Carrier 50PCH User Manual

AQUAZONE™
50PCH,PCV006-060
Compact High-Efficiency Water Source Heat Pumps
®
with PURON
Refrigerant (R-410A)
Installation, Start-Up, and
Service Instructions
CONTENTS
Page
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . .1,2
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Step 1 — Check Jobsite . . . . . . . . . . . . . . . . . . . . . . . . 2
Step 2 — Check Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
• STORAGE
•PROTECTION
•INSPECT UNIT
Step 3 — Locate Unit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
• FIELD CONVERSION OF DISCHARGE AIR
Step 4 — Mount the Unit . . . . . . . . . . . . . . . . . . . . . . . . . 8
• HORIZONTAL UNITS
• VERTICAL UNITS
Step 5 — Check Duct System . . . . . . . . . . . . . . . . . . . . 8
• SO U N D AT T E NUATI O N
• EXISTING DUCT SYSTEM
Step 6 — Install Condensate Drain . . . . . . . . . . . . . . . 8
• HORIZONTAL UNITS
• VERTICAL UNITS
• VENTING
Step 7 — Pipe Connections . . . . . . . . . . . . . . . . . . . . . . 9
• WATER LOOP APPLICATIONS
• GROUND LOOP APPLICATIONS
• INSTALLATION OF SUPPLY AND RETURN HOSE KIT
Step 8 — Wire Field Power Supply . . . . . . . . . . . . . . 10
• POWER CONNECTION
• SUPPLY VOLTAGE
• 208-VOLT OPERATION
• 460-VOLT OPERATION
Step 9 — Wire Field Controls. . . . . . . . . . . . . . . . . . . . 20
• THERMOSTAT CONNECTIONS
• WATER FREEZE PROTECTION
• AIR COIL FREEZE PROTECTION
• ACCESSORY CONNECTIONS
• WATER SOLENOID VALVES
• WSHP OPEN WIRING
PRE-START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22,23
System Checkout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
PSC Blower Speed Selection . . . . . . . . . . . . . . . . . . 22
FIELD SELECTABLE INPUTS . . . . . . . . . . . . . . . .24,25
Complete C Control Jumper Settings. . . . . . . . . . . 24
Complete C Control DIP Switches. . . . . . . . . . . . . . 24
Deluxe D Control Jumper Settings . . . . . . . . . . . . . 24
Deluxe D Control DIP Switches . . . . . . . . . . . . . . . . 24
Deluxe D Control Accessory Relay
Configurations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Water Valve (Slow Opening) . . . . . . . . . . . . . . . . . . . 25
Outside Air Damper (OAD) . . . . . . . . . . . . . . . . . . . . 25
START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25-33
Operating Limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Scroll Compressor Rotation. . . . . . . . . . . . . . . . . . . . . 26
Unit Start-Up Cooling Mode . . . . . . . . . . . . . . . . . . . . . 26
Page
Unit Start-Up Heating Mode . . . . . . . . . . . . . . . . . . . . . 30
Unit Start-Up with WSHP Open Controls . . . . . . . . 30
Flow Regulation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Flushing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Antifreeze . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Cooling Tower/Boiler Systems . . . . . . . . . . . . . . . . . . 32
OPERATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33-36
Power Up Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Units with Aquazone Complete C Control . . . . . . . 33
Units with Aquazone Deluxe D Control
Units with WSHP Open Multiple Protocol. . . . . . . . 33
COMPLETE C AND DELUXE D BOARD
SYSTEM TEST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36-38
Test Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
WSHP Open Test Mode. . . . . . . . . . . . . . . . . . . . . . . . . . 36
Retry Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Aquazone Deluxe D Control LED Indicators . . . . . 37
SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38-40
Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Water Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Condensate Drain Pans . . . . . . . . . . . . . . . . . . . . . . . . . 38
Refrigerant System. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Compressor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Fan Motors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Condensate Drain Cleaning . . . . . . . . . . . . . . . . . . . . . 38
Air Coil Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Condenser Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Checking System Charge . . . . . . . . . . . . . . . . . . . . . . . 39
Refrigerant Charging. . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Air Coil Fan Motor Removal . . . . . . . . . . . . . . . . . . . . . 40
Replacing the WSHP Open Controller’s
Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . 40-42
Thermistor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Control Sensors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
WSHP Open Controller . . . . . . . . . . . . . . . . . . . . . . . . . . 40
APPENDIX A — WSHP OPEN SCREEN
CONFIGURATION . . . . . . . . . . . . . . . . . . . . . . . . . . 43-48
50PCH,PCV START-UP CHECKLIST . . . . . CL-1, CL-2
IMPORTANT: Read the entire instruction manual before starting installation.
. . . . . . . . . . 33
SAFETY CONSIDERATIONS
Installation and servicing of air-conditioning equipment can be hazardous due to system pressure and electrical compo­nents. Only trained and qualified service personnel should install, repair, or service air-conditioning equipment.
Untrained personnel can perform basic maintenance func­tions of cleaning coils and filters and replacing filters. All other operations should be performed by trained service personnel. When working on air-conditioning equipment, observe precautions in the literature, tags and labels attached to the unit, and other safety precautions that may apply.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53500094-01 Printed in U.S.A. Form 50PC-3SI Pg 1 3-11 Replaces: 50PC-2SI
Improper installation, adjustment, alteration, service, mainte­nance, or use can cause explosion, fire, electrical shock or other conditions which may cause personal injury or property dam­age. Consult a qualified installer, service agency, or your distrib­utor or branch for information or assistance. The qualified in­staller or agency must use factory-authorized kits or accessories when modifying this product. Refer to the individual instruc­tions packaged with the kits or accessories when installing.
Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth for brazing operations. Have fire extinguisher available. Read these instructions thoroughly and follow all warnings or cautions attached to the unit. Consult local building codes and the National Electrical Code (NEC) for special installation requirements.
Understand the signal words — DANGER, WARNING, and CAUTION. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARN­ING signifies hazards that could result in personal injury or death. CAUTION is used to identify unsafe practices, which would result in minor personal injury or product and property damage.
Recognize safety information. This is the safety-alert symbol ( ). When you see this symbol on the unit and in instructions or manuals, be alert to the potential for personal injury.
WARNING
Electrical shock can cause personal injury or death. Before installing or servicing system, always turn off main power to system. There may be more than one disconnect switch. Turn off accessory heater power if applicable.
GENERAL
This Installation and Start-Up Instructions literature is for Aquazone™ water source heat pump systems.
Water source heat pumps (WSHPs) are single-package hori­zontally and vertically mounted units with electronic controls designed for year-round cooling and heating. Aquazone WSHPs are available in the following unit configurations:
• PCH standard efficiency with horizontal airflow and
right, left or back discharge
• PCV standard efficiency with vertical airflow and top
discharge
IMPORTANT: The installation of water source heat pump units and all associated components, parts, and accessories which make up the installation shall be in accordance with the regulations of ALL authorities having jurisdiction and MUST conform to all applicable codes. It is the responsi­bility of the installing contractor to determine and comply with ALL applicable codes and regulations.
INSTALLATION
Step 1 — Check Jobsite —
maintenance instructions are provided with each unit. Before unit start-up, read all manuals and become familiar with the unit and its operation. Thoroughly check out the system before operation. Complete the inspections and instructions listed below to prepare a unit for installation. See Table 1 for unit physical data.
HORIZONTAL UNITS (50PCH) — Horizontal units are designed for indoor installation only. Be sure to allow adequate space around the unit for servicing. See Fig. 1 for overall unit dimensions. Refer to Fig. 2 for an illustration of a typical hori­zontal installation.
