CONTROLS AND FUNCTIONS
Marquee Display Usage
Clearing Unit Alarms
Service Test
OPERATION
Unit Control Type (U.CTL)
Occupancy Determination
Indoor Fan
Outdoor Fans
Economizer
Indoor Air Quality (IAQ)
Power Exhaust
Compressor Staging
Heating (48HG Units)
• THERMOSTAT CONTROL
• SPACE SENSOR CONTROL
Heating (50HG Units)
• THERMOSTAT CONTROL
• SPACE SENSOR CONTROL
Cooling
• THERMOSTAT CONTROL
• SPACE SENSOR CONTROL
Space Temperature Sensor Calibration
and Trim
Alarm Handling
TROUBLESHOOTING
Complete Unit Stoppage
Single Circuit Stoppage
Service Analysis
Restart Procedure
Alarms and Alerts
Installation and servicing of air-conditioning equipment can
be hazardous due to system pressure and electrical components. Only trained and qualified service personnel should
install, repair, or service air-conditioning equipment. Untrained
personnel can perform the basic maintenance functions of
replacing filters. All other operations should be performed by
trained service personnel. When working on air-conditioning
equipment, observe precautions in the literature, tags and labels
attached to the unit, and other safety precautions that may
apply. Follow all safety codes. Wear safety glas ses and work
gloves. Use quenching cloth for unbrazing operations. Have
fire extinguishers available for all brazing operations.
GENERAL
This publication contains Start-Up, Controls, Operation,
and Troubleshooting information for the 48/50HG rooftop
units. See Table 1. These units are equipped with ComfortLink
controls.
Table 1 — Unit Sizes (48/50HG)
UNIT MODELNOMINAL TONS
48/50HG014
48/50HG016
48/50HG020
48/50HG024
48/50HG028
MAJOR SYSTEM COMPONENTS
General —
electric cooling and with gas heating (48HG units) or electric
cooling and electric heating (50HG Units) contain the
ComfortLink electronic control system that monitors all operations of the rooftop. The control system is composed of several
components as listed in sections below. See Fig. 1-3 for the
control and power schematics. Figure 4 shows the layout of the
control box, unit, and thermistor and transducer locations.
Main Base Board (MBB) —
the center of the ComfortLink control system. It contains t he
major portion of the operating software and controls the operation of the unit. The MBB continuously monitors input/output
channel information received from its inputs and from the
Economizer Control Board (ECB). The MBB receives inputs
The 48/50HG single package rooftop units with
See Fig. 5. The MBB is
Page
. . . . . . . . . .CL-1, CL-2
1
/
12
2
15
18
20
25
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1144
Tab 1a1b6a6b
PC 111Catalog No. 534-80090Printed in U.S.A.Form 48/50HG-2TPg 120210-01Replaces: 48/50HG-1T
Page 2
from thermistors T1 through T5 and transducers T6 through
T8. See Table 2. The MBB also receives the Current Sensor
inputs for compressors A1, B1 and C1 and other discrete or
digital inputs. See Table 3. The MBB reads space temperature
(SPT) from either a T55, T56 or T58 device and space temperature offset (SPTO) from a T56 device. See Table 4 and FieldInstalled Accessories section below. The MBB controls 11 relays. See Table 5.
Economizer Control Board (ECB) —
trols the economizer actuator. See Fig. 6. Relay 6 on the ECB
supplies 24 VAC to the actuator. The control signal from the
ECB uses the Belimo communication protocol. The ECB has
inputs for Indoor Air Quality (IAQ), Outdoor Air Quality
(OAQ), and enthalpy. See Table 4. It also controls two power
exhaust motors (PE1 and PE2). See Table 5.
By communicating with the ECB, the e conomizer actuator
is able to provide the damper position and diagnostic information to the ComfortLink controller. The damper position is displayed as EC.AP under Outputs/Econ on the Scrolling Marquee. Diagnostic information is displayed via Alert T414.
More information about these alarms is contained in the
Alarms and Alerts section.
Scrolling Marquee Display —
pad interface used to access rooftop information, read sensor
values, and test the unit. See Fig. 7. The marquee display is a
4-key, 4-character, 16-segment LED (light-emitting diode)
display. Eleven mode LED s are located on the display as well
as an Alarm Status LED. See Marquee Di splay Usage se ction
on page 11 for further details.
Board Addresses —
a 3-position instance jumper that is set at the factory to “1.”
Do not change this setting. The ECB has a 4-position DIP
switch. Each DIP switch is s et to “0” at the factory. Do not
change this setting.
The Main Base Board (MBB) has
The ECB con-
This device is the key-
Control Module Communication
RED LE D — Proper operation of the control boards can be
visually checked by looking at the red status LEDs. When
operating correctly, the red status LEDs should blink in unison
at a rate of once every 2 seconds. If the red LEDs are not blinking in unison, verify that correct power is being supplied to all
modules. Also, be sure that the Main Base Board is supplied
with the current software. If necessary, reload current software.
If the problem still persists, replace the MBB. A board LED
that is lit continuously or blinking at a rate of once per second
or faster indicates that the board should be replaced.
GREE N LED — The MBB has one green LED. The Local
Equipment Network (LEN) LED should always be blinking
whenever power is on. All other boards have a LEN LED that
will blink whenever power is on. If LE N LED is not blinking,
check LEN connections for potential communication errors
(J3 and J4 connectors). Communication between modules is
accomplished by a 3-wire sensor bus. These 3 wires run in
parallel from module to module. The J4 connector on the MBB
provides both power and communication directly to the
marquee display.
YELLOW LED — The MBB has one yellow LED. The
Carrier Comfort Network (CCN) LED will blink during times
of network communication.
Carrier Comfort Network Interface —
units can be connected to the CCN if desired. The communication bus wiring is a shielded, 3-conductor cable with drain wire
and is field supplied and installed. See T able 6 for wiring information. The system elements are connected to the communication bus in a daisy chain arrangement. The positive pin of each
The 48/50HG
system element communication connector must be wired to the
positive pins of the system elements on either side of it. This is
also required for the negative and signal ground pins of each
system element. Wiring connections for CCN should be made
at TB2. See Fig. 1 and 2. Consult the CCN Contractor's Manual for further information.
NOTE: Conductors and drain wire must be 20-AWG (American Wire Gage) minimum stranded, tinned copper. Individual
conductors must be insulated with PVC, PVC/nylon, vinyl,
Teflon, or polyethylene. An aluminum/polyester 100% foil
shield and an outer jacket of PVC, PVC/nylon, chrome vinyl,
or Teflon with a minimum operating temperature range of
–20 C to 60 C is required. See Table 6.
It is important when connecting to a CCN communication
bus that a color-coding scheme be used for the entire network
to simplify the installation. It is recommended that red be used
for the signal positive, black for the signal negative and white
for the signal ground. Use a similar scheme for cables containing different colored wires.
At each system element, the shields of its communic ation
bus cables must be tied together. If the communication bus is
entirely within one building, the resulting continuous shield
must be connected to a ground at one point only. If the communication bus cable exits from one building and enters another,
the shields must be connected to grounds at the lightning
suppressor in each building where the cable enters or exits the
building (one point per building only). To connect the unit to
the network:
1. Turn off power to the control box.
2. Cut the CCN wire and strip the ends of the red (+), white
(ground), and black (–) conductors. (Substitute appropriate colors for different colored cables.)
3. Connect the red wire to (+) terminal on TB2 of the plug,
the white wire to COM terminal, and the black wire to the
(–) terminal.
4. The RJ14 CCN connector on TB2 can also be used, but is
only intended for temporary connection (for example, a
laptop computer running Service Tool).
5. Restore power to unit.
IMPORTANT: A shorted CCN bus cable will prevent
some routines from running and may prevent the unit
from starting. If abnormal conditions occur, unplug the
connector. If conditions return to normal, check the
CCN connector and cable. Run new cable if necessary.
A short in one section of the bus can cause probl ems
with all sys tem elem en ts on th e bu s.
Field-Installed Accessories
SPACE TEMPERATURE SENSOR (T55) — The T55 Space
Temperature Sensor (Part No. CEC0121448-01) is a fieldinstalled accessory. The sensor is installed on a building interior wall to measure room air temperature. T he T55 sensor a lso
includes an override button on the front cover to permit occupants to override the Unoccupied Schedule (if programmed).
The jumper wire in the inst aller’s packet must be connected
between R and W1 when using a T55 device. See Fig. 8-10.
SPACE TEMPERATURE SENSOR (T56) — The T56 Space
Temperature Sensor (Part No. CEC0121503-01) is a fieldinstalled accessory. This sensor includes a sliding scale on the
front cover that permits an occupant to adjust the space temperature set point remotely. The jumper wire in the installer’s
packet must be connected between R and W1 when using a
T56 device. See Fig. 8, 9, and 11.
2
Page 3
Fig. 1 — Low Voltage Control Schematic — 48HG Units
3
Page 4
Fig. 2 — Low Voltage Control Schematic — 50HG Units
4
Page 5
Fig. 3 — Typical Power Schematic
5
Page 6
THERMOSTAT/IGC MARKINGS
NOTES:
1. Factory wiring is in accordance with the National Electrical
Te r m i na l B l oc k
TB—
Codes. Any field modifications or additions must be in com-
pliance with all applicable codes.
2. Use 75° C min wire for field power supply. Use copper wires
Blower Motor
Common
Inducer Motor
BM —
C—
CM —
Transformer
Room Temp Device
Room Temp Device with Set
TRAN —
T- 55—
T- 56—
for all units.
3. All circuit breakers Must Trip Amps are equal to or less than
Centrifugal Switch
Fan
Indoor Fan On
CS —
G—
IFO —
Point Adjustment
Te r m i na l B l oc k
156% RLA.
phase motors protected against primar y single-phase
4. Compressor and fan motors are thermally protected. Three-
Line 1
Thermostat Power
Power Supply
L1 —
R—
RT —
Terminal (Unmarked)
conditions.
5. Red jumper wire must be added between R and W1 for
Speed Sensor
Thermostat Heat
SS —
W—
Terminal (Marked)
Splice
Space Temperature mode and temporarily during Service-
Test mode when the heaters need to operate.
1st Stage of Heating
2nd Stage of Heating
W1 —
W2 —
Factory Wiring
Alarm Output
1st Stage of Cooling
2nd Stage of Cooling
X—
Y1 —
Y2 —
Field Wiring
To indicate common potential
only, not to represent wiring.
To indicate FIOP or Accessory
Fig. 4 — Typical Component Arrangement
Induced-Draft Motor
Indoor-Fan Contactor
Indoor-Fan Circuit Breaker
Indoor-Fan Motor
Integrated Gas Controller
Local Equipment Network
Limit Switch
Main Base Board
Outdoor-Air Quality
Outdoor-Air Temperature
Outdoor-Fan Contactor
Outdoor-Fan Motor
Power Exhaust Contactor
Power Exhaust Motor
Plug
Quick Connect
Quadruple Terminal
Rollout Switch
Supply-Air Temperature
Saturated Condensing Temp
QC —
QT —
RS —
Fuse
Ground
Gas Valve
FU—
GND —
GV—
Saturated Suction Pressure
SAT —
SCT —
SSP —
High-Pressure Switch
Ignitor
Indoor-Air Quality
HPS —
I—
IAQ—
LEGEND FOR FIG. 1 TO 4
IDM —
IFC —
IFCB —
IFM —
IGC —
LEN —
LS—
MBB —
OAQ —
OAT —
OFC —
OFM —
PEC —
PEM —
PL—
Circuit A
Auxiliary Contact
Circuit B
Circuit C
Compressor, Contactor
Capacitor
Circuit Breaker
Carrier Comfort Network
Crankcase Heater
Compressor
Current Sensor
Enthalpy Control
Economizer Control Board
Factory-Installed Option
Flame Sensor
---.A —
AUX —
---.B —
---.C —
C—
CAP —
CB—
CCN —
CCH —
COMP —
CS—
EC—
ECB —
FIOP —
FS—
6
Page 7
RED LED - STATUSGREEN LED -
LEN (LOCAL EQUIPMENT NETWORK)
CEPL130346-01
YELLOW LED CCN (CARRIER COMFORT NETWORK)
INSTANCE JUMPER
J1
J4
J6
SENSOR
OAT
(T1)
SAT
(T2)
SCT_A
(T3)
SCT_B
(T4)
SCT_C
(T5)
SSP_A
(T6)
SSP_B
(T7)
SSP_C
(T8)
J2
J3
LEN
STATUS
CCN
J5
J7
J8
Fig. 5 — Main Base Board
Table 2 — Thermistor and Transducer Designations
PIN
CONNECTION
POINT
J8 — 5,6 (MBB)Outside Air Temperature (OAT) — Attached to the economizer support
J8 — 7,8 (MBB)Supply Air Temperature (SAT) — Inserted into the heat section under-
J8 — 9,10 (MBB)Saturated Condensing Temperature for Cir. A (SCT_A) — Circuit A
J8 — 11,12 (MBB)Saturated Condensing Temperature for Cir. B (SCT_B) — Circuit B
J8 — 13,14 (MBB)Saturated Condensing Temperature for Cir. C (SCT_C) — Circuit C
J8 — 18,19,20 (MBB)Saturated Suction Pressure for Cir. A (SSP_A) — Suction line of Circuit A
J8 — 21,22,23 (MBB)Saturated Suction Pressure for Cir. B (SSP_B) — Suction line of Circuit B
J8 — 24,25,26 (MBB)Saturated Suction Pressure for Cir. C (SSP_C) — Suction line of Circuit C
bracket, behind the control box, inside the outside air duct of the
economizer.
J10 — 11 (MBB)First compressor of Circuit A
J10 — 9 (MBB)First compressor of Circuit B
J10 — 6 (MBB)First compressor of Circuit C
J10 — 21 (MBB)Request for indoor fan. IGC controls the Indoor Fan Motor (48HG only)
J10 — 3 (MBB)Allows indoor fan to operate
J10 — 19 (MBB)Controls outdoor fan motor 1
J10 — 16 (MBB)Controls outdoor fan motor 3 and 6 (also 2 and 5 on size 028 units)
J10 — 13 (MBB)Controls outdoor fan motor 4
J10 — 27 (MBB)Request for first stage of heating. IGC controls heating (48HG only).
J10 — 25 (MBB)Second stage of heating.
J10 — 23 (MBB)TB4 — 7,8
J8 — 18 (ECB)ECB can turn off the power to the actuator
J7 — 1, 3 (ECB)Belimo Communication Protocol
J8 — 3 (ECB)Power Exhaust Motor No. 1
J8 — 6 (ECB)Power Exhaust Motor No. 2
ECB —
IFC—
IGC —
MBB —
OFC —
Economizer Control Board
Indoor-Fan Contactor
Integrated Gas Controller
Main Base Board
Outdoor-Fan Contactor
Table 6 — CCN Communication Bus Wiring
LEGEND
MANUFACTURERPART NO.
Alpha
American
Belden
Columbia
2413 or 5463
A22503
8772
02525
MODE
Run Status
Service Test
Temperature
Pressures
Setpoints
Inputs
Outputs
Configuration
Time Clock
Operating Modes
Alarms
Alarm Status
ESCAPE
ENTER
9
Page 10
SW1
2
3
SEN
45
61
RED(+)
WHT(GND)
BLK(-)
CCN COM
Cool
Warm
Fig. 8 — Space Temperature Sensor
(P/N CEC0121503-01 Shown)
BLK (GND)
RED (SPT)
SENSOR WIRING
Fig. 10 — T55 Space Temperature Sensor Wiring
(P/N CEC0121448-01)
2
3
45
61
RED(+)
WHT(GND)
BLK(-)
CCN COM
NOTE: Dimensions are in inches.
Fig. 9 — Space Temperature Sensor Mounting
SET
SEN
SW1
WHT
(T56)
BLK (GND)
RED (SPT)
CoolWarm
Fig. 11 — T56 Space Temperature Sensor Wiring
(P/N CEC0121503-01)
10
SENSOR WIRING
JUMPER
TERMINALS
AS SHOWN
Page 11
SPACE TEMPERATURE SENSOR (T58) — T h e T58 Space
ESCAPE
ENTER
ENTER
ENTER
Temperature Sensor (Part No. CEPL130464-01) is a fieldinstalled accessory. The T58 sensor communicates with the
ComfortLink™ controller, providing space temperature, heating and cooling set points, and mode operation information.
