Carrier 50AH024-096 User Manual

Horizontal Indoor Single-Package Cooling Units
with PURON® Refrigerant (R-410A)
Installation, Start-Up, and
Service Instructions
ROOMTOP
50AH024-096
®
CONTENTS
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . 1
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-17
Step 3 — Provide Unit Support . . . . . . . . . . . . . . . . . . . 1
Step 4 — Rig and Place Unit . . . . . . . . . . . . . . . . . . . . . 8
Step 5 — Make Condensate Piping
Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Step 6 — Install Ductwork. . . . . . . . . . . . . . . . . . . . . . . . 8
Step 7 — Split Systems (Factory Option,
if Required). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Step 8 — Make Electrical Connections . . . . . . . . . . 10
• FIELD CONTROL WIRING
• THERMOSTAT WIRE
Step 9 — Adjust Fan Speed . . . . . . . . . . . . . . . . . . . . . 10
START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17,18
SAFETY CONSIDERATIONS
Installing and servicing air-conditioning equipment can be hazardous due to system pressure and electrical components. Only trained and qualified service personnel should install, repair, or service air-conditioning equipment.
Untrained personnel can perform basic maintenance func­tions such as cleaning coils and filters and replacing filters. All other operations should be performed by trained service per­sonnel. When working on air-conditioning equipment, observe precautions in the literature and on tags and labels attached to unit.
Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth for unbrazing operations. Have fire extinguisher available.
WARNING
Disconnect all power to the unit before performing mainte­nance or service. Electrical shock and personal injury could result.
NOTE: Ensure voltage on unit agrees with voltage listed on the unit rating plate.
GENERAL
The 50AH024-096 units are single-package, indoor, hori­zontally mounted air conditioners of 2 to 8 tons capacity. The 50AH units are ASHRAE (American Society of Heating, Re­frigerating and Air Conditioning Engineers) 90.1 compliant.
These units can be mounted as factory-shipped single­package units or can be separated and mounted as a split
system. If unit is split, the condensing section must be mounted horizontally.
All units are designed to be ducted on both the condenser and evaporator sides. Centrifugal blowers are used to ensure quiet air delivery to the conditioned space. Sound level requirements should be determined before final unit installa­tion site is chosen.
Unit servicing is relatively simple since access to the con­denser and evaporator motors, blowers, belt, and pulley is gained through access panels located on the sides of the unit. These panels may also be used for cleaning of condenser coils. Unit side panels also provide access to control box and pres­sure switches.
Refrigeration cycle components (e.g., compressor, filter drier, etc.) can be serviced upon removal of the base unit from the space.
INSTALLATION
WARNING
Determine building alterations required to run piping, wir­ing, and ductwork. Follow dimensional drawings carefully for ductwork, piping locations, electrical wiring, and over­all unit dimensions. Read all installation instructions before starting installation.
The 50AH units are intended for indoor installation only.
Step 1 — Receive and Inspect Unit — Unpack and
check unit against shipping order. See Fig. 1 for model number nomenclature. Inspect carefully for concealed shipping dam­age. If unit is damaged or incomplete, file claim with transpor- tation company and advise Carrier immediately.
Step 2 — Protect Unit from Damage — To main-
tain warranty, unit must be protected against theft and vandal­ism and stored indoors at all times.
Step 3 — Provide Unit Support — Refer to Fig. 2-5
for unit dimensions. Refer to Table 1 for unit sizes and weights.
Each unit requires the following field-supplied items:
8 — threaded suspension rods (
minimum), 4 additional rods are needed if the unit
has a factory-installed air-side economizer 8—washers 8 — locknuts
Install the 8 field-supplied rods by suspending them from a
suitable ceiling support. Locate rods to mate with 8 outside cor­ner rigging holes shown in Fig. 2-5. Unit center of gravity is shown in Fig. 6.
The ceiling and ceiling supports of existing buildings may
require reinforcements; follow all applicable codes.
3
/8-in.-16 SAE Grade 1
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53500057-01 Printed in U.S.A. Form 50AH-14SI Pg 1 5-10 Replaces: 50AH-12SI
Evaporator Configuration
Factory-Installed Options
50AH AC 048 5 – – – – 2 1 XX
50AH – Horizontal, Indoor
Single-Package Cooling Unit
Packaging 1 – Domestic 2 – Export
Voltage Description
5 – 208/230-3-60 6 – 460-3-60
Unit Size - Nominal Tons 024 –2 036 – 3 048 – 4
Compressor Options AC – Air Cooled
060 –5 072 – 6 096 – 8
3 – 208/230-1-60
Condenser Configuration
Design Changes 2 – R-410A Original Design
Cabinet Type
S – Splittable*
– – Standard
Economizer and Hot Gas Options
A – Hot Gas Bypass B – Hot Gas Reheat†
– None
C – Air-S
ide Economizer with Controls
E – Hot Gas Bypass and Air-Side Economizer† F – Hot Gas Bypass, Air-Side Economizer, and
Hot Gas Reheat†
D – Hot Gas Bypass and Hot Gas Reheat†
G – Hot Gas Reheat and Air-Side Economizer†
B – Standard Motor with Alternate 2 Drive
A – Standard Motor with Alternate 1 Drive
– – Standard Motor with Standard Drive
E – Upgrade 1 Motor with Alternate 2 Drive
D – Upgrade 1 Motor with Alternate 1 Drive
C – Upgrade 1 Motor with St
andard Drive
H – Upgrade 3 Motor with Alternate 2 Drive
G – Upgrade 2 Motor with Alternate 2 Drive
F – Upgrade 2 Motor with Alternate 1 Drive
B – Standard Motor with Alternate 1 Drive
A – Standard Motor with Standard Drive, Flooded Condenser
– – Standard Motor with Standard Drive
E – Upgrade 1 Motor with Alternate 3 Drive
D – Upgrade 1 Motor with Alternate 2 Drive
C – Upgrade 1 Motor with Alternate 1 Drive
H – Upgrade 2 Motor with Alternate 3 Drive
G – Upgrade 2 Motor with Alternate 2 Drive
F – Upgra
de 2 Motor with Alternate1 Drive
J – Standard Motor with Alternate 1 Drive, Flooded Condenser
M – Upgrade 1 Motor with Alternate 3 Drive, Flooded Condenser
L – Upgrade 1 Motor with Alternate 2 Drive, Flooded Condenser
K – Upgrade 1 Motor with Alternate 1 Drive, Flooded Condenser
Q – Upgrade 2 Motor with Alternate 3 Drive, Flooded Condenser
P – Upgrade 2 Motor with Alternate 2 Drive, Flooded Condenser
N – Upgrade 2 Motor with Alternate1 Drive, Flooded Condenser
* Includes interconnecting kit and electrical box. †Not available with splitable units.
a50-8546
Fig. 1 — Model Number Nomenclature
2
DETAIL A
CLEARANCE HOLE FOR
3/8" HANGING ROD
TYP 8 PLS
AIR
IN
COIL
ACCESS
FRONT
TOP
RIGHT
REAR LEFT
RETURN
AIR
SUPPLY
AIR
AIR
OUT
MOTOR
ACCESS
ELECT
BOX
ACCESS
BLOWER
ACCESS
EVAP
SECTION
COND
SECTION
ISOMETRIC VIEW
MOTOR
ACCESS
DETAIL "A"
ELECTRICAL
CONNECTIONS
TYP
CONDENSATE DRAIN
7/8" OD
FILTER
ACCESS
COMPRESSOR
ACCESS
QUICK
CONNECT
ACCESS
RA
LEFT
RIGHT
REAR
FRONT
26 IN. SERVICE
CLEARANCE
36 IN. SERVICE
CLEARANCE
31
90
6 7/16
13 5/8
34 3/4
1 3/8
9 5/16
12 3/8
60
24
3 3/4
3 13/16
33
2
28
64 1/2
6 1/8
18 3/4
1 3/4
16 1/8
48
42
2 1/4
3 1/2
62
1 15/16
38 1/8
3 7/8
44 1/8
1
1
1
A
B
C
DEG
FH
OSA
OPERATING WEIGHT DISTRIBUTION
UNIT
50AH
WEIGHT OF CORNER (lb)
ABCDEFGH
024 8711188 113 143 136 105 100
036 8711189 114 144 138 106 101
048 91 116 92 118 152 145 111 106
060 91 117 93 119 153 146 112 107
Fig. 2 — Unit Dimensions — 50AH024-060 Standard Units
NOTE: Dimensions are in inches.
