Installation and servicing of air conditioning
equipment can be hazardous due to system pressure and
electrical components. Only trained and qualified service
personnel should install, repair or service air conditioning
equipment.
Untrained personnel can perform basic maintenance
functions of cleaning coils and filters and replacing filters.
All other operations should be performed by trained
service personnel. When working on air conditioning
equipment, observe precautions in the literature, tags and
labels attached to the unit and other safety precautions
that may apply.
Follow all safety codes. Wear safety glasses and work
gloves. Use quenching cloth for unbrazing operations.
Have fire extinguisher available for all brazing
operations.
Single-Package Cooling Units
Alternate Unit Support Methods — Where the
preferred curb or slab mount cannot be used, support
unit with sleepers on perimeter, using curb support area.
However, if sleepers cannot be used, support long sides
of unit (dimension A, Fig. 4) with three 4-in. x 4-in. pads
equally spaced. U nit may sag if supported by corners only.
Positioning — Unit condenser air inlets and outlets
may be located in any compass direction since they are
not affected by wind. Provide clearances around and
above unit for airflow, safety and service access (Fig 4).
Do not install unit in an indoor location Do not locate
air inlets near exhaust vents or other sources of con
taminated air
Although unit is weatherproof, guard against water
from higher level runoff and overhangs.
A WARNING
Before performing service or maintenance operations
on unit, turn off main power switch to unit. Elec
trical shock could cause personal injury.
INSTALLATION
Rigging and Unit Placement — Inspect unit for
transportation damage. File claim with transportation
agency. Do not remove shipping skid until unit is ready
to be set in final location. Do not drop unit; keep upright.
Use spreader bars over unit to prevent sling or cable
damage. Rollers may be used to move unit across a roof.
Level by using unit frame as reference. See Fig. 1 for
additional information. Unit weight is shown in Table 1.
Units are designed to be hoisted only. However, units
with optional shipping skids may be moved with a fork
truck. Refer to Accessory Roof Curb Installation Instruc
tions for additional information as required.
Roof Curb — Assemble and install as described in
instructions shipped with this accessory. Accessory roof
curb and information required to field fabricate a roof
curb of 2-in.
insulation, cant strips, roofing and flashing as required.
For unit drains to function properly, curb must be level
or within tolerances shown in Fig. 3.
Roof Mount — Check building codes for weight dis
tribution requirements Unit weight is shown in Table 1.
Slab Mount — Provide a level concrete slab that
extends beyond unit cabinet at least 6 inches. Make a slab
8 in. thick with 4 in. above grade. Use gravel apron in
front of condenser air inlet to prevent grass and foliage
from obstructing airflow.
X 14-in. planks is shown in Fig. 2. Install
NOTES1 All unit panels must be In place when rigging.
2 Do not handle unit with fork trucks
3 Use 4 cables and four 2-by-4’s or 4-by-4's of dimensions
shown.
Fig. 1 — Rigging Details
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obiigations.
Book|l PC111 Catalog No 565-032 PrintedinUSA Form 50DF-9SI Pgl 4-86 Replaces: 50DF-7SI
Tab lib
For replacement items use Carrier Specified Parts
NOTE' Certified dimension drawings available upon request
Fig. 2 — Roof Curb Dimensions
GASKET
RIGID INSULATION
(FIELD SUPPLIED)
CANT STRIP
(FIELD SUPPLIED)
3-|"{ENDS OF UNIT)
ROOFING MATERIAL
(FIELD SUPPLIED)
Field-Fabricated Ductwork — Secure all ducts to
building structure. Use flexible duct connectors between
unit and ducts as required. Insulate and weatherproof
all external ductwork, joints and all roof openings with
flashing and mastic in accordance with applicable codes.
Insulate ducts passing through unconditioned spaces
and cover with a vapor barrier.
Maintain one-in. minimum clearance between supply
air duct and any combustible material for at least 3 ft of
duct run from unit.
Unit is shipped set up for through-the-bottom duct
connections. Ductwork openings are shown in Fig. 4.
Field-fabricated concentric ductwork may be connected
to units as shown in Fig. 5.
Modifications are required to convert unit for throughthe-side duct connections.
Do not use side duct connections on units with optional
power exhaust packages or accessory barometric relief
dampers.
To convert unit for through-the-side duct connection,
refer to Fig. 6 and perform the following procedure.
(Units without optional economizer);
1. Remove return air filter access panel.
2. Remove side air opening panels. Save sheet metal
screws.
3. Remove return air filters.
4. Remove slant baffle that separates bottom flow supply
and return air paths. Save screws.
5. Reinstall baffle on top of horizontal plenum deck
so that deck opening is covered. Face insulation side
of baffle down. Drill holes in horizontal plenum deck
using baffle holes as location guide Use sheet metal
screws removed in step 4 to secure baffle to deck.
6. Install side air opening panels in bottom air openings.
Face insulation side up Drill holes in unit basepan,
using panel holes as location guide. Use sheet metal
screws removed in step 2 to secure panels to basepan.
7. Reinstall return air filters. Be sure all relocated com
ponents are secure.
8. Open manual outdoor air inlet hood as described
below.
Manual Damper Hood Adjustment — Loosen
hood adjustment bolts, pull hood open to desired setting.
Tighten bolts. See Fig. 4.
CONDENSER
AND
COMPRESSOR
END
Fig. 3 — Unit Leveling Tolerances
HORIZONTAL
10. Route the red and yellow wires through knockout
in side plate. Wrap end of blue wire with electrical
tape. Using wire connectors from envelope injunc
tion box, wire enthalpy control assembly as shown in
Fig. 8. Use strain reliefs from envelope on side plate
and junction box. Refer to Fig. 9 for Psychrometric
Chart for enthalpy control.
