Installing and servicing heating equipment can be hazardous due to
gas and electrical components. Only trained and qualified personnel should install, repair, or service heating equipment.
Untrained personnel can perform basic maintenance functions
such as cleaning and replacing air filters. All other operations must
be performed by trained service personnel. When working on
®
heating equipment, observe precautions in the literature, on tags,
and on labels attached to or shipped with the unit and other safety
precautions that may apply.
Table 1—Clearances From Combustible
UNIT SIZE050 AND 070 096-135
DOWNFLOW (In Alcove or Closet)
SidesSingle-Wall Vent10
Type B-1 Double-Wall Vent00
Back00
Top11
FrontSingle-Wall Vent6†6†
Type B-1 Double-Wall Vent3†3†
VentSingle-Wall Vent66
Type B-1 Double-Wall Vent11
HORIZONTAL (Attic, Alcove, or Crawlspace)
Sides *10
Back00
TopSingle-Wall Vent11
Type B-1 Double-Wall Vent11
Front‡Single-Wall Vent6†6†
Type B-1 Double-Wall Vent3†3†
VentSingle-Wall Vent66
Type B-1 Double-Wall Vent11
HORIZONTAL (In Closet)
Sides *11
Back00
TopSingle-Wall Vent22
Type B-1 Double-Wall Vent22
FrontSingle-Wall Vent66
Type B-1 Double-Wall Vent33
VentSingle-Wall Vent66
Type B-1 Double-Wall Vent11
* Indicates supply or return sides when furnace is in the horizontal position.
† Clearance shown is for outlet end. The inlet end must maintain 6-in.
minimum clearance from the vent to combustible materials when using
single-wall vent.
‡ Minimum 18-in. front clearance required for alcove.
NOTES:
1. Provide 30-in. front clearance for servicing. An open door in front of the
furnace can meet this requirement.
2. A minimum clearance of 3 in. must be provided in front of the furnace for
combustion air and proper operation.
3. Line contact is permitted as shown in Fig. 7.
Follow all safety codes. In the United States, follow all safety
codes including the National Fuel Gas Code (NFGC) NFPA No.
54-1992/ANSI Z223.1-1992. In Canada, refer to the current
ama
Materials (In.)
58RAV
CANADIAN GAS ASSOCIATION
APPROVED
R
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4
Tab 6a 8a
PC 101Catalog No. 565-863Printed in U.S.A.Form 58RA-10SIPg 18-95Replaces: 58RA-9SI
Page 2
13
⁄16″
39 7⁄8″
20″
INLET
ACCESSORY
3
1
⁄4″ DIA HOLE
GAS ENTRY
28 1⁄2″
7
⁄8″ DIA
VENT CONNECTION
13
⁄16″
9 1⁄8″
10 1⁄4″
1
⁄2″ DIA
D
4 3⁄16″
2 15⁄16″
16 1⁄16″
2″
THERMOSTAT
WIRE ENTRY
7
⁄8″ DIA
ACCESSORY
7
⁄8″ DIA HOLE
POWER ENTRY
1 1⁄2″ DIA
R.H. GAS ENTRY
7
⁄8″ DIA
ACCESSORY
″ TYP
1
11
⁄16″
OUTLET
19″
ADDITIONAL 7⁄8″ DIA K.O. ARE
NOTE:
LOCATED IN THE TOP PLATE
AND BOTTOM PLATE
1 1⁄16″
2 1⁄8″
8 1⁄4″
E
11
⁄16″
A
AIRFLOW
13 5 ⁄16″
10 1⁄4″
11
⁄16″
DIMPLES TO DRILL HOLES
FOR HANGER BOLTS (4 PLACES)
IN HORIZONTAL POSITION
edition of the National Standard of Canada CAN/CGA-B149.1and .2-M91 Natural Gas and Propane Installation Codes (NSCNGPIC). Wear safety glasses and work gloves. Have fire extinguisher available during start-up and adjustment procedures and
service calls.
Recognize safety information. This is the safety-alert symbol
When you see this symbol on the unit and in instructions or
manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, and CAUTION. These words are used with the safety-alert symbol. DANGER identifies the most serious hazards which will result in severe
personal injury or death. WARNING signifies a hazard which
could result in personal injury or death. CAUTION is used to
identify unsafe practices which would result in minor personal
injury or product and property damage. NOTE is used to highlight
suggestions which will result in enhanced installation, reliability,
or operation.
These instructions cover minimum requirements and conform to
existing national standards and safety codes. In some instances,
these instructions exceed certain local codes and ordinances,
especially those that may not have kept up with changing residential construction practices. We require these instructions as a
minimum for a safe installation.
.
ELECTROSTATIC DISCHARGE (ESD) PRECAUTIONS
PROCEDURE
Electrostatic discharge can affect electronic components.
Take precautions during furnace installation and servicing to
protect the furnace electronic control. Precautions will prevent electrostatic discharges from personnel and hand tools
which are held during the procedure. These precautions will
help to avoid exposing the control to electrostatic discharge
by putting the furnace, the control, and the person at the same
electrostatic potential.
1. Disconnect all power to the furnace. DO NOT TOUCH THE
CONTROL OR ANY WIRE CONNECTED TO THE CONTROL PRIOR TO DISCHARGING YOUR BODY’S ELECTROSTATIC CHARGE TO GROUND.
2. Firmly touch a clean, unpainted, metal surface of the furnace
chassis which is close to the control. Tools held in a person’s
hand during grounding will be satisfactorily discharged.
3. After touching the chassis you may proceed to service the
control or connecting wires as long as you do nothing that
recharges your body with static electricity (for example; DO
NOT move or shuffle your feet, DO NOT touch ungrounded
objects, etc.).
5
⁄8″ TYP
A88324
2
Page 3
4. If you touch ungrounded objects (recharge your body with
static electricity), firmly touch furnace again before touching
control or wires.
5. Use this procedure for installed and uninstalled (ungrounded)
furnaces.
6. Before removing a new control from its container, discharge
your body’s electrostatic charge to ground to protect the
control from damage. If the control is to be installed in a
furnace, follow items 1 through 5 before bringing the control
or yourself into contact with the furnace. Put all used AND
new controls into containers before touching ungrounded
objects.
7. An ESD service kit (available from commercial sources) may
also be used to prevent ESD damage.
INTRODUCTION
The model 58RAV Series 151 Furnaces are available in sizes
→
50,000 through 135,000 Btuh input capacities.
The design of the downflow/horizontal gas-fired furnace is
A.G.A./C.G.A. certified for natural and propane gas and for
installation on noncombustible flooring. The furnace may be
installed on combustible flooring when installed with the accessory downflow subbase. This furnace is for installation in alcoves,
attics, crawlspaces, basements, closets, or utility rooms. The
design of this furnace line is not A.G.A./C.G.A. certified for
installation in mobile homes, recreation vehicles, or outdoors.
Before installing the furnace, refer to the current edition of the
NFGC. Canadian installations must be installed in accordance
NSCNGPIC and all authorities having jurisdiction. For further
information, the NFGC is available from National Fire Protection
Association Inc. Batterymarch Park, Quincy, MA 02269; American Gas Association, 1515 Wilson Boulevard, Arlington, VA
22209; or from Literature Distribution.
