Carrier 50PSH009, 50PSH012, 50PSH018, 50PSH024, 50PSH030 Installation And Service Instructions Manual

...
50PSH, PSV, PSD006-070
Single-Stage Water Source Heat Pumps
with PURON® Refrigerant (R-410A)
Installation, Start-Up, and
Service Instructions
AQUAZONE™
CONTENTS
Page
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . . 2
GENERAL. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Step 1 — Check Jobsite. . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Step 2 — Check Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
• STORAGE
• PROTECTION
• INSPECT UNIT
Step 3 — Locate Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
• FIELD CONVERSION OF DISCHARGE AIR
Step 4 — Mount the Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
• HORIZONTAL UNIT
• VERTICAL UNITS
Step 5 — Check Duct System . . . . . . . . . . . . . . . . . . . . . . 9
• SOUND ATTENUATION
• EXISTING DUCT SYSTEM
Step 6 — Install Condensate Drain . . . . . . . . . . . . . . . . . 9
• HORIZONTAL UNIT
• VERTICAL UNITS
• VENTING
Step 7 — Pipe Connections . . . . . . . . . . . . . . . . . . . . . . . 10
• WATER LOOP APPLICATIONS
• GROUND-WATER APPLICATIONS
• GROUND-LOOP APPLICATIONS
• INSTALLATION OF SUPPLY AND RETURN HOSE KIT
Step 8 — Wire Field Power Supply . . . . . . . . . . . . . . . . 13
• POWER CONNECTION
• SUPPLY VOLTAGE
• 208-VOLT OPERATION
• 460-VOLT OPERATION
Step 9 — Wire Field Controls . . . . . . . . . . . . . . . . . . . . . 27
• THERMOSTAT CONNECTIONS
• WATER FREEZE PROTECTION
• AIR COIL FREEZE PROTECTION
• ACCESSORY CONNECTIONS
• WATER SOLENOID VALVES
• WSHP OPEN WIRING
• COOLING
• HEATING
• CFM ADJUST
• DEHUMIDIFICATION MODE
PRE-START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
System Checkout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
FIELD SELECTABLE INPUTS . . . . . . . . . . . . . . . . . . 32-35
Complete C Control Jumper Settings . . . . . . . . . . . . . 32
Deluxe D Control Jumper Settings . . . . . . . . . . . . . . . . 32
Complete C Control DIP Switches. . . . . . . . . . . . . . . . . 32
Deluxe D Control DIP Switches . . . . . . . . . . . . . . . . . . . 32
Units with Modulating Hot Water Reheat
(HWR) Option . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Deluxe D Control Accessory
Relay Configurations . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Page
START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35-42
Operating Limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .35
Scroll Compressor Rotation. . . . . . . . . . . . . . . . . . . . . . .35
Unit Start-Up Cooling Mode . . . . . . . . . . . . . . . . . . . . . . .35
Unit Start-Up Heating Mode . . . . . . . . . . . . . . . . . . . . . . .36
Flow Regulation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .41
Flushing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .41
Antifreeze . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .41
Cooling Tower/Boiler Systems . . . . . . . . . . . . . . . . . . . .42
Ground Coupled, Closed Loop and Plateframe
Heat Exchanger Well Systems. . . . . . . . . . . . . . . . . . .42
OPERATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42-46
Power Up Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .42
Units with Aquazone Complete C Control . . . . . . . . .42
Units with HWR Option. . . . . . . . . . . . . . . . . . . . . . . . . . . .43
Units with WSHP Open Multiple Protocol. . . . . . . . . .43
COMPLETE C AND DELUXE D BOARD
SYSTEM TEST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46,47
Test Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .46
WSHP Open Test Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . .47
Retry Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .47
Aquazone Deluxe D Control LED Indicators . . . . . . .47
SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48,49
Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .48
Water Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .48
Condensate Drain Pans . . . . . . . . . . . . . . . . . . . . . . . . . . .48
Refrigerant System. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .48
Compressor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .48
Fan Motors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .48
Condensate Drain Cleaning . . . . . . . . . . . . . . . . . . . . . . .48
Air Coil Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .48
Condenser Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .48
Checking System Charge . . . . . . . . . . . . . . . . . . . . . . . . .49
Refrigerant Charging. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .49
Air Coil Fan Motor Removal . . . . . . . . . . . . . . . . . . . . . . .49
Replacing the WSHP Open Controller’s
Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .49
TROUBLESHOOTING. . . . . . . . . . . . . . . . . . . . . . . . . . . 49-57
Control Sensors
Thermistor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .49
WSHP Open Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . .50
Thermostatic Expansion Valves
Stopped or Malfunctioned ECM Motor. . . . . . . . . . . . . 54
Moisture Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
APPENDIX A — WSHP OPEN SCREEN
CONFIGURATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58-63
50PSH,PSV,PSD START-UP
CHECKLIST . . . . . . . . . . . . . . . . . . . . . . . . . . . . CL-1, CL-2
IMPORTANT: Read the entire instruction manual before starting installation.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
. . . . . . . . . . . . . . . . . . . 50
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53500055-01 Printed in U.S.A. Form 50PS-3SI Pg 1 7-09 Replaces: 50PS-2SI
SAFETY CONSIDERATIONS
Installation and servicing of air-conditioning equipment can be hazardous due to system pressure and electrical compo­nents. Only trained and qualified service personnel should install, repair, or service air-conditioning equipment.
Untrained personnel can perform basic maintenance func­tions such as cleaning coils and filters and replacing filters. All other operations should be performed by trained service per­sonnel. When working on air-conditioning equipment, observe precautions in the literature, tags and labels attached to the unit, and other safety precautions that may apply.
Improper installation, adjustment, alteration, service, main­tenance, or use can cause explosion, fire, electrical shock or other conditions which may cause personal injury or property damage. Consult a qualified installer, service agency, or a local distributor or branch for information or assistance. The qualified installer or agency must use factory-authorized kits or accessories when modifying this product. Refer to the individ­ual instructions packaged with the kits or accessories when installing.
Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth for brazing operations. Have fire extinguisher available. Read these instructions thoroughly and follow all warnings or cautions attached to the unit. Consult local building codes and the National Electrical Code (NEC) for special installation requirements.
Understand the signal words — DANGER, WARNING, and CAUTION. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards that could result in personal inju­ry or death. CAUTION is used to identify unsafe practices, which would result in minor personal injury or product and property damage.
Recognize safety information. This is the safety-alert symbol ( ). When this symbol is displayed on the unit and in instructions or manuals, be alert to the potential for personal injury.
WARNING
Electrical shock can cause personal injury or death. Before installing or servicing system, always turn off main power to system. There may be more than one disconnect switch. Turn off accessory heater power if applicable.
Water source heat pumps (WSHPs) are single-package hori­zontally and vertically mounted units with electronic controls designed for year-round cooling and heating. Aquazone WSHPs are available in the following unit configurations:
• 50PSH unit with horizontal airflow and right, left or back
discharge
• 50PSV unit with vertical airflow and top discharge
• 50PSD unit with vertical airflow and bottom discharge
(downflow)
IMPORTANT: The installation of water source heat pump units and all associated components, parts, and accessories which make up the installation shall be in accordance with the regulations of ALL authorities having jurisdiction and MUST conform to all applicable codes. It is the responsi­bility of the installing contractor to determine and comply with ALL applicable codes and regulations.
INSTALLATION
Step 1 — Check Jobsite —
maintenance instructions are provided with each unit. Before unit start-up, read all manuals and become familiar with the unit and its operation. Thoroughly check out the system before operation. Complete the inspections and instructions listed below to prepare a unit for installation. See Table 1 for unit physical data.
IMPORTANT: This equipment is designed for indoor installation ONLY. Extreme variations in temperature, humidity and corrosive water or air will adversely affect the unit performance, reliability and service life.
HORIZONTAL UNIT (50PSH) —
ed for indoor installation only. Be sure to allow adequate space around the unit for servicing. Refer to Fig. 1 for an illustration of a typical horizontal installation. See Fig. 2 for overall unit dimensions.
VERTICAL AND DOWNFLOW UNITS (50PSV, PSD) — Vertical units are designed for indoor installations. While verti­cal units are typically installed in a floor-level closet or a small mechanical room, the unit access guidelines for these units are very similar to those described for horizontal units. See Fig. 3 and 4 for overall dimensions. Refer to Fig. 5 for an example of a typical vertical installation. Refer to Fig. 6 for a sample downflow installation.
Installation, operation and
Horizontal units are design-
GENERAL
This installation and start-up instructions literature is for
Aquazone™ single-stage water source heat pump systems.
CAUTION
To avoid equipment damage, do not use these units as a source of heating or cooling during the construction pro­cess. The mechanical components and filters used in these units quickly becomes clogged with construction dirt and debris which may cause system damage.
2
Table 1 — Physical Data — 50PSH, PSV, PSD018-070 Units
50PS UNIT SIZE 006* 009* 012* 018 024 030 036 042 048 060 070 COMPRESSOR (1 Each) Rotary Scroll FACTORY CHARGE R-410A (oz) 24 32 34 50 56 58 70 80 80 136 144 ECM FAN MOTOR AND BLOWER
Fan Motor (Hp) N/A N/A N/A Blower Wheel Size (D x W) (in.) N/A N/A N/A 9 x 7 9 x 7 9 x 7 11 x 10 11 x 10 11 x 10 11 x 10 11 x 10
PSC FAN MOTOR AND BLOWER (3 Speeds)
Fan Motor (Hp) High Static Fan Motor (Hp) N/A N/A N/A Blower Wheel Size (D x W) (in.) 6 x 5 6 x 5 6 x 5 9 x 7 9 x 7 9 x 7 10 x 10 10 x 10 10 x 10 11 x 10 11 x 10
Heat Exchanger Water Volume (gal.) 0.56 0.56 0.56 0.56 0.76 0.76 0.92 1.24 1.24 1.56 1.56 COAXIAL VOLUME (gal.) .17 .29 .45 .56 .76 .76 .92 1.24 1.24 1.56 1.56
WATER CONNECTION SIZE, FPT (in.)
HWG CONNECTION SIZE, FPT (in.) N/A N/A N/A
VERTICAL UPFLOW/DOWNFLOW
Air Coil Dimensions (H x W) (in.) 16 x 16 16 x 16 16 x 16 24 x 20 28 x 20 28 x 20 28 x 25 32 x 25 32 x 25 36 x 25 36 x 25
Throwaway Filter, Standard 1-in.,
Qty...Size 1...
Weight
Operating (lb) 126 146 150 252 266 268 327 414 416 441 443 Packag ed (lb) 136 156 160 262 276 278 337 424 426 451 453
HORIZONTAL
Air Coil Dimensions (H x W) (in.) 16 x 16 16 x 16 16 x 16 18 x 27 18 x 31 18 x 31 20 x 35 20 x 40 20 x 40 20 x 45 20 x 45
Throwaway Filter, Standard 1-in.,
Qty...Size 1...
Weight
Operating (lb) 136 156 160 257 266 268 327 414 416 441 443 Packag ed (lb) 146 166 170 267 276 278 337 424 426 451 453 Corner (lb)
Left Front 45.0 55.0 56.0 74.7 78.8 79.4 104.4 144.3 145.0 182.3 183.1 Left Rear 33.0 36.0 37.0 66.2 69.9 70.4 83.7 97.7 98.1 78.4 78.8 Right Front 30.0 33.0 34.0 63.6 67.2 67.7 74.9 92.1 92.6 72.5 72.8 Right Rear 28.0 32.0 33.0 47.5 50.2 50.5 64.0 79.9 80.3 107.8 108.3
ECM — Electronically Controlled Motor PSC — Permanent Split Capacitor FPT — Female Pipe Thread TXV — Thermostatic Expansion Valve HWG — Hot Water Generator
LEGEND *Unit sizes 006-012 not available on 50PSD unit.
1
/
25
1
/
2
16 x 20
16 x 20
1
/
20
1
/
2
1...
16 x 20
1...
16 x 20
1
/
8
1
/
2
1...
16 x 20
1...
16 x 20
1
/
2
1
/
6
1
/
5
3
/
4
1
/
2
1...
24 x 24
2...
18 x 18
1
/
2
1
/
5
1
/
3
3
/
4
1
/
2
1...
28 x 24
2...
18 x 18
NOTE: All units have spring compressor mountings, TXV expansion devices, and in. and 3/4-in. electrical knockouts.
1
/
2
1
/
3
1
/
2
3
/
4
1
/
2
1...
28 x 24
2...
18 x 18
1
/
2
1
/
2
1
/
2
3
/
4
1
/
2
1...
28 x 30
1...
12 x 20;
1...
20 x 25
1
/
2
1
/
2
3
/
4
1111
1
/
2
2...
16 x 30
1...
18 x 20;
1...
20 x 24
111
3
/
4
3
/
4
1
/
2
2...
16 x 30
1...
18 x 20;
1...
20 x 24
11 1N/A
1
/
2
1...
16 x 30;
20 x 30
20 x 24
1...
2...
16 x 30;
20 x 30
20 x 24
1...
2...
1
/
2
1..
1
/2-
Step 2 — Check Unit — Upon receipt of shipment at
the jobsite, carefully check the shipment against the bill of lading. Make sure all units have been received. Inspect the car­ton or crating of each unit, and inspect each unit for damage. Ensure the shipping company makes proper notation of any shortages or damage on all copies of the freight bill. Concealed damage not discovered during unloading must be reported to the shipping company within 15 days of receipt of shipment.
NOTE: It is the responsibility of the purchaser to file all necessary claims with the shipping company.
1. Be sure that the location chosen for unit installation pro­vides ambient temperatures maintained above freezing. Well water applications are especially susceptible to freezing.
2. Be sure the installation location is isolated from sleeping areas, private offices and other acoustically sensitive spaces.
NOTE: A sound control accessory package may be used to help eliminate sound in sensitive spaces.
3. Check local codes to be sure a secondary drain pan is not required under the unit.
4. Be sure unit is mounted at a height sufficient to provide an adequate slope of the condensate lines. If an appropri­ate slope cannot be achieved, a field-supplied condensate pump may be required.
5. Provide sufficient space for duct connection. Do not al­low the weight of the ductwork to rest on the unit.
6. Provide adequate clearance for filter replacement and drain pan cleaning. Do not allow piping, conduit, etc. to block filter access.
7. Provide sufficient access to allow maintenance and servicing of the fan and fan motor, compressor and coils. Removal of the entire unit from the closet should not be necessary.
8. Provide an unobstructed path to the unit within the closet or mechanical room. Space should be sufficient to allow removal of unit if necessary.
9. Provide ready access to water valves and fittings, and screwdriver access to unit side panels, discharge collar, and all electrical connections.
10. Where access to side panels is limited, pre-removal of the control box side mounting screws may be necessary for future servicing.
STORAGE — If the equipment is not needed immediately at the jobsite, it should be left in its shipping carton and stored in a clean, dry area of the building or in a warehouse. Units must be stored in an upright position at all times. If carton stacking is necessary, stack units a maximum of 3 high. Do not remove any equipment from its shipping package until it is needed for installation.
PROTECTION — Once the units are properly positioned on the jobsite, cover them with either a shipping carton, vinyl film, or an equivalent protective covering. Cap open ends of pipes stored on the jobsite. This precaution is especially important in areas where painting, plastering, or spraying of fireproof mate­rial, etc. is not yet complete. Foreign material that accumulates within the units can prevent proper start-up and necessitate costly clean-up operations.
3
Before installing any of the system components, be sure to examine each pipe, fitting, and valve, and remove any dirt or foreign material found in or on these components.
CAUTION
DO NOT store or install units in corrosive environments or in locations subject to temperature or humidity extremes (e.g., attics, garages, rooftops, etc.). Corrosive conditions and high temperature or humidity can significantly reduce performance, reliability, and service life. Always move units in an upright position. Tilting units on their sides may cause equipment damage.
INSPECT UNIT — To prepare the unit for installation, com­plete the procedures listed below:
1. Compare the electrical data on the unit nameplate with ordering and shipping information to verify that the correct unit has been shipped.
2. Do not remove the packaging until the unit is ready for installation.
Filter Access
Field-supplied transition to minimize pressure loss
Supply Air
Insulated supply duct with at least one 90 degree elbow to reduce air noise (field-supplied)
Flexible Connection
Field-Supplied Electric Heat (if applicable)
Aux Electric Heat Disconnect
Power Wiring
Unit Power Disconnect (by others)
Unit Hanger (factory­supplied)
3/8” threaded rods
(by others)
Return Air (Ductwork not shown)
Unit Power
3. Verify that the unit’s refrigerant tubing is free of kinks or dents, and that it does not touch other unit components.
4. Inspect all electrical connections. Be sure connections are clean and tight at their terminations.
5. Loosen compressor bolts until the compressor rides freely on springs. Remove shipping restraints.
6. Remove the four
1
/4 in. shipping bolts from compressor support plate (two bolts on each side) to maximize vibra­tion and sound alternation.
CAUTION
Failure to remove shipping brackets from spring-mounted compressors will cause excessive noise and could cause component failure due to added vibration.
7. Remove any blower support cardboard from inlet of the blower.
8. Locate and verify any accessory kit located in compressor and/or blower section.
9. Remove any access panel screws that may be difficult to remove once unit is installed.
Thermostat
Wiring
Stainless steel braid hose with integral “J” swivel
(field-installed accessory)
Ball Valve with optional integral P/T plug (typical for supply and return piping)
Balancing Valve (field­installed accessory)
Low Pressure Drop Water Control Valve (optional) (field-installed accessory)
Building
Loop
Water Out
Water In
(field-installed accessory)
3/8” Threaded
Rod (by others)
Vibration Isolator
(white-compressor end
and red-blower end)
Washer
(by others)
Double Hex Nuts
(by others)
UNIT HANGER ISOLATION DETAIL
Fig. 1 — Typical Installation — 50PSH Unit
Integral hanger support­pre-attached in factory
A50-7728
4
WATER CONNECTIONS
F
HWG
In
G
HWG
Out
(in.)
H
Con-
densate
Loop
Wate r
FPT
1
/2N/A N/A N/A 3.8 6.3 8.8 5.3 4.1 9.0 9.0 5.3 4.1 17.1 15.3 2.1 1.0
3
/
4
4
4
OVER ALL
50PSH
UNIT SIZE
006,009,
012
018 22.4 62.2 19.3 2.1 10.0 13.9 16.9 0.6
024,
030
036 25.4 71.2 21.3 3.4 10.8 15.6 18.9 0.63/
042,
048
060,
070
NOTES:
1. Condensate is
2. Horizontal unit shipped with filter bracket only. This bracket should be removed for return duct connection.
3. Discharge flange and hanger kit is factory installed.
4. Shaded areas are recommended service areas, not required.
CABINET
(in.)
12 3 4 5
A
WidthBDepthCHeightDInEOut
22.4 43.1 17.3 3.7 9.7 N/A N/A 0.8
22.4 62.2 19.3 2.1 10.0 13.9 16.9 0.63/
25.4 76.2 21.3 3.4 10.8 15.6 18.9 0.6 11/25.96 13.13 3.6 6.1 8.6 3.1 1.2 19.0 17.5 3.1 1.0 39.8 18.2 3.1 1.5
25.4 81.2 21.3 3.4 10.8 15.6 18.9 0.6 11/25.96 13.13 3.6 6.1 8.6 3.1 1.2 19.0 17.5 3.1 1.0 44.8 18.2 3.1 1.5
3
/4-in. FPT copper.
a50-8231
WATER
CONNEC­TIONS (in.) ­UNITS WITH
HWR
12
HWG
FPT
Loop
Loop
In D
Out E
1
/22.1 10.0 3.6 6.1 8.6 3.6 2.0 12.5 15.5 3.6 2.0 28.1 16.2 2.3 1.5
1
/25.26 13.13 3.6 6.1 8.6 3.6 2.0 12.5 15.5 3.6 2.0 33.8 16.2 2.3 1.5
1
/25.96 13.13 3.6 6.1 8.6 3.1 1.2 19.0 17.5 3.1 1.0 34.8 18.2 3.1 1.5
ASP — Alternate Service Panel BSP — Blower Service Panel CAP — Control Access Panel CSP — Compressor Service Panel FPT — Female Pipe Thread HWG — Hot Water Generator HWR — Hot Water Reheat LH Left Hand RH Right Hand
ELECTRICAL KNOCKOUTS
J
1
/
2
Cond
Low
Vol ta g e
LEGEND
(in.)
K
1
/
Cond
Ext
Pump
DISCHARGE CONNECTION (in.)
DUCT FLANGE INSTALLED
(±0.10 in.)
L
3
/
2
4
M
Cond
Power
Supply
(LH
rtrn)
NO
Supply Height
P
Supply
Width
Q
(RH
rtrn)
RS
PSC BLOWER AIRFLOW
CONFIGURATION
CODE RETURN DISCHARGE
E Left Back B Right Back S Left Right Z Right Left
RETURN
CONNECTION (in.)
USING RETURN
AIR OPENING
(±0.10 in.)
Depth
T Return Height
Return
UV
Fig. 2 — 50PSH Dimensional Data
5
WATER CONNECTIONS
F
HWG
In
G
HWG
Out
(in.)
H
Conden-
sate
Loop
Water
FPT
4
4
4
OVERALL
50PSV
UNIT SIZE
006,009,
012
018 22.4 25.6 44.6 2.1 10.0 13.9 16.9 7.83/
024,
030
036 25.4 30.6 50.5 3.4 10.8 15.6 18.9 7.83/
042,
048
060,
070
NOTES:
1. Condensate is 3/4-in. FPT copper and is switchable from side to front.
2. Vertical unit shipped with filter bracket only, extending from unit 2.5-in. This bracket should be removed for return duct connection.
3. Discharge flange field installed.
4. Shaded areas are recommended service areas, not required.
CABINET
(in.)
12 3 4 5
A
WidthBDepthCHeightDInEOut
22.4 21.6 34.5 3.7 9.7 N/A N/A 7.41/2N/A N/A N/A 3.8 6.3 8.8 6.7 6.3 9.0 9.0 6.7 2.3 17.1 15.3
22.4 25.6 48.5 2.1 10.0 13.9 16.9 7.83/
25.4 30.6 54.5 3.4 10.8 15.6 18.9 7.8 11/25.96 13.13 3.6 6.1 8.6 6.4 6.3 18.0 18.0 5.3 2.2 26.1 31.2
25.4 30.6 58.5 3.4 10.8 15.6 18.9 7.8 11/25.96 13.13 3.6 6.1 8.6 6.4 6.3 18.0 18.0 5.3 2.2 26.1 35.2
WATER
CONNEC­TIONS (in.) ­UNITS WITH
HWR
12
HWG
FPT
Loop
Loop
In D
Out E
1
/22.1 10.0 3.6 6.1 8.6 7.2 5.8 14.0 14.0 4.9 2.2 21.1 23.2
1
/25.26 13.13 3.6 6.1 8.6 7.2 5.8 14.0 14.0 4.9 2.2 21.1 27.2
1
/25.96 13.13 3.6 6.1 8.6 6.4 6.3 18.0 18.0 5.3 2.2 26.1 27.2
ASP — Alternate Service Panel BSP — Blower Service Panel CAP — Control Access Panel CSP — Compressor Service Panel FPT — Female Pipe Thread HWG — Hot Water Generator HWR — Hot Water Reheat LH Left Hand RH Right Hand
ELECTRICAL KNOCKOUTS
J
1
/
2
Cond
Low
Vol t ag e
LEGEND
(in.)
K
1
/
Cond
Ext
Pump
2
L
3
/
4
Cond
Powe r
Supply
DISCHARGE CONNECTION (in.)
DUCT FLANGE INSTALLED
(±0.10 in.)
M
(LH
rtrn)
NO
Supply
Width
P
Supply
Depth
PSC BLOWER AIRFLOW
CONFIGURATION
CODE RETURN DISCHARGE
L Left Top R Right Top
Q
(RH
rtrn)
RS
RETURN
CONNECTION (in.)
USING RETURN
AIR OPENING
(±0.10 in.)
Return
Depth
T
Return
Height
U
1.0
1.0
1.0
1.0
1.0
1.0
R - Configuration Right Return / Top Discharge
- Top View
Right Return
- Air Coil Opening
- Right Side View
a50-8183
L - Configuration Left Return / Top Discharge
- Top View
Left Return
- Air Coil Opening
- Left Side View
Fig. 3 — 50PSV Dimensional Data
6
WATER CONNECTIONS
F
HWG
In
G
HWG
Out
(in.)
H
Conden-
sate
Loop
Wate r
FPT
4
4
4
OVERALL
50PSD
UNIT
SIZE
018 22.4 25.6 48.4 2.1 10.0 13.9 16.9 3.63/
024,
030
036 25.4 30.6 54.5 3.4 10.8 15.6 18.9 3.63/
042,
048
060,
070
NOTES:
1. Condensate is
2. Vertical unit shipped with filter bracket only, extending from unit 2.5-in. This bracket should be removed for return duct connection.
3. Downflow unit does not have discharge flange, and is rated for zero clearance installation.
4. Shaded areas are recommended service areas, not required.
CABINET
(in.)
12 3 4 5
A
WidthBDepthCHeightDInEOut
22.4 25.6 52.5 2.1 10.0 13.9 16.9 3.63/
25.4 30.6 58.5 3.4 10.8 15.6 18.9 3.6 11/25.96 13.13 3.6 6.1 8.6 7.2 9.0 13.4 12.9 10.4 2.2 26.1 31.2 1.0
25.4 30.6 62.5 3.4 10.8 15.6 18.9 3.6 11/25.96 13.13 3.6 6.1 8.6 7.2 9.0 13.4 12.9 10.4 2.2 26.1 35.2 1.0
3
/4-in. FPT copper and is switchable from side to front.
WATER
CONNEC­TIONS (in.) ­UNITS WITH
HWR
12
HWG
FPT
Loop
Loop
In D
Out E
1
/22.1 10.0 3.6 6.1 8.6 6.7 8.4 10.1 9.1 10.8 2.2 21.1 23.2 1.0
1
/25.96 13.13 3.6 6.1 8.6 6.7 8.4 10.1 9.1 10.8 2.2 21.1 27.2 1.0
1
/25.96 13.13 3.6 6.1 8.6 7.2 9.0 13.4 12.9 10.4 2.2 26.1 27.2 1.0
ASP — Alternate Service Panel BSP — Blower Service Panel CAP — Control Access Panel CSP — Compressor Service Panel FPT — Female Pipe Thread HWG — Hot Water Generator HWR — Hot Water Reheat LH Left Hand RH Right Hand
KNOCKOUTS
J
1
/
2
Cond
Low
Vol ta ge
LEGEND
ELECTRICAL
(in.)
K
1
/
2
Cond
Ext
Pump
L
3
/
4
Cond
Power
Supply
DISCHARGE CONNECTION (in.)
DUCT FLANGE INSTALLED
(±0.10 in.)
M
(LH
rtrn)
NO
Supply
Width
CODE RETURN DISCHARGE
P
Supply
Depth
PSC BLOWER AIRFLOW
CONFIGURATION
L Left Bottom
R Right Bottom
Standard Filter Bracket
Q
(RH
rtrn)
RS
RETURN
CONNECTION (in.)
USING RETURN
AIR OPENING
(±0.10 in.)
Return
Depth
T
Return
Height
U
a50-7846ef
P
Blower
O
Opening
Front
Q
Air Coil Side
B
Right Return / Bottom Discharge
U
ASP
N
A
Air Coil
N
P
Blower
O
A
Opening
M
Air Coil Side
B
Left Return / Bottom Discharge
1.1
U
CSP
2' Optional Service
Access Right Rtn
(left opposite)
Front
2' Service
Power Supply 3/4”
HV Knockout
1/2” Knockout
Low Voltage 1/2”
LV Knockout
Air Coil
Access
CSP
CSP
ASP
CAP
BSP
Condensate 3/4”
FPT
Isometric View
1.6
L
K
J
CAP
BSP
ASP
1.6
G
4
3
F
E
D
2
1
T
Front
S
Right Return Right View -
Air Coil Opening
Back
R
T
C
Back
R
Left Return Left View -
Air Coil Opening
S
Front
Fig. 4 — 50PSD Dimensional Data
7
Condensate 3/4” FPT
Right Return
H
Condensate 3/4” FPT
5
Left Return
Front-View
5
Supply Air
Building
Flexible Connection
Return
Air
Power
Thermostat Wiring
Compressor Access Panel
A50-7730
NOTE: Ball valve with integral pressure temperature plug recommended.
Loop
Water Out
Water In
Stainless steel braid hose with integral “J” swivel (field-installed accessory)
integral P/T plug (typical for supply and return piping) (field-Installed accessory)
Control Valve (optional) (field-installed accessory)
Ball Valve with optional
Balancing Valve (field-installed accessory)
Low Pressure Drop Water
Fig. 5 — Typical Vertical Installation — 50PSV Unit
FIELD CONVERSION OF DISCHARGE AIR — The dis­charge air of the 50PSH horizontal units can be converted between side and back discharge in the field. The conversion process is the same for right and left return configurations. See Fig. 7 and 8.
NOTE: It is not possible to convert return air between left or right return models in the field due to refrigerant piping changes.
Water
Connection End
Side Discharge
Water
Connection End
Remove Screws
Return Air
Rotate
Return Air
Flexible Connection
Return
Air
Power
Thermostat
Wiring
Compressor Access Panel
A50-7729
NOTE: Ball valve with integral pressure temperature plug recommended.
Supply Air
Building Loop
Water
Out Stainless steel braid hose with integral ”J” swivel(field­installed accessory)
Flexible
Connection
Water In
Balancing Valve
(field-installed
accessory)
Low Pressure Drop Water Control Valve (optional) (field-installed accessory)
Ball Valve with optional integral
P/T plug (typical for supply and return piping)(field-installed accessory)
Fig. 6 — Typical Downflow Installation —
50PSD Unit
Step 3 — Locate Unit — The following guidelines
should be considered when choosing a location for a WSHP:
• Units are for indoor use only.
• Locate in areas where ambient temperatures are between 39 F and 102 F and relative humidity is no greater than 75%.
• Provide sufficient space for water, electrical and duct connections.
• Locate unit in an area that allows easy access and removal of filter and access panels.
• Allow enough space for service personnel to perform maintenance.
• Return air must be able to freely enter the space if unit needs to be installed in a confined area such as a closet.
NOTE: Correct placement of the horizontal unit can play an important part in minimizing sound problems. Since ductwork is normally applied to these units, the unit can be placed so that the principal sound emission is outside the oc­cupied space in sound-critical applications. A fire damper may be required by the local code if a fire wall is penetrated.
Connection End
A50-6256
Return Air
Drain
Discharge Air
Move to Side
Water
Back Discharge
Replace Screws
Fig. 7 — Conversion Left Return,
Side Discharge to Back Discharge
Return Air
Supply Duct
Side Discharge
Back Discharge
Connection End
Fig. 8 — Conversion Right Return, Side Discharge to Back Discharge
Return Air
Drain
Discharge Air
Water
Connection End
Water
A50-6257
8
Preparation
— The unit should be on the ground in a well lit area. Hung units should be taken down to ground level before converting.
Side to Back Discharge Conversion
1. Remove screws to free the top and discharge panels. Set screws aside for later use. See Fig. 7.
2. Remove the access panel and set aside.
3. Lift the discharge panel from side of unit and rotate it to back using care not to damage blower wiring.
4. Check blower wire routing and connections for undue tension or contact with sheet metal edges. Re-route if necessary.
5. Check refrigerant tubing for contact with other compo­nents. Adjust if necessary.
6. Reinstall top panel using screws set aside in Step 1. NOTE: Location for some screws at bottom of discharge
panel may have to be changed.
7. Manually spin fan wheel to check for obstructions. Adjust for any obstruction found.
8. Replace access panel.
Back to Side Discharge Conversion
— Follow instructions above for Side to Back Discharge Conversion, noting the panels would be reversed.
Step 4 — Mount the Unit
HORIZONTAL UNIT (50PSH) — Horizontal units should be mounted using the factory-installed hangers. Proper attach­ment of hanging rods to building structure is critical for safety. See Fig. 1. Rod attachments must be able to support the weight of the unit. See Table 1 for unit operating weights.
VERTICAL UNITS (50PSV, PSD) — Vertical and downflow units are available in left or right return air configurations. See Fig. 3 and 4. Mount the unit (except 50PSD) on a vibration absorption pad slightly larger than the entire base to minimize vibration transmission. It is not necessary to mount the unit on the floor. See Fig. 9.
NOTE: Some codes require the use of a secondary drain pan under vertical units. Check local codes for more information.
Step 5 — Check Duct System — Size the duct sys-
tem to handle the design airflow quietly. NOTE: Depending on the unit, the fan wheel may have a ship-
ping support installed at the factory. This must be removed before operating unit.
SOUND ATTENUATION — To eliminate the transfer of vibration to the duct system, a flexible connector is recom­mended for both discharge and return air duct connections on metal duct systems. The supply and return plenums should in­clude internal duct liner of fiberglass or be made of duct board construction to maximize sound attenuation of the blower. Installing the WSHP unit to uninsulated ductwork in an uncon­ditioned space is not recommended since it will sweat and adversely affect the unit’s performance.
To reduce air noise, at least one 90-degree elbow could be included in the supply and return air ducts, provided system performance is not adversely impacted. The blower speed can also be changed in the field to reduce air noise or excessive air­flow, provided system performance is not adversely impacted.
EXISTING DUCT SYSTEM — If the unit is connected to existing ductwork, consider the following:
• Verify that the existing ducts have the proper capacity to
handle the unit airflow. If the ductwork is too small, install
larger ductwork.