VERTICAL UNITS (50PCV) — Vertical units are designed for indoor installations. While vertical units are typically
Installation, operation and
installed in a floor-level closet or a small mechanical room, the unit access guidelines for these units are very similar to those described for horizontal units. See Fig. 3 for overall di­mensions. Refer to Fig. 4 for an example of a typical vertical installation.
CAUTION
To avoid equipment damage, do not use these units as a source of heating or cooling during the construction process. The mechanical components and filters used in these units quickly become clogged with construction dirt and debris which may cause system damage.
Step 2 — Check Unit — Upon receipt of shipment at
the jobsite, carefully check the shipment against the bill of lading. Make sure all units have been received. Inspect the car­ton or crating of each unit, and inspect each unit for damage. Ensure the shipping company makes proper notation of any shortages or damage on all copies of the freight bill. Concealed damage not discovered during unloading must be reported to the shipping company within 15 days of receipt of shipment.
NOTE: It is the responsibility of the purchaser to file all necessary claims with the shipping company.
1. Verify unit is correct model for entering water tempera­ture of job.
2. Be sure that the location chosen for unit installation pro­vides ambient temperatures maintained above freezing. Well water applications are especially susceptible to freezing.
3. Be sure the installation location is isolated from sleeping areas, private offices and other acoustically sensitive spaces.
NOTE: A sound control accessory package may be used to help eliminate sound in sensitive spaces.
4. Check local codes to be sure a secondary drain pan is not required under the unit.
5. Be sure unit is mounted at a height sufficient to provide an adequate slope of the condensate lines. If an appropri­ate slope cannot be achieved, a field-supplied condensate pump may be required.
6. Provide sufficient space for duct connection.
7. Provide adequate clearance for filter replacement and drain pan cleaning. Do not allow piping, conduit, etc. to block filter access.
8. Provide sufficient access to allow maintenance and servicing of the fan and fan motor, compressor and coils. Removal of the entire unit from the closet should not be necessary.
9. Provide an unobstructed path to the unit within the closet or mechanical room. Space should be sufficient to allow removal of unit if necessary.
10. Provide ready access to water valves and fittings, and screwdriver access to unit side panels, discharge collar, and all electrical connections.
11. Where access to side panels is limited, pre-removal of the control box side mounting screws may be necessary for future servicing.
STORAGE — If the equipment is not needed immediately at the jobsite, it should be left in its shipping carton and stored in a clean, dry area of the building or in a warehouse. Units must be stored in an upright position at all times. If carton stacking is necessary, stack units a maximum of 3 high. Do not remove any equipment from its shipping package until it is needed for installation.
PROTECTION — Once the units are properly positioned on the jobsite, cover them with either a shipping carton, vinyl film,
2
or an equivalent protective covering. Cap open ends of pipes stored on the jobsite. This precaution is especially important in areas where painting, plastering, or spraying of fireproof mate­rial, etc. is not yet complete. Foreign material that accumulates within the units can prevent proper start-up and necessitate costly clean-up operations.
Before installing any of the system components, be sure to examine each pipe, fitting, and valve, and remove any dirt or foreign material found in or on these components.
CAUTION
DO NOT store or install units in corrosive environments or in locations subject to temperature or humidity extremes (e.g., attics, garages, rooftops, etc.). Corrosive conditions and high temperature or humidity can significantly reduce performance, reliability, and service life. Always move units in an upright position. Tilting units on their sides may cause equipment damage.
INSPECT UNIT — To prepare the unit for installation, com­plete the procedures listed below:
1. Compare the electrical data on the unit nameplate with ordering and shipping information to verify that the correct unit has been shipped.
2. Verify that the unit is the correct model for the entering water temperature of the job.
3. Do not remove the packaging until the unit is ready for installation.
4. Verify that the refrigerant tubing is free of kinks or dents, and that it does not touch other unit components.
5. Inspect all electrical connections. Be sure connections are clean and tight at the terminals.
6. Loosen compressor bolts until the compressor rides freely on springs. Remove shipping restraints.
7. Remove the four
1
/4 in. shipping bolts from compressor support plate (two bolts on each side) to maximize vibra­tion and sound alternation.
CAUTION
Failure to remove shipping brackets from spring-mounted compressors will cause excessive noise and could cause component failure due to added vibration.
8. Remove any blower support cardboard from inlet of the blower.
9. Locate and verify any accessory kit located in compressor section.
10. Remove any access panel screws that may be difficult to remove once unit is installed.
Table 1 — Physical Data — 50PCH,PCV Units
50PCH,PCV UNIT 006 009 012 015 018 024 030 036 042 048 060 COMPRESSOR (1 each) Rotary Scroll REFRIGERANT TYPE R-410A
Factory Charge (oz) 1718.5233243434750707482
FAN MOTOR AND BLOWER
Fan Motor Type/Speeds PSC/3 Fan Motor (hp) Blower Wheel Size (Dia x W) (in.) 5 x 5 6 x 5 8 x 7 9 x 7 9 x 8 10 x 10 11 x 10
COAX VOLUME (gal.) 0.123 0.143 0.167 0.286 0.450 0.286 0.323 0.323 0.890 0.738 0.939
WATER CONNECTION SIZE FPT (in.) HORIZONTAL
Air Coil Dimensions (H x W)(in.) 10 x 15 16 x 22 20 x 25 20 x 35 Standard Filter - (Qty) 1 in. Throwaway Weight (lb)
Operating 103 105 114 153 158 174 182 203 218 263 278 Packaged 113 115 124 158 163 179 187 209 224 270 285
Corner Weight (lb)*
Left-Front 37 38 42 53 55 62 67 75 81 98 103 Right-Front 24 24 26 36 37 40 41 47 50 60 64 Left-Back 23 23 25 34 35 39 40 44 48 58 61 Right-Back 19 20 21 30 31 33 34 37 39 47 75
VERTICAL
Air Coil Dimensions (H x W)(in.) 10 x 15 20 x 17.25 24 x 17.75 24 x 28.25 Standard Filter - (Qty) 1 in. Throwaway Weight (lb)
Operating 103 105 114 153 158 189 197 203 218 263 278 Packaged 113 115 124 158 163 194 202 209 224 270 285
LEGEND *Front is located at control box end.
FPT — Female Pipe Thread PSC — Permanent Split Capacitor
1
/
1
25
/
(1) 10 x 18 (1) 16 x 25 (1) 18 x 25
(1) 10 x 18 (1) 20 x 20 (1) 24 x 24
1
10
/
10
1
/
1
/
2
1
6
/
NOTES:
1. All units have grommet compressor mountings, and
3
2. Maximum water working pressure is 500 psig.
1
6
/4-in. electrical knockouts.
