Carrier 50NQ User Manual

50NQ

HEATING A COOLING

Single-Package Heat Pumps

Installation, Start-Up and Service Instructions
CONTENTS
Page SAFETY CONSIDERATION INSTALLATION Step 1 —Moving and Setting Unit in Place
• ROOFTOP INSTALLATION
• GROUND-LEVEL INSTALLATION
• CLEARANCES
Step 2—Condensate Disposal....................................................4
Step 3—Duct Connections.........................................................6
Step 4—Electrical Connections
• HIGH-VOLTAGE CONNECTIONS
• PROCEDURES FOR 208V
• CONTROL VOLTAGE CONNECTIONS
• HEAT ANTICIPATOR SETTING
• CIRCUIT BREAKER PREPARING UNIT FOR START-UP START-UP AND ADJUSTMENTS
CARE AND MAINTENANCE...............................................10
NOTE TO INSTALLER: Leave these instructions and the
User’s ManurJ with the equipment user after installation.
Model 50NQ Packaged Heat Pump Units are fully self­contained, heating/cooling units designed for outdoor insted­lation. These units may be installed either on a rooftop or ground-level slab. For rooftop downflow applications, an accessory roof-mounting curb may be used.
Installing and servicing Eur conditioning equipment can be hazardous due to system pressure and electrical compo nents. Only trained and qualified service personnel should install or service air conditioning equipment.
Untrained personnel can perform basic meiintenance func tions such as cleaning coils and filters and replacing filters. All other operations should be performed by trained service personnel. When working on air conditioning equipmei^, observe precautions in the literature and on tags and labels attached to unit.
Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth for brazing operations. Have fire extinguisher available.
Recognize safety information: This is the safety-alert sym bol A, when you see this symbol on the unit and in instruc tions or manuals, be alert to the potential for personal injury.
Understand the signal word—DANGER, WARNING or CAUTION. These words are used with the safety-alert sym bol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING, on the other hand could result in personal injury or death. CAUTION is used to identify unsafe practices, which would
...................................................................
INTRODUCTION
SAFETY CONSIDERATIONS
..................................................
.............................
................................................
....................................
.........................................
1-7
Fig. 1 —Model 50NQ
result in minor personal injury or product and property damage.
1. This installation must conform with eJI applicable local and national codes.
2. The power supply (volts, hertz, and phase) must corre spond to that specified on unit rating plate. (See Fig. 4 for location.)
3. The electrical supply provided by the utility must be sufficient to handle load imposed by this unit.
4. Refer to the dimensional drawings (Figs. 2 and 3) for locations of electriceJ inlets, condensate drain, duct connections, and required clearances before setting unit in place.
5. Unit designed for outdoor installation on wood flooring or on class A, B, or C roof covering materials.
GENERAL
Model 50NQ Packaged Heat Pump has been designed and tested in accordance with ARI Standard 240, 270 and U.L.
Standard 559.
These units are factory-charged with R-22 refrigerant.
Installation is simple: connect air ducts, high- and low-
voltage wiring, condensate drain, and install a field-supplied
air filter. All units can be connected into existing duct systems that
are properly sized and designed to handle an airflow of 375 to 450 Cfm per each 12,000 Btuh of rated cooling capacity.
Refer to pre-sale literature for detailed air delivery capacity.
NOTE: When installing any accessory item, see the manu
facturer’s Installation Instructions packaged with the accessory. The Qualified Agency must use factory author ized kits or accessories when modifying this unit.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book| 1 I 4 PC 101 Catalog No 565-116 Printed in U.S.A Form 50NQ-1SI Pg 1 7-89 Replaces: New
Tab 15a 15a
N3
OPTIONAL SUPPLY
AIR OPENING
-CONTROL BOX
BLOWER ACCESS
DOOR
SUPPLY AIR-\
OPENING/DUCT ^
COVER
r-14 21/32
372.3
RETURN AIR-
0PENIN6/DUCT
COVER
OPTIONAL RETURN
AIR OPENING
UNIT CHARACTERISTICS LBS. KG.
ELECTRICAL UNIT WT. CORNER WT. LB./KG. CENTER OF GRAVITY
50NQ018 208/230/1/60 326 148 50NQ024 208/230/1/60 50NQ030 208/230/1/60 356 161 88/40 50NQ036 208/230/1/60 370 168 101/46 108/49 83/38 78/35 20" (508.0) 50NQ042 208/230/1/60 375
334 152
A B
100/45
102/46 63/29
102/46 108/49 63/29
103/47 89/40 76/34 21-1/4" (615.9) 22-3/4" (577.8)
170 102/46 112/51
UNIT TOP
..............................................
DUCT SIDE OF UNIT...6 MIN. CONTROL BOX ACCESS SIDE
SIDE OPPOSITE DUCTS.........................30 BOTTOM OF UNIT
NOTE. PROVISION MUST BE MADE FOR FRESH AMBIENT AIR TO REACH THE OUTDOOR COIL WITHOUT RECIRCULATION OF THE AIR FROM THE OUTDOOR FAN DISCHARGE.
EVAP COIL ACCESS PANEL
D E F
C
61/26 17-1/2" (444.5) 24-1/2" (622.3) 60/27
76/34 19-3/4" (501.6) 23-1/2" (596.9)
85/39
50NQ REQUIRED CLEARANCES CINCHES)
48 BLOWER ACCESS PANEL SIDE...........................................30
17" (431.8)
24" (658.6)
24" (658.6)
.............................................
...............................................................
1 3/8' DIA.CH.V. ENTRY3-
7/8' DIA.CL.V. ENTRY)-
22.2
30
0
35.0 (ACCESSORY ELECTRIC HEAT)
RIGHT SIDE VIEW
^1 1/4'
31.7
3/4' NPT
19.0
DRAIN OUTLET
7/8' DIA K.O.-^
22.2 ELECT. ENTRY
ALT.
f
U-2 5/16 SQ.
3 25/32 -»1
96.0
LEFT SIDE VIEW FRONT VIEW
-
---------------------
58.7 TYP 38 3/8'
974.7

