NOTE: Remove the Energy Guide tag from the furnace
when the installation is complete.
NOTE: This is a highly specialized piece of equipment.
Before beginning the installation, READ THESE
INSTRUCTIONS CAREFULLY AND COMPLETELY.
INTRODUCTION
Before installing the furnace, refer to “Procedure for
Induced-Combustion Furnaces” (packaged with the equip
ment) for information concerning combustion, venting, pip
ing, and other standard installation practices. Further refer
ence is made to the current edition of the National Fuel Gas
Code NFPA No. 54, TIA-54-1984-1/ANSI Z223.1-1984,
Z223.la-1987 and American Gas Association.
The inducedrcombustion vent system of this furnace is
designed to operate at zero or negative pressure at the vent
connector outlet. This furnace, therefore, comphes with the
National Fuel Gas Code (NFPA No. 54, TIA-54-1984-1/
ANSI Z223.1-1984, Z223.1a-1987), Part 7.3.4.b. This furnace
is also Usted by A.G.A. for use with the type B1 gas vent, as
described in the National Fuel Gas Code, Part 7.4.2.
Each furnace is shipped from the factory completely assem
bled with multispeed direct-drive blower and wired ready for
indoor heating installation. AU sizes featxire a blower con
trol center with easy-to-read low-voltage terminal strip to
ensure proper connections.
Fig. 1—Downflow
Aæo33
Table 1—Clearances (In Inches)
Sizes
DOWNFLOW (In Alcove or Closet)
Sides—Single-Wali Vent
Type-B1 Double-Wall Vent
Back
Top
Front*—Single-Wall Vent
Type-B1 Double-Wall Vent
Vent—Single-Wall
Type-BI Double Wall
HORIZONTAL (In Alcove)
Sidesf
Back
Top—Single-Wall Vent
Type-BI Double-Wall Vent
Front*
Vent—Single-Wall
Type-BI Double-Wall
HORIZONTAL (In Closet)
Sidest
Back
Top—Single-Wall Vent
Type-BI Double-Wall Vent
Front*—Single-Wall Vent
Type-BI Double-Wall Vent
Vent—Single-Wall
Type-BI Double-Wall1
*Provide a 30-in. service clearance in front of thè furnace,
tindicates suppiy or return sides when furnace is in the horizontai posi
tion.
055
1818
075 thru 115
10
0
00
1
66
33
6
1
10
0
1
00
6
1
1
3
2
2
6
33
6
?
iiilil
0
1
The output capacity and any representations of efficiency
for this product are based on standard Department of
Energy test procedures. The installed operation may veiry,
6
1
0
1
depending on installation, weather, or other factors.
Do not install furnace in a corrosive or contaminated
atmosphere. Make sure aU combustion and circulating
are requirements hsted in “Procedure for Induced-Com
6
1
bustion Furnaces” are adhered to, in addition to all
local codes and ordinances.
Do not use this furnace during construction when adhe
1
3
2
2
6
sives, sealers, and/or new carpets are being installed. If
the furnace is required during construction, use clean
outside air for combustion and ventilation. Compounds
of chlorine and flourine when burned with combustion
air form acids which will cause corrosion of the heat
6
1
exchangers and metal vent system. Some of these com
pounds are: paneling and dry wall adhesives, paints,
thinners, masonry cleaning materials, and many other
solvents commonly used in the construction process.
n
Fig. 2—Horizontai
A CAUTION
A88034
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book] 1 I 4 PC 101 Catalog No. 565-807 Printed In U.S.A. Form 58DHL-1SI Pg 1 5-88 Replaces: New
Tab 16a 18a
Table 2—Dimensions (in inches)
Size
055BC
055CC
OrSBC
075CC
095CC
095DC21
115CC
14^,6
14=/i6
1772
V'k
M'k157s
2472
AD
127,6
127,6
157a
157fc
197a
22-'7,6
E
12”/,6
12’7,6
164
164
16
1972
235
Tabie 3—Ratings and Performance*
SIZE
055BC
055CC
075BC
075CC
095CC
095DC
115CC
*The above gas inputs are certified for altitudes to 2000 ft. For elevations above 2000 ft, reduce input 4% for each 1000 ft above sea level.
tDetermined by U.S. Government test.
The design of the downflow/horizontal gas-fifed furnace is
A.G.A. certified for natural and LP (propane) gas and for
installation on noncombustible flooring. The furnace may be
installed on combustible flooring when installed with the
accessory floor base. This furnace is for installation in
alcoves, attics, crawl spaces, basements, closets, or iitUity
rooms. The design of this furnace line is not A.G.A. certified
for installation in mobile homes, recreation vehicles, or
outdoors.
