Carrier 50DP User Manual

Page 1
Carrier Parkway • Syracuse NY 13221
Single-Package Cooling Units
INSTALLATION
Rigging and Unit Placement — Inspect unit for
transportation damage. File any claim with trans portation agency. Do not drop unit. Keep unit upright. Use spreader bars over unit to prevent
sling or cable damage. Rollers may be used to move
unit across a roof. Level unit by using unit frame as
Four lifting holes are provided in ends of unit base rails as shown in Fig. 1. Refer to rigging instructions on unit. Refer to Accessory Roof Curb
Installation Instructions for additional information as required.
Roof Curb — Assemble and install accessory roof
curb in accordance with instructions shipped with
this accessory. Refer to Fig. 2. Accessory roof curb
and information required to field fabricate a roof curb of 2 in. X 12 in. planks is shown in Fig. 2. Install insulation, cant strips, roofing and flashing as shown. Ductwork can be installed to roof curb before unit is set in place. Curb should be level. Unit leveling tolerance is ±1/16 in. per linear ft in
any direction. This is necessary to permit unit drain to function properly.
Parrlor Pnrnnratinn 1Q7Q
Fig. 1 — Rigging Details
Form 50DP-9SI
Page 2
Table 1 — Physical Data
UNIT SIZE 50DP OPERATING WT (lb)
Unit
With Economizer
Roof Curb
COMPRESSOR
No. ... Type 2 ... P64
Oil (oz)
REFRIGERANT (Capillary Control) R-22
Charge (lb) Sys 1*, Sys 2
OUTDOOR COIL
Rows 2 F ins/in. Total Face Area (sq ft)
OUTDOOR AIR FAN
Nominal Cfm
No. ... Diam (in.)
Motor Hp (1075 Rpm) 1/2
INDOOR COIL
Rows F ins/in. Total Face Area (sq ft)
INDOOR BLOWER
Qty ... Size (in.) Nominal Cfm
Rpm Range Max Allowable Rpm Motor Pulley Pitch Diam (in.)
Fan Pulley Pitch Diam (in.)
Belt, No. ... Type ... Length (in.)
Speed Change per Full Turn Std
of Moveable Pulley Flange (Rpm) Opt
Moveable Pulley Max Full Turns
from Closed Position
Factory Setting - Full Turns Open Factory Speed Setting (Rpm)
Motor Hp (Service Factor)
HIGH PRESSURE SWITCH
Cutout (psig) Reset (psig) 320
LOW PRESSURE SWITCH (Liquid Line)
Cutout (psig) Reset (psig)
AIR INLET SCREENS
Economizer, No. ... Size (in.)
INDOOR AIR FILTERS (Type)
No. ... Size (in.)
Std 753-1066
Std 2 4-3.4
Std
Std 1 (1.25)
012
1350 1500
200
Hermetic -
76 ea
7 9, 6.6
14
18.9
9000
2 ..22
2
14
14.7
2 .. 10x10
4000
878-1191
1550
2.8-3.8
5.5
5.5
1 ... V .. 41
62 63
5 753 878
1-1/2 (1.20)
2 ... 16x20x2
4 .. 16x25x2 4 ... 16x23x2
- 2 Cy t inders
10% efficient — 2-in. D isposable Fiber Glass
014
1410 1560
200
2 ... P77
76 ea
R-22
8 3, 8.3
Copper Tube, Aluminum Plate Fins/in.
3
14
18 9
Prope 1 ler Type.
8000
2 22
1/2
Copper Tube, Aluminum Plate Fins/in
3
15
13.8
........................ _ .... .
Centrifugal, Adjustable Belt Drive
.............................................
2 10x10
5000 805-1093 978-1265
1550
2 8-3.8
3.4-4 4
6.0
6.0
1 ... V . 43
58 57
5 805 978
2 (1.15) 3 (1.15)
2 ... 20x25x1
1 .. 20x20x1
2 16x20x2
Direct Drive
428
27 60
016
1590 1740
200
Semi-Hermetic — 6 Cylinders
1 . 06DA537
160
R-22
23.2, -
3
14
18 9
12,000 2 ... 26
1
3
14
16.5
2 .. 10 X 10
6000
916-1 186
1158-1428
1550
3.4-4.4
4.3-5.3
6.4
6.4
1 . V ... 45
54 55
5
916
1158 3 (1 15) 3 (1 15)
4 ... 20x20x2
4 .. 16x20x2
t
•System 1 consists of upper portion of outdoor coil and lower portion of indoor coil
Page 3
Roof Mount — Check building codes for weight
distribution requirements. Unit weight is shown in Table 1.
