IMPORTANT: Read the entire instruction manual before
starting installation.
SAFETY CONSIDERATIONS
Installation and servicing of air-conditioning equipment can
be hazardous due to system pressure and electrical components.
Only trained and qualified service personnel should install,
repair, or service air-conditioning equipment.
Untrained personnel can perform basic maintenance functions of cleaning coils and filters and replacing filters. All other
operations should be performed by trained service personnel.
When working on air-conditioning equipment, observe precautions in the literature, tags and labels attached to the unit, and
other safety precautions that may apply.
Improper installation, adjustment, alteration, service, maintenance, or use can cause explosion, fire, electrical shock or other
conditions which may cause personal injury or property
damage. Consult a qualified installer, service agency, or your
distributor or branch for information or assistance. The qualified
installer or agency must use factory-authorized kits or accessories when modifying this product. Refer to the individual
instructions packaged with the kits or accessories when
installing.
Follow all safety codes. Wear safety glasses and work
gloves. Use quenching cloth for brazing operations. Have fire
extinguisher available. Read these instructions thoroughly and
follow all warnings or cautions attached to the unit. Consult
local building codes and applicable electrical codes for special
installation requirements.
Understand the signal words — DANGER, WARNING, and
CAUTION. DANGER identifies the most serious hazards
which will result in severe personal injury or death. WARNING
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53500052-01Printed in U.S.A.Form 50PEC-2SIPg 17-09Replaces: 50PEC-1SI
Page 2
signifies hazards that could result in personal injury or death.
CAUTION is used to identify unsafe practices, which would result in minor personal injury or product and property damage.
WARNING
Electrical shock can cause personal injury or death. Before
installing or servicing system, always turn off main power
to system. There may be more than one disconnect switch.
Turn off accessory heater power if applicable.
1. Compare the electrical data on the unit nameplate with
ordering and shipping information to verify that the correct unit has been shipped.
2. Keep both the chassis and cabinet covered with the shipping carton until all plastering, painting, and finish work
is complete and it is time to install the chassis and cabinet.
3. Verify that the refrigerant tubing is free of kinks or dents,
and that it does not touch other unit components.
4. Inspect all electrical connections. Connections must be
clean and tight at the terminals.
GENERAL
The 50PEC water source heat pump console unit is a decentralized room terminal designed for field connection to a
closed-circuit piping loop.
Units are typically installed in perimeter zones, usually under windows. Supply air is discharged directly into the conditioned space through discharge grilles located in the top of the
unit.
IMPORTANT: The installation of console water source heat
pump units and all associated components, parts, and accessories which make up the installation shall be in accordance
with the regulations of ALL authorities having jurisdiction
and MUST conform to all applicable codes. It is the responsibility of the installing contractor to determine and comply
with ALL applicable codes and regulations.
INSTALLATION
Step 1 — Check Jobsite —
stalled along an outside wall of the room. Refer to Fig. 1 and 2
for an illustration showing piping locations. Install units with
adequate clearance to allow maintenance and servicing. Refer
to Table 1 and Fig. 3-14. Locate the console unit so that it provides adequate air circulation throughout the room.
Installation, operation and maintenance instructions are
provided with each unit. Before unit start-up, read all manuals
and become familiar with the unit and its operation. Thoroughly
check out the system before operation. Complete the inspections
and instructions listed below to prepare a unit for installation.
Units are typically in-
CAUTION
To avoid equipment damage, do not use these units as a
source of heating or cooling during the construction process. The mechanical components and filters used in these
units quickly become clogged with construction dirt and
debris which may cause system damage.
CAUTION
To avoid the release of refrigerant into the atmosphere, the
refrigerant circuit of this unit must only be serviced by
technicians who meet local, regional, and national proficiency requirements.
CAUTION
All refrigerant discharged from this unit must be recovered
without exception. Technicians must follow industry
accepted guidelines and all local, regional, and national
statutes for the recovery and disposal of refrigerants.
CAUTION
When a compressor is removed from this unit, system
refrigerant circuit oil will remain in the compressor. To
avoid leakage of compressor oil, the refrigerant lines of the
compressor must be sealed after it is removed.
Table 1 — 50PEC Physical Data
BASE UNIT 50PEC09121518
NOMINAL COOLING CAPACITY (Btuh)
COMPRESSOR
BLOWER
Motor Horsepower
Wheel Size D x W (in.) 2 each
FILTER SIZE (in.) Bottom Return (Qty)
FILTER SIZE (in.) Front Return (Qty)
UNIT WEIGHT (lb)
Shipping
Operating
REF. TO AIR HEAT EXCHANGER
Face Area (sq ft)
No. of Rows Deep
Copper Tube Size OD (in.)
Fin Spacing (FPI)
REFRIG. CHARGE (R-410A)/CKT (oz)
No. of Circuits
UNIT CABINET WITH BOTTOM RETURN WITH STANDARD
5 in. SUBBASE Width x Height x Depth (in.)48 x 26 x 1248 x 26 x 1248 x 26 x 1254 x 26 x 12
UNIT CABINET WITH FRONT RETURN
(NO SUBBASE) Width x Height x Depth (in.)48 x 21 x 1248 x 21 x 1248 x 21 x 1254 x 21 x 12
WATER IN/OUT SIZE OD SWEAT (in.)
CONDENSATE SIZE ID VINYL (in.)
9,30012,30013,80016,000
Rotary
1
/
20
51/4 x 61/
4
10 x 30 x 1 (1)10 x 30 x 1 (1)10 x 30 x 1 (1)10 x 36 x 1 (1)
7 x 291/2 x 1/8 (1)7 x 291/2 x 1/8 (1)7 x 291/2 x 1/8 (1)7 x 351/2 x 1/8 (1)
*If optional subbase is selected, add 4.9 in. to dimension.
1. Dimensions shown are in inches. Dimensions in parentheses are in millimeters.
NOTES:
2. Optional autoflow valve, motorized water valve and disconnect box are shown.
Page 16
(76)
3.01
5.36
(187)
Hard Wire
Power Supply
not chassis)
Optional Fused
(mounted to cabinet
Disconnect Box
Optional
Autoflow
Valve
0.87
(22)
30˚
Power supply enters
Bottom of Box
Optional
(423)
16.66
Water Valve
Motorized
7.5
(191)
3.56
(90)
Power supply enters
Only Box (All Configurations)
Optional Disconnect
(87)
3.43
11.54
Bottom of Box
4.56
(116)
(293)
4.46
(113)
46.98
(1193)
Valve
Optional
Autoflow
Optional
Motorized
Water Valve
Control Box
Blower Deck
20.50
(521)
(19)
0.75
Panel
Access
Compressor
7.38
(187)
a50-8350
Blower Screen
(914)
36.00
Filter
(19)
0.75
4.49
(114)
46.98
(1193)
Control Box
Access
Compressor
Blower Deck
(521)
20.50
Panel
7.38
(187)
Filter
4.46
(113)
0.75
Blower Screen
0.75
(19)
(19)
36.00
(914)
Right Hand Configuration
Hard Wire
5.36
Power Supply
(136)
3.01
(76)
0.87
30˚
(22)
Valve
Optional
Autoflow
(423)
16.66
(87)
3.42
Optional
Motorized
Water Valve
7.50
(191)
3.56
(90)
(293)
11.54
Optional
not chassis)
Disconnect Box
(mounted to cabinet
Left Hand Configuration
Bottom of Box
Power supply enters
1. Dimensions shown are in inches. Dimensions in parentheses are in millimeters.
NOTES:
Fig. 14 — 50PEC18 Chassis Dimensions — Front Return
2. Optional autoflow valve, motorized water valve and disconnect box are shown.
3. Chassis can mount directly on floor.
16
Page 17
Step 2 — Check Unit — Upon receipt of shipment at
the jobsite, carefully check the shipment against the bill of lading. Make sure all units have been received. Inspect the carton
or crating of each unit, and inspect each unit for damage. Ensure the shipping company makes proper notation of any shortages or damage on all copies of the freight bill. Concealed
damage not discovered during unloading must be reported to
the shipping company within 15 days of receipt of shipment.
NOTE: It is the responsibility of the purchaser to file all necessary claims with the shipping company.
STORAGE
CAUTION
DO NOT store or install console units in corrosive environments or in locations subject to temperature or humidity
extremes (e.g., attics, garages, rooftops, etc.). Corrosive
conditions and high temperature or humidity can significantly reduce performance, reliability, and service life.
Always move units in an upright position. Tilting units on
their sides may cause equipment damage.
Upon the arrival of equipment at the jobsite, immediately
store units in their shipping cartons in a clean, dry area. Store
units in an upright position at all times. Stack units a maximum of 3 units high. Use pallets to separate each layer of
units. DO NOT remove equipment from shipping cartons
until equipment is required for installation.
UNIT PROTECTION — Cover console units on the jobsite
with either shipping cartons, vinyl film, or an equivalent
protective covering. Cap the open ends of pipes stored on the
jobsite. In areas where painting, plastering, or the spraying of
fireproof material has not been completed, all due precautions
must be taken to avoid physical damage to the units and contamination by foreign material. Physical damage and contamination may prevent proper start-up and may result in costly
equipment clean-up.
Examine all pipes, fittings, and valves before installing any
of the system components. Remove any dirt found on these
components.
Step 3 — Mount Unit
1. Unpack the unit from the shipping carton. Remove the
front cabinet by lifting up and away from the backplate.
Protect the cabinet from damage during installation by returning it to its original vinyl pack until required.
2. Remove compressor isolation plate shipping bolts (4), as
shown in Fig. 15.
3. Using a carpenter’s square and a level, ensure the unit
is level. Shim the unit if necessary to assure proper
installation.
Poor or inadequate installation may result in noisy
unit operation or unattractive appearance.
4. Select the proper fasteners to connect the backplate securely to the wall.
5. Fasten the backplate onto the wall through the screw holes
located in the back flange. Secure the subbase in place.
Step 4 — Wire Electrical Connections
WARNING
To avoid possible injury or death due to electrical shock,
open the power supply disconnect switch and secure it in
an open position during installation.
CAUTION
Use only copper conductors for field-installed electrical
wiring. Unit terminals are not designed to accept other
types of conductors.
All field-installed wiring, including the electrical ground,
MUST comply with National Electrical Code (NEC) as well as
all applicable local codes. In addition, all field wiring must
conform to the Class II temperature limitations described in the
NEC.
Consult the unit wiring diagram located on the inside of the
compressor access panel to ensure proper electrical hookup. The
installing (or electrical) contractor must make the field connections shown in Fig. 16 when using field-supplied disconnect.
Refer to unit wiring diagrams Fig. 17-29 for a schematic of
the field connections, which must be made by the installing (or
electrical) contractor. Operating voltage must be within voltage
range shown in Table 2.
Make all final electrical connections with a length of flexible conduit to minimize vibration and sound transmission to
the building.
SUPPLY VOLTAGE — Operating voltage to unit must be
within voltage range indicated on unit nameplate.
EXTERNAL LOOP POWER CONNECTION — If the unit
will be connected to an external loop pump or flow controller,
connect the pump to the loop pump terminal block PB1. The
maximum power handling is 4 amps at 240-v. The pumps will
automatically cycle as required by the unit.
230-V OPERATION — All 208/230-v units are factorywired for 208-v. The transformer wiring may be switched for
230-v operation (as illustrated on the wiring diagrams) by
switching the RED and ORG leads at L1.
SHIPPING
BOLTS
Fig. 15 — Remove 4 Shipping Bolts on
Compressor Isolator Plate
A
HEAT PUMP
A = Two power wires for single-phase units.
B = 1 heat/1 cool/manual or auto changeover remote 24-V thermostat.
NOTE: All customer-supplied wiring to be copper only and must conform to national and local electrical codes. Wiring shown with dashed lines must be
field-supplied and field-installed. “B” wiring only required with systems using remote-mounted thermostats.
B
FIELD SUPPLIED
DISCONNECT SWITCH
ROOM THERMOSTAT
Disconnect electrical power source to prevent injury or death from electrical shock.
Use copper conductors only to prevent equipment damage.
WARNING
CAUTION
Fig. 16 — Typical Field-Installed Wiring
17
Page 18
a50-8452
Complete C
AL— Alarm Relay Contacts
BM— Blower Motor
BR— Blower Relay
CAP— Capacitor
CB— Circuit Breaker
CO— Sensor, Condensate Overflow
CR— Compressor Relay
DM— Damper Motor
FP1— Sensor, Water Coil Freeze Protection
FP2— Sensor, Air Coil Freeze Protection
HP— High-Pressure Switch
JW1— Jumper Wire for Alarm
LOC— Loss of Charge Pressure Switch
PB— Power Terminal Block
RAS— Return Air Sensor
RVS— Reversing Valve Solenoid
TRANS
WV
----------Field Line Voltage Wiring
Transformer
—
Wate r Valve
—
Field Low-Voltage Wiring
Printed Circuit Trace
Option Low Voltage Wiring
LEGEND
Relay/Contactor Coil
Solenoid Coil
Thermistor
Circuit Breaker
Relay Contacts-N.O.
Switch-Temperature
Switch-High Pressure
Switch-Low Pressure
Ground
Wire Nut
>
>
Mate-N-Lok
*Optional wiring.
†Registered trademark of AMP Incorporated.
SEE NOTE 9
Complete C
BLOWER MOTOR WIRING
UNIT SIZEPOLE APOLE B
09-1854
NOTES:
1. Compressor and blower motor thermally protected internally.
2. All wiring to the unit must comply with local
codes.
3. Transformer is wired to 115-V (WHT) lead for
115/1/60 units; 265-V (BRN) lead for 265/1/60
units; or 208-V (RED) lead for 208/1/60 units.
For 230/1/60 operation, switch the RED and
ORG leads at L1 and insulate the RED lead.
Transformer is energy limiting or may have a
circuit breaker.
4. FP1 thermistor provides freeze protection for
WATER. When using ANTI-FREEZE solutions,
cut JW3 jumper.
5. For remote sensor, position jumper J1 on upper
2 pins.
6. For F position, position jumper on both pins.
°
For C, position jumper on one pin.
°
7. Transformer secondary ground via Complete C
board standoffs and screws to control box.
(Ground available from top two standoffs as
shown.)
8. Mate-N-Lok† plug is optional.
9. Factory-cut jumper (JW1). Dry contact will be
available between AL1 and AL2.
Fig. 17 — 50PEC Unit Manual or Auto Changeover with Complete C Controller Wiring
18
Page 19
COMPLETE C
COMPLETE C
a50-8327.eps
PEC
PEC12-18
PEC
AL— Alarm Relay Contacts
BM— Blower Motor
BR— Blower Relay
CAP— Capacitor
CB— Circuit Breaker
CO— Sensor, Condensate Overflow
CR— Compressor Relay
DM— Damper Motor
FP1— Sensor, Water Coil Freeze Protection
FP2— Sensor, Air Coil Freeze Protection
FSS— Fan Speed Switch
HP— High-Pressure Switch
JW1— Jumper Wire for Alarm
LOC— Loss of Charge Pressure Switch
PB— Power Terminal Block
RVS— Reversing Valve Solenoid
TRANS — Tr a n sf o r me r
WV— Water Valve
----------Field Line Voltage Wiring
Field Low-Voltage Wiring
Option Low-Voltage Wiring
Printed Circuit Trace
Fig. 18 — 50PEC Unit with Complete C and LON Controllers
LEGEND
Relay/Contactor Coil
Solenoid Coil
Thermistor
Circuit Breaker
Relay Contacts-N.O.
Switch-Temperature
Switch-High Pressure
Switch-Low Pressure
Ground
>
>
*Optional wiring.
†Registered trademark of Echelon Corporation.
Wire Nut
Mate-N-Lock
NOTES:
1. Compressor and blower motor thermally protected internally.
2. All wiring to the unit must comply with local
codes.
3. Transformer is wired to 115-V (WHT) lead for
115/1/60 units, 265-V (BRN) lead for 265/1/60
units, 240-V (ORG) lead for 240/1/50 units, or
208-V (RED) lead for 208/1/60 units.
Rewire transformer L1 connection if voltage is
230-1-60 or 220-1-50, insulate unused lead.
4. FP1 thermistor provides freeze protection for
WATER. When using ANTI-FREEZE solutions,
cut JW3 jumper.
5. Refer to LonWorks† Installation, Application, and
Operation manual for control wiring to the unit.
Low voltage wiring must be “class 1” and voltage
rated equal to or greater than unit supply
voltage.
6. Factory-cut jumper (JW1). Dry contact will be
available between AL1 and AL2.
7. Transformer secondary ground via Complete C
board standoffs and screws to control box.
(Ground available from top 2 standoffs as
shown.)
19
Page 20
DELUXE D
DELUXE D
AL— Alarm Relay Contacts
BM— Blower Motor
CAP— Capacitor
CB— Circuit Breaker
CO— Sensor, Condensate Overflow
CR— Compressor Relay
DM— Damper Motor
FP1— Sensor, Water Coil Freeze Protection
FP2— Sensor, Air Coil Freeze Protection
FSS— Fan Speed Switch
HP— High-Pressure Switch
JW1— Jumper Wire for Alarm
LOC— Loss of Charge Pressure Switch
PB— Power Terminal Block
RVS— Reversing Valve Solenoid
TRANS — Transformer
WV— Wate r Valve
----------Field Line Voltage Wiring
*Optional wiring.
Field Low-Voltage Wiring
Printed Circuit Trace
Fig. 19 — 50PEC Unit with Deluxe D and LON Controllers
a50-8328
LEGEND
Relay/Contactor Coil
Solenoid Coil
Thermistor
Circuit Breaker
Relay Contacts-N.O.
Switch-Temperature
Switch-High Pressure
Switch-Low Pressure
Ground
Wire Nut
>
>
Mate-N-Lock
NOTES:
1. Compressor and blower motor thermally protected internally.
2. All wiring to the unit must comply with local
codes.
3. Transformer is wired to 115-V (WHT) lead for
115/1/60 units, 265-V (BRN) lead for 265/1/60
units, 240-V (ORG) lead for 240/1/50 units, or
208-V (RED) lead for 208/1/60 units.
Rewire transformer L1 connection if voltage is
230-1-60 or 220-1-50, insulate unused lead.
4. FP1 thermistor provides freeze protection for
WATER. When using ANTI-FREEZE solutions,
cut JW3 jumper.
5. Refer to Microprocessor Control Installation,
Application, and Operation manual for control
wiring to the unit. Low voltage wiring must be
“class 1” and voltage rated equal to or greater
than unit supply voltage.
6. Factory-cut jumper (JW4). Dry contact will be
available between AL1 and AL2.
