Carrier 50PEC09-18 User Manual

Page 1
AQUAZONE™
50PEC09-18
Water Source Heat Pump Console Unit
with PURON
®
Refrigerant (R-410A)
Installation, Start-Up and Service Instructions
CONTENTS
Page
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . .1,2
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-33
Step 1 — Check Jobsite . . . . . . . . . . . . . . . . . . . . . . . . 2
• STORAGE
• UNIT PROTECTION
Step 4 — Wire Electrical Connections . . . . . . . . . . 17
• SUPPLY VOLTAGE
• EXTERNAL LOOP POWER CONNECTION
• 230-V OPERATION
Step 5 — Wire Low Voltage Connections . . . . . . . 30
• WATER FREEZE PROTECTION
• ACCESSORY CONNECTIONS
• WATER SOLENOID VALVES
• OPTIONAL WALL-MOUNTED THERMOSTAT
• OPTIONAL PREMIERLINK™ CONTROLLER
• WSHP OPEN WIRING
Step 6 — Install Supply and Return Piping. . . . . . 32
• SUPPLY AND RETURN HOSES
• SUPPLY AND RETURN PIPING
Step 7 — Install Condensate Piping . . . . . . . . . . . . 33
PRE-START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33-35
System Cleaning and Flushing . . . . . . . . . . . . . . . . 33
System Checkout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
FIELD SELECTABLE INPUTS . . . . . . . . . . . . . . . .36,37
Complete C Control Jumper Settings. . . . . . . . . . . 36
Complete C Control DIP Switches. . . . . . . . . . . . . . 36
Deluxe D Control Jumper Settings . . . . . . . . . . . . . 36
Deluxe D Control DIP Switches . . . . . . . . . . . . . . . . 36
Deluxe D Control Accessory
Relay Configurations . . . . . . . . . . . . . . . . . . . . . . . 37
START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37-40
Unit Start-Up/Cooling . . . . . . . . . . . . . . . . . . . . . . . . . 37
Operating Limits. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Unit Start-Up/Heating . . . . . . . . . . . . . . . . . . . . . . . . . 37
Unit Start-Up with WSHP Open Controls. . . . . . . . 38
Flow Regulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Antifreeze . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Cooling Tower/Boiler Systems . . . . . . . . . . . . . . . . . 40
Ground Coupled, Closed Loop and Plateframe
Heat Exchanger Well Systems . . . . . . . . . . . . . . . 40
OPERATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40-43
Power Up Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Units with Aquazone Complete C Control. . . . . . . 40
Units with Aquazone Deluxe D Control . . . . . . . . . 40
Units with WSHP Open Multiple Protocol . . . . . . . 41
COMPLETE C AND DELUXE D BOARD
SYSTEM TEST. . . . . . . . . . . . . . . . . . . . . . . . . . . 43-45
Test Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
WSHP Open Test Mode . . . . . . . . . . . . . . . . . . . . . . . 44
Retry Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Page
SERVICE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .45-47
Unit Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
System Flushing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Water Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Refrigerant System . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Condenser Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Blower Motors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Compressor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Safety Control Reset. . . . . . . . . . . . . . . . . . . . . . . . . . 46
Checking System Charge . . . . . . . . . . . . . . . . . . . . . 47
Refrigerant Charging . . . . . . . . . . . . . . . . . . . . . . . . . 47
Air Coil Fan Motor Removal . . . . . . . . . . . . . . . . . . . 47
Replacing the WSHP Open Controller’s
Battery. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . .47-49
Thermistor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
WSHP Open Controller. . . . . . . . . . . . . . . . . . . . . . . . 47
APPENDIX A — WSHP OPEN SCREEN
CONFIGURATION . . . . . . . . . . . . . . . . . . . . . . . . .50-55
START-UP CHECKLIST. . . . . . . . . . . . . . . . . CL-1, CL-2
IMPORTANT: Read the entire instruction manual before starting installation.
SAFETY CONSIDERATIONS
Installation and servicing of air-conditioning equipment can be hazardous due to system pressure and electrical components. Only trained and qualified service personnel should install, repair, or service air-conditioning equipment.
Untrained personnel can perform basic maintenance func­tions of cleaning coils and filters and replacing filters. All other operations should be performed by trained service personnel. When working on air-conditioning equipment, observe precau­tions in the literature, tags and labels attached to the unit, and other safety precautions that may apply.
Improper installation, adjustment, alteration, service, mainte­nance, or use can cause explosion, fire, electrical shock or other conditions which may cause personal injury or property damage. Consult a qualified installer, service agency, or your distributor or branch for information or assistance. The qualified installer or agency must use factory-authorized kits or accesso­ries when modifying this product. Refer to the individual instructions packaged with the kits or accessories when installing.
Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth for brazing operations. Have fire extinguisher available. Read these instructions thoroughly and follow all warnings or cautions attached to the unit. Consult local building codes and applicable electrical codes for special installation requirements.
Understand the signal words — DANGER, WARNING, and CAUTION. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53500052-01 Printed in U.S.A. Form 50PEC-2SI Pg 1 7-09 Replaces: 50PEC-1SI
Page 2
signifies hazards that could result in personal injury or death. CAUTION is used to identify unsafe practices, which would re­sult in minor personal injury or product and property damage.
WARNING
Electrical shock can cause personal injury or death. Before installing or servicing system, always turn off main power to system. There may be more than one disconnect switch. Turn off accessory heater power if applicable.
1. Compare the electrical data on the unit nameplate with ordering and shipping information to verify that the cor­rect unit has been shipped.
2. Keep both the chassis and cabinet covered with the ship­ping carton until all plastering, painting, and finish work is complete and it is time to install the chassis and cabinet.
3. Verify that the refrigerant tubing is free of kinks or dents, and that it does not touch other unit components.
4. Inspect all electrical connections. Connections must be clean and tight at the terminals.
GENERAL
The 50PEC water source heat pump console unit is a decen­tralized room terminal designed for field connection to a closed-circuit piping loop.
Units are typically installed in perimeter zones, usually un­der windows. Supply air is discharged directly into the condi­tioned space through discharge grilles located in the top of the unit.
IMPORTANT: The installation of console water source heat pump units and all associated components, parts, and acces­sories which make up the installation shall be in accordance with the regulations of ALL authorities having jurisdiction and MUST conform to all applicable codes. It is the respon­sibility of the installing contractor to determine and comply with ALL applicable codes and regulations.
INSTALLATION
Step 1 — Check Jobsite —
stalled along an outside wall of the room. Refer to Fig. 1 and 2 for an illustration showing piping locations. Install units with adequate clearance to allow maintenance and servicing. Refer to Table 1 and Fig. 3-14. Locate the console unit so that it pro­vides adequate air circulation throughout the room.
Installation, operation and maintenance instructions are provided with each unit. Before unit start-up, read all manuals and become familiar with the unit and its operation. Thoroughly check out the system before operation. Complete the inspections and instructions listed below to prepare a unit for installation.
Units are typically in-
CAUTION
To avoid equipment damage, do not use these units as a source of heating or cooling during the construction pro­cess. The mechanical components and filters used in these units quickly become clogged with construction dirt and debris which may cause system damage.
CAUTION
To avoid the release of refrigerant into the atmosphere, the refrigerant circuit of this unit must only be serviced by technicians who meet local, regional, and national profi­ciency requirements.
CAUTION
All refrigerant discharged from this unit must be recovered without exception. Technicians must follow industry accepted guidelines and all local, regional, and national statutes for the recovery and disposal of refrigerants.
CAUTION
When a compressor is removed from this unit, system refrigerant circuit oil will remain in the compressor. To avoid leakage of compressor oil, the refrigerant lines of the compressor must be sealed after it is removed.
Table 1 — 50PEC Physical Data
BASE UNIT 50PEC 09 12 15 18 NOMINAL COOLING CAPACITY (Btuh)
COMPRESSOR
BLOWER
Motor Horsepower Wheel Size D x W (in.) 2 each
FILTER SIZE (in.) Bottom Return (Qty)
FILTER SIZE (in.) Front Return (Qty) UNIT WEIGHT (lb)
Shipping Operating
REF. TO AIR HEAT EXCHANGER
Face Area (sq ft) No. of Rows Deep Copper Tube Size OD (in.) Fin Spacing (FPI)
REFRIG. CHARGE (R-410A)/CKT (oz)
No. of Circuits
UNIT CABINET WITH BOTTOM RETURN WITH STANDARD 5 in. SUBBASE Width x Height x Depth (in.) 48 x 26 x 12 48 x 26 x 12 48 x 26 x 12 54 x 26 x 12
UNIT CABINET WITH FRONT RETURN (NO SUBBASE) Width x Height x Depth (in.) 48 x 21 x 12 48 x 21 x 12 48 x 21 x 12 54 x 21 x 12
WATER IN/OUT SIZE OD SWEAT (in.)
CONDENSATE SIZE ID VINYL (in.)
9,300 12,300 13,800 16,000
Rotary
1
/
20
51/4 x 61/
4
10 x 30 x 1 (1) 10 x 30 x 1 (1) 10 x 30 x 1 (1) 10 x 36 x 1 (1)
7 x 291/2 x 1/8 (1) 7 x 291/2 x 1/8 (1) 7 x 291/2 x 1/8 (1) 7 x 351/2 x 1/8 (1)
185 175
1.4 2
3
/
8
13 28
1
1
/
2
5
/
8
1
/
12
51/4 x 61/
190 180
1.4 3
3
/
8
13 29
1
1
/
2
5
/
8
1
/
8
4
51/4 x 61/
200 190
1.8 3
3
/
8
13 37
1
1
/
2
5
/
8
4
1
/
8
51/4 x 61/
232 220
1.8 3
3
/
8
12 39
1
3
/
4
5
/
8
2
4
Page 3
CONTROL BOX
1.62 (41)
2.00 (51)
OPTIONAL MOTORIZED WATER VALVE
OPTIONAL FLOW REGULATOR
OUT
IN
COMPRESSOR ACCESS PANEL
OUT
IN
AL
oW
vE
WATER IN
8.00 MIN (203)
a50-8335
WATER OUT
WATER CONNECTIONS
5/8” (15.9) OD
COPPER, 1/2” IPT, OR
1/2” EPT
Right Hand Configuration
WATER IN
WATER CONNECTIONS
5/8” (15.9) OD COPPER, 1/2” IPT, OR 1/2” EPT
*11.25 (286)
1.75 (44)
WATER OUT
1.84 (77)
2.25 (57)
CONDENSATE
5/8" (15.9) ID VINYL HOSE
OPTI AUTO VALV
OPTIO MOTOR WATER
WATER C
5/8" (15 OD COP 1/2" IPT 1/2" EP
oNAL
IZED aLVE
2.25
oNNECTIONS
AA)
eR,
or
(57)
*
11.25 (286)
2.25 (57)
2.00 (51)
8.00 MIN (203)
CONDENSATE
5/8" (15.9) ID
VINYL HOSE
LEGEND
EPT — External Pipe Thread IPT — Internal Pipe Thread
*Dimension reduced by fitting if selected. NOTE: Dimensions shown are in inches. Dimensions in parentheses are in millimeters.
2.72 (96)
Left Hand Configuration
Fig. 1 — 50PEC09-15 Piping Dimensions
1.50 (38)
a50-8336
3
Page 4
V
R
1.75 (44)
CONTROL BOX
COMPRESSOR
ACCESS
PANEL
1.50 (38)
WATER CONNECTIONS
7/8” (22.2) OD
COPPER, 3/4” IPT, OR
3/4” EPT
WATER
IN
WATER
OUT
8.00 MIN (203)
a50-8337
Right Hand Configuration
OPTIONAL MOTORIZED WATER VALVE
*11.12 (282)
1.75 (44)
OPTIONAL AUTO FLOW VALVE
2.12 (54)
CONDENSATE
1.84 (47)
5/8" (15.9) ID
VINYL HOSE
OUT
IN
OPT AUT VAL
OPT MOT WAT
WATE
.875 ( OD C
3/4" IP 3/4" E
OUT
NS
IN
WATER CONNECTIONS 7/8” (22.2) OD COPPER, 3/4”
IPT OR 3/4” EPT
2.12 (54)
OPTIONAL AUTOFLOW VALVE
OPTIONAL MOTORIZED WATER VALVE
WATER
IN
*11.12 (282)
2.25
(286)
1.50 (38)
8.00 MIN (203)
1.75 (44)
WATER
OUT
CONDENSATE
5/8" (15.9) ID
VINYL HOSE
LEGEND
EPT — External Pipe Thread IPT — Internal Pipe Thread
*Dimension reduced by fitting if selected. NOTE: Dimensions shown are in inches. Dimensions in parentheses are in millimeters.
2.72 (96)
Left Hand Configuration
BLOWER DECK
BLOWER ACCESS PANEL
a50-8338
Fig. 2 — 50PEC18 Piping Dimensions
4
Page 5
Filter located inside and at top of air inlet area. Rotate
filter latch forward, filter rack can be pulled forward 3” to 4” for filter access
16.0
(406)
CONTROL ACCESS DOOR
FRONT VIEW
3.53 (90)
5.0
(127)
DISCHARGE
AIR
30
˚
VIEW
SIDE
3.5
(89)
(658)
25.9
1.75
(44.5)
1.0
1.0 (25)
R.H.
REAR ACCESS (NOTE 2)
(25)
4.5
(114)
AIR INLET AREA
(851)
20.0
(508)
33.5
BOTTOM VIEW
48.0
(1219)
48.0
(1219)
REAR VIEW
.75 (19)
3.00 (76)
10.0
(254)
AIR
INLET
(292)
12.0 (305)
R.H. PIPE AND
ELECTRIC AREA (NOTE 2)
6.88 (174)
2.12 (54)
1.75 (44)
21.0
(533)
11.5
4.9
(125)
a50-8339
1.63 (41)
DAMPER OPENING
11.75 (298)
48.0
(1219)
NOTES:
1. Dimensions are shown in inches. Dimensions in parentheses are in millimeters.
2. Access is reduced if optional disconnect box is selected.
3. Optional autoflow valve, motorized water valve and disconnect box are shown.
Fig. 3 — 50PEC09-15 Bottom Return Cabinet Dimensions — Right Hand Piping
5
0.59
(15)
9.81
(249)
4.9
(125)
Page 6
16.00 (406)
5.00
(127)
DISCHARGE
AIR
3
3.50
(89)
1.75
(44.5)
1.00
(25)
Filter located inside and at top of air inlet area. Push tabs up and back to release filter for replacement.
AIR INLET AREA
39.50
(1003)
4.50
(114)
54.00
(1372)
54.00
(1372)
BOTTOM VIEW
CONTROL ACCESS DOOR
FRONT VIEW
3.53
(90)
10.00 (254)
3.00 (76)
AIR
INLET
R.H. PIPE AND ELECTRIC AREA (NOTE 2)
6.88 (174)
2.12 (54)
0.75 (19)
1.75 (44)
SIDE
VIEW
11.50 (292)
12.00 (305)
25.90 (658)
4.90
(125)
1.00 (25)
RH REAR
ACCESS
(NOTE 2)
NOTES:
1. Dimensions are shown in inches. Dimensions in parentheses are in millimeters.
2. Access is reduced if optional disconnect box is selected.
3. Optional autoflow valve, motorized water valve and disconnect box are shown.
20.00 (508)
REAR VIEW
1.63 (41)
DAMPER OPENING
11.75 (298)
54.00
(1372)
Fig. 4 — 50PEC18 Bottom Return Cabinet Dimensions — Right Hand Piping
0.59 (15)
9.81
(249)
21.00 (533)
4.90
(125)
a50-8340
6
Page 7
Filter located inside and at top of air inlet area. Rotate
filter latch forward, filter rack can be pulled forward 3” to 4” for filter access
CONTROL ACCESS DOOR
FRONT VIEW
3.53 (90)
12.6 (320)
1.5
(38)
DISCHARGE
AIR
3
SIDE
VIEW
3.5
(89)
(658)
25.9
1.75
(44.5)
6.88
(174)
2.12 (54)
1.75 (44)
3.00 (76)
10.0
(254)
AIR INLET AREA
33.5
(851)
L.H. PIPE AND ELECTRIC AREA NOTE 2
0.75 (19)
48.0
(1219)
48.0
(1219)
BOTTOM VIEW
REAR VIEW
L.H.
REAR ACCESS (NOTE 2)
4.5
(114)
1
20.0
(508)
AIR
INLET
(25)
1 (25)
21.0 (533)
11. 5
(292)
12.0 (305)
4.9
(125)
1.63 (41)
DAMPER OPENING
11.75
48.0
(1219)
NOTES:
1. Dimensions are shown in inches. Dimensions in parentheses are in millimeters.
2. Access is reduced if optional disconnect box is selected.
3. Optional autoflow valve, motorized water valve and disconnect box are shown.
(298)
Fig. 5 — 50PEC09-15 Bottom Return Cabinet Dimensions — Left Hand Piping
7
0.59 (15)
9.9
(251)
4.9
(125)
a50-8341
Page 8
Filter located inside and at top of air inlet area. Rotate
filter latch forward, filter rack can be pulled forward 3” to 4” for filter access
CONTROL ACCESS DOOR
FRONT VIEW
(90)
3.53
12.60 (320)
1.50 (38)
DISCHARGE
AIR
3
SIDE
VIEW
3.50 (89)
25.90 (658)
2.12 (54)
1.75
(44.5)
6.88
(174)
1.75
3.00 (76)
(44)
10.00 (254)
AIR INLET AREA
39.50
(1003)
L.H. PIPE AND ELECTRIC AREA (Note 2)
0.75 (19)
54.00
(1372)
54.00
(1372)
BOTTOM VIEW
REAR VIEW
REAR
ACCESS
(Note 2)
4.50
(114)
20.00 (508)
AIR
INLET
1.00 (25)
1.00 (25)
21.00 (533)
11.50 (292)
12.00 (305)
4.90
(125)
1.63 (41)
DAMPER OPENING
11.75
54.00
(1372)
NOTES:
1. Dimensions are shown in inches. Dimensions in parentheses are in millimeters.
2. Access is reduced if optional disconnect box is selected.
3. Optional autoflow valve, motorized water valve and disconnect box are shown.
(298)
Fig. 6 — 50PEC18 Bottom Return Cabinet Dimensions — Left Hand Piping
8
0.59 (15)
9.90
(251)
4.90
(125)
a50-8342
Page 9
21.0
(533)
CONTROL ACCESS DOOR
FRONT VIEW
16.0
(406)
5.0
(127)
7.9
(201)
DISCHARGE
30
˚
AIR
INLET
AIR
SIDE
VIEW
3.5
(89)
21.0
(533)
12.0
(305)
(25)
1.0
1.0 (25)
R.H.
REAR
ACCESS
(NOTE 2)
4.5
(114)
BOTTOM VIEW
20.0
(508)
48.0
(1219)
48.0
(1219)
REAR VIEW
43.7
(1110)
Filter located behind return air grille and requires removal of cabinet front for access.
4.12 (105)
11.50 (292)
R.H. PIPE AND
ELECTRIC AREA
.75 (19)
21.0
(533)
.50 (13)
12.0 (305)
48.0
(1219)
NOTES:
1. Dimensions are shown in inches. Dimensions in parentheses are in millimeters.
2. Access is reduced if optional disconnect box is selected.
3. Optional autoflow valve, motorized water valve and disconnect box are shown.
Fig. 7 — 50PEC09-15 Front Return Cabinet Dimensions — Right Hand Piping
9
a50-8343
Page 10
21.00 (533)
CONTROL ACCESS DOOR
FRONT VIEW
16.00 (406)
5.00
(127)
7.90
(201)
DISCHARGE
3
AIR
INLET
AIR
SIDE VIEW
3.50 (89)
21.00 (533)
12.00 (305)
(25)
1.00
1.00(25)
RH REAR
ACCESS
(NOTE 2)
4.12
(105)
BOTTOM VIEW
20.00
(508)
54.00
(1372)
54.00
(1372)
REAR VIEW
48.00
(1219)
Filter located behind return air grille and requires removal of cabinet front for access.
4.12
(105)
.50 (13)
11.50 (292)
.75 (19)
21.00 (533)
12.00 (305)
R.H. PIPE AND ELECTRIC AREA (NOTE 2)
54.00
(1372)
NOTES:
1. Dimensions are shown in inches. Dimensions in parentheses are in millimeters.
2. Access is reduced if optional disconnect box is selected.
3. Optional autoflow valve, motorized water valve and disconnect box are shown.
Fig. 8 — 50PEC18 Front Return Cabinet Dimensions — Right Hand Piping
10
a50-8344
Page 11
(89)
L.H.
(NOTE 2)
.50 (13)
11.50 (292)
.75 (19)
4.12 (105)
(Note 2)
°
NOTES:
1. Dimensions are shown in inches. Dimensions in parentheses are in millimeters.
2. Access is reduced if optional disconnect box is selected.
3. Optional autoflow valve, motorized water valve and disconnect box are shown.
Fig. 9 — 50PEC09-15 Front Return Cabinet Dimensions — Left Hand Piping
a50-8345
11
Page 12
21.00 (533)
CONTROL ACCESS DOOR
FRONT VIEW
12.60 (320)
1.50
(38.1)
7.90
(201)
DISCHARGE
AIR
3
AIR
INLET
SIDE VIEW
3.50 (89)
21.00 (533)
.50
(13)
11.50 (292)
.75
(19)
4.12
(105)
L.H. PIPE AND ELECTRIC (Note 2)
AREA
REAR VIEW
54.00
(1372)
54.00
(1372)
48.00
(1219)
Filter located behind return air grille and requires removal of cabinet front for access.
