48/50PG C03-14
48/50PM C16-28
Single Package Rooftop Units
With COMFORTLinkt Controls Version 5.x
and PURONR (R-410A) Refrigerant
Controls, Start-Up, Operation, Service
and Troubleshooting Instructions
IMPORTANT: This literature covers 48/50PG03−14 and
48/50PM16−28 models with Comfortlink Software version 5.x.
The 48/50PG C16−28 (15 – 25 ton) model reference has been
removed from this manual; however version 5.x software is
backward compatible with all Comfortlink PG models. Refer to
past manuals for obsolete model information.
Installation and servicing of air-conditioning equipment can be
hazardous due to system pressure and electrical components. Only
trained and qualified service personnel should install, repair, or
service air-conditioning equipment. Untrained personnel can
perform the basic maintenance functions of replacing filters.
Trained service personnel should perform all other operations.
When working on air-conditioning equipment, observe precautions
in the literature, tags and labels attached to the unit, and other
safety precautions that may apply. Follow all safety codes. Wear
safety glasses and work gloves. Use quenching cloth for unbrazing
operations. Have fire extinguishers available for all brazing
operations.
Follow all safety codes. Wear safety glasses and work gloves. Have
fire extinguisher available. Read these instructions thoroughly and
follow all warnings or cautions attached to the unit. Consult local
building codes and National Electrical Code (NEC) for special
requirements.
Recognize safety information. This is the safety−alert symbol
When you see this symbol on the unit and in instructions or
manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, and
CAUTION. These words are used with the safety−alert symbol.
DANGER identifies the most serious hazards which will result in
severe personal injury or death. WARNING signifies a hazard
which could result in personal injury or death. CAUTION is used
to identify unsafe practices which may result in minor personal
injury or product and property damage. NOTE is used to highlight
suggestions which will result in enhanced installation, reliability, or
operation.
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could cause personal
injury or death.
Before performing service or maintenance operations
on unit, turn off main power switch to unit and install
lockout tag. Ensure electrical service to rooftop unit
agrees with voltage and amperage listed on the unit
rating plate.
!
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may cause equipment
damage.
This unit uses a microprocessor−based electronic control
system. Do not use jumpers or other tools to short out
components or to bypass or otherwise depart from
recommended procedures. Any short−to−ground of the
control board or accompanying wiring may destroy the
electronic modules or electrical components.
.
2
!
WARNING
FIRE, EXPLOSION HAZARD
Failure to follow this warning could result in personal
injury, death and/or property damage.
Improper installation, adjustment, alteration, service, or
maintenance can cause property damage, personal
injury, or loss of life. Refer to the User’s Information
Manual provided with this unit for more details.
Do not store or use gasoline or other flammable vapors
and liquids in the vicinity of this or any other appliance.
What to do if you smell gas:
1. DO NOT try to light any appliance.
2. DO NOT touch any electrical switch, or use any
phone in your building.
3.IMMEDIATELY call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s
instructions.
4. If you cannot reach your gas supplier, call the fire
department.
GENERAL
This publication contains Start−Up, Controls, Operation, Service,
and Troubleshooting information for the 48/50PG and 48/50PM
rooftop units. (See Table 1.) These units are equipped with
ComfortLink controls version 5.X or higher and use Puron
refrigerant. The specific base unit installation instructions and/or
wiring label diagram may also be required in conjunction with this
book as a guide to a specific unit on the roof. All the units in table
1 are Constant Volume (CV) units that provide stand−alone or
network operation.
Table 1 – Rooftop Units
MODELSIZENOMINAL TONS
032
043
054
48/50PG
48/50PM
065
076
087.5
098.5
1210
1412.5
1615
2018
2420
28
25
BASIC CONTROL USAGE
ComfortLink Control
The ComfortLink control is a comprehensive unit-management
system. The control system is easy to access, configure, diagnose
and troubleshoot.
The ComfortLink control is fully communicating and cable-ready
for connection to the Carrier Comfort Network (CCN) building
management system. The control provides high-speed
communications for remote monitoring via the Internet. Multiple
units can be linked together (and to other ComfortLink control
equipped units) using a 3-wire communication bus.
The ComfortLink control system is easy to access through the use
of a unit-mounted display module. There is no need to bring a
separate computer to this unit for start-up. Access to control menus
is simplified by the ability to quickly select from 11 menus. A
scrolling readout provides detailed explanations of control
information. Only four, large, easy-to-use buttons are required to
maneuver through the entire controls menu. The display readout is
designed to be visible even in bright sunlight.
For added service flexibility, an accessory hand-held Navigator
module is also available. This portable device has an extended
communication cable that can be plugged into the unit’s
communication network at the main control box. The Navigator
display provides the same menu structure, control access and
display data as is available at the unit-mounted Scrolling Marquee
display.
MODE
Run Status
Service Test
Temperature
Pressures
Setpoints
Inputs
Outputs
Configuration
Time Clock
Operating Modes
Alarms
Alarm Status
ESCAPE
ENTER
C06320
Fig. 1 − Scrolling Marquee
Scrolling Marquee
This device is the keypad interface used to access the control
information, read sensor values, and test the unit. The Scrolling
Marquee is located in the main control box and is standard on all
units. The Scrolling Marquee display is a 4-key, 4-character,
16-segment LED (light-emitting diode) display module. The
display also contains an Alarm Status LED. (See Fig. 1.)
The display is easy to operate using 4 buttons and a group of 11
LEDs that indicate the following menu structures:
Run Status
Service Test
Temperatures
Pressures
Set points
Inputs
Outputs
Configuration
Timeclock
Operating Modes
Alarms
Through the Scrolling Marquee, the user can access all of the
inputs and outputs to check on their values and status, configure
operating parameters plus evaluate the current decision status for
operating modes. The control also includes an alarm history which
can be accessed from the display. In addition, through the Scrolling
Marquee, the user can access a built-in test routine that can be used
at start-up commissioning and to diagnose operational problems
with the unit. (See Table 2.)
48/50PG and PM
3
Accessory Navigator Display
The accessory hand-held Navigator display can be used with the
48/50PG and 48/50PM units. (See Fig. 2.) The Navigator display
operates the same way as the Scrolling Marquee device. The
Navigator display is plugged into the LEN (local equipment
network) port on either TB1/TB2 or the J3 port on the ECB
(economizer control board).
48/50PG and PM
Operation
All units are shipped from the factory with the Scrolling Marquee
display, which is located in the main control box. (See Fig. 1.) In
addition, the ComfortLink control also supports the use of the
handheld Navigator display.
Both displays provide the user with an interface to the
ComfortLink control system. The displays have up and down
arrow keys, an ESCAPE key and an ENTER key. These keys are
used to navigate through the different levels of the display
structure. The Navigator display and the Scrolling Marquee operate
in the same manner, except that the Navigator display has multiple
lines of display and the Scrolling Marquee has a single line. All
further discussions and examples in this document will be based on
the Scrolling Marquee display. See Table 2 for the menu structure.
The four keys are used to navigate through the display structure,
which is organized in a tiered mode structure. If the buttons have
not been used for a period, the display will default to the AUTO
VIEW display category as shown under the RUN STATUS
category. To show the top-level display, press the ESCAPE key
until a blank display is shown. Then use the up and down arrow
keys to scroll through the top-level categories. These are listed in
Appendix A and will be indicated on the Scrolling Marquee by the
LED next to each mode listed on the face of the display.
When a specific mode or sub-mode is located, push the ENTER
key to enter the mode. Depending on the mode, there may be
additional tiers. Continue to use the up and down keys and the
ENTER keys until the desired display item is found. At any time,
the user can move back a mode level by pressing the ESCAPE key.
Once an item has been selected the display will flash showing the
item, followed by the item value and then followed by the item
units (if any).
Items in the Configuration and Service Test modes are password
protected. The display will flash PASS and WORD when required.
Use the ENTER and arrow keys to enter the four digits of the
password. The default password is 1111.
C
o
m
f
o
r
t L
N
in
A
V
I
G
A
T
O
T
IM
E
W
L
W
S
E
T
M
O
D
Ru
n Sta
S
e
rv
ice
T
em
p
era
P
res
s
ure
s
S
e
tpo
in
ts
In
pu
ts
O
utp
uts
C
on
fig
u
ra
tion
T
im
e C
lo
ck
O
per
ating
M
od
es
A
la
rm
s
E
N
T
E
R
R
E
1
2
T
.
5
8
5
4
T
.
6
°
F
4
4
P
.1
°
F
4
4
.
0
°
F
E
Ala
rm
Sta
tus
tu
s
Te
s
t
ture
s
E
S
C
Fig. 2 − Accessory Navigator Display
Pressing the ESCAPE and ENTER keys simultaneously will scroll
an expanded text description across the display indicating the full
meaning of each display point. Pressing the ESCAPE and ENTER
keys when the display is blank (MODE LED level) will return the
display to its default menu of rotating AUTO VIEW display items.
In addition, the password will need to be entered again before
changes can be made.
Changing item values or testing outputs is accomplished in the
same manner. Locate and display the desired item. If the display is
k
in rotating auto-view, press the ENTER key to stop the display at
the desired item. Press the ENTER key again so that the item value
flashes. Use the arrow keys to change the value of state of an item
and press the ENTER key to accept it. Press the ESCAPE key and
the item, value or units display will resume. Repeat the process as
required for other items.
There are some points that can be forced from the Scrolling
Marquee or the Navigator. If the user needs to force a variable,
follow the same process as when editing a configuration parameter.
A forced variable, regardless where the force has come from will
be displayed with a blinking “.” on a Scrolling Marquee and a
blinking “f” on a Navigator following its value. For example, if
economizer commanded position (EC.CP) is forced, the Navigator
display shows “80f”, where the “f” is blinking to signify a force on
the point. The Scrolling Marquee display shows “80.” Where the
“.” is blinking to signify a force on the point. Remove the force by
C06321
selecting the point that is forced with the key ENTER and then
pressing the up and down arrow keys simultaneously.
Depending on the unit model, factory-installed options and
field-installed accessories, some of the items in the various Mode
categories may not apply.
System Pilott and Touch Pilot Devices
The System Pilot device (33PILOT-01) and Touch Pilot device
(33CNTPILOT) can be used as CCN communication
user−interfaces. These devices can be put on the CCN bus and
addressed to communicate with any other device on the network.
Unlike the Scrolling Marquee and Navigator, these pilots read the
unit’s CCN tables and its CCN points can be monitored, forced, or
configured. The Pilot devices can be used to install and
commission a 3V zoning system, linkage compatible air source,
universal controller, and all other devices operating on the Carrier
communicating network.
Additionally, the System Pilot device can serve as a wall-mounted
temperature sensor for space temperature measurement. The
occupant can use the System Pilot device to change set points. A
security feature is provided to limit access of features for
unauthorized users. See Fig. 3 for System Pilot device details.
CCN Tables and Display
In addition to the unit−mounted Scrolling Marquee display, the
user can also access the same information through the CCN tables
by using the Service tool or other CCN programs/devices. The
variable names used for the CCN tables and the Scrolling Marquee
menus may be different and more items may be displayed in the
CCN tables. Details on the CCN tables are included with the local
display menus in Appendix A. Appendix A is structured towards
the organization of the local display (Scrolling Marquee) menus.
Because of the variety of CCN programs and devices, the CCN
tables, sub−tables, and points are referenced within that
organization.
4
RUN
/
STATUS
Auto View
of
Run Status
(VIEW)
↓
Software
Version
Numbers
(VERS)
↓
Control
Modes
(MODE)
↓
Cooling
Status
(COOL)
↓
Heating
Status
(HEAT)
↓
Economizer
Status
(ECON)
↓
Outside Air
Unit Status
(OAU)
↓
Component
Run Hours
(HRS)
↓
Component
Starts
(STRT)
SERVICE
TEST
Service Test
Mode
(TEST)
↓
Test Indepen
dent
Outputs
(INDP)
↓
Test Fans
(FANS)
↓
Test Cooling
(COOL)
↓
Test
Humidi‐MiZer™
(HMZR)
↓
Test Heating
(HEAT)
Table 2 – Scrolling Marquee Mode and Menu Display Structure
There is a hierarchy in CCN with regards to forcing a point.
Programs and devices write a force at different priority levels. A
higher level (smaller number, 1 being the highest) will override a
lower level force. The Scrolling Marquee uses a Control Force at
level 7. The Navigator writes a Service Force which is level 3.
System Pilots and Touch Pilots write Supervisor Forces at level 4.
Network programs can be set to write different level priority forces.
Generic Status Display Table
The GENERIC points table allows the service/installer the ability
to create a custom table in which up to 20 points from the 5 CCN
categories (Points, Config, Service−Config, Set Point, and
Maintenance) may be collected and displayed.
In the Service−Config table section, there is a table named
“GENERICS.” This table contains placeholders for up to 20 CCN
point names and allows the user to decide which points are
displayed in the GENERIC points sub−table under the status
display table. Each one of these placeholders allows the input of an
8−character ASCII string. Using a CCN interface, enter the Edit
mode for the Service−Config table “GENERICS” and enter the
CCN name for each point to be displayed in the custom points
table in the order they will be displayed. When done entering point
names, download the table to the rooftop unit control.
IMPORTANT: The computer system software (ComfortVIEW,
Service Tool, etc.) that is used to interact with CCN controls,
always saves a template of items it considers as static (e.g., limits,
units, forcibility, 24−character text strings, and point names) after
the software uploads the tables from a control. Thereafter, the
software is only concerned with run time data like value and
hardware/force status. With this in mind, it is important that
anytime a change is made to the Service−Config table
“GENERICS” (which in turn changes the points contained in the
GENERIC point table), that a complete new upload be performed.
This requires that any previous table database be completely
removed first. Failure to do this will not allow the user to display
the new points that have been created and the CCN interface will
have a different table database than the unit control.
5
Conventions Used in This Manual
The following conventions for discussing configuration points for
the local display (Scrolling Marquee or Navigator accessory) will
be used in this manual.
Point names will be written with the Mode name first, then any
submodes, then the point name, each separated by an arrow symbol
(→). Names will also be shown in bold and italics. As an example,
the Thermostat Control Type which is located in the Configuration
mode, and Unit sub-mode would be written as Configuration→
UNIT→T.CTL.
This path name will show the user how to navigate through the
local display to reach the desired configuration. The user would
scroll through the modes and sub-modes using the up and down
keys. The arrow symbol in the path name represents pressing
ENTER to move into the next level of the menu structure.
When a value is included as part of the path name, it will be shown
at the end of the path name after an equals sign. If the value
represents a configuration setting, an explanation will be shown in
parenthesis after the value. As an example,
Configuration→UNIT→T.CTL= 1 (1 Stage Y1).
Pressing the ESCAPE and ENTER keys simultaneously will scroll
an expanded text description of the point name across the display.
48/50PG and PM
The expanded description is shown in the local display tables but
will not be shown with the path names in text.
The CCN point names are also referenced in the local display
tables for users configuring the unit with CCN software instead of
the local display. See Appendix A of this manual.
IMPORTANT: Do not attempt to start unit, even momentarily,
until all items on the Start−Up Checklist (last page) and the
following steps have been read/completed.
Unit Preparation
Check that unit has been installed in accordance with these
installation instructions and all applicable codes.
Compressor Mounting
Compressors are internally spring mounted. Do not loosen or
remove compressor holddown bolts.
Refrigerant Service Ports
Each independent refrigerant system has a total of 3 Schrader-type
service gauge ports per circuit. One port is located on the suction
line, one on the compressor discharge line, and one on the liquid
line. Be sure that caps on the ports are tight.
Crankcase Heater(s)
Compressor crankcase heater operation varies depending on the
unit size and type. In general for all units, the crankcase heaters are
energized if there is power to the unit, the compressor is not
operating, and the ambient temperature is below 75F.
IMPORTANT: Unit power must be on for 24 hours prior to
start−up. Otherwise, damage to compressor may result.
START-UP
Compressor Rotation
!
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in unit damage.
Improper wiring will cause compressor stoppage and alarm.
Correct wiring by switching leads as indicated below.
On 3-phase units, it is important to be certain the compressors are
rotating in the proper direction. To determine whether or not
compressors are rotating in the proper direction, use a
phase-rotation meter on the unit input power to check for
L1-L2-L3 or clockwise rotation or use the Service Test mode to
energize a compressor. If the compressor is rotating in the wrong
direction, the controls will stop the compressor and display alarm
for “Circuit x Failure to Pressurize,” where x is the corresponding
A, B or C compressor circuit.
NOTE: Indoor or outdoor fan rotation direction may not indicate
proper input power phase sequence, as some 3-phase units use
single-phase fan motors.
To correct the wrong compressor rotation direction, perform the
following procedure:
1. Turn off power to the unit and lock out the power.
2. Switch any two of the incoming unit power leads.
3. Turn on power to the unit.
4. Verify corrected compressor rotation.
Power Supply
All 208/230-v units are factory wired for 230-v power supply. If
the 208/230-v unit is to be connected to a 208-v power supply, the
transformers (TRAN1, TRAN2 and TRAN3) must be rewired by
moving the wire from the 230-volt connection and moving to the
200-volt terminal on the primary side of the transformer. Refer to
unit label diagram for additional information.
Internal Wiring
Check all electrical connections in unit control boxes; tighten as
required.
Evaporator Fan
Fan belt and variable pulleys are factory−installed, but may need to
be adjusted for specific applications. Be sure that the fans rotate in
the proper direction. See Appendix C for unit specific fan
performance data. See Appendix D for unit specific air quality
limits, evaporator fan motor specifications, FIOP static pressures,
and fan RPM for various motor pulley settings. To alter fan
performance, see Evaporator Fan Performance Adjustment in the
Service section.
NOTE: Units equipped with Adaptive Fan still must conform to
minimum CFM requirements at all times and the fan speed
configurations must be set for this compliance.
6
OUTDOOR AIR
SCREEN
(HIDDEN)
ELECTRICAL
OPTIONS PANEL
CONTROL BOX
AND
COMPRESSOR
INDOOR MOTOR
ACCESS DOOR
CONDENSER COIL
ACCESS PANEL
BASEPAN CONNECTIONS
ACCESS PANEL
FILTER ACCESS DOOR
Fig. 4 − 48/50PG03−14 Size Units, Panel and Filter Locations (48PG03−07 Unit Shown)
OUTDOOR AIR
SCREEN
(HIDDEN)
PEM 1 & 2
CONTROL BOX
CONVENIENCE
OUTLET
CO SENSOR
2
RETURN SMOKE
DETECTOR
SMOKE CONTROL
MODULE
FILTER ACCESS
DOOR
GAS SECTION
Fig. 5 − 48/50PM16−28 Size Units, Panel and Filter Locations (48PM24 Unit Shown)
GAS SECTION
ACCESS
48/50PG and PM
C07002
C08076
7
Condenser Fans and Motors
Condenser fans and motors are factory set. Refer to Condenser-Fan
Adjustment section as required.
Return−Air Filters
Check that correct filters are installed in filter tracks (see Physical
Data table in Installation Instructions). Do not operate unit without
return-air filters.
NOTE: For units with 4-in. filter option, units are shipped with
standard 2-in. filters. To install 4-in. filters, the filter spacers must
be removed.
Outdoor−Air Inlet Screens
Outdoor-air inlet screens must be in place before operating unit.
Air Baffles
Units with Humidi-MiZer option are equipped with
Motormaster control to maintain adequate discharge pressure for
proper unit operation during low ambient operation.
Field-fabricated and installed wind baffles may be required. See
Optional Humidi-MiZer Dehumidification System section.
Accessory Installation
Check to make sure that all accessories including space thermostats
48/50PG and PM
and sensors have been installed and wired as required by the
instructions and unit wiring diagrams.
Orifice Change (48PG and 48PM)
This unit is factory assembled for heating operation using natural
gas at an elevation from sea level to 2000 ft.
Use accessory high altitude kit when installing this unit at an
elevation of 2000 to 7000 ft. For elevations above 7000 ft, refer to
High Altitude section to identify the correct orifice size for the
elevation. Purchase these orifices from your local Carrier dealer.
Follow instructions in accessory Installation Instructions to install
the correct orifices.
Use accessory LP (liquid propane) gas conversion kit when
converting this unit for use with LP fuel usage for elevations up to
7000 ft. For elevations above 7000 ft, refer to High Altitude
section to identify the correct orifice size for the elevation.
Purchase these orifices from your local Carrier dealer. Follow
instructions in accessory Installation Instructions to install the
correct orifices.
Gas Heat (48PG and 48PM)
Inspect the gas heat section of the unit. Verify the number of
burners match the number of heat exchanger openings and the
burner assembly is properly aligned. If the orifices were changed
out for elevation or Liquid Propane purposes, verify proper
installation. Visually inspect other components in heat section.
Verify gas pressures before turning on heat as follows:
1. Turn off field-supplied manual gas stop, located external to
unit.
2. Connect pressure gauge to supply gas tap, located on
field-supplied manual shutoff valve. (See Fig. 6.)
3. Connect pressure gauge to manifold pressure tap.
4. Turn on field-supplied manual gas stop. Enter Service Test
mode by setting Service Test→TEST to “ON” using the
Scrolling Marquee display. Temporarily install the jumper
wire between “R” and “W1” on TB1. Use the Service Test
feature to set Service Test→HEAT→HT.1 to ON (first stage
of heat) using the Scrolling Marquee.
MANUAL SHUT OFF
(FIELD SUPPLIED)
GAS
SUPPLY
PRESSURE TAP
(1/8˝ NPT PLUG)
TO
UNIT
UNION
SEDIMENT TRAP
C09242
Fig. 6 − Field Gas Piping
5. After the unit has run for several minutes, verify the supply
gas pressure is between 5.5−in. wg to 13.0−in. wg, and the
manifold pressure is 3.50−in. wg on sizes 03−14,
3.00−in.wg on sizes 16−28 with a vertical supply or
2.95−in.wg on sizes 16−28 with a horizontal supply. If
manifold pressure must be adjusted, refer to Gas Valve
Adjustment section.
NOTE: Supply gas pressure must not exceed 13.0−in. wg.
6. Set Service Test→HEAT→HT.1 to OFF using Scrolling
Marquee.
7. Remove jumper wire if the unit will be operating under
thermostat mode. The jumper must remain if a space
temperature sensor (T-55, T-56, T-58, or System Pilot
device) will control the unit.
8. Exit Service Test mode by setting Service Test→TEST to
“OFF” using the Scrolling Marquee.
EnergyX
For units equipped with the EnergyX factory installed option, there
is an EnergyXv2 Supplement Installation Instructions in the unit’s
information packet. Follow the start up sequence and complete the
start up checklist contained in the EnergyXv2 manual to complete
unit startup.
CONTROLS QUICK SET−UP
The following information will provide a quick guide to setting up
and configuring the 48/50PG and 48/50PM series units with
ComfortLink controls. Unit controls are pre-configured at the
factory for factory-installed options. Field-installed accessories will
require configuration at start-up. Service Test is recommended for
initial start−up. Additionally, specific job requirements may require
changes to default configuration values. See the CCN and Display
parameter tables and other sections of these instructions for more
details. Refer to the Major System Components or accessory
installation instructions for specific wiring detail.
Control Set Point and Configuration Log
During start up, accessory installation, and equipment service set
points and/or configuration changes might have to be made. When
setting set points or changing configuration settings,
documentation is recommended. The Control Log starting on page
192 should be filled out and left with the unit at all times, a copy
should also be provided to the equipment owner.
Thermostat Control
Wire accessory thermostat to the corresponding R, Y1, Y2, W1,
W2, and G terminals on the field connection terminal board located
at the unit control box.
The Unit Control Type configuration, Configuration→UNIT→U.CTL, default value is for Thermostat (2) so there is
no need to configure this item.
The Thermostat Control Type, Configuration →UNIT→T.CTL,
selects the unit response to the thermostat inputs above.
8
Space Temperature Sensor Control − Direct Wired
(T−55 or T−56 or T−59)
Wire accessory space temperature sensor(s) to the T-55 terminals
on the field connection terminal board located at the unit control
box. Refer to Field-Installed Accessories section for additional
information.
The Unit Control Type configuration, Configuration→UNIT→U.CTL, must be set to Space Sensor (3). The jumper
wire in the installer’s packet must be connected between R and W1
for heating mode to operate.
T−58 Communicating Room Sensor
Install the T-58 communicating thermostat. Connect the CCN
communication bus from the T-58 to the CCN terminals on the
field connection terminal board located at the unit control box.
Configure the unit’s CCN communication element number, bus
number, and baud rate. Configure the T−58’s CCN communication
bus number and baud rate the same as the unit, while the element
number has to be different. Configure the T−58 to send SPT to the
unit’s element number. Refer to the Field−Installed Accessories
section for additional information.
The Unit Control Type configuration, Configuration→UNIT→U.CTL, must be set to Space Sensor (3). The jumper
wire in the installer’s packet must be connected between R and W1
for heating mode to operate.
CCN Linkage Control
The CCN communication must be properly configured for the
48/50PG and 48/50PM units and all other devices. Linkage
configuration is automatically done by the supervisory CCN
Linkage device.
The Unit Control Type configuration, Configuration→UNIT→U.CTL must be set to Space Sensor (3). The jumper
wire in the installer’s packet must be connected between R and W1
for heating mode to operate.
Installation of an accessory supply air temperature (SAT) sensor in
the supply duct is recommended for Linkage applications. A
supply duct SAT measurement is valid for heating mode display,
while the factory-standard internal SAT is not valid for heating due
to its location upstream of the heating section. When installing the
supply duct SAT, the heating mode display is enabled by setting
Configuration→HEAT→SAT.H to ENBL.
Installation of an accessory return air temperature (RAT) sensor in
the return duct and wired to the space sensor input is recommended
for Linkage applications. This will allow the unit to continue to
run if Linkage communication is lost.
System Pilot − Communication Space Sensor
Install the System Pilot and connect the CCN communication bus
from it to the unit’s CCN connection on the low voltage terminal
board. Configure the unit’s CCN communication element number,
bus number, and baud rate. Refer to the System Pilot’s installation
instructions for configuring it to be used as a space temperature and
attaching it to a unit.
Thermidistat Control
The thermidistat is a thermostat and humidistat combined
and the inputs are provided on the field connection
terminal board. The unit control type configuration,
Configuration→UNIT→U.CTL, default value is for thermostat
(2) so there is no need to configure this item. The thermostat
control type configuration, Configuration→UNIT→T.CTL,
selects the unit response to the thermostat inputs above. The space
humidity switch configuration, Configuration→UNIT→RH.SW,
identifies the normally open or normally closed status of this input
at LOW humidity, and the input is the Humidistat 1 terminal (only
on Humidi-MiZer units).
Space Humidistat Control
For units with the factory Humidi-MiZer option, the
humidistat input is provided on the field connection
terminal board. The Space Humidity Switch configuration,
Configuration→UNIT→RH.SW, identifies the normally open or
normally closed status of this input at LOW humidity. Humidistat
2 terminal is the 24 VAC source for dry contact and the Humidistat
1 terminal is the signal input.
NOTE: On units with Humidi-MiZer, the Humidistat terminals
1 and 2 are the same as the Fire Shutdown terminals 1 and 2 on a
standard unit. See Fire Shutdown section.
Relative Humidity Sensor Control
For units with the factory installed Humidi-MiZer option and the
economizer option (with the ECB−economizer control board), the
humidity sensor input is provided on the field connection terminal
board (TB1/TB2). The sensor can be used in addition to or instead
of a humidistat or thermidistat. The RH Sensor on OAQ Input
configuration, Configuration→UNIT→RH.S=YES, identifies that
the sensor is being used instead of an OAQ sensor. Adjust RH
setpoints as needed. Terminal 1 is the 24vdc loop power and
Terminal 4 is the 4−20 mA signal input. Refer to the Field Installed
Accessories and Humidi-MiZer Operation sections for more
information.
CCN Communication
Configure Configuration→CCN→CCN.A to desired element
number. (Default is 1.) Configure Configuration"CCN" CCN.B
to desired bus number. (Default is 0.) Configure
Configuration→CCN→BAUD to desired code number for baud
rate (Default is 3 = 9600 baud).
Accessories
Below are quick configuration settings for field installed
accessories. If these accessories were installed by the factory, they
will already be configured. See the Field−Installed Accessories
section, third party control, control connection tables, and CCN or
Display parameter tables for any accessories not mentioned below
and any additional information on accessories.
Economizer
If an Economizer accessory was field installed, the unit must be
configured for it by setting Configuration"ECON"EC.EN to
YES. The default settings for the other economizer configurations
should be satisfactory. If they need to be changed, additional
information about these configuration settings can be found in the
Economizer section.
Power Exhaust
If a Power Exhaust accessory was field installed, the unit must be
configured for it by setting Configuration"ECON"PE.EN to
ENBL. The default settings for the other power exhaust
configurations should be satisfactory. If they need to be changed,
additional information about these configurations can be found in
the Power Exhaust section.
Electric Heat
If an Electric Heat accessory was field installed, the unit must be
configured for it by setting Configuration→HEAT→HT.TY to a
value of 2. The number of electric heat stages must be configured
by setting Configuration→HEAT→N.HTR per the installed
heater.
Fire Shutdown
If a Fire Shutdown or Smoke Detector accessory was field
installed, the unit must be configured for it by setting
Configuration→UNIT→FS.SW to normally open (1) or normally
closed (2) when there is not a fire alarm. Normally open (1) is the
preferred configuration.
48/50PG and PM
9
NOTE: On standard units, the fire shutdown input is the terminals
Fire Shutdown 1 and 2. On Humidi-MiZer units, the fire
shutdown connections are at PL19.
Outdoor Enthalpy
If an Outdoor Enthalpy accessory was field installed, the unit must
be configured for it by setting Configuration→ECON→EN.SW,
identifies the normally open or normally closed status of this input
when the outdoor enthalpy is low.
IAQ Switch
If an IAQ Switch accessory was field installed, the unit must be
configured for it by setting Configuration→AIR.Q→II.CF,
identifies the normally open or normally closed status of this input
when the indoor air quality value is low (good) and also selects the
unit response to this input.
NOTE: An IAQ switch cannot be used if an enthalpy switch is
already on this input.
IAQ Sensor
If an CO2 Sensor accessory was field installed, the unit must be
configured for it by setting Configuration→AIR.Q→IA.CF
selects the unit response to this input. Default conversion to 0 to
2000 ppm.
48/50PG and PM
OAQ Sensor
If an Outdoor Air Quality Sensor accessory was field installed, the
unit must be configured for it by setting Configuration→AIR.Q→OA.CF selects the unit response to this input. Default
conversion to 0 to 2000 ppm.
Fan Status
If a Fan Status accessory was field installed, the unit must be
configured for it by setting Configuration→UNIT→FN.SW to
normally open (1) or normally closed (2). Normally open (1) is the
preferred configuration.
NOTE: Fan Status input is not on the terminals marked Fan
Status.
Filter Status
If a Filter Status accessory was field installed, the unit must be
configured for it by setting Configuration→UNIT→FL.SW to
normally open (1) or normally closed (2). Normally open (1) is the
preferred configuration.
Programming Operating Schedules
The ComfortLink controls will accommodate up to eight
different schedules (Periods 1 through 8), and each schedule is
assigned to the desired days of the week. Each schedule includes
an occupied on and off time. As an example, to set an occupied
schedule for 8 AM to 5 PM for Monday through Friday, the user
would set days Monday through Friday to ON for Period 1. Then
the user would configure the Period 1 Occupied From point to
08:00 and the Period 1 Occupied To point to 17:00. To create a
different weekend schedule, the user would use Period 2 and set
days Saturday and Sunday to ON with the desired Occupied On
and Off times.
NOTE: By default, the time schedule periods are programmed for
24 hours of occupied operation.
To create a schedule, perform the following procedure:
1. Scroll to the Configuration mode, and select CCN
CONFIGURATION (CCN). Scroll down to the Schedule
Number (Configuration→CCN→SCH.O=SCH.N). If
password protection has been enabled, the user will be
prompted to enter the password before any new data is
accepted. SCH.N has a range of 0 to 99. The default value
is 1. A value of 0 is always occupied, and the unit will
control to its occupied set points. A value of 1 means the
unit will follow a local schedule, and a value of 65 to 99
means it will follow a CCN schedule. Schedules 2−64 are
not used as the control only supports one internal/local
schedule. If one of the 2−64 schedules is configured, then
the control will force the number back to 1. Make sure the
value is set to 1 to use a local schedule.
2. Enter the Time Clock mode. Scroll down to the LOCAL
TIME SCHEDULE (SCH.L) sub−mode, and press
ENTER. Period 1 (PER.1) will be displayed.
3. Scroll down to the MON.1 point. This point indicates if
schedule 1 applies to Monday. Use the ENTER command
to go into Edit mode, and use the Up or Down key to
change the display to YES or NO. Scroll down through the
rest of the days and apply schedule 1 where desired. The
schedule can also be applied to a holiday.
4. Configure the beginning of the occupied time period for
Period 1 (OCC). Press ENTER to go into Edit mode, and
the first two digits of the 00.00 will start flashing. Use the
Up or Down key to display the correct value for hours, in
24−hour (military) time. Press ENTER and hour value is
saved and the minutes digits will start flashing. Use the
same procedure to display and save the desired minutes
value.
5. Configure the unoccupied time for period 1 (UNC). Press
ENTER to go into Edit mode, and the first two digits of the
00.00 will start flashing. Use the Up or Down key to display
the correct value for hours, in 24−hour (military) time. Press
ENTER and hour value is saved and the minutes digits will
start flashing. Use the same procedure to display and save
the desired minutes value.
6. The first schedule is now complete. If a second schedule is
needed, such as for weekends or holidays, scroll down and
repeat the entire procedure for period 2 (PER.2). If
additional schedules are needed, repeat the process for as
many as are needed. Eight schedules are provided. See
Table 3 for an example of setting the schedule.