7. Transformer secondary ground via Deluxe D
board standoffs and screws to control box.
(Ground available from top 2 standoffs as
shown.)
20
Page 21
DELUXE D
AL— Alarm Relay Contacts
BM— Blower Motor
BR— Blower Relay
CAP— Capacitor
CB— Circuit Breaker
CO— Sensor, Condensate Overflow
CR— Compressor Relay
DM— Damper Motor
FP1— Sensor, Water Coil Freeze Protection
FP2— Sensor, Air Coil Freeze Protection
HP— High-Pressure Switch
JW1— Jumper Wire for Alarm
LOC— Loss of Charge Pressure Switch
NLL— Night Low Limit Switch
PB— Power Terminal Block
RAS— Return Air Sensor
RVS— Reversing Valve Solenoid
TRANS — Transformer
WV— Wate r Valve
----------Field Line Voltage Wiring
*Optional wiring.
Field Low-Voltage Wiring
Printed Circuit Trace
LEGEND
Relay/Contactor Coil
Solenoid Coil
Thermistor
Circuit Breaker
Relay Contacts-N.O.
Switch-Temperature
Switch-High Pressure
Switch-Low Pressure
Ground
Wire Nut
>
>
Mate-N-Lock
DELUXE D
a50-8329
PEC09-18
NOTES:
1. Compressor and blower motor thermally protected internally.
2. All wiring to the unit must comply with local
codes.
3. Transformer is wired to 115-V (WHT) lead for
115/1/60 units, 265-V (BRN) lead for 265/1/60
units, 240-V (ORG) lead for 240/1/50 units, or
208-V (RED) lead for 208/1/60 units.
Rewire transformer L1 connection if voltage is
230-1-60 or 220-1-50, insulate unused lead.
4. FP1 thermistor provides freeze protection for
WATER. When using ANTI-FREEZE solutions,
cut JW3 jumper.
5. Refer to Microprocessor Control Installation,
Application, and Operation manual for control
wiring to the unit. Low voltage wiring must be
“class 1” and voltage rated equal to or greater
than unit supply voltage.
6. Factory-cut jumper (JW4). Dry contact will be
available between AL1 and AL2.
7. Transformer secondary ground via Deluxe D
board standoffs and screws to control box.
(Ground available from top 2 standoffs as
shown.)
Fig. 20 — 50PEC Unit Manual or Auto Changeover and Deluxe D Controller
21
Page 22
POWER SUPPLY
REFER TO DATA PLATE
USE COPPER CONDUCTORS ONLY.
SEE NOTE 2
REFER TO DISCONNECT
BOX FOR OPTIONAL
POWER SUPPLY CONNECTION
OPTIONAL
CORD
CONNECTION
CB*
24V
GROUND
L2
L1
SEE
NOTE 3
TRANS
L2 (ribbed)
L1 (plain)
BLK
ORG
230V
NEUTRAL ON 265V
SYSTEMS
2
PB
1
GROUND
RED
BLK
COM
8
4
BM
FSS
COMPRESSOR
BLU
R
RED
BLK
B (HIGH)
A (LOW)
RED
1
S
C
BLK
H
CAP
6
RED
C
NO
BLK
BRN
YEL
BLK
CR
2
2
1
2
F
BR
CAP
TYPICAL HEAT PUMP T-STAT
SEE NOTE 5
CLASS 1 OR 2
WIRING ACCEPTABLE
OUTSIDE
CONTROL BOX
Y
O
G
R
C
L
BRNYEL
GROUND
PB
BLK
RED
(220V)
ORG (240V)
WV
TRANSFORMER
CR
BR
SEE
NOTE 7
TRANS
CB
24V
BLU
BRN
CLASS 1 WIRING
REQUIRED INSIDE
CONTROL BOX
COMPRESSOR
COOLING
FAN
24 VAC
COMMON
ALARM
YEL
C
R
Y
W
O
G
R
C
AL1
AL2
A
P1
Y
ORGYEL
DM
10
BR
BR BRG CCG
TEST PINS
SEE
NOTE 4
JW3
FP1
JW2
FP2
DIP SWITCH
JW1
OFF ON
SEE
ALARM
NOTE 6
RELAY
BRNYEL
10
CR
BRNBRNGRYYEL
1
PM: DISABLED/
ENABLED
2
STAGE 2: 2/1
3
NOT USED
4
NOT USED
5
FP1/FP2
FAULTS: 3/1
G
COMPLETE C
MICRO-
PROCESSOR
CONTROL
LOGIC
CC
COMPR.
RELAY
STATUS
LED
TRANSFORMER PRIMARY
SEE
NOTE 7
YELBRN
1
HP
2
3
LOC
4
5
FP1
6
7
FP2
8
9
RV
10
CO12
P2
24V
DC
EH1
EH2
P3
CO
LEAD COLORS
VOLTAGE
RED
RED
BLU
BRN
GRY
GRY
VIO
VIO
BRN
ORG
NOT USED
YEL
115
208
230
265
LEAD COLOR
WHT
RED
ORG
BRN
HP
LOC
FP1
SEE
NOTE 4
FP2
RVS
CO
BLOWER MOTOR WIRING
UNIT SIZE POLE A POLE B
0954
1243
1543
1843
COMPLETE
C
CONTROL
LEGEND
AL— Alarm Relay Contacts
BM— Blower Motor
BR— Blower Relay
CAP— Capacitor
CB— Circuit Breaker
CO— Sensor, Condensate Overflow
CR— Compressor Relay
DM— Damper Motor
FP1— Sensor, Water Coil Freeze Protection
FP2— Sensor, Air Coil Freeze Protection
FSS—Fan Speed Switch
HP—High-Pressure Switch
JW1— Jumper Wire for Alarm
LOC— Loss of Charge Pressure Switch
PB—Power Terminal Block
PM— Performance Monitor
RVS— Reversing Valve Solenoid
TRANS — Transformer
WV— Water Valve
----------Field Line Voltage Wiring
Field Low-Voltage Wiring
Fig. 21 — 50PEC Unit Remote-Mounted Thermostat with Complete C Controller Wiring
Printed Circuit Trace
Option Low Voltage
Wiring
Relay/Contactor Coil
Solenoid Coil
Thermistor
Circuit Breaker
Relay Contacts-N.O.
Switch-High Pressure
Switch-Low Pressure
Ground
Wire Nut
>
>
Mate-N-Lock
22
*Optional wiring.
NOTES:
1. Compressor and blower motor thermally
protected internally.
2. All wiring to the unit must comply with
local codes.
3. Transformer is wired to 115-V (WHT) lead
for 115/1/60 units; 265-V (BRN) lead for
265/1/60 units; or 208-V (RED) lead for
208/1/60 units.
For 230/1/60 operation, switch the RED
and ORG leads at L1 and insulate the
RED lead.
Transformer is energy limiting or may
have a circuit breaker.
4. FP1 thermistor provides freeze protection
for WATER. When using ANTI-FREEZE
solutions, cut JW3 jumper.
5. Typical heat pump thermostat wiring
shown. Refer to thermostat Installation
Instructions for wiring to the unit.
6. 24-V alarm signal shown. For dry alarm
contact, cut JW1 jumper and dry contact
will be available between AL1 and AL2.
7. Transformer secondary ground via Complete C board standoffs and screws to
control box. (Ground available from top
two standoffs as shown.)
Page 23
POWER SUPPLY
REFER TO DATA PLATE
CAP
DELUXE
D
CONTROL
BR 2
(HI)
USE COPPER CONDUCTORS ONLY.
CLASS 1 OR 2 WIRING
ACCEPTABLE
OUTSIDE
CONTROL BOX
Y
O
G
R
C
X1
TYPICAL HEAT
PUMP T-STAT
SEE NOTE 5
BRN
BRN
ORG
YELYEL YEL
DM
GROUND
PB
OVERRIDE
WITH DIGITAL T-STAT
OV
OV
LUG
SEE NOTE 2
REFER TO DISCONNECT
BOX FOR OPTIONAL
POWER SUPPLY CONNECTION
OPTIONAL
CORD
CONNECTION
BRN
CLASS 1 WIRING
REQUIRED INSIDE
CLOSED=UNOCCUPIED
NLL
SEE
NOTE 7
COMPRESSOR
COOLING
FAN
24 VAC
COMMON
ALARM
RED
TIME CLOCK
BRN
WHT
YEL
WV
RED
OVERRIDE
OVERRIDE
TRANSFORMER
CR
BR 1
(LO)
LEGEND
AL— Alarm Relay Contacts
BM— Blower Motor
BR— Blower Relay
CAP— Capacitor
CB— Circuit Breaker
CO— Sensor, Condensate Overflow
CR— Compressor Relay
DM— Damper Motor
FP1— Sensor, Water Coil Freeze Protection
FP2— Sensor, Air Coil Freeze Protection
FSS— Fan Speed Switch
HP— High-Pressure Switch
JW1— Jumper Wire for Alarm
LOC— Loss of Charge Pressure Switch
NLL— Night Low Limit
OV— Override
PB— Power Terminal Block
PM— Performance Monitor
RVS— Reversing Valve Solenoid
TRANS — Transformer
WV— Water Valve
---------- Field Line Voltage Wiring
Fig. 22 — 50PEC Unit Remote-Mounted Thermostat with Deluxe D Controller Wiring
Y1
Y1
W1
O/W2
G
R
C
AL1
P2
AL2
NSB
ESD
OVR
P3
R
NO1
NC1
COM
NO2
NC2
COM
R
GROUND
6
2
1
2
3
4
5
6
7
8
9
10
CCG
CR
CC
8
4
2
BM
1
3
FSS
RED
RED
BLU
BRN
GRY
GRY
VIO
VIO
BRN
ORG
NOT USED
YEL
BRN
YEL
BLU
RED
2
COMPRESSOR
S
R
C
BLK
B (HIGH)
A (LOW)
RED
BLK
TRANSFORMER PRIMARY
LEAD COLORS
1
VOLTAGE
1
BLOWER MOTOR WIRING
CR
UNIT SIZE POLE A POLE B
0
115
208
230
265
HP
LOC
FP1
FP2
RVS
CO
LEAD COLOR
SEE
NOTE
4
WHT
RED
ORG
BRN
0954
1243
1543
1843
NEUTRAL ON 265V
SYSTEMS
L2
L1
CB*
TRANS
24V
YEL
BLU
C
1
2
3
4
5
6
7
8
ACC1
RELAY
ACC2
RELAY
R
ALARM
RELAY
SEE
NOTE 6
AL2 DRY
OFF ON
S1
DIP SWITCH
PACKAGE
P1
R
C
H
A
2
PB
1
L2 (ribbed)
GROUND
L1 (plain)
BLK
ORG
230V
SC
R C S
COM2 COM1
JW4
TEST
PINS
1
PM: DISABLE/
ENABLE
2
UNIT STAGE: 2/1
3
T-STAT: HEAT COOL/
HEAT PUMP
4
RV ON B/RV ON O
5
DEHUMID/NORMAL
6
NOT USED
7
BOILERLESS:
ENABLE/DISABLE
8
BOILERLESS:
40°F/50°F
RED
SEE
NOTE 3
DELUXE D
MICROPROCESSOR
CONTROL LOGIC
JW3
FP1 LOW
JW2
FP2 LOW
JW1
LP N.O.
OFF ON
DIP SWITCH
PACKAGE
STATUS
SEE
NOTE 4
S2
H
CAP
RED
C
F
BLK
FAN ENABLE
GRY
COM
NO
GRY
COM
NONC
G
Y
TEST
R
FAULT
RV
RELAY
1
ACC1
2
FUNCTIONS
3
4
ACC2
5
FUNCTIONS
6
7
H: HI FAN/DEHUMID
8
NOT USED
BRN
YEL
RELAY
FAN
SPEED
RELAY
HP
LOC
FP1
FP2
RV
CO12
P7
24V
DC
EH1
EH2
P6
COMPR.
RELAY
*Optional wiring.
NOTES:
1. Compressor and blower motor thermally
protected internally.
2. All wiring to the unit must comply with local
Field Low-Voltage Wiring
Printed Circuit Trace
Option Low Voltage Wiring
Relay/Contactor Coil
Solenoid Coil
Thermistor
Circuit Breaker
Relay Contacts-N.O.
Switch-High Pressure
Switch-Low Pressure
Ground
Wire Nut
>
>
Mate-N-Lock
codes.
3. Transformer is wired to 115-V (WHT) lead
for 115/1/60 units; 265-V (BRN) lead for 265/
1/60 units; or 208-V (RED) lead for 208/1/60
units.
For 230/1/60 operation, switch the RED and
ORG leads at L1 and insulate the RED lead.
Transformer is energy limiting or may have a
circuit breaker.
4. FP1 thermistor provides freeze protection
for WATER. When using ANTI-FREEZE
solutions, cut JW3 jumper.
5. Typical heat pump thermostat wiring shown.
Refer to thermostat Installation Instructions
for wiring to the unit.
6. 24-V alarm signal shown. For dry alarm contact, cut AL2 DRY (JW4) jumper and dry
contact will be available between AL1 and
AL2.
7. Transformer secondary ground via Deluxe D
board standoffs and screws to control box.
(Ground available from top two standoffs as
shown.)
23
Page 24
PREMIER
LINK
PWR
HS1/EXH/RVS
CR
CR
COMPLETE
C
CONTROL
Y
W
O
LEGEND
CR — Control Relay
LWT — Leaving Water Temperature Sensor
SAT — Supply Air Temperature Sensor
SPT — Space Temperature Sensor
NOTE: Reversing valve is on in Cooling mode.
J6
S
P
T
J5
L
S
A
W
T
T
Fig. 23 — PremierLink™ Controller Applications with Complete C Control
J8
PWR
J1
CMPSAFE
PREMIER
LINK
CMP1
FAN
PWR
G
R
C
AL1
AL2
A
J4
DELUXE
D
CONTROL
LEGEND
LWT — Leaving Water Temperature Sensor
SAT — Supply Air Temperature Sensor
SPT — Space Temperature Sensor
NOTE: Reversing valve is on in Cooling mode.
J6
S
P
T
J5
L
S
A
W
T
T
Fig. 24 — PremierLink Controller Applications with Deluxe D Control
J8
PWR
J1
CMPSAFE
HS2
HS1
CMP2
CMP1
FAN
Y1
Y2
W1
O/W2
G
R
C
AL1
J4
24
Page 25
Fig. 25 — Units with Complete C and WSHP Open Multiple Protocol Controls
WHSP-OPEN
A50-8355
25
LEGEND
BM— Blower Motor
BR— Blower Relay
CO— Condensate Overflow
LWT — Leaving Water Temperature
N.C. — Normally Closed
OAD — Outside Air Damper
OCC — Occupancy Input Contact
RH— Relative Humidity
SAT — Supply Air Temperature
SPT — Space Temperature
Page 26
Fig. 26 — Units with Deluxe D and WSHP Open Multiple Protocol Controls
WSHP-OPEN
A50-8354
26
LEGEND
BM— Blower Motor
CO— Condensate Overflow
LWT — Leaving Water Temperature
N.C. — Normally Closed
OAD — Outside Air Damper
OCC — Occupancy Input Contact
RH— Relative Humidity
SAT — Supply Air Temperature
SPT — Space Temperature
Page 27
A50-8356
27
WSHP-OPEN
LEGEND
CO— Condensate Overflow
LWT — Leaving Water Temperature
N.C. — Normally Closed
OAD — Outside Air Damper
OCC — Occupancy Input Contact
RH— Relative Humidity
SAT — Supply Air Temperature
SPT — Space Temperature
Fig. 27 — Units with Complete C, ECM and WSHP Open Multiple Protocol Controls
Page 28
A50-8353
28
WSHP-OPEN
LEGEND
CO— Condensate Overflow
LWT — Leaving Water Temperature
N.C. — Normally Closed
OAD — Outside Air Damper
OCC — Occupancy Input Contact
RH— Relative Humidity
SAT — Supply Air Temperature
Fig. 28 — Units with Deluxe D, ECM and WSHP Open Multiple Protocol Controls
SPT — Space Temperature
Page 29
CHANNEL
DESIGNATION
CONNECTION
PIN NUMBERS
Factory Wiring
Field Wiring
N/AAO (0-10Vdc/2 - 10Vdc)J2 4 and 5*Analog Output 1
N/ABO Relay (24VAC, 1A)J1, 4*Binary Output 1 (G)
Outside Air DamperN/AAO (0-10Vdc/2 - 10Vdc)J22 1 and 2*Analog Output 2
located at the end of network
Gnd
N/ABO Relay (24VAC, 1A)J1, 5*Binary Output 2
Rnet+
Rnet-
+12V
Supply Fan On/Low Speed
(3 Speed Only)
Auxiliary Heat or 2-Position Water Loop
Economizer
Reversing Valve (B or O Operation)N/ABO Relay (24VAC, 1A)J1, 6*Binary Output 3 (RV)
WATER FREEZE PROTECTION — The Aquazone™ control allows the field selection of source fluid freeze protection
points through jumpers. The factory setting of jumper JW3
(FP1) is set for water at 30 F. In earth loop applications, jumper
JW3 should be clipped to change the setting to 10 F when
using antifreeze in colder earth loop applications. See Fig. 30.
FAN MOTO R
FLA
TOTAL UN IT
FLA
MIN CIRCUIT
AMPS
MAX
FUSE/HACR
WATER SOLENOID VALVES — An external solenoid
valve(s) should be used on ground water installations to shut
off flow to the unit when the compressor is not operating. A
slow closing valve may be required to help reduce water
hammer. Figure 31 shows typical wiring for a 24-vac external
solenoid valve. Figures 32 and 33 illustrate typical slow closing
water control valve wiring for Taco 500 Series and Taco ESP
Series valves. Slow closing valves take approximately 60 sec.
to open (very little water will flow before 45 sec.). Once fully
open, an end switch allows the compressor to be energized
(only on valves with end switches). Only relay or triac based
electronic thermostats should be used with slow closing valves.
When wired as shown, the slow closing valve will operate
properly with the following notations:
1. The valve will remain open during a unit lockout.
2. The valve will draw approximately 25 to 35 VA through
the “Y” signal of the thermostat.
a50-7467tf
AQUAZONE CONTROL (Complete C Control Shown)
Fig. 30 — Typical Aquazone Control Board
Jumper Locations
ACCESSORY CONNECTIONS — Terminal labeled A on
the control is provided to control accessory devices such as
water valves, electronic air cleaners, humidifiers, etc. This
signal operates with the compressor terminal. See Fig. 31.
Refer to the specific unit wiring schematic for details.
