NOTE TO INSTALLER — READ THESE INSTRUCTIONS
CAREFULLY AND COMPLETELY before installing this unit.
Also, make sure the Owner’s Manual and Service Instructions are
left with the unit after installation.
Installation and servicing of air-conditioning equipment can be
hazardous due to system pressure and electrical components. Only
trained and qualified personnel should install, repair, or service
air-conditioning equipment.
Untrained personnel can perform basic maintenance functions of
cleaning coils andfilters. All other operations should be performed
by trained service personnel. When working on air-conditioning
equipment, observe precautions in the literature, tags and labels
attached to the unit, and other safety precautions that may apply.
Follow all safety codes. Wear safety glasses and work gloves. Use
quenching cloth for unbrazing operations. Have fire extinguisher
available for all brazing operations.
Improper installation, adjustment, alteration, service, maintenance, or use can cause explosion, fire, electric shock, or
other occurrences, which could cause serious injury or death
or damage your property. Consult a qualified installer or
service agency for information or assistance. The qualified
installer or agency must use only factory-authorized kits or
accessories when modifying this product.
Recognize safety information. This is the safety-alert symbol.
When you see this symbol on the product or in instructions or
manuals, be alert to the potential for personal injury.
Understand the signal words — DANGER, WARNING, CAUTION, and NOTE. Danger identifies the most serious hazards,
which will result in severe personal injury or death. Warning
indicates a condition that could cause serious personal injury or
death. Caution is used to identify unsafe practices, which would
result in minor personal injury or product and property damage.
NOTE is used to highlight suggestions which will result in
enhanced installation, reliability or operation.
1. The power supply (volts, phase, and hertz) must correspond to
that specified on unit rating plate.
2. The electrical supply provided by the utility must be sufficient
to handle load imposed by this unit.
3. This installation must conform with local building codes and
with NEC (National Electrical Code). Refer to provincial and
local plumbing or wastewater codes andother applicablelocal
codes.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4
Tab 5a 5a
PC 101Catalog No. 565-057Printed in U.S.A.Form 50JS,JX-1SIPg 15-00Replaces: 50JX-2SI
Page 2
REQUIRED CLEARANCE TO COMBUSTIBLE MATL.
TOP OF UNIT...................................................................................14.00 [355.6]
DUCT SIDE OF UNIT.........................................................................2.00 [50.8]
SIDE OPPOSITE DUCTS ................................................................14.00 [355.6]
BOTTOM OF UNIT.............................................................................0.50 [12.7]
ELECTRIC HEAT PANEL.................................................................36.00 [914.4]
NEC. REQUIRED CLEARANCES.
BETWEEN UNITS, POWER ENTRY SIDE....................................42.00 [1066.8]
UNIT AND UNGROUNDED SURFACES, POWER ENTRY SIDE .36.00 [914.0]
UNIT AND BLOCK OR CONCRETE WALLS AND OTHER
GROUNDED SURFACES, POWER ENTRY SIDE.........................42.00 [1066.8]
Before performing service or maintenance operations on
system, turn offmain power to unit. Turnoff accessory heater
power switch if applicable. Electrical shock could cause
severe injury or death.
Step 1—General
The 50JS and 50JX heat pumps are fully self-contained and
designed for outdoor installation (See Fig. 1). Standard units are
3
SIDE
(2)
SUPPORT B
SUPPORT A (2)
A
END VIEW
A
IN. [MM]
B
IN. [MM]
C
IN. [MM]
shipped in a horizontal-discharge configuration for installation on
a ground-level slab. Standard units can be converted to downflow
(vertical) discharge configurations for rooftop applications.
RECEIVING AND INSTALLATION
Step 1—Check Equipment
IDENTIFY UNIT — The unit model number and serial number
are stamped onthe unit identification plate. Check this information
against shipping papers.
4
7/8
2
D
IN. [MM]
13/16
A99320
Page 5
INSPECT SHIPMENT — Inspect for shipping damage while unit
is still on shipping pallet. If unit appears to be damaged or is torn
loose from its anchorage, have it examined by transportation
inspectors before removal. Forward claim papers directly to
transportation company. Manufacturer is not responsible for any
damage incurred in transit. Check all items against shipping list.
Immediately notify the nearest Carrier Air Conditioning office if
any item is missing. To prevent loss or damage, leave all parts in
original packages until installation.
Step 2—Provide Unit Support
ROOF CURB — Install accessory roof curb in accordance with
instructions shipped with curb (See Fig. 4). Install insulation, cant
strips, roofing, and flashing. Ductwork must be attached to curb.
IMPORTANT: Thegasketing ofthe unitto the roof curb is critical
for a watertight seal. Install gasketing material supplied with the
roof curb. Improperly applied gasketing also can result in air leaks
and poor unit performance.
Curb should be level to within 1/4 in. (See Fig. 5). This is
necessary for unit drain to function properly. Refer to accessory
roof curb installation instructions for additional information as
required.
A
B
C
MAXIMUM ALLOWABLE
DIFFERENCE (in.)
A-BB-CA-C
1/41/41/4
C99065
Fig. 5—Unit Leveling Tolerances
SLAB MOUNT — Place the unit on a solid, level concrete pad
that is a minimum of 4 in. thick with 2 in. above grade (See Fig.
6). The slab should extend approximately 2 in. beyond the casing
on all 4 sides of the unit. Do not secure the unit to the slab except
when required by local codes.
OPTIONAL
RETURN
AIR
OPENING
2"
EVAP. COILCOND. COIL
OPTIONAL
SUPPLY
AIR
OPENING
C99096
Fig. 6—Slab Mounting Detail
corner or under an overhead obstruction. The minimum clearance
under a partial overhang (such as a normal house overhang) is 36
in. above the unit top. The maximum horizontal extension of a
partial over-hang must not exceed 36 in. For extended overhangs,
provide a minimum clearance of 36 in.
IMPORTANT: Do not restrict outdoor airflow. An air restriction
at either the outdoor-air inlet or the fan discharge may be
detrimental to compressor life.
Do not place the unit where water, ice, or snow from an overhang
or roof will damage or flood the unit. Do not install the unit on
carpeting, tile, or other combustible materials. Slab-mounted units
should be at least 4 in. above the highest expected water and runoff
levels. Do not use unit if it has been under water.
Step 4—Rig and Place Unit
Rigging and handling ofthis equipmentcan behazardous formany
reasons due to the installation location (roofs, elevated structures,
etc.)
Only trained, qualified crane operators and ground support staff
should handle and install this equipment.
When working with this equipment, observe precautions in the
literature, on tags, stickers and labels attached to the equipment,
and any other safety precautions that might apply.
Follow all applicable safety codes. Wear safety shoes and work
gloves.
INSPECTION — Prior to initial use, and at monthly intervals, all
rigging brackets and straps should be visually inspected for any
damage, evidence of wear, structural deformation, or cracks.
Particular attention should be paid to excessive wear at hoist
hooking points and load support areas. Brackets or straps showing
any kind of wear in these areas must not be used and should be
discarded.
INSTALLATION
1. Remove unit from shipping carton. Leave top shipping skid on
the unit as a spreader bar to prevent the rigging straps from
damaging the unit. If the wood skid is not available, use a
spreader bar of sufficient length to protect unit from damage.
2. Position the lifting bracket assembly around the base of the
unit. Be sure the strap does not twist.
3. Place each of the 4 metal lifting brackets into the handholds in
the composite pan.
4. Thread lifting bracket strapping around bottom perimeter of
unit as follows:
a. Open lever of tension buckle (ratchet type).
b. Feed strapping through tension buckle as shown in Fig. 7.
c. Pull strapping through tension buckle unit taut.
d. Snap lever down to lock strap in tension buckle. To release
strapping, squeeze safety latch, lift lever, and pull webbing
outward.
GROUND MOUNT — The unit may be installed either on a slab
or placed directly on the ground if local codes permit. Place the
unit on level ground prepared with gravel for condensate discharge.
Step 3—Provide Clearances
The required minimum service clearances are shown in Figs. 2 and
3. Adequate ventilation and outdoor air must be provided. The
outdoor fan draws air through the outdoor coil and discharges it
through the top fan grill. Be sure that the fan discharge does not
recirculate to the outdoor coil. Do not locate the unit in either a
HANDHOLD
HOOK
FEED
C99067
Fig. 7—Threading Belt
5
Page 6
5. Tighten the tension buckle until it is taut. Lifting brackets
must be secure in the handholds.
6. Attach field-supplied clevis or hook of sufficient strength to
hole in the lifting bracket (See Fig. 8).
7. Attach the 2 safety straps directly to the clevis or hook at the
4 rigging brackets. DO NOT attach the safety straps to the
lifting brackets (See Fig. 8).
914-137"
“A”
“B”
INSTALL SAFETY STRAPS TO
RIGGING CLEVIS AT 4 RIGGING BRACKETS
PLACE RIGGING BRACKET ASSEMBLY IN 4
HAND HOLES AND INSTALL TIE DOWN STRAP
AROUND PERIMETER OF UNIT AND THROUGH
For vertical supply and return units, tools or parts could drop
into ductwork and cause serious injury or death. Install a 90
degree turn in the return ductwork between the unit and the
conditioned space. If a 90 degree elbow cannot be installed,
then a grille of sufficient strength and density should be
installed to prevent objects from falling into the conditioned
space. Units with electric heaters require 90 degree elbow in
supply duct.
