Carrier 50PG03-07 User Manual

Page 1
50PG03---07 Single Package Rooftop Units Electric Cooling with PURONR (R ---410A)
Refrigerant and COMFORTLinkt Controls
Installation Instructions
IMPORTANT: This installation instruction contains basic unit installation information including installation of field control devices. For information on unit start--up, service, and operation, refer to the unit Controls, Start-- Up, Operation, Service, and Troubleshooting Instructions also enclosed in the unit literature packet.
TABLE OF CONTENTS
SAFETY CONSIDERATIONS 1.........................
INSTALLATION 4....................................
Step 1 -- Provide unit Support 4.........................
Step 2 -- Rig and Place Unit 4...........................
Step 3 -- Field Fabricate Ductwork 7......................
Step 4 -- Make Unit Duct Connections 7...................
Step 5 -- Install External Trap for Condensate Drain 7........
Step 6 -- Make Electrical Connections 8...................
Step 7 -- Install Outdoor Air Hoods (Units With
Economizer 22...............................
Step 8 -- Install All Accessories 22.......................
SAFETY CONSIDERATIONS
Installation and servicing of air-conditioning equipment can be hazardous due to system pressure and electrical components. Only trained and qualified service personnel should install, repair, or service air-conditioning equipment.
Untrained personnel can perform the basic maintenance functions of cleaning coils and filters and replacing filters. All other operations should be performed by trained service personnel. When working on air-conditioning equipment, observe precautions in the literature, tags and labels attached to the unit, and other safety precautions that may apply.
Follow all safety codes. Wear safety glasses and work gloves. Recognize safety information. This is the safety--alert symbol
When you see this symbol on the unit and in instructions or manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, and CAUTION. These words are used with the safety--alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies a hazard which could result in personal injury or death. CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could cause personal injury or death.
Before performing service or maintenance operations on unit, turn off main power switch to unit and install lockout tag.
!
WARNING
UNIT OPERATION AND SAFETY HAZARD
Failure to follow this warning could cause personal injury, death and/or equipment damage.
Puron (R--410a) refrigerant systems operate at higher pressures than standard R--22 systems. Do not use R--22 service equipment or components on Puron refrigerant equipment.
!
WARNING
FIRE, EXPLOSION HAZARD
Failure to follow this warning could result in personal injury, death and/or property damage.
1. Improper installation, adjustment, alteration, service, or maintenance can cause property damage, personal
injury, or loss of life. Refer to the User’s Information
Manual provided with this unit for more details.
2. Do not store or use gasoline or other flammable
.
vapors and liquids in the vicinity of this or any other
appliance.
IMPORTANT: Units have high ambient operating limits. If limits are exceeded, the units will automatically lock the compressor out of operation. Manual reset will be required to restart the compressor.
Page 2
C07269
50PG03--07
Fig. 1 -- Roof Curb Details
2
Page 3
C07271
50PG03--07
Fig. 2 -- Base Unit Dimensions
3
Page 4
INSTALLATION
Step 1 — Provide Unit Support
Roof Curb
Assemble or install accessory roof curb in accordance with instructions shipped with this accessory. (See Fig. 1.) Install insulation, cant strips, roofing, and counter flashing as shown. Ductwork can be installed to roof curb before unit is set in place. Ductwork must be attached to curb and not to the unit. Curb must be level. This is necessary to permit unit drain to function properly. Unit leveling tolerance is 1/16--in. per linear ft in any direction. Refer to Accessory Roof Curb Installation Instructions for additional information as required. When accessory roof curb is used, unit may be installed on class A, B, or C roof covering material. Carrier roof curb accessories are for flat roofs or slab mounting.
IMPORTANT: The gasketing of theunit to the roof curb is critical for a watertight seal. Install gasket with the roof curb as shown in Fig. 1. Improperly applied gasket can also result in air leaks and poor unit performance. Do not slide unit to position on roof curb.
Alternate Unit Support
50PG03--07
When a curb cannot be used, install unit on a noncombustible surface. Support unit with sleepers, using unit curb support area. If sleepers cannot beused, support long sides of unit with a minimum of 3 equally spaced 4--in. x 4--in. pads on each side.
Step 2 — Rig and Place Unit
Inspect unit for transportation damage. See Table 1 for physical data. File any claim with transportation agency.
!
CAUTION
PERSONAL INJURY AND PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in damage to roof. All panels must be in place when rigging. Unit is not
designed for handling by fork truck.
Do not drop unit; keep upright. Use spreader bars over unit to prevent sling or cable damage. Rollers may be used to move unit across a roof. Level by using unit rail as a reference; leveling tolerance is ± 1/16--in. per linear ft in any direction. See Fig. 3 for additional information. Unit rigging weight is shown in Fig. 3.
Rigging holes are provided in the unit base rails as shown in Fig. 3. Refer to rigging instructions on unit.
Positioning
Maintain clearance, per Fig. 2, around and above unit to provide minimum distance from combustible materials, proper airflow, and service access. See Fig. 4 for location of access panels.
Do not install unit in an indoor location. Do not locate air inlets near exhaust vents or other sources of contaminated air.
Although unit is weatherproof, guard against water from higher level runoff and overhangs.
After unit is in position, remove crating and polyethylene sheet.
Roof Mount
Check building codes for weight distribution requirements. Unit operating weight is shown in Table 1.
Installation Onto Curb
The 50PG units are designed to fit on the accessory full perimeter curb. In either case, correct placement of the unit onto the curb is critical to operating performance. To aid in correct positioning, place unit on roof curb to maintain 1/4--in. gap between the inside of rail and roof curb on long sides and a 1/2--in. gap between the inside of rail and roof curb on both duct and condenser ends. Refer to Fig. 1 and 3, to assure proper duct opening alignment.
NOTE: Before positioning unit onto curb, refer to Step 5 -- Install External Trap for Condensate Drain section concerning bottom drain connection plug.
!
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage.
Do not slide unit to position when it is sitting on the curb. Curb gasketing material may be damaged and leaks may result.
Slab Mount (Horizontal Units Only)
Provide a level concrete slab that extends a minimum of 6--in. beyond unit cabinet. Install a gravel apron in front of condenser--coil air inlet to prevent grass and foliage from obstructing airflow.
NOTE: Horizontal units may be installed on a roof curb if required.
CAU OTI
ACCESS PANEL MUST BE IN PLACE WHEN RIGGING.
Hook rigging shackles through holes in base rail, as shown in Detail A. Holes in base rails are centered around the unit center of gravity. Use wooden top skid, when rigging, to prevent rigging straps from damaging unit.
A B C D E MAX. WEIGHT
UNIT SIZE
in. mm in. mm in. mm in. mm in. mm lb kg
03-07 77.9 1978 36-54 914-1371 44.8 1139 42.0 1067 23.5 597 1156 52
N- NOTICE TO R GGERS:I
Fig. 3 -- 50PG Rigging Label
4
5
C07270
Page 5
Table 1 – Physical Data
BASE UNIT 50PG 03 04 05 06 07 NOMINAL CAPACITY (Tons) OPERATING WEIGHT (lb)
Unit* Economizer
Vert ical Horizontal
Humidi-MiZerAdaptive Dehumidification
System
Roof Curb
14-in. 24-in.
COMPRESSOR
Quantity Oil Type Number of Refrigerant Circuits Oil (o z )
REFRIGERANT TYPE
Expansion Device Operating Charge (lb) — Standard Unit Operating Charge (lb) — Unit with
Humidi-MiZer System CONDENSER COIL
Condenser A (Outer)
Rows...Fins/in. Face A rea (s q ft)
Condenser B (Inner)
Rows...Fins/in. Face A rea (s q ft)
Humidi-MiZer Coil
Rows...Fins/in. Face A rea (s q ft)
CONDENSER FAN
QuantityDiameter (in.) Nominal Cfm (Total, all fans) Motor Hp
Nominal Rpm — High Speed
Nominal Rpm — Low Speed
EVAPORATOR COIL
RowsFins/in. Face A rea (s q ft)
* See Legend on next page.
2 3 4 5 6
704 704 775 829 874
40 40 40 40 40 50 50 50 50 50
22
22 31 27 26
122 122 122 122 122 184 184 184 184 184
Fully Hermetic Scroll
1 1 1 1 1
Copeland 3MA
1 1 1 1 1
38 42 42 66 56
R-410A (Puron® Refrigerant)
TXV TXV TXV TXV TXV
7.3 9.0 15.7 16.6 19.0
11.75 13.50 25.00 22.00 22.70
Enhanced Copper Tubes, Aluminum Lanced Fins
117 117 217 217 217
12.6 12.6 12.6 12.6 12.6
117 217 217 217 — 12.6 12.6 12.6 12.6
1...17 1...17 1...17 1...17 1...17
6.4 6.4 9.3 9.3 9.3 Propeller
124 124 124 124 124
3500 3500 3500 4500 4500
1
/
8
825 825 825 1100 1100
1
/
8
1
/
8
1
/
4
300 300 300 300 300
Enhanced Copper Tubes, Aluminum Double-Wavy Fins, Face Split
215 215 215 315 415
9.3 9.3 9.3 9.3 9.3
50PG03--07
1
/
4
5
Page 6
BASE UNIT 50PG (co nt) 03 04 05 06 07 EVAPORATOR FAN
QuantitySize (in.) Low
Ty pe D ri ve Low
Nominal Cfm Maximum Continuous Bhp Low
Motor Nominal Rpm Motor Frame Size Low
Fan Rp m Range Low
Motor Bearing Type Maximum Fan Rpm Motor Pulley Pitch Diameter Range (in.) Low
Fan Pulley Pitch Diameter (in.) Low
Nominal Motor Shaft Diameter (in.) Low
Belt...PitchLength(in.)
BeltTy pe Low
50PG03--07
Pulley Center L ine Distance Min. (in.) Low
Pulley Center Line Distance Max. (in.) Low
Speed Change per Full Turn of
Movable Pulley Flange (rpm)
Movable Pulley Maximum Full
Turns from Closed Position
FactoryPulleySetting(rpm) Low
Fan Shaft Diameter at Pulley (in.)
HIGH-PRESSURE SWITCH (psig)
Cutout Reset (Auto.)
RETURN-AIR FILTERS
QuantitySize (in.)
LEGEND TXV --- Thermostatic Expansion Valve * Aluminum evaporator coil/aluminum condenser coil. { Single phase/three phase.
Table 1 — Physical Data (cont)
High
High
High
High
High
High
High
High
Low
High
High
High
High Low High Low High
High
1...12 x 9
1...12 x 9 Belt Belt 800 1200 1600 2000 2400
0.85
0.85
1620 1620 1620 1725 1725
48Y 48Y
482-736
656-1001
Ball Ball Ball Ball Ball
2000 2000 2000 2000 2000
1.9-2.9
1.9-2.9
6.8
5.0
1
/
2
1
/
2
49.3 49.3 49.3 49.3 49.3
49.3 AX AX
16.2
16.2
20.2
20.2
48 65
5
5 482 656
3
/
4
660 ± 10 660 ± 10 660 ± 10 660 ± 10 660 ± 10 505 ± 20 505 ± 20 505 ± 20 505 ± 20 505 ± 20
416 x 20 x 2 416 x 20 x 2 416 x 20 x 2 416 x 20 x 2 416 x 20 x 2
1...12 x 9 1...12 x 9 1...12 x 9 1...12 x 9
Centrifugal Type, Belt Drive
1...12 x 9 1...12 x 9 1...12 x 9 1...12 x 9 Belt Belt Belt Belt Belt Belt Belt Belt
0.85 0.85 0.85/2.40† 2.40
0.85 1.60/2.40† 1.60/2.40† 3.10
48Y 48Y 56Y 56Y 48Y 56Y 56Y 56Y
482-736 596-910 690-978 796-1128
796-1128 828-1173 929-1261 1150-1438
1.9-2.9 1.9-2.9 2.4-3.4 2.4-3.4
2.4-3.4 2.4-3.4 2.8-3.8 4.0-5.0
6.8 5.5 6.0 5.2
5.2 5.0 5.2 6.0
1
/
2
1
/
2
1
/
2
5
/
8
5
/
8
5
/
8
5
/
8
7
/
8
49.3 49.3 49.3 52.3 AX AX AX AX AX AX AX AX
16.2 16.2 16.2 16.2
16.2 16.2 16.2 16.2
20.2 20.2 20.2 20.2
20.2 20.2 20.2 20.2
48 59 58 66 62 69 66 58
5 5 5 5
5 5 5 5 482 596 690 796 796 828 929 1150
3
/
4
3
/
4
3
/
4
3
/
4
Throwaway
6
Page 7
Step 3 — Field Fabricate Ductwork
On vertical units, secure all ducts to roof curb and building structure. Do not connect ductwork to unit. For horizontal applications, field--supplied flanges should be attached to horizontal discharge openings and all ductwork secured to the flanges. Insulate and weatherproof all external ductwork, joints, and roof openings with counter flashing and mastic in accordance with applicable codes.
