50VT
Performancet Single ---Packaged Heat Pump Units with PuronR
(R ---410A) Refrigerant
S i n g l e --- A n d T h r e e --- P h a s e
2 to 5 Nominal Tons (Sizes 024--- 060)
Product Data
Durable, dependable components Compressors are designed
for high efficiency. Each compressor is hermetically sealed against
contamination to help promote longer life and dependable
operation. Each compressor also has vibration isolation to provide
quieter operation. All compressors have internal high pressure and
overcurrent protection.
Direct-- drive multi--speed brushless DC blower motoris
standard on all 50VT models. Direct --drive, PSC condenser--fan
motors are designed to help reduce energy consumption and
provide for cooling operation down to 40_F(4.4_C) outdoor
temperature. MotormasterR II low ambient kit is available as a
field installed accessory.
Thermostat Controls designed to work as a system with Carrier’s
small packaged product.
Thermostatic Expansion Valve -- A hard shutoff, balance port
TXV maintains a constant superheat at the evaporator exit (cooling
cycle) resulting in higher overall system efficiency.
Refrigerant system is designed to provide dependability. Liquid
filter driers are used to promote clean, unrestricted operation. Each
unit leaves the factory with a full refrigerant charge. Refrigerant
service connections make checking operating pressures easier.
A99001
Fig. 1 -- Unit 50VT
Single--Packaged Products with Energy-- Saving Features and
PuronR refrigerant.
S Up to 14.5 SEER
S 8.0 HSPF
S 12 EER at 95_F(35_C) OD
S Factory-- Installed TXV
S Multi--Speed Blower--Standard
FEATURES/BENEFITS
One--piece Heat Pump unit with optional electric heater, low
installation cost, dependable performance and easy maintenance.
Efficient operation High--efficiency designwith SEERs
(Seasonal Energy Efficiency Ratio) of up to 14.5.
Puron Environmentally Sound Refrigerant is Carrier’s unique
refrigerant designed to help protect the environment. Puron is an
HFC refrigerant which does not contain chlorine that can harm the
ozone layer. Puron refrigerant is in service in millions of systems,
proving highly reliable, environmentally sound performance.
Easy Installation
Factory--assembled package is a compact, fully self--contained,
heat pump unit that is prewired, pre--piped, and pre--charged for
minimum installation expense. These units are available in a
variety of standard capacity ranges with voltage options to meet
residential and light commercial requirements. Units are
lightweight and install easily on a rooftop or at ground level. The
high tech composite base eliminates rust problems associated with
ground level applications.
High and Low Pressure Switches provide added reliability for the
compressor.
Indoor and Outdoor coils are computer--designed for optimum
heat transfer and efficiency. The indoor coil is fabricated from
copper tube and aluminum fins and is located inside the unit for
protection against damage. The outdoor coil is internally mounted
on the top tier of the unit. Copper fin coils and pre--coated fin coils
are available from the factory by special order. These coils are
recommended in applications where aluminum fins are likely to be
damaged due to corrosion. They are ideal for seacoast applications.
Low sound ratings ensure a quiet indoor and outdoor
environment with sound ratings as low as 72dBA.
Easy to service cabinets provide easy single--panel accessibility to
serviceable components during maintenance and installation. The
base with integrated drain pan provides easy ground level
installation with or without a mounting pad. Convenient
hand--holds are provided to manipulate the unit on the jobsite. A
nesting feature ensures a positive basepan to roof curb seal when
the unit is roof mounted. A convenient 3/4--in. wide perimeter
flange makes frame mounting on a rooftop easy.
Convertible duct configuration
Unit is designed for easy use in either downflow or horizontal
applications. Each unit is easily converted from horizontal to
downflow with the two duct covers, standard on 3 phase units and
available as an accessory for single phase units. Downflow
operation is easily provided in the field to allow vertical ductwork
connections. The basepan utilizes knockout style seals on the
bottom openings to ensure a positive seal in the horizontal airflow
mode.
Cabinets are constructed of heavyduty, phosphated, zinc--coated
prepainted steel capable of withstanding 500 hours in salt spray.
