Installation and servicing of air conditioning
equipment can be hazardous due to system pressure
and electrical components. Only trained and quali
fied service personnel should install, repair or
service air conditioning equipment.
Untrained personnel can perform basic mainten
ance functions of cleaning coils and cleaning and
replacing filters. All other operations should be
performed by trained service personnel. When
working on air conditioning equipment, observe
precautions in the literature, tags and labels
attached to the unit and other safety precautions
that may apply.
Follow all safety codes. Wear safety glasses and
work gloves. Use quenching cloth for brazing
operations. Have fire extinguishers available for all
cooling and heating systems. They are water-to-air
heat pumps designed for indoor installation. They
may be connected into existing duct systems which
are properly sized and designed to handle air
quantity of 350 to 450 cfm per ton of cooling. Re
quired connections include supply air duct, water
supply and return lines, high- and low-voltage
wiring. Factory-supplied air filter is installed in rack
on unit return air section. See Table I for filter size.
Use recommended thermostat and subbase (Table 3)
for proper unit operation.
INSTALLATION
Step 1 — Check Equipment and Jobsite
UNPACKAGE UNIT — Move to final location.
Slide from carton taking special care not to damage
service valves or grilles.
INSPECT EQUIPMENT — File claim with ship
ping company if shipment is damaged or incomplete.
COMPLETE OR CONSIDER THESE SYSTEM
REQUIREMENTS before installation:
a. Consult local building codes and National Elec
trical Code (NEC) for special installation
requirements.
b. Consider type of water source. Ensure there is an
adequate supply of water at temperature of 45 F
to 90 F with minimum pressure of 10 psig.
c. Provide sufficient space for water piping, con
densate drain, wiring and servicing unit. See
Fig. 1. When front (external) water piping
connections are used, locate unit so piping does
not block front access panels. (Units installed in
confined areas may have to be removed for major
servicing such as compressor or fan motor
replacement.)
d. Provide a minimum 6-in. clearance between
return air filter and adjacent wall.
e. Mount 50WQ on floor or solid platform so unit is
elevated. Make sure unit is supported from the
bottom. To reduce sound transmission, es
pecially when 50WQ is located in a closet or
utility room having louvered doors, the following
acoustical treatment is recommended; place an
isolation pad under unit. Pad must be same size
as unit base. Construct a 1-in. fiberglass sound
shield in front of unit.
Step 2 — Connect Supply Ductwork to unit
supply air duct connection flange. Refer to Fig. 1
and Table 1 for connection size and location. If
necessary, refer to Carrier System Design
Manual, Part 2, for system air duct design. When
designing and installing ductwork, consider the
following:
a. Size duct for 350 to 450 cfm per ton of cooling
capacity.
b. Avoid abrupt duct size increases and reductions.
c. Use flexible connectors between ductwork and
*Permissible limits of the voltage range at which the units will
operate satisfactorily
fRequired when using nonmetallic conduit
V/PH
208-230/1
" -23Ö/T-
208-230/3
460/3
OPER
VOLTAGE*
Max
253
253
253
506
COMPRESSOR ’ FAN
Min
197
187
414
LRARLA
37 5
54 0134
65 0
75.0
88 0
100 0
75 0
80 018 53 212541040
30 0
36 5
_
____
.. 1
FLAWire Size
60
69
'07”
0.9
1 7
2 512
1 114
1 6
r -9 6"
1331 5
16 2
23 3
27 732To56
13 8' ' '2 5 ■"'""14
Power
(AWG)
Ï4
14
14
14
.............
15212 " ■
14
NOTES
1
Fan motors are 208-v, 230-v or 460-v single phase
2
All units equipped with 24-v transformer for external control
circuit
Copper wire sizes based on 60 C Use copper or copper-clad
aluminum wire only.
BRANCH CIRCUIT
Max Ft
Wire
41
33
31
38
4310
135
1181415
Gnd
Wire Sizef
(AWG)Amps
14
14
1430
1235
u. ...
1415
Max
Fuse
20
30
50
6Ö
30
■ **?