a50-8547
LEGEND
OSA Outside Supply Air
RA Return Air
3
64 1/2
6 1/8
183/4
1 3/4
16 1/
8
1 1/2
3 13/16
1 15/16
44 1/8
3 7/8
38 1/8
6 1/16
24 3/4
38 1/2
5 15/16
3 1/4
1/4
5 7/
8
13 5/8
9 5/16
12 3/
8
6 7/16
2 1/4
5 7/8
12
Fig. 3 — Unit Dimensions — 50AH024-060 Units with Factory-Installed Air-Side Economizer
a50-8548
NOTES:
1. Dimensions are in inches.
2. Economizer weight is 180 lb.
LEGEND
OSA Outside Supply Air
RA Return Air
4
DETAIL A
CLEARANCE HOLE FOR
3/8" HANGING ROD
TYP 8 PLS
DETAIL "A"
AIR
IN
MOTOR
ACC
ELECT
BOX
ACCESS
COIL
ACCESS
COMPRESSOR
ACCESS
FILTER
ACCESS
CONDENSATE DRAIN
7/8" OD
FRONT
TOP
RIGHT
REAR LEFT
RETURN
AIR
SUPPLY
AIR
AIR
OUT
MOTOR
ACCESS
ELECT
BOX
ACCESS
BLOWER
ACCESS
QUICK
CONNECT
ACCESS
EVAP
SECTION
COND
SECTION
ELECTRICAL
CONNECTIONS
TYP
ISOMETRIC VIEW
21 7/16
22 1/8
18 15/16
10 7/8
32
112
25
3 5/8
39
1 1/4
16 1/16
6 7/16
18 3/4
6
70 1/2
29
653
2
2 1/4
3 1/2
47
65
72 1/2
1 15/16
43 1/8
3 7/8
61 1/8
75
26 IN. SERVICE
CLEARANCE
36 IN. SERVICE
CLEARANCE
36 IN. SERVICE
CLEARANCE
1
1
1
A
B
C
DEG
F
H
OSA
RA
REAR
RIGHT
LEFT
FRONT
OPERATING WEIGHT DISTRIBUTION
UNIT
50AH
WEIGHT OF CORNER (lb)
ABCDEFGH
072 125 128 149 152 126 128 188 192
096 126 129 149 153 139 142 208 212
NOTE: Dimensions are in inches.
a50-8549
Fig. 4 — Unit Dimensions — 50AH072,096 Standard Units
LEGEND
OSA Outside Supply Air
RA Return Air
5
13 7/16
16 1/16
6 7/16
18 3/4
6 5/8
70 1/2
5 7/8
22 1/8 21 7/16
18 15/16
10 7/8
3 1/4
5 15/16
1 1/2
72 1/2
1 15/16 61 1/8
3 7/8
43 1/8
6 1/16
42 1/2
29 3/4
12
NOTES:
1. Dimensions are in inches.
2. Economizer weight is 200 lbs.
a50-8550
Fig. 5 — Unit Dimensions — 50AH072,096 Units with Factory-Installed Air-Side Economizer
LEGEND
OSA Outside Supply Air
RA Return Air
6
Table 1 — Physical Data
Fig. 6 — Rigging Details
CENTER OF GRAVITY
NOTE: Fasten threaded rods through holes in end frames as shown. Use 4 rods on each side of unit for a total of 8.
UNIT 50AH
DIMENSIONS (in.)
AB
024 29.0 25.6 036 28.8 26.0 048 29.0 27.0 060 28.8 26.8 072 59.3 31.2 096 60.0 31.5
CAUTION
All panels must be in place when rigging.
UNIT 50AH 024 036 048 OPERATING WEIGHT (lb)
Base Unit 903 910 952
Evaporator/Condenser Sections 399/484401/489 417/515 SHIPPING WEIGHT (lb)* 1036 1043 1085 REFRIGERANT TYPE R-410A
Operating Charge (lb-oz)† 4-5 4-5 8-8 COMPRESSOR — TYPE Scroll
Quantity...Model 1...ZP20K5E 1...ZP31K5E 1...ZP38K5E
Oil (oz) 25 25 42
HPS Setting (psig)
Cutout 650 ± 7 Reset Manual Reset
LPS Setting (psig)
Cutout 75 ± 7 Reset 100 ± 7
CONDENSATE DRAIN CONNECTION
Size (in.)...Type CONDENSER COIL Copper Tubes — Aluminum Fins
Size (L x H) (in.) 40 x 30 40 x 30 90 x 30
Number of Rows...Fins/in. 4...14 4...14 2...12 CONDENSER FAN Centrifugal — Belt Drive
Nominal Cfm 1700 2000 2500
Blower Size (in.) 15 x15 15 x 15 15 x 15
Motor Hp (Rpm) Standard Motor 0.33 (1725) 0.33 (1725) Upgrade 1 Motor —— Upgrade 2 Motor ——
EVAPORATOR COIL Copper Tubes — Aluminum Fins
Size (L x H) (in.) 32 x 16 32 x 16 32 x 26
Number of Rows...Fins/in. 3...12 3...12 3...14 EVAPORATOR AIR FAN Centrifugal — Belt Drive
Nominal Cfm 800 1200 1600
Blower Size (in.) 12 x 9 12 x 9 12 x 9
Motor Hp (Rpm) Standard Motor 0.25 (1725) 0.33 (1725) Upgrade 1 Motor 0.33 (1725) 0.50 (1725) Upgrade 2 Motor 0.50 (1725) 0.75 (1725) Upgrade 3 Motor 1.00 (1725)
INDOOR-AIR FILTERS Factory-Supplied Disposable Type
Number...Size (in.) 2...18 x 24 x 1 2...18 x 24 x 1 2...18 x 24 x 1 INTERCONNECTING TUBING SIZE
Suction (Qty...in.) 1...
Liquid (Qty...in.)
LEGEND
HPS — High-Pressure Switch LPS — Low-Pressure Switch
*Shipping weights include base unit plus packaging. †If components are to be split, additional refrigerant will be needed.
5
/
8
3
/
1...
8
NOTE: If components are to be split, the maximum length of refrigerant tubing to be used is 50 equivalent ft, assuming components will be installed in same horizontal plane. If components are not to be installed in same horizontal plane, contact your Carrier representative for more information. For additional piping information, refer to Carrier System Design Manual, Part 3.
7
/8...OD
0.33 (1725)
0.50 (1725)
0.75 (1725)
0.33 (1725)
0.50 (1725)
0.75 (1725)
1.00 (1725)
1...5/
1...3/
8
8
1...7/
1...3/
8
8
7
Table 1 — Physical Data (cont)
UNIT 50AH 060 072 096 OPERATING WEIGHT (lb)
Base Unit 960 1214 1283
Evaporator/Condenser Sections 421/519 554/634 556/701 SHIPPING WEIGHT (lb)* 1093 1647 1716 REFRIGERANT TYPE R-410A
Operating Charge (lb-oz)† 8-8 6-6 6-6 COMPRESSOR — TYPE Scroll
Quantity...Model 1...ZPKP51K5E 2...ZP31K5E 2...ZP38K5E
Oil (oz) 42 25 42
HPS Setting (psig)
Cutout 650 ± 7 Reset Manual Reset
LPS Setting (psig)
Cutout 75 ± 7 Reset 100 ± 7
CONDENSATE DRAIN CONNECTION
Size (in.)...Type CONDENSER COIL Copper Tubes — Aluminum Fins
Size (L x H) (in.) 90 x 30 40 x 30 (2 coils) 40 x 30 (2 coils)
Number of Rows...Fins/in. 2...12 2...20 2...20 CONDENSER FAN Centrifugal — Belt Drive
Nominal Cfm 3000 5200 6400
Blower Size (in.) 15 x 15 18 x 18 18 x 18
Motor Hp (Rpm) Standard Motor 0.33 (1725) 1.00 (1725) Upgrade 1 Motor 0.50 (1725) 1.50 (1725) Upgrade 2 Motor 0.75 (1725)
EVAPORATOR COIL Copper Tubes — Aluminum Fins
Size (L x H) (in.) 32 x 26 46 x 28 46 x 28
Number of Rows...Fins/in. 3...14 3...14 3...14 EVAPORATOR AIR FAN Centrifugal — Belt Drive
Nominal Cfm 2000 2400 3200
Blower Size (in.) 12 x 9 15 x 15 15 x 15
Motor Hp (Rpm) Standard Motor 0.33 (1725) 0.50 (1725) Upgrade 1 Motor 0.50 (1725) 0.75 (1725) Upgrade 2 Motor 0.75 (1725) 1.00 (1725) Upgrade 3 Motor 1.00 (1725) 1.50 (1725)
INDOOR-AIR FILTERS Factory-Supplied Disposable Type
Number...Size (in.) 2...18 x 24 x 1 2...20 x 25 x 1 2...20 x 25 x 1 INTERCONNECTING TUBING SIZE
Suction (Qty...in.) 1...
