Carrier 50JZ036310, 50JZ042300, 50JZ048300, 50JZ036300, 50JZ030310 Installation Guide

...
HFATUNG & COOLING
%isitx__ _.¢arrier.com
Installation, Start-Up and Service instructions
50JZ 7-t4 kW (024-048)
SingMe-Package 50Hz Heat Pump Units
with Puron® (R-410A) Refrigerant
NOTE: Read the entire instruction manual be%re starting the installation.
TABLE OF CONTENTS
SAFETY < ONSIDERATIONS 1 Introduction 2
Receiving and Installation .............................................................. 2
(heck Equipment ...................................................................... 2
Provide -Unit Support ................................................................ 2
Provide Clearances ................................... 2
Rig and Place Unit ................................... 3
Select and Install Ductwork ........................... 5
Converting Horizontal Discharge Units To
Provide for Condensate Disposal 7
Install Electrical Connections ................................................... 9
Routing Powm Leads into Lnit .................... 1l
Connecting Ground Lead to Ground Lug ............. 1l
Routing Control Power Wires (24-V) i 1
PRE-START-UP !4 START-UP 14
(beck f_r Refrigerant Leaks 14 Start-Up Adjustments 14
No ( harge .................................... !6
Defiost ( ontrol ....................................................................... 18
MAINTENANCE .................................... 20
Air Filter .......................................... 20
Indom Blower and Motor ........................... 21
Outdoor (oil, Indoor Coil, and Condensate D*ain......... 21
Outdoor Fan ...................................... 2l
Eleckical Controls and Wiring ...................... 22
Refrigerant Circuit ................................. 22
Indoor Airflow ................................... 22
PURON_R:Systems Items .......................... 22
System Infbnamtion .............................. 24
Phase Monitor Control .......................... 24
TROL BLESHOOTING ............................................................... 24
Start°L p Checklist ........................................................................ 24
NOTE TO INSTALLER READ THESE INSTRUCTIONS CAREFULLY AND COMPLETELY befbre installing this unit.
Also, nmke sure the Owner's Manual and Se*vice Instructions are left with the unit afle* installation
SAFETY CONSIDERATIONS
Installation and servicing of air-conditioning equipment can be hazardous due to system pressure and electrical components Only trained and qualified personnel should install, repair, or service air-conditioning equipment.
Untrained personnel can perfbrm basic nmintenance functions of cleaning coils and filters. All other operations should be performed by trained service personnel. When working on air-conditioning equipment, observe precautions in the literature, tags, and labels attached to the unit, and other safety precautions that may apply.
Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth fbr unbrazing operations. Have fire extinguisher
available for all brazing operations.
Improper installation, adjustment, alteration, service, nmiute° nance, or use can cause explosion, fire, electric shock, or
other occurrences, which could cause serious injury or death or danmge your proper U. Consult a qualified installer or
service agency for infbrmation or assistance. The qualified installer or agency must use only fhctory-authorized kits or accessories when modifying this product
Recognize safety information. This is the safhty-alert symbol/\. When you see this symbol on d'*e product or in instructions or manuals, be alert to the potential fbr personal injury
Understand die signal words DANGER, WARNING, (AU° TION, and NOTE Danger identifies the most serious hazards, which will result in severe personal injury or death. Warning indicates a condition that could cause serious personal injury or death. Caution is used to identif}' unsaf_ practices, which would result in minor personal injmy or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliabili w, or operation.
1. The power supply (volts, phase, and hertz) must correspond to that specified on unit rating plate.
2. The electrical supply provided by the utility must be sufficient to handle toad imposed by this unit.
3. This installation must confbrm with local building codes and with IE( (International Electrical (ode). Refer to provincial
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
PC 101 Catalog No. 005-00027 Printed in U.S.A. Form 50JZ-C2SI Pg 1 7-02 Replaces: 50JZ-C1SI
Fig. 1--UNt 50JZ (50 Hz)
and local plumbing or _xaste water codes and other applicable local codes
Be%re per%rming service or maintenance operations on system, turn off main power to unit. Turn off accessory heater
power switch if applicable Electrical shock could cause
severe injury or death
Puron (R-410A) systems operate at higher pressures than standard R=22 systems. DO not use R=22 service equipment or components on Pnron (R-410A) equipment. Ensure service
equipment is rated for Puron (R-4IOA)
INTRODUCTmON
The 50JZ (50 Hz) heat pump is fhlly selfocontained and designed fbr otttdoor installation (See Fig. 1) Standard units are shipped in a horizontal-discharge configuration for installation on a ground=
level slab Standard units can be converted to downflow (vertical) discharge configurations for rooftop applications
RECEIVING AND INSTALLATION
Step 1--Check Equipment IDENTIFY UNIT
The unit model number and serial nm'nher are stamped on the unit rating identification plate. Check this infbrmafion against ship= ping papers.
INSPECT SHIPMENT
Inspect tbr shipping damage while unit is still on shipping pallet
If unit appears to be damaged or is torn loose ti'om its anchorage, have it examined by transportation inspectors be%re removal. Fopxard claim papers directly to transportation company. Manu=
fitcmrer is not responsible fbr any damage incurred in transit.
Check all items against shipping list. Immediately notify the nearest ( mTier Air Conditioning once if any item is missing. To prevent toss or damage, leave all parts in original packages until
installation.
C99064
Step 2--Provide Unit Support ROOF ([RB
Install accessory roof curb in accordance with instrt/cfions shipped with curb. (See Fig. 5) Install insulation, cant strips, roofing, and flashing Ductwork must be attached to cuIS.
INPORTANT: The gasketing of the nnit to the roof cm:b is critical for a watertight seal Install gasketing material supplied with the roof curb Improperly applied gasketing also can result in air leaks and poor unit perfbrmance
Curb should be level (See Fig. 6) to within 1/4 in. (6.4 ram). This is necessa_" t'or unit &ain to fimction properly. Refkr to accessow-
roof curh installation instructions for additional infbrmation as required.
SLAB MOUNT
Place the unit on a solid, level concrete pad that is a minimum of 4 in. (102 ram) thick with 2 in. (51 ram) above grade. (See Fig. 7) The slab should extend approximately 2 in. (51 ram) beyond the casing on all 4 sides of the unit. Do not secure the unit to the slab except when required by local codes.
GROUND MOUNT The unit may be installed either on a slab or placed directly on the
ground if local codes permit. Place the unit on level ground prepared with gravel fbr condensate discharge.
Step a--Provide Clearances The required minimum service clearances are shown in Figs 2 and
3 Adequate ventilation and outdoor air must be provided. The outdoor fire &aws air through the outdoor coil and discharges it through the top fYn grill. Be sure that the fan discharge does not
recirculate to the outdoor coil. Do not locate the unit in either a corner or under an overhead obstruction. The minimum clearance
under a partial overhang (such as a nom_al house overhang) is 48 in. (1219 ram) above the unit top. The maximum horizontal extension of a partial overhang must not exceed 48 in. (1219 ram).
IMPORTANT: Do not restrict outdoor airflow. An air restriction at either the outdoor=air inlet or the fire discharge may be
detrimental to compressor tifk Do not place the unit where water, ice, or snow fi'om an overhang
or roof will damage or flood the unit Do not install the unit on
il..........................r LLLo vE l
Tt
406 5
[_6 60]
EVAP l
TOP VIEW
RE'G_RED CLEARANCES TO COMBtIS_BLE MA'n-
TOP OF UNIT ............................................. 3556 [1400]
DUCT SiDE OF RNIT ......................................... 508 {200]
SIDE OPPOSITE DUCTS ..................................... 3556 [14001
BOTTOM OF UNIT ............................................ 127 {0501
ELECTRIC HEAT PANEL ..................................... 9144 [36001
NED. REQUIRED CLEARANCE&
BETWEEN UNITS, POWER ENTRY SIDE ........................ 10668 [4200]
UNiT AND UNGROUNDED SORTADES, POWER ENTRY SIDE .......... 914¸0 [3600]
UNiT AND BLOCN OR CONCREIE WAILS AND OTHER
GROUNDED SURFACES, POWER ENTRY SIDE .................. 1066¸8 [4200]
{31 44/
_IEIR _NTRY
S£RV_CE PORTS
11939
loiH
i" -n
MiLLiMETERS [iN]
MIllIMETERS [IN]
[47 O0
4020 [_583]
SUPP{ Y DUCT
OPENING
i ;
177
Y
{463]
}
885 ....................................
[3¸48}
D_EeN_LEARANG_TO_ ORERM_'_ON AND SERVICINB
EVAP COIL ACCESS SIDE .................................. 914¸0 [36¸001
POWER ENTRY Si0E ........................................ 914¸0 [36.001
(EXCEPT HOH NEE REOUIREWENTS)
UNIT TOP ................................................ 914¸0 [36¸001
SiDE OPPOSITE 00GTS ..................................... 914¸0 [36¸001
DUCT PANEL .............................................. 304¸8 [12061,
*NININON DISTANCES:IF UNiT IS P{ACED LESS THAN 3048 [JRO0] FRON WALL
SYSTEM,IHEN SYSIEN PER;ORNANCE NAY_E COMPROMISER
24£¸6 I983]
I
_5505
REAR VIEW
t I
[2167]
NILLIMETERS [IN1
RETURN DUCT OPENING
[9831
A
i I i _
[168]
[2851
_12851
13212]
LCO_PRESSOR, BLOWER, EtECJRIC HEAY
& ELECTRICAL ACCESS PANgL
................................................._2263 ..........................................................
[48 281
LEFT SIDE VIEW FRONTVIEW RIGHT SIDE VIEW
UNiT
80JZ024
80JZO30 50JZ036
ELECTRICAL CHARACTERiSTiCS
400-3-50 400-3-50
400-3-50
UNIT WE_GHT
Ib kg
299 135.6 320 145.2
328 148.8
Fig. 2--50JZ024-036 Unit Dimensions
carpeting or other combustible materials Slab=mounted malts should be at least 4 in. (101.6 ram) abo_e the highest expected
v, ater and runoff levels Do not use unit if it has been under water.
Step 4--Rig and Place Unit Rigging and handling of this equipment can be hazardmEs %r many
reasons due to the installation location (roo£q, elevated structures,
etc,)
-}..LO..i
..62 l ' _
.......i [IO 87} 13_ / ........ ,
7 4 _-- 445 { 75] DIA K 0
{4 81]
C00160
UNIT HEBGHT
IN.(MM)
"A"
35.02 (889.5)
37.02 (940.3)
37.02 (940.3)
Only trained, qnalified crane operators and ground support staff should handle and install this equipment,
When working with this equipment, obseza'e precautions in tlae literature, on tags, stickers, and labels attached to the equipment, and any other safety precautions that might apply.
Follow all applicable safety codes. Wear safety shoes and work gloves.