Alternate Unit Support Methods — Where the curb
cannot be used, support unit with sleepers using unit curb support area. If sleepers cannot be used, support long sides of unit with a minimum of 3 equally spaced 4-in. x 4-in. pads on each side.
Positioning — Provide clearance around and above
unit for airflow, safety and service access. (Fig. 3)
Do not install unit in an indoor location. Do not locate unit air inlets near exhaust vents or other sources of contaminated air.
Although unit is weatherproof, guard against
water from higher level runoff and overhangs.
Outdoor Air Intake — The unit can be equipped
with an outdoor air damper (economizer) which
mixes outdoor air with return air.
Field-Fabricated Ductwork — Secure all ducts to
building structure. Use flexible duct connectors between unit and ducts as required. Insulate and weatherproof all external ductwork, joints and roof openings with flashing and mastic in accord ance with applicable codes.
Ducts passing thru • an unconditioned space
must be insulated and covered with a vapor barrier.
A minimum clearance is not required for any
air duct installation.
Outlet grilles must not lie directly below unit
discharge.
Unit Duct Connections — Unit is shipped for
thru'the-bottom duct connections. Ductwork
openings are shown in Fig. 2 and 3. Duct connec tions are shown in Fig. 4. Field-fabricated con centric ductwork may be connected as shown in
Fig. 5. Attach all ductwork to roof curb and roof
curb basepans.
Concentric duct details are shown in Fig. 6. Also, refer to installation instructions shipped with accessory roof curb.
Economizer Section — Remove filter access panel.
Check that outdoor air damper is closed and return air damper is open.
Economizer operation and adjustment is de scribed in Start-Up, Economizer Operation; and
Service, Economizer Adjustment, respectively.
•î33)io«K>'
4 PLACÉS.
Dmçmims
unît
50S>f>OÎ2/<Ji4 ölÄ
■-0
ms)
to-i-Uÿ 5
MTSRSO COf»<S»
yÇ!<»0№:'A
TYPS
OurUN£:«:««T
CCMR ^
SECTiOiî^
ftAfiViÉA'OÉ ^
/ROOF CORS ,/V
: ‘-jT-; !-K>5r
GASKET (S'JPPl.iSO WTH OURS)
r*
ROOF Oi^i«S
f atCTfsou.
^ SECT(0N
; V
0-S^«32i
. COÜRTES FLASHING
-------
f£iS> Süfw=Ct£D
NOT£Sî
'. OiTOerisSoos io paiGfftïwisis i 5 «srs miliimetefs,
AtTRCSi CÄ} iJ:K5tWOr){ TO fooi'curo
3. c« tiOPscsg&-oîbasepaos teibre sostatffOij mix.
Fig. 2 — Roof Curb Details — 50DP012,014,016
SSCTK5» A-A
ÎS«PΫSUÎ.AriON
FiElP StJPPCiED
Page 4
~T
-----
7 2S?5i>Af«/aX)N0M}2Ef?ti00a. .
t
[^IMOOOR Ai'?FLOW
a "=>T ORAtN
-JCUTOOO'i AtRELOV/
Fig. 3 — Physical Data and Dimensions
>Aa£RNAT£ AiRfLOW
------
! SPACE RECUIREC FOR
.....J SERVSCE AND AtRFUOW
Page 5
Outside Air Damper (25% ventilation dir) -- Outside
air damper can be adjusted to permit up to 25% outdoor air entry into return air compartment.
Outdoor Air Hood Installation (Fig. 3) — The
outdoor air hood is common to 25% air ventilation and economizer. The economizer and all electrical connections are factory installed and adjusted. The hood assembly, outdoor air inlet screen(s) and required hardware are shipped in a carton located on outdoor fan section and must be field installed.
Using screws in carton install hood as follows;
1. Assemble hood top cover, side panels and bottom track angle (Fig. 7).
Loosen base unit top cover sheet metal screws
2.
located above outdoor air inlet opening.
3.
Match notches in hood top cover to unit top
cover screws. Insert hood flange between unit
top cover flange and unit. Tighten screws.
4
Secure hood sides and bottom track angle to unit. The screw on unit that matches bottom track angle center hole must be removed prior to assembly. Re-use screw to secure bottom track angle to unit.
Insert outdoor air filters and spacer in hood
5. filter tracks. NOTE: Hood may also be installed by individually attaching hood parts to base unit following sequence above.
6. Attach filter retainers to bottom track angle.
Indoor Blower — Blower belts and pulleys are
factory installed. Belts are secured to pulleys with tape. Remove tape and, if required, adjust as described in Service, Indoor Blower Adjustment.
