Carrier 58CTA070-08, 58CTA045-08, 58CTA045-12, 58CTA070-12, 58CTA070-16 Product Data

...
58CTA/C TX P E R F O R M A N C E ™ 8 0 T W O --- S T A G E 4 --- W AY MUL TIPOISE INDUCED---COMBUSTION GAS FURNACE Input Capacities: 45,000 thru 155,000 Btuh Series 140
Product Data
the home by automatically adjusting high and low heat times to maximize comfort. The 58CTA/CTX furnaces are approved for use with natural or propane gas, and the 58CTX is approved for use in Low NOx Air Quality Management Districts.
STANDARD FEATURES
S ComfortHeatt Technology Intelligent microprocessor
control
S Two--stage heating with single-stage thermostat with
patented Adaptive Control Technology
S Very low operating sound through low--stage operation and
QuieTecht system
S SmartEvapt--Humidity control when using a
Thermidistatt control
S Comfort Fant adjustable constant fan speed from the
Performance
A10249
The 58CTA/CTX Two-Stage, 4-way Multipoise Gas Furnaces offer unmatched comfort in their class with ComfortHeatt technology in an 80% AFUE gas furnace. You get the benefits of a ComfortHeatt technology furnace: reduced drafts, reduced sound levels, longer cycles, less temperature swings between cycles, and less temperature differences between rooms. Its exclusive, intelligent microprocessor control adapts to the heating needs of
thermostat
S Microprocessor based control center
Enhanced diagnostics with LED and reflective sight glass Stores fault codes during power outages Adjustable heating air temperature rise Adjustable cooling airflow
S 4-way Multipoise furnace, 13 vent applications S Compact design -- only 33-1/3 in. (847 mm)tall S Power Heatt Igniter S Draft Safeguard switch to ensure proper furnace venting S Insulated blower compartment S Inner door for tighter sealing S Certified to leak 2 percent or less of its nominal air
conditioning CFM delivered when pressurized to 1--In. Water Gauge with all present air inlets, air outlets, and condensate drain port(s) sealed.
S HYBRID HEATr Dual Fuel System compatible S All models are Chimney Friendly when used with accessory
vent kit
S Twinning in Upflow, Downflow and Horizontal S Residential installations eligible for consumer financing
through the Retail Credit Program
MODEL NUMBER NOMENCLATURE
58CTA 045 100 08
58CTA Two-Stage 4-Way Multipoise Nominal Cooling Size
58CTX Low NOx version (Airflow at .5 e.s.p.)
Input Capacity 120 20---2000 CFM
045---44,000 Btuh 110---110,000 Btuh 130 22---2200 CFM
070---66,000 Btuh 135---132,000 Btuh 140
090---88,000 Btuh 155---154,000 Btuh Series Number
58CTA/CTX
FURNACE COMPONENTS
(400 CFM per 12,000 Btuh) 08---800 CFf7
12---1200 CFM 100 14---1400 CFM 110 16---1600 CFM
A02169
HEAT EXCHANGER
CONTROL BOARD
2
A02238
A02170
INDUCER BLOWER
FURNACE COMPONENTS
INDUCER MOTOR
ASSEMBLY
VENT ELBOW
PRESSURE
SWITCHES
FLUE COLLECTOR
BOX
GAS VALVE
MANUAL RESET
LIMIT SWITCHES
HOT SURFACE
IGNITOR
BLOWER DOOR
SAFETY SWITCH
FURNACE CONTROL
BOARD
MAIN LIMIT SWITCH (BEHIND GAS VALVE)
BLOCKED VENT SWITCH
FLAME SENSOR
GAS MANIFOLD
58CTA/CTX
GAS BURNER
BLOWER AND MOTOR
CAPACITOR/ POWER CHOKE
A10313
NOTE: The 58CTA/CTX Furnaces are factory shipped for use with natural gas. These furnaces can be field-converted for propane gas with a factory-authorized and listed accessory conversion kit.
3
CARRIER ACCESSORIES
CONTROLS:
THERMOSTATS
AND ZONING
Available in programmable and non-programmable models, Carrier thermostats maintain a constant temperature level in the home.
For the ultimate in home comfort, Carrier’s 2, 4, and 8-zone systems allow temperature control of
58CTA/CTX
individual “zones” of the home. This is accomplished through a series of electronic dampers and remote room sensors. The 4-zone system is shown.
A97432
C04008
MECHANICAL
OR ELECTRONIC
AIR CLEANER
Cleans the air of smoke, dirt, and many pollens commonly found. Saves decorating and cleaning expenses by keeping carpets, furniture, and drapes cleaner.
Electronic air cleaner is shown.
A01484
MODEL HUMCCLFP
HUMIDIFIER
By adding moisture to winter-dry air, a Carrier humidifier can often improve comfort and keep furniture, rugs, and draperies in better condition. Moisturizing household air also helps to retain normal body heat and provides comfort at lower temperatures.
Accessories
ELECTRONIC AIR CLEANER (EAC) Model EACB
MECHANICAL AIR CLEANER Models EZXCAB, FILCAB
HUMIDIFIER Model HUM
HEAT RECOVERY VENTILATOR Model HRV
ENERGY RECOVERY VENTILATOR Model ERV
For u s e w i t h 1 --- spe e d A i r C o n d i t i o n e r --- deg. F / C , A u t o C h a n g e over --- TP --- N A C, T C --- N A C
T H E R M OSTA T --­NON---PROGRAMMABLE
T H E R M OSTA T --­PROGRAMMABLE
ZONING CONTROL
* Model HP and 2S thermostat must be field converted to air conditioner operation. † Thermidistat Control can be configured for multiple use and staging, it mu st be configured for each specific application.
