Carrier 50CR User Manual

Page 1
50CR Infinityt Single--Packaged Heat Pump Units With Puron®(R--410A) Refrigerant Sizes 024--060
Installation Instructions
installation.
NOTE: Installer: Make sure the Owner’s Manual and Service Instructions are left with the unit after installation.
TABLE OF CONTENTS
Page
SAFETY CONSIDERATIONS 2........................
INTRODUCTION 2..................................
RECEIVING AND INSTALLATION 2--16................
Check Equipment 2.................................
Identify Unit 2...................................
Inspect Shipment 2................................
Provide Unit Support 2..............................
Roof Curb 2.....................................
Slab Mount 2....................................
Ground Mount 2.................................
Provide Clearances 2................................
Rig and Place Unit 7................................
Inspection 7.....................................
Introduction 7....................................
Use of Rigging Bracket 7...........................
Select and Install Ductwork 9..........................
Converting Horizontal Discharge Units to Downflow
(Vertical) Discharge Units 9.........................
Provide for Condensate Disposal 9.....................
Install Electrical Connections 11.......................
High-- Voltage Connections 11.......................
Routing Power Leads Into Unit 11....................
Connecting Ground Lead to Ground Screw 11..........
Routing Control Wires 11..........................
Accessory Installation 16...........................
Special Procedures for 208--v Operation 16.............
PRE--START--UP 17..................................
START--UP 17.......................................
Unit Start--Up 17--23................................
Sequence of Operation 20............................
Check for Refrigerant Leaks 20........................
Start--Up Adjustments 20.............................
Checking Cooling and Heating Control Operation 20.....
Checking and Adjusting Refrigerant Charge 22..........
Refrigerant Charge 22.............................
No Charge 22....................................
Low Charge Cooling 22............................
To Use Cooling Charging Charts 22...................
Indoor Airflow and Airflow Adjustments 22............
Defrost Control 22..................................
Quiet Shift 22....................................
Defrost 22......................................
Emergency Heat/Cool Mode 22........................
A05307
Fig. 1 -- Unit 50CR
MAINTENANCE 24--28...............................
Air Filter 25.......................................
Indoor Blower and Motor 25..........................
Outdoor Coil, Indoor Coil, and Condensate Drain Pan 25....
Outdoor Fan 25....................................
Electrical Controls and Wiring 26......................
Refrigerant Circuit 26................................
Indoor Airflow 26..................................
Metering Devices–TXV & AccuRater
Pressure Switches 26................................
L o s s -- o f -- C h a r g e S w i t c h 2 7...........................
High--Pressure Switch 27.............................
Copeland Scroll Compressor (Puron
Refrigerant System 27...............................
Refrigerant 27...................................
Compressor Oil 27................................
Servicing Systems on Roofs with Synthetic Materials 27...
Liquid--Line Filter Drier 28.........................
Puron (R--410A) Refrigerant Charging 28..............
System Information 28...............................
L o s s -- o f -- C h a r g e S w i t c h 2 8.........................
Check Defrost Thermostat 28........................
TROUBLESHOOTING 28.............................
START--UP CHECKLIST 28...........................
®
Piston 26..........
®
Refrigerant) 27.......
1
Page 2
SAFETY CONSIDERATIONS
Installation and servicing of this equipment can be hazardous due to mechanical and electrical components. Only trained and qualified personnel should install, repair, or service this equipment.
Untrained personnel can perform basic maintenance functions such as cleaning and replacing air filters. All other operations must be performed by trained service personnel. When working on this equipment, observe precautions in the literature, on tags, and on labels attached to or shipped with the unit and other safety precautions that may apply.
Follow all safety codes. Installation must be in compliance with local and national building codes. Wear safety glasses, protective clothing, and work gloves. Have fire extinguisher available. Read these instructions thoroughly and follow all warnings or cautions included in literature and attached to the unit.
Recognize safety information. This is the safety--alert symbol Whenyou seethissymbolon the unit andin instructions or manuals, be alert to the potential for personal injury.
50CR
Understand these signal words; DANGER, WARNING, and CAUTION. These words are used with the safety--alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Before installing or servicing system, always turn off main power to system. There may be more than one disconnect switch. Turn off accessory heater power switch if applicable.
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in unit component damage.
Puron (R--410A) systems operate at higher pressures than standard R--22 systems. DO NOT use R--22 service equipment or components on Puron (R--410A) equipment. Ensure service equipment is rated for Puron (R--410A).
The 50CR heat pump is fully self--contained and designed for outdoor installation. Standard units are shipped in a horizontal--discharge configuration for installation on a ground-- level slab. Standard units can be converted to downflow (vertical) discharge configurations for rooftop applications.
WARNING
!
CAUTION
INTRODUCTION
RECEIVING AND INSTALLATION
Step 1—Check Equipment
IDENTIFY UNIT
The unit model number and serial number are printed on the unit informative plate. Check this information against shipping papers.
INSPECT SHIPMENT
Inspect for shipping damage while unit is still on shipping pallet. If unit appears to be damaged or is tornloose from its anchorage, have it examined by transportation inspectors before removal. Forward claim papers directly to transportation company. Manufacturer is not responsible for any damage incurred in transit. Check all items against shipping list. Immediately notify the nearest Carrier Air Conditioning office if any item is missing. To prevent loss or damage, leave all parts in original packages until installation.
!
!
Step 2—Provide Unit Support
For hurricane tie downs, contact distributor for details and PE Certificate (Professional Engineering) if required.
ROOF CURB
Install accessory roof curb in accordance with instructions shipped with curb (See Fig. 2). Install insulation, cant strips, roofing, and flashing. Ductwork must be attached to curb.
IMPORTANT: The gasketing of the unit to the roof curb is critical for a water tight seal. Install gasketing material supplied with the roof curb. Improperly applied gasketing also can result in air leaks and poor unit performance.
Curb should be level to within 1/4 in. (See Fig. 3). This is necessary for unit drain to function properly. Refer to accessory roof curb installation instructions for additional information as required.
SLAB MOUNT
Place the unit on a solid, level concrete pad that is a minimum of 4 in. thick with 2 in. above grade. The slab should extend approximately 2 in. beyond the casing on all 4 sides ofthe unit (See Fig. 4). Do not secure the unit to the slab except when required by local codes.
GROUND MOUNT
The unit may be installed either on a slab or placed directly on the groundif localcodespermit.Placethe unit on level ground prepared with gravel for condensate discharge.
Step 3—Provide Clearances
The required minimum service clearances are shown in Fig.6 and 7. Adequate ventilation and outdoor air must be provided. The outdoor fan draws air through the outdoor coil and discharges it through the top fan grille. Be sure that the fan discharge does not recirculate to the outdoor coil. Do not locate the unit in either a corner or under an overhead obstruction. The minimum clearance undera partialoverhang (such as a normal house overhang)is 48 in. above the unit top. The maximum horizontal extension of a partial overhang must not exceed 48 in.
IMPORTANT: Do not restrict outdoorairflow. An air restriction at either the outdoor--air inlet or the fan discharge may be detrimental to compressor life.
Do not place the unit where water, ice, or snow from an overhang or roof will damage or flood the unit. Do not install the unit on carpeting or other combustible materials. Slab--mounted units should be at least 4 in. above the highest expected water and runoff levels. Do not use unit if it has been under water.
2
Page 3
HVAC unit
Scre w
(NO TE A)
*Gask eting
outer flange
Flashing field
supplied
Roofing material
field supplied
Cant str ip
field supplied
base
Gask eting
inner flange*
Wood nailer*
Roof curb*
Insulation (field
supplied)
Ductwork
field supplied
HVAC unit
Scre w
(NOTE A)
*Gask eting
outer flange
Flashing field
supplied
Roofing material
field supplied
Cant str ip
field supplied
base
Gask eting
inner flange*
Ductwork
field supplied
Wood nailer*
Roof curb*
Insulation (field
supplied)
*Provided with roof curb
Roof Curb for Small Cabinet
Note A: When unit mounting scre w is used,
Return opening
UNIT SIZE
50CR024--036
50CR042--060
retainer bra cke t must also be used.
G
F
(B X C)
ODS CATALOG
NUMBER
CPRFCURB006A00 8 (203) 11 (279) 16--1/2 (419) 28--3/4 (730) 30--3/8 (771) 44--5/16 (1126) 45 --15/16 (1167) CPRFCURB007A00 14 (356) 11 (279) 16 --1/2 (419) 28 --3/4 (730) 30 --3/8 (771) 44--5/16 (1126) 45--15/16 (1167) CPRFCURB008A00 8 (203) 16--3/16 (411) 17 --3/8 (441) 40--1/4 (1022) 41--15/16 (1065) 44 --7/16 (1129) 46--1/16 (1169) CPRFCURB009A00 14 (356) 16--3/16 (411) 17--3/8 (441) 40--1/4 (1022) 41--15/16 (1065) 44--7/16 (1129) 46 --1/16 (1169)
B Typ.
Insulated deck pan
Roof
E
Supply opening
(B x C)
D
C Typ.
Short
Support
Long
Support
A
IN. (MM)BIN. (MM)
A
E
C
IN. (MM)
*Provided with roof curb
Roof Curb for Large Cabinet
Note A: When unit mounting scre w is used,
retainer bra cket must also be used.
G
F
R/A
D
Insulated deck pan
D
IN. (MM)
Gask et around
duct
Gask et around
outer edge
E
IN. (MM)
F
IN. (MM)
Roof
S/A
IN. (MM)
NOTES:
1. Roof curb must be set up for unit being installed.
2. Seal strip must be applied, as required, to unit being installed.
3. Dimension in ( ) are in millimeters.
4. Roof curb is made of 16--gauge steel.
5. Table lists only the dimensions, per part number, that have changed.
6. Attach ductwork to curb (flanges of duct rest on curb).
7. Insulated panels: 1--in. thick fiberglass 1 lb. density.
8. Dimensions are in inches.
9. When unit mounting screw is used (see Note A), a retainer bracket mu st be u sed as well. This bracket must also be used when required by code f or hur ricaneorseismic conditions. This bracket is available through Micrometl.
Fig. 2 -- Roof Curb Dimensions
50CR
A05308
G
3
Page 4
A
B
C
MAXIMUM ALLOWABLE
DIFFERENCE (in.)
A-B B-C A-C
1/4 1/4 1/4
C99065
Fig. 3 -- Unit Leveling Tolerances
OPTIONAL
RETURN
AIR
50CR
2"
OPENING
EVAP. COIL COND. COIL
OPTIONAL
SUPPLY
AIR
OPENING
C99096
Fig. 4 -- Slab Mounting Detail
A06114
Fig. 5 -- Corner Weights (Lbs.)
CORNER WEIGHTS (SMALL CABINET) CORNER WEIGHTS (LARGE CABINET)
Unit 024 030 036
Unit 042 048 060
Total Weight 349 349 373 Total Weight 438 463 499
Corner Weight 1 70 70 75 Corner Weight 1 88 98 107
Model
Corner Weight 2 54 54 58 Corner Weight 2 68 61 70
50CR
Corner Weight 3 84 84 90 Corner Weight 3 106 127 136
50CR
Model
Corner Weight 4 141 141 150 Corner Weight 4 177 177 186
4
Page 5
A05299
50CR
Fig. 6 -- 50CR024--036 Unit Dimensions
5
Page 6
A05300
50CR
Fig. 7 -- 50CR042--060 Unit Dimensions
6
Page 7
Step 4—Rig and Place Unit
Rigging and handling of this equipment can be hazardous for many reasons due to the installation location (roofs, elevated structures, etc.).