/
3
4
/
4
3
1
/
4
(1) 20 x 28 or
/
2
(2) 20 x 14
3
/
4
3
/
4
1
(1) 20 x 24,
(1) 20 x 14
(1) 14 x 24,
(1) 18 x 24
1
/2-in. and
1
3
F
RIGHT RETURN STRAIGHT DISCHARGE
FRONT
L
N
O
M
RIGHT RETURN
FRONT
LEFT/STRAIGHT DISCHARGE
CSP
BACK
DISCHARGE
CONDENSATE
3 / 4" FPT
3.3"
[83.8 MM]
0.7"
[17.8 MM]
FRONT-VIEW
E
D
K
J
2
1
1.1 [27.9 MM]
A
CAP
BSP
RIGHT RETURN RIGHT VIEW -
AIR COIL OPENING
AIR COIL
C
T
S
B
R
Q
FRONT
L
N
O
M
LEFT RETURN STRAIGHT DISCHARGE
FRONT
BSP
LEFT RETURN RIGHT RETURN
AIR COIL
CSP
FRONT
LEFT RETURN LEFT VIEW -
AIR COIL OPENING
1.75 [44.5 MM]
C
T
R
QS
B
UNIT HANGER DETAIL
U
V
FRONT
W
MODEL U V W
015-030 43.1 [109.5] 22.2 [56.4] 18.0 [45.7] 036-042 47.1 [119.6] 22.2 [56.4] 18.0 [45.7] 048-060 54.1 [137.4] 26.2 [66.5] 22.0 [55.9]
RIGHT RETURN BACK DISCHARGE
A
AIR COIL SIDE
C
P
N
O
M
CSP
BSP
2 FT [610 MM] SERVICE
ACCESS
FRONT
LEFT RETURN
0.7" [17.8 MM]
3.3" [83.8 MM]
CSP
CONDENSATE
3 / 4" FPT
2 FT [610 MM] SERVICE
ACCESS
AIR COIL SIDE
M
A
C
LEFT RETURN BACK DISCHARGE
N
O
P
BSP
BLOWER
OUTLET
BLOWER
OUTLET
BLOWER
OUTLET
BLOWER
OUTLET
OPTIONAL 2 FT
[610 MM] SERVICE ACCESS
OPTIONAL 2 FT
[610 MM] SERVICE ACCESS
G
H
006-012 34.1 [86.6] 21.1 [53.6] 18.9 [42.9]
NOTE: BLOWER SERVICE PANEL REQUIRES 2 FT SERVICE ACCESS
POWER SUPPLY
3 / 4" [19.1 MM] KNOCKOUT
1 / 2"
[12.7 MM]
KNOCKOUT
LOW VOLTAGE 1 / 2" [12.7 MM]
KNOCKOUT
3
RIGHT/STRAIGHT
DISCHARGE
BACK
DISCHARGE
NOTE: CHOOSE EITHER BACK OR STRAIGHT DISCHARGE
NOTE: CHOOSE EITHER
BACK OR STRAIGHT DISCHARGE
50PCH006-060 UNITS
NOTES:
1. While clear access to all removable panels is not required, installer should take care to comply with all building codes and allow adequate clearance for future field service.
2. Horizontal units shipped with filter bracket only. This bracket should be removed for return duct connection.
3. Discharge flange and hanger brackets are factory installed.
4. Condensate is
3
/4-in. (19.1 mm) FPT copper.
5. Blower service panel requires 2 ft (610 mm) service access.
6. Blower service access is through back panel on left or right discharge units or through panel opposite air coil on back discharge units.
50PCH
UNIT SIZE
OVERALL CABINET
WATER
CONNECTIONS
ELECTRICAL KNOCKOUTS
DISCHARGE CONNECTIONS
DUCT FLANGE
( 0.10 in., 2.5 mm)
RETURN CONNECTION
USING RETURN AIR
OPENING
A
WidthBDepthCHeight
12 34
Size
(IPT)
H
1
/2-in.
J
1
/2-in.
K
3
/4-in.
LMSupply
Height
N
Supply
Width
OPQReturn
Depth
R Return Height
ST
Loop In Loop Out
DE F G
Low
Vol ta ge
Low
Vol ta ge
Power
Supply
006-
012
in. 19.1 34.1 11.1 9.6 1.1 1.5 1.1
1
/
2
8.1 5.1 2.1 0.8 8.9 6.7 8.2 1.3 16.1 9.8 1.1 0.6
cm 48.5 86.6 28.2 24.3 2.7 3.8 2.7 1.3 20.6 13.0 5.4 1.9 22.7 17.0 13.3 3.3 41.0 25.0 2.7 1.5
015
in. 20.1 43.1 17.0 15.1 1.4 3.2 1.4
1
/
2
12.1 9.1 6.1 2.6 13.3 9.9 4.1 1.3 23.0 15.0 1.1 1.0
cm 51.1 109.5 43.2 38.4 3.4 8.1 3.5 1.3 30.8 23.2 15.6 6.6 33.8 25.1 10.5 3.3 58.4 38.1 2.8 2.5
018
in. 20.1 43.1 17.0 15.1 1.4 4.1 1.4
1
/
2
12.1 9.1 6.1 2.6 13.3 9.9 4.1 1.3 23.0 15.0 1.1 1.0
cm 51.1 109.5 43.2 38.4 3.4 10.4 3.5 1.3 30.8 23.2 15.6 6.6 33.8 25.1 10.5 3.3 58.4 38.1 2.8 2.5
024
in. 20.1 43.1 18.3 15.1 1.4 4.4 1.4
3
/
4
12.1 9.1 6.1 2.6 13.3 9.9 4.1 1.3 23.0 16.3 1.1 1.0
cm 51.1 109.5 46.5 38.4 3.4 11.3 3.5 1.9 30.8 23.2 15.6 6.6 33.8 25.1 10.5 3.3 58.4 41.4 2.8 2.5
030
in. 20.1 43.1 18.3 15.1 1.4 3.1 1.4
3
/
4
12.1 9.1 6.1 2.6 13.3 9.9 4.1 1.3 23.0 16.3 1.1 1.0
cm 51.1 109.5 46.5 38.4 3.4 7.8 3.5 1.9 30.8 23.2 15.6 6.6 33.8 25.1 10.5 3.3 58.4 41.4 2.8 2.5
036
in. 20.1 47.1 21.0 15.1 1.4 5.3 1.4
3
/
4
16.1 13.1 10.1 2.5 16.1 11.0 3.0 2.5 25.9 19.0 1.1 1.0
cm 51.1 119.6 53.3 38.4 3.4 13.4 3.5 1.9 41.0 33.3 25.7 6.3 40.9 27.9 7.7 6.4 65.8 48.3 2.8 2.5
042
in. 20.1 47.1 21.0 15.1 1.4 4.4 1.4
3
/
4
16.1 13.1 10.1 2.5 16.1 11.0 3.0 2.5 25.9 19.0 1.1 1.0
cm 51.1 119.6 53.3 38.4 3.4 11.3 3.5 1.9 41.0 33.3 25.7 6.3 40.9 27.9 7.7 6.4 65.8 48.3 2.8 2.5
048
in. 24.1 54.1 21.0 15.1 1.4 4.4 1.4 1 16.1 13.1 10.1 3.7 16.1 13.7 4.1 1.3 35.9 19.0 1.1 1.0 cm 61.2 137.4 53.3 38.4 3.4 11.1 3.5 2.5 41.0 33.3 25.7 9.5 41.0 34.8 10.3 3.2 91.2 48.3 2.8 2.5
060
in. 24.1 54.1 21.0 15.1 1.4 3.8 1.4 1 16.1 13.1 10.1 1.7 18.1 13.7 4.1 1.3 35.9 19.0 1.1 1.0 cm 61.2 137.4 53.3 38.4 3.4 9.7 3.5 2.5 41.0 33.3 25.7 4.4 46.0 34.8 10.3 3.2 91.2 48.3 2.8 2.5
Fig. 1 — 50PCH Unit Dimensions
a50-8695
LEGEND
BSP — Blower Service Panel CAP — Control Access Panel CSP — Compressor Service Panel FPT — Female Pipe Thread
4
Return Loop
Fig. 2 — Typical Installation — 50PCH Units
UNIT HANGER ISOLATION DETAIL
a50-7842ef
Field-supplied transition to minimize pressure loss
Supply Air
Insulated supply duct with at least one 90 degree elbow to reduce air noise (field supplied)
Flexible Connection
Accessory Electric Heat (if applicable)
3/8" Threaded
Rod (by others)
Filter Access
Power Wiring
Unit Power Disconnect
Unit Hanger
3/8" threaded rods
(by others)
Return Air (Ductwork not shown)
Unit Power
Thermostat
Wiring
Supply Loop
ater In
W
Water Out
Accessory stainless steel braid hose with integral “J” swivel
Ball Valve Accessory with optional integral P/T plug (typical for supply and return piping)
Balancing Valve (Field installed and calibrated accessory)
Low Pressure Drop Water Control Valve (optional) or (field-installed accessory)
Water Out Water In
Vibration Isolator
(white compressor end
and red blower end)
Washer
(by others)
Double Hex Nuts
(by others)
Integral hanger support­pre-attached in factory
5
O
50PCV006-060 UNITS
NOTES:
1. Shaded areas are recommended service areas. Installer should take care to comply with all building codes and allow adequate clearance for future field service.