Interior surfaces of the evaporator and electric heater compartments
are insulated with cleanable semi--rigid insulation board, which
1
Page 2
keeps the conditioned air from being affected by the outdoor
A
ambient temperature and provides improved indoor air quality.
(Conforms to American Society of Heating, Refrigeration and Air
Conditioning Engineers No. 62P.) The sloped drain pan minimizes
standing water in the drain. An external drain is provided.
Short--Cycling protection for the compressor is incorporated into
our defrost control board ensuring a five minute delay (+/ --2
minutes) before restarting compressor after shutdown for any
reason.
50VT
MODEL NUMBER NOMENCLATURE
Typ e of Un i t
50VT --- Single Packaged
Heat Pump Unit
AD --- Louvered Grille
BT --- AL evap, vinyl condenser
CC --- AL evap, CU condenser
CU --- CU evap & condenser
TP --- Base unit with tin plated indoor coil hairpins
TV --- TP with vinyl coating on outdoor coil
TC --- TP with AL indoor coil & CU/CU outdoor coil
See Price Page fo r full l ist of f actory options.
Only used if ordering an option
N/A
ISO 9001:2000
REGISTERED
s an Energy Star® Partner, Carrier
Corporation has determined that this
product meets the ENERGY STAR®
guidelines for energy efficiency.
d B --- Sound Levels (decibels)
db—Dry Bulb
SEER—Seasonal Energy Efficiency Ratio
wb—Wet Bulb
COP--- Coefficient of Performance
HSPF ---Heating Season Performance Factor
* Air Conditioing & Refrigeration Institute.
**At “A” conditions - -- 80_ F (26.7_C) indoor db/67_F (19.4_C) indoor wb &
95_F(35_C) outdoor db.{ Rated in accordance with U.S. Government DOE Department of Energy)
test procedures and/or ARI Standards 210/240.
(BTUH) @ 47 ˚F
(8.3 ˚C)
COP @ 47 ˚F(8.3˚C)
HEATING CAPACITY
(BTUH) @ 17 ˚F
( --- 8 . 3 ˚C)
Notes:
1. Ratings are net values, reflecting the effects of circulating fan heat.
Ratings are based on:
Cooling Standard: 80°F (26.7_C) db, 67°F ( 19.4_C ) w b i n do o r e n t e r in g ---
air temperature and 95°F(35_C)dboutdoorentering---airtemperature.
2. Before purchasing this appliance, read important energy cost and efficiency information available from your retailer.
COP @ 17˚F
( --- 8 . 3 ˚C)
HSPF
50VT
3
Page 4
PHYSICAL DA TA -- UNIT 50VT
UNIT SIZE50VT02450VT03050VT03650VT04250VT04850VT060
NOMINAL CAPACITY (ton)22.533.545
OPERATING WEIGHT} (lb)
COMPRESSOR QUANTITY1
Refrigerant (R --- 410A) Quantity (lb)
Diameter Motor HP (RPM)
Nominal Cooling Airflow (CFM)
50VT
HIGH --- PRESSURE SWITCH (psig)
L O S S --- O F --- C H A R G E / L O W --- P R E S S U R E
RETURN--- AIR FILTERS*{
*Required filter sizes shown are based on the larger of the ARI (Air conditioning and Refrigeration Institute) rated cooling airflow or the heating airflow velocity of
300 ft/minute for throwaway type or 450 ft/minute for high ---capacity type. Air filter pressure drop for non ---standard filters must not exceed 0.08 IN. W.C.
{ If using accessory filter rack refer to the filter rack installation instructions for correct filter size and quantity.
} For 460 volt units, add 14 lb (6.4 kg) to the weight.
NOTE: Tested in accordance with ARI Standard 270---95 (not listed in ARI).
RATING
(dBA)
1252505001000200040008000
TYPICAL OCTAVE BAND SPECTRUM (dBA) (without tone adjustment)
4
Page 5
OPTIONS AND ACCESSORIES
Factory--installed options
Louver grille provides hail and vandalism protection. A wire grille
is standard on all models. See model number nomenclature for
louver grille options.