Only trained, qualified crane operators and ground support staff should handle and install this equipment.
When working with this equipment, observe precautions in the literature, on tags, stickers, and labels attached to the equipment, and any other safety precautions that might apply.
Training for operators of the lifting equipment should include, but not be limited to, the following:
1. Application of the lifter to the load, and adjustment of the lifts to adapt to various sizes or kinds of loads.
2. Instruction in any special operation or precaution.
3. Condition of the load as it relates to operation of the lifting kit, such as balance, temperature, etc.
Follow all applicable safety codes. Wear safety shoes and work gloves.
INSPECTION
Prior to initial use, and at monthly intervals, all rigging brackets and straps should be visually inspected for any damage, evidence of wear, structural deformation, or cracks. Particular attention should be paid to excessive wear at hoist hooking points and load support areas. Brackets or straps showing any kind of wear in these areas must not be used and should be discarded.
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Before installing or servicing system, always turn off main power to system. There may be more than one disconnect switch. Turn off accessory heater power switch if applicable. Tag disconnect switch with a suitable warning label.
!
UNIT FALLING HAZARD
Failure to follow this warning could result in personal injury or death.
Never stand beneath rigged units or lift over people.
INTRODUCTION
The lifting/rigging bracket is engineered and designed to be installed only on Small Packaged Products. This bracket is to be used to rig/lift a Small Packaged Product onto roofs or other elevated structures.
!
PROPERTY DAMAGE HAZARD
Failure to follow this warning could result in personal injury/death or property damage.
Rigging brackets for one unit use only. When removing a unit at the end of its useful life, use a new set of brackets.
WARNING
WARNING
WARNING
USE OF RIGGING BRACKET
Field Installation of Rigging
1. If applicable, remove unit from shipping carton. Leave top shipping skid on the unit for use asa spreaderbar to prevent the rigging straps from damaging the unit. If the skid is not available, use a spreader bar of sufficient length to protect the unit from damage.
2. Remove 4 screws in unit corner posts.
3. Attach each of the 4 metal rigging brackets under the panel rain lip (See Fig. 8). Use the screws removed in step 2 above to secure the brackets to the unit.
!
PROPERTY DAMAGE HAZARD
Failure to follow this warning could result in personal injury/death or property damage.
Rigging bracket MUST be under the rain lip to provide adequate lifting.
!
PROPERTY DAMAGE HAZARD
Failure to follow this warning could result in personal injury/death or property damage.
Do not strip screws when re-- securing the unit. If a screw is stripped, replacethe stripped one with a larger diameterscrew (included).
Rigging/Lifting of Unit
1. Bend top of brackets down approximately 30 degrees from the corner posts.
2. Attach straps of equal length to the rigging brackets at oppositeends of the unit. Be sure straps are rated to hold the weight of the unit (See Fig. 9).
3. Attach a clevis of sufficient strength in the middle of the straps. Adjust the clevis location to ensure unit is lifted level with the ground.
4. Afterunit is securely in placedetachrigging straps.Remove corner posts, screws, and rigging brackets then reinstall screws.
!
UNIT FALLING HAZARD
Failure to follow this warning could result in personal injury/death or property damage.
When straps are taut, the clevis should be a minimum of 36 inches above the unit top cover.
After the unit is placed on the roof curb or mounting pad, remove the top crating. On 50CR060 units only, 2 wire ties fastened to the outdoor coils and reversing valve/accumulator assembly must be cut. Remove the left and front louvered panels and corner post to access wire ties. The wire tie to be cut on the left is located approximately 4 in. down the tube sheet. The wire tie to be cut on the right is located approximately 6 in. down the tube sheet.
Bracket
WARNING
WARNING
WARNING
50CR
7
Page 8
50CR50CR
DETAIL
A
C03017
Fig. 8 -- Rigging Bracket Under Unit Rain Lip
UNIT SIZE
50CR024 372 169 50CR030 372 169 50CR036 395 179 50CR042 462 210 50CR048 485 220 50CR060 521 236
MAXIMUM SHIPPING WEIGHT
Lb Kg
Fig. 9 -- Suggested Rigging
8
A06113
Page 9
Step 5—Select and Install Ductwork
The design and installation of the duct system must be in accordance with the standards of the NFPA for installation of non--residence type air conditioning and ventilating systems, NFPA 90A or residence type, NFPA 90B and/or local codes and ordinances.
Select and size ductwork, supply-- air registers, and return air grilles according to ASHRAE (American Society of Heating, Refrigeration, and Air Conditioning Engineers) recommendations.
The unit hasduct flangeson the supply-- and return--air openings on the side of the unit.
!
ELECTRICAL OPERATION HAZARD
Failure to follow this warning could result in personal injury or death.
For vertical supply and return units, tools or parts could drop into ductwork, therefore, install a 90 degree turn in the return ductwork between the unit and the conditioned space. If a 90 degree elbow cannot be installed, then a grille of sufficient strength and density should be installed to prevent objects from falling into the conditioned space. Units with electric heaters require 90 degree elbow in supply duct.
When designing and installing ductwork, consider the following:
1. Allunits should havefield--supplied filtersor accessory filter rack installed in the return--air side of the unit. Recommended sizes for filters are shown in Table 1.
2. Avoid abrupt duct size increases and reductions. Abrupt change in duct size adversely affects air performance.
IMPORTANT: Use flexible connectors between ductwork and unit to prevent transmission of vibration. Use suitable gaskets to ensure weather tight and airtight seal. When electric heat is installed, use fireproof canvas (or similar heat resistant material) connector between ductworkand unit discharge connection. If flexibleduct is used, insert a sheet metal sleeve inside duct. Heat resistant duct connector (or sheet metal sleeve) must extend 24--in. from electric heater element.
3. Size ductwork for max cooling air quantity (400 cfm/ton).
4. Seal,insulate, and weatherproof all externalductwork. Seal, insulate and cover with a vapor barrier all ductwork passing through conditioned spaces. Follow latest Sheet Metal and Air Conditioning Contractors National Association (SMACNA) and Air Conditioning ContractorsAssociation (ACCA) minimum installation standards for residential heating and air conditioning systems.
5. Secure all ducts to building structure. Flash, weatherproof, and vibration--isolate duct openings in wall or roof according to good construction practices.
WARNING
CONVERTING HORIZONTAL DISCHARGE UNITS TO DOWNFLOW (VERTICAL) DISCHARGE UNITS
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Before installing or servicing system, always turn off main power to system. There may be more than one disconnect switch.Turn off accessory heater power switch if applicable.
1. Open allelectrical disconnects and install lockout tag before starting any service work.
2. Remove side duct covers to access bottom return and supply knockouts.
NOTE: These panels are held in place with tabs similar to an electrical knockout.
3. Use a screwdriver and hammer to remove the panels in the bottom of the composite unit base.
4. Ensure the side duct covers are in place to block off the horizontal air openings (See Fig. 11).
Step 6—Provide for Condensate Disposal
NOTE: Ensure that condensate--water disposal methods comply
with local codes, restrictions, and practices.
Theunits disposeof condensate through a3/4 in.NPT femalefitting that exits on the compressor end of the unit. Condensate water can be drained directly onto the roof in rooftop installations (where permitted) or onto a gravel apron in ground level installations. Install a field--supplied condensate trap at end of condensate connection to ensure proper drainage. Make sure that the outlet of the trap is at least 1 in. lower than the drain--pan condensate connection to preventthe pan fromoverflowing. Primethe trap with water. When using a gravel apron, make sureit slopes away fromthe unit.
If the installation requires draining the condensate water away from the unit, install a field--supplied 2 --in. trap at the condensate connection to ensure proper drainage. Condensate trap is available as an accessory or is field--supplied. Make sure that the outlet of the trap is at least 1 in. lower than the unit drain--pan condensate connection to prevent the pan from overflowing. Connect a drain trough using a minimum of field--supplied 3/4 -- in. PVC or field--supplied 3/4 --in. copper pipe at outlet end of the 2 -- in. trap (See Fig. 12). Do not undersize the tube. Pitch the drain trough downwardat a slopeof at least1 in.for every 10 ft.of horizontal run. Be sure to check the drain trough for leaks. Prime the trap at the beginning of the cooling season start--up.
WARNING
50CR
9
Page 10
Table 1—Physical Data -- Unit 50CR
UNIT SIZE 024 030 036 042 048 060
NOMINAL CAPACITY (ton) 2 2--1/2 3 3--1/2 4 5
OPERATING WEIGHT (lb.) 350 350 373 440 463 499
Refrigerant (R-- 410A) Quantity (lb.) 7.5 8 9.5 10.8 11. 5 14.0
REFRIGERANT METERING DEVICE TXV
50CR
HIGH--PRESSURE SWITCH (psig)
LOSS--O F -- CHARGE/LOW--PRESSURE SWITCH
*Required filter sizes shown are based on the larger of the ARI (Air Conditioning and Refrigeration Institute) rated cooling airflow or the heating airflow velocity of 300 ft/minute for throw away type o r 450 f t/minute for high-- capacity type. Air filter pressure drop for non--standard filters must not exceed 0.08 in. wg.
Compressor Scroll
ORIFICE OD (in.) 0.035 (2) 0.035 (2) 0.038 (2) 0.038 (2)
OUTDOOR COIL
RowsFins/in. 221 221 221 221 221 221
Face Area (sq. ft.) 12.3 12.3 13.6 15.4 17.2 19.4
OUTDOOR FAN
Nominal Cfm 2700 2700 2800 2800 3300 3300
Diameter 22 22 22 22 22 22
Motor HP (RPM) 1/8 (825) 1/8 (825) 1/8 (825) 1/8 (825) 1/4 (1100) 1/4 (1100)
INDOOR COIL
RowsFins/in. 315 315 415 315 415 417
Face Area (sq. ft.) 3.7 3.7 3.7 4.7 4.7 5.7
INDOOR BLOWER
Nominal Airflow (Cfm)
Size (in.) 10x10 10x10 11x1 0 11x 1 0 11x 1 0 11x 1 0
Motor HP (RPM) 1/2 1/2 3/4 3/4 3/4 1
Cutout
Reset (Auto)
(Liquid Line) (psig)
Cutout
Reset (Auto)
Return-- Air Filters (in.)*
Throwaway
Comfort Variable based on Comfort Roll back (see User Interface instructions for more information).
Efficiency 700 875 1050 1225 1400 1750
Max 800 1000 1200 1400 1600 2000
20x24x1 20x24x1 24x30x1 24x36x1 24x36x1 24x36x1
0.038 (Left OD Coil)
0.046 (Right OD Coil)
650 ± 15 420 ± 25
20 ± 5
45 ± 10
0.042 (Left OD Coil)
0.052 (Right OD Coil)
TOP COVER
USER INTERFACE
RETURN AIR
FROM POWER SOURCE
DISCONNECT
PER NEC* FROM GAS LINE
*NEC - NATIONAL ELECTRICAL CODE
Fig. 10 -- Typical Installation
10
A06091
Page 11
1” (25mm) MIN.
Duct Covers
Fig. 11 -- 50CR with Duct Covers On
TRAP OUTLET
A05301
!
