HE_ATtNG & COOLING
ViSil "WWw.catTICr.CORI
Installation, Start-Up, and Service Instructions
NOTE: Read the entire instruction manual before starting the
installation.
This symbol --_ indicates a change since the last issue.
TABLE OF CONTENTS
SAFETY CONSIDERATIONS ..................................................... l
Introduction .................................................................................... 4
Receiving and Installation .............................................................. 4
Check Equipment ...................................................................... 4
Provide Unit Support ................................................................ 4
Provide Clearances .................................................................... 6
Rig and Place Unit .................................................................... 6
Select and Install Ductwork ..................................................... 7
Provide for Condensate Disposal ............................................. 8
Install Electrical Connections ................................................... 8
PRE-START-UP .......................................................................... lO
START- U P ................................................................................... 16
Check for Refrigerant Leaks .................................................. 16
Start-Up Adjustments .............................................................. 16
Defrost Control ....................................................................... 19
MAINTENANCE ......................................................................... 21
Air Filter .................................................................................. 22
Indoor Blower and Motor ....................................................... 22
Outdoor Coil, Indoor Coil, and Condensate Drain Pan ........ 22
Outdoor Fan ............................................................................ 23
Electrical Controls and Wiring ............................................... 23
Refrigerant Circuit .................................................................. 23
Indoor Airflow ........................................................................ 23
Metering Devices-Accurater Piston ....................................... 23
Pressure Switches .................................................................... 23
Loss of Charge Switch ........................................................... 23
High-Pressure Switch .............................................................. 23
Copeland Scroll Compressor (Puron Refrigerant) ................. 23
Refrigerant System .................................................................. 24
System Information ................................................................. 24
TROUBLESHOOTING ............................................................... 25
Sta_-Up Checklist ........................................................................ 25
NOTE TO INSTALLER -- READ THESE INSTRUCTIONS
CAREFULLY AND COMPLETELY before installing this unit.
Also, make sure the Owner's Manual and Service Instructions are
left with the unit after installation.
SAFETY CONSIDERATIONS
Installation and servicing of air-conditioning equipment can be
hazardous due to system pressure and electrical components. Only
trained and qualified personnel should install repair, or service
air-conditioning equipment.
Untrained personnel can perform basic maintenance functions of
cleaning coils and filters. All other operations should be performed
50JZ024-060
Single-Package Heat Pump Units
with Puron (R-410A) Refrigerant
C99064
Fig. 1--Unit 50JZ
by trained service personnel. When working on air-conditioning
equipment, observe precautions in the literature, tags, and labels
attached to the unit, and other safety precautions that may apply.
Follow all safety codes. Wear safety glasses and work gloves. Use
quenching cloth for unbrazing operations. Have fire extinguisher
available for all brazing operations.
Improper installation, adjustment, alteration, service, mainte-
nance, or use can cause explosion, fire. electric shock, or
other occurrences, which could cause serious injury or death
or damage your property. Consult a qualified installer or
service agency for information or assistance. The qualified
installer or agency must use only factory-authorized kits or
accessories when modifying this product.
Recognize safety information. TItis is the safety-alert symbol_.
When you see this symbol on the product or in instructions or
manuals, be alert to the potential for personal injury.
Understand the signal words -- DANGER, WARNING, CAU-
TION, and NOTE. Danger identifies the most serious hazards.
which will result in severe personal injury or death. Warning
indicates a condition that could cause serious personal injury or
death. Caution is used to identify unsafe practices, which would
result in minor personal injury or product and property damage.
NOTE is used to highlight suggestions which will result in
enhanced installation, reliability, or operation.