Application of this furnace should be indoors with special
attention given to vent sizing and material, gas input rate, air
temperature rise, and unit sizing. Improper installation or
misapplication of the furnace can require excessive servicing
or cause premature component failure.
Installation must conform to the regulations of the serving gas
supplier and the local building, heating, and plumbing codes in
effect in the area in which the installation is made, or in the
absence of local codes with the requirements of the NFGC.
This furnace is designed for a minimum continuous return-air
temperature of 60°F db or intermittent operation down to 55°F db
such as when used with a night setback thermostat. Return-air
temperature must not exceed a maximum of 85°F db.
Improper installation, adjustment, alteration, service, maintenance, or use can cause carbon monoxide poisoning, explosion, fire, electrical shock, or other conditions which may
cause personal injury, loss of life, or property damage.
Consult a qualified installer, service agency, local gas supplier, or your distributor or branch for information or assistance. The qualified installer or agency must use only
factory-authorized and listed kits or accessories when modifying this product. Failure to follow this warning could result
in electrical shock, fire, personal injury, or death.
For accessory installation details, refer to the applicable installation literature.
NOTE: Remove all shipping brackets and materials before operating the furnace.
Step 1—Location
GENERAL
Do not install furnace in a corrosive or contaminated atmosphere. Make sure all combustion and circulating air requirements are followed, in addition to all local codes and
ordinances.
Do not use this furnace during construction when adhesives,
sealers, and/or new carpets are being installed. If the furnace
is required during construction, use clean outside air for
combustion and ventilation. Compounds of chlorine and
fluorine when burned with combustion air form acids which
cause corrosion of the heat exchangers and metal vent system.
Some of these compounds are found in paneling and dry wall
adhesives, paints, thinners, masonry cleaning materials, and
many other solvents commonly used in the construction
process.
This furnace must be installed so the electrical components are
protected from water.
Locate the furnace as close to the chimney/vent and as near the
center of the air distribution system as possible. The furnace
should be installed as level as possible.
When a furnace is installed so that the supply ducts carry air to
areas outside the space containing the furnace, the return air must
also be handled by a duct(s) sealed to the furnace casing and
terminating outside the space containing the furnace.
Provide ample space for servicing and cleaning. Always comply
with the minimum fire protection clearances shown on the unit
rating plate. This furnace shall not be installed directly on
carpeting, tile, or any combustible material other than wood
flooring. The furnace may be installed on combustible flooring
when installed with the accessory downflow subbase, which is
available from your distributor or branch when required.
LOCATION RELATIVE TO COOLING EQUIPMENT — The
cooling coil must be installed parallel with or on the downstream
side of the furnace to avoid condensation in the heat exchangers.
When installed parallel with a furnace, dampers or other means
used to control the flow of air must prevent chilled air from
entering the unit. If the dampers are manually operated, they must
be equipped with means to prevent operation of either unit unless
the damper is in the full-heat or full-cool position.
HAZARDOUS LOCATIONS — When the furnace is installed in
a residential garage, it must be installed so that the burners and
ignition source are located at least 18 in. above the floor. The
furnace should be protected from physical damage by vehicles.
When a furnace is installed in public garages, airplane hangars, or
other buildings having hazardous atmospheres, the unit must be
installed in accordance with the recommended good practice
requirements of the National Fire Protection Association, Inc.
Step 2—Air For Combustion and Ventilation
Provisions for adequate combustion and ventilation air must be
provided in accordance with Section 5.3 of the NFGC, Air for
Combustion and Ventilation, or applicable provisions of the local
building codes.
Canadian installations must be installed in accordance with NSCNGPIC and all authorities having jurisdiction.
3
Page 4
Air for combustion must not be contaminated by halogen
compounds, which include fluoride, chloride, bromide, and
iodide. These elements are found in aerosol sprays, detergents, bleaches, cleaning solvents, salts, air fresheners, and
other household products.
The operation of exhaust fans, kitchen ventilation fans,
clothes dryers, or fireplaces could create a NEGATIVE
PRESSURE CONDITION at the furnace. Make-up air MUST
be provided for the ventilation devices, in addition to that
required by the furnace.
All fuel-burning equipment must be supplied with air for combustion of the fuel. Sufficient air MUST be provided to ensure there
will not be a negative pressure in the equipment room or space. In
addition, a positive seal MUST be made between the furnace
cabinet and the return-air duct to avoid pulling air from the burner
area and draft safeguard opening.
The requirements for combustion and ventilation air depend upon
whether the furnace is located in an unconfined or confined space.
UNCONFINED SPACE — An unconfined space must have at
least 50 cu ft for each 1000 Btuh of input for all the appliances
(such as furnaces, clothes dryer, water heaters, etc.) in the space.
For Example:
58RAV FURNACE
INPUT BTUH
46,000307
69,000460
92,000613
115,000767
135,000920
MINIMUM SQ FT
WITH
7-1/2 FT CEILING
If the unconfined space is constructed unusually tight, air for
combustion and ventilation MUST come from either the outdoors
or spaces freely communicating with the outdoors. Combustion
and ventilation openings must be sized the same as for a confined
space. A minimum opening with a total of at least 1 sq in. per 5000
Btuh of total input rating for all equipment must be provided.
Return air must not be taken from the room unless an equal or
greater amount of air is supplied to the room.
CONFINED SPACE — A confined space has volume less than 50
cu ft per 1000 Btuh of the total input ratings of all appliances
installed in that space. A confined space MUST have 2 permanent
openings, 1 within 12 in. of the ceiling, and the other within 12 in.
of the floor. (See Fig. 2.)
NOTE: In determining the free area of an opening, the blocking
effect of the louvers, grilles, and screens must be considered. If the
free area of a louver or grille design is unknown, assume that wood
louvers have a 20 percent free area and metal louvers or grilles
have a 60 percent free area. Screens, when used, must not be
smaller than 1/4-in. mesh. Louvers and grilles must be constructed
so they cannot be closed.
The size of the openings depends upon whether the air comes from
inside or outside the structure.
1. All air from inside the structure:
a. Each opening MUST have at least 1 sq in. of free area per
1000 Btuh of the total input for all equipment within the
confined space, but not less than 100 sq in. per opening.
(See Fig. 2.)
INTERIOR
HEATED
SPACE
SUPPLY AIR
* Minimum opening size is 100 square in. with
minimum dimensions of 3-In.
†
Minimum of 3-In. when type B-1 vent is used.
Fig. 2—Air for Combustion and Ventilation
For Example:
58RAV FURNACE
INPUT BTUH
46,000100
69,000100
92,000100
115,000115
135,000138
b. If the building is constructed unusually tight, a permanent
opening directly communicating with the outdoors should
be provided. This opening should have a minimum free
area of 1 sq in. per 5000 Btuh of total input rating for all
equipment in the enclosure.
c. If the furnace is installed on a raised platform to provide a
return-air plenum, and return air is taken directly from the
hallway or space adjacent to the furnace, all air for
combustion must come from outdoors. (See Fig. 3.)