UNIT COMPONENT DAMAGE HAZARD
Failure to follow this caution may result in damage to the unit being installed.
1. Make all electrical connections in accordance with NEC
ANSI/NFPA (latest edition) and local electrical codes governing such wiring. In Canada, all electrical connections must be in accordance with CSA standard C22.1 Canadian Electrical Code Part 1 and applicable local codes. Refer to unit wiring diagram.
2. Use only copper conductor for connections between
field--supplied electrical disconnect switch and unit. DO NOT USE ALUMINUM WIRE.
3. Be sure that high --voltagepower to unit is within operating
voltage range indicated on unit rating plate. On 3--phase units,ensure phases are balanced within 2 percent. Consult local power company for correction of improper voltage and/or phase imbalance.
4. Insulate low-- voltage wires for highest voltage contained
withinconduit when low--voltagecontrol wiresarein same conduit as high--voltage wires.
5. Do not damageinternal componentswhen drilling through
any panel to mount electrical hardware, conduit, etc.
CAUTION
50CR
2” (50mm) MIN.
C99013
Fig. 12 -- Condensate Trap
Step 7—Install Electrical Connections
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
The unit cabinet must have an uninterrupted, unbroken electricalground to minimizethe possibility of personal injury if an electrical fault should occur. This ground may consist of an electrical wire connected to the unit ground screw in the control compartment, or conduit approved for electrical ground when installed in accordance with NEC, ANSI/NFPA American National Standards Institute/National Fire Protection Association (latest edition) (in Canada, Canadian Electrical Code CSA C22.1) and local electrical codes.
HIGH--VOLTAGE CONNECTIONS
The unit must have a separate electrical service with a field--supplied, waterproofdisconnect switch mountedat, or within sight from the unit. Refer to the unit rating plate, NEC and local codes for maximum fuse/circuit breaker size and minimum circuit amps (ampacity) for wire sizing (See Table 2 for electrical data).
The field--supplieddisconnect maybe mounted on the unit overthe high-- voltage inlet hole (See Fig. 6 and 7).
If the unit has an electric heater, a second disconnect may be required. Consult the Installation, Start--Up, and Service Instructions provided with the accessory for electrical service connections.
Operation of unit on improper line voltage constitutes abuse and may cause unit damage that could affect warranty.
WARNING
ROUTING POWER LEADS INTO UNIT
Use only copper wire between disconnect and unit. The high voltage leads should be in a conduit until they enter the duct panel; conduit termination at the duct panel must be watertight. Run the high-- voltage leads throughthe powerentry knockout on the power entry side panel. See Fig. 6 and 7 for location and size. For single--phase units, connect leads to the black and yellow wires ; for 3--phase units, connect the leads to the black, yellow, and blue wires.
CONNECTING GROUND LEAD TO GROUND SCREW
Connectthe ground leadto thechassis using theground screw in the wiring splice box (See Fig. 14 and 17).
ROUTING CONTROL POWER WIRES
For detailed instruction on the low voltage connections to the User Interface (UI), refer to the UI installation guide.
Form a drip-- loop with the control leadsbeforeroutingthem into the unit. Route the low voltage control leads through grommeted, low-- voltagehole providedinto unit (See Fig. 6 and 7). Connect user interface leads to unit control power leads as shown in Fig. 14.
The unit transformer supplies 24--v power for complete system including accessory electrical heater.A fuse is provided in the 24--v circuit on the control board (See Fig. 19); see the caution label on the transformer. Transformer is factory wired for 230--v operation. If supply voltage is 208--v, rewiretransformer primary as described in Special Procedures for 208--v Operation section.
11
Page 12
Table 2 — Electrical Data—50CR
UNIT SIZE
024 208/230--1--60 187 253 13.5 61.0 0.9 4.3
030 208/230--1--60 187 253 15.9 73.0 0.9 4.3
036
V--PH--HZ
208/230--1--60 187 253 16.9 83.0 0.9 6.8
VO LTAG E
RANGE
MIN MAX RLA LRA kW*
COMPRESSOR OFM
FLA
IFM
FLA
50CR
208/230--3--60 187 253 12.2 77.0 1.6 6.8
208/230--1--60 187 253 22.4 105.0 0.9 6.8
042
208/230--3--60 187 253 15.4 88.0 0.9 6.8
208/230--1--60 187 253 21.3 109.0 1.6 6.8
048
208/230--3--60 187 253 14.7 91.0 1.6 6.8
208/230--1--60 187 253 26.9 145.0 1.5 9.1
060
208/230--3--60 187 253 17.6 123.0 1.5 9.1
ELECTRIC HEAT
NOMINAL
-- / -- -- / -- 22.1/22.1 30/30
3.8/5 18.1/20.8 44.6/48.1 50/50
5.4/7.2 26.0/30.0 54.6/59.6 60/60
7.5/10.0 36.1/41.7 67.2/74.2 70/80
-- / -- -- / -- 25.1/25.1 30/30
3.8/5 18.1/20.8 47.6/51.1 50/60
5.4/7.2 26.0/30.0 57.6/62.6 60/70
7.5/10.0 36.1/41.7 70.2/77.2 80/80
-- / -- -- / -- 29.5/29.5 35/35
3.8/5 18.1/20.8 52.1/55.6 60/60
5.4/7.2 26.0/30.0 62.0/67.0 70/70
7.5/10.0 36.1/41.7 74.7/81.6 80/90
11.3/15.0 54.2/62.5 97.2/107.7 100/110
-- / -- -- / -- 23.7/23.7 30/30
3.8/5.0 10.4/12.0 36.7/38.7 45/45
7.5/10.0 20.8/24.1 49.7/53.7 50/60
11.3/15.0 31.3/36.1 62.7/68.8 70/70
-- / -- -- / -- 35.7/35.7 45/45
3.8/5.0 18.1/20.8 58.3/61.7 70/70
5.4/7.2 26.0/30.0 68.2/73.2 80/80
7.5/10.0 36.1/41.7 80.8/87.8 90/90
11.3/15.0 54.2/62.5 103.4/113.8 110/125
15.0/20.0 72.2/83.3 126.0/139.9 150/150
-- / -- -- / -- 27.0/27.0 35/35
3.8/5.0 10.4/12.0 40.0/42.0 50/50
7.2/10.0 20.8/24.1 53.0/57.0 60/60
11.3/15.0 31.3/36.1 66.0/72.1 70/80
15.0/20.0 41.6/48.0 78.9/86.9 80/90
-- / -- -- / -- 35.0/35.0 45/45
3.8/5.0 18.1/20.8 57.6/61.1 70/70
5.4/7.2 26.0/30.0 67.5/72.5 80/80
7.5/10.0 36.1/41.7 80.2/87.1 90/90
11.3/15.0 54.2/62.5 102.7/113.2 110/125
15.0/20.0 72.2/83.3 125.3/139.2 150/150
-- / -- -- / -- 26.8/26.8 35/35
3.8/5.0 10.4/12.0 39.8/41.8 50/50
7.5/10.0 20.8/24.1 52.8/56.8 60/60
11.3/15.0 31.3/36.1 65.9/71.9 70/80
15.0/20.0 41.6/48.0 78.7/86.7 80/90
-- / -- -- / -- 44.2/44.2 60/60
3.8/5.0 18.1/20.8 66.8/70.3 80/90
5.4/7.2 26.0/30.0 76.7/81.7 90/100
7.5/10.0 36.1/41.7 89.4/96.3 100/110
11.3/15.0 54.2/62.5 111.9/122.4 125/125
15.0/20.0 72.2/83.3 134.5/148.4 150/150
-- / -- -- / -- 34.6/34.6 40/40
3.8/5.0 10.4/12.0 47.6/49.6 60/60
7.5/10.0 20.8/24.1 60.7/64.7 70/70
11.3/15.0 31.3/36.1 73.7/79.7 80/80
15.0/20.0 41.6/48.0 86.6/94.6 90/100
FLA MCA MOCP
SINGLE POINT POWER
SUPPLY
12
Page 13
LEGEND
g
r
FLA — Full Load Amps LRA — Locked Rotor Amps MCA -- Minimum Circuit Amps MOCP — Maximum Overcurrent Protection RLA — Rated Load Amps
®
NO TES:
1. In compliance with NEC (National Electrical Code) requirements for multimotor and combination load equipment (refer to NE C Articles 430 and 440), the overcurrent protective device for the unit shall be Power Supply fuse. The CGA (Canadian Gas Association) units may be fuse or circuit break er.
2. Minimum wire size is based on 60 C copper wire. I f other than 60 C wire is used, or if length exceeds wire length in table, determine siz e from NEC..
3. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply volt­age is greater than 2%.
the percentage of voltage imbalance.
Use the following formula to determine
% Voltage imbalance
= 100 x
Heater capacity (kW) based on heater voltage of 208v & 240v. If power distibution voltage to unit varies from rated heater
*
volta
max voltage deviation from average voltage
average voltage
e, heater kW will vary accordingly.
Fig. 13 -- Electrical Data Legend
EXAMPLE: Supply voltage is 230-3-60.
AB = 228 v BC = 231 v AC = 227 v
Average Voltage =
228 + 231 + 227
3
686
=
3
= 229
Determine maximum deviation from average voltage.
(AB) 229 ­(BC) 231 ­(AC) 229 -
228 =1v 229 =2v
227 =2v Maximum deviation is 2 v.
Determine percent of voltage imbalance.
% Voltage Imbalance = 100 x
2
229
= 0.8%
This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.
C03014
50CR
User Interface
Humidifier (Optional)
D
C
B
A
C
24vac
Infinity Control Board
D
C
B
A
OAT
RYOWCHUM
LEGEND
Field Control-Voltage
Wiring
Fig. 14 -- Control Voltage Wiring Connections
Outdoor Air Thermisto
(if used)
A05302
13
Page 14
50CR
Fig. 15 -- Wiring Schematics--50CR Single Phase
14
7.0
A05304
Page 15
50CR
Fig. 16 -- Wiring Schematics--50CR Three Phase
15
5.0
A05259
Page 16
GROUND SCREW
(IN SPLICE BOX)
GROUND
LEAD
SINGLE-PHASE
L1 CONNECTIONS TO DISCONNECT PER NEC
3-PHASE CONNECTIONS
L2
L3
NOTE: Use copper wire only.
LEGEND NEC – National Electrical Code
Field Wiring Splice Connections
Fig. 17 -- Line Power Connections
50CR
Fig. 18 -- Control Plate
The low--voltage circuit is fused by a board--mounted automotive fuse placed in series with transformer SEC1 and R circuit. The C circuit of transformer circuit is referenced to chassis ground through a printed circuit run at SEC2 and metal control board mounting eyelets. Check to be sure control board is mounted securely using both factory--installed screws.
BLK
YEL
BLU
C99057
A05303
ACCESSORY INSTALLATION
A. Accessory Electric Heaters
Electric heaters may be installed in 50CR per instructions supplied with electric heater package. See unit rating plate for factory--approved electric heater kits.
NOTE: Units installed without electric heat should have a factory--supplied sheet metal block--off plate installed over heater opening. This reduces air leakage and formation of exterior condensation.
B. Outdoor Air Thermistor (OAT)
A 2 --screw terminal strip is provided for connection of an outdoor temperature thermistor. This strip is marked OAT.
NOTE: While the installation of an outdoor temperature sensor using the Infinity control board OAT terminals is optional, certain Infinity features(ComfortHeat, electric heat lockout, autohumidity control) will be lost.