1. All units should have field-supplied filters or accessory filter
rack installed in the return-air side of the unit. Recommended
sizes for filters are shown in Tables 1A and 1B.
2. Avoid abrupt duct size increases and reductions. Abrupt
change in duct size adversely affects air performance.
IMPORTANT: Use flexible connectors between ductwork and
unit to prevent transmission of vibration. Use suitable gaskets to
ensure weather tight and airtight seal. When electric heat is
installed, use fireproof canvas (or similar heat resistant material)
connector between ductwork and unit discharge connection. If
flexible duct is used, insert a sheet metal sleeve inside duct. Heat
resistant duct connector (or sheet metal sleeve) must extend 24-in.
from electric heater element.
3. Size ductwork for cooling air quantity (cfm). The minimum
air quantity for proper electric heater operation is listed in
Tables 2A and 2B. Heater limit switches may trip at air
quantities below those recommended.
4. Seal, insulate and weatherproof all external ductwork. Seal,
insulate and cover with a vapor barrier all ductwork passing
through conditioned spaces. Follow latest Sheet Metal and Air
Conditioning Contractors National Association (SMACNA)
and Air Conditioning Contractors Association (ACCA) minimum installation standards for residential heating and air
conditioning systems.
5. Secure all ducts to building structure. Flash,weatherproof, and
vibration-isolate duct openings in wall or roof according to
good construction practices.
CONVERTING HORIZONTAL DISCHARGE UNITS TO
DOWNFLOW (VERTICAL) DISCHARGE UNITS
Before performing service or maintenance operations on
system, turn offmain power to unit. Turnoff accessory heater
power switch if applicable. Electrical shock could cause
serious injury or death.
8. Position lifting point directly over the unit’s center of gravity.
9. Lift unit. When unit is directly over the roof curb, remove the
2 safety straps. Lower the equipment onto the roof curb.
Step 5—Select and Install Ductwork
The design and installation of the duct system must be in
accordance with the standards of the NFPA for installation of
non-residence type air conditioning andventilating systems,NFPA
90A or residence-type, NFPA 90B and/or local codes and ordinances.
Select and sizeductwork, supply-air registers, and return air grilles
according to ASHRAE (American Society of Heating, Refrigeration, and Air Conditioning Engineers) recommendations.
The unit hasduct flanges on the supply- and return-airopenings on
the side of the unit.
When designing and installing ductwork, consider the following:
1. Open all electrical disconnects before starting any service
work.
2. Remove side duct covers to access bottom return and supply
knock outs.
3. Use a screwdriver and hammer to remove the panels in the
bottom of the base pan.
4. Reinstall the side duct covers to block off the horizontal air
openings.
NOTE: These panels are held in place with tabs similar to an
electrical knockout.
NOTE: Avoid abrupt duct size increases and reductions. Abrupt
change in duct size adversely affects air performance.
Step 6—Provide for Condensate Disposal
NOTE: Ensure that condensate-water disposal methods comply
with local codes, restrictions, and practices.
6
Page 7
Table 1A—Physical Data
UNIT SIZE50JS01850JS02450JS03050JS03650JS04250JS04850JS060
Table 2B—Minimum Airflow for Reliable Electric Heater Operation (Cfm)
SIZE50JX02450JX03050JX03650JX04250JX04850JX060
AIRFLOW (CFM)8001000*1200140016002000
* The 030 size models must be run on medium or high speed when used in conjunction with 15 Kw electric heat accessory.
7
Page 8
RETURN
AIR
INDOOR
THERMOSTAT
1” MIN.
TRAP
OUTLET
2” MIN.
TOP COVER
FROM
POWER
SOURCE
DISCONNECT
PER NEC
C99061
Fig. 9—Typical Installation
Accessory Duct Covers
C99030
Fig. 10—50JX with Duct Covers On
(Unit shown with optional louvered grille)
The units dispose of condensate through a 3/4 in. NPT female
fitting that exits on the compressor end of the unit. Condensate
water can be drained directly onto the roof in rooftop installations
(where permitted) or onto a gravel apron in ground level installations. Install a field-supplied condensate trap at end of condensate
connection to ensure proper drainage. Make sure that the outlet of
the trap is at least 1 in. lower than the drain-pan condensate
connection to prevent the pan from overflowing. Prime the trap
with water. When using a gravel apron, make sure it slopes away
from the unit.
If the installation requires draining the condensate water away
from the unit, install a field-supplied 2 -in. trap at the condensate
connection to ensure proper drainage. Condensate trap is available
as an accessory oris field-supplied.Make surethat theoutlet ofthe
trap is at least 1 in. lower than the unit drain-pan condensate
connection to prevent the pan from overflowing. Connect a drain
trough using a minimum of field-supplied 3/4 -in. PVC or
field-supplied 3/4 -in. copper pipe at outlet end of the 2 -in. trap
(See Fig. 11). Do not undersize the tube. Pitch the drain trough
downward at a slope of at least 1 in. every 10 ft of horizontal run.
Be sure to check the drain trough for leaks. Prime the trap at the
beginning of the cooling season start-up.
C99013
Fig. 11—Condensate Trap
Step 7—Install Electrical Connections
The unit cabinet must have an uninterrupted, unbroken
electrical ground to minimize the possibility of personal
injury if an electrical fault should occur. This ground may
consist of an electrical wire connected to the unit ground lug
in the control compartment, or conduit approved for electrical
ground when installed in accordance with NEC, ANSI/NFPA
American National Standards Institute/National Fire Protection Association (latest edition) (in Canada, Canadian Electrical Code CSA C22.1) and local electrical codes. Failure to
adhere to this warning could result in serious injury or death.
Failure to follow these precautions could result in damage to
the unit being installed:
1. Make all electrical connections in accordance with NEC
ANSI/NFPA (latest edition) and local electrical codes
governing such wiring. In Canada, all electrical connections must be in accordance with CSA standard C22.1
Canadian Electrical Code Part 1 and applicable local
codes. Refer to unit wiring diagram.
2. Use only copper conductor for connections between
field-supplied electrical disconnect switch and unit. DO
NOT USE ALUMINUM WIRE.
3. Be sure that high-voltage power to unit is within operating
voltage range indicated on unit rating plate. On 3-phase
units, ensure phases are balanced within 2%. Consult local
power company for correction of improper voltage and/or
phase imbalance.
4. Insulate low-voltage wires for highest voltage contained
within conduit when low-voltage control wires are in same
conduit as high-voltage wires.
5. Do not damage internal components when drilling through
any panel to mount electrical hardware, conduit, etc.
HIGH-VOLTAGE CONNECTIONS — The unit must have a
separate electrical service with a field-supplied, waterproof disconnect switch mounted at, or within sight from the unit. Refer to
the unit rating plate, NEC and local codes for maximum
fuse/circuit breaker size and minimum circuit amps (ampacity) for
wire sizing (See Tables 3A and 3B for electrical data).
The field-supplied disconnectmay be mounted on theunit over the
high-voltage inlet hole (See Figs. 2-3).
If the unit has an electric heater, a second disconnect may be
required. Consult the Installation, Start-Up and Service Instructions provided with the accessory for electrical service connections.
Operation of unit on improper line voltage constitutes abuse and
may cause unit damage that could affect warranty.
ROUTING POWER LEADS INTO UNIT — Use only copper
wire between disconnect and unit. The high-voltage leads should
8
Page 9
FIELD SPLICE
TERMINAL (MARKED)
TERMINAL (UNMARKED)
SPLICE
SPLICE (MARKED)
FACT OR Y WIRING
FIELD CONTROL WIRING
FIELD POWER WIRING
ACCESSORY OR OPTIONAL
WIRING
TO INDICATE COMMON
POTENTIAL ONLY:
NOT TO REPRESENT WIRING
NOTES:
1. IF ANY OF THE ORIGINAL WIRES FURNISHED ARE REPLACED, IT MUST BE
REPLACED WITH TYPE 90 DEGREE C WIRE OR IT’S EQUIVALENT.
2. SEE PRICE PAGES FOR THERMOSTAT AND SUBBASES.
3. USE 75 DEGREE COPPER CONDUCTORS FOR FIELD INSTALLATION.
4. FOR HIGH SPEED IFM, DISCONNECT RED
WIRE FROM TDR 3 AND CONNECT BLK WIRE FROM IFM.
FOR MEDIUM SPEED, DISCONNECT RED WIRE
FROM TDR 3 AND CONNECT BLU WIRE FROM IFM.
5. DEFROST TIMER TO BE SET AT 90 MINUTES EXCEPT FOR 50JS048, 060 MODELS
SET AT 50 MINUTES.