2. All air from outside the structure:
a. If combustion air is taken from outdoors through vertical
ducts, the openings and ducts MUST have at least 1 sq in.
of free area per 4000 Btuh of the total input for all
equipment within the confined space.
b. If combustion air is taken from the outdoors through
horizontal ducts, the openings and ducts MUST have at
least 1 sq in. of free area per 2000 Btuh of the total input
for all equipment within the confined space.
c. When ducts are used, they must be of the same cross-
sectional area as the free area of the openings to which they
connect. The minimum dimension of rectangular ducts
must not be less than 3 in. (See Fig. 3.)
4
RETURN
AIR
(Inside Air)
VENT THROUGH ROOF
(CATEGORY I)
12″ MAX
1 SQ IN.
PER 1000
BTUH* IN DOOR
OR WALL
UNCONFINED
SPACE
6″ MIN
(FRONT)
1 SQ IN.
PER 1000
BTUH* IN DOOR
OR WALL
FREE AREA PER
OPENING (SQ IN.)
†
12″ MAX
A93387
Page 5
DUCTS TO
OUTDOORS
1 SQ IN.
PER 4000
BTUH
*
A
12″ MAX
1 SQ IN.
PER 2000
BTUH
*
DUCTS
TO
OUTSIDE
1 SQ IN.
PER 2000
BTUH
*
12″ MAX
SUPPLY AIR
Minimum dimensions of 3-In.
*
Use any of the following
NOTE:
combinations of openings:
A & B C & D D & E F & G
RETURN
A
B
AIR
D
VENT
THROUGH
ROOF
(CATEGORY I)
CONFINED
E
C
DUCT
TO
OUTDOORS
F
SPACE
G
12″ MAX
1 SQ IN.
PER 4000
BTUH
Fig. 3—Air for Combustion and Ventilation
(Outside Air)
12″
MAX
1 SQ IN.
PER 4000
BTUH
*
OUTDOORS
1 SQ IN.
PER 4000
BTUH
*
12″
MAX
A93388
HOLE IN
FLOOR
B
A73382
Fig. 4—Floor Opening for Concrete Slab
Table 3—Opening Dimensions (In.)
FURNACE CASING
WIDTH
14-3/1613-1/819-5/819-7/16
17-1/216-7/1619-5/819-7/16
2119-7/819-5/819-7/16
24-1/223-7/1619-5/819-7/16
* These dimensions apply when a model CB or CD Evaporator Coil casing is
to be installed.
A
Heat-OnlyHeat/Cool*
B
For Example:
58RAV FURNACE
INPUT BTUH
46,00011.54
69,00017.35
92,00023.06
115,00028.87
135,00034.57
FREE AREA PER
OPENING (SQ IN.)
ROUND PIPE
(IN. DIA)
For Example:
58RAV FURNACE
INPUT BTUH
46,00023.06
69,00034.37
92,00046.08
115,00057.69
135,00069.010
FREE AREA PER
OPENING (SQ IN.)
ROUND PIPE
(IN. DIA)
Step 3—Supply-Air Plenum Installation (Downflow)
INSTALLATION ON A CONCRETE SLAB
1. Construct hole in floor per dimensions in Fig. 4 and Table 3.
2. Install plenum and furnace as shown in Fig. 5.
INSTALLATION ON A COMBUSTIBLE FLOOR
1. Cut and frame hole in floor per dimensions in Installation
Instructions packaged with downflow subbase.
FURNACE
PLENUM
A73383
Fig. 5—Furnace on a Concrete Slab
(Non-Garage Installation)
2. When completed, downflow subbase, plenum, and furnace (or
coil casing when used) should be installed as shown in Fig. 6.
5
Page 6
FURNACE
(OR COIL CASING
WHEN USED)
DOWNFLOW
SUBBASE
SHEET METAL
PLENUM
A78651
Fig. 6—Furnace, Plenum, and Subbase Installed on
a Combustible Floor
Step 4—Horizontal Attic Installation
CONSTRUCT A WORKING PLATFORM
Construct working platform on location where all required
furnace clearances are met. (See Table 1 and Fig. 7.)
INSTALL FURNACE
1. Position furnace in desired location.
2. Connect gas supply pipe. See Fig. 7 for typical piping entry.
3. Install field-supplied filter retainers as indicated in Fig. 8 and
Table 4 before connecting return-air duct to furnace.
4. Connect supply- and return-air ducts.
5. Install 24- X 24-in. sheet metal shield on platform in front of
louvered control panel as shown in Fig. 7.
Step 5—Horizontal Crawlspace Installation
The furnace can be installed horizontally with either the LH or RH
side up. In a crawlspace, the furnace can either be hung from the
floor joist or installed on suitable blocks or pad. The furnace can
be suspended from each corner by hanger bolts (4 each 3/8-in.
all-thread rod) cut to desired length, 1- X 3/8-in. flat washer,
3/8-in. lockwasher, and 3/8-in. nut. Dimples are provided for hole
locations. (See Fig. 1.)
Since horizontal crawlspace installation is very similar to the attic
installation, refer to Step 4. The installation of a sheet metal shield
in front of the louvered control panel is covered in Step 4. For a
crawlspace installation, this same sheet metal shield must be
installed above the louvered control panel. Extend the sheet metal
shield over the furnace top far enough to cover the gas pipe entry
hole.
Step 6—Filter Arrangement
Do not install the furnace on its back; safety control operation
will be adversely affected. Never connect return-air ducts to
the sides or back of the furnace. Failure to follow this warning
could result in fire, personal injury, or death.
The furnace can be installed horizontally on either the left-hand
(LH) or right-hand (RH) side. A typical attic installation is shown
in Fig. 7.
LINE CONTACT ONLY PERMISSIBLE BETWEEN
LINES FORMED BY INTERSECTIONS OF
THE TOP AND TWO SIDES OF THE FURNACE
JACKET AND BUILDING JOISTS,
STUDS, OR FRAMING.
SHEET
METAL
GAS
ENTRY
24
Never operate unit without a filter or with filter access door
removed. Failure to follow this warning could result in fire,
personal injury, or death.
The 2 factory-supplied filters are shipped in the blower compartment. After the return-air duct has been connected to the furnace,
install the filters in a V-formation inside the return-air plenum. See
FLUE VENT
MIN
″
24
6
″
″
30-IN. MIN
WORK AREA
SEDIMENT TRAP
A82178
Fig. 7—Typical Attic Installation
6
Page 7
Fig. 8 and Table 4 for horizontal applications. Horizontal filter
retainers must be field supplied. See Fig. 9 for downflow applications.
AIRFLOW
12″
4″
FIELD-SUPPLIED
FILTER RETAINERS
D
A82173
Fig. 8—Horizontal Filter Arrangement
Table 4—Filter Retainer (In.)
FURNACE
CASING WIDTH
14-3/16(2) 14 X 20 X 114-3/8
17-1/2(2) 14 X 20 X 113-3/8
21(2) 16 X 20 X 111-5/8
24-1/2(2) 16 X 20 X 110-1/4
FILTER SIZE
AND QUANTITY
D
Canadian installations must be installed in accordance with NSCNGPIC and all authorities having jurisdiction.
Refer to Table 5 for recommended gas pipe sizing. Risers should
be used to connect to the furnace and to the meter.
* Cubic ft of gas per hr for gas pressures of 0.5 psig (14-in. wc) or less, and a
pressure drop of 0.5-in. wc (based on a 0.60 specific gravity gas). Ref: Table
10-2 NFPA 54/ANSI Z223.1-1992.