OAT input is used to supply outdoor temperature data for system level functions and for temperature display on User Interface.
Using two wires of field--supplied thermostat wire cable, wire one lead of thermistor to one screw terminal and the other lead to remaining screw terminal; there is no polarity to be observed. It is strongly recommended that two wires be used to connect the thermistor to eliminate noise interference in temperature reading. If there are not two spare wires available in cable, one wire may be used to connect thermistor to OA T screw terminal 1 and the other lead of the thermistor can be wired to 24--vac COM (C) wire. OAT screw terminal 1 is terminal located closest to the ABCD system communications and is marked with a small number 1 next to the terminal strip.
NOTE: Mis--wiring OAT inputs will not cause damage to either Infinity control or thermistor. If the thermistor is wired incorrectly, no reading will appear at User Interface. Re--wire thermistor correctly for normal operation.
C. Humidifier Connections
The Infinity control board terminal marked HUM is provided for low voltage (24--vac) control of a humidifier. No humidistat is required as User Interface monitors indoor humidity. When commanded to operate humidifier, the unit control will energize the HUM output to turn humidifier on and de--energize HUM output to turn humidifier off. Wire HUM and C terminals directly to humidifier as shown in Fig. 14.
SPECIAL PROCEDURES FOR 208--V OPERATION
Be sure unit disconnect switch is open.
Disconnect the yellow primary lead from the transformer. See unit wiring label. (See Fig. 15, 16 and 18)
Connect the yellow primary lead to the transformer terminal labeled 200--v.
16
Page 17
5
SEC-2 SEC-1
HK38EA002
HEATER
1
F1
STATUS
ABCD
1
COMM
1
OAT
1
HUM C W O Y R
MOTOR
A03169
Fig. 19 -- Detail of Printed Circuit Board
PRE--START--UP
!
WARNING
FIRE,EXPLOSION, ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death and/or property damage.
1. Follow recognized safety practices and wear protective goggles when checking or servicing refrigerant system.
2. Do not operate compressor or provide any electric power to unit unless compressor terminal cover is in place and secured.
3. Do not remove compressor terminal cover until all electrical sources are disconnected and tagged.
4. Relieve and recover all refrigerant from system before touching or disturbing anything inside terminal box if refrigerant leak is suspected around compressor terminals.
5. Never attempt to repair soldered connection while refrigerant system is under pressure.
6. Do not use torch to remove any component. System contains oil and refrigerant under pressure.
7. To remove a component, wear protective goggles and proceed as follows:
a. Shut off electrical power to unit and install lockout
tag.
b. Relieve and reclaim all refrigerant from system
using both high-- and low--pressure ports.
c. Cut component connecting tubing with tubing
cutter and remove component from unit.
d. Carefully unsweat remaining tubing stubs when
necessary. Oil can ignite when exposed to torch flame.
Use the Start--Up Checklist supplied at the end of this book and proceed as follows to inspect and prepare the unit for initial start--up:
1. Remove all access panels.
2. Read and follow instructions on all DANGER,WARNING, CAUTION, and INFORMATION labels attached to, or shipped with unit.
3. Make the following inspections:
a. Inspect for shipping and handling damages, such as
broken lines, loose parts, disconnected wires, etc.
b. Inspect for oil at all refrigerant tubing connections and on
unit base. Detecting oil generally indicates a refrigerant leak. Leak test all refrigerant tubing connections using electronic leak detector, or liquid--soap solution. If a refrigerant leak is detected, see following Check for Refrigerant Leaks section.
c. Inspect all field-- and factory--wiring connections. Be
sure that connections are completed and tight.
d. Ensure wires do not touch refrigerant tubing or sharp
sheet metal edges.
e. Inspect coil fins. If damaged during shipping and
handling, carefully straighten fins with a fin comb.
4. Verify the following conditions:
a. Make sure that outdoor fan blade is correctly positioned
in fan orifice (See Fig. 24).
b. Make sure that condensate drain pan and trap are filled
with water to ensure proper drainage.
c. Make sure that all tools and miscellaneous loose parts
have been removed.
5. Compressors are internally spring mounted. Do not loosen or remove compressor holddown bolts.
6. Each unit system has two Schrader--type ports,one low--side Schrader fitting located on the suction line, and one high-- side Schrader fitting located on the compressor discharge line. Be sure that caps on the ports are tight.
START--UP
Step 1—Unit Start-- Up
NOTE: Always check high-- and low--voltage supply to the unit components. Check the integrity of the plug receptacle connections and unit wiring harness prior to assuming a component failure.
A. LED Description:
LEDs built into Infinityt control board provide installer or service person information concerning operation and/or fault condition of the unit control and ECM motor. This information is also available at the system user interface in text with basic troubleshooting instructions. Careful use of information displayed will reduce the need for extensive manual troubleshooting.
The amber LED located at bottom center of control adjacent to motor harness plug is Motor Status LED and it is labeled MOTOR. A second amber LED located in upper right center of control adjacent to System Communications connector (A,B,C,D) is the System Status LED and it is labeled STATUS. The green LED labeled COMM is also located adjacent to System Communications connector, below STATUS LED, and is used as an indicator of system communications status. Status Codes will be displayed on the STATUS LED using the following protocol:
1. The number of short flashes indicates first digit of code.
2. The number of long flashes indicates second digit of code.
3. A short flash is 0.25 secondson. A long flash is1 second on.
4. The time between flashes is 0.25 seconds.
5. The time between last short flash and first long flash is 1 second.
6. The LED will be off for 2.5 seconds before repeating code.
B. Control Start--Up and System Communications
Troubleshooting:
On powerup, green COMM LED will be turned offuntil successful system communications areestablished (this should happen within
17
50CR
Page 18
10 seconds). Once communications with User Interface are successful, COMM LED will be lit and held on. At the same time, amber STATUS LED will be lit and held continuously on until a request for operating mode is received. The STATUS LED will be on any time unit is in idle mode.
If, at any time, communications are not successful for a period exceeding 2 minutes, the Infinity control will only allow emergency heating or cooling operationusing a common thermostat and the R, C, Y, O, W terminal strip connections and will display Status Code 16, System Communication Fault, on amber STATUS LED. No further troubleshooting information will be available at User Interface until communications are re--established.
If COMM LED does not light within proper time period and status code is not displayed;
1. Check system transformer high -- and low-- voltage to be sure the system is powered.
2. Check fuse on control board to be sure it is not blown. Iffuse is open, check system wiring before replacing it to be sure a
50CR
short does not cause a failure of replacement fuse.
If COMM LED does not light within proper time period and status code is displayed,
1. Check system wiring to be sure User Interface is powered and connections are made A to A, B to B, etc. and wiring is not shorted. Mis--wiring or shorting of the ABCD communications wiring will not allow successful communications.
NOTE:Shortingor mis--wiringlow--voltage systemwiring willnot cause damage to unit control or user interface but may cause low voltage fuse to open.
C. ECM Motor Troubleshooting
The ECM motor used in this product consists of two parts: the control module and the motor winding section. Do not assume motor or module is defective if it will not start. Use the designed--in LED information aids and follow troubleshooting steps described below before replacing motor control module or entire motor. Motor control module is available as a replacement part.
VERIFY MOTOR WINDING SECTION
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Afterdisconnecting power from the ECM motor,wait at least 5 minutes before removing the control section. Internal capacitors require time to discharge.
Before proceeding to replace a motor control module:
1. Check motor winding section to be sure it is functional.
2. Remove motor control module section and unplug winding plug. Motor shaft should turn freely,resistance between any two motor leads should be similar and resistance between any motor lead and unpainted motor end should exceed 100,000 ohms.
3. Failing any of these tests, entire ECM motor must be replaced.
4. Passing all of the tests, motor control module alone can be replaced.
MOTOR TURNS SLOWLY
1. Low static pressure loading of blower while access panel is removed will cause blower to run slowly. Particularly at low airflow requests. This is normal,do not assume a fault exists.
WARNING
2. Recheck airflow and system static pressure using User Interface service screens with access panel in place.
NOTE: Blower motor faults will not cause a lockout of blower operation. The unit control will attempt to run the blower motor as long as User Interface maintains a demand for airflow. The unit control will not operate electric heaters while a fault condition exists. The unit control communicates with the motor at least once everyfive seconds,even when the motoris idle.If, during operation, theunit control does not communicatewith the motor for more than 25 seconds, the motor will shut itself down and wait for communications to be reestablished.
D. Using Motor LED in Troubleshooting
The MOTOR LED is connected to the blower motor communicationline and workswith the unitcontrolmicroprocessor and the STATUS LED to provide unit operation and troubleshooting information. When the motor is commanded to operate, the MOTOR LED will be turned on and will flash each time instructionsare sent to the motor. When the motor is commandedto stop, the MOTOR LED will be turned off.
If the MOTOR LED is lit, flashing, and the motor is running, or if the MOTOR LED is off and the motor is stopped, operation is normal and no motor fault exists.
If the MOTOR LED is lit, flashing, and the motor does not run, or if the MOTOR LED is off and the motor is running, check the STATUS LED for the Status Code. Refer to the troubleshooting instructions for the indicated Status Code in Section E, Unit Troubleshooting.
E. Unit Troubleshooting
Unit faults indicated by flashing codes on the amber system STATUS LED can be resolved using troubleshooting information provided below. Codes are listed in order of their priority, highest to lowest. Though multiple faults can exist at any time, only the highest priority code will be displayed on STATUS LED. Clearin g the indicated fault when multiple faults exist will cause the next highestpriority Status Code to be flashed.All existing faults,aswell as a fault history, can be viewed at User Interface.
STATUS CODE 45, CONTROL BOARD TEST FAULT
Unit control has failed internal start--up tests and must be replaced. No other service procedure will correct.
STATUS CODE 37, HEATER OUTPUT SENSED “ON” WHEN NOT ENERGIZED:
Unit control is provided with circuitry to detect presence of a 24 --vac signal on electric heater stage 1 and stage 2 outputs.
If unit control detects a 24--vac signal on either heater stage output and it is not supplying signal, Status Code 37 will be displayed on STATUS LED. Unit control will turn off output and command blowermotor to supply an airflowdetermined to be safe for current operation mode with electric heaters energized.
To find the fault:
1. Stop all system operations at User Interface and check heater stage 24--vac outputs.
2. Disconnect electric heater at power and check heater wiring for faults. See Status Code 36 for more information.
STATUS CODE 44, MOTOR COMMUNICATION FAULT
The MOTOR LED is connected to the blower motor communicationline and workswith the unitcontrolmicroprocessor and STATUS LED to provide unit operation and troubleshooting information.
When motor is commanded to operate, the MOTOR LED will be turned on and will flash each time instructions are sent to the motor.
18
Page 19
When the motor is commanded to stop, the MOTOR LED will be turned off. The MOTOR LED will not flash to indicate communications when it is turned off.
Unit control is constantly communicating with the motor, even when the motor and MOTOR LED are off. If motor does not acknowledge receipt of communications, the control will display Status Code 44 on STATUS LED and continue to try to communicate with the motor. If motor acknowledges communication, status code will be cleared.
If MOTOR LED is lit and flashing and motor does not run:
1. Check the STATUS LED. If STATUS LED is indicating a Status 44 code, check the motor wiring harness for proper connection to control and motor receptacles.
