Carrier 50RHC, RVS, RDS006-060, RVC, RHR User Manual

...
50RHC,RVC,RHR,RHS,
RVR,RVS,RDS006-060
Water Source Heat Pump Units
Installation, Start-Up, and
Service Instructions
AQUAZONE™
CONTENTS
Page
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-26
Step 1 — Check Jobsite. . . . . . . . . . . . . . . . . . . . . . . . 2
Step 2 — Check Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
• STORAGE
•PROTECTION
•INSPECT UNIT
Step 3 — Unit Location. . . . . . . . . . . . . . . . . . . . . . . . . . 14
• FIELD CONVERSION OF DISCHARGE AIR
Step 4 — Mounting the Unit . . . . . . . . . . . . . . . . . . . . . 15
• HORIZONTAL UNITS
• VERTICAL UNITS
Step 5 — Duct System . . . . . . . . . . . . . . . . . . . . . . . . . . 15
• SO U N D AT T E NUATIO N
• EXISTING DUCT SYSTEM
Step 6 — Condensate Drain . . . . . . . . . . . . . . . . . . . . . 16
• HORIZONTAL UNITS
• VERTICAL UNITS
• VENTING
Step 7 — Piping Connections . . . . . . . . . . . . . . . . . . . 16
• WATER LOOP APPLICATIONS
• GROUND-WATER APPLICATIONS
• GROUND-LOOP APPLICATIONS
Step 8 — Field Power Supply Wiring . . . . . . . . . . . . 18
• POWER CONNECTION
• SUPPLY VOLTAGE
• 208-VOLT OPERATION
Step 9 — Field Control Wiring. . . . . . . . . . . . . . . . . . . 18
• THERMOSTAT CONNECTIONS
• WATER FREEZE PROTECTION
• AIR COIL FREEZE PROTECTION
• ACCESSORY CONNECTIONS
• WATER SOLENOID VALVES
PRE-START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26-30
System Checkout. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
PSC Blower Speed Selection . . . . . . . . . . . . . . . . . . 27
FIELD SELECTABLE INPUTS . . . . . . . . . . . . . . . 30-32
C Control DIP Switches . . . . . . . . . . . . . . . . . . . . . . . 30
D Control DIP Switches . . . . . . . . . . . . . . . . . . . . . . . 30
Units with Modulating Hot Water Reheat
(HWR) Option . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
D Control Accessory Relay Configurations . . . . . 32
START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32-36
Operating Limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Scroll Compressor Rotation. . . . . . . . . . . . . . . . . . . . . 33
Unit Start-Up Cooling Mode . . . . . . . . . . . . . . . . . . . . . 33
Unit Start-Up Heating Mode . . . . . . . . . . . . . . . . . . . . . 34
Flow Regulation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Page
Flushing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Antifreeze . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Cooling Tower/Boiler Systems . . . . . . . . . . . . . . . . . . 36
Ground Coupled, Closed Loop and Plateframe
Heat Exchanger Well Systems . . . . . . . . . . . . . . . . 36
OPERATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .36,37
Power Up Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Units with Aquazone Complete C Control . . . . . . . 36
Units with Aquazone Deluxe D Control. . . . . . . . . . 36
Units with HWR Option. . . . . . . . . . . . . . . . . . . . . . . . . . 37
SYSTEM TEST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37,38
Test Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Retry Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Aquazone Deluxe D Control LED Indicators . . . . . 38
SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38-40
Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Water Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Condensate Drain Pans . . . . . . . . . . . . . . . . . . . . . . . . . 38
Refrigerant System. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Compressor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Fan Motors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Condensate Drain Cleaning . . . . . . . . . . . . . . . . . . . 39
Air Coil Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Condenser Cleaning. . . . . . . . . . . . . . . . . . . . . . . . . . 39
Checking System Charge . . . . . . . . . . . . . . . . . . . . . 39
Refrigerant Charging . . . . . . . . . . . . . . . . . . . . . . . . . 40
Air Coil Fan Motor Removal . . . . . . . . . . . . . . . . . . . . . 40
TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . 40-42
Thermistor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Control Sensors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
50RHC,RVC,RHR,RHS,RVR,RVS,RDS
START-UP CHECKLIST . . . . . . . . . . . . . . . . . . CL-1, CL-2
IMPORTANT: Read the entire instruction manual before starting installation.
SAFETY CONSIDERATIONS
Installation and servicing of air-conditioning equipment can be hazardous due to system pressure and electrical compo­nents. Only trained and qualified service personnel should install, repair, or service air-conditioning equipment.
Untrained personnel can perform basic maintenance func­tions of cleaning coils and filters and replacing filters. All other operations should be performed by trained service personnel. When working on air-conditioning equipment, observe precau­tions in the literature, tags and labels attached to the unit, and other safety precautions that may apply.
Improper installation, adjustment, alteration, service, mainte­nance, or use can cause explosion, fire, electrical shock or other conditions which may cause personal injury or property dam­age. Consult a qualified installer, service agency, or your distrib­utor or branch for information or assistance. The qualified in­staller or agency must use factory-authorized kits or accessories when modifying this product. Refer to the individual instruc­tions packaged with the kits or accessories when installing.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4 Ta b 5 a 5 a
Catalog No. 04-53500007-01 Printed in U.S.A. Form 50R-5SI Pg 1 6-07 Replaces: 50R-4SI
Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth for brazing operations. Have fire extinguisher available. Read these instructions thoroughly and follow all warnings or cautions attached to the unit. Consult local building codes and the National Electrical Code (NEC) for special installation requirements.
Understand the signal words — DANGER, WARNING, and CAUTION. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARN­ING signifies hazards that could result in personal injury or death. CAUTION is used to identify unsafe practices, which would result in minor personal injury or product and property damage.
Recognize safety information. This is the safety-alert symbol ( ). When you see this symbol on the unit and in instructions or manuals, be alert to the potential for personal injury.
adequate space around the unit for servicing. See Fig. 1-3 for overall unit dimensions. Refer to Fig. 4 for an illustration of a typical horizontal installation.
VERTICAL AND DOWNFLOW UNITS (50RVC,RVR, RVS,RDS) — Vertical units are designed for indoor installa­tions. While vertical units are typically installed in a floor-level closet or a small mechanical room, the unit access guidelines for these units are very similar to those described for horizontal units. See Fig. 5-8 for overall dimensions. Refer to Fig. 9 for an example of a typical vertical installation. Refer to Fig. 10 for a sample downflow installation.
To avoid equipment damage, do not use these units as a source of heating or cooling during the construction process. The mechanical components and filters used in these units quickly become clogged with construction dirt and debris which may cause system damage.
Electrical shock can cause personal injury or death. Before installing or servicing system, always turn off main power to system. There may be more than one disconnect switch. Turn off accessory heater power if applicable.
GENERAL
This Installation and Start-Up Instructions literature is for Aquazone™ water source heat pump systems.