BOTTOM VIEW
REAR
ACCESS
(Note 2)
4.50
(114)
1.00 (25)
20.00 (508)
1.00 (25)
21.00 (533)
12.00 (305)
54.00
(1372)
NOTES:
1. Dimensions are shown in inches. Dimensions in parentheses are in millimeters.
2. Access is reduced if optional disconnect box is selected.
3. Optional autoflow valve, motorized water valve and disconnect box are shown.
Fig. 10 — 50PEC18 Front Return Cabinet Dimensions — Left Hand Piping
12
a50-8346
Page 13
Power Supply
Blower Deck
Blower Access Panel
Compressor
Access
Panel
Control Box
40.98
(1041)
4.46
(113)
0.75
(19)
0.75
(19)
*20.50
(521)
11.54
(293)
*16.66
(423)
30°
0.87
(22)
Hard Wire
Power Supply
Blower Deck
Blower Access Panel
Compressor
Access
Panel
Control Box
7.50
(191)
0.87
(22)
11.54
(293)
3.42
(87)
*16.66
(423)
30°
3.01
(76)
5.36
(136)
0.75
(19)
0.75
(19)
4.46
(113)
*
20.50
(521)
40.98
(1040)
3.01
(76)
5.36
(136)
Optional
Motorized
Water Valve
Optional
Autoflow
Valve
Optional
Fused Disconnect Box
(mounted to cabinet
not chassis)
Optional
Motorized
Water Valve
Optional
Autoflow
Valve
*
3.56
(90)
7.50
(191)
3.42
(87)
*3.56
(90)
Optional Fused
Disconnect Box
(mounted to cabinet
not chassis)
Power supply enters
Bottom of Box
Optional Disconnect
Only Box (All Configurations)
Power supply enters
Bottom of Box
4.46
(113)
4.56
(116)
Power supply enters
Bottom of Box
a50-8347
Right Hand Configuration
Left Hand Configuration
Fig. 11 — 50PEC09-15 Chassis Dimensions — Bottom Return
13
1. Dimensions shown are in inches. Dimensions in parentheses are in millimeters.
2. Optional autoflow valve, motorized water valve and disconnect box are shown.
*If optional subbase is selected or if unit is installed raised above the floor, add 4.9 in. to dimension.
NOTES:
Page 14
not chassis)
Optional Fused
Disconnect Box
(mounted to cabinet
Optional
Autoflow
Valve
Power supply enters
Bottom of Box
Optional
Motorized
Water Valve
Power supply enters
Optional Disconnect
Only Box (All Configurations)
Bottom of Box
4.56
(116)
4.46
(113)
a50-8348
40.98
(1041)
Control Box
20.50
(521)
(19)
0.75
Panel
Access
Compressor
7.38
(187)
(762)
30.00
Blower Screen
(76)
3.01
5.36
(136)
Hard Wire
Power Supply
0.87
(22)
30°
Control Box
16.66
(423)
(191)
3.56
(90)
3.42
(87)
11.54
(293)
Blower Deck
Right Hand Configuration
16.66
(423)
Filter
4.46
(19)
0.75
(113)
7.50
Left Hand Configuration
30°
5.36
(136)
Power Supply
(76)
3.01
0.87
(22)
3.42
(87)
7.50
(191)
3.56
(90)
(293)
11.54
Fig. 12 — 50PEC09-15 Chassis Dimensions — Front Return
(19)
0.75
4.46
(113)
Panel
Access
Compressor
7.38
(187)
40.98
(1040)
Blower Deck
(521)
20.50
Filter
Blower Screen
(19)
0.75
30.00
(762)
14
Valve
Optional
Autoflow
Optional
Motorized
Water Valve
Optional
not chassis)
(mounted to cabinet
Fused Disconnect Box
Bottom of Box
Power supply enters
1. Dimensions shown are in inches. Dimensions in parentheses are in millimeters.
2. Optional autoflow valve, motorized water valve and disconnect box are shown.
3. Chassis can mount directly on floor.
NOTES:
Page 15
not chassis)
Optional Fused
(mounted to cabinet
Disconnect Box
Optional
Autoflow
Valve
Power supply enters
Bottom of Box
Optional
Water Valve
Motorized
Power supply enters
Only Box (All Configurations)
Optional Disconnect
Bottom of Box
4.56
(116)
4.46
(113)
46.98
(1193)
Control Box
*20.50
(521)
(19)
0.75
Panel
Access
Compressor
a50-8349
(76)
3.01
(136)
Hard Wire
Power Supply
0.87
(22)
30˚
Control Box
(423)
*16.66
7.5 (191)
3.56
*
(90)
3.43
(87)
11.54
(293)
Valve
Optional
Autoflow
inyl Hose
5/8" ID V
Condensate
(15.8mm)
(19)
0.75
4.46
(113)
Panel
Access
Compressor
Right Hand Configuration
Optional
Motorized
Hard Wire
5.36
Power Supply
(136)
3.01
(76)
0.87
30˚
(22)
Water Valve
Blower Deck
(423)
*16.66
(87)
3.42
7.50
(191)
3.56
*
Blower Access Panel
(90)
4.49
11.54
(114)
Condensate
(293)
0.75
(19)
5/8" ID Vinyl Hose
Left Hand Configuration
Fig. 13 — 50PEC18 Chassis Dimensions — Bottom Return
46.98
(1193)
Blower Deck
(521)
20.50
*
Blower Access Panel
0.75
(19)
15
Valve
Optional
Autoflow
Optional
Motorized
Water Valve
Optional
not chassis)
Disconnect Box
(mounted to cabinet
Bottom of Box
Power supply enters
*If optional subbase is selected, add 4.9 in. to dimension.
1. Dimensions shown are in inches. Dimensions in parentheses are in millimeters.
NOTES:
2. Optional autoflow valve, motorized water valve and disconnect box are shown.
Page 16
(76)
3.01
5.36
(187)
Hard Wire
Power Supply
not chassis)
Optional Fused
(mounted to cabinet
Disconnect Box
Optional
Autoflow
Valve
0.87
(22)
30˚
Power supply enters
Bottom of Box
Optional
(423)
16.66
Water Valve
Motorized
7.5 (191)
3.56
(90)
Power supply enters
Only Box (All Configurations)
Optional Disconnect
(87)
3.43
11.54
Bottom of Box
4.56
(116)
(293)
4.46
(113)
46.98
(1193)
Valve
Optional
Autoflow
Optional
Motorized
Water Valve
Control Box
Blower Deck
20.50
(521)
(19)
0.75
Panel
Access
Compressor
7.38
(187)
a50-8350
Blower Screen
(914)
36.00
Filter
(19)
0.75
4.49
(114)
46.98
(1193)
Control Box
Access
Compressor
Blower Deck
(521)
20.50
Panel
7.38
(187)
Filter
4.46
(113)
0.75
Blower Screen
0.75
(19)
(19)
36.00
(914)
Right Hand Configuration
Hard Wire
5.36
Power Supply
(136)
3.01
(76)
0.87
30˚
(22)
Valve
Optional
Autoflow
(423)
16.66
(87)
3.42
Optional
Motorized
Water Valve
7.50
(191)
3.56
(90)
(293)
11.54
Optional
not chassis)
Disconnect Box
(mounted to cabinet
Left Hand Configuration
Bottom of Box
Power supply enters
1. Dimensions shown are in inches. Dimensions in parentheses are in millimeters.
NOTES:
Fig. 14 — 50PEC18 Chassis Dimensions — Front Return
2. Optional autoflow valve, motorized water valve and disconnect box are shown.
3. Chassis can mount directly on floor.
16
Page 17
Step 2 — Check Unit — Upon receipt of shipment at
the jobsite, carefully check the shipment against the bill of lad­ing. Make sure all units have been received. Inspect the carton or crating of each unit, and inspect each unit for damage. En­sure the shipping company makes proper notation of any short­ages or damage on all copies of the freight bill. Concealed damage not discovered during unloading must be reported to the shipping company within 15 days of receipt of shipment.
NOTE: It is the responsibility of the purchaser to file all neces­sary claims with the shipping company.
STORAGE
CAUTION
DO NOT store or install console units in corrosive environ­ments or in locations subject to temperature or humidity extremes (e.g., attics, garages, rooftops, etc.). Corrosive conditions and high temperature or humidity can signifi­cantly reduce performance, reliability, and service life. Always move units in an upright position. Tilting units on their sides may cause equipment damage.
Upon the arrival of equipment at the jobsite, immediately
store units in their shipping cartons in a clean, dry area. Store
units in an upright position at all times. Stack units a maxi­mum of 3 units high. Use pallets to separate each layer of units. DO NOT remove equipment from shipping cartons until equipment is required for installation.
UNIT PROTECTION — Cover console units on the jobsite with either shipping cartons, vinyl film, or an equivalent protective covering. Cap the open ends of pipes stored on the jobsite. In areas where painting, plastering, or the spraying of fireproof material has not been completed, all due precautions must be taken to avoid physical damage to the units and con­tamination by foreign material. Physical damage and contami­nation may prevent proper start-up and may result in costly equipment clean-up.
Examine all pipes, fittings, and valves before installing any of the system components. Remove any dirt found on these components.
Step 3 — Mount Unit
1. Unpack the unit from the shipping carton. Remove the front cabinet by lifting up and away from the backplate. Protect the cabinet from damage during installation by re­turning it to its original vinyl pack until required.
2. Remove compressor isolation plate shipping bolts (4), as shown in Fig. 15.
3. Using a carpenter’s square and a level, ensure the unit is level. Shim the unit if necessary to assure proper installation.
Poor or inadequate installation may result in noisy unit operation or unattractive appearance.
4. Select the proper fasteners to connect the backplate se­curely to the wall.
5. Fasten the backplate onto the wall through the screw holes located in the back flange. Secure the subbase in place.
Step 4 — Wire Electrical Connections
WARNING
To avoid possible injury or death due to electrical shock, open the power supply disconnect switch and secure it in an open position during installation.
CAUTION
Use only copper conductors for field-installed electrical wiring. Unit terminals are not designed to accept other types of conductors.
All field-installed wiring, including the electrical ground, MUST comply with National Electrical Code (NEC) as well as all applicable local codes. In addition, all field wiring must conform to the Class II temperature limitations described in the NEC.
Consult the unit wiring diagram located on the inside of the compressor access panel to ensure proper electrical hookup. The installing (or electrical) contractor must make the field connec­tions shown in Fig. 16 when using field-supplied disconnect.
Refer to unit wiring diagrams Fig. 17-29 for a schematic of the field connections, which must be made by the installing (or electrical) contractor. Operating voltage must be within voltage range shown in Table 2.
Make all final electrical connections with a length of flexi­ble conduit to minimize vibration and sound transmission to the building.
SUPPLY VOLTAGE — Operating voltage to unit must be within voltage range indicated on unit nameplate.
EXTERNAL LOOP POWER CONNECTION — If the unit will be connected to an external loop pump or flow controller, connect the pump to the loop pump terminal block PB1. The maximum power handling is 4 amps at 240-v. The pumps will automatically cycle as required by the unit.
230-V OPERATION — All 208/230-v units are factory­wired for 208-v. The transformer wiring may be switched for 230-v operation (as illustrated on the wiring diagrams) by switching the RED and ORG leads at L1.
SHIPPING BOLTS
Fig. 15 — Remove 4 Shipping Bolts on
Compressor Isolator Plate
A
HEAT PUMP
A = Two power wires for single-phase units. B = 1 heat/1 cool/manual or auto changeover remote 24-V thermostat.
NOTE: All customer-supplied wiring to be copper only and must conform to national and local electrical codes. Wiring shown with dashed lines must be field-supplied and field-installed. “B” wiring only required with systems using remote-mounted thermostats.
B
FIELD SUPPLIED
DISCONNECT SWITCH
ROOM THERMOSTAT
Disconnect electrical power source to prevent injury or death from electri­cal shock.
Use copper conductors only to prevent equipment damage.
WARNING
CAUTION
Fig. 16 — Typical Field-Installed Wiring
17
Page 18
a50-8452
Complete C
AL Alarm Relay Contacts BM Blower Motor BR Blower Relay CAP Capacitor CB Circuit Breaker CO Sensor, Condensate Overflow CR Compressor Relay DM Damper Motor FP1 Sensor, Water Coil Freeze Protection FP2 Sensor, Air Coil Freeze Protection HP High-Pressure Switch JW1 Jumper Wire for Alarm LOC Loss of Charge Pressure Switch PB Power Terminal Block RAS Return Air Sensor RVS Reversing Valve Solenoid TRANS WV
---------- Field Line Voltage Wiring
Transformer
Wate r Valve
Field Low-Voltage Wiring Printed Circuit Trace Option Low Voltage Wiring
LEGEND
Relay/Contactor Coil
Solenoid Coil
Thermistor
Circuit Breaker
Relay Contacts-N.O.
Switch-Temperature
Switch-High Pressure
Switch-Low Pressure
Ground
Wire Nut
>
>
Mate-N-Lok
*Optional wiring. †Registered trademark of AMP Incorporated.
SEE NOTE 9
Complete C
BLOWER MOTOR WIRING
UNIT SIZE POLE A POLE B
09-18 5 4
NOTES:
1. Compressor and blower motor thermally pro­tected internally.
2. All wiring to the unit must comply with local codes.
3. Transformer is wired to 115-V (WHT) lead for 115/1/60 units; 265-V (BRN) lead for 265/1/60 units; or 208-V (RED) lead for 208/1/60 units.
For 230/1/60 operation, switch the RED and ORG leads at L1 and insulate the RED lead. Transformer is energy limiting or may have a circuit breaker.
4. FP1 thermistor provides freeze protection for WATER. When using ANTI-FREEZE solutions, cut JW3 jumper.
5. For remote sensor, position jumper J1 on upper 2 pins.
6. For F position, position jumper on both pins.
°
For C, position jumper on one pin.
°
7. Transformer secondary ground via Complete C board standoffs and screws to control box. (Ground available from top two standoffs as shown.)
8. Mate-N-Lok† plug is optional.
9. Factory-cut jumper (JW1). Dry contact will be available between AL1 and AL2.
Fig. 17 — 50PEC Unit Manual or Auto Changeover with Complete C Controller Wiring
18
Page 19
COMPLETE C
COMPLETE C
a50-8327.eps
PEC
PEC12-18
PEC
AL Alarm Relay Contacts BM Blower Motor BR Blower Relay CAP Capacitor CB Circuit Breaker CO Sensor, Condensate Overflow CR Compressor Relay DM Damper Motor FP1 Sensor, Water Coil Freeze Protection FP2 Sensor, Air Coil Freeze Protection FSS Fan Speed Switch HP High-Pressure Switch JW1 Jumper Wire for Alarm LOC Loss of Charge Pressure Switch PB Power Terminal Block RVS Reversing Valve Solenoid TRANS — Tr a n sf o r me r WV Water Valve
---------- Field Line Voltage Wiring
Field Low-Voltage Wiring Option Low-Voltage Wiring Printed Circuit Trace
Fig. 18 — 50PEC Unit with Complete C and LON Controllers
LEGEND
Relay/Contactor Coil
Solenoid Coil
Thermistor
Circuit Breaker
Relay Contacts-N.O.
Switch-Temperature
Switch-High Pressure
Switch-Low Pressure
Ground
>
>
*Optional wiring.
†Registered trademark of Echelon Corporation.
Wire Nut
Mate-N-Lock
NOTES:
1. Compressor and blower motor thermally pro­tected internally.
2. All wiring to the unit must comply with local codes.
3. Transformer is wired to 115-V (WHT) lead for 115/1/60 units, 265-V (BRN) lead for 265/1/60 units, 240-V (ORG) lead for 240/1/50 units, or 208-V (RED) lead for 208/1/60 units.
Rewire transformer L1 connection if voltage is 230-1-60 or 220-1-50, insulate unused lead.
4. FP1 thermistor provides freeze protection for WATER. When using ANTI-FREEZE solutions, cut JW3 jumper.
5. Refer to LonWorks† Installation, Application, and Operation manual for control wiring to the unit. Low voltage wiring must be “class 1 and voltage rated equal to or greater than unit supply voltage.
6. Factory-cut jumper (JW1). Dry contact will be available between AL1 and AL2.
7. Transformer secondary ground via Complete C board standoffs and screws to control box. (Ground available from top 2 standoffs as shown.)
19
Page 20
DELUXE D
DELUXE D
AL Alarm Relay Contacts BM Blower Motor CAP Capacitor CB Circuit Breaker CO Sensor, Condensate Overflow CR Compressor Relay DM Damper Motor FP1 Sensor, Water Coil Freeze Protection FP2 Sensor, Air Coil Freeze Protection FSS Fan Speed Switch HP High-Pressure Switch JW1 Jumper Wire for Alarm LOC Loss of Charge Pressure Switch PB Power Terminal Block RVS Reversing Valve Solenoid TRANS — Transformer WV Wate r Valve
---------- Field Line Voltage Wiring
*Optional wiring.
Field Low-Voltage Wiring Printed Circuit Trace
Fig. 19 — 50PEC Unit with Deluxe D and LON Controllers
a50-8328
LEGEND
Relay/Contactor Coil
Solenoid Coil
Thermistor
Circuit Breaker
Relay Contacts-N.O.
Switch-Temperature
Switch-High Pressure
Switch-Low Pressure
Ground
Wire Nut
>
>
Mate-N-Lock
NOTES:
1. Compressor and blower motor thermally pro­tected internally.
2. All wiring to the unit must comply with local codes.
3. Transformer is wired to 115-V (WHT) lead for 115/1/60 units, 265-V (BRN) lead for 265/1/60 units, 240-V (ORG) lead for 240/1/50 units, or 208-V (RED) lead for 208/1/60 units.
Rewire transformer L1 connection if voltage is 230-1-60 or 220-1-50, insulate unused lead.
4. FP1 thermistor provides freeze protection for WATER. When using ANTI-FREEZE solutions, cut JW3 jumper.
5. Refer to Microprocessor Control Installation, Application, and Operation manual for control wiring to the unit. Low voltage wiring must be “class 1 and voltage rated equal to or greater than unit supply voltage.
6. Factory-cut jumper (JW4). Dry contact will be available between AL1 and AL2.
7. Transformer secondary ground via Deluxe D board standoffs and screws to control box. (Ground available from top 2 standoffs as shown.)
20
Page 21
DELUXE D
AL Alarm Relay Contacts BM Blower Motor BR Blower Relay CAP Capacitor CB Circuit Breaker CO Sensor, Condensate Overflow CR Compressor Relay DM Damper Motor FP1 Sensor, Water Coil Freeze Protection FP2 Sensor, Air Coil Freeze Protection HP High-Pressure Switch JW1 Jumper Wire for Alarm LOC Loss of Charge Pressure Switch NLL Night Low Limit Switch PB Power Terminal Block RAS Return Air Sensor RVS Reversing Valve Solenoid TRANS — Transformer WV Wate r Valve
---------- Field Line Voltage Wiring
*Optional wiring.
Field Low-Voltage Wiring Printed Circuit Trace
LEGEND
Relay/Contactor Coil
Solenoid Coil
Thermistor
Circuit Breaker
Relay Contacts-N.O.
Switch-Temperature
Switch-High Pressure
Switch-Low Pressure
Ground
Wire Nut
>
>
Mate-N-Lock
DELUXE D
a50-8329
PEC09-18
NOTES:
1. Compressor and blower motor thermally pro­tected internally.
2. All wiring to the unit must comply with local codes.
3. Transformer is wired to 115-V (WHT) lead for 115/1/60 units, 265-V (BRN) lead for 265/1/60 units, 240-V (ORG) lead for 240/1/50 units, or 208-V (RED) lead for 208/1/60 units.
Rewire transformer L1 connection if voltage is 230-1-60 or 220-1-50, insulate unused lead.
4. FP1 thermistor provides freeze protection for WATER. When using ANTI-FREEZE solutions, cut JW3 jumper.
5. Refer to Microprocessor Control Installation, Application, and Operation manual for control wiring to the unit. Low voltage wiring must be “class 1 and voltage rated equal to or greater than unit supply voltage.
6. Factory-cut jumper (JW4). Dry contact will be available between AL1 and AL2.
7. Transformer secondary ground via Deluxe D board standoffs and screws to control box. (Ground available from top 2 standoffs as shown.)
Fig. 20 — 50PEC Unit Manual or Auto Changeover and Deluxe D Controller
21
Page 22
POWER SUPPLY
REFER TO DATA PLATE
USE COPPER CONDUCTORS ONLY.
SEE NOTE 2
REFER TO DISCONNECT
BOX FOR OPTIONAL
POWER SUPPLY CONNECTION
OPTIONAL CORD CONNECTION
CB*
24V
GROUND
L2
L1
SEE NOTE 3
TRANS
L2 (ribbed)
L1 (plain)
BLK
ORG 230V
NEUTRAL ON 265V SYSTEMS
2
PB 1
GROUND
RED
BLK
COM
8
4
BM
FSS
COMPRESSOR
BLU
R
RED
BLK
B (HIGH)
A (LOW)
RED
1
S
C
BLK
H
CAP
6
RED
C
NO
BLK
BRN
YEL
BLK
CR
2
2
1
2
F
BR
CAP
TYPICAL HEAT PUMP T-STAT
SEE NOTE 5
CLASS 1 OR 2 WIRING ACCEPTABLE OUTSIDE CONTROL BOX
Y
O
G
R
C
L
BRN YEL
GROUND PB
BLK
RED
(220V)
ORG (240V)
WV
TRANSFORMER
CR
BR
SEE NOTE 7
TRANS
CB 24V
BLU
BRN
CLASS 1 WIRING REQUIRED INSIDE CONTROL BOX
COMPRESSOR
COOLING
FAN
24 VAC
COMMON
ALARM
YEL
C
R
Y
W
O
G
R
C
AL1
AL2
A
P1
Y
ORGYEL
DM
10
BR
BR BRG CCG
TEST PINS
SEE NOTE 4
JW3
FP1
JW2
FP2
DIP SWITCH
JW1
OFF ON
SEE
ALARM
NOTE 6
RELAY
BRNYEL
10
CR
BRNBRNGRYYEL
1
PM: DISABLED/ ENABLED
2
STAGE 2: 2/1
3
NOT USED
4
NOT USED
5
FP1/FP2 FAULTS: 3/1
G
COMPLETE C
MICRO-
PROCESSOR
CONTROL
LOGIC
CC
COMPR. RELAY
STATUS LED
TRANSFORMER PRIMARY
SEE NOTE 7
YELBRN
1
HP
2 3
LOC
4 5
FP1
6 7
FP2
8 9
RV
10
CO12
P2
24V DC
EH1 EH2
P3
CO
LEAD COLORS
VOLTAGE
RED RED BLU BRN GRY GRY VIO VIO BRN ORG NOT USED
YEL
115 208 230 265
LEAD COLOR
WHT RED ORG BRN
HP
LOC
FP1
SEE NOTE 4
FP2
RVS
CO
BLOWER MOTOR WIRING
UNIT SIZE POLE A POLE B
09 5 4 12 4 3 15 4 3 18 4 3
COMPLETE
C
CONTROL
LEGEND
AL Alarm Relay Contacts BM Blower Motor BR Blower Relay CAP Capacitor CB Circuit Breaker CO Sensor, Condensate Overflow CR Compressor Relay DM Damper Motor FP1 Sensor, Water Coil Freeze Protection FP2 Sensor, Air Coil Freeze Protection FSS Fan Speed Switch HP High-Pressure Switch JW1 Jumper Wire for Alarm LOC Loss of Charge Pressure Switch PB Power Terminal Block PM Performance Monitor RVS Reversing Valve Solenoid TRANS — Transformer WV Water Valve
---------- Field Line Voltage Wiring
Field Low-Voltage Wiring
Fig. 21 — 50PEC Unit Remote-Mounted Thermostat with Complete C Controller Wiring
Printed Circuit Trace Option Low Voltage
Wiring
Relay/Contactor Coil
Solenoid Coil
Thermistor
Circuit Breaker Relay Contacts-N.O.
