Carrier 58SS, 58DH User Manual

58SS/DH

HEATING «COOLING

Induced-Combustion Gas-Fired Furnaces

Application Data

Installation Guidelines Procedures

INTRODUCTION

The desire to conserve energy has created
greater use of insulation, improved vapor barriers, weather stripping, etc. Homes are now tighter, resulting in less natural air infiltration and inefficient furnace oper ation. The condition is further affected by the growing use of kitchen and bathroom exhausts and even fireplaces.
Field studies indicate that combustion air starvation, particularly in closet installations, points to a need for positive furnace air supply, plus new guidelines for to day’s furnace applications.

A WARNING

These instructions cover minimum combustion air requirements and venting practices. They also reflect current conditions found in the field, and conform to existing national standards, and safety codes. In some instances, these instructions exceed certain local codes and ordinances, especially those that may not have kept pace with changing construction practices. Carrier requires these standard pro
cedures as a minimum for safe installation.
CONTENTS
INSPECTION
...................................................
1
FURNACE LOCATION — COMBUSTION/
VENTILATION AIR ...................................... 1
GAS PIPING................................................................... 3
VENTING.......................................................... 4
ELECTRICAL................................................................ 5
START-UP, ADJUSTMENT AND
SAFETY CHECK...................................................... 5
FURNACE LOCATION WITH RESPECT
TO COOLING EQUIPMENT................................. 7
SPECIAL LOCATIONS.............................................. 7
APPENDIX — VENTING REPLACEMENT
INSTALLATIONS..................................................... 7
INSPECTION
Check available power supply to be sure it meets speci
fications on wiring diagram and all motors in furnace.
Check available gas supply to see that it conforms to
gas specifications on AGA rating plate.
Page

A CAUTION

Do not block openings in front of furnace or on furnace top along side vent pipe. These openings pro vide air for combustion and ventilation. Never store anything on or in contact with furnace, such as: aerosol cans, rags, brooms and mops, cleaning tools and aids, powders, bleaches, waxes, plastic items, gasoline, kerosene, lighter fluids, cleaning fluids, thinners, painting compounds or paper products.
Installation Procedures — These recommendations
apply to the installation and operation of gas furnaces and piping systems for natural or LP (propane) gases. Use these procedures in conjunction with your specific furnace installation instructions.
Refer also to your gas supplier regulations and local building, heating, plumbing and other codes for your installation area.
Portions of the following have been adopted in part from the National Fuel Gas Code (NFPA No. 54-1984 or ANSI Z223.1-1984) copyrighted by the National Fire
Protection Association and American Gas Association.
For further details, consult this publication or current edition available from NFPA, Batterymarch Park, Quincy, MA 02269, or American Gas Association, 1515
Wilson Boulevard, Arlington, VA 22209.
FURNACE LOCATION —
COMBUSTION/VENTILATION AIR
Locate furnace close to chimney and as near to the center of the air distribution system as possible. Install furnace as level as possible. Provide ample space for servicing and cleaning. Always comply with minimum
fire protection clearances shown on unit rating plate. Do
not install directly on carpeting, tile or any combustible material other than wood flooring. Accessory eom-
bustible floor base is available from your dealer when required.
The relief-air supply for the draft safeguard duct (draft
hood) must be in the same atmospheric pressure zone as
the combustion-air inlet supply to the furnace.
When a furnace is installed so that the supply ducts
carry air to areas outside the space containing the
furnace, the return air must also be handled by duct(s)
sealed to the furnace casing and terminating outside the furnace location area.
All fuel-burning furnaces must be supplied with air
that enters the combustion process and then is vented to the outdoors. Sufficient air must enter the space contain ing the furnace to replace the amount drawn up the vent stack. Replacement air must be provided by means of ducts from the outside to the furnace area or heated
spaee. Under all eonditions, enough air must be provided
to ensure there will be no negative pressure condition
Bookh PC101 Catalog No 515-808 Printed in U S A Form 58D.S-2XA Pg 1 6-85 Replaces: 58D,S-1XA
Tab l6a
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
within the space containingHlte fut'^ace. A positive seal
must be made between the furnace base and platform
or return-air duct connections. Even a slight leak can create a negative pressure condition in a confined closet or basement and affect combustion. If necessary, seal the furnace base-to-floor opening with fiberglass or other approved material. Furnaces with side-connected returns should use the factory-supplied bottom closure, properly sealed.
For complete combustion and ventilation, the furnace requires approximately 20 cu ft of air for every 1000 Btuh of gas consumed. Thus, for each 1000 Btuh of gas con sumed, a total of 20 cu ft of air must be supplied. For a
100,000-Btuh gas furnace, this equals 2000 cu ft of air per hour (100 X 20) or 33 cu ft of air per minute (2000 60). In the past, the infiltration of outside air assumed in heat loss calculations (one air change per hour) was sufficient. However, current construction methods using more insu lation and vapor barriers, tighter fitting and gasketed doors and windows, or weatherstripping, and the presence of fuel-burning fireplaces and household exhaust fans require positive introduction of outside air.
Use of exhaust fans, kitchen ventilation systems, clothes dryers and fireplaces may create conditions that require special attention to avoid unsatisfactory furnace operation. Exhaust fans and range hoods can handle from 60 to 300 cfm (or more). Gas and electric clothes dryers remove even more air. Use of multiple appliances requires special mandatory provisions for positive intro duction of outside air. This makeup air requirement is several times that required by the furnace and must be replaced, in addition to the air required by the furnace.

