Carrier 48KHA User Manual

0 (0)
48KHA,KLA
Packaged Heating/Cooling Units
Installation, Start-Up and Service Instructions
NOTE TO INSTALLER: After installation, leave these instructions, Owner’s Manual and Peurts Replace
ment Guide with equipment owner.

CONTENTS

Page

SAFETY CONSIDERATIONS

GENERAL..........................................................................1,2
INSTALLATION
Step 1—Rig and Place Unit..............................................2-4
.................................................................
1
2-8
• ROOFTOP INSTALLATION
• GROUND LEVEL INSTALLATION
• CLEARANCES
• CONDENSATE DISPOSAL
• VENTING
Step 2—Make Gas Piping Connections
Step 3—Make Duct Connections........................................6
Step 4—Make Wiring Connections
..........................
.................................
5,6 6,7
• HIGH-VOLTAGE CONNECTIONS
• SPECIAL PROCEDURES FOR 208-V OPERATION
• LOW-VOLTAGE CONNECTIONS
• HEAT ANTICIPATOR SETTING
START-UP........................................................................9-16
SERVICE........................................................................16-19
TROUBLESHOOTING CHARTS
SAFETY CONSIDERATIONS
...................................
20,21

A WARNING

Improper installation, adjustment, eJteration, service, maintenance or use can cause carbon monoxide poison ing, explosion, fire, electric shock or other occurrences which may injure you or damage your property. Con sult a qualified instedler, service agency or the gas sup
plier for information or assistance.
NOTE: Installation of this unit must conform to the guide
lines presented in these Installation Instructions. Read and become familiar with this publication before starting installation.
Only trained, qualified installers and service mechanics should install, start-up and service this equipment. Consult the User’s Manual for routine maintenance. All other opera tions should be performed by tredned service personnel,
personnel.
• Follow all safety codes.
• Wear safety glasses and work gloves.
• Use care in handling, rigging and setting bulky equip ment.
• Observe precautions in these instructions and on equip ment tags, stickers and labels.
* •

A WARNING

Do not disconnect electric power to this appliance with out first turning off gas supply. Be sure power to equip ment is shut off before meuntenance or service.
Fig. 1—Model 48KHA,KLA
GENERAL
Models 48KHA,KLA packaged gas/electric units (Fig. 1) eire design certified in accordance with ANSI Z21.47B-1986, ARI Standeird 210-81 and ARI Stemdard 270-84. The units are design certified by the American Gas Association (AGA) for use with natural or propane gases with appropri ate controls or orifices. See Table 1 for heating input rat ings. Models 48KHA,KLA units are fully self-contedned, combination gas-heating/electric-cooling units designed for outdoor installation on either a rooftop or ground-level slab. May be instedled directly on wood flooring or on Class A, Class B or Class C roof covering materials.
These units are equipped with an energy-saving automatic, intermittent, electric spark ignition system that does not have a continuously burning pilot. All units are manufac tured with natural gas controls.
Units with number 1 in the 4th digit location of model num ber in Table 1 meet California oxides of nitrogen (NOx) max imum emission requirements.
Units are factory charged with R-22 refrigerant. To install: connect gas supply, air ducts, high- and low-voltage wiring and condensate drain, and install a field-supplied air filter in the return-air ductwork.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obiigations.
BookI 1 I 4 PC 101 Cataiog No 534-862 Printed in USA Form 48KH,KL-19Si Pg 1 1-88 Replaces: 48KH,KL-17SI Tab ila 11a For replacement items contact distributor.
Table 1—Performance Data
COOLING
MODEL 48-
KLA118310BE KLA124310BE
KHA024310BF KLA130310BE
KHA030310BF KLA136310BE
KLA136510CE KLA136610CE KHA136310BE KHA136S10CE KHA036310BF
KHA036510CF KLA142310BE
KLA142510CE KHA042310BF KHA042510CF
KLA148310BE KLA148510CE KLA148610CE KHA048310BE KHA048510CF
KLA160310BE KHA060310BF
♦Rated in accordance with U S. Government D.O.E. test procedures and/
or ARI Standard 210-81.
tSound rating per ARi 270-84. tThe capacity ratings of singie-phase units are in accordance with U.S.
Government D.O.E. test procedures and/or AGA certification require ments. For 3-phase units, the efficiency rating is a product thermai effi ciency rating determined under continuous operating conditions, inde pendent of any installed system.
CAPACITY
(Btuh)*
17,800 40,000 32,000 23,800 40,000
24,000 75,000 29,600
29,600 75,000 58,000 36,000 60,000
36,000 36,000 60,000 36,000 36,000 36,000 36,000
42,000 60,000 42,000 60,000 42,000 42,000 125,000
49,000 49,000 49,000 49,000
49,000 60,000
60,000
RATED
HEATING
INPUT (Btuh)
40,000 32,000
60,000
100,000 79,000 100,000 75,000 125,000 125,000
125,000 97,000
80,000 63,000 80,000 60,000
80,000 60,000 125,000 97,000 125,000 93,750 8.4*
100,000* 79,000* 8.4* 150,000* 116,000* 8.4*
OUTPUT
CAPACITY
(Btuh)
32,000 58,000
47,000 45,000 45,000
97,000 93,750
47,000 45,000
93,750
ARI* SOUND RATING
(Bels)
7.8
7.8
8.0
7.8
7.8
8.0
8.0
8.0
8.0
8.0
8.0
8.0 78
7.8
7.8
7.8
8.4*
8.4*
8.4*
8.4*
SPREADER OARS' ^
(2)2x4xUNIT LENGTH PLUS 10"WITH
11 DEEP 90° NOTCHES EACH END
(2) 2x4xUNIT WIDTH WITH l^
DEEP 90° NOTCHES
EACH END
LOCATE CHAINS THROUGH HOLES IN BASE
CHANNELS
Fig. 2—48KHA,KLA Suggested Rigging
INSTALLATiON
Step 1—Rig and Place Unit