10
Table 3 – Setting an Occupied Time Schedule — Weekdays Only for 7:30 to 22:30
DISPLAY
MENU
TIMECLOCK
SCH.L
SUB‐SUB
MODE
PER.1
KEYPAD
ENTRY
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ESCAPE
ENTER
ENTER
ENTER
ENTER
ESCAPE
ENTER
ENTER
ESCAPE
ENTER
ENTER
ESCAPE
ENTER
ENTER
ESCAPE
ENTER
ENTER
ESCAPE
ENTER
ENTER
ESCAPE
ESCAPE
ESCAPE
ITEMDISPLAYITEM EXPANSIONCOMMENT
Local Occupancy Schedule
OCC.1Period Occupied Time
00.00
00.00
07.00
07.00
07.30
07.30
OCC.107.30Period Occupied Time
UNC.100.00Period Unoccupied Time
00.00
00.00
22.00
22.00
22.30
22.30
UNC.122.30Period Unoccupied Time
MON.1NOMonday In Period
NO
YES
YES
MON.1YESMonday In Period
TUE.1NOTuesday In Period
NO
YES
YES
TUE.1YESTuesday In Period
WED.1NOWednesday In Period
NO
YES
YES
WED.1YESWednesday In Period
THU.1NOThursday In Period
NO
YES
YES
THU.1YESThursday In Period
FRI.1NOFriday In Period
NO
YES
YES
FRI.1YESFriday In Period
Scrolling stops
Hours Flash
Select 7
Change accepted, minutes flash
Select 30
Change accepted
Item/Value/Units scrolls again
Scrolling stops
Hours Flash
Select 22
Change accepted, minutes flash
Select 30
Change accepted
Item/Value/Units scrolls again
Scrolling stops
Select YES
Change accepted
Item/Value/Units scrolls again
Scrolling stops
Select YES
Change accepted
Item/Value/Units scrolls again
Scrolling stops
Select YES
Change accepted
Item/Value/Units scrolls again
Scrolling stops
Select YES
Change accepted
Item/Value/Units scrolls again
Scrolling stops
Select YES
Change accepted
Item/Value/Units scrolls again
48/50PG and PM
11
The Service Test function can be used to verify proper operation of
compressors, heating stages, Humidi−MiZer System, indoor fan,
outdoor fans, power exhaust fans, economizer, crankcase heaters,
and the alarm relay. Use of Service Test is recommended at initial
system start up and during troubleshooting (See Table 4 for point
details).
Service Test mode has the following changes from normal
operation:
Outdoor air temperature limits for cooling circuits, economizer,
and heating are ignored. Normal compressor time guards and
other staging delays are reduced to 30 seconds or less.
Circuit alerts are limited to 1 strike (versus 3) before changing to
alarm shut down state.
The status of ALM.N is ignored so all alerts and alarms are
broadcast on CCN.
The words “SERVICE TEST” are inserted into every alarm
message.
Service test can only be turned ON/OFF at the unit display. Once
turned ON, other entries may be made with the display or through
CCN. To turn Service Test on, change the value of TEST to ON.
To turn service test off, change the value of TEST to OFF.
48/50PG and PM
NOTE: Service Test mode may be password protected. Refer to
Basic Control Usage section for more information. Depending on
the unit model, factory−installed options, and field−installed
accessories, some of the Service Test functions may not apply.
Independent Outputs
The independent (INDP) submenu is used to change output status
for the economizer, power exhaust stages, crankcase heaters, alarm
relay, and outside air unit.. These independent outputs can operate
simultaneously with other Service Test modes. All outputs return to
normal operation when Service Test is turned off. When the
economizer is using the factory default Digital Control Type
(Configuration→ECON→E.CTL is 1 or 2) then the Economizer
Calibration feature may be used to automatically check and reset
the economizer actuator range of motion. Refer to the economizer
operation section of more details. On EnergyX equipped units, use
the outside air unit (OAU) points to test the ERV components.
Fan Test
The fans (FANS) submenu is used to change output status for the
indoor fan and outdoor fan stages. Indoor fan speed test (F.SPD) is
only available for use when adaptive fan is configured
(Configuration→A.FAN→AF.EN) for Yes. F.SPD runs the fan at
the desired speed entered. Units with Humidi−MiZer systems have
limited or no manual outdoor fan control from test mode.
Cooling Test
The cooling (COOL) submenu is used to change output status for
the individual compressors. Compressor starts are staggered by 15
seconds. The fans (FANS) and heating (HEAT) service test outputs
are reset to OFF for the cooling service test. Indoor fans and
outdoor fans are controlled normally to maintain proper unit
operation. If adaptive fan is configured, then the indoor fan speed
will default to the Mech. Cooling Fan Speed configuration point
(Configuration→A.FAN→FS.CL) when one compressor is
turned on. The Reduced Cool Fan Speed (F.SPD) can only be
changed while one stage is running. If more then one stage is on
the actual fan speed will be 100%. F.SPD shows the reduced speed
not actual speed. On single stage units, actual fan speed will be
100% when the compressor is on. All normal cooling alarms and
alerts are functional.
When charging unit, all outdoor fans may be forced on in cooling
service test modes by setting the Outdoor Fan Override (OF.OV) to
on.
NOTE: Circuit A is always operated with Circuit B and/or C in
Humidi-MiZer system equipped units.
SERVICE TEST
Humidi−MiZert Test
For units with the factory Humidi-MiZer option, the
Humidi-MiZer (HZMR) submenu is used to change the output
status to operate the circuits in different Humidi−MiZer modes or
to separately test the Humidi−MiZer valve operations. Refer to the
Humidi-MiZer operation section for details on these modes and
valves. The fans (FANS), cooling (COOL), and heating (HEAT)
service test outputs are reset to OFF for the Humdi−MiZer service
test. Indoor and outdoor fans are controlled normally to maintain
proper unit operation. If adaptive fan is configured, then the indoor
fan speed will default to the Reheat2 Fan Speed configuration
point (Configuration→A.FAN→FS.RH) when Reheat2 test is
turned on. The Reheat2 fan speed (F.SPD) only reflects the speed
setting for testing Reheat2 circuits, and can only be changed when
a circuit is in Reheat2. Actual speed may be different if Reheat 1
tests are being performed. All normal cooling alarms and alerts are
functional. Refer to the Humidi−MiZer operating section for more
information.
NOTE: Circuit A is always operated with Circuit B and/or C in
Humidi-MiZer system equipped units.
Table 4 – Service Test Modes and Submodes Directory
DISPLAY MENU/
SUB-MENU/
NAME
SERVICE TEST
TESTField Service Test ModeOff/On
INDPTest Independent Outputs
ECONEconomizer Position Test0 to 100
E.CALCalibrate EconomizerOff/On
PE.1Power Exhaust 1 TestOff/On
PE.2Power Exhaust 2 TestOff/On
ALRMAlarm Relay TestOff/On
CCHCrankcase Heat TestOff/On
OA.DMOAU 2position DamperClose/Open
WHLOAU Wheel Test0 to 100
OA.OFOAU OA Fan Speed Test0 to100
OA.XFOAU PE Fan Speed Test0 to100
OA.HTOAU Tempring Heater Test0 to 100
FANSTest Fans
IDFIndoor Fan Power TestOff/On
F.SPDIndoor Fan Speed Test0 to 100
OFC.1Outdoor Fan 1 TestOff/On
OFC.2Outdoor Fan 2 TestOff/On
OFC.3Outdoor Fan 3 TestOff/On
COOLTest Cooling
CMP.ACool A TestOff/On
CMP.BCool B TestOff/On
CMP.CCool C TestOff/On
F.SPDReduced Cool Fan Speed60 to 100
OF.OVOutdoor Fan OverrideOff/On
HMZRTest Humidi-MiZer
RH1.AReheat1 A TestOff/On
RH1.BReheat1 B TestOff/On
RH1.CReheat1 C TestOff/On
RH2.AReheat2 A TestOff/On
RH2.BReheat2 B TestOff/On
RH2.CReheat2 C TestOff/On
F.SPDReheat2 Fan Speed65 to 100
CRCCool>Reheat1 Valve TestOff/On
RHV.AReheat2 Valve A TestOff/On
RHV.BReheat2 Valve B,C TestOff/On
HEATTest Heating
HT.1Heat Stage 1 TestOff/On
HT.2Heat Stage 2 TestOff/On
F.SPDReduced Heat Fan Speed65 to 100
EXPANDED NAMEVALUES
12
Heating Test
The heating (HEAT) submenu is used to change output status for
the individual heat stages, gas or electric. The fans (FANS) and
cooling (COOL) service test outputs are reset to OFF for the
heating service test. Indoor and outdoor fans are controlled
normally to maintain proper unit operation. If adaptive fan is
configured, then the indoor fan speed will default to the heating
configuration point (Configuration→A.FAN→FS.HT) when a
stage of heat is turned on. The Reduced Heat Fan Speed (F.SPD)
can only be changed while one stage is running. If more then one
stage is on the actual fan speed will be 100%. F.SPD shows the
reduced speed not actual speed. On single stage units actual fan
speed will be 100% when that stage is turned on. All normal
heating alarms and alerts are functional.
NOTE: Field terminal strip terminal R must be connected to W1
for the heat to operate in service test. Alert number T410 will occur
as a reminder if not done. If the normal unit control mode is
thermostat mode, then remove the R−W1 jumper after completing
service test.
THIRD PARTY CONTROL
Third party controls may interface with the unit ComfortLink
controls through the connections described below. See other
sections of these instructions for more information on the related
unit control and configurations.
Cooling/Heating Control
The thermostat inputs are provided on the field connection terminal
board. The Unit Control Type configuration,
Configuration→UNIT→U.CTL, must be 2 to recognize the
below inputs. Terminal R is the 24vac source for the following:
Y1 = First stage cooling
Y2 = Second stage cooling
W1 = First stage heating
W2 = Second stage heating
G = Indoor fan
Dehumidification Control
On Humidi−MiZer units terminals Humidistat 1 and 2 are
provided on the field connection terminal board. Humidity Switch
configuration, Configuration→UNIT→RH.SW, identifies the
normally open or normally closed status of this input at LOW
humidity. The Humidistat 1 terminal is the input signal and R can
be used as the source.
NOTE: Dehumidification is considered a cooling function in the
software and is only available on Humidi-MiZer equipped units.
Remote Occupancy
The remote occupancy input is provided on the field connection
terminal board (TB1). The Remote Occupancy Switch
configuration, Configuration→UNIT→RM.SW, identifies the
normally open or normally closed status of this input when
unoccupied.
5 = 24 VAC signal input
6 = 24 VAC source for dry contact
Fire Shutdown
The fire shutdown input is provided for unit shutdown in response
to a fire alarm or smoke detector. The Fire Shutdown Switch
configuration, Configuration→UNIT→FS.SW, identifies the
normally open or normally closed status of this input when there is
no fire alarm.
For 48/50 units without Humidi-MiZer system, input at field
connection terminal board (TB1)
Fire Shutdown 1 = 24 VAC sourcefor dry contact
Fire Shutdown 2 = 24 VAC signal input
For 50 series units with Humidi-MiZer system, input at wire
harness plug 19 (PL 19). (See Fig. 7.)
For 48 series units with Humidi-MiZer system, input at wire
harness plug 19 (PL 19). (See Fig. 8.)
PL 19-3 = 24 VAC sourcefor dry contact
PL 19-5 = 24 VAC signalfor Fire Shutdown
PL 19-4 = 24 VAC power for indoor fan contactor control
circuit
NOTE: If the indoor fan must be shut down without any delay
upon Fire Shutdown input, then the factory jumper between
PL19-3 and PL19-4 must be replaced with a normally closed
contact when there is no alarm (open with alarm).
The plug PL19 is located in the return air section on
48/50PG03−14 size units and under the control box on and
48/50PM16−28 units.
Alarm Output
The alarm output is provided on the field connection terminal
board (TB1) to indicate a current alarm status. The output will be
24VAC if a current alarm exists.
C = 24 VAC common
X = 24 VAC signal output
C08580
Fig. 7 − 50PG/PM Humidi−MiZert − Third Party Smoke
Detector Wiring
48/50PG and PM
13
FS.SW = 1 (NO)
Fig. 8 − 48PG/PM Humidi−MiZert − Third Party Smoke Detector Wiring
FS.SW = 2 (NC)
C09346
Economizer Monitoring
48/50PG and PM
On field terminal board (TB1), terminals 8, 9, and 10 can be used
to monitor economizer position from a third party control system.
See economizer operation section for additional information.
NOTE: Terminal 8 will not represent economizer position if the
unit is equipped with Adaptive Fan.
In digital mode (E.CTL = 1 or 2), the economizer commanded
position can be read as a 2−10v or 4−20mA signal. TB1−8 and
TB1−9 are used as follows:
To read a 2−10v signal, disconnect the violet wire on
TB1−J10−8 and place volt meter device across TB1−8 and
TB1−9.
To read a 4−20mA signal, disconnect the violet wire on
TB1−J10−8 and the 500Ω resister at TB1−J10−6. Place amp
meter device between TB1−8 and TB1−9.
In analog mode (E.CTL = 3), the economizer position can be read
as a 2−10v feedback signal across TB1−10 and TB1−9 at any time.
NOTE: The violet wire and 500Ω resister must be connected at
the J10 connector as originally wired to operate the economizer in
analog mode.
Economizer Damper Control
For units with the economizer option or accessory and the ECB
control board, the damper position can be directly controlled
through the IAQ sensor input provided on the field connection
terminal board. The IAQ Analog Input configuration,
Configuration→AIR.Q→IA.CF will have to set to 3 (Control
Minimum Position). When IA.CF = 3, an external 4 to 20 mA
source is used to move the damper 0% to 100% directly.
Terminal 2 = 4−20mA + signal
Terminal 3 = 4−20mA − common
NOTE: In this mode, preset minimum positions configurations are
not valid, the damper position may exceed the input position to
provide economizer cooling and CO
for DCV control. Refer to the Indoor Air Quality operation section
for more information.
sensor input can not be used
2
CONTROLS OPERATION
Display Configuration
The Configuration→DISP submenu is used to configure the local
display settings.
Metric Display (METR)
This variable is used to change the display from English units to
Metric units.
Language Selection (LANG)
This variable is used to change the language of the ComfortLink
display. At this time, only English is available.
Password Enable (PROT)
This variable enables or disables the use of a password. The
password is used to restrict use of the control to change
configurations.
Service Password (PSWD)
This variable is the 4-digit numeric password that is required if
enabled.
Test Display LEDs (TEST)
This is used to test the operation of the ComfortLink display.
Unit Configuration
Many configurations that indicate what factory options and/or field
accessories are installed and other common operation variables are
included in Unit Configuration (Configuration→UNIT). These
configurations will be set in the factory for the factory−installed
options (FIOPs). Field−installed accessories installed will require
configuration changes. General unit and fan control configurations
are also covered under this Unit Configuration menu.
Start−Up Delay (S.DLY)
This configuration sets the control start-up delay after the power is
interrupted. This can be used to stagger the start-up of multiple
units.
Unit Control Type (U.CTL)
This configuration defines if temperature control is based on
thermostat inputs or space temperature sensor input.
U.CTL = 2 (Thermostat) – The unit determines cooling and
heating demand by the state of G, Y1, Y2, W1, and W2 inputs
from a space thermostat. This value is the factory default.
U.CTL = 3 (Space Sensor) – The unit determines cooling and
heating demand based on the space temperature and the
appropriate set point. Used also as Linkage configuration. The
jumper wire in the installer’s packet must be connected between
R and W1 on the low voltage terminal board (TB) for heating
mode to operate.
14
Thermostat Control Type (T.CTL)
This configuration applies only if Unit Control Type is Thermostat
(Configuration→Unit→U.CTL = 2). The value determines
alternative cooling and Humidi-MiZer circuit staging. See the
Cooling and Humidi-MiZer sections for more information. The
factory default value is T.CTL = 0 (Adaptive).
Fan On When Occupied (OC.FN)
This configuration applies only if Unit Control Type is Space
Sensor (Configuration →Unit→U.CTL = 3). A YES value will
operate the indoor fan whenever the unit is in the Occupied mode.
A NO value will operate the indoor fan only when heating or
cooling is necessary. The factory default value is YES.
Shut Down on IDF Failure (IDF.F)
This configuration applies only if a fan switch is installed and
configured. A YES value will enable diagnostic Alert T409 to shut
down the unit when incorrect fan status is sensed. A NO value will
still permit Alert T409 but will not cause unit shutdown. The
factory default value is YES.
Fan Status Switch (FN.SW)
This configuration identifies if a fan status switch is installed, and
what status (normally open, normally closed) the input is when the
indoor fan is OFF.
Filter Status Switch (FL.SW)
This configuration identifies if a filter status switch is installed, and
what status (normally open, normally closed) the input is when the
filter is CLEAN.
Fire Shutdown Switch (FS.SW)
This configuration identifies if a fire shutdown switch is installed,
and what status (normally open, normally closed) the input is when
the fire or smoke alarm is OFF (no alarm).
Remote Occupancy Switch (RM.SW)
This configuration identifies if a remote occupancy switch is
installed, and what status (normally open, normally closed) the
input is when UNOCCUPIED.
SAT Settling Time (SAT.T)
This configuration sets the settling time of the supply air
temperature (SAT). This tells the control how long to wait after a
stage change before trusting the SAT reading. See Adaptive
Thermostat Control (U.CTL = 2, T.CTL = 0) and Space Sensor
Control (U.CTL = 3) within the Cooling operation section for
more information. The factory default value is 240 seconds.
RAT Sensor On SPTO Input (RAT.S)
This configuration identifies if a return air temperature (RAT)
sensor is installed on the space temperature offset (SPTO) input. A
YES value enables RAT display. A NO value disables RAT
display. Installing an RAT sensor will allow economizer differential
dry bulb control. Refer to the economizer operation for more
information.
RH Sensor On OAQ Input (RH.S)
This configuration identifies if a space relative humidity sensor is
installed on the outdoor air quality (OAQ) input. A YES value
enables SP.RH display. If a Humdi-MiZer unit, then the unit
determines dehumidification demand based on this input and the
appropriate set point. A NO value disables SP.RH display and use.
Space Humidity Switch (RH.SW)
This configuration identifies if a space relative humidity switch is
installed on the ENTHALPY input, and what status (normally
open, normally closed) the input is when the space humidity is
LOW.
Temperature Compensated Start Cooling Factor
(TCS.C)
This factor is used in the equation of the Temperature
Compensated Start Time Bias for cooling. A setting of 0 minutes
indicates Temperature Compensated Start in Cooling is not
permitted.
Temperature Compensated Start Heating Factor
(TCS.H)
This factor is used in the equation of the Temperature
Compensated Start Time Bias for heating. A setting of 0 minutes
indicates Temperature Compensated Start in Heating is not
permitted.
Modes
The ComfortLink controls operate under a hierarchy of
command structure as defined by four main elements: the System
Mode, the HVAC Mode, the Occupied status, and the Unit Control
Type.
The System Mode is the top level that defines three main states of
the control system: Disabled, Enabled, or Test.
The HVAC Mode is the next level that defines four main states of
functional operation: Disabled, Fan Only, Cool, and Heat.
The Occupied status affects set points for cooling and heating in
Space Sensor control mode and operation of the economizer for
indoor air quality ventilation and free cooling.
The Unit Control Type (Configuration→UNIT→U.CTL) defines
if temperature control is based on thermostat inputs or space
temperature sensor input.
The general operating mode of the control and the status of some
related operation lockouts are located on the display at two
locations: Run Status→ MODE and Operating Modes→ MODE.
System Mode (SYS)
In Run Status and Operating Modes, the current system mode is
displayed with expandable text. This is an overall state of the unit.
Three states are: Unit Operation Disabled, Unit Operation Enabled,
or Service Test Enabled.
HVAC Mode (HVAC)
In Run Status and Operating Modes, the current allowed HVAC
mode is displayed with expandable text. This is the mode the unit
decides to run in based on its inputs. There are four main HVAC
modes; cooling has six different expanded texts. These modes are
shown below.
HVAC
Mode
DisabledHVAC Operation
Fan OnlyVentilation (fan-
Cooling
HeatingHeatingHeating mode
Expanded TextBrief Description
Disabled
only)
CoolingMechanical cooling
Free CoolingOnly economizer used for cooling
Unoccupied Free
Cooling
Reheat1All running circuits in sub-cooling
Reheat2All running circuits in Hot Gas Reheat
Reheat1/Reheat2Sub-cooling and Hot Gas Reheat
Unit is in test mode or System mode
is disabled
Fan may run for ventilation
Only economizer use for cooling
(occupied cooling set point active)
mode
mode
active
48/50PG and PM
15
HVAC Operation Disabled (HV.DN)
Allow disabling of HVAC mode. This is only available on a
network connection and shows if the unit has been forced into the
disabled status.
Cool Setpoint In Effect (EFF.C)
This shows the actual setpoint that is being used for control during
cooling mode. If a 0 is displayed, then space sensor control is not
being used and the unit is being controlled by a thermostat.
Heat Setpoint In Effect (EFF.H)
This shows the actual setpoint that is being used for control during
heating mode. If a 0 is displayed, then space sensor control is not
being used and the unit is being controlled by a thermostat.
Currently Occupied (OCC)
Displays the current state of assumed space occupancy based on
unit configuration and inputs.
Timed Override in Effect (T.OVR)
Displays if the state of occupancy is currently occupied due to an
override.
Linkage Active (LINK)
Displays if a linkage communication “Linkage” is established
48/50PG and PM
between the unit and a linkage source.
Demand Limit in Effect (D.LMT)
Displays if a demand limit has been placed on the unit’s capacity.
Compressor OAT Lockout (C.LOC)
Displays if operation of one or more compressors is prevented due
to outdoor temperature limit lockout.
Heat OAT Lockout (H.LOC)
Displays if heating operation is prevented due to outdoor
temperature limit lockout.
Econo Cool OAT Lockout (E.LOC)
Displays if economizer operation for cooling is prevented due to
outdoor temperature limit lockout.
General Operation
48/50PG and 48/50PM units can provide cooling,
dehumidification, heating, and ventilation operation. Each unit
will operate under one of two basic types of control: thermostat or
space temperature sensor. There are many inputs, configurations,
safety factors, and conditions that ultimately control the unit. Refer
to the specific operation sections for detail on a specific unit
operation.
When thermostat control is enabled (Configuration→UNIT→U.CTL = 1), the unit will operate based on discrete input
commands (G, Y1, Y2, W1, and W2) and there is a one minute
time delay between modes and when re−entering a mode. The G
command calls for ventilation, the Y1 and Y2 commands call for
cooling, and the W1 and W2 commands call for heating.
Thermostat Control Type (Configuration→UNIT→T.CTL) affects
how cooling operates based on Y1 and Y2 commands and if
cooling/heating stage time guards are applied.
When space temperature sensor control is enabled (Configuration→UNIT→U.CTL = 2), the unit will try to maintain the Space
Temperature (Temperatures→AIR.T→SPT) between the effective
cool and heat setpoints (Run Status→MODE→EFF.C andEFF.H). However, to minimize unnecessary cool to heat and heat
to cool changes, there is a 10 minute delay after the last stage turns
off before the control will switch modes and a 1 minute delay when
re−entering the last mode. Linkage operation overrides the mode
changeover delay to 15 seconds. The cooling and heating Mode
Select Timeguard (Operating Modes→COOL→MS.TG and
Operating Modes→HEAT→MS.TG) show the remaining time
before allowing the respective mode to be entered.
Temperature Setpoint Determination
Setpoints are used to control the unit while under space
temperature sensor control. The Cool Setpoint in Effect (EFF.C)
and the Heat Setpoint in Effect (EFF.H) are the points in which the
unit is controlling to at a specific time. These points are read only
points and change according to occupancy, the offset slider status,
and network writes (Linkage or LON).
If the building is in occupied mode, the Occupied Cool Setpoint
(Setpoints→OCSP) and the Occupied Heat Setpoint (Setpoints→OHSP) are active. When the building is in unoccupied mode,
the Unoccupied Cool Setpoint (Setpoints→UCSP) and the
Unoccupied Heat Setpoint (Setpoints→UHSP) are active. The
heating and cooling set points are also separated by a Heat−Cool
Set Point Gap (Setpoints→GAP) that is user configurable from 2
to 10 degrees F. This parameter will not allow the setpoints to be
set too close together, it will change the last setpoint adjusted if it is
set within the GAP.
When the space sensor has a setpoint slider adjustment, the cool
and heat setpoints (occupied) can be offset by sliding the bar from
one side to the other. The SPT Offset Range (+/−) (Setpoints→STO.R) sets the total positive or negative degrees that can be
added to the setpoints. With the slider in the middle, no offset is
applied. Moving the slider to the “COOL” side will subtract from
each setpoint, and sliding it to the “WARM” side will add to the
setpoints. The slider offset being applied at any given time is
displayed as Space Temperature Offset (Temperatures→AIR.T→SPTO).
16
Occupancy Determination
The building’s occupancy is affected by a number of different
factors. When the unit is operating with a space temperature sensor
(T−55, T−56, T−58 or T−59), occupancy affects the unit set points
and the operation of the economizer. If the unit is operating under
thermostat control, occupancy only affects the operation of the
economizer. If the unit’s Humidi−MiZer is being controlled by a
relative humidity sensor, then occupancy will affect the RH
setpoints. The factors affecting occupancy are listed below from
highest to lowest priority.
Level 1 Priority
Level 1 classification is a force/write to occupancy and can occur three
ways. Listed in order of priority: force on OCCUPIED, a write to
NVI_OCC, and a Linkage write. The CCN point OCCUPIED is
forced via an external device such as a ComfortID controller or a
service tool. When OCCUPIED is forced to YES, the unit is
considered occupied, when OCCUPIED is forced to NO, the unit is
considered unoccupied. If the 3rd party protocol LON is writing to
NVI_OCC, the control maps it to OCCUPIED as an input. If the unit
is being controlled by Linkage, the occupancy is communicated and
mapped to OCCUPIED as an input. LON and Linkage do not force
the point, only write to it, therefore a force applied to OCCUPIED
will override them.
If OCCUPIED is not being forced or written to, proceed to the
level 2 priority.
Level 2 Priority
Remote Occupancy Switch should be configured to either
Normally Open or Normally Closed when the user would like to
control the occupancy with an external switch. This switch is
field−supplied (24v, single pole, single throw [SPST]). There are
three possible configurations for the remote occupancy switch:
1. (Configuration→UNIT→RM.SW = 0) No Switch
2. (Configuration→UNIT→RM.SW = 1) Normally Open
Switch
3. (Configuration→UNIT→RM.SW = 2) Normally Closed
Switch
If the switch is configured to No Switch (0), the switch input value
will be ignored and software will proceed to level 3 priority. For
each type of switch, the appropriate configuration and states are
listed in the table below. The Remote Occupancy Switch
(INPUTS→GEN.I→RM.OC) point will show the status of the
switch.
TYPE OF SWITCH
Occupied when Closed
or Unoccupied when
Open
Occupied when Open or
Unoccupied when
Closed
SWITCH
CONFIGURATION
Normal Open (1)
Normal Closed (2)
NOTE: To perform remote occupancy, an Economizer Control
Board must be installed in the unit.
Level 3 Priority
The following occupancy options are determined by the state of
Occupancy Schedule Number (Configuration→CCN→SCH.O
→SCH.N) and the Global Schedule Broadcast (Configuration
→CCN→ BROD→B.GS).
1. (Configuration→CCN→SCH.O→SCH.N = 0)
The unit is always considered occupied and the
programmed schedule is ignored. This is the factory
default.
2. (Configuration→CCN→SCH.O→SCH.N = 1−64)
Follow the local programmed schedule. Schedules 1 to 64
are local within the controller. The unit can only store one
STATE OF SWITCH
AND STATE OF
OCCUPANCY
Open and Unoccupied
Closed and Occupied
Open and Occupied
Closed and Unoccupied
local schedule and therefore changing this number only
changes the title of the schedule table.
3. (Configuration→CCN→SCH.O→SCH.N = 65−99)
Follow the global programmed schedule. If the unit is
configured as a Global Schedule Broadcaster
(Configuration→CCN→BROD→B.GS = YES), the unit
will follow the unit’s programmed schedule and broadcast
the schedule so that other devices programmed to follow
this schedule number can receive the schedule. If the unit is
not programmed as a Global Schedule Broadcaster
(Configuration→CCN→BROD→B.GS = NO), the unit
will receive broadcasted schedules from a unit programmed
to broadcast this schedule number. While using the
programmed schedule, occupancy can be temporarily
switched from unoccupied to occupied by pressing the
override button for approximately 3 seconds on the T−55,
T−56, T−58 or T−59 space temperature sensor. Override
will only occur if SPT Override Enabled (Configuration→CCN→SCH.O→OV.SP) is set to YES. The length of the
override period when pressing the override button is
determined by the Override Time Limit (Configuration→CCN→SCH.O→OV.TL). The hours remaining in
override is displayed as Timed Override Hours
(Configuration→CCN→SCH.O→OV.EX). This point can
also be changed from the local display or network to set or
change the override period length.
Indoor Fan Operation
The indoor fan is controlled by the Indoor Fan Relay (Outputs→FANS→IDF) on the MBB (main base board) control, which
then operates the indoor fan contactor (IFC). For gas heating units,
the IGC control fan output is also monitored by the MBB control.
This can result in additional modification of fan delays or other
operation due to safety functions of the IGC control. The
Humidi−MiZer gas heating units do not monitor the IGC fan
output; instead an indoor fan on relay (IFOR) is used to allow the
IGC to turn the fan on. If configured for IAQ fan operation, the
fan may be turned on to satisfy air quality demands. See the
Indoor Air Quality section if using IAQ (indoor air quality)
accessory sensors. The fan can only be turned on under thermostat
or space sensor control if the System Mode (SYS) status is enabled.
The fan will remain on if compressors or heat relays are ever stuck
on. If configured for fan status switch (FN.SW) and Shut Down
on IDF Failure (Configuration→UNIT→IDF.F = Yes) is enabled,
the fan and unit will be shutdown on alarm. See the Adaptive Fan
section for information on its operation.
Thermostat Control
In thermostat mode, the IDF relay will be on in the following
situations: fan request G in ON, cooling request Y1 or Y2 is ON,
or heating request W1 or W2 is ON. If G is dropped or never on
with an Y1, Y2, W1, or W2 call, the IDF relay will turn off after a
configurable time delay with respect to the HVAC mode that is
ending. The Fan−off Delay delays are as follows: Mech Cool
(Configuration→COOL→FOD.C), Elect Heat (Configuration
→HEAT→FOD.E), and Gas Heat (Configuration→HEAT
→FOD.G).
Space Sensor Control
In Space Sensor mode, the IDF relay will be on if the unit is in
Occupied mode and the indoor fan is configured to always run
while occupied (Configuration→UNIT→OC.FN = YES). If the
indoor fan is configured for intermittent fan (Configuration→UNIT→OC.FN = No), the fan will only be on when there are
cooling, heating, or dehumidification stages running; or if there is
an air quality demand. During the unoccupied period, the fan will
operate intermittent. With intermittent fan, the IDF relay will turn
off after a configurable time delay with respect to the HVAC mode
that is ending. The Fan−off Delay delays are as follows: Mech
Cool (Configuration→COOL →FOD.C), Elect Heat
(Configuration→HEAT→FOD.E), and Gas Heat
(Configuration→HEAT→FOD.G).
48/50PG and PM
17
Cooling Operation
The 48/50PG and 48/50PM unit’s cooling operation consists of:
demand, mode determination, staging request to satisfy the
demand, and handling a request with the unit’s resources. These
resources can include compressors, an economizer, and a reheat
coil. This section covers mechanical cooling. For economizer and
reheat cooling, refer to the Economizer and Humidi−mizer
sections, respectively. The unit enters a cooling mode based on a
demand, decides how to satisfy the demand, executes its plan, and
then leaves the cooling mode.
Cooling Mode Control
The cooling HVAC mode (Run Status→MODE→HVAC=3) has
six different expandable texts: Cooling, Free Cooling, Unoccupied
Free Cooling, Reheat1, Reheat2, or Reheat1/Reheat2. These are all
part of a general cooling mode and resemble the specific type of
cooling that is being performed at any given time. All types of
cooling are still performed under the general cooling function, and
the expanded text is for user reference only. The control will
display if it is ok to select the cooling mode (Operating Modes→COOL→OK.CL= Yes).
Thermostat Control
For the unit to enter cooling mode, three things must be true: the
48/50PG and PM
indoor fan must be ok to use, the mode changeover time guard
must be expired, and there must be a cooling demand (Y1, Y2, or
reheat demand). The unit will remain in cooling until the cooling
demand is dropped or if any of the above conditions turn false. If
only a reheat demand exists and a heat demand (W1, W2) occurs,
the unit will end cooling. The cooling mode can not officially end
until all compressors are off.
Space Sensor Control
For the unit to enter cooling mode, four things must be true: the
indoor fan must be ok to use, the mode changeover time guard
must be expired, the unit must have a valid space temperature, and
there must be a cooling or reheat demand. The unit will remain in
cooling for at least one minute and until the cooling demand drops
below −0.5F or if any of the above conditions turn false. If only a
reheat demand exists and the heat demand becomes greater than the
Reheat Heat Setpoint Deadband (Setpoints→RH.HB), the unit will
end cooling. The cooling mode can not officially end until all
compressors are off.
Staging Control
Once the unit is in a cooling mode, it must decide what the demand
is and how to satisfy it. If an economizer is installed and can be
used for cooling (Operating Modes→COOL→OK.EC= Yes), the
unit will use it first (see economizer section for its operation). If
the economizer can not be used or additional cooling is needed, a
mechanical cooling check is performed. OK to use Compressors?
(Operating Modes→COOL→OK.MC), will be set to yes when
compressors are enabled and not locked out. Based on the unit
control configuration, requested cooling stages (Run Status→COOL→REQ.C) will be determined then passed to compressor
control to actually add the cooling stages.
Thermostat Control
There are two ways of requesting stages when thermostat control is
enabled, Traditional Thermostat control or Adaptive control.
Traditional Thermostat control is used if the Thermostat Control
Type (T.CTL) is set to 1, 2, or 3 and the economizer is not
available for free cooling. If Thermostat Control (T.CTL) is set to
0 or any time the economizer is available for free cooling, the unit
will use Adaptive control for staging.
T.CTL = 0 (Adaptive Control)
Stage timers, Supply air trend, and supply air temperature limits
apply when determining the request for stages. The first request
(REQ.C=1) comes immediately when the Y1 input is active. The
Cool Stage Increase Time (Configuration→COOL→C.INC) or
the Cool Stage Decrease Time (Configuration→COOL→C.DEC)
has to expire before another stage can be added or a stage can be
subtracted. The Supply−Air Trend (OperatingModes→COOL→SA.TR) decides if the next stage can be
requested or should be subtracted based on the Y2 input status.
For 48/50PG16 units, the supply air trend will allow up to 2
requested stages for just the Y1 input and allow up to 3 requested
stages for an Y1 and Y2 input. If the Y1 and Y2 inputs are
dropped, the supply air trend is not considered because cooling is
no longer needed. If at any time the Supply−Air Temperature
(SAT) falls below the Minimum Supply Air Temperature Upper
Level (Configuration→COOL→SAT→SAT.U), the requested
stages will not be allowed to increase. If at any time the SAT falls
below the Minimum Supply Air Temperature Lower Level
(Configuration→COOL→SAT→SAT.L), the requested stages will
be reduced by one without honoring C.DEC. If SAT.L and SAT.U
are configured so that they are close together, the last stage of
compressor might cycle rapidly, slowed only by its minimum on
and off−time requirements.