A CAUTION

In addition, if ths building is of unusually tight con struction, there shall be one permanent opening commu nicating directly with outdoors. This opening shall have a minimum free area of one sq in. per 5000 Btuh of total input rating of all equipment in the enclosure. Ducts shall be used to convey makeup air, and shall be of the same cross-sectional area as the free area of the openings to which they connect. This duct should be connected to the cold air return of the heating system. The minimum dimension of the rectangular air ducts should not be less than 3 inches. See Fig. 1.
If furnace is installed on a raised platform to provide a return-air plenum, and return air is taken directly from the hallway or space adjacent to the furnace, all air for combustion must come from the outside, as prescribed in paragraph below.
ALL AIR FROM OUTDOORS — The confined space shall be provided with 2 permanent openings, one com mencing within 12 in. of the top and one commencing within 12 in. of the bottom of the enclosure. These open ings shall communicate directly, or by ducts, with out doors. See Fig. 2.
a. When communicating with the outdoors through
horizontal ducts, each opening shall have a minimum free area of one sq in. per 2000 Btuh of the total rated input of all equipment in the enclosure. If vertical ducts or openings with louvers and grilles are used, each opening or duct shall have a minimum free area of one sq in. per 4000 Btuh of the total rated input of all equipment in the enclosure.
b. When ducts are used, they shall be of the same cross-
sectional area as the free area of the openings to which they connect. The minimum dimension of rectangular air ducts shall not be less than 3 inches.
Combustion air must come from a source not con taminated by halogens, which include fluorides, chlorides, bromides and iodides. These elements are found in aerosols, detergents, bleaches, cleaning solvents, salts, air fresheners and other household
products. Vapors from these products are highly corrosive to gas-fired furnaces, even in extremely low concentrations — as low as 1/2 part per million.
When such contaminants are present, outside air
must be ducted separately to the furnace room.
Requirements for combustion and ventilation air
depend upon whether furnace is located in a confined or
unconfined space. An unconfined space is defined as a
space where volume is not less than 50 cu ft per 1000 Btuh of the total input rating of all appliances installed in that space. Rooms directly open (no doors) to the space in which the appliances are installed are considered a part of the unconfined space. A confined space is defined as a space with volume less than 50 cu ft per 1000 Btuh of the total input ratings of all appliances in that space.
Furnaces in Confined Spaces (Typical Furnace
Closet)
ALL AIR FROM INSIDE BUILDINGS — The con fined space shall be provided with 2 permanent openings, one beginning within 12 in. of the top and one beginning within 12 in. of the bottom of the enclosure. Each opening shall have a minimum free area of one sq in. per 1000 Btuh of the total input rating of all equipment in the enclo sure, but not less than 100 sq inches. The openings must freely communicate with other interior areas served by the furnace, of sufficient volume so that the combined volume of all spaces meets the criteria for an unconfined space. This can be accomplished through either per manent openings or louvered doors.
Furnaces in Unconfined Spaces (Basements, Large Equipment Rooms, etc.) — If the uncon
fined space is within a building of unusually tight con struction, air for combustion, ventilation and dilution of flue gases shall be obtained from outdoors or from spaces freely communicating with the outdoors. A permanent opening, or openings, having a total free area of not less than one sq in. per 5000 Btuh of total input rating for all equipment shall be provided. A duct may be used to con vey makeup air from the outdoors and shall be of the same cross-sectional area as the free area of the openings to which it connects. The duct may be connected to the cold air return of the heating system only if it connects
directly to outside air. The minimum dimension of
rectangular air ducts shall be not less than 3 inches.