Switch-High Pressure
Switch-Low Pressure
Ground
Wire Nut
>
>
Mate-N-Lock
22
*Optional wiring. NOTES:
1. Compressor and blower motor thermally protected internally.
2. All wiring to the unit must comply with local codes.
3. Transformer is wired to 115-V (WHT) lead for 115/1/60 units; 265-V (BRN) lead for 265/1/60 units; or 208-V (RED) lead for 208/1/60 units.
For 230/1/60 operation, switch the RED and ORG leads at L1 and insulate the RED lead.
Transformer is energy limiting or may have a circuit breaker.
4. FP1 thermistor provides freeze protection for WATER. When using ANTI-FREEZE solutions, cut JW3 jumper.
5. Typical heat pump thermostat wiring shown. Refer to thermostat Installation Instructions for wiring to the unit.
6. 24-V alarm signal shown. For dry alarm contact, cut JW1 jumper and dry contact will be available between AL1 and AL2.
7. Transformer secondary ground via Com­plete C board standoffs and screws to control box. (Ground available from top two standoffs as shown.)
Page 23
POWER SUPPLY
REFER TO DATA PLATE
CAP
DELUXE
D
CONTROL
BR 2
(HI)
USE COPPER CONDUCTORS ONLY.
CLASS 1 OR 2 WIRING ACCEPTABLE OUTSIDE CONTROL BOX
Y
O G R C
X1
TYPICAL HEAT
PUMP T-STAT
SEE NOTE 5
BRN
BRN
ORG
YEL YEL YEL
DM
GROUND
PB
OVERRIDE
WITH DIGITAL T-STAT
OV OV
LUG
SEE NOTE 2
REFER TO DISCONNECT
BOX FOR OPTIONAL
POWER SUPPLY CONNECTION
OPTIONAL CORD CONNECTION
BRN
CLASS 1 WIRING REQUIRED INSIDE
CLOSED=UNOCCUPIED
NLL
SEE
NOTE 7
COMPRESSOR
COOLING FAN 24 VAC COMMON ALARM
RED
TIME CLOCK
BRN
WHT
YEL
WV
RED
OVERRIDE OVERRIDE
TRANSFORMER
CR
BR 1
(LO)
LEGEND
AL Alarm Relay Contacts BM Blower Motor BR Blower Relay CAP Capacitor CB Circuit Breaker CO Sensor, Condensate Overflow CR Compressor Relay DM Damper Motor FP1 Sensor, Water Coil Freeze Protection FP2 Sensor, Air Coil Freeze Protection FSS Fan Speed Switch HP High-Pressure Switch JW1 Jumper Wire for Alarm LOC Loss of Charge Pressure Switch NLL Night Low Limit OV Override PB Power Terminal Block PM Performance Monitor RVS Reversing Valve Solenoid TRANS — Transformer WV Water Valve
---------- Field Line Voltage Wiring
Fig. 22 — 50PEC Unit Remote-Mounted Thermostat with Deluxe D Controller Wiring
Y1 Y1 W1
O/W2
G R C
AL1
P2
AL2
NSB
ESD
OVR
P3
R NO1 NC1
COM
NO2 NC2
COM
R
GROUND
6
2
1 2 3 4 5 6 7 8 9
10
CCG
CR
CC
8
4
2
BM
1
3
FSS
RED RED BLU BRN GRY GRY VIO VIO BRN ORG NOT USED YEL
BRN
YEL
BLU
RED
2
COMPRESSOR
S
R
C
BLK
B (HIGH)
A (LOW)
RED
BLK
TRANSFORMER PRIMARY
LEAD COLORS
1
VOLTAGE
1
BLOWER MOTOR WIRING
CR
UNIT SIZE POLE A POLE B
0
115 208 230 265
HP
LOC
FP1
FP2
RVS
CO
LEAD COLOR
SEE NOTE 4
WHT RED ORG BRN
09 5 4 12 4 3 15 4 3 18 4 3
NEUTRAL ON 265V SYSTEMS
L2
L1
CB*
TRANS
24V
YEL
BLU
C
1 2 3 4 5 6 7 8
ACC1 RELAY
ACC2 RELAY
R
ALARM
RELAY
SEE
NOTE 6
AL2 DRY
OFF ON
S1
DIP SWITCH
PACKAGE
P1
R
C
H A
2
PB 1
L2 (ribbed)
GROUND
L1 (plain)
BLK
ORG 230V
SC
R C S
COM2 COM1
JW4
TEST
PINS
1
PM: DISABLE/ ENABLE
2
UNIT STAGE: 2/1
3
T-STAT: HEAT COOL/ HEAT PUMP
4
RV ON B/RV ON O
5
DEHUMID/NORMAL
6
NOT USED
7
BOILERLESS: ENABLE/DISABLE
8
BOILERLESS: 40°F/50°F
RED
SEE NOTE 3
DELUXE D
MICROPROCESSOR
CONTROL LOGIC
JW3 FP1 LOW
JW2 FP2 LOW JW1 LP N.O.
OFF ON
DIP SWITCH
PACKAGE
STATUS
SEE NOTE 4
S2
H
CAP
RED
C
F
BLK
FAN ENABLE
GRY
COM
NO
GRY
COM
NO NC
G
Y
TEST
R
FAULT
RV
RELAY
1
ACC1
2
FUNCTIONS
3 4
ACC2
5
FUNCTIONS
6 7
H: HI FAN/DEHUMID
8
NOT USED
BRN
YEL
RELAY
FAN SPEED RELAY
HP
LOC
FP1
FP2
RV
CO12
P7
24V DC
EH1 EH2
P6
COMPR. RELAY
*Optional wiring. NOTES:
1. Compressor and blower motor thermally protected internally.
2. All wiring to the unit must comply with local
Field Low-Voltage Wiring Printed Circuit Trace Option Low Voltage Wiring
Relay/Contactor Coil
Solenoid Coil
Thermistor
Circuit Breaker Relay Contacts-N.O.
Switch-High Pressure
Switch-Low Pressure
Ground
Wire Nut
>
>
Mate-N-Lock
codes.
3. Transformer is wired to 115-V (WHT) lead for 115/1/60 units; 265-V (BRN) lead for 265/ 1/60 units; or 208-V (RED) lead for 208/1/60 units. For 230/1/60 operation, switch the RED and ORG leads at L1 and insulate the RED lead. Transformer is energy limiting or may have a circuit breaker.
4. FP1 thermistor provides freeze protection for WATER. When using ANTI-FREEZE solutions, cut JW3 jumper.
5. Typical heat pump thermostat wiring shown. Refer to thermostat Installation Instructions for wiring to the unit.
6. 24-V alarm signal shown. For dry alarm con­tact, cut AL2 DRY (JW4) jumper and dry contact will be available between AL1 and AL2.
7. Transformer secondary ground via Deluxe D board standoffs and screws to control box. (Ground available from top two standoffs as shown.)
23
Page 24
PREMIER
LINK
PWR
HS1/EXH/RVS
CR
CR
COMPLETE
C
CONTROL
Y
W
O
LEGEND
CR — Control Relay LWT — Leaving Water Temperature Sensor SAT — Supply Air Temperature Sensor SPT — Space Temperature Sensor
NOTE: Reversing valve is on in Cooling mode.
J6
S
P
T
J5
L
S A
W
T
T
Fig. 23 — PremierLink™ Controller Applications with Complete C Control
J8
PWR
J1
CMPSAFE
PREMIER
LINK
CMP1
FAN
PWR
G
R
C
AL1
AL2
A
J4
DELUXE
D
CONTROL
LEGEND
LWT — Leaving Water Temperature Sensor SAT — Supply Air Temperature Sensor SPT — Space Temperature Sensor
NOTE: Reversing valve is on in Cooling mode.
J6
S P
T
J5
L
S A
W
T
T
Fig. 24 — PremierLink Controller Applications with Deluxe D Control
J8
PWR
J1
CMPSAFE
HS2
HS1
CMP2
CMP1
FAN
Y1
Y2
W1
O/W2
G
R
C
AL1
J4
24
Page 25
Fig. 25 — Units with Complete C and WSHP Open Multiple Protocol Controls
WHSP-OPEN
A50-8355
25
LEGEND
BM Blower Motor
BR Blower Relay
CO Condensate Overflow
LWT — Leaving Water Temperature
N.C. — Normally Closed
OAD — Outside Air Damper
OCC — Occupancy Input Contact
RH Relative Humidity
SAT — Supply Air Temperature
SPT — Space Temperature
Page 26
Fig. 26 — Units with Deluxe D and WSHP Open Multiple Protocol Controls
WSHP-OPEN
A50-8354
26
LEGEND
BM Blower Motor
CO Condensate Overflow
LWT — Leaving Water Temperature
N.C. — Normally Closed
OAD — Outside Air Damper
OCC — Occupancy Input Contact
RH Relative Humidity
SAT — Supply Air Temperature
SPT — Space Temperature
Page 27
A50-8356
27
WSHP-OPEN
LEGEND
CO Condensate Overflow
LWT — Leaving Water Temperature
N.C. — Normally Closed
OAD — Outside Air Damper
OCC — Occupancy Input Contact
RH Relative Humidity
SAT — Supply Air Temperature
SPT — Space Temperature
Fig. 27 — Units with Complete C, ECM and WSHP Open Multiple Protocol Controls
Page 28
A50-8353
28
WSHP-OPEN
LEGEND
CO Condensate Overflow
LWT — Leaving Water Temperature
N.C. — Normally Closed
OAD — Outside Air Damper
OCC — Occupancy Input Contact
RH Relative Humidity
SAT — Supply Air Temperature
Fig. 28 — Units with Deluxe D, ECM and WSHP Open Multiple Protocol Controls
SPT — Space Temperature
Page 29
CHANNEL
DESIGNATION
CONNECTION
PIN NUMBERS
Factory Wiring
Field Wiring
N/A AO (0-10Vdc/2 - 10Vdc) J2 4 and 5* Analog Output 1
N/A BO Relay (24VAC, 1A) J1, 4* Binary Output 1 (G)
Outside Air Damper N/A AO (0-10Vdc/2 - 10Vdc) J22 1 and 2* Analog Output 2
located at the end of network
Gnd
N/A BO Relay (24VAC, 1A) J1, 5* Binary Output 2
Rnet+
Rnet-
+12V
Supply Fan On/Low Speed
(3 Speed Only)
Auxiliary Heat or 2-Position Water Loop
Economizer
Reversing Valve (B or O Operation) N/A BO Relay (24VAC, 1A) J1, 6* Binary Output 3 (RV)
Compressor 2nd Stage N/A BO Relay (24VAC, 1A) J1, 7 Binary Output 4 (Y2)
Compressor 1st Stage N/A BO Relay (24VAC, 1A) J1, 8 Binary Output 5 (Y1)
Dehumidification Relay N/A BO Relay (24VAC, 1A) J11, 7 and 8 (NO) Binary Output 6
*These inputs are configurable.
Fan Speed Medium/Low (3 Speed Only) N/A BO Relay (24VAC, 1A) J11, 5 and 6 (NO)* Binary Output 7
Fan Speed High/Low (3 Speed Only) N/A BO Relay (24VAC, 1A) J11, 2 and 3 (NO)* Binary Output 8
Fig. 29 — WSHP Open Control
segment only.
LEGEND
with at least two #6 x 1 in. self-tapping screws. Allow adequate clearance for wiring.
sors requiring a separate isolated 24 vac power source will not utilize WSHP termi-
nals J4-1, or 4.
1. Mount the water source heat pump controller in the equipment controls enclosure
2. Verify sensor power and wiring requirements prior to making any terminations. Sen-
AI Analog Input
AO Analog Output
BI Binary Input
-Gnd
+ 24vac
NOTES:
BO Binary Output
SPT Space Temperature
a50-8380
(If not installed, it must be connected to DO-5)
(DI-3/Dry Contact)
Fan (DO-1) (Fan On or Low Speed)
Condensate
Overflow Switch
RED
BRN
GRN
WHT
Comp Status (DI-5)
LWT (Input 6)
SAT (LAT) (Input 7)
Aux Heat (DO-2)
Comp #1 (DO-5)
Comp #2 (DO-4)
Reversing Valve (DO-3)
RED
BLU
PINK
YLW
ORN
WTR. Loop Econ. (AO 1)
AO1 – Aux Reheat or Cond.
VIO
BRN
ORN
PINK
PINK
BLU
1
2 3
7
4
5
67
8
J5
10
OA DAMPER (AO-2)
12
FAN SPEED (DO-7) (MED OR LOW)
DEHUMIDIFY OUTPUT CONTACT (DO-6) (FACTORY OPTION)
J11
J22
WSHP Open Inputs and Outputs Table
SPT PLUS Sensor
Shown
INPUT/OUTPUT TYPE PART NUMBERS TYPE OF I/O
Inputs
Space Temperature Sensor SPS, SPPL, SPP Communicating J13, 1 - 4 Local Access Port
Space Relative Humidity 33ZCSENSRH-01 AI (4 - 20mA) J4, 5 and 6 Analog Input 1
FIELD INSTALLED
FAN SPEED (DO-8) (HIGH OR FAN ON )
123 45678
To
SPT PLUS
J14
2 3
1
J17
J19
GREEN
WHITE
BLACK
RED
Indoor Air Quality 33ZCSENCO2 AI (4 -20mA) J4, 2 and 3 Analog Input 2
Condensate Switch N/A BI (Dry Contacts) J1, 2 Binary Input 3
Stage 1 Compressor Status N/A BI (Dry Contacts) J1, 10 Binary Input 5
Leaving Condenser Water Temperature 10K Type II AI (10K Thermistor) J2, 1 and 2 Analog Input 6
To WSHP Controller Rnet Terminals (J13)
Supply Air Temperature 33ZCSENSAT AI (10K Thermistor) J2, 3 and 4 Analog Input 7
Outputs
Modulating Valve (Auxiliary Heat/Water
Economizer)
DB
012207-1BT485BT
LED1
Install BT485 where device is
J20
1
11
J1 J2
1
2
3
-
+
+24vac
SENSOR
4-20mA
SPACE CO2
-
+
+24vac
SENSOR
4-20mA
SPACE RH
FIELD INSTALLED (OPTIONAL) – SEE NOTE 2
45
6
J4
Field Installed
123 4
RED
BLACK
WHITE
GREEN
123 4
Local Access Port
J12
J13
3
2
4
1
0
5
LSB
9
7
6
8
3
2
4
MSTP Baud
1
0
5
9600 19.2k 38.4k 76.8k
9
MSB
7
6
8
2
3
4
O
N
12
3 45
SW3
6
7 8
FIELD INSTALLED
SPT PLUS Sensor
Shown
GREEN
WHITE
BLACK
RED
To WSHP Controller
Rnet Terminals (J13)
Gnd
Rnet+
Rnet-
+12V
29
Page 30
Table 2 — Electrical Data — 50PEC Units
50PEC
UNIT SIZE
09
12
15
18
FLA Full Load Amps HACR — Heating, Air Conditioning and Refrigeration LRA Locked Rotor Amps RLA Rated Load Amps
VOLTAGE
CODE
1 115-1-60 104/126 1 8.1 46.5 0.6 8.6 10.7 15 3 208/230-1-60 197/254 1 4.5 23.0 0.4 4.9 6.0 15 4 265-1-60 239/292 1 3.1 24.0 0.4 3.5 4.3 15 1 115-1-60 104/126 1 10.6 55.8 1.0 11.6 14.3 25 3 208/230-1-60 197/254 1 5.2 24.0 0.6 5.8 7.1 15 4 265-1-60 239/292 1 4.2 25.0 0.4 4.6 5.7 15 3 208/230-1-60 197/254 1 6.1 30.0 0.8 6.9 8.4 15 4 265-1-60 239/292 1 4.7 28.5 0.6 5.3 6.5 15 3 208/230-1-60 197/254 1 6.8 38.0 0.7 7.5 9.2 15 4 265-1-60 239/292 1 6.2 29.0 0.6 6.8 8.4 15
LEGEND
V-P H- Hz
MIN/MAX
VOLTAGE
COMPRESSOR
QTY RLA LRA
Step 5 — Wire Low Voltage Connections
WATER FREEZE PROTECTION — The Aquazone™ con­trol allows the field selection of source fluid freeze protection points through jumpers. The factory setting of jumper JW3 (FP1) is set for water at 30 F. In earth loop applications, jumper JW3 should be clipped to change the setting to 10 F when using antifreeze in colder earth loop applications. See Fig. 30.
FAN MOTO R
FLA
TOTAL UN IT
FLA
MIN CIRCUIT
AMPS
MAX
FUSE/HACR
WATER SOLENOID VALVES — An external solenoid valve(s) should be used on ground water installations to shut off flow to the unit when the compressor is not operating. A slow closing valve may be required to help reduce water hammer. Figure 31 shows typical wiring for a 24-vac external solenoid valve. Figures 32 and 33 illustrate typical slow closing water control valve wiring for Taco 500 Series and Taco ESP Series valves. Slow closing valves take approximately 60 sec. to open (very little water will flow before 45 sec.). Once fully open, an end switch allows the compressor to be energized (only on valves with end switches). Only relay or triac based electronic thermostats should be used with slow closing valves. When wired as shown, the slow closing valve will operate properly with the following notations:
1. The valve will remain open during a unit lockout.
2. The valve will draw approximately 25 to 35 VA through the “Y” signal of the thermostat.
a50-7467tf
AQUAZONE CONTROL (Complete C Control Shown)
Fig. 30 — Typical Aquazone Control Board
Jumper Locations
ACCESSORY CONNECTIONS — Terminal labeled A on the control is provided to control accessory devices such as water valves, electronic air cleaners, humidifiers, etc. This signal operates with the compressor terminal. See Fig. 31. Refer to the specific unit wiring schematic for details.
NOTE: The A terminal should only be used with 24-v signals — not line voltage signals.
Terminal Strip
C
Typical
24 VAC
A
Water
Valve
IMPORTANT: Connecting a water solenoid valve can overheat the anticipators of electromechanical thermo­stats. Only use relay based electronic thermostats.
C
1Y
a50-8441
1
2
HEATER SWITCH
1Y
C
THERMOSTAT
AMV
3
TACO VALVE
Fig. 32 — AMV Valve Wiring
Fig. 31 — Typical Aquazone Accessory Wiring
a50-8442
Fig. 33 — Taco SBV Valve Wiring
30
Page 31
OPTIONAL WALL-MOUNTED THERMOSTAT — The 50PEC water source heat pump units are built with standard in­ternal thermostats in either manual changeover (MCO) or auto­matic changeover (ACO) configuration. Refer to Fig. 17-20.
When desired, the unit can be furnished with a 24-v control circuit which is field wired to a Carrier-supplied accessory re­mote thermostat. Most heat pump thermostats can be used with the controller. Use a thermostat with Y, G, O and W outputs. Refer to unit wiring diagrams in Fig. 21 and 22 and Aquazone Controls, Operation, and Troubleshooting Instructions for addi­tional information.
Vendor installation instructions and additional installation information is shipped with each thermostat.
NOTE: Low-voltage wiring between the unit and the wall ther­mostat must comply with all applicable electrical codes (i.e., NEC and local codes), and be completed before the unit is installed.
Table 3 lists recommended wire sizes and lengths to install the thermostat. The total resistance of low-voltage wiring must not exceed 1 ohm. Any resistance in excess of 1 ohm may cause the control to malfunction because of high voltage drop.
Table 3 — Recommended Thermostat Wire Sizes
WIRE SIZE MAX WIRE LENGTH*
18-Gage 75 ft 16-Gage 125 ft 14-Gage 200 ft
*Length = Physical distance from thermostat to unit.
OPTIONAL PREMIERLINK™ CONTROLLER — This di­rect digital controller (DDC) allows the water source heat pump to be incorporated into a Carrier Comfort Network (CCN) system installation. PremierLink control is factory­installed with the Complete C controller, or field-installed with the Deluxe D control option. Refer to Fig. 23 and 24.
WSHP OPEN WIRING — The WSHP Open controller will be factory wired to the Complete C or Deluxe D control board, however, the system wiring will need to be completed utilizing WSHP Open controller wiring diagrams and the Third Party Integration (TPI) Guide. Factory installation includes harness, LWT (leaving water temperature), supply air, and condensate sensor.
WARNING
Disconnect all power to the unit before performing mainte­nance or service. Unit may automatically start if power is not disconnected. Failure to follow this warning could cause personal injury, death, and/or equipment damage.
Wiring Sensors to Inputs WSHP Open controller’s inputs. See Table 4.
All field control wiring that connects to the WSHP Open con­troller must be routed through the raceway built into the corner post. The raceway provides the UL required clearance between high and low-voltage wiring.
1. Pass control wires through the hole provided in the corner post.
2. Feed the wires through the raceway to the WSHP Open controller.
3. Connect the wires to the removable Phoenix connectors.
4. Reconnect the connectors to the board.
— Sensors can be wired to the
Field-Supplied Sensor Hardware
— The WSHP Open con­troller is configurable with the following field-supplied sen­sors. See Table 4.
Table 4 — Field-Supplied Sensors for
WSHP Open Controller
SENSOR NOTES
Space Temperature Sensor
Indoor Air Quality Sensor
Space Relative Humidity
NOTE: BACview6 Handheld or Virtual BACview can be used as the user interface.
(SPT)
Outdoor Air
Temperature Sensor
(Separate Sensor)
Sensor
Field Installed (Must be used with
WSHP Open controller.)
Network Sensor
Required only for demand
control ventilation.
