Carrier 50QT User Manual

Carrier Corporation • Syracuse N Y 13221
Single-Package Heat Pumps
Chassis Only (Install ONLY after
50OT wall sleeve is in place)
CONTENTS
Page
SAFETY CONSIDERATIONS
INTRODUCTION .......................................................1
INSTALLATION.......................................................1-4
Step 1 — Check Equipment and Jobsite .. I
• UNPACK UNIT
• INSPECT EQUIPMENT
• INSPECT WALL SLEEVE
Step 2 — Install Chassis in Wall Sleeve.... 3
• SLIDE CHASSIS INTO SLEEVE
Step 3 — Install Thermostat and
Connect Thermostat Wiring....................................3
• TO MOUNT THERMOSTAT IN UNIT
• TO MOUNT THERMOSTAT REMOTELY
COLD CLIMATE ACCESSORY START-UP SERVICE
.................................................................
.................................................................
..................................
................................
4-14
SAFETY CONSIDERATIONS
Installation and servicing of air conditioning equipment can be hazardous due to system pressure and electrical components. Only trained and quali fied service personnel should install, repair or service air conditioning equipment.
servke <ar
dixsr ’Tvm ^ feoatsr
mwst 4cfm bdoxa ^
WARNii^C: The 5QQT is. uatt astd, thsr^ore, req«*res special casse m liasEtdSas^ to lo asad clastaags lo oast, Avcàé ìsspact visàì% or
other stapdmg «bjects whs® cissssim
INTRODUCTION
Install Model 50QT112, 115 and 118 heat pump chassis in 50QT wall sleeve. Part No. 50QT900060; and Model 50QT124 and 130 chassis in 50QT wall sleeve. Part No. 50QT900080. Wall sleeves are shipped separately with aecompanying installation instructions. All electrical power, ductwork and condensate drain hookups are made at time of wall sleeve installation.
Untrained personnel can perform basic mainte nance functions of cleaning indoor coil or replacing filter. All other operations should be performed by trained service personnel. When working on air conditioning equipment, observe precautions in the literature, tags and labels attached to the unit and
other safety precautions that may apply.
Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth for brazing operations. Have fire extinguisher available for all brazing operations.
>P Carrier Corporation 1984
Bart

aad so '