19.0 (482.6) 18.3 (463.6) 16.0 (406.4)
20.0 (508.0) 19.3 (489.0) 17.6 (447.0)
20.0 (508.0) 19.0 (462.6) 16.5 (419.1)
CENTER OF GRAVITY
IN.(MM)
X Y Z
. FULL LOUV[R
J
I
EVAP c011
° /
CO_l) COil
TOP VIEW
REQ4JIRB_CLEARANCES TO COr_BIJSTIBLE MAll..
lOP OF UNIT ........................................... 3556 [1400]
DUCT SIDE OF UNIT ......................................... 508 [?OO]
SIDE OPPOSITE DUCTS ..................................... 355¸6 [14OO]
_OTTOM OP UNIT ............................................ 127 [OSO]
ELECTRIC NEAT PANEl..................... 9}4¸4 {36 00}
NEC. REel]RED CLEARANCES.
BETWEEN UNITS, POWER ENTRY SIDE ........................ 10668 [420DI
UNIT AND UNGROUNDED SURFACES, POWER ENTRY SIDE .......... 9}4¸0 [3DOO]
UNIT AND BLOCK OR CONCRETE WALES AND OTHER
GROUNDED SURFACES, POWER ENTRY S{DE ...... {066 8 {42 00]
.............................................I090_ ............................................
[4294]
FULL _OUV#R
SERVICE PORTS
F_E_D [NTRY_
....................................... I
MILLIMETERS IIN]
MILL!ME]ENS [IN]
................................................ 11_39 ...................................................
[47 00)
4020 [5831
t
117 7
SUPPLY RETURN
DUCT DUCT
OPEN NG OPEN NG
,il'
l i J
_81,2 _3AYS
1S,431 IIS 6YI
_351 ? _ _331,2
I13_DSI I13_831
REAR VIEW
REQUIRED CLEARANCE FOR OPERATION AND SB_IVICING
EVAP CO{L ACCESS SIDE ................................. 914¸0 [36¸001
POWER ENTRY SIDE ........................................ 914D [36¸001
{EXCEPT FOR NED REQUIREMENTS}
UNIT TOP ................................................ 9140 [36¸00I
SIDE OPPOSITE DUCTS ............................... 914¸0 [36¸001
DUCT PANZL ............................. 304 8 {I?OO}_
_MINIMNM D!STANDES:IF UNIT IS PLACED LESS THAN 3048 [!DOO] FROM WALL
SYSTEM,THEN SYSTEM PERFORMANCE MAYDE COMPROMISED
DIMENSIONS IN {} ARE IN INCHES
MILLIMETERS [IN}
FULL LOUVZR
620 2
'14.'i
[48 28
FRONT VIEW
UNIT
50JZ048
ELECTRICAL CHARACTERiSTiCS IN. (Mivl}
400-%50 355 161.0 40.98 (1040.9)
[NSPE(TION
Prior to initial use, and at monthly intervals, all rigging brackets
and straps should be visually inspected for any damage, evidence
of wear, structural deformatiom or cracks. Pa_1icular attention
should be paid to excessive wear at hoist hooking points and load
support areas. Brackets or straps showing any kind of wear in these
areas must not be used and should be discarded.
[NSTALLATION
1, Remove unit li'ona shipping carton. Leave top shipping skid on
the unit as a spreader bar to prevent the rigging straps flora
UNIT WEIGHT UNIT HEIGHT
tb kg "A"
Fig. 3--50JZ 048 Unit Dimensions
44 5 [{ 75101A K O_
POWER _NTRY
.............. 4
0 161
'2;'- L_
[4 81 RIGHT SIDE VIEW
CENTER OF GRAVITY
IN. {MN)
X Y Z
200 (508.0) 21.3 (539.8) 18.0 (457.2)
damaging the unit. If the wood skid is not available, use a spreader bar of sufficient length to protect unit fi'orn damage.
2,
Position the ti_ing bracket assembly around the base of the unit. Be sure the strap does not twist
3,
Place each of the 4 metal lifting brackets into the rigging holds in the composite unit base
4,
Thread lifting bracket strapping around bottom perimeter of unit as follows:
a Open lever of tension buckle (ratchet type) b. Feed strapping through tension buckle as shown in Fig 8
C00161
1
Y
4 x 3
CORNER WEIGHTS (SMALL CABRNET)
N
O
o
c Pull strapping through tension buckle unit taut. d. Snap lever down to lock strap in tension buckle. To release
strapping, squeeze safkty latch, lift lever, and pull webbing outward
5. Tighten the tension buckle until it is taut Lifting brackets n-rest be secure in the rigging holds
6. Attach field-supplied clevis or hook of sufficient strength to hole in the lifting bracket. (See Fig 9)
7. Attach the 2 safkty straps directly to the clevis or hook at the 4 rigging brackets. DO NOT attach the safkty straps to the
lifting brackets. (See Fig 9)
8. Position lifting point directly over the unit's center of gravity
9. Lift unit When unit is directly over the roof curb, remove the
2 safBty straps. Lower the equipment onto d3e roof curb
10. After the unit is placed on the roofcurb or mounting pad, remove [he top crating.
Step 5--Select and hstaH Duetwork The design and installation of the duct system must be in
accoIdance with [he standards of [he NFPA for installation of non-residence type air conditioning and ventilating systems, NFPA
90A or residence-Vpe, NFPA 90B an_or local codes and ordi- nances
Select and size ductworl% supply_air registers, and return air grilles according to ASHRAE (American Society of Heating, Ret'rigerao tion, and Air Conditioning Engineers) recommendations.
The unit has duct flanges on the suppty_ and returnoair openings on the side of [he unit.
When designing and installing ductwork, consider the _bllowing:
Unit
Total Weiqh_
Corner Weight 1 Corner Weight 2
Corner Weight 3 Corner Weight 4
24 30
18_ 14_
28.5 28.5 28 33.5 25 25
53.5 58
Fig. 4_Comer Weights (kg)
CORNER WEIGHTS (LARGE CABINET)
36
149
29
34.5 26 59
IMPORTANT: Use flexible connectors between ductwork and unit to prevent transmission of vibration. Use suitable gaskets to
ensure weather tight and airtight seal. When electric heat is installed, use fireproof canvas (or similar heat resistant material) connector between ductwork and unit discharge connection. If
flexible duct is use& insert a sheet metal sleeve inside duct. Heat resistant duct connector (or sheet metal sleeve) must extend 24-in.
(610 ram) fi'om electIic heater element.
N
O
o
For vertical supply and return units, tools or parts could &op into dnctwork and cause serious injury or death Install a 90 degree mrn in the return ductwork between the unit and the conditioned space. If a 90 degree elbow cannot be installed. then a grille of sufficient strength and density should be installed to prevent objects fiom fi_lling into the conditioned space Units with electric heaters require 90 degree elbow in supply duct
1 All units should have field-supplied filters or accessory filter
rack installed in the return-air side of the unit. Recommended sizes _br filters are shown in Table 1
2. Avoid abrupt duct size increases and reductions. Abrupt change in duct size adversely affects air per_bm_ance.
3. Size ductwork _br cooling air quantity (CFM or L/s). The minimum air quantity fbr proper electric heater operation is listed in Table 2. Heater limit switches may trip at air quantities below those recommended.
4. Seal, insulate, and weatherproof all external ductwork. Seal, insulate and cover with a vapor battier all ductwork passing through conditioned spaces. Follow latest Sheet Metal and Air (onditioning Conkactors National Association (SMACNA) and Air ( onditioning Contractors Association (AC(A) mini- mum installation standards for residential heating and air conditioning systems.
Unit
Total Weight
Corner Weight 1 Corner Weight 2
Corner Weight 3 Corner Weight 4
C00071
48
161
34.5 23
43.5 60
Roof Curb for Smart Cabinet
Note A: When unit mounting screw is used,
retainer bracket must also be used.
01255mm)
Roof Curb for Large Cabinet
Note A: When unit mounting screw is used,
retainer bracket must also be used.
\
R/A
A
_Gasket around_
\
\
\
\
duct
S/A
/2
s ipport
Loug
Support
Retur iopen ng
(B X C)
UNIT SBZE ODS CATALOG NUMB_::R
50JZ 024-036
80dZ 048
NOTES: 1 Roof curb must be set up for unit being instalbd.
2 Seal strip must be applied, as required, to unit being installed. 3 Dimensions in ( ) are in milfimeters
4 Roof curb is made of 16-gage steel.
5 Table lists only the dimensions, per part number, that have changed. 6 Attach ductwork to curb (flanges of duct rest on curb) 7 insulated panels: ldn (254 mm) thick fiberglass 1 Ib (45 kg) density.
8 Dimensions are in inches 9 When unit mounting screw is used (see Note A), a retainer bracket must be used as well This bracket must also be used when required by code for hurricane or
seismic conditions This bracket is available through Micrometl
CPRFCURB006A00 8 (203) 11(279) 161/2 (419) 26-3/4 (730) CPRFCURB007A00 14 (356) 11(279) 161/2 (419) 28-3/4 (730)
CPRFCURB008A00 8 (203) 16 3/16 (411) 17 3/8 (441) 40-1/4 (1022) CPRFCURB009A00 14 (356) 16 3/16 (411) 17 3/8 (441) 40-1/4 (1022)
A B C D
IN. {MM) IN. (MM) IN. {MN} IN. (NM)
Insulated deck pan
Gasket around
outer edge \
\"\4
'\
C00076
Fig. 5--Roof Curb Dimensions
5, Secure ai! ducts to building structure, Flash, _ eatherproof, and
_ibration=isolate duct openings in _xall or roof according to
good construction practices
3
MAXIMUM ALLOWABLE
DIFFERENCE (in.)
A-B B-C A-C
1/4 1/4 1/4
C99065
Fig. 6--UnBt Leveling ToMrances
Illll Itlll
Illll I1111
It111 It111
2 _r
mL
EVAR COIL COND. COIL
C99096
Fig. 7--Slab Mounting Detail
HANDHOLD
/
HOOK
Fig. 8--Threading Be{t
CONVERTING HORIZONTAL DISCHARGE UNITS TO DOVv%*FLOW(VERTICAL) DISCHARGE LNITS
Before perfc_rming service or maintenance operations on system, trim off main power to unit. Turn off accessory heater
power switch if applicable. Electrical shock could cause
serious injury or death.
1. Open all electrical disconnects before starting any service work
2. Remove horizontal duct covers to access bottom remm and supply knock out panels.
3. Use a screwdriver and hammer to remove the panels in the
bottom of the unit base.
NOTE: These panels are held in place with tabs similar to an electrical knockout
4. Reinstall the horizontal duct covers (Fig. 11) to block offthe
horizontal air openings.
FEED
C99067
NOTE: Avoid abrupt duct size increases and reductions Abrl/pt change in duct size adversely affects air performance.
Step 6--Provide for Condensate Disposal
NOTE: Ensure that condensate-water disposal methods comply with local codes, restrictions, and practices.
The 50JZ units dispose of condensate through a 3/4 in. NPT (I9.05 ram) f_male fitting that exits on the compressor end of d'*e unit. Condensate water can be drained directly onto the roof in rooflop installations (where permitted) or onto a gravel apron in ground level installations. Install a field-supplied condensate trap at end of condensate connection to ensure proper drainage. Make sure that the outlet of the trap is at least 1 in. lower than the &ain condensate connection to prevent the drain fi'om overflowing. Prime the trap with water. When using a gravel apron, make sure it slopes away
I_'om the unit.