Manufacturer rese_ve_ the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book t 4 PC t0t Catalo<j NO. 535_0020 Printed in U.S.A. Form 50JZ-2SI Pg 1 12-00 Re#aces: 50JZ-t SI
_IlO 00]
• * i i
fULL LOUVER
B
If
{16 00)
I
D
TOP VIEW
_TOC_IilJ611IJEMA'iL
TOP OF UNII ................. )556 114 00]
DUCT SISE OF UNIT ..... 50 8 (2 001
SIDE OPPO$1f[ DUCTS .... 3556 [14¸001
BOT10H OF UNIT .......... 121 1050]
ELECTRIC H[_1 PANEL.............. g14 4 []6 00}
NE_ REOURm_
BETWEEN UNITS, POIII[R [NIRY Sll)[ ...... IOGG8 [47 OO}
UNI1 AND UNgROUNDEd) SURFACES, POW[_ ENTRY S_O[ ..... 914 0 [36 00}
UNI[ ANO BLOCK OR CONCRETE WALLS AND OIH[r
GROURD[II SURFACES, POWER ENTRY SIO[ ...... i0666 [42 00]
MILLIMETERS FIN]
MILL ll4[ TERS (IN]
SUPPLV
DUCl
OPEniNG
249¸6
[983]
--5505
[2[ 67]
TURN
CT
[NIN
19 6
[9 83]
REARVIEW
[VAP COIL ACCESS SIDE ........................ 914 0 [36¸00)
POWER [NTRT SIDE................ 9[4¸0 [3600]
(EXCEPT for N[C R[OUIREM[NTS}
UNIT TOP ...................... 914 0 [3600]
$1D[ OPPOSITE OUCTS .................... 91_0 [36,00]
DUCT PANEL........................ 304 8 [I?00]*
*MINIMUMDISTANCES IF UNIT IS PLACEDLESS THAN 304 8 [12 OOJFROIKWALL
SYSTEMT_[N SYSTEMP[RFOttMANC[MkYfi[ COMPROMISED
MILLIMETERS FIN]
.-.)
UNIT
50JZ024
50JZ030
50JZ036
FULL LOUV[_
?? ? 1o BBI OqA HOL£
C_tROL ZNtRt_
[10 8 I 13 _ T
fULL LOUV[R
I 1 , L
h_l?? ?
[4 811
LEFT SIDE VIEW FRONTVIEW RIGHT SIDEVIEW
ELECTRICAL CHARACTERISTICS
UNIT WEIGHT
Ib, kg
208/230-1-60 299 135.6
208/230-1-60,208/230-3-60 320 145.2
208/230-1-60,208/230-3-60, 460-3-60 328 148.8
UNIT HEIGHT
IN. (MM)
"A" X
35.02 (889,5) 19.0 (482,6)
37.02 (940.3) 20,0 (508.0)
37,02 (940.3) 20.0 (508.0)
CENTER OF GRAVITY
IN. (MM)
Y
18.3 (463.6)
19.3 (489,0)
19.0 (482.6)
Fig, 2--50JZ024-036 Unit Dimensions
2
io 20
CC0160
Z
16.0 (406.4)
17.6 (447.0)
16.5 (419.1)
• = . , ,,
.j DIlL LOIIVER _L'
m <1
TOPVIEW
REOtlB_ _ lo COMBUSTIBLE MATL
TOP OF U_IT ........ 35_ IJ_ OO]
_UCT SIDE Of UNI1 SO B I_ 00}
SIDE OPPOSITE DUCTS 35S 6 [14 001
BOttOMOf UNiT . i? 1 [o Sol
ELECTRIC HEAl PANEL ..... 914 4 [3b DO]
{_C• RB1URED CI_.ARANCES.
B[TWE[_ UNITS, POWER ENIRY SIDE IOGI,8 [_2 OOI
UNIT AND UNGROUNDED SURFACES POWERENTRI SiDZ 9_4 O 136 GO]
UNIT AND BLOC_ OR (ONCRZT£ WALLS AND OIH[R
GROUNDED SURFACES, POWER ENTRT SIDE 106_ 8 {42 00)
Mit LIf4ETERS {IN]
WILLIW[1ERS [INI
I
!