Min
Circuit
Amps
”'1"2 7 "■
17.7
18 1
22 0
31 6
-"sT?"'
Ï9 8 ^
26 3
. ^ -
102
Table 3 — Accessories
PART NO.
Fh0Ta"D042'
HH93ÄZÖ44^
38CQ900141
DESCRIPTION UNIT
Honeywell thermostat | Ail
Thermostat Subbase ~j All
Solid-State Time Guard® Device
(Six 38CQ900152)
All
d. Ducts passing thru an unconditioned space must
be insulated and covered with vapor barrier in
accordance with the latest issue of SMACNA
(Sheet Metal and Air Conditioning Contractor’s
National Association) and NESCA (National
Environmental Systems Contractor’s Associa
tion) minimum installation standards for resi
dential heating and air conditioning systems.
Step 3 — Make Piping Connections
CONNECT WATER SUPPLY AND RETURN
LINES to water inlet and outlet pipe connections
shown in Fig. I and 2. Place plug in unused connec
tions. Use flexible hose for water line to reduce
possible vibration and improve unit serviceability.
Make sure hoses or pipes are suitable for system
water pressure and sized for proper flow rate.
CAUTION: Improper heat exchanger water
flow due to pjpiiîg, valving or improper pump
operation is hazardous to units.
For water flow and temperature data refer to
Start-Up section, page 4.
CAUTION: Galvanized pipe or fittings are not
recomtnended for use with these units due to
possible electrolysis.
INSTALL BALANCING VALVES (with shutoff)
in water supply and return lines for water flow
adjustment and a means of water shutoff, if neces
sary, when servicing unit. When multiple units are
conneeted to a eooling tower, valves permit removal
of one unit without interrupting water flow to other
units.
INSTALL WATER REGULATING VALVES (if
used) in water supply line near unit. Multiple unit
installations using cooling tower water do not
normally use a water regulating valve.
MAKE CONDENSATE DRAIN LINE CON
NECTION to female pipe connection provided on
unit. Fig. 2. Install a trap in condensate line as close
as possible to unit. Trap must be at least 3 in. deep
and not higher than the bottom of unit condensate
drain opening. Pitch condensate line to open drain
or sump. Insulate a condensate drain line located
above a living area.
Step 4 — Make Electrical Connections — Field
wiring must comply with local and national fire,
safety and electrical codes. Voltage to unit must be
within the operating voltage range indicated on
nameplate or in Table 2. On 3-phase units, phases
must be balanced within 2%.
Operation of unit on improper line voltage or
with excessive phase imbalance constitutes abuse
and is not covered by Carrier Warranty.
INSTALL A BRANCH CIRCUIT DISCONNECT
PER NEC of adequate size to handle unit starting
current. Locate disconnect within sight of and
readily accessible from the unit, per Section 440-14
of National Electrical Code (NEC).
BRING POWER LEADS INTO UNIT — Extend
leads from diseonnect per NEC thru hole provided
(Fig. 1) into line wiring splice box. Fig. 3.
CONNECT GROUND LEAD TO GROUND
LUG IN SPLICE BOX for safety. Connect power
wiring. See Fig. 3. Splice line power leads to yellow
and black pigtails on single-phase units or yellow
pigtails on 3-phase units. Use wire nuts. Tape each
connection.
Unit transformer on 208-230-volt units is factory
wired for 230/24-volt operation. For 208/24-volt
operation, remove black (230-v) transformer lead
from unit contactor and connect red (208-v) lead to
contactor. Cap unused transformer lead.
M
1-PHASE
CONN TO
DISCONNECTPER NEC
_____
GROUND
LEAD
—^YEL —
—^BLK —
,__^GROUND
—Hä] LUG
50WQ
HEAT PUMP
CONTROL BOX
I-PHASE
3-PHASE
CONN. TO
DISCONNECTPER NEC
_____
----- _
GROUND
LEAD
—^YEL —
^^YEL-
^^YEL-
,__^GROUND
—CöJlug
50WQ
HEAT PUMP
CONTROL BOX
3-PHASE
Fig. 3 — Line Power Connections
SET FAN MOTOR SPEED — All units are factory
wired for high fan speed operation. Set fan motor
for medium or low speed operation as follows:
1. Remove unit fan section access panel.
2. Locate Molex fan speed selector block on fan
housing, Fig. 5. Selector block receptacle 1 is
high fan speed, receptacle 2 is medium fan speed
and receptacle 3 is low fan speed. Yellow and
black fan motor power leads from control box
are connected to selector block receptacle C and
1. Yellow lead is common, black lead is speedchange lead.
3. Change fan motor speed by removing black lead
from selector block receptacle 1 and plugging it
into receptacle 2 or 3. Receptacle 4 is not used.
