Improper installation or misapplication of furnace may
require excessive servicing or cause premature component
failure.
Application of this furnace should be indoors with special
attention given to vent sizing and material combustion air
requirements, gas input rate, air temperature rise, unit
leveling, and unit sizing.
!
FIRE, EXPLOSION, ELECTRICAL SHOCK AND
CARBON MONOXIDE POISONING HAZARD
58UVB
Failure to follow this warning could result in electrical
shock, fire, personal injury, or death.
Improper installation, adjustment, alteration, service,
maintenance, or use can cause carbon monoxide
poisoning, explosion, tire, electrical shock, or other
conditions which may cause personal injury or property
damage. Consult a qualified installer, service agency,
local gas supplier, or your distributor or branch for
information or assistance. The qualified installer or
agency must use only factory--authorized and listed kits
or accessories when modifying this product.
Installing and servicing heating equipment can be hazardous due
to gas and electrical components. Only trained and qualified
personnel should install, repair, or service heating equipment.
Untrained personnel can perform basic maintenance functions
such as cleaning and replacing air filters. All other operations
must be performed by trained service personnel. When working
on heating equipment, observe precautions in literature, on tags,
and on labels attached to or shipped with unit and other safety
precautions that may apply.
These instructions cover the minimum requirements and conform
to existing national standards and safety codes. In some instances,
these instructions exceed certain local codes and ordinances,
especially those that may not have kept up with changing
residential construction practices. We require these instructions as
a minimum for a safe installation.
Wear safety glasses and work gloves. Have a fire extinguisher
available during start--up and adjustment procedures and service
calls.
Recognize safety information. This is the safety--alert symbol
.When you see this symbol on the furnace and in
instructions or manuals, be alert to the potential for personal
injury.
Understand the signal words DANGER, WARNING, and
CAUTION. These words are used with the safety--alert symbol.
DANGER identifies the most serious hazards which will result in
severe personal injury or death. WARNING signifies a hazard
which could result in personal injury or death. CAUTION is used
to identify unsafe practices which may result in minor personal
WARNING
injury or product and property damage. NOTE is used to
highlight suggestions which will result in enhanced installation,
reliability, or operation.
!
CAUTION
CUT HAZARD
Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care
and wear appropriate protective clothing and gloves when
handling parts.
The 58UVB Condensing Gas--Fired Furnaces are CSA (formerly
AGA and CGA) design--certified for natural and propane gases
(see furnace rating plate) and for installation in alcoves, attics,
basements, closets, utility rooms, crawlspaces, and garages. The
furnace is factory--shipped for use with natural gas. A CSA listed
gas conversion kit is required to convert furnace for use with
propane gas.
See Fig. 3 for required clearances to combustibles.
Maintain a 1--in. clearance from combustible materials to supply
air ductwork for a distance of 36 inches horizontally from the
furnace. See NFPA 90B or local code for further requirements.
These furnaces SHALL NOT be installed directly on carpeting,
tile, or any other combustible material other than wood flooring.
These furnaces are suitable for installation in a structure built on
site or a manufactured building completed at final site. The
design of this furnace line is NOT CSA design--certified for
installation in recreation vehicles, manufactured (mobile) homes
or outdoors.
This furnace is designed for continuous return--air minimum
temperature of 60_F db or intermittent operation down to 55_F
db such as when used with a night setback thermostat. Return--air
temperature must not exceed 80_F db. Failure to follow these
return air limits may affect reliability of heat exchangers, motors
and controls. (See Fig. 4.)
These furnaces are shipped for UPFLOW applications ONLY.
See details in Applications section.
Install this furnace only in a location and position as specified in
LOCATION and INSTALLATION sections of these instructions.
Combustion products must be discharged outdoors. Connect this
furnace to an approved vent system only, as specified in the
Combustion Air and Vent piping sections of these instructions.
Never test for gas leaks with an open flame. Use a commercially
available soap solution made specifically for detection of leaks to
check all connections as specified in the GAS PIPING section of
these instructions.
Always install the furnace to operate within the furnace’s
intended rise range with a duct system which has an external
static pressure within the allowable range as specified in the SET
TEMPERA TURE RISE section of these instructions.
When a furnace is installed so that supply ducts carry air
circulated by the furnace to areas outside the space containing the
furnace, the return air shall also be handled by ducts sealed to the
furnace casing and terminating outside the space containing the
furnace.
2
Page 3
14 1⁄2"
TYP
1
26 15⁄16"
26 1⁄4"
1
⁄2"
24
5
22
⁄16"
-IN. COMBUSTION-
2
AIR CONN
1
⁄2-IN. DIA
GAS CONN
2
-IN. VENT CONN
⁄2-IN. DIA THERMOSTAT
ENTRY
22 11⁄16"
SIDE INLET
7
⁄8-IN. DIA
POWER CONN
7
⁄8-IN. DIA
ACCESSORY
POWER ENTRY
CONDENSATE
DRAIN TRAP
LOCATION
(ALTERNATE
UPFLOW)
9 7⁄16"
TYP
17 5⁄16"
1
⁄2"
28
AIRFLOW
13
⁄16"
1
33
⁄4"
TYP
5
⁄8"
32
TYP
13
⁄16"
30
11
29
⁄16"
TYP
5
27
⁄8"
9
27
⁄16"
TYP
1
24
⁄2"
A
D
OUTLET
13
⁄16"
CONDENSATE
ALTERNATE 1/2-IN.
DIA GAS CONN
DRAIN
30 1⁄2"
18 1⁄4"
TYP
9
⁄16"
26 15⁄16"
26 1⁄4"
5
⁄16"
22
19"
OUTLET
2-IN. COMBUSTIONAIR CONN
1
⁄2-IN. DIA
GAS CONN
7
⁄8-IN. DIA
POWER CONN
1
⁄2-IN. DIA
THERMOSTAT ENTRY
2-IN. VENT CONN
22 11⁄16"
SIDE INLET
13
⁄16"
5
⁄8"
5
⁄16"
7
39
⁄8"
1"
11⁄4"
1"E
23 1⁄4" TYP
SIDE INLET
26 15⁄16" TYP
CONDENSATE
DRAIN LOCATION
(UPFLOW)
NOTES: 1. Minimum return-air openings at furnace, based on metal duct. If flex duct is used,
see flex duct manufacturer’s recommendations for equivalent diameters.
2. Minimum return-air opening at furnace:
a. For 800 CFM–16-in. round or 14
b. For 1200 CFM–20-in. round or 141/2
c. For 1600 CFM–22-in. round or 14
d. For airflow requirements above 1800 CFM, see Air Delivery table in Product Data
literature for specific use of single side inlets. The use of both side inlets, a
combination of 1 side and the bottom, or the bottom only will ensure adequate
return air openings for airflow requirements above 1800 CFM.
11
⁄16"
1
/2
x 12-in. rectangle.
1
/2
DIMENSIONS (IN.)
UNIT SIZEADE
060 --- 1417--- 1/215--- 7/816
080 --- 142119---3/819---1/2
080 --- 202119---3/819---1/2
100 --- 202119---3/819---1/2
120 --- 2024--- 1/222--- 7/823
Fig. 2 --- Dimensional Drawing
A gas--fired furnace for installation in a residential garage must be
installed as specified in the Hazardous Locations section of these
instructions and Fig. 5.
The furnace may be used for construction heat provided that the
furnace installation and operation complies with the first
CAUTION in the LOCATION section of these instructions.
This gas furnace may be used for construction heat provided that:
SThe furnace is permanently installed with all electrical
wiring, piping, air filters, venting and ducting installed
according to these installation instructions. A return air
duct is provided, sealed to the furnace casing, and terminated outside the space containing the furnace. This
prevents a negative pressure condition as created by the
circulating air blower, causing a flame rollout and/or
drawing combustion products into the structure.
SThe furnace is controlled by a thermostat. It may not be
“hot wired” to provide heat continuously to the structure without thermostatic control.
SClean outside air is provided for combustion. This is to
minimize the corrosive effects of adhesives, sealers and
other construction materials. It also prevents the entrainment of drywall dust into combustion air, which
can cause fouling and plugging of furnace components.
INLET
x 191/2
x 231/4
-in. rectangle.
-in. rectangle.
11
⁄16"
CONDENSATE
DRAIN LOCATION
(UPFLOW)
22 1⁄4" TYP
24 3⁄16"
BOTTOM INLET
SThe temperature of the return air to the furnace is
maintained between 55_F(13_C) and 80_F(27_C),
with no evening setback or shutdown. The use of the
furnace while the structure is under construction is
deemed to be intermittent operation per our installation
instructions.
SThe air temperature rise is within the rated rise range on
the furnace rating plate, and the firing rate has been set
to the nameplate value.
SThe filters used to clean the circulating air during the
construction process must be either changed or
thoroughly cleaned prior to occupancy.
SThe furnace, ductwork and filters are cleaned as
necessary to remove drywall dust and construction
debris from all HVAC system components after
construction is completed.
SAfter construction is complete, verify furnace operating
conditions including ignition, input rate, temperature
rise and venting, according to the manufacturer’s
instructions.
7
⁄16"
11
⁄16"
A06341
58UVB
3
Page 4
58UVB
Fig. 3 --- Clearances to Combustibles
If this furnace is installed with a direct-- vent (combustion air and
flue) system, a factory accessory termination kit must be installed.
In a direct--vent system, all air for combustion is taken directly
from the outside atmosphere and all flue products are discharged
to the outside atmosphere. See furnace and factory accessory
termination kit instructions for proper installation.
These furnaces are shipped with the following materials to assist
in proper furnace installation. These materials are shipped in the
main blower compartment.
332713-201 REV. A (LIT. TOP)
A06489
Installer Packet Includes:
Installation, Startup, and Op erating Instructions
Service and Maintenance Instructions
User’s Information Manual
Warranty Certificate
Loose Parts Bag includes:Quantity
Collector Box or Condensate trap extension tube1
Inducer housing drain tube1
1/2--- in CPVC street elbow2
Drain tube coupling1
Drain tube coupling grommet1
Gas line grommet1
Vent pipe grommet1
Combustion --- air pipe grommet1
Gas line entry hole filler plug1
Power entry hole filler plug2
Condensate trap hole filler plug3
Vent and combustion---air intake hole filler plug2
Combustion - -- air pipe perforated disk assembly1
4
Page 5
0
60
A05004
Fig. 4 --- Return--Air Temperature
18-IN. MINIMUM
TO BURNERS
A93044
Fig. 5 --- Installation in a Garage
The furnace shall be installed so that the electrical components are
protected from water.
For accessory installation details, refer to applicable installation
literature.
CODES AND STANDARDS
Follow all national and local codes and standards in addition
to these instructions. The installation must comply with
regulations of the serving gas supplier, local building, heating,
plumbing, and other codes. In absence of local codes, the
installation must comply with the national codes listed below and
all authorities having jurisdiction in Canada.
In the United States and Canada, follow all codes and standards
for the following:
Step 1 —Safety
US: National Fuel Gas Code (NFGC) NFPA
S
54--2002/ANSI Z223.1--2002 and the Installation
Standards, Warm Air Heating and Air Conditioning
Systems ANSI/NFPA 90B
SCANADA: National Standard of Canada, Natural Gas
and Propane Installation Code (NSCNGPIC) CSA
B149.1--05
Step 2 —General Installation
US: NFGC and the NFPA 90B. For copies, contact the
S
National Fire Protection Association Inc., Batterymarch
Park, Quincy, MA 02269; or for only the NFGC
contact the American Gas Association, 400 N. Capitol,
N.W., Washington DC 20001
US: Section 9.3 of the NFGC, Air for Combustion and
S
Ventilation
SCANADA: Part 7 of the NSCNGPIC, Venting Systems
and Air Supply for Appliances
Step 4 —Duct Systems
US and CANADA: Air Conditioning Contractors
S
Association (ACCA) Manual D, Sheet Metal and Air
Conditioning Contractors National Association
(SMACNA), or American Society of Heating,
Refrigeration, and Air Conditioning Engineers
(ASHRAE) 2001 Fundamentals Handbook Chapter 34.
Step 5 —Acoustical Lining and Fibrous Glass
Duct
US and CANADA: current edition of SMACNA,
S
NFPA 90B as tested by UL Standard 181 for Class I
Rigid Air Ducts
Step 6 —Gas Piping and Gas Pipe Pressure
Testing
US: NFGC; chapters 5, 6, 7, and 12 and national
S
plumbing codes
SCANADA: NSCNGPIC Parts 3, 4, 5, A, B, E, G, and
H
In the state of Massachusetts:
SThis product must be installed by a licensed plumber or
gas fitter.
SWhen flexible connectors are used, the maximum
length shall not exceed 36 inches.
SWhen lever type gas shutoffs are used they shall be
T--handle type.
SThe use of copper tubing for gas piping is not approved
by the state of Massachusetts.
Step 7 —Electrical Connections
US: National Electrical Code (NEC) ANSI/NFPA
S
70--2002
SCANADA: Canadian Electrical Code CSA C22 .1
58UVB
5
Page 6
ELECTROSTATIC DISCHARGE (ESD)
PRECAUTIONS
!
CAUTION
!
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in damage to unit
components.
Electrostatic discharge can affect electronic components.
Take precautions during furnace installation and servicing
to protect the furnace electronic control. Precautions will
prevent electrostatic discharges from personnel and hand
tools which are held during the procedure. These
precautions will help to avoid exposing the control to
electrostatic discharge by putting the furnace, the control,
and the person at the same electrostatic potential.
1. Disconnect all power to the furnace. Multiple disconnects
may be required. DO NOT TOUCH THE CONTROL OR
58UVB
ANY WIRE CONNECTED TO THE CONTROL PRIOR
TODISCHARGINGYOURBODY’S
ELECTROSTATIC CHARGE TO GROUND.
2. Firmly touch a clean, unpainted, metal surface of the
furnace chassis which is close to the control. T ools held in
a person’s hand during grounding will be satisfactorily
discharged.
3. After touching the chassis, you may proceed to service the
control or connecting wires as long as you do nothing that
recharges your body with static electricity (for example;
DO NOT move or shuffle your feet, DO NOT touch
ungrounded objects, etc.).
4. If you touch ungrounded objects (recharge your body with
static electricity), firmly touch furnace again before
touching control or wires.
5. Use this procedure for installed and uninstalled
(ungrounded) furnaces.
6. Before removing a new control from its container,
discharge your body’s electrostatic charge to ground to
protect the control from damage. If the control is to be
installed in a furnace, follow items 1 through 5 before
bringing the control or yourself into contact with the
furnace. Put all used AND new controls into containers
before touching ungrounded objects.
7. An ESD service kit (available from commercial sources)
mayalsobeusedtopreventESDdamage.
INTRODUCTION
The model 58UVB Direct Vent, Upflow, Gas-- Fired, Category IV,
condensing furnace is available in model sizes ranging in input
capacities of 60,000 to 120,000 Btuh.
APPLICATIONS
Step 1 —General
Some assembly and modifications are required for condensate
trap drainage tubes. (See Fig. 6, 7 and 8.) All drain and pressure
tubes are connected as shown in Fig. 7 from the factory. See
appropriate application instructions for these procedures.
MINOR PROPERTY DAMAGE
Failure to follow this caution may result in minor property
damage.
Local codes may require a drain pan under entire furnace
and condensate trap when a condensing furnace is used in
an attic application or over a finished ceiling.
NOTE: In Canada, installations shall be in accordance with
current NSCNGPIC and/or local codes.
Step 2 —Upflow Application Only
An upflow furnace application is where furnace blower is located
below combustion and controls section of furnace, and
conditioned air is discharged upwards.
CONDENSATE TRAP (FACTORY--SHIPPED LOCA
The condensate trap is factory installed in the blower shelf. A
factory--supplied tube is used to extend the condensate trap drain
connection to the desired furnace side for field drain attachment.
See Condensate Trap Tubing section for drain tube extension
details. (See Fig. 6.)
CONDENSATE TRAP TUBING (FACTOR
CONFIGURA
NOTE: See Fig. 7 or review label on main furnace door to
NOTE: If internal filter or side filter/media cabinet is used, drain
tube should be located to opposite side of casing from return duct
attachment to assist in filter removal.
TION)
and Pressure Switch Tubes
These tubes should be factory attached to condensate trap
andpressureswitchreadyforuseininternaltrapapplications. These tubes can be identified by their connection
location and also by a color label on each tube. These
tubes are identified as follows: collector box drain tube
(blue label), inducer housing drain tube (violet label or
molded), relief port tube (green label), and pressure switch
tube (pink label).
The condensate trap drain connection must be extended
for field attachment by doing the following:
a. Determine location of field drain connection. (See Fig.
2or7.)
b. Remove and discard casing drain hole plug button
from desired side.
c. Install drain tube coupling grommet (factory--supplied
in loose parts bag) in selected casing hole.
d. Slide drain tube coupling (factory--supplied in loose
parts bag) through grommet so long end of coupling
faces blower.
e. Cement 2 factory--supplied 1/2--in. street CPVC
elbows to rigid drain tube connection on condensate
trap. (See Fig. 7.) These elbows must be cemented
together and cemented to condensate trap drain
connection.
Y--SHIPPED
TION)
6
Page 7
BLOWER SHELF
CONDENSATE
TRAP (INSIDE)
FURNACE
DOOR
CONDENSATE
TRAP
FURNACE
7
4
8
SIDE
ALTERNATE DRAIN
TUBE LOCATION
CONDENSATE TRAP
DRAIN TUBE LOCATION
FACTORY-SHIPPED LOCATION
1
2
1
3
4
3
1
4
WIRE TIE
GUIDES
(WHEN USED)
7
FRONT VIEWSIDE VIEW
Fig. 6 --- Condensate Trap
NOTE: Failure to use CPVC elbows may allow drain to kink,
preventing draining.
f. Connect larger diameter drain tube and clamp
(factory--supplied in loose parts bag) to condensate
trap and clamp securely.
g. Route tube to coupling and cut to appropriate length.
h. Attach tube to coupling and clamp securely.