• Check existing ductwork for leaks and repair as necessary.
NOTE: Local codes may require ventilation air to enter the
space for proper indoor air quality. Hard-duct ventilation
may be required for the ventilating air supply. If hard
ducted ventilation is not required, be sure that a proper air
path is provided for ventilation air to unit to meet ventila-
tion requirement of the space.
Step 6 — Install Condensate Drain
HORIZONTAL UNIT (50PSH) — Slope the unit toward the drain at quired pitch, install a condensate at the unit to pump conden­sate to building drain.
1
/4 in. See Fig. 10. If it is not possible to meet the re-
A50-7731ef
Fig. 9 — 50PSV Units Mounted With
Vibration Absorption Pad
1/4Ó Pitch for Drainage
Pitch Toward Drain
A50-6260
Drain Connection
Fig. 10 — Horizontal Unit Pitch
Horizontal units are not internally trapped, therefore an ex­ternal trap is necessary. Install each unit with its own individual trap and means to flush or blow out the condensate drain line. Do not install units with a common trap or vent. See Fig. 11 for typical condensate connections.
NOTE: Never use a pipe size smaller than the connection.
9
A50-7732
NOTE: Trap should be deep enough to offset maximum unit static difference. A 4-in. trap is recommended.
Fig. 11 — Trap Condensate Drain Connection
VERTICAL UNITS (50PSV, PSD) — Each unit uses a con­densate hose inside all cabinets as a trapping loop, therefore an external trap is not necessary. See Fig. 12.
Each unit must be installed with its own individual vent and means to flush or blow out the condensate drain line. Do not in­stall units with a common trap or vent.
3/4 Copper FPT/PVC
1/2
Water Connections
A50-6262
NOTE: Unit does not need to be sloped toward drain.
3/4 PVC Vent
Alternate Condensate Location
1/4 per foot slope to drain
1/2
Fig. 12 — Vertical Condensate Connection
VENTING — Install a vent in the condensate line of any application that may allow dirt or air to collect in the line. Con­sider the following:
• Always install a vent where an application requires a long
horizontal run.
• Always install a vent where large units are working against
higher external static pressure and to allow proper drainage
for multiple units connected to the same condensate main.
• Be sure to support the line where anticipated sagging from
the condensate or when “double trapping” may occur.
• If condensate pump is present on unit, be sure drain connec-
tions have a check valve to prevent back flow of condensate
into other units.
Step 7 — Pipe Connections — Depending on the
application, there are 3 types of WSHP piping systems to choose from: water loop, ground-water and ground loop. Refer to Piping Section of Carrier System Design Manual for addi­tional information.
All WSHP units use low temperature soldered female pipe thread fittings for water connections to prevent annealing and out-of-round leak problems which are typically associated with high temperature brazed connections. Refer to Table 1 for
connection sizes. When making piping connections, consider the following:
• Use a backup wrench when making screw connections to unit to prevent internal damage to piping.
• Insulation may be required on piping to avoid condensation in the case where fluid in loop piping operates at tempera­tures below dew point of adjacent air.
• Piping systems that contain steel pipes or fittings may be subject to galvanic corrosion. Dielectric fittings may be used to isolate the steel parts of the system to avoid galvanic corrosion.
WATER LOOP APPLICATIONS — Water loop applications usually include a number of units plumbed to a common pip­ing system. Maintenance to any of these units can introduce air into the piping system. Therefore, air elimination equipment comprises a major portion of the mechanical room plumbing.
The flow rate is usually set between 2.25 and 3.5 gpm per
ton of cooling capacity. For proper maintenance and servicing, pressure-temperature (P/T) ports are necessary for temperature and flow verification.
Cooling tower/boiler systems typically utilize a common
loop maintained at 60 to 95 F. The use of a closed circuit evap­orative cooling tower with a secondary heat exchange between the tower and the water loop is recommended. If an open type cooling tower is used continuously, chemical treatment and fil­tering will be necessary.
In addition to complying with any applicable codes, consid-
er the following for system piping:
• Piping systems using water temperatures below 50 F require
1
/2-in. closed cell insulation on all piping surfaces to
eliminate condensation.
• Avoid all plastic to metal threaded fittings due to the poten­tial to leak. Use a flange fitted substitute.
• Teflon tape thread sealant is recommended to minimize internal fouling of the heat exchanger.
• Use backup wrench. Do not overtighten connections.
• Route piping to avoid service access areas to unit.
• Flush the piping system prior to operation to remove dirt and foreign materials from the system.
GROUND-WATER APPLICATIONS — Typical ground­water piping is shown in Fig. 13. In addition to complying with any applicable codes, consider the following for sys­tem piping:
• Install shut-off valves for servicing.
• Install pressure-temperature plugs to measure flow and temperature.
• Connect boiler drains and other valves using a “T” connec­tor to allow acid flushing for the heat exchanger.
• Do not overtighten connections.
• Route piping to avoid service access areas to unit.
• Use PVC SCH80 or copper piping material.
NOTE: PVC SCH40 should not be used due to system high pressure and temperature extremes.
Water Supply and Quantity
— Check water supply. Water supply should be plentiful and of good quality. See Table 2 for water quality guidelines.
IMPORTANT: Failure to comply with the above required water quality and quantity limitations and the closed­system application design requirements may cause damage to the tube-in-tube heat exchanger. This damage is not the responsibility of the manufacturer.
10
Table 2 — Water Quality Guidelines
CONDITION
Scaling Potential — Primary Measurement
Above the given limits, scaling is likely to occur. Scaling indexes should be calculated using the limits below.
pH/Calcium Hardness Method
Index Limits for Probable Scaling Situations (Operation outside these limits is not recommended.)
Scaling indexes should be calculated at 150 F for direct use and HWG applications, and at 90 F for indirect HX use. A monitoring plan should be implemented.
Ryznar Stability Index
Langelier Saturation Index
Iron Fouling
Iron Fe2+ (Ferrous) (Bacterial Iron Potential)
Iron Fouling
Corrosion Prevention††
pH
Hydrogen Sulfide (H2S)
Ammonia Ion as Hydroxide, Chloride, Nitrate and Sulfate Compounds
Maximum Chloride Levels Maximum allowable at maximum water temperature.
Erosion and Clogging
Particulate Size and Erosion
Brackish
LEGEND
HWG — Hot Water Generator HX Heat Exchanger N/A — Design Limits Not Applicable Considering Recirculating
NR Application Not Recommended SS Stainless Steel
*Heat exchanger materials considered are copper, cupronickel, 304 SS
(stainless steel), 316 SS, titanium.
†Closed recirculating system is identified by a closed pressurized piping
system.
**Recirculating open wells should obser ve the open recirculating design
considerations.
Potable Water
HX
MATERIAL*
All N/A pH < 7.5 and Ca Hardness, <100 ppm
All N/A
All N/A
All N/A
All N/A
All
All N/A
All N/A
Copper N/A
Cupronickel N/A <150 ppm NR NR
304 SS N/A <400 ppm <250 ppm <150 ppm 316 SS N/A <1000 ppm <550 ppm <375 ppm
Titanium N/A >1000 ppm >550 ppm >375 ppm
All
All N/A
CLOSED
RECIRCULATING†
Monitor/treat as needed.
<10 ppm of particles and a maximum velocity of 6 fps.
6 - 8.5
Filtered for maximum
800 micron size.
OPEN LOOP AND RECIRCULATING WELL**
6.0 - 7.5
If >7.5 minimize steel pipe use.
–0.5 to +0.5
Based upon 150 F HWG and direct well, 85 F indirect well HX.
If Fe2+ (ferrous) >0.2 ppm with pH 6 - 8, O2<5 ppm check for iron bacteria.
Minimize steel pipe below 7 and no open tanks with pH <8.
At H2S>0.2 ppm, avoid use of copper and cupronickel piping of HXs.
Copper alloy (bronze or brass) cast components are okay to <0.5 ppm.
50 F (10 C) 75 F (24 C) 100 F (38 C)
<20 ppm NR NR
<10 ppm (<1 ppm “sandfree for reinjection) of par ticles and a maximum velocity of 6 fps. Filtered for maximum 800 micron size. Any particulate that is not removed can potentially clog components.
Use cupronickel heat exchanger when concentrations of calcium or sodium chloride are greater than 125 ppm are present. (Seawater is approximately 25,000 ppm.)
††If the concentration of these corrosives exceeds the maximum allow-
able level, then the potential for serious corrosion problems exists. Sulfides in the water quickly oxidize when exposed to air, requiring that no agitation occur as the sample is taken. Unless tested immediately at the site, the sample will require stabilization with a few drops of one Molar zinc acetate solution, allowing accurate sulfide determination up to 24 hours after sampling. A low pH and high alkalinity cause system problems, even when both values are within ranges shown. The term pH refers to the acidity, basicity, or neutrality of the water supply. Below 7.0, the water is considered to be acidic. Above 7.0, water is considered to be basic. Neutral water contains a pH of 7.0. To convert ppm to grains per gallon, divide by 17. Hardness in mg/l is equivalent to ppm.
If <–0.5 minimize steel pipe use.
<0.2 ppm (Ferrous)
<0.5 ppm of Oxygen
Above this level deposition will occur.
6 - 8.5
<0.5 ppm
Rotten egg smell appears at 0.5 ppm level.
<0.5 ppm
11
In all applications, the quality of the water circulated through the heat exchanger must fall within the ranges listed in the Water Quality Guidelines table. Consult a local water firm, independent testing facility, or local water authority for specific recommendations to maintain water quality within the pub­lished limits.
GROUND-LOOP APPLICATIONS — Temperatures be­tween 25 and 110 F and a cooling capacity of 2.25 to 3 gpm of flow per ton is recommended. In addition to complying with any applicable codes, consider the following for system piping:
• Limit piping materials to only polyethylene fusion in the
buried sections of the loop.
• Do not use galvanized or steel fittings at any time due to
corrosion.
• Avoid all plastic to metal threaded fittings due to the poten-
tial to leak. Use a flange fitted substitute.
• Do not overtighten connections.
• Route piping to avoid service access areas to unit.
• Use pressure-temperature (P/T) plugs to measure flow of
pressure drop. INSTALLATION OF SUPPLY AND RETURN HOSE
KIT — Follow these piping guidelines.
1. Install a drain valve at the base of each supply and return riser to facilitate system flushing.
2. Install shutoff/balancing valves and unions at each unit to permit unit removal for servicing.
3. Place strainers at the inlet of each system circulating pump.
4. Select the proper hose length to allow slack between con­nection points. Hoses may vary in length by +2% to –4% under pressure.
5. Refer to Table 3. Do not exceed the minimum bend radius for the hose selected. Exceeding the minimum bend radi­us may cause the hose to collapse, which reduces water flow rate. Install an angle adapter to avoid sharp bends in the hose when the radius falls below the required minimum.
NOTE: Piping must comply with all applicable codes.
Table 3 — Metal Hose Minimum Bend Radii
HOSE DIAMETER (in.) MINIMUM BEND RADII (in.)
1
/
2
3
/
4
15
21/
2
4
1
/
2
Insulation is not required on loop water piping except where the piping runs through unheated areas or outside the building or when the loop water temperature is below the minimum ex­pected dew point of the pipe ambient. Insulation is required if loop water temperature drops below the dew point.
IMPORTANT: Do not bend or kink supply lines or hoses.
Pipe joint compound is not necessary when Teflon threaded tape is pre-applied to hose assemblies or when flared-end connections are used. If pipe joint compound is preferred, use compound only in small amounts on the male pipe threads of the fitting adapters. Prevent sealant from reaching the flared surfaces of the joint.
NOTE: When anti-freeze is used in the loop, assure that it is compatible with Teflon tape or pipe joint compound employed.
Maximum allowable torque for brass fittings is 30 ft-lb. If a torque wrench is not available, tighten finger-tight plus one quarter turn. Tighten steel fittings as necessary.
Water Control Valve (field-installed accessory)
Flow Regulator (field-installed accessory)
Boiler Drains (field-installed)
Pressure
Ta nk
Water Out
Shut-Off Valve (field-installed accessory)
Strainer (field-installed accessory) (16 to 20 mesh recommended for filter sediment)
Fig. 13 — Typical Ground-Water Piping Installation
A50-7733
Water In From Pump
12
Optional pressure-rated hose assemblies designed specifi­cally for use with Carrier units are available. Similar hoses can be obtained from alternate suppliers. Supply and return hoses are fitted with swivel-joint fittings at one end to prevent kink­ing during installation.
CAUTION
Backup wrench is required when tightening water connec­tions to prevent water line damage. Failure to use a backup wrench could result in equipment damage.
Refer to Fig. 14 for an illustration of a supply/return hose kit. Male adapters secure hose assemblies to the unit and risers. Install hose assemblies properly and check them regularly to avoid system failure and reduced service life.
Step 8 — Wire Field Power Supply
WARNING
To avoid possible injury or death due to electrical shock, open the power supply disconnect switch and secure it in an open position during installation.
CAUTION
Use only copper conductors for field-installed electrical wiring. Unit terminals are not designed to accept other types of conductors. Failure to use copper conductors could result in equipment damage.
All field-installed wiring, including the electrical ground, MUST comply with the National Electrical Code (NEC) as well as applicable local codes. In addition, all field wiring must conform to the Class II temperature limitations described in the NEC.
Refer to unit wiring diagrams Fig. 15-25 for a schematic of the field connections, which must be made by the installing (or electrical) contractor. Refer to Tables 4-6 for fuse sizes.
Consult the unit wiring diagram located on the inside of the compressor access panel to ensure proper electrical hookup. The installing (or electrical) contractor must make the field connections when using field-supplied disconnect.
Operating voltage must be the same voltage and phase as shown in electrical data shown in Tables 4-6.
Make all final electrical connections with a length of flexi­ble conduit to minimize vibration and sound transmission to the building.
POWER CONNECTION — Make line voltage connection by connecting the incoming line voltage wires to the line side of the compressor contactor terminal as shown in Fig. 26. See Tables 4-6 for amperage ratings to provide cor­rect wire and maximum overcurrent protection sizing.
SUPPLY VOLTAGE — Operating voltage to unit must be within voltage range indicated on unit nameplate.
On 3-phase units, voltages under load between phases must be balanced within 2%. Use the following formula to deter­mine the percentage voltage imbalance:
% Voltage Imbalance
= 100 x
Example: Supply voltage is 460-3-60.
Determine maximum deviation from average voltage: (AB) 457 – 452 = 5 v
(BC) 464 – 457 = 7 v (AC) 457 – 455 = 2 v
Maximum deviation is 7 v. Determine percent voltage imbalance.
% Voltage Imbalance = 100 x
below the maximum allowable 2%.
imbalance constitutes abuse and may cause damage to electri­cal components.
NOTE: If more than 2% voltage imbalance is present, contact your local electric utility.
208-VOLT OPERATION — All 208-230 volt units are factory wired for 208 volts. The transformers may be switched to 230-volt operation by switching the red (208 volt) wire with the orange (230 volt) wire at the L1 terminal.
460-VOLT OPERATION — Units using 460-v and an ECM (electronically commutated motor) fan motor, modulat­ing HWR, and/or internal secondary pump will require a neutral wire from the supply side in order to feed accessory with 265-v.
max voltage deviation from average voltage
average voltage
AB = 452 volts BC = 464 volts AC = 455 volts
Average Voltage =
= 1.53%
This amount of phase imbalance is satisfactory as it is
Operation on improper line voltage or excessive phase
452 + 464 + 455
1371
=
3
= 457
7
457
3
A50-7734
Swivel Brass
Rib Crimped
Fitting
Length
(2 ft Length Standard)
Fig. 14 — Supply/Return Hose Kit
13
Brass Fitting
MPT
LEGEND
AL Alarm Relay Contacts ASTAT — Aquastat BR Blower Relay CB Circuit Breaker CC Compressor Contactor CO Condensate Overflow Sensor COMPR — Compressor DTS Discharge Temp Switch FP1 Water Coil Freeze Protection Sensor FP2 Air Coil Freeze Protection Sensor HP High-Pressure Switch HWG Hot Water Generator JW Jumper Wire LOC Loss of Charge Pressure Switch MV Motorized Valve NEC National Electrical Code PSC Permanent Split Capacitor P1 Field Wiring Terminal Block RVS Reversing Valve Solenoid
*Optional.
NOTES:
1. Compressor and blower motor thermally protected internally.
2. All wiring to the unit must comply with NEC and local codes.
3. 208/230 v transformer will be connected for 208 v operation. For 230 v operation, disconnect RED lead at L1 and attach ORANGE lead to L1. Insulate open end of RED lead. Transformer is energy limiting or may have circuit breaker.
4. FP1 thermistor provides freeze protection for water. When using antifreeze solutions, cut JW3 jumper.
5. Check installation wiring information for specific thermostat hookup. Refer to thermostat installation instructions for wiring to the unit. Thermostat wiring must be “Class 1 and voltage rating equal to or greater than unit supply voltage.
6. 24-v alarm signal shown. For dry alarm contact, cut JW1 jumper and dry contact will be available between AL1 and AL2.
7. Transformer secondary ground via Complete C board standoffs and screws to control box. (Ground available from top two standoffs as shown.)
8. Aquastat is supplied with unit and must be wired in series with the hot leg to the pump. Aquastat is rated for voltage up to 277 v.
9. Fan motors factory wired for medium speed. For high and low speed remove BLU wire from fan motor speed tap ‘M’ and connect to ‘H’ for high or ‘L’ for low.
TRANS — Transformer UPS Unit Performance Sentinel
Solenoid Coil
Factory Low Voltage Wiring Factory Line Voltage Wiring Field Low Voltage Wiring Field Line Voltage Wiring Printed Circuit Trace Optional Wiring
Relay/Contactor Coil
Thermistor
Condensate Pan
Circuit Breaker
COMPLETE C CONTROLLER FAULT CODES
DESCRIPTION OF OPERATION LED ALARM RELAY
Normal Mode ON Open
Normal Mode with UPS Warning ON
Complete C is Non-Functional OFF Open Fault Retry Slow Flash Open Lockout Fast Flash Closed
Over/Under Voltage Shutdown Slow Flash
Test Mode-No Fault in Memory Flashing Code 1 Cycling Code 1 Test Mode-HP Fault in Memory Flashing Code 2 Cycling Code 2 Test Mode-LP Fault in Memory Flashing Code 3 Cycling Code 3 Test Mode-FP1 Fault in Memory Flashing Code 4 Cycling Code 4 Test Mode-FP2 Fault in Memory Flashing Code 5 Cycling Code 5 Test Mode-CO Fault in Memory Flashing Code 6 Cycling Code 6 Test Mode-Over/Under Shutdown
in Memory Test Mode-UPS in Memory Flashing Code 8 Cycling Code 8 Swapped FP1/FP2 Lockout Flashing Code 9 Cycling Code 9
Flashing Code 7 Cycling Code 7
Relay Contacts - N.C.
Relay Contacts - N.O.
Capacitor
Temperature Switch
Low Pressure Switch
High Pressure Switch
Wire Nut
Splice Cap
G
LED
Cycle (Closed 5 Sec.
Open 25 Sec.)
(Closed After 15 Min.)
Open
Fig. 15 — Units with Complete C Controller, Single-Phase
14
AL Alarm Relay Contacts ASTAT Aquastat BM Blower Motor BMC Blower Motor Capacitor BR Blower Relay CB Circuit Breaker CC Compressor Contactor CO Condensate Overflow Sensor COMPR — Compressor DTS Discharge Temp Switch FP1 Water Coil Freeze Protection Sensor FP2 Air Coil Freeze Protection Sensor HP High-Pressure Switch HWG Hot Water Generator JW Jumper Wire LOC Loss of Charge Pressure Switch MV Motorized Valve NEC National Electric Code
*Optional.
NOTES:
1. Compressor and blower motor thermally protected inter nally.
2. All wiring to the unit must comply with NEC and local codes.
3. Transformer is wired to 460 v (BLK/RED) lead for 460/60/3 units, 575 v (GRY) lead for 575/60/3. Transformer is energy limiting or may have circuit breaker.
4. FP1 ther mistor provides freeze protection for water. When using anti­freeze solutions, cut JW3 jumper.
5. Check installation wiring information for specific thermostat hookup. Refer to thermostat installation instructions for wiring to the unit. Thermostat wiring must be “Class 1 and voltage rating equal to or greater than unit supply voltage.
6. 24-v alar m signal shown. For dry alarm contact, cut JW4 jumper and dry contact will be available between AL1 and AL2.
7. Transformer secondary ground via Deluxe D board standoffs and screws to control box. (Ground available from top two standoffs as shown.)
8. Aquastat is supplied with unit and must be wired in series with the hot leg to the pump. Aquastat is rated for voltage up to 277 v.
9. Blower motor is factory wired for high and low speeds. No other com­bination is available.
10. The 460-v units using an ECM (electronically commutated motor) fan motor, modulating HWR, and/or an internal secondary pump will require a neutral wire from the supply side in order to feed the acces­sory with 265-v.
TABLE 1 WIRE NUMBER
Blower Speeds
Factory
HI + MED
HI + LOW
MED + LOW
12345
BM(H) to
BM(H) to
BM(H) to
BR2(6)
BR2(6)
BR2(3)
BM(R) to
BR2(3)
BM(R) to
BR2(3)
BM(R) to
BR2(3)
BM(M) to
BR2(7)
Not Used
BM(M) to
BR2(6)
Not Used
BM(L) to
BR2(7)
BM(L) to
BR2(7)
BR2(6) to
BR2(4)
BR2(6) to
BR2(4)
BR2(2) to
BR2(4)
LEGEND
P1 Field Wiring Terminal Block RVS Reversing Valve Solenoid TRANS — Transformer
Normal Mode ON OFF Note 2 Open Deluxe D is Non-Functional OFF OFF OFF Open Test Mode ON Note 2 Cycle (Note 3) Night Setback Flashing Code 2 Note 2 — Emergency Shut Down Flashing Code 3 Note 2 — Invalid Thermostat Inputs Flashing Code 4 Note 2 — No Fault in Memory ON OFF Flashing Code 1 Open
HP Fault/(Lockout) Note 1
LP Fault/(Lockout) Note 1
FP1 Fault/(Lockout) Note 1
FP2 Fault/(Lockout) Note 1
CC Fault/(Lockout) Note 1
Over-Under Voltage Slow Flash OFF Flashing Code 7 Open (Note 4) Normal Mode with UPS ON OFF Flashing Code 8 Cycle (Note 5) Swapped FP1/FP2 Lockout Fast Flash OFF Flashing Code 9 Closed
NOTES:
1. Status LED (GREEN) Slow Flash - Controller In - Fault Retry Mode. Fast Flash - Controller in Lock­out Mode. Slow Flash = 1 Flash per every 2 seconds. Fast Flash = 2 Flashes per every 1 second.
2. Fault LED (RED) flashes a code representing last fault in memory. If no fault in memory code 1 is flashed.
3. Cycles appropriate code, by cycling alarm relay in the same sequence as fault LED.
4. Alarm relay closes after 15 minutes.
5. Alarm relay cycles. Closed for 5 seconds and open for 25 seconds.
Factory Low Voltage Wiring Factory Line Voltage Wiring Field Low Voltage Wiring Field Line Voltage Wiring Printed Circuit Trace Optional Wiring
Relay/Contactor Coil
Thermistor
Condensate Pan
Circuit Breaker
OPERATION
DELUXE D CONTROLLER FAULT CODES
STATUS LED
(GREEN)
Slow Flash/
(Fast Flash)
Slow Flash/
(Fast Flash)
Slow Flash/
(Fast Flash)
Slow Flash/
(Fast Flash)
Slow Flash/
(Fast Flash)
TEST LED (YELLOW)
OFF Flashing Code 2 Open/(Closed)
OFF Flashing Code 3 Open/(Closed)
OFF Flashing Code 4 Open/(Closed)
OFF Flashing Code 5 Open/(Closed)
OFF Flashing Code 6 Open/(Closed)
Ground
Solenoid Coil
Relay Contacts - N.C.
Relay Contacts - N.O.
Capacitor
Temperature Switch
Low Pressure Switch
High Pressure Switch
Wire Nut
Splice Cap
G
LED
FAULT LED
(RED)
ALARM
RELAY
Fig. 16 — Units with Deluxe D Controller, Three-Phase (460/575 V)
15
AL Alarm Relay Contacts ASTAT — Aquastat BM Blower Motor BR Blower Relay CB Circuit Breaker CC Compressor Contactor CO Condensate Overflow Sensor COMPR — Compressor DTS Discharge Temp Switch ECM Electronically Commutated Motor FP1 Water Coil Freeze Protection Sensor FP2 Air Coil Freeze Protection Sensor HP High-Pressure Switch HWG Hot Water Generator JW Jumper Wire LOC Loss of Charge Pressure Switch LWT Leaving Water Temperature MV Motorized Valve NEC National Electric Code P1 Field Wiring Terminal Block
*Optional.
LEGEND
RVS Reversing Valve Solenoid TRANS — Transformer UPS Unit Performance Sentinel
Factory Low Voltage Wiring Factory Line Voltage Wiring Field Low Voltage Wiring Field Line Voltage Wiring Printed Circuit Trace Optional Wiring
Relay/Contactor Coil
Thermistor
Condensate Pan
Circuit Breaker
Ground
Solenoid Coil
Relay Contacts - N.C.
Relay Contacts - N.O.
Capacitor
Temperature Switch
Low Pressure Switch
High Pressure Switch
Wire Nut
Splice Cap
G
LED
NOTES:
1. Compressor and blower motor thermally protected internally.
2. All wiring to the unit must comply with NEC and local codes.
3. 208/230 v transformer will be connected for 208 v operation. For 230 v operation, disconnect RED lead at L1 and attach ORANGE lead to L1. Insulate open end of RED lead. Transformer is energy limiting or may have circuit breaker.
4. FP1 thermistor provides freeze protection for water. When using antifreeze solutions, cut JW3 jumper.
5. Check installation wiring information for specific thermostat hookup. Refer to thermostat installation instructions for wiring to the unit. Thermostat wiring must be “Class 1 and voltage rating equal to or greater than unit supply voltage.
6. 24-v alarm signal shown. For dry alarm contact, cut JW1 jumper and dry contact will be available between AL1 and AL2.
7. Transformer secondary ground via Complete C board standoffs and screws to control box. (Ground available from top two standoffs as shown.)
8. Aquastat is supplied with unit and must be wired in series with the hot leg to the pump. Aquastat is rated for voltage up to 277 v.
Fig. 17 — Units with Complete C ECM Blower, Three-Phase (208/230 V)
COMPLETE C CONTROLLER FAULT CODES
DESCRIPTION OF OPERATION LED ALARM RELAY
Normal Mode ON Open
Normal Mode with UPS Warning ON
Complete C is Non-Functional OFF Open Fault Retry Slow Flash Open Lockout Fast Flash Closed
Over/Under Voltage Shutdown Slow Flash
Test Mode-No Fault in Memory Flashing Code 1 Cycling Code 1 Test Mode-HP Fault in Memory Flashing Code 2 Cycling Code 2 Test Mode-LP Fault in Memory Flashing Code 3 Cycling Code 3 Test Mode-FP1 Fault in Memory Flashing Code 4 Cycling Code 4 Test Mode-FP2 Fault in Memory Flashing Code 5 Cycling Code 5 Test Mode-CO Fault in Memory Flashing Code 6 Cycling Code 6 Test Mode-Over/Under Shutdown
in Memory Test Mode-UPS in Memory Flashing Code 8 Cycling Code 8 Swapped FP1/FP2 Lockout Flashing Code 9 Cycling Code 9
Flashing Code 7 Cycling Code 7
Cycle (Closed 5 Sec.
Open 25 Sec.)
Open
(Closed After 15 Min.)
16
LEGEND
a50-8363
Complete C
AL Alarm Relay Contacts ASTAT — Aquastat BM Blower Motor BMC Blower Motor Capacitor BR Blower Relay CB Circuit Breaker CC Compressor Contactor CO Sensor, Condensate Overflow DTS Discharge Temperature Switch ECM Electronically Commutated Motor FP1 Sensor, Water Coil Freeze Protection FP2 Sensor, Air Coil Freeze Protection HP High-Pressure Switch HPWS High-Pressure Water Switch HWG Hot Water Generator JW1 Clippable Field Selection Jumper LOC Loss of Charge Pressure Switch LON Local Operating Network MV Motorized Valve MVES Motorized Valve End Switch *Optional Wiring.
NOTES:
1. Compressor and blower motor thermally protected internally.
2. All wiring to the unit must comply with NEC and local codes.
3. Transformer is wired to 460 v (BLK/RED) lead for 460/3/60 units. Transformer is energy limiting or may have circuit breaker.
4. FP1 thermistor provides freeze protection for water. When using antifreeze solutions, cut JW3 jumper.
5. Typical thermostat wiring shown. Refer to thermostat installa­tion instructions for wiring to the unit. Thermostat wiring must be Class 1 and voltage rating equal to or greater than unit sup­ply voltage.
6. Factory cut JW1 jumper. Dry contact will be available between AL1 and AL2.
7. Transformer secondary ground via Complete C board standoffs and screws to control box. (Ground available from top two standoffs as shown.)
NEC National Electrical Code P1 Field Wiring Terminal Block RVS Reversing Valve Solenoid TRANS — Transformer
Wire Nut
Relay Contacts - N.C.
Field Line Voltage Wiring Field Low Voltage Wiring Printed Circuit Trace Optional Wiring
Relay/Contactor Coil
Condensate Pan
Solenoid Coil
Temperature Switch
Thermistor
Ground
8. Aquastat is supplied with unit and must be wired in series with the hot leg to the pump. Aquastat is rated for voltages up to 277-v.
9. Optional LON wires. Only connect if LON connection is desired at the wall sensor.
10. Fan motors are factory wired for medium speed. For high or low speed, remove BLU wire from fan motor speed tap “M and connect to “H for high speed or “L” for low speed.
11. For low speed, remove BLK wire from BR “6 and replace with RED. Connect BLK and BRN wires together.
12. For blower motors with leads. For medium or low speed, disconnect BLK wire from BR “6. Connect BLK and ORG/PUR wire together. Connect RED for low or BLU for medium to BR “6”.
13. The 460-v units using an ECM (electronically commutated motor) fan motor, modulating HWR (hot water reheat), and/or an internal secondary pump will require a neutral wire from the supply side in order to feed the accessory with 265-v.
Relay Contacts - N.O.
Low Pressure Switch
High Pressure Switch
Splice Cap
Circuit Breaker
Fig 18 — Units with ECM, Complete C and LON Controller (460 V)
17
LEGEND
Deluxe D
HP
LOC
SEE NOTE 4
FP1
FP2
RVS
CO
a50-8364
AL Alarm Relay Contacts ASTAT — Aquastat BM Blower Motor BMC Blower Motor Capacitor BR Blower Relay CB Circuit Breaker CC Compressor Contactor CO Sensor, Condensate Overflow DTS Discharge Temperature Switch ECM Electronically Commutated Motor FP1 Sensor, Water Coil Freeze Protection FP2 Sensor, Air Coil Freeze Protection HP High-Pressure Switch HPWS High-Pressure Water Switch HWG Hot Water Generator JW1 Clippable Field Selection Jumper LOC Loss of Charge Pressure Switch LON Local Operating Network MV Motorized Valve NEC National Electrical Code
P1 Field Wiring Terminal Block RVS Reversing Valve Solenoid TRANS — Transformer
*Optional Wiring.
NOTES:
1. Compressor and blower motor thermally protected internally.
2. All wiring to the unit must comply with NEC and local codes.
3. Transformer is wired to 460 v (BLK/RED) lead for 460/3/60 units. Transformer is energy limiting or may have circuit breaker.
4. FP1 thermistor provides freeze protection for water. When using antifreeze solutions, cut JW3 jumper.
5. Typical thermostat wiring shown. Refer to thermostat installa­tion instructions for wiring to the unit. Thermostat wiring must be Class 1 and voltage rating equal to or greater than unit sup­ply voltage.
6. Factory cut JW1 jumper. Dry contact will be available between AL1 and AL2.
7. Transformer secondary ground via Deluxe D board standoffs and screws to control box. (Ground available from top two standoffs as shown.)
Wire Nut
Relay Contacts - N.C. Field Line Voltage Wiring Field Low Voltage Wiring Printed Circuit Trace Optional Wiring
Relay/Contactor Coil
Relay Contacts - N.O.
Low Pressure Switch
High Pressure Switch
Splice Cap
Circuit Breaker
Condensate Pan
Solenoid Coil
Temperature Switch
Thermistor
Ground
8. Aquastat is supplied with unit and must be wired in series with the hot leg to the pump. Aquastat is rated for voltages up to 277-v.
9. Blower motor is factory wired for medium and high speeds. For any other combination of speeds, at the motor attach the BLK wire to the higher of the two desired speed taps and the BLU wire to the lower of the two desired speed taps.
10. Optional LON wires. Only connect if LON connection is desired at the wall sensor.
11. Blower motor is factory wired for high and low speeds. No other combination is available.
12. The 460-v units using an ECM (electronically commutated motor) fan motor, modulating HWR (hot water reheat), and/or an internal secondary pump will require a neutral wire from the supply side in order to feed the accessory with 265-v.