4DE (I
115 831
--
II? 1
14 63]
SUPPLy R[TUNN I
DUCT - _UCI l"
OPENIN G OPENING
r i , , i jl
--8T 2 P,,-347 3
_35q ? _351 2
113831 [13 831
REAR ViEW
R£(ZURB) _ F_t (_/L'i'K_ A/_ SI_VII:IN6
_VAR COiL ACCESS SI_[ • • • _14 0 [36 00]
_OWER ENTRY SIDE 914 0 {3_ 001
(EXC[P1 PO_ N_C R[OUlR[MENTSi
UNll TOP .......... _ 0 {3G 00}
_IDE OPPOSITE OUCTS ...... _14 0 [3_ OO]
bUC! PANEL ...... _04 8 {12 00]_
tMINIMU_ OlSIANCES IF UNIT I_ PLACZO LESS THAN 3Oa 8 I1200] FRO_ WALL
DIMENSIONS IN I] ARE IN INCHES
_ILLIMEFERS IIN]
UNIT
50JZ042
50JZ048
50JZO60
i
ELECTRICAL CHARACTERISTICS
208/230-1.60, 208/230-3.60, 460-3.60 350 158.8
208/230-1.60, 208/230-3-60, 460-3-60 365 161.0
208/230-1-60, 208_230-3.60, 460-3-60 428 194.1
Fig. 3--50JZ 042-060 Unit Dimensions
UNIT WEIGHT
lb. kg
3
UNIT HEIGHT
IN. (MM)
,,A,,
40.98 (1040.9)
40,98 (1040,9)
42,98 (1091.7)
_ULt LO_V{r
;_l lid _1 o,, .o_iI _ '-
i?? o --
RIGHT SIDE VIEW
CENTER OF GRAVITY
IN. (MM)
X Y Z
21,0 (533,4) 20.5 (520,7) 16.6 (421,6)
20.0 (508.0) 21,3 (539,8) 18,0 (457.2)
21.0 (533.4) 20.0 (508,0) 17.6 (447,0)
{o i_]
(300161
1 2
Y
O
Z
CORNER WEIGHTS (SMALL CABINET) CORNER WEIGHTS (LARGE CABINET)
Unit
N
1. The power supply (volts, phase, and hertz) must correspond to
that specified on unit rating plate.
2. The electrical supply provided by the utility must be sufficient
to handle load imposed by this unit.
3. This installation must conform with local building codes and
with NEC (National Electrical Code). Refer to provincial and
local plumbing or waste water codes and other applicable local
codes.
Before performing service or maintenance operations on
system, turnoff main power to unit. Turn off accessory heater
power switch if applicable. Electrical shock could cause
severe injmy or death.
Puron (R_I-10A) systems operate at higher pressures than
standard R-22 systems. DO not use R-22 service equipment
or components on Puron (R4 10A t equipment. Ensure service
equipment is rated for Puron (RMIOA)
Tbe 50JZ heat ptanp is fully self contained and designed for
outdoor installation (See Fig. 1). Standard units are shipped in a
horizontal-discharge configuration for installation on a ground-
level slab, Standard units can be converted to downflow (vertical)
discharge configurations for rooftop applications.
Tnt_l W_inht
Comer Weight t
Comer Weight 2
Comer Weight 3
Comer Weight 4
INTRODUCTION
24
299
63
62
56
118
30 36
63 64
74 76
56 58
127 130
FJg. 4_CornerWeights
X
Unit
N Total Weight
..j
o
m Comer Weight 1
• Comer Weight 210
O
Step 1.---Check Equipment
IDENTIFY UNIT
The unit model number and serial number are stamped on the unit
identification plate. Check this information against shipping pa-
pet's.
INSPECT SHIPMENT
Inspect for shipping damage while unit is still on shipping pallet.
If unit appears to be damaged or is tom loose from its anchorage,
have it examined by transportation inspectors before removal.
Forward claim papers directly to transportation company• Manu-
facturer is not responsible for any damage incurred in transit.
Check all items against shipping list. Immediately notify the
nearest Carder Air Conditioning office if any item is missing. To
prevent loss or damage, leave all parts in original packages until
installation.
Step 2--Provide Unit Support
ROOF CURB
Install accessory roof curb in accordance with instructions shipped
with curb (See Fig. 5). Install insulation, cant strips, roofing, and
flashing. Duetwork must be attached to curb.
IMPORTANT: The go.¢keting of the unit to the roof curb is critical
for a watertight seal. Install gasketing material supplied with the
roof curb. Improperly applied gasketing also can result in air leaks
and poor unit performance.
Curb should be level to within 1/4 in. (See Fig. 6). This is
necessary for unit drain to function properly. Refer to accessory
roof curb installation instructions for additional information as
required.
4
Comer Weight 3
Comer Weight 4
RECEIVING AND INSTALLATION
3
42
350
75
49
95
131
48 60
355 428
76 92
50 60
96 116
133 160
000071
Roof Curb for Small Cabinet
Note A: When unit mounting screw is used,
retainer bracket must also be used.