CONDENSATE T RAP(ALTERNATE LOCA
TION)
An alternate location for the condensate trap is the left--hand side
of casing. (See Fig. 2 and 8.)
NOTE: If the alternate left--hand side of casing location is used,
the factory--connected drain and relief port tubes must be
disconnected and modified for attachment. See Condensate Trap
Tubing (Alternate Configuration) section for tubing attachment.
To relocate condensate trap to the left-- hand side, perform the
following:
1. Remove 3 tubes connected to condensate trap.
2. Remove trap from blower shelf by gently pushing tabs
inward and rotating trap.
3. Install casing hole filler cap (factory--supplied in loose
parts bag) into blower shelf hole where trap was removed.
FIELD
DRAIN
CONN
1
26
4
1
1
2
SIDE VIEWFRONT VIEW
ALTERNATE LOCATION
1/
OD
4
COLLECTOR BOX TO
TRAP RELIEF PORT
1/
OD
2
INDUCER HOUSING
DRAIN CONNECTION
5/
OD
8
COLLECTOR BOX
1
8
7
8
1
2
4
DRAIN CONNECTION
SCREW HOLE FOR
UPFLOW APPLICATIONS
(OPTIONAL)
1/
-IN. PVC OR CPVC
2
!
WARNING
A06501
58UVB
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal
injury or death.
Casing hole filler cap must be installed in blower shelf
hole when condensate trap is relocated to prevent
combustion products being drawn in from appliances in
the equipment room.
4. Install condensate trap into left--hand casing hole by
inserting the top two outer tabs into casing hole, while
making sure that the larger center tab is on the outside of
the casing. Push the condensate trap up as far as possible
and then rotate the connection stubs through the hole.
Slide the condensate trap downwards to secure it in the
casing hole.
5. Fill unused condensate trap casing holes with plastic filler
caps (factory--supplied in loose parts bag).
CONDENSATE T RAP TUBING (ALTERNA
CONFIGURA
TION)
TE
NOTE: See Fig. 8 or tube routing label on main furnace door to
NOTE: On 17--1/2--in. wide furnaces ONLY, cut tube between
corrugated sections to prevent kinks.
7
Page 8
2. Inducer Housing Drain Tube
a. Remove and discard LOWER (molded) inducer
housing drain tube which was previously connected to
condensate trap.
b. Use inducer housing drain extension tube (violet label
and factory--supplied in loose parts bag) to connect
LOWER inducer housing drain connection to
condensate trap.
c. Determine appropriate length, then cut and connect
tube.
d. Clamp tube to prevent any condensate leakage.
3. Relief Port Tube
a. Connect relief port tube (green label) to condensate
trap.
b. Determine appropriate length, then cut and connect
tube.
Attached to the UPPER collector box drain connection is a
factory--installed plug. This plug prevents condensate leakage in
this application. Ensure this plug is secure.
NOTE: See Fig. 7 or 8 or tube routing label on main furnace
door to check for proper connections.
Upper Inducer Housing Drain Connection
Attached to the UPPER (unused) inducer housing drain
connection is a cap and clamp. This cap is used to prevent
condensate leakage in this application. Ensure this connection is
capped.
NOTE: See Fig. 7 or 8 or tube routing label on main furnace
door to check for proper connections.
CAP
58UVB
CAP
COLLECTOR BOX
TUBE (PINK)
INDUCER HOUSING
(MOLDED) DRAIN
TUBE (BEHIND
COLLECTOR BOX
DRAIN TUBE)
COLLECTOR BOX
DRAIN TUBE (BLUE)
COLLECTOR BOX
TUBE (GREEN)
FIELD-INSTALLED
FACTORY-SUPPLIED
DRAIN TUBE
COUPLING (LEFT
DRAIN OPTION)
FIELD-INSTALLED
FACTORY-SUPPLIED
DRAIN TUBE
FIELD-INSTALLED
FACTORY-SUPPLIED
1/2-IN. CPVC STREET
ELBOWS (2) FOR
LEFT DRAIN OPTION
FIELD-INSTALLED
FACTORY-SUPPLIED
COUPLING (RIGHT
Fig. 7 --- Factory--Shipped Trap Location
(Shown with Blower Access Panel Removed)
CONDENSATE TRAP FIELD DRAIN ATT
Refer to Condensate Drain section for recommendations and
procedures.
PRESSURE SWITCH
TUBING
The LOWER collector box pressure tube (pink label) is factory
connected to the pressure switch and should not require any
modification.
NOTE: See Fig. 7 or 8 or tube routing label on main furnace
door to check for proper connections.
UPPER COLLECTOR BOX AND INDUCER
(UNUSED) DRAIN
CONNECTIONS
Upper Collector Box Drain Connection
CONDENSATE
TRAP
DRAIN TUBE
DRAIN OPTION)
ACHMENT
HOUSING
PLUG
A06498
COLLECTOR BOX
TUBE (PINK)
COLLECTOR BOX
TUBE (GREEN)
COLLECTOR BOX
DRAIN TUBE (GREEN)
CONDENSATE
TRAP
INDUCER
HOUSING
DRAIN TUBE
(VIOLET)
PLUG
A06499
Fig. 8 --- Alternate Trap Location
CONDENSATE TRAP FREEZE
PROTECTION
RefertoCondensateDrainProtectionsectionfor
recommendations and procedures.
CONDENSATE TRAP FIELD DRAIN ATT
ACHMENT
Refer to Condensate Drain section for recommendations and
procedures.
LOCATION
Step 1 —General
This furnace must
Sbe installed in upflow position ONLY
Sbe installed so the electrical components are protected
from water .
Snot be installed directly on any combustible material
other than wood flooring (refer to SAFETY
CONSIDERATIONS).
Sbe located so combustion--air and vent pipe maximum
lengths are not exceeded. Refer to Table 8.
Sbe located where available electric power and gas
supplies meet specifications on the furnace rating plate.
Sbe attached to an air distribution system and be located
as close to the center of the distribution system as
possible. Refer to Air Ducts section.
8
Page 9
Sbe provided with ample space for servicing and
cleaning. Always comply with minimum fire
protection clearances shown on the furnace
clearance--to--combustibles label. (See Fig. 3.)
This furnace may be located in a confined space without special
provisions for dilution or ventilation air.
NOTE: Install furnace so that it is level or pitched forward
within 1/2--in. for proper furnace operation. (See Fig. 9.)
LEVEL (0″)
TO
1
⁄2″ MAX
UPFLOW
Fig. 9 --- Proper Condensate Drainage
When a furnace is installed so that supply ducts carry air
circulated by the furnace to areas outside the space containing the
furnace, the return air shall also be handled by ducts sealed to
furnace casing. The ducts terminate outside the space containing
the furnace to ensure there will not be a negative pressure
condition within equipment room or space.
!
FIRE, INJURY OR DEATH HAZARD
Failure to follow this warning could result in fire,
property damage, personal injury, or death.
Do not install furnace on its back. (See Fig. 10.) Safety
control operation will be adversely affected. Never
connect return--air ducts to back of furnace.
WARNING
FRONT
A06343
!
CAUTION
UNIT DAMAGE HAZARD
This gas furnace may be used for construction heat
provided that:
--The furnace is permanently installed with all electrical
wiring, piping, air filters, venting and ducting installed
according to these installation instructions. A return air duct
is provided, sealed to the furnace casing, and terminated
outside the space containing the furnace. This prevents a
negative pressure condition as created by the circulating air
blower, causing a flame rollout and/or drawing combustion
products into the structure.
--The furnace is controlled by a thermostat. It may not be
“hot wired” to provide heat continuously to the structure
without thermostatic control.
--Clean outside air is provided for combustion. This is to
minimize the corrosive effects of adhesives, sealers and
other construction materials. It also prevents the
entrainment of drywall dust into combustion air, which can
cause fouling and plugging of furnace components.
--The temperature of the return air to the furnace is
maintained between 55_F(13_C) and 80_F(27_C), with
no evening setback or shutdown. The use of the furnace
while the structure is under construction is deemed to be
intermittent operation per our installation instructions.
--The air temperature rise is within the rated rise range on
the furnace rating plate, and the firing rate has been set to
the nameplate value.
--The filters used to clean the circulating air during the
construction process must be either changed or thoroughly
cleaned prior to occupancy.
--The furnace, ductwork and filters are cleaned as necessary
to remove drywall dust and construction debris from all
HVAC system components after construction is completed.
--After construction is complete, verify furnace operating
conditions including ignition, input rate, temperature rise
and venting, according to the manufacturer’s instructions.
58UVB
FRONT
B
A
C
K
BACK
FRONT
A93043
Fig. 10 --- Prohibit Installation on Back
The furnace and its return air system shall be designed and
installed so that negative pressure created by the air circulating
fan cannot affect another appliance’s combustion air supply or act
to mix products of combustion with circulating air, and that the
air circulating fan of the furnace, if installed in an enclosure
communicating with another fuel--burning appliance not of the
direct--vent type, shall be operable only when any door or panel
covering an opening in the furnace fan compartment or in a return
air plenum on ducts is in the closed position.
9
Page 10
!
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in minor property
or unit damage.
If these furnaces are installed in an unconditioned space
where ambient temperatures may be 32_F or lower, freeze
protection measures must be taken. See Condensate Drain
Protection section and Fig. 11.
Step 3 —Furnace Location Relative to Cooling
Equipment
The cooling coil must be installed parallel with or on downstream
side of furnace to avoid condensation in heat exchanger. When
installed parallel with a furnace, dampers or other means used to
control flow of air shall be adequate to prevent chilled air from
entering furnace. If dampers are manually operated, they must be
equipped with a means to prevent operation of either unit unless
damper is in full--heat or full--cool position.
Step 4 —Hazardous Locations
32oF MINIMUM INSTALLED
58UVB
AMBIENT OR FREEZE
PROTECTION REQUIRED
Fig. 11 --- Freeze Protection
Step 2 —Low--Heat Only Installation
This 58UVB furnace can be installed to operate in the low--heat
only heating mode when sized using the low-- heat heating
capacity. This is accomplished by placing setup switch SW1--2 in
the ON position to provide only low--heat operation. See Fig. 33
and Table 9. With this setup, high --heat operation will not occur.
!
CAUTION
A93058
!
FIRE, EXPLOSION,INJURY ORDEATH
HAZARD
Improper location or inadequate protection could result
in fire or explosion.
When furnace is installed in a residential garage, it must
be installed so that burners and ignition sources are
located a minimum of 18 in. above floor. The furnace
must be located or protected to avoid physical damage
by vehicles. When furnace is installed in a public
garage, airplane hangar, or other building having a
hazardous atmosphere, unit must be installed in
accordance with requirements of National Fire
Protection Association, Inc. (See Fig. 5.)
5
WARNING
⁄16″
5
⁄16″
1 3⁄4″
3
⁄4″
1
UNIT DAMAGE HAZARD
Failure to follow this caution may result in minor property
or unit damage.
The furnace can operate in the high--heat mode when
certain fault conditions occur. The following precautions
should be taken:
1. Size gas piping based on the high--heat input.
2. Check the high-- heat input and adjust it per the main
literature instructions.
5
⁄16″
5
⁄16″
3
⁄4″
1
3
⁄4″
1
A89014
Fig. 12 --- Leveling Legs
INSTALLATION
Step 1 —Leveling Legs (If Desired)
When furnace is used in upflow position with side inlet(s),
leveling legs may be desired. (See Fig. 12.) Install field--supplied,
corrosion --resistant 5/16-- in. machine bolts and nuts.
NOTE: The maximum length of bolt should not exceed 1 --1/2
in.
1. Position furnace on its back. Locate and drill a 5/16--in.
diameter hole in each bottom corner of furnace. (See Fig.
12.) Holes in bottom closure panel may be used as guide
locations.
10
Page 11
2. For each hole, install nut on bolt and then install bolt and
nut in hole. (Install flat washer if desired.)
3. Install another nut on other side of furnace base. (Install
flat washer if desired.)
4. Adjust outside nut to provide desired height, and tighten
inside nut to secure arrangement.
NOTE: Bottom closure must be used when leveling legs are
used. See Bottom Closure Panel section.
Step 2 —Installation
1. Construct hole in floor per dimensions specified in Fig. 13
and Table 1.
2. Construct plenum to dimensions specified in Fig. 13 and
Tab le 1.
A
PLENUM
OPENING
B
OPENING
C
D
FLOOR
Secure ductwork with proper fasteners for type of ductwork used.
Seal supply-- and return--duct connections to furnace with code
approved tape or duct sealer.
Flexible connections should be used between ductwork and
furnace to prevent transmission of vibration. Ductwork passing
through unconditioned space should be insulated to enhance
system performance. When air conditioning is used, a vapor
barrier is recommended.
Maintain a 1-- in. clearance from combustible materials to supply
air ductwork for a distance of 36 in. horizontally from the
furnace. See NFPA 90B or local code for further requirements.
For a furnace not equipped with a cooling coil, the outlet duct
shall be provided with a removable access panel. This opening
shall be accessible when the furnace is installed and shall be of
such a size that the heat exchanger can be viewed for possible
openings using light assistance or a probe can be inserted for
sampling the air stream. The cover attachment shall prevent leaks.
DUCTWORK ACOUSTICAL TREA
Metal duct systems that do not have a 90 degree elbow and 10 ft
of main duct to the first branch take--off may require internal
acoustical lining. As an alternative, fibrous ductwork may be used
if constructed and installed in accordance with the latest edition of
SMACNA construction standard on fibrous glass ducts. Both
acoustical lining and fibrous ductwork shall comply with NFPA
90B as tested by UL Standard 181 for Class 1 Rigid air ducts.
SUPPLY AIR
Connect supply--air duct to 3/4--in. flange on furnace supply--air
outlet. The supply--air duct attachment must ONLY be connected
to furnace supply-- /outlet-- air duct flanges or air conditioning coil
casing (when used). DO NOT cut main furnace casing to attach
supply side air duct, humidifier, or other accessories. All
accessories MUST be connected external to furnace main casing.
RETURN AIR
CONNECTIONS
CONNECTIONS
TMENT
58UVB
A96283
Fig. 13 --- Floor and Plenum Opening Dimensions
TABLE 1—OPENING DIMENSIONS (IN.)
FURNACE
CASING
WIDTH
17--- 1/21624---1/816- --5/824---3/4
2119---1/224---1/820--- 1/824---3/4
24--- 1/22324---1/823- --5/824---3/4
PLENUM OPENING
A
BCD
FLOOR OPENING
Step 3 —Air Ducts
GENERAL REQUIREMENTS
The duct system should be designed and sized according to
accepted national standards such as those published by: Air
Conditioning Contractors Association (ACCA), Sheet Metal and
Air Conditioning Contractors National Association (SMACNA)
or American Society of Heating, Refrigerating and Air
Conditioning Engineers (ASHRAE) or consult The Air SystemsDesign Guidelines reference tables available from your local
distributor. The duct system should be sized to handle the
required system design CFM at the design static pressure.
When a furnace is installed so that the supply ducts carry air
circulated by the furnace to areas outside the space containing the
furnace, the return air must also be handled by a duct(s) sealed to
the furnace casing and terminating outside the space containing
the furnace.
!
FIRE HAZARD
Failure to follow this warning could result in fire,
personal injury, or death.
Never connect return--air ducts to the back of the
furnace.
The return--air duct must be connected to bottom, sides (left or
right), or a combination of bottom and side(s) of main furnace
casing. Bypass humidifier may be attached into unused side
return air portion of the furnace casing. DO NOT connect any
portion of return-- air duct to back of furnace casing.
WARNING
Step 4 —Filter Arrangement
!
FIRE, CARBON MONOXIDE AND POISONING
HAZARD
Failure to follow this warning could result in fire,
personal injury or death.
Never operate unit without a filter or with filter access
door removed.
The air filter arrangement will vary due to return air configuration
and filter type. The filter may be installed in an external
Filter/Media cabinet (if provided) or the furnace blower
compartment. Factory supplied washable filters are shipped in the
blower compartment.
If a factory--supplied external Filter/Media cabinet is provided,
instructions for its application, assembly, and installation are
WARNING
11
Page 12
packaged with the cabinet. The Filter/Media cabinet can be used
R
with the factory--supplied washable filter or a factory--specified
high--efficiency disposable filter (see cabinet instructions).
If installing the filter in the furnace blower compartment,
determine location for filter and relocate filter retaining wire, if
necessary. See Table 2 to determine correct filter size for desired
filter location. Table 2 indicates filter size, location, and quantity
shipped with this furnace. See Fig. 2 for location and size of
bottom and side return--air openings.
!
CAUTION
CUT HAZARD
Failure to follow this caution may result in minor personal
injury.
Use care when cutting support rods in filters to protect
against flying pieces and sharp rod ends. Wear safety
glasses, gloves, and appropiate protective clothing.
NOTE: Side return--air openings can be used for return air
connections. Install filter(s) as shown in Fig. 14.
For bottom return--air applications, filter may need to be cut to fit
some furnace widths. Install filter as shown in Fig. 15.
171⁄2-IN. WIDE
CASINGS ONLY:
INSTALL FIELD-SUPPLIED
FILTER FILLER STRIP
UNDER FILTER.
3
″
1
24
/2″
1
″
21-IN. WIDE
CASINGS ONLY:
SUPPORT RODS (3)
EXTEND 1/4" ON EACH
SIDE OF FILTER AND
REST ON CASING FLANGE
58UVB
Furnace
Casing Width
* Filters may be field modified by cutting filter material and support rods
(3) in filters. Alternate sizes can be ordered from your distributor or
dealer.
{ Factory--- provided with the furnace
TABLE 2—FILTER INFORMATION
AIR FILTER LOCATED IN BLOWER COMPARTMENT
Filter Size (In.)