Ducts passing through an unconditioned space must be insulated and covered with a vapor barrier.
If a plenum return is used on a vertical unit, the return should be ducted through the roof deck to comply with applicable fire codes.
A minimum clearance is not required around ductwork. Cabinet return--air static pressure (a negative condition) shall not exceed
0.35--in. wg with economizer or 0.45--in. wg without economizer.
Step 4 — Make Unit Duct Connections
Vertical Supply/Return Configuration
Unit is shipped in vertical supply/return configuration. Ductwork openings are shown in Fig. 1 and 3. Attach the ductwork to the roof curb. Do not attach duct directly to the unit.
!
WARNING
PERSONAL INJURY HAZARD
Failure to follow this warning could result in personal injury.
For vertical supply and return units, tools or parts could drop into ductwork and cause an injury. Install a 90--degree turn in the return ductwork between the unit and the conditioned space. If a 90--degree elbow cannot be installed, then a grille of sufficient strength and density should be installed to prevent objects from falling into the conditioned space.
Horizontal Supply/Return Applications
Unit can be field--converted from vertical supply/return to horizontal supply/return. Remove all screws securing horizontal
CONTROL BOX AND COMPRESSOR
ELECTRICAL
OPTIONS PANEL
duct covers to duct panel. Save panels. Install duct covers in the vertical duct openings in the basepan with the insulation side up. Covers will drop into openings and can be secured using field--supplied self--tapping screws. Ductwork can be attached to duct flanges provided on unit. When securing ductwork to unit, do not drill in area below bead or above top edge of duct opening.
Step 5 — Install External Trap for Condensate Drain
The unit’s 3/4--in. condensate drain connections are located on the bottom and side of the unit. If the down drain is used, drill a minimum of a 5/8-in. diameter hole but not larger than a diameter hole through the drain pan. A dimple of 2 mm in diameter and 1.5 mm deep will be provided in the drain pan to help locate the drill bit and to start the hole. Do not cut through the PVC pipe threads. Unit discharge connections do not determine the use of drain connections; either drain connection can be used with vertical or horizontal applications. See Fig. 2 for locations.
When using the standard side drain connection, make sure the plug (red) in the alternate bottom connection is tight before installing the unit. (See Fig. 5.)
To use the bottom drain connection for a roof curb installation, relocate the factory--installed plug (red) from the bottom connection to the side connection. A 1/2--in. socket extension can be used to remove the plug. (See Fig. 5.) The piping for the condensate drain and external trap can be completed after the unit is in place.
All units must have an external trap for condensate drainage. Install a trap at least 4--in. deep and protect against freezeup. If drain line is installed downstream from the external trap, pitch the line away from the unit at 1--in. per 10 ft of run. Do not use a pipe size smaller than the unit connection (3/4--in.). (See Fig. 6 and 7.)
The 50PG units are provided with a removable condensate pan for ease of cleaning. It is recommended that a union be placed between the unit and condensate drainage to ease the removal of the pan during servicing. Adequate clearance should be allowed if removal of condensate pan is required. Allow 54--in. between condensate pan access panel and any obstruction for complete removal.
INDOOR MOTOR ACCESS DOOR
3
/4-in.
50PG03--07
OUTDOOR AIR SCREEN (HIDDEN)
ECONOMIZER HOOD
BAROMETRIC RELIEF DAMPER HOOD
BASEPAN CONNECTIONS
ACCESS PANEL
Fig. 4 -- Panel and Filter Locations
FILTER ACCESS DOOR
7
ELECTRIC HEAT ACCESS DOOR
CONDENSER COIL
ACCESS PANEL
C07272
Page 8
INSERT SIDE DRAIN
A
PLUG FOR DOWN DRAIN USE.
DRILL 5/8” DIA. (0.625 mm) HOLE THRU FOR DOWN DRAIN USE.
C10321
Fig. 5 -- Condensate Drain Pan
OPTIONAL UNIONS
TO ALLOW FOR CONDENSATE
PAN REMOVAL
50PG03--07
4" (102mm)
CONDENSATE
PAN ACCESS
PANEL
Fig. 6 -- External Trap for Condensate Drain
NOTE: Trap should be deep enough to offset maximum unit static difference.
4-in. trap is recommended.
C06291
Fig. 7 -- Condensate Drain Piping Details
C06234
Step 6 — Make Electrical Connections
(For more details, refer to the Controls, Start--up, Operation, and Troubleshooting manual).
Field Power Supply
All 208/230--v units are factory wired for 230--v power supply. If the 208/230--v unit is to be connected to a 208--v power supply, the transformers (TRAN1 and TRAN2) must be rewired by moving the black wire with the 1/4--in. female quick connect from the 230--volt connection and moving to the 200--volt 1/4--in. male terminal on the primary side of the transformer.
Refer to unit label diagram for additional information. Leads are provided for field wire connections. Use UL (Underwriters Laboratories) approved copper/aluminum connector.
When installing rooftop units, provide safety disconnect per NEC (National Electrical Code) Article 440 or local codes. For non--fused disconnects, size the disconnect according to the sizing data provided in the electrical data tables. If a fused disconnect is used, determine the minimum size for the switch based on the disconnect sizing data provided in the electrical data tables and then coordinate the disconnect housing size to accommodate the Maximum Overcurrent Protection (MOCP) device size as marked on the unit informative plate. (See Table 2 and 3.) All field wiring must comply with NEC and local codes. Size wire based on MCA (Minimum Circuit Amps) on the unit informative plate. See Fig. 8 for power wiring connection to the unit leads and equipment ground.
Route power and ground lines through control box end panel or unit basepan (see Fig. 2) to connections as shown on unit wiring diagram and Fig. 8. Factory leads may be wired directly to the disconnect.
8
Page 9
!
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage.
The correct power phasing is critical to the operation of the scroll compressors. An incorrect phasing will result in an alarm being generated and compressor operation lockout. Should this occur, power phase correction must be made to the incoming power. Damage to compressor could result.
Set heat anticipator settings as follows:
VOLTAGE
All 0.2 0.4
Stage 1
(W1) ON
STAGE 1 AND 2
(W1 AND W2) ON
Settings may be changed slightly to provide a greater degree of comfort for a particular installation.
C.A1
FIELD
POWER
WIRING
FACTOR
POWER
WIRING
21
11
12
22
23
13
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Unit cabinet must have an uninterrupted, unbroken electrical ground to minimize the possibility of personal injury if an electrical fault should occur. This ground may consist of electrical wire connected to unit ground lug in control compartment, or conduit approved for electrical ground when installed in accordance with NEC; ANSI (American National Standards Institute)/NFPA (National Fire Protection Association), latest edition, and local electrical codes.
Field wiring must conform to temperature limitations for type “T” wire. All field wiring must comply with NEC and local requirements.
Operating voltage to compressor must be within voltage range indicated on unit nameplate. On 3--phase units, voltages between phases must be balanced within 2%.
Unit failure as a result of operation on improper line voltage or excessive phase imbalance constitutes abuse and may cause damage to electrical components.
Field Control Wiring (Units Without Optional Humidi--MiZer
Unit can be controlled with either a Carrier--approved accessory thermostat or a Carrier--approved space temperature sensor. Install thermostat according to the installation instructions included with accessory. Locate thermostat assembly or space temperature sensor on a solid interior wall in the conditioned space to sense average temperature.
Route thermostat or space temperature sensor cable or equivalent single leads of colored wire from subbase terminals through conduit into unit to low--voltage connections as shown on unit label wiring diagram and in Fig. 9 or 10.
NOTE: For wire runs up to 50 ft, use no. 18 AWG (American Wire Gauge) insulated wire (35_C minimum). For 50 to 75 ft, use no. 16 AWG insulated wire (35_C minimum). For over 75 ft, use no. 14 AWG insulated wire (35_C Minimum). All wire larger than no. 18 AWG cannot be directly connected at the thermostat and will require a junction box and splice at the thermostat.
t Adaptive Dehumidification System)
PER NEC
DISCONNECT
EQUIP GND
LEGEND
C.A1 -- Compressor Contactor (A1) EQUIP -- Equipment GND -- Ground NEC -- National Electrical Code
NOTE: The maximum wire size for C.A1 is 2/0.
C06237
Fig. 8 -- Field Power Wiring Connections
THERMOSTAT ASSEMB Y
REMOVABLE JUMPER
TB1
RH
Y1 Y2
RC
R
Y1 Y2
W1 W2 G CLX
W1 W2 G C X
ROOFTOP UNIT
C06292
Fig. 9 -- Field Control Thermostat Wiring
SEN
WHITE
T-56 SPT
SET
JUMPER
C06239
T55 TB1
T-55 SPT
SEN
RED
BLACK
RED
12 3
BLACK
ROOFTOP UNIT
Fig. 10 -- Field Control Space Temperature Sensor Wiring
Field Control Wiring (Units With Optional Humidi--
t Adaptive Dehumidification System)
MiZer
Units require temperature control inputs for cooling and heating operation and humidity control inputs for Humidi--MiZer operation.
50PG03--07
9
Page 10
Temperature Control
The unit can be controlled with either a Carrier--approved space temperature sensor, a Carrier accessory Thermidistatt device, or a Carrier--approved accessory thermostat. Install the temperature control device according to the installation instructions included with the accessory. Locate the device on a solid interior wall in the conditioned space to sense average temperature. Carrier space temperature sensor wiring connections are shown in Fig. 10. General thermostat field control wiring connections are shown in Fig. 9. Carrier Thermidistat device wiring connections are shown in Fig. 11. Configuration of the unit control is required to specify the control input type before unit operation.
Route thermostat or space temperature sensor cable or equivalent single leads of colored wire from subbase terminals through conduit into unit to low--voltage connections as shown on unit label wiring diagram and in Fig. 9--11.
NOTE: For wire runs up to 50 ft, use no. 18 AWG (American Wire Gauge) insulated wire (35_C minimum). For 50 to 75 ft, use no. 16 AWG insulated wire (35_C minimum). For over 75 ft, use no. 14 AWG insulated wire (35_C Minimum). All wire larger than no. 18 AWG cannot be directly connected at the thermostat and will require a junction box and splice at the thermostat.
50PG03--07
Set heat anticipator settings as follows:
VOLTAGE
All 0.2 0.4
Stage 1
(W1) ON
STAGE 1 AND 2
(W1 AND W2) ON
Settingsmay be changed slightly to provide a greater degree of comfort for a particular installation.
Humidity Control
Unit can be controlled with either a Carrier accessory Thermidistat device or a Carrier--approved accessory humidistat (switch output). The input for an accessory humidity sensor with 4 to 20 mA output is another option available when an economizer board is installed. Install the humidity control device according to the installation instructions included with the accessory. Locate the device on a solid interior wall in the conditioned space to sense average humidity. Carrier Thermidistat device wiring connections are shown in Fig. 11. General humidistat wiring connections are shown in Fig. 12. Configuration of the unit control is required to specify the control input type before unit operation. Refer to the
Controls, Start--up, Operation and Troubleshooting manual for configuration.
Units with the Humidi--MiZert option receive a discrete input from a field--installed device (such as from the Carrier humidistat or Thermidistat device). The discrete input is connected to the TB1 terminal strip points labeled Humidistat 1 and 2. As this is a discrete input, one of the connection points is for power to the switch and the other is the return path. (See Fig. 12.)