Fig 19 — Units with ECM, Deluxe D and LON Controller (460 V)
18
LEGEND
a50-8232
AL Alarm Relay Contacts ASTAT Aquastat BM Blower Motor BR Blower Relay CB Circuit Breaker CC Compressor Contactor CO Sensor, Condensate Overflow CR Cooling Relay DTS Discharge Temp Switch ECM Electronically Commuted Motor FP1 Sensor, Water Coil Freeze Protection FP2 Sensor, Air Coil Freeze Protection HP High Pressure Switch HPWS High Pressure Water Switch HWG Hot Water Generator JW Jumper Wire LOC Loss of Charge Pressure Switch LWT Leaving Water Temperature MV Motorized Valve MVES Motorized Valve End Switch P1 Field Wiring Terminal Block
RVS Reversing Valve Solenoid SAT Saturated Air Temperature TRANS — Transformer UPS Unit Performance Sentinel
*Optional Wiring.
NOTES:
1. Compressor and blower motor thermally protected internally.
2. All wiring to the unit must comply with NEC and local codes.
3. 208-240 60 Hz units are wired for 208v operation. Transformer is energy limiting or may have circuit breaker.
4. FP1 thermistor provides low temperature protection for water. When using antifreeze solutions, cut JW3 jumper.
5. Refer to multiple protocol controller (MPC), LON, or TSTAT Installation, Application, and Operation Manual for control wiring to the wire from PremierLink controller to “Y Complete C when motorized valve is not used. Thermostat wiring must be “Class 1 and voltage rating equal to or greater than unit supply voltage.
6. 24v alarm signal shown. For dry contact, cut JW1 jumper and dry con­tact will be available between AL1 and AL2.
7. Transformer secondary ground via green wire with yellow stripe from “C terminal to control box.
8. Aquastat is supplied with unit and must be wired in series with the hot leg to the pump. Aquastat is rated for voltages up to 277v.
Thermistor
Ground
Field Line Voltage Wiring Field Low Voltage Wiring Field Line Voltage Wiring Field Low Voltage Wiring Printed Circuit Trace Optional Wiring
Relay/Contactor Coil
Condensate Pan
Solenoid Coil
Temperature Switch
COMPLETE C CONTROLLER FAULT CODES
DESCRIPTION OF OPERATION LED ALARM RELAY
Normal Mode ON Open
Normal Mode with UPS Warning ON
Complete C is Non-Functional OFF Open Fault Retry Slow Flash Open Lockout Fast Flash Closed Over/Under Voltage Shutdown Slow Flash Open (Closed After 15 Min.) Test Mode-No Fault in Memory Flashing Code 1 Cycling Code 1 Test Mode-HP Fault in Memory Flashing Code 2 Cycling Code 2 Test Mode-LP Fault in Memory Flashing Code 3 Cycling Code 3 Test Mode-FP1 Fault in Memory Flashing Code 4 Cycling Code 4 Test Mode-FP2 Fault in Memory Flashing Code 5 Cycling Code 5 Test Mode-CO Fault in Memory Flashing Code 6 Cycling Code 6 Test Mode-Over/Under Shutdown
in Memory Test Mode-UPS in Memory Flashing Code 8 Cycling Code 8 Swapped FP1/FP2 Lockout Flashing Code 9 Cycling Code 9
Flashing Code 7 Cycling Code 7
Wire Nut
Relay Contacts - N.C.
Relay Contacts - N.O.
Low Pressure Switch
High Pressure Switch
Splice Cap
Circuit Breaker
Capacitor
G
LED
Cycle (Closed 5 Sec.
Open 25 Sec.)
Fig. 20 — Units with Complete C and Premierlink™ Controller, Single-Phase (208/230 V)
19
Fig. 21 — Units with Complete C and WSHP Open Multiple Protocol Controls
WHSP-OPEN
A50-8355
20
LEGEND
BM — Blower Motor
BR Blower Relay
CO Condensate Overflow
LWT — Leaving Water Temperature
N.C. — Normally Closed
OAD — Outside Air Damper
OCC — Occupancy Input Contact
RH Relative Humidity
SAT — Supply Air Temperature
SPT — Space Temperature
Fig. 22 — Units with Deluxe D and WSHP Open Multiple Protocol Controls
WSHP-OPEN
A50-8354
21
LEGEND
BM — Blower Motor
CO Condensate Overflow
LWT — Leaving Water Temperature
N.C. — Normally Closed
OAD — Outside Air Damper
OCC — Occupancy Input Contact
RH Relative Humidity
SAT — Supply Air Temperature
SPT — Space Temperature
A50-8356
22
WSHP-OPEN
LEGEND
CO Condensate Overflow
LWT — Leaving Water Temperature
N.C. — Normally Closed
OAD — Outside Air Damper
OCC — Occupancy Input Contact
RH Relative Humidity
SAT — Supply Air Temperature
Fig. 23 — Units with Complete C, ECM and WSHP Open Multiple Protocol Controls
SPT — Space Temperature
A50-8353
23
WSHP-OPEN
LEGEND
CO Condensate Overflow
LWT — Leaving Water Temperature
N.C. — Normally Closed
OAD — Outside Air Damper
OCC — Occupancy Input Contact
RH Relative Humidity
SAT — Supply Air Temperature
Fig. 24 — Units with Deluxe D, ECM and WSHP Open Multiple Protocol Controls
SPT — Space Temperature
CHANNEL
DESIGNATION
CONNECTION
PIN NUMBERS
Factory Wiring
Field Wiring
LEGEND
N/A AO (0-10Vdc/2 - 10Vdc) J2 4 and 5* Analog Output 1
N/A BO Relay (24VAC, 1A) J1, 4* Binar y Output 1 (G)
Outside Air Damper N/A AO (0-10Vdc/2 - 10Vdc) J22 1 and 2* Analog Output 2
located at the end of network
Gnd
N/A BO Relay (24VAC, 1A) J1, 5* Binary Output 2
Rnet+
Rnet-
+12V
Supply Fan On/Low Speed
(3 Speed Only)
Auxiliary Heat or 2-Position Water Loop
Economizer
Reversing Valve (B or O Operation) N/A BO Relay (24VAC, 1A) J1, 6* Binary Output 3 (RV)
Compressor 2nd Stage N/A BO Relay (24VAC, 1A) J1, 7 Binary Output 4 (Y2)
Compressor 1st Stage N/A BO Relay (24VAC, 1A) J1, 8 Binary Output 5 (Y1)
Dehumidification Relay N/A BO Relay (24VAC, 1A) J11, 7 and 8 (NO) Binary Output 6
*These inputs are configurable.
Fan Speed Medium/Low (3 Speed Only) N/A BO Relay (24VAC, 1A) J11, 5 and 6 (NO)* Binary Output 7
Fan Speed High/Low (3 Speed Only) N/A BO Relay (24VAC, 1A) J11, 2 and 3 (NO)* Binary Output 8
Fig. 25 — WSHP Open Control
segment only.
with at least two #6 x 1 in. self-tapping screws. Allow adequate clearance for wiring.
sors requiring a separate isolated 24 vac power source will not utilize WSHP termi-
nals J4-1, or 4.
1. Mount the water source heat pump controller in the equipment controls enclosure
2. Verify sensor power and wiring requirements prior to making any terminations. Sen-
AI Analog Input
AO Analog Output
BI Binary Input
-Gnd
+ 24vac
(DI-3/Dry Contact)
Aux Heat (DO-2)
Fan (DO-1) (Fan On or Low Speed)
Condensate
Overflow Switch
PINK
RED
BRN
GRN
WHT
NOTES:
BO Binar y Output
SPT Space Temperature
a50-8380
(If not installed, it must be connected to DO-5)
Comp Status (DI-5)
LWT (Input 6)
SAT (LAT) (Input 7)
Comp #1 (DO-5)
Comp #2 (DO-4)
Reversing Valve (DO-3)
RED
BLU
YLW
ORN
WTR. Loop Econ. (AO 1)
AO1 – Aux Reheat or Cond.
VIO
BRN
ORN
PINK
PINK
BLU
1
2 3
7
4
5
67
8
J5
10
OA DAMPER (AO-2)
DEHUMIDIFY OUTPUT CONTACT (DO-6) (FACTORY OPTION)
J11
12
J22
WSHP Open Inputs and Outputs Table
SPT PLUS Sensor
Shown
INPUT/OUTPUT TYPE PART NUMBERS TYPE OF I/O
Inputs
Space Temperature Sensor SPS, SPPL, SPP Communicating J13, 1 - 4 Local Access Port
Space Relative Humidity 33ZCSENSRH-01 AI (4 - 20mA) J4, 5 and 6 Analog Input 1
FIELD INSTALLED
FAN SPEED (DO-7) (MED OR LOW)
FAN SPEED (DO-8) (HIGH OR FAN ON )
123 45678
To
SPT PLUS
J14
2 3
1
J17
J19
GREEN
WHITE
BLACK
RED
Indoor Air Quality 33ZCSENCO2 AI (4 -20mA) J4, 2 and 3 Analog Input 2
Condensate Switch N/A BI (Dry Contacts) J1, 2 Binary Input 3
Stage 1 Compressor Status N/A BI (Dry Contacts) J1, 10 Binary Input 5
Leaving Condenser Water Temperature 10K Type II AI (10K Thermistor) J2, 1 and 2 Analog Input 6
Supply Air Temperature 33ZCSENSAT AI (10K Thermistor) J2, 3 and 4 Analog Input 7
To WSHP Controller
Rnet Terminals (J13)
Outputs
Modulating Valve (Auxiliary Heat/Water
Economizer)
DB
012207-1BT485BT
LED1
Install BT485 where device is
11
J1 J2
1
2
3
-
+
+24vac
SENSOR
4-20mA
SPACE CO2
-
+
+24vac
SENSOR
4-20mA
SPACE RH
FIELD INSTALLED (OPTIONAL) – SEE NOTE 2
45
6
J4
J20
1
123 4
RED
BLACK
WHITE
GREEN
123 4
Field Installed
Local Access Port
J12
J13
3
2
4
1
0
5
LSB
9
7
6
8
3
2
4
MSTP Baud
1
0
5
9600 19.2k 38.4k 76.8k
9
MSB
7
6
8
2
3
4
O
N
12
3 45
SW3
6
7 8
FIELD INSTALLED
SPT PLUS Sensor
Shown
GREEN
WHITE
BLACK
RED
To WSHP Controller Rnet Terminals (J13)
Gnd
Rnet+
Rnet-
+12V
24
Table 4 — 50PSH, PSV, PSD Electrical Data — PSC Motor
50PS UNIT SIZE
006 208/230-1-60 197/254 3.1 17.7 1 0.4 3.5 4.3 15 0.43 3.9 4.7 15 009 208/230-1-60 197/254 3.9 21.0 1 0.4 4.3 5.3 15 0.43 4.8 5.7 15 012 208/230-1-60 197/254 5.0 25.0 1 0.4 5.7 7.0 15 0.43 6.1 7.4 15
018
024
030
036
042
048
060
070
FLA Full Load Amps HACR — Heating, Air Conditioning and Refrigeration HWR — Hot Water Reheat LRA Locked Rotor Amps RLA Rated Load Amps
RATED
VOLTAGE
V-P h-H z
208/230-1-60 197/254 9.0 48.0 1 1.0 10.0 12.3 20 0.43 10.4 12.7 20
265-1-60 239/292 8.4 40.0 1 0.9 9.3 11.4 15 N/A N/A N/A N/A
208/230-1-60 197/254 12.8 60.0 1 1.1 13.9 17.1 25 0.43 14.3 17.5 30 208/230-3-60 197/254 8.0 55.0 1 1.1 9.1 11.1 15 0.43 9.5 11.5 15
460-3-60 414/506 4.0 22.4 1 0.6 4.6 5.6 15 N/A N/A N/A N/A
208/230-1-60 197/254 13.5 61.0 1 1.4 14.9 18.3 30 0.80 15.7 19.1 30
265-1-60 239/292 10.9 58.0 1 1.6 12.5 15.2 25 0.70 13.2 15.9 25
208/230-3-60 197/254 8.3 63.0 1 1.4 9.7 11.8 20 0.80 10.5 12.6 20
460-3-60 414/506 4.5 27.0 1 0.9 5.4 6.5 15 0.70 6.1 7.2 15
208/230-1-60 197/254 14.7 72.5 1 2.1 16.8 20.5 35 0.80 17.6 21.3 35
265-1-60 239/292 12.5 61.0 1 2.2 14.7 17.8 30 0.70 15.4 18.5 30
208/230-3-60 197/254 10.4 63.0 1 2.1 12.5 15.1 25 0.80 13.3 15.9 25
460-3-60 414/506 4.5 32.0 1 1.3 5.8 6.9 15 0.70 6.5 7.6 15
208/230-1-60 197/254 15.4 83.0 1 2.1 17.5 21.4 35 0.80 18.3 22.2 35 208/230-3-60 197/254 11.5 77.0 1 2.1 13.6 16.5 25 0.80 14.4 17.3 25
460-3-60 414/506 5.1 35.0 1 1.0 6.1 7.4 15 0.70 6.8 8.1 15 575-3-60 518/633 4.3 31.0 1 0.8 5.1 6.2 15 N/A N/A N/A N/A
208/230-1-60 197/254 20.5 109.0 1 3.0 23.5 28.6 45 0.80 24.3 29.4 45 208/230-3-60 197/254 14.6 91.0 1 3.0 17.6 21.3 35 0.80 18.4 22.1 35
460-3-60 414/506 7.1 46.0 1 1.7 8.8 10.6 15 0.70 9.5 11.3 15 575-3-60 518/633 5.1 34.1 1 1.4 6.5 7.8 15 N/A N/A N/A N/A
208/230-1-60 197/254 26.9 145.0 1 4.9 31.8 38.5 60 1.07 32.9 39.6 60 208/230-3-60 197/254 17.6 123.0 1 4.9 22.5 26.9 40 1.07 23.6 28.0 45
460-3-60 414/506 9.6 64.0 1 2.5 12.1 14.5 20 1.07 13.2 15.6 25 575-3-60 518/633 6.1 40.0 1 1.9 8.0 9.5 15 N/A N/A N/A N/A
208/230-1-60 197/254 30.1 158.0 1 5.8 35.9 43.4 70 1.07 37.0 44.5 70 208/230-3-60 197/254 20.5 155.0 1 5.8 26.3 31.4 50 1.07 27.4 32.5 50
460-3-60 414/506 9.6 75.0 1 2.6 12.2 14.6 20 1.07 13.3 15.7 25 575-3-60 518/633 7.6 54.0 1 2.3 9.9 11.8 15 N/A N/A N/A N/A
VOLTAGE
MIN/MAX
LEGEND NOTE: Unit sizes 006-012 are not available on 50PSD units.
COMPRESSOR
RLA LRA Qty
FAN
MOTOR
FLA
TOTAL
UNIT
FLA
MIN
CIRCUIT
AMP
MAX FUSE/ HACR
UNITS WITH PSC MOTOR AND HWR
REHEAT
PUMP
FLA
TOTAL
UNIT
FLA
MIN
CIRCUIT
AMP
MAX
FUSE /
HACR
Table 5 — 50PSH, PSV, PSD Electrical Data — PSC High-Static Motor
50PS UNIT
SIZE
018
024
030
036
042
048
060
FLA Full Load Amps HACR — Heating, Air Conditioning and Refrigeration HWR — Hot Water Reheat LRA Locked Rotor Amps RLA Rated Load Amps
RATED
VO LTAGE
V-P h-H z
208/230-1-60 197/254 9.0 48.0 1 1.10 7.9 12.4 20 0.80 10.9 13.2 20
265-1-60 239/292 8.4 40.0 1 0.90 7.1 11.4 15 0.70 10.0 12.1 20
208/230-1-60 197/254 12.8 60.0 1 1.40 14.2 17.4 30 0.80 15.0 18.2 30 208/230-3-60 197/254 8.0 55.0 1 1.40 9.4 11.4 15 0.80 10.2 12.2 20
460-3-60 414/506 4.0 22.4 1 0.90 4.9 5.9 15 0.70 5.6 6.6 15
208/230-1-60 197/254 13.5 61.0 1 1.80 15.3 18.7 30 0.80 16.1 19.5 30
265-1-60 239/292 10.9 58.0 1 2.00 12.9 15.6 25 0.70 13.6 16.3 25
208/230-3-60 197/254 8.3 63.0 1 1.80 10.1 12.2 20 0.80 10.9 13.0 20
460-3-60 414/506 4.5 27.0 1 1.24 5.7 6.9 15 0.70 6.4 7.6 15
208/230-1-60 197/254 14.7 72.5 1 2.00 16.7 20.4 35 0.80 17.5 21.2 35
265-1-60 239/292 12.5 61.0 1 1.66 14.2 17.3 25 0.70 14.9 18.0 30
208/230-3-60 197/254 10.4 63.0 1 2.00 12.4 15.0 25 0.80 13.2 15.8 25
460-3-60 414/506 4.5 32.0 1 1.00 5.5 6.6 15 0.70 6.2 7.3 15
208/230-1-60 197/254 15.4 83.0 1 3.00 18.4 22.3 35 0.80 19.2 23.1 35 208/230-3-60 197/254 11.5 77.0 1 3.00 14.5 17.4 25 0.80 15.3 18.2 25
460-3-60 414/506 5.1 35.0 1 1.70 6.8 8.1 15 0.70 7.5 8.8 15 575-3-60 518/633 4.3 31.0 1 1.40 5.7 6.8 15 N/A N/A N/A N/A
208/230-1-60 197/254 20.5 109.0 1 3.40 23.9 29.0 45 1.07 25.0 30.1 50 208/230-3-60 197/254 14.6 91.0 1 3.40 18.0 21.7 35 1.07 19.1 22.7 35
460-3-60 414/506 7.1 46.0 1 1.80 8.9 10.7 15 1.07 10.0 11.7 15 575-3-60 518/633 5.1 34.1 1 1.40 6.5 7.8 15 N/A N/A N/A N/A
208/230-1-60 197/254 26.9 145.0 1 5.80 32.7 39.4 60 1.07 33.8 40.5 60 208/230-3-60 197/254 17.6 123.0 1 5.80 23.4 27.8 45 1.07 24.5 28.9 45
460-3-60 414/506 9.6 64.0 1 2.60 12.2 14.6 20 1.07 13.3 15.7 25 575-3-60 518/633 6.1 40.0 1 2.30 8.4 9.9 15 N/A N/A N/A N/A
VO LTAGE
MIN/MAX
LEGEND NOTE: Unit sizes 006-012 are not available with PSC high-static motors.
COMPRESSOR
RLA LRA Qty
FAN
MOTOR
FLA
TOTAL
UNIT
FLA
MIN
CIRCUIT
AMP
MAX FUSE/ HACR
UNITS WITH HIGH-STATIC PSC MOTOR
REHEAT
PUMP
FLA
AND HWR
TOTAL
UNIT
FLA
MIN
CIRCUIT
AMP
MAX
FUSE /
HACR
25
Table 6 — 50PSH, PSV, PSD Electrical Data, ECM Motor
50PS UNIT SIZE
018
024
030
036
042
048
060
070
FLA Full Load Amps HACR — Heating, Air Conditioning and Refrigeration HWR — Hot Water Reheat LRA Locked Rotor Amps RLA Rated Load Amps
RATED
VO LTAGE
V-P h-H z
208/230-1-60 197/254 9.0 48.0 1 4.3 13.3 15.6 20 0.8 14.1 16.4 25
265-1-60 239/292 8.4 40.0 1 4.1 12.5 14.6 20 0.7 13.2 15.3 20
208/230-1-60 197/254 12.8 60.0 1 4.3 17.1 20.3 30 0.8 17.9 21.1 30 208/230-3-60 197/254 8.0 55.0 1 4.3 12.3 14.3 20 0.8 13.1 15.1 20
460-3-60 414/506 4.0 22.4 1 4.1 8.1 9.1 15 0.7 8.8 9.8 15
208/230-1-60 197/254 13.5 61.0 1 4.3 17.8 21.2 30 0.8 18.6 22.0 35
265-1-60 239/292 10.9 58.0 1 4.1 15.0 17.7 25 0.7 15.7 18.4 25
208/230-3-60 197/254 8.3 63.0 1 4.3 12.6 14.7 20 0.8 13.4 15.5 20
460-3-60 414/506 4.5 27.0 1 4.1 8.6 9.7 15 0.7 9.3 10.4 15
208/230-1-60 197/254 14.7 72.5 1 4.3 19.0 22.7 35 0.8 19.8 23.5 35
265-1-60 239/292 12.5 61.0 1 4.1 16.6 19.7 30 0.7 17.3 20.4 30
208/230-3-60 197/254 10.4 63.0 1 4.3 14.7 17.3 25 0.8 15.5 18.1 25
460-3-60 414/506 4.5 32.0 1 4.1 8.6 9.7 15 0.7 9.3 10.4 15
208/230-1-60 197/254 15.4 83.0 1 4.3 19.7 23.6 35 0.8 20.5 24.4 35 208/230-3-60 197/254 11.5 77.0 1 4.3 15.8 18.7 30 0.8 16.6 19.5 30
460-3-60 414/506 5.1 35.0 1 4.1 9.2 10.5 15 0.7 9.9 11.2 15
208/230-1-60 197/254 20.5 109.0 1 7.0 27.5 32.6 50 1.07 28.6 33.7 50 208/230-3-60 197/254 14.6 91.0 1 7.0 21.6 25.3 35 1.07 22.7 26.3 40
460-3-60 414/506 7.1 46.0 1 6.9 14.0 15.8 20 1.07 15.1 16.8 20
208/230-1-60 197/254 26.9 145.0 1 7.0 33.9 40.6 60 1.07 35.0 41.7 60 208/230-3-60 197/254 17.6 123.0 1 7.0 24.6 29.0 45 1.07 25.7 30.1 45
460-3-60 414/506 9.6 64.0 1 6.9 16.5 18.9 25 1.07 17.6 20.0 25
208/230-1-60 197/254 30.1 158.0 1 7.0 37.1 44.6 70 1.07 38.2 45.7 70 208/230-3-60 197/254 20.5 155.0 1 7.0 27.5 32.6 50 1.07 28.6 33.7 50
460-3-60 414/506 9.6 75.0 1 6.9 16.5 18.9 25 1.07 17.6 20.0 25
VOLTAGE
MIN/MAX
LEGEND NOTES:
COMPRESSOR
RLA LRA Qty
FAN
MOTOR
FLA
TOTAL
UNIT
FLA
1. The 460-v units using an ECM (electronically commutated motor) fan
2. Unit sizes 006-012 are not available with ECM motors.
MIN
CIRCUIT
AMP
motor, modulating HWR, and/or an internal secondary pump will require a neutral wire from the supply side in order to feed the accessory with 265-v.
MAX FUSE/ HACR
UNITS WITH ECM MOTOR AND HWR
REHEAT
PUMP
FLA
TOTAL
UNIT
FLA
MIN
CIRCUIT
AMP
MAX
FUSE /
HACR
COMPRESSOR CONTACTOR
LINE
TRANSFORMER
A50-7737
CAPACITOR
LOAD
COMPLETE C CONTROL
ECM CONTROL
BOARD
Fig. 26 — 50PSH,PSV,PSD Typical Single-Phase Line Voltage Power Connection
26
Step 9 — Wire Field Controls
THERMOSTAT CONNECTIONS — The thermostat should be wired directly to the ECM control board. See Fig. 27.
WATER FREEZE PROTECTION — The Aquazone™ con­trol allows the field selection of source fluid freeze protection points through jumpers. The factory setting of jumper JW3 (FP1) is set for water at 30 F. In earth loop applications, jumper JW3 should be clipped to change the setting to 10 F when us­ing antifreeze in colder earth loop applications. See Fig. 28.
NOTE: The extended range option should be selected with water temperatures below 60 F to prevent internal condensation.
AIR COIL FREEZE PROTECTION — The air coil freeze protection jumper JW2 (FP2) is factory set for 30 F and should not need adjusting.
ACCESSORY CONNECTIONS — Terminal A on the control is provided to control accessory devices such as water valves, electronic air cleaners, humidifiers, etc. This signal operates with the compressor terminal. See Fig. 29. Refer to the specific unit wiring schematic for details.
NOTE: The A terminal should only be used with 24-volt signals — not line voltage signals.
COMPRESSOR CONTACTOR
CAPACITOR
WATER SOLENOID VALVES — An external solenoid valve(s) should be used on ground water installations to shut off flow to the unit when the compressor is not operating. A slow closing valve may be required to help reduce water hammer. Figure 29 shows typical wiring for a 24-vac external solenoid valve. Figures 30 and 31 illustrate typical slow closing water control valve wiring for Taco 500 Series and Taco ESP Series valves. Slow closing valves take approximately 60 sec. to open (very little water will flow before 45 sec.). Once fully open, an end switch allows the compressor to be energized (only on valves with end switches). Only relay or triac based electronic thermostats should be used with slow closing valves. When wired as shown, the slow closing valve will operate properly with the following notations:
1. The valve will remain open during a unit lockout.
2. The valve will draw approximately 25 to 35 VA through the “Y” signal of the thermostat.
IMPORTANT: Connecting a water solenoid valve can overheat the anticipators of electromechanical thermo­stats. Only use relay based electronic thermostats.
COMPLETE C CONTROL
TRANSFORMER
a50-8197
LINE
LOAD
W
O
Y2
Y1
G
GGGGR
TB1
R
C
THERMOSTAT CONNECTION
CFM
Y2
G
Y1
O
Fig. 27 — Low Voltage Field Wiring
Fig. 29 — Typical Accessory Wiring
Y
DH
R
C
W
A
AL1
TERMINAL STRIP P2
C
A
SW1 SW2 SW3 SW4 SW5 SW6 SW7 SW8 SW9
G
A
J1
S1
OFF
DEHUM
ON
AL1
24 VAC
A50-6269
TYPICAL WATER VALVE
A50-7764
AQUAZONE CONTROL (Complete C Shown)
Fig. 28 — Typical Aquazone™ Control Board
Jumper Locations
27
C
1
HEATER SWITCH
C
THERMOSTAT
1Y
a50-8441
2
1Y
AMV
3
TACO VALVE
Fig. 30 — AMV Valve Wiring
a50-8442
Fig. 31 — Taco SBV Valve Wiring
WSHP OPEN WIRING — The WSHP Open controller will be factory mounted to the unit control panel and wired to the Complete C or Deluxe D control board, however, the system wiring will need to be completed utilizing WSHP Open con­troller wiring diagrams and the Third Party Integration (TPI) Guide. Factory installation includes harness, LWT (leaving water temperature), supply air, and condensate sensor.
WARNING
Disconnect all power to the unit before performing mainte­nance or service. Unit may automatically start if power is not disconnected. Failure to follow this warning could cause personal injury, death, and/or equipment damage.
Wiring Sensors to Inputs WSHP Open controller’s inputs. See Table 7.
All field control wiring that connects to the WSHP Open con­troller must be routed through the raceway built into the corner post. The raceway provides the UL required clearance between high and low-voltage wiring.
1. Pass control wires through hole provided in corner post.
2. Feed the wires through the raceway to the WSHP Open controller.
3. Connect the wires to the removable Phoenix connectors.
4. Reconnect the connectors to the board.
Field-Supplied Sensor Hardware troller is configurable with the following field-supplied sen­sors. See Table 7.
Table 7 — Field-Supplied Sensors for
WSHP Open Controller
SENSOR NOTES
Space Temperature Sensor
Indoor Air Quality Sensor
NOTE: BACview6 Handheld or Virtual BACview can be used as the user interface.
(SPT)
Outdoor Air
Temperature Sensor
(Separate Sensor)
Space Relative
Humidity Sensor
— Sensors can be wired to the
— The WSHP Open con-
Field Installed (Must be used with
WSHP Open controller.)
Network Sensor
Required only for demand
control ventilation.
Separate Sensor
For specific details about sensors, refer to the literature sup-
plied with the sensor. Wiring a SPT Sensor
— A WSHP Open controller is connect­ed to a wall-mounted space temperature (SPT) sensor to moni­tor room temperature using a Molex plug.
The WSHP Open system offers the following SPT sensors.
See Table 8.
Table 8 — SPT Sensors
SENSOR
SPT
Standard
SPT Plus SPPL
SPT Pro SPP
SPT Pro
Plus
*The SPT Pro Plus fan speed adjustment has no effect in this application.
PA RT
NUMBER
SPS
SPPF
FEATURES
• Local access por t
• No operator control
• Slide potentiometer to adjust set point
• Manual on button to override schedule
• LED to show occupied status
• Local access por t
• LCD display
• Manual on button to override schedule
• Warmer and cooler buttons to adjust set point
• Info button to cycle through zone and outside air temperatures, set points, and local override time
• Local access por t
• LCD display
• Manual on button to override schedule
• Warmer and cooler buttons to adjust set point
• Info button to cycle through zone and outside air temperatures, set points, and local override time
• Local access por t
• Fan speed*
Wire SPT sensors to the WSHP Open controller’s Rnet port. An Rnetbus can consist of any of the following combinations of devices wired in a daisy-chain configuration:
• 1 SPT Plus, SPT Pro, or SPT Pro Plus sensor
• 1 to 4 SPT Standard sensors
• 1 to 4 SPT Standard sensors and 1 SPT Plus, SPT Pro, or
SPT Pro Plus sensor
• Any of the above combinations, plus up to 2 BACview
Handheld but no more than 6 total devices NOTE: If the Rnetbus has multiple SPT Standard sensors, each
sensor must be given a unique address on the Rnetbus. See the Carrier Open Sensor Installation Guide.
Use the specified type of wire and cable for maximum signal integrity. See Table 9.
Table 9 — Rnet Wiring Specifications
RNET WIRING SPECIFICATIONS
Description
Conductor 18 AWG
Maximum Length 500 ft
Recommended Coloring
UL Temperature 32 to 167 F
Vol ta ge 300-vac, power limited
Listing UL: NEC CL2P, or better
LEGEND
AWG — American Wire Gage CMP — Communications Plenum Cable NEC — National Electrical Code UL Underwriters Laboratories
4 conductor, unshielded, CMP,
plenum rated cable
Jacket: white
Wiring: black, white, green, red
To wire the SPT sensor to the controller:
1. Partially cut , then bend and pull off the outer jacket of the Rnet cable(s), being careful not to nick the inner insulation.
2. Strip about
1
/4 in. of the inner insulation from each wire.
See Fig. 32.
6
28
OUTER JACKET
.25 IN.
INNER INSULATION
a50-8443
Fig. 32 — Rnet Cable Wire
3. Wire each terminal on the sensor to the same terminal on the controller. See Fig. 15-25. Table 10 shows the recom­mended Rnet wiring scheme.
Table 10 — Rnet Wiring
WIRE TERMINAL
Red +12-v Black .Rnet White Rnet+
Green Gnd
NOTE: The wire should be connected to the terminal shown.
Wiring a Supply Air Temperature (SAT) Sensor — The SAT sensor is required for reheat applications.
If the cable used to wire the SAT sensor to the controller will be less than 100 ft, an unshielded 22 AWG (American Wire Gage) cable should be used. If the cable will be greater than 100 ft, a shield 22 AWG cable should be used. The cable should have a maximum length of 500 ft.
To wire the SAT sensor to the controller:
1. Wire the sensor to the controller. See Fig. 15-25.
2. Verify that the Enable SAT jumper is on.
3. Verify that the Enable SAT and Remote jumper is in the left position.
Wiring an Indoor Air Quality (IAQ) Sensor
— An IAQ sensor monitors CO2 levels. The WSHP Open controller uses this information to adjust the outside-air dampers to provide proper ventilation. An IAQ sensor can be wall-mounted or mounted in a return air duct. (Duct installation requires an aspi­rator box assembly.)
The sensor has a range of 0 to 2000 ppm and a linear 4 to
20 mA output. This is converted to 1 to 5 vdc by a 250-ohm,
1
/4 watt, 2% tolerance resistor connected across the zone con-
troller’s IAQ input terminals. NOTE: Do not use a relative humidity sensor and CO
on the same zone controller if both sensors are powered off the
sensor
2
board. If sensors are externally powered, both sensors may be used on the same zone controller.
If the cable used to wire the IAQ sensor to the controller will be less than 100 ft, an unshielded 22 AWG (American Wire Gage) cable should be used. If the cable will be greater than 100 ft, a shield 22 AWG cable should be used. The cable should have a maximum length of 500 ft.
To wire the IAQ sensor to the controller:
1. Wire the sensor to the controller. See Fig. 15-25.
2. Install a field-supplied 250-ohm,
1
/4 watt, 2% tolerance resistor across the controller’s RH/IAQ and Gnd terminals.
3. Verify the the RH/IAQ jumper is set to 0 to 5 vdc.
Wiring a Relative Humidity (RH) Sensor
— The RH sensor is used for zone humidity control (dehumidification) if the WSHP unit has a dehumidification device. If not, the sensor only monitors humidity.
NOTE: Do not use a relative humidity sensor and CO on the same zone controller if both sensors are powered off the
sensor
2
board. If sensors are externally powered, both sensors may be used on the same zone controller.
If the cable used to wire the RH sensor to the controller will
be less than 100 ft, an unshielded 22 AWG (American Wire
Gage) cable should be used. If the cable will be greater than 100 ft, a shield 22 AWG cable should be used. The cable should have a maximum length of 500 ft.
To wire the RH sensor to the controller:
1. Strip the outer jacket from the cable for at least 4 in.
2. Strip
1
/4 in. of insulation from each wire.
3. Wire the sensor to the controller.
Step 10 — Operate ECM Interface Board —
The ECM fan is controlled by an interface board that converts thermostat inputs and field selectable cfm settings to signals used by the ECM (electronically commutated motor) controller. See Fig. 33.