Fig. 2—Dimensional Drawing—Small Cabinet

UNIT 50NQ048 208/230/1/60 450 204 50NQ060 208/230/1/60
LBS. KG.
483
ELECTRICAL UNIT WT.
CHARACTERISTICS
A B C
120/54 147/67 101/46
219 128/58
CORNER WT. LB./KG. CENTER OF GRAVITY
170/77 106/48 80/36 21-1/2" 546.1 27-1/2" 698.5
82/37
D
E
22-3/4" 577.8 28-1/4" 717.5
F
CO
OPTIONAL SUPPLY-
-CONTROL BOX ACCESS DOOR
AIR OPENING
3/4 NPT
19.0 DRAIN OUTLET
RIGHT SIDE VIEW
-BLOWER ACCESS DOOR
7/8' DIA. K.O.-
22.2
ALT. ELECT. ENTRY
SUPPLY AIR DUCT COVER
-OPTIONAL RETURN AIR OPENING
50NQ REQUIRED CLEARANCES (INCHES)
UNIT TOP
..............................................
DUCT SIDE OF UNIT...6 MIN. CONTROL BOX ACCESS SIDE SIDE OPPOSITE DUCTS NOTES PROVISION MUST BE MADE FOR FRESH AMBIENT AIR TO REACH THE OUTDOOR COIL WITHOUT RECIRCULATION OF THE AIR FROM THE OUTDOOR FAN DISCHARGE.
........................
LEFT SIDE VIEW
48 BLOWER ACCESS PANEL SIDE........................................30
30 BOTTOM OF UNIT
............................................
..............................................................
1 3/8' DIA.(H.V. ENTRY)-
30
0
35.0 (ACCESSORY ELECTRIC HEAT)

Fig. 3—Dimensional Drawing—Large Cabinet

Fig. 5—Suggested Rigging
RATING CONTROL BOX BLOWER PLATE ACCESS DOOR ACCESS
Fig. 4—Rating Plate Location
Step 1—Moving and Setting Unit in Piace
DOOR

A CAUTION

Use spreader bars and crate top when rigging the unit to be lifted. Model 50NQ must be rigged for lifting as shown in Fig. 5. Use extreme caution to prevent dam age when moving the unit. Unit must remain in an upright position during all rigging and moving opera tions. The unit must be level for proper condensate drainage; therefore, the ground-level pad or accessory roof-mounting curb must be level before setting the unit in place. When a field-fabricated support is used, ensure that the support is level and properly supports the unit.
ROOFTOP INSTALLATION

A CAUTION

When installing the unit on a rooftop, be sure that the roof will support the additional weight. Refer to Figs. 2 and 3 for total weight and corner weight information.
For downflow applications, an accessory roof-mounting curb may be installed on, and flashed into the roof before unit installation. The instructions for installing the acces sory curb are packaged with the curb.
For end-discharge applications place the unit on a level base that provides proper support. Refer to Fig. 7 for location of additional supports/sleepers. On flat roofs, be sure that the unit is located at least 4 ins. above the highest expected water level on the roof to prevent flooding.
GROUND-LEVEL INSTALLATION Place the unit on a solid, level, concrete pad that extends
approximately 2 ins. beyond the casing on all four sides of the unit. Do not secure the unit to the pad except when required by local codes. Ensure pad does not obstruct coil drainage holes in bottom of unit. (Holes drain water during cooling and defrost cycles.) In areas where prolonged sub freezing temperatures or snowfall occur, increase clearance to 12-18 ins. by constructing an angle-iron frame to support
the unit. The frame should be designed so as not to block the drainage holes. See Fig. 8 and Table 1 for recommended frame construction. Extend a 24-in. gravel apron around pad for condensate and defrost water drainage.
CLEARANCES The required minimum operating and service clearances are
shown in Figs. 2 and 3. Adequate condenser air must be provided.