For u s e w i t h 1 --- spe e d H e a t P u m p --- d e g . F / C , A u t o C h a n g e o v e r --- T P --- N H P , T C --- N H P *
For u s e w i t h 2 --- spe e d A i r C o n d i t i o n e r --- deg. F / C , A u t o C h a n g e over --- TP --- N R H*
For use with multi---use / stage configurations --- deg. F/C, Auto Changeover/Temperature and Humidity control
--- T P --- P R H†
For u s e w i t h 1 --- spe e d A i r C o n d i t i o n e r --- deg. F / C , A u t o C h a n g e over , 7 --- D a y P r o g r ammabl e --- TP --- PA C
For u s e w i t h 1 --- spe e d H e a t P u m p --- d e g . F / C , A u t o C h a n g e o v e r, 7 --- D a y P rogr a m m a b l e --- T P --- P H P *
For u s e w i t h 2 --- spe e d A i r c o n d i t i o n e r --- deg. F / C , A u t o C h a n g eover , 7 --- D a y P r o g rammabl e --- T P --- P R H*
For u s e w i t h 1 --- spe e d A i r C o n d i t i o n e r --- deg. F / C , 5 --- 2 D a y P r o g rammabl e --- T P --- PA C
For u s e w i t h m u l t i --- s t a g e a p pli c a t i o n s --- d e g . F / C , A u t o C h a n g e over , 7 --- D a y P r o g r ammabl e --- T C --- P R H†
For m u l t i --- u s e / s t a g e c onfig u r a t i o n s --- d e g. F / C , A u t o C h a n geove r, 7 --- D a y P r o g rammab l e / Te m p e r ature a n d H u m i dit y C o n t r o l --- T P --- P R H †
Comfort™ Series 3-Zone Kit --- ZONECC3ZAC01, ZONECC3ZHP01
2 Performance™ Series ComfortZone™ II Zoning/Temperature and Humidity Control --- ZONECC2KIT01--- B
4 Performance™ Series ComfortZone™ II Zoning/Temperature and Humidity Control --- ZONECC4KIT01--- B
8 Performance™ Series ComfortZone™ II Zoning/Temperature and Humidity Control --- ZONECC8KIT01--- B
4
CARRIER ACCESSORIES
58CTA/CTX DESCRIPTION PAR T NO. 045-08045-12070-08070-12070-16090-14090-16090-20110-12110-16110-22135-16135-22155-
FILCABCC0016 X X X X X X X
Media Filter Cabinet
Cartridge Media Fi lte r
EZ Flex Media Filter with En d Caps
Replacement EZ Flex Filter Media
External Bottom Return Filter Rack
External Side Return Filter Rack KGA FR0801SRE X X X X X X X X X X X X X X
Unframed Filter 3/4-in. (19 mm)
Flue Exte ns ion KGAFE0112UPH X X X X X X X X X X X X X X
T w inning Kit KGATW0601HSI X X X X X X X X X X X X X X
Combustible Floor Base KGASB0201ALL X X X X X X X X X X X X X X
Downflow Vent Guard KGBVG0101DFG X X X X X X X X X X X X X X
Vent Extension Kit KGAVE0101DNH X X X X X X X X X X X X X X
Chimney Adapter Kit
Natural-to-Propane Conversion Kit* KGANP4601ALL X X X X X X X X X X X X X X
Propane-to-Natural Convers ion Kit KGAPN3901ALL X X X X X X X X X X X X X X
Label Kit KGALB0101KIT X X X X X X X X X X X X X X
Gas Orifice Kit (Qty 50)
* Fac t o ry- aut ho rized and field installed. Fuel conversi o n kits are CSA (formerly AGA/CGA) recognized. † Suitable for Side Return Filter Rack X = Accessory S=Standard
FILCABCC0020 X X X X X
FILCABCC0024 X X
FILCCCAR0016 X X X X X X X
FILCCCAR0020 X X X X X
FILCCCAR0024 X X
EXPXXUNV0016 X X X X X X X
EXPXXUNV0020 X X X X X
EXPXXUNV0024 X X
EXPXXFIL0016 X X X X X X X
EXPXXFIL0020 X X X X X
EXPXXFIL0024 X X
KGAFR0401B14 X X X X
KGAFR0501B17 X X X
KGAFR0601B21 X X X X X
KGAFR0701B24 X X
KGAWF1301UFR† X X X X X X X
KGAWF1401UFR X X X X X
KGAWF1501UFR X X
KGAWF1306UFR† X X X X X X X
KGAWF1406UFR X X X X X
KGAWF1506UFR X X
KGACA02014FC X X X X X X X X X X X
KGACA02015FC X X X
KGAHA0150N42
KGAHA0250N43
(factory supplied)
KGAHA0350N44
KGAHA0450N45
KGAHA0550N46
KGAHA1550N47
KGAHA1650N48
KGAHA0650P54
KGAHA0750P55
KGAHA0850P56
KGAHA5750125
KGAHA5750130
See Installatio n Instructi o ns for model, altitude, and heat value usages
20
58CTA/CTX
5
PHYSICAL DATA
045 070 090
UNIT SIZE
OUTPUT CAPACITY BTUH* (Nonweatherized ICS) †
INPUT BTUH*
AFUE † * Nonweatherized ICS 80.0 80.0 80.0 80.0 80.0 80.0 80.0 80.0
SHIPPING WEIGHT --- LB (KG) 104 (47) 107 (49) 111 (50) 115 (52) 126 (57) 127 (58) 140 (64) 146 (66)
CERTIFIED TEMP RISE RANGE --- ° F (° C)
CERTIFIED EXT STATIC PRESSURE
58CTA/CTX
AIRFLOW CFM‡
LIMIT CONTROL SPST
HEATING BLOWER CONTROL Solid-State Time Operation
BURNERS (Monoport) 2 2 3 3 3 4 4 4
GAS CONNECTION SIZE 1 /2 --- i n . N P T
GAS VALVE (Redundant) Manufacturer White-Rodgers
Minimum Inlet Pressure (In. W.C.) 4.5 (Natural Gas)
Maximum Inlet Pressure (In. W.C.) 13.6 (Natural Gas)
IGNITION DEVICE Hot S urface
* Gas input ratings are certified for elevations to 2000 ft. (610 M). For elevations above 2000 ft. (610 M), reduce r a tings 4 percent for each 1000 ft. (305M)
above sea level. Refer to National Fuel Gas Code NFPA 54/ANSI Z223.1 ---2009 Table F.4 or furn a ce Installation Instructions.