Liquid (Qty...in.)
LEGEND
HPS — High-Pressure Switch LPS — Low-Pressure Switch
*Shipping weights include base unit plus packaging.
†If components are to be split, additional refrigerant will be needed.
7
/
8
3
/
1...
8
NOTE: If components are to be split, the maximum length of refrigerant tubing to be used is 50 equivalent ft, assuming components will be installed in same horizontal plane. If components are not to be installed in same horizontal plane, contact your Carrier representative for more information. For additional piping information, refer to Carrier System Design Manual, Part 3.
7
/8...OD
1...5/
1...3/
1.50 (1725)
2.00 (1725)
3.00 (1725)
0.75 (1725)
1.00 (1725)
1.50 (1725)
2.00 (1725)
8 8
1...7/
1...7/
8 8
Step 4 — Rig and Place Unit — Move and store unit
in horizontal position. Provide space around unit for service, filter access, ductwork, and overhead clearance as indicated in Fig. 2-5.
Using suitable hydraulic lift source, raise unit up to meet
bottom of the 8 threaded rods suspended from ceiling (12 rods for units with air-side economizer). Center unit so that the 8 or 12 threaded rods can be easily inserted into the factory-drilled holes at each end. Refer to Fig. 6 for rigging details.
Apply washers and locknuts on ends of each of the 8 or 12
rods.
Tighten locknuts sufficiently so that unit weight is support-
ed entirely by the 8 or 12 rods. Level unit within the space by adjusting locknuts.
IMPORTANT: Unit must be level to operate properly.
NOTE: For split systems, 8 (or 12) suspension rods are required (4 for each section and 4 for economizer if required). Refer to Splitting Systems section below.
Step 5 — Make Condensate Piping Connec­tions —
nection is provided for the evaporator section.
One 7/8-in. OD pipe thread condensate drain con-
Step 6 — Install Ductwork — Use flexible ductwork
to attach duct to unit and to help control transmission of vibra­tions to building structures. Attach ductwork to the return and supply ends of both coils.
If unit is located with condenser close to outside of building, install a field-supplied rainhood. Hood intake dimensions should be same as condenser return-air dimensions. In addi­tion, install a triple-layer bird screen over rainhood intake to eliminate possibility of insects, birds, water, or debris from entering unit. Ensure hood and/or louvers are installed correct­ly to avoid condenser air recirculation.
Step 7 — Split Systems (Factory Option, if Required) — The Roomtop
2 sections, if desired, with condensing section mounted remotely horizontally. The unit must be ordered with the “Splittable” cabinet type as shown in the unit model number nomenclature. See Fig. 1. All splittable units come with the interconnecting tubing kit.
Sections installed in the same horizontal plane may be sepa­rated by up to 50 equivalent ft of tubing. Use type L copper or better.
8
®
50AH units may be split into
Condensing section must be located in same plane as, or
SELF-SEALING COUPLING (FEMALE HALF)
SELF-SEALING COUPLING (MALE HALF)
SELF-SEALING FLANGE
SCREWS
Fig. 7 — Self Sealing Coupling
a50-8551
A — Male self-sealing fittings B — Refrigerant piping between sections C — Female self-sealing fittings D — Schrader fittings
Fig. 8 — Tubing Installation
a50-8552
above, evaporator section to maintain the liquid refrigerant seal at the expansion device. This permits expansion device to feed liquid refrigerant to evaporator coil properly. To split sections (some of the following steps may be eliminated depending on particular application):
1. Disconnect all electrical power to unit.
2. Remove the 10 size 10 drive screws that hold on the top tie strap.
3. Remove the 8 size
3
/8-in. drive bolts that hold on each
side angle.
4. Control panel access panels are held on with 2 size 10 drive screws for each panel. A standard 50AH024-060 unit has one control panel located in the evaporator sec­tion. A standard 50AH072 or 096 unit has a control panel in both the evaporator and condenser sections.
5. Units have resealable fittings. Do not cut refrigerant pip­ing. See Interconnecting Refrigerant Tubing section be­low for procedure on installing tubing.
6. Install evaporator and condensing sections in desired locations.
7. Use sufficient length of refrigerant piping to reconnect piping cut in previous step. Refer to Carrier System Design Manual, Part 3, for additional piping data.
8. Recharge unit with R-410A. See Refrigerant Charge sec­tion on page 18 for more information.
After splitting sections, additional refrigerant must be added to system to ensure proper refrigerant charge. The amount of refrigerant to be added depends on length of tubing added to system and operating temperatures of system. Refer to Carrier System Design Manual, Chapter 3. Allow unit to operate at least 10 minutes before adjusting refrigerant charge.
Since standard roomtop unit has negligible line losses, split­ting the system can increase line loss and decrease system capacity. Capacity reduction can be determined by referring to Carrier System Design Manual.
INTERCONNECTING REFRIGERANT TUBING — The interconnecting tubing kit comes with all factory-optional split­table units. After the separated sections have been installed, the interconnecting tubing can be run, using the self-sealing cou­plings supplied in the interconnect tubing kit (see Fig. 7 and 8).
Perform the following procedure:
1. For condensing section, hand thread the female halves of the self-sealing couplings (supplied with the interconnect tubing kit) onto the male couplings (factory supplied and installed on the condensing section). Turn union nut ap­proximately 1 to 1
1
/2 turns. This is to make sure that the interconnecting tubing will be routed and brazed with the self-sealing couplings in their final proper location, so that there will be no difficulty when the final coupling as­sembly is made.
2. For evaporator section, hand thread the male halves of the self-sealing couplings (supplied with the interconnect tubing kit) onto the female couplings (factory supplied and installed on the evaporating section). Turn union nut approximately 1 to 1
1
/2 turns. This is to make sure that the interconnecting tubing will be routed and brazed with the self-sealing couplings in their final proper location, so that there will be no difficulty when the final coupling as­sembly is made.
3. Run the interconnecting tubing required. NOTE: Installations may be made with up to 50 ft equiv-
alent line lengths by installing the recommended tube siz­es and adding the necessary refrigerant. For equivalent line lengths greater than 50 ft, contact Carrier for line siz­ing and additional accesories required.
IMPORTANT: On units with more than one refrig­erant circuit, be careful not to intermix lines of the various circuits. If the connections were labeled before disconnecting the couplings, this should not be a problem. Half couplings may be removed to make brazing to the interconnecting tubing more convenient.
D
B
B
C
D
C
A
CONDENSING SECTION
A
C
EVAPORATOR SECTION
C
D
A
D
A
For dual circuits, 2 kits are supplied. It is recommended that some refrigerant oil be placed on the coupling threads to facili­tate threading.
