: Section 9.3 of the NFGC, Air for Combustion and Ventilation and applicable provisions of the local building codes.
Canadian Installations: Part 7 of the NSCNGPIC, V enting Systems and Air Supply for Appliances and all authorities having jurisdiction.
!
CARBON MONOXIDE POISONING HAZARD
Failure to supply outdoor air via grilles, louvers or vents could result in death and/or personal injury. Many homes require air to be supplied from outdoors for furnace combustion, ventilation, and dilution of flue gases.
The furnace combustion air supply must be provided in accordance with this instruction manual.
An attic or crawlspace may be considered a space that freely communicates with the outdoors provided there are adequate permanent ventilation openings directly to outdoors having free area of at least 1-- in.2/4,000 Btuh of total input rating for all gas appliances in the space.
NOTE: In determining the free area of an opening, the blocking effect of the louvers, grilles, and screens must be considered. If the free area of a louver or grille design is unknown, it may be assumed that wood louvers have a 20 percent free area, and metal louvers or grilles have a 60 percent free area. Screens, when used, must not be smaller than 1/4 --in. mesh. Louvers and grilles must be constructed so they cannot be closed.
WARNING
!
UNIT CORROSION HAZARD
Air for combustion must not be contaminated by halogen compounds, which include fluoride, chloride, bromide, and iodide. These elements may corrode heat exchangers and shorten furnace life. Air contaminants are found in aerosol sprays, detergents, bleaches, cleaning
This furnace requires OUTDOOR AIR for combustion.
!
CARBON MONOXIDE POISONING HAZARD
The operation of exhaust fans, kitchen ventilation fans, clothes dryers, attic exhaust fans or fireplaces could create a NEGATIVE PRESSURE CONDITION at the furnace. Make--up air MUST be provided for the ventilation devices, in addition to that required by the furnace. Refer to the Carbon Monoxide Poisoning Hazard warning in the venting section of these instructions to determine if an adequate amount of make--up air is available.
WARNING
WARNING
22
Page 23
Fig. 28 --- Crawlspace Termination
58UVB
A06495
A06496
Fig. 29 --- Crawlspace Termination
23
Page 24
COMBUSTION AIR TERMINA VENT/2--PIPE
Combustion air pipe must terminate outside the structure with the vent pipe as shown in Fig. 31. Follow the clearance requirements show in Fig. 34. Refer to Vent Termination section for complete details on termination options.
PIPE
VENT
General
Furnace vent connection must be attached as shown in Fig. 25.
CARBON MONOXIDE POISONING AND PROPERTY DAMAGE HAZARD
Failure to follow this warning could result in property damage, personal injury, or death.
Vent pipes must be airtight.
NOTE: A 2--in. diameter pipe must be used within the furnace
58UVB
casing. Make all pipe diameter transitions outside furnace casing per Fig. 24.
The minimum vent pipe length for these furnaces is 5 ft. Short pipe lengths (5--8 ft) may discharge condensate droplets. These condensate droplets may be undesirable. A 12--in. minimum offset pipe section is recommended to reduce excessive condensate droplets from exiting vent pipe outlet. (See Fig. 30.)
Attachment of Vent Pipe
NOTE: Vent pipe system has the same diameter and same length
as combustion air pipe as mentioned in section “Combustion Air Pipe and Vent Pipe Diameter.”
UNIT DAMAGE HAZARD
Failure to follow this caution may result in unit component damage.
Vent pipe must be installed and fully seated against inducer housing. Clamp must be tightened to prevent any condensate leakage.
1. Determine location of vent pipe connection to inducer housing as shown in Fig. 25 for application.
2. Verify synthetic rubber inducer housing outlet cap and clamp are installed on appropriate unused inducer housing connection and that clamp is tight.
3. Install combustion--air pipe grommet (factory-- supplied in loose parts bag) into selected furnace casing vent pipe hole. (See Fig. 18.)
4. Be certain that mating surfaces of inducer housing connection synthetic rubber coupling, and 2 -- in. diameter vent pipe are clean and dry. Assemble the synthetic rubber vent coupling (with 2 loose clamps) onto inducer housing connection. Insert the 2--in. diameter vent pipe through the synthetic rubber coupling and fully into inducer housing connection until it touches a stop inside the inducer housing outlet. Tighten the screws on both clamps to 15--in--lb. of torque.
NOTE: Starting at furnace, slope vent pipe a minimum of 1/4--in. per linear ft back toward furnace with no sags between hangers.
SYSTEM
!
!
WARNING
CAUTION
TION--DIRECT
5. Install casing hole filler cap (factory--supplied in loose parts bag) in unused vent pipe casing hole.
VENT TERMINA
General
Combustion--air (direct vent/2--pipe system only) and vent pipe must terminate outside structure, either through sidewall or roof. For vent termination clearance, refer to Fig. 34 for Direct Vent/2--Pipe system and Fig. 35 for Ventilated Combustion Air option.
Roof termination is preferred since it is less susceptible to damage or contamination, and it has less visible vent vapors. Sidewall termination require sealing or shielding of building surfaces with a corrosive resistance material due to corrosive combustion products of vent system.
NOTE: (Direct Vent/2--Pipe system ONLY) A factory accessory termination kit MUST be used. See section “V ent Termination Kit (Direct Vent/2--Pipe System Only)” in this instruction.
When determining appropriate location for termination, consider the following guidelines:
1. Comply with all clearance requirements stated in Fig. 34 or Fig. 35 per application.
2. Termination or termination kit should be positioned where vent vapors will not damage plants/shrubs or air conditioning equipment.
3. Termination or termination kit should be positioned so that it will not be affected by wind eddy, such as inside building corners, nor by recirculation of flue gases, airborne leaves, or light snow.
4. Termination or termination kit should be positioned where it will not be damaged by or subjected to foreign objects such as stones, balls, etc.
5. Termination or termination kit should be positioned where vent vapors are not objectionable.
Extended Exposed Sidewall Pipes
Sidewall combustion air pipe termination (direct vent/2--pipe system only) and vent pipe termination may be extended beyond areashowninFig.31orinFig.32perapplicationinoutside ambient by insulating pipe as indicated in Table 7.
1. Determine combustion air pipe diameter (direct vent/2--pipe system only) and vent pipe diameter, as stated above, using total pipe length and number of elbows.
2. Using winter design temperature (used in load calculations), find appropriate temperature for your application and furnace model.
3. Determine required insulation thickness for exposed pipe length(s).
NOTE: Pipe length(ft) specified for maximum pipe lengths located in unconditioned spaces cannot exceed total allowable pipe length as specified in Table 8.
Vent Termination Kit (Direct Vent/2--Pipe System Only)
NOTE: Always refer to the instructions in termination kit for the
latest version.
Combustion air and vent pipes MUST terminate outside structure. A factory accessory termination kit must be installed as shown in Table 6. There are four options of vent/combustion air termination kits available as shown in Table 6.
TION
24
Page 25
V
COMBUSTION-AIR PIPE
COMBUSTION-AIR PIPE
ERTICAL TO ROOF
Vertical separation between combustion air and vent 8 3/4 in. for 3 in. kit 6 3/4 in. for 2 in. kit
VENT PIPE
12″ MIN
VERTICAL TO SIDEWALL
NOTE: A 12 In. minimum offset pipe section is recommended with
short (5 to 8 ft) vent systems. This recommendation is to reduce excessive condensate droplets from exiting the vent pipe.
Fig. 30 --- Short Vent (5 to 8 Ft) System
Roof Termination (Preferred)
At least 36 in.
A
18 in. maximum
Concentric Vent and Combustion Air Roof Termination (preferred)
12″ MIN
VENT PIPE
At least
36 in.
A
Maintain 12
in.
min. clearance above highest anticipated snow level, maximum of 24 in. above roof
A06356
58UVB
Maintain 12 in. min. clearance above highest anticipated snow level Maximum of 24 in. above roof
Note: "A" denotes 0 to < 2 in. Between the first 2 vents Third vent must be > 36 in. away
Abandoned masonry used as raceway (per code)
12
in.
min from
overhang or roof
(typ)
A
separation
in.
At least 36 in.
Side wall termination
of less than 12
in.
90°
At least 36 in
A
.
12 between bottom of combustion air and bottom of vent (typ)
Maintain 12 min. clearance above highest anticipated snow level or grade whichever is greater (typ)
Fig. 31 --- Combustion Air and Vent Pipe Termination
for Direct Vent (2--pipe) System (All Sizes)
in.
above highest snow level
1
in.
A
t lea
3
st
6
in.
Concentric Vent and Combustion - Air Side Termination
maximum (typ) from wall to inlet
12
in.
minimum from
overhang or roof
A
in.
Maintain 12 min. clearance above highest anticipated snow level or grade whichever is greater
A05090
25
Page 26
Roof Termination (Preferred)
Vent
Maintain 12 in.
minimum clearance
above highest anticipated
snow level maximum of
24 in. above roof.
Abandoned masonry used as raceway (per code)
12 in. min. from
6 in. minimum clearance
between wall and end of vent pipe.
10 in. maximum pipe length
12 in. min. from
overhang or roof
58UVB
90°
Side wall termination with 2 elbows (preferred)
Maintain 12 in. minimum clearance above highest anticipated snow level or grade whichever is greater.
overhang or roof
Sidewall Termination
with Straight Pipe (preferred)
Maintain 12 in. minimum clearance above highest anticipated snow level or grade whichever is greater
A05091
Fig. 32 --- Vent Pipe Termination for Ventilated Combustion Air (1--pipe) System (All Sizes)
TABLE 6 —VENT TERMINATION KIT FOR DIRECT VENT/2--PIPE SYSTEM
DIRECT VENT (2--- PIPE) TERMINATION KIT TERMINATION SYSTEM
2---in. Concentric Vent Kit Single Penetration of Wall or Roof 1, 1--- 1/2, 2, or 2 --- 1/2 3---in. Concentric Vent Kit Single Penetration of Wall or Roof 2 ---1/2, 3 2---in . Termination Bracket Kit 2---Pipe Termination System 1, 1 ---1/2 or 2 3---in . Termination Bracket Kit 2---Pipe Termination System 2--- 1/2, 3
DIAM. OF COMBUSTION AIR AND VENT
PIPES (IN INCHES)
TABLE 7—MAXIMUM ALLOWABLE EXPOSED VENT PIPE LENGTH (FT) WITH INSULATION IN WINTER DESIGN
TEMPERATURE AMBIENT*
UNIT SIZE
WINTER DESIGN
TEMPERATURE (°F)
20 2 30 55 61 70 70
060 --- 14
0 2 16 33 38 46 53
--- 2 0 2 9 23 26 33 38
080 --- 14 080 --- 20
20 2 37 65 70 70 70
0 2 20 39 45 55 63
--- 2 0 2 11 27 31 39 45 20 2 --- 1 / 2 41 70 70 70 70
100 --- 20
0 2 --- 1 / 2 21 42 48 59 68
--- 2 0 2 --- 1 / 2 11 28 33 41 49 20 3 49 70 70 70 70
120 --- 20
* Pipe length (ft) specified for maximum pipe lengths located in unconditioned spaces. Pipes located in unconditioned space cannot exceed total allowable pipe
length as specified in Table 6.