NOTE: The A terminal should only be used with 24-v signals
— not line voltage signals.
Terminal Strip
C
Typical
24 VAC
A
Water
Valve
IMPORTANT: Connecting a water solenoid valve can
overheat the anticipators of electromechanical thermostats. Only use relay based electronic thermostats.
C
1Y
a50-8441
1
2
HEATER SWITCH
1Y
C
THERMOSTAT
AMV
3
TACO VALVE
Fig. 32 — AMV Valve Wiring
Fig. 31 — Typical Aquazone Accessory Wiring
a50-8442
Fig. 33 — Taco SBV Valve Wiring
30
Page 31
OPTIONAL WALL-MOUNTED THERMOSTAT — The
50PEC water source heat pump units are built with standard internal thermostats in either manual changeover (MCO) or automatic changeover (ACO) configuration. Refer to Fig. 17-20.
When desired, the unit can be furnished with a 24-v control
circuit which is field wired to a Carrier-supplied accessory remote thermostat. Most heat pump thermostats can be used with
the controller. Use a thermostat with Y, G, O and W outputs.
Refer to unit wiring diagrams in Fig. 21 and 22 and Aquazone
Controls, Operation, and Troubleshooting Instructions for additional information.
Vendor installation instructions and additional installation
information is shipped with each thermostat.
NOTE: Low-voltage wiring between the unit and the wall thermostat must comply with all applicable electrical codes
(i.e., NEC and local codes), and be completed before the unit is
installed.
Table 3 lists recommended wire sizes and lengths to install
the thermostat. The total resistance of low-voltage wiring must
not exceed 1 ohm. Any resistance in excess of 1 ohm may
cause the control to malfunction because of high voltage drop.
Table 3 — Recommended Thermostat Wire Sizes
WIRE SIZEMAX WIRE LENGTH*
18-Gage75 ft
16-Gage125 ft
14-Gage200 ft
*Length = Physical distance from thermostat to unit.
OPTIONAL PREMIERLINK™ CONTROLLER — This direct digital controller (DDC) allows the water source heat
pump to be incorporated into a Carrier Comfort Network
(CCN) system installation. PremierLink control is factoryinstalled with the Complete C controller, or field-installed with
the Deluxe D control option. Refer to Fig. 23 and 24.
WSHP OPEN WIRING — The WSHP Open controller will
be factory wired to the Complete C or Deluxe D control board,
however, the system wiring will need to be completed utilizing
WSHP Open controller wiring diagrams and the Third Party
Integration (TPI) Guide. Factory installation includes harness,
LWT (leaving water temperature), supply air, and condensate
sensor.
WARNING
Disconnect all power to the unit before performing maintenance or service. Unit may automatically start if power is
not disconnected. Failure to follow this warning could
cause personal injury, death, and/or equipment damage.
Wiring Sensors to Inputs
WSHP Open controller’s inputs. See Table 4.
All field control wiring that connects to the WSHP Open controller must be routed through the raceway built into the corner
post. The raceway provides the UL required clearance between
high and low-voltage wiring.
1. Pass control wires through the hole provided in the corner
post.
2. Feed the wires through the raceway to the WSHP Open
controller.
3. Connect the wires to the removable Phoenix connectors.
4. Reconnect the connectors to the board.
— Sensors can be wired to the
Field-Supplied Sensor Hardware
— The WSHP Open controller is configurable with the following field-supplied sensors. See Table 4.
Table 4 — Field-Supplied Sensors for
WSHP Open Controller
SENSORNOTES
Space Temperature Sensor
Indoor Air Quality Sensor
Space Relative Humidity
NOTE: BACview6 Handheld or Virtual BACview can be used as the
user interface.
(SPT)
Outdoor Air
Temperature Sensor
(Separate Sensor)
Sensor
Field Installed (Must be used with
WSHP Open controller.)
Network Sensor
Required only for demand
control ventilation.
Separate Sensor
For specific details about sensors, refer to the literature sup-
plied with the sensor.
Wiring a SPT Sensor
— A WSHP Open controller is connected to a wall-mounted space temperature (SPT) sensor to monitor room temperature using a Molex plug.
The WSHP Open system offers the following SPT sensors.
See Table 5.
Table 5 — SPT Sensors
SENSOR
SPT
Standard
®
SPT PlusSPPL
SPT ProSPP
SPT Pro
Plus
*The SPT Pro Plus fan speed adjustment has no effect in this
application.
PA RT
NUMBER
SPS
SPPF
FEATURES
• Local access port
• No operator control
• Slide potentiometer to adjust set point
• Manual on button to override schedule
• LED to show occupied status
• Local access port
•LCD display
• Manual on button to override schedule
• Warmer and cooler buttons to adjust set
point
• Info button to cycle through zone and
outside air temperatures, set points, and
local override time
• Local access port
• LCD display
• Manual on button to override schedule
• Warmer and cooler buttons to adjust set
point
• Info button to cycle through zone and
outside air temperatures, set points, and
local override time
• Local access port
• Fan speed*
Wire SPT sensors to the WSHP Open controller’s Rnet port.
An Rnetbus can consist of any of the following combinations
of devices wired in a daisy-chain configuration:
• 1 SPT Plus, SPT Pro, or SPT Pro Plus sensor
• 1 to 4 SPT Standard sensors
• 1 to 4 SPT Standard sensors and 1 SPT Plus, SPT Pro, or
SPT Pro Plus sensor
• Any of the above combinations, plus up to 2 BACview
6
Handheld but no more than 6 total devices
NOTE: If the Rnetbus has multiple SPT Standard sensors, each
sensor must be given a unique address on the Rnetbus. See the
Carrier Open Sensor Installation Guide.
Use the specified type of wire and cable for maximum signal
integrity. See Table 6.
31
Page 32
Table 6 — Rnet Wiring Specifications
RNET WIRING SPECIFICATIONS
Description
Conductor18 AWG
Maximum Length500 ft
Recommended Coloring
UL Temperature32 to 167 F
Volt ag e300-vac, power limited
ListingUL: NEC CL2P, or better
LEGEND
AWG — American Wire Gage
CMP — Communications Plenum Cable
NEC — National Electrical Code
UL— Underwriters Laboratories
4 conductor, unshielded, CMP,
plenum rated cable
Wiring: black, white, green, red
Jacket: white
To wire the SPT sensor to the controller:
1. Partially cut , then bend and pull off the outer jacket of
the Rnet cable(s), being careful not to nick the inner
insulation.
2. Strip about
1
/4 in. of the inner insulation from each wire.
See Fig. 34.
OUTER JACKET
a50-8443
.25 IN.
INNER INSULATION
Fig. 34 — Rnet Cable Wire
3. Wire each terminal on the sensor to the same terminal on
the controller. See Fig. 25-29. Table 7 shows the recommended Rnet wiring scheme.
Table 7 — Rnet Wiring
WIRETERMINAL
Red+12-v
Black.Rnet
WhiteRnet+
GreenGnd
NOTE: The wire should be connected to the terminal shown.
–
Wiring a Supply Air Temperature (SAT) Sensor — The
SAT sensor is required for reheat applications.
If the cable used to wire the SAT sensor to the controller
will be less than 100 ft, an unshielded 22 AWG (American
Wire Gage) cable should be used. If the cable will be greater
than 100 ft, a shield 22 AWG cable should be used. The cable
should have a maximum length of 500 ft.
To wire the SAT sensor to the controller:
1. Wire the sensor to the controller. See Fig. 25-29.
2. Verify that the Enable SAT jumper is on.
3. Verify that the Enable SAT and Remote jumper is in the
left position.
Wiring an Indoor Air Quality (IAQ) Sensor
sensor monitors CO
levels. The WSHP Open controller uses
2
— An IAQ
this information to adjust the outside-air dampers to provide
proper ventilation. An IAQ sensor can be wall-mounted or
mounted in a return air duct. (Duct installation requires an aspirator box assembly.)
The sensor has a range of 0 to 2000 ppm and a linear 4 to
20 mA output. This is converted to 1 to 5 vdc by a 250-ohm,
1
/4 watt, 2% tolerance resistor connected across the zone con-
troller’s IAQ input terminals.
NOTE: Do not use a relative humidity sensor and CO
sensor
2
on the same zone controller if both sensors are powered off the
board. If sensors are externally powered, both sensors may be
used on the same zone controller.
If the cable used to wire the IAQ sensor to the controller
will be less than 100 ft, an unshielded 22 AWG (American
Wire Gage) cable should be used. If the cable will be greater
than 100 ft, a shield 22 AWG cable should be used. The cable
should have a maximum length of 500 ft.
To wire the IAQ sensor to the controller:
1. Wire the sensor to the controller. See Fig. 25-29.
2. Install a field-supplied 250-ohm,
1
/4 watt, 2% tolerance
resistor across the controller’s RH/IAQ and Gnd
terminals.
3. Verify the the RH/IAQ jumper is set to 0 to 5-vdc.
Wiring a Relative Humidity (RH) Sensor
— The RH sensor
is used for zone humidity control (dehumidification) if the
WSHP unit has a dehumidification device. If not, the sensor
only monitors humidity.
NOTE: Do not use a relative humidity sensor and CO
on the same zone controller if both sensors are powered off the
board. If sensors are externally powered, both sensors may be
used on the same zone controller.
If the cable used to wire the RH sensor to the controller will
be less than 100 ft, an unshielded 22 AWG (American Wire
Gage) cable should be used. If the cable will be greater than
100 ft, a shield 22 AWG cable should be used. The cable
should have a maximum length of 500 ft.
To wire the RH sensor to the controller:
1. Strip the outer jacket from the cable for at least 4 inches.
2. Strip
1
/4 in. of insulation from each wire.
3. Wire the sensor to the controller.
Step 6 — Install Supply and Return Piping
CAUTION
To ensure proper functioning of unit and system, be sure to
connect entering water to upper pipe on right-hand units.
On left-hand units, connect entering water to lower pipe.
Failure to do so could result in equipment damage.
SUPPLY AND RETURN HOSES — Optional pressure-rated
hose assemblies are available for use with units. Use the following guidelines when installing supply and return hose
assemblies.
1. Install supply and return hoses fitted with swivel-joint
fittings at one end to prevent the hose from twisting.
2. Use male adapters to secure the hose assembly to the unit
and the riser.
3. Do not allow the hose to twist during installation. Twisting may damage the hose wall or the rubber compound.
4. Use pipe joint compound sparingly on the fitting adapters’ male pipe threads.
5. Prevent sealant from reaching the joint’s flared surfaces.
6. Do not use pipe joint compound when Teflon* thread
tape is pre-applied to hose assemblies or when flared-end
connections are used.
7. Maximum torque that may be applied to brass fittings is
30 ft-lb. When a torque wrench is not used, tighten brass
fittings finger-tight plus one quarter turn.
8. Tighten steel fittings as necessary.
9. Use shut-off/balancing valves, flow indicators, and drain
tees in the supply runout and return at each floor to aid in
loop balancing and servicing.
SUPPLY AND RETURN PIPING — System piping MUST
comply with all applicable codes.
1. Install a drain valve at the base of each supply and return
riser to enable system flushing at start-up and during routine servicing.
*Teflon is a trademark of E. I. du Pont de Nemours and Company.
32
sensor
2
Page 33
2. Install shut-off/balancing valves and unions at each unit
to allow unit removal for servicing.
NOTE: If flex hoses are used, unions are not necessary.
3. Install strainers at the inlet of each system circulating
pump.
PRE-START-UP
System Cleaning and Flushing —
flushing the unit and system is the single most important step to
ensure proper start-up and continued efficient operation of the
system.
Cleaning and
IMPORTANT: Since loop temperatures are normally
between 60 and 90 F, pipe sweating and heat loss do not
occur at normal ambient temperature conditions. Insulation
must be installed on loop water piping on those sections
that run through unheated areas or are located outside the
building. If loop temperatures are expected below the
ambient dew point, the optional internal insulation
(extended range) package must be ordered.
CAUTION
DO NOT bend or kink supply lines or hoses. Damage to
unit may result.
4. Before making the final water connections, flush the system as described in the Pre-Start-Up section of this
manual. After flushing the system, connect piping and
hoses to the proper supply, return and condensate connections of the unit.
NOTE: When necessary, use adapters to connect hoses.
5. Install any other system components, as required, following manufacturer’s instructions.
6. Reinstall the front cabinet by carefully lowering the front
cabinet over the chassis onto the backplate.
Step 7 — Install Condensate Piping — Connect
the unit condensate drain to the building condensate drain with
a flexible, nonpressure-rated
Avoid kinks in this hose to ensure an unobstructed flow of condensate from the unit to the drain.
The horizontal run of the condensate hose is usually too
short to pose any drainage problems, however, the horizontal
run of condensate line should be pitched at least 1 in. for every
10 ft of run (in the direction of flow). Avoid low points and unpitched piping since dirt collects in these areas and may cause
stoppage and overflow.
Field installation of a trap or vent is not required unless
specified by local codes. The 50PEC units are designed in a
blow-thru configuration. The condensate drain pan is located
on the outlet side of the blower so that the pressure in the drain
pan is higher than the atmospheric pressure.
5
/8-in. (16 mm) ID plastic hose.
WARNING
To prevent injury or death due to electrical shock or contact
with moving parts, open unit disconnect before servicing
unit.
Follow the instructions below to properly clean and flush
the system:
CAUTION
DO NOT FLUSH SYSTEM THROUGH THE UNIT!
1. Verify that electrical power to the units is disconnected,
and that the circulation pump is deenergized.
2. Connect the supply hose directly to the return riser valve.
Use a single length of flexible hose, as shown in Fig. 35.
NOTE: If the length of hose is too short (i.e., the resulting connection would exceed the minimum bend radius of the hose),
substitute two lengths of flexible hose joined together with a
field-supplied, standard NPT coupling and the flare-fitting-topipe adapters provided with the hose kit (Fig. 35).
3. Open all air vents. Fill the system with water. Do not allow system to overflow. Bleed all air from the system.
Check the system for leaks and repair appropriately.
4. Check and adjust the water and air level in the expansion
tank.
5. Verify all strainers are in place. Start the pumps, and systematically check each vent to ensure all air is bled from
the system.
6. Verify make-up water is available. Adjust make-up water
appropriately to replace the air that was bled from the
system. Pressure test and inspect the system for leaks and
make any necessary repairs. Check and adjust the water
and air level in the expansion tank.
7. Open a drain at the lowest point in the system. Adjust the
make-up water replacement rate to equal the rate of bleed.
Continue to bleed the system until the water appears
clean or for at least three hours, whichever is longest;
then, completely drain the system.
Supply Valve
Floor Line
1/2” Flexible Hose
Brass Adapter
(1/2” MPT x 1/2”
Male Flare)
Return Valve
NOTE: Use standard coupling (field-supplied)
and hose adapters to join 2 hoses.
Fig. 35 — Temporary Connection for Flushing System Piping
33
Page 34
8. Refill the system with clean, chemically treated water.
Since water varies for each locality, contact a local water
treatment company for the correct treatment chemicals to
use in the area. Set the boiler to raise the loop temperature
to approximately 85 F.
.
CAUTION
To avoid possible damage to piping systems constructed of
plastic piping DO NOT allow loop temperature to exceed
110 F.
Circulate the solution for a minimum of 8 to 24 hours. At
the end of this period, shut off the circulating pump and
drain the solution. Repeat system cleaning as necessary.
9. When the cleaning process is complete, remove the shortcircuited hoses. Connect the hoses to the proper supply
and return connections on each unit. Refill the system and
bleed off all air.
10. Test the system pH with litmus paper. The system water
should be slightly alkaline (pH 7.0 to 8.5). Add chemicals, as appropriate, to maintain acidity levels.
3. System Water pH: Verify system water is slightly alkaline
(pH = 7.5 to 8.5). Proper pH promotes the longevity of
the hoses and heat exchangers. See Table 9.
4. Closed-Type Cooling Tower (Open Tower with Heat Exchanger): Check equipment for proper temperature set
points and operation.
5. Balanced Water Flow Rate to Heat Pump: Record the
inlet and outlet water temperatures as each heat pump
unit is started. This check will eliminate nuisance unit
tripouts resulting from water velocities that are either too
low or too high; it can also prevent erosive water flow
rates.
6. Standby Pump: Verify the standby pump is properly installed and in operating condition.
7. System Control: To ensure no catastrophic system failures occur, verify system controls are functioning and the
sequencing is correct.
8. Freeze Protection for Water Systems: Verify freeze
protection is provided for the outdoor portion of the loop
water system. Inadequate freeze protection leads to
expensive repairs.
CAUTION
DO NOT use “Stop-Leak” or any similar chemical agent in
this system. Addition of these chemicals to the loop water
will foul the system and will inhibit unit operation.
11. When the system is successfully cleaned, flushed, refilled
and bled, check the main system panels, safety cutouts
and alarms. Set the controls to properly maintain loop
temperatures.
System Checkout — When the installation is complete
and the system is cleaned and flushed, follow the system
checkout procedure outlined below.
1. Voltage: Ensure voltage is within the utilization range
specifications of the unit compressor and fan motor.
2. System Water Temperature: Ensure temperature is within
an acceptable range shown in Table 8. (When conducting
this check, also verify proper heating and cooling set
points.)
Table 8 — Air and Water Limits
50PEC UNITCOOLING (F)HEATING (F)
Min Ambient Air5050
Rated Ambient Air8070
Max Ambient Air10085
Min Entering Air5050
Rated Entering Air, dry bulb/wet bulb80/6770
Max Entering Air, dry bulb/wet bulb100/8380
Min Entering Water3020
Normal Entering Water8570
Max Entering Water11090
NOTES:
1. Minimum air and water conditions can only be used at nominal flow rates.
2. 50PEC units may have up to two values at maximum or minimum with all
other parameters at normal conditions.
3. Operating limits shown are for start-up, not continuous operation. It is
assumed that such a start-up is for the purpose of bringing the space to
desired occupancy temperature.
CAUTION
To avoid equipment damage, DO NOT leave system filled
in a building without heat during the winter unless antifreeze is added to system water. Condenser coils never
fully drain by themselves and will freeze unless winterized
with antifreeze.
9. System Water Loop: Verify all air is bled from the system. Air in the system impedes unit operation and causes
corrosion in the system piping.
10. Unit Filters: To avoid system damage and to provide
maximum performance, ensure the unit filter is clean.
11. Unit Fans: Manually rotate fans to assure free rotation.
Ensure fans are properly secured to the fan shaft. Do not
oil fan motors on start-up since they are lubricated at the
factory.