Separate Sensor
For specific details about sensors, refer to the literature sup-
plied with the sensor. Wiring a SPT Sensor
— A WSHP Open controller is connect­ed to a wall-mounted space temperature (SPT) sensor to moni­tor room temperature using a Molex plug.
The WSHP Open system offers the following SPT sensors.
See Table 5.
Table 5 — SPT Sensors
SENSOR
SPT
Standard
®
SPT Plus SPPL
SPT Pro SPP
SPT Pro
Plus
*The SPT Pro Plus fan speed adjustment has no effect in this
application.
PA RT
NUMBER
SPS
SPPF
FEATURES
• Local access port
• No operator control
• Slide potentiometer to adjust set point
• Manual on button to override schedule
• LED to show occupied status
• Local access port
•LCD display
• Manual on button to override schedule
• Warmer and cooler buttons to adjust set point
• Info button to cycle through zone and outside air temperatures, set points, and local override time
• Local access port
• LCD display
• Manual on button to override schedule
• Warmer and cooler buttons to adjust set point
• Info button to cycle through zone and outside air temperatures, set points, and local override time
• Local access port
• Fan speed*
Wire SPT sensors to the WSHP Open controller’s Rnet port. An Rnetbus can consist of any of the following combinations of devices wired in a daisy-chain configuration:
• 1 SPT Plus, SPT Pro, or SPT Pro Plus sensor
• 1 to 4 SPT Standard sensors
• 1 to 4 SPT Standard sensors and 1 SPT Plus, SPT Pro, or
SPT Pro Plus sensor
• Any of the above combinations, plus up to 2 BACview
6
Handheld but no more than 6 total devices NOTE: If the Rnetbus has multiple SPT Standard sensors, each
sensor must be given a unique address on the Rnetbus. See the Carrier Open Sensor Installation Guide.
Use the specified type of wire and cable for maximum signal integrity. See Table 6.
31
Page 32
Table 6 — Rnet Wiring Specifications
RNET WIRING SPECIFICATIONS
Description
Conductor 18 AWG
Maximum Length 500 ft
Recommended Coloring
UL Temperature 32 to 167 F
Volt ag e 300-vac, power limited
Listing UL: NEC CL2P, or better
LEGEND
AWG — American Wire Gage CMP — Communications Plenum Cable NEC — National Electrical Code UL Underwriters Laboratories
4 conductor, unshielded, CMP,
plenum rated cable
Wiring: black, white, green, red
Jacket: white
To wire the SPT sensor to the controller:
1. Partially cut , then bend and pull off the outer jacket of the Rnet cable(s), being careful not to nick the inner insulation.
2. Strip about
1
/4 in. of the inner insulation from each wire.
See Fig. 34.
OUTER JACKET
a50-8443
.25 IN.
INNER INSULATION
Fig. 34 — Rnet Cable Wire
3. Wire each terminal on the sensor to the same terminal on the controller. See Fig. 25-29. Table 7 shows the recom­mended Rnet wiring scheme.
Table 7 — Rnet Wiring
WIRE TERMINAL
Red +12-v
Black .Rnet
White Rnet+
Green Gnd
NOTE: The wire should be connected to the terminal shown.
Wiring a Supply Air Temperature (SAT) Sensor — The SAT sensor is required for reheat applications.
If the cable used to wire the SAT sensor to the controller will be less than 100 ft, an unshielded 22 AWG (American Wire Gage) cable should be used. If the cable will be greater than 100 ft, a shield 22 AWG cable should be used. The cable should have a maximum length of 500 ft.
To wire the SAT sensor to the controller:
1. Wire the sensor to the controller. See Fig. 25-29.
2. Verify that the Enable SAT jumper is on.
3. Verify that the Enable SAT and Remote jumper is in the left position.
Wiring an Indoor Air Quality (IAQ) Sensor sensor monitors CO
levels. The WSHP Open controller uses
2
— An IAQ
this information to adjust the outside-air dampers to provide proper ventilation. An IAQ sensor can be wall-mounted or mounted in a return air duct. (Duct installation requires an aspi­rator box assembly.)
The sensor has a range of 0 to 2000 ppm and a linear 4 to
20 mA output. This is converted to 1 to 5 vdc by a 250-ohm,
1
/4 watt, 2% tolerance resistor connected across the zone con-
troller’s IAQ input terminals. NOTE: Do not use a relative humidity sensor and CO
sensor
2
on the same zone controller if both sensors are powered off the board. If sensors are externally powered, both sensors may be used on the same zone controller.
If the cable used to wire the IAQ sensor to the controller will be less than 100 ft, an unshielded 22 AWG (American Wire Gage) cable should be used. If the cable will be greater than 100 ft, a shield 22 AWG cable should be used. The cable should have a maximum length of 500 ft.
To wire the IAQ sensor to the controller:
1. Wire the sensor to the controller. See Fig. 25-29.
2. Install a field-supplied 250-ohm,
1
/4 watt, 2% tolerance resistor across the controller’s RH/IAQ and Gnd terminals.
3. Verify the the RH/IAQ jumper is set to 0 to 5-vdc.
Wiring a Relative Humidity (RH) Sensor
— The RH sensor is used for zone humidity control (dehumidification) if the WSHP unit has a dehumidification device. If not, the sensor only monitors humidity.
NOTE: Do not use a relative humidity sensor and CO on the same zone controller if both sensors are powered off the board. If sensors are externally powered, both sensors may be used on the same zone controller.
If the cable used to wire the RH sensor to the controller will be less than 100 ft, an unshielded 22 AWG (American Wire Gage) cable should be used. If the cable will be greater than 100 ft, a shield 22 AWG cable should be used. The cable should have a maximum length of 500 ft.
To wire the RH sensor to the controller:
1. Strip the outer jacket from the cable for at least 4 inches.
2. Strip
1
/4 in. of insulation from each wire.
3. Wire the sensor to the controller.
Step 6 — Install Supply and Return Piping
CAUTION
To ensure proper functioning of unit and system, be sure to connect entering water to upper pipe on right-hand units. On left-hand units, connect entering water to lower pipe. Failure to do so could result in equipment damage.
SUPPLY AND RETURN HOSES — Optional pressure-rated hose assemblies are available for use with units. Use the fol­lowing guidelines when installing supply and return hose assemblies.
1. Install supply and return hoses fitted with swivel-joint fittings at one end to prevent the hose from twisting.
2. Use male adapters to secure the hose assembly to the unit and the riser.
3. Do not allow the hose to twist during installation. Twist­ing may damage the hose wall or the rubber compound.
4. Use pipe joint compound sparingly on the fitting adapt­ers’ male pipe threads.
5. Prevent sealant from reaching the joint’s flared surfaces.
6. Do not use pipe joint compound when Teflon* thread tape is pre-applied to hose assemblies or when flared-end connections are used.
7. Maximum torque that may be applied to brass fittings is 30 ft-lb. When a torque wrench is not used, tighten brass fittings finger-tight plus one quarter turn.
8. Tighten steel fittings as necessary.
9. Use shut-off/balancing valves, flow indicators, and drain tees in the supply runout and return at each floor to aid in loop balancing and servicing.
SUPPLY AND RETURN PIPING — System piping MUST comply with all applicable codes.
1. Install a drain valve at the base of each supply and return riser to enable system flushing at start-up and during rou­tine servicing.
*Teflon is a trademark of E. I. du Pont de Nemours and Company.
32
sensor
2
Page 33
2. Install shut-off/balancing valves and unions at each unit to allow unit removal for servicing.
NOTE: If flex hoses are used, unions are not necessary.
3. Install strainers at the inlet of each system circulating pump.
PRE-START-UP
System Cleaning and Flushing —
flushing the unit and system is the single most important step to ensure proper start-up and continued efficient operation of the system.
Cleaning and
IMPORTANT: Since loop temperatures are normally between 60 and 90 F, pipe sweating and heat loss do not occur at normal ambient temperature conditions. Insulation must be installed on loop water piping on those sections that run through unheated areas or are located outside the building. If loop temperatures are expected below the ambient dew point, the optional internal insulation (extended range) package must be ordered.
CAUTION
DO NOT bend or kink supply lines or hoses. Damage to unit may result.
4. Before making the final water connections, flush the sys­tem as described in the Pre-Start-Up section of this manual. After flushing the system, connect piping and hoses to the proper supply, return and condensate connec­tions of the unit.
NOTE: When necessary, use adapters to connect hoses.
5. Install any other system components, as required, follow­ing manufacturer’s instructions.
6. Reinstall the front cabinet by carefully lowering the front cabinet over the chassis onto the backplate.
Step 7 — Install Condensate Piping — Connect
the unit condensate drain to the building condensate drain with a flexible, nonpressure-rated Avoid kinks in this hose to ensure an unobstructed flow of con­densate from the unit to the drain.
The horizontal run of the condensate hose is usually too short to pose any drainage problems, however, the horizontal run of condensate line should be pitched at least 1 in. for every 10 ft of run (in the direction of flow). Avoid low points and un­pitched piping since dirt collects in these areas and may cause stoppage and overflow.
Field installation of a trap or vent is not required unless specified by local codes. The 50PEC units are designed in a blow-thru configuration. The condensate drain pan is located on the outlet side of the blower so that the pressure in the drain pan is higher than the atmospheric pressure.
5
/8-in. (16 mm) ID plastic hose.
WARNING
To prevent injury or death due to electrical shock or contact with moving parts, open unit disconnect before servicing unit.
Follow the instructions below to properly clean and flush
the system:
CAUTION
DO NOT FLUSH SYSTEM THROUGH THE UNIT!
1. Verify that electrical power to the units is disconnected, and that the circulation pump is deenergized.
2. Connect the supply hose directly to the return riser valve. Use a single length of flexible hose, as shown in Fig. 35.
NOTE: If the length of hose is too short (i.e., the resulting con­nection would exceed the minimum bend radius of the hose), substitute two lengths of flexible hose joined together with a field-supplied, standard NPT coupling and the flare-fitting-to­pipe adapters provided with the hose kit (Fig. 35).
3. Open all air vents. Fill the system with water. Do not al­low system to overflow. Bleed all air from the system. Check the system for leaks and repair appropriately.
4. Check and adjust the water and air level in the expansion tank.
5. Verify all strainers are in place. Start the pumps, and sys­tematically check each vent to ensure all air is bled from the system.
6. Verify make-up water is available. Adjust make-up water appropriately to replace the air that was bled from the system. Pressure test and inspect the system for leaks and make any necessary repairs. Check and adjust the water and air level in the expansion tank.
7. Open a drain at the lowest point in the system. Adjust the make-up water replacement rate to equal the rate of bleed. Continue to bleed the system until the water appears clean or for at least three hours, whichever is longest; then, completely drain the system.
Supply Valve
Floor Line
1/2 Flexible Hose
Brass Adapter (1/2 MPT x 1/2 Male Flare)
Return Valve
NOTE: Use standard coupling (field-supplied) and hose adapters to join 2 hoses.
Fig. 35 — Temporary Connection for Flushing System Piping
33
Page 34
8. Refill the system with clean, chemically treated water. Since water varies for each locality, contact a local water treatment company for the correct treatment chemicals to use in the area. Set the boiler to raise the loop temperature to approximately 85 F.
.
CAUTION
To avoid possible damage to piping systems constructed of plastic piping DO NOT allow loop temperature to exceed 110 F.
Circulate the solution for a minimum of 8 to 24 hours. At the end of this period, shut off the circulating pump and drain the solution. Repeat system cleaning as necessary.
9. When the cleaning process is complete, remove the short­circuited hoses. Connect the hoses to the proper supply and return connections on each unit. Refill the system and bleed off all air.
10. Test the system pH with litmus paper. The system water should be slightly alkaline (pH 7.0 to 8.5). Add chemi­cals, as appropriate, to maintain acidity levels.
3. System Water pH: Verify system water is slightly alkaline (pH = 7.5 to 8.5). Proper pH promotes the longevity of the hoses and heat exchangers. See Table 9.
4. Closed-Type Cooling Tower (Open Tower with Heat Ex­changer): Check equipment for proper temperature set points and operation.
5. Balanced Water Flow Rate to Heat Pump: Record the inlet and outlet water temperatures as each heat pump unit is started. This check will eliminate nuisance unit tripouts resulting from water velocities that are either too low or too high; it can also prevent erosive water flow rates.
6. Standby Pump: Verify the standby pump is properly in­stalled and in operating condition.
7. System Control: To ensure no catastrophic system fail­ures occur, verify system controls are functioning and the sequencing is correct.
8. Freeze Protection for Water Systems: Verify freeze protection is provided for the outdoor portion of the loop water system. Inadequate freeze protection leads to expensive repairs.
CAUTION
DO NOT use “Stop-Leak” or any similar chemical agent in this system. Addition of these chemicals to the loop water will foul the system and will inhibit unit operation.
11. When the system is successfully cleaned, flushed, refilled and bled, check the main system panels, safety cutouts and alarms. Set the controls to properly maintain loop temperatures.
System Checkout — When the installation is complete
and the system is cleaned and flushed, follow the system checkout procedure outlined below.
1. Voltage: Ensure voltage is within the utilization range specifications of the unit compressor and fan motor.
2. System Water Temperature: Ensure temperature is within an acceptable range shown in Table 8. (When conducting this check, also verify proper heating and cooling set points.)
Table 8 — Air and Water Limits
50PEC UNIT COOLING (F) HEATING (F)
Min Ambient Air 50 50 Rated Ambient Air 80 70 Max Ambient Air 100 85 Min Entering Air 50 50 Rated Entering Air, dry bulb/wet bulb 80/67 70 Max Entering Air, dry bulb/wet bulb 100/83 80 Min Entering Water 30 20 Normal Entering Water 85 70 Max Entering Water 110 90
NOTES:
1. Minimum air and water conditions can only be used at nominal flow rates.
2. 50PEC units may have up to two values at maximum or minimum with all other parameters at normal conditions.
3. Operating limits shown are for start-up, not continuous operation. It is assumed that such a start-up is for the purpose of bringing the space to desired occupancy temperature.
CAUTION
To avoid equipment damage, DO NOT leave system filled in a building without heat during the winter unless anti­freeze is added to system water. Condenser coils never fully drain by themselves and will freeze unless winterized with antifreeze.
9. System Water Loop: Verify all air is bled from the sys­tem. Air in the system impedes unit operation and causes corrosion in the system piping.
10. Unit Filters: To avoid system damage and to provide maximum performance, ensure the unit filter is clean.
11. Unit Fans: Manually rotate fans to assure free rotation. Ensure fans are properly secured to the fan shaft. Do not oil fan motors on start-up since they are lubricated at the factory.
12. System Control Center: To ensure control of the tempera­ture set points for operation of the system’s heat rejector and boiler, examine the system control and alarm panel for proper installation and operation.
34
Page 35
Table 9 — Water Quality Guidelines
CONDITION
Scaling Potential — Primary Measurement
Above the given limits, scaling is likely to occur. Scaling indexes should be calculated using the limits below.
pH/Calcium Hardness Method
Index Limits for Probable Scaling Situations (Operation outside these limits is not recommended.)
Scaling indexes should be calculated at 150 F for direct use and HWG applications, and at 90 F for indirect HX use. A monitoring plan should be implemented.
Ryznar Stability Index
Langelier Saturation Index
Iron Fouling
Iron Fe2+ (Ferrous) (Bacterial Iron Potential)
Iron Fouling
Corrosion Prevention††
pH
Hydrogen Sulfide (H2S)
Ammonia Ion as Hydroxide, Chloride, Nitrate and Sulfate Compounds
Maximum Chloride Levels Maximum allowable at maximum water temperature.
Erosion and Clogging
Particulate Size and Erosion
Brackish
LEGEND
HWG — Hot Water Generator HX Heat Exchanger N/A — Design Limits Not Applicable Considering Recirculating
NR Application Not Recommended SS Stainless Steel
*Heat exchanger materials considered are copper, cupronickel, 304 SS
(stainless steel), 316 SS, titanium.
†Closed recirculating system is identified by a closed pressurized piping
system.
**Recirculating open wells should obser ve the open recirculating design
considerations.
Potable Water
HX
MATERIAL*
All N/A pH < 7.5 and Ca Hardness, <100 ppm
All N/A
All N/A
All N/A
All N/A
All
All N/A
All N/A
Copper N/A
Cupronickel N/A <150 ppm NR NR
304 SS N/A <400 ppm <250 ppm <150 ppm 316 SS N/A <1000 ppm <550 ppm <375 ppm
Titanium N/A >1000 ppm >550 ppm >375 ppm
All
All N/A
CLOSED
RECIRCULATING†
Monitor/treat as needed.
<10 ppm of particles and a maximum velocity of 6 fps.
6 - 8.5
Filtered for maximum
800 micron size.
OPEN LOOP AND RECIRCULATING WELL**
6.0 - 7.5
If >7.5 minimize steel pipe use.
–0.5 to +0.5
Based upon 150 F HWG and direct well, 85 F indirect well HX.
If Fe2+ (ferrous) >0.2 ppm with pH 6 - 8, O2<5 ppm check for iron bacteria.
Minimize steel pipe below 7 and no open tanks with pH <8.
At H2S>0.2 ppm, avoid use of copper and cupronickel piping of HXs.
Copper alloy (bronze or brass) cast components are okay to <0.5 ppm.
50 F (10 C) 75 F (24 C) 100 F (38 C)
<20 ppm NR NR
<10 ppm (<1 ppm “sandfree for reinjection) of par ticles and a maximum velocity of 6 fps. Filtered for maximum 800 micron size. Any particulate that is not removed can potentially clog components.
Use cupronickel heat exchanger when concentrations of calcium or sodium chloride are greater than 125 ppm are present. (Seawater is approximately 25,000 ppm.)
††If the concentration of these corrosives exceeds the maximum allow-
able level, then the potential for serious corrosion problems exists. Sulfides in the water quickly oxidize when exposed to air, requiring that no agitation occur as the sample is taken. Unless tested immediately at the site, the sample will require stabilization with a few drops of one Molar zinc acetate solution, allowing accurate sulfide determination up to 24 hours after sampling. A low pH and high alkalinity cause system problems, even when both values are within ranges shown. The term pH refers to the acidity, basicity, or neutrality of the water supply. Below 7.0, the water is considered to be acidic. Above 7.0, water is considered to be basic. Neutral water contains a pH of 7.0. To convert ppm to grains per gallon, divide by 17. Hardness in mg/l is equivalent to ppm.
If <–0.5 minimize steel pipe use.
<0.2 ppm (Ferrous)
<0.5 ppm of Oxygen
Above this level deposition will occur.
6 - 8.5
<0.5 ppm
Rotten egg smell appears at 0.5 ppm level.
<0.5 ppm
35
Page 36
FIELD SELECTABLE INPUTS
Jumpers and DIP (dual in-line package) switches on the control board are used to customize unit operation and can be configured in the field.
IMPORTANT: Jumpers and DIP switches should only be clipped when power to control board has been turned off.
Complete C Control Jumper Settings (See Fig. 17, 18, and 21)
WATER COIL FREEZE PROTECTION (FP1) LIMIT SETTING — Select jumper 3, (JW3-FP1 Low Temp) to choose FP1 temperature limit of 10 F or 30 F. To select 30 F as the temperature limit, DO NOT clip the jumper. To select 10 F as the limit, clip the jumper.
ALARM RELAY SETTING — Select jumper 1 (JW1) for connecting alarm relay terminal (AL2) to 24-vac (R) or to re­main as a dry contact (no connection). To connect AL2 to R, do not clip the jumper. To set as dry contact, clip the jumper.
Complete C Control DIP Switches — The Com-
plete C control has one DIP switch block with five switches. See Fig. 17, 18, and 21.
PERFORMANCE MONITOR (PM) — DIP switch 1 will enable or disable this feature. To enable the PM, set the switch to ON. To disable the PM, set the switch to OFF.
STAGE 2 — DIP switch 2 will enable or disable compressor delay. Set DIP switch to OFF for Stage 2 in which the compres­sor will have a 3-second delay before energizing.
SWITCH 3 AND SWITCH 4 — Not used. FREEZE PROTECTION (FP1) — DIP switch 5 is used to
initiate one or 3 tries for the FP1 fault. If there is water freeze protection for the water coil then DIP switch 5 can be set to lock out on the FP1 fault after one try. ON = One try. OFF = 3 tries.
Deluxe D Control Jumper Settings (See Fig. 19, 20, and 22)
WATER COIL FREEZE PROTECTION (FP1) LIMIT SETTING — Select jumper 3, (JW3-FP1 Low Temp) to choose FP1 temperature limit of 10 F or 30 F. To select 30 F as the temperature limit, DO NOT clip the jumper. To select 10 F as the limit, clip the jumper.
ALARM RELAY SETTING — Select jumper 4 (JW4-AL2 Dry) for connecting alarm relay terminal (AL2) to 24-vac (R) or to remain as a dry contact (no connection). To connect AL2 to R, do not clip the jumper. To set as dry contact, clip the jumper.
LOW PRESSURE SETTING — The Deluxe D control can be configured for low pressure setting (LP). Select jumper 1 (JW1-LP Norm Open) for choosing between low pressure in­put normally opened or closed. To configure for normally closed operation, do not clip the jumper. To configure for nor­mally open operation, clip the jumper.
Deluxe D Control DIP Switches — The Deluxe D
control has 2 DIP switch blocks. Each DIP switch block has 8 switches and is labeled either S1 or S2 on the circuit board. See Fig. 19, 20, and 22.
DIP SWITCH BLOCK 1 (S1) — This set of switches offers the following options for Deluxe D control configuration:
Performance Monitor (PM) able performance monitor. To enable the PM, set the switch to ON. To disable the PM, set the switch to OFF.
Compressor Relay Staging Operation able or disable compressor relay staging operation. The
— Set switch 1 to enable or dis-
— Switch 2 will en-
compressor relay can be set to turn on with Stage 1 or Stage 2 call from the thermostat. This setting is used with dual stage units (units with 2 compressors and 2 Deluxe D controls) or in master/slave applications. In master/slave applications, each compressor and fan will stage according to its switch 2 setting. If switch is set to Stage 2, the compressor will have a 3-second delay before energizing during stage 2 demand.
NOTE: If DIP switch is set for Stage 2, the alarm relay will not cycle during Test mode.
