Carrier 50BV020-064 User Manual

Water-Cooled and Remote Air-Cooled
Indoor Self-Contained Systems and
Water-Cooled Heat Pumps
Installation, Start-Up and
Service Instructions
OMNIZONE™
50BV020-064
CONTENTS
Page
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . .1,2
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Constant Volume (CV) Units. . . . . . . . . . . . . . . . . . . . . . 2
Variable Air Volume (VAV) Units . . . . . . . . . . . . . . . . . . 2
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-30
Step 1 — Complete Pre-Installation Checks . . . . . . 3
• EXAMINE THE UNIT
• UNIT STORAGE
• MODULAR UNITS
Step 2 — Rig and Place Unit . . . . . . . . . . . . . . . . . . . . . 3
• REMOVE PACKAGING
• UNIT LOCATION
• UNIT PLACEMENT
• ACOUSTICAL CONSIDERATIONS
• ASSEMBLING MODULAR UNITS
Step 3 — Install Ductwork. . . . . . . . . . . . . . . . . . . . . . . 19
• DUCT STATIC PRESSURE PROBE AND TUBING ( VAV O nl y)
• DUCT HIGH-STATIC (DHS) LIMIT SWITCH (VAV Only)
Step 4 — Make Piping Connections . . . . . . . . . . . . . 21
• CONDENSER WATER PIPING (Water-Cooled Only)
• EVAPORATOR CONDENSATE DRAIN
• HOT WATER HEATING COIL (Optional)
• WATER ECONOMIZER (Optional)
• REMOTE REFRIGERANT PIPING (Remote Air-Cooled Only)
Step 5 — Complete Electrical Connections. . . . . . 24
• POWER WIRING
• CONTROL WIRING (CV Only)
• REMOTE CONDENSER FAN CONTACTOR WIRING
• CONTROL WIRING (VAV Only)
• SUPPLY AIR TEMPERATURE SENSOR (SAT)
• SMOKE DETECTOR/FIRE ALARM SHUTDOWN (FSD)
• ALARM (ALARM) AND WARNING (WARN) OUTPUTS
• REMOTE OCCUPANCY (ROCC)
• RETURN AIR TEMPERATURE SENSOR (RAS)
START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30-48
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
• CRANKCASE HEATERS
• CONFIRM THE INPUT POWER PHASE SEQUENCE
• INTERNAL WIRING
• RETURN-AIR FILTERS
• COMPRESSOR MOUNTING
• REFRIGERANT SERVICE PORTS
CV Unit Start-Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
• EVAPORATOR FAN
•COOLING
• HEATING (Heat Pump Units Only)
VAV Unit Start-Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
• PERFORM AUTOMATIC RUN TEST
•CHECK VFD
• POWER UP LID DISPLAY
• LOG ON TO THE LID DISPLAY
Page
• CHANGE THE DEFAULT PASSWORD
• SET THE CLOCK
• CONFIGURE SCHEDULES
• PROGRAM SET POINTS
• CHECK SYSTEM PARAMETERS
• DISPLAY ALARM HISTORY
• CONFIGURE THE CUSTOM PROGRAMMING SELECTIONS
• SET CONTROLLER ADDRESS
• LOG OFF FROM THE CONTROLLER
Sequence of Operation (CV Only) . . . . . . . . . . . . . . . 47
• WATER ECONOMIZER COOLING
Sequence of Operation (VAV Only) . . . . . . . . . . . . . . 48
• SUPPLY FAN
• COMPRESSOR COOLING
• WATER ECONOMIZER COOLING
• COOLING RESET
Diagnostic Features (CV Only) . . . . . . . . . . . . . . . . . . 48
VAV Control and VFD Diagnostics. . . . . . . . . . . . . . . 48
SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Compressor Rotation . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Fan Motor Replacement. . . . . . . . . . . . . . . . . . . . . . . . . 49
MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49-51
Cleaning Unit Exterior. . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Coil Cleaning. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Inspection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Air Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Condensate Drains. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Water-Cooled Condensers . . . . . . . . . . . . . . . . . . . . . . 49
• GRAVITY FLOW METHOD
• FORCED CIRCULATION METHOD
Fan Motor Lubrication. . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Fan Bearing Lubrication . . . . . . . . . . . . . . . . . . . . . . . . 50
Fan Sheaves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
•ALIGNMENT
Evaporator Fan Performance Adjustment . . . . . . . 51
• BELT TENSION ADJUSTMENT
Charging the System. . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
• REMOTE AIR-COOLED UNITS
Compressor Oil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . 51-65
Forcing and Clearing an Input or Output
(VAV only) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
START-UP CHECKLIST . . . . . . . . . . . . . . . . . . .CL-1, CL-2
SAFETY CONSIDERATIONS
Installing, starting up, and servicing air-conditioning
components and equipment can be dangerous. Only trained, qualified installers and service mechanics should install, start­up, and service this equipment.
When working on the equipment, observe precautions in
the literature and on tags, stickers, and labels attached to the
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53500001-01 Printed in U.S.A. Form 50BV-3SI Pg 1 10-08 Replaces: 50BV-2SI
equipment. Follow all safety codes. Wear safety glasses and work gloves.
WARNING
The 50BV units have removable access panels for easy servicing. These panels allow access to controls, compressors, condensers, VFD(s) (if applicable), evaporator motors, blow­ers, belts, pulleys, and refrigeration components.
Before performing service or maintenance operations on unit, turn off main power switch to unit and open all dis­connects. More than one disconnect switch may be required to deenergize this equipment. Electric shock haz­ard can cause injury or death.
CAUTION
Use care in handling, rigging, and setting bulky equipment.
GENERAL
Omnizone™ 50BV indoor packaged units are very flexible for a variety of applications. These self-contained units are available as water-cooled or remote air-cooled air conditioning units. The 50BV units are available with either constant vol­ume (CV) or variable air volume (VAV) controls. In addition, the 50BV unit is available as a water-cooled heat pump. Final­ly, Omnizone 50BV units are available in two cabinet styles. Nominal 18 through 30-ton units are constructed in a single­piece, unpainted galvanized cabinet. Nominal 30 through 60-ton units are available as modular units, and can be taken apart for easier installation. Modular units are built using an un­painted, galvanized steel cabinet with steel framework, and can be easily disassembled without breaking the refrigerant lines. See Table 1 for a model number reference by application.
Each unit contains multiple scroll compressors piped in separate refrigerant circuits. Each water-cooled circuit includes a coaxial (tube-in-tube) condenser, TXV (thermostatic expan­sion valve), individual evaporator coils, and all interconnecting piping. Water-cooled units are shipped fully charged with refrigerant. Remote air-cooled units are shipped with a nitrogen holding charge.
Each unit is equipped with one or two forward-curved cen­trifugal blowers, to ensure quiet air delivery to the conditioned space. Constant volume units operate at a single, adjustable fan speed and provide zone temperature control using a standard commercial thermostat. For VAV applications, the unit is sup­plied with a variable frequency drive(s) (VFD) that automati­cally adjusts blower speed to maintain a constant, adjustable duct static pressure. Compressors are automatically staged to provide supply air temperature control (VAV applications) or zone temperature control using a two-stage commercial ther­mostat (CV applications).