(In.)
17---1/2(1) 16 x 25 x 1{(1) 16 x 25 x 1{Cleanable
21(1) 16 x 25 x 1*(1) 20 x 25 x 1{Cleanable
24---1/2
WASHABLE
Side
Return
(1 or 2)
16 x 25 x 1*
FILTER
Bottom
Return*
(1) 24 x 25 x 1{Cleanable
Fig. 14 --- Filter Installed for Side Inlet
!
CAUTION
UNIT MAY NOT OPERATE
Failure to follow this caution may result in intermittent unit
operation or performance satisfaction.
For airflow requirements above 1800 CFM, see Air
Delivery table in Product Data literature for specific use of
single side inlets. The use of both side inlets, a combination
of 1 side and the bottom, or the bottom only will ensure
adequate return air openings for airflow requirements above
1800 CFM.
Filter Type
Framed
FILTER
RETAINE
A93045
WASHABLE
FILTER
FILTER
SUPPORT
FILTER
RETAINER
Fig. 15 --- Bottom Filter Arrangement
NOTE: Remove and discard bottom closure panel when bottom
inlet is used.
Step 5 —Bottom Closure Panel
These furnaces are shipped with bottom closure panel installed in
bottom return--air opening. This panel MUST be in place when
side return air is used.
To remove bottom closure panel, perform following:
1. Tilt or raise furnace and remove 2 screws holding front
filler panel. (See Fig. 16.)
2. Rotate front filler panel downward to release holding tabs.
3. Remove bottom closure panel.
4. Reinstall front filler panel and screws.
Step 6 —Gas Piping
Gas piping must be installed in accordance with national and
local codes. Refer to NFGC in the U.S. Canadian installations
must be made in accordance with NSCNGPIC and all authorities
having jurisdiction. Gas supply line should be a separate line
running directly from meter to furnace, if possible. Refer to Table
3 for recommended gas pipe sizing. Risers must be used to
connect to furnace and to meter. Support all gas piping with
12
A00290
Page 13
appropriate straps, hangers, etc. Use a minimum of 1 hanger
every 6 ft. Joint compound (pipe dope) should be applied
sparingly and only to male threads of joints. Pipe dope must be
resistant to propane gas.
!
WARNING
FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in fire, explosion,
personal injury, or death.
-- Connect gas pipe to furnace using a backup wrench to
avoid damaging gas controls.
-- Gas valve shutoff switch MUST be facing forward or
tilted upward.
-- Never purge a gas line into a combustion chamber.
Never test for gas leaks with an open flame. Use a
commercially available soap solution made specifically
for the detection of leaks to check all connections.
-- Use proper length of pipe to avoid stress on gas
control manifold.
-- If a flexible connector is required or allowed by
authority having jurisdiction, black iron pipe shall be
installed at furnace gas valve and extend a minimum
of 2 in. outside furnace casing.
--Protect gas valve from water and debris. Gas valve
inlet and/or inlet piping must remain capped until gas
supply line is permanently installed to protect the valve
from moisture and debris. Also, install a sediment trap
in the gas supply piping at the inlet to the gas valve.
Install a sediment trap in riser leading to furnace. Trap can be
installed by connecting a tee to riser leading to furnace so
straight--through section of tee is vertical. Then connect a capped
nipple into lower end of tee. Capped nipple should extend below
level of gas controls. Place a ground joint union between gas
control manifold and manual gas shutoff valve. (See Fig. 17.)
An accessible manual shutoff valve MUST be installed external
to furnace casing and within 6 ft of furnace. A 1/8--in. NPT
plugged tapping, accessible for test gauge connection, MUST be
installed immediately upstream of gas supply connection to
furnace and downstream of manual shutoff valve.
Gas line grommet (factory--supplied loose parts bag) should be
used when installing gas piping. Gas line entry hole filler plug
should be installed in unused gas line entry hole. (See Fig. 18.)
COMBUSTION-AIR PIPE GROMMET
BOTTOM
CLOSURE
PANEL
FRONT FILLER
PANEL
Fig. 16 --- Removing Bottom Closure Panel
GAS
SUPPLY
MANUAL
SHUTOFF
VALVE
(REQUIRED)
SEDIMENT
TRAP
UNION
Fig. 17 --- Typical Gas Pipe Arrangement
A93047
58UVB
A93324
COMBUSTION
-AIR PIPE
GAS LINE
VENT PIPE
NOTE: PIPE GROMMETS AND ENTRY HOLE FILLER
PLUGS ARE INCLUDED IN FACTORY-SUPPLIED
LOOSE PARTS BAG
*Cubic ft of gas per h r for gas pressures of 0.5 psig (14 ---in. wc) or less,
and a pressure drop of 0.5---in. wc (based on a 0.60 specific gravity
gas). Ref: Table 9---2 NFPA 54 --- 2002.
NOTE: The gas valve inlet pressure tap connection is suitable to
use as test gauge connection providing test pressure DOES NOT
exceed maximum 0.5 psig (14-- in. wc) stated on gas valve. (See
Fig. 51.)
Piping should be pressure and leak tested in accordance with
58UVB
NFGC in the United States or NSCNGPIC in Canada, local, and
national plumbing and gas codes before the furnace has been
connected. If pressure exceeds 0.5 psig (14 --in. wc), gas supply
pipe must be disconnected from furnace and capped before
pressure test.
If test pressure is equal to or less than 0.5 psig (14--in. wc), turn
off electric shutoff switch located on gas valve before test. It is
recommended that ground joint union be loosened before
pressure testing. After all connections have been made, purge
lines and check for leakage at furnace prior to placing it into
service.
The gas supply pressure shall be within the maximum and
minimum inlet supply pressures marked on the rating plate with
the furnace burners ON at HI--HEAT and OFF.
INTERNAL
DIAMETER
(IN.)
LENGTH OF PIPE (FT)
1020304050
Step 7 —Electrical Connections
See Fig. 19 for field wiring diagram showing typical field 115--v
and 24-- v wiring. Check all factory and field electrical
connections for tightness.
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal
injury or death.
Blower access door switch opens 115--v power to
furnace control. No component operation can occur. Do
not bypass or close switch with panel removed.
WARNING
!
UNIT MAY NOT OPERATE
Failure to follow this caution may result in intermittent
unit operation.
Furnace control must be grounded for proper operation
or control will lock out. Control is grounded through
green/yellow wire connected to gas valve and burner
box screw.
115 -- V WIRING
Before proceeding with electrical connections, make certain that
voltage, frequency, and phase correspond to that specified on
furnace rating plate. Also, check to be sure that service provided
by power supply is sufficient to handle load imposed by this
equipment. Refer to rating plate or Table 4 for equipment
electrical specifications.
Make all electrical connections in accordance with National
Electrical Code (NEC) ANSI/NFPA 70--2002 and any local codes
or ordinances that might apply. For Canadian installations, all
electrical connections must be made in accordance with Canadian
Electrical Code CSA C22.1 or authorities having jurisdiction.
Field--supplied wiring shall conform with the limitations of 63_F
(33_C) rise.
The furnace must be electrically grounded in accordance with
local codes; or in the absence of local codes, with the National
Electric Code ANSI/NFPA 70 and/or the Canadian Electric Code,
CSA C22.1, Part I, if an external electrical source is utilized.
Use a separate branch electrical circuit containing a properly sized
fuse or circuit breaker for this furnace. See Table 4 for wire size
and fuse specifications. A disconnecting means must be located
within sight from and readily accessible to furnace.
NOTE: Proper polarity must be maintained for 115-- v wiring. If
polarity is incorrect or furnace is not grounded properly, furnace
control status code indicator light will flash rapidly and furnace
will NOT operate.
!
FIRE HAZARD
Failure to follow this warning could result in
intermittent operation or performance satisfaction.
Do not connect aluminum wire between disconnect
switch and furnace. Use only copper wire. (See Fig. 20.)
WARNING
WARNING
14
Page 15
115-V
SINGLE
PHASE
115-V
FIELD-SUPPLIED
DISCONNECT
SWITCH
FURNACE
CONTROL
CENTER
FIVE
WIRE
THREE-WIRE
NOTE 5
WCRGY
THERMOSTAT
TERMINALS
HEATING
ONLY
W/W1
NOTE
W2
3
R
Y/Y2
24-V
G
C
NOTE 1
CONDENSING
TWO WIRE
AUXILIARY
J-BOX
TERMINAL
BLOCK
NOTES:
1.
Connect Y or Y/Y2 terminal as shown for proper cooling operation.
2.
Proper polarity must be maintained for 115-v wiring.
3.
Use W2 with 2-stage thermostat when zoning.
4.
If any of the original wire, as supplied, must be replaced, use
same type or equivalent wire.
5.
Some thermostats require a "C" terminal connection as shown.
Fig. 19 --- Heating and Cooling Application Wiring Diagram
FIELD 24-V WIRING
FIELD 115-, 208/230-, 460-V WIRING
FACTORY 24-V WIRING
FACTORY 115-, 208/230-, 460-V WIRING
FIELD-SUPPLIED
DISCONNECT
208/230- OR
460-V
THREE PHASE
GND
GND
208/230-V
SINGLE
PHASE
GND
GND
UNIT
58UVB
A98325
TABLE 4—ELECTRICAL DATA
MAXIMUM
WIRE
LENGTH
(FT)}
UNIT SIZE
V O L T S ---
H E R T Z ---
PHASE
OPERATING VOLTAGE
RANGE
Maximum*Minimum*
MAXIMUM
UNIT
AMPS
MINIMUM
WIRE SIZE
060--- 141 1 5 --- 6 0 --- 11271048.9143115
080--- 141 1 5 --- 6 0 --- 11271048.9143115
080--- 201 1 5 --- 6 0 --- 112710413.8123220
100--- 201 1 5 --- 6 0 --- 112710413.8123220
120--- 201 1 5 --- 6 0 --- 112710413.8123220
* Permissible limits of voltage range at which unit will operate satisfactorily.
{ Unit ampacity = 125 percent of largest operating component’s full load amps plus 100 percent of al l other potential operating components’ (EAC,
humidifier, etc.) full l oad amps.
} Length shown is as measured 1 way along wire path between unit and service panel for maximum 2 percent voltage drop.
** Time ---delay type is recommended.
!
ELECTRICAL SHOCK AND FIRE HAZARD
Failure to follow this warning coud result in electrical
shock, fire, or death.
The cabinet MUST have an uninterrupted or unbroken
WARNING
ELECTRIC
DISCONNECT
SWITCH
COPPER
WIRE ONLY
MAXIMUM
FUSE OR CKT
AMPS**
ground according to NEC ANSI/NFPA 70--2002 and
Canadian Electrical Code CSA C22.1 or local codes to
minimize personal injury if an electrical fault should
ALUMINUM
WIRE
occur. This may consist of electrical wire or conduit
approved for electrical ground when installed in
accordance with existing electrical codes. Do not use
Fig. 20 --- Disconnect Switch and Furnace
gas piping as an electrical ground.
BKR
A93033
15
Page 16
FACTORY INSTALLED J--BOX LOCA
TION
Install power entry hole filler plugs (factory--supplied in loose
parts bag) in unused power entry holes. (See Fig. 21.)
POWER ENTRY HOLE
FILLER PLUG (FACTORYSUPPLIED LOOSE PARTS BAG)
UNUSED 7/8-IN.
DIAMETER POWER
ENTRY HOLES
Fig. 21 --- Factory Installed J--Box Location
J--BOX RELOCA
TION
1. Remove 2 screws holding auxiliary J--box. (See Fig. 22.)
2. Rotate J--box 180_ and attach box to left side, using holes
58UVB
provided.
3. Install power entry hole filler plugs (factory--supplied
loose parts bag) in unused power entry holes. (See Fig.
22.)
!
WARNING
FIRE OR ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in
intermittent unit operation or performance satisfaction.
If manual disconnect switch is to be mounted on
furnace, select a location where a drill or fastener will
not contact electrical or gas components.
CONTINUOUS FAN (CF) SETUP SWITCHES
The CF setup switches are used to select desired airflow when
thermostat is in continuous fan mode or to select low--cooling
airflow for two--speed cooling units. This setup feature allows
continuous fan airflow or low-- cooling airflow to be adjusted. To
set desired continuous fan airflow or low--cooling airflow:
1. Remove main furnace door and blower access panel.
2. Locate CF setup switches on furnace control. (See Fig.
33.)
3. Determine desired continuous fan airflow or low--cooling
airflow.
4. Use wiring schematic to determine proper setup position
of CF switches. (See Fig. 23 and 39.)
5. Replace main furnace door and blower access panel.
FACT ORY
INSTALLED
LOCATION
A05113
SETUP SWITCHES
(SW1)
The furnace control has 8 setup switches that may be set to meet
the application requirements. Position these setup switches for the
appropriate requirement.
1. Remove main furnace door and blower access panel.
2. Locate setup switches on furnace control. (See Fig. 33.)
3. See Table 9 for setup switch description.
4. Replace main furnace door and blower access panel.
NOTE: If a bypass humidifier is used, setup switch SW1--3
(Low Heat Rise Adjust) should be in ON position. This
compensates for the increased temperature in return air resulting
from bypass.
NOTE:If modulating dampers are used, blower motor
automatically compensates for modulating dampers. If manual
disconnect switch is to be mounted on furnace, select a location
where a drill or fastener will not contact electrical or gas
components.
24--V
WIRING
Make field 24--v thermostat connections at 24-- v terminal block
on furnace control. Y wire from thermostat MUST be connected
to Y/Y2 terminal on control, as shown in Fig. 19, for proper
cooling operation. The 24--v terminal block is marked for easy
connection of field wiring. (See Fig. 33.) The 24 -- v circuit
contains a 3-- amp, automotive--type fuse located on furnace
control. (See Fig. 33.)
Any electrical shorts of 24--v wiring during installation, service,
or maintenance may cause fuse to blow. If fuse replacement is
required, use only a fuse of identical size (3 amp) and type. The
furnace control will flash status code 24 when fuse needs
replacement.
NOTE: Use AWG No. 18 color--coded copper thermostat wire
for lengths up to 100 ft. For wire lengths over 100 ft, use AWG
No. 16 wire.
1. Electronic Air Cleaner (EAC)
The furnace control EAC terminals are energized with
115v (1.0--amp maximum) during blower operation.
Connect an accessory Electronic Air Cleaner (if used)
using 1/4--in. female quick connect terminals to the two
male 1/4--in. quick--connect terminals on the control board
marked EAC--1 and EAC--2. The terminals are rated for
115VAC, 1.0 amps maximum and are energized during
blower motor operation. (See Fig. 33.)
POWER ENTRY HOLE
FILLER PLUG (FACTORYSUPPLIED LOOSE PARTS BAG)
UNUSED 7/8-IN. DIAMETER
POWER ENTRY HOLES
ALTERNATE
FIELD
LOCATION
Fig. 22 --- Relocating J--Box
16
FACTORY
INSTALLED
LOCATION
POWER ENTRY HOLE
FILLER PLUG (FACTORYSUPPLIED LOOSE PARTS BAG)
SW1-5 Manual Switch, Cooling CFM/Ton, SPST (N.O.)
SW1-6 Manual Switch, Component Test, SPST (N.O.)
SW1-7,8 Manual Switches, Blower Off-Delay, SPST(N.O.)
SW4-1 Manual Switch, Twinning Main (OFF) / Sec. (ON)
SW4-2&3 FOR FUTURE USE
TRAN Transformer, 115VAC / 24VAC
1 2 3
OFF
1750
CODE
SPST (N.O.)
LS
RED
RED
LPS
YEL
1
1 2 3
OFF
122512251225
1750
1
210017501400
1
NEUTRAL - L2
SEC-1
EAC-2
FUSE 3-AMP
SEC-2
WHT
EAC-1
NOTE #11
NOTE #8
WHT
FSE
BLK
HSI
VS
WHT
PL2
BLK
L1
BLK
PL12
NOTE #7
BLK
WHT
BLU
WHT
FRS
REDRED
ORN
(WHEN USED)
LGPS
GRN/YEL
4
BRN
2
YEL
10
1
ORN
12
WHT
6
BLK
BLK
BLK
4
PL13
IND
10
16
17
GRN
BLU
YEL
PL12
WHT
TRAN
RED
IDM
HSI
1
PL10
2
BLWM
PL14
1
432
5
RED
YEL
GRN/YEL
JUNCTION
TERMINAL
CONTROL TERMINAL
FACTORY POWER
WIRING (115VAC)
FACTORY CONTROL
WIRING (24VAC)
FIELD CONTROL
WIRING (24VAC)
CONDUCTOR ON
CONTROL
FIELD WIRING
SCREW TERMINAL
EQUIPMENT
GROUND
PLUG RECEPTACLE
FUSED OR CIRCUIT
BREAKER DISCONNECT
SWITCH (WHEN REQ'D)
NOTE #2
L1
FU2
BLK
WHT
JB
ILK
PRINTED CIRCIUT BOARD
NOTES:
1. If any of the original equipment wire is replaced use wire rat ed for 105°C.
2. Use only copper wire between the disconnect switch and the furnace junction box (JB).
3. This wire must be connected to furnace sheet metal f or control to pr ove flame.
4. Symbols are electrical representation only.
5. Soli d lines inside PCB ar e printed circu it board conductor s and are not included in legend.
6. Replace only with a 3 amp fuse.
7. Inductor is used with 3/4 hp and 1 hp ECM Blower motors.
8. Factory connected when (LGPS) not used.
9. Blower off-delay, gas heating selections are (90, 120, 150, 180) seconds, cooling or heat pump
10. Ignition lockout will occur after four consecutive unsuccessful trials for ignition. Control will
11. Any of the 5 wires shown within the NEUTRAL L2 box can be connected to any terminal within the box.
12. Blower motor (BLWM) and Inducer motor (IDM) are locked-rotor overload protected by redundant
TO 115VAC FIELD-DISCONNECT SWITCH
ILK
NEUTRAL
GND
IDR
NOTE #5
PCB
CPU
PL3
123 4
PL12
L1
EAC
FRS
ACRDJ
PCB
NOTE #5
HUMR
ACR
CPU
HUM
R
COMMR
W/W1
DHUM
W2
Y/Y2
G
Y1
COM
90 seconds or 5 sec onds when dehumidify cal l is active.
