Carrier 580PB User Manual

Page 1
58ED,PB
HEATING A COOLING
Horizontal Gas-Fired Furnaces
Installation, Start-Up and Service Instructions
CONTENTS
Page
SAFETY CONSIDERATIONS
GENERAL .................................................................1
INSTALLATION ....................................................2-13
Step 1 — Select Location ...........................................2
Step 2 — Provide Air For Combustion and
Ventilation..............................................................3
Step 3 — Assemble Furnace ......................................3
• DRAFT HOOD
Step 4 — Size Ductwork
Step 5 — Vent Furnace ..............................................4
• MASONRY CHIMNEY
• TYPE B-1 VENT
• ATTIC INSTALLATION
Step 6 — Connect Gas Piping
• BURNER ORIFICES
Step 7 — Make Electrical Connections Step 8 — Install Filters
.............................................
Step 9 — Reverse Components
(if required) ........................................................ 11-13
START-UP AND ADJUSTMENT ........................13-15
SERVICE AND MAINTENANCE
SAFETY CONSIDERATIONS
These instructions are intended for use by qualified personnel who have been trained in installing this type of furnace. Installation of this furnace by an unqualified person may lead to equipment damage and/or a hazardous condition which may lead to personal injury
GENERAL
This furnace is designed for use with either natural or liquefied petroleum (propane) gases and has been design certified by the American Gas Association It is shipped as a packaged unit, complete with burners and controls, and requires only a line voltage ( 115-v) connection to the
................................
...........................................
...................................
.....................
.......................
II
15-17
Fig. 1 — Furnace Dimensions
(Modei 58ED Shown)
junction box and a thermostat hookup as shown in the wiring diagram. The design of the furnace is such that the burners, controls and flue outlet can be assembled
on the same side to facilitate servicing for installations where only limited access to the unit is available. (See Step 9 — Reverse Components.) The 58ED furnace (with intermittent electronic ignition) is shown in Fig. I. This furnace has been designed to interface with split­system cooling equipment (approved by UL) to provide year-round air conditioning. The blower is sized for both heating and cooling. Table I provides physical data and dimensions of the furnaces, and Table 2 pro vides airflow data.
The furnace installation must conform with local building codes or, in the absence of local codes, with the National Fuel Gas Code, NFPA54-I984/ANSI Z223.I-
I984 For complete information on installation standards consult the National Fuel Gas Code, obtainable at a nominal cost from the National Fire Protection Associa tion, Inc., Batterymarch Park, Quincy MA 02269 or the

Table 1 — Physical Data and Dimensions

SIZE 58ED/PB FURNACE
INPUT (1000 Btuh)*
HEATING CAPACITY (1000 Btuh)t
Non-Weatherized
Indoor TEMPERATURE RISE (F) DIMENSIONS (ft-ln.)
NUMBER OF BURNERS
SHIPPING WEIGHT (lb)
‘Ratings shown are for elevations up to 2000 ft above sea level.
For elevations above 2000 ft, deduct 4% of input capacity for
each 1000 ft above sea level
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obiigations.
Book|1 |4 PC101 Catalog No 535-834 Printed in U S A Form 58ED,PB-1SI Pg 1 6-85 Replaces: 58PB-1 SI Tab |6a|8a
Length A
Width B
Duct Opening C
Vent Diameter D
E F G
OSO
50
38 39
35-65
4-6
1- V/2
0-11 Ye 0-11 Ye 1-ЗУв
0-4
1- 8%
0- 8%
1-4
1- 9У4 1- 9'/4
1- 7%
2
155
For replacement items use Carrier Specified Parts.
075 100
75 100 125 140
56 58 77
40-70 40-70
4-6
1-
0-4 0-5
1- 8У4 1-8У4
0- 8% 0-6У8
1-4
1- 7У4 1-7У4 1- 5У4
3
165 190
fDetermined as per U S Government standard tests
75
4-6 1-5
1-4
1-9У4
4
125
94 105 96
40-70
4-8
1- 8Уг 2-0
1- 6Ув 1-10Ув
0-5 0-6 1- 8У4 0- 9У2 0- 9Уг 1- 5У4
1-11 '/4
5
230 250
140
108
40-70
4-8
1- 7У4 1- 5У4
1-11 '/4
1- 5'/4
6
Page 2
58ED,PB
HEATING A COOLING
American Gas Association, 1515 Wilson Boulevard, Arlington, VA 22209.

A WARNING

The furnace cabinet must have an uninterrupted or unbroken electrical ground to minimize personal
injury if an electrical fault should occur. The unit must also be electrically grounded in accordance with local codes, with the National Electrical Codes ANSl/NFPA No. 70-1984 or the latest edition. Do not use gas piping as an electrical ground.

INSTALLATION

Step 1 — Select Location — This furnace may be
located in an attic, basement crawl space, alcove or suspended from the ceiling of a utility room or basement. As shown in Table 3, the minimum clearances, or greater, must be provided between the furnace and adjacent construction.

A WARNING

Failure to comply with all the recommended clear
ances will result in a fire hazard.
If a furnace is to be installed in a residential garage, it must be installed so the burners and the ignition source are located not less than 18 in. above the floor and the furnace must be located or protected to avoid physical damage by vehicles.
The furnace should be located as close to the chimney as possible in order to keep vent connections as short and direct as possible. The furnace should also be located as near to the center of the air distribution as possible, and should be mounted level.
Horizontal Gas-Fired Furnaces
Since this furnace is suitable for attic installation, it must not be installed directly on carpeting, tile or other combustible material. Line contact is only permissible between lines formed by the intersection of the furnace top and two sides and the building joists, studs or framing. See Fig. 2
A clearance of at least 30 in. should be provided at the
front of the furnace for combustion air and servicing.
For attic installations, the passageway and service area adjacent to the furnace should have a floor installed. The areas adjacent to the combustion air openings must be covered with fireproof board or sheet metal extending a minimum of 12 in. from the furnace. See Fig. 2.
If the furnace is to be installed in a crawl space, consult
local codes. Use of a concrete pad one to 2 in. thick is recommended.
If the furnace is to be suspended from the ceiling, it is
necessary to use steel pipe straps around each end of the furnace. These straps should be attached to the furnace with sheet metal screws and bolted to the rafters. The furnace may also be suspended by an angle iron frame bolted to the rafters.

A WARNING

Do not place combustible material on or against
the draft hood.

