Carrier 58BTA User Manual

HEATING & COOUNG
Upflow/Horizontal Oil Furnace
Installation, Start-up and Operating Instructions
FOR YOUR SAFETY
DO NOT STORE OR USE GASOLINE OR OTHER FLAMMABLE
VAPORS AND LIQUIDS IN THE VICINITY OF THIS OR ANY OTHER APPLIANCE.
ACCUMULATED, WHEN THE FURNACE IS FULL OF VAPOR OR WHEN THE COMBUSTION CHAMBER IS VERY HOT.
58BTA

WARNING

For use with grade 2 Fuel Oil maximum. Do Not use Gasoline, Crankcase Oil or any Oil containing Gasoline!

CAUTION

Never burn garbage or paper in the heating systems and never leave rags or paper around the unit.

CAUTION

These instructions are intended to be used by qualified personnel who have been trained in installing this type of furnace. Installation of this furnace by an unqualified person may lead to equipment damage and/or a hazardous condition which may lead to bodily harm.

GENERAL

This furnace is a three position unit, in that it may be operated in upflow, horizontal left-to-right, and horizontal right-to-left air flow positions. Very few modifications are required to change the furnace from one position to another at the job site. The furnace is shipped in the upflow configuration-instructions on changing to other configurations are on page 6 of this document.
It is shipped as a packaged unit, complete with burner and controls. It requires a line voltage (115VAC) connection to the control box, a thermostat hook-up as shown on the wiring diagram, oil line connection(s), adequate ductwork, and connection to a properly sized vent.
The air handling capacity of this furnace is designed for cooling air flow. Refer to Figure 6 for the expected airflows at various external duct static pressures.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 14' PC 101 Tab 6a 8a
Catalog No. 565-878
Printed in U.S.A. Form 58BTA-1SI
Issue 9413
20142901 118
Replaces; New
IMPORTANT: All local and national code requirements
governing the installation of oil burning equipment, wiring and flue connections must be followed. Some of the codes (issued by the Canadian Standards Association, the National Fire Protection Agency, and/or the American National Standards Institute) that may be applicable are:
CSA B139 ANSI/NFPA 31 ANSI/NFPA 90B WARM AIR HEATING AND AIR ANSI/NFPA 211
ANSI/NFPA 70 CSA C22.1
Only the latest issues of the above codes should be used, and are available from either:
The National Fire Protection Agency
Batterymarch Park
Qunicy, MA 02269
INSTALLATION CODE FOR OIL BURNING EQUIPMENT INSTALLATION OF OIL BURNING EQUIPMENT
CONDITIONING SYSTEMS
CHIMNEYS, FIREPLACES, VENTS AND SOLID FUEL BURNING APPLIANCES NATIONAL ELECTRICAL CODE CANADIAN ELECTRICAL CODE
attic instailation. As this unit may be installed as an upflow or horizontal furnace, it may be located in a basement, on the same level as the area to be heated, suspended, or in a crawlspace. In any case, the unit should always be installed level.
In a basement, or when installed on the floor (as in a crawlspace), it is recommended that the unit be installed on a concrete pad that is 1" to 2" thick.
When installed in a horizontal position, the furnace may be suspended by using an angle iron frame, as long as the total weight of both the furnace and the frame are allowed for in the support calculations. (Other methods of suspending are acceptable.)
The required minimum clearances for this furnace in all positions are specified in Figure 5.
The furnace should be located as close as possible to the chimney or vent in order to keep vent connections short and direct. The furnace should also be located as near as possible to the center of the air distribution system.
or The Canadian Standards Association
178 Rexdale Blvd. Rexdale, Ontario M9W 1R3

LOCATION

WARNING

This furnace is not watertight and is not designed for outdoor installation. This furnace shall be installed in such a manner as to protect the electrical components from water. Outdoor installation would lead to a hazardous electrical condition and to premature furnace failure.

