Carrier 58DH User Manual

5 (1)
Carrier Corporation • Syracuse. N.Y. 13221
Downflow/Horizontal Induced-Draft
Gas Furnace
Before starting installation of this furnace, read these instructions carefully and completely. After installation is complete, remove the Energy Guide tag from the furnace. Also read the Procedures for Induced-Draft Gas-Fired Furnaces (packaged with furnace) for important information concerning combustion, venting, piping and other standard installation practices. Further reference can be made to the current edition of the American National Standard Z223.1 National Fuel Gas Code.
The induced-draft vent system of this furnace is designed to operate at zero or negative pressure at the vent connector outlet. This furnace, therefore, complies with the National Fuel Gas Code (NFPA 54-1980 or ANSI Z223.1-1980), Part 7.14.3.b. This furnace is also listed by AGA for use with the type B1 gas vent, as described in the National Fuel Gas Code, Part 7.3.2.
Each furnace is shipped from the factory com pletely assembled with multispeed direct-drive blower, and wired ready for indoor heating installa tion. All sizes feature a blower control center with easy-to-read low-voltage terminal strip to ensure proper connections.
The output capacity and any representations of efficiency for this product are based on standard Department of Energy test procedures. The installed operation may vary, depending on installation, weather and other factors.
EPFICIENCY
RATING
CERTIFIED
a
Fig. 1 — Furnace in Downflow Position
ama
( \l NON Ddik'I II Mall liiinaCL
^l^.c III i.iiiilaminali.d atmnMilu n. Xdlicu lo.ill combustion and ciiculatmg air requirements listed in Procedures foi Induced-Dratt (ias­I ii..d liiiiiai.is ()h'^eI\l. all loi.al Lodes and
1 1 1
a >.ono
Fig. 2 — Furnace in Horizontal Position
The design of the downflow/horizontal (Fig. 1 and 2) gas-fired furnace is AGA certified for in stallation on combustible flooring (with optional
floor base), in alcoves, attics, crawl spaces, base-
Carrier Corporation 1984 Form 58DH-3SI
ments, closets or utility rooms. The design of this furnace line is not AGA certified for installation in mobile homes, recreation vehicles or outdoors.
-H THERMOSTAT „„
S
WIRE ENTRY 13..
-2l
o
.. f
_ _
-4"
llll
j
1" 7“
“'2
S POWER
ENTRY
F"
H
1
■ r
_ _
Ì
l^DIA KO. RH.GAS
ENTRY
M
► ---i"
=^ORI
BOLTS (BOTH SIDES)
Fig. 3 — Dimensional Drawing (in.)
Installation Procedures
Page
1
**
*
* *
SIDESt
1
0 0
Iti lit
nt nt
ut
BACK
0
0 18 0 18
3 6 3 3
0 18
Horizontal Attic Installation...................................4
Crawl Space Installation
Filter Arrangement ............................................... 5
Electrical Connections Sequence of Operation Start-Up and Adjustment
Care and Maintenance ...........................................8
*Provide a 30-in. service clearance in front of
FRONT VENT
6»*
3»*
1
6 1
6 1
1
6
the furnace.
flndicates supply or return sides \A/hen furnace
is in the horizontal position.
íFor installation on non-combustiblefloorsonly.
For installation on combustible flooring only when installed on special base (Part No. 58DS900041).
**Alcove installations require 18-in. front
clearance.
ttLine contact permissible only between lines
formed by intersections of the top and 2 sides of the furnace jacket, and building joists, studs or framing.
ifClearance shown is for the outlet side. The inlet
side must maintain 6-in. clearance from flue to combustible materials with single-wall vent.
Inspection
........................................................
Location, Ventilation and Air for
Combustion
Gas Piping
.....................................................
...........................................................
Venting ................................................................ *
Supply-Air Plenum Installation
(downflow) ...................................................... 3
‘Refer to appropriate sections of ProcSdures for Induced-Draft Gas-Fired Furnaces booklet packed with this furnace.
Table 1 — Clearances (in.)^
FURNACE DOWNFLOW (In Alcove or Closet)|
Single-Wall Vent 1
Type B1 Double-Wall Vent
HORIZONTAL (In Alcove)ft
Single-Wall Vent 1
Type B1 Double-Wall Vent 0
HORIZONTAL (In Closet)
Single-Wall Vent 2 Type B1 Double-Wall Vent 2
HORIZONTAL (Attic or Unoccupied Spaces)
Type B1 or Type L Double-Wall Vent
TOP
1
.......................................
.........................................
.........................................
......................................