If a flexible connector is required or allowed by the authority
having jurisdiction, black iron pipe shall be installed at the
gas valve and extend a minimum of 2 in. outside the furnace
casing.
Use the proper length of pipes to avoid stress on the gas
control manifold. Failure to follow this warning could result
in a gas leak, causing fire, explosion, personal injury, or
death.
INTERNAL
DIAMETER
(IN.)
LENGTH OF PIPE (FT)
1020304050
AIRFLOW
INSTALLATION
POSITION
OF FILTERS
RETURN-AIR
PLENUM
ACCESS DOOR
A88486
Fig. 9—Downflow Filter Arrangement
Step 7—Gas Piping
Gas piping must be installed in accordance with national and local
codes. Refer to the current edition of the NFGC.
Connect the gas pipe to the furnace using a backup wrench to
avoid damaging gas controls.
Never purge a line into a combustion chamber. Never use
matches, candles, flame, or other sources of ignition to check
for gas leakage. Use a soap-and-water solution to check for
gas leaks. Failure to follow this warning could result in fire,
explosion, personal injury, or death.
Joint compounds (pipe dope) should be applied sparingly and only
to the male threads of the joints. This pipe dope must be resistant
to the action of propane gas.
Install an accessible manual shut-off valve upstream of the furnace
gas controls and within 72 in. of the furnace. A 1/8-in. NPT
plugged tapping, accessible for test gage connection, must be
installed immediately upstream of the gas supply connection to the
furnace and downstream of the manual shut-off valve. Place a
ground joint union between the gas control manifold and the
manual shut-off.
Install a sediment trap in the riser leading to the furnace. The trap
can be installed by connecting a tee to the riser leading from the
furnace. Connect a capped nipple into the lower end of the tee. The
capped nipple should extend below the level of the gas controls.
(See Fig. 10.)
Piping should be pressure tested in accordance with local and
national plumbing and gas codes before the furnace has been
attached. If the pressure exceeds 0.5 psig (14-in. wc), the gas
supply pipe must be disconnected from the furnace and capped
before the pressure test. If the test pressure is equal to or less than
7
Page 8
GAS
SUPPLY
MANUAL
SHUTOFF
VALVE
SEDIMENT
TRAP
UNION
A89414
Fig. 10—Typical Gas Pipe Arrangement
0.5 psig (14-in. wc), close the manual shut-off valve located on the
gas valve before the test. It is recommended that the ground joint
union be loosened before pressure testing.
After all connections have been made, purge the lines and check
for gas leakage with regulated gas supply pressure.
Step 8—Electrical Connections
115-V WIRING
Refer to the unit rating plate or Table 6 for equipment electrical
requirements. The control system requires an earth ground for
proper operation.
Do not connect aluminum wire between disconnect switch
and furnace. Use only copper wire.
Make all electrical connections in accordance with the current
edition of the National Electrical Code (NEC) ANSI/NFPA
70-1993, and any local codes or ordinances that might apply. For
Canadian installations, all electrical connections must be made in
accordance with Canadian Electrical Code CSA C22.1, or authorities having jurisdiction.
NOTE: Proper polarity must be maintained for 115-v wiring. If
polarity is incorrect, control center fault code indicator light will
flash rapidly and furnace will not operate.
The cabinet MUST have an uninterrupted or unbroken ground
according to NEC ANSI/NFPA 70-1990 and Canadian Electrical Code CSA C22.1 or local codes to minimize personal
injury if an electrical fault should occur. This may consist of
electrical wire or conduit approved for electrical ground when
installed in accordance with existing electrical codes. Do not
use gas piping as an electrical ground. Failure to follow this
warning could result in electrical shock, fire, or death.
24-V WIRING — Make field 24-v connections at the 24-v terminal strip. (See Fig. 11.) Connect terminal Y as shown in Fig. 12 for
proper operation in cooling mode. Use AWG No. 18 color-coded
wire only.
The 24-v circuit contains an automotive-type, 3-amp fuse located
on the main control board. Any direct shorts during installation,
service, or maintenance could cause this fuse to blow. If fuse
replacement is required, use ONLY a 3-amp fuse of identical size.
ACCESSORIES
1. Electronic air cleaner (EAC)
Two quick-connect terminals, marked EAC-1 and EAC-2, are
provided for EAC connection. (See Fig. 11.) These terminals
are energized with 115v (1.5-amp maximum) during blower
motor operation.
2. Humidifier (HUM)
Quick-connect terminal (HUM) and screw terminal (Com) are
provided for 24-v humidifier connection. The terminals are
energized with 24v (0.5-amp maximum) after inducer motor
prepurge period.
NOTE: A field-supplied, 115-v controlled relay connected to
EAC terminals may be added if humidifier operation is desired
during blower operation.
Step 9—Venting
Refer to the enclosed Installation Instructions, GAMA Venting
Tables for Category I Furnaces and Venting Tables for Category I
Fan-Assisted Furnaces. The horizontal portion of the venting
system shall maintain a minimum of 1/4-in. upward slope per
linear ft and it shall be rigidly supported every 5 ft or less with
hangers or straps to ensure that there will be no movement after
installation.
* Permissible limits of the voltage range at which the unit will operate satisfactorily.
† Time-delay fuse is recommended.
‡ Length shown is as measured 1 way along wire path between unit and service panel for maximum 2 percent voltage drop.
VOLTS—
HERTZ—
PHASE
OPERATING VOLTAGE RANGE
Maximum*Minimum*
Table 6—Electrical Data
MAXIMUM
UNIT AMPS
8
MINIMUM
WIRE GAGE
MAXIMUM WIRE
LENGTH FT‡
MAXIMUM
FUSE OR HACR-
TYPE CKT BKR
AMPS†
Page 9
GRYW
24-V THERMOSTAT
TERMINALS
TEST/TWIN
3-AMP FUSE
115-VAC (L1)
POWER SUPPLY
HOT SURFACE
IGNITOR CONNECTOR
SEC-1
COOL
HEAT
OM
C
HUM
24V
HUMIDIFIER TERMINAL
(24-VAC 0.5 AMP MAX)
LED OPERATION &
DIAGNOSTIC LIGHT
HARNESS CONNECTOR
24-V TRANSFORMER SEC-2
SPARE-1
BLOWER SPEED
SELECTION TERMINALS
SPARE-2
EAC-1
EAC-ELECTRONIC AIR CLEANER
TERMINALS (115-VAC 1.5 AMP MAX)
EAC-2
115-VAC (L2) NEUTRAL
CONNECTION
INDUCER MOTOR
CONNECTOR
Fig. 11—Control Board
A95086
BLK
WHT
GND
115-VOLT FIELD-
SUPPLIED
FUSED
DISCONNECT
THREE-WIRE
BLK
WHT
AUXILIARY
J-BOX
FIELD 24-VOLT WIRING
FIELD 115-, 208/230-, 460-VOLT WIRING
FACTORY 24-VOLT WIRING
FACTORY 115-VOLT WIRING
FIVE
WIRE
NOTE 2
WCRGY
THERMOSTAT
TERMINALS
FIELD-SUPPLIED
FUSED DISCONNECT
HEATING-
ONLY
W
R
GND
CONTROL
BOX
FURNACE
G
C
Y
24-VOLT
TERMINAL
BLOCK
NOTE 1
CONDENSING
UNIT
TWO
WIRE
NOTES:Connect Y-terminal as shown for proper operation.