CAUTION

For an attic installation it is important to keep insulation 12" or more away from any furnace openings. Some types of insulating materials may be combustible.
Air for Combustion and Ventilation:
This furnace should be installed in a location in which the facilities for ventilation permit satisfactory combustion of oil, proper venting and the maintenance of ambient temperature at safe limits under normal conditions of use. The location should not interfere with proper circulation of air within the confined space.
In addition to air needed for combustion, process air shall be provided as required for: cooling of equipment or material, controlling dew point, heating, drying, oxidation or dilution, safety exhaust and odor control.
In addition to air needed for combustion, air shall be supplied for ventilation, including all air required for comfort and proper working conditions for personnel.
The barometric draft regulator, included with the furnace, shall be installed in the same room or enclosure as the furnace in such a manner as to prevent any difference in pressure between the regulator and the combustion air supply.
Air requirements for the operation of exhaust fans, kitchen ventilation systems, clothes dryers, and fireplaces shall be considered in determining the adequacy of a space to provide combustion air requirements.
This furnace is approved for reduced clearances to combustible construction, therefore, it may be installed in an alcove or similar enclosure. It is also approved for
Issue 9413
20142901 218
In unconfined spaces in buildings of conventional frame, brick or stone construction infiltration may be adequate to provide air for combustion, ventilation and dilution of flue
/--xgases. This determination must be made on an individual
( hstallation basis and must take into consideration the
overall volume of the unconfined space, the number of windows and ventilation openings, the number of doors to the outside, internal doors which can close off the unconfined space and the overall tightness of the building construction.
Many new buildings and homes (and older ones that have been weatherized) must be considered as being tight construction and, therefore, infiltration will not be sufficient to supply the necessary air for combustion and ventilation.
A building can be considered as being of tight construction when:
a. Walls and ceilings exposed to the outside
atmosphere have a continuous water vapor retarder with a rating of one perm or less with openings gasketed or sealed and /or
b. Weatherstripping has been added on operable
windows and doors, and/or
c. Caulking or sealants are applied to areas such as
joints around window and door frames, between sole plates and floors, between wall-ceiling joints, between wall panels, at penetrations for plumbing, electrical and fuel lines and at other openings.
If combustion and ventilation air must be supplied to an
unconfined space from outside, an opening with a free area of not less than one square inch per 1,000 BTU per
hour of total input of all appliances within the unconfined space (but not less than 100 square inches) must be provided. This opening must be located such that it can
not be blocked at any time.
When ducts are used to supply air, they must be of the same cross sectional area as the free area of the openings to which they connect.
The minimum dimension of rectangular air ducts must not be less than 3 inches.
In calculating free area, consideration shall be given to the blocking effect of louvers, grilles or screens protecting openings. Screens used shall not be smaller than 1/4 inch mesh and shall be readily accessible for cleaning.
If the free area through a design of louvered or grille is known, it shall be used in calculating the size design and free area specified. If the design and free area is not known, it may be assumed that wood louvers will have 20 percent free area and metal louvers and grilles will have 60 percent free area. Louvers shall be fixed in the open position or interlocked with the furnace so they are opened automatically at furnace start-up and remain open during furnace operation.

WARNING

Do not block the combustion air openings in the furnace. Any blockage will result in improper combustion and may result in a fire hazard and/or cause bodily harm.

Ductwork Recommendations:

The proper sizing of warm air ducts is necessary to insure
satisfactory furnace operation. Ductwork should be in
accordance with the latest editions of NFPA-90A
(Installation of Air Conditioning and Ventilating Systems)
and NFPA-90B (Warm Air Heating and Air Conditioning
Systems) or Canadian equivalent.
For a confined space, where air is taken from an interior
space, two permanent openings of equal area are
required. One opening must be within 12" of the ceiling
and the other within 12" of the floor. Each opening must
have a free area of at least 1 sq. inch per 1,000 BTU of
total input rating but no less than 100 sq. inches.
If outside air is supplied to a confined space, then the two openings must be equal and located as above and the free area of each must be:
1. 1 sq. inch per 4,000 BTU of total rating when the air is directly communicated from the outdoors.
2. 1 sq. inch per 4,000 BTU of total input rating
\ when the air is brought in through vertical ducts.
3. 1 sq. inch per 2,000 BTU of total input rating when the air is transferred through horizontal ducts.
The supply ductwork should be attached to the flanged
opening provided at the discharge end of the furnace. See Figure 7 for the dimensions of this opening.
Knockouts are provided on both sides of the furnace to facilitate the side panel cut out required to assemble the return ductwork. This can be done on either the right or
the left side of the furnace. See Figure 7 for location and
dimensions. Undersized cut-outs will adversely affect the airflow capability of the furnace.
When the provided external filter rack is used, the return air duct should be attached as per Figure 9.
Provision is also made on this furnace for a bottom return
air duct. (We recommend the use of this opening for
horizontal installations.) The specifications for this
ISSUE 9413
20142901 318
opening are also illustrated in Figure 7. If the bottom return is not used, a field-supplied galvanized steel filler plate should be used to block off the opening.
The following recommendations should be followed when installing the ductwork:
1. Install locking type dampers in ail branches of the individual ducts to balance out the system. Dampers should be adjusted to impose the proper static at the outlet of the furnace.
2. A flexible duct connector of noncombustible material should be installed at the unit on both the supply and return air system. In applications where extremely quiet operation is necessary, the first 10 feet (if possible) of supply and return ducts should be internally lined with acoustical material.