T
Roof Curb for Large Cabinet
Note A: When unit mounting screw is used,
retainer bracket must also be used.
R/A
_-_Gasket around'_
\
duct
J
\ /
\\, /
'\\ /
S/A
' \
/
/
Insulated
deck pan
UNIT SIZE ODS CATALOG NUMBER iN. (MM)
A
50JZ024-036
50JZ042-060
NOTES:
1. Roof curb must be set up for unit being installed.
2. Seal strip must be applied, as required, to unit being installed.
3. Dimensions in ( ) are in millimeters.
4. Roof curb is made of 16-gage steel.
5. Table lists only the dimensions, per part number, that have changed.
6. Attach ductwork to curb (flanges of duct rest on curb).
7. Insulated panels: 1-in. thick fiberglass 1 Ib density.
8. Dimensions are in inches.
9. When unit mounting screw is used (see Note A), a retainer bracket must be used as well. This bracket must also be used when required by cede for hurdcane or
seismic conditions. This bracket is available through Micromet[
--)
CPRFCURB006A00 8 (203)
CPRFCURB007AO0 14 (356)
CPRFCURB008AO0 8 (203)
CPRFCURB009AO0 14 (356)
Fig. 5_Roof Curb Dimensions
B
IN. (MM)
11(279)
11(279)
163/16 (411)
16 3/16 (411)
Gasket around
outer edge \\
IN. (MM)
161/2 (419)
161/2 (419)
17 3/8 (441)
17 3/8 (441)
C
D
IN. (MM)
28-3/4 (730)
28-3/4 (730)
40-1/4 (1022)
40-1/4 (1022)
5
C00076
3
MAXIMUM ALLOWABLE
DIFFERENCE (in.)
B
A-B B-C / A-C
t/4 1/4 1/4
/
C99065
Fig. 6---Unit Leveling Tolerances
SLAB MOUNT
Place the unit on a solid, level concrete pad that is a minimum of
4 in. thick with 2 in. above grade (See Fig. 71. The slab should
extend approximately 2 in. beyond the casing on all 4 sides of the
unit. Do not secure the unit to the slab except when required by
local codes.
Step 4_Rig and Place Unit
Rigging and handling of this equipment can be hazardous for many
reasons due to the installation location (roofs. elevated structures.
etc. /
Only trained, qualified crane operators and ground support staff
should handle and install this equipment.
When working with this equipment, obserxe precautions in the
literature, on tags, stickers, and labels attached to the equipment,
and any other salety precautions that might apply.
Follow all applicable safety codes. Wear safety shoes and work
gloves.
INSPECTION
prior to initial use, and at monthly intervals, all rigging brackets
and straps should be visually inspected for any d_nage, evidence
of wear, structural deformation, or cracks, particular attention
should be paid to excessive wear at hoist hooking points and load
support areas. Brackets or straps showing an) kind of wear in these
areas must not be used and should be discarded.
GROUND MOUNT
The unit may be installed either on a slab or placed directly on the
ground if local codes permit. Place the unit on level ground
prepared with gravel for condensate discharge.
Step 3_Provide Clearances
The required minimum service clearances are shown in Figs. 2 and
3. Adequate ventilation and outdoor air must be provided. The
outdoor fan draws air through the outdoor coil and discharges it
through the top fan grill. Be sure that the fan discharge does not
recirculate to the outdoor coil. Do not locate the unit in either a
comer or under an overhead obstruction. The minimum clearance
under a partial overhang (such _s a normal house overhang! is 48
in. above the unit top. The maximum horizontal extension of a
partial overhang must not exceed 48 in.
IMPORTANT: Do not restrict outdoor airflow. An air restriction
at either the outdoor-air inlet or the fan discharge may be
detrimental to compressor life.
Do not place the unit where water, ice, or snow from an overhang
or roof will damage or flood the unit. Do not install the unit on
carpeting or other combustible materials. Slab-mounted units
should be at least 4 in. above the highest expected water and runoff
levels. Do not use unit if it has been under water.