The jumper wire in the installer’s packet must be connected between R and W1 when using a T58 device.
IMPORTANT: A T58 sensor can only be used with unit
running Version 2.0 or higher of the unit software. If a
T58 sensor is installed but will not function with the 48/
50HG unit, check the unit software version with the
ComfortLink controls. The new version of the software
may need to be loaded into the unit controls.
SPACE TEMPERATURE SENSOR CALIBRATION —
The temperature reading of th e space tempe rature sensors can
be calibrated. Refer to the Space Temperature Sensor Calibration and Trim section on page 31 for more information.
ECONOMIZER — The economizer accessory (Part No.
CRECOMZR009A00) is a field-installed accessory. When installing this accessory, the unit must be configured for economizer installation by setting EC.EQ to YES. The default settin gs
for the other economizer configurations should be satisfactory.
If they need to be changed, additional information about these
configuration settings can be found in the Ec onomizer section.
POWER EXHAUST — The power exhaust accessories
(Part No. CRPWREXH018A00, CRPWREXH019A00,
CRPWREXH020A00) are field-installed accessories for
power exhaust for different voltages. When installing this
accessory, the unit must be configured for power exhaust
installation by setting PE.EN to YES. The default settings for
the other power exhaust configurations should be satisfactory.
If they need to be changed, additional information about these
configurations can be found in the Power Exhaust section.
INDOOR AIR QUALITY — The indoor air quality (IAQ)
accessory (Part No. CRCBDIOX001A00) is a field-installed
accessory. This sensor measures CO
return. The defaults for IAQ configurations should be satisfactory; however, if they are not, additional information about
these configurations can be found in the I ndoor Air Quality
section.
SMOKE DETECTOR — The smoke detector accessory
(Part No. CRSMKDET001A00) is a field-installed accessory.
This accessory detects smoke in the return duct. When installing this accessory, set the switch configuration to normally
open or normally closed as wired (FS.SW). Normally closed
(2) is the preferred configuration.
FI LTER STATUS — The filter status accessory (Part No.
CRSTATUS002A00) is a field-installed accessory. This accessory detects plugged filters. When installing this accessory, set the
switch configuration to normally open or normally closed as
wired (FL.SW). Normally open (1) is the preferred configuration.
FAN S TATUS — The fan status accessory (Part
No. CRSTATUS003A00) is a field-installed accessory. This
accessory detects when the indoor fan is blowing air. When installing this accessory, set the switch configuration to normally
open or normally closed as wired (FN.SW). Normally open (1)
is the preferred configuration.
ENTHALPY SENSORS — The enthalpy accessories (Part
No. CRENTSNG001A00 or CRDENTDIF001A00) are f ieldinstalled accessories. The first accessory (outdoor air only)
determines when the enthalpy is low relative to a fixed reference. The second accessory (outdoor and return enthalpy are
measured) compares the enthalpy between the outdoor and
return airstreams. In each case, the enthalpy 4-20mA signals
are converted to a switch output which i s read by the ECB.
When installing this accessory, set the switch configuration to
normally open or normally closed as wired (EN.SW).
Normally open (1) is the preferred configuration.
concentrations in the unit
2
CONTROLS AND FUNCTIONS
Marquee Display Usage —
The display module provides the user interface to the
ComfortLink control system. The display has up and down arrow keys, an key, and an key. These keys
are used to navigate through the different levels of the display
structure. See Table 7. Press the key until the display is blank to move through the top 11 mode levels indicated
by LEDs on the left side of the display.
When a specific item is located, the display will flash showing the operator the item, followed by the item value and then
followed by the item units (if any). Press the key to
stop the display at the item value. Items in the Configuration
and Service Test modes are password protected. The display
will flash PASS and WORD when require d. Use the
and arrow keys to enter the 4 digits of the password. The default password is 1111.
Pressing the and ke ys simultaneously
will scroll a clear language text description across the display
indicating the full meaning of each display acronym. Pressing
the and ke ys when the display is blank
(Mode LED level) will return the display to its default menu
of rotating display items. In addition, the password will be
disabled requiring that it be entered again before changes can
be made to password protected items.
Changing item values or testing outputs is accomplished in
the same manner. Locate and display the desired item. Press the
arrow keys to change the value or state of an item and press the
item, value, or units display will resume. Repeat the process as
required for other items. See Tables 7-21 for further details.
ESCAPEENTER
ESCAPEENTER
ENTER
key to stop the display at the item value. Press th e
key again so that the item value flashes. Use the
key to accept it. Press the key and the
Clearing Unit Alarms —
through the ComfortLink display. To check the current alarms,
enter into the Alarms menu. The first submenu is the CURR
submenu. The CURR function displays the list of current
alarms (maximum of 25). The second submenu item is the
R.CUR (Reset Current Alarms) function. Press to reset the current alarms. The next submenu item, HIST, displays
the list of cleared alarms (maximum of 20). The HIST function
can be cleared with the R.HIS function. See Tables 21 and 22.
→
ECONOMIZER CALIBRATION — Because of a mechanical problem with the economizer, the actuator might acquire a
new degree of rotation which is less than 90 degrees. If this
occurs, a “T414 Economizer Damper Actuator Out of Calibration” alert will be generated. The economizer calibration procedure (E.CAL under the INDP submenu) will reconfigure the
actuator to the new fully closed and fully open positions. To
implement the calibration procedure, change E.CAL from OFF
to ON. E.CAL will remain ON as long as the calibration procedure is being implemented (as long as 5 minutes). During th e
calibration procedure the actuator will close fully and then
open fully. After the calibration is complete, the degree of rotation should be greater than 90 degrees, causing the T414 alarm
to clear. If the T414 alert does not clear, check th e economiz er
damper for other mechanical problems.
See Fig. 7 and T ables 7-21.
ESCAPE
ENTER
ENTER
ESCAPE
The unit alarms can be cleared
ENTER
11
202
Page 12
Service Test —
The Service Test function can be used to
verify proper operation of compressors, indoor, outdoor and
power exhaust fans, heaters, economizer and alarm relay. The
Service Test function can also be used to calibrate the economizer. Refer to Table 9. Use the display keys to enter the mode
and display TEST. Pr ess twice so that OFF flashes.
ENTER
En ter the password i f required (1111 default). Use either arrow
key to change the TEST value to the ON position and press
ENTER
Press and the button to enter the INDP, FANS,
. By selecting ON, Service Test mode is now enabled.
ESCAPE
COOL or HEAT submodes.
Of these four submodes, only INDP is independent, and
therefore only its items can be changed at any time without
affecting the performance of other items (FANS, COOL or
HEAT submodes). For exampl e, if A1 was selected from the
COOL submode, compressor A1 would operate with the
indoor fan and necessary outdoor fans. If ECON (part of
INDP) was changed, the performance of t he COOL outputs
would not be affected. However, if the user selected IDF from
FANS, all of the outputs currently operat ing beca use of A1,
including IDF, would be turned off and then IDF would be
→
Table 7 — Marquee Display Menu Structure
turned on again after a small delay. The ECON settin g, as a
member of INDP , w ould not be affected.
This system of dependent and independent submodes was
developed to ensure that the indoor and outdoor fans were
adequately controlled at all times. It wa s also implemented to
make sure that certain outputs, which could cause the MCA
(Minimum Current Amps) and the MOCP (Maximum Overcurrent Protection) of the unit to be exceeded, do not operate at
the same time.
The INDP submode can used to test the system outputs that
are independent and can operate in all modes: fan only, cooling
and heating. These outputs are ECON, E.PWR, PE.1, PE.2 and
ALM.
When an economizer output (ECON) other than zero is
selected, the economizer power relay E.PWR will automatically be turned ON and the economizer is moved to the selected
position. Afterwards, the user can turn off the power to the
economizer by setting E.PWR to OFF. However, this will not
turn off ECON. If the user reselects ECON, the economizer
power relay will once again be turned ON.
Text continues on page 25.
RUN
STATUS
Auto
Display
(VIEW)
Software
Ver si on
(VERS)
Run Hours
(HRS)
Component
Cycles
(CYCS)
Comp/Heater
Timeguard
(TMGD)
SERVICE
TEST
Manual
Mode
On/Off
(TEST)
Test
Independent
Outputs
(INDP)
Test Fa ns
(FANS)
Test Cooling
(COOL)
Test Heating
(HEAT)
TEMPERATURESPRESSURES
Unit
Temperatures
(UNIT)
Circuit
Temperatures
(CIRC)
Calibrate
Temperatures
(CALB)
SET
POINTS
Cooling
(COOL)
Heating
(HEAT)
Supply Air
(SAT)
Heat-Cool
Set Point
Gap
(HC.SG)
INPUTSOUTPUTS
Thermostat
Inputs
(STAT)
Switch
Inputs
(SW.IN)
IAQ Inputs
(AQ.IN)
Compressor
Current
Sensor
(CS.IN)
Fans
(FANS)
Compressor
(CMPR)
Heat
(HEAT)
Economizer
(ECON)
CONFIGURA-
TION
Unit
Configuration
(UNIT)
Cooling
Configuration
(COOL)
Heating
Configuration
(HEAT)
Economizer
Configuration
(ECON)
IAQ
Configuration
(IAQ)
CCN
Configuration
(CCN)
Display
Configuration
(DISP)
Alarm Output
Control (ALRM)
TIME
CLOCK
Time
(TIME)
Date
(DATE)
Daylight
Savings
Config
(DST)
Occupancy
Schedule
Number
(SCH.N)
Override
Time
Limit
(OTL)
SPT
Override
Enabled?
(OVR.E)
Local
Occupancy
Schedule
(SCH.L)
Accept
Global
Holidays
(HOL.G)
Local
Holiday
Schedule
(HOL.L)
OPERATING
MODES
System
(SYS)
HVAC
(HVAC)
ALARMS
Current
Alarms
(CURR)
Reset
Current
Alarms
(R.CUR)
Alarm
History
(HIST)
Reset
Alarm
History
(R.HIS)
202
12
Page 13
Table 8 — “Run Status” Mode and Submode Directory
SUBMODE
VIEWAuto View of Run Status
KEYPAD
ENTRY
ENTER
ITEMDISPLAYITEM EXPANSIONCOMMENT
SATXXX.XSupply Air Temperature
OCCYES/NOCurrently Occupied
ALRMXXCurrent Alarms & Alerts
TIMEXX.XXTime of Day00.00 – 23.59
VERSSoftware Version Numbers
ENTER
MBBCESR131248-XX-XX
ECBCESR131249-XX-XX
MARQCESR131171-XX-XX
HRSComponent Run Hours
ENTER
A1XXXXComp A1 Run Hours
B1XXXXComp B1 Run Hours
C1XXXXComp C1 Run Hours
IDFXXXXIndoor Fan Run Hours
OFC.1XXXXOD Fan Cont. 1 Run Hours
OFC.2XXXXOD Fan Cont. 2 Run Hours
OFC.3XXXXOD Fan Cont. 3 Run Hours
HTR.1XXXXHeat Stage 1 Run Hours
HTR.2XXXXHeat Stage 2 Run Hours
PE.1XXXXPower Exhaust1 Run Hours
PE.2XXXXPower Exhaust2 Run Hours
E.PWRXXXXEconomizer Pwr Run Hours
ALMXXXXAlarm Output Run Hours
CYCSComponent Cycles
ENTER
A1XXXXCompressor A1 Cycles
B1XXXXCompressor B1 Cycles
C1XXXXCompressor C1 Cycles
IDFXXXXIndoor Fan Cycles
OFC.1XXXXOD Fan Contact. 1 Cycles
OFC.2XXXXOD Fan Contact. 2 Cycles
OFC.3XXXXOD Fan Contact. 3 Cycles
HTR.1XXXXHeat Stage 1 Cycles
HTR.2XXXXHeat Stage 2 Cycles
PE.1XXXXPower Exhaust 1 Cycles
PE.2XXXXPower Exhaust 2 Cycles
E.PWRXXXXEconomizer Power Cycles
ALMXXXXAlarm Output Cycles
TMGDComp/Heater Timeguards
ENTER
TG.A1XXXA1 Timeguard (secs)
TG.B1XXXB1 Timeguard (secs)
TG.C1XXXC1 Timeguard (secs)
TG.H1XXXHeat 1 Timeguard (secs)
TG.H2XXXHeat 2 Timeguard (secs)
13
Page 14
SUBMODE
TEST
INDP
FANS
COOL
HEAT
KEYPAD
ENTRY
ENTER
ENTER
ENTER
ENTER
ENTER
Table 9 — “Service Test” Mode and Submode Directory
ITEMDISPLAYITEM EXPANSIONCOMMENT
ON/OFFField Service Test ModeUse to Enable/Disable Manual Mode
Test Independent Outputs
ECONXXXEconomizer Position Test%
E.PWRON/OFFEconomizer Power Test
E.CALON/OFFCalibrate Economizer
PE.1ON/OFFPower Exhaust 1 Test
PE.2ON/OFFPower Exhaust 2 Test
ALMON/OFFAlarm Relay Test
Te s t F a n s
IDFON/OFFIndoor Fan Test
IDFPON/OFFIndoor Fan Power Test
OFC.1ON/OFFOutdoor Fan Cntr 1 Test
OFC.2ON/OFFOutdoor Fan Cntr 2 Test
OFC.3ON/OFFOutdoor Fan Cntr 3 Test
Test Cooling
A1ON/OFFCompressor A1 Test
B1ON/OFFCompressor B1 Test
C1ON/OFFCompressor C1 Test
Test Heating
HTR.1ON/OFFHeat Stage 1 Test
HTR.2ON/OFFHeat Stage 2 Test
SUBMODE
UNIT
CIRC
CALB
KEYPAD
ENTRY
ENTER
ENTER
ENTER
Table 10 — “Temperatures” Mode and Submode Directory
ITEMDISPLAYITEM EXPANSIONCOMMENT
Unit Temperatures
SATXXX.XSupply Air Temperature
OATXXX.XOutdoor Air Temperature
SPTXXX.XSpace Temperature
SPTOX.XSpace Temperature Offset
Circuit Temperatures
SST.AXXX.XSaturated Suct Temp ATemperature is calculated
SCT.AXXX.XSaturated Cond Temp A
SST.BXXX.XSaturated Suct Temp BTemperature is calculated
SCT.BXXX.XSaturated Cond Temp B
SST.CXXX.XSaturated Suct Temp CTemperature is calculated
SCT.CXXX.XSaturated Cond Temp C
Calibrate Temperatures
SPT.CXXX.XSpace Sensor Calibration
SPT.TXXX.XSpace Temperature Trim
Enter either temperature or
trim but not both
Enter either temperature or
trim but not both
14
Page 15
Table 11 — “Pressures” Mode and Submode Directory
SUBMODE
SUBMODE
COOL
HEAT
SAT
KEYPAD
ENTRY
KEYPAD
ENTRY
ENTER
ENTER
ENTER
ITEMDISPLAYITEM EXPANSIONCOMMENT
SSP.AXXX.XSaturated Suct Press A
SCP.AXXX.XSaturated Cond Press APressure is calculated
SSP.BXXX.XSaturated Suct Press B
SCP.BXXX.XSaturated Cond Press BPressure is calculated
SSP.CXXX.XSaturated Suct Press C
SCP.CXXX.XSaturated Cond Press CPressure is calculated
Table 12 — “Set Points” Mode and Submode Directory
ITEMDISPLAYITEM EXPANSIONCOMMENT
Cooling Set points
OCSPXXOccupied Cool Set pointDefault: 78
UCSPXXUnoccupied Cool Set pointDefault: 85
Heating Set points
OHSPXXOccupied Heat Set pointDefault: 68
UHSPXXUnoccupied Heat Set pointDefault: 60
Supply Air Set points
LCSPXXLow Cool SAT Set pointDefault: 65
HC.SG
SUBMODE
COOL
ENTER
KEYPAD
ENTRY
ENTER
ENTER
ENTER
ENTER
ESCAPE
HCSPXXHigh Cool SAT Set pointDefault: 55
MIN.LXX.XMinimum SAT Lower LevelDefault: 48.0
MIN.HXX.XMinimum SAT Upper LevelDefault: 58.0
HC.SGXXHeat-Cool Set Point GapDefault: 5
Table 13 — Reading and Changing Cooling Occupied Set Point
ITEMDISPLAYITEM EXPANSIONCOMMENT
OCSP78Occupied Cool Set pointDefault: 78
78Scrolling Stops
78Value flashes
Select 75
75Change accepted
OCSP75Occupied Cool Set pointItem/Value/Units scroll again
15
Page 16
Table 14 — “Inputs” Mode and Submode Directory
SUBMODE
STAT
SW.IN
AQ.IN
CS.IN
KEYPAD
ENTRY
ENTER
ENTER
ENTER
ENTER
ITEMDISPLAYITEM EXPANSION
Thermostat Inputs
Y1ON/OFFThermostat Y1 Input
Y2ON/OFFThermostat Y2 Input
W1ON/OFFThermostat W1 Input
W2ON/OFFThermostat W2 Input
GON/OFFThermostat G Input
Switch Inputs
FIL.SDRT/CLNFilter Status
FAN.SON/OFFFan Status
FDWNON/OFFUnit Shutdown Input
ENTHHIGH/LOWEnthalpy Switch Input
RM.OCON/OFFRemote Occupancy Input
IAQ Inputs
IAQXXXXIndoor Air Quality
OAQXXXXOutdoor Air Quality
Current Sensor Inputs
CS.A1ON/OFFA1 Current Sensor
CS.B1ON/OFFB1 Current Sensor
CS.C1ON/OFFC1 Current Sensor
SUBMODE
FANS
CMPR
HEAT
ECON
Table 15 — “Outputs” Mode and Submode Directory
KEYPAD
ENTRY
ENTER
ENTER
ENTER
ENTER
ITEMDISPLAYITEM EXPANSION
Fan Outputs
IDFON/OFFIndoor Fan
IDFPON/OFFIndoor Fan Power
OFC.1ON/OFFOutdoor Fan Contactor 1
OFC.2ON/OFFOutdoor Fan Contactor 2
OFC.3ON/OFFOutdoor Fan Contactor 3
Compressor Outputs
A1ON/OFFCompressor A1
B1ON/OFFCompressor B1
C1ON/OFFCompressor C1
Heat Outputs
HTR.1ON/OFFHeat Stage 1
HTR.2ON/OFFHeat Stage 2
Economizer Outputs
EC.APXXXEconomizer Position
EC.CPXXXEconomizer Commanded Pos
E.PWRON/OFFEconomizer Power
PE.1ON/OFFPower Exhaust Relay 1
PE.2ON/OFFPower Exhaust Relay 2
16
Page 17
SUBMODE
UNIT
COOL
KEYPAD
ENTRY
ENTER
ENTER
Table 16 — “Configuration” Mode and Submode Directory
ITEMDISPLAYITEM EXPANSIONCOMMENT
Unit Configuration
Default: 1
U.CTLXUnit Control Type
T.CTLXThermostat Control Type
OC.FNYES/NOFan On When OccupiedDefault: YES
S.DLYXXXStart Up DelayDefault: 30 sec
IDF.FYES/NOShut Down On IDF FailureDefault: YES
FN.SWXFan Status Input
FL.SWXFilter Status Input
FS.SWXFire Shutdown Input
RM.SWXRemote Occupancy Switch
ECBYES/NOECB InstalledDefault: YES
SAT.TXXXSAT Settling Time (Secs)Default: 240 sec
Cooling Configuration
N.CMPXNumber of CompressorsDefault: 3 (016-024), 2 (014,028)
Table 17 — Example of Changing the CCN Configuration
ITEMDISPLAYITEM EXPANSIONCOMMENT
CCN.A1CCN AddressDefault: 1
1Scrolling Stops
Value flashes
Select 2
Change accepted
CCN.AItem/Value/Units scroll again
CCN.BCCN Bus NumberNo change
BAUDCCN Baud RateDefault: 3 = 9600
3Scrolling Stops
3Value flashes
Select 5 = 38,400
5Change accepted
BAUD5CCN Baud RateItem/Value/Units scroll again
19
Page 20
Table 18 — “Time Clock” Mode and Submode Directory
SUBMODE
TIME
DATE
DST
SCH.N
OVR.E
OTL
SCH.L
SUB-SUB
MODE
KEYPAD
ENTRY
ENTER
ENTER
ITEMDISPLAYITEM EXPANSIONCOMMENT
TIMEXX.XXHour and MinuteMilitary (00.00-23.59)
Current Date
MNTHXXMonth of Year1=Jan, 2=Feb, etc.