A CAUTION

Do not restrict condenser airflow. An air restriction at either the outdoor-air inlet (the entire surface of the out door coil) or the fan discharge can be detrimental to compressor life.
The condenser fan discharges through the top of the unit. Ensure that the fan discharge does not recirculate to the condenser coil. Do not locate the unit in either a corner or under a complete overhead obstruction. The minimum clear ance under a partial overhang (such as a normal house roof overhang) is 48 ins. above unit top. The maximum horizon tal extension of a partial overhang must not exceed 48 ins.
Do not locate the unit where water, ice, or snow from an overhang or roof will damage or flood the unit by falling on the top. Do not locate the unit where grass, shrubs, or other plants will interfere with the airflow either into or out of the unit. Do not install the unit on carpeting, tile, or other com bustible material other than wood flooring. Heat pump may be installed on wood flooring or on Class A, B, or C roof cov ering materieds.
Step 2—Condensate Disposal NOTE: Ensure that condensate-water disposal methods
comply with IoceJ codes, restrictions, and practices. Model 50NQ disposes of condensate water through a 3/4-in.
NPT drain fitting. See Figs. 2 and 3 for location. Install a 3-in. trap at the dredn fitting to ensure proper
drainage. See Fig. 6. Meike sure that the outlet of the trap is at least 1 in. lower than the unit drain pan connection to prevent the pan from overflowing. Prime the trap with water.
If the installation requires draining the condensate water away from the unit, connect a drain tube using a minimum of 7/8-in. OD copper tubing, 3/4-in. gedvemized pipe, or 3/4-in. plastic pipe. Do not undersize the tube. Pitch the
1" MIN.
2" MIN.
A88130
♦These embossments are located on Large Cabinet Units (048-060 size only.)
Fig. 7—Additional Support/Sleeper
Location
©I" -------------­®' I ~ I I
^ _j Ui_i/2" (38mm)
®^" I 0 —ZZT—j
MATERIAL;
ANGLE IRON - 1-1/4" (31 8mm) TO 1-1/2" (38mm) COMM’L STD WELD FRAME TOGETHER PAINT WITH ZINC-RICH PAINT (RUSTPROOF)
—I [—1-1/2" (38mm)
Table 1—Mounting Frame
Dimensions
Large Cabinet
Item No.
A 50 in B 60-1/2 in C 30-1/4 in
1
2 60 in 3 49-1/2 in 4 49-1/2 in 5
Length
(1269mm)
(1535mm)
(766mm)
12 in (305mm)
to
24 in (610mm)
(1523mm)
(1257mm)
(1257mm)
16 in
(406mm)
Small Cabinet
Length
40-3/8 in
(1024mm)
47 in
(1193mm)
23-1/2 in (597mm)
12 in (305mm)
to
24 in (610mm)
46-1/2 in
(1181mm)
39-7/8 in
(1012mm)
39-7/8 in
(1012mm)
16 in
(406mm)
Quantity
4
2
2
1
8
Fig. 8—Mounting Frame
drain tube downward at a slope of at least 1 in, in every 10 ft of horizontal run. Be sure to check the dreun tube for leaks.
Condensate water can be drained directly onto the roof in rooftop installations (where permitted) or onto a gravel apron in ground-level instaJlations. When using a gravel apron, make sure it slopes away from the unit.
Step 3—Duct Connections
Model 50NQ has duct flemges on the supply and return mr openings on the side and bottom of the unit except on sizes 048 and 060. 048 and 060 sizes do not have flanges on side dischetrge openings. See Figs. 2 and 3 for connection sizes and locations.
NOTE; The design and insteJlation of the duct system must
be in accordance with the standards of the National Fire Protection Association for installation of nonresidence-type air conditioning and ventilating systems, NFPA No. 90A or residence type, NFPA No. 90B, and/or loced codes and ordinances.
Adhere to the following criteria when selecting, sizing, and installing the duct system:
1. Remove appropriate panels from unit to obtain either horizontal or down discharge. If models 018 through 042 are installed in horizontal discharge applications, remove side duct covers, save screws, and instedl the covers on bottom duct openings. To install duct covers on bottom duct openings, remove one flange which interferes with heater mounting plate. For models 048 through 060 remove either side or bottom duct covers as needed and discard.
2. Select and size ductwork, supply-air registers, and
return-air grilles according to ASHRAE recom
mendations. Refer to Tables 2 & 3 for static pressure capability.

A CAUTION

When the duct-system fastening holes are being drilled into side of unit instead of the unit duct flanges, use extreme care to avoid puncturing the coil or coil tubes. See Fig. 9.
3. Use flexible transition between rigid ductwork and unit to prevent transmission of vibration. The transition may be screwed or bolted to duct flemges. Use suitable gaskets to ensure weather and edrtight seed.
4. Install external, field-supplied air filter(s) in return-air* ductwork where it is easily accessible for service. Rec ommended filter sizes are shown in Table 4.
5.
Size all ductwork for maximum required airflow (either heating or cooling) for unit being installed. Avoid abrupt duct size increases or decreases.
6.
Adequately insulate and weatherproof all ductwork located outdoors. Insulate ducts passing through unconditioned space and use vapor barrier in accor dance with latest issue of SMACNA and ACCA mini mum installation standards for heating and air condi tioning systems. Secure edl ducts to building structure.
Flash, weatherproof, and vibration-isolate £dl openings
7. in building structure in accordance with local codes and good building practices.
8.
For Canadian Installations Only—An L-shaped exhaust duct fabricated of sheet metal or a material rated 94-5V shall be used in the case of downflow
applications.
Step 4—Electricial Connections

A WARNING

The unit cabinet must have an uninterrupted, unbro ken, electrical ground to minimize the possibility of per
sonal injury if an electriced fault should occur. This ground may consist of electrical wire connected to the
unit ground lug in the control compartment, or conduit
approved for electriced ground when instedled in accor dance with the National Electrical Code ANSI/NFPA­70 (in Canada, Canadian Electrical Code CSA C22.1) and loced electriceil codes.