Heating/Cooling Thermostat Type
— Switch 3 provides selec­tion of thermostat type. Heat pump or heat/cool thermostats can be selected. Select OFF for heat/cool thermostats. When in heat/cool mode, Y1 is used for Cooling Stage 1, Y2 is used for Cooling Stage 2, W1 is used for Heating Stage 1 and O/W2 is used for Heating Stage 2. Select ON for heat pump applica­tions. In heat pump mode, Y1 used is for Compressor Stage 1, Y2 is used for Compressor Stage 2, W1 is used for Heating Stage 3 or emergency heat, and O/W2 is used for RV (heating or cooling) depending upon switch 4 setting.
O/B Thermostat Type
— Switch 4 provides selection for heat pump O/B thermostats. O is cooling output. B is heating out­put. Select ON for heat pumps with O output. Select OFF for heat pumps with B output.
Dehumidification Fan Mode
— Switch 5 provides selection of normal or dehumidification fan mode. Select OFF for dehu­midification mode. The fan speed relay will remain OFF dur­ing Cooling Stage 2. Select ON for normal mode. The fan speed relay will turn on during Cooling Stage 2 in normal mode.
Switch 6 Boilerless Operation
— Not used.
— Switch 7 provides selection of boiler­less operation and works in conjunction with switch 8. In boil­erless operation mode, only the compressor is used for heating when FP1 is above the boilerless changeover temperature set by switch 8 below. Select ON for normal operation or select OFF for boilerless operation.
Boilerless Changeover Temperature
— Switch 8 on S1 pro­vides selection of boilerless changeover temperature set point. Select OFF for set point of 50 F or select ON for set point of 40 F.
If switch 8 is set for 50 F, then the compressor will be used for heating as long as the FP1 is above 50 F. The compressor will not be used for heating when the FP1 is below 50 F and the compressor will operate in emergency heat mode, staging on EH1 and EH2 to provide heat. If a thermal switch is being used instead of the FP1 thermistor, only the compressor will be used for heating mode when the FP1 terminals are closed. If the FP1 terminals are open, the compressor is not used and the control goes into emergency heat mode.
DIP SWITCH BLOCK 2 (S2) — The following set of DIP switches is used to configure accessory relay options.
Switches 1 to 3
— These DIP switches provide selection of Accessory 1 relay options. See Table 10 for DIP switch combinations.
Table 10 — DIP Switch Block S2 —
Accessory 1 Relay Options
ACCESSORY 1
RELAY OPTIONS
Digital NSB Off On On
Water Valve — Slow Opening On Off On
LEGEND
NSB — Night Setback
NOTE: All other DIP switch combinations are invalid.
DIP SWITCH POSITION
123
Switches 4 to 6 — These DIP switches provide selection of Accessory 2 relay options. See Table 11 for DIP switch combinations.
36
Page 37
Table 11 — DIP Switch Block S2 —
Accessory 2 Relay Options
ACCESSORY 2
RELAY OPTIONS
Digital NSB Off On On
Water Valve — Slow Opening On Off On
LEGEND
NSB — Night Setback
NOTE: All other switch combinations are invalid.
DIP SWITCH POSITION 456
Auto Dehumidification Mode or High Fan Mode — Switch 7 provides selection of auto dehumidification fan mode or high fan mode. In auto dehumidification fan mode, the fan speed relay will remain off during Cooling Stage 2 if terminal H is active. In high fan mode, the fan enable and fan speed relays will turn on when terminal H is active. Set the switch to ON for auto dehumidification fan mode or to OFF for high fan mode.
Switch 8
— Not used.
Deluxe D Control Accessory Relay Configura­tions —
ble for Deluxe D control only: CYCLE WITH COMPRESSOR — In this configuration, the
relay will be ON any time the compressor relay is on. DIGITAL NIGHT SETBACK (NSB) — In this configura-
tion, the relay will be ON if the NSB input is connected to ground C.
NOTE: If there are no relays configured for digital NSB, then the NSB and OVR (override) inputs are automatically config­ured for mechanical operation.
MECHANICAL NIGHT SETBACK — When NSB input is connected to ground C, all thermostat inputs are ignored. A thermostat setback heating call will then be connected to the OVR input. If OVR input becomes active, then the Deluxe D control will enter night low limit (NLL) staged heating mode. The NLL staged heating mode will then provide heating during the NSB period.
WATER VALVE (SLOW OPENING) — If relay is config­ured for water valve (slow opening), the relay will start 60 sec­onds prior to starting compressor relay.
The following accessory relay settings are applica-
CAUTION
To avoid equipment damage, DO NOT leave system filled in a building without heat during the winter unless anti­freeze is added to system water. Condenser coils never fully drain by themselves and will freeze unless winterized with antifreeze.
START-UP
Use the procedure outlined below to initiate proper unit
start-up:
IMPORTANT: This equipment is designed for indoor installation ONLY.
WARNING
When the disconnect switch is closed, high voltage is present in some areas of the electrical panel. Exercise cau­tion when working with the energized equipment.
1. Adjust all valves to the full open position and turn on the line power to all heat pump units.
2. Operate each unit in the Cooling mode first. Room temperature should be in the normal range
(i.e., approximately 50 to 80 F dry bulb). Loop water tem­perature entering the heat pumps should be at least 40 F but not in excess of 110 F. Refer to Table 8 for more spe­cific information on the operating parameters of units.
IMPORTANT: Three factors determine the operating limits of a unit: (1) return-air temperature, (2) water temperature and (3) ambient temperature. Whenever any one of these factors is at a minimum or maximum level, the other two factors must be at normal levels to ensure proper unit oper­ation. Flow rates must be at nominal ARI (Air Condition­ing and Refrigeration Institute)/ISO (International Organization for Standardization)/ ASHRAE (American Society of Heating, Refrigerating and Air Conditioning Engineers) 13256-1 standards.
Unit Start-Up/Cooling
1. Turn the unit thermostat to the cooling position and turn the fan speed switch to “HI.” If the unit has an optional MCO thermostat, set the selector switch to Cool. Both the fan and compressor should run.
2. Check for cool air delivery at unit grille 15 minutes after the unit has begun operating. List the identification num­ber of any machines that do not function at this time.
3. Check the elevation and cleanliness of the condensate lines; any dripping could be a sign of a blocked line.
4. Select low fan speed. Airflow should decrease and com­pressor should operate.
5. Slowly turn thermostat toward warmer position. Both fan and compressor should shut off when thermostat set point equals room temperature. Room temperature must be below 90 F for unit to shut off.
6. Operate each heat pump in the heating cycle immediately after checking cooling cycle operation. A time delay will prevent the compressor from re-starting for approximate­ly 5 minutes.
Operating Limits
ENVIRONMENT — This equipment is designed for indoor installation ONLY.
POWER SUPPLY — A voltage variation of ± 10% of name­plate utilization voltage is acceptable.
50PEC UNIT STARTING CONDITIONS — The 50PEC units will start and operate at an ambient temperature of 50 F with entering-air temperature at 50 F, entering water at 60 F, and with both air and water at the flow rates used in the ARI/ISO/ASHRAE Standard 13256-1 rating test, for initial start-up in winter.
IMPORTANT: These operating limits are not normal or continuous operating conditions. It is assumed that such a start-up is for the purpose of bringing the building space up to occupancy temperature.
Unit Start-Up/Heating
1. Adjust the unit thermostat to the warmest setting and turn the fan speed switch to “HI.” If the unit has an optional MCO thermostat, set the selector switch to Heat. The blower should start immediately and after the time delay is complete, the compressor will start.
2. Once the unit has begun to run, check for warm air delivery at the unit grille. Again, the installing contractor must list the serial number of any machine that does not function.
3. Log the unit operating conditions at initial start-up for each unit to establish a permanent operating record.
4. Select low fan speed. Airflow should decrease and com­pressor should continue to operate.
37
Page 38
5. Slowly turn thermostat toward cooler position. Both fan and compressor should shut off when thermostat set point equals room temperature. Room temperature must be above 65 F for unit to shut off.
Unit Start-Up with WSHP Open Controls —
The WSHP Open is a multi-protocol (default BACnet*) con­troller with extensive features, flexible options and powerful capabilities. The unit comes from the factory pre-programmed and needs minimal set up to function in a BAS (Building Automation System) system or provide additional capabilities to Carrier's WSHP product line. Most settings on the controller have factory defaults set for ease of installation. There are a few settings that must be configured in the field and several settings that can be adjusted if required by unique job condi­tions. Refer to Appendix A — WSHP Open Screen Configura­tion. In order to configure the unit, a BACview required. See Fig. 36.
NOTE: If the WSHP Open control has lost its programming, all display pixels will be displayed on the SPT sensor. See the WSHP Third Party Integration Guide.
When the unit is OFF, the SPT sensor will indicate OFF. When power is applied, the SPT sensor will indicate tempera­ture in the space at 78 F.
To start-up a unit with WSHP Open controls:
1. To plug in the BACview
6
handheld display into a SPT sensor, point the two ears on the connector up and tilt the bottom of the plug toward you. Insert the plug up into the SPT sensor while pushing the bottom of the plug away from you.
2. BACview
6
should respond with "Establishing Connec­tion." The Home screen will then appear on the display showing operating mode and space temperature. Press any button to continue.
See Appendix A — WSHP Open Screen Configuration for the hierarchal structure of the WSHP Open controller. All functions of the controller can be set from the Home screen.
3. When the Login is requested, type 1111 and push the OK softkey. The Logout will then be displayed to indicate the password was accepted.
4. To set the Clock if it is not already displayed:
a. Select System Settings from the Home screen, then
press Clockset.
b. Scroll to hour, minute and second using the arrow
keys. Use the number keypad to set actual time.
6
display is
c. Scroll to day, month and year using arrow keys.
Use number keypad to set date.
5. To set Daylight Savings Time (DST): a. Push the DST softkey. The display will indicate
02:00:060 which is equal to 2:00AM.
b. To program the beginning and end dates, scroll
down to the beginning month and press the enter key. The softkeys (INCR and DECR) will activate to increment the month in either direction, Jan, Feb, March, etc.
c. Use number keys to select the day of month and
year.
d. Push the OK softkey to finalize the data.
6. To view configuration settings: a. Select the Config softkey. b. Select the Service Config softkey. Scroll through
the factory settings by using the up and down arrow keys. See below for factory settings.
Only the following settings will need to be checked.
• # of Fan Speeds — This should be set to "1" for units with PSC motors and set to "3" for units with ECM motors.
• Compressor Stages — This should be set to "1."
• Factory Dehumidification Reheat Coil — This should be set to "none" unless the modulating hot water reheat option is supplied in the unit, then set to "installed."
• The condenser water limit needs to be verified depending on design parameters and application, whether geothermal or boiler/tower.
7. To view unit configuration settings: a. Select the Unit Configuration softkey, then select
Unit.
b. Scroll through the unit settings by using the up and
down arrow keys. Unit settings include:
• Fan Mode: Default Continuous
• Fan Delay:
• Minimum SAT Cooling: Default 50 F
• Maximum SAT Heating: Default 110 F
• Filter Service Alarm: Must be set from 0 to 9999 hr
8. To set local schedules: a. Select the Schedule softkey from the Configuration
screen, then press enter.
a50-8444
Fig. 36 — BACview6 Display Interface
*Sponsored by ASHRAE (American Society of Heating, Refrigerat­ing and Air Conditioning Engineers).
38
Page 39
b. Select Weekly, then press enter (7 schedules
available). c. Select day and press enter. d. Press enter again and select ADD or DEL (DECR
or INCR) set schedule. e. Enter ON/OFF time, then press continue. f. Press OK to apply and save to a particular day of
the week. g. Continue to add the same or different schedule spe-
cific days of the week.
To add exceptions to the schedule:
i. Press Add softkey.
ii. Select exception type from following:
• Date
• Date Range
• Week-N-Day
• Calender Reference
9. Go back to Home Screen.
10. Remove BACview
6
cable from SPT sensor by reversing
the process in Step 1.
11. Perform system test.
Flow Regulation — Flow regulation can be accom-
plished by two methods. Most water control valves have a built-in flow adjustment valve. Determine the flow rate by measuring the pressure drop through the unit heat exchanger. See Table 12. Adjust the water control valve until a flow of 1.5 to 2 gpm per ton cooling is achieved. Since the pressure constantly varies, two pressure gages may be needed.
An alternative method for regulating flow is to install a flow control device. These devices are typically an orifice of plastic material mounted on the outlet of the water control valve, designed to allow a specified flow rate. Occasionally these valves produce a velocity noise that can be reduced by
applying some back pressure. To accomplish this, slightly close the leaving isolation valve of the water regulating device.
CAUTION
DO NOT use “Stop Leak” or any similar chemical agent in this system. Addition of these chemicals to the loop water will foul the system and inhibit unit operation.
Antifreeze — In areas where entering loop temperatures
drop below 40 F or where piping will be routed through areas subject to freezing, antifreeze is needed.
Alcohols and glycols are commonly used as antifreeze agents. Freeze protection should be maintained to 15 F below the lowest expected entering loop temperature. For example, if the lowest expected entering loop temperature is 30 F, the leaving loop temperature would be 22 to 25 F. Therefore, the freeze pro­tection should be at 15 F (30 F –15 F) = 15 F.
IMPORTANT: All alcohols should be pre-mixed and pumped from a reservoir outside of the building or intro­duced under water level to prevent alcohols from fuming.
Calculate the total volume of fluid in the piping system. See Table 13. Use the percentage by volume in Table 14 to deter­mine the amount of antifreeze to use. Antifreeze concentration should be checked from a well mixed sample using a hydrome­ter to measure specific gravity.
FREEZE PROTECTION SELECTION — The 30 F FP1 fac­tory setting (water) should be used to avoid freeze damage to the unit.
Once antifreeze is selected, the JW3 jumper (FP1) should be clipped on the control to select the low temperature (antifreeze 10 F) set point to avoid nuisance faults.
Table 12 — Coaxial Water Pressure Drop
UNIT
50PEC
Cv Flow Coefficient MOPD — Maximum Operating Pressure Differential
09
12
15
18
FLOW (GPM)
1.3 1.8 2.0 1.3 1.5 1.2 1.3 1.0 1.2
1.9 3.2 3.6 2.5 2.9 2.2 2.7 2.0 2.4
2.5 5.0 5.8 3.9 4.6 3.5 4.2 3.0 3.8
1.6 1.8 6.5 1.6 6.5 1.4 6.5 1.3 6.5
2.3 3.3 11.4 2.9 11.4 2.6 11.4 2.3 11.4
3.1 5.3 19.6 4.5 19.6 4.1 19.6 3.7 19.6
1.8 1.2 1.6 1.2 1.6 1.1 1.5 1.0 1.4
2.7 2.6 3.4 2.2 3.1 2.0 2.9 1.9 2.7
3.6 4.2 5.7 3.5 5.0 3.2 4.8 3.0 4.5
2.4 2.1 2.8 2.0 2.6 1.8 2.4 1.6 2.3
3.6 4.2 5.8 3.7 5.2 3.3 4.9 3.0 4.6
4.8 6.8 9.6 6.0 8.8 5.5 8.2 4.9 7.7
Without
Motorized
Valve
LEGEND
30 F 50 F 70 F 90 F
With Cv = 2.9
MOPD = 125 psi
Without
Motorized
Valve
PRESSURE DROP (ft wg)
With Cv = 2.9
MOPD = 125 psi
Without
Motorized
Val ve
With Cv = 2.9
MOPD = 125 psi
Without
Motorized
Valve
With Cv = 2.9
MOPD = 125 psi
39
Page 40
Table 13 — Approximate Fluid Volume (gal)
per 100 ft of Pipe
PIPE DIAMETER (in.) VOLUME (gal.)
Copper 14.1
Rubber Hose 13.9 Polyethylene
IPS Internal Pipe Size SCH — Schedule SDR — Standard Dimensional Ratio
NOTE: Volume of heat exchanger is approximately 1.0 gallon.
LEGEND
1.25 6.4
1.5 9.2
3
/4 IPS SDR11 2.8
1 IPS SDR11 4.5
1
1
/4 IPS SDR11 8.0
1
/2 IPS SDR11 10.9
2 IPS SDR11 18.0
1
1
/4 IPS SCH40 8.3
1
1
/2 IPS SCH40 10.9
2 IPS SCH40 17.0
Table 14 — Antifreeze Percentages by Volume
ANTIFREEZE
Methanol (%) 25 21 16 10 100% USP Food Grade
Propylene Glycol (%)
MINIMUM TEMPERATURE FOR FREEZE
PROTECTION (F)
10 15 20 25
38 30 22 15
Cooling Tower/Boiler Systems — These systems
typically use a common loop maintained at 60 to 90 F. Carrier recommends using a closed circuit evaporative cooling tower with a secondary heat exchanger between the tower and the water loop. If an open type cooling tower is used continuously, chemical treatment and filtering will be necessary.
Ground Coupled, Closed Loop and Plateframe Heat Exchanger Well Systems — These systems al-
low water temperatures from 30 to 110 F. The external loop field is divided up into 2 in. polyethylene supply and return lines. Each line has valves connected in such a way that upon system start-up, each line can be isolated for flushing using only the system pumps. Air separation should be located in the pip­ing system prior to the fluid re-entering the loop field.
OPERATION
Power Up Mode —
inputs, terminals and safety controls are checked for normal operation.
NOTE: The compressor will have a 5-minute anti-short cycle delay upon power up.
The unit will not operate until all the
Units with Aquazone™ Complete C Control
STANDBY — The Y and W terminals are not active in Stand­by mode, however the O and G terminals may be active, de­pending on the application. The compressor will be off.
COOLING — The Y and O terminals are active in Cooling mode. After power up, the first call to the compressor will ini­tiate a 5 to 80-second random start delay and a 5-minute anti­short cycle protection time delay. After both delays are com­plete, the compressor is energized.
NOTE: On all subsequent compressor calls the random start delay is omitted.
HEATING STAGE 1 — Terminal Y is active in Heating Stage 1. After power up, the first call to the compressor will initiate a 5 to 80-second random start delay and a 5-minute anti-short cycle protection time delay. After both delays are complete, the compressor is energized.
NOTE: On all subsequent compressor calls the random start delay is omitted.
HEATING STAGE 2 — To enter Stage 2 mode, terminal W is active (Y is already active). Also, the G terminal must be active
or the W terminal is disregarded. The compressor relay will re­main on and EH1 (emergency heat) is immediately turned on. EH2 will turn on after 10 minutes of continual Stage 2 demand.
NOTE: EH2 will not turn on (or if on, will turn off) if FP1 (freeze protection) temperature is greater than 45 F and FP2 is greater than 110 F.
EMERGENCY HEAT — In Emergency Heat (EH) mode, terminal W is active while terminal Y is not. Terminal G must be active or the W terminal is disregarded. EH1 is immediately turned on. EH2 will turn on after 5 minutes of continuous emergency heat demand.
Units with Aquazone Deluxe D Control
STANDBY/FAN ONLY — The compressor will be off. The fan enable, fan speed, and reversing valve (RV) relays will be on if inputs are present. If there is a Fan 1 demand, the fan enable will immediately turn on. If there is a Fan 2 demand, the fan enable and fan speed will immediately turn on.
NOTE: DIP switch 5 on S1 does not have an effect upon Fan 1 and Fan 2 outputs.
HEATING STAGE 1 — In Heating Stage 1 mode, the fan en­able and compressor relays are turned on immediately. Once the demand is removed, the relays are turned off and the con­trol reverts to Standby mode. If there is a master/slave or dual compressor application, all compressor relays and related functions will operate per their associated DIP switch 2 setting on S1.
HEATING STAGE 2 — In Heating Stage 2 mode, the fan en­able and compressor relays remain on. The fan speed relay is turned on immediately and turned off immediately once the de­mand is removed. The control reverts to Heating Stage 1 mode. If there is a master/slave or dual compressor application, all compressor relays and related functions will operate per their associated DIP switch 2 setting on S1.
HEATING STAGE 3 — In Heating Stage 3 mode, the fan en­able, fan speed and compressor relays remain on. The EH1 out­put is turned on immediately. With continuing Heat Stage 3 de­mand, EH2 will turn on after 10 minutes. EH1 and EH2 are turned off immediately when the Heating Stage 3 demand is re­moved. The control reverts to Heating Stage 2 mode.
Output EH2 will be off if FP1’s temperature is greater than 45 F AND FP2 (when shorted) is greater than 110 F during Heating Stage 3 mode. This condition will have a 30-second recognition time. Also, during Heating Stage 3 mode, EH1, EH2, fan enable, and fan speed will be ON if G input is not active.
EMERGENCY HEAT — In Emergency Heat mode, the fan enable and fan speed relays are turned on. The EH1 output is turned on immediately. With continuing emergency heat de­mand, EH2 will turn on after 5 minutes. Fan enable and fan speed relays are turned off after a 60-second delay. The control reverts to Standby mode.
Output EH1, EH2, fan enable, and fan speed will be ON if the G input is not active during Emergency Heat mode.
COOLING STAGE 1 — In Cooling Stage 1 mode, the fan enable, compressor and RV relays are turned on immediately. If configured as stage 2 (DIP switch set to OFF) then the com­pressor and fan will not turn on until there is a stage 2 demand. The fan enable and compressor relays are turned off immedi­ately when the Cooling Stage 1 demand is removed. The con­trol reverts to Standby mode. The RV relay remains on until there is a heating demand. If there is a master/slave or dual compressor application, all compressor relays and related func­tions will track with their associated DIP switch 2 on S1.
COOLING STAGE 2 — In Cooling Stage 2 mode, the fan enable, compressor and RV relays remain on. The fan speed re­lay is turned on immediately and turned off once the Cooling Stage 2 demand is removed. The control reverts to Cooling Stage 1 mode. If there is a master/slave or dual compressor
40
Page 41
application, all compressor relays and related functions will track with their associated DIP switch 2 on S1.
NIGHT LOW LIMIT (NLL) STAGED HEATING — In NLL staged Heating mode, the override (OVR) input becomes active and is recognized as a call for heating and the control will immediately go into a Heating Stage 1 mode. With an additional 30 minutes of NLL demand, the control will go into Heating Stage 2 mode. With another additional 30 minutes of NLL demand, the control will go into Heating Stage 3 mode.