Condenser Air Fans and Motors are factory set.
Refer to Service, Condenser Air Fan Adjustment as required.
NOTE: Do not drill in this area, damage to basepan may result in water leak
Fig. 5 — Concentric Duct Air Distribution
NOTE: Do not drill in this area, damage to basepan may result in water leak
Fig. 4 — Air Distribution — Thru-the-Bottom
NOTE: Dimension A, A1 and B, B1 are obtained from field-supplied
ceiling diffuser
Fig. 6 — Concentric Duct Details
Page 6
Condensate Drain — See Fig. 3 and 8 for drain
locations. Plugs are provided in both drain holes and at least one must be removed when unit is operating. Two 3/4-in. half couplings are provided inside the unit evaporator section for the con densate drain connection(s). An 8 1/2-in. x 3/4-in. diameter and 2 in. x 3/4-in. diameter pipe nipple coupled to standard 3/4-in. diameter elbows pro vide a straight path down thru holes in the unit base rails (see Fig. 9). A trap at least 4 in. deep must be used and must be protected against freeze-up. If only one drain connection is trapped, other connection must be plugged.
Field Power Supply — Unit is factory wired for
voltage shown on nameplate. Units are provided with terminal block.
When installing units, provide a disconnect per
NEC of adequate size. (Table 2, 3, 4.)
All field wiring must comply with National
Electrical Code and local requirements.
Route power lines thru control box end panel — or unit basepan — (Fig. 3) to terminal connections as shown on unit wiring diagram and Fig. 10.
Operating voltage to compressor must be within voltage range indicated on unit nameplate. On 3-phase units, voltages between phases must be balanced within 2% and the current must be
drain i| drain hole
CONNECTION (BOTH SIDES)
Fig. 8 — Condensate Drain Details
3'ppT
* rSAÌWCOKfiECTlOÌ'ÌU_____
(HAt.fCOyPt.iSSi p i
SASEftfiit.
r
TO TRAP •5'
r
I
Fig. 9 — Condensate Drain Piping Details
f
VOLTS/PH/HZ
200/3/60
230/3/60
460/3/60 414 508
575/3/60 518 632
VOLTAGE
RANGE
Max RLA LRA
Min
220 24
180
207
253
COMPR
20.9
10.5
8.3
Table 2 — Electrical Data; 50DP012
OUTDOOR
FAN MOTOR
Qty
113 2
98 2
49 2.1
41
2
2 1.8
FLA
4 6
3.8
INDOOR
FAN MOTOR
FLA FLA
Hp
1 3 45
5.5
1.5 1
3 45 1 3.45 1
3 45
1 3.45 156
5.5 39 18.8
1.5
5.5 72
1.5
1.5 5.5
5.5
1.5 1 3.2
1.5 5.1 1
3.2
1
3.2
1
3 2
1.5 5.1 1 5 5.1
1.5 5.1 1 1.6
2.Ó
1.5 1 1.6 1
1 Ó
1 1.6
2.6
1 5
1.5 2.6
2.6 66
1.5 1
1 35 1 7
1 5
FACTORY INSTALLED
HEATERS
Nom Kw
_
39 72
117 56.1 155
117
156
-
47 18.8 65 70 82
135
47 18.8 82 34 2
135 56.1
_
-
21 39 32.4 66 55 0 85 21 39 32.4 55
--
18.8
34 2 100 90
74.8 205
34.2
56.1
74.8
34 2
56.1
17.1 30
17.1
55.5
-
POWER
Min Ckt
Amps
SUPPLY
Max Fuse
70 70 7$ 70 70
• ••
70 100 155 205 175
60
60
1 10
180
65 110 180 i7d
30
35 35
55
35
90 25
25
Amps
70
1 oO
175
9>3
150
' 70'
no
35 3S
50 30 3S 50
30 25
2.5
..........