A CAUTION

SPREADER BARS
TWO OR THREE BASE CHANNELS ATTACHED TO BOTTOM OF UNIT
CHAIN
All units can be connected into existing duct systems that are properly sized and designed to handle an airflow of 350
to 450 cfm per each 12,000 Btuh of rated cooling capacity.
See Table 8 for cooling euid heating airflow requirements.
NOTE: When insteJling any accessory item, see Installation
Instructions packaged with accessory.
IMPORTANT-
READ BEFORE INSTALLING
1. This instEdlation must conform with all applicable local and nationed codes.
2. Power supply (volts, hertz and phase) must corre spond to that specified on unit rating plate.
3. Electrical supply provided by utility must be suffi cient to handle load imposed by unit.
4. Refer to Fig. 4 for locations of gas inlet, electrical inlets, condensate drain, duct connections, and required clearances before setting unit in place.
5. Locate unit where vent cap will be a minimum of 4 ft from openable windows or doors.
6. Installation must conform with local building codes and with National Fuel Gas Code, NFPA 54-1984/ ANSI Z223.1-1984.
IMPORTANT: On some models, the high-voltage igni tion cable is not connected to the spark generator termi nal on the control head/gas valve assembly when shipped from the factory. The cable is fastened to the manifold on these models. Push the boot toward center of the cable to expose the connector on the end of the cable. Attach the connector securely to the terminal on the end of the con trol head/gas vedve assembly. Push the boot over connec tor to insulate the high-voltage connection.
When rigging unit to be hfted, use spreader bars to pro tect top and sides. Rig unit as shown in Fig. 2. Use extreme caution to prevent damage when moving unit. Unit must remain in upright position during all rigging and moving operations. Unit must be level for proper condensate drainage; therefore, the ground-level pad or accessory roof-mounting curb must be level before set
ting unit in place. When a field-fabricated support is used, ensure that support is level and properly supports unit and plenum.
ROOFTOP INSTALLATION

A CAUTION

When installing a unit on a rooftop, be sure roof will
support the additioneil weight. Refer to Fig. 4 to obtain
total weight and corner weight information.
When installing a Model 48KHA,KLA end discharge unit with a field-supplied downflow plenum, a field-supplied roof mounting curb must be installed on emd flashed into roof before unit installation. When installing a Model 48KHA,KLA end discharge unit without a downflow ple num, place unit on a level base that provides proper sup port. On flat roofs be sure unit is located at least 4 in. above highest expected water level on roof to prevent flooding. Consult local codes for additional installation requirements.
GROUND LEVEL INSTALLATION-Place unit on a solid, level concrete pad that is a minimum of 4 in. thick and that extends approximately 2 in. beyond casing on all sides of unit. Do not secure unit to pad except when required by local codes.
CLEARANCES—Required minimum operating and service clearances are shown in Fig. 4 for providing adequate com bustion, ventilation emd condenser edr.