{ Insulation thickness based on R value of 3.5 per in.
0 3 26 51 58 70 70
--- 2 0 3 15 35 40 50 59
MAXIMUM PIPE DIAMETER (IN.)
INSULATION THICKNESS (IN.)†
0 3/8 1/2 3/4 1
NOTE: Combustion air pipe must have the same diameter as vent pipe.
Concentric Vent/Combustion Air Termination Kit (Direct Vent/2--Pipe System Only)
Determine an appropriate location for termination kit using the guidelines provided in section “Vent Termination: General” in this instruction.
1. Cut one 4--in. diameter hole for 2--in. kit, or one 5--in. diameter hole for 3-- in. kit.
2. Loosely assemble concentric vent/combustion air termination components together using instructions in kit.
3. Slide assembled kit with rain shield REMOVED through hole.
NOTE: Do not allow insulation or other materials to accumulate inside of pipe assembly when installing it through hole.
26
Page 27
Roof terminations--Locate assembly through roof to
(
appropriate height as shown in Fig. 31 and 32. Sidewall terminations-- Locate assembly through
sidewall with rain shield positioned no more than 1--in. from wall as shown in Fig. 31 and 32.
4. Disassemble loose pipe fittings. Clean and cement using same procedures as used for system piping.
5. Check required dimensions as shown.
Two--Pipe Termination Kit (Direct Vent/2-- Pipe System Only
Determine an appropriate location for termination kit using the guidelines provided in section “Vent Termination: General” in this instruction.
1. Cut 2 holes, 1 for each pipe, of appropriate size for pipe size being used.
2. Loosely install elbow in bracket and place assembly on combustion--air pipe.
Roof terminations--Loosely install pipe coupling on properly cut vent pipe. Coupling must be positioned so bracket will mount as shown in Fig. 31. For applications using combustion-- air pipe option,
CONTINUOUS FAN
(CF) AIRFLOW
SETUP SWITCHES
MODEL PLUG
CONNECTOR
SW1 SETUP
SWITCHES AND
BLOWER OFF-
DELAY
COMMUNICATION
CONNECTOR
indicated by dashed lines in Fig. 31, install 90_ street elbow into 90_ elbow, making a U--fitting. A 180_ U--fitting may be used.
Sidewall terminations--Install bracket as shown in Fig.
31. For applications using vent pipe option indicated by dashed lines in Fig. 31, rotate vent elbow 90_ from position shown in Fig. 31.
3. Disassemble loose pipe fittings. Clean and cement using same procedures as used for system piping.
4. Check required dimensions as shown in Fig. 31.
Multiventing and Vent Terminations
When 2 or more 58UVB Furnaces are vented near each other, each furnace must be individually vented. NEVER common vent or breach vent 58UVB furnaces. (Direct Vent/2--Pipe System ONLY)--When 2 or more 58UVB furnaces are vented near each other, 2 vent terminations may be installed as shown in Fig. 31, but next vent termination must be at least 36 in. away from first 2 terminations. It is important that vent terminations be made as shown in Fig. 31 to avoid recirculation of flue gases.
FUTURE
APPLICATIONS
58UVB
AIR CONDITIONING
(A/C) AIRFLOW
SETUP SWITCHES
24-V THERMOSTAT
TERMINALS
STATUS AND COMM
LED LIGHTS
3-AMP FUSE
TRANSFORMER 24-VAC
CONNECTIONS
115-VAC (L2) NEUTRAL
CONNECTIONS
PL1 LOW VOLTAGE MAIN
HARNESS CONNECTOR
EAC-1 TERMINAL
115-VAC 1.0 AMP MAX.)
Fig. 33 --- Control Center
115-VAC (L1) LINE
VOLTAGE CONNECTIONS
HUMIDIFIER
TERMINAL (24-VAC
0.5 AMP MAX.
ACRDJ AIR
CONDITIONING
RELAY DISABLE
JUMPER
FLASH
UPGRADE
CONNECTOR
(FACTORY
ONLY)
PL3 ECM BLOWER
HARNESS
CONNECTOR
DATE CODE XXXXN
PL2 HOT SURFACE IGNITER & INDUCER
MOTOR CONNECTOR
A06494
27
Page 28
58UVB
A05009
Fig. 34 --- Direct Vent Termination Clearance
28
Page 29
58UVB
Fig. 35 --- Other than Direct Vent Termination Clearance
A05013
29
Page 30
TABLE 8—MAXIMUM ALLOWABLE PIPE LENGTH (FT)
ALTITUDE
0 to 2000
ALTITUDE
2001 to 3000
58UVB
ALTITUDE
3001 to 4000
ALTITUDE
4001 to 5000‡
ALTITUDE
5001 to 6000‡
See notes on page 24
UNIT SIZE
(BTUH)
60,000
80,000
100,000
120,000
UNIT SIZE
(BTUH)
60,000
80,000
100,000
120,000
UNIT SIZE
(BTUH)
60,000
80,000
100,000
120,000
UNIT SIZE
(BTUH)
60,000
80,000
100,000
120,000
UNIT SIZE
(BTUH)
60,000
80,000
100,000
120,000
Termination
Type
2 P i p e o r 2 --- I n . Concentric
2 P i p e o r 2 --- I n . Concentric
2 P i p e o r 2 --- I n . Concentric
2 P i p e o r 3 --- I n . Concentric
Termination
Type
2 P i p e o r 2 --- I n . Concentric
2 P i p e o r 2 --- I n . Concentric
2 P i p e o r 2 --- I n . Concentric
2 P i p e o r 3 --- I n . Concentric
Termination
Type
2 P i p e o r 2 --- I n . Concentric
2 P i p e o r 2 --- I n . Concentric
2 P i p e o r 2 --- I n . Concentric
2 P i p e o r 3 --- I n . Concentric
Termination
Type
2 P i p e o r 2 --- I n . Concentric
2 P i p e o r 2 --- I n . Concentric
2 P i p e o r 2 --- I n . Concentric
2 P i p e o r 3 --- I n . Concentric
Termination
Type
2 P i p e o r 2 --- I n . Concentric
2 P i p e o r 2 --- I n . Concentric
2 P i p e o r 2 --- I n . Concentric
2 P i p e o r 3 --- I n . Concentric
Pipe Dia
(IN.)*
1 --- 1 / 2 50 45 40 35 30 25
2 70 70 70 70 70 70
1 --- 1 / 2 30 25 20 15 10 5
2 70 70 70 70 70 70 2 45 40 35 30 25 20
2 --- 1 / 2 70 70 70 70 70 70
2 --- 1 / 2 o n e d i s k 10 NA NA NA NA NA
3onedisk 35 30 15 NA NA NA
3onedisk† 70 70 70 70 70 70
Pipe Dia
(IN.)*
1 --- 1 / 2 45 40 35 30 25 20
2 70 70 70 70 70 70
1 --- 1 / 2 26 21 16 11 6 NA
2 70 70 70 70 70 70 2 40 35 30 25 20 15
2 --- 1 / 2 70 70 70 70 70 70
3onedisk 31 26 12 NA NA NA
3onedisk† 63 62 62 61 61 61
Pipe Dia
(IN.)*
1 --- 1 / 2
2 70 70 70 70 70 70
1 --- 1 / 2 25 20 15 10 5 NA
2 70 70 70 70 70 70 2 38 33 28 23 18 13
2 --- 1 / 2 70 70 70 70 70 70
3onedisk 29 24 10 NA NA NA
3onedisk† 59 59 58 57 57 56
Pipe Dia
(IN.)*
1 --- 1 / 2 40 35 30 25 20 15
2 70 70 70 70 70 70
1 --- 1 / 2 23 18 13 8 NA NA
2 70 70 70 70 70 68 2 36 31 26 21 16 11
2 --- 1 / 2 70 70 70 70 70 70
3onedisk† 56 55 54 53 52 52
Pipe Dia
(IN.)*
1 --- 1 / 2 37 32 27 22 17 12
2 70 70 70 70 70 70
1 --- 1 / 2 22 17 12 7 NA NA
2 70 70 70 70 68 63 2 33 28 23 18 13 8
2 --- 1 / 2 70 70 70 70 70 70
3onedisk† 53 52 50 49 48 47
NUMBER OF 90_ ELBOWS
1 2 3 4 5 6
NUMBER OF 90_ ELBOWS
1 2 3 4 5 6
NUMBER OF 90_ ELBOWS
1 2 3 4 5 6
42 37 32 27 22
NUMBER OF 90_ ELBOWS
1 2 3 4 5 6
NUMBER OF 90_ ELBOWS
1 2 3 4 5 6
17
30
Page 31
TABLE 8 — MAXIMUM ALLOWABLE PIPE LENGTH (FT) (CONTINUED)
ALTITUDE
UNIT SIZE
(BTUH)
60,000
80,000
6001 to 7000‡
100,000
120,000
ALTITUDE
UNIT SIZE
(BTUH)
60,000
80,000
7001 to 8000‡
100,000
120,000
ALTITUDE
UNIT SIZE
(BTUH)
60,000
80,000
8001 to 9000‡
100,000
120,000
ALTITUDE
UNIT SIZE
(BTUH)
60,000
9001 to 10000‡
80,000
100,000
120,000
* Disk usage -- -Unless otherwise stated, use perforated disk assembly (factory---su pplied in loose parts bag).
{ Wide radius elbow. } Vent sizing for Canadian installations over 4500 ft (1370m) above sea level are subject to acceptance by the local authorities having jurisdiction.
NA---Not Allowed; pressure switch will not make.
NOTES:
1. Do not use pipe size greater than those specified in table or incomplete combustion, flame disturbance, or flame sense lockout may occur.
2. Size both the combustion ---air and vent pipe independently, determine the smallest diameter allowed by the table for each pipe, then use the larger diameter for both pipes.
3. Assume two 45_ elbows equal one 90_ elbow. Long radius elbows are desirable and may be required in some cases.
4. Elbows and pipe sections within the furnace casing and at the vent termination should not be included in vent length or elbow count.