Failure to follow this caution may result in unit component
damage.
DO NOT connect furnace control HUM terminal to HUM
(humidifier) terminal on Thermidistatt, Zone Controller or
similar device. See Thermidistatt, Zone Controller,
thermostat, or controller manufacturer’s instructions for
proper connection.
2. Humidifier (HUM)
Connect an accessory 24 VAC, 0.5 amp maximum
humidifier (if used) to the 1/4--in. male quick--connect
HUM terminal and COM --24V screw terminal on the
control board thermostat strip. The HUM terminal is
energized when blower is energized in heating. (See Fig.
23 and 33.)
Step 8 —Removal of Existing Furnaces from
Common Vent Systems
When an existing Category I furnace is removed or replaced, the
original venting system may no longer be sized to properly vent
the remaining attached appliances. An improperly sized Category
I venting system could cause the formation of condensate in the
furnace and vent, leakage of condensate and combustion
products, spillage of combustion products into the living space,
etc.
17
Page 18
!
CAUTION
CARBON MONOXIDE POISONING HAZARD
Failure to follow the steps outlined below for each
appliance connected to the venting system being placed into
operation could result in carbon monoxide poisoning or
death.
The following steps shall be followed for each appliance
connected to the venting system being placed into
operation, while all other appliances connected to the
venting system are not in operation:
1. Seal any unused openings in venting system.
2. Inspect the venting system for proper size and horizontal
pitch, as required in the National Fuel Gas Code, ANSI
Z223.1--2002/NFPA 54--2002 or the CSA B149.1, Natural
Gas and Propane Installation Code and these instructions.
Determine that there is no blockage or restriction, leakage,
corrosion and other deficiencies, which could cause an
58UVB
unsafe condition.
3. As far as practical, close all building doors and windows
and all doors between the space in which the appliance(s)
connected to the venting system are located and other
spaces of the building.
4. Close fireplace dampers.
5. Turn on clothes dryers and any appliance not connected
to the venting system. Turn on any exhaust fans, such as
range hoods and bathroom exhausts, so they are operating
at maximum speed. Do not operate a summer exhaust fan.
6. Follow the lighting instructions. Place the appliance
being inspected into operation. Adjust the thermostat so
appliance is operating continuously.
7. Test for spillage from draft hood equipped appliances at
the draft hood relief opening after 5 minutes of main burner
operation. Use the flame of a match or candle.
8. If improper venting is observed during any of the above
tests, the venting system must be corrected in accordance
withtheNationalFuelGasCode,ANSI
Z223.1--2002/NFPA 54--2002 and/or CSA B149.1, Natural
Gas and Propane Installation Code.
9. After it has been determined that each appliance
connected to the venting system properly vents when tested
as outlined above, return doors, windows, exhaust fans,
fireplace dampers and any other gas--fired burning
appliance to their previous conditions of use.
Step 9 —Combustion Air and Vent Pipe Systems
GENERAL
Vent system or vent connectors of other appliances may need to
be resized. For any other appliances when resizing vent systems
or vent connectors, system or connector must be sized to
approach minimum size as determined using appropriate table
found in the NFGC or NSCNGPIC.
The 58UVB can be vented as either a direct vent furnace or as an
optional ventilated combustion air application. A direct vent
system shall be installed in accordance with the direct vent
(2--pipe) procedures in the following Combustion Air and Vent
Pipe Systems section. For optional ventilated combustion air
applications, refer to the ventilated combustion air option
procedures in the same section. Common venting prohibited.
DIRECT VENT/2--PIPE
In a direct--vent (2--pipe) system, all air for combustion is taken
directly from outdoor atmosphere, and all flue products are
discharged to outdoor atmosphere. Combustion-- air and vent
pipes must terminate together in the same atmospheric pressure
zone, either through the roof or a sidewall (roof termination
preferred). A factory accessory vent termination kit MUST be
used in a direct vent (2--pipe) system. See Table 6. See Fig. 34
for required clearances.
SYSTEM
VENTILATED COMBUSTION AIR
In a ventilated combustion air option, the vent terminates and
discharges the flue products directly to the outdoors similar to a
direct vent system. See Fig. 35 for required clearances. All air
for combustion is piped directly to the furnace from a space that
is well ventilated with outdoor air (such as an attic or crawl space)
and the space is well isolated from the living space or garage.
TERIALS
MA
Combustion-- air and vent pipe, fittings, primers, and solvents
must conform to American National Standards Institute (ANSI)
standards and American Society for Testing and Materials
(ASTM) standards. See Table 5 for approved materials for use in
the U.S.A.
!
FIRE AND EXPLOSION HAZARD
Failure to follow this warning could result in fire,
property damage, personal injury, or death.
Solvent cements are combustible. Keep away from heat,
sparks, and open flame. Use only in well ventilated
areas. Avoid breathing in vapor or allowing contact
with skin or eyes.
In Canada, construct all combustion--air and vent pipes for this
unit of CSA or ULC listed schedule--40 PVC, PVC-- DWV or
ABS--DWV pipe and pipe cement. SDR pipe is NOT approved in
Canada.
!
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in property
damage, personal injury, or death.
All combustion--air and vent pipes must be airtight and
watertight. Pipes must also terminate exactly as shown
in Fig. 31 for direct vent (2--pipe) system or Fig. 32 for
ventilated combusion air option.
An abandoned masonry chimney may be used as a raceway for
properly insulated and supported combustion--air (when
applicable) and vent pipes. Each furnace must have its own set of
combustion--air and vent pipes and be terminated individually, as
shown in Fig. 31 for Direct Vent (2-- Pipe) system or Fig. 32 for
ventilated combusion air option.
A furnace shall not be connected to a chimney flue serving a
separate appliance designed to burn solid fuel.
Other gas appliances with their own venting system may also use
the abandoned chimney as a raceway providing it is permitted by
local code, the current edition of the National Fuel Gas Code and
the vent or liner manufacturer’s installation instructions. Care
must be taken to prevent the exhaust gases from one appliance
from contaminating the combustion air of other gas appliances.
Do not take combustion air from inside the chimney when using
the Ventilated Combustion Air option.
WARNING
WARNING
OPTION
18
Page 19
TABLE 5 —APPROVED COMBUSTION--AIR AND VENT PIPE, FITTING AND CEMENT MATERIALS
ASTM
SPECIFICATION
(MARKED ON MATERIAL)
D1527ABSPipe——S c h e d u l e --- 4 0
D1785PVCPipe——S c h e d u l e --- 4 0
D2235For ABS——Solvent CementFor ABS
D2241PVCPipe——SD R --- 21 & S D R --- 26
D2466PVC—Fittings—S c h e d u l e --- 4 0
D2468ABS—Fittings—S c h e d u l e --- 4 0
D2564For PVC——Solvent CementFor PVC
D2661ABSPipeFittings—DWV at Schedule---40 IPS sizes
D2665PVCPipeFittings—DWV
F438CPVC—Fittings—S ch e d u l e --- 4 0
F441CPVCPipe——S c h e d u l e --- 40
F442CPVCPipe——SDR
F493For CPVC——Solvent CementFor CPVC
Failure to follow this caution may result in intermittent unit
operation.
When vent pipe is exposed to temperatures below freezing,
such as when it passes through an unheated space or when a
chimney is used as a raceway, pipe must be insulated as
shown in Table 7 with Armaflex--type insulation.
FURNACE
NOT IN
HORIZONTAL
SECTION
PIPE DIAMETER
TRANSITION IN
VERTICAL SECTION
A93034
Fig. 24 --- Combustion-- Air and Vent Pipe Diameter
Transition Location and Elbow Configuration
Furnace combustion air and vent pipe connections are sized for
2--in. pipe. Any pipe size change should be made outside furnace
casing in vertical pipe. The transition has to be made as close to
the furnace as reasonably possible. (See Fig. 24.)
Installation Guidelines for Combustion Air Pipe and Vent
Pipe
It is recommended that all pipes be cut, prepared, and
preassembled before permanently cementing any joint.
1. Attach combustion air pipe and vent pipe per instructions
in sections “Combustion Air Pipe” and “Vent Pipe.”
2. Working from furnace to outside, cut pipe to required
length(s).
3. Deburr inside and outside of pipe.
SOLVENT CEMENT AND
PRIMERS
Cellular Core DWV at Schedule --- 40
DESCRIPTION
IPS sizes
4. Chamfer outside edge of pipe for better distribution of
primer and cement.
5. Clean and dry all surfaces to be joined.
6. Check dry fit of pipe and mark insertion depth on pipe.
7. After pipes have been cut and preassembled, apply
generous layer of cement primer to pipe fitting socket and
end of pipe to insertion mark. Quickly apply approved
cement to end of pipe and fitting socket (over primer).
Apply cement in a light, uniform coat on inside of socket
to prevent buildup of excess cement. Apply second coat.
8. While cement is still wet, twist pipe into socket with 1/4
turn. Be sure pipe is fully inserted into fitting socket.
9. Wipe excess cement from joint. A continuous bead of
cement will be visible around perimeter of a properly
made joint.
10. Handle pipe joints carefully until cement sets.
11. Horizontal portions of the venting system shall be
supported to prevent sagging. Support combustion air
piping (if applicable) and vent piping a minimum of every
5ft(3ftforSDR--21or--26PVC)usingperforatedmetal
hanging strap.
12. Slope combustion air piping (if applicable) and vent
piping downward towards furnace a minimum of 1/4--in.
per linear ft with no sags between hangers.
13. Horizontal portions of the venting system shall be installed
so as to prevent the accumulation of condensate.
14. Use appropriate methods to seal openings where
combustion air pipe (if applicable) and vent pipe pass
through roof or sidewall.
Combustion--Air and Vent Pipe Diameter
Determine combustion--air and vent pipe diameter.
1. Using Table 8, individually determine the diameter of the
combustion--air and vent pipe allowed. If different, pick
the larger of these two diameters and use this diameter for
both combustion--air and vent pipes.
2. When installing vent systems of short pipe length, use the
smallest allowable pipe diameter. Do not use pipe size
greater than required or incomplete combustion, flame
disturbance, or flame sense lockout may occur.
NOTE: Do not count elbows or pipe sections in terminations or
within furnace.
58UVB
19
Page 20
NOTE: A 2 --in. diameter pipe must be used within furnace
-
casing. Make all pipe diameter transitions outside furnace casing.
(See Fig. 24).
!
CAUTION
NOTE:
Select 1 vent pipe connection and
1 combustion-air pipe connection.
AIR
COMBUSTION-
AIR
VENT
FLOW
COMBUSTION
AIR
UNIT MAY NOT OPERATE
VENT
Failure to follow this caution may result in incomplete
combustion, flame disturbance, or flame sense lockout.
When installing combustion air and vent system of short
pipe length, the smallest allowable pipe diameter must be
used.
UPFLOW
!
CAUTION
A06500
Fig. 25 --- Combustion Air and Vent Pipe Connections
UNIT CORROSION HAZARD
Excessive exposure to contaminated combustion air may
58UVB
result in safety and performance related problems.
Combustion air must not be taken from inside structure
because that air is frequently contaminated by halogens,
which include fluorides, chlorides, bromides, and iodides.
These elements are found in aerosols, detergents, bleaches,
cleaning solvents, salts, air fresheners, adhesives, paint, and
other household products. Locate combustion--air inlet as
far as possible from swimming pool and swimming pool
pump house.
Attachment of Combustion Air Pipe
NOTE: Combustion air pipe system has the same diameter and
same length as the vent pipe as mentioned in section
“Combustion-- Air and Vent Pipe Diameter.”
1. Determine location of combustion--air intake pipe
connection to combustion--air intake housing as shown in
Fig. 25.
2. Verify combustion--air intake housing plug fitting is
installed in appropriate unused intake housing connection.
3. Install combustion--air pipe grommet (factory-- supplied in
EXAMPLE:
An 100,000 BTUH furnace located in Indianapolis,
elevation 650 ft above sea level, could be installed as
either a direct vent/2--pipe system that requires 3 elbows
and 28 ft of vent pipe, along with 5 elbows and 34 ft of
combustion--air pipe. Table 8 indicates this application
would allow a 2--in. diameter vent pipe, but require a
2--1/2 in. diameter combustion air pipe. According to
Table 8, 2--in. diameter pipe is good for 35 ft with 3
elbows, but only 25 ft with 5 elbows. Therefore, 2--1/2
in. diameter pipe must be used for both vent and
combustion air pipes since larger required diameter
must always be used for both pipes.
If same installations were in Albuquerque, elevation
5250 ft above sea level:
Table 8 indicates that 2--1/2 in. diameter vent pipe and
combustion--air pipe are required.
If same applications are to be installed at 5001-- to 6000
ft elevation:
2--in. pipe is only good for 23 ft (with 3 elbows) and 13
4. Determine the number of combustion air disk halves to be
installed in the combustion air intake housing. Insert
perforated disk half or assembly (factory supplied in loose
parts bag) in intake housing where combustion--air intake
pipe will be connected.
5. Insert assembled combustion air inlet pipe into intake
housing as shown in Fig. 25.
NOTE: Do not cement combustion air intake pipe permanently
to combustion air intake housing since it may be necessary to
remove pipe for service of igniter or flame sensor.
6. Drill a 1/8--in. hole in 2-- in, combustion air pipe using the
hole in intake housing as a guide.
7. Install a field--supplied No. 6 or No. 8 sheet metal screw
into combustion air pipe.
8. Install casing hole filler cap (factory--supplied in loose
parts bag) in unused combustion air pipe casing hole.
ft (with 5 elbows). Therefore, 2--1/2 in. diameter
combustion air and vent pipe must be used.
3/8" ID TUBE
COMBUSTION AIR
INTAKE HOUSING
BURNER
BOX
COMBUSTION AIR
PIPE
General
Furnace combustion-- air connection must be attached as shown in
Fig. 25. Combustion-- air intake housing plug may need to be
relocated in some applications.
NOTE: All pipe joints must be cemented except attachment of
combustion--air pipe to inlet housing connection, since it may be
necessary to remove pipe for servicing.
NOTE: A 2--in. diameter pipe must be used within the furnace
casing. Make all pipe diameter transitions outside furnace casing.
(See Fig. 24).
20
3/16"
DRILL
TRAP
4″
MIN
TO OPEN
DRAIN
Fig. 26 --- Intake Housing Plug Fitting Drain
COMBUSTION
AIR PIPE
A93035
Page 21
Fig. 27 --- Attic Termination
58UVB
A06497
Attachment of Combustion Air Intake Housing Plug Fitting
The combustion-- air intake plug fitting must be installed in
unused combustion air intake housing. This fitting must be
attached by using RTV sealant, or by drilling a 1/8--in. hole in
fitting, using hole in intake housing as a guide. Install a
field--supplied No. 6 or No. 8 sheet metal screw.
NOTE:DO NOT OVERTIGHTEN SCREW. Breakage of
intake housing or fitting may cause air leakage to occur.
A plugged drain connection has been provided on this fitting for
use when moisture is found in combustion air intake pipe and
combustion box.
If use of this drain connection is desired, drill out fitting’s tap
plug with 3/16--in. drill and connect a field-- supplied 3/8--in. tube.
This tube should be routed to open condensate drain for furnace
and A/C (if used), and should be trapped, as shown in Fig. 26.
!
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in unit component
damage.
Inducer housing outlet cap must be installed and fully
seated against inducer housing. Clamp must be tightened to
prevent any condensate leakage.
NOTE:(Direct Vent/2--Pipe System ONLY). Moisture in
combustion air intake may be a result of improper termination.
Ensure combustion air pipe termination is similar to those as
shown in Fig. 31 so that it will not be susceptible to area where
light snow or others sources of moisture could be pulled in.
21
Page 22
Combustion Air Termination-- Ventilated Combustion Air
Option
Combustion air is piped directly to the burner box on furnace
using the same materials used to vent the furnace. (See Table 5.)
The combustion air pipe is terminated in an attic or crawl space
that is well ventilated with outdoor air and is well isolated from
the living space or garage. If the furnace is installed in a well
ventilated attic, the combustion air pipe can be terminated in the
same space. Refer to the Air for Combustion and Ventilation -Ventilated Combusion Air Option Section in these instructions.
The combustion air pipe cannot be terminated in attics or
crawlspaces that use ventilation fans designed to operate during
the heating season. If ventilation fans are present in these areas,
the combustion air pipe must terminate outdoors as a Direct
Vent/2--Pipe system.
NOTE: Combustion air pipe must have the same diameter as
vent pipe.
Attic terminations require at least (1) 90 degree elbow, with the
open end pointing horizontally or downward. The open end of
the elbow must be at least 12--inches above any insulation or
58UVB
other materials. Screen the elbow with a wire mesh screen no
smaller than 3/8--inch square. (See Fig. 27.)
Crawlspace termination requires the open end of the pipe
pointing downward. Maintain 3 -- inches of clearance below the
floor joist insulation and 12--inches above the grade. Screen the
elbow with a wire mesh screen no smaller than 3/8--inch square.
(See Fig. 28 and 29.)
AIR FOR COMBUSTION AND VENTILATION -Ventilated Combustion Air Option
Provisions for adequate combustion, ventilation, and dilution air
must be provided in accordance with:
U.S. Installations: Section 9.3 of the NFGC, Air for Combustion
and Ventilation and applicable provisions of the local building
codes.
Canadian Installations: Part 7 of the NSCNGPIC, V enting
Systems and Air Supply for Appliances and all authorities having
jurisdiction.
!