† Capacity in accordance with U.S. Government DOE test procedures.
‡ Airflow shown is for bottom only return ---air supply. For air delivery above 1800 CFM, see Air Delivery Table for other options. A filter is required for each
return-air supply.
ICS — Isolated Combustion System
All 58CTA; 58CTX
Upflow
All 58CTX Downflow/
Horizontal
All 58CTA; 58CTX
Upflow
All 58CTX Downflow/
Horizontal
Heating 0.10 0.10 0.12 0.12 0.12 0.15 0.15 0.15
Cooling 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50
Heating H ig h/Low 820/725 1030/860 790/685 885/695 1570/1045 1375/1195 1265/1030 1580/1325
Cooling 895 1175 955 1240 1605 1385 1755 2005
High 35,000 36,000 54,000 54,000 53,000 71,000 71,000 71,000
Low 23,000 23,000 36,000 36,000 35,000 47,000 47,000 47,000
High 34,000 34,000 51,000 51,000 51,000 68,000 68,000 68,000
Low 23,000 23,000 36,000 36,000 35,000 47,000 47,000 47,000
High 44,000 44,000 66,000 66,000 66,000 88,000 88,000 88,000
Low 29,000 29,000 43,500 43,500 43,500 58,000 58,000 58,000
HIgh 42,000 42,000 63,000 63,000 63,000 84,000 84,000 84,000
Low 29,000 29,000 43,500 43,500 43,500 58,000 58,000 58,000
High 30 ---60
Low 20 ---50
08 12 08 12 16 14 16 20
( 17 --- 3 3 )
( 11 --- 2 8 )
20--- 50
( 11 --- 2 8 )
15--- 45 ( 8 --- 2 5 )
40--- 70
( 22 --- 3 9 )
30--- 60
( 17 --- 3 3 )
30--- 60
( 17 --- 3 3 )
30--- 60
( 17 --- 3 3 )
25--- 55
( 14 --- 3 0 )
15--- 45 ( 8 --- 2 5 )
40--- 70
( 22 --- 3 9 )
25--- 55
( 14 --- 3 0 )
30--- 60
( 17 --- 3 3 )
25--- 55
( 14 --- 3 0 )
25--- 55
( 14 --- 3 0 )
15--- 45 ( 8 --- 2 5 )
BLOWER PERFORMANCE DATA
UNIT SIZE
DIRECT-DRIVE MOTOR Hp (PSC) 1/5 1/3 1/5 1/3 1/2 1/3 1/2 3/4
MOTOR FULL LOAD AMPS 2.8 5.1 2.8 5.1 7.4 5.2 7.4 11.0
RPM (Nominal) – Speeds 1075-4 1075-5 1075-4 1075-5 1075-5 1075-4 1075-5 1075-5
BLOWER WHEEL DIAMETER × WIDTHS --­In. (mm)
PSC ---Permanent Split Capacitor
045 070 090
08 12 08 12 16 14 16 20
10 x 6 (254 x
152)
10 x 6 (254 x
152)
10 x 6 (254 x
152)
10 x 6 (254 x
152)
11 x 8 (279 x
203)
10 x 8 (254 x
203)
10 x 10
(254 x
254)
6
11 x 11
(279 x
279)
PHYSICAL DATA
110 135 155
UNIT SIZE
OUTPUT CAPACITY BTUH* (Nonweatherized ICS) †
INPUT BTUH*
AFUE † * Nonweatherized ICS 80.0 80.0 80.0 80.0 80.0 80.0
SHIPPING WEIGH T --- LB. (KG) 135 (61) 146 (66) 152 (69) 149 (68) 163 (74) 170 (77)
CERTIFIED TEMP RISE RANGE --- ° F (° C)
CERTIFIED EXT STATIC PRESSURE
AIRFLOW CFM‡
LIMIT CONTROL SPST
HEATING BLOWER CONTROL Solid-State Time Operation
BURNERS (Monoport) 5 5 5 6 6 7
GAS CONNECTION SIZE 1 /2 --- i n . N P T
GAS VALVE (Redundant) Manufacturer White-Rodgers
Minimum Inlet Pressure (In. W.C.) 4.5 (Natural Gas)
Maximum Inlet Pressure (In. W.C.) 13.6 (Natural Gas)
IGNITION DEVICE Hot S urface
* Gas input ratings are certified for elevations to 2000 ft. (610 M). For elevations above 2000 ft. (610 M), reduce r a tings 4 percent for each 1000 ft. (305M)
above sea level. Refer to National Fuel Gas Code NFPA 54/ ANSI Z223.1---2009 Table F.4 or furnace Installation Instructions.
† Capacity in accordance with U.S. Government DOE test procedures.
‡ Airflow shown is for bottom only return ---air supply. For air delivery above 1800 CFM, see Air Delivery Table for other options. A filter is required for each
return-air supply.