LEGEND
AHAADJUSTABLE HEAT ANTICIPATOR
CCONTACTOR
CAPCAPACITOR
CBCIRCUIT BREAKER
COMP COMPRESSOR MOTOR
CTDCOMPRESSOR TIME DELA Y
DBDEFROST BOARD
DFTDEFROST THERMOST AT
DRDEFROST RELAY
EQUIP EQUIPMENT
FUFUSE
GNDGROUND
HRHEATER RELAY
HTRHEATER
IFMINDOOR FAN MOTOR
LPSLOW PRESSURE SWITCH
OFMOUTDOOR FAN MOTOR
QTQUADRUPLE TERMINAL
RVS REVERSING VALVE SOLENOID
S.B.SLOW BLOW FUSE
TCTHERMOSTAT - COOLING
TDRTIME DELAY RELAY
THTHERMOSTAT - HEATING
TRANTRANSFORMER
Fig. 12—Wiring Schematics
9
A00073
Page 10
Fig. 13—Wiring Schematics
A00074
Page 11
LEGEND
FIELD SPLICE
TERMINAL (MARKED)
TERMINAL (UNMARKED)
SPLICE
SPLICE (MARKED)
FACT OR Y WIRING
FIELD CONTROL WIRING
FIELD POWER WIRING
ACCESSORY OR OPTIONAL
WIRING
TO INDICATE COMMON
POTENTIAL ONLY:
NOT TO REPRESENT WIRING
NOTES:
1. IF ANY OF THE ORIGINAL WIRES FURNISHED ARE REPLACED, IT MUST BE
REPLACED WITH TYPE 90 DEGREE C WIRE OR IT’S EQUIVALENT.
2. SEE PRICE PAGES FOR THERMOSTAT AND SUBBASES.
3. USE 75 DEGREE COPPER CONDUCTORS FOR FIELD INSTALLATION.
4. FOR HIGH SPEED IFM, DISCONNECT RED
WIRE FROM TDR 3 AND CONNECT BLK WIRE FROM IFM.
FOR MEDIUM SPEED, DISCONNECT RED WIRE
FROM TDR 3 AND CONNECT BLU WIRE FROM IFM.
5. DEFROST TIMER TO BE SET AT 90 MINUTES EXCEPT FOR 50JS048, 060 MODELS
SET AT 50 MINUTES.
Fig. 14—Wiring Schematics
11
AHAADJUSTABLE HEAT ANTICIPATOR
CCONTACTOR
CAPCAPACITOR
CBCIRCUIT BREAKER
COMP COMPRESSOR MOTOR
CTDCOMPRESSOR TIME DELA Y
DBDEFROST BOARD
DFTDEFROST THERMOST AT
DRDEFROST RELAY
EQUIP EQUIPMENT
GNDGROUND
HRHEATER RELAY
HTRHEATER
IFMINDOOR FAN MOTOR
LPSLOW PRESSURE SWITCH
OFMOUTDOOR FAN MOTOR
OFROUTDOOR FAN RELAY
QTQUADRUPLE TERMINAL
RVS REVERSING VALVE SOLENOID
TCTHERMOSTAT - COOLING
TDRTIME DELAY RELAY
THTHERMOSTAT - HEATING
TRANTRANSFORMER
A00075
Page 12
Table 3A—Electrical Data—50JS
UNIT 50JS
SIZE
018208/230-1-60 1872539480.91.8
024208/230-1-60 18725312.8610.92
030
036
042
048
060
* Heater capacity (KW) based on heater voltage of 208v, 240v, and 480v. If power distribution voltage to unit varies from rated heater voltage, heater KW will vary
accordingly.
V-PH-HZ
208/230-1-60 18725314.7820.92
208/230-3-60 1872539.9780.92
208/230-1-60 18725316.8821.54.1
208/230-3-60 1872539.9851.54.1
460-3-604145065.5400.81.9
208/230-1-60 18725320.61150.93.8
208/230-3-60 18725312.4900.93.8
460-3-604145066.7450.81.8
208/230-1-60 18725324.41401.53.5
208/230-3-60 18725314.11051.53.5
460-3-604145067.1530.81.8
208/230-1-60 18725328.81651.56.2
208/230-3-60 18725319.41251.56.2
460-3-604145068630.83.2
VOLTAGE
RANGE
Min MaxRLALRAFLAFLA Nominal KW*FLAMCAMax Fuse or CRCT BreakerMOCP
COMPRESSOR ODFM IDFMELECTRIC HEATPOWER SUPPLY
-/-
3.8/5
7.5/10
-/-
3.8/5
7.5/10
-/-
3.8/5
7.5/10
11.3/15
-/-
3.8/5
7.5/10
11.3/15
-/-
3.8/5
7.5/10
11.3/15
-/-
3.8/5
7.5/10
11.3/15
-/5
10
15
-/5
10
15
20
-/-
3.8/5
7.5/10
11.3/15
15/19.94
-/5
10
15
15-20
-/-
3.8/5
7.5/10
11.3/15
15/20
-/-
3.8/5
7.5/10
11.3/15
15/19.94
-/5
10
15
20
-/-
3.8/5
7.5/10
11.3/15
15/20
-/-
3.8/5
7.5/10
11.3/15
15/19.94
-/5
10
15
20
-/-
18.1/20.8
36.1/41.7
-/-
18.1/20.8
36.1/41.7
-/-
18.1/20.8
36.1/41.7
54.2/62.5
-/-
10.4/12
20.8/24.1
31.3/36.1
-/-
18.1/20.8
36.1/41.7
54.2/62.5
-/-
10.4/12
31.3/36.1
36.1/41.7
-/-
6.0
12.0
18.0
-/-
18.1/20.8
36.1/41.7
54.2/62.5
72.2/83.3
-/-
10.4/12
20.8/24.1
31.3/36.1
41.6/48
-/-
6.0
12.0
18.0
24.1
-/-
18.1/20.8
36.1/41.7
54.2/62.5
72.2/83.3
-/-
10.4/12
20.8/24.1
31.3/36.1
41.6/48.0
-
6.0
12.0
18.0
24.1
-/-
18.1/20.8
36.1/41.7
54.2/62.5
72.2/83.3
-/-
10.4/12
20.8/24.1
31.3/36.1
41.6/48.0
-
6.0
12.0
18.0
24.1
14.0/14.0
24.8/28.3
47.4/54.3
18.9/18.9
25.1/28.5
47.6/54.6
21.3/21.3
25.1/28.5
47.6/54.6
72.8/83.3
15.3/15.3
15.5/17.5
28.6/32.6
44.2/50.2
26.6/26.6
27.7/31.2
50.3/57.2
72.8/83.3
18.0/18.0
18.2/20.2
44.2/50.2
47.8/54.7
9.6
9.9
17.4
24.9
30.5/30.5
30.5/30.8
49.9/56.8
72.4/82.9
95.0/108.9
20.2/20.2
20.2/20.2
30.8/34.8
43.8/49.9
56.7/64.7
11.0
11.0
17.3
24.8
32.3
35.5/35.5
35.5/35.5
49.5/56.5
72.1/82.5
94.6/108.5
22.6/22.6
22.6/22.6
30.4/34.4
43.5/49.5
56.3/64.3
11.5
11.5
17.3
24.8
32.3
43.7/43.7
43.7/43.7
52.9/59.8
75.4/85.9
98.0/111.9
32.0/32.0
32.0/32.0
33.8/37.8
46.8/52.9
59.7/67.7
14.0
14.0
19.0
26.6
34.1
20/20
25/25
50/60
25/25
25/30
50/60
25/25
25/30
50/60
-
20/20
20/20
30/35
45/60
35/35
35/35
60/60
-
25/25
25/25
35/40
45/60
15
15
20
25
40/40
40/40
50/60
-
-
25/25
25/25
35/35
45/50
-
15
15
20
25
35
45/45
45/45
50/60
-
-
30/30
30/30
35/35
45/50
-
15
15
20
25
35
60/60
60/60
60/60
-
-
40/40
40/40
35/40
50/60
-
20
20
20
30
35
-
-
-
-
-
-
-
-
-
80/90
-
-
-
-
-
-
-
80/90
-
-
-
-
-
-
-
-
-
-
-
90.0
100/110
-
-
-
-
60/70
-
-
-
-
-
-
-
-
90.0
100/110
-
-
-
-
60/70
-
-
-
-
-
-
-
-
90.0
100/125
-
-
-
-
60/70
-
-
-
-
-
12
Page 13
→Table 3B—Electrical Data—50JX
UNIT 50JX
SIZE
024208/230-1-60 187 253.0010.8560.902
030
036
042
048
060
* Heater capacity (KW) based on heater voltage of 208v, 240v, and 480v. If power distribution voltage to unit varies from rated heater voltage, heater KW will vary
accordingly.