If the installation requires draining the condensate water away from the unit, install a field-supplied 2 -in. (50.8 ram) trap at the condensate connection to ensure proper &ainage. Condensate trap is available as an accessory or is field-supplied. Make sure that the
DETAIL A
SCALE 0250
TIGHTEN STRAPPING SECURELY WITH TENSION BUCKLE
= INSTALL SAFETY STRAPS TO
RIGGING CLEVIS AT 4 RIGGING BRACKETS
PLACE RIGGING BRACKET ASSEMBLY IN 4 RIGGING HOLES AND INSTALL TIE DOWN STRAP
AROUND PERIMETER OF UNIT AND THROUGH
SPACE IN BRACKET ASSEMBLY
in.
19.0
20.0
20.0
20.0
C99075
A
mm.
482.6 5O8
5O8 5O8
in.
18.25
19.25
19.0
21.25
B
mm.
463.6 489
482.6
539.8
UNiT
Size
80JZ024
80JZ0S0 80JZ036 80JZ048
SEE DETAIL A
MAXBMUMWEJGHT
tb kg
321 145.6 342 155.2
350 158.8 377 171.0
Fig. 9--Suggested RiggBng
Table 1--Physicam Data-UnR 50JZ (50Hz}-English
UNIT SIZE
NOMINAL CAPACITY (ton} OPERATING WEBGHT (lb.)
COMPRESSOR QUANTITY
TYPE
REFRIGERANT
REFRBGERANT METERBNG DEVICE
Refrigerant (R-41OA} Quantity (lb.)
ORIFICE ID (in.}
ORIFICE OD (in.}
OUTDOOR CO_L
Rows... Finslin.
face area (sq. ft.}
OUTDOOR FAN
Nomina_ Airflow (CFM}
Diameter
Motor HP (RPM)
_NDOOR COBL
Rows... Fins/in.
face area (sq. ft.}
mNDOOR BLOWER
Nomina_ Airflow (CFM)
Size (in.)
Motor (HP}
RETURN-AIR HLTERS (in,)*
throwaway
Required filter sizes shown are based on the larger of the ARI (Air Conditioning and Refrigeration Institute) rated cooling airflow or the heating airflow velocity of 300
ft/minute for throwaway type or 450 if/minute for high-capacity type. Air filter pressure drop for non-standard filters must not exceed 0.08 in wg
80JZ024
2
299
50JZ08O 50JZ088
2-1/2 3
320 328
80JZ048
4
355
1
SCROLL COMPRESSOR
R-410A
Accurater
6.9
0.059
0.032 (2)
2...17
8.5
2200
22
1/4...900
3...15
3.7
800
10x10
1/2
9.6
0.061
0.040 (2)
2...17
10.3
2200
22
1_...900
3...15
3.7
1000
10x10
1/4
10.0
0.067
O.040 (2)
2...17
10.3
22OO
22
1/4...900
41..15
3.7
1200
10x10
1/2
12.0
0.078
0.046 (2)
2...17
13.5
2400
22
1/3...1340
4...15
4.7
1600
11x10
1
20x20x1 20x20xl 20x24xl 24x30xl
outlet of the tlap is at least 1 in, (25,4 mnx) lower than the unit drain condensate connection to prevent the &ain flora overflow° ing (onnect a drain tlough using a n_inil*num of _ield-supplied
3/4=in PVC (19,05 ram) o1"copper pipe at outlet end of the 2=in (508 nxm) trap (See Fig 12) Do not undersize the tube, Pitch the drain t*ough downward at a slope of at 1east 1 in, (254 mnx) eve W
Table 2--PhysicN Data-UNt 50JZ (50 Hz)-SI
UNIT SiZE
NOMINAL CAPACBTY (kW} OPERATING WEBGNT (kg}
COMPRESSOR QUANTITY
TYPE
REFRBGERANT
REFRIGERANT METERBNG DEVtCE
Refrigerant (R-410A) Quantity (kg)
ORIFICE ID (ram)
ORIFICE OD (ram)
OUTDOOR COiL
Rows.,. Finstin.
Face Area (sq. m)
OUTDOOR FAN
Nomina_ Airflow (L/s)
Diameter (ram)
Motor HP (rls) iNDOOR COraL
Rows... Finstm.
Face Area (sq. m)
RNDOOR BLOWER
Nominal Airflow (Lls)
Size (m)
Motor (r/s)
RETDRN-ABR FBLTERS (ram)
* Required filter sizes shown are based on the larger of the ARI (Air Conditioning and Refrigeration Institute) rated cooling airflow or the heating airflow velocity of 91.5 m/min, for throwaway type or 137 m cu../min for high-capacity type Air filter pressure drop for non-standard filters must not exceed 203 mm wg
throwaway
50JZ024
7
135
3.2
1.55
0.81
2...659
8.5
1038
556.8
.167...15
3...590
0.34
378
0.254x0.254
186...17.9
508x508
50JZ030 50J2:03$
8.8 10.6 145 149
1
SCROLL COMPRESSOR
R-410A
Accurater
4.0
1.55
1.02
2...669
10.3
1036
558.8
.167...15
3...590
0.34
472
0.254x0.254
373...21.7
508x508
2_.669
558.8
.187...15
3...590
0.254x0.254
373...21.9
508x508
4.2
1.70
1.02
10.3
1038
0.34
566
50JZ048
14.1 161
4.8
1.93
1.17
2...669
13.5
1133
558.8
.249...22
4...590
0.44
7O8
0.254x0.254
746...20.5
610x762
Table 3--MiNmum Airflow for Reliable Electric Heater Operation
ABRFLOW
CFM
L/s
10 ft. (3.05 m) of horizontal run. Be sure to check the drain trough for leaks Prime tile trap at the beginning of tile cooling season start=up.
Step 7--Install Electrical Connections
The unit cabinet must have an uninterrupted, unhroken electrical ground [o minimize the possibility of personal injury if an electrical _imlt should occur. This ground may consist of an electrical wire connected to the unit ground lug in the control compartment, or conduit approved for electrical ground when installed in accordance with IEC, ANSI NFPA
American National Standards Institute/National Fire Protec- tion Association (latest edition) and local electrical codes. Failure to adhere to this warning could result in serious inju_'
or death.
50JZ024 80JZ030 50JZ036
800 1000 1200 378 472 567
50JZ648
1600
756
Failure to %llow these precautions could result in damage to the unit being installed:
1_ Make all electrical connections in accordance with IEC
ANSINFPA (latest edition) and local electrical codes governing such wiring.
2_ Use only copper conductor for connections between
field-supplied electrical disconnect switch and unit. DO
NOT USE ALUMINUM WIRE.
3. Be sure that high-voltage power to unit is within operating voltage range indicated on unit rating plate. On 3-phase units_ ensure phases are balanced within 2 percent. ( onsult
local power company fbr correction of improper voltage and/or phase imbalance.
4. Insulate low-voltage wires for highest voltage contained within conduit when low=voltage control wires are in same
conduit as high-voltage wires.
5. De not dan?age internal components when drilling through
any panel to mount electrical hardware, conduit, etc_
HIGH-VOLTAGE ( ONNECTIONS The unit must have a separate electrical service with a field-
supplied, waterproof disconnect switch mounted at. or within sight from the unit. Refer to the unit rating plate, IE( and local codes tbr maximnm _i/seicircuit breaker size and minin-mm circuit amps (ampacity) fbr wire sizing (See Table 4 for electrical data).
The field=supplied disconnect may be mounted on the unit over the high=voltage inlet hole (See Figs. 2 and 3).
TOP COVER
INDOOR THERMOSTAT
RETURN
DISCONNECT PERIEC*
Fig. 10--Typical Installation
Duct Covers
Fig. 11--50JZ with Duct Covers On
C02003
C00092
TRAP
_.,__ 2" (50ram) MIN.
C99013
Fig. 12--Condensate Trap
If the unit has an electric heateL a second discom_ect may be Operation of unit o_1 improper line voltage co_lstitutes abuse and
required. Consult the Installation, Start°Up, and Service Iustruc° may cause unit damage that could affect warranty. tions provided with the accessory fc_r electrical service connec= tions.
10
Table 4_ElectricN Data--50JZ {50Hz)
UNiT 50JZ
SIZE
O24
030
03G
O48
(See legend following ElectricN Data charts /
FLA -- Futt Load Amps LRA -- Locked Rotor Amps MCA -- Minimum Circuit Amps
MOCP -- Maximum Overcurrent Protection RLA -- Rated Load Amps
CKTBKR -- Circuit Breaker
NOTES:
1. In compliance with IEC(International Electrical Code) requirements for multimotor and combination toad equipment (refer to IEC
Artictes 430 and 440), the overcurrent protective device for the unit shalt be Power Supply fuse.
2. Minimum wire size is based on 60 C copper wire. If other than
60 C wire is used, or if length exceeds wire length in table, determine size from tEC.
3. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply volt- age is greater than 2%. Use the following formula to determine
the percentage of voltage imbalance.
% Voltage imbalance
V-PH-HZ
400-3-50
400-3-50
400-3-50
400-3-50
= 100 x max vottage deviation from average voltage
VOLTAGE
RANGE
Min Max
380 420
380 420
380 420
380 420
LEGEND
average voltage
COMPRESSOR OFM IFM ELECTRIC HEAT
RLA LRA FLA FLA
4.5 32.0 0.8 1.1
5.2 35.0 0.8 1.7
6.5 46.0 0.8 2.0
6.7 50.0 1.3 3.9
Nominal Kw FLA
6.5 9.4
8.7 12.6
6.5 9.4
8.7 12.6
13.0 18.8
6.5 9.4
8.7 12.6
13.0 18.8
6.5 9.4
8.7 12.6
13.0 18.8
17.4 25.1
EXAMPLE: Supply vottage is 400-3-50.
A B C AB = 393 v
Determine maximum deviation from average voltage.
(AB) 397- 393=4v (BC) 403- 397 = 6 v (AC) 397 - 396 = 1 v
Maximum deviation is 6 v. Determine percent of voltage imbalance.
% Voltage Imbalance = 100 x --
This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.
more than 2%, contact your local etectdc utility company IMPORTANT: If the supply voltage phase imbalance is
immediately.
