Carrier 58 User Manual

Page 1
Number One AirConditbninq Maker
Division o1 Carrier Corporation
V
-------
U-
Procedures for Gas-Fired Furnaces

INTRODUCTION

The Need for Adequate Combustion Air —
Modern construction methods involve greater use of
insulation, improved vapor barriers and weather
stripping, with the result that both apartments and single-family residences generally are much tighter structurally than they have been in the past. Combustion air supply for gas-fired equipment can be affected by these construction conditions, be cause infiltration that existed in the past may not now be adequate. Extensive use of kitchen and bath room exhaust fans, and even fireplaces, aggravates the situation.
Today’s building practices invalidate the old rule of thumb of “one air change by infiltration.” Reli ance on this practice can result in combustion air
starvation if proper combustion air is not provided. In fact, recent field investigations, particularly with
closet installation of gas-fired furnaces, indicate the
need for positive provision for combustion air and for a better understanding of application guidelines that relate to today’s conditions.
These instructions cover minimum combustion air requirements and venting practices, reflect current conditions found in the field, and conform to existing national standards and safety codes. In
some instances, these instructions exceed certain local codes and ordinances, especially those that may not have kept pace with the changing resi dential construction practices. Carrier requires these
standard procedures as a minimum for a safe installation.
CAUTION: Do not obstruct openings in front of the furnace or in the top on each side of the vent pipe. These provide air for combustion and ventilation. Never store anything on or in con tact with the furnace such as;
Spray or aerosol cans, rags, brooms, dust mops, vacuum cleaners, or other cleaning tools.
Soap powders, bleaches, waxes or other clean ing compounds, plastic or plastic containers, gasoline, kerosene, cigarette lighter fluid, dry cleaning fluids, or other volatile fluids.
Paint ihinners and other painting compounds,
paper bags or other paper products.
Installation Procedures — The following recom
mendations apply to the installation and operation
of gas furnaces and piping systems for natural and LP gases. Use these procedures in conjunction with
the specific furnace installation instructions.
Refer also to the regulations of the serving gas
supplier and the local building, heating, plumbing
or other codes in effect in the area in which the
installation is made.
Portions of the following have been adopted in
part from the “National Fuel Gas Code” (NFPA
No. 54-1980 or ANSI Z223.I-I980) copyrighted by
the National Fire Protection Association and
American Gas Association. For further details, con sult this publication or current edition available from NFPA, 470 Atlantic Avenue, Boston, MA 02210, or American Gas Association, 1515 Wilson
Boulevard, Arlington, VA 22209.
These instructions contain the following sections:
Page