A CAUTION

Do not restrict condenser airflow. An air restriction at either outdoor-edr inlet (the entire surface of the outdoor coil) or fan discharge can be detrimental to compressor life.
Condenser fan discharges through top of unit. Ensure that fan discharge does not recirculate to condenser coil. Do not locate unit in either a corner or under a complete overhead obstruction. Minimum clearance under a partial overhang (such as a typical house roof overhang) is 3 ft above vent cap. Maximum horizontal extension of a partial overhang must not exceed 4 feet.
Do not locate unit where water, falling ice or snow from an
overhang or roof will damage or flood the unit. Do not locate
unit where grass, shrubs, or other plants will interfere with
the airflow either into or out of unit. Do not install unit on carpeting, tile or other combustible material other than wood flooring.
CONDENSATE DISPOSAL
NOTE: Be sure condensate water disposed methods comply
with local codes, restrictions and practices. Models 48KHA,KLA dispose of condensate water through
a %-in. MPT drain fitting. See Fig. 4 for location.
Install a 3-in. trap at the drain fitting to ensure proper drainage. See Fig. 3. Make sure trap outlet is at least 2 in. lower than unit dredn pan connection to prevent pan from overflowing. Prime trap with water.
TO DRAIN
Fig. 3—Condensate Trap
If installation requires draining the condensate water away from unit, connect a dredn tube using a minimum of 7s-in. OD copper tubing, %-in. galvanized pipe or 7s-in. plastic pipe. Do not undersize the tube. Pitch drain tube downward at a slope at least one in. for every 10 ft of horizontal run. Be sure to check drain tube for leaks.
Condensate water can be drained directly onto roof in roof
top installations (where permitted) or onto a gravel apron in ground level installations. When using a gravel apron, make
sure it slopes away from the unit.
VENTING—The vent cap, combustion air shroud and flue
assembly are shipped in either the blower or control com
partment. Vent screen is taped to blower housing. Remove
access doors to locate assemblies. See Fig. 4 for door
locations.
A CAUTION
Venting system is designed to ensure proper venting. Vent cap assembly must be installed as indicated below.
NOTE: Screw holes in flue assembly and unit top eire posi
tioned to ensure proper orientation when installed. Refer to
Fig. 5 emd instedl vent cap as follows:
1. Place combustion air shroud over combustion air open ing in unit top, and line up screw holes in shroud with holes in top. Secure shroud to top, using screws with
rubber washers (provided).
2. The flue gasket is shipped in the literature assembly envelope. Place gasket and flue assembly through hole in combustion air shroud, orient screw holes in base of flue assembly with holes in unit top, and secure gasket
and flue assembly to unit top, using screws provided.
3. Form flat wire screen (provided) into circular shape around protruding lip of combustion-air shroud and bend wire ends through holes of screen mesh to secure screen in place. Make sure that no sharp edges are left exposed.
4. Place vent cap sleeve inside flue assembly. Orient spring chp of vent cap with slot in assembly. Be sure clip snaps into slot to secure clip onto assembly.
i MPT / U-—G
DRAIN CONN
PLUGGED ACCESS HOLE FOR REFRIGERANT PRESSURE GAGE HOSES
*NOTON MODELS48KLAII8THROUGH
I36i KHA024 THROUGH 030
CONTROL ACCESS DOOR
BLOWER ACCESS DOOR
I LOW VOLTAGE
INLET
K HIGH VOLTAGE INLET
T-4Í
C> EVAPORATION AIRFLOW ^CONDENSER AIRFLOW
VENT CAP COMBUSTION AIR INLET BOX
■NOT ON MODELS 48KLAII8 THROUGH 136; KHA024 THROUGH 030
MODEL 48-
Dimensions
(ft-in.)
A B C D E F G H J K
L M N
MODEL
48-
KLA118 82 KLA124 KHA024 KLA130 KHA030 97 KLA136 KHA136 122 KHA036 KLA142 KHA042 KLA148 130 135 137 KHA048 134 139 144 KLA160 KHA060
KLA118 KLA124
4-5% 4-5% 5-5% 2-6% 3-4% 3-8%
3-2'/a
1-4 1-7 2-0 1-4 1-4
0-7'/4
0-11% 0-10% 0-10%
1-3’A
0-1 %2 0-1% 0-1% 0-1%
0-1%
0-47,6
1-10 2-4 2-4
CORNER WT (ib)
A B
83 81 96 94 97 93
98 97 92
122 120 116 117 475 485 108 105 102 113 111 107
148 144 139 155 151
C D
79
93 91 94 375 385
120 116 117
148 151 605
KHA024
KLA130
KHA030
KLA136
3-57s 3-107e
0-8?8 1-374 1-874
0-17e 0-67,6
79 81 320 330
82
79 91 94 375 385 90 92 372 382
93 380
105 420 109 440 133 535 138 555 144 575
KHA136 KHA036 KLA142 KHA042
1-174 0-8%
1-1 O'732
1-4
0-87,6 0-87,6
TOTAL
OPERATiNG
WT (ib)
325 335
475
KLA148 KHA048 KLA160 KHA060
6-0% 3-8% 4-6%
2-8
1-174 0-8%
0-11%
1-8%
2-0=»/32
1-5
2-4
TOTAL
SHiPPING
WT (ib)
390 485
430 450 545 565 585 615
Above flue vent........................................................................................................3-0
Duct side of unit .....................................................................................................0-6
Side opposite ducts................................................................................................2-6
Biower access panel side. Side opposite biower access panel.
Bottom of unit.................................................
NOTE: Provision must be made for fresh ambient air to reach the
outdoor coil without recirculation of the air from the outdoor fan discharge