A CAUTION

Return air must not be taken from the room, unless
an equal or greater amount of air is supplied to the room. All duct connections to the furnace must be airtight to avoid causing a negative pressure condi tion within the room.
Louvers and Grilles — In calculating the free area,
consideration shall be given to the blocking effect of
louvers, grilles, or screens protecting openings. Screens
used must not be smaller than 1 / 4-in. mesh. If the free
area through a design of louver or grille is known, it should be used in calculating the size opening required to provide the free area specified. If the design and free area is not known, assume that wood louvers will have 20 to 25% free area and metal louvers and grilles will have 60 to 75% free area. Louvers and grilles that provide combustion and dilution air must be constructed so they cannot be closed.
©
RETURN OR SUPPLY AIR
pl~1
I I I I I I I I I
VENT TO ROOF
12 IN. MAX
I so IN. PER
2000 BTUH
DUCTS TO OUTSIDE
I SO IN. PER 2000 BTUH
12 IN. MAX
±
T
I so IN. PER
4000 BTUH
DUCTS TO ROOF
I I
I I
T
i
RETURN
OR
SUPPLY
AIR
VENT
TO ROOF
1 3
-12 IN.MAX
* MINIMUM OPENING SIZE IS 100 SO IN. (REUIRN
+ MINIMUMOF 3 IN. WHEN TYPE-BI VENT IS USED. AIR ONLY)
Fig. 1 — Upflow or Counterflow, Using Air
from Inside Building
GAS PIPING
Gas piping must be installed in accordance with
national and local codes.
The gas supply line should be a separate line directly from the meter to the furnace, if possible. Referto Table 1 for recommended gas pipe sizing.
Table 1 — Maximum Capacity of Gas Pipe*
NOMINAL
IRON PIPE
SIZE
(in.)
'k
% 0.824
1 1.049
r/4
1V2
'Cubic ft of gas per hour for gas pressure of 0.5 psig or less, and a
pressure drop of 0.5 in wg (based on a 0 60 specific gravity) Ref. Table C-4 NFPA 54-1984.
INTERNAL DIAMETER
(in.)
0 622
1 380 1400 950
1 610 2100 1460 1180
LENGTH OF PIPE (ft)
10 20 30
175 120 97 360 250 200 680 465 375
40
50
82 73
170
151 285
320
770 660 580
990 900
RETURN OR
SUPPLY AIR
USE ANY OF THE FOLLOWING COMBINATIONS OF OPENINGS; AaB CSD D8E
J
TO OUTSIDE
5
DUCT
I so IN. PER
4000 BTUH
Fig. 2 — Upflow or Counterflow, Using Air
from Outside Building
Install a sediment trap in the riser leading to the furnace. This trap collects dirt or condensate. It can be installed by connecting a Tee to the riser leading to the furnace, so that the straight through section of the Tee is vertical. Then connect a capped nipple into the lower end of the Tee. The capped nipple should extend below the level of the gas controls. See Fig. 3. Where a gum filter
is required by local codes, install it in accordance with
Avoid low spots in long runs of pipe. It is best to slope all pipe I/4inch in 15 ft to prevent traps. All horizontal runs should slope away from the meter, to risers. Risers should be used to connect to the furnace and to the meter.
Joint compounds (pipe dope) should be applied sparingly and only to the male threads of the joints. Consult local supplier for type of compound to be used. This pipe dope must be resistant to the action of LP (propane) gas.
An accessible manual shutoff valve shall be installed upstream of the furnace gas controls and within 6 ft of the furnace. A 1/8-in. NPT plugged tapping, accessible for test gage connection, must be installed immediately up stream of the gas supply connection to the furnace, and downstream of the manual shutoff valve.
Place a ground joint union between the gas control
manifold and the manual gas shutoff valve. See Fig. 4.