INSTALLATION
I. Remove unit from shipping carton. Leave top shipping skid on
the unit as a spreader bar to prevent the rigging straps from
damaging the unit. If the wood skid is not available, use a
spreader bar of sufficient length to protect unit from damage.
2. Position the lifting bracket assembly around the base of the
unit. Be sure thestrap does not twist.
3. Place each of the 4 metal lifting brackets into the handholds in
the composite pan.
4. Thread lifting bracket strapping around bot/om perimeter of
unit 0s follows:
a. Open lever of tension buckle (ratchet type).
b. Feed strapping through tension buckle as shown in Fig. 8.
c. Pull strapping through tension buckle unit taut.
d. Snap lever down to lock strap in tension buckle. To release
strapping, squeeze safety latch, lift lever, and pull webbing
outward.
5. Tighten the tension buckle until it is taut. Lifting brackets
must be secure in the handholds.
6, Attach field-supplied clevis or hook of sufficient strength to
hole in the lifting bracket (See Fig. 91.
2-
EVAI_ COIL COND. COIL
Fig. 7--Slab Mounting Detail
C90096
6
HOOK
J
J
FEED
C99067
Fig. 8---Threading Belt
914-137"
136"-54")
SCALE0 250
tIGHTEN STRAPPING SECURELY
WfTH TENSION BUCKLE
INSTALL SAFE I_" _TRAPS TO
RIGGING CLEVI_ AT 4 RIGGING BRACKET_
PLACE RIGGING BRACKET A_SEMBLY IN 4
HANO HOLES AND INSTALL TIE DOWN STRAP
ARODND PERIMETER OF UNIT AND THROUGH
SPACE IN BRACKET ASSEMBLy
C99075
UNIT MAXIMUM WEIGHT A B
Size lb. kg in. mm. in, mm.
50JZ024 321 145.6 19.0 482.6 18.25 463.6
50JZ030 342 155.2 20.0 508 19,25 489
50JZ036 I 350 158.8 20.0 508 19.0 482.6
80JZ042 372 168,8 21.0 533.4 20.5 520.7
50JZ048 377 171.0 20.0 508 21.25 539.8
50JZ060 450 204.2 21.0 533.4 20.0 508.0
Fig. 9--Suggested Rigging
7. Attach the 2 safety straps directly to the clevis or hook at the
4 rigging brackets. DO NOT attach the safety straps to the
lifting brackets (See Fig. 9}.
8. Position lifting point directly over the tmit's center of _avity.
9. Lift unit. When unit is directly over the roof curb. remove the
2 safety straps. Lower the equipment onto the roof curb.
10. After the unit is placed on the roofcurb or mounting pad,
remove [he top crating. On 50JZ060 units only, 2 wire ties
fastened to the outdoor coils and reversing valve/accumulator
assembly must be cut. Remove the left and front louver panels
and corner post to access wire ties. The wire tie to he cut on
the left is located approximately 4" down the tube sheet. The
wire tie to be cut on the right is located approximately 6"
down the tube sheet.
Step 5--Select and Install Ductwork
The design and installation of the duct system must be in
accordance with the standards of the NFPA for installation of
D_TAIL A
non-residence type air conditioning and ventilating systems, NFPA
9flA or residence type. NFPA 90B and/or local codes and ordi
nantes.
Select and size ductwork, supply-air registers, and return air grilles
according to ASHRAE (Amefican Society of Heating, Refrigera
tion, and Air Conditioning Engineers) recommendations.
The unit has duct flanges on the supply and return-air openings on
the side of the unit.
When designing and installing ductwork, consider the following:
For vertical supply and return units, tools or parts could drop
into ductwork and cause serious injury or death. Install a 90
de_ee turn in the return ductwork between the unit and the
conditioned space. If a 90 degree elbow cannot be installed.
then a grille of sufficient strength and density should be
installed to prevent objects from falling into the conditioned
space. Units with electric heaters require 90 degree elbow in
supply duct.
I. All units should have field-supplied filters or accessory filter
rack installed in the return-air side of the unit. Recommended
sizes for filters are shown in Table 1.
2. Avoid abrupt duct size increases and reductions. Abrupt
change in duct size adversely affects air perforroance.