5. The minimum pipe length is 5 ft for all applications.
Termination
Type
2 P i p e o r 2 --- I n . Concentric
2 P i p e o r 2 --- I n . Concentric
2 P i p e o r 2 --- I n . Concentric
2 P i p e o r 3 --- I n . Concentric
Termination
Type
2 P i p e o r 2 --- I n . Concentric
2 P i p e o r 2 --- I n . Concentric
2 P i p e o r 2 --- I n . Concentric
2 P i p e o r 3 --- I n . Concentric
Termination
Type
2 P i p e o r 2 --- I n . Concentric
2 P i p e o r 2 --- I n . Concentric
2 P i p e o r 2 --- I n . Concentric
2 P i p e o r 3 --- I n . Concentric
Termination
Type
2 P i p e o r 2 --- I n . Concentric
2 P i p e o r 2 --- I n . Concentric
2 P i p e o r 2 --- I n . Concentric
2 P i p e o r 3 --- I n . Concentric
Pipe Dia
(IN.)*
NUMBER OF 90_ ELBOWS
1 2 3 4 5 6
1 --- 1 / 2 35 30 25 20 15 10
2 70 70 68 67 66 64
1 --- 1 / 2 20 15 10 5 NA NA
2 70 70 68 67 62 57 2 31 26 21 16 11 6
2 --- 1 / 2 70 70 68 67 66 64
3onedisk† 49 48 47 45 44 43
Pipe Dia
(IN.)*
NUMBER OF 90_ ELBOWS
1 2 3 4 5 6
1 --- 1 / 2 32 27 22 17 12 7
2 66 65 63 62 60 59
1 --- 1 / 2 18 13 8 NA NA NA
2 66 65 63 62 57 52 2 29 24 19 14 9 NA
2 --- 1 / 2 66 65 63 62 60 59
3onedisk† 46 44 43 41 40 38
Pipe Dia
(IN.)*
NUMBER OF 90_ ELBOWS
1 2 3 4 5 6
1 --- 1 / 2 30 25 20 15 10 5
2 62 60 58 56 55 53
1 --- 1 / 2 17 12 7 NA NA NA
2 62 60 58 56 51 46 2 27 22 17 12 7 NA
2 --- 1 / 2 62 60 58 56 55 53
3onedisk† 43 41 39 37 35 34
Pipe Dia
(IN.)*
NUMBER OF 90_ ELBOWS
1 2 3 4 5 6
1 --- 1 / 2 27 22 17 12 7 NA
2 57 55 53 51 49 47
1 --- 1 / 2 15 10 5 NA NA NA
2 57 55 53 51 46 41 2 24 19 14 9 NA NA
2 --- 1 / 2 57 55 53 51 49 47
3onedisk† 39 37 35 33 31 29
58UVB
31
Page 32
Step 10 —Condensate Drain
GENERAL
Condensate trap is shipped installed in the blower shelf. Condensate trap can be RELOCATED to the side of the casing.
Condensate trap MUST be used for all applications. An external trap is not required when connecting the field drain
to this condensate trap. The field drain connection (condensate trap or drain tube
coupling) is sized for 1/2--in. CPVC, 1/2--in. PVC, or 5/8--in. ID tube connection.
Drain pipe and fittings must conform to ANSI standards and ASTM D1785, D2466, or D2846. CPVC or PVC cement must conform to ASTM D2564 or F493. Primer must conform to ASTM F656. In Canada, use CSA or ULC certified schedule 40 CPVC or PVC drain pipe, fittings, and cement.
When a condensate pump is required, select a pump which is approved for condensing furnace applications. To avoid condensate spillage, select a pump with an overflow switch.
Furnace condensate is mildly acidic, typically in the pH range of
58UVB
3.2 to 4.5. Due to corrosive nature of this condensate, a
condensate pH neutralizing filter may be desired. Check with local authorities to determine if a pH neutralizer is required.
APPLICA
The furnace, A/C, and humidifier drains may be combined and drained together. The A/C drain must have an external, field supplied trap prior to the furnace drain connection. All drain connections (furnace, A/C, or humidifier) must be terminated into an open or vented drain as close to the respective equipment as possible to prevent siphoning of the equipment’s drain.
See Fig. 37 for example of possible field drain attachment using 1/2--in. CPVC or PVC tee for vent and A/C or humidifier drain connection.
Outdoor draining of the furnace is permissible if allowed by local codes. Caution should be taken when freezing ambient may freeze drain pipe and prohibit draining.
TION
!
CAUTION
CONDENSATE DRAIN PROTECTION
Freezing condensate left in condensate trap and drain line may cause cracks, and possible water damage may occur. If freeze protection is required, use condensate freeze protection accessory or equivalent 3 to 6 watt per ft at 120v and 40_F self--regulating, shielded, and waterproof heat tape. See Installation Instructions supplied with accessory or heat tape manufacturer’s recommendations.
1. Fold heat tape in half and wrap on itself 3 times.
2. Locate heat tape between sides of condensate trap back. (See Fig. 38.)
3. Use wire ties to secure heat tape in place. Wire ties can be positioned in notches of condensate trap sides. (See Fig.
38.)
4. Wrap field drain pipe with remaining heat tape, approximately 1 wrap per ft.
5. When using field-- supplied heat tape, follow heat tape manufacturer’s instructions for all other installation guidelines.
32oF MINIMUM INSTALLED AMBIENT OR FREEZE PROTECTION REQUIRED
A93058
Fig. 36 --- Freeze Protection
UNIT MAY NOT OPERATE
Failure to follow this caution may result in intermittent unit operation.
Unit must not be installed, operated, and then turned and left off in an unoccupied structure during cold weather when temperature drops to 32_F or below unless drain trap and drain line have adequate freeze protection. See Service and Maintenance Instructions for winterizing procedure. (See Fig. 36.)
!
WARNING
PERSONAL INJURY HAZARD
Failure to follow this warning could result in property damage and personal injury or death.
Caution should be taken to prevent draining where slippery conditions may cause personal injuries. Excessive condensate draining may cause saturated soil conditions which may result in damage to plants.
OPEN STAND
PIPE FOR
A/C OR
HUMIDIFIER
DRAIN
TEE
TO OPEN DRAIN
Fig. 37 --- Example of Field Drain Attachment
A94054
32
Page 33
CONDENSATE TRAP
WIRE TIE(S)
HEAT TAPE
(3 WRAPS MINIMUM)
A93036
Fig. 38 --- Condensate Trap Heat Tape
START--UP , ADJUSTMENTS AND SAFETY
CHECK
Step 1 —General
1. Furnace must have a 115--v power supply properly connected and grounded.
NOTE: Proper polarity must be maintained for 115-- v wiring. If polarity is incorrect, control status indicator light flashes rapidly and furnace does not operate.
2. Thermostat wire connections at terminals R, W/W1, G, and Y/Y2 must be made at 24--v terminal block on furnace control.
3. Natural gas service pressure must not exceed 0.5 psig (14--in. wc), but must be no less than 0.16 psig (4.5--in. wc).
4. Blower access panel must be in place to complete 115--v electrical circuit to furnace.
!
CAUTION
UNIT MAY NOT OPERATE
Failure to follow this caution may result in intermittent unit operation or performance satisfaction.
These furnaces are equipped with a manual reset limit switch in burner box. This switch opens and shuts off power to the gas valve if an overheat condition (flame rollout) occurs in burner enclosure. Correct inadequate combustion--air supply or improper venting condition before resetting switch. DO NOT jumper this switch.
Before operating furnace, check flame rollout manual reset switch for continuity. If necessary, press button to reset switch.
Step 2 —Select Setup Switch Positions
AIR CONDITIONING (A/C) SETUP SWITCHES
The air conditioning setup switches are used to match furnace airflow to cooling unit used.
To set the desired cooling airflow:
1. Remove main furnace door and blower access panel.
2. Locate A/C setup switches on furnace control. (See Fig.
33.)
58UVB
33
Page 34
AIR CONDITIONING AIRFLOW* 060 & 080-14
TONS (12,000 BTU/HR) (CFM)
1-1/2 525 (600) X
2 700 (800) X X X
2-1/2 875 (1000) X X X
3 1050 (1200) X X X
3-1/2 1225 (1400) X X X
4 1400 (1600) X X
5 1750 (2000) X
6 2100 (2100) X
X-INDICATES AN ALLOWABLE SELECTION.
* Airflow shown in parentheses is airflow unit that the unit will deliver when setup switch SW1-5 is ON (selects 400 CFM/ton)
MODEL
080-20 & 100
MODEL
X
120 MODEL
MODEL
58UVB
SIZE
060,
080-14
080-20, 100 DEF 700 875 1050 1225 1400 1750
120 DEF 700 875
1.DEFAULT A/C AIRFLOW WHEN A/C SWITCHES ARE IN OFF POSITION
2.DEFAULT CONT. FAN AIRFLOW WHEN CF SWITCHES ARE IN OFF POSITION
DEF 525
Fig. 39 --- A/C or CF Airflow Selection Chart Based on 350 and 400CFM/Ton
3. Determine air conditioning tonnage used.
4. Use wiring schematic to determine proper setup position of A/C switches. (See Fig. 23 and 39.)
NOTE: Excessive airflow caused by improper A/C switch setup may cause condensate blowoff in cooling mode.
5. Replace main furnace door and blower access panel.
NOTE: EAC--1 terminal is energized whenever blower operates. HUM terminal is only energized when blower is energized in heating.
CONTINUOUS FAN (CF) SETUP
SWITCHES
The CF setup switches are used to select desired airflow when thermostat is in continuous fan mode or to select low--cooling airflow for two--speed cooling units. This setup feature allows continuous fan airflow or low-- cooling airflow to be adjusted. To set desired continuous fan airflow or low--cooling airflow:
1. Remove main furnace door and blower access panel.
2. Locate CF setup switches on furnace control. (See Fig.
33.)
3. Determine desired continuous fan airflow or low--cooling airflow.
4. Use wiring schematic to determine proper setup position of CF switches. (See Fig. 23 and 39.)
5. Replace main furnace door and blower access panel.
SETUP SWITCHES
(SW1)
The furnace control has 8 setup switches that may be set to meet the application requirements. Position these setup switches for the appropriate requirement.
1. Remove main furnace door and blower access panel.
A/C OR CF AIRFLOW SELECTION CHART
BASED ON 350 CFM/TON
700 875 105011225 1225 1225
2
2
1050 1225 1400 1750
2
2. Locate setup switches on furnace control. (See Fig. 33.)
3. See Table 9 for setup switch description. (See Fig. 23.))
4. Replace main furnace door and blower access panel.
NOTE: If a bypass humidifier is used, setup switch SW1--3 (Low HEAT Rise Adjust) should be in ON position. This compensates for the increased temperature in return air resulting from bypass.
NOTE: If modulating dampers are used, blower motor automatically compensates for modulating dampers.
Step 3 —Prime Condensate Trap With Water
!
UNIT MAY NOT OPERATE
Failure to follow this caution may result in intermittent unit operation or performance satisfaction.
Condensate trap must be PRIMED or proper draining may not occur. The condensate trap has 2 internal chambers which can ONLY be primed by pouring water into the inducer drain side of condensate trap.
1. Remove upper inducer housing drain connection cap. (See Fig. 41.)
2. Connect field-- supplied 1/2--in. ID tube to upper inducer housing drain connection.
3. Insert field--supplied funnel into tube.
4. Pour 1 quart of water into funnel/tube. Water should run through inducer housing, overfill condensate trap, and flow into open field drain. (See Fig. 42.)