A WARNING

Use the proper length of pipes to avoid stress on the
gas control manifold.
Protect all segments of the piping system against physical and thermal damage. Support all piping with appropriate straps, hangers, etc. Use a minimum of one hanger every 6 feet. For pipe sizes larger than l/2in., follow recommendations of national codes.

A CAUTION

If a flexible connector is required or allowed by the authority having jurisdiction, black iron pipe shall be installed at the gas valve and extend a minimum of 2 in. outside the furnace casing.
point temperature. Do not attempt to confirm this data by field measurement, as specific laboratory equipment and test conditions are required.
Consult local codes. For additional information refer to the National Fuel Gas Code (NFPA No. 54-1984 or ANSI Z223.1-1984). Unless the local codes direct other wise, unit may be vented to an NFPA-or ANSI-approved chimney, or to a listed type-Bl gas vent. Connect the vent collar to the chimney or gas vent to be used. Follow these recommendations:
1. Select flue connection material that is satisfactory for installation and that meets requirements of local codes.
2. Flue connection pipe must be at least as large as outlet collar on furnace. No reduction in this size is
permissible in pipe run.
NOTE: The clearance requirements which must be maintained between the furnace vent pipe and com bustible materials are as follows: 6 in. for single-wall vent and one in. for type-Bl (double-wall) vent.
When B1 vent material is used, make the single wall­to-B 1 transition with a listed transition fitting directly on the flue collar or flue extension pipe.
3. Run pipe as directly as possible with minimum number of turns and minimum of 12 in. straight pipe before the first bend (upflow and downflow).
4. Maintain minimum of 1/4in. per linear ft upward slope on all horizontal runs.
5. Rigidly support flue pipe with hangers and straps to ensure that there will be no movement after installation.
6. Insert smallest flue connection pipe at highest level consistent with available headroom or clearance to combustible materials, when 2 or more vent eon-
nectors enter a common gas vent or chimney flue.
7. Extend flue connection pipe through chimney wall flush with inner face of chimney liner and above extreme bottom to avoid restriction.

A WARNING

Piping should be pressure tested in accordance with local and national plumbing and gas codes before furnace has been attached. If pressure exceeds 0.5 psig(14in. wg), gas supply pipe must be disconnected from furnaee before pressure test. If test pressure is equal to or less than 0.5 psig (14 in. wg), close manual shutoff valve located on gas valve before test. Ground joint union should be loosened
before pressure testing.
After all connections have been made, purge the lines and check for leakage.