A WARNING

The furnace is not watertight and is not designated
for outdoor installation.
Table 2 — Blower Data (Direct Drive)
FURNACE 58ED/PB
SERiES (15th Digit
of Model No.)
BLOWER SIZE (in) DXW
MOTOR HP (PSC)
SPEED TAP
WIRE COLOR
BLOWER RPM
EXTERNAL STATIC
PRESSURE (in wg)
A
10x4 10x4
%
Hi
Lo Red BIk
830 1070
20 50
930
765
050
B c
10x6 10x6
Va
Lo Hi Red BIk
1080 700 920 1020
760
50 20
20
1220 790 1165
735
075 100
A B c A B c C
10x6 10x6
'/3 %
Lo Lo Red Red BIk Blu BIk Blu Red
Va
Hi Med Hi
790
20 50 20 50 20 20
1130 995 1260 1090
'/3
Med Lo
1060 820 860
10x8
10x8 10x8
Va
'4
Hi
Med Hi Med
BIk Blu
990 730 1050
50 20 50
AIRFLOW (Cfm)
1290 1090 1530 1360 2010 I860
1310
'/3
BIk Blu
840 1070
20 50 20 50
Hi BIk
125 140
D B c
12 X 9
'h
Med Hi Blu BIk
12x9 12 X 12 12x12
3/4
Med Hi
820
Blu BIk Blu BIk Blu
920
1000
20 50 20 50 20
1810
2115
’/2
Med
1070 970
2100 1930
3/4
Hi Med
980 780
2350 2100

A WARNING

When operating furnace in heating mode, the static pressure and the temperature rise (outlet air temperature minus room temperature) must be within those limits specified on the AGA rating plate.
Book|1 |4 PC101 Catalog No 535-834 Printed in U S A Form 58ED.PB-1 SI Pg 2 6-85 Replaces: 58PB-1 SI Tab I6al8a
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without Incurring obligations.
For replacement Items use Carrier Specified Parts
Page 3
58ED,PB
HEATING A COOLING
Table 3 — Alcove Clearances (In.)
TOP
8 6
’With draft hood in front of furnace
tWith draft hood on back of furnace
SIDES
BACK
8*
18t
DRAFT
HOOD
Line
Contact
SINGLE
WALL VENT
6
Step 2 — Provide Air For Combustion and
Ventilation — For an unconfined space (more than
50 cu ft of volume per 1,000 Btu of aggregate input rating
of all appliances installed in that space) such as a base ment or attic, infiltration air is normally adequate to provide air for combustion, ventilation and dilution of flue gases. Adjoining rooms may be included if there are no doors between the rooms
For a confined space, where air is taken from an interior space, 2 permanent openings of equal area are required. One opening must be within 12 in. of the ceiling and the other must be within 12 in. of the floor. Each opening must have a free area of at least 1 sq in. per
1000 Btu of total input rating but not less than 100 sq
inches.
If the outside air is supplied to a confined space, then
the 2 openings must be equal and located as above and the free area of each must be:
Horizontal Gas-Fired Furnaces

A CAUTION

Whenever this furnace is installed in an area along with one or more gas appliances, the total Btu input of all appliances must be included when determining the free area requirements for combustion and ventilation air openings.
When ducts are used, they must be of the same cross-
sectional area as the free area of the openings to which they connect. The minimum dimension of rectangular air ducts must not be less than 3 inches.
The free area through a design of louver or grille should be used in calculating the size opening required to provide the free area specified. If the design and free
area is not known, it may be assumed that wood louvers
have 20-25% free area and metal louvers and grilles have 60-75% free area. Screens used must not be smaller than
1/4 in. mesh and louvers shall be fixed in the open posi tion or interlocked with the equipment so that they are opened automatically during equipment operation.

A WARNING

Do not block the combustion air openings in the
furnace. Any blockage will result in improper com
bustion and may result in a fire hazard or unsafe
condition
1. Onesqin. per 4,000 Btu of total input rating when the air is directly communicated from the outdoors.
2. One sq in. per 4,000 Btu of total input rating when the air is brought in through vertical ducts.
3 One sq in. per 2,000 Btu of total input rating when the
air is transferred through horizontal ducts.
LINE CONTACT ONLY PERMISSIBLE BETWEEN TOP CORNERS OF FURNACE AND BUILDING JOISTS.
STUDS OR FRAMING.
KEEP ALL INSULATING MATERIAL CLEAR OF FURNACE. INSULATING MATERIALS MAY BE COMBUSTIBLE.
METAL EXTENDING 12 IN, FROM UNDER COMBUSTION CHAMBER
Fig. 2 — Attic Installation Showing Point Contact

A CAUTION

For an attic installation, keep insulation 12 in. or more away from any furnace openings. Some types of insulating materials may be combustible.
Step 3 — Assemble Furnace — The burner and
controls are shipped in place and the furnace high- and low-voltage wiring is complete to facilitate the installa tion. Low-voltage wiring to the field-supplied thermostat
is necessary to complete the unit wiring (see Step 7 — Make Electrical Connections).
In order to accommodate all the possible field installa tions that may exist, the unit is designed so that the gas valve, controls and draft hood assembly may be assembled on either side of the furnace. Refer to Com ponent Reversal section for details. After reversal (if required), return to this section.

A CAUTION

Remove cardboard shipping insert from eye of the blower scroll before energizing blower.
DRAFT HOOD — In order to save shipping space the
draft hood is shipped disassembled (on models 125 and
140 the left panel is spotwelded in place). Remove the
draft hood components from the blower compartment
(on some models the panels might be packed outside the
furnace jacket). On the models 50, 75 and 100 there will
Book|1 |4 PC101 Catalog No 535-834 PrintedinUSA Form 58ED.PB-1 SI Pg 3 6-85 Replaces: 58PB-1SI Tab l6a|8a
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obiigations.
For replacement items use Carrier Specified Parts
Page 4
r
58ED,PB
HEATING & COOLING
be a wrapper, 2 panels (one marked with an “R”, the other marked with an “L”) and a hardware package.
Refer to Fig 3 to assemble the draft hood. Depending on the model, one or both panels are slid into the proper location in order to line up the 4 mounting holes. Secure the panel(s) with the screws provided
After completing the draft hood assembly, it is advisable to check the overall size with Table 4.
Install the draft hood over the selected flue opening by placing it on top of the draft hood clip and securing it to the furnace jacket with screws provided. Adhere to the necessary clearances as shown in Table 3.
Table 4 — Draft Hood Dimensions (in.)
FURNACE
58ED/PB
050 075 100 125 140
LENGTH
16 16
16 10 17'/4 17'/4
HEIGHT
10 10
10 10
DEPTH
8 8 8 8 8
PIPE DIA.
4 4 5 5 6
Step 4 — Size Ductwork— Proper ductwork sizing
is necessary to ensure satisfactory heating operation Ductwork should be in accordance with the latest editions of NFPA-90A (Air Conditioning Systems) and NFPA-
90 B(Warm Air Heating and Air Conditioning Systems).
Follow these recommendations when installingductwork:
1. Install locking-type dampers in all branch or indi vidual ducts to balance out system. Dampers should be adjusted to impose the proper static pressure at
the outlet of the furnace.
2 Noncombustible flexible duct connectors are recom
mended to connect both the supply and return ducts
to the furnace
3 In cases where the return air grille is located close to
the fan inlet, there should be at least one 90 degree air
turn between fan and inlet grille. Further reduction
in sound can be accomplished by installing acoustical air turning vanes and/ or lining the inside of duct with acoustical material.
Horizontal Gas-Fired Furnaces
When installing the furnace with cooling equipment for year-round operation, the following recommenda tions should be followed for series or parallel airflow:
1. In series airflow applications, the coil is mounted after the furnace in an enclosure in the supply air-
stream. The furnace blower is used for both heating
and cooling airflow.