A CAUTION

A failure to follow these precautions could result in damage to the unit being installed:
1. Meike all electrical connections in accordance with the latest National Electrical Code, ANSI/NFPA-70 and local electrical codes governing such wiring. In Canada,
all electrical connections must be in accordance with CSA standead C22.1 Canadian Electrical Code part 1 and applicable local codes. Refer to Unit Wiring Diagram.
2. Use only copper conductor for connections between field-supplied electrical disconnect switch and unit. DO
NOT USE ALUMINUM WIRE.
3. Ensure that high-voltage power to unit is within oper
ating voltage range indicated on unit rating plate (Fig.
4). On 3-phase units, ensure that phases are voltage and current balanced. Consult local power company for correction of improper voltage and/or phase balance.
4. Insulate low-voltage wires for highest voltage con
tained within conduit when low-voltage control wires are run in same conduit as high-voltage wires.
5. Do not damage internal components when drilling
through any panel to mount electriceil hardware, con duit, etc.
CAUTION: DO NOT DRILL OR SCREW IN SHADED AREA
«
SUPPLY
INLET/OUTLET PANEL
Cabinet Size
Smaii Cabinet
018-042
Large Cabinet 21-1/4"
048-060
Fig. 9—Location of Coii Area-
Not to be Drilied
5 0"-
RETURN
A
20-1/2"
O
HIGH-VOLTAGE CONNECTIONS The unit must have a separate electrical service with a field-
supplied, waterproof disconnect switch mounted at, or within sight from the unit. Refer to the unit rating plate (Fig. 4) for meiximum over-current device size and minimum circuit amps (ampacity) for wire sizing.
The field-supplied disconnect switch box may be mounted on the unit over the high-voltage inlet hole in the control corner panel. See Figs. 2 and 3.
Proceed as follows to complete the high-voltage connections to the unit:
1. Connect ground lead to chassis ground connection when using separate ground wire.
2. Run high voltage leads into unit through inlet hole in control box post, and to contactor through the hole in the bottom of control box. The high voltage leads should remain in conduit until entering control box and a watertight termination should be made at bottom of control box.
SPECIAL PROCEDURES FOR 208-V OPERATION
A WARNING
Make sure that the power supply to the unit is switched OFF before making any wiring changes. Electrical shock can cause personal injury or death.
For operation of 208 volts, disconnect the yellow transformer-primary lead from the contactor. See the unit wiring label. Remove the tape and cover from the termined on the end of the blue tremsformer-primeiry lead. Save the cover. Connect the blue lead to the contactor terminal from which the yellow lead was disconnected.
Using the cover removed from the blue lead, insulate the loose terminal on the yellow lead. Wrap the cover with elec trical tape so that the metal terminal cannot be shorted.
Indoor blower motor speed taps should be changed for 208V operation on 208/230v rated units. Interchange motor lead at blower motor. See “Start-up and Adjustments” section (page 9) and unit wiring label.
CONTROL VOLTAGE CONNECTIONS Locate the room thermostat on an inside wall in the space to
be conditioned where it will not be subjected to either a cool ing or heating source or direct exposure to sunlight. Mount the thermostat 4 to 5 ft above the floor.
Use No. 18 AWG color-coded, insulated (35 C minimum) wires to make the control voltage connections between the thermostat and the unit. If the thermostat is located more than 100 ft from the unit (as measured along the control voltage wires), use No. 16 AWG color-coded, insulated (35 C minimum) wires.
A grommeted control voltage inlet hole is located in the panel adjacent to the control access panel. See Figs. 2 and 3. Run the low-voltage leads from the thermostat, through the inlet hole, and to the control voltage terminals. Connect the thermostat leads to the terminals as shown in Fig. 10.
HEAT ANTICIPATOR SETTING Factory thermostats have fixed heat anticipator settings.
No adjustment is required. CIRCUIT BREAKER Unit has manual reset circuit breaker which is located in the
low-voltage wiring box adjacent to low-voltage terminal board. If unit fails to operate, first check breaker for tripped
position. If breaker is tripped, re-set and try to start unit. If breaker continues to trip there is a problem in the low­voltage electrical circuit (electrical short, ground, or trems­former overload). Correct the condition and check for nor mal unit operation.
PREPARING UNIT FOR START-UP
A WARNING
Failure to observe the following warnings could result in serious personal injury:
1. Follow recognized safety practices and wear protec tive goggles when checking or servicing refrigerant system.
2. Do not operate compressor or provide any electric power to unit unless compressor termined cover is in place and secured.
3. Do not remove compressor terminal cover until edl electrical sources have been disconnected.
4. Relieve all pressure from system before touching or disturbing anything inside compressor termined box if refrigerant leak is suspected eiround terminals.
5. Never attempt to repair soldered connection while refrigerant system is under pressure.
6. Do not use torch to remove any component. System contains oil and refrigerant under pressure. To remove a component, wear protective goggles and proceed as follows:
a. Relieve all pressure from system.
b. Cut component connecting tubing with tubing
cutter and remove component from unit.
c. Ceirefully unsweat remaining tubing stubs when
necessary. Oil can ignite when exposed to torch flame.
PRESTARTUP PROCEDURES Proceed as follows to inspect and prepare the unit for initial
startup:
1. Remove all access panels.
2. Read and follow instructions on all WARNING, CAU TION, and INFORMATION labels attached to, or shipped with, unit.
3. Make the following inspections:
a. Inspect for shipping and handling damages such as
broken lines, loose parts, disconnected wires, etc.
b. Inspect for oil at all refrigerant tubing connections
and on unit base. Detecting oil generally indicates a refrigerant leak. Leeik-test all refrigerant tubing connections using electronic leak detector, halide torch, or liquid-soap solution. If refrigerant leak is detected, see “Refrigerant Leaks” section on page 9.
c. Inspect all field- and factory-wiring connections. Be
sure that connections are completed and tight.
d. Inspect coil fins. If damaged during shipping and
handling, carefully straighten fins with a fin comb.
4. Verify the following conditions:
a. Make sure that outdoor fan blade is correctly posi
tioned in fan orifice. Blades should clear fan motor
by no more than 1/4 in. The fan blade hub should be
flush with end of motor shaft.
b. Meike sure that air filter(s) is in place.
c. Make sure that condensate drain pan and trap are
filled with water to ensure proper drainage.
THERMOSTAT
8 SUBBASE
(SEE BELOW)
UNIT CONTROL WIRING TERMINAL BOARD
THERMOSTAT
a SUBBASE
UNIT
CONTROL WIRING
TERMINAL BOARD
& &
0-
0
-
B-
[£>
0-
COOLING AND ONE-STAGE HEATING
THERMOSTAT
a SUBBASE
(without Electric Heater)
UNIT CONTROL WIRING TERMINAL BOARD
0)
-<D
0)
<8>
-B)
ODT — Outdoor Thermostat HR — Heater Relay
COOLING AND TWO-STAGE HEATING
(Unit equipped with Electric Heater, Supplemental
Heat, One Outdoor Thermostat)
THERMOSTAT
a SUBBASE
UNIT
CONTROL WIRING
TERMINAL BOARD
COOLING AND TWO-STAGE HEATING
(Unit equipped with Electric Heater, Supplemental
Heat, No Outdoor Thermostats)