is iiìsiaJled, isso? cm
pr^^per
<md<m m piace.
INSTALLATION
Step 1 — Check Equipment and Jobsite
UNPACK UNIT — Move to final loeation. Lift eardboard carton off chassis taking special care not to damage unit.
Form 50QT-10SI
Table 1 — Electrical Data (&©^zt
MODEL
50QT
AB
112300 II
115300
AB
118300 AD
AF AD
124300 AF
AG AD
130300 AF
AG
♦Permissible limits of the voltage range at which units will
operate satisfactorily
fField wiring to be sized for NEC or local codes Use copper wire
only
^Maximum dual element fuse
♦♦Minimum voltage is 197 when outdoor ambient temperature
exceeds 105 F
NOTE: Dual values in this table (for example Electric Fleeter Amps 9 4/12 5) apply to 208- and 230-volt connections respectively
V/PH
208/230/1
208/230/1
208/230/1
208/230/1
208/230/1
OPER
VOLTAGE^
Max Min^*
254 187 37 6 8 1 5 1 0
254
254
254 187 59 13 0 2 0
254
187
187
187
COMPR
LRA
43 8 7
49
79
IFM OFM
RLA FLA
1 5
10 3
1 7
16 9 2 4
ELECTRIC
HEATER
AMPS
FLA
9 4/12 5
18.0/20.8
1 0
1 0
1 5
1 5
9 4/12 5
18 0/20 8
9 4/12 5 18 0/20 8 26 8/31 3
17 3/20 8 26 8/31 3 36 1/41.7
17 4/ 20 8
26 8/31 3 36 0/41 7
FLA — Full Load Amps
FIACR— Heating, Air Conditioning IFM — Indoor Fan Motor
Max Fuse or
.....
These units require 2 separate supply circuits Refer to BOTFI branch circuit charts for complete
electrical data
and Refrigeration
BRANCH CIRCUIT #1
(or Total Unit)t
HACR Ckt
Bkr Ampst
25/30 35/40
25/30 35/40
30/35 40/45 50/55
45/50 55/60
MCA
22 8/26 6
33.5/37.0 25 1/29 0
35.9/39.4 27 3/31 2
38 1/41 6 49 1/54 7
41 4/45 9
53.6/59.1
50/55 ^ 1 47.5/52J
BRANCH CIRCUIT #2
(When Used)t
Max Fuse or
HACR Ckt
Bkr Ampst
LRA — Locked Rotor Amps MCA— Minimum Circuit
Amps
OFM — Outdoor Fan Motor RLA — Rated Load Amps
MCA
1
♦INSPECT EQUIPMENT for damage prior to in
stallation. To remove plastic wrapper, grasp bottom and pull out until velcro strips separate. To remove metal cover plate, remove 6 screws. Eile claim with shipping company if shipment is damaged or
incomplete.
Leave chassis bolted to skid and replace metal cover plate, plastic wrapper, and carton until ready for installation into wall sleeve.
INSPECT WALL SLEEVE installation for damage. Condensate drain pan must be free of debris and installed in accordance with local build ing regulations. Electrical connector on left side of sleeve should be free of dirt, grease, paint, etc.
Connector must be properly wired before chassis
installation. Duct connection panel must be level and duct connections complete. Do not rest weight
of ductwork on duct connector panel. Inspect name
plate on sleeve to ensure wire and fuse sizing is
correct for model size to be installed.
At ^
-i
Fig. 1 — Chassis with Indoor Plastic Wrapper
©
Step 2 — Install Chassis in Wall Sleeve —
Remove sleeve filler panel and save screws. Install outdoor grille using these screws. Remove indoor plastic wrapper as described in Step 1. Do not handle cha.ssis with plastic wrapper in place.
SLIDE CHASSIS INTO SLEEVE — Chassis is
heavy. Portable lifting device must be used. Exercise caution to make sure forks do not damage chassis components (such as drain connections) while
lifting and installing. Guide chassis into sleeve on
indoor side by first placing chassis guide channels
onto sleeve guide channels at bottom of sleeve.
Slide chassis into sleeve until center partition peri
meter meets gasket provided around outer edge of
sleeve. Check electrical plugs for alignment as
chassis is slid into place.
Tighten chassis into place by driving 6 screws, provided in separate bag with chassis, into nuts provided on sleeve (see Fig. 3).
Electrical and condensate drain connections are
complete when chassis is installed correctly into
sleeve.
Step 3 — Install Thermostat and Connect Thermostat Wiring — (Thermostat and subbase
are packaged separately with unit shipment.) Thermostat can be installed in 50QT or in remote location.
TO MOUNT THERMOSTAT IN UNIT;
1. Remove metal cover plate by removing 6 screws.
2. Locate and install subbase onto thermostat bracket running between right and left coil par tition (see Fig. 3). Push plug and wires through hole provided.
3. Connect plug from subbase to mating socket located on left coil partition (see Fig. 3).
4. Attach thermostat to subbase and snap on thermostat cover.
5. Cut hole in stenciled area on back side of wrapper with a sharp utility knife.
6. Cut and remove insulation from hole in metal cover plate.
7. Replace metal cover plate.
TO MOUNT THERMOSTAT REMOTELY:
1. Pull subbase extension cord, previously installed, up into the return air inlet. Plug cord into mating socket on the left-hand coil partition. (See Fig. 3.)
FUSIBLE-
PLUG
CRANKCASE HEATER THERMOSTAT
50QT112, 115, 118
^Accumulator and compressor location reversed on 50QT112 tCompressor guard removed