A WARNING

The coil must be installed on the air discharge
side of the furnace. U nder no circumstance should the airflow be such that cooled, conditioned air can pass over the furnace heat exchanger. This causes condensation in the heat exchanger and possibly early failure due to rust.
2. In parallel flow installation, dampers must be pro vided to direct air over the furnace heat exchanger
when heat is desired and over the cooling coil when cooling is desired.
IMPORTANT: The dampers should be adequate to prevent cooled air from entering the furnace, and if manually operated, must be equipped with means to prevent operation of either the cooling unit or furnace unless the damper is in the full cool or heat position.
Step 5 — Vent Furnace — This furnace must be

A CAUTION

Air openings in burner cover, return air grilles, and warm air registers must not be obstructed.

A WARNING

When supply ducts carry air circulated by the furnace to areas outside the spaces containing the furnace, return air shall also be handled by a duct sealed to the furnace casing and terminating outside the space containing the furnace.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book|1 14 PCiOl Catalog No 535-834 Printed in U S A Form 58ED,PB-1SI Pg4 6-85 Replaces: 58PB-1SI Tab l6al8a
For replacement items use Carrier Specified Parts.
vented to the outside and in accordance with local codes or requirements of the local utility. In the absence of local codes, venting should conform to the requirements of the National Fuel Gas Code (NFPA 54-1984/ANSI Z223.1-1984 Part 7).
For additional venting information, refer to ANSI/
NFPA 211 Chimneys, Fireplaces, Vents and Solid Fuel
Burning Appliances.
This furnace must not be vented into a solid fuel burning chimney. The chimney must be checked for deterioration. Correct the condition before venting the furnace into the chimney. The chimney must be
properly lined and sized per National Fuel Gas Code
(ANSI Z223.1-1984/NFPA-54, 1984).
Page 5
58ED,PB
HEATING A COOLING
MASONRY CHIMNEY — This furnace can be vented into an existing masonry chimney. Normal connections to a chimney are made using single wall pipe; however, single wall pipe is not approved to pass through any attic, inside wall or concealed space or through any floor. For further information, consult venting section of National
Fuel Gas Code. TYPE B-1 VENT — The furnace is also approved for
use with a Type B-1 vent that terminates through the roof (horizontal venting through an outside wall is not approved). The vent must be terminated with a listed cap or roof assembly. This venting must be installed in accordance with the vent manufacturer’s instructions and be in accordance with all local codes.
ATTIC INSTALLATION — Attic and/or National Fuel
Gas installations require the use of Type B or Type L vent
material The following requirements are provided for
venting system;
1. Ensure the chimney flue is clear of any dirt or debris.
2. Ensure the chimney is not serving an open fireplace.
3. Never reduce the pipe size below the outlet size of the furnace.
GAS
SUPPLY
Horizontal Gas-Fired Furnaces
4. All pipe should be supported using the proper clamps and/ or straps
5. All horizontal runs of pipe must have an upward slope of 1/4 in. per foot.
6. All runs of pipe should be as short as possible with as few turns as possible.
7. Seams must be tightly joined and checked for leaks.
8 The flue pipe must not extend into the chimney,
but be flush with the inside chimney wall.
9. The chimney or gas vent must extend 3 ft above the highest point where it passes through a roof of a building and at least 2 ft higher than any portion of a building within a horizontal distance of 10 feet. It shall also extend at least 5 ft above the highest connected equipment flue collar.
10 Check local codes for any variance.
Step 6 — Connect Gas Piping — Install gas piping
to provide a supply of gas sufficient to meet the maximum demand without undue loss of pressure between the gas
meter and the furnace. The gas line to the furnace should be a separate line direct from the meter, unless the existing gas line is of ample capacity. Refer to Table 5 for sizing gas piping.
Use a joint compound (pipe dope) resistant to the action of liquefied petroleum gases or to any other chemical constituents of the gases to be conducted through the piping.
Before any system of gas piping is finally put into
service, it should be carefully tested to determine if it is
gas tight. The piping must withstand a pressure of 6 in. Hg for a period of 10 minutes or as required by local authority.
note:
LOCATE MANUAL SHUTOFF VALVE AS REQUIRED BY THE LOCAL AUTHORITY OR CODE IN THE ABSENCE OF SUCH A CODE, LOCATE THE MANUAL MAIN FROM THE FLOOR
FIELD SUPPLIED MAIN MANUAL SHUTOFF VALVE
FURNACE GAS VALVE -
Tl
CD
r'l
PIPE CAP MINIMUM OF I IN. FROM FLOOR TO PERMIT REMOVAL
GAS PIPE LAYOUT AFTER REVERSING COMPONENTS
(SEE NOTE)
r
Lj

Fig. 4 — Gas Pipe Layout

A WARNING

The furnace and its individual shutoff valve must be disconnected from the gas supply system during any pressure testing of that system at test pressures in excess of 1 / 2 psig. The furnace must be isolated from the gas supply piping system at pressures equal to or less than 1/2 psig.
GAS
SUPPLY
The recommended method for installing the gas piping to the furnace is shown in Fig. 4. Also shown is correct piping if the gas valve and controls have been reversed in the field.
Table 5 — Gas Pipe Sizing (Cu Ft of Gas per Hour)'*
)
PIPE (ft)
10 20 30 40 50 75
100
150
* Based on gas pressures of 0 5 psig or less and pressure drop of
0 3 in wg and 0 60 specific gravity gas
DIAMETER OF PIPE — IPS (in.)
Vr % 1 IV4
132
278
92
190
73
152
63
130
115
— —
_
520 1050 350 730 285 590 245 500 215 440
93 175 360
150 305
79 64 120 250
IV2
1600 1100
890 760 670 545 460 380
Manufacturer reserves the right to discontinue, or change at any time, specitications or designs without notice and without incurring obligations.
Book|1 |4 PC101 Catalog No 535-834 PrintedinUSA Form 58ED.PB-1SI Pg5 6-85 Replaces; 58PB-1 SI
Tab l6a|8a
For replacement items use Carrier Specified Parts
Page 6
58ED,PB
HEATING & COOLING
Support all gas piping independent of the furnace. For propane gas, a tank regulator is required to reduce supply pressure to 12-13in.wg. For manifold pressure, see Table 6.
Check all piping for leaks using soapy water and a brush.