A space relative humidity sensor input (SP.RH) is only available if an economizer board (ECB) is installed in the unit and then the sensor can be connected to the OAQ point TB1--4. (See Fig. 12.) This input is used instead of the discrete humidistat or thermidistat inputs. The input controls the Humidi--MiZer using the 4 to 20 mA as percent humidity. The relative humidity value (measured by the relative humidity sensor) can be displayed on the Scrolling Marquee, in the space through a System Pilott device, or can be read by other CCN devices where it can be used to perform more advanced functions. The humidity sensor must be configured correctly; refer to the Controls, Start--up, Operation, and Troubleshooting manual for details.
If the customer also wishes to install a smoke detector into a Humidi--MiZer equipped 50PG unit, the fire shutdown connection points are on Plug PL--19, located in the economizer section. See the unit wiring schematic for wiring. For third--party smoke detector, see Fig. 13.
Point 19--3 is the 24 vac power source for the detector and point 19--5 is the 24 vac signal input for fire shutdown.
More information is available in the third party control section of the Controls, Start--up, Operation, and Troubleshooting manual.
THERMIDISTAT
DEHUM
1
HUMIDISTAT
2
C07055
TB1
OC
5
RY1
R
Y1
Y2
Y2
W2
W1
W2
W1
ROOFTOP UNIT
G
C
C
G
Fig. 11 -- Field Control Thermidistat Wiring
Fig. 12 -- Humidi--MiZer Low--Voltage Terminal Strip -- Humidity Sensor/Humidity Wiring
10
C07045
Page 11
Fig. 13 -- Third Party Smoke Detector on Humidi--MiZert
50PG03--07
C07191
11
Page 12
Table 2 – Electrical Data -- Units Without Optional Convenience Outlet
UNIT
50PG
03
NOMINAL
POWER SUPPLY
Volt s-Ph- Hz
208/230-1-60 187 253 12.8 60 1.0
VOLTAGE
RANGE
COMPRESSOR
Min Max RLA LRA FLA
50PG03--07
208/230-1-60 187 253 15.4 83 1.0
04
208/230-3-60 187 253 11.5 77 1.0
FLA --- Fu l l Lo a d A mps HACR --- Heating, Air Conditioning and Refrigeration IFM --- Indoor (Evaporator) Fan Motor LRA --- L oc k ed Rot o r A mp s MCA --- Minimum Circuit Amps MOCP --- M aximum Overcurrent Protection NEC --- Natio nal Electrical Code OFM --- Outdoor (Condenser) Fan Motor RLA --- RatedLoadAmps
*Heater capacity (kW) is based o n heater voltage of 208v, 240v, 480v, or 600v. If power distribution voltage to unit varies from rated heater voltage, heater kW will vary accord­ingly. { Fuse or HACR ci rcuit breaker.
NOTES:
1. In comp liance with NE C require ments for multim otor and combin a tion load equip ment (refe r
2. Unbalanced 3- Phase Supply Voltage
% Voltage Imbalance = 100 x
LEGEND
to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. Canadian units may be fuse or circuit breaker.
Never operate a motor where a phase imb alance in supply voltage is greater than 2%.Use the following formula to deter mine the percentage of voltage imb alance.
max voltage deviation from average voltage
averag e voltage
OFM
FLA
POWER
EXHAUST
FLA
1.4
—-
1.4
IFM
TYPE
Low
High
Low
High
Low
High
Low
High
Low
High
E xa mp le : S up p ly v ol ta ge i s 2 3 0 --- 3 ---6 0
Determine maxim um deviation from average voltage. (AB) 227 – 224 = 3 v (BC) 231 – 227 = 4 v (AC) 227 – 226 = 1 v Maximum deviation is 4 v. Deter mine per cent of voltage imbalance .
% Voltage Imbalance = 100 x
This amou nt of phase im balance is satisfactor y as it is be low the maxim um allowable 2%. IMPORTANT: If the supply voltage phase imb alance is more than 2 %, contact your local el ectric utility company immed iately.
ELECTRIC HEAT POWER SUPPLY
IFM FLA
10.8/12.5 2.3/ 3.0 21.9/21.9 25/25 22/22 74/74
17.3/20.0 3.8/ 5.0 27.8/31.1 30/35 26/29 74/74
26.0/30.0 5.6/ 7.5 38.6/43.6 40/45 36/40 74/74
34.7/40.0 7.5/10.0 49.5/56.1 50/60 46/52 74/74
10.8/12.5 2.3/ 3.0 21.9/21.9 25/25 22/22 74/74
17.3/20.0 3.8/ 5.0 27.8/31.1 30/35 26/29 74/74
26.0/30.0 5.6/ 7.5 38.6/43.6 40/45 36/40 74/74
34.7/40.0 7.5/10.0 49.5/56.1 50/60 46/52 74/74
4.9
10.8/12.5 2.3/ 3.0 23.3/23.5 25/25 23/23 76/76
17.3/20.0 3.8/ 5.0 29.5/32.9 30/35 27/30 76/76
26.0/30.0 5.6/ 7.5 40.4/45.4 45/50 37/42 76/76
34.7/40.0 7.5/10.0 51.3/57.9 60/60 47/53 76/76
10.8/12.5 2.3/ 3.0 23.3/23.5 25/25 23/23 76/76
17.3/20.0 3.8/ 5.0 29.5/32.9 30/35 27/30 76/76
26.0/30.0 5.6/ 7.5 40.4/45.4 45/50 37/42 76/76
34.7/40.0 7.5/10.0 51.3/57.9 60/60 47/53 76/76
10.8/12.5 2.3/ 3.0 25.2/25.2 30/30 24/24 97/97
17.3/20.0 3.8/ 5.0 27.8/31.1 30/35 26/29 97/97
26.0/30.0 5.6/ 7.5 38.6/43.6 40/45 36/40 97/97
34.7/40.0 7.5/10.0 49.5/56.1 50/60 46/52 97/97
52.0/60.0 11.3/15.0 71.1/81.1 80/90 65/75 97/97
10.8/12.5 2.3/ 3.0 25.2/25.2 30/30 24/24 97/97
17.3/20.0 3.8/ 5.0 27.8/31.1 30/35 26/29 97/97
26.0/30.0 5.6/ 7.5 38.6/43.6 40/45 36/40 97/97
34.7/40.0 7.5/10.0 49.5/56.1 50/60 46/52 97/97
52.0/60.0 11.3/15.0 71.1/81.1 80/90 65/75 97/97
4.9
10.8/12.5 2.3/ 3.0 26.6/26.6 30/30 26/26 99/99
17.3/20.0 3.8/ 5.0 29.5/32.9 30/35 27/30 99/99
26.0/30.0 5.6/ 7.5 40.4/45.4 45/50 37/42 99/99
34.7/40.0 7.5/10.0 51.3/57.9 60/60 47/53 99/99
52.0/60.0 11.3/15.0 72.9/82.9 80/90 67/76 99/99
10.8/12.5 2.3/ 3.0 26.6/26.6 30/30 26/26 99/99
17.3/20.0 3.8/ 5.0 29.5/32.9 30/35 27/30 99/99
26.0/30.0 5.6/ 7.5 40.4/45.4 45/50 37/42 99/99
34.7/40.0 7.5/10.0 51.3/57.9 60/60 47/53 99/99
52.0/60.0 11.3/15.0 72.9/82.9 80/90 67/76 99/99
6.3/ 7.2 2.3/ 3.0 20.3/20.3 25/25 20/20 91/91
10.0/11.5 3.8/ 5.0 20.3/20.5 25/25 20/20 91/91
15.0/17.3 5.6/ 7.5 24.9/27.8 25/30 23/26 91/91
20.0/23.1 7.5/10.0 31.1/35.0 35/40 29/32 91/91
30.0/34.6 11.3/15.0 43.6/49.4 45/50 40/45 91/91
4.9
6.3/ 7.2 2.3/ 3.0 20.3/20.3 25/25 20/20 91/91
10.0/11.5 3.8/ 5.0 20.3/20.5 25/25 20/20 91/91
15.0/17.3 5.6/ 7.5 24.9/27.8 25/30 23/26 91/91
20.0/23.1 7.5/10.0 31.1/35.0 35/40 29/32 91/91
30.0/34.6 11.3/15.0 43.6/49.4 45/50 40/45 91/91
Nominal
kW*
MCA MOCP† FLA LRA
21.9/21.9 25/25 22/22 74/74
21.9/21.9 25/25 22/22 74/74
23.3/23.3 25/25 23/23 76/76
23.3/23.3 25/25 23/23 76/76
25.2/25.2 30/30 24/24 97/97
25.2/25.2 30/30 24/24 97/97
26.6/26.6 30/30 26/26 99/99
26.6/26.6 30/30 26/26 99/99
20.3/20.3 25/25 20/20 91/91
20.3/20.3 25/25 20/20 91/91
AB = 224 v BC = 231 v AC = 226 v
Average Voltage =
= 1.76%
224 + 231 + 226
681
=
=
227
3
3
4
227
DISCONNECT
SIZE
12
Page 13
NOMINAL
POWER SUPPLY
UNIT
50PG
(cont)
Volts -Ph-Hz
208/230-3-60 187 253 11.5 77 1.0 1.4
04
460-3-60 414 506 5.1 35 0.5
575-3-60 518 633 4.3 31 0.5
208/230-1-60 187 253 20.5 109 1.0
05
208/230-3-60 187 253 14.6 91 1.0
*See Legend on next page.