Coil options include copper/copper and vinyl--coated construction
for refrigerant coils. Units are shipped standard with copper
tube/aluminum fin construction. See model number nomenclature
for coil options.
Field--installed accessories
Economizer with Solid -- State Controls and Barometric
Relief Dampers
Manual Air Damper (25% open)
Electric Heaters
Filter Rack
Flat Roof Curbs (8--in. [203 mm]and 14 --in. ]356 mm])
Square--to--Round Duct Transition Kit
Thermostats
Crankcase Heater
Compressor Start Kit (for use on single--phase units only)
Rigging Kit
Low Ambient Kit (Motormaster® II Control)
Economizer with solid--state controls and barometric relief
dampers includes filter racks and provide outdoor air during
cooling and reduce compressor operation.
Manual outside air damper includes hood and filter rack with
adjustable damper blade for up to 25% outdoor air.
Electric heaters provide additional heat in the unit when required.
Each package has a heater module that slides into the controls
compartment. Heater sizes range from 5.0 to 20.0 kW. The electric
heater design allows the use of a single--point power supply for the
entire unit, resulting in lower installed costs.
Filter rack features easy installation, serviceability, and
high--filtering performance for vertical applications.
Flat roof curbs in both 8 in. (203 mm) and 14 in. (356 mm) sizes
are available for roof mounted applications.
Square--to--round duct transition kit enables 024--048 size units
to be fitted to 14 in. (356 mm) round ductwork.
Corporate Thermostats provide control for the system heating
and cooling functions. Thermostat models are available in both
programmable and non--programmable versions.
Crankcase heater provides anti--floodback protection for
low--load cooling applications.
Compressor start kit assists compressor start--up by providing
additional starting torque on single phase units and prolongs
compressor motor life.
Rigging kit includes lifting brackets which are inserted into the
unit base rigging holds to lift unit for rooftop applications.
Low--ambient kit (Motormaster II control) allows the use of
mechanical cooling down to outdoor temperatures as low as 0_F
(--18_C) when properly installed.
8. When unit mounting screw is used (see Note A) , a retainer bracket must
be used as well. This bracket must also be used when required by code for
hurricane or seismic conditions. This bracket is available through Micrometl.
*For 460 volt units add 14 lb (6.4 kg) to the weight.
NOTE: See dimensional drawing for corner weight distribution. Corner weights shown on drawing are based on unit---only weights and do not include pack-
aging.
SELECTION PROCEDURE (WITH EXAMPLE)
1. Determine cooling and heating requirements at
design conditions:
2. Select unit based on required cooling capacity.
Enter Net Cooling Capacities table at condenser entering
temperature of 95°F(35°C). Unit 036 at 1200 cfm and 67°F
(19°C) ewb (entering wet bulb) will provide a total capacity of
36,000 Btuh and a SHC of 27,400 Btuh. Calculate SHC correction,
if required, using Note 4 under Cooling Capacities tables.
3. Select heating capacity of unit to provide design
condition requirement.
In the Heating Capacities and Efficiencies table, note that the 036
size unit will deliver 34,800 BTUH at the ARI high temp rating
point. To achieve 60,000 BTUH, accessory electric heat will be
required. Use the Balance Point Worksheet to plot the load line
with the unit capacity. The difference between the load line and
unit capacity at the design heating temperature is the amount of
electric heat that will be required.
024030
lbkglbkglbkglbkglbkglbkg
354171364165
317144327148
Unit
Shipping
Weight
Rigging
Weight
036*042*048*060*
419190464210484220514233
382173427164447203477216
4. Determine fan speed and power requirements at
design conditions.
Before entering the air delivery tables, calculate the total static
pressure required. From the given example, the Wet Coil Pressure
Drop Table, and the Filter Pressure Drop Table:
External Static Pressure0.200 IN. W.C.
Filter0.130 IN. W.C.
Wet Coil Pressure Drop0.18
IN. W.C.
Total Static Pressure0.51 IN. W.C.
Enter the table for Dry Coil Air Delivery— At 0.50 IN. W.C.
ESP (external static pressure) and MED--LOW speed the motor
delivers 1140 cfm. To achieve 1200 cfm, a higher speed tap is
required.