1/4" SPADE
CONNECTIONS
TO COMPLETE C OR
DELUXE D BOARD
THERMOSTAT
CONNECTIONS
DEHUMIDIFICATION
LED
Y2
Y1
G
R
GGGGR
C
TB1
Y2
Y1
G
O
W
C
R DH
AL1
A
A
AL1
FAN SPEED SELECTION DIP SWITCH
G
DEHUM
OFF
ON
SW9
SW8
SW7
SW6
SW5
SW4
O
SW3
SW2
SW1
W
CFM
Y
S1
THERMOSTAT INPUT LEDS
CFM COUNTER 1 FLASH PER 100 CFM
ECM MOTOR LOW VOLTAGE CONNECTOR
J1
A50-7739
Fig. 33 — ECM Interface Board Physical Layout
NOTE: Power must be off to the unit for at least three seconds before the ECM will recognize a speed change. The motor will recognize a change in the CFM Adjust or Dehumidification mode settings while the unit is powered.
There are four different airflow settings from lowest airflow rate (speed tap 1) to the highest airflow rate (speed tap 4). Table 11 indicates settings for both versions of the ECM inter­face board, followed by detailed information for each setting.
CAUTION
When the disconnect switch is closed, high voltage is present in some areas of the electrical panel. Exercise cau­tion when working with energized equipment. Failure to heed this safety precaution could lead to personal injury.
COOLING — The cooling setting determines the cooling (normal) cfm for all units with ECM motor. Cooling (normal) setting is used when the unit is not in Dehumidification mode. Tap 1 is the lowest cfm setting, while tap 4 is the highest cfm setting. To avoid air coil freeze-up, tap 1 may not be used if the Dehumidification mode is selected. See Table 11.
HEATING — The heating setting determines the heating cfm for 50PSH, PSV, PSD units. Tap 1 is the lowest cfm setting, while tap 4 is the highest cfm setting. See Table 11.
CFM ADJUST — The CFM Adjust setting allows four selec­tions. The NORM setting is the factory default position. The + or – settings adjust the airflow by ±15%. The + or – settings are used to “fine tune” airflow adjustments. The TEST setting runs the ECM at 70% torque, which causes the motor to operate like a standard PSC motor, and disables the cfm counter. See Tables 11-13 for ECM and PSC blower motors performance data.
29
DEHUMIDIFICATION MODE — The dehumidification mode setting provides field selection of humidity control. When oper­ating in the normal mode, the cooling airflow settings are deter­mined by the cooling tap setting in Table 11. When dehumidifi­cation is enabled, there is a reduction in airflow in cooling to in­crease the moisture removal of the heat pump. The Dehumidification mode can be enabled in two ways:
1. Constant Dehumidification mode: When the Dehumidifi­cation mode is selected via DIP switch, the ECM will operate with a multiplier applied to the cooling CFM settings (approximately 20 to 25% lower airflow). Any time the unit is running in the Cooling mode, it will oper­ate at the lower airflow to improve latent capacity. The “DEHUM” LED will be illuminated at all times. Heating airflow is not affected.
Table 11 — ECM Blower Motor Performance Data
NOTE: Do not select Dehumidification mode if cooling setting is tap 1.
2. Automatic (humidistat-controlled) Dehumidification mode: When the Dehumidification mode is selected via DIP switch AND a humidistat is connected to termi­nal DH, the cooling airflow will only be reduced when the humidistat senses that additional dehumidification is required. The DH terminal is reverse logic. Therefore, a humidistat (not dehumidistat) is required. The “DEHUM” LED will be illuminated only when the humi­distat is calling for Dehumidification mode. Heating airflow is not affected.
NOTE: Do not select Dehumidification mode if cooling setting is tap 1.
50PS
UNIT SIZE
018 0.50
024 0.50
030 0.50
036 0.50
042 0.50
048 0.75 1
060 0.75 1
070 0.75 1
LEGEND ESP — External Static Pressure
NOTES:
1. Factory setting is Tap Setting 2.
2. Airflow is controlled within 5% up to the Max ESP shown with
3. Do not select Dehumidification mode if Tap Setting is on
MAX
ESP
(in. wg)
wet coil.
Setting 1.
FAN
MOTOR
(hp)
1
/
2
1
/
2
1
/
2
1
/
2
1
/
2
TAP
SETTING
4 750 620 380 590 480 380 750 620 380 3 700 570 350 550 450 350 700 570 350 2 620 510 310 480 400 310 620 510 310 1 530 430 270 530 430 270
4 950 780 470 740 610 470 1060 870 470 3 850 700 420 660 540 420 950 780 420 2 730 600 360 570 470 360 820 670 360 1 610 500 300 690 570 300
4 1130 920 560 880 720 560 1230 1000 560 3 1000 820 500 780 640 500 1100 900 500 2 880 720 440 680 560 440 980 800 440 1 750 620 380 850 700 380
4 1400 1150 700 1090 900 700 1400 1150 700 3 1250 1020 630 980 800 630 1250 1020 630 2 1080 890 540 840 690 540 1080 890 540 1 900 740 450 900 740 450
4 1580 1290 790 1230 1010 790 1580 1290 790 3 1400 1150 700 1100 900 700 1400 1150 700 2 1230 1000 610 960 790 610 1230 1000 610 1 1050 860 530 1050 860 530
4 1730 1420 870 1350 1110 870 1850 1520 870 3 1550 1270 780 1210 990 780 1650 1350 780 2 1330 1090 670 1040 850 670 1430 1180 670 1 1120 920 560 1200 980 560
4 2050 1680 1030 1600 1310 1030 2280 1870 1030 3 1825 1500 910 1420 1170 910 2050 1680 910 2 1580 1300 790 1230 1010 790 1750 1430 790 1 1320 1080 660 1470 1210 660
4 2230 1780 1100 1710 1400 1100 2230 1780 1100 3 1950 1600 980 1520 1250 980 2100 1680 980 2 1700 1400 850 1330 1090 850 1840 1470 850 1 1450 1200 730 1520 1220 730
COOLING MODE
(cfm)
Stage 1 Stage 2 Fan Stage 1 Stage 2 Fan Stage 1 Stage 2 Fan
DEHUMIDIFICATION MODE
4. All units are ARI/ISO (Air Conditioning & Refrigeration Institute/ International Organization for Standardization) 13256-1 rated Tap Setting 3.
5. Airflow in cfm with wet coil and clean air filter.
6. Units have an ECM (electronically commuted motor) fan motor as a standard feature. The small additional pressure drop of the reheat coil causes the ECM motor to slightly increase rpm to overcome the added pressure drop and maintain selected cfm up to maximum ESP (external static pressure).
7. Unit sizes 006-012 are not available with ECM motors.
(cfm)
HEATING MODE
(cfm)
30
Table 12 —
PSC Blower Motor Performance Data
50PS UNIT SIZE
RATED
AIRFLOW
018 600 450
024 850 600
030 950 750
036 1250 900
042 1400 1050
048 1600 1200
060 1950 1500
070 2100 1800
MIN
CFM
SPEED
HS MED 765 760 755 747 738 725 711 690 668 654 640 602
HS LO 683 672 661 649 636 616 596 584 571 560 549
HS MED 1048 1037 1025 1016 1007 994 981 962 943 915 886 822 731 626
HS LO 890 887 884 879 874 865 855 842 829 809 789 726 660
HS MED 1186 1174 1162 1151 1140 1126 1112 1089 1065 1039 1013 946 870 762
HS LO 1039 1038 1036 1028 1020 1009 997 983 968 946 923 866 798
HS MED 1344 1335 1325 1312 1299 1276 1253 1220 1186 1143 1099 1007 903
HS LO 1141 1128 1115 1106 1097 1077 1057 1031 1005 966 926
HS MED 1384 1382 1379 1375 1371 1356 1341 1318 1294 1261 1227
HS LO 1091 1088 1084 1081 1078 1069 1060
HS MED 1881 1858 1834 1807 1780 1746 1711 1676 1640 1604 1567 1469 1378 1286
HS LO 1738 1716 1694 1673 1651 1634 1617 1584 1551 1508 1465 1390 1321 1228
HS MED 2171 2167 2162 2162 2162 2158 2153 2135 2117 2101 2085 2024 1971 1891 1823 1691
HS LO 2010 2008 2006 2006 2006 2006 2006 1992 1977 1962 1947 1892 1851 1782 1705 1600
LEGEND
ESP — External Static Pressure HS — High Static
FAN
MED 602 601 599 590 581 583 585 579 573 560 547 492
HS HI 894 886 877 859 841 827 812 786 760 744 728 659
MED 841 833 825 817 809 800 790 777 763 747 731 686 623
HS HI 1271 1250 1229 1207 1185 1164 1143 1118 1093 1061 1029 953 875 753
MED 1048 1037 1025 1016 1007 994 981 962 943 915 886 822
HS HI 1439 1411 1383 1355 1327 1297 1266 1232 1198 1160 1122 1041 943 830
MED 1171 1164 1156 1145 1133 1113 1092 1064 1035 997 958
HS HI 1648 1633 1617 1597 1576 1557 1537 1493 1448 1397 1345 1207 1051 957
MED 1332 1323 1314 1298 1282 1263 1243 1206 1169 1115 1060
HS HI 1798 1781 1764 1738 1711 1688 1665 1630 1595 1555 1514 1420 1239
MED 1384 1382 1379 1375 1371 1356 1341 1318 1294 1261 1227
HS HI 2011 1977 1942 1923 1903 1841 1778 1755 1732 1689 1645 1520 1431 1307 1211
MED 2058 2049 2039 2028 2016 2000 1983 1966 1949 1935 1920 1874 1807 1750 1670 1582
HS HI 2510 2498 2486 2471 2455 2440 2424 2401 2377 2348 2318 2247 2161 2078 1986 1855
MED 2171 2167 2162 2162 2162 2158 2153 2135 2117 2101 2085 2024 1971 1891 1823
0.00 0.05 0.10 0.15 0.20 0.25 0.30 0.35 0.40 0.45 0.50 0.60 0.70 0.80 0.90 1.00
HI 704 708 711 702 693 692 690 683 675 658 640 598 515
LO 531 529 527 522 517 512 506 501 495 479 462
HI 965 960 954 943 931 923 914 898 882 862 842 794 725 635
LO 723 715 707 703 698 689 680 668 656 642 627
HI 1271 1250 1229 1207 1185 1164 1143 1118 1093 1061 1029 953 875 753
LO 890 887 884 879 874 865 855 842 829 809 789
HI 1411 1407 1402 1390 1378 1370 1361 1326 1290 1248 1205 1083 942
LO 983 967 950 943 936 936
HI 1634 1626 1618 1606 1594 1583 1571 1539 1507 1464 1420 1265 1078
LO 1130 1109 1088 1086 1084 1066 1048 1052 1055
HI 1798 1781 1764 1738 1711 1688 1665 1630 1595 1555 1514 1420 1239
LO
HI 2311 2306 2300 2290 2279 2268 2257 2233 2209 2175 2140 2088 1990 1901 1856 1752
LO 1868 1863 1858 1858 1858 1848 1838 1822 1806 1799 1792 1749 1699 1636 1570
HI 2510 2498 2486 2471 2455 2440 2424 2401 2377 2348 2318 2247 2161 2078 1986 1855
LO 2010 2008 2006 2006 2006 2006 2006 1992 1977 1962 1947 1892 1851
AIRFLOW (cfm) AT EXTERNAL STATIC PRESSURE (in. wg)
NOTES:
1. Shaded areas denote ESP where operation is not recommended.
2. Units factory shipped on medium speed. Other speeds require field selection.
3. All airflow is rated and shown above at the lower voltage if unit is dual voltage rated, e.g., 208 v for 208/230 v units.
4. Only two-speed fan (high and medium) available on 575 v units.
5. Data for units 006-012 not available at time of printing.
Table 13 — PSC Blower Motor Performance Data for 50PS Units with HWR
COIL
FACE VELOCITY
FPM
200 0.037 0.033 0.031 0.028 0.026 250 0.052 0.046 0.042 0.038 0.034 300 0.077 0.066 0.059 0.051 0.044 350 0.113 0.096 0.085 0.073 0.061 400 0.181 0.160 0.145 0.131 0.117 450 0.242 0.226 0.215 0.205 0.194 500 0.360 0.345 0.335 0.326 0.316
LEGEND
ESP — External Static Pressure HWR — Hot Water Reheat
NOTES:
1. For units with HWR coil applications, calculate face velocity of the enter­ing air. From the data table, find ESP for reheat application. The loss includes wet coil loss.
2. Data for units 006-012 not available at time of printing.
018
in. wg
024,030
in. wg
UNITS WITH REHEAT ESP LOSS
036
in. wg
31
042,048
in. wg
060,070
in. wg
PRE-START-UP
System Checkout —
follow the system checkout procedure outlined below before starting up the system. Be sure:
1. Voltage is within the utilization range specifications of the unit compressor and fan motor and voltage is balanced for 3-phase units.
2. Fuses, breakers and wire are correct size.
3. Low voltage wiring is complete.
4. Piping and system flushing is complete.
5. Air is purged from closed loop system.
6. System is balanced as required. Monitor if necessary.
7. Isolation valves are open.
8. Water control valves or loop pumps are wired.
9. Condensate line is open and correctly pitched.
10. Transformer switched to lower voltage tap if necessary.
11. Blower rotates freely — shipping support is removed.
12. Blower speed is on correct setting.
13. Air filter is clean and in position.
14. Service/access panels are in place.
15. Return-air temperature is between 40 to 80 F heating and 50 to 110 F cooling.
16. Air coil is clean.
17. Control field-selected settings are correct.
AIR COIL — To obtain maximum performance, clean the air coil before starting the unit. A 10% solution of dishwasher detergent and water is recommended for both sides of the coil. Rinse thoroughly with water.
When the installation is complete,
FIELD SELECTABLE INPUTS
Jumpers and DIP (dual in-line package) switches on the control board are used to customize unit operation and can be configured in the field.
IMPORTANT: Jumpers and DIP switches should only be clipped when power to control board has been turned off.
Complete C Control Jumper Settings
WATER COIL FREEZE PROTECTION (FP1) LIMIT SETTING — Select jumper 3 (JW3-FP1 Low Temp) to choose FP1 limit of either 30 F or 10 F. To select 30 F as the limit, DO NOT clip the jumper. To select 10 F as the limit, clip the jumper.
AIR COIL FREEZE PROTECTION (FP2) LIMIT SET­TING — Select jumper 2 (JW2-FP2 Low Temp) to choose FP2 limit of either 30 F or 10 F. To select 30 F as the limit, DO NOT clip the jumper. To select 10 F as the limit, clip the jumper.
ALARM RELAY SETTING — Select jumper 1 (JW1-AL2 Dry) to either connect alarm relay terminal (AL2) to 24 vac (R) or to remain as a dry contact (no connection). To connect AL2 to R, DO NOT clip the jumper. To set as dry contact, clip the jumper.
Deluxe D Control Jumper Settings
WATER COIL FREEZE PROTECTION (FP1) LIMIT SETTING — Select jumper 3 (JW3-FP1 Low Temp) to choose FP1 limit of either 30 F or 10 F. To select 30 F as the limit, DO NOT clip the jumper. To select 10 F as the limit, clip the jumper.
AIR COIL FREEZE PROTECTION (FP2) LIMIT SET­TING — Select jumper 2 (JW2-FP2 Low Temp) to choose FP2 limit of either 30 F or 10 F. To select 30 F as the limit, DO NOT clip the jumper. To select 10 F as the limit, clip the jumper.
ALARM RELAY SETTING — Select jumper 4 (JW4-AL2 Dry) to either connect alarm relay terminal (AL2) to 24 vac (R) or to remain as a dry contact (no connection). To connect AL2 to R, DO NOT clip the jumper. To set as dry contact, clip the jumper.
LOW PRESSURE SETTING — The Deluxe D control can be configured for Low Pressure Setting (LP). Select jumper 1 (JW1-LP Norm Open) for choosing between low pressure input normally opened or closed. To configure for normally closed operation, DO NOT clip the jumper. To configure for normally open operation, clip the jumper.
Complete C Control DIP Switches — The Com-
plete C control has 1 DIP (dual in-line package) switch bank with five switches labeled SW1. See Fig. 15, 17, 18, 20, 21, or
23. PERFORMANCE MONITOR (PM) — The PM is a unique
feature that monitors water temperature and will display a warn­ing when heat pump is beyond typical operating range. Refer to Control Operation section for detailed information. DIP switch 1 will enable or disable this feature. To enable the PM, set the switch to ON. To disable the PM, set the switch to OFF.
STAGE 2 — DIP switch 2 will enable or disable compressor delay. Set DIP switch to OFF for stage 2 in which the compres­sor will have a 3-second delay before energizing.
NOTE: The alarm relay will not cycle during Test mode if switch is set to OFF, stage 2.
SWITCH 3 — Not used. DDC OUTPUT AT EH2 — Switch 4 provides a selection for
Direct Digital Control (DDC) operation. If set to DDC output at EH2, the EH2 terminal will continuously output the last fault code of the controller. If the control is set to EH2 Normal, then EH2 will operate as standard electric heat output. Set the switch to ON to set the EH2 to normal. Set the switch to OFF to set the DDC output at EH2.
FACTORY SETTING — Switch 5 is set to ON. Do not change the switch to OFF unless instructed to do so by the factory.
Deluxe D Control DIP Switches — The Deluxe D
control has 2 DIP (dual in-line package) switch banks. Each bank has 8 switches and is labeled either S1 or S2 on the cir­cuit board. See Fig. 16, 19, 22, or 24.
DIP SWITCH BANK 1 (S1) — This set of switches offers the following options for Deluxe D control configuration:
Performance Monitor (PM) that monitors water temperature and will display a warning when heat pump is beyond typical operating range. Set switch 1 to enable or disable performance monitor. To enable the PM, set the switch to ON. To disable the PM, set the switch to OFF.
Compressor Relay Staging Operation able or disable compressor relay staging operation. The com­pressor relay can be set to turn on with stage 1 or stage 2 call from the thermostat. This setting is used with dual stage units (units with 2 compressors and 2 Deluxe D controls) or in mas­ter/slave applications. In master/slave applications, each com­pressor and fan will stage according to its switch 2 setting. If switch is set to stage 2, the compressor will have a 3-second delay before energizing during stage 2 demand.
NOTE: If DIP switch is set for stage 2, the alarm relay will not cycle during Test mode.
— The PM is a unique feature
— Switch 2 will en-
32
Heating/Cooling Thermostat Type
— Switch 3 provides se­lection of thermostat type. Heat pump or heat/cool thermostats can be selected. Select OFF for heat/cool thermostats. When in heat/cool mode, Y1 is used for cooling stage 1, Y2 is used for cooling stage 2, W1 is used for heating stage 1 and O/W2 is used for heating stage 2. Select ON for heat pump thermostats. In heat pump mode, Y1 used is for compressor stage 1, Y2 is used for compressor stage 2, W1 is used for heating stage 3 or emergency heat, and O/W2 is used for reversing valve (heating or cooling) depending upon switch 4 setting.
O/B Thermostat Type
— Switch 4 provides selection for heat pump O/B thermostats. O is cooling output. B is heating out­put. Select ON for thermostats with O output. Select OFF for thermostats with B output.
Dehumidification Fan Mode
— Switch 5 provides selection of normal or dehumidification fan mode. Select OFF for dehu­midification mode. The fan speed relay will remain OFF dur­ing cooling stage 2. Select ON for normal mode. The fan speed relay will turn on during cooling stage 2 in normal mode.
Output
— Switch 6 provides selection for DDC operation. If set to DDC output at EH2, the EH2 terminal will continuously output the last fault code of the controller. If the control is set to EH2 normal, then the EH2 will operate as standard electric heat output. Set the switch to ON to set the EH2 to normal. Set the switch to OFF to set the DDC output at EH2.
Boilerless Operation
— Switch 7 provides selection of boiler­less operation and works in conjunction with switch 8. In boil­erless operation mode, only the compressor is used for heating when FP1 is above the boilerless changeover temperature set by switch 8 below. Select ON for normal operation or select OFF for boilerless operation.
Boilerless Changeover Temperature
— Switch 8 on S1 pro­vides selection of boilerless changeover temperature set point. Select OFF for set point of 50 F or select ON for set point of 40 F.
If switch 8 is set for 50 F, then the compressor will be used for heating as long as the FP1 is above 50 F. The compressor will not be used for heating when the FP1 is below 50 F and the compressor will operates in emergency heat mode, staging on EH1 and EH2 to provide heat. If a thermal switch is being used instead of the FP1 thermistor, only the compressor will be used for heating mode when the FP1 terminals are closed. If the FP1 terminals are open, the compressor is not used and the control goes into emergency heat mode.
DIP SWITCH BANK 2 (S2) — This set of DIP switches is used to configure accessory relay options.
Switches 1 to 3
— These DIP switches provide selection of Accessory 1 relay options. See Table 14 for DIP switch combinations.
Switches 4 to 6
— These DIP switches provide selection of Accessory 2 relay options. See Table 15 for DIP switch combinations.
Table 14 — DIP Switch Block S2 —
Accessory 1 Relay Options
ACCESSORY 1
RELAY OPTIONS
Cycle with Fan On On On
Digital NSB Off On On
Water Valve — Slow Opening On Off On
OAD On On Off
Reheat — Humidistat Off Off Off
Reheat — Dehumidistat Off On Off
LEGEND
NSB — Night Setback OAD — Outside Air Damper
NOTE: All other DIP switch combinations are invalid.
DIP SWITCH POSITION
123
Table 15 — DIP Switch Block S2 —
Accessory 2 Relay Options
ACCESSORY 2
RELAY OPTIONS
Cycle with Compressor On On On
Digital NSB Off On On
Water Valve — Slow Opening On Off On
OAD On On Off
LEGEND
NSB — Night Setback OAD — Outside Air Damper
NOTE: All other switch combinations are invalid.
DIP SWITCH POSITION
456
Auto Dehumidification Mode or High Fan Mode — Switch 7 provides selection of auto dehumidification fan mode or high fan mode. In auto dehumidification fan mode, the fan speed relay will remain off during cooling stage 2 if terminal H is active. In high fan mode, the fan enable and fan speed relays will turn on when terminal H is active. Set the switch to ON for auto dehumidification fan mode or to OFF for high fan mode.
Factory Setting
— Switch 8 is set to ON. Do not change the
switch to OFF unless instructed to do so by the factory.
Units with Modulating Hot Water Reheat (HWR) Option —
reheat (HWR) can operate in three modes: cooling, cooling with reheat, and heating. The cooling and heating modes are like any other water source heat pump. The reversing valve ("O" signal) is energized in cooling, along with the compressor contactor(s) and blower relay. In the heating mode, the revers­ing valve is deenergized. Almost any thermostat will activate the heat pump in heating or cooling modes. The Deluxe D microprocessor board, which is standard with the HWR option, will accept either heat pump (Y,O) thermostats or non­heat pump (Y,W) thermostats.
The reheat mode requires either a separate humidistat/ dehumidistat or a thermostat that has an integrated dehumidifi­cation function for activation. The Deluxe D board is config­ured to work with either a humidistat or dehumidistat input to terminal “H” (DIP switch settings for the Deluxe D board are shown in Table 16). Upon receiving an “H” input, the Deluxe D board will activate the cooling mode and engage reheat.
Table 16 — Humidistat/Dehumidistat Logic and
Deluxe D DIP Switch Settings
Sensor 2.1
Humidistat
Dehumidistat Off On Off Standard 24 VAC 0 VAC
Table 17 shows the relationship between thermostat input signals and unit operation. There are four operational inputs for single-stage units and six operational inputs for dual-stage units:
•Fan Only
• Cooling Stage 1
• Cooling Stage 2
• Heating Stage 1
• Heating Stage 2
• Reheat Mode
A heat pump equipped with hot water
2.2 2.3 Logic
Off Off Off Reverse 0 VAC 24 VAC
Reheat
(ON) - H
Reheat
(OFF) - H
33
HWR APPLICATION CONSIDERATIONS — Unlike most hot gas reheat options, the HWR option will operate over a wide range of entering-water temperatures (EWTs). Special flow regulation (water regulating valve) is not required for low EWT conditions. However, below 55 F, supply-air temperatures cannot be maintained at 72 F because the cooling capacity exceeds the reheat coil capac­ity at low water temperatures. Below 55 F, essentially all water is diverted to the reheat coil (no heat of rejection to the building loop). Although the HWR option will work fine with low EWTs, overcooling of the space may result with well water systems or, on rare occasions, with ground loop (geothermal) systems (NOTE: Extended range units are required for well water and ground loop systems). Since dehumidification is generally only required in cooling, most ground loop systems will not experience overcooling of the supply-air temperature. If overcooling of the space is a con­cern (e.g., computer room well water application), auxiliary heating may be required to maintain space temperature when the unit is operating in the dehumidification mode. Water source heat pumps with HWR should not be used as makeup air units. These applications should use equipment specifically designed for makeup air.
Table 17 — HWR Operating Modes
HWR COMPONENT FUNCTIONS — The proportional controller operates on 24 VAC power supply and automatically adjusts the water valve based on the supply-air sensor. The supply-air sensor senses supply-air temperature at the blower inlet, providing the input signal necessary for the proportional control to drive the motorized valve during the reheat mode of operation. The motorized valve is a proportional actuator/three­way valve combination used to divert the condenser water from the coax to the hydronic reheat coil during the reheat mode of operation. The proportional controller sends a signal to the motorized valve based on the supply-air temperature reading from the supply air sensor.
The loop pump circulates condenser water through the hy­dronic reheat coil during the reheat mode of operation (refer to Fig. 34). In this application, the loop pump is only energized during the reheat mode of operation. The hydronic coil is uti­lized during the reheat mode of operation to reheat the air to the set point of the proportional controller. Condenser water is di­verted by the motorized valve and pumped through the hydron­ic coil by the loop pump in proportion to the control set point. The amount of reheating is dependent on the set point and how far from the set point the supply air temperature is. The factory set point is 70 to 75 F, generally considered "neutral" air.
MODE
No Demand On/Off
Fan Only On/Off On Off Off Off On/Off On Off Off Off
Cooling Stage 1 Cooling Stage 2 Cooling and Dehumidistat Dehumidistat Only Heating Stage 1 Heating Stage 2 Heating and Dehumidistat**
*Not applicable for single stage units; Full load operation for dual
capacity units.
†Cooling input takes priority over dehumidify input.
**Deluxe D is programmed to ignore the H demand when the unit is
in heating mode.
NOTE: On/Off is either on or off.
O
On On On Off Off On On On Off Off On On On On Off On On On On Off On On On On/Off On On On On On/Off Off
On/Off Off Off Off
Off Off Off
INPUT
GY1Y2*H O GY1Y2*Reheat
Off
On On Off Off Off On On Off Off On On On Off Off On On On Off On On On/Off On Off On On On/Off Off
Off Off Off On/Off Off Off Off Off
On On On On On On
OUTPUT
a50-8145
Water Out (To Water Loop)
Water In (From Water Loop)
Mixing Valve
Internal Pump
Refrigerant In
(Cooling)
COAX
NOTE: All components shown are internal to the heat pump unit.
Refrigerant Out
(Cooling)
Entering Air
Fig. 34 — HWR Schematic
34
Evaporator Coil
Leaving
Air
Reheat
Coil
Deluxe D Control Accessory Relay Configura­tions —
ble for Deluxe D control: CYCLE WITH FAN — In this configuration, the accessory
relay 1 will be ON any time the Fan Enable relay is on. CYCLE WITH COMPRESSOR — In this configuration, the
accessory relay 2 will be ON any time the Compressor relay is on.
DIGITAL NIGHT SET BACK (NSB) — In this configura­tion, the relay will be ON if the NSB input is connected to ground C.
NOTE: If there are no relays configured for digital NSB, then the NSB and override (OVR) inputs are automatically config­ured for mechanical operation.
MECHANICAL NIGHT SET BACK — When NSB input is connected to ground C, all thermostat inputs are ignored. A thermostat set back heating call will then be connected to the OVR input. If OVR input becomes active, then the Deluxe D control will enter night low limit (NLL) staged heating mode. The NLL staged heating mode will then provide heating dur­ing the NSB period.
WATER VALVE (SLOW OPENING) — If relay is configured for Water Valve (slow opening), the relay will start 60 seconds prior to starting compressor relay.
OUTSIDE AIR DAMPER (OAD) — If relay is configured for OAD, the relay will normally be ON any time the Fan Enable relay is energized. The relay will not start for 30 minutes fol­lowing a return to normal mode from NSB, when NSB is no longer connected to ground C. After 30 minutes, the relay will start if the Fan Enable is set to ON.
The following accessory relay settings are applica-
CAUTION
To avoid equipment damage, DO NOT leave system filled in a building without heat during the winter unless anti­freeze is added to system water. Condenser coils never fully drain by themselves and will freeze unless winterized with antifreeze.
START-UP
Use the procedure outlined below to initiate proper unit
start-up. NOTE: This equipment is designed for indoor installation only.
Operating Limits
ENVIRONMENT — This equipment is designed for indoor installation ONLY. Extreme variations in temperature, humidi­ty and corrosive water or air will adversely affect the unit per­formance, reliability and service life.
POWER SUPPLY — A voltage variation of ± 10% of name­plate utilization voltage is acceptable.
UNIT STARTING CONDITIONS — Units start and operate in an ambient temperature of 45 F with entering-air tempera­ture at 50 F, entering-water temperature at 60 F and with both air and water at the flow rates used.
NOTE: These operating limits are not normal or continuous operating conditions. Assume that such a start-up is for the purpose of bringing the building space up to occupancy tem­perature. See Table 18 for operating limits.
WARNING
When the disconnect switch is closed, high voltage is present in some areas of the electrical panel. Exercise cau­tion when working with the energized equipment. Failure to heed this warning may result in personal injury.
1. Restore power to system.
2. Turn thermostat fan position to ON. Blower should start.
3. Balance airflow at registers.
4. Adjust all valves to the full open position and turn on the line power to all heat pump units.
5. Operate unit in the cooling cycle. Refer to Table 14 for unit operating limits.
NOTE: Three factors determine the operating limits of a unit: (1) entering air temperature, (2) water temperature and (3) ambient temperature. Whenever any of these factors are at a minimum or maximum level, the other two factors must be at a normal level to ensure proper unit operation. See Table 18.
Table 18 — Operating Limits —
50PSH, PSV, PSD Units
Min. Ambient Air 45 39 Rated Ambient Air 80.6 68 Max. Ambient Air 110 85 Min. Entering Air 50 40 Rated Entering Air db/wb 80/67 68 Max. Entering Air db/wb 110/83 80
Min. Entering Water 30 20 Normal Entering Water 50-110 30-70 Max. Entering Water 120 90
db — Dry Bulb wb — Wet Bulb
NOTE: Value in heating column is dry bulb only. Any wet bulb reading is acceptable.
AIR LIMITS COOLING (F) HEATING (F)
WATER LIMITS
LEGEND
Scroll Compressor Rotation — It is important to be
certain compressor is rotating in the proper direction. To determine whether or not compressor is rotating in the proper direction:
1. Connect service gages to suction and discharge pressure fittings.
2. Energize the compressor.
3. The suction pressure should drop and the discharge pressure should rise, as is normal on any start-up.
If the suction pressure does not drop and the discharge
pressure does not rise to normal levels:
1. Turn off power to the unit. Install disconnect tag.
2. Reverse any two of the unit power leads.
3. Reapply power to the unit and verify pressures are correct.
The suction and discharge pressure levels should now move
to their normal start-up levels.
When the compressor is rotating in the wrong direction, the
unit makes more noise and does not provide cooling.
After a few minutes of reverse operation, the scroll com­pressor internal overload protection will open, thus activating the unit lockout. This requires a manual reset. To reset, turn the thermostat on and then off.
NOTE: There is a 5-minute time delay before the compressor will start.
Unit Start-Up Cooling Mode
1. Adjust the unit thermostat to the warmest position. Slowly reduce the thermostat position until the compres­sor activates.
2. Check for cool air delivery at unit grille a few minutes after the unit has begun to operate.
3. Verify that the compressor is on and that the water flow rate is correct by measuring pressure drop through the heat exchanger using P/T plugs. See Table 19. Check the elevation and cleanliness of the condensate lines; any dripping could be a sign of a blocked line. Be sure the condensate trap includes a water seal.
35
4. Check the temperature of both supply and discharge water. Compare to Tables 20-30. If temperature is within range, proceed. If temperature is outside the range, check the cooling refrigerant pressures in Tables 20-30.
5. Check air temperature drop across the coil when com­pressor is operating. Air temperature drop should be between 15 and 25 F.