IMPORTANT: Use flexible connectors between ductwork and
unit to prevent transmission of vibration. Use suitable gaskets Io
ensure weather tight and airtight seal. When electric heat is
installed, use fireproof canvas (or similar heat resistant material)
connector between ductwork and unit discharge connection. If
flexible duct is used, insert a sheet metal sleeve inside duct. Heat
resistant duct connector (or sheet metal sleeve) must extend 24-in.
from electric heater element.
3. Size ductwork for cooling air quantity (cfm). The minimum
air quantity for proper electric heater operation is listed in
Table 2. Heater limit switches may trip at air quantities below
those recommended.
4. Seal. insulate, and weatherproof all external ductwork. Seal,
insulate and cover with a vapor barrier all ductwork passing
through conditioned spaces. Follow latest Sheet Metal and Air
Conditioning Contractors National Association (SMACNA)
and Air Conditioning Contractors Association (ACCA) mini-
mum installation standards for residential heating and air
conditioning system_.
5. Secure all ducts to building structure. Flash, weatherprooL and
vibration-isolate duct openings in wail or roof according to
good construction practices.
CONVERTING HORIZONTAL DISCHARGE UNITS TO
DOWNFLOW (VERTICAL) DISCHARGE UNITS
serious injury or death.
1. Open all electrical disconnects before starting any service
work.
2. Remove horizontal duct covers to access bottom return and
supply knock out panels.
3. Use a screwdriver and hammer to remove the panels in the
bottom of the bzL_e pan.
7
Table 1--Physical Data--Unit 50JZ
UNIT SIZE
NOMINAL CAPACITY (ton)
OPERATING WEIGHT (lb.)
COMPRESSOR QUANTITY
TYPE
REFRIGERANT
REFRIGERANT METERING DEVICE
Refrigerant (R-410A) Quantity (lb.)
ORIFICE ID (in.)
ORIFICE OD (in,)
OUTDOOR COIL
Rows.,. Fins/in.
face area (sq. ft.)
OUTDOOR FAN
Nominal Airflow (CFM)
Diameter
Motor HP (RPM)
INDOOR COIL
Rows._ Fins/in.
face area (sq. ft.)
INDOOR SLOWER
Nominal Airflow (CFM_
Size (in,)
Motor (HP)
HIGH-PRESSURE SWITCH (psig)
LOSS-OF-CHARGE/LOW-PRESSURE SWITCH
RETURN-AIR FILTERS (in._"
• Required tilter sizes shown are based on the larger of the ARI (Air Conditioning and Refrigeration Institute) rated cooling airflow or the heating airflow velocity of 300
if/minute for throwaway type or 450 if/minute for high-capacity type. Air tilter pressure drop for non-standard filters must not exceed 0.08 in. wg.
Cutout
Reset (Auto)
(Liquid Line) (psig)
Cutout
Reset (Auto)
throwaway
50JZ024 I 50JZ030 50JZ036 50JZ042 50JZ048 I 50JZ060
2 I 2-1/2 3 3-1/2 4 I 5299 320 328 350 355 428
1
SCROLL COMPRESSOR
R-410A
Accurater
7.0 8.9 9.3 9.5 10,6 12.4
0.061 0.061 0.067 0.073 0.076 0.088
0.032 (2) 0.040 (2) 0.040 (2) 0.038 (2) 0.046 (2) 0.052 (2)
2...17 2...17 2...17 2...J7 2..._7 2...17
8.5 10.3 10.3 13.5 13.5 15.4
2350 2350 2800 2500 3300 3300
22 22 22 22 22 22
1/8 (825) 1/8 (825) 1/4 (1100) 1/8 (825) 1/4 (1100) 1/4 (1100)
3...15 3...15 4...15 3...15 4...15 4,..15
3.7 3.7 3.7 4.7 4.7 / 5.7
10x10 10x10 10x10 11x10 11x10 11x10
800 1000 1200 1400 1600 / 1750
1/4 1/4 1/2 1/2 1/2 1
610 ± 15
420 ± 25
20± 5
45± 10
20x20x1f20x20Xli 20x2,xlf24x30 1f 24x30Xlf 2,x30x1
NOTE: These panels are held in place with tabs similar to an
electrical knockout.
4. Reinstall the horizontal duct covers (Fig, 11) to block off the
horizontal air openings.
NOTE: Avoid abrupt duct size increases anti reductions. Abrupt
change in duct size adversely affects air performance.