MAJOR SYSTEM COMPONENTS
Constant Volume (CV) Units
MAIN CONTROL BOARD (MCB) — The main control board for the 50BVC, E, Q, T, U, and V units provides both controls and diagnostics including:
• Condensate Overflow Protection
prevents unit operation in the event that the drain pan clogs (optional sensors required).
• Random Start
provides a programmable start with a range
of 30 to 60 seconds.
• Anti-short Cycle Timer
provides a 5-minute delay to pre-
vent compressor short cycling.
• Low Pressure Bypass Timer
bypasses the low-pressure switch for 90 seconds to avoid nuisance trips during cold start-up.
• High Pressure Switch Delay
is a one-second delay that pre-
vents nuisance trips at start-up.
• Brownout/Surge/Power Interruption Protection
is a 20-second moving scale that works in conjunction with the random start timer to delay unit start when a nuisance lock­out would otherwise have occurred. This allows the water pumps to restart and establish water flow.
• Alarm Output
contacts provide remote fault indication.
• Test/Service Pin is a jumper that reduces all time delay settings to 6 seconds during troubleshooting or operation verification.
• Reset
occurs after a 5-minute delay when a fault condition occurs. When the timer expires, the unit will restart. If the same condition occurs a second time, the unit will be locked out.
• Lockout Reset
requires that the unit power be cycled at the
unit controller via either the thermostat or unit disconnect.
NOTE: The refrigerant circuits on dual compressor models are completely independent. If either stage has a fault condi­tion the remaining stage will continue to operate without interruption. A freeze (optional sensor required) or condensate overflow lockout will shut down both refrigerant circuits.
• LEDs
are provided for diagnostic purposes.
Variable Air Volume (VAV) Units — The 50BVJ, K,
W, and X units come equipped with a Carrier 6400 Comfort Controller and a VFD. Refer to the 50BV,XJ Controls, Opera­tion and Troubleshooting manual for details.
NOTE: The VAV units utilize face split coils and should not be operated below 50% of nominal airflow to prevent coil freezing.
Table 1 — Model Number Reference By Application Type
MODEL TYPE* AVAILABLE CAPACITY CONSTRUCTION CONTROLS
50BVC Water-Cooled 18 to 30 nominal tons Single-piece CV 50BVE Remote Air-Cooled 18 to 30 nominal tons Single-piece CV 50BVQ Water-Cooled Heat Pump 18 to 30 nominal tons Single-piece CV 50BVJ Water-Cooled 18 to 30 nominal tons Single-piece VAV 50BVK Remote Air-Cooled 18 to 30 nominal tons Single-piece VAV 50BVT Water-Cooled 30 to 60 nominal tons Modular CV 50BVU Remote Air-Cooled 30 to 60 nominal tons Modular CV 50BVV Water-Cooled Heat Pump 30 to 60 nominal tons Modular CV 50BVW Water-Cooled 30 to 60 nominal tons Modular VAV 50BVX Remote Air-Cooled 30 to 60 nominal tons Modular VAV
LEGEND
CV Constant Volume VAV — Variable Air Volume
*All units are cooling only unless specified.
2
INSTALLATION
Omnizone™ 50BV units are intended for indoor installa­tion only. Determine building alterations required to run piping, wiring, and ductwork. Read all installation instructions before installing the unit.
Step 1 — Complete Pre-Installation Checks
EXAMINE THE UNIT — Examine the unit for shipping damage. File a claim with the transit company if damage is found. Check the shipment for completeness. Verify that the nameplate electrical requirements match the available power supply.
UNIT STORAGE — The 50BV units are designed and pack­aged for indoor storage and use only. If the equipment is not needed for immediate installation upon its arrival at the job site, it should be left in its shipping carton and stored in a clean, dry area. Units must only be stored or moved in the normal upright position, as indicated by the “UP” arrows on each carton, at all times. DO NOT STACK UNITS.
MODULAR UNITS — The 50BVT,U,V,W,X units are shipped in multiple sections for easy movement and installation. The separate modules will pass through a standard 36-in. steel­framed door or service elevator. Circuit integrity is maintained because none of the refrigerant piping requires disconnection. Water piping connections are made with the use of heavy-duty bronze-bodied unions so no field welding or brazing is required. See Table 2 for the number of sections per unit.
Table 2 — Modular Unit Shipping Table
NUMBER OF SECTIONS
SECTIONS
Main Air Conditioning Weight (lb) (each)
Reheat Coil Option Weight (lb) (each)
Economizer/Filter Filter Section Weight (lb) Economizer Weight (lb)
Fan Section Weight (lb) (each)
Tot al U ni t Weight (lb)
50BVT, U, V, W, X
034 044 054 064
1
2100218252220022225
1
40
1 310 200
1 650
4
3300854008615086150
2
40
2 310 200
2 650
2
40
2 310 200
2 650
2
40
2 310 200
2 650
For single piece units, use spreader bars and rigging straps if lifting with a crane to avoid damage to the unit. Otherwise, move with a fork truck using the shipping pallet.
Refer to Fig. 2-14 for unit dimensions.
Refer to Tables 3A and 3B for physical data. REMOVE PACKAGING — Remove all protective plastic,
remove and discard unit top cover protector, filter cover, controller display protector, and water piping connection packaging.
UNIT LOCATION — Locate the unit in an indoor area that allows easy removal of the filters, access panels, and accessories. Make certain enough space is available for service personnel to perform maintenance or repairs. Provide sufficient room to make all water, duct, and electrical connections. If the unit is located in a small mechanical equipment room, make sure adequate space is available for air to return freely to the unit. These units are not approved for outdoor installations and must be installed inside the structure. Do not locate in areas that are subject to freezing.
UNIT PLACEMENT — Ensure that the floor is structurally strong enough to support the weight of the equipment with minimum deflection. A good, level floor is required for proper unit operation and to ensure proper fit-up and alignment of all bolt together and union coupled modules on modular units.
a50-7257ef
USE SPREADER BAR TO PREVENT DAMAGE TO UNIT
4 X 4 ABOVE AND BELOW RETURN DUCT CONNECTIONS
NOTE: Units ship with the main air conditioning, economizer/ filter, and, when selected, the reheat coil sections assembled together. These can be easily disassembled, as required, in the field. The fan section(s) always ships separately.
Step 2 — Rig and Place Unit — Use proper lifting
and handling practices to avoid damage to the unit. Move modular units with a fork truck using the baserails provided, or use spreader bars and lifting straps as shown in Fig. 1.
Fig. 1 — Modular Unit Rigging
3
NOTES:
1. Dimensions in inches [mm].
2. VAV models (50BVJ) are rear return, top supply only.
3. Compressor, controls, and condenser access are through front panels.
4. Field power connections are 1-3/4 inches. Control connections are 7/8 inches.
5. Optional blower orientation is selected in model number nomenclature as option 9 in FIOP section (digits 15 and 16).
Shows recommended minimum service clearances.