Table 2 -- Electrical Data -- Units Without Optional Convenience Outlet (cont)
VOLTAGE
RANGE
Min Max RLA LRA FLA
COMPRESSOR
OFM
FLA
POWER
EXHAUST
FLA
0.6
1.4
1.4
IFM
TYPE
Low
High
Low
High
Low
High
Low
High
Low
High
Low 4.9
High 7.0
Low 4.9
High 7.0
Low 4.9
High 5.2
Low 4.9
High 5.2
ELECTRIC HEAT POWER SUPPLY
IFM
FLA
6.3/ 7.2 2.3/ 3.0 21.7/21.7 25/25 22/22 93/93
10.0/11.5 3.8/ 5.0 21.7/22.3 25/25 22/22 93/93
15.0/17.3 5.6/ 7.5 26.6/29.5 30/30 24/27 93/93
20.0/23.1 7.5/10.0 32.9/36.8 35/40 30/34 93/93
30.0/34.6 11.3/15.0 45.4/51.1 50/60 42/47 93/93
4.9
6.3/ 7.2 2.3/ 3.0 21.7/21.7 25/25 22/22 93/93
10.0/11.5 3.8/ 5.0 21.7/22.3 25/25 22/22 93/93
15.0/17.3 5.6/ 7.5 26.6/29.5 30/30 24/27 93/93
20.0/23.1 7.5/10.0 32.9/36.8 35/40 30/34 93/93
30.0/34.6 11.3/15.0 45.4/51.1 50/60 42/47 93/93
11.5 10.0 17.0 20 16 42
17.3 15.0 24.3 25 22 42
11.5 10.0 17.0 20 16 42
2.1
2.1
17.3 15.0 24.3 25 22 42
11.5 10.0 17.8 20 16 43
17.3 15.0 25.0 30 23 43
11.5 10.0 17.8 20 16 43
17.3 15.0 25.0 30 23 43
13.9 15.0 20.0 25 18 37
13.9 15.0 20.0 25 18 37
13.9 15.0 21.8 25 20 39
13.9 15.0 21.8 25 20 39
17.3/20.0 3.8/ 5.0 31.5/ 31.5 35/ 35 30/30 123/123
26.0/30.0 5.6/ 7.5 38.6/ 43.6 40/ 45 36/40 123/123
34.7/40.0 7.5/10.0 49.5/ 56.1 50/ 60 46/52 123/123
52.0/60.0 11.3/15.0 71.1/ 81.1 80/ 90 65/75 123/123
69.3/80.0 15.0/20.0 92.8/106.1 100/110 85/98 123/ 123
17.3/20.0 3.8/ 5.0 33.6/ 33.8 35/ 35 33/ 33 148/148
26.0/30.0 5.6/ 7.5 41.3/ 46.3 45/ 50 38/ 43 148/148
34.7/40.0 7.5/10.0 52.1/ 58.8 60/ 60 48/ 54 148/148
52.0/60.0 11.3/15.0 73.8/ 83.8 80/ 90 68/ 77 148/148
69.3/80.0 15.0/20.0 95.4/108.8 100/110 88/100 148/148
17.3/20.0 3.8/ 5.0 32.9/ 32.9 35/ 35 32/32 125/125
26.0/30.0 5.6/ 7.5 40.4/ 45.4 45/ 50 37/42 125/125
34.7/40.0 7.5/10.0 51.3/ 57.9 60/ 60 47/53 125/125
52.0/60.0 11.3/15.0 72.9/ 82.9 80/ 90 67/76 125/125
69.3/80.0 15.0/20.0 94.5/107.9 100/110 87/99 125/ 125
17.3/20.0 3.8/ 5.0 35.0/ 35.5 40/ 40 34/ 34 150/150
26.0/30.0 5.6/ 7.5 43.0/ 48.0 45/ 50 40/ 44 150/150
34.7/40.0 7.5/10.0 53.9/ 60.5 60/ 70 50/ 56 150/150
52.0/60.0 11.3/15.0 75.5/ 85.5 80/ 90 69/ 79 150/150
69.3/80.0 15.0/20.0 97.1/110.5 100/125 89/102 150/150
10.0/11.5 3.8/ 5.0 24.2/24.2 25/25 24/24 105/105
15.0/17.3 5.6/ 7.5 24.9/27.8 25/30 24/26 105/105
20.0/23.1 7.5/10.0 31.1/35.0 35/40 29/32 105/105
30.0/34.6 11.3/15.0 43.6/49.4 45/50 40/45 105/105
40.0/46.2 15.0/20.0 56.1/63.9 60/70 52/59 105/105
10.0/11.5 3.8/ 5.0 24.5/24.5 25/25 24/24 123/123
15.0/17.3 5.6/ 7.5 25.3/28.1 30/30 24/26 123/123
20.0/23.1 7.5/10.0 31.5/35.4 35/40 29/33 123/123
30.0/34.6 11.3/15.0 44.0/49.8 45/50 40/46 123/123
40.0/46.2 15.0/20.0 56.5/64.3 60/70 52/59 123/123
10.0/11.5 3.8/ 5.0 25.6/25.6 30/30 25/25 107/107
15.0/17.3 5.6/ 7.5 26.6/29.5 30/30 25/27 107/107
20.0/23.1 7.5/10.0 32.9/36.8 35/40 30/34 107/107
30.0/34.6 11.3/15.0 45.4/51.1 50/60 42/47 107/107
40.0/46.2 15.0/20.0 57.9/65.6 60/70 53/60 107/107
10.0/11.5 3.8/ 5.0 25.9/25.9 30/30 26/26 125/125
15.0/17.3 5.6/ 7.5 27.0/29.9 30/30 26/27 125/125
20.0/23.1 7.5/10.0 33.3/37.1 35/40 31/34 125/125
30.0/34.6 11.3/15.0 45.8/51.5 50/60 42/47 125/125
40.0/46.2 15.0/20.0 58.3/66.0 60/70 54/61 125/125
Nominal
21.7/21.7 25/25 22/22 93/93
21.7/21.7 25/25 22/22 93/93
9.0 15 9 42
3.5 3.0 9.0 15 9 42
5.8 5.0 9.9 15 9 42
8.7 7.5 13.5 15 12 42
9.0 15 9 42
3.5 3.0 9.0 15 9 42
5.8 5.0 9.9 15 9 42
8.7 7.5 13.5 15 12 42
9.6 15 10 43
3.5 3.0 9.6 15 10 43
5.8 5.0 10.6 15 10 43
8.7 7.5 14.3 15 13 43
9.6 15 10 43
3.5 3.0 9.6 15 10 43
5.8 5.0 10.6 15 10 43
8.7 7.5 14.3 15 13 43
8.0 15 8 37
9.2 10.0 14.1 15 13 37
8.0 15 8 37
9.2 10.0 14.1 15 13 37
9.4 15 10 39
9.2 10.0 15.9 20 15 39
9.4 15 10 39
9.2 10.0 15.9 20 15 39
31.5/ 31.5 35/ 35 30/30 123/123
33.6/ 33.6 35/ 35 33/ 33 148/148
32.9/ 32.9 35/ 35 32/32 125/125
35.0/ 35.5 40/ 40 34/ 34 150/150
24.2/24.2 25/25 24/24 105/105
24.5/24.5 25/25 24/24 123/123
25.6/25.6 30/30 25/25 107/107
25.9/25.9 30/30 26/26 125/125
kW*
DISCONNECT
SIZE
MCA MOCP† FLA LRA
50PG03--07
13
Page 14
Table 2 -- Electrical Data -- Units Without Optional Convenience Outlet (cont)
UNIT
50PG
05
(cont)
NOMINAL
POWER SUPPLY
Volts -Ph-Hz
460-3-60 414 506 7.1 46 0.5
VOLTAGE
RANGE
COMPRESSOR
Min Max RLA LRA FLA
50PG03--07
575-3-60 518 633 5.1 34 0.5
06
208/230-1-60 187 253 26.9 145 1.5
FLA --- Fu l l Lo a d A mps HACR --- Heating, Air Conditioning and Refrigeration IFM --- Indoor (Evaporator) Fan Motor LRA --- L oc k ed Rot o r A mp s MCA --- Minimum Circuit Amps MOCP --- M aximum Overcurrent Protection NEC --- Natio nal Electrical Code OFM --- Outdoor (Condenser) Fan Motor RLA --- RatedLoadAmps
*Heater capacity (kW) is based o n heater voltage of 208v, 240v, 480v, or 600v. If power distribution voltage to unit varies from rated heater voltage, heater kW will vary accord­ingly. { Fuse or HACR ci rcuit breaker.
NOTES:
1. In comp liance with NE C require ments for multim otor and combin a tion load equip ment (refe r
2. Unbalanced 3- Phase Supply Voltage
% Voltage Imbalance = 100 x
LEGEND
to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. Canadian units may be fuse or circuit breaker.
Never operate a motor where a phase imb alance in supply voltage is greater than 2%.Use the following formula to deter mine the percentage of voltage imb alance.
max voltage deviation from average voltage
averag e voltage
OFM
FLA
POWER
EXHAUST
FLA
0.6
1.4
1.4
IFM
TYPE
Low 2.1
High 2.6
Low 2.1
High 2.6
Low 2.1
High 2.0
Low 2.1
High 2.0
Low 4.9
High 7.0
Low 4.9
High 7.0
E xa mp le : S up p ly v ol ta ge i s 2 3 0 --- 3 ---6 0
Determine maxim um deviation from average voltage. (AB) 227 – 224 = 3 v (BC) 231 – 227 = 4 v (AC) 227 – 226 = 1 v Maximum deviation is 4 v. Deter mine per cent of voltage imbalance .
% Voltage Imbalance = 100 x
This amou nt of phase im balance is satisfactor y as it is be low the maxim um allowable 2%. IMPORTANT: If the supply voltage phase imb alance is more than 2 %, contact your local el ectric utility company immed iately.
ELECTRIC HEAT POWER SUPPLY
IFM FLA
17.3/ 20.0 3.8/ 5.0 40.0/ 40.0 45/ 45 38/38 160/160
26.0/ 30.0 5.6/ 7.5 40.0/ 43.6 45/ 45 38/40 160/160
34.7/ 40.0 7.5/10.0 49.5/ 56.1 50/ 60 46/52 160/160
52.0/ 60.0 11.3/15.0 71.1/ 81.1 80/ 90 65/75 160/160
69.3/ 80.0 15.0/20.0 92.8/106.1 100/110 85/98 160/160
86.7/100.0 18.8/25.0 114.5/131.1 125/150 105/121 160/160
17.3/ 20.0 3.8/ 5.0 42.1/ 42.1 45/ 45 41/41 185/185
26.0/ 30.0 5.6/ 7.5 42.1/ 46.3 45/ 50 41/43 185/185
34.7/ 40.0 7.5/10.0 52.1/ 58.8 60/ 60 48/54 185/185
52.0/ 60.0 11.3/15.0 73.8/ 83.8 80/ 90 68/77 185/185
69.3/ 80.0 15.0/20.0 95.4/108.8 100/110 88/100 185/185
86.7/100.0 18.8/25.0 117.1/133.8 125/150 108/123 185/185
17.3/ 20.0 3.8/ 5.0 41.4/ 41.4 45/ 45 40/40 162/162
26.0/ 30.0 5.6/ 7.5 41.4/ 45.4 45/ 50 40/42 162/162
34.7/ 40.0 7.5/10.0 51.3/ 57.9 60/ 60 47/53 162/162
52.0/ 60.0 11.3/15.0 72.9/ 82.9 80/ 90 67/76 162/162
69.3/ 80.0 15.0/20.0 94.5/107.9 100/110 87/99 162/162
86.7/100.0 18.8/25.0 116.3/132.9 125/150 107/122 162/162
17.3/ 20.0 3.8/ 5.0 43.5/ 43.5 50/ 50 42/42 187/187
26.0/ 30.0 5.6/ 7.5 43.5/ 48.0 50/ 50 42/44 187/187
34.7/ 40.0 7.5/10.0 53.9/ 60.5 60/ 70 50/56 187/187
52.0/ 60.0 11.3/15.0 75.5/ 85.5 80/ 90 69/79 187/187
69.3/ 80.0 15.0/20.0 97.1/110.5 100/125 89/102 187/187
86.7/100.0 18.8/25.0 118.9/135.5 125/150 109/125 187/187
Nominal
11.5 15 11 53
5.8 5.0 11.5 15 11 53
8.7 7.5 13.5 15 12 53
11.5 10.0 17.0 20 16 53
17.3 15.0 24.3 25 22 53
23.1 20.0 31.5 35 29 53 — 12.0 15 12 62
5.8 5.0 12.0 15 12 62
8.7 7.5 14.1 15 13 62
11.5 10.0 17.6 20 16 62
17.3 15.0 24.9 25 23 62
23.1 20.0 32.1 35 30 62 — 12.1 15 12 54
5.8 5.0 12.1 15 12 54
8.7 7.5 14.3 15 13 54
11.5 10.0 17.8 20 16 54
17.3 15.0 25.0 30 23 54
23.1 20.0 32.3 35 30 54 — 12.6 15 12 63
5.8 5.0 12.6 15 12 63
8.7 7.5 14.9 15 14 63
11.5 10.0 18.4 20 17 63
17.3 15.0 25.6 30 24 63
23.1 20.0 32.9 35 30 63 — 9.0 15 9 40
9.2 10.0 14.1 15 13 40
13.9 15.0 20.0 25 18 40
18.5 20.0 25.8 30 24 40 — 8.9 15 9 46
9.2 10.0 14.0 15 13 46
13.9 15.0 19.9 20 18 46
18.5 20.0 25.6 30 24 46 — 10.4 15 10 42
9.2 10.0 15.9 20 15 42
13.9 15.0 21.8 25 20 42
18.5 20.0 27.5 30 25 42 — 10.3 15 10 48
9.2 10.0 15.8 20 14 48
13.9 15.0 21.6 25 20 48
18.5 20.0 27.4 30 25 48 — 40.0/ 40.0 45/ 45 38/38 160/160
kW*
MCA MOCP† FLA LRA
42.1/ 42.1 45/ 45 41/41 185/185
41.4/ 41.4 45/ 45 40/40 162/162
43.5/ 43.5 50/ 50 42/42 187/187
AB = 224 v BC = 231 v AC = 226 v
Average Voltage =
= 1.76%
224 + 231 + 226
681
=
=
227
3
3
4
227
DISCONNECT
SIZE
14
Page 15
UNIT
50PG
06
(cont)
07
NOMINAL
POWER SUPPLY
Volts -Ph-Hz
208/230-3-60 187 253 17.6 123 1.5
460-3-60 414 506 7.7 50 0.8
575-3-60 518 633 6.1 40 0.8
208/230-3-60 187 253 20.5 149 1.5
* See Legend on next page.