DOMXXDay ofMonthRange 1-31
YEARXXXXYear
DAYXXDay of Week1=Mon, 2=Tue, etc.
ENTER
Daylight Savings Config.
STR.MXXDST Start MonthDefault: 4
STR.WXDST Start WeekDefault: 1
STR.DXDST Start DayDefault: 7
M.ADDXXDST Minutes to AddDefault: 60
STP.MXXDST Stop MonthDefault: 10
STP.WXDST Stop WeekDefault: 5
STP.DXDST Stop DayDefault: 7
M.SUBXXDST Minutes to SubtractDefault: 60
ENTER
ENTER
ENTER
ENTER
PER.1Occupancy Period 1
ENTER
SCH.NXXOccupancy Schedule Num.
OVR.EYES/NOSPT Override EnabledDefault: YES
OTLXOverride Time LimitDefault: 4
Local Occupancy Schedule
0 = Always Occupied
1 – 64 = Local Schedule
65 – 99 = Global Schedule
OCC.1XX.XXPeriod Occupied TimeRange: 00.00 to 23.59; Default: 00.00
UNC.1XX.XXPeriod Unoccupied TimeRange: 00.00 to 23.59; Default: 00.00
MON.1YES/NOMonday In PeriodDefault = No
TUE.1YES/NOTuesday In PeriodDefault = No
WED.1YES/NOWednesday In PeriodDefault = No
THU.1YES/NOThursday In PeriodDefault = No
FRI.1YES/NOFriday In PeriodDefault = No
SAT.1YES/NOSaturday In PeriodDefault = No
SUN.1YES/NOSunday In PeriodDefault = No
ESCAPE
PER.2Occupancy Period 2
ENTER
HOL.1YES/NOHoliday In PeriodDefault = No
OCC.2XX.XXPeriod Occupied TimeRange: 00.00 to 23.59; Default: 00.00
UNC.2XX.XXPeriod Unoccupied TimeRange: 00.00 to 23.59; Default: 00.00
20
Page 21
Table 18 — “Time Clock” Mode and Submode Directory (cont)
SUBMODE
SCH.L
(cont)
SUB-SUB
MODE
PER.2
KEYPAD
ENTRY
ITEMDISPLAYITEM EXPANSIONCOMMENT
MON.2YES/NOMonday In PeriodDefault = No
(cont)
TUE.2YES/NOTuesday In PeriodDefault = No
WED.2YES/NOWednesday In PeriodDefault = No
THU.2YES/NOThursday In PeriodDefault = No
FRI.2YES/NOFriday In PeriodDefault = No
SAT.2YES/NOSaturday In PeriodDefault = No
SUN.2YES/NOSunday In PeriodDefault = No
ESCAPE
PER.3Occupancy Period 3
ENTER
HOL.2YES/NOHoliday In PeriodDefault = No
OCC.3XX.XXPeriod Occupied TimeRange: 00.00 to 23.59; Default: 00.00
UNC.3XX.XXPeriod Unoccupied TimeRange: 00.00 to 23.59; Default: 00.00
MON.3YES/NOMonday In PeriodDefault = No
TUE.3YES/NOTuesday In PeriodDefault = No
WED.3YES/NOWednesday In PeriodDefault = No
THU.3YES/NOThursday In PeriodDefault = No
FRI.3YES/NOFriday In PeriodDefault = No
SAT.3YES/NOSaturday In PeriodDefault = No
SUN.3YES/NOSunday In PeriodDefault = No
ESCAPE
PER.4Occupancy Period 4
ENTER
HOL.3YES/NOHoliday In PeriodDefault = No
OCC.4XX.XXPeriod Occupied TimeRange: 00.00 to 23.59; Default: 00.00
UNC.4XX.XXPeriod Unoccupied TimeRange: 00.00 to 23.59; Default: 00.00
MON.4YES/NOMonday In PeriodDefault = No
TUE.4YES/NOTuesday In PeriodDefault = No
WED.4YES/NOWednesday In PeriodDefault = No
THU.4YES/NOThursday In PeriodDefault = No
FRI.4YES/NOFriday In PeriodDefault = No
SAT.4YES/NOSaturday In PeriodDefault = No
SUN.4YES/NOSunday In PeriodDefault = No
ESCAPE
PER.5Occupancy Period 5
ENTER
HOL.4YES/NOHoliday In PeriodDefault = No
OCC.5XX.XXPeriod Occupied TimeRange: 00.00 to 23.59; Default: 00.00
UNC.5XX.XXPeriod Unoccupied TimeRange: 00.00 to 23.59; Default: 00.00
MON.5YES/NOMonday In PeriodDefault = No
TUE.5YES/NOTuesday In PeriodDefault = No
WED.5YES/NOWednesday In PeriodDefault = No
THU.5YES/NOThursday In PeriodDefault = No
FRI.5YES/NOFriday In PeriodDefault = No
SAT.5YES/NOSaturday In PeriodDefault = No
21
Page 22
Table 18 — “Time Clock” Mode and Submode Directory (cont)
SUBMODE
SCH.L
(cont)
SUB-SUB
MODE
PER.5
KEYPAD
ENTRY
ITEMDISPLAYITEM EXPANSIONCOMMENT
SUN.5YES/NOSunday In PeriodDefault = No
(cont)
ESCAPE
PER.6Occupancy Period 6
ENTER
HOL.5YES/NOHoliday In PeriodDefault = No
OCC.6XX.XXPeriod Occupied TimeRange: 00.00 to 23.59; Default: 00.00
UNC.6XX.XXPeriod Unoccupied TimeRange: 00.00 to 23.59; Default: 00.00
MON.6YES/NOMonday In PeriodDefault = No
TUE.6YES/NOTuesday In PeriodDefault = No
WED.6YES/NOWednesday In PeriodDefault = No
THU.6YES/NOThursday In PeriodDefault = No
FRI.6YES/NOFriday In PeriodDefault = No
SAT.6YES/NOSaturday In PeriodDefault = No
SUN.6YES/NOSunday In PeriodDefault = No
ESCAPE
PER.7Occupancy Period 7
ENTER
HOL.6YES/NOHoliday In PeriodDefault = No
OCC.7XX.XXPeriod Occupied TimeRange: 00.00 to 23.59; Default: 00.00
UNC.7XX.XXPeriod Unoccupied TimeRange: 00.00 to 23.59; Default: 00.00
MON.7YES/NOMonday In PeriodDefault = No
TUE.7YES/NOTuesday In PeriodDefault = No
WED.7YES/NOWednesday In PeriodDefault = No
THU.7YES/NOThursday In PeriodDefault = No
FRI.7YES/NOFriday In PeriodDefault = No
SAT.7YES/NOSaturday In PeriodDefault = No
SUN.7YES/NOSunday In PeriodDefault = No
ESCAPE
PER.8Occupancy Period 8
ENTER
HOL.7YES/NOHoliday In PeriodDefault = No
OCC.8XX.XXPeriod Occupied TimeRange: 00.00 to 23.59; Default: 00.00
UNC.8XX.XXPeriod Unoccupied TimeRange: 00.00 to 23.59; Default: 00.00
MON.8YES/NOMonday In PeriodDefault = No
TUE.8YES/NOTuesday In PeriodDefault = No
WED.8YES/NOWednesday In PeriodDefault = No
THU.8YES/NOThursday In PeriodDefault = No
FRI.8YES/NOFriday In PeriodDefault = No
SAT.8YES/NOSaturday In PeriodDefault = No
SUN.8YES/NOSunday In PeriodDefault = No
ESCAPE
HOL.8YES/NOHoliday In PeriodDefault = No
22
Page 23
Table 18 — “Time Clock” Mode and Submode Directory (cont)
SUBMODE
HOL.G
HOL.L
SUB-SUB
MODE
HOL.1Holiday 1
KEYPAD
ENTRY
ENTER
ENTER
ENTER
ITEMDISPLAYITEM EXPANSIONCOMMENT
HOL.GYES/NOAccept Global HolidaysDefault: YES
Local Holiday Schedule
MTH.1XXHoliday Start MonthDefault: 0
DAY.1XHoliday Start DayDefault: 0
ESCAPE
HOL.2Holiday 2
ENTER
LEN.1XXHoliday Duration (Days)Default: 0
MTH.2XXHoliday Start MonthDefault: 0
DAY.2XHoliday Start DayDefault: 0
ESCAPE
HOL.3Holiday 3
ENTER
LEN.2XXHoliday Duration (Days)Default: 0
MTH.3XXHoliday Start MonthDefault: 0
DAY.3XHoliday Start DayDefault: 0
ESCAPE
HOL.4Holiday 4
ENTER
LEN.3XXHoliday Duration (Days)Default: 0
MTH.4XXHoliday Start MonthDefault: 0
DAY.4XHoliday Start DayDefault: 0
ESCAPE
HOL.5Holiday 5
ENTER
LEN.4XXHoliday Duration (Days)Default: 0
MTH.5XXHoliday Start MonthDefault: 0
DAY.5XHoliday Start DayDefault: 0
ESCAPE
HOL.6Holiday 6
ENTER
LEN.5XXHoliday Duration (Days)Default: 0
MTH.6XXHoliday Start MonthDefault: 0
DAY.6XHoliday Start DayDefault: 0
ESCAPE
HOL.7Holiday 7
ENTER
LEN.6XXHoliday Duration (Days)Default: 0
MTH.7XXHoliday Start MonthDefault: 0
DAY.7XHoliday Start DayDefault: 0
ESCAPE
HOL.8Holiday 8
ENTER
LEN.7XXHoliday Duration (Days)Default: 0
MTH.8XXHoliday Start MonthDefault: 0
DAY.8XHoliday Start DayDefault: 0
ESCAPE
HOL.9Holiday 9
ENTER
LEN.8XXHoliday Duration (Days)Default: 0
ESCAPE
MTH.9XXHoliday Start MonthDefault: 0
DAY.9XHoliday Start DayDefault: 0
LEN.9XXHoliday Duration (Days)Default: 0
23
Page 24
Table 19 — Setting an Occupied Time Schedule – Weekdays Only for 7:30 to 22:30
SUBMODE
SCH.L
SUB-SUB
MODE
PER.1OCC.1Period Occupied Time
KEYPAD
ENTRY
ENTER
ENTER
ENTER
ENTER
ITEMDISPLAYITEM EXPANSIONCOMMENT
Local Occupancy Schedule
00.00Scrolling stops
00.00Hours Flash
07.00Select 7
ENTER
07.00Change accepted, minutes flash
07.30Select 30
ENTER
ESCAPE
OCC.107.30Period Occupied TimeItem/Value/Units scrolls again
07.30Change accepted
UNC.100.00Period Unoccupied Time
ENTER
ENTER
00.00Scrolling stops
00.00Hours Flash
22.00Select 22
ENTER
22.00Change accepted, minutes flash
22.30Select 30
ENTER
ESCAPE
UNC.122.30Period Unoccupied TimeItem/Value/Units scrolls again
22.30Change accepted
MON.1NOMonday In Period
ENTER
NOScrolling stops
YESSelect YES
ENTER
ESCAPE
MON.1YESMonday In Period Item/Value/Units scrolls again
YESChanged accepted
TUE.1NOTuesday In Period
ENTER
NOScrolling stops
YESSelect YES
ENTER
ESCAPE
TUE.1YESTuesday In Period Item/Value/Units scrolls again
YESChanged accepted
WED.1NOWednesday In Period
ENTER
NOScrolling stops
YESSelect YES
ENTER
ESCAPE
WED.1YESWednesday In Period Item/Value/Units scrolls again
YESChanged accepted
THU.1NOThursday In Period
ENTER
NOScrolling stops
YESSelect YES
ENTER
ESCAPE
THU.1YESThursday In Period Item/Value/Units scrolls again
YESChanged accepted
FRI.1NOFriday In Period
ENTER
NOScrolling stops
YESSelect YES
ENTER
ESCAPE
ESCAPE
ESCAPE
FRI.1YESFriday In Period Item/Value/Units scrolls again
YESChanged accepted
24
Page 25
Table 20 — “Operating Modes” Mode and Submode Directory
SUBMODE
SYS
HVAC
SUBMODE
CURR
R.CUR
HIST
R.HIS
SUBMODE
CURR
CURR
KEYPAD
ENTRY
KEYPAD
ENTRY
ENTER
ENTER
ENTER
ENTER
KEYPAD
ENTRY
ENTER
ESCAPE
ITEMDISPLAYCOMMENT
Item expansion changes as a function of system status
Item expansion changes as a function of the HVAC status.