Fig. 2 — Outdoor Component Location

OUTDOOR COIL
00 FAN MOTOR (PROPELLER FAN REMOVED TO SHOW MOTOR)
COMPRESSOR MOUNTING PAN
CHASSIS GUIDE CHANNEL
50QT124, 130
^Outdoor fan guard and compressor guard removed to show
components
ACCURATER LOCATION
MAIN CONTROL BOX COVER
MATING SOCKET
LOCATION
INDOOR NAMEPLATE LOCATION
THERMOSTAT MOUNTING BRACKET
50QT112,115,118
ELECTRIC HEATER CONTROL BOX COVER
CHASSIS MOUNTING BOLTS (6 TOTAL)
SLEEVE ELECTRIC HEATER JUNCTION LOCATION BOX ACCESS PLATE
MAIN CONTROL
BOX (SLIDES OUT FOR servicing:
CENTER PARTITION
INDOOR COIL CONDENSATE
DRAIN LEFT COIL PARTITION
INDOOR NAMEPLATE LOCATION

Fig. 3 — Indoor Component Location

THERMOSTAT PLUG
50QT124,130
ELECTRIC HEATER COVER
./INDOOR FAN
MOTOR (NOT VISIBLE)
DEFROST
/THERMOSTAT ON
LIQUID LINE LOW-PRESSURE
SWITCH
v(NOT SHOWN)
^COMPRESSOR
SUCTION SERVICE PORT
BRIGHT COIL
■ PARTITION
ROOM THERMOSTAT
(CAN BE MOUNTED
REMOTELY)
INDOOR AIR FILTER
2. Plug other end of cord, hanging from the wall at its remote location, securely into subbase.
3. Push plug and excess leads into wall hole. Cover hole appropriately to avoid incorrect thermostat
readings.
4. Mount subbase onto wall.
5. Attach thermostat to subbase. Snap on cover
and install chassis indoor cover.

> COLD CLIMATE ACCESSORY

Cold climate accessory should be installed on 50QT100 units where the outdoor ambient tem perature consistently falls below 30 F. Cold climate accessory is available in both six packs and single packs as indicated below: for 50QT112, 115, 118 —
accessory part no. 50QT90016106 (six pack) or 50QT900160 (single pack); for 50QT124, 130 — accessory part no. 50QT90017106 (six pack) or 50QT900170 (single pack).

START-UP

Crankcase Heater — The 50QT compressor is
equipped with a crankcase heater that is thermo statically activated in cold weather. (See Fig. 2 and
3.) If temperature is below 65 F, operate crankcase heater 24 hours before starting unit. To energize crankcase heater only, after chassis installation, set thermostat to <C > ^position and turn on unit power at disconnect switch.
Thermostat Anticipator Room thermostat anticipator settings for all 50QT heat pumps is
0.20 amps. This setting may be changed slightly to
provide a greater degree of comfort fora particular installation.
To Start Unit — Check that main power is on and, if temperature is below 65 F, that compressor crankcase heater has been energized for at least
24 hours.
1. Set selector switch at*C •
2. Set fan switch as desired (FAN) (AUTO.).
3. Set thermostat lever at the desired temperature.
4. Set selector switch at HEAT or COOL. Check system refrigerant charge. See Refrigerant
Charging.