Units with WSHP Open Multiple Protocol —
The WSHP Open multi-protocol controller will control me­chanical cooling, heating and waterside economizer outputs based on its own space temperature input and set points. An optional CO space can maximize the occupant comfort. The WSHP Open controller has its own hardware clock that is automatically set when the heat pump software is downloaded to the board. Oc­cupancy types are described in the scheduling section below. The following sections describe the functionality of the WSHP Open multi-protocol controller. All point objects referred to in this sequence of operation will be referenced to the objects as viewed in the BACview
SCHEDULING — Scheduling is used to start/stop the unit based on a time period to control the space temperature to spec­ified occupied heating and cooling set points. The controller is defaulted to control by occupied set points all the time, until ei­ther a time schedule is configured with BACview tant, i-Vu able the BAS (Building Automation System) on/off point. The local time and date must be set for these functions to operate properly. The occupancy source can be changed to one of the following:
Occupancy Schedules until a time schedule has been configured using either Field Assistant, i-Vu Open, BACview to enable/disable the BAS on/off point. The BAS point can be disabled by going to Config, then Unit, then Occupancy Sched­ules and changing the point from enable to disable then click­ing OK.
NOTE: This point must be enabled in order for the i-Vu Open, Field Assistant, or BACview schedule to the controller.
Schedule_schedule schedule configured and stored in the unit. The schedule is accessible via the BACview Field Assistant control system. The daily schedule consists of a start/stop time (standard or 24-hour mode) and seven days of the week, starting with Monday and ending on Sunday. To enter a daily schedule, navigate to Config, then Sched, then enter BACview schedule_schedule. From here, enter either a Weekly or Excep­tion schedule for the unit.
Occupancy Input Contact the capability to use an external dry contact closure to deter­mine the occupancy status of the unit. The Occupancy Sched­ules will need to be disabled in order to utilize the occupancy contact input.
NOTE: Scheduling can only be controlled from one source. BAS (Building Automation System) On/Off
system that supports network scheduling can control the unit through a network communication and the BAS scheduling function once the Occupancy Schedules have been disabled.
NOTE: Scheduling can either be controlled via the unit or the BAS, but not both.
INDOOR FAN — The indoor fan will operate in any one of three modes depending on the user configuration selected.
Fan mode can be selected as Auto, Continuous, or Always
On. In Auto mode, the fan is in intermittent operation during
IAQ (indoor air quality) sensor mounted in the
2
6
handheld user interface.
6
®
Open, or a third party control system to enable/dis-
, Field Assis-
— The controller will be occupied 24/7
6
or a third party control system
6
control system to assign a time
— The unit will operate according to the
6
Handheld tool, i-Vu Open, or
6
Admin Password (1111), then go to
— The WSHP Open controller has
— A BAS
both occupied and unoccupied periods. Continuous fan mode is intermittent during unoccupied periods and continuous dur­ing occupied periods. Always On mode operates the fan con­tinuously during both occupied and unoccupied periods. In the default mode, Continuous, the fan will be turned on whenever any one of the following is true:
• The unit is in occupied mode as determined by its occu­pancy status.
• There is a demand for cooling or heating in the unoccu­pied mode.
• There is a call for dehumidification (optional). When power is reapplied after a power outage, there will be
a configured time delay of 5 to 600 seconds before starting the fan. There are also configured fan delays for Fan On and Fan Off. The Fan On delay defines the delay time (0 to 30 seconds; default 10) before the fan begins to operate after heating or cooling is started while the Fan Off delay defines the delay time (0 to 180 seconds; default 45) the fan will continue to op­erate after heating or cooling is stopped. The fan will continue to run as long as the compressors, heating stages, or the dehu­midification relays are on. If the SPT failure alarm or conden­sate overflow alarm is active; the fan will be shut down imme­diately regardless of occupancy state or demand.
Fan Speed Control (During Heating)
— Whenever heat is re­quired and active, the control continuously monitors the sup­ply-air temperature to verify it does not rise above the config­ured maximum heating SAT limit (110 F default). As the SAT approaches this value, the control will increase the fan speed as required to ensure the SAT will remain within the limit. This feature provides the most quiet and efficient operation by oper­ating the fan at the lowest speed possible.
Fan Speed Control (During Cooling)
— Whenever mechani­cal cooling is required and active, the control continuously monitors the supply-air temperature to verify it does not fall be­low the configured minimum cooling SAT limit (50 F default). As the SAT approaches this value, the control will increase the fan speed as required to ensure the SAT will remain within the limit. The fan will operate at lowest speed to maximize latent capacity during cooling.
COOLING — The WSHP Open controller will operate one or two stages of compression to maintain the desired cooling set point. The compressor outputs are controlled by the PI (propor­tional-integral) cooling loop and cooling stages capacity algo­rithm. They will be used to calculate the desired number of stages needed to satisfy the space by comparing the space tem­perature (SPT) to the appropriate cooling set point. The water side economizer, if applicable, will be used for first stage cool­ing in addition to the compressor(s). The following conditions must be true in order for the cooling algorithm to run:
• Cooling is set to Enable.
• Heating mode is not active and the compressor time
guard has expired.
• Condensate overflow input is normal.
• If occupied, the SPT is greater than the occupied cooling
set point.
• Space temperature reading is valid.
• If unoccupied, the SPT is greater than the unoccupied
cooling set point.
• If economizer cooling is available and active and the
economizer alone is insufficient to provide enough cool­ing.
• OAT (if available) is greater than the cooling lockout
temperature.
If all the above conditions are met, the compressors will be energized as required, otherwise they will be deenergized. If cooling is active and should the SAT approach the minimum SAT limit, the fan will be indexed to the next higher speed. Should this be insufficient and if the SAT falls further (equal to the minimum SAT limit), the fan will be indexed to the
41
Page 42
maximum speed. If the SAT continues to fall 5 F below the
°
°
minimum SAT limit, all cooling stages will be disabled.
During Cooling mode, the reversing valve output will be held in the cooling position (either B or O type as configured) even after the compressor is stopped. The valve will not switch position until the Heating mode is required.
The configuration screens contain the minimum SAT parameter as well as cooling lockout based on outdoor-air temperature (OAT) Both can be adjusted to meet various specifications.
There is a 5-minute off time for the compressor as well as a 5-minute time delay when staging up to allow the SAT to achieve a stable temperature before energizing a second stage of capacity. Likewise, a 45-second delay is used when staging down.
After a compressor is staged off, it may be restarted again after a normal time-guard period of 5 minutes and if the sup­ply-air temperature has increased above the minimum supply­air temperature limit.
The WSHP Open controller provides a status input to moni­tor the compressor operation. The status is monitored to deter­mine if the compressor status matches the commanded state. This input is used to determine if a refrigerant safety switch or other safety device has tripped and caused the compressor to stop operating normally. If this should occur, an alarm will be generated to indicate the faulted compressor condition.
HEATING — The WSHP Open controller will operate one or two stages of compression to maintain the desired heating set point. The compressor outputs are controlled by the heating PI (proportional-integral) loop and heating stages capacity algo­rithm. They will be used to calculate the desired number of stages needed to satisfy the space by comparing the space tem­perature (SPT) to the appropriate heating set point. The follow­ing conditions must be true in order for the heating algorithm to run:
• Heating is set to Enable.
• Cooling mode is not active and the compressor time
guard has expired.
• Condensate overflow input is normal.
• If occupied, the SPT is less than the occupied heating set
point.
• Space temperature reading is valid.
• If unoccupied, the SPT is less than the unoccupied heat-
ing set point.
• OAT (if available) is less than the heating lockout
temperature.
If all the above conditions are met, the heating outputs will be energized as required, otherwise they will be deenergized. If the heating is active and should the SAT approach the maxi­mum SAT limit, the fan will be indexed to the next higher speed. Should this be insufficient, and the SAT rises further reaching the maximum heating SAT limit, the fan will be indexed to the maximum speed. If the SAT still continues to rise 5 F above the maximum limit, all heating stages will be disabled.
During Heating mode, the reversing valve output will be held in the heating position (either B or O type as configured) even after the compressor is stopped. The valve will not switch position until the Cooling mode is required.
The configuration screens contain the maximum SAT parameter as well as heating lockout based on outdoor-air temperature (OAT); both can be adjusted to meet various specifications.
There is a 5-minute off time for the compressor as well as a 5-minute time delay when staging up to allow the SAT to achieve a stable temperature before energizing a second stage of capacity. Likewise, a 45-second delay is used when staging down.
After a compressor is staged off, it may be restarted again after a normal time-guard period of 5 minutes and if the sup­ply-air temperature has fallen below the maximum supply air temperature limit.
The WSHP Open controller provides a status input to moni­tor the compressor operation. The status is monitored to deter­mine if the compressor status matches the commanded state. This input is used to determine if a refrigerant safety switch or other safety device has tripped and caused the compressor to stop operating normally. If this should occur, an alarm will be generated to indicate the faulted compressor condition. Also, if auxiliary heat is available (see below), the auxiliary heat will operate to replace the reverse cycle heating and maintain the space temperature as required.
AUXILIARY HEAT — The WSHP Open controller can con­trol a two-position, modulating water, or steam valve connect­ed to a coil on the discharge side of the unit and supplied by a boiler or a single-stage ducted electric heater in order to main­tain the desired heating set point. Should the compressor capac­ity be insufficient or a compressor failure occurs, the auxiliary heat will be used. Unless the compressor fails, the auxiliary heat will only operate to supplement the heat provided by the compressor if the space temperature falls more than one degree below the desired heating set point (the amount is config­urable). The heat will be controlled so the SAT will not exceed the maximum heating SAT limit.
Auxiliary Modulating Hot Water/Steam Heating Reheat — The control can modulate a hot water or steam valve con­nected to a coil on the discharge side of the unit and supplied by a boiler in order to maintain the desired heating set point should the compressor capacity be insufficient or a compressor failure occurs. Unless a compressor fault condition exists, the valve will only operate to supplement the heat provided by the compressor if the space temperature falls more than one degree below the desired heating set point. The valve will be con­trolled so the SAT will not exceed the maximum heating SAT limit.
Two-Position Hot Water/Steam Heating Reheat trol can operate a two-position, NO or NC, hot water or steam valve connected to a coil on the discharge side of the unit and supplied by a boiler in order to maintain the desired heating set point should the compressor capacity be insufficient or a com­pressor failure occurs. Unless a compressor fault condition ex­ists, the valve will only open to supplement the heat provided by the compressor if the space temperature falls more than one degree below the desired heating set point. The valve will be controlled so the SAT will not exceed the maximum heating SAT limit. The heat stage will also be subject to a 2-minute minimum OFF time to prevent excessive valve cycling.
Single Stage Electric Auxiliary Heat erate a field-installed single stage of electric heat installed on the discharge side of the unit in order to maintain the desired heating set point should the compressor capacity be insufficient or a compressor failure occurs. Unless a compressor fault con­dition exists, the heat stage will only operate to supplement the heat provided by the compressor if the space temperature falls more than one degree below the desired heating set point. The heat stage will be controlled so the SAT will not exceed the maximum heating SAT limit. The heat stage will also be sub­ject to a 2-minute minimum OFF time to prevent excessive cycling.
INDOOR AIR QUALITY (IAQ) AND DEMAND CON­TROLLED VENTILATION (DCV) — If the optional in­door air quality sensor is installed, the WSHP Open controller can maintain indoor air quality via a modulating OA damper providing demand controlled ventilation. The control operates the modulating OA damper during occupied periods. The con­trol monitors the CO set points, adjusting the ventilation rate as required. The control provides proportional ventilation to meet the requirements of
level and compares it to the configured
2
— The control can op-
The con-
42
Page 43
ASHRAE (American Society of Heating, Refrigerating and
°
°
°
°
Air Conditioning Engineers) specifications by providing a base ventilation rate and then increasing the rate as the CO creases. The control will begin to proportionally increase venti­lation when the CO point and will reach the full ventilation rate when the CO2 level is at or above the maximum set point. A user-configurable min­imum damper position ensures that proper base ventilation is delivered when occupants are not present. The IAQ configura­tions can be accessed through the configuration screen. The following conditions must be true in order for this algorithm to run:
• Damper control is configured for DCV.
• The unit is in an occupied mode.
• The IAQ sensor reading is greater than the DCV start control set point.
The control has four user adjustable set points: DCV start
control set point, DCV maximum control set point, minimum damper position, and DCV maximum damper position.
Two-Position OA Damper to operate a ventilation damper in a two-position ventilation mode to provide the minimum ventilation requirements during occupied periods.
WATERSIDE ECONOMIZER — The WSHP Open control­ler has the capability of providing modulating or two-position water economizer operation (for a field-installed economizer coil mounted to the entering air side of the unit and connected to the condenser water loop) in order to provide free cooling (or preheating) when water conditions are optimal. Water econ­omizer settings can be accessed through the equipment status screen. The following conditions must be true for economizer operation:
• SAT reading is available.
• LWT reading is available.
• Space temperature reading is valid.
• If unoccupied, the SPT is greater than the unoccupied cooling set point or less than the unoccupied heating set point and the condenser water is suitable.
Modulating Water Economizer Control the capability to modulate a water valve to control condenser water flowing through a coil on the entering air side of the unit.
Cooling — The purpose is to provide an economizer cooling function by using the water loop when the entering water loop temperature is suitable (at least 5 F below space temperature). If the water loop conditions are suitable, then the valve will modulate open as required to maintain a supply-air temperature that meets the load conditions. Should the economizer coil ca­pacity alone be insufficient for a period greater than 5 minutes, or should a high humidity condition occur, then the compressor will also be started to satisfy the load. Should the SAT ap­proach the minimum cooling SAT limit, the economizer valve will modulate closed during compressor operation.
Heating — Additionally, the control will modulate the water valve should the entering water loop temperature be suitable for heating (at least 5 F above space temperature) and heat is required. The valve will be controlled in a similar manner ex­cept to satisfy the heating requirement. Should the economizer coil capacity alone be insufficient to satisfy the space load con­ditions for more than 5 minutes, then the compressor will be started to satisfy the load. Should the SAT approach the maxi­mum heating SAT limit, the economizer valve will modulate closed during compressor operation.
Two-Position Water Economizer Control the capability to control a NO or NC, two-position water valve to control condenser water flow through a coil on the entering air side of the unit.
level rises above the start ventilation set
2
— The control can be configured
— The control has
— The control has
level in-
2
Cooling — The purpose is to provide a cooling economizer function directly from the condenser water loop when the en­tering water loop temperature is suitable (at least 5 F below space temperature). If the optional coil is provided and the wa­ter loop conditions are suitable, then the valve will open to pro­vide cooling to the space when required. Should the capacity be insufficient for a period greater than 5 minutes, or should a high humidity condition occur, then the compressor will be started to satisfy the load. Should the SAT reach the minimum cooling SAT limit, the economizer valve will close during compressor operation.
Heating — Additionally, the economizer control will open the water valve should the entering water loop temperature be suit­able for heating (at least 5 F above space temperature) and heat is required. The valve will be controlled in a similar man­ner except to satisfy the heating requirement. Should the coil capacity be insufficient to satisfy the space load for more than 5 minutes, then the compressor will be started to satisfy the load. Should the SAT reach the maximum heating SAT limit, the economizer valve will close during compressor operation.
DEMAND LIMIT — The WSHP Open controller has the ability to accept three levels of demand limit from the network. In response to a demand limit, the unit will decrease its heating set point and increase its cooling set point to widen the range in order to immediately lower the electrical demand. The amount of temperature adjustment in response is user adjustable for both heating and cooling and for each demand level. The re­sponse to a particular demand level may also be set to zero.
CONDENSER WATER LINKAGE — The control pro­vides optimized water loop operation using an universal con­troller (UC) open loop controller. Loop pump operation is auto­matically controlled by WSHP equipment occupancy sched­ules, unoccupied demand and tenant override conditions. Positive pump status feedback prevents nuisance fault trips. The condenser water linkage operates when a request for con­denser water pump operation is sent from each WSHP to the loop controller. This request is generated whenever any WSHP is scheduled to be occupied, is starting during optimal start (for warm-up or pull down prior to occupancy), there is an unoccu­pied heating or cooling demand, or a tenant pushbutton over­ride. At each WSHP, the water loop temperature and the loop pump status is given. The WSHP will NOT start a compressor until the loop pumps are running or will shutdown the com­pressors should the pumps stop. This prevents the WSHP from operating without water flow and thus tripping out on refriger­ant pressure, causing a lockout condition. The WSHP Open controller control will prevent this from occurring. Also, the loop controller can be configured to start the pumps only after a configurable number of WSHPs are requesting operation (from 1-"N"). This can be used to prevent starting the entire loop op­eration for only one WSHP. Meanwhile, the WSHPs will not operate if the loop pump status is off and therefore the WSHP compressor will not run.
COMPLETE C AND DELUXE D BOARD
SYSTEM TEST
System testing provides the ability to check the control operation. The control enters a 20-minute Test mode by momentarily shorting the test pins. All time delays are reduced by a factor of 15.
Test Mode — To enter Test mode on Complete C or
Deluxe D controls, cycle the power 3 times within 60 seconds. The LED (light-emitting diode) will flash a code representing the last fault when entering the Test mode. The alarm relay will also power on and off during Test mode. See Tables 15-17. To exit Test mode, short the terminals for 3 seconds or cycle the power 3 times within 60 seconds.
NOTE: The Deluxe D control has a flashing code and alarm relay cycling code that will both have the same numerical
43
Page 44
label. For example, flashing code 1 will have an alarm relay cycling code 1. Code 1 indicates the control has not faulted since the last power-off to power-on sequence.
WSHP Open Test Mode — To enter WSHP Open test
mode, navigate from the BACview
6
home screen to the config­uration screen. Choose the service screen and enable unit test. The controller will then test the following:
FAN TEST — Tests all fan speeds, sequences fan from low to high, and operates each speed for one minute. Resets to disable on completion.
COMPRESSOR TEST — Tests compressor cooling and heating operation. Sequences cooling stage 1 then cooling stage 2 followed by heating stage 2 then reduces capacity to heating stage 1. Operates for 1 minute per step.
DEHUMIDIFICATION TEST — Tests dehumidification mode. Operates for 2 minutes.
AUXILIARY HEATING TEST — Tests auxiliary heat. Sequences fan on and enables heating coil for 1 minute.
H
O ECONOMIZER TEST — Tests entering/returning
2
water loop economizer operation. Sequences fan and opens economizer water valve for one minute.
OPEN VENT DAMPER 100% TEST — Tests outside air (OA) damper operation.
PREPOSITION OA DAMPER — Prepositions OA damper actuator to set proper preload.
NOTE: The auxiliary heating test, H vent damper 100% test, and preposition OA damper features will not be visible on the screen unless configured.
Once tests are complete, set unit test back to disable. Unit will automatically reset to disable after 1 hour.
Retry Mode — In Retry mode, the status LED will start to
flash slowly to signal that the control is trying to recover from an input fault. The control will stage off the outputs and try to again satisfy the thermostat used to terminal Y. Once the thermostat in­put calls are satisfied, the control will continue normal operation.
NOTE: If 3 consecutive faults occur without satisfying the thermostat input call to terminal Y, the control will go into lockout mode. The last fault causing the lockout is stored in memory and can be viewed by entering Test mode.
Aquazone™ Deluxe D Control LED Indica­tors —
STATUS LED — Status LED indicates the current status or mode of the Deluxe D control. The Status LED light is green.
TEST LED — Test LED will be activated any time the De­luxe D control is in Test mode. The Test LED light is yellow.
FAULT LED — Fault LED light is red. The fault LED will always flash a code representing the last fault in memory. If there is no fault in memory, the fault LED will flash code 1 and appear as 1 fast flash alternating with a 10-second pause. See Table 17.
There are 3 LED indicators on the Deluxe D control:
Table 15 — Complete C Control Current LED Status and Alarm Relay Operations
LED STATUS DESCRIPTION OF OPERATION ALARM RELAY
On
Off Complete C Control is non-functional Open
Slow Flash
Fast Flash Lockout Closed Flashing Code 1 Test Mode — No fault in memory Cycling Code 1 Flashing Code 2 Test Mode — HP Fault in memory Cycling Code 2 Flashing Code 3 Test Mode — LP Fault in memory Cycling Code 3 Flashing Code 4 Test Mode — FP1 Fault in memory Cycling Code 4 Flashing Code 5 Test Mode — FP2 Fault in memory Cycling Code 5 Flashing Code 6 Test Mode — CO Fault in memory Cycling Code 6 Flashing Code 7 Test Mode — Over/Under shutdown in memory Cycling Code 7 Flashing Code 8 Test Mode — PM in memory Cycling Code 8 Flashing Code 9 Test Mode — FP1/FP2 swapped fault in memory Cycling Code 9
LEGEND NOTES:
CO — Condensate Overflow LED — Light-Emitting Diode FP — Freeze Protection LP Low Pressure HP — High Pressure PM — Performance Monitor
Normal Mode Open Normal Mode with PM Warning Cycle (Closed 5 sec, Open 25 sec)
Fault Retry Open Over/Under Voltage Shutdown Open (Closed after 15 minutes)
1. Slow flash is 1 flash every 2 seconds.
2. Fast flash is 2 flashes every 1 second.
3. EXAMPLE: “Flashing Code 2 is represented by 2 fast flashes followed by a 10-second pause. This sequence will repeat continually until the fault is cleared.
Table 16 — Complete C Control LED Code and Fault Descriptions
O economizer test, open
2
LED CODE FAULT DESCRIPTION
1 No fault in memory There has been no fault since the last power-off to power-on sequence 2 High-Pressure Switch HP open instantly 3 Low-Pressure Switch LP open for 30 continuous seconds before or during a call (bypassed for first 60 seconds) 4 Freeze Protection Coax — FP1 FP1 below temp limit for 30 continuous seconds (bypassed for first 60 seconds of operation) 5 Freeze Protection Air Coil — FP2 FP2 below temp limit for 30 continuous seconds (bypassed for first 60 seconds of operation) 6 Condensate overflow Sensor overflow (grounded) for 30 continuous seconds 7 (Autoreset) Over/Under Voltage Shutdown "R" power supply is <19-vac or >30-vac 8 PM Warning Performance monitor Warning has occurred. 9 FP1 and FP2 Thermistors are swapped FP1 temperature is higher than FP2 in heating/test mode, or FP2 temperature is higher than FP1 in
LEGEND
FP Freeze Protection LP — Low Pressure HP — High Pressure PM — Performance Monitor LED — Light-Emitting Diode
cooling/test mode.