Table 21 — “Alarms” Mode and Submode Directory
ITEMITEM EXPANSIONCOMMENT
AXXX or TXXXCurrently Active Alarms
YES/NOReset All Current Alarms
AXXX or TXXXAlarm History
YES/NOReset Alarm History
Alarms are shown as AXXX
Alerts are shown as TXXX
Alarms are shown as AXXX
Alerts are shown as TXXX
Table 22 — Example of Reading and Clearing Alarms
ITEMITEM EXPANSIONCOMMENT
AXXX or TXXX
Active Alarms (AXXX) or Aler ts (TXXX)
displayed
R.CUR
ENTER
ENTER
NOUse to clear active alarms/alerts
NONO Flashes
YESSelect YES
NOAlarms/alerts clear, YES changes to NO
The FANS submode is used to test the IDF, IDFP, OFC.1,
OFC.2 and OFC.3 variables. The IDF variable is used to force
the IGC to turn on the indoor fan (48HG units only). The IGC
closes a relay, which then supplies power to the IDFP relay. On
50HG units, the PL3 is jumpered by simulating a permanently
closed IGC relay. The indoor fan power relay then is energized
to close the IDF contactor. If IDFP is off, the indoor fan cannot
operate. This enables the software to tu rn off the indoor fan
power imme di at ely, even if an I G C is inst al led .
The COOL submode is used to test the compressors. In t h is
mode, the user can turn on any combination of the three compressors. The software will stagger the compressor start-ups by
15 seconds. During Service Test, the compressor minimum off
time is 30 seconds. While the compressors operate, the software will control the indoor and outdoor fans as necessary to
maintain safe unit operation. All safeties are monitored while
the compressors operate and the safeties will turn a compressor, circuit or the unit off if required. If a compressor shuts
down because of a safety, the software will set the compressor
request (A1, B1 or C1) to OFF, forcing the user to reselect the
compressor to re start the compress or in Service mode. All other menus are available during Service Test, enabling the user to
watch temperatures and pressures while the compressors operate in Service mode.
In the HEAT submode, TB4-1 (R) must be connected to
TB4-4 (W1) in order to operate the heaters. If the control mode
is Thermostat Mode, remove the jumper after l eaving Service
T est mode.
All outputs are turned off when the software transitions
from TEST m o d e t o NO R M AL mode. To r e tu r n to NORMAL
mode, set TEST to OFF.
25
Page 26
OPERATION
Unit Control Type (U.CTL) —
determined by Unit Control Type, which can be found in
UNIT, a submode of Configuration. There are three available
options that can be set from the Scrolling Marquee.
1. Auto (U.CTL = 1) — This mode selects the active mode
by evaluating the devices connected to the unit. If a valid
space temperature probe is connected t o the unit, the unit
will operate in Space Sensor mode. If not, the unit will
operate in Thermostat mode.
2. Thermostat (U.CTL = 2) — The unit determines cooling
and heating demand by the state of G, Y1, Y 2, W1 and
W2.
3. Space Sensor (U.CTL = 3) — The unit det ermines cooling or heating demand based on the space temperature
and the appropriate set point.
The available set points are Occupied Cool Set Point
(OCSP), Unoccupied Cool Set Point (UCSP), Occupied Heat
Set Point (OHSP), and Unoccupied Heat Set Point (UHSP).
The occupied or unoccupied heating set point should always be
a minimum of 5 F below the corresponding cooling set point.
This ensures that the unit does not switch from cooling to heating unnecessarily. The cooling and heating set point deadband
can be changed (HC.SG).
Occupancy Determination —
mine whether the unit considers the building occupied or unoccupied. If the unit is operating with a space tempera ture probe
(T55, T56 or T58), occupancy affects the unit set points and the
operation of the economizer. If the unit is operating under thermostat control, occupancy only affects the operation of the
economizer. The factors affecting occupancy are listed below
from highest to lowest priority.
1. The CCN point OCCUPIED is forced via an external device such as a ComfortID ™ cont roller — Whe n O CCU PIED is forced to YES, the unit is considered occupied.
When OCCUPIED is forced to NO, the unit is considered
unoccupied. If OCCUPIED is not being forced, proceed
to the level 2.
2. Remote Occupancy Switch is configured as Normally
Open or Normally Closed — This switc h should b e configured to either Normally Open or Normally Closed
when the user would like to control the occupancy with an
external switch. There are three possible configurations
for the remote occupancy switch: No Switch (0), Normally Open (1) or Normally Closed (2). This configuration is
accessible on the display at Configuration/Unit/RM.SW.
If the switch is configured to No Switch (0), the switch input value will be ignored and software will proceed to the
level 3 priority. For each type of switch, the appropriate
configuration and states are listed in the table below .
TYPE OF SWITCH
Occupied when
closed or Unoccupied
when open
Occupied when
open or Unoccupied
when closed
3. The following occupancy options are determined by the
state of Occupancy Schedule Number (SCH.N) and the
Global Schedule Broadcast (B.GS). The Schedule Number is a submode of Time Clock on the Scrolling Marquee
SWITCH
CONFIGURATION
Normal Open (1)
Normal Close (2)
The control method is
Many factors deter-
STATE OF
SWITCH AND STATE
OF OCCUPANCY
Open and Unoccupied
Closed and Occupied
Open and Occupied
Closed and Unoccupied
and Global Schedule Broadcast can be found on the
Scrolling Marquee under Configuration/CCN.
a. SCH.N = 0: The unit is always considered occu-
pied and the programmed schedule is ignored. This
is the factory default.
b. SCN.N = 1-64: Follow the local programmed
schedule. Schedules 1 to 64 are local within the
controller. The Centurion unit can only store one
local schedule and therefore changing this number
only changes the title of the schedule table.
c. SCH.N = 65-99: Follow the global programmed
schedule. If the Centurion unit is configured as a
Global Schedule broadcaster (B.GS = YES), the
unit will follow the unit’s programmed schedule
and broadcast the schedule so that other devices
programmed to follow this schedule number can
receive the schedule. If the Centurion unit is not
programmed as a Global Schedule broadcaster
(B.GS = NO), the unit will receive its information
from the unit programmed to broadcast this schedule number.
Indoor Fan
48HG UN ITS — The indoor fan is controlled by three independent relays on a 48HG unit. The MBB fan relay is located
on the MBB and signals the IGC to turn on the indoor fan. The
IGC fan relay is located on the IGC and ca n operate independently of the MBB relay. When the IGC receives a request
from the MBB rela y, t he IGC will turn on it s relay. The IGC
will also turn on its relay when it determines that the indoor fan
should be on for gas heating. The IGC fan relay supplies
24 volts to the final relay known as indoor fan power relay
(IDFP), located on the MBB. This final relay supplies 24V t o
the indoor fan contactor and to the indoor fan feedback input.
Unless there is a problem, this relay will be closed. When the
unit needs to shut down immediately because of a smoke problem, this relay will open. This allows the Centurion unit to turn
off the indoor fan immediately even when the IGC is control ling the indoor fan. The fan feedback input allows the MBB to
determine when the IGC has turned on the indoor fan. For indoor fan operation, see Indoor Fan Control section below.
50HG UNITS — Because a 50HG unit does not have an IGC,
the indoor fan is controlled by the indoor fan rel ay (IDF) and
the indoor fan power relay (IDFP) on the MBB. The IGC fan
relay is replaced by a jumper wire on the 50HG unit. The indoor fan will operate whenever the IDF and the IDFP are
closed. For indoor fan operation, see the Indoor Fan Control
section below. Unless there is a problem, the IDFP relay will be
closed. When the unit needs to shut down immediately because
of a smoke problem, this relay will open.
INDOOR-FAN CONTROL (48HG AND 50HG
UNITS) — In Space Temperature mode, the IDF relay will be
on in the following situations. If the unit is in Occupied mode
and the indoor fan is configured to always run while occupied
(OC.FN = YES), the indoor fan will be ON. If OC.FN equals
NO or the unit is unoccupied, the indoor fan will opera te only
when heating or cooling is necessary.
In Thermostat mode, the IDF relay will be on in the following situatio n s. If G is On, then the I D F w ill be On. If the unit is
in the Cool mode, the IDF will be on. If the unit is in the H eat
mode for a 50HG unit, the IDF will be On. The unit will not
turn on the IDF on a 48HG unit while in Heat mode (unless G
is On) because the IGC is capable of controlling the indoor fan
in this situation.
26
Page 27
Outdoor Fans —
The operation of the outdoor fans
depends on the on/off status and discharge pressure, measured
by the condensing temperature thermistors, of each circuit.
Depending upon these values, the “fan level” for each circuit
will be either 0, 1, or 2 as defined by Table 23. Fan level will
increment when the discharge pressure is greater than the “On”
level and decrement when the discharge pressure is less than
the “Off” level. For example, if the discharge pressure starts at
90 psig for Circuit A, the fan level for Circuit A will be 0.
When the pressure rises above 150 psig, the fan level will
change from 0 to 1. Later, if the pressure drops below 0 psig,
the fan level will return to 0. However, since the pressure cannot drop below 0 once the circuit is level 1, it will remain at
least level 1 until the corresponding compressor is turned off.
Depending upon the fan level of each circuit, the unit will
control the three outdoor fan contactors as specified in
Table 24. If any circuit requires an outdoor fan contactor to be
ON, then it will be ON even if another circuit does not require
it to be ON. As shown in Fig. 3, OFC1 controls OFM1; OFC2
controls OFM2 (028 only), OFM3, OFM5 (028 only) and
OFM6; and OFC3 controls OFM4. For example, if the fan
levels for Circuits A and B are 0 and the fan level for Circuit C
is 1, OFC1 and OFC3 will be energized.
Economizer —
If an economizer is installed, then Economizer Equipped configuration should be set to YES (EC.EQ).
If the indoor fan is off or the building is unoccupied, the economizer position is zero. If in Occupied mode and the unit is heating or cooling and the economizer cannot provide free cooling,
the economizer position is the Economizer Min Position
(MIN.P) or the position specified by the IAQ algorithm. If in
Unoccupied mode, the position is 0% open.
In cooling, the economizer will be allowed to help with
cooling if the outdoor air temperature (OAT) is less than the
economizer high temperature lockout (ECL.H). If an enthalpy
sensor is installed, the outdoor temperature must be be low the
economizer high temperature lockout temperature and enthalpy must be low. If the outdoor temperature is less than
economizer low temperature lockout (ECL.L), the economizer
will not provide free cooling.
If the unit is in cooling, operating under thermostat control,
Y1 = ON, and the economizer is available for cooling, the
economizer will control the supply air temperature to the low
cool set point (LCSP). When Y2 = ON, the economizer
will control the supply air temperature to high cool set point
(HCSP).
If the unit is in cooling, operating under spac e temperature
control, the economizer is available for cooling, and no compressors are operating, the economizer will control the SAT to
either LCSP or HCSP (see Table 25). If a compress or is ON,
the economizer will try to position itself at 100%.
If at any time there is a l o w suction pressure problem whil e
the economizer is cooling, the maximum allowable economizer position will be reduced. The maximum values are 50, 25
and 0% for circuits A, B and C respectively. The maximum
value will remain in effect until the compressor “in trouble”
turns off. The effective maximum economizer position must
always be higher than the current minimum position.
Table 23 — Outdoor Fan Level Transitions
FAN LEVEL
Lev1Off
Lev1On
Lev2Off
Lev2On
CIRCUIT (PRESSURE) (psig)
ABC
000
150150150
100100100
200200200
Table 24 — Fan Level Control of
Outdoor Fan Contactors (1,2,3)
FAN L E V E L
0
1
2
ABC
———
131, 3
1, 22, 31, 2, 3
CIRCUIT
Table 25 — LCSP and HCSP Transitions for
Space Temperature Mode
CURRENT SAT
SET POINT
LCSP
HCSP
LCSP
LEGEND
Supply-Air Temperature
SAT —
Indoor Air Quality (IAQ) —
indoor air quality (IAQ) is measured using a CO
COOL DEMAND
∆∆∆∆
(
F)
>0.5HCSP
<0LCSP
<–0.5Exit Cooling
On the Centurion unit,
NEXT SAT
SET POINT
sensor whose
2
measurements are displayed in parts per million (PPM). The
IAQ sensor can be field- or factory-installed in the return duct.
If IAQ must be measured directly in the space instead of the
unit return, a wall-mounted accessory can be field installed.
The Centurion unit’s indoor air quality algorithm modulates
the position of the economizer damper between two user
configurations depending upon the relationship between the
IAQ and the Outdoor Air Quality (OAQ). The lower of these
two positions is referred to as the Minimum IAQ Damper
Position (AQ.MP) while the higher is referred as Economizer
Minimum Position (MIN.P). The AQ.MP should be set to an
economizer position that brings in enough fresh air to remove
contaminants and CO
The MIN.P should be set to an economizer position that brings
in enough fresh air to remove contaminants and CO
generated by sources other than people.
2
generated
2
by all sources including people. The MIN.P value is the design
value for maximum occupancy.
The ComfortLink™ control will begin to open the damper
from the AQ.MP position when the IAQ level begins to exceed
the OAQ level by a configurable amount, which is referred to
as AQ Differential Low (AQD.L). If OAQ is not being
measured, OAQ will be assumed to equal 400 PPM. When the
differential between IAQ and OAQ reaches AQ Differential
High (AQD.H), the economizer position will be MIN.P. When
the IAQ/OAQ differential is between AQD.L and AQD.H, th e
control will modulate the damper between AQ.MP and MIN.P
in a linear manner as shown in Fig. 12 below. The damper
position will never exceed the bounds specified by AQ.MP and
MIN.P during IAQ control. If the building is occupied and the
indoor fan is running and the differential between IAQ and
OAQ is less than AQD.L, the economizer will remain at
AQ.MP. The economizer will not close completely. The
damper position will be 0 when the fan is not running or the
building is unoccupied. The damper position may exceed
MIN.P in order to provide free cooling.
The ComfortLink control is configured for air quality
sensors which provide 4 mA at 0 PPM and 20 mA at
2000 PPM. If a sensor has a different range, these bounds must
be reconfigured. The values for I.4M, I.20M, O.4M and
O.20M on the display represent the PPM corresponding to
4 mA and 20 mA for IAQ and OAQ, respectively.
If OAQ exceeds the OAQ Lockout Value (OAQ.L), the
economizer will remain at AQ.MP.
27
Page 28
ECONOMIZER
MINIMUM
DAMPER
POSITION
(MIN. P)
VENTILATION FOR PEOPLE
MINIMUM
IAQ
DAMPER
POSITION
(AQ.MP)
INCREASING VENTILATION
VENTILATION FOR SOURCES
100
500
AQ
DIFFERENTIAL
LOW (AQD.L)
→
Power Exhaust —
To enable power exhaust, PE.EN
must be set to YES. If power exhaust is enabled, Power
Exhaust 1 will turn on when the economizer position is greater
than PE1.P. If power exhaust is enabled, Power Exhaust 2 will
turn on when the economizer position is greater than PE2.P.