POWER SUPPLY DISCONNECT SBZE
iMCA FUSE ORCKT. BKR MOCP
7.5 10 --
19.2 20 --
23.2 25 --
9.0 10 --
20.7 20 --
24.7 25 --
32.5 35 --
10.9 15 --
22.7 25 --
26.6 30 --
34.4 35 --
13.6 15 --
25.3 30 --
29.3 30 --
37.0 40 --
45.0 45 --
AC = 396 v
Average Voltage = 393 + 403 + 396
BC = 403 v
1192
= 397
6
397
= 1.5%
FLA LRA
7 35
18 44 22 48
9 39 20 49 23 52 30 59
11 51 21 61 25 64 32 70
14 58 24 67 28 71 35 77 43 83
3
3
Fig. 13--Electrical Data Legend
ROUTING POWER LEADS INTO "kNIT
Use only copper wire between disconnect and unit The high- voltage leads should be in a conduit until they enter the duct panel;
conduit termination at the duct panel must be watertight. Run the high-voltage leads through the power entry knockout on the power entry side panel, (See Fig, 2 arid 3 for location and size) When the leads are inside the uriit, run leads up the high-voltage raceway to the line wiring splice box (See Fig, 13 through 15),
CONNECTING GROUND LEAD TO GROUND LUG Refer to Fig, 18, Connect the ground lead to the chassis using the
ground lug in the wiring splice box, ROUTING CONTROL POWER WIRES (24-V) Form a &ip-toop with the them_ostat leads before routing them
into the unit, Route the thermostat leads through grommeted,
C02002
tow=voltage hole provided in unit into unit control power splice box, (See Fig 2 arid 3) Connect thermostat leads to unit control power leads as shown in Fig, 16 & 17,
The unit transfbm_er supplies 24-v power for complete system including accessory electrical heater, An automatic-reset circuit breaker (See Fig 17) is provided in the 24=v circuit; see the caution label on the tIansl\_rmer or Fig, 18
11
MAXIMUM WIRE SIZE 6 AWG, TBI
FIELD
POWER
SUPPLY
SCHEMATIC
I I L 1 _)_BRN_
(BLK)_ I _ W8 BLN_ QT
Ij,
OPTION ONLY. I I
5,10,15& 20 KW MAXIMUM WIRE SIZE 2 AWG.
ON G
L 28 _
FAr
H I-(_D f- W43 BLK
Wll BLK W15 BLK
IL:: PN.
J
IFC--WiDBL_?-t_;_WI4 BLK_
W12 BLK Wl60RN
Wl3 BLK WIT BLU
BLK _
W41 YEL
.
IFM
&
TRAN I
W33 GRN YEL
__ W34 GRN YEL
HPS LPS
W39 BRN-
W38 BRN-
OFC
c
OFC
PRM IFC
RVS TRAN
IF
THI ON (
AUTO SW
L I
SUPPLHEAT
FIELD THERMOSTAT
SEE NOTE#2
UNIT COMPONENTARRANGEMENT
OUTDOOR FAN SECTION
INDOOR FAN SECTION
50JZOAS& 060
--W200 PNK-
-- W203 GRA--
_[ _W32 BAN-- W207 BAN
-- -- -- FIELDCONTROLWIRING DB BEFROSTBOARD
CONTROL BOX AREA
ELECT HEAl
_C _
IFC
OFC
EQUIP. TRAN TRANSFORMER
/GND
24V PO_ER ENTRY _mE FROMIFR 21AND CONNECTBLK_IIE FRO_IF_
i i FIELD POWERWIRING DFT DEFROSTTHERMOSTAT CTD (TI,T2) COMPRESSORDELAY I ACCESSORyOR OPTIONAL DR DEFROSTRELAY I i , i F
I TO INDICATECOMMON Hp_ HIGH PRESSURES_ITCH CI Cl
ACCESSORY ELECTRIC
HAl & 2 (10 KW) I 5 BAN
..... 6 BRN
-'.... _W204 BR#--_
HAl 2 3 & 4 (20 KW)
HEAT'_.X_ IIV38BRN-
HAl (5 KW]_,_[_W204 BR_-
---- _W207 BAN--
LEGEND
Z_'FIELD SPLICE _HA ADJUSTABLEHEATANTICIPATOR
C3TERMINALCMARKED) CONTACTOR
o TERMINAL(UNMARKED) CAP CAPACITOR
O SPLICE CB CIRCUIT BREAKER C)SPLICE (MAR_ED_ CCN CRANKCASEHEATER
FACTORYWIRING CTD COMPRESSORTIMEDELAY
WIRING EQUIP EQUIPMENT
POTENTIALONLY: HR HEATERRELAY CLOSES OPENS NOT TO REPRESENT_IRINGHTR HEATER TSAT
NOTES:
I IF _N_ OF THE ORI61N_L _IRES FURNISHED A_E _EPL_CED,
IT NU_T_E REPLACED_ITH T_PE_0 DEGREEC _IRE OR
IT'S EOUIV_LENT
_. SEE PtlCE PA_E$FORTHERMOSTATANDIUBBASEI 3 USE lS _EGREECOPPERCONDUCTORSFORFIEL_ INSTALLATION 4 FORHIGHSPEE_IFM,DI$CONNECTlED
FOREDlU_ SPEED,_ISCONNECTRE_HE FROMIFRZl AN_CONNECTBLU_IRE FROMIFM
5 _EFROSTTI_ERm BE SET AT 9_ _INUTESEXCEPT
FOR50J$O4B060 HODEL$IETAT 50 HINUTES.
COMP COMPRESSORMOTOR
6N_ GROUN_ 0 5 SECT T+5 MIN
IFM INDOORFANMOTOR IFC INDOORFANCONTACTOR
LPS LOW PRESSURESWITCH OFM OUTDOORFAN _OTOR OFC OUTDOORFAN CONTACTOR PRM PHASE ROTATIONMONITOR OT QUADRUPLETERMINAL RVS REVERSINGVALVESOLENOID TC THERMOSTATCOOLING TH THERMOSTATHEATING 0 _ T:30 _+I0 MIN
LAST DFROST T:50 MAXIMUM
TRAM
CYCLE T:90
Fig. 14--Wiring Schematics
12
©-- ®
©
L_
Lii
_ --[__ _¢z.__wHT-
THERMOSTAT UNIT CONTROL POWER
AND SUBBASE SPLICE BOX
Fig. 15--Control Connections
GROUND LUG
GROUND
LEAD
L1 ........ /L_.,_ BLK--
L2 ....... zL__ YEL-
L3
LEGEND IEC = International Electrical Code
- - - Field Wiring Splice Connections
NOTE: Use copper wire only,
C99056
IN SLPICE BOX
C02005
Fig. 16--Line Power Connections
C99070
13
TRANSFORMER CIRCUIT CONTAINS A MANUAL RESET OVERCURRENT PROTECTOR
IT WILL NOT AUTOMATICALLY RESET
DISCONNECT POWER PRIOR TO SERVICING
THIS COMPARTMENT MUST BE CLOSED EXCEPT WHEN SERVICING
Fig. 18--Transformer Label
PRE-STAR%UP
Failure to obsela'e the %tlowing warnings could result in serious personal injury or death:
1 Follow recognized safety practices and wear protective
goggles when checking or servicing refrigerant system
2. Do not operate compressor or provide any electric power to unit unless compressor terminal cover is in place and
secured.
3 Do not remove compressor terminal cover until all electri=
cal sources are disconnected
4. Relieve and recover all refiigerant fi'om both high- and low-pressure sides of system befbre touching or disturbing anything inside terminal box if refiigerant leak is suspected around compressor temainals.
5. Never attempt to repair soldered connection while refi'ig= erant system is under pressure.
6. Do not use torch to remove any component. System contains oil and refrigerant under pressure. To remove a component, wear protective goggles and proceed as follows: a. Shut off electrical power to unit. b. Relieve and reclaim al! refrigerant from system using
both high- and low-pressure ports.
c Cut component connecting robing witk robing cutter and
remove component fiom unit.
d. Carefully unsweat remaining tubing stubs when neces-
saN-. Oil can ignite when exposed to torch flame.
Use the Start=Up Checklist supplied at the end of this book and proceed as fbllows to inspect and prepare tke unit fbr initial
start-up:
1. Remove all access panels.
2. Read and foilow instructions on all DANGER, WARNING, CAI. TION, and INFORMATION 1abels attached to, or shipped with, unit.
3. Make the following inspections: a. Inspect fbr shipping and handling damages such as broken
lines, loose parts, disconnected wires, etc.
b. Inspect for oil at all refi'igerant robing connections and on
unit base Detecting oil generally indicates a refrigerant leak. Leak-test all refrigerant robing connections using electronic leak detector, or liquid=soap solution It" a tel'rig= erant leak is detected, see following Check for Refrigerant
Leaks section
c. Inspect all field and factow-wiring connections Be sure
tkat connections are completed and tight.
d. Inspect coil fins. If damaged during shipping and handling,
carefully straighten fins with a ['in comb.
4. Verif}' the fbllowing conditions:
a. Make sure that outdoor-fan blade is correctly positioned in
f_n orifice
b. Make sure that air filter(s) is in place. c. Make sure that condensate drain and trap are filled witk
water to ensure proper &ainage.
d. Make sure that all tools and miscellaneous loose parts have
been removed.
5,
Compressors are internally spring mounted. Do not loosen or remove compressor hold=down bolts
6.
Each unit system has 2 Schrader=type ports, one tow=side Schrader fitting located on the suction line, and one high=side Schrader fitting tocated on the compressor discharge line Be
sure that caps on the ports are tight.
START-UP
Using the Start-Up Checklist supplied at the end of this book, proceed as fbltows:
Step l--Check for Refrigerant Leaks
Locate and repair refrigerant leaks and charge the unit as fbllows:
1. Use both high- and tow-pressure ports to relieve system pressure and reclaim remaining ret'rigerant.
2. Repair leak fbltowing accepted practices.
NOTE: Install a bi-flow filter &ier whenever the system has been opened fbr repair.
3. (beck system fbr leaks using an approved method.
4. Evacuate refrigerant system and reclaim refi'igerant if" no additional leaks are found
5. Charge unit witk R=410A refrigerant, using a volumetric= charging cylinder or accu*ate scale. Refer to unit rating plate fbr required charge
Step 2--Start°Up Adjustments Complete the required procedures given in the Pre=Start=tp
section be_bre starting the unit Do not jumper any sat'cry devices when operating the unit Do not operate the unit in Cooling mode when tke outdoor temperature is below 55°F (12.7%), unless accessory low=ambient kit is installed. Do not rapid=cycle the compressor Allow 5 rain between "on" cycles to prevent corn= pressor damage
CHE(KING (70()LING AND HEATING CONTROL OPERA= TION
Start and check the unit for proper control operation as follows:
1. Place room themmstat SYSTEM switch or MODE control in OFF position. Observe that blower motor starts when FAN
mode is placed in FAN ON position and sitars down aker proper _hn off delay, when FAN MODE switch is placed in AUTO position.