12. System Control Center: To ensure control of the temperature set points for operation of the system’s heat rejector
and boiler, examine the system control and alarm panel
for proper installation and operation.
34
Page 35
Table 9 — Water Quality Guidelines
CONDITION
Scaling Potential — Primary Measurement
Above the given limits, scaling is likely to occur. Scaling indexes should be calculated using the limits below.
pH/Calcium
Hardness Method
Index Limits for Probable Scaling Situations (Operation outside these limits is not recommended.)
Scaling indexes should be calculated at 150 F for direct use and HWG applications, and at 90 F for indirect HX use. A monitoring plan should be
implemented.
Ryznar Stability Index
Langelier Saturation Index
Iron Fouling
Iron Fe2+ (Ferrous)
(Bacterial Iron Potential)
Iron Fouling
Corrosion Prevention††
pH
Hydrogen Sulfide (H2S)
Ammonia Ion as Hydroxide,
Chloride, Nitrate and Sulfate
Compounds
Maximum Chloride LevelsMaximum allowable at maximum water temperature.
Erosion and Clogging
Particulate Size and Erosion
Brackish
LEGEND
HWG — Hot Water Generator
HX— Heat Exchanger
N/A — Design Limits Not Applicable Considering Recirculating
NR— Application Not Recommended
SS— Stainless Steel
*Heat exchanger materials considered are copper, cupronickel, 304 SS
(stainless steel), 316 SS, titanium.
†Closed recirculating system is identified by a closed pressurized piping
system.
**Recirculating open wells should obser ve the open recirculating design
<10 ppm of particles and a
maximum velocity of 6 fps.
6 - 8.5
Filtered for maximum
800 micron size.
OPEN LOOP AND RECIRCULATING WELL**
6.0 - 7.5
If >7.5 minimize steel pipe use.
–0.5 to +0.5
Based upon 150 F HWG and direct well, 85 F indirect well HX.
If Fe2+ (ferrous) >0.2 ppm with pH 6 - 8, O2<5 ppm check for iron bacteria.
Minimize steel pipe below 7 and no open tanks with pH <8.
At H2S>0.2 ppm, avoid use of copper and cupronickel piping of HXs.
Copper alloy (bronze or brass) cast components are okay to <0.5 ppm.
50 F (10 C)75 F (24 C)100 F (38 C)
<20 ppmNRNR
<10 ppm (<1 ppm “sandfree” for reinjection) of par ticles and a maximum
velocity of 6 fps. Filtered for maximum 800 micron size. Any particulate that
is not removed can potentially clog components.
Use cupronickel heat exchanger when concentrations of calcium or sodium
chloride are greater than 125 ppm are present. (Seawater is approximately
25,000 ppm.)
††If the concentration of these corrosives exceeds the maximum allow-
able level, then the potential for serious corrosion problems exists.
Sulfides in the water quickly oxidize when exposed to air, requiring that
no agitation occur as the sample is taken. Unless tested immediately
at the site, the sample will require stabilization with a few drops of one
Molar zinc acetate solution, allowing accurate sulfide determination up
to 24 hours after sampling. A low pH and high alkalinity cause system
problems, even when both values are within ranges shown. The term
pH refers to the acidity, basicity, or neutrality of the water supply.
Below 7.0, the water is considered to be acidic. Above 7.0, water is
considered to be basic. Neutral water contains a pH of 7.0.
To convert ppm to grains per gallon, divide by 17. Hardness in mg/l is
equivalent to ppm.
If <–0.5 minimize steel pipe use.
<0.2 ppm (Ferrous)
<0.5 ppm of Oxygen
Above this level deposition will occur.
6 - 8.5
<0.5 ppm
Rotten egg smell appears at 0.5 ppm level.
<0.5 ppm
35
Page 36
FIELD SELECTABLE INPUTS
Jumpers and DIP (dual in-line package) switches on the
control board are used to customize unit operation and can be
configured in the field.
IMPORTANT: Jumpers and DIP switches should only
be clipped when power to control board has been turned
off.
Complete C Control Jumper Settings (See
Fig. 17, 18, and 21)
WATER COIL FREEZE PROTECTION (FP1) LIMIT
SETTING — Select jumper 3, (JW3-FP1 Low Temp) to
choose FP1 temperature limit of 10 F or 30 F. To select 30 F as
the temperature limit, DO NOT clip the jumper. To select 10 F
as the limit, clip the jumper.
ALARM RELAY SETTING — Select jumper 1 (JW1) for
connecting alarm relay terminal (AL2) to 24-vac (R) or to remain as a dry contact (no connection). To connect AL2 to R, do
not clip the jumper. To set as dry contact, clip the jumper.
Complete C Control DIP Switches — The Com-
plete C control has one DIP switch block with five switches.
See Fig. 17, 18, and 21.
PERFORMANCE MONITOR (PM) — DIP switch 1 will
enable or disable this feature. To enable the PM, set the switch
to ON. To disable the PM, set the switch to OFF.
STAGE 2 — DIP switch 2 will enable or disable compressor
delay. Set DIP switch to OFF for Stage 2 in which the compressor will have a 3-second delay before energizing.
SWITCH 3 AND SWITCH 4 — Not used.
FREEZE PROTECTION (FP1) — DIP switch 5 is used to
initiate one or 3 tries for the FP1 fault. If there is water freeze
protection for the water coil then DIP switch 5 can be set to
lock out on the FP1 fault after one try. ON = One try.
OFF = 3 tries.
Deluxe D Control Jumper Settings (See Fig. 19,
20, and 22)
WATER COIL FREEZE PROTECTION (FP1) LIMIT
SETTING — Select jumper 3, (JW3-FP1 Low Temp) to
choose FP1 temperature limit of 10 F or 30 F. To select 30 F as
the temperature limit, DO NOT clip the jumper. To select 10 F
as the limit, clip the jumper.
ALARM RELAY SETTING — Select jumper 4 (JW4-AL2
Dry) for connecting alarm relay terminal (AL2) to 24-vac (R)
or to remain as a dry contact (no connection). To connect AL2
to R, do not clip the jumper. To set as dry contact, clip the
jumper.
LOW PRESSURE SETTING — The Deluxe D control can
be configured for low pressure setting (LP). Select jumper 1
(JW1-LP Norm Open) for choosing between low pressure input normally opened or closed. To configure for normally
closed operation, do not clip the jumper. To configure for normally open operation, clip the jumper.
Deluxe D Control DIP Switches — The Deluxe D
control has 2 DIP switch blocks. Each DIP switch block has
8 switches and is labeled either S1 or S2 on the circuit board.
See Fig. 19, 20, and 22.
DIP SWITCH BLOCK 1 (S1) — This set of switches offers
the following options for Deluxe D control configuration:
Performance Monitor (PM)
able performance monitor. To enable the PM, set the switch to
ON. To disable the PM, set the switch to OFF.
Compressor Relay Staging Operation
able or disable compressor relay staging operation. The
— Set switch 1 to enable or dis-
— Switch 2 will en-
compressor relay can be set to turn on with Stage 1 or Stage 2
call from the thermostat. This setting is used with dual stage
units (units with 2 compressors and 2 Deluxe D controls) or in
master/slave applications. In master/slave applications, each
compressor and fan will stage according to its switch 2 setting.
If switch is set to Stage 2, the compressor will have a 3-second
delay before energizing during stage 2 demand.
NOTE: If DIP switch is set for Stage 2, the alarm relay will not
cycle during Test mode.
Heating/Cooling Thermostat Type
— Switch 3 provides selection of thermostat type. Heat pump or heat/cool thermostats
can be selected. Select OFF for heat/cool thermostats. When in
heat/cool mode, Y1 is used for Cooling Stage 1, Y2 is used for
Cooling Stage 2, W1 is used for Heating Stage 1 and O/W2 is
used for Heating Stage 2. Select ON for heat pump applications. In heat pump mode, Y1 used is for Compressor Stage 1,
Y2 is used for Compressor Stage 2, W1 is used for Heating
Stage 3 or emergency heat, and O/W2 is used for RV (heating
or cooling) depending upon switch 4 setting.
O/B Thermostat Type
— Switch 4 provides selection for heat
pump O/B thermostats. O is cooling output. B is heating output. Select ON for heat pumps with O output. Select OFF for
heat pumps with B output.
Dehumidification Fan Mode
— Switch 5 provides selection
of normal or dehumidification fan mode. Select OFF for dehumidification mode. The fan speed relay will remain OFF during Cooling Stage 2. Select ON for normal mode. The fan
speed relay will turn on during Cooling Stage 2 in normal
mode.
Switch 6
Boilerless Operation
— Not used.
— Switch 7 provides selection of boilerless operation and works in conjunction with switch 8. In boilerless operation mode, only the compressor is used for heating
when FP1 is above the boilerless changeover temperature set
by switch 8 below. Select ON for normal operation or select
OFF for boilerless operation.
Boilerless Changeover Temperature
— Switch 8 on S1 provides selection of boilerless changeover temperature set point.
Select OFF for set point of 50 F or select ON for set point of
40 F.
If switch 8 is set for 50 F, then the compressor will be used
for heating as long as the FP1 is above 50 F. The compressor
will not be used for heating when the FP1 is below 50 F and the
compressor will operate in emergency heat mode, staging on
EH1 and EH2 to provide heat. If a thermal switch is being used
instead of the FP1 thermistor, only the compressor will be used
for heating mode when the FP1 terminals are closed. If the FP1
terminals are open, the compressor is not used and the control
goes into emergency heat mode.
DIP SWITCH BLOCK 2 (S2) — The following set of DIP
switches is used to configure accessory relay options.
Switches 1 to 3
— These DIP switches provide selection of
Accessory 1 relay options. See Table 10 for DIP switch
combinations.
Table 10 — DIP Switch Block S2 —
Accessory 1 Relay Options
ACCESSORY 1
RELAY OPTIONS
Digital NSBOffOnOn
Water Valve — Slow OpeningOnOffOn
LEGEND
NSB — Night Setback
NOTE: All other DIP switch combinations are invalid.
DIP SWITCH POSITION
123
Switches 4 to 6 — These DIP switches provide selection of
Accessory 2 relay options. See Table 11 for DIP switch
combinations.
36
Page 37
Table 11 — DIP Switch Block S2 —
Accessory 2 Relay Options
ACCESSORY 2
RELAY OPTIONS
Digital NSBOffOnOn
Water Valve — Slow OpeningOnOffOn
LEGEND
NSB — Night Setback
NOTE: All other switch combinations are invalid.
DIP SWITCH POSITION
456
Auto Dehumidification Mode or High Fan Mode — Switch
7 provides selection of auto dehumidification fan mode or high
fan mode. In auto dehumidification fan mode, the fan speed
relay will remain off during Cooling Stage 2 if terminal H is
active. In high fan mode, the fan enable and fan speed relays
will turn on when terminal H is active. Set the switch to ON for
auto dehumidification fan mode or to OFF for high fan mode.
Switch 8
— Not used.
Deluxe D Control Accessory Relay Configurations —
ble for Deluxe D control only:
CYCLE WITH COMPRESSOR — In this configuration, the
relay will be ON any time the compressor relay is on.
DIGITAL NIGHT SETBACK (NSB) — In this configura-
tion, the relay will be ON if the NSB input is connected to
ground C.
NOTE: If there are no relays configured for digital NSB, then
the NSB and OVR (override) inputs are automatically configured for mechanical operation.
MECHANICAL NIGHT SETBACK — When NSB input is
connected to ground C, all thermostat inputs are ignored. A
thermostat setback heating call will then be connected to the
OVR input. If OVR input becomes active, then the Deluxe D
control will enter night low limit (NLL) staged heating mode.
The NLL staged heating mode will then provide heating during
the NSB period.
WATER VALVE (SLOW OPENING) — If relay is configured for water valve (slow opening), the relay will start 60 seconds prior to starting compressor relay.
The following accessory relay settings are applica-
CAUTION
To avoid equipment damage, DO NOT leave system filled
in a building without heat during the winter unless antifreeze is added to system water. Condenser coils never
fully drain by themselves and will freeze unless winterized
with antifreeze.
START-UP
Use the procedure outlined below to initiate proper unit
start-up:
IMPORTANT: This equipment is designed for indoor
installation ONLY.
WARNING
When the disconnect switch is closed, high voltage is
present in some areas of the electrical panel. Exercise caution when working with the energized equipment.
1. Adjust all valves to the full open position and turn on the
line power to all heat pump units.
2. Operate each unit in the Cooling mode first.
Room temperature should be in the normal range
(i.e., approximately 50 to 80 F dry bulb). Loop water temperature entering the heat pumps should be at least 40 F
but not in excess of 110 F. Refer to Table 8 for more specific information on the operating parameters of units.
IMPORTANT: Three factors determine the operating limits
of a unit: (1) return-air temperature, (2) water temperature
and (3) ambient temperature. Whenever any one of these
factors is at a minimum or maximum level, the other two
factors must be at normal levels to ensure proper unit operation. Flow rates must be at nominal ARI (Air Conditioning and Refrigeration Institute)/ISO (International
Organization for Standardization)/ ASHRAE (American
Society of Heating, Refrigerating and Air Conditioning
Engineers) 13256-1 standards.
Unit Start-Up/Cooling
1. Turn the unit thermostat to the cooling position and turn
the fan speed switch to “HI.” If the unit has an optional
MCO thermostat, set the selector switch to Cool. Both the
fan and compressor should run.
2. Check for cool air delivery at unit grille 15 minutes after
the unit has begun operating. List the identification number of any machines that do not function at this time.
3. Check the elevation and cleanliness of the condensate
lines; any dripping could be a sign of a blocked line.
4. Select low fan speed. Airflow should decrease and compressor should operate.
5. Slowly turn thermostat toward warmer position. Both fan
and compressor should shut off when thermostat set point
equals room temperature. Room temperature must be
below 90 F for unit to shut off.
6. Operate each heat pump in the heating cycle immediately
after checking cooling cycle operation. A time delay will
prevent the compressor from re-starting for approximately 5 minutes.
Operating Limits
ENVIRONMENT — This equipment is designed for indoor
installation ONLY.
POWER SUPPLY — A voltage variation of ± 10% of nameplate utilization voltage is acceptable.
50PEC UNIT STARTING CONDITIONS — The 50PEC
units will start and operate at an ambient temperature of 50 F
with entering-air temperature at 50 F, entering water at 60 F,
and with both air and water at the flow rates used in the
ARI/ISO/ASHRAE Standard 13256-1 rating test, for initial
start-up in winter.
IMPORTANT: These operating limits are not normal or
continuous operating conditions. It is assumed that such a
start-up is for the purpose of bringing the building space up
to occupancy temperature.
Unit Start-Up/Heating
1. Adjust the unit thermostat to the warmest setting and turn
the fan speed switch to “HI.” If the unit has an optional
MCO thermostat, set the selector switch to Heat. The
blower should start immediately and after the time delay
is complete, the compressor will start.
2. Once the unit has begun to run, check for warm air delivery
at the unit grille. Again, the installing contractor must list
the serial number of any machine that does not function.
3. Log the unit operating conditions at initial start-up for
each unit to establish a permanent operating record.
4. Select low fan speed. Airflow should decrease and compressor should continue to operate.
37
Page 38
5. Slowly turn thermostat toward cooler position. Both fan
and compressor should shut off when thermostat set point
equals room temperature. Room temperature must be
above 65 F for unit to shut off.
Unit Start-Up with WSHP Open Controls —
The WSHP Open is a multi-protocol (default BACnet*) controller with extensive features, flexible options and powerful
capabilities. The unit comes from the factory pre-programmed
and needs minimal set up to function in a BAS (Building
Automation System) system or provide additional capabilities
to Carrier's WSHP product line. Most settings on the controller
have factory defaults set for ease of installation. There are a
few settings that must be configured in the field and several
settings that can be adjusted if required by unique job conditions. Refer to Appendix A — WSHP Open Screen Configuration. In order to configure the unit, a BACview
required. See Fig. 36.
NOTE: If the WSHP Open control has lost its programming,
all display pixels will be displayed on the SPT sensor. See the
WSHP Third Party Integration Guide.
When the unit is OFF, the SPT sensor will indicate OFF.
When power is applied, the SPT sensor will indicate temperature in the space at 78 F.
To start-up a unit with WSHP Open controls:
1. To plug in the BACview
6
handheld display into a SPT
sensor,point the two ears on the connector up and tilt the
bottom of the plug toward you. Insert the plug up into the
SPT sensor while pushing the bottom of the plug away
from you.
2. BACview
6
should respond with "Establishing Connection." The Home screen will then appear on the display
showing operating mode and space temperature. Press
any button to continue.
See Appendix A — WSHP Open Screen Configuration
for the hierarchal structure of the WSHP Open controller.
All functions of the controller can be set from the Home
screen.
3. When the Login is requested, type 1111 and push the OK
softkey. The Logout will then be displayed to indicate the
password was accepted.
4. To set the Clock if it is not already displayed:
a. Select System Settings from the Home screen, then
press Clockset.
b. Scroll to hour, minute and second using the arrow
keys. Use the number keypad to set actual time.
6
display is
c. Scroll to day, month and year using arrow keys.
Use number keypad to set date.
5. To set Daylight Savings Time (DST):
a. Push the DST softkey. The display will indicate
02:00:060 which is equal to 2:00AM.
b. To program the beginning and end dates, scroll
down to the beginning month and press the enter
key. The softkeys (INCR and DECR) will activate
to increment the month in either direction, Jan,
Feb, March, etc.
c. Use number keys to select the day of month and
year.
d. Push the OK softkey to finalize the data.
6. To view configuration settings:
a. Select the Config softkey.
b. Select the Service Config softkey. Scroll through
the factory settings by using the up and down
arrow keys. See below for factory settings.
Only the following settings will need to be
checked.
• # of Fan Speeds — This should be set to "1" for
units with PSC motors and set to "3" for units with
ECM motors.
• Compressor Stages — This should be set to "1."
• Factory Dehumidification Reheat Coil — This
should be set to "none" unless the modulating hot
water reheat option is supplied in the unit, then set
to "installed."
• The condenser water limit needs to be verified
depending on design parameters and application,
whether geothermal or boiler/tower.
7. To view unit configuration settings:
a. Select the Unit Configuration softkey, then select
Unit.
b. Scroll through the unit settings by using the up and
down arrow keys. Unit settings include:
• Fan Mode: Default Continuous
• Fan Delay:
• Minimum SAT Cooling: Default 50 F
• Maximum SAT Heating: Default 110 F
• Filter Service Alarm: Must be set from 0 to 9999 hr
8. To set local schedules:
a. Select the Schedule softkey from the Configuration
screen, then press enter.
a50-8444
Fig. 36 — BACview6 Display Interface
*Sponsored by ASHRAE (American Society of Heating, Refrigerating and Air Conditioning Engineers).