Table 2 -- Electrical Data -- Units Without Optional Convenience Outlet (cont)
VOLTAGE
RANGE
Min Max RLA LRA FLA
COMPRESSOR
OFM
FLA
POWER
EXHAUST
FLA
1.4
0.6
1.4
IFM
TYPE
Low
High
Low
High
Low
High
Low
High
Low
High
Low
High
Low 5.2
High 7.5
ELECTRIC HEAT POWER SUPPLY
IFM FLA
10.0/11.5 3.8/ 5.0 28.7/28.7 30/30 28/28 156/156
15.0/17.3 5.6/ 7.5 28.7/28.7 30/30 28/28 156/156
20.0/23.1 7.5/10.0 31.5/35.4 35/40 29/33 156/156
30.0/34.6 11.3/15.0 44.0/49.8 45/50 40/46 156/156
40.0/46.2 15.0/20.0 56.5/64.3 60/70 52/59 156/156
50.0/57.7 18.8/25.0 69.0/78.6 70/80 63/72 156/156
10.0/11.5 3.8/ 5.0 28.7/28.7 30/30 28/28 156/156
15.0/17.3 5.6/ 7.5 28.7/28.7 30/30 28/28 156/156
20.0/23.1 7.5/10.0 31.5/35.4 35/40 29/33 156/156
30.0/34.6 11.3/15.0 44.0/49.8 45/50 40/46 156/156
40.0/46.2 15.0/20.0 56.5/64.3 60/70 52/59 156/156
50.0/57.7 18.8/25.0 69.0/78.6 70/80 63/72 156/156
5.2
10.0/11.5 3.8/ 5.0 30.1/30.1 35/35 30/30 158/158
15.0/17.3 5.6/ 7.5 30.1/30.1 35/35 30/30 158/158
20.0/23.1 7.5/10.0 33.3/37.1 35/40 31/34 158/158
30.0/34.6 11.3/15.0 45.8/51.5 50/60 42/47 158/158
40.0/46.2 15.0/20.0 58.3/66.0 60/70 54/61 158/158
50.0/57.7 18.8/25.0 70.8/80.4 80/90 65/74 158/158
10.0/11.5 3.8/ 5.0 30.1/30.1 35/35 30/30 158/158
15.0/17.3 5.6/ 7.5 30.1/30.1 35/35 30/30 158/158
20.0/23.1 7.5/10.0 33.3/37.1 35/40 31/34 158/158
30.0/34.6 11.3/15.0 45.8/51.5 50/60 42/47 158/158
40.0/46.2 15.0/20.0 58.3/66.0 60/70 54/61 158/158
50.0/57.7 18.8/25.0 70.8/80.4 80/90 65/74 158/158
11.5 10.0 17.6 20 16 67
17.3 15.0 24.9 25 23 67
23.1 20.0 32.1 35 30 67
28.9 25.0 39.4 40 36 67
11.5 10.0 17.6 20 16 67
17.3 15.0 24.9 25 23 67
23.1 20.0 32.1 35 30 67
2.6
2.0
28.9 25.0 39.4 40 36 67
11.5 10.0 18.4 20 17 68
17.3 15.0 25.6 30 24 68
23.1 20.0 32.9 35 30 68
28.9 25.0 40.1 45 37 68
11.5 10.0 18.4 20 17 68
17.3 15.0 25.6 30 24 68
23.1 20.0 32.9 35 30 68
28.9 25.0 40.1 45 37 68
13.9 15.0 19.9 20 18 53
18.5 20.0 25.6 30 24 53
23.1 25.0 31.4 35 29 53
13.9 15.0 19.9 20 18 53
18.5 20.0 25.6 30 24 53
23.1 25.0 31.4 35 29 53
13.9 15.0 21.6 25 20 55
18.5 20.0 27.4 30 25 55
23.1 25.0 33.1 35 30 55
13.9 15.0 21.6 25 20 55
18.5 20.0 27.4 30 25 55
23.1 25.0 33.1 35 30 55
10.0/11.5 3.8/ 5.0 32.3/32.3 35/35 31/31 182/182
15.0/17.3 5.6/ 7.5 32.3/32.3 35/35 31/31 182/182
20.0/23.1 7.5/10.0 32.3/35.4 35/40 31/33 182/182
30.0/34.6 11.3/15.0 44.0/49.8 45/50 40/46 182/182
40.0/46.2 15.0/20.0 56.5/64.3 60/70 52/59 182/182
50.0/57.7 18.8/25.0 69.0/78.6 70/80 63/72 182/182
10.0/11.5 3.8/ 5.0 34.6/34.6 35/35 34/34 208/208
15.0/17.3 5.6/ 7.5 34.6/34.6 35/35 34/34 208/208
20.0/23.1 7.5/10.0 34.6/38.3 35/40 34/35 208/208
30.0/34.6 11.3/15.0 46.9/52.6 50/60 43/48 208/208
40.0/46.2 15.0/20.0 59.4/67.1 60/70 55/62 208/208
50.0/57.7 18.8/25.0 71.9/81.5 80/90 66/75 208/208
Nominal
28.7/28.7 30/30 28/28 156/156
28.7/28.7 30/30 28/28 156/156
30.1/30.1 35/35 30/30 158/158
30.1/30.1 35/35 30/30 158/158
13.0 15 13 67
5.8 5.0 13.0 15 13 67
8.7 7.5 14.1 15 13 67
13.0 15 13 67
5.8 5.0 13.0 15 13 67
8.7 7.5 14.1 15 13 67
13.6 15 13 68
5.8 5.0 13.6 15 13 68
8.7 7.5 14.9 15 14 68
13.6 15 13 68
5.8 5.0 13.6 15 13 68
8.7 7.5 14.9 15 14 68
10.4 15 10 53
9.2 10.0 14.0 15 13 53
10.4 15 10 53
9.2 10.0 14.0 15 13 53
11.8 15 12 55
9.2 10.0 15.8 20 14 55
11.8 15 12 55
9.2 10.0 15.8 20 14 55
32.3/32.3 35/35 31/31 182/182
34.6/34.6 35/35 34/34 208/208
kW*
DISCONNECT
SIZE
MCA MOCP† FLA LRA
50PG03--07
15
Page 16
Table 2 -- Electrical Data -- Units Without Optional Convenience Outlet (cont)
UNIT
50PG
NOMINAL
POWER SUPPLY
Volts -Ph-Hz
208/230-3-60 187 253 20.5 149 1.5 1.4
50PG03--07
07
(cont)
460-3-60 414 506 9.6 75 0.8
575-3-60 518 633 7.6 54 0.8
FLA --- Fu l l Lo a d A mps HACR --- Heating, Air Conditioning and Refrigeration IFM --- Indoor (Evaporator) Fan Motor LRA --- L oc k ed Rot o r A mp s MCA --- Minimum Circuit Amps MOCP --- M aximum Overcurrent Protection NEC --- Natio nal Electrical Code OFM --- Outdoor (Condenser) Fan Motor RLA --- RatedLoadAmps
*Heater capacity (kW) is based o n heater voltage of 208v, 240v, 480v, or 600v. If power distribution voltage to unit varies from rated heater voltage, heater kW will vary accord­ingly. { Fuse or HACR ci rcuit breaker.
NOTES:
1. In comp liance with NE C require ments for multim otor and combin a tion load equip ment (refe r
2. Unbalanced 3- Phase Supply Voltage
% Voltage Imbalance = 100 x
LEGEND
to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. Canadian units may be fuse or circuit breaker.
Never operate a motor where a phase imb alance in supply voltage is greater than 2%.Use the following formula to deter mine the percentage of voltage imb alance.
VOLTAGE
RANGE
COMPRESSOR
Min Max RLA LRA FLA
max voltage deviation from average voltage
averag e voltage
OFM
FLA
POWER
EXHAUST
FLA
0.6
1.4
IFM
TYPE
Low 5.2
High 7.5
Low 2.6
High 3.4
Low 2.6
High 3.4
Low 2.0
High 2.8
Low 2.0
High 2.8
E xa mp le : S up p ly v ol ta ge i s 2 3 0 --- 3 ---6 0
Determine maxim um deviation from average voltage. (AB) 227 – 224 = 3 v (BC) 231 – 227 = 4 v (AC) 227 – 226 = 1 v Maximum deviation is 4 v. Deter mine per cent of voltage imbalance .
% Voltage Imbalance = 100 x
This amou nt of phase im balance is satisfactor y as it is be low the maxim um allowable 2%. IMPORTANT: If the supply voltage phase imb alance is more than 2 %, contact your local el ectric utility company immed iately.
ELECTRIC HEAT POWER SUPPLY
IFM FLA
10.0/11.5 3.8/ 5.0 33.7/33.7 35/35 33/33 184/184
15.0/17.3 5.6/ 7.5 33.7/33.7 35/35 33/33 184/184
20.0/23.1 7.5/10.0 33.7/37.1 35/40 33/34 184/184
30.0/34.6 11.3/15.0 45.8/51.5 50/60 42/47 184/184
40.0/46.2 15.0/20.0 58.3/66.0 60/70 54/61 184/184
50.0/57.7 18.8/25.0 70.8/80.4 80/90 65/74 184/184
10.0/11.5 3.8/ 5.0 36.0/36.0 40/40 36/36 210/210
15.0/17.3 5.6/ 7.5 36.0/36.0 40/40 36/36 210/210
20.0/23.1 7.5/10.0 36.1/40.0 40/45 36/37 210/210
30.0/34.6 11.3/15.0 48.6/54.4 50/60 45/50 210/210
40.0/46.2 15.0/20.0 61.1/68.9 70/70 56/63 210/210
50.0/57.7 18.8/25.0 73.6/83.3 80/90 68/77 210/210
11.5 10.0 17.6 20 16 92
17.3 15.0 24.9 25 23 92
23.1 20.0 32.1 35 30 92
28.9 25.0 39.4 40 36 92
11.5 10.0 18.6 20 17 105
17.3 15.0 25.9 30 24 105
23.1 20.0 33.1 35 30 105
28.9 25.0 40.4 45 37 105
11.5 10.0 18.4 20 17 93
17.3 15.0 25.6 30 24 93
23.1 20.0 32.9 35 30 93
28.9 25.0 40.1 45 37 93
11.5 10.0 19.4 20 18 106
17.3 15.0 26.6 30 24 106
23.1 20.0 33.9 35 31 106
28.9 25.0 41.1 45 38 106
13.9 15.0 19.9 20 18 67
18.5 20.0 25.6 30 24 67
23.1 25.0 31.4 35 29 67
27.7 30.0 37.1 40 34 67
13.9 15.0 20.9 25 19 78
18.5 20.0 26.6 30 24 78
23.1 25.0 32.4 35 30 78
27.7 30.0 38.1 40 35 78
13.9 15.0 21.6 25 20 69
18.5 20.0 27.4 30 25 69
23.1 25.0 33.1 35 30 69
27.7 30.0 38.9 40 36 69
13.9 15.0 22.6 25 21 80
18.5 20.0 28.4 30 26 80
23.1 25.0 34.1 35 31 80
27.7 30.0 39.9 40 37 80
Nominal
kW*
MCA MOCP† FLA LRA
33.7/33.7 35/35 33/33 184/184
36.0/36.0 40/40 36/36 210/210
15.4 20 15 92
5.8 5.0 15.4 20 15 92
8.7 7.5 15.4 20 15 92
16.2 20 16 105
5.8 5.0 16.2 20 16 105
8.7 7.5 16.2 20 16 105
16.0 20 16 93
5.8 5.0 16.0 20 16 93
8.7 7.5 16.0 20 16 93
16.8 20 17 106
5.8 5.0 16.8 20 17 106
8.7 7.5 16.8 20 17 106
12.3 15 12 67
9.2 10.0 14.0 15 13 67
13.1 15 13 78
9.2 10.0 15.0 15 14 78
13.7 15 14 69
9.2 10.0 15.8 20 14 69
14.5 15 14 80
9.2 10.0 16.8 20 15 80
AB = 224 v BC = 231 v AC = 226 v
Average Voltage =
= 1.76%
224 + 231 + 226
681
=
=
227
3
3
4
227
DISCONNECT
SIZE
16
Page 17
Table 3 – Electrical Data -- Units With Optional Powered Convenience Outlet
UNIT 50PG
03
NOMINAL
POWER SUPPLY
Volts -Ph-Hz
208/230-1-60 187 253 12.8 60 1.0
208/230-1-60 187 253 15.4 83 1.0
04
208/230-3-60 187 253 11.5 77 1.0
FLA --- Fu l l Lo a d A mps HACR --- Heating, Air Conditioning and Refrigeration IFM --- Indoor (Evaporator) Fan Motor LRA --- L oc k ed Rot o r A mp s MCA --- Minimum Circuit Amps MOCP --- M aximum Overcurrent Protection NEC --- Natio nal Electrical Code OFM --- Outdoor (Condenser) Fan Motor RLA --- RatedLoadAmps
*Heater capacity (kW) is based o n heater voltage of 208v, 240v, 480v, or 600v. If power distribution voltage to unit varies from rated heater voltage, heater kW will vary accord­ingly. { Fuse or HACR ci rcuit breaker.