44
Page 45
Table 17 — Aquazone™ Deluxe D Control Current LED Status and Alarm Relay Operations
DESCRIPTION
Normal Mode On Off Flash Last Fault Code in Memory Open Normal Mode with PM On Off Flashing Code 8 Cycle (closed 5 sec, open 25 sec, …) D Control is non-functional Off Off Off Open Test Mode On Flash Last Fault Code in Memory Cycling Appropriate Code Night Setback Flashing Code 2 Flash Last Fault Code in Memory ESD Flashing Code 3 Flash Last Fault Code in Memory Invalid T-stat Inputs Flashing Code 4 Flash Last Fault Code in Memory No Fault in Memory On Off Flashing Code 1 Open HP Fault Slow Flash Off Flashing Code 2 Open LP Fault Slow Flash Off Flashing Code 3 Open FP1 Fault Slow Flash Off Flashing Code 4 Open FP2 Fault Slow Flash Off Flashing Code 5 Open CO Fault Slow Flash Off Flashing Code 6 Open Over/Under Voltage Slow Flash Off Flashing Code 7 Open (closed after 15 minutes) HP Lockout Fast Flash Off Flashing Code 2 Closed LP Lockout Fast Flash Off Flashing Code 3 Closed FP1 Lockout Fast Flash Off Flashing Code 4 Closed FP2 Lockout Fast Flash Off Flashing Code 5 Closed CO Lockout Fast Flash Off Flashing Code 6 Closed
LEGEND NOTES:
CO — Condensate Overflow LED — Light-Emitting Diode ESD — Emergency Shutdown LP Low Pressure FP Freeze Protection PM — Performance Monitor HP High Pressure
STATUS LED
(Green)
TEST LED
(Yellow)
FAULT LED (Red) ALARM RELAY
1. If there is no fault in memory, the Fault LED will flash code 1.
2. Codes will be displayed with a 10-second Fault LED pause.
3. Slow flash is 1 flash every 2 seconds.
4. Fast flash is 2 flashes every 1 second.
5. EXAMPLE: “Flashing Code 2 is represented by 2 fast flashes followed by a 10-second pause. This sequence will repeat continually until the fault is cleared.
SERVICE
Perform the procedures outlined below periodically, as
indicated.
WARNING
To prevent injury or death due to electrical shock or contact with moving parts, open unit disconnect switch before ser­vicing unit.
IMPORTANT: When a compressor is removed from this unit, system refrigerant circuit oil will remain in the com­pressor. To avoid leakage of compressor oil, the refrigerant lines of the compressor must be sealed after it is removed.
IMPORTANT: All refrigerant discharged from this unit must be recovered without exception. Technicians must fol­low industry accepted guidelines and all local, state and fed­eral statutes for the recovery and disposal of refrigerants.
IMPORTANT: To avoid the release of refrigerant into the atmosphere, the refrigerant circuit of this unit must only be serviced by technicians who meet local, state and federal proficiency requirements.
Unit Inspection — Visually inspect the unit at least once
a month. Pay special attention to hose assemblies. Repair any leaks and replace deteriorated hoses immediately. Note any signs of deterioration or cracking.
System Flushing — Properly clean and flush system
periodically. Refer to Pre-Start-Up, System Cleaning and Flushing section.
Water Coil — Keep air out of the water coil. Check open
loop systems to be sure the well head is not allowing air to in­filtrate the water line. Always keep lines airtight.
Inspect heat exchangers regularly and clean more frequently
if the unit is located in a “dirty” environment. The heat
exchanger should be kept full of water at all times. Open loop systems should have an inverted P trap placed in the discharge line to keep water in the heat exchanger during off cycles. Closed loop systems must have a minimum of 15 psig during the summer and 40 psig during the winter.
Check P trap frequently for proper operation.
FILTERS — Inspect filters. Establish a regular maintenance schedule. Clean or replace filters frequently depending on need.
To remove the filter from the 50PEC unit, slide the filter out of its frame located in the return air opening at the bottom front of the unit. When re-installing the filter, use the slide-in rails of the filter frame to guide the filter into the proper position.
CAUTION
To avoid fouled machinery and extensive unit clean-up, DO NOT operate units without filters in place. DO NOT use equipment as a temporary heat source during construction.
Refrigerant System — Verify air and water flow rates
are at proper levels before servicing. To maintain sealed circuit­ry integrity, do not install service gages unless unit operation appears abnormal.
Condenser Cleaning — Water-cooled condensers may
require cleaning of scale (water deposits) due to improperly maintained closed-loop water systems. Open water tower systems may require removal of sludge build-up due to induced contaminants.
Local water conditions may cause excessive fouling or pitting of tubes. Therefore, condenser tubes should be cleaned at least once a year, or more often if the water is contaminated.
Use standard coil cleaning procedures which are compatible with both the heat exchanger material and copper water lines. Generally, the more water flowing through the unit, the less chance for scaling, however flow rates over 3 gpm per ton can
45
Page 46
produce water (or debris) velocities that can erode the heat ex­changer wall and ultimately produce leaks.
Proper water treatment can minimize tube fouling and pitting. If such conditions are anticipated, water treatment anal­ysis is recommended. Refer to the Carrier System Design Man­ual, Part 5, for general water conditioning information.
CAUTION
Follow all safety codes. Wear safety glasses and rubber gloves when using inhibited hydrochloric acid solution. Observe and follow acid manufacturer’s instructions.
PUMP
SUCTION
PUMP SUPPORT
TANK
PRIMING CONN.
GAS VENT
GLOBE VALV ES
SUPPLY
1 PIPE
CONDENSER
REMOVE WATER REGULATING VALVE
Clean condensers with an inhibited hydrochloric acid solu­tion. The acid can stain hands and clothing, damage concrete, and, without inhibitor, damage steel. Cover surroundings to guard against splashing. Vapors from vent pipe are not harmful, but take care to prevent liquid from being carried over by the gases.
Warm solution acts faster, but cold solution is just as effec­tive if applied for a longer period.
GRAVITY FLOW METHOD — Do not add solution faster than vent can exhaust the generated gases.
When condenser is full, allow solution to remain overnight, then drain condenser and flush with clean water. Follow acid manufacturer’s instructions. See Fig. 37.
FILL CONDENSER WITH CLEANING SOLUTION. DO NOT ADD SOLUTION MORE RAPIDLY THAN VENT CAN EXHAUST GASES CAUSED BY CHEMICAL ACTION.
VENT PIPE
3’ TO 4’
PAIL
1 PIPE
5’ APPROX
FUNNEL
PAIL
CONDENSER
Fig. 37 — Gravity Flow Method
FORCED CIRCULATION METHOD — Fully open vent pipe when filling condenser. The vent may be closed when condenser is full and pump is operating. See Fig. 38.
Regulate flow to condenser with a supply line valve. If pump is a nonoverloading type, the valve may be fully closed while pump is running.
For average scale deposit, allow solution to remain in con­denser overnight. For heavy scale deposit, allow 24 hours. Drain condenser and flush with clean water. Follow acid manu­facturer’s instructions.
FINE MESH SCREEN
RETURN
Fig. 38 — Forced Circulation Method
Condensate Pans — Check condensate drain pans for
algae growth every three months. If algae growth is apparent, consult a water treatment specialist for proper chemical treat­ment. The application of an algaecide every three months will typically eliminate algae problems in most locations. Check condensate hose for leaks and blockage and correct any problems.
Blower Motors — All units have lubricated fan motors.
BLOWER MOTORS SHOULD NEVER BE LUBRICATED UNLESS OBVIOUS, DRY OPERATION IS SUSPECTED. Periodic maintenance oiling is not recommended because it will result in dirt accumulating on excess oil and cause eventu­al motor failure. Conduct annual dry operation check and am­perage check to ensure amp draw is no more than 10% greater than that indicated by serial plate data.
Compressor — Conduct an amperage check annually on
the compressor and fan motor. Amperage draw should not exceed normal full load amps. Maintain a log of amperage to detect deterioration prior to component failure.
Safety Control Reset — The 50PEC heat pumps are
furnished with high-pressure, low-pressure and low­temperature cutouts to prevent the machine from operating at abnormal conditions of temperature or water flow.
The contacts of the high-pressure control used on 50PEC units are designed to open at 376 psig and automatically re-close at 304 psig. The Complete C or Deluxe D control monitors this and other functions such as refrigerant tempera­tures and pressures and condensate overflow and will interrupt unit heating or cooling operation.
The machine must be reset manually. Reset is accomplished by pressing the STOP button and then pushing either HI HEAT, LOW HEAT, HI COOL or LO COOL to restart the unit in the desired mode of operation. (The 50PEC unit can also be reset by opening and closing the supply power disconnect switch.)
IMPORTANT: If the unit must be reset more than twice, check the unit for a dirty filter, abnormal entering water temperature, inadequate or excessive water flow, and inter­nal malfunctions. If the unit continues to cut out, contact a trained service technician.
WARNING
When replacing the compressor contactor or lockout relay in a unit with electromechanical controls, use only Carrier factory authorized parts. Substitution of other components may result in an inoperative safety circuit and may cause a hazardous condition.
46
Page 47
Checking System Charge — Units are shipped with
full operating charge. If recharging is necessary:
1. Insert thermometer bulb in insulating rubber sleeve on liquid line near filter drier. Use a digital thermometer for all temperature measurements. DO NOT use a mercury or dial-type thermometer.
2. Connect pressure gage to discharge line near compressor.
3. After unit conditions have stabilized, read head pressure on discharge line gage.
NOTE: Operate unit a minimum of 15 minutes before checking charge. From standard field-supplied Pressure­Temperature chart for R-410A, find equivalent saturated condensing temperature.
4. Read liquid line temperature on thermometer, then subtract from bubble point temperature. The difference equals subcooling temperature.
Refrigerant Charging
WARNING
To prevent personal injury, wear safety glasses and gloves when handling refrigerant. Do not overcharge system — this can cause compressor flooding.
NOTE: Do not vent or depressurize unit refrigerant to atmo­sphere. Remove and recover refrigerant following accepted practices.
Air Coil Fan Motor Removal
CAUTION
Before attempting to remove fan motors or motor mounts, place a piece of plywood over evaporator coils to prevent coil damage.
Motor power wires need to be disconnected from motor
terminals before motor is removed from unit.
1. Shut off unit main power supply.
2. Loosen bolts on mounting bracket so that fan belt can be removed.
3. Loosen and remove the 2 motor mounting bracket bolts on left side of bracket.
4. Slide motor/bracket assembly to extreme right and lift out through space between fan scroll and side frame. Rest motor on a high platform such as a step ladder. Do not allow motor to hang by its power wires.
Replacing the WSHP Open Controller’s Bat­tery —
CR2032 battery provides a minimum of 10,000 hours of data retention during power outages.
NOTE: Power must be ON to the WSHP Open controller when replacing the battery, or the date, time and trend data will be lost.
1. Remove the battery from the controller, making note of
2. Insert the new battery, matching the battery's polarity
The WSHP Open controller’s 10-year lithium
the battery's polarity.
with the polarity indicated on the WSHP Open controller.
TROUBLESHOOTING
When troubleshooting problems with a WSHP, consider the
following and refer to Table 18.
Thermistor — A thermistor may be required for single-
phase units where starting the unit is a problem due to low voltage.
WSHP Open Controller — With the WSHP Open con-
troller option, the 100 most recent alarms can be viewed using the BACview
To view the alarms:
1. Navigate to the Alarm Status screen from the Home
2. From the Alarm Status screen, press the Alarm softkey to
3. To view alarms which have been corrected, scroll down
6
alarm status and alarm history.
screen using the arrow softkeys. The screen will display the current alarm status, either normal or Alarm, and al­low for scrolling through the unit’s alarm status.
view the 100 most recent alarms which are labeled with date and time for easy reference.
NOTE: Active faults can be viewed by scrolling down, these faults indicate a possible bad sensor or some condi­tion which may not merit an alarm.
through the Alarm screen to Return Top Normal screen. NOTE: Alarms are automatically reset once alarm con-
dition has been corrected. See Table 18 for possible alarm cause and solution.
47
Page 48
Table 18 — Troubleshooting
FAULT HEATING COOLING POSSIBLE CAUSE SOLUTION
Main Power Problems X X Green Status LED Off Check line voltage circuit breaker and disconnect.
Check for line voltage between L1 and L2 on the contactor. Check for 24-vac between R and C on controller. Check primary/secondary voltage on transformer.
HP Fault — Code 2 High Pressure
X Reduced or no airflow in
X Air temperature out of range
X X Overcharged with refrigerant Check superheat/subcooling vs. typical operating condition. X X Bad HP switch Check switch continuity and operation. Replace.
LP Fault — Code 3 Low Pressure/Loss of Charge
FP1 Fault — Code 4 Water Freeze Protection
FP2 Fault — Code 5 Air Coil Freeze Protection
Condensate Fault — Code 6
Over/Under Voltage — Code 7 (Auto Resetting)
Performance Monitor — Code 8
No Fault Code Shown X X Compressor overload Check and replace if necessary.
Unit Short Cycles X X Dirty air filter Check and clean air filter.
Only Fan Runs X X Thermostat position Ensure thermostat set for heating or cooling operation.
LEGEND
FP Freeze Protection HP — High Pressure LED — Light-Emitting Diode LP Low Pressure RV Reversing Valve
X X Insufficient charge Check for refrigerant leaks. X Compressor pump down at
X Reduced or no water flow in
X Inadequate antifreeze level Check antifreeze density with hydrometer. X Improper freeze protect set-
X Water temperature out of
X X Bad thermistor Check temperature and impedance correlation.
X X Bad thermistor Check temperature and impedance correlation. X X Blocked drain Check for blockage and clean drain. X X Improper trap Check trap dimensions and location ahead of vent.
X X Under voltage Check power supply and 24-vac voltage before and during operation.
X X Over voltage Check power supply voltage and 24 vac before and during operation.
X Heating mode FP2>125 F Check for poor airflow or overcharged unit.
X X Control board Reset power and check operation.
X X Unit in Test mode Reset power or wait 20 minutes for auto exit. X X Unit selection Unit may be oversized for space. Check sizing for actual load of space. X X Compressor overload Check and replace if necessary.
X X Unit locked out Check for lockout codes. Reset power. X X Compressor overload Check compressor overload. Replace if necessary. X X Thermostat wiring Check Y and W wiring at heat pump. Jumper Y and R for compressor
X Reduced or no water flow in
cooling
X Water temperature out of
range in cooling
heating
in heating
start-up
heating
ting (10 F vs. 30 F)
range
X Reduced or no airflow in
cooling
X Air temperature out of range Too much cold vent air. Bring entering-air temperature within design
X Improper freeze protect set-
ting (10 F vs. 30 F)
X Poor drainage Check for piping slope away from unit.
X Moisture on sensor Check for moisture shorting to air coil.
X Cooling mode FP1>125 F
OR FP2< 40 F
Check pump operation or valve operation/setting. Check water flow adjust to proper flow rate. Bring water temperature within design parameters.
Check for dirty air filter and clean or replace. Check fan motor operation and airflow restrictions. Dirty air coil — construction dust, etc. Perform preventative mainte-
nance; Clean air coil. High external static. Check duct design and downstream interference. Bring return-air temperature within design parameters.
Check charge and start-up water flow.
Check pump operation or water valve operation/setting. Plugged strainer or filter. Clean or replace. Check water flow adjust to proper flow rate.
Clip JW3 jumper for antifreeze (10 F) use.
Bring water temperature within design parameters.
Check for dirty air filter and clean or replace. Check fan motor operation and airflow restrictions. High external static. Check duct design and downstream interference.
parameters. Normal airside applications will require 30 F only.
Check slope of unit toward outlet. Poor venting. Check vent location.
Check power supply wire size. Check compressor starting. Check 24-vac and unit transformer tap for correct power supply voltage.
Check 24-vac and unit transformer tap for correct power supply voltage.
Check for poor water flow or airflow.
operation in Test mode.
48
Page 49
Table 18 — Troubleshooting (cont)
FAULT HEATING COOLING POSSIBLE CAUSE SOLUTION
Only Compressor Runs X X Thermostat wiring Check G wiring at heat pump. Jumper G and R for fan operation.
Check Y and W wiring at heat pump. Jumper Y and R for compressor
X X Fan motor relay Jumper G and R for fan operation. Check for line voltage across BR
Unit Does Not Operate in Cooling
Insufficient Capacity/ Not Cooling or Heating Properly
High Head Pressure X Reduced or no airflow in
Low Suction Pressure X Reduced water flow in
Low Discharge Air Temperature in Heating
High Humidity X Too high airflow Check blower.
LEGEND
FP Freeze Protection HP — High Pressure LED — Light-Emitting Diode LP Low Pressure RV Reversing Valve
X X Fan motor Check for line voltage at motor. Check capacitor.
X X Dirty filter Replace or clean. X Reduced or no airflow in
X X Leaky ductwork Check supply and return-air temperatures at the unit and at distant
X X Low refrigerant charge Check superheat and subcooling. X X Restricted metering device Check superheat and subcooling. Replace.
X X Thermostat improperly
X X Unit undersized Recheck loads and sizing check sensible cooling load and heat pump
X X Scaling in water heat
X X Inlet water too hot or cold Check load, loop sizing, loop backfill, ground moisture.
X Air temperature out of range
X X Unit overcharged Check superheat and subcooling. Reweigh in charge. X X Non-condensables in
X X Restricted metering device Check superheat and subcooling. Replace.
X Water temperature out of
X X Insufficient charge Check for refrigerant leaks. X Too high airflow Check blower. X Poor performance See ‘Insufficient Capacity’ above.
X Reversing valve Set for cooling demand and check 24-vac on RV coil and at control.
X Thermostat setup Check for ‘O’ RV setup not ‘B’. X Thermostat wiring Check O wiring at heat pump. Jumper O and R for RV coil.
heating
X Reduced or no airflow in
cooling
X Defective reversing valve Perform RV touch test.
located
exchanger
heating
X Reduced or no water flow in
cooling
X Inlet water too hot Check load, loop sizing, loop backfill, ground moisture.
in heating
X Scaling in water heat
exchanger
system
heating
range
X Reduced airflow in cooling Check for dirty air filter and clean or replace.
X Air temperature out of range Too much cold vent air. Bring entering air temperature within design
X Unit oversized Recheck loads and sizing check sensible cooling load and heat pump
operation in Test mode.
contacts. Check fan power enable relay operation (if present).
If RV is stuck, run high pressure up by reducing water flow and while operating engage and disengage RV coil voltage to push valve.
Check for dirty air filter and clean or replace. Check fan motor operation and airflow restrictions. High external static. Check duct design and downstream interference. Check for dirty air filter and clean or replace. Check fan motor operation and airflow restrictions. High external static. Check duct design and downstream interference.
duct registers if significantly different, duct leaks are present.
Check location and for air drafts behind thermostat.
capacity. Perform scaling check and clean if necessary.
Check for dirty air filter and clean or replace. Check fan motor operation and airflow restrictions. High external static. Check duct design and downstream interference. Check pump operation or valve operation/setting. Check water flow adjust to proper flow rate.
Bring return-air temperature within design parameters.
Perform scaling check and clean if necessary.
Vacuum system and reweigh in charge.
Check pump operation or water valve operation/setting. Plugged strainer or filter. Clean or replace. Check water flow adjust to proper flow rate. Bring water temperature within design parameters.
Check fan motor operation and airflow restrictions. High external static. Check duct design and downstream interference.
parameters.
capacity.
