Carrier 58STX09010016, 58STX11010012, 58STX09010014, 58STX07010012, 58STX07010016 Installation Guide

...
Installation, Start-up, Operating and
Service and Maintenance Instructions
SAFETY CONSIDERATIONS ........................ 2
INTRODUCTION .................................. 3
CODES AND STANDARDS .......................... 4
Safety ......................................... 4
General Installation ............................... 4
Combustion and Ventilation Air ..................... 4
Duct Systems ................................... 5
Acoustical Lining and Fibrous Glass Duct ............. 5
Gas Piping and Gas Pipe Pressure Testing ............. 5
Electrical Connections ............................ 5
Venting ........................................ 5
LOCATION ....................................... 5
AIR FOR COMBUSTION AND VENTILATION ......... 7
INSTALLATION .................................. 10
Bottom Return Air Inlet .......................... 10
Side Return Air Inlet ............................. 10
Leveling Legs (If Desired) ........................ 11
Bottom Return Air Inlet .......................... 12
Suspended Furnace Support ....................... 12
Platform Furnace Support ......................... 12
Roll-Out Protection ............................. 12
Bottom Return Air Inlet .......................... 12
Side Return Air Inlet ............................. 12
General Requirements ............................ 13
Ductwork Acoustical Treatment .................... 13
Supply Air Connections .......................... 13
Return Air Connections .......................... 19
115-V Wiring .................................. 21
J-box Relocation ............................... 21
Electrical Connection to J-Box ..................... 21
Power Cord Installation in Furnace J-Box ............ 22
BX Cable Installation in Furnace J-Box .............. 22
24-V Wiring ................................... 24
Accessories .................................... 24
General Venting Requirements ..................... 24
Masonry Chimney Requirements ................... 25
Appliance Application Requirements ................ 27
Sidewall Venting ................................ 27
START-UP, ADJUSTMENT, AND SAFETY CHECK ..... 32
General ....................................... 32
Start-Up Procedures ............................. 32
Adjustments ................................... 37
Check Safety Controls ........................... 37
Checklist ...................................... 38
SERVICE AND MAINTENANCE PROCEDURES ....... 43
Introduction ................................... 43
Care and Maintenance ........................... 44
Sequence of Operation ........................... 47
Wiring Diagrams ............................... 48
Troubleshooting ................................ 48
PARTS REPLACEMENT INFORMATION GUIDE ....... 51
Use of tile AIIR[ Cmlified 1-,i Mark indicates a manulilcturer's pallicipation in the program. ]or verification (if cellification lbr individual products, go to www.ahridJreclory.org.
ISO9001
NOTE: Read the entire instruction manual before starting the installation.
Portions of the text and tables are reprinted from NFPA 54/ANSI Z223.1-2012©, with pernfission of Nation Fire Protection
Association, Quincy, MA 02269 and American Gas Association, Washington DC 20001. This reprinted material is not the
complete and official position of the NFPA or ANSI on the referenced subject, which is represented only by the standard in its entirely.
SAFETY CONSIDERATIONS
FIRE, EXPLOSION, ELECTRICAL SHOCK, AND
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal iniury, death, or property damage.
Improper installation, adjustment, alteration, service, maintenance, or use can cause carbon monoxide poisoning, explosion, fire, electrical shock, or other conditions which may cause personal iniury or property damage. Consult a qualified service agency, local gas supplier, or your
distributor or branch for information or assistance. The qualified service agency must use only factory-authorized
and listed kits or accessories when modifying this product.
FURNACE RELIABILITY HAZARD Failure to follow this caution may result in unit component
damage. Application of this furnace should be indoors with special
attention given to vent sizing and material, gas input rate, air temperature rise, unit leveling, and unit sizing.
CUT HAZARD Failure to follow this caution may result in personal iniury.
Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate protective clothing, safety glasses and gloves when handling parts, and servicing furnaces.
Improper installation, adjustment, alteration, service, maintenance, or use can cause explosion, fire, electrical shock, or other conditions which may cause death, personal injury, or
property damage. Consult a qualified installer, service agency, or your distributor or branch for information or assistance. The
qualified installer or agency must use factory-authorized kits or accessories when modifying this product. Refer to the individual instructions packaged with the kits or accessories when installing.
Follow all safety codes. Wear safety glasses, protective clothing, and work gloves. Have a fire extinguisher available. Read these
instructions thoroughly and follow all warnings or cautions include in literature and attached to the unit. Consult local
building codes, the current editions of the National Fuel Gas Code (NFGC) NFPA 54/ANSI Z223.1 and the National
Electrical Code (NEC) NFPA 70.
Recognize safety information. This is the safety-alert symbol/_. When you see this symbol on the unit and in instructions or manuals, be alert to the potential for personal iniury.
Understand the signal words DANGER, WARNING, and CAUTION. These words are used with the safety-alert symbol.
DANGER identifies the most serious hazards which will result in severe personal iniury or death. WARNING signifies hazards
which could result in personal iniury or death. CAUTION is used to identify unsafe practices which may result in minor
personal iniury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced
installation, reliability, or operation.
1. Use only with type of gas approved for this furnace. Refer to the furnace rating plate.
2. Install this furnace only in a location and position as spe- cified in the "Location" section of these instructions.
3. Provide adequate combustion and ventilation air to the furnace space as specified in "Air for Combustion and
Ventilation" section.
4. Combustion products must be discharged outdoors. Con- nect this furnace to an approved vent system only, as spe-
cified in the "Venting" section of these instructions.
5. Never test for gas leaks with an open flame. Use a com- mercially available soap solution made specifically for the
detection of leaks to check all connections, as specified in the "Gas Piping" section.
6. Always install furnace to operate within the furnace's in- tended temperature-rise range with a duct system which
has an external static pressure within the allowable range, as specified in the "Start-Up, Adjustments, and Safety
Check" section. See furnace rating plate.
7. When a furnace is installed so that supply ducts carry air circulated by the furnace to areas outside the space con- taining the furnace, the return air shall also be handled by
duct(s) sealed to the furnace casing and terminating out- side the space containing the furnace. See "Air Ducts" sec-
tion.
8. A gas-fired furnace for installation in a residential garage must be installed as specified in the warning box in the
"Location" section.
9. The furnace may be used for construction heat provided that the furnace installation and operation complies with
the first CAUTION in the LOCATION section of these in- structions.
10. These Multipoise Gas-Fired Furnaces are CSA (formerly A.G.A. and C.G.A.) design-certified for use with natural
and propane gases (see furnace rating plate) and for install- ation in alcoves, attics, basements, closets, utility rooms,
crawlspaces, and garages. The furnace is factory-shipped for use with natural gas. A CSA (A.G.A. and C.G.A.) lis-
ted accessory gas conversion kit is required to convert fur- nace for use with propane gas.
11. See Fig. 1 for required clearances to combustible construc- tion.
12. Maintain a 1-in. (25 mm) clearance from combustible ma- terials to supply air ductwork for a distance of 36 in. (914
mm) horizontally from the furnace. See NFPA 90B or loc- al code for further requirements.