NOTES:
1. In comp liance with NE C require ments for multim otor and combin a tion load equip ment (refe r
2. Unbalanced 3- Phase Supply Voltage
% Voltage Imbalance = 100 x
LEGEND
to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. Canadian units may be fuse or circuit breaker.
Never operate a motor where a phase imb alance in supply voltage is greater than 2%.Use the following formula to deter mine the percentage of voltage imb alance.
VOLTAGE
RANGE
Min Max RLA LRA FLA
COMPRESSOR
OFM
FLA
max voltage deviation from average voltage
averag e voltage
POWER
EXHAUST
FLA
1.4
1.4
IFM
IFM
FLA
TYPE
Low
High
Low
High
Low
High
Low
High
Low
High
E xa mp le : S up p ly v ol ta ge i s 2 3 0 --- 3 ---6 0
Determine maxim um deviation from average voltage. (AB) 227 – 224 = 3 v (BC) 231 – 227 = 4 v (AC) 227 – 226 = 1 v Maximum deviation is 4 v. Deter mine per cent of voltage imbalance .
% Voltage Imbalance = 100 x
This amou nt of phase im balance is satisfactor y as it is be low the maxim um allowable 2%. IMPORTANT: If the supply voltage phase imb alance is more than 2 %, contact your local el ectric utility company immed iately.
ELECTRIC HEAT POWER SUPPLY
Nominal
26.7/26.7 30/30 27/27 79/79
10.8/12.5 2.3/ 3.0 26.7/27.8 30/30 27/27 79/79
17.3/20.0 3.8/ 5.0 33.8/37.1 35/40 31/34 79/79
26.0/30.0 5.6/ 7.5 44.6/49.6 45/50 41/46 79/79
34.7/40.0 7.5/10.0 55.5/62.1 60/70 51/57 79/79 — 26.7/26.7 30/30 27/27 79/79
10.8/12.5 2.3/ 3.0 26.7/27.8 30/30 27/27 79/79
17.3/20.0 3.8/ 5.0 33.8/37.1 35/40 31/34 79/79
26.0/30.0 5.6/ 7.5 44.6/49.6 45/50 41/46 79/79
34.7/40.0 7.5/10.0 55.5/62.1 60/70 51/57 79/79
4.9
4.9
4.9
28.1/28.1 30/30 29/29 81/81
10.8/12.5 2.3/ 3.0 28.1/29.5 30/30 29/29 81/81
17.3/20.0 3.8/ 5.0 35.5/38.9 40/40 33/36 81/81
26.0/30.0 5.6/ 7.5 46.4/51.4 50/60 43/47 81/81
34.7/40.0 7.5/10.0 57.3/63.9 60/70 53/59 81/81 — 28.1/28.1 30/30 29/29 81/81
10.8/12.5 2.3/ 3.0 28.1/29.5 30/30 29/29 81/81
17.3/20.0 3.8/ 5.0 35.5/38.9 40/40 33/36 81/81
26.0/30.0 5.6/ 7.5 46.4/51.4 50/60 43/47 81/81
34.7/40.0 7.5/10.0 57.3/63.9 60/70 53/59 81/81 — 30.0/30.0 30/30 30/30 102/102
10.8/12.5 2.3/ 3.0 30.0/30.0 30/30 30/30 102/102
17.3/20.0 3.8/ 5.0 33.8/37.1 35/40 31/34 102/102
26.0/30.0 5.6/ 7.5 44.6/49.6 45/50 41/46 102/102
34.7/40.0 7.5/10.0 55.5/62.1 60/70 51/57 102/102
52.0/60.0 11.3/15.0 77.1/87.1 80/90 71/80 102/102 — 30.0/30.0 30/30 30/30 102/102
10.8/12.5 2.3/ 3.0 30.0/30.0 30/30 30/30 102/102
17.3/20.0 3.8/ 5.0 33.8/37.1 35/40 31/34 102/102
26.0/30.0 5.6/ 7.5 44.6/49.6 45/50 41/46 102/102
34.7/40.0 7.5/10.0 55.5/62.1 60/70 51/57 102/102
52.0/60.0 11.3/15.0 77.1/87.1 80/90 71/80 102/102 — 31.4/31.4 35/35 32/32 104/104
10.8/12.5 2.3/ 3.0 31.4/31.4 35/35 32/32 104/104
17.3/20.0 3.8/ 5.0 35.5/38.9 40/40 33/36 104/104
26.0/30.0 5.6/ 7.5 46.4/51.4 50/60 43/47 104/104
34.7/40.0 7.5/10.0 57.3/63.9 60/70 53/59 104/104
52.0/60.0 11.3/15.0 78.9/88.9 80/90 73/82 104/104 — 31.4/31.4 35/35 32/32 104/104
10.8/12.5 2.3/ 3.0 31.4/31.4 35/35 32/32 104/104
17.3/20.0 3.8/ 5.0 35.5/38.9 40/40 33/36 104/104
26.0/30.0 5.6/ 7.5 46.4/51.4 50/60 43/47 104/104
34.7/40.0 7.5/10.0 57.3/63.9 60/70 53/59 104/104
52.0/60.0 11.3/15.0 78.9/88.9 80/90 73/82 104/104 — 25.1/25.1 30/30 26/26 96/96
6.3/ 7.2 2.3/ 3.0 25.1/25.1 30/30 26/26 96/96
10.0/11.5 3.8/ 5.0 25.1/26.5 30/30 26/26 96/96
15.0/17.3 5.6/ 7.5 30.9/33.8 35/35 28/31 96/96
20.0/23.1 7.5/10.0 37.1/41.0 40/45 34/38 96/96
30.0/34.6 11.3/15.0 49.6/55.4 50/60 46/51 96/96 — 25.1/25.1 30/30 26/26 96/96
6.3/ 7.2 2.3/ 3.0 25.1/25.1 30/30 26/26 96/96
10.0/11.5 3.8/ 5.0 25.1/26.5 30/30 26/26 96/96
15.0/17.3 5.6/ 7.5 30.9/33.8 35/35 28/31 96/96
20.0/23.1 7.5/10.0 37.1/41.0 40/45 34/38 96/96
30.0/34.6 11.3/15.0 49.6/55.4 50/60 46/51 96/96
kW*
AB = 224 v BC = 231 v AC = 226 v
Average Voltage =
= 1.76%
MCA MOCP† FLA LRA
224 + 231 + 226
3
681
=
3
=
227
4
227
DISCONNECT
SIZE
50PG03--07
17
Page 18
UNIT
50PG
04
(cont)
50PG03--07
05
* See Legend on next page.
Table 3 -- Electrical Data -- Units With Optional Powered Convenience Outlet (cont)
NOMINAL
POWER SUPPLY
Volts -Ph-Hz
208/230-3-60 187 253 11.5 77 1.0 1.4
460-3-60 414 506 5.1 35 0.5
575-3-60 518 633 4.3 31 0.5
208/230-1-60 187 253 20.5 109 1.0
208/230-3-60 187 253 14.6 91 1.0
VOLTAGE
RANGE
Min Max RLA LRA FLA
COMPRESSOR
OFM
FLA
POWER
EXHAUST
FLA
0.6
1.4
1.4
1.4
IFM
TYPE
Low
High
Low
High
Low
High
Low
High
Low
High
Low 4.9
High 7.0
Low 4.9
High 7.0
Low 4.9
High 5.2
Low 4.9
High 5.2
ELECTRIC HEAT POWER SUPPLY
IFM
FLA
6.3/ 7.2 2.3/ 3.0 26.5/26.5 30/30 27/27 98/98
10.0/11.5 3.8/ 5.0 26.5/28.3 30/30 27/27 98/98
15.0/17.3 5.6/ 7.5 32.6/35.5 35/40 30/33 98/98
20.0/23.1 7.5/10.0 38.9/42.8 40/45 36/39 98/98
30.0/34.6 11.3/15.0 51.4/57.1 60/60 47/53 98/98
4.9
6.3/ 7.2 2.3/ 3.0 26.5/26.5 30/30 27/27 98/98
10.0/11.5 3.8/ 5.0 26.5/28.3 30/30 27/27 98/98
15.0/17.3 5.6/ 7.5 32.6/35.5 35/40 30/33 98/98
20.0/23.1 7.5/10.0 38.9/42.8 40/45 36/39 98/98
30.0/34.6 11.3/15.0 51.4/57.1 60/60 47/53 98/98
11.5 10.0 19.8 20 18 44
17.3 15.0 27.0 30 25 44
11.5 10.0 19.8 20 18 44
2.1
2.1
17.3 15.0 27.0 30 25 44
11.5 10.0 20.5 25 19 45
17.3 15.0 27.8 30 26 45
11.5 10.0 20.5 25 19 45
17.3 15.0 27.8 30 26 45
13.9 15.0 22.1 25 20 39
13.9 15.0 22.1 25 20 39
13.9 15.0 23.9 25 22 41
13.9 15.0 23.9 25 22 41
17.3/20.0 3.8/ 5.0 36.3/ 37.1 40/ 40 36/ 36 128/128
26.0/30.0 5.6/ 7.5 44.6/ 49.6 45/ 50 41/ 46 128/128
34.7/40.0 7.5/10.0 55.5/ 62.1 60/ 70 51/ 57 128/128
52.0/60.0 11.3/15.0 77.1/ 87.1 80/ 90 71/ 80 128/128
69.3/80.0 15.0/20.0 98.8/112.1 100/125 91/103 128/128
17.3/20.0 3.8/ 5.0 38.4/ 39.8 40/ 40 38/ 38 153/153
26.0/30.0 5.6/ 7.5 47.3/ 52.3 50/ 60 43/ 48 153/153
34.7/40.0 7.5/10.0 58.1/ 64.8 60/ 70 53/ 60 153/153
52.0/60.0 11.3/15.0 79.8/ 89.8 80/ 90 73/ 83 153/153
69.3/80.0 15.0/20.0 101.4/114.8 110/125 93/106 153/153
17.3/20.0 3.8/ 5.0 37.7/ 38.9 40/ 40 37/ 37 130/130
26.0/30.0 5.6/ 7.5 46.4/ 51.4 50/ 60 43/ 47 130/130
34.7/40.0 7.5/10.0 57.3/ 63.9 60/ 70 53/ 59 130/130
52.0/60.0 11.3/15.0 78.9/ 88.9 80/ 90 73/ 82 130/130
69.3/80.0 15.0/20.0 100.5/113.9 110/125 92/105 130/130
17.3/20.0 3.8/ 5.0 39.8/ 41.5 40/ 45 40/ 40 155/155
26.0/30.0 5.6/ 7.5 49.0/ 54.0 50/ 60 45/ 50 155/155
34.7/40.0 7.5/10.0 59.9/ 66.5 60/ 70 55/ 61 155/155
52.0/60.0 11.3/15.0 81.5/ 91.5 90/100 75/ 84 155/155
69.3/80.0 15.0/20.0 103.1/116.5 110/125 95/107 155/155
10.0/11.5 3.8/ 5.0 29.0/29.0 30/30 29/29 110/110
15.0/17.3 5.6/ 7.5 30.9/33.8 35/35 29/31 110/110
20.0/23.1 7.5/10.0 37.1/41.0 40/45 34/38 110/110
30.0/34.6 11.3/15.0 49.6/55.4 50/60 46/51 110/110
40.0/46.2 15.0/20.0 62.1/69.9 70/70 57/64 110/110
10.0/11.5 3.8/ 5.0 29.3/29.3 30/30 29/29 128/128
15.0/17.3 5.6/ 7.5 31.3/34.1 35/35 29/31 128/128
20.0/23.1 7.5/10.0 37.5/41.4 40/45 35/38 128/128
30.0/34.6 11.3/15.0 50.0/55.8 60/60 46/51 128/128
40.0/46.2 15.0/20.0 62.5/70.3 70/80 58/65 128/128
10.0/11.5 3.8/ 5.0 30.4/30.4 35/35 31/31 112/112
15.0/17.3 5.6/ 7.5 32.6/35.5 35/40 31/33 112/112
20.0/23.1 7.5/10.0 38.9/42.8 40/45 36/39 112/112
30.0/34.6 11.3/15.0 51.4/57.1 60/60 47/53 112/112
40.0/46.2 15.0/20.0 63.9/71.6 70/80 59/66 112/112
10.0/11.5 3.8/ 5.0 30.7/30.7 35/35 31/31 130/130
15.0/17.3 5.6/ 7.5 33.0/35.9 35/40 31/33 130/130
20.0/23.1 7.5/10.0 39.3/43.1 40/45 36/40 130/130
30.0/34.6 11.3/15.0 51.8/57.5 60/60 48/53 130/130
40.0/46.2 15.0/20.0 64.3/72.0 70/80 59/66 130/130
Nominal
26.5/26.5 30/30 27/27 98/98
26.5/26.5 30/30 27/27 98/98
11.2 15 11 44
3.5 3.0 11.2 15 11 44
5.8 5.0 12.6 15 12 44
8.7 7.5 16.3 20 15 44
11.2 15 11 44
3.5 3.0 11.2 15 11 44
5.8 5.0 12.6 15 12 44
8.7 7.5 16.3 20 15 44
11.8 15 12 45
3.5 3.0 11.8 15 12 45
5.8 5.0 13.4 15 12 45
8.7 7.5 17.0 20 16 45
11.8 15 12 45
3.5 3.0 11.8 15 12 45
5.8 5.0 13.4 15 12 45
8.7 7.5 17.0 20 16 45
9.7 15 10 39
9.2 10.0 16.3 20 15 39
9.7 15 10 39
9.2 10.0 16.3 20 15 39
11.1 15 12 41
9.2 10.0 18.0 20 17 41
11.1 15 12 41
9.2 10.0 18.0 20 17 41
36.3/ 36.3 40/ 40 36/ 36 128/128
38.4/ 38.4 40/ 40 38/ 38 153/153
37.7/ 37.7 40/ 40 37/ 37 130/130
39.8/ 39.8 40/ 40 40/ 40 155/155
29.0/29.0 30/30 29/29 110/110
29.3/29.3 30/30 29/29 128/128
30.4/30.4 35/35 31/31 112/112
30.7/30.7 35/35 31/31 130/130
kW*
MCA MOCP† FLA LRA
DISCONNECT
SIZE
18
Page 19
Table 3 -- Electrical Data -- Units With Optional Powered Convenience Outlet (cont)
NOMINAL
POWER SUPPL Y
UNIT
50PG
Volt s-Ph -Hz
460-3-60 414 506 7.1 46 0.5
05
(cont)
575-3-60 518 633 5.1 34 0.5
06
208/230-1-60 187 253 26.9 145 1.5
FLA --- Fu l l Lo a d A mps HACR --- Heating, Air Conditioning and Refrigeration IFM --- Indoor (Evaporator) Fan Motor LRA --- L oc k ed Rot o r A mp s MCA --- Minimum Circuit Amps MOCP --- M aximum Overcurrent Protection NEC --- Natio nal Electrical Code OFM --- Outdoor (Condenser) Fan Motor RLA --- RatedLoadAmps
*Heater capacity (kW) is based o n heater voltage of 208v, 240v, 480v, or 600v. If power distribution voltage to unit varies from rated heater voltage, heater kW will vary accord­ingly. { Fuse or HACR ci rcuit breaker.