2. Check motor wiring harness to be sure all wiring complies with wiring diagram description, makes a complete circuit from connector to connector, and is not shorted.
3. Check 12-- vdc low voltage supply to motor at pins 1 (+) and 2 (--) of motor header connection to unit control.
If all checksare normal, unit control is good and control module on motor may need replacement. Check motor and Motor Control Module following the instructions in Section C, ECM Motor Troubleshooting.
Shorted or mis--wiring of the low voltagemotor harness wiring will not cause damage to unit control or to motor control module.
If the MOTOR LED is off, STATUS LED is indicating a Status Code 44 and motor is running:
1. Disconnect the motor harness at the unit control. If motor continues to run, unit controlis good and control module on motor may need replacement.
STATUS CODE 25, INVALID MOTOR / MODEL SELECTION
On initial start--up, unit control shall poll motor for its size data and check unit size data stored in unit control memory.
1. If motor size is incorrect for unit size or size data is invalid, Status Code 25 will be displayed on STATUS LED.
2. If model size data is missing (as is the case when a replacement control board is installed), system User Interface will prompt installer to enter correct model size from a list of valid sizes.
3. If motor size is incorrect for model size, motor must be replaced with proper size motor. Unit control will not respond to operation requests until this fault condition is resolved.
STATUS CODE 26, INVALID HEATER SIZE
On initial power--up, unit control will write into memory electric heater size as read from heater if heater is provided with Identifier Resistor (IDR). Heater size must be valid for combination of indoor and outdoor components installed. Unit control will read IDR value connected to pins 1 and 2 of heater harness connector. If no resistor isfound, system User Interfacewillprompt installerto verify that no heater is installed. Verifying that this is correct will establish that the unit is operating without an electric heater accessory. Upon choosingnegative option,installer willbe promptedto select heater size installed from a list of valid heater sizes for unit size installed.
If heater ID resistor value read is invalid, Status Code 26 will be displayed on STATUS LED.
Ifheater installed is equippedwith a resistorconnected to pins 1 and 2 of heater harness connector and status code 26 is displayed on STATUS LED:
1. Check wiring harnessconnectionsto besure connectionsare secure.
2. If symptoms persist, disconnect wiring harness at unit control board and check for a resistance value greater than 5000 ohms.
3. Check for proper wiring of resistor assembly.
4. Make sure heater size installed is an approved size for unit and size installed.
NOTE: Unit control will not operateelectric heateruntil this Status Code is resolved. If the heater size is set through the User Interface, the heater will be operated as a single stage heater. If staging is desired, the IDR value must be read in by the unit control.
STATUS CODE 36, HEATER OUTPUT NOT SENSED WHEN ENERGIZED
Unit control is provided with circuitry to detect presence of a 24 --vac signal on electric heater stage 1 and stage 2 outputs.
If unit control energizes either heater stage and does not detect the 24--vac signal on output, Status Code 36 will be displayed on the STATUS LED, unit control will continue to energize heater output(s) and adjust blower operation to a safe airflow level for energized electric heat stage(s).
To find the fault:
1. Check for 24--vac on heater stage outputs. Unit control or sensing circuit may be bad.
NOTE: It may be useful as an electric heater troubleshooting procedure to disconnectthe system communications to force Status Code 16 enabling of emergency heat mode. It is difficult to know which heater output is energized or not energized in normal operation. When unit is operated in emergency heat mode using electric heaters, both outputs are energized and de--engergized together. Terminal strip inputs to control canthen be connectedR to W to turn on both electric heat outputs. Heater output sensing circuits can then be checked to resolve Status Code 36 or 37 problems.
STATUS CODE 41, BLOWER MOTOR FAULT
If MOTOR LED is lit and flashing and motor does not run:
1. Check STATUS LED. If STA TUS LED is indicating Status Code 41, motor control has detected that the motor will not comeup to speedwithin 30 seconds of being commanded to run or that the motor has been slowed to below 250 rpm for more than 10 seconds after coming up to speed. Motor wiring harness and unit control are operating properly, do not replace.
2. Check to be sure that the blower wheel is not rubbing the housing.
3. Check motor to be sure that the motor shaft is not seized (motor control module must be removed and electronics disconnected from windings to perform this check properly).
4. Check motor windings section following instructions in Section C, ECM Motor Troubleshooting.
If all these checks are normal, the motor control module may need replacement.
STATUS CODE 16, SYSTEM COMMUNICATION FAULT
If, at any time, system communications are not successful for a period exceeding 2 minutes, the unit control will only allow emergency heating or cooling operation using a common thermostat, and the R, C, Y,O, W terminal strip connections and will display Status code 16 on the amber STA TUS LED (see section E, Emergency Heating and Cooling Modes). No further unit troubleshooting information will be available at the User Interface until communications are re--established.
50CR
19
Page 20
Check system wiring to be sure the User Interface is powered and connections are made A to A, B to B, etc., and wiringis not shorted. Mis--wiring or shorting of the ABCD communications wiring will not allow successful communications. Correcting wiring faults will clear the code and re--establish communications.
Shortingor mis--wiring the low voltagesystemwiring will notcause damage to unit control or to User Interface but may cause the low voltage fuse to open.
STATUS CODE 46, BROWNOUT CONDITION
If the secondary voltage of the transformer falls below 15--vac for a period exceeding 4 seconds, Status Code 46 will be displayed on STATUS LED and the User Interface will command the control board to turn off Y output controlling compressor.
When secondary voltage rises above 17--vac for more than 4 seconds, the brownout condition is cleared and normal system operation will resume subject to any minimum compressor off--delayfunction which maybe ineffect. Brownoutdoes notaffect blower or electric heater operation.
STATUS CODE 53, OUTDOOR AIR TEMPERATURESENSOR
50CR
FAULT
If an OAT sensor is found at power--up, input is constantly checked to be within a valid temperature range. If sensor is found to be open or shorted at any time after initial validation, Status Code 53 will be displayed at amber STATUS LED.
Check for faults in wiring connecting sensor to OAT terminals. Using an Ohm meter, check resistance of thermistor for a short or open condition.
If thermistor is shorted or open, replace it to return the system to normal operation.If faultis inthe wiring connections, correcting the fault will clear the code and return the system to normal operation.
NOTE: If fault condition is an open thermistor or a wiring problem that appears to be an open thermistor and the power to the unit is cycled off, the fault code will be cleared on the next power--up but the fault will remain and system operation will not be as expected.
This is because on power--up, the unit control cannot discern the difference between an open sensor or if a sensor is not installed.
Step 2—Sequence of Operation
The packaged heat pump is designed for installation with a communicating User Interface. This unit will not respond to commands provided by a common thermostat except under certain emergency situations described in Step 1—Start--Up.
The User Interface uses temperature, humidity and other data supplied from indoor and outdoor system components to control heating or cooling system for optimum comfort. The unit will be commanded by User Interface to supply airflow. The unit will operate the indoor blower at requested airflow for most modes.
The nominal requested airflow will be 350 cfm per ton of nominal cooling capacity as defined by unit size. Actual airflow request will be adjusted from nominal using indoor and outdoor temperature and indoor humidity data to optimize the system operation for occupant comfort and system efficiency. Refer to User Interface literature for further system control details.
Airflow during electric heater operation must be greater than a minimum level for safe operation. If User Interface instructs unit to turn on electric heat and the requested airflow is less than the minimum level the unit control will override requested value.
NOTE: Once the compressor has started and then has stopped, it should not be started again until 4 minutes have elapsed. The cooling cycle remains “on” until the room temperature drops to point that is slightly below the cooling control setting of the user interface. Additionally, there is a 5--minute compressor delay built into the control for heat pump heating mode.
Step 3—Check for Refrigerant Leaks
Locate and repair refrigerant leaks and charge the unit as follows:
1. Use both high-- and low--pressure ports to relieve system pressure and reclaim remaining refrigerant.
2. Repair leak following accepted practices.
NOTE: Install a bi--flow filter drier whenever the system has been opened for repair.
3. Check system for leaks using an approved method.
4. Evacuate refrigerant system and reclaim refrigerant if no additional leaks are found.
5. Charge unit with Puron (R--410A) refrigerant, using a volumetric--charging cylinder or accurate scale. Refer to unit rating plate for required charge.
Step 4—Start--Up Adjustments
Complete the required procedures given in the Pre--Start--Up section before starting the unit. Do not jumper any safety devices when operating the unit. Do not operate the unit in cooling mode when the outdoor temperature is below 40°F (unless accessory low-- ambient kit is installed). Do not rapid cycle the compressor. Allow 5 min. between “on” cycles to prevent compressor damage.
CHECKING COOLING AND HEATING CONTROL OPERATION
Start and check the unit for proper control operation as follows:
1. Place room UI SYSTEM switch or MODE control in OFF position. Observe that blower motor starts when FAN mode is placed in FAN ON position and shuts down within 60 sec (030-- 060 size) or 30 sec (024 size) when FAN MODE switch is placed in AUTO position.
2. Placesystemswitch or MODE controlin HEATposition.Set control above room temperature. Observe that compressor, outdoor fan, and indoor blower motors start. Observe that heating cycle shuts down when control setting is satisfied.
3. When using an automatic changeover room thermostat, place both SYSTEM or MODE control and FAN mode switches in AUTO positions. Observe that unit operates in cooling mode when temperature control is set to “call for cooling” (below room temperature), and unit operates in heating mode when temperature control is set to “call for heating” (above room temperature).
IMPORTANT: Three-- phase, scroll compressors are direction oriented. Unit must be checked to ensure proper compressor 3--phase power lead orientation. If not corrected within 5 minutes, the internal protector will shut off the compressor. The 3 --phase power leads to the unit must be reversed to correct rotation. When turning backwards, the difference between compressor suction and discharge pressures may be dramatically lower than normal.
20
Page 21
HP S
ACCUMULATOR
COMPRESSOR
LEGEND
HPS – High Pressure Switch LCS – Loss of Charge Switch
Accurater
®
Metering De vice
Arrow indicates direction of flo w
OUTDOOR COIL
TXV in Metering
Position
LCS
Bypass
Position
Fig. 20 -- Typical Heat Pump Operation, Cooling Mode
INDOOR COIL
50CR
C03011
HP S
ACCUMULATOR
COMPRESSOR
LEGEND
HPS – High Pressure Switch LCS – Loss of Charge Switch
®
Accurater
Metering De vice
Arrow indicates direction of flo w
OUTDOOR COIL
TXV in Bypass
Position
LCS
Metering
Position
Fig. 21 -- Typical Heat Pump Operation, Heating Mode
INDOOR COIL
C03012
21
Page 22
CHECKING AND ADJUSTING REFRIGERANT CHARGE
The refrigerant system is fully charged with Puron (R--410A) refrigerant and is tested and factory sealed.
NOTE: Adjustment of the refrigerant charge is not required unless the unit is suspected of not having the proper R--410A charge. The charging label and the tables shown refer to system temperatures and pressures in cooling mode only. A refrigerant charging label is attached to the outside of the service access door. If charge level is suspect in heating mode, reclaim all refrigerant and charge to informative plateamount. (This information may be obtained from the physical data table also.) The charging label and the tables shown refer to system temperatures and pressures in cooling mode only. A refrigerant charging label is attached to the outside of the service access door.
IMPORTANT: When evaluating the refrigerant charge, an indicated adjustment to the specified factory charge must always be very minimal. If a substantial adjustment is indicated, an abnormal condition exists somewhere in the cooling system, such as
50CR
insufficient airflow across either coil or both coils.