OPTIONAL BLOWER ORIENTATION
OPTIONAL BLOWER ORIENTATION
STANDARD BLOWER ORIENTATION
STANDARD BLOWER ORIENTATION
Fig. 2 — 50BVC,J,Q020-034 Dimensions
4
a50-8199
NOTES:
1. Dimensions in inches [mm].
2. VAV models (50BVK) are rear return, top supply only.
3. Compressor, controls, and condenser access are through front panels.
4. Field power connections are 1-3/4 inches. Control connections are 7/8 inches.
5. Discharge (hot gas) connections are 1-1/8 in. OD.
6. Liquid line connections are 7/8 in. OD.
7. Optional blower orientation is selected in model number nomenclature as option 9 in FIOP section (digits 15 and 16).
RECOMMENDED CONDENSER MATCHES: 50BV020 one (1) 09DK020 (50/50 split each) 50BV024 one (1) 09DK024 (50/50 split each) 50BV028 one (1) 09DK028 (50/50 split each) 50BV034 one (1) 09DK034 (50/50 split each)
Shows recommended minimum service clearances.
OPTIONAL BLOWER ORIENTATION
OPTIONAL BLOWER ORIENTATION
STANDARD BLOWER ORIENTATION
STANDARD BLOWER ORIENTATION
Fig. 3 — 50BVE,K020-034 Dimensions
5
a50-8200
69.50
SHIPPING SECTION
65.50
BLOWER SECTION ACCESS
2.00
54.75
31.00
54.38
2.88
BLOWER SECTION ACCESS
EVAPORATOR
ACCESS
2.00
STANDARD DISCHARGE
COMPRESSOR ACCESS
REAR VIEW RETURN AIR VIEW
EVAPORATOR
ACCESS
49.75
21.75
9.88
EVAPORATOR ACCESS
LIFTING SUPPORT RAIL
23.75
18.75
80.00
15.00
REAR DISCHARGE (Optional)
FILTER ACCESS
ECONO COIL (Optional)
DIRECT EXPANSION EVAPORATOR
13.00
3.19
5.50
8.75
5.00
23.25
51.63
LEFT SIDE VIEW
EVAPORATOR
ACCESS
BLOWER SECTION ACCESS
81.50
3.75
10.75
111.00
ELECTRICAL BOX
ELECTRICAL BOX ACCESS
COMPRESSOR ACCESS
1.50
FRONT VIEW
NOTES:
1. Dimensions in inches.
2. All units are rear return airflow configuration.
3. Constant volume units are available with front or rear air supply.
4. VAV units (50BVW) are available with rear supply only.
5. Recommended minimum service clearances are as follows: a. Front and rear — 30 in. (762 mm) b. Left or right side — 65 in. (1651 mm) for coil removal c. Side opposite coil removal — 20 in. (508 mm)
Fig. 4 — 50BVT,V,W034 (High-Boy) Dimensions
a50-8201
REHEAT COIL (Optional)
WATER IN
(ECONO COIL
OPTIONAL)
6
ELECTRICAL
1.50
D
A
B
C
CONNECTIONS
A WATER OUT 2-1/2 in. FPT
B WATER IN 2-1/2 in. FPT
C CONDENSATE DRAIN 1-1/4 in. FPT
D ECONOMIZER DRAIN 1-1/4 in. FPT
REPLACEMENT FILTERS : EIGHT (8) AT 17 x 27 x 4 INCHES.
LEFT SIDE VIEW
CONNECTIONS
A WATER OUT 2-1/2 in. FPT
B WATER IN 2-1/2 in. FPT
C CONDENSATE DRAIN 1-1/4 in. FPT
D ECONOMIZER DRAIN 1-1/4 in. FPT
REPLACEMENT FILTERS : EIGHT (8) AT 17 x 27 x 4 INCHES.
NOTES:
1. Dimensions in inches.
2. All units are rear return airflow configuration.
3. Recommended minimum service clearances are as follows: a. Front and rear — 30 in. (762 mm) b. Left or right side — 65 in. (1651 mm) for coil removal c. Side opposite coil removal — 20 in. (508 mm)
Fig. 5 — 50BVT,V,W034 (Low-Boy) Dimensions
a50-8202
a50-8202.eps
7
69.50
SHIPPING SECTION
2.00 2.00
69.50
SHIPPING SECTION
4.00
65.50 65.50
BLOWER SECTION ACCESS
BLOWER SECTION ACCESS
54.75
80.00
31.00
54.38
2.88
BLOWER SECTION ACCESS
EVAPORATOR ACCESS
2.00
STANDARD DISCHARGE
81.50
COMPRESSOR
ACCESS
REAR VIEW RETURN AIR VIEW
9.88
19.75
COMPRESSOR ACCESS
LIFTING SUPPORT RAIL
49.75
21.75
EVAPORATOR ACCESS
ELECTRICAL BOX
ELECTRICAL BOX
ACCESS
EVAPORATOR ACCESS
COMPRESSOR ACCESS
EVAPORATOR ACCESS
ELECTRICAL BOX
ELECTRICAL BOX ACCESS
139.00
FRONT VIEW
NOTES:
1. Dimensions in inches.
2. All units are rear return airflow configuration.
3. CV units are available with front or rear air supply.
4. VAV units (50BVW) are available with rear supply only.
5. Recommended minimum service clearances are as follows: a. Front and rear — 30 in. (762 mm) b. Left and right sides — 65 in. (1651 mm) for coil removal
a50-8203
49.75
21.75
9.88
EVAPORATOR ACCESS
COMPRESSOR ACCESS
15.00
13.00
8.75
5.00
23.25
51.63
LEFT SIDE VIEW
18.75
23.75
5.50
REAR DISCHARGE
(OPTIONAL)
BLOWER SECTION ACCESS
3.19
FILTER ACCESS
ECONO COIL (OPTIONAL)
DIRECT EXPANSION EVAPORATOR
REHEAT COIL (OPTIONAL)
WATER IN
(ECONO COIL
1.50
OPTIONAL)
EVAPORATOR ACCESS
D
B
A
C
LEFT SIDE VIEW
CONNECTIONS
UNIT SIZE 044 054 064
A WATER OUT 2-1/2 in. FPT 3 in. FPT 3 in. FPT
B WATER IN 2-1/2 in. FPT 3 in. FPT 3 in. FPT
C CONDENSATE DRAIN 1-1/4 in. FPT 1-1/4 in. FPT 1-1/4 in. FPT
D ECONOMIZER DRAIN 1-1/4 in. FPT 1-1/4 in. FPT 1-1/4 in. FPT
REPLACEMENT FILTERS : SIXTEEN (16) AT 17 x 27 x 4 INCHES.