CARBON MONOXIDE POISONING HAZARD
Failure to supply outdoor air via grilles, louvers or vents
could result in death and/or personal injury. Many homes
require air to be supplied from outdoors for furnace
combustion, ventilation, and dilution of flue gases.
The furnace combustion air supply must be provided in
accordance with this instruction manual.
An attic or crawlspace may be considered a space that freely
communicates with the outdoors provided there are adequate
permanent ventilation openings directly to outdoors having free
area of at least 1-- in.2/4,000 Btuh of total input rating for all gas
appliances in the space.
NOTE: In determining the free area of an opening, the blocking
effect of the louvers, grilles, and screens must be considered. If
the free area of a louver or grille design is unknown, it may be
assumed that wood louvers have a 20 percent free area, and metal
louvers or grilles have a 60 percent free area. Screens, when used,
must not be smaller than 1/4 --in. mesh. Louvers and grilles must
be constructed so they cannot be closed.
WARNING
!
UNIT CORROSION HAZARD
Air for combustion must not be contaminated by
halogen compounds, which include fluoride, chloride,
bromide, and iodide. These elements may corrode heat
exchangers and shorten furnace life. Air contaminants
are found in aerosol sprays, detergents, bleaches,
cleaning
This furnace requires OUTDOOR AIR for combustion.
!
CARBON MONOXIDE POISONING HAZARD
The operation of exhaust fans, kitchen ventilation fans,
clothes dryers, attic exhaust fans or fireplaces could create a
NEGATIVE PRESSURE CONDITION at the furnace.
Make--up air MUST be provided for the ventilation devices,
in addition to that required by the furnace. Refer to the
Carbon Monoxide Poisoning Hazard warning in the venting
section of these instructions to determine if an adequate
amount of make--up air is available.
WARNING
WARNING
22
Page 23
Fig. 28 --- Crawlspace Termination
58UVB
A06495
A06496
Fig. 29 --- Crawlspace Termination
23
Page 24
COMBUSTION AIR TERMINA
VENT/2--PIPE
Combustion air pipe must terminate outside the structure with the
vent pipe as shown in Fig. 31. Follow the clearance requirements
show in Fig. 34. Refer to Vent Termination section for complete
details on termination options.
PIPE
VENT
General
Furnace vent connection must be attached as shown in Fig. 25.
CARBONMONOXIDEPOISONINGAND
PROPERTY DAMAGE HAZARD
Failure to follow this warning could result in property
damage, personal injury, or death.
Vent pipes must be airtight.
NOTE: A 2--in. diameter pipe must be used within the furnace
58UVB
casing. Make all pipe diameter transitions outside furnace casing
per Fig. 24.
The minimum vent pipe length for these furnaces is 5 ft. Short
pipe lengths (5--8 ft) may discharge condensate droplets. These
condensate droplets may be undesirable. A 12--in. minimum
offset pipe section is recommended to reduce excessive
condensate droplets from exiting vent pipe outlet. (See Fig. 30.)
Attachment of Vent Pipe
NOTE: Vent pipe system has the same diameter and same length
as combustion air pipe as mentioned in section “Combustion Air
Pipe and Vent Pipe Diameter.”
UNIT DAMAGE HAZARD
Failure to follow this caution may result in unit component
damage.
Vent pipe must be installed and fully seated against inducer
housing. Clamp must be tightened to prevent any
condensate leakage.
1. Determine location of vent pipe connection to inducer
housing as shown in Fig. 25 for application.
2. Verify synthetic rubber inducer housing outlet cap and
clamp are installed on appropriate unused inducer housing
connection and that clamp is tight.
3. Install combustion--air pipe grommet (factory-- supplied in
loose parts bag) into selected furnace casing vent pipe
hole. (See Fig. 18.)
4. Be certain that mating surfaces of inducer housing
connection synthetic rubber coupling, and 2 -- in. diameter
vent pipe are clean and dry. Assemble the synthetic rubber
vent coupling (with 2 loose clamps) onto inducer housing
connection. Insert the 2--in. diameter vent pipe through
the synthetic rubber coupling and fully into inducer
housing connection until it touches a stop inside the
inducer housing outlet.Tighten the screws on both
clamps to 15--in--lb. of torque.
NOTE: Starting at furnace, slope vent pipe a minimum of
1/4--in. per linear ft back toward furnace with no sags between
hangers.
SYSTEM
!
!
WARNING
CAUTION
TION--DIRECT
5. Install casing hole filler cap (factory--supplied in loose
parts bag) in unused vent pipe casing hole.
VENT TERMINA
General
Combustion--air (direct vent/2--pipe system only) and vent pipe
must terminate outside structure, either through sidewall or roof.
For vent termination clearance, refer to Fig. 34 for Direct
Vent/2--Pipe system and Fig. 35 for Ventilated Combustion Air
option.
Roof termination is preferred since it is less susceptible to damage
or contamination, and it has less visible vent vapors. Sidewall
termination require sealing or shielding of building surfaces with
a corrosive resistance material due to corrosive combustion
products of vent system.
NOTE: (Direct Vent/2--Pipe system ONLY) A factory accessory
termination kit MUST be used. See section “V ent Termination Kit
(Direct Vent/2--Pipe System Only)” in this instruction.
When determining appropriate location for termination, consider
the following guidelines:
1. Comply with all clearance requirements stated in Fig. 34
or Fig. 35 per application.
2. Termination or termination kit should be positioned where
vent vapors will not damage plants/shrubs or air
conditioning equipment.
3. Termination or termination kit should be positioned so that
it will not be affected by wind eddy, such as inside
building corners, nor by recirculation of flue gases,
airborne leaves, or light snow.
4. Termination or termination kit should be positioned where
it will not be damaged by or subjected to foreign objects
such as stones, balls, etc.
5. Termination or termination kit should be positioned where
vent vapors are not objectionable.
Extended Exposed Sidewall Pipes
Sidewall combustion air pipe termination (direct vent/2--pipe
system only) and vent pipe termination may be extended beyond
areashowninFig.31orinFig.32perapplicationinoutside
ambient by insulating pipe as indicated in Table 7.
1. Determine combustion air pipediameter (direct
vent/2--pipe system only) and vent pipe diameter, as stated
above, using total pipe length and number of elbows.
2. Using winter design temperature (usedin load
calculations), find appropriate temperature for your
application and furnace model.
3. Determine required insulation thickness for exposed pipe
length(s).
NOTE: Pipe length(ft) specified for maximum pipe lengths
located in unconditioned spaces cannot exceed total allowable
pipe length as specified in Table 8.
Vent Termination Kit (Direct Vent/2--Pipe System Only)
NOTE: Always refer to the instructions in termination kit for the
latest version.
Combustion air and vent pipes MUST terminate outside structure.
A factory accessory termination kit must be installed as shown in
Table 6. There are four options of vent/combustion air
termination kits available as shown in Table 6.
TION
24
Page 25
V
COMBUSTION-AIR PIPE
COMBUSTION-AIR PIPE
ERTICAL TO ROOF
Vertical separation
between combustion
air and vent
8 3/4 in. for 3 in. kit
6 3/4 in. for 2 in. kit
VENT PIPE
12″ MIN
VERTICAL TO SIDEWALL
NOTE: A 12 In. minimum offset pipe section is recommended with
short (5 to 8 ft) vent systems. This recommendation is to reduce
excessive condensate droplets from exiting the vent pipe.
Fig. 30 --- Short Vent (5 to 8 Ft) System
Roof Termination (Preferred)
At least 36 in.
A
18 in. maximum
Concentric Vent and Combustion Air
Roof Termination (preferred)
12″ MIN
VENT PIPE
At least
36 in.
A
Maintain 12
in.
min. clearance above
highest anticipated
snow level, maximum of
24 in. above roof
A06356
58UVB
Maintain 12 in. min.
clearance above
highest anticipated
snow level
Maximum of 24 in.
above roof
Note: "A" denotes 0 to < 2 in.
Between the first 2 vents
Third vent must be > 36 in. away
Abandoned masonry
used as raceway
(per code)
12
in.
min from
overhang or roof
(typ)
A
separation
in.
At least 36 in.
Side wall termination
of less than 12
in.
90°
At least 36 in
A
.
12
between bottom of
combustion air and
bottom of vent (typ)
Maintain 12
min. clearance above
highest anticipated
snow level or grade
whichever is greater (typ)
Fig. 31 --- Combustion Air and Vent Pipe Termination
for Direct Vent (2--pipe) System (All Sizes)
in.
above highest snow level
1
in.
A
t lea
3
st
6
in.
Concentric Vent
and Combustion - Air
Side Termination
maximum (typ) from wall to inlet
12
in.
minimum from
overhang or roof
A
in.
Maintain 12
min. clearance above
highest anticipated
snow level or grade
whichever is greater
A05090
25
Page 26
Roof Termination (Preferred)
Vent
Maintain 12 in.
minimum clearance
above highest anticipated
snow level maximum of
24 in. above roof.
Abandoned masonry
used as raceway
(per code)
12 in. min. from
6 in. minimum clearance
between wall and end of vent pipe.
10 in. maximum pipe length
12 in. min. from
overhang or roof
58UVB
90°
Side wall termination
with 2 elbows (preferred)
Maintain 12 in.
minimum clearance
above highest anticipated
snow level or grade
whichever is greater.
overhang or roof
Sidewall Termination
with Straight Pipe (preferred)
Maintain 12 in.
minimum clearance
above highest anticipated
snow level or grade
whichever is greater
A05091
Fig. 32 --- Vent Pipe Termination for Ventilated Combustion Air (1--pipe) System (All Sizes)
TABLE 6 —VENT TERMINATION KIT FOR DIRECT VENT/2--PIPE SYSTEM
DIRECT VENT (2--- PIPE) TERMINATION KITTERMINATION SYSTEM
2---in. Concentric Vent KitSingle Penetration of Wall or Roof1, 1--- 1/2, 2, or 2 --- 1/2
3---in. Concentric Vent KitSingle Penetration of Wall or Roof2 ---1/2, 3
2---in . Termination Bracket Kit2---Pipe Termination System1, 1 ---1/2 or 2
3---in . Termination Bracket Kit2---Pipe Termination System2--- 1/2, 3
DIAM. OF COMBUSTION AIR AND VENT
PIPES (IN INCHES)
TABLE 7—MAXIMUM ALLOWABLE EXPOSED VENT PIPE LENGTH (FT) WITH INSULATION IN WINTER DESIGN
TEMPERATURE AMBIENT*
UNIT SIZE
WINTER DESIGN
TEMPERATURE (°F)
2023055617070
060 --- 14
021633384653
--- 2 02923263338
080 --- 14
080 --- 20
2023765707070
022039455563
--- 2 021127313945
202 --- 1 / 24170707070
100 --- 20
02 --- 1 / 22142485968
--- 2 02 --- 1 / 21128334149
2034970707070
120 --- 20
* Pipe length (ft) specified for maximum pipe lengths located in unconditioned spaces. Pipes located in unconditioned space cannot exceed total allowable pipe
length as specified in Table 6.
{ Insulation thickness based on R value of 3.5 per in.
032651587070
--- 2 031535405059
MAXIMUM PIPE
DIAMETER (IN.)
INSULATION THICKNESS (IN.)†
03/81/23/41
NOTE: Combustion air pipe must have the same diameter as
vent pipe.
Concentric Vent/Combustion Air Termination Kit (Direct
Vent/2--Pipe System Only)
Determine an appropriate location for termination kit using the
guidelines provided in section “Vent Termination: General” in
this instruction.
1. Cut one 4--in. diameter hole for 2--in. kit, or one 5--in.
diameter hole for 3-- in. kit.
2. Loosely assemble concentric vent/combustionair
termination components together using instructions in kit.
3. Slide assembled kit with rain shield REMOVED through
hole.
NOTE: Do not allow insulation or other materials to accumulate
inside of pipe assembly when installing it through hole.
26
Page 27
Roof terminations--Locate assembly through roof to
(
appropriate height as shown in Fig. 31 and 32.
Sidewallterminations-- Locateassemblythrough
sidewall with rain shield positioned no more than 1--in.
from wall as shown in Fig. 31 and 32.
4. Disassemble loose pipe fittings. Clean and cement using
same procedures as used for system piping.
5. Check required dimensions as shown.
Two--Pipe Termination Kit (Direct Vent/2-- Pipe System Only
Determine an appropriate location for termination kit using the
guidelines provided in section “Vent Termination: General” in
this instruction.
1. Cut 2 holes, 1 for each pipe, of appropriate size for pipe
size being used.
2. Loosely install elbow in bracket and place assembly on
combustion--air pipe.
Roof terminations--Loosely install pipe coupling on
properly cut vent pipe. Coupling must be positioned so
bracket will mount as shown in Fig. 31.
For applications using combustion-- air pipe option,
CONTINUOUS FAN
(CF) AIRFLOW
SETUP SWITCHES
MODEL PLUG
CONNECTOR
SW1 SETUP
SWITCHES AND
BLOWER OFF-
DELAY
COMMUNICATION
CONNECTOR
indicated by dashed lines in Fig. 31, install 90_ street
elbow into 90_ elbow, making a U--fitting. A 180_
U--fitting may be used.
Sidewall terminations--Install bracket as shown in Fig.
31.
For applications using vent pipe option indicated by
dashed lines in Fig. 31, rotate vent elbow 90_ from
position shown in Fig. 31.
3. Disassemble loose pipe fittings. Clean and cement using
same procedures as used for system piping.
4. Check required dimensions as shown in Fig. 31.
Multiventing and Vent Terminations
When 2 or more 58UVB Furnaces are vented near each other,
each furnace must be individually vented. NEVER common vent
or breach vent 58UVB furnaces.
(Direct Vent/2--Pipe System ONLY)--When 2 or more 58UVB
furnaces are vented near each other, 2 vent terminations may be
installed as shown in Fig. 31, but next vent termination must be at
least 36 in. away from first 2 terminations. It is important that
vent terminations be made as shown in Fig. 31 to avoid
recirculation of flue gases.
FUTURE
APPLICATIONS
58UVB
AIR CONDITIONING
(A/C) AIRFLOW
SETUP SWITCHES
24-V THERMOSTAT
TERMINALS
STATUS AND COMM
LED LIGHTS
3-AMP FUSE
TRANSFORMER 24-VAC
CONNECTIONS
115-VAC (L2) NEUTRAL
CONNECTIONS
PL1 LOW VOLTAGE MAIN
HARNESS CONNECTOR
EAC-1 TERMINAL
115-VAC 1.0 AMP MAX.)
Fig. 33 --- Control Center
115-VAC (L1) LINE
VOLTAGE CONNECTIONS
HUMIDIFIER
TERMINAL (24-VAC
0.5 AMP MAX.
ACRDJ AIR
CONDITIONING
RELAY DISABLE
JUMPER
FLASH
UPGRADE
CONNECTOR
(FACTORY
ONLY)
PL3 ECM BLOWER
HARNESS
CONNECTOR
DATE CODE XXXXN
PL2 HOT SURFACE
IGNITER & INDUCER
MOTOR CONNECTOR
A06494
27
Page 28
58UVB
A05009
Fig. 34 --- Direct Vent Termination Clearance
28
Page 29
58UVB
Fig. 35 --- Other than Direct Vent Termination Clearance
A05013
29
Page 30
TABLE 8—MAXIMUM ALLOWABLE PIPE LENGTH (FT)
ALTITUDE
0 to 2000
ALTITUDE
2001 to 3000
58UVB
ALTITUDE
3001 to 4000
ALTITUDE
4001 to 5000‡
ALTITUDE
5001 to 6000‡
See notes on page 24
UNIT SIZE
(BTUH)
60,000
80,000
100,000
120,000
UNIT SIZE
(BTUH)
60,000
80,000
100,000
120,000
UNIT SIZE
(BTUH)
60,000
80,000
100,000
120,000
UNIT SIZE
(BTUH)
60,000
80,000
100,000
120,000
UNIT SIZE
(BTUH)
60,000
80,000
100,000
120,000
Termination
Type
2 P i p e o r 2 --- I n .
Concentric
2 P i p e o r 2 --- I n .
Concentric
2 P i p e o r 2 --- I n .
Concentric
2 P i p e o r 3 --- I n .
Concentric
Termination
Type
2 P i p e o r 2 --- I n .
Concentric
2 P i p e o r 2 --- I n .
Concentric
2 P i p e o r 2 --- I n .
Concentric
2 P i p e o r 3 --- I n .
Concentric
Termination
Type
2 P i p e o r 2 --- I n .
Concentric
2 P i p e o r 2 --- I n .
Concentric
2 P i p e o r 2 --- I n .
Concentric
2 P i p e o r 3 --- I n .
Concentric
Termination
Type
2 P i p e o r 2 --- I n .
Concentric
2 P i p e o r 2 --- I n .
Concentric
2 P i p e o r 2 --- I n .
Concentric
2 P i p e o r 3 --- I n .
Concentric
Termination
Type
2 P i p e o r 2 --- I n .
Concentric
2 P i p e o r 2 --- I n .
Concentric
2 P i p e o r 2 --- I n .
Concentric
2 P i p e o r 3 --- I n .
Concentric
Pipe Dia
(IN.)*
1 --- 1 / 2504540353025
2707070707070
1 --- 1 / 230252015105
2707070707070
2454035302520
2 --- 1 / 2707070707070
2 --- 1 / 2 o n e d i s k10NANANANANA
3onedisk353015NANANA
3onedisk†707070707070
Pipe Dia
(IN.)*
1 --- 1 / 2454035302520
2707070707070
1 --- 1 / 2262116116NA
2707070707070
2403530252015
2 --- 1 / 2707070707070
3onedisk312612NANANA
3onedisk†636262616161
Pipe Dia
(IN.)*
1 --- 1 / 2
2707070707070
1 --- 1 / 2252015105NA
2707070707070
2383328231813
2 --- 1 / 2707070707070
3onedisk292410NANANA
3onedisk†595958575756
Pipe Dia
(IN.)*
1 --- 1 / 2403530252015
2707070707070
1 --- 1 / 22318138NANA
2707070707068
2363126211611
2 --- 1 / 2707070707070
3onedisk†565554535252
Pipe Dia
(IN.)*
1 --- 1 / 2373227221712
2707070707070
1 --- 1 / 22217127NANA
2707070706863
233282318138
2 --- 1 / 2707070707070
3onedisk†535250494847
NUMBER OF 90_ ELBOWS
123456
NUMBER OF 90_ ELBOWS
123456
NUMBER OF 90_ ELBOWS
123456
4237322722
NUMBER OF 90_ ELBOWS
123456
NUMBER OF 90_ ELBOWS
123456
17
30
Page 31
TABLE 8 — MAXIMUM ALLOWABLE PIPE LENGTH (FT) (CONTINUED)
ALTITUDE
UNIT SIZE
(BTUH)
60,000
80,000
6001 to 7000‡
100,000
120,000
ALTITUDE
UNIT SIZE
(BTUH)
60,000
80,000
7001 to 8000‡
100,000
120,000
ALTITUDE
UNIT SIZE
(BTUH)
60,000
80,000
8001 to 9000‡
100,000
120,000
ALTITUDE
UNIT SIZE
(BTUH)
60,000
9001 to
10000‡
80,000
100,000
120,000
* Disk usage -- -Unless otherwise stated, use perforated disk assembly (factory---su pplied in loose parts bag).
