The design of the 58BB,BD Downflow GasFired Furnaces is A.G.A. certified for close clear
ance, “hide-a-way” installation. These units meet
requirements for under-the-house warm air delivery
for either concrete slab or crawl space construc
tion. See Fig. 1 and Table 1 for furnace dimensions
and physical data. See Table 2 for blower data.
Table 1 — Dimensions and Physical Data
58ВВ,В
FURNACE 58
MODEL
SERIES^
APPROX SHIP. WT (lb)
DIMENSIONSlin.)
Width A
Length B
Height C
With Plenum D
Supply Air Opening E
Return Air Open
Front to Vent Cl H
Front to Conn. Cl J
Vent Diom K
Min Floor Opening L
Input (1000 Btuh)
Bonn Cop. (1000 Btuh)
T emp
Series 100,400
Rise
Series 200,500
(F)**
ESP’
Series 100,400
(in.
Series 200,500
wg)
FILTERStt No.
Size (in.)
BB
080 100 120
100^200,400,500
16У4
20У4
26
18Ув
"ТаУв'"
']4% ^
18%
16
^2%
2% ”
01::
]4%
Natural or
100
80
70-100
120
^9¿-
80
'64
' 45-Ю0
,12|.15 [.20
:50' '
16x16x1
080 100 125 150
200,500
, J54„
16У4
56 V
Г
^ 14%"
*
i'Jl
14У4
’ropane (3as
100
'so'
45-100
16x18x1
BD
208 244
20У4 24У4
-- -28
' ¿0*
18%
22%
18%
22%
18% "
4%
18%
22%“
125
150
loó
50
18>
floor
OPENING
ESP — External Static Pressure
*Add 1-1/4 in when installed on combustible flooring with non
combustible base
fAdd 18 1/2 in. when installed with 28AE900051 cooling coil
plenum; 22 1/2 in when installed with 28AE900061 plenum
(series 200 and 500 units only)
t Ratings shown for elevations up to 2000 ft For elevations above
2000 ft, deduct 4% of input capacity for each 1000 ft above sea
level
**Air temp rise may be calculated using the following formula:
At =
0 24 X specific wt of air x 60 x cfm
bonnet capacity
At
tf58BB units use throwaway filters; 58BD units use permanent
cleanable filters
(s)(?) Сягг!яг Piirnnratinn 1Q79
______
1 08 x cfm
bonnet capacity_____________
AIR FLOW
¡SERVICE aEARANCE
58BB,BD
NOTE; Aiiow safety ciesrance of 1 in. from sdes, top, and
type B vent; 6 in. from unlisted vent; 1 in. at rear.
Fig. 1 — Dimensions
Furnaces may be matched with certain 28
Series cooling coils to form combination heating/
cooling systems (see Table 3) and employed with
humidifiers and electronic air cleaners to form
complete controlled-environment systems.
. COD D D ГЛ OO I
Table 2 — Blower Data
BLOWER
FURNACE 58
SERIES
MOTOR
Nom Size (in.)
Hp
PPD
BL
BMPS*
ESP (in. wg)t
Air Delivery (max cfm)1
BL — Belt Length
BMPS — Blower Motor Pulley Setting (turns open from closed position)
ESP — External Static Pressure
PPD — Pulley Pitch Diameter (range 2.1 — 2 9 in )
100,400
.20
730"
080
9x8
„.30
650
BB DIRECT DRIVE
200,500100,400
J0x8
.20
1100501020
20
890'
9x8
Ve
100120
200,500100,400
J0x8
V3
.20
.20
1180
.50
1080
1070
*Do not close blower motor pulley beyond setting shown
fFilter in place
:fWith motor set at "High" speed
NOTE; Referto Application Data literature for fan performance curves.
_^0
760
9xj0
Ve
.30
920
200,500
jo>i!0
V3
.50
.20
1250
1200
080,100
10x8
"36"
.20
980 1120
BD BELT DRIVE
200,500
12x9
^ Al
.20.50
.50
260 1380
125150
J2xU
^ 1
42
" "41 ‘
_4_
.20
1620 1800
J„„
.50
Table 3 — Furnace-Coil-Plenum Combinations
FURNACE
58BB080,
58BB100,
58BB120
58BD080,
58BD100
58BD125
58BD150
NOTE; Adapters not required.
28AF002
28AE,AF003
28AE,AF004
28AF002
28AE,AF003
28AE,AF004
28AE,AF003
28AE,AF004
28AE,AF005
28AE,AF005
28AE006
COIL
PLENUM
28AE900051
28AE900051
28AE900051
28AE900061
Series 100 and 200 units are tested and
approved for use with natural gas. Series 400 and
500 are factory built and approved for use with
100% propane gas. Firing of these units with any
other gas or mixture is not approved.
Furnaces are shipped fully assembled, including
built-in draft diverters. Heating/cooling models are
equipped with a printed circuit control center,
which provides a central control connection point
for furnace components and field-added acces
sories. All internal electric and gas controls are
factory assembled and wired.
When unpacking unit, should any in-transit
damage be observed, file claim with transportation
agency.
This publication covers furnace and non
combustible base installation. It also shows ter
minal connections used for wiring accessories to
furnace. For accessory installation details, refer to
applicable installation literature.
INSTALLATION
Location Selection
When selecting a location for the furnace,
observe the following:
1. Install furnace close to chimney and as central
ized as possible with respect to distribution
system.
2. Locate cooling coil (if used) downstream from
furnace.