WARNING

The coil MUST be installed on the air discharge side of the furnace. Under no circumstances should the air flow be such that cooled, conditioned air can pass over the furnace heat exchanger. This will cause condensation in the heat exchanger and possible failure of the heat exchanger which could lead to a fire hazard and/or a hazardous condition which may lead to bodily harm. Heat exchanger failure due to improper installation may not be covered by warranty.
2. In parallel flow installation, dampers must be provided to direct air over the furnace heat exchanger when heat is desired and over the cooling coil when cooling is desired.
3. In cases where the return air grille is located close to the fan inlet, there should be at least one 90° air turn between fan inlet and grille. Further reduction in sound level can be accomplished by installing acoustical air turning vanes or lining duct as described in item 2 above.
4. When a single air grille is used, the duct between grille and furnace must be the same size as return opening in furnace.

CAUTION

Return air grilles and warm air registers must not be obstructed.

WARNING

When supply ducts carry air circulated by the furnace to areas outside the spaces containing the furnace, the return air shall also be handled by a duct sealed to the furnace casing and terminating outside the space containing the furnace. Incorrect ductwork termination and sealing will create a hazardous condition which could lead to bodily harm.

IMPORTANT: The dampers should be adequate to

prevent cooled air from entering the furnace, and if manually operated, must be equipped with the means to prevent operation of either the cooling unit or furnace unless the damper is in the full cool or heat position.

Venting Instructions:

Venting of the furnace should be to the outside and in accordance with local codes or requirements of the local utility.
OIL FIRED APPLIANCES SHALL BE CONNECTED TO FLUES HAVING SUFFICIENT DRAFT AT ALL TIMES TO ENSURE SAFE AND PROPER OPERATION OF APPLIANCE.
For additional venting information refer to ANSI/NFPA 211 Chimney. Fireplaces. Vents and Solid Fuel Burning Appliances and/or CSA B139 Installation Code.
When installing the furnace with cooling equipment for
year round operation, the following recommendations must be followed for series or parallel air flow:
1. In series air flow applications, the coil is mounted after the furnace in an enclosure in the supply air stream. The furnace blower is used for both heating and cooling air flow.
This furnace is certified for use with Type "L" vent
(maximum flue gas temperature 575°F).
ISSUE 9413 20142901 418

Pre-Installation Vent System Inspection:

Before this furnace is installed, it is highly recommended
;"^^that any existing vent system be completely inspected.
For any chimney or vent, this should include the following:
1. Inspection for any deterioration in the chimney or vent. If deterioration is discovered, the chimney must be repaired or the vent must be replaced.
2. Inspection to ascertain that the vent system is clear and free of obstructions. Any blockage must be cleared before installing this furnace.
3. Cleaning the chimney or vent if previously used for venting a solid fuel burning appliance or fireplace.
4. Confirming that all unused chimney or vent connections are properly sealed.
5. Verification that the chimney is properly lined and sized per the applicable codes. (Refer to list of codes on page 2.)

Masonry Chimney:

This furnace can be vented into an existing masonry chimney. This furnace must not be vented into a chimney servicing a solid fuel burning appliance. Before venting
) this furnace into a chimney, the chimney must be checked
for deterioration and repaired if necessary. The chimney must be properly lined and sized per local or national codes.
If the furnace is vented into a common chimney, the chimney must be of sufficient area to accommodate the total flue products of all appliances vented into the chimney.
The following requirements are provided for a safe venting system:
the highest point where it passes through a roof of a building and at least two (2) feet higher than any portion of a building within a horizontal distance of ten (10) feet. It shall also be extended at least five (5) feet above the highest connected equipment flue collar.
10. Check local codes for any variance.