ICS — Isolated Combustion System
All 58CTA; 58CTX
Upflow
All 58CTX Downflow/
Horizontal
All 58CTA; 58CTX
Upflow
All 58CTX Downflow/
Horizontal
Heating 0.20 0.20 0.20 0.20 0.20 0.20
Cooling 0.50 0.50 0.80 0.50 0.50 0.50
Heating H ig h/Low 1335/1180 1290/1045 1555/1295 1525/1320 1865/1640 1790/1565
Cooling 1355 1695 2200 1710 2110 2230
High 89,000 89,000 89,000 107,000 107,000 125,000
Low 59,000 59,000 59,000 70,000 70,000 82,000
High 85,000 85,000 85,000 102,000 102,000 119,000
Low 59,000 59,000 59,000 70,000 70,000 82,000
High 110,000 110,000 110,000 132,000 132,000 154,000
Low 72,500 72,500 72,500 87,000 87,000 101,500
HIgh 105,000 105,000 105,000 126,000 126,000 147,000
Low 72,500 72,500 72,500 87,000 87,000 101,500
High 50 ---80
Low 30--- 60
12 16 22 16 22 20
( 17 --- 3 3 )
( 17 --- 3 3 )
40--- 70
( 17 --- 3 3 )
25--- 55
( 14 --- 3 0 )
30--- 60
( 17 --- 3 3 )
20--- 50
( 11 --- 2 8 )
50--- 80
( 17 --- 3 3 )
30--- 60
( 17 --- 3 3 )
40--- 70
( 17 --- 3 3 )
25--- 55
( 14 --- 3 0 )
45--- 75
( 17 --- 3 3 )
30--- 60
( 17 --- 3 3 )
58CTA/CTX
BLOWER PERFORMANCE DATA
UNIT SIZE
DIRECT-DRIVE MOTOR Hp (PSC) 1/3 1/2 3/4 1/2 3/4 3/4
MOTOR FULL LOAD AMPS 5.2 7.4 11.0 7.9 11.1 11.1
RPM (Nominal) – Speeds 1075-4 1075-5 1075-5 1075-4 1075-4 1075-5
BLOWER WHEEL DIAMETER × WIDTHS ---
In. (mm)
PSC ---Permanent Split Capacitor
110 135 155
12 16 22 16 22 20
10 x 8
(254 X 203)
10 x 10
(254 X 254)
11 x 11
(279 x 279)
10 x 10
(254 x 254)
11 x 11
(279 x 279)
7
11 x 11
(279 x279)
58CTA/CTX
SEE NOTES: 1,2,4,7,8,9
UPFLOW
A02058
SEE NOTES: 1,2,3,4,7,8,9
UPFLOW
SEE NOTES: 1,2,4,5,7,8,9
DOWNFLOW
A02059 A02061
SEE NOTES:1,2,3,4,5,7,8,9
DOWNFLOW
A02060 A02063
Venting Notes
1. For common vent, vent connector sizing and vent material: United States, latest edition of the National Fuel Gas Code (NFGC), ANSI Z223.1/NFPA 54.
2. Immediately increase to 5-in. (127 mm) vent connector outside furnace casing when 5-in. (127 mm) vent connector required, refer to Note 1.
3. Side outlet vent for upflow and downflow installations must use Type B vent immediately after exiting the furnace, except when Downflow Vent Guard is used in downflow position.
4. Type B vent where required, refer to Note 1.
5. 4---in. (102 mm) single wall vent must be used inside furnace casing and the Downflow Vent Guard Kit.
6. Accessory Downflow Vent Guard Kit, required in downflow installations with bottom vent configuration.
7. Chimney Adapter Kit required for exterior masonry chimney applications. Refer to Chimney Adapter Kits for sizing and complete application details.
8. Secure vent connector to furnace elbow with (2) corrosion-resistant sheet metal screws, space approximately 180° apart.
9. Secure all other single wall vent connector joints with (3) corrosion-resistant screws spaced approximately 120° apart. Secure Type B vent connectors per vent connector manufacturer’s recommendations.
SEE NOTES: 1,2,3,4,5,7,8,9
DOWNFLOW
SEE NOTES: 1,2,4,5,6,7,8,9
DOWNFLOW
A02062
8
SEE NOTES: 1,2,4,5,7,8,9
HORIZONTAL RIGHT
A02068
SEE NOTES: 1,2,4,7,8,9
HORIZONTAL RIGHT
SEE NOTES: 1,2,4,5,7,8,9
HORIZONTAL RIGHT
A02069
A02070
58CTA/CTX
SEE NOTES: 1,2,4,7,8,9
HORIZONTAL LEFT
SEE NOTES: 1,2,4,5,7,8,9
HORIZONTAL LEFT
A02066
A02064
SEE NOTES: 1,2,4,5,7,8,9
HORIZONTAL LEFT
SEE NOTES: 1,2,4,5,7,8,9
HORIZONTAL LEFT
A02065
A02067
9
AIR DELIVERY—CFM (With Filter)*
RETURN-AIR
UNIT SIZE
045-08
045-12
070-08
070-12
070-16
58CTA/CTX
090-14
090-16
090-20
* A filter is required for each return-- -air supply. Airflow perf ormance includes 3/4--- in. (19 mm) washable filter media su ch as contained in factory --- a uth o r i ze d
accessory filter rack. To determine airflow performance without this filter, assume an additional .1 available external static pressure.
— Indicates unstable operating conditions.