There are small time delays to ensure that rapid cyc ling does
not occur.
Compressor Staging —
The electronic controls determine the number of cooling stages neede d at any given time
as specified in the Cooling section. However, which specific
cooling stage operates at any given time depends on compressor staging order and compressor status.
COMPRESSOR ST AGI NG ORDER — T he 48/50HG016-024
units have three stages of cooling (Circuits A, B and C).
The 48/50HG014 and 028 units have two stag es of cooling ( Circuits A and B). The position of the evaporators for Circuits A, B
and C are bottom, mi ddle and to p (see Fig. 4 ) for a 3-ci rcuit unit.
The position of the evaporators is bottom and top for Circuits A
and B on a 2-circuit unit. Depending on conditions listed below,
circuits will either stage from the bottom evaporator to the top
evaporator (BtoT) or from the top evaporator to the bottom
evaporator (TtoB). When the unit is staging TtoB, the unit is
stated to be inverted.
If inverting is not allowed as determined by the configuration (INV.E = NO), the unit will always stage BtoT. However,
if INV.E = YES, then the unit will invert if the outdoor temperature as measured by OAT is greater than 80 F for 15 minutes
continuously. Inverting will continue until either INV.E is set to
NO or the OAT drops below 75 F for 1 minute.
COMPRESSOR STATUS — Having determined whether
staging will occur as either BtoT or TtoB, the unit controls will
determine the final order of compressor staging. If all circuits
are functioning properly, the compressor staging will always
follow either BtoT or TtoB. Therefore if the staging method is
BtoT, then Circuit A must turn On before Circuit B and
Circuit B before Circuit C. Likewise when removing stages,
Fig. 12 — IAQ Control
700
1100
AQ
DIFFERENTIAL
HIGH (AQD.H)
INSIDE/OUTSIDE CO
INSIDE CO
CONCENTRATION
2
DIFFERENTIAL
2
the stages must be removed in the opposite order. In all cases,
the minimum on-time of 3 minutes (MRT.C) and the minimum
off-time of 5 minutes (MOT.C) must be honored. Therefore, if
the staging order is BtoT and Circuit A was shut down two
minutes previously, no circuits will turn on until the minimum
off-time for Circuit A has expired; no matter how many circuits
are requested.
The rules are different if a circuit has shutdown because of
an alarm such as low refrigerant pressure. When a circuit is unavailable because it is not functioning properly, it will be replaced immediately by another circuit. Therefore, if Circuit A
and B are operating because two circuits have been requested,
the staging is BtoT, and then Circuit A shuts down because of
low refrigerant pressure, the control will turn off Circuit A and
replace it with Circuit C. Later if Circuit A is allowed to restart
(see Alarm Handling on page 31) and BtoT is still active with
two requested stages, Circuit A will attempt to restart. If Circuit
A has run for 1 minute without sensing any problems, it will be
deemed acceptable, causing Circuit C to shutdown. Circuit C
will shut down because only two circuits are needed and
Circuit A and B are functioning properly.
Heating (48HG Units)
NOTE: THE 48HG units have 2 stages of heat.
For 48HG units, the heat type will automatical ly be set to 1
for gas units (HT.TY). Heat will not operate if the outdoor temperature is greater than the heat lockout temp (HT.LO).
THERMOSTAT CO NTROL — Wh en the thermostat calls
for heating, the MBB senses that W1 is On and closes the
HTR.1 relay. When the relay is closed, it sends power to W on
the IGC (integrated gas unit controller) board. An LED (lightemitting diode) on the IGC board will be on during normal
operation. A check is made to ensure that the rollout switch and
limit switch are closed. The induced-draft motor is then
energized. When speed is proven with the Hall Effect sensor on
the motor, the ignition activation period begins.
202
28
Page 29
The burners will ignite within 5 seconds. If the burners do
not light, there is a 22-second delay before another 5-second
attempt. If the burners still do not light, this sequence is repeated for 15 minutes. After the 15 minutes have elapsed, i f the
burners still have not ignited, heating is locked out. The control
will reset when the request for heat is temporarily removed.
When ignition occurs, the IGC board will continue to monitor the condition of the rollout switch, limit switches, Hall
Effect sensor, and the flame sensor. If the unit is controlled
through a room thermostat set for fan auto, 45 seconds after
ignition occurs the indoor-fan motor will be energized (and the
outdoor-air dampers will open to their minimum position). If
for some reason the overtemperature limit opens prior to the
start of the indoor fan blower, on the next attempt, the
45-second delay will be shortened to 5 seconds less than the
time from initi ation of heat to w hen th e limi t trip ped. Ga s will
not be interrupted to the burners and heating will continue.
Once modified, the fan on delay will not change back to
45 seconds unless power is reset to the control.
When additional heat is required and the MBB senses that
W2 is On, the MBB closes the HTR.2 relay and sends power to
the second stage of the main gas valve. If the thermostat
removes the call for W2, the unit will turn off HTR.2 (minimum on-time 2 minutes [MRT.H], minimum off-time 2 mi nutes [MOT.H]). If W1 is satisfied, the main base board will
open HTR.1 (minimum on-time 2 minutes and minimum
off-time 2 minutes), interrupting the flow of gas to the main
burners. The IGC also has a minimum on-time of 1 mi nute.
Therefore, in modes such as Service Test where the long minimum on-time and off-times are not enforced, the one minute
minimum on-time for the IGC will still be followed. If the unit
is controlled through a room thermostat set for fan auto, the
indoor-fan motor will continue to operate for an additional
45 seconds then stop. If the overtempera ture limit opens after
the indoor motor is stopped within 10 minutes of W becoming
inactive, on the next cycle the time will be extended by 15 seconds. The maximum delay is 3 minutes. Once modified, the
fan off delay will not change back to 45 seconds unless power
is reset to the control.
An LED indicator is provided on the IGC to monitor operation. The IGC is located by removing the heat section side
panel. See Fig. 4. During normal operation, the LED is continuously on. See Ta ble 26 for error codes.
If the user has selected Adaptive (see Cooling section) for
its thermostat mode, the algorithm will follow the configurable
delays for adding and removing stages. When adding additional heat stages, the delay is measured from whe n the last stage
was added (H.INC). When removing stages, the delay is measured from when the last stage was removed (H.DEC). Therefore, if W1 and W2 turn on simultaneously, the second stage
will turn on after a H.INC delay.
NOTE: If the mode is not Adaptive, then there are no delays
for adding and removing stages.
SPACE SENSOR CONTROL — During Space Sensor control, the electronic control uses information from the space sensor to determine the number of heat stages. Once the number of
stages needed for heating is determined, this information is
passed to the IGC by turning on either HTR.1 or HTR.1 and
HTR.2. See Thermostat Control section for description of IGC
operation.
NOTE: The jumper wire in the instal ler’s packer must be connected between R and W1 when using a T55, T56, or T58
device. See Fig. 1 and 2.
During Space Sensor control, two methods are used to add
stages of heat and two methods are used to subtract stages of
heat. The first method of adding and subtracting stages causes
the unit to operate around its configured steady state number of
stages. Fo r ex a m p le , if the correct numb er o f s t ag es is between
0 and 1, this method will cause the first stage to cycle. If the
correct number of stages is between 1 and 2, this method will
cause the second stage to cycle.
The second method of adding and subtracting stages causes
the unit to find the steady state number of stages. The first
method will not add or remove a stage of heating unless the
current Heat Demand (set point – SPT), corrected by the rate of
change in the Heat Demand, is greater than Heat Demand
Positive Level (HT.PD) or less than Heat Demand Negative
Level (HT.ND). The correction term is the Heat Thermal Lag
(H.LAG) multiplied by the change in the Heat Demand. Therefore, if the corrected current demand is in between –1.0 and
1.0, the number of stages will not change no matter how long
there has been a positive error. Because the corrected heat
demand incorporates the rate of change in heat demand, it will
have a tendency to add or remove stages earlier when the
temperature in the space is moving very rapidly, thereby
reducing overshoot.
Because the first method of adding or removing a stage of
heat is used to operate around the steady number of stages, this
method can not be used to add an additional stage until a stage
has been subtracted. Likewise, if this method has subtract ed a
stage, it can not be used again to subtract another stage until a
stage has been added.
The second method will add additional stages of heat whenever Heat Demand is greater than HT.PD + 0.5 and the heat demand is increasing at rate greater than 0.3 F per min. Additional stages of heat will be removed whenever the Heat Demand is
less than HT.ND – 0.5 and the heat demand is decreasing at
rate less than 0.3 F per min.
Table 26 — IGC LED Indications
ERROR CODELED INDICATION
Normal Operation
Hardware Failure
Fan On/Off Delay Modified
Limit Switch Fault
Flame Sense Fault
Five Consecutive Limit Switch Faults
Ignition Lockout Fault
Inducer Switch Fault
Rollout Switch Fault
Internal Control Fault
Software Lockout
LEGEND
IGC —
LED —
NOTES:
1. There is a 3-second pause between error code displays.
2. If more than one error code exists, all applicable error codes will
3. Error codes on the IGC will be lost if power to the unit is
Integrated Gas Unit Controller
Light-Emitting Diode
For 50HG units, the heat type will automatical ly be set to 2
for electric heat units if the electric heat was installed in the factory (HT.TY ). If elec tric heat is being i nstalled in the field, the
user must change HT.TY from 0 to 2. If a 15 kW heater is installed, N.HTR must be changed from 2 to 1.
Heat will not operate if the outdoor temperature is greater
than the heat lockout temperature (HT.LO).
THERMOSTAT CO NTROL — The first stage of electric
heat (HTR.1) will follow the W1 input and the second stage
(HTR.2) of heat will follow the W2 input. During auto fan, the
indoor fan will follow the HTR.1 output. During continuous
fan, the indoor fan will follow the G input.
29
Page 30
If the user has selected Adaptive (see Cooling section) for
thermostat mode, the algorithm will follow the configurable
delays for adding and removing stages. When adding additional heat stages, the delay is measured from whe n the last stage
was added (H.INC). When removing stages, the delay is measured from when the last stage was removed (H.DEC). Therefore, if W1 and W2 turn on simultaneously, the second stage
will turn on after a H.INC delay.
NOTE: If the mode is not Adaptive, then there are no delays
for adding and removing stages.
SPACE SENSOR CONTROL — During Space Sensor control, the electronic control uses information from the space
sensor to determine the number of heat stages. Once, the number of stages needed for heating is determined, either HTR.1 or
W1 and W2 outputs will be turned on. See Space Sensor
Control section for 48HG units.
NOTE: The jumper wire in the installer's pa cker must be connected between R and W1 when using a T55, T56, or T58
device. See Fig. 1 and 2.
Cooling —
pressor Lockout Temperature (MC.LO), then compressors will
not operate.
THERMOST AT CONTROL — There ar e three t yp e s o f thermostat control as defined by thermostat control type (T.CTL):
0 is referred to as Adaptive control, 1 is referred to as 1-stage
Y1, and 2 as 2-stage Y1. The preferred method of control is
Adaptive.
For both 1-stage Y1 and 2-stage Y1 control methods, the
adaptive control method is used whenever the ec onomizer c an
provide cooling, regardless of the selected control method.
This will ensure proper time delays and SAT control whe n the
economizer is cooling. If the economizer cannot provide cooling, then the 1-stage Y1 and 2-stage Y1 control methods follow
the thermostat inputs directly.
On two-compressor units (size 014 and 028 units), the
1-stage Y1 and 2-stage Y1 control methods are ide ntical and
the compressor outputs follow the thermostat inputs directly,
obeying the compressor minimum on-time (MRT.C) and
minimum off-time (MOT.C) (equal to 3 and 5 minutes,
respectively).
For 3-compressor units (size 016 to 024 units), Y1 will turn
on one stage when configured for 1-stage Y1, and two stages
when configured for 2-stage Y1. When Y2 is On, all three
stages will operate. The compressor must follow the minimum
on- and off-time requirements. If multiple compressor are
requested on or off simultaneously, the compressors will be
staged at a 5-second interval.
In Adaptive mode, thermostat cooling begins when the Y 1
input is energized. If the economizer is available for cooling,
the economizer will try to provide cooling as discussed in the
Economizer section. If the economizer is not available for cooling or the economizer has been at 100% for 5 minutes, compressor staging will begin when Y1 is energized.
For size 014 and 028 units, the compressor stages will follow the Y1 and Y2 inputs directly with a configurable delay
when adding stages (C.INC) and when removing stages
(C.DEC). Therefore, if Y1 and Y2 turn on simultaneously, the
second stage will turn on after a C.INC delay. In Adaptive
mode, a stage of compression cannot be turned on if the Supply
Air Temperature (SAT) is less than Minimum Supply Air
Temperature Upper Level (MIN.H). In addition, a stage of
compression will be removed if SAT is less than the Minimum
Supply Air Temperature Lower Level (MIN.L). If MIN.H and
MIN.L are configured so that they are close togethe r, the last
If the outdoor temperature is less than the Com-
stage of compressor might cycle rapidly, slowed only by its
minimum on- and off-time requirements.
For size 016 to 024 units, the algorithm must decide how to
map a two-stage thermostat to three stages of compression. The
staging algorithm uses information from Y1, Y2, and the
supply-air temperature to determine the number of stages. If
Y1 = OFF, then no compressors will operate unless they are
being forced to run in order to status their minimum on-time. If
Y1 = ON, then either 1 or 2 stages will operate. Finally, if
Y2 = ON, then after the C.INC delay times, the maximum
number of stages will operate. When only Y1 is ON, the unit
will decide to operate 1 or 2 stages of compression using the
following logic. When Y1 turns ON, the first stage of compressor will turn on immediately . The algorithms begin to count the
number of seconds since the last change in the number of
compressors (in this case, from 0 to 1). After the compressor
settling time (SAT.T) is reached, a reference value for SAT is
stored. If, while operating with only one compressor on, the
return temperature begins to rise, and therefore the SAT
temperature rises also, the second compressor will be added
when SAT is greater the SAT reference plus SAT positive
demand (SA.PD). After the second compressor has been added, another SAT reference value will be taken. The second
stage will be turned off when SAT is less than SAT reference
plus SAT negative demand (SA.ND). If at anytime Y2 is turned
ON, then the algorithm would immediately try to reach 3 stages following the C.INC requirement. If Y1 turns OFF, then all
the compressors will turn off after their minimum on-time has
been met.
SPACE SENSOR C ONTROL — To operate the unit in
Space Sensor mode, Unit Control Type must be set to Space
Sensor (3) and a wire must be added between R and W1 on
TB4. See Fig. 1 or 2.
While in space sensor control mode, the unit tries to maintain the Space Temperature (SPT) at one of 4 different set
points: the Occupied Cool Set Point (OCSP), the Unoccupied
Cool Set Point (UCSP), the Occupied Heat Set Point (OHSP),
or the Unoccupied Heat Set Point (UHSP). The building’s
occupancy is affected by a number of different factors. See
Occupancy Determination section on page 26. When the building is occupied, the occupied set points are active. When the
building is unoccupied, the unoccupied set points are active.
Because Space Sensor mode is an “Auto” mode, the control
will switch between cooling and heating to maintain t emperature. However, to minimize unnecessary cool to heat and heat
to cool changes, there is a 10-minute delay after the last stage
turns off before the control will switch modes.
T o maintain temperature while cooling, the unit will turn on
compressors as needed when the economizer is either unavailable or not providing enough cooling. Information from the
space sensor and the supply temperature sensor is used to
determine the number of necessary stages. The minimum
on-time for each compressor is 3 minutes (MRT.C). The minimum off-time is 5 minutes (MOT .C).
Because the unit contains 3 compressors, each with its own
circuit, there are 3 stages of cooling (the economizer is not
considered a stage of cooling even though it can provide cooling in certain situations). In general, the minimum time
between increasing stages is a configurable delay (C.INC). The
minimum time between decreasing stages is a configurable
delay (C.DEC).