Fig. 10—Control Connections

HR — Heater Relay
ODT — Outdoor Thermostat
COOLING AND TWO-STAGE HEATING
(Unit equipped with Electric Heater, Supplemental
Heat Relay, Two Outdoor Thermostats)
d. Make sure that all tools and miscellaneous loose
parts have been removed. Unit is now ready for initial steirtup. REFRIGERANT LEAKS Proceed as follows to repair a refrigerant leak and to charge
the unit:
1. Locate leak and ensure that refrigerant system pres sure has been relieved.
2. Repeiir leak following accepted practices.
NOTE: Install a filter-drier whenever the system has been opened for repair.
3. Add a small charge of R-22 refrigerant vapor to system and leak-test unit.
4. Evacuate refrigerant system if additional leaks are not found.
5. Charge unit with R-22 refrigerant, using a volumetric­charging cylinder or accurate scede. Refer to unit rating
plate for required charge. Be sure to add extra refriger
ant to compensate for internal volume of filter-drier.
START-UP AND ADJUSTMENTS

A CAUTION

Complete the required procedures given in “Preparing Unit for Start-up,” page 7, before starting the unit.
Do not jumper any safety devices when operating the unit.
Do not operate unit in the cooling mode when the out door temperature is below 55 F (unless accessory low­temperature kit is installed).
Do not operate unit in heating mode when outdoor tem perature is above 60 F.
Do not rapid-cycle the compressor. Allow 5 minutes between “on” cycles to prevent compressor damage.
The unit compressor is equipped with a crankcase heater. It is recommended that heater be energized a minimum of 24 hours before starting unit. To energize heater only, set ther mostat at OFF position; turn on unit main power at discon nect switch.
TO START UNIT—Check that main power is on and that compressor crankcase heater has been energized for at least 24 hours.
1. Check that heater main power is on as applicable.
2. Set selector switch at OFF.
3. Set fan switch as desired (FAN) (AUTO.).
4. Set thermostat dial at the desired temperature.
5. Set selector switch at HEAT or COOL. Check system refrigerant charge as described in “Checking Charge”
section below.
CHECKING CHARGE-Factory Charge is shown on unit rating plate (See Fig. 4).

A CAUTION

Compressor damage may occur if system is over charged.
Adjust charge in cooling mode by following procedure shown on the “superheat charging tables” located on unit. Check charge in heating by following procedure shown on “heating check chart” located on unit.
INDOOR AIRFLOW AND AIRFLOW ADJUSTMENTS

A CAUTION

For proper operation, the recommended airflow is 375 to 450 CFM for each 12,000 BTUH of rated cooling capacity. Minimum airflows may be different if supple mental electric heaters are installed. See Table 5.
These units have direct-drive blower motors. Blower motors are factory-connected to deliver the proper heating and cool ing airflows at normal external static pressures.
Tables 2 and 3 show both heating and cooling airflows at various external static pressures. Refer to these tables to determine the airflow for the system being insteilled. See Table 4 for the rated heating and cooling airflows.
NOTE: Be sure that all supply- and return-eur grilles are
open, free from obstructions, and adjusted properly.

A WARNING

Disconnect electrical power to the unit before changing blower speed. Electrical shock can cause personal injury or death.
The heating and/or cooling airflow of 208/230-V direct-drive blower motors cem be changed by changing the lead connec tions at the blower motor. The motor leads are color-coded as follows:
black = high speed blue = medium speed red = low speed
UNIT CONTROLS All compressors have the following internal-protection
controls:
1. High-pressure Relief Va/ue—This valve opens when the pressure differential between the low and high side becomes excessive.
2. Compressor Overload—This overload interrupts power to the compressor when either the current or internal temperature become excessive, and automatically resets when the internal temperature drops to a safe level. This overload may require up to 60 minutes (or longer) to reset; therefore, if the internal overload is suspected of being open, disconnect the electrical power to the unit and check the circuit through the overload with an ohmmeter or continuity tester.
SEQUENCE OF OPERATION COOLING—On a call for cooling, thermostat makes circuit
R-0, R-Y and R-G. When room temperature rises to within 2 degrees of control setting of thermostat, circuit R-O makes, energizing reversing valve solenoid (RVS). Unit is now in standby condition for cooling. As room temperature rises, the second-stage bulb makes, allowing a circuit (R-Y) through low-pressure switch (LPS) to contactor (C), starting compressor (COMP) and outdoor fan motor (OFM). Circuit R-G energizes indoor fan relay (IFR) starting indoor fan motor (IFM).
When thermostat is satisfied, contacts open de-energizing contactor. Indoor fan relay, compressor and motor stop.
HEATING—On a call for heat, thermostat makes circuits R-Y and R-G. Circuit R-Y is completed, allowing circuit through low-pressure switch (LPS) to contactor (C), starting compressor (COMP) and outdoor fan motor (OFM). Circuit R-G also is completed, energizing indoor fan relay (IFR) and
starting indoor fan motor (IFM).
Should room temperature continue to fall, circuit R-W is made through second-stage thermostat bulb. If optional electric heat package is used, a sequencer is energized bring
ing on first bank of supplemental electric heat. When ther mostat is satisfied, contacts open, de-energizing contactor and sequencer. Motors and heaters de-energize.
DEFROST—Defrost board (DB) is a time/temperature con trol which includes a field-selectable time period between check if defrost is necessary (30, 50 and 90 minutes). Elec tronic timer and defrost cycle start only when contactor is energized and defrost thermostat (DFT) is closed.
Defrost mode is identical to cooling mode except outdoor fan motor stops and a bank of optional electric heat turns on to warm air supplying the conditioned space.
CARE AND MAINTENANCE
To ensure continuing high performance, and to minimize the possibility of premature equipment failure, periodic mainte nance must be performed on this equipment. This combina tion heating/cooling unit should be inspected at least once each year by a queilified service person.
NOTE TO EQUIPMENT OWNER: Consult your local Dealer
about the aveulability of a maintenance contract.