A WARNING

Never purge a line into a combustion chamber. Never use matches, candles, flame, or other sources of ignition for the purpose of checking leakage. Use a soap-and-water solution to cheek for leakage.
VENTING
■ Venting Category I — This furnace complies with
Venting Category 1, as noted on the furnace rating plate. This refers to the type of venting system as specified in the ANSI 21.47 requirements, against which this appliance is tested and design certified by the American Gas Associa tion Laboratories. Specifically, Venting Category 1 is a nonpositive venting system, meaning the static pressure in the vent is less than atmospheric pressure, and the stack gas temperature is at least 140 degrees F above the dew
Never connect into a chimney serving a fireplace unless the fireplace opening is sealed off.
8. No portion of venting system shall extend into, or pass through, any circulating air duct or plenum.
9. Chimney or gas vent shall extend at least 5 ft above highest connected draft hood and should extend high enough above roof or neighboring obstruction, so that wind from any direction will not create positive
pressure in vicinity of chimney or gas vent outlet. Chimney or gas vent should extend 3 ft higher than point of emergence through roof, and at least 2 ft higher than any object within a radius of 10 feet. See
Fig. 5.
A type-B 1 gas vent shall terminate above roof surface
10.
with a listed cap or roof assembly.
Common Venting with Other Appliances —
This furnace may be connected to a common chimney or listed type-Bl gas vent with other listed gas-fired appli ances. The vent system of this induced-draft furnace operates at negative pressure during normal operation. If
for any reason the pressure in the vent system becomes positive (may happen if chimney is inadvertently blocked), the furnace shuts down and locks off. This is accomplished by means of draft safeguard switch located on tube attached to relief box just above draft inducer blower. The design of this furnace, equipped with draft safeguard switch, has been tested by the American Gas Association Laboratories.
MORE THAN
Fig. 5 — Chimney, Gas Vent Height
Type-BI Gas Vent — Note that this furnace may
be connected to type-Bl gas vents. Type-Bl vents are suitable, providing the vent system always operates at zero or negative pressure. The vent system of this furnace meets this standard.
For Replacement Installations, Refer to
Appendix, page 7.
ELECTRICAL
IMPORTANT: Before proceeding with electrical connections, make certain that voltage, frequency and phase correspond to that specified on the furnace rating plate. Also, check to be sure the service pro vided by the utility is sufficient to handle the addi tional load imposed by this equipment. Refer to unit rating plate for equipment electrical requirements.
The specific furnace installation instructions contain wiring diagrams which show the proper field high- and low-voltage wiring. Make all connections in accordance with National Electrical Code and any local codes or ordinances that apply.

A WARNING

The cabinet must have an uninterrupted or unbroken
ground according to National Electrical Code,
ANSl/NFPA 70-1984 and local codes to minimize
personal injury if an electrical fault should occur.
Ground may be electrical wire or conduit, approved
for electrical ground when installed in accordance
with electrical codes. Do not use gas piping as
electrical ground.
START-UP, ADJUSTMENT, AND
SAFETY CHECK
Intermittent Ignition Systems — Check to be sure
all connections have been properly made, then proceed as follows:
Light furnace, using the procedure outlined on the lighting instruction plate attached to the furnace. However, when lighting the pilot for the first time, perform the following additional steps:
1. If supply line was not purged before connecting fur nace, it will be full of air. It is recommended that the ground joint union be loosened, and supply line be allowed to purge until odor of gas is detected. Never purge gas lines into a combustion chamber. Imme diately upon detection of gas odor, retighten the union. Allow 5 minutes to elapse, then light pilot in accordance with instructions on furnace.
2. After pilot lights, main burners should light in 25-75 seconds. If main burners do not light within that time period, adjust pilot flame, allow pilot to cool for 5 minutes, repeat time check.
3. Locate pilot adjusting screw on top of gas valve. a. Remove cap screw; turn pilot adjusting screw
counterclockwise to decrease burner-on time delay,
clockwise to increase burner-on time delay.
b. Replace cap screw.
Gas Input — Determine gas input as follows:
NATURAL GAS
a. Turn off all other gas appliances and pilots.
b. Measure time (in seconds) for gas meter test dial to
complete one revolution.
c. Refer to Table 2 for cu ft of gas per hour.
Multiply cu ft per hour times heating value of gas
d.
(Btu/cu ft). Obtain heating value of gas from local
utility. Example:
Btuh heating input = Btu/cu ft x cu ft/hr
Heat value of gas = 1070 Btu/cu ft Time for one revolution of 2 cu ft dial = 72 seconds Gas rate = 100 cu ft/hr (from Table 2)
Btuh heating input = 1070 x 100 = 107,000 Btuh Measured gas input should not exceed gas input
e.
shown on unit rating plate.
PILOT flame
BURNER FLAME