2. Front and side access is preferred for service access. However, all components may be serviced from the front access panel if side access is not available except on 50PCV009­030 with front return.
3. Discharge flange is field installed.
4. Condensate is 3/4 in. (19.1 mm) FPT.
5. Units shipped with filter rails. These rails should be removed for return duct connection. See WSHP Accessory Price Page for accessory air filter frame with duct collar.
50PCV
UNIT SIZE
OVERALL CABINET WATER CONNECTIONS ELECTRICAL KNOCKOUTS
DISCHARGE CONNECTION
DUCT FLANGE INSTALLED
(0.10 in., 2.5 mm)
RETURN CONNECTION
USING RETURN AIR
OPENING
A
WidthBDepthCHeight
12 3
Size
(IPT)
J
1/2-in.
(1.3 cm)
K
1/2-in.
(1.3 cm)
L
3/4-in.
(1.3 cm)
MNOSupply
Width
P
Supply
Depth
QRSReturn
Depth
T Return Height
U
DE FG
HI
Low
Vol ta ge
Low
Vol ta ge
Power
Supply
Loop In Loop Out
006-
012
in. 19.1 19.1 22.0 1.4 1.6 9.5 1.6 6.1 1.61/
2
2.9 5.9 8.9 8.9 5.1 9.0 9.0 5.5 2.1 16.2 9.9 0.7
cm 48.5 48.5 55.9 3.6 4.1 24.1 4.3 15.6 4.1 1.3 7.3 14.9 22.5 22.7 12.9 22.9 22.9 14.0 5.3 41.1 25.1 1.9
015
in. 21.5 21.5 39.0 1.9 1.4 13.8 1.4 8.1 1.4
1
/
2
4.1 7.1 10.1 6.4 3.8 14.0 14.0 5.3 2.3 18.3 20.9 0.7
cm 54.6 54.6 99.1 4.8 3.6 35.1 3.6 20.6 3.6 1.3 10.5 18.1 25.7 16.1 9.5 35.6 35.6 13.6 5.8 46.5 53.1 1.9
018
in. 21.5 21.5 39.0 1.9 1.4 12.9 1.4 8.1 1.41/
2
4.1 7.1 10.1 6.4 3.8 14.0 14.0 5.3 2.3 18.3 20.9 0.7
cm 54.6 54.6 99.1 4.8 3.6 32.8 3.6 20.6 3.6 1.3 10.5 18.1 25.7 16.1 9.5 35.6 35.6 13.6 5.8 46.5 53.1 1.9
024
in. 21.5 21.5 40.0 1.9 1.4 13.8 1.4 8.1 1.4
3
/
4
4.1 7.1 10.1 6.4 3.8 14.0 14.0 5.3 2.3 18.3 20.9 0.7
cm 54.6 54.6 101.6 4.8 3.6 35.1 3.6 20.6 3.6 1.9 10.5 18.1 25.7 16.1 9.5 35.6 35.6 13.6 5.8 46.5 53.1 1.9
030
in. 21.5 21.5 40.0 1.9 1.4 15.2 1.4 8.1 1.4
3
/
4
4.1 7.1 10.1 6.4 3.8 14.0 14.0 5.3 2.3 18.3 20.9 0.7
cm 54.6 54.6 101.6 4.8 3.6 38.6 3.6 20.6 3.6 1.9 10.5 18.1 25.7 16.1 9.5 35.6 35.6 13.6 5.8 46.5 53.1 1.9
036
in. 21.5 26.0 45.0 1.9 1.4 15.7 1.4 8.1 1.43/
4
4.1 7.1 10.1 6.4 3.8 14.0 14.0 5.1 2.3 22.8 23.9 0.7
cm 54.6 66.0 114.3 4.8 3.6 39.9 3.6 20.6 3.6 1.9 10.5 18.1 25.7 16.1 9.5 35.6 35.6 13.1 5.8 57.9 60.7 1.9
042
in. 21.5 26.0 45.0 1.9 1.4 16.6 1.4 8.1 1.4
3
/
4
4.1 7.1 10.1 6.4 3.8 14.0 14.0 5.1 2.3 22.8 23.9 0.7
cm 54.6 66.0 114.3 4.8 3.6 42.0 3.6 20.6 3.6 1.9 10.5 18.1 25.7 16.1 9.5 35.6 35.6 13.1 5.8 57.9 60.7 1.9
048
in. 24.0 32.5 46.0 1.9 1.4 16.6 1.4 8.1 1.4 1 4.1 7.1 10.1 6.9 7.3 16.0 18.0 5.1 2.3 29.3 22.5 0.7 cm 61.0 82.6 116.8 4.8 3.6 42.2 3.6 20.6 3.6 2.5 10.5 18.1 25.7 17.4 18.4 40.6 45.7 13.1 5.8 74.4 57.0 1.9
060
in. 24.0 32.5 46.0 1.9 1.4 16.7 1.4 8.1 1.4 1 4.1 7.1 10.1 6.9 7.3 16.0 18.0 5.1 2.3 29.3 22.5 0.7 cm 61.0 82.6 116.8 4.8 3.6 42.4 3.6 20.6 3.6 2.5 10.5 18.1 25.7 17.4 18.4 40.6 45.7 13.1 5.8 74.4 57.0 1.9
Fig. 3 — 50PCV Unit Dimensions
LEGEND
ASP — Alternate Service Panel BSP — Blower Service Panel CAP — Control Access Panel CSP — Compressor Service Panel FPT — Female Pipe Thread HV — High Voltage LV — Low Voltage
a50-8696
Q
AIR COIL AND FRONT SIDE
TOP VIEW-FRONT RETURN
FRONT
O
Q
TOP VIEW-RIGHT RETURN
R
U
P
P
AIR COIL SIDE
S
N
N
N
TOP VIEW-LEFT RETURN
U
B
P
AIR COIL SIDE
S
O
FRONT
A
M
R
FIELD INSTALLED
STANDARD FILTER BRACKET
AIR COIL
CSP
2 FT [610 MM]
DISCHARGE FLANGE
SERVICE
BSP
CAP
ISOMETRIC
VIEW
ACCESS PANELS
ASP
1.00 [25.4 MM]
OPTIONAL 2 FT [610 MM] SERVICE ACCESS LEFT RTN
(RIGHT RTN OPPOSITE
SIDE)
AIR COIL
T
C
T
C
BACKFRONT
RIGHT RETURN RIGHT VIEW
- AIR COIL OPENING
LEFT RETURN LEFT VIEW
- AIR COIL OPENING
AIR COIL
BSP
G
POWER SUPPLY 3/4" [19.1 MM] HV
KNOCKOUT
LOW VOLTAGE
1/2" [12.7 MM] LV
CSPCSP
FRONTBACK
KNOCKOUT
LOW VOLTAGE
1/2" [12.7 MM] LV
KNOCKOUT
CSP
J
2
CAP
3
L
K
1
FRONT-VIEW
E
I
D
6
CONDENSATE 3/4" FPT
F
H
Step 3 — Locate Unit — The following guidelines
Return
Air
Power
Thermostat Wiring
Compressor Access Panel
Balancing Valve (field installed and calibrated accessory)
Field-supplied stainless steel braid hose with integral “ J” swivel
Low Pressure
Drop Water Control Valve (optional) (field-installed accessory)
Ball Valve with optional integral P/T plug (typical for supply and return piping)
Water Out
Water In
Building
Loop
Supply Air
Flexible Connection
NOTE: Ball valve with integral pressure temperature plug recommended.