Page
5
5 V
8
Table 2 — Dimensions (in.)
Furnace
Size 035,040 055,060 070,080 090,1 OO(CC) 17-1/2 090,1 OO(DC) 21 110,120 24-1 /2
A
14-3/16 14-3/16
17-1/2
B
12-9/16 12-9/16 12-11/16 4 15-7/8 16 15-7/8 16i 4 19-3/8 19-1/2 4
22-13/16 23 5
C
12-11/16 4
Vent Diam
NOI I \Mn.i' l)4().i)SS ,|iul iibli size )m-
n.iccN .ih. iiiM.iILd in d hoii/iMiul poMiion on conibiixliblc ni,iîi.iial 11 IS iictcss.ii\ lo i.iisciIil
I LI I IKK I. OIK in lo ohi.iin icqiiiicd (<-in \Liiipipc
lIc.LI.1IKl tOI
.1
Mllglc V^dll Lent
The Carrier induced-draft gas furnace is designed
4
to accept a Carrier electronic air cleaner and humidifier.
For accessory installation details, refer to appli
cable installation literature.
Table 3 — Ratings and Performance*
FURNACE
SIZE
OJS 100CC
040-100CC 48,000 38,000
055-1OOCC ; 6.1,UCiO beo-'iooc'c i /1000 070-1 OOCC f 86,OCiO 71 000
080-1 OOCC 95,000 77,000
OiJO loncr
1 100 1 OOCC
OOlllOODC 107,000
100-100DC 119,000 ^ iio-ii)ocf;
120-1 OOCC 143,000 117,000
. ' I r. Models meet or exceed California low NOx requirements.
PSC — Permanent Split Capacitor *Ratings are certified for altitudes to 2000feet. For elevations above 2000ft, reduce ratings 4% for each 1000ft above sea level.
tOetermined by U.S. Government Standard test procedures using outdoor combustion air method.
INPUT
(Btuh)
43,000
107,000 119,000 98,000
)bo"'
CAPACITY
(Btuht)
3b,000
52,000
57,000 \ 45-75
88,000 ¡ 55-85
88,000 50 80
97,000
106,000
TEMP
RISE
RANGE (F)
20- 50
25-55 .12
•10 7(J 012
40-70 015 45-75 0.15
60-90 _!20 I 1348
3-85 40 '7Ó 50-80
HEATING COOLING
Ext Static
Pressure
(in. wg)
0 12
0 12
0.20 0 2n 0 20 193/
0.20" 1937
Cfm
1060 0 50
1060 0.50 1080 1080 1240 0 50 ' 1553 1240
0 20 ! 1348 0 50
13i)0 1350 0.50 1929 1/2PSC 188
Ext Static
Pressure
(in. wg)
0.50
0.50
0.50 1553
0.50 1590 1 2 PSC 0 50
0 50 2010
0.50
Table 4 — Opening Dimensions
MOTOR
Cfm
1 171 11/1 1 /3 PSC 1157 1 3PSC 1157 1 3PSC
1590 1 2 PSC
1929 ! 1 2PSC 188
2010 1/2PSC 208
HP & TYPE
1 '3PSC
1 2 PSC
1/2PSC
1 2PsSC 208
APPROX
SHIP.
WT (lb)
132 132 142 142 163
16.1 178 178
(in.)
Fig. 4 — Floor Opening
for Concrete Slab
Fig. 5 — Furnace on a Concrete
Slab
INSTALLATION
Supply-Air Plenum (Downflow)
INSTALLATION ON CONCRETE SLAB
1. See Fig. 3 for dimensions and location of supply­air opening in furnace bottom.
2. Construct hole in floor. See Fig. 4 and Table 4.
3. Place plenum and furnace. See Fig. 5. INSTALLATION ON COMBUSTIBLE FLOOR
1. Read installation instructions packaged with accessory combustible floor base.
2. Cut and frame hole in floor. See Table 1 of in stallation instructions packaged with combus
tible floor base. If this requires cutting a floor
Furnace
Size
035—060
070—lOO(CC) 090—100(00 110—120 23-7/16
13-1/8
16-7/16
19-7/8
A
B
Heat-Only
19-5/8
joist, tie ends of cut joist into adjacent joists for
proper floor support.
3. Assemble and install combustible floor base per instructions packaged with base.
4. When completed, install combustible floor base, plenum, and furnace (or coil casing when used). See Fig. 7.
Fig. 6 — Accessory Combustible Floor Base
Fig. 7 — Furnace, Plenum, and
Base Installed on Combustible Floor
Loading...
+ 7 hidden pages