The unit will request a stage of c ooling whenever t he Cool
Demand (SPT – set point) is greater than the SPT Cool Demand Positive Level (CL.PD) plus the change in Cool Demand
times the Cool Thermal Lag (C.LAG).
30
Page 31
Consider the following values: Cool Demand = 0.9, change
in Cool Demand = 0.2, Cool Thermal Lag = 1.0, and Cool
Demand Positive Level = 1.0. Because 0.9 + 0.2*1.0 is greater
than 1.0, a stage of cooling would be added. This method of
adding a stage can only be used after the compressor settling
time has expired (SAT.T) and trend in SAT is increasing or
slowly decreasing. This method of adding a stage of cooling
can not be used again until a stage of cooling has been
removed. Additional stages of cooling can be added whenever
Cool Demand is greater than CL.PD + 0.5 and the SAT is
increasing at rate greater than –0.3 F/min.
The unit will remove a stage of cooling whenever the Cool
Demand (SPT – set point) is less than the SPT Cool Demand
Negative Level (CL.ND) plus the change in Cool Demand
times the Cool Thermal Lag (C.LAG). Consider the following
values: Cool Demand = –0.9, change in Cool Demand = –0.2,
Cool Thermal Lag = 1.0, and Cool Demand Negative Level =
–1.0. Because –0.9 + –0.2*1.0 is less than –1.0, a stage of cooling would be removed. This method of removing a stage can
only be used after the compressor settling time has expired
(SAT.T) and the trend in SAT is decreasing or slowly increasing. This method of removing a stage of cooling cannot be used
again until a stage of cooling has been added. Additional stages
of cooling can be removed whenever the Cool – D emand is
less than CL.ND –0.5 and the SAT is increasing at rate less
than 0.2 F/min.
Space Temperature Sensor Calibration and
Tri m —
temperature sensor (SPT) can be calibrated. The sensor can be
calibrated by entering data using either the ComfortLink™ display or by using Service Tool. The SPT calibration information
is found under CALB submenu of Temperatures when using
the Scrolling Marquee, or under the maintenance table
SENS_CAL when using Service Tool. When using either
method, the user can calibrate the sensor by entering the correct
space temperature at SPT.C (display) or SPT_CAL (Service
Too l ). The s oftw are wil l a utom a tical ly ca lcu lat e the tri m v al ue
SPT.T (display) or SPT_OFF (Service Tool). The space temperature should be measured with an accurate temperature
measuring device. The user can also calibrate the sensor by entering the trim value directly. The trim value should be positive
when the SPT sensor is reading low and it should be negative
when the SPT is reading high.
calibrated. In general, the SPT should be calibrated only when
the space is near its expected operating temperature. If the calibration value is refused by either the Scrolling Marquee or its
CCN table, calibration is currently not being allowed by the
software. The SPT Trim can be set at any time.
→
Alarm Handling —
and alarms in the system. Alerts are indicated by TXXX
(where XXX is the alert number) on the display and generally
signify that the improperly functioning circuit can restart without human interaction. If an alarm occurs, indicated by AXXX
(where XXX is the alarm number), the damaged circuit will
generally not restart without an alarm reset via the Scrolling
Marquee display or CCN.
alarms depends on the seriousness of the particular alert or
alarm. In the mildest case, an alert does not affect the operation
of the unit in any manner. An alert can also cause a “strike.” A
“striking” alert will cause the circuit to shut down for 15 minutes. This feature reduces the likelihood of false alarms causing
a properly working system to be shutdown incorrectly. If three
strikes occur before the circuit has an opportunity to show that
it can function properly, the circuit will strike out, causing the
shutdown alarm for that parti cular circuit. Once activated, the
shutdown alarm can only be cleared via an alarm reset.
On units with V ersion 2.1 software or later , the space
If SP T if forced (T58 sensors) or failed, the sensor cannot be
There are a variety of different alerts
The response of the control system to various alerts and
However, circuits with strikes will be given an opportunity
to reset their strike counter to zero. As discussed above, a strike
typically causes the circuit to shutdown. Fifteen minutes lat er,
that circuit will once again be allowed to run. If the circuit is
able to run for 1 minute, its replacement circuit will be allowed
to shut down (if not required to run to satisfy requested stages).
However, the “troubled” circuit must run continuously for
5 minutes with no detectable problems before the strike counter
will be reset to zero.
Operators with CCN networks might not want to be notified
of “striking” alerts until a circuit has been shut down because
of three alerts. If the operator sets A.NOW (Alarm Now ) to
NO, alerts will not be announced until a circuit is permanently
shut down. This implies that alarm will not be broadcast on the
CCN network or listed on the display until a permanent shutdown alarm occurs.
The status of A.NOW is ignored during Service Test mode
because it is presumed that the service techni cian will want to
be notified of any alerts or alarms immediately. So as not to
confuse a monitor center, the words “SERVICE TEST” are
inserted into every alarm message while the unit is operating in
Service Test Mode. The alarm output relay can be configured
using the Scrolling Marquee under ALRM in the configuration
menu or by using the ALARMOUT table via Service Tool.
This configuration allows the user to decide whether or not the
alarm output will activate when a part icular set of alarms occurs. (See Appendix A, ALARMOUT table.)
TROUBLESHOOTING
The Scrolling Marquee display shows the actual operating
conditions of the unit while it is running. If there are alarms or
there have been alarms, they will be displayed in either the
current alarm list or the history alarm list. See Tables 21 and
27. The Service Test mode allows proper operation of the
compressors, fans, and other components to be checked while
the unit is not operating. See Service Test on page 12.
Complete Unit Stoppage —
tions that can cause the unit not to provide heating or cooling:
•If an alarm is active which causes the unit to shut down,
diagnose the problem using the information provided in
Alarms and Alerts section below.
•Cooling and heating loads are satisfied.
•Programmed schedule.
•General power failure.
•Tripped CB1, CB2 or CB3 (24-volt transformer circuit
breakers).
•Blown fuse (1 or 2).
•Unit is turned off through the CCN network.
•If unit cannot cool, supply air temperature may be less
than variable MIN.L (Default = 48 F).
Single Circuit Stoppage —
incorrectly, there are several possible causes. The problem
should be investigated using information from the alarm list.
See Tabl e 27.
Service Analysis —
found in T ables 28, 29, and 30 and in Fig. 13.
Restart Procedure —
machine, check the alarm list to determine the cause of the
shutdown. If the shutdown alarm for a particular circuit has
occurred, determine and correct the cause before allow ing the
unit to run under its own control again. When there is problem,
the unit should be diagnosed in Service Test mode. The alarms
must be reset before the circuit can operate in either Normal
mode or Service Test mode.
Detailed service analysis can be
Before attempting to restart the
There are several condi-
If a single circuits stops
31
202
Page 32
Alarms and Alerts —
abnormal or fault conditions, and may cause either one circuit
or the entire unit to shut down. They are assigned code
numbers and descriptions as described below. The description
for an alarm can be viewed from the Scrolling Marquee display
by pressing and keys simultaneously
while displaying the alarm code number. Be sure to expand the
description for each alert a nd alarm, because in some cases,
there are different possible descriptions for each number.
T able 27 contains a detailed description of each alarm and alert
code error and possible cause. Possible actions taken by the
electronic controls are:
•nothing
•adding a “strike” to the strike counter for a particular
circuit
•shutting down a circuit
•shutting down the unit.
When a “strike” is added, the circuit is shut down for
15 minutes. After 3 strikes, the circuit will be permanently shut
down until the alarms are reset via the Scrolling Marquee
display. More i nformation concerning alarm handling can be
found in Alarm Handling on page 31.
DIAGNOSTIC ALARM CODES AND POSSIBLE
CAUSES
→
Alert Codes 51, 55 and 59 (Compressor Safety)
codes 51, 55, and 59 are for compressors A1, B1, and C1, re spectively. These alerts occur when the Current Sensor (CS)
does not detect compressor current during compressor operation. When this occurs, the control turns off the compressor and
logs a strike for the respective circuit. These alerts reset
automatically.
The possible causes are:
1. High-pressure switch (HPS) open. The HPS-pressure
switch is wired in series with compressor relays on the
MBB. If the high-pressure switch opens during compressor operation, the compressor stops, and the CS no longer
detects current, causing the control to activate this alert.
2. Compressor internal protection is open.
3. Wiring error . A wiring error might not allow the compressor to start.
T o check out alerts 51, 55 and 59:
1. Turn on the compressor in question using Service Test
mode. If the compressor does not start, then most l ikely
the problem is one of the following: HPS open, open internal protection, incorrect safety wiring, or incorrect
compressor wiring.
2. If the compressor starts, verify that the indoor and outdoor fans are operating properly.
3. If the CS is always detecting current, then verify that the
compressor is on. If the compressor is on, check the contactor and the relay on the MBB. If the compressor is off
and there is no current, verify CS wiring and replace if
necessary.
4. Return to Normal mode and observe compressor operation to verify that compressor current sensor is working
and condenser fans are energized after compressor starts.
Alert Codes 51, 55 and 59 (Current Detected After Turnoff)
— Alert codes 51, 55, and 59 are for compressors A1, B1, and
C1, respectively. These alerts occur when the Current Sensor
(CS) detects current when the compressor should be off. When
this occurs, the control turns off the compressor and logs a
strike for the respective circuit. Use the Scrolling Marquee to
reset the alert.
ESCAPE
Alarms and alerts are warnings of
ENTER
— Alert
The possible causes are
1. W elded contactor.
2. Frozen compressor relay on MBB.
T o check out alerts 51, 55 and 59:
1. Place the unit in Service Test Mode. All compressors
should be Off.
2. Verify that there is not 24V at the contactor coil. If there is
24V at the contactor, check relay on MBB and wiring.
3. Check for welded contactor.
4. Verify CS wiring.
5. Return to Normal mode and observe compressor operation to verify that compressor current sensor is working
and condenser fans are energized after compressor starts.
Alert Codes 64, 65 and 80 (Condensing Temp. Failure)
Alert codes 64, 65, and 80 are for circuits A , B and C, respectively. These alerts occur when the temperature is outside the
range –40 to 240 F (–40 to 116 C). When this occurs, the
control uses the outdoor temperature to control the outdoor
fans. If the outdoor temperature is greater than 40 F, t h e circuit
will run at Fan Level 2. If t he outdoor temperature is less t han
35 F , the circuits will run at Fan Level 1. If the outdoor-air sensor is also bad, the circuit will be locked out, otherwise this
alert resets automatically.
The cause of the alert is usually a faulty thermistor, a
shorted or open thermistor caused by a wiring error, or a loose
connection.
Alert Code 73 (Outside Air Temp. Failure)
when the temperature is outside the range –40 to 240 F (–40 to
116 C). This alert resets automatically. The cause of the alert is
usually a faulty thermistor, a shorted or open thermistor caused
by a wiring error, or a loose connection.
Alert Code 74 (Space Temp. Failure)
when the temperature is outside the range –40 to 240 F (–40 to
116 C). This alert will only occur if the unit is in Space Sensor
Mode. The unit will shut down if this alert occurs while in
Space Sensor mode. This al ert resets automa tically. The cause
of the alert is usually a faulty thermistor in the T55, T56, or
T58 device, a shorted or open thermistor caused by a wiring error, or a loose connection.
→
Alert Code 75 (Supply Air Temp. Failure)
when the temperature is outside the range –40 to 240 F (–40 to
116 C). This alert resets automatically. The cause of the alert is
usually a faulty thermistor, a shorted or open thermistor caused
by a wiring error, or a loose connection.
codes 92, 93, and 101 are for circuits A, B and C, respectively.
These alerts occur when the pressure is outside the range 0.5 to
134.5 psig. A circuit cannot run when this alert is active. U se
the Scrolling Marquee to reset the alarm. The cause of the alert
is usually a faulty transducer, faulty 5-V power supply, or a
loose connection.
Alert Codes 102, 103, 104 (Current Sensor Failure)
codes 102, 103, and 104 are for compressors A1, B1, and C1,
respectively. These alerts occur when the output of the current
sensor (CS) is a constant high value. These alerts reset automatically. The cause of the alert is a wiring error or a loose connection. If the problem cannot be resolved and the CS board
must be replaced, the CS board can be temporarily disabled
while securing a replaced board. A CS board is disabled by setting the corresponding configuration to DISABLE (CS.A1,
CS.B1 or CS.C1).
— This alert oc curs
— This alert occurs
— This alert occurs
— See Alert 64.
— Alert
— Alert
—
202
32
Page 33
Alert Codes 110, 111, 140 (Loss of Charge)
110, 111, and 140 are for circuits A, B and C, respectively.
These alerts occur when the compressor is OFF and the suction
pressure < 5 psig and OAT > –5 F for 1 continuous minute. Use
the Scrolling Marquee to res et the alert. The cause of the al ert
is usually low refrigerant pressure or a faulty suction pressure.
These alerts only occur when the compressor is OFF because
the low refrigerant pressure alarms (alerts 133, 134 and 141)
handle this situation when the compressor is operating.
→
Alert Codes 126 , 127, 14 2 (Hi gh Ref rige rant Pres sure)
codes 126, 127, and 142 are for circuits A, B, and C, respectively. These alerts occur when alerts 51, 55, or 59 are active
while the appropriate condensing temperature is greater than
150 F. Thes e alert s reset automat ically. The cause of the alarm
is usually an overcharged system, high outdoor ambient temperature coupled with dirty outdoor coil, plugged filter drier , or
a faulty high pressure switch. See Alerts 51, 55 and 59 for diagnostic procedure.
Alert Codes 133, 134, 141 (Low Refrigerant Pressure)
codes 133, 134, and 141 are f or c irc uits A, B and C, res pectively. These alerts occur when the compressor is operating and the
evaporating temperature (converted from the suction pressure)
is less than 20 F for 5 minutes , 15 F for 3 minutes, or 10 F for
1.5 minutes. When the outdoor temperature is less than 40 F , the
above values are reduced by an o ffset that scales between 0 and
10 as the outdoor temperature goes from 40 to 0° F. These alerts
cause a strike for the respective circuit. These alerts will activate
when the coil becomes frosted. However, during the 15-minute
reset period, the coils will thaw and strike should clear at restart
if there is nothing else wrong with the circuit. The alert resets
automatically. The cause of the alert is usually low refrigerant
charge, dirty filters, evaporator fan operating backwards, loose
or broken belt, plugged filter drier, faulty transducer, excessively cold return air, or stuck open economizer when the ambient
temperature is low.
codes 143, 144, and 145 are for circuits A, B, and C, respectively. These alerts occur when the compressor turns on and the
suction pressure does not drop 5 psig during the first 15 seconds and the condensing temperature does not rise 5 F during
the first minute. These alerts cause a s trike for the respective
circuit. The alert resets automatica lly. The cause of the alert is
usually compressor wiring causing reverse rotation or a faulty
compressor.
Alarm Codes 163, 164, 165 (Circuit Failure)
163, 164, and 165 are for circuits A, B, and C, respectively.
These alarms occur when a circuit has 3 strikes. Use the
Scrolling Marquee display to reset the a larm. Investigate the
alarm that caused the strikes to occur.
Alert Code 179 (Com. Failure with ECB)
when the MBB cannot communicate with the ECB. This is
usually caused by a wiring problem. Investigate using the Low
Voltage Schematic.
Alert Codes 180 (Com. Failure with Economizer Actuator)
This alert occurs when the MBB cannot communicate with the
— See Alert 110.
— Alert codes
— Alert
— See Alert 133.
— See Alert 126.
— Alert
— Alarm codes
— This aler t occurs
— Alert
—
Belimo Actuator. This is usually caused by a wiring problem.
Investigate using the Low Voltage Schematic.
Alarm Code 404 (Fire Shutdown)
the shutdown input is either open or closed depending upon its
configuration. This alarm is usually caused by an auxiliary
device that is trying to shut down the unit, e.g., smoke detector.
The configuration for this switch input can be found at variable
FS.SW. Verify t hat the configuration is set correct, verify the
wiring and auxiliary device. This alarm resets automatically .