Water source heat pumps (WSHPs) are single-package hori­zontally and vertically mounted units with electronic controls designed for year-round cooling and heating. Aquazone WSHPs are available in the following unit configurations:
• RHC standard efficiency with horizontal airflow and
right, left or back discharge
• RHR high efficiency with horizontal airflow and right,
left or back discharge
• RHS premium efficiency with horizontal airflow and
right, left or back discharge
• RVC standard efficiency with vertical airflow and top
discharge
• RVR high efficiency with vertical airflow and top
discharge
• RVS premium efficiency with vertical airflow and top
discharge
• RDS premium efficiency with vertical airflow and bot-
tom discharge (downflow)
IMPORTANT: The installation of water source heat pump units and all associated components, parts, and accessories which make up the installation shall be in accordance with the regulations of ALL authorities having jurisdiction and MUST conform to all applicable codes. It is the responsi­bility of the installing contractor to determine and comply with ALL applicable codes and regulations.
INSTALLATION
Step 1 — Check Jobsite —
maintenance instructions are provided with each unit. Before unit start-up, read all manuals and become familiar with the unit and its operation. Thoroughly check out the system before operation. Complete the inspections and instructions listed below to prepare a unit for installation. See Tables 1-3 for unit physical data.
HORIZONTAL UNITS (50RHC,RHR,RHS) — Horizontal units are designed for indoor installation only. Be sure to allow
Installation, operation and
Step 2 — Check Unit — Upon receipt of shipment at
the jobsite, carefully check the shipment against the bill of lading. Make sure all units have been received. Inspect the car­ton or crating of each unit, and inspect each unit for damage. Ensure the shipping company makes proper notation of any shortages or damage on all copies of the freight bill. Concealed damage not discovered during unloading must be reported to the shipping company within 15 days of receipt of shipment.
1. Verify unit is correct model for entering water tempera­ture of job.
2. Be sure that the location chosen for unit installation pro­vides ambient temperatures maintained above freezing. Well water applications are especially susceptible to freezing.
3. Be sure the installation location is isolated from sleeping areas, private offices and other acoustically sensitive spaces.
NOTE: A sound control accessory package may be used to help eliminate sound in sensitive spaces.
4. Check local codes to be sure a secondary drain pan is not required under the unit.
5. Be sure unit is mounted at a height sufficient to provide an adequate slope of the condensate lines. If an appropri­ate slope cannot be achieved, a field-supplied condensate pump may be required.
6. Provide sufficient space for duct connection.
7. Provide adequate clearance for filter replacement and drain pan cleaning. Do not allow piping, conduit, etc. to block filter access.
8. Provide sufficient access to allow maintenance and servicing of the fan and fan motor, compressor and coils. Removal of the entire unit from the closet should not be necessary.
9. Provide an unobstructed path to the unit within the closet or mechanical room. Space should be sufficient to allow removal of unit if necessary.
10. Provide ready access to water valves and fittings, and screwdriver access to unit side panels, discharge collar, and all electrical connections.
11. Where access to side panels is limited, pre-removal of the control box side mounting screws may be necessary for future servicing.
2
STORAGE — If the equipment is not needed immediately at the jobsite, it should be left in its shipping carton and stored in a clean, dry area of the building or in a warehouse. Units must be stored in an upright position at all times. If carton stacking is necessary, stack units a maximum of 3 high. Do not remove any equipment from its shipping package until it is needed for installation.
PROTECTION — Once the units are properly positioned on the jobsite, cover them with either a shipping carton, vinyl film, or an equivalent protective covering. Cap open ends of pipes stored on the jobsite. This precaution is especially important in areas where painting, plastering, or spraying of fireproof mate­rial, etc. is not yet complete. Foreign material that accumulates within the units can prevent proper start-up and necessitate costly clean-up operations.
Before installing any of the system components, be sure to examine each pipe, fitting, and valve, and remove any dirt or foreign material found in or on these components.
DO NOT store or install units in corrosive environments or in locations subject to temperature or humidity extremes (e.g., attics, garages, rooftops, etc.). Corrosive conditions and high temperature or humidity can significantly reduce performance, reliability, and service life. Always move units in an upright position. Tilting units on their sides may cause equipment damage.
INSPECT UNIT — To prepare the unit for installation, com­plete the procedures listed below:
1. Compare the electrical data on the unit nameplate with ordering and shipping information to verify that the correct unit has been shipped.
2. Verify that the unit is the correct model for the entering water temperature of the job.
3. Do not remove the packaging until the unit is ready for installation.
4. Verify that the refrigerant tubing is free of kinks or dents, and that it does not touch other unit components.
5. Inspect all electrical connections. Be sure connections are clean and tight at the terminals.
6. Loosen compressor bolts until the compressor rides freely on springs. Remove shipping restraints.
7. Remove the four
1
/4 in. shipping bolts from compressor support plate (two bolts on each side) to maximize vibra­tion and sound alternation.
Failure to remove shipping brackets from spring-mounted compressors will cause excessive noise and could cause component failure due to added vibration.
8. Remove any blower support cardboard from inlet of the blower.
9. Locate and verify any accessory kit located in compressor section.
