Carrier 50WQ User Manual

0 (0)
Number One AirConditbninq Maker
Division of Carrier Corporation
Carrier Parkway • Syracuse NY 13221
Single-Package
SAFETY CONSIDERATIONS INTRODUCTION
...................................................
INSTALLATION....................................................2-4
Step 1 — Check Equipment and Jobsite
• UNPACKAGE UNIT
• INSPECT EQUIPMENT
• COMPLETE OR CONSIDER THESE
..................................................................
SYSTEM REQUIREMENTS
Step 2 — Connect Supply Ductwork Step 3 — Make Piping Connections
• CONNECT WATER SUPPLY AND RETURN LINES
• INSTALL BALANCING VALVES
• INSTALL WATER REGULATING VALVES
..............................
.................
..................
Page
1
2
2
2
3
INDEX
' ; '*• : '^•s\- >:■ .vt •:■ ; ': <?!v:'! ••• ■ ' .*!^ '; *r\ *i ^*;'!';'i’;*
• MAKE CONDENSATE DRAIN LINE CONNECTION
Step 4 — Make Electrical Connections.. 3,4
• INSTALL A BRANCH CIRCUIT DISCONNECT PER NEC
• BRING POWER LEADS INTO UNIT
• CONNECT GROUND LEAD TO GROUND LUG IN SPLICE BOX
• SET FAN MOTOR SPEED
• CONNECT CONTROL POWER WIRING
START-UP
............................................................
SERVICE...............................................................6
MAINTENANCE
..................................................
Page
4
10
SAFETY CONSIDERATIONS
Installation and servicing of air conditioning equipment can be hazardous due to system pressure and electrical components. Only trained and quali fied service personnel should install, repair or service air conditioning equipment.
Untrained personnel can perform basic mainten
ance functions of cleaning coils and cleaning and
replacing filters. All other operations should be performed by trained service personnel. When working on air conditioning equipment, observe precautions in the literature, tags and labels attached to the unit and other safety precautions that may apply.
Follow all safety codes. Wear safety glasses and
work gloves. Use quenching cloth for brazing
operations. Have fire extinguishers available for all
brazing operations.
WARNING; Before performing service or
mabiienaace operations oa system, turn off
rsi^ swsidr io sodoor anti and oatdoor
onit, Tam acces&oiy Sweater power switch if
applicate. shock, conld cause per-
I'duct conn
FLANGE
© Carrier Corporation 1980
Fig. 1 — Dimensions and Connections
Form 50WQ-2SI
' " Table 1
MODEL 50WQ OPER WT (lb) DIMENSIONS (ft-in.)
B 1-9-1/8 C
E
SUPPLY DUCT CONN.
(ft-in.) F
G
FILfER (1) Disposable. 1 -in thick
Size (in.)
1 014
220
A
2-10-5/16
D
0- 1-1/2 0- 1-5/8
0-11-1/4 0-10-1/4 0-10-1/4
16x20
— Installation Data (s®e Fi^- 1)
018
240
2-10-5/16 2-10-5/16 3- 2-5/16 1 0- 1-1/2 0- 1-1/2 0- 1-1/2
0- 1-5/8
0-11-1/4 0-11-1/4 0-11-1/4 1
16x20
_
022
260
1-10-1/8 (Includes Filter Section)
0- 7-5/8
0-11-7/8
16x20
027 1 033
,^270 f
1
0- 7-5/8
j
0-11-7/8
1
290
3- 2-5/16
0- 1-1/2 0- 7-5/8
0-11-1/4 0-11-7/8
20x20 20x20
3- 2-5/16
042
320
f
0-3
0- 5-7/8
0-10-1/4
1- 1-5/8
INTRODUCTION
The 50WQ units are completely self-contained
cooling and heating systems. They are water-to-air heat pumps designed for indoor installation. They may be connected into existing duct systems which are properly sized and designed to handle air quantity of 350 to 450 cfm per ton of cooling. Re quired connections include supply air duct, water supply and return lines, high- and low-voltage wiring. Factory-supplied air filter is installed in rack on unit return air section. See Table I for filter size.