3.75
10.75
111.00
ELECTRICAL
1.50
Fig. 6 — 50BVT,V,W044-064 (High-Boy) Dimensions
8
NOTES:
1. Dimensions in inches.
2. All units are rear return airflow configuration.
3. Recommended minimum service clearances are as follows: a. Front and rear — 30 in. (762 mm) b. Left and right sides — 65 in. (1651 mm) for coil removal
CONNECTIONS
UNIT SIZE 044 054 064
A WATER OUT 2-1/2 in. FPT 3 in. FPT 3 in. FPT
B WATER IN 2-1/2 in. FPT 3 in. FPT 3 in. FPT
C CONDENSATE DRAIN 1-1/4 in. FPT 1-1/4 in. FPT 1-1/4 in. FPT
D ECONOMIZER DRAIN 1-1/4 in. FPT 1-1/4 in. FPT 1-1/4 in. FPT
REPLACEMENT FILTERS : SIXTEEN (16) AT 17 x 27 x 4 INCHES.
Fig. 7 — 50BVT,V,W044-064 (Low-Boy) Dimensions
a50-8204
9
69.50
SHIPPING SECTION
65.50
BLOWER SECTION ACCESS
2.00
54.75
31.00
54.38
2.88
BLOWER SECTION ACCESS
EVAPORATOR
ACCESS
2.00
STANDARD DISCHARGE
D C
COMPRESSOR
B
ACCESS
A
REAR VIEW RETURN AIR VIEW
EVAPORATOR
ACCESS
ELECTRICAL BOX
49.75
21.75
9.88
EVAPORATOR ACCESS
LIFTING SUPPORT RAIL
23.75
18.75
80.00
13.00
REAR DISCHARGE
(Optional)
FILTER ACCESS
ECONO COIL (Optional)
DIRECT EXPANSION EVAPORATOR
REHEAT COIL (Optional)
3.19
5.50
8.75
5.00
23.25
51.63
LEFT SIDE VIEW
EVAPORATOR
ACCESS
BLOWER SECTION ACCESS
81.50
10.75
111.00
ELECTRICAL
ELECTRICAL BOX ACCESS
COMPRESSOR ACCESS
1.50
FRONT VIEW
NOTES:
1. Dimensions in inches.
2. All units are rear return airflow configuration.
3. Constant volume units are available with front or rear air supply.
4. VAV units (50BVX) are available with rear supply only.
5. Recommended condenser match is ONE (1) 09DK034 (50/50 split).
6. Use proper piping practice for remote refr igerant connections. Refer to Carrier System Design Manual Part 3.
7. Recommended minimum service clearances are as follows:
a. Front and rear — 30 in. (762 mm) b. Left or right side — 65 in. (1651 mm) for coil removal c. Side opposite coil removal — 20 in. (508 mm)
Fig. 8 — 50BVU,X034 (High-Boy) Dimensions
WATER IN
(ECONO COIL
OPTIONAL)
F
E
CONNECTIONS
A LIQUID LINE CIRCUIT 1 7/8 in. OD
B LIQUID LINE CIRCUIT 2 7/8 in. OD
C DISCHARGE LINE CIRCUIT 1 1-1/8 in. OD
D DISCHARGE LINE CIRCUIT 2 1-1/8 in. OD
E CONDENSATE DRAIN 1-1/4 in. FPT
F ECONOMIZER DRAIN 1-1/4 in. FPT
REPLACEMENT FILTERS : EIGHT (8) AT 17 x 27 x 4 INCHES.
10
LEFT SIDE VIEW
1.50
a50-8205
CONNECTIONS
A LIQUID LINE CIRCUIT 1 7/8 in. OD
B LIQUID LINE CIRCUIT 2 7/8 in. OD
C DISCHARGE LINE CIRCUIT 1 1-1/8 in. OD
D DISCHARGE LINE CIRCUIT 2 1-1/8 in. OD
E CONDENSATE DRAIN 1-1/4 in. FPT
F ECONOMIZER DRAIN 1-1/4 in. FPT
REPLACEMENT FILTERS : EIGHT (8) AT 17 x 27 x 4 INCHES.
NOTES:
1. Dimensions in inches.
2. All units are rear return airflow configuration.
3. Recommended condenser match is ONE (1) 09DK034 (50/50 split).
4. Use proper piping practice for remote refrigerant connections. Refer to Carrier System Design Manual Part 3.
5. Recommended minimum service clearances are as follows:
a. Front and rear — 30 in. (762 mm) b. Left or right side — 65 in. (1651 mm) for coil removal c. Side opposite coil removal — 20 in. (508 mm)
Fig. 9 — 50BVU,X034 (Low-Boy) Dimensions
a50-8206
a50-8206
11
69.50
SHIPPING SECTION
2.00 2.00
69.50
SHIPPING SECTION
4.00
65.50 65.50
BLOWER SECTION ACCESS
BLOWER SECTION ACCESS
54.75
80.00
31.00
54.38
2.88
BLOWER SECTION ACCESS
EVAPORATOR
ACCESS
2.00
STANDARD DISCHARGE
81.50
D C
COMPRESSOR
B A
ACCESS
REAR VIEW RETURN AIR VIEW
9.88
49.75
21.75
EVAPORATOR ACCESS
ELECTRICAL BOX
ELECTRICAL BOX
ACCESS
EVAPORATOR ACCESS
COMPRESSOR ACCESS
19.75
EVAPORATOR ACCESS
ELECTRICAL BOX
ELECTRICAL BOX ACCESS
D
C
COMPRESSOR
B
A
ACCESS
LIFTING SUPPORT RAIL
49.75
21.75
EVAPORATOR ACCESS
COMPRESSOR ACCESS
139.00
FRONT VIEW
NOTES:
1. Dimensions in inches.
2. All units are rear return airflow configuration.
3. CV units are available with front or rear air supply.
4. VAV units (50BVX) are available with rear supply only.
5. Use proper piping practice for remote refrigerant connections. Refer to Carrier System Design Manual Part 3.
6. Recommended minimum service clearances are as follows:
a. Front and rear — 30 in. (762 mm) b. Left and right sides — 65 in. (1651 mm) for coil removal
a50-8207
9.88
13.00
8.75
5.00
23.25
51.63
LEFT SIDE VIEW
18.75
23.75
5.50
REAR DISCHARGE
(OPTIONAL)
BLOWER SECTION
ACCESS
3.19
FILTER ACCESS
ECONO COIL (OPTIONAL)
DIRECT EXPANSION EVAPORATOR
REHEAT COIL (OPTIONAL)
WATER IN
(ECONO COIL
1.50
OPTIONAL)
EVAPORATOR
ACCESS
111.00
F
E
CONNECTIONS
UNIT SIZE 044 054 064
A LIQUID LINE CIRCUIT 1, 2 7/8 in. OD 7/8 in. OD 7/8 in. OD
B LIQUID LINE CIRCUIT 3, 4 7/8 in. OD 7/8 in. OD 7/8 in. OD
C DISCHARGE LINE CIRCUIT 1, 2 1-1/8 in. OD 1-1/8 in. OD 1-1/8 in. OD
D DISCHARGE LINE CIRCUIT 3, 4 1-1/8 in. OD 1-1/8 in. OD 1-1/8 in. OD
E CONDENSATE DRAIN 1-1/4 in. FPT 1-1/4 in. FPT 1-1/4 in. FPT
F ECONOMIZER DRAIN 1-1/4 in. FPT 1-1/4 in. FPT 1-1/4 in. FPT
REPLACEMENT FILTERS : SIXTEEN (16) AT 17 x 27 x 4 INCHES.