V-PH-HZ
208/230-1-60 18725314730.92.1
208/230-3-60 18725310.3630.92.1
208/230-1-60 18725316.7971.63.6
208/230-3-60 18725311.9751.63.6
460-3-604145065.437.50.91.9
208/230-1-60 18725318.41040.94.1
208/230-3-60 18725312.4880.94.1
460-3-604145065.8440.92.0
208/230-1-60 18725323.41041.64.1
208/230-3-60 18725313.5881.64.1
460-3-604145066.8440.92
208/230-1-60 18725328.81691.46.2
208/230-3-60 18725317.31231.46.2
460-3-604145069620.93.2
VOLTAGE
RANGE
MinMaxRLALRAFLAFLA Nominal KW*FLAMCAMax Fuse or CRCT BreakerMOCP
COMPRESSOR ODFM IDFMELECTRIC HEATPOWER SUPPLY
-/-
3.75/5.0
7.5/10
-/-
3.75/5.0
7.5/10
11.3/15
-/-
3.75/5.0
7.5/10
11.3/15
-/-
3.75/5.0
7.5/10
11.3/15
-/-
3.75/5.0
7.5/10
11.3/15
--/5
10
15
-/-
3.75/5.0
7.5/10
11.3/15
15.0/20.0
-/-
3.75/5.0
7.5/10
11.3/15
15.0/20.0
-/5
10
15
20
-/-
3.75/5.0
7.5/10
11.3/15
15.0/20.0
-/-
3.75/5.0
7.5/10
11.3/15
15.0/20.0
-/5
10
15
20
-/-
3.75/5.0
7.5/10
11.3/15
15.0/20.0
-/-
3.75/5.0
7.5/10
11.3/15
15.0/20.0
-/5
10
15
20
-/-
18.1/20.8
36.1/41.7
-/-
18.1/20.8
36.1/41.7
54.2/62.5
-/-
10.4/12.0
20.8/24.1
31.3/36.1
-/-
18.1/20.8
36.1/41.7
54.2/62.5
-/-
10.4/12.0
20.8/24.1
31.3/36.1
--/6
12
18
-/-
18.1/20.8
36.1/41.7
54.2/62.5
72.2/83.3
-/-
10.4/12.0
20.8/24.1
31.3/36.1
41.6/48.0
-/6
12
18
24
-/-
18.1/20
36.1/41.7
54.2/62.5
72.2/83.8
-/-
10.4/12.0
20.8/24.1
31.3/36.1
41.6/48
-/6
12
18
24
-/-
18.1/20.8
36.1/41.7
54.2/62.5
72.2/83.3
-/-
10.4/12.0
20.8/24.1
31.3/36.1
41.6/48.0
-/6
12
18
24
16.4/16.4
25.1/28.5
47.6/54.6
20.5/20.5
25.2/28.7
47.8/54.7
72.2/82.6
16.0/16.0
16.0/17.7
28.7/32.7
41.7/47.7
26.1/26.1
27.1/30.5
49.6/56.6
72.2/82.6
19.2/19.2
19.2/19.5
47.8/54.7
43.6/49.6
9.6
9.9
17.4
24.9
28.0/28.0
28.0/31.2
50.3/57.2
72.8/83.3
95.4/109.3
20.5/20.5
20.5/20.5
31.2/35.2
44.2/50.2
57.1/65.1
10.2
10.2
17.5
25.1
32.6
35.0/35.0
35.0/35.0
50.3/57.2
72.8/83.3
95.4/109.3
22.6/22.6
22.6/22.6
31.2/35.2
44.2/50.2
57.1/65.1
11.4
11.4
17.5
25.1
32.6
43.6/43.6
43.6/43.6
52.9/59.8
75.4/85.9
98.0/111.9
29.2/29.2
29.2/29.2
33.8/37.8
46.8/52.9
59.7/67.7
15.4
15.4
19.0
26.6
34.1
20/20
25/30
50/60
25/25
25/30
50/60
-
20/20
20/20
30/35
45/50
35/35
35/35
50/60
-
25/25
25/25
35/35
45/50
15
15
20
25
35/35
35/35
60/60
-
-
25/25
25/25
35/40
45/60
-
15
15
20
30
35
45/45
45/45
60/60
-
-
30/30
30/30
35/40
45/60
-
15
15
20
30
35
60/60
60/60
60/60
-
-
35/35
35/35
35/40
50/60
-
20
20
20
30
35
-
-
-
-
-
-
80/90
-
-
-
-
-
-
-
80/90
-
-
-
-
-
-
-
-
-
-
-
90.0
100/110
-
-
-
-
60/70
-
-
-
-
-
-
-
-
90.0
100/110
-
-
-
-
60/70
-
-
-
-
-
-
-
-
90.0
100/125
-
-
-
-
60/70
-
-
-
-
-
13
Page 14
LEGEND
FLA— Full Load Amps
LRA— Locked Rotor Amps
MCA— Minimum CircuitAmps
MOCP — Maximum Overcurrent Protection
RLA— Rated Load Amps
NOTES:
1. In compliance with NEC (National Electrical Code) requirements
for multimotor and combination load equipment (refer to NEC
Articles 430 and 440), the overcurrent protective device for the
unit shall be Power Supply fuse. The CGA (Canadian Gas
Association) units may be fuse or circuit breaker.
2. Minimum wire size is based on 60 C copper wire. If other than
60 C wire is used, or if length exceeds wire length in table,
determine size from NEC.
3. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is greater than 2%.
the percentage of voltage imbalance.
% Voltage imbalance
max voltage deviation from average voltage
= 100 x
Use the following formula to determine
average voltage
®
Fig. 15—Electrical Data Legend
EXAMPLE: Supply voltage is 460-3-60.
Determine maximum deviation from average voltage.
(AB) 457
(BC) 464
(AC) 457
Maximum deviation is 7 v.
Determine percent of voltage imbalance.
% Voltage Imbalance = 100 x
This amount of phase imbalance is satisfactory as it is below the
maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is
more than 2%, contact your local electric utility company
immediately.
AB = 452 v
BC = 464 v
AC = 455 v
Average Voltage =
452=5v
457=7v
455=2v
= 1.53%
7
457
452 + 464 + 455
3
1371
=
3
= 457
C99024
be in a conduit until they enter the duct panel; conduit termination
at the duct panel must be watertight. Run the high-voltage leads
through the power entry knockout on the power entry side panel
(See Fig. 2 and 3 for location and size). When the leads are inside
the unit, run leads up the high-voltage raceway to the line wiring
splice box (See Fig. 12 through 14). For single-phase units,
connect leads to the black and yellow wires; for 3-phase units,
connect the leads to the black, yellow, and blue wires (See Fig.
17).
C
O
R
G
Y
E
W2
THERMOSTAT
AND SUBBASE
UNIT CONTROL POWER
BRN
ORN
RED
GRN
YEL
WHT
SPLICE BOX
C99056
Fig. 16—Control Connections
CONNECTING GROUND LEAD TO GROUND LUG — Refer
to Fig. 17. Connect the ground lead to the chassis using the ground
lug in the wiring splice box.
ROUTING CONTROL POWER WIRES — (24 V) — Form a
drip-loop with the thermostat leads before routing them into the
unit. Route the thermostat leads through grommeted, low-voltage
hole provided in unit into unit control power splice box (See Fig.
2 and 3). Connect thermostat leads to unit control power leads as
shown in Fig. 16.
The unit transformer supplies 24-v power for complete system
including accessory electrical heater. An automatic-reset circuit
breaker (See Fig. 18)is provided inthe 24-vcircuit; seethe caution
label on the transformer or Fig. 19. Transformer is factory wired
for 230-v operation. If supply voltage is 208 v, rewire transformer
primary as described in Special Procedures for 208-V Operation
section.
GROUND LUG
(IN SLPICE BOX)
GROUND
LEAD
SINGLE-PHASE
L1
CONNECTIONS
TO DISCONNECT
PER NEC
3-PHASE
CONNECTIONS
LEGEND
L2
L3
NOTE: Use copper wire only.
NEC – National Electrical Code
Field Wiring
Splice Connections
Fig. 17—Line Power Connections
BLK
YEL
BLU
C99057
24 V Circuit Breaker
24 V olt Compartment
C99070
Fig. 18—Control Wiring Plate
14
Page 15
TRANSFORMER CONTAINS A MANUAL
RESET OVERCURRENT PROTECTOR
IT WILL NOT AUTOMATICALLY RESET
DISCONNECT POWER PRIOR TO
SERVICING
THIS COMPARTMENT MUST BE CLOSED
EXCEPT WHEN SERVICING
Fig. 19—Transformer Label
C99058
SPECIAL PROCEDURES FOR 208-V OPERATION
1. Disconnect the yellow primary lead (w110) from the transformer. See unit wiring label (See Fig. 12 through 14).
2. Connect the yellow primary lead (w110) to the transformer
terminal labeled 200v.
Indoor blower-motor speeds may need to be changed for 208-v
operation. Refer to indoor airflow and airflow adjustments section.
PRE-START-UP
Failure to observe the following warnings could result in
serious personal injury or death:
1. Follow recognized safety practices and wear protective
goggles when checking or servicing refrigerant system.
2. Do not operate compressor or provideany electric power to
unit unless compressor terminal cover is in place and
secured.
3. Do not remove compressor terminal cover until all electrical sources are disconnected.
4. Relieve and recover all refrigerant from system before
touching or disturbing anything inside terminal box if
refrigerant leak is suspected around compressor terminals.
5. Never attempt to repair soldered connection while refrigerant system is under pressure.
6. Do not use torch to remove any component. System
contains oil and refrigerant under pressure.