Inspection

...............................................................
1
Location and Air for Combustion
and Ventilation.................................................. I
Gas Piping.............................................................. 4
Venting..................................................................... 4
Electrical.................................................................. 5
Start-Up, Adjustment, and Safety Check .... 5
Furnace Location with Respect to
Cooling Equipment........................................... 7
Special Locations
...
................................................
INSPECTION
7
Check the available power supply to be sure that
it meets the specifications on the wiring diagram and all motors in the furnace.
Check the available gas supply to see that it con
forms to the gas specification on the AGA rating
plate.
LOCATION AND AIR FOR COMBUSTION
AND VENTILATION
Locate the furnace close to the chimney and as near the center of the air distribution system as possible. Provide ample space for servicing and cleaning. Always comply with minimum fire protec
tion clearances shown on the unit rating plate. Do
not install directly on carpeting, tile or any com
bustible material other than wood flooring. If base
for combustible floor is required, obtain from
Carrier distributor or dealer.
© Carrier Corporation 1982 Form 58-9XA
Page 2
The draft hood relief air supply must be in the same atmospheric pressure zone as the combustion air inlet supply to the furnace.
When a furnace is installed so that supply ducts carry air to areas outside the space containing the furnace, the return air must also be handled by duct(s) sealed to the furnace casing and terminating outside the space containing the furnace.
All fuel-burning equipment must be supplied with air, which enters into the combustion process and is then vented to the outdoors. Sufficient air must enter the equipment room to replace that drawn up the vent stack. Replacement air must be provided by means of ducts from the outside to the equipment location or conditioned space. Under all conditions, enough air must be provided to ensure there will not be a negative pressure condition within the equip ment room or space. A positive seal
must be made between the furnace base and platform or return-air duct connections. Even a “slight” leak can create a negative pressure condition in a confined closet or basement, and affect combustion. If necessary, seal the furnace base to floor opening with fiberglass or other approved material. Furnaces with side­connected returns should utilize an accessory bottom closure, properly sealed.
Complete combustion requires approximately
10 cu ft of air for every 1000 Btu of gas fuel. In addi tion, approximately 10 more cu ft of air is required for draft hood dilution, and 10 more for ventilation of the furnace enclosure. Thus, for eaeh 1000 Btu of gas consumed, a total of 30 cu ft of air must be sup plied. For a 100,000 Btuh gas furnace, this equals 3000 cu ft of air per hour (100 x 30) or 50 cu ft of air per minute (3000 60). In the past, the infiltration of outside air assumed in heat loss calculations (one air change per hour) was assumed to be sufficient.
However, current eonstruction methods, utilizing more insulation and vapor barriers, tighter fitting and gasketed doors and windows or weatherstrip ping, and the presence of fuel-burning fireplaces and
mechanical exhaust fans from kitchens, laundries, and baths require the positive introduction of outside air.
CAUTION; Combustion air must come from a source that is not contaminated by halogens, which include fluorides, chlorides, bromides, and iodides. These elements are found in aerosol sprays, detergents, bleaches, cleaning solvents, salts, air fresheners, and other household prod
ucts. Vapors from these products are highly corrosive to gas-fired furnaces, in even ex tremely low concentrations—as low as 1 / 2 part per million. When such contaminants are pre
sent, outside air mttft be ducted separately to the furnace room.
Operation of exhaust fans, kitchen ventilation
systems, clothes dryers, or fireplaces may create
conditions requiring special attention to avoid un satisfactory operation of installed gas furnaces. Commonly used exhaust fans and range hoods handle anywhere from 60 to 300 cfm (or more) and gas or electric clothes dryers may remove more air. With multiple use of such appliances common in both old and new homes and apartments, special provisions for positive introduction of outside air are mandatory. This air requirement is several times that required by the furnace, and must be replaced, in addition to the air required by the furnace.
The requirements for combustion and ventilation
air depend upon whether the furnace is located in a
confined or unconfined space. An unconfined space
is defined as a space with a volume not less than
50 cu ft/1000 Btuh of the total input rating of all appliances installed in that space. Rooms communi cating directly with the space in which the appliances are installed, thru openings not furnished with doors, are considered a part of the unconfined space.
A confined space is defined as a space with a vol
ume less than 50 cu ft/1000 Btuh of the total input
ratings of all appliances installed in that space.
Furnaces in Confined Spaces (Typical Furnace
Closet)
ALL AIR FROM INSIDE BUILDINGS:
The confined space shall be provided with 2 per manent openings, one beginning within 12 in. of the top and one beginning within 12 in. of the bottom of the enclosure. Each opening shall have a minimum free area of 1 sq in. per 1000 Btuh of the total input rating of all equipment in the enclosure, but not have less than 100 sq inches. The openings must freely communicate with interior areas served by the furnace, either thru permanent openings or louvered doors.
In addition, if building is of unusually tight con struction, provide one permanent opening directly communicating with outdoors. This opening shall have a minimum free area of 1 sq in. per 5000 Btuh of total input rating of all equipment in the en closure. Ducts shall be used to convey makeup air and shall be of the same cross-sectional area as the
free areas of the openings to which they connect. This duct should be connected to the cold air return
of the heating system. The minimum dimension of
the rectangular air ducts should not be less than
3 inches. See Fig. 1.
If the furnace is instafled on a raised platform
to provide a return air plenum, and return air is taken directly from the hallway or space adjacent to the furnace, all air for combustion must come from outdoors, as prescribed below.
ALL AIR FROM OUTDOORS:
The confined space shall be provided with 2 per manent openings, one commencing within 12 in. of the top and one commencing within 12 in. of the
i
/
A.
Page 3
RETURN OR SUPPLY AIR
VENT TO ROOF
I I
I I I I I I
T
12 IN MAX
I
D_L
■= I so IN.
~ PER 1000
BTUH*
INTERIOR HEATED
SPACE
-6IN MIN
(FRONT)
ISO IN
# per 1000 HTBTUH*
I so IN. PER 2000 BTUH ^
i
RETURN OR SUPPLY AIR
*MINIMUM OPENING SIZE IS 100 SO IN
J
-d
*-12 IN MAX
MAKEUP AIR ISO IN
-PER 5000 BTUH FROM OUTSIDE (RETURN
AIR ONLY)
Fig. 1 — Upflow or Counterflow, Using Air
from Inside Building
bottom of the enclosure. These openings shall com municate directly, or by ducts, with outdoors. See Fig. 2.
a. When communicating with the outdoors thru
horizontal ducts, each opening shall have mini mum free area of 1 sq in. per 2000 Btuh of total input rating for all equipment in the enclosure. If vertical ducts or openings with louvers and grilles are used, each opening or duct shall have a minimum free area of 1 sq in. per 4000 Btuh of the total rated input of all equipment in the enclosure.
b. When ducts are used, they shall be of the
same cross-sectional area as the free area of the openings to which they connect. The mini
mum dimension of rectangular air ducts shall not be less than 3 inches.
Furnaces in Unconfined Spaces (Basements, Large Equipment Rooms, etc.) — If the uncon
fined space is within a building of unusually tight construction, air for combustion, ventilation, and dilution of flue gases shall be obtained from out doors or from spaces freely communicating with the outdoors. A permanent opening, or openings, having a total free area of not less than 1 sq. in. per 5000 Btuh of total input rating for all equipment shall be provided. A duct may be used to convey
USE ANY OF THE FOLLOWING COMBINATIONS OF OPENINGS: ABB CSD D&E
*MINIMUM OPENING SIZE IS 100 SO IN
Fig. 2 — Upflow or Counterflow. Using Air
from Outside Building
makeup air from the outdoors and shall be of the same cross-sectional area as the free area of the openings to which it connects. The duct may be con nected to the eold air return of the heating system only if it connects directly to outside air. The minimum dimension of rectangular air ducts shall be not less than 3 inches.
CAUTION: Return air must not be taken from the room, unless an equal or greater amount of air is supplied to the room. All duct connections to the furnace must be airtight to avoid causing
I
a “negative” pressure condition within the room.
Louvers and Grilles — In calculating the free area,
consideration shall be given to the blocking effect of
louvers, grilles, or screens protecting openings. Screens used must not be smaller than I / 4-in. mesh. If the free area thru a design of louver or grille is known, it should be used in calculating the size opening required to provide the free area specified.
If the design and free area is not known, assume that wood louvers will have 20- to 25-percent free area and metal louvers and grilles will have 60- to 75­percent free area. Louvers and grilles that provide combustion and dilution air must be constructed so
they cannot be closed.
Page 4