Weight Data

VIEW AA
CLEARANCES (ft-in.)
2-6 2-6
0

Fig. 4—Dimensions and Ciearances (ft-in.)

Fig. 5—Vent Cap Assembly
COMBUSTION-AIR SHROUD
CONTROL TRANSFORMER
COMPRESSOR CONTACTOR
GAS INLET PRESSURE TAP (BACK SIDE)
‘GAS PIPE
ENTRANCE HOLE
REGULATOR
LOW VOLTAGE SECONDARY p. pf'TpoNIC \
WIRES air SHIELD ^^)n7rOL GAS VALVE
HEAD
ADJUSTING SCREW
Fig. 6—Model 48KLA136—Side View
(Partiai) with Access Doors Removed
2. Protect all segments of piping system against physiceJ and thermal deimage. Support all piping with appropri ate hangers, etc. Use a minimum of one hanger in every 6 feet. For pipe sizes larger them V2-in., follow recom mendations of national codes.
Apply joint compound (pipe dope) speiringly and only
3. to male threads of joint when meiking pipe connections. Use only pipe dope that is resistant to action of lique fied petroleum gases as specified by local and/or nationeJ codes. Never use pipe thread tape.
InsteJl a sediment trap in riser leading to the heating
4. section. See Fig. 7. This drip leg functions as a trap for dirt and condensate. Install trap where condensate can not freeze. Install this sediment trap by connecting a piping tee to riser leading to heating section, so that straight-through section of tee is vertical. Then, con nect capped nipple into lower end of tee. Extend capped nipple below level of gas controls.
Step 2—Make Gas Piping Connections—A manual shutoff
vedve is shipped loose in the burner compartment or blower compartment. Connect one end of a field-supplied V2-in. streught nipple to the gas valve inlet. Connect the other end of the nipple to the manual shutoff valve as shown in Pig. 6. The gas supply pipe enters unit through access hole pro vided. See Fig. 4 for location. The gas connection to unit is made to the V2-in. FPT gas inlet on manual shutoff. See Fig. 6 for inlet location.
Install a separate gas supply line that runs directly from meter to heating section. Do not use cast-iron pipe. Check local utility for recommendations concerning existing lines. Choose a supply pipe that is large enough to keep pressure loss as low as practical. Never use pipe smaller than the ^¡¿-in.
FPT gas inlet on unit manual shutoff.
When installing gas supply line, observe local codes pertain ing to gas pipe installations. Refer to National Fuel Gas Code, NFPA 54-1984/ANSI Z223.1-1984 in absence of local building codes. Adhere to following pertinent recom mendations:
1. Avoid low spots in long runs of pipe. Grade all pipe %- in. in every 15 ft to prevent traps. Grade all horizonteJ runs downward to risers. Use risers to connect to heat ing section and to meter.
Fig. 7—Sediment Trap
5. Install an accessible, external, manual shutoff valve in gas supply pipe within 6 ft of heating section.
NOTE: The unit manual shutoff valve has a Vs-in. tap
ping on the inlet side of this shutoff for measuring gas input pressure.
6. Install ground-joint union close to heating section between unit manual shutoff and external manual main shutoff valve.
7. Pressure-test all gas piping in accordance with loceil and national plumbing and gas codes before connecting
piping to unit.
NOTE: When pressure-testing the gas supply system
after the gas supply piping has been connected to the unit gas valve, the supply piping must be disconnected from the gas valve during any pressure testing of the piping systems at test pressures in excess of 0.5 in. psig. When pressure testing the gas supply piping sys tem at test pressures equal to or less than 0.5 in. psig, the unit heating section must be isolated from the gas piping system by closing the external main manual shutoff valve and slightly opening ground-joint union.