1.
2.
Some thermostats require a "C" terminal connection as shown.
3.
If any of the original wire, as supplied, must be replaced, use
same type or equivalent wire.
Fig. 12—Heating and Cooling Application Wiring Diagram
GND
208/230- OR
460-VOLT
THREE
PHASE
208/230-
VOLT
SINGLE
PHASE
A95241
Step 10—Start-up, Adjustment, and Safety Check
GENERAL
NOTE: Proper polarity must be maintained for 115-v wiring. If
polarity is incorrect, control center fault indicator light will flash
rapidly and furnace will not operate.
The furnace must have a 115-v power supply properly connected
and grounded. Proper polarity must be maintained for correct
operation. Thermostat wire connections at R, W, C, and Y must be
made at the 24-v terminal block on the control board. The gas
service pressure must not exceed 0.5 psig (14-in. wc), but must be
no less than 0.16 psig (4.5-in. wc).
9
Page 10
Before operating the furnace, check each manual reset switch for
continuity. If necessary, press the button to reset the switch.
The blower compartment door must be in place to complete the
115-v circuit to the furnace.
This furnace is equipped with 2 manual reset limit switches in
the gas control area. The switches will open and shut off
power to the gas valve if a flame rollout or an overheating
condition occurs in the gas control area. DO NOT bypass the
switches. Correct inadequate combustion air supply problem
and reset the switches.
SEQUENCE OF OPERATION
Furnace control must be grounded for proper operation or
control will lockout. Control is grounded through green wire
routed to gas valve and burner bracket screw.
Using the schematic diagram shown in Fig. 13, follow the
sequence of operation through the different modes. Read and
follow the wiring diagram very carefully.
NOTE: If there is a power interruption and any thermostat call,
the control will initiate a 90-sec blower only on period before
starting another cycle.
1. Heating mode
When the thermostat "calls for heat," R-W circuit closes. The
furnace control performs a self-check, verifies the pressure
switch contacts are open, and starts the inducer motor.
a. Prepurge period—As the inducer motor comes up to speed,
the pressure switch contacts close to begin a 15-sec
prepurge period.
b. Ignitor warm-up—At the end of the prepurge period, the
ignitor is energized for a 17-sec ignitor warm-up period.
c. Ignition sequence—When the ignitor warm-up period is
completed, the gas valve opens, permitting gas flow to the
burners where it is ignited. After 5 sec, the ignitor is
de-energized and a 2-sec flame-sensing period begins.
d. HUM terminal is energized with the gas valve. See
Accessories in Electrical Connections section.
e. Flame-sensing—When burner flame is sensed, the control
begins the blower on delay period and continues holding
the gas valve open. If burner flame is not sensed, the
control closes the gas valve and repeats the ignition cycle.
NOTE: Ignition sequence will repeat 3 additional times before a
lockout occurs. Lockout automatically resets after 3 hrs, or can be
manually reset by turning 115v off (not at thermostat) for 3 sec
minimum, then on again.
f. Blower on delay—Forty sec after burner flame is proven,
the blower motor is energized on heating speed. Simultaneously, the humidifier and electronic air cleaner terminals
(HUM and Com for humidifier, EAC-1 and EAC-2 for
electronic air cleaner) are energized.
g. Blower off delay—When the thermostat is satisfied, the
circuit between R and W is broken, de-energizing the gas
valve and stopping gas flow to the burners. The blower
motor, and EAC remain energized for 135 sec.
h. Post-purge—The inducer motor remains energized 5 sec
after the burners are extinguished.
2. Cooling mode
When the thermostat "calls for cooling," R-G and R-Y circuits
close. The R-Y circuit starts the outdoor condensing unit and
combined R-Y and R-G circuits start the furnace blower motor
on cooling speed. The EAC-1 terminal is energized with 115v
whenever the blower is operating on cooling speed.
When the thermostat is satisfied, R-G and R-Y circuits are
broken. Furnace blower and EAC continue operating on
cooling speed for an additional 90 sec.
3. Continuous blower mode
NOTE: EAC-1 terminal is energized with 115v whenever blower
is operating.
When the R-G circuit is made, the blower motor operates on
heating speed. During a call for heat, the blower stops,
allowing the furnace heat exchangers to heat up more quickly,
then restarts at the end of the 40-sec blower on delay period.
The blower reverts to continuous operation after the heating
cycle is completed.
When the thermostat "calls for cooling," the blower operates
on cooling speed. When the thermostat is satisfied, the blower
operates an additional 90 sec before reverting back to continuous operation on heating speed.
4. Heat pump mode
When installed with a heat pump, the furnace control auto-
matically changes the timing sequence to avoid long blower
off time during demand defrost cycles. When the W-Y or
W-Y-G thermostat inputs are received at the same time, the
control changes the blower to heating speed or starts the
blower if it was off, and begins a heating cycle. The blower
remains on until the end of the prepurge period, then shuts off
until the end of the ignition warm up and trial for ignition
periods (a total of 24 sec). The blower then comes back on at
heating speed.
When the W input signal disappears, the control begins the
normal inducer post-purge period and the blower changes to
cooling speed after a 1-sec delay. If the W-Y-G signals
disappear at the same time, the blower remains on for the
selected heating blower off delay period and the inducer goes
through its normal post-purge period. If the W-Y inputs
should disappear, leaving the G signal input, the control goes
into continuous blower and the inducer remains on for the
normal post-purge period.
Anytime the control senses false flame, the control locks out
of the heating mode. This occurs because the control cannot
sense the W input due to the false flame signal and, as a result,
sees only the Y input and goes into cooling mode blower off
delay. All other control functions remain in standard format.
NOTE: EAC-1 terminal is energized whenever blower operates.
HUM terminal is only energized when gas valve is energized.
START-UP PROCEDURES
1. Purge gas lines—After all connections have been made, purge
the lines and check for leaks.
Never purge a line into a combustion chamber. Never use
matches, candles, flame or other sources of ignition to check
for gas leakage. Use a soap-and-water solution to check for
gas leaks. Failure to follow this warning could result in fire,
explosion, personal injury, or death.
2. Component test—The furnace control allows all components,
except gas valve, to be run for a short period of time.
3. Blower motor speed selections are for average conditions, see installation instructions for details on
4. Use only copper wire between the disconnect switch and the furnace junction box (JB).
5. This wire must be connected to furnace sheetmetal for control to detect flame.
JUNCTION
UNMARKED TERMINAL
PCB TERMINAL
FACTORY WIRING (115VAC)
FACTORY WIRING (24VAC)
TEST/TWIN COMPONENT TEST & TWIN TERMINAL
TRANTRANSFORMER-115VAC/24VAC
(135 seconds only on some models)
after three hours.
6. Replace only with a 3 amp fuse.
7. Yellow lead not on all motors.
8. Blower-on delay, gas heating 45 seconds, cooling or heat pump 2 seconds.
9. Blower-off delay, gas heating 90, 135, 180 or 225 seconds, cooling or heat pump 90 seconds.
FIELD WIRING (115VAC)
FIELD WIRING (24VAC)
CONDUCTOR ON PCB
models only.
