• quiet and efficient scroll compressor
technology
Features/Benefits
All in one package — high
cooling efficiency,
installation convenience,
ease of accessibility for timesaving maintenance.
Space and cost saving design
Model 50AH is specifically designed to
provide the building owner with truly outof-sight cooling, because it installs inside
the ceiling. That’s why we call it the Carrier ROOMTOP® unit. The compact design and low silhouette enable it to fit
easily and securely above the conditioned
space. Single-package construction
makes it easy to install with minimal time
and cost.
Application flexibility
If desired for particular applications, the
unit can also be installed as a split system
with the condenser section mounted horizontally. Centrifugal fans permit ducting
of both evaporator and condenser air.
Quiet operation
Commercial end users appreciate the extra comfort of quiet operation. Carrier
engineers met the challenge by specifying heavy insulation, vibration-resistant
construction and operating components
that function at low noise levels, all of
which keep system sound at a minimum
level.
Easy maintenance
When it comes to maintenance, the
50AH rates high in accessibility. Indoor
Copyright 2002 Carrier CorporationForm 50AH-6PD
Page 2
location is ideal for the maintenance
technician, and five access panels, easily
removed, provide quick and convenient
access to all components when needed.
As an added plus, all required service/
maintenance access can be from one
side allowing the unit to be located
against a wall or ceiling plenum obstruction, an obvious space-saving idea.
Carrier quality and reliability
The Carrier 50AH ROOMTOP® units
have much to offer the cost- and
efficiency-conscious commercial owner.
Every unit is thoroughly run tested at the
factory and equipped with safety controls
designed to monitor and protect over the
life of the unit.
Scroll compressors are designed for high
efficiency and are internally spring
mounted to minimize vibration noise.
Each compressor is hermetically sealed
against contamination to promote longer
life and dependable operation. Scroll
compressors are standard on all units.
Quality Assurance
®
I
S
O
9
0
0
1
:
2
5
2
3
2
A
#
0
0
0
Model number nomenclature
50AH–048–M–541XX
Model Designation –
50AH Horizontal,
Indoor Single-Package
Cooling Unit
Nominal Tons
024 – 2
036 – 3
Indoor Fan Motor
– – Standard Motor
M – 1.5 hp Optional Motor
*FIOP — Factory-Installed option, contact your Carrier representative for details.
048–4
060–5
FIOP*
Packaging
1 – Domestic
2 – Export
Design Revision
Voltage
3 – 230-1-60
5 – 208/230-3-60
6 – 460-3-60
ARI* capacity ratings
UNIT
50AH
024230-1-602.5624,800800——10.50†78
036
048
060
dB— Decibels
EER — Energy Efficiency Ratio
SEER — Seasonal Energy Efficiency Ratio
TDR — Time-Delay Relay2. EER =
*Air-conditioning and Refrigeration Institute.
†TDR is standard.
V-P H- Hz
230-1-60
460-3-608.40——
230-1-60
460-3-608.80——
230-1-60
460-3-608.50——
LEGEND
TOTAL
kW
4.336,0001200
5.6349,5001600
6.958,5002000
NET TOTAL
COOLING CAP. (Btuh)
NOTES:
1. Ratings are at zero condenser air static and rated in
accordance with ARI Standard 210.
NET CAPACITY (Btuh)
TOTAL WATTS
NOMINAL
CFM
EERSEER
—10.0010.00
—— 10.00†
—9.7010.00
SEER
(with TDR)
SOUND RATING
(dB)
82208/230-3-608.40——
82208/230-3-608.80——
82208/230-3-608.50——
2
Page 3
Physical data
UNIT 50AH024036048060
SHIPPING WEIGHT (lb)*560590690700
OPERATING WEIGHT (lb)
Base Unit, Evaporator/Condenser Section450, 193/256480, 206/274580, 250/330590, 254/336
*Shipping weights include base unit plus packaging.
†If components are to be split, additional refrigerant will be needed.
**Two-speed motor.
††Use Type L copper only.
LEGEND
1
1
/6(850)
1
3
/
2
Not
Available
/
2
/
8
3
/
4
1
/2(1075)
1
/
2
3
/
8
NOTE: If components are to be split, the maximum length of refrigerant tubing to be
used is 50 equivalent ft, assuming components will be installed in same horizontal plane.
If components are not to be installed in same hor izontal plane, contact your Carrier representative for more information. For additional piping information, refer to Carrier
System Design Manual, Part 3.