Fig. 4 — Typical Vertical Installation of 50PCV Unit
a50-6803ef
Return Air
Remove Screws
Return Air
Rotate
Move to Side
Side Discharge
Return Air
Discharge Air
Drain
Back Discharge
Replace Screws
Water
Connection End
Water
Connection End
Water
Connection End
Fig. 5 — Conversion Left Return,
Side Discharge to Back Discharge
Water
Connection End
Supply Duct
Return Air
Water
Connection End
Drain
Return Air
Discharge Air
Side Discharge
Back Discharge
Fig. 6 — Conversion Right Return, Side Discharge to Back Discharge
a50-6257ef
should be considered when choosing a location for a WSHP:
• Units are for indoor use only.
• Locate in areas where ambient temperatures are between 40 F and 100 F and relative humidity is no greater than 75%.
• Provide sufficient space for water, electrical and duct connections.
• Locate unit in an area that allows easy access and removal of filter and access panels.
• Allow enough space for service personnel to perform maintenance.
• Return air must be able to freely enter the space if unit needs to be installed in a confined area such as a closet.
• Install the unit on a piece of rubber, neoprene or other mounting pad material for sound isolation. The pad should be at least thickness. Extend the pad beyond all four edges of the
3
/8 in. [10 mm] to 1/2 in. [13 mm] in
unit.
• Provide adequate clearance for filter replacement and drain pan cleaning. Do not block filter access with pip­ing, conduit or other materials. Refer to Fig. 1 and 3 for dimensional data.
• Provide access for fan and fan motor maintenance and for servicing the compressor and coils without removing the unit.
• Provide an unobstructed path to the unit within the closet or mechanical room. Space should be sufficient to allow removal of the unit, if necessary.
• In limited side access installations, pre-removal of the control box side mounting screws will allow control box removal for future servicing.
• Provide access to water valves and fittings and screw­driver access to the unit side panels, discharge collar and all electrical connections.
NOTE: Correct placement of the horizontal unit can play an important part in minimizing sound problems. Since duct­work is normally applied to these units, the unit can be placed so that the principal sound emission is outside the oc­cupied space in sound-critical applications. A fire damper may be required by the local code if a fire wall is penetrated.
FIELD CONVERSION OF DISCHARGE AIR — The dis­charge air of the 50PCH horizontal units can be converted
between side and back discharge in the field. The conversion process is the same for right and left return configurations. See Fig. 5 and 6.
NOTE: It is not possible to convert return air between left or right return models in the field due to refrigerant piping changes.
Preparation
— The unit should be on the ground in a well lit area for conversion. Hung units should be taken down to ground level before converting.
7
Side to Back Discharge Conversion
Fig. 7 — Horizontal Hanger Bracket
(Factory Installed)
a50-8489
Vibration Absorption Pad
Fig. 8 — 50PCV Unit Mounted with
Vibration Absorption Pad
a50-6259ef
Fig. 9 — Horizontal Unit Pitch
1/4” Pitch for Drainage
Drain Connection
Pitch Toward Drain
a50-6260ef
1. Remove screws to free the top and discharge panels. See Fig. 5.
2. Remove the access panel and set aside.
3. Lift the discharge panel from side of unit and rotate it to back using care not to damage blower wiring.
4. Check blower wire routing and connections for undue tension or contact with sheet metal edges. Re-route if necessary.
5. Check refrigerant tubing for contact with other compo­nents. Adjust if necessary.
6. Reinstall top panel using screws set aside in Step 1.
NOTE: Location for some screws at bottom of discharge panel may have to be changed.
7. Manually spin fan wheel to check for obstructions. Adjust for any obstruction found.
8. Replace access panel.
Back to Side Discharge Conversion
— Follow instructions above for Side to Back Discharge Conversion, noting the panels would be reversed.
Step 4 — Mount the Unit
HORIZONTAL UNITS (50PCH) — Horizontal units should be mounted using the factory-installed hangers. Proper attachment of hanging rods to building structure is critical for safety. See Fig. 2 and 7. Rod attachments must be able to support the weight of the unit. See Table 1 for unit operating weights.
COMPRESSOR
SECTION
AIR HANDLER
SECTION
NOTE: Some codes require the use of a secondary drain pan under vertical units. Check local codes for more information.
Step 5 — Check Duct System — Size the duct sys-
tem to handle the design airflow quietly.
NOTE: Depending on the unit, the fan wheel may have a ship­ping support installed at the factory. This must be removed before operating unit.
SOUND ATTENUATION — To eliminate the transfer of vibration to the duct system, a flexible connector is recom­mended for both discharge and return air duct connections on metal duct systems. The supply and return plenums should in­clude internal duct liner of fiberglass or be made of duct board construction to maximize sound attenuation of the blower. Installing the WSHP unit to uninsulated ductwork in an uncon­ditioned space is not recommended since it will sweat and adversely affect the unit’s performance.
To reduce air noise, at least one 90-degree elbow could be included in the supply and return air ducts, provided system performance is not adversely impacted. The blower speed can also be changed in the field to reduce air noise or excessive air­flow, provided system performance is not adversely impacted.
EXISTING DUCT SYSTEM — If the unit is connected to existing ductwork, consider the following:
• Verify that the existing ducts have the proper capacity to
handle the unit airflow. If the ductwork is too small,
install larger ductwork.
• Check existing ductwork for leaks and repair as
necessary. NOTE: Local codes may require ventilation air to enter the
space for proper indoor air quality. Hard-duct ventilation may be required for the ventilating air supply. If hard ducted venti­lation is not required, be sure that a proper air path is provided for ventilation air to unit to meet ventilation requirement of the space.
Step 6 — Install Condensate Drain
HORIZONTAL UNITS (50PCH) — Slope the unit toward the drain at a sible to meet the required pitch, install a condensate pump at the unit to pump condensate to building drain.
1
/4 in. drop at drain end. See Fig. 9. If it is not pos-
VERTICAL UNITS (50PCV) — Vertical units are available in left or right return air configurations. See Fig. 3. Mount the unit on a vibration absorption pad slightly larger than the entire base to minimize vibration transmission. It is not necessary to mount the unit on the floor. See Fig. 8.
Horizontal units are not internally trapped, therefore an ex­ternal trap is necessary. Install each unit with its own individual trap and means to flush or blow out the condensate drain line. Do not install units with a common trap or vent. For typical condensate connections see Fig. 10.