CAUTION
When brazing tubing to the self-sealing couplings, be sure to use a wet rag, running water bath or chill blocks on the quick-connects to prevent overheating the valves and dam­aging the seals
4. The interconnect tubing kit contains a sufficient number of Schrader access valves to permit installation of one in each end of both the liquid and suction lines of the field­supplied tubing. Each interconnecting line (suction, liq­uid, hot gas) must have one of the supplied Schrader ac­cess fittings installed into the field-supplied tubing, how­ever, for short lengths of tubing, only one Schrader in each line is necessary. Install the Schrader valve fittings into the tubing before brazing the couplings onto the ends
9
.
of the tubing. Use a
1
/4-in. hole to mount the valve. Clean and debur the tubing before doing any brazing to ensure that no chips or debris are left in the refrigerant circuit. Remove the Schrader valve cap and core before doing any brazing.
5. After brazing the tubing to the self-sealing coupling halves, evacuate each line to 500 microns. Check to make sure that each line holds a vacuum after removal of the vacuum pump (indicating no leaks). Add the appropriate charge of R-410A refrigerant using the Schrader valves. Refasten male halves to outer back panel of evaporator section with flanges and screws (if they were removed for brazing to tubing). Wipe off coupling seals and threaded surfaces with a clean cloth to prevent the inclusion of dirt or foreign material into the system. Lubricate rubber seal and metal seal in the male halves with refrigeration oil. Thread coupling halves together by hand to ensure proper mating of threads. Continue to handthread each half-cou­pling to its mating half until resistance is felt (approxi­mately 1
1
/2 to 13/4 turns). Complete the connection of the mating half-couplings with a wrench. The suction line couplings (size 12) will be totally engaged after an addi-
1
tional 5 will be totally engaged after an additional 4
/2 to 53/4 turns. The liquid line couplings (size 8)
1
/2 to 43/ turns. Use a backup wrench to prevent the couplings from twisting.
6. Refrigerant piping must be insulated in accordance with local codes and/or applicable ASHRAE standards. Insu­lation exposed to weather must be suitable for outdoor use. Provide protection from water and shielding from so­lar radiation as necessary.
7. Add refrigerant to the system to compensate for the addi­tional interconnecting tubing. The suction line should be pitched downward to the compressor, sloping approxi-
1
mately
/4-in. every 10 ft to facilitate oil return. P-traps (field supplied) are required for all suction line risers ev­ery 15 ft. When the evaporator is above the condensing section, an inverted P-trap should be incorporated as close as possible to the evaporator (this minimizes flood­back/oil slugging during the off cycle). If the condensing
Table 2A — Electrical Data — Standard Evaporator Motor with Standard Condenser Motor
section is more than 50 ft above the evaporator, consult Carrier for specific refrigeration components.
Step 8 — Make Electrical Connections — Con-
nect power wiring to junction box located on unit side near control box access panel. All wiring must comply with National Electrical Code (NEC) and all local code requirements.
Operating voltage to compressor must be within voltage range as indicated on unit nameplate. On 3-phase units, volt­ages between phases must be balanced within 2% and current must be balanced within 10%. Contact local power company for correction of improper voltage or phase imbalance. Unit failure as a result of operation on improper line voltage or ex­cessive phase imbalance constitutes abuse and may cause dam­age to electrical components. Such operation would invalidate any applicable Carrier warranty.
Install a fused disconnect per NEC. Refer to unit nameplate and Tables 2A-2L for fuse sizes and wire amperages for all units.
FIELD CONTROL WIRING — Install a Carrier-approved accessory thermostat assembly according to installation instructions provided by thermostat manufacturer. Locate
4
thermostat assembly on a solid wall in the conditioned space away from drafts to sense average room temperature.
Using thermostat cable or equivalent single leads of no. 18 AWG (American Wire Gage) colored wire, route cable or wire from the subbase terminals, up and through connector on unit side (below power lead junction box) and connect to low-volt­age terminal block inside the control box.
THERMOSTAT WIRE — Use 18 gage for 0 to 50-ft long wires and 16 gage for 51 to 75-ft wire lengths.
Step 9 — Adjust Fan Speed — Adjust fan speed to
meet jobsite conditions. Refer to Tables 3 and 4 to determine fan speed settings. See Service section of this document for instructions to adjust fan speed.
The evaporator and condenser fan motors on all units are belt drive.
VOLTAGE
UNIT
50AH
024 208/230-1 187 254 1 13.5 58.0
036
048
060
072*
096*
HACR — Heating, Air Conditioning, and Refrigeration Hp Horsepower FLA Full Load Amps LRA Locked Rotor Amps MOCP — Maximum Overcurrent Protection (HACR breaker) RLA Rated Load Amps
*Unit has two compressors.
V-PH
(60 Hz)
208/230-1 187 254 208/230-3 187 254 10.4 73.0
460-3 414 508 5.8 38.0
208/230-1 187 254 208/230-3 187 254 13.6 83.1
460-3 414 508 6.1 41.0
208/230-1 187 254 208/230-3 187 254 16.0 110.0
460-3 414 508 7.8 52.0
208/230-1 187 254 208/230-3 187 254 10.4 73.0
460-3 414 508 5.8 38.0
208/230-1 187 254 208/230-3 187 254 13.6 83.1
460-3 414 508 6.1 41.0
LEGEND
RANGE
Min Max QTY RLA LRA Hp FLA Hp FLA
COMPRESSOR
16.7 79.0
1
19.9 109.0
1
26.4 134
1
16.7 79.0
2
19.9 109.0
2
FAN MOTORS
Evaporator
(Standard)
1
/
1.25
4
1
/
3
1
/
3
1
/
3
1
/
3
1
/
3
1
/
3
1
/
3
1
/
3
1
/
3
1
/
2
1
/
2
1
/
2
3
/
4
3
/
4
3
/
4
Condenser
(Standard)
1
/
1.7 19.8 35
3
1.7
1.3
0.7
1.7
1.3
0.7
1.7
1.3
0.7
2.5 1 4.2 44.3 60
1.8 13.228.4 40
0.9 1 1.6 15.6 20
3.2 1 1/
2.4 1 1/
1.2 1 1/
1
/
1.7 24.3 40
3
1
/
1.3 15.6 25
3
1
/
0.7 8.6 15
3
1
/
1.7 28.3 50
3
1
/
1.3 19.6 35
3
1
/
0.7 8.9 15
3
1
/
1.7 36.4 65
3
1
/
1.3 22.6 40
3
1
/
0.7 11.1 20
3
6.5 54.5 75
2
4.8 37.8 50
2
2.4 17.3 25
2
POWER SUPPLY
Min Ckt
Amps
MOCP
Amps
10
Table 2B — Electrical Data — Upgrade 1 Evaporator Motor with Standard Condenser Motor
UNIT
50AH
V-PH
(60 Hz)
VOLTAGE
RANGE
COMPRESSOR
Min Max QTY RLA LRA Hp FLA Hp FLA
024 208/230-1 187 254 1 13.5 58.0
036
048
060
072*
096*
208/230-1 187 254 208/230-3 187 254 10.4 73.0
460-3 414 508 5.8 38.0
1
208/230-1 187 254 208/230-3 187 254 13.6 83.1
460-3 414 508 6.1 41.0
1
208/230-1 187 254 208/230-3 187 254 16.0 110.0
460-3 414 508 7.8 52.0
1
208/230-1 187 254 208/230-3 187 254 10.4 73.0
460-3 414 508 5.8 38.0
2
208/230-1 187 254 208/230-3 187 254 13.6 83.1 1 3.2 1
460-3 414 508 6.1 41.0 1 1.6 1
2
16.7 79.0
19.9 109.0
26.4 134.0
16.7 79.0
19.9 109.0 1 4.2 1
Table 2C — Electrical Data — Upgrade 2 Evaporator Motor with Standard Condenser Motor
VOLTAGE
UNIT
50AH
V-PH
(60 Hz)
RANGE
Min Max QTY RLA LRA Hp FLA Hp FLA
024 208/230-1 187 254 1 13.5 58.0
036
048
060
072*
096*
208/230-1 187 254 208/230-3 187 254 10.4 73.0
460-3 414 508 5.8 38.0
208/230-1 187 254 208/230-3 187 254 13.6 83.1
460-3 414 508 6.1 41.0
208/230-1 187 254 208/230-3 187 254 16.0 110.0
460-3 414 508 7.8 52.0
208/230-1 187 254 208/230-3 187 254 10.4 73.0 1 3.2 1 3.2 29.8 40
460-3 414 508 5.8 38.0 1 1.6 1 1.6 16.3 20
208/230-1 187 254 208/230-3 187 254 13.6 83.1 11/
460-3 414 508 6.1 41.0 11/
LEGEND
HACR — Heating, Air Conditioning, and Refrigeration Hp Horsepower FLA Full Load Amps LRA Locked Rotor Amps MOCP — Maximum Overcurrent Protection (HACR breaker) RLA Rated Load Amps
*Unit has two compressors.