10. Remove any access panel screws that may be difficult to remove once unit is installed.
3
Table 1 — Physical Data — Aquazone™ 50RHC,RVC006-060 Units
UNIT 50RHC,RVC 006* 009 012 018 024 030 COMPRESSOR (1 each) Rotary FACTORY REFRIGERANT CHARGE R-22
VERTICAL (oz) FACTORY REFRIGERANT CHARGE R-22
HORIZONTAL (oz) PSC FAN MOTOR AND BLOWER
Fan Motor Type/Speeds PSC/3 PSC/3 PSC/3 PSC/3 PSC/3 PSC/3 Fan Motor Std/High Static (Hp) Blower Wheel Size (D x W) (in.) Std/High Static 5 x 5/— 5 x 5/— 6 x 5/— 8 x 7/8 x 7 9 x 7/9 x 7 9 x 7/10 x 8
WATER CONNECTION SIZE (FPT) VERTICAL
Air Coil
Dimensions (H x W) (in.) 10 x 15 10 x 15 20 x 17.25 20 x 17.25 20 x 17.25 Total Face Area (ft2) 1.04 1.04 2.4 2.4 2.4
Tube Size (in.) Fin Spacing (FPI) —1212121212 Number of Rows —23233 Filter Standard — 1-in. Throwaway 10 x 18 10 x 18 1 — 20 x 20 1 — 20 x 20 1 — 20 x 20 Weight (lb)
Operating 105 114 181 189 197 Packaged 115 124 186 194 202
HORIZONTAL
Air Coil
Dimensions (H x W) (in.) 10 x 15 10 x 15 10 x 15 16 x 22 16 x 22 16 x 22 Total Face Area (ft2) 1.04 1.04 1.04 2.44 2.44 2.44
Tube Size (in.) Fin Spacing (FPI) 12 12 12 12 12 12 Number of Rows 223233 Filter Standard — 1-in. Throwaway 10 x 18 10 x 18 10 x 18 1 — 16 x 25 1 — 16 x 25 1 — 16 x 25 Weight (lb)
Operating 103 105 114 181 189 197 Packaged 113 115 124 186 194 202
—1414263837
14 14 14 25 38 37
1
/25/—
1
3
/
2
/
8
1
/10/—
1
3
3
1
/10/—
/
2
/
8
/
8
1
/
2
3
/
8
3
/
8
1
/8/1/
1
3
3
/
2
/
8
/
8
6
Reciprocating
1
/4/3/
4
3
/
4
3
/
8
3
/
8
3
/4/3/
3
3
3
4
/
4
/
8
/
8
UNIT 50RHC,RVC 036 041† 042 048 060 COMPRESSOR (1 each) Reciprocating Scroll FACTORY REFRIGERANT CHARGE R-22
VERTICAL (oz) FACTORY REFRIGERANT CHARGE R-22
HORIZONTAL (oz) PSC FAN MOTOR AND BLOWER
Fan Motor Type/Speeds PSC/3 PSC/3 PSC/3 PSC/3 PSC/3 Fan Motor Std/High Static (Hp)
Blower Wheel Size (D x W) (in.) Std/High Static 9 x 8/10 x 8 9 x 8/— 9 x 8/10 x 8 10 x 10/12 x 10 11 x 10/11 x 10 WATER CONNECTION SIZE (FPT) VERTICAL
Air Coil
Dimensions (H x W) (in.) 24 x 21.25 1 — 20 x 17.25 24 x 21.25 24 x 28.25 20 x 28.25 Total Face Area (ft2) 3.62 2.4 3.62 4.71 4.71
Tube Size (in.) Fin Spacing (FPI) 14 11 12 12 12 Number of Rows 2433 3
Filter Standard — 1-in. Throwaway 1 — 24 x 24 1 — 20 x 20 1 — 24 x 24 Weight (lb)
Operating 203 207 218 263 278 Packaged 209 212 224 270 285
HORIZONTAL
Air Coil
Dimensions (H x W) (in.) 20 x 25 20 x 25 20 x 35 20 x 35 Total Face Area (ft
Tube Size (in.) Fin Spacing (FPI) 14 12 12 12 Number of Rows 2—3 3 3
2
) 3.47 3.47 4.86 4.86
Filter Standard — 1-in. Throwaway Weight (lb)
Operating 203 218 263 278 Packaged 209 224 270 285
LEGEND
FPI Fins per Inch PSC — Permanent Split Capacitor
*Size 006 available in 50RHC unit only.
†Size 041 available in 50RVC unit only.
42 50 51 66 74
41 50 51 66 74
1
/2/3/
4
3
/
4
3
/
8
3
/
8
1 — 20 x 28 2 — 20 x 14
3
/4/—
3
/
4
3
/
8
NOTES:
1. All units have grommet compressor mountings, and electrical knockouts.
2. All sizes available as high-static units.
3
/4/3/
4
3
/
4
3
/
8
3
/
8
1 — 20 x 28 2 — 20 x 14
3
/4/1 1/1
11
3
/
8
1 — 14 x 24 1 — 18 x 24
3
/
8
1 — 20 x 24 1 — 20 x 14
3
/
8
1 — 14 x 24 1 — 18 x 24
3
/
8
1 — 20 x 24 1 — 20 x 14
1
/2 and 3/4-in.
4
Table 2 — Physical Data — Aquazone™ 50RHR,RVR006-060 Units
UNIT 50RHR,RVR 006* 009 012 015 019 024 030 036 042 048 060 COMPRESSOR (1 each) Rotary Reciprocating Scroll FACTORY CHARGE R-22 (oz) 12 15 15 30 30 30 41 44 46 54 80 PSC FAN MOTOR AND BLOWER
Fan Motor Type/Speeds PSC/3 PSC/3 PSC/3 PSC/3 PSC/3 PSC/3 PSC/3 PSC/3 PSC/3 PSC/3 PSC/3 Fan Motor (Hp) Blower Wheel Size (D x W) (in.) 5 x 5 5 x 5 6 x 5 9 x 7 9 x 7 9 x 7 9 x 7 10 x 10 10 x 10 10 x 10 11 x 10
1
WATER CONNECTION SIZE (FPT) VERTICAL
Air Coil
Dimensions (H x W) (in.) 10 x 16 16 x 16 20 x 20 28 x 20 28 x 25 Total Face Area (ft2) 1.1 1.8 2.8 3.9 4.9 Tube Size (in.) Fin Spacing (FPI) 1212121210 Number of Rows 33334 Filter Standard — 1-in. Throwaway 10 x 20 16 x 20 20 x 24 28 x 24 28 x 30 Weight (lb)
Operating 112 121 147 169 193 219 229 257 267 323 Packaged 122 131 157 179 203 231 241 269 279 338
HORIZONTAL
Air Coil
Dimensions (H x W) (in.) 10 x 16 16 x 16 18 x 22 18 x 31 20 x 35 Total Face Area (ft2) 1.1 1.8 2.8 3.9 4.9 Tube Size (in.) Fin Spacing (FPI) 12 12 12 12 10 Number of Rows 223 3 3 3 4
Filter Standard — 1-in. Throwaway 1 — 10 x 20 1 — 16 x 20 1 — 18 x 24 2 — 18 x 18 Weight (lb)
Operating 110 112 121 147 169 193 219 229 257 267 323 Packaged 120 122 131 157 179 203 231 241 269 279 338
LEGEND
FPI Fins per Inch PSC — Permanent Split Capacitor
*Size 006 available in 50RHR unit only.
1
/
25
1
1
/
2
3
1
/
/
10
1
/
2
3
/
8
/
8
1
10
3
/
2
1
/
6
3
/
4
3
3
NOTES:
1. All units have spring compressor mountings, TXV (thermostatic expansion valve) expansion devices, and 1/2 and 3/4-in. electrical knockouts.
2. Size 048 available as high-static unit.
1
/
5
3
/
4
/
8
/
8
1
/
3
3
/
4
3
/
2
3
/
4
3
/
8
3
/
8
3
/
4
/
4
3
/
/
4
4
11 1
3
/
8
3
/
8
1 — 12 x 20 1 — 25 x 20
1
3
/
8
3
/
8
Table 3 — Physical Data — Aquazone 50RHS,RVS,RDS015-070 Units
UNIT 50RHS,RVS,RDS 015 018 024 030 036 042 048 060 070 COMPRESSOR (1 each) Rotary Scroll FACTORY CHARGE R-22 (oz) 44 44 48 48 60 74 74 102 104 PSC FAN MOTOR AND BLOWER
Fan Motor Type/Speeds PSC/3 PSC/3 PSC/3 PSC/3 PSC/3 PSC/3 PSC/3 PSC/3 PSC/3 Fan Motor (Hp) Blower Wheel Size (D x W) (in.) 9 x 7 9 x 7 9 x 7 9 x 7 9 x 7 10 x 10 10 x 10 11 x 10 11 x 10
WATER CONNECTION SIZE (FPT) (in.) HWG CONNECTION SIZE (FPT) (in.) VERTICAL/DOWNFLOW
Air Coil
Dimensions (H x W) (in.) 20 x 20 24 x 20 28 x 20 28 x 25 32 x 25 36 x 25 Total Face Area (ft
Tube Size (in.) Fin Spacing (FPI) 12 12 12 10 10 10 Number of Rows 3 33444
2
) 2.8 3.3 3.9 4.9 5.6 6.3
1
/
6
3
/
4
1
/
2
Filter Standard — 1-in. Throwaway 1 — 20 x 24 1 — 24 x 24
Weight (lb)
Operating 174 184 250 252 266 323 327 416 443 Packaged 184 194 260 262 276 333 337 426 453
HORIZONTAL
Air Coil
Dimensions (H x W) (in.) 18 x 22 18 x 27 18 x 31 20 x 35 20 x 40 20 x 45 Total Face Area (ft
Tube Size (in.) Fin Spacing (FPI) 12 12 12 10 10 10 Number of Rows 3 33444
2
) 2.8 3.4 3.9 4.9 5.6 6.3
Filter Standard — 1-in. Throwaway 1 — 18 x 24 2 — 18 x 18
Weight (lb)
Operating 179 189 250 252 266 323 327 416 443 Packaged 189 199 260 262 276 333 337 426 453
LEGEND NOTES:
FPI Fins per Inch HWG — Hot Water Generator PSC — Permanent Split Capacitor
1
/
6
3
/
4
1
/
2
3
/
8
3
/
8
1
/
5
3
/
4
1
/
2
1
/
3
3
/
4
1
/
2
3
/
8
3
/
8
1. All units have spring compressor mountings, TXV (thermostatic
2. Size 030 and 036 available as high-static units.
1
/
2
3
/
4
1
/
2
3
/
8
2 — 14 x
24
3
/
8
2 — 18 x 182 — 12 x 201 — 20 x
expansion valve) expansion devices, and 1/2 and 3/4-in. electrical knockouts.
1
/
2
3
/
4
3
/
4
1111
1
/
2
2 — 14 x 30
1
/
2
3
/
8
3
/
8
25
1
/
2
3
/
8
2 — 10 x
30
1 — 12 x
30
3
/
8
1 — 18 x
20
1 — 24 x
20
1
1
/
2
3
/
8
3 — 12 x
30
3
/
8
2 — 24 x
20
5
50RHC
UNITS
006-012
018-030
036-042
048
060
NOTES:
1. Condensate is 3/4-in. FPT copper.
2. Horizontal unit shipped with filter bracket only. This bracket should be removed for return duct connection.
3. Hanger kit is factory installed.
OVERALL CABINET
A
WidthBDepthCHeight
in. 19.1 34.1 11.0 9.6 0.8 1.8 0.8 8.1 5.1 2.1 0.8 8.9 6.7 5.2 1.3 16.1 9.8 1.1 0.6 cm 48.5 86.6 27.9 24.4 2.0 4.4 2.0 20.6 13.0 5.4 1.9 22.7 17.0 13.3 3.3 41.0 25.0 2.7 1.5
in. 20.1 43.1 17.1 15.3 2.4 1.9 2.1 12.1 9.1 6.1 2.6 13.3 9.9 4.1 1.3 23.0 15.0 1.1 1.0 cm 51.1 109.5 43.4 38.9 6.1 4.9 5.3 30.8 23.2 15.6 6.6 33.8 25.1 10.5 3.3 58.4 38.1 2.8 2.5
in. 20.1 47.1 21.1 18.8 2.2 4.7 1.2 16.1 13.1 10.1 2.5 16.1 11.0 3.0 2.5 25.9 19.0 1.1 1.0 cm 51.1 119.6 53.6 47.6 5.5 11.9 3.0 41.0 33.3 25.7 6.3 40.9 27.9 7.7 6.4 65.8 48.3 2.8 2.5
in. 24.1 54.1 21.1 19.4 5.9 4.3 2.3 16.1 13.1 10.1 3.7 16.1 13.7 4.1 1.3 35.9 19.0 1.1 1.0 cm 61.2 137.4 53.6 49.2 14.9 11.0 5.8 41.0 33.3 25.7 9.5 41.0 34.8 10.3 3.2 91.2 48.3 2.8 2.5
in. 24.1 54.1 21.1 19.4 5.9 4.3 2.3 16.1 13.1 10.1 1.7 18.1 13.7 4.1 1.3 35.9 19.0 1.1 1.0 cm 61.2 137.4 53.6 49.2 14.9 11.0 5.8 41.0 33.3 25.7 4.4 46.0 34.8 10.3 3.2 91.2 48.3 2.8 2.5
WATER CONNECTIONS ELECTRICAL KNOCKOUTS (in.)
1 — In 2 — Out
D E F G Therm Ext Pump
H
1
/2 conduit
ASP — Alternate Service Panel BSP — Blower Service Panel CAP — Control Access Panel CSP — Compressor Service Panel
J
1
/2 conduit
LEGEND
K
3
/4 conduit
Power
Supply
DISCHARGE CONNECTION
Duct Flange Installed (±0.10 in.)
LMSupply
Height
N
Supply
Depth
OPQReturn
RETURN CONNECTION Using Air Coil Opening
R
Return
Depth
Height
ST
AIRFLOW CONFIGURATION
Code Return Discharge
S Left Right E Left Back Z Right Left
B Right Back
Fig. 1 — 50RHC Dimensional Data
a50-8155
6
WATER
OVER ALL
50RHR
UNITS
in. 22.4 43.1 11.3 2.4 5.4 0.6
006-012
cm 56.8 109.5 28.7 6.1 13.7 1.5 8.9 14.0 20.8 14.7 10.2 14.7 20.3 14.7 3.8 43.4 23.6 5.6 2.5
in. 22.4 43.1 17.3 2.4 4.9 0.6
015-024
cm 56.8 109.5 43.9 6.1 12.4 1.5 8.9 19.1 25.9 12.7 14.2 26.4 23.6 12.7 3.8 43.4 38.9 5.6 2.5
in. 22.4 53.2 19.3 2.4 5.4 0.6
030
cm 56.8 135.1 49.0 6.1 13.7 1.5 14.5 24.6 31.0 12.7 17.3 26.4 23.6 12.7 5.3 58.7 43.9 5.6 2.5
in. 22.4 53.2 19.3 2.4 5.4 0.6
036
cm 56.8 135.1 49.0 6.1 13.7 1.5 14.5 24.6 31.0 7.4 9.7 34.3 33.3 7.4 4.8 58.7 43.9 5.6 2.5
in. 22.4 62.2 19.3 2.4 5.4 0.6
042-048
cm 56.8 158.0 49.0 6.1 13.7 1.5 14.5 24.6 31.0 7.4 9.7 34.3 33.3 7.4 4.8 81.5 43.9 5.6 2.5
in. 25.4 71.2 21.3 2.4 5.4 0.6
060
cm 64.5 180.8 54.1 6.1 13.7 1.5 20.6 29.7 36.1 14.7 12.7 34.5 33.8 14.7 7.4 91.7 49.0 5.6 2.5
NOTES:
1. Condensate is 3/4-in. FPT copper.
2. Horizontal unit shipped with filter bracket only. This bracket should be removed for return duct connection.
3. Hanger kit is factory installed. Isolation grommets are provided.
4. Right and left orientation is determined by looking at water connection side.
CABINET
A
WidthBDepthCHeightDInEOut
3op?œŸ•‘ “ ’
CONNECTIONS
12 3
²±¢p³µ¶·¸¹º»¼½¾¿ÀÁÂ?‘’“”•…†‡denµ´ÇÆÅÄ´
F
Cond-
ensate
Loop
Wate r
ELECTRICAL KNOCKOUTS (in.)