13. These furnaces SHALL NOT be installed directly on car- peting, tile, or any other combustible material other than
wood flooring. In downflow installations, factory access- ory floor base MUST be used when installed on combust-
ible materials and wood flooring. Special base is not re- quired when this furnace is installed on manufacturer's
Coil Assembly Part No. CNPV, CNRV, CAR or CAP or when Coil Box Part No. KCAKC is used. See Fig. 1 for
clearance to combustible construction information.
f_7/8
1/16
[4a_
,,@/,°
51/2 _R_Ctt# _52/_
--TOp OF¢.A_NG
[14a_
Q
_B
27 @/4
57/S--
[!;_;t
71_511/15
1
_ 21.6
tT,_,_1 [15sN
BOTTOM_T
NOTES:
1. Two additional 7/8-in. (22 mm) diameter holes are located in the top plate.
2. Minimum return-air openings at furnace, based on metal duct. If flex duct is used, see flex duct manufacturer's recommendations for equivalent diameters. (a,) For 800 CFM-16-in. (406 mm) round or 14 1/2 x 12-in. (368 x 305 mm) rectangle.
(b.) For 1200 CFM-20-in. (508 mm) round or 14 1/2 x 19 1/2-in. (368 x 495 mm) rectangle,
(c.) For 1600 CFM-22-in. (559 mm) round or 14 1/2 x 22 1/16-in. (368 x 560mm) rectangle.
(d.) For airflow requirements above 1800 CFM, see Air Delivery table in Product Data literature for specific use of single side inlets. The use of both side
inlets, a combination of 1 side and the bottom, or the bottom only will ensure adequate return air openings for airflow requirements above 1800 CFM.
FURNACE SIZE A B C D VENT SHIP WT
CABINET OUTLET TOP & BOTTOM BOTTOM CONNECTION LB (KG)
WIDTH WIDTH FLUE COLLAR INLET WIDTH SIZE
045 - 08/024045 045 - 12/036045 070 - 08/024070
070 - 12/036070 070 - 16/048070 090 - 14/042090 090 - 16/048090 090 - 20/080090
110-12/038110 110-16/048110 110-22/088110 135-16/048135 135 -22/088135
155 -20/080155
"135 and 155 size furnaces require a 5 or 6-in. complete installation requirements.
14-3/16 (360) 12-9/16 (319) 9-5/16 (237) 12-11/16 (322) 4 (102) 104 (47) 14-3/16 (360) 12-9/16 (319) 9-5/16 (237) 12-11/16 (322) 4 (102) 107 (49) 14-3/16 (360) 12-9/16 (319) 9-5/16 (237) 12-11/16 (322) 4 (102) 111 (50) 14-3/16 (360) 12-9/16 (319) 9-5/16 (237) 12-11/16 (322) 4 (102) 115 (52)
17-1/2 (445) 15-7/8 (403) 11-9/16 (294) 16 (406) 4 (102) 126 (57) 17-1/2 (445) 15-7/8 (403) 11-9/16 (294) 16 (406) 4 (102) 127 (58)
21 (533) 19-3/8 (492) 13-5/16 (338) 19-1/2 (495) 4 (102) 140 (64) 21 (533) 19-3/8 (492) 13-5/16 (338) 19-1/2 (495) 4 (102) 146 (66)
17-1/2 (445) 15-7/8 (403) 11-9/16 (294) 16 (406) 4 (102) 135 (61)
21 (533) 19-3/8 (492) 13-5/16 (338) 19-1/2 (495) 4 (102) 146 (66) 21 (533) 19-3/8 (492) 13-5/16 (338) 19-1/2 (495) 4 (102) 152 (69)
21 (533) 19-3/8 (492) 13-5/16 (338) 19-1/2 (495) 4 (102)* 149 (68) 24-1/2 (622) 22-7/8 (581) 15-1/16 (383) 23 (584) 4 (102)* 163 (74) 24-1/2 (622) 22-7/8 (581) 15-1/16 (383)
(127 or
152 mm) vent. Use a vent adapter between furnace and vent stack. See Installation Instructions for
LOCATION
Fig. 1 - Dimensional Drawing
[15.1_
I N_N
23 (584) 4 (102)* 170 (77)
A10290
improper adjustment, alteration, service, maintenance, or installation can cause serious injury or death.
Read and follow instructions and precautions in User's Information Manual
provided with this furnace. Installation
and service must be performed by a
qualified service agency or the gas
supplier.
Check entire gas assembly for leaks after lighting this appliance.
iNSTALLATION
1. This furnace must be installed in accordance with the manufacturer's
instructions and local codes. In the absence of local codes, follow the National
Fuel Gas Code ANSI Z223.1 / NFPA54 or CSA B-149. 1 Gas Installation Code.
2. This furnace must be installed so there are provisions for combustion and ventilation
air. See manufacturer's installation information provided with this appliance.
OPERATION
This furnace is equipped with manual reset limit switch(es) in burner compartment to
protect against overheat conditions that can result from inadequate combustion air
supply or blocked vent conditions.
1. Do not bypass limit switches.
2. If a limit opens, call a quallified serviceman to correct the condition
and reset limit switch.
Fig. 2 - Clearances to Combustibles
MiNiMUMiNCHESCLEARANCETOCOMBUSTIBLECONSTRUCTION
This forced air furnace is
equipped for use with natural gas at altitudes 0 - 10,000 ft
(0 - 3,050m).
An accessory kit, supplied by
the manufacturer, shall be used to convert to propane gas use or may be required for some
natural gas applications.
This furnace is for indoor
installation in a building constructed on site.
This furnace may be installed
on combustible flooring in alcove or closet at minimum clearance
as indicated by the diagram from combustible material.
This furnace may be used with
a Type B-1 Vent and may be vented in common with other
gas fired appliances.
This furnace is approved for UPFLOW, DOWNFLOW, and
HORIZONTAL installations.
Clearancearrows donotchangewith
furnaceorientation.
Clearancein inches
Vent Clearance to combustibles:
For SingleWallvents 6 inches(6 po). ForType B-1 venttype I inch (1 po).
MINIMUM INCHES CLEARANCE TO
COMBUSTIBLE CONSTRUCTION
DOWNFLOWPOSiTiONS:
1-
Installation on non-combustible floors only. For Installation on combustible flooring only when installed on special
base, Part No. KGASB0201ALL or NAHA01101SB, Coil Assembly, Part No. CAR, CAP, CNPV, CNRV, END4X, ENW4X, WENC, WTNC,
WENW OR WTNW. 18 inches front clearance required for alcove.
O
Indicates supply or return sides when furnace is in the horizontal position. Line contact only permissible between lines formed by
intersections of the Top and two Sides of the furnace jacket, and building joists, studs or framing.
IIIIIIIIIIIIIIIIIIIIIIIIIII
336996-161 REV. C
A10269
! MAX80°F/27C
o
FRONT
__ :_ MIN60°F/16C
A06745
Fig. 3 - Return Air Temperature
INTRODUCTION
This 4-way nmltipoise Category I fan-assisted furnace is CSA design-certified. A Category I fan-assisted furnace is an appliance equipped with an integral mechanical means to either
draw or force products of combustion through the combustion
chamber and/or heat exchanger. The furnace is factory-shipped for use with natural gas. This furnace is not approved for
installation in mobile homes, recreational vehicles, or outdoors. This furnace is designed for minimum continuous return-air
temperature of 60 °F (16 ° C) db or intermittent operation down to 55°F (13°C) db such as when used with a night setback
thermostat. Return-air temperature must not exceed 80 ° F (27 °C) db. Failure to follow these return-air temperature limits may
affect reliability of heat exchangers, motors, and controls. (See Fig. 3.)
For accessory installation details, refer to the applicable instruction literature.
NOTE: Remove all shipping brackets and materials before operating the furnace.