NOTES:
1. In comp liance with NE C require ments for multim otor and combin a tion load equip ment (refe r
2. Unbalanced 3- Phase Supply Voltage
% Voltage Imbalance = 100 x
LEGEND
to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. Canadian units may be fuse or circuit breaker.
Never operate a motor where a phase imb alance in supply voltage is greater than 2%.Use the following formula to deter mine the percentage of voltage imb alance.
VOLTAGE
RANGE
Min Max RLA LR A FLA
COMPRESSO R
OFM
FLA
max voltage deviation from average voltage
averag e voltage
POWER
EXHAUST
FLA
0.6
1.4
1.4
IFM
IFM
FLA
TYPE
Low 2.1
High 2.6
Low 2.1
High 2.6
Low 2.1
High 2.0
Low 2.1
High 2.0
Low 4.9
High 7.0
Low 4.9
High 7.0
E xa mp le : S up p ly v ol ta ge i s 2 3 0 --- 3 ---6 0
Determine maxim um deviation from average voltage. (AB) 227 – 224 = 3 v (BC) 231 – 227 = 4 v (AC) 227 – 226 = 1 v Maximum deviation is 4 v. Deter mine per cent of voltage imbalance .
% Voltage Imbalance = 100 x
This amou nt of phase im balance is satisfactor y as it is be low the maxim um allowable 2%. IMPORTANT: If the supply voltage phase imb alance is more than 2 %, contact your local el ectric utility company immed iately.
ELECTRIC HEAT POWER SUPPLY
Nominal
13.7 15 14 55
5.8 5.0 13.7 15 14 55
8.7 7.5 16.3 20 15 55
11.5 10.0 19.8 20 18 55
17.3 15.0 27.0 30 25 55
23.1 20.0 34.3 35 32 55
14.2 15 14 64
5.8 5.0 14.2 15 14 64
8.7 7.5 16.9 20 16 64
11.5 10.0 20.4 25 19 64
17.3 15.0 27.6 30 25 64
23.1 20.0 34.9 35 32 64
14.3 15 14 56
5.8 5.0 14.3 15 14 56
8.7 7.5 17.0 20 16 56
11.5 10.0 20.5 25 19 56
17.3 15.0 27.8 30 26 56
23.1 20.0 35.0 40 32 56
14.8 15 15 65
5.8 5.0 14.8 15 15 65
8.7 7.5 17.6 20 16 65
11.5 10.0 21.1 25 19 65
17.3 15.0 28.4 30 26 65
23.1 20.0 35.6 40 33 65
10.7 15 11 42
9.2 10.0 16.3 20 15 42
13.9 15.0 22.1 25 20 42
18.5 20.0 27.9 30 26 42
10.6 15 11 48
9.2 10.0 16.1 20 15 48
13.9 15.0 22.0 25 20 48
18.5 20.0 27.8 30 26 48
12.1 15 12 44
9.2 10.0 18.0 20 17 44
13.9 15.0 23.9 25 22 44
18.5 20.0 29.6 30 27 44
12.0 15 12 50
9.2 10.0 17.9 20 16 50
13.9 15.0 23.8 25 22 50
18.5 20.0 29.5 30 27 50
44.8/ 44.8 50/ 50 44/44 165/165
17.3/ 20.0 3.8/ 5.0 44.8/ 44.8 50/ 50 44/44 165/165
26.0/ 30.0 5.6/ 7.5 44.8/ 49.6 50/ 50 44/46 165/165
34.7/ 40.0 7.5/10.0 55.5/ 62.1 60/ 70 51/57 165/165
52.0/ 60.0 11.3/15.0 77.1/ 87.1 80/ 90 71/80 165/165
69.3/ 80.0 15.0/20.0 98.8/112.1 100/125 91/103 165/165
86.7/100.0 18.8/25.0 120.5/137.1 125/150 111/126 165/165 — 46.9/ 46.9 50/ 50 46/ 46 190/190
17.3/ 20.0 3.8/ 5.0 46.9/ 46.9 50/ 50 46/ 46 190/190
26.0/ 30.0 5.6/ 7.5 47.3/ 52.3 50/ 60 46/ 48 190/190
34.7/ 40.0 7.5/10.0 58.1/ 64.8 60/ 70 53/ 60 190/190
52.0/ 60.0 11.3/15.0 79.8/ 89.8 80/ 90 73/ 83 190/190
69.3/ 80.0 15.0/20.0 101.4/114.8 110/125 93/106 190/190
86.7/100.0 18.8/25.0 123.1/139.8 125/150 113/129 190/190 — 46.2/ 46.2 50/ 50 45/ 45 167/167
17.3/ 20.0 3.8/ 5.0 46.2/ 46.2 50/ 50 45/ 45 167/167
26.0/ 30.0 5.6/ 7.5 46.4/ 51.4 50/ 60 45/ 47 167/167
34.7/ 40.0 7.5/10.0 57.3/ 63.9 60/ 70 53/ 59 167/167
52.0/ 60.0 11.3/15.0 78.9/ 88.9 80/ 90 73/ 82 167/167
69.3/ 80.0 15.0/20.0 100.5/113.9 110/125 92/105 167/167
86.7/100.0 18.8/25.0 122.3/138.9 125/150 112/128 167/167 — 48.3/ 48.3 50/ 50 48/ 48 192/192
17.3/ 20.0 3.8/ 5.0 48.3/ 48.3 50/ 50 48/ 48 192/192
26.0/ 30.0 5.6/ 7.5 49.0/ 54.0 50/ 60 48/ 50 192/192
34.7/ 40.0 7.5/10.0 59.9/ 66.5 60/ 70 55/ 61 192/192
52.0/ 60.0 11.3/15.0 81.5/ 91.5 90/100 75/ 84 192/192
69.3/ 80.0 15.0/20.0 103.1/116.5 110/125 95/107 192/192
86.7/100.0 18.8/25.0 124.9/141.5 125/150 115/130 192/192
kW*
AB = 224 v BC = 231 v AC = 226 v
Average Voltage =
= 1.76%
MCA MOCP† FLA LRA
224 + 231 + 226
3
681
=
3
=
227
4
227
DISCONNECT
SIZE
50PG03--07
19
Page 20
UNIT
50PG
50PG03--07
06
(cont)
07
* See Legend on next page.