14
C99058
1/8" (3.175mm) MAX BETWEEN MOTOR SHAFT MOTOR AND FAN HUB
Fig. 19--Fan Blade Cmearance
C99009
LEGEND HPS - High Pressure Switch
LCS - Loss of Charge Switch
Accurater _ Metering Device Arrow indicates direction of flow
Fig. 20--TypicN Heat Pump Operation, Heating Mode
OUTDOOR COIL
OUTDOOR COIL
Metering
Position
Bypass Position
Metering
Position
C00095
INDOOR COIL
LEGEND HPS - High Pressure Switch LCS - Loss of Charge Switch
Accurate€ Metering Device
] Arrow indicates direction of flow
Fig. 21--TypicN Heat Pump Operation, CoNing Mode
2. Place system switch or MODE contlol iu HEAT position. Set control above room temperature, Observe d_at compressor,
outdoor fire, and indoor blower motors start. Observe that
heating cycle shuts down when control setting is satisfied,
3, When using an automatic changeover room thermostat, place
both SYSTEM or MODE contlol and FAN mode switches in AUTO positions, Observe that unit operates in ( ooling mode
Bypass
Position
when temperature conuol is set Go "call for (ooling" (below room temperature), and unit operates in Heating mode when
temperature control is set to "call for Heating" (above room temperature),
IMPORTANT: Three=phase, scroll compressors are direction ori- euted Unit must be checked to ensure proper compressor 3=phase power lead orientation, If not corrected within the phase monitor
15
C00096
Table 5--Wet Coil Air Delivery=English
Unit 50JZ 024=048"
UNiT
024
030
038
048
Air delivery values are based on operating voltage of 400-v, wet coil, without filter or electric heater. Deduct filter and electric heater pressure drop (see Tables 5 and
6) to obtain static pressure available for ducting
NOTES: 1 Do not operate the unit at a cooling airflow that is less than 350 cfm for each 12,000 Btuh (165 L/s for each 35 kW) of rated cooling capacity Evaporator coil frosting
may occur at airflows below this point. 2 Dashes indicate portions of table that are beyond the blower motor capadty or are not recommended.
MOTOR SPEED
Low
High
Low
High
Low
High
Low
High
Watts 303 305 303 300 .......
Cfm 969 879 785 687 .......
Watts .... 435 428 428 422 -- -- --
Cfm .... 963 833 758 676 -- -- --
Watts -- 814 853 889 921 954 1002 ....
Cfm -- 1189 1115 1041 971 903 833 ....
Watts ....... 700 683 688 755
Cfm ....... 1223 1142 1075 1058
Watts 552 540 529 523 514 480 .....
Cfm 1296 1237 1167 1097 1029 952 .....
Watts ..... 782 765 736 721 780 1002
Cfm ..... 1467 1398 1321 1237 1165 1137
Watts 692 686 678 664 652 664 736 ....
Cfm 1571 1509 1444 1370 1295 1240 1237 ....
Watts -- -- 1112 930 856 834 825 811 793 -- --
Cfm -- -- 1693 1670 1601 1521 1447 1378 1294 -- --
0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
(See Fig. 25) will not provide the unit with power, A red light on
the phase monitor will blink_ The 3-phase power leads to the unit must be reversed to correct rotation,
(HECKING AND ADJ[ STING REFRIGERANT CHARGE
The refi'igerant system is _idly charged with R-410A rel'rigerant and is tested and _ctory sealed
NOTE: Adjustment of the refrigerant charge is not required
unless the unit is suspected of not having the proper R-410A
charge. The charging label and d'*e tables shown refer to system
temperatures and pressures in Cooling mode, only. A refrigerant
charging label is attached to the outside of the service access door. If charge level is suspect in Heating mode, reclaim all refrigerant and charge to nameplate amount. (This information may be obtained ]:iom the physical data table also.) The charging label and
the tables shown refkr to system temperatures and pressures in
( ooling mode only. A refi'igerant charging label is attached to the outside of the service access door. If charge level is suspect in
Heating mode, reclaim all refrigerant and charge to nameplate
amount. (This information may be obtained fi'om the physical data
table also.)
mNPORTANT: When evaluating the rd:i'igerant charge, an indio cared adjustment to the specified factoQ' charge must always be
very minimal. If a substantial adjustment is indicated, an abnomaal
condition exists somewhere in the cooling system, such as insuf- ficient airflow across either coil or both coils.
REFRIGERANT CHARGE
The amount of refi'igerant charge is listed on the unit nameplate and/or the physical data table Refer to the Re_i'igeration Service Techniques Manual, Rd:_'igerants Section
NO CHARGE
Check for leak. "Use standard evacuating techniques Aiier evacuo ating system, weigh in the specified amount of refi'igerant (refer to system data plate),
EXTERNAL STATIC PRESSURE (IN, WG}
LOW CHARGE COOLING Use Cooling Charging Table. Vary refi'igerant until the conditions
of the table are met Note that charging tables are different from type normally used. Tables are based on charging the units to correct superheat for the various operating conditions Accurate pressure gauge and temperature sensing devices are required. Connect the pressure gauge to the service port on the suction line Mount the temperature sensing device on the suction line and insulate it so that the outdoor ambient does not affect the reading Indoor air (FM (L/s) must be within the normal operating range of
the unit,
HEATING MODE CHANGE
Do not attempt to adjust charge by cooling methods while in Heating mode. When charging is necessaw in Heating mode, recover refi'igerant and weigh in according to unit data plate refrigeration data.
TO USE COOLING CHARGING (}HARTS Take the outdoor ambient temperature and read the suction
pressure gauge Re_kr to the chart to determine what the suction temperature should be.
NOTE: If the problem causing the inaccurate readings is a refrigerant leak, refer to Check for Re_?igerant Leaks section.
INDOOR AIRFLOW AND AIRFLOW ADJUSTMENTS
? = Le _ m
For heating and cooling operation, the recommended airflow is 350 to 450 cfm for each 12,000 Bmh (165 Lis to 212 for each 3.5 kW) of rated cooling capacity. For units with optional electric heat, the airflow must not be reduced below
the levels stated in Table 2
Table 5 and Table 6 show both heating and cooling airflows at various external static pressures Refer to these tables to determine the airflow for the system being installed
16
Table 6--Wet Coil Air Delivery-SI
Unit 50JZ 024-048*
UNIT
O24
030
036
O48
* Air delivery values are based on operating voltage of 400-v, wet coil, without filter or electdc heater. Deduct filter and electric heater pressure drop (see Tables 5 and
6) to obtain stafic pressure available for ducfing
NOTES:
1. Do not operate the unit at a cooling airflow that is less than 165 L/s for each 3.5 kW of rated cooling capacity Evaporator coil frosting may occur at airflows below this point.
2. Dashes indicate portions of table that are beyond the blower motor capacity or are not recommended.
MOTOR SPEED
Low
High
Low
High
Low
High
Low
High
0 25 50 75 100 125 150 175 200 225 250
Watts 303 305 303 300 .......
L/s 458 415 371 324 .......
Watts .... 435 428 428 422 -- -- --
L/s .... 455 393 358 319 -- -- --
Watts -- 814 853 889 92I 954 1002 ....
L/s -- 561 526 491 458 426 393 ....
Watts ....... 700 683 688 755
L/s ....... 577 539 508 499
Watts 552 540 529 523 514 480 .....
L/s 612 584 551 518 486 449 .....
Watts ..... 782 765 736 721 780 1002
L/s ..... 693 660 624 584 550 536
Watts 692 686 678 664 652 664 736 ....
L/s 741 712 681 647 611 585 584 ....
Watts -- -- 1112 930 856 834 825 811 793 -- --
L/s -- -- 799 788 756 718 683 650 611 -- --
EXTERNAL STATIC PRESSURE (PA)
Table 7--Filter Pressure Drop (in. wg)-English
FILTER SBZE CFM
(iN.) 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700
20 X 20 X 1 0.05 0.07 0.08 0.10 0.12 0.13 0.14 0.15 20X24X1 0.09 0.10 0.11 0.13 0.14 0.15 0.16
24X30X1 0.07 0.08 0.09 0.10 0.11 0.12
1800 1900 2000 2100 2200 2300
0.13 0.14 0.15 0.16 0.17 0.18
Table 8--Filter Pressure Drop (Pa)-SI
FILTER S_ZE L/S
(MM} 236 283 330 378 425 472 519 566 614 661 707 755
508 x 508 12.4 17.4 19.9 24.9 29.9 32.3 34.8 37.3
508 x $10 .... 22.4 24.9 27.4 32.3 34.8 37.4 39.9
610 x 752 -- 17.4 19.9 22.4 24.9 27.4
802 850 896 944 991 1038
29.9 32.3 34.8 37.3 39.8 42.3
Table 9--Accessory Electric Heat Pressure Drop (in. wg)-ENGLISH
HEATER
KW 2000 2200
6.5-t7.4 0.067 0.075
HEATER WS
KW 283 378 472 569 661 755 850 944 1038
&8-17.4 7.5 8.2 9.2 10.4 11.7 12.9 14.9 16.7 18.7
NOTE: Be sure that all supply-and return-air grilles are open_ free
from obstIT./ctions, and adjusted properly. Airflow can be changed by changing the lead connection of the
blower motor,
To change the speed of the indoor _bn motor (IFM), remove the fSn motor speed leg lead tiom the indoor _Sn contactor (IF(7). To
600 800 1000 1200 1400 1600 1800
0.030 0.033 0.037 0.042 0.047 0.052 0.060
Table 10--Accessory Electric Heat Pressure (Pa)-Sl
CFM
change the speed, remove and replace with lead fbr desired blower motor speed. Insz_/atc lhe *'emo*ed lead to avoid contact with chassis parts For 400-v Motors The motor leads are color coded as _bllows: 3-SPEED
Black high White common
Blue medium Red low
17
SUPERHEAT
TEMP
(°C)
0
1
2
a
4 6
7 8 9
10 tt
12 t3 14 t5
16 t7 18 t9
20 21 22
Table 11--Required Suction=Line Temperature (Metric)
SUCTION PRESSURE AT SERVICE PORT {KPA)
424
1.7
2.8
3.9
5.0
6.1
7.2
8.3
9.4
10.6
11.7
12.8
13.9
15.0
16.1
16.7
17.2
18.3
19.4
20.6
21.7
22.8
23.9
443
2.8
3.9
5.0
6.1
7.2
8.3
9.4
10.6
11.7
12.8
13.9
15.0
16.1
17.2
17.8
18.3
19.4
20.6
21.7
22.8
23.9
25.0
463
3.9
5.0
6.1
7.2
8.3
9.4
10.6
11.7
12.8
13.9
15.0
16.1
17.2
18.3
18.9
19.4
20.6
21.7
22.8
23.9
25.0
26.1
483
5.0
6.1
7.2
8.3
9.4
10.6
11.7
12.8
13.9
15.0
16.1
17.2
18.3
19.4
20.0
20.6
21.7
22.8
23.9
25.0
26.1
27.2
503
6.1
7.2
8.3
9.4
10.6
11.7
12.8
13.9
15.0
16.1
17.2
18.3
19.4
20.6
21.1
21.7
22.8
23.9
25.0
26.1
27.2
28.3
524
7.2
8.3
9.4
10.6
11.7
12.8
13.9
15.0
16.1
17.2
18.3
19.4
20.6
21.7
22.2
22.8
23.9
25.0
26.1
27.2
28.3
29.4
546
8.3
9.4
10.6
11.7
12.8
13.9
15.0
16.1
17.2
18.3
19.4
20.6
21.7
22.8
23.3
23.9
25.0
26.1
27.2
28.3
29.4
30.6
568
9.4
10.6
11.7
12.8
13.9
15.0
16.1
17.2
18.3
19.4
20.6
21.7
22.8
23.9
24.4
25.0
26.1
27.2
28.3
29.4
30.6
31.7
591
10.6
11.7
12.8
13.9
15.0
16.1
17.2
18.3
19.4
20.6
21.7
22.8
23.9
25.0
25.6
26.1
27.2
28.3
29.4
30.6
31.7
32.8
TaNe 12--Superheat Charging Table (Metric)
OUTDOOR EVAPORATOR ENTERING ABR TEMPERATURE (°C WB)
TEMP
(°C) 10 11 12 13 14 15 16 17 18
13 5.0 6.7 7.8 9.4 11.1 11.9 12.8 14.4 16.1 16 3.9 5.6 6.7 8.3 10.0 10.8 11.7 13.3 15.0
18 - 3.3 5.6 7.2 8.9 9.7 10.6 11.7 13.3 2t - - 3.9 5.6 7.2 8.1 8.9 10.6 11.7 24 - - 3.3 5.0 5.8 6.7 8.3 10.0 27 - - 2.8 3.6 4.4 6.7 8.3
29 ..... 4.4 6.1
32 ..... 2.8 5.0
38 ..... 3.3
a8 ......