SERVICE

Low-Pressure Switch (Safety Control) is lo
cated on liquid line downstream of AccuRater™ control during cooling mode (or upstream of Accu
Rater control during heating mode). Switch opens at 5 psig and shuts down compressor to protect it
from overheating if refrigerant charge is too low.
High and low side pressure connections are acces
sible from the incloor portion of the unit for
charging. (See Fig. 3.)
High-Pressure Relief Valve (Safety Control) is located in compressor. Relief valve opens at a pres
sure differential of approximately 450 ± 50 psi between suction (low side) and discharge (high side) to allow pressure equalization.
Internal Current and Temperature Sensitive Overload (Safety Control) re.sets automatically
when compressor motor temperature drops to a safe level (overloads may require up to one hour to reset).
#
#
When an internal overload is suspected of being open, check by using an ohmmeter or continuity tester. If necessary, refer to Carrier Standard Service Techniques Manual, Chapter 2, Electrical, for complete instructions.
Defrost Control, consisting of a defrost timer, defrost thermostat and defrost relay, interrupts normal system heating operation to remove frost and ice formation on outdoor coil. Frost impairs unit performance. Defrost control simultaneously stops outdoor fan, energizes reversing valve sole noid to switch system into cooling cycle (outdoor unit as condenser, indoor unit as evaporator), and activates electric heater. Unit can defrost every 90 minutes, but will do so only if outdoor temperatures are in the frosting temperature zone.
For heat pump to defrost, 2 conditions are
necessary:
1. Defrost timer contacts must be closed.
2. Coil temperature must be cold enough to cause defrost thermostat contacts to close.
Contacts close at 28 ±3 F (50QT112 - 118) and
35 ± 3 F (50QT124, 130). Every 90 minutes of elapsed running time, the defrost timer contacts close for 10 seconds. If the defrost thermostat contacts are closed, the unit defrosts. The defrost timer limits defrosting period to 10 minutes.
Normally the frost is removed and the defrost ther mostat contacts will open to terminate defrosting before 10 minutes have elapsed. Defrost thermostat contacts open at 65 ±5F (50QT112 - 118) and 75 ±5F (50QT124,130). When defrosting is terminated, the outdoor fan motor is energized and reversing valve solenoid is de-energized, re turning unit to heating cycle.
HEAT PUMP CIRCUITS shown in Fig. 4 are refrigerant flow diagrams for heating and cooling
cycles.