To remove a component, wear protective goggles and
proceed as follows:
a. Shut off electrical power to unit.
b. Relieve and reclaim all refrigerant from system using
both high- and low-pressure ports.
c. Cut component connecting tubing with tubing cutter and
remove component from unit.
d. Carefully unsweat remaining tubing stubs when neces-
sary. Oil can ignite when exposed to torch flame.
Use the Start-Up Checklist supplied at the end of this book and
proceed as follows to inspect and prepare the unit for initial
start-up:
1. Remove access panel.
2. Read and follow instructions on all DANGER, WARNING,
CAUTION, and INFORMATION labels attached to, or
shipped with, unit.
3. Make the following inspections:
a. Inspect for shipping and handling damages such as broken
lines, loose parts, disconnected wires, etc.
b. Inspect for oil at all refrigerant tubing connections and on
unit base. Detecting oil generally indicates a refrigerant
leak. Leak-test all refrigerant tubing connections using
electronic leak detector, or liquid-soap solution. If a refrigerant leak is detected, see following Check for Refrigerant
Leaks section.
c. Inspect all field and factory-wiring connections. Be sure
that connections are completed and tight.
d. Inspect coil fins. If damaged during shipping and handling,
carefully straighten fins with a fin comb.
4. Verify the following conditions:
a. Make sure that outdoor-fan blade is correctly positioned in
fan orifice.
b. Make sure that condensate drain pan and trap are filled
with water to ensure proper drainage.
c. Make sure that all tools and miscellaneous loose parts have
been removed.
5. Compressors are internally spring mounted. Do not loosen or
remove compressor hold-down bolts.
6. Each unit system has 2 Schrader-type ports, one low-side
Schrader fitting located on the suction line, and one high-side
Schrader fitting located on the compressor discharge line. Be
sure that caps on the ports are tight.
MOTOR
1/8" MAX BETWEEN
MOTORAND FAN HUB
MOTOR SHAFT
FAN GRILLE
C99009
Fig. 20—Fan Blade Clearance
START-UP
Using the Start-Up Checklist supplied at the end of this book,
proceed as follows:
Step 1—Check for Refrigerant Leaks
Locate and repair refrigerant leaks and charge the unit as follows:
1. Use both high- and low-pressure ports to relieve system
pressure and reclaim remaining refrigerant
2. Repair leak following accepted practices.
NOTE: Install a bi-flow filter drier whenever the system has
been opened for repair.
3. Check system for leaks using an approved method.
4. Evacuate refrigerant system and reclaim refrigerant if no
additional leaks are found.
5. Charge unit with R-22 refrigerant, using a volumetriccharging cylinder or accurate scale. Refer to unit rating plate
for required charge. Be sure to add extra refrigerant to
compensate for internal volume of filter drier.
Step 2—Start-Up Adjustments
Complete the required procedures given in the Pre-Start-Up
section on this page before starting the unit. Do not jumper any
safety devices when operating the unit. Do not operate the unit in
Cooling mode when the outdoor temperature is below 40°F (unless
accessory low-ambient kit is installed). Do not rapid-cycle the
compressor. Allow 5 min. between ‘‘on’’ cycles to prevent
compressor damage.
CHECKING COOLING AND HEATING CONTROL OPERATION — Start and check the unit for proper control operation as
follows:
1. Place room thermostat SYSTEM switch in OFF position.
Observe that blower motor starts when FAN switch is placed
in ON position and shuts down within 60 sec. when FAN
switch is placed in AUTO position.
15
Page 16
OUTDOOR COIL
ACCUMULATOR
COMPRESSOR
Metering
Position
Bypass
Position
LCS
INDOOR COIL
LEGEND
LCS – Loss of Charge Switch
Accurater® Metering Device
Arrow indicates direction of flow
C99027
1. Hot gas from compressor flows through the 4-way valve and is directed to the indoor coil. It is then condensed and subcooled through the coil circuits and then leaves
the indoor coil by way of the ID Accurater in the bypass position to the liquid line.
2. The refrigerant then feeds the outdoor coil through the OD Accurater device in the metering position and distributes to each circuit.
3. Each circuit evaporates the refrigerant and the circuits are combined in the outdoor coil header.
4. The refrigerant then flows through the 4-way valve, accumulator, and back to the compressor.
Fig. 21—Typical Heat Pump Operation, Heating Mode
INDOOR COIL
ACCUMULATOR
LEGEND
COMPRESSOR
OUTDOOR COIL
Bypass
Position
Metering
Position
LCS
LCS – Loss of Charge Switch
®
Accurater
Metering Device
Arrow indicates direction of flow
C99028
1. Hot gas from compressor flows through the 4-way valve and is directed to the outdoor coil. It is then condensed and subcooled through the coil circuits. Refrigerant leaves
the outdoor coil by way of the OD Accurater in the bypass position to the liquid line.
2. The refrigerant then feeds the indoor coil through the ID Accurater device in the metering position and distributes to each circuit.
3. Each circuit evaporates the refrigerant and the circuits are combined in the indoor coil header.
4. The refrigerant then flows through the 4-way valve, accumulator, and back to the compressor.
Fig. 22—Typical Heat Pump Operation, Cooling Mode
16
Page 17
Table 4A—Wet Coil Air Delivery
Unit 50JS 018-060 (Deduct 10% for 208v)*
UNITMOTOR SPEED
Low
018
024
30
36
42
48
60
* Air delivery valuesare basedon operating voltage of 230 v or 460 v,wet coil, without filter or electric heater. Deduct filter and electricheater pressure drops to obtain
static pressure available for ducting.
NOTES:
1. Do not operate the unit at a cooling airflow that is less than 350 cfm for each 12,000 Btuh of rated cooling capacity. Evaporator coil frosting may occur at airflows below
this point.
2. Dashes indicate portions of table that are beyond the blower motor capacity or are not recommended.
3. Deduct 10% for 208v.
Med
High
Low
Med
High
Low
Med
High
Low
Med
High
Low
Med
High
Low
Med
High
Low
Med
High
Watts---214191170-----
Cfm---821696575-----
Watts-----------
Cfm-----------
Watts----283274267----
Cfm----848707555----
Watts--237214191------
Cfm--971821696------
Watts----368366365360---
Cfm----957872785688---
Watts-------425414--
Cfm-------891735--
Watts295292289--------
Cfm928882802--------
Watts388383377372366361-----
Cfm1203112010621004930838-----
Watts----469458449442---
Cfm----11411027924828---
Watts592581567552538525512499---
Cfm1499142113511281120711251034936---
Watts---660636617603592581566-
Cfm---147513711274118611051024928-
Watts-----776761744725706689
Cfm-----14521356125411451030910
Watts606596586575563550537----
Cfm1464139913411282121811461066----
Watts680665649635622611600590---
Cfm16081535146113871316124711801111---
Watts768755742730718707696684671--
Cfm165615761508144713901331126811981119--
Watts741724709690664631594562543552-
Cfm1994193718691797172216451566148013841269-
Watts---773744715687662640625-
Cfm---1957186717871719165315751463-
Watts-----799782773756704-
Cfm-----19141842177416861538-
Watts742723698666629591559540---
Cfm21972141210320571988189417831674---
Watts838822803780752721689661639632-
Cfm2485240622692127201219371894185517701571-
Watts-934913891866837806776750735-
Cfm-248323912283217020611960186817801687-
0.00.10.20.30.40.50.60.70.80.91.0
EXTERNAL STATIC PRESSURE (IN. WG)
2. Place SYSTEM switch in COOL position and FAN switch in
AUTO position. Setcontrol below room temperature. Observe
that cooling cycleshuts down when control settingis satisfied.
3. Place system switch in HEAT position. Set control above
room temperature. Observe that compressor, outdoor fan, and
indoor blower motors start. Observe that heating cycle shuts
down when control setting is satisfied.
4. When using an automatic changeover room thermostat, place
both SYSTEM and FAN switches in AUTO positions. Observe that unit operates in Cooling mode when temperature
control is setto ‘‘call for Cooling’’ (below room temperature),
and unit operates in Heating mode when temperature control
is set to "call for Heating" (above room temperature).
IMPORTANT: Three-phase, scroll compressors are direction oriented. Unit must be checked to ensure proper compressor 3-phase
power lead orientation. If not corrected within 5 min., the internal
protector will shut off the compressor. The 3-phase power leads to
the unit must be reversed to correct rotation. When turning
backwards, scroll compressors emit elevated noise levels, and the
difference between compressor suction and discharge pressures
may be dramatically lower than normal.
CHECKING AND ADJUSTING REFRIGERANT CHARGE
— The refrigerant system is fully charged with R-22 refrigerant
and is tested and factory sealed.
NOTE: Adjustment of the refrigerant charge is not required
unless the unit is suspected of not having the proper R-22 charge.
17
Page 18
Table 4B—Wet Coil Air Delivery
Unit 50JX 024-060 (Deduct 10% for 208v)*
UNITMOTOR SPEED
Low
024
30
36
42
48
60
* Air delivery valuesare basedon operating voltage of 230 v or 460 v,wet coil, without filter or electric heater. Deduct filter and electricheater pressure drops to obtain
static pressure available for ducting.