CODES AND STANDARDS
Follow all national and local codes and standards in addition to these instructions. The installation nmst comply with
regulations of the serving gas supplier, local building, heating, plumbing, and other codes. In absence of local codes, the
installation must comply with the national codes listed below and all authorities having jurisdiction. In the United States, follow all
codes and standards for the following:
Step 1 mSafety
National Fuel Gas Code (NFGC) NFPA 54-2012/AN- SI Z223.1-2012 and the Installation Standards, Warm
Air Heating and Air Conditioning Systems ANSI/
NFPA 90B
Step 2
Step 3
Step 4
Step 5
mGeneral Installation
Current edition of the NFGC and the NFPA 90B. For copies, contact the National Fire Protection Association
Inc., Batterymarch Park, Quincy, MA 02269; (www.NFPA.org) or for only the NFGC, contact the
American Gas Association, 400 N. Capitol Street,
N.W., Washington, DC 20001 (www.AGA.org).
mCombustion and Ventilation Air
Section 9.3 of the NFGC, NFPA 54 / ANSI Z223.1-2012 Air for Combustion and Ventilation
_Duct Systems
Air Conditioning Contractors Association (ACCA)
Manual D, Sheet Metal and Air Conditioning Contract- ors National Association (SMACNA), or American
Society of Heating, Refrigeration, and Air Condition- ing Engineers (ASHRAE) 2001 Fundamentals Hand-
book Chapter 34 or 2000 HVAC Systems and Equip-
ment Handbook Chapters 9 and 16.
---Acoustical Lining and Fibrous Glass
Duct
Current edition of SMACNA and NFPA 90B as tested by UL Standard 181 for Class I Rigid Air Ducts
Step 6 _Gas Piping and Gas Pipe Pressure Testing
NFGC; NFPA 54 / ANSI Z223.1-2012 chapters 5, 6, 7
and 8 and National Plumbing Codes
Step 7 _Electrical Connections
National Electrical Code (NEC) ANSI/NFPA 70-2011
Step 8 inVenting
NFGC NFPA 54 / ANSI Z223.1-2012; chapters 12
and 13
ELECTROSTATIC DISCHARGE (ESD)
PRECAUTIONS PROCEDURE
FURNACE RELIABILITY HAZARD Failure to follow this caution may result in furnace
component damage. Electrostatic discharge can affect electronic components.
Follow the Electrostatic Discharge Precautions Procedure listed below during furnace installation and servicing to
protect the furnace electronic control. Precautions will prevent electrostatic discharges from personnel and hand
tools which are held during the procedure. These precautions will help to avoid exposing the control to electrostatic discharge by putting the furnace, the control, and the person at the same electrostatic potential.
1. Disconnect all power to the furnace. Multiple disconnects
may be required. DO NOT TOUCH THE CONTROL OR
ANY WIRE CONNECTED TO THE CONTROL PRIOR TO DISCHARGING YOUR BODY'S
ELECTROSTATIC CHARGE TO GROUND.
2. Firmly touch the clean, unpainted, metal surface of the fur- nace chassis which is close to the control. Tools held in a
person's hand during grounding will be satisfactorily dis- charged.
3. After touching the chassis, you may proceed to service the control or connecting wires as long as you do nothing to
recharge your body with static electricity (for example; DO NOT move or shuffle your feet, do not touch un-
grounded objects, etc.).
4. If you touch ungrounded objects (and recharge your body with static electricity), firmly touch a clean, unpainted
metal surface of the furnace again before touching control or wires.
5. Use this procedure for installed and uninstalled (ungroun- ded) furnaces.
6. Before removing a new control from its container, dis- charge your body's electrostatic charge to ground to pro- tect the control from damage. If the control is to be in-
stalled in a furnace, follow items 1 through 4 before bringing the control or yourself in contact with the fur-
nace. Put all used and new controls into containers before touching ungrounded objects.
7. An ESD service kit (available from commercial sources) may also be used to prevent ESD damage.
LOCATION
CARBON MONOXIDE POISONING AND UNIT
DAMAGE HAZARD
Failure to follow this warning could result in personal injury or death, and unit component damage.
Corrosive or contaminated air may cause failure of parts containing flue gas, which could leak into the living space. Air for combustion must not be contaminated by halogen compounds, which include fluoride, chloride, bromide, and iodide. These elements can corrode heat exchangers and
shorten furnace life. Air contaminants are found in aerosol sprays, detergents, bleaches, cleaning solvents, salts, air
fresheners, and other household products. Do not install furnace in a corrosive or contaminated atmosphere. Make sure all combustion and circulating air requirements are met,
in addition to all local codes and ordinances.
GENERAL
This multipoise furnace is shipped in packaged configuration. Some assembly and modifications are required when used in any
of the four applications shown in Fig. 4. This furnace must:
be installed so the electrical components are protected from water.
not be installed directly on any combustible material other than wood flooring for upflow applications.
Downflow installations require use of a factory-ap- proved floor base or coil assembly when installed on combustible materials or wood flooring. (Refer to
SAFETY CONSIDERATIONS).
THE BLOWER IS LOCATED
TOTHE RIGHT OFTHE
BURNER SECTION, AND
AIR CONDiTiONED AiR IS
DISCHARGED TO THE LEFT.
t
AIRFLOW
d>
THE BLOWER IS
LOCATED BELOW THE
BURNER SECTION, AND
CONDiTiONED AIR IS
DISCHARGED UPWARD.
\
B
HORIZONTAL LEFT
THE BLOWER IS
LOCATED ABOVE THE
BURNER SECTION, AND
CONDITIONED AIR IS
DISCHARGED DOWNWARD
be located as close to the chimney or vent and attached
to an air distribution system. Refer to Air Ducts section.
be provided ample space for servicing and cleaning. Always comply with minimum fire protection clear-
ances shown on the furnace clearance to combustible label.
The following types of furnace installations may re-
quire OUTDOOR AIR for combustion due to chemical exposures:
Commercial buildings
Buildings with indoor pools
Laundry rooms
Hobby or craft rooms, and
Chemical storage areas
If air is exposed to the following substances, it should not be used for combustion air, and outdoor air may be required for
combustion:
Permanent wave solutions
Chlorinated waxes and cleaners
Chlorine based swimming pool chemicals
Water softening chemicals
De-icing salts or chemicals
Carbon tetrachloride
Halogen type refrigerants
_AIRFLOW
Fig. 4 - Multipoise Orientations
HORIZONTAL RIGH-'_AIR FL_OW
THE BLOWER IS
LOCATED TO THE LEFT
OF THE BURNER SECTION,
AND CONDiTiONED AIR IS
DISCHARGED TO THE RIGHT.
A02097
Cleaning solvents (such as perchloroethylene)
Printing inks, paint removers, varnishes, etc.
Hydrochloric acid
Cements and glues
Antistatic fabric softeners for clothes dryers
Masonry acid washing materials
All fuel-burning equipment must be supplied with air for fuel combustion. Sufficient air must be provided to avoid negative
pressure in the equipment room or space. A positive seal must be made between the furnace cabinet and the return-air duct to
prevent pulling air from the burner area and from draft safeguard opening.
FIRE AND EXPLOSION HAZARD Failure to follow this warning could result in personal
iniury, death, and/or property damage. When the furnace is installed in a residential garage, the
burners and ignition sources must be located at least 18 inches above the floor. The furnace must be located or
protected to avoid damage by vehicles. When the furnace is installed in a public garage, airplane hangar, or other building having a hazardous atmosphere, the furnace must
be installed in accordance with the NFGC. (See Fig. 5.)