A WARNING

The ability to properly maintain this equipment requires certain expertise, mechanical skills, tools, and equipment. If you do not possess these, do not attempt to perform any maintenance on this equipment other than those procedures recommended in the Users Man ual. A FAILURE TO HEED THIS WARNING COULD RESULT IN SERIOUS PERSONAL
INJURY AND POSSIBLE DAMAGE TO THIS
EQUIPMENT.
The minimum maintenemce requirements for this equipment
are as follows:
1. Inspect Eur filter(s) each month. Clean or replace when necessary.
2. Inspect cooling coil, drain pan, and condensate dreiin each cooling season for cleanliness. Clean when necessary.
3. Inspect blower motor and wheel for cleanliness each heating and cooling season. Clean when necessary.
4. Check electrical connections for tightness on controls for proper operation each heating and cooling season.
; Service when necessary.

A WARNING

A failure to follow these warnings could result in seri ous personal injury.
AIR FILTER

A CAUTION

Never operate the unit without a suitable air filter in the return-air duct system. Always replace the filter with the same dimensional size and type as originally installed. See Table 4 for recommended filter sizes.
Inspect air filter(s) at least once each month and replace (disposable-type) or clean (cleemable-type) at least twice dur ing each heating and cooling season or whenever the filter(s) becomes clogged with dust and lint.
10
Table 2—Models 50NQ Air Delivery (Cfm) in 208V-Horizontal Fiow Set-up at indicated
Externai Static Pressure & Voltage (Sizes 018, 024,030, 036, 048, 060)
UNIT SIZE
018
024
VOLT/PHASE/HZ
208/1/60
208/1/60
030 208/1/60
036
208/1/60
042 208/1/60
048 208/1/60
060 208/1/60
MOTOR
SPEED
LOW MED
HI LOW MED
HI LOW
0.0 0.1 0.2 0.3 788 761 758
1195t
1184t 1160t
1425t 1375t 1359t
802 787 772 738
1211t 1473t
1200t 1190t 1169t 1138t 1444t 1418t 1377t 1339t
MED 1225 1220 1211
HI 1483 1470 1450 1415 LOW MED
HI LOW
1421 1388 1343 1306
1882f
MED 1421
HI
1882t 1809t 1722t 1644t 1546T
1809f
1388
1722t 1644t 1546t
1343 1306
LOW 1603 1584 1489 MED 2035 1985
HI LOW MED
HI
2304t 2262t 2139t
2205t 2198t 2190t 2188t 2122t 25811
2538t 2455t 2382t 2305t 2258t 2168t
1923 1851 1771 1678 1497
EXTERNAL STATIC PRESSURE—INCHES W.C.
734
1121t
675
1092t
1308t 1248t 1139t 1030t
702
0.4
0.5 644
987t
1061t 1260t
1177 1166 1105 1040
1372 1319
_
1252 1165
1386 1296
_
1252
1386
2046
1940
1815 1687
2084 2020
0.6 600
886
0.7 0.8 0.9 1.0 564
744
917t
525 724 667 786
702 647
993t
1195t
878
997t
913
1245
1058
1098 891
_
1225
1296
1225
__
1462
1943
2084
768 838 750
_ _
_
_ _
__
1054
— _
1863
1992
__
— —
1893
581
__
Tabie 3—Modeis 50NQ Air Deiivery (Cfm) in 230-V Horizontai Fiow Set-Up at indicated
External Static Pressure & Voltage (Sizes 018, 024, 030, 036, 048, 060)
UNIT
VOLT/PHASE/HZ
SIZE
018 230/1/60
024 230/1/60
030 230/1/60
MOTOR
SPEED
LOW MED
HI
LOW
MED
HI
LOW
0.0
0.1
913t 905t 1366t 1336t 1584t
1552t
0.2 0.3 0.4 891 848 827 765 699
1302
1467t 1414t 1332t 1256t 1146t
950t 935t 926t 1414t 1399t 1373t 1333t 1652t
1614t
1556T
937 933 929 919 893
MED 1425 1413 1391 1358
HI
1670t 1576t 1552t 1533t
LOW 1088 1075 1050
036 230/1/60
042 230/1/60
048 230/1/60
MED
HI LOW MED
HI
1636t 1599t 1553t 2034t 1957t 1846t 1734t
1636t 1599t 1553t
2034t LOW 1891 MED
HI
2230t 2155t
2385t 2304t 2183t
1957t 1846t 1734t
1852
1819 1746 2060
LOW 2027 2000 1993 1972 1940 1872
060
230/1/60
MED
HI
2546t 2508t 2448t
2837t 2758t
2652t
Air deliveries based on unit dry coil without air filter or optional electrical heaters. Deduct field supplied air filter and electric heater pressure drop to obtain external static pressure available for ducting. Dashes indicate less than minimum airflow and coil icing may occur.
tAirflow exceeds maximum coil velocity. Condensate may be blown off of coil.
If supplemental electric heaters are used, refer to Table 5 for minimum air-flows. These airflows will be slightly greater than those required for unit operation.
EXTERNAL STATIC PRESSURE—INCHES W.C.
0.6
1250t
1201t
900 885
0.5
1098t 982t
811 733
1289t 1229t 1148t
1520t
1440t 1375t 1277t
1326 1268 1196
1468 1419 1324
1480 1393 1275
1602T
1480 1393
1602f
1684
1989t
1885 1782
2097 1982
2382t
2297t 2234t 2150t
1571t
1275
1571t 1553
1863 1717
1158 1316
1316
_
1630
2587t 2476t 2392t 2304t
0.7 0.8 0.9 1.0 651 606 575
898 776 676 609
101 Of
825 750 665
700 1015t 1098t
1071
811 747 876 799 701
875
1134 920 875
1050 1225
1225
__
1483 1614
— —
1072
_
— —
__ —
1493
_
_
2070 1977 1870 2224t
2089 2003 1872
_
— — — —
— — —
_
_
Table 4—Rated Airflow and Filter Sizes
Model
Size
Rated Airflow (Cfm)*
018300 024300 030300 036300 1 036500 1 036600 042300 1 042500 | 042600
675 900
1100
1300
Recommended Min f
Field Supplied
Filter Size
324 432 540 648
Disposable Type
Cleanableor High-
Capacity
216 288
360
432
♦Rated in accordance with U.S. Government D.O.E. test procedures and/or ARI Standard 210. tRequired filter areas shown are based on the larger of the ARI-rated cooling or heating airflow at a velocity of 300 ft/min for disposable type or
450 ft/min for high-capacity type.
50NQ
048300 1 048500 | 048600
1500 1750
756
504 576
060300 1 060500 1 060600
864
11
2100
1030
720
SIZE
AIRFLOW
(CFM)
Table 5—Minimum Airfiow for Safe
Electric Heater Operation
018 600
024 030 036 042 048 060 800 1000
1200
1400
1600 2000
Tabie 6—Wet Coil Pressure Drop
Unit Size Wet Coil P.D. (In. wc.)
018, 024 0.54
030 .060 036 .070 042 .075 048 060 .100
.086
UNIT TOP REMOVAL