COMPRESSOR
1
1
1
2
2
16.7 79.0
19.9 109.0
26.4 134.0
16.7 79.0 1 4.2 1 4.2 46.0 60
19.9 109.0 1
FAN MOTORS
Evaporator
(Upgrade 1)
1
/
1
/
1
/
1
/
1
/
1
/
1
/
1
/
1
/
1
/
3
/
3
/
3
/
1.7
3
2.5
2
1.8
2
0.9
2
2.5
2
1.8
2
0.9
2
2.5
2
1.8
2
0.9
2
3.2 1 4.2 45.0 60
4
2.4 1 3.2 29.0 40
4
1.2 1 1.6 15.9 20
4
FAN MOTORS
Evaporator
(Upgrade 2)
1
/
3
/
3
/
3
/
3
/
3
/
3
/
3
/
3
/
3
/
1
2
4 4 4
4 4 4
4 4 4
/
2 2 2
2.5
3.2
2.4
1.2
3.2
2.4
1.2
3.2
2.4
1.2
6.5 1 1/
4.8 1 1/
2.4 1 1/
Condenser
(Standard)
1
/
1.7 20.3 35
3
1
/
1.7 25.1 40
3
1
/
1.3 16.1 25
3
1
/
0.7 8.8 15
3
1
/
1.7 29.1 50
3
1
/
1.3 20.1 35
3
1
/
0.7 9.2 15
3
1
/
1.7 37.2 65
3
1
/
1.3 23.1 40
3
1
/
0.7 11.3 20
3
1
/
6.5 55.5 75
2
1
/
4.8 38.6 50
2
1
/
2.4 17.7 25
2
Condenser
(Standard)
1
/
1.7 21.1 35
3
1
/
1.7 25.8 40
3
1
/
1.3 16.7 25
3
1
/
0.7 9.1 15
3
1
/
1.7 29.8 50
3
1
/
1.3 20.7 35
3
1
/
0.7 9.5 15
3
1
/
1.7 37.9 65
3
1
/
1.3 23.7 40
3
1
/
0.7 11.6 20
3
6.5 57.880
2
4.8 40.2 55
2
2.4 18.5 25
2
POWER SUPPLY
Min Ckt
Amps
MOCP
Amps
POWER SUPPLY
Min Ckt
Amps
MOCP
Amps
11
Table 2D — Electrical Data — Upgrade 3 Evaporator Motor with Standard Condenser Motor
FAN MOTORS
Evaporator
(Upgrade 3)
Condenser
(Standard)
POWER SUPPLY
Min Ckt
Amps
UNIT
50AH
V-PH
(60 Hz)
VOLTAGE
RANGE
COMPRESSOR
Min Max QTY RLA LRA Hp FLA Hp FLA
024 208/230-1 187 254 1 N/A N/A N/A N/A N/A N/A N/A N/A
1
/
036
048
060
072*
096*
208/230-1 187 254 208/230-3 187 254 10.4 73.0 1 2.4
460-3 414 508 5.8 38.0 1 1.2
1
208/230-1 187 254 208/230-3 187 254 13.6 83.1 1 2.4
460-3 414 508 6.1 41.0 1 1.2
1
208/230-1 187 254 208/230-3 187 254 16.0 110.0 1 2.4
460-3 414 508 7.8 52.0 1 1.2
1
208/230-1 187 254 208/230-3 187 254 10.4 73.0 1
460-3 414 508 5.8 38.0 1
2
208/230-1 187 254 208/230-3 187 254 13.6 83.1 2 6.0 1
460-3 414 508 6.1 41.0 2 2.9 1
2
16.7 79.0 1 3.2
19.9 109.0 1 3.2
26.4 134.0 1 3.2
1
/
16.7 79.0 1
6.5 1 4.2 48.3 65
2
1
/
4.8 1 3.2 31.4 40
2
1
/
2.4 1 1.6 17.1 25
2
N/A N/A N/A N/A N/A N/A N/A N/A
1 1
1 1 1
1 1 1
1.7 25.8 40
3
/
1.3 16.7 25
3
/
0.7 9.1 15
3
/
1.7 29.8 50
3
/
1.3 20.7 35
3
/
0.7 9.5 15
3
/
1.7 37.9 65
3
/
1.3 23.7 40
3
/
0.7 11.6 20
3
1
/
4.8 41.4 55
2
1
/
2.4 19.0 25
2
Table 2E — Electrical Data — Standard Evaporator Motor with Upgrade 1 Condenser Motor
FAN MOTORS
Evaporator
(Standard)
1
/
3
1
/
3
1
/
3
1
/
3
1
/
3
1
/
3
1
/
2
1
/
2
1
/
2
3
/
4
3
/
4
Condenser
(Upgrade 1)
1.7
1.3
0.7
1.7
1.3
0.7
2.5 1 1/
1.8 1 1/
1 1 1
1 1 1
0.9 1 1/
/
2.5 29.1 50
2
/
1.8 20.1 35
2
/
0.9 9.2 15
2
/
2.5 37.2 65
2
/
1.8 23.1 40
2
/
0.9 11.3 20
2
6.5 46.6 65
2
4.8 30.0 40
2
2.4 16.4 20
2
POWER SUPPLY
Min Ckt
Amps
2.4 2 6.0 39.0 55
1.2 2 2.9 17.8 25
UNIT
50AH
V-PH
(60 Hz)
VOLTAGE
RANGE
COMPRESSOR
Min Max QTY RLA LRA Hp FLA Hp FLA
024 208/230-1 187 254 1 N/A N/A N/A N/A N/A N/A N/A N/A
036
208/230-1 187 254 208/230-3 187 254 N/A N/A N/A N/A N/A N/A N/A N/A
1
N/A N/A N/A N/A N/A N/A N/A N/A
460-3 414 508 N/A N/A N/A N/A N/A N/A N/A N/A
048
208/230-1 187 254 208/230-3 187 254 13.6 83.1
1
19.9 109.0
460-3 414 508 6.1 41.0
060
208/230-1 187 254 208/230-3 187 254 16.0 110.0
1
26.4 134.0
460-3 414 508 7.8 52.0
072*
208/230-1 187 254 208/230-3 187 254 10.4 73.0
2
16.7 79.0
460-3 414 508 5.8 38.0
096*
208/230-1 187 254 208/230-3 187 254 13.6 83.1
2
N/A N/A N/A N/A N/A N/A N/A N/A
460-3 414 508 6.1 41.0
LEGEND
HACR — Heating, Air Conditioning, and Refrigeration Hp Horsepower FLA Full Load Amps LRA Locked Rotor Amps MOCP — Maximum Overcurrent Protection (HACR breaker) RLA Rated Load Amps
*Unit has two compressors.