GAS PIPING

The gas supply line should be a separate line
directly from the meter to the furnace, if possible.
Refer to Table 1 for recommended gas pipe sizing.
Do not use cast-iron or galvanized pipe.
located on the gas valve before the test. It is recom mended that the ground joint union be cracked be fore pressure testing.
After all connections have been made, purge the
lines and check for leakage.

Table 1 — Maximum Capacity of Gas Pipe*

NOMINAL
IRON PIPE
SIZE
(in.)
Z
’"3/4
1 T
1-1/4 1-1/2
*Cu ft of gas per hour for gas pressures of 0 5 psig or less, and a
pressure drop of 0 5 in wg (based on a 0 60 specific gravity) Ref Table C-4 NFPA 54-1980
INTERNAL
DIAMETER
(in.)
”^622~
0 824
1^049 1 380
1 6IO"
r''
1400
2100
LENGTH OF PIPE
(ft)
10_
20 30
120 97
360
250 200 170 151
68Í
465 375
950 770
1460 1180 990 900
40
320 660
50
82
73
285 580
Avoid low spots in long runs of pipe. It is best to slope all pipe 1/4in. in 15ft to prevent traps. All horizontal runs should slope away from the meter, to risers. Risers should be used to connect to the furnace and to the meter.
Joint compounds (pipe dope) should be applied sparingly and only to the male threads of the joints (omit the first 2 threads). Consult local supplier for type of compound to be used. This pipe dope must be resistant to the action of LP gas.
Install a sediment trap in the riser leading to the furnace. This trap will collect dirt or condensate. It can be installed by connecting a tee to the riser lead ing to the furnace, so that the straight-thru section of the tee is vertical. Then connect a capped nipple into the lower end of the tee. The capped nipple should extend below the level of the gas controls. See Fig. 3.
Where a gum filter is required by local codes, install
it in accordance with those requirements.
An accessible manual shutoff valve shall be in
stalled upstream of the furnace gas controls and within 6 ft of the furnace. A 1/8-in. NPT plugged
tapping, accessible for test gage connection, must
be installed immediately upstream of the gas supply connection to the furnace and downstream from the manual shutoff valve.
Place a ground joint union between the gas con trol manifold and the manual gas shutoff valve, or use an approved flexible or semirigid conductor.
Support all piping with the appropriate straps, hangers, etc. (one hanger every 10 ft minimum).
Piping should be pressure-tested before any
furnace, appliance, or shutoff valve is attached, in
accordance with the requirements of local and national plumbing and gas codes.
If the pressure exceeds 0.5 psig, the gas supply pipe must be disconnected from the furnace before the pressure test. If the test pressure is equal to or less than 0.5 psig, close the manual shutoff valve
WARNING: Never purge a fine into a combus tion chamber. Never use matches, candles, ñame or other sources of ignition for the pur pose of checking leakage. Use a soap-and-water solution to check for leakage.