«
Compr Compressor
FLA — Full Load Amps
Hp Horsepower
Locked Rotor Amps
LRA
— Rated Load Amps
RLA
.1 Fuse only; unshaded values indicate fuses or circuit breakers may be used
Page 7
Table 3 — Electrical Data; 50DP014
VOLTAGE
VOLTS/PH/HZ
200/3/60 180 220 27.0
230/3/60 207 253 22.8
460/3/60
575/3/60
Compr — Compressor
FLA — Full Load Amps Hp — Horsepower
RANGE
Min
414
518 632 9.3
COMPR
Max
508 11.6
LRA Qty FLA
RLA
160
137 2
69 2
55
LRA — Locked Rotor Amps RLA — Rated Load Amps
OUTDOOR
FAN MOTOR
2 4.6
4 5
2.3
2 1 8
INDOOR
FAN MOTOR
FLA
Hp
2.0
3.0
2.0 7 4
2 0
2.0
2.0
3.0 8.4
3.0
3.0 3 0 8.4 156 74 8 210 200
2.Ò 6.6
3.0 8 4
2.0 6 6 2 0 2 0 3 0
3.0
3.0 8.4 2 0 3.3
3.0
2.0
2.0 2 0 3 0 4 2
3.0 4.2
3.0 4.2 2 0
3,0
7 4
8.4
7.4 7 4
7.4
8.4 72
8.4
6.6
6.6
8.4
8.4
4.2 3 3
3.3
3.3
2 3
3.8
FACTORY INSTALLED
HEATERS
FLA Nom Kw
__
39
72 34 2 100 117 156
39
117
_ __
- -
47 18.8 70
82 135
47
82 135
__ — _
21
39 66 21
39 32.4 55 66 55 0
-
Fuse only; unshaded values indicate fuses or circuit breakers
may be used
18.8 80 90
56.1
74.8
18.8 80 ■ ■■ ■ 90
34.2 105 56 1 165 ; 75
34 2 56 1
18.8
34.2
56.1 185
_
17.1
32.4 55 0
17.1 40
-
POWER SUPPLY
Min Ckt
Amps
80 90 80 90
160 205
70 70
Max Fuse
:7L::::A8e.:A.;/
115 180
70
120 DO
35 i 40
40 35 55 90
90
30 30
Amps
LOO
150
200
: 10
Ì Ì0 .
] 75
' / J
..
SO 8C'
30 ■
40 40
60 40 50
SO
30
Table 4 — Electrical Data; 50DP016
VOLTAGE
VOLTS/PH/HZ
208-230/3/60 187 253
460/3/60 414
575/3/60 518
Compr — Compressor LRA
FLA — Full Load Amps RLA
Hp — Horsepower
RANGE
Min Max
508 32 120
632 25.6 96
RLA
61.6
COMPR
LRA
266
Locked Rotor Amps Rated Load Amps
OUTDOOR
FAN MOTOR
Qty
FLA
2 6.6 3
2
3.3
2 2.6 3
balanced within 10%. Contact local power com pany for correction of improper voltage or phase imbalance. Unit failure as a result of operation on improper line voltage or excessive phase imbalance constitutes abuse and may cause damage to elec trical components. Such operation would invali date applicable Carrier warranty.
Field Control Wiring — Install a Carrier-approved
accessory thermostat assembly according to instal
lation instructions included with accessory. Locate
thermostat assembly on a solid wall in the condi tioned space to sense average temperature.
Route thermostat cable or equivalent single
leads of no. 18 AWG colored wire from subbase
INDOOR
FAN MOTOR
Hp FLA FLA
10.4
3
4.7
3 8
*Fuse only.
FACTORY INSTALLED
HEATERS
Nom Kw
_ _
72-82 117-135 6.1 165-185 150-175 156-180
34.2 105-120
74.8
39 66 96
- -
32.4 55
55.0 90
79.8
POWER SUPPLY*
Min Ckt
Amps
105 125
210-240
55
130
50 45
Max Fuse
Amps
125
200-225
125
terminals thru conduit in unit to low-voltage connections as shown on unit label wiring diagram
and in Fig. 11. Use no. 16 AWG wire for lengths exceeding 50 feet. Set heat anticipator settings as indicated in Table 5. Settings may be changed slightly to provide a greater degree of comfort for a particular installation.
Refer to accessory remote control panel in
structions as required.
Return Air Filters — Check that correct filters are
installed in filter tracks. See Table 1. Do not operate unit without return air filters.
Outdoor Air Inlet Screens — Outdoor air inlet
screen(s) must be in place before operating unit.
60 60 90
Page 8
TBJ.
REMOVABLE JUMPER rr°^ I
THE RMOSTAT ASSEMBLY
Ijji-i-g ® ^ ^ [g]
ao
o cc
O Ili
(/> a
Fig. 10 — Field Power Wiring Connections

START-UP

Unit Preparation — Make sure that unit has been
installed in accordance with installation instruc tions and applicable codes.
Compressor Mounting — On 50DP012/014 units,
compressors are internally spring mounted. Do not loosen or remove compressor hold-down bolts. On
50DP016 units, loosen compressor hold-down bolts until sidewise movement of the washer under each hold-down bolt head can be obtained. Do not loosen completely as bolts are self-locking and will maintain adjustment.
Internal Wiring — Check all electrical connections
in unit control boxes . . . tighten as required.
