Carrier 58DHL User Manual

58DHL
HEATING A COOLING
Downflow/Horizontal Induced-Combustion Furnaces
Installation, Start-Up and Service Instructions
Sizes 055-115 = ~ —
NOTE: Remove the Energy Guide tag from the furnace
when the installation is complete.
NOTE: This is a highly specialized piece of equipment.

INTRODUCTION

Before installing the furnace, refer to “Procedure for Induced-Combustion Furnaces” (packaged with the equip ment) for information concerning combustion, venting, pip ing, and other standard installation practices. Further refer ence is made to the current edition of the National Fuel Gas Code NFPA No. 54, TIA-54-1984-1/ANSI Z223.1-1984, Z223.la-1987 and American Gas Association.
The inducedrcombustion vent system of this furnace is designed to operate at zero or negative pressure at the vent
connector outlet. This furnace, therefore, comphes with the National Fuel Gas Code (NFPA No. 54, TIA-54-1984-1/ ANSI Z223.1-1984, Z223.1a-1987), Part 7.3.4.b. This furnace is also Usted by A.G.A. for use with the type B1 gas vent, as described in the National Fuel Gas Code, Part 7.4.2.
Each furnace is shipped from the factory completely assem bled with multispeed direct-drive blower and wired ready for indoor heating installation. AU sizes featxire a blower con trol center with easy-to-read low-voltage terminal strip to ensure proper connections.

Fig. 1—Downflow

Aæo33
Table 1—Clearances (In Inches)
Sizes DOWNFLOW (In Alcove or Closet) Sides—Single-Wali Vent
Type-B1 Double-Wall Vent Back Top Front*—Single-Wall Vent
Type-B1 Double-Wall Vent
Vent—Single-Wall
Type-BI Double Wall HORIZONTAL (In Alcove) Sidesf Back
Top—Single-Wall Vent
Type-BI Double-Wall Vent Front* Vent—Single-Wall
Type-BI Double-Wall HORIZONTAL (In Closet) Sidest
Back Top—Single-Wall Vent
Type-BI Double-Wall Vent
Front*—Single-Wall Vent
Type-BI Double-Wall Vent
Vent—Single-Wall
Type-BI Double-Wall 1
*Provide a 30-in. service clearance in front of thè furnace, tindicates suppiy or return sides when furnace is in the horizontai posi
tion.
055
18 18
075 thru 115
1 0 0 0 0 1 6 6 3 3 6 1
1 0 0 1 0 0
6 1
1 3 2 2 6 3 3 6
?
iiilil
0
1
The output capacity and any representations of efficiency for this product are based on standard Department of Energy test procedures. The installed operation may veiry,
6 1
0 1
depending on installation, weather, or other factors.
Do not install furnace in a corrosive or contaminated atmosphere. Make sure aU combustion and circulating are requirements hsted in “Procedure for Induced-Com
6
1
bustion Furnaces” are adhered to, in addition to all local codes and ordinances.
Do not use this furnace during construction when adhe
1 3 2 2 6
sives, sealers, and/or new carpets are being installed. If the furnace is required during construction, use clean outside air for combustion and ventilation. Compounds of chlorine and flourine when burned with combustion air form acids which will cause corrosion of the heat
6 1
exchangers and metal vent system. Some of these com pounds are: paneling and dry wall adhesives, paints, thinners, masonry cleaning materials, and many other solvents commonly used in the construction process.
n

Fig. 2—Horizontai

A CAUTION

A88034
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book] 1 I 4 PC 101 Catalog No. 565-807 Printed In U.S.A. Form 58DHL-1SI Pg 1 5-88 Replaces: New
Tab 16a 18a
Table 2—Dimensions (in inches)
Size 055BC 055CC OrSBC
075CC 095CC 095DC 21 115CC
14^,6
14=/i6
1772
V'k M'k 157s
2472
A D
127,6 127,6
157a
157fc
197a
22-'7,6
E
12”/,6
12’7,6
16 4 16 4 16
1972
23 5

Tabie 3—Ratings and Performance*

SIZE
055BC 055CC 075BC 075CC
095CC 095DC 115CC
*The above gas inputs are certified for altitudes to 2000 ft. For elevations above 2000 ft, reduce input 4% for each 1000 ft above sea level. tDetermined by U.S. Government test.
Input Btuh* 67,000 56,000 40—70 67,000 56,000 90,000 75,000
90,000 75,000 114,000 95,000 55—85 114,000 95,000 137,000 115,000
Capacity
Btuht
Temperature
Rise
Range
35—65 0.12 45—75 40—70
. 55—85
45—75 0.20 1937
Heating
External Static
Pressure
0.12 775
0.15 1005 0.5
0.15 1240 0.5
0.20 1248
0.20 1350 0.5
CFM
1080 0.5 1157
Cooling
External Static
Pressure
0.5 850 74 psc 140
0.5 1590 72 PSC 178
0.5
CFM
1225 1553
1929 2010 ’¿ PSC 208
Motor
HP & Type
7a PSC 7a PSC
’¿PSC 163
’¿PSC
Vent Conn
4 4
4 4
Shipping
Weight
(Lbs)
142 160
188
The design of the downflow/horizontal gas-fifed furnace is A.G.A. certified for natural and LP (propane) gas and for installation on noncombustible flooring. The furnace may be installed on combustible flooring when installed with the accessory floor base. This furnace is for installation in alcoves, attics, crawl spaces, basements, closets, or iitUity rooms. The design of this furnace line is not A.G.A. certified for installation in mobile homes, recreation vehicles, or outdoors.
Installation comprises the following:
*1. Inspection
*11. Location, Ventilation, and Air for Combustion
*III. Gas Piping
HOLE IN
FLOOR
3
*IV. Venting