38
Page 39
b. Select Weekly, then press enter (7 schedules
available).
c. Select day and press enter.
d. Press enter again and select ADD or DEL (DECR
or INCR) set schedule.
e. Enter ON/OFF time, then press continue.
f. Press OK to apply and save to a particular day of
the week.
g. Continue to add the same or different schedule spe-
cific days of the week.
To add exceptions to the schedule:
i. Press Add softkey.
ii. Select exception type from following:
• Date
• Date Range
• Week-N-Day
• Calender Reference
9. Go back to Home Screen.
10. Remove BACview
6
cable from SPT sensor by reversing
the process in Step 1.
11. Perform system test.
Flow Regulation — Flow regulation can be accom-
plished by two methods. Most water control valves have a
built-in flow adjustment valve. Determine the flow rate by
measuring the pressure drop through the unit heat exchanger.
See Table 12. Adjust the water control valve until a flow of 1.5
to 2 gpm per ton cooling is achieved. Since the pressure
constantly varies, two pressure gages may be needed.
An alternative method for regulating flow is to install a flow
control device. These devices are typically an orifice of plastic
material mounted on the outlet of the water control valve,
designed to allow a specified flow rate. Occasionally these
valves produce a velocity noise that can be reduced by
applying some back pressure. To accomplish this, slightly close
the leaving isolation valve of the water regulating device.
CAUTION
DO NOT use “Stop Leak” or any similar chemical agent in
this system. Addition of these chemicals to the loop water
will foul the system and inhibit unit operation.
Antifreeze — In areas where entering loop temperatures
drop below 40 F or where piping will be routed through areas
subject to freezing, antifreeze is needed.
Alcohols and glycols are commonly used as antifreeze
agents. Freeze protection should be maintained to 15 F below the
lowest expected entering loop temperature. For example, if the
lowest expected entering loop temperature is 30 F, the leaving
loop temperature would be 22 to 25 F. Therefore, the freeze protection should be at 15 F (30 F –15 F) = 15 F.
IMPORTANT: All alcohols should be pre-mixed and
pumped from a reservoir outside of the building or introduced under water level to prevent alcohols from fuming.
Calculate the total volume of fluid in the piping system. See
Table 13. Use the percentage by volume in Table 14 to determine the amount of antifreeze to use. Antifreeze concentration
should be checked from a well mixed sample using a hydrometer to measure specific gravity.
FREEZE PROTECTION SELECTION — The 30 F FP1 factory setting (water) should be used to avoid freeze damage to
the unit.
Once antifreeze is selected, the JW3 jumper (FP1) should
be clipped on the control to select the low temperature
(antifreeze 10 F) set point to avoid nuisance faults.
Table 12 — Coaxial Water Pressure Drop
UNIT
50PEC
Cv— Flow Coefficient
MOPD — Maximum Operating Pressure Differential
09
12
15
18
FLOW
(GPM)
1.31.82.01.31.51.21.31.01.2
1.93.23.62.52.92.22.72.02.4
2.55.05.83.94.63.54.23.03.8
1.61.86.51.66.51.46.51.36.5
2.33.311.42.911.42.611.42.311.4
3.15.319.64.519.64.119.63.719.6
1.81.21.61.21.61.11.51.01.4
2.72.63.42.23.12.02.91.92.7
3.64.25.73.55.03.24.83.04.5
2.42.12.82.02.61.82.41.62.3
3.64.25.83.75.23.34.93.04.6
4.86.89.66.08.85.58.24.97.7
Without
Motorized
Valve
LEGEND
30 F50 F70 F90 F
With Cv = 2.9
MOPD = 125 psi
Without
Motorized
Valve
PRESSURE DROP (ft wg)
With Cv = 2.9
MOPD = 125 psi
Without
Motorized
Val ve
With Cv = 2.9
MOPD = 125 psi
Without
Motorized
Valve
With Cv = 2.9
MOPD = 125 psi
39
Page 40
Table 13 — Approximate Fluid Volume (gal)
per 100 ft of Pipe
PIPEDIAMETER (in.)VOLUME (gal.)
Copper14.1
Rubber Hose13.9
Polyethylene
IPS— Internal Pipe Size
SCH — Schedule
SDR — Standard Dimensional Ratio
NOTE: Volume of heat exchanger is approximately 1.0 gallon.
LEGEND
1.256.4
1.59.2
3
/4 IPS SDR112.8
1 IPS SDR114.5
1
1
/4 IPS SDR118.0
1
/2 IPS SDR1110.9
2 IPS SDR1118.0
1
1
/4 IPS SCH408.3
1
1
/2 IPS SCH4010.9
2 IPS SCH4017.0
Table 14 — Antifreeze Percentages by Volume
ANTIFREEZE
Methanol (%)25211610
100% USP Food Grade
Propylene Glycol (%)
MINIMUM TEMPERATURE FOR FREEZE
PROTECTION (F)
10152025
38302215
Cooling Tower/Boiler Systems — These systems
typically use a common loop maintained at 60 to 90 F. Carrier
recommends using a closed circuit evaporative cooling tower
with a secondary heat exchanger between the tower and the
water loop. If an open type cooling tower is used continuously,
chemical treatment and filtering will be necessary.
Ground Coupled, Closed Loop and Plateframe
Heat Exchanger Well Systems — These systems al-
low water temperatures from 30 to 110 F. The external loop
field is divided up into 2 in. polyethylene supply and return
lines. Each line has valves connected in such a way that upon
system start-up, each line can be isolated for flushing using only
the system pumps. Air separation should be located in the piping system prior to the fluid re-entering the loop field.
OPERATION
Power Up Mode —
inputs, terminals and safety controls are checked for normal
operation.
NOTE: The compressor will have a 5-minute anti-short cycle
delay upon power up.
The unit will not operate until all the
Units with Aquazone™ Complete C Control
STANDBY — The Y and W terminals are not active in Standby mode, however the O and G terminals may be active, depending on the application. The compressor will be off.
COOLING — The Y and O terminals are active in Cooling
mode. After power up, the first call to the compressor will initiate a 5 to 80-second random start delay and a 5-minute antishort cycle protection time delay. After both delays are complete, the compressor is energized.
NOTE: On all subsequent compressor calls the random start
delay is omitted.
HEATING STAGE 1 — Terminal Y is active in Heating
Stage 1. After power up, the first call to the compressor will
initiate a 5 to 80-second random start delay and a 5-minute
anti-short cycle protection time delay. After both delays are
complete, the compressor is energized.
NOTE: On all subsequent compressor calls the random start
delay is omitted.
HEATING STAGE 2 — To enter Stage 2 mode, terminal W is
active (Y is already active). Also, the G terminal must be active
or the W terminal is disregarded. The compressor relay will remain on and EH1 (emergency heat) is immediately turned on.
EH2 will turn on after 10 minutes of continual Stage 2 demand.
NOTE: EH2 will not turn on (or if on, will turn off) if FP1
(freeze protection) temperature is greater than 45 F and FP2 is
greater than 110 F.
EMERGENCY HEAT — In Emergency Heat (EH) mode,
terminal W is active while terminal Y is not. Terminal G must
be active or the W terminal is disregarded. EH1 is immediately
turned on. EH2 will turn on after 5 minutes of continuous
emergency heat demand.
Units with Aquazone Deluxe D Control
STANDBY/FAN ONLY — The compressor will be off. The
fan enable, fan speed, and reversing valve (RV) relays will be
on if inputs are present. If there is a Fan 1 demand, the fan
enable will immediately turn on. If there is a Fan 2 demand, the
fan enable and fan speed will immediately turn on.
NOTE: DIP switch 5 on S1 does not have an effect upon Fan 1
and Fan 2 outputs.
HEATING STAGE 1 — In Heating Stage 1 mode, the fan enable and compressor relays are turned on immediately. Once
the demand is removed, the relays are turned off and the control reverts to Standby mode. If there is a master/slave or dual
compressor application, all compressor relays and related
functions will operate per their associated DIP switch 2 setting
on S1.
HEATING STAGE 2 — In Heating Stage 2 mode, the fan enable and compressor relays remain on. The fan speed relay is
turned on immediately and turned off immediately once the demand is removed. The control reverts to Heating Stage 1 mode.
If there is a master/slave or dual compressor application, all
compressor relays and related functions will operate per their
associated DIP switch 2 setting on S1.
HEATING STAGE 3 — In Heating Stage 3 mode, the fan enable, fan speed and compressor relays remain on. The EH1 output is turned on immediately. With continuing Heat Stage 3 demand, EH2 will turn on after 10 minutes. EH1 and EH2 are
turned off immediately when the Heating Stage 3 demand is removed. The control reverts to Heating Stage 2 mode.
Output EH2 will be off if FP1’s temperature is greater than
45 F AND FP2 (when shorted) is greater than 110 F during
Heating Stage 3 mode. This condition will have a 30-second
recognition time. Also, during Heating Stage 3 mode, EH1,
EH2, fan enable, and fan speed will be ON if G input is not
active.
EMERGENCY HEAT — In Emergency Heat mode, the fan
enable and fan speed relays are turned on. The EH1 output is
turned on immediately. With continuing emergency heat demand, EH2 will turn on after 5 minutes. Fan enable and fan
speed relays are turned off after a 60-second delay. The control
reverts to Standby mode.
Output EH1, EH2, fan enable, and fan speed will be ON if
the G input is not active during Emergency Heat mode.
COOLING STAGE 1 — In Cooling Stage 1 mode, the fan
enable, compressor and RV relays are turned on immediately.
If configured as stage 2 (DIP switch set to OFF) then the compressor and fan will not turn on until there is a stage 2 demand.
The fan enable and compressor relays are turned off immediately when the Cooling Stage 1 demand is removed. The control reverts to Standby mode. The RV relay remains on until
there is a heating demand. If there is a master/slave or dual
compressor application, all compressor relays and related functions will track with their associated DIP switch 2 on S1.
COOLING STAGE 2 — In Cooling Stage 2 mode, the fan
enable, compressor and RV relays remain on. The fan speed relay is turned on immediately and turned off once the Cooling
Stage 2 demand is removed. The control reverts to Cooling
Stage 1 mode. If there is a master/slave or dual compressor
40
Page 41
application, all compressor relays and related functions will
track with their associated DIP switch 2 on S1.
NIGHT LOW LIMIT (NLL) STAGED HEATING — In NLL
staged Heating mode, the override (OVR) input becomes
active and is recognized as a call for heating and the control
will immediately go into a Heating Stage 1 mode. With an
additional 30 minutes of NLL demand, the control will go into
Heating Stage 2 mode. With another additional 30 minutes of
NLL demand, the control will go into Heating Stage 3 mode.
Units with WSHP Open Multiple Protocol —
The WSHP Open multi-protocol controller will control mechanical cooling, heating and waterside economizer outputs
based on its own space temperature input and set points. An
optional CO
space can maximize the occupant comfort. The WSHP Open
controller has its own hardware clock that is automatically set
when the heat pump software is downloaded to the board. Occupancy types are described in the scheduling section below.
The following sections describe the functionality of the WSHP
Open multi-protocol controller. All point objects referred to in
this sequence of operation will be referenced to the objects as
viewed in the BACview
SCHEDULING — Scheduling is used to start/stop the unit
based on a time period to control the space temperature to specified occupied heating and cooling set points. The controller is
defaulted to control by occupied set points all the time, until either a time schedule is configured with BACview
tant, i-Vu
able the BAS (Building Automation System) on/off point. The
local time and date must be set for these functions to operate
properly. The occupancy source can be changed to one of the
following:
Occupancy Schedules
until a time schedule has been configured using either Field
Assistant, i-Vu Open, BACview
to enable/disable the BAS on/off point. The BAS point can be
disabled by going to Config, then Unit, then Occupancy Schedules and changing the point from enable to disable then clicking OK.
NOTE: This point must be enabled in order for the i-Vu Open,
Field Assistant, or BACview
schedule to the controller.
Schedule_schedule
schedule configured and stored in the unit. The schedule is
accessible via the BACview
Field Assistant control system. The daily schedule consists of a
start/stop time (standard or 24-hour mode) and seven days of
the week, starting with Monday and ending on Sunday. To
enter a daily schedule, navigate to Config, then Sched, then
enter BACview
schedule_schedule. From here, enter either a Weekly or Exception schedule for the unit.
Occupancy Input Contact
the capability to use an external dry contact closure to determine the occupancy status of the unit. The Occupancy Schedules will need to be disabled in order to utilize the occupancy
contact input.
NOTE: Scheduling can only be controlled from one source.
BAS (Building Automation System) On/Off
system that supports network scheduling can control the unit
through a network communication and the BAS scheduling
function once the Occupancy Schedules have been disabled.
NOTE: Scheduling can either be controlled via the unit or the
BAS, but not both.
INDOOR FAN — The indoor fan will operate in any one of
three modes depending on the user configuration selected.
Fan mode can be selected as Auto, Continuous, or Always
On. In Auto mode, the fan is in intermittent operation during
IAQ (indoor air quality) sensor mounted in the
2
6
handheld user interface.
6
®
Open, or a third party control system to enable/dis-
, Field Assis-
— The controller will be occupied 24/7
6
or a third party control system
6
control system to assign a time
— The unit will operate according to the
6
Handheld tool, i-Vu Open, or
6
Admin Password (1111), then go to
— The WSHP Open controller has
— A BAS
both occupied and unoccupied periods. Continuous fan mode
is intermittent during unoccupied periods and continuous during occupied periods. Always On mode operates the fan continuously during both occupied and unoccupied periods. In the
default mode, Continuous, the fan will be turned on whenever
any one of the following is true:
• The unit is in occupied mode as determined by its occupancy status.
• There is a demand for cooling or heating in the unoccupied mode.
• There is a call for dehumidification (optional).
When power is reapplied after a power outage, there will be
a configured time delay of 5 to 600 seconds before starting the
fan. There are also configured fan delays for Fan On and Fan
Off. The Fan On delay defines the delay time (0 to 30 seconds;
default 10) before the fan begins to operate after heating or
cooling is started while the Fan Off delay defines the delay
time (0 to 180 seconds; default 45) the fan will continue to operate after heating or cooling is stopped. The fan will continue
to run as long as the compressors, heating stages, or the dehumidification relays are on. If the SPT failure alarm or condensate overflow alarm is active; the fan will be shut down immediately regardless of occupancy state or demand.
Fan Speed Control (During Heating)
— Whenever heat is required and active, the control continuously monitors the supply-air temperature to verify it does not rise above the configured maximum heating SAT limit (110 F default). As the SAT
approaches this value, the control will increase the fan speed as
required to ensure the SAT will remain within the limit. This
feature provides the most quiet and efficient operation by operating the fan at the lowest speed possible.
Fan Speed Control (During Cooling)
— Whenever mechanical cooling is required and active, the control continuously
monitors the supply-air temperature to verify it does not fall below the configured minimum cooling SAT limit (50 F default).
As the SAT approaches this value, the control will increase the
fan speed as required to ensure the SAT will remain within the
limit. The fan will operate at lowest speed to maximize latent
capacity during cooling.
COOLING — The WSHP Open controller will operate one or
two stages of compression to maintain the desired cooling set
point. The compressor outputs are controlled by the PI (proportional-integral) cooling loop and cooling stages capacity algorithm. They will be used to calculate the desired number of
stages needed to satisfy the space by comparing the space temperature (SPT) to the appropriate cooling set point. The water
side economizer, if applicable, will be used for first stage cooling in addition to the compressor(s). The following conditions
must be true in order for the cooling algorithm to run:
• Cooling is set to Enable.
• Heating mode is not active and the compressor time
guard has expired.
• Condensate overflow input is normal.
• If occupied, the SPT is greater than the occupied cooling
set point.
• Space temperature reading is valid.
• If unoccupied, the SPT is greater than the unoccupied
cooling set point.
• If economizer cooling is available and active and the
economizer alone is insufficient to provide enough cooling.
• OAT (if available) is greater than the cooling lockout
temperature.
If all the above conditions are met, the compressors will be
energized as required, otherwise they will be deenergized. If
cooling is active and should the SAT approach the minimum
SAT limit, the fan will be indexed to the next higher speed.
Should this be insufficient and if the SAT falls further (equal to
the minimum SAT limit), the fan will be indexed to the
41
Page 42
maximum speed. If the SAT continues to fall 5 F below the
°
°
minimum SAT limit, all cooling stages will be disabled.
During Cooling mode, the reversing valve output will be
held in the cooling position (either B or O type as configured)
even after the compressor is stopped. The valve will not switch
position until the Heating mode is required.
The configuration screens contain the minimum SAT
parameter as well as cooling lockout based on outdoor-air
temperature (OAT) Both can be adjusted to meet various
specifications.
There is a 5-minute off time for the compressor as well as a
5-minute time delay when staging up to allow the SAT to
achieve a stable temperature before energizing a second stage
of capacity. Likewise, a 45-second delay is used when staging
down.
After a compressor is staged off, it may be restarted again
after a normal time-guard period of 5 minutes and if the supply-air temperature has increased above the minimum supplyair temperature limit.
The WSHP Open controller provides a status input to monitor the compressor operation. The status is monitored to determine if the compressor status matches the commanded state.
This input is used to determine if a refrigerant safety switch or
other safety device has tripped and caused the compressor to
stop operating normally. If this should occur, an alarm will be
generated to indicate the faulted compressor condition.
HEATING — The WSHP Open controller will operate one or
two stages of compression to maintain the desired heating set
point. The compressor outputs are controlled by the heating PI
(proportional-integral) loop and heating stages capacity algorithm. They will be used to calculate the desired number of
stages needed to satisfy the space by comparing the space temperature (SPT) to the appropriate heating set point. The following conditions must be true in order for the heating algorithm to
run:
• Heating is set to Enable.
• Cooling mode is not active and the compressor time
guard has expired.
• Condensate overflow input is normal.
• If occupied, the SPT is less than the occupied heating set
point.
• Space temperature reading is valid.
• If unoccupied, the SPT is less than the unoccupied heat-
ing set point.
• OAT (if available) is less than the heating lockout
temperature.
If all the above conditions are met, the heating outputs will
be energized as required, otherwise they will be deenergized. If
the heating is active and should the SAT approach the maximum SAT limit, the fan will be indexed to the next higher
speed. Should this be insufficient, and the SAT rises further
reaching the maximum heating SAT limit, the fan will be
indexed to the maximum speed. If the SAT still continues to
rise 5 F above the maximum limit, all heating stages will be
disabled.