Refrigerant Service Valves — Each 50DP012/014
unit system has 2 Schraeder type service ports, 1 on suction line and 1 on compressor discharge line.
Be sure that caps on the ports are tight. The
50DP016 has one service valve on suction line, one
on discharge line and one on liquid line. Be sure valves are open.
Crankcase Heater(s) are energized as long as there
is power to the unit. NOTE Unit power must be
on for 24 hrs. prior to startup
Table 5 — Heat Anticipator Settings
UNIT MODEL
50DP012/014
50DP016
VOLTAGES
200/3/60
230/3/60
460/3/60
208-230/3/60
460/3/60
KW STAGE 1
13 23 8 39 1
52.0 52
17.3 31 4 51 7
15.7
29.8
50.5
23.8-31.4 39 0-51.7 52 .26
52.0-68.8
29.8 50 5 .26 .52
73.3
STAGE 2
.26 .26 .52
.26
26 52
.26 .26 .26
.26
.52
.26
.52 .52
.26 .52
.52
.52
_
26 26 52
26 26
_
.26
' ¡H É É É [g] è É'
Q <
liJ QH
I ^ 3
O > CD
gJlW-VOLT^ TS^l^ 8upq<
Z
_ DC
CD CO
Fig. 11 — Field Control Thermostat Wiring
Cooling — To start unit, turn on main power
supply. Set system selector switch at COOL and
fan switch at AUTO. Set thermostat below room temperature.
DP012 AND DP014 No. 1 compressor starts on closure of No. 1
contact in thermostat. Additional rise in room temperature closes contact
No. 2 in thermostat, energizing No. 2 contactor.
Second compressor starts. DP016
Compressor starts unloaded on closure of No. 1 contact in thermostat.
> Additional rise in room temperature closes contact
No. 2 in thermostat which de-energizes the unloader coil. Compressor is now fully loaded.
Check cooling effects at a setting above room temperature. Check unit charge. Refer to Refrig eration Charge in Service Section.
Reset thermostat at a temperature above room
temperature. Compressor(s) will shut off. TO SHUT OFF UNIT ^ Set system selector switch
at OFF position or reset thermostat above room temperature. Units with Signal-LOC'^''^ protection
device shut down on any safety trip and thermo stat light comes on. Determine reason for safety trip. Restart 012/014 compressor by turning ther
mostat selector switch OFF then ON. Restart 016
compressor by resetting circuit breaker at unit.
Heating — Turn on main power to unit. Set
thermostat at HEAT, fan at AUTO, and above
room temperature. First stage of electric heater
elements are energized on closing of heating
contact No. 1 in thermostat. On a further fall of
room temperature, heater contact No. 2 closes en
ergizing second stage electric heater elements.
TO SHUT OFF UNIT — Set system selector switch
at OFF.
HEAD PRESSURE CONTROL - All units have
fan cycling thermostats which, at 55 F, shut off one outdoor fan motor. This permits unit to operate down to 35 F outdoor air temperature.
Ventilating (Continuous Fan) — Set fan and system
selector switches at ON and OFF, respectively. Indoor air fans operate continuously to provide constant air circulation.
I
i
Page 9

Table 6 — Air Quantity Limits

#
UNIT MODEL T
50DP0Ì2 50DP014 50DP016
* Indoor Fan Max Watts = 3000
Automatic Changeover — The unit automatically
MIN CFM
3000 3750
—4500
MAX CFM
5000 6250
7500‘
switches from heating mode to cooling mode when system selector switch is set at AUTO, and temperature of the conditioned space rises to cooling selector lever setting. When temperature of the conditioned space falls to the heating selector lever setting, unit automatically changes from cooling mode to heating mode. The thermostat is interlocked so that cooling and heating systems do not operate at the same time.
Economizer Operation — If unit is equipped with
modulating outdoor air control (economizer), it should operate as follows:
ENTHALPY CONTROL SETTING ^ Set enthalpy control (Fig. 12) to desired temperature and relative humidity which provides cooling with outside air only (no compressor operation). To
determine appropriate setting of enthalpy control;
1. Determine maximum combination of relative humidity and temperature of supply air con sidered acceptable for the installation.
2. In Fig. 13, locate percent humidity on the left-hand scale and dry-bulb temperature on the right hand scale. Example in Fig. 13 uses 60%
RH and 66 F.
3. Draw a straight line connecting the 2 points.
4. Adjust the enthalpy control dial to the setting
indicated on control setting scale in Fig. 13. The control setting for example conditions is the B range.