MOCP
Amps
MOCP
Amps
12
Table 2F — Electrical Data — Upgrade 1 Evaporator Motor with Upgrade 1 Condenser Motor
FAN MOTORS
Evaporator
(Upgrade 1)
Condenser
(Upgrade 1)
POWER SUPPLY
Min Ckt
Amps
UNIT
50AH
V-PH
(60 Hz)
VOLTAGE
RANGE
COMPRESSOR
Min Max QTY RLA LRA Hp FLA Hp FLA
024 208/230-1 187 254 1 N/A N/A N/A N/A N/A N/A N/A N/A
036
048
060
072*
096*
208/230-1 187 254 208/230-3 187 254 N/A N/A N/A N/A N/A N/A N/A N/A
460-3 414 508 N/A N/A N/A N/A N/A N/A N/A N/A
1
208/230-1 187 254 208/230-3 187 254 13.6 83.1
460-3 414 508 6.1 41.0
1
208/230-1 187 254 208/230-3 187 254 16.0 110.0
460-3 414 508 7.8 52.0
1
208/230-1 187 254 208/230-3 187 254 10.4 73.0
460-3 414 508 5.8 38.0
2
208/230-1 187 254 208/230-3 187 254 13.6 83.1 1 3.2 2 6.0 39.8 55
460-3 414 508 6.1 41.0 1 1.6 2 2.9 18.2 25
2
N/A N/A N/A N/A N/A N/A N/A N/A
19.9 109.0
26.4 134.0
16.7 79.0
1
/
1
/
1
/
1
/
1
/
1
/
3
/
3
/
3
/
2 2 2
2 2 2
4 4 4
2.5
1.8
0.9
2.5
1.8
0.9
3.2 1 1/
2.4 1 1/
1.2 1 1/
1
/
2.5 29.9 50
2
1
/
1.8 20.6 35
2
1
/
0.9 9.4 15
2
1
/
2.5 38.0 65
2
1
/
1.8 23.6 40
2
1
/
0.9 11.6 20
2
6.5 47.3 65
2
4.8 30.6 40
2
2.4 16.7 20
2
N/A N/A N/A N/A N/A N/A N/A N/A
Table 2G — Electrical Data — Upgrade 2 Evaporator Motor with Upgrade 1 Condenser Motor
FAN MOTORS
Evaporator
(Upgrade 2)
/ / /
/ / /
3.2
4
2.4
4
1.2
4
3.2
4
2.4
4
1.2
4
1
/
4.8 2 6.0 41.4 55
2
1
/
2.4 2 2.9 19.0 25
2
Condenser
(Upgrade 1)
1
/
2.5 30.6 50
2
1
/
1.8 21.2 35
2
1
/
0.9 9.7 15
2
1
/
2.5 38.7 65
2
1
/
1.8 24.2 40
2
1
/
0.9 11.9 20
2
1
/
6.5 48.3 65
2
4.8 31.4 40
2
1
/
2.4 17.1 25
2
POWER SUPPLY
Min Ckt
Amps
UNIT
50AH
V-PH
(60 Hz)
VOLTAGE
RANGE
COMPRESSOR
Min Max QTY RLA LRA Hp FLA Hp FLA
024 208/230-1 187 254 1 N/A N/A N/A N/A N/A N/A N/A N/A
036
208/230-1 187 254 208/230-3 187 254 N/A N/A N/A N/A N/A N/A N/A N/A
1
N/A N/A N/A N/A N/A N/A N/A N/A
460-3 414 508 N/A N/A N/A N/A N/A N/A N/A N/A
048
060
072*
208/230-1 187 254 208/230-3 187 254 13.6 83.1
1
19.9 109.0
460-3 414 508 6.1 41.0
208/230-1 187 254 208/230-3 187 254 16.0 110.0
1
26.4 134.0
460-3 414 508 7.8 52.0
208/230-1 187 254 208/230-3 187 254 10.4 73.0 1 3.2 1 1/
2
16.7 79.0 1 4.2 1
3 3 3
3 3 3
460-3 414 508 5.8 38.0 1 1.6 1
096*
208/230-1 187 254 208/230-3 187 254 13.6 83.1 1
2
N/A N/A N/A N/A N/A N/A N/A N/A
460-3 414 508 6.1 41.0 1
LEGEND
HACR — Heating, Air Conditioning, and Refrigeration Hp Horsepower FLA Full Load Amps LRA Locked Rotor Amps MOCP — Maximum Overcurrent Protection (HACR breaker) RLA Rated Load Amps
*Unit has two compressors.
MOCP
Amps
MOCP
Amps
13
Table 2H — Electrical Data — Upgrade 3 Evaporator Motor with Upgrade 1 Condenser Motor
FAN MOTORS
Evaporator
(Upgrade 3)
Condenser
(Upgrade 1)
POWER SUPPLY
Min Ckt
Amps
UNIT
50AH
V-PH
(60 Hz)
VOLTAGE
RANGE
COMPRESSOR
Min Max QTY RLA LRA Hp FLA Hp FLA
024 208/230-1 187 254 1 N/A N/A N/A N/A N/A N/A N/A N/A
036
048
060
072*
096*
208/230-1 187 254 208/230-3 187 254 N/A N/A N/A N/A N/A N/A N/A N/A
460-3 414 508 N/A N/A N/A N/A N/A N/A N/A N/A
1
208/230-1 187 254 208/230-3 187 254 13.6 83.1 1 2.4
460-3 414 508 6.1 41.0 1 1.2
1
208/230-1 187 254 208/230-3 187 254 16.0 110.0 1 2.4
460-3 414 508 7.8 52.0 1 1.2
1
208/230-1 187 254 208/230-3 187 254 10.4 73.0 1
460-3 414 508 5.8 38.0 1
2
208/230-1 187 254 208/230-3 187 254 13.6 83.1 2 6.0 2 6.0 42.6 55
460-3 414 508 6.1 41.0 2 2.9 2 2.9 19.5 25
2
N/A N/A N/A N/A N/A N/A N/A N/A
19.9 109.0 1 3.2
26.4 134.0 1 3.2
1
/
16.7 79.0 1
2
1
/
2
1
/
2
6.5 1 1/
4.8 1 1/
2.4 1 1/
1
/
2.5 30.6 50
2
1
/
1.8 21.2 35
2
1
/
0.9 9.7 15
2
1
/
2.5 38.7 65
2
1
/
1.8 24.2 40
2
1
/
0.9 11.9 20
2
6.5 50.6 65
2
4.8 33.0 45
2
2.4 17.9 25
2
N/A N/A N/A N/A N/A N/A N/A N/A
Table 2I — Electrical Data — Standard Evaporator Motor with Upgrade 2 Condenser Motor
FAN MOTORS
Evaporator
(Standard)
1
/
3
1
/
3
1
/
3
1
/
3
1
/
3
1
/
3
3
/
4
3
/
4
POWER SUPPLY
Min Ckt
Amps
1.7
1.3
0.7
1.7
1.3
0.7
Condenser
(Upgrade 2)
3
/
3.2 29.8 50
4
3
/
2.4 20.7 35
4
3
/
1.2 9.5 15
4
3
/
3.2 37.9 65
4
3
/
2.4 23.7 40
4
3
/
1.2 11.6 20
4
2.4 3 8.4 41.4 55
1.2 3 4.0 18.9 25
UNIT
50AH
V-PH
(60 Hz)
VOLTAGE
RANGE
COMPRESSOR
Min Max QTY RLA LRA Hp FLA Hp FLA
024 208/230-1 187 254 1 N/A N/A N/A N/A N/A N/A N/A N/A
036
208/230-1 187 254 208/230-3 187 254 N/A N/A N/A N/A N/A N/A N/A N/A
1
N/A N/A N/A N/A N/A N/A N/A N/A
460-3 414 508 N/A N/A N/A N/A N/A N/A N/A N/A
048
208/230-1 187 254 208/230-3 187 254 13.6 83.1
1
19.9 109.0
460-3 414 508 6.1 41.0
060
208/230-1 187 254 208/230-3 187 254 16.0 110.0
1
26.4 134.0
460-3 414 508 7.8 52.0
072*
208/230-1 187 254 208/230-3 187 254 N/A N/A N/A N/A N/A N/A N/A N/A
2
N/A N/A N/A N/A N/A N/A N/A N/A
460-3 414 508 N/A N/A N/A N/A N/A N/A N/A N/A
096*
208/230-1 187 254 208/230-3 187 254 13.6 83.1
2
N/A N/A N/A N/A N/A N/A N/A N/A
460-3 414 508 6.1 41.0
LEGEND
HACR — Heating, Air Conditioning, and Refrigeration Hp Horsepower FLA Full Load Amps LRA Locked Rotor Amps MOCP — Maximum Overcurrent Protection (HACR breaker) RLA Rated Load Amps
*Unit has two compressors.