T.CTL = 1 (1 Stage Y1)
Stage timers, Supply air trend, and supply air temperature limits do
not apply when determining the request for stages. Request staging
will follow the thermostat inputs directly. Y1 will request one
stage. Y2 will request all stages.
T.CTL = 2 (2 Stage Y1)
Stage timers, Supply air trend, and supply air temperature limits do
not apply when determining the request for stages. Request staging
will follow the thermostat inputs directly. Y1 will request two
stages on 48/50PG16 units and one stage for all other units. Y2
will request all stages.
T.CTL = 3 (Digital)
Stage timers, Supply air trend, and supply air temperature limits do
not apply when determining the request for stages. Request staging
will follow the thermostat inputs directly. Y1 will request one
stage. Y2 will request two stages. Y1 and Y2 will request three
stages on 48/50PG16 units and two stages for all other nits.
18
Space Sensor Control
Space sensor staging control is an adaptive anticipation control that
weighs the actual space demand against the trend of that demand
and the trend of the supply air. It also honors stage time guards
and supply air limits. The demand for cooling in the space is
displayed as the Cooling Demand (Run Status→COOL→DMD.C). The control tries to anticipate the change in the space
because of its current stage status. This anticipation is based on the
Supply−Air Trend (Operating Modes→COOL→SA.TR) and the
Cool Demand Trend (Operating Modes→COOL→TRD.C).
These trends will show the control how the space is reacting to the
current running conditions and help it decide when to add or
remove one stage from the requested stages. The Cool Stage
Increase Time (Configuration→COOL→C.INC) or the Cool
Stage Decrease Time (Configuration→COOL→C.DEC) has to
expire before another stage can be added or a stage can be
subtracted. If at any time the Supply−Air Temperature (SAT) falls
below the Minimum Supply Air Temperature Upper Level
(Configuration→COOL→SAT→SAT.U), the requested stages
will not be allowed to increase. If at any time the SAT falls below
the Minimum Supply Air Temperature Lower Level
(Configuration→COOL→SAT→SAT.L), the requested stages will
be reduced by one without honoring C.DEC. If SAT.L and SAT.U
are configured so that they are close together, the last stage of
compressor might cycle rapidly, slowed only by its minimum on
and off−time requirements.
Compressor Control
The compressor control works hand and hand with the staging
control. As the staging control requests stages, the compressor
control determines what actual compressors are available or
running and tries to provide stages for what is requested. The
availability of a compressor depends on time guards, circuit
diagnostics, outdoor temperature, and the unit size.
The Number of Circuits (Configuration→COOL→N.CIR)
configuration tells the control how many compressors are installed
on the unit. The Circuit A Lockout Temp
(Configuration→COOL→CIR.A →CA.LO), Circuit B Lockout
Temp (Configuration→COOL →CIR.B→CB.LO), and Circuit C
Lockout Temp (Configuration →COOL→CIR.C→CC.LO)
configurations set the outdoor temperature in which the respective
compressor is allowed to run down to. Timeguard A (Run
Status→COOL→CIR.A→TG.A), Timeguard B (Run
Status→COOL→CIR.B→TG.B), and Timeguard C (Run
Status→COOL→CIR.C→TG.C) display the time a respective
compressor has before it is available for use. Individual circuit
diagnostic tests are performed during operation which may or may
not allow a compressor to be used. The configuration point
Compressors On Circuit A (Configuration →COOL→N.A)
informs the control to run diagnostics on one or two compressors
for circuit A. The available stages at any given time are displayed
as Available Compressors (Run Status→COOL →AVL.C). The
actual compressors running at any given time are displayed as
Actual Cooling Stages (Operating Modes→COOL →ACT.C).
Compressor A (Run Status→COOL→CIR.A →CMP.A),
Compressor B (Run Status→COOL→CIR.B →CMP.B), and
Compressor C (Run Status→COOL→CIR.C →CMP.C) are
displayed on when the respective compressor is running.
There are time guards to protect the compressors. Compressor Min
On Time (Configuration→COOL→MRT.C) and Compressor Min
Off Time (Configuration→COOL→MOT.C) apply before a
compressor can be turned back on or turned off.
Outdoor Fan Control
Each unit has a means for variable outdoor airflow to control
condenser pressure control within an acceptable range by
responding to varied operating modes and ambient temperatures.
This is implemented differently on different units using
multi−speed motors, multiple outdoor fans, or variable−speed
motor controllers.
NOTE: Factory default configurations account for these model
differences and should not be changed. The default configurations
have been qualified over a large range of conditions and are
provided in case a field replacement of a control board occurs and
the settings need to be checked or manually configured. Outdoor
fan operation is further described below to assist in
troubleshooting.
The outdoor fans are controlled by levels. There are 4 levels of
operation (0−3) and the current operating level is shown as
Outdoor Fan Level (Operating Modes→COOL→F.LEV). The
fan level selected during operation is based on factory
configurations of outdoor temperature limits and condenser
pressure limits. These are in the Outdoor Fan Control submenu
(Configuration→COOL→OFC) and shown in Table 5. The
starting level is picked after a compressor is turned on and is based
on the Outdoor Air Temperature (Temperatures→AIR.T→OAT).
A circuit’s Saturated Condensing Temperature (Temperatures→REF.T→SCT.x) can override the fan level at any time if the
specific Fan Level Max Pressure (Configuration→COOL→OFC→x.MXP) is exceeded. This override will end if the circuit’s
saturated condensing temperature (SCT) drops below the specific
Fan Level Min Pressure (Configuration→COOL→OFC→x.MNP). The number of fans and contactors on at a given fan
level depends on the specific unit options and size. See Tables 6
and 7 and below text for specific fan and contactor status at any
given fan level.
Units Without Humidi−MiZert System
Outdoor Fan Motors (OFM) are controlled by Outdoor Fan
Contactors (OFC) which are controlled by the main base board
(MBB).
For 48/50PG03−07 units, a duel speed motor is used. The
Compressor Contactor (C.A1) turns the OFM on in high speed and
the OFC1 is used to change to low speed.
For 48/50PG08−14 units, OFM1 is controlled by OFC1 and
OFM2 is controlled by OFC2.
For 48/50PG16 units, OFM1 is controlled by OFC1 and OFM1
and 2 are controlled by OFC2.
For 48/50PG20−28 and 48/50PM16−28 units, OFM1 is controlled
by OFC1, OFM4 is controlled by OFC3, and OFC2 controls the
remaining two fans (16 and 20 size) or remaining 4 fans (24 and 28
sizes).
Units With Humidi−MiZer System
Outdoor fan control for Humidi−MiZer units includes a
Motormaster variable−speed control of some or all outdoor fans,
depending on unit size. The Motormaster control automatically
adjusts the outdoor fan speed to maintain approximately 80 to
100F condenser temperature for circuit A at all outdoor ambient
temperatures. Some unit sizes have additional on/off staging of
some outdoor fans. The fan level operation is determined by some
or all Outdoor Fan Control configurations described above, plus
additional Humidi−MiZer Configuration (Configuration→HZMR). Refer to the Humidi−MiZer operation section for
details on the Reheat function fan control.
48/50PG and PM
19
For 48/50PG03−07 units, one outdoor fan is controlled in all
modes by the Motormaster sensing on circuit A.
For 48/50PG08−14 units, 2 outdoor fans are controlled in all
modes by the Motormaster sensing on circuit A.
For 48/50PG16 units, 3 outdoor fans are controlled in normal
cooling and sub−cooling Reheat1 modes by the Motormaster
sensing circuit A. Two of the fans are additionally controlled with
OFC.1 output, based on outdoor temperature, during the hot−gas
Reheat2 mode (level 1 = 1 fan, level 2 = 3 fans).
Table 5 – Outdoor Fan Level Transitions
For 48/50PG20−28 and 48/50PM16−28 units, contactor OFC1
controls power to the Motormaster which controls OFM1 and
OFM4. Contactor OFC2 controls the remaining two fans (16 and
20 size) or remaining 4 fans (24 and 28 sizes).
FAN LEVEL
NOTE: Where not specified, the models are both PG and PM. Levels 0 and 1 are only in play if the OAT is lower than the Level 2 On temperature and the
pressure is not above its respected max.
48/50PG and PM
FAN LEVEL
0OFFOFFOFFOFFOFFOFF
1
2
3N/AN/AN/AN/AN/AN/A
FAN LEVEL
0---
1
2
3
OUTDOOR TEMPERATURE (F)
Without Humidi-MiZer™ SystemWith Humidi-MiZer System
Table 6 – 48/50PG03−16 Fan Level Control of Fans and Contactors
48/50PG03-0748/50PG08-1448/50PG16
Standard UnitHumidi-MiZer UnitStandard UnitHumidi-MiZer UnitStandard UnitHumidi-Mizer Unit
OFC1 On
Low Speed
OFC1 Off
High Speed
Motormaster
Fan 1
N/A
OFC1 On,
OFC2 Off
Fan 1 On
OFC1 On,
OFC2 On
Fan 1 and 2 On
Motormaster
Fan 1 and Fan 2
N/A
OFC1 On,
OFC2 Off
Fan 1 On
OFC1 On,
OFC2 On
Fan 1, 2, 3 On
Motormaster, OFC1
Off
Fan 2
Motormaster, OFC1
On
Fan 1, 2, 3
Table 7 – 48/50PG20−28 and PM16−28 Fan Level Control of Outdoor Fan contactors (OFC(X))
With Humidi-MiZer SystemWith Humidi-MiZer System
Circuit ACircuit BCircuit A and B
1
1, 3 (PG28)
1,2 (20, PM16)
2 (24-28)
1,2
1, 2, 3 (PG28)
31
2, 3 (20, PM16)
2 (24-28)
2, 31, 2
1, 2 (20, PM16)
2 (24-28)
20
Heating Operation
The 48/50PG and 48/50PM unit’s heating operation consists of:
demand, mode determination, staging request to satisfy the
demand, and handling a request with the unit’s resources. These
resources can be gas heat or electric heat. This section covers both
gas heat units and electric heat units. The Type of Heat Installed
(Configuration→HEAT→HT.TY) configuration will be factory
set to 1 for gas units, 2 for electric heat units with heaters installed,
and 0 for electric heat units without heat installed. The unit enters
a heating mode based on a demand, decides how to satisfy the
demand, executes its plan, and then leaves the heating mode.
Heating Mode Control
The heating HVAC mode (Run Status→MODE→HVAC=4),
represents both types of heating (gas or electric) under all types of
control. For the unit to be allowed to enter the heat mode, heat
must be enabled (HT.TY = 1 or 2), and the Outdoor Air
Temperature (Temperatures→AIR.T→OAT) must be less than the
Heating Lockout Temp (Configuration→HEAT→HT.LO). Heat
OAT Lockout (Run Status→MODE→H.LOC) displays when
heat is locked out on outdoor temperature and therefore can not
allow heat mode. The control will display if it is ok to select the
heating mode (Operating Modes→HEAT →OK.HT= Yes).
Thermostat Control
For the unit to enter heating mode, three additional things must be
true: the indoor fan must be ok to use, the mode changeover time
guard must be expired, and there must be a heating demand (W1,
W2). The unit will remain in heating until the heating demand is
dropped or if any of the above conditions turn false. The heating
mode can not officially end until all heat stages are off and the IGC
fan request is dropped (on gas units without Humidi−MiZer).
Space Sensor Control
For the unit to enter heating mode, five additional things must be
true: the indoor fan must be ok to use, the mode changeover time
guard must be expired, the unit must have a valid space
temperature, the W1 jumper must be installed, and there must be a
heating demand. The unit will remain in heating for at least one
minute and until the heat demand drops below −0.5F or if any of
the above conditions turn false. The heating mode can not
officially end until all heat stages are off and the IGC fan request is
dropped (on gas units without Humidi−MiZer).
Supply−Air Temperature Sensor (SAT)
The SAT Heat Mode Sensing (Configuration→HEAT→SAT→SAT.H) informs the unit if the supply air sensor
has been relocated downstream of the heat section. This
configuration affects the Supply Air Temperature (Temperatures→AIR.T→SAT) value displayed as listed below.
When SAT.H = DSBL, the Supply Air Temperature (Temperatures→AIR.T→SAT) value on the Scrolling Marquee and the CCN
tables will be forced to zero when heat outputs turn ON or OFF
and for 5 minutes after. The default Supply Air Temperature
location is at the fan inlet, upstream of the heat section.
When SAT.H = ENBL, the Supply Air Temperature (Temperatures→AIR.T→SAT) sensor reading is displayed at the Scrolling
Marquee and the CCN tables during heating mode. This setting
should only be used if the original SAT sensor wires are removed
from the Main Base Board (MBB) and replaced by an accessory
SAT sensor located in the supply duct downstream of the
heat section.
There are two supply air temperature limits that affect heating
operation, the Maximum SAT Lower Level (Configuration→HEAT→SAT→SAM.L) the Maximum SAT Upper Level
(Configuration→HEAT→SAT→SAM.U). Any time the supply
air temperature rises above SAM.L the heat staging will be limited
to what is currently on and no additional stages can be added until
the supply air temperature falls back below SAM.L. If the supply
air temperature rises above SAM.U, then heating will be reduced
by removing a heat stage. That stage can not be added again until
the Supply Air Temperature falls below SAM.L. If the supply air
temperature stays above SAM.U, then another stage will be
removed after the Heat Stage Decrease Time (Configuration→HEAT→H.DEC). If SAM.L and SAM.U are configured so that
they are close together, the last stage of heat might cycle rapidly,
slowed only by its minimum on and off−time requirements.
Staging Control
Once the unit is in a heating mode, it must decide what the demand
is and how to satisfy. Based on the unit control configuration,
requested heating stages (Run Status→HEAT→REQ.H) will be
determined then passed to heat control to actually add the heating
stages.
Thermostat Control
There are two ways of requesting stages when thermostat control is
enabled: Traditional Thermostat control or Adaptive control.
Traditional Thermostat control is used if the Thermostat Control
Type (T.CTL) is set to 1, 2, or 3. Adaptive control is used if
Thermostat Control (T.CTL) is set for 0.
T.CTL = 0 (Adaptive Control)
Stage timers and supply air temperature limits apply when
determining the request for stages. The first request (REQ.C=1)
comes immediately when the W1 input is active. The Heat Stage
Increase Time (Configuration→HEAT→H.INC) or the Heat
Stage Decrease Time (Configuration→HEAT→H.DEC) has to
expire before another stage can be added or a stage can be
subtracted. If at any time the Supply−Air Temperature (SAT) rises
above the Maximum Supply Air Temperature Lower Level
(Configuration→HEAT→SAT→SAM.L), the requested stages
will not be allowed to increase. If at any time the SAT rises above
the Maximum Supply Air Temperature Upper Level
(Configuration→HEAT→SAT→SAM.U), the requested stages
will be reduced by one without honoring H.DEC.
T.CTL = 1, 2 or 3 (Traditional thermostat control)
Stage timers and supply air temperature limits do not apply when
determining the request for stages. Request staging will follow the
thermostat inputs directly. W1 will request one stage. W2 will
request all stages.
48/50PG and PM
21
Space Sensor Control
Space sensor staging control is an adaptive anticipation control that
weighs the actual space demand against the trend of that demand.
It also honors stage time guards and supply air limits. The demand
for heating in the space is displayed as the Heating Demand (RunStatus→HEAT→DMD.H). The control tries to anticipate the
change in the space because of its current stage status. This
anticipation is based on the Heat Demand Trend (Operating Modes→HEAT→TRD.H). This trend will show the control how the
space is reacting to the current running conditions and help it
decide when to add or remove one stage from the requested stages.
The Heat Stage Increase Time (Configuration→HEAT→H.INC)
or the Heat Stage Decrease Time (Configuration→HEAT→H.DEC) has to expire before another stage can be added or a
stage can be subtracted. If at any time the Supply−Air Temperature
(SAT) rises above the Maximum Supply Air Temperature Lower
Level (Configuration→HEAT→SAT→SAM.L), the requested
stages will not be allowed to increase. If at any time the SAT rises
above the Maximum Supply Air Temperature Upper Level
(Configuration→HEAT→SAT→SAM.U), the requested stages
will be reduced by one without honoring H.DEC.
Heat Relay Control
48/50PG and PM
The heat relay control is responsible for energizing or
de−energizing the MBB’s heat stage relays and works hand in hand
with the staging control. As the staging control requests stages, the
heat relay control determines what actual heat relays are available
or energized and tries to provide stages for what is requested. The
availability of a heat relays depends on heat being installed, how
many stages, and time guards. The type of Heat Installed
(Configuration→HEAT→HT.TY) must be set for gas or electric
for any stages to be available. The Number of Heat Stages
(Configuration→HEAT→N.HTR) configuration tells the control
how many heat relays can be used. Heat Stage 1Timeguard (Run
Status→HEAT→TG.H1) and Heat Stage 2 Timeguard (Run
Status→HEAT→TG.H2) display the time a respective heat relay
has before it is available for use. The available stages at any given
time are displayed as Available Heating Stages (Run Status→HEAT→AVL.H). The actual heat relays on at any given time
are displayed as Actual Heating Stages (Operating Modes→HEAT→ACT.H). Heat Stage 1 Relay (Run Status→HEAT→HT.1) and
Heat Stage 2 Relay (Run Status→HEAT→HT.2) are displayed on
when the respective relay is energized. There are time guards to
protect from short cycling, Heat Minimum On Time
(Configuration→HEAT→MRT.H) and Heat Minimum Off Time
(Configuration→HEAT→MOT.H) apply before a heat relay can
be turned back on or turned off.
Integrated Gas Controller (IGC)
The heat staging is determined as described above and the
Integrated Gas Controller (IGC) initiates the gas heat module
start−up. The Integrated Gas Controller (IGC) minimum on−time
of 1 minute will be followed even if Heat Minimum On Time
(Configuration→HEAT→MRT.H) is lower and during Service
Test. If the IGC temperature limit switch opens within 10 minutes
of the end of the gas heat cycle, the next fan off delay will be
extended by 15 seconds. The maximum delay is 3 minutes. Once
modified by the IGC, the fan off delay will not change back to the
configured Fan−off Delay, Gas Heat (Configuration→HEAT→FOD.G) unless power is reset to the control. A light emitting
diode (LED) is provided on the IGC to indicate status. During
normal operation the LED is continuously on. See the
Troubleshooting section if the LED is off or flashing. The IGC is
located behind the gas section access panel door.
When the control energizes Heat Stage 1 Relay (Run Status→HEAT→HT.1), power is sent to the W terminal on the IGC
board. A check is made to ensure that the rollout switch and limit
switch are closed. The induced−draft motor is then energized, and
when speed is proven with the Hall Effect sensor on the motor, the
ignition activation period begins. The burners will ignite within 5
seconds. If the burners do not light, there is a 22−second delay
before another 5−second attempt. If the burners still do not light,
this sequence is repeated for 15 minutes. After the 15 minutes have
elapsed, if the burners still have not lit, heating is locked out. The
control will reset when the request for heat is temporarily removed.
When ignition occurs, the IGC board will continue to monitor the
condition of the rollout switch, limit switches, the Hall Effect
sensor, as well as the flame sensor. If the unit is controlled through
a room thermostat or space sensor set for fan auto, 45 seconds after
ignition occurs the indoor−fan motor will be energized (and the
outdoor−air dampers will open to their minimum position). If for
some reason the over temperature limit opens prior to the start of
the indoor fan blower, on the next attempt, the 45−second delay
will be shortened to 5 seconds less than the time from initiation of
heat to when the limit tripped. Gas will not be interrupted to the
burners and heating will continue. Once modified, the fan on delay
will not change back to 45 seconds unless power is reset to the
control. When the control energizes Heat Stage 2 Relay (RunStatus→HEAT→HT.2), power is supplied to the second stage of
the main gas valve. If both stage 1 and stage 2 of the gas valve
close, gas will be turned off to the main burners.
22
Economizer
If an economizer is installed, then Economizer Installed configuration
(Configuration→UNIT→EC.EN) should be set to YES. The
economizer is controlled by the economizer output signal
(Outputs→ECON→EC.CP) on the ECB control. If the indoor fan is
off or the building is unoccupied, the economizer position is zero. If in
Occupied mode and the unit is heating or cooling and the economizer
cannot provide free cooling, the economizer position is the configured
economizer minimum position (Configuration→ECON→EC.MN)
or the position specified by the IAQ algorithm. If in Unoccupied
mode, the position is 0% open.
The economizer will be allowed to help with cooling if the outdoor-air
temperature (Te mp er at ur e→AIR.T→OAT) is less than the configured
economizer high temperature lockout (Setpoints→EH.LO) and
greater than the configured economizer low temperature lockout
(Setpoints→EL.LO). If an enthalpy sensor is installed, the outdoor
temperature must be below the economizer high temperature lockout
and the enthalpy (Inputs→GEN.I→ENTH) must be LOW. If a return
air temperature (RAT) sensor is installed and Diff Dry Bulb Control
(Configurations→ ECON → DF.DB = Enable) is enabled, the
outdoor air temperature must be lower than the return air temperature
in addition to the the lockouts and enthaply. For
cooling, the economizer position can vary between the configured
economizer minimum position (Configuration→ECON→EC.MN)
and the economizer maximum cooling position
(Configuration→ECON→EC.MX).
Thermostat Control
If the unit is in cooling, operating under thermostat control, Y1 = ON,
and the economizer is available for cooling, the economizer will
control the supply-air temperature to the low cool set point
(Setpoints→LCSP). When Y2 = ON, the economizer will control the
supply-air temperature to high cool set point (Setpoints→HCSP).
Space Sensor Control
If the unit is in cooling, operating under space temperature control,
the economizer is available for cooling, and no compressors are
operating, the economizer will control the SAT to either
Setpoints→LCSP or Setpoints→HCSP (See Table 8.) If a
compressor is ON, the economizer will try to position
itself at the economizer maximum cooling position
(Configuration→ECON→EC.MX).
If the control senses low suction pressure for any active refrigerant
circuit when the economizer is also providing cooling, the
maximum allowable economizer position will be reduced. Factory
default configurations have been qualified over a large range of
conditions and should only be changed with care. For unit
troubleshooting, factory default maximum economizer limits for
this condition are provided in Table 9.
Table 8 – LCSP and HCSP Transitions for
Space Temperature Mode
CURRENT SAT
SET POINT
LCSP
HCSP
LCSP
LEGEND
HCSP - High Cool Set Point
LCSP - Low Cool Set Point
SAT - Supply-Air Temperature
Table 9 – Maximum Economizer Limits
COOLING
STAGE
Bottom
Middle
To p
SIZES
03‐07
COOL DEMAND
(∆F)
>0.5HCSP
<0LCSP
<–0.5Exit Cooling
NEXT SAT
SET POINT
During Low Suction Pressure
SIZES
08‐14
50505050
——3550
—25250
SIZE 16
20-28
SIZES
Economizer Actuator Communications
The actuator used with 48/50PG and PM units is a Multi−Function
Technology (MFT) actuator. This allows the ComfortLink
system to communicate with the actuator through a feedback
signal. The configuration Economizer Control Type determines the
communication method, either digital or analog, used to
communicate between the ECB and the economizer actuator.
Economizer Control Type is accessible via the Scrolling Marquee
at Configurations→ECON→E.CTL. The power to the unit
must be cycled after E.CTL is changed.
NOTE: If unit is equipped with Adaptive Fan, the control
automatically defaults the economizer control type to 1 (E.CTL =
1) and controls the actuator digitally. This is because the analog
signal from the ECB is used to drive the VFD’s speed and therefore
can not be used to control the actuator. The field connection
terminal block TB−8 no longer represents the commanded or
actual position of the actuator.
E.CTL = 1 or 2 (Digital/Position or Digital/Command)
When E.CTL is set to 1, the ECB will communicate with the
economizer actuator using the digital protocol, from ECB J7−1 to
actuator pin 5. The commanded position and the actuators actual
position are communicated back and forth between actuator and
ECB. When the ECB and actuator first initiate communication, a
control angle (Operating Modes→ECON→C.ANG) is provided to
the ECB and represents the actuator’s range of motion. This control
angle must be greater then the minimum angle
(Configurations→ECON→M.ANG).
During this digital control, the ECB’s analog 4 to 20mA output
will represent the actuator’s actual position when E.CTL = 1 or
commanded position when E.CTL = 2. Because the wiring has a
built−in 500−ohm resistor, the 4 to 20mA signal is converted to a 2
to 10−v signal that is accessible via field connection terminal board
TB−8 and TB−9. However, before this signal can be read remotely,
the violet wire that connects the actuator to field connection
terminal board TB−J10−8 must be removed or cut.
E.CTL = 3 (Analog Control)
When E.CTL is set to 3, the ECB will NOT communicate with the
economizer actuator using the digital MFT. It will instead control
the actuator directly with the 4 to 20 mA analog signal wired to
TB−8 and TB−9 along with the 500−ohm resistor producing a 2 to
10−v signal for the actuator. While in this mode, the actuator’s
built−in 2 to 10−v feedback signal is accessible via TB−9 and
TB−10 any time because it is not used by the ECB.
Unoccupied Free Cooling
The unoccupied free cooling algorithm attempts to maintain the
building space temperature half way between the occupied cool
and occupied heat setpoints using only the economizer when the
conditions in the building and the outdoors are suitable. Three
different configurations define this algorithm: Unoccupied Free
Cooling (Configuration→ECON→UEFC), Free Cooling
Preoccupancy Time (Configuration→ECON→FC.TM) and Free
Cool Low Temp Limit (Configuration→ECON→FC.LO).
UEFC = 0 (Disabled)
When UEFC = 0, unoccupied free cooling is disabled. Cooling
will only occur if the space exceeds the unoccupied setpoints.
UEFC = 1 (Unoccupied)
When UEFC is set to 1, unoccupied free cooling can occur
throughout the entire unoccupied period. The space temperature
must be higher then the mid−point between the occupied cooling
and heating setpoints.
UEFC = 2 (Preoccupancy)
When UEFC is set to 2, unoccupied free cooling can only occur
when the time until the next occupied period is less than the Free
Cool PreOcc Time (FC.TM) in minutes.
48/50PG and PM
23
Free Cool PreOcc Time (FC.TM)
FC.TM is the configuration that determines how many minutes
before occupancy that free cooling can occur when set for
Preoccupancy (UEFC = 2).
Free Cool Low Temp Limit (FC.LO)
Unoccupied free cooling cannot occur if the Outdoor Air
Temperature (Temperature→ AIR.T→ OAT) is less than FC.LO.
Power Exhaust
To enable power exhaust, Configuration→ECON→PE.EN must
be set to ENBL. If power exhaust is enabled, Power Exhaust 1 will
turn on when the economizer position is greater than the value of
Configuration→ECON→PE.1. If power exhaust is enabled,
Power Exhaust 2 will turn on when the economizer position is
greater than the value of Configuration→ECON→PE.2. There are
small time delays to ensure that rapid cycling does not occur.
Optional Humidi−MiZert Dehumidification
System
Units with the factory−equipped Humidi−MiZer option are capable
of providing multiple modes of improved dehumidification as a
variation of the normal cooling cycle. The Humidi−MiZer option
includes additional valves in the liquid line and discharge line of
48/50PG and PM
each refrigerant circuit, a small reheat condenser coil downstream
of the evaporator, and Motormaster variable−speed control of
some or all outdoor fans. The Humidi−MiZer Equipped
(Configuration→HMZR→REHT) configuration is factory set to
Yes for Humidi−MiZer equipped units. This enables
Humidi−MiZer operating modes and service test.
NOTE: If the unit is a Humidi−MiZer unit, this configuration
must always be set to yes. The Humidi−MiZer option does affect
the base unit wiring.
Humidi−MiZer operation requires installation and configuration of
either a space relative humidity sensor or a relative humidity switch
input. Space Humidity Switch (Configuration→UNIT→RH.SW)
set to 1 for use of a normally open switch or 2 for normally closed
switch. The switch is wired to field connection terminal board
terminals labeled HUMDISTAT. Set RH Sensor on OAQ Input
(Configuration→UNIT→RH.S) to Yes for use of a 4 to 20 mA
output RH sensor wired to field connection terminal board (TB)
terminals 1 and 4 (for loop powered). RH Sensor Value at 4ma
(Configuration→AIR.Q→H.4M) sets the % display for a 4mA
input from the relative humidity sensor. RH Sensor Value at 20ma
(Configuration→AIR.Q→H.20M) sets the % display for a 20mA
input from the relative humidity sensor.
Dehumidification Demand
When using a humidistat or switch input, the demand for
dehumidification is seen as Space Humidity Switch (Inputs→GEN.I→HUM) being Low or High. A low value means
humidity level is good and a high value means that
dehumidification is needed. When using an RH sensor, the demand
is based on the Space Humidity Sensor (Inputs→AIR.Q→SP.RH)
value compared to the Space RH Occupied Setpoint
(Setpoints→RH.SP) during the occupied period and Space RH
Unoccupied Setpoint (Setpoints → RH.UN) during unoccupied
periods. If the Space Humidity Sensor (SP.RH) value is above the
Space RH Setpoint (RH.SP), then dehumidification is needed. If
the Space Humidity Sensor (SP.RH) value is below the Space RH
Setpoint (RH.SP) minus the Space RH Deadband
(Setpoints→RH.DB), then dehumidification is no longer needed.
If the unit is configured for space sensor control
(Configuration→UNIT →U.CTL = 3), then the setpoint Reheat
Heat SP Deadband (Setpoints→RH.HB) applies. This
configuration sets the offset above the heating set point at which a
unit in Reheat2 mode will turn off. This is a protection against over
cooling the space and causing a heat demand.
NOTE: When there is a dehumidification demand, the economizer
damper position is limited to it’s minimum damper position
(Operating Mode→ECON→EC.MP).
Reheat Modes
Dehumidification (reheat) is a cooling mode function. Refer to
Cooling Operation for cooling mode control. With Humidi−MiZer
units there are three additional HVAC Mode (HVAC) expanded
texts available for the user: Reheat1, Reheat2, and
Reheat1/Reheat2. Selection of the reheat mode for each refrigerant
circuit is determined by the dehumidification demand and the
cooling demand. Table 10 shows the corresponding circuit mode
and output status for the different demand combinations. Units
with multiple circuits can operate with a combination of Reheat1
and Reheat2 circuits, as determined by the amount of space cooling
demand. See Appendix B for complete tables of unit operation
response to thermostat and humidity inputs.
NOTE: Compressor staging control for Humidi−MiZer units
requires that circuit A always operates when either circuits B or C
are on. This applies to normal operation, service test, and for
control alarm responses. This operation difference is required due
to the fact that the Motormaster outdoor fan control senses circuit
A only.
Operation of the revised refrigerant circuit for each mode is
described below.
NOTE: x = refrigerant circuit A, B, or C
Normal Cooling
For 48/50PG03−16 units, refrigerant flows from the outdoor
condenser through the normally open Cooling Valve (CV.x) to the
expansion device. Reheat1 Valve (RH1.x) and Reheat2 Valve
(RH2.x) are closed. (See Fig. 9.)
For 48/50PG20−28 and 48/50PM16−28 units, refrigerant flows
from the outdoor condenser through the de−energized 3−way valve
(RH.x) to the expansion device. Reheat2 Valve (RH2.x) is closed.
(See Fig. 12.)
Reheat 1 (Subcooling Mode)
This mode increases latent cooling and decreases sensible cooling
compared to normal cooling.
For 48/50PG03−16 units, refrigerant flows from the outdoor
condenser, through the normally open Reheat 1 Valve (RH1.x),
and through the reheat condenser coil to the expansion device.
Cooling Valve (CV.x) and Reheat2 Valve (RH2.x) are closed. (See
Fig. 10.)
For 48/50PG20−28 and 48/50PM16−28 units, refrigerant flows
from the outdoor condenser, through the energized 3−way Valve
(RH1.x), and through the reheat condenser coil to the expansion
device. Cooling Reheat2 Valve (RH2.x) is closed. (See Fig. 13.)
Reheat 2 (Hot Gas Reheat Mode)
This mode provides maximum latent cooling with little to no
sensible capacity. This mode can operate to provide
dehumidification when there is no cooling demand. Similar to
Reheat 1 mode, refrigerant flows from the outdoor condenser,
through the normally open Reheat 1 Valve (RH1.x), or through the
energized 3−way valve (RH.1x), and through the reheat condenser
coil to the expansion device. Reheat2 Valve (RH2.x) is open which
provides some compressor discharge gas to the reheat condenser to
further increase the reheat of the evaporator air stream (See Fig. 11
or 14 based on unit and size).
NOTE: Humidi−MiZer outdoor fan configurations are dependent
on the specific unit and should not be changed. The configurations
are provided in case a field replacement of a control board occurs
and the settings need to be checked or manually configured. See
Appendix A for range and defaults.