- VENTING

Fig. 3 — Sediment Trap
Consult local codes. For additional information refer to the “National Fuel Gas Code” (NFPA No. 54-1980 or ANSI Z223.1-1980). Unless the local
codes direct otherwise, the unit may be vented to a
permanent chimney, or to a listed type-B 1 gas vent. All gas-fired furnaces are shipped with draft diverters; therefore, connect the vent collar to the chimney or gas vent to be used. The following recommendations are made:
1. Select flue connection material that is satis factory for installation and that meets require ments of local codes.
2. Flue connection pipe must be at least as large as outlet collar on furnace. No reduction in this
size is permissible in pipe run.
3. Run pipe as directly as possible with minimum
number of turns. Maintain minimum of 1/4in. per linear ft up
4.
ward slope on all horizontal runs. Rigidly support flue pipe with hangers and
straps to ensure that there will no movement after installation.
Page 5
km
6. Insert the smallest flue conneetion pipe at the highest level consistent with available head­room or clearance to combustible materials,
when 2 or more vent connectors enter a com
mon gas vent or chimney flue.
7. Extend flue connection pipe thru chimney wall, flush with inner face of chimney liner and above extreme bottom to avoid restriction.
WARNING; Never connect into a chimney serving an open fireplace unless fireplace opening is sealed off.
8.
No portion of the venting system shall extend into or pass thru any circulating air duct or plenum.
9.
Chimney or gas vent should extend at least 5 ft above highest connected draft hood and should extend high enough above roof of any neighbor ing obstruction so that wind from any direction will not create positive pressure in vicinity of a chimney or gas vent outlet. Chimney or gas vent should extend 3 ft higher than point of emer gence thru roof, and at least 2 ft higher than any
object within radius of 10 feet. See Fig. 4. A type-Bl gas vent shall terminate above the
10.
roof surface with a listed cap or roof assembly.
HEIGHT ABOVE ANY ROOF SURFACE WITHIN 10' HORIZONTALLY
3 MIN GAS VENT OR CHIMNEY
Tn
Fig. 4 — Chimney, Gas Vent Height