1750
1
2100
1
CAUTION
A06508
34
Page 35
TABLE 9 —FURNACE SETUP SWITCH DESCRIPTION
SETUP SWITCH
NO.
S W 1 --- 1 Status Code Recovery OFF
S W 1 --- 2 Adaptive Heat Mode OFF
S W 1 --- 3 Low Heat Rise Adjust OFF
S W 1 --- 4 Comfort/Efficiency Adjustment ON
S W 1 --- 5 CFM per ton adjust OFF Turn ON for 400 CFM per ton. Turn OFF for 350 CFM per ton.
S W 1 --- 6 Component Self---Test OFF
S W 1 --- 7 Blower OFF delay ON or OFF
S W 1 --- 8 Blower OFF delay ON or OFF
SWITCH NAME
NORMAL
POSITION
DESCRIPTION OF USE
Turn ON to retrieve up to 7 stored status codes for troubleshooting assistance when R thermostat lead is disconnected.
Allows 2 ---stage operation with a single stage thermostat. Turn ON
when using 2 stage thermostat to allow Low Heat operation when
R to W/W1 closes and High Heat operation when R to W/W1 and
Turn ON to increase Low Heat airflow by 10 percent. This com-
pensates for increased return air temperature caused with bypass
Turn ON to decrease Low Heat airflow by 22 percent and High
Heat airflow 15 percent for maximum comfort.
Turn ON to initiate Component Self--- Test for troubleshooting as-
sistance when R thermostat lead is disconnected. Turn OFF when
Control blower Off Delay time. Used in conjunction with SW1--- 8. See Table 10.
Control blower Off Delay time. Used in conjunction with SW1--- 7. See Table 10.
!
UNIT MAY NOT OPERATE
Failure to follow this caution may result in intermittent unit operation.
Furnace control must be grounded for proper operation, or control will lock out. Control is grounded through green/yellow wire routed to gas valve and burner box screw.
W2 close.
humidifier.
Self--- Test is completed.
CAUTION
58UVB
A04001
Fig. 40 --- Example of Setup Switch in Off Position
5. Remove funnel and tube from inducer housing and replace drain connection cap and clamp.
Step 4 —Purge Gas Lines
If not previously done, purge the lines after all connections have been made and check for leaks.
!
FIRE AND EXPLOSION HAZARD
Failure to follow this warning could result in a fire, explosion, personal injury, or death.
Never purge a gas line into a combustion chamber. Never test for gas leaks with an open flame. Use a commercially available soap solution made specifically for the detection of leaks to check all connections.
WARNING
Step 5 —Sequence of Operation
Using schematic diagram, follow sequence of operation through different modes. (See Fig. 23.) Read and follow wiring diagram carefully.
NOTE: If a power interruption occurs during a call for heat (W/W1 or W/W1--and--W2), the control will start a 90--second blower--only ON period two seconds after power is restored, if the thermostat is still calling for gas heating. The amber LED light will flash code 12 during the 90--second period, after which the LED will be ON continuous, as long as no faults are detected. After the 90 -- second period, the furnace will respond to the thermostat normally.
The blower door must be installed for power to be conducted through the blower door interlock switch ILK to the furnace control CPU, transformer TRAN, inducer motor IDM, blower motor BLWM, hot--surface igniter HSI, and gas valve GV.
SINGLE--STAGE THERMOSTAT AND TWO--ST HEATING (ADAPTIVE
See Fig. 19 or 50 for thermostat connections. NOTE: Low--heat--only switch, SW1--2, selects either the low
heat--only operation mode when ON, (see item 2. below) or adaptive heating mode when OFF, in response to a call for heat. (See Fig. 33.) When the W2 thermostat terminal is energized, it will always cause high--heat operation when the R to W circuit is closed, regardless of the setting of the low-- heat only switch.
This furnace can operate as a two--stage furnace with a single-- stage thermostat because furnace control CPU includes a programmed adaptive sequence of controlled operation, which selects low--heat or high--heat operation. This selection is based upon the stored history of the length of previous gas heating periods of the single-- stage thermostat.
The furnace will start up in either low-- or high--heat. If the furnace starts up in low--heat, the furnace control CPU determines the low--heat on time (from 0 to 16 minutes) which is permitted before switching to high--heat.
MODE)
AGE
35
Page 36
If power is interrupted, the stored history is erased. When this happens, the control CPU will initially select low--heat for up to 16 minutes and then switch to high-- heat, as long as the thermostat continues to call for heat. Subsequent selection is based on stored history of thermostat cycle times.
The wall thermostat “calls for heat,” closing the R to W circuit. The furnace control CPU performs a self--check, verifies the low-- heat and high --heat pressure switch contacts LPS and HPS are open.
58UVB
Fig. 41 --- Inducer Housing Drain Tube
A06456
A06457
Fig. 42 --- Filling Condensate T rap
TABLE 10—BLOWER OFF DELAY S ETUP SWITCH
POSITION
DESIRED
HEATING MODE
BLOWER OFF
DELAY (SEC)
90 OFF OFF 120 ON OFF 150 OFF ON 180 ON ON
SETUP SWITCH (SW1 --- 7 AND SW1---8) POSITION
S W 1 --- 7 SW 1 --- 8
1. Inducer Prepurge Period--The furnace control CPU turns on inducer motor IDM and slowly increases the inducer motor speed. When the low--heat pressure switch LPS closes, inducer motor RPM is noted by the furnace control CPU, and a 25--sec. prepurge period begins. The RPM is used to evaluate vent system resistance. This evaluation is then used to determine the required RPM necessary to operate the inducer motor during the low--heat prepurge period and low--heat mode.
NOTE: The heat cycle can start in either high--or low-- heat. If a high--heat cycle is initiated, the furnace control CPU will deenergize the high--heat pressure switch relay HPSR to close the NC contact and continues to increase the inducer motor speed after the low--heat pressure switch LPS closes. When the high--heat pressure switch closes, inducer motor RPM is noted by the furnace control CPU before the 25 -- sec prepurge period begins. The RPM is used to evaluate vent system resistance. This evaluation is then used to determine the required RPM necessary to operate the inducer motor in high--heat mode.
36
Page 37
2. Igniter Warm-- Up--At end of the prepurge period, the Hot Surface Igniter HSI is energized for a 17--sec igniter warm--up period.
3. Trial--For--Ignition Sequence--When the igniter warm--up period is completed, the main gas valve relay contacts GVR close to energize the gas valve GV, the gas valve opens. The gas valve GV permits gas flow to the burners where it is ignited by the Hot Surface Igniter HSI. Five seconds after the GVR closes, a 2--second flame period begins. The HSI igniter will remain energized until the flame is sensed or until the 2 --second flame proving period begins. If the furnace control CPU selects high-- heat operation, the high--heat gas valve solenoid GV--HI is also energized.
4. Flame--Proving-- When burner flame is proved at the flame proving sensor electrode FSE, the furnace control CPU begins the blower--ON delay period and continues to hold the gas valve GV--M open. If the burner flame is not proved within two seconds, the control CPU will close the gas valve GV--M, and the furnace control CPU will repeat the ignition sequence for up to three more Trials--For--Ignition before going to Ignition --Lockout. Lockout will be reset automatically after three hours, by momentarily interrupting 115 vac power to the furnace, or by interrupting 24 vac power at SEC1 or SEC2 to the furnace control CPU (not at W/W1, G, R, etc.). If flame is proved when flame should not be present, the furnace control CPU will lock out of Gas--Heating mode and operate the inducer motor IDM on high speed until flame is no longer proved.
5. Inducer Speed Change-- If the cycle starts in low--heat, the furnace control CPU reduces the inducer speed slightly after flame sense. If cycle starts in high--heat, the furnace control CPU increases the inducer speed 15 seconds after flame sense. The reduction in speed in low--heat is to optimize combustion for maximum efficiency.
6. Blower--On delay--If the burner flame is proven, the blower--ON delay for low--heat and high--heat are as follows: Low--heat opened, the BLWM is turned ON at low--heat airflow. High--heat the BLWM is turned ON at high-- heat airflow. Simultaneously, the humidifier terminal HUM and electronic air cleaner terminal EAC--1 are energized and remain energized throughout the heating cycle.
7. Switching From Low -- To High-- Heat-- If the furnace control CPU switches from low--heat to high--heat, the furnace control CPU will de-- energize the the high--heat pressure switch relay HPSR to close the NC contact and slowly increase the inducer motor speed until the high--heat pressure switch HPS closes. When the high--heat pressure switch HPS closes, the high-- heat gas valve solenoid GV--HI is energized and the inducer motor RPM is noted by the furnace control CPU. The RPM is used to evaluate vent system resistance. This evaluation is then used to determine the required RPM necessary to operate the inducer motor in high--heat mode. The blower motor BLWM will transition to high --heat airflow five seconds after the furnace control CPU switches from low--heat to high--heat.
8. Switching From High-- To Low-- Heat--The furnace control CPU will not switch from high--heat to low-- heat while the thermostat R-- to-- W circuit is closed when using a single--stage thermostat.
9. Blower--Off delay-- When the thermostat is satisfied, the R to W circuit is opened, de--energizing the gas valve GV--M, stopping gas flow to the burners, and
--30 seconds after the gas valve GV--M is
--35 seconds after gas valve GV--M is opened,
de--energizing the humidifier terminal HUM. The inducer motor IDM will remain energized for a 15--second post-- purge period. The blower motor BLWM and air cleaner terminal EAC--1 will remain energized at low--heat airflow or transition to low--heat airflow for 90, 120, 150, or 180 seconds (depending on selection at blower--OFF delay switches). The furnace control CPU is factory--set for a 120--second blower--OFF delay.
TWO--STAGE THERMOSTAT AND TWO--ST HEA
TING
See Fig. 49 for thermostat connections.
NOTE: In this mode, the low--heat only switch SW1 -- 2 must be ON to select the low--heat only operation mode in response to closing the thermostat R--to--W1 circuit. Closing the thermostat R--to--W1--and--W2 circuits always causes high--heat operation, regardless of the setting of the low--heat--only switch.
The wall thermostat “calls for heat,” closing the R toW1 circuit for low--heat or closing the R to W1 --and-- W2 circuits for high--heat. The furnace control performs a self--check and verifies the low heat and high --heat pressure switch contacts LPS and HPS are open. The start--up and shutdown functions and delays described in item 1. above apply to 2--stage heating mode as well, except for switching from low-- to high--heat and vice versa.
1. Switching From Low-- To High-- Heat--If the thermostat R to W1 circuit is closed and the R toW2 circuit closes, the furnace control CPU will de--energize the high--heat pressure switch relay HPSR to close the NC contact and slowly increase the inducer motor speed until the high--heat pressure switch HPS closes. When the high--heat pressure switch closes, the high--heat gas valve solenoid GV--HI is energized and the inducer motor RPM is noted by the furnace control CPU. The RPM is used to evaluate vent system resistance. This evaluation is then used to determine the required RPM necessary to operate the inducer motor in high--heat mode. The blower motor BLWM will transition to high--heat airflow five seconds after the R to W2 circuit closes.