SUPPLY
Bottom
or
Side(s)
Bottom
or
Side(s)
Bottom
or
Side(s)
Bottom
or
Side(s)
Bottom
or
Side(s)
Bottom
or
Side(s)
Bottom
or
Side(s)
Bottom
Only
Both Sides
or 1
Side & Bottom
1SideOnly
SPEED
High
Med-High
Med-Low
Low
High
Med-High
Medium
Med-Low
Low
High
Med-High
Med-Low
Low
High
Med-High
Medium
Med-Low
Low
High
Med-High
Medium
Med-Low
Low
High
Med-High
Med-Low
Low
High
Med-High
Medium
Med-Low
Low
High
Med-High
Medium
Med-Low
Low
High
Med-High
Medium
Med-Low
Low
High
Med-High
Medium
Med-Low
Low
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
1120
930 820 725
1465 1295 1150 1030
860
1140
915 795 690
1440 1180 1015
885 695
1840 1610 1460 1260 1065
1650 1515 1385 1205
2060 1710 1470 1260 1030
2380 2185 1905 1595 1340
2485 2175 1845 1540 1280
2420 2160 1850 1530 1290
1075
890 785 690
1400 1260 1120 1008
835
1105
885 770 665
1400 1165 1020
885 700
1790 1575 1430 1240 1040
1600 1485 1360 1180
2000 1695 1475 1265 1025
2295 2115 1865 1565 1310
2415 2130 1815 1515 1250
2345 2110 1815 1490 1250
1020
1325 1210 1085
1055
1355 1150 1010
1730 1535 1400 1215 1015
1535 1440 1320 1160
1930 1665 1450 1245 1020
2205 2045 1815 1530 1280
2330 2070 1770 1475 1220
2265 2045 1765 1455 1220
EXTERNAL STATIC PRESSURE (In. W.C.)
850 750 655
980 810
855 740 630
880 700
960 805 700 605
1250 1155 1040
945 780
1010
825 700 590
1300 1125
990 865 690
1670 1485 1360 1180
985
1465 1380 1260 1120
1835 1585 1390 1225
990
2105 1960 1740 1485 1225
2230 2000 1720 1435 1190
2165 1960 1710 1420 1190
895 750 650 555
1175 1090
985 895 745
955 785 655 550
1240 1085
965 845 670
1605 1435 1315 1145
955
1385 1300 1195 1065
1755 1480 1335 1165
940
2005 1875 1670 1430 1170
2135 1930 1655 1385 1155
2070 1885 1635 1375 1155
815 680 585 495
1085 1015
920 835 700
885 725 600 475
1170 1030
925 815 640
1530 1370 1260 1100
915
1285 1220 1120 1005
1620 1390 1230 1090
890
1900 1770 1590 1355 1120
2030 1840 1580 1335 1105
1960 1790 1560 1320 1110
720 600 505 405
980 930 835 765 635
815 655 510 415
1090
970 875 770 600
1450 1305 1205 1040
875
1175 1115 1025
925
1490 1245 1120
995 810
1775 1655 1490 1275 1040
1920 1740 1500 1270 1035
1850 1695 1480 1250 1040
605 500 400 305
860 830 740 685 555
715 530 420 340
1000
890 800 700 540
1370 1230 1130
985 825
1055
990 915 810
1315 1110 1005
880 720
1650 1535 1390 1160
955
1790 1620 1395 1175
945
17720
1570 1380 1160
950
455 345 235
725 700 620
— —
545 420 325 245
890 785 700 605 460
1275 1145 1055
915 765
895 830 710 630
1115
955 855 750 615
1510 1400 1245 1055
850
1645 1495 1270 1045
845
1570 1445 1250 1055
835
340 195
— —
— — — — —
390 280
— —
745 645 560 475 345
1170 1055
965 835 695
645 600 565 510
910 775 690 600 500
1335 1240 1110
920 750
1485 1345 1090
915 745
1420 1305 1110
905 740
10
AIR DELIVERY—CFM (With Filter)* continued
RETURN-AIR
UNIT SIZE
110-12
110-16
110-22
135-16
135-22
155-20
* A filter is required for each return-- -air supply. Airflow perf ormance includes 3/4--- in. (19 mm) washable filter media su ch as contained in factory --- a uth o r i ze d
accessory filter rack. To determine airflow performance without this filter, assume an additional .1 available external static pressure.
— Indicates unstable operating conditions.
SUPPLY
Bottom
or
Side(s)
Bottom
or
Side(s)
Bottom
Only
Both Sides
or 1
Side & Bottom
1SideOnly
Bottom
or
Side(s)
Bottom
Only
Both Sides
or 1
Side & Bottom
1SideOnly
Bottom
Only
Both Sides
or 1
Side & Bottom
1SideOnly
SPEED
High
Med-High
Med-Low
Low
High
Med-High
Medium
Med-Low
Low
High
Med-High
Medium
Med-Low
Low
High
Med-High—2205
High
Med-High
Medium
Med-Low
Low
High
Med-High
Med-Low
Low
High
Med-High
Med-Low
Low
High
Med-High
Med-Low
Low
High
Med-High
Med-Low
Low
High
Med-High
Med-Low
Low
High
Med-High—2155
High
Med-High—2140
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
1625 1510 1360 1195
2055 1750 1545 1300 1050
2530 2225 1895 1565 1320
2485 2155 1830 1520 1275
2090 1790 1545 1325
2485 2195 1880 1640
— 2180 1880 1640
2320 2125 1845 1640
2465 2115 1800 1570
1575 1470 1335 1180
1990 1725 1525 1290 1045
2460 2190 1885 1555 1295
2175
2430 2135 1830 1505 1260
2010 1755 1525 1320
2400 2150 1850 1635
— 2145 1850 1635
2250 2065 1825 1620
2430 2105 1790 1565
— 2135
— 2095
1515 1415 1295 1155
1910 1670 1490 1275 1015
2380 2135 1865 1535 1265
2415 2120
2360 2100 1810 1490 1240
1930 1705 1500 1295
2310 2090 1820 1615
2385 2060 1820 1615
2155 1995 1765 1580
2375 2075 1770 1551
2375 2095
2260 2040
EXTERNAL STATIC PRESSURE (In. W.C.)