11. Install outdoor air screens.
12. Push retainer snugly against screens and tighten
screws.
Exhaust Air Hood Installation — The optional
power exhaust hood and damper assemblies and required
sheet metal screws are shipped in the compartment at
right of indoor air fan motor compartment. Using screws
provided, install a hood damper assembly over each
exhaust air opening as shown in Fig. 4. Power exhaust is
applied only to economizer units using bottom duct con
nections. Exhaust fan and motor assembly is factory
wired and adjusted. Refer to Service, Power Exhaust Air
Fan Adjustment if required.
Indoor Air Fans — The fan belt and pulleys are factory
installed and adjusted. If required, adjust as described
in Service, Indoor Air Fan Adjustment.
Economizer Section
ECONOMIZER HOOD INSTALLATION (Fig. 7) —
The economizer mechanism and all electrical connections
are factory installed and adjusted except as noted below.
Hood assembly, outdoor air inlet screens and required
hardware are shipped separately and must be field
installed.
Install economizer hood and enthalpy control as
follows:
1. Loosen unit top panel sheet metal screws above out
door air inlet opening.
2. Assemble hood top panel, side panels and support
channel.
3. Insert hood flange between unit top panel flange and
unit. Slots are provided in hood flange to clear sheet
metal screws. Tighten sheet metal screws. To insure
water tightness, apply RTV to edges as indicated
by shaded portions of Fig. 7.
4. Secure hood side panels to outdoor air opening
flanges, using screws provided.
5. Install hood support bracket(s) between U-channel
and support channel.
6. Install screen retainer on support channel, using
screws in the slots. Do not tighten.
7.
A CAUTION
Shut off main power to unit before installing
enthalpy control assembly.
8. Remove enthalpy control assembly from shipping
location on horizontal deck in return air filter
compartment.
9. Using 4 no. 10-1/2 screws from envelope in control
assembly junction box, mount enthalpy control
assembly to inside of economizer hood side panel
nearest condenser section (Fig. 4).
Condensate Drains — See Fig. 4 for drain locations.
Condensate drain is open to atmosphere and must be
trapped. Install a trapped drain line at connection to be
used. Trap must be at least 3 in. deep and made of flexible
material or be installed to prevent freeze-up.
Condensate drain pan under unit is fitted with a one-in.
FPT coupling. A gasket is shipped taped to this drain.
Install gasket in unit basepan opening or alternate open
ing on end of unit.
Field Power Supply — Unit is factory wired for
voltage shown on nameplate. The main power terminal
block is suitable for use with aluminum or copper wire.
See Fig. 10 and 11. Units have circuit breakers for
compressors, fan motors and control circuit. If required
by local codes, provide an additional disconnect switch.
If an external electrical source is used, unit must be
electrically grounded in accordanee with local codes, or
in the absence of local codes, with the National Electrical
Code, NFPA 70.
All field wiring must comply with National Electrical
Code and local requirements.
Install conduit connector in unit basepan or side panel
openings provided as shown in Fig. 4. Route power lines
through connector to terminal connections in control box
as shown in Fig. 10 and 11.
Affix crankcase heater sticker to unit disconnect
switch.
Voltage to compressor terminals during compressor
operation must be within voltage range indicated on unit
nameplate. Also, see Table 2. Phases must be balanced
within 2% Contact local power company for correction
of improper voltage or phase unbalance. Failure due to
operation of unit on improper line voltage or with exces
sive phase unbalance constitutes abuse and may cause
damage to unit electrical components.
OUTDOOR AIR FANS
" (3)
ALTERNATE
CONTROL WIRE
OPENING
3 AND 4g- K 0
ALTERNATE FIELD-POWER WIRING
(COOLING ONLY UNIT )
INDOOR AIR FAN
AND FILTER
ACCESS PANELS
ALTERNATE
DRAIN 2|" KO d" MPT
L-2^" UNIT)
' CONDUIT
CONN INSIDE)
ALTERNATE
POWER WIRE
OPENING 3^“
(HEATING/COOLING
NPT
► OUTDOOR AIRFLOW
► INDOOR AIRFLOW
OPTIONAL
ECONOMIZER
AIR INTAKE HOOD
DSAM U"
^MPT CONN. INSIDE)
DIMENSIONS (ft-in :
UNIT
50DF
A
B
c
D
E0-10yi6
F0- 97a
G
H
J
Certified dimension drawings available on request
NOTES-
1. Allow 12 ft above unit, 8 ft on filter access panel end and 4 ft on remaining sides of unit for airflow and service clearance
2 For smaller clearances, contact manufacturer.
3 Refer to Roof Curb Dimensions for details of roof openings
034
17- 1
7- 3'/a
4-11
9- 0
4" NPT
2-10
11- 5
Fig. 4 Base Unit Dimensions
MAIN POWER WIRE
OPENING (G) (HEATING/
COOLING UNIT)
OPTIONAL
EXHAUST HOODS
(3)
V:
Fig. 5 — Concentric Duct Details
Fig. 7 — Economizer Outdoor Air Inlet
Hood Assembly
Fig. 8 — Enthalpy Control Assembly
Fig. 6 — Manual Damper Unit Indoor Air Section
DRY BULB TEMPERATURE (APPROXIMATE)-FAHRENHEIT
Fig. 9 — Psychrometric Chart for Enthalpy Control
Loading...
+ 11 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.