5. Select unit that corresponds to power source
available.
The Electrical Data Table shows that the unit is designed to operate
at 208/230--1--60.
A08005
50VT
11
Page 12
KW
Sys
KW
Sys
To t a l
Tot a l
MBtuh
Capacity
Tot a lInteg
Capacity MBtuh
KW
Sys
Tot a l
KW
Sys
To t a l
MBtuh
Capacity
KW
Sys
Capacity MBtuh
50VT
KW
Sys
To t a l
Tot a l
MBtuh
Capacity
KW
Sys
Tot a l
Capacity MBtuh
KW
Sys
To t a l
CONDENSER ENTERING AIR TEMPERATURES deg F
Capacity MBtuh
MBtuh
Capacity
KW
Sys
Tot a l
EVAPORATOR AIR
758595105115125
To t a l
To t a l
Capacity MBtuh
Capacity MBtuh
MBtuh
KW
Sys
KW
Sys
To t a lSensTo t a lSensTo t a lSensTo t a lSensTo t a lSensTo ta lSens
*At 75_F (23.9 _C) entering dry bulb—Tennessee Valley Authority [TVA] rating conditions; all others at 80_F (26.7 _C) entering dry bulb. See Legend and Notes.
*At 75_F (23.9 _C) entering dry bulb—Tennessee Valley Authority [TVA] rating conditions; all others at 80_F (26.7 _C) entering dry bulb. See Legend and Notes.
*At 75_F (23.9 _C) entering dry bulb—Tennessee Valley Authority [TVA] rating conditions; all others at 80_F (26.7 _C) entering dry bulb. See Legend and Notes.
*At 75_F (23.9 _C) entering dry bulb—Tennessee Valley Authority [TVA] rating conditions; all others at 80_F (26.7 _C) entering dry bulb. See Legend and Notes.
*At 75_F (23.9 _C) entering dry bulb—Tennessee Valley Authority [TVA] rating conditions; all others at 80_F (26.7 _C) entering dry bulb. See Legend and Notes.
*At 75_F (23.9 _C) entering dry bulb—Tennessee Valley Authority [TVA] rating conditions; all others at 80_F (26.7 _C) entering dry bulb. See Legend and Notes.
1. Ratings are net; they account for the effects of the evaporator--- fan motor power and heat.
2. Direct interpolation is permissible. Do not extrapolate.
t
3. The following formulas may be used:
lwb =
t
lwb)
h
ewb = Enthalpy of air en tering evaporator coil
air leaving evaporator coil (
h
4. The SHC is based on 80_F (26.7 _C) edb temperature of air entering evaporator coil. Below 80_F (26.7_C) edb, subtract (corr factor x cfm) from SHC. Above 80_F (26.7_C) edb, add (corr factor x cfm) to SHC.
Where:
Correction Factor = 1.10 x (1 + BF) x (edb + 80).
5. Integrated capacity is maximum (instantaneous) capacity less the effect of frost on the outdoor coil and the heat required to defrost it.
18
Page 19
PERFORMANCE DATA (CONT)
Wet Coil Air Delivery 50VT036--060 -- Downflow Discharge -- High Speed
50VT060CFM2113204919791911184017711681161415241418
* Air delivery values are without air filter and are for wet coil.
Note: Deduct field ---supplied air filter pressure drop to obtain external static pressure available for ducting.
BF — Bypass Factor
e d b — E n t e r i n g Dr y --- B u l b
Ewb — Entering Wet---Bulb
kW — Total Unit Power Input
SHC — Sensible Heat Capacity (1000 Btuh)
TC — Total Capacity (1000 Btuh) (net)
rh—Relative Humidity
COOLING NOTES:
1. Ratings are net; they account for the effects of the evaporator---fan motor
power and heat.