Table 19 — Water Temperature Change
through Heat Exchanger
WATER FLOW RATE (GPM)
For Closed Loop: Ground Source or Cooling/Boiler Systems at 3 gpm/ton
For Open Loop: Ground Water Systems at
1.5 gpm/ton
COOLING
RISE (F)
Min Max Min Max
91248
20 26 10 17
HEATING
DROP (F)
Table 20 — 50PSH, PSV, PSD006 Typical Unit Operating Pressures and Temperatures
ENTERING
WATER
TEMP
(F)
110
DB Dry Bulb HWG — Hot Water Generator ——No Heating Operation in This Temperature Range
30
50
70
90
WATER
FLOW
(GPM/ton)
1.5 114-124 142-162 24-29 3-8 15.2-17.2 17-23 75-85 272-292 13-18 4- 9 5.9- 7.9 16-22
2.25 111-121 132-152 26-31 3-8 11.4-13.4 17-23 78-88 274-294 13-18 4- 9 4.3- 6.3 16-22 3 109-119 122-142 28-33 3-8 7.5-9.5 17-23 81-91 276-296 13-18 4- 9 2.7- 4.7 17-23
1.5 130-140 190-210 14-19 2-7 16.5-18.5 18-24 104-114 299-319 12-17 6-11 8.8-10.8 21-27
2.25 129-139 180-200 16-21 2-7 12.3-14.3 18-24 112-122 304-324 12-17 4- 9 6.7- 8.7 22-28 3 128-138 170-190 19-24 2-7 8.00-10.0 18-24 120-130 308-328 12-17 3- 8 4.5- 6.5 23-29
1.5 143-153 265-285 9-14 2-7 15.5-17.5 18-24 129-139 321-341 11-16 7-12 11.2-13.2 25-31
2.25 141-151 252-272 10-15 2-7 11.5-13.5 18-24 144-154 330-350 13-18 4- 9 8.8- 10.8 27-33 3 140-150 240-260 11-16 2-7 7.5-9.5 18-24 159-169 340-360 15-20 3- 8 6.3- 8.3 28-34
1.5 149-159 340-370 8-13 2-7 14.2-16.2 17-23 163-173 349-369 13-18 7-12 14.3-16.3 30-36
2.25 149-159 335-355 8-13 2-7 10.6-12.6 17-23 180-190 360-380 11-16 4- 9 11.2-13.2 32-38 3 148-158 320-340 8-13 2-7 7.00-9.00 17-23 198-208 372-392 10-15 3- 8 8.1-10.1 34-40
1.5 154-164 451-471 8-13 2-7 12.7-14.7 15-21
2.25 154-164 428-448 8-13 2-7 9.5-11.5 15-21 — 3 153-163 405-425 8-13 2-7 6.5-8.5 15-21
LEGEND
FULL LOAD COOLING — WITHOUT HWG ACTIVE FULL LOAD HEATING — WITHOUT HWG ACTIVE
Suction
Pressure
(psig)
Discharge
Pressure
(psig)
Super-
heat
(F)
Sub-
cooling
(F)
Water Tem p
Rise
(F)
Unit Start-Up Heating Mode
NOTE: Operate the unit in heating cycle after checking the cooling cycle. Allow 5 minutes between tests for the pressure or reversing valve to equalize.
1. Turn thermostat to lowest setting and set thermostat switch to HEAT position.
2. Slowly turn the thermostat to a higher temperature until the compressor activates.
3. Check for warm air delivery at the unit grille within a few minutes after the unit has begun to operate.
4. Check the temperature of both supply and discharge water. Compare to Tables 20-30. If temperature is within range, proceed. If temperature is outside the range, check the heating refrigerant pressures in Tables 20-30.
5. Once the unit has begun to run, check for warm air deliv­ery at the unit grille.
6. Check air temperature rise across the coil when compres­sor is operating. Air temperature rise should be between 20 and 30 F after 15 minutes at load.
7. Check for vibration, noise and water leaks.
Air Temp
Drop
(F) DB
Suction
Pressure
(psig)
Discharge
Pressure
(psig)
Super-
heat
(F)
Sub-
cooling
(F)
Wate r Temp
Drop
(F)
Air Temp
Rise
(F) DB
Table 21 — 50PSH, PSV, PSD009 Typical Unit Operating Pressures and Temperatures
ENTERING
WATER
TEMP
(F)
110
DB Dry Bulb HWG — Hot Water Generator ——No Heating Operation in This Temperature Range
30
50
70
90
WATER
FLOW
(GPM/ton)
1.5 126-136 161-181 17-22 8-13 19.8-21.8 21-27 74-84 278-298 6-11 4-9 6.1-8.1 18-24
2.25 126-136 146-166 17-22 7-12 14.9-16.9 21-27 77-87 280-300 6-11 4-9 4.5-6.5 18-24 3 126-136 131-151 17-22 6-11 9.9-11.9 21-27 79-89 283-303 6-11 3-8 2.8-4.8 19-25
1.5 132-142 215-235 10-15 8-13 18.8-20.8 20-26 104-114 309-329 8-12 7-12 9.6-11.6 24-30
2.25 132-142 200-220 10-15 7-12 14.1-16.1 20-26 106-116 312-332 8-12 7-12 7.0-9.0 24-30 3 132-142 185-205 10-15 6-11 9.4-11.4 20-26 108-118 315-335 8-12 7-12 4.5-6.5 25-31
1.5 138-148 278-298 8-13 9-14 17.7-19.7 19-25 127-137 332-352 10-15 10-15 12.0-14.0 29-35
2.25 138-148 263-283 8-13 8-13 13.1-15.1 19-25 132-142 340-360 11-16 10-15 9.0-10 29-35 3 137-147 248-268 8-13 7-12 8.5-10.5 19-25 138-148 347-367 13-18 10-15 6.1-8.1 30-36
1.5 142-152 365-385 8-13 9-14 16.0-18.0 18-24 164-174 372-392 17-22 13-18 14.5-16.5 35-41
2.25 142-152 351-371 8-13 8-13 12.0-14.0 18-24 165-175 375-395 18-23 13-18 11.2-13.2 35-41 3 142-152 337-357 8-13 7-12 8.0-10.0 18-24 167-177 379-399 19-24 13-18 7.9-9.9 36-42
1.5 150-160 439-459 7-12 9-14 14.2-16.2 17-23
2.25 150-160 439-459 7-12 8-13 10.6-12.6 17-23 — 3 150-160 439-459 7-12 7-12 6.9-8.9 17-23
LEGEND
FULL LOAD COOLING — WITHOUT HWG ACTIVE FULL LOAD HEATING — WITHOUT HWG ACTIVE
Suction
Pressure
(psig)
Discharge
Pressure
(psig)
Super-
heat
(F)
Sub-
cooling
(F)
Water Tem p
Rise
(F)
Air Temp
(F) DB
36
Drop
Suction
Pressure
(psig)
Discharge
Pressure
(psig)
Super-
heat
(F)
Sub-
cooling
(F)
Wate r Temp
Drop
(F)
Air Temp
Rise
(F) DB
Table 22 — 50PSH, PSV, PSD012 Typical Unit Operating Pressures and Temperatures
ENTERING
WATER
TEMP
DB Dry Bulb HWG — Hot Water Generator ——No Heating Operation in This Temperature Range
(F)
30
50
70
90
110
WATER
FLOW
(GPM/ton)
1.5 98-108 140-160 36-41 14-19 17.1-19.1 19-25 72-82 301-321 9-14 12-17 6.5-8.5 21-27
2.25 98-108 135-155 36-41 12-17 12.5-14.5 19-25 85-95 304-324 9-14 12-17 4.7-6.7 21-27 3 99-109 127-148 36-41 10-15 7.9-9.9 19-25 78-88 308-328 9-14 12-17 2.9-4.9 22-28
1.5 118-128 215-235 22-27 14-19 18.1-20.1 20-26 100-110 337-357 10-15 15-20 9.5-11.5 26-32
2.25 118-128 200-220 22-27 12-17 13.1-15.1 20-26 98-108 334-354 10-15 15-20 6.6-8.6 26-32 3 118-128 185-205 22-27 10-15 8.1-10.1 19-25 95-105 332-352 11-16 15-20 3.8-5.8 26-32
1.5 132-142 300-320 11-16 12-17 17.0-19.0 19-25 115-125 361-381 19-24 18-23 11.1-13.1 29-35
2.25 132-142 263-282 11-16 10-15 12.6-14.6 19-25 112-122 360-380 20-25 18-23 8.0-10.0 29-35 3 132-142 245-265 12-17 7-12 8.2-10.2 19-25 110-120 356-376 21-26 18-23 4.8-6.8 29-35
1.5 138-148 366-386 9-14 11-16 15.8-17.8 18-24 122-132 376-396 34-39 22-27 12.1-14.1 32-38
2.25 138-148 353-373 9-14 9-14 14.9-16.9 18-24 123-133 378-398 36-41 22-27 9.0-11.0 32-38 3 138-148 340-360 9-14 6-11 14.0-16.0 18-24 124-134 380-400 38-43 23-28 5.8-7.8 32-38
1.5 145-155 453-473 9-14 9-14 14.7-16.7 16-22
2.25 145-155 442-462 9-14 7-12 10.8-12.8 16-22 — 3 145-155 431-451 9-14 5-10 6.8-8.8 17-23
LEGEND
FULL LOAD COOLING — WITHOUT HWG ACTIVE FULL LOAD HEATING — WITHOUT HWG ACTIVE
Suction
Pressure
(psig)
Discharge
Pressure
(psig)
Super-
heat
(F)
Table 23 — 50PSH, PSV, PSD018 Typical Unit Operating Pressures and Temperatures
Sub-
cooling
(F)
Water
Tem p
Rise
(F)
Air Temp
Drop
(F) DB
Suction
Pressure
(psig)
Discharge
Pressure
(psig)
Super-
heat
(F)
Sub-
cooling
(F)
Water Tem p
Drop
(F)
Air Temp
Rise
(F) DB
ENTERING
WATER
TEMP
(F)
30
50
70
90
110
DB Dry Bulb HWG — Hot Water Generator ——No Heating Operation in This Temperature Range
WATER
FLOW
(GPM/ton)
1.5 120-130 155-175 27-32 11-16 16.9-19.9 16-22 73- 83 268-288 8-13 4- 9 6.1- 8.1 15-21
2.25 120-130 142-162 27-32 9-14 12.5-14.5 17-23 75- 85 270-290 8-13 4- 9 4.4- 6.4 16-22 3 120-130 128-148 27-32 9-14 8.1-10.1 17-23 78- 88 272-292 8-13 4- 9 2.9- 4.9 16-22
1.5 137-147 220-240 16-21 10-15 17.0-19.0 16-22 102-112 295-315 8-13 8-13 9.1-11.1 20-26
2.25 137-147 206-226 16-21 8-13 12.6-14.6 17-23 106-116 297-317 8-13 8-13 6.9- 8.9 21-27 3 137-147 192-212 16-21 8-13 8.4-10.4 17-23 110-120 299-319 8-13 8-13 4.7- 6.7 21-27
1.5 142-152 287-307 7-12 10-15 15.9-17.9 16-22 131-141 324-344 9-14 10-15 12.1-14.1 25-33
2.25 142-152 273-239 7-12 8-13 11.8-13.8 17-23 137-147 326-346 9-14 10-15 9.3-11.3 26-34 3 142-152 259-279 7-12 8-13 7.8- 9.8 17-23 144-154 328-348 9-14 10-15 6.6- 8.6 26-34
1.5 146-156 375-395 6-11 10-15 14.9-16.9 16-22 174-184 360-380 10-15 12-17 15.8-17.8 32-40
2.25 146-156 361-381 6-11 8-13 11.0-13.0 17-23 180-190 367-387 11-16 12-17 11.9-13.9 33-41 3 146-156 347-367 6-11 8-13 7.2- 9.2 17-23 187-197 374-394 12-17 12-17 8.0-10.0 33-41
1.5 154-164 478-498 6-11 10-15 14.0-16.0 16-22
2.25 154-164 461-481 6-11 8-13 10.2-12.2 16-22 — 3 154-164 445-465 6-11 8-13 6.5- 8.5 16-22
LEGEND
FULL LOAD COOLING — WITHOUT HWG ACTIVE FULL LOAD HEATING — WITHOUT HWG ACTIVE
Suction
Pressure
(psig)
Discharge
Pressure
(psig)
Super-
heat
(F)
Table 24 — 50PSH, PSV, PSD024 Typical Unit Operating Pressures and Temperatures
ENTERING
WATER
TEMP
(F)
30
50
70
90
110
LEGEND
DB Dry Bulb HWG — Hot Water Generator ——No Heating Operation in This Temperature Range
WATER
FLOW
(GPM/ton)
1.5 115-125 154-174 40-45 8-13 16.5-18.5 19-25 73- 83 283-303 8-12 6-11 5.9- 7.9 16-22
2.25 115-125 141-161 40-45 6-11 12.1-14.1 20-26 75- 85 285-305 8-12 6-11 4.2- 6.2 17-23 3 115-125 127-147 40-45 6-11 77.7- 9.7 20-26 78- 88 287-307 8-12 6-11 2.7- 4.7 18-24
1.5 115-120 209-229 24-29 10-15 15.7-17.7 18-24 102-112 313-333 8-12 8-13 8.9-10.9 22-28
2.25 115-120 195-215 24-29 8-13 11.6-13.6 18-24 106-116 314-334 8-12 8-13 6.7- 8.7 23-29 3 115-120 181-201 24-29 8-13 7.6- 9.6 18-24 110-120 316-336 8-12 8-13 4.5- 6.5 23-29
1.5 136-146 275-295 6-11 6-11 15.7-17.7 18-24 128-138 340-360 9-14 9-14 11.3-13.3 27-34
2.25 136-146 261-281 6-11 5-10 11.6-13.6 18-24 134-144 342-362 9-14 9-14 8.5-10.5 28-35 3 136-146 247-267 6-11 4- 9 7.6- 9.6 18-24 141-151 344-364 9-14 9-14 5.8- 7.8 28-35
1.5 140-150 361-381 6-11 6-11 14.9-16.9 18-24 162-172 370-390 14-19 9-14 14.4-16.4 32-40
2.25 140-150 347-367 6-11 5-10 11.0-13.0 18-24 166-176 376-396 15-20 9-14 10.8-12.8 34-42 3 140-150 333-353 6-11 4- 9 7.2- 9.2 18-24 171-181 383-403 16-21 9-14 7.1- 9.1 34-42
1.5 144-154 460-480 6-11 6-11 13.9-15.9 17-23
2.25 144-154 445-465 6-11 4- 9 10.2-12.2 17-23 — 3 144-154 428-448 6-11 4- 9 6.5- 8.5 17-23
FULL LOAD COOLING — WITHOUT HWG ACTIVE FULL LOAD HEATING — WITHOUT HWG ACTIVE
Suction
Pressure
(psig)
Discharge
Pressure
(psig)
Super-
heat
(F)
Sub-
cooling
(F)
Sub-
cooling
(F)
Water
Tem p
Rise
(F)
Water
Tem p
Rise
(F)
Air Temp
Drop
(F) DB
Air Temp
Drop
(F) DB
Suction
Pressure
(psig)
Suction
Pressure
(psig)
Discharge
Pressure
(psig)
Discharge
Pressure
(psig)
Super-
heat
(F)
Super-
heat
(F)
Sub-
cooling
(F)
Sub-
cooling
(F)
Wate r Tem p
Drop
(F)
Wate r Temp
Drop
(F)
Air Temp
Rise
(F) DB
Air Temp
Rise
(F) DB
37
Table 25 — 50PSH, PSV, PSD030 Typical Unit Operating Pressures and Temperatures
ENTERING
WATER
TEMP
(F)
30
50
70
90
110
DB Dry Bulb HWG — Hot Water Generator ——No Heating Operation in This Temperature Range
WATER
FLOW
(GPM/ton)
1.5 116-126 146-166 27-32 7-13 19.6-21.6 16-22 69- 79 275-295 7-12 6-11 7.2- 9.2 16-22
2.25 115-125 138-158 27-32 6-11 14.3-16.3 17-23 73- 83 277-297 7-12 6-11 5.4- 7.4 17-23 3 115-125 128-148 27-32 6-11 8.0-10.0 17-23 76- 86 279-299 7-12 6-11 3.5- 5.5 17-23
1.5 129-139 217-237 12-17 6-11 20.8-22.8 17-23 96-106 300-320 10-15 9-14 10.5-12.5 21-27
2.25 128-138 203-223 12-17 5-10 15.0-17.0 18-24 100-110 304-324 10-15 9-14 7.6- 9.6 22-28 3 128-138 189-209 12-17 5-10 9.2-11.2 18-24 105-115 309-329 10-15 9-14 4.8- 6.8 22-28
1.5 132-142 293-313 9-14 6-11 20.1-22.1 17-23 123-133 327-347 11-16 11-16 13.2-15.2 25-32
2.25 131-141 274-294 9-14 5-10 14.4-16.4 18-24 129-139 333-353 11-16 11-16 9.8-11.8 26-33 3 131-141 256-276 9-14 5-10 8.6-10.6 18-24 135-145 339-359 11-16 11-16 6.4- 8.4 27-34
1.5 137-147 383-403 7-12 5-10 19.4-21.4 16-22 155-165 355-375 13-18 11-16 16.8-18.8 30-38
2.25 137-147 362-382 7-12 5-10 13.8-15.8 16-22 162-172 362-382 14-19 11-16 12.7-14.7 31-39 3 137-147 342-362 7-12 5-10 8.2-10.2 16-22 169-179 369-389 16-21 11-16 8.6-10.6 32-40
1.5 143-153 475-495 6-11 9-14 18.2-20.2 16-22
2.25 143-153 457-477 6-11 6-11 13.0-14.0 16-22 — 3 143-153 439-459 6-11 6-11 7.7- 9.7 16-22
LEGEND
FULL LOAD COOLING — WITHOUT HWG ACTIVE FULL LOAD HEATING — WITHOUT HWG ACTIVE
Suction
Pressure
(psig)
Discharge
Pressure
(psig)
Super-
heat
(F)
Table 26 — 50PSH, PSV, PSD036 Typical Unit Operating Pressures and Temperatures
ENTERING
WATER
TEMP
(F)
30
50
70
90
110
DB Dry Bulb HWG — Hot Water Generator ——No Heating Operation in This Temperature Range
WATER
FLOW
(GPM/ton)
1.5 117-127 142-162 33-38 8-14 19.1-21.1 15-22 69- 79 276-296 10-15 10-15 7.2- 9.2 17-23
2.25 116-126 134-154 33-38 7-12 13.8-15.8 15-22 73- 83 278-298 10-15 10-15 5.3- 7.3 18-24 3 116-126 124-144 33-38 7-12 7.4- 9.4 15-22 76- 86 280-300 10-15 10-15 3.5- 5.5 18-24
1.5 136-146 211-231 11-16 6-11 20.6-22.6 17-23 99-109 302-322 10-15 13-18 10.6-12.6 22-28
2.25 136-146 197-217 11-16 5-10 14.8-16.8 17-23 103-113 306-326 10-15 13-18 7.7- 9.7 23-29 3 136-146 183-203 11-16 5-10 9.0-11.0 17-23 108-118 311-331 10-15 13-18 5.0- 7.0 23-29
1.5 137-147 275-295 9-14 10-15 19.0-21.0 18-24 127-137 332-352 10-15 15-20 13.5-15.5 27-34
2.25 137-147 260-280 9-14 9-14 13.8-15.8 19-25 133-143 338-358 10-15 15-20 10.1-12.1 28-35 3 137-147 245-265 9-14 9-14 8.0-10.0 19-25 139-149 344-364 10-15 15-20 6.7- 8.7 29-36
1.5 142-152 373-393 7-12 10-15 19.5-21.5 17-23 164-174 365-385 11-16 15-20 17.4-19.4 34-42
2.25 142-152 352-372 8-13 6-11 13.9-15.9 17-23 172-182 372-392 11-16 15-20 13.2-15.2 35-43 3 142-152 332-352 8-13 6-11 8.3-10.3 17-23 181-191 379-399 12-17 15-20 9.0-11.0 36-44
1.5 147-157 467-487 6-11 10-15 16.2-18.2 16-22
2.25 147-157 448-468 6-11 8-13 11.9-13.9 16-22 — 3 147-157 430-450 6-11 7-12 7.6- 9.6 16-22
LEGEND
FULL LOAD COOLING — WITHOUT HWG ACTIVE FULL LOAD HEATING — WITHOUT HWG ACTIVE
Suction
Pressure
(psig)
Discharge
Pressure
(psig)
Super-
heat
(F)
Sub-
cooling
(F)
Sub-
cooling
(F)
Water Tem p
Rise
(F)
Wate r
Tem p
Rise
(F)
Air Temp
Drop
(F) DB
Air Temp
Drop
(F) DB
Suction
Pressure
(psig)
Suction
Pressure
(psig)
Discharge
Pressure
(psig)
Discharge
Pressure
(psig)
Super-
heat
(F)
Super-
heat
(F)
Sub-
cooling
(F)
Sub-
cooling
(F)
Wate r Temp
Drop
(F)
Wate r Tem p
Drop
(F)
Air Temp
Rise
(F) DB
Air Temp
Rise
(F) DB
Table 27 — 50PSH, PSV, PSD042 Typical Unit Operating Pressures and Temperatures
ENTERING
WATER
TEMP
(F)
30
50
70
90
110
LEGEND
DB Dry Bulb HWG — Hot Water Generator ——No Heating Operation in This Temperature Range
WATER
FLOW
(GPM/ton)
1.5 114-124 170-190 27-32 10-15 17.2-19.2 17-23 69- 79 286-306 5-10 5-10 4.5- 6.5 16-22
2.25 113-123 150-170 27-32 9-14 12.7-14.7 17-23 72- 82 289-309 5-10 6-11 3.9- 5.9 17-23 3 113-123 131-151 27-32 7-12 8.2-10.2 17-23 75- 85 292-312 6-11 6-11 3.2- 5.2 18-24
1.5 130-140 226-246 10-15 6-11 17.8-19.8 20-26 100-110 315-335 7-12 6-11 9.0-11.0 22-28
2.25 129-139 208-228 10-15 5-10 13.3-15.3 20-26 105-115 322-342 8-13 6-11 7.0- 9.0 23-29 3 129-139 190-210 10-15 4- 9 8.8-10.8 20-26 110-120 330-350 10-15 7-12 5.0- 7.0 24-30
1.5 132-142 290-310 6-11 6-11 17.3-19.3 19-25 131-141 347-367 11-16 6-11 13.4-15.4 29-35
2.25 131-141 273-293 6-11 5-10 12.8-14.8 19-25 138-148 358-378 13-18 8-13 10.0-12.0 30-36 3 131-141 255-275 6-11 4- 9 8.3-10.3 19-25 145-155 369-389 16-21 9-14 6.9- 8.9 31-37
1.5 136-146 370-390 6-11 6-11 16.0-18.0 17-23 175-185 393-413 19-24 7-12 17.6-19.6 36-42
2.25 135-145 350-370 6-11 5-10 11.8-13.8 17-23 177-187 401-421 20-25 9-14 13.2-15.2 37-43 3 135-145 330-350 6-11 4- 9 7.6- 9.6 17-23 180-190 409-429 22-27 12-17 8.7-10.7 38-44
1.5 143-153 469-489 6-11 6-11 14.0-16.0 16-22
2.25 142-152 448-468 6-11 5-10 11.0-13.0 16-22 — 3 141-151 427-447 6-11 4- 9 7.0- 9.0 16-22
FULL LOAD COOLING — WITHOUT HWG ACTIVE FULL LOAD HEATING — WITHOUT HWG ACTIVE
Suction
Pressure
(psig)
Discharge
Pressure
(psig)
Super-
heat
(F)
Sub-
cooling
(F)
Water Tem p
Rise
(F)
38
Air Temp
Drop
(F) DB
Suction
Pressure
(psig)
Discharge
Pressure
(psig)
Super-
heat
(F)
Sub-
cooling
(F)
Wate r Tem p
Drop
(F)
Air Temp
Rise
(F) DB
Table 28 — 50PSH, PSV, PSD048 Typical Unit Operating Pressures and Temperatures
ENTERING
WATER
TEMP
(F)
30
50
70
90
110
DB Dry Bulb HWG — Hot Water Generator ——No Heating Operation in This Temperature Range
WATER
FLOW
(GPM/ton)
1.5 108-118 180-200 27-32 12-17 19.8-21.8 19-25 65- 75 293-313 7-12 9-14 8.2-10.2 17-23
2.25 107-117 161-181 28-33 10-15 14.8-16.8 19-25 68- 78 297-217 8-13 9-14 6.2- 8.2 18-24 3 107-117 142-162 29-34 9-14 9.8-11.8 19-25 72- 82 301-321 9-14 9-14 4.2- 6.2 19-25
1.5 123-133 236-256 16-21 8-13 20.2-22.2 21-27 92-102 321-341 10-15 11-16 11.6-13.6 23-29
2.25 122-132 218-238 17-22 7-12 15.2-18.2 21-27 100-110 330-350 11-16 11-16 8.9-10.9 24-30 3 122-132 200-220 17-22 6-11 10.2-12.2 21-27 108-118 340-360 12-17 11-16 6.0- 8.0 26-32
1.5 130-140 305-325 10-15 8-13 20.0-22.0 20-26 122-132 353-373 12-17 11-16 15.0-17.0 29-35
2.25 129-139 285-305 11-16 6-11 15.0-17.0 20-26 133-143 365-385 14-19 11-16 11.5-13.5 31-37 3 129-139 265-285 11-16 5-10 10.0-12.0 20-26 144-154 378-398 16-21 11-16 8.0-10.0 33-39
1.5 133-143 390-410 8-13 8-13 19.0-21.0 19-25 166-176 397-417 16-21 9-14 19.5-21.5 37-43
2.25 132-142 368-388 9-14 6-11 14.0-16.0 19-25 173-183 407-727 18-23 9-14 14.7-16.7 38-44 3 132-142 345-365 9-14 5-10 9.0-11.0 19-25 181-191 417-437 19-24 10-15 9.9-11.9 40-46
1.5 141-151 497-517 6-11 8-13 18.0-20.0 18-24
2.25 140-150 472-492 7-12 6-11 13.5-15.5 18-24 — 3 140-150 447-467 8-13 5-10 8.7-10.7 18-24
LEGEND
FULL LOAD COOLING — WITHOUT HWG ACTIVE FULL LOAD HEATING — WITHOUT HWG ACTIVE
Suction
Pressure
(psig)
Discharge
Pressure
(psig)
Super-
heat
(F)
Table 29 — 50PSH, PSV, PSD060 Typical Unit Operating Pressures and Temperatures
Sub-
cooling
(F)
Water
Tem p
Rise
(F)
Air Temp
Drop
(F) DB
Suction
Pressure
(psig)
Discharge
Pressure
(psig)
Super-
heat
(F)
Sub-
cooling
(F)
Wate r Temp
Drop
(F)
Air Temp
Rise
(F) DB
ENTERING
WATER
TEMP
(F)
30
50
70
90
110
DB Dry Bulb HWG — Hot Water Generator ——No Heating Operation in This Temperature Range
WATER
FLOW
(GPM/ton)
1.5 98-108 160-180 40-45 12-17 20.0-22.0 19-25 62- 72 276-296 6-11 6-11 8.0-10.0 17-23
2.25 97-107 149-169 41-46 12-17 14.3-16.3 19-25 66- 76 280-300 6-11 6-11 6.0- 8.0 18-24 3 96-106 137-157 42-48 11-16 8.5-10.5 20-26 70- 80 284-304 7-12 6-11 4.0- 6.0 19-25
1.5 118-128 225-245 36-41 11-16 21.2-23.2 19-25 88- 98 306-326 10-15 8-13 11.0-13.0 23-29
2.25 117-127 210-230 37-42 10-15 15.7-17.7 20-26 94-104 311-331 10-15 8-13 8.3-10.3 24-30 3 115-125 195-215 38-43 9-14 10.2-12.2 21-27 100-110 317-337 11-16 9-14 5.5- 7.5 25-31
1.5 135-145 300-320 12-17 9-14 20.3-22.3 21-27 112-122 333-353 12-17 10-15 14.0-16.0 28-34
2.25 133-143 285-305 14-19 8-13 15.0-17.0 21-27 122-132 342-362 14-19 10-15 10.5-12.5 30-36 3 132-142 270-290 16-21 7-12 10.0-12.0 22-28 130-140 351-371 15-20 11-16 7.3- 9.3 32-38
1.5 139-149 390-410 8-13 7-12 19.3-21.3 20-26 147-157 369-389 15-20 10-15 17.7-19.7 36-42
2.25 138-148 370-390 8-13 6-11 14.3-16.3 21-27 154-164 377-397 18-23 10-15 13.4-15.4 37-43 3 138-148 350-370 8-13 6-11 9.3-11.3 21-27 160-170 385-405 19-24 11-16 9.0-11.0 38-44
1.5 144-154 488-508 8-13 8-13 18.4-20.4 21-27
2.25 143-153 468-488 7-12 6-11 13.6-15.6 21-27 — 3 142-152 448-468 7-12 5-10 8.8-10.8 21-27
LEGEND
FULL LOAD COOLING — WITHOUT HWG ACTIVE FULL LOAD HEATING — WITHOUT HWG ACTIVE
Suction
Pressure
(psig)
Discharge
Pressure
(psig)
Super-
heat
(F)
Table 30 — 50PSH, PSV, PSD070 Typical Unit Operating Pressures and Temperatures
ENTERING
WATER
TEMP
(F)
30
50
70
90
110
LEGEND
DB Dry Bulb HWG — Hot Water Generator ——No Heating Operation in This Temperature Range
WATER
FLOW
(GPM/ton)
1.5 110-120 177-197 36-41 15-20 20.2-22.2 21-27 61- 71 290-310 12-18 9-14 8.0-10.0 19-25
2.25 109-119 162-182 37-42 13-18 15.0-17.0 21-27 65- 75 292-312 12-18 10-15 6.0- 8.0 20-26 3 107-117 147-167 38-43 11-16 9.7-11.7 22-28 68- 78 296-316 12-18 10-15 4.0- 6.0 21-27
1.5 128-138 246-266 18-23 11-16 21.0-23.0 22-28 88- 98 320-340 11-17 13-18 11.7-13.7 26-32
2.25 128-138 228-248 19-24 9-14 15.6-17.6 23-29 96-106 330-350 11-17 11-16 9.0-11.0 27-33 3 127-137 210-230 20-25 6-11 10.2-12.2 24-30 105-115 338-358 11-17 9-14 6.0- 8.0 29-35
1.5 134-144 305-325 9-14 11-16 20.8-22.8 23-29 118-128 355-375 10-16 14-19 15.2-17.2 33-39
2.25 133-143 289-309 9-14 9-14 15.4-17.4 23-29 130-140 368-388 12-18 13-18 11.7-13.7 35-41 3 131-141 273-293 9-14 6-11 10.0-12.0 23-29 141-151 380-400 15-21 11-16 8.0-10.0 37-43
1.5 140-150 390-410 10-15 11-16 19.6-21.6 22-28 158-168 401-421 9-15 13-18 19.5-21.5 41-47
2.25 139-149 373-393 10-15 9-14 14.5-16.5 22-28 168-178 412-432 10-16 12-17 14.8-16.8 43-49 3 138-148 355-375 10-15 6-11 9.3-11.3 22-28 178-188 423-443 12-18 12-17 10.0-12.0 45-51
1.5 144-154 488-508 10-15 9-14 18.4-20.4 20-27
2.25 143-153 468-488 10-15 6-11 13.6-15.6 20-27 — 3 142-152 448-468 9-14 5-10 8.8-10.8 20-27
FULL LOAD COOLING — WITHOUT HWG ACTIVE FULL LOAD HEATING — WITHOUT HWG ACTIVE
Suction
Pressure
(psig)
Discharge
Pressure
(psig)
Super-
heat
(F)
Sub-
cooling
(F)
Sub-
cooling
(F)
Water
Tem p
Rise
(F)
Wate r
Tem p
Rise
(F)
Air Temp
Drop
(F) DB
Air Temp
Drop
(F) DB
Suction
Pressure
(psig)
Suction
Pressure
(psig)
Discharge
Pressure
(psig)
Discharge
Pressure
(psig)
Super-
heat
(F)
Super-
heat
(F)
Sub-
cooling
(F)
Sub-
cooling
(F)
Wate r Tem p
Drop
(F)
Wate r
Tem p
Drop
(F)
Air Temp
Rise
(F) DB
Air Temp
Rise
(F) DB
39
Unit Start-Up with WSHP Open Controls
The WSHP Open is a multi-protocol (default BACnet*) con­troller with extensive features, flexible options and powerful capabilities. The unit comes from the factory pre-programmed and needs minimal set up to function in a BAS (Building Auto­mation System) system or provide additional capabilities to Carrier's WSHP product line. Most settings on the controller have factory defaults set for ease of installation. There are a few settings that must be configured in the field and several set­tings that can be adjusted if required by unique job conditions. Refer to Appendix A — WSHP Open Screen Configuration. In order to configure the unit, a BACview Fig. 35.
NOTE: If the WSHP Open control has lost its programming, all display pixels will be displayed on the SPT sensor. See the WSHP Third Party Integration Guide.
When the unit is OFF, the SPT sensor will indicate OFF. When power is applied, the SPT sensor will indicate tempera­ture in the space at 78 F.
To start-up a unit with WSHP Open controls:
1. To plug in the BACview sensor, point the two ears on the connector up and tilt the bottom of the plug toward you. Insert the plug up into the SPT sensor while pushing the bottom of the plug away from you.
2. BACview
6
should respond with "Establishing Connec­tion." The Home screen will then appear on the display showing operating mode and space temperature. Press any button to continue.
See Appendix A — WSHP Open Screen Configuration for the hierarchal structure of the WSHP Open controller. All functions of the controller can be set from the Home screen.
3. When the Login is requested, type 1111 and push the OK softkey. The Logout will then be displayed to indicate the password was accepted.
4. To set the Clock if it is not already displayed: a. Select System Settings from the Home screen, then
press Clockset.
b. Scroll to hour, minute and second using the arrow
keys. Use the number keypad to set actual time.
c. Scroll to day, month and year using arrow keys.
Use number keypad to set date.
5. To set Daylight Savings Time (DST): a. Push the DST softkey. The display will indicate
02:00:060 which is equal to 2:00AM.
6
display is required. See
6
handheld display into a SPT
b. To program the beginning and end dates, scroll
down to the beginning month and press the enter key. The softkeys (INCR and DECR) will activate to increment the month in either direction, Jan, Feb, March, etc.
c. Use number keys to select the day of month and
year.
d. Push the OK softkey to finalize the data.