G
1
/2 conduit
FPT
Therm
(in.)
1
3
3
3
3.5 5.5 8.2 5.8 4.0 5.8 8.0 5.8 1.5 17.1 9.3 2.2 1.0
/
2
3.5 7.5 10.2 5.0 5.6 10.4 9.3 5.0 1.5 17.1 15.3 2.2 1.0
/
4
5.7 9.7 12.2 5.0 6.8 10.4 9.3 5.0 2.1 23.1 17.3 2.2 1.0
/
4
5.7 9.7 12.2 2.9 3.8 13.5 13.1 2.9 1.9 23.1 17.3 2.2 1.0
/
4
5.7 9.7 12.2 2.9 3.8 13.5 13.1 2.9 1.9 32.1 17.3 2.2 1.0
1
8.1 11.7 14.2 5.8 5.0 13.6 13.3 5.8 2.9 36.1 19.3 2.2 1.0
1
H
1
/2 conduit
Ext
Pump
3
LEGEND
Water Connection
3‘ Service
Access
ASP
BSP
E Configuration - Left Return Back Discharge
Right View
Fron t
LEFT RETURN RIGHT RETURN
Fron t
Right
Discharge
CSP
M
N
Blower
L
Outlet
O
ASP
S Configuration - Left Return Right Discharge -
A
Air Coil Opening
Left Return
Back
Discharge
C
Air Coil Side
3
ASP — Alternate Service Panel BSP — Blower Service Panel CAP — Control Access Panel CSP — Compressor Service Panel
Power Supply
Knockout
3/4
1/2
Knockout
3.25
Low Voltage
1/2
Knockout
F
Condensate
3/4
FPT
Unit Hanger Detail
Model X Y Z
Y
M
Blower
Outlet
006-024 43.1 24.375 20.375
Front
030-036 53.1 24.375 20.375 042-048 62.1 24.375 20.375 060 71.1 27.375 23.375
J
BSP
L
K
1.6 [40.6mm]
I
CAP
H
G
A
Front-View
X
SERVICE
ACCESS
I
/4 conduit
Powe r
Supply
2 1
K
BSP
3
DISCHARGE CONNECTION
Duct Flange Installed (±0.10 in.)
JKLSupply
Height
M
Supply
Depth
Right Return
3.25
F
Condensate
3/4
FTP
Z
L
3
Back
Discharge
C
Air Coil Side
B Configuration - Right Return Back Discharge
Air Coil Opening
E
D
M
Blower
Outlet
M
Z Configuration - Right Return Left Discharge -
RETURN CONNECTION
Using Return Air Opening
NOPReturn
ASP
M
Blower
Outlet
A
CSP
Depth
Water Connection
Discharge
O
L
N
Fron t
Left
CSP
BSP
Q Return Height
Left
View
Fron t
Service
2
Access
RS
Left
View
S
Q
C
PR
S Configuration - Left Return Right Discharge -
B
Air Coil Opening
AIRFLOW CONFIGURATION
Code Return Discharge
S Left Right E Left Back Z Right Left B Right Back
Fig. 2 — 50RHR Dimensional Data
Air Coil
CSP
1.1
C
Fron t
Fron t
Air Coil
ASP
Z Configuration - Right Return Left Discharge -
Air Coil Opening
P
B
S
R
Q
Right View
a50-8156
7
50RHS
UNITS
015-018
024-030
036
042-048
060
070
NOTES:
1. Condensate is 3/4-in. FPT copper.
2. Horizontal unit shipped with filter bracket only. This bracket should be removed for return duct connection.
3. Hanger kit is factory installed. Isolation grommets are provided.
4. Right and left orientation is determined by looking at water connection side.
OVERALL CABINET
A
WidthBDepthCHeightDInEOut
in. 22.4 53.2 19.3 2.4 5.4 0.6 cm 56.8 135.1 49.0 6.1 13.7 1.5 14.5 24.6 31.0 12.7 17.3 26.4 23.6 12.7 5.3 58.7 43.9 5.6 2.5
in. 22.4 62.2 19.3 2.4 5.4 0.6 cm 56.8 158.0 49.0 6.1 13.7 1.5 14.5 24.6 31.0 12.7 17.3 26.4 23.6 12.7 5.3 71.4 43.9 5.6 2.5
in. 22.4 62.2 19.3 2.4 5.4 0.6 cm 56.8 158.0 49.0 6.1 13.7 1.5 14.5 24.6 31.0 12.7 17.3 26.4 23.6 12.7 5.3 81.5 43.9 5.6 2.5
in. 25.4 71.2 21.3 2.4 5.4 0.6 cm 64.5 180.8 54.1 6.1 13.7 1.5 20.6 29.7 36.1 14.7 12.7 34.5 33.8 14.7 7.4 91.7 49.0 5.6 2.5
in. 25.4 76.2 21.3 2.4 5.4 0.6 cm 64.5 193.5 54.1 6.1 13.7 1.5 20.6 29.7 36.1 14.7 12.7 34.5 33.8 14.7 7.4 104.4 49.0 5.6 2.5
in. 25.4 81.2 21.3 2.4 5.4 0.6 cm 64.5 206.2 54.1 6.1 13.7 1.5 20.6 29.7 36.1 14.7 12.7 34.5 33.8 14.7 7.4 117.1 49.0 5.6 2.5
WATER CONNECTIONS ELECTRICAL KNOCKOUTS (in.)
12 3
F
Cond-
ensate
Loop
Water
FPT (in.)
3
/
3
/
3
/
1
11/
11/
G
1
/2 conduit
HWG
FPT (in.)
Therm Ext Pump
5.7 9.7 12.2 5.0 6.8 10.4 9.3 5.0 2.1 23.1 17.3 2.2 1.0
1
/
4
2
5.7 9.7 12.2 5.0 6.8 10.4 9.3 5.0 2.1 28.1 17.3 2.2 1.0
1
/
4
2
5.7 9.7 12.2 5.0 6.8 10.4 9.3 5.0 2.1 32.1 17.3 2.2 1.0
1
/
4
2
8.1 11.7 14.2 5.8 5.0 13.6 13.3 5.8 2.9 36.1 19.3 2.2 1.0
1
/
2
8.1 11.7 14.2 5.8 5.0 13.6 13.3 5.8 2.9 41.1 19.3 2.2 1.0
2
8.1 11.7 14.2 5.8 5.0 13.6 13.3 5.8 2.9 46.1 19.3 2.2 1.0
2
H
1
/2 conduit
LEGEND
ASP — Alternate Service Panel BSP — Blower Service Panel CAP — Control Access Panel CSP — Compressor Service Panel
I
3
/4 conduit
Power
Supply
DISCHARGE CONNECTION
Duct Flange Installed (±0.10 in.)
