Number One
AirConditbninq
Maker
Division o1
Carrier Corporation
Carrier Parkway • Syracuse NY 13221
V
-------
U-
Procedures for Gas-Fired Furnaces
INTRODUCTION
The Need for Adequate Combustion Air —
Modern construction methods involve greater use of
insulation, improved vapor barriers and weather
stripping, with the result that both apartments and
single-family residences generally are much tighter
structurally than they have been in the past.
Combustion air supply for gas-fired equipment can
be affected by these construction conditions, be
cause infiltration that existed in the past may not
now be adequate. Extensive use of kitchen and bath
room exhaust fans, and even fireplaces, aggravates
the situation.
Today’s building practices invalidate the old rule
of thumb of “one air change by infiltration.” Reli
ance on this practice can result in combustion air
starvation if proper combustion air is not provided.
In fact, recent field investigations, particularly with
closet installation of gas-fired furnaces, indicate the
need for positive provision for combustion air and
for a better understanding of application guidelines
that relate to today’s conditions.
These instructions cover minimum combustion
air requirements and venting practices, reflect
current conditions found in the field, and conform
to existing national standards and safety codes. In
some instances, these instructions exceed certain
local codes and ordinances, especially those that
may not have kept pace with the changing resi
dential construction practices. Carrier requires these
standard procedures as a minimum for a safe
installation.
CAUTION: Do not obstruct openings in front
of the furnace or in the top on each side of the
vent pipe. These provide air for combustion and
ventilation. Never store anything on or in con
tact with the furnace such as;
Spray or aerosol cans, rags, brooms, dust mops,
vacuum cleaners, or other cleaning tools.
Soap powders, bleaches, waxes or other clean
ing compounds, plastic or plastic containers,
gasoline, kerosene, cigarette lighter fluid, dry
cleaning fluids, or other volatile fluids.
Paint ihinners and other painting compounds,
paper bags or other paper products.
Installation Procedures — The following recom
mendations apply to the installation and operation
of gas furnaces and piping systems for natural and
LP gases. Use these procedures in conjunction with
the specific furnace installation instructions.
Refer also to the regulations of the serving gas
supplier and the local building, heating, plumbing
or other codes in effect in the area in which the
installation is made.
Portions of the following have been adopted in
part from the “National Fuel Gas Code” (NFPA
No. 54-1980 or ANSI Z223.I-I980) copyrighted by
the National Fire Protection Association and
American Gas Association. For further details, con
sult this publication or current edition available
from NFPA, 470 Atlantic Avenue, Boston, MA
02210, or American Gas Association, 1515 Wilson
Boulevard, Arlington, VA 22209.
These instructions contain the following sections:
Page
Inspection
...............................................................
1
Location and Air for Combustion
and Ventilation.................................................. I
Gas Piping.............................................................. 4
Venting..................................................................... 4
Electrical.................................................................. 5
Start-Up, Adjustment, and Safety Check .... 5
Furnace Location with Respect to
Cooling Equipment........................................... 7
Special Locations
...
................................................
INSPECTION
7
Check the available power supply to be sure that
it meets the specifications on the wiring diagram
and all motors in the furnace.
Check the available gas supply to see that it con
forms to the gas specification on the AGA rating
plate.
LOCATION AND AIR FOR COMBUSTION
AND VENTILATION
Locate the furnace close to the chimney and as
near the center of the air distribution system as
possible. Provide ample space for servicing and
cleaning. Always comply with minimum fire protec
tion clearances shown on the unit rating plate. Do
not install directly on carpeting, tile or any com
bustible material other than wood flooring. If base
for combustible floor is required, obtain from
Carrier distributor or dealer.
© Carrier Corporation 1982 Form 58-9XA
The draft hood relief air supply must be in the
same atmospheric pressure zone as the combustion
air inlet supply to the furnace.
When a furnace is installed so that supply ducts
carry air to areas outside the space containing the
furnace, the return air must also be handled by
duct(s) sealed to the furnace casing and terminating
outside the space containing the furnace.
All fuel-burning equipment must be supplied with
air, which enters into the combustion process and is
then vented to the outdoors. Sufficient air must
enter the equipment room to replace that drawn up
the vent stack. Replacement air must be provided by
means of ducts from the outside to the equipment
location or conditioned space. Under all conditions,
enough air must be provided to ensure there will not
be a negative pressure condition within the equip
ment room or space. A positive seal
must be made
between the furnace base and platform or return-air
duct connections. Even a “slight” leak can create a
negative pressure condition in a confined closet or
basement, and affect combustion. If necessary, seal
the furnace base to floor opening with fiberglass or
other approved material. Furnaces with sideconnected returns should utilize an accessory
bottom closure, properly sealed.
Complete combustion requires approximately
10 cu ft of air for every 1000 Btu of gas fuel. In addi
tion, approximately 10 more cu ft of air is required
for draft hood dilution, and 10 more for ventilation
of the furnace enclosure. Thus, for eaeh 1000 Btu of
gas consumed, a total of 30 cu ft of air must be sup
plied. For a 100,000 Btuh gas furnace, this equals
3000 cu ft of air per hour (100 x 30) or 50 cu ft of air
per minute (3000 60). In the past, the infiltration
of outside air assumed in heat loss calculations (one
air change per hour) was assumed to be sufficient.
However, current eonstruction methods, utilizing
more insulation and vapor barriers, tighter fitting
and gasketed doors and windows or weatherstrip
ping, and the presence of fuel-burning fireplaces and
mechanical exhaust fans from kitchens, laundries,
and baths require the positive introduction of
outside air.