24
Table 10 – Control Modes with Humidi−MiZert System
Output and Valve States versus Circuit Mode .x = Circuit A, B, or C identifier
DEMAND AND MODEOUTPUTS48/50PG03-16 VALVES
Space
Humidity
——
LowNoOff
LowYe sCoolOnOnOffOff
HighYe sReheat1OnOnOnOff
HighNoReheat2OnOnOnOn
Circuit
Cooling
Demand
Circuit
Mode
No
power
Indoor
Fan (IDF)
OFFOffOffOff
Per
Ventilation
Control
Circuit
Compressor
(CMP.x)
OffOffOff
RH2.x
Cooling-
Reheat
Control
(CRC)*
Reheat2
Valve
(RH2.x)
CV.x
Valve
2-way
Off
(open)
Off
(open)On(closed)
Off
(open)On(closed)
On
(closed)
On
(closed)
RH1.x
Valve
2-way
(open)
(open)
(open)
Off
Off
Off
RH2.x
Valve
2-way
Off
(closed)
Off
(closed)
Off
(closed)
Off
(closed)
On
(open)
48/50PG20-28
48/50PM16-28
VALVES
RH1.x
Valve
3-way
Off
Off
Off
On
On
RH2.x
Valve
2-way
Off
(closed)
Off
(closed)
Off
(closed)
Off
(closed)
On
(open)
48/50PG and PM
COMP
CLOSED VALVE
OPEN VALVE
3-WAY VALVE
COND COIL
HUMIDI-MIZER COIL
CV.x
OUTDOOR AIR
EVAP COIL
INDOOR ENTERING
AIR
Fig. 9 − Normal Cooling Mode — Humidi−MiZert System
48/50PG03−16
RH1.x
METERING
DEVICE
C07003
25
RH2.x
COMP
48/50PG and PM
CLOSED VALVE
OPEN VALVE
3-WAY VALVE
COND COIL
CV.x
OUTDOOR AIR
RH1.x
HUMIDI-MIZER COIL
EVAP COIL
INDOOR ENTERING
AIR
Fig. 10 − Subcooling Mode (Reheat1) — Humidi−MiZert System
48/50PG03−16
RH2.x
METERING
DEVICE
C07004
COMP
CLOSED VALVE
OPEN VALVE
COND COIL
CV.x
OUTDOOR AIR
RH1.x
HUMIDI-MIZER COIL
EVAP COIL
INDOOR ENTERING
AIR
Fig. 11 − Hot Gas Reheat Mode (Reheat2) — Humidi−MiZer System
48/50PG03−16
METERING
DEVICE
a48-8174
C07005
26
RH2.x
COMP
CLOSED VALVE
OPEN VALVE
3-WAY VALVE
COND COIL
OUTDOOR AIR
a48-8222
RH1.x
HUMIDI-MIZER COIL
EVAP COIL
INDOOR ENTERING
AIR
Fig. 12 − Normal Cooling Mode — Humidi−MiZert System
48/50PG20−28 and 48/50PM16−28
RH2.x
METERING
DEVICE
48/50PG and PM
a48-8172
C07122
COMP
CLOSED VALVE
OPEN VALVE
3-WAY VALVE
COND COIL
OUTDOOR AIR
RH1.x
HUMIDI-MIZER COIL
EVAP COIL
INDOOR ENTERING
AIR
Fig. 13 − Subcooling Mode (Reheat1) — Humidi−MiZer System
48/50PG20−28 and 48/50PM16−28
METERING
DEVICE
C07123
27
RH2.x
COMP
48/50PG and PM
Reheat Control
The cooling staging and compressor control routines are
responsible for controlling each circuit in one of the three
sub−modes (Cool, Reheat1, or Reheat2). When there is only a
cooling demand, one or more circuits will operate in normal
cooling mode. When there is only dehumidification demand, all
circuits will operate in Reheat2 mode. When there is both cooling
demand and dehumidification demand, all circuits will operate in
either Reheat1 or Reheat2 mode, with the portion of Reheat1
circuits determined from the cooling demand. The Requested
Reheat2 Stages (Operating Modes→COOL→HMZR→REQ.R)
shows the control’s request for reheat circuits if cooling is not
already requesting all stages. Available Reheat2 Stages (OperatingModes→COOL→HMZR→AVL.R) displays circuits that are
available for reheat use. Actual Reheat2 Stages (OperatingModes→COOL→HMZR→ACT.R) displays the current number
of circuits running in Reheat2 mode. These three status points
should only be monitored when there is only a dehumidification
demand, because their values can be forfeited to cooling stages
when cooling demand is present. Reheat2 Stage Incr. Time
(Configuration→HMZR →R.INC) and Reheat2 Stage Decr. Time
(Configuration→HMZR→R.DEC) set the time delay when
adding or subtracting a compressor for a reheat function. These
only apply when using adaptive thermostat or space sensor control.
There are three relay outputs that show reheat status. Cool − >
Reheat1 Control (Outputs→COOL→CRC) show when the unit
has switch from pure cooling to reheat ready (based on a
dehumidification demand). Reheat2 Valve A
(Outputs→COOL→RH2.A) and Reheat2 Valve B,C
(Outputs→COOL→RH2.B) display when the respective circuit’s
Reheat2 valve is energized.
CLOSED VALVE
OPEN VALVE
3-WAY VALVE
COND COIL
OUTDOOR AIR
RH1.x
HUMIDI-MIZER COIL
EVAP COIL
INDOOR ENTERING
AIR
Fig. 14 − Hot Gas Reheat Mode (Reheat2) — Humidi−MiZert System
48/50PG20−28 and 48/50PM16−28
A circuit can be restricted from Reheat2 operation by the outside
temperature and saturated suction temperature. Reheat2 OAT
Limit A (Configuration→HMZR→RA.LO) and Reheat2 OAT
Limit B,C (Configuration→HMZR→RB.LO) set the lowest
outside temperature the respected circuit is allowed to run in
reheat2 mode. The lockout on/off status is shown as Reheat2 OAT
Lockout A (Operating Modes→COOL→HMZR→R.LO.A) and
Reheat2 OAT Lockout B,C (Operating Modes→COOL→HMZR→R.LO.B) for their respective circuit. If a circuit’s saturated
suction pressure falls below the low limit configuration during
Reheat2 operation, the circuit will switch to reheat1 (the circuits
Reheat2 valve will be turned off) for at least 2 minutes and until its
suction rises back above the high limit. Reheat2 SSP Lo Limit A
(Configuration→HMZR→RA.LP) and Reheat2 SSP Lo Limit
B,C (Configuration→HMZR→RB.LP) set the low pressure limit
for Reheat2 mode for individual circuits. Reheat2 SSP Hi Limit A
(Configuration→HMZR→RA.HP) and Reheat2 SSP Hi Limit B,
C (Configuration→HMZR→RB.HP) set the high pressure limit
for Reheat2 mode for each circuit.
Reheat Outdoor Fan Control
On specific units, the outdoor fans are controlled differently while
in a reheat mode versus just cooling mode. If Reheat Fan Control
(Configurations → HMZR → RH.FN) is set to yes, reheat fan
control is enabled and anytime the unit is running reheat it will use
the following logic to control the outdoor fans.
During reheat fan control, the outdoor fans will start and stay at
level 1 until the Reheat ODF Fan On Temp (Configurations →HMZR → RF.ON) is reached. When the outdoor air temperature
is above this reheat fan on temperature, the outdoor fans will
change to the Reheat ODF Fan On Level (Configurations →HMZR → RF.LV). The fans will stay at this level until the Reheat
ODF Fan Off Temp (Configurations → HMZR → RF.OF) is
reached. When the outdoor temperature drops below the reheat fan
off temperature, the outdoor fans will change back to level 1.
Reheat fan control will cease if at any time the unit stops running
reheat and shuts off or switches to just cooling. At this time the
fans will either stay off or run under normal fan control.
METERING
DEVICE
C07124
28
Reheat Mode Diagnostic Help
The status of reheat mode sensor inputs may be viewed within the
display Inputs menu. The status of reheat mode outputs may be
viewed within the display Outputs or Run Status→COOL menus.
Additional diagnostic help, including status of circuit reheat
temperature limit lockouts may be viewed within the
Humidi-MiZer sub-menu of the cooling mode diagnostic table atOperating Modes→COOL→HMZR.
The Service Test mode may be used to force the system to operate
in various stages of Reheat1 or Reheat2 mode, or to independently
operate the reheat valve control outputs. Fig. 15−19 show the
valve locations of Humidi−MiZer equipped units.
The following forced operating states are changed or added to the
available service test operation for a Humidi-MiZer equipped unit:
Service Test"COOL"CMP.A (Cool A Test)
A value of On will turn on circuit A in Normal Cooling mode.
Service Test→COOL→CMP.B (Cool B Test)
A value of On will turn on circuits A and B in Normal Cooling
mode.
Service Test→COOL→CMP.C (Cool C Test)
A value of On will turn on circuits A and C in Normal Cooling
mode.
Service Test"HMZR"RH1.A (Reheat1 A Test)
A value of On will turn on circuit A in Reheat1 mode.
Service Test"HMZR"RH1.B (Reheat1 B Test)
A value of On will turn on circuits A and B in Reheat1 mode.
Service Test"HMZR"RH1.C (Reheat1 C Test)
A value of On will turn on circuits A and C in Reheat 1 mode.
Service Test"HMZR"RH2.A (Reheat2 A Test)
A value of On will turn on circuit A in Reheat2 mode.
Service Test"HMZR"RH2.B (Reheat2 B, C Test)
A value of On will turn on circuits A B and C in Reheat2 mode.
Service Test"HMZR"CRC (Cool-Reheat1 Valve Test)
For 48/50PG03−16 units, a value of On will turn on the CRC
relay. This will turn on CV.x valves and turn off RH1.x valves.
For 48/50PG20−28 and 48/50PM16−28 units, a value of On will
turn on the CRC relay. This will energize RH.1 and RH.B.
Service Test"HMZR"RHV.A (Reheat2 Valve A Test)
A value of On will turn on the RH2.A valve.
Service Test"HMZR"RHV.B (Reheat2 Valve B,C Test)
A value of On will turn on the RH2.B and RH2.C valves.
Service Test"Fans"OFC.1 (Outdoor Fan 1 Test)
For 48/50PG03−14: not used. For 48/50PG16 only: a value of On
will turn on the OFC relay only which controls status of fans 1 and
3; but fans are not powered unless compressor A contactor is on.
For 48/50PG20−28 and 48/50PM16−28: Turning on OFC1,
provides power to the Motormaster controller. Outdoor fans 1 and
4 will operate under the control of the Motormaster controller.
Service Test"Fans"OFC.2 (Outdoor Fan 2 Test)
For 48/50PG03−16: Not used. For 48/50PG20−28 and
48/50PM16−28: Turn on OFC2. Outdoor fans 2, 3, 5, and 6 will
operate.
Service Test"Fans"OFC.3 (Outdoor Fan 1 Test)
Not used.
Service Test"INDP"CCH (Crankcase Heat Test)
Not used. Compressor crankcase heaters are wired directly to line
power.
RH1A
CVA
RH2A
LEGEND
CV -- Cooling Valve
RH -- Reheat Valve
Fig. 15 − Humidi−MiZert System Valve Locations
48/50PG03−07
RH1B
CVB
RH2B
CVA
RH2A
LEGEND
CV -- Cooling Valve
RH -- Reheat Valve
RH1A
Fig. 16 − Humidi−MiZert System Valve Locations
48/50PG08−14
C07007
C07006
48/50PG and PM
29
48/50PG and PM
Fig. 17 − Humidi−MiZer System Valve Locations
Air Baffles
The units with Humidi-MiZer option are equipped with
Motormaster control to maintain adequate discharge pressure for
proper unit operation during low ambient operation. This becomes
especially critical in the Reheat2 mode of operation. Wind could
have a detrimental effect depending on the orientation and the
expected design latent load of the space. If the unit is oriented with
the vertical condenser coil toward the prevailing wind, then the
field-fabricated wind baffles are required. If the unit is not oriented
as described above, but there is expected long operational periods
in the Reheat2 mode, then the field-fabricated wind baffles are
recommended. See Fig. 18 or 19 for dimensions of the
field-fabricated wind baffles.
Indoor Air Quality (IAQ)
The ComfortLink control has the capability for several methods
of demand ventilation control. Indoor air quality is typically
measured using a CO2 sensor whose measurements are displayed
in parts per million (ppm). Outdoor air quality may be measured
with a CO2 sensor for indoor-outdoor differential demand
ventilation control, or with other sensor types for the outdoor air
lockout function. The factory-installed indoor air quality CO
sensor is mounted in the return section. A field-installed indoor air
quality CO
occupied space, per job requirements. The indoor air quality modes
of operation can be affected by configurations for indoor air quality
sensor (Configuration→AIR.Q→IA.CF), indoor air quality
switch (Configuration→AIR.Q→II.CF), outdoor air quality
sensor (Configuration→AIR.Q→OA.CF) and other related fan
and limit configurations as described below.
C08057
48/50PM16−28
sensor may be mounted in the return or directly in the
2
IAQ (Analog Input)
The ComfortLink control is configured for indoor air quality
sensors which provide 4 to 20 mA for 0 to 2000 ppm. If a sensor
has a different range, the ppm display range must be reconfigured
by entering new values for Configuration→AIR.Q→I.4M andConfiguration→AIR.Q→I.20M.
IA.CF = 0 (No IAQ)
IA.CF = 0 signifies that there is no IAQ sensor installed. The
damper will operate at the Configuration→AIR.Q→EC.MN
position when the space is occupied and the indoor fan is on.
IA.CF = 1 (DCV)
When IA.CF = 1, the IAQ algorithm is set for Demand Control
Ventilation (DCV). During DCV, the damper modulates between
two user configurations depending upon the relationship between
the IAQ and the Outdoor Air Quality (OAQ). The lower of these
two positions is referred to as the Minimum IAQ Damper Position
(Configuration→AIR.Q→AQ.MN) while the higher is referred to
as Economizer Minimum Position (EC.MN). The AQ.MN should
be set to an economizer position that brings in enough fresh air to
remove contaminants and CO
people. The EC.MN should be set to an economizer position that
brings in enough fresh air to remove contaminants and CO
generated by all sources including people. The EC.MN value is the
design value for maximum occupancy.
The ComfortLink control will begin to open the damper from the
AQ.MN position when the IAQ level begins to exceed the Outdoor
Air Quality (OAQ) level by a configurable amount. This amount is
referred to as AQ Differential Low
(Configuration→AIR.Q→AQD.L). When the differential
between IAQ and OAQ reaches AQ Differential High
(Configuration→AIR.Q→AQD.H), the economizer position will
be EC.MN. When the IAQ/OAQ differential is between AQD.L
and AQD.H, the control will modulate the damper betweenAQ.MN and EC.MN in a linear manner as shown in Fig. 20. The
damper position will never exceed the bounds specified by
AQ.MN and EC.MN during IAQ control.
IA.CF = 2 (Override IAQ)
When IA.CF = 2, the IAQ algorithm maintains the damper at
Configuration →AIR.Q→EC.MN until the override condition
triggers. The override triggers when the IAQ/OAQ differential is
greater than Configuration→AIR.Q→AQD.H. The override
position is Configuration→AIR.Q→OVR.P (Economizer
Override Position). The economizer position will return to EC.MN
when the IAQ/OAQ differential is less than Configuration→AIR.Q→AQD.L.
The Override algorithm will operate whenever the building is
occupied and the indoor fan is operating or whenever the IAQ
2
algorithm has caused the indoor fan to operate. The configuration
IA.FN determines whether or not the IAQ algorithm can turn on
the indoor fan.
If the indoor fan is not operating, the economizer position will be
zero. If the override is not active and the building is
unoccupied, the economizer position will be zero. The damper
position may exceed Configuration→AIR.→EC.MN orConfiguration→AIR.Q→OVR.P to provide economizer cooling.
generated by sources other than
2
2
30
48/50PG and PM
C07009
Fig. 18 − Air Baffle Dimensions
48/50PG03−16
31
48/50PG and PM
C08077
Fig. 19 − Air Baffle Dimensions
48/50PM16−28
32
ECONOMIZER
MINIMUM
DAMPER
POSITION
(EC. MN)
VENTILATION FOR PEOPLE
MINIMUM
IAQ
DAMPER
POSITION
(AQ. MN)
INCREASING VENTILATION
VENTILATION FOR SOURCES
100
AQ
DIFFERENTIAL
LOW (AQD.L)
Fig. 20 − IAQ Control
IA.CF = 3 (Control Minimum Position)
When IA.CF = 3, an external 4 to 20 mA source is used to set the
minimum position. The 4 mA signal corresponds to 0% and the 20
mA signal corresponds to 100%. In this mode, configurations such
as Configuration→AIR.Q→EC.MN and Configuration→AIR.Q→AQ.MN are not used.
If the indoor fan is not operating, the economizer position will be
zero. The damper position may exceed the economizer minimum
position to provide economizer cooling.
IAQ (Switch Input)
Indoor air quality can also be measured using a switch input. For
the purpose of specifying the type of switch input, low CO
are considered normal. The IAQ switch input is defined by the
configuration by Configuration→AIR.Q→II.CF IAQ Level
(Switch Input). Enthalpy and IAQ are controlled by the same
switch input and therefore they cannot be used simultaneously.
II.CF = 0 (No IAQ)
The II.CF = 0 configuration signifies that there is no IAQ switch
input. The damper will operate at the EC.MN position when the
space is occupied and the indoor fan is on.
II.CF = 1 (DCV NO) or II.CF = 2 (DCV NC)
The Demand Control Ventilation (DCV) allows the economizer
minimum position to be decreased when there is no IAQ problem.
If IAQ is low, the economizer minimum position is Minimum IAQ
Damper Position (Configuration→AIR.Q→AQ.MN). If IAQ is
high, the economizer minimum position is the Economizer
Minimum Position (Configuration→AIR.Q→EC.MN).
The damper override function permits absolute positioning of the
economizer damper for ventilation purposes. The override is active
when IAQ is high and inactive when IAQ is low. The override
position is configurable by the configuration by Configuration→AIR.Q→OVR.P (Economizer Override Position).
Outdoor Air Quality (Analog Input)
The ComfortLink control is configured for outdoor air quality
sensors which provide 4 to 20 mA for 0 to 2000 ppm. If a sensor
has a different range, the ppm display range must be reconfigured
by entering new values for Configuration→AIR.Q →O.4M and
Configuration→AIR.Q→O.20M.
OA.CF = 0 (No OAQ)
This signifies there is no outdoor air sensor installed. The default
value of OAQ is 400 ppm.
OA.CF = 1 (DCV)
The outdoor air quality sensor analog input is for the value of OAQ
during demand control ventilation operation.
OA.CF = 2 (OAQ Lockout)
The outdoor air quality sensor analog input is only used to lock out
the outdoor ventilation. The economizer commanded position is set
to 0% when the ppm exceeds the OAQ lockout value configured
for Configuration→AIR.Q→OAQ.L. The default value of OAQ.L
is 600 ppm.
48/50PG and PM
C07010
33
Fan Enable (Analog IAQ Sensor)
The DCV algorithm will operate whenever the building is
occupied and the indoor fan is operating or whenever the IAQ
algorithm has caused the indoor fan to operate. The configuration
Configuration→AIR.Q→IA.FN (Fan Enable for IAQ),
determines whether or not the IAQ algorithm can turn on the
indoor fan. If the indoor fan is not operating, the economizer
position will be zero. The damper position may exceed
Configuration→AIR.Q→EC.MN to provide economizer cooling.
IA.FN = 0 (Never)
When IA.FN = 0, the IAQ algorithm can never turn on the fan.
IA.FN = 1 (Occupied)
When IA.FN = 1, the IAQ algorithm will turn on the indoor fan
whenever the building is occupied and IAQ/OAQ differential is
greater than the configuration Configuration→AIR.Q→ DF.ON
(Fan On AQ Differential). The indoor fan will turn off when the
IAQ/OAQ differential is less than the configuration
Configuration→AIR.Q→DF.OF (Fan Off AQ Differential).
IA.FN = 2 (Always)
The indoor fan performance for IA.FN = 2 is the same as the
performance when IA.FN = 1 except the algorithm is not limited to
48/50PG and PM
occupied periods only. The fan can be triggered on when the space
is occupied or unoccupied.
Fan Enable (Switch Input)
The DCV algorithm will operate whenever the building is
occupied and the indoor fan is operating or the whenever the IAQ
algorithm has caused the indoor fan to operate. The configuration
Configuration→AIR.Q→II.FN (IAQ Switch Input Fan CFG)
determines whether or not the IAQ algorithm can turn on the
indoor fan. If the indoor fan is not operating, the economizer
position will be zero. The damper position may exceed
Configuration→AIR.Q→EC.MN to provide economizer cooling.
II.FN = 0 (Never)
When II.FN = 0, the IAQ algorithm can never turn on the fan.
II.FN = 1 (Occupied)
When II.FN = 1, the IAQ algorithm will turn on the indoor fan
whenever the building is occupied and IAQ is high. The indoor fan
will turn off if IAQ returns to normal.
II.FN = 2 (Always)
The indoor fan performance for II.FN = 2 is the same as the
performance when II.FN = 1 except the algorithm is not limited to
occupied periods only. The fan can be triggered on when the space
is occupied or unoccupied.
EnergyX
For units equipped with the EnergyX factory installed option, there
will be an EnergyXv2 Supplement Installation Instructions in the
unit’s information packet. Refer to this supplement for details on
how the ERV operates relative to the base unit.
Adaptive Fan
The Adaptive Fan Option is a new method of controlling the
supply fan in a typical constant volume rooftop unit. This control
method employs a Variable Frequency Drive (VFD) to operate the
supply fan at different speeds in order to achieve energy savings
through reduced fan power. This method is specifically not
concerned with controlling static pressure in the supply duct, but
rather with setting different fan speeds for different operating
conditions, such as ventilation mode or part−load mechanical
cooling. This option should not be confused with a linearly
variable VFD concept − the different speeds are pre−programmed
per condition; there is no linear−modulation of fan speed.
Adaptive Fan is enabled by setting Adaptive Fan Operation to yes,
(Configuration→A.FAN→AF.EN = Ye s ).
The adaptive fan function is NOT a Variable Air Volume (VAV)
function. The fan adapts its speed to one of nine based on mode
and current state to satisfy a demand. The nine speeds consist of
two hard coded values and seven configurable values. The two
hard coded values are 0% (or OFF) and 100%. The seven
configurable fan speeds are: Ventilation (FS.VN), IAQ Override
(FS.AQ), Free Cool Lo (FS.E1), Free Cool Hi (FS.E2), Mech
Cooling (FS.CL), Heating (FS.HT), and Reheat2 (FS.RH).
The VFD is powered by the indoor fan contactor and is always on
unless the unit is in test mode. When the thermostat or space
sensor control conditions require the fan on, the VFD will then
ramp to desired speed. Fan speed is always calculated by
evaluating the current applicable conditions. Each fan speed
“mode” is evaluated independently, and the highest fan speed is
used. For example, if an IAQ Override event occurs during
Ventilation mode, the fan speed is set to the higher of the two
(FE.VN or FS.AQ)
NOTE: Adaptive Fan operation and Analog economizer actuator
operation are mutually exclusive because they both use the AO1
output on the ECB. Priority is given to Adaptive Fan, so if the unit
is configured for Adaptive Fan (Configuration→A.FAN→AF.EN
= Ye s), the software will automatically set the actuator control
method to digital (Configuration→ECON→E.CTL = 1
(DIG/POSITION).
Fan Speed − Ventilation (FS.VN)
This configuration defines the fan speed used in Ventilation
(fan−only) mode. Ventilation mode is when the supply fan is
running, but there is no demand for heating or cooling.
Fan Speed − IAQ Override (FS.AQ)
This configuration defines the fan speed used when an IAQ
Override is active. This pertains only to the Override function of
IAQ (Configuration→AIR.Q→IA.CF = 2) (Override IAQ) or
(Configuration→AIR.Q→II.CF = 3 or 4) (Override N/O or N/C),
not the DCV or Minimum Position functions.
Fan Speed − Free Cool Lo (FS.E1)
This configuration defines the fan speed used when in Free
Cooling at low cool mode. Refer to the Economizer Controls
Operation section for details on low cool mode.
Fan Speed − Free Cool Hi (FS.E2)
This configuration defines the fan speed used when in Free
Cooling at high cool mode. Refer to the Economizer Controls
Operation section for details on high cool mode.
Fan Speed − Mech Cooling (FS.CL)
This configuration defines the intermediate fan speed used when
mechanical cooling is being requested. Fan speed is based on how
many cooling stages the unit has, how many cooling stages are
being requested, and how many reheat stages are being requested.
If the unit only has one circuit of cooling, then the fan speed will
be 100% whenever that stage is requested. If the unit has more
then one circuit of cooling but only one is being requested, the fan
speed will be set to FS.CL. Any time more than one stage is
requested the fan speed will be set to 100%. On Humidi−MiZer
equipped units fan speed is more complex. Refer to the FS.RH and
Table 11 for details.
34
Fan Speed − Reheat2 (FS.RH)
This configuration defines the fan speed used when Hot Gas
Reheat (reheat2) is being requested. Fan speed is based on how
many cooling stages the unit has, how many cooling stages are
being requested, and how many reheat stages are being requested.
If only reheat stages are being requested, then the fan speed will be
set to FS.RH. If the unit only has one circuit of cooling, then the
fan speed will be 100% when dehumidification and cooling is
being requested. If the unit has more then one circuit of cooling
and only one cooling stage is being requested, the fan speed will be
set to FS.CL. Any time more then one cooling stage is requested
the fan speed will be set to 100%. If only one cooling stage is
requested and reheat is requested, then the fan speed will be set to
the greater of the two configurations (FS.CL or FS.RH). (See
Table 11.)
Fan Speed − Heating (FS.HT)
This configuration defines the intermediate fan speed used when in
heating mode. Fan speed is based on how many heating stages the
unit has and how many heating stages are actually on. If the unit
only has one stage of heat, then the fan speed is set to 100%
anytime the heat stage is on. If the unit has more than one stage of
heat but only one heat stage is on, then the fan speed will be set to
FS.HT. Any time more than one stage of heat is on, the fan speed
is set to 100%.
Table 11 – Cooling Fan Speed Determination
Number
of
Circuits
1
>1
Cooling
Stages
Requested
10Cooling100%
1>0Reheat1100%
0>0Reheat2FS.RH
10CoolingFS.CL
>10Cooling100%
>1>0Reheat1100%
1>0
0>0Reheat2FS.RH
Reheat
Stages
Requested
HVAC Mode
Reheat1/
Reheat2
Fan
Speed
FS.CL
or
FS.RH
Temperature Compensated Start
This logic is used when the unit is in the unoccupied state. The
control will calculate early Start Bias time based on Space
Temperature deviation from the occupied cooling and heating set
points. This will allow the control to start the unit so that the space
is at conditioned levels when the occupied period starts. This is
required for ASHRAE 90.1 compliance. A space sensor is required
for non-linkage applications.
Setting Up the System
The settings for temperature compensated start can be found in the
local display under Configuration→UNIT.
ITEMEXPANSIONRANGE UNITS CCN POINT
TCS.C
TCS.H
Temp Comp Strt Cool Factr (TCS.C)
This is the factor for the start time bias equation for cooling.
Temp Comp Strt Heat Factr (TCS.H)
This is the factor for the start time bias equation for heating.
NOTE: Temperature compensated start is disabled when these
factors are set to 0.
The following conditions must be met for the algorithm to run:
Unit is in unoccupied state.
Next occupied time is valid.
Current time of day is valid.
Valid space temperature reading is available (sensor or CCN
network).
The algorithm will calculate a Start Bias time in minutes using the
following equations:
If (space temperature > occupied cooling set point)
Start Bias Time = (space temperature – occupied cooling set
point)* TCS.C
If (space temperature < occupied heating set point)
Start Bias Time = (occupied heating set point – space
temperature)*TCS.H
When the Start Bias Time is greater than zero the algorithm will
subtract it from the next occupied time to calculate the new start
time. When the new start time is reached, the Temperature
Compensated Start mode is set, the fan is started and the unit
controlled as in an occupied state. Once set, Temperature
Compensated mode will stay on until the unit goes into the
Occupied mode. The Start Bias Time will be written into the CCN
Linkage Equipment Table if the unit is controlled in DAV mode. If
the Unoccupied Economizer Free Cool mode is active when
temperature compensated start begins, the Unoccupied Free Cool
mode will be stopped.
NOTE: The maximum minutes Start Bias can be is 180.
Carrier Comfort Network (CCN)R Configuration
It is possible to configure the ComfortLink control to participate
as an element of the Carrier Comfort Network (CCN) system
directly from the local display. This section will deal with
explaining the various programmable options which are found
under the CCN sub-menu in the Configuration mode.
The major configurations for CCN programming are located in the
local displays at Configuration→CCN. See Appendix A.
CCN Address (CCN.A)
This configuration is the CCN address the rooftop is assigned.
CCN Address (CCN.B)
This configuration is the CCN bus the rooftop is assigned.
CCN Baud Rate (BAUD)
This configuration is the CCN baud rate.
CCN Time/Date Broadcast (BROD"B.TIM)
If this configuration is set to ON, the control will periodically send
the time and date out onto the CCN bus once a minute. If this
device is on a CCN network then it will be important to make sure
that only one device on the bus has this configuration set to ON. If
more than one time broadcaster is present, problems with the time
will occur.
NOTE: Only the time and date broadcaster can perform
daylight savings time adjustments. Even if the rooftop is stand
alone, the user may want to set this to ON to accomplish the
daylight/savings function.
CCN OAT Broadcast (BROD"B.OAT)
If this configuration is set to ON, the control will periodically
broadcast its outside-air temperature at a rate of once every 30
minutes.
48/50PG and PM
35
Global Schedule Broadcast (BROD"B.GS)
If this configuration is set to ON and the schedule number
(SCH.N) is between 65 and 99, then the control will broadcast the
internal time schedule once every 2 minutes.
CCN Broadcast Acknowledger (BROD"B.ACK)
If this configuration is set to ON, then when any broadcasting is
done on the bus, this device will respond to and acknowledge.
Only one device per bus can be configured for this option.
Schedule Number (SCH.O"SCH.N)
This configuration determines what schedule the control may
follow.
48/50PG and PM
Accept Global Holidays? (SCH.O"HOL.G)
If a device is broadcasting the time on the bus, it is possible to
accept the time yet not accept the global holiday from the broadcast
message.
Override Time Limit (SCH.O"OV.TL)
This configuration allows the user to decide how long an override
occurs when it is initiated. The override may be configured from 1
to 4 hours. If the time is set to 0, the override function will
become disabled.
Timed Override Hours (SCH.O"OV.EX)
This displays the current number of hours left in an override. It is
possible to cancel an override in progress by writing “0” to this
variable, thereby removing the override time left.
SPT Override Enabled? (SCH.O"OV.SP)
If a space sensor is present, then it is possible to override an
unoccupied period by pushing the override button on the T55 or
T56 sensor. This option allows the user to disable this function by
setting this configuration to NO.
Demand Limit
Demand Limit Control may override the cooling algorithm to limit
or reduce cooling capacity during run time. The term Demand
Limit Control refers to the restriction of machine capacity to
control the amount of power that a machine will use. This can save
the owner money by limiting peaks in the power supply. Demand
limit control is intended to interface with an external network
system. This is through a CCN Loadshed POC Device or writing
to network points.
To limit stages through network writes, the points Run Status→COOL→MAX.C and Run Status→HEAT→MAX.H are forced
on the network through CCN points MAXCSTGS and
MAXHSTGS respectively. Force these to the desired maximum
stages of cooling/dehumidification and heating, respectively. When
there is no force on these points, they automatically reset to allow
all cooling/dehumidification and heating stages to be used. These
points are reset at power−on/reset (POR).
SCH.N = 0The control is always occupied.
SCH.N = 1The control follows its internal
time schedules. The user may
enter any number between 1
and 64 but it will be overwritten
to “1” by the control as it only
has one internal schedule.
SCH.N = 65-99The control is either set up to
receive to a broadcasted time
schedule set to this number or
the control is set up to broad
cast its internal time schedule
(B.GS) to the network and this is
the global schedule number it is
broadcasting. If this is the case,
then the control still follows its
internal time schedules.
When using the Loadshed POC to do Demand Limiting, the cool
and heat stage limits under both Redline and Loadshed conditions
can be set individually with configuration decisions. If the active
stages is greater then the loadshed or redline configurations when a
loadshed or redline command is given, the unit will remove stages.
Configuration→CCN→LDSH→S.GRP
This is the Loadshed Group Number and corresponds to the
loadshed supervisory devices that resides elsewhere on the CCN
network and broadcasts loadshed and redline commands to its
associated equipment parts. This variable will default to zero which
is an invalid group number. This allows the loadshed function to be
disabled until configured.
Configuration→CCN→LDSH→R.MXC
This configuration tells the unit the maximum cooling stages
allowed to be on during a redline condition.
Configuration→CCN→LDSH→S.MXC
This configuration tells the unit the maximum cooling stages
allowed to be on during a loadshed condition.
Configuration→CCN→LDSH→R.MXH
This configuration tells the unit the maximum heating stages
allowed to be on during a redline condition.
Configuration→CCN→LDSH→S.MXH
This configuration tells the unit the maximum heating stages
allowed to be on during a loadshed condition.
The two Demand Limiting methods can be active simultaneously.
The lowest cool and heat stage limits imposed by either method are
applied, and these ”effective stage limits” are shown in the points
CSTGLIMT (Run Status→COOL→LMT.C) and HSTGLIMT
(Run Status→HEAT→LMT.H), respectively. In normal running
mode, these limits will prevent stages from being added, or stages
to be removed, as applicable. In test mode, these limits are ignored,
and the user may continue to operate all stages. The point
MODEDMDL (Run Status→MODE→D.LMT) is used to show if
any Demand Limiting is in effect that prevents the unit from
operating either cooling or heating at full−capacity.
NOTE: MODEDMDL may reflect that staging is NOT limited
even though Loadshed is active, or the network points are being
forced, if the stage limits in effect are not less than the stages
present in the unit.
If a more drastic mode of Demand Limiting is required, the
network point HVACDOWN (Run Status→MODE→HV.DN) can
be used to prohibit the unit from selecting any HVAC mode, thus
preventing the operation of the supply fan, compressors, condenser
fans, and heat stages. This point must also be forced, and is reset
automatically when not forced, and at POR.
NOTE: HVACDOWN can be used as an immediate shutdown of
the unit before limiting capacity (ex. Generator switching).
Linkage
ComfortLink controls do not require any configuration settings
to establish linkage with a Linkage Coordinator. This is done
automatically when the unit’s bus and element address are
configured in the Linkage Coordinator’s LINKAGE configuration
table. The linkage information that is supplied to the ComfortLink
unit by the Linkage Coordinator is as follows:
Reference zone temperature
Reference zone occupied biased heating and cooling set points
Reference zone unoccupied heating and cooling set points
Composite occupancy mode
The unit will control the equipment based on this information and
in return will provide the Linkage Coordinator with the following
data:
Operating mode − Cooling, Heating, Free Cooling, Fire
Shutdown Evacuation, or Off
Supply−air temperature
Optimal Start Bias time (Based on worst case zone)
36
This synchronization of data optimizes the efficiency of the unit
and the zones to operate at peak system performance at all times.
This information can be seen in linkage maintenance tables of the
Linkage Coordinator and the RTU; it is updated at approximately
1−minute intervals.
Cooling and heating operation is slightly modified during Linkage
control. A PID loop is run to calculate required stages. This is
necessary because in stand alone operation, the unit tries to
anticipate the space. With Linkage, the unit must try to satisfy the
demand as soon as possible. The PID configurations are in
Configuration→PID. These values have been field tested and the
default values should NOT BE CHANGED.
For information on set up and configuration, see the Space
Temperature Control−CCN Linkage text in the Controls Quick
Start section of this book.
For additional information on the Linkage Coordinator or Zone
Controllers, please refer to their appropriate manuals.
Alarm Handling
There are a variety of different alerts and alarms in the system.