Refrigerant Charging

CAtlTiOf^; To pfeveat persotial fejury. 'wear

safeij; giasoe» ao<3 giovfes ha»d3t»g

Do not overcharge system. An overcharge can
cause compressor flooding.
Unit refrigerant system is factory charged. When
recharging is necessary, weigh in total charge indi cated in Table 2. (Charge must be weighed in during heating season.) Remove any refrigerant remaining in system before recharging. If system has lost com
plete charge, triple-evacuate system to 5000 microns (29.7 in. vacuum) before recharging. Service port connections are provided on unit suction and dis
charge lines for evacuation and charging. (See Fig. 4
for service port location.) Dial-a-charge charging
cylinder is an accurate device used to recharge
systems by weight. These cylinders are available at
refrigeration supply firms.
Table 2 — Service Data
UI\IIT50QT 112 MODEL R-22 CHARGE* (lb) 2 7 2 7 3 2
Refrig Control AccuRater™ Bypass Type
INDOOR FAN Centrifugal Blower,
Rotationt Rpm
Diameter (in ) Width (in.)
Range (cfm) Motor Hp
OUTDOOR FAN
Cfm
Rpm 1125 Diameter (in ) Motor Hp Vs
ccw cw
Counterclockwise Clockwise
1580
430/ 375
1700
115
300
300
Direct Drive, 2-Speed
CW CW CCW
CW
1550 1570 1675
6
6
550/ 575/ 475 480
'A Vs.
'A
Propeller, Direct Drive, Single Speed
1700 1700 2000 2000
‘Factory refrigerant charge fLooking at fan motor shaft
118
300
6
8
15
124 130
300 300
4 5
CCW 1675
7 7
885/ 800
1025/
'/4 V4
47
960
To check and/or adjust charge during cooling season, use Cooling Cycle Charging Charts (Fig. 5, 7, 9, II, 13) and follow Charging Chart Method below. The charging chart may also be used as an alternate method of recharging system.
To check system operation during heating cycle, use Heating Cycle Operation Check Chart (Fig. 6, 8,
10, 12, 14). These charts indicate whether a correct relationship exists between system operating pres sures and air temperatures entering unit. If pressure and temperature lines do not intersect on chart, the system refrigerant charge may not be correct or other system abnormalities may exist. Do not use Operating Check Charts to adjust refrigerant charge. Weigh charge into system.
COOLING CYCLE CHARGING CHART
METHOD
1. Operate unit a minimum of 10 minutes before checking charge, and after each charge adjustment.
2. Measure suction pressure by attaching a gage to unit suction service port. (See Fig. 4 for correct
service port location.)
3. Measure outdoor (coil inlet) air dry-bulb tem perature. Use service thermometer.
4. Using a sling psychrometer, measure wet-bulb temperature of air entering indoor fan coil.
5. Refer to Charging Chart. Locate on curves where outdoor air dry-bulb and indoor air wet-bulb temperature lines intersect.
6. From intersect point, project vertically down ward to chart suction pressure line. Compare
chart suction pressure to unit suction pressure
(Step 2).
7. If unit suction pressure is lower than chart pres sure, add refrigerant to system until chart
pressure is reached. If unit suction pressure is higher than chart pressure, remove refrigerant until chart pressure is reached.
3 Unit Piping
t
Fig. 4 — 50QT Refrigerant Flow Diagrams
70 72 74 76 78 80 82 84 86 88 90 92
SUCTION PRESSURE (PSIG)
Fig. 5 — 50QT112 Cooling Cycle
Charging Chart
Fig. 6 — 50QT112 Heating Operation
Check Chart
360
350
340
330
320
310
300
290
280
270
260
250
240
230
220
210
200
190
64 66 68 70 72 74 76 78 80 82 84 86
SUCTION PRESSURE (PSIG)
Fig. 7 — 50QT115 Cooling Cycle
Charging Chart
SUCTION PRESSURE (PSIG)
Fig. 9 — 50QT118 Cooling Cycle
Charging Chart
Fig. 8 — 50QT115 Heating Operation
Check Chart
Fig. 10 — 50QT118 Heating Operation
Check Chart
390
380
370
360
350
340
330
320
310
300
290
280
270
260
250
240
230
220
70 72 74 76 78 80 82 84 86 88 90 92
SUCTION PRESSURE (PSIG)
Fig. 11 — 50QT124 Cooling Cycle
Charging Chart
68 70 72 74 76 78 80 82 84 86 88 90
SUCTION PRESSURE (PSIG)
Fig. 13 — 50QT130 Cooling Cycle
Charging Chart
10 20 30 40 50 60
SUCTION PRESSURE (PSIG)
Fig. 12 — 50QT124 Heating Operation
Check Chart
10 20 30 40 50 60
SUCTION PRESSURE (PSIG)
Fig. 14 — 50QT130 Heating Operation
Check Chart
#
AccuRater™ Device (Dual-Piston Type) Servicing — See Fig. 15 for dual-piston AccuRater
components. The pistons have a refrigerant meter ing orifice through them. The retainers form a stop for the pistons in the refrigerant bypass mode, and a sealing surface for liquid line flare connection. To clean or replace piston;
1. Shut off power to unit.
2. Protect area around unit to prevent damage to interior, furnishings, etc.
3. Remove refrigerant from unit.
4. Remove liquid line flare connections from AccuRater. See Fig. 3 for AccuRater location.
5. Note position of arrow on AccuRater body in relation to unit.
6. Pull retainer out of body. Be careful not to scratch flare sealing surface. If retainer does not pull out easily, carefully use locking pliers to remove retainer. Replace scratched or damaged
retainer.
7. Slide piston out by in.serting a small soft wire through metering hole (18-gage thermostat
wire). Check that metering hole, sealing surface around piston cones and fluted portion of piston are not damaged.
8. See chart on indoor blower scroll for illustration
of proper arrangement and sizes of pistons.
9. Clean piston refrigerant metering orifice.
10. Replace retainer O-ring before reassembling AccuRater. Carrier O-ring Part No. is 99CC501052.
LIQUID LINE STRAINERS (protect AccuRater), are made of wire mesh and located in the liquid line on each side of the AccuRater. The strainers are pressed into the line. Remove strainer by threading a #10 sheet metal screw into strainer and pulling the screw with pliers.
Compressor Removal — (Refer to Fig. 2.)

caafsoi be

xaoVfiiS fmm aa btsislied cfesssis* Rmove
fnbi» sleeve, feratg. io &eTvice ijttcfe
or deales' sJiojr T^efore retaoviag coiap-ressor.
See Table 3 for compressor information. Follow safety codes and wear safety glasses and work gloves. Have quenching cloth available.
Table 3 — Compressor Data
UNIT 50QT
112
115
118
124
130
CONIPRESSOR
Copeland
RE-Z30150-PFV
Tecumseh
AB5515H Copeland
CRB1-0175 PFV
Copeland
CRD-10200-PFV
Copeland
CRF1-0250-PFV