A CAUTION

Condenser fan and motor eire fastened to the unit top. When removing the top, use extreme care not to pull the fan motor leads loose.
NOTE: When performing maintenance or service proce
dures that require removal of the unit top, be sure to per form all of the routine maintenance procedures that require top removal, including; coil inspection and cleaning, and condensate drain pan inspection and cleaning.
Only qualified service personnel should perform mainte nance and service procedures that require unit top removal. Refer to the following top removed procedures:
1. Remove all screws that secure unit top, including screws around four sides and those on top that screw into internal divider panels. Save all screws.
2. Tape edl side panels at each seam near unit top. Use tape strips that are at least 5 ins. long to prevent sides from falling when top is removed.
3. Lift top from unit carefully. Set top on edge and ensure that top is supported by unit side that is opposite duct (or plenum) side.Use extreme care to prevent damage to
the fan blades, motor, and insulation.
4. Carefully replace and secure unit top to unit, using screws removed in step 1, when maintenance and/or service procedures are concluded. (Be sure to use origi nal screws that have rubber washers to seal out water
when securing top to internal divider panels.) INDOOR BLOWER AND MOTOR For longer life, operating economy, and continuing effi
ciency; clean accumulated dirt and grease from the blower wheel and motor annually.

A WARNING

Disconnect and tag electrical power to the unit before cleaning the blower assembly. Failure to adhere to this warning could cause personal injury or death.
Clean the hlower assembly as follows:
1. Remove and disassemble blower assembly as follows: a. Remove blower access door.
b. Disconnect blower motor leads from their termina
tion points at motor. Disconnect yellow lead from control box at capacitor.
c. Remove blower assembly from unit. Be careful not
to tear insulation in blower compartment.
d. Ensure proper reassembly by marking blower wheel
and motor in relation to blower housing before
disassembly.
e. Loosen setscrew(s) that secures wheel to motor
shaft, remove screws that secure motor mount brackets to housing, and slide motor and motor mount out of housing.
2. Remove and clean blower wheel as follows: a. Ensure proper reassembly by marking wheel orien
tation and cutoff plate location.
b. Remove screws holding cutoff plate, and remove
plate from housing.
c. Lift wheel from housing. When handling and/or
cleaning blower wheel, be sure not to disturb bal ance weights (clips) on blower wheel vanes.
d. Remove caked-on dirt from wheel and housing with
a brush. Remove lint and/or dirt accumulations from wheel and housing with vacuum cleaner, using soft brush attachment. Remove grease and oil with mild solvent.
e. Reassemble wheel and cutoff plate into housing.
f. Reassemble motor into housing. Be sure setscrews
are tightened on motor shaft flats and not on round part of shaft.
OUTDOOR COIL, INDOOR COIL, AND CONDENSATE DRAIN PAN
Inspect the coils and condensate drain pan at least once each year. Proper inspection and cleaning requires the removal of the unit top. See “Unit Top Removal” section.
The coils are easily cleaned when dry; therefore, inspect and clean the coils either before or after each cooling season. Remove all obstructions, including weeds and shrubs that interfere with the airflow through the outdoor coil. Straighten bent fins with a fin comb. If coated with dirt or lint, clean the coils with a vacuum cleaner using the soft brush attachment. Be careful not to bend the fins. If coated with oil or grease, clean the coils with a mild detergent-and­water solution. Rinse coils with clear water using a garden hose. Be careful not to splash water on motors, insulation, wiring, or air filter(s). For best results, spray outdoor coil fins from inside to outside the unit. On units with an outer and inner outdoor coil, be sure to clean between the coils. Be sure to flush all dirt and debris from the unit base.
Inspect the drain pan and condensate drain line when inspecting the coils. Clean the drain pan and condensate drain by removing all foreign matter from the pan. Flush the pan and drain tube with clear water. Do not splash water on the insulation, motor, wiring, or air filter(s). If the drain tube is restricted, clear it with a “plumbers snake” or similar probe device.
OUTDOOR FAN