2. Direct interpolation is permissible. Do not extrapolate.
3. The following formulas may be used:
t
ldb =tedb
--
240
480
Sensible capacity
1.10 x cfm
(Btuh)
200
208
230
240
460
Wet--- bulb temperature corresponding to enthalpy
t
lwb =
air leaving evaporator coil (
total capacity (Btuh)
h
lwb =he w b ---
4.5 x cfm
h
ewb = Enthalpy of air en tering evaporator coil
Where:
4. The SHC is based on 805 F (26.6_C) edb temperature of air entering evaporator coil. Below 805 F (26.6_C) edb, subtract (corr factor x cfm) from SHC.
Above 805 F (26.6_C) edb, add (corr factor x cfm) to SHC.
Correction Factor = 1.10 x (1 + BF) x (edb + 80).
5. Integrated capacity is maximum (instantaneous) capacity less the effect of
frost on the outdoor coil and the heat required to defrost it.
h
0.69
0.75
0.92
1.00
0.92
lwb)
50VT
Electric Heat Pressure Drop Table
Small Cabinet: 024--030 cfm
Condensate trap — A 2-- in. (51 mm) condensate trap must be
field supplied.
1” (25 mm) MIN
Ductwork — Secure downflow discharge ductwork to roof curb.
For horizontal discharge applications, attach ductwork to unit with
flanges.
To convert a unit to downflow discharge — Units are equipped
with factory--installed inserts in the downflow openings. Removal
of the inserts is similar to removing an electrical knock-- out. Units
installed in horizontal discharge orientation do not require duct
covers.
.
TRAP
OUTLET
2” (51 mm) MIN.
A08001
Maximum cooling airflow — To minimize the possibility of
condensate blow--off from the evaporator, airflow through the units
should not exceed 450 cfm per ton.
Minimum cooling airflow — Minimum cooling airflow is 350
cfm per ton in cooling mode. Airlow can be lower in certain modes
when humidity removal is an issue however, low airflow could
result in indoor coil freezing and/or refrigerant floodback.
Minimum ambient cooling operation temperature —All
standard units have a minimum ambient cooling operating
temperature of 40_F(4.4_C). With accessory low ambient
temperature kit, units can operate at temperatures down to 0_F
(17.8_C).
Maximum operating outdoor air temperature for cooling is
125_F (51.7_C).
1. In compliance with NEC (National Electrical Code) requirements
for multimotor and combination load equipment (refer to NE C
Articles 430 and 440), the overcurrent protective device for the
unit shall be Power Supply fuse. The CGA (Canadian Gas
Association) units may be fuse or circuit break er.
2. Minimum wire size is based on 60 C copper wire. I f other than
60 C wire is used, or if length exceeds wire length in table,
determine siz e from NEC..
3. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is greater than 2%.
the percentage of voltage imbalance.
Use the following formula to determine
% Voltage imbalance
= 100 x
max voltage deviation from average voltage
average voltage
50VT
EXAMPLE: Supply voltage is 230-3-60.
AB = 228 v
BC = 231 v
(R)
AC = 227 v
Average Voltage =
228 + 231 + 227
3
686
=
3
= 229
Determine maximum deviation from average voltage.
(AB) 229 (BC) 231 (AC) 229 -
228 =1v
229 =2v
227 =2v
Maximum deviation is 2 v.
Determine percent of voltage imbalance.
% Voltage Imbalance = 100 x
2
229
= 0.8%
This amount of phase imbalance is satisfactory as it is below the
maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is
more than 2%, contact your local electric utility company
immediately.
A06564
24
Page 25
TYPICAL WIRING SCHEMATIC -- 208/230--1--60
50VT
A08024
25
Page 26
TYPICAL WIRING SCHEMATIC -- 208/230--3--60
50VT
A08025
26
Page 27
TYPICAL WIRING SCHEMATI C -- 460--3--60
50VT
A08026
27
Page 28
CONTROLS
Operating sequence
When power is supplied to unit, the transformer (TRAN) is
energized.
On units with crankcase heater, heater is also energized.
Cooling — With the thermostat in the cooling position, the
thermostat makes circuit R--O. This energizes the reversing valve
solenoid (RVS) and places the unit in standby condition for
cooling.
As the space temperature rises, the thermostat closes circuit R--Y.