LEFT SIDE VIEW
10.75
ELECTRICAL
1.50
Fig. 10 — 50BVU,X044-064 (High-Boy) Dimensions
12
NOTES:
1. Dimensions in inches.
2. All units are rear return airflow configuration.
3. Use proper piping practice for remote refrigerant connections. Refer to Carrier System Design Manual Part 3.
4. Recommended minimum service clearances are as follows:
a. Front and rear — 30 in. (762 mm) b. Left and right sides — 65 in. (1651 mm) for coil removal
CONNECTIONS
A LIQUID LINE CIRCUIT 1, 2 7/8 in. OD 7/8 in. OD 7/8 in. OD
B LIQUID LINE CIRCUIT 3, 4 7/8 in. OD 7/8 in. OD 7/8 in. OD
C DISCHARGE LINE CIRCUIT 1, 2 1-1/8 in. OD 1-1/8 in. OD 1-1/8 in. OD
D DISCHARGE LINE CIRCUIT 3, 4 1-1/8 in. OD 1-1/8 in. OD 1-1/8 in. OD
E CONDENSATE DRAIN 1-1/4 in. FPT 1-1/4 in. FPT 1-1/4 in. FPT
F ECONOMIZER DRAIN 1-1/4 in. FPT 1-1/4 in. FPT 1-1/4 in. FPT
REPLACEMENT FILTERS : SIXTEEN (16) AT 17 x 27 x 4 INCHES.
UNIT SIZE 044 054 064
Fig. 11 — 50BVU,X044-064 (Low-Boy) Dimensions
a50-8208
13
NOTES:
1. Dimensions in inches [mm].
2. Refer to base unit certified drawing for additional unit dimensions, service clearance, and alternate airflow configurations.
a50-7306ef
Fig. 12 — 50BVC,J,Q020-028 with Optional Waterside Economizer Dimensions
14
NOTES:
1. Dimensions in inches [mm].
2. Refer to base unit certified drawing for additional unit dimensions, service clearances, and alternate airflow configurations.
a50-7307ef
Fig. 13 — 50BVC,J,Q034 with Optional Waterside Economizer Dimensions
15
a50-8235
*
*
Size 034 Units
Size 044-064 Units
Shipping Weights (lb)
50BVT,U,V,W,X UNIT
MAIN AIR CONDITIONING SECTION (EACH) NUMBER OF SECTIONS 12221222 SECTION WEIGHT 1450 1175 1550 1575 2100 1825 2200 2225 REHEAT COIL OPTION 40 40 40 40 40 40 40 40 FILTER/ECONOMIZER SECTION (EACH) NUMBER OF SECTIONS 12221222 FILTER SECTION 310 310 310 310 310 310 310 310 ECONOMIZER OPTION 200 200 200 200 200 200 200 200 FAN SECTION (EACH) NUMBER OF SECTIONS 1222 FAN SECTION 650 650 650 650 TOTAL UN IT NUMBER OF SECTIONS 36662444 UNIT WITH OPTIONS 2650 4750 5500 5550 2650 4750 5500 5550
*High-boy/low-boy.
034 044 054 064 034 044 054 064
Fig. 14 — Modular Shipping Weights — 50BVT,U,V,W,X
HIGH-BOY UNIT LOW-BOY UNIT
AIR CONDITIONING SECTION
INCLUDED IN
16
Table 3A — Physical Data — 50BVC,E,J,K,Q
UNIT 50BVC,E,J,K,Q 020 024 028 034 NOMINAL CAPACITY (Tons) 18 20 25 30 OPERATING WEIGHT (lb)
50BVC,Q…50BVJ 1192…1227 1378…1413 1428…1473 1680…1725 50BVE…50BVK 1110…1145 1290…1325 1320…1365 1520…1565
COMPRESSOR Copeland Scroll
Quantity 2222 Number of Refrigerant Circuits 2222 Oil (ounces) Ckt 1…Ckt 2 85…85 110…110 110…110 140…140
REFRIGERANT TYPE R-22 or R-410A
Expansion Device TXVTXVTXVTXV Operating Charge (lb) Ckt 1…Ckt 2 8.1…8.1 9.1…9.1 9.1…9.1 18.0…18.0
CONDENSER (50BVC,Q,J only) Tube-in-Tube Coaxial
Quantity of Manifolded Circuits 2222 Nominal Flow Rate (GPM) 54 60 75 90 Water Flow Range (GPM) 36-72 40-80 50-100 60-120 Max. Water Working Pressure (PSIG) 400 400 400 400 Max. Refrig. Working Pressure (PSIG) 450 (600*) 450 (600*) 450 (600*) 450 (600*) Min. Entering Water Temp. (°F) 50 50 50 50 Max. Entering Water Temp. (°F) 110 110 110 110 Waterside Volume (gal) 3.6 4.0 5.0 6.0
EVAPORATOR COIL
Rows…Fins/in. 3…14 3…14 3…14 3…14 Total Face Area (sq ft) 18.1 18.1 18.1 22.0
EVAPORATOR FAN
Quantity…Size 2…15x15 2…15x15 2…15x15 2…15x15 Type Drive Belt Belt Belt Belt Nominal CFM 7200 8000 10,000 12,000 Std Motor Qty…HP…Frame Size 2…1.5…56 2…2…56H 2…3…56HZ 2…5…56HZ Alt 1 Motor Qty…HP…Frame Size 2…2…56H 2…3…56HZ 2…5…56HZ Alt 2 Motor Qty…HP…Frame Size 2…3…56HZ 2…5…56HZ Alt 3 Motor Qty…HP…Frame Size 2…5…56HZ Motor Nominal RPM (1.5, 2, 3, HP) 1725 1725 1725 Motor Nominal RPM (5 HP) 3450 3450 3450 3450 Fan Drive RPM Range
Std Fan Drive (1.5, 2, 3 HP) 753-952 753-952 753-952 Std Fan Drive (5 HP) 967-1290 967-1290 967-1290 967-1290
Med Static Fan Drive (1.5, 2, 3 HP) 872-1071 872-1071 872-1071 Motor Bearing Type Ball Ball Ball Ball Maximum Allowable RPM 1300 1300 1300 1300 Motor Pulley Pitch Diameter
Std Fan Drive (1.5, 2, 3 HP) 3.7-4.7 3.7-4.7 3.7-4.7
Std Fan Drive (5 HP) 2.9-3.9 2.9-3.9 2.9-3.9 2.9-3.9
Med Static Fan Drive (1.5, 2, 3 HP) 4.3-5.3 4.3-5.3 4.3-5.3 Motor Shaft Diameter (in.) (1.5, 2 HP) Motor Shaft Diameter (in.) (3, 5 HP) Belt, Qty…Type…Length (in.)