3. Ensure adequate door clearance for service
access.
4. Ensure adequate ventilation. (See Combustion
Air.)
5. Follow local and national utility codes.
a. Allow safety clearance of 1 in. from sides,
top and type B vent; 6 in. from unlisted
vent; 0 in. at rear.
b. Provide service clearance of 30 in. at front
of unit.
c. Downflow furnaces are not approved for
installation directly on combustible floors.
Unless furnace is set on a concrete slab
floor, use of a noncombustible base is
required. (See Fig. 2.) Noncombustible base
is available as an accessory package. If
furnace is combined with a cooling coil,
plenum can serve as the noncombustible
base.
d. If furnace is to be installed on the first floor
of a house built over a crawl space, make
sure that unit and noncombustible base (if
required) will rest on supported floor joists.
Otherwise, vibrations could be set up, result
ing in unnecessary and undesirable noises.
e. Make sure that a positive air seal is made on
all four sides of the furnace.
Fig. 2 — Installation of Noncombustible Base On
Combustible Flooring
f. If cooling coil is to be used with furnace,
provision should be made downstream of
the coil to collect and drain any condensate
that may blow off the coil.
^ g. Consult NFPA No. 54; Installation of Gas
Appliances Gas Piping 1969.
Installation Procedures
Install ductwork, filters, and vents; complete
external piping and wiring; and provide for com
bustion and recirculating air.
Fig. 3 - Installation of Filters in Return Air Duct
DUCTWORK RECOMMENDATIONS
1. Install locking-type dampers in all branch or
individual ducts to balance out system.
2. Use tapered fittings or starter collars between
ducts and plenum.
3. Use flexible duct connection (asbestos cloth)
between furnace and discharge plenum.
4. Install acoustical insulation in warm air plenum;
install sound traps in short run ducts.
5. Run return air connections under floor or I'un
full size return from space outside enclosed
area. If outdoor air is used, combination of
outdoor and return air requires duct design and
diverting dampers so installed that volume of
circulating air entering furnace cannot be re
duced or restricted below that which would
normally enter thru circulating air intake of
furnace
Table 4 — Pipe Sizing*, Capacity For Natural Gas,
Cu Ft/Hr
PIPE SIZE
10
1329273635650
’4
1
U/4
*Based on pressure drop of 0 3 in. wg, 0 6 sp gr gas
fWithout elbows
NOTE: For pipe sizing capacity for LP gases, refer to NFPA No. 54
278
520
1050 730590
X — J
PIPE
LENGTH (ft)t
203040
190
152 130
350 285245
500
___
60
50
1151059690
215195 180170
440 400370
70
46
_-,J
vent outlet terminates in an approved cap with
a venting capacity not less than that of the
vent. (See Table 1 for vent sizes.)
80
43
350
FILTERS — Filters are shipped from factory in
blower compartment of furnace. (See Fig. 3.) To
gain access, remove top front panel and filter
compartment doors located at right- and left-hand
sides of vent. Install by raising filters above rightand left-hand side of blower and positioning on
filter rack as shown in Fig. 3. As an aid in filter
removal, an access panel could be field fabricated
in the front of the return air supply plenum.
VENTS — Vent furnace to permanent chimney or
thru roof with vent of approved design. (Type B
vent is recommended.) Observe local ordinances.
1. Size flue pipe connections same as furnace
vent connection. (See Fig. 1 and Table 1.)
2. Run pipe as directly as possible with minimum
number of turns.
3. Maintain minimum pitch of 1/4 in. per linear
ft on horizontal runs. Pitch should not exceed
75% of vertical vent.
4. Maintain minimum angle of 60 degrees from
vertical for vent pipe crossovers in attic.
5. Rigidly support pipe with hangers or straps.
6. Do not connect into a chimney serving an
open fireplace.
7. If chimney is used, total equivalent straight
length of flue piping between furnace and flue
pipe connection at chimney must not be
greater than 75% of vertical height of chimney
above flue pipe connection.
8. Install flue pipe to extend thru chimney wall
but not beyond inside wall of flue.
9. Minimum vertical stack height is 5 ft. Extend
flue pipe at least 3 ft above roof and 2 ft above
any object within a 15-ft radius. Ensure that
10. Insulate flue pipe where it passes near com
bustible material. Underwriter’s Laboratories
(UL) require that uninsulated flue pipe be
installed with a minimum clearance of 6 in.
from combustible materials. Vent piping,
which meets with National Board of Fire
Underwriter’s Specifications for type B vents,
may be installed with a clearance of 1 in. from
combustible materials.
If other gas appliances are vented into
common flue, flue area must equal largest vent area
plus one-half total areas of other vent conneetors.
GAS PIPING — Install piping per national and local
codes, and NFPA No. 54.
1. Furnish gas line from main gas supply to
furnace.
2. Size supply pipe per volume of gas used and
allowable pressure drop. (See Table 4.) Supply
pipe size must at least equal that of furnace gas
connection.
■ 3. Refer to NFPA No. 54 for additional suggested
methods of piping.
a. Install drop pipe adjacent to, but not in
front of furnace.
b. Install manual shutoff valve on gas piping
per local codes.
c. Install tee in pipe at same elevation as gas
inlet connection to unit; provide ground
joint union between tee and furnace
controls.
d. Extend drip leg and cap it.
e. Test for pressure and leaks.
CAUTION: Never rise open flame for testjxig.
Loading...
+ 7 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.