JKLSupply
Height
M
Supply
Depth
RETURN CONNECTION Using Air Coil Opening
NOPReturn
Depth
Q Return Height
RS
AIRFLOW CONFIGURATION
Code Return Discharge
S Left Right E Left Back Z Right Left B Right Back
Fig. 3 — 50RHS Dimensional Data
a50-8157
8
UNIT HANGER ISOLATION DETAIL
Fig. 4 — Typical Installation — 50RHC,RHR,RHS Units
9
50RVC UNITS
009-012
018-030
036 & 042
041
048-060
NOTES:
1. Condensate is 3/4-in. (19.1 mm) FPT.
2. Filter bracket extending from unit 2.5-in. (6.4 cm). This bracket should be removed when connecting return duct.
3. Discharge flange field installed.
OVERALL CABINET
A
WidthBDepthCHeight
in. 19.1 19.1 22.0 1.4 2.8 9.4 2.8 6.1 2.3 1/2 2.9 5.9 8.9 8.9 5.1 9.0 9.0 5.5 2.1 16.2 9.9 0.7 cm 48.5 48.5 55.9 3.6 7.1 24.0 7.1 15.6 5.9 1.3 7.3 14.9 22.5 22.7 12.9 22.9 22.9 14.0 5.3 41.1 25.1 1.9
in. 21.5 21.5 39.0 1.8 3.8 15.2 3.6 8.1 2.33/ cm 54.6 54.6 99.1 4.5 9.7 38.6 9.1 20.6 5.8 1.9 10.5 18.1 25.7 16.1 9.5 35.6 35.6 13.6 5.8 46.5 51.3 1.9
in. 21.5 26.0 44.0 2.0 3.7 16.2 2.6 10.4 2.33/ cm 54.6 66.0 111.8 5.1 9.4 41.1 6.6 28.4 5.8 1.9 10.5 18.1 25.7 16.1 9.5 35.6 35.6 13.1 5.8 57.9 61.4 1.9
in. 21.5 21.5 39.0 1.7 3.6 16.4 2.6 8.1 2.33/ cm 54.6 54.6 99.1 4.4 9.1 41.7 6.6 20.6 5.8 1.9 10.5 18.1 25.7 16.1 9.5 35.6 35.6 13.6 5.8 46.5 51.3 1.9
in. 24.0 32.5 46.0 1.8 5.9 16.7 2.3 10.1 2.3 1 4.1 7.1 10.1 6.9 7.3 16.0 18.0 5.1 2.3 29.3 24.2 0.7 cm 6.10 82.6 116.8 4.5 14.9 42.4 5.8 25.7 5.8 2.5 10.5 18.1 25.7 17.4 18.4 40.6 45.7 13.1 5.8 74.4 61.4 1.9
WATER CONNECTIONS ELECTRICAL KNOCKOUTS (in.)
12 3
DE FG H I
In Out Condensate
Water
FPT
Size
ASP — Alternate Service Panel BSP — Blower Service Panel CAP — Control Access Panel CSP — Compressor Service Panel
J
4
4
4
LEGEND
1
/2 conduit
1
/2 conduit
Therm
4.1 7.1 10.1 6.4 3.8 14.0 14.0 5.3 2.3 18.3 20.2 0.7
4.1 7.1 10.1 6.4 3.8 14.0 14.0 5.1 2.3 22.8 24.2 0.7
4.1 7.1 10.1 6.4 3.8 14.0 14.0 5.3 2.3 18.3 20.2 0.7
Pump
K
Ext.
L
3
/4 conduit
Power
Supply
DISCHARGE CONNECTION
Duct Flange Installed (±0.10 in.)
MNOSupply
Width
P
Supply
Depth
RETURN CONNECTION Using Air Coil Opening
QRSReturn
Depth
T Return Height
U
AIRFLOW CONFIGURATION
Code Return Discharge
L Left Top R Right Top
a50-8158
Fig. 5 — 50RVC Dimensional Data
10
50RVR UNITS
009-012
015-024
030
036
042-048
060
NOTES:
1. Condensate is 3/4-in. FPT and is switchable from side to front.
2. Vertical unit shipped with filter bracket only extending from unit 2.5 inches. This bracket should be removed when connecting return duct.
3. Discharge flange field installed.
4. Right and left orientation is determined by looking at water connection side.
OVERALL CABINET
A
WidthBDepthCHeightDInEOut
in. 22.4 21.6 22.6 2.6 5.4 7.8 cm 56.8 54.9 57.4 6.6 13.7 19.8 8.9 14.0 20.8 26.9 17.3 14.7 20.3 15.2 5.6 43.4 23.6 2.5
in. 22.4 21.6 34.6 2.4 4.8 8.5 cm 56.8 54.9 87.9 6.1 12.2 21.6 8.9 19.1 25.9 18.3 9.7 35.6 35.6 10.9 5.6 43.4 38.9 2.5
in. 22.4 25.6 40.6 2.4 5.4 9.7 cm 56.8 65.1 103.1 6.1 13.7 24.6 14.5 24.6 31.0 18.3 14.7 35.6 35.6 10.9 5.6 53.6 48.8 2.5
in. 22.4 25.6 40.6 2.4 5.4 9.7 cm 56.8 65.1 103.1 6.1 13.7 24.6 14.5 24.6 31.0 18.3 14.7 35.6 35.6 10.9 5.6 53.6 48.8 2.5
in. 22.4 25.6 48.6 2.4 5.4 9.7 cm 56.8 65.1 123.4 6.1 13.7 24.6 14.5 24.6 31.0 18.3 14.7 35.6 35.6 10.9 5.6 53.6 69.1 2.5
in. 25.4 30.6 50.6 2.4 5.4 10.7 cm 64.5 77.8 128.5 6.1 13.7 27.2 20.6 29.7 36.1 15.7 16.0 45.7 45.7 13.0 5.6 66.3 69.1 2.5
WATER CONNECTIONS ELECTRICAL KNOCKOUTS (in.)
12 3
Loop
Wate r
F
FPT
Cond-
(in.)
ensate
ASP — Alternate Service Panel BSP — Blower Service Panel CAP — Control Access Panel CSP — Compressor Service Panel
G
1
/2 conduit
Therm Ext Pump
3.5 5.5 8.2 10.6 6.8 5.8 8.0 6.0 2.2 17.1 9.3 1.0
1
/
2
3.5 7.5 10.2 7.2 3.8 14.0 14.0 4.3 2.2 17.1 15.3 1.0
3
/
4
5.7 9.7 12.2 7.2 5.8 14.0 14.0 4.3 2.2 21.1 19.2 1.0
3
/
4
5.7 9.7 12.2 7.2 5.8 14.0 14.0 4.3 2.2 21.1 19.2 1.0
3
/
4
5.7 9.7 12.2 7.2 5.8 14.0 14.0 4.3 2.2 21.1 27.2 1.0
1
8.1 11.7 14.2 6.2 6.3 18.0 18.0 5.1 2.2 26.1 27.2 1.0
1
LEGEND
H
1
/2 conduit
3
/4 conduit
Power
Supply
I
DISCHARGE CONNECTION
Duct Flange Installed (±0.10 in.)