Compressor Removal — 50QT112, 115, 118

1. Shut off power to unit. Remove chassis indoor cover, Fig. 1.
2. Remove chassis to truck or shop.
3. Remove refrigerant from unit using refrigerant removal methods described in Carrier Standard Service Techniques Manual, Chapter I,
Refrigerants.
4. Remove core from suction and discharge line Schrader valves.
5. Remove compressor guard.
OIL RECHARGE
(oz)
20
32
51
51
51
#
CQCSL»i&
coociweEssTOii
mr
TO
i«>T£. are too&iec «sideciPAccvRiaw ssi cosi>t>0oeRt& ¡s ««(cai-fijr
iOQiTirtCATiOM
COOytiiS
STA»P££f

coupi.{(«5aocif ,

STRiawes
correct

Fig. 15 — AccuRater Device (Dual-Piston) Components

'50
(«BOOR
<m.
6. Disconnect compressor wiring at compressor terminal box.
7. Using a tubing cutter, cut suction and discharge lines at convenient place near compressor for easy reassembly to new eompressor with copper slip couplings.
8. Remove crankcase heater from compressor
base.
9. Remove clamp holding accumulator to shell.
10. Remove compressor holddown bolts and lift compressor out, sliding and tipping it towards the outside.
11. Carefully unbraze suction and discharge line
piping stubs from compressor. If oil vapor in piping stubs ignites, use quenching cloth.
12. Braze piping stubs (removed in step 11) on new
compressor, in .same position as before.
13. Install new compressor in unit. Braze suction
and discharge lines to compressor piping using field-supplied copper couplings. Ensure com pressor holddown bolts are in place. Reinstall crankcase heater. Connect wiring.
14. Triple-evacuate to 5000 microns and recharge unit. See Refrigerant Charging section.
15. Refer to NOTE at the end of this section for important information.