{ Wide radius elbow.
} Vent sizing for Canadian installations over 4500 ft (1370m) above sea level are subject to acceptance by the local authorities having jurisdiction.
NA---Not Allowed; pressure switch will not make.
NOTES:
1. Do not use pipe size greater than those specified in table or incomplete combustion, flame disturbance, or flame sense lockout may occur.
2. Size both the combustion ---air and vent pipe independently, determine the smallest diameter allowed by the table for each pipe, then use the larger diameter
for both pipes.
3. Assume two 45_ elbows equal one 90_ elbow. Long radius elbows are desirable and may be required in some cases.
4. Elbows and pipe sections within the furnace casing and at the vent termination should not be included in vent length or elbow count.
5. The minimum pipe length is 5 ft for all applications.
Termination
Type
2 P i p e o r 2 --- I n .
Concentric
2 P i p e o r 2 --- I n .
Concentric
2 P i p e o r 2 --- I n .
Concentric
2 P i p e o r 3 --- I n .
Concentric
Termination
Type
2 P i p e o r 2 --- I n .
Concentric
2 P i p e o r 2 --- I n .
Concentric
2 P i p e o r 2 --- I n .
Concentric
2 P i p e o r 3 --- I n .
Concentric
Termination
Type
2 P i p e o r 2 --- I n .
Concentric
2 P i p e o r 2 --- I n .
Concentric
2 P i p e o r 2 --- I n .
Concentric
2 P i p e o r 3 --- I n .
Concentric
Termination
Type
2 P i p e o r 2 --- I n .
Concentric
2 P i p e o r 2 --- I n .
Concentric
2 P i p e o r 2 --- I n .
Concentric
2 P i p e o r 3 --- I n .
Concentric
Pipe Dia
(IN.)*
NUMBER OF 90_ ELBOWS
123456
1 --- 1 / 2353025201510
2707068676664
1 --- 1 / 22015105NANA
2707068676257
231262116116
2 --- 1 / 2707068676664
3onedisk†494847454443
Pipe Dia
(IN.)*
NUMBER OF 90_ ELBOWS
123456
1 --- 1 / 232272217127
2666563626059
1 --- 1 / 218138NANANA
2666563625752
2292419149NA
2 --- 1 / 2666563626059
3onedisk†464443414038
Pipe Dia
(IN.)*
NUMBER OF 90_ ELBOWS
123456
1 --- 1 / 230252015105
2626058565553
1 --- 1 / 217127NANANA
2626058565146
2272217127NA
2 --- 1 / 2626058565553
3onedisk†434139373534
Pipe Dia
(IN.)*
NUMBER OF 90_ ELBOWS
123456
1 --- 1 / 2272217127NA
2575553514947
1 --- 1 / 215105NANANA
2575553514641
22419149NANA
2 --- 1 / 2575553514947
3onedisk†393735333129
58UVB
31
Page 32
Step 10 —Condensate Drain
GENERAL
Condensate trap is shipped installed in the blower shelf.
Condensate trap can be RELOCATED to the side of the casing.
Condensate trap MUST be used for all applications.
An external trap is not required when connecting the field drain
to this condensate trap.
The field drain connection (condensate trap or drain tube
coupling) is sized for 1/2--in. CPVC, 1/2--in. PVC, or 5/8--in. ID
tube connection.
Drain pipe and fittings must conform to ANSI standards and
ASTM D1785, D2466, or D2846. CPVC or PVC cement must
conform to ASTM D2564 or F493. Primer must conform to
ASTM F656. In Canada, use CSA or ULC certified schedule 40
CPVC or PVC drain pipe, fittings, and cement.
When a condensate pump is required, select a pump which is
approved for condensing furnace applications. To avoid
condensate spillage, select a pump with an overflow switch.
Furnace condensate is mildly acidic, typically in the pH range of
58UVB
3.2 to 4.5. Due to corrosive nature of this condensate, a
condensate pH neutralizing filter may be desired. Check with
local authorities to determine if a pH neutralizer is required.
APPLICA
The furnace, A/C, and humidifier drains may be combined and
drained together. The A/C drain must have an external, field
supplied trap prior to the furnace drain connection. All drain
connections (furnace, A/C, or humidifier) must be terminated into
an open or vented drain as close to the respective equipment as
possible to prevent siphoning of the equipment’s drain.
See Fig. 37 for example of possible field drain attachment using
1/2--in. CPVC or PVC tee for vent and A/C or humidifier drain
connection.
Outdoor draining of the furnace is permissible if allowed by local
codes. Caution should be taken when freezing ambient may
freeze drain pipe and prohibit draining.
TION
!
CAUTION
CONDENSATE DRAIN PROTECTION
Freezing condensate left in condensate trap and drain line may
cause cracks, and possible water damage may occur. If freeze
protection is required, use condensate freeze protection accessory
or equivalent 3 to 6 watt per ft at 120v and 40_F self--regulating,
shielded, and waterproof heat tape. See Installation Instructions
suppliedwithaccessoryorheattapemanufacturer’s
recommendations.
1. Fold heat tape in half and wrap on itself 3 times.
2. Locate heat tape between sides of condensate trap back.
(See Fig. 38.)
3. Use wire ties to secure heat tape in place. Wire ties can be
positioned in notches of condensate trap sides. (See Fig.
38.)
4. Wrap field drain pipe with remaining heat tape,
approximately 1 wrap per ft.
5. When using field-- supplied heat tape, follow heat tape
manufacturer’s instructions for all other installation
guidelines.
32oF MINIMUM INSTALLED
AMBIENT OR FREEZE
PROTECTION REQUIRED
A93058
Fig. 36 --- Freeze Protection
UNIT MAY NOT OPERATE
Failure to follow this caution may result in intermittent unit
operation.
Unit must not be installed, operated, and then turned and
left off in an unoccupied structure during cold weather
when temperature drops to 32_F or below unless drain trap
and drain line have adequate freeze protection. See Service
and Maintenance Instructions for winterizing procedure.
(See Fig. 36.)
!
WARNING
PERSONAL INJURY HAZARD
Failure to follow this warning could result in property
damage and personal injury or death.
Caution should be taken to prevent draining where
slippery conditions may cause personal injuries.
Excessive condensate draining may cause saturated soil
conditions which may result in damage to plants.
OPEN STAND
PIPE FOR
A/C OR
HUMIDIFIER
DRAIN
TEE
TO OPEN
DRAIN
Fig. 37 --- Example of Field Drain Attachment
A94054
32
Page 33
CONDENSATE TRAP
WIRE TIE(S)
HEAT TAPE
(3 WRAPS MINIMUM)
A93036
Fig. 38 --- Condensate Trap Heat Tape
START--UP , ADJUSTMENTS AND SAFETY
CHECK
Step 1 —General
1. Furnace must have a 115--v power supply properly
connected and grounded.
NOTE: Proper polarity must be maintained for 115-- v wiring. If
polarity is incorrect, control status indicator light flashes rapidly
and furnace does not operate.
2. Thermostat wire connections at terminals R, W/W1, G,
and Y/Y2 must be made at 24--v terminal block on furnace
control.
3. Natural gas service pressure must not exceed 0.5 psig
(14--in. wc), but must be no less than 0.16 psig (4.5--in.
wc).
4. Blower access panel must be in place to complete 115--v
electrical circuit to furnace.
!
CAUTION
UNIT MAY NOT OPERATE
Failure to follow this caution may result in intermittent unit
operation or performance satisfaction.
These furnaces are equipped with a manual reset limit
switch in burner box. This switch opens and shuts off
power to the gas valve if an overheat condition (flame
rollout) occurs in burner enclosure. Correct inadequate
combustion--air supply or improper venting condition
before resetting switch. DO NOT jumper this switch.
Before operating furnace, check flame rollout manual reset switch
for continuity. If necessary, press button to reset switch.
Step 2 —Select Setup Switch Positions
AIR CONDITIONING (A/C) SETUP SWITCHES
The air conditioning setup switches are used to match furnace
airflow to cooling unit used.
To set the desired cooling airflow:
1. Remove main furnace door and blower access panel.
2. Locate A/C setup switches on furnace control. (See Fig.
33.)
58UVB
33
Page 34
AIR CONDITIONINGAIRFLOW*060 & 080-14
TONS (12,000 BTU/HR)(CFM)
1-1/2525 (600)X
2700 (800)XXX
2-1/2875 (1000)XXX
31050 (1200)XXX
3-1/21225 (1400)XXX
41400 (1600)XX
51750 (2000)X
62100 (2100)X
X-INDICATES AN ALLOWABLE SELECTION.
* Airflow shown in parentheses is airflow unit that the unit will deliver when setup switch SW1-5 is ON (selects 400 CFM/ton)
MODEL
080-20 & 100
MODEL
X
120 MODEL
MODEL
58UVB
SIZE
060,
080-14
080-20, 100 DEF7008751050122514001750
120DEF700875
1.DEFAULT A/C AIRFLOW WHEN A/C SWITCHES ARE IN OFF POSITION
2.DEFAULT CONT. FAN AIRFLOW WHEN CF SWITCHES ARE IN OFF POSITION
DEF525
Fig. 39 --- A/C or CF Airflow Selection Chart Based on 350 and 400CFM/Ton
3. Determine air conditioning tonnage used.
4. Use wiring schematic to determine proper setup position
of A/C switches. (See Fig. 23 and 39.)
NOTE: Excessive airflow caused by improper A/C switch setup
may cause condensate blowoff in cooling mode.
5. Replace main furnace door and blower access panel.
NOTE: EAC--1 terminal is energized whenever blower operates.
HUM terminal is only energized when blower is energized in
heating.
CONTINUOUS FAN (CF) SETUP
SWITCHES
The CF setup switches are used to select desired airflow when
thermostat is in continuous fan mode or to select low--cooling
airflow for two--speed cooling units. This setup feature allows
continuous fan airflow or low-- cooling airflow to be adjusted. To
set desired continuous fan airflow or low--cooling airflow:
1. Remove main furnace door and blower access panel.
2. Locate CF setup switches on furnace control. (See Fig.
33.)
3. Determine desired continuous fan airflow or low--cooling
airflow.
4. Use wiring schematic to determine proper setup position
of CF switches. (See Fig. 23 and 39.)
5. Replace main furnace door and blower access panel.
SETUP SWITCHES
(SW1)
The furnace control has 8 setup switches that may be set to meet
the application requirements. Position these setup switches for the
appropriate requirement.
1. Remove main furnace door and blower access panel.
A/C OR CF AIRFLOW SELECTION CHART
BASED ON 350 CFM/TON
70087510501122512251225
2
2
1050122514001750
2
2. Locate setup switches on furnace control. (See Fig. 33.)
3. See Table 9 for setup switch description. (See Fig. 23.))
4. Replace main furnace door and blower access panel.
NOTE: If a bypass humidifier is used, setup switch SW1--3
(Low HEAT Rise Adjust) should be in ON position. This
compensates for the increased temperature in return air resulting
from bypass.
NOTE:If modulating dampers are used, blower motor
automatically compensates for modulating dampers.
Step 3 —Prime Condensate Trap With Water
!
UNIT MAY NOT OPERATE
Failure to follow this caution may result in intermittent unit
operation or performance satisfaction.
Condensate trap must be PRIMED or proper draining may
not occur. The condensate trap has 2 internal chambers
which can ONLY be primed by pouring water into the
inducer drain side of condensate trap.
2. Connect field-- supplied 1/2--in. ID tube to upper inducer
housing drain connection.
3. Insert field--supplied funnel into tube.
4. Pour 1 quart of water into funnel/tube. Water should run
through inducer housing, overfill condensate trap, and
flow into open field drain. (See Fig. 42.)
1750
1
2100
1
CAUTION
A06508
34
Page 35
TABLE 9 —FURNACE SETUP SWITCH DESCRIPTION
SETUP SWITCH
NO.
S W 1 --- 1Status Code RecoveryOFF
S W 1 --- 2Adaptive Heat ModeOFF
S W 1 --- 3Low Heat Rise AdjustOFF
S W 1 --- 4Comfort/Efficiency AdjustmentON
S W 1 --- 5CFM per ton adjustOFFTurn ON for 400 CFM per ton. Turn OFF for 350 CFM per ton.
S W 1 --- 6Component Self---TestOFF
S W 1 --- 7Blower OFF delayON or OFF
S W 1 --- 8Blower OFF delayON or OFF
SWITCH NAME
NORMAL
POSITION
DESCRIPTION OF USE
Turn ON to retrieve up to 7 stored status codes for troubleshooting
assistance when R thermostat lead is disconnected.
Allows 2 ---stage operation with a single stage thermostat. Turn ON
when using 2 stage thermostat to allow Low Heat operation when
R to W/W1 closes and High Heat operation when R to W/W1 and
Turn ON to increase Low Heat airflow by 10 percent. This com-
pensates for increased return air temperature caused with bypass
Turn ON to decrease Low Heat airflow by 22 percent and High
Heat airflow 15 percent for maximum comfort.
Turn ON to initiate Component Self--- Test for troubleshooting as-
sistance when R thermostat lead is disconnected. Turn OFF when
Control blower Off Delay time. Used in conjunction with SW1--- 8.
See Table 10.
Control blower Off Delay time. Used in conjunction with SW1--- 7.
See Table 10.
!
UNIT MAY NOT OPERATE
Failure to follow this caution may result in intermittent unit
operation.
Furnace control must be grounded for proper operation, or
control will lock out. Control is grounded through
green/yellow wire routed to gas valve and burner box
screw.
W2 close.
humidifier.
Self--- Test is completed.
CAUTION
58UVB
A04001
Fig. 40 --- Example of Setup Switch in Off Position
5. Remove funnel and tube from inducer housing and replace
drain connection cap and clamp.
Step 4 —Purge Gas Lines
If not previously done, purge the lines after all connections have
been made and check for leaks.
!
FIRE AND EXPLOSION HAZARD
Failure to follow this warning could result in a fire,
explosion, personal injury, or death.
Never purge a gas line into a combustion chamber.
Never test for gas leaks with an open flame. Use a
commercially available soap solution made specifically
for the detection of leaks to check all connections.
WARNING
Step 5 —Sequence of Operation
Using schematic diagram, follow sequence of operation through
different modes. (See Fig. 23.) Read and follow wiring diagram
carefully.
NOTE: If a power interruption occurs during a call for heat
(W/W1 or W/W1--and--W2), the control will start a 90--second
blower--only ON period two seconds after power is restored, if
the thermostat is still calling for gas heating. The amber LED
light will flash code 12 during the 90--second period, after which
the LED will be ON continuous, as long as no faults are detected.
After the 90 -- second period, the furnace will respond to the
thermostat normally.
The blower door must be installed for power to be conducted
through the blower door interlock switch ILK to the furnace
control CPU, transformer TRAN, inducer motor IDM, blower
motor BLWM, hot--surface igniter HSI, and gas valve GV.
SINGLE--STAGE THERMOSTAT AND TWO--ST
HEATING (ADAPTIVE
See Fig. 19 or 50 for thermostat connections.
NOTE: Low--heat--only switch, SW1--2, selects either the low
heat--only operation mode when ON, (see item 2. below) or
adaptive heating mode when OFF, in response to a call for heat.
(See Fig. 33.) When the W2 thermostat terminal is energized, it
will always cause high--heat operation when the R to W circuit is
closed, regardless of the setting of the low-- heat only switch.
This furnace can operate as a two--stage furnace with a
single-- stage thermostat because furnace control CPU includes a
programmed adaptive sequence of controlled operation, which
selects low--heat or high--heat operation. This selection is based
upon the stored history of the length of previous gas heating
periods of the single-- stage thermostat.
The furnace will start up in either low-- or high--heat. If the
furnace starts up in low--heat, the furnace control CPU determines
the low--heat on time (from 0 to 16 minutes) which is permitted
before switching to high--heat.
MODE)
AGE
35
Page 36
If power is interrupted, the stored history is erased. When this
happens, the control CPU will initially select low--heat for up to
16 minutes and then switch to high-- heat, as long as the
thermostat continues to call for heat. Subsequent selection is
based on stored history of thermostat cycle times.
The wall thermostat “calls for heat,” closing the R to W circuit.
The furnace control CPU performs a self--check, verifies the
low-- heat and high --heat pressure switch contacts LPS and HPS
are open.