Step 6--Provide for Condensate Disposal
NOTE: Ensure that condensate-water disposal methods comply
with local codes, restrictions, and practices.
The 50JZ units dispose of condensate through a 3/4 in. NPT female
fitting that exits on the compressor end of the unit. Condensate
water can be drained directly onto the roof in rooftop installations
(where permitted) or onto a gravel apron in ground level installa-
tions, Install a field-supplied condensate trap at end of condensate
connection to ensure proper drainage. Make sure that the outlet of
the trap is at least I in. lower than the drain-pan condensate
connection to prevent the pan from overflowing. Prime the trap
with water. When using a gravel apron, make sure it slopes away
from the unit.
If the installation requires draining the condensate water away
from the unit, install a field-supplied 2 -in. trap at the condensate
connection to ensure proper drainage. Conden,_ate trap is available
as an accessory or is field supplied. Make sure that the outlet of the
trap is at least I in. lower than the unit drain-pan condensate
connection to prevent the pan from overflowing. Connect a drain
trough using a minimum of field-supplied 3/4 -in. PVC or
field-gupplJed 314 .in. copper pil)_ _ outh_l elt_ of _ 2 -in.
(See Fig. 12). Do not undersize the tube. Pitch the drain trough
downward at a slope of at least 1 in. every, 10 ft. of horizontal run.
Be sure to check the drain trough for leaks. Prime the trap at the
beginning of the cooling season start-up.
Step 7_nstall Electrical Connections
r_ 'kk_r:_ttLllT[d
The unit cabinet must have an uninterrupted, unbroken
electrical ground to minimize the possibility of personal
injury if an electrical fault should occur. This ground may
consist of an electrical wire connected to the unit ground lug
in tile_ontrol compartment, or conduit approved for electrica_
ground when installed in accordance with NEC, ANSI/NFPA
American National Standards Institute/National Fire Protec-
tion Association (latest edition) iin Canada, Canadian Elec-
trical Code CSA C22.1) and local electrical codes. Failure to
adhere to this warning could result in serious injury or death.
Table 2_Minimum Airflow for Reliable Electric Heater Operation (Cfm)
SIZE 50JZ024 50JZ030 50JZ036 50JZ042 50JZ048 50JZ060
AIR FLOW (CFM) 800 1000" 1200 1400 1600 2000
• The 030 size mOdels must be run on medium or high speed when used in conjunction with 15 kW electric heataccessory
INDOOR
I THERMOSTAT
@
FROM
SOURCE
Fig. 10--Typical Installation
1" MIN.
_t 2" MIN.
DISCONNECT
PER NEC*
*NEC - NATIONAL ELECTRICAL CODE
C00063
TRAP
OUTLET
C99013
Fig. 12_Condensate Trap
Duct Covers
Fig. 11--50JZ with Duct Covers On
C00092
Failure to follow these precautions could result in damage to
the unit being installed:
I. Make all electrical connections in accordance with NEC
ANSI/NFPA Ilatest edition) and local electrical codes
governing such wirthg. In Canada, all electrical connec-
tions must be in accordance with CSA standard C22.1
Canadian Electrical Code P,'u-t I and applicable local
codes. Refer to unit wiring diag,am.
2. Use only copper conductor for connections between
field-supplied electrical disconnect switch and unit. DO
NOT USE ALUMINUM WIRE.
3. Be sure that high-voltage power to unit is within operating
voltage range indicated on unit rating plate. On 3-phase
units, ensure pbases are balanced within 2 percent. Consult
local power company for correction of improper voltage
and/or phase imbalance.
4, Insulate low-voltage wires for highest voltage contained
within conduit when low-voltage control wires are in same
conduit as high-voltage wires.
5. Do not damage internal components when drilling through
any panel to mount electrical hardware, conduit, etc.
HIGH-VOLTAGE CONNECTIONS
The unit must have a separate electrical service with a field-
supplied, waterproof disconnect switch mounted at, or within sight
from the unit. Refer to the unit rating plate, NEC and local codes
for maximum fuse/circuit breaker size and minimum circuit amps
(ampacity) for wire sizing (See Table 3 for electrical data}.
The field-supplied disconnect may be mounted on the unit o_'er the
high-voltage inlet hole (See Figs. 2 and 3).