Std Fan Drive (1.5, 2 HP) 1…B…39 1…B…39
Std Fan Drive (3 HP) 2…B…39 2…B…39 2…B…39
Std Fan Drive (5 HP) 2...BX…42 2...BX…42 2...BX…42 2...BX…42
Med Static Fan Drive (1.5, 2 HP) 1…B…40 1…B…40
Med Static Fan Drive (3 HP) 2…B…40 2…B…40 2…B…40 Pulley Center Line Distance (in.) 10.1…10.9 10.1…10.9 10.1…10.9 10.1…10.9 Speed Change Per Full Turn of
Moveable Pulley Flange (RPM)
Std Fan Drive (1.5, 2, 3 HP) 33 33 33
Std Fan Drive (5 HP) 54 54 54 54
Med Static Fan Drive (1.5, 2, 3 HP) 33 33 33 Fan Shaft Diameter (in.) 1111
5
/
8
7
/
8
HIGH PRESSURE SWITCHES (PSIG)
Cutout 380 (420*) ± 10 380 (420*) ± 10 380 (420*) ± 10 380 (420*) ± 10 Reset (Auto) 300 (420*) ± 15 300 (420*) ± 15 300 (420*) ± 15 300 (420*) ± 15
LOW PRESSURE SWITCHES (PSIG)
Cutout 20 (40*) ± 3 20 (40*) ± 3 20 (40*) ± 3 20 (40*) ± 3 Reset (Auto) 40 (60*) ± 5 40 (60*) ± 5 40 (60*) ± 5 40 (60*) ± 5
REMOTE REFRIGERANT CONNECTIONS
(50BVE,K Only) Discharge (Hot Gas) Connection (in.) Qty…Size 2…1 Liquid Connection (in.) Qty…Size 2…7/
1
/
8
8
RETURN AIR FILTERS
Quantity…Size (in.) 4…20x34.5x1 4…20x34.5x1 4…20x34.5x1 4…30x34.5x1
LEGEND *R-410A models.
TXV — Thermostatic Expansion Valve
5
/
8
7
/
8
2…11/
2…7/
——
7
/
8
8
8
2…11/
2…7/
8
8
7
/
8
2…11/
2…7/
8
8
17
Table 3B — Physical Data — 50BVT,U,V,W,X
UNIT 50BVT,U,V,W,X 034 044 054 064 NOMINAL CAPACITY (Tons) 30 40 50 60 OPERATING WEIGHT (lb)
50BVT,V…50BVW 2580…2645 4334…4404 5198…5298 5230…5330 50BVU…50BVX 2420…2485 4094…4164 4938…5038 4970…5070
COMPRESSOR Copeland Scroll
Quantity 2444 Number of Refrigerant Circuits 2444 Oil (oz.)
Circuit 1…Circuit 2 140…140 110…110 140…140 140…140 Circuit 3…Circuit 4 110…110 140…140 140…140
REFRIGERANT TYPE R-22
Expansion Device TXV TXV TXV TXV Operating Charge (lb)
Circuit 1…Circuit 2 18.0…18.0 10.0…10.0 18.0…18.0 18.0…18.0 Circuit 3…Circuit 4 10.0…10.0 18.0…18.0 18.0…18.0
CONDENSER (50BVT,V,W only) Tube-in-Tube Coaxial
Quantity of Manifolded Circuits 2444 Nominal Flow Rate (GPM) 90 120 150 180 Water Flow Range (GPM) 60-120 80-160 100-200 120-240 Max. Water Working Pressure (PSIG) 400 400 400 400 Max. Refrig. Working Pressure (PSIG) 450 450 450 450 Min. Entering Water Temp. (°F) 50 50 50 50 Max. Entering Water Temp. (°F) 110 110 110 110 Waterside Volume (gal) 6.0 9.0 11.3 13.5
EVAPORATOR COIL
Rows…Fins/in. 4…12 3…12 4…12 4…12 Total Face Area (sq ft) 23.2 46.4 46.4 46.4
EVAPORATOR FAN
Quantity…Size 1…18x18 2…18x18 2…18x18 2…18x18 Type Drive Belt Belt Belt Belt Nominal CFM 12,000 16,000 20,000 24,000 Motor Option 1 Qty…HP…Frame Size 1…7.5…213T 2…7.5…213T 2…7.5…213T 2…7.5…213T Motor Option 2 Qty…HP…Frame Size 1…10…215T 2…10…215T 2…10…215T 2…10…215T Motor Option 3 Qty…HP…Frame Size 1…15…254T 2…15…254T 2…15…254T 2…15…254T Motor Option 4 Qty…HP…Frame Size 1…20…256T 2…20…256T 2…20…256T Motor Nominal RPM 1750 1750 1750 1750 Fan Drive RPM Range
Standard (7.5 HP) 780-960 780-960 780-960 780-960 Standard (10, 15, 20 HP), Med Static (7.5 HP) 805-991 805-991 805-991 805-991 Med Static (10, 15, 20 HP), High Static (7.5 HP) 960-1146 960-1146 960-1146 960-1146
High Static (10, 15, 20 HP) 1119-1335 1119-1335 1119-1335 1119-1335 Motor Bearing Type Ball Ball Ball Ball Maximum Allowable RPM 1450 1450 1450 1450 Motor Pulley Pitch Diameter
Std Fan Drive (7.5 HP) 5.2-6.4 5.2-6.4 5.2-6.4 5.2-6.4
Std Fan Drive (10, 15, 20 HP), Med Static (7.5 HP) 4.8-6.0 4.8-6.0 4.8-6.0 4.8-6.0
Med Static Fan Drive (10, 15, 20 HP), High Static (7.5 HP) 5.8-7.0 5.8-7.0 5.8-7.0 5.8-7.0
High Static Fan Drive (10, 15, 20 HP) 5.8-7.0 5.8-7.0 5.8-7.0 5.8-7.0 Motor Shaft Diameter (in.) (7.5, 10 HP) 1 Motor Shaft Diameter (in.) (15, 20 HP) 15/ Belt, Qty…Type…Length (in.)