ELECTRICAL

3MIN GAS VENT OR CHIMNEY
IMPORTANT: Before proceeding with the electrical connections, make certain that voltage, frequency, and phase correspond tp that specified on the furnace rating plate. Also, check to be sure that the service provided by the utility is sufficient to handle the additional load imposed by this equipment. Refer to the unit rating plate for equipment electrical requirements.
" The specific furnace installation instructions con
tain wiring diagrams that show the proper field high­and low-voltage wiring. Make all connections in accordance with the National Electrical Code and any local codes or ordinances that might apply.
^ W.ARNING: The cabinet must have an unin-
terruoted or unbroken ground according to National Electrical Code, ANSI/NFPA
70-1981, ANSI C1-19SI, or local codes to mini mize personal injury if an electrical fault should occur. This may consist of electrical wire or conduit approved for electrical ground when installed in accordance with existing electrical codes. Do not use gas piping as an electrical ground.
CAUTION; If manual disconnect switch is to be mounted on the furnace, select a location where drill or fastener will not contact electrical or gas components.
NOTE; Use only copper wire between disconnect switch and furnace. If aluminum wire is used be tween service panel and disconnect switch, adhere to the following recommendations.
When making aluminum conductor connections to copper conductors or terminals, use only con nectors that are UL approved (marked Al/Cu with the UL symbol) for the application and wire size. Do not reduce wire size to fit connector by cutting off strands. Use properly sized connectors.
After insulation has been stripped from the aluminum conductor, coat the conductor end with corrosion inhibitor (Burndy Pentrox A or equiv alent), and wire-brush the aluminum surface thru the inhibitor.
CAUTION: Do not wire-brush connectors and
lugs. The plating will be broken.
After cleaning, recoat the aluminum conductor with inhibitor, and make connection, then coat entire connection. When it is suspected that the connection will be exposed to moisture, it is very important to cover the entire connection completely to prevent an electrochemical action that will cause the con nection to fail very quickly.
If aluminum conductors are to be used, the wire size selected must have a current capacity not less than that of the copper wire specified, and must not create a voltage drop between the service panel and the furnace in excess of 2% of the unit rated voltage.
Check all electrical connections (both factory and field) for tightness. This should also be done after the unit has reached operating temperatures, especially if aluminum conductors are used.
START-UP, ADJUSTMENT, AND
SAFETY CHECK
Pilot — Check to be sure that all connections have
been properly made, then proceed as follows;
Light the pilot, using the procedure outlined on
the Lighting Instruction Plate attached to the fur-
Page 6
nace. However, when lighting the pilot for the first time, perform the following additional steps;
■ 1. If supply line was not purged before connecting furnace, it will be full of air. It is recommended that the ground joint union be cracked, and sup ply line be allowed to purge until odor of gas is detected. Never purge gas lines into combustion chamber. Immediately upon detection of gas odor, retighten the union. Allow 5 minutes to elapse, then light pilot in accordance with in structions on furnace.
2. Pilot flame should be soft blue in color. a. For natural gas controls, flame should be long
enough to provide good impingement on ele ment of pilot. Flame should extend above the carryover ports of the burner.
b. For complete shutoff gas controls, flame
should surround tip of thermocouple element of pilot and extend downward to include 3/8 to 1 / 2-in. of thermocouple. Flame must never come in contact with any other part of ther mocouple or its lead wire. Flame lies under carryover port of burner and merges with carryover flame.
3. Pilot adjusting screw is located on main gas valve or pilot shutoff valve.
a. Remove capscrew; turn pilot gas full on and
turn adjusting screw until desired appearance is obtained.
b. Replace capscrew.
4. For natural gas controls, check the pilot oper ation as follows: Attach a low-voltage test light to electrical leads of gas valve. With thermostat set above room temperature, shut off gas supply to burners and pilot with main manual shutoff valve. If test light goes out within 45 seconds,
pilot is functioning properly. If light does not go out within 60 seconds, replace pilot.
5. The 100% safety control can be easily checked by unscrewing pilot thermocouple lead from gas valve. Pilot and main burner gas should shut off — no gas should flow thru valve. After valve is checked and found to operate satisfactorily, reconnect thermocouple to gas valve to finger­tight position. Then tighten 1/4 turn with a wrench. Relight pilot, following lighting instruc tions on furnace.
Burners — Light main burners using procedure
contained on Lighting Instruction Plate attached to furnace.
Gas Input — Determine the gas input as follows:
NATURAL GAS
1. Turn off all other gas appliances and pilots.
2. Measure time (in seconds) for gas meter test dial to complete one revolution.