1445 1355 1250 1115
1815 1605 1445 1235
975
2285 2075 1820 1505 1235
2330 2065
2270 2040 1780 1470 1210
1835 1640 1450 1265
2215 2000 1780 1585
2305 2010 1780 1585
2055 1910 1710 1540
2305 2030 1735 1525
2285 2040
2180 1975
1355 1285 1180 1065
1695 1515 1355 1165
935
2200 1995 1770 1465 1205
2235 1975
2175 1970 1730 1430 1180
1710 1550 1380 1210
2110 1920 1715 1530
2195 1945 1715 1530
1970 1815 1650 1485
2230 1980 1695 1495
2200 1975
2085 1890
1260 1185 1100
980
1575 1400 1260 1085
880
2085 1910 1700 1410 1160
2125 1900
2070 1885 1665 1385 1135
1590 1465 1315 1150
2000 1825 1635 1465
2085 1865 1635 1465
1855 1710 1570 1410
2110 1910 1640 1445
2105 1895
1975 1810
1165 1070
985 860
1425 1255 1135 1005
815
1970 1805 1610 1350 1105
1995 1790
1950 1790 1595 1330 1090
1470 1360 1215
995
1880 1720 1540 1370
1960 1765 1540 1370
1725 1610 1475 1330
2000 1830 1570 1370
1995 1790
1865 1705
990 890 810 740
1230 1120 1020
895 715
1835 1695 1520 1265 1035
1860 1685
1825 1680 1505 1250 1025
1335 1210 1005
865
1725 1565 1415 1255
1825 1660 1415 1255
1600 1490 1370 1220
1865 1725 1465 1270
1870 1685
1740 1595
785 725 670 605
1090
975 880 750 610
1695 1565 1410 1175
950
1735 1580
1685 1560 1395 1165
930
1025
945 855 745
1535 1405 1290 1150
1670 1515 1290 1150
1450 1340 1240 1080
1725 1590 1345 1175
1730 1550
1605 1480
595 530 475 410
910 785 750 620 515
1545 1430 1290 1050
870
1605 1460
1535 1420 1275 1055
840
835 785 670 540
1355 1255 1160 1040
1465 1325 1160 1040
1280 1175 1100
960
1545 1425 1225 1070
1570 1400
1455 1325
58CTA/CTX
11
DIMENSIONS
A
B
[736.9]
29
Ø7/8 [22.2]
ACCESSORY
5 15/16 [150.7]
28.39
[721.2]
Ø7/8 [22.2]
ACCESSORY
14 7/8
[337.3]
(BOTH SIDES)
Ø7/8 [22.2] ACCESSORY
Ø7/8
[22.2]
ACCESSORY
Ø1 3/4 [44.5] GAS ENTRY
Ø1/2 [12.7] THERMOSTAT WIRE ENTRY
22 1/16
[560]
SIDE INLET
(BOTH SIDES)
11 7/16 [290.7]
9 11/16 [245.4]
[197.8]
7 13/16
Ø7/8
[22.2]
J.BOX PROVISION
Ø7/8 [22.2] JUNCTION BOX LOCATION
Ø1 3/4 [44.5] GAS ENTRY
1 15/16 [49.2]
1
[25.4]
1 1/4 [31.8]
29 9/16 [750.7]
1 15/16
[49.2]
5 5/8
[143.3] 5 7/16 [138.5]
6 13/16
[172.3]
Ø1/2 [12.7]
THERMOSTAT WIRE ENTRY
19
[481.7]
OUTLET
D
21.6
[549.5]
BOTTOM INLET
C
33 1/4
[843.9]
9 9/16 [243.3]
3/4
[19.1]
5 7/8 [148.5]
3 7/16 [86.8]
9 7/8
[250.7]
27 3/4 [704.7]
2 5/16 [59]
FRONT OF CASING
TOP OF CASING
4 13/16 [122.2]
27 3/4 [704.7]
5 7/8
[148.5]
8 5/8 [219]
5 1/2 [140.3]
8 7/16 [213.5]
FRONT OF CASING
TOP OF CASING
6.1
[155.7]
2 1/16 [51.6]
5.1
[130.5]
1.7 [43.5]
Ø7/8 [22.2] ACCESSORY (2)
AIR FLOW
AIR FLOW
BOTTOM RETURN
WIDTH
AIR FLOW
KNOCK OUTS FOR VENTING(5 PLACES)
5.1
[130.5]
2 1/16 [51.6]
1.7 [43.5]
Ø7/8 [22.2] ACCESSORY (2)
FRONT OF CASING
8 5/8 [219]
6 13/16
FRONT OF CASING
1 15/16
33 1/4
[843.9]
27 3/4
[704.7]
9 7/8
[250.7]
8 7/16
[213.5]
5 15/16 [150.7]
5 1/2 [140.3]
AIR FLOW
ACCESSORY
THERMOSTAT WIRE ENTRY
Ø7/8 [22.2]
Ø1/2
[12.7]
[49.2]
3 7/16 [86.8]
5 7/8 [148.5]
2 5/16 [59]
TOP OF CASING
Ø7/8 [22.2] JUNCTION BOX LOCATION
Ø1 3/4 [44.5] GAS ENTRY
AIR FLOW
A
TOP OF CASING
29 9/16 [750.7]
27 3/4 [704.7]
58CTA/CTX
Ø7/8
[22.2]
ACCESSORY
21.6
[549.5]
BOTTOM INLET
28.39
[721.2]
29
[736.9]
NOTES:
1. Two additional 7/8---in. (22 mm) diameter holes are located in the top plate.
2. Minimum return ---air openings at furnace, based on metal duct. If flex duct is used, see flex duct manufacturer’s recommendations for equivalent diameters.