V. Supply-Air Plenum Installation (Downflow)

VI. Attic Installation
VII. Crawl Space Installation
VIII. Filter Arrangement
IX. Sequence of Operation
*To perform these sections (or installation steps), refer to the appropriate sections of “Procedures for Induced-Com
bustion Furnaces” booklet packaged with this unit.
X. Electrical Connections
XI. Startup and Adjustment
XII. Care and Maintenance
For accessory installation details, refer to apphcable instal lation hterature.
V. SUPPLY-AIR PLENUM INSTALLATION (DOWNFLOW) A. Installation on a concrete slab
1. See Fig. 3 for dimensions and location of supply-air
opening in furnace bottom.
2. Construct hole in floor per dimensions in Fig. 4 and
Table 4.
3. Place plenum and furnace as shown in Fig. 5.
B. installation on a combustible floor
1. Read Installation Instructions packaged with combus tible floor base.
A73382
Fig. 4—Floor Opening for Concrete Slab
Table 4—Opening Dimensions
Furnace Casing
Width
147,6
17’¿
21
24’¿
♦These dimensions apply when a Model 28RC or 28RD Evaporator Coil
casing is to be installed.
A
13’¿ 19%
167,6
19’¿ 19%
237,6
Heat-Only
19%
19%
B
Heat/Cool*
197,6
197,6 197,6 197,6
Fig. 5—Furnace on a Concrete Slab
The furnace can be installed horizontally on either the LH or RH side. A typical attic installation is shown in Fig. 8.
NOTE; The National Fuel Gas Code requires the use of a
t5q>e B1 vent in an attic or concealed space.
A. Construct a working platform.
1. Place working platform in location where all required
furnace clearances are obtainable. See Table 1.
2. Use materials in platform that will support installer
and service persons.
3. Secure platform to building joists.
Fig. 7—Furnace, Plenum, and
Base Installed on a Combustible Floor
2.
Cut and frame hole in floor per dimensions in Table 1 of Installation Instructions packaged with combustible floor base. If this requires cutting of a floor joist, tie ends of cut joist into adjacent joists so that proper floor support wül be maintained.
3.
Assemble and install combustible floor base per instructions packaged with base.
4. When completed, combustible floor base, plenum, and furnace (or coil casing when used) should be installed as shown in Fig. 7.

VI. HORIZONTAL ATTIC INSTALLATION

A WARNING

Do not install the furnace on its back. Fusible link oper ation will be adversely affected. Never connect return­air ducts to the sides or back of the furnace. A failure to adhere to this warning can cause a fire, physical injury,
or death.
LINE CONTACT ONLY PERMISSIBLE BETWEEN LINES FORMED BY INTERSECTIONS OF THE TOP AND TWO SIDES OF THE FURNACE JACKET AND BUILDING JOISTS. STUDS OR FRAMING.'

B. Install furnace

1. Position furnace in desired location.
2. Connect gas supply pipe. See Fig. 8 for typical piping entry. It is important to install a sediment trap in the gas pipe riser.
3. Connect supply- and return-air ducts.
a. Install field-supplied duct flanges as shown in
Fig. 9.
b. Using appropriate fasteners for type of supply-air
duct being used, connect duct to furnace.
c. Install field-supphed filter retainers as indicated in
Fig. 10 and Table 5 before coimecting return-air duct to furnace.
NOTE: For ease of servicing, a return-air filter can be
installed in a common return-air grille. The air velocity rat ing must not exceed 300 ft/min for disposable filters. The air velocity through permanent-type filters shall not exceed the mEuiufacturer’s recommendation.
d. Using appropriate fasteners for type of duct being
used, connect return-air duct to furnace.
4. Install 24-x24-in. sheet metal shield on platform in
front of louvered control panel, as shown in Fig. 8.

VII. CRAWL SPACE INSTALLATION

The furnace can be installed horizontally with either the LH
or RH side up. In a crawl space, the furnace can either be
hung from the floor joist or installed on suitable blocks or pad. The furnace can be suspended from each corner by
SEDIMENT TRAP
Fig. 8—Typical Attic installation
Loading...
+ 7 hidden pages