2. Switching From High-- To Low-- Heat-- If the thermostat R to W2 circuit opens, and the R to W1 circuit remains closed, the furnace control CPU will energize the high--heat pressure switch relay HPSR to open the NC contact and slowly decrease the inducer motor speed to the required low-- heat RPM. When the high --heat pressure switch HPS opens, the high--heat gas valve solenoid GV--HI is de-- energized. When the inducer motor IDM reduces pressure sufficiently, the high--heat pressure switch HPS will open. The gas valve solenoid GV-- M will remain energized as long as the low--heat pressure switch LPS remains closed. The blower motor BLWM will transition to low--heat airflow five seconds after the R to W2 circuit opens.
COOLING
The thermostat “calls for cooling.”
1. Single--Speed Cooling
MODE
(See Fig. 19 for thermostat connections.) The thermostat closes R--to--G--and--Y circuits. The R--to--Y circuit starts the outdoor unit, and R--to--G--and-- Y/Y2 circuits start the furnace blower motor BLWM on cooling airflow. Cooling airflow is based on the A/C selection shown in Fig. 39. The electronic air cleaner terminal EAC--1 is energized with 115--v when blower motor BLWM is operating. When the thermostat is satisfied, the R-- to-- G-- and--Y circuits are opened. The outdoor unit will stop, and furnace blower motor BLWM will continue operating at cooling airflow for an additional 90 sec. Jumper Y/Y2 to
AGE
58UVB
37
Page 38
DHUM to reduce the cooling off--delay to 5 seconds. (See Fig. 33.)
2. Single--Stage Thermostat and Two--Speed Cooling
(Adaptive Mode)
(See Fig. 50 for thermostat connections.) This furnace can operate a two --speed cooling unit with a single-- stage thermostat because the furnace control CPU includes a programmed adaptive sequence of controlled operation, which selects low--cooling or high--cooling operation. This selection is based upon the stored history of the length of previous cooling period of the single--stage thermostat.
NOTE: The air conditioning relay disable jumper ACRDJ must be connected to enable the adaptive cooling mode in response to a call for cooling. (See Fig. 33.) When in place the furnace control CPU can turn on the air conditioning relay ACR to energize the Y/Y2 terminal and switch the outdoor unit to high--cooling.
The furnace control CPU can start up the cooling unit in
58UVB
either low-- or high--cooling. If starting up in low--cooling, the furnace control CPU determines the low--cooling on --time (from 0 to 20 minutes) which is permitted before switching to high-- cooling. If the power is interrupted, the stored history is erased and the furnace control CPU will select low--cooling for up to 20 minutes and then energize the air conditioning relay ACR to energize the Y/Y2 terminal and switch the outdoor unit to high--cooling, as long as the thermostat continues to call for cooling. Subsequent selection is based on stored history of the thermostat cycle times. The wall thermostat “calls for cooling,” closing the R to G--and--Y circuits. The R to Y1 circuit starts the outdoor unit on low--cooling speed, and the R to G--and--Y1 circuits starts the furnace blower motor BLWM at low--cooling airflow which is the true on--board CF selectionasshowninFig.39. If the furnace control CPU switches from low--cooling to high--cooling, the furnace control CPU will energize the air conditioning relay ACR. When the air conditioning relay ACR is energized the R to Y1-- and--Y2 circuits switch the outdoor unit to high--cooling speed, and the R to G--and--Y1--and-- Y/Y2 circuits transition the furnace blower motor BLWM to high cooling airflow. High--cooling airflow is based on the A/C selection shown in Fig. 39.
NOTE: When transitioning from low--cooling to high--cooling the outdoor unit compressor will shut down for 1 minute while the furnace blower motor BLWM transitions to run at high--cooling airflow.
The electronic air cleaner terminal EAC-- 1 is energized with 115 vac whenever the blower motor BLWM is operating. When the thermostat is satisfied, the R to G--and--Y circuit are opened. The outdoor unit stops, and the furnace blower BLWM and electronic air cleaner terminal EAC-- 1 will remain energized for an additional 90 seconds. Jumper Y1 to DHUM to reduce the cooling off--delay to 5 seconds. (See Fig. 33.)
3. Two--Stage Thermostat and Two-- Speed Cooling (See Fig. 49 for thermostat connections)
NOTE: The air conditioning relay disable jumper ACRDJ must be disconnected to allow thermostat control of the outdoor unit staging. (See Fig. 33.)
The thermostat closes the R to G and--Y1 circuits for low cooling or closes the R to G and--Y1--and-- Y2 circuits for high--cooling. The R to Y1 circuit starts the outdoor unit on low--cooling speed, and the R to G--and--Y1 circuit
starts the furnace blower motor BLWM on low--cooling airflow which is the true on --board CF selection as shown in Fig. 41. The R to Y1--and-- Y2 circuits start the outdoor unit on high-- cooling speed, and the R to G --and --Y/Y2 circuits start the furnace blower motor BLWM at high--cooling ariflow. High--cooling airflow is based on the A/C selection shown in Fig. 39. The electronic air cleaner terminal EAC-- 1 is energized with 115 vac whenever the blower motor BLWM is operating. When the thermostat is satisfied, the R to G--and--Y1 or R to G--and--Y1--and--Y2 circuits are opened. The outdoor unit stops, and the furnace blower BLWM and electronic air cleaner terminal EAC--1 will remain energized for an additional 90 seconds. Jumper Y1 to DHUM to reduce the cooling off-- delay to 5 seconds. (See Fig. 33.)
THERMIDISTAT
See Fig. 43 --46 for Thermidistat connections. The dehumidification output, DHUM on the Thermidistat should be connected to the furnace control thermostat terminal DHUM. When there is a dehumidify demand, the DHUM input is activated, which means 24 vac signal is removed from the DHUM input terminal. In other words, the DHUM input logic is reversed. The DHUM input is turned ON when no dehumidify demand exists. Once 24 vac is detected by the furnace control on the DHUM input, the furnace control operates in Thermidistat mode. If the DHUM input is low for more than 48 hours, the furnace control reverts back to non-- Thermidistat mode. The cooling operation described in item 3. above applies to operation with a Thermidistat. The exceptions are listed below:
1. Low cooling--When the R to G--and--Y1 circuit is closed and there is a demand for dehumidification, the furnace blower motor BLWM will drop the blower airflow to 86% of low--cooling airflow which is the true on--board CF selectionasshowninFig.39.
2. High cooling--When the R to G-- and Y/Y2 circuit is closed and there is a demand for dehumidification, the furnace blower motor BLWM will drop the blower airflow to 86% of high--cooling airflow. High--cooling airflow is basedontheA/CselectionshowninFig.39.
3. Cooling off--delay-- When the “call for cooling” is satisfied and there is a demand for dehumidification, the cooling blower--off delay is decreased from 90 seconds to 5 seconds.
SUPER--DEHUMIDIFY
Super--Dehumidify mode can only be entered if the furnace control is in Thermidistat mode and there is a demand for dehumidification. The cooling operation described in item 3. above also applies to operation with a Thermidistat. The exceptions are listed below:
1. Low cooling --When the R to Y1 circuit is closed, R to G circuit is open, and there is a demand for dehumidification, the furnace blower motor BLWM will drop the blower airflow to 65% of low--cooling airflow for a maximum of 10 minutes each cooling cycle or until the R to G circuit closes or the demand for dehumidification is satisfied. Low-- cooling airflow is the true on--board CF selection as shown in Fig. 39.
MODE
MODE
38
Page 39
2. High cooling--When the R to Y/Y2 cicuit is closed, R to G circuit is open, and there is a demand for dehumidifiation, the furnace blower motor BLWM will drop the blower to 65% of high--cooling airflow for a maximum of 10 minutes each cooling cycle or until the R to G circuit closes or the demand for dehumidification is satisfied. High--cooling airflow is based on the A/C selectionshowninFig.39.
3. Cooling off--delay-- When the “call for cooling” is satisfied and there is a demand for dehumidification, the cooling blower--off delay is decreased from 90 seconds to 5 seconds.
CONTINUOUS BLOWER
When the R to G circuit is closed by the thermostat, the blower motor BLWM will operate at continuous--blower airflow. Continuous blower airflow selection is initially based on the CF selection shown in Fig. 39. Factory default is shown in Fig. 39. Terminal EAC--1 is energized as long as the blower motor BLWM is energized. During a call for heat, the blower BLWM will transition the blower motor BLWM to continuous blower airflow, low--heat airflow, or the midrange airflow, whichever is lowest. The blower motor BLWM will remain ON until the main burners ignite then shut OFF and remain OFF for the blower--ON delay (30 seconds in low--heat and 35 seconds in high--heat) allowing the furnace heat exchangers to heat more quickly, then restarts at the end of the blower--ON delay period at low-- heat or high--heat airflow respectively. The blower motor BLWM will revert to continuous--blower airflow after the heating cycle is completed. In high --heat, the furnace control CPU will drop the blower motor BLWM to low-- heat airflow during the selected blower--OFF delay period before transitioning to continuous--blower airflow. When the thermostat “calls for high--cooling,” the blower motor BLWM will operate at high-- cooling airflow. When the thermostat is satisfied, the blower motor BLWM will operate an additional 90 seconds at high--cooling airflow before transitioning back to continuous-- blower airflow. When the R to G circuit is opened, the blower motor BLWM will continue operating for an additional 5 seconds, if no other function requires blower motor BLWM operation.
MODE
58UVB
39
Page 40
58UVB
A00275
Fig. 43 --- Two--Stage Furnace with Single--Speed
Air Conditioner
Fig. 45 --- Two--Stage Furnace with Single--Speed
Heat Pump (Dual Fuel)
A00277
Fig. 44 --- Two--Stage Furnace with Two--Speed
Air Conditioner
A00276
A00278
Fig. 46 --- Two--Stage Furnace with Two--Speed
Heat Pump (Dual Fuel)
40
Page 41
Fig. 47 --- Dual Fuel Thermostat with Two-- Stage
Furnace and Single--Speed Heat Pump
Fig. 48 --- Dual Fuel Thermostat With Two--Stage
Furnace and Two--Speed Heat Pump
A00279
A00280
A00281
Fig. 49 --- Two--Stage Thermostat With Two--Stage Furnace
and Two--Speed Air Conditioner
See note 2
A02348
Fig. 50 --- Single-- Stage Thermostat With Two--Stage
Furnace and Two--Speed Air Conditioner
58UVB
41
Page 42
Notes for Fig. 43 --50:
1. Heat pump MUST have a high pressure switch for dual fuel applications.
2. Refer to outdoor equipment Installation Instructions for additional information and setup procedure.
3. Select the “ZONE” position on the two--speed heat pump control.
4. Outdoor Air Temperature Sensor must be attached in all dual fuel applications.
5. Dip switch No.1 on Thermidistat should be set in OFF position for air conditioner installations. This is factory default.