NOTE: Never use a pipe size smaller than the connection. VERTICAL UNITS (50PCV) — Each unit uses a condensate
hose inside all cabinets as a trapping loop, therefore an external trap is not necessary and should not be used. See Fig. 11.
8
Each unit must be installed with its own individual vent and
NOTE: Trap should be deep enough to offset maximum unit static difference. A 4-in. trap is recommended.
Fig. 10 — Trap Condensate Drain
a50-6261tf
Alternate Condensate Location
Vent
1/4” per foot slope to drain
3/4” Copper FPT/PVC
Water Connections
1/2”
1/2”
3/4” PVC
NOTE: Unit does not need to be sloped toward drain.
Fig. 11 — Vertical Condensate Connection
a50-6262ef
means to flush or blow out the condensate drain line. Do not in­stall units with a common trap or vent.
VENTING — Install a vent in the condensate line of any application that may allow dirt or air to collect in the line. Con­sider the following:
• Always install a vent where an application requires a long horizontal run.
• Always install a vent where large units are working against higher external static pressure and to allow proper drainage for multiple units connected to the same condensate main.
• Be sure to support the line where anticipated sagging from the condensate or when “double trapping” may occur.
• If condensate pump is present on unit, be sure drain con­nections have a check valve to prevent back flow of con­densate into other units.
Step 7 — Pipe Connections — Depending on the
application, there are 3 types of WSHP piping systems to choose from: water loop, ground-water and ground loop. Refer to Piping Section of Carrier System Design Manual for addi­tional information.
thread fittings for water connections to prevent annealing and out-of-round leak problems which are typically associated with high temperature brazed connections. Refer to Table 1 for con­nection sizes. When making piping connections, consider the following:
• Use a backup wrench when making screw connections to
All WSHP units use low temperature soldered female pipe
unit to prevent internal damage to piping.
• Insulation may be required on piping to avoid condensa­tion in the case where fluid in loop piping operates at temperatures below dew point of adjacent air.
• Piping systems that contain steel pipes or fittings may be subject to galvanic corrosion. Dielectric fittings may be used to isolate the steel parts of the system to avoid galvanic corrosion.
WATER LOOP APPLICATIONS — Water loop applications usually include a number of units plumbed to a common pip­ing system. Maintenance to any of these units can introduce air into the piping system. Therefore, air elimination equipment comprises a major portion of the mechanical room plumbing.
The flow rate is usually set between 2.25 and 3 gpm per ton
of cooling capacity. For proper maintenance and servicing, pressure-temperature (P/T) ports are necessary for temperature and flow verification.
In addition to complying with any applicable codes, consid-
er the following for system piping:
• Piping systems using water temperatures below 50 F require
1
/2-in. closed cell insulation on all piping surfaces
to eliminate condensation.
• Avoid all plastic to metal threaded fittings due to the potential to leak. Use a flange fitted substitute.
• Teflon tape thread sealant is recommended to minimize internal fouling of the heat exchanger.
• Use backup wrench. Do not overtighten connections.
• Route piping to avoid service access areas to unit.
• Flush the piping system prior to operation to remove dirt and foreign materials from the system.
GROUND-LOOP APPLICATIONS — Temperatures be­tween 25 and 110 F and a cooling capacity of 2.25 to 3 gpm of flow per ton is recommended. In addition to complying with any applicable codes, consider the following for system piping:
• Limit piping materials to only polyethylene fusion in the buried sections of the loop.
• Do not use galvanized or steel fittings at any time due to corrosion.
• Avoid all plastic to metal threaded fittings due to the poten­tial to leak. Use a flange fitted substitute.
• Do not overtighten connections.
• Route piping to avoid service access areas to unit.
• Use pressure-temperature (P/T) plugs to measure flow of pressure drop.
INSTALLATION OF SUPPLY AND RETURN HOSE KIT — Follow these piping guidelines.
1. Install a drain valve at the base of each supply and return riser to facilitate system flushing.
2. Install shutoff/balancing valves and unions at each unit to permit unit removal for servicing.
3. Place strainers at the inlet of each system circulating pump.
4. Select the proper hose length to allow slack between con­nection points. Hoses may vary in length by +2% to –4% under pressure.
5. Refer to Table 2. Do not exceed the minimum bend radius for the hose selected. Exceeding the minimum bend radi­us may cause the hose to collapse, which reduces water flow rate. Install an angle adapter to avoid sharp bends in the hose when the radius falls below the required minimum.
NOTE: Piping must comply with all applicable codes.
Table 2 — Metal Hose Minimum Bend Radii
HOSE DIAMETER (in.) MINIMUM BEND RADII (in.)
1
/
2
3
/
4
15
21/
2
4
1
/
2
9
Rib Crimped
Length
(2 ft Length Standard)
Swivel Brass Fitting
Brass Fitting
MPT
Fig. 12 — Supply/Return Hose Kit
A50-7734
Insulation is not required on loop water piping except where the piping runs through unheated areas or outside the building or when the loop water temperature is below the minimum ex­pected dew point of the pipe ambient. Insulation is required if loop water temperature drops below the dew point.
IMPORTANT: Do not bend or kink supply lines or hoses.
Pipe joint compound is not necessary when Teflon* thread­ed tape is pre-applied to hose assemblies or when flared-end connections are used. If pipe joint compound is preferred, use compound only in small amounts on the male pipe threads of the fitting adapters. Prevent sealant from reaching the flared surfaces of the joint.
NOTE: When anti-freeze is used in the loop, assure that it is compatible with Teflon tape or pipe joint compound employed.
Maximum allowable torque for brass fittings is 30 ft-lb. If a torque wrench is not available, tighten finger-tight plus one quarter turn. Tighten steel fittings as necessary.
Optional pressure-rated hose assemblies designed specifi­cally for use with Carrier units are available. Similar hoses can be obtained from alternate suppliers. Supply and return hoses are fitted with swivel-joint fittings at one end to prevent kink­ing during installation.
CAUTION
Backup wrench is required when tightening water connec­tions to prevent water line damage. Failure to use a backup wrench could result in equipment damage.
Refer to Fig. 12 for an illustration of a supply/return hose kit. Male adapters secure hose assemblies to the unit and risers. Install hose assemblies properly and check them regularly to avoid system failure and reduced service life.
Step 8 — Wire Field Power Supply
WARNING
To avoid possible injury or death due to electrical shock, open the power supply disconnect switch and secure it in an open position during installation.
CAUTION
Use only copper conductors for field-installed electrical wiring. Unit terminals are not designed to accept other types of conductors. Failure to follow this safety precaution could lead to equipment damage.
All field installed wiring, including the electrical ground, MUST comply with the National Electrical Code (NEC) as well as applicable local codes. In addition, all field wiring must conform to the Class II temperature limitations described in the NEC.
*Registered trademark of E. I. du Pont de Nemours and Company.
Refer to unit wiring diagrams Fig. 13-20 for a schematic of the field connections, which must be made by the installing (or electrical) contractor. Refer to Table 3 for fuse sizes.
Consult the unit wiring diagram located on the inside of the compressor access panel to ensure proper electrical hookup. The installing (or electrical) contractor must make the field connections when using field-supplied disconnect.
Operating voltage must be the same voltage and phase as shown in Table 3.
Make all final electrical connections with a length of flexi­ble conduit to minimize vibration and sound transmission to the building.
POWER CONNECTION — Make line voltage connection by connecting the incoming line voltage wires to the L side of the CC terminal as shown in Fig. 21. See Table 3 for cor­rect wire and maximum overcurrent protection sizing.