MIXED AIR THERMOSTAT SETTING ^ Set mixed air thermostat in return air compartment to desired temperature of air delivered to the condi tioned space (not less than 35 F or condensation in unit will result). Do not uncoil mixed air thermo stat capillary.
Cooling Season
When stage 1 is satisfied, outdoor fans, indoor blowers and compressors shut off. Outdoor air damper closes.
If fan switch is at ON, and stage 1 is satisfied, outdoor air fans and compressors shut off, indoor blowers continue to operate and outdoor air
damper stays in ventilation position. INTERMEDIATE SEASON (Economizer Control)
— Operation is similar to cooling season except when stage 1 of cooling thermostat closes, outdoor air fans and compressor remain off if outdoor enthalpy is below enthalpy control setting. Only indoor blowers are operative. As temperature of the mixed air (outdoor air mixed with return air)
rises above or drops below mixed air thermostat setting, outdoor air damper modulates to maintain
mixed air setting.
Fig. 12 — Enthalpy Control Assembly
:Oi
20-
I-I
7g:v;3|
CONTROL SETTING
e>c
% I
a:
o
s
É 50-
Z
ui . ^'60^
O;
70r
80-
Fig. 13 — Nomograph for Determining
Enthalpy Control Setting
With the fan switch at AUTO, and the room
thermostat satisfied, indoor blowers shut off and
outdoor air damper closes. If fan switch is at ON and room thermostat satisfied, damper goes to ventilation position.
HEATING SEASON - Outdoor air damper always
stays in ventilation position while indoor blowers are operating. The damper closes and the indoor blowers shut off when the room thermostat is
satisfied.
-> Variable Volume Units — Units suitable for use
with variable volume air handling systems are
equipped with 2 electric unloaders on the com
pressor. The control panel for these units (Fig. 14)
consists of a step controller, a proportional ther
mostat, a 7-day timer and a power switch.
Before starting unit, open compressor seiwice
valves and liquid line shutoff valve. Be sure com
pressor crankcase heaters have been on for 24 hours
and that crankcase oil level indicates half full.
-> Control Sequence Checkout
1. Turn on unit main power supply. Be sure unit is ready to operate.
2. Set variable volume control panel POWER switch at ON.
Page 10
CYCLE-LOG
STEP CONTROLLER
PROPORTIONAL THERMOSTAT
SEVEN DAY
TIMER
t
Fig. 14 — Control Panel, Variable Volume Units
3. If supply air leaving unit is above 50 F (or other field-set temperature), step controller will oper ate to de-energize compressor unloader solenoids (compressor loads up) until set temperature is achieved. An interval of 13.5 minutes is required to maximum loading position. Refer to unit label diagram for unloader sequencing. Also see
Fig. 15.
4. Step controller, 7-day timer and proportional
thermostat are factory set and adjusted. If other settings or changes in adjustment are required, refer to discussion of these items.
Seven-Day Timer Adjustment — Factory settings
are ON —6:30 AM; OFF —7:30 PM for each of 7 days.
l.On the timer dial face (Fig. 14), loosen the
thumbscrews which position the system ON and
OFF trippers.
2. Set trippers at desired system ON and OFF time settings and tighten thumbscrews. Skipping a day(s) is accomplished by removing trippers from the dial.
3. Set the timer by turning the dial face clockwise until fixed pointer indicates correct day and time.
Do not turn dial face counterclockwise. Do not
move fixed pointer.
Proportional Thermostat — The proportional ther
mostat, Fig. 14, monitors temperature of the con ditioned air leaving unit. On signal from the thermostat, sequence motor operates cam switches to load or unload compressor to maintain thermo stat setting. Thermostat is factory set at 50 F ± 6 F but may be reset between 0° F and 100 F as
follows:
TEMPERATURE SETTING - Turn knob on front of case until pointer indicates desired set point temperature. This is the center point of propor tional range.
RANGE ADJUSTMENT — Remove cover and turn adjustment wheel until pointer indicates desired range.
If sequencer motor shaft constantly moves back and forth, increase proportional thennostat range (about 5 F" at a time) until system is stable.
^ Step Controller — The step controller consists of a
reversible electric motor which drives a set of cams
that activate up to 5 snap-acting switches. Each cam is adjustable to operate at any point on the
160 angular degrees of cam shaft rotation. The
differential of each switch may be adjusted from a minimum of 5 angular degrees to a maximum limited only by the 160 degrees of camshaft
rotation.
Rotational direction is controlled by the propor tional thermostat thru the step controller feedback potentiometer and balancing relay.