Alerts are indicated by TXXX (where XXX is the alert number) on
the display and generally signify that the improperly functioning
circuit can restart without human interaction. If an alarm occurs,
indicated by AXXX (where XXX is the alarm number), the
damaged circuit will generally not restart without an alarm reset via
the Scrolling Marquee display or CCN.
The response of the control system to various alerts and alarms
depends on the seriousness of the particular alert or alarm. In the
mildest case, an alert does not affect the operation of the unit in any
manner. An alert can also cause a “strike.” A “striking” alert will
cause the circuit to shut down for 15 minutes. This feature reduces
the likelihood of false alarms causing a properly working system to
be shut down incorrectly. If three strikes occur before the circuit
has an opportunity to show that it can function properly, the circuit
will strike out, causing the shutdown alarm for that particular
circuit. Once activated, the shutdown alarm can only be cleared via
an alarm reset.
However, circuits with strikes will be given an opportunity to reset
their strike counter to zero. As discussed above, a strike typically
causes the circuit to shut down. Fifteen minutes later, that circuit
will once again be allowed to run. If the circuit is able to run for 1
minute, its replacement circuit will be allowed to shut down (if not
required to run to satisfy requested stages). However, the
“troubled” circuit must run continuously for a user defined time
(Configuration→COOL→RST.C) with no detectable problems
before the strike counter will be reset to zero. Default value is
5 minutes.
CCN Alarm Broadcast
Operators of CCN networks might not want to be notified of
“striking” alerts for refrigerant circuits until the circuit has been
shut down due to 3 strikes. Set the cooling configuration of Alert
Each Strike (Configuration→COOL→ALM.N on display,
ALM_NOW on CCN) to YES to broadcast each circuit strike alert.
Set Alert Each Strike to NO to broadcast only circuit shut down.
Alert Each Strike configuration is ignored during Service Test and
all alerts are broadcast.
Alarm Relay Output
The alarm relay output is a normally open 24 vac output between
field connection terminal board terminals C and X. Selection of
which alerts and alarms will result in closing of the alarm relay
may be set in the Alarm Relay Configuration
(Configuration→ALM.O). Setting a configuration to YES will
result in the alarm output relay, ALRM, status of ON and 24 vac
between C and X when that particular condition is in an alarm
state. Setting a configuration to NO will result in no action by the
alarm output relay for that particular condition.
NOTE: An accessory filter switch can be used along with the
alarm relay output function to indicate dirty filter service need.
See the Troubleshooting section for more information on viewing,
diagnosing, and clearing alerts and alarms.
TROUBLESHOOTING
The Scrolling Marquee display shows the actual operating
conditions of the unit while it is running. If there are alarms or
there have been alarms, they will be displayed in either the current
alarm list or the history alarm list. (See Table 14.) The Service Test
mode allows proper operation of the compressors, fans, and other
components to be checked while the unit is not operating. See
Service Test.
Complete Unit Stoppage
There are several conditions that can cause the unit not to provide
heating or cooling:
If an alarm is active which causes the unit to shut down,
diagnose the problem using the information provided in Alarms
and Alerts section below.
Cooling and heating loads are satisfied.
Programmed occupancy schedule.
General power failure.
Tripped CB1, CB2, or CB3 (24-volt transformer circuit
breakers).
Blown fuse (FU1−4)
Unit is turned off through the CCN network.
If supply-air temperature is less than the Minimum SAT Lower
Level (SAT.L) configuration value, unit cannot cool.
If outdoor-air temperature is less than the Compressor Lockout
Temperature (CA.LO, CB.LO, CC.LO) configuration value, unit
cannot cool.
If outdoor-air temperature is greater than the Heating Lockout
Temperature (HT.LO) configuration value, unit cannot heat.
Restart Procedure
Before attempting to restart the machine, check the alarm list to
determine the cause of the shut down. If the shutdown alarm for a
particular control function has occurred, determine and correct the
cause before allowing the unit to run under its own control again.
When there is problem, the unit should be diagnosed in Service
Test mode. The alarms must be reset before the control function
can operate in either Normal mode or Service Test mode.
Alarms and Alerts
Viewing and Clearing Unit Alarms
Presence of active alarms will be indicated on the Scrolling
Marquee display by the Alarm Status light turning on and by the
number of active alarms being displayed in the automatic View of
Run Status. Presence of active alarms may also be signaled on the
Alarm Output terminals. Each alarm may also be broadcast on the
CCN network. Active alarms and past alarm history can be
reviewed and cleared via the local display or a CCN device. The
following menu locations are used for the local display:
Alarms"R.CURR (Reset All Current Alarms)
Change to YES to reset all active alarms. Turning unit power off
will also reset all current alarms.
48/50PG and PM
37
Alarms"R.HIST (Reset Alarm History)
Change to YES to reset the alarm history. Turning unit power off
will not reset the alarm history.
Alarms"CURR (Currently Active Alarms)
Use the ENTER key, then scroll through any alarm numbers using
the up and down arrow keys. Alarms are displayed in numerical
order.
Alarms"HIST (Alarm History)
Use the ENTER key, then scroll through any alarm numbers using
the up and down arrow keys. Up to 20 alarms are displayed in
order of occurrence, with time and date.
The description for an alarm can be viewed on the Scrolling
Marquee display by pressing ESCAPE and ENTER keys
simultaneously while displaying the alarm code number. Be sure to
expand description for each code, because in some cases there are
different possible descriptions and causes for the same code
number.
Diagnostic Alarm Codes and Possible Causes
Alert Codes T051, T052, T055 and T059
There are 4 different texts for each alert code. There are two
different alerts which have corresponding test mode alerts indicated
48/50PG and PM
with “Service Test” in the expanded text. Pressing enter and esc on
the marquee or navigator to expand the T051, T052, T055, or
T059 alert will show you one of the below alerts. Make sure the
expanded text is read correctly before troubleshooting. Alert codes
T051, T052, T055, and T059 are for compressors A1, A2, B1, and
C1, respectively.
Compressor Safety Trip
These alerts occur when the Current Sensor (CS) does not detect
compressor current during compressor operation. When this
occurs, the control turns off the compressor and logs a strike for
the respective circuit. These alerts reset automatically. The
possible causes are: high−pressure switch (HPS) open (The HPS
is wired in series with compressor relays on the MBB. If the
high−pressure switch opens during compressor operation, the
compressor stops, and the CS no longer detects current, causing
the control to activate this alert), compressor internal protection
is open, or a wiring error (a wiring error might not allow the
compressor to start).
To check out the alert:
1. Turn on the compressor in question using Service Test
mode. If the compressor does not start, then most likely the
problem is one of the following: HPS open, open internal
protection, incorrect safety wiring, or incorrect compressor
wiring.
2. If the compressor starts, verify that the indoor and outdoor
fans are operating properly.
3. If the CS is always detecting current, then verify that the
compressor is on. If the compressor is on, check the
contactor and the relay on the MBB. If the compressor is off
and there is no current, verify CS wiring and replace if
necessary.
4. Return to Normal mode and observe compressor operation
to verify that compressor current sensor is working and
condenser fans are energized after compressor starts.
Compressor Current Detected After Turnoff
These alerts occur when the Current Sensor (CS) detects current
when the compressor should be off. When this occurs, the
control turns off all of the compressors. Use the Scrolling
Marquee to reset the alert. The possible causes are a welded
contactor or frozen compressor relay on MBB.
To check out alert:
1. Place the unit in Service Test mode. All compressors should
be Off.
2. Verify that there is not 24vac at the contactor coil. If there is
24vac at the contactor, check relay on MBB and wiring.
3. Check for welded contactor.
4. Verify CS wiring.
5. Return to Normal mode and observe compressor operation
to verify that compressor current sensor is working and
condenser fans are energized after compressor starts.
Alert codes T064, T065, and T080 are for circuits A, B and C,
respectively. These alerts occur when the temperature is outside the
range –40 to 240F (–40 to 116C). When this occurs, the
control will use only the outdoor temperature to control the
outdoor fans. If both the SCT and OAT fail, then circuit shutdown
alarm will occur also. The cause of the alert is usually a faulty
thermistor, a shorted or open thermistor caused by a wiring error,
or a loose connection.
Alert Code T066, T067, and T081 − Circuit Saturated Suction
Temperature Thermistor Failure
Alert codes T066, T067, and T081 are for circuits A, B and C,
respectively. These alerts occur when the unit’s suction transducers
are turned off internally. Cooling will not operate. This is usually
due to a network force on a non exposed CCN point. Reload
factory defaults or reinstall software on the MBB. Consult the
network manager if alert continues.
Alert Code T073 − Outdoor Air Temperature Thermistor
Failure
This alert occurs when the temperature is outside the range –40 to
240F (–40 to 116C). For all units, all ambient temperature
lockout limits for cooling and heating are ignored. For all units, if
both SCT and OAT fail, then circuit shutdown alarm will also
occur. For economizer equipped units, the economizer will not
operate to provide cooling. The economizer will still operate for
ventilation. The control will use condenser temperatures for
outdoor fan control. For units with CCH crankcase heat relay
control, the crankcase heat relay will be turned on if any
compressor is off. This alert resets automatically. The cause of the
alert is usually a faulty thermistor, a shorted or open thermistor
caused by a wiring error, or a loose connection.
Alert Code T074 − Space Temperature Thermistor Failure
This alert occurs when the temperature is outside the range –40 to
240F (–40 to 116C). This alert will only occur if the unit
control type is configured for Space Sensor (versus Thermostat).
Cooling and heating will not operate. For economizer equipped
units, the economizer will still operate for ventilation. This alert
resets automatically. The cause of the alert is usually a faulty
thermistor in the T−55, T−56, or T−58 device, a shorted or open
thermistor caused by a wiring error, or a loose connection.
38
Alert Code T075 − Supply Air Temperature Thermistor
Failure
This alert occurs when the temperature is outside the range –40 to
240F (–40 to 116C). Economizer cooling and adaptive
compressor staging cannot occur while this alarm is active. This
alert resets automatically. The cause of the alert is usually a faulty
thermistor, a shorted or open thermistor caused by a wiring error,
or a loose connection.
Alert Code T076 − Return Air Thermistor Failure
This alert occurs when the temperature is outside the range –40 to
240F (–40 to 116C). This alert will only occur if the unit is
configured for a return air sensor. Economizer differential dry bulb
control will not be allowed during this alert. This alert resets
automatically. The cause of the alert is usually a faulty thermistor, a
shorted or open thermistor caused by a wiring error, or a loose
connection.
Alert Code T077 − Space Relative Humidity Sensor Failure
This alert occurs when the input is less than 3.5 mA and the sensor
is configured as installed. If a humidistat is not installed, then
dehumidification will not be functional. Check sensor and wiring.
This alert clears automatically.
NOTE: An ECB must be installed to use the space relative
humidity sensor.
Alert codes T092, T093, and T101 are for circuits A, B and C,
respectively. These alerts occur when the board does not properly
read the transducer voltage. A circuit cannot run when this alert is
active. Use the Scrolling Marquee to reset the alarm. The cause of
the alert is usually a faulty transducer, faulty 5−v power supply, or
a loose connection.
Alert Codes T102, T103, and T104 − Compressor Current
Sensor Failure
Alert codes T102, T103, and T104 are for compressors A1 and A2,
B1 and C1, respectively. These alerts occur when the output of the
current sensor (CS) is a constant high value. These alerts reset
automatically. The cause of the alert is a wiring error or a loose
connection. If the problem cannot be resolved and the CS board
must be replaced, the CS board can be temporarily disabled while
securing a replaced board. A CS board is disabled by setting the
corresponding configuration to DISABLE
(Configuration→COOL→CIR.A→CS.A1, CS.B1 or CS.C1).
Alert Codes T110, T111, and T140 – Circuit Loss of Charge
Alert codes T110, T111, and T140 are for circuits A, B and C,
respectively. These alerts have “Service Test” text that will be
displayed if the alert occurred during service test. These alerts
occur when the compressor is OFF and the suction pressure is less
than 5 psig and OAT is greater than –5F for 1 continuous minute.
Use the Scrolling Marquee to reset the alert. The cause of the alert
is usually low refrigerant pressure or a faulty suction pressure.
These alerts only occur when the compressor is OFF because the
low refrigerant pressure alarms (alerts T133, T134 and T141)
handle this situation when the compressor is operating.
Alert Codes T126, T127 and T142 − Circuit High Discharge
Pressure
Alert codes T126, T127, and T142 are for circuits A, B and C,
respectively. These alerts have “Service Test” text that will be
displayed if the alert occurred during service test. These alerts
occur when alerts T051, T055, or T059 are active while the
appropriate condensing temperature is greater than 150F. These
alerts reset automatically. The cause of the alert is usually an
overcharged system, high outdoor ambient temperature coupled
with dirty outdoor coil, plugged filter drier, or a faulty
high−pressure switch. See Alerts T051, T055 and T059 for
diagnostic procedure.
Alert codes T133, T134 and T141 are for circuits A, B and C,
respectively. These alerts have “Service Test” text that will be
displayed if the alert occurred during service test. These alerts
occur when the compressor is operating and the evaporating
temperature (converted from the suction pressure) is less than
configured low suction control levels,
Configuration→COOL→SST→SST.1 (Low Suction — Level 1)
or SST.2 (Low Suction — Level 2) or SST.3 (Low Suction Level
3). The circuit SST value must be less than SST.1 (for 5 minutes),
SST.2 (for 4 minutes), or SST.3 (for 3 minutes when using the
economizer and 1.5 minutes when not using the economizer) for
the alert to occur. When the outdoor temperature is less than 40F,
the above values are reduced 1F for every 2F the OAT is below
40F. An alert will also occur if the circuit SST value is less than
SST.3 –5F for 20 seconds and the outdoor temperature is above
40F. All the above timers will reset if the suction temperature rises
above SST.O for 1 minute. These alerts cause a strike for the
respective circuit. If the OAT is less than 10F, the circuit will shut
down without a strike. These alerts will activate when the coil
becomes frosted. However, during the 15−minute reset period, the
coils will thaw and strike should clear at restart if there is nothing
else wrong with the circuit. The alert resets automatically. The
cause of the alert is usually low refrigerant charge, dirty filters,
evaporator fan operating backwards, loose or broken belt, plugged
filter drier, faulty transducer, excessively cold return air, or stuck
open economizer when the ambient temperature is low.
Alert Codes T140 − Circuit C Loss of Charge
See Alert T110.
Alert Codes T141 – Circuit C Low Refrigerant Pressure
See Alert T133.
Alert Codes T142 – Circuit High Discharge Pressure
See Alert T126.
Alert Codes T143, T144 − Circuit Failure to Pressurize
Alert codes T143, T144, and T145 are for circuits A, B, and C,
respectively. These alerts have “Service Test” text that will be
displayed if the alert occurred during service test. These alerts
occur when the compressor turns on and the suction pressure does
not drop at least 10 PSIG and stay there for the first 20 seconds
AND the condensing temperature does not rise at least 5F and
stay there for the first 65 seconds (both conditions have to occur).
These alerts cause a strike for the respective circuit. The alert resets
automatically. The cause of the alert is usually compressor wiring
causing reverse rotation or a faulty compressor.
48/50PG and PM
39
Alarm Code T153 − Real Time Clock Hardware Failure
The alert occurs when the RTC clock chip on the MBB is not
responding. Time and date functions will not operate, such as local
occupancy schedules. The unit will default to 24/7 unoccupied
mode. Recovery is automatic but MBB board replacement may be
necessary. Cycling power to the control and reconfiguring the time
and date should be tried before board replacement.
Alarm Code A154 − Serial EEPROM Hardware Failure
The unit will completely shut down. The serial EEPROM chip on
the MBB which stores the unit’s configuration is not responding.
Recovery is automatic, but MBB board replacement may be
necessary. Cycling the power to the control should be tried before
board replacement.
Alarm Code T155 − Serial EEPROM Storage Failure Error
Configuration data in the serial EEPROM chip can not be verified.
The unit will run to last know good values or defaults, and
therefore operating errors may occur. Recovery is automatic but
MBB board replacement may be necessary. Cycling power to the
control and reconfiguring the control points should be tried before
board replacement.
Alarm Code A156 − Critical Serial EEPROM Storage
Fail Error
48/50PG and PM
The unit will completely shut down. Critical configuration data in
the serial EEPROM chip can not be verified. Recovery is automatic
but MBB board replacement may be necessary. Cycling power to
the control and reconfiguring the critical control points should be
tried before board replacement. Check the configurations for the
following critical points:
Configuration→COOL→N.CIR (Number of Circuits)
Configuration→COOL→N.A(Compressors on Circuit A)
Configuration→COOL→OFC→OFC.3 (OFC.3 Enable, CCH
Disable)
Configuration→HMZR→REHT (Humidi−MiZer Equipped)
Configuration→HMZR→RH.FN (Reheat Fan Control)
Alarm Code A157 − A/D Hardware Failure
The unit will completely shut down. The analog to digital
conversion chip on the MBB has failed. Recovery is automatic but
MBB board replacement may be necessary. Cycling power to the
control should be tried before board replacement.
Alarm Codes A163, A164, and A165 − Circuit Down due to
Failure
Alarm codes A163, A164, and A165 are for circuits A, B, and C,
respectively. These alarms have “Service Test” text that will be
displayed if the alarm occurred during service test. These alarms
occur when a circuit has 3 strikes. Use the Scrolling Marquee
display to reset the alarm. Investigate the alarm that caused the
strikes to occur.
Alert Code T173 – Loss of Communication with the Energy
Management Module
This alert occurs when the MBB cannot communicate with the
EMM. These units do not currently support any operation with the
EMM. This alert is caused by an internal force to look for the
EMM board. When this happens, reload software on the MBB and
do not restore configurations, the factory configurations must be
used at first. Replace the MBB if alert continues.
Alert Code T179 – Loss of Communication with the
Economizer Control Board
This alert occurs when the MBB cannot communicate with the
ECB. Economizer operation will be disabled. This is usually
caused by a wiring problem. If a relative humidity sensor is
installed and configured but there is not an ECB installed on the
unit, this alert will be generated (the ECB is required for RH sensor
operation). Investigate using the Low Voltage Schematic, check
that the ECB address is correct, and verify the resistance between
pins on the LEN connections.
Alert Code T180 − Loss of Communication with the
Economizer Actuator
This alert occurs when the ECB cannot communicate with the
Belimo Actuator. If the analog signal is connected properly, the
economizer can still be controlled through it. This is usually
caused by a wiring problem, actuator failure, or the wrong actuator.
Investigate using the Low Voltage Schematic. Make sure the
actuator is a MFT communication actuator and verify the feedback
signal from the actuator is correct.
Alert Code T181 – Loss of communication with Outside Air
Unit
This alert occurs when the Outdoor Air Unit Type (Configuration→ OAU → OA.TY) is not set to 0 and the OAU Operating Mode
(Run Status → OAU → OA.OP) has not been communicated in
the past 3 minutes. The control will reset all OAU data. This alert
will automatically reset when communication is established again.
This alert is usually caused by a wiring problem or a problem with
the OAU communication.
Alarm Code A200 − Linkage Timeout − Comm Failure
This alarm occurs when the MBB fails to communicate with a
Linkage device. This only occurs when the MBB has previously
communicated with a Linkage device since last power cycle. If a
back up sensor was not installed the T074 alert will occur shortly
after this one. Reset power to the unit and verify Linkage is
communicating.
Alarm Code A404 − Fire Shutdown
This alarm occurs when the shutdown input is either open or
closed depending upon its configuration. This alarm is usually
caused by an auxiliary device that is trying to shut down the unit,
e.g., smoke detector. The configuration for this switch input can be
found at variable Configuration→UNIT→FS.SW. Verify that the
configuration is set correct, verify the wiring and auxiliary device.
This alarm resets automatically.
Alert Code T408 − Dirty Air Filter
This alert occurs when the Filter Status switch senses a plugged
filter for 120 continuous seconds after the indoor fan has been
running for 10 seconds. Because the Dirty Air Filter switch can be
configured normally opened or closed, the switch might be open or
closed. The configuration for this switch input can be found at
variable Configuration→UNIT→FL.SW. Verify that the
configuration is set correct, verify the wiring and filter status
switch. The hose should be connected to the low side of the switch.
This alert resets automatically.
Alert Code T409
There are 2 different texts for this alert code. Pressing enter and esc
on the marquee or navigator to expand the T409 alert will show
you one of the below alerts. Make sure the expanded text is read
correctly before troubleshooting.
Fan Status Switch On, Fan Contactor Off
This alarm occurs when the fan status switch has sensed that the
indoor fan has been on for 10 seconds and the indoor fan
feedback has determined that the indoor fan should be off.
Because the Fan Status switch can be configured normally
opened or closed, the switch might be open or closed. The
configuration for this switch input can be found at
Configuration→UNIT→FN.SW. Verify that the configuration
is set correctly. Verify the wiring and fan status switch. The hose
should be connected to the high side of the switch. If the IDF is
configured to shut down the unit when this alarm occurs
(Configuration→UNIT→IDF.F = YES), then this alarm can
only be reset manually and the unit is shut down. If the IDF is
not configured to shut the unit down when this alarm occurs
(IDF.F = NO), then this alarm resets automatically and no
specific control action is taken.
40
Table 12 – ComfortLinkt Alarm Codes
ALARM
OR
ALERT
NUMBER
T051
T052
T055
T059
T064
T065
T066
T067
T073Outdoor Air Temperature Thermistor FailureNo cooling with economizerAutomatic
T074Space Temperature Thermistor Failure
T075Supply Air Temperature Thermistor Failure
T076Return Air Thermistor Failure
T077Space Relative Humidity Sensor Failure
T080
T081
T092Circuit A Suction Pressure Transducer FailureLockout Circuit AManual
T093Circuit B Suction Pressure Transducer FailureLockout Circuit BManual
T101Circuit C Suction Pressure Transducer FailureLockout Circuit CManual
T102Compressor A1 Current Sensor Failure
T103Compressor B1 Current Sensor Failure
T104Compressor C1 Current Sensor Failure
T110
T111
T126
T127
T133
T134
T140
T141
T142
T143
T144
T145
T153Real Timeclock Hardware Failure
Compressor A1 Safety Trip
Service Test - Compressor A1 Safety Trip
Compressor A1 Current Detected After Turnoff
After Turnoff
Compressor A2 Safety Trip
Service Test - Compressor A2 Safety Trip
Compressor A2 Current Detect After Turnoff
After Turnoff
Compressor B1 Safety Trip
Service Test - Compressor B1 Safety Trip
Compressor B1 Current Detect After TurnoffTurn off all compressorsAutomatic
After Turnoff
Compressor C1 Safety Trip
Service Test - Compressor C1 Safety Trip
Compressor C1 Current Detect After Turnoff
After Turnoff
Circuit A Saturated Condensing Temp Thermistor
Failure
Circuit B Saturated Condensing Temp Thermistor
Failure
Circuit A Saturated Suction Temperature
Thermistor Failure
Circuit B Saturated Suction Temperature
Thermistor Failure
Circuit C Saturated Condensing Temp Thermistor
Failure
Circuit C Saturated Suction Temperature
Thermistor Failure
Compressor A2 Current Sensor Failure
Circuit A Loss of Charge
Service Test - Circuit A Loss of Charge
Circuit B Loss of Charge
Service Test - Circuit B Loss of Charge
Circuit A High Discharge Pressure
Service Test - Circuit A High Discharge Pressure
Circuit B High Discharge Pressure
Service Test - Circuit B High Discharge Pressure
Circuit A Low Refrigerant Pressure
Service Test - Circuit A Low Refrigerant Pressure
Circuit B Low Refrigerant Pressure
Service Test - Circuit B Low Refrigerant Pressure
Circuit C Loss of Charge
Service Test - Circuit C Loss of Charge
Circuit C Low Refrigerant Pressure
Service Test - Circuit C Low Refrigerant Pressure
Circuit C High Discharge Pressure
Service Test - Circuit C High Discharge Pressure
Circuit A Failure To Pressurize
Service Test - Circuit A Failure to Pressurize
Circuit B Failure To Pressurize
Service Test - Circuit B Failure to Pressurize
Circuit C Failure To Pressurize
Service Test - Circuit C Failure to Pressurize
DESCRIPTION
* See Legend on next page
ACTION TAKEN BY
CONTROL
Add Strike for Circuit AAutomatic
Turn off all compressorsAutomaticWelded contactorService Test - Compressor A1 Current Detected
Add Strike for Circuit AAutomatic
Turn off all compressorsAutomaticWelded contactorService Test - Compressor A2 Current Detected
Add Strike for Circuit BAutomatic
Add Strike for Circuit CAutomatic
Turn off all compressorsAutomaticWelded contactorService Test - Compressor C1 Current Detected
Use OAT to control Outdoor
Use OAT to control Outdoor
No cooling with economizer
and No adaptive compressor
differential Dry Bulb control
Use OAT to control Outdoor
If CS.A1 = Enable, then no
If CS.A2 = Enable, then no
If CS.B1 = Enable, then no
If CS.C1 = Enable, then no
No time and date schedule
fans
fans
No Circuit A CoolingAutomaticCircuit A Suction transducer internally forced inactive
No Circuit B CoolingAutomaticCircuit B Suction transducer internally forced inactive
If U.CTL = 3, then no
heating or cooling
staging
If RAT.S = Yes, then no
If RH.S = Yes, then no
indoor humidity control
fans
No Circuit C CoolingAutomaticCircuit C Suction transducer internally forced inactive
T051 current alarm
T052 current alarm
T055 current alarm
T059 current alarm
Lockout Circuit AManualLow refrigerant or faulty suction pressure transducer
Lockout Circuit BManualLow refrigerant or faulty suction pressure transducer
Shutdown Circuit AAutomatic
Shutdown Circuit BAutomatic
Add Strike for Circuit AAutomatic
Add Strike for Circuit BAutomatic
Lockout Circuit CManualLow refrigerant or faulty suction pressure transducer
Add Strike for Circuit CAutomatic
Shutdown Circuit CAutomatic
Add Strike for Circuit AAutomaticWiring causing reverse rotation or faulty compressor
Add Strike for Circuit BAutomaticWiring causing reverse rotation or faulty compressor
Add Strike for Circuit CAutomaticWiring causing reverse rotation or faulty compressor
AutomaticNo time/date configured, software failure, or MBB failure
Faulty, shorted, or open thermistor caused by wiring error or
loose connection.
Faulty, shorted, or open thermistor caused by wiring error or
loose connection.
Faulty, shorted, or open thermistor caused by wiring error or
loose connection.
Faulty, shorted, or open thermistor caused by wiring error or
loose connection.
Faulty, shorted, or open thermistor caused by wiring error or
loose connection.
Faulty, shorted, or open thermistor caused by wiring error or
loose connection.
Faulty, shorted, or open sensor caused by wiring error or loose
connection.
Faulty, shorted, or open thermistor caused by wiring error or
loose connection.
Faulty transducer, faulty 5-V power supply, or loose
connection
Faulty transducer, faulty 5-V power supply, or loose
connection
Faulty transducer, faulty 5-V power supply, or loose
connection
Faulty current sensor caused by wiring error or loose
connection
Faulty current sensor caused by wiring error or loose
connection
Faulty current sensor caused by wiring error or loose
connection
Faulty current sensor caused by wiring error or loose
connection
An overcharged system, high outdoor ambient temperature
coupled with dirty outdoor coil, plugged filter drier, or a faulty
high-pressure switch.
An overcharged system, high outdoor ambient temperature
coupled with dirty outdoor coil, plugged filter drier, or a faulty
high-pressure switch.
Low refrigerant charge, dirty filters, evaporator fan turning
backwards, loose or broken fan belt, plugged filter drier, faulty
transducer, excessively cold return air, or stuck open
economizer when the ambient temperature is low.
Low refrigerant charge, dirty filters, evaporator fan turning
backwards, loose or broken fan belt, plugged filter drier, faulty
transducer, excessively cold return air, or stuck open
economizer when the ambient temperature is low.
Low refrigerant charge, dirty filters, evaporator fan turning
backwards, loose or broken fan belt, plugged filter drier, faulty
transducer, excessively cold return air, or stuck open
economizer when the ambient temperature is low.
An overcharged system, high outdoor ambient temperature
coupled with dirty outdoor coil, plugged filter drier, or a faulty
high-pressure switch.
PROBABLE CAUSE
48/50PG and PM
41
ALARM
OR
ALERT
NUMBER
A154Serial EEPROM Hardware FailureUnit ShutdownAutomaticSoftware failure or MBB failure
T155Serial EEPROM Storage Failure ErrorUnit operation errorsAutomaticSoftware failure or MBB failure
A156Critical Serial EEPROM Storage Fail ErrorUnit ShutdownAutomaticSoftware failure or MBB failure
A157A/D Hardware FailureUnit ShutdownAutomaticSoftware failure or MBB failure
A163
A164
A165
T173
T179
T180
T181Loss of communication with Outside Air UnitReset OAU dataAutomaticWiring Problem or OAU communication failure
A200Linkage Timeout Error - Comm Failure
A404Fire ShutdownUnit ShutdownAutomaticSmoke detected by smoke detector
T408Dirty Air FilterAlert GeneratedAutomaticDirty Filter
48/50PG and PM
T409
T410
T411Thermostat Y2 Input Activated without Y1 Activated
T412
T413
T414
T415IAQ Input Out of RangeNo IAQ OperationsAutomaticBad sensor, bad wiring, or sensor configured incorrectly.
T416OAQ Input Out of RangeNo OAQ OperationsAutomaticBad sensor, bad wiring, or sensor configured incorrectly.
T418
LEGEND
ECB- Economizer Control Board
IGC- Integrated Gas Controller
MBB - Main Base Board
OAT- Outdoor-Air Thermistor
Table 12 — ComfortLinkt Alarm Codes (cont)
DESCRIPTION
Circuit A Down Due to Failure
Service Test - Circuit A Down Due to Failure
Circuit B Down Due to Failure
Service Test - Circuit B Down Due to Failure
Circuit C Down Due to FailureLockout Circuit CManualCircuit has 3 strikes or has been locked out by another alarm
Service Test - Circuit C Down Due to Failure
Loss of communication with the Energy
Management Module
Loss of communication with the Economizer
Control Board
Loss of communication with the Economizer
Actuator
Fan Status Switch ON, fan commanded off
Fan Status Switch OFF, fan commanded on
R-W1 Jumper Not Installed in Space Temp ModeUnable to run heatAutomaticMissing jumper wire
R-W1 Jumper Must Be Installed to Run Heat In
Service Test
Thermostat W2 Input Activated without W1
Activated
Thermostat Y and W Inputs Activated
Simultaneously
Economizer Damper Actuator Out of CalibrationAlert GeneratedAutomatic
This alert occurs in Thermostat mode when Y2 is energized and
Y1 is not. Verify thermostat and thermostat wiring. When Y2 turns
On, the software will behave as if Y1 and Y2 are both On. When
Y2 turns Off, the software will behave as if Y1 and Y2 are both
Off. This alert resets automatically when Y1 is turned On.
This alert occurs in Thermostat mode when W2 is energized and
W1 is not. Verify thermostat and thermostat wiring. When W2
turns On, the software will behave as if W1 and W2 are both On.
When W2 turns Off, the software will behave as if W1 and W2 are
both Off. This alert resets automatically when W1 is turned On.
Alert Code T413 – Thermostat Y and W Inputs Activated
Simultaneously
This alert occurs in Thermostat mode when Y1 or Y2 is energized
simultaneously with W1 or W2. Verify thermostat and thermostat
wiring. The software will enter either the cooling or heating mode
depending upon which input turned on first. This alert resets
automatically when Y1 and Y2 are not on simultaneously with W1
and W2.
Alert Code T414
There are 6 different alerts under this one alert code. Pressing enter
and esc on the marquee or navigator to expand the T414 alert will
show you one of the below alerts. All these alerts are generated by
the Belimo actuator and reported to the ECB. These alerts can only
occur if the ECB is controlling the actuator digitally through MFT.
Economizer Damper Actuator Out of Calibration
This alert occurs when the economizer actuator reports a control
angle (Operating Modes→ECON→C.ANG) less than the
minimum control angle (Configuration→ECON→M.ANG).
Initiate economizer calibration (Service Test→INDP→E.CAL)
using the Service Test menu. The economizer calibration
procedure will try to find new maximum open and closed
positions. If the alert does not clear automatically after the
calibration procedure is complete, investigate what is limiting
economizer rotation. After that step, run another calibration, but
first power off unit (spring return the damper), loosen the
actuator clamp, and while pushing the damper closed, tighten the
This alert occurs when the actuator load is too high. Investigate
to determine what is increasing damper load, and verify that the
actuator is the correct size for the unit. This alert resets
automatically.
Economizer Damper Actuator Hunting Excessively
This alert occurs when the commanded damper position is
changing too rapidly. The stop jog ratio must be less than 21%
to clear this alert. Leave the actuator powered with no signal for
a few hours to allow the ratio to decrease (may have to wait
longer than a few hours). If the alert continues, determine if the
ECB or actuator is bad. This alert resets automatically.
Economizer Damper Stuck or Jammed
This alarm occurs when the actuator is no longer moving and the
actual position is greater than or less than 3% of the commanded
position for 20 seconds. Investigate what is stopping the rotation
of the actuator and fix. This alert resets automatically.
Economizer Damper Actuator Mechanical Failure
This alert occurs when the actuator senses a catastrophic failure.
Investigate actuator and replace if necessary. This alert resets
automatically.
Economizer Damper Actuator Direction Switch Wrong Position
This alert occurs when the economizer damper direction switch
is in the wrong position. The direction switch should be in the
clockwise position and the actuator should be mounted so that
the CW face of the actuator is accessible. Correct if necessary.
This alert clears automatically.
48/50PG and PM
43
Alert Code T415 − IAQ Input Out of Range
This alert occurs when the IAQ input (on ECB) is less than 3.5 mA
and the sensor is configured as installed. IAQ operation will be
disabled. Check sensor and wiring. This alert clears automatically.
Alert Code T416 − OAQ Input Out of Range
This alert occurs when the OAQ input (on ECB) is less than 3.5
mA and the sensor is configured as installed. OAQ operation will
be disabled. Check sensor and wiring. This alert clears
automatically.
Alert Code T418
There are 4 different alerts under this one alert code. Pressing enter
and esc on the marquee or navigator to expand the T418 alert will
show you one of the below alerts. All these alerts are generated by
the OAU device and reported to the MBB. These alerts can only
occur if the Outdoor Air Unit Type (Configuration → OAU →OA.TY) is not set to 0. Control action is only taken on the OAU
side and these alerts will reset automatically when the OAU clears
them. Refer to the EnergyXv2 Supplement Installation
Instructions for more information on these alarms.