During Heating mode, the reversing valve output will be
held in the heating position (either B or O type as configured)
even after the compressor is stopped. The valve will not switch
position until the Cooling mode is required.
The configuration screens contain the maximum SAT
parameter as well as heating lockout based on outdoor-air
temperature (OAT); both can be adjusted to meet various
specifications.
There is a 5-minute off time for the compressor as well as a
5-minute time delay when staging up to allow the SAT to
achieve a stable temperature before energizing a second stage
of capacity. Likewise, a 45-second delay is used when staging
down.
After a compressor is staged off, it may be restarted again
after a normal time-guard period of 5 minutes and if the supply-air temperature has fallen below the maximum supply air
temperature limit.
The WSHP Open controller provides a status input to monitor the compressor operation. The status is monitored to determine if the compressor status matches the commanded state.
This input is used to determine if a refrigerant safety switch or
other safety device has tripped and caused the compressor to
stop operating normally. If this should occur, an alarm will be
generated to indicate the faulted compressor condition. Also, if
auxiliary heat is available (see below), the auxiliary heat will
operate to replace the reverse cycle heating and maintain the
space temperature as required.
AUXILIARY HEAT — The WSHP Open controller can control a two-position, modulating water, or steam valve connected to a coil on the discharge side of the unit and supplied by a
boiler or a single-stage ducted electric heater in order to maintain the desired heating set point. Should the compressor capacity be insufficient or a compressor failure occurs, the auxiliary
heat will be used. Unless the compressor fails, the auxiliary
heat will only operate to supplement the heat provided by the
compressor if the space temperature falls more than one degree
below the desired heating set point (the amount is configurable). The heat will be controlled so the SAT will not exceed
the maximum heating SAT limit.
Auxiliary Modulating Hot Water/Steam Heating Reheat
— The control can modulate a hot water or steam valve connected to a coil on the discharge side of the unit and supplied
by a boiler in order to maintain the desired heating set point
should the compressor capacity be insufficient or a compressor
failure occurs. Unless a compressor fault condition exists, the
valve will only operate to supplement the heat provided by the
compressor if the space temperature falls more than one degree
below the desired heating set point. The valve will be controlled so the SAT will not exceed the maximum heating SAT
limit.
Two-Position Hot Water/Steam Heating Reheat
trol can operate a two-position, NO or NC, hot water or steam
valve connected to a coil on the discharge side of the unit and
supplied by a boiler in order to maintain the desired heating set
point should the compressor capacity be insufficient or a compressor failure occurs. Unless a compressor fault condition exists, the valve will only open to supplement the heat provided
by the compressor if the space temperature falls more than one
degree below the desired heating set point. The valve will be
controlled so the SAT will not exceed the maximum heating
SAT limit. The heat stage will also be subject to a 2-minute
minimum OFF time to prevent excessive valve cycling.
Single Stage Electric Auxiliary Heat
erate a field-installed single stage of electric heat installed on
the discharge side of the unit in order to maintain the desired
heating set point should the compressor capacity be insufficient
or a compressor failure occurs. Unless a compressor fault condition exists, the heat stage will only operate to supplement the
heat provided by the compressor if the space temperature falls
more than one degree below the desired heating set point. The
heat stage will be controlled so the SAT will not exceed the
maximum heating SAT limit. The heat stage will also be subject to a 2-minute minimum OFF time to prevent excessive
cycling.
INDOOR AIR QUALITY (IAQ) AND DEMAND CONTROLLED VENTILATION (DCV) — If the optional indoor air quality sensor is installed, the WSHP Open controller
can maintain indoor air quality via a modulating OA damper
providing demand controlled ventilation. The control operates
the modulating OA damper during occupied periods. The control monitors the CO
set points, adjusting the ventilation rate as required. The control
provides proportional ventilation to meet the requirements of
level and compares it to the configured
2
— The control can op-
— The con-
42
Page 43
ASHRAE (American Society of Heating, Refrigerating and
°
°
°
°
Air Conditioning Engineers) specifications by providing a base
ventilation rate and then increasing the rate as the CO
creases. The control will begin to proportionally increase ventilation when the CO
point and will reach the full ventilation rate when the CO2 level
is at or above the maximum set point. A user-configurable minimum damper position ensures that proper base ventilation is
delivered when occupants are not present. The IAQ configurations can be accessed through the configuration screen. The
following conditions must be true in order for this algorithm to
run:
• Damper control is configured for DCV.
• The unit is in an occupied mode.
• The IAQ sensor reading is greater than the DCV start
control set point.
The control has four user adjustable set points: DCV start
control set point, DCV maximum control set point, minimum
damper position, and DCV maximum damper position.
Two-Position OA Damper
to operate a ventilation damper in a two-position ventilation
mode to provide the minimum ventilation requirements during
occupied periods.
WATERSIDE ECONOMIZER — The WSHP Open controller has the capability of providing modulating or two-position
water economizer operation (for a field-installed economizer
coil mounted to the entering air side of the unit and connected
to the condenser water loop) in order to provide free cooling
(or preheating) when water conditions are optimal. Water economizer settings can be accessed through the equipment status
screen. The following conditions must be true for economizer
operation:
• SAT reading is available.
• LWT reading is available.
• If occupied, the SPT is greater than the occupied cooling
set point or less than the occupied heating set point and
the condenser water is suitable.
• Space temperature reading is valid.
• If unoccupied, the SPT is greater than the unoccupied
cooling set point or less than the unoccupied heating set
point and the condenser water is suitable.
Modulating Water Economizer Control
the capability to modulate a water valve to control condenser
water flowing through a coil on the entering air side of the unit.
Cooling — The purpose is to provide an economizer cooling
function by using the water loop when the entering water loop
temperature is suitable (at least 5 F below space temperature).
If the water loop conditions are suitable, then the valve will
modulate open as required to maintain a supply-air temperature
that meets the load conditions. Should the economizer coil capacity alone be insufficient for a period greater than 5 minutes,
or should a high humidity condition occur, then the compressor
will also be started to satisfy the load. Should the SAT approach the minimum cooling SAT limit, the economizer valve
will modulate closed during compressor operation.
Heating — Additionally, the control will modulate the water
valve should the entering water loop temperature be suitable
for heating (at least 5 F above space temperature) and heat is
required. The valve will be controlled in a similar manner except to satisfy the heating requirement. Should the economizer
coil capacity alone be insufficient to satisfy the space load conditions for more than 5 minutes, then the compressor will be
started to satisfy the load. Should the SAT approach the maximum heating SAT limit, the economizer valve will modulate
closed during compressor operation.
Two-Position Water Economizer Control
the capability to control a NO or NC, two-position water valve
to control condenser water flow through a coil on the entering
air side of the unit.
level rises above the start ventilation set
2
— The control can be configured
— The control has
— The control has
level in-
2
Cooling — The purpose is to provide a cooling economizer
function directly from the condenser water loop when the entering water loop temperature is suitable (at least 5 F below
space temperature). If the optional coil is provided and the water loop conditions are suitable, then the valve will open to provide cooling to the space when required. Should the capacity
be insufficient for a period greater than 5 minutes, or should a
high humidity condition occur, then the compressor will be
started to satisfy the load. Should the SAT reach the minimum
cooling SAT limit, the economizer valve will close during
compressor operation.
Heating — Additionally, the economizer control will open the
water valve should the entering water loop temperature be suitable for heating (at least 5 F above space temperature) and
heat is required. The valve will be controlled in a similar manner except to satisfy the heating requirement. Should the coil
capacity be insufficient to satisfy the space load for more than
5 minutes, then the compressor will be started to satisfy the
load. Should the SAT reach the maximum heating SAT limit,
the economizer valve will close during compressor operation.
DEMAND LIMIT — The WSHP Open controller has the
ability to accept three levels of demand limit from the network.
In response to a demand limit, the unit will decrease its heating
set point and increase its cooling set point to widen the range in
order to immediately lower the electrical demand. The amount
of temperature adjustment in response is user adjustable for
both heating and cooling and for each demand level. The response to a particular demand level may also be set to zero.
CONDENSER WATER LINKAGE — The control provides optimized water loop operation using an universal controller (UC) open loop controller. Loop pump operation is automatically controlled by WSHP equipment occupancy schedules, unoccupied demand and tenant override conditions.
Positive pump status feedback prevents nuisance fault trips.
The condenser water linkage operates when a request for condenser water pump operation is sent from each WSHP to the
loop controller. This request is generated whenever any WSHP
is scheduled to be occupied, is starting during optimal start (for
warm-up or pull down prior to occupancy), there is an unoccupied heating or cooling demand, or a tenant pushbutton override. At each WSHP, the water loop temperature and the loop
pump status is given. The WSHP will NOT start a compressor
until the loop pumps are running or will shutdown the compressors should the pumps stop. This prevents the WSHP from
operating without water flow and thus tripping out on refrigerant pressure, causing a lockout condition. The WSHP Open
controller control will prevent this from occurring. Also, the
loop controller can be configured to start the pumps only after a
configurable number of WSHPs are requesting operation (from
1-"N"). This can be used to prevent starting the entire loop operation for only one WSHP. Meanwhile, the WSHPs will not
operate if the loop pump status is off and therefore the WSHP
compressor will not run.
COMPLETE C AND DELUXE D BOARD
SYSTEM TEST
System testing provides the ability to check the control
operation. The control enters a 20-minute Test mode by
momentarily shorting the test pins. All time delays are reduced
by a factor of 15.
Test Mode — To enter Test mode on Complete C or
Deluxe D controls, cycle the power 3 times within 60 seconds.
The LED (light-emitting diode) will flash a code representing
the last fault when entering the Test mode. The alarm relay will
also power on and off during Test mode. See Tables 15-17. To
exit Test mode, short the terminals for 3 seconds or cycle the
power 3 times within 60 seconds.
NOTE: The Deluxe D control has a flashing code and alarm
relay cycling code that will both have the same numerical
43
Page 44
label. For example, flashing code 1 will have an alarm relay
cycling code 1. Code 1 indicates the control has not faulted
since the last power-off to power-on sequence.
WSHP Open Test Mode — To enter WSHP Open test
mode, navigate from the BACview
6
home screen to the configuration screen. Choose the service screen and enable unit test.
The controller will then test the following:
FAN TEST — Tests all fan speeds, sequences fan from low to
high, and operates each speed for one minute. Resets to disable
on completion.
COMPRESSOR TEST — Tests compressor cooling and
heating operation. Sequences cooling stage 1 then cooling
stage 2 followed by heating stage 2 then reduces capacity to
heating stage 1. Operates for 1 minute per step.
DEHUMIDIFICATION TEST — Tests dehumidification
mode. Operates for 2 minutes.
AUXILIARY HEATING TEST — Tests auxiliary heat.
Sequences fan on and enables heating coil for 1 minute.
H
O ECONOMIZER TEST — Tests entering/returning
2
water loop economizer operation. Sequences fan and opens
economizer water valve for one minute.
OPEN VENT DAMPER 100% TEST — Tests outside air
(OA) damper operation.
PREPOSITION OA DAMPER — Prepositions OA damper
actuator to set proper preload.
NOTE: The auxiliary heating test, H
vent damper 100% test, and preposition OA damper features
will not be visible on the screen unless configured.
Once tests are complete, set unit test back to disable. Unit will
automatically reset to disable after 1 hour.
Retry Mode — In Retry mode, the status LED will start to
flash slowly to signal that the control is trying to recover from an
input fault. The control will stage off the outputs and try to again
satisfy the thermostat used to terminal Y. Once the thermostat input calls are satisfied, the control will continue normal operation.
NOTE: If 3 consecutive faults occur without satisfying the
thermostat input call to terminal Y, the control will go into
lockout mode. The last fault causing the lockout is stored in
memory and can be viewed by entering Test mode.
Aquazone™ Deluxe D Control LED Indicators —
STATUS LED — Status LED indicates the current status or
mode of the Deluxe D control. The Status LED light is green.
TEST LED — Test LED will be activated any time the Deluxe D control is in Test mode. The Test LED light is yellow.
FAULT LED — Fault LED light is red. The fault LED will
always flash a code representing the last fault in memory. If
there is no fault in memory, the fault LED will flash code 1 and
appear as 1 fast flash alternating with a 10-second pause. See
Table 17.
There are 3 LED indicators on the Deluxe D control:
Table 15 — Complete C Control Current LED Status and Alarm Relay Operations
LED STATUSDESCRIPTION OF OPERATIONALARM RELAY
On
OffComplete C Control is non-functionalOpen
Slow Flash
Fast FlashLockoutClosed
Flashing Code 1Test Mode — No fault in memoryCycling Code 1
Flashing Code 2Test Mode — HP Fault in memoryCycling Code 2
Flashing Code 3Test Mode — LP Fault in memoryCycling Code 3
Flashing Code 4Test Mode — FP1 Fault in memoryCycling Code 4
Flashing Code 5Test Mode — FP2 Fault in memoryCycling Code 5
Flashing Code 6Test Mode — CO Fault in memoryCycling Code 6
Flashing Code 7Test Mode — Over/Under shutdown in memoryCycling Code 7
Flashing Code 8Test Mode — PM in memoryCycling Code 8
Flashing Code 9Test Mode — FP1/FP2 swapped fault in memoryCycling Code 9
LEGENDNOTES:
CO — Condensate OverflowLED — Light-Emitting Diode
FP — Freeze ProtectionLP— Low Pressure
HP — High PressurePM — Performance Monitor
Normal ModeOpen
Normal Mode with PM WarningCycle (Closed 5 sec, Open 25 sec)
Fault RetryOpen
Over/Under Voltage ShutdownOpen (Closed after 15 minutes)
1. Slow flash is 1 flash every 2 seconds.
2. Fast flash is 2 flashes every 1 second.
3. EXAMPLE: “Flashing Code 2” is represented by 2 fast flashes followed
by a 10-second pause. This sequence will repeat continually until the
fault is cleared.
Table 16 — Complete C Control LED Code and Fault Descriptions
O economizer test, open
2
LED CODEFAULTDESCRIPTION
1No fault in memoryThere has been no fault since the last power-off to power-on sequence
2High-Pressure SwitchHP open instantly
3Low-Pressure SwitchLP open for 30 continuous seconds before or during a call (bypassed for first 60 seconds)
4Freeze Protection Coax — FP1FP1 below temp limit for 30 continuous seconds (bypassed for first 60 seconds of operation)
5Freeze Protection Air Coil — FP2FP2 below temp limit for 30 continuous seconds (bypassed for first 60 seconds of operation)
6Condensate overflowSensor overflow (grounded) for 30 continuous seconds
7 (Autoreset)Over/Under Voltage Shutdown"R" power supply is <19-vac or >30-vac
8PM WarningPerformance monitor Warning has occurred.
9FP1 and FP2 Thermistors are swappedFP1 temperature is higher than FP2 in heating/test mode, or FP2 temperature is higher than FP1 in
LEGEND
FP— Freeze ProtectionLP — Low Pressure
HP — High PressurePM — Performance Monitor
LED — Light-Emitting Diode
cooling/test mode.
44
Page 45
Table 17 — Aquazone™ Deluxe D Control Current LED Status and Alarm Relay Operations
DESCRIPTION
Normal ModeOnOffFlash Last Fault Code in MemoryOpen
Normal Mode with PMOnOffFlashing Code 8Cycle (closed 5 sec, open 25 sec, …)
D Control is non-functionalOffOffOffOpen
Test Mode—OnFlash Last Fault Code in MemoryCycling Appropriate Code
Night SetbackFlashing Code 2—Flash Last Fault Code in Memory—
ESDFlashing Code 3—Flash Last Fault Code in Memory—
Invalid T-stat InputsFlashing Code 4—Flash Last Fault Code in Memory—
No Fault in MemoryOnOffFlashing Code 1Open
HP FaultSlow FlashOffFlashing Code 2Open
LP FaultSlow FlashOffFlashing Code 3Open
FP1 FaultSlow FlashOffFlashing Code 4Open
FP2 FaultSlow FlashOffFlashing Code 5Open
CO FaultSlow FlashOffFlashing Code 6Open
Over/Under VoltageSlow FlashOffFlashing Code 7Open (closed after 15 minutes)
HP LockoutFast FlashOffFlashing Code 2Closed
LP LockoutFast FlashOffFlashing Code 3Closed
FP1 LockoutFast FlashOffFlashing Code 4Closed
FP2 LockoutFast FlashOffFlashing Code 5Closed
CO LockoutFast FlashOffFlashing Code 6Closed
1. If there is no fault in memory, the Fault LED will flash code 1.
2. Codes will be displayed with a 10-second Fault LED pause.
3. Slow flash is 1 flash every 2 seconds.
4. Fast flash is 2 flashes every 1 second.
5. EXAMPLE: “Flashing Code 2” is represented by 2 fast flashes followed
by a 10-second pause. This sequence will repeat continually until the
fault is cleared.
SERVICE
Perform the procedures outlined below periodically, as
indicated.
WARNING
To prevent injury or death due to electrical shock or contact
with moving parts, open unit disconnect switch before servicing unit.
IMPORTANT: When a compressor is removed from this
unit, system refrigerant circuit oil will remain in the compressor. To avoid leakage of compressor oil, the refrigerant
lines of the compressor must be sealed after it is removed.
IMPORTANT: All refrigerant discharged from this unit
must be recovered without exception. Technicians must follow industry accepted guidelines and all local, state and federal statutes for the recovery and disposal of refrigerants.
IMPORTANT: To avoid the release of refrigerant into the
atmosphere, the refrigerant circuit of this unit must only be
serviced by technicians who meet local, state and federal
proficiency requirements.
Unit Inspection — Visually inspect the unit at least once
a month. Pay special attention to hose assemblies. Repair any
leaks and replace deteriorated hoses immediately. Note any
signs of deterioration or cracking.
System Flushing — Properly clean and flush system
periodically. Refer to Pre-Start-Up, System Cleaning and
Flushing section.
Water Coil — Keep air out of the water coil. Check open
loop systems to be sure the well head is not allowing air to infiltrate the water line. Always keep lines airtight.
Inspect heat exchangers regularly and clean more frequently
if the unit is located in a “dirty” environment. The heat
exchanger should be kept full of water at all times. Open loop
systems should have an inverted P trap placed in the discharge
line to keep water in the heat exchanger during off cycles.
Closed loop systems must have a minimum of 15 psig during
the summer and 40 psig during the winter.
Check P trap frequently for proper operation.
FILTERS — Inspect filters. Establish a regular maintenance
schedule. Clean or replace filters frequently depending on
need.