JKLSupply
Standard Filter Bracket
Height
Field Installed Discharge Flange (Shipped loose in blower section)
M
Supply
Depth
RETURN CONNECTION Using Air Coil Opening
NOPReturn
Depth
Water Connection
Access Panels
Q Return Height
R
RIGHT RETURN
M
Fron t
L
N
Air Coil Side
R Configuration - Top View-Right Return
P
K
O
R
Q
C
ASP
Front
R Configuration - Right Return Right View
- Air Coil Opening
Back
LEFT RETURN
K
L Configuration - Top View-Left Return
M
Air Coil Side
O
R
Air Coil
Q
C
Back
L Configuration - Left Return Left View
- Air Coil Opening
P
CSP
Air Coil
B
BSP
L
Front
A
CSP
CAP
ASP
ASP
3Service
Access
Left Return
(right
Opposite)
J
Fron t
Water Connections
1.000
E
D
Condensate 3/4
FPT
F
Air Coil
Fron t
Power Supply
3/4 HV Knockout
Power for
Condensate Pump
1/2“ Knockout
Low Voltage
1/2“ LV Knockout
3Service
Access
CSP
CAP
H
G
Front View
Isometric
View
I
3
2 1
AIRFLOW CONFIGURATION
Code Return Discharge
L Left Top R Right Top
a50-8159
Fig. 6 — 50RVR Dimensional Data
11
50RVS UNITS
015-018
024-030
036
042-048
060
070
NOTES:
1. Condensate is 3/4-in. FPT and is switchable from side to front.
2. Vertical unit shipped with filter bracket only extending from unit 2.5 inches. This bracket should be removed when connecting return duct.
3. Discharge flange field installed.
4. Right and left orientation is determined by looking at water connection side.
OVERALL CABINET
A
WidthBDepthCHeightDInEOut
in. 22.4 25.6 40.6 2.4 5.4 9.7 cm 56.8 65.1 103.1 6.1 13.7 24.6 14.5 24.6 31.0 18.3 14.7 35.6 35.6 10.9 5.6 53.6 48.8 2.5
in. 22.4 25.6 44.6 2.4 5.4 9.7 cm 56.8 65.1 113.3 6.1 13.7 24.6 14.5 24.6 31.0 18.3 14.7 35.6 35.6 10.9 5.6 53.6 58.9 2.5
in. 22.4 25.6 48.6 2.4 5.4 9.7 cm 56.8 65.1 123.4 6.1 13.7 24.6 14.5 24.6 31.0 18.3 14.7 35.6 35.6 10.9 5.6 53.6 69.1 2.5
in. 25.4 30.6 50.6 2.4 5.4 10.7 cm 64.5 77.8 128.5 6.1 13.7 27.2 20.6 29.7 36.1 15.7 16.0 45.7 45.7 13.0 5.6 66.3 69.1 2.5
in. 25.4 30.6 54.6 2.4 5.4 10.7 cm 64.5 77.8 138.7 6.1 13.7 27.2 20.6 29.7 36.1 15.7 16.0 45.7 45.7 13.0 5.6 66.3 79.2 2.5
in. 25.4 30.6 58.6 2.4 5.4 10.7 cm 64.5 77.8 148.8 6.1 13.7 27.2 20.6 29.7 36.1 15.7 16.0 45.7 45.7 13.0 5.6 66.3 89.4 2.5
WATER CONNECTIONS ELECTRICAL KNOCKOUTS (in.)
12 3
F
Cond-
ensate
Loop Water
FPT (in.)
3
/
4
3
/
4
3
/
4
11/
11/
11/
HWG
FPT (in.)
G
1
/2 conduit
Therm Ext Pump
5.7 9.7 12.2 7.2 5.8 14.0 14.0 4.3 2.2 21.1 19.2 1.0
1
/
2
5.7 9.7 12.2 7.2 5.8 14.0 14.0 4.3 2.2 21.1 23.2 1.0
1
/
2
5.7 9.7 12.2 7.2 5.8 14.0 14.0 4.3 2.2 21.1 27.2 1.0
1
/
2
8.1 11.7 14.2 6.2 6.3 18.0 18.0 5.1 2.2 26.1 27.2 1.0
2
8.1 11.7 14.2 6.2 6.3 18.0 18.0 5.1 2.2 26.1 31.2 1.0
2
8.1 11.7 14.2 6.2 6.3 18.0 18.0 5.1 2.2 26.1 35.2 1.0
2
H
1
/2 conduit
I
3
/4 conduit
Power
Supply
DISCHARGE CONNECTION
Duct Flange Installed (±0.10 in.)
JKLSupply
Height
M
Supply
Depth
RETURN CONNECTION
Using Air Coil Opening
NOPReturn
Depth
Q Return Height
R
RIGHT RETURN
M
Fron t
L
N
Air Coil Side
R Configuration - Top View-Right Return
P
K
O
R
Air Coil
LEGEND
ASP — Alternate Service Panel BSP — Blower Service Panel CAP — Control Access Panel CSP — Compressor Service Panel
LEFT RETURN
B
K
L Configuration - Top View-Left Return
O
M
Air Coil Side
P
Front
J
R
L
A
Air Coil
Standard Filter Bracket
Air Coil
CSP
Fron t
3Service
Access
Field Installed Discharge Flange (Shipped loose in blower section)
BSP
CAP
Isometric
Water Connection
Access Panels
ASP
ASP
View
Water Connections
1.000
3Service
Access
Left Return
(right
Opposite)
Q
C
ASP
Front
R Configuration - Right Return Right View
- Air Coil Opening
AIRFLOW CONFIGURATION
Code Return Discharge
L Left Top R Right Top
Back
Q
C
CSP
Back
L Configuration - Left Return Left View
- Air Coil Opening
Fron t
Fig. 7 — 50RVS Dimensional Data
12
Power Supply
3/4 HV Knockout
Power for
Condensate Pump
1/2“ Knockout
Low Voltage
1/2“ LV Knockout
a50-8169
CSP
H
G
Front View
CAP
I
Condensate 3/4
FPT
3
2 1
F
E
D
50RDS
UNITS
015-018
024-030
036
042-048
060
070
HWG — Hot Water Generator
NOTES:
1. Condensate is
2. Vertical unit shipped with filter bracket only extending from unit 2.5 inch. This bracket should be removed when connecting return duct.
OVERALL CABINET
A
WidthBDepthCHeightDInEOut
in.
22.4 25.6 44.6 16.9 13.9 5.4 2.4 3.5
cm 56.8 65.1 113.3 42.9 35.3 13.7 6.1 8.9 34.5 24.6 18.3 15.4 20.8 26.4 23.5 27.9 5.6 53.6 51.3 51.8 in.
22.4 25.6 48.6 16.9 13.9 5.4 2.4 3.5
cm 56.8 65.1 123.4 42.9 35.3 13.7 6.1 8.9 34.5 24.6 18.3 15.4 20.8 26.4 23.5 27.9 5.6 53.6 61.5 51.8 in.
22.4 25.6 52.6 16.9 13.9 5.4 2.4 3.5
cm 56.8 65.1 133.6 42.9 35.3 13.7 6.1 8.9 34.5 24.6 18.3 15.4 20.8 26.4 23.5 27.9 5.6 53.6 71.6 51.8 in.