4t ......
48 ......
4G ......
Where a dash (-) appears, do not attempt to charge system under these conditions, or refrigerant
NOTE: Superheat °C is at low-side service port
2 SPEED
Black high Red low
Yellow common
To change the speed of the indoor fan motor (IFM), remove f_n motor speed lead fi'om the indoor fire contactor (IF() and replace with the lead for the desired blower motor speed. The motor speed
lead is attached to tem_inal BM. Insulate removed lead end to
avoid contact with chassis parts.
Step 3--Defrost Control
QUIET SHIFT
Quiet Shill is a field-selectable defiost mode, which will eliminate
occasional noise that could be heard at the start of defrost cycle
and restarting of heating cycle. It is selected by placing DIP switch
3 (on defrost board) in ON position.
When Quiet Shit't switch is placed in ON position, and a de_i'ost is initiated, the fbllowing sequence of operation will occur. Revers-
ing valve will energize, outdoor fire will mrn off, compressor will mrn off for 30 sec and then mm back on to complete defrost. At the start of heating after conclusion of defiost reversing valve will de-energize, compressor will turn off for another 30 sec, and the outdoor fan will stay off for 40 sec, before starting in the Heating
l'node,
DEFROST
The defi'ost control is a time/temperature control (See Fig_ 23) which includes a field=selectable time period (DIP switch 1 and 2 on the board) between defi'ost cycles of 30, 50 or 90 minutes (ihctory set at 30 minutes).
To initiate a forced defrost, two options are available depending on the status of the defrost thermostat.
19 20 21 22 23 24
17.8 19.4 20.6 22.2 23.3 25.0
16.7 18.3 20.0 21.1 22.2 23.9
15.0 16.7 18.3 20.0 21.1 22.8
13.3 15.0 16.7 18.3 20.0 21.7
11.7 7.8 15.6 17.2 18.9 20.6
10.0 11.7 13.9 15.6 17.2 19.4
8.3 10.6 12.2 14.4 16.7 18.3
7.2 8.9 11.1 13.3 15.0 17.2
5.6 7.8 10.0 12.2 13.9 16.1
4.4 6.7 8.3 11.1 12.8 15.0
2.8 5.0 7.2 9.4 12.2 14.4
- 3.3 6.1 8.3 11.1 13.9
- - 4.4 7.8 10.0 12.8
slugging
may occur Charge must beweighed in.
18
Table 13--Required Suction=Line Temperature (English)
SUPERHEAT SUCTION PRESSURE AT SERVICE PORT (PSBG)
TEMP
(°F) 61.5 64.2 67.1 70.0 73.0 76.0 79.2 82.4 85.7
0 35 37 39 41 43 45 47 49 51 2 37 39 41 43 45 47 49 51 53
4 39 41 43 45 47 49 51 53 55 6 41 43 45 47 49 51 53 55 57 8 43 45 47 49 51 53 55 57 59
10 45 47 49 51 53 55 57 59 61 t2 47 49 51 53 55 57 59 61 63
14 49 51 53 55 57 59 61 63 65 t6 51 53 55 57 59 61 63 65 67 18 53 55 57 59 61 63 65 67 69
20 55 57 59 61 63 65 67 69 71 22 57 59 61 63 65 67 69 71 73 24 59 61 63 65 67 69 71 73 75 26 61 63 65 67 69 71 73 75 77 28 63 65 67 69 71 73 75 77 79
30 65 67 69 71 73 75 77 79 81 32 67 69 71 73 75 77 79 81 83 34 69 71 73 75 77 79 81 83 85 36 71 73 75 77 79 81 83 85 87
38 73 75 77 79 81 83 85 87 89 40 75 77 79 81 83 85 87 89 91
TaNe 14_Superheat Charging TaNe (English)
OUTDOOR EVAPORATOR ENTERING ABR TEMPERATURE (°FWB)
TEMP
(OF} 50 52 54 56 58 60 62 64 66 68 70 72 74 76
58 9 12 14 17 20 23 26 29 32 35 37 40 42 45 60 7 10 12 15 18 21 24 27 30 33 35 38 40 43
68 -- 6 10 13 16 19 21 24 27 30 33 36 38 41 70 -- -- 7 10 13 16 19 21 24 27 30 33 36 39 78 -- -- -- 6 9 12 15 18 21 24 28 31 34 37
80 .... 5 8 12 15 18 21 25 28 31 35
85 ...... 8 11 15 19 22 26 30 33
90 ...... 5 9 13 16 20 24 27 31
98 ....... 6 10 14 18 22 25 29
100 ........ 8 12 15 20 23 27
105 ........ 5 9 13 17 22 26
110 ......... 6 11 15 20 25
11S .......... 8 14 18 23
Where a dash (-) appears, do not attempt to charge system under these conditions, or refrigerant slugging may occur. Charge must be weighed in. NOTE: Superheat °F is at low-side service port
If de['rost them_ostat is closed, speedup pins (J1) must be shorted
by placing a flat head screw driver in between for 5 sec and
releasing, to observe a complete defiost cycle. When the Quiet Shi_ switch is selected, compressor will be mined off _br two 30
sec intervals during this complete defi'ost cyctQ as explained previously When Quiet Shift switch is in bactory default OFF position, a normal and complete defrost cycle will be observed.
If defrost them_ostat is in open position, and spee&/p pins are
shorted (with a flat head screw driver) for 5 sec and re]eased_ a
short defi'ost cycle will be observed (actual length is dependent upon the selected Quiet Shift position) When Quiet Shift switch is
in ON position, the length of defiost is 1 minute (30 sec
compressor off period _bllowed by 30 sec of del:i'ost with com_ pressor operation) On return to heating operation, compressor will
again mm off _br an additional 30 sec and the outdoor _hn for 40
sec When the Quiet Shift is in OFF position, only a brief 30 sec
cycle will be observed
If it is desirable to observe a complete defrost in warmer weather, the det'rost thermostat must be closed as follows
1 Turn off power to outdoor unit and install lockout tag
2. Disconnect outdoor _im motor tead flora OF2 on control board. (See Fig. 23) Tape to prevent grounding.
3. Restart unit in Heating mode, allowing I:i'ost to accumulate on outdoor coil.
4. Aker a few minutes in Heating mode, liquid line temperate/re should drop below closing point of defi'ost thermostat (ap- proximately 30_>F/- 1. I _>().
NOTE: Uit will remain in defrost until defrost thermostat reopens at approximately 80°F (26.7°C) coil temperature at liquid
line or remainder of defrost cycle time up to a maximum defi'ost time of 10 minutes.
19
_@, @@
5 @, @@
4@, @@
o o
3@, @@
CL
_D
C
N
0J
i 20,0@
ff
I@,0@
_lance Point Workmheet _ _limh
_m_ _ In_r _nt_ing Air of 7@ F. and,P.at_C_
@, 0@
-20
=I@ @ I@ 2@ 3@ 4@ 5@ 6@
_t_r Air _, (D_g F)
Fig, 22A--80JZ BaMnce Point Worksheet-English
5. Tm'n off power tag disconnect to outdoor and reconnect fire motor tend to OF2 on control board after above forced defrost
cycle.
MAINTENANCE
_o ensure continuing high perfbrmance, and to minimize the
possibility of premature equipment fitilure, periodic maintenance must be pert'ormed on this equipment. This heat pump unit should
be inspected at least once each year by a qualified service person.
To troubleshoot unit, refer to Troubleshooting (hart at the end of
these instructions NOTE TO EQ(IPMENT OWNER: Consult your local dealer
about the availability of a maintenance contlact.
The ability to properly perfbrm maintenance on this equip= ment requires certain expertise, mechanical skills, tools and
equipment. If you do not possess these, do not attempt to perfbrm any maintenance on this equipment, other than those procedures recommended in the User's Manual. FAILURE
TO HEED THIS WARNING COULD RESULT IN SERI=
OUS INJURY OR DEATH AND POSSIBLE DAMAGE TO
THIS EQUIPMENT.
7@
C02006
Failure to _bllow these warnings could result in serious injury or death:
1. Turn off electrical power to the unit and install lockout mg befbre perfbrming any maintenance or selwice on this unit.
2. Use extreme caution when removing panels and parts. As with any mechanical equipment, personal injury can result ti'om sharp edges,
3 Never place anything combustible either on, or in contact
with, the unit
Errors made when reconnecting wires may cause improper and dangerous operation. Label all wires prior to disconnect= ing when servicing
The n_ininmm maintenance requirements fbr this equipment are as follows:
1. Inspect air filter(s) each month. Clean or replace when
necessa1%/
2. Inspect indoor coil, &aim and condensate drain line each cooling season for cleanliness. (;lean when necessary.
3. Inspect blower motor and wheel fbr cleanliness each cooling season. Clean when necessary.
4. (heck electrical connections fbr tighmess and controls _br proper operation each cooling season. Service when neces=
sa_
Step l--Air FHter
IMPORTANT: Never operate the unit without a suitable air filter in the return=air duct system Always replace the filter with the
2O
Balance Point Worksh_t - _tr±c
I$
_ _n _r _t_Ting Air of 21 C, and _at_ C_
14
12
o
CL
8
C
0J
212
.,=_ g
c
0
=30
=25 =20 =15 =10 -5 @ 5 !0 15
Fig, 22B--80JZ Balance Po{nt VVorksheet-SI
same dimensional size and type as originally installed See Table
1 for recommended filter sizes.
Inspect air filter(s) at least once each month and replace (throwaway=type) or clean (cteanable-type) at least twice during each cooling season and twice during d_e heating season, or
whenever the filter becomes clogged with dust arid tint
Step 2--Indoor Blower and Motor NOTE: All motors are prelubricate& Do not attempt to lubricate
these motors.
For longer life, operating economy, and continuing efficiency, clean accumulated dirt and grease fiom the blower wheel and
motor annually.