To remove the filter from the 50PEC unit, slide the filter out
of its frame located in the return air opening at the bottom front
of the unit. When re-installing the filter, use the slide-in rails of
the filter frame to guide the filter into the proper position.
CAUTION
To avoid fouled machinery and extensive unit clean-up,
DO NOT operate units without filters in place. DO NOT
use equipment as a temporary heat source during
construction.
Refrigerant System — Verify air and water flow rates
are at proper levels before servicing. To maintain sealed circuitry integrity, do not install service gages unless unit operation
appears abnormal.
Condenser Cleaning — Water-cooled condensers may
require cleaning of scale (water deposits) due to improperly
maintained closed-loop water systems. Open water tower
systems may require removal of sludge build-up due to
induced contaminants.
Local water conditions may cause excessive fouling or
pitting of tubes. Therefore, condenser tubes should be cleaned
at least once a year, or more often if the water is contaminated.
Use standard coil cleaning procedures which are compatible
with both the heat exchanger material and copper water lines.
Generally, the more water flowing through the unit, the less
chance for scaling, however flow rates over 3 gpm per ton can
45
Page 46
produce water (or debris) velocities that can erode the heat exchanger wall and ultimately produce leaks.
Proper water treatment can minimize tube fouling and
pitting. If such conditions are anticipated, water treatment analysis is recommended. Refer to the Carrier System Design Manual, Part 5, for general water conditioning information.
CAUTION
Follow all safety codes. Wear safety glasses and rubber
gloves when using inhibited hydrochloric acid solution.
Observe and follow acid manufacturer’s instructions.
PUMP
SUCTION
PUMP
SUPPORT
TANK
PRIMING
CONN.
GAS VENT
GLOBE
VALV ES
SUPPLY
1” PIPE
CONDENSER
REMOVE WATER
REGULATING VALVE
Clean condensers with an inhibited hydrochloric acid solution. The acid can stain hands and clothing, damage concrete,
and, without inhibitor, damage steel. Cover surroundings to
guard against splashing. Vapors from vent pipe are not harmful,
but take care to prevent liquid from being carried over by the
gases.
Warm solution acts faster, but cold solution is just as effective if applied for a longer period.
GRAVITY FLOW METHOD — Do not add solution faster
than vent can exhaust the generated gases.
When condenser is full, allow solution to remain overnight,
then drain condenser and flush with clean water. Follow acid
manufacturer’s instructions. See Fig. 37.
FILL CONDENSER WITH
CLEANING SOLUTION. DO
NOT ADD SOLUTION
MORE RAPIDLY THAN
VENT CAN EXHAUST
GASES CAUSED BY
CHEMICAL ACTION.
VENT
PIPE
3’ TO 4’
PAIL
1”
PIPE
5’ APPROX
FUNNEL
PAIL
CONDENSER
Fig. 37 — Gravity Flow Method
FORCED CIRCULATION METHOD — Fully open vent
pipe when filling condenser. The vent may be closed when
condenser is full and pump is operating. See Fig. 38.
Regulate flow to condenser with a supply line valve. If
pump is a nonoverloading type, the valve may be fully closed
while pump is running.
For average scale deposit, allow solution to remain in condenser overnight. For heavy scale deposit, allow 24 hours.
Drain condenser and flush with clean water. Follow acid manufacturer’s instructions.
FINE MESH
SCREEN
RETURN
Fig. 38 — Forced Circulation Method
Condensate Pans — Check condensate drain pans for
algae growth every three months. If algae growth is apparent,
consult a water treatment specialist for proper chemical treatment. The application of an algaecide every three months will
typically eliminate algae problems in most locations. Check
condensate hose for leaks and blockage and correct any
problems.
Blower Motors — All units have lubricated fan motors.
BLOWER MOTORS SHOULD NEVER BE LUBRICATED
UNLESS OBVIOUS, DRY OPERATION IS SUSPECTED.
Periodic maintenance oiling is not recommended because it
will result in dirt accumulating on excess oil and cause eventual motor failure. Conduct annual dry operation check and amperage check to ensure amp draw is no more than 10% greater
than that indicated by serial plate data.
Compressor — Conduct an amperage check annually on
the compressor and fan motor. Amperage draw should not
exceed normal full load amps. Maintain a log of amperage to
detect deterioration prior to component failure.
Safety Control Reset — The 50PEC heat pumps are
furnished with high-pressure, low-pressure and lowtemperature cutouts to prevent the machine from operating at
abnormal conditions of temperature or water flow.
The contacts of the high-pressure control used on 50PEC
units are designed to open at 376 psig and automatically
re-close at 304 psig. The Complete C or Deluxe D control
monitors this and other functions such as refrigerant temperatures and pressures and condensate overflow and will interrupt
unit heating or cooling operation.
The machine must be reset manually. Reset is accomplished
by pressing the STOP button and then pushing either HI HEAT,
LOW HEAT, HI COOL or LO COOL to restart the unit in the
desired mode of operation. (The 50PEC unit can also be reset
by opening and closing the supply power disconnect switch.)
IMPORTANT: If the unit must be reset more than twice,
check the unit for a dirty filter, abnormal entering water
temperature, inadequate or excessive water flow, and internal malfunctions. If the unit continues to cut out, contact a
trained service technician.
WARNING
When replacing the compressor contactor or lockout relay
in a unit with electromechanical controls, use only Carrier
factory authorized parts. Substitution of other components
may result in an inoperative safety circuit and may cause a
hazardous condition.
46
Page 47
Checking System Charge — Units are shipped with
full operating charge. If recharging is necessary:
1. Insert thermometer bulb in insulating rubber sleeve on
liquid line near filter drier. Use a digital thermometer for
all temperature measurements. DO NOT use a mercury
or dial-type thermometer.
2. Connect pressure gage to discharge line near compressor.
3. After unit conditions have stabilized, read head pressure
on discharge line gage.
NOTE: Operate unit a minimum of 15 minutes before
checking charge. From standard field-supplied PressureTemperature chart for R-410A, find equivalent saturated
condensing temperature.
4. Read liquid line temperature on thermometer, then
subtract from bubble point temperature. The difference
equals subcooling temperature.
Refrigerant Charging
WARNING
To prevent personal injury, wear safety glasses and gloves
when handling refrigerant. Do not overcharge system —
this can cause compressor flooding.
NOTE: Do not vent or depressurize unit refrigerant to atmosphere. Remove and recover refrigerant following accepted
practices.
Air Coil Fan Motor Removal
CAUTION
Before attempting to remove fan motors or motor mounts,
place a piece of plywood over evaporator coils to prevent
coil damage.
Motor power wires need to be disconnected from motor
terminals before motor is removed from unit.
1. Shut off unit main power supply.
2. Loosen bolts on mounting bracket so that fan belt can be
removed.
3. Loosen and remove the 2 motor mounting bracket bolts
on left side of bracket.
4. Slide motor/bracket assembly to extreme right and lift out
through space between fan scroll and side frame. Rest
motor on a high platform such as a step ladder. Do not
allow motor to hang by its power wires.
Replacing the WSHP Open Controller’s Battery —
CR2032 battery provides a minimum of 10,000 hours of data
retention during power outages.
NOTE: Power must be ON to the WSHP Open controller
when replacing the battery, or the date, time and trend data will
be lost.
1. Remove the battery from the controller, making note of
2. Insert the new battery, matching the battery's polarity
The WSHP Open controller’s 10-year lithium
the battery's polarity.
with the polarity indicated on the WSHP Open controller.
TROUBLESHOOTING
When troubleshooting problems with a WSHP, consider the
following and refer to Table 18.
Thermistor — A thermistor may be required for single-
phase units where starting the unit is a problem due to low
voltage.
WSHP Open Controller — With the WSHP Open con-
troller option, the 100 most recent alarms can be viewed using
the BACview
To view the alarms:
1. Navigate to the Alarm Status screen from the Home
2. From the Alarm Status screen, press the Alarm softkey to
3. To view alarms which have been corrected, scroll down
6
alarm status and alarm history.
screen using the arrow softkeys. The screen will display
the current alarm status, either normal or Alarm, and allow for scrolling through the unit’s alarm status.
view the 100 most recent alarms which are labeled with
date and time for easy reference.
NOTE: Active faults can be viewed by scrolling down,
these faults indicate a possible bad sensor or some condition which may not merit an alarm.
through the Alarm screen to Return Top Normal screen.
NOTE: Alarms are automatically reset once alarm con-
dition has been corrected.
See Table 18 for possible alarm cause and solution.
47
Page 48
Table 18 — Troubleshooting
FAULTHEATING COOLINGPOSSIBLE CAUSESOLUTION
Main Power ProblemsXXGreen Status LED OffCheck line voltage circuit breaker and disconnect.
Check for line voltage between L1 and L2 on the contactor.
Check for 24-vac between R and C on controller.
Check primary/secondary voltage on transformer.
HP Fault — Code 2
High Pressure
XReduced or no airflow in
XAir temperature out of range
XXOvercharged with refrigerant Check superheat/subcooling vs. typical operating condition.
XXBad HP switchCheck switch continuity and operation. Replace.
LP Fault — Code 3
Low Pressure/Loss of
Charge
FP1 Fault — Code 4
Water Freeze Protection
FP2 Fault — Code 5
Air Coil Freeze
Protection
Condensate Fault —
Code 6
Over/Under Voltage —
Code 7
(Auto Resetting)
Performance Monitor —
Code 8
No Fault Code ShownXXCompressor overloadCheck and replace if necessary.
Unit Short CyclesXXDirty air filterCheck and clean air filter.
Only Fan RunsXXThermostat positionEnsure thermostat set for heating or cooling operation.
LEGEND
FP— Freeze Protection
HP — High Pressure
LED — Light-Emitting Diode
LP— Low Pressure
RV— Reversing Valve
XXInsufficient chargeCheck for refrigerant leaks.
XCompressor pump down at
XReduced or no water flow in
XInadequate antifreeze level Check antifreeze density with hydrometer.
XImproper freeze protect set-
XWater temperature out of
XXBad thermistorCheck temperature and impedance correlation.
XXBad thermistorCheck temperature and impedance correlation.
XXBlocked drainCheck for blockage and clean drain.
XXImproper trapCheck trap dimensions and location ahead of vent.
XXUnder voltageCheck power supply and 24-vac voltage before and during operation.
XXOver voltageCheck power supply voltage and 24 vac before and during operation.
XHeating mode FP2>125 FCheck for poor airflow or overcharged unit.
XXControl boardReset power and check operation.
XXUnit in Test modeReset power or wait 20 minutes for auto exit.
XXUnit selectionUnit may be oversized for space. Check sizing for actual load of space.
XXCompressor overloadCheck and replace if necessary.
XXUnit locked outCheck for lockout codes. Reset power.
XXCompressor overloadCheck compressor overload. Replace if necessary.
XXThermostat wiringCheck Y and W wiring at heat pump. Jumper Y and R for compressor
XReduced or no water flow in
cooling
XWater temperature out of
range in cooling
heating
in heating
start-up
heating
ting (10 F vs. 30 F)
range
XReduced or no airflow in
cooling
XAir temperature out of range Too much cold vent air. Bring entering-air temperature within design
XImproper freeze protect set-
ting (10 F vs. 30 F)
XPoor drainageCheck for piping slope away from unit.
XMoisture on sensorCheck for moisture shorting to air coil.
XCooling mode FP1>125 F
OR FP2< 40 F
Check pump operation or valve operation/setting.
Check water flow adjust to proper flow rate.
Bring water temperature within design parameters.
Check for dirty air filter and clean or replace.
Check fan motor operation and airflow restrictions.
Dirty air coil — construction dust, etc. Perform preventative mainte-
nance; Clean air coil.
High external static. Check duct design and downstream interference.
Bring return-air temperature within design parameters.
Check charge and start-up water flow.
Check pump operation or water valve operation/setting.
Plugged strainer or filter. Clean or replace.
Check water flow adjust to proper flow rate.
Clip JW3 jumper for antifreeze (10 F) use.
Bring water temperature within design parameters.
Check for dirty air filter and clean or replace.
Check fan motor operation and airflow restrictions.
High external static. Check duct design and downstream interference.
parameters.
Normal airside applications will require 30 F only.
Check slope of unit toward outlet.
Poor venting. Check vent location.
Check power supply wire size.
Check compressor starting.
Check 24-vac and unit transformer tap for correct power supply voltage.
Check 24-vac and unit transformer tap for correct power supply voltage.
Check for poor water flow or airflow.
operation in Test mode.
48
Page 49
Table 18 — Troubleshooting (cont)
FAULTHEATING COOLINGPOSSIBLE CAUSESOLUTION
Only Compressor RunsXXThermostat wiringCheck G wiring at heat pump. Jumper G and R for fan operation.
Check Y and W wiring at heat pump. Jumper Y and R for compressor
XXFan motor relayJumper G and R for fan operation. Check for line voltage across BR
Unit Does Not Operate in
Cooling
Insufficient Capacity/
Not Cooling or Heating
Properly
High Head PressureXReduced or no airflow in
Low Suction PressureXReduced water flow in
Low Discharge Air
Temperature in Heating
High HumidityXToo high airflowCheck blower.
LEGEND
FP— Freeze Protection
HP — High Pressure
LED — Light-Emitting Diode
LP— Low Pressure
RV— Reversing Valve
XXFan motorCheck for line voltage at motor. Check capacitor.
XXDirty filterReplace or clean.
XReduced or no airflow in
XXLeaky ductworkCheck supply and return-air temperatures at the unit and at distant
XXLow refrigerant chargeCheck superheat and subcooling.
XXRestricted metering device Check superheat and subcooling. Replace.
XXThermostat improperly
XXUnit undersizedRecheck loads and sizing check sensible cooling load and heat pump
XXScaling in water heat
XXInlet water too hot or coldCheck load, loop sizing, loop backfill, ground moisture.
XAir temperature out of range
XXUnit overchargedCheck superheat and subcooling. Reweigh in charge.
XXNon-condensables in
XXRestricted metering device Check superheat and subcooling. Replace.
XWater temperature out of
XXInsufficient chargeCheck for refrigerant leaks.
XToo high airflowCheck blower.
XPoor performanceSee ‘Insufficient Capacity’ above.
XReversing valveSet for cooling demand and check 24-vac on RV coil and at control.
XThermostat setupCheck for ‘O’ RV setup not ‘B’.
XThermostat wiringCheck O wiring at heat pump. Jumper O and R for RV coil.
heating
XReduced or no airflow in
cooling
XDefective reversing valvePerform RV touch test.
located
exchanger
heating
XReduced or no water flow in
cooling
XInlet water too hotCheck load, loop sizing, loop backfill, ground moisture.
in heating
XScaling in water heat
exchanger
system
heating
range
XReduced airflow in coolingCheck for dirty air filter and clean or replace.
XAir temperature out of range Too much cold vent air. Bring entering air temperature within design
XUnit oversizedRecheck loads and sizing check sensible cooling load and heat pump
operation in Test mode.
contacts.
Check fan power enable relay operation (if present).
If RV is stuck, run high pressure up by reducing water flow and while
operating engage and disengage RV coil voltage to push valve.
Check for dirty air filter and clean or replace.
Check fan motor operation and airflow restrictions.
High external static. Check duct design and downstream interference.
Check for dirty air filter and clean or replace.
Check fan motor operation and airflow restrictions.
High external static. Check duct design and downstream interference.
duct registers if significantly different, duct leaks are present.
Check location and for air drafts behind thermostat.
capacity.
Perform scaling check and clean if necessary.
Check for dirty air filter and clean or replace.
Check fan motor operation and airflow restrictions.
High external static. Check duct design and downstream interference.
Check pump operation or valve operation/setting.
Check water flow adjust to proper flow rate.
Bring return-air temperature within design parameters.
Perform scaling check and clean if necessary.
Vacuum system and reweigh in charge.
Check pump operation or water valve operation/setting.
Plugged strainer or filter. Clean or replace.
Check water flow adjust to proper flow rate.
Bring water temperature within design parameters.
Check fan motor operation and airflow restrictions.
High external static. Check duct design and downstream interference.
parameters.
capacity.