Use recommended thermostat and subbase (Table 3)
for proper unit operation.
INSTALLATION
Step 1 — Check Equipment and Jobsite
UNPACKAGE UNIT — Move to final location. Slide from carton taking special care not to damage service valves or grilles.
INSPECT EQUIPMENT — File claim with ship ping company if shipment is damaged or incomplete.
COMPLETE OR CONSIDER THESE SYSTEM
REQUIREMENTS before installation:
a. Consult local building codes and National Elec
trical Code (NEC) for special installation requirements.
b. Consider type of water source. Ensure there is an
adequate supply of water at temperature of 45 F to 90 F with minimum pressure of 10 psig.
c. Provide sufficient space for water piping, con
densate drain, wiring and servicing unit. See
Fig. 1. When front (external) water piping
connections are used, locate unit so piping does
not block front access panels. (Units installed in
confined areas may have to be removed for major
servicing such as compressor or fan motor replacement.)
d. Provide a minimum 6-in. clearance between
return air filter and adjacent wall.
e. Mount 50WQ on floor or solid platform so unit is
elevated. Make sure unit is supported from the bottom. To reduce sound transmission, es pecially when 50WQ is located in a closet or utility room having louvered doors, the following
acoustical treatment is recommended; place an isolation pad under unit. Pad must be same size as unit base. Construct a 1-in. fiberglass sound shield in front of unit.
Step 2 — Connect Supply Ductwork to unit
supply air duct connection flange. Refer to Fig. 1
and Table 1 for connection size and location. If
necessary, refer to Carrier System Design Manual, Part 2, for system air duct design. When designing and installing ductwork, consider the
following:
a. Size duct for 350 to 450 cfm per ton of cooling
capacity. b. Avoid abrupt duct size increases and reductions. c. Use flexible connectors between ductwork and
unit to prevent transmission of vibration.
BALANCING VALVES (2) WITH SHUTOFF
3
MIN
w
i
SUPPLY RETURN WATER WATER
CONDENSATE TRAP
CONDENSATE DRAIN
Fig. 2 — Water Piping
'WATER
REGULATING VALVE
► AIRFLOW
i
©
Table 2 — Electrical Data (60-Hz)
MODEL
50WQ
■ "014*“
018
022
027 033
""042
" 033"-
042 033
042
FLA — Full Load Amps LRA — Locked Rotor Amps RLA — Rated Load Amps
*Permissible limits of the voltage range at which the units will
operate satisfactorily
fRequired when using nonmetallic conduit
V/PH
208-230/1
" -23Ö/T-
208-230/3
460/3
OPER
VOLTAGE*
Max
253
253 253
506
COMPRESSOR ’ FAN
Min
197
187
414
LRA RLA
37 5 54 0 134 65 0
75.0 88 0
100 0
75 0 80 0 18 5 3 2 12 54 10 40
30 0 36 5
_
____
.. 1
FLA Wire Size
60 69
'07
0.9 1 7
2 5 12
1 1 14 1 6
r -9 6"
133 1 5 16 2 23 3
27 7 32 To 56
13 8' ' '2 5 ■ "'""14
Power
(AWG)
Ï4 14 14 14
.............
152 12 " ■
14
NOTES
1
Fan motors are 208-v, 230-v or 460-v single phase
2
All units equipped with 24-v transformer for external control circuit
Copper wire sizes based on 60 C Use copper or copper-clad
aluminum wire only.
BRANCH CIRCUIT
Max Ft
Wire
41 33
31
38
43 10
135 118 14 15
Gnd
Wire Sizef
(AWG) Amps
14 14 14 30 12 35
u. ...
14 15
Max
Fuse
20 30
50 6Ö 30
■ **? Min
Circuit
Amps
”'1"2 7 "■
17.7 18 1
22 0
31 6
-"sT?"'