A CAUTION

Never use an open flame when testing for gas leaks!
Use a soap and water solution
A 1/8 in. NPT plugged tap accessible for test gage
connection must be installed immediately upstream of
the gas supply connection to the furnace if one is not supplied on gas valve.
BURNER ORIFICES — The furnace is supplied with standard orifices for the gas shown on the rating plate. Table 6 shows combinations of heating values and specific gravities for various fuels, from which proper input may be obtained
Regardless of the type of gas used, when installation is at an elevation of 2000 ft or more above sea level, orifices may need to be changed, depending on local gas value. For operation at elevations above 2000 ft, input ratings should be reduced at the rates of 4% for each 1000 ft
above sea level. To change orifices, remove the burner removal cover on the gas valve side of unit. Remove
manifold locking device and slide the manifold tray back
until each burner is clear of heat exchanger tube. See
Fig. 5 Pull the manifold tray forward until burners are
clear of furnace. Remove the locking device from each burner and pull each burner back off the orifice.

A CAUTION

Take care when removing the pilot burner not to
damage the pilot gas line.
Horizontal Gas-Fired Furnaces
Fig. 5 — Burners Removed From Furnace
After securing the manifold assembly, replace all other components and/or wiring, being sure that all connec tions and screws are tightened.

A WARNING

If it is necessary to adjust the manifold pressure more than 0.3 in. wg, the orifices must be changed

A WARNING

Never set the furnace input rate above that shown
on rating plate.
Use the following formula to determine the furnace
input rate:
After removing orifices, ensure the new orifiees are
Input (Btuh) = Heating Value of Gas (Btu/cu ft)
seated properly and tightened. Replace burners correctly and secure with the locking device before replacing and securing the manifold assembly.
X 7200 sec/2 hr
Time in sec for 2 cu ft of gas
Example. If the heating value of natural gas is 1015
_______
______
Btu/cu ft and it takes 75 seconds to burn 2cuft of gas,

A CAUTION

The manifold must be properly positioned in order to engage the locking mechanism
then: Input (Btuh) = 1015 Btu/cu ft X 7200 sec/2 hr
75 sec/2 cu ft
Input = 97,440 Btuh
When checking rate, make sure all other gas appliances
are shut off except for pilot burners.
Table 6 — Burner Orifices

Step 7 — Make Electrical Connections — The

control system depends on the correct polarity of the
TYPE OF GAS
(Heating Value — SP GR)
BTU PER CU FT
NATURAL — MANIFOLD PRESS. 3.5 in. wg
800 — 0.6
900 — 0.6 1000 — 0.6 1100 — 0.6
PROPANE — MANIFOLD PRESS. 10 in. wg
2500 — 1.53
Book|1 |4 PC101 Catalog No 535-834 Printed in U S A Form 58ED.PB-1 SI Pg6 6-85 Replaces: 58PB-1SI Tab l6al8a
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
ORIFICE SIZE
(Drill No.)
43 44 45 46
54
For replacement items use Carrier Specified Parts
power supply. Connect field power wiring and field ground wire as shown in Fig. 6 and 7.

A WARNING

The unit cabinet must have a separate uninterrupted or unbroken electrical ground to minimize personal injury if an electrical fault should occur.
Page 7
“ü
o
(O
O 3
FIELD POWER SUPPLY C115-1-60)
CN0TE5 #2,3 g 4)
SCHEMATIC DIAGRAM
ORN
WHT
<i~I <ri^
ic
9 ij> o Cj)
PI
BLK
GRN
YEL
m
1
GV
(NOTES #2, 3 g 4)
GROUND
COMPONENT ARRANGEMENT
YEL
TB
MLS
g
FS
WHT
IFR
DS
TRAN
WHT
C--BLK-
GRN
RED-i
FM
BLK
BLU WHT
^ o>.1/ 3
Q. sS
« d' Ä
i c 3
E CO i® = > 45
<D ^
3 O
« 2.
c S:
w o
O 0)
S "n 5’
q o 3
0 5*"
-» 3 o
W C71
•O 05 Q.
g m ®
2; O 2.
<5' <o
m 3
T3 r «
0) _L <
2. 05 S.
"D
CD
THERMOSTAT g SUB-BASE
(NOTE #1)
— Capacitor
Cap. CC
— Cooling Compensator
DS — Door Switch IC — Ignition Control FM
— Fan Motor
FS — Fan Switch
GV
— Automatic Gas Valve
HA — Heat Anticipator
— Indoor Fan Relay
IFR
— Limit Switch
LS
— Mam Limit Switch
MLS
— Outdoor Relay
OR
P — Pilot
— Pilot Igniter
PI
— Spark Igniter
SI
— Terminal Board
TB
NOTES;
1 USE THERMOSTAT PART NO. HH01PD042 WITH SUB-BASE
2. USE COPPER CONDUCTORS ONLY.
3. TO BE WIRED IN ACCORDANCE WITH NATIONAL ELECTRIC
4 MAKE FIELD POWER SUPPLY CONECTIONS TO BLACK AND
5. IF ANY OF THE ORIGINAL WIRE AS SUPPLIED WITH THE
6. IMPORTANT - UNIT HAS 5866 CONTROL, IF PILOT
7 DO NOT ATTEMPT TO LIGHT THE FURNACE MANUALLY
8. OR - OUTDOOR RELAY SUPPLIED WITH CONDENSING UNIT.

Fig. 6 — 58ED Furnace Wiring Label — Heat/Cool

LEGEND (FIG. 6 and 7)
Tran — Transformer
CommoH Potential (Not Actual Wiring) _______Fieid Power Wiring —Field Ground Wiring
______
Field Control Wiring
PART NO. HH93RZ03G OR ENG. EQUIVALENT.
(N.E.C ) AND LOCAL CODES. UNIT MUST BE GROUNDED
WHITE WIRES CAPRED WITH ORANGE WIRE NUTS.
FURNACE MUST BE REPLACED, IT MUST BE REPLACED WITH WIRING MATERIAL HAVING A TEMPERATURE RATING OF AT LEAST 105°C AND BE A MINIMUM OF 16 GA.AWG.
FLAME 15 NOT ESTABLI5HED, CONTROL WILL SHUT DOWN THE SYSTEM. TO INITIATE A RE-IGNITION TRIAL,TURN DOWN THERMOSTAT TO LOWEST SETTING, WAIT AT LEAST 60 SECONDS g THEN RESET THERMOSTAT TO ABOVE TEMP
o Component Connection (Unmarked)
O Component Connection (Marked)
Field Splice —O— Junction —•— Junction Thermostat to Subbase
T
o
Ñ'
o
3
O
fi)
0)
(D
Q.