10. Ignition-lockout will occur after four consecutive unsuccessful trials-for-ignition. Control will auto-reset
11. When used auxiliary limit switch (ALS) is on downflow models only. When used FL is on upflow
FIELD WIRING TERMINAL
FIELD GROUND
EQUIPMENT GROUND
FIELD SPLICE
PLUG RECEPTACLE
A95335
12. Some models may have spade quick connect terminals.
→ Fig. 13—Unit Wiring Diagram
(FIELD INSTALLED & SUPPLIED)
CAPCAPACITOR
CPUMICROPROCESSOR AND CIRCUITRY
DSSDRAFT SAFEGUARD SWITCH
EAC-1 ELECTRONIC AIR CLEANER CONNECTION (115 VAC 1.5 AMP MAX.)
EAC-2 ELECTRONIC AIR CLEANER CONNECTION (COMMON)
FLFUSIBLE LINK
FRSFLAME RO LLOUT SW. -MANUAL RESET, SPST-(N.C.)
FSEFLAME PROVING ELECTRODE
FU1FUSE, 3 AMP, AUTOMOTIV E BLADE TYPE, FACTORY INSTALLED
FU2FUSE OR CIRCUIT BREAKER CURRENT INTERR UP T DEVICE
GVGAS VALVE-REDUNDANT OPERATORS
GVR GAS VALVE RELAY, DPST-(N.O.)
HI/LO BLOWER MOTOR SPEED CHANGE RELAY, SPDT
HSIHOT SURFACE IGNITOR (115 VAC )
HSIR HOT SURFACE IGNITOR RELAY, SPST-(N.O.)
HUM 24VAC HUMIDIFIER CONNECTION (.5 AMP. MAX.)
IDMINDUCED DRAFT MOTOR
IDRINDUCED DRAFT RELAY, SPST- (N.O.)
ILKBLOWER ACCESS PANEL INTERLOCK SW I T CH, SPST-(N.O.)
JBJUNCTION BOX
LEDLIGHT-EMITTING DIODE FOR STATUS CODES
LGPS LOW GAS PRESSURE SWITCH, SPST-(N.O.)
LSLIMIT SWITCH, AUTO RESET, SPST(N.C.)
OLAUTO-RESET INTERNAL MOTOR OVERLOAD TEMP. SW.
11
Page 12
This feature helps diagnose a system problem in case of a
component failure. To initiate component test procedure, short
(jumper) the TEST 1/4-in. quick connect terminal on control
board (adjacent to diagnostic light) and the Com terminal on
thermostat connection block for approximately 2 sec. (See Fig.
11.)
NOTE: Component test feature will not operate if any thermostat
signal is present at control center.
Component test sequence is as follows.
a. Momentarily jumper TEST and Com terminals until LED
goes off.
b. LED will display previous fault 4 times.
c. Inducer motor operates for 10 sec, then stops.
d. Hot surface ignitor is energized for 15 sec, then de-
energized.
e. Blower motor operates on cooling speed for 10 sec, then
stops.
f. Blower motor operates on heating speed for 10 sec, then
stops.
3. To operate furnace, follow procedures on operating instruction
label attached to furnace.
4. With furnace operating, set thermostat below room temperature and observe that furnace goes off. Set thermostat above
room temperature and observe that furnace restarts.
ADJUSTMENTS
1. Set gas input rate.
There are 2 methods of adjusting the gas input rate. The
preferred method is by using Table 7 and following instructions in item a. The second method is by clocking the gas
meter and following instructions in item b.
The gas valve regulator has been nominally set at 3.5-in. wc
for natural gas. When adjusting input rate, do not set manifold
pressure above 3.8-in. wc or below 3.2-in. wc.
a. Check gas input rate using Table 7.
(1.) Obtain average yearly heat value for local gas supply.
(2.) Obtain average yearly specific gravity for local gas
supply.
(3.) Verify furnace model. Table 7 can only be used for
model 58RAV Furnaces.
(4.) Check and verify orifice size in furnace. NEVER
ASSUME THE ORIFICE SIZE. ALWAYS CHECK
AND VERIFY.
DO NOT redrill burner orifices. Improper drilling (burrs,
out-of-round holes, etc.) can cause excessive burner noise and
misdirection of burner flames. This can result in flame
impingement of the burners and heat exchangers, causing
failure.
(5.) Find natural gas heat value and specific gravity in
Table 7.
(6.) Follow heat value and specific gravity lines to point of
intersection. Find orifice size and manifold pressure
settings for proper operation at given natural gas
conditions.
EXAMPLE:
Heat value 1070 Btu/cu ft
Specific gravity 0.58
Therefore; Orifice No. 44 *
Manifold pressure 3.6-in. wc
* The furnace is shipped with No. 43 orifices. Therefore, in
this example all main burner orifices must be changed and
the manifold pressure must be adjusted.
(7.) Proceed to item c to adjust manifold pressure.
b. Check gas input rate by clocking gas meter.
(1.) Obtain average yearly heat value for local gas supply.
(2.) Check and verify orifice size in furnace. NEVER
ASSUME THE ORIFICE SIZE. ALWAYS CHECK
AND VERIFY.
(3.) Turn off all other gas appliances and pilots.
(4.) Start furnace and let run for 3 minutes.
(5.) Measure time (in sec) for gas meter to complete 1
revolution.
(6.) Refer to Table 8 for cu ft of gas per hr.
(7.) Multiply gas rate (cu ft/hr) by heating value (Btu/cu
ft).
EXAMPLE:
Btu heating input = Btu/cu ft X cu ft/hr
Heating value of gas = 1070 Btu/cu ft
Time for 1 revolution of 2-cu ft dial = 72 sec
Gas rate = 100 X 1070 = 107,000 Btuh
(8.) Check to make sure that measured gas input does not
exceed gas input on unit rating plate.
(9.) Proceed to item c to adjust manifold pressure.
c. Adjust gas input.
(1.) Remove regulator adjustment seal cap. (See Fig. 14.)
(2.) Turn adjusting screw counterclockwise to decrease
input. Turn screw clockwise to increase input. DO
NOT set manifold pressure less than 3.2-in. wc or
more than 3.8-in. wc for natural gas. Make any major
adjustments by changing main burner orifices.
(3.) When correct input is obtained, replace regulator
adjustment seal cap. Main burner flame should be
clear blue, almost transparent. (See Fig. 15.)
d. High altitude—In the United States, gas input on unit rating
plate is for altitudes up to 2000 ft. Ratings for altitudes over
2000 ft must be 4 percent less for each 1000 ft above sea
level. To obtain the adjusted altitude rating, adjust the
manifold pressure, item c, and replace the main burner
orifices as needed. Refer to NFGC Appendix F, Table F-4
for proper orifice sizing at high altitudes.
e. Canadian installations only—The Canadian ratings are
approved for altitudes up to 2000 ft for natural and propane
gases. High-altitude ratings are from 2000 ft to 4500 ft
above sea level. See Table 9 for nominal burner orifice
size. High-altitude input ratings include a 10 percent
derated as required by Canadian standards.