[155.7]
6.1
BOTTOM RETURN
WIDTH
[19.1]
3/4
a. For 800 CFM--- 16 --- in. (406 mm) round or 14 1/2 x 12---in. (368 x 305 mm) rectangle.
b. For 1200 CFM---20 ---in. (508 mm) round or 14 1/2 x 19 1/2---in. (368 x 495 mm) rectangle.
c. For 1600 CFM---22 ---in. (559 mm) round or 14 1/2 x 22 1/16---in. (368 x 560mm) rectangle.
d. For airflow requirements above 1800 CFM, see Air Delivery table in Product Data literature f o r specific use of single side inlets. The use of both sideinlets,
a combination of 1 side and the bottom, or the bottom only will ensure adequate return air openings for airflow requirements above 1800 CFM.
KNOCK OUTS FOR VENTING(5 PLACES)
[148.5]
5 7/16
[138.5]
4 13/16 [122.2]
9 9/16 [243.3]
J.BOX PROVISION
ACCESSORY
5 7/8
[172.3]
[143.3]
1 15/16
[49.2]
[22.2]
Ø7/8
[22.2]
5 5/8
Ø7/8
AIR FLOW
19
[481.7]
OUTLET
Ø1/2 [12.7] THERMOSTAT WIRE ENTRY
Ø1 3/4 [44.5] GAS ENTRY
Ø7/8 [22.2] ACCESSORY
22 1/16
[560]
SIDE INLET
(BOTH SIDES)
7 13/16
9 11/16
[197.8]
[245.4]
14 7/8
[337.3]
(BOTH SIDES)
1 1/4 [31.8]
[25.4]
11 7/16 [290.7]
A10270
A
FURNACE
SIZE
045 ---08 14--- 3/16 (360) 12--- 9/16 (319) 9 ---5/16 (237) 12---11/16 (322) 4 (102) 104 (47) 16 (406)
045 ---12 14--- 3/16 (360) 12--- 9/16 (319) 9 ---5/16 (237) 12---11/16 (322) 4 (102) 107 (49) 16 (406)
070 ---08 14--- 3/16 (360) 12--- 9/16 (319) 9 ---5/16 (237) 12---11/16 (322) 4 (102) 111 (50) 16 (406)
070 ---12 14--- 3/16 (360) 12--- 9/16 (319) 9 ---5/16 (237) 12---11/16 (322) 4 (102) 115 (52) 16 (406)
070 ---16 17---1/2 (445) 15--- 7/8 (403) 11 ---9/16 (294) 16 --- 1/8 (410) 4 (102) 126 (57) 16 (406)
CABINET
WIDTH
IN (mm)
090 ---14 17---1/2 (445) 15--- 7/8 (403) 11 ---9/16 (294) 16 --- 1/8 (410) 4 (102) 127 (58) 16 (406)
090 ---16 21 (533) 19 --- 3/8 (492) 13 --- 5/16 (338) 19--- 1/2 (495) 4 (102) 140 (64) 20 (508)
090 ---20 21 (533) 19 --- 3/8 (492) 13 --- 5/16 (338) 19--- 1/2 (495) 4 (102) 146 (66) 20 (508)
110 ---12 17---1/2 (445) 15--- 7/8 (403) 11 ---9/16 (294) 16 --- 1/8 (410) 4 (102) 135 (61) 16 (406)
110 ---16 21 (533) 19 --- 3/8 (492) 13 --- 5/16 (338) 19--- 1/2 (495) 4 (102) 146 (66) 20 (508)
110 ---22 21 (533) 19 --- 3/8 (492) 13 --- 5/16 (338) 19--- 1/2 (495) 4 (102) 152 (69) 20 (508)
135 ---16 21 (533) 19 --- 3/8 (492) 13 --- 5/16 (338) 19--- 1/2 (495) 4 (102)* 149 (68) 20 (508)
135 ---22 24---1/2 (622) 22--- 7/8 (581) 15 ---1/16 (383) 23 (584) 4 (102))* 163 (74) 24 (610)
155 ---20 24---1/2 (622) 22--- 7/8 (581) 15 ---1/16 (383) 23 (584) 4 (102)* 170 (77) 24 (610)
*135 and 155 size furnaces require a 5 or 6 ---in. (127 or 152 mm) vent. Use a vent adapter between furnace and vent stack. See Installation Instructions for complete installation requirements.
B
OUTLET
WIDTH
IN (mm)
C
TOP AND
BOTTOM FLUE
COLLAR
IN (mm)
12
D
BOTTOM
INLET WIDTH
IN (mm)
VENT
CONNECTION
SIZE
IN (mm)
SHIP WT
LB (KG)
ACCESSORY
MEDIA
CABINET SIZE
IN (mm)
58CTA/CTX
A10269
I
G
S
E
N
D
Always Ask For
Use of the AHRI Certified TM Mark indicates a manufacturer’s participation in the program. For verification of certification for individual products, go to www.ahridirectory.org.