T| cn

C 00
D o
c/) W
Page 8
58ED,PB
HEATING & COOLING
Horizontal Gas-Fired Furnaces
CC LU
I— O
o z
UJ 3
¿iJ
< C D O O <
ox cr 3 < Q 3
cn C 3 O 2
_( o
c r
<D
C L U
H- cn cn a: i:u
:3c 3 LU •
o cn
2 L U
< o
Q O
cr. o
o
O -j
a. cn OD
CD I—
3
o
2
z c
o cr o o
cr :3c
2
3
Ln Q
LU
cr Cl
3 1 — < 2 X C
Q L U 3 ^
' n. ■< <C C 3 I
cn O L—
. 2 >— <
‘ 3 o
O ^ <C I— >
< L i_ t j_ — 1 z < O
O o I
O o I
Ln < o LH <D
3 2 cn
' cr 3
• 223
3 q : Q
) h- 3 2
•3X0
>- h- o
I 3 3
I X o o
h- Q 3
o
CO
0)
X
0)
n
(0
u
O)
o
(0
w 3
Li.
Q
LU
00
in
O
CO
Q>
C
o
d)
CTr
CL^r
3
Cno5
crcn
lU K
:3:(M O it
Cl
3
Book 11 |4 PC101 Catalog No 535-834 Printed in U S A Form 58ED,PB-1 SI Pg 8 6-85 Replaces'. 58PB-1 SI Tab I6al8a For replacement items use Carrier Specified Parts
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Page 9
58ED,PB
HEATING & COOLING
Horizontal Gas-Fired Furnaces
o o
0
(0 a>
1
c
0)
SI
(0
-I
O)
c
u
CD
a
oo
lO
d>
a> n>
c
Book 11 14 PC101 Catalog No 535-834 PrintedinUSA Form 58ED,PB-1 SI Pg9 6-85
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obiigations.
Tab !6al8a For replacement items use Carrier Specified Parts
Replaces: 58PB-1SI
Page 10
58ED,PB
HEATING & COOLING
Horizontal Gas-Fired Furnaces
>
C
O
(0
0)
X
0)
n
(0
_l
u>
0)
o
(0
3
u. m
0.
00
IT)
o
d)
Bookll 14 PC101 Catalog No 535-834 Printed in U S A Form 58ED,PB-1Sl Pg 10 6-85 Replaces; 58PB-1 SI Tab l6a l8a For replacement Items use Carrier Specified Parts
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without Incurring obilgations.
Page 11
58ED,PB
HEATING & COOLING
Use only copper wire for 115v supply service to
furnace. When replacing any original wiring, use only
105 C, 16 gage AWG copper wire.
Instructions for wiring the thermostat are packaged with the thermostat (field supplied). Make connections as shown in wiring labels at the 24 v terminal board located on the electrical junction box. When installing accessories to this furnace, follow manufacturer’s instructions included with the accessory Except for thermostat wiring, a minimum of typeT (63 F rise) must be used.
Step 8 — Install Filters — Filters and racks are
available as accessories. See Fig. 8 for recommended filter size rating and type.
IMPORTANT: All furnaces must be equipped with
a filter.

Step 9 — Reverse Components (if required).

A WARNING

Before proceeding with component reversal, make
sure that all power is turned off upstream of furnace and all gas piping is shut off and disconnected from furnace.