6. To view configuration settings: a. Select the Config softkey. b. Select the Service Config softkey. Scroll through
the factory settings by using the up and down arrow keys. See below for factory settings.
Only the following settings will need to be checked.
• # of Fan Speeds — This should be set to "1" for units with PSC motors and set to "3" for units with ECM motors.
• Compressor Stages — This should be set to "1."
• Factory Dehumidification Reheat Coil — This should be set to "none" unless the modulating hot water reheat option is supplied in the unit, then set to "installed."
• The condenser water limit needs to be verified depending on design parameters and application, whether geothermal or boiler/tower.
7. To view unit configuration settings: a. Select the Unit Configuration softkey, then select
Unit.
b. Scroll through the unit settings by using the up and
down arrow keys. Unit settings include:
• Fan Mode: Default Continuous
• Fan Delay:
• Minimum SAT Cooling: Default 50 F
• Maximum SAT Heating: Default 110 F
• Filter Service Alarm: Must be set from 0 to 9999 hr
8. To set local schedules: a. Select the Schedule softkey from the Configuration
screen, then press enter.
b. Select Weekly, then press enter (7 schedules
available). c. Select day and press enter. d. Press enter again and select ADD or DEL (DECR
or INCR) set schedule. e. Enter ON/OFF time, then press continue.
Fig. 35 — BACview6 Display Interface
*Sponsored by ASHRAE (American Society of Heating, Refrigerat­ing and Air Conditioning Engineers).
a50-8444
40
f. Press OK to apply and save to a particular day of
the week.
g. Continue to add the same or different schedule spe-
cific days of the week. To add exceptions to the schedule: i. Press Add softkey. ii. Select exception type from following:
• Date
• Date Range
• Week-N-Day
• Calender Reference
9. Go back to Home Screen.
10. Remove BACview
6
cable from SPT sensor by reversing
the process in Step 1.
11. Perform system test.
Flow Regulation — Flow regulation can be accom-
plished by two methods. Most water control valves have a flow adjustment built into the valve. By measuring the pressure drop through the unit heat exchanger, the flow rate can be deter­mined. See Table 31. Adjust the water control valve until the flow of 1.5 to 2 gpm is achieved. Since the pressure constantly varies, two pressure gages may be needed in some applications.
Table 31 — 50PSH, PSV, PSD Coaxial
Water Pressure Drop
50PSH, PSV, PSD
UNIT SIZE
006
009
012
018
024
030
036
042
048
060
070
WATER
FLOW (GPM)
1.0 0.3 0.3 0.2 0.2
1.5 1.6 1.4 1.2 1.0
2.0 3.0 2.6 2.2 1.8
1.4 0.8 0.7 0.6 0.6
2.1 1.5 1.4 1.2 1.1
2.8 2.7 2.4 2.2 1.9
1.8 0.6 0.5 0.4 0.3
2.6 2.1 1.9 1.6 1.4
3.5 3.8 3.4 3.0 2.6
2.8 0.7 0.5 0.3 0.2
4.1 2.1 1.7 1.4 1.1
5.5 3.5 2.8 2.4 2.0
4.0 1.5 1.3 1.1 1.0
6.0 3.1 2.6 2.3 2.1
8.0 5.1 4.3 3.8 3.4
4.0 1.5 1.3 1.1 1.0
6.0 3.1 2.6 2.3 2.1
8.0 5.1 4.3 3.8 3.4
4.5 1.7 1.3 1.1 0.9
6.8 3.3 3.1 2.9 2.6
9.0 5.7 5.2 4.8 4.4
5.5 1.1 0.9 0.8 0.7
8.3 2.2 2.1 2.0 1.8
11.0 3.9 3.6 3.2 3.1
6.0 1.3 1.1 1.0 0.9
9.0 2.6 2.5 2.3 2.2
12.0 4.5 4.2 3.8 3.5
7.5 0.6 0.4 0.3 0.2
11.3 2.3 2.1 2.0 1.8
15.0 4.8 4.3 3.9 3.5
8.3 2.4 2.0 1.7 1.6
12.4 5.2 4.5 4.0 3.8
16.5 8.0 7.0 6.3 6.0
An alternative method is to install a flow control device. These devices are typically an orifice of plastic material de­signed to allow a specified flow rate that are mounted on the outlet of the water control valve. Occasionally these valves produce a velocity noise that can be reduced by applying some back pressure. To accomplish this, slightly close the leaving isolation valve of the well water setup.
WATER TEMPERATURE (F)
30 F 50 F 70 F 90 F
Pressure Drop (psi)
WARNING
To avoid possible injury or death due to electrical shock, open the power supply disconnect switch and secure it in an open position before flushing system.
Flushing — Once the piping is complete, units require final
purging and loop charging. A flush cart pump of at least 1.5 hp is needed to achieve adequate flow velocity in the loop to purge air and dirt particles from the loop. Flush the loop in both direc­tions with a high volume of water at a high velocity. Follow the steps below to properly flush the loop:
1. Verify power is off.
2. Fill loop with water from hose through flush cart before using flush cart pump to ensure an even fill. Do not allow the water level in the flush cart tank to drop below the pump inlet line in order to prevent air from filling the line.
3. Maintain a fluid level in the tank above the return tee in order to avoid air entering back into the fluid.
4. Shutting off the return valve that connects into the flush cart reservoir will allow 50 psig surges to help purge air pockets. This maintains the pump at 50 psig.
5. To purge, keep the pump at 50 psig until maximum pumping pressure is reached.
6. Open the return valve to send a pressure surge through the loop to purge any air pockets in the piping system.
7. A noticeable drop in fluid level will be seen in the flush cart tank. This is the only indication of air in the loop.
NOTE: If air is purged from the system while using a 10 in. PVC flush tank, the level drop will only be 1 to 2 in. since liquids are incompressible. If the level drops more than this, flushing should continue since air is still being compressed in the loop. If level is less than 1 to 2 in., reverse the flow.
8. Repeat this procedure until all air is purged.
9. Restore power.
Antifreeze may be added before, during, or after the flush­ing process. However, depending on when it is added in the process, it can be wasted. Refer to the Antifreeze section for more detail.
Loop static pressure will fluctuate with the seasons. Pres­sures will be higher in the winter months than during the warm­er months. This fluctuation is normal and should be considered when charging the system initially. Run the unit in either heating or cooling for several minutes to condition the loop to a homogenous temperature.
When complete, perform a final flush and pressurize the loop to a static pressure of 40 to 50 psig for winter months or 15 to 20 psig for summer months.
After pressurization, be sure to remove the plug from the end of the loop pump motor(s) to allow trapped air to be discharged and to ensure the motor housing has been flooded. Be sure the loop flow center provides adequate flow through the unit by checking pressure drop across the heat exchanger. Compare the results to the data in Table 31.
Antifreeze — In areas where entering loop temperatures
drop below 40 F or where piping will be routed through areas subject to freezing, antifreeze is needed.
Alcohols and glycols are commonly used as antifreeze agents. Freeze protection should be maintained to 15 F below the lowest expected entering loop temperature. For example, if the lowest expected entering loop temperature is 30 F, the leav­ing loop temperature would be 22 to 25 F. Therefore, the freeze protection should be at 15 F (30 F – 15 F = 15 F).
41
IMPORTANT: All alcohols should be pre-mixed and pumped from a reservoir outside of the building or introduced under water level to prevent fuming.
Calculate the total volume of fluid in the piping system. See Table 32. Use the percentage by volume in Table 33 to deter­mine the amount of antifreeze to use. Antifreeze concentration should be checked from a well-mixed sample using a hydrom­eter to measure specific gravity.
FREEZE PROTECTION SELECTION — The 30 F FP1 factory setting (water) should be used to avoid freeze damage to the unit.
Once antifreeze is selected, the JW3 jumper (FP1) should be clipped on the control to select the low temperature (anti­freeze 13 F) set point to avoid nuisance faults.
Table 32 — Approximate Fluid Volume (gal.)
per 100 Ft of Pipe
PIPE DIAMETER (in.) VOLUME (gal.)
Copper 14.1
Rubber Hose 13.9 Polyethylene
LEGEND
IPS Internal Pipe Size SCH — Schedule SDR — Standard Dimensional Ratio
NOTE: Volume of heat exchanger is approximately 1.0 gallon.
1.25 6.4
1.5 9.2
3
/4 IPS SDR11 2.8 1 IPS SDR11 4.5 11/4 IPS SDR11 8.0
1
/2 IPS SDR11 10.9 2 IPS SDR11 18.0 11/4 IPS SCH40 8.3 11/2 IPS SCH40 10.9 2 IPS SCH40 17.0
Table 33 — Antifreeze Percentages by Volume
MINIMUM TEMPERATURE FOR
ANTIFREEZE
Methanol (%) 25 21 16 10 100% USP Food Grade
Propylene Glycol (%) Ethanol (%) 29 25 20 14
FREEZE PROTECTION (F)
10 15 20 25
38 30 22 15
Cooling Tower/Boiler Systems — These systems
typically use a common loop temperature maintained at 60 to 95 F. Carrier recommends using a closed circuit evaporative cooling tower with a secondary heat exchanger between the tower and the water loop. If an open type cooling tower is used continuously, chemical treatment and filtering will be necessary.
Ground Coupled, Closed Loop and Plateframe Heat Exchanger Well Systems —
low water temperatures from 30 to 110 F. The external loop field is divided up into 2 in. polyethylene supply and return lines. Each line has valves connected in such a way that upon system start-up, each line can be isolated for flushing using only the system pumps. Locate air separation in the piping sys­tem prior to the fluid re-entering the loop field.
These systems al-
OPERATION
Power Up Mode —
inputs, terminals and safety controls are checked for normal operation.
NOTE: The compressor will have a 5-minute anti-short cycle upon power up.
The unit will not operate until all the
Units with Aquazone™ Complete C Control
STANDBY — Y and W terminals are not active in Standby mode, however the O and G terminals may be active, depend­ing on the application. The compressor will be off.
COOLING — Y and O terminals are active in Cooling mode. After power up, the first call to the compressor will initiate a 5 to 80 second random start delay and a 5-minute anti-short cycle protection time delay. After both delays are complete, the compressor is energized.
NOTE: On all subsequent compressor calls the random start delay is omitted.
HEATING STAGE 1 — Terminal Y is active in heating stage 1. After power up, the first call to the compressor will initiate a 5 to 80 second random start delay and a 5-minute anti-short cycle protection time delay. After both delays are complete, the compressor is energized.
NOTE: On all subsequent compressor calls the random start delay is omitted.
HEATING STAGE 2 — To enter Stage 2 mode, terminal W is active (Y is already active). Also, the G terminal must be active or the W terminal is disregarded. The compressor relay will remain on and EH1 is immediately turned on. EH2 will turn on after 10 minutes of continual stage 2 demand.
NOTE: EH2 will not turn on (or if on, will turn off) if FP1 tem­perature is greater than 45 F and FP2 is greater than 110 F.
LOCKOUT MODE — The status LED will flash fast in Lockout mode and the compressor relay will be turned off immediately. Lockout mode can be “soft” reset via the Y input or can be “hard” reset via the disconnect. The last fault causing the lockout is stored in memory and can be viewed by entering test mode.
LOCKOUT WITH EMERGENCY HEAT — While in Lock­out mode, if W becomes active, then Emergency Heat mode will occur.
EMERGENCY HEAT — In Emergency Heat mode, terminal W is active while terminal Y is not. Terminal G must be active or the W terminal is disregarded. EH1 is immediately turned on. EH2 will turn on after 5 minutes of continual emergency heat demand.
Units with Aquazone Deluxe D Control
EXTENDED COMPRESSOR OPERATION MONITOR — If the compressor has been on for 4 continuous hours the con­trol will automatically turn off the compressor relay and wait the short cycle time protection time. All appropriate safeties, including the low-pressure switch, will be monitored. If all operations are normal and the compressor demand is still present, the control will turn the compressor back on.
STANDBY/FAN ONLY — The compressor will be off. The Fan Enable, Fan Speed, and reversing valve (RV) relays will be on if inputs are present. If there is a Fan 1 demand, the Fan Enable will immediately turn on. If there is a Fan 2 demand, the Fan Enable and Fan Speed will immediately turn on.
NOTE: DIP switch 5 on S1 does not have an effect upon Fan 1 and Fan 2 outputs.
HEATING STAGE 1 — In Heating Stage 1 mode, the Fan Enable and Compressor relays are turned on immediately. Once the demand is removed, the relays are turned off and the control reverts to Standby mode. If there is a master/slave or dual compressor application, all compressor relays and related functions will operate per their associated DIP switch 2 setting on S1.
HEATING STAGE 2 — In Heating Stage 2 mode, the Fan Enable and Compressor relays are remain on. The Fan Speed relay is turned on immediately and turned off immediately once the demand is removed. The control reverts to Heating Stage 1 mode. If there is a master/slave or dual compressor
42
application, all compressor relays and related functions will operate per their associated DIP switch 2 setting on S1.
HEATING STAGE 3 — In Heating Stage 3 mode, the Fan Enable, Fan Speed and Compressor relays remain on. The EH1 output is turned on immediately. With continuing Heat Stage 3 demand, EH2 will turn on after 10 minutes. EH1 and EH2 are turned off immediately when the Heating Stage 3 demand is re­moved. The control reverts to Heating Stage 2 mode.
The output signal EH2 will be off if FP1 is greater than 45 F AND FP2 (when shorted) is greater than 110 F during Heating Stage 3 mode. This condition will have a 30-second recognition time. Also, during Heating Stage 3 mode, EH1, EH2, Fan Enable, and Fan Speed will be ON if G input is not active.
EMERGENCY HEAT — In Emergency Heat mode, the Fan Enable and Fan Speed relays are turned on. The EH1 output is turned on immediately. With continuing Emergency Heat de­mand, EH2 will turn on after 5 minutes. Fan Enable and Fan Speed relays are turned off after a 60-second delay. The control reverts to Standby mode.
Output EH1, EH2, Fan Enable, and Fan Speed will be ON if the G input is not active during Emergency Heat mode.
COOLING STAGE 1 — In Cooling Stage 1 mode, the Fan Enable, compressor and RV relays are turned on immediately. If configured as stage 2 (DIP switch set to OFF) then the com­pressor and fan will not turn on until there is a stage 2 demand. The Fan Enable and compressor relays are turned off immedi­ately when the Cooling Stage 1 demand is removed. The con­trol reverts to Standby mode. The RV relay remains on until there is a heating demand. If there is a master/slave or dual compressor application, all compressor relays and related func­tions will track with their associated DIP switch 2 on S1.
COOLING STAGE 2 — In Cooling Stage 2 mode, the Fan Enable, compressor and RV relays remain on. The Fan Speed relay is turned on immediately and turned off immediately once the Cooling Stage 2 demand is removed. The control reverts to Cooling Stage 1 mode. If there is a master/slave or dual compressor application, all compressor relays and related functions will track with their associated DIP switch 2 on S1.
NIGHT LOW LIMIT (NLL) STAGED HEATING — In NLL staged Heating mode, the override (OVR) input becomes ac­tive and is recognized as a call for heating and the control will immediately go into a Heating Stage 1 mode. With an addition­al 30 minutes of NLL demand, the control will go into Heating Stage 2 mode. With another additional 30 minutes of NLL demand, the control will go into Heating Stage 3 mode.
Units with HWR Option
FAN ONLY — A (G) call from the thermostat to the (G) terminal of the Deluxe D control board will bring the unit on in fan only mode.
COOLING STAGE 1 — A simultaneous call from (G), (Y1), and (O) to the (G), (Y1), (O/W2) terminals of the Deluxe D control board will bring the unit on in Cooling Stage 1.
COOLING STAGE 2 — A simultaneous call from (G), (Y1), (Y2), and (O) to the (G), (Y1), (Y2), and (O/W2) ter­minals of the Deluxe D control board will bring the unit on in Cooling Stage 2. When the call is satisfied at the thermo­stat the unit will continue to run in Cooling Stage 1 until the Cooling Stage 1 call is removed or satisfied, shutting down the unit.
NOTE: Not all units have two-stage cooling functionality. HEATING STAGE 1 — A simultaneous call from (G) and
(Y1) to the (G) and (Y1) terminals of the Deluxe D control board will bring the unit on in Heating Stage 1.
HEATING STAGE 2 — A simultaneous call from (G), (Y1), and (Y2) to the (G), (Y1), and (Y2) terminals of the Deluxe
D control board will bring the unit on in Heating Stage 2. When the call is satisfied at the thermostat the unit will con­tinue to run in Heating Stage 1 until the call is removed or satisfied, shutting down the unit.
NOTE: Not all units have two-stage heating functionality. REHEAT MODE — A call from the humidistat/dehumidis-
tat to the (H) terminal of the Deluxe D control board will bring the unit on in Reheat mode if there is no call for cool­ing at the thermostat. When the humidistat/dehumidistat call is removed or satisfied the unit will shut down.
NOTE: Cooling always overrides Reheat mode. In the Cooling mode, the unit cools and dehumidifies. If the cool­ing thermostat is satisfied but there is still a call for dehu­midification, the unit will continue to operate in Reheat mode.
Units with WSHP Open Multiple Protocol —
The WSHP Open multi-protocol controller will control me­chanical cooling, heating and waterside economizer outputs based on its own space temperature input and set points. An optional CO space can maximize the occupant comfort. The WSHP Open controller has its own hardware clock that is automatically set when the heat pump software is downloaded to the board. Oc­cupancy types are described in the scheduling section below. The following sections describe the functionality of the WSHP Open multi-protocol controller. All point objects referred to in this sequence of operation will be referenced to the objects as viewed in the BACview
SCHEDULING — Scheduling is used to start/stop the unit based on a time period to control the space temperature to spec­ified occupied heating and cooling set points. The controller is defaulted to control by occupied set points all the time, until ei­ther a time schedule is configured with BACview tant, i-Vu able the BAS (Building Automation System) on/off point. The local time and date must be set for these functions to operate properly. The occupancy source can be changed to one of the following:
Occupancy Schedules until a time schedule has been configured using either Field Assistant, i-Vu Open, BACview to enable/disable the BAS on/off point. The BAS point can be disabled by going to Config, then Unit, then Occupancy Sched­ules and changing the point from enable to disable then click­ing OK.
NOTE: This point must be enabled in order for the i-Vu Open, Field Assistant, or BACview schedule to the controller.
Schedule_schedule schedule configured and stored in the unit. The schedule is accessible via the BACview Field Assistant control system. The daily schedule consists of a start/stop time (standard or 24-hour mode) and seven days of the week, starting with Monday and ending on Sunday. To enter a daily schedule, navigate to Config, then Sched, then enter BACview schedule_schedule. From here, enter either a Weekly or Excep­tion schedule for the unit.
Occupancy Input Contact the capability to use an external dry contact closure to deter­mine the occupancy status of the unit. The Occupancy Sched­ules will need to be disabled in order to utilize the occupancy contact input.
NOTE: Scheduling can only be controlled from one source. BAS (Building Automation System) On/Off
system that supports network scheduling can control the unit through a network communication and the BAS scheduling function once the Occupancy Schedules have been disabled.
IAQ (indoor air quality) sensor mounted in the
2
6
handheld user interface.
6
®
Open, or a third party control system to enable/dis-
, Field Assis-
— The controller will be occupied 24/7
6
or a third party control system
6
control system to assign a time
— The unit will operate according to the
6
Handheld tool, i-Vu Open, or
6
Admin Password (1111), then go to
— The WSHP Open controller has
— A BAS
43
NOTE: Scheduling can either be controlled via the unit or the
°
BAS, but not both. INDOOR FAN — The indoor fan will operate in any one of
three modes depending on the user configuration selected.
Fan mode can be selected as Auto, Continuous, or Always On. In Auto mode, the fan is in intermittent operation during both occupied and unoccupied periods. Continuous fan mode is intermittent during unoccupied periods and continuous dur­ing occupied periods. Always On mode operates the fan con­tinuously during both occupied and unoccupied periods. In the default mode, Continuous, the fan will be turned on whenever any one of the following is true:
• The unit is in occupied mode as determined by its occu-
pancy status.
• There is a demand for cooling or heating in the unoccu-
pied mode.
• There is a call for dehumidification (optional).
When power is reapplied after a power outage, there will be a configured time delay of 5 to 600 seconds before starting the fan. There are also configured fan delays for Fan On and Fan Off. The Fan On delay defines the delay time (0 to 30 seconds; default 10) before the fan begins to operate after heating or cooling is started while the Fan Off delay defines the delay time (0 to 180 seconds; default 45) the fan will continue to op­erate after heating or cooling is stopped. The fan will continue to run as long as the compressors, heating stages, or the dehu­midification relays are on. If the SPT failure alarm or conden­sate overflow alarm is active; the fan will be shut down imme­diately regardless of occupancy state or demand.
Automatic Fan Speed Control is capable of controlling up to three fan speeds using the ECM (electronically commutated motor). The motor will operate at the lowest speed possible to provide quiet and efficient fan op­eration with the best latent capability. The motor will increase speed if additional cooling or heating is required to obtain the desired space temperature set point. The control increases the motor's speed as the space temperature rises above the cooling or below the heating set point. The amount of space tempera­ture increase above or below the set point required to increase the fan speed is user configurable in the set point. Also, the control will increase the fan speed as the supply-air tempera­ture approaches the configured minimum or maximum limits.
Fan Speed Control (During Heating) quired and active, the control continuously monitors the sup­ply-air temperature to verify it does not rise above the config­ured maximum heating SAT limit (110 F default). As the SAT approaches this value, the control will increase the fan speed as required to ensure the SAT will remain within the limit. This feature provides the most quiet and efficient operation by oper­ating the fan at the lowest speed possible.
Fan Speed Control (During Cooling) cal cooling is required and active, the control continuously monitors the supply-air temperature to verify it does not fall be­low the configured minimum cooling SAT limit (50 F default). As the SAT approaches this value, the control will increase the fan speed as required to ensure the SAT will remain within the limit. The fan will operate at lowest speed to maximize latent capacity during cooling.
COOLING — The WSHP Open controller will operate one or two stages of compression to maintain the desired cooling set point. The compressor outputs are controlled by the PI (propor­tional-integral) cooling loop and cooling stages capacity algo­rithm. They will be used to calculate the desired number of stages needed to satisfy the space by comparing the space tem­perature (SPT) to the appropriate cooling set point. The water side economizer, if applicable, will be used for first stage cool­ing in addition to the compressor(s). The following conditions must be true in order for the cooling algorithm to run:
• Cooling is set to Enable.
— The WSHP Open controller
— Whenever heat is re-
— Whenever mechani-
• Heating mode is not active and the compressor time guard has expired.
• Condensate overflow input is normal.
• If occupied, the SPT is greater than the occupied cooling set point.
• Space temperature reading is valid.
• If unoccupied, the SPT is greater than the unoccupied cooling set point.
• If economizer cooling is available and active and the economizer alone is insufficient to provide enough cool­ing.
• OAT (if available) is greater than the cooling lockout temperature.
If all the above conditions are met, the compressors will be
energized as required, otherwise they will be deenergized. If cooling is active and should the SAT approach the minimum SAT limit, the fan will be indexed to the next higher speed. Should this be insufficient and if the SAT falls further (equal to the minimum SAT limit), the fan will be indexed to the maxi­mum speed. If the SAT continues to fall 5 F below the mini­mum SAT limit, all cooling stages will be disabled.
During Cooling mode, the reversing valve output will be
held in the cooling position (either B or O type as configured) even after the compressor is stopped. The valve will not switch position until the Heating mode is required.
The configuration screens contain the minimum SAT
parameter as well as cooling lockout based on outdoor-air temperature (OAT) Both can be adjusted to meet various specifications.
There is a 5-minute off time for the compressor as well as a
5-minute time delay when staging up to allow the SAT to achieve a stable temperature before energizing a second stage of capacity. Likewise, a 45-second delay is used when staging down.
After a compressor is staged off, it may be restarted again
after a normal time-guard period of 5 minutes and if the sup­ply-air temperature has increased above the minimum supply­air temperature limit.
The WSHP Open controller provides a status input to moni-
tor the compressor operation. The status is monitored to deter­mine if the compressor status matches the commanded state. This input is used to determine if a refrigerant safety switch or other safety device has tripped and caused the compressor to stop operating normally. If this should occur, an alarm will be generated to indicate the faulted compressor condition.
HEATING — The WSHP Open controller will operate one or two stages of compression to maintain the desired heating set point. The compressor outputs are controlled by the heating PI (proportional-integral) loop and heating stages capacity algo­rithm. They will be used to calculate the desired number of stages needed to satisfy the space by comparing the space tem­perature (SPT) to the appropriate heating set point. The follow­ing conditions must be true in order for the heating algorithm to run:
• Heating is set to Enable.
• Cooling mode is not active and the compressor time guard has expired.
• Condensate overflow input is normal.
• If occupied, the SPT is less than the occupied heating set point.
• Space temperature reading is valid.
• If unoccupied, the SPT is less than the unoccupied heat­ing set point.
• OAT (if available) is less than the heating lockout temperature.
If all the above conditions are met, the heating outputs will
be energized as required, otherwise they will be deenergized. If the heating is active and should the SAT approach the maxi­mum SAT limit, the fan will be indexed to the next higher
44
speed. Should this be insufficient, and the SAT rises further
°
reaching the maximum heating SAT limit, the fan will be indexed to the maximum speed. If the SAT still continues to rise 5 F above the maximum limit, all heating stages will be disabled.
During Heating mode, the reversing valve output will be held in the heating position (either B or O type as configured) even after the compressor is stopped. The valve will not switch position until the Cooling mode is required.
The configuration screens contain the maximum SAT parameter as well as heating lockout based on outdoor-air temperature (OAT); both can be adjusted to meet various specifications.
There is a 5-minute off time for the compressor as well as a 5-minute time delay when staging up to allow the SAT to achieve a stable temperature before energizing a second stage of capacity. Likewise, a 45-second delay is used when staging down.
After a compressor is staged off, it may be restarted again after a normal time-guard period of 5 minutes and if the sup­ply-air temperature has fallen below the maximum supply air temperature limit.
The WSHP Open controller provides a status input to moni­tor the compressor operation. The status is monitored to deter­mine if the compressor status matches the commanded state. This input is used to determine if a refrigerant safety switch or other safety device has tripped and caused the compressor to stop operating normally. If this should occur, an alarm will be generated to indicate the faulted compressor condition. Also, if auxiliary heat is available (see below), the auxiliary heat will operate to replace the reverse cycle heating and maintain the space temperature as required.
AUXILIARY HEAT — The WSHP Open controller can con­trol a two-position, modulating water, or steam valve connect­ed to a coil on the discharge side of the unit and supplied by a boiler or a single-stage ducted electric heater in order to main­tain the desired heating set point. Should the compressor capac­ity be insufficient or a compressor failure occurs, the auxiliary heat will be used. Unless the compressor fails, the auxiliary heat will only operate to supplement the heat provided by the compressor if the space temperature falls more than one degree below the desired heating set point (the amount is config­urable). The heat will be controlled so the SAT will not exceed the maximum heating SAT limit.
Auxiliary Modulating Hot Water/Steam Heating Reheat — The control can modulate a hot water or steam valve con­nected to a coil on the discharge side of the unit and supplied by a boiler in order to maintain the desired heating set point should the compressor capacity be insufficient or a compressor failure occurs. Unless a compressor fault condition exists, the valve will only operate to supplement the heat provided by the compressor if the space temperature falls more than one degree below the desired heating set point. The valve will be con­trolled so the SAT will not exceed the maximum heating SAT limit.
Two-Position Hot Water/Steam Heating Reheat
The con-
trol can operate a two-position, NO or NC, hot water or steam valve connected to a coil on the discharge side of the unit and supplied by a boiler in order to maintain the desired heating set point should the compressor capacity be insufficient or a com­pressor failure occurs. Unless a compressor fault condition ex­ists, the valve will only open to supplement the heat provided by the compressor if the space temperature falls more than one degree below the desired heating set point. The valve will be controlled so the SAT will not exceed the maximum heating SAT limit. The heat stage will also be subject to a 2-minute minimum OFF time to prevent excessive valve cycling.
Single Stage Electric Auxiliary Heat
— The control can op-
erate a field-installed single stage of electric heat installed on
the discharge side of the unit in order to maintain the desired heating set point should the compressor capacity be insufficient or a compressor failure occurs. Unless a compressor fault con­dition exists, the heat stage will only operate to supplement the heat provided by the compressor if the space temperature falls more than one degree below the desired heating set point. The heat stage will be controlled so the SAT will not exceed the maximum heating SAT limit. The heat stage will also be sub­ject to a 2-minute minimum OFF time to prevent excessive cycling.
INDOOR AIR QUALITY (IAQ) AND DEMAND CON­TROLLED VENTILATION (DCV) — If the optional in­door air quality sensor is installed, the WSHP Open controller can maintain indoor air quality via a modulating OA damper providing demand controlled ventilation. The control operates the modulating OA damper during occupied periods. The con­trol monitors the CO set points, adjusting the ventilation rate as required. The control
level and compares it to the configured
2
provides proportional ventilation to meet the requirements of ASHRAE (American Society of Heating, Refrigerating and Air Conditioning Engineers) specifications by providing a base ventilation rate and then increasing the rate as the CO
level in-
2
creases. The control will begin to proportionally increase venti­lation when the CO point and will reach the full ventilation rate when the CO
level rises above the start ventilation set
2
level
2
is at or above the maximum set point. A user-configurable min­imum damper position ensures that proper base ventilation is delivered when occupants are not present. The IAQ configura­tions can be accessed through the configuration screen. The following conditions must be true in order for this algorithm to run:
• Damper control is configured for DCV.
• The unit is in an occupied mode.
• The IAQ sensor reading is greater than the DCV start control set point.
The control has four user adjustable set points: DCV start
control set point, DCV maximum control set point, minimum damper position, and DCV maximum damper position.
Two-Position OA Damper
— The control can be configured to operate a ventilation damper in a two-position ventilation mode to provide the minimum ventilation requirements during occupied periods.
DEHUMIDIFCATION — The WSHP Open controller will provide occupied and unoccupied dehumidification only on units that are equipped with the modulating hot water reheat (HWR) option. This function requires an accessory space rela­tive humidity sensor. When using a relative humidity sensor to control dehumidification during occupied or unoccupied times, the dehumidification set points are used accordingly. When the indoor relative humidity becomes greater than the dehumidifi­cation set point, a dehumidification demand will be acknowl­edged. Once acknowledged, the dehumidification output will be energized, bringing on the supply fan (medium speed), me­chanical cooling, and the integral hot water reheat coil. The controls will engage Cooling mode and waste heat from the compressor cooling cycle will be returned to the reheat coil si­multaneously, meaning that the reversing valve is causing the compressor to operate in the Cooling mode. During Cooling mode, the unit cools, dehumidifies, and disables the HWR coil; however, once the call for cooling has been satisfied and there is still a call for dehumidification, the unit will continue to op­erate using the Reheat mode and HWR coil.
WATERSIDE ECONOMIZER — The WSHP Open control­ler has the capability of providing modulating or two-position water economizer operation (for a field-installed economizer coil mounted to the entering air side of the unit and connected to the condenser water loop) in order to provide free cooling (or preheating) when water conditions are optimal. Water econ­omizer settings can be accessed through the equipment status
45
screen. The following conditions must be true for economizer
°
°
°
°
operation:
• SAT reading is available.
• LWT reading is available.
• If occupied, the SPT is greater than the occupied cooling set point or less than the occupied heating set point and the condenser water is suitable.
• Space temperature reading is valid.
• If unoccupied, the SPT is greater than the unoccupied cooling set point or less than the unoccupied heating set point and the condenser water is suitable.
Modulating Water Economizer Control
— The control has the capability to modulate a water valve to control condenser water flowing through a coil on the entering air side of the unit.
Cooling — The purpose is to provide an economizer cooling function by using the water loop when the entering water loop temperature is suitable (at least 5 F below space temperature). If the water loop conditions are suitable, then the valve will modulate open as required to maintain a supply-air temperature that meets the load conditions. Should the economizer coil ca­pacity alone be insufficient for a period greater than 5 minutes, or should a high humidity condition occur, then the compressor will also be started to satisfy the load. Should the SAT ap­proach the minimum cooling SAT limit, the economizer valve will modulate closed during compressor operation.
Heating — Additionally, the control will modulate the water valve should the entering water loop temperature be suitable for heating (at least 5 F above space temperature) and heat is required. The valve will be controlled in a similar manner ex­cept to satisfy the heating requirement. Should the economizer coil capacity alone be insufficient to satisfy the space load con­ditions for more than 5 minutes, then the compressor will be started to satisfy the load. Should the SAT approach the maxi­mum heating SAT limit, the economizer valve will modulate closed during compressor operation.
Two-Position Water Economizer Control
— The control has the capability to control a NO or NC, two-position water valve to control condenser water flow through a coil on the entering air side of the unit.
Cooling — The purpose is to provide a cooling economizer function directly from the condenser water loop when the en­tering water loop temperature is suitable (at least 5 F below space temperature). If the optional coil is provided and the wa­ter loop conditions are suitable, then the valve will open to pro­vide cooling to the space when required. Should the capacity be insufficient for a period greater than 5 minutes, or should a high humidity condition occur, then the compressor will be started to satisfy the load. Should the SAT reach the minimum cooling SAT limit, the economizer valve will close during compressor operation.