PERSONALINJURYAND/ORPROPERTY DAMAGEHAZARD
Failureto follow this caution may result in furnace
component damage. This gas furnace may be used for heating buildings under
construction provided that:
-The furnace is permanently installed with all electrical wiring, piping, venting and ducting installed according to these installation instructions. A return air duct is provided, sealed to the furnace casing, and terminated outside the space containing the furnace. This prevents a negative pressure condition as created by the circulating air blower, causing a flame rollout and/or drawing combustion products into the structure.
-The furnace is controlled by a thermostat. It may not be hot wired to provide heat continuously to the structure
without thermostatic control.
-Clean outside air is provided for combustion. This is to nfininfize the corrosive effects of adhesives, sealers and
other construction materials. It also prevents the entrainment of drywall dust into combustion air, which can cause fouling and plugging of furnace components.
-The temperature of the return air to the furnace is maintained between 55°F (13°C) and 80°F (27°C), with no evening setback or shutdown. The use of the furnace
while the structure is under construction is deemed to be intermittent operation per our installation instructions.
-The air temperature rise is within the rated rise range on the furnace rating plate, and the gas input rate has been set to the nameplate value.
-The filters used to clean the circulating air during the construction process must be either changed or thoroughly cleaned prior to occupancy.
-The furnace, ductwork and filters are cleaned as necessary to remove drywall dust and construction debris from all HVAC system components after construction is completed.
-Verify proper furnace operating conditions including ignition, gas input rate, air temperature rise, and venting according to these installation instructions.
FIRE HAZARD Failure to follow this warning could result in personal
iniury, death and/or property damage. Do not install the furnace on its back or hang furnace with
control compartment facing downward. Safety control operation will be adversely affected. Never connect return-air ducts to the back of the furnace. (See Fig. 60
BACK J
A
A02054
Fig. 6 - Prohibit Installation on Back
LOCATION RELATIVE TO COOLING EQUIPMENT The cooling coil must be installed parallel with, or on the
downstream side of the unit to avoid condensation in the heat exchangers. When installed parallel with the furnace, dampers or
other flow control must prevent chilled air from entering the furnace. If the dampers are manually operated, they must be
equipped with means to prevent operation of either unit unless the damper is in the full-heat or full-cool position.
AIR FOR COMBUSTION AND
VENTILATION
Provisions for adequate combustion, ventilation, and dilution air must be provided in accordance with:
Section 9.3 of the NFPA 54 / ANSI Z223.1-2012, Air for Combustion and Ventilation, and applicable provi-
sions of the local building codes.
18-IN. (457.2 mm)
MINIMUM TO BURNERS
Fig. 5 - Installation in a Garage
FURNACE CORROSION HAZARD Failure to follow this caution may result in furnace damage.
Air for combustion nmst not be contanfinated by halogen compounds, which include fluoride, chloride, bronfide, and iodide. These elements can corrode heat exchangers and
shorten furnace life. Air contanfinants are found in aerosol sprays, detergents, bleaches, cleaning solvents, salts, air
fresheners, and other household products.
A93044
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury or death.
The operation of exhaust fans, kitchen ventilation fans, clothes dryers, attic exhaust fans or fireplaces could create a
NEGATIVE PRESSURE CONDITION at the furnace. Make-up air MUST be provided for the ventilation devices,
in addition to that required by the furnace. Refer to Carbon Monoxide Poisoning Hazard warning in venting section of these instructions to deternfine if an adequate amount of make-up air is available.
The requirements for combustion and ventilation air depend
upon whether or not the furnace is located in a space having a volume of at least 50 cu/ft, per 1,000 Btuh input rating for all gas appliances installed in the space.
Spaces having less than 50 cu/ft, per 1,000 Btuh re- quire the OUTDOOR COMBUSTION AIR METHOD.
Spaces having at least 50 cu/fl, per 1,000 Btuh may use the INDOOR COMBUSTION AIR, STANDARD or
KNOWN AIR INFILTRATION METHOD.
Outdoor Combustion Air Method
1. Provide the space with sufficient air for proper combus- tion, ventilation, and dilution of flue gases using perman- ent horizontal or vertical duct(s) or opening(s) directly
communicating with the outdoors or spaces that freely communicate with the outdoors.
2. Fig. 7 illustrates how to provide TWO OUTDOOR OPENINGS, one inlet and one outlet combustion and
ventilation air opening, to the outdoors.
e. One opening MUST commence within 12 in. (300
ram) of the ceiling and the second opening MUST commence within 12 in. (300 ram) of the floor.
f. Size openings and ducts per Fig. 7 and Table 1.
g. TWO HORIZONTAL DUCTS require 1 sq./in, of free
area per 2,000 Btuh (1,100 mm2/kW) of combined input for all gas appliances in the space per Fig. 7 and
Table 1.
h. TWO OPENINGS OR VERTICAL DUCTS require 1
sq./in, of free area per 4,000 Btuh (550 mm2/kW) for combined input of all gas appliances in the space per Fig. 7 and Table 1.
3. ONE OUTDOOR OPENING requires: a. 1 square inch of free area per 3,000 Btuh (734
mm2/kW) for combined input of all gas appliances in the space per Table 1 and
b. Not less than the sum of the areas of all vent connect-
ors in the space.
The opening shall commence within 12 in. (300 ram) of the ceiling. Appliances in the space shall have clearances of at least 1
in. (25 ram) from the sides and back and 6 in. (150 ram) from the front. The opening shall directly communicate with the outdoors or shall conmmnicate through a vertical or horizontal duct to the
outdoors or spaces (crawl or attic) that freely communicate with the outdoors.
Indoor Combustion Air NFPA & AGA Standard and Known-Air-Infiltration Rate Methods
Indoor air is pernfitted for combustion, ventilation, and dilution, if the Standard or Known-Air-Infiltration Method is used.
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in death and/or personal iniury.
Many homes require air to be supplied from outdoors for furnace combustion, ventilation, and dilution of flue gases. The furnace combustion air supply must be provided in
accordance with this instruction manual.
Table 1--Minimum Free Area Required for Each Combustion Air Opening of Duct to Outdoors
TWO HORIZONTAL DUCTS SINGLE DUCT OR OPENING
FURNACE (1 SQ. IN./2,000 BTUH) (1 SQ. IN./3,000 BTUH) (1 SQ. IN./4,000 BTUH)
INPUT (1,100 SO. MMiKW) (734 SO. MMiKW) (550 SO. MMiKW)
(BTUH) Free Area of Open- Round Duct Free Area of Open- Round Duct Free Area of Open- Round Duct
ing and Duct Dia. ing and Duct Dia. ing and Duct Dia.