3
/4...FPT
11
3
/4(1050)
Centrifugal Belt Drive
1
/
2
1
/
2
3
/
8
1
/
2
1
/
2
3
/
8
NOTE: Fasten threaded rods through holes in end frames. Use 2 rods
on each side of unit for a total of 4.
Thermostat and subbase — Attractive wall-mounted
24-v accessory provides precise temperature control.
Automatic and Manual changeover models available. A
thermostat subbase is available that works with CycleLOC™ circuitry. If a safety device trips, compressor locks
out and subbase warning light (LK OUT) alerts occupant.
Three models available: One stage cool/two stage heat;
two stage cool/two stage heat; one stage cool/one stage
heat.
Time Guard® II circuit (standard on single-phase
units) — Time Guard II device prevents short cycling of
compressor if thermostat is rapidly changed; automatically
prevents compressor from restarting for 5 minutes after
shutdown.
Electric heaters — A wide range of models is available
from 5 to 30 kW, 208-, 240- and 480-v, single- and 3-ph
units. The heaters mount easily on 50AH discharge opening. The heater control box is accessible from the bottom
of heater.
Condensate pump — The condensate pump is used
when the distance and slope to the nearest drain is far
enough to prevent the natural drainage of unit. The pump
is mounted remotely from the unit and includes a signal
light (field-installed) which illuminates when the reservoir
rises beyond a certain level. The unit automatically shuts
down when this reservoir level is achieved.
Head pressure control damper — This accessory is
duct mounted and allows unit to mechanically cool down to
0° F.
Damper dimensions fit 024, 036 sizes.
NOTE: For use with 048 and 060 size units, ductwork
from unit to damper must be reduced in size to fit damper
dimensions.
Vibration isolators — Package of four isolators used for
dampening any unit vibration so that vibrating sounds are
not transmitted to building structure. Isolators are spring,
ceiling type.
of 0.06 in. wg) . . . . . . . . . . . . . . .0.20 in. wg
II Select unit based upon required cooling
capacity.
Enter cooling capacity table at temperature of air
entering condenser of 95 F. The 50AH036 unit at
1200 cfm and 67 F ewb will provide a Total
Capacity (TC) of 44,200 Btuh and a Sensible Heat
Capacity (SHC) of 31,300 Btuh. Since the entering
air is 80 F edb, an SHC correction is not required.
III Determine evaporator fan performance.
Enter Evaporator Fan Performance table at
1200 cfm and 50AH036 data. The external static
pressure shown (0.23 in. wg) will exceed the
0.20 in. wg required. The fan motor will require
0.52 kW.
IV Determine condenser fan performance and
motor pulley setting requirements.
Enter Condenser Fan Performance table at
the selected cfm and required static pressure of
0.50 in. wg. The fan motor will require 0.73 kW
and the motor pulley should be set at 2 turns open
at 1350 cfm of condenser air required.
NOTE: Unit 50AH024 contains a direct-drive condenser fan assembly.
ESP — External Static Pressure (in. wg)
kW — Total Fan Motor Power Input (kilowatts)
*Standard direct drive indoor (evaporator) fan motor (IFM). For optional
belt drive IFM performance, see table on page 8.
NOTES:
1. Above fan performance is based on wet coil and deducted casing
losses, and clean factory-installed permanent cleanable filter.
024036048*060*
LEGEND
2. Evaporator fans are direct drive (except 048, 060 special order
evaporator-fan motor option). Refer to Belt Drive Evaporator Fan
Performance table on page 8.
3. Interpolation is permissible, do not extrapolate.
4. For units installed with accessory electric heaters, see Electric
Heater Static Pressure Drop table for additional performance losses.
7
Page 8
Performance data (cont)
BELT DRIVE EVAPORATOR FAN PERFORMANCE
(Special Order Only, Pricing and
ordering on related price pages.)
8. Care should be taken when hoods and/or louvers are installed to
avoid condenser air recirculation.
Page 9
ELECTRIC HEATER STATIC PRESSURE DROP (in. wg)
ELECTRIC HEATER
UNIT 88EN
0500CA01
0075CA01510.03.06.10.16—————
0115CA01620
0075EA013201150EA01720
0100EA01
0150EA011240
0200EA011350
0300EA011220
0300CA011220
0100FA011130
0150FA011360
0200FA011350
0300FA011270
NOTE: Above electric heaters are
listed for use with optional high-static evaporator-fan motor (048, 060 units only).