REFRIGERANT CHARGE
The amount of refrigerant charge is listed on the unit rating plate and/or the physical data table. Refer to the Refrigeration Service Techniques Manual, Refrigerants Section.
NO CHARGE
Check for leak. Use standard evacuating techniques. After evacuating system, weigh in the specified amount of refrigerant (refer to system rating plate).
LOW CHARGE COOLING
Use Cooling Charging Chart (Fig. 22). Vary refrigerant until the conditions of the chart are met. Note that charging charts are different from type normally used. Charts are based on charging the units to correct subcooling for the various operating conditions. Accurate pressure gauge and temperature sensing devices are required. Connect the pressure gauge to the service port on the suction line. Mount the temperature sensing device on the suction line and insulate it so that the outdoor ambient does not affect the reading. Indoor airCFM must be within the normaloperating range of the unit.
TO USE COOLING CHARGING CHARTS
Take the liquid line temperature and read the manifold pressure gauges. Refer to the chart to determine what the liquid line temperature should be.
NOTE: If the problem causing the inaccurate readings is a refrigerant leak, refer to Check for Refrigerant Leaks section.
INDOOR AIRFLOW AND AIRFLOW ADJUSTMENTS
NOTE: Be sure that all supply-- and return--air grilles are open, free from obstructions, and adjusted properly.
Unit 50CR utilizes state of the art ECM (Electronic Computated Motor) ID Blower Motors. See user interface instructions for detailed information on adjusting airflow.
Step 5—Defrost Control
QUIET SHIFT
Quiet Shift is a field--selectable defrost mode, which will eliminate occasional noise that could be heard at the start of defrost cycle and restarting of heating cycle. It is selected by placing DIP switch 3 (on defrost board) in ON position.
When Quiet Shift switch is placed in ON position, and a defrost is initiated, the following sequence of operation will occur. Reversing valve will energize, outdoor fan will turn off, compressor will turn offfor 30 sec and then turn back on to complete defrost. At the start of heating after conclusion of defrost reversing valve will de--energize, compressor will turn off for another 30 sec, and the outdoor fan will stay off for 40 sec, before starting in the heating mode.
DEFROST
The defrost control is a time/temperature control which includes a field--selectable time period (DIP switch 1 and 2 on the board) between defrost cycles of 30, 60, 90, or 120 minutes (factory set at 30 minutes).
To initiate a forced defrost, two options are available depending on the status of the defrost thermostat.
If defrost thermostat is closed, speedup pins (J1) mustbe shorted by placing a flat head screw driver in between for 5 sec and releasing, to observe a complete defrost cycle. When the Quiet Shift switch is selected, compressor will be turned off for two 30 sec intervals during this complete defrost cycle, as explained previously. When Quiet Shift switch is in factory default OFF position, a normal and complete defrost cycle will be observed.
If defrost thermostat is in open position, and speedup pins are shorted (with a flat head screw driver) for 5 sec and released, a short defrost cycle will be observed (actual length is dependent upon the selected Quiet Shift position). When Quiet Shift switch is in ON position, the length of defrost is 1 minute (30 sec compressor off period followed by 30 sec of defrost with compressor operation). On return to heating operation, compressor will again turn off for an additional 30 sec and the outdoor fan for 40 sec. When the Quiet Shift is in OFF position, only a brief 30 sec cycle will be observed.
Ifit isdesirable to observe a complete defrostin warmer weather, the defrost thermostat must be closed as follows:
1. Turn off power to outdoor unit.
2. Disconnect outdoor fan motor lead from OF2 on control board (See Fig. 23). Tape to prevent grounding.
3. Restart unit in heating mode, allowing frost to accumulate on outdoor coil.
4. After a few minutes in heating mode, liquid-- line temperature should drop below closing point of defrost thermostat (approximately 30°F).
NOTE: Unit will remain in defrost untildefrostthermostat reopens at approximately 80 of defrost cycle time.
5. Turn off power to outdoor and reconnect fan motor lead to OF2 on control board after above forced defrost cycle.
NON--COMMUNICATING EMERGENCY COOLING / HEATING MODE
Thismode ofoperation is provided onlyin the case wherethe UI has failed or is otherwise unavailable. If communications cannot be established with the UI, the Infinity control board will enable the following thermostat input terminals to allow simple thermostatic control of the 50CR unit:
a. Y&Oforcooling
b. W for electric heat (if applicable)
c. Y for heat pump heat
The Infinity control will respond to cooling and heating demands with the maximum safe airflow based on electric heat size (if applicable) and unit capacity.
°F coil temperature at liquid line or remainder
22
Page 23
Required Subcooling oF (oC)
Outdoor Ambient Temperature
Model Size
024 10.3 ( 5.7 ) 9.8 ( 5.4 ) 9.4 ( 5.2 ) 9 ( 5 ) 8.6 ( 4.7 ) 189 61 56 51 46 41 1303 16 13 11 8 5 030 9.3 ( 5.2 ) 8.8 ( 4.9 ) 8.6 ( 4.8 ) 7.8 ( 4.3 ) 7 ( 3.9 ) 196 63 58 53 48 43 1351 17 15 12 9 6 036 17.6 ( 9.8 ) 16. 8 ( 9.3 ) 16.5 ( 9.2 ) 15.4 ( 8.6 ) 14.3 ( 7.9 ) 203 66 61 56 51 46 1399 19 16 13 10 8 042 12.8 ( 7.1 ) 12. 7 ( 7.1 ) 12.7 ( 7.1 ) 12.6 ( 7 ) 12.6 ( 7 ) 210 68 63 58 53 48 1448 20 17 14 11 9 048 17.5 ( 9.7 ) 16. 9 ( 9.4 ) 16.6 ( 9.2 ) 15.7 ( 8.7 ) 14.8 ( 8.2 ) 217 70 65 60 55 50 1496 21 18 15 13 10 060 13.7 ( 7.6 ) 13 ( 7.2 ) 13 ( 7.2 ) 14.5 ( 8.1 ) 11.5 ( 6.4 ) 224 72 67 62 57 52 1544 22 19 16 14 11
75 (24) 82 (28) 85 (29) 95 (35) 105 (41)
Charging Procedure
1- Measure Discharge line pressure by attaching a gauge to the service port.
2- Measure the Liquid line temperature by attachi ng a temperature sensing device to it.
3- Insulate the temperature sensing device so that the Outdoor Ambient doesn’t affect the reading.
4- Refer to the required Subcooling in the table based on the model size and the Outdoor Ambient temperature.
5- Interpolate if the Outdoor ambi ent temperature lies in betw een the table values. Extrapolate if the temperatur e lies beyond the table range.
6- Find the Pressure Value in the table corresponding to t he the measured Pressure of the Compressor Discharge line.
7- Read across from the Pressure reading to obtain the Liqui d line temperature for a required Subcooling
8- Add Charge if the measured temperature is higher than t he table value.
Pressure
(psig)
231 74 69 64 59 54 1593 23 20 18 15 12 238 76 71 66 61 56 1641 24 21 19 16 13
245 77 72 67 62 57 1689 25 22 20 17 14 252 79 74 69 64 59 1737 26 23 21 18 15 260 81 76 71 66 61 1792 27 25 22 19 16 268 83 78 73 68 63 1848 29 26 23 20 17
276 85 80 75 70 65 1903 30 27 24 21 19 284 87 82 77 72 67 1958 31 28 25 22 20 292 89 84 79 74 69 2013 32 29 26 23 21 300 91 86 81 76 71 2068 33 30 27 24 22
309 93 88 83 78 73 2130 34 31 28 26 23 318 95 90 85 80 75 2192 35 32 29 27 24 327 97 92 87 82 77 2254 36 33 31 28 25 336 99 94 89 84 79 2316 37 34 32 29 26
345 101 96 91 86 81 2378 38 35 33 30 27 354 103 98 93 88 83 2440 39 36 34 31 28 364 105 100 95 90 85 2509 40 38 35 32 29 374 107 102 97 92 87 2578 41 39 36 33 30
384 108 103 98 93 88 2647 42 40 37 34 31 394 110 105 100 95 90 2716 44 41 38 35 32 404 112 107 102 97 92 2785 45 42 39 36 33 414 114 109 104 99 94 2854 46 43 40 37 34
424 116 111 106 101 96 2923 47 44 41 38 35 434 118 113 108 103 98 2992 48 45 42 39 36 444 119 114 109 104 99 3061 48 46 43 40 37 454 121 116 111 106 101 3130 49 47 44 41 38
464 123 118 113 108 103 3199 50 48 45 42 39 474 124 119 114 109 104 3268 51 48 46 43 40 484 126 121 116 111 106 3337 52 49 47 44 41 494 127 122 117 112 107 3406 53 50 47 45 42
504 129 124 119 114 109 3475 54 51 48 46 43 514 131 126 121 116 111 3544 55 52 49 46 44 524 132 127 122 117 112 3612 56 53 50 47 45 534 134 129 124 119 114 3681 56 54 51 48 45
Required Liquid Line Temperature for a Specif ic Subcooling (R-410A)
Pressure
5 10152025
(kPa)
Required Subcooling (
3 6 8 11 14
Fig. 22 -- Cooling Charging Table--Subcooling
o
C)Required Subcooling (oF)
50CR
C03027
Table 3 — ECM Wet Coil Pressure Drop (in. wg)
UNIT SIZE
600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100
024 0.005 0.007 0.010 0.012 0.015
030 0.007 0.010 0.012 0. 015 0.018 0.021 0.024
036 0. 019 0.023 0.027 0.032 0.037 0.042 0.047
042 0.014 0.017 0.020 0.024 0.027 0.031 0.035 0.039 0.043
048 0.027 0.032 0.036 0.041 0.046 0. 052 0.057 0.063 0.068
060 0.029 0.032 0.036 0.040 0.045 0.049
STANDARD CFM (SCFM)
Table 4 — Filter Pressure Drop Table (in. wg)
FILTER SIZE
500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 2300 20X20X1 0.05 0.07 0.08 0.1 0.12 0.13 0.14 0.15 24X30X1 0.05 0.6 0.07 0.07 0.08 0.09 0.1 24X36X1 0.06 0.07 0.07 0.08 0.09 0.09 0.10 0.11 0.12 0.13 0.14 0.14
CFM
Table 5 — Electric Heat Pressure Drop Table
Small Cabinet: 024--036
CFM
500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600
5kw 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.02 0.04 0.06 0.07
7.2 kw 0.00 0.00 0.00 0.00 0.00 0.00 0.02 0.03 0.05 0.07 0.08 0.09 10 kw 0.00 0.00 0.00 0.00 0.00 0.02 0.04 0.06 0.07 0.09 0.10 0.11 15 kw 0.00 0.00 0.00 0.02 0.04 0.06 0.08 0.10 0.12 0.14 0.16 0.18 20 kw 0.00 0.00 0.02 0.04 0.06 0.08 0.09 0.11 0.13 0.15 0.17 0.19
0.053
23
Page 24
Table 6 — Electric Heat Pressure Drop Table
Large Cabinet: 042--060
CFM
1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 2300 2400 2500
5kw 0.00 0.00 0.00 0.01 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.10 0.11 0.12
7.2 kw 0.00 0.00 0.01 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.10 0.11 0.12 0.13 10 kw 0.00 0.00 0.01 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.10 0.11 0.12 0.13 15 kw 0.00 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.10 0.11 0.12 0.13 0.14 0.15 20 kw 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.10 0.11 0.12 0.13 0.14 0.15 0.16
T2 C C O
OF1
OF2
P1
J1
DFT
DFT
T1 Y
30
60
INTERVAL TIMER
120
90
60
OFF
30
QUIET
SHIFT
ON
P3
O R W
2
50CR
Y C
SPEEDUP
CESO130076–00
Speedup Pins
Quiet Shift
Fig. 23 -- Defrost Control
MAINTENANCE
To ensure continuing high performance, and to minimize the possibility of premature equipment failure, periodic maintenance must be performed on this equipment. This heat pump unit should be inspected at least once each year by a qualified service person. To troubleshoot unit, refer to Table 8, Troubleshooting Chart.