Ï9 8 ^ 26 3
. ^ -
102
Table 3 — Accessories
PART NO.
Fh0Ta"D042'
HH93ÄZÖ44^
38CQ900141
DESCRIPTION UNIT
Honeywell thermostat | Ail Thermostat Subbase ~j All Solid-State Time Guard® Device
(Six 38CQ900152)
All
d. Ducts passing thru an unconditioned space must
be insulated and covered with vapor barrier in accordance with the latest issue of SMACNA
(Sheet Metal and Air Conditioning Contractor’s National Association) and NESCA (National Environmental Systems Contractor’s Associa
tion) minimum installation standards for resi
dential heating and air conditioning systems.
Step 3 — Make Piping Connections
CONNECT WATER SUPPLY AND RETURN LINES to water inlet and outlet pipe connections shown in Fig. I and 2. Place plug in unused connec tions. Use flexible hose for water line to reduce possible vibration and improve unit serviceability.
Make sure hoses or pipes are suitable for system
water pressure and sized for proper flow rate.
CAUTION: Improper heat exchanger water
flow due to pjpiiîg, valving or improper pump
operation is hazardous to units.
For water flow and temperature data refer to
Start-Up section, page 4.
CAUTION: Galvanized pipe or fittings are not recomtnended for use with these units due to possible electrolysis.
INSTALL BALANCING VALVES (with shutoff)
in water supply and return lines for water flow
adjustment and a means of water shutoff, if neces sary, when servicing unit. When multiple units are conneeted to a eooling tower, valves permit removal of one unit without interrupting water flow to other units.
INSTALL WATER REGULATING VALVES (if used) in water supply line near unit. Multiple unit installations using cooling tower water do not
normally use a water regulating valve.
MAKE CONDENSATE DRAIN LINE CON
NECTION to female pipe connection provided on
unit. Fig. 2. Install a trap in condensate line as close
as possible to unit. Trap must be at least 3 in. deep
and not higher than the bottom of unit condensate
drain opening. Pitch condensate line to open drain
or sump. Insulate a condensate drain line located above a living area.
Step 4 — Make Electrical Connections — Field
wiring must comply with local and national fire, safety and electrical codes. Voltage to unit must be within the operating voltage range indicated on nameplate or in Table 2. On 3-phase units, phases must be balanced within 2%.
Operation of unit on improper line voltage or with excessive phase imbalance constitutes abuse and is not covered by Carrier Warranty.
INSTALL A BRANCH CIRCUIT DISCONNECT PER NEC of adequate size to handle unit starting current. Locate disconnect within sight of and readily accessible from the unit, per Section 440-14 of National Electrical Code (NEC).
BRING POWER LEADS INTO UNIT — Extend leads from diseonnect per NEC thru hole provided (Fig. 1) into line wiring splice box. Fig. 3.
CONNECT GROUND LEAD TO GROUND
LUG IN SPLICE BOX for safety. Connect power
wiring. See Fig. 3. Splice line power leads to yellow
and black pigtails on single-phase units or yellow
pigtails on 3-phase units. Use wire nuts. Tape each
connection.
Unit transformer on 208-230-volt units is factory wired for 230/24-volt operation. For 208/24-volt operation, remove black (230-v) transformer lead from unit contactor and connect red (208-v) lead to contactor. Cap unused transformer lead.
M
1-PHASE CONN TO DISCONNECT­PER NEC
_____
GROUND LEAD
—^YEL —
—^BLK —
,__^GROUND
—Hä] LUG
50WQ HEAT PUMP CONTROL BOX
I-PHASE
3-PHASE CONN. TO DISCONNECT­PER NEC
_____
----- _
GROUND LEAD
—^YEL —
^^YEL-
^^YEL-
,__^GROUND
—CöJlug
50WQ HEAT PUMP CONTROL BOX
3-PHASE
Fig. 3 — Line Power Connections
SET FAN MOTOR SPEED — All units are factory wired for high fan speed operation. Set fan motor for medium or low speed operation as follows:
1. Remove unit fan section access panel.
2. Locate Molex fan speed selector block on fan housing, Fig. 5. Selector block receptacle 1 is high fan speed, receptacle 2 is medium fan speed and receptacle 3 is low fan speed. Yellow and black fan motor power leads from control box are connected to selector block receptacle C and
1. Yellow lead is common, black lead is speed­change lead.
3. Change fan motor speed by removing black lead from selector block receptacle 1 and plugging it
into receptacle 2 or 3. Receptacle 4 is not used.