Table 3 -- Electrical Data -- Units With Optional Powered Convenience Outlet (cont)
NOMINAL
POWER SUPPLY
Volts -Ph-Hz
208/230-3-60 187 253 17.6 123 1.5
460-3-60 414 506 7.7 50 0.8
575-3-60 518 633 6.1 40 0.8
208/230-3-60 187 253 20.5 149 1.5
VOLTAGE
RANGE
Min Max RLA LRA FLA
COMPRESSOR
OFM
FLA
POWER
EXHAUST
FLA
1.4
0.6
1.4
IFM
TYPE
Low
High
Low
High
Low
High
Low
High
Low
High
Low
High
Low 5.2
High 7.5
ELECTRIC HEAT POWER SUPPLY
IFM FLA
10.0/11.5 3.8/ 5.0 33.5/33.5 35/35 33/33 161/161
15.0/17.3 5.6/ 7.5 33.5/34.1 35/35 33/33 161/161
20.0/23.1 7.5/10.0 37.5/41.4 40/45 35/38 161/161
30.0/34.6 11.3/15.0 50.0/55.8 60/60 46/51 161/161
40.0/46.2 15.0/20.0 62.5/70.3 70/80 58/65 161/161
50.0/57.7 18.8/25.0 75.0/84.6 80/90 69/78 161/161
10.0/11.5 3.8/ 5.0 33.5/33.5 35/35 33/33 161/161
15.0/17.3 5.6/ 7.5 33.5/34.1 35/35 33/33 161/161
20.0/23.1 7.5/10.0 37.5/41.4 40/45 35/38 161/161
30.0/34.6 11.3/15.0 50.0/55.8 60/60 46/51 161/161
40.0/46.2 15.0/20.0 62.5/70.3 70/80 58/65 161/161
50.0/57.7 18.8/25.0 75.0/84.6 80/90 69/78 161/161
5.2
10.0/11.5 3.8/ 5.0 34.9/34.9 35/35 35/35 163/163
15.0/17.3 5.6/ 7.5 34.9/35.9 35/40 35/35 163/163
20.0/23.1 7.5/10.0 39.3/43.1 40/45 36/40 163/163
30.0/34.6 11.3/15.0 51.8/57.5 60/60 48/53 163/163
40.0/46.2 15.0/20.0 64.3/72.0 70/80 59/66 163/163
50.0/57.7 18.8/25.0 76.8/86.4 80/90 71/79 163/163
10.0/11.5 3.8/ 5.0 34.9/34.9 35/35 35/35 163/163
15.0/17.3 5.6/ 7.5 34.9/35.9 35/40 35/35 163/163
20.0/23.1 7.5/10.0 39.3/43.1 40/45 36/40 163/163
30.0/34.6 11.3/15.0 51.8/57.5 60/60 48/53 163/163
40.0/46.2 15.0/20.0 64.3/72.0 70/80 59/66 163/163
50.0/57.7 18.8/25.0 76.8/86.4 80/90 71/79 163/163
11.5 10.0 20.4 25 19 69
17.3 15.0 27.6 30 25 69
23.1 20.0 34.9 35 32 69
28.9 25.0 42.1 45 39 69
11.5 10.0 20.4 25 19 69
17.3 15.0 27.6 30 25 69
23.1 20.0 34.9 35 32 69
2.6
2.0
28.9 25.0 42.1 45 39 69
11.5 10.0 21.1 25 19 70
17.3 15.0 28.4 30 26 70
23.1 20.0 35.6 40 33 70
28.9 25.0 42.9 45 39 70
11.5 10.0 21.1 25 19 70
17.3 15.0 28.4 30 26 70
23.1 20.0 35.6 40 33 70
28.9 25.0 42.9 45 39 70
13.9 15.0 22.0 25 20 55
18.5 20.0 27.8 30 26 55
23.1 25.0 33.5 35 31 55
13.9 15.0 22.0 25 20 55
18.5 20.0 27.8 30 26 55
23.1 25.0 33.5 35 31 55
13.9 15.0 23.8 25 22 57
18.5 20.0 29.5 30 27 57
23.1 25.0 35.3 40 32 57
13.9 15.0 23.8 25 22 57
18.5 20.0 29.5 30 27 57
23.1 25.0 35.3 40 32 57
10.0/11.5 3.8/ 5.0 37.1/37.1 40/40 37/37 187/187
15.0/17.3 5.6/ 7.5 37.1/37.1 40/40 37/37 187/187
20.0/23.1 7.5/10.0 37.5/41.4 40/45 37/38 187/187
30.0/34.6 11.3/15.0 50.0/55.8 60/60 46/51 187/187
40.0/46.2 15.0/20.0 62.5/70.3 70/80 58/65 187/187
50.0/57.7 18.8/25.0 75.0/84.6 80/90 69/78 187/187
10.0/11.5 3.8/ 5.0 39.4/39.4 40/40 39/39 213/213
15.0/17.3 5.6/ 7.5 39.4/39.4 40/40 39/39 213/213
20.0/23.1 7.5/10.0 40.4/44.3 45/45 39/41 213/213
30.0/34.6 11.3/15.0 52.9/58.6 60/60 49/54 213/213
40.0/46.2 15.0/20.0 65.4/73.1 70/80 60/67 213/213
50.0/57.7 18.8/25.0 77.9/87.5 80/90 72/81 213/213
Nominal
33.5/33.5 35/35 33/33 161/161
33.5/33.5 35/35 33/33 161/161
34.9/34.9 35/35 35/35 163/163
34.9/34.9 35/35 35/35 163/163
15.2 20 15 69
5.8 5.0 15.2 20 15 69
8.7 7.5 16.9 20 16 69
15.2 20 15 69
5.8 5.0 15.2 20 15 69
8.7 7.5 16.9 20 16 69
15.8 20 16 70
5.8 5.0 15.8 20 16 70
8.7 7.5 17.6 20 16 70
15.8 20 16 70
5.8 5.0 15.8 20 16 70
8.7 7.5 17.6 20 16 70
12.1 15 12 55
9.2 10.0 16.1 20 15 55
12.1 15 12 55
9.2 10.0 16.1 20 15 55
13.5 15 14 57
9.2 10.0 17.9 20 16 57
13.5 15 14 57
9.2 10.0 17.9 20 16 57
37.1/37.1 40/40 37/37 187/187
39.4/39.4 40/40 39/39 213/213
kW*
MCA MOCP† FLA LRA
DISCONNECT
SIZE
20
Page 21
Table 3 -- Electrical Data -- Units With Optional Powered Convenience Outlet (cont)
UNIT
50PG
NOMINAL
POWER SUPPLY
Volts -Ph-Hz
208/230-3-60 187 253 20.5 149 1.5 1.4
460-3-60 414 506 9.6 75 0.8
07
(cont)
575-3-60 518 633 7.6 54 0.8
FLA --- Fu l l Lo a d A mps HACR --- Heating, Air Conditioning and Refrigeration IFM --- Indoor (Evaporator) Fan Motor LRA --- L oc k ed Rot o r A mp s MCA --- Minimum Circuit Amps MOCP --- M aximum Overcurrent Protection NEC --- Natio nal Electrical Code OFM --- Outdoor (Condenser) Fan Motor RLA --- RatedLoadAmps
*Heater capacity (kW) is based o n heater voltage of 208v, 240v, 480v, or 600v. If power distribution voltage to unit varies from rated heater voltage, heater kW will vary accord­ingly. { Fuse or HACR ci rcuit breaker.
NOTES:
1. In comp liance with NE C require ments for multim otor and combin a tion load equip ment (refe r
2. Unbalanced 3- Phase Supply Voltage
% Voltage Imbalance = 100 x
LEGEND
to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. Canadian units may be fuse or circuit breaker.
Never operate a motor where a phase imb alance in supply voltage is greater than 2%.Use the following formula to deter mine the percentage of voltage imb alance.
VOLTAGE
RANGE
Min Max RLA LRA FLA
COMPRESSOR
OFM
FLA
max voltage deviation from average voltage
averag e voltage
POWER
EXHAUST
FLA
0.6
1.4
IFM
TYPE
Low 5.2
High 7.5
Low 2.6
High 3.4
Low 2.6
High 3.4
Low 2.0
High 2.8
Low 2.0
High 2.8
E xa mp le : S up p ly v ol ta ge i s 2 3 0 --- 3 ---6 0
Determine maxim um deviation from average voltage. (AB) 227 – 224 = 3 v (BC) 231 – 227 = 4 v (AC) 227 – 226 = 1 v Maximum deviation is 4 v. Deter mine per cent of voltage imbalance .
% Voltage Imbalance = 100 x
This amou nt of phase im balance is satisfactor y as it is be low the maxim um allowable 2%. IMPORTANT: If the supply voltage phase imb alance is more than 2 %, contact your local el ectric utility company immed iately.
ELECTRIC HEAT POWER SUPPLY
IFM FLA
10.0/11.5 3.8/ 5.0 38.5/38.5 40/40 38/38 189/189
15.0/17.3 5.6/ 7.5 38.5/38.5 40/40 38/38 189/189
20.0/23.1 7.5/10.0 39.3/43.1 40/45 38/40 189/189
30.0/34.6 11.3/15.0 51.8/57.5 60/60 48/53 189/189
40.0/46.2 15.0/20.0 64.3/72.0 70/80 59/66 189/189
50.0/57.7 18.8/25.0 76.8/86.4 80/90 71/79 189/189
10.0/11.5 3.8/ 5.0 40.8/40.8 45/45 41/41 215/215
15.0/17.3 5.6/ 7.5 40.8/40.8 45/45 41/41 215/215
20.0/23.1 7.5/10.0 42.1/46.0 45/50 41/42 215/215
30.0/34.6 11.3/15.0 54.6/60.4 60/70 50/56 215/215
40.0/46.2 15.0/20.0 67.1/74.9 70/80 62/69 215/215
50.0/57.7 18.8/25.0 79.6/89.3 80/90 73/82 215/215
11.5 10.0 20.4 25 19 94
17.3 15.0 27.6 30 25 94
23.1 20.0 34.9 35 32 94
28.9 25.0 42.1 45 39 94
11.5 10.0 21.4 25 20 107
17.3 15.0 28.6 30 26 107
23.1 20.0 35.9 40 33 107
28.9 25.0 43.1 45 40 107
11.5 10.0 21.1 25 19 95
17.3 15.0 28.4 30 26 95
23.1 20.0 35.6 40 33 95
28.9 25.0 42.9 45 39 95
11.5 10.0 22.1 25 20 108
17.3 15.0 29.4 30 27 108
23.1 20.0 36.6 40 34 108
28.9 25.0 43.9 45 40 108
13.9 15.0 22.0 25 20 69
18.5 20.0 27.8 30 26 69
23.1 25.0 33.5 35 31 69
27.7 30.0 39.3 40 36 69
13.9 15.0 23.0 25 21 80
18.5 20.0 28.8 30 26 80
23.1 25.0 34.5 35 32 80
27.7 30.0 40.3 45 37 80
13.9 15.0 23.8 25 22 71
18.5 20.0 29.5 30 27 71
23.1 25.0 35.3 40 32 71
27.7 30.0 41.0 45 38 71
13.9 15.0 24.8 25 23 82
18.5 20.0 30.5 35 28 82
23.1 25.0 36.3 40 33 82
27.7 30.0 42.0 45 39 82
Nominal
kW*
MCA MOCP† FLA LRA
38.5/38.5 40/40 38/38 189/189
40.8/40.8 45/45 41/41 215/215
17.6 20 17 94
5.8 5.0 17.6 20 17 94
8.7 7.5 17.6 20 17 94
18.4 20 18 107
5.8 5.0 18.4 20 18 107
8.7 7.5 18.4 20 18 107
18.2 20 18 95
5.8 5.0 18.2 20 18 95
8.7 7.5 18.2 20 18 95
19.0 20 19 108
5.8 5.0 19.0 20 19 108
8.7 7.5 19.0 20 19 108
14.0 15 14 69
9.2 10.0 16.1 20 15 69
14.8 15 15 80
9.2 10.0 17.1 20 16 80
15.4 20 16 71
9.2 10.0 17.9 20 16 71
16.2 20 16 82
9.2 10.0 18.9 20 17 82
AB = 224 v BC = 231 v AC = 226 v
Average Voltage =
= 1.76%
224 + 231 + 226
681
=
=
227
3
3
4
227
DISCONNECT
SIZE
50PG03--07
21
Page 22
Step 7 — Install Outdoor Air Hoods (Units with
/
/
/
Economizer)
Perform the following procedure to install the outdoor--air hoods:
1. Economizer and barometric relief hoods are located in the condenser section under the slanted coil for shipping. (See Fig. 14.) Barometric relief/power exhaust hood is shipped inside of economizer hood. Remove screws that secure the wooden rails of the hood assemblies to the unit. Save screws. Slide complete assembly from condenser section.
2. Remove the screws that secure the economizer and barometric relief/power exhaust hoods to the wooden railing. Discard or recycle wooden rails. Save screws.
3. The barometric relief damper is factory mounted onto the economizer panel for shipping. Remove the screw holding the barometric relief damper to the panel. Damper should be free to swing open during operation. (See Fig. 15.)
POWER EXHAUST
50PG03--07
4. Hang the barometric relief/power exhaust hood on the mounting flange on the economizer panel. Secure hood to panel with screws saved from Step 2. (See Fig. 15 and 16.)
5. Align hole in flange of economizer panel with left edge of hood. Hang economizer hood on the top flange of the economizer panel by rotating hood until top flange of the economizer hood engages the bent flange on the economizer panel. Rotate hood until hood is flush with the economizer panel. Hood will support itself from flange. Align holes in hood with holes in panel and secure hood to panel with screws saved from Step 2. (See Fig. 16 and 17.)
Step 8 — Install All Accessories
After all of the factory--installed options have been adjusted, install all field--installed accessories. Refer to the accessory installation instructions included with each accessory. Consult the Carrier Price Pages for accessory package numbers for particular applications.
BAROMETRIC RELIEF HOOD
POWER EXHAUST BAROMETRIC RELIEF HOOD
WOODEN RAILS
ECONOMIZER HOOD
Fig. 14 -- Economizer and Baromatric
Relief/Power Exhaust Hoods Shipping Positions
ECONOMIZER HOOD
POWER EXHAUST BAROMETRIC RELIEF HOOD
C06290
MOUNTING FLANGE
C06262
Fig. 16 -- Barometric Relief/Power Exhaust
Hood Flange
MOUNTING FLANGE
ECONOMIZER HOOD
ECONOMIZER PANEL
BAROMETRIC RELIEF DAMPER SCREW
C06260
Fig. 15 -- Hood Installation
Copyright 2010 Carrier Corp. S 7310 W. Morris St. S Indianapolis, IN 46231 Printed in U.S.A. Edition Date: 03/10
Manufacturer reserves the right to change, at any ti me, specifications and designs without notice and without obligations.
22
C06263
Fig. 17 -- Economizer Flange
Catalog No:50PG---40SI
Replaces: 50PG---36SI
Loading...