2. Set temperature rise.
Furnace must operate within range of temperature rise speci-
fied on the unit rating plate. Determine the air temperature rise
as follows.
12
Page 13
Table 7—Model 58RAV Orifice Size and Manifold Pressure for Correct Input Rate*
(Tabulated Data Based on Altitude Up to 2000 ft and 23,000 Btuh Per Burner)
SPECIFIC GRAVITY OF NATURAL GAS
GAS HEAT VALUE
(BTU/CU FT)
860
875
890
905
920
935
950
965
980
995
1010
1025
1035
1055
1070
1085
1100
*For size 135-20 only, deduct 0.1-in. wc from manifold pressure shown in table due to 22,500 Btuh per burner input. If resultant manifold pressure falls below 3.2-in. wc,
change orifice size.
0.560.580.600.620.640.660.680.700.72
Orf
Mnfld
Orf
Mnfld
Orf
Mnfld
Orf
Mnfld
Orf
Mnfld
Orf
Mnfld
Orf
Mnfld
Orf
No.
Press.
40
41
—
—
41
42
—
41
42
—
—
42
—
—
42
42
—
—
42
—
—
—
43
—
—
43
—
—
43
—
—
43
—
—
43
44
—
43
44
—
—
44
—
—
44
—44—
—44—
No.
Press.
3.2
40
41
39
40
41
41
42
41
42
42
42
42
42
43
43
43
43
43
44
43
44
44
3.3
3.6
—
3.2
3.5
—
—
—
—
3.4
3.7
—
—
3.2
3.6
—
—
—
—
3.5
3.4
—
—
—
—
3.3
—
—
—
—
3.2
—
—
—
—
—
—
3.7
—
—
—
—
3.6
—
—
—
—
3.5
—
—
—
—
3.4
—
—
—
—
3.3
3.8
—
—
3.2
3.7
—
—
—
—
3.6
3.5
—
—
3.3
3.7
—
3.2
3.6
—
—
3.5
—
—
3.4
3.3
—
—
3.2
—
—
—
3.7
—
—
3.6
—
—
3.5
—
—
3.4
—
—
3.3
3.8
—
3.2
3.7
—
—
3.6
—
—
3.5
3.4—44—3.54344
3.3—44—3.4—44—3.54344
No.
40
41
39
40
41
—
40
41
—
—
41
42
—
41
42
42
—
—
42
—
—
42
—
—
42
—
—
—
43
—
—
43
—
—
43
—
—
43
—
—
43
44
—
43
44
Press.
3.4
3.7
3.2
3.3
3.6
—
3.2
3.5
—
—
3.4
3.7
—
3.2
3.6
3.5
—
—
3.4
—
—
3.3
—
—
3.2
—
—
—
3.8
—
—
3.6
—
—
3.5
—
—
3.4
—
—
3.3
3.8
—
3.3
3.7
3.2
3.64344
No.
40
41
39
40
41
39
40
41
—
40
41
—
—
41
42
42
—
41
42
—
—
42
—
—
42
—
—
42
—
—
—
43
—
—
43
—
—
43
—
—
43
—
—
43
44
Press.
3.5
3.8
3.3
3.4
3.7
3.2
3.3
3.6
—
3.2
3.5
—
—
3.4
3.7
3.6
—
3.2
3.5
—
—
3.4
—
—
3.3
—
—
3.2
—
—
—
3.6
—
—
3.7
—
—
3.6
—
—
3.5
—
—
3.4
3.8
3.3
3.743—
3.2
3.64344
No.
Press.
40
38
39
40
41
39
40
41
39
40
41
—
40
41
42
42
—
41
42
—
41
42
—
—
42
—
—
42
—
—
42
—
—
—
43
—
—
43
—
—
43
—
—
43
—
No.
Press.
No.
Press.
3.7
40
3.8
—
3.2
38
3.4
3.5
3.8
3.3
3.4
3.7
3.2
3.3
3.6
—
3.2
3.5
3.8
3.7
—
3.4
3.6
—
3.2
3.5
—
—
3.4
—
—
3.3
—
—
3.2
—
—
—
3.8
—
—
3.7
—
—
3.6
—
—
3.5
—
3.4—43—3.5—43—3.6—43—3.7—43—3.8
3.3
3.743—
3.3
39
3.5
40
3.6
38
3.2
39
3.4
40
3.5
41
3.8
39
3.3
40
3.4
41
3.7
39
3.2
40
3.3
41
3.6
—
—
42
3.8
40
3.2
41
3.5
42
3.7
—
—
41
3.3
42
3.6
—
—
41
3.2
42
3.5
—
—
—
—
42
3.4
—
—
—
—
42
3.3
—
—
—
—
42
3.2
—
—
—
—
—
—
43
3.8
—
—
—
—
43
3.7
—
—
—
—
43
3.6
—
—
3.4—43—3.5—43—3.6—43—3.7
38
39
40
38
39
40
—
39
40
41
39
40
41
39
—
40
41
42
40
41
42
—
41
42
—
41
42
—
—
42
—
—
42
—
—
42
—
—
—
43
—
—
43
—
—
3.4
3.6
3.8
3.3
3.5
3.6
—
3.4
3.5
3.8
3.3
3.4
3.7
3.2
—
3.3
3.6
3.8
3.2
3.5
3.7
—
3.3
3.6
—
3.2
3.5
—
—
3.4
—
—
3.3
—
—
3.2
—
—
—
3.8
—
—
3.7
—
No.
37
38
39
—
38
39
40
38
39
40
—
39
40
41
39
39
40
41
—
40
41
42
40
41
42
—
41
42
—
41
42
—
—
42
—
—
42
—
—
42
—
—
—
43
—
Mnfld
Press.
3.2
3.5
3.8
—
3.4
3.6
3.7
3.2
3.5
3.6
—
3.4
3.5
3.8
3.3
3.2
3.4
3.7
—
3.3
3.6
3.8
3.2
3.4
3.7
—
3.3
3.6
—
3.2
3.5
—
—
3.4
—
—
3.3
—
—
3.2
—
—
—
3.8
—
Orf
No.
37
38
—
—
38
39
40
38
39
40
38
39
40
—
39
39
40
41
39
40
41
—
40
41
42
44
41
42
—
41
42
—
41
42
—
—
42
—
—
42
—
—
42
—
—
Mnfld
Press.
3.2
3.6
—
—
3.4
3.7
3.8
3.3
3.6
3.7
3.2
3.5
3.6
—
3.4
3.3
3.5
3.8
3.2
3.4
3.7
—
3.3
3.5
3.8
3.2
3.4
3.7
—
3.3
3.6
—
3.2
3.5
—
—
3.4
—
—
3.3
—
—
3.2
—
—
—
—
a. Place duct thermometers in return and supply ducts as near
furnace as possible. Be sure thermometers do not "see" heat
exchangers so that radiant heat does not affect thermometer
readings. This is particularly important with straight-run
ducts.
b. When thermometer readings stabilize, subtract return-air
temperature from supply-air temperature to determine temperature rise.
c. Adjust air temperature rise by adjusting blower speed.
Increase blower speed to reduce temperature rise. Decrease
blower speed to increase temperature rise.