MOCP
Amps
MOCP
Amps
14
Table 2J — Electrical Data — Upgrade 1 Evaporator Motor with Upgrade 2 Condenser Motor
FAN MOTORS
Evaporator
(Upgrade 1)
Condenser
(Upgrade 2)
POWER SUPPLY
Min Ckt
Amps
UNIT
50AH
V-PH
(60 Hz)
VOLTAGE
RANGE
COMPRESSOR
Min Max QTY RLA LRA Hp FLA Hp FLA
024 208/230-1 187 254 1 N/A N/A N/A N/A N/A N/A N/A N/A
036
048
060
072*
096*
208/230-1 187 254 208/230-3 187 254 N/A N/A N/A N/A N/A N/A N/A N/A
460-3 414 508 N/A N/A N/A N/A N/A N/A N/A N/A
1
208/230-1 187 254 208/230-3 187 254 13.6 83.1
460-3 414 508 6.1 41.0
1
208/230-1 187 254 208/230-3 187 254 16.0 110.0
460-3 414 508 7.8 52.0
1
208/230-1 187 254 208/230-3 187 254 N/A N/A N/A N/A N/A N/A N/A N/A
460-3 414 508 N/A N/A N/A N/A N/A N/A N/A N/A
2
208/230-1 187 254 208/230-3 187 254 13.6 83.1 1 3.2 3 8.4 42.2 55
460-3 414 508 6.1 41.0 1 1.6 3 4.0 19.3 25
2
N/A N/A N/A N/A N/A N/A N/A N/A
19.9 109.0
26.4 134.0
1
/
1
/
1
/
1
/
1
/
1
/
2.5
2
1.8
2
0.9
2
2.5
2
1.8
2
0.9
2
3
/
3.2 30.6 50
4
3
/
2.4 21.2 35
4
3
/
1.2 9.7 15
4
3
/
3.2 38.7 65
4
3
/
2.4 24.2 40
4
3
/
1.2 11.9 20
4
N/A N/A N/A N/A N/A N/A N/A N/A
N/A N/A N/A N/A N/A N/A N/A N/A
Table 2K — Electrical Data — Upgrade 2 Evaporator Motor with Upgrade 2 Condenser Motor
FAN MOTORS
Evaporator
(Upgrade 2)
/ / /
/ / /
3.2
4
2.4
4
1.2
4
3.2
4
2.4
4
1.2
4
1
/
4.8 3 8.4 43.8 55
2
1
/
2.4 3 4.0 20.1 25
2
Condenser
(Upgrade 2)
3
/
3.2 31.3 50
4
3
/
2.4 21.8 35
4
3
/
1.2 10.0 15
4
3
/
3.2 39.4 65
4
3
/
2.4 24.8 40
4
3
/
1.2 12.2 20
4
POWER SUPPLY
Min Ckt
Amps
UNIT
50AH
V-PH
(60 Hz)
VOLTAGE
RANGE
COMPRESSOR
Min Max QTY RLA LRA Hp FLA Hp FLA
024 208/230-1 187 254 1 N/A N/A N/A N/A N/A N/A N/A N/A
036
208/230-1 187 254 208/230-3 187 254 N/A N/A N/A N/A N/A N/A N/A N/A
1
N/A N/A N/A N/A N/A N/A N/A N/A
460-3 414 508 N/A N/A N/A N/A N/A N/A N/A N/A
048
060
072*
208/230-1 187 254 208/230-3 187 254 13.6 83.1
1
19.9 109.0
460-3 414 508 6.1 41.0
208/230-1 187 254 208/230-3 187 254 16.0 110.0
1
26.4 134.0
460-3 414 508 7.8 52.0
208/230-1 187 254 208/230-3 187 254 N/A N/A N/A N/A N/A N/A N/A N/A
2
N/A N/A N/A N/A N/A N/A N/A N/A
3 3 3
3 3 3
460-3 414 508 N/A N/A N/A N/A N/A N/A N/A N/A
096*
208/230-1 187 254 208/230-3 187 254 13.6 83.1 1
2
N/A N/A N/A N/A N/A N/A N/A N/A
460-3 414 508 6.1 41.0 1
LEGEND
HACR — Heating, Air Conditioning, and Refrigeration Hp Horsepower FLA Full Load Amps LRA Locked Rotor Amps MOCP — Maximum Overcurrent Protection (HACR breaker) RLA Rated Load Amps
*Unit has two compressors.
MOCP
Amps
MOCP
Amps
15
Table 2L — Electrical Data — Upgrade 3 Evaporator Motor with Upgrade 2 Condenser Motor
FAN MOTORS
Evaporator
(Upgrade 3)
Condenser
(Upgrade 2)
POWER SUPPLY
Min Ckt
Amps
UNIT
50AH
V-PH
(60 Hz)
VOLTAGE
RANGE
COMPRESSOR
Min Max QTY RLA LRA Hp FLA Hp FLA
024 208/230-1 187 254 1 N/A N/A N/A N/A N/A N/A N/A N/A
036
048
060
072*
096*
208/230-1 187 254 208/230-3 187 254 N/A N/A N/A N/A N/A N/A N/A N/A
460-3 414 508 N/A N/A N/A N/A N/A N/A N/A N/A
1
208/230-1 187 254 208/230-3 187 254 13.6 83.1 1 2.4
460-3 414 508 6.1 41.0 1 1.2
1
208/230-1 187 254 208/230-3 187 254 16.0 110.0 1 2.4
460-3 414 508 7.8 52.0 1 1.2
1
208/230-1 187 254 208/230-3 187 254 N/A N/A N/A N/A N/A N/A N/A N/A
460-3 414 508 N/A N/A N/A N/A N/A N/A N/A N/A
2
208/230-1 187 254 208/230-3 187 254 13.6 83.1 2 6.0 3 8.4 45.0 55
460-3 414 508 6.1 41.0 2 2.9 3 4.0 20.6 25
2
N/A N/A N/A N/A N/A N/A N/A N/A
19.9 109.0 1 3.2
26.4 134.0 1 3.2
3
/
3.2 31.3 50
4
3
/
2.4 21.8 35
4
3
/
1.2 10.0 15
4
3
/
3.2 39.4 65
4
3
/
2.4 24.8 40
4
3
/
1.2 12.2 20
4
N/A N/A N/A N/A N/A N/A N/A N/A
N/A N/A N/A N/A N/A N/A N/A N/A
LEGEND
HACR — Heating, Air Conditioning, and Refrigeration Hp Horsepower FLA Full Load Amps LRA Locked Rotor Amps MOCP — Maximum Overcurrent Protection (HACR breaker) RLA Rated Load Amps
*Unit has two compressors.
MOCP
Amps
UNIT SIZE
50AH
CFM
RpmBhpRpmBhpRpmBhpRpmBhpRpmBhpRpmBhp
900 509 0.11 632 0.14 739 0.19 833 0.24
024
800 495 0.07 623 0.12 733 0.17 829 0.22 915 0.28 700 470 0.06 604 0.10 717 0.14 814 0.19 901 0.25 1350 550 0.17 651 0.23 744 0.29 831 0.36
036
1200 526 0.14 635 0.19 734 0.25 825 0.31 908 0.38 1050 510 0.11 627 0.16 731 0.21 824 0.27 910 0.33 988 0.40 1800 607 0.29 685 0.36 760 0.43
048
1600 566 0.22 652 0.28 734 0.35 813 0.42 1400 537 0.17 632 0.23 722 0.29 806 0.35 886 0.42 2250 640 0.44
060
2000 588 0.32 670 0.40 1750 552 0.24 642 0.31 725 0.38 2700 461 0.36 543 0.47 619 0.60
072
2400 449 0.29 537 0.40 616 0.53 —————— 2100 435 0.24 529 0.34 611 0.47 683 0.61 ———— 3600 555 0.74 618 0.87
096
3200 514 0.66 584 0.80 652 0.81 2800 448 0.37 552 0.51 626 0.64 695 0.79
LEGEND NOTES:
Bhp Brake Horsepower
Table 3 — Evaporator-Fan Performance
EXTERNAL STATIC PRESSURE (in. wg)