DETERMINING SWITCH SETTINGS - Switches are factory set at angular settings as shown on Fig. 15 (also shown on unit label diagram). To reset, if desired, determine angular differential for each switch and between switches. Then determine minimum differential or throttling range of propor tional thermostat to provide desired step controller differential or throttling range. This range should be wide enough to prevent rapid cycling from one capacity step to another. Then adjust cams to new
settings as required.
10
Page 11
12 3 4
STEP CONTROL SWITCH
Fig. 15 — Step Controller Sequence
CAM ADJUSTMENTS - The step controller is shipped with cams set to operate switches (i.e. com pressor unloaders) as shown in Fig. 15. All switches
are closed (compressor unloaded). The shaft is
positioned all the way counterclockwise (as viewed
from motor end).
Using the following procedure, first adjust all operating points in one direction of motor drive. Then reverse motor direction and adjust switch differentials. Use potentiometer wiper as an approximate indicator of angular adjustments
using angular displacement scale mounted on
potentiometer back plate. Also see Fig. 16.
1. Loosen all bushing setscrews with a 1/16-in. Allen wrench. Loosen all cam hex screws with
a 3/16-in. open-end wrench.
If setscrews are not accessible from top of con troller, operate motor to rotate cams and bushings by shorting terminals R and B for
counterclockwise rotation and terminals R and W for clockwise rotation.
2. Momentarily de-energize motor to permit motor to recycle to start position. Jumper terminals R and W to run motor camshaft to desired position
MAKE
POIMT
St^EAX
POINT
for operating first switch. "Stop motor in this position by removing jumper between terminals
S and T.
3. Starting with first switch, turn cam clockwise until switch makes an audible “click” as roller moves up cam rise to higher level. This is the
operating point. Lock bushing setscrews.
4. Set operating point of each of remaining switches
in like manner. Advance motor by momentarily
jumpering terminals S and T.
5. Set switch differential by reversing motor (short terminals R and B) and running it to desired break point. Stop motor at this point by de
energizing power at LI (POWER switch off). Start at last switch and progress to first switch.
Move differential cam clockwise so that roller is on high part of cam. Be sure that switch is at make position. To check this, manually lift
roller assembly to make switch. Move differential cam counterclockwise until roller drops to low level of cam. At this point switch should break.
Lock the hex screw.
6. Check settings by performing Control Sequence Checkout.
7. If 115-volt to step controller is de-energized,
timer recycles to start point when power is restored.

SERVICE

Cleaning — Inspect unit interior at beginning of
each heating and cooling season or as operating conditions require. Remove unit top panel and/or side panels for access to unit interior.
EVAPORATOR COIL - Clean with Oakite 164 ­available from Carrier (Service Parts) under Part No. 28GS680002.
CONDENSER COIL - Clean outdoor coil annually
or as required by location or outdoor air condi
tions. Inspect coil monthly — clean as required.
CONDENSATE DRAINS - Check and clean each
year at start of cooling season. In winter, keep
drains and traps dry or protect against freeze-up. FILTERS — Clean or replace at start of each heat
ing and cooling season, or more often if operating conditions require it. Refer to Table 1 for type and size.
OUTDOOR AIR INLET SCREENS - Clean screens with steam or hot water and a mild deter gent. Do not use throwaway filters in place of screens.
Fig. 16 — Step Controller Cam Adjusting Details
(motor end view)

Lubrication

COMPRESSORS — Each compressor is charged with correct amount of oil at the factory.
FAN SHAFT BEARINGS - No lubrication required. Bearings are permanently lubricated.
FAN MOTOR BEARINGS - No lubrication of outdoor fan or indoor blower motors are required for first 5 years of operation. Annually thereafter, clean and repack bearings with a suitable bearing grease.
11
Page 12
his
lals
'ise lier the
lies rily
ort
red
dé
fi).
i.
lier
1 at
lift
tial
ow ak.
nce
,ed,
■ is
of
ing
/or
1 -
'art
illy idi-
ich îep
;at-
ing
фе
îan ter-
of
»ed
ion
of red ter,
ing
Evaporator Blower Adjustrnent — Blower motor
pulleys are factory set for speed shown in Table 1.
To change blower speed:
1. Shut off unit power supply.
2 Loosen belt by loosening blower motor mount
ing plate nuts.
3 Loosen movable pulley flange setscrew (see
Fig. 17).
4 Screw movable flange toward fixed flange to
increase speed and away from fixed flange to decrease speed. Increasing blower speed in creases load on motor. Do not exceed maximum speed specified in Table 1.
See Table 6 for air quantity limits.
5. Set movable flange at nearest key way of pulley hub and tighten setscrew. (See Table 1 for speed change for each full turn of pulley flange.)