Installation comprises the following:
*1. Inspection
*11. Location, Ventilation, and Air for Combustion
*III. Gas Piping
HOLE IN
FLOOR
3
*IV. Venting
V. Supply-Air Plenum Installation (Downflow)
VI. Attic Installation
VII. Crawl Space Installation
VIII. Filter Arrangement
IX. Sequence of Operation
*To perform these sections (or installation steps), refer to
the appropriate sections of “Procedures for Induced-Com
bustion Furnaces” booklet packaged with this unit.
X. Electrical Connections
XI. Startup and Adjustment
XII. Care and Maintenance
For accessory installation details, refer to apphcable instal
lation hterature.
V. SUPPLY-AIR PLENUM INSTALLATION (DOWNFLOW)
A. Installation on a concrete slab
1. See Fig. 3 for dimensions and location of supply-air
opening in furnace bottom.
2. Construct hole in floor per dimensions in Fig. 4 and
Table 4.
3. Place plenum and furnace as shown in Fig. 5.
B. installation on a combustible floor
1. Read Installation Instructions packaged with combus
tible floor base.
A73382
Fig. 4—Floor Opening for Concrete Slab
Table 4—Opening Dimensions
Furnace Casing
Width
147,6
17’¿
21
24’¿
♦These dimensions apply when a Model 28RC or 28RD Evaporator Coil
casing is to be installed.
A
13’¿19%
167,6
19’¿19%
237,6
Heat-Only
19%
19%
B
Heat/Cool*
197,6
197,6
197,6
197,6
Fig. 5—Furnace on a Concrete Slab
The furnace can be installed horizontally on either the LH
or RH side. A typical attic installation is shown in Fig. 8.
NOTE; The National Fuel Gas Code requires the use of a
t5q>e B1 vent in an attic or concealed space.
A. Construct a working platform.
1. Place working platform in location where all required
furnace clearances are obtainable. See Table 1.
2. Use materials in platform that will support installer
and service persons.
3. Secure platform to building joists.
Fig. 7—Furnace, Plenum, and
Base Installed on a Combustible Floor
2.
Cut and frame hole in floor per dimensions in Table 1 of
Installation Instructions packaged with combustible
floor base. If this requires cutting of a floor joist, tie
ends of cut joist into adjacent joists so that proper
floor support wül be maintained.
3.
Assemble and install combustible floor base per
instructions packaged with base.
4. When completed, combustible floor base, plenum, and
furnace (or coil casing when used) should be installed as
shown in Fig. 7.
VI. HORIZONTAL ATTIC INSTALLATION
A WARNING
Do not install the furnace on its back. Fusible link oper
ation will be adversely affected. Never connect returnair ducts to the sides or back of the furnace. A failure to
adhere to this warning can cause a fire, physical injury,
or death.
LINE CONTACT ONLY PERMISSIBLE BETWEEN
LINES FORMED BY INTERSECTIONS OF
THE TOP AND TWO SIDES OF THE FURNACE
JACKET AND BUILDING JOISTS.
STUDS OR FRAMING.'
B. Install furnace
1. Position furnace in desired location.
2. Connect gas supply pipe. See Fig. 8 for typical piping
entry. It is important to install a sediment trap in the
gas pipe riser.
3. Connect supply- and return-air ducts.
a. Install field-supplied duct flanges as shown in
Fig. 9.
b. Using appropriate fasteners for type of supply-air
duct being used, connect duct to furnace.
c. Install field-supphed filter retainers as indicated in
Fig. 10 and Table 5 before coimecting return-air
duct to furnace.
NOTE: For ease of servicing, a return-air filter can be
installed in a common return-air grille. The air velocity rat
ing must not exceed 300 ft/min for disposable filters. The air
velocity through permanent-type filters shall not exceed the
mEuiufacturer’s recommendation.
d. Using appropriate fasteners for type of duct being
used, connect return-air duct to furnace.
4. Install 24-x24-in. sheet metal shield on platform in
front of louvered control panel, as shown in Fig. 8.
VII. CRAWL SPACE INSTALLATION
The furnace can be installed horizontally with either the LH
or RH side up. In a crawl space, the furnace can either be
hung from the floor joist or installed on suitable blocks or
pad. The furnace can be suspended from each corner by
SEDIMENT TRAP
Fig. 8—Typical Attic installation
Loading...
+ 7 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.