Alert Code 408 (Dirty Air Filter)
the Filter Status switch senses a plugged filter for 120 continuous seconds after the indoor fan has been running for 10 seconds. Because the Dirty Air Filter switch can be configured
normally opened or closed, the switch might be open or closed.
The configuration for this switch input can be found at variable
FL.SW. Verify that the configuration is set correct, verify the
wiring and filter status switch. The hose should be connected to
the low side of the switch. This alert resets automatically.
Alert Code 409 (Fan Status Switch On, Fan Contactor
Off) — This alarm occurs when the fan status switch has
sensed that the indoor fan has been on for 10 seconds and the
indoor fan feedback has determined that the indoor fan should
be off. Because the Fan Status switch can be configured normally opened or closed, the switch might be open or closed.
The configuration for this switch input can be found at Scrolling Marquee: Configuration mode, UNIT submode, FN.SW.
Verify that the configuration is set correctly. Verify the wiring
and fan status switch. The hose should be connected to the high
side of the switch. If the IDF is configured to shut down the
unit when this alarm occurs (Scrolling Marquee: Configuration
mode, UNIT submode, IDF .F = YES), then this alarm can only
be reset manually and the unit is shut down. I f the IDF is not
configured to shut the unit down when this alarm occurs
(Scrolling Marquee: Configuration mode, UNIT submode,
IDF.F = NO), then this alarm resets automatically and no specific control action is taken.
→
Alert Code 409 (Fan Status Switch Off, Fan Contactor
On) — This alert occurs when the fan status switch has sensed
that the indoor fan has been off for 10 seconds and the indoor
fan feedback has determined that the indoor fan should be on.
Because the Fan Status switch can be configured normally
opened or closed, the switch might be open or closed. The configuration for this switch input can be found at Scrolling Marquee: Configuration mode, UNIT submode, FN.SW. Verify
that the configuration is set correctly. Verify the wiring and fan
status switch. The hose should be connected to the high side of
the switch. If the IDF is configured to shut down the unit down
when this alert occurs (Scrolling Marquee: Configuration
mode, UNIT submode, IDF .F = YES), then this alarm can only
be reset manually and the unit is shut down. I f the IDF is not
configured to shut the unit down when this alert occurs (Scrolling Marquee: Configuration mode, UNIT submode, IDF.F =
NO), then this alert resets automatically and no specific control
action is taken.
Alert Code 409 (Fan Feedback On When Not Expected)
This alert occurs when the Fan Fe edback signal has been On
for more than 5 seconds yet the Fan Power relay is Off. Verify
wiring.
— This alarm occurs when
— This alert occurs when
—
33
202
Page 34
Alert Code 409 (Fan Feedback Off When Not Expected)
This alert occurs when the IDF has been on for more than
15 seconds yet the Fan Feedback is Off. Verify wiring.
Compressors will not be allowed to run until this alert clears.
Check for errors on the IGC which might have caused the IDF
to turn off.
Alert Code 410 (R-W1 Jumper Not Installed in Spare Temp
Mode) — This alert occurs when the control mode is Space
Tem perature Mode via Auto Select or Spa ce Temp Select yet
there is no power to W1. Verify that space temperature mode is
the desired mode or add jumper between R and W1. This alert
resets automatically.
→
Alert Code 410 (R-W1 Jumper Must be Installed to Run
Heat in Service Test) — This alert occurs when a request for a
heat output has occurred yet the W1 input is not high. A jumper
must be installed between R and W1 when trying to test heat in
Service Test. The alert will clear when Service Test is exited or
if another Service Test mode is selected. Remove jumper when
done using Service Test if the unit is operating with a Thermostat. The jumper should only be left in place if the unit is operating with a Space Temperature Probe.
Alert Code 411 (Y2 without Y1)
Thermostat Mode when Y2 is energized and Y1 is not. Verify
thermostat and thermostat wiring. When Y2 turns On, the software will behave as if Y1 and Y2 are both On. When Y2 turns
Off, the software will behave as if Y1 and Y2 are both Off.
This alert resets automatically when Y1 is turned On.
Alert Code 412 (W2 without W1)
Thermostat Mode when W2 is energized and W1 is not. Verify
thermostat and thermostat wiring. When W2 turns On, the software will behave as if W1 and W2 are both On. When W2
turns Off, the software will behave as if W1 and W2 a re both
Off. This alert resets automatically when W1 is turned On.
Alert Code 413 (Y and W Simultaneously)
occurs in Thermostat Mode when Y1 or Y2 is energized simultaneously with W1 or W2. Verify thermostat and thermostat
— This alert occurs in
— This alert occurs in
— This alert
—
wiring. The software will enter either the cooling or heating
mode depending upon which input turned on first. This alert
resets automatically when Y1 and Y2 are not on simultaneously with W1 and W2.
Alert Code 414 (Economizer Damper Actuator Out of Calibration) — This alert occurs when the economizer range of
motion is less than 90 degrees. Initiate economizer calibration
(E.CAL) using the Service Test menu. The economizer calibration procedure will try to find new maximum open and closed
positions. If the alert does not clear automatically after the calibration procedure is complete, investigate what is limiting
economizer rotation. This alert resets automatically.
Alert Code 414 (Economizer Damper Actuator Torque
Above Load Limit) — This alert occurs when the actuator
load is too high. Investigate to determine what is increasing
damper load . Th is aler t r eset s a utom ati cal ly.
Alert Code 414 (Economizer Damper Actuator Hunting
Excessively) — This alert occurs when the commanded
damper position is changing too rapidly. This alert resets
automatically.
Alert Code 414 (Economizer Damper Stuck or Jammed)
This alarm occurs when the actuator senses it can no longer
move. Investigate what is stopping the rotation of the actuator
and fix. This alert resets automatically.
Alert Code 414 (Economizer Damper Actuator Mechanical
Failure) — This alert occurs when the actuator senses a catastrophic failure. Investigate actuator and replace if necessary.
This alert r es ets a utom ati cal ly.
Alert Code 414 (Economizer Damper Actuator Direction
Switch Wrong) — This alert occurs when the economizer
damper direction switch is in the wrong position. The direction
switch should be in the clockwise position and the actuator
should be mounted so that the CW face of the actuator is accessible. Correct if necessary. This alert clears automatically.
—
202
34
Page 35
→
ALARM OR
ALERT
NUMBER
T051
T055
T059
T064
T065
T073
T074
T075
T080
T092
T093
T101
T102
T103
T104
T110
T111
T126
T127
T133
T134
T140
T141
T142
T143
T144
T145
A163
A164
A165
T179
T180
A404
T408
T409
T410
T411
T412
T413
T414
ECB —
IGC —
MBB —
OAT —
Table 27 — Alarm Codes
DESCRIPTION
Compressor A1 Safety TripAdd Strike for Circuit AAutomaticHigh-pressure switch open. Check for T126 Compressor internal pro-
Compressor A1 Current Detected After TurnoffTurn off all compressorsAutomaticWelded contactor
Compressor B1 Safety TripAdd Strike for Circuit BAutomaticHigh-pressure switch open. Check for T127 Compressor internal pro-
Compressor B1 Current Detected After TurnoffTurn off all compressorsAutomaticWelded contactor
Compressor C1 Safety TripAdd Strike for Circuit CAutomaticHigh-pressure switch open. Check for T142 Compressor internal pro-
Compressor C1 Current Detected After TurnoffTurn off all compressorsAutomaticWelded contactor
Circuit A Saturated Condensing Temp Thermistor
Failure
Circuit B Saturated Condensing Temp Thermistor
Failure
Outdoor Air Temperature Thermistor Failure—AutomaticFaulty, shorted, or open thermistor caused by wiring error or loose
Space Temperature Thermistor FailureUnit shutdownAutomaticFaulty, shorted, or open thermistor caused by wiring error or loose
Supply Air Temperature T hermistor Failure—AutomaticFaulty, shor ted, or open thermistor caused by wiring error or loose
Circuit C Saturated Condensing Temp Thermistor
Failure
Circuit A Suction Pressure Transducer FailureShutdown Circuit AManualFaulty transducer, faulty 5-V power supply, or loose connection
Circuit B Suction Pressure Transducer FailureShutdown Circuit BManualFaulty transducer, faulty 5-V power supply, or loose connection
Circuit C Suction Pressure Transducer FailureShutdown Circuit CManualFaulty transducer, faulty 5-V power supply, or loose connection
Compressor A1 Current Sensor Failure—AutomaticFaulty current sensor caused by wiring error or loose connection
Compressor B1 Current Sensor Failure—AutomaticFaulty current sensor caused by wiring error or loose connection
Compressor C1 Current Sensor Failure—AutomaticFaulty current sensor caused by wiring error or loose connection
Circuit A Loss of ChargeShutdown Circuit AManualLow refrigerant or faulty suction pressure transducer
Circuit B Loss of ChargeShutdown Circuit BManualLow refrigerant or faulty suction pressure transducer
Circuit A High Refrigerant PressureShutdown Circuit AAutomaticAn overcharged system, high outdoor ambient temperature coupled
Circuit B High Refrigerant PressureShutdown Circuit BAutomaticAn overcharged system, high outdoor ambient temperature coupled
Circuit A Low Refrigerant PressureAdd Strike for Circuit AAutomaticLow refrigerant charge, dirty filters, evaporator fan turning backwards,
Circuit B Low Refrigerant PressureAdd Strike for Circuit BAutomaticLow refrigerant charge, dirty filters, evaporator fan turning backwards,
Circuit C Loss of ChargeShutdown Circuit CManualLow refrigerant or faulty suction pressure transducer
Circuit C Low Refrigerant PressureAdd Strike for Circuit CAutomaticLow refrigerant charge, dir ty filters, evaporator fan turning backwards,
Circuit C High Refrigerant PressureShutdown Circuit CAutomaticAn overcharged system, high outdoor ambient temperature coupled
Circuit A Failure To PressurizeAdd Strike for Circuit AAutomaticWiring causing reverse rotation or faulty compressor
Circuit B Failure To PressurizeAdd Strike for Circuit BAutomaticWiring causing reverse rotation or faulty compressor
Circuit C Failure To PressurizeAdd Strike for Circuit CAutomaticWiring causing reverse rotation or faulty compressor
Circuit A Down Due to FailureShutdown Circuit AManualCircuit has 3 strikes or has been locked out by another alarm
Circuit B Down Due to FailureShutdown Circuit BManualCircuit has 3 strikes or has been locked out by another alarm
Circuit C Down Due to FailureShutdown Circuit CManualCircuit has 3 strikes or has been locked out by another alarm
Loss of communication with the Economizer
Control Board
Loss of communication with the Economizer
Actuator
Fire ShutdownUnit ShutdownAutomaticSmoke detected by smoke detector
Dirty Filter—AutomaticDirty Filter
Fan Status Switch ON, Contactor OFFIf IDF.F = Yes, then Unit ShutdownIf IDF.F = YES,
Fan Status Switch OFF, Contactor ONIf IDF.F = Yes, then Unit ShutdownIf IDF.F = YES,
Fan Feedback ON when not Expected—AutomaticBad relay.
Fan Feedback OFF when not ExpectedCompressors will not operateAutomaticBad IGC, wiring problem, or bad MBB relays.
R-W1 Jumper Not Installed in Space Temp ModeUnable to run heatAutomaticMissing jumper wire
R-W1 Jumper Must Be Installed to Run Heat In
Service Test
Thermostat Y2 Input Activated without Y1
Activated
Thermostat W2 Input Activated without W1
Activated
Thermostat Y and W Inputs Activated
Simultaneously
Economizer Damper Actuator Out of CalibrationAler t GeneratedAutomaticCalibrate economizer (E.CAL). If problem still exist then determine
with dirty outdoor coil, plugged filter drier, or a faulty high-pressure
switch.
with dirty outdoor coil, plugged filter drier, or a faulty high-pressure
switch.
loose or broken fan belt, plugged filter drier, faulty transducer, excessively cold return air, or stuck open economizer when the ambient
temperature is low.
loose or broken fan belt, plugged filter drier, faulty transducer, excessively cold return air, or stuck open economizer when the ambient
temperature is low.
loose or broken fan belt, plugged filter drier, faulty transducer, excessively cold return air, or stuck open economizer when the ambient
temperature is low.
with dirty outdoor coil, plugged filter drier, or a faulty high-pressure
switch.
Bad Fan Status Switch.
Configuration incorrect.
Tripped Circuit Breaker.
Broken belt.
Bad indoor fan motor.
Configuration incorrect. Bad fan status switch.
what is limiting economizer rotation.
35
202
Page 36
→
PROBLEM CAUSEREMEDY
Compressor and fan will not
start.
Compressor cycles (other than
normally satisfying thermostat).
Compressors operates
continuously.
Excessive head pressures.
Condenser fans not operating.
Excessive suction pressure.
Suction pressure too low.
LEGEND
CB —
TXV —
Circuit Breaker
Thermostatic Expansion Valve
Table 28 — Cooling Service Analysis
Power failure.Call power company.
Fuse blown or circuit breaker tripped. Check CB1,
CB2, and CB3.
Disconnect off.Power disconnect.
Compressor time guard to prevent short cycling.Check using
Thermostat or occupancy schedule set point not call-
ing for Cooling.
Outdoor temperature too low.Check Compressor Lockout Temperature (MC.LO)
Active alarm.Check active alarms using
Insufficient line voltage.Determine cause and correct.
Active alarm.Check active alarms using
Unit undersized for load.Decrease load or increase of size of unit.
Thermostat or occupancy schedule set point too low. Reset thermostat or schedule set point.
Dirty air filters.Replace filters.
Low refrigerant charge.Check pressure, locate leak, repair evacuate, and
Condenser coil dirty or restricted.Clean coil or remove restriction.
Loose condenser thermistors.Tighten thermistors.
Dirty condenser coil.Clean coil.
Refrigerant overcharge.Recover excess refrigerant.
Faulty TXV.1. Check TXV bulb mounting and secure tightly to
Condenser air restricted or air short cycling.Determine cause and correct.
Restriction in liquid tube.Remove restriction.
No Power to contactors.Fuse blown or plug at motor loose.
High heat load.Check for sources and eliminate
Faulty TXV.1. Check TXV bulb mounting and secure tightly to
Refrigerant overcharged.Recover excess refrigerant.
Dirty air filters.Replace air filters.
Low refrigerant charge.Check for leaks, repair, and recharge.
Faulty TXV.1. Check TXV bulb mounting and secure tightly to
Insufficient evaporator airflow.Check belt tension. Check for other restrictions.
Temperature too low in conditioned area (low return-
air temperature).
Replace fuse or reset circuit breaker.
Comfor t
Link™ Scrolling Marquee.
Check using
using
Marquee.
Marquee.
recharge.
suction line and insulate.
2. Replace TXV (and filter drier) if stuck open or
closed.
suction line and insulate.
2. Replace TXV (and filter drier) if stuck open or
closed.
suction line and insulate.
2. Replace TXV (and filter drier) if stuck open or
closed.
Reset thermostat or occupancy schedule.
Comfor t
Comfort
Link Scrolling Marquee.
Link Scrolling Marquee.
Comfor t
Link Scrolling
Comfor t
Link Scrolling
202
36
Page 37
PROBLEM CAUSEREMEDY
Burners will not ignite.
Inadequate Heating.
Poor flame characteristics.
Burners will not turn off.
Table 29 — Gas Heating Service Analysis
Active alarm.Check active alarms using
No power to unit.Check power supply, fuses, wiring, and circuit breakers.
No power to IGC (Integrated Gas Control).Check fuses and plugs.
Heaters off due to time guard to prevent short
cycling.
Thermostat or occupancy schedule set point not
calling for Cooling.
No gas at main burners.Check gas line for air and purge as necessary. After purg-
Water in gas line.Drain water and install drip.
Dirty air filters.Replace air filters.
Gas input too low.Check gas pressure at manifold. Refer to gas valve adjust-
Thermostat or occupancy schedule set point only
calling for W1.
Unit undersized for load.Decrease load or increase of size of unit.
Restricted airflow.Remove restriction.
Too much outdoor air.Check economizer position and configuration. Adjust mini-
Limit switch cycles main burners.Check rotation of blower, thermostat heat anticipator set-
Incomplete combustion (lack of combustion air)
results in: Aldehyde odors, CO, sooting flame, or
floating flame.