Disconnect the electrical power before changing the speed
tap. Failure to follow this warning could result in personal
injury.
d. To change blower motor speed selections for heating mode,
remove blower motor lead from control board HEAT
terminal. (See Fig. 11.) Select desired blower motor speed
lead from 1 of the other terminals and relocate it to HEAT
terminal. See Table 10 for lead color identification. Reconnect original lead on SPARE terminal.
Follow this same procedure for proper selection of COOL
speed selection.
13
Page 14
SECONDS
FOR 1
REVOLUTION
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
Table 8—Gas Rate (Cu Ft/Hr)
SIZE OF TEST DIAL
1
cu ft2cu ft5cu ft
360
720
655
600
555
514
480
450
424
400
379
360
343
327
313
300
288
277
267
257
248
240
232
225
218
212
206
200
195
189
185
180
176
172
167
164
160
157
153
150
147
1800
1636
1500
1385
1286
1200
1125
1059
1000
947
900
857
818
783
750
720
692
667
643
621
600
581
563
545
529
514
500
486
474
462
450
439
429
419
409
400
391
383
375
367
327
300
277
257
240
225
212
200
189
180
171
164
157
150
144
138
133
129
124
120
116
113
109
106
103
100
97
95
92
90
88
86
84
82
80
78
76
75
73
SECONDS
FOR 1
REVOLUTION
50
51
52
53
54
55
56
57
58
59
60
62
64
66
68
70
72
74
76
78
80
82
84
86
88
90
92
94
96
98
100
102
104
106
108
110
112
116
120
SIZE OF TEST DIAL
1
cu ft2cu ft5cu ft
72
144
141
138
136
133
131
129
126
124
122
120
116
112
109
106
103
100
97
95
92
90
88
86
84
82
80
78
76
75
74
72
71
69
68
67
65
64
62
60
360
355
346
340
333
327
321
316
310
305
300
290
281
273
265
257
250
243
237
231
225
220
214
209
205
200
196
192
188
184
180
178
173
170
167
164
161
155
150
71
69
68
67
65
64
63
62
61
60
58
56
54
53
51
50
48
47
46
45
44
43
42
41
40
39
38
38
37
36
35
35
34
33
33
32
31
30
BURNER FLAME
BURNER
MANIFOLD
Fig. 15—Burner Flame
Table 9—Canadian Orifice Size
GAS
SEA LEVEL 0-2000
FT
Natural4344
Propane5455
HIGH ALTITUDE
2000-4500 FT
Table 10—Speed Selector
COLORSPEED
BlackHighCOOL
Yellow
(When present)
Medium-HighSPARE
BlueMedium-LowHEAT
RedLowSPARE
WhiteCommonCOM
FACTORY
ATTACHED TO
A89020
CONTROL
KNOB
OFF
INLET
PRESSURE TAP
MANIFOLD
PRESSURE TAP
GAS
PRESSURE
REGULATOR
ADJUSTMENT
A90044
Fig. 14—Redundant Automatic Gas Control Valve
Recheck temperature rise. It must be within limits specified
on unit rating plate. Recommended operation is at midpoint of
rise or above.
3. Set thermostat heat anticipator.
The thermostat heat anticipation must be set to match the amp
draw of the electrical components in the R-W circuit. Accurate
amp draw readings can be obtained at thermostat subbase
terminals R and W. Fig. 16 illustrates an easy method of
obtaining the actual amp draw. The amp reading should be
taken after the blower motor has started. See the thermostat
manufacturer’s instructions for adjusting the heat anticipator
and for varying the heating cycle length.
NOTE: When using an electronic thermostat, set cycle rate for 3
cycles per hr.
CHECK SAFETY CONTROLS
The flame sensor, gas valve, and pressure switch were all checked
in the Start-Up Procedures section as part of normal operation.
1. Check primary limit control.
This control shuts off the combustion control system and
energizes the circulating-air blower motor if the furnace
overheats.
The preferred method of checking the limit control is to
gradually block off the return air after the furnace has been
operating for a period of at least 5 minutes. As soon as the
limit has shut off the burners, the return-air opening should be
unblocked. By using this method to check the limit control, it
can be established that the limit is functioning properly and
operates if there is a motor failure.
2. Check draft safeguard switch.
The purpose of this control is to permit the safe shutdown of
the furnace during certain blocked vent conditions.
a. Disconnect power to furnace and remove vent connector
from furnace outlet collar. Be sure to allow time for vent
pipe to cool down before removing.
b. Restore power to furnace and set room thermostat above
room temperature.
c. After normal start-up, allow furnace to operate for 2
minutes, then block flue outlet 100 percent. Furnace should
cycle off within 2 minutes.
d. Remove blockage and reconnect vent pipe to furnace outlet
collar.
e. Wait 5 minutes and then reset draft safeguard switch.
3. Check pressure switch.
This control proves operation of draft inducer blower.
a. Turn off 115-v power to furnace.
b. Remove control door and disconnect inducer motor lead
wires from wire harness.
A80201
c. Turn on 115-v power to furnace.
d. Set thermostat to "call for heat" and wait 1 minute. When
pressure switch is functioning properly, hot surface ignitor
should NOT glow and control center diagnostic light
flashes a 31 fault. If hot surface ignitor glows when inducer
motor is disconnected, shut down furnace immediately.
Determine reason pressure switch did not function properly
and correct condition.
e. Turn off 115-v power to furnace.
f. Reconnect inducer motor wires, replace control door, and
turn on 115-v power to furnace.
4. Check auxiliary limits (when used).
a. Turn off 115-v power to furnace.
b. Remove blower access door.
c. Disconnect red motor lead at blower speed selector. Mark
terminal for proper re-connection.
d. Replace blower access door.
e. Turn on 115-v power to furnace. Be sure room thermostat
is calling for heat.
f. Allow furnace to operate until auxiliary limit activates, but
DO NOT operate furnace longer than 4 minutes.
g. If furnace operates for 4 minutes, check/replace limit
switch(es).
h. Turn off 115-v power to furnace.
i. Remove blower access door.
j. Reconnect red motor lead, reset switch, and replace door.
k. Turn on 115-v power to furnace.
CHECKLIST
1. Put away tools, instruments, and clean up debris.
2. Verify manual reset switches have continuity.
3. Ensure blower and control access doors are properly installed.
4. Cycle test furnace with room thermostat.
5. Check operation of accessories per manufacturer’s instructions.
6. Review User’s Manual with owner.
7. Leave literature packet near furnace.
15
Page 16
SERVICE TRAINING
Packaged Service Training programs are an excellent way to increase your
knowledge of the equipment discussed in this manual, including:
• Unit Familiarization• Maintenance
• Installation Overview• Operating Sequence
A large selection of product, theory, and skills programs is available, using popular
video-based formats and materials. All include video and/or slides, plus companion
book.
Classroom Service Training plus "hands-on" the products in our labs can mean
increased confidence that really pays dividends in faster troubleshooting, fewer
callbacks. Course descriptions and schedules are in our catalog.
CALL FOR FREE CATALOG 1-800-962-9212
[ ] Packaged Service Training[ ] Classroom Service Training
A94328
Copyright 1995 CARRIER Corp. • 7310 W. Morris St. • Indianapolis, IN 4623158ra10si
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.