3. Refer to Table 2 for cu ft of gas per hour.
Table 2 — Gas Rate (Cubic Feet Per Hour)
SECONDS
FOR ONE
REVOLUTION
10 11 12 300
13 277 555 14
15 16 17 212 18 19 189
20 180
21 171 343 857
22 23 24 150 300
25 26 27 133 28 29 124
30 120
31 116
32 113 33 34 106
35 36 37 97 38 39
40 41 88 176 42
43 44 82
45 46 47 48 49
Multiply cu ft per hour times heating value of
4.
SIZE OF
TEST DIAL
2 5
1
cu ft cu ft
360 720 1800 327 655
600
257 514
480 1200
240 225 450
424 1059
200 400 1000
379 947 360 900
164 327 818 157 313
144 288 720
277 692
138
267 667
129 257 643
248 240 600
232 581 225
109 218
212 529 206
103 100 200 500
195 486 189
95 92 185 462
90 180 450 86 172
84 167 419
164
80 160 400
157 391
78
76 153 383 75 150 375 73 147
SECONDS
FOR ONE
REVOLUTION
cu ft
1636 51 1500 1385 1286 54
1125 56
783 750
621 78
563 545 86
514 90 40
474 96 38
439 429
409
367
50 52 69 138
53 68
55 57 63 126
58 59
60 60"^ 120
62 58 116
64 56 112 281 66 68
70 72 74 76
80 82 84
88
92 39 78 94 38
98
100 102 104 35 69 106 108
110 33 112 116 120
SIZE OF
TEST DIAL
»»"—
---
----
,
1
2 5
CU ft cu ft cu ft
72 144 360 71 141 355
136 340
67 133 333 65 131 327
64
129
62
124
61 122 305
54
109
53 106 265 51 103
50 100 48 97 243 47 95 46 92 231
45 90 44
88 43 86 42 84 209 41 82 205
80
76
75
74
37 36 72
71 178
35 34 68
67 167
33
65 32 64 161 31 62 30 60
J
gas (Btu/ cu ft). Obtain heating value of gas from local gas utility.
Example: Btu/cu ft X cu ft = Btuh heating input
Time for one revolution of 2 cu ft dial = 72 seconds
Heat value of gas = 1070 Btuh/cu ft
100 X 1070 = 107,000 Btuh input
Measured gas input should not exceed gas
^ 5.
input shown on unit rating plate.
6. To adjust input rate, remove cap that conceals regulator adjustment. Turn adjusting screw counterclockwise (out) to decrease input. When adjusting, DO NOT change manifold pressure more than 0.3 in. wg. Any major adjustment should be made by changing main burner orifices.
LP (PROPANE) GAS — These units are equipped with pressure regulators. Burner orifices are sized to
346
321 316 310
300 290
273
257 250
237
225 220 214
200 196 192
188 184
180 173
170
164
155 150
Page 7
give rated input at a manifold pressure of 10.5 in. wg. Check manifold pressure and, if necessary, adjust pressure.
HIGH ALTITUDE — Ratings are approved for altitudes to 2000 ft for all gases. Ratings for altitudes over 2000 ft are 4% less for each 1000 ft above sea level.
Adjust Main Burner Flame — The main burner
flame should be clear blue, almost transparent,
with a well-defined inner cone. If there is too much primary air, the flame will be well defined, but with a tendency to float or lift off the burner ports.
See Fig. 5.
Limit Control Safety Check — This control shuts
off the gas and energizes the blower motor if the furnace becomes overheated.
The recommended method of checking the limit control is to gradually block off the return air after the furnace has been operating for a period of at least 5 minutes. As soon as the limit has proven safe, the return air opening should be unblocked to permit normal air circulation. By using this method to check the limit control, it can be established that the limit is functioning properly and will be fail-safe if there is a motor failure.
FURNACE LOCATION WITH RESPECT
TO COOLING EQUIPMENT
The cooling coil must be installed parallel with or on the downstream side of the furnace to avoid condensation in the heating element. When installed parallel with a furnace, dampers or other means used to control the flow of air must prevent chilled air from entering the unit. If the dampers are manually operated, they must be equipped with means to prevent operation of either unit unless the damper is in the full-heat or full-cool position, i
1. Allow unit to operate 5 minutes.
2. When burners are equipped with primary air adjustment, adjust each burner by closing air adjustment device until slight yellow tip appears
on flame; then open, just enough to clear yellow
from flame.
Temperature Rise — The unit is to be adjusted
within the temperature rise range specified on the
rating plate. Determine the air temperature rise as follows:
1. Place duct thermometers in return and supply ducts as near furnace as possible. Be sure ther
mometers do not “see” heat element so that radiant heat will not affect thermometer read ings. This is particularly important with straight­run ducts.
2. When thermometers stabilize, subtract return air temperature from supply air temperature to
determine air temperature rise.
3. Adjust air temperature rise by adjusting blower speed. Increase blower speed to reduce tempera ture rise. Decrease blower speed to raise tempera ture rise.

^ SPECIAL LOCATIONS

A gas-fired furnace installed in a residential garage should be installed so the burners and igni tion source are located not less than 18 in. above the floor and the furnace is located or protected to avoid physical damage by vehicles.
When furnaces are installed in public garages, air plane hangars, or other buildings having hazardous atmospheres, the unit should be installed in accord ance with the recommended good practice require ments of the National Board of Fire Underwriters.
#
Page 8
#
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1
Tab
6a
Form58-9XA Supersedes58-7XA PrintedinUSA 3-82 PC 101
Catalog No 515-802
Loading...