Factory Built Chimneys:

May use listed factory built chimneys. Refer to chimney manufacturers instructions for proper installation.

Horizontal Venting ”150 Size Only"!:

This furnace may be horizontally vented through an outside wall when installed with the following auxiliary inducer blower:
Tjernlund Products, Inc. Model SS1C
available from:
Tjernlund Products, Inc.
1601 Ninth Street
\A/hite Bear Lake, MN 55110-6795
NOTE: An isolation relay should be used to allow proper
operation of the ignition control with the auxiliary blower. Instructions for connecting the relay are included in the Tjernlund blower.

CAUTION

USE METALLIC VENT PIPE, ONLY! PLASTIC VENTING MATERIALS ARE PROHIBITED!

1. Be sure that the chimney flue is clear of any dirt or debris.
2. Be sure that the chimney is not servicing an open fireplace.
3. Never reduce the pipe size below the size of the furnace flue pipe.
4. All pipe should be supported using the proper clamps and/or straps. These supports should be at least every four (4) feet.
5. All horizontal runs of pipe should have at least a 1/4" per foot of upward slope.
6. All runs of pipe should be as short as possible with as few turns as possible.
7. Seams should be tightly joined and checked for leaks.
8. The flue pipe must not extend into the chimney but be flush with the inside wall.
9. The chimney must extend three (3) feet above

Oil Burner:

This furnace is supplied with a high pressure atomizing retention head type burner (for use with not heavier than grade 2 Fuel Oil). The air tube length, from the face of the mounting plate to the extreme face of the end cone, should be seven (7) inches.
Lubricate the burner motor with SAE 10 oil. Once each year, pour two (2) teaspoons of oil slovviy into each oil cup.
ISSUE 9413
20142901 518

Oil Connections:

Complete instructions for installation of the fuel oil piping will be found in the oil burner installation instructions included with the furnace.
Oil line entry holes are produced in the side panels and top panel. Two holes are provided in each location, so that a two-pipe system may be used if desired. See
Figure 1 below.
Oil Connection Entry Holes
Figure 1
An oil filter should be used with all oil burners, installed as close as possible to the burner.

WARNING

TTie unit cabinet must have an uninterrupted or unbroken electrical ground to minimize personal injury
if an electrical fault should occur. A green ground screw is provided in the control box for this connection.
Use copper wire only for 115V supply service to unit.
Metallic conduit (where required/used) may terminate at the side panel of the unit. It is not necessary to extend the conduit inside the unit from the side panel to the control box.
When replacing any original furnace wiring, use only 105 degree C, 16 AWG copper wire.
Instructions for wiring the thermostat are packed in the thermostat (field supplied) box. Make the thermostat connections as shown in Figure 10 at the 24 volt terminal board on the control box.
When installing optional accessories to this appliance, follow the manufacturer's installation instructions included with the accessory. Other than wiring for the thermostat, wire with a minimum of type "T" insulation (63°F rise) must be used for accessories.

Barometric Draft Control:

The barometric draft control shipped with the furnace must be used with the furnace to insure proper operation. Instructions for installing the control are packed with the control. Refer also to Figure 8 on page 14 for suggested locations.

Electrical:

The appliance must be installed In accordance with current ANSI/NFPA 70 National Electrical Code, CSA C22.1 Canadian Electrical Code Part 1 and/or local codes.
The control system depends on the correct polarity of the power supply. Connect "HOP' wire (H) and "NEUTRAL"
wire (N) as shown in Figure 10. A separate line voltage supply should be used with a
fused disconnect switch or circuit breaker between the main power panel and the unit. See Figure 10.

Filters:

An external filter rack is provided as standard equipment with this furnace. The assembly and installation of this filter rack is shown in Figure 9.

To Change from Upflow to Horizontal:

• Remove the burner from the unit by removing the three burner mounting nuts. Prevent putting
undue strain on burner wiring. (It may be necessary to disconnect the burner wiring in some cases.)
Note that the three burner mounting studs are in the "nine, twelve, and three" o'clock positions on the burner mounting plate.
Place the furnace in the installation position (i.e., on its side). Remove the burner mounting stud that is now in the six o’clock position (See Illustrations A & B). Reinstall the stud in the other open position on the mounting plate, so that
ISSUE 9413
20142901 618
Loading...
+ 14 hidden pages