NOTES:
1. Do not operate the unit at a cooling airflow that is less than 350 cfm for each 12,000 Btuh of rated cooling capacity. Evaporator coil frosting may occur at airflows below
this point.
2. Dashes indicate portions of table that are beyond the blower motor capacity or are not recommended.
3. Deduct 10% for 208v.
Med
High
Low
Med
High
Low
Med
High
Low
Med
High
Low
Med
High
Low
Med
High
Watts275273271270-------
Cfm923844754669-------
Watts---359353350347341---
Cfm---941876814737622---
Watts------447439431423-
Cfm------968869765659-
Watts276276272--------
Cfm963929781--------
Watts375377371362354350-----
Cfm120211701079976884807-----
Watts----469449435428---
Cfm----1174988828718---
Watts462451431411394381-----
Cfm13741290120511161020916-----
Watts523506490471449426-----
Cfm15001408130111901082977-----
Watts-645628610595584575----
Cfm-14741369126711691069962----
Watts620600586574562548530510487462439
Cfm16621621158115401496144713921331126311861103
Watts----686661634606577547517
Cfm----1722166215941515142713301227
Watts-------757730704682
Cfm-------1669157714861402
Watts620600586574562548530-487--
Cfm166216211581154014961447139213311263--
Watts763747729709686661634606577547517
Cfm19171868182217741722166215941515142713301227
Watts---852832809784757730704682
Cfm---19821914183917571669157714861402
Watts597592578526460452445----
Cfm2265219021012033197418691614----
Watts754730707687671658646630603558486
Cfm23832282220221342070200519351858177116671576
Watts901876856836813785755723696681687
Cfm24802383230122332175212220661998191017881619
0.00.10.20.30.40.50.60.70.80.91.0
EXTERNAL STATIC PRESSURE (IN. WG)
The charging label and the tables shown refer to system temperatures and pressures in cooling mode only. A refrigerant charging
label is attached to the outside of the service access door. If charge
level is suspect in Heating mode, reclaim all refrigerant and charge
to nameplate amount. (This information may be obtained from the
physical data table also.)
IMPORTANT: When evaluating the refrigerant charge, an indicated adjustment to the specified factory charge must always be
very minimal. If a substantial adjustment is indicated, an abnormal
condition exists somewhere in the cooling system, such as insufficient airflow across either coil or both coils.
REFRIGERANT CHARGE — The amount of refrigerant charge
is listed on the unit nameplate and /or the physical data table. Refer
to the Refrigeration Service Techniques Manual, Refrigerants
Section.
NO CHARGE — Check for leak. Use standard evacuating techniques. After evacuating system, weigh in the specified amount of
refrigerant (refer to system data plate).
LOW CHARGE COOLING — Use Cooling Charging Charts
(Figs. 23-35). Vary refrigerant until the conditions of the chart are
met. Note that charging charts are different from type normally
used. Charts are based on charging the units to correct superheat
for the various operating conditions. Accurate pressure gage and
temperature sensing devices are required. Connect the pressure
gage to the service port on the suction line. Mount the temperature
sensing device on the suction line and insulate it so that the
outdoor ambient does not effect the reading. Indoor air CFM must
be within the normal operating range of the unit.
TO USE COOLING CHARGING CHARTS — Take the outdoor
ambient temperature and read the suction pressure gage. Refer to
the chart to determine what the suction temperature should be.
NOTE: If the problem causing the inaccurate readings is a
refrigerant leak, refer to Check for Refrigerant Leaks section.
18
Page 19
689
100
620
90
551
80
483
70
414
60
SUCTION LINE PRESSURE (PSIG)
345
50
SUCTION LINE PRESSURE (KILOPASCALS)
276
40
(018) 60HZ CHARGING CHART
OUTDOOR TEMP
° F° C
125 52
115 46
105 41
95 35
85 29
75 24
65 18
55 13
457
758
110
689
100
620
90
551
80
483
70
SUCTION LINE PRESSURE (PSIG)
414
60
SUCTION LINE PRESSURE (KILOPASCALS)
345
50
(024) 60HZ CHARGING CHART
OUTDOOR TEMP
° F° C
125 52
115 46
105 41
95 35
85 29
75 24
65 18
55 13
457
207
30
20.030.040.050.060.070.080.0
SUCTION LINE TEMPERATURE (°F)
-7-1410162127
SUCTION LINE TEMPERATURE (°C)
50JS500087
C00026
Fig. 23—Cooling Charging Chart, 50JS 018 Units
OUTDOOR TEMP
° F° C
125 52
115 46
105 41
95 35
85 29
75 24
65 18
55 13
457
50JS500089
C00028
689
100
620
90
551
80
483
70
414
60
SUCTION LINE PRESSURE (PSIG)
345
50
SUCTION LINE PRESSURE (KILOPASCALS)
276
40
207
30
20.030.040.050.060.070.080.0
SUCTION LINE TEMPERATURE (°F)
-7-1410162127
SUCTION LINE TEMPERATURE (°C)
(030) 60HZ CHARGING CHART
Fig. 25—Cooling Charging Chart, 50JS030 Units
276
40
20.030.040.050.060.070.080.0
SUCTION LINE TEMPERATURE (°F)
-7-1410162127
SUCTION LINE TEMPERATURE (°C)
50JS500088
C00027
Fig. 24—Cooling Charging Chart, 50JS 024 Units
OUTDOOR TEMP
° F° C
125 52
115 46
105 41
95 35
85 29
75 24
65 18
55 13
457
50JS500090
C00029
689
100
620
90
551
80
483
70
414
60
SUCTION LINE PRESSURE (PSIG)
345
50
SUCTION LINE PRESSURE (KILOPASCALS)
276
40
207
30
20.030.040.050.060.070.080.0
SUCTION LINE TEMPERATURE (°F)
-7-1410162127
SUCTION LINE TEMPERATURE (°C)
(036) 60HZ CHARGING CHART
Fig. 26—Cooling Charging Chart, 50JS 036 Units
INDOOR AIRFLOW AND AIRFLOW ADJUSTMENTS
For heating and cooling operation, the recommended airflow
is 350 to 450 cfm for each 12,000 Btuh of rated cooling
capacity. for units withoptional electricheat, theairflow must
not be reduced below the levels stated in Tables 2A and 2B.
Tables 4A and 4B shows both heating and cooling airflows at
various external static pressures. Refer to these tables to determine
the airflow for the system being installed.
NOTE: Be sure that all supply-and return-air grilles are open, free
from obstructions, and adjusted properly.
Airflow can be changed by changing the lead connection of the
blower motor.
Unit 50JS and JX three-speed motors (except sizes JS 018 and JX
030) are factory wired for low speed operation. Unit 50JX 030 is
factory wired for medium speed. Unit 50JS 018 has a two-speed
motor wired for low speed.
For 208/230-v Motors:—The motor leads are color-coded as
follows:
3-SPEED
Black = high speed
Blue = medium speed
Red = low speed
19
Page 20
OUTDOOR TEMP
° F° C
125 52
115 46
105 41
95 35
85 29
75 24
65 18
55 13
457
50JS500091
689
100
620
90
551
80
483
70
414
60
SUCTION LINE PRESSURE (PSIG)
345
50
SUCTION LINE PRESSURE (KILOPASCALS)
276
40
207
30
20.030.040.050.060.070.080.0
SUCTION LINE TEMPERATURE (°F)
-7-1410162127
SUCTION LINE TEMPERATURE (°C)
(042) 60HZ CHARGING CHART
C00030
Fig. 27—Cooling Charging Chart, 50JS 042 Units
OUTDOOR TEMP
° F° C
125 52
115 46
105 41
95 35
85 29
75 24
65 18
55 13
457
50JS500092
689
100
620
90
551
80
483
70
414
60
SUCTION LINE PRESSURE (PSIG)
345
50
SUCTION LINE PRESSURE (KILOPASCALS)
276
40
207
30
20.030.040.050.060.070.080.0
SUCTION LINE TEMPERATURE (°F)
-7-1410162127
SUCTION LINE TEMPERATURE (°C)
(048) 60HZ CHARGING CHART
C00031
Fig. 28—Cooling Charging Chart, 50JS 048 Units
OUTDOOR TEMP
° F° C
125 52
115 46
105 41
95 35
85 29
75 24
65 18
55 13
457
50JS500093
689
100
620
90
551
80
483
70
414
60
SUCTION LINE PRESSURE (PSIG)
345
50
SUCTION LINE PRESSURE (KILOPASCALS)
276
40
207
30
20.030.040.050.060.070.080.0
SUCTION LINE TEMPERATURE (°F)
-7-1410162127
SUCTION LINE TEMPERATURE (°C)
(060) 60HZ CHARGING CHART
C00032
Fig. 29—Cooling Charging Chart, 50JS 060 Units
To change the speed of the blower motor (BM), remove the fan
motor speed leg lead from the blower relay (BR). This wire is
attached to IGC terminal BM for single-phase and 3-phase units.
To change the speed, remove and replace with lead for desired
blower motor speed. Insulate the removed lead to avoid contact
with chassis parts.