A CAUTION

Unstable operation may occur, peirticularly under high­wind conditions, when gas valve and manifold assembly are forced out of position while connecting improperly routed, rigid gas piping to gas valve. Use a backup wrench when making connection to avoid strain on, or distortion of, gas control piping.
2. Use a flexible transition between rigid ductwork and unit to prevent transmissions of vibration. The transi tion may be screwed or bolted to duct flanges. Use suit able gaskets to ensure a weathertight and air-tight
seal.
3. Install external, field-supplied air filter(s) in return-air ductwork where it is easily accessible for service. Rec ommended filter sizes are shown in Table 2.
4. Size all ductwork for maximum required airflow (either heating or cooling) for unit being installed. Avoid abrupt duct size increases or decreases.
5. Adequately insulate and weatherproof all ductwork located outdoors. Insulate ducts passing through an unconditioned space, and use a vapor barrier in accord ance with the latest issue of SMACNA and NE SC A minimum installation standards for heating and air conditioning systems. Secure all ducts to building structure.
6. Flash, weatherproof and vibration-isolate all openings in building structure in accordance with local codes and good building practices.
8. Where permitted by local codes, use an approved corru gated metal tubing gas connector between rigid gas
piping and unit manual shutoff.

A WARNING

Never use a match or other open flame when checking for leaks. Failure to adhere to this warning may cause an explosion.
9. Check for gas leeiks at eJl field-installed and factory­installed gas lines after all piping connections have been completed. Use soap-and-water solution (or method specified by local codes and/or regulations).
Step 3—Make Duct Connections—Model 48KHA,KLA
has duct flanges on the supply- and return-air openings on side of unit. See Fig. 4 for connection sizes and locations.

A WARNING

The design and installation of duct system must be in
accordance with standards of National Fire Protection Association for installation of non-residence type air conditioning and ventilating systems. NFPA No. 90; or residence-type NFPA No. 90B; and/or local codes and ordinances.
Table 2—Filter Sizes (Field Supplied),
(Sq In.)*
MODEL 48-
KLA118310BE KHA024310BF KLA124310BE
KHA030310BF
KLA130310BE KHA036310BF
KHA136510CE KHA036510CF KHA136310BE KLA136510CE
KLA136610CE KLA136310BE
KHA042310BF 694 KHA042510CF 694 KLA142510CE KLA142310BE 672
KHA048310BF 768 KHA048510CF 768 KLA148510CE 768 KLA148610CE KLA148310BE
KHA060310BF 960 KLA160310BE 960
*Required air filter areas shown are based on the ARI-rated cooling air
flow or the heating airflow at a velocity of 300 fpm depending on whichever value is larger. Air filter pressure drop should not exceed 0 08
, in wg
STANDARD CLEANABLEOR
DISPOSABLE HIGH CAPACITY
TYPE
302 202 454 384 257
480 320 480 320
694 576 694 576 576 576 384 576 384
672
768 512 768 512
TYPE
303
462 384 462 384 384
462 462 448 448
512 512 512
640 640

Step 4—Make Wiring Connections

Adhere to the following requirements when selecting, sizing tmd installing duct system;
1. Select and size ductwork, supply-air registers and return-£ur grilles according to ASHRAE recommenda tions emd as presented in Carrier System Design Man ual, Part 2.

A CAUTION

When duct system fastening holes are drilled into side
of Model 48KHA,KLA instead of the unit duct flanges,
use extreme care to avoid puncturing coil or coil tubes.