58UVB
Fig. 41 --- Inducer Housing Drain Tube
A06456
A06457
Fig. 42 --- Filling Condensate T rap
TABLE 10—BLOWER OFF DELAY S ETUP SWITCH
POSITION
DESIRED
HEATING MODE
BLOWER OFF
DELAY (SEC)
90OFFOFF
120ONOFF
150OFFON
180ONON
SETUP SWITCH (SW1 --- 7 AND
SW1---8) POSITION
S W 1 --- 7SW 1 --- 8
1. Inducer Prepurge Period--The furnace control CPU turns
on inducer motor IDM and slowly increases the inducer
motor speed. When the low--heat pressure switch LPS
closes, inducer motor RPM is noted by the furnace control
CPU, and a 25--sec. prepurge period begins. The RPM is
used to evaluate vent system resistance. This evaluation is
then used to determine the required RPM necessary to
operate the inducer motor during the low--heat prepurge
period and low--heat mode.
NOTE: The heat cycle can start in either high--or low-- heat. If a
high--heat cycle is initiated, the furnace control CPU will
deenergize the high--heat pressure switch relay HPSR to close the
NC contact and continues to increase the inducer motor speed
after the low--heat pressure switch LPS closes. When the
high--heat pressure switch closes, inducer motor RPM is noted by
the furnace control CPU before the 25 -- sec prepurge period
begins. The RPM is used to evaluate vent system resistance. This
evaluation is then used to determine the required RPM necessary
to operate the inducer motor in high--heat mode.
36
Page 37
2. Igniter Warm-- Up--At end of the prepurge period, the Hot
Surface Igniter HSI is energized for a 17--sec igniter
warm--up period.
3. Trial--For--IgnitionSequence--Whentheigniter
warm--up period is completed, the main gas valve relay
contacts GVR close to energize the gas valve GV, the gas
valve opens. The gas valve GV permits gas flow to the
burners where it is ignited by the Hot Surface Igniter HSI.
Five seconds after the GVR closes, a 2--second flame
period begins. The HSI igniter will remain energized until
the flame is sensed or until the 2 --second flame proving
period begins.
If the furnace control CPU selects high-- heat operation, the
high--heat gas valve solenoid GV--HI is also energized.
4. Flame--Proving-- When burner flame is proved at the
flame proving sensor electrode FSE, the furnace control
CPU begins the blower--ON delay period and continues to
hold the gas valve GV--M open. If the burner flame is not
proved within two seconds, the control CPU will close the
gas valve GV--M, and the furnace control CPU will repeat
theignitionsequenceforupto threemore
Trials--For--Ignition before going to Ignition --Lockout.
Lockout will be reset automatically after three hours, by
momentarily interrupting 115 vac power to the furnace, or
by interrupting 24 vac power at SEC1 or SEC2 to the
furnace control CPU (not at W/W1, G, R, etc.).
If flame is proved when flame should not be present, the
furnace control CPU will lock out of Gas--Heating mode
and operate the inducer motor IDM on high speed until
flame is no longer proved.
5. Inducer Speed Change-- If the cycle starts in low--heat,
the furnace control CPU reduces the inducer speed slightly
after flame sense. If cycle starts in high--heat, the furnace
control CPU increases the inducer speed 15 seconds after
flame sense. The reduction in speed in low--heat is to
optimize combustion for maximum efficiency.
6. Blower--On delay--If the burner flame is proven, the
blower--ON delay for low--heat and high--heat are as
follows:
Low--heat
opened, the BLWM is turned ON at low--heat airflow.
High--heat
the BLWM is turned ON at high-- heat airflow.
Simultaneously, the humidifier terminal HUM and
electronic air cleaner terminal EAC--1 are energized and
remain energized throughout the heating cycle.
7. Switching From Low -- To High-- Heat-- If the furnace
control CPU switches from low--heat to high--heat, the
furnace control CPU will de-- energize the the high--heat
pressure switch relay HPSR to close the NC contact and
slowly increase the inducer motor speed until the
high--heat pressure switch HPS closes.When the
high--heat pressure switch HPS closes, the high-- heat gas
valve solenoid GV--HI is energized and the inducer motor
RPM is noted by the furnace control CPU. The RPM is
used to evaluate vent system resistance. This evaluation is
then used to determine the required RPM necessary to
operate the inducer motor in high--heat mode. The blower
motor BLWM will transition to high --heat airflow five
seconds after the furnace control CPU switches from
low--heat to high--heat.
8. Switching From High-- To Low-- Heat--The furnace
control CPU will not switch from high--heat to low-- heat
while the thermostat R-- to-- W circuit is closed when using
a single--stage thermostat.
9. Blower--Off delay-- When the thermostat is satisfied, the
R to W circuit is opened, de--energizing the gas valve
GV--M, stopping gas flow to the burners, and
--30 seconds after the gas valve GV--M is
--35 seconds after gas valve GV--M is opened,
de--energizing the humidifier terminal HUM. The inducer
motor IDM will remain energized for a 15--second
post-- purge period. The blower motor BLWM and air
cleaner terminal EAC--1 will remain energized at low--heat
airflow or transition to low--heat airflow for 90, 120, 150,
or 180 seconds (depending on selection at blower--OFF
delay switches). The furnace control CPU is factory--set
for a 120--second blower--OFF delay.
TWO--STAGE THERMOSTAT AND TWO--ST
HEA
TING
See Fig. 49 for thermostat connections.
NOTE: In this mode, the low--heat only switch SW1 -- 2 must be
ON to select the low--heat only operation mode in response to
closing the thermostat R--to--W1 circuit. Closing the thermostat
R--to--W1--and--W2 circuits always causes high--heat operation,
regardless of the setting of the low--heat--only switch.
The wall thermostat “calls for heat,” closing the R toW1 circuit
for low--heat or closing the R to W1 --and-- W2 circuits for
high--heat.The furnace control performs a self--check and
verifies the low heat and high --heat pressure switch contacts LPS
and HPS are open.
The start--up and shutdown functions and delays described in
item 1. above apply to 2--stage heating mode as well, except for
switching from low-- to high--heat and vice versa.
1. Switching From Low-- To High-- Heat--If the thermostat
R to W1 circuit is closed and the R toW2 circuit closes, the
furnace control CPU will de--energize the high--heat
pressure switch relay HPSR to close the NC contact and
slowly increase the inducer motor speed until the
high--heat pressure switch HPS closes. When the
high--heat pressure switch closes, the high--heat gas valve
solenoid GV--HI is energized and the inducer motor RPM
is noted by the furnace control CPU. The RPM is used to
evaluate vent system resistance. This evaluation is then
used to determine the required RPM necessary to operate
the inducer motor in high--heat mode. The blower motor
BLWM will transition to high--heat airflow five seconds
after the R to W2 circuit closes.
2. Switching From High-- To Low-- Heat-- If the thermostat
R to W2 circuit opens, and the R to W1 circuit remains
closed, the furnace control CPU will energize the
high--heat pressure switch relay HPSR to open the NC
contact and slowly decrease the inducer motor speed to the
required low-- heat RPM. When the high --heat pressure
switch HPS opens, the high--heat gas valve solenoid
GV--HI is de-- energized. When the inducer motor IDM
reduces pressure sufficiently, the high--heat pressure
switch HPS will open. The gas valve solenoid GV-- M will
remain energized as long as the low--heat pressure switch
LPS remains closed. The blower motor BLWM will
transition to low--heat airflow five seconds after the R to
W2 circuit opens.
COOLING
The thermostat “calls for cooling.”
1. Single--Speed Cooling
MODE
(See Fig. 19 for thermostat connections.)
The thermostat closes R--to--G--and--Y circuits. The
R--to--Ycircuitstartstheoutdoorunit,and
R--to--G--and-- Y/Y2 circuits start the furnace blower motor
BLWM on cooling airflow. Cooling airflow is based on
the A/C selection shown in Fig. 39.
The electronic air cleaner terminal EAC--1 is energized
with 115--v when blower motor BLWM is operating.
When the thermostat is satisfied, the R-- to-- G-- and--Y
circuits are opened. The outdoor unit will stop, and
furnace blower motor BLWM will continue operating at
cooling airflow for an additional 90 sec. Jumper Y/Y2 to
AGE
58UVB
37
Page 38
DHUM to reduce the cooling off--delay to 5 seconds. (See
Fig. 33.)
2. Single--Stage Thermostat and Two--Speed Cooling
(Adaptive Mode)
(See Fig. 50 for thermostat connections.)
This furnace can operate a two --speed cooling unit with a
single-- stage thermostat because the furnace control CPU
includes a programmed adaptive sequence of controlled
operation, which selects low--cooling or high--cooling
operation. This selection is based upon the stored history
of the length of previous cooling period of the
single--stage thermostat.
NOTE: The air conditioning relay disable jumper ACRDJ must
be connected to enable the adaptive cooling mode in response to
a call for cooling. (See Fig. 33.) When in place the furnace
control CPU can turn on the air conditioning relay ACR to
energize the Y/Y2 terminal and switch the outdoor unit to
high--cooling.
The furnace control CPU can start up the cooling unit in
58UVB
either low-- or high--cooling. If starting up in
low--cooling, the furnace control CPU determines the
low--cooling on --time (from 0 to 20 minutes) which is
permitted before switching to high-- cooling.
If the power is interrupted, the stored history is erased
and the furnace control CPU will select low--cooling for
up to 20 minutes and then energize the air conditioning
relay ACR to energize the Y/Y2 terminal and switch the
outdoor unit to high--cooling, as long as the thermostat
continues to call for cooling. Subsequent selection is
based on stored history of the thermostat cycle times.
The wall thermostat “calls for cooling,” closing the R to
G--and--Y circuits. The R to Y1 circuit starts the outdoor
unit on low--cooling speed, and the R to G--and--Y1
circuits starts the furnace blower motor BLWM at
low--cooling airflow which is the true on--board CF
selectionasshowninFig.39.
If the furnace control CPU switches from low--cooling to
high--cooling, the furnace control CPU will energize the
air conditioning relay ACR. When the air conditioning
relay ACR is energized the R to Y1-- and--Y2 circuits
switch the outdoor unit to high--cooling speed, and the R
to G--and--Y1--and-- Y/Y2 circuits transition the furnace
blower motor BLWM to high cooling airflow.
High--cooling airflow is based on the A/C selection
shown in Fig. 39.
NOTE: When transitioning from low--cooling to high--cooling
the outdoor unit compressor will shut down for 1 minute while
the furnace blower motor BLWM transitions to run at
high--cooling airflow.
The electronic air cleaner terminal EAC-- 1 is energized
with 115 vac whenever the blower motor BLWM is
operating.
When the thermostat is satisfied, the R to G--and--Y
circuit are opened. The outdoor unit stops, and the
furnace blower BLWM and electronic air cleaner terminal
EAC-- 1 will remain energized for an additional 90
seconds. Jumper Y1 to DHUM to reduce the cooling
off--delay to 5 seconds. (See Fig. 33.)
3. Two--Stage Thermostat and Two-- Speed Cooling
(See Fig. 49 for thermostat connections)
NOTE: The air conditioning relay disable jumper ACRDJ must
be disconnected to allow thermostat control of the outdoor unit
staging. (See Fig. 33.)
The thermostat closes the R to G and--Y1 circuits for low
cooling or closes the R to G and--Y1--and-- Y2 circuits for
high--cooling. The R to Y1 circuit starts the outdoor unit
on low--cooling speed, and the R to G--and--Y1 circuit
starts the furnace blower motor BLWM on low--cooling
airflow which is the true on --board CF selection as shown
in Fig. 41. The R to Y1--and-- Y2 circuits start the outdoor
unit on high-- cooling speed, and the R to G --and --Y/Y2
circuits start the furnace blower motor BLWM at
high--cooling ariflow. High--cooling airflow is based on
the A/C selection shown in Fig. 39.
The electronic air cleaner terminal EAC-- 1 is energized
with 115 vac whenever the blower motor BLWM is
operating.
When the thermostat is satisfied, the R to G--and--Y1 or R
to G--and--Y1--and--Y2 circuits are opened. The outdoor
unit stops, and the furnace blower BLWM and electronic
air cleaner terminal EAC--1 will remain energized for an
additional 90 seconds. Jumper Y1 to DHUM to reduce
the cooling off-- delay to 5 seconds. (See Fig. 33.)
THERMIDISTAT
See Fig. 43 --46 for Thermidistat connections.
The dehumidification output, DHUM on the Thermidistat should
be connected to the furnace control thermostat terminal DHUM.
When there is a dehumidify demand, the DHUM input is
activated, which means 24 vac signal is removed from the
DHUM input terminal. In other words, the DHUM input logic is
reversed. The DHUM input is turned ON when no dehumidify
demand exists. Once 24 vac is detected by the furnace control on
the DHUM input, the furnace control operates in Thermidistat
mode. If the DHUM input is low for more than 48 hours, the
furnace control reverts back to non-- Thermidistat mode.
The cooling operation described in item 3. above applies to
operation with a Thermidistat. The exceptions are listed below:
1. Low cooling--When the R to G--and--Y1 circuit is closed
and there is a demand for dehumidification, the furnace
blower motor BLWM will drop the blower airflow to 86%
of low--cooling airflow which is the true on--board CF
selectionasshowninFig.39.
2. High cooling--When the R to G-- and Y/Y2 circuit is
closed and there is a demand for dehumidification, the
furnace blower motor BLWM will drop the blower airflow
to 86% of high--cooling airflow. High--cooling airflow is
basedontheA/CselectionshowninFig.39.
3. Cooling off--delay-- When the “call for cooling” is
satisfied and there is a demand for dehumidification, the
cooling blower--off delay is decreased from 90 seconds to
5 seconds.
SUPER--DEHUMIDIFY
Super--Dehumidify mode can only be entered if the furnace
control is in Thermidistat mode and there is a demand for
dehumidification. The cooling operation described in item 3.
above also applies to operation with a Thermidistat. The
exceptions are listed below:
1. Low cooling --When the R to Y1 circuit is closed, R to G
circuit is open, and there is a demand for dehumidification,
the furnace blower motor BLWM will drop the blower
airflow to 65% of low--cooling airflow for a maximum of
10 minutes each cooling cycle or until the R to G circuit
closes or the demand for dehumidification is satisfied.
Low-- cooling airflow is the true on--board CF selection as
shown in Fig. 39.
MODE
MODE
38
Page 39
2. High cooling--When the R to Y/Y2 cicuit is closed, R to
G circuit is open, and there is a demand for
dehumidifiation, the furnace blower motor BLWM will
drop the blower to 65% of high--cooling airflow for a
maximum of 10 minutes each cooling cycle or until the R
to G circuit closes or the demand for dehumidification is
satisfied. High--cooling airflow is based on the A/C
selectionshowninFig.39.
3. Cooling off--delay-- When the “call for cooling” is
satisfied and there is a demand for dehumidification, the
cooling blower--off delay is decreased from 90 seconds to
5 seconds.
CONTINUOUS BLOWER
When the R to G circuit is closed by the thermostat, the blower
motor BLWM will operate at continuous--blower airflow.
Continuous blower airflow selection is initially based on the CF
selection shown in Fig. 39. Factory default is shown in Fig. 39.
Terminal EAC--1 is energized as long as the blower motor
BLWM is energized.
During a call for heat, the blower BLWM will transition the
blower motor BLWM to continuous blower airflow, low--heat
airflow, or the midrange airflow, whichever is lowest. The blower
motor BLWM will remain ON until the main burners ignite then
shut OFF and remain OFF for the blower--ON delay (30 seconds
in low--heat and 35 seconds in high--heat) allowing the furnace
heat exchangers to heat more quickly, then restarts at the end of
the blower--ON delay period at low-- heat or high--heat airflow
respectively.
The blower motor BLWM will revert to continuous--blower
airflow after the heating cycle is completed. In high --heat, the
furnace control CPU will drop the blower motor BLWM to
low-- heat airflow during the selected blower--OFF delay period
before transitioning to continuous--blower airflow.
When the thermostat “calls for high--cooling,” the blower motor
BLWM will operate at high-- cooling airflow. When the
thermostat is satisfied, the blower motor BLWM will operate an
additional 90 seconds at high--cooling airflow before
transitioning back to continuous-- blower airflow.
When the R to G circuit is opened, the blower motor BLWM will
continue operating for an additional 5 seconds, if no other
function requires blower motor BLWM operation.
MODE
58UVB
39
Page 40
58UVB
A00275
Fig. 43 --- Two--Stage Furnace with Single--Speed
Air Conditioner
Fig. 45 --- Two--Stage Furnace with Single--Speed
Heat Pump (Dual Fuel)
A00277
Fig. 44 --- Two--Stage Furnace with Two--Speed
Air Conditioner
A00276
A00278
Fig. 46 --- Two--Stage Furnace with Two--Speed
Heat Pump (Dual Fuel)
40
Page 41
Fig. 47 --- Dual Fuel Thermostat with Two-- Stage
Furnace and Single--Speed Heat Pump
Fig. 48 --- Dual Fuel Thermostat With Two--Stage
Furnace and Two--Speed Heat Pump
A00279
A00280
A00281
Fig. 49 --- Two--Stage Thermostat With Two--Stage Furnace
and Two--Speed Air Conditioner
See note 2
A02348
Fig. 50 --- Single-- Stage Thermostat With Two--Stage
Furnace and Two--Speed Air Conditioner
58UVB
41
Page 42
Notes for Fig. 43 --50:
1. Heat pump MUST have a high pressure switch for dual fuel applications.
2. Refer to outdoor equipment Installation Instructions for additional information and setup procedure.
3. Select the “ZONE” position on the two--speed heat pump control.
4. Outdoor Air Temperature Sensor must be attached in all dual fuel applications.
5. Dip switch No.1 on Thermidistat should be set in OFF position for air conditioner installations. This is factory default.