A CAUTION

Before proceeding with field reversing, ensure a correct wiring diagram is available and/or be prepared to mark all wiring as it is disconnected.
Horizontal Gas-Fired Furnaces
All references to left or right side of furnace refer to
the furnace looking at the heat exchanger (supply
air side).
The gas valve, pilot burner components and controls
may be reversed as follows:
1 Loosen burner removal cover screws and remove
both covers
2 Disconnect all wires to gas valve and unplug the
igniter cable from the ignition control (if so equipped).
3. Remove the manifold locking device and slide the burner and manifold assembly back towards the furnace inlet until the burners are clear of the heat exchanger tubes. See Fig. 5.
4. Slide manifold assembly towards the front of furnace .
until it clears the blower deck. NOTE: Keep manifold assembly straight while
removing. If manifold is cocked, then the assembly
will bind in burner box.
5. Place manifold on a work area and disconnect the
pilot tubing and thermocouple, if equipped, from the
valve
6. Using 2 pipe wrenches (one on the gas valve and one on the manifold extension pipe), remove the gas valve
7. Remove the manifold extension pipe from the manifold (it may be necessary to put a pipe wrench on the manifold pipe while turning the extension).
8. Using 2 pipe wrenches (one on the manifold pipe between the pipe cap and burner orifices and one on the pipe cap), remove the pipe cap.
9. Clean the threads on manifold pipes, gas valve and pipe cap of any old pipe dope.
NOTE: Use a joint compound (pipe dope) resistant to the action of liquefied petroleum gases or to any other chemical constituents of the gases to be conducted through the piping.
10. Using a suitable joint compound and 2 pipe wrenches, replace the manifold pipe extension where the pipe cap was. The pipe extension should be tightened and positioned so that it is pointing towards the back of the burners.
11. Using 2 pipe wrenches (one on the manifold exten
sion and the other on the gas valve), tighten gas
INPUT
(iOOO BTUH)
50
75 100 125 20i
140 I5Î
A
(IN)
I4i
I6|
valve to the extension and position the valve so that the manual knob is in the 12 o’clock position
12. Using 2 pipe wrenches (one on the pipe cap and the other on the manifold pipe), tighten the pipe cap to the other end of the manifold pipe
13. Remove the screws holding the pilot bracket to the crossovers of the first 2 burners When removing
pilot assembly, be carelul not to damage the pilot
note;
FILTER RACK TO INLET END OF FURNACE INSTALLED INTO RETURN DUCTWORK.
Fig. 8 — Accessory Filter Rack Assembly
Manulacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book|1 |4 PC 101 Catalog No 535-834 PrintedinUSA Form 58ED,PB-1SI Pgll 6-85 Replaces: 58PB-1SI Tab I6al8a
For replacement items use Carrier Specified Parts
gas tubing and ignition cable (or thermocouple, if so equipped).
NOTE This step is not required foi 050 size, as
there are only 2 burners
Page 12
58ED,PB
HEATING & COOLING
1415With the pilot bracket removed from burners, rebend
the pilot tubing and thermocouple at the second bend per Fig. 10. Make sure there are no kinks in tubing.
Connect the 1/4 in. diameter pilot gas tubing (and the thermocouple, if equipped on standing pilot models) to the gas valve. Be careful not to kink the aluminum tubing.
16. Check the pilot position as shown in Fig. 9 and 10.
17. Standing pilot models only: Mount the pilot bracket on the crossovers of the first 2 burners on the side of manifold where valve is now mounted (Fig. 10). Connect thermocouple and the 1/4 in. diameter pilot gas tubing to gas valve This requires adjust ments to pilot tubing and thermocouple. It is ex tremely important not to kink either the thermo couple or aluminum tubing.
Insert the manifold tray back into the furnace and
18. slide the burners into the heat exchanger tubes. The locking device will not engage unless the manifold is in the correct position.
Lock the manifold in place (on electronic ignition
19. models, be sure the ignition cable or sensing lead is not pinched under the burners).
Remove the junction box cover and disconnect the
20
motor leads.
21. Remove junction box. See Fig. 11. On standing pilot models, remove 2 hole plugs from back side of furnace and then remove junction hox.
IMPORTANT; Pull junction box straight out
from furnace until fan and limit is clear of side
panel.
22. Mount the junction box on the opposite side of furnace. Ensure door switch is kept towards the blower door when mounting junction box
Horizontal Gas-Fired Furnaces
EDGE OF PILOT HOOD TO BE FLUSH TO
NOTE; The fan and limit dial will be upside down when junction box is properly reversed. This does
not affect the operation of fan and limit. Remove the strain relief holding the motor wires,
23
route motor leads under blower, feed wires into back of junction box and snap the strain relief into place.
Reconnect motor leads and replace junction box
24. cover.
Replace hole plugs in openings where fan and limit
25
and motor leads were
26. Remove the draft hood and draft hood support clip
PILOT
TUBE
PILOT ASSEMBLY AS SHIPPED
FROM FACTORY
PILOT ASSEMBLY AFTER FIELD REVERSAL
PILOT LOCATION
Fig. 10 — Pilot Assembly
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obiigations.
Book|1 [4 PC101 Catalog No 535-834 Printed in U S A Form 58ED.PB-1S1 Pg 12 6-85 Replaces: 58PB-1 SI Tab i6al8a
For replacement Items use Carrier Specitied Parts
Page 13
58ED,PB
HEATING & COOLING
27. Remove the flue box cover and flue box cover gasket and remount them where the draft hood was located. See Fig. 12. Do not glue gasket to cover plate.
28. Replace the draft hood support clip and the draft hood where the flue box cover plate was located.
NOTE; All controls, wiring, draft hood and the
AG A lighting instruction plates must be located on the same side of the furnace as the automatic main gas valve. Reattach all wires to gas valve and check against wiring diagram.
29. Elect}onic ignition models only: Reattach all wires to the gas valve and the ignition cable to the ignition control.
Check all wiring against the wiring diagram. Fig. 6 and 7.
30. After the furnace components have been reversed,
return to Step 3, Assemble Furnace Draft Hood and proceed with remainder of installation.
START-UP AND ADJUSTMENT
Standing Pilot Models
OPERATIONAL CHECKOUT — The automatic gas valve controls the flow of gas to both the pilot and main burners. The manual valve built into the automatic valve body has 3 positions- OFF, PILOT, and ON.
SEQUENCE OF OPERATION — The furnace operates
automatically. It is controlled by a thermostat which is
set at the desired temperature. When indoor temperature
/ drops below this setting, the thermostat turns on the
system.
When the thermostat calls for heat, power from the transformer energizes the main gas valve (the pilot must be lit already) and gas flows through the valve to the burners. The pilot flame lights the burners.
A heat sensing switch automatically energizes the blower when heat buildup is sufficient. The air is moved by the blower over the heating element, thus warming it, and it goes through the ducts to room registers.
When the thermostat is satisfied, the circuit is broken,
de-energizing the main gas valve and stopping gas flow
to the main burners.
Horizontal Gas-Fired Furnaces
The blower continues to run until the heat in the heat exchanger is removed and then the sensing switch shuts off the blower.
All forced air furnaces are equipped with a high temperature limit switch which prevents the furnace from overheating. If the furnace overheats for any reason, the high temperature limit opens, breaking the
circuit to the gas valve. The blower motor continues to run. The main burners cycle on limit until the fault is corrected.

A WARNING

If overheating occurs, or if the gas supply fails to shut off, shut off the manual gas valve to the furnace before shutting off the electrical supply.
Electronic Ignition Models
OPERATIONAL CHECKOUT — The automatic gas
valve controls the flow of gas to both the pilot and main
burners. The manual valve built into the automatic valve body has 2 positions: OFF and ON.
SEQUENCE OF OPERATION — The furnace operates
automatically. It is controlled by a thermostat which is
set at the desired temperature. When indoor temperature drops below this setting, the thermostat turns on the system.
When the thermostat calls for heat, power from the
transformer simultaneously energizes the pilot gas valve
(inside the main gas valve) and the spark igniter. After
the pilot flame is established, the electrode ceases to spark and the flame sensing probe acts to energize the main gas valve, permitting gas flow to the burners.
A heat sensing switch automatically energizes the blower when heat buildup is sufficient. The air is moved by the blower over the heating element, thus warming it, and it goes through the ducts to room registers.
When the thermostat is satisfied, the circuit is broken, de-energizing the main gas valve and stopping gas flow to the pilot and main burners. The blower continues to run until the heat in the heat exchanger is removed and then the sensing switch shuts off the blower.
JUNCTION BOX
FLUE BOX COVER (GASKET IS UNDERNEATH)
Fig. 11 — Junction Box
(Model 58ED Shown)
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
BookH 14 PC101 Catalog No 535-834 PrintedinUSA Form 58ED,PB-1SI Pg 13 6-85 Replaces: 58PB-1 SI
Fig. 12 — Flue Box Cover
Page 14
58ED,PB
HEATING & COOLING
All forced air furnaces are equipped with a high temperature limit switch which prevents the furnace from overheating. If the furnace overheats for any reason, the high temperature limit opens, breaking the circuit to the gas valve. The blower motor continues to
run. The main burners cycle on limit until the fault is
corrected.
A WARNING
If overheating occurs, or if the gas supply fails to shut off, shut off the manual gas valve to the furnace before shutting off the electrical supply.
The furnace is equipped with either Honeywell S86E or
S86G intermittent pilot control.
S86E control. If the pilot fails to light, the pilot valve
and spark gap remain energized until there is a successful ignition.
S86G control: If the pilot fails to light, the control
will shut down the system. To initiate a reignition trial, turn down the thermostat to lowest setting, wait at least 60 seconds, and then reset thermostat to a setting above room temperature.
Starting Procedure
STANDING PILOT MODELS
1. Set the manual gas shutoff valve at OFF position. Wait 5 minutes.
2. Be sure all electrical power to furnace is off. 3 Check all wiring using proper wiring diagram on
inside of blower door.
4. Light the pilot by following instructions on lighting
plate. (Main burners should not light.)
a) Remove burner cover.
b) Turn manual gas shutoff valve to PILOT position.
c) Depress dial, light pilot with a match or taper.
Keep dial depressed until pilot remains lit after dial is released (approximately 30-45 seconds). If pilot does not remain lit, repeat operation, allowing a longer period before releasing dial.
d) Replace burner cover.
5. Adjust pilot flame to envelop the thermocouple a distance of 3/8 to 1/2 inch. The adjusting screw for pilot flame is located on main gas control. With standing pilot, rate is approximately 1000 Btuh. See Pig. 13.
Fig. 13 — Pilot Thermocouple or Sensor Position
6. With the pilot lit, set thermostat above room temperature.
7. Turn on power supply to furnace. This energizes gas valve which should click open. The burners should not light.
Horizontal Gas-Fired Furnaces
Open the manual gas valve on the automatic gas valve. Burners should light and remain on.
Check for leaks in manual valve, gas control valve
and gas connections using soap and water solution.