Disconnect and tag electrical power to the unit before cleaning and lubricating the blower motor arid _heel Failure to adhere to this warning could cause personal il_iury or death
Step 3--Outdoor Coi!, hdoor Coil, and Condensate
Drain Inspect the condenser coil, evaporator coil, and condensate drain at
least once each year. The coils are easily cleaned when &y; therefore, inspect and clean
the coils either be_bre or after each cooling season. Remove all obstructions, including weeds and shrubs, that interfere with the airflow through the condenser coil.
Stlaighten bent fins with a fin comb. If coated with dirt or tint, clean the coils with a vacuum cleaner, using the soft brush
attachment. Be caret\d not to bend the fins. If coated with oil or grease, clean the coils with a mild detergent=and-water solution.
20
C02011
Rinse coils with clear water, using a garden hose. Be carefi/l not to splash water on motors, insulation, wiring, or air filter(s) For best results, spray condenser coil fins fi'om inside to outside the unit.
On units with an outer and inner condenser coil, be sure to clean between the coils Be sure to flush all dirt and debris from the unit
base
Inspect the drain and condensate &ain line when inspecting the coils, Clean the drain and condensate &ain tine by removing all foreign matter fiom the &ain Flush the &ain and &ain trough with clear water Do not splash water on the insulation, motor, wiring, or air filter(s) It"the &ain trough is restricted, clear it with a "plumbers snake" or similar probe device,
Step 4--Outdoor Fan
Keep the condenser fan t'ree t'rom all obstructions to ensure proper cooling operation. Never place articles on top of the unit. Damage to unit may result.
1 Remove 6 screws holding outdoor grille and motor to top
COVer,
2. Turn motor/grille assembly upside down on top cover to expose fire blade.
3. Inspect the _im blades t'or cracks or bends.
4. If fan needs to be removed, loosen setscrew and slide _m off motor shaft.
5. When replacing thn blade, position blade so that the hub is 1/8 in. (3A75 ram) away fiom the motor end (See Fig. 19).
6. Ensure that setscrew engages the flat area on the motor shaft when tightening,
2i
O <-"b_
Q'--P:b
--< Q_ C) <:_
O
7q
bO
CD__
o
©
r 1 r 1 C 1
r ] r ]
C 1 C
CESO130076-00
©
--3 3
3 ]
3 3 3
3
Speedup Pins
Quiet rost interval Shift DI P switches
Fig. 23--Defrost Control
7. Replace grille. Step 5--Electrical Controms and Wiring Inspect and check [he electrical contlols and wiring armually. Be
s_me to t_t's_ q{/the e/ectrica/ yo_ e_' to i/Tezmit a_cl inst_dl loci_o_t
ldt_,
Remove access panel [o locate all the electrical controls and wiring. Check all electrica! connections for rightness. Tighten a11
screw connections. If any smoky or burned connections are
notice& disassemble the connection, clean all the parts, restrip the wire end and reassemble the connection properly and securely.
After inspecting the electrical controls and wiring, replace all the panels. Start the unit, and obsela-e at least one complete cooling
cycle to ensure proper operation. If discrepancies are observed in operating cycle, or if a suspected malt\ruction has occurred, check each electrical component with the proper electrical instromentao
tion. Refer to the unit wiring label when making these checkouts.
Step 6--Refrigerant Circuit
Inspect all refrigerant robing connections and the unit base Ibroil accumulation annually. Detecting oil generally indicates a refrigo
erant leak. If oil is detected or if tow pertbmaance is suspected, leakotest all
refrigerant robing using an electronic leak detector, or tiquidosoap
solution. If a refrigerant leak is detected, refer to Check for
Re_iJgerant Leaks section.
If no refl'igerant leaks are %und and low performance is suspected,
refer to (hecking and Adjusting Refrigerant Charge section.
A99442
Step 7--hdoor Airflow The heating and/or cooling airflow does not require checking
unless improper perfbm_ance is suspected tya proMem e_i._ts, /_e .sz_re that a// szlppl)- and _'em_'n-air gH/les are oi_eI_ w_d free _'om obst_'zzction.s, and that the ai_' fi]ter is c]ea_. When necessm?-, refer to Indoor Airflow and Airflow Adjustments section to check the system airflow.
Step 8--PURON® Systems Items The Following items should be taken into consideration when
maintaining your PuronR; System. Metering Deviees-Aeeurater Piston
This metering device is a fixed orifice and is contained in the brass hexobody in the liquid line _)eding the indoor and outdoor coils.
Pressure Switches Pressure switches are protective devices wired into control circuit
(low voltage). They shut off compressor if abnom_ally high or tow pressures are present in the refi'igeration circuit. These pressure switches are specifically designed to operate with Puron (R-410A) systems. R-22 pressure switches must not be used as replacements for the Puron (Ro410A) system.
Loss of Charge Switch This switch is located on the liquid line and protects against tow suction pressures caused by such events as toss of charge, low airflow across indoor coil., dirty filters, etc. It opens on a pressure drop at about 20 psig (138 kpa). If system pressure is above this,
switch should be closed. To check switch:
22
Fig. 24_Refrigerant Circuit
C99097
1. Turn off all power to unit and install lockout tag
2. Disconnect leads on switch
3. Apply ohm meter leads across switch. You should have continuity on a good switch.
NOTE: Because these switches are attached to refrigeration system under pressure, it is not advisable to remove this device for troubleshooting unless you are reasonably certain that a problem exists. If switch must be removed, remove and recover all system charge so that pressure gauges read 0 psi. Never open system
without breaking vacuum with dw nitlogen.
High-Pressure Switch
The high=pressure switch is located in the discharge line and protects against excessive condenser coil pressure. It opens at (510 psig (4205 kpa). High pressure may be caused by a dirty outdoor
coil, gtiled fan motor, or outdoor air recirculation.
To check switch:
1. Turn off all power to unit and install lockout tag.
2. Disconnect leads on switch.
3. Apply ohm meter leads across switch. You should have continuity on a good switch.
Cepeland Scroll Compressor (Puren Refrigerant) The compressor used in this product is specifically designed to operate wRh Puron (R-410A) refrigerant and cannot be inter- changed.
The compressor is an electrical (as well as mechanical) device. Exercise extreme caution when working near compressors. Power
should be shut off: if possible, fbr most troubleshooting tech- niques. Refrigerants present additional sa_ty hazards.
Wear safety glasses and gloves when handling refrigerants Keep torches and other ignition sources away fi'om refl'iger= ants and oils. Failure to _bltow this warning can cause a fire, serious injury, or death
The scroll compressor pumps refrigerant throughout the system by the interaction of a stationary and an orbiting scroll. The scroll
H
compressor has no dynamic suction or discharge valves, and it is more tolerant of stresses caused by debris, liquid slugging, and flooded starts The pressure relief port is a safkty device, designed to protect against extreme high pressure The relief port has an operating range between 550 (3792) and 625 psi (4309 kpa) dif_[krenfial pressure.
The infbrmation below covers the refi'igerant system of the 50JZ, including the compressor oi! needed, smwicing systems on roofs containing synthetic materials, the filter drier and refi'igerant charging.
The Copeland scroll compressor uses Mobil 3MA POE oil. This is the only oil allowed %r oil recharge.
Refrigerant
This system uses Puron (R°410A) regigerant which has higher operating pressures than R-22 and other refi'igerants. No other refrigerant may be used in this system Gauge set, hoses, and recovew system must be designed to handle Puron. If you are unsure consult the equipment manugtcmrer Failure to use Puron compatible servicing equipment or replacement components may result in property damage or injury.
Compressor Oil The compressor in this system uses a polyolester (POE) oil, Mobil 3MA POE. This oil is extremely hygroscopic, meaning it absorbs water readily. POE oils can absorb 15 times as much water as other oils designed [br HCF( and CFC refi'igerants. Take all necessa U precautions to avoid exposure of the oil to the atmosphere
Servicing S3stems on Roe_s with Synthetic Materials POE (polyolester) compressor lubricants are known to cause long term damage to some synthetic roofing materials.
Exposure, even if immediately cleaned up, may cause ernbrittle- ment (leading to cracking) to occur in one year or more. When performing any service that may risk exposure of compressor oil to the roof, take appropriate precautions to protect roofing. Proce- dures which risk oil leakage include, but are not limited to, compressor replacement, repairing refrigerant leaks, replacing
23
refrigerant components such as fiher drier, pressm'e switch, me= tering device, coil, accumulator, or reversing valve.
Synthetic Roof Precautionm°y Procedure
1. Cover extended roof working area with an in, permeable polyethylene (plastic) drip cloth or tarp Cover an approximate
10x 10ft (3x3m) area.
2. Cover area in front of the unit smvice panel with a ter W cloth shop towel to absorb lubricant spills and prevent run-orEs, and
protect drop cloth fiom tears caused by tools or components.
3. Place ter O' cloth shop towel inside unit immediately under component(s) to be serviced and prevent lubricant run-offs
through the touvered openings in the unit base.
4. Pert'otto required service.
5. Remove and dispose of any oil contaminated material per local codes.
Liquid Line Filter Drier
The biflow filter &ier is specifically designed to operate with Puron. Use only fi_ctoo'°authorized replacement components. Fil°
ter drier must be replaced whenever the refrigerant system is
opened. When removing a filter &ier. use a tubing cutter to cut the
drier fiom the system. Do not 14nsweat a filter drier J_om tl_e srsWm. Heat fiom unsweating will release moisture and contami° nants from drier into system.
Puron (R-410A) Refrigerant Charging Refkr to unit infbm?ation plate and charging chart. Some R-410A
refrigerant cylinders contain a dip tube to allow liquid refrig-
erant to flow from cylinder in upright position. For cylinders
equipped with a dip robe, charge Puron units with cylinder in upright position and a comnmrcial metering device in manifold hose. Charge refiigerant into suction-line.
Refrigeration Service Ports Each unit system has 3 Schrader-type service ports: one on the
suction line, one on the liquid line, and one on the compressor
discharge line. Be sure that caps on the ports are tight.
High Flmv Valves Located on the compressor hot gas and suction robes are High Flow Valves. Large black plastic caps distinguish these valves
with o=rings located inside the caps. These valves cannot be
accessed for smwice in the field. Ensure the plastic caps are in place and tight or the possibility of leakage could occur.
Step 9--System information
PHASE MONITC)R CONTROL
1. 3 phase scroll compressors are rotational sensitive
2. A flashing LED on phase monitor (See Fig. 25) indicates reverse rotation
3. This will not allow contactor to be energized
4. Disconnect power to unit and interchange 2 field wiring leads
on unit contactor.
Follow these steps to properly start up the system:
1. Fully back seat (open) liquid and vapor-robe service valves.
2. [?nit is shipped with valve stem(s) fi'ont seated (closed) and
caps installed. Replace stem caps after system is opened to refi'igerant flow Replace caps finger-tight and tighten with wrench an additional 1/12 mm £_r back-seating valves (male
square stem).