Std Fan Drive (7.5 HP) 2…B…48 2...B...48 2…B…48 2…B…48
Std Fan Drive (10, 15, 20 HP), Med Static (7.5 HP) 2…B…46 2…B…46 2…B…46 2…B…46
Med Static Fan Drive (10, 15, 20 HP), High Static 7.5 HP) 2…B…48 2…B…48 2…B…48 2…B…48
High Static Fan Drive (10, 15, 20 HP) 2…B…45 2…B…45 2…B…45 2…B…45 Pulley Center Line Distance (in.) 10.2-11.4 10.2-11.4 10.2-11.4 10.2-11.4 Speed Change Per Full Turn of Moveable Pulley Flange (RPM)
Std Fan Drive (7.5 HP) 36 36 36 36
Std Fan Drive (10, 15, 20 HP), Med Static (7.5 HP) 31 31 31 31
Med Static Fan Drive (10, 15, 20 HP), High Static (7.5 HP) 31 31 31 31
High Static Fan Drive (10, 15, 20 HP) 36 36 36 36 Fan Shaft Diameter (in.) 1
HIGH PRESSURE SWITCHES (PSIG)
Cutout 380 ± 10 380 ± 10 380 ± 10 380 ± 10 Reset (Auto) 300 ± 15 300 ± 15 300 ± 15 300 ± 15
LOW PRESSURE SWITCHES (PSIG)
Cutout 20 ± 3 20 ± 3 20 ± 3 20 ± 3 Reset (Auto) 40 ± 5 40 ± 5 40 ± 5 40 ± 5
REMOTE REFRIGERANT CONNECTIONS (50BVU,X Only)
Discharge (Hot Gas) Connection (in.) Qty…Size 2…1 Liquid Connection (in.) Qty…Size 2…7/
RETURN AIR FILTERS
Quantity…Size (in.) 8…17x27x4 16…17x27x4 16…17x27x4 16…17x27x4
3
/
8 8
7
/
16
1
/
8
8
13/ 15/
17/
16
4…11/
4…7/
8 8
8
8
13/ 15/
17/
16
4…11/
4…7/
8 8
8
8
13/ 15/
17/
4…11/
4…7/
8 8
16
8
8
18
ACOUSTICAL CONSIDERATIONS — Proper acoustical considerations are a critical part of every system’s design and operation. Each system design and installation should be reviewed for its own unique requirements. For job specific requirements, contact an acoustical consultant for guidance and recommendations.
In general, to reduce noise, consider the following:
• Locate mechanical room and ducts away from noise sensitive locations. Whenever possible, work with the architect to locate the equipment rooms around the perimeters of restrooms, hallways, fire escapes, stair wells, etc., to reduce noise transmission. This allows not only for isolation from radiated sound but also enables the contractor to route duct systems around sensitive locations.
• Construct the equipment room of concrete block or use a double offset stud wall with interwoven insulation. Seal all penetrations.
• Design the system for low total static pressure.
• Use suitable vibration isolation pads or isolation springs according to the design engineer's specifications.
• A flexible canvas duct connector is recommended on both the supply and return air sides of units to be connected to system ductwork.
• Use a minimum of 15 ft of return ductwork between the last air terminal or diffuser and the unit.
• Insulate supply and return ducts with 2-in., 3-lb density insulation.
• Round duct is recommended. If rectangular ductwork is used, keep aspect ratios as small as possible (i.e., as close to square as possible).
• Avoid any direct line of sight from return air grilles into the unit's return. If return air is to be ducted to an equipment room, an elbow should be installed within the equipment room.
• Running a return air drop to near the floor of the room will aid in sound attenuation.
• Do not exceed the recommended supply duct velocity of 2,000 fpm.
• Do not exceed the recommended return duct velocity of 1,000 fpm.
• Use turning vanes on 90-degree elbows.
• Place isolation springs under each corner and under each compressor if utilized.
ASSEMBLING MODULAR UNITS — 50BVT,U,V,W,X 30 to 60 ton units ship in the number of pieces shown in Table
2. Reassemble the unit. Use the loose hardware provided in the
main air-conditioning section and the instructions below.
1. The filter/economizer section ships bolted to the main air­conditioning section and can be removed in the field. When reattaching the filter/economizer section to the main air-conditioning section, place the filter side of the filter/economizer section facing out and away from the main air conditioning section.
2. If the unit has 2 filter/economizer and 2 main air­conditioning sections (40 through 60 ton units), bolt the remaining filter/economizer section and main air­conditioning section together, as in Step 1.
3. For units with 2 filter/economizer and 2 main air­conditioning sections, use the provided unions to assem­ble the water connections between the 2 additional sections joined in Step 2.
4. For units with multiple air conditioning sections, connect the condensate drain hoses from the “B” side of the unit to the drain manifold on the “A” side of the unit.
5. For unit sizes 044-064, connect power wiring from the main terminal block in the “A” side of the unit to the power terminal block in the “B” side of the unit.
6. For VAV units only, connect the plenum tubing, coiled behind the VAV control panel, to the bulkhead fittings located in the discharge of the supply fan. This connects the high pressure supply to the high side of the duct high static pressure switch.
CAUTION
Remove all shipping blocks, if any, under blower housing or damage to the fan may occur.
Step 3 — Install Ductwork — The VAV units must
use a “pair of pants” configuration as shown in Fig. 15. Refer to the Carrier System Design Manual or ASHRAE (American Society of Heating, Refrigerating and Air Conditioning Engi­neers) standards for the recommended duct connection to unit with 2 fans.
A
NOTE: A = 11/2 to 21/2B
Fig. 15 — Typical Fan Discharge Connections for
Multiple Fan Units
A supply air outlet collar and return air duct flange are pro­vided on all units to facilitate duct connections. Refer to dimen­sional drawings (Fig. 2-14) for connection sizes and locations.
A flexible canvas duct connector is recommended on both supply and return air sides of the units to be connected to the system ductwork.
All metal ductwork should be adequately insulated to avoid heat loss or gain and to prevent condensation from forming on the duct walls. Uninsulated ductwork is not recommended, as the unit's performance will be adversely affected.
Do not connect discharge ducts directly to the blower outlet(s). The factory filter should be left in place on a free return system.
If the unit will be installed in a new installation, the duct system should be designed in accordance with the System De­sign Manual, Part 2 and with ASHRAE (American Society of Heating, Refrigeration and Air Conditioning Engineers) proce­dures for duct sizing. If the unit will be connected to an existing duct system, check that the existing duct system has the capaci­ty to handle the required airflow for the unit application at an
a50-8357.eps
B
19
acceptable system static pressure. If the existing duct system is too small, larger ductwork must be installed.
The duct system and diffusers should be sized to handle the design airflow volumes quietly. To maximize sound attenuation of the unit's blower(s), the supply and return air plenums should be insulated for a length of at least 15 ft from the unit. Direct line of sight from return air grilles into the unit's return should be avoided. If return air is to be ducted to an equipment room, an elbow should be installed within the equipment room. Running a return air drop to near the floor of the room will aid in sound attenuation. Avoid transmitting vibrations generated by the movement of air in the ducting to the walls of the building. This is especially important where ductwork penetrates walls. The maximum recommended return air velocity is 1,000 fpm. Lower return air velocities will result in lower sound power levels. The use of round supply duct plenums should be considered, as it will significantly reduce low frequency sound at the equipment room. If rectangular supply plenums are used, the aspect ratio of the duct should be kept as small as possible (i.e., as close to square as possible). The large, flat surface areas associated with large aspect ratio duct systems will transmit sound to the space, and the potential for duct-generated noise is increased. The max­imum recommended supply air duct velocity is 2,000 fpm.