13
C
E
R
D
E
I
T
F
I
TYPICAL WIRING SCHEMATIC
58CTA/CTX
A95236
ELECTRICAL DATA
OPERATING VOLTAGE RANGE
58CTA/CTX
UNIT SIZE
045-08 115-60-1 127 104 5.3 49 (14.9) 15 14
045-12 115-60-1 127 104 7.1 38 (11.5) 15 14
070-08 115-60-1 127 104 5.2 51 (15.5) 15 14
070-12 115-60-1 127 104 7.3 37 (11.2) 15 14
070-16 115-60-1 127 104 10.1 27 (8.2) 15 14
090-14 115-60-1 127 104 8.2 34 (10.3) 15 14
090-16 115-60-1 127 104 9.9 28 (8.5) 15 14
090-20 115-60-1 127 104 12.9 34 (10.3) 20 12
110-12 115-60-1 127 104 8.2 34 (10.3) 15 14
110-16 115-60-1 127 104 10.1 28 (8.5) 15 14
110-22 115-60-1 127 104 13.7 32 (9.7) 20 12
135-16 115-60-1 127 104 10.2 27 (8.2) 15 14
135-22 115-60-1 127 104 14.5 30 (9.1) 20 12
155-20 115-60-1 127 104 15.0 29 (8.8) 20 12
* Permissible limits of the voltage range at which unit operates satisfactorily.
† Time--- delay type is recommended.
‡ Length shown is as measured 1 way along wire path between unit and service panel for maximum 2 percent voltage drop.
VOLTS HERTZ
PHASE
Maximum* Minimum*
MAXIMUM
UNIT AMPS
MAXIMUM
WIRE
LENGTH --
FT (M)‡
MAXIMUM
FUSE OR CKT
BKR AMPS†
MINIMUM
WIRE GAGE
14
TYPICAL INSTALLATION
CONDENSING UNIT
HUMIDIFIER
AIRFLOW
ELECTRONIC AIR CLEANER
GAS-FIRED WATER HEATER
58CTA/CTX
A10211
15
GUIDE SPECIFICATIONS
Gas Furnace 58CTA/CTX General
SYSTEM DESCRIPTION
Furnish a _________________ fixed capacity gas-fired furnace for use with natural gas or propane (factory authorized conversion kit required for propane); furnish cold air return plenum.
QUALITY
ASSURANCE
Unit will be designed, tested and constructed to the current ANSI Z 21.47/CSA 2.3 design standard for gas--fired central furnaces.
Unit will be 3rd party certified by CSA to the current ANSI Z 21.47/CSA 2.3 design standard for gas--fired central furnaces.
Unit will carry the CSA Blue StarR label.
Unit efficiency testing will be performed per the current DOE test procedure as listed in the Federal Register.
Unit will be certified for capacity and efficiency and listed in the latest AHRI Consumer’s Directory of
58CTA/CTX
Certified Efficiency Ratings.
Unit shall carry the current Federal Trade Commission Energy Guide efficiency label.
DELIVERY, STORAGE AND
HANDLING
Unit shall be shipped as single package only and is stored and handled per unit manufacturer’s recommendations.
WARRANTY (for inclusion by specifying
engineer)
U.S. only. Warranty certificate available upon request.
Products
EQUIPMENT
Components shall include: slow-opening two stage gas valve to reduce ignition noise, regulate gas flow, with electric switch gas shut-off; flame proving sensor, hot surface igniter, pressure switch assembly, flame rollout switch, blower and inducer assembly, 40va transformer; low-voltage (heating) (heating/cooling) thermostat.
Blower Wheel and Blower Motor
Galvanized blower wheel shall be centrifugal type, statically and dynamically balanced. Blower motor of PSC type shall be permanently lubricated with sealed bearings, of _______hp, and shall be multiple-speed direct drive. Blower motor shall be soft mounted to the blower scroll to reduce vibration transmission.
Filters
Furnace may have reusable--type filters. Filter shall be _______ (x) _______in. (mm). An accessory high efficiency Media Filter is available as an option. _______________ Media Filter.
Casing
Casing shall be of .030 in. (.76 mm) thickness
minimum, pre-painted galvanized steel.
Two Speed Inducer Motor
Two Speed Inducer motor shall be soft mounted to
reduce vibration transmission.
Draft Safeguard Switch
Draft Safeguard Switch (blocked vent safeguard) shall be factory installed to reduce the possibility of vent gas infiltration due to a blocked or restricted vent pipe.
Heat Exchangers
Heat exchangers shall be a 4-Pass 20 gage aluminized steel of fold--and--crimp sectional design when applied operating under negative pressure.
Controls
Control shall include a micro--processor based integrated electronic control board with at least 11 service troubleshooting codes displayed via diagnostic flashing enhanced LED light on the control, a self--test feature that checks all major functions of the furnace within one minute, and a replaceable automotive-type circuit protection fuse. Multiple operational settings available including, separate blower speeds for low heat, high heat, low cooling, high cooling and continuous fan. Continuous fan speed may be adjusted from the thermostat. Cooling airflow will be selectable between 350 or 400 CFM per ton of air conditioning. Features will also include temporary reduced airflow in the cooling mode for improved dehumidification when a control or Thermidistatt is selected as the thermostat.
OPERATING
CHARACTERISTICS
Heating Capacity shall be ________ Btuh input; ________ Btuh output capacity.
Fuel Gas Efficiency shall be 80% AFUE.
Air delivery shall be ___________ CFM minimum at
0.50 in. W.C. external static pressure.
Dimensions shall be: depth __________ in. (mm); width _________ in. (mm); height_________in. (mm). (casing only). Height shall be_________in. (mm). with A/C coil and _____________in. (mm) overall with plenum.
ELECTRICAL
REQUIREMENTS
Electrical supply shall be 115 volts, 60 Hz, single--phase (nominal). Minimum wire size shall be_________AWG; maximum fuse size or circuit breaker shall be __________Amps.
SPECIAL FEA
TURES
Refer to section of the product data sheet identifying accessories and descriptions for specific features and available enhancements.
Copyright 2010 Carrier Corp. D 7310 W. Morris St. D Indianapolis, IN 46231 Printed in U.S.A. Edition Date: 09/10
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
Catalog No: 58CT--- 7PD
Replaces: 58CT --- 6PD