Sq. In. (Sq. ram) In. (ram) Sq. In. (Sq. ram) In. (ram) Sq. In. (Sq. ram) In. (ram)
44,000 22 (14194) 6 (152) 14.7 (9484) 5 (127) 11 (7096) 4 (102) 66,000 33 (21290) 7 (178) 22.0 (14193) 6 (152) 16.5 (10645) 5 (127) 88,000 44 (28387) 8 (203) 29.3 (18903) 7 (178) 22 (14193) 6 (152)
110,000 55 (35484) 9 (229) 36.7 (23677) 7 (178) 27.5 (17742) 6 (152) 132,000 66 (42580) 10 (254) 44.0 (28387) 8 (203) 33 (21290) 7 (178)
154,000 77 (49677) 10 (254) 51.3 (33096) 9 (229) 38.5 (24839) 8 (203)
EXAMPLES: Determining Free Area
FURNACE WATER HEATER TOTAL INPUT
110,000 + 30,000 = (140,000 divided by 4,000) = 35.0 Sq. In. for each two Vertical Ducts or Openings
66,000 + 40,000 = (106,000 divided by 3,000) 35.3 Sq. In. for a Single Duct or Opening 88,000 + 30,000 = (118,000 divided by 2,000) 59.0 Sq. In. for each of two Horizontal Ducts
TWO OPENINGS OR VERTICAL
DUCTS
Table 2--Minimum Space Volumes for 100 % Combustion, Ventilation, and Dilution from Indoors
OTHER THAN FAN-ASSISTED TOTAL FAN-ASSISTED TOTAL
(1,000'S BTUH GAS INPUT RATE) (1,000'S BTUH GAS INPUT RATE)
30 40 50 44 66 88 110 132 154
ACH Space Volume Ft3 (M 3)
0.60 (29.7) (39.6) (49.5) (31.1) (46.7) (62.2) (77.8) (93.4) (109.0)
0.60 (35.6) (47.5) (59.4) (37.3) (56.0) (74.7) (93.4) (112.1) (130.8)
0.40 (44.5) (59.4) (74.3) (46.7) (70.0) (93.4) (116.8) (140.1) (163.5)
0.30 (59.4) (79.2) (99.1) (62.2) (93.4) (124.5) (155.7) (186.8) (218.0)
0.20 (89.1) (118.9) (148.6) (93.4) (140.1) (186.8) (233.6) (280.3) (327.0)
0.10 (178.3) (237.8) (297.3) (186.8) (280.3) (373.7) (467.2) (560.6) (654.1)
0.00 NP NP NP NP NP NP NP NP NP
NP = Not Permitted
1,050 1,400 1,750 1,1 O0 1,650 2,200 2,750 3,300 3,850
1,260 1,680 2,1 O0 1,320 1,980 2,640 3,300 3,960 4,620
1,575 2,1 O0 2,625 1,650 2,475 3,300 4,125 4,950 5,775
2,1 O0 2,800 3,500 2,200 3,300 4,400 5,500 6,600 7,700
3,150 4,200 5,250 3,300 4,950 6,600 8,250 9,900 11,550
6,300 8,400 10,500 6,600 9,900 13,200 16,500 19,800 23,1 O0
PER 4000 CIRCULATING AIR
TO
OUTDOORS
(305mm) 12"MAX I _J
lSQiN _11:1
PER2000 IIB
©
BTUi"
DUCTS
OUTiOORS _
PER 2000 _ I:IAI BTUH* T
305mm 12"MAX | .
*Minimum dimensions of 3-in. (76 mm). NOTE: Use any of the following combinations of openings:
Fig. 7 - Air for Combustion, Ventilation, and Dilution for
i,
I
CIRCULATING AIR DUCTS
A&BC&DD&EF&G
TO PER 4000
OUTDOORS BTUH*
Outdoors
1SQ IN. !
BTUH* _DUCTS !1
12_ (305mm)
SO IN. PER
4000
3TUH*
cO n-
O
o
a F-
o
SQ IN. PER
4000
BTUH*
12" (305mm) MAX
12" MAX
(305mm)
1 SQ IN.
A03174
VENT THROUGH ROOF
,, ,, ,, ,,,,
I I I I I
:305mm)
1 SQ IN. PER 1000
BTUH* IN DOOR ORWALL
INTERIOR
HEATED
SPACE
UNCONFINED SPACE
6" MIN (152mm) (FRONT)0
1 SQ IN. PER 1000 BTUH* IN DOOR
-- OR WALL
L 12" MAX(305mm)
I
CIRCULATING AIR DUCTS
* Minimum opening size is 100 sq in. (64516 sq. mm)with minimum dimensions of 3 in. (76 mm)
1-Minimum of 3 in. (76 mm) when type-B1 vent is used.
Fig. 8 - Air for Combustion, Ventilation, and Dilution from
Indoors
A03175
The Standard Method:
1. The space has no less volume than 50 cu/fl, per 1,000 Btuh of the maximum input ratings for all gas appliances
installed in the space and
2. The air infiltration rate is not known to be less than 0.40 air changes per hour (ACH).
The Known Air Infiltration Rate Method shall be used, if the infiltration rate is known to be:
1. Less than 0.40 ACH and
2. Equal to or greater than 0.10 ACH
Infiltration rates greater than 0.60 ACH shall not be used. The minimum required volume of the space varies with the number of
ACH and shall be deternfined per TaMe 2 or Equations I and 2. Deternfine the minimum required volume for each appliance in
the space and add the volumes together to get the total minimum required volume for the space.
Table 2 - Minimum Space Volumes were deternfined by using the following equations from the National Fuel Gas Code ANSI Z223.1-2012/NFPA 54-2012, 9.3.2.2:
1. For other than fan-assisted appliances, such as a draft hood-equipped water heater:
Volume - 21ft3 L_ !°ther
2. For fan-assisted appliances such as this furnace:
Volume _ 15ft 3 _ I fan
If: Iother = combined input of all other than fan-assisted
appliances in Btuh/hr Ifan = combined input of all fan-assisted appliances in Btuh/hr
ACH = air changes per hour (ACH shall not exceed 0.60.) The following requirements apply to the Standard Method and to the
Known Air Infiltration Rate Method.
1. Adjoining rooms can be considered part of a space if:
a. There are no closeaMe doors between rooms.
b. Combining spaces on same floor level. Each opening
c. Combining space on different floor levels. The
2. An attic or crawlspace may be considered a space that freely conmmnicates with the outdoors provided there are
adequate permanent ventilation openings directly to out- doors having free area of at least 1-in.2/4,000 Btuh of total
input rating for all gas appliances in the space.
3. In spaces that use the Indoor Combustion Air Method, in- filtration should be adequate to provide air for combus-
tion, permanent ventilation and dilution of flue gases.
Other ACH H000 Btu/hr
A04002
Fan ACH 000 Btu/hr
A04003
shall have free area of at least I in.2/1,000 Btuh (2,000 mm2/kW) of the total input rating of all gas appliances in the space, but not less than 100 in. 2 (0.06 m2). One
opening shall commence within 12 in. (300 ram) of the ceiling and the second opening shall commence
within 12 in. (300 ram) of the floor. The minimum dimension of air openings shall be at least 3 in. (80
ram). (See Fig. 8.)
volumes of spaces on different floor levels shall be considered as conmmnicating spaces if connected by
one or more permanent openings in doors or floors having free area of at least 2 in.2/1,000 Btuh (4,400 mm2/kW) of total input rating of all gas appliances.
However, in buildings with unusually tight construction, additional air MUST be provided using the methods de-
scribed in the Outdoor Combustion Air Method section.
Unusually tight construction is defined as Construction with:
a. Walls and ceilings exposed to the outdoors have a con-
tinuous, sealed vapor barrier. Openings are gasketed or sealed and
b. Doors and openable windows are weatherstripped and
c. Other openings are caulked or sealed. These include
joints around window and door frames, between sole
plates and floors, between wall-ceiling joints, between wall panels, at penetrations for plumbing, electrical
and gas lines, etc.