Compressor Removal — 50QT124, 130

1. Shut off power to unit. Remove chassis indoor cover. Fig. 1.
2. Remove chassis to truck or shop.
3. Remove refrigerant from unit using refrigerant removal methods described in Carrier Standard Service Techniques Manual, Chapter 1,
Refrigerants.
4. Remove core from suction and discharge line Schrader valves.
5. Remove outdoor fan guard.
6. Remove outdoor compressor guard.
7. Remove outdoor propeller fan.
8. Remove outdoor fan orifice ring by removing 4 screws attaching it to outdoor fan motor bracket.
9. Remove 3 of 4 outdoor fan motor bolts, leaving bolt at upper right of fan motor in place. Rotate motor up and out of the way by hinging it on remaining bolt. Use wire or solder to tie outdoor fan motor to outdoor coil support on top side
of coil.
10. Using a miniature tubing cutter, cut compressor suction tube on short vertical run as tube enters compressor.
11. Cut compressor discharge tube on horizontal tubing run approximately 6 to 12 in. from where it leaves the compressor. Keep crankcase heater thermostat on right side of cut so it stays in place when compressor is removed.
12. Disconnect compressor wiring at compressor terminal box. Remove compressor wires and crankcase heater splice from box.
13. Using an 18-in. long extension on ratchet wrench, remove 4 compressor holddown bolts.
14. Slide compressor out to edge of pan. Remove erankcase heater by loosening worm drive clamp and sliding over top of compressor.
15. Remove compressor from pan.
16. Carefully unbraze suction and discharge line piping stubs from compressor. If oil vapor in piping stubs ignites, use quenching cloth.
17. Braze piping stubs (removed in step 11) on new compressor, in same direction as before.
18. Using field-supplied copper couplings, install
new compressor in unit.
19. Reassembly is reverse of above procedure.
20. Triple-evacuate to 5000 microns and recharge unit. See Refrigerant Charging section.
NOTE: If a compressor failure was caused by motor winding burnout, the by-products of the burnout must be separated from the circulating refrigerant. This must be done before the by products enter the reversing valve or aceumu­lator and render parts inoperative. Burnout by-products can cause future system operating problems if left in the system.
Clean the system by installing a suetion line drier in the refrigerant line where the suction gas enters the reversing valve. During the cooling cycle, this is the line from the indoor eoil run ning to the compressor compartment; during heating cycle, install drier in line between outdoor eoil and reversing valve. If possible,
run unit in cooling mode when cleaning system
as no defrosting occurs.
To provide protection for the 4-way valve, do not place filter drier between 4-way valve and accumulator. Since the suction drier works
on one mode only, temporarily wire the unit in the seleeted mode (heating or cooling, based on
suction drier location). To insure cooling opera
tion only, install a jumper between terminals
no. 1 and no. 4 on receptaele no. 3. For heating
operation only, remove and insulate one of the
reversing valve solenoid leads. Run unit for
48 hours and check oil for acidity. If satis
factory, remove suction line drier. Refer to
and follow procedure under AccuRater™
Servicing for cleaning of AccuRater. Rewire
unit to normal condition.
Lubrication — Compressor contains factory oil charge. Replace oil when lost. See Table 3 for oil
#
10
recharge. If necessary, refer to Carrier Standard Service Techniques Manual, Chapter 1, Refrig erants, page 1-21, for oil recharging procedure. Use Carrier PP33-1, Texaco WF-32 or Suniso 3GS oil.
FAN MOTOR BEARINGS — Oiling holes are pro vided at each end of condenser fan motor. Remove fan motor and lubricate motor with 32 drops (16 drops per hole) of SAE 10 nondetergent oil at intervals described below:
a. Annually, when environment is very dirty,
ambient temperature is higher than 105 F and average unit operating time exceeds 15 hours a day.
b. Every 3 years when environment is reasonably
clean, ambient temperature is less than 105 F and unit operating time averages 8 to 15 hours a day.
c. Every 5 years when environment is clean,
ambient temperature is less than 105 F and unit operating time averages less than 8 hours a day.
INDOOR MOTOR — To oil indoor motor, remove dust caps or plugs from oil holes located at each end of the motor. Use a teaspoon, 5 cc (5 ml), 3/16 oz or
16 to 25 drops of a good grade of SAE 20 nondeter gent motor oil in each oil hole. Allow time for total quantity of oil to be absorbed into each bearing. After oiling motor, be sure to wipe off excess oil from housing and replace cap or plugs on oil port.
Outdoor Coil Cleaning — To be done at the beginning of each cooling season or more often if
required.
4. If oil deposits are present, spray coil with liquid household detergent. Wait 10 minutes, then proceed to step 5.
5. Using garden hose, spray coil perpendicularly to coil tubes with a constant stream of water at moderate pressure (see Fig. 17). Keep nozzle at a
15 to 20 degree angle, about 3 in. from coil face
and 18 in. from tube. Spray so debris is washed
out and away from coil making sure water does not contact components on side of chassis.