For 460-v GE Motors—The motor leads are color coded as
follows:
3-SPEED
Black = high
Violet = jumper
Orange = medium
Red = low
To change the speed of the blower motor (BM), remove fan motor
speed lead from the blower relay (BR) and replace with the lead
for the desired blower motor speed. The motor speed lead is
attached to terminal BM. For low and medium speeds black must
be connected to the jumper wire. Insulate removed lead end to
avoid contact with chassis parts. To select high speed on 460-v GE
motors, separate the black female quick connect (QC) from the
jumper lead male quick connect (QC) and connect the black lead
to the BR. Insulate the jumper to avoid contact with any chassis
parts.
MAINTENANCE
To ensure continuing high performance, and to minimize the
possibility of premature equipment failure, periodic maintenance
must be performed on this equipment. This heat pump unit should
be inspected at least once each year by a qualified service person.
To troubleshoot unit, refer to Table 5.
NOTE TO EQUIPMENT OWNER: Consult your local dealer
about the availability of a maintenance contract.
The ability to properly perform maintenance on this equipment requires certain expertise, mechanical skills, tools and
equipment. If you do not possess these, do not attempt to
perform any maintenance on this equipment, other than those
procedures recommended in the User’s Manual. FAILURE
TO HEED THIS WARNING COULD RESULT IN SERIOUS INJURY OR DEATH AND POSSIBLE DAMAGE TO
THIS EQUIPMENT.
20
Page 21
80.070.060.050.040.030.0
OUTDOOR
TEMP
F C
125 52
115 46
105 41
95 35
85 29
75 24
65 18
55 13
45 7
50JX500219
689 100.0
620
90.0
551
80.0
483
70.0
414
60.0
345
50.0
SUCTION LINE PRESSURE (PSIG)
276
40.0
SUCTION LINE PRESSURE (KILOPASCALS)
207
30.0
20.0
-7272116104-1
(024) 60 Hz CHARGING CHART
SUCTION LINE TEMPERATURE (DEG. F)
SUCTION LINE TEMPERATURE (DEG. C)
C99031
Fig. 30—Cooling Charging Chart, 50JX 024 Units
80.070.060.050.040.030.0
OUTDOOR
TEMP
F C
125 52
115 46
105 41
95 35
85 29
75 24
65 18
55 13
45 7
50JX500221
C99033
689 100.0
620
90.0
551
80.0
483
70.0
414
60.0
345
50.0
SUCTION LINE PRESSURE (PSIG)
276
40.0
SUCTION LINE PRESSURE (KILOPASCALS)
207
30.0
20.0
-7272116104-1
(036) 60 Hz CHARGING CHART
SUCTION LINE TEMPERATURE (DEG. F)
SUCTION LINE TEMPERATURE (DEG. C)
Fig. 32—Cooling Charging Chart, 50JX036 Units
80.070.060.050.040.030.0
OUTDOOR
TEMP
F C
125 52
115 46
105 41
95 35
85 29
75 24
65 18
55 13
45 7
50JX500223
C99035
689 100.0
620
90.0
551
80.0
483
70.0
414
60.0
345
50.0
SUCTION LINE PRESSURE (PSIG)
276
40.0
SUCTION LINE PRESSURE (KILOPASCALS)
207
30.0
20.0
-7272116104-1
(048) 60 Hz CHARGING CHART
SUCTION LINE TEMPERATURE (DEG. F)
SUCTION LINE TEMPERATURE (DEG. C)
Fig. 34—Cooling Charging Chart, 50JX 048 Units
689 100.0
620
90.0
551
80.0
483
70.0
414
60.0
345
50.0
SUCTION LINE PRESSURE (PSIG)
276
40.0
SUCTION LINE PRESSURE (KILOPASCALS)
207
30.0
20.0
-7272116104-1
(030) 60 Hz CHARGING CHART
SUCTION LINE TEMPERATURE (DEG. F)
SUCTION LINE TEMPERATURE (DEG. C)
115 46
95 35
75 24
55 13
80.070.060.050.040.030.0
OUTDOOR
TEMP
F C
125 52
105 41
85 29
65 18
45 7
50JX500220
C99032
Fig. 31—Cooling Charging Chart, 50JX 030 Units
689 100.0
620
90.0
551
80.0
483
70.0
414
60.0
345
50.0
SUCTION LINE PRESSURE (PSIG)
276
40.0
SUCTION LINE PRESSURE (KILOPASCALS)
207
30.0
20.0
-7272116104-1
(042) 60 Hz CHARGING CHART
SUCTION LINE TEMPERATURE (DEG. F)
SUCTION LINE TEMPERATURE (DEG. C)
115 46
95 35
75 24
55 13
80.070.060.050.040.030.0
OUTDOOR
TEMP
F C
125 52
105 41
85 29
65 18
45 7
50JX500222
C99034
Fig. 33—Cooling Charging Chart, 50JX 042 Units
115 46
95 35
75 24
55 13
80.070.060.050.040.030.0
OUTDOOR
TEMP
F C
125 52
105 41
85 29
65 18
45 7
50JX500224
C99036
689 100.0
620
90.0
551
80.0
483
70.0
414
60.0
345
50.0
SUCTION LINE PRESSURE (PSIG)
276
40.0
SUCTION LINE PRESSURE (KILOPASCALS)
207
30.0
20.0
-7272116104-1
(060) 60 Hz CHARGING CHART
SUCTION LINE TEMPERATURE (DEG. F)
SUCTION LINE TEMPERATURE (DEG. C)
Fig. 35—Cooling Charging Chart,50JX 060 Units
21
Page 22
Failure to follow these warnings could result in serious injury
or death:
1. Turn off electrical power to the unit before performing any
maintenance or service on this unit.
2. Use extreme caution when removing panels and parts. As
with any mechanical equipment, personal injury can result
from sharp edges.
3. Never place anything combustible either on, or in contact
with, the unit.
Errors made when reconnecting wires may cause improper
and dangerous operation. Label all wires prior to disconnection when servicing.
The minimum maintenance requirements for this equipment are as
follows:
1. Inspect air filter(s) each month. Clean or replace when
necessary.
2. Inspect indoor coil, drain pan, and condensate drain each
cooling season for cleanliness. Clean when necessary.
3. Inspect blower motor and wheel for cleanliness each cooling
season. Clean when necessary.
4. Check electrical connections for tightness and controls for
proper operation each cooling season. Service when necessary.
AIR FILTER
IMPORTANT: Never operate the unit without a suitable air filter
in the return-air duct system. Always replace the filter with the
same dimensional size and type as originally installed (See Tables
1A and 1B for recommended filter sizes).
Inspect air filter(s) at least once each month and replace
(throwaway-type) or clean (cleanable-type) at least twice during
each cooling season or whenever the filters become clogged with
dust and lint.
INDOOR BLOWER AND MOTOR
NOTE: All motors are prelubricated. Do not attempt to lubricate
these motors.
For longer life, operating economy, and continuing efficiency,
clean accumulated dirt and grease from the blower wheel and
motor annually.
Disconnect and tag electrical power to the unit before
cleaning and lubricating the blower motor and wheel. Failure
to adhere to thiswarning could cause personal injury or death.
results, spray condenser coil fins from inside to outside the unit.
On units with an outer and inner condenser coil, be sure to clean
between the coils. Be sure to flush all dirt and debris from the unit
base.
Inspect the drain pan and condensate drain line when inspecting
the coils. Clean thedrain pan and condensate drain by removing all
foreign matter from the pan. Flush the pan and drain trough with
clear water. Do not splash water on the insulation, motor, wiring,
or air filter(s). If the drain trough is restricted, clear it with a
‘‘plumbers snake’’ or similar probe device. Ensure that the
auxiliary drain port above the drain trough is also clear.
OUTDOOR FAN
Keep the condenser fan free from all obstructions to ensure
proper cooling operation. Never place articles on top of the
unit. Damage to unit may result.
1. Inspect the fan blades for cracks or bends.
2. If fan needs to be removed, remove screws holding outdoor air
intake grille and remove grille.
3. Loosen the setscrew and slide the fan off the motor shaft.
4. When replacing fan blade,position blade so that the hub is1/8
in. away from the motor end (1/8 in. of motor shaft will be
visible) (See Fig. 20).
5. Ensure that setscrew engages the flat area on the motor shaft
when tightening.
6. Replace grille.
ELECTRICAL CONTROLS AND WIRING — Inspect and check
the electrical controls and wiring annually. Be sure to turn off the
electrical power to the unit.
Remove access panel to locate all the electrical controls and
wiring. Check all electrical connections for tightness. Tighten all
screw connections. If any smoky or burned connections are
noticed, disassemble the connection, clean all the parts, restrip the
wire end and reassemble the connection properly and securely.
After inspecting the electrical controls and wiring, replace all the
panels. Start the unit, and observe at least one complete cooling
cycle to ensure proper operation. If discrepancies are observed in
operating cycle, or if a suspected malfunction has occurred, check
each electrical component with the proper electrical instrumentation. Refer to the unit wiring label when making these checkouts.
NOTE: Refer to the Sequence of Operation section as an aid in
determining proper control operation.