6. Dip switch No. 1 on Thermidistat should be set in ON position for heat pump installations.
7. Dip switch No. 2 on Thermidistat should be set in OFF position for single--speed compressor operation.
8. Dip switch No. 2 on Thermidistat should be set in ON position for two--speed compressor operation.
9. Configuration Option No. 10 “Dual Fuel Selection” must be turned ON in all dual fuel applications.
10. NO connection should be made to the furnace HUM terminal when using a Thermidistat.
11. Optional connection. If wire is connected, dip switch SW1--2 on furnace control should be set in ON position to allow
12. Optional connection. If wire is connected, ACRDJ jumper on furnace control should be removed to allow Thermidistat/Thermostat to
13. Furnace must control its own high--stage heating operation via furnace control algorithm. This is factory default.
58UVB
14. The RVS Sensing terminal “L” should not be connected. This is internally used to sense defrost operation.
15. DO NOT SELECT the “FURNACE INTERFACE” or “BALANCE POINT” option on the two--speed heat pump control board. This
16. Dip switch D on Dual Fuel Thermostat should be set in OFF position for single-- speed compressor operation.
17. Dip switch D on Dual Fuel Thermostat should be set in ON position for two--speed compressor operation.
This is factory default.
Thermidistat/Thermostat to control furnace staging.
control outdoor unit staging.
is controlled internally by the Thermidistat/Dual Fuel Thermostat.
This is factory default.
42
Page 43
Continuous Blower Speed Selection from Thermostat
To select different continuous--blower speeds from the room
thermostat, momentarily turn off the FAN switch or push button
on the room thermostat for 1--3 seconds after the blower motor
BLWM is operating. The furnace control CPU will shift the
continuous--blower airflow from the factory setting to the next
highest CF selection airflow as shown in Fig. 39. Momentarily
turning off the FAN switch again at the thermostat will shift the
continuous--blower airflow up one more increment. If you repeat
this procedure enough, you will eventually shift the
continuous--blower airflow to the lowest CF selection as shown
in Fig. 39. The selection can be changed as many times as desired
and is stored in the memory to be automatically used following a
power interruption.
This feature is disabled when blower off delay is set for 180 sec.
PUMP
HEAT
See Fig. 45 --48 for thermostat connections.
When installed with a heat pump, the furnace control
automatically changes the timing sequence to avoid long blower
off times during demand defrost cycles. Whenever W/W1 is
energized along with Y1 or Y/Y2, the furnace control CPU will
transition to or bring on the blower motor BLWM at cooling
airflow, low-- heat airflow, or the midrange airflow, whichever is
the lowest. The blower motor BLWM will remain on until the
main burners ignite, then shut OFF and remain OFF for 25
seconds before coming back on at heating airflow. When the
W/W1 input signal disappears, the furnace control begins a
normal inducer post--purge period while changing the blower
airflow. If Y/Y2 input is still energized, the furnace control CPU
will transition the blower motor BLWM airflow to cooling
airflow. If Y/Y2 input signal disappears and the Y1 input is still
energized, the furnace control CPU will transition the blower
motor BLWM to low-- cooling airflow. If both the Y1 and Y/Y2
signals disappear at the same time, the blower motor BLWM will
remain on at low--heat airflow for the selected blower--OFF delay
period. At the end of the blower--OFF delay, the blower motor
BLWM will shut OFF unless G is still energized, in which case
the blower motor BLWM will operate at continuous blower
airflow.
COMPONENT
The furnace features a component test system to help diagnose a
system problem in the case of a component failure. To initiate the
component test procedure, ensure that there are no thermostat
inputs to the control and all time delays have expired. Turn on
setup switch SW1--6 (See Fig. 33.)
NOTE: The component test feature will not operate if the control
is receiving any thermostat signals or until all time delays have
expired.
The component test sequence is as follows:
1. The furnace control CPU turns the inducer motor IDM
ON at medium speed and keeps it ON through step c.
2. After waiting 15 seconds, the furnace control CPU turns
the hot surface igniter ON for 15 seconds, then OFF.
3. The furnace control CPU then turns the blower motor
BLWM ON at midrange airflow for 15 seconds, then OFF.
4. After shutting the blower motor BLWM OFF, the furnace
control CPU shuts the inducer motor IDM OFF.
NOTE: The EAC terminals are energized when the blower is
operating.
After the component test is completed, 1 or more status codes (11,
25, 41, or 42) will flash. See Service Label on blower access
panel or Service/Status Code Instructions for explanation of
status codes.
NOTE: To repeat component test, turn setup switch SW1--6 to
OFF and then back ON.
TEST
Step 6 —Adjustments
SETGASINPUTRATE
Furnace gas input rate on rating plate is for installations at
altitudes up to 2000 ft.
In the U.S.A., the input rating for altitudes above 2000 ft must be
reduced by 2 percent for each 1000 ft above sea level.
In Canada, the input rating must be derated by 5 percent for
altitudes of 2000 ft to 4500 ft above sea level.
Adjust manifold pressure to obtain input rate.
Furnace input rate must be within ¦2 percent of input rate on
furnace rating plate.
1. Determine natural gas orifice size and manifold pressure
for correct input.
a. Obtain average heat value (at installed altitude) from
local gas supplier.
b. Obtain average specific gravity from local gas supplier.
c. Verify furnace model. Table 11 can only be used for
model 58UVB Furnaces.
d. Find installation altitude in T able 11.
NOTE: For Canadian altitudes of 2000 to 4500 ft, use U.S.A.
altitudes of 2001 to 3000 ft in Table 11.
e. Find closest natural gas heat value and specific gravity
in Table 11.
f. Follow heat value and specific gravity lines to point of
intersection to find orifice size and low-- and high--heat
manifold pressure settings for proper operation.
EXAMPLE: (0 -- 2000 ft altitude)
Heating value = 1050 Btu/cu ft
Specific gravity = 0.62
Therefore: Orifice No. 45
Manifold pressure: 3.8--in. wc for high heat
1.6--in. wc for low heat
* Furnace is shipped with No. 45 orifices. In this
example, all main burner orifices are the correct size and
do not need to be changed to obtain proper input rate.
g. Check and verify burner orifice size in furnace.
NEVER ASSUME ORIFICE SIZE; ALWAYS
CHECK AND VERIFY.
2. Adjust manifold pressure to obtain input rate.
a. Remove burner enclosure front.
NOTE: Manifold pressure MUST always be measured with the
burner box cover REMOVED.
b. Remove regulator seal caps that conceal adjustment
screws for low-- and high--heat gas valve regulators.
(See Fig 51.)
c. MovesetupswitchSW1--2oncontrolcentertoON
position. (See Fig. 33.) This keeps furnace locked in
low--heat operation.
d. Jumper R and W/W1 thermostat connections on
control to start furnace.
e. Turn low--heat adjusting screw (3/32) hex Allen
wrench) counterclockwise (out) to decrease input rate
or clockwise (in) to increase input rate.
NOTE: DO NOT set low--heat manifold pressure less than
1.3--in. wc or more than 1.7--in. wc for natural gas. If manifold
pressure is outside this range, change main burner orifices to
obtain manifold pressure in this range.
58UVB
43
Page 44
TABLE 11—ORIFICE SIZE* AND MANIFOLD PRESSURES FOR GAS INPUT RATE
*
(TABULATED DATA BASED ON 20,000 BTUH HIGH--HEAT/13,000 BTUH LOW--HEAT PER BURNER,
Orifice numbers shown inBOLD are factory-installed.
A97386
45
Page 46
INLET
PRESSURE
TAP
ON/OFF
SWITCH
ON
LOW-FIRE
ADJUSTMENT
ALLEN SCREW
(UNDER CAP)
HIGH-FIRE
ADJUSTMENT
ALLEN SCREW
O
F
F
(UNDER CAP)
58UVB
ENCLOSURE
REFERENCE
PRESSURE TAP
Fig. 51 --- Redundant Automatic Gas Valve
!
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in reduced furnace
life, property damage, personal injury, and death.
DO NOT bottom out gas valve regulator adjusting screw.
This can result in unregulated manifold pressure and result
in excess overfire and heat exchanger failures.
NOTE: If orifice hole appears damaged or it is suspected to have
been redrilled, check orifice hole with a numbered drill bit of
correct size. Never redrill an orifice. A burr--free and squarely
aligned orifice hole is essential for proper flame characteristics.
f. Move setup switch SW1--2 to OFF position after
completing low--heat adjustment.
g. Jumper R and W/W1 and W2 thermostat connections
on furnace control. (See Fig. 33.) This keeps furnace
locked in high--heat operation.
h. Turn high--heat adjusting screw (3/32 hex Allen
wrench) counterclockwise (out) to decrease input rate
or clockwise (in) to increase rate.
NOTE: DO NOT set high--heat manifold pressure less than
3.2--in. wc or more than 3.8--in. wc for natural gas. If manifold
pressure is outside this range, change main burner orifices to
obtain manifold pressures in this range.
i. When correct input is obtained, replace caps that
conceal gas valve regulator adjustment screws. Main
burner flame should be clear blue, almost transparent.
(See Fig. 53.)
j. Remove jumpers R to W/W1 and R to W2
BURNER
MANIFOLD
PRESSURE
A097386
TAP
BURNER
ORIFICE
Fig. 52 --- Burner Orifice
3. Verify natural gas input rate by clocking gas meter.
NOTE: Be sure all pressure tubing, combustion--air and vent
pipes, and burner enclosure front are in place when checking
input by clocking gas meter.
a. Calculate high-- altitude adjustment (if required).
UNITED STATES
At altitudes above 2000 ft, this furnace has been
approved for a 2 percent derate for each 1000 ft above
sea level. See Table 12 for derate multiplier factor and
example.
CANADA
At installation altitudes from 2000 to 4500 ft, this
furnace must be derated 5 percent by an authorized
Gas Conversion Station or Dealer. To determine
correct input rate for altitude, see example and use
0.95 as derate multiplier factor.
EXAMPLE: 100,000 BTUH HIGH--HEAT INPUT
FURNACE INSTALLED AT 4,300 FT
A93059
Furnace Input Rate at Sea Level X Derate Multiplier
Factor = Furnace Input Rate at Installation Altitude
100,000X 0.91 = 91,000
b. Reinstall burner box cover.
46
Page 47
NOTE: Clocking gas input rate MUST always be performed
with the burner box cover INSTALLED.
c. Check that gas valve adjustment caps are in place for
proper input to be clocked.
d. Obtain average heat value (at altitude) from local gas
supplier.
NOTE: Be sure heating value of gas used for calculations is
correct for your altitude. Consult local gas utility for altitude
adjustment of gas heating value.
e. Check and verify orifice size in furnace. NEVER
ASSUME THE ORIFICE SIZE. ALWAYS CHECK
AND VERIFY.
f. Turn off all other gas appliances and pilots.
g. Move setup switch SW1--2 to ON position. (See Fig.
33.) This keeps furnace locked in low-- heat operation.
BURNER FLAME
BURNER
!
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in component
damage due to flame impingement of burners and heat
exchangers.
DO NOT redrill orifices. Improper drilling (burrs,
out--of--round holes, etc.) can cause excessive burner noise
and misdirection of burner flames. (See Fig. 52.)
EXAMPLE: (High--heat operation at 0 -- 2000 ft altitude)
Furnace input from rating plate is 100,000 Btuh
Btuh heating input = Btuh/cu ft X cu ft/hr
Heating value of gas = 975 Btuh/cu ft
Time for 1 revolution of 2 --cu ft dial = 70 sec
Gas rate = 103 cu ft/hr (from Table 13)
Btuh heating input = 103 X 975 = 100,425 Btuh
In this example, the orifice size and manifold pressure
adjustment is within ±2 percent of the furnace input rate.
NOTE: Measured gas inputs (high heat and low heat) must be
within ±2 percent of that stated on furnace rating plate when
installed at sea level or derated per that stated above when
installed at higher altitudes.
n. Remove jumper across R, W/W1, and W2 thermostat
* Derate multiplier factor is based on midpoint altitude for al titude range
h. Jumper R to W/W1.
i. Let furnace run for 3 minutes in low-- heat operation.
j. Measure time (in sec) for gas meter to complete 1
revolution. Note reading.
k. Refer to Table 13 for cubic ft of gas per hr.
l. Multiply gas rate cu ft/hr by heating value (Btu/cu ft).
m. Move setup switch SW1--2 to OFF position and
jumper R and W/W1 and W2 thermostat connections.
(See Fig. 33.) This keeps furnace locked in high--heat
operation. Repeat items i through l for high--heat
operation.
%OF
DERATE
DERATE MULTIPLIER
FACTOR FOR U.S.A.*
!
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in overheating the
heat exchangers or condensing flue gases in heat exchanger
areas not designed for condensate.
Temperature rise must be within limits specified on unit
rating plate. Operation is within a few degrees of midpoint
ofriserangewhensetupswitchSW1--4isOFF.
Furnace must operate within ranges of temperature rise specified
on the furnace rating plate. Determine air temperature rise as
follows:
1. Place thermometers in return and supply ducts as near
furnace as possible. Be sure thermometers do not see heat
exchanger so that radiant heat does not affect readings.
This practice is particularly important with straight--run
ducts.
2. When thermometer readings stabilize, subtract return-- air
temperature from supply--air temperature to determine air
temperature rise.
NOTE:Temperature rise can be determined for low-- heat
operation by placing setup switch SW1--2 on furnace control in
ON position. For high --heat operation, place setup switch SW1-- 2
in OFF position and jumper R-- W2 on furnace control. DO NOT
forget to return setup switch to OFF position and remove R--W2
jumper upon completion of testing. (See Fig. 33 for switch and
terminal location.)
47
Page 48
TABLE 13—GAS RATE CU FT/HR
SECONDSSIZE OF TEST DIALSECONDSSIZE OF TEST DIAL
FOR 1
REVOLUTIONcu ftcu ftcu ftREVOLUTIONcu ftcu ftcu ft
3. This furnace is capable of automatically providing proper
airflow to maintain the temperature rise within the range
specified on furnace rating plate. If temperature rise is
outside this range, proceed as follows:
a. Check gas input for low-- and high--heat operation.
b. Check derate for altitude if applicable.
c. Check all return and supply ducts for excessive
restrictions causing static pressure greater than 0.5--in.
wc.
d. Ensure Low Heat Rise Adjust switch SW1--3 on
furnace control is in ON position when a bypass
humidifier is used. (See Fig. 33 for switch location.)
e. Check Troubleshooting Guide for Variable--Speed
2--Stage Electronic Condensing Furnaces Series 100.
SETTHERMOSTATHEATANTICIPAT
OR
When using a non--electronic thermostat, the thermostat heat
anticipator must be set to match the amp draw of components in
the R--W/W1 circuit. Accurate amp draw measurements can be
obtained only at the thermostat subbase terminals R and W.
The thermostat and anticipator should NOT be in the circuit while
measuring current. If thermostat has no subbase, the thermostat
must be disconnected from R and W/W1 wires during current
measurement.
Fig. 54 illustrates an easy method of obtaining thermostat amp
draw measurements. The amp reading should be taken after
blower motor has started and furnace is operating in low--heat.
1. To operate furnace in low--heat, turn setup switch SW1--2
to ON position (See Fig. 33) and connect ammeter leads
across thermostat subbase R--W.
2. See thermostat manufacturer’s instructions for adjusting
the heat anticipator and for varying heating cycle length.
NOTE: When using an electronic thermostat, set cycle rate for 3
cycles per hr.
3. Return setup switch SW1--2 to OFF position and replace
thermostat on subbase.
Step 7 —Check Safety Controls
This section covers the safety controls that must be checked
before the installation is complete. The flame sensor, gas valve,
and pressure switches were all checked in the Start--up procedure
section as part of normal operation.
CHECK PRIMARY LIMIT
This control shuts off the gas control system and energizes the
air--circulating blower motor if furnace overheats.
CONTROL
48
Page 49
1. The recommended method of checking this limit control is
to gradually block off return air after furnace has been
operating for a period of at least 5 minutes.
THERMOSTAT SUBBASE
TERMINALS WITH
THERMOSTAT REMOVED
(ANITICIPATOR, CLOCK, ETC.,
MUST BE OUT OF CIRCUIT.)
HOOK-AROUND
AMMETER
R Y W G
CHECKLIST
1. Put away tools and instruments. Clean up debris.
2. Verify flame rollout manual reset switch has continuity.
3. Ve rify that blower and main access doors are properly
installed.
4. Cycle test furnace with room thermostat.
5. Check operation of accessories per manufacturer’s
instructions.
6. Review User’s Manual with owner.
7. Leave literature packet near
furnace.
10 TURNS
FROM UNIT 24-V
CONTROL TERMINALS
EXAMPLE:
5.0 AMPS ON AMMETER
10 TURNS AROUND JAWS
0.5 AMPS FOR THERMOSTAT
=
ANTICIPATOR SETTING
A96316
Fig. 54 --- AmpDrawwithAmmeter
2. As soon as limit control has shut off burners, a status code
33 will appear on furnace control.
3. The return--air opening should be unblocked to permit
normal air circulation.
By using this method to check the limit control, it can be
established that the limit is functioning properly and the furnace
will operate safely if there is a restricted return--air duct or motor
failure. If the limit control does not function during this test, the
cause must be determined and corrected.
CHECK PRESSURE
SWITCHES
This control proves operation of the draft inducer. Check switch
operation as follows:
1. Turn off 115--v power to furnace.
2. Remove control access door and disconnect inducer motor
12--pin wire harness at inducer motor.
3. Turn on 115-- v power to furnace.
4. Set thermostat to “call for heat.” When pressure switches
are functioning properly, status code 42 will flash on
furnace control approximately 20 sec after thermostat
switch is closed. If either a status code 31 or 32 is flashed
when inducer motor is disconnected, the furnace will shut
itself down immediately. Determine the reason pressure
switches did not function properly and correct the
condition.
5. Turn off 115--v power to furnace.
6. Reconnect inducer motor wire harness. Reinstall furnace
access door.