A circuit is made to contactor (C), starting the compressor (COMP)
and outdoor--fan motor (OFM). Circuit R--G is made at the same
time and starts the indoor--fan motor (IFM).
When the thermostat is satisfied, contacts open, deenergizing C.
The COMP and OFM stop, and the IFM stops after the preselected
time delay.
Heating — On a call for heat, thermostat makes circuites R--Y and
R--G.
A circuit is made to C, starting COMP and OFM. Circuit R--G also
is complted, energizing IFR and starting IFM after the selected time
50VT
delay.
Should room temperature continue to fall, circuit R-- W is made
through second-- stage thermostat. If optional electric heat package
is used, a relay is energized, bringing on first bank of supplemental
electric heat. When thermostat is satisfied, contacts open,
deenergizing contactor and relay; motors and heaters deenergize.
Defro st — Defrost board (DB) is a time and temperature control,
which includes a field--selectable time period (dip switch 1 and 2
on the board) between checks for defrost (30, 60, 90, or 120
minutes). Electronic timer and defrost cycle start only when
contactor is energized and defrost thermostat (DFT) is closed.
The defrost board is also equipped with a third dip switch for
selecting Quiet Shift operation. The Quiet Shift operation turns
compressor off at defrost initiation and termination. Unit is factory
shipped with quiet shift turned off.
Defrost mode is identical to cooling mode, except outdoor fan
motor stops and a bank of optional electric heat turns on to warm
air supplying the conditioned space.
NOTE:
1. Compressor time delay occurs through the defrost control
board.
2. Defrost control board has built in 5 minute compressor
delay; once the compressor has started and then stopped, it
cannot be restarted again until 5 minutes have elapsed.
28
Page 29
GUIDE SPECIFICATIONS (CONT)
Packaged Heat Pumps
HVAC Guide Specifications
Size Range: 2to5Tons,NominalCooling
Carrier Model Number: 50VT
Part 1⎯General
SYSTEM DESCRIPTION
Outdoor,packaged,air--to--air heatpump unitutilizing a hermetic
scroll compressor for cooling duty and optional electric heating.
Unit shall discharge supplyairvertically or horizontally asshown
on contract drawings. Outdoor fan/coil section shall have a
draw-- thru design with vertical discharge for minimum sound
levels.
QUALITY ASSURANCE
A. Unit shall be rated in accordance with ARI Standards 210/240
and 270.
B. Unit shall be designed in accordance with UL Standard
1995.
C. Unit shall be manufactured in a facility registered to ISO 9001
manufacturing quality standard.
D. Unit shall be UL listed and c--UL certified as a total package
for safety requirements.
E. Roof curb shall be designed to conform to NRCA Standards.
F. Insulation and adhesives shall meet NFPA 90A requirements
for flame spread and smoke generation.
G. Cabinet insulation shall meet ASHRAE Standard 62P.
DELIVERY, STORAGE AND HANDLING
Unit shall be stored and handled per manufacturer’s
recommendations.
Part 2 ⎯ Products
EQUIPMENT
A. General:
Factory--assembled, single--piece, heat pump unit. Contained
within the enclosure shall be all factory wiring, piping, controls,
refrigerant charge (R--22), and special features required prior to
field start-- up.
B. Unit Cabinet:
1. Unit cabinet shall be constructed of phosphated,
zinc-- coated, pre--painted steel capable of withstanding 500
hours of salt spray.
2. Normal service shall be through a single removable cabinet
panel.
3. The unit shall be constructed on a rust proof unit base that
has an externally trapped, integrated sloped drain.
4. Indoor fan compartment top surface shall be insulated with
a minimum 1/2--in. (13 mm) thick, flexible fiberglass
insulation, coated on the air side and retained by adhesive
and mechanical means. The indoor wall sections will be
insulated with a minimum semi--rigid, foil-- faced board
capable of being wiped clean. Aluminum foil-- faced
fiberglass insulation shall be used in the entire indoor air
cavity section.
5. Unit shall have a field--supplied condensate trap.
6. Metal Insulated Duct Covers for side discharge will be
standard on all sizes.
7. Unit insulation conforms to ASHRAE 62P.
C. Fans:
1. The indoor fan shall be 5--speed, direct--drive, as shown on
equipment drawings.