A CAUTION

Never use an open flame when testing for leaks.
Use soap and water solution.
lO. Leave burners on for 15 minutes before making
combustion adjustment
ELECTRONIC IGNITION MODELS
1. Set the manual gas shutoff valve at OFF position. Wait 5 minutes.
2. Be sure all electrical power to furnace is off 3 Check all wiring using proper wiring diagram on
inside of blower door.
4 Set thermostat above room temperature.
5. Turn on power supply to furnace. This energizes the
pilot valve and spark igniter. The burners should not light.
6. Turn dial on gas valve to ON position. The pilot should light. When the sensing probe detects the presence of pilot flame, the control de-energizes spark igniter and energizes main gas valve. Main burners should light and remain on. (If system shuts down on S86G control, a reignition trial is necessary.)
7. Check for leaks in manual valve, gas control valve and gas connections using a soap and water solution.

A CAUTION

Never use an open flame when testing for gas leaks. Use a soap and water solution.
8 Leave burners on for 15 minutes before making a
combustion adjustment.
Combustion Adjustment
ALL FURNACES — A primary air shutter assembly is provided on all furnaces. The shutters are factory set for natural gas furnaces and a closed position for LP gas
furnaces. Readjustment may be required to obtain
optimum setting. Shutters are individual to each burner, so adjustment of the burner flame must be done one burner at a time. See Fig. 14.
Loosen the locking screw and close the air shutter. This should cause the burner flame to glow bright yellow Open the shutter until the flame turns blue. Lock the locking screw. See Fig. 15 for proper flame. Repeat this procedure until all burners are properly adjusted. A visual check of the main burner and pilot flame should be made at the beginning of each heating season.
Safety Pilot Check — For Standing Pilot Models
Only. After operating for 15 minutes, turn the valve to
the OFF position. The pilot switch should snap open between 20 seconds and 3 minutes later. To re-ignite pilot, follow the nameplate instructions.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book|1 |4 PC101 Catalog No 535-834 Printed in U S A Form 58ED,PB-1SI Pg 14 6-85 Replaces: 58PB-1SI Tab |6a|8a
For replacement items use Carrier Specified Parts
Page 15
58ED,PB
HEATING & COOLING
LOCATION OF SHUTTER LOCKING SCREW
SHUTTER ADJUSTING TAB
NOTE; LOOSEN LOCKING SCREW BEFORE ADJUSTING SHUTTER. RETIGHTEN SCREW AFTER FINAL ADJUSTMENTS ARE MADE.
Fig. 14 — Air Shutter Adjustment
Manifold Pressure Adjustment — For natural
gas, best results are obtained with a manifold pressure of
3.0 in. to 3.5 in. wg. Remove pressure tap pipe plug from the gas valve and connect to a water manometer. Measure
gas pressure with the furnace on.
Turn regulator adjusting screw in to increase pressure,
or out to decrease pressure.
For LP gases, a 10 in. wg pressure is required. Input
rate must be maintained at ± 2%.
Fan Adjustment Check — This furnace is equipped
with a 3-speed direct drive motor to deliver a temperature rise within the range specified on the rating plate, between the return and supply plenums at the external duct static pressure noted on the AGA rating plate. Consult the wiring diagram for speed changes on the direct drive motor. Adjust fan speed so that temperature rise is within rating plate specifications.
Fan and Limit Control Check — After the furnace
has been operating for at least 15 minutes, restrict the
return air supply by blocking the filters or closing the return air registers and allow the furnace to shut down on
high limit. The fan must continue to run. Remove the restriction and the burner should come on in a few minutes.
The operational checkout is now complete. Be sure to adjust the thermostat to the desired setting and inform the owner how to operate the furnace system before leaving the jobsite.
Stopping the Furnace— Follow these procedures to
shut down the furnace for the summer, if required.
1. Disconnect electrical power to all accessories.
2. To shut down main burner, turn gas cock dial clock wise to OFF position
3. (Standing pilot models only): To shut down both pilot and main burner, depress dial and turn clockwise to OFF position
4. Turn off all electrical power to furnace.
5. Turn off water supply to humidifier, if so equipped.
Horizontal Gas-Fired Furnaces
Fig. 15 — Burner Flames
SERVICE AND MAINTENANCE

A CAUTION

The ability to properly perform maintenance on this
equipment requires certain mechanical skills and
tools. If you are at all uncertain, contact your Carrier
dealer for qualified maintenance and service.

A WARNING

Turn off all gas and electrical power to furnace before performing any maintenance or service on unit. Failure to take this precaution may result in
personal injury due to electrical shock or uncon
trolled gas leakage.
NOTE; Furnace is equipped with a blower door switch
which cuts electric power when blower door is removed.
Air Filter — In order to aequaint the user of the furnace
with proper procedure for inspecting and cleaning the filter, the installer should instruct the user to locate, remove, clean and replace the furnace filter(s).
NOTE: If furnace is equipped with accessory filter rack, refer to section on page 11.