A CAUTION

If manual disconnect switch is to be mounted on furnace, select a mounting location where drill or fastener will not contact electrical or gas components.
NOTE: Use only copper wire between disconnect switch and furnace.
Check all electrical connections (both factory and field)
for tightness. This should also be done after the unit has reached operating temperatures, especially if aluminum conductors are used.
Table 2 — Gas Rate (Cu Ft Per Hr)
SECONDS
FOR ONE
REVOLU-
TION
10 11 12 13 14 257
15 16 17 18 19
20 21 22 23 24 150
25 26 138 27 133 28 29
30 31 32 33 34 106
35 36 37 38 39
40 41 88
42 86 43 44
45 46 47 48 75
49
SIZE OF
TEST DIAL
1 2
cu ft cu ft cu ft
720
360 327 655 1636 51 300 600 1500 52 69 138 346
555
277
514
240 480 1200 55 225 450 1125 56
424
212 200 400 1000 58 189 379 947 59
180 360 900 60 60 171 343 857 62 58 164 327 818 64 56 112 157 313 783 66
300 750 68 53 106 265
144 288
277 692 72 267 667 74 257 643
129
124 248 621 78 46
240 600 80 45
120
232
116 113 225 563
218
109
212
103 206 100 200 500 92 39 78
97 195 486 94 38 75 192 95 189 474 96 38 75 188
185
92 90 180 450 100 36 72 180
176
172 84 167 82 164
80 160
157
78 76 153
150 73 147
SECONDS
FOR ONE REVOLU-
5
TION
1800 50
1385 53 68 1286
54 67 133 333
1059 57 63
720 70
76 47
581 545 86
529 88 514
82 44 84
90 40 80 200
462 98 439 102 35
429 419 409
400 391 383 375
367
104 35 69 173 106 34 68 170 108 33 67
110 33 65 112 32 64 161 116 31 62 155 120
SIZE OF
TEST DIAL
1
2
cuft cu ft
72 144 360 71
cu ft
141 355 136 340
131
65 64
129
126 316 62 124 310 61
122
120 300
116 290 54
109 51 103 257
100 250
50
97 243
48
95 237 92
80 78 76
43
75
42
74
41
37 74 184
71 178
60 150
30
5
327 321
305
281 273
231
225 220 214 209 205
196
167 164
f. To adjust input rate, remove cap that conceals regu
lator adjustment. Turn adjusting screw counterclock
wise (out) to decrease input When adjusting, DO
NOT change manifold pressure more than 0.3 in. wg. Make any major adjustment by changing main burner orifices.
HIGH ALTITUDE— Ratings are approved for altitudes to 2000 ft for all gases. Ratings for altitudes over 2000 ft are 4% less for each 1000 ft above sea level. (Furnace must be derated by changing main burner orifices.)
BURNER AND PILOT FLAMES — The main burner flame should be elear blue, almost transparent. The pilot flame should be well defined. See Fig. 6.
Temperature Rise — Do not exceed the range of
temperature rise specified on the unit rating plate. Deter
mine the air temperature rise as follows:
1. Place duct thermometers in return and supply ducts as near furnace as possible. Be sure thermometers do not “see” heat element so that radiant heat will not affect thermometer readings. This is partieularly important with straight-run duets.
2. When thermometer readings stabilize, subtract return­air temperature from supply-air temperature to deter
mine air temperature rise.
3. Adjust air temperature rise by adjusting blower speed.
Increase blower speed to reduce temperature rise. Decrease blower speed to increase temperature rise.
Thermostat Heat Anticipator Check — Thermo
stat heat anticipator must be set to match amp draw of gas valve and eleetrical components in R-W circuit.
Accurate amp draw readings can be obtained at thermo
stat subbase terminals R & W. Figure 7 illustrates an easy
method of obtaining actual amp draw. Amp reading should be taken after blower motor has started.
Fig. 7 — Amp Draw Check with Ammeter
Limit Control Safety Check — This control shuts
off the combustion control system and energizes the circulating-air blower motor if the furnace overheats.