49
Page 50
APPENDIX A — WSHP OPEN SCREEN CONFIGURATION
SCREEN NAME POINT NAME
Operating Mode
SPT F Displays SPT SAT F Displays SAT
Condenser Leaving
Temperature
Condenser Entering
Temperature
Fan
Equipment
Status
Alarm Status
Sensor
Calibration
BAS — Building Automation System DCV — Demand Controlled Ventilation IAQ — Indoor Air Quality OAT — Outdoor Air Temperature RH Relative Humidity SAT — Supply Air Temperature SPT — Space Temperature TPI Third Party Integration
Compressor Capacity 0 - 100% Displays compressor capacity
Damper Position 0 - 100%
O Economizer 0 - 100% Displays position of economizer valve
H
2
Auxiliary Heat 0 - 100%
Space RH 0 - 100%
Dehumidification Inactive/Active
IAQ CO
2
SPT Alarm Status
Alarming SPT F
SPT Alarm Limit F
SPT Sensor Alarm
Status
IAQ Alarm Status Normal/Alarm Current IAQ/ventilation condition
Compressor Alarm
Status
SAT Alarm Status Normal/Alarm Current SAT condition
Condensate Overflow
Alarm Status
Condenser Water Tem-
perature Alarm Status
Filter Alarm Status Normal/Alarm Current filter condition
Space RH Alarm Status Normal/Alarm Current space RH condition
OAT Alar m Status Normal/Alarm
Airside Linkage Status Normal/Alarm Current linkage status if enabled
Condenser Water
Linkage
SAT
SAT Offset X -9.9 - 10.0 F 0 F Used to correct sensor reading
Leaving Condenser Water Temperature
Leaving CW Offset X -9.9 - 10.0 F 0 F Used to correct sensor reading
Rnet Sensor Temperature
Rnet Offset X -9.9 - 10.0 F 0 F Used to correct sensor reading
RH % Displays Space RH value
RH Sensor Offset X -15% - 15% 0 % Used to correct sensor reading
LEGEND
PASSWO RD
LEVEL
No Password
Required
No Password
Required
Admin Password level access only
EDITABLE RANGE DEFAULT NOTES
Off, Fan Only, Economize,
Cooling, Heating, Cont Fan,
Test, Start Delay, Dehumidify
°
°
°
F
°
F
Off/Low Speed/
Medium Speed
High Speed/On
0 - 9999 ppm Displays the space CO2 level
Normal/Alarm
°
°
Normal/Alarm
Normal/Alarm Current compressor condition
Normal/Alarm
Normal/Alarm
Normal/Alarm Current linkage status if enabled
°
F Display SAT
°°
°
F
°°
°
F Displays SPT
°°
Displays unit operating mode
Displays leaving condenser
water temperature
Displays entering condenser
water temperature (Value
will not update when compressor
Displays current damper position (Viewable only if Ventilation DMP
reheat valve (Viewable only if Leaving
Air Auxiliary Heat Type = 2 position,
Displays space RH% (Viewable only if
Displays if dehumidification is active
Dehumidification Reheat = Installed)
exceeded the alarm limit (when SPT
Displays the SPT alarm limit that was
exceeded; causing the alarm condition
(when SPT alarm above is in Alarm)
SPT sensor - ALARM is displayed
should the sensor fail to communicate
Current status of the condensate
is operating)
Displays fan speed status
Type = 2 position or DCV)
Displays position of auxiliary
1 stage Elect or Modulating)
Humidity Sensor = Installed)
(Viewable only if Factory
Displays current space
temperature condition Displays the SPT that
alarm above is in Alarm)
Displays the status of the Rnet
with the control module
drain (overflow switch)
Current status of the
condenser water
Current status of the OAT
broadcast function
Displays Leaving Condenser
Water Temperature
50
Page 51
APPENDIX A — WSHP OPEN SCREEN CONFIGURATION (cont)
SCREEN NAME POINT NAME
Operating Mode
Fan Operating Mode Auto/Continuous/Always On
Occupancy Status Unoccupied/Occupied Displays the current occupancy status
Occupancy Control
Outside Air
Temperature
SPT F Displays SPT
SPT Status
SPT Sensor Status Inactive/Connected
Condensate Overflow Normal/Alarm
Cooling Set Point F
Unit
Maintenance
System Settings
Occupancy
Maintenance
Schedule
Configuration
BAS — Building Automation System DCV — Demand Controlled Ventilation IAQ — Indoor Air Quality OAT — Outdoor Air Temperature RH Relative Humidity SAT — Supply Air Temperature SPT — Space Temperature TPI Third Party Integration
Heating Set Point F
Set Point Adjustment F
Auxiliary Heat Control
Set Point
O Economizer
H
2
Control Set Point
Calculated IAQ/
Ventilation Damper
position
Active Compressor
Stages
SAT F Displays SAT
Reset Filter Alarm X No/Yes
Overflow Contact Closed/Open
Occupancy Contact Closed/Open
BAS/Keypad Override X
OAT Input N/A / Network
BACnet X See TPI
Keypad Configuration X Mapping
Password X Changes password
Network X See TPI
BACnet Time Master X See TPI
Clock Set X Changes clock/time setting
Override Schedules
Pushbutton Override Inactive/Active Occupied
Keypad Override
Schedules Inactive/Active Occupied
Occupancy Contact Inactive/Active Occupied
BAS on/off Inactive/Active Occupied
Local Occupancy
Schedules
Local Holiday
Schedules
Local Override
Schedules
BACnet Occupancy
Schedules
LEGEND
PASSWORD
LEVEL
No Password
required
No Password
required
User/Admin
Password level
access
EDITABLE RANGE DEFAULT NOTES
Off, Fan Only,Economize,
Cooling, Heating, Cont Fan, Test,
Start Delay, Dehumidify
Always Occupied/Local Schedule/
BACnet Schedule/BAS Keypad/
Occupied Contact/Holiday Schedule/
Override Schedule/Pushbutton
Override/Unoccupied None
°
F
°
Normal/Above Limit/Below
Limit/Sensor Failure
°
°
°
°
F
°
F
%
0/1/2
°
Inactive/Occupied/
Unoccupied
Inactive/Active Occupied
Inactive/Active Occupied/Active
Unoccupied
X Disable/Enable Enable
X Disable/Enable Disable
X Disable/Enable Disable
X Disable/Enable Disable
Inactive
Displays unit operating mode
Displays how the fan is configured
Displays OAT (Viewable only if OAT
Displays the connection status
Displays the offset values from the Rnet
user set point adjustment that is being
applied to the configured set points
Displays the calculated set point being
used for auxiliary heating control
Displays the calculated set point being
Displays the ventilation damper
position calculated by the DCV control
Used to reset the filter alarm timer after
the filter has been cleaned or replaced
Displays the state of the condensate
Displays the state of the external/
remote occupancy input switch contact
Provides capability to force the
occupied or unoccupied mode
Displays if an OAT value is being
Used to display the active and
inactive occupancy control inputs
Used to define which occupancy inputs
to operate
Displays the origin of the
occupancy control
is a network broadcast)
Displays the SPT status
of the Rnet sensor
Displays the status of the
condensate overflow
Displays the actual set point
being used for cooling control
Displays the actual set point
being used for heating control
used for economizer control
Displays the actual number of
compressor stages operating
overflow switch contact
equipment to operate in an
received from the Network
are used to determine
occupancy mode.
51
Page 52
APPENDIX A — WSHP OPEN SCREEN CONFIGURATION (cont)
→→→
SCREEN NAME POINT NAME
Occupied Heating
Occupied Cooling X 55 - 99 F 76 F
Unoccupied Heating X 40 - 90 F 55 F
Unoccupied Cooling X 55 - 99 F 90 F
Effective Heating
Set Point
Effective Cooling
Set Point
Optimal Start
Configuration
Occupied RH
Set Points
Configuration
Schedule
Weekly Schedule
Configuration
Schedule
Exception
Schedules 1 - 12
LEGEND
BAS — Building Automation System DCV — Demand Controlled Ventilation IAQ — Indoor Air Quality OAT — Outdoor Air Temperature RH Relative Humidity SAT — Supply Air Temperature SPT — Space Temperature TPI Third Party Integration
Set Point
Unoccupied RH
Set Point
DCV CTRL Start
Set Point
DCV Max CTRL
Set Point
Start Time
End Time X 00:00 - 24:00 18:00
Mon X No/Yes Yes
Tu e X N o /Ye s Yes
Wed X No/Yes Yes
Thur X No/Yes Yes
Fri X No/Yes Ye s
Sat X No/Yes No
Sun X No/Yes No
Start Month
Start Day X 0 - 31 0
Start Time X 00:00 - 23:59 0:00
End Month X 0 - 12 0
End Day X 0 - 31 0
End Time X 00:00 - 24:00 0:00
PASSWORD
LEVEL
User/Admin
Password level
access
User/Admin
Password level
access
User/Admin
Password level
access
EDITABLE RANGE DEFAULT NOTES
X 40 - 90 F 72 F
X0 - 10 F
X0 - 10 F
X 0 - 100% 65%
X 0 - 100% 90%
X 0 - 9999 ppm 500 ppm
X 0 - 9999 ppm 1050 ppm
X 00:00 - 23:59 06:00
X0 - 120
°°
°°
°°
°°
°
°
Defines the Occupied
Heating Set Point
Defines the Occupied
Cooling Set Point
Defines the Unoccupied
Heating Set Point
Defines the Unoccupied
Cooling Set Point
Takes into effect bias (maximum
allowable set point deviation)
Takes into effect bias (maximum
allowable set point deviation)
Uses historical data to calculate
ramp up time so as to be at set point
at occupied/unoccupied time
Defines the control set point used
during occupied periods (Viewable
only if Humidity Sensor = Installed/
Determines when to start
Dehumidification when occupied) Defines the control set point used
during unoccupied periods
(Viewable only if Humidity Sensor =
Installed/Determines when to start
Dehumidification when unoccupied)
Defines the control set point used to
start increasing ventilation during
occupied periods (Viewable only if
Ventilation DMP Type = DCV)
Defines the control set point
used to define where the ventilation
will reach its maximum limit during occupied periods (Viewable only if Ventilation DMP Type = DCV/Used
to determine DCV ending control
Defines the start time for an
Defines the ending time of an
Determines if this day is included
Determines if this day is included
Determines if this day is included
Determines if this day is included
Determines if this day is included
Determines if this day is included
Determines if this day is included
Defines the start month of this
Defines the start day of this holiday
Determines the start time for this
Defines the month to end this
Defines the day to end this holiday
Determines the time to end this
point)
occupied period
occupied period
in this schedule
in this schedule
in this schedule
in this schedule
in this schedule
in this schedule
in this schedule
hoilday schedule
schedule
schedule
hoilday schedule
schedule
schedule
52
Page 53
APPENDIX A — WSHP SCREEN OPEN CONFIGURATION (cont)
SCREEN NAME POINT NAME
Fan Mode
Fan On Delay X 0 - 30 sec 10 sec
Fan Off Delay X 0 - 180 sec 45 sec
Heating Enable X Disable/Enable Enable
Cooling Enable X Disable/Enable Enable
Minimum SAT in
Configuration
Unit
Configuration
Configuration
Service
Test
LEGEND
BAS — Building Automation System DCV — Demand Controlled Ventilation IAQ — Indoor Air Quality OAT — Outdoor Air Temperature RH Relative Humidity SAT — Supply Air Temperature SPT — Space Temperature TPI Third Party Integration
Cooling
Maximum SAT in
Heating
Damper Ventilation
Position
DCV Maximum Vent
Position
Filter Alarm Timer X 0 - 9999 hrs 0 hrs Disables Filter Alarm if set to 0
Pushbutton Override X Disable/Enable Enable Enables Override Feature on Rnet sensor
SPT Sensor Set Point
Adjustment
Lockout Cooling if
OAT <
Lockout Heating if
OAT >
Power Fail Restart
Delay
Occupancy Schedules X Disable/Enable Enable Enables unit occupied
Set Point Separation X 2 - 9 F 4 F
Test Mode
Fan Test X Disable/Enable Disable
Fan Speed
Compressor Test X Disable/Enable Disable
Dehumidification Test X Disable/Enable Disable
Testing Compressor
Aux Heating Test X Disable/Enable Disable
O Economizer Test X Disable/Enable Disable
H
2
Preposition OA
Damper
Open Vent
Damper 100%
SAT F Displays SAT
LCWT F
PASSWORD
LEVEL
Admin Password
level access only
Admin Password
level access only
EDITABLE RANGE DEFAULT NOTES
Auto= Intermittant operation during both
occupied and unoccupied periods/
X
X40 - 60 F50 F
X 80 - 140 F 110 F
X 0 - 100% 100%
X 0 - 100% 100%
X Disable/Enable Enable
X -65 - 80 F -65 F
X 35 - 150 F 150 F
X 0 - 600 sec 60 sec Delay before equipment starts
X Disable/Enable Disable
X Disable/Enable Disable
X Disable/Enable Disable Used to test OA damper operation
Auto/Continuous/
Always On
°°
°°
°°
°°
°°
Off/Low Speed/Medium
Speed/High Speed/On
Inactive/Heating/Cooling/
Dehumidify/TimeGard
Wait
°
°
Continuous
Continuous = Intermittant during unoccupied
periods and continuous during occupied
periods/Always on = fan operates
continuously during both occupied and
unoccupied periods
Defines the delay time before the fan begins
to operate after heating or cooling is started
Defines the amount of time the fan will
continue to operate after heating or
cooling is stopped
Provides capability to manually
disable heating operation
Provides capability to manually
disable cooling operation
Defines the minimum acceptable operating
temperature for the Supply Air
Defines the maximum acceptable operating
temperature for the Supply Air
Normally set to 100% if 2 position damper
type or set to minimum ventilation position if
Usually set at 100% - Used to limit maximum
Enables Set Point adjustment capability
Cooling is locked out when OAT is less than
configured value and OAT is actively being
Heating is locked out when OAT is greater
than configured value and OAT is actively
Used to enable test mode. Will automatically
Used to test all fan speeds. Sequences fan
from low to high and operates each speed for
1 minute. Resets to disable on completion
Used to test compressor cooling and heating
operation. Sequences cooling stage 1, then
stage 2, then heating stage 2 and reduces
capacity to stage 1. Operates for 1 minute per
Used to test entering/return air water loop
economizer coil operation. Sequences fan on
and opens economizer coil water valve for 1
minute. Resets to disable on completion
damper type = DCV
damper opening in DCV mode
on Rnet Sensor
broadcast
being broadcast
Used to enforce minimum
set point separation
reset to disable after 1 hour
Displays current fan operation
step. Resets to disable on completion.
Used to test dehumification mode -
Operates for 2 minutes. Resets to
disable on completion.
Displays compressor test mode
Used to test auxiliary heat.
Sequences fan on and enables
heating coil for 1 minute. Resets to
disable on completion
Used to preposition OA damper
actuator to set proper preload
Displays Leaving Condenser
Water Temperature
53
Page 54
APPENDIX A — WSHP SCREEN OPEN CONFIGURATION (cont)
SCREEN NAME POINT NAME
# of Fan Speeds
G Output Type X Fan On/Fan Low Fan On
Compressor Stages X One Stage/Two Stages One Stage
Reversing Valve Type X O type output/B type output O type
Leaving Air Auxiliary
Heat Type
Entering Air Water
Economizer Type
2-Position Water
Val ve Type
Modulating Water
Val ve Type
Ventilation Damper
Ty pe
Damper Actuator Type X (0-10 volt)/(2-10 volt) 0-10 volt
Configuration
Service
Configuration
LEGEND
BAS — Building Automation System DCV — Demand Controlled Ventilation IAQ — Indoor Air Quality OAT — Outdoor Air Temperature RH Relative Humidity SAT — Supply Air Temperature SPT — Space Temperature TPI Third Party Integration
Humidity Sensor X None/Installed None
Factory Dehumidifica-
tion Reheat Coil
Occupancy Input Logic
Condensate Switch
Alarm Delay
Condensate Switch
Alarm State
Minimum Condenser
Water Temperature in
Heating
Maximum Condenser Water Temperature in
Heating
Minimum Condenser
Water Temperature in
Cooling
Maximum Condenser Water Temperature in
Cooling
IAQ sensor
minimum input
IAQ sensor
maximum input
IAQ sensor
minimum output
IAQ sensor
maximum output
PASSWORD
LEVEL
Admin Password level access only
EDITABLE RANGE DEFAULT NOTES
X 1,2,3 3
X
X None/2-Position/Modulating None
X Normally Closed/Normally Open
X Normally Closed/Normally Open
X None/2-Position/DCV None
X None/Installed None
X Occupied Open/Occupied Closed
X 5 - 600 seconds 10 sec
X Alarm OPEN/Alarm CLOSED
X25 - 60 F60 F
X 65 - 100 F 90 F
X30 - 60 F60 F
X 85 - 120 F 95 F
X 0 - 5 ma 4 ma
X 5 - 20 ma 20 ma
X 0 - 9999 ppm 0 ppm
X 0 - 9999 ppm 2000 ppm
None/2-Position HW/1 Stage
Electric/Modulating HW
°°
°°
°°
°°
None
Normally
Closed
Normally
Closed
Occupied CLOSED
Alarm
CLOSED
Used to set number of
fan motor speeds
When set to Fan On, G output is energized when ever any fan speed is active (required for ECM and Fan
control board). When set to Fan
Low, output is only energized for
Determines type of modulating
Set to Installed if factory-installed
Used to determine external occu-
pancy switch contact occupied state
Delay before equipment alarms on
acceptable water loop temperature
acceptable water loop temperature
acceptable water loop temperature
acceptable water loop temperature
Maximum output current (mA) for
Corresponding value in ppm for
Corresponding value in ppm for
Low Speed
Defines the number of stages of compression
Determines reversing valve
signal output type
Determines Auxiliary
Reheat Coil Type
Determines Entering Air
Economizer Coil Type
Determines type of 2-position
water valve used
water valve used
Determines Type of ventilation
damper control to be used
Used to determine ventilation
damper output signal range
(closed - open)
Set to Installed if Humidity
sensor is present
dehumidification reheat coil
is present
high condensate level
Determine Alarm state of
condensate switch input
Determines the minimum
to start heating
Determines the maximum
to start heating
Determines the minimum
to start cooling
Determines the maximum
to start cooling
Minimum output current (mA)
for IAQ sensor
IAQ sensor
minimum output current
maximum output current
54
Page 55
APPENDIX A — WSHP SCREEN OPEN CONFIGURATION (cont)
SCREEN NAME POINT NAME
SPT Occupied Alarm
Hysteresis
SPT Alarm Delay X 0 - 30 min per degree 10 min
SPT Unoccupied Low
Alarm Temperature
SPT Unoccupied High
Alarm Temperature
SAT Low SAT
Alarm Limit
SAT High SAT
Alarm Limit
Condensate Overflow
Alarm Delay
Space Humidity Occupied
High Alarm Limit
Configuration
Alarm
Configuration
Configuration
Linkage
BAS — Building Automation System DCV — Demand Controlled Ventilation IAQ — Indoor Air Quality OAT — Outdoor Air Temperature RH Relative Humidity SAT — Supply Air Temperature SPT — Space Temperature TPI Third Party Integration
Space Humidity Alarm
Delay
Space Humidity Unoccu-
pied High Alarm Limit
IAQ/Ventilation Occupied
High Alarm Limit
IAQ/Ventilation
Alarm Delay
Rnet Sensor SPT Alarm X Ignore/Display Ignore
Rnet Sensor SAT Alarm X Ignore/Display Ignore
Rnet Sensor Compressor
Lockout Alarm
Rnet Sensor Condenser
Water Temperature Alarm
Rnet Sensor Condensate
Overflow Alarm
Rnet Sensor Dirty
Filter Alarm
Rnet Sensor Space
High Humidity Alarm
Loop Control Network
Number
Loop Control Network
Address
Number of Linked Heat
Pumps
LEGEND
PASSWO RD
LEVEL
Admin Password level access only
EDITABLE RANGE DEFAULT NOTES
Defines the hysteresis applied above
X2 - 20 F5 F
X 35 - 90 F 45 F
X 45 - 100 F 95 F
X 15 - 90 F 45 F
X 90 - 175 F 120 F
X 5 - 600 sec 10 sec
X 45% - 100% 100%
X 0 - 30 min per % RH 5 min
X 45% - 100% 100%
X 0 - 9999 ppm 1100 ppm
X 0.1 - 1.0 min per ppm 0.25 min
X Ignore/Display Display
X Ignore/Display Display
X Ignore/Display Display
X Ignore/Display Display
X Ignore/Display Ignore
°°
°°
°°
°°
°°
the cooling and below the heating set
points before an alarm condition will
Used to calculate the delay time before
an alarm is generated after the alarm
Defines the fixed unoccupied
Defines the fixed unoccupied
Defines the fixed minimum
Defines the fixed maximum
Defines the delay time before an alarm
is generated after the alarm condition
Defines the fixed occupied
high space RH alarm limit
Used to calculate the delay time before
an alarm is generated after the alarm
Defines the fixed unnoccupied
high space RH alarm limit
Defines the fixed occupied high
space IAQ/Ventilation alarm limit
Used to calculate the delay time before
an alarm is generated after the alarm
Determines if the SPT alarm is
displayed on the local Rnet sensor
Determines if the SAT alarm is
displayed on the local Rnet sensor
Determines if the Compressor Lockout
alarm is displayed on the local Rnet
Determines if the Condenser Water
Temperature alarm is displayed on the
Determines if the Condensate
Overflow alarm is displayed on the
Determines if the Dirty Filter alarm is
displayed on the local Rnet sensor
Determines if the High Space
RH alarm is displayed on the
occur
condition occurs
ow SPT alarm limit
high SPT alarm limit
SAT alarm limit
SAT alarm limit
occurs
condition occurs
condition occurs
sensor
local Rnet sensor
local Rnet sensor
local Rnet sensor
See TPI
See TPI
See TPI
55
Page 56
56
Page 57
57
Page 58
Copyright 2009 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53500052-01 Printed in U.S.A. Form 50PEC-2SI Pg 58 7-09 Replaces: 50PEC-1SI
Page 59
50PEC UNIT
START-UP CHECKLIST
CUSTOMER:___________________________ JOB NAME: _______________________________________
MODEL NO.:___________________________ SERIAL NO.:____________________ DATE:_________
I. PRE-START-UP
DOES THE UNIT VOLTAGE CORRESPOND WITH THE SUPPLY VOLTAGE AVAILABLE? (Y/N)
HAVE THE POWER AND CONTROL WIRING CONNECTIONS BEEN MADE AND TERMINALS TIGHT? (Y/N)
HAVE WATER CONNECTIONS BEEN MADE AND IS FLUID AVAILABLE AT HEAT EXCHANGER? (Y/N)
HAS PUMP BEEN TURNED ON AND ARE ISOLATION VALVES OPEN? (Y/N)
HAS CONDENSATE CONNECTION BEEN MADE AND IS A TRAP INSTALLED? (Y/N)
IS AN AIR FILTER INSTALLED? (Y/N)
II. START-UP
IS FAN OPERATING WHEN COMPRESSOR OPERATES? (Y/N)
UNIT VOLTAGE — COOLING OPERATION
PHASE AB VOLTS
PHASE AB AMPS
CONTROL VOLTAGE
IS CONTROL VOLTAGE ABOVE 21.6 VOLTS? (Y/N) . IF NOT, CHECK FOR PROPER TRANSFORMER CONNECTION.
TEMPERATURES
FILL IN THE ANALYSIS CHART ATTACHED.
COAXIAL HEAT EXCHANGER
COOLING CYCLE: WATER IN
F WATER OUT F ft wg gpm
HEATING CYCLE: WATER IN
F WATER OUT F ft wg gpm
AIR COIL COOLING CYCLE:
AIR IN
F AIR OUT F
HEATING CYCLE: AIR IN
F AIR OUT F
CL-1
Page 60
HEATING CYCLE ANALYSIS
ft wg
F
SST (SATU RATED SUCTION TEMPERATURE)
AIR
COIL
F
F
EXPANSION
VALV E
LIQUID LINE
COOLING CYCLE ANALYSIS
AIR
COIL
F
F
SUCTION
COMPRESSOR
COAX
F
WATER IN
F
ft wg
WATER OUT
F
ft wg
LOOK UP PRESSURE DROP IN TABLE 12 TO DETERMINE FLOW RATE
DISCHARGE
a50-8453
ft wg
F
SUCTION
COMPRESSOR
SST (SATURATED SUCTION TEMPERATURE)
EXPANSION
VALV E
F
LIQUID LINE
WATER IN
COAX
F
ft wg
F
WATER OUT
a50-8454
ft wg
LOOK UP PRESSURE DROP IN TABLE 12 TO DETERMINE FLOW RATE
DISCHARGE
HEAT OF EXTRACTION (ABSORPTION) OR HEAT OF REJECTION =
FLOW RATE (gpm) x TEMP. DIFF. (DEG. F) x FLUID FACTOR* =
(Btu/hr)
SUPERHEAT = SUCTION TEMPERATURE – SATURATED SUCTION TEMPERATURE
=
(DEG F)
SUBCOOLING = SATURATED CONDENSING TEMPERATURE – LIQUID LINE TEMPERATURE
=
*Use 500 for water, 485 for antifreeze.
(DEG F)
97B0035N06
CUT ALONG DOTTED LINE CUT ALONG DOTTED LINE
Copyright 2009 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53500052-01 Printed in U.S.A. Form 50PEC-2SI CL-2 7-09 Replaces: 50PEC-1SI
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -- - - - - - - - - - - - - - - - - - - -
Loading...