SUPPLY VOLTAGE — Operating voltage to unit must be within voltage range indicated on unit nameplate.
On 3-phase units, voltages under load between phases must be balanced within 2%. Use the following formula to deter­mine the percentage voltage imbalance:
% Voltage Imbalance
= 100 x
max voltage deviation from average voltage
average voltage
Example: Supply voltage is 460-3-60.
AB = 452 volts BC = 464 volts AC = 455 volts
Average Voltage =
452 + 464 + 455
3
1371
=
3
= 457
Determine maximum deviation from average voltage: (AB) 457 – 452 = 5 v
(BC) 464 – 457 = 7 v (AC) 457 – 455 = 2 v
Maximum deviation is 7 v. Determine percent voltage imbalance.
% Voltage Imbalance = 100 x
7
457
= 1.53%
This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.
Operation on improper line voltage or excessive phase imbalance constitutes abuse and may cause damage to electri­cal components.
NOTE: If more than 2% voltage imbalance is present, contact your local electric utility.
208-VOLT OPERATION — All 208-230 volt units are factory wired for 208 volts. The transformers may be switched to 230-volt operation by switching the red (208 volt) wire with the orange (230 volt) wire at the L1 terminal.
460-VOLT OPERATION — Units using 460-v and internal secondary pump will require a neutral wire from the supply side in order to feed accessory with 265-v.
10
NOTES:
1. Compressor and blower motor thermally protected internally.
2. All wiring to the unit must comply with NEC and local codes.
3. Transformer for 208/230 v will be connected for 208 v operation. For
230 v operation, switch RED wire to ORG wire. Insulate open end of
RED lead. Transformer is energy limiting or may have circuit breaker.
4. FP1 thermistor provides freeze protection for water. When using anti-
freeze solutions, cut JW3 jumper.
5. Typical heat pump thermostat wiring shown. Refer to thermostat installa-
tion instructions for wiring to the unit. Wire “Y” from thermostat to “Y”
Complete C when a motorized valve is not used. “O” terminal is not used
in cooling only applications. Thermostat wiring must be Class 1 and volt-
age rating equal to or greater than unit supply voltage.
6. 24-v alarm signal shown. For dry alarm contact, cut JW1 jumper and for
anti-freeze solutions, cut JW3 jumper.
7. Transformer secondary ground via green wire with yellow stripe from “C”
terminal to control box.
8. Hot water generator pump only in models with hot water generation and
internal pump option.
9. For auxiliary staging options, consult electric heat installation manual.
10. Fan motors factory wired for medium speed. For high or low speed,
remove BLU wire from fan motor speed trap “M” and connect to “H” for
high speed or “L” for low speed.
11. Aquastat is with unit and must be wired in series with the hot leg to the
pump. Aquastat is rated for voltage up to 277 v.
a50-8490
Fig. 13 — 50PCH,PCV Units with Complete C Controller, Single-Phase
Complete C
*Optional.
AL Alarm Relay Contacts
BM Blower Motor
BMC Blower Motor Capacitor
BR Blower Relay
CAP Compressor Capacitor
CB Circuit Breaker
CC Compressor Contactor
CO Sensor, Condensate Overflow
FP1 Sensor, Low Temperature Protection Water Coil
FP2 Sensor, Low Temperature Protection Air Coil
HP High-Pressure Switch
HPWS — High-Pressure Water Switch
HWTS — High Leaving Water Temperature Switch
JW1 Jumper, Alarm
LEGEND
LOC Loss of Charge Pressure Switch
MV Motorized Valve
MVES Motorized Valve End Switch
NEC National Electrical Code
P1 Field Wiring Terminal Block
PSC Permanent Split Capacitor
RV Reversing Valve Coil
TRANS — Transformer
TXV Thermostatic Expansion Valve
Field Line Voltage Wiring
Field Low Voltage Wiring
Printed Circuit Trace
Optional Wiring
Relay/Contactor Coil
Condensate Pan
Solenoid Coil
Temperature Switch
Thermistor
Ground
Wire Nut
11
NOTES:
1. Compressor thermally protected internally.
2. All wiring to the unit must comply with NEC and local codes.
3. Transformer is wired to 208-v RED lead for 208-3-60 units. For 230-3-60,
switch RED and ORG leads at L1 and insulate RED lead. Transformer is
energy limiting or may have circuit breaker.
4. FP1 thermistor provides freeze protection for water. When using anti-
freeze solutions, cut JW3 jumper.
5. Refer to microprocessor control, LON, or thermostat installation instruc-
tions for wiring to the unit. Wire “Y” from thermostat to “Y1” Deluxe D
when motorized valve is not used. Thermostat wiring must be Class 1
and voltage rating equal to or greater than unit supply voltage. Heat/cool
thermostats not compatible with motorized water valve.
6. 24-v alarm signal shown. For dry alarm contact, cut JW4 jumper and dry
contact will be available between AL1 and AL2.
7. Transformer secondary ground via green wire with yellow stripe from “C”
terminal to control box.
8. Blower motor is factory wired for medium and high speeds. For any other
combination of speeds, attach black wire to the higher of the two desired
speed taps and the blue wire to the lower of the two desired speed taps.
a50-8491
Fig. 14 — 50PCH,PCV Units with Deluxe D Controller, Three-Phase (208/230 V)
LEGEND
Relay/Contactor Coil
Condensate Pan
Solenoid Coil
Thermistor
Ground
Wire Nut
*Optional.
AL Alarm Relay Contacts
BM Blower Motor
BMC Blower Motor Capacitor
CB Circuit Breaker
CC Compressor Contactor
CO Sensor, Condensate Overflow
FP1 Sensor, Low Temperature Protection Water Coil
FP2 Sensor, Low Temperature Protection Air Coil
HP High-Pressure Switch
HPWS — High-Pressure Water Switch
HWTS — High Leaving Water Temperature Switch
JW1 Jumper, Alarm
LOC Loss of Charge Pressure Switch
MV Motorized Valve
MVES Motorized Valve End Switch
NEC National Electrical Code
P1 Field Wiring Terminal Block
RVS Reversing Valve Solenoid
TRANS — Transformer
TXV Thermostatic Expansion Valve
Field Line Voltage Wiring
Field Low Voltage Wiring
Printed Circuit Trace
Optional Wiring
Deluxe D
12
NOTES:
1. Compressor thermally protected internally.
2. All wiring to the unit must comply with NEC and local codes.
3. Transformer is wired to 460-v BLK/RED lead for 460-3-60 units or 575-v
GRY lead for 575-3-60 units. Transformer is energy limiting or may have
circuit breaker.
4. FP1 thermistor provides low temperature protection for water. When
using antifreeze solutions, cut JW3 jumper.
5. Refer to microprocessor control, LON, or thermostat installation instruc-
tions for wiring to the unit. Wire “Y” from thermostat to “Y1” Deluxe D
when motorized valve is not used. Thermostat wiring must be Class 1
and voltage rating equal to or greater than unit supply voltage. Heat/cool
thermostats not compatible with motorized water valve.
6. 24-v alarm signal shown. For dry alarm contact, cut JW4 jumper and dry
contact will be available between AL1 and AL2.
7. Transformer secondary ground via green wire with yellow stripe from “C”
terminal to control box.
8. Blower motor is factory wired for medium and high speeds. For any
other combination of speeds, attach black wire to the higher of the two
desired speed taps at the motor. Attach the blue wire to the lower of the
two desired speed taps.
9. Blower motor is factory wired for high and low speeds. No other combi-
nation of speeds is available.