UNIT
50AH
024, 036
1-stage
heat
048, 060
2-stage
heat
MIN
CFM
400.02.04.06.10—————
970
not
UL (Underwriters’ Laboratories) or CSA (Canadian Standards Association)
6008001000120014001600180020002200
.04.08.13.19—————
———.04.06.08.12.15.17
———.08.11.14.18.22.26
———.04.06.08.12.15.17
———.08.11.14.18.22.26
UNIT CFM
Controls
Operating sequence
Cooling — Thermostat calls for cooling. Indoor (evapora-
tor) fan relay is energized and starts evaporator fan. Compressor contactor is energized to start compressor and
condenser fan (up to a 5-minute delay on single-phase
units). When room thermostat is satisfied, the evaporator
fan, compressor, and condenser fan shut off.
Continuous fan operation — The thermostat can be
set for continuous operation by setting the fan switch to
ON.
Electrical data
UNIT
50AH
024230-120725411.456.171.10.503.4019.025
036
048
048*
060
060*
HACR — Heating, Air Conditioning, and Refrigeration
Hp— Horsepower
FLA— Full Load Amps
LRA— Locked Rotor Amps
MOCP — Maximum Overcurrent Protection (HACR breaker)
RLA— Rated Load Amps
*May be field converted to single-phase units, see electric heat installation instructions.
NOTE: Separate power source is required for all heaters. Control from base unit 50AH (24 v).
Denotes connection point between subbase and thermostat
Terminal (Marked)
Terminal (Unmarked)
Terminal Block
Field Splice
Splice (Marked)
Factory Splice
Factory Wiring
Accessory or Optional Wiring
Field Control Wiring
Field Power Wiring
To indicate common potential only not to represent wiring
12
Page 13
Typical piping and wiring
LEGEND
NEC — National Electrical Code
NOTES:
1. Wiring and piping shown are not intended for or to include all
details for specific installation.
2. All wiring must comply with applicable local and national codes.
3. All piping must follow standard refrigerant piping techniques. Refer
to Carrier System Design Manual, Part 3, for details.
4. For other installation details refer to Installation Instructions.
5. If unit sections are field split, 8 threaded support rods are required.
6. Ensure condenser air recirculation is minimized.
Application data
OUTDOOR-AIR TEMPERATURE OPERATING LIMITS (F)
UNIT 50AH024036048060
Without Head Pressure ControlMinimum35354040
With Head Pressure ControlMinimum0000
Field splitting instructions — If components are split,
maximum length of refrigerant tubing to be used is 50 ft,
assuming components are installed in same horizontal
plane. Condenser may be mounted up to 12 ft above evaporator. Liquid line tubing is
1
discharge line is
/2-in. OD copper tubing. For additional
piping information, refer to Carrier System Design Manual, Part 3. Units should always be within line of sight from
each other, or separate NEC (National Electrical Code)
Maximum126126126126
Maximum126126126126
3
/8-in. OD copper tubing, and
disconnects will be required. Junction boxes should be
installed in both the evaporator and condenser sections
adjacent to D-shaped grommets, to provide a location to
splice the outdoor-fan motor factory wiring (no. 16 AWG
[American Wire Gage],
ing should be a minimum of no. 16 AWG,
insulation. Check all applicable electrical codes to ensure
proper compliance.
4
/64-in. thick insulation). Field wir-
4
/64-in. thick
13
Page 14
Guide specifications
Indoor Packaged Unit
HVAC Guide Specifications — Section 15787
Size Range: 2 to 5 Tons, Nominal
Carrier Model Number: 50AH
Part 1 — General
1.01 SYSTEM DESCRIPTION
Indoor mounted, electrically controlled packaged
horizontal cooling unit utilizing a hermetic type
scroll compressor.
1.02 QUALITY ASSURANCE
A. Unit shall be certified in accordance with ARI
Standard 210.
B. Unit shall be UL listed and carry a UL label.
C. Unit shall be CSA approved (except 3 ton, 3-phase
units).
D. Unit shall be factory run-tested to ensure proper
performance prior to delivery.
1.03 DELIVERY, STORAGE, AND HANDLING
A. Unit shall be shipped completely assembled and
ready to operate.
B. Unit shall be shipped factory charged with refriger-
ant R-22.
C. Unit shall be stored and handled in accordance with
the unit manufacturer’s instructions.
Part 2 — Products
2.01 EQUIPMENT
A. General:
Factory assembled horizontal, single piece, air
cooled, indoor, ceiling plenum mounted electric
cooling unit. Contained within the unit enclosure
shall be all factory wiring, piping, controls, refrigerant charge (R-22), and special features required
prior to start-up.