6. Dip switch No. 1 on Thermidistat should be set in ON position for heat pump installations.
7. Dip switch No. 2 on Thermidistat should be set in OFF position for single--speed compressor operation.
8. Dip switch No. 2 on Thermidistat should be set in ON position for two--speed compressor operation.
9. Configuration Option No. 10 “Dual Fuel Selection” must be turned ON in all dual fuel applications.
10. NO connection should be made to the furnace HUM terminal when using a Thermidistat.
11. Optional connection. If wire is connected, dip switch SW1--2 on furnace control should be set in ON position to allow
12. Optional connection. If wire is connected, ACRDJ jumper on furnace control should be removed to allow Thermidistat/Thermostat to
13. Furnace must control its own high--stage heating operation via furnace control algorithm. This is factory default.
58UVB
14. The RVS Sensing terminal “L” should not be connected. This is internally used to sense defrost operation.
15. DO NOT SELECT the “FURNACE INTERFACE” or “BALANCE POINT” option on the two--speed heat pump control board. This
16. Dip switch D on Dual Fuel Thermostat should be set in OFF position for single-- speed compressor operation.
17. Dip switch D on Dual Fuel Thermostat should be set in ON position for two--speed compressor operation.
This is factory default.
Thermidistat/Thermostat to control furnace staging.
control outdoor unit staging.
is controlled internally by the Thermidistat/Dual Fuel Thermostat.
This is factory default.
42
Page 43
Continuous Blower Speed Selection from Thermostat
To select different continuous--blower speeds from the room thermostat, momentarily turn off the FAN switch or push button on the room thermostat for 1--3 seconds after the blower motor BLWM is operating. The furnace control CPU will shift the continuous--blower airflow from the factory setting to the next highest CF selection airflow as shown in Fig. 39. Momentarily turning off the FAN switch again at the thermostat will shift the continuous--blower airflow up one more increment. If you repeat this procedure enough, you will eventually shift the continuous--blower airflow to the lowest CF selection as shown in Fig. 39. The selection can be changed as many times as desired and is stored in the memory to be automatically used following a power interruption.
This feature is disabled when blower off delay is set for 180 sec.
PUMP
HEAT
See Fig. 45 --48 for thermostat connections. When installed with a heat pump, the furnace control automatically changes the timing sequence to avoid long blower off times during demand defrost cycles. Whenever W/W1 is energized along with Y1 or Y/Y2, the furnace control CPU will transition to or bring on the blower motor BLWM at cooling airflow, low-- heat airflow, or the midrange airflow, whichever is the lowest. The blower motor BLWM will remain on until the main burners ignite, then shut OFF and remain OFF for 25 seconds before coming back on at heating airflow. When the W/W1 input signal disappears, the furnace control begins a normal inducer post--purge period while changing the blower airflow. If Y/Y2 input is still energized, the furnace control CPU will transition the blower motor BLWM airflow to cooling airflow. If Y/Y2 input signal disappears and the Y1 input is still energized, the furnace control CPU will transition the blower motor BLWM to low-- cooling airflow. If both the Y1 and Y/Y2 signals disappear at the same time, the blower motor BLWM will remain on at low--heat airflow for the selected blower--OFF delay period. At the end of the blower--OFF delay, the blower motor BLWM will shut OFF unless G is still energized, in which case the blower motor BLWM will operate at continuous blower airflow.
COMPONENT
The furnace features a component test system to help diagnose a system problem in the case of a component failure. To initiate the component test procedure, ensure that there are no thermostat inputs to the control and all time delays have expired. Turn on setup switch SW1--6 (See Fig. 33.)
NOTE: The component test feature will not operate if the control is receiving any thermostat signals or until all time delays have expired.
The component test sequence is as follows:
1. The furnace control CPU turns the inducer motor IDM ON at medium speed and keeps it ON through step c.
2. After waiting 15 seconds, the furnace control CPU turns the hot surface igniter ON for 15 seconds, then OFF.
3. The furnace control CPU then turns the blower motor BLWM ON at midrange airflow for 15 seconds, then OFF.
4. After shutting the blower motor BLWM OFF, the furnace control CPU shuts the inducer motor IDM OFF.
NOTE: The EAC terminals are energized when the blower is operating.
After the component test is completed, 1 or more status codes (11, 25, 41, or 42) will flash. See Service Label on blower access panel or Service/Status Code Instructions for explanation of status codes.
NOTE: To repeat component test, turn setup switch SW1--6 to OFF and then back ON.
TEST
Step 6 —Adjustments
SETGASINPUTRATE
Furnace gas input rate on rating plate is for installations at altitudes up to 2000 ft.
In the U.S.A., the input rating for altitudes above 2000 ft must be reduced by 2 percent for each 1000 ft above sea level.
In Canada, the input rating must be derated by 5 percent for altitudes of 2000 ft to 4500 ft above sea level.
Adjust manifold pressure to obtain input rate.
Furnace input rate must be within ¦2 percent of input rate on furnace rating plate.
1. Determine natural gas orifice size and manifold pressure for correct input.
a. Obtain average heat value (at installed altitude) from
local gas supplier.
b. Obtain average specific gravity from local gas supplier.
c. Verify furnace model. Table 11 can only be used for
model 58UVB Furnaces.
d. Find installation altitude in T able 11.
NOTE: For Canadian altitudes of 2000 to 4500 ft, use U.S.A. altitudes of 2001 to 3000 ft in Table 11.
e. Find closest natural gas heat value and specific gravity
in Table 11.
f. Follow heat value and specific gravity lines to point of
intersection to find orifice size and low-- and high--heat manifold pressure settings for proper operation.
EXAMPLE: (0 -- 2000 ft altitude) Heating value = 1050 Btu/cu ft Specific gravity = 0.62 Therefore: Orifice No. 45
Manifold pressure: 3.8--in. wc for high heat
1.6--in. wc for low heat
* Furnace is shipped with No. 45 orifices. In this example, all main burner orifices are the correct size and do not need to be changed to obtain proper input rate.
g. Check and verify burner orifice size in furnace.
NEVER ASSUME ORIFICE SIZE; ALWAYS CHECK AND VERIFY.
2. Adjust manifold pressure to obtain input rate.
a. Remove burner enclosure front.
NOTE: Manifold pressure MUST always be measured with the burner box cover REMOVED.
b. Remove regulator seal caps that conceal adjustment
screws for low-- and high--heat gas valve regulators. (See Fig 51.)
c. MovesetupswitchSW1--2oncontrolcentertoON
position. (See Fig. 33.) This keeps furnace locked in low--heat operation.
d. Jumper R and W/W1 thermostat connections on
control to start furnace.
e. Turn low--heat adjusting screw (3/32) hex Allen
wrench) counterclockwise (out) to decrease input rate or clockwise (in) to increase input rate.
NOTE: DO NOT set low--heat manifold pressure less than
1.3--in. wc or more than 1.7--in. wc for natural gas. If manifold pressure is outside this range, change main burner orifices to obtain manifold pressure in this range.
58UVB
43
Page 44
TABLE 11—ORIFICE SIZE* AND MANIFOLD PRESSURES FOR GAS INPUT RATE
*
(TABULATED DATA BASED ON 20,000 BTUH HIGH--HEAT/13,000 BTUH LOW--HEAT PER BURNER,
DERATED 2%/1,000 FT ABOVE SEA LEVEL)
ALTITUDE
RANGE
(ft)
0 950 44 3.6 / 1.5 44 3.8 / 1.6 43 3.4 / 1.4 43 3.5 / 1.5
to 1000 44 3.3 / 1.4 44 3.4 / 1.4 44 3.5 / 1.5 44 3.6 / 1.5
2000 1050 45 3.6 / 1.5 45 3.7 / 1.6 45 3.8 / 1.6 44 3.3 / 1.4
U.S.A
.