Units with two fans should have a properly designed “pair of pants” duct connection. An adequate straight length of ducting from the unit should be allowed before elbows are installed. If connecting an elbow directly to the fan outlet, a minimum straight length of 2 fan diameters from the fan outlet is recommended. Elbows should turn in the direction of fan ro­tation, if possible. Abrupt turns will generate air turbulence and excessive noise. Turning vanes should be used in all short radi­us bends. Ensure that ducting does not obstruct access to the unit for routine servicing.
DUCT STATIC PRESSURE PROBE AND TUBING (VAV Only) — On VAV systems, the duct static pressure sensor and tubing are field-mounted. The sensor tubing sensing point should be located near the end of the main supply trunk duct in a position free from turbulence effects and at least 10 duct di­ameters downstream and 4 duct diameters upstream from any major transitions or branch take-offs. Incorrectly placing the sensing point could result in improper operation of the entire VAV s y st e m .
Install the factory-supplied duct static pressure probe with the tip facing into the airflow. See Fig. 16.
AIRFLOW
PROBE
a50-7138ef
TUBING
Fig. 16 — Duct Static Pressure Probe
(P/N 39EK20462)
1
Use
/4-in. OD approved polyethylene tubing for up to 50 ft (3/8-in. OD for 50 to 100 ft) to connect the probe to the bulkhead fitting mounted above the unit display panel (Fig. 17). Carefully route the tubing from the probe to this bulkhead fitting.
The static pressure control should be adjusted so that, at full airflow, all of the remote VAV terminal boxes receive the minimum static pressure required plus any downstream resis­tance. Control the system to the lowest static pressure set point that will satisfy airflow requirements. Lower static pressure set points reduce total required brake horsepower and reduce generated sound levels.
DUCT HIGH-STATIC (DHS) LIMIT SWITCH (VAV Only) — The duct high static limit switch is a mechanical safety that prevents duct overpressurization. The switch is lo­cated on the side of the VAV low voltage control panel (Fig. 18) and is factory set at 3 in. wg. To make an adjustment using an accurate differential pressure gage, connect low side and high side to gage and pressure source. Place a voltmeter across common and normally open contacts. Rotate the adjust­ment knob (Fig. 19) clockwise to increase pressure setting and counterclockwise to decrease pressure setting. When the bot­tom of the adjustment knob is approximately
1
/8-in. from the
switch body, the switch will trip at approximately 3 in. wg.
IMPORTANT: Use tubing that complies with local codes. Improper location or installation of the supply duct pres­sure tubing will result in unsatisfactory unit operation and poor performance.
a50-7267ef
DUCT STATIC PRESSURE PROBE BULKHEAD FITTING
EXPN
TEST
STAT
3
2
1
SRVC
ALRM
EDIT
HISTALGO
SET
5
SCHD
6
4
CLEAR
8
9
7
ENTER
.
0
WARNING
ALARM
LOCAL
OFF
REMOTE
EXPN
STAT
SET
2
1
EDIT
5
SCHD
4
8
7
0
WARNING
LOCAL
REMOTE
Fig. 17 — Display Panel Location on Unit Front Panel
20
3
6
9
.
OFF
TEST
SRVC
ALRM
HIST ALGO
CLEAR
ENTER
ALARM
a50-8253
Fig. 18 — DHS Pressure Limit Location
a50-7268tf
Fig. 19 — DHS Limit Switch (P/N 190060)
Step 4 — Make Piping Connections
CONDENSER WATER PIPING (Water-Cooled Only) — Always follow national and local codes when installing water piping to ensure a safe and proper installation. Connections to the unit should incorporate vibration eliminators to reduce noise and vibration to the building, and shutoff valves to facili­tate servicing.
Prior to connecting the unit(s) to the condenser water system, the system should be flushed to remove foreign material that could cause condenser fouling. Install a screen strainer with a minimum of 20 mesh ahead of the condenser inlet to prevent condenser fouling and internal condenser tube damage from foreign material.
Supply and return water piping must be at least as large as the unit connections, and larger for long runs. Refer to the System Design Manual, Part 3, and standard piping practice, when sizing, planning, and routing water piping. See dimen­sion drawings (Fig. 2-14) for water connection sizes and locations.
Units are furnished standard with a copper heat exchanger. A cupronickel heat exchanger is also available as a
factory-installed option. Copper is adequate for closed loop systems where good quality water is available. In conditions where scale formation or water treatment is questionable, the optional cupronickel heat exchanger should be used. Where the water is especially corrosive or could lead to excessive fouling, intermediate plate frame heat exchangers are recommended.
CAUTION
Galvanized pipe or fittings are not recommended with 50BV units due to the possibility of galvanic corrosion caused by dissimilar metals. When selecting piping materials, use only approved piping materials that meet applicable codes and that will handle the temperatures and pressures that may be experienced in the application. Piping systems will sweat if low temperature fluid is used in the system. For these applications, supply and return water piping should be insulated to protect from condensa­tion damage. The minimum recommended entering water temperature to the unit is 50 F.
The unit is capable of operating with entering water temper­atures as low as 50 F, without the need for head pressure control. If the entering water temperature is expected to be lower, or more stable unit operation is desired, a field-supplied water-regulating valve may be used.
This unit has multiple independent refrigerant circuits with separate condensers. The individual condensers are manifolded together on the waterside to provide easy, single-point water connections. In order to achieve proper head pressure control when a water-regulating valve is used, a temperature-actuated valve is recommended. This allows any of the independent refrigerant circuits to operate while still modulating condenser water flow in response to loop water temperature.
A glycol solution should be used if ambient temperatures are expected to fall below freezing or if the loop water temper­ature is below 50 F while operating in the reverse cycle heating mode (heat pump units only). Refer to Table 4, which lists freezing points of glycol at different concentrations. A minimum concentration of 20% is recommended. Water pressure drop will increase and unit performance will decrease with increasing glycol concentrations.
Units with factory-installed waterside economizers have cooling water passing through the economizer and condenser in series while operating in the economizer mode. During normal operation, water bypasses the economizer coil.
Table 4 — Glycol Freezing Points
% GLYCOL
20 18 19 30 79 40 –7 –5 50 –28 –27
Ethylene Glycol Proplylene Glycol
All manual flow valves used in the system should be of the ball valve design. Globe or gate valves must not be used due to high pressure drops and poor throttling characteristics.
Do not exceed recommended condenser fluid flow rates shown in Tables 5A and 5B. Serious damage or erosion of the heat exchanger tubes could occur. Piping systems should not exceed 10 fps fluid velocities to ensure quietness and tube wall integrity. Refer to Tables 5A and 5B for condenser water pres­sure drop versus flow rate. Flow rates outside of the published range should not be used.
Ball valves should be installed in the supply and return lines for unit isolation and water flow balancing.
FREEZE POINT (° F)
21
Loading...
+ 47 hidden pages