B. Unit Cabinet:
1. Constructed of galvanized steel.
2. Interior shall be insulated with
prene coated fiberglass. Insulation shall be
bonded to interior surfaces by sprayed water
reduceable adhesive.
3. Equipped with 3 same side access panels and
2 bottom hanging removable doors to facilitate
ease of maintenance. Side panels allow access
to the control box, refrigeration components,
and condenser coil. Control box shall be hinged
allowing access to the compressor and pressure
switches. Bottom doors shall allow access to
and easy removal of the condenser and evaporator motors and blower assemblies.
4. Equipped with two
drain connections below the evaporator coil
and one
denser coil wash down. Connections shall be
factory plugged for field removal.
3
/4-in. threaded connection for con-
3
/4-in. threaded condensate
1
/2-in. thick neo-
5. Field splittable through the removal of 4 bolts
and extending refrigerant piping and wiring to
allow remote horizontal or vertical condenser
mounting.
6. Unit shall have an integral hanging bracket
requiring only 4 threaded rods (8 if unit is split)
run to the top flange of the unit for hanging,
eliminating need for external hanger brackets.
7. Contains junction box for power connection
and opening for routing of control wiring.
C. Fans:
1. Evaporator:
a. Blower shall be of the forward-curved, cen-
trifugal, direct-drive type or belt drive (4 and
5 tons only).
b. Motor shall have permanently lubricated
bearings.
c. Unit sizes 048, 060 shall be available with
an optional 1.5 hp fan motor.
2. Condenser:
a. Blower shall be of the forward-curved, cen-
trifugal, direct-driven type (024 only), or belt
drive (036,048,060).
b. Motor shall have permanently lubricated
bearings.
D. Compressor:
1. Fully hermetic scroll type.
2. Mounted on suitable spring vibration isolators.
3. Equipped with internal line break protection.
E. Coils:
Evaporator and condenser coils shall be of nonferrous construction with aluminum fins mechanically bonded to seamless copper tubes with all joints
brazed.
F. Refrigerant Components:
Refrigerant components shall include:
1. Capillary tube feed system.
2. Refrigerant filter-drier.
G. Filter Section:
Filter section shall consist of factory-installed, permanent, cleanable air filter, removable from the
same side as the access panels without the use of
tools.
H. Controls and Safeties:
Control system shall include a high-pressure switch,
a low-pressure switch, and a compressor lockout
feature which upon tripping of any safety device
shall prevent compressor from restarting until reset
at the thermostat (on all 3-phase units and 036
single-phase units only).
Time Guard® II device (single-phase only) shall prevent the compressor from restarting for a minimum
of 5 minutes after shutdown.
14
Page 15
I. Operating characteristics:
1. Unit shall operate using refrigerant R-22.
2. Unit shall be designed for indoor suspended
horizontal mounting and operation.
J. Electrical Requirements
Unit shall have single point power connection to
leads in terminal box.
K. Special Features:
Certain standard features are not applicable when
the features designated by * are specified. For assistance in amending the specifications, your local
Carrier Sales Office should be contacted.
* 1. Electric Heat Module:
a. Provides encased heater elements that shall
attach directly to the base unit discharge.
b. Shall have bottom access.
c. UL listed.
2. Thermostat Assembly:
Provides cooling and fan control. Standard sub-
base shall include ‘‘Compressor malfunction
light’’ designed to illuminate if compressor lockout is activated.
3. Time Guard® II Device Compressor Cycle
Delay:
Prevents compressor from restarting for a minimum of 5 minutes after shutdown.
*4.Condensate Pump:
Unit shall be equipped with remotely located
condensate pump. A field-installed light shall
illuminate when reservoir rises above a preset
level. Unit shall shut down upon reservoir light
illumination.
* 5. Head Pressure Control Package:
Allows unit to mechanically cool down to 0° F
ambient temperature. Package shall include
damper operating device and all necessary
hardware.
6. Vibration Isolation Package:
Shall provide 4 spring hangers for ceiling
mounted unit to damper vibration that may be
transmitted to building structure.
15
Page 16
Carrier Corporation • Syracuse, New York 132212049-02
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4
Ta b 2 b 7 a
Book 1
NewPg 16Catalog No. 525-00039Printed in U.S.A.PC 111Form 50AH-6PD
Ta b I P 1a
Replaces: 50AH-5PD
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.