25.4 30.6 54.6 18.9 15.9 5.4 2.4 3.5
cm 64.5 77.8 138.7 48.0 40.4 13.7 6.1 8.9 33.3 24.6 18.3 18.3 22.1 34.4 33.7 26.7 5.6 66.3 71.6 56.9 in.
25.4 30.6 58.6 18.9 15.9 5.4 2.4 3.5
cm 64.5 77.8 148.8 48.0 40.4 13.7 6.1 8.9 33.3 24.6 18.3 18.3 22.1 34.4 33.7 26.7 5.6 66.3 81.8 56.9 in.
25.4 30.6 62.6 18.9 15.9 5.4 2.4 3.5
cm 64.5 77.8 159.0 48.0 40.4 13.7 6.1 8.9 33.3 24.6 18.3 18.3 22.1 34.4 33.7 26.7 5.6 66.3 91.9 56.9
LEGEND
3
/4-in. PVC FPT and is switchable from side to front.
WATER CONNECTIONS (in.) ELECTRICAL KNOCKOUTS (in.)
12 3 4 5
F
G
HWG
HWG
In
Out
H
Cond-
ensate
Loop
HWG
Water
FPT
FPT
(in.)
(in.)
3/4 1/2
3/4 1/2
3/4 1/2
11/2
11/2
11/2
J
1
/2 conduit
Therm
13.6 9.7 7.2 6.1 8.2 10.4 9.3 11.0 2.2 21.1 20.2 20.4
13.6 9.7 7.2 6.1 8.2 10.4 9.3 11.0 2.2 21.1 24.2 20.4
13.6 9.7 7.2 6.1 8.2 10.4 9.3 11.0 2.2 21.1 28.2 20.4
13.1 9.7 7.2 7.2 8.7 13.6 13.3 10.5 2.2 26.1 28.2 22.4
13.1 9.7 7.2 7.2 8.7 13.6 13.3 10.5 2.2 26.1 32.2 22.4
13.1 9.7 7.2 7.2 8.7 13.6 13.3 10.5 2.2 26.1 36.2 22.4
K
1
/2 conduit
Ext
Pump
L
3
/4 conduit
Power
Supply
DISCHARGE CONNECTION
Outlet Opening Only
MNOSupply
Width
Supply
Depth
P
RETURN CONNECTION
Using Return Air Opening
QRSReturn
Depth
T Return Height
U
a50­6743ef. eps
P
Blower
O
Opening
Front
Q
Air Coil Side
B
Right Return/Bottom Discharge
Floor Foot Print (Top View)
U
ASP
LEGEND
ASP — Alternate Service Panel BSP — Blower Service Panel CAP — Control Access Panel CSP — Compressor Service Panel
N
N
P
Blower
O
A
A
Opening
Front
CSP
ASP
3Service
Access Left Rtn
(right opposite)
Standard Filter Bracket
CAP
BSP
Condensate 3/4
FPT
ASP
M
Air Coil Side
3Service
Access
B
Air Coil
Left Return/Bottom Discharge
Floor Foot Print (Top View)
1.1
U
CSP
Power Supply
HV Knockout
3/4
1/2
Low Voltage
1/2
LV Knockout
Air Coil
Knockout
CSP
Isometric View
1.6
L
K
J
CAP
BSP
1.6
G
4
3
F
E
D
2 1
T
Front
S
Right Return­Air Coil Opening (Right Side View)
Front
Condensate
FPT
3/4
Right Return
T
C
Back
R
Back
R
S
Left Return -
Air Coil Opening
(Left Side View)
H
Condensate 3/4
FPT
5
Front-View
Left Return
5
Fig. 8 — 50RDS Dimensional Data
13
Supply Air
Building
Flexible Connection
Return
Air
Power
Thermostat Wiring
Compressor Access Panel
NOTE: Ball valve with integral pressure temperature plug recommended.
Loop
Water Out
Water In
Field-supplied stainless steel braid hose with integral “ J” swivel
Ball Valve with optional integral P/T plug (typical for supply and return piping)
Balancing Valve (field installed and calibrated accessory)
Low Pressure
Drop Water Control Valve (optional) (field-installed accessory)
Fig. 9 — Typical Vertical Installation —
50RVC,RVR,RVS Units
Flexible Connection
Return
Air
Power
Thermostat Wiring
Compressor Access Panel
NOTE: Ball valve with integral pressure temperature plug recommended.
Supply Air
Building Loop
Water Out
Field-supplied stainless steel braid hose
with integral “ J” swivel
Flexible Connection
Water In
Balancing Valve
(field-installed
and calibrated
accessory)
Low Pressure
Drop Water Control Valve (optional) (field-installed accessory)
Ball Valve with optional integral P/T plug (typical for supply and return piping)
conversion process is the same for right and left return configu­rations. See Fig. 11 and 12.
NOTE: It is not possible to convert return air between left or right return models in the field due to refrigerant piping changes.
Preparation
— The unit should be on the ground in a well lit area for conversion. Hung units should be taken down to ground level before converting.
Side to Back Discharge Conversion
1. Remove screws to free the top and discharge panels. See Fig. 11.
2. Remove the access panel and set aside.
3. Lift the discharge panel from side of unit and rotate it to back using care not to damage blower wiring.
4. Check blower wire routing and connections for undo tension or contact with sheet metal edges. Re-route if necessary.
5. Check refrigerant tubing for contact with other compo­nents. Adjust if necessary.
6. Reinstall top panel using screws set aside in Step 1.
NOTE: Location for some screws at bottom of discharge panel may have to be changed.
7. Manually spin fan wheel to check for obstructions. Adjust for any obstruction found.
8. Replace access panel.
Back to Side Discharge Conversion
— Follow instructions above for Side to Back Discharge Conversion, noting the panels would be reversed.
Water
Connection End
Remove Screws
Return Air
Fig. 10 — Typical Downflow Installation —
50RDS Units
Step 3 — Unit Location — The following guidelines
should be considered when choosing a location for a WSHP:
• Units are for indoor use only.
• Locate in areas where ambient temperatures are between 40 F and 100 F and relative humidity is no greater than 75%.
• Provide sufficient space for water, electrical and duct connections.
• Locate unit in an area that allows easy access and removal of filter and access panels.
• Allow enough space for service personnel to perform maintenance.
• Return air must be able to freely enter the space if unit needs to be installed in a confined area such as a closet.
NOTE: Correct placement of the horizontal unit can play an important part in minimizing sound problems. Since duct­work is normally applied to these units, the unit can be placed so that the principal sound emission is outside the oc­cupied space in sound-critical applications. A fire damper may be required by the local code if a fire wall is penetrated.
FIELD CONVERSION OF DISCHARGE AIR — The dis­charge air of the 50RHC,RHR,RHS horizontal units can be converted between side and back discharge in the field. The
Side Discharge
Water
Connection End
Return Air
Move to Side
Water
Connection End
Back Discharge
Replace Screws
Fig. 11 — Conversion Left Return, Side Discharge to Back Discharge
Rotate
Return Air
Drain
Discharge Air
14
Loading...
+ 30 hidden pages