Heating — Additionally, the economizer control will open the water valve should the entering water loop temperature be suit­able for heating (at least 5 F above space temperature) and heat is required. The valve will be controlled in a similar man­ner except to satisfy the heating requirement. Should the coil capacity be insufficient to satisfy the space load for more than 5 minutes, then the compressor will be started to satisfy the load. Should the SAT reach the maximum heating SAT limit, the economizer valve will close during compressor operation.
DEMAND LIMIT — The WSHP Open controller has the ability to accept three levels of demand limit from the network. In response to a demand limit, the unit will decrease its heating set point and increase its cooling set point to widen the range in order to immediately lower the electrical demand. The amount of temperature adjustment in response is user adjustable for both heating and cooling and for each demand level. The re­sponse to a particular demand level may also be set to zero.
CONDENSER WATER LINKAGE — The control pro­vides optimized water loop operation using an universal
controller (UC) open loop controller. Loop pump operation is automatically controlled by WSHP equipment occupancy schedules, unoccupied demand and tenant override conditions. Positive pump status feedback prevents nuisance fault trips. The condenser water linkage operates when a request for con­denser water pump operation is sent from each WSHP to the loop controller. This request is generated whenever any WSHP is scheduled to be occupied, is starting during optimal start (for warm-up or pull down prior to occupancy), there is an unoccupied heating or cooling demand, or a tenant pushbutton override. At each WSHP, the water loop temperature and the loop pump status is given. The WSHP will NOT start a com­pressor until the loop pumps are running or will shutdown the compressors should the pumps stop. This prevents the WSHP from operating without water flow and thus tripping out on re­frigerant pressure, causing a lockout condition. The WSHP Open controller control will prevent this from occurring. Also, the loop controller can be configured to start the pumps only after a configurable number of WSHPs are requesting opera­tion (from 1-"N"). This can be used to prevent starting the en­tire loop operation for only one WSHP. Meanwhile, the WSHPs will not operate if the loop pump status is off and therefore the WSHP compressor will not run.
COMPLETE C AND DELUXE D BOARD
SYSTEM TEST
Test mode provides the ability to check the control opera­tion in a timely manner. The control enters a 20-minute test mode by momentarily shorting the test terminals. All time de­lays are sped up 15 times. The follow operations are common to both Complete C and Deluxe D controls.
Test Mode — To enter Test mode, cycle the power 3 times
within 60 seconds. The LED will flash a code representing the last fault when entering the Test mode. The alarm relay will also power on and off during Test mode. See Tables 34 and 35. To exit Test mode, short the terminals for 3 seconds or cycle the power 3 times within 60 seconds.
NOTE: The flashing code and alarm relay cycling code will both have the same numerical label. For example, flashing code 1 will have an alarm relay cycling code 1. Code 1 indi­cates the control has not faulted since the last power off to power on sequence.
Table 34 — Complete C Control Current LED
Status and Alarm Relay Operations
LED STATUS DESCRIPTION OF OPERATION ALARM RELAY
On
Off Complete C Control is non-functional Open
Slow Flash Fault Retry Open
Fast Flash Lockout Closed
Slow Flash Over/Under Voltage Shutdown
Flashing Code 1 Test Mode — No fault in memory Cycling Code 1 Flashing Code 2 Test Mode — HP Fault in memory Cycling Code 2 Flashing Code 3 Test Mode — LP Fault in memory Cycling Code 3 Flashing Code 4 Test Mode — FP1 Fault in memory Cycling Code 4 Flashing Code 5 Test Mode — FP2 Fault in memory Cycling Code 5 Flashing Code 6 Test Mode — CO Fault in memory Cycling Code 6
Flashing Code 7
Flashing Code 8 Test Mode — PM in memory Cycling Code 8
Flashing Code 9
CO — Condensate Overflow LED — Light-Emitting Diode FP — Freeze Protection LP Low Pressure HP — High Pressure PM — Performance Monitor
NOTES:
1. Slow flash is 1 flash every 2 seconds.
2. Fast flash is 2 flashes every 1 second.
3. EXAMPLE: “Flashing Code 2 is represented by 2 fast flashes followed by a 10-second pause. This sequence will repeat continually until the fault is cleared.
Normal Mode Open
Normal Mode with PM Warning
Test Mode — Over/Under
shutdown in memory
Test Mode — FP1/FP2
Swapped Fault in memory
LEGEND
Cycle (closed 5 sec.,
open 25 sec.)
Open, (Closed after
15 minutes)
Cycling Code 7
Cycling Code 9
46
Table 35 — Complete C Control LED Code and
Fault Descriptions
LED CODE FAULT DESCRIPTION
1 No fault in memory There has been no fault since the
2 High-Pressure Switch HP switch opens instantly 3 Low-Pressure Switch LP switch opens for 30 continu-
4 Freeze Protection Coax —
FP1
5 Freeze Protection Air Coil —
FP2
6 Condensate overflow Sense overflow (grounded) for
7
(Autoreset)
FP Freeze Protection LP Low Pressure HP High Pressure PM — Performance Monitor LED — Light-Emitting Diode
Over/Under Voltage Shutdown
8 PM Warning Performance Monitor Warning
9 FP1 and FP2
Thermistors are swapped
LEGEND
last power-down to power-up sequence
ous seconds before or during a call (bypassed for first 60 seconds)
FP1 below Temp limit for 30 continuous seconds (bypassed for first 60 seconds of operation)
FP2 below Temp limit for 30 continuous seconds (bypassed for first 60 seconds of operation)
30 continuous seconds “R power supply is <19VAC or
>30VAC
has occurred. FP1 temperature is higher than
FP2 in heating/test mode, or FP2 temperature is higher than FP1 in cooling/test mode.
WSHP Open Test Mode — To enter WSHP Open test
mode, navigate from the BACview6 home screen to the config­uration screen. Choose the service screen and enable unit test. The controller will then test the following:
FAN TEST — Tests all fan speeds, sequences fan from low to high, and operates each speed for one minute. Resets to disable on completion.
COMPRESSOR TEST — Tests compressor cooling and heating operation. Sequences cooling stage 1 then cooling stage 2 followed by heating stage 2 then reduces capacity to heating stage 1. Operates for 1 minute per step.
DEHUMIDIFICATION TEST — Tests dehumidification mode. Operates for 2 minutes.
Table 36 — Aquazone™ Deluxe D Control Current LED Status and Alarm Relay Operations
AUXILIARY HEATING TEST — Tests auxiliary heat. Sequences fan on and enables heating coil for 1 minute.
H
O ECONOMIZER TEST — Tests entering/returning
2
water loop economizer operation. Sequences fan and opens economizer water valve for one minute.
OPEN VENT DAMPER 100% TEST — Tests outside air (OA) damper operation.
PREPOSITION OA DAMPER — Prepositions OA damper actuator to set proper preload.
NOTE: The auxiliary heating test, H
O economizer test, open
2
vent damper 100% test, and preposition OA damper features will not be visible on the screen unless configured.
Once tests are complete, set unit test back to disable. Unit will automatically reset to disable after 1 hour.
Retry Mode — In Retry mode, the status LED will start to
flash slowly to signal that the control is trying to recover from an input fault. The control will stage off the outputs and try to again satisfy the thermostat used to terminal Y. Once the ther­mostat input calls are satisfied, the control will continue normal operation.
NOTE: If 3 consecutive faults occur without satisfying the thermostat input call to terminal Y, the control will go into lockout mode. The last fault causing the lockout is stored in memory and can be viewed by entering Test mode.
Aquazone™ Deluxe D Control LED Indica­tors —
STATUS LED — Status LED indicates the current status or mode of the D control. The Status LED light is green.
TEST LED — Test LED will be activated any time the D control is in test mode. The Test LED light is yellow.
FAULT LED — Fault LED light is red. The fault LED will always flash a code representing the last fault in memory. If there is no fault in memory, the fault LED will flash code 1 and appear as one fast flash alternating with a 10-second pause. See Table 36.
There are 3 LED indicators on the Deluxe D control:
DESCRIPTION
Normal Mode On Off Flash Last Fault Code in Memory Open
Normal Mode with PM On Off Flashing Code 8
Deluxe D Control
is non-functional
Test Mode On Flash Last Fault Code in Memory Cycling Appropriate Code
Night Setback Flashing Code 2 Flash Last Fault Code in Memory
ESD Flashing Code 3 Flash Last Fault Code in Memory Invalid T-stat Inputs Flashing Code 4 Flash Last Fault Code in Memory No Fault in Memory On Off Flashing Code 1 Open
HP Fault Slow Flash Off Flashing Code 2 Open
LP Fault Slow Flash Off Flashing Code 3 Open FP1 Fault Slow Flash Off Flashing Code 4 Open FP2 Fault Slow Flash Off Flashing Code 5 Open
CO Fault Slow Flash Off Flashing Code 6 Open
Over/Under Voltage Slow Flash Off Flashing Code 7 Open (closed after 15 minutes)
HP Lockout Fast Flash Off Flashing Code 2 Closed
LP Lockout Fast Flash Off Flashing Code 3 Closed FP1 Lockout Fast Flash Off Flashing Code 4 Closed FP2 Lockout Fast Flash Off Flashing Code 5 Closed
CO Lockout Fast Flash Off Flashing Code 6 Closed
LEGEND NOTES:
CO — Condensate Overflow HP — High Pressure ESD — Emergency Shutdown LP Low Pressure FP Freeze Protection PM — Performance Monitor
STATUS LED
(Green)
Off Off Off Open
TEST LED
(Yellow)
FAULT LED (Red) ALARM RELAY
Cycle (closed 5 sec,
open 25 sec, …)
1. If there is no fault in memory, the Fault LED will flash code 1.
2. Codes will be displayed with a 10-second Fault LED pause.
3. Slow flash is 1 flash every 2 seconds.
4. Fast flash is 2 flashes every 1 second.
5. EXAMPLE: “Flashing Code 2 is represented by 2 fast flashes followed by a 10-second pause. This sequence will repeat continually until the fault is cleared.
47
SERVICE
Perform the procedures outlined below periodically, as
indicated.
WARNING
To prevent injury or death due to electrical shock or contact with moving parts, open unit disconnect switch before ser­vicing unit.
IMPORTANT: When a compressor is removed from this unit, system refrigerant circuit oil will remain in the com­pressor. To avoid leakage of compressor oil, the refrigerant lines of the compressor must be sealed after it is removed.
IMPORTANT: All refrigerant discharged from this unit must be recovered without exception. Technicians must fol­low industry accepted guidelines and all local, state and fed­eral statutes for the recovery and disposal of refrigerants.
IMPORTANT: To avoid the release of refrigerant into the atmosphere, the refrigerant circuit of this unit must only be serviced by technicians who meet local, state and federal proficiency requirements.
Filters — Filters must be clean for maximum performance.
Inspect filters every month under normal operating conditions. Replace when necessary.
IMPORTANT: Units should never be operated without a filter.
Water Coil — Keep all air out of the water coil. Check
open loop systems to be sure the well head is not allowing air to infiltrate the water line. Always keep lines airtight.
Inspect heat exchangers regularly, and clean more frequent­ly if the unit is located in a “dirty” environment. Keep the heat exchanger full of water at all times. Open loop systems should have an inverted P trap placed in the discharge line to keep water in the heat exchanger during off cycles. Closed loop systems must have a minimum of 15 psig during the summer and 40 psig during the winter.
Check P trap frequently for proper operation.
CAUTION
To avoid fouled machinery and extensive unit clean-up, DO NOT operate units without filters in place. DO NOT use equipment as a temporary heat source during construction.
Condensate Drain Pans — Check condensate drain
pans for algae growth twice a year. If algae growth is apparent, consult a water treatment specialist for proper chemical treat­ment. Applying an algaecide every three months will typically eliminate algae problems in most locations.
Refrigerant System — Verify air and water flow rates
are at proper levels before servicing. To maintain sealed circuit­ry integrity, do not install service gages unless unit operation appears abnormal.
Check to see that unit is within the superheat and subcool­ing temperature ranges shown in Tables 20-30. If the unit is not within these ranges, recover and reweigh in refrigerant charge.
Compressor — Conduct annual amperage checks to en-
sure that amp draw is no more than 10% greater than indicated on the serial plate data.
Fan Motors — All units have lubricated fan motors. Fan
motors should never be lubricated unless obvious, dry opera­tion is suspected. Periodic maintenance oiling is NOT recom­mended as it will result in dirt accumulating in the excess oil and cause eventual motor failure. Conduct annual dry opera­tion check and amperage check to ensure amp draw is no more than 10% greater than indicated on serial plate data.
Condensate Drain Cleaning — Clean the drain line
and unit drain pan at the start of each cooling season. Check flow by pouring water into drain. Be sure trap is filled to main­tain an air seal.
Air Coil Cleaning — Remove dirt and debris from evap-
orator coil as required by condition of the coil. Clean coil with a stiff brush, vacuum cleaner, or compressed air. Use a fin comb of the correct tooth spacing when straightening mashed or bent coil fins.
Condenser Cleaning — Water-cooled condensers may
require cleaning of scale (water deposits) due to improperly maintained closed-loop water systems. Sludge build-up may need to be cleaned in an open water tower system due to induced contaminants.
Local water conditions may cause excessive fouling or pitting of tubes. Condenser tubes should therefore be cleaned at least once a year, or more often if the water is contaminated.
Proper water treatment can minimize tube fouling and pitting. If such conditions are anticipated, water treatment analysis is recommended. Refer to the Carrier System Design Manual, Part 5, for general water conditioning information.
CAUTION
Follow all safety codes. Wear safety glasses and rubber gloves when using inhibited hydrochloric acid solution. Observe and follow acid manufacturer’s instructions.
Clean condensers with an inhibited hydrochloric acid solu­tion. The acid can stain hands and clothing, damage concrete, and, without inhibitor, damage steel. Cover surroundings to guard against splashing. Vapors from vent pipe are not harmful, but take care to prevent liquid from being carried over by the gases.
Warm solution acts faster, but cold solution is just as effec­tive if applied for a longer period.
GRAVITY FLOW METHOD — Do not add solution faster than vent can exhaust the generated gases.
When condenser is full, allow solution to remain overnight, then drain condenser and flush with clean water. Follow acid manufacturer’s instructions. See Fig. 36.
FORCED CIRCULATION METHOD — Fully open vent pipe when filling condenser. The vent may be closed when condenser is full and pump is operating. See Fig. 37.
Regulate flow to condenser with a supply line valve. If pump is a non overloading type, the valve may be fully closed while pump is running.
For average scale deposit, allow solution to remain in con­denser overnight. For heavy scale deposit, allow 24 hours. Drain condenser and flush with clean water. Follow acid manu­facturer’s instructions.
48
FILL CONDENSER WITH CLEANING SOLUTION. DO NOT ADD SOLUTION MORE RAPIDLY THAN VENT CAN EXHAUST GASES CAUSED BY CHEMICAL ACTION.
VENT PIPE
3’ TO 4’
1 PIPE
5’ APPROX
FUNNEL
PAIL
CONDENSER
6. Compare the subcooling temperature with the normal temperature listed in Tables 20-30. If the measured liquid line temperature does not agree with the required liquid line temperature, ADD refrigerant to raise the tempera­ture or REMOVE refrigerant (using standard practices) to lower the temperature (allow a tolerance of ± 3° F).
Refrigerant Charging
WARNING
To prevent personal injury, wear safety glasses and gloves when handling refrigerant. Do not overcharge system — this can cause compressor flooding.
NOTE: Do not vent or depressurize unit refrigerant to atmo­sphere. Remove and recover refrigerant following accepted practices.
Air Coil Fan Motor Removal
A50-6286
PAIL
Fig. 36 — Gravity Flow Method
PUMP
SUCTION
PUMP SUPPORT
TANK
FINE MESH SCREEN
PRIMING CONN.
GAS VENT
GLOBE VALV ES
SUPPLY
1 PIPE
RETURN
CONDENSER
REMOVE WATER REGULATING VALVE
A50-6287
Fig. 37 — Forced Circulation Method
Checking System Charge — Units are shipped with
full operating charge. If recharging is necessary:
1. Insert thermometer bulb in insulating rubber sleeve on liquid line near filter drier. Use a digital thermometer for all temperature measurements. DO NOT use a mercury or dial-type thermometer.
2. Connect pressure gage to discharge line near compressor.
3. After unit conditions have stabilized, read head pressure on discharge line gage.
NOTE: Operate unit a minimum of 15 minutes before checking charge.
4. From standard field-supplied Pressure-Temperature chart for R-410A, find equivalent saturated condensing temperature.
5. Read liquid line temperature on thermometer; then subtract from saturated condensing temperature. The dif­ference equals subcooling temperature.
CAUTION
Before attempting to remove fan motors or motor mounts, place a piece of plywood over evaporator coils to prevent coil damage.
Disconnect motor power wires from motor terminals before
motor is removed from unit.
1. Shut off unit main power supply.
2. Loosen bolts on mounting bracket so that fan belt can be removed.
3. Loosen and remove the 2 motor mounting bracket bolts on left side of bracket.
Slide motor/bracket assembly to extreme right and lift out through space between fan scroll and side frame. Rest motor on a high platform such as a step ladder. Do not allow motor to hang by its power wires.
Replacing the WSHP Open Controller’s Bat­tery — The WSHP Open controller’s 10-year lithium
CR2032 battery provides a minimum of 10,000 hours of data retention during power outages.
NOTE: Power must be ON to the WSHP Open controller when replacing the battery, or the date, time and trend data will be lost.
1. Remove the battery from the controller, making note of the battery's polarity.
2. Insert the new battery, matching the battery's polarity with the polarity indicated on the WSHP Open controller.
TROUBLESHOOTING
When troubleshooting problems with a WSHP, consider the
following:
Control Sensors — The control system employs 2 nom-
inal 10,000 ohm thermistors (FP1 and FP2) that are used for freeze protection. Be sure FP1 is located in the discharge fluid and FP2 is located in the air discharge. See Fig. 38.
Thermistor — A thermistor may be required for single-
phase units where starting the unit is a problem due to low voltage. See Fig. 39 for thermistor nominal resistance.
49
AIR
AIRFLOW
(°F)
THERMISTOR
LEGEND
COAX — Coaxial Heat Exchanger
Airflow Refrigerant Liquid Line Flow
COIL
CONDENSATE
OVERFLOW
(CO)
AIRFLOW
(°F)
FP2
AIR COIL FREEZE PROTECTION
EXPANSION
VALV E
LIQUID LINE
WATER COIL PROTECTION
FP1
WATER IN
COAX
WATER OUT
Fig. 38 — FP1 and FP2 Thermistor Location
SUCTION
COMPRESSOR
DISCHARGE
a50-8163
90.0
80.0
70.0
60.0
50.0
40.0
30.0
Resistance (kOhm)
20.0
10.0
0.0
A50-6270
0.0 20.0 40.0 60.0 80.0 100.0 120.0 140.0
Temperature (degF)
Fig. 39 — Thermistor Nominal Resistance
WSHP Open Controller — With the WSHP Open con-
troller option, the 100 most recent alarms can be viewed using the BACview
To view the alarms:
1. Navigate to the Alarm Status screen from the Home screen using the arrow softkeys. The screen will display the current alarm status, either normal or Alarm, and al­low for scrolling through the unit’s alarm status.
2. From the Alarm Status screen, press the Alarm softkey to view the 100 most recent alarms which are labeled with date and time for easy reference.
NOTE: Active faults can be viewed by scrolling down, these faults indicate a possible bad sensor or some condi­tion which may not merit an alarm.
3. To view alarms which have been corrected, scroll down through the Alarm screen to Return Top Normal screen.
NOTE: Alarms are automatically reset once alarm con­dition has been corrected.
See Table 37 for possible alarm cause and solution.
6
alarm status and alarm history.
Thermostatic Expansion Valves — Thermostat-
ic expansion valves (TXV) are used as a means of metering the refrigerant through the evaporator to achieve a preset superheat
at the TXV sensing bulb. Correct superheat of the refrigerant is important for the most efficient operation of the unit and for the life of the compressor.
Packaged heat pumps typically use one bi-flow TXV to meter refrigerant in both modes of operation. When diagnosing possible TXV problems it may be helpful to reverse the refrig­erant flow to assist with the diagnosis.
Geothermal and water source heat pumps are designed to op­erate through a wide range of entering water temperatures that will have a direct effect on the unit refrigerant operating pres­sures. Therefore, diagnosing TXV problems can be difficult.
TXV FAILURE — The most common failure mode of a TXV is when the valve fails while closed. Typically, a TXV uses spring pressure to close the valve and an opposing pressure, usually from a diaphragm, to open the valve. The amount of pressure exerted by the diaphragm will vary, depending on the pressure inside of the sensing bulb. As the temperature of and pressure within the bulb decreases, the valve will modulate closed and restrict the refrigerant flow through the valve. The result is less refrigerant in the evaporator and an increase in the superheat. As the temperature at the bulb increases the dia­phragm pressure will increase, which opens the valve and allows more refrigerant flow and a reduction in the superheat.
If the sensing bulb, connecting capillary, or diaphragm assembly are damaged, pressure is lost and the spring will force the valve to a closed position. Often, the TXV will not close completely so some refrigerant flow will remain, even if inade­quate flow for the heat pump to operate.
The TXV sensing bulb must be properly located, secured, and insulated as it will attempt to control the temperature of the line to which it is connected. The sensing bulb must be located on a dedicated suction line close to the compressor. On a pack­aged heat pump, the bulb may be located almost any place on the tube running from the compressor suction inlet to the reversing valve. If the bulb is located on a horizontal section, it should be placed in the 10:00 or 2:00 position for optimal performance.
CAUTION
Use caution when tightening the strap. The strap must be tight enough to hold the bulb securely but caution must be taken not to over-tighten the strap, which could dent, bend, collapse or otherwise damage the bulb.
50
The bulb must be secured to the pipe using a copper strap. The use of heat transfer paste between the bulb and the pipe will also help ensure optimum performance.
The bulb must also be properly insulated to eliminate any influence on valve operation by the surrounding conditions. Cork tape is the recommended insulation as it can be molded tight to the bulb to prevent air infiltration.
Causes of TXV Failure failure are:
1. A cracked, broken, or damaged sensing bulb or capillary can be caused by excessive vibration of the capillary dur­ing shipping or unit operation.
If the sensing bulb is damaged or if the capillary is cracked or broken, the valve will be considered failed and must be replaced. Replacement of the TXV “power head” or sensing bulb, capillary, diaphragm assembly is possible on some TXVs. The power head assembly screws onto most valves, but not all are intended to be replaceable. If the assembly is not replaceable, replace the entire valve.
2. Particulate debris within the system can be caused by sev­eral sources including contaminated components, tubing, and service tools, or improper techniques used during brazing operations and component replacement.
Problems associated with particulate debris can be com­pounded by refrigerant systems that use POE (polyol es­ter oil). POE oil has solvent-like properties that will clean the interior surfaces of tubing and components. Particu­lates can be released from interior surfaces and may mi­grate to the TXV strainer, which can lead to plugging of the strainer.
3. Corrosive debris within the system may happen after a failure, such as a compressor burn out, if system was not properly cleaned.
4. Noncondensables may be present in the system. Non­condensables includes any substance other than the refrigerant or oil such as air, nitrogen, or water. Contami­nation can be the result of improper service techniques, use of contaminated components, and/or improper evacu­ation of the system.
Symptoms and will include one or more of the following:
• Low refrigerant suction pressure
• High refrigerant superheat
• High refrigerant subcooling
• TXV and/or low pressure tubing frosting
• Equalizer line condensing and at a lower temperature than the suction line or the equalizer line frosting
• FP1 faults in the heating mode in combination with any of the symptoms listed above
• FP2 faults in the cooling mode in combination with any of the symptoms listed above. Some symptoms can mimic a failed TXV but may actually be caused be another problem.
Before conducting an analysis for a failed TXV the follow-
ing must be verified:
• Confirm that there is proper water flow and water tempera­ture in the heating mode.
• Confirm that there is proper airflow and temperature in the cooling mode.
• Ensure coaxial water coil is clean on the inside; this applies to the heating mode and may require a scale check.
• Refrigerant may be undercharged. To verify, subcooling and superheat calculations may be required.
— The symptoms of a failed TXV can be varied
— The most common causes of TXV
Diagnostics a TXV has failed. The following tools may be required for testing:
1. Refrigerant gage manifold compatible with the refriger-
2. Digital thermometer, preferably insulated, with wire leads
3. Refrigerant pressure-temperature chart for the refrigerant
To determine that a TXV has failed, verify the following:
• The suction pressure is low and the valve is non-responsive. The TXV sensing bulb can be removed from the suction line and warmed by holding the bulb in your hand. This
action should result in an increase in the suction pressure while the compressor is operating. The sensing bulb can also be chilled by immersion in ice water, which should result in a decrease in the suction pressure while the compressor is operating. No change in the suction pres­sure would indicate a nonresponsive valve.
• Simultaneous LOW suction pressure, HIGH refrigerant subcooling and HIGH superheat may indicate a failed valve.
• LOW suction pressure, LOW subcooling and HIGH super­heat may indicate an undercharge of refrigerant. HIGH sub­cooling and LOW superheat may indicate an overcharge of refrigerant. The suction pressure will usually be normal or high if there is an overcharge of refrigerant.
• LOW suction pressure and frosting of the valve and/or equalizer line may indicate a failed valve. However, these symptoms may also indicate an undercharge of refrigerant. Calculate the subcooling and superheat to verify a failed valve or refrigerant charge issue.
Repair
—Several tests may be required to determine if
ant in the system
that can be connected directly to the tubing
used
WARNING
Puron® refrigerant (R-410A) operates at higher pressure than R-22, which is found in other WSHPs. Tools such as manifold gages must be rated to withstand the higher pres­sures. Failure to use approved tools may result in a failure of tools, which can lead to severe damage to the unit, injury or death.
WARNING
Most TXVs are designed for a fixed superheat setting and are therefore considered non-adjustable. Removal of the bottom cap will not provide access for adjustment and can lead to damage to the valve or equipment, unintended vent­ing of refrigerant, personal injury, or possibly death.
CAUTION
Use caution when tightening the strap. The strap must be tight enough to hold the bulb securely but caution must be taken not to over-tighten the strap, which could dent, bend, collapse or otherwise damage the bulb.
CAUTION
Puron refrigerant (R-410A) requires the use of synthetic lubricant (POE oil). Do not use common tools on systems that contain R-22 refrigerants or mineral oil. Contamina­tion and failure of this equipment may result.
51
IMPORTANT: Always recover the refrigerant from the system with suitable approved tools, recovery equipment, and practices prior to attempting to remove or repair any TXV.
IMPORTANT: Repair of any sealed refrigerant system requires training in the use of refrigeration tools and proce­dures. Repair should only be attempted by a qualified ser­vice technician. A universal refrigerant handling certificate will be required. Local and/or state license or certificate may also be required.
IMPORTANT: Due to the hygroscopic nature of the POE oil in Puron refrigerant (R-410A) and other environ­mentally sound refrigerants, any component replace-
See Tables 37-39 for additional troubleshooting
information. ment must be conducted in a timely manner using caution and proper service procedure for these types of refrigerants. A complete installation instruction will be included with each replacement TXV/filter drier assem­bly. It is of critical importance these instructions are carefully understood and followed. Failure to follow these instructions can result in a system that is contami-
Disconnect power from unit before removing or replacing connectors, or servicing motor. Wait 5 minutes after dis­connecting power before opening motor.
nated with moisture to the extent that several filter drier replacements may be required to properly dry the system.
Table 37 — ECM Troubleshooting
FAULT DESCRIPTION SOLUTION
Motor rocks slightly when starting
Motor will not start No movement Check power at motor.
Motor rocks Check for loose or non-compliant motor mount.
Motor oscillates up and down while being tested off of blower
Motor starts, but runs erratically Varies up and down or intermittent Check line voltage for variation or “sag.
“Hunts or “puffs at high cfm (speed)
Stays at low cfm despite system call for cool or heat cfm
Stays at high cfm Check to see if “R is missing/not connected at motor.
Blower will not shut off Check to see if there is current leakage from controls into G, Y, or W. Check for Triac switched
Excessive noise Noisy blower or cabinet Determine if it is air, cabinet, duct, or motor noise.
“Hunts or “puffs at high cfm
Evidence of moisture Motor failure or malfunction has
(speed)
occurred and moisture is present Evidence of moisture present
inside air mover
This is normal start-up for ECM.
Check low voltage (24-vac R to C) at motor. Check low voltage connections (G,Y, W, R, C) at motor. Check for unseated pins in connectors on motor harness. See Fig. 40. Test with a temporary jumper between R and G. Check motor for tight shaft. Perform motor/control replacement check. Run moisture check. See Moisture Check section in Troubleshooting.
Make sure blower wheel is tight on shaft. Perform motor/control replacement check. It is normal for motor to oscillate with no load on shaft.
Check low voltage connections (G,Y, W, R, C) at motor, unseated pins in motor harness connectors. See Fig. 40.
Check “Bk for erratic cfm command (in variable speed applications). Check system controls, thermostat. Perform moisture check. See Moisture Check section in Troubleshooting. If removing panel or filter reduces “puffing, reduce restriction or reduce maximum airflow.
Check low voltage (thermostat) wires and connections.
Verify fan is not in delay mode. Wait until delay is complete. Check to see if “R is missing/not connected at motor. Perform motor/control replacement check.
Verify fan is not in delay mode. Wait until delay is complete. Perform motor/control replacement check.
thermostat or solid state relay.
Check for loose blower housing, panels, etc. If high static is creating high blower speed, check for air whistling through seams in ducts,
cabinets, or panels. If high static is creating high blower speed, check for cabinet/duct deformation. If removing panel or filter reduces “puffing, reduce restriction or reduce maximum airflow.
Replace motor and perform moisture check. See Moisture Check section in Troubleshooting.
Perform moisture check. See Moisture Check section in Troubleshooting.
CAUTION
52
a50-8448
Fig. 40 — ECM Pin Connectors
53
Stopped or Malfunctioned ECM Motor — Refer
to Fig. 41 to determine the possible cause of a stopped or mal­functioned ECM motor. Follow the instructions in the boxes.
a50-8447
Fig. 41 — ECM Troubleshooting Flow Diagram
54
Moisture Check — To perform moisture check:
• Check that connectors are orientated “down” (or as recom­mended by equipment manufacturer).
• Arrange harnesses with “drip loop” under motor.
• Check if condensate drain is plugged.
• Check for low airflow (too much latent capacity).
• Check for undercharged condition.
• Check and plug leaks in return ducts, cabinet.
Table 38 — Good Practices
DO DO NOT
Check motor, controls wiring, and connections thoroughly before replac­ing motor.
Automatically assume the motor is bad.
Orient connectors down so water cannot get in. Install “drip loops. Locate connectors above 7 and 4 o’clock positions. Use authorized motor and control model numbers for replacement. Replace one motor or control model number with another (unless
Keep static pressure to a minimum by:
• Using high efficiency, low-static filters.
• Keeping filters clean.
• Designing ductwork for minimum static and maximum comfort.
replacement is authorized). Use high pressure drop filters.
Use restricted returns.
• Improving ductwork when replacement is necessary. Size equipment wisely. Oversize system then compensate with low airflow. Check orientation before inserting motor connectors. Plug in power connector backwards.
Force plugs.
Table 39 — WSHP Troubleshooting
Main Power Problems X X Green Status LED Off Check line voltage circuit breaker and disconnect.
HP Fault — Code 2 High Pressure
LP/LOC Fault — Code 3 Low Pressure/Loss of Charge
FP1 Fault — Code 4 Water Freeze Protection
FP2 Fault — Code 5 Air Coil Freeze Protection
LED — Light-Emitting Diode RV Reversing Valve TXV — Thermostatic Expansion Valve
FAULT HEATING COOLING POSSIBLE CAUSE SOLUTION
Check for line voltage between L1 and L2 on the contactor. Check for 24 vac between R and C on controller. Check primary/secondary voltage on transformer. Check pump operation or valve operation/setting. Check water flow adjust to proper flow rate. Bring water temperature within design parameters.
Check for dirty air filter and clean or replace. Check fan motor operation and airflow restrictions. Dirty air coil — construction dust etc. External static too high. Check blower performance per
Tables 11-13. Bring return-air temperature within design parameters.
Tables 20-30.
Check pump operation or water valve operation/setting. Plugged strainer or filter. Clean or replace. Check water flow adjust to proper flow rate.
Clip JW2 jumper for antifreeze (10 F) use.
Check for dirty air filter and clean or replace. Check fan motor operation and airflow restrictions. External static too high. Check blower performance per
Tables 11-13.
parameters. Normal airside applications will require 30 F only.
LEGEND
X Reduced or no water flow in cool-
ing
X Water temperature out of range in
X Reduced or no airflow in
X Air temperature out of range
X X Overcharged with refrigerant Check superheat/subcooling vs typical operating condition per
X X Bad HP switch Check switch continuity and operation. Replace. X X Insufficient charge Check for refrigerant leaks. X Compressor pump down at star t-upCheck charge and start-up water flow.
X Reduced or no water flow
X Inadequate antifreeze level Check antifreeze density with hydrometer. X Improper freeze protect setting
X Water temperature out of range Bring water temperature within design parameters. X X Bad thermistor Check temperature and impedance correlation.
X X Bad thermistor Check temperature and impedance correlation.
cooling
heating
in heating
in heating
(30 F vs 10 F)
X Reduced or no airflow in
cooling
X Air temperature out of range Too much cold vent air. Bring entering air temperature within design
X Improper freeze protect setting
(30 F vs 10 F)
55
Table 39 — WSHP Troubleshooting (cont)
FAULT HEATING COOLING POSSIBLE CAUSE SOLUTION
Condensate Fault — Code 6
Over/Under Voltage — Code 7 (Auto Resetting)
Performance Monitor — Code 8
FP1 and FP2 Thermistors — Code 9
No Fault Code Shown X X No compressor operation See Scroll Compressor Rotation section.