OAU Motor Failure
This alert occurs when the OAU Motor Failure Alarm (Operating
48/50PG and PM
Modes → OAU → ALM.1) is on. This is usually due to motor
status reporting a failure on the OAU.
OAU Dirty Filter
This alert occurs when the OAU Dirty Filter Alarm (Operating
Modes → OAU → ALM.2) is on. This is usually due to filter
status reporting a dirty filter on the OAU.
OAU Low CFM
This alert occurs when the OAU Low CFM Alarm (Operating
Modes → OAU → ALM.3) is on. This is usually due to OAU not
capable of achieving proper CFM.
OAU General Alarm
This alert occurs when the OAU Alarm (Operating Modes →
OAU → ALM.4) is on. Refer to the specific OAU documentation
for details.
Control Module Communication
Red LED
Proper operation of the MBB and ECB control boards can be
visually checked by looking at the red status LEDs. When
operating correctly, the red status LEDs should blink in unison at a
rate of once every 2 seconds. If the red LED on the ECB is not
blinking, check the DIP switch positions on the board. If the red
LEDs are not blinking in unison, verify that correct power is being
supplied to all modules. A blinking red LED at the rate of once per
second means that software is not loaded on the board. Also, be
sure that the board is supplied with the current software. If
necessary, reload current software. A board LED that is lit
continuously should be replaced.
Green LED
The MBB and ECB each have one green LED. The Local
Equipment Network (LEN) LED should always be blinking
whenever power is on. If LEN LED is not blinking, check LEN
connections for potential communication errors (MBB J3, J4, and
J5). Communication between modules is accomplished by a 3-wire
sensor bus. These 3 wires run in parallel from module to module.
The J4 connector on the MBB also provides both power and
communication directly to the Scrolling Marquee display. The J5
connector on the MBB provides a LEN interface at the field
connection terminal (TB).
Yellow LED
The MBB has one yellow LED which is used to indicate CCN
communication activity. The Carrier Comfort Network (CCN)
LED will blink during times of network communication.
Communication Failures
If the Scrolling Marquee or Navigator display Communication
Failure or the green or yellow LED’s do not flash on the boards
then the problem could be the communication chip on one of the
control boards (MBB or ECB). Disconnect all the LEN and CCN
plugs from the board and use an ohm meter to measure the
resistance on the communication pins of the boards to determine if
the board is bad. If the reading is less than half the value indicated
in Table 13, then the board needs to be replaced.
NOTE: The resistive values should be read when the board is
powered off and the unit is locked out.
Device
MBB
ECB
Board Serial
Number
Prior to 4702N
Starting 4702N
Prior to 0803N
Starting 0803N
Table 13 – LEN and CCN Communication Resistances
(LEN) Resistance between Pins/Connector(CCN) Resistance between Pins/Connector
Pins 1 to 3Pins 1 to 2Pins 2 to 3Pins 5 to 7Pins 5 to 6Pins 6 to 7
15K Ω
J3, J4, & J5
18.9K Ω
J3, J4, & J5
5.9K Ω
J2
18.9K Ω
J2
7.5K Ω
J3, J4, & J5
9.9K Ω
J3, J4, & J5
5.2K Ω
J2
9.9K Ω
J2
7.5K Ω
J3, J4, & J5
9.9K Ω
J3, J4, & J5
5K Ω
J2
9.9K Ω
J2
15K Ω
J5
18.9K Ω
J5
---
---
7.5K Ω
J5
9.9K Ω
J5
7.5K Ω
J5
9.9K Ω
J5
44
Cooling Troubleshooting
Use the Scrolling Marquee display or a CCN device to view the
cooling status display and the cooling diagnostic display (see
Appendix A) for information on the cooling operation. Check the
If alarms conditions are corrected and cleared, operation of the
compressors and fans may be verified by using the Service Test
mode. (See Table 4.) See Table 14 for general cooling service
analysis.
current alarms and alarm history for any cooling alarm codes and
correct any causes. (See Table 12.) Verify any unique control
configurations per installed site requirements or accessories.
Table 14 – Cooling Service Analysis
PROBLEMCAUSEREMEDY
Compressor and Fan Will Not
Start.
Compressor Cycles (other than
normally satisfying thermostat).
Compressor Operates
Continuously.
Excessive Condenser Pressures.
Condenser Fans Not Operating.No Power to contactors.Fuse blown or plug at motor loose.
Excessive Suction Pressure.
Power failure.Call power company.
Fuse blown or circuit breaker tripped. Check CB1,
CB2, and CB3.
Disconnect off.Power disconnect.
Compressor time guard to prevent short cycling.Check using ComfortLinkScrolling Marquee.
Thermostat or occupancy schedule set point not
calling for Cooling.
Outdoor temperature too low.Check Compressor Lockout Temperature using
Active alarm.Check active alarms using ComfortLink Scrolling
Insufficient line voltage.Determine cause and correct.
Active alarm.Check active alarms using ComfortLink Scrolling
Unit undersized for load.Decrease load or increase size of unit.
Thermostat or occupancy schedule set point too low.Reset thermostat or schedule set point.
Dirty air filters.Replace filters.
Low refrigerant charge.Check pressure, locate leak, repair, evacuate, and
Condenser coil dirty or restricted.Clean coil or remove restriction.
Loose condenser thermistors.Tighten thermistors.
Dirty condenser coil.Clean coil.
Refrigerant overcharge.Recover excess refrigerant.
Faulty TXV.1. Check TXV bulb mounting and secure tightly to
Condenser air restricted or air short cycling.Determine cause and correct.
Restriction in liquid tube.Remove restriction.
High heat load.Check for sources and eliminate
Faulty TXV.1. Check TXV bulb mounting and secure tightly to
Refrigerant overcharged.Recover excess refrigerant.
Dirty air filters.Replace air filters.
Low refrigerant charge.Check pressure, locate leak, repair, evacuate, and
Faulty TXV.1. Check TXV bulb mounting and secure tightly to
Insufficient evaporator airflow.Check belt tension. Check for other restrictions.
Temperature too low in conditioned area (low
return‐air temperature).
Replace fuse or reset circuit breaker.
Check using ComfortLink Scrolling Marquee.
ComfortLink Scrolling Marquee.
Marquee.
Marquee.
recharge.
suction line and insulate.
2. Replace TXV (and filter drier) if stuck open or
closed.
suction line and insulate.
2. Replace TXV (and filter drier) if stuck open or
closed.
recharge.
suction line and insulate.
2. Replace TXV (and filter drier) if stuck open or
closed.
Reset thermostat or occupancy schedule.
48/50PG and PM
45
Humidi−MiZert Troubleshooting
Use the unit Scrolling Marquee display or a CCN device to view
the cooling status display and the cooling diagnostic display (see
Appendix A) for information on the cooling operation and the
related Humidi-MiZer operation. Check the current alarms and
alarm history for any cooling alarm codes and correct any causes.
(See Table 12.) Verify any unique control configurations per
installed site requirements or accessories.
Subcooling Reheat Mode
Will Not Activate.
Hot Gas Reheat Mode
Will Not Activate.
48/50PG and PM
No Dehumidification Demand.
CRC Relay Operation.
CV or RH1 Valve Operation.
(NOTE: Normally Open
When De‐energized)
RH2 Valve Operation.
(NOTE: Normally Closed
When De‐energized)
Low Latent Capacity in Subcooling or
Hot Gas Reheat Modes.
Low Sensible Capacity in Normal Cool
or Subcooling Reheat Modes.
Low Suction Pressure and High
Superheat During Normal Cool Mode.
Low Suction Pressure
and High Discharge Pressure.
RH2 Valve Cycling On/Off.
Circuit B or C Will Not Operate With
Circuit A Off.
If alarm conditions are corrected and cleared, operation of the
compressors, fans, and Humidi-MiZer valves may be verified by
using the Service Test mode. (See Table 4.) In addition to general
cooling service analysis (See Table 14), see Table 15 for general
Humidi-MiZer service analysis.
NOTE: Wiring, operation, and charge are different on a
Humidi-MiZer unit compared to a standard unit.
Table 15 – Humidi-MiZer Service Analysis
PROBLEMCAUSEREMEDY
General cooling mode problem.See Cooling Service Analysis (Table 14).
No dehumidification demand.See No Dehumidification Demand, below.
CRC relay operation.See CRC Relay Operation, below.
Circuit RH1 valve is not open.See RH1 Valve Operation, below.
Circuit CV valve is not closed.See CV Valve Operation, below.
General cooling mode problem.See Cooling Service Analysis (Table 14).
No dehumidification demand.See No Dehumidification Demand, below.
CRC relay operation.See CRC Relay Operation, below.
Circuit RH1 valve is not open.See RH1 Valve Operation, below.
Circuit CV valve is not closed.See CV Valve Operation, below.
Circuit RH2 valve is not open.See RH2 Valve Operation, below.
Outdoor temperature too low.
Relative humidity setpoint is
too low — Humidistat
Relative humidity setpoint is
too low — RH sensor.
Software configuration error
for accessory humidistat.
Software configuration error
for accessory humidity sensor.
No humidity signal.Check wiring. Check humidistat or humidity sensor.
No 24V signal to input terminals.
No power to output terminals.Check wiring.
Relay outputs do not change state.Replace faulty relay.
No 24V signal to input terminals.
Solenoid coil burnout.
Stuck valve.Replace valve. Replace filter drier.
No 24V signal to input terminals.
Solenoid coil burnout.
Stuck valve.Replace valve. Replace filter drier.
CV valve open or leaking.See CV Valve Operation, above.
RH2 valve open or leaking.See RH2 Valve Operation, above.
General cooling mode problem.See Cooling Service Analysis (Table 14).
RH2 valve open or leaking.See RH2 Valve Operation, above.
General cooling mode problem.See Cooling Service Analysis (Table 14).
Both RH1 and CV valves closed.See RH1 and CV Valve Operation, above.
Hot Gas Reheat mode low suction pressure limit.
Normal operation. Motormaster outdoor fan con
trol requires operation of circuit A.
Check Reheat2 Circuit Limit Temperatures
(Configuration→HMZR→RA.LO and RB.LO)
using ComfortLink Scrolling Marquee.
Check/reduce setting on accessory humidistat.
Check Space RH Setpoints (Setpoints→RH.SP and RH.UN) and
occupancy using ComfortLink Scrolling Marquee.
Check Space Humidity Switch (Configuration→
UNIT→RH.SW) using ComfortLink Scrolling Marquee.
Check RH Sensor on OAQ Input (Configuration→
UNIT→RH.S) using ComfortLink Scrolling Marquee.
Check using Cool→Reheat1 Valve Test (Service Test→HMZR→CRC)
using ComfortLink Scrolling Marquee.
Check using Cool→Reheat1 Valve Test (Service Test→HMZR→CRC)
using ComfortLink Scrolling Marquee.
Check CRC Relay Operation.
Check Wiring.
Check transformer and circuit beaker or fuses.
Check continuous over‐voltage is less than 10%.
Check under‐voltage is less than 15%.
Check for missing coil assembly parts.
Check for damaged valve enclosing tube.
Check using Cool→Reheat1 Valve Test (Service Test→HMZR→RHV.A or
RHV.B) using ComfortLink Scrolling Marquee.
Check MBB relay output.
Check wiring.
Check transformer and circuit breaker or fuses.
Check continuous over‐voltage is less than 10%.
Check under‐voltage is less than 15%.
Check for missing coil assembly parts.
Check for damaged valve enclosing tube.
Normal Operation During Mixed Circuit Subcooling and Hot Gas Reheat
Modes at Lower Outdoor Temperatures.
None
46
Economizer Troubleshooting
Use the unit Scrolling Marquee display or a CCN device to view
the economizer status display and the economizer diagnostic
display (see Appendix A) for information on the economizer
operation. Check the current alarms and alarm history for any
economizer alarm codes and correct any causes. (See Table 12.)
Verify any unique control configurations per installed site
requirements or accessories. If alarms conditions are corrected and
cleared, operation of the economizer may be verified by using the
Service Test mode (see Service Test section and Table 4). The
following steps specify how to test the economizer using the
Scrolling Marquee display. See Table 16 for general economizer
service analysis.
1. Enter the Service Test main menu on the display.
2. Enter TEST and turn ON test mode. A password may be
needed in order to turn ON the Service Test. The default
password is 1111.
3. Return to the main level of Service Test.
4. Enter the INDP submenu and enter an initial value for
ECON. This will drive the economizer damper to the
specified position. Continue to adjust the ECON value to
make sure the economizer opens and closes.
Table 16 – Economizer Service Analysis
PROBLEMPOSSIBLE CAUSEREMEDY
Damper Does Not Move.Indoor Fan is off.
Actuator is unplugged at motor or at
economizer board.
Unit is not configured for economizer.Configure unit for economizer per the
Outdoor‐air temperature is above economizer
high temperature lockout.
Outdoor‐air temperature is below economizer low
temperature lockout.
Communication loss to economizer board.Check wiring connections.
Damper is jammed.Identify the obstruction and safely remove.
Economizer Operation is Limited
to Minimum Position.
Economizer Position is Less
Than Minimum Position.
Economizer Does Not Return
to Minimum Position.
Damper Does Not Close on
Power Loss.
Outdoor Damper Does Not Fully
Close at 0% or Fully Open at 100%.
Economizer is Not at Configured
Minimum Position
LEGEND
CCN - Carrier Comfort Network
IAQ- Indoor Air Quality
Minimum position is set incorrectly.Adjust minimum position setting.
Outdoor‐air temperature is above economizer
high temperature lockout.
Outdoor‐air temperature is below economizer
low temperature lockout.
Enthalpy or differential dry bulb are preventing free
cooling.
Outdoor‐air thermistor is faulty.Replace outdoor‐air thermistor.
Low suction pressure problem with a compressor.Economizer is operating correctly, identify
IAQ is controlling minimum damper position.Adjust the IAQ settings if incorrect,
Unit is in Unoccupied mode.Adjust unit occupied schedule if incorrect,
Unit is operating under free cooling.Economizer is operating correctly.
Damper is jammed or spring return is backwards.Identify the obstruction and safely remove.
Economizer actuator is out of calibration or spring
return is backwards.
Unit is operating under free cooling or a force is
applied to the commanded position.
5. Because of a mechanical problem with the economizer, the
actuator might acquire a new degree of rotation which is
less than M.ANG. If this occurs, a “T414 Economizer
Damper Actuator Out of Calibration” alert will be
generated. This alert can only occur if the economizer is
using digital communications (Configuration→ECON→E.CTL = 1 or 2). The economizer calibration
procedure (Service Test→IND.P→E.CAL) will reconfigure
the actuator to the new fully closed and fully open
positions. To implement the calibration procedure, change
E.CAL from OFF to ON. E.CAL will remain ON as long as
the calibration procedure is being implemented (as long as 5
minutes). During the calibration procedure the actuator will
close fully and then open fully. After the calibration is
complete, the degree of rotation should be greater than
M.ANG, causing the T414 alert to clear. If the T414 alert
does not clear, check the economizer damper for other
mechanical problems.
6. Return to Service Test→TEST and turn OFF test mode.
This will cause the unit to return to normal operation.
Check for proper thermostat connection.
Unit is not configured for continuous fan
operation and the thermostat is not calling for
heating or cooling.
Unit is in Unoccupied mode and there is no
call for heating or cooling.
Tripped circuit breaker.
No power to the unit.
Unit is off via CCN command.
Check wiring connections.
instructions.
Adjust the high temperature lockout setting
if it is incorrect, otherwise, economizer is
operating correctly.
Adjust the low temperature lockout setting
if it is incorrect, otherwise, economizer is
operating correctly.
Adjust the high temperature lockout setting
if it is incorrect, otherwise, economizer is
operating correctly.
Adjust the low temperature lockout setting if it is
incorrect, otherwise, economizer is operating
correctly.
Check enthalpy and return air compared to
outside air temperature.
compressor problem.
otherwise, the economizer is operating correctly.
otherwise, economizer is operating correctly.
Enter Service Test mode and run the Calibrate
Economizer (E.CAL) procedure.
Economizer is operating correctly.
48/50PG and PM
47
Heating Troubleshooting
Use the unit Scrolling Marquee display or a CCN device to view
the heating status display and the heating diagnostic display (see
Appendix A) for information on the heating operation. Check the
current alarms and alarm history for any heating alarm codes and
correct any causes. (See Table 12.) Verify any unique control
configurations per installed site requirements or accessories. If
alarms conditions are corrected and cleared, operation of the heat
stages and indoor fan may be verified by using the Service Test
mode. (See Table 4.)
PROBLEMCAUSEREMEDY
Heat Will Not Turn On.
Burners Will Not Ignite.
48/50PG and PM
Inadequate Heating.
Poor Flame
Characteristics.
Burners Will Not Turn Off.
Gas Heat (48PG Units)
See Table 17 for general gas heating service analysis. See Fig. 21
for service analysis of the IGC board logic. Check the status LED
on the IGC board for any flashing alarm codes and correct any
causes. (See Table 18.)
Electric Heat (50PG Units)
See Table 19 for electric heating service analysis.
Table 17 – Gas Heating Service Analysis
Unit is NOT configured for heat.Check heating configurations using the ComfortLink Scrolling
Active alarm.Check active alarms using ComfortLink Scrolling Marquee
No power to unit.Check power supply, fuses, wiring, and circuit breakers.
No power to IGC (Integrated Gas Control).Check fuses and plugs.
Heaters off due to time guard to prevent short
cycling.
Thermostat or occupancy schedule set point not
calling for Cooling.
No gas at main burners.Check gas line for air and purge as necessary. After purging gas
Water in gas line.Drain water and install drip.
Dirty air filters.Replace air filters.
Gas input too low.Check gas pressure at manifold. Refer to gas valve adjustment.
Thermostat or occupancy schedule set point only
calling for W1.
Unit undersized for load.Decrease load or increase of size of unit.
Restricted airflow.Remove restriction. Check SAT compared to the SAT heating
Too much outdoor air.Check economizer position and configuration. Adjust minimum
Limit switch cycles main burners.Check rotation of blower, thermostat heat anticipator settings,
Incomplete combustion (lack of combustion air)
results in: Aldehyde odors, CO, sooting flame, or
floating flame.
Unit is in Minimum on‐time.Check using ComfortLink Scrolling Marquee and the IGC flash
Unit running in Service Test mode.Check using ComfortLink Scrolling Marquee.
Main gas valve stuck.Turn off gas supply and unit power. Replace gas valve.
Marquee
and the IGC flash codes.
Check using ComfortLink Scrolling Marquee and the IGC flash
codes.
Check using ComfortLink Scrolling Marquee.
line of air, allow gas to dissipate for at least 5 minutes before
attempting to re‐light unit.
Allow time for W2 to energize or adjust setpoints.
limits.
position using ComfortLink Scrolling Marquee.
and temperature rise of unit. Adjust as needed.
Check all screws around flue outlets and burner compartment.
Tighten as necessary.
Cracked heat exchanger, replace.
Unit is over‐fired, reduce input. Adjust gas line or manifold
pressure.
Check vent for restriction. Clean as necessary.
Check orifice to burner alignment.
codes.
48
48/50PG and PM
LEGEND
IDM -- Induced-Draft Motor
IGC -- Integrated Gas Unit Controller
NOTE: Thermostat Fan Switch in the
“AUTO” position.
C07014
Fig. 21 − IGC Service Analysis Logic
49
LED
FLASH
CODE
OnNormal Operation
OffHardware FailureNo gas heating.
1 FlashIndoor Fan On/Off Delay
2 Flashes Limit Switch FaultGas valve and igniter Off.
3 Flashes Flame Sense FaultIndoor fan and inducer On. Flame sense normal.
4 Flashes Four Consecutive Limit
5 Flashes Ignition FaultNo gas heating.Heat call (W) Off.
48/50PG and PM
6 Flashes Induced Draft Motor
7 Flashes Rollout Switch LockoutGas valve and igniter Off.
8 Flashes Internal Control Lockout No gas heating.Power reset.IGC has sensed internal hardware or software error. If
9 Flashes Temporary Software
LEGEND
IGC - Integrated Gas Unit Control
LED - Light-Emitting Diode
DESCRIPTION
Modified
Switch Fault
Fault
Lockout
Table 18 – IGC Board LED Alarm Codes
ACTION TAKEN BY
CONTROL
———
5 seconds subtracted from
On delay.
5 seconds added to Off
delay (3 min max).
Indoor fan and inducer On.
No gas heating.Heat call (W) Off.
If heat off: no gas heating.
If heat on: gas valve Off
and inducer On.
Indoor fan and inducer On.
No gas heating.1 hour auto reset, or
RESET METHODPROBABLE CAUSE
—
Power reset.High temperature limit switch opens during heat
Limit switch closed, or
heat call (W) Off.
Power reset for LED
reset.
Power reset for LED
reset.
Power reset for LED
reset.
Inducer sense normal, or
heat call (W) Off.
Power reset.Rollout switch has opened. Check gas valve
power reset.
NOTES:
1. There is a 3-second pause between alarm code displays.
2. If more than one alarm code exists, all applicable alarm codes will be
displayed in numerical sequence.
3. Alarm codes on the IGC will be lost if power to the unit is interrupted.
Loss of power to the IGC. Check 5 amp fuse on IGC,
power to unit, 24V circuit breaker, transformer, and
wiring to the IGC.
exchanger warm‐up period before fan‐on delay
expires.
High temperature limit switch opens within
10 minutes of heat call (W) Off.
See Limit Switch Fault.
High temperature limit switch is open. Check the
operation of the indoor (evaporator) fan motor.
Ensure that the supply‐air temperature rise is within
the range on the unit nameplate. Check wiring and
limit switch operation.
The IGC sensed a flame when the gas valve should
be closed. Check wiring, flame sensor, and gas valve
operation.
4 consecutive limit switch faults within a single call for
heat. See Limit Switch Fault.
Unit unsuccessfully attempted ignition for 15 minutes.
Check igniter and flame sensor electrode spacing, gaps,
etc. Check flame sense and igniter wiring. Check gas
valve operation and gas supply.
Inducer sense On when heat call Off, or inducer
sense Off when heat call On. Check wiring, voltage,
and operation of IGC motor. Check speed sensor
wiring to IGC.
operation. Check induced‐draft blower wheel is
properly secured to motor shaft.
fault is not cleared by resetting 24 v power, replace
the IGC.
Electrical interference is disrupting the IGC software.
PROBLEMCAUSEREMEDY
Heat Will Not Turn On.
Inadequate Heating.
Heat Will Not Turn Off.
Table 19 – Electric Heat Service Analysis
Active alarm.Check active alarms using ComfortLink Scrolling
Unit is NOT configured for heat.Check heating configurations using the ComfortLink
No power to unit.Check power supply, fuses, wiring, and circuit breakers.
Unit is in minimum heat off‐time, or minimum cool‐heat
changeover time.
Thermostat or occupancy schedule setpoint not
calling for heating.
Heat forced off in Service Test mode.Check using ComfortLink Scrolling Marquee. Turn Service
No 24 vac at heater contactor.
Open temperature limit switch on heater.Check minimum airflow. Check limit switch when it is cool,
Dirty air filters.Replace air filters.
Thermostat or occupancy schedule setpoint only
calling for W1.
Heat undersized for load.Decrease load or increase size of heater.
Restricted airflowRemove restriction. Check SAT compared to the SAT
Too much outdoor air.Check economizer position and configuration. Adjust
Limit switch cycles heaters.Check rotation of blower and minimum airflow.
Bad heater elements.Power off unit and remove high voltage wires. Check
Unit is in minimum heat on‐time.Check using ComfortLink Scrolling Marquee.
Thermostat or occupancy schedule setpoint still
calling for heating.
Heat forced on in Service Test mode.Check using ComfortLink Scrolling Marquee. Turn Service
Heater contactor failed.Power off unit. Check contactor and replace if closed.
Marquee.
Scrolling Marquee
Check using ComfortLink Scrolling Marquee.
Check using ComfortLink Scrolling Marquee.
Test mode off.
Check transformer and circuit breaker.
Check auto‐reset limit switches on heater.
Check manual‐reset limit switch (LS) on indoor fan housing.
replace if open.
Allow time for W2 to energize or adjust setpoints.
heating limits.
minimum position.
resistance of element, replace if open.
Check using ComfortLink Scrolling Marquee.
Test mode off.
50
Phase Loss Protection
The phase loss protection option will monitor the three-phase
electrical system to provide phase reversal and phase loss
protection.
Phase Reversal Protection
If the control senses an incorrect phase relationship, the relay (K1)
will be de-energized (opening its contact). If the phase relationship
is correct, the relay will be energized. The control has a self-bypass
function after a pre-set time. If the control determines that the three
phases stay in a correct relationship for 10 consecutive minutes, the
relay will stay energized regardless of the phase sequence of three
inputs as long as 24-vac control voltage is applied. This self-bypass
function will be reset if all three phases are restored in a phase loss
event.
Phase Loss Protection
If the reverse rotation board senses any one of the three phase
inputs has no AC voltage, the relay will be de−energized (opening
its contact). This protection is always active as long as 24-vac
control voltage is applied, and is not affected by the self by-pass
function of the phase sequence monitoring function. However, in
the event of phase loss, the relay will be re-energized only if all
three phases are restored and the three phases are in the correct
sequence.
A red LED is provided to indicate the function of the board. See
the table below.
LED STATUSFUNCTION
On ContinuouslyRelay contact closed (normal operation).
Blinking
Off24 vac control power not present (off).
Relay contact open (phase loss or phase
reversal has occurred) — No power will be
supplied to the control system.
Thermistor Troubleshooting
The electronic control uses thermistors to sense temperatures used
to control operation of the unit. Resistances at various temperatures
are listed in Table 20 and 21. Thermistor pin connection points are
shown in the Major System Components section. The general
locations of the thermistors are shown the Major System
Components section.
Air Temperatures
Air temperatures are measured with 10 kilo-ohm thermistors. This
includes supply-air temperature (SAT), outdoor-air temperature
(OAT), space temperature sensors (T55, T56, T58), and return air
temperature (RAT).
The supply air temperature (SAT) and outdoor air temperature
(OAT) thermistors use a snap-mount to attach through the unit
sheet metal panels. The snap-mount tabs must be flattened on the
tip end of the sensor to release for removal from the panel. (See
Fig. 22.) To reinstall, make sure the snap-mount tabs extend out.
Refrigerant Temperatures
Condenser coil temperatures are measured with 5 kilo-ohm
thermistors. These measurements provide an approximate saturated
condensing temperature for each circuit (SCT.A, SCT.B, SCT.C).
Fig. 23−24 show the factory locations for the SCT thermistors on
48/50PG03−16 units. On 48/50PG20−28 and 48/50PM16−28
units the location is on the component arrangement diagrams.
Ensure that thermistors are placed at the correct location and are
snapped securely over the return bend so that contact is made
between the thermistor and the tube.
48/50PG and PM
C07015
Fig. 22 − SAT and OAT Thermistor Mounting
Thermistor/Temperature Sensor Check
A high quality digital volt-ohmmeter is required to perform this
check.
Connect the digital voltmeter across the appropriate thermistor
terminals at the J8 terminal strip on the Main Base Board (see
Major System Components section).
Using the voltage reading obtained, read the sensor temperature
from Table 20 and 21.
To check thermistor accuracy, measure temperature at
probe location with an accurate thermocouple-type
temperature-measuring instrument. Insulate thermocouple to avoid
ambient temperatures from influencing reading. Temperature
measured by thermocouple and temperature determined from
thermistor voltage reading should be close, within 5°F if care was
taken in applying thermocouple and taking readings.
If a more accurate check is required, unit must be shut down and
thermistor removed and checked at a known temperature (freezing
point or boiling point of water) using either voltage drop measured
across thermistor at the J8 terminal, or by determining the
resistance with unit shut down and thermistor disconnected from
J8. Compare the values determined with the value read by the
control in the Temperatures mode using the Scrolling Marquee
display.
51
SCT.A
MOTORMASTER
SENSOR
(3rd return bend
down from top)
MOTORMASTER
SENSOR
(bottom stub
of outside header)
SCT.A
48/50PG and PM
THERMISTOR
LOCATION
(SCT.B)
Sensor Trim
Corrective offsets can be applied to the space temperature and the
supply air temperature sensor readings. These corrections are set in
the Configuration→TRIM menu for the display, or in the
Maintenance→TRIM table for CCN. See the Indoor Air Quality
section for available adjustments to IAQ and OAQ sensor readings.
The space temperature may be corrected by entering either a
calibration temperature value in SPT.C, or an offset temperature
value in SPT.T. The supply-air temperature may be corrected by
entering either a calibration temperature value in SAT.C, or an
offset temperature value in SAT.T. Temperature corrections should
only be made if sensor readings are compared to an accurate
reference temperature measurement device.
Transducer Troubleshooting
The electronic control uses suction pressure transducers to measure
the suction pressure of the refrigerant circuits. The pressure/voltage
characteristics of these transducers are in shown in Table 22, the
5vdc power is applied to legs A and B of the transducer and legs B
to C represent the signal voltage. To use the voltage drop table for
troubleshooting, read the voltage across A and B, then subtract the
voltage reading from B to C. This is the voltage drop which can be
48/50PG03,04
48/50PG03-07
Fig. 23 − Saturated Condensing Temperature Thermistor Location — 48/50PG03−07
THERMISTOR
LOCATION
(SCT.B)
THERMISTOR
LOCATION
(SCT.A)
MOTORMASTER
SENSOR
(2nd stub from bottom
of outside header)
48/50PG08-12
48/50PG14
Fig. 24 − Saturated Condensing Temperature Thermistor Location — 48/50PG08−14
looked up in table 22. The accuracy of these transducers can be
verified by connecting an accurate pressure gauge to the second
refrigerant port in the suction line.
Forcing Inputs and Outputs
Many variables may have their value forced through CCN or
directly at the local display. This can be useful during diagnostic
testing and also during operation, typically as part of an advanced
third party control scheme. Input and output points that may be
forced are indicated as ‘forcible’ in the write status column of the
display and CCN tables.
If the user needs to force a variable, follow the same process as
when editing a configuration parameter. A forced variable will be
displayed on the Scrolling Marquee with a blinking period “.”
following its value. A forced value on Navigator accessory is
indicated with a blinking “f”. A forced value on CCN devices is
indicated with “Control” if forced at the unit display, or
“Supervisor” if forced via CCN. To remove a local force with the
Scrolling Marquee, select the point with the ENTER key and then
press the up-arrow and down-arrow keys simultaneously.
NOTE: In the case of a control power reset, any force in effect at
the time of power reset will be cleared.
THERMISTOR
LOCATION
(SCT.A)
MOTORMASTER
SENSOR
(4th stub from bottom
of outside header)
C09347
C09348
52
Table 20 – Temperature (_F) vs Resistance/Voltage Drop Values for
OAT, SAT, and SPT Thermistors (10K at 25_C Type II Resistors)
The 48/50PG and 48/50PM single package rooftop units contain
the ComfortLink electronic control system that monitors all
operations of the rooftop. The control system is composed of
several main control components and available factoryinstalled options or field-installed accessories as listed in
sections below. See Fig. 25−36 for the control and power
schematics for 48/50PG. See Fig. 31−36 for the control and power
schematics for 48/50PM. Fig. 37 shows the layout of the control
box, unit, and thermistor and transducer locations for the 48/50PG
and Fig. 38−39 for the 48/50PM.
55
48/50PG and PM
C08549
Fig. 25 − 48PG03−16 Control Wiring Schematic
56
48/50PG and PM
C08550
Fig. 26 − 50PG03−16 Control Wiring Schematic
57
48/50PG and PM
Fig. 27 − Typical 48/50PG03−14 Power Wiring Schematic and Legend (48/50PG08−14 Shown)
C101249
58
48/50PG and PM
Fig. 28 − Typical 48PG03−16 with Humidi−MiZert System Control Wiring Schematic(48PG08−16 Shown)
C08552
59
48/50PG and PM
Fig. 29 − Typical 50PG03−16 with Humidi−MiZert System Control Wiring Schematic(50PG08−16 Shown)
C08554
60
48/50PG and PM
Fig. 30 − Typical 48/50PG03−14 with Humidi−MiZert System Power Wiring Schematic and Legend
C101250
(48/50PG08−14 Shown)
61
48/50PG and PM
C08471
Fig. 31 − Typical 48PM16−28 Control Schematic
62
48/50PG and PM
Fig. 32 − Typical 48PM16−28 with Humidi−MiZert System Control Schematic
C08062
63
48/50PG and PM
C101251
Fig. 33 − Typical 50PM16−28 Control Schematic
64
48/50PG and PM
Fig. 34 − Typical 50PM16−28 with Humidi−MiZert Control Schematic
C08064
65
48/50PG and PM
C10902
Fig. 35 − Typical 48/50PM16−28 Power Schematic
66
48/50PG and PM
Fig. 36 − Typical 48/50PM16−28 with Humidi−MiZert System Power Schematic
Fig. 39 − 48/50PM16−28 with Humidi−MiZert Component Arrangement
C101252
70
Main Base Board (MBB)
See Fig. 40 and Table 23. The MBB is the center of the
ComfortLink control system. It contains the major portion of the
operating software and controls the operation of the unit. The
MBB continuously monitors input/output channel information
received from its inputs and from the Economizer Control Board
(ECB). The MBB receives inputs from thermistors and transducers.
The MBB also receives the Current Sensor inputs for compressors
and other discrete or digital inputs. The MBB reads space
temperature (SPT) from either a T-55, T-56 or T-58 device and
space temperature offset (SPTO) from a T-56 device. See
Field-Installed Accessories section. The MBB controls 9 relays.
NOTE: The Main Base Board (MBB) has a 3-position instance
jumper that is factory set to ‘1.’ Do not change this setting.