Combination of Indoor and Outdoor Air
1. Indoor openings shall comply with the Indoor Combus- tion Air Method below and,
2. Outdoor openings shall be located as required in the Out- door Combustion Air Method mentioned previously and,
3. Outdoor openings shall be sized as follows:
a. Calculate the Ratio of all Indoor Space volume divided
by required volume for Indoor Combustion Air Method below.
b. Outdoor opening size reduction Factor is 1 nfinus the
Ratio in a. above.
c. Minimum size of Outdoor openings shall be the size
required in Outdoor Combustion Air Method above nmltiplied by reduction Factor in b. above. The nfin-
imum dimension of air openings shall be not less than 3 in. (80 mm).
INSTALLATION
UPFLOW INSTALLATION Bottom Return Air Inlet These furnaces are shipped with bottom closure panel installed in
bottom return-air opening. Remove and discard this panel when bottom return air is used. To remove bottom closure panel,
perform the following:
1. Tilt or raise furnace and remove 2 screws holding bottom filler panel. (See Fig. 90
Bottom Closure Panel
Bottom Filler Panel
A10273
Fig. 9 - Removing Bottom Closure Panel
2. Rotate bottom filler panel downward to release holding
tabs.
3. Remove bottom closure panel.
4. Reinstall bottom filler panel and screws.
Side Return Air Inlet These furnaces are shipped with bottom closure panel installed in
bottom return-air opening. This panel MUST be in place when only side return air is used.
10
NOTE: Side return-air openings can be used in UPFLOW and most HORIZONTAL configurations. Do not use side return-air openings in DOWNFLOW configuration.
In upflow position with side return inlet(s), leveling legs may be used. (See Fig. 10.) Install field-supplied, 5/16 x 1-1/2 in. (8 x
38 ram) (max) corrosion-resistant machine bolts, washers and nuts.
NOTE: Bottom closure must be used when leveling legs are used. It may be necessary to remove and reinstall bottom closure panel to install leveling legs. To remove bottom closure panel, see
Item 1. in Bottom Return Air Inlet section.
(8mm)
I 3/4'
(44mm)
1 3/4"
(44mm)
4. If downflow subbase, KGASB is used, install as shown in Fig. 12. If Coil Assembly Part No. CNPV, CNRV, CAR,
or CAP or Coil Box Part No. KCAKC is used, install as shown in Fig. 13.
(8mm)
5/16"
(8mm)
(44mm) 1 3/4"
(44mm) I 3/4'_"_
A89014
Fig. 10 - Leveling Legs
Leveling Legs (If Desired) To install leveling legs:
1. Position furnace on its back. Locate and drill a hole in each bottom corner of furnace. (See Fig. 10.)
2. For each leg, install nut on bolt and then install bolt and nut in hole. (Install flat washer if desired.)
3. Install another nut on other side of furnace base. (Install flat washer if desired.)
4. Adjust outside nut to provide desired height, and tighten inside nut to secure arrangement.
5. Reinstall bottom closure panel if removed.
DOWNFLOW INSTALLATION NOTE: For downflow applications, this furnace is approved for
use on combustible flooring when any one of the following 3 accessories are used:
Special Base, KGASB
Cased Coil Assembly Part No. CNPV, CNRV, CAR, or CAP
Coil Box Part No. KCAKC
1. Determine application being installed from Table 3.
2. Construct hole in floor per Table 3 and Fig. 11.
3. Construct plenum to dimensions specified in Table 4 and Fig. 11.
A96283
Fig. 11 - Floor and Plenum Opening Dimensions
NOTE: It is recommended that the perforated supply-air duct
flanges be completely folded over or removed from furnace when installing the furnace on a factory-supplied cased coil or coil box. To remove the supply-air duct flange, use wide duct pliers or hand seamers to bend flange back and forth until it breaks off. Be
careful of sharp edges. (See Fig. 140
FURNACE
(OR COIL CASING
WHEN USED)
COMBUSTIBLE
FLOORING \
SUBBASE
SHEET METAL
PLENUM
FLOOR
OPENING
A96285
Fig. 12 - Furnace, Plenum, and Subbase Installed on a
Combustible Floor
11
FURNACE
APPROVED
COIL ASSEMBLY
OR
COIL BOX
COMBUSTIBLE
FLOORING
\\\\_
SHEET METAL _
PLENUM
I
Fig. 13 - Furnace, Plenum, and Coil Assembly or Coil Box
Installed on a Combustible Floor
Bottom Return Air Inlet These furnaces are shipped with bottom closure panel installed in
bottom return-air opening. Remove and discard this panel when bottom return air is used. To remove bottom closure panel,
perform the following:
1. Tilt or raise furnace and remove 2 screws holding bottom filler panel. (See Fig. 9.)
2. Rotate bottom filler panel downward to release holding
tabs.
3. Remove bottom closure panel.
4. Reinstall bottom filler panel and screws.
HORIZONTAL INSTALLATION
FLOOR
OPENING 12
A08556
If the screws are attached to ONLY the furnace sides and not the bottom, the straps must be vertical against the furnace sides and
not pull away from the furnace sides, so that the strap attachment screws are not in tension (are loaded in shear) for reliable support.
Platform Furnace Support Construct working platform at location where all required furnace
clearances are met, (See Fig, 2 and 170 For furnaces with 1-in, (25 ram) clearance requirement on side, set furnace on non-
combustible blocks, bricks or angle iron, For crawl space installations, if the furnace is not suspended from the floor joists,
the ground underneath furnace must be level and the furnace set on blocks or bricks,
Roll- Out Protection Provide a minimum 17-3/4 in, x 22 in, (451 x 559 ram) piece of
sheet metal for flame roll-out protection in front of burner area for furnaces closer than 12 inches (305 ram) above the
combustible deck or suspended furnaces closer than 12 inches (305 ram) to joists, The sheet metal MUST extend underneath the
furnace casing by 1 in, (25 ram) with the door removed, The bottom closure panel on furnaces of widths 17-1/2 in, (445
ram) and larger may be used for flame roll-out protection when bottom of furnace is used for return air connection, See Fig, 17
for proper orientation of roll-out shield, Bottom Return Air Inlet
These furnaces are shipped with bottom closure panel installed in bottom return-air opening, Remove and discard this panel when
bottom return air is used, To remove bottom closure panel, perform the following:
1, Tilt or raise furnace and remove 2 screws holding bottom
filler panel, (See Fig, 90
2, Rotate bottom filler panel downward to release holding
tabs.
3. Remove bottom closure panel.
4. Reinstall bottom filler panel and screws.
Side Return Air Inlet These furnaces are shipped with bottom closure panel installed in
bottom return-air opening. This panel MUST be in place when side return air inlet(s) is used without a bottom return air inlet.
Not all horizontal furnaces are approved for side return air connections. (See Fig. 20.) FILTER ARRANGEMENT
FIRE, EXPLOSION, AND CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury, death, or property damage.
Do not install the furnace on its back or hang furnace with control compartment facing downward. Safety control operation will be adversely affected. Never connect
return-air ducts to the back of the furnace.
The furnace can be installed horizontally in an attic or crawl
space on either the left-hand (LH) or right-hand (RH) side. The furnace can be hung from floor joists, rafters or trusses or installed on a non-combustible platform, blocks, bricks or pad.