CAUTiONt For proper rniit operaiioit, set unit
fast inoitor ;^>eed ibr air tjuantity mtìàa range
&ÌK>wn in Tabie 4,
Set fan motor speed on 460-volt units — Two-speed fan motor is factory wired for high-speed operation. (Yellow and black power leads from control box are connected to the yellow and black fan motor leads.)
Change fan motor to low speed by wiring as follows:
1. Splice the violet and black fan motor leads together.
2. Splice yellow and black power leads from control box to yellow and red motor leads. (Yellow-to­yellow and black-to-red.)
CONNECT CONTROL POWER WIRING (24-v)
— Power leads are brought thru 1 / 2-in. hole pro vided in unit. Fig. 1. Extend leads to low-voltage terminal board located on top of control box. Fig. 5.
Connect leads to terminal board as shown in Fig. 3.
Use room thermostat HH01AD042 and thermo stat subbase HH93AZ044 for proper unit operation. Be sure that field-installed jumper wire is connected between subbase terminals W and Y. Set thermo stat heat anticipator at 0.45 amp for 1-phase units and 0.50 amp for 3-phase units.
2. Ensure that water temperature entering unit is between 45 F minimum and 90 F maximum. For water temperature below 60 F, insulate supply line and install a secondary drain pan under the unit to remove condensate from heat exchanger and internal plumbing.
CAUTION: Water teniperattJre otttside
specified temperature range may cause damage to uiijt.
3. Ensure that supply water is clean and air is purged from system. Air in supply water causes scaling in heat exchanger. Foreign material in water and/or excessive velocity of water can cause damage to tubing.
4. When using a semi-closed system with an “open” cooling tower, a water treatment system should be operational with initial water flow.
To Start Unit — Ensure that air filter is in place on
unit filter flanges provided. Do not operate unit without filter in place. Adjust the thermostat as follows:
1. Set selector switch at OFF.
2. Turn on main disconnect switch to unit.
3. Set fan switch as desired (ON or AUTO.).
4. Set thermostat dial at desired temperature.
5. Set selector switch at HEAT or COOL.
Check system refrigerant charge. See Refrigerant
Charging on page 6.
-^Unit Single-Phase Compressors that are
equipped with a compressor start thermistor (PTC device) — When supply voltage is within limits indicated on nameplate and compressor will not start, check the thermistor with an ohmmeter.
If the PTC is good, and the compressor does not start, disconnect the PTC from the starting circuit and give unit a temporary capacitance boost. Refer to Carrier Standard Service Techniques Manual, Chapter 2, for details on capacitance boost pro cedure. If unit does not start with capacitance boost, compressor may be defective. If unit does not start, check starting capability with PTC assistance. If questionable, remove PTC, add start capacitor and
start relay per start kit installation instructions.
WARNINGc Caftaciiaace boosa or ijistaliatioa of start capadtor and start shtutki be per^ fonued by irauted persoaaet improper pro­cedrn» couici cause tajtjry or equipoaeat
damage.
START-UP
Water Flow and Temperature Data
1. Consider design water flow rates for efficient operation. See Table 4 for permissible water flow range.
Unit Controls and Safety Devices
HIGH-PRESSURE RELIEF VALVE (except 50WQ0I4) is located in compressor. Relief valve opens at a pressure differential of approximately 550 psi between suetion (low side) and discharge (high side) to allow pressure equalization.
Loading...
+ 8 hidden pages