NOTE TO EQUIPMENT OWNER: Consult your local dealer about the availability of a maintenance contract.
!
WARNING
PERSONAL INJURY AND UNIT DAMAGE HAZARD
Failure to follow this warning could result in personal injury or death and possible unit component damage.
The ability to properly perform maintenance on this equipment requires certain expertise, mechanical skills, tools and equipment. If you do not possess these, do not attempt to perform any maintenanceon this equipment, other than those procedures recommended in the Owner’s Manual.
Defrost interval DIP switches
ELECTRICAL SHOCK HAZARD
Failure to follow thesewarnings could result in serious injury or death:
1. Turn off electrical power to the unitbefore performingany
2. Use extreme caution when removing panels and parts.
3. Never place anything combustible either on or in contact
UNIT OPERATION HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
Errors made when reconnecting wires may cause improper and dangerous operation. Label all wires prior to disconnecting when servicing.
!
WARNING
maintenance or service on this unit.
with the unit.
!
CAUTION
24
Page 25
The minimum maintenance requirements for this equipment are as follows:
1. Inspect air filter(s) each month. Clean or replace when necessary.
2. Inspect indoor coil, drain pan, and condensate drain each cooling season for cleanliness. Clean when necessary.
3. Inspect blower motor and wheel for cleanliness each cooling season. Clean when necessary.
4. Check electrical connections for tightness and controls for proper operation each cooling season. Service when necessary.
Step 1—Air Filter
IMPORTANT: Never operate the unit without a suitable air filter
in the return--air duct system. Always replace the filter with the same dimensional size and type as originally installed. See Table 1 for recommended filter sizes.
Inspect air filter(s) at least once each month and replace (throwaway--type) or clean (cleanable--type) at least twice during each cooling season and twice during the heating season, or whenever the filter becomes clogged with dust and lint.
Step 2—Indoor Blower and Motor
NOTE: All motors are pre--lubricated. Do not attempt to lubricate
these motors.
For longer life,operating economy,and continuing efficiency,clean accumulated dirt and grease from the blower wheel and motor annually.
Step 4—Outdoor Fan
!
CAUTION
UNIT OPERATION HAZARD
Failure to follow this caution may result in damage to unit components.
Keep the condenser fan free from all obstructions to ensure proper cooling operation. Never place articles on top of the unit.
1. Remove 6 screws holding outdoor grille and motor to top cover.
2. Turn motor/grille assembly upside down on top cover to expose fan blade.
3. Inspect the fan blades for cracks or bends.
4. If fan needs to be removed, loosen setscrew and slide fan off motor shaft.
5. When replacing fan blade, position blade so that the hub is 1/8 in. away from the motor end (1/8 in. of motor shaft will be visible) (See Fig. 24).
6. Ensure that setscrew engages the flatareaon the motorshaft when tightening.
7. Replace grille.
50CR
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Disconnect and tag electrical power to the unit before cleaning and lubricating the blower motor and wheel.
Step 3—Outdoor Coil, Indoor Coil, and Condensate Drain Pan
Inspect the condenser coil, evaporator coil, and condensate drain pan at least once each year.
The coils are easily cleaned when dry; therefore, inspect and clean the coils either before or after each cooling season. Remove all obstructions, including weeds and shrubs, that interfere with the airflow through the condenser coil. Straighten bent fins with a fin comb. If coated with dirt or lint, clean the coils with a vacuum cleaner, using the soft brush attachment. Be careful not to bend the fins. If coated with oil or grease, clean the coils with a mild detergent and water solution. Rinse coils with clear water, using a garden hose. Be careful not to splash water on motors, insulation, wiring, or air filter(s). For best results, spray condenser coil fins from inside to outsidethe unit.On units with an outer and inner condenser coil, be sure to clean between the coils. Be sure to flush all dirt and debris from the unit base.
Inspect the drain pan and condensatedrain linewhen inspecting the coils. Clean the drain pan and condensate drain by removing all foreign matter from the pan. Flush the pan and drain trough with clear water. Do not splash water on the insulation, motor, wiring, or air filter(s). If the drain trough is restricted, clear it with a “plumbers snake” or similar probe device.
WARNING
Infinity Top
A06035
UNIT SIZE
024 25 030 25 036 24 042 24 048 24 060 19
Fig. 24 -- Fan Blade Clearance
Step 5—Electrical Controls and Wiring
Inspect and check the electrical controls and wiring annually. Be sure to turn off the electrical power to the unit.
Remove access panel to locate all the electrical controls and wiring. Check all electrical connections for tightness. Tighten all screw connections. If any smoky or burned connections are noticed, disassemble the connection,clean all the parts, re--strip the wireend and reassemble the connection properly and securely.
After inspecting the electrical controls and wiring, replace all the panels. Start the unit, and observe at least one complete cooling cycle to ensure proper operation. If discrepancies are observed in operating cycle, or if a suspected malfunction has occurred, check each electrical component with the proper electrical instrumentation. Refer to the unit wiring label when making these checks.
“A” DIMENSION
Infinity
25
Page 26
Balance Point Worksheet
70
Based on Entering Indoor Air of 70 Deg. F and Rated CFM
60
50
060
048
40
042
1000BTUH
30
50CR50CR
036
030
024
20
Building Heat Loss, 1000BTUH
Unit Integrated Heating Capacity,
10
0
-20 -10 0 10 20 30 40 50 60
Outdoor Air Temp (Deg F)
Fig. 25 -- 50CR Balance Point Worksheet
Step 6—Refrigerant Circuit
Inspect all refrigerant tubing connections and the unit base for oil accumulation annually. Detecting oil generally indicates a refrigerant leak.
If oil is detected or if low performance is suspected, leak test all refrigerant tubing using an electronic leak detector, or liquid-- soap solution. If a refrigerant leak is detected, refer to Check for Refrigerant Leaks section.
If no refrigerant leaks are found and low performance is suspected, refer to Checking and Adjusting Refrigerant Charge section.
Step 7—Indoor Airflow
Theheatingand/orcoolingairflow does notrequire checkingunless improper performance is suspected. If a problem exists, be sure that all supply-- and return--air grilles are open and free from obstructions, and that the air filter is clean.
Step 8—Metering Devices--TXV & Accurater Piston
This unit uses 2 types of metering devices. The outdoor metering deviceis a fixed orificeand iscontainedin the brass--hex body in the liquid linefeeding the outdoor coils.The indoor metering deviceis a TXV--type device.
Step 9—Pressure Switches
Pressure switches are protective devices wired into control circuit (low voltage). They shut off compressor if abnormally high or low pressures are present in the refrigeration circuit. These pressure switches are specifically designed to operate with Puron (R--410A) systems. R--22 pressure switches must not be used as replacements for the Puron (R--410A) system.
C03008
C99097
Fig. 26 -- Refrigerant Circuit
Step 10—Loss--of--Charge Switch
This switch is located on the liquid line and protects against low suction pressures caused by such events as loss of charge, low
26
Page 27
airflow across indoor coil, dirty filters, etc. It opens on a pressure drop at about20 psig. If system pressureis above this, switchshould be closed. To check switch:
1. Turn off all power to unit.
2. Disconnect leads on switch.
3. Apply ohm meter leads across switch. You should have continuity on a good switch.
NOTE: Because these switches are attached to refrigeration system under pressure, it is not advisable to remove this device for troubleshooting unless you are reasonably certain that a problem exists. If switch must be removed, remove and recover all system charge so that pressure gauges read 0 psi. Never open system without breaking vacuum with dry nitrogen.
Step 11 —High -- Pressure Sw itch
The high--pressure switch is located in the discharge line and protects against excessive condenser coil pressure. It opens at 650 psig.
High pressure may be caused by a dirty outdoor coil, failed fan motor, or outdoor air recirculation.
To check switch:
1. Turn off all power to unit.
2. Disconnect leads on switch.
3. Apply ohm meter leads across switch. You should have continuity on a good switch.
Step 12—Copeland Scroll Compressor (Puron Refrigerant)
The compressor used in this product is specifically designed to operate with Puron (R--410A) refrigerant and cannot be interchanged.
The compressor is an electrical (as well as mechanical) device. Exercise extreme caution when working near compressors. Power should be shut off, if possible,for most troubleshooting techniques. Refrigerants present additional safety hazards.
!
EXPLOSION,FIRE, ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death and/or property damage.
Wear safety glasses and gloves when handling refrigerants. Keep torches and other ignition sources away from refrigerants and oils.
The scroll compressor pumps refrigerant throughout the system by the interaction of a stationary and an orbiting scroll. The scroll compressor has no dynamic suction or discharge valves, and it is more tolerant of stresses caused by debris, liquid slugging, and flooded starts. The compressor is equipped with an anti--rotational device and an internal pressure--relief port. The anti--rotational device prevents the scroll from turning backwards and replaces the needfor acycleprotector. The pressure--reliefport isa safety device, designed to protect against extreme high pressure. The relief port has an operating range between 550 and 625 psi differential pressure.
The Copeland scroll compressor uses Mobil 3MA POE oil. This is the only oil allowed for oil recharge.
Step 13—Refrigerant System
This step covers the refrigerant system of the 50CR, including the compressor oil needed, servicing systems on roofs containing synthetic materials, the filter drier, and refrigerant charging.
WARNING
REFRIGERANT
!
CAUTION
PERSONAL INJURY, UNIT OPERATION HAZARD
Failure to follow this caution may result in personal injury, equipment damage or improper operation.
This system uses Puron (R--410A) refrigerant which has higher operating pressures than R--22 and other refrigerants. No other refrigerant may be used in this system. Gauge set, hoses,and recovery systemmustbe designed to handle Puron. If you are unsure, consult the equipment manufacturer.
COMPRESSOR OIL
The compressor in this system uses a polyolester (POE) oil, Mobil 3MA POE. This oil is extremely hygroscopic, meaning it absorbs water readily. POE oils can absorb 15 times as much water as other oils designed for HCFC and CFC refrigerants. Take all necessary precautions to avoid exposure of the oil to the atmosphere.
SERVICING SYSTEMS ON ROOFS WITH SYNTHETIC MATERIALS
POE (polyolester) compressor lubricants are known to cause long term damage to some synthetic roofing materials.
Exposure, even if immediately cleaned up, may cause embrittlement (leading to cracking) to occur in one year or more. When performingany servicethatmay risk exposure of compressor oil to the roof, take appropriate precautions to protect roofing. Procedures which risk oil leakage include, but are not limited to, compressor replacement, repairing refrigerant leaks, and replacing refrigerant components such as filter drier, pressure switch, metering device, coil, accumulator, or reversing valve.