The recommended method of checking the limit con trol is to gradually block off the return air after the furnace has been operating for at least 5 minutes. As soon as the limit has proven safe, the return air opening should be unblocked to permit normal air circulation. By using this method to check the limit control, it can be established that the limit is functioning properly and will “fail-safe” if there is a motor failure. The downflow/ horizontal furnaces have a manual reset limit switch located on blower housing.
Flow-Sensing Switch Safety Check — This con
trol proves operation of the draft inducer blower. Check as follows:
1. Turn off 115-volt power to furnace.
2. Remove control door and disconnect inducer motor lead wires from inducer printed-circuit board.
3. Turn on 115-volt power to furnaee.
4. Close thermostat switch as if making a normal furnace start. The pilot should light and then cycle off and on.
If main burners do not light, flow-sensing switch is
functioning properly.
5. Turn off 115-volt power to furnace.
6. Reconnect inducer motor wires, replace control door, turn on 115-volt power.
Draft Safeguard Switch Safety Check — This
control permits safe shutdown of furnace during certain blocked flue conditions. Check as follows:
1. Disconnect power to furnace and remove vent pipe from furnace outlet collar. Allow time for vent pipe to cool before removing.
2. Set room thermostat above room temperature and restore power to furnace.
3. After normal start-up, allow furnace to operate 2 minutes. Block (100%) flue outlet. Furnace should cycle off within 2 minutes.
4. Reeonneet vent pipe to furnaee outlet collar.
5. Wait 5 minutes. Reset draft safeguard switch.
FURNACE LOCATION WITH RESPECT
TO COOLING EQUIPMENT
The cooling coil must be installed parallel with, or on the downstream side of the furnace to avoid condensa tion in the heating element. When installed parallel with a furnace, dampers or other means used to control the flow of air must prevent chilled air from entering the unit. If the dampers are manually operated, they must be equipped with means to prevent operation of either unit unless the damper is in the full-heat or full-cool position.
APPENDIX —
Venting Replacement Installations
SPECIAL LOCATIONS
When the furnace is installed in a residential garage, burners and ignition source should be no less than 18 in. above the floor. Furnace should be protected against physical damage by vehicles.
When the furnace is installed in public garages, air plane hangars, or other buildings having hazardous atmospheres, it should be installed in accordance with recommended good practice requirements of the National
Fire Protection Association.
1. The vent is a critical part of the heating system. It should always be examined prior to installation of the furnace.
II. When installing high-efficiency furnaces on a venting
system that is “marginal,” the following suggestions may help;
A. Set furnace to full input rate. New furnaces are
commonly set conservatively at factory.
Existing Chimney
Type-BI Vents
Existing Chimney
Masonry Chimney
B. Minimize restrictions in vent connector — use as
few elbows as possible.
C. Insulate any long horizontal single-wall vent
connector with 1/2-in. insulation or use double wall pipe.
D. Follow recommendations in flow charts regarding
application of 58SC, SS, DH induced-draft fur naces on existing chimney.
Existing Chimney
Masonry Chimney — Tile Liner

58SS/DH

HEATING A COOLING

Induced-Combustion Gas-Fired Furnaces

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book|l PC 101 Catalog No 515-808 Printed in USA Form 58D,S-2XA Pg 8 6-85 Replaces: 58D,S-1XA Tab l6a
Loading...