0.2 0.4 0.6 0.8 1.0 1.2
919 0.30 997 0.37
993 0.34 979 0.31
912 0.43
986 0.45
832 0.50 902 0.58 ——
888 0.49 960 0.56
962 0.49
715 0.52 786 0.61——————
747 0.48 819 0.56 889 0.64
803 0.46 878 0.53 950 0.61 689 0.75
680 1.01——————
707 0.94 769 1.10
759 0.95 818 1.12
1. Refer to Table 1 for evaporator fan motor and drive information.
2. Upgrade 1 Static Motor is required for boldface values.
3. Upgrade 2 Static Motor is required for shaded values.
16
Table 4 — Condenser-Fan Performance
UNIT
SIZE
50AH
024 1700 247 0.07 255 0.07 262 0.08 269 0.08 277 0.08 2840.09 036 2000 276 0.11 2820.11289 0.12 295 0.12 301 0.12 307 0.13 048 2500 251 0.17 305 0.18 357 0.22 408 0.27 456 0.32 060 3000 287 0.22 334 0.28 378 0.33 421 0.38 072 5200 367 0.68 438 0.89 464 0.98 490 1.07 516 1.16 542 1.25 096 6400 448 1.26 524 1.59 546 1.70
Bhp Brake Horsepower
CFM
LEGEND NOTES:
0.0 0.1 0.2 0.3 0.4 0.5
RpmBhpRpmBhpRpmBhpRpmBhpRpmBhpRpmBhp
START-UP
Unit Preparation —
accordance with installation instructions and applicable codes.
Make sure unit has been installed in
Compressor Mounting — Compressors are internally
mounted on rubber-in-shear (RIS) isolators. Do not loosen or remove compressor holddown bolts.
EXTERNAL STATIC PRESSURE (in. wg)
568 1.81————
1. Refer to Table 1 for condenser fan motor and drive information.
2. Upgrade 1 Static Motor is required for boldface values.
3. Upgrade 2 Static Motor is required for shaded values.
Disconnect all power to the unit before performing mainte­nance or service. Electrical shock and personal injury could result.
501 0.37
464 0.43 505 0.49
SERVICE
WARNING
Internal Wiring — Check all electrical connections in
unit control boxes and tighten as required.
Refrigerant Service Valves — Each unit system has
2 Schrader-type service ports, one on the suction line and one on the compressor discharge line. Be sure that caps on the ports are tight.
Compressor Rotation — On 50AH036-096, 3-phase
units, it is important to be certain compressor is rotating in the proper direction. To determine whether or not compressor is rotating in the proper direction:
1. Connect service gages to suction and discharge pressure fittings.
2. Energize the compressor.
3. The suction pressure should drop and the discharge pres­sure should rise, as is normal on any start-up.
If the suction pressure does not drop and the discharge pres-
sure does not rise to normal levels:
1. Note that the condenser and evaporator fans may also be rotating in the wrong direction.
2. Turn off power to the unit and tag disconnect.
3. Reverse any two of the unit power leads.
4. Reapply power to the unit; remove tag.
5. Verify correct refrigerant pressures.
The suction and discharge pressure levels should move to
their normal start-up levels. NOTE: When the compressor is rotating in the wrong direc-
tion, the unit will sound louder than normal and will not provide cooling.
Cooling — To start unit, turn on main power supply. Set
system selector switch at COOL position and fan switch at AUTO. position. Adjust thermostat to a setting below room temperature. Compressor, condenser and evaporator motors start on closure of contactors.
TO SHUT OFF UNIT — Set system selector switch at OFF position or reset thermostat at a position above room temperature.
IMPORTANT: If repairs to refrigerant cycle compo­nents (e.g., compressor, filter drier, etc.) are required, recover all refrigerant from the system by using both high and low-pressure ports. Then remove base unit from the space.
Filters —
Filters are disposable and should be inspected and replaced at regular intervals monthly or as conditions require. They are located in front of the evaporator coil and may be re­moved by sliding them horizontally out to edge of unit. See Fig. 2-5. No tools are required for installation or removal of filters.
Condenser Coil — The condenser coil is accessible
through the side access panel on condenser section, or through side access panel on condenser section. Use a stiff brush when cleaning coil. Be careful not to bend aluminum fins.
Evaporator Coil — The evaporator coil is accessible for
cleaning through the side access panel on evaporator section. When necessary, wash coil with a commercial cleaner (Oakite
164) or dishwasher detergent using a pressurized spray canis­ter. Flush coil from return-air duct side and take care not to get
water in ductwork or unit insulation.
Condensate Drain — Clean and empty drain pan at
least once a year to prevent sludge build-up.
Lubrication — Lubrication of the condenser and evapora-
tor motors is not necessary since both are equipped with permanently lubricated bearings. Do not oil.
Unit Condenser Motor — All 50AH units contain
belt-driven adjustable-pulley fan systems. The unit fan motors are shipped with adjustable pulley at 4 turns open.
Blower Wheel Servicing — In-space servicing is rec-
ommended for the evaporator and condenser blowers. Both are removed by loosening and removing the 2 screws (sizes 024-
060) or 4 screws (sizes 072 and 096) that hold them in place. In both cases, the entire assembly is then moved outside of the base unit. Once outside, the blower wheel and condenser shaft bearings and/or evaporator motor can be serviced.
17
Blower Belt Adjustment — Inspect blower belt for
Fig. 9 — Sheave Alignment
a50-7135tf
BELT SPAN
LB FORCE
DEFLECTION
Fig. 10 — Fan Belt Tension
a50-7136ef
wear, proper belt tension, and pulley alignment as conditions require or at the beginning of each heating and air conditioning season.
Make sure that fan shafts and motor shafts are parallel and level. The most common causes of misalignment are nonparal­lel shafts and improperly located sheaves. Where shafts are not parallel, belts on one side are drawn tighter and pull more than their share of the load. As a result, these belts wear out faster, requiring the entire set to be replaced before it has given maxi­mum service. If misalignment is in the sheave, belts enter and leave the grooves at an angle, causing excessive belt and sheave wear.
SHAFT ALIGNMENT — Check shaft alignment by measur­ing the distance between the shafts at 3 or more locations. If the distances are equal, then the shafts are parallel.
SHEAVE ALIGNMENT
1. To check the location of the fixed sheaves on the shafts, use a straightedge or a piece of string. If the sheaves are properly aligned, the string will touch them at the points indicated by the arrows in Fig. 9. Rotate each sheave a half revolution to determine whether the sheave is wob­bly or the drive shaft is bent. Correct any misalignment.
2. With sheaves aligned, tighten cap screws evenly and progressively.
NOTE: There should be a the mating part hub and the bushing flange. If the gap is closed, the bushing is probably the wrong size.
3. With taper-lock bushed hubs, be sure the bushing bolts are tightened evenly to prevent side-to-side pulley wob­ble. Check by rotating sheaves and rechecking sheave alignment. When substituting field-supplied sheaves for factory-supplied sheaves, only the motor sheave should be changed.
BELT TENSION ADJUSTMENT — Using a gage, apply 4 lb of force to the center of the belt and adjust the tension until a deflection of
1
/64-in. is achieved for every inch of shaft center
distance. See Fig. 10.
Ideal belt tension is the lowest value under which belt slip
will not occur at peak load conditions.
1
/8-in. to 1/4-in. gap between
Refrigerant Charge — Unit is shipped fully charged.
Amount of refrigerant charge is listed on unit nameplate (also refer to Table 1). Refer to Carrier GTAC II; Module 5; Charg­ing, Recovery, Recycling, and Reclamation manual.
Unit panels must be in place when unit is operating during charging procedure. Unit must operate for at least 10 minutes before adjusting charge. Use standard evacuating techniques. After evacuating system, weigh in the specified amount of re­frigerant. (Refer to Table 1.)
18
Copyright 2010 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53500057-01 Printed in U.S.A. Form 50AH-14SI Pg 20 5-10 Replaces: 50AH-12SI
Loading...