Altitudes 825 43 3.6 / 1.5 43 3.7 / 1.6 43 3.8 / 1.6 42 3.2 / 1.4
2001 850 43 3.4 / 1.4 43 3.5 / 1.5 43 3.6 / 1.5 43 3.7 / 1.6
58UVB
to 3000 875 44 3.7 / 1.5 44 3.8 / 1.6 43 3.4 / 1.4 43 3.5 / 1.5
or 900 44 3.5 / 1.5 44 3.6 / 1.5 44 3.7 / 1.6 44 3.8 / 1.6
Canada 925 44 3.3 / 1.4 44 3.4 / 1.4 44 3.5 / 1.5 44 3.6 / 1.5
Altitudes 950 45 3.7 / 1.6 44 3.2 / 1.4 44 3.3 / 1.4 44 3.4 / 1.4
U.S.A. and Canada U.S.A. and CanadaU.S.A. OnlyU.S.A. OnlyU.S.A. OnlyU.S.A. Only
2001 975 45 3.6 / 1.5 45 3.7 / 1.6 45 3.8 / 1.6 44 3.2 / 1.4
to 4500 1000 45 3.4 / 1.4 45 3.5 / 1.5 45 3.6 / 1.5 45 3.7 / 1.6
3001 800 43 3.5 / 1.5 43 3.6 / 1.5 43 3.8 / 1.6 42 3.2 / 1.3
to 850 44 3.6 / 1.5 44 3.7 / 1.6 44 3.8 / 1.6 43 3.4 / 1.5
4000 900 44 3.2 / 1.3 44 3.3 / 1.4 44 3.4 / 1.4 44 3.5 / 1.5
4001 775 43 3.5 / 1.5 43 3.6 / 1.5 43 3.7 / 1.6 43 3.8 / 1.6
to 825 44 3.5 / 1.5 44 3.6 / 1.5 44 3.7 / 1.6 43 3.4 / 1.4
5000 875 45 3.8 / 1.6 44 3.2 / 1.4 44 3.3 / 1.4 44 3.4 / 1.5
5001 750 43 3.4 / 1.4 43 3.5 / 1.5 43 3.6 / 1.5 43 3.8 / 1.6
to 800 44 3.4 / 1.5 44 3.6 / 1.5 44 3.7 / 1.6 44 3.8 / 1.6
6000 850 45 3.7 / 1.6 45 3.8 / 1.6 44 3.2 / 1.4 44 3.4 / 1.4
6001 700 43 3.6 / 1.5 43 3.7 / 1.6 43 3.8 / 1.6 42 3.3 / 1.4
to 750 44 3.6 / 1.5 44 3.7 / 1.6 44 3.8 / 1.6 43 3.5 / 1.5
7000 800 45 3.8 / 1.6 44 3.3 / 1.4 44 3.4 / 1.4 44 3.5 / 1.5
AVG. GAS SPECIFIC GRAVITY OF NATURAL GAS
HEAT VALUE 0.58 0.60 0.62 0.64
AT ALTITUDE Orifice Mnfld Press Orifice Mnfld Press Orifice Mnfld Press Orifice Mnfld Press
(Btu/cu ft) No. High/Low No. High/Low No. High/Low No. High/Low
900 43 3.5 / 1.5 43 3.6 / 1.5 43 3.8 / 1.6 42 3.2 / 1.3
925 44 3.8 / 1.6 43 3.5 / 1.5 43 3.6 / 1.5 43 3.7 / 1.6
975 44 3.4 / 1.5 44 3.6 / 1.5 44 3.7 / 1.6 44 3.8 / 1.6
1025 45 3.8 / 1.6 44 3.2 / 1.4 44 3.3 / 1.4 44 3.4 / 1.5
1075 45 3.4 / 1.4 45 3.5 / 1.5 45 3.7 / 1.5 45 3.8 / 1.6
1100 45 3.3 / 1.4 45 3.4 / 1.4 45 3.5 / 1.5 45 3.6 / 1.5
800 43 3.8 / 1.6 42 3.2 / 1.4 42 3.3 / 1.4 42 3.5 / 1.5
775 43 3.7 / 1.6 42 3.2 / 1.3 42 3.3 / 1.4 42 3.4 / 1.4
825 44 3.8 / 1.6 43 3.4 / 1.4 43 3.5 / 1.5 43 3.7 / 1.5
875 44 3.4 / 1.4 44 3.5 / 1.5 44 3.6 / 1.5 44 3.7 / 1.6
925 45 3.7 / 1.5 45 3.8 / 1.6 44 3.2 / 1.4 44 3.3 / 1.4
950 45 3.5 / 1.5 45 3.6 / 1.5 45 3.7 / 1.6 45 3.8 / 1.6
750 43 3.7 / 1.6 43 3.8 / 1.6 42 3.2 / 1.4 42 3.3 / 1.4
800 44 3.7 / 1.6 43 3.4 / 1.4 43 3.5 / 1.5 43 3.6 / 1.5
850 44 3.3 / 1.4 44 3.4 / 1.4 44 3.5 / 1.5 44 3.6 / 1.5
900 45 3.6 / 1.5 45 3.7 / 1.6 45 3.8 / 1.6 44 3.2 / 1.4
925 45 3.4 / 1.4 45 3.5 / 1.5 45 3.6 / 1.5 45 3.7 / 1.6
725 43 3.6 / 1.5 43 3.8 / 1.6 42 3.2 / 1.4 42 3.3 / 1.4
775 44 3.7 / 1.5 44 3.8 / 1.6 43 3.4 / 1.4 43 3.5 / 1.5
825 44 3.2 / 1.4 44 3.3 / 1.4 44 3.4 / 1.5 44 3.6 / 1.5
875 45 3.5 / 1.5 45 3.6 / 1.5 45 3.7 / 1.6 45 3.8 / 1.6
900 45 3.3 / 1.4 45 3.4 / 1.4 45 3.5 / 1.5 45 3.6 / 1.5
675 42 3.2 / 1.3 42 3.3 / 1.4 42 3.4 / 1.4 42 3.5 / 1.5
725 44 3.8 / 1.6 43 3.5 / 1.5 43 3.6 / 1.5 43 3.7 / 1.6
775 44 3.4 / 1.4 44 3.5 / 1.5 44 3.6 / 1.5 44 3.7 / 1.6
825 45 3.6 / 1.5 45 3.7 / 1.6 45 3.8 / 1.6 44 3.3 / 1.4
850 45 3.4 / 1.4 45 3.5 / 1.5 45 3.6 / 1.5 45 3.7 / 1.6
Orifice numbers shown inBOLD are factory-installed.
44
Page 45
TABLE 11 — ORIFICE SIZE* AND MANIFOLD PRESSURES FOR GAS INPUT RATE
*
(TABULATED DATA BASED ON 20,000 BTUH HIGH--HEAT/13,000 BTUH LOW--HEAT PER BURNER,
DERATED 2%/1,000 FT ABOVE SEA LEVEL) (CONT)
ALTITUDE
RANGE
(ft)
7001 675 43 3.5 / 1.5 43 3.7 / 1.6 43 3.8 / 1.6 42 3.2 / 1.4
to 725 44 3.5 / 1.5 44 3.6 / 1.5 44 3.8 / 1.6 43 3.4 / 1.4
U.S.A. Only
8000 775 45 3.7 / 1.6 44 3.2 / 1.3 44 3.3 / 1.4 44 3.4 / 1.4
8001 650 43 3.5 / 1.5 43 3.6 / 1.5 43 3.8 / 1.6 42 3.2 / 1.3
to 700 44 3.5 / 1.5 44 3.6 / 1.5 44 3.7 / 1.6 44 3.8 / 1.6
U.S.A. OnlyU.S.A. Only
9000 750 45 3.7 / 1.5 45 3.8 / 1.6 44 3.2 / 1.4 44 3.3 / 1.4
9001 625 43 3.5 / 1.5 43 3.6 / 1.5 43 3.7 / 1.6 43 3.8 / 1.6
to 675 44 3.4 / 1.4 44 3.5 / 1.5 44 3.7 / 1.5 44 3.8 / 1.6
10000 725 45 3.6 / 1.5 45 3.7 / 1.6 45 3.8 / 1.6 44 3.3 / 1.4
AVG. GAS SPECIFIC GRAVITY OF NATURAL GAS
HEAT VALUE 0.58 0.60 0.62 0.64
AT ALTITUDE Orifice Mnfld Press Orifice Mnfld Press Orifice Mnfld Press Orifice Mnfld Press
(Btu/cu ft) No. High/Low No. High/Low No. High/Low No. High/Low
650 43 3.8 / 1.6 42 3.2 / 1.4 42 3.4 / 1.4 42 3.5 / 1.5
700 44 3.8 / 1.6 43 3.4 / 1.4 43 3.5 / 1.5 43 3.6 / 1.5
750 44 3.3 / 1.4 44 3.4 / 1.4 44 3.5 / 1.5 44 3.6 / 1.5
800 45 3.5 / 1.5 45 3.6 / 1.5 45 3.7 / 1.6 44 3.2 / 1.4
825 45 3.3 / 1.4 45 3.4 / 1.4 45 3.5 / 1.5 45 3.6 / 1.5
625 43 3.8 / 1.6 42 3.2 / 1.4 42 3.3 / 1.4 42 3.4 / 1.5
675 44 3.7 / 1.6 43 3.4 / 1.4 43 3.5 / 1.5 43 3.6 / 1.5
725 44 3.2 / 1.4 44 3.4 / 1.4 44 3.5 / 1.5 44 3.6 / 1.5
775 45 3.4 / 1.5 45 3.6 / 1.5 45 3.7 / 1.6 45 3.8 / 1.6
600 43 3.8 / 1.6 42 3.2 / 1.4 42 3.3 / 1.4 42 3.4 / 1.4
650 44 3.7 / 1.6 44 3.8 / 1.6 43 3.4 / 1.5 43 3.6 / 1.5
700 44 3.2 / 1.3 44 3.3 / 1.4 44 3.4 / 1.4 44 3.5 / 1.5
58UVB
Orifice numbers shown inBOLD are factory-installed.
A97386
45
Page 46
INLET PRESSURE TAP
ON/OFF SWITCH
ON
LOW-FIRE ADJUSTMENT ALLEN SCREW (UNDER CAP)
HIGH-FIRE ADJUSTMENT ALLEN SCREW
O
F
F
(UNDER CAP)
58UVB
ENCLOSURE REFERENCE
PRESSURE TAP
Fig. 51 --- Redundant Automatic Gas Valve
!
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in reduced furnace life, property damage, personal injury, and death.
DO NOT bottom out gas valve regulator adjusting screw. This can result in unregulated manifold pressure and result in excess overfire and heat exchanger failures.
NOTE: If orifice hole appears damaged or it is suspected to have been redrilled, check orifice hole with a numbered drill bit of correct size. Never redrill an orifice. A burr--free and squarely aligned orifice hole is essential for proper flame characteristics.
f. Move setup switch SW1--2 to OFF position after
completing low--heat adjustment.
g. Jumper R and W/W1 and W2 thermostat connections
on furnace control. (See Fig. 33.) This keeps furnace locked in high--heat operation.
h. Turn high--heat adjusting screw (3/32 hex Allen
wrench) counterclockwise (out) to decrease input rate or clockwise (in) to increase rate.
NOTE: DO NOT set high--heat manifold pressure less than
3.2--in. wc or more than 3.8--in. wc for natural gas. If manifold pressure is outside this range, change main burner orifices to obtain manifold pressures in this range.
i. When correct input is obtained, replace caps that
conceal gas valve regulator adjustment screws. Main burner flame should be clear blue, almost transparent. (See Fig. 53.)
j. Remove jumpers R to W/W1 and R to W2
BURNER
MANIFOLD
PRESSURE
A097386
TAP
BURNER
ORIFICE
Fig. 52 --- Burner Orifice
3. Verify natural gas input rate by clocking gas meter.
NOTE: Be sure all pressure tubing, combustion--air and vent pipes, and burner enclosure front are in place when checking input by clocking gas meter.
a. Calculate high-- altitude adjustment (if required).
UNITED STATES At altitudes above 2000 ft, this furnace has been approved for a 2 percent derate for each 1000 ft above sea level. See Table 12 for derate multiplier factor and example. CANADA At installation altitudes from 2000 to 4500 ft, this furnace must be derated 5 percent by an authorized Gas Conversion Station or Dealer. To determine correct input rate for altitude, see example and use
0.95 as derate multiplier factor.
EXAMPLE: 100,000 BTUH HIGH--HEAT INPUT FURNACE INSTALLED AT 4,300 FT
A93059
Furnace Input Rate at Sea Level X Derate Multiplier Factor = Furnace Input Rate at Installation Altitude
100,000 X 0.91 = 91,000
b. Reinstall burner box cover.
46
Page 47
NOTE: Clocking gas input rate MUST always be performed with the burner box cover INSTALLED.
c. Check that gas valve adjustment caps are in place for
proper input to be clocked.
d. Obtain average heat value (at altitude) from local gas
supplier.
NOTE: Be sure heating value of gas used for calculations is correct for your altitude. Consult local gas utility for altitude adjustment of gas heating value.
e. Check and verify orifice size in furnace. NEVER
ASSUME THE ORIFICE SIZE. ALWAYS CHECK AND VERIFY.
f. Turn off all other gas appliances and pilots.
g. Move setup switch SW1--2 to ON position. (See Fig.
33.) This keeps furnace locked in low-- heat operation.
BURNER FLAME
BURNER
!
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in component damage due to flame impingement of burners and heat exchangers.
DO NOT redrill orifices. Improper drilling (burrs, out--of--round holes, etc.) can cause excessive burner noise and misdirection of burner flames. (See Fig. 52.)
EXAMPLE: (High--heat operation at 0 -- 2000 ft altitude) Furnace input from rating plate is 100,000 Btuh Btuh heating input = Btuh/cu ft X cu ft/hr Heating value of gas = 975 Btuh/cu ft Time for 1 revolution of 2 --cu ft dial = 70 sec Gas rate = 103 cu ft/hr (from Table 13) Btuh heating input = 103 X 975 = 100,425 Btuh
In this example, the orifice size and manifold pressure adjustment is within ±2 percent of the furnace input rate.