Suspended Furnace Support The furnace may be supported under each end with threaded rod,
angle iron or metal plumber's strap as shown. (See Fig. 15 and
16.) Secure angle iron to bottom of furnace as shown. Heavy-gauge sheet metal straps (plumber's straps) may be used
to suspend the furnace from each bottom corner. To prevent screws from pulling out, use 2 #8 x 3/4-in. (19 ram) screws into
the side and 2 #8 x 3/4-in. (19 ram) screws in the bottom of the furnace casing for each strap. (See Fig. 15 and 16.)
CARBON MONOXIDE AND POISONING HAZARD
Failure to follow this warning could result in personal iniury, death and/or property damage.
Never operate a furnace without a filter or with filter access door removed.
There are no provisions for an internal filter rack in these furnaces.
Refer to the instructions supplied with accessory Media Cabinet for assembly and installation options.
This furnace requires a field-supplied external filter rack or a suitable field-supplied substitute, such as the media cabinet. See
the Product Data Sheet for accessory list. Refer to the instructions supplied with external filter rack for
assembly and installation options.
12
Table 3--Opening Dimensions - In. (mm)
FURNACE
CASING
APPLICATION
WIDTH
Upflow Applications on Combustible or Noncombustible Floor- 12-11/16 21-5/8 13-5/16 22-1/4
Downflow Applications on Noncombustible Flooring (KGASB 12-9/16 19 13-3/16 19-5/8
14-3/16 Downflow applications on combustible flooring (KGASB sub- 11 - 18/16 19 18- 7/16 20- 5/8
(360) base required) (284) (483) (341) (600)
Downflow Applications on Combustible Flooring with CNPV,
CNRV, CAR, or CAP Coil Assembly or KCAKC coil box
Upflow Applications on Combustible or Noncombustible Floor- 16 21 -5/8 16-5/8 22-1/4
Downflow Applications on Noncombustible Flooring (KGASB 15-7/8 19 16-1/2 19-5/8
17-1/2 Downflow applications on combustible flooring (KGAS B su b- 15-1/8 19 16-3/4 20-5/8
(445) base required) (384) (483) (425) (600)
Downflow Applications on Combustible Flooring with CNPV,
CNRV, CAR, or CAP Coil Assembly or KCAKC coil box
Upflow Applications on Combustible or Noncombustible Floor- 19-1/2 21-5/8 20-1/8 22-1/4
Downflow Applications on Noncombustible Flooring (KGASB 19-3/8 19 20 19-5/8
21 Downflow applications on combustible flooring (KGASB sub- 18-5/8 19 20-1/4 20-5/8
(533) base required) (473) (483) (514) (600)
Downflow Applications on Combustible Flooring with CNPV,
CNRV, CAR, or CAP Coil Assembly or KCAKC coil box
Upflow Applications on Combustible or Noncombustible Floor- 23 21 - 1/8 28- 5/8 22-1/4
Downflow Applications on Noncombustible Flooring (KGASB 22-7/8 19 28-1/2 19-5/8
24-1/2 Downflow applications on Combustible flooring (KGAS B su b- 22-1/8 19 28- 3/4 20-5/8
(622) base required) (562) (483) (603) (600)
Downflow Applications on Combustible Flooring with CNPV,
CNRV, CAR, or CAP Coil Assembly or KCAKC coil box
ing (KGASB subbase not required) (322) (549) (338) (565)
subbase not required) (819) (483) (335) (498)
(KGASB subbase not required) (819) (483) (338) (508)
ing (KGASB subbase not required) (406) (549) (422) (565)
subbase not required) (403) (483) (419) (498)
(KGASB subbase not required) (394) (483) (419) (508)
ing (KGASB subbase not required) (495) (549) (511) (565)
subbase not required) (492) (483) (508) (498)
(KGASB subbase not required) (483) (483) (508) (508)
ing (KGASB subbase not required) (584) (537) (600) (565)
subbase not required) (581) (483) (597) (498)
(KGASB subbase not required) (572) (483) (597) (508)
PLENUM OPENING FLOOR OPENING
A B C D
12-5/16 19 13-5/16 20
15-1/2 19 16-1/2 20
19 19 20 20
22-1/2 19 28-1/2 20
AIR DUCTS General Requirements
The duct system should be designed and sized according to accepted national standards such as those published by: Air
Conditioning Contractors Association (ACCA), Sheet Metal and Air Conditioning Contractors National Association (SMACNA)
or American Society of Heating, Refrigerating and Air Conditioning Engineers (ASHRAE) or consult The Air Systems
Design Guidelines reference tables available from your local distributor. The duct system should be sized to handle the
required system design CFM at the design external static pressure. The furnace airflow rates are provided in Table 4 - AIR DELIVERY-CFM (With Filter).
When a furnace is installed so that the supply ducts carry air circulated by the furnace to areas outside the space containing the
furnace, the return air shall also be handled by duct(s) sealed to the furnace casing and terminating outside the space containing
the furnace. Secure ductwork with proper fasteners for type of ductwork used.
Seal supply- and return-duct connections to furnace with code approved tape or duct sealer. NOTE: Flexible connections should be used between ductwork
and furnace to prevent transmission of vibration. Ductwork passing through unconditioned space should be insulated and sealed to enhance system performance. When air conditioning is used, a vapor barrier is recommended.
Maintain a 1-in. (25 ram) clearance from combustible materials to supply air ductwork for a distance of 36 in. (914 ram) horizontally from the furnace. See NFPA 90B or local code for
further requirements.
Ductwork Acoustical Treatment NOTE: Metal duct systems that do not have a 90 degree elbow
and 10 ft. (3 M) of main duct to the first branch take-off may require internal acoustical lining. As an alternative, fibrous ductwork may be used if constructed and installed in accordance
with the latest edition of SMACNA construction standard on fibrous glass ducts. Both acoustical lining and fibrous ductwork shall comply with NFPA 90B as tested by UL Standard 181 for
Class 1 Rigid air ducts. Supply Air Connections For a furnace not equipped with a cooling coil, the outlet duct
shall be provided with a removable access panel. This opening shall be accessible when the furnace is installed and shall be of
such a size that the heat exchanger can be viewed for possible openings using light assistance or a probe can be inserted for
sampling the air stream. The cover attachment shall prevent leaks.
13
Table4--Air Delivery - CFM (with Filter)*
FURNACE RETURN-AIR SPEED EXTERNAL STATIC PRESSURE (In. W.C.)