CAUTiONt For proper rniit operaiioit, set unit
fast inoitor ;^>eed ibr air tjuantity mtìàa range
&ÌK>wn in Tabie 4,
Set fan motor speed on 460-volt units — Two-speed
fan motor is factory wired for high-speed operation.
(Yellow and black power leads from control box are
connected to the yellow and black fan motor leads.)
Change fan motor to low speed by wiring as follows:
1. Splice the violet and black fan motor leads
together.
2. Splice yellow and black power leads from control
box to yellow and red motor leads. (Yellow-toyellow and black-to-red.)
CONNECT CONTROL POWER WIRING (24-v)
— Power leads are brought thru 1 / 2-in. hole pro
vided in unit. Fig. 1. Extend leads to low-voltage
terminal board located on top of control box. Fig. 5.
Connect leads to terminal board as shown in Fig. 3.
Use room thermostat HH01AD042 and thermo
stat subbase HH93AZ044 for proper unit operation.
Be sure that field-installed jumper wire is connected
between subbase terminals W and Y. Set thermo
stat heat anticipator at 0.45 amp for 1-phase units
and 0.50 amp for 3-phase units.
2. Ensure that water temperature entering unit is
between 45 F minimum and 90 F maximum. For
water temperature below 60 F, insulate supply
line and install a secondary drain pan under the
unit to remove condensate from heat exchanger
and internal plumbing.
CAUTION: Water teniperattJre otttside
specified temperature range may cause
damage to uiijt.
3. Ensure that supply water is clean and air is
purged from system. Air in supply water causes
scaling in heat exchanger. Foreign material in
water and/or excessive velocity of water can
cause damage to tubing.
4. When using a semi-closed system with an “open”
cooling tower, a water treatment system should
be operational with initial water flow.
To Start Unit — Ensure that air filter is in place on
unit filter flanges provided. Do not operate unit
without filter in place. Adjust the thermostat as
follows:
1. Set selector switch at OFF.
2. Turn on main disconnect switch to unit.
3. Set fan switch as desired (ON or AUTO.).
4. Set thermostat dial at desired temperature.
5. Set selector switch at HEAT or COOL.
Check system refrigerant charge. See Refrigerant
Charging on page 6.
-^Unit Single-Phase Compressors that are
equipped with a compressor start thermistor (PTC
device) — When supply voltage is within limits
indicated on nameplate and compressor will not
start, check the thermistor with an ohmmeter.
If the PTC is good, and the compressor does not
start, disconnect the PTC from the starting circuit
and give unit a temporary capacitance boost. Refer
to Carrier Standard Service Techniques Manual,
Chapter 2, for details on capacitance boost pro
cedure. If unit does not start with capacitance boost,
compressor may be defective. If unit does not start,
check starting capability with PTC assistance. If
questionable, remove PTC, add start capacitor and
start relay per start kit installation instructions.
WARNINGc Caftaciiaace boosa or ijistaliatioa
of start capadtor and start shtutki be per^
fonued by irauted persoaaet improper procedrn» couici cause tajtjry or equipoaeat
damage.
START-UP
Water Flow and Temperature Data
1. Consider design water flow rates for efficient
operation. See Table 4 for permissible water flow
range.
Unit Controls and Safety Devices
HIGH-PRESSURE RELIEF VALVE (except
50WQ0I4) is located in compressor. Relief valve
opens at a pressure differential of approximately
550 psi between suetion (low side) and discharge
(high side) to allow pressure equalization.
Loading...
+ 8 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.