10. The 460-v units using an internal secondary pump will require a neutral
wire from the supply side in order to feed the accessory with 265-v.
a50-8492
Fig. 15 — 50PCH,PCV Units with Deluxe D Controller, Three-Phase (460 V)
Deluxe D
LEGEND
Relay/Contactor Coil
Condensate Pan
Solenoid Coil
Thermistor
Ground
Wire Nut
*Optional.
AL Alarm Relay Contacts
BM Blower Motor
BMC Blower Motor Capacitor
BR Blower Relay
CB Circuit Breaker
CC Compressor Contactor
CO Sensor, Condensate Overflow
FP1 Sensor, Low Temperature Protection Water Coil
FP2 Sensor, Low Temperature Protection Air Coil
HP High-Pressure Switch
HPWS — High-Pressure Water Switch
JW1 Clippable Field Selection Jumper
LOC Loss of Charge Pressure Switch
MV Motorized Valve
MVES Motorized Valve End Switch
NEC National Electrical Code
P1 Field Wiring Terminal Block
PB Power Block
RVS Reversing Valve Solenoid
TRANS — Transformer
TXV Thermostatic Expansion Valve
Field Line Voltage Wiring
Field Low Voltage Wiring
Printed Circuit Trace
Optional Wiring
13
Fig. 16 — 50PCH,PCV Units with Complete C and LON Controller (460 V)
a50-8493
LEGEND
AL Alarm Relay Contacts
BM Blower Motor
BMC Blower Motor Capacitor
BR Blower Relay
CB Circuit Breaker
CC Compressor Contactor
CO Sensor, Condensate Overflow
FP1 Sensor, Low Temperature Protection, Water Coil
FP2 Sensor, Low Temperature Protection, Air Coil
HP High-Pressure Switch
HPWS — High-Pressure Water Switch
JW1 Clippable Field Selection Jumper
LOC Loss of Charge Pressure Switch
LON Local Operating Network
MV Motorized Valve
MVES — Motorized Valve End Switch
NEC National Electrical Code
*Optional Wiring.
P1 Field Wiring Terminal Block
RVS Reversing Valve Solenoid
TRANS — Transformer
TXV Thermostatic Expansion Valve
Field Line Voltage Wiring
Field Low Voltage Wiring
Printed Circuit Trace
Optional Wiring
Relay/Contactor Coil
Condensate Pan
Solenoid Coil
Temperature Switch
Thermistor
Ground
Wire Nut
Relay Contacts - N.C.
Relay Contacts - N.O.
Low Pressure Switch
High Pressure Switch
Splice Cap
Circuit Breaker
NOTES:
1. Compressor and blower motor thermally protected internally.
2. All wiring to the unit must comply with NEC and local codes.
3. Transformer is wired to 460 v BLK/RED lead for 460-3-60 units. Trans-
former is energy limiting or may have circuit breaker.
4. FP1 thermistor provides low temperature protection for water. When
using antifreeze solutions, cut JW3 jumper.
5. Refer to microprocessor control, LON, or thermostat installation
instructions for wiring to the unit. Wire “N01” from LON to “Y1” Com-
plete C when a motorized valve is not used. Low voltage wiring must
be Class 1 and voltage rating equal to or greater than unit supply
voltage.
6. Factory cut JW1 jumper. Dry contact will be available between AL1 and
AL2.
7. Transformer secondary ground via green wire with yellow strip from “C”
terminal to control box.
8. Fan motors are factory wired for medium speed. For high or low speed,
remove BLU wire from fan motor speed tap “M” and connect to “H” for
high speed or “L” for low speed.
9. For low speed, remove BLK wire from BR “6” and replace with RED.
Connect BLK and BRN wires together.
10. Optional LON wires. Only connect if LON connection is desired at the
wall sensor.
11. For blower motors with leads. For medium or low speed, disconnect
BLK wire from BR “6”. Connect BLK and ORG/PUR wire together.
Connect RED for low or BLU for medium to BR “6”.
12. Blower motor factory wired to medium speed. For low speed remove
BLU wire from medium tap and connect to low speed tap. For high
speed, remove BLU wire from exisiting speed tap and remove BRN
jumper wire from high speed tap. Connect BLU wire to high speed tap.
Tape off unconnected end of BRN jumper.
13. The 460-v units using an internal secondary pump will require a neu-
tral wire from the supply side in order to feed the accessory with 265-v.
Complete C
14
NOTES:
1. Compressor and blower motor thermally protected internally.
2. All wiring to the unit must comply with NEC and local codes.
3. Transformer is wired to 460-v BLK/RED lead for 460-3-60 units. Trans-
former is energy limiting or may have circuit breaker.
4. FP1 thermistor provides low temperature protection for water. When
using antifreeze solutions, cut JW3 jumper.
5. Refer to microprocessor control, LON, thermostat installation instruc-
tions for wiring to the unit. Wire “N01” from LON to “Y1” Deluxe D when
motorized valve is not used. Thermostat wiring must be Class 1 and
voltage rating equal to or greater than unit supply voltage.
6. Factory cut JW4 jumper. Dry contact will be available between AL1 and
AL2.
7. Transformer secondary ground via green wire with yellow stripe from
“C” terminal to control box.
8. Blower motor is factory wired for medium and high speeds. For any
other combination of speeds, attach black wire to the higher of the two
desired speed taps at the motor, and attach the blue wire to the lower of
the two desired speed taps.
9. Blower motor is factory wired for high and low speeds. No other combi-
nation is available.
10. Optional LON wires. Only connect if LON connection is desired at the
wall sensor.
11. The 460-v units using an internal secondary pump will require a neutral
wire from the supply side in order to feed the accessory with 265-v.
Fig. 17 — 50PCH,PCV units with Deluxe D and LON Controller (460 V)
LEGEND
AL Alarm Relay Contacts
BM Blower Motor
BMC Blower Motor Capacitor
BR Blower Relay
CB Circuit Breaker
CC Compressor Contactor
CO Sensor, Condensate Overflow
FP1 Sensor, Low Temperature Protection, Water Coil
FP2 Sensor, Low Temperature Protection, Air Coil
HP High-Pressure Switch
HPWS — High-Pressure Water Switch
JW1 Clippable Field Selection Jumper
LOC Loss of Charge Pressure Switch
LON Local Operating Network
MV Motorized Valve
MVES — Motorized Valve End Switch
NEC National Electrical Code
*Optional Wiring.
P1 Field Wiring Terminal Block
RVS Reversing Valve Solenoid
TRANS — Transformer
TXV Thermostatic Expansion Valve
Field Line Voltage Wiring
Field Low Voltage Wiring
Printed Circuit Trace
Optional Wiring
Relay/Contactor Coil
Condensate Pan
Solenoid Coil
Temperature Switch
Thermistor
Ground
Wire Nut
Relay Contacts - N.C.
Relay Contacts - N.O.
Low Pressure Switch
High Pressure Switch
Splice Cap
Circuit Breaker
a50-8440
Deluxe D
15
WHSP-OPEN
FSD
Fig. 18 — Units with Complete C and WSHP Open Multiple Protocol Controls
A50-8697
LEGEND
BM Blower Motor
BR Blower Relay
CO Condensate Overflow
FSD — Fire Smoke Detector
LWT — Leaving Water Temperature
N.C. — Normally Closed
OAD — Outside Air Damper
OCC — Occupancy Input Contact
RH Relative Humidity
SAT — Supply Air Temperature
SPT — Space Temperature
16
Loading...
+ 36 hidden pages