Swapped Thermistor — Code 9
Unit Short Cycles X X Dirty air filter Check and clean air filter.
Only Fan Runs X X Thermostat position Ensure thermostat set for heating or cooling operation.
Only Compressor Runs X X Thermostat wiring Check G wiring at heat pump. Jumper G and R for fan operation.
Unit Does Not Operate in Cooling
Insufficient Capacity/ Not Cooling or Heating Properly
LEGEND
LED — Light-Emitting Diode RV Reversing Valve TXV —
Thermostatic Expansion Valve
X X Blocked drain Check for blockage and clean drain. X X Improper trap Check trap dimensions and location ahead of vent.
X X Under voltage Check power supply and 24 vac voltage before and during
X X Over voltage Check power supply voltage and 24 vac before and during operation.
X Heating mode FP2>125 F Check for poor airflow or overcharged unit.
X FP1 temperature is higher
X X Compressor overload Check and replace if necessary. X X Control board Reset power and check operation. X X FP1 and FP2 swapped Reverse position of thermistors.
X X Unit in 'Test Mode' Reset power or wait 20 minutes for auto exit. X X Unit selection Unit may be oversized for space. Check sizing for actual load of space. X X Compressor overload Check and replace if necessary.
X X Unit locked out Check for lockout codes. Reset power. X X Compressor overload Check compressor overload. Replace if necessary. X X Thermostat wiring Check Y and W wiring at heat pump. Jumper Y and R for compressor
X X Fan motor relay Jumper G and R for fan operation. Check for line voltage across BR
X X Fan motor Check for line voltage at motor. Check capacitor.
X X Dirty filter Replace or clean. X Reduced or no airflow in
X X Leaky ductwork Check supply and return air temperatures at the unit and at distant duct
X X Low refrigerant charge Check superheat and subcooling per Tables 20-30. X X Restricted metering device Check superheat and subcooling per Tables 20-30. Replace.
X X Thermostat improperly located Check location and for air drafts behind thermostat. X X Unit undersized Recheck loads and sizing check sensible cooling load and heat pump
X X Scaling in water heat exchanger Perform condenser cleaning. X X Inlet water too hot or cold Check load, loop sizing, loop backfill, ground moisture.
X Poor drainage Check for piping slope away from unit.
Check slope of unit toward outlet.
X Moisture on sensor Check for moisture shorting to air coil.
X Cooling mode FP1>125 F OR
FP2< 40 F
than FP2 temperature.
X FP2 temperature is higher
than FP1 temperature.
X Reversing valve Set for cooling demand and check 24 vac on RV coil and at control.
X Thermostat setup Check for 'O' RV setup not 'B'. X Thermostat wiring Check O wiring at heat pump. Jumper O and R for RV coil 'Click'.
heating
X Reduced or no airflow in
cooling
X Defective reversing valve Set for cooling demand and check 24 vac on RV coil and at control.
Poor venting. Check vent location.
operation. Check power supply wire size. Check compressor starting. Check 24 vac and unit transformer tap for correct power supply
voltage.
Check 24 vac and unit transformer tap for correct power supply voltage.
Check for poor water flow or airflow.
Swap FP1 and FP2 thermistors.
Swap FP1 and FP2 thermistors.
operation in Test mode.
Check Y and W wiring at heat pump. Jumper Y and R for compressor operation in test mode.
contacts. Check fan power enable relay operation (if present).
If RV is stuck, run high pressure up by reducing water flow and while operating, engage and disengage RV coil voltage to push valve.
Check for dirty air filter and clean or replace. Check fan motor operation and airflow restrictions. External static too high. Check blower performance per
Tables 11-13. Check for dirty air filter and clean or replace. Check fan motor operation and airflow restrictions. External static too high. Check blower performance per
Tables 11-13.
registers if significantly different, duct leaks are present.
If RV is stuck, run high pressure up by reducing water flow and while operating, engage and disengage RV coil voltage to push valve.
capacity.
56
Table 39 — WSHP Troubleshooting (cont)
FAULT HEATING COOLING POSSIBLE CAUSE SOLUTION
High Head Pressure X Reduced or no airflow in
X Air temperature out of range in
X X Unit overcharged Check superheat and subcooling. Reweigh in charge. X X Noncondensables in system Remove refrigerant, evacuate system and charge unit. X X Restricted metering device Check superheat and subcooling per Tables 20-30. Replace.
Low Suction Pressure X Reduced water flow in
X Water temperature out of range Bring water temperature within design parameters.
X X Insufficient charge Check for refrigerant leaks.
Low Discharge Air Temperature in Heating
High Humidity X Too high airflow Check blower performance per Tables 11-13.
Low Refrigerant Suction Pressure
X Too high airflow Check blower performance per Tables 11-13. X Poor performance See “Insufficient Capacity.
X Normal operation Check/compare with Tables 20-30. X Reduced water flow Check pump operation.
heating
X Reduced or no water flow in cool-
ing
X Inlet water too hot Check load, loop sizing, loop backfill, ground moisture.
heating
X Scaling in water heat exchanger Perform condenser cleaning.
heating
X Reduced airflow in cooling Check for dirty air filter and clean or replace.
X Air temperature out of range Too much cold vent air. Bring entering air temperature within design
X Unit oversized Recheck loads and sizing check sensible cooling load and heat pump
X Water temperature out of range Bring water temperature within proper range. X Scaling in water to refrigerant
heat exchanger
X Reduced airflow Check for dirty air filter.
X X Return air temperature below
minimum
X Supply air bypassing to return
airstream (zone systems)
X X Insufficient refrigerant charge Locate and repair leak.
High Refrigerant Superheat
High Refrigerant Subcooling
TXV and/or Low Pressure Tubing Frosting
Equalizer Line Condensing or Frosting
X X Improperly located TXV sens-
X X Failed or restricted metering
X X Insufficient refrigerant charge Locate and repair leak. X X Improperly located TXV sens-
X X Failed or restricted metering
X X Excessive refrigerant charge Remove refrigerant as needed. X X Failed or restricted metering
X Normal operation May occur when entering water temperature is close to minimum. X X Insufficient refrigerant charge Locate and repair leak. X X Failed or restricted metering
X X Failed or restricted metering
ing bulb
device
ing bulb
device
device
device
device
LEGEND
LED — Light-Emitting Diode RV Reversing Valve TXV — Thermostatic Expansion Valve
Check for dirty air filter and clean or replace. Check fan motor operation and airflow restrictions. External static too high. Check blower performance per
Tables 11-13. Check pump operation or valve operation/setting. Check water flow adjust to proper flow rate. See Tables 19 and 31.
Bring return-air temperature within design parameters.
Check pump operation or water valve operation/setting. Plugged strainer or filter. Clean or replace. Check water flow adjust to proper flow rate.
Check fan motor operation and airflow restrictions. External static too high. Check blower performance per
Tables 11-13.
parameters.
capacity.
Check strainer or filter. Improper flow regulator. Replace flow regulator.
Conduct water quality analysis.
Check for dirty air coil. Check fan motor operation. External static pressure exceeds fan operating parameters. Space temperature too cold. Increase space temperature.
Excessive fresh air. Reduce amount of fresh air exposure. Check for leaking ductwork.
Locate bulb on suction line between reversing valve and compressor.
Failed TXV power head, capillary or sensing bulb. Replace. Plugged TXV strainer. Unplug TXV strainer.
Locate bulb on suction line between reversing valve and compressor.
Failed TXV power head, capillary or sensing bulb. Replace. Plugged TXV strainer. Unplug TXV strainer.
Failed TXV power head, capillary or sensing bulb. Replace. Plugged TXV strainer. Unplug TXV strainer.
Failed TXV power head, capillary or sensing bulb. Replace. Plugged TXV strainer. Unplug TXV strainer. Failed TXV power head, capillary or sensing bulb. Replace. Plugged TXV strainer. Unplug TXV strainer.
57
APPENDIX A — WSHP OPEN SCREEN CONFIGURATION
SCREEN NAME POINT NAME
Operating Mode
SPT F Displays SPT
SAT F Displays SAT
Condenser Leaving
Temperature
Condenser Entering
Temperature
Fan
Equipment
Status
Alarm Status
Sensor
Calibration
BAS — Building Automation System DCV — Demand Controlled Ventilation IAQ — Indoor Air Quality OAT — Outdoor Air Temperature RH Relative Humidity SAT — Supply Air Temperature SPT — Space Temperature TPI Third Party Integration
Compressor Capacity 0 - 100% Displays compressor capacity
Damper Position 0 - 100%
O Economizer 0 - 100% Displays position of economizer valve
H
2
Auxiliary Heat 0 - 100%
Space RH 0 - 100%
Dehumidification Inactive/Active
IAQ CO
2
SPT Alarm Status
Alarming SPT F
SPT Alarm Limit F
SPT Sensor Alarm
Status
IAQ Alarm Status Normal/Alarm Current IAQ/ventilation condition
Compressor Alarm
Status
SAT Alarm Status Normal/Alarm Current SAT condition
Condensate Overflow
Alarm Status
Condenser Water Tem-
perature Alarm Status
Filter Alarm Status Normal/Alarm Current filter condition
Space RH Alarm Status Normal/Alarm Current space RH condition
OAT Alarm Status Normal/Alarm
Airside Linkage Status Normal/Alarm Current linkage status if enabled
Condenser Water
Linkage
SAT
SAT Offset X -9.9 - 10.0 F 0 F Used to correct sensor reading
Leaving Condenser Water Temperature
Leaving CW Offset X -9.9 - 10.0 F 0 F Used to correct sensor reading
Rnet Sensor Temperature
Rnet Offset X -9.9 - 10.0 F 0 F Used to correct sensor reading
RH % Displays Space RH value
RH Sensor Offset X -15% - 15% 0 % Used to correct sensor reading
LEGEND
PASSWO RD
LEVEL
No Password
Required
No Password
Required
Admin Password
level access only
EDITABLE RANGE DEFAULT NOTES
Off, Fan Only, Economize,
Cooling, Heating, Cont Fan,
Test, Start Delay, Dehumidify
°
°
°
F
°
F
Off/Low Speed/
Medium Speed
High Speed/On
0 - 9999 ppm Displays the space CO2 level
Normal/Alarm
°
°
Normal/Alarm
Normal/Alarm Current compressor condition
Normal/Alarm
Normal/Alarm
Normal/Alarm Current linkage status if enabled
°
F Display SAT
°°
°
F
°°
°
F Displays SPT
°°
Displays unit operating mode
Displays leaving condenser
water temperature
Displays entering condenser
water temperature (Value
will not update when compressor
Displays current damper position (Viewable only if Ventilation DMP
reheat valve (Viewable only if Leaving
Air Auxiliary Heat Type = 2 position,
Displays space RH% (Viewable only if
Displays if dehumidification is active
Dehumidification Reheat = Installed)
exceeded the alarm limit (when SPT
Displays the SPT alarm limit that was
exceeded; causing the alarm condition
(when SPT alarm above is in Alarm)
SPT sensor - ALARM is displayed
should the sensor fail to communicate
Current status of the condensate
is operating)
Displays fan speed status
Type = 2 position or DCV)
Displays position of auxiliary
1 stage Elect or Modulating)
Humidity Sensor = Installed)
(Viewable only if Factory
Displays current space
temperature condition Displays the SPT that
alarm above is in Alarm)
Displays the status of the Rnet
with the control module
drain (overflow switch)
Current status of the
condenser water
Current status of the OAT
broadcast function
Displays Leaving Condenser
Water Temperature
58
APPENDIX A — WSHP OPEN SCREEN CONFIGURATION (cont)
SCREEN NAME POINT NAME
Operating Mode
Fan Operating Mode Auto/Continuous/Always On
Occupancy Status Unoccupied/Occupied Displays the current occupancy status
Occupancy Control
Outside Air
Temperature
SPT F Displays SPT
SPT Status
SPT Sensor Status Inactive/Connected
Condensate Overflow Normal/Alarm
Cooling Set Point F
Unit
Maintenance
System Settings
Occupancy
Maintenance
Schedule
Configuration
BAS — Building Automation System DCV — Demand Controlled Ventilation IAQ — Indoor Air Quality OAT — Outdoor Air Temperature RH Relative Humidity SAT — Supply Air Temperature SPT — Space Temperature TPI Third Party Integration
Heating Set Point F
Set Point Adjustment F
Auxiliary Heat Control
Set Point
O Economizer
H
2
Control Set Point
Calculated IAQ/
Ventilation Damper
position
Active Compressor
Stages
SAT F Displays SAT
Reset Filter Alarm X No/Yes
Overflow Contact Closed/Open
Occupancy Contact Closed/Open
BAS/Keypad Override X
OAT Input N/A / Network
BACnet X See TPI
Keypad Configuration X Mapping
Password X Changes password
Network X See TPI
BACnet Time Master X See TPI
Clock Set X Changes clock/time setting
Override Schedules
Pushbutton Override Inactive/Active Occupied
Keypad Override
Schedules Inactive/Active Occupied
Occupancy Contact Inactive/Active Occupied
BAS on/off Inactive/Active Occupied
Local Occupancy
Schedules
Local Holiday
Schedules
Local Override
Schedules
BACnet Occupancy
Schedules
LEGEND
PASSWORD
LEVEL
No Password
required
No Password
required
User/Admin
Password level
access
EDITABLE RANGE DEFAULT NOTES
Off, Fan Only,Economize,
Cooling, Heating, Cont Fan, Test,
Start Delay, Dehumidify
Always Occupied/Local Schedule/
BACnet Schedule/BAS Keypad/
Occupied Contact/Holiday Schedule/
Override Schedule/Pushbutton
Override/Unoccupied None
°
F
°
Normal/Above Limit/Below
Limit/Sensor Failure
°
°
°
°
F
°
F
%
0/1/2
°
Inactive/Occupied/
Unoccupied
Inactive/Active Occupied
Inactive/Active Occupied/Active
Unoccupied
X Disable/Enable Enable
X Disable/Enable Disable
X Disable/Enable Disable
X Disable/Enable Disable
Inactive
Displays unit operating mode
Displays how the fan is configured
Displays OAT (Viewable only if OAT
Displays the connection status
Displays the offset values from the Rnet
user set point adjustment that is being
applied to the configured set points
Displays the calculated set point being
used for auxiliary heating control
Displays the calculated set point being
Displays the ventilation damper
position calculated by the DCV control
Used to reset the filter alarm timer after
the filter has been cleaned or replaced
Displays the state of the condensate
Displays the state of the external/
remote occupancy input switch contact
Provides capability to force the
occupied or unoccupied mode
Displays if an OAT value is being
Used to display the active and
inactive occupancy control inputs
Used to define which occupancy inputs
to operate
Displays the origin of the
occupancy control
is a network broadcast)
Displays the SPT status
of the Rnet sensor
Displays the status of the
condensate overflow
Displays the actual set point
being used for cooling control
Displays the actual set point
being used for heating control
used for economizer control
Displays the actual number of
compressor stages operating
overflow switch contact
equipment to operate in an
received from the Network
are used to determine
occupancy mode.
59
APPENDIX A — WSHP OPEN SCREEN CONFIGURATION (cont)
→→→
SCREEN NAME POINT NAME
Occupied Heating
Occupied Cooling X 55 - 99 F 76 F
Unoccupied Heating X 40 - 90 F 55 F
Unoccupied Cooling X 55 - 99 F 90 F
Effective Heating
Set Point
Effective Cooling
Set Point
Optimal Start
Configuration
Occupied RH
Set Points
Configuration
Schedule
Weekly Schedule
Configuration
Schedule
Exception
Schedules 1 - 12
LEGEND
BAS — Building Automation System DCV — Demand Controlled Ventilation IAQ — Indoor Air Quality OAT — Outdoor Air Temperature RH Relative Humidity SAT — Supply Air Temperature SPT — Space Temperature TPI Third Party Integration
Set Point
Unoccupied RH
Set Point
DCV CTRL Start
Set Point
DCV Max CTRL
Set Point
Start Time
End Time X 00:00 - 24:00 18:00
Mon X No/Yes Yes
Tu e X N o /Ye s Ye s
Wed X No/Yes Yes
Thur X No/Yes Yes
Fri X No/Yes Yes
Sat X No/Yes No
Sun X No/Yes No
Start Month
Start Day X 0 - 31 0
Start Time X 00:00 - 23:59 0:00
End Month X 0 - 12 0
End Day X 0 - 31 0
End Time X 00:00 - 24:00 0:00
PASSWORD
LEVEL
User/Admin
Password level
access
User/Admin
Password level
access
User/Admin
Password level
access
EDITABLE RANGE DEFAULT NOTES
X 40 - 90 F 72 F
X0 - 10 F
X0 - 10 F
X 0 - 100% 65%
X 0 - 100% 90%
X 0 - 9999 ppm 500 ppm
X 0 - 9999 ppm 1050 ppm
X 00:00 - 23:59 06:00
X0 - 120
°°
°°
°°
°°
°
°
Defines the Occupied
Heating Set Point
Defines the Occupied
Cooling Set Point
Defines the Unoccupied
Heating Set Point
Defines the Unoccupied
Cooling Set Point
Takes into effect bias (maximum
allowable set point deviation)
Takes into effect bias (maximum
allowable set point deviation)
Uses historical data to calculate
ramp up time so as to be at set point
at occupied/unoccupied time
Defines the control set point used during occupied periods (Viewable only if Humidity Sensor = Installed/
Determines when to start
Dehumidification when occupied)
Defines the control set point used
during unoccupied periods
(Viewable only if Humidity Sensor =
Installed/Determines when to start
Dehumidification when unoccupied)
Defines the control set point used to
start increasing ventilation during
occupied periods (Viewable only if
Ventilation DMP Type = DCV)
Defines the control set point
used to define where the ventilation
will reach its maximum limit during occupied periods (Viewable only if Ventilation DMP Type = DCV/Used
to determine DCV ending control
Defines the start time for an
Defines the ending time of an
Determines if this day is included
Determines if this day is included
Determines if this day is included
Determines if this day is included
Determines if this day is included
Determines if this day is included
Determines if this day is included
Defines the start month of this
Defines the start day of this holiday
Determines the start time for this
Defines the month to end this
Defines the day to end this holiday
Determines the time to end this
point)
occupied period
occupied period
in this schedule
in this schedule
in this schedule
in this schedule
in this schedule
in this schedule
in this schedule
hoilday schedule
schedule
schedule
hoilday schedule
schedule
schedule
60
APPENDIX A — WSHP SCREEN OPEN CONFIGURATION (cont)
SCREEN NAME POINT NAME
Fan Mode
Fan On Delay X 0 - 30 sec 10 sec
Fan Off Delay X 0 - 180 sec 45 sec
Heating Enable X Disable/Enable Enable
Cooling Enable X Disable/Enable Enable
Minimum SAT in
Configuration
Unit
Configuration
Configuration
Service
Test
LEGEND
BAS — Building Automation System DCV — Demand Controlled Ventilation IAQ — Indoor Air Quality OAT — Outdoor Air Temperature RH Relative Humidity SAT — Supply Air Temperature SPT — Space Temperature TPI Third Party Integration
Cooling
Maximum SAT in
Heating
Damper Ventilation
Position
DCV Maximum Vent
Position
Filter Alarm Timer X 0 - 9999 hrs 0 hrs Disables Filter Alarm if set to 0
Pushbutton Override X Disable/Enable Enable Enables Override Feature on Rnet sensor
SPT Sensor Set Point
Adjustment
Lockout Cooling if
OAT <
Lockout Heating if
OAT >
Power Fail Restart
Delay
Occupancy Schedules X Disable/Enable Enable Enables unit occupied
Set Point Separation X 2 - 9 F 4 F
Test Mode
Fan Test X Disable/Enable Disable
Fan Speed
Compressor Test X Disable/Enable Disable
Dehumidification Test X Disable/Enable Disable
Testing Compressor
Aux Heating Test X Disable/Enable Disable
O Economizer Test X Disable/Enable Disable
H
2
Preposition OA
Damper
Open Vent
Damper 100%
SAT F Displays SAT
LCWT F
PASSWORD
LEVEL
Admin Password level access only
Admin Password level access only
EDITABLE RANGE DEFAULT NOTES
Auto= Intermittant operation during both
occupied and unoccupied periods/
X
X40 - 60 F50 F
X 80 - 140 F 110 F
X 0 - 100% 100%
X 0 - 100% 100%
X Disable/Enable Enable
X -65 - 80 F -65 F
X 35 - 150 F 150 F
X 0 - 600 sec 60 sec Delay before equipment starts
X Disable/Enable Disable
X Disable/Enable Disable
X Disable/Enable Disable Used to test OA damper operation
Auto/Continuous/
Always On
°°
°°
°°
°°
°°
Off/Low Speed/Medium
Speed/High Speed/On
Inactive/Heating/Cooling/
Dehumidify/TimeGard
Wait
°
°
Continuous
Continuous = Intermittant during unoccupied
periods and continuous during occupied
periods/Always on = fan operates
continuously during both occupied and
unoccupied periods
Defines the delay time before the fan begins
to operate after heating or cooling is started
Defines the amount of time the fan will
continue to operate after heating or
cooling is stopped
Provides capability to manually
disable heating operation
Provides capability to manually
disable cooling operation
Defines the minimum acceptable operating
temperature for the Supply Air
Defines the maximum acceptable operating
temperature for the Supply Air
Normally set to 100% if 2 position damper
type or set to minimum ventilation position if
Usually set at 100% - Used to limit maximum
Enables Set Point adjustment capability
Cooling is locked out when OAT is less than
configured value and OAT is actively being
Heating is locked out when OAT is greater
than configured value and OAT is actively
Used to enable test mode. Will automatically
Used to test all fan speeds. Sequences fan
from low to high and operates each speed for
1 minute. Resets to disable on completion
Used to test compressor cooling and heating
operation. Sequences cooling stage 1, then
stage 2, then heating stage 2 and reduces
capacity to stage 1. Operates for 1 minute per
Used to test entering/return air water loop
economizer coil operation. Sequences fan on
and opens economizer coil water valve for 1
minute. Resets to disable on completion
damper type = DCV
damper opening in DCV mode
on Rnet Sensor
broadcast
being broadcast
Used to enforce minimum
set point separation
reset to disable after 1 hour
Displays current fan operation
step. Resets to disable on completion.
Used to test dehumification mode -
Operates for 2 minutes. Resets to
disable on completion.
Displays compressor test mode
Used to test auxiliary heat.
Sequences fan on and enables
heating coil for 1 minute. Resets to
disable on completion
Used to preposition OA damper
actuator to set proper preload
Displays Leaving Condenser
Water Temperature
61
APPENDIX A — WSHP SCREEN OPEN CONFIGURATION (cont)
SCREEN NAME POINT NAME
# of Fan Speeds
G Output Type X Fan On/Fan Low Fan On
Compressor Stages X One Stage/Two Stages One Stage
Reversing Valve Type X O type output/B type output O type
Leaving Air Auxiliary
Heat Type
Entering Air Water
Economizer Type
2-Position Water
Val ve Type
Modulating Water
Val ve Type
Ventilation Damper
Ty pe
Damper Actuator Type X (0-10 volt)/(2-10 volt) 0-10 volt
Configuration
Service
Configuration
LEGEND
BAS — Building Automation System DCV — Demand Controlled Ventilation IAQ — Indoor Air Quality OAT — Outdoor Air Temperature RH Relative Humidity SAT — Supply Air Temperature SPT — Space Temperature TPI Third Party Integration
Humidity Sensor X None/Installed None
Factory Dehumidifica-
tion Reheat Coil
Occupancy Input Logic
Condensate Switch
Alarm Delay
Condensate Switch
Alarm State
Minimum Condenser
Water Temperature in
Heating
Maximum Condenser Water Temperature in
Heating
Minimum Condenser
Water Temperature in
Cooling
Maximum Condenser Water Temperature in
Cooling
IAQ sensor
minimum input
IAQ sensor
maximum input
IAQ sensor
minimum output
IAQ sensor
maximum output
PASSWORD
LEVEL
Admin Password
level access only
EDITABLE RANGE DEFAULT NOTES
X 1,2,3 3
X
X None/2-Position/Modulating None
X Normally Closed/Normally Open
X Normally Closed/Normally Open
X None/2-Position/DCV None
X None/Installed None
X Occupied Open/Occupied Closed
X 5 - 600 seconds 10 sec
X Alarm OPEN/Alarm CLOSED
X25 - 60 F60 F
X 65 - 100 F 90 F
X30 - 60 F60 F
X 85 - 120 F 95 F
X 0 - 5 ma 4 ma
X 5 - 20 ma 20 ma
X 0 - 9999 ppm 0 ppm
X 0 - 9999 ppm 2000 ppm
None/2-Position HW/1 Stage
Electric/Modulating HW
°°
°°
°°
°°
None
Normally
Closed
Normally
Closed
Occupied
CLOSED
Alarm
CLOSED
Used to set number of
fan motor speeds
When set to Fan On, G output is energized when ever any fan speed is active (required for ECM and Fan
control board). When set to Fan
Low, output is only energized for
Set to Installed if factory-installed
Used to determine external occu-
pancy switch contact occupied state
Delay before equipment alarms on
acceptable water loop temperature
acceptable water loop temperature
acceptable water loop temperature
acceptable water loop temperature
Maximum output current (mA) for
Corresponding value in ppm for
Corresponding value in ppm for
Low Speed
Defines the number of stages of compression
Determines reversing valve
signal output type
Determines Auxiliary
Reheat Coil Type
Determines Entering Air
Economizer Coil Type
Determines type of 2-position
water valve used
Determines type of modulating
water valve used
Determines type of ventilation
damper control to be used
Used to determine ventilation
damper output signal range
(closed - open)
Set to Installed if humidity
sensor is present
dehumidification reheat coil
is present
high condensate level
Determine Alarm state of
condensate switch input
Determines the minimum
to start heating
Determines the maximum
to start heating
Determines the minimum
to start cooling
Determines the maximum
to start cooling
Minimum output current (mA)
for IAQ sensor
IAQ sensor
minimum output current
maximum output current
62
APPENDIX A — WSHP SCREEN OPEN CONFIGURATION (cont)
SCREEN NAME POINT NAME
SPT Occupied Alarm
Hysteresis
SPT Alarm Delay X 0 - 30 min per degree 10 min
SPT Unoccupied Low
Alarm Temperature
SPT Unoccupied High
Alarm Temperature
SAT Low SAT
Alarm Limit
SAT High SAT
Alarm Limit
Condensate Overflow
Alarm Delay
Space Humidity Occupied
High Alarm Limit
Configuration
Alarm
Configuration
Configuration
Linkage
BAS — Building Automation System DCV — Demand Controlled Ventilation IAQ — Indoor Air Quality OAT — Outdoor Air Temperature RH Relative Humidity SAT — Supply Air Temperature SPT — Space Temperature TPI Third Party Integration
Space Humidity Alarm
Delay
Space Humidity Unoccu-
pied High Alarm Limit
IAQ/Ventilation Occupied
High Alarm Limit
IAQ/Ventilation
Alarm Delay
Rnet Sensor SPT Alarm X Ignore/Display Ignore
Rnet Sensor SAT Alarm X Ignore/Display Ignore
Rnet Sensor Compressor
Lockout Alarm
Rnet Sensor Condenser
Water Temperature Alarm
Rnet Sensor Condensate
Overflow Alarm
Rnet Sensor Dirty
Filter Alarm
Rnet Sensor Space
High Humidity Alarm
Loop Control Network
Number
Loop Control Network
Address
Number of Linked Heat
Pumps
LEGEND
PASSWO RD
LEVEL
Admin Password level access only
EDITABLE RANGE DEFAULT NOTES
Defines the hysteresis applied above
X2 - 20 F5 F
X 35 - 90 F 45 F
X 45 - 100 F 95 F
X 15 - 90 F 45 F
X 90 - 175 F 120 F
X 5 - 600 sec 10 sec
X 45% - 100% 100%
X 0 - 30 min per % RH 5 min
X 45% - 100% 100%
X 0 - 9999 ppm 1100 ppm
X 0.1 - 1.0 min per ppm 0.25 min
X Ignore/Display Display
X Ignore/Display Display
X Ignore/Display Display
X Ignore/Display Display
X Ignore/Display Ignore
°°
°°
°°
°°
°°
the cooling and below the heating set
points before an alarm condition will
Used to calculate the delay time before
an alarm is generated after the alarm
Defines the fixed unoccupied
Defines the fixed unoccupied
Defines the fixed minimum
Defines the fixed maximum
Defines the delay time before an alarm
is generated after the alarm condition
Defines the fixed occupied
high space RH alarm limit
Used to calculate the delay time before
an alarm is generated after the alarm
Defines the fixed unnoccupied
high space RH alarm limit
Defines the fixed occupied high
space IAQ/Ventilation alarm limit
Used to calculate the delay time before
an alarm is generated after the alarm
Determines if the SPT alarm is
displayed on the local Rnet sensor
Determines if the SAT alarm is
displayed on the local Rnet sensor
Determines if the Compressor Lockout
alarm is displayed on the local Rnet
Determines if the Condenser Water
Temperature alarm is displayed on the
Determines if the Condensate
Overflow alarm is displayed on the
Determines if the Dirty Filter alarm is
displayed on the local Rnet sensor
Determines if the High Space
RH alarm is displayed on the
occur
condition occurs
ow SPT alarm limit
high SPT alarm limit
SAT alarm limit
SAT alarm limit
occurs
condition occurs
condition occurs
sensor
local Rnet sensor
local Rnet sensor
local Rnet sensor
See TPI
See TPI
See TPI
63
64
65
Copyright 2009 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53500055-01 Printed in U.S.A. Form 50PS-3SI Pg 66 7-09 Replaces: 50PS-2SI
50PSH,PSV,PSD
START-UP CHECKLIST
CUSTOMER:___________________________ JOB NAME: _______________________________________
MODEL NO.:___________________________ SERIAL NO.:____________________ DATE:_________
I. PRE-START-UP
DOES THE UNIT VOLTAGE CORRESPOND WITH THE SUPPLY VOLTAGE AVAILABLE? (Y/N)
HAVE THE POWER AND CONTROL WIRING CONNECTIONS BEEN MADE AND TERMINALS TIGHT? (Y/N)
HAVE WATER CONNECTIONS BEEN MADE AND IS FLUID AVAILABLE AT HEAT EXCHANGER? (Y/N)
HAS PUMP BEEN TURNED ON AND ARE ISOLATION VALVES OPEN? (Y/N)
HAS CONDENSATE CONNECTION BEEN MADE AND IS A TRAP INSTALLED? (Y/N)
IS AN AIR FILTER INSTALLED? (Y/N)
II. START-UP
IS FAN OPERATING WHEN COMPRESSOR OPERATES? (Y/N)
IF 3-PHASE SCROLL COMPRESSOR IS PRESENT, VERIFY PROPER ROTATION PER INSTRUCTIONS. (Y/N)
UNIT VOLTAGE — COOLING OPERATION
PHASE AB VOLTS PHASE BC VOLTS PHASE CA VOLTS
(if 3 phase) (if 3 phase)
PHASE AB AMPS
PHASE BC AMPS PHASE CA AMPS (if 3 phase) (if 3 phase)
CONTROL VOLTAGE
IS CONTROL VOLTAGE ABOVE 21.6 VOLTS? (Y/N) . IF NOT, CHECK FOR PROPER TRANSFORMER CONNECTION.
TEMPERATURES
FILL IN THE ANALYSIS CHART ATTACHED.
COAXIAL HEAT EXCHANGER
COOLING CYCLE: FLUID IN
FFLUID OUT F PSI FLOW
HEATING CYCLE: FLUID IN
FFLUID OUT F PSI FLOW
AIR COIL COOLING CYCLE:
AIR IN
HEATING CYCLE: AIR IN
FAIR OUT F
FAIR OUT F
CL-1
HEATING CYCLE ANALYSIS
PSI
SAT
AIR
COIL
°F
°F
LIQUID LINE
COOLING CYCLE ANALYSIS
a50-8494
EXPANSION
VALVE
°F
FLUID IN
°F
PSI
COAX
FLUID OUT
°F
PSI
LOOK UP PRESSURE DROP IN TABLE 31 TO DETERMINE FLOW RATE
PSI
°F
SUCTION
COMPRESSOR
DISCHARGE
SAT
°F
AIR
COIL
°F
°F
EXPANSION
VALVE
LIQUID LINE
COAX
°F
FLUID IN
°F
PSI
FLUID OUT
°F
PSI
LOOK UP PRESSURE DROP IN TABLE 31 TO DETERMINE FLOW RATE
a50-8495
SUCTION
COMPRESSOR
DISCHARGE
HEAT OF EXTRACTION (ABSORPTION) OR HEAT OF REJECTION =
FLOW RATE (GPM) x TEMP. DIFF. (DEG. F) x FLUID FACTOR* =
SUPERHEAT = SUCTION TEMPERATURE – SUCTION SATURATION TEMPERATURE
=
(DEG F)
SUBCOOLING = DISCHARGE SATURATION TEMPERATURE – LIQUID LINE TEMPERATURE
=
*Use 500 for water, 485 for antifreeze.
(DEG F)
CUT ALONG DOTTED LINE CUT ALONG DOTTED LINE
(Btu/hr)
Copyright 2009 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53500055-01 Printed in U.S.A. Form 50PS-3SI Pg CL-2 7-09 Replaces: 50PS-2SI
97B0038N04
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -- - - - - - - - - - - - - - - - - - - -
Loading...