A CAUTION

Keep the outdoor fan free from all obstructions to ensure proper operation. Never place articles on top of the unit.
12
FLARE NUT
STRAINER
STAMPED ARROW ON COUPLING BODY
COIL
RUBBER 0-RING
Fig. 11—Metering Device (Duai-Piston) Components
(TOWARD INDOOR COIL)
Inspect the fan blades for cracks or bends each year. Ensure that blades clear the motor by no more than 1/4 in. The fan blade hub should be flush with end of motor shaft. If the blade assembly has slipped down the motor shaft, adjust the fan position on the motor shaft by loosening the setscrew(s), then moving the blade assembly up. Be sure that the set­screw(s) is on the flat(s) of the motor shaft before tightening.
ELECTRICAL CONTROLS AND WIRING Inspect and check the electrical controls and wiring annu
ally. Be sure to turn off the electrical power to the unit. Remove the control, blower, and compressor compartment
access panels to locate all the electrical controls and wiring. Check all electrical connections for tightness. Tighten all screw connections. If any smoky or burned connections are noticed: disassemble the connection, clean all the parts, restrip the wire end, and reassemble the connection properly and securely.
After inspecting the electrical controls and wiring, replace all the panels. Start the unit and observe at least one com plete heating cycle and one complete cooling cycle to ensure proper operation. If discrepancies are observed in either or both operating cycles, or if a suspected malfunction has occurred, check each electrical component with the proper electrical instrumentation. Refer to the unit wiring label when making these checkouts.
NOTE: Refer to the heating and/or cooling sequence of oper
ation in this publication as an aid in determining proper con trol operation.
REFRIGERANT CIRCUIT Inspect Eill refrigerant tubing connections and the unit base
for oil accumulations annually. Detecting oil generally indi cates a refrigerant leak.
If oil is detected or if low cooling performance is suspected, leak-test all refrigerant tubing; using an electronic leak­detector, halide torch or liquid-soap solution. If a refrigerant leak is detected, see “Refrigerant Leaks” in this publication.
If no refrigerant leaks are found and low cooling perfor mance is suspected, refer to “Checking Charge” and unit rating plate.
STRAINER
RETAINER
A87292
INDOOR AIRFLOW The heating and/or cooling airflow does not require checking
unless improper performance is suspected. If a problem
exists, be sure that all supply- and return-air grilles are open and free from obstructions, and that the air filter is clean.
When necessary, refer to “Indoor Airflow and Airflow Adjustments,” page 10 of this publication to check the sys tem airflow.
METERING DEVICE SERVICING See Fig. 11 for metering device components. The pistons
have a refrigerant metering orifice through them. The retainer forms a sealing surface for liquid line flare connec tion. To check, clean or replace piston:
1. Shut off power to unit.
2. Remove refrigerant from unit using approved refriger ant removal methods.
3. Remove liquid line flare connections from metering device.
4. Note position of arrow on metering device body with respect to unit.
5. Pull retainers out of body. Be careful not to scratch flare sealing surfaces. If retainers do not pull out eas ily, carefully use locking pliers to remove retainers.
Replace scratched or damaged reteuners. Slide pistons out by inserting a small soft wire through
6.
metering hole (18-gauge thermostat wire). See that metering hole, seeding surface around piston cones and fluted portion of pistons are not damaged.
Chart on unit access panel illustrates proper arrange
ment and size of pistons.
Clean pistons refrigerant metering orifice. Replacement retainer 0-ring Part No. is 99CC501052.
LIQUID LINE STRAINER The Liquid Line Strainers (to protect metering device), are
made of wire mesh and are located in the liquid line on both sides of the metering device. Strainers are pressed into the line. Remove strainers by threading a No. 10 sheet metal screw into strainers and pulling the screw with pliers.
13
UNIT SINGLE-PHASE COMPRESSORS are equipped with a Compressor Start Thermistor (PTC device). When supply voltage is within 10% limit and compressor does not start, check the start thermistor with an ohmmeter.
Checking Start Thermistor
1. Shut off all power to unit and wait 10 minutes for thermistor to cool to ambient temperature.
2. Remove thermistor from circuit.
3. Measure resistance of thermistor with ohmmeter. Nor
mal resistance readings are 12.5 or 25 ohms -I- 20% at 75 F ambient temperature depending on your unit.
4. If ohmmeter resistance reading is not within ± 20%, the thermistor is defective and must be replaced.
If start thermistor is good and compressor does not steu-t, disconnect the thermistor from starting circuit and give compressor a temporeiry capacitance boost. Run compressor for 10 minutes, then shut off and allow system pressure to equalize. Reconnect start thermistor and try restarting compressor without boost capacitor. If after two attempts the compressor does not start, remove thermistor and add an accessory start capacitor and relay.
14
TROUBLESHOOTING CHART—COOLING CYCLE
DEFECTIVE LOW VOLTAGE TRANSFORMER
SUPPLEMENTAL HEAT RELAY ENERGIZED OR WIRED WRONG
TROUBLESHOOTING CHART—HEATING CYCLE
LOW LINE VOLTAGE OK UNBALANCED 3 PHASE LINE
COMPRESSOK POWER supplì OPEN
FAULTY START CAP OR RELAY ISINGLE PHASE) OR PTC
INDOOR IANS CVCLINti ON OVERLOAD
OVERCHARGE OR NONCONDENSAOLES IN SYSTEM
RESTHiCTED OR STUCK METERING DEVICE
OEFLCIIVE RUN
i;apaciioh
• SINCU E PHASE I
REVERSING VALVE
JAMMED IN MID
POSITION
LOOSE LEADS A OUTDOOR FAN MOTOR
INTERNAI FAN MOTOR KLIXON OPEN
DEFROST BOARD N C CONTACTS OPEN
METERING DEVICE
• RESTRICTED OR
ICE-CLOGGED
UNDERCHARGED
DEFROST T STAT IN POOR PHYSICAL CONTACT WITH LINE
DEFECTIVE DEFROST RELAY OR DEFROST TIMER
OUTDOOR THERMOSTAT DEFECTIVE
CAP TUBE PINCHED
OR BULB NOT
SENSING TRUE ODT
STRIP HEATER RELAY OR CÜNIACTOH DETECTIVE
OPENING IN POWER CIRCUIT TO HEATER ELEMENTS
OPEN (Kl IXON) OVERTEMPERATURE
THERMOSTAT
DEFECTIVE ROOM THEHMOSTAI |?ND STAGEl
15
BAD ELECTRICAL CON NECTION ANYWHERE IN DEFROST CIRCUIT
A88431
Manufacturer resenres the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
BookI 1 I 4 PC 101 Catalog No. 565-116 Printed in USA Form 50NQ-1SI Pg 16 7-89 Replaces: New
Tab 15a 15a
Loading...