REFRIGERANT CIRCUIT — Inspect all refrigerant tubing connections and the unit base for oil accumulation annually. Detecting
oil generally indicates a refrigerant leak.
OUTDOOR COIL, INDOOR COIL, AND CONDENSATE
DRAIN PAN — Inspect the condenser coil, evaporator coil, and
condensate drain pan at least once each year.
The coils are easily cleaned when dry; therefore, inspect and clean
the coils either before or after each cooling season. Remove all
obstructions, including weeds and shrubs, that interfere with the
airflow through the condenser coil.
Straighten bent fins with a fin comb. If coated with dirt or lint,
clean the coils with a vacuum cleaner, using the soft brush
attachment. Be careful not to bend the fins. If coated with oil or
grease, clean the coils with a mild detergent-and-water solution.
Rinse coils with clear water, using a garden hose. Be careful not to
splash water on motors, insulation, wiring, or air filter(s). For best
System under pressure. Relieve pressure and recover all
refrigerant before system repair or final unit disposal to avoid
personal injury or death. Use all service ports and open all
flow-control devices, including solenoid valves.
If oil is detected or if low performance is suspected, leak-test all
refrigerant tubing using an electronic leak detector, or liquid-soap
solution. If a refrigerant leak is detected, refer to Check for
Refrigerant Leaks section.
If no refrigerant leaks are found and low performance is suspected,
refer to Checking and Adjusting Refrigerant Charge section.
INDOOR AIRFLOW — The indoor airflow does not require
checking unless improper performance is suspected. If a problem
22
Page 23
C99097
Fig. 36—Refrigerant Circuit
exists, be sure that all supply- and return-air grilles are open and
free from obstructions, and that the air filter is clean. When
necessary, refer to Indoor Airflow and Airflow Adjustments
section to check the system airflow.
METERING DEVICES — Refrigerant metering devices are fixed
orifices and are located in the inlet header to the indoor and
outdoor coils.
LIQUID LINE STRAINERS — The liquid line strainers (to protect metering devices) aremade ofwire meshand arelocated in the
liquid lines on the inlet side of the metering devices.
SYSTEM INFORMATION
TIME-DELAY RELAY — The Time-Delay Relay (TDR) is a
solid-state control, recycle delay timer which keeps indoor blower
operating for 60 sec. after thermostat is satisfied. This delay
enables blower to remove residual cooling in coil after compression shutdown, thereby improving efficiency of system. The
sequence of operation is that on closure of wall thermostat and at
end of a fixed on delay of 1 sec., fan relay is energized. When
thermostat is satisfied, an off delay is initiated. When fixed delay
of 60 ± 5 sec. is completed, fan relay is de-energized and fan motor
stops. If wall thermostat closes during this delay, TDR is reset and
fan relay remains energized. TDR is a 24-v device that operates
within a range of 15v to 30v and draws about 0.5 amps. If the
blower runs continuously instead of cycling off when the fan
switch is seton AUTO, the TDR isprobably defective and must be
replaced.
LOSS OF CHARGE SWITCH — The loss of charge switch is a
protective device wired into control circuit (low voltage). It shuts
off the compressor if abnormally low pressures are present in the
refrigeration circuit.
NOTE: Because these switches are attached to refrigeration
system under pressure, it is not advisable to remove this device for
troubleshooting unless you are reasonably certain that a problem
exists. If switch must be removed, remove and recover all system
charge so that pressure gages read 0 psi. Never open system
without breaking vacuum with dry nitrogen.
CHECK DEFROST THERMOSTAT — There is a liquid header
with a brass distributor and feeder tube going into outdoor coil. At
the end of 1 of the feeder tubes, there is a 3/8-in. OD stub tube
approximately 3 in. long. (See Fig. 37.) The defrost thermostat
should be located on stub tube. Note that there is only 1 stub tube
used with liquid header, and on most units it is the bottom circuit.
pump that conditions are right for defrost or that conditions have
changed to terminate defrost. It is a thermally actuated switch
clamped to outdoor coil to sense its temperature. Normal temperature range is closed at 30˚ +/- 3˚F and open at 80˚ +/- 5˚F.
NOTE: The defrost thermostat must be located on the liquid side
of the outdoor coil on the bottom circuit and as close to the coil as
possible.
23
Page 24
Table 5—Cooling and Heating Troubleshooting Chart
SYMPTOMCAUSEREMEDY
Compressor and outdoor fan will not start
Compressor will not start but condenser fan
runs
Three-phase scroll compressor (size 030060units) makes excessive noise, and there
may be a low pressure differential
Compressor cycles (other than normally satisfying thermostat)
Compressor operates continuously
Excessive head pressure
Head pressure too low
Excessive suction pressure
Power failureCall power company
Fuse blown or circuit breaker trippedReplace fuse or reset circuit breaker
Defective thermostat, contactor, transformer, con-
trol relay or defrost board
Insufficient line voltageDetermine cause and correct
Incorrect or faulty wiringCheck wiring diagram and rewire correctly
Thermostat setting too high
Units have a 5-min. time delay
Faulty wiring or loose connections in compressor
circuit
Compressor motor burned out, seized, or internal
overload open
Defective run capacitor, overload, or PTC (positive temperature coefficient) thermistor
One leg of 3-phase power dead
Low input voltage (20% low)Determine cause and correct
Scroll compressor is rotating in the wrong direc-
tion
Refrigerant overcharge or undercharge
Defective compressorReplace and determine cause
Insufficient line voltageDetermine cause and correct
Blocked outdoor coilDetermine cause and correct
Defective run/start capacitor, overload or start
relay
Defective thermostatReplace thermostat
Faulty outdoor-fan motor or capacitorReplace
Damaged reversing valveDetermine cause and correct
Restriction in refrigerant systemLocate restriction and remove
Dirty air filterReplace filter
Unit undersized for loadDecrease load or increase unit size
Thermostat set too lowReset thermostat
Low refrigerant chargeLocate leak, repair, and recharge
Leaking valves in compressorReplace compressor
Frosted coil with incorrect defrost operation
Air in system
Outdoor coil dirty or restrictedClean coil or remove restriction
Dirty air filterReplace filter
Dirty indoor or outdoor coilClean coil
Refrigerant overchargedRecover excess refrigerant
Air in system
(Heat) Indoor air restricted or recirculatingDetermine cause and correct
Indoor or outdoor air restricted or air short-cyclingDetermine cause and correct
Low refrigerant chargeCheck for leaks, repair and recharge
Compressor valves leakingReplace compressor
Restriction in liquid tubeRemove restriction
(Heat) Outdoor coil frosted
(Cool) High Heat loadCheck for source and eliminate
Compressor valves leakingReplace compressor
Reversing valve hung up or leaking internallyReplace valve
Refrigerant overchargedRecover excess refrigerant
Replace component
Lower thermostat setting below room temperature
DO NOT bypass this compressor time
delay—wait for 5 min. until time-delay relay is
deenergized
Check wiring and repair or replace
Determine cause
Replace compressor
Determine cause and replace
Replace fuse or reset circuit breaker
Determine cause
Correct the direction of rotation by reversing the
3-phase power leads to the unit
Recover refrigerant, evacuate system, and recharge to capacities shown on nameplate
Determine cause and replace
Check defrost time settings
Reset as necessary
Check defrost temperature switch
Replace as necessary
Recover refrigerant, evacuate system, and recharge
Recover refrigerant, evacuate system, and recharge
Move timer on control board to 30 min. between
defrost cycles
24
Page 25
Cooling and Heating Troubleshooting Chart (cont’d)
SYMPTOMCAUSEREMEDY
Suction pressure too low(Cool) Dirty air filterReplace filter
(Heat) Outdoor coil frosted
Low refrigerant chargeCheck for leaks, repair and recharge
Metering device or low side restrictedRemove source of restriction
(Cool) Insufficient coil airflow
(Cool) Temperature too low in conditioned areaReset thermostat
Compressor runs but outdoor fan does not
IFM does not runBlower wheel not secured to shaftProperly tighten blower wheel to shaft
IFM runs when it should be off
IFM operation is intermittent
IFM—Indoor Fan Motor
NC (normally closed) contacts on defrost board
open
Insufficient voltage at motorDetermine cause and correct
Power connectors not properly sealedConnectors should snap easily; do not force
Motor programmed with a delay profileAllow a few min. for motor to shut off
With thermostat in off state, the voltage on G,
Y1,Y, Y2, W with respect to common, should be
1/2 of actual low voltage supply
Water dripping into motorVerify proper drip loops in connector wires
Connectors not firmly sealed
START-UP CHECKLIST
(REMOVE AND STORE IN JOB FILE)
I. PRELIMINARY INFORMATION
Model No...............................................................................................................................................................................................................
Serial No................................................................................................................................................................................................................
___ Verify that all packing materials have been removed from unit
___ Remove all shipping holddown bolts and brackets per installation instructions
___ Verify that condensate connection is installed per installation instructions
___ Check all electrical connections and terminals for tightness
___ Check that indoor (evaporator) air filter is clean and in place
___ Verify that unit installation is level
___ Check fan wheel and propeller for location in housing and setscrew tightness