A CAUTION

Personal injury or property damage may result if furnace is operated with the blower compartment door removed. A lack of adequate combustion air may cause the main burner flame to be drawn out of the furnace unless blower compartment door is secured.
After inspecting or replacing the filter, be sure that the blower compartment door is securely fastened in place. Never operate the furnace without a filter.
Lubricating Motors — Direct drive motor and
blower assemblies are factory lubricated and normally do not require oiling.
Bookjl |4 PC101 Catalog No 535-834 Printed in U S A Form 58ED,PB-1SI Pg 15 6-85 Replaces: 58PB-1SI
Tab l6a|8a
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
For replacement items use Carrier Specified Parts
Page 16
58ED,PB
HEATING & COOLING
Cleaning Heat Exchanger and Venting System
— The heat exchanger and venting system should be checked each year by a qualified dealer. If necessary, the following procedures should be performed:
1. Make sure that all utilities are turned off upstream of the furnace (both gas and electrical supplies),
2. Remove burner covers, manifold assembly with burners, vent connectors and draft hood.
3. Clean flue box, flue ways, burner box and burners with brush and/or vacuum cleaner.
4. After cleaning, check pilot for proper position.
Replace all parts.
Table 7 — Trouble Analysis Chart for Standing Pilot Models
Turn off gas and electrical supplies to furnace before servicing. (Unless specific test requires gas and electrical supplies )
Horizontal Gas-Fired Furnaces
5. Turn on gas and electrical supplies. Test for leaks using soap and water solution.

A CAUTION

Never use an open flame when testing for gas leaks. Use a soap and water solution.
6. Check for proper operation of all controls.

A WARNING

SYMPTOM AND PROBABLE CAUSE
BURNERS WILL NOT IGNITE
1 Pilot light out
2 No 115-v power to furnace
3 No 24-v power to control circuit
4. Miswired or loose connections
5. No gas at main burners
6 Flame probe or connecting lead is shorted or open 6, Correct electrical shorting or open circuit
INADEQUATE HEATING
1 Furnace undersized for application 2 Gas input to furnace too low
3 Limit switch cycles main burners
ALDEHYDE ODORS (CO), SOOTING FLAME, FLOATING FLAME
1 Incomplete combustion — poor flame characteristics
1 Relight pilot If pilot does not remain lit, replace
thermocouple
2. Connect to power supply. Check fuse, wiring or circuit breaker.
3. Check transformer; replace.
4 Check all wiring and wirenut connections. 5 Check to see if main valve is operating Look for loose or
broken wiring connections If no deficiency is found, replace valve assembly.
1 Replace with proper size furnace
2. Check gas pressure at manifold. Clock gas meter for input If too low, increase manifold pressure, or replace with correct orifices.
3 OFF setting of fan control set too high; reset.
Dirty air filters; clean and reinstall. Blower speed too low; use faster speed tap Registers closed, restricted ductwork, open or remove
restriction Check heat anticipator setting on thermostat, readjust.
1 Air shutter on burners closed, adjust to soft, blue flame.
Check all screws aroundflueoutletsand burner compartment, tighten
Lack of combustion air, see Installation section Cracked heat exchanger; replace Overfired furnace; reduce input or change orifices. Check vent for restriction; clean as required
REMEDY
Bookp |4 PC101 Catalog No 535-834 PrintedinUSA Form 58ED.PB-1SI Pg16 6-85 Replaces: 58PB-1 SI Tab I6al8a
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
For replacement items use Carrier Specified Parts.
Page 17
58ED,PB
HEATING & COOLING
Table 8 — Trouble Analysis Chart for Electronic ignition Modeis
Turn off gas and electrical supplies to furnace before servicing (Unless specific test requires gas and electrical supplies.)
SYMPTOM AND PROBABLE CAUSE
PILOT WILL NOT LIGHT
1 No spark at electrode
2 Spark shorting out to main burner
3. No gas at pilot burner
BURNERS WILL NOT IGNITE
1 No 115-v power to furnace
2. No 24-v power to control circuit
3. Miswired or loose connections 4 No gas at main burners
5 Flame probe or connecting lead is shorted or open
INADEQUATE HEATING
1. Furnace undersized for application
2 Gas input to furnace too low
3 Limit switch cycles main burners
Horizontal Gas-Fired Furnaces
A WARNING
REMEDY
1 Check spark gap, refer to Start-Up and Adjustment section
Check if Induced draft motor is operating If not, check power
to motor Check for any blockage in flue venting system and chimney,
thereby preventing pressure switch from closing Unblock
if necessary Check moisture or dirt accumulation on electrode ceramic,
clean ceramic with cloth Cracked ceramic, replace pilot electrode assembly Check for loose or broken wiring at and between electronic
control box and electrode. Replace wire as necessary Check fuse or circuit breaker for 115-v supply to furnace Check 24 v input to electronic control box If you read 24 v,
and above steps have been completed, replace electronic control box assembly
Check pressure switch and tube assembly for any blockage that prevents pressure switch from operating
Check continuity to determine if pressure switch has disengaged
2 Realign electrode tip away from main burner but maintain
spark gap to pilot burner as noted above
3 Check to see if pilot valve is opening Look for loose or broken
wiring connections If no deficiency is found, replace valve assembly
1 Connect to power supply Check fuse, wiring or circuit
breaker 2 Check transformer; replace 3 Check all wiring and wirenut connections 4 Check to see if main valve is operating. Look for loose or
broken wiring connections If no deficiency is found, replace valve assembly
5. Correct electrical shorting or open circuit
1 Replace with proper size furnace 2 Check gas pressure at manifold Clock gas meter for input.
If too low, increase manifold pressure, or replace with correct
orifices
3 OFF setting of fan control set too high, reset
Dirty air filters, clean and reinstall. Blower speed too low, use faster speed tap Registers closed, restricted ductwork, open or remove
restriction. Check heat anticipator setting on thermostat; readjust
ALDEHYDE ODORS (CO), SOOTING FLAME, FLOATING FLAME
1 Incomplete combustion — poor flame characteristics
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book|1 [4 PC101 Catalog No 535-834 PrintedinUSA Form 58ED,PB-1SI Pg17 6-85 Replaces: 58PB-1 SI
1 Air shutter on burners closed, adjust to soft, blue flame
Check all screws around flue outlets and burner compart
ment; tighten Lack of combustion air, see Installation section Cracked heat exchanger, replace Overfired furnace; reduce input or change orifices Check vent for restriction; clean as required
>% Dorfo
Page 18
58ED,PB
HEATING A COOLING
Horizontal Gas-Fired Furnaces
t
t
BookM 14 PC101 Catalog No 535-834 Printed in U S A Form 58ED,PB-1Si Pg 18 6-85 Repiaces: 58PB-1Si
Tab IGaTSa For replacement items use Carrier Specified Parts
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Loading...