49
Page 50
APPENDIX A — WSHP OPEN SCREEN CONFIGURATION
SCREEN NAMEPOINT NAME
Operating Mode
SPT FDisplays SPT
SAT FDisplays SAT
Condenser Leaving
Temperature
Condenser Entering
Temperature
Fan
Equipment
Status
Alarm Status
Sensor
Calibration
BAS — Building Automation System
DCV — Demand Controlled Ventilation
IAQ — Indoor Air Quality
OAT — Outdoor Air Temperature
RH— Relative Humidity
SAT — Supply Air Temperature
SPT — Space Temperature
TPI— Third Party Integration
Rnet OffsetX-9.9 - 10.0 F0 FUsed to correct sensor reading
RH%Displays Space RH value
RH Sensor OffsetX-15% - 15%0 %Used to correct sensor reading
LEGEND
PASSWO RD
LEVEL
No Password
Required
No Password
Required
Admin Password
level access only
EDITABLERANGEDEFAULTNOTES
Off, Fan Only, Economize,
Cooling, Heating, Cont Fan,
Test, Start Delay, Dehumidify
°
°
°
F
°
F
Off/Low Speed/
Medium Speed
High Speed/On
0 - 9999 ppmDisplays the space CO2 level
Normal/Alarm
°
°
Normal/Alarm
Normal/AlarmCurrent compressor condition
Normal/Alarm
Normal/Alarm
Normal/AlarmCurrent linkage status if enabled
°
FDisplay SAT
°°
°
F
°°
°
FDisplays SPT
°°
Displays unit operating mode
Displays leaving condenser
water temperature
Displays entering condenser
water temperature (Value
will not update when compressor
Displays current damper position
(Viewable only if Ventilation DMP
reheat valve (Viewable only if Leaving
Air Auxiliary Heat Type = 2 position,
Displays space RH% (Viewable only if
Displays if dehumidification is active
Dehumidification Reheat = Installed)
exceeded the alarm limit (when SPT
Displays the SPT alarm limit that was
exceeded; causing the alarm condition
(when SPT alarm above is in Alarm)
SPT sensor - ALARM is displayed
should the sensor fail to communicate
Current status of the condensate
is operating)
Displays fan speed status
Type = 2 position or DCV)
Displays position of auxiliary
1 stage Elect or Modulating)
Humidity Sensor = Installed)
(Viewable only if Factory
Displays current space
temperature condition
Displays the SPT that
alarm above is in Alarm)
Displays the status of the Rnet
with the control module
drain (overflow switch)
Current status of the
condenser water
Current status of the OAT
broadcast function
Displays Leaving Condenser
Water Temperature
50
Page 51
APPENDIX A — WSHP OPEN SCREEN CONFIGURATION (cont)
SCREEN NAMEPOINT NAME
Operating Mode
Fan Operating ModeAuto/Continuous/Always On
Occupancy StatusUnoccupied/OccupiedDisplays the current occupancy status
Occupancy Control
Outside Air
Temperature
SPT FDisplays SPT
SPT Status
SPT Sensor StatusInactive/Connected
Condensate OverflowNormal/Alarm
Cooling Set Point F
Unit
Maintenance
System Settings
Occupancy
Maintenance
Schedule
Configuration
BAS — Building Automation System
DCV — Demand Controlled Ventilation
IAQ — Indoor Air Quality
OAT — Outdoor Air Temperature
RH— Relative Humidity
SAT — Supply Air Temperature
SPT — Space Temperature
TPI— Third Party Integration
Heating Set Point F
Set Point Adjustment F
Auxiliary Heat Control
Set Point
O Economizer
H
2
Control Set Point
Calculated IAQ/
Ventilation Damper
position
Active Compressor
Stages
SAT FDisplays SAT
Reset Filter AlarmXNo/Yes
Overflow ContactClosed/Open
Occupancy ContactClosed/Open
BAS/Keypad OverrideX
OAT InputN/A / Network
BACnetXSee TPI
Keypad ConfigurationXMapping
PasswordXChanges password
NetworkXSee TPI
BACnet Time MasterXSee TPI
Clock SetXChanges clock/time setting
Override Schedules
Pushbutton OverrideInactive/Active Occupied
Keypad Override
SchedulesInactive/Active Occupied
Occupancy ContactInactive/Active Occupied
BAS on/offInactive/Active Occupied
Local Occupancy
Schedules
Local Holiday
Schedules
Local Override
Schedules
BACnet Occupancy
Schedules
LEGEND
PASSWORD
LEVEL
No Password
required
No Password
required
User/Admin
Password level
access
EDITABLERANGEDEFAULTNOTES
Off, Fan Only,Economize,
Cooling, Heating, Cont Fan, Test,
Start Delay, Dehumidify
Always Occupied/Local Schedule/
BACnet Schedule/BAS Keypad/
Occupied Contact/Holiday Schedule/
Override Schedule/Pushbutton
Override/Unoccupied None
°
F
°
Normal/Above Limit/Below
Limit/Sensor Failure
°
°
°
°
F
°
F
%
0/1/2
°
Inactive/Occupied/
Unoccupied
Inactive/Active Occupied
Inactive/Active Occupied/Active
Unoccupied
XDisable/EnableEnable
XDisable/EnableDisable
XDisable/EnableDisable
XDisable/EnableDisable
Inactive
Displays unit operating mode
Displays how the fan is configured
Displays OAT (Viewable only if OAT
Displays the connection status
Displays the offset values from the Rnet
user set point adjustment that is being
applied to the configured set points
Displays the calculated set point being
used for auxiliary heating control
Displays the calculated set point being
Displays the ventilation damper
position calculated by the DCV control
Used to reset the filter alarm timer after
the filter has been cleaned or replaced
Displays the state of the condensate
Displays the state of the external/
remote occupancy input switch contact
Provides capability to force the
occupied or unoccupied mode
Displays if an OAT value is being
Used to display the active and
inactive occupancy control inputs
Used to define which occupancy inputs
to operate
Displays the origin of the
occupancy control
is a network broadcast)
Displays the SPT status
of the Rnet sensor
Displays the status of the
condensate overflow
Displays the actual set point
being used for cooling control
Displays the actual set point
being used for heating control
used for economizer control
Displays the actual number of
compressor stages operating
overflow switch contact
equipment to operate in an
received from the Network
are used to determine
occupancy mode.
51
Page 52
APPENDIX A — WSHP OPEN SCREEN CONFIGURATION (cont)
→
→→→
→
SCREEN NAMEPOINT NAME
Occupied Heating
Occupied CoolingX55 - 99 F76 F
Unoccupied HeatingX40 - 90 F55 F
Unoccupied CoolingX55 - 99 F90 F
Effective Heating
Set Point
Effective Cooling
Set Point
Optimal Start
Configuration
Occupied RH
Set Points
Configuration
Schedule
Weekly Schedule
Configuration
Schedule
Exception
Schedules 1 - 12
LEGEND
BAS — Building Automation System
DCV — Demand Controlled Ventilation
IAQ — Indoor Air Quality
OAT — Outdoor Air Temperature
RH— Relative Humidity
SAT — Supply Air Temperature
SPT — Space Temperature
TPI— Third Party Integration
Set Point
Unoccupied RH
Set Point
DCV CTRL Start
Set Point
DCV Max CTRL
Set Point
Start Time
End TimeX00:00 - 24:0018:00
MonXNo/YesYes
Tu eXN o /Ye sYes
WedXNo/YesYes
ThurXNo/YesYes
FriXNo/YesYe s
SatXNo/YesNo
SunXNo/YesNo
Start Month
Start Day X0 - 310
Start TimeX00:00 - 23:590:00
End MonthX0 - 120
End DayX0 - 310
End Time X00:00 - 24:000:00
PASSWORD
LEVEL
User/Admin
Password level
access
User/Admin
Password level
access
User/Admin
Password level
access
EDITABLERANGEDEFAULTNOTES
X40 - 90 F72 F
X0 - 10 F
X0 - 10 F
X0 - 100%65%
X0 - 100%90%
X0 - 9999 ppm500 ppm
X0 - 9999 ppm1050 ppm
X00:00 - 23:5906:00
X0 - 120
°°
°°
°°
°°
°
°
Defines the Occupied
Heating Set Point
Defines the Occupied
Cooling Set Point
Defines the Unoccupied
Heating Set Point
Defines the Unoccupied
Cooling Set Point
Takes into effect bias (maximum
allowable set point deviation)
Takes into effect bias (maximum
allowable set point deviation)
Uses historical data to calculate
ramp up time so as to be at set point
at occupied/unoccupied time
Defines the control set point used
during occupied periods (Viewable
only if Humidity Sensor = Installed/
Determines when to start
Dehumidification when occupied)
Defines the control set point used
during unoccupied periods
(Viewable only if Humidity Sensor =
Installed/Determines when to start
Dehumidification when unoccupied)
Defines the control set point used to
start increasing ventilation during
occupied periods (Viewable only if
Ventilation DMP Type = DCV)
Defines the control set point
used to define where the ventilation
will reach its maximum limit during
occupied periods (Viewable only if
Ventilation DMP Type = DCV/Used
to determine DCV ending control
Defines the start time for an
Defines the ending time of an
Determines if this day is included
Determines if this day is included
Determines if this day is included
Determines if this day is included
Determines if this day is included
Determines if this day is included
Determines if this day is included
Defines the start month of this
Defines the start day of this holiday
Determines the start time for this
Defines the month to end this
Defines the day to end this holiday
Determines the time to end this
point)
occupied period
occupied period
in this schedule
in this schedule
in this schedule
in this schedule
in this schedule
in this schedule
in this schedule
hoilday schedule
schedule
schedule
hoilday schedule
schedule
schedule
52
Page 53
APPENDIX A — WSHP SCREEN OPEN CONFIGURATION (cont)
→
→
→
SCREEN NAMEPOINT NAME
Fan Mode
Fan On DelayX0 - 30 sec10 sec
Fan Off DelayX0 - 180 sec45 sec
Heating EnableXDisable/EnableEnable
Cooling EnableXDisable/EnableEnable
Minimum SAT in
Configuration
Unit
Configuration
Configuration
Service
Test
LEGEND
BAS — Building Automation System
DCV — Demand Controlled Ventilation
IAQ — Indoor Air Quality
OAT — Outdoor Air Temperature
RH— Relative Humidity
SAT — Supply Air Temperature
SPT — Space Temperature
TPI— Third Party Integration
Cooling
Maximum SAT in
Heating
Damper Ventilation
Position
DCV Maximum Vent
Position
Filter Alarm TimerX0 - 9999 hrs0 hrsDisables Filter Alarm if set to 0
Pushbutton OverrideXDisable/EnableEnableEnables Override Feature on Rnet sensor
SPT Sensor Set Point
Adjustment
Lockout Cooling if
OAT <
Lockout Heating if
OAT >
Power Fail Restart
Delay
Occupancy SchedulesXDisable/EnableEnableEnables unit occupied
Set Point SeparationX2 - 9 F4 F
Test Mode
Fan TestXDisable/EnableDisable
Fan Speed
Compressor TestXDisable/EnableDisable
Dehumidification TestXDisable/EnableDisable
Testing Compressor
Aux Heating TestXDisable/EnableDisable
O Economizer TestXDisable/EnableDisable
H
2
Preposition OA
Damper
Open Vent
Damper 100%
SAT FDisplays SAT
LCWT F
PASSWORD
LEVEL
Admin Password
level access only
Admin Password
level access only
EDITABLERANGEDEFAULTNOTES
Auto= Intermittant operation during both
occupied and unoccupied periods/
X
X40 - 60 F50 F
X80 - 140 F110 F
X0 - 100%100%
X0 - 100%100%
XDisable/EnableEnable
X-65 - 80 F-65 F
X35 - 150 F150 F
X0 - 600 sec60 secDelay before equipment starts
XDisable/EnableDisable
XDisable/EnableDisable
XDisable/EnableDisableUsed to test OA damper operation
Auto/Continuous/
Always On
°°
°°
°°
°°
°°
Off/Low Speed/Medium
Speed/High Speed/On
Inactive/Heating/Cooling/
Dehumidify/TimeGard
Wait
°
°
Continuous
Continuous = Intermittant during unoccupied
periods and continuous during occupied
periods/Always on = fan operates
continuously during both occupied and
unoccupied periods
Defines the delay time before the fan begins
to operate after heating or cooling is started
Defines the amount of time the fan will
continue to operate after heating or
cooling is stopped
Provides capability to manually
disable heating operation
Provides capability to manually
disable cooling operation
Defines the minimum acceptable operating
temperature for the Supply Air
Defines the maximum acceptable operating
temperature for the Supply Air
Normally set to 100% if 2 position damper
type or set to minimum ventilation position if
Usually set at 100% - Used to limit maximum
Enables Set Point adjustment capability
Cooling is locked out when OAT is less than
configured value and OAT is actively being
Heating is locked out when OAT is greater
than configured value and OAT is actively
Used to enable test mode. Will automatically
Used to test all fan speeds. Sequences fan
from low to high and operates each speed for
1 minute. Resets to disable on completion
Used to test compressor cooling and heating
operation. Sequences cooling stage 1, then
stage 2, then heating stage 2 and reduces
capacity to stage 1. Operates for 1 minute per
Used to test entering/return air water loop
economizer coil operation. Sequences fan on
and opens economizer coil water valve for 1
minute. Resets to disable on completion
damper type = DCV
damper opening in DCV mode
on Rnet Sensor
broadcast
being broadcast
Used to enforce minimum
set point separation
reset to disable after 1 hour
Displays current fan operation
step. Resets to disable on completion.
Used to test dehumification mode -
Operates for 2 minutes. Resets to
disable on completion.
Displays compressor test mode
Used to test auxiliary heat.
Sequences fan on and enables
heating coil for 1 minute. Resets to
disable on completion
Used to preposition OA damper
actuator to set proper preload
Displays Leaving Condenser
Water Temperature
53
Page 54
APPENDIX A — WSHP SCREEN OPEN CONFIGURATION (cont)
→
SCREEN NAMEPOINT NAME
# of Fan Speeds
G Output TypeXFan On/Fan LowFan On
Compressor StagesXOne Stage/Two StagesOne Stage
Reversing Valve TypeXO type output/B type outputO type
Leaving Air Auxiliary
Heat Type
Entering Air Water
Economizer Type
2-Position Water
Val ve Type
Modulating Water
Val ve Type
Ventilation Damper
Ty pe
Damper Actuator TypeX(0-10 volt)/(2-10 volt)0-10 volt
Configuration
Service
Configuration
LEGEND
BAS — Building Automation System
DCV — Demand Controlled Ventilation
IAQ — Indoor Air Quality
OAT — Outdoor Air Temperature
RH— Relative Humidity
SAT — Supply Air Temperature
SPT — Space Temperature
TPI— Third Party Integration
Humidity SensorXNone/InstalledNone
Factory Dehumidifica-
tion Reheat Coil
Occupancy
Input Logic
Condensate Switch
Alarm Delay
Condensate Switch
Alarm State
Minimum Condenser
Water Temperature in
Heating
Maximum Condenser
Water Temperature in
Heating
Minimum Condenser
Water Temperature in
Cooling
Maximum Condenser
Water Temperature in
Cooling
IAQ sensor
minimum input
IAQ sensor
maximum input
IAQ sensor
minimum output
IAQ sensor
maximum output
PASSWORD
LEVEL
Admin Password
level access only
EDITABLERANGEDEFAULTNOTES
X1,2,33
X
XNone/2-Position/ModulatingNone
XNormally Closed/Normally Open
XNormally Closed/Normally Open
XNone/2-Position/DCVNone
XNone/InstalledNone
XOccupied Open/Occupied Closed
X5 - 600 seconds10 sec
XAlarm OPEN/Alarm CLOSED
X25 - 60 F60 F
X65 - 100 F90 F
X30 - 60 F60 F
X85 - 120 F95 F
X0 - 5 ma4 ma
X5 - 20 ma20 ma
X0 - 9999 ppm0 ppm
X0 - 9999 ppm2000 ppm
None/2-Position HW/1 Stage
Electric/Modulating HW
°°
°°
°°
°°
None
Normally
Closed
Normally
Closed
Occupied
CLOSED
Alarm
CLOSED
Used to set number of
fan motor speeds
When set to Fan On, G output is
energized when ever any fan speed
is active (required for ECM and Fan
control board). When set to Fan
Low, output is only energized for
Determines type of modulating
Set to Installed if factory-installed
Used to determine external occu-
pancy switch contact occupied state
Delay before equipment alarms on
acceptable water loop temperature
acceptable water loop temperature
acceptable water loop temperature
acceptable water loop temperature
Maximum output current (mA) for
Corresponding value in ppm for
Corresponding value in ppm for
Low Speed
Defines the number of
stages of compression
Determines reversing valve
signal output type
Determines Auxiliary
Reheat Coil Type
Determines Entering Air
Economizer Coil Type
Determines type of 2-position
water valve used
water valve used
Determines Type of ventilation
damper control to be used
Used to determine ventilation
damper output signal range
(closed - open)
Set to Installed if Humidity
sensor is present
dehumidification reheat coil
is present
high condensate level
Determine Alarm state of
condensate switch input
Determines the minimum
to start heating
Determines the maximum
to start heating
Determines the minimum
to start cooling
Determines the maximum
to start cooling
Minimum output current (mA)
for IAQ sensor
IAQ sensor
minimum output current
maximum output current
54
Page 55
APPENDIX A — WSHP SCREEN OPEN CONFIGURATION (cont)
→
→
SCREEN NAMEPOINT NAME
SPT Occupied Alarm
Hysteresis
SPT Alarm DelayX0 - 30 min per degree10 min
SPT Unoccupied Low
Alarm Temperature
SPT Unoccupied High
Alarm Temperature
SAT Low SAT
Alarm Limit
SAT High SAT
Alarm Limit
Condensate Overflow
Alarm Delay
Space Humidity Occupied
High Alarm Limit
Configuration
Alarm
Configuration
Configuration
Linkage
BAS — Building Automation System
DCV — Demand Controlled Ventilation
IAQ — Indoor Air Quality
OAT — Outdoor Air Temperature
RH— Relative Humidity
SAT — Supply Air Temperature
SPT — Space Temperature
TPI— Third Party Integration
Space Humidity Alarm
Delay
Space Humidity Unoccu-
pied High Alarm Limit
IAQ/Ventilation Occupied
High Alarm Limit
IAQ/Ventilation
Alarm Delay
Rnet Sensor SPT AlarmXIgnore/DisplayIgnore
Rnet Sensor SAT AlarmXIgnore/DisplayIgnore
Rnet Sensor Compressor
Lockout Alarm
Rnet Sensor Condenser
Water Temperature Alarm
Rnet Sensor Condensate
Overflow Alarm
Rnet Sensor Dirty
Filter Alarm
Rnet Sensor Space
High Humidity Alarm
Loop Control Network
Number
Loop Control Network
Address
Number of Linked Heat
Pumps
LEGEND
PASSWO RD
LEVEL
Admin Password
level access only
EDITABLERANGEDEFAULTNOTES
Defines the hysteresis applied above
X2 - 20 F5 F
X35 - 90 F45 F
X45 - 100 F95 F
X15 - 90 F45 F
X90 - 175 F120 F
X5 - 600 sec10 sec
X45% - 100%100%
X0 - 30 min per % RH5 min
X45% - 100%100%
X0 - 9999 ppm1100 ppm
X0.1 - 1.0 min per ppm0.25 min
XIgnore/DisplayDisplay
XIgnore/DisplayDisplay
XIgnore/DisplayDisplay
XIgnore/DisplayDisplay
XIgnore/DisplayIgnore
°°
°°
°°
°°
°°
the cooling and below the heating set
points before an alarm condition will
Used to calculate the delay time before
an alarm is generated after the alarm
Defines the fixed unoccupied
Defines the fixed unoccupied
Defines the fixed minimum
Defines the fixed maximum
Defines the delay time before an alarm
is generated after the alarm condition
Defines the fixed occupied
high space RH alarm limit
Used to calculate the delay time before
an alarm is generated after the alarm
Defines the fixed unnoccupied
high space RH alarm limit
Defines the fixed occupied high
space IAQ/Ventilation alarm limit
Used to calculate the delay time before
an alarm is generated after the alarm
Determines if the SPT alarm is
displayed on the local Rnet sensor
Determines if the SAT alarm is
displayed on the local Rnet sensor
Determines if the Compressor Lockout
alarm is displayed on the local Rnet
Determines if the Condenser Water
Temperature alarm is displayed on the
Determines if the Condensate
Overflow alarm is displayed on the
Determines if the Dirty Filter alarm is
displayed on the local Rnet sensor
Determines if the High Space
RH alarm is displayed on the
occur
condition occurs
ow SPT alarm limit
high SPT alarm limit
SAT alarm limit
SAT alarm limit
occurs
condition occurs
condition occurs
sensor
local Rnet sensor
local Rnet sensor
local Rnet sensor
See TPI
See TPI
See TPI
55
Page 56
56
Page 57
57
Page 58
Copyright 2009 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53500052-01Printed in U.S.A.Form 50PEC-2SIPg 587-09Replaces: 50PEC-1SI