A WARNING

Unit cabinet must have an uninterrupted, unbroken electrical ground to minimize the possibility of personeil injury if an electrical fault should occur. This ground may consist of electrical wire connected to unit ground lug in control compartment, or conduit approved for electrical ground when installed in accordance with National Electrical Code ANSI/NFPA 70-1984 and local electriced codes. Do not use gas piping as an elec
trical ground. Failure to follow this warning could result in the installer being held liable for personal injury of others.
A CAUTION
Feiilure to follow these precautions could result in dam age to unit being installed.
1. Make all electrical connections in accordance with National Electrical Code ANSI/NFPA 70-1984 and local electrical codes governing such wiring.
2. Use only copper conductor for connections between the field-supplied electrical disconnect switch and the unit.
Do not use aluminum or copper-clad aluminum wire.
3. Ensure that high-voltage power to unit is within oper ating voltage range indicated on unit rating plate. On 3-phase units, ensure that phases are balanced within 2%. Consult local power company for correction of improper voltage and/or phase balance.
4. When low-voltage control wires are run in same conduit as high-voltage wires, insulate low-voltage wires for highest voltage contained within conduit.
5. Do not damage internal components when drilling through any panel to mount electrical hardware, con duit, etc.
HIGH-VOLTAGE CONNECTIONS-Unit must have a sepeirate electriceil service with a field-supplied, waterproof, fused disconnect switch per NEC mounted near, and within
sight from, the unit. Refer to unit rating plate for maximum fuse size and minimum circuit amps (ampacity) for wire siz ing. Table 3 shows recommended wire sizes and lengths based on rating plate data.
The field-supplied disconnect switch box may be mounted
on unit over the high-voltage inlet hole in control corner pemel. See Fig. 4.

A WARNING

Label Part No. A74191B, which is shipped loose in bag of parts, must be affixed to the disconnect switch box. This label states: "DO NOT DISCONNECT THE ELECTRICAL POWER TO THIS APPLIANCE WITHOUT FIRST TURNING OFF THE GAS SUPPLY.”
Proceed as follows to complete the high-voltage connections
to unit:
1. Connect ground lead to chassis ground connection when using a separate ground wire.
2. Run high-voltage leads into unit control box and con nect to contactor. See unit wiring label and Fig. 6 and 8.
NOTE; On 3-phase units, connect third high-voltage lead to
brown high-voltage pigtail lead. See unit wiring label and Fig. 8.
SPECIAL PROCEDURES FOR 208-V OPERATION
A WARNING
Make sure power supply to unit is switched OFF before making any wiring changes. Electrical power may cause personal injury or death.
For operation on 208 volts, disconnect orange transformer primary lead from contactor. See unit wiring label and Fig. 6. Remove tape emd cover from terminal on end of red transformer-primary lead. Save cover. Connect red lead to contactor terminal from which orange lead was dis connected.
Using cover removed from red lead, insulate loose terminal on orange lead. Wrap cover with electricEd tape so that metal terminal cannot be seen.
NOTE: For some 48KHA,KLA units, the factory-wired
blower-motor speed connections may require changing for 208-v operation to ensure adequate airflow at the rated external static pressure. See unit wiring label. Insulate all unused motor leads following same procedures described for tremsformer leads.
LOW-VOLTAGE CONNECTIONS-Use a suitable room thermostat as specified on unit wiring label.
Locate room thermostat on an inside wall in space to be con ditioned where it will not be subjected to either a cooling or heating source, or direct exposure to sunlight. Mount ther
mostat 4 to 5 ft above floor.
Use no. 18 AWG color-coded, insulated (35 C minimum)
v/ires to make low-voltage connections between thermostat
and unit. If thermostat is located more than 100 ft from unit (as measured along the low-voltage wires), use no. 16
AWG color-coded, insulated (35 C minimum) wires.
A grommeted, low-voltage inlet hole is located in the panel
adjacent to control access panel. See Fig. 4. Run low-voltage
leads from thermostat, through inlet hole and to low-voltage
flagged pigtail leads that run through a hole in bottom of
unit control box. See Fig. 6. Connect thermostat leads to
pigtail leads as shown in Fig. 8
HEAT ANTICIPATOR SETTING—Room thermostat heat
anticipator must be properly adjusted to ensure proper heating performance. Set heat anticipator, using ammeter to determine exact required setting.
NOTE: For thermostat selection purposes, use 1.0 amps for
approximate required setting.
Failure to make a proper heat anticipator adjustment will
result in improper operation, discomfort to occupants of
conditioned space and inefficient energy use; however,
required setting may be changed slightly to provide a
greater degree of comfort for a particular installation.
Loading...
+ 15 hidden pages