2. Fan wheel shall be made from steel and shall be
double--inlet type with forward--curved blades with
corrosion resistant finish. Fan wheel shall be dynamically
balanced.
3. Outdoor fan shall be direct--drive, propeller--type with
aluminum blades riveted to corrosion resistant steel spiders,
be dynamically balanced, and discharge air vertically.
D. Compressor:
1. Fully hermetic compressors with factory--installed vibration
isolation.
2. Scroll compressors shall be standard on all units.
3. Compressor Protection:
Defrost control shall protect compressor by preventing
“short cycling.”
E. Coils:
Indoor and outdoor coils shall have aluminum plate fins
mechanically bonded to seamless copper tubes with all joints
brazed. (Copper/copper and vinyl--coated construction available
as option.) Tube sheet openings shall be belled to prevent tube
wear.
F. Refrigerant Metering Device:
Refrigerant metering device shall be thermostatic expansion
valve for cooling, and fixed orifice for heating.
G. Filters:
Filter section shall consist of field--installed, throwaway, 1--in.
(25 mm) -- thick fiberglass filters of commercially available
sizes.
H. Controls and Safeties:
1. Unit controls shall be complete with a self--contained, low-voltage control circuit.
2. Units shall incorporate an internal compressor protector that
provides reset capability.
I. Operating Characteristics:
1. Unit shall be capable of starting and running at 125_F
(51.7_C) ambient outdoor temperature.
2. Compressor with standard controls shall be capable of
operation down to 40_F(4.4_C) ambient outdoor
temperature in cooling mode.
3. Unit shall be provided with 60--second fan time delay after
the thermostat is satisfied.
J. Electrical Requirements:
All unit power wiring shall enter the unit cabinet at a single
location.
K. Motors:
1. Compressor motors shall be of the refrigerant--cooled type
with line--break thermal and current overload protection.
2. All fan motors shall have permanently lubricated bearings,
and inherent, automatic reset, thermal overload protection.
3. Condenser fan motor shall be totally enclosed.
L. Special Features Available:
1. Louvered Grille:
Wire grille shall be standard on all units. Louvered grille
shall be available as a factory--installed option to provide
hail guard and vandalism protection.
2. Coil Options:
Shall include factory--installed optional copper/copper and
vinyl--coated refrigerant coils.
3. Economizer:
a. Economizer controls capable of providing free cooling
using outside air.
b. Equipped with low leakage dampers not to exceed 3%
leakage, at 1.0 in. wc pressure differential.
c. Spring return motor shuts off outdoor damper on power
failure.
29
50VT
Page 30
GUIDE SPECIFICATIONS (CONT)
4. Flat Roof Curb:
Curbs shall have seal strip and a wood nailer for flashing
and shall be installed per manufacturer’s instructions.
5. Manual Outdoor Air Damper:
Package shall consist of damper, birdscreen, and rainhood
which can be preset to admit outdoor air for year--round
ventilation.
6. Thermostat:
To provide for two--stage heating and one-- stage cooling in
addition manual or automatic changeover and indoor fan
control.
7. Low Ambient Package:
Shall consist of a solid--state control and outdoor coil temperature sensor for controlling outdoor--fan motor operation, which shall allow unit to operate down to 0_F
(--17.7_C) outdoor ambient temperature.
50VT
8. Filter Rack Kit:
Shall provide filter mounting for downflow applications.
9. Square--To--Round Duct Transitions (024--048):
Shall have the ability to convert the supply and return openings from rectangular to round.
10. Crankcase Heater:
Shall provide anti--floodback protection for lowload cooling
applications.
11. Electric heaters:
a. Electric heater shall be available as a field installed
option.
b. Heater elements shall be open wire type, adequately
supported and insulated with ceramic bushings.
c. Electric heater packages must provide single point
power connection capability.
Copyright 2008 Carrier Corp. D 7310 W. Morris St. D Indianapolis, IN 46231Printed in U.S.A.Edition Date: 05/08
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
Catalog No:50VT--- 01PD
Replaces: NEW
30