RED LED - STATUSGREEN LED -
LEN (LOCAL EQUIPMENT NETWORK)
CEPL130346-01
J1
J6
J4
J5
J2
J3
LEN
CCN
STATUS
YELLOW LED CCN (CARRIER COMFORT NETWORK)
INSTANCE JUMPER (SET TO 1)
J10
48/50PG and PM
J7
J8
Fig. 40 − Main Base Board (MBB)
J9
C07026
71
Table 23 – MBB Connections
DISPLAY
NAME
Input power from TRAN1control box24 VACJ1, 1-3
HUM
FDWNFire shutdown switchsupply/return/spaceswitch inputJ6, 6
GThermostat G (Fan)spaceswitch inputJ7, 2
W2Thermostat W2 (2nd Stage Heat)spaceswitch inputJ7, 4
W1Thermostat W1 (1st Stage Heat)spaceswitch inputJ7, 6
Y2Thermostat Y2 (2nd Stage Cool)spaceswitch inputJ7, 8
Y1Thermostat Y1 (1st Stage Cool)spaceswitch inputJ7, 10
FIL.SFilter status switchindoor fan sectionswitch inputJ9, 2-3
CS.A1Compressor A1 Current Sensorcontrol box0-5vdc digital inputJ9, 4-6
CS.B1 or
CS.A2
CS.C1 or
CS.B1
SPTSpace temperature (T55/56)space10k thermistorJ8, 1-2
SPTO or
RAT
48/50PG and PM
OATOutdoor air temperatureoutdoor coil support10k thermistorJ8, 5-6
The ECB controls the economizer actuator. (See Fig. 41 and Table
24.) The control signal from the ECB uses either the MFT
(Multi-Function Technology) digital communication protocol or a
4 to 20 mA output signal as defined by the configuration
Configuration→ECON→E.CTL. The ECB has inputs for
Indoor Air Quality (IAQ), Outdoor Air Quality (OAQ), enthalpy
and RH sensor. It also controls two power exhaust outputs.
By digitally communicating with the ECB, the economizer
actuator is able to provide the damper position and diagnostic
information to the ComfortLink controller. The damper
position is displayed at Outputs→ECON→EC.AP. Diagnostic
information is displayed via Alert T414. More information about
these alarms is contained in the Alarms and Alerts section.
NOTE: The Economizer Control Board (ECB) has a
4-position DIP switch that is factory set to ‘0’ (ON, towards the
center of the board). Do not change this setting.
48/50PG and PM
C07027
Fig. 41 − Economizer Control Board (ECB)
73
Table 24 – ECB Connections
DISPLAY
NAME
Input power from MBBcontrol box24 VACJ1, 1-2
RM.OCRemote occupancy switchfield installedswitch inputJ4, 2
ENTH or
IAQ.S
IAQIndoor air quality sensorreturn/space0-20 mAJ5, 2
OAQ or
Output power to enthalpy switch24 VACJ4, 3
Output power for loop power sensors24 VDCJ5, 1
Output power to economizer actuator24 VACJ7, 2
PE.1Power exhaust 1 relayrelayJ8, 3
PE.2Power exhaust 2 relayrelayJ8, 6
EC.CP or
Outdoor enthalpy switch, or
Indoor air quality switch
Outdoor air quality sensor, or
Relative humidity sensor
Commanded Economizer position or
Commanded Fan Speed
Economizer actuator position
(digital control)
LOCATION
INPUTS
economizer, or
return/space
field installed0-20 mAJ5, 5
OUTPUTS
COMMUNICATION
TYPE OF I/OCONNECTION
switch inputJ4, 4
0-20 mAJ9, 1
MFT
communication
PIN NUMBER
J7, 1
74
Integrated Gas Control (IGC) Board
The IGC is provided on gas heat units. (See Fig. 42 and Table 25.)
The IGC controls the direct spark ignition system and monitors the
rollout switch, limit switch, and induced-draft motor Hall Effect
switch.
RED LED-STATUS
The IGC is equipped with an LED (light-emitting diode) for
diagnostics. See the Troubleshooting section for more information.
(TB1 on PG03−16 size and TB2 on PG20−28 and
PM16−28 size units)
This circuit board provides a connection point between the major
control boards and a majority of the field-installed accessories. (See
Fig. 43 and Table 26.)
17
J10
SEPARATION OF CIRCUITS TO EACH 24V TRANSFORMER MUST BE MAINTAINED
12345678910 R Y1 Y2
14
J11
W2 G CX1212312
W1
Fig. 43 − Low−Voltage Terminal Strip
The circuit breakers for the low voltage control transformers,
interface connection for the Carrier Comfort Network (CCN)
communication, and interface connection for the Local Equipment
Network (LEN) communications are also located on the low
voltage terminal strip.
J13
7
RUN TEST
FIRE SHUTDOWN
7
J12
T55
FAN STA TUS
8
(COM)
(+)
LEN
CCN
(-)
SHIELD
CCN
C07029
48HG500382
48/50PG and PM
TERMINAL LABEL
FIRE SHUTDOWN
HUMIDISTAT 1*
FIRE SHUTDOWN
HUMIDISTAT 2*
FAN STATUS
* Refer to Third Party Control section for more information
SPTSpace temperature (T55/56)space10k thermistorJ12, 4-5
SPTO or
RAT
NOT USEDJ12, 1-2
POINT DESCRIPTION
Outdoor air quality sensor or
Relative humidity sensor
Outdoor enthalpy switch, or
Indoor air quality switch
Economizer commanded position actu
ator (when in digital control)
Economizer position feedback (when in
analog control)
Fire shutdown switch 24 VAC output
or
Humidistat switch input
Fire shutdown switch input
or
Humidistat switch 24 VAC output
Space temperature offset (T56) or
Return air temperature
SENSOR
LOCATION
field installed4-20 mA inputJ10, 14
economizer, or
return/space
economizer2-10 VDC outputJ10, 6-8
economizer
supply/return/
space
supply/return/
space
space or return10k thermistorJ12, 3-4
TYPE OF I/O
24 VAC inputJ10, 9-10
communication
2-10 VDC output
switch inputJ12, 7
switch inputJ12, 6
CONNECTION
PIN NUMBER
J10, 1-2
76
Scrolling Marquee Display
This device is the keypad interface used to access rooftop
information, read sensor values, and test the unit. (See Fig. 44.)
The Scrolling Marquee display is a 4-key, 4-character, 16-segment
LED (light-emitting diode) display. Eleven mode LEDs are located
on the display as well as an Alarm Status LED. See Basic Control
Usage section for further details.
Accessory Navigatort Display
The accessory hand-held Navigator display can be used with
48/50PG and PM units. (See Fig. 45.) The Navigator display
operates the same way as the Scrolling Marquee device. The
Navigator display plugs into the LEN port on either TB or the
ECB board.
MODE
Run Status
Service Test
Temperature
Pressures
Setpoints
Inputs
Outputs
Configuration
Time Clock
Operating Modes
Alarms
Fig. 45 − Accessory Navigatort Display
Alarm Status
ESCAPE
ENTER
Fig. 44 − Scrolling Marquee
C
o
m
N
A
T
IM
E
E
1
W
2
T
L
W
5
4
T
S
4
E
4
T
P
4
4
.
M
O
D
E
Ala
rm
Ru
n Sta
tu
s
S
e
rv
ice
Te
s
t
T
em
p
era
ture
s
P
res
s
ure
s
S
e
tpo
in
ts
In
pu
ts
O
utp
uts
C
on
fig
u
ra
tion
T
im
e C
lo
ck
E
O
S
p
er
C
ating
M
od
es
A
la
rm
s
E
N
T
E
R
C06320
f
o
r
t L
in
V
I
k
G
A
T
O
R
.
5
8
.
6
°
F
.1
°
F
0
°
F
Sta
tus
C06321
Carrier Comfort Network (CCN)R Interface
The units can be connected to the CCN if desired. The
communication bus wiring is a shielded, 3-conductor cable with
drain wire and is field supplied and installed. The system elements
are connected to the communication bus in a daisy chain
arrangement. (See Fig. 46.) The positive pin of each system
element communication connector must be wired to the positive
pins of the system elements on either side of it. This is also
required for the negative and signal ground pins of each system
element. Wiring connections for CCN should be made at TB. (See
Fig. 18.) Consult the CCN Contractor’s Manual for further
information.
NOTE: Conductors and drain wire must be 20 AWG (American
Wire Gauge) minimum stranded, tinned copper. Individual
conductors must be insulated with PVC, PVC/nylon, vinyl, Teflon,
or polyethylene. An aluminum/polyester 100% foil shield and an
outer jacket of PVC, PVC/nylon, chrome vinyl, or Teflon with a
minimum operating temperature range of –20C to 60C is
required. See Table below for acceptable wiring.
MANUFACTURERPART NO.
Alpha2413 or 5463
Belden8772
CarolC2528
West Penn302
It is important when connecting to a CCN communication bus that
a color-coding scheme be used for the entire network to simplify
the installation. It is recommended that red be used for the signal
positive, black for the signal negative and white for the signal
ground. Use a similar scheme for cables containing different
colored wires.
At each system element, the shields of its communication bus
cables must be tied together. The shield screw on TB1 can be used
to tie the cables together. If the communication bus is entirely
within one building, the resulting continuous shield must be
connected to a ground at one point only. The shield screw on TB1
is not acceptable for grounding. If the communication bus cable
exits from one building and enters another, the shields must be
connected to grounds at the lightning suppressor in each building
where the cable enters or exits the building (one point per building
only). To connect the unit to the network:
1. Turn off power to the control box.
2. Cut the CCN wire and strip the ends of the red (+), white
(ground), and black (–) conductors. (Substitute appropriate
colors for different colored cables.)
3. Connect the red wire to (+) terminal on TB1, the white wire
to COM terminal, and the black wire to the (–) terminal.
4. The RJ14 CCN connector on TB1 can also be used, but is
only intended for temporary connection (for example, a
laptop computer running Carrier network software).
5. Restore power to unit.
IMPORTANT: A shorted CCN bus cable will prevent some
routines from running and may prevent the unit from starting. If
abnormal conditions occur, unplug the connector. If conditions
return to normal, check the CCN connector and cable. Run new
cable if necessary. A short in one section of the bus can cause
problems with all system elements on the bus.
48/50PG and PM
77
CCN BUS
48/50PG and PM
REMOTE
CCN SITE
BUILDING SUPERVISOR
NETWORK
OPTIONS
AUTODIAL
GATEWAY
TERMINAL
SYSTEM
MANAGER
CL
CL
ROOFTOP
UNIT
ROOFTOP
UNIT
CL
ROOFTOP
UNIT
HEATING/COOLING UNITS
TCU
DAV AIR
TERMINAL
TCU
DAV AIR
TERMINAL
CL
CL
ROOFTOP
UNIT
ROOFTOP
UNIT
TCU
CCN -- Carrier Comfort Networkr
LEGEND
CL -- ComfortLinkt Controls
DAV -- Digital Air Volume
HVAC -- Heating, Ventilation, and
Air Conditoning
TCU -- Terminal Control Unit
TO
ADDITIONAL
TERMINALS
DAV FAN
POWERED
MIXING
BOX
NON CARRIER
HVAC
EQUIPMENT
COMFORT
CONTROLLER
AIR DISTRIBUTION-DIGITAL AIR VOLUME CONTROL (DAV)
Fig. 46 − CCN System Architecture
EnergyX
Units equipped with Optional EnergyX have a factory installed
energy recovery ventilator (ERV). The ERV is used to
pre−condition outside air as it is brought into the rooftop unit. To
do this it uses building air and an enthalpy wheel. It can also have
a wheel bypass that acts as an economizer to allow free cooling. In
Appendix A there are ERV points for display under Outside Air
Unit (OAU) menus. These points and ERV specifics are explained
in the EnergyXv2 Supplement Installation Instructions contained
in the unit’s information packet.
C07030
78
Field-Installed Accessories
Space Temperature Sensor (T−55)
The T-55 space temperature sensor (part no. 33ZCT55SPT) is a
field-installed accessory. The sensor is installed on a building
interior wall to measure room air temperature. The T-55 sensor also
includes an override button on the front cover to permit occupants
to override the Unoccupied Schedule (if programmed). The jumper
wire in the installer’s packet must be connected between R and W1
when using a T-55 device.
TB−T55−1Sensor Input.......
TB−T55−2Sensor Common.......
Space Temperature Sensor (T−56)
The T-56 space temperature sensor (part no. 33ZCT56SPT) is a
field-installed accessory. This sensor includes a sliding scale on the
front cover that permits an occupant to adjust the space temperature
set point remotely. The T-56 sensor also includes an override
button on the front cover to allow occupants to override the
unoccupied schedule (if programmed). The jumper wire in the
installer’s packet must be connected between R and W1 when
using a T-56 device.
TB−T55−1Sensor Input.......
TB−T55−2Sensor Common.......
TB−T55−3Setpoint Offset Input.......
Space Temperature Sensor (T−58)
The T-58 space temperature sensor (part no. 33ZCT58SPT) is a
field-installed accessory. The T-58 sensor communicates with the
ComfortLink controller, providing space temperature, heating
and cooling set points, and mode operation information. The
jumper wire in the installer’s packet must be connected between R
and W1 when using a T-58 device.
Refer to the T-58 installation instructions for information on
installing and configuring the T-58 sensor.
Each T-58 sensor must have a unique address on the CCN. Each
T-58 sensor must also be configured with the address of the unit
control it is communicating to.
Space Temperature Sensor Averaging
See Fig. 47 for space temperature averaging with T-55 sensors
only. If the use of one T-56 sensor is required, refer to Fig. 48.
48/50PG and PM
79
RED
T
BLK
RED
BLK
48/50PG and PM
LEGEND
B -- Terminal Block
______ -- Factory Wiring
_ _ _ _ -- Field Wiring
TB1-T55
1
2
TO MAIN
BASE BOARD
TB1-T55
1
2
TO MAIN
BASE BOARD
RED
BLK
SENSOR 1SENSOR 2SENSOR 3SENSOR 4
RED
BLK
RED
BLK
SPACE TEMPERATURE AVERAGING --4 T-55 SENSOR APPLICATION
RED
BLK
BLK
SENSOR 1
RED
RED
BLK
SENSOR 2
RED
BLK
RED
BLK
RED
BLK
SENSOR 3
SENSOR 6SENSOR 5
BLK
SENSOR 4
RED
RED
BLK
RED
BLK
SENSOR 8SENSOR 7SENSOR 9
SPACE TEMPERATURE AVERAGING --9 T-55 SENSOR APPLICATION
Fig. 48 − Space Temperature Sensor Averaging with 3 T−55 Sensors and One T−56 Sensor
WHT
C07033
80
Carrier Accessory Kits
There are specific accessory kits sold for various field installed
accessories. These kits vary based on model, size, voltage,
manufacture date, and duct orientation. Some of these kits include
Economizer, Power Exhaust, and Electric Heat. Refer to the
Controls Quick Set−Up section for configuration and more
information on these accessories.
Two−Position Damper
The two-position outdoor air damper accessory usage depends on
model size and return duct orientation. This accessory wires
directly into the low voltage circuit for the indoor fan control. No
other control configuration is needed.
Indoor Air Quality
The indoor air quality (IAQ) sensor (part no. 33ZCSENCO2) is a
field-installed accessory which measures CO
When installing this sensor, an ECB board must be installed and
the unit must be configured for IAQ use by setting
Configuration→AIR.Q→IA.CF to a value of 1, 2, or 3. See the
Indoor Air Quality section for more information.
TB−24−20mA Input..........
TB−3Sensor Common..........
TB−R24vac Output.........
TB−CCommon (GND).........
levels in the air.
2
Outdoor Air Quality
The outdoor air quality (OAQ) sensor is a field-installed accessory
that measures CO
ECB board must be installed and the unit must be configured for
OAQ use by setting Configuration→AIR.Q→OA.CF to a value
of 1 or 2. See the Indoor Air Quality section for more information.
TB−24−20mA Input..........
TB−3Sensor Common..........
TB−R24vac Output.........
TB−CCommon (GND).........
levels in the air. When installing this sensor, an
2
Smoke Detectors
The smoke detectors are field-installed accessories. These detectors
can detect smoke in either the return air (part no.
CRSMKDET003A00) or supply and return air (part no.
CRSMKSUP002A00). When installing either detector, the unit
must be configured for fire shutdown by setting
Configuration→UNIT→FS.SW to normally open (1) or normally
closed (2).
TB−Fire Shutdown−1Dry Contact Source.............
TB−Fire Shutdown−2Discrete Input to Board...........
TB−R24vac Output.........
TB−CCommon (GND).........
NOTE: When a Humidi-Mizer system is installed, the inputs to
the fire shutdown are moved to the control harness. See the Third
Party Control section for more information.
Filter Status
The filter status accessory (part no. CRSTATUS002B00) is a
field-installed accessory. This accessory detects plugged filters.
When installing this accessory, the unit must be configured for
filter status by setting Configuration→UNIT→FL.SW to
normally open (1) or normally closed (2). Normally open (1) is the
preferred configuration.
Filter status wires are pre−run in the unit harness and located near
the switch installation location. Refer to the Filter Accessory
installation instructions for more information.
Fan Status
The fan status accessory (part no. CRSTATUS003B00) is a
field-installed accessory. This accessory detects when the indoor
fan is blowing air. When installing this accessory, the unit must be
configured for fan status by setting
Configuration→UNIT→FN.SW to normally open (1) or
normally closed (2). Normally open (1) is the preferred
configuration.
Fan status wires are pre−run in the unit harness and located near the
switch installation location. Refer to the Fan Accessory installation
instructions for more information.
NOTE: The fan status terminals on TB1 are NOT to be used.
Enthalpy Sensors
The enthalpy accessories (part no. CRENTSNG002A00 and
CRENTDIF002A00) are field-installed accessories. The first
accessory (outdoor air only) determines when the enthalpy is low
relative to a fixed reference. Adding the second accessory (return
air) compares the enthalpy between the outdoor and return
airstreams. In each case, the enthalpy 4 to 20 mA signals are
converted to a switch output which is read by the ECB. When
installing this accessory, the unit must be configured for
enthalpy-based control by setting
Configuration→ECON→EN.SW to normally open (1). See Fig.
26 and 27 for wiring details.
Normal status is an active switch which tells the control that
enthalpy is LOW. The actual switch terminal LOW is normally
closed. Refer to the Enthalpy Kit installation instructions for more
information on the installation.
Return/Supply Air Temperature Sensor
The temperature sensor (part no. 33ZCSENSAT) is a field-installed
accessory which may be installed on the common return air duct
and/or the common supply air duct near the unit. The duct return
air temperature (RAT) may be selected for display only if the space
temperature offset (SPTO) is not used. When installing the sensor,
the unit must be configured by setting
Configuration→UNIT→RAT.S to YES. Using a RAT will allow
differential dry bulb control of the economizer. The duct supply air
temperature (SAT) may be used to replace the SAT sensor that is
internal to the unit. A supply duct SAT measurement is valid for
heating mode display while the factory-standard internal SAT is
not valid for heating due to its location upstream of the heating
section. When installing the supply duct SAT, the unit must be
configured by setting Configuration→UNIT→SAT.H to ENBL.
A SAT sensor in the supply duct is the preferred configuration for
systems with Carrier variable volume and temperature (VVT)
accessory controls.
Space Humidistat
The Space Humidistat (part no. −−HL−−38MG−029) is a wall
mounted device with an adjustable setpoint to control humidity
levels. The humidistat input is provided on the field connection
terminal board. The Space Humidity Switch configuration,
Configuration→UNIT→RH.SW, identifies the normally open or
normally closed status of this input at LOW humidity.
TB−HUMIDISTAT1Discrete Input to Board............
TB−HUMIDISTAT224 VAC Dry Contact Source.......
NOTE: The humidistat terminals are only in use when the unit is
equipped with the Humidi−MiZer factory option.
48/50PG and PM
81
Space Humidity Sensor
The space relative humidity sensor (part no. 33ZCSENDRH−01
duct mount or 33ZCSENSRH−01 wall mount) is a field−installed
accessory. The space relative humidity (RHS) may be selected for
use if the outdoor air quality sensor (OAQ) is not used and an
economizer board is installed. When installing the relative
humidity sensor, the unit must be configured by setting
Configuration→UNIT→RH.S to YES.
TB−124 VDC Loop Power..........
TB−44−20mA Input Signal..........
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could cause personal
injury or death.
Before performing service or maintenance operations
on unit, turn off main power switch to unit and install
lockout tag. Ensure electrical service to rooftop unit
48/50PG and PM
agrees with voltage and amperage listed on the unit
rating plate.
UNIT OPERATION AND SAFETY HAZARD
Failure to follow this warning could cause personal
injury, death and/or equipment damage.
Puron (R−410A) refrigerant systems operate at higher
pressures than standard R−22 systems. Do not use R−22
service equipment or components on Puron refrigerant
equipment.
FIRE, EXPLOSION HAZARD
Failure to follow this warning could result in personal
injury, death and/or property damage.
1. Improper installation, adjustment, alteration, service,
or maintenance can cause property damage, personal
injury, or loss of life. Refer to the User’s Information
Manual provided with this unit for more details.
2. Do not store or use gasoline or other flammable
vapors and liquids in the vicinity of this or any other
appliance.
What to do if you smell gas:
1. DO NOT try to light any appliance.
2. DO NOT touch any electrical switch, or use any
phone in your building.
3. IMMEDIATELY call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s
instructions.
4. If you cannot reach your gas supplier, call the fire
department.
SERVICE
!
WARNING
!
WARNING
!
WARNING
!
WARNING
FIRE, EXPLOSION HAZARD
Failure to follow this warning could result in personal
injury or death.
Disconnect gas piping from unit when pressure testing at
pressure greater than 0.5 psig. Pressures greater than
0.5 psig will cause gas valve damage resulting in hazardous
condition. If gas valve is subjected to pressure greater than
0.5 psig, it must be replaced before use. When pressure
testing field-supplied gas piping at pressures of 0.5 psig or
less, a unit connected to such piping must be isolated by
closing the manual gas valve(s).
Cleaning
Inspect unit interior at beginning of each heating and cooling
season and as operating conditions require. Remove unit top panel
and/or side panels for access to unit interior.
Coil Maintenance and Cleaning Recommendation
Routine cleaning of coil surfaces is essential to maintain proper
operation of the unit. Elimination of contamination and removal of
harmful residues will greatly increase the life of the coil and extend
the life of the unit. The following maintenance and cleaning
procedures are recommended as part of the routine maintenance
activities to extend the life of the coil.
Remove Surface Loaded Fibers
Surface loaded fibers or dirt should be removed with a vacuum
cleaner. If a vacuum cleaner is not available, a soft non-metallic
bristle brush may be used. In either case, the tool should be applied
in the direction of the fins. Coil surfaces can be easily damaged (fin
edges can be easily bent over and damage to the coating of a
protected coil) if the tool is applied across the fins.
NOTE: Use of a water stream, such as a garden hose, against a
surface loaded coil will drive the fibers and dirt into the coil. This
will make cleaning efforts more difficult. Surface loaded fibers
must be completely removed prior to using low velocity clean
water rinse.
Periodic Clean Water Rinse
A periodic clean water rinse is very beneficial for coils that are
applied in coastal or industrial environments. However, it is very
important that the water rinse is made with very low velocity water
stream to avoid damaging the fin edges. Monthly cleaning as
described below is recommended.
Routine Cleaning of NOVATION Heat Exchanger Coil
Surfaces
To clean the NOVATION Heat Exchanger condenser coil,
chemicals are NOT to be used; only water is approved as the
cleaning solution. Only clean portable water is authorized for
cleaning NOVATION Heat Exchanger condensers. Carefully
remove any foreign objects or debris attached to the coil face or
trapped within the mounting frame and brackets. Using a high
pressure water sprayer, purge any soap or industrial cleaners from
hose and/or dilution tank prior to wetting the coil.
Clean condenser face by spraying the coil core steadily and
uniformly from top to bottom directing the spray straight into or
toward the coil face. Do not exceed 900 psig or a 45 degree angle;
nozzle must be at least 12” (30 cm) from the coil face. Reduce
pressure and use caution to prevent damage to air centers (fins). Do
not fracture the braze between air centers and refrigerant tubes.
Allow water to drain from the coil core and check for refrigerant
leaks prior to startup.
82
NOTE: Please see the NOVATION Heat Exchanger Condenser
Service section for specific information on the NOVATION Heat
Exchanger coil.
!
CAUTION
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in damage to
equipment.
Chemical cleaner should NOT be used on the aluminum
NOVATION condenser. Damage to the coil can occur. Only
approved cleaner is recommended.
Routine Cleaning of Round−Tube Coil Surfaces
Monthly cleaning with Totaline environmentally sound coil
cleaner is essential to extend the life of coils. This cleaner is
available from Carrier Replacement parts division as part number
P902-0301 for a one gallon container, and part number P902-0305
for a 5 gallon container. It is recommended that all round−tube
coils, including standard aluminum, pre-coated, copper/copper or
E-coated coils be cleaned with the Totaline environmentally sound
coil cleaner as described below. Coil cleaning should be part of the
unit’s regularly scheduled maintenance procedures to ensure long
life of the coil. Failure to clean the coils may result in reduced
durability in the environment.
Avoid the use of:
coil brighteners
acid cleaning prior to painting
high pressure washers
poor quality water for cleaning
Totaline environmentally sound coil cleaner is non-flammable,
hypoallergenic, non−bacterial, and a USDA accepted
biodegradable agent that will not harm the coil or surrounding
components such as electrical wiring, painted metal surfaces, or
insulation. Use of non-recommended coil cleaners is strongly
discouraged since coil and unit durability could be affected.
Failure to follow this caution may result in corrosion and
damage to the unit.
Harsh chemicals, household bleach or acid or basic cleaners
should not be used to clean outdoor or indoor coils of any
kind. These cleaners can be very difficult to rinse out of the
coil and can accelerate corrosion at the fin/tube interface
where dissimilar materials are in contact. If there is dirt
below the surface of the coil, use the Totaline
environmentally sound coil cleaner as described above.
!
CAUTION
UNIT RELIABILITY HAZARD
Failure to follow this caution may result in reduced unit
performance.
High velocity water from a pressure washer, garden hose, or
compressed air should never be used to clean a coil. The
force of the water or air jet will bend the fin edges and
increase airside pressure drop.
1. Proper eye protection such as safety glasses is
recommended during mixing and application.
2. Remove all surface loaded fibers and dirt with a vacuum
cleaner as described above.
3. Thoroughly wet finned surfaces with clean water and a low
velocity garden hose, being careful not to bend fins.
4. Mix Totaline environmentally sound coil cleaner in a
1
2
/2 gallon garden sprayer according to the instructions
included with the cleaner. The optimum solution
temperature is 100F.
NOTE: Do NOT USE water in excess of 130F, as the enzymatic
activity will be destroyed.
5. Thoroughly apply Totaline environmentally sound coil
cleaner solution to all coil surfaces including finned area,
tube sheets and coil headers.
6. Hold garden sprayer nozzle close to finned areas and apply
cleaner with a vertical, up-and-down motion. Avoid
spraying in horizontal pattern to minimize potential for fin
damage.
7. Ensure cleaner thoroughly penetrates deep into finned
areas.
8. Interior and exterior finned areas must be thoroughly
cleaned.
9. Finned surfaces should remain wet with cleaning solution
for 10 minutes.
10. Ensure surfaces are not allowed to dry before rinsing.
Reapplying cleaner as needed to ensure 10-minute
saturation is achieved.
11. Thoroughly rinse all surfaces with low velocity clean water
using downward rinsing motion of water spray nozzle.
Protect fins from damage from the spray nozzle.
Condensate Drain Pan (48/50PG03−14 Units)
Check and clean each year at the start of the cooling season. In
winter, keep drains and traps dry.
To clean the condensate pan:
1. Disconnect condensate drain system from side or bottom
drain connection.
2. Remove and clean trap.
3. Remove 4 screws securing condensate pan access cover to
unit. Save screws and panel.
4. Slide condensate pan out from unit and clean. Pan is made
of non-corrosive plastic. Use a mild cleaner to remove
heavy deposits of dirt and grime.
5. Replace pan in unit.
6. Replace condensate pan access cover with 4 screws saved
from Step 3.
7. Re-attach and prime condensate trap.
8. Connect condensate drainage system.
48/50PG and PM
83
Condensate Drain Pan (48/50PM16−28 Units)
Check and clean each year at the start of the cooling season. An
access panel is located above the condensate connection to allow
easy clean out of the condensate pan. The first time the panel is
removed, the insulation behind the access panel will need to be cut
away. Carefully cut the insulation with a knife or blade on three
sides so the insulation can be folded out of the way during
cleaning. Be careful not to damage components behind the
insulation while cutting. Once cleaning is completed, fold the
insulation back into place and secure the access panel in the
original position.
Filters
Clean or replace at start of each heating and cooling season, or
more often if operating conditions require. Refer to unit Installation
Instructions for type and size.
Outdoor−Air Inlet Screens
Clean screens with steam or hot water and a mild detergent. Do
not use throwaway filters in place of screens. See unit installation
instructions for quantity and size.
Main Burner (48PG and PM)
At the beginning of each heating season, inspect for deterioration
48/50PG and PM
or blockage due to corrosion or other causes. Observe the main
burner flames. Refer to Main Burners section.
Flue Gas Passageways (48PG and PM)
The flue collector box and heat exchanger cells may be inspected
by opening heat section access door (Fig. 5), flue box cover, and
main burner assembly. (See Fig. 50.) Refer to Main Burners section
for burner removal sequence. If cleaning is required, clean tubes
with a wire brush. Use Caution with ceramic heat exchanger
baffles. When installing retaining clip, be sure the center leg of the
clip extends inward toward baffle. (See Fig. 49.)
CERAMIC
BAFFLE
CLIP
NOTE: One baffle and clip will be in each upper tube of the heat exchanger.
Combustion−Air Blower
Clean periodically to assure proper airflow and heating efficiency.
Inspect blower wheel every fall and periodically during heating
season. For the first heating season, inspect blower wheel
bi-monthly to determine proper cleaning frequency.
To inspect blower wheel, open heat section door. Using a
flashlight, look into the flue exhaust duct to inspect. If cleaning is
required, remove motor and wheel assembly by removing the
screws holding the flue box cover to the flue box. (See Fig. 50 or
51.) Remove the screws holding the inducer housing to the inlet
plate. The wheel can then be removed from the motor shaft and
cleaned with a detergent or solvent. Replace the wheel onto the
motor shaft in the correct position and reassemble the flue cover
onto the flue box.
Fig. 49 − Removing Heat Exchanger Ceramic
Baffles and Clips
C07260
Lubrication
Compressors
Each compressor is charged with the correct amount of oil at the
factory.
!
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in damage to unit
components.
The compressor is in a Puron refrigerant system and uses a
polyolester (POE) oil. This oil is extremely hygroscopic,
meaning it absorbs water readily. POE oils can absorb 15
times as much water as other oils designed for HCFC and
CFC refrigerants. Avoid exposure of the oil to the
atmosphere.
Polyolester (POE) compressor lubricants are known to cause long
term damage to some synthetic roofing materials. Exposure, even if
immediately cleaned up, may cause roofing materials to become
brittle (leading to cracking) within a year. When performing any
service which may risk exposure of compressor oil to the roof, take
appropriate precautions to protect roofing. Procedures which risk
oil leakage include compressor replacement, repairing refrigerant
leaks, and replacing refrigerant components. To prepare rooftop:
1. Cover extended roof work area with an impermeable plastic
dropcloth or tarp. Make sure a 10 x 10 ft area around the
work area is covered.
2. Cover area in front of the unit service panel with a terry
cloth shop towel to absorb lubricant spills and prevent
run-offs. Towel will also protect dropcloth from tears caused
by tools or components.
3. Place terry cloth shop towel inside the unit directly under
components to be serviced to prevent spills through the
bottom of the unit.
4. Perform the required service.
5. Remove and dispose of any oil contaminated material per
local codes.
Indoor Fan Shaft Bearings (Sizes 03−14)
The indoor fan has permanently sealed bearings. No field
lubrication is necessary.
Indoor Fan Shaft Bearings (Sizes 16−28)
Lubricate bearings at least every 6 months with suitable bearing
grease. Typical lubricants are given below:
MANUFACTURERLUBRICANT
Texaco
Mobil
Sunoco
Texaco
* Preferred lubricant because it contains rust and oxidation inhibitors.
Regal AFB‐2*
Mobilplex EP No. 1
Prestige 42
Multifak 2
84
ROLLOUT
SWITCH
HEAT EXCHANGER
SECTION
MAIN BURNER SECTION
Fig. 50 − 48PG03−14 Typical Gas Heating Section
(48PG03−07 Shown)
INDUCED
DRAFT
MOTOR
COMBUSTION
FAN HOUSING
MAIN GAS
VALVE
C07037
4. For 48/50PG03−14 units, disconnect the electrical wires
connected to the slide−out fan deck (supply air thermistor
and fan status switch if installed). Wires may be damaged if
not disconnected. For 48/50PM16−28 units, disconnect the
limit switch wires located on the right side of the fan deck
(48 series only). Other wires do not need to be
disconnected.
5. Fan deck can now be slid out to access serviceable
components.
!
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in damage to the
unit.
DO NOT SLIDE FAN DECK OUT PAST THE FAN
DECK STOP. If further access is required, the fan deck
must be supported. Make sure plugs and wiring are not
pinched between fan housing and unit sheet metal post.
6. To replace fan deck to operating position, slide fan deck
back into the unit. Secure with the two no. 10 screws
removed in Step 3.
7. Re-attach electrical wires.
8. Close fan section access door.
9. Restore power to unit.
48/50PG and PM
COMBUSTION
HEAT
EXCHANGER
SECTION
IGC BOARD
(HIDDEN)
MAIN BURNER
SECTION
FAN HOUSING
INDUCED
DRAFT
MOTOR
MAIN GAS
VALVE
C07259
Fig. 51 − 48PM16−28
Typical Gas Heating Section
Condenser and Evaporator−Fan Motor Bearings
The condenser-fan and evaporator-fan motors have permanently
sealed bearings, so no field lubrication is necessary.
Economizer or Manual Outside Air Damper
If blade adjustment is required, refer to unit or accessory
installation instructions.
Evaporator Fan Service and Replacement
The units feature a slide-out fan deck for easy servicing of the
indoor-fan motor, pulleys, belt, and bearings. To service
components in this section, perform the following procedure:
1. Turn off unit power.
2. Open the fan section access door.
3. Remove two no. 10 screws at front of slide-out fan deck.
Save screws. (See Fig. 52 or 53.)
Evaporator Fan Performance Adjustment
(Fig. 52−54)
Fan motor pulleys are factory set for speed shown in Appendix D.
To change fan speeds:
1. Shut off unit power supply.
2. Loosen nuts on the 4 carriage bolts in the mounting base.
Using adjusting bolts and plate, slide motor and remove
belt.
3. Loosen movable-pulley flange setscrew. (See Fig. 54.)
4. Screw movable flange toward fixed flange to increase speed
and away from fixed flange to decrease speed. Increasing
fan speed increases load on motor. Do not exceed maximum
speed specified in Appendix D.
See Appendix D for air quantity limits.
5. Set movable flange at nearest keyway of pulley hub and
tighten setscrew. (See Appendix D for speed change for
each full turn of pulley flange.)
6. Replace belts.
7. Realign fan and motor pulleys:
a. Loosen fan pulley setscrews.
b. Slide fan pulley along fan shaft.
c. Make angular alignment by loosening motor from
mounting plate.