3. Close electrical disconnects to energize system
4. Set room thermostat desired tempera*me Be sure set point is below indoor ambient temperature
5. Set room themmstat to COOL and fan control to ON or AUTO mode, as desired Operate unit for 15 minutes. Check system
refi'igerant charge
SEQUENCE OF OPERATION Turn on power to indoor and outdoor unit. Trans£m_ner is
energized. C)n a call fbr cooling, them_ostat make circuits R-Y and R=G. On
three phase models with scroll compressors, d-*eunits are equipped with aphase monitor (See Fig. 25) to detect if the incoming power is colTectty phased fm comp*essor operation. If the phasing is correct, circuit R=¥ energizes contactor, starting outdoor fan motor and compressor circuit R-G energizes indoor unit blowe* relay, starting indoor blower nmtor on high speed.
NOTE: If the phasing is incolTect, the contactor will not be energized. To correct the phasing, interchange any two of the three power connections on the field side
When the themmstat is satisfied, its contacts open, de=engergizing contactor and blower relay. Compressor and nmtors stop
If"indoor unit is equipped with an off-delay circuit, the indoor blower can be 1am up to an additional 120 sec to increase the system efficiency
LOSS OF CHARGE SWITCH The toss of charge switch is a protective device wired into control
circuit (low voltage). It shuts off the compressor if abnormally tow pressures are present in the refi'igeration circuit.
NOTE: Because these switches are attached to refrigeration system under pressure, it is not advisable to remove this device for troubleshooting unless you are reasonably certain that a problem exists. If switch must be removed, remove and recover all system charge so that pressure gauges read 0 psi. Never open system without breaking vacuum with do - nitrogen.
CHECK DEFROST THERMOSTAT There is a liquid header with a brass distributor and feeder robe
going into outdoor coil. At the end of 1 of the feeder tubes, there is a 3/8=in. (9.5 ram) OD stub tube approximately 3 in. (76.2 mm) tong. The det'rost themmstat slmuld be located on stub robe. Note that there is only 1 stub robe used wit}*liquid header, and on most
units it is the bottom circuit. The det'rost thernmstat (See Fig. 26) signals heat pump that
conditions are right fbr defiost or that conditions have changed to terminate defiost. It is a thermally actuated switch clamped to outdoor coil to sense its temperature. Nomaal temperature range is closed at 30° ÷ 3_>F(°1.1%; _/- 1.7%;) and open at 80_>÷ 5_>F (26.7%; +/- 2.8%7).
NOTE: The defrost tlaermostat must be located on the tiquid side of the outdoor coil on the bottom circuit and as close to the coil as
possible.
TROUBLESHOOTING
Re_r to the < ooling and Heating Trmlbleshooting <harts (Table
15 & 16) for troubleshooting information.
START-UP CHECKLIST
Use the Start=Up checklist to ensm'e prope* start-up proced-ures are followed.
24
LED
OFF
FLASHING
ON
CDNTACTOR 24VAC 00M
OFF:NO 24VAC
ON :O1<
FLASFhPHASE PROBLEM
STATUS
No Call for compressor operation
Reversed phase
Normal
Fig. 25--Phase Monitor Control and LED Indicators
STUB TUBE
A00010
DEFROST
THERMOSTAT
Fig. 26--Defrost Thermostat
C99029
25
HEATPUMPWITHPURON--QUJCKREFERENCEGUIDE
Puron refrigerant operates at 50-70 percent higher pressures than R-22. Be sure that servicing equipment and replacement components are
designed to operate with Puron. Puron refrigerant cylinders are rose colored.
Puron refrigerant cylinders manufactured prior to March 1, I999, have a dip tube that allows liquid to flow out of cytinder in upright position. Cylinders manufactured March 1, 1999 and later DO NOT have a dip tube and MUST be positioned upside down to allow liquid to flow.
Recovery cylinder service pressure rating must be 400 psig (2758 kpa). DOT 4BA4O0 or DOT BW400. Puron systems should be charged with liquid refrigerant. Use a commercial type metering device in the manifold hose.
Manifold sets should be 750 psig (5171 kpa) high-side and 200 psig (1379 kpa) low-side with 520 psig (3585 kpa) tow-side retard. Use hoses with 750 psig (5171 kpa) service pressure rating. Leak detectors should be designed to detect HFC refrigerant. Puron, as with other HFCs, is only compatible with POE oils.
Vacuum pumps witt not remove moisture from oil. Only use factory specified liquid-line filter driers with rated working pressures no less than 600 psig (4137 kpa). Do not install a suction-line filter drier in liquid line. POE oils absorb moisture rapidly'. Do not expose oil to atmosphere.
POE oils may cause damage to certain plastics and roofing materials. Wrap ati filter driers and service valves with wet cloth when brazing. A Puron liquid-line filter drier is required on every unit.
Do not use an R-22 TXV. Never open system to atmosphere while it is under a vacuum.
When system must be opened for service, break vacuum with dry nitrogen and replace filter driers. Do not vent Puron into the atmosphere. Observe all warnings, cautions, and boJd text.
Do not leave Puron suction line driers in olaoe for more than 72 hrs,
26
SYMPTOM
Compressor and outdoor fan will not start
Compressor will not start but condenser fan runs
compressor producing a low pressure differential
(not pumping properly)
Compressor cycmes (other than normally
satisfying thermostat)
Compressor operates continuously
Excessive head pressure
(Continued next page)
Table 15--Troubleshooting Chart
CAUSE
Power Failure Fuse blown or circuit breaker tripped
Defective thermostat, contactor, transformer, control relay, defrost board, or high pressure or loss-
of-charge/low pressure switch
Insufficient line voltage Incorrect or faulty wiring
Thermostat setting too high
Units have a 5-minute time delay
Phase Monitor Faulty wiring or loose connections in compressor
circuit Compressor motor burned out, seized, or
internal overload open Defective overload
One leg of 3-phase power dead Low input voltage (20 percent low)
Power Leads running out of phase Scroll compressor is rotating in the wrong
direction
Refrigerant overcharge or undercharge Defective compressor
Insufficient line voltage Blocked outdoor coil Defective overload
Defective thermostat Faulty outdoor-fan motor
Damaged reversing valve Restriction in refrigerant system
Dirty air filter Unit undersized for load
Thermostat set too low
Low refrigerant charge
Frosted coil with incorrect defrost operation
Air in system
Outdoor coil dirty or restricted Dirty air filter Dirty indoor or outdoor coil Refrigerant overcharged
Air in system
(Heating) Indoor air restricted or recJrculating (Coo{ing) outdoor air restricted or recircalating
REMEDY
Carl power company Replace fuse or reset circuit breaker
Replace component
Determine cause and correct Check wiring diagram and rewire correct{y
Lower thermostat setting below room temperature
DO NOT bypass this compressor time delay-wait for 5 minutes until time-delay relay is deenergized
Correct incorrect power supply
Check wiring and repair or replace Determine cause
Replace compressor Determine cause and replace Replace fuse or reset circuit breaker. Determine
cause Determine cause and correct
Change 2 Leads or 3 Phase Power Supply Correct the direction of rotation by reversing the
3-phase power leads to the unit Recover refrigerant, evacuate system, and
recharge to capacities shown on nameplate Replace and determine cause Determine cause and correct
Determine cause and correct Determine cause and replace
Replace thermostat Replace
Determine cause and correct Locate restriction and remove
Replace filter Decrease load or increase unit size Reset thermostat
Locate leak, repair, and recharge Check defrost time settings
Reset as necessary Check defrost temperature switch Replace as necessary
Recover refrigerant, evacuate system, and recharge
Clean coil or remove restriction Replace filter
Clean coil Recover excess refrigerant
Recover refrigerant, evacuate system, and recharge
Determine cause and correct Determine cause and correct
27
SYMPTOM
Head pressure toe low
Excessive auction pressure
Suction preeeul'e toe low
Compressor runs but outdoor fan does not
IFM does not run
IFM operation is intermittent
IFM-Indoor Fan Motor
Table 16--Troubleshooting Chart (Cont'd)
CAUSE
Low refrigerant charge Restriction in liquid tube
(Heat) Outdoor ceil frosted
(Cool) High Heat load Reversing valve hung up or leaking internally Refrigerant overcharged
(Cool) Dirty air filter
(Heat) Outdoor ceil frosted
Low refrigerant charge Metering device or low side restricted
(Cool) Insufficient coil airflow
(Cool) Temperature too low in conditioned area (Cool) Outdoor ambient below 55°F (128°C)
Filter-drier restricted NC (normally dosed) contacts on defrost board
open
Blower wheel not secured to shaft insufficient voltage at motor
Power connectors not properly seated
Water dripping into motor
Connectors not firmly seated
REMEDY
Check for leaks, repair and recharge
Remove restriction Move timer on control board to 30 minutes
between defrost cycles
Check for source and eliminate
Replace valve Recover excess refrigerant
Replace filter Move timer on control board to 30 minutes
between defrost cycles
Check for leaks, repair and recharge
Remove source of restriction increase air quantity
Check filter-replace if necessary
Reset thermostat install low-ambient kit
Replace
Check condition of relay on board
Replace if necessary Properly tighten blower wheel to shaft
Determine cause and correct
Connectors should snap easily: do not force Verify proper drip loops in connector wires
Gently pull wires individually to be sure they are
crimped into the housing
2g
START-UPCHECKLIST
(REMOVEANDSTOREINJOBFILE)
L PR_=LJMRNARY INFORMATION
Modet No .............................................................................................................................................................
Serial No ..............................................................................................................................................................
Date .....................................................................................................................................................................
Technician ...........................................................................................................................................................
H. PRE-STARToUp
___ Verify that all packing materials have been removed from unit ___ Remove all shipping hotd down bolts and brackets per installation instructions ___ Verify that condensate connection is installed per installation instructions ___ Check all electrical connections and terminals for tightness
___ Check that indoor (evaporator) air filter is clean and in place ___ Verify that unit installation is level ___ Check fan wheel propeller for location in housing and setscrew tightness
HL START-UP
Supply Voltage: L1-L2 L2-L3 L3-L1 Compressor Amps: L1 L2 L3
Indoor Fan Amps:
Outdoor Motor Amps
AIR TEMPERATURE
Outdoor-Air Temperature: DB
Return-Air Temperature: DB WB Heating Mode: Heat Pump Supply Air: DB WB
Cooling Mode: Supply Air Temperature DB WB
Electric Heater Supply Air:
REFRBGERANT PRESSURf=S AND TEMPERATURES
Refrigerant Suction psig Refrigerant Discharge psig Suction Line Temp* Discharge Line Tempi-
Liquid Line Temps ___ Verify Refrigerant charge using charging tables ___ Verify that 3-phase scroll compressor is rotating in correct direction.
* Measured at suction inlet to compressor
Measured at discharge outlet from compressor
:t Measured at liquid line leavir_g condenser
29
30
31
Copyright 2002 CARRIER Corp. _ 7310 W. Morris St Indianapolis, IN 46231 50jzc2si
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations,
B°°k 1h_ PC 101 catalog No. 005-00027 Printed in U.S.A. Form 50JZ-C2SI Pg 32 7-02 Replaces: 50JZ-C1SI
Tab 15al 5a
Loading...