Synthetic Roof Precautionary
1. Cover extended roof working area with an impermeable polyethylene (plastic) drip cloth or tarp. Cover an approximate 10 X 10 ft area.
2. Cover areain frontof the unit service panel witha terry cloth shop towel to absorb lubricant spills and prevent run--offs, and protect drop cloth from tears caused by tools or components.
3. Place terry cloth shop towel inside unit immediately under component(s) to be serviced and prevent lubricant run--offs through the louvered openings in the unit base.
4. Perform required service.
5. Remove and dispose of any oil--contaminated material per local codes.
LIQUID-- LINE FILTER DRIER
The biflow filter drier is specifically designed to operate with Puron. Use only factory--authorized components. Filter drier must be replaced whenever the refrigerant system is opened. When removing a filter drier, use a tubing cutter to cut the drier from the system. Do not unsweat a filter drier from the system. Heat from unsweating will release moisture and contaminants from drier into system.
PURON (R--410A) REFRIGERANT CHARGING
Refer to unit information plate and charging chart. Some R--410A
refrigerant cylinders contain a dip tube to allow liquid refrigerant to flow from cylinder in upright position. For
cylinders equipped with a dip tube, charge Puron cylinder in upright position and a commercial metering device in manifold hose. Charge refrigerant into suction line.
Procedure
®
units with
50CR
27
Page 28
Step 14—System Information
LOSS--OF--CHARGE SWITCH
The loss of charge switch is a protective device wired into control circuit (low voltage). It shuts off the compressor if abnormally low pressures are present in the refrigeration circuit.
NOTE: Because these switches are attached to refrigeration system under pressure, it is not advisable to remove this device for troubleshooting unless you are reasonably certain that a problem exists. If switch must be removed, remove and recover all system charge so that pressure gauges read 0 psi. Never open system without breaking vacuum with dry nitrogen.
CHECK DEFROST THERMOSTAT
There is a liquid header with a brass distributor and feeder tube going into outdoor coil. At the end of one of the feeder tubes, there is a 3/8--in.OD stub tube approximately3 in. long (SeeFig. 27). The defrost thermostat should be located on stub tube.
NOTE: Thereis only one stub tube used with liquid header, and on most units it is the bottom circuit.
The defrost thermostat signals heat pump that conditions are right for defrost or that conditions have changed to terminate defrost. It is a thermally--actuated switch clamped to outdoor coil to sense its temperature. Normal temperature range is closed at 30°±3°Fand open at 80°±5°F.
TROUBLESHOOTING
Refer to the Cooling and Heating Troubleshooting Chart (Table 7) for troubleshooting information.
START--UP CHECKLIST
Use the Start--Up Checklist at the back of this manual.
Defrost Sensor
See Detail A
Unit Top
Detail A
Fig. 27 -- Defrost Sensor Location
A06068
28
Page 29
HEAT PUMP WITH PURON
REFRIGERATION SECTION QUICK--REFERENCE GUIDE
Puron refrigerant operates at 50--70 percent higher pressures than R--22. Be sure that servicing equipment and replacement components are designed to operate with Puron. Puron refrigerant cylinders are rose colored.
S
Puron refrigerant cylinders manufactured prior to March 1, 1999, have a dip tube that allows liquid to flow out of cylinder in upright position. Cylinders manufactured March 1, 1999 and later DO NOT have a dip tube and MUST be positioned upside down to allow liquid to flow.
S
Recovery cylinder service pressure rating must be 400 psig. DOT 4BA400 or DOT BW400.
S
Puron systems should be charged with liquid refrigerant. Use a commercial--type metering device in the manifold hose.
S
Manifold sets should be 750 psig high side and 200 psig low side with 520 psig low side retard.
S
Use hoses with 750 psig service pressure rating.
S
Leak detectors should be designed to detect HFC refrigerant.
S
Puron, as with other HFCs, is only compatible with POE oils.
S
Vacuum pumps will not remove moisture from oil.
S
Only use factory--specified liquid--line filter driers with rated working pressures no less than 600 psig.
S
Do not install a suction--line filter drier in liquid line.
S
POE oils absorb moisture rapidly. Do not expose oil to atmosphere.
S
POE oils may cause damage to certain plastics and roofing materials.
S
Wrap all filter driers and service valves with wet cloth when brazing.
S
A Puron liquid--line filter drier is required on every unit.
S
Do not use an R--22 TXV.
S
Never open system to atmosphere while it is under a vacuum.
S
When system must be opened for service, break vacuum with dry nitrogen and replace filter driers.
S
Do not vent Puron into the atmosphere.
S
Observe all warnings, cautions, and bold text.
S
Do not leave Puron suction line driers in place for more than 72 hrs.
50CR
29
Page 30
Table 7 — Troubleshooting Chart
SYMPTOM CAUSE REMEDY
Compressor and outdoor fan will not start
50CR
Compressor will not start but condenser fan runs
Three-- phase scroll compressor (size 030-­060 unit) has a low pressure differential 3--phase power leads to the unit
Compressor cycles (other than normally satis­fying) cooling/heating calls
Compressor operates continuously
Excessive head pressure
Power failure Call power company Fuse blown or circuit breaker tripped Replace fuse or reset circuit breaker
Defective contactor, transformer, control relay, defrost board, or high-- pressure, loss -­of--charge or low- -pressure switch
Insufficient line voltage Determine cause and correct
Incorrect or faulty wiring Check wiring diagram and rewire correctly
User Interface setting too low/too high ResetUIsetting
Units have a 5 --minute time delay
Faulty wiring or circuit Loose connections in compressor
Compressor motor burned out, seized, or Determine cause internal overload open Replace compressor Defective run capacitor, overload, or PTC (positive
temperature coefficient) thermistor
One leg of 3--phase power dead
Low input voltage (20 percent low) Determine cause and correct
Scroll compressor is rotating in the wrong direction
Refrigerant overcharge or undercharge
Defective compressor Replace and determine cause Insufficient line voltage Determine cause and correct Blocked outdoor coil Determine cause and correct Defective run/start capacitor, overload or start relay Determine cause and replace Faulty outdoor fan motor or capacitor Replace Damaged reversing valve Determine cause and correct Restriction in refrigerant system Locate restriction and remove Dirty air filter Replace filter Unit undersized for load Decrease load or increase unit size UI temperature set too low/too high ResetUIsetting Low refrigerant charge Locate leak, repair, and recharge
Frosted coil with incorrect defrost operation
Air in system
Outdoor coil dirty or restricted Clean coil or remove restriction Dirty air filter Replace filter Dirty indoor or outdoor coil Clean coil Refrigerant overcharged Recover excess refrigerant
Air in system
(Heat) Indoor air restricted or recirculating Determine cause and correct Indoor or outdoor air restricted or air short-- cycling Determine cause and correct
Replace component
DO NOT bypass this compressor time delay–wait for 5 minutes until time--delay relay is de-- energized
Check wiring and repair or replace
Determine cause and replace
Replace fuse or reset circuit breaker Determine cause
Correct the direction of rotation by reversing the
Recover refrigerant, evacuate system, and re­charge to capacities shown on rating plate
Check defrost time settings
Reset as necessary
Check defrost temperature switch
Replace as necessary
Recover refrigerant, evacuate system, and re­charge
Recover refrigerant, evacuate system, and re­charge
(Continued next page)
30
Page 31
Table 7—Troubleshooting Chart (Cont’d)
SYMPTOM CAUSE REMEDY
Head pressure too low
Excessive suction pressure
Suction pressure too low
Compressor runs but outdoor fan does not
IFM does not run
IFM operation is intermittent
Low refrigerant charge Check for leaks, repair and recharge Restriction in liquid tube Remove restriction (Cool) High Heat load Check for source and eliminate Reversing valve hung up or leaking internally Replace valve Refrigerant overcharged Recover excess refrigerant (Cool) Dirty air filter Replace filter
(Heat) Outdoor coil frosted
Low refrigerant charge Check for leaks, repair and recharge Metering device or low side restricted Remove source of restriction
(Cool) Insufficient coil airflow
(Cool) Temperature too low in conditioned area ResetUIsetting (Cool) Outdoor ambient below 55°F Install low --ambient kit Filter drier res tricted Replace NC (normally closed) contacts on defrost board
open
Blower wheel not secured to shaft Properly tighten blower wheel to shaft Insufficient voltage at motor Determine cause and correct Power connectors not properly sealed Connectors should snap easily; do not force Water dripping into motor Verify proper drip loops in connector wires
Connectors not firmly sealed
Move timer on control board to 30 minutes between defrost cycles
Increase air quantity Check filter–replace if necessary
Check condition of relay on board Replace if necessary
Gently pull wires individually to be sure they are crimped into the housing
IFM--Indoor Fan Motor
50CR
31
Page 32
START-UP CHECKLIST
g
(Remove and Store in Job File)
I. Preliminary Information
MODEL NO.:_________________________________ SERIAL NO.:__________________________________ DATE:_______________________________________ TECHNICIAN:_________________________________
II. PRE-START-UP (Insert checkmark in box as each item is completed)
( ) VERIFY THAT ALL PACKING MATERIALS HAVE BEEN REMOVED FROM UNIT ( ) REMOVE ALL SHIPPING HOLD DOWN BOLTS AND BRACKETS PER INSTALLATION INSTRUCTIONS ( ) CHECK ALL ELECTRICAL CONNECTIONS AND TERMINALS FOR TIGHTNESS ( ) CHECK GAS PIPING FOR LEAKS (WHERE APPLICABLE) ( ) CHECK THAT INDOOR (EVAPORATOR) AIR FILTER IS CLEAN AND IN PLACE ( ) VERIFY THAT UNIT INSTALLATION IS LEVEL ( ) CHECK FAN WHEEL, AND PROPELLER FOR LOCATION IN HOUSING/ORIFICE AND SETSCREW TIGHTNESS ( ) MAKE SURE THAT -
(If Applicable) ON 060 SIZE PURON HEATPUMP ONLY, THE TWO WIRE TIES FASTEN
TO THE OUTDOOR COILS AND REVERSING VALVE/ACCUMULATOR HAVE BEEN REMOVED
50CR
III. START-UP ELECTRICAL
SUPPLY VOLTAGE __________________________________ COMPRESSOR AMPS_________________________________ INDOOR (EVAPORATOR) FAN AMPS___________
TEMPERATURES
OUTDOOR (CONDENSER) AIR TEMPERATURE ___________DB RETURN-AIR TEMPERATURE ___________DB ___________WB COOLING SUPPLY AIR ___________DB ___________WB HEAT PUMP SUPPLY AIR ___________ ELECTRIC HEAT SUPPLY AIR ___________
PRESSURES
REFRIGERANT SUCTION ___________PSIG SUCTION LINE TEMP*___________ REFRIGERANT DISCHARGE ___________PSIG DISCHARGE TEMP†___________ ( ) VERIFY REFRIGERANT CHARGE USING CHARGING CHARTS
*Measured at suction inlet to compressor †Measured at liquid line leavin
condenser.
A05306
Copyright 2006 Carrier Corp. S 7310 W. Morris St. S Indianapolis, IN 46231
Manufacturer reser ves the right to change, at any time, specifications and designs without notice and without obligations.
Printed in U.S.A. Editi on Date: 03/06
32
Catalog No: 50CR ---1SI
Replaces: New
Loading...