Unit is in Minimum on-time.Check using
Unit running in Service Test Mode.Check using
Marquee.
Check using
Check using
ing gas line of air, allow gas to dissipate for at least 5 minutes before attempting to re-light unit.
ment in Installation, Start-up, and Service Manual.
Allow time for W2 to energize.
mum position using
tings, and temperature rise of unit. Adjust as needed.
Check all screws around flue outlets and burner compart-
ment. Tighten as necessary.
Cracked heat exchanger, replace.
Over-fire unit reduce input. Adjust gas line or manifold
pressure.
Check vent for restriction. Clean as necessary.
Check orifice to burner alignment.
Comfor t
Comfor t
Comfor t
Comfor t
Comfor t
Link™ Scrolling
Link Scrolling Marquee.
Link Scrolling Marquee.
Comfort
Link Scrolling Marquee
Link Scrolling Marquee.
Link Scrolling Marquee.
.
No Heat.
Table 30 — Electric Heating Service Analysis
PROBLEM CAUSEREMEDY
Power failure.Call power company.
Fuse blown or circuit breaker tripped. Check CB1,
CB2, and CB3.
Thermostat occupancy schedule set point not call-
ing for Heating.
No 24 VAC at primary contactor.Check transformer and circuit breaker.
No power (high voltage) to L2 of primary contactor. Check safety switches “one-shot” backup and auto limit.
Bad electrical elements.Power off unit and remove high voltage wires. Check resis-
Replace fuse or reset circuit breaker.
Check using
tance of heater, replace if open.
Comfort
Link Scrolling Marquee.
37
Page 38
LEGEND
IDM —
IGC —
NOTE: Thermostat Fan Switch in the
“AUTO” position.
Induced-Draft Motor
Integrated Gas Unit Controller
Fig. 13 — IGC Control (Heating and Cooling)
38
Page 39
Thermistor Troubleshooting —
trol uses five 5K-thermistors (T1 through T5) to sense temperatures used to control operation of the unit. See Fig. 1 or 2.
Resistances at various temperatures ar e listed in Tables 31 and
32. Thermistor pin connection points are shown in T abl e 2. The
locations of the thermistors are shown on Fig. 4. When replacing thermistors T3 through T5, reuse the original hardware.
These thermistors must be clamped tightly to the hairpins of
the condenser.
The T55, T56, and T58 space temperature sensors use 10K
thermistors. Resistances at vari ous temperatures are listed in
T ables 33 and 34.
THERMISTOR/TEMPERATURE SENSOR CHECK — A
high quality digital volt-ohmmeter is required to perform this
check.
1. Connect the digital voltmeter across the appropriate thermistor term ina ls at the J8 terminal st rip o n the M a in Base
Board (see Fig. 1).
2. Using the voltage reading obtained, read the sensor temperature from Tables 31-34.
3. To check thermistor accuracy, measure temperature at
probe location with an accurate thermocouple-type
temperature-measuring instrument. Insulate thermocouple to avoid ambient temperatures from influencing reading. Temperature measured by thermocouple and temperature determined from thermistor voltage reading should
be close, 5 F (3 C) if care was taken in applying the rmocouple and taking readings.
If a more accurate check is required, unit must be shut down
and thermistor removed and checked at a known temperature
(freezing point or boiling point of water) using either voltage
drop measured across thermistor at the J8 terminal, or by determining the resistance with unit shut down and thermistor disconnected from J8. Compare the values determined with the
value read by the control in the Temperatures mode using the
Scrolling Marquee display .
Transducer Troubleshooting —
trol uses 3 suction pressure transducers to measure the suction
The electronic con-
The electronic con-
pressure of circuits A, B, and C. The pressure/voltage characteristics of these transducers are in shown in Table 35. The
accuracy of these transducers can be verified by connecting an
accurate pressure gage to the second refrigerant port in the
suction line.
START-UP
IMPORTANT: Do not attempt to start unit, even
momentarily, until all items on the Start-Up Checklist (in
installation instructions) and the following steps have
been completed.
1. Verify unit has been instal led per t he Installation Instructions included in the unit installation packet.
2. Verify that all auxiliary components (thermostat, sensors,
controls, etc.) have been in stalled and wired to the unit
control box per these instructions, the unit Installation
instructions, and the unit wiring label diagrams.
3. Set any control configurations that are required (fieldinstalled accessories, etc.). The unit is factory configured
for all appropriate factory-installed options with the
applicable controls, pre-programmed to the default
values. See Table 16 and Table 17 for additional information on setting configurations.
4. Enter unit set points. The unit is shipped with the set point
default values. If a different set point is required, change
per directions in Tables 12 and 13.
5. Configure the Occupancy schedule.
6. Verify that the control time periods programmed meet
current requirements.
7. Check all electrical connections to be sure that they are
tight.
8. Start unit using Service Test mode to veri fy operation of
all major components.
Compressor Min On Time
Compressor Min Off Time
Runtime to Reset Strikes
Cool Stage Decrease Rate
Cool Stage Increase Rate
Fan-off Delay, Mech Cool
Invert Evaporators
Alert Each Strike
Suction OK Temperature
Low Suction — Level 1
Low Suction — Level 2
Low Suction — Level 3
Heat Minimum On Time
Heat Minimum Off Time
Heat Stage Decrease Rate
Heat Stage Increase Rate
Fan-off Delay, Elec Heat
Fan-off Delay, Gas Heat
SAT Cool Demand (+) Level
SAT Cool Demand (–) Level
SAT Settling Time
Minimum SAT Upper Level
Minimum SAT Lower Level
A1 Current Sensing
Circuit A Evaporator Pos
Circuit A Level 1 Fans
A Fan Lev1 ON Pressure
A Fan Lev1 OFF Pressure
Circuit A Level 2 Fans
A Fan Lev2 ON Pressure
A Fan Lev2 OFF Pressure
B1 Current Sensing
Circuit B Evaporator Pos
Circuit B Level 1 Fans
B Fan Lev1 ON Pressure
B Fan Lev1 OFF Pressure
Circuit B Level 2 Fans
B Fan Lev2 ON Pressure
B Fan Lev2 OFF Pressure
C1 Current Sensing
Circuit C Evaporator Pos
Circuit C Level 1 Fans
C Fan Lev1 ON Pressure
C Fan Lev1 OFF Pressure
Circuit C Level 2 Fans
C Fan Lev2 ON Pressure
C Fan Lev2 OFF Pressure
DESCRIPTIONSTATUSDEFAULTUNITSPOINT
Economizer Control Board Installed
Economizer Min Position
Econ High Temp Lockout
Econ Low Temp Lockout
Unoccupied Free Cooling
Economizer Travel Time
Bottom Stage Max Econmzr
Middle Stage Max Econmzr
Top Stage Max Econmzr
Economizer PID Deadband
Economizer PID – kP
Economizer PID – kI
Economizer PID – kD
Economizer PID – rate
DESCRIPTIONSTATUSDEFAULTUNITSPOINT
Occupied Cool Set point
Occupied Heat Set point
Unoccupied Cool Set point
Unoccupied Heat Set point
Heat-Cool Set point Gap
Enable/DisableDisable : NO FIOP
0 – 10025%PE1_POS
0 – 10075%PE2_POS
0 = Not Installed
1 = Normally Open
2 = Normally Closed
DESCRIPTIONSTATUSUNITSPOINTFORCIBLE
UNIT:
Currently Occupied
Supply Air Temperature
Outdoor Air Temperature
Space Temperature
Space Temperature Offset
Cooling Demand
Heating Demand
Unit Shutdown Input
Fan Status
Filter Status
Remote Occupancy Input
Indoor Fan
Indoor Fan Feedback
Indoor Fan Power
Outdoor Fan Contactor 1
Outdoor Fan Contactor 2
Outdoor Fan Contactor 3
CIRCUIT A:
Saturated Suct Temp A
Saturated Suct Press A
Saturated Cond Temp A
Saturated Cond Press A
Compressor A1
A1 Current Sensor
A1 Timeguard (secs)
Circuit A Fan Level
Circuit A Strikes
CIRCUIT B:
Saturated Suct Temp B
Saturated Suct Press B
Saturated Cond Temp B
Saturated Cond Press B
Compressor B1
B1 Current Sensor
B1 Timeguard (secs)
Circuit B Fan Level
Circuit B Strikes
CIRCUIT C:
Saturated Suct Temp C
Saturated Suct Press C
Saturated Cond Temp C
Saturated Cond Press C
Compressor C1
C1 Current Sensor
C1 Timeguard (secs)
Circuit C Fan Level
Circuit C Strikes
Outdoor Air is Cool
OK to Use Compressors
Available Cooling Stages
Requested Cooling Stages
Actual Cooling Stages
Compressor A1
Compressor B1
Compressor C1
Space Temperature
Cooling Demand
Cool Demand d/dt (F/min)
Supply Air Temperature
Supply Air d/dt (F/min)
Supply Air Temp Demand
SAT Delta Reference Temp
Economizer Position
Cool Thermal Lag Factor
SPT Cool Demand(+) Level
SPT Cool Demand(-) Level
SAT Cool Demand(+) Level
SAT Cool Demand(-) Level
MET2Add SAT Trend Level
Space Sensor Failure
SAT Thermistor Failure
OAT Thermistor Failure
Current Sensor Failure
Compressor Failure
Refrig Circuit Failure
Thermostat Failure
Economizer Failure
SSP Transducer Failure
SCT Thermistor Failure
Indoor Fan Failure
Plugged Filter
STRTHOUR (Component Hours and Cycles)
DESCRIPTIONSTATUSUNITSPOINT
Compressor A1 Run Hours
Compressor B1 Run Hours
Compressor C1 Run Hours
Compressor A1 Cycles
Compressor B1 Cycles
Compressor C1 Cycles
ALARMOUT
Yes/NoYesSPT_AL
Yes/NoYesSAT_AL
Yes/NoYesOAT_AL
Ye s / N oYe sC S _ A L
Ye s / N oYe sC O M P _ A L
Yes/NoYesCKT_AL
Yes/NoYesTSTAT_AL
Yes/NoYesECON_AL
Yes/NoYesSSP_AL
Yes/NoYesSCT_AL
Yes/NoYesFAN_AL
Ye s / N oYe sF I LT _ A L
DESCRIPTIONSTATUSPOINT
Current Mode (1=Occup.)
Current Occup. Period #
Timed-Override in Effect
Time-Override Duration
Current Occupied Time
Current Unoccupied Time
Next Occupied Day
Next Occupied Time
Next Unoccupied Day
Next Unoccupied Time
Previous Unoccupied Day
Previous Unoccupied Time
DESCRIPTIONSTATUSDEFAULTUNITSPOINT
Service Password
Password Enable
Metric Display
Language Selection
nnnn1111PASSWORD
Enable/DisableEnablePASS_EBL
Off/OnOffDISPUNIT
0 = ENGLISH
1 = FRANCAIS
2 = ESPANOL
3 = PORTUGUES
0LANGUAGE
SCHEDOVR (TIMED OVERRIDE SETUP)
DESCRIPTIONSTATUSDEFAULTUNITSPOINT
Schedule Number
Accept Global Holidays
Override Time Limit
Timed Override Hours
Timed Override
0-990SCHEDNUM
Yes/NoYesHOLIDAYT
0-44hoursOTL
0-40hoursOTL_EXT
Yes/NoYesTIMEOVER
51
Page 52
APPENDIX A — CCN TABLES (cont)
ALARMDEF (Alarm Definition Table)
DESCRIPTIONSTATUSDEFAULTUNITSPOINT
Alarm Routing Control
Equipment Priority
Comm Failure Retry Time
Re-alarm Time
Alarm System Name
DESCRIPTIONSTATUSUNITSPOINT
Reset All Current Alarms
Reset Alarm History
0000000000000000ALRM_CNT
0 to 74EQP_TYPE
1 to 24010minRETRY_TM
1 to 25530minRE-ALARM
XXXXXXXX48/50HGALRM_NAM
ALARMS
NoALRESET
NoALHISCLR
Circuit A Strikes
Circuit B Strikes
Circuit C Strikes
Active Alarm #1
Active Alarm #2
Active Alarm #3
Active Alarm #4
Active Alarm #5
Active Alarm #6
Active Alarm #7
Active Alarm #8
Active Alarm #9
Active Alarm #10
Active Alarm #11
Active Alarm #12
Active Alarm #13
Active Alarm #14
Active Alarm #15
Active Alarm #16
Active Alarm #17
Active Alarm #18
Active Alarm #19
Active Alarm #20
Active Alarm #21
Active Alarm #22
Active Alarm #23
Active Alarm #24
Active Alarm #25
NOTE: Alerts will displayed as Txxx.
nASTRIKES
nBSTRIKES
nCSTRIKES
Axxx or TxxxALARM01C
Axxx or TxxxALARM02C
Axxx or TxxxALARM03C
Axxx or TxxxALARM04C
Axxx or TxxxALARM05C
Axxx or TxxxALARM06C
Axxx or TxxxALARM07C
Axxx or TxxxALARM08C
Axxx or TxxxALARM09C
Axxx or TxxxALARM10C
Axxx or TxxxALARM11C
Axxx or TxxxALARM12C
Axxx or TxxxALARM13C
Axxx or TxxxALARM14C
Axxx or TxxxALARM15C
Axxx or TxxxALARM16C
Axxx or TxxxALARM17C
Axxx or TxxxALARM18C
Axxx or TxxxALARM19C
Axxx or TxxxALARM20C
Axxx or TxxxALARM21C
Axxx or TxxxALARM22C
Axxx or TxxxALARM23C
Axxx or TxxxALARM24C
Axxx or TxxxALARM25C
52
Page 53
Page 54
Copyright 2001 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book1144
Tab 1a1b6a6b
PC 111Catalog No. 534-80090Printed in U.S.A.Form 48/50HG-2TPg 5420210-01Replaces: 48/50HG-1T
Page 55
CONTROL SET-UP CHECKLIST
Model Number: ____________________________________Software Versions: ____________________________________
Serial Number:_____________________________________MBB: CESR131278-00- __ __
Date: ____________________________________________SCB/ECB: CESR131249-00- __ __
T echnician:________________________________________MARQ: CESR131171-01- __ __
INDICATE UNIT SETTINGS BELOW
Control Type:Thermostat / T55 Space Temp. / T56 Space T emp. / T58 Space T emp.
Set Points:CoolingOccupied:___________Unoccupied:____________
U.CTL ________AutoThermostatSpace Sensor
T .CTL ________Adaptive1 Stage Y12 Stage Y1
OC.FN ________YN
S.DLY ________30
IDF .F________NY
FN.SW________No SwitchNormal OpenNormal Close
FL.SW________No SwitchNormal OpenNormal Close
FS.SW________No SwitchNormal OpenNormal Close
RM.SW ________No SwitchNormal OpenNormal Close
ECB ________YN
SAT.T ________240
COOL
N.CMP________3 (016-024) or 2 (014,028)
MC.LO________0° F
MRT.C________180 sec
MOT .C________300 sec
CL.PD________1.0 ∆F
CL.ND________–1.0 ∆F
C.LAG________1.0 min
SA.PD________1.0 ∆F
SA.ND________–1.0 ∆F
C.INC________450 sec
C.DEC________300 sec
A.NOW________YN
INV.E ________YN
A1.CS________YN
B1.CS________YN
C1.CS________YN
HEAT
→
HT.TY________No HeatGASELECTRIC
N.HTR________2
HT .LO________75 F
MRT.H________120 sec
MOT .H________120 sec
HT .PD________1.0 ∆F
HT.N D________–1.0 ∆F
H.LAG________1.0 min
H.INC________450 sec
H.DEC________300 sec
CL-1
202
Page 56
ECON
IAQ
CCN
DISP
ALRM
EC.EQ________NY
MIN.P________30 %
ECL.H________65 F
ECL.L________0° F
FC.EN________YN
EN.SW________No SwitchNormal Open Normal Close
PE.EN________NY
PE1.P________25 %
PE2.P________75 %