If the unit has an electric heater, a second disconnect may be
required. Consult the lnstullation, Start-Up, and Service Instruc-
tions provided with the accessory for electrical service connec-
tions.
Operation of unit on improper line voltage constitutes abuse and
may cause unit damage that could affect warranty.
ROUTING POWER LEADS fNTO UNIT
Use only copper wire between disconnect and unit. The high-
voltage leads should be in a conduit until they enter the duct panel;
conduit termination at the duct panel must be watertight. Run the
high-voltage leads through the power entry knockout on the power
entry side panel ISee Fig. 2 and 3 for location and size). When the
leads are inside the unit. run leads up the high-voltage raceway to
the line wiring splice box (See Fig. 13 through 15). For single-
phase units, connect leads to the black and yellow wires; for
3-phase units, connect the leads to the black, yellow, and blue
wires (See Fig. 18).
CONNECTING GROUND LEAD TO GROUND LUG
Refer to Fig. 18. Connect the ground lead to the chassis using the
ground lug in the wiring splice box.
ROUTING CONTROL POWER WIRES (24-V)
Form a drip-loop with the thermostat leads before routing them
intu the unit. Route the thermostat leads through grommeted,
low-voltage hole provided in unit into unit control power splice
box (See Fig. 2 and 3). Connect thermostat leads to unit control
power leads as shown in Fig. 17.
The unit transformer supplies 24-v power for complete system
including accessory electrical heater. An automatic-reset circuit
breaker (See Fig. 19) is provided in the 24-v circuit; see the caution
label on the transformer or Fig. 20. Transformer is factory wired
lor 230-v operation. If supply voltage is 208-v, rewire transformer
primary, as described in Special Procedures for 208-v Operation
section.
SPECIAL PROCEDURES FOR 208-V OPERATION
I. Be sure unit disconnect switch is open.
2. Disconnect the yellow primary lead /w 110) from the trans-
former. See unit wiring label 1See Fig, 13 and 141.
3. Connect the yellow primary lead (wl i0) to the transformer
terminal labeled 200-v.
Indoor blower-motor speeds may need to be changed for 208-v
operation. Refer to indoor airflow and airflow adjustments section.
PRE-START-UP
r.', LV/_q 2WE_
Failure to observe the following warnings could result in
serious personal injury or death:
1. Follow recognized safety practices and wear protective
goggles when checking or servicing refrigerant system.
2. Do not operatecompressor or provide any electric power to
unit unless compressor terminal cover is in place and
secured.
3. Do not remove compressor terminal cover until all electri-
cal sources are disconnected.
4. Relieve and recover all refrigerant from both high- and
low-pressure sides of system before touching or disturbing
anything inside terminal box if refrigerant leak is suspected
around compressor terminals.
5. Never attempt to repair soldered connection while refrig-
erant system is under pressure.
6. Do not use torch to remove any component. System
contains oil and refrigerant under pressure.
To remove a component, wear protective goggles and
proceed as follows:
a. Shut off electrical power to unit.
b. Relieve and reclaim all refrigerant from system using
both high- and low-pressure ports.
c. Cut component connecting tubing with tubing cutter and
remove component from unit.
d. Carefully unsweat remaining tubing stubs when neces-
sary. Oil can ignite when exposed to torch flame.
Use the Start-Up Checklist supplied at the end of this book and
proceed as follows to inspect and prepare the unit for initial
start-up:
1. Remove all access panels.
2. Read and follow instructions on all DANGER, WARNING,
CAUTION, and INFORMATION labels attached to, or
shipped with, unit.
3. Make the following inspections:
a. Inspect for shipping and handling damages such as broken
lines, loose parts, disconnected wires, etc.
b. Inspect for oil at all refrigerant tubing connections and on
unit base. Detecting oil generally indicates a refrigerant
leak. Leak-test all refrigerant tubing connections using
electronic leak detector, or liquid-soap solution. If a refrig-
erant leak is detected, see following Check for Refrigerant
Leaks section.
c, Inspect all field and factory-wiring connections. Be sure
that connections are completed and tight.
d. Inspect coil fins. If damaged during shipping and handling,
carefully straighten fins with a fin comb.
4. Verify the following conditions:
10