CAUTION; Combustion air must come from a
source that is not contaminated by halogens,
which include fluorides, chlorides, bromides,
and iodides. These elements are found in aerosol
sprays, detergents, bleaches, cleaning solvents,
salts, air fresheners, and other household prod
ucts. Vapors from these products are highly
corrosive to gas-fired furnaces, in even ex
tremely low concentrations—as low as 1 / 2 part
per million. When such contaminants are pre
sent, outside air mttft be ducted separately to
the furnace room.
Operation of exhaust fans, kitchen ventilation
systems, clothes dryers, or fireplaces may create
conditions requiring special attention to avoid un
satisfactory operation of installed gas furnaces.
Commonly used exhaust fans and range hoods
handle anywhere from 60 to 300 cfm (or more) and
gas or electric clothes dryers may remove more air.
With multiple use of such appliances common in
both old and new homes and apartments, special
provisions for positive introduction of outside air
are mandatory. This air requirement is several times
that required by the furnace, and must be replaced,
in addition to the air required by the furnace.
The requirements for combustion and ventilation
air depend upon whether the furnace is located in a
confined or unconfined space. An unconfined space
is defined as a space with a volume not less than
50 cu ft/1000 Btuh of the total input rating of all
appliances installed in that space. Rooms communi
cating directly with the space in which the appliances
are installed, thru openings not furnished with
doors, are considered a part of the unconfined space.
A confined space is defined as a space with a vol
ume less than 50 cu ft/1000 Btuh of the total input
ratings of all appliances installed in that space.
Furnaces in Confined Spaces (Typical Furnace
Closet)
ALL AIR FROM INSIDE BUILDINGS:
The confined space shall be provided with 2 per
manent openings, one beginning within 12 in. of the
top and one beginning within 12 in. of the bottom of
the enclosure. Each opening shall have a minimum
free area of 1 sq in. per 1000 Btuh of the total input
rating of all equipment in the enclosure, but not have
less than 100 sq inches. The openings must freely
communicate with interior areas served by the
furnace, either thru permanent openings or louvered
doors.
In addition, if building is of unusually tight con
struction, provide one permanent opening directly
communicating with outdoors. This opening shall
have a minimum free area of 1 sq in. per 5000 Btuh
of total input rating of all equipment in the en
closure. Ducts shall be used to convey makeup air
and shall be of the same cross-sectional area as the
free areas of the openings to which they connect.
This duct should be connected to the cold air return
of the heating system. The minimum dimension of
the rectangular air ducts should not be less than
3 inches. See Fig. 1.
If the furnace is instafled on a raised platform
to provide a return air plenum, and return air
is taken directly from the hallway or space
adjacent to the furnace, all air for combustion
must come from outdoors, as prescribed below.
ALL AIR FROM OUTDOORS:
The confined space shall be provided with 2 per
manent openings, one commencing within 12 in.
of the top and one commencing within 12 in. of the
i
/
A.
RETURN OR
SUPPLY AIR
VENT TO ROOF
I I
I I I
I I I
T
12 IN MAX
I
D_L
■= I so IN.
~ PER 1000
BTUH*
INTERIOR
HEATED
SPACE
-6IN MIN
(FRONT)
ISO IN
# per 1000
HTBTUH*
I so IN. PER
2000 BTUH ^
i
RETURN OR
SUPPLY AIR
*MINIMUM OPENING SIZE IS 100 SO IN
J
-d
*-12 IN MAX
MAKEUP AIR
ISO IN
-PER 5000
BTUH FROM
OUTSIDE
(RETURN
AIR ONLY)
Fig. 1 — Upflow or Counterflow, Using Air
from Inside Building
bottom of the enclosure. These openings shall com
municate directly, or by ducts, with outdoors.
See Fig. 2.
a. When communicating with the outdoors thru
horizontal ducts, each opening shall have mini
mum free area of 1 sq in. per 2000 Btuh of total
input rating for all equipment in the enclosure. If
vertical ducts or openings with louvers and
grilles are used, each opening or duct shall have
a minimum free area of 1 sq in. per 4000 Btuh
of the total rated input of all equipment in the
enclosure.
b. When ducts are used, they shall be of the
same cross-sectional area as the free area of
the openings to which they connect. The mini
mum dimension of rectangular air ducts shall not
be less than 3 inches.
Furnaces in Unconfined Spaces (Basements,
Large Equipment Rooms, etc.) — If the uncon
fined space is within a building of unusually tight
construction, air for combustion, ventilation, and
dilution of flue gases shall be obtained from out
doors or from spaces freely communicating with the
outdoors. A permanent opening, or openings,
having a total free area of not less than 1 sq. in. per
5000 Btuh of total input rating for all equipment
shall be provided. A duct may be used to convey
USE ANY OF THE FOLLOWING COMBINATIONS
OF OPENINGS: ABB CSD D&E
*MINIMUM OPENING SIZE IS 100 SO IN
Fig. 2 — Upflow or Counterflow. Using Air
from Outside Building
makeup air from the outdoors and shall be of the
same cross-sectional area as the free area of the
openings to which it connects. The duct may be con
nected to the eold air return of the heating system
only if it connects directly to outside air. The
minimum dimension of rectangular air ducts shall
be not less than 3 inches.
CAUTION: Return air must not be taken from
the room, unless an equal or greater amount of
air is supplied to the room. All duct connections
to the furnace must be airtight to avoid causing
I
a “negative” pressure condition within the room.
Louvers and Grilles — In calculating the free area,
consideration shall be given to the blocking effect of
louvers, grilles, or screens protecting openings.
Screens used must not be smaller than I / 4-in. mesh.
If the free area thru a design of louver or grille is
known, it should be used in calculating the size
opening required to provide the free area specified.
If the design and free area is not known, assume that
wood louvers will have 20- to 25-percent free area
and metal louvers and grilles will have 60- to 75percent free area. Louvers and grilles that provide
combustion and dilution air must be constructed so
they cannot be closed.