8. Tighten belts.
9. Restore power to unit.
C06041
Fig. 54 − Evaporator−Fan Alignment and Adjustment
Evaporator Fan Belt Tension Adjustment
To adjust belt tension:
1. Turn off unit power.
2. Slide out fan deck to service position as shown in
Evaporator Fan Service and Replacement section above.
3. Loosen motor mounting plate bolts.
4. Move motor mounting plate to adjust to proper belt tension.
Motor adjuster bolts may be used to tighten belts. (See Fig.
52 or 53.) Do not overtighten belt. See Table 27 for
48/50PM16−28 size belt tension
5. Check for proper belt alignment. Adjust if necessary.
6. Tighten motor mounting plate bolts to lock motor in proper
position.
7. Return fan deck back into operating position.
8. Restore power to unit.
86
Condenser-Fan Adjustment (Fig. 55)
T
1. Shut off unit power supply.
2. Remove condenser-fan assembly (grille, motor, motor
cover, and fan) and loosen fan hub setscrews.
3. Adjust fan height as shown in Fig. 55.
4. Tighten setscrews and replace condenser-fan assembly.
5. Turn on power to unit.
C09292
Fig. 55 − Condenser−Fan Adjustment
NOVATION Heat Exchanger Condenser Service
and Replacement
The condenser coil in this unit is a NOVATION heat exchanger
surface. The NOVATION heat exchanger is an all−aluminum
construction with fins over a single−depth crosstube. The
crosstubes have multiple small passages through which the
refrigerant passes from header to header on each end. (See Fig. 56.)
The all−aluminum construction provides increased resistance to
corrosion over aluminum fins on copper tubes in normal and mild
marine applications.
!
CAUTION
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in damage to
equipment.
Refer to product data manual for coil usage in coastal or
industrial applications.
TUBES
FINS
MANIFOLD
a30-4457
Fig. 56 − NOVATION Heat Exchanger Coils
Repairing Tube Leaks
RCD offers service repair kits for repairing tube leaks in the
crosstubes. These kits include approved braze materials and
instructions specific to the aluminum NOVATION heat exchanger
coil.
MICROCHANNELS
C07273
!
CAUTION
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in damage to
equipment.
Use of other than approved repair procedures may affect the
pressure rating or the corrosion resistance of the NOVATION
heat exchanger condenser coil.
Replacing the NOVATION Heat Exchanger Coil
The service replacement coil is preformed and is equipped with
transition joints with copper stub tubes. When brazing the
connection joints to the unit tubing, use a wet cloth around the
aluminum tube at the transition joint. Avoid applying torch flame
directly onto the aluminum tubing.
Verify Sensor Performance
Verify that thermistor, transducer, and switch inputs are reading
correctly. These values can be accessed through the Scrolling
Marquee display in the Temperatures, Pressures, and Inputs menus.
Some values will depend on configuration choices. Refer to the
Control Set Up Checklist completed for the specific unit
installation and to the configuration tables in Appendix A.
Economizer Operation During Power Failure
Dampers have a spring return. In event of power failure, dampers
will return to fully closed position until power is restored. Do not
manually operate damper motor.
Evacuation
Proper evacuation of the system will remove noncondensables and
ensure a tight, dry system before charging. Evacuate from both
high and low side ports. Never use the system compressor as a
vacuum pump. Refrigerant tubes and indoor coil should be
evacuated to 500 microns. Always break a vacuum with dry
nitrogen. The two possible methods are the deep vacuum method
and the triple evacuation method.
Deep Vacuum Method
The deep vacuum method requires a vacuum pump capable of
pulling a minimum vacuum of 500 microns and a vacuum gauge
capable of accurately measuring this vacuum depth. The deep
vacuum method is the most positive way of assuring a system is
free of air and liquid water. (See Fig. 57.)
5000
4500
4000
3500
3000
2500
MICRONS
2000
1500
1000
500
0
2
1
MINUTES
4
3
Fig. 57 − Deep Vacuum Graph
LEAK IN
SYSTEM
VACUUM TIGH
TOO WET
TIGHT
DRY SYSTEM
56
7
C06264
48/50PG and PM
87
Triple Evacuation Method
R410A
REFRIGERANTNT
OUTDOOR
FAN
MUSTBEBE
OPERATINGONON
HIGH
SPEED
20
40
60
80
100
120
140
160
150
200
250
300
350
400
450
500
550
600
Comp
ressor
Disch
arge
Pressu
re,[p[p
sig
Outdoor
Coil
eavin
Temp
eratu
re,
[Deg
rees
F]
Chargeifif
bove
the
Curve
Removeve
Chargeifif
Below
the
Curve
RANT
R F
N M
N H
H S
20
40
60
80
12
14
16
150
200
250
300
350
400
450
500
550
600
isc
sig
bov
the
Outdoor
Coil
eavin
Temp
eratu
re,
[Deg
rees
F]
The triple evacuation method should only be used when vacuum
pump is capable of pumping down to 28−in. of mercury and
system does not contain any liquid water. Proceed as follows:
1. Pump system down to 28−in. of mercury and allow pump
to continue operating for an additional 15 minutes.
2. Close service valves and shut off vacuum pump.
3. Connect a nitrogen cylinder and regulator to system and
open until system pressure is 2 psig.
4. Close service valve and allow system to stand for 1 hr.
During this time, dry nitrogen will be able to diffuse
throughout the system, absorbing moisture.
5. Repeat this procedure. System will then contain minimal
amounts of contaminants and water vapor.
Refrigerant Charge
Amount of refrigerant charge is listed on unit nameplate. Refer to
Carrier GTAC II; Module 5; Charging, Recovery, Recycling, and
Reclamation section for charging methods and procedures. Unit
panels must be in place when unit is operating during charging
procedure.
Puron (R-410A) refrigerant systems should be charged with
48/50PG and PM
liquid refrigerant. Use a commercial type metering device in the
manifold hose.
R410A
FAN
Above
Comp
MUST
the
300
ressor
REFRIGERA
OPERATING
Curve
Remo
350
Disch
arge
Pressu
Charge
400
160
140
F]
120
rees
[Deg
re,
100
eratu
g Te m p
80
eavin
L
Coil
60
Outdoor
40
20
150
OUTDOOR
AddddCharge
200
250
Fig. 58 − Charging Chart — 48/50PG03
HIGH
SPEED
Below
the
Curve
450
500
550
re,
sig
]
600
C07038
!
WARNING
UNIT OPERATION AND SAFETY HAZARD
Failure to follow this warning could cause personal
injury, death and/or equipment damage.
OUTDOORF
16
0
14
0
R4R410A REREFRIRIGERANT
ANM
UST BE OPERATING ONH
IGHS
PEED
Puron (R−410A) refrigerant systems operate at higher
pressures than standard R−22 systems. Do not use R−22
service equipment or components on Puron refrigerant
equipment. Gauge set, hoses, and recovery system must
be designed to handle Puron refrigerant. If unsure
about equipment, consult the equipment manufacturer.
NOTE: Do not use recycled refrigerant as it may contain
contaminants.
12
rees
[Deg
re,
10100
eratu
g Te m p
Leavin
Coil
Outdoor
80
60
Add Chahargegeif Abov
0
e the
Cururve
ReRemove Charge if BeBelow the Curve
F]
No Charge
Use standard evacuating techniques. After evacuating system,
weigh in the specified amount of refrigerant (refer to unit
nameplate).
NOTE: System charge for units with Humidi-MiZer system is
greater than the system charge of the standard unit.
Low Charge Cooling
Using cooling charging chart (see Fig. 58−79), add or remove
refrigerant until conditions of the chart are met. An accurate
pressure gauge and temperature-sensing device is required.
Charging is accomplished by ensuring the proper amount of liquid
subcooling. Connect pressure gauge to the compressor discharge
service valve. Connect temperature sensing device to the liquid
line between the condenser and the TXV (thermostatic expansion
valve), and insulate it so that ambient temperature does not affect
reading.
To Use the Cooling Charging Chart, Standard Unit
NOTE: All circuits must be running in normal cooling mode.
Indoor airflow must be within specified air quantity limits for
cooling. (See Appendix D.) All outdoor fans must be on and
running at high speed. Use the Cooling Service Test Outdoor Fan
Override function to start all outdoor fans.
Use the temperature and pressure readings, and find the
intersection point on the cooling charging chart. If intersection
point on chart is above line, add refrigerant. If intersection point on
chart is below line, carefully recover some of the charge. Recheck
suction pressure as charge is adjusted.
The TXV is set to maintain between 10 and 15 degrees of
superheat at the compressors. The valves are factory set and cannot
be adjusted. Do not use A TXV designed for use with R-22.
To Use the Cooling Charging Charts, Units With
Humidi−Mizert Adaptive Dehumidification System
NOTE: All circuits must be running in normal cooling mode.
Indoor airflow must be within specified air quantity limits for
cooling. (See Appendix D.) All outdoor fans must be on and
running at high speed. Use the Cooling Service Test Outdoor Fan
function (Service Test→COOL→OF.OV) to start all outdoor fans.
40
20
200
250
300
350
400
150
Compre ssssor Disc
ha rge P re ssssure , [psig
450
Fig. 59 − Charging Chart — 48/50PG04
500
550
]
600
C07039
88
If the outdoor temperature is low, the Motormaster outdoor fan
RANT
R F
N M
N H
H S
20
40
60
80
12
14
16
150
2002525
350
400
450
500
550
600
isc
sig
bov
the
ve
Outdoor
Coil
eavin
Temp
eratu
re,
[Deg
rees
F]
RANT
R F
N M
N H
H S
20
40
60
80
12
14
16
150
2002525
350
400
450
500
550
600
isc
sig
bov
the
ve
Outdoor
Coil
eavin
Temp
eratu
re,
[Deg
rees
F]
RANT
R F
N M
N H
H S
20
40
60
80
12
14
16
150
2002525
350
400
450
500
550
600
isc
sig
bov
the
ve
Outdoor
Coil
eavin
Temp
eratu
re,
[Deg
rees
F]
R
410A R R
GE R R A A
NT
AL L L O O
UTDO O O R R F F
ANS M M
US T T
BE
RUNNI
NG
20
40
60
80
10 0 0
12 0 0
14 0 0
16 0 0
100
150
20 0 0
250
300
35 0 0
400
450
500
550
600
ss o o r r D D
isc h h a a r r g g e e P P r r e e
ss u u r r e e , , [ [ p p
sig ] ]
dd C C
ha r r g g e e i i f f A A
bov e e
the C C
ur v v e e
ve
Ch
ar g g e e
if B B
e
lo w w t t h h e e
Cu r r
ve
Outdoor
Coil
L
eavin
g
Temp
eratu
re,
[Deg
rees
F]
control device may need to be temporarily bypassed by rewiring
the power leads to obtain full speed.
R4R410A REREFRIRIGERANT
ANM
UST BE OPERATING ONH
e the
Cururve
RemoveveChChararge ififBelolow the CuCurve
IGHS
PEED
16
14
F]
12
rees
[Deg
re,
eratu
10100
g Te m p
Leavin
Coil
Outdoor
80
60
0
0
AddddChaharge if Abov
0
OUTDOORF
16
14
F]
12
rees
[Deg
re,
10100
eratu
g Te m p
Leavin
Coil
Outdoor
0
0
0
80
60
40
OUTDOORF
ANM
AddddChaharge if Abov
R4R410A REREFRIRIGERANT
UST BE OPERATING ONH
e the
Cururve
RemoveveChChararge ififBelolow the CuCurve
IGHS
PEED
40
20
200
150
030000350
Compre ssssor Disc
400
ha rge Pressssure , [psig
Fig. 60 − Charging Chart — 48/50PG05
R4R410A REREFRIRIGERANT
ANM
UST BE OPERATING ONH
e the
Cururve
RemoveveChChararge ififBelolow the CuCurve
030000350
Compre ssssor Disc
400
ha rge Pressssure , [psig
16
14
F]
12
rees
[Deg
re,
eratu
10100
g Te m p
Leavin
Coil
Outdoor
80
60
40
20
0
0
AddddChaharge if Abov
0
150
OUTDOORF
200
20
200
150
450
500
550
]
600
030000350
Compre ssssor Disc
400
ha rge P re ssssure , [psig
450
500
550
]
600
C07042
48/50PG and PM
Fig. 62 − Charging Chart — 48/50PG07
C07040
R
E E F F R R I I GE
410A
AL
UTDO
ANS
IGHS
PEED
16
14
F]
12
A A dd
ha
bov
the
rees
[Deg
re,
10
eratu
Temp
g
eavin
80
L
Coil
60
Outdoor
ur
R R e e m m o o ve
40
20
100
150
20
250
450
500
550
]
600
C C o o m m p p r r e e ss
300
isc
NT
US
BE
RUNNI
NG
Ch
ar
if
lo
Cu
ve
e
35
400
450
500
550
ss
sig
600
Fig. 61 − Charging Chart — 48/50PG06
C07041
C06265
Fig. 63 − Charging Chart — 48/50PG08 and 09
89
R
410A R R
GE R R A A
NT
AL L L O O
UTDO O O R R F F
ANS M M
US T T
BE
RUNNI
NG
20
40
60
80
10 0 0
12 0 0
14 0 0
16
16 0 0
100
150
20 0 0
250
300
35 0 0
400
450
500
550
600
ss o o r r D D
isc h h a a r r g g e e P P r r e e
ss u u r r e e , , [ [ p p
sig ] ]
dd C C
ha r r g g e e i i f f A A
bov e e
the C C
ur v v e e
ve
Ch
ar g g e e
if B B e e
lo w w t t h h e e
Cu r r
ve
Outdoor
Coil
L
eavin
g
Temp
eratu
re,
[Deg
rees
F]
R4
10 A A
REF
RI G G E E
RANT
UT
DO O O R R F F
ANS M M
US T T B B E E R R
UNNI
NG
20
40
60
80
10 0 0
12 0 0
14 0 0
16 0 0
100
150
20 0 0
250
300
35 0 0
400
450
500
550
600
ss o o r r D D
isc h h a a r r g g e e P P r r e e
ss u u r r e e , , [ [ p p
sig ] ]
dd C C
ha r r g g e e i i f f A A
bov e e
the C C
ur v v e e
ve
Ch
ar g g e e
if B B e e
lo w w t t h h e e
Cu r r
ve
Outdoor
Coil
L
eavin
g
Temp
eratu
re,
[Deg
rees
F]
14
F]
12
rees
[Deg
re,
10
eratu
T emp
g
80
eavin
L
Coil
60
Outdoor
40
20
100
A A dd
150
ha
AL
20
C C o o m m p p r r e e ss
bov
250
R
410A
UTDO
the
ur
R R e e m m o o ve
300
isc
E E F F R R I I GE
ANS
Ch
35
US
ar
400
ss
NT
BE
if
RUNNI
lo
450
sig
NG
500
PM16 and 20
Cu
ve
C09294
Fig. 66 − Charging Chart − 48/50PM16 and 20
550
600
48/50PG and PM
Fig. 64 − Charging Chart — 48/50PG12
R4
10
REF
RI
ur
ANS
35
RANT
US
Ch
ar
if
400
ss
A A L L L L O O UT
ha
20
C C o o m m p p r r e e ss
DO
bov
250
the
300
R R e e m m o o ve
isc
16
14
A A dd
12
F]
rees
10
[Deg
re,
eratu
80
Temp
g
eavin
L
Coil
60
Outdoor
40
20
100
150
Fig. 65 − Charging Chart — 48/50PG14
UNNI
lo
450
sig
NG
500
C06266
Cu
ve
C08048
Fig. 67 − Charging Chart − 48/50PM24
550
600
C06267
C08049
Fig. 68 − Charging Chart − 48/50PM28
90
Be sure unit is in normal cooling mode by checking that the RH2
solenoid coil(s) and the CRC relay are deenergized (control outputs
off). Adjust charge per the charging charts as described in the To
Use The Cooling Charging Charts, Standard Unit section. Switch
system to run in the dehumidification mode for 5 minutes.
Dehumidification mode is when the RH2 solenoid coil(s) and the
CRC relay are energized. Switch back to cooling mode to recheck
pressures and temperatures on the charging chart and adjust charge
if necessary. If charge adjustment is necessary, then repeat the steps
in this paragraph until no charge adjustment is necessary. When no
more charge adjustment is necessary after switching from
Dehumidification mode back to Cooling mode, then charge
adjustment procedure is complete. Remove jumper from the
outdoor motor speed controller.
PuronR Refrigerant
Puron refrigerant operates at 50 to 70 percent higher pressures than
R-22. Be sure that servicing equipment and replacement
components are designed to operate with Puron refrigerant. Do not
mix with components that have been used with other refrigerants.
Puron refrigerant, as with other HFCs, is only compatible with
POE oils.
Recovery cylinder service pressure rating must be 400 psig. Puron
systems should be charged with liquid refrigerant. Use a
commercial-type metering device in the manifold hose. Manifold
sets should be 750 psig high-side and 200 psig low-side with 520
psig low-side retard. Use hoses with 750 psig service pressure
rating. Leak detectors should be designed to detect HFC
refrigerant.
*As the height above sea level increases, there is less oxygen per cubic foot of air.
Therefore, heat input rate should be reduced at higher altitudes. Includes a 4%
input reduction per each 1000 ft.
†Orifices available through your Carrier dealer.
The gas valve opens and closes in response to the thermostat or
limit control.
When power is supplied to valve terminals W2 (High Fire) and C1,
the main valve opens to its preset position.
The regular factory setting is stamped on the valve body.
To adjust regulator:
1. Set unit at setting for no call for heat.
2. Turn main gas valve to OFF position.
3. Remove
connection. Install a suitable pressure-measuring device.
4. Set main gas valve to ON position.
5. Set thermostat at setting to call for heat.
6. Remove screw cap covering regulator adjustment screw.
(See Fig. 69.)
7. Turn adjustment screw clockwise to increase pressure or
counterclockwise to decrease pressure. The setting is 3.50
in. wg on sizes 03-14 and 3.00 on size 16−28.
8. Once desired pressure is established, set unit setting for no
call for heat, turn off main gas valve, remove
pressure-measuring device, and replace
screw cap.
*As the height above sea level increases, there is less oxygen per cubic foot of air. Therefore, heat input rate should be reduced at higher altitudes. Includes a
4% input reduction per each 1000 ft.
†Orifices available through the local Carrier dealer.
*As the height above sea level increases, there is less oxygen per cubic foot of air. Therefore, heat input rate should be reduced at higher altitudes. Includes a
4% input reduction per each 1000 ft.
†Orifices available through the local Carrier dealer.
High Altitude (48PG and PM)
For high altitude applications greater than 2,000 ft the heat input
rate should be reduced. The higher the altitude is above sea level,
the less oxygen is in the air. See Table 28 for orifice sizing. A high
altitude kit is available to convert unit for altitudes up to 7,000 ft.
Main Burners (48PG and 48PM)
For all applications, main burners are factory set and should require
no adjustment.
Main Burner Removal
1. Shut off (field-supplied) manual main gas valve.
2. Shut off power to unit.
3. Open gas section access door.
4. Disconnect gas piping from gas valve inlet.
5. Remove wires from gas valve.
6. Remove wires from rollout switch.
7. Remove sensor wire and ignitor cable from IGC board.
8. Remove 2 screws that hold the burner assembly to vestibule
plate. For 48PM16−28 units, also remove the 2 screws securing the manifold bracket to the basepan.
9. Rotate the burner/manifold assembly to the right, away
from the flue extension and lift burner/manifold assembly
out of unit.
1. Remove burner rack from unit as described in Main Burner
Removal section above.
2. Inspect burners, and if dirty, remove burners from rack. The
two outer burners have the flame crossover closed off in
order to prevent gas flow from exiting the sides of the
burner assembly. To prevent ignition problems, make sure
the outer burners are returned to their original position when
done servicing.
3. Using a soft brush, clean burners and crossover port as
required.
4. Adjust spark gap. (See Fig. 70.)
5. Reinstall burners on rack.
6. Reinstall burner rack as described above.
92
E
E
SPARK GAP
0.181”
[4.6]
SECTION
C-C
AA
C
C
SECTION
A-A
SCALE 1:1
B
Fig. 70 − Spark Gap Adjustment
Filter Drier
Replace whenever refrigerant system is exposed to atmosphere.
Only use factory specified liquid-line filter driers with working
pressures no less than 650 psig. Do not install a suction-line filter
drier in liquid line. A liquid-line filter drier designed for use with
Puron refrigerant is required on every unit.
Protective Devices
Compressor Rotation
Overcurrent
Each compressor has internal line break motor protection.
Overtemperature
Each compressor has an internal protector to protect it against
excessively high discharge gas temperatures.
High−Pressure Switch
If the high-pressure switch trips, the compressor will shut down
and the current sensor (3-phase units only) will not detect current.
See the Current Sensor section below for more information.
Current Sensor (CS) (3−Phase Units Only)
The purpose of the CS is to detect losses in compressor power.
After detecting a loss in compressor power, unit control locks out
the compressor for 15 minutes. After 15 minutes, the alarm will
automatically reset. If this alarm occurs 3 times consecutively, the
compressor will remain locked out until an alarm reset is initiated
via CCN or manually via the Scrolling Marquee display (see
Alarms and Alerts section for more details).
Evaporator Fan Motor Protection
Indoor-fan motors less than 5 hp are equipped with internal
overcurrent and overtemperature protection. Protection devices
reset automatically. Disconnect and lock out power when servicing
motor. Indoor-fan motors 5 hp and larger are equipped with a
manual reset, calibrated trip, magnetic circuit breaker and
overcurrent protection. Do not bypass connections or increase the
size of the breaker to correct trouble. Determine the cause and
correct it before resetting the breaker.
25.4
MAX. TYP .
B
SECTION
E-E
SCALE 2:1
SECTION
SCALE 1:1
D
D
B-B
SPARK GAP
0.120 TO 0.140”
[3.05 TO 3.56]
SECTION
D-D
C06269
Condenser−Fan Motor Protection
Each condenser-fan motor is internally protected against
overtemperature.
Fuses are located in the control box and feed power to the
condenser fan motors. Always replace blown fuses with the
correct size fuse as indicated on the unit fuse label.
Saturated Suction Pressure (SSP)
If the SSP for a particular circuit is reading below the alarm set point
for an extended period of time, that circuit will be shut down. After 15
minutes, the alarm will automatically reset. If this alarm occurs 3 times
consecutively, the circuit will remain locked out until an alarm reset is
initiated via CCN or manually via the Scrolling Marquee display (see
Alarms and Alerts section for more details).
Relief Devices
All units have relief devices to protect against damage from
excessive pressures (i.e., fire). These devices protect the high and
low side and are located at the suction line service port. Protect
joint during brazing operations near joint.
Control Circuit, 24−V
Each control circuit is protected against overcurrent by a circuit
breaker. Breaker can be reset. If it trips, determine cause of trouble
before resetting.
Replacement Parts
A complete list of replacement parts may be obtained from any
Carrier distributor upon request.
Diagnostic LEDs
The MBB, ECB, and IGC control boards have LED lights for
diagnostic purposes. The meanings and error codes can be found
in the troubleshooting section of this manual.
EnergyX
For units equipped with the EnergyX factory installed option, there
will be an EnergyXv2 Supplement Installation Instructions in the
unit’s information packet. Refer to this supplement for details on
service and Maintenance.
93
48/50PG and PM
ITEMEXPANSIONRANGEUNITSCCN TABLE/
RUN STATUSSTATUS DISPLAY
VIEWAuto View of Run Status(VIEW = Display only)
HVACHVAC Mode Status1=Disabled
OCCCurrently OccupiedNo/YesOCCUPIED
SATSuppy Air Temperaturexxx..x°FSAT_DISP
ALRMCurrent Alarms & AlertsxxALRMALRT
TIMETime of Dayxx.xxhh.mmTIMECOPY
VERSSoftware Version NumbersVERSIONS
MBBCESR131320xxxx(xxxx in table)MODEL_NUMBER_01
ECBCESR131249xxxxMODEL_NUMBER_02
MARQCESR131171xxxxMODEL_NUMBER_03
EFF.CCool Setpoint In Effectxx.x°FCSP_EFF
EFF.HHeat Setpoint In Effectxx.x°FHSP_EFF
OCCCurrently OccupiedNo/YesOCCUPIEDforcibleforcible
T.OVRTimed Override in EffectNo/YesMODETOVR
LINKLinkage ActiveNo/YesMODELINK
D.LMTDemand Limit In EffectNo/YesMODEDMDL
C.LOCCompressor OAT LockoutNo/YesCOMPLOCK
H.LOCHeat OAT LockoutNo/YesHEATLOCK
OK.ECOK to Use Economizer?No/YesECONCOOL
COOLCooling StatusCOOLDISP
DMD.CCooling Demandxxx.x^FCOOL_DMD
AVL.CAvailable Cooling StagesxAVLCSTGS
REQ.CRequested Cooling StagesxREQCSTGS
MAX.CMax Allowed Cool StagesxMAXCSTGSforcible
LMT.CMax Cool Stage In EffectxCSTGLIMT
IDFIndoor Fan StateOff/OnIDFSTATE
F.SPDCommanded Fan Speedxxx%FANSPEED
OFC.1Outdoor Fan 1 RelayOff/OnOFC_1
OFC.2Outdoor Fan 2 RelayOff/OnOFC_2
OFC.3Outdoor Fan 3 RelayOff/OnOFC_3
CRCCool>Reheat1 ControlOff/OnCRC
CIR.ARefrigerant Circuit A CIRCUIT A
EC.CPEcono Commanded Positionxxx%ECONOCMD
EC.APEcono Actual Positionxxx%ECONOPOS
EC.MPMin Position in Effectxxx%MIN_POSforcible
IAQ.SIAQ Level (switch)Low/HighIAQIN
IAQIAQ Level (sensor)xxxxIAQ
OATOutdoor Air Temperaturexxx.x°FOA_TEMP
ENTHOutdoor Enthalpy SwitchLow/HighENTHALPY
OAQOAQ Level (sensor)xxxxOAQ
PE.1Power Exhaust 1 RelayOff/OnPE_1
PE.2Power Exhaust 2 RelayOff/OnPE_2
OAUOutside Air Unit StatusOAUDISP
OA.RNOAU System Run State1=AUTO
OA.OPOAU Operating Mode0=Off
UPCUPC Software VersionxxxxUPC_VER
OAUOA Unit Software VersionxxxxOAU_VER
2P.DMOAU 2position DamperClose/OpenOAUDMPR
WHLOAU Wheel Speedxxx%OAUWHEEL
LATOAU Leaving Air Tempxxx.x°FOAU_LAT
EXATOAU Exhaust Air Tempxxx.x°FOAU_EXAT
OA.MNMinimum Outside Air CFMxxxxxCFMMINOACFM
DCV.MMin DCV Outside Air CFMxxxxxCFMMINDCVSP
OA.FSOAU OA Fan Speedxxx%OAFANSPD
A.OAActual Outside Air CFMxxxxxCFMACTOACFM
C.OACommand Outside Air CFMxxxxxCFMCMDOACFM
PE.OFPower Exhaust CFM OffsetxxxxxCFMEXOFFSET
EX.FSOAU Exhaust Fan Speedxxx%OAUPESPD
A.EXActual Exhaust Air CFMxxxxxCFMACTEXCFM
C.EXCommand Exhaust Air CFMxxxxxCFMCMDEXCFM
BP.SPBuilding Pressure Setpntx.xxin H2OOAU_BPSP
BPBuilding Pressurex.xxin H2OOAU_BP
TM.LOOA Tempring Lockout Tempxx°FOATMPLOC
TM.SPOA Tempring SAT Setpointxx°FOATMPSPT
OA.HTOAU Tempering Heaterxxx%OAHEATER
HRSComponent Run HoursSTRTHOUR
A1Compressor A1 Run Hoursxxxxx.xxhoursHR_A1forcible
A2Compressor A2 Run Hoursxxxxx.xxhoursHR_A2forcible
B1Compressor B1 Run Hoursxxxxx.xxhoursHR_B1forcible
C1Compressor C1 Run Hoursxxxxx.xxhoursHR_C1forcible
CCHCrankcase Heat Run Hoursxxxxx.xxhoursHR_CCHforcible
IDFIndoor Fan Run Hoursxxxxx.xxhoursHR_IDFforcible
OFC.1Outdoor Fan 1 Run Hoursxxxxx.xxhoursHR_OFC_1forcible
OFC.2Outdoor Fan 2 Run Hoursxxxxx.xxhoursHR_OFC_2forcible
OFC.3Outdoor Fan 3 Run Hoursxxxxx.xxhoursHR_OFC_3forcible
HT.1Heat Stage 1 Run Hoursxxxxx.xxhoursHR_HTR_1forcible
HT.2Heat Stage 2 Run Hoursxxxxx.xxhoursHR_HTR_2forcible
PE.1Power Exhaust1 Run Hoursxxxxx.xxhoursHR_PE_1forcible
PE.2Power Exhaust2 Run Hoursxxxxx.xxhoursHR_PE_2forcible
ALRMAlarm Relay Run Hoursxxxxx.xxhoursHR_ALMforcible
CRCReheat1 Valve Run Hoursxxxxx.xxhoursHR_CRCforcible
RH2.AReheat2 Valve A Run Hrsxxxxx.xxhoursHR_RH2_Aforcible
RH2.BReheat2 Valve BC Run Hrsxxxxx.xxhoursHR_RH2_Bforcible
WHLOAU Wheel Test0 to 100%0S_WHEELforcibleforcible
OA.OFOAU OA Fan Speed Test0 to100%0S_OAFANforcibleforcible
OA.XFOAU PE Fan Speed Test0 to100%0S_EXFANforcibleforcible
OA.HTOAU Tempring Heater Test0 to 100%0S_OAHEATforcibleforcible
FANSTest FansTESTFANS
IDFIndoor Fan Power TestOff/OnOffS_IDFforcibleforcible
F.SPDIndoor Fan Speed Test0 to 100%0S_FANSPDforcibleforcible
OFC.1Outdoor Fan 1 TestOff/OnOffS_OFC_1forcibleforcible
OFC.2Outdoor Fan 2 TestOff/OnOffS_OFC_2forcibleforcible
OFC.3Outdoor Fan 3 TestOff/OnOffS_OFC_3forcibleforcible
COOLTest CoolingTESTCOOL
CMP.ACool A TestOff/OnOffS_COMP_Aforcibleforcible
CMP.BCool B TestOff/OnOffS_COMP_Bforcibleforcible
CMP.CCool C TestOff/OnOffS_COMP_Cforcibleforcible
F.SPDReduced Cool Fan Speed60 to 100%0S_FSPDCLforcibleforcible
OF.OVOutdoor Fan OverrideOff/OnOffS_OFC_OVforcibleforcible
HMZRTest HumidimizerTESTHMZR
RH1.AReheat1 A TestOff/OnOffS_RH1_Aforcibleforcible
RH1.BReheat1 B TestOff/OnOffS_RH1_Bforcibleforcible
RH1.CReheat1 C TestOff/OnOffS_RH1_Cforcibleforcible
RH2.AReheat2 A TestOff/OnOffS2_RH2_Aforcibleforcible
RH2.BReheat2 B TestOff/OnOffS2_RH2_Bforcibleforcible
RH2.CReheat2 C TestOff/OnOffS2_RH2_Cforcibleforcible
F.SPDReheat2 Fan Speed65 to 100%0S_FSPDRHforcibleforcible
CRCCool>Reheat1 Valve TestOff/OnOffS_CRCforcibleforcible
RHV.AReheat2 Valve A TestOff/OnOffS_RH2_Aforcibleforcible
RHV.BReheat2 Valve B,C TestOff/OnOffS_RH2_Bforcibleforcible
HEATTest HeatingTESTHEAT
HT.1Heat Stage 1 TestOff/OnOffS_HEAT_1forcibleforcible
HT.2Heat Stage 2 TestOff/OnOffS_HEAT_2forcibleforcible
F.SPDReduced Heat Fan Speed65 to 100%0S_FSPDHTforcibleforcible
Open
CloseS_OADMPRforcibleforcible
CCN TABLE/
SUB-TABLE
MAINTENANCE
DISPLAY
CCN POINT
CCN
WRITE
STATUS
DISPLAY
WRITE
STATUS
48/50PG and PM
MODE — TEMPERATURES
ITEMEXPANSIONRANGEUNITS
STATUS DISPLAY
TEMPERATURESUINPUT
AIR.TAir Temperatures
SATSupply Air Temperaturexxx.xdFSAT_DISP
OATOutdoor Air Temperaturexxx.xdFOA_TEMPforcibleforcible
SPTSpace Temperaturexxx.xdFSPACE_Tforcibleforcible
SPTOSpace Temperature Offsetxxx.xdFSPTOforcibleforcible
RATReturn Air Temperaturexxx.xdFRETURN_Tforcible
OCSPOccupied Cool Setpoint55 to 80°F78OCSP
UCSPUnoccupied Cool Setpoint65 to 95°F85UCSP
OHSPOccupied Heat Setpoint55 to 80°F68OHSP
UHSPUnoccupied Heat Setpoint40 to 80°F60UHSP
GAPHeatCool Setpoint Gap2 to 10^F5HCSP_GAP
STO.RSPT Offset Range (+/)0 to 5^F5SPTO_RNG
RH.SPSpace RH Occupied SP30 to 100%50SPRH_SP
RH.UNSpace RH Unoccupied SP30 to 100%50SPRH_USP
RH.DBSpace RH Deadband2 to 20%8SPRH_DB
RH.HBReheat Heat SP Deadband5 to 5^F2RH_HSPDB
CA.LOCircuit A Lockout Temp0 to 100°F0OATLCMPA
CB.LOCircuit B Lockout Temp0 to 100°F0: no HumidiMiZer FIOP
CC.LOCircuit C Lockout Temp0 to 100°F0OATLCMPC
HT.LOHeating Lockout Temp40 to 125°F75OATLHEAT
EH.LOEcono Cool Hi Temp Limit40 to 100°F65OATLECLH
EL.LOEcono Cool Lo Temp Limit 30 to 50°F0OATLECLL
FC.LOFree Cool Low Temp Limit 30 to 70°F50OATLUEFC
LCSPLow Cool SAT Setpoint55 to 75°F55 (0307)
IDFIndoor Fan StateOn/OffIDFSTATE
F.SPDCommanded Fan SpeedxxxFANSPEED
OFC.1Outdoor Fan 1 RelayOn/OffOFC_1
OFC.2Outdoor Fan 2 RelayOn/OffOFC_2
OFC.3Outdoor Fan 3 RelayOn/OffOFC_3