<iajiiage or re^val eati tessli

aot iiSre waiec, steam>

or voiatUe or coiro^xve oji tass m "
1. Shut off power to unit.
2. Remove chassis from sleeve by removing 6 bolts and sliding chassis out. Transport chassis to an appropriate cleaning location.
3. Clean coil using vacuum cleaner and its crevice tool (see Fig. 16). Work crevice tool perpendicu larly to coil tubes, making sure tool only touches dirt on fins. To prevent fin removal, do not “scrub” fins with tool or move tool parallel to coil tube configuration.
w
Fig. 16 — Crevice Cleaning Tool
Fig. 17 — Positioning Hose to Spray Coil
II
6. Make sure condensate pan drain is not clogged with debris.
7. Reinstall chassis in sleeve.
8. Restore power to unit.
Indoor Coil and Condensate Pan Cleaning —
Clean and inspect indoor coil, condensate pan and drain at same time outdoor coil is cleaned.
1. Use vacuum cleaner nozzle to clean the face of coil.
2. Clean condensate pan with a brush similar to that shown.
3. Hold pail under condensate pan drain connec tion and flush pan by slowly pouring water on coil. Do not overflow pan.
Indoor Air Filter Replacement (Refer to Fig. 3.) — Replace filters at least 4 times per year especially
at the beginning of the heating and cooling seasons.
On 50QT112, 115 and 118, slide filter through slots at bottom of left and right coil partitions. Slide filter upward until top of filter reaches top of filter brackets. Then, rest bottom of filter on bottom flanges of left and right coil partitions.
On 50QT124 and 130, slide filter upward until top of filter reaches top of filter brackets. Then,
rest bottom of filter on horizontal sheet metal shelf
between left and right coil partitions making sure
tabs at bottom of filter brackets hold filter in place. Outdoor Fan Adjustment — Required fan posi
tion is shown in Fig. 18. Adjust position by loosen ing setscrew on fan hub and moving in or out of orifice.
Outdoor Fan/Motor Removal
1. Shut off power to unit.
2. Remove chassis from sleeve as described pre viously in Outdoor Coil Cleaning section.
UNIT 50QT
112, 115, 118 2V2
124, 130 2
DIMENSION A
(in.)
Fig. 18 — Outdoor Fan Position
Remove 4 nuts from outer tip of coil support
rods and remove wire mesh guard.
Remove fan blade from motor shaft by loosening
4. hub setscrews and slipping it off shaft.
5. Remove fan motor leads from electrical com
ponents in indoor side control box and pull through bulkhead so they are loose in outdoor machine compartment.
6. Remove nuts and bolts connecting 4 motor ears to motor support struts.
7. Remove motor and leads.
8. Reassembly is reverse of above procedure. Make sure guard is replaced and fan is positioned correctly as in Fig. 2.
12
TROUBLESHOOTING CHART — COOLING CYCLE
#
LU
o
>■
o
CD
tog
DC £
lij|_
b< < CC
HI uj
X Q. Q.O
<02
<o^
ljjy> I ccOu-1
I— LU LU I
(0(00 I
Z <
X
gg o~
QZ HZ 3D OX X -i
X Xiu tUH
5< OLU X I
-h-i2 “t-z
2-uj ZoS
LU ^ LU X i _l OGLU
O X LUZ
EC2 H 3
(0/-1
III LU
Z
-J
to 3 X
z g
o
-J CO
5 CC
h OQ
ccqI^
LU S C5
HhO
<oo
oiSg
<0:9
<i
X X
_l -J <x
Zq:
£°2
E50
X H
<
LU
zz LU LU
CQ LU
Q X (3
< X G X X Q Z 3
XD oo
o° 2z
Z X <3 X ffl
X
lLU H
X 3
to X
f ^
X UJ
<o Zx
X X
H^
5x Ex
On
_l
lQ
X
Ov
H^
dE
OQ
ai
U. LU LU I
OK
IL CC
0>(r
lu<E
U. U ¡c
LU LU £
OXh-
IW
!iJo
s?
[Xm
G CC
<|d
<
G?G
>
E^£
o
H<f G
z
^i=X QGX <XX' XZ C
X
O
- E
a o
?cc
zm
LU 3
Q-O
O a.
(O CO Q CO <LU
Sec
“^5
wg
OK
_) <
LJ QJ lU CC
>iuo
pou.
o <
lul-Z
Li. -i <
lUOX
Q>l-
k
So
O
o ^
Oi-
5
cc<
X
o
(O
to LU
5d
ofe
5>
LU
(5 LL
Z LU
x> LU <
> -I
8t
cc:?
Oco
Gqc
<o
Z LU
OQl
GO
X LU
LU>
X cu
QU-
LU
9q
2<
-JO
X
< xO
H. OZ
ZlunS
yccejo Xh-XLU
X < LU X OLUZ> (OXLU&
So
X CC
Og
OJZ
X
o X
<
For replacement items use Carrier Specified Parts
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book
1
Tab
5a
4 5a
Form 50QT-1OSI Supersedes 50QT-8SI
Printed in U S A
5-84
PC101 Catalog No 565-033
t
Loading...