To align blower and motor pulleys, loosen
blower pulley setscrews and slide blower pulley along blower shaft. Make angular alignment by loosening motor from mounting plate.
MOVABLE a.ANG£S
STRAIGHT EDGE
MOST BE
4WRAU£L
\VWTH8ELT f\
IsETSCREWsj^^'^l
'ПХЕО FLANGES^
Si№LE-GROOve TVfO-GROOVE
MOTOR a FAR SHAFTS MUST BE PARALLEL

Fig. 17 — Indoor Blower Pulley Adjustment

To Adjust Belt Tension — Loosen blower motor
SETSCREVVS
pivot bolts. Move motor mounting plate up or down for proper belt tension (1/2-in. deflection with one finger) and tighten pivot bolts. Adjust lock bolt and nut on mounting plate to secure in
fixed position.
Outdoor Air Fan Adjustment (Fig. 18) Shut off
unit power supply. Remove fan top grille assembly
and loosen fan hub screws. Adjust fan height on
unit using a straight edge placed across the fan
orifice. Tighten setscrews and replace rubber hub cap to prevent hub from rusting to motor shaft. Fill hub recess with permagum if rubber hubcap is missing.
Economizer Adjustment
1. Set enthalpy control at its highest setting. If outdoor temperature is above 70 F, perform the following; install jumper between enthalpy control terminals 1 and 2 (red and yellow wires).

Fig. 18 — Outdoor Air Fan Adjustment

2. Set system selector switch at COOL and set cooling selector lever at lowest setting. (Cooling
mode may be simulated by removing thermostat
wires from terminals Y1 and Y2 [if used] and installing jumper between Y1 and R.)
3. Set mixed air thermostat (MAT.) at lowest setting. Outdoor air damper goes to fully open position (indoor air damper closes).
4. Set mixed air thermostat at highest setting. Out door air damper goes to fully closed position (indoor air damper opens).
5. Adjust mechanical linkage for correct position ing if necessary. If cooling was simulated in 2, remove jumper and reconnect thermostat wire(s).
DAMPER VENT POSITION SETTING
1. Set fan switch at ON (continuous fan operation) and close niglit switch if used.
2. Set system selector switch at OFF.
3. Remove cap from vent adjustment screw on damper motor terminal box cover.
4. Turn adjustment screw slowly until dampers
assume desired vent position. Do not manually
operate damper motor. Damper to motor will
result.
POWER FAILURE — Dampers do not have a spring return. In event of power failure, dampers remain in position until power is restored. Do not
manually operate damper motor.
Refrigerant Charge — Amount of refrigerant charge
is listed on unit nameplate (also refer to Table 1). Refer to Carrier Standard Service Techniques Manual, Chapter 1, Refrigerants.
Unit panels must be in place when unit is
operating during charging procedure.
NO CHARGE — Use standard evacuating tech
niques. After evacuating system, weigh in the
specified amount of refrigerant. (Refer to Table 1.) LOW CHARGE COOLING — Using appropriate
cooling charging chart. Fig. 19, 20 or 21 add refrig erant until conditions of the chart are met. Note that charging charts are different from ones nor mally used. Charts are based on charging units to
12
Page 13
correct superheat for various operating conditions.
An accurate pressure gage and temperature sensing device are required. Connect temperature sensing device to service port on suction line and insulate it so that outdoor ambient temperature does not affect reading. Indoor air cfm must be within normal operating range of unit.
TO ÚSE COOLING CHARGING CHART - Take outdoor ambient temperature and read the suction pressure gage. Refer to chart to determine correct suction temperature. If suction temperature is high, add refrigerant. If suction temperature is low, care fully blow some of the charge. Recheck suction pressure as charge is adjusted.
Example: Fig. 19 — 50DP012 Outdoor Temperature
............................................
75 F
Suction Pressure....................................................65 F
Suction Temperature should be
............................
62 F
(Suction Temperature may vary ±5 F.)
If Chargemaster® charging device is used, tem perature and pressure readings must be accom plished using appropriate charging chart.
Fig. 20 — Charging Chart — 50DP014
20 30 40 50 60
SUCTK3N LINE TEMP F
Fig. 19 — Charging Chart — 50DP012 Fig. 21 — Charging Chart — 50DP016
70
13
20 30 40 50 60
SUCTION LINE TEMP F
70
Page 14
i
For replacement items use Carrier Specified Parts.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4 Tab
1b 6b
Form 50DP-9SI Supersedes 50DP-3SI
Printed in U.S.A. 11-79 PC 111 Catalog No. 535-007
i
Loading...