NOTE: Measured gas inputs (high heat and low heat) must be within ±2 percent of that stated on furnace rating plate when installed at sea level or derated per that stated above when installed at higher altitudes.
n. Remove jumper across R, W/W1, and W2 thermostat
connections to terminate call for heat.
SET TEMPERATURE
RISE
58UVB
MANIFOLD
A89020
Fig. 53 --- Burner Flame
TABLE 12—ALTITUDE DERATE MULTIPLIER FOR
U.S.A.
ALTITUDE
(FT)
0—2000 0 1.00 2001—3000 4—6 0.95 3001—4000 6—8 0.93 4001—5000 8—10 0.91 5001—6000 10—12 0.89 6001—7000 12—14 0.87 7001—8000 14—16 0.85 8001—9000 16—18 0.83
9001—10,000 18—20 0.81
* Derate multiplier factor is based on midpoint altitude for al titude range
h. Jumper R to W/W1.
i. Let furnace run for 3 minutes in low-- heat operation. j. Measure time (in sec) for gas meter to complete 1
revolution. Note reading.
k. Refer to Table 13 for cubic ft of gas per hr.
l. Multiply gas rate cu ft/hr by heating value (Btu/cu ft).
m. Move setup switch SW1--2 to OFF position and
jumper R and W/W1 and W2 thermostat connections. (See Fig. 33.) This keeps furnace locked in high--heat operation. Repeat items i through l for high--heat operation.
%OF
DERATE
DERATE MULTIPLIER FACTOR FOR U.S.A.*
!
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in overheating the heat exchangers or condensing flue gases in heat exchanger areas not designed for condensate.
Temperature rise must be within limits specified on unit rating plate. Operation is within a few degrees of midpoint ofriserangewhensetupswitchSW1--4isOFF.
Furnace must operate within ranges of temperature rise specified on the furnace rating plate. Determine air temperature rise as follows:
1. Place thermometers in return and supply ducts as near furnace as possible. Be sure thermometers do not see heat exchanger so that radiant heat does not affect readings. This practice is particularly important with straight--run ducts.
2. When thermometer readings stabilize, subtract return-- air temperature from supply--air temperature to determine air temperature rise.
NOTE: Temperature rise can be determined for low-- heat operation by placing setup switch SW1--2 on furnace control in ON position. For high --heat operation, place setup switch SW1-- 2 in OFF position and jumper R-- W2 on furnace control. DO NOT forget to return setup switch to OFF position and remove R--W2 jumper upon completion of testing. (See Fig. 33 for switch and terminal location.)
47
Page 48
TABLE 13—GAS RATE CU FT/HR
SECONDS SIZE OF TEST DIAL SECONDS SIZE OF TEST DIAL
FOR 1
REVOLUTION cu ft cu ft cu ft REVOLUTION cu ft cu ft cu ft
10 360 720 1800 50 72 144 360 11 327 655 1636 51 71 141 355 12 300 600 1500 52 69 138 346 13 277 555 1385 53 68 136 340 14 257 514 1286 54 67 133 333 15 240 480 1200 55 65 131 327 16 225 450 1125 56 64 129 321 17 212 424 1059 57 63 126 316 18 200 400 1000 58 62 124 310 19 189 379 947 59 61 122 305 20 180 360 900 60 60 120 300 21 171 343 857 62 58 116 290 22 164 327 818 64 56 112 281 23 157 313 783 66 54 109 273 24 150 300 750 68 53 106 265 25 144 288 720 70 51 103 257 26 138 277 692 72 50 100 250
58UVB
27 133 267 667 74 48 97 243 28 129 257 643 76 47 95 237 29 124 248 621 78 46 92 231 30 120 240 600 80 45 90 225 31 116 232 581 82 44 88 220 32 113 225 563 84 43 86 214 33 109 218 545 86 42 84 209 34 106 212 529 88 41 82 205 35 103 206 514 90 40 80 200 36 100 200 500 92 39 78 196 37 97 195 486 94 38 76 192 38 95 189 474 96 38 75 188 39 92 185 462 98 37 74 184 40 90 180 450 100 36 72 180 41 88 176 439 102 35 71 178 42 86 172 429 104 35 69 173 43 84 167 419 106 34 68 170 44 82 164 409 108 33 67 167 45 80 160 400 110 33 65 164 46 78 157 391 112 32 64 161 47 76 153 383 116 31 62 155 48 75 150 375 120 30 60 150 49 73 147 367
1 2 5 FOR 1 1 2 5
3. This furnace is capable of automatically providing proper airflow to maintain the temperature rise within the range specified on furnace rating plate. If temperature rise is outside this range, proceed as follows:
a. Check gas input for low-- and high--heat operation.
b. Check derate for altitude if applicable.
c. Check all return and supply ducts for excessive
restrictions causing static pressure greater than 0.5--in. wc.
d. Ensure Low Heat Rise Adjust switch SW1--3 on
furnace control is in ON position when a bypass humidifier is used. (See Fig. 33 for switch location.)
e. Check Troubleshooting Guide for Variable--Speed
2--Stage Electronic Condensing Furnaces Series 100.
SETTHERMOSTATHEATANTICIPAT
OR
When using a non--electronic thermostat, the thermostat heat anticipator must be set to match the amp draw of components in the R--W/W1 circuit. Accurate amp draw measurements can be obtained only at the thermostat subbase terminals R and W.
The thermostat and anticipator should NOT be in the circuit while measuring current. If thermostat has no subbase, the thermostat must be disconnected from R and W/W1 wires during current measurement.
Fig. 54 illustrates an easy method of obtaining thermostat amp draw measurements. The amp reading should be taken after blower motor has started and furnace is operating in low--heat.
1. To operate furnace in low--heat, turn setup switch SW1--2 to ON position (See Fig. 33) and connect ammeter leads across thermostat subbase R--W.
2. See thermostat manufacturer’s instructions for adjusting the heat anticipator and for varying heating cycle length.
NOTE: When using an electronic thermostat, set cycle rate for 3 cycles per hr.
3. Return setup switch SW1--2 to OFF position and replace thermostat on subbase.
Step 7 —Check Safety Controls
This section covers the safety controls that must be checked before the installation is complete. The flame sensor, gas valve, and pressure switches were all checked in the Start--up procedure section as part of normal operation.
CHECK PRIMARY LIMIT
This control shuts off the gas control system and energizes the air--circulating blower motor if furnace overheats.
CONTROL
48
Page 49
1. The recommended method of checking this limit control is to gradually block off return air after furnace has been operating for a period of at least 5 minutes.
THERMOSTAT SUBBASE TERMINALS WITH THERMOSTAT REMOVED (ANITICIPATOR, CLOCK, ETC., MUST BE OUT OF CIRCUIT.)
HOOK-AROUND AMMETER
R Y W G
CHECKLIST
1. Put away tools and instruments. Clean up debris.
2. Verify flame rollout manual reset switch has continuity.
3. Ve rify that blower and main access doors are properly installed.
4. Cycle test furnace with room thermostat.
5. Check operation of accessories per manufacturer’s instructions.
6. Review User’s Manual with owner.
7. Leave literature packet near
furnace.
10 TURNS
FROM UNIT 24-V CONTROL TERMINALS
EXAMPLE:
5.0 AMPS ON AMMETER 10 TURNS AROUND JAWS
0.5 AMPS FOR THERMOSTAT
=
ANTICIPATOR SETTING
A96316
Fig. 54 --- AmpDrawwithAmmeter
2. As soon as limit control has shut off burners, a status code 33 will appear on furnace control.
3. The return--air opening should be unblocked to permit normal air circulation.
By using this method to check the limit control, it can be established that the limit is functioning properly and the furnace will operate safely if there is a restricted return--air duct or motor failure. If the limit control does not function during this test, the cause must be determined and corrected.
CHECK PRESSURE
SWITCHES
This control proves operation of the draft inducer. Check switch operation as follows:
1. Turn off 115--v power to furnace.
2. Remove control access door and disconnect inducer motor 12--pin wire harness at inducer motor.
3. Turn on 115-- v power to furnace.
4. Set thermostat to “call for heat.” When pressure switches are functioning properly, status code 42 will flash on furnace control approximately 20 sec after thermostat switch is closed. If either a status code 31 or 32 is flashed when inducer motor is disconnected, the furnace will shut itself down immediately. Determine the reason pressure switches did not function properly and correct the condition.
5. Turn off 115--v power to furnace.
6. Reconnect inducer motor wire harness. Reinstall furnace access door.
7. Turn on 115-- v power to furnace.
8. Reset thermostat to desired temperature.
58UVB
49
Page 50
CHECKLIST — INSTALLATION
LOAD CALCULATION
________________ Heating Load (Btuh) Condensate Drain
________________ Cooling Load (Btuh) ________________ Unit Level or Pitched Forward
________________
Furn ace Model Selection
COMBUSTION AND VENT PIPING
Termination Location
________________ Vent Heat Tape Installed if Required
________________ Roof C H E C K L I S T --- S T A R T --- U P
________________
Sidewall
________________ Combustion--- Air ________________ Temperature Rise Adjusted
________________ Roof Thermostat Anticipator
58UVB
________________ Sidewall ________________ Anticipator Setting Adjusted or
________________ Attic ________________ Cycle Rate (3 Cycles per Hr)
________________ Crawl Space Safety Controls Check Operation
________________ Termination Kit--- 2 Pipe or
Concentric
________________
C o m b u s t i o n --- A i r P i p e L e n g t h
________________ Combustion--- Air Pipe Elbow
Quantity
________________ Vent Pipe Length Thermostat Anticipator
________________ Vent Pipe Elbow Quantity ________________ Anticipator Setting Adjusted or
________________ Pipe Diameter Determined from
Sizing Table
________________ Pipe Sloped To Furnace Safety Controls Check Operation
Pipe Insulation ________________ Primary Limit
________________ Over Ceilings ________________ Pressure Switches
________________ Low---Ambient Exposed Pipes
________________ Internal Tubing Connections
Free of Kinks and Traps
________________ External Drain Connection Leak
Tight and Sloped
________________ Condensate Trap Primed before
S t a r t --- U p
________________ Gas Input Rate (Set Within 2
percent of Rating Plate)
Selected
C H E C K L I S T --- S T A R T --- U P
________________ Gas Input Rate (Set Within 2
percent of Rating Plate)
________________
TemperatureRiseAdjusted
________________ Cycle Rate (3 Cycles per Hr)
Selected
Copyright 2006 Carrier Corp. S 7310 W. Morris St. S Indianapolis, IN 46231
Manufacturer reserves the right to change, at any time, specifications and designs without notice a nd witho ut obligations.
Printed in U.S.A. Edition Date: 09/06
Catalog No:58 UVB--1SI
Replaces:New
50
Loading...