SiZE INLET 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
045-08/ Bottom or High 1035 995 945 895 835 770 675 565 390 195
024048 Side(s) Med - High 865 830 790 745 690 625 545 440 250 195
045-12/ Bottom or High 1440 1375 1305 1240 1160 1070 975 870 730 560
036045 Side(s) Med - High 1360 1300 1240 1175 1115 1040 950 850 725 575
070-08/ Bottom or High 1030 1005 965 925 870 810 740 645 465 280
024070 Side(s) Med- High 835 815 790 755 710 660 590 480 325 205
070-12/ Bottom or High 1425 1375 1320 1265 1200 1125 1035 940 830 655
036070 Side(s) Med- High 1320 1280 1240 1205 1140 1075 995 905 790 620
070-16/ Bottom or High 1755 1700 1635 1570 1505 1435 1350 1260 1160 1055
048070 Side(s) Med- High 1550 1520 1475 1430 1375 1310 1240 1155 1070 970
090-14/ Bottom or High 1605 1570 1535 1465 1385 1285 1175 1055 895 645
042090 Side(s) Med - High 1470 1445 1410 1380 1300 1220 1115 990 830 600
090-16/ Bottom or High 1940 1880 1805 1720 1635 1540 1425 1290 1090 830
048090 Side(s) Med - High 1740 1700 1650 1590 1525 1440 1335 1195 1010 820
Bottom Only Med - High 2170 2110 2040 1970 1895 1785 1675 1565 1420 1260
090-20/ Both Sides or 1 High 2530 2450 2365 2270 2165 2065 1940 1805 1670 1505
060090 Side & Bottom Med - High 2230 2170 2110 2050 1985 1890 1780 1660 1525 1360
1Side Only Med - High 2105 2145 2070 2010 1940 1845 1735 1620 1475 1325
110-12/ Bottom or High 1600 1550 1490 1425 1355 1260 1135 990 785 530
036110 Side(s) Med- High 1475 1435 1395 1335 1285 1185 1070 890 725 450
110-16/ Bottom or High 1980 1915 1835 1750 1655 1495 1365 1185 965 700
048110 Side(s) Med-High 1745 1710 1650 1560 1450 1340 1205 1090 865 605
Bottom Only Med- High 2135 2100 2060 2000 1930 1860 1765 1670 1555 1425
110-22/
066110 or 1 Side & Bot- Med-High 2140 2100 2050 1990 1935 1865 1760 1670 1545 1410
A filter is required for each return-air inlet. Airflow performance included 3/4-in. (19 mm) washable filter media such as contained in factory-authorized ac-
cessory filter rack. To determine airflow performance without this filter, assume an additional 0.1 In. W.C. available external static pressure.
-- Indicates unstable operating conditions.
Bottom Sides High .... 2355 2285 2190 2090 1965 1850 1705 1535
tom Med - Low 1855 1840 1815 1775 1725 1675 1600 1510 1405 1290
1Side Only Med - High 2030 2025 2000 1950 1905 1850 1750 1660 1555 1425
Med - Low 760 720 680 635 580 520 445 345 220 195
Med - Low 1250 1210 1160 11 O0 1040 965 885 790 670 520
Med - Low 725 700 675 635 595 545 460 350 250 - -
Med - Low 1200 1175 1145 1105 1050 990 920 840 725 555
Med - Low 1355 1340 1310 1280 1240 1190 1125 1060 975 890
Med- Low 1310 1295 1265 1230 1195 1120 1025 915 710 565
Med - Low 1505 1505 1480 1440 1375 1300 1190 1045 890 740
High 2405 2310 2220 2130 2025 1920 1790 1660 1530 1350
Med - Low 1920 1875 1835 1780 1715 1630 1535 1420 1275 1135
Med - Low 1895 1890 1845 1815 1755 1685 1600 1480 1350 1180
High 2475 2395 2300 2200 2090 1985 1865 1730 1585 1425
Med - Low 1850 1860 1810 1770 1715 1650 1555 1445 1310 1150
Med - Low 1315 1295 1265 1220 1155 1080 985 810 675 440
Med- Low 1530 1515 1470 1400 1310 1215 1095 990 830 670
High 2485 2415 2340 2255 2160 2080 1950 1840 1720 1565
Med - Low 1855 1840 1815 1775 1725 1675 1600 1510 1405 1290
High 2495 2440 2370 2290 2205 2120 2015 1910 1775 1625
Med - Low - - 1735 1725 1695 1650 1595 1535 1455 1335 1230
14
Table 5---Air Delivery - CFM (with Filter)* (Continued)
FURNACE RETURN-AIR SPEED EXTERNAL STATIC PRESSURE (In. W.C.)
SIZE iNLET 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
135-16/ Bottom or High 2065 2000 1930 1835 1710 1590 1420 1235 1025 835
048135 Side(s) Med - High 1790 1755 1705 1640 1550 1465 1295 1145 945 775
Bottom Only Med - High 2130 2080 2025 1960 1880 1795 1690 1550 1405 1255
135-22/
066135 or 1 Side & Bot- Med-High 2120 2075 1995 1970 1905 1835 1735 1645 1515 1325
155-2o/
060155
A filter is required for each return-air inlet. Airflow performance included 3/4-in. (19 mm) washable filter media such as contained in factory-authorized ac-
cessory filter rack. To determine airflow performance without this filter, assume an additional 0.1 In. W.C. available external static pressure.
-- Indicates unstable operating conditions.
Bottom, Sides High .... 2355 2280 2160 2065 1930 1805 1655 1465
tom Med - Low 1860 1830 1800 1755 1725 1630 1530 1415 1280 1140
1 Side Only Med-High 2070 2015 1970 1935 1855 1765 1655 1550 1445 1265
Bottom Only
BothSidesOr I
Side& Bottom
ISideOnly
Med - Low 1480 1480 1480 1450 1380 1295 1160 1005 855 670
High 2445 2365 2280 2190 2085 1980 1850 1705 1520 1355
Med - Low 1860 1830 1800 1755 1705 1630 1530 1415 1280 1140
High .... 2215 2130 2030 1920 1795 1675 1540 1385
Med - Low 1860 1830 1800 1755 1725 1630 1530 1415 1280 1140
High 2465 2430 2375 2305 2215 2110 2000 1865 1715 1530
Med-High
Med - Low
High
Med-High
Med - Low
High
Med-High
Med - Low
2115 2095 2055 2005 1940 1845 1820 1675 1525 1390 1800 1790 1770 1735 1695 1640 1570 1465 1345 1225
.... 2375 2285 2185 2105 1995 1870 1720 1555
2155 2125 2075 2015 1935 1830 1780 1635 1485 1365 1800 1790 1770 1735 1695 1640 1570 1465 1345 1225
.... 2260 2180 2070 1975 1865 1740 1595 1440
2140 2085 2020 1950 1850 1745 1695 1545 1415 1290 1800 1790 1770 1735 1695 1640 1570 1465 1345 1225
/
U PFLOW DOWN FLOW HO REZO NTAL
I ......
YES
120°_ MIN
YES
\
YES 120°_ YES 120°_ YES
NO NO NO
/\ /\
MIN MIN
Fig. 14 - Duct Flanges
YES
A02020
15
ASSEMBLY
L.
8" (203mm) MtN
FOR DOOR REMOVAL
(2) HEX NUTS, (2) WASHERS & (2) LOCK WASHERS REQ. PER ROD
_/4"(6mm) THREADED ROD 4 REQ.
SECURE ANGLE
IRON TO BOTTOM
OF FURNACE WiTH 3 #8 x3/4'' (19mm) SCREWS
TYPICAL FOR 2 SUPPORTS
1" (25ram) SQUARE, 1-1/4"x1-1/4"x1/8" (32x32x3mm) ANGLE IRON OR UNI-STRUT MAY BE USED
OUTER DGOR ASSEMB_
A10130
Fig. 15 - Horizontal Unit Suspension
22 GAUGE GALVANIZED STRAPS TYPICAL
FOR 4 STRAPS
METHOD 2
&
BACK OF FURNACE
METHOD 1 FOLD ALL STRAPS UNDER FURNACE AND SECURE WTH
(4) #8 x 3/4 (t9 ram) SHEET METAL SCREWS (2 SCREWS IN SIDE AND 2 SCREWS
IN BOTTOM).
USE (4) #8 x 3/4 (19 ram) SHEET METAL SCREWS FOR EACH
STRAR THE STRAPS SHOULD BE VERTICAL AGAINST THE FURNACE SIDES AND NOT PULL AWAY FROM THE FURNACE SIDES.
Fig. 16 